Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:49:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 16079.90 | 1417.32 | 1417.32 |
Net Site Energy | 16079.90 | 1417.32 | 1417.32 |
Total Source Energy | 34911.35 | 3077.17 | 3077.17 |
Net Source Energy | 34911.35 | 3077.17 | 3077.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3615.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1412.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1395.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 245.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.31 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1011.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1796.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 200.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 414.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.80 | 2283.22 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 73.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8392.10 | 7687.80 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 3615.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1412.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1395.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 245.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 33.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1796.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 200.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 414.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.80 | 2283.22 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 308.56 | 519.95 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 286.46 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.70 | 677.62 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 308.56 | 519.95 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 286.46 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.70 | 677.62 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8392.098 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8392.098 | 100.00 |
Total On-Site and Utility Electric Sources | 8392.098 | 100.00 |
Total Electricity End Uses | 8392.098 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 910.19 | 10.75 |
Air to Air Heat Recovery for Heating | 7558.50 | 89.25 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 8468.69 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 750.67 |
Time Setpoint Not Met During Occupied Cooling | 132.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6837.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| Environment |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.1931 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 15.2897 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 15.2897 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 15.2897 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.1545 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.1159 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 13.2510 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 11.2124 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 11.8403 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 11.8403 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 5.0966 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 11.8403 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 11.8403 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 11.8403 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 13.2510 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 13.2510 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 12.2317 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 5.0966 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 10.4431 | 7.60 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 10.4431 | 7.60 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-18:10 | 02-FEB-20:49 | - | - | - | 05-JAN-21:30 |
Heating | 0.00 | 951908.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 291127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 98435.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 51433.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69481.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13070.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 17225.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4660.95 | 177731.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2892.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 627943.55 | 1219350.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 951908.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 291127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 98435.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1573.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 971.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 69481.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 13070.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 17225.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4660.95 | 177731.68 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1164.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1085.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3919.45 | 0.00 | 0.00 | 0.00 |
Cooling | 4473.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4419.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 778.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.39 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3202.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5689.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 636.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1312.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.58 | 2475.01 | 0.00 | 0.00 | 0.00 |
Refrigeration | 231.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 26577.77 | 8333.57 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 345.47 | 0.00 | 0.00 | 0.00 |
Cooling | 394.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 389.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 282.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 501.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 115.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.35 | 218.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2342.63 | 734.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 345.47 | 0.00 | 0.00 | 0.00 |
Cooling | 394.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 389.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 282.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 501.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 115.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.35 | 218.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2342.63 | 734.54 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.73 | 0.551901 | 0.978000 | 2.67 | 1.00 | 0.500000 | 0.000690 | 0.000340 | 2.67 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.336778 | 0.151757 | 0.978000 | 0.329369 | 0.978000 | 0.500000 | 0.002511 | 0.000132 | 0.329369 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.249468 | 0.237239 | 0.978000 | 0.243980 | 0.978000 | 0.500000 | 0.001606 | 0.000052 | 0.243980 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.282730 | 0.442659 | 0.978000 | 0.276510 | 1.00 | 0.500000 | 0.000861 | 0.000074 | 0.276510 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.116840 | 0.617997 | 0.978000 | 0.114269 | 1.00 | 0.500000 | 0.000617 | 0.000043 | 0.114269 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.42 | 0.069065 | 0.978000 | 3.34 | 0.978000 | 0.500000 | 0.021891 | 0.000429 | 3.34 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.46 | 0.098618 | 0.978000 | 1.43 | 0.978000 | 0.500000 | 0.003863 | 0.000407 | 1.43 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.89 | 0.203984 | 0.978000 | 4.78 | 0.978000 | 0.500000 | 0.001868 | 0.001041 | 4.78 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.978000 | 1.16 | 1.00 | 0.500000 | 0.000381 | 0.000386 | 1.16 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.28 | 0.110613 | 0.978000 | 2.23 | 0.978000 | 0.500000 | 0.003444 | 0.000422 | 2.23 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.40 | 0.105197 | 0.978000 | 2.35 | 0.978000 | 0.500000 | 0.003622 | 0.000438 | 2.35 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.40 | 0.785153 | 0.978000 | 2.35 | 0.978000 | 0.500000 | 0.011637 | 0.000317 | 2.35 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.568025 | 0.552861 | 0.978000 | 0.555528 | 1.00 | 0.500000 | 0.000689 | 0.000244 | 0.555528 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 15388.81 | 0.000340 | 274.52 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5968.80 | 0.000132 | 119.87 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2353.28 | 0.000052 | 43.91 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3332.65 | 0.000074 | 64.01 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1931.16 | 0.000043 | 38.45 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19412.66 | 0.000429 | 346.50 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 18432.14 | 0.000407 | 357.63 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 47114.40 | 0.001041 | 881.19 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 7834.28 | 0.000173 | 178.36 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 7855.97 | 0.000174 | 178.85 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 44155.96 | 0.000976 | 1005.28 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 44542.91 | 0.000984 | 1014.09 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 7795.99 | 0.000172 | 177.49 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 7817.58 | 0.000173 | 177.98 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17453.99 | 0.000386 | 343.14 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 2397.78 | 0.000053 | 54.59 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 2410.10 | 0.000053 | 54.87 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 11445.74 | 0.000253 | 260.57 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 19096.23 | 0.000422 | 351.71 |
DINING_FLR_6 VAV BOX REHEAT COIL | 19814.58 | 0.000438 | 364.46 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 14353.06 | 0.000317 | 257.04 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11054.96 | 0.000244 | 225.02 |
VAV WITH REHEAT_HEATC | 324346.27 | 0.007166 | 4129.81 |
FLR_3_DOAS_HEATC | 30467.96 | 0.000673 | 387.94 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.21 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.20 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 6.66 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 6.76 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.09 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.09 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.317748 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.312814 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.25 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.21 | 0.000173 | 0.000519 |
ROOM_2_FLR_3 FAN COIL | 1.20 | 0.000174 | 0.000511 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.66 | 0.000976 | 0.002801 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.76 | 0.000984 | 0.002991 |
ROOM_5_FLR_3 FAN COIL | 1.09 | 0.000172 | 0.000470 |
ROOM_6_FLR_3 FAN COIL | 1.09 | 0.000173 | 0.000467 |
ROOM_1_FLR_6 FAN COIL | 0.317748 | 0.000053 | 0.000136 |
ROOM_2_FLR_6 FAN COIL | 0.312814 | 0.000053 | 0.000133 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.25 | 0.000253 | 0.000545 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.21 |
ROOM_2_FLR_3 FAN COILFAN | 1.20 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 6.66 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 6.76 |
ROOM_5_FLR_3 FAN COILFAN | 1.09 |
ROOM_6_FLR_3 FAN COILFAN | 1.09 |
ROOM_1_FLR_6 FAN COILFAN | 0.317748 |
ROOM_2_FLR_6 FAN COILFAN | 0.312814 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.25 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000519 | 1.21 | 0.008681 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000511 | 1.20 | 0.008683 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002801 | 6.66 | 0.008615 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002991 | 6.76 | 0.008828 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000470 | 1.09 | 0.008703 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000467 | 1.09 | 0.008705 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000136 | 0.317748 | 0.008673 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000133 | 0.312814 | 0.008676 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000545 | 1.25 | 0.008770 | 22.55 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.034260 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 959177.97 | 21.84 | |
FLR_3_DOAS_COOLC | 0.003132 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 87700.73 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 21.84 | 21.84 | 22.33 | 21.84 | 21.84 | 21.84 | 0.300000 | 1.00 | 21.84 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.84 | 21.83 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 21.83 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 21.84 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.034260 | 0.000014 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.007166 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003132 | 0.000152 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000673 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.045964 | 11008.85 |
HEATSYS1 PUMP | 0.015174 | 3876.64 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.015174 | 1.82 |
COOLSYS1 | 0.045964 | 5.52 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.045964 | 3669.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 686777.26 | 686777.26 | 0.015174 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.045964 | 1286878.33 | 1287488.95 | 146.77 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.193 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.573 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 15.290 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.050 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 15.290 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.050 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 15.290 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.670 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 8.154 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.844 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.116 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.646 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 13.251 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.631 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 11.212 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.282 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 5.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.097 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 13.251 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 81.071 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 13.251 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 81.071 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.232 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.648 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 5.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 20170.425 | 10.193 | 189.395 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20170.425 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1025.498 | 15.290 | 94.699 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1025.498 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1187.531 | 15.290 | 94.699 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1187.531 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 2511.222 | 15.290 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2511.222 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 772.713 | 8.154 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 772.713 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 477.279 | 6.116 | 56.819 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 477.279 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2502.616 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2502.616 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 14667.927 | 11.212 | 34.722 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14667.927 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 290.370 | 11.840 | 193.580 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.370 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 290.449 | 11.840 | 193.633 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.449 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 1984.622 | 5.097 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.622 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 290.449 | 11.840 | 193.633 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.449 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 4394.805 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4394.805 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 4394.805 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4394.805 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1263.592 | 12.232 | 56.821 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1263.592 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2100.415 | 5.097 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2100.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4744 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.941 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.31219756E-14 | -0.25237900E-15 | -0.17078023E-09 | -0.40080417E-16 |
25 | 8 | 0.24827770E-07 | 0.64895754E-13 | 0.40814970E-03 | -0.28230026E-09 |
26 | 7 | -0.13145170E-01 | 0.32788080E-08 | -0.24386180E-01 | 0.14946539E-03 |
27 | 6 | 0.42990022 | 0.11289000E-05 | 0.49294528 | -0.50371474E-02 |
28 | 5 | -5.4301032 | 0.41776872E-04 | -4.6011904 | 0.66154067E-01 |
29 | 4 | 34.062169 | 0.33899226E-03 | 22.064921 | -0.43618800 |
30 | 3 | -113.47938 | 0.73347792E-03 | -56.858567 | 1.5477483 |
31 | 2 | 199.36357 | 0.40991987E-03 | 79.008039 | -2.9361691 |
32 | 1 | -171.98885 | 0.43498902E-04 | -55.585984 | 2.7600347 |
33 | 0 | 57.057407 | 0.24596459E-06 | 15.505383 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 31 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
2 | RESWINDOW_U_0.37_SHGC_0.4 | 32 | 1 | VerySmooth | 2.102 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.55893E-002 | 0.31435 | 0.48047 | 0.48047 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11739 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35866.37724 | 35866.37724 | 2.73214 | 2.73214 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 26.28867 | 1.53444E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 1932.73462 | 1932.73462 | 8.68539E-002 | 0.85413 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4420.06936 | 4420.06936 | 0.33678 | 0.33678 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4313.13764 | 4313.13764 | 0.19380 | 0.19380 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3274.46033 | 3274.46033 | 0.24947 | 0.24947 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53444E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1126.19416 | 1126.19416 | 5.06073E-002 | 9.16993E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3711.94601 | 3711.94601 | 0.28273 | 0.28273 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53444E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1942.37709 | 1942.37709 | 8.72835E-002 | 8.72835E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1533.96997 | 1533.96997 | 0.11684 | 0.11684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53444E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1356.62873 | 1356.62873 | 6.09616E-002 | 6.09616E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44850.47367 | 44850.47367 | 3.41669 | 3.41669 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53444E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2614.19318 | 2614.19318 | 0.11747 | 0.23597 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19137.11958 | 19137.11958 | 1.45930 | 1.45930 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11257.38220 | 11257.38220 | 0.50582 | 0.67613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64124.70068 | 64124.70068 | 4.88684 | 4.88684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23082.68915 | 23082.68915 | 1.03724 | 1.89326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11830.99057 | 11830.99057 | 1.21450 | 1.21450 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7834.58251 | 7834.58251 | 0.35411 | 0.35411 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11652.19708 | 11652.19708 | 1.19615 | 1.19615 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7856.26659 | 7856.26659 | 0.35509 | 0.35509 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 64903.37785 | 64903.37785 | 6.66203 | 6.66203 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 44156.78327 | 44156.78327 | 1.99590 | 1.99590 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 65824.16751 | 65824.16751 | 6.75706 | 6.75706 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 44543.74585 | 44543.74585 | 2.01339 | 2.01339 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10653.42294 | 10653.42294 | 1.09362 | 1.09362 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7796.28827 | 7796.28827 | 0.35238 | 0.35238 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10594.69388 | 10594.69388 | 1.08759 | 1.08759 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7817.87746 | 7817.87746 | 0.35335 | 0.35335 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 10870.90528 | 10870.90528 | 0.82800 | 1.18691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11613.16708 | 11613.16708 | 0.52187 | 0.52187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3095.32122 | 3095.32122 | 0.31775 | 0.31775 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2397.87047 | 2397.87047 | 0.10838 | 0.10838 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3047.25943 | 3047.25943 | 0.31281 | 0.31281 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2410.18608 | 2410.18608 | 0.10894 | 0.10894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12156.10643 | 12156.10643 | 1.24789 | 1.24789 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11446.07278 | 11446.07278 | 0.51735 | 0.51735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29955.76140 | 29955.76140 | 2.28475 | 2.28475 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7850.91485 | 7850.91485 | 0.35280 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31498.57631 | 31498.57631 | 2.40238 | 2.40238 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7990.64359 | 7990.64359 | 0.35907 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31480.71519 | 31480.71519 | 2.40436 | 2.40436 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53444E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2551.76002 | 2551.76002 | 0.11465 | 0.36721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7457.64043 | 7457.64043 | 0.56802 | 0.56802 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8258.89833 | 8258.89833 | 0.37113 | 0.37113 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 463482.05 | 21.83312 | 21.83312 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 382636.93 | 7.72810 | 7.72810 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43559.48 | 18.55174 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101559.87 | 6.15889 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.73214 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55190 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.67203 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.90341E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.39997E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.67203 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15388.80551 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.39997E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.52047 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.33678 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15176 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32937 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51060E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31873E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32937 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5968.80481 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31873E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.87440 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24947 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23724 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24398 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60597E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.19929E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24398 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2353.28166 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.19929E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.90730 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28273 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44266 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27651 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.60707E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.36308E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27651 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3332.65024 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.36308E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 64.00863 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11684 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61800 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11427 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.16508E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.26665E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11427 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1931.15670 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26665E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.44593 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.41669 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.90651E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.34152 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18908E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.28899E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.34152 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19412.66382 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.28899E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 346.49769 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45930 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.86176E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.42720 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.86341E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.07236E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.42720 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18432.13622 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.07236E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 357.62680 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.88684 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20398 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.77933 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86779E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04094E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.77933 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 47114.39863 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04094E-003 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 881.19421 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21450 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21450 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.21450 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73089E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.18921E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.18921E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.21450 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68100E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55379 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7834.28272 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73089E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.36131 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19615 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.19615 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.19615 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73568E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.11381E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.11381E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.19615 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68343E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55378 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7855.96592 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73568E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.85487 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.66203 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.66203 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.66203 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.75572E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.80057E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.80057E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.66203 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.61457E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55469 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44155.95864 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.75572E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1005.28416 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.75706 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.75706 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.75706 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.84121E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.99050E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.99050E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.75706 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.82784E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55348 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44542.91465 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.84121E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1014.09235 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09362 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09362 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09362 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.72243E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.69810E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.69810E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.09362 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70328E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55371 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7795.98978 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72243E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.48966 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08759 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08759 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.08759 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.72720E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.67364E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.67364E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.08759 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70455E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55370 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7817.57810 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72720E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.98107 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16079 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.85625E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16079 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17453.99416 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.85625E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.14307 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31775 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31775 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.31775 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.29761E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.35509E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.35509E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.31775 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67328E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55382 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2397.78267 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.29761E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.58789 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31281 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31281 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.31281 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.32482E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.33482E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.33482E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.31281 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67565E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55381 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2410.09785 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32482E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.86821 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24789 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.24789 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.24789 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.52880E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.44693E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.44693E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.24789 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.76952E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.55345 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 11445.73652 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52880E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.57265 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28475 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11061 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.23449 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44445E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21908E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.23449 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19096.22520 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21908E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.70771 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.40238 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10520 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.34953 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.62179E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.37779E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.34953 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19814.58247 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.37779E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 364.45797 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.40436 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78515 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35146 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97800 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16372E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.17113E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.35146 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14353.05706 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17113E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 257.03886 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56802 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55286 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.97800 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55553 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.89142E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.44246E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55553 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11054.96341 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44246E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 225.01564 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.83601 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.83601 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.32721 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.83601 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.83601 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.83601 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.83601 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.83601 |
346 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 21.83312 |
347 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 21.83312 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 959177.96916 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.42596E-002 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 21.83601 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
355 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 324346.27273 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 7.16603E-003 |
358 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 4129.80736 |
359 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 21.83601 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.42596E-002 |
361 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.38995E-005 |
362 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.16603E-003 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
365 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 87700.73147 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.13247E-003 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
373 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 30467.96244 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.73152E-004 |
376 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 387.93976 |
377 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.13247E-003 |
379 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.52018E-004 |
380 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73152E-004 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 4.59643E-002 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11008.84641 |
383 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
384 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
386 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
387 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.51735E-002 |
389 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.82082 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.51735E-002 |
391 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3876.63580 |
392 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 686777.26192 |
393 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 686777.26000 |
394 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.51735E-002 |
395 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 4.59643E-002 |
396 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 5.51572 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 4.59643E-002 |
398 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3669.61547 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 4.59643E-002 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 1286878.33377 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 1287488.95000 |
402 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 146.77374 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 15476.79 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6006.16 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2366.22 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3350.17 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1943.36 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19523.60 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 18553.75 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 47369.04 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 8454.28 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 8477.67 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 47650.46 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 48067.98 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 8412.96 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 8436.25 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 17567.20 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2587.47 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2600.76 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 12351.21 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 19202.30 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 19924.76 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 14434.81 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11123.28 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 197307.62 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 18534.39 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 21611.62 | 16645.61 | 4966.01 | 0.77 | 2553.08 | 25.89 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 21292.87 | 16397.65 | 4895.23 | 0.77 | 2515.26 | 25.51 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 117346.89 | 90759.19 | 26587.70 | 0.77 | 13888.01 | 140.86 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 122888.28 | 93818.08 | 29070.20 | 0.76 | 14464.78 | 146.71 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 19526.40 | 15018.89 | 4507.51 | 0.77 | 2305.39 | 23.38 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 19422.47 | 14937.79 | 4484.68 | 0.77 | 2293.04 | 23.26 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 5647.55 | 4351.92 | 1295.63 | 0.77 | 667.31 | 6.77 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 5561.88 | 4285.27 | 1276.61 | 0.77 | 657.14 | 6.67 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 22502.18 | 17238.44 | 5263.74 | 0.77 | 2652.30 | 26.90 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 731652.68 | 453846.13 | 277806.55 | 0.62 | 103693.25 | 1051.71 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67062.26 | 41857.36 | 25204.89 | 0.62 | 8925.08 | 90.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 3.82 | 13.05 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 5.3255545922E-003 | 1.2808256451E-002 | Pass | Pass | 1.4260382128E-002 | 3.3122383707E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5351641357E-003 | 1.7534245257E-003 | Pass | Pass | 7.1877085316E-002 | 0.1696057057 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4554395253E-003 | 1.0542933315E-003 | Pass | Pass | 2.6005467046E-002 | 5.6138448994E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5357612432E-004 | 6.3798123901E-004 | Pass | Pass | 5.6694330301E-002 | 0.1005089364 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5737727541E-004 | 7.1070512462E-004 | Pass | Pass | 0.4398347576 | 4.3049794593 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5679077124E-002 | 0.1426240303 | Pass | Pass | 1.9406597305E-002 | 5.5599170380E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9664535082E-003 | 2.1245725864E-003 | Pass | Pass | 0.1205633030 | 0.4142546744 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.0843892315E-003 | 2.3125465319E-003 | Pass | Pass | 2.7611022628E-002 | 6.6361498942E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1080846735E-002 | 0.3130682622 | Pass | Pass | 0.3285157303 | 1.1877050759 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1356110014E-002 | 0.3178891037 | Pass | Pass | 0.2881172034 | 1.1345524761 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.6115840341E-002 | 3.5252584984E-002 | Pass | Pass | 0.9534163158 | 10.3407242223 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6822487073E-002 | 6.4956293276E-002 | Pass | Pass | 0.3707608987 | 1.3787953606 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.0890615973E-002 | 0.3092009897 | Pass | Pass | 0.3044286218 | 1.0851645342 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1148715566E-002 | 0.3133362862 | Pass | Pass | 0.3293777539 | 1.1926820280 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6734996740E-004 | 4.9639888555E-004 | Pass | Pass | 2.8297779647E-002 | 3.2053782300E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2692626391E-002 | 0.3401950642 | Pass | Pass | 0.5580270312 | 3.4391445238 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2768845915E-002 | 0.3444468126 | Pass | Pass | 1.0867702388 | 8.5428109729 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.7547390192E-002 | 0.2608478837 | Pass | Pass | 0.6402830524 | 5.2598791753 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5834393950E-002 | 6.9994543823E-002 | Pass | Pass | 1.2252325827E-002 | 3.6521194818E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8640829099E-002 | 7.1228311863E-002 | Pass | Pass | 1.0992125807E-002 | 3.0088383794E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2349511574E-002 | 0.1388474471 | Pass | Pass | 1.7413777409E-002 | 3.1610600369E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1024262241E-003 | 8.1399782188E-004 | Pass | Pass | 2.7525447660E-002 | 3.3645324100E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.394 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.394 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.394 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.102 | 0.394 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.085 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 432.93 | 2.087 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 781.15 | 2.084 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 10.1931 | 1978.83 | 20170.43 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 55.03 | 168.00 | 54.96 | 0.0000 | Y | 208.11 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 15.2897 | 67.07 | 1025.50 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.29 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 15.2897 | 77.67 | 1187.53 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.07 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 15.2897 | 164.24 | 2511.22 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 27.64 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 8.1545 | 94.76 | 772.71 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 4.42 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 6.1159 | 78.04 | 477.28 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.25 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 13.2510 | 188.86 | 2502.62 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 27.54 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 11.2124 | 1308.19 | 14667.93 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 161.43 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 11.8403 | 156.09 | 1848.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 11.8403 | 156.07 | 1847.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 11.8403 | 1863.81 | 22068.10 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 286.71 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 11.8403 | 1864.32 | 22074.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 286.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 11.8403 | 156.09 | 1848.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 11.8403 | 156.07 | 1847.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 5.0966 | 1557.62 | 7938.49 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 87.37 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 11.8403 | 39.02 | 462.03 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.00 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 11.8403 | 39.02 | 461.98 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.00 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 11.8403 | 220.77 | 2614.04 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 33.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 13.2510 | 331.66 | 4394.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 48.37 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 13.2510 | 331.66 | 4394.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 48.37 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 12.2317 | 103.30 | 1263.59 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.91 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 5.0966 | 412.12 | 2100.42 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 23.12 |
Interior Lighting Total | 10.4431 | 11345.29 | 118479.68 | 661.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15665.55 | AstronomicalClock | - | 83.63 | 83.63 | 245.92 | |
Exterior Lighting Total | 15665.55 | 245.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 686777.26 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 1287488.95 | 2.80 | 3.82 | 13.05 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 14528.68 | 21611.62 | 16645.61 | 4966.01 | 0.77 | - | 2553.08 | 25.89 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 14317.58 | 21292.87 | 16397.65 | 4895.23 | 0.77 | - | 2515.26 | 25.51 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 78409.89 | 117346.89 | 90759.19 | 26587.70 | 0.77 | - | 13888.01 | 140.86 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 83727.70 | 122888.28 | 93818.08 | 29070.20 | 0.76 | - | 14464.78 | 146.71 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 13153.69 | 19526.40 | 15018.89 | 4507.51 | 0.77 | - | 2305.39 | 23.38 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 13085.19 | 19422.47 | 14937.79 | 4484.68 | 0.77 | - | 2293.04 | 23.26 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3793.95 | 5647.55 | 4351.92 | 1295.63 | 0.77 | - | 667.31 | 6.77 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3737.21 | 5561.88 | 4285.27 | 1276.61 | 0.77 | - | 657.14 | 6.67 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 15250.24 | 22502.18 | 17238.44 | 5263.74 | 0.77 | - | 2652.30 | 26.90 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 959177.97 | 731652.68 | 453846.13 | 277806.55 | 0.62 | - | 103693.25 | 1051.71 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 87700.73 | 67062.26 | 41857.36 | 25204.89 | 0.62 | - | 8925.08 | 90.52 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 15388.81 | 15476.79 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5968.80 | 6006.16 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2353.28 | 2366.22 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3332.65 | 3350.17 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1931.16 | 1943.36 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19412.66 | 19523.60 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18432.14 | 18553.75 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 47114.40 | 47369.04 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7834.28 | 8454.28 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7855.97 | 8477.67 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44155.96 | 47650.46 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44542.91 | 48067.98 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7795.99 | 8412.96 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7817.58 | 8436.25 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17453.99 | 17567.20 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2397.78 | 2587.47 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2410.10 | 2600.76 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 11445.74 | 12351.21 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19096.23 | 19202.30 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19814.58 | 19924.76 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14353.06 | 14434.81 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11054.96 | 11123.28 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 324346.27 | 197307.62 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 30467.96 | 18534.39 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.21 | 2056.30 | 1693.13 | 1.00 | 0.48 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.20 | 2025.23 | 1693.12 | 1.00 | 0.48 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 6.66 | 11279.64 | 1693.12 | 1.00 | 0.40 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 6.76 | 11440.55 | 1693.12 | 1.00 | 0.40 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.09 | 1851.64 | 1693.12 | 1.00 | 0.49 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.09 | 1841.43 | 1693.12 | 1.00 | 0.49 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 0.32 | 537.99 | 1693.12 | 1.00 | 0.70 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 0.31 | 529.63 | 1693.12 | 1.00 | 0.70 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.25 | 2112.84 | 1693.12 | 1.00 | 0.48 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.84 | 48926.61 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.045964 | 11008.85 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.015174 | 3876.64 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.045964 | 3669.62 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35866.38 | 35866.38 | 18.13 | 2.732 | 2.732 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00917 | 26.29 | 0.01534 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4420.07 | 4420.07 | 65.90 | 0.337 | 0.337 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00938 | 30.85 | 0.01534 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3274.46 | 3274.46 | 42.16 | 0.249 | 0.249 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00946 | 30.14 | 0.01534 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44850.47 | 44850.47 | 574.72 | 3.417 | 3.417 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01534 | 0.236 | 0.00 |
CAFE_FLR_1 | 19137.12 | 19137.12 | 101.33 | 1.459 | 1.459 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01034 | 30.85 | 0.01534 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64124.70 | 64124.70 | 49.02 | 4.887 | 4.887 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01009 | 30.93 | 0.01534 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 11830.99 | 11830.99 | 303.19 | 1.215 | 1.215 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11652.20 | 11652.20 | 298.64 | 1.196 | 1.196 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 64903.38 | 64903.38 | 2646.54 | 6.662 | 6.662 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00861 | 30.85 | 0.01534 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 65824.17 | 65824.17 | 2683.35 | 6.757 | 6.757 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00883 | 31.20 | 0.01534 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10653.42 | 10653.42 | 273.01 | 1.094 | 1.094 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00870 | 25.37 | 0.01534 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10594.69 | 10594.69 | 271.54 | 1.088 | 1.088 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 21.11 | 21.11 | 0.00870 | 25.03 | 0.01534 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 3095.32 | 3095.32 | 79.32 | 0.318 | 0.318 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00867 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3047.26 | 3047.26 | 78.10 | 0.313 | 0.313 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12156.11 | 12156.11 | 495.55 | 1.248 | 1.248 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00877 | 30.93 | 0.01534 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29955.76 | 29955.76 | 90.32 | 2.285 | 2.285 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01041 | 31.20 | 0.01534 | 1.187 | 0.00 |
DINING_FLR_6 | 31498.58 | 31498.58 | 94.97 | 2.402 | 2.402 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01032 | 31.20 | 0.01534 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 31480.72 | 31480.72 | 304.74 | 2.404 | 2.404 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 23.97 | 0.00999 | 25.97 | 0.01534 | 0.367 | 0.00 |
MECH_FLR_1 | 3711.95 | 3711.95 | 22.60 | 0.283 | 0.283 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00870 | 30.88 | 0.01534 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1533.97 | 1533.97 | 16.19 | 0.117 | 0.117 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00883 | 31.20 | 0.01534 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 10870.91 | 10870.91 | 27.92 | 0.828 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00872 | 31.20 | 0.01534 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7457.64 | 7457.64 | 18.10 | 0.568 | 0.568 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00864 | 31.20 | 0.01534 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1932.73 | 1932.73 | 0.98 | 0.087 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4313.14 | 4313.14 | 64.31 | 0.194 | 0.194 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00719 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1126.19 | 1126.19 | 14.50 | 0.051 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00734 | -26.20 | 0.00036 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2614.19 | 2614.19 | 33.50 | 0.117 | 0.236 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00715 | -26.20 | 0.00036 | 0.236 | 0.00 |
CAFE_FLR_1 | 11257.38 | 11257.38 | 59.61 | 0.506 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00722 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23082.69 | 23082.69 | 17.64 | 1.037 | 1.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00723 | -26.20 | 0.00036 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 7834.58 | 7834.58 | 200.77 | 0.354 | 0.354 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7856.27 | 7856.27 | 201.35 | 0.355 | 0.355 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 44156.78 | 44156.78 | 1800.57 | 1.996 | 1.996 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 44543.75 | 44543.75 | 1815.85 | 2.013 | 2.013 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7796.29 | 7796.29 | 199.79 | 0.352 | 0.352 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7817.88 | 7817.88 | 200.37 | 0.353 | 0.353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2397.87 | 2397.87 | 61.45 | 0.108 | 0.108 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2410.19 | 2410.19 | 61.77 | 0.109 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11446.07 | 11446.07 | 466.60 | 0.517 | 0.517 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7850.91 | 7850.91 | 23.67 | 0.353 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
DINING_FLR_6 | 7990.64 | 7990.64 | 24.09 | 0.359 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 2551.76 | 2551.76 | 24.70 | 0.115 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00659 | -26.20 | 0.00036 | 0.367 | 0.00 |
MECH_FLR_1 | 1942.38 | 1942.38 | 11.83 | 0.087 | 0.087 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00717 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1356.63 | 1356.63 | 14.32 | 0.061 | 0.061 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00718 | -26.20 | 0.00036 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11613.17 | 11613.17 | 29.82 | 0.522 | 0.522 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00755 | -26.20 | 0.00036 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8258.90 | 8258.90 | 20.04 | 0.371 | 0.371 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00771 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.83 | 21.83 | 7.73 | 7.73 | 21.8360 | 21.8360 | 21.8360 | 1.0000 | 0.3000 |
FLR_3_DOAS | 18.55 | 2.05 | 6.16 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 15388.806 | 15388.806 | 2.672030 | 0.00034000 | 274.520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15476.79 | 15388.81 | 2.672030 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797381 | 49.1695 | 1932.73 | 0.00 | 15479.76 | 15479.76 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5968.805 | 5968.805 | 0.329369 | 0.00013187 | 119.874 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6006.16 | 5968.80 | 0.329369 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00719163 | 44.4059 | 4313.14 | 0.00 | 6008.29 | 6008.29 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2353.282 | 2353.282 | 0.243980 | 0.00005199 | 43.907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2366.22 | 2353.28 | 0.243980 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00733652 | 45.2869 | 1126.19 | 0.00 | 2367.00 | 2367.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3332.650 | 3332.650 | 0.276510 | 0.00007363 | 64.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3350.17 | 3332.65 | 0.276510 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00717286 | 44.2883 | 1942.38 | 0.00 | 3351.55 | 3351.55 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1931.157 | 1931.157 | 0.114269 | 0.00004267 | 38.446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1943.36 | 1931.16 | 0.114269 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00717619 | 44.3089 | 1356.63 | 0.00 | 1943.98 | 1943.98 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19412.664 | 19412.664 | 3.341519 | 0.00042890 | 346.498 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 19523.60 | 19412.66 | 3.341519 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00714519 | 44.1205 | 2614.19 | 0.00 | 19527.37 | 19527.37 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 18432.136 | 18432.136 | 1.427196 | 0.00040724 | 357.627 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18553.75 | 18432.14 | 1.427196 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00721564 | 44.5521 | 11257.38 | 0.00 | 18557.66 | 18557.66 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 47114.399 | 47114.399 | 4.779332 | 0.00104094 | 881.194 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 47369.04 | 47114.40 | 4.779332 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723496 | 44.6679 | 23082.69 | 0.00 | 47384.89 | 47384.89 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14528.678 | -999.000 | 1.214503 | 0.00051892 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 14528.68 | 13988.05 | 1.214503 | 22.55 | 15.54 | 0.00868100 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868100 | 53.1103 | 11830.99 | 0.00 | 15158.43 | 14285.92 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7834.283 | 7834.283 | 0.354108 | 0.00017309 | 178.361 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8454.28 | 7834.28 | 0.354108 | 21.11 | 13.92 | 0.00745935 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745935 | 45.7248 | 7834.58 | 0.00 | 8457.32 | 8457.32 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 14317.578 | -999.000 | 1.196150 | 0.00051138 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 14317.58 | 13777.94 | 1.196150 | 22.55 | 15.54 | 0.00868343 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868343 | 53.1250 | 11652.20 | 0.00 | 14938.00 | 14071.09 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7855.966 | 7855.966 | 0.355088 | 0.00017357 | 178.855 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8477.67 | 7855.97 | 0.355088 | 21.11 | 13.93 | 0.00746077 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746077 | 45.7335 | 7856.27 | 0.00 | 8480.73 | 8480.73 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 78409.886 | -999.000 | 6.662027 | 0.00280057 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 78409.89 | 76537.66 | 6.662027 | 22.55 | 15.48 | 0.00861457 | 12.80 | 11.67 | 0.00850000 | 30.85 | 0.01534436 | 23.01 | 0.0000 | 21.11 | 0.00861457 | 52.7071 | 64903.38 | 0.00 | 81836.09 | 78205.59 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 44155.959 | 44155.959 | 1.995904 | 0.00097557 | 1005.284 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47650.46 | 44155.96 | 1.995904 | 21.11 | 13.95 | 0.00748932 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00748932 | 45.9048 | 44156.78 | 0.00 | 47668.02 | 47668.02 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 83727.703 | -999.000 | 6.757063 | 0.00299050 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 83727.70 | 78249.93 | 6.757063 | 22.55 | 15.66 | 0.00882784 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 0.0000 | 21.11 | 0.00882784 | 53.9958 | 65824.17 | 0.00 | 87293.66 | 79834.80 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 44542.915 | 44542.915 | 2.013394 | 0.00098412 | 1014.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48067.98 | 44542.91 | 2.013394 | 21.11 | 13.96 | 0.00749334 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749334 | 45.9291 | 44543.75 | 0.00 | 48085.76 | 48085.76 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13153.686 | -999.000 | 1.093623 | 0.00046981 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 13153.69 | 12606.48 | 1.093623 | 22.55 | 15.56 | 0.00870328 | 12.80 | 11.67 | 0.00850000 | 25.37 | 0.01534436 | 21.50 | 0.0000 | 21.11 | 0.00870328 | 53.2448 | 10653.42 | 0.00 | 13722.30 | 12872.88 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7795.990 | 7795.990 | 0.352377 | 0.00017224 | 177.490 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8412.96 | 7795.99 | 0.352377 | 21.11 | 13.92 | 0.00745688 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745688 | 45.7099 | 7796.29 | 0.00 | 8415.98 | 8415.98 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 13085.188 | -999.000 | 1.087595 | 0.00046736 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | 7/21 08:50:00 | 13085.19 | 12537.59 | 1.087595 | 22.55 | 15.56 | 0.00870455 | 12.80 | 11.67 | 0.00850000 | 25.03 | 0.01534436 | 21.41 | 0.0000 | 21.11 | 0.00870455 | 53.2524 | 10594.69 | 0.00 | 13650.76 | 12802.41 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7817.578 | 7817.578 | 0.353353 | 0.00017272 | 177.981 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8436.25 | 7817.58 | 0.353353 | 21.11 | 13.92 | 0.00745831 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745831 | 45.7186 | 7817.88 | 0.00 | 8439.29 | 8439.29 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 17453.994 | 17453.994 | 1.160794 | 0.00038562 | 343.143 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 17567.20 | 17453.99 | 1.160794 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00755067 | 46.5922 | 11613.17 | 0.00 | 17571.91 | 17571.91 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3793.949 | -999.000 | 0.317748 | 0.00013551 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3793.95 | 3658.58 | 0.317748 | 22.55 | 15.53 | 0.00867328 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00867328 | 53.0637 | 3095.32 | 0.00 | 3958.55 | 3736.70 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2397.783 | 2397.783 | 0.108379 | 0.00005298 | 54.588 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2587.47 | 2397.78 | 0.108379 | 21.11 | 14.01 | 0.00755247 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755247 | 46.2888 | 2397.87 | 0.00 | 2588.47 | 2588.47 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3737.206 | -999.000 | 0.312814 | 0.00013348 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3737.21 | 3602.10 | 0.312814 | 22.55 | 15.53 | 0.00867565 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00867565 | 53.0780 | 3047.26 | 0.00 | 3899.30 | 3678.95 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2410.098 | 2410.098 | 0.108936 | 0.00005325 | 54.868 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2600.76 | 2410.10 | 0.108936 | 21.11 | 14.01 | 0.00755466 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755466 | 46.3021 | 2410.19 | 0.00 | 2601.77 | 2601.77 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15250.241 | -999.000 | 1.247893 | 0.00054469 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 15250.24 | 14420.32 | 1.247893 | 22.55 | 15.61 | 0.00876952 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00876952 | 53.6447 | 12156.11 | 0.00 | 15904.27 | 14718.21 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11445.737 | 11445.737 | 0.517351 | 0.00025288 | 260.573 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12351.21 | 11445.74 | 0.517351 | 21.11 | 14.02 | 0.00756742 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00756742 | 46.3788 | 11446.07 | 0.00 | 12356.03 | 12356.03 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19096.225 | 19096.225 | 2.234488 | 0.00042191 | 351.708 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 19202.30 | 19096.23 | 2.234488 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765928 | 47.2546 | 7850.91 | 0.00 | 19207.83 | 19207.83 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19814.582 | 19814.582 | 2.349532 | 0.00043778 | 364.458 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 19924.76 | 19814.58 | 2.349532 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766498 | 47.2898 | 7990.64 | 0.00 | 19930.43 | 19930.43 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14353.057 | 14353.057 | 2.351463 | 0.00031711 | 257.039 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 14434.81 | 14353.06 | 2.351463 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00658932 | 40.7313 | 2551.76 | 0.00 | 14437.75 | 14437.75 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11054.963 | 11054.963 | 0.555528 | 0.00024425 | 225.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 11123.28 | 11054.96 | 0.555528 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771406 | 47.5883 | 8258.90 | 0.00 | 11127.77 | 11127.77 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 959177.969 | -999.000 | 21.836011 | 0.03425961 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 959177.97 | 522753.62 | 21.836011 | 31.20 | 23.10 | 0.01534436 | 10.91 | 10.90 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 99.9868 | 23.99 | 0.00952651 | 48.8581 | 286307.63 | 0.00 | 1016329.75 | 539656.10 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 324346.273 | 324346.273 | 6.550803 | 0.00716603 | 4129.807 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 197307.62 | 324346.27 | 6.550803 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.2892 | 21.00 | 0.00747199 | 46.1137 | 84894.89 | 0.00 | 196852.36 | 196852.36 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 10.91 | 11.67 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 100.0000 | 21.11 | 0.00872192 | 53.3559 | 179045.07 | 0.00 | 93045.89 | 49604.71 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 0.615360 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3333 | 21.11 | 0.00749192 | 45.9206 | 136259.67 | 0.00 | 18491.63 | 18491.63 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 15388.806 | 15388.806 | 2.672030 | 0.00034000 | 274.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.2091 | 2.240727 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15476.79 | 15388.81 | 1.0000 | 3.06897546 | 2.672030 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33996217 | 60.00 | 49.00 | 11.00 | 0.000 | 15476.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797381 | 21.00 | 0.00797381 | 49.1695 | 1932.73 | 0.00 | 15479.76 | 15479.76 | 3.06897546 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.55 | 15.04 | 0.00800000 | 41978.7 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5968.805 | 5968.805 | 0.329369 | 0.00013187 | 119.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.8573 | 0.869103 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6006.16 | 5968.80 | 1.0000 | 0.37829905 | 0.329369 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.13186000 | 60.00 | 49.00 | 11.00 | 0.000 | 6006.16 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00719163 | 21.00 | 0.00719163 | 44.4059 | 4313.14 | 0.00 | 6008.29 | 6008.29 | 0.37829905 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 32.18 | 18.73 | 0.00800000 | 52817.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2353.282 | 2353.282 | 0.243980 | 0.00005199 | 43.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.3377 | 0.342656 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2366.22 | 2353.28 | 1.0000 | 0.28022462 | 0.243980 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05198758 | 60.00 | 49.00 | 11.00 | 0.000 | 2366.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00733652 | 21.00 | 0.00733652 | 45.2869 | 1126.19 | 0.00 | 2367.00 | 2367.00 | 0.28022462 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.88 | 16.25 | 0.00800000 | 45381.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3332.650 | 3332.650 | 0.276510 | 0.00007363 | 64.009 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.4782 | 0.485259 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3350.17 | 3332.65 | 1.0000 | 0.31758764 | 0.276510 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.07362332 | 60.00 | 49.00 | 11.00 | 0.000 | 3350.17 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00717286 | 21.00 | 0.00717286 | 44.2883 | 1942.38 | 0.00 | 3351.55 | 3351.55 | 0.31758764 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.95 | 16.98 | 0.00800000 | 47487.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1931.157 | 1931.157 | 0.114269 | 0.00004267 | 38.446 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.2774 | 0.281191 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1943.36 | 1931.16 | 1.0000 | 0.13124466 | 0.114269 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.04266220 | 60.00 | 49.00 | 11.00 | 0.000 | 1943.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00717619 | 21.00 | 0.00717619 | 44.3089 | 1356.63 | 0.00 | 1943.98 | 1943.98 | 0.13124466 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.13 | 18.39 | 0.00800000 | 51746.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19412.664 | 19412.664 | 3.341519 | 0.00042890 | 346.498 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.7867 | 2.826632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 19523.60 | 19412.66 | 1.0000 | 3.83792155 | 3.341519 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.42885533 | 60.00 | 49.00 | 11.00 | 0.000 | 19523.60 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00714519 | 21.00 | 0.00714519 | 44.1205 | 2614.19 | 0.00 | 19527.37 | 19527.37 | 3.83792155 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.59 | 15.06 | 0.00800000 | 42022.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18432.136 | 18432.136 | 1.427196 | 0.00040724 | 357.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.6483 | 2.683859 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18553.75 | 18432.14 | 1.0000 | 1.63921447 | 1.427196 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.40719398 | 60.00 | 49.00 | 11.00 | 0.000 | 18553.75 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00721564 | 21.00 | 0.00721564 | 44.5521 | 11257.38 | 0.00 | 18557.66 | 18557.66 | 1.63921447 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.70 | 17.24 | 0.00800000 | 48255.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 47114.399 | 47114.399 | 4.779332 | 0.00104094 | 881.194 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 6.7612 | 6.860215 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 47369.04 | 47114.40 | 1.0000 | 5.48933007 | 4.779332 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 1.04082888 | 60.00 | 49.00 | 11.00 | 0.000 | 47369.04 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723496 | 21.00 | 0.00723496 | 44.6679 | 23082.69 | 0.00 | 47384.89 | 47384.89 | 5.48933007 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 25.07 | 16.32 | 0.00800000 | 45566.9 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14528.678 | -999.000 | 1.214503 | 0.00051892 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9776 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.214503 | 1.39492399 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 1.1290 | 1.128965 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 14528.68 | 13988.05 | 1.0000 | 1.39492399 | 1.214503 | 22.55 | 15.54 | 0.00868100 | 44737.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.51886810 | 6.70 | 11.72 | 6.67 | 0.000 | 14528.68 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868100 | 21.11 | 0.00868100 | 53.1103 | 11830.99 | 0.00 | 15158.43 | 14285.92 | 1.39492399 | 22.55 | 16.02 | 0.00868100 | 44737.6 | 12.52 | 11.92 | 0.00843321 | 33870.7 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7834.283 | 7834.283 | 0.354108 | 0.00017309 | 178.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.214503 | 1.39492399 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.2067 | 1.140731 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8454.28 | 7834.28 | 1.0000 | 0.40671319 | 0.354108 | 21.11 | 13.92 | 0.00745935 | 40160.2 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17307125 | 60.00 | 49.00 | 11.00 | 0.000 | 8454.28 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745935 | 21.11 | 0.00745935 | 45.7248 | 7834.58 | 0.00 | 8457.32 | 8457.32 | 0.40671319 | 16.60 | 12.61 | 0.00745935 | 35565.9 | 37.01 | 19.84 | 0.00745935 | 56360.2 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14317.578 | -999.000 | 1.196150 | 0.00051138 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9821 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.196150 | 1.37384449 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 1.1126 | 1.112561 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 14317.58 | 13777.94 | 1.0000 | 1.37384449 | 1.196150 | 22.55 | 15.54 | 0.00868343 | 44743.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.51132901 | 6.70 | 11.72 | 6.67 | 0.000 | 14317.58 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868343 | 21.11 | 0.00868343 | 53.1250 | 11652.20 | 0.00 | 14938.00 | 14071.09 | 1.37384449 | 22.55 | 16.02 | 0.00868343 | 44743.7 | 12.52 | 11.92 | 0.00843345 | 33870.6 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7855.966 | 7855.966 | 0.355088 | 0.00017357 | 178.855 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.196150 | 1.37384449 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.2101 | 1.143888 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8477.67 | 7855.97 | 1.0000 | 0.40783886 | 0.355088 | 21.11 | 13.93 | 0.00746077 | 40163.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17355026 | 60.00 | 49.00 | 11.00 | 0.000 | 8477.67 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746077 | 21.11 | 0.00746077 | 45.7335 | 7856.27 | 0.00 | 8480.73 | 8480.73 | 0.40783886 | 16.60 | 12.61 | 0.00746077 | 35569.5 | 37.01 | 19.84 | 0.00746077 | 56363.8 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78409.886 | -999.000 | 6.662027 | 0.00280057 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8541 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.662027 | 7.65170980 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 6.0930 | 6.092916 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | 78409.89 | 76537.66 | 1.0000 | 7.65170980 | 6.662027 | 22.55 | 15.48 | 0.00861457 | 44569.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.80028148 | 6.70 | 11.72 | 6.67 | 0.000 | 78409.89 | 30.85 | 0.01534436 | 23.01 | 0.00000000 | 0.0000 | 21.11 | 0.00861457 | 21.11 | 0.00861457 | 52.7071 | 64903.38 | 0.00 | 81836.09 | 78205.59 | 7.65170980 | 22.55 | 15.96 | 0.00861457 | 44569.6 | 12.54 | 11.92 | 0.00842660 | 33874.4 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44155.959 | 44155.959 | 1.995904 | 0.00097557 | 1005.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.662027 | 7.65170980 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 6.8014 | 6.429444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47650.46 | 44155.96 | 1.0000 | 2.29240666 | 1.995904 | 21.11 | 13.95 | 0.00748932 | 40236.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.97547243 | 60.00 | 49.00 | 11.00 | 0.000 | 47650.46 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748932 | 21.11 | 0.00748932 | 45.9048 | 44156.78 | 0.00 | 47668.02 | 47668.02 | 2.29240666 | 16.60 | 12.64 | 0.00748932 | 35641.8 | 37.01 | 19.87 | 0.00748932 | 56435.7 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 83727.703 | -999.000 | 6.757063 | 0.00299050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2505 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.757063 | 7.76086422 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 6.5063 | 6.506143 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 83727.70 | 78249.93 | 1.0000 | 7.76086422 | 6.757063 | 22.55 | 15.66 | 0.00882784 | 45110.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.99019864 | 6.70 | 11.72 | 6.67 | 0.000 | 83727.70 | 31.20 | 0.01534436 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00882784 | 21.11 | 0.00882784 | 53.9958 | 65824.17 | 0.00 | 87293.66 | 79834.80 | 7.76086422 | 22.55 | 16.14 | 0.00882784 | 45110.6 | 12.48 | 11.91 | 0.00844708 | 33862.7 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44542.915 | 44542.915 | 2.013394 | 0.00098412 | 1014.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.757063 | 7.76086422 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 6.8610 | 6.485788 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48067.98 | 44542.91 | 1.0000 | 2.31249592 | 2.013394 | 21.11 | 13.96 | 0.00749334 | 40247.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.98402088 | 60.00 | 49.00 | 11.00 | 0.000 | 48067.98 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749334 | 21.11 | 0.00749334 | 45.9291 | 44543.75 | 0.00 | 48085.76 | 48085.76 | 2.31249592 | 16.60 | 12.65 | 0.00749334 | 35652.0 | 37.01 | 19.87 | 0.00749334 | 56445.8 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13153.686 | -999.000 | 1.093623 | 0.00046981 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0190 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.093623 | 1.25608712 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 1.0221 | 1.022120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 13153.69 | 12606.48 | 1.0000 | 1.25608712 | 1.093623 | 22.55 | 15.56 | 0.00870328 | 44794.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.46976247 | 6.70 | 11.72 | 6.67 | 0.000 | 13153.69 | 25.37 | 0.01534436 | 21.50 | 0.00000000 | 0.0000 | 21.11 | 0.00870328 | 21.11 | 0.00870328 | 53.2448 | 10653.42 | 0.00 | 13722.30 | 12872.88 | 1.25608712 | 22.55 | 16.03 | 0.00870328 | 44794.1 | 12.52 | 11.92 | 0.00843538 | 33869.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7795.990 | 7795.990 | 0.352377 | 0.00017224 | 177.490 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.093623 | 1.25608712 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.2008 | 1.135155 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8412.96 | 7795.99 | 1.0000 | 0.40472523 | 0.352377 | 21.11 | 13.92 | 0.00745688 | 40153.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17222530 | 60.00 | 49.00 | 11.00 | 0.000 | 8412.96 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745688 | 21.11 | 0.00745688 | 45.7099 | 7796.29 | 0.00 | 8415.98 | 8415.98 | 0.40472523 | 16.60 | 12.61 | 0.00745688 | 35559.7 | 37.01 | 19.84 | 0.00745688 | 56354.0 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13085.188 | -999.000 | 1.087595 | 0.00046736 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0213 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.087595 | 1.24916310 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 1.0168 | 1.016797 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | unknown | unknown | 7/21 08:50:00 | 13085.19 | 12537.59 | 1.0000 | 1.24916310 | 1.087595 | 22.55 | 15.56 | 0.00870455 | 44797.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.46731619 | 6.70 | 11.72 | 6.67 | 0.000 | 13085.19 | 25.03 | 0.01534436 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00870455 | 21.11 | 0.00870455 | 53.2524 | 10594.69 | 0.00 | 13650.76 | 12802.41 | 1.24916310 | 22.55 | 16.04 | 0.00870455 | 44797.4 | 12.52 | 11.92 | 0.00843550 | 33869.4 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7817.578 | 7817.578 | 0.353353 | 0.00017272 | 177.981 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.087595 | 1.24916310 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.2041 | 1.138299 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8436.25 | 7817.58 | 1.0000 | 0.40584597 | 0.353353 | 21.11 | 13.92 | 0.00745831 | 40157.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17270222 | 60.00 | 49.00 | 11.00 | 0.000 | 8436.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745831 | 21.11 | 0.00745831 | 45.7186 | 7817.88 | 0.00 | 8439.29 | 8439.29 | 0.40584597 | 16.60 | 12.61 | 0.00745831 | 35563.3 | 37.01 | 19.84 | 0.00745831 | 56357.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17453.994 | 17453.994 | 1.160794 | 0.00038562 | 343.143 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.5075 | 2.541434 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 17567.20 | 17453.99 | 1.0000 | 1.33323618 | 1.160794 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.38558534 | 60.00 | 49.00 | 11.00 | 0.000 | 17567.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00755067 | 21.00 | 0.00755067 | 46.5922 | 11613.17 | 0.00 | 17571.91 | 17571.91 | 1.33323618 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.53 | 17.86 | 0.00800000 | 50114.6 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3793.949 | -999.000 | 0.317748 | 0.00013551 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9632 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.317748 | 0.36495113 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 0.2948 | 0.294812 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3793.95 | 3658.58 | 1.0000 | 0.36495113 | 0.317748 | 22.55 | 15.53 | 0.00867328 | 44718.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.13549470 | 6.70 | 11.72 | 6.67 | 0.000 | 3793.95 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00867328 | 21.11 | 0.00867328 | 53.0637 | 3095.32 | 0.00 | 3958.55 | 3736.70 | 0.36495113 | 22.55 | 16.01 | 0.00867328 | 44718.0 | 12.53 | 11.92 | 0.00843245 | 33871.2 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2397.783 | 2397.783 | 0.108379 | 0.00005298 | 54.588 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.317748 | 0.36495113 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.3693 | 0.349135 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2587.47 | 2397.78 | 1.0000 | 0.12447983 | 0.108379 | 21.11 | 14.01 | 0.00755247 | 40396.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05297067 | 60.00 | 49.00 | 11.00 | 0.000 | 2587.47 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755247 | 21.11 | 0.00755247 | 46.2888 | 2397.87 | 0.00 | 2588.47 | 2588.47 | 0.12447983 | 16.60 | 12.70 | 0.00755247 | 35801.7 | 37.01 | 19.91 | 0.00755247 | 56596.0 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3737.206 | -999.000 | 0.312814 | 0.00013348 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9676 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.312814 | 0.35928471 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 0.2904 | 0.290403 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3737.21 | 3602.10 | 1.0000 | 0.35928471 | 0.312814 | 22.55 | 15.53 | 0.00867565 | 44724.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.13346824 | 6.70 | 11.72 | 6.67 | 0.000 | 3737.21 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00867565 | 21.11 | 0.00867565 | 53.0780 | 3047.26 | 0.00 | 3899.30 | 3678.95 | 0.35928471 | 22.55 | 16.01 | 0.00867565 | 44724.0 | 12.52 | 11.92 | 0.00843269 | 33871.0 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2410.098 | 2410.098 | 0.108936 | 0.00005325 | 54.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.312814 | 0.35928471 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 0.3712 | 0.350929 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2600.76 | 2410.10 | 1.0000 | 0.12511917 | 0.108936 | 21.11 | 14.01 | 0.00755466 | 40402.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05324274 | 60.00 | 49.00 | 11.00 | 0.000 | 2600.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755466 | 21.11 | 0.00755466 | 46.3021 | 2410.19 | 0.00 | 2601.77 | 2601.77 | 0.12511917 | 16.60 | 12.71 | 0.00755466 | 35807.2 | 37.01 | 19.91 | 0.00755466 | 56601.5 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15250.241 | -999.000 | 1.247893 | 0.00054469 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1421 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.247893 | 1.43327425 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 1.1851 | 1.185035 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 15250.24 | 14420.32 | 1.0000 | 1.43327425 | 1.247893 | 22.55 | 15.61 | 0.00876952 | 44962.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.54463753 | 6.70 | 11.72 | 6.67 | 0.000 | 15250.24 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00876952 | 21.11 | 0.00876952 | 53.6447 | 12156.11 | 0.00 | 15904.27 | 14718.21 | 1.43327425 | 22.55 | 16.09 | 0.00876952 | 44962.3 | 12.50 | 11.91 | 0.00844169 | 33865.9 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11445.737 | 11445.737 | 0.517351 | 0.00025288 | 260.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.247893 | 1.43327425 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.7630 | 1.666586 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12351.21 | 11445.74 | 1.0000 | 0.59420673 | 0.517351 | 21.11 | 14.02 | 0.00756742 | 40435.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.25285377 | 60.00 | 49.00 | 11.00 | 0.000 | 12351.21 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756742 | 21.11 | 0.00756742 | 46.3788 | 11446.07 | 0.00 | 12356.03 | 12356.03 | 0.59420673 | 16.60 | 12.72 | 0.00756742 | 35839.5 | 37.01 | 19.92 | 0.00756742 | 56633.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19096.225 | 19096.225 | 2.234488 | 0.00042191 | 351.708 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.7408 | 2.780556 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 19202.30 | 19096.23 | 1.0000 | 2.56643415 | 2.234488 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.42186472 | 60.00 | 49.00 | 11.00 | 0.000 | 19202.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00765928 | 21.00 | 0.00765928 | 47.2546 | 7850.91 | 0.00 | 19207.83 | 19207.83 | 2.56643415 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.94 | 15.92 | 0.00800000 | 44419.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19814.582 | 19814.582 | 2.349532 | 0.00043778 | 364.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.8440 | 2.885154 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 19924.76 | 19814.58 | 1.0000 | 2.69856829 | 2.349532 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.43773433 | 60.00 | 49.00 | 11.00 | 0.000 | 19924.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766498 | 21.00 | 0.00766498 | 47.2898 | 7990.64 | 0.00 | 19930.43 | 19930.43 | 2.69856829 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.84 | 15.88 | 0.00800000 | 44320.3 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14353.057 | 14353.057 | 2.351463 | 0.00031711 | 257.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.0604 | 2.089914 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 14434.81 | 14353.06 | 1.0000 | 2.70078620 | 2.351463 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.31708091 | 60.00 | 49.00 | 11.00 | 0.000 | 14434.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.63 | 0.00658932 | 21.00 | 0.00658932 | 40.7313 | 2551.76 | 0.00 | 14437.75 | 14437.75 | 2.70078620 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.84 | 15.15 | 0.00800000 | 42280.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11054.963 | 11054.963 | 0.555528 | 0.00024425 | 225.016 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 1.5877 | 1.609687 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 11123.28 | 11054.96 | 1.0000 | 0.63805543 | 0.555528 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.24422099 | 60.00 | 49.00 | 11.00 | 0.000 | 11123.28 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771406 | 21.00 | 0.00771406 | 47.5883 | 8258.90 | 0.00 | 11127.77 | 11127.77 | 0.63805543 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 33.70 | 19.22 | 0.00800000 | 54374.9 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 959177.969 | -999.000 | 21.836011 | 0.03425961 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.836011 | 25.07987776 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 74.5352 | 74.535249 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 959177.97 | 522753.62 | 1.0000 | 25.07987776 | 21.836011 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 10.90 | 0.00868318 | 32395.4 | 34.25611980 | 6.70 | 11.72 | 6.67 | 48926.609 | 910251.36 | 31.20 | 0.01534436 | 23.10 | 21.83312000 | 99.9868 | 23.99 | 0.00967911 | 23.99 | 0.00952651 | 48.8581 | 286307.63 | 0.00 | 1016329.75 | 539656.10 | 25.07987776 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.38 | 10.35 | 0.00780290 | 30092.6 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 324346.273 | 324346.273 | 6.550803 | 0.00716603 | 4129.807 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.836011 | 25.07987776 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 28.1627 | 47.227288 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 197307.62 | 324346.27 | 1.0000 | 7.52396333 | 6.550803 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 7.16530356 | 60.00 | 49.00 | 11.00 | 0.000 | 197307.62 | -26.20 | 0.00036134 | -26.20 | 21.83312000 | 333.2892 | 20.94 | 0.00728850 | 21.00 | 0.00747199 | 46.1137 | 84894.89 | 0.00 | 196852.36 | 196852.36 | 7.52396333 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 45.95962353 | 13.37 | 6.70 | 6.67 | 1286878.33 | 6.8150 | 6.814998 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 1.0000 | 2.35591662 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 11.67 | 0.00868318 | 34322.2 | 3.13214738 | 6.70 | 11.72 | 6.67 | 2194.880 | 85505.85 | 31.20 | 0.01534436 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00873456 | 21.11 | 0.00872192 | 53.3559 | 179045.07 | 0.00 | 93045.89 | 49604.71 | 2.35591662 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.82 | 10.78 | 0.00803030 | 31121.7 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 15.17195655 | 71.00 | 82.00 | 11.00 | 700598.93 | 2.6455 | 4.436367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 1.0000 | 0.70677499 | 0.615360 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 0.67308373 | 60.00 | 49.00 | 11.00 | 0.000 | 18534.39 | -26.20 | 0.00036134 | -26.20 | 2.05119905 | 333.3333 | 21.11 | 0.00749246 | 21.11 | 0.00749192 | 45.9206 | 136259.67 | 0.00 | 18491.63 | 18491.63 | 0.70677499 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 21.83 | 21.84 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1045.00 | 8760.00 | 1045.00 |
RETAIL_1_FLR_1 | 2762.83 | 8711.33 | 2756.00 |
RETAIL_2_FLR_1 | 1042.00 | 8760.00 | 1042.00 |
LAUNDRY_FLR_1 | 2767.67 | 5690.67 | 1128.33 |
CAFE_FLR_1 | 1526.50 | 8723.67 | 1524.83 |
LOBBY_FLR_1 | 719.00 | 8760.00 | 719.00 |
ROOM_1_FLR_3 | 3041.33 | 8360.83 | 2948.00 |
ROOM_2_FLR_3 | 3439.00 | 8460.67 | 3368.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2004.67 | 8760.00 | 2004.67 |
ROOM_5_FLR_3 | 2951.83 | 8302.67 | 2927.67 |
ROOM_6_FLR_3 | 3320.33 | 8416.83 | 3296.83 |
ROOM_1_FLR_6 | 3563.67 | 8209.67 | 3347.00 |
ROOM_2_FLR_6 | 3917.50 | 8297.17 | 3755.00 |
ROOM_3_MULT9_FLR_6 | 2384.67 | 8216.00 | 2333.17 |
BANQUET_FLR_6 | 521.00 | 8759.33 | 521.00 |
DINING_FLR_6 | 370.17 | 8723.83 | 370.17 |
KITCHEN_FLR_6 | 6412.83 | 6439.00 | 4549.33 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 7696.17 | 8760.00 | 6837.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 717.00 | 0.00 | 717.00 | 0.00 |
RETAIL_1_FLR_1 | 305.67 | 0.00 | 305.67 | 0.00 |
RETAIL_2_FLR_1 | 288.17 | 0.00 | 288.17 | 0.00 |
LAUNDRY_FLR_1 | 178.83 | 21.33 | 178.83 | 21.33 |
CAFE_FLR_1 | 208.33 | 0.00 | 208.33 | 0.00 |
LOBBY_FLR_1 | 265.17 | 0.00 | 265.17 | 0.00 |
ROOM_1_FLR_3 | 28.00 | 0.00 | 28.00 | 0.00 |
ROOM_2_FLR_3 | 44.33 | 0.00 | 44.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 52.00 | 2.00 | 52.00 | 2.00 |
ROOM_5_FLR_3 | 41.50 | 0.00 | 41.50 | 0.00 |
ROOM_6_FLR_3 | 59.17 | 0.00 | 59.17 | 0.00 |
ROOM_1_FLR_6 | 4.33 | 1.17 | 4.33 | 1.17 |
ROOM_2_FLR_6 | 16.83 | 0.50 | 16.83 | 0.50 |
ROOM_3_MULT9_FLR_6 | 5.17 | 5.67 | 5.17 | 5.67 |
BANQUET_FLR_6 | 207.50 | 0.00 | 207.50 | 0.00 |
DINING_FLR_6 | 204.00 | 0.00 | 204.00 | 0.00 |
KITCHEN_FLR_6 | 177.50 | 106.33 | 177.50 | 106.33 |
MECH_FLR_1 | 385.33 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 405.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 595.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 389.33 | 0.00 | 0.00 | 0.00 |
Facility | 942.50 | 132.50 | 750.67 | 132.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 2.011 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 4.502 | 0.276 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.880 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 39.287 | 0.153 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 6.933 | 0.247 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 3.352 | 0.071 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.062 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.537 | 0.081 | 0.000 | 0.099 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.063 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.075 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.148 | 0.000 | 0.131 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 8.046 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 8.461 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 27.353 | 0.150 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.834 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 4.088 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.615 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 34.579 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 6.271 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 3.042 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.518 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.518 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 7.262 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 7.624 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 24.091 | 0.003 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
Electricity:Building | 3164.99 | 38600.85 | 02-JAN-02:10 | 200309.15 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 358.37 | 4020.20 | 02-JAN-02:10 | 27132.60 | 02-JAN-20:10 |
InteriorLights:Electricity | 1395.41 | 12235.54 | 02-JAN-02:10 | 110670.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 208.12 | 1890.98 | 02-JAN-02:10 | 17018.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1395.41 | 12235.54 | 02-JAN-02:10 | 110670.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 21.47 | 246.89 | 02-JAN-02:10 | 1608.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.29 | 102.55 | 02-JAN-02:10 | 922.95 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 24.86 | 285.90 | 02-JAN-02:10 | 1862.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.07 | 118.75 | 02-JAN-02:10 | 1068.78 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 40.11 | 427.85 | 02-JAN-02:10 | 3099.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 27.64 | 251.12 | 02-JAN-02:10 | 2260.10 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 8.02 | 91.16 | 02-JAN-02:10 | 603.79 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.42 | 40.18 | 02-JAN-02:10 | 361.63 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.19 | 1010.42 | 02-JAN-02:10 | 5002.35 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.25 | 47.73 | 02-JAN-02:10 | 429.55 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 41.88 | 453.48 | 02-JAN-02:10 | 3217.63 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 27.54 | 250.26 | 02-JAN-02:10 | 2252.35 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 310.43 | 3578.21 | 02-JAN-02:10 | 23230.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 161.43 | 1466.79 | 02-JAN-02:10 | 13201.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 36.30 | 414.01 | 01-JAN-02:10 | 2585.65 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.01 | 203.29 | 01-JAN-02:10 | 1848.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 36.30 | 413.96 | 01-JAN-02:10 | 2585.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.01 | 203.27 | 01-JAN-02:10 | 1847.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 515.47 | 6348.95 | 01-JAN-02:10 | 35793.21 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 286.72 | 2427.49 | 01-JAN-02:10 | 22068.10 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 515.61 | 6350.69 | 01-JAN-02:10 | 35803.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 286.80 | 2428.15 | 01-JAN-02:10 | 22074.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 36.30 | 414.01 | 01-JAN-02:10 | 2585.65 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.01 | 203.29 | 01-JAN-02:10 | 1848.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 36.30 | 413.96 | 01-JAN-02:10 | 2585.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.01 | 203.27 | 01-JAN-02:10 | 1847.91 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 87.37 | 793.85 | 02-JAN-02:10 | 7144.64 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 87.37 | 793.85 | 02-JAN-02:10 | 7144.64 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 9.08 | 103.50 | 01-JAN-02:10 | 646.41 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.00 | 50.82 | 01-JAN-02:10 | 462.03 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 9.07 | 103.49 | 01-JAN-02:10 | 646.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.00 | 50.82 | 01-JAN-02:10 | 461.98 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 61.06 | 752.06 | 01-JAN-02:10 | 4239.83 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 33.96 | 287.54 | 01-JAN-02:10 | 2614.04 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 224.23 | 2688.78 | 02-JAN-02:10 | 10703.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 48.37 | 439.48 | 02-JAN-02:10 | 3955.32 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 224.23 | 2688.78 | 02-JAN-02:10 | 10703.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 48.37 | 439.48 | 02-JAN-02:10 | 3955.32 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 472.20 | 6790.65 | 02-JAN-02:10 | 19337.58 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.91 | 126.36 | 02-JAN-02:10 | 1137.23 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 23.12 | 210.04 | 02-JAN-02:10 | 1890.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 23.12 | 210.04 | 02-JAN-02:10 | 1890.37 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.31 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 73.09 | 272.72 | 02-FEB-23:30 | 3631.70 | 19-MAY-07:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 1759.08 | 3161.02 | 28-OCT-00:20 | 339579.54 | 04-AUG-16:00 |
LowTempRefrigeration:Refrigeration:Electricity | 21.96 | 0.00 | 01-JAN-11:10 | 1934.44 | 09-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 32.86 | -134.66 | 02-FEB-06:00 | 1181.30 | 16-MAY-07:30 |
WaterSystems:Electricity | 90.80 | 1087.06 | 07-JAN-02:00 | 4757.79 | 02-FEB-07:20 |
Water Heater:WaterSystems:Electricity | 90.80 | 1087.06 | 07-JAN-02:00 | 4757.79 | 02-FEB-07:20 |
Fans:Electricity | 1796.49 | 52142.75 | 19-AUG-05:10 | 85392.81 | 02-FEB-07:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2243.93 | 53007.01 | 19-AUG-05:10 | 104488.53 | 02-FEB-07:10 |
ExteriorEquipment:Electricity | 1011.27 | 7639.31 | 02-JAN-02:20 | 63968.34 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 33.10 | 556.81 | 19-JAN-02:20 | 1934.93 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
ElectricityPurchased:Plant | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
Cogeneration:ElectricityPurchased | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
ElectricityNet:Plant | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
Cogeneration:ElectricityNet | 8392.10 | 130160.47 | 22-SEP-01:40 | 627943.55 | 26-JUL-18:10 |
General:Fans:Electricity | 1796.49 | 52142.75 | 19-AUG-05:10 | 85392.81 | 02-FEB-07:10 |
ExteriorLights:Electricity | 245.92 | 0.00 | 01-JAN-08:00 | 15665.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 245.92 | 0.00 | 01-JAN-08:00 | 15665.55 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.63 | 971.40 | 01-JAN-00:10 | 971.40 | 01-JAN-00:10 |
HeatRecovery:Electricity | 414.34 | 0.00 | 19-MAR-11:20 | 17225.46 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1412.61 | 0.00 | 01-JAN-00:10 | 322225.98 | 04-AUG-16:00 |
General:Cooling:Electricity | 1412.61 | 0.00 | 01-JAN-00:10 | 322225.98 | 04-AUG-16:00 |
Pumps:Electricity | 200.84 | 249.24 | 27-SEP-17:20 | 13828.09 | 20-JUL-08:10 |
General:Pumps:Electricity | 200.84 | 249.24 | 27-SEP-17:20 | 13828.09 | 20-JUL-08:10 |
WIRED_LTG_ELECTRICITY | 49.12 | 0.00 | 01-JAN-00:10 | 3895.60 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 7687.80 | 60134.03 | 04-SEP-24:00 | 1219350.34 | 02-FEB-20:50 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 5898.94 | 28350.09 | 29-OCT-10:50 | 1138706.08 | 02-FEB-00:20 |
WaterSystems:Gas | 2283.22 | 18467.44 | 19-JAN-14:00 | 182781.20 | 03-FEB-22:00 |
Water Heater:WaterSystems:Gas | 2283.22 | 18467.44 | 19-JAN-14:00 | 182781.20 | 03-FEB-22:00 |
Heating:Gas | 3615.73 | 3875.06 | 19-APR-19:20 | 999812.26 | 02-FEB-06:00 |
Boiler:Heating:Gas | 3615.73 | 3875.06 | 19-APR-19:20 | 999812.26 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4556.44 | 0.00 | 01-JAN-00:10 | 961973.69 | 26-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 4556.44 | 0.00 | 01-JAN-00:10 | 961973.69 | 26-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 4556.44 | 0.00 | 01-JAN-00:10 | 961973.69 | 26-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:30 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 35636.79 | 275995.50 | 20-NOV-09:00 | 4201588.37 | 26-JUL-18:20 |
EnergyTransfer:Building | 5561.73 | 69409.99 | 06-JAN-12:50 | 433251.39 | 19-JAN-02:00 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 739.22 | 6042.99 | 04-FEB-11:30 | 40727.12 | 25-NOV-21:30 |
Refrigeration:EnergyTransfer | 182.33 | -95.78 | 02-FEB-04:00 | 10360.66 | 16-MAY-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.17 | -47.89 | 02-FEB-04:00 | 5180.33 | 16-MAY-07:30 |
EnergyTransfer:Plant | 14388.12 | 43307.97 | 28-OCT-00:20 | 2280423.64 | 26-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 65.57 | -403.98 | 02-FEB-06:00 | 2493.89 | 16-MAY-07:30 |
PlantLoopHeatingDemand:Facility | 3510.39 | 24099.25 | 14-SEP-22:10 | 873848.86 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 848.59 | 9900.56 | 05-SEP-00:10 | 63639.54 | 23-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 848.59 | 9900.56 | 05-SEP-00:10 | 63639.54 | 23-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 469.39 | 9.40 | 20-JAN-15:00 | 63892.18 | 19-JAN-06:00 |
Heating:EnergyTransfer | 296.84 | 0.00 | 13-JAN-12:20 | 195564.10 | 04-FEB-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.53 | 0.00 | 01-JAN-00:10 | 31213.26 | 04-FEB-14:00 |
Cooling:EnergyTransfer | 5173.72 | 10581.51 | 04-FEB-11:30 | 395535.52 | 05-JAN-22:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 465.87 | 0.00 | 06-JAN-10:50 | 63892.18 | 19-JAN-06:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.67 | 0.02 | 12-MAR-05:10 | 4110.27 | 20-JAN-08:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 7.35 | 0.00 | 02-JAN-09:40 | 4110.27 | 20-JAN-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 30.32 | 0.00 | 01-JAN-00:10 | 3949.38 | 20-OCT-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.37 | 0.01 | 21-JAN-00:50 | 4636.01 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.31 | 0.00 | 01-JAN-00:10 | 2869.66 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.06 | 0.00 | 05-JAN-08:40 | 4636.01 | 19-JAN-02:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 31.39 | 0.06 | 15-JAN-03:10 | 4943.34 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.56 | 0.00 | 01-JAN-00:10 | 4406.14 | 04-FEB-11:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.83 | 0.00 | 02-JAN-03:20 | 4943.34 | 19-JAN-02:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.93 | 0.01 | 11-NOV-22:00 | 2252.44 | 04-FEB-11:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.12 | 0.00 | 01-JAN-20:20 | 2252.44 | 04-FEB-11:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 7.81 | 0.00 | 01-JAN-00:10 | 1594.71 | 19-JAN-02:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 600.14 | 1490.98 | 04-FEB-11:40 | 49663.09 | 05-JAN-22:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 2481.49 | 06-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 600.14 | 729.94 | 04-FEB-11:30 | 49663.09 | 05-JAN-22:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 224.64 | 0.30 | 26-DEC-12:10 | 18814.96 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.98 | 0.00 | 01-JAN-00:10 | 10119.66 | 20-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 222.66 | 0.00 | 01-JAN-14:20 | 18814.96 | 19-JAN-02:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 857.92 | 32.21 | 06-FEB-03:00 | 88719.38 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 4.17 | 0.00 | 01-JAN-00:10 | 44878.10 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 853.75 | 0.00 | 05-JAN-08:40 | 88719.38 | 19-JAN-02:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 64.96 | 0.01 | 30-NOV-11:50 | 11693.29 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 25.97 | 0.00 | 01-JAN-08:10 | 7837.59 | 04-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.99 | 0.00 | 01-JAN-00:10 | 11693.29 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 65.54 | 0.03 | 25-FEB-17:50 | 11514.54 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 30.92 | 0.00 | 01-JAN-08:10 | 8645.14 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 34.62 | 0.00 | 01-JAN-00:10 | 11514.54 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 433.10 | 1.14 | 11-JAN-02:10 | 62676.91 | 20-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 15.76 | 0.00 | 01-JAN-00:10 | 24841.84 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 417.34 | 0.00 | 01-JAN-01:30 | 62676.91 | 20-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 493.62 | 0.74 | 22-FEB-10:10 | 78692.71 | 18-JUN-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 49.93 | 0.00 | 01-JAN-00:10 | 49796.71 | 04-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 443.69 | 0.00 | 01-JAN-04:00 | 78692.71 | 18-JUN-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 64.09 | 0.04 | 07-NOV-00:50 | 10255.84 | 25-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 25.99 | 0.00 | 01-JAN-08:10 | 8117.46 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 38.10 | 0.00 | 01-JAN-00:10 | 10255.84 | 25-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.58 | 0.19 | 23-MAY-03:50 | 10272.50 | 25-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.96 | 0.00 | 01-JAN-08:10 | 9003.30 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 33.62 | 0.00 | 01-JAN-00:10 | 10272.50 | 25-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 127.70 | 0.13 | 24-NOV-12:50 | 19479.48 | 26-NOV-07:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 30.51 | 0.00 | 02-JAN-11:00 | 14564.96 | 04-FEB-14:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 97.20 | 0.00 | 01-JAN-00:10 | 19479.48 | 26-NOV-07:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.92 | 0.02 | 18-MAY-00:30 | 3269.31 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.98 | 0.00 | 01-JAN-08:10 | 2352.36 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.94 | 0.00 | 01-JAN-00:10 | 3269.31 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.35 | 0.02 | 09-NOV-02:10 | 3232.82 | 25-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.58 | 0.00 | 01-JAN-08:10 | 2443.59 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.77 | 0.00 | 01-JAN-00:10 | 3232.82 | 25-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 94.04 | 0.33 | 05-NOV-05:40 | 14960.96 | 04-NOV-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 23.81 | 0.00 | 01-JAN-08:10 | 11037.95 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 70.24 | 0.00 | 01-JAN-00:10 | 14960.96 | 04-NOV-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 498.14 | 24.79 | 06-JAN-14:10 | 40104.66 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.40 | 0.00 | 01-JAN-00:10 | 12909.24 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 497.74 | 0.00 | 06-JAN-10:50 | 40104.66 | 19-JAN-02:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 535.64 | 30.89 | 20-JAN-09:50 | 42248.23 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.37 | 0.00 | 01-JAN-00:10 | 13024.42 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 535.27 | 0.00 | 06-JAN-10:50 | 42248.23 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 435.85 | 06-JAN-10:50 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 648.05 | 4333.97 | 06-JAN-10:50 | 38160.90 | 25-NOV-21:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 69.34 | 0.03 | 04-DEC-12:20 | 10801.07 | 04-FEB-11:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 20.63 | 0.00 | 02-JAN-11:00 | 10801.07 | 04-FEB-11:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 48.71 | 0.00 | 01-JAN-00:10 | 5926.24 | 19-JAN-02:00 |
WaterSystems:EnergyTransfer | 848.59 | 9900.56 | 05-SEP-00:10 | 63639.54 | 23-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 848.59 | 9900.56 | 05-SEP-00:10 | 63639.54 | 23-FEB-07:30 |
EnergyTransfer:HVAC | 15686.94 | 33348.66 | 21-SEP-17:40 | 1616787.23 | 04-AUG-16:00 |
HeatingCoils:EnergyTransfer | 2661.80 | 3159.15 | 08-SEP-21:00 | 818221.86 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 2661.80 | 3159.15 | 08-SEP-21:00 | 818221.86 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 2661.80 | 3159.15 | 08-SEP-21:00 | 818221.86 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 4556.44 | 0.00 | 01-JAN-00:10 | 961973.69 | 26-JUL-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 7558.50 | 0.00 | 05-JAN-08:00 | 918533.46 | 19-JAN-01:40 |
HeatRecoveryForCooling:EnergyTransfer | 910.19 | 0.00 | 01-JAN-00:10 | 664350.25 | 04-AUG-13:00 |
Boilers:EnergyTransfer | 2629.94 | 2327.96 | 19-APR-19:20 | 813660.79 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 4702.91 | 0.00 | 01-JAN-00:10 | 971842.44 | 26-JUL-18:20 |
HeatRejection:EnergyTransfer | 6115.52 | 0.00 | 01-JAN-00:10 | 1261826.19 | 26-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.526 | -465.868 | 0.000 | 0.000 | 160.278 | 208.116 | 150.259 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -56.311 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 7.352 | -30.317 | 0.000 | 0.000 | 16.318 | 11.286 | 10.186 | 20.876 | 0.000 | 0.365 | 0.000 | 0.000 | -13.801 | 0.000 | -11.418 | -10.848 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.315 | -39.058 | 0.000 | 0.000 | 18.860 | 13.070 | 11.795 | 0.000 | 0.000 | 0.078 | 0.000 | 0.000 | 0.000 | 0.000 | -2.395 | -2.663 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.006 | -600.137 | 0.000 | 0.000 | 12.415 | 5.253 | 658.148 | 0.000 | 0.000 | 0.262 | 0.000 | 0.000 | 0.000 | 0.000 | -7.441 | -68.505 |
CAFE_FLR_1 | 0.000 | 0.000 | 1.979 | -222.665 | 0.000 | 0.000 | 214.115 | 27.543 | 14.341 | 58.529 | 0.000 | 0.931 | 0.000 | 0.000 | -38.818 | 0.000 | -28.844 | -27.112 |
LOBBY_FLR_1 | 0.000 | 0.000 | 4.170 | -853.757 | 0.000 | 0.000 | 633.468 | 161.431 | 149.002 | 77.581 | 0.000 | 1.859 | 0.000 | 0.000 | -51.814 | 0.000 | -57.635 | -64.305 |
ROOM_1_FLR_3 | 25.973 | -23.443 | 0.000 | -15.547 | 0.000 | 0.000 | 9.761 | 24.012 | 12.292 | 39.222 | 0.000 | 0.628 | 0.000 | 0.000 | -34.367 | 0.000 | -14.430 | -24.100 |
ROOM_2_FLR_3 | 30.917 | -19.328 | 0.000 | -15.296 | 0.000 | 0.000 | 9.785 | 24.009 | 12.291 | 28.563 | 0.000 | 0.599 | 0.000 | 0.000 | -36.450 | 0.000 | -14.279 | -20.811 |
ROOM_3_MULT19_FLR_3 | 15.759 | -174.737 | 0.000 | -242.604 | 0.000 | 0.000 | 0.000 | 286.718 | 228.754 | 238.697 | 0.000 | 3.404 | 0.010 | 0.000 | -194.818 | 0.000 | -98.688 | -62.485 |
ROOM_4_MULT19_FLR_3 | 49.933 | -232.544 | 0.000 | -211.136 | 0.000 | 0.000 | 185.323 | 286.797 | 228.817 | 67.708 | 0.000 | 7.180 | 0.000 | 0.000 | -209.683 | 0.000 | -84.122 | -88.272 |
ROOM_5_FLR_3 | 25.987 | -22.486 | 0.000 | -15.615 | 0.000 | 0.000 | 9.756 | 24.012 | 12.292 | 37.903 | 0.000 | 0.629 | 0.000 | 0.000 | -33.760 | 0.000 | -14.473 | -24.244 |
ROOM_6_FLR_3 | 30.962 | -18.243 | 0.000 | -15.377 | 0.000 | 0.000 | 9.780 | 24.009 | 12.291 | 27.076 | 0.000 | 0.599 | 0.000 | 0.000 | -35.688 | 0.000 | -14.321 | -21.087 |
ROOM_1_FLR_6 | 8.981 | -7.064 | 0.000 | -3.873 | 0.000 | 0.000 | 2.441 | 6.003 | 3.073 | 9.731 | 0.000 | 0.169 | 0.000 | 0.000 | -8.637 | 0.000 | -3.649 | -7.175 |
ROOM_2_FLR_6 | 10.576 | -5.954 | 0.000 | -3.818 | 0.000 | 0.000 | 2.446 | 6.002 | 3.073 | 7.076 | 0.000 | 0.159 | 0.000 | 0.000 | -9.161 | 0.000 | -3.609 | -6.791 |
ROOM_3_MULT9_FLR_6 | 23.807 | -44.654 | 0.000 | -25.581 | 0.000 | 0.000 | 21.875 | 33.963 | 27.097 | 52.324 | 0.000 | 1.180 | 0.000 | 0.000 | -40.163 | 0.000 | -17.824 | -32.025 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.402 | -497.738 | 0.000 | 0.000 | 366.244 | 48.368 | 175.857 | 8.105 | 0.000 | 0.254 | 0.000 | 0.000 | -23.405 | 0.000 | -8.434 | -69.653 |
DINING_FLR_6 | 0.000 | 0.000 | 0.368 | -535.273 | 0.000 | 0.000 | 365.240 | 48.368 | 175.857 | 7.963 | 0.000 | 0.253 | 0.000 | 0.000 | -23.804 | 0.000 | -8.453 | -30.519 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -648.046 | 0.000 | 0.000 | 31.367 | 13.907 | 556.656 | 18.956 | 0.000 | 0.157 | 50.808 | 0.000 | -15.835 | 0.000 | -7.970 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 1.561 | -29.827 | 0.000 | 0.000 | 0.000 | 27.638 | 12.472 | 0.000 | 0.000 | 0.171 | 0.000 | 0.000 | 0.000 | 0.000 | -5.257 | -6.757 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.123 | -7.810 | 0.000 | 0.000 | 0.000 | 4.422 | 3.598 | 0.000 | 0.000 | 0.119 | 0.202 | 0.000 | 0.000 | 0.000 | -3.655 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 30.506 | -97.196 | 0.000 | 0.000 | 0.000 | 87.369 | 0.000 | 35.162 | 0.000 | 0.520 | 1.014 | 0.000 | -41.060 | 0.000 | -16.314 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 20.634 | -48.709 | 0.000 | 0.000 | 0.000 | 23.117 | 0.000 | 17.462 | 0.000 | 0.225 | 12.716 | 0.000 | -18.234 | 0.000 | -7.211 | -0.000 |
Total Facility | 222.896 | -548.453 | 73.942 | -4625.249 | 0.000 | 0.000 | 2069.471 | 1395.412 | 2458.149 | 752.934 | 0.000 | 19.741 | 64.756 | 0.000 | -829.499 | 0.000 | -430.421 | -623.663 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -67072.39 | 0.00 | 0.00 | 8319.23 | 2836.47 | 2661.53 | 0.00 | 0.00 | 0.00 | 53255.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-OCT-13:10 | 0.00 | 0.00 | 0.00 | -3949.47 | 0.00 | 0.00 | 159.81 | 256.37 | 252.59 | 6606.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.34 | -3300.72 |
RETAIL_2_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -5050.98 | 0.00 | 0.00 | 1006.08 | 178.13 | 208.93 | 0.00 | 0.00 | 0.00 | 3893.06 | 0.00 | -0.00 | 0.00 | -235.22 | 0.00 |
LAUNDRY_FLR_1 | 25-NOV-21:21 | 0.00 | 0.00 | 0.00 | -56949.45 | 0.00 | 0.00 | 604.49 | 334.10 | 37304.74 | 0.00 | 0.00 | 0.00 | 19347.88 | 0.00 | -0.00 | 0.00 | -641.76 | 0.00 |
CAFE_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -23281.29 | 0.00 | 0.00 | 11811.70 | 375.39 | 254.02 | 0.00 | 0.00 | 0.00 | 18640.63 | 0.00 | -5049.13 | 0.00 | -2751.32 | 0.00 |
LOBBY_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -98669.74 | 0.00 | 0.00 | 33674.26 | 2200.19 | 2639.27 | 0.00 | 0.00 | 0.00 | 72668.73 | 0.00 | -6857.61 | 0.00 | -5655.10 | 0.00 |
ROOM_1_FLR_3 | 20-SEP-15:01 | 0.00 | -14170.66 | 0.00 | -702.22 | 0.00 | 0.00 | 235.28 | 517.48 | 273.93 | 9561.58 | 0.00 | 0.00 | 4370.41 | 0.00 | -0.00 | 0.00 | -85.81 | 0.00 |
ROOM_2_FLR_3 | 06-MAY-15:01 | 0.00 | -13878.73 | 0.00 | -694.89 | 0.00 | 0.00 | 130.71 | 609.81 | 305.51 | 8815.95 | 0.00 | 0.00 | 5024.68 | 0.00 | -0.00 | 0.00 | -313.04 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-OCT-12:30 | 0.00 | -52389.30 | 0.00 | -10286.63 | 0.00 | 0.00 | 0.00 | 6179.07 | 5097.90 | 84013.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -266.78 | -32347.73 |
ROOM_4_MULT19_FLR_3 | 06-MAY-15:01 | 0.00 | -79575.81 | 0.00 | -9266.08 | 0.00 | 0.00 | 2550.52 | 7284.46 | 5687.67 | 7574.03 | 0.00 | 0.00 | 70571.33 | 0.00 | -0.00 | 0.00 | -4826.13 | 0.00 |
ROOM_5_FLR_3 | 20-SEP-15:01 | 0.00 | -12673.70 | 0.00 | -695.35 | 0.00 | 0.00 | 235.28 | 517.48 | 273.93 | 2621.69 | 0.00 | 0.00 | 9789.37 | 0.00 | -0.00 | 0.00 | -68.71 | 0.00 |
ROOM_6_FLR_3 | 06-MAY-15:01 | 0.00 | -12501.56 | 0.00 | -686.35 | 0.00 | 0.00 | 130.71 | 609.81 | 305.51 | 1328.49 | 0.00 | 0.00 | 11103.42 | 0.00 | -0.00 | 0.00 | -290.04 | 0.00 |
ROOM_1_FLR_6 | 20-SEP-15:01 | 0.00 | -3712.03 | 0.00 | -175.95 | 0.00 | 0.00 | 58.82 | 129.37 | 68.48 | 2376.56 | 0.00 | 0.00 | 1285.44 | 0.00 | -0.00 | 0.00 | -30.69 | 0.00 |
ROOM_2_FLR_6 | 06-MAY-15:01 | 0.00 | -3631.93 | 0.00 | -174.02 | 0.00 | 0.00 | 32.68 | 152.45 | 76.38 | 2188.25 | 0.00 | 0.00 | 1456.05 | 0.00 | -0.00 | 0.00 | -99.86 | 0.00 |
ROOM_3_MULT9_FLR_6 | 20-SEP-15:01 | 0.00 | -15091.24 | 0.00 | -1157.36 | 0.00 | 0.00 | 529.38 | 731.93 | 603.86 | 6152.51 | 0.00 | 0.00 | 8599.20 | 0.00 | -0.00 | 0.00 | -368.28 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -47348.19 | 0.00 | 0.00 | 20115.17 | 659.22 | 2249.30 | 0.00 | 0.00 | 0.00 | 27928.27 | 0.00 | -2805.81 | 0.00 | -797.96 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -50025.79 | 0.00 | 0.00 | 20089.22 | 659.22 | 2249.30 | 0.00 | 0.00 | 0.00 | 30650.71 | 0.00 | -2824.69 | 0.00 | -797.97 | 0.00 |
KITCHEN_FLR_6 | 25-NOV-21:21 | 0.00 | 0.00 | 0.00 | -43980.57 | 0.00 | 0.00 | 1541.91 | 884.51 | 19460.75 | 0.00 | 0.00 | 0.00 | 24715.09 | 0.00 | -1953.36 | 0.00 | -668.32 | 0.00 |
MECH_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -5252.91 | 0.00 | 0.00 | 0.00 | 376.68 | 220.91 | 0.00 | 0.00 | 0.00 | 5178.79 | 0.00 | -0.00 | 0.00 | -523.47 | 0.00 |
STORAGE_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -1689.56 | 0.00 | 0.00 | 0.00 | 60.27 | 63.73 | 0.00 | 0.00 | 0.00 | 1931.71 | 0.00 | -0.00 | 0.00 | -366.15 | 0.00 |
CORRIDOR_FLR_3 | 26-NOV-06:55 | 0.00 | 0.00 | 0.00 | -19500.91 | 0.00 | 0.00 | 0.00 | 2381.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23958.66 | 0.00 | -5109.59 | 0.00 | -1729.71 | 0.00 |
CORRIDOR_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -6508.27 | 0.00 | 0.00 | 0.00 | 315.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9336.67 | 0.00 | -2428.51 | 0.00 | -714.96 | 0.00 |
Total Facility | 19-JAN-01:51 | 0.00 | 140733.98 | 0.00 | -488805.71 | 0.00 | 0.00 | 111440.66 | 18628.67 | 37257.04 | 0.00 | 0.00 | 0.00 | 322466.28 | 0.00 | -103795.39 | 0.00 | -37925.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-14:00 | 0.00 | 0.00 | 31214.06 | -0.00 | 0.00 | 0.00 | 3722.10 | 4727.44 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -43389.74 |
RETAIL_1_FLR_1 | 20-JAN-08:61 | 0.00 | 0.00 | 4344.55 | -0.00 | 0.00 | 0.00 | 454.03 | 410.20 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1319.27 | 0.00 | -972.29 | -3278.07 |
RETAIL_2_FLR_1 | 04-FEB-11:31 | 0.00 | 0.00 | 2927.71 | -0.00 | 0.00 | 0.00 | 438.80 | 296.88 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -171.34 | -3784.55 |
LAUNDRY_FLR_1 | 06-JAN-10:41 | 0.00 | 0.00 | 15249.91 | -0.00 | 0.00 | 0.00 | 192.08 | 119.32 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -609.00 | -31273.13 |
CAFE_FLR_1 | 20-JAN-08:61 | 0.00 | 0.00 | 11763.32 | -0.00 | 0.00 | 0.00 | 5728.80 | 1001.05 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3816.63 | 0.00 | -2540.63 | -12643.93 |
LOBBY_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 46534.13 | -0.00 | 0.00 | 0.00 | 14689.47 | 3666.98 | 3694.97 | 24556.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4353.81 | -88787.84 |
ROOM_1_FLR_3 | 26-NOV-09:01 | 9474.37 | 272.90 | 0.00 | -272.90 | 0.00 | 0.00 | 163.32 | 1034.95 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -978.37 | 0.00 | -1292.28 | -9055.22 |
ROOM_2_FLR_3 | 26-NOV-09:01 | 9504.53 | 269.03 | 0.00 | -269.03 | 0.00 | 0.00 | 163.32 | 1034.83 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2833.70 | 0.00 | -1290.52 | -7231.62 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 24840.48 | 28251.31 | 0.00 | -28251.31 | 0.00 | 0.00 | 0.00 | 2427.49 | 3921.46 | 0.00 | 0.00 | 0.00 | 1337.20 | 0.00 | -24888.36 | 0.00 | -7638.27 | 0.00 |
ROOM_4_MULT19_FLR_3 | 04-FEB-16:02 | 52125.66 | 3591.41 | 0.00 | -3591.41 | 0.00 | 0.00 | 3103.17 | 7284.46 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17445.61 | 0.00 | -6311.97 | -44443.39 |
ROOM_5_FLR_3 | 04-FEB-19:02 | 8994.10 | 273.62 | 0.00 | -273.62 | 0.00 | 0.00 | 353.88 | 1848.13 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3959.47 | 0.00 | -1207.19 | -6545.70 |
ROOM_6_FLR_3 | 04-FEB-16:02 | 9183.73 | 262.86 | 0.00 | -262.86 | 0.00 | 0.00 | 163.33 | 609.81 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3197.48 | 0.00 | -1189.32 | -5875.58 |
ROOM_1_FLR_6 | 26-NOV-09:01 | 2708.99 | 68.57 | 0.00 | -68.57 | 0.00 | 0.00 | 40.83 | 258.74 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -255.20 | 0.00 | -323.77 | -2592.91 |
ROOM_2_FLR_6 | 26-NOV-09:01 | 2717.99 | 67.60 | 0.00 | -67.60 | 0.00 | 0.00 | 40.83 | 258.71 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -716.62 | 0.00 | -323.32 | -2140.88 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 11664.44 | 578.93 | 0.00 | -578.93 | 0.00 | 0.00 | 332.99 | 862.63 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4243.75 | 0.00 | -1397.33 | -7892.52 |
BANQUET_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 13876.24 | -0.00 | 0.00 | 0.00 | 8417.76 | 1098.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -901.58 | 0.00 | -666.41 | -28572.61 |
DINING_FLR_6 | 06-JAN-10:41 | 0.00 | 0.00 | 14557.92 | -0.00 | 0.00 | 0.00 | 5557.92 | 1098.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1373.61 | 0.00 | -682.48 | -25906.35 |
KITCHEN_FLR_6 | 06-JAN-10:41 | 0.00 | 0.00 | 3951.49 | -0.00 | 0.00 | 0.00 | 479.11 | 315.90 | 24459.16 | 1216.77 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -654.38 | -29768.03 |
MECH_FLR_1 | 04-FEB-11:31 | 0.00 | 0.00 | 4457.02 | -0.00 | 0.00 | 0.00 | 0.00 | 627.81 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -351.05 | -5043.04 |
STORAGE_FLR_1 | 04-FEB-11:53 | 0.00 | 0.00 | 2262.11 | -0.00 | 0.00 | 0.00 | 0.00 | 100.45 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -241.97 | -2209.81 |
CORRIDOR_FLR_3 | 04-FEB-14:00 | 0.00 | 0.00 | 14565.34 | -0.00 | 0.00 | 0.00 | 0.00 | 1984.62 | 0.00 | 6520.39 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1236.47 | -21833.88 |
CORRIDOR_FLR_6 | 04-FEB-11:31 | 0.00 | 0.00 | 10856.50 | -0.00 | 0.00 | 0.00 | 0.00 | 525.10 | 0.00 | 4586.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -508.98 | -15459.55 |
Total Facility | 04-FEB-16:02 | 54144.62 | 30645.28 | 115812.26 | -30645.28 | 0.00 | 0.00 | 40188.09 | 33617.82 | 78917.49 | 27574.17 | 0.00 | 0.00 | 0.00 | 0.00 | -26133.10 | 0.00 | -33208.76 | -290912.60 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.3272 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 21.8360 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.8360 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 21.8360 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7321 | 2.7321 | 2.6720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3368 | 0.3368 | 0.3294 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2495 | 0.2495 | 0.2440 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4167 | 3.4167 | 3.3415 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4593 | 1.4593 | 1.4272 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8868 | 4.8868 | 4.7793 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2848 | 2.2848 | 2.2345 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4024 | 2.4024 | 2.3495 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4044 | 2.4044 | 2.3515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2827 | 0.2827 | 0.2765 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1168 | 0.1168 | 0.1143 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 1.1608 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5680 | 0.5680 | 0.5555 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.3272 | 21.8360 | 22.3272 | 21.8360 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6720 | 2.6720 | 2.6720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3294 | 0.3294 | 0.3294 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2440 | 0.2440 | 0.2440 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3415 | 3.3415 | 3.3415 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4272 | 1.4272 | 1.4272 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7793 | 4.7793 | 4.7793 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2345 | 2.2345 | 2.2345 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3495 | 2.3495 | 2.3495 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3515 | 2.3515 | 2.3515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2765 | 0.2765 | 0.2765 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1143 | 0.1143 | 0.1143 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1608 | 1.1608 | 1.1608 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5555 | 0.5555 | 0.5555 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.8360 | 21.8360 | 21.8360 | 21.8360 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 750.67 |
Number of hours cooling loads not met | 132.50 |
Number of hours not met | 882.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 3615.73 | 999812.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1412.61 | 322225.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1395.41 | 110670.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 245.92 | 15665.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 33.10 | 1934.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.63 | 971.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1796.49 | 85392.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 200.84 | 13828.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 414.34 | 17225.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.80 | 4757.79 | 2283.22 | 182781.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 21.96 | 1934.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.86 | 1181.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1824.40 | 8392.10 |
Natural Gas | 1788.85 | 7687.80 |
Additional | 0.00 | 0.00 |
Total | 3613.25 | 16079.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 122.99 |
Space Heating | 0.00 |
Space Cooling | 124.51 |
Fans (All) | 158.35 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 739.70 |
Subtotal | 739.70 |
Natural Gas [MJ/m2] | |
Space Heating | 318.70 |
Service Water Heating | 201.25 |
Miscellaneous (All) | 677.62 |
Subtotal | 677.62 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.68 |
Space Heating | 22.49 |
Space Cooling | 8.78 |
Fans (All) | 11.17 |
Service Water Heating | 14.76 |
Receptacle Equipment | 22.02 |
Miscellaneous | 12.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 3599. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2869. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.845233E+12 |
February | 0.000 | 0.594724E+12 |
March | 0.000 | 0.254000E+12 |
April | 0.000 | 0.169527E+12 |
May | 0.000 | 0.159121E+12 |
June | 0.000 | 0.170811E+12 |
July | 0.000 | 0.189699E+12 |
August | 0.000 | 0.176084E+12 |
September | 0.000 | 0.141395E+12 |
October | 0.000 | 0.119853E+12 |
November | 0.000 | 0.309576E+12 |
December | 0.000 | 0.485706E+12 |
Annual Sum or Average | 0.361573E+13 | |
Minimum of Months | 0.000 | 0.119853E+12 |
Maximum of Months | 0.000 | 0.845233E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442661E+11 | 67059.34 | 19-JAN-01:51 | -23.9 | -24.0 | 0.556544E+10 | 3814.81 | 04-JAN-22:10 | -17.1 | -17.4 |
February | 0.339043E+11 | 53609.09 | 01-FEB-08:00 | -32.2 | -32.3 | 0.453451E+10 | 3752.83 | 17-FEB-22:10 | -13.4 | -14.0 |
March | 0.313866E+11 | 18396.60 | 28-MAR-20:00 | 11.70 | 8.26 | 0.613379E+10 | 3709.55 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.279953E+11 | 18059.53 | 12-APR-19:30 | 11.65 | 8.93 | 0.586636E+10 | 3655.64 | 06-APR-21:10 | 5.60 | 1.66 |
May | 0.318874E+11 | 19334.37 | 10-MAY-21:00 | 13.90 | 13.61 | 0.603658E+10 | 3683.96 | 02-MAY-21:10 | 6.70 | 2.78 |
June | 0.350815E+11 | 21016.63 | 06-JUN-19:30 | 15.25 | 14.23 | 0.582168E+10 | 3688.83 | 05-JUN-21:10 | 11.70 | 11.34 |
July | 0.396198E+11 | 22309.17 | 10-JUL-20:00 | 17.20 | 14.78 | 0.602331E+10 | 3594.97 | 10-JUL-21:10 | 15.92 | 14.26 |
August | 0.436032E+11 | 24194.90 | 25-AUG-21:00 | 19.40 | 17.91 | 0.609226E+10 | 3662.88 | 24-AUG-21:10 | 15.40 | 14.12 |
September | 0.442860E+11 | 25605.09 | 07-SEP-21:00 | 22.80 | 16.43 | 0.597905E+10 | 3933.02 | 29-SEP-21:10 | 2.62 | 0.96 |
October | 0.463536E+11 | 22823.61 | 20-OCT-18:10 | 17.02 | 10.75 | 0.629324E+10 | 3956.26 | 18-OCT-21:10 | -0.1 | -1.4 |
November | 0.443815E+11 | 64916.66 | 25-NOV-21:32 | -24.0 | -24.4 | 0.600362E+10 | 3949.51 | 01-NOV-21:10 | 6.60 | 5.09 |
December | 0.431019E+11 | 19270.18 | 01-DEC-22:00 | -3.9 | -4.7 | 0.622477E+10 | 3909.51 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.465867E+12 | 0.705746E+11 | ||||||||
Minimum of Months | 0.279953E+11 | 18059.53 | -32.2 | -32.3 | 0.453451E+10 | 3594.97 | -17.1 | -17.4 | ||
Maximum of Months | 0.463536E+11 | 67059.34 | 22.80 | 17.91 | 0.629324E+10 | 3956.26 | 15.92 | 14.26 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776409E+09 | 3661.13 | 19-JAN-01:51 | -23.9 | -24.0 | 0.550070E+09 | 364.27 | 18-JAN-04:30 | -2.5 | -2.7 |
February | 0.813704E+09 | 2846.06 | 08-FEB-13:30 | 2.50 | 1.29 | 0.483272E+09 | 364.22 | 24-FEB-01:39 | 0.37 | -1.1 |
March | 0.129243E+10 | 3029.71 | 25-MAR-14:10 | 17.07 | 9.75 | 0.622888E+09 | 364.23 | 27-MAR-03:30 | 1.70 | 0.37 |
April | 0.209176E+10 | 3595.89 | 15-APR-13:20 | 28.67 | 20.38 | 0.601082E+09 | 364.24 | 25-APR-03:00 | 2.20 | -0.9 |
May | 0.327333E+10 | 2859.24 | 05-MAY-13:00 | 23.30 | 18.17 | 0.620804E+09 | 364.19 | 25-MAY-03:39 | 10.00 | 9.66 |
June | 0.416169E+10 | 3112.97 | 26-JUN-18:07 | 29.72 | 22.35 | 0.601879E+09 | 364.20 | 03-JUN-04:00 | 5.60 | 5.31 |
July | 0.477850E+10 | 3157.42 | 30-JUL-12:00 | 26.70 | 21.50 | 0.619505E+09 | 364.19 | 15-JUL-02:09 | 20.50 | 19.98 |
August | 0.481038E+10 | 3353.75 | 29-AUG-13:30 | 23.60 | 16.38 | 0.622230E+09 | 364.19 | 26-AUG-03:30 | 18.30 | 17.19 |
September | 0.394701E+10 | 3821.11 | 07-SEP-13:10 | 31.78 | 18.09 | 0.602888E+09 | 364.21 | 29-SEP-01:00 | 0.00 | -0.7 |
October | 0.256433E+10 | 3949.38 | 20-OCT-13:10 | 21.93 | 12.66 | 0.623336E+09 | 364.22 | 16-OCT-04:19 | 1.57 | 0.63 |
November | 0.119179E+10 | 3468.47 | 04-NOV-13:10 | 13.98 | 6.79 | 0.590203E+09 | 364.24 | 24-NOV-01:19 | -9.3 | -9.7 |
December | 0.615795E+09 | 2967.89 | 03-DEC-13:00 | 5.60 | 2.40 | 0.617275E+09 | 364.24 | 06-DEC-01:19 | -8.9 | -10.8 |
Annual Sum or Average | 0.303171E+11 | 0.715543E+10 | ||||||||
Minimum of Months | 0.615795E+09 | 2846.06 | -23.9 | -24.0 | 0.483272E+09 | 364.19 | -9.3 | -10.8 | ||
Maximum of Months | 0.481038E+10 | 3949.38 | 31.78 | 22.35 | 0.623336E+09 | 364.27 | 20.50 | 19.98 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250729E+10 | 5049.65 | 19-JAN-01:51 | -23.9 | -24.0 | 0.643670E+09 | 443.02 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.245799E+10 | 3643.40 | 01-FEB-00:01 | -24.1 | -24.4 | 0.555256E+09 | 450.03 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.283850E+10 | 1909.97 | 19-MAR-21:00 | 15.00 | 11.82 | 0.724717E+09 | 456.88 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.316879E+10 | 2287.79 | 18-APR-19:10 | 20.22 | 15.85 | 0.701360E+09 | 461.44 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.372907E+10 | 2392.28 | 31-MAY-21:00 | 22.20 | 17.23 | 0.724681E+09 | 459.93 | 22-MAY-21:10 | 9.32 | 7.91 |
June | 0.392781E+10 | 2420.08 | 26-JUN-21:00 | 25.60 | 21.31 | 0.699624E+09 | 455.87 | 01-JUN-21:10 | 9.90 | 8.78 |
July | 0.420443E+10 | 2414.29 | 03-JUL-21:00 | 24.40 | 22.86 | 0.718405E+09 | 435.93 | 10-JUL-21:10 | 15.92 | 14.26 |
August | 0.416996E+10 | 2401.65 | 02-AUG-21:00 | 24.40 | 21.64 | 0.722984E+09 | 444.86 | 29-AUG-21:10 | 15.82 | 13.60 |
September | 0.374690E+10 | 2412.89 | 07-SEP-21:00 | 22.80 | 16.43 | 0.701060E+09 | 460.25 | 19-SEP-21:10 | 7.12 | 5.30 |
October | 0.336438E+10 | 2046.33 | 20-OCT-18:10 | 17.02 | 10.75 | 0.725307E+09 | 459.43 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.271099E+10 | 4722.98 | 25-NOV-21:32 | -24.0 | -24.4 | 0.687096E+09 | 459.86 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.223227E+10 | 1626.54 | 01-DEC-22:03 | -3.8 | -4.6 | 0.718205E+09 | 438.02 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.390584E+11 | 0.832236E+10 | ||||||||
Minimum of Months | 0.223227E+10 | 1626.54 | -24.1 | -24.4 | 0.555256E+09 | 435.93 | -3.8 | -4.6 | ||
Maximum of Months | 0.420443E+10 | 5049.65 | 25.60 | 22.86 | 0.725307E+09 | 461.44 | 15.92 | 14.26 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152080E+10 | 5252.13 | 19-JAN-01:51 | -23.9 | -24.0 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.138373E+10 | 3487.39 | 01-FEB-08:00 | -32.2 | -32.3 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.170185E+10 | 1904.84 | 28-MAR-20:00 | 11.70 | 8.26 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.231922E+10 | 2440.57 | 18-APR-19:50 | 18.68 | 15.34 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.321114E+10 | 2637.83 | 31-MAY-20:00 | 24.40 | 17.90 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.359958E+10 | 2680.86 | 26-JUN-20:00 | 26.70 | 21.51 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.389012E+10 | 2671.40 | 03-JUL-20:00 | 26.70 | 23.79 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.382657E+10 | 2667.81 | 03-AUG-20:00 | 25.00 | 23.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.321954E+10 | 2636.68 | 07-SEP-20:00 | 23.90 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.251866E+10 | 2178.80 | 20-OCT-19:40 | 15.37 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.175742E+10 | 5043.32 | 25-NOV-21:32 | -24.0 | -24.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.878740E+09 | 1546.13 | 04-DEC-21:00 | 1.70 | 0.04 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.298274E+11 | 0.00 | ||||||||
Minimum of Months | 0.878740E+09 | 1546.13 | -32.2 | -32.3 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.389012E+10 | 5252.13 | 26.70 | 23.79 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315652E+09 | 1689.37 | 19-JAN-01:51 | -23.9 | -24.0 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.140087E+09 | 1003.46 | 01-FEB-07:15 | -31.9 | -32.0 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.175796E+09 | 481.06 | 28-MAR-20:00 | 11.70 | 8.26 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.459545E+09 | 760.15 | 16-APR-20:00 | 23.30 | 18.48 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.954912E+09 | 851.13 | 31-MAY-20:00 | 24.40 | 17.90 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.125474E+10 | 953.50 | 26-JUN-19:50 | 26.97 | 21.56 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.140810E+10 | 919.18 | 03-JUL-19:10 | 28.03 | 24.15 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.135620E+10 | 893.62 | 03-AUG-20:00 | 25.00 | 23.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.994994E+09 | 844.16 | 07-SEP-20:00 | 23.90 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.490625E+09 | 589.37 | 20-OCT-20:00 | 15.00 | 9.89 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.252766E+09 | 1608.29 | 25-NOV-21:32 | -24.0 | -24.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 6203700.59 | 160.72 | 04-DEC-22:00 | 1.70 | 0.04 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.780961E+10 | 0.00 | ||||||||
Minimum of Months | 6203700.59 | 160.72 | -31.9 | -32.0 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.140810E+10 | 1689.37 | 28.03 | 24.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486998E+11 | 54228.11 | 05-JAN-21:51 | -23.9 | -24.2 | 0.451230E+09 | 393.06 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.442681E+11 | 38073.27 | 01-FEB-22:00 | -30.6 | -30.8 | 0.407883E+09 | 394.47 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.497909E+11 | 36192.46 | 28-MAR-20:00 | 11.70 | 8.26 | 0.518004E+09 | 396.83 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.491231E+11 | 37289.53 | 18-APR-20:00 | 18.30 | 15.20 | 0.494339E+09 | 398.64 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.522665E+11 | 38121.72 | 31-MAY-20:00 | 24.40 | 17.90 | 0.501687E+09 | 398.06 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.515258E+11 | 38211.65 | 26-JUN-20:00 | 26.70 | 21.51 | 0.469076E+09 | 396.74 | 01-JUN-21:10 | 9.90 | 8.78 |
July | 0.534460E+11 | 38107.21 | 03-JUL-20:00 | 26.70 | 23.79 | 0.472852E+09 | 354.71 | 11-JUL-21:10 | 15.92 | 14.61 |
August | 0.534391E+11 | 38123.60 | 03-AUG-20:00 | 25.00 | 23.43 | 0.481307E+09 | 358.58 | 16-AUG-21:10 | 15.50 | 13.14 |
September | 0.506080E+11 | 38131.47 | 07-SEP-20:00 | 23.90 | 17.03 | 0.480741E+09 | 397.72 | 25-SEP-21:10 | 10.00 | 6.67 |
October | 0.508060E+11 | 36597.35 | 20-OCT-20:00 | 15.00 | 9.89 | 0.514374E+09 | 397.64 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.480491E+11 | 56941.19 | 25-NOV-21:21 | -23.9 | -24.2 | 0.488353E+09 | 397.38 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.481138E+11 | 35194.36 | 04-DEC-21:00 | 1.70 | 0.04 | 0.513585E+09 | 391.70 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.600136E+12 | 0.579343E+10 | ||||||||
Minimum of Months | 0.442681E+11 | 35194.36 | -30.6 | -30.8 | 0.407883E+09 | 354.71 | -3.8 | -4.6 | ||
Maximum of Months | 0.534460E+11 | 56941.19 | 26.70 | 23.79 | 0.518004E+09 | 398.64 | 15.92 | 14.61 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108867E+11 | 23269.17 | 19-JAN-01:51 | -23.9 | -24.0 | 0.730303E+10 | 4826.27 | 13-JAN-22:19 | 1.83 | 0.64 |
February | 0.125280E+11 | 16541.77 | 01-FEB-00:01 | -24.1 | -24.4 | 0.642667E+10 | 4934.42 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.153383E+11 | 12460.90 | 25-MAR-14:00 | 16.70 | 9.60 | 0.819273E+10 | 5100.15 | 23-MAR-21:30 | 9.15 | 5.91 |
April | 0.178444E+11 | 14282.29 | 15-APR-13:00 | 28.30 | 20.27 | 0.791615E+10 | 5076.03 | 19-APR-21:19 | 7.43 | 3.85 |
May | 0.219740E+11 | 13375.45 | 31-MAY-21:05 | 21.80 | 16.81 | 0.818249E+10 | 5075.36 | 22-MAY-21:30 | 9.15 | 7.84 |
June | 0.238590E+11 | 13904.54 | 26-JUN-21:20 | 25.20 | 21.19 | 0.791753E+10 | 4999.75 | 01-JUN-21:30 | 9.70 | 8.80 |
July | 0.258198E+11 | 13894.43 | 25-JUL-21:20 | 25.93 | 21.29 | 0.814244E+10 | 4827.25 | 25-JUL-21:30 | 25.85 | 21.21 |
August | 0.260564E+11 | 13801.49 | 02-AUG-21:10 | 24.32 | 21.63 | 0.818595E+10 | 4982.85 | 29-AUG-22:10 | 14.40 | 12.80 |
September | 0.235243E+11 | 14786.98 | 16-SEP-13:10 | 28.48 | 18.06 | 0.792610E+10 | 5093.71 | 20-SEP-21:40 | 11.87 | 8.63 |
October | 0.202739E+11 | 15230.54 | 20-OCT-12:50 | 21.68 | 12.53 | 0.821669E+10 | 5197.88 | 24-OCT-21:19 | 9.80 | 5.67 |
November | 0.141649E+11 | 19628.03 | 25-NOV-21:21 | -23.9 | -24.2 | 0.777582E+10 | 5076.55 | 03-NOV-21:19 | 5.73 | 3.32 |
December | 0.103938E+11 | 12361.63 | 03-DEC-13:00 | 5.60 | 2.40 | 0.815497E+10 | 4789.55 | 27-DEC-05:40 | -9.2 | -9.7 |
Annual Sum or Average | 0.222664E+12 | 0.943406E+11 | ||||||||
Minimum of Months | 0.103938E+11 | 12361.63 | -24.1 | -24.4 | 0.642667E+10 | 4789.55 | -9.2 | -9.7 | ||
Maximum of Months | 0.260564E+11 | 23269.17 | 28.48 | 21.63 | 0.821669E+10 | 5197.88 | 25.85 | 21.21 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573276E+11 | 98639.19 | 19-JAN-01:51 | -23.9 | -24.0 | 0.218009E+11 | 15228.26 | 13-JAN-22:19 | 1.83 | 0.64 |
February | 0.553539E+11 | 71055.69 | 01-FEB-00:01 | -24.1 | -24.4 | 0.189220E+11 | 15401.60 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.642697E+11 | 38540.29 | 19-MAR-21:00 | 15.00 | 11.82 | 0.245622E+11 | 15694.79 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.688664E+11 | 44964.12 | 16-APR-20:10 | 23.12 | 18.42 | 0.238234E+11 | 15787.07 | 19-APR-21:19 | 7.43 | 3.85 |
May | 0.793512E+11 | 46887.68 | 31-MAY-21:10 | 21.80 | 16.81 | 0.246480E+11 | 15762.51 | 24-MAY-22:10 | 10.00 | 9.66 |
June | 0.829015E+11 | 47550.57 | 26-JUN-21:10 | 25.40 | 21.25 | 0.236886E+11 | 15647.31 | 01-JUN-21:19 | 9.80 | 8.79 |
July | 0.882372E+11 | 47291.23 | 25-JUL-21:20 | 25.93 | 21.29 | 0.242318E+11 | 14934.51 | 11-JUL-22:10 | 14.90 | 13.94 |
August | 0.881481E+11 | 47193.90 | 03-AUG-21:10 | 24.32 | 23.15 | 0.244620E+11 | 15262.61 | 15-AUG-22:10 | 13.22 | 12.93 |
September | 0.804450E+11 | 47364.45 | 07-SEP-21:10 | 22.43 | 16.37 | 0.238246E+11 | 15735.04 | 14-SEP-21:49 | 9.18 | 7.09 |
October | 0.741065E+11 | 40478.72 | 20-OCT-18:10 | 17.02 | 10.75 | 0.247182E+11 | 15805.49 | 11-OCT-21:00 | 9.30 | 4.81 |
November | 0.614392E+11 | 88293.92 | 25-NOV-21:21 | -23.9 | -24.2 | 0.232977E+11 | 15759.21 | 03-NOV-21:19 | 5.73 | 3.32 |
December | 0.533083E+11 | 32963.02 | 04-DEC-23:00 | 2.20 | 0.30 | 0.242427E+11 | 15012.22 | 01-DEC-22:19 | -3.7 | -4.5 |
Annual Sum or Average | 0.853755E+12 | 0.282222E+12 | ||||||||
Minimum of Months | 0.533083E+11 | 32963.02 | -24.1 | -24.4 | 0.189220E+11 | 14934.51 | -3.7 | -4.5 | ||
Maximum of Months | 0.882372E+11 | 98639.19 | 25.93 | 23.15 | 0.247182E+11 | 15805.49 | 14.90 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33490888.47 | 3340.30 | 12-JAN-16:02 | 2.62 | 1.03 | 92731799.53 | 56.69 | 26-JAN-05:10 | -17.1 | -17.5 |
February | 82495379.15 | 3573.97 | 25-FEB-16:01 | 5.50 | 2.73 | 83928972.54 | 56.69 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.234574E+09 | 3604.76 | 25-MAR-15:01 | 18.72 | 10.43 | 95242274.57 | 56.69 | 28-MAR-21:30 | 9.45 | 7.46 |
April | 0.703500E+09 | 3625.16 | 19-APR-15:01 | 11.70 | 7.43 | 93372847.96 | 56.69 | 16-APR-01:10 | 20.00 | 16.43 |
May | 0.112994E+10 | 3705.20 | 06-MAY-15:01 | 20.92 | 11.57 | 98041617.76 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.170245E+10 | 3547.58 | 29-JUN-15:02 | 29.50 | 20.45 | 95299085.95 | 56.70 | 29-JUN-21:40 | 23.67 | 18.92 |
July | 0.203701E+10 | 3565.34 | 05-JUL-15:02 | 27.80 | 20.25 | 98684482.65 | 56.70 | 27-JUL-21:10 | 20.92 | 17.78 |
August | 0.184589E+10 | 3568.74 | 04-AUG-15:02 | 33.90 | 25.47 | 98734915.33 | 56.70 | 22-AUG-21:10 | 22.02 | 19.96 |
September | 0.128502E+10 | 3718.29 | 20-SEP-15:01 | 22.12 | 11.87 | 94775190.60 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.489130E+09 | 3638.58 | 19-OCT-15:01 | 18.53 | 10.63 | 96678310.25 | 56.69 | 20-OCT-21:40 | 13.90 | 9.50 |
November | 0.160078E+09 | 3649.68 | 04-NOV-15:01 | 14.13 | 6.69 | 91400338.10 | 56.69 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 44241877.09 | 3375.34 | 02-DEC-16:01 | 4.95 | 2.78 | 93170448.26 | 56.69 | 11-DEC-00:10 | -21.7 | -22.1 |
Annual Sum or Average | 0.974781E+10 | 0.113206E+10 | ||||||||
Minimum of Months | 33490888.47 | 3340.30 | 2.62 | 1.03 | 83928972.54 | 56.69 | -21.7 | -22.1 | ||
Maximum of Months | 0.203701E+10 | 3718.29 | 33.90 | 25.47 | 98734915.33 | 56.70 | 23.67 | 19.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13566079.61 | 686.30 | 12-JAN-19:04 | 1.20 | -0.1 | 92344585.89 | 56.69 | 08-JAN-02:09 | -13.3 | -14.2 |
February | 42697310.38 | 3350.85 | 24-FEB-16:02 | 8.12 | 5.75 | 82857099.23 | 56.69 | 01-FEB-03:09 | -28.2 | -28.4 |
March | 0.151154E+09 | 3521.47 | 25-MAR-15:01 | 18.72 | 10.43 | 94353399.60 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.584860E+09 | 3551.36 | 19-APR-15:01 | 11.70 | 7.43 | 92913413.60 | 56.69 | 15-APR-23:00 | 20.00 | 16.36 |
May | 0.105570E+10 | 3643.45 | 06-MAY-15:01 | 20.92 | 11.57 | 97855946.44 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.165899E+10 | 3520.02 | 30-JUN-15:02 | 29.32 | 21.45 | 95263332.78 | 56.70 | 30-JUN-21:40 | 21.53 | 16.80 |
July | 0.196265E+10 | 3514.23 | 04-JUL-18:02 | 26.42 | 21.17 | 98647354.39 | 56.70 | 03-JUL-21:40 | 23.67 | 22.66 |
August | 0.170670E+10 | 3494.92 | 10-AUG-18:02 | 24.03 | 17.75 | 98644983.34 | 56.69 | 03-AUG-21:10 | 24.32 | 23.15 |
September | 0.106017E+10 | 3630.95 | 20-SEP-15:01 | 22.12 | 11.87 | 94391404.20 | 56.69 | 07-SEP-23:40 | 18.17 | 15.56 |
October | 0.300676E+09 | 3525.28 | 19-OCT-15:01 | 18.53 | 10.63 | 95583464.29 | 56.69 | 11-OCT-21:10 | 10.80 | 5.63 |
November | 99595856.23 | 3525.35 | 04-NOV-15:01 | 14.13 | 6.69 | 90679074.84 | 56.69 | 08-NOV-23:10 | 14.40 | 12.79 |
December | 19473546.84 | 693.94 | 01-DEC-16:03 | -2.1 | -4.2 | 92443361.28 | 56.69 | 12-DEC-23:19 | -13.3 | -13.7 |
Annual Sum or Average | 0.865622E+10 | 0.112598E+10 | ||||||||
Minimum of Months | 13566079.61 | 686.30 | -2.1 | -4.2 | 82857099.23 | 56.69 | -28.2 | -28.4 | ||
Maximum of Months | 0.196265E+10 | 3643.45 | 29.32 | 21.45 | 98647354.39 | 56.70 | 24.32 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131440E+09 | 370.29 | 30-JAN-10:40 | -27.1 | -27.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.211717E+09 | 496.78 | 08-FEB-13:40 | 2.60 | 1.30 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.292919E+09 | 568.23 | 24-MAR-12:50 | 12.12 | 6.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.405354E+09 | 677.29 | 15-APR-12:50 | 28.22 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.539272E+09 | 547.28 | 05-MAY-17:17 | 26.33 | 14.13 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.665643E+09 | 694.37 | 18-JUN-20:20 | 26.30 | 20.76 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.753238E+09 | 632.88 | 25-JUL-19:30 | 26.65 | 21.77 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.758682E+09 | 597.33 | 29-AUG-13:20 | 23.50 | 16.48 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.704776E+09 | 749.17 | 17-SEP-13:20 | 26.13 | 17.87 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.559880E+09 | 824.70 | 20-OCT-12:30 | 21.45 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.304407E+09 | 820.66 | 04-NOV-12:20 | 13.17 | 6.63 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.164023E+09 | 591.21 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.549135E+10 | 0.00 | ||||||||
Minimum of Months | 0.131440E+09 | 370.29 | -27.1 | -27.3 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.758682E+09 | 824.70 | 28.22 | 21.77 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66084570.89 | 685.19 | 01-JAN-09:02 | -3.2 | -3.4 | 93592646.19 | 56.69 | 17-JAN-22:10 | 4.68 | 2.60 |
February | 0.109374E+09 | 1038.44 | 25-FEB-09:02 | 0.78 | -0.3 | 84506701.55 | 56.69 | 13-FEB-22:10 | -2.3 | -2.9 |
March | 0.262108E+09 | 1104.49 | 25-MAR-18:02 | 14.82 | 10.04 | 95783821.64 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.457757E+09 | 1153.46 | 30-APR-18:01 | 15.22 | 9.03 | 93478810.05 | 56.69 | 26-APR-21:10 | 7.70 | 3.04 |
May | 0.722762E+09 | 1168.98 | 06-MAY-15:01 | 20.92 | 11.57 | 97671864.58 | 56.69 | 30-MAY-21:10 | 19.82 | 17.01 |
June | 0.892423E+09 | 1139.94 | 16-JUN-18:02 | 23.62 | 16.29 | 95045886.51 | 56.70 | 30-JUN-21:49 | 21.37 | 16.73 |
July | 0.967883E+09 | 1145.47 | 18-JUL-18:02 | 23.22 | 16.07 | 98211047.86 | 56.70 | 03-JUL-21:00 | 23.30 | 22.56 |
August | 0.903190E+09 | 1148.36 | 09-AUG-15:02 | 27.20 | 17.24 | 98180971.45 | 56.70 | 03-AUG-21:49 | 23.98 | 22.73 |
September | 0.692771E+09 | 1147.39 | 07-SEP-15:02 | 31.70 | 18.51 | 94390617.66 | 56.69 | 11-SEP-21:10 | 19.40 | 17.91 |
October | 0.441550E+09 | 1089.52 | 29-OCT-18:01 | 11.57 | 6.87 | 96557576.66 | 56.69 | 24-OCT-21:10 | 9.90 | 5.73 |
November | 0.242164E+09 | 1079.16 | 03-NOV-18:02 | 9.32 | 6.09 | 92285908.54 | 56.69 | 07-NOV-23:10 | 12.80 | 11.46 |
December | 79966486.92 | 753.70 | 02-DEC-09:01 | -0.2 | -1.7 | 94066204.31 | 56.69 | 04-DEC-22:30 | 1.95 | 0.17 |
Annual Sum or Average | 0.583803E+10 | 0.113377E+10 | ||||||||
Minimum of Months | 66084570.89 | 685.19 | -3.2 | -3.4 | 84506701.55 | 56.69 | -2.3 | -2.9 | ||
Maximum of Months | 0.967883E+09 | 1168.98 | 31.70 | 18.51 | 98211047.86 | 56.70 | 23.98 | 22.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30840990.78 | 957.08 | 12-JAN-09:03 | -4.1 | -4.6 | 92649166.48 | 56.69 | 06-JAN-00:40 | -25.4 | -25.6 |
February | 70213147.83 | 3130.30 | 24-FEB-09:01 | 3.07 | 0.60 | 83475266.13 | 56.69 | 01-FEB-03:09 | -28.2 | -28.4 |
March | 0.231799E+09 | 3253.57 | 24-MAR-15:01 | 12.43 | 6.31 | 95398640.61 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.613899E+09 | 3274.68 | 30-APR-15:01 | 15.18 | 8.64 | 93474466.14 | 56.69 | 15-APR-23:00 | 20.00 | 16.36 |
May | 0.118830E+10 | 3325.62 | 06-MAY-15:01 | 20.92 | 11.57 | 98476890.02 | 56.69 | 31-MAY-23:40 | 15.90 | 10.89 |
June | 0.171312E+10 | 3261.05 | 09-JUN-08:62 | 21.97 | 17.04 | 95558842.20 | 56.70 | 29-JUN-21:40 | 23.67 | 18.92 |
July | 0.197362E+10 | 3219.66 | 01-JUL-08:61 | 23.07 | 18.40 | 98935276.81 | 56.70 | 25-JUL-21:30 | 25.85 | 21.21 |
August | 0.176995E+10 | 3223.53 | 11-AUG-15:02 | 26.60 | 18.12 | 98982063.20 | 56.70 | 22-AUG-21:10 | 22.02 | 19.96 |
September | 0.128632E+10 | 3342.33 | 20-SEP-15:01 | 22.12 | 11.87 | 95076465.10 | 56.69 | 07-SEP-21:19 | 22.07 | 16.31 |
October | 0.449256E+09 | 3281.55 | 19-OCT-15:01 | 18.53 | 10.63 | 96833559.50 | 56.69 | 11-OCT-21:10 | 10.80 | 5.63 |
November | 0.151433E+09 | 3278.75 | 04-NOV-15:01 | 14.13 | 6.69 | 91375777.30 | 56.69 | 07-NOV-22:10 | 12.80 | 11.46 |
December | 46892782.20 | 2251.66 | 03-DEC-09:02 | -1.5 | -1.7 | 93096479.53 | 56.69 | 13-DEC-02:49 | -12.3 | -12.7 |
Annual Sum or Average | 0.952565E+10 | 0.113333E+10 | ||||||||
Minimum of Months | 30840990.78 | 957.08 | -4.1 | -4.6 | 83475266.13 | 56.69 | -28.2 | -28.4 | ||
Maximum of Months | 0.197362E+10 | 3342.33 | 26.60 | 18.40 | 98982063.20 | 56.70 | 25.85 | 21.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13478247.14 | 751.93 | 13-JAN-19:04 | 0.40 | -0.5 | 92267041.11 | 56.69 | 20-JAN-23:49 | -11.9 | -12.3 |
February | 35721229.60 | 3002.35 | 24-FEB-09:01 | 3.07 | 0.60 | 82265766.07 | 56.69 | 05-FEB-03:49 | -16.6 | -17.1 |
March | 0.149888E+09 | 3123.48 | 28-MAR-08:62 | 5.37 | 3.26 | 94488266.09 | 56.69 | 28-MAR-21:40 | 9.27 | 7.38 |
April | 0.500126E+09 | 3244.05 | 30-APR-15:01 | 15.18 | 8.64 | 92977454.43 | 56.69 | 13-APR-21:10 | 12.70 | 10.28 |
May | 0.110887E+10 | 3297.02 | 06-MAY-15:01 | 20.92 | 11.57 | 98348562.32 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.166772E+10 | 3212.56 | 24-JUN-08:61 | 21.38 | 16.07 | 95533306.25 | 56.70 | 26-JUN-21:00 | 24.40 | 20.94 |
July | 0.189686E+10 | 3206.74 | 01-JUL-08:61 | 23.07 | 18.40 | 98920392.32 | 56.70 | 14-JUL-21:10 | 22.70 | 20.22 |
August | 0.162531E+10 | 3174.28 | 09-AUG-08:62 | 21.05 | 16.08 | 98935759.46 | 56.70 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.105049E+10 | 3273.50 | 20-SEP-15:01 | 22.12 | 11.87 | 94788445.03 | 56.70 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.254624E+09 | 2865.46 | 08-OCT-08:62 | 5.03 | 3.00 | 95676519.83 | 56.69 | 10-OCT-21:10 | 10.67 | 9.78 |
November | 85014839.61 | 2060.44 | 04-NOV-08:62 | 2.77 | 0.70 | 90634491.51 | 56.69 | 07-NOV-22:49 | 12.80 | 11.46 |
December | 17337737.71 | 826.69 | 02-DEC-09:03 | -0.2 | -1.7 | 92417637.45 | 56.69 | 13-DEC-00:40 | -13.0 | -13.4 |
Annual Sum or Average | 0.840545E+10 | 0.112725E+10 | ||||||||
Minimum of Months | 13478247.14 | 751.93 | -0.2 | -1.7 | 82265766.07 | 56.69 | -16.6 | -17.1 | ||
Maximum of Months | 0.189686E+10 | 3297.02 | 23.07 | 18.40 | 98935759.46 | 56.70 | 24.40 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123804E+10 | 4793.90 | 19-JAN-08:00 | -28.3 | -28.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.115224E+10 | 4827.93 | 02-FEB-06:03 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.689276E+09 | 1661.05 | 24-MAR-13:40 | 12.93 | 6.49 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.153696E+10 | 2446.27 | 15-APR-18:03 | 27.85 | 18.46 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.279284E+10 | 2464.01 | 31-MAY-18:30 | 26.65 | 18.93 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.358312E+10 | 2731.01 | 26-JUN-19:10 | 28.03 | 21.71 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.404750E+10 | 2617.05 | 03-JUL-19:10 | 28.03 | 24.15 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.390826E+10 | 2464.87 | 04-AUG-15:05 | 33.90 | 25.47 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.299496E+10 | 2749.00 | 08-SEP-13:30 | 30.30 | 19.30 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.157579E+10 | 2282.93 | 20-OCT-14:00 | 22.60 | 13.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.696678E+09 | 4875.23 | 26-NOV-06:55 | -28.9 | -29.0 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 83419475.83 | 1272.77 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.242991E+11 | 0.00 | ||||||||
Minimum of Months | 83419475.83 | 1272.77 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.404750E+10 | 4875.23 | 33.90 | 25.47 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22052170.41 | 3452.05 | 12-JAN-16:02 | 2.62 | 1.03 | 92543968.76 | 56.69 | 20-JAN-00:00 | -23.9 | -24.2 |
February | 73075651.49 | 3716.79 | 25-FEB-16:01 | 5.50 | 2.73 | 84223409.19 | 56.69 | 06-FEB-05:10 | -14.5 | -15.3 |
March | 0.213928E+09 | 3748.11 | 25-MAR-15:01 | 18.72 | 10.43 | 94838762.27 | 56.69 | 23-MAR-21:40 | 9.07 | 5.84 |
April | 0.761186E+09 | 3789.00 | 19-APR-15:01 | 11.70 | 7.43 | 93201366.00 | 56.70 | 19-APR-03:00 | 7.20 | 6.10 |
May | 0.126937E+10 | 3873.09 | 06-MAY-15:01 | 20.92 | 11.57 | 98187143.57 | 56.70 | 31-MAY-21:30 | 21.00 | 15.97 |
June | 0.198631E+10 | 3765.43 | 25-JUN-18:02 | 30.82 | 21.74 | 95398588.93 | 56.70 | 07-JUN-04:10 | 12.80 | 12.80 |
July | 0.239112E+10 | 3724.59 | 13-JUL-18:02 | 24.72 | 19.29 | 98767746.02 | 56.70 | 05-JUL-22:10 | 20.60 | 19.73 |
August | 0.213845E+10 | 3679.61 | 11-AUG-18:02 | 24.35 | 17.81 | 98787475.37 | 56.70 | 02-AUG-21:00 | 23.90 | 21.57 |
September | 0.143842E+10 | 3888.08 | 20-SEP-15:01 | 22.12 | 11.87 | 94750973.59 | 56.70 | 25-SEP-00:10 | 7.02 | 3.86 |
October | 0.472463E+09 | 3792.17 | 19-OCT-15:01 | 18.53 | 10.63 | 96463899.30 | 56.69 | 11-OCT-23:40 | 6.20 | 2.93 |
November | 0.138160E+09 | 3810.82 | 04-NOV-15:01 | 14.13 | 6.69 | 91022566.83 | 56.70 | 06-NOV-00:40 | 11.30 | 9.09 |
December | 32574428.15 | 3477.71 | 02-DEC-16:01 | 4.95 | 2.78 | 92842313.89 | 56.69 | 12-DEC-23:40 | -13.3 | -13.7 |
Annual Sum or Average | 0.109371E+11 | 0.113103E+10 | ||||||||
Minimum of Months | 22052170.41 | 3452.05 | 2.62 | 1.03 | 84223409.19 | 56.69 | -23.9 | -24.2 | ||
Maximum of Months | 0.239112E+10 | 3888.08 | 30.82 | 21.74 | 98787475.37 | 56.70 | 23.90 | 21.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8456860.82 | 885.65 | 12-JAN-16:03 | 2.62 | 1.03 | 92311917.49 | 56.69 | 20-JAN-23:49 | -11.9 | -12.3 |
February | 32413097.34 | 3415.61 | 24-FEB-16:02 | 8.12 | 5.75 | 83455406.16 | 56.69 | 28-FEB-02:30 | -16.1 | -16.6 |
March | 0.123882E+09 | 3643.38 | 24-MAR-18:01 | 8.35 | 4.46 | 93989014.05 | 56.69 | 20-MAR-00:10 | 13.12 | 11.03 |
April | 0.629116E+09 | 3706.64 | 19-APR-15:01 | 11.70 | 7.43 | 92755396.07 | 56.70 | 24-APR-01:30 | 11.95 | 10.22 |
May | 0.118447E+10 | 3806.01 | 06-MAY-15:01 | 20.92 | 11.57 | 98051973.45 | 56.70 | 30-MAY-21:10 | 19.82 | 17.01 |
June | 0.193923E+10 | 3716.77 | 25-JUN-18:02 | 30.82 | 21.74 | 95378860.12 | 56.70 | 28-JUN-21:40 | 21.50 | 16.96 |
July | 0.231051E+10 | 3680.98 | 13-JUL-18:02 | 24.72 | 19.29 | 98757607.78 | 56.70 | 28-JUL-21:10 | 19.40 | 17.20 |
August | 0.198548E+10 | 3655.81 | 13-AUG-15:02 | 26.02 | 20.37 | 98748974.82 | 56.70 | 16-AUG-04:00 | 10.60 | 10.60 |
September | 0.119145E+10 | 3790.79 | 20-SEP-15:01 | 22.12 | 11.87 | 94421031.33 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.279486E+09 | 3641.59 | 19-OCT-15:01 | 18.53 | 10.63 | 95279121.60 | 56.70 | 02-OCT-01:30 | 13.60 | 10.00 |
November | 76488685.72 | 3651.88 | 04-NOV-15:01 | 14.13 | 6.69 | 90342828.34 | 56.69 | 02-NOV-21:10 | 11.10 | 9.90 |
December | 11814761.24 | 750.16 | 02-DEC-16:03 | 4.95 | 2.78 | 92286377.21 | 56.69 | 28-DEC-04:10 | -16.8 | -17.0 |
Annual Sum or Average | 0.977280E+10 | 0.112578E+10 | ||||||||
Minimum of Months | 8456860.82 | 750.16 | 2.62 | 1.03 | 83455406.16 | 56.69 | -16.8 | -17.0 | ||
Maximum of Months | 0.231051E+10 | 3806.01 | 30.82 | 21.74 | 98757607.78 | 56.70 | 22.43 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124288E+09 | 1728.47 | 12-JAN-16:02 | 2.62 | 1.03 | 94475393.05 | 56.69 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.200235E+09 | 1750.10 | 08-FEB-16:02 | 2.02 | 0.66 | 85981541.44 | 56.69 | 08-FEB-22:00 | -0.6 | -1.2 |
March | 0.305807E+09 | 1754.46 | 24-MAR-15:01 | 12.43 | 6.31 | 96343953.98 | 56.69 | 23-MAR-21:40 | 9.07 | 5.84 |
April | 0.519716E+09 | 1748.40 | 19-APR-15:01 | 11.70 | 7.43 | 93665686.13 | 56.69 | 15-APR-23:10 | 20.50 | 16.26 |
May | 0.795564E+09 | 1772.54 | 06-MAY-15:01 | 20.92 | 11.57 | 98251687.44 | 56.69 | 12-MAY-22:10 | 16.70 | 15.64 |
June | 0.109057E+10 | 1694.82 | 11-JUN-15:02 | 33.22 | 24.66 | 95407530.17 | 56.70 | 28-JUN-21:10 | 22.85 | 17.35 |
July | 0.128096E+10 | 1714.76 | 13-JUL-15:02 | 25.60 | 19.53 | 98689374.15 | 56.70 | 19-JUL-21:10 | 22.62 | 20.36 |
August | 0.127341E+10 | 1709.44 | 14-AUG-15:02 | 25.32 | 19.81 | 98762380.24 | 56.69 | 02-AUG-23:49 | 24.40 | 22.05 |
September | 0.106849E+10 | 1805.49 | 20-SEP-15:01 | 22.12 | 11.87 | 95070658.35 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.679875E+09 | 1777.60 | 19-OCT-15:01 | 18.53 | 10.63 | 97608296.73 | 56.69 | 10-OCT-21:10 | 10.67 | 9.78 |
November | 0.288145E+09 | 1791.19 | 04-NOV-15:01 | 14.13 | 6.69 | 92744569.23 | 56.69 | 03-NOV-21:40 | 5.37 | 2.99 |
December | 0.176930E+09 | 1731.18 | 01-DEC-16:01 | -2.1 | -4.2 | 94729884.82 | 56.69 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.780399E+10 | 0.114173E+10 | ||||||||
Minimum of Months | 0.124288E+09 | 1694.82 | -2.1 | -4.2 | 85981541.44 | 56.69 | -3.8 | -4.6 | ||
Maximum of Months | 0.128096E+10 | 1805.49 | 33.22 | 24.66 | 98762380.24 | 56.70 | 24.40 | 22.05 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362574E+11 | 47322.58 | 19-JAN-01:51 | -23.9 | -24.0 | 0.132796E+11 | 9908.13 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.337259E+11 | 34379.16 | 01-FEB-00:01 | -24.1 | -24.4 | 0.118549E+11 | 9972.26 | 24-FEB-23:10 | 0.60 | 0.06 |
March | 0.386719E+11 | 20012.06 | 19-MAR-21:00 | 15.00 | 11.82 | 0.154275E+11 | 10227.14 | 28-MAR-22:10 | 8.80 | 7.20 |
April | 0.405435E+11 | 22720.00 | 16-APR-21:00 | 22.20 | 18.08 | 0.150245E+11 | 10282.97 | 19-APR-22:10 | 6.60 | 3.32 |
May | 0.457300E+11 | 23827.52 | 31-MAY-21:20 | 21.40 | 16.39 | 0.154909E+11 | 10351.50 | 24-MAY-22:10 | 10.00 | 9.66 |
June | 0.472880E+11 | 24094.86 | 26-JUN-21:30 | 25.00 | 21.13 | 0.146544E+11 | 10296.71 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.498809E+11 | 24022.48 | 25-JUL-22:00 | 25.60 | 20.99 | 0.148000E+11 | 9724.53 | 11-JUL-22:10 | 14.90 | 13.94 |
August | 0.489004E+11 | 23941.76 | 03-AUG-22:00 | 23.90 | 22.63 | 0.150353E+11 | 9914.92 | 15-AUG-22:10 | 13.22 | 12.93 |
September | 0.441221E+11 | 23718.55 | 07-SEP-21:30 | 21.70 | 16.24 | 0.148104E+11 | 10264.27 | 25-SEP-22:10 | 10.10 | 6.68 |
October | 0.410702E+11 | 20602.15 | 20-OCT-22:00 | 13.90 | 9.53 | 0.155723E+11 | 10254.74 | 11-OCT-22:10 | 8.98 | 4.63 |
November | 0.369638E+11 | 40537.44 | 25-NOV-21:21 | -23.9 | -24.2 | 0.145295E+11 | 10170.56 | 03-NOV-22:10 | 4.82 | 2.55 |
December | 0.345833E+11 | 18137.88 | 04-DEC-23:00 | 2.20 | 0.30 | 0.149633E+11 | 9880.84 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.497737E+12 | 0.175443E+12 | ||||||||
Minimum of Months | 0.337259E+11 | 18137.88 | -24.1 | -24.4 | 0.118549E+11 | 9724.53 | 0.60 | 0.04 | ||
Maximum of Months | 0.498809E+11 | 47322.58 | 25.60 | 22.63 | 0.155723E+11 | 10351.50 | 14.90 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391657E+11 | 49998.41 | 19-JAN-01:51 | -23.9 | -24.0 | 0.133348E+11 | 10022.52 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.365139E+11 | 36359.29 | 01-FEB-00:01 | -24.1 | -24.4 | 0.119582E+11 | 10090.79 | 24-FEB-23:10 | 0.60 | 0.06 |
March | 0.419083E+11 | 21283.19 | 19-MAR-21:00 | 15.00 | 11.82 | 0.155583E+11 | 10338.08 | 28-MAR-22:10 | 8.80 | 7.20 |
April | 0.437260E+11 | 23970.83 | 16-APR-21:00 | 22.20 | 18.08 | 0.151458E+11 | 10399.06 | 19-APR-22:10 | 6.60 | 3.32 |
May | 0.490528E+11 | 25152.43 | 31-MAY-21:20 | 21.40 | 16.39 | 0.155819E+11 | 10460.88 | 24-MAY-22:10 | 10.00 | 9.66 |
June | 0.504452E+11 | 25421.89 | 26-JUN-21:20 | 25.20 | 21.19 | 0.146997E+11 | 10408.66 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.530721E+11 | 25339.28 | 25-JUL-22:00 | 25.60 | 20.99 | 0.148203E+11 | 9785.32 | 11-JUL-22:10 | 14.90 | 13.94 |
August | 0.520977E+11 | 25251.67 | 03-AUG-22:00 | 23.90 | 22.63 | 0.150626E+11 | 9975.51 | 15-AUG-22:10 | 13.22 | 12.93 |
September | 0.472282E+11 | 25009.55 | 07-SEP-21:30 | 21.70 | 16.24 | 0.148807E+11 | 10380.59 | 25-SEP-22:10 | 10.10 | 6.68 |
October | 0.443190E+11 | 21870.71 | 20-OCT-22:00 | 13.90 | 9.53 | 0.157027E+11 | 10371.45 | 03-OCT-22:10 | 8.67 | 6.83 |
November | 0.400225E+11 | 42891.57 | 25-NOV-21:21 | -23.9 | -24.2 | 0.146378E+11 | 10284.40 | 01-NOV-22:10 | 6.10 | 4.82 |
December | 0.377211E+11 | 19380.80 | 04-DEC-23:00 | 2.20 | 0.30 | 0.150632E+11 | 9993.21 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.535272E+12 | 0.176446E+12 | ||||||||
Minimum of Months | 0.365139E+11 | 19380.80 | -24.1 | -24.4 | 0.119582E+11 | 9785.32 | 0.60 | 0.04 | ||
Maximum of Months | 0.530721E+11 | 49998.41 | 25.60 | 22.63 | 0.157027E+11 | 10460.88 | 14.90 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494746E+11 | 41984.49 | 19-JAN-01:51 | -23.9 | -24.0 | 0.184313E+11 | 11330.72 | 14-JAN-18:00 | -9.4 | -10.4 |
February | 0.458530E+11 | 30054.60 | 01-FEB-00:01 | -24.1 | -24.4 | 0.166606E+11 | 11356.20 | 25-FEB-18:00 | 1.70 | 0.04 |
March | 0.525091E+11 | 27773.59 | 19-MAR-10:50 | 14.13 | 10.20 | 0.186552E+11 | 11365.88 | 18-MAR-17:00 | 8.90 | 7.46 |
April | 0.531936E+11 | 29324.58 | 18-APR-10:40 | 26.33 | 20.74 | 0.180454E+11 | 11368.50 | 22-APR-17:00 | 3.90 | 1.51 |
May | 0.580843E+11 | 29469.62 | 29-MAY-10:50 | 24.82 | 18.70 | 0.186165E+11 | 11350.05 | 13-MAY-17:00 | 12.20 | 10.89 |
June | 0.581240E+11 | 29818.72 | 11-JUN-10:50 | 30.13 | 22.30 | 0.179753E+11 | 11327.33 | 03-JUN-17:00 | 14.40 | 10.98 |
July | 0.607351E+11 | 29742.37 | 02-JUL-10:50 | 28.03 | 21.98 | 0.185417E+11 | 11280.97 | 22-JUL-17:30 | 20.00 | 14.37 |
August | 0.601371E+11 | 29501.89 | 11-AUG-10:50 | 27.43 | 19.25 | 0.185542E+11 | 11273.95 | 12-AUG-17:00 | 19.40 | 17.20 |
September | 0.561264E+11 | 29666.03 | 08-SEP-10:50 | 28.62 | 18.91 | 0.180019E+11 | 11370.52 | 30-SEP-17:00 | 6.10 | 1.60 |
October | 0.544901E+11 | 28224.81 | 01-OCT-10:50 | 16.33 | 11.52 | 0.186559E+11 | 11364.55 | 28-OCT-17:00 | 7.20 | 3.19 |
November | 0.501047E+11 | 43977.32 | 25-NOV-21:21 | -23.9 | -24.2 | 0.180083E+11 | 11365.79 | 04-NOV-17:00 | 5.60 | 2.18 |
December | 0.492213E+11 | 25741.36 | 03-DEC-11:50 | 4.90 | 2.33 | 0.186198E+11 | 11348.56 | 02-DEC-18:00 | 1.10 | 0.61 |
Annual Sum or Average | 0.648053E+12 | 0.218766E+12 | ||||||||
Minimum of Months | 0.458530E+11 | 25741.36 | -24.1 | -24.4 | 0.166606E+11 | 11273.95 | -9.4 | -10.4 | ||
Maximum of Months | 0.607351E+11 | 43977.32 | 30.13 | 22.30 | 0.186559E+11 | 11370.52 | 20.00 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110947E+10 | 6507.27 | 19-JAN-01:51 | -23.9 | -24.0 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.583652E+09 | 3491.57 | 24-FEB-13:50 | 7.62 | 4.98 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.135613E+10 | 3788.18 | 19-MAR-13:00 | 16.70 | 12.77 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.330114E+10 | 5409.07 | 15-APR-13:40 | 29.03 | 20.49 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.613020E+10 | 5409.32 | 31-MAY-13:50 | 29.50 | 19.47 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.799395E+10 | 5534.98 | 30-JUN-14:30 | 29.40 | 21.76 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.897403E+10 | 5507.19 | 29-JUL-13:40 | 27.80 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.844938E+10 | 5568.35 | 04-AUG-14:50 | 33.80 | 25.39 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.619249E+10 | 5792.21 | 07-SEP-13:40 | 32.03 | 18.26 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.312653E+10 | 5314.69 | 20-OCT-13:10 | 21.93 | 12.66 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.129917E+10 | 6000.80 | 25-NOV-21:32 | -24.0 | -24.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.192505E+09 | 2775.89 | 03-DEC-12:50 | 5.50 | 2.39 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.487086E+11 | 0.00 | ||||||||
Minimum of Months | 0.192505E+09 | 2775.89 | -24.0 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.897403E+10 | 6507.27 | 33.80 | 25.39 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484562E+09 | 15450.29 | 31-JAN-11:52 | -22.8 |
February | 0.304000E+10 | 31213.26 | 04-FEB-14:00 | -20.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 1167209.82 | 2991.37 | 26-NOV-09:02 | -22.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.352573E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.304000E+10 | 31213.26 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237595E+10 | 4344.53 | 20-JAN-08:61 | -23.0 |
February | 0.116627E+10 | 3954.05 | 04-FEB-11:22 | -23.0 |
March | 0.640420E+09 | 1524.81 | 06-MAR-05:00 | -15.6 |
April | 0.238949E+09 | 1027.68 | 03-APR-06:05 | -7.1 |
May | 416856.66 | 76.65 | 02-MAY-06:05 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 13038915.53 | 456.28 | 30-SEP-06:30 | 0.60 |
October | 52490397.41 | 565.16 | 23-OCT-06:05 | -3.0 |
November | 0.874477E+09 | 3747.41 | 26-NOV-09:02 | -22.7 |
December | 0.199029E+10 | 2246.88 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.735230E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.237595E+10 | 4344.53 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126464E+09 | 2326.12 | 31-JAN-11:42 | -23.1 |
February | 0.167588E+09 | 2927.70 | 04-FEB-11:31 | -22.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 20725152.60 | 1579.17 | 26-NOV-09:02 | -22.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.314777E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.167588E+09 | 2927.70 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670763E+09 | 3238.79 | 31-JAN-11:52 | -22.8 |
February | 0.589069E+09 | 4457.02 | 04-FEB-11:31 | -22.8 |
March | 11777734.80 | 362.92 | 06-MAR-04:50 | -15.7 |
April | 154291.72 | 48.99 | 03-APR-04:00 | -6.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.145473E+09 | 2139.82 | 26-NOV-09:02 | -22.7 |
December | 0.143337E+09 | 527.48 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.156057E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.670763E+09 | 4457.02 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104954E+10 | 1701.58 | 31-JAN-11:52 | -22.8 |
February | 0.692010E+09 | 2262.11 | 04-FEB-11:53 | -22.2 |
March | 0.250882E+09 | 510.93 | 06-MAR-05:00 | -15.6 |
April | 64323419.18 | 297.42 | 03-APR-04:00 | -6.7 |
May | 121886.17 | 20.23 | 03-MAY-04:00 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1568266.45 | 95.01 | 30-SEP-04:50 | -0.1 |
October | 11340991.74 | 130.31 | 28-OCT-04:50 | -1.7 |
November | 0.349927E+09 | 1232.66 | 26-NOV-09:02 | -22.7 |
December | 0.703699E+09 | 601.02 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.312342E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.104954E+10 | 2262.11 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3930655.85 | 15250.24 | 06-JAN-10:41 | -23.2 |
February | 1347455.17 | 8751.05 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 682882.11 | 10154.99 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 5960993.13 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 3930655.85 | 15250.24 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.836288E+09 | 11763.13 | 20-JAN-08:61 | -23.0 |
February | 0.424656E+09 | 9525.84 | 04-FEB-11:22 | -23.0 |
March | 9408562.68 | 527.75 | 01-MAR-11:02 | -4.9 |
April | 456203.13 | 278.31 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.200109E+09 | 8983.75 | 26-NOV-09:02 | -22.7 |
December | 0.508139E+09 | 3497.73 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.197906E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.836288E+09 | 11763.13 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164152E+10 | 38452.28 | 31-JAN-11:42 | -23.1 |
February | 0.224889E+10 | 46533.85 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.279329E+09 | 26707.90 | 26-NOV-09:02 | -22.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.416974E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.224889E+10 | 46533.85 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190930E+10 | 2327.12 | 20-JAN-09:02 | -21.6 |
February | 0.130545E+10 | 2336.67 | 04-FEB-19:02 | -20.0 |
March | 0.592106E+09 | 2253.94 | 01-MAR-16:02 | -3.9 |
April | 0.216949E+09 | 2243.75 | 03-APR-08:62 | -5.9 |
May | 12441172.86 | 1632.44 | 02-MAY-08:61 | 4.08 |
June | 3648197.29 | 885.73 | 22-JUN-08:03 | 15.18 |
July | 1086616.96 | 667.97 | 30-JUL-08:04 | 21.38 |
August | 1176517.73 | 796.22 | 07-AUG-08:03 | 15.47 |
September | 33140255.82 | 2011.77 | 29-SEP-08:62 | 5.05 |
October | 0.143019E+09 | 2196.76 | 27-OCT-08:61 | 3.15 |
November | 0.777155E+09 | 2368.72 | 26-NOV-09:01 | -22.7 |
December | 0.149766E+10 | 2320.93 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.649314E+10 | |||
Minimum of Months | 1086616.96 | 667.97 | -22.7 | |
Maximum of Months | 0.190930E+10 | 2368.72 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225261E+10 | 2331.42 | 19-JAN-16:02 | -22.9 |
February | 0.156916E+10 | 2353.17 | 04-FEB-19:02 | -20.0 |
March | 0.703676E+09 | 2258.55 | 07-MAR-09:01 | -4.9 |
April | 0.246710E+09 | 2236.25 | 03-APR-08:62 | -5.9 |
May | 15754134.33 | 1872.30 | 02-MAY-08:61 | 4.08 |
June | 3964292.09 | 871.07 | 15-JUN-08:03 | 14.60 |
July | 1117492.94 | 687.31 | 29-JUL-08:04 | 22.48 |
August | 1288969.09 | 757.62 | 07-AUG-08:03 | 15.47 |
September | 42122315.10 | 2144.29 | 30-SEP-08:62 | 3.35 |
October | 0.213192E+09 | 2212.00 | 27-OCT-08:61 | 3.15 |
November | 0.933360E+09 | 2376.24 | 26-NOV-09:01 | -22.7 |
December | 0.174624E+10 | 2320.82 | 11-DEC-16:13 | -20.2 |
Annual Sum or Average | 0.772920E+10 | |||
Minimum of Months | 1117492.94 | 687.31 | -22.9 | |
Maximum of Months | 0.225261E+10 | 2376.24 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89960390.75 | 326.87 | 19-JAN-05:00 | -27.2 |
February | 34766990.58 | 314.99 | 03-FEB-05:00 | -33.9 |
March | 7402753.06 | 120.79 | 04-MAR-06:00 | -8.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 12316367.16 | 242.45 | 28-NOV-05:00 | -21.7 |
December | 62912973.05 | 272.92 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.207359E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 89960390.75 | 326.87 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262878E+09 | 682.99 | 31-JAN-16:02 | -20.1 |
February | 0.149649E+09 | 685.86 | 04-FEB-16:02 | -19.5 |
March | 24239416.29 | 673.06 | 23-MAR-15:03 | 16.28 |
April | 1824555.00 | 629.23 | 03-APR-15:02 | -3.2 |
May | 538036.34 | 538.26 | 18-MAY-15:04 | 15.68 |
June | 303723.93 | 331.94 | 15-JUN-08:05 | 14.60 |
July | 70785.89 | 135.31 | 25-JUL-08:05 | 21.05 |
August | 84887.12 | 370.22 | 07-AUG-08:05 | 15.47 |
September | 782244.51 | 563.29 | 24-SEP-15:04 | 15.92 |
October | 1604023.99 | 366.75 | 20-OCT-08:03 | 9.70 |
November | 58895491.79 | 678.01 | 25-NOV-16:02 | -18.1 |
December | 0.156145E+09 | 681.16 | 10-DEC-16:02 | -17.9 |
Annual Sum or Average | 0.657016E+09 | |||
Minimum of Months | 70785.89 | 135.31 | -20.1 | |
Maximum of Months | 0.262878E+09 | 685.86 | 21.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189531E+10 | 2228.28 | 19-JAN-16:02 | -22.9 |
February | 0.131032E+10 | 2248.52 | 04-FEB-19:02 | -20.0 |
March | 0.579306E+09 | 2161.15 | 01-MAR-16:02 | -3.9 |
April | 0.240170E+09 | 2148.61 | 21-APR-15:01 | -0.5 |
May | 10802572.74 | 817.96 | 16-MAY-15:04 | 16.60 |
June | 2344693.08 | 784.55 | 04-JUN-15:04 | 15.00 |
July | 539047.33 | 726.16 | 11-JUL-15:04 | 17.77 |
August | 799393.58 | 662.84 | 30-AUG-15:04 | 18.07 |
September | 29668223.57 | 800.04 | 24-SEP-08:04 | 11.20 |
October | 0.143505E+09 | 2074.10 | 26-OCT-08:62 | 1.28 |
November | 0.781873E+09 | 2247.92 | 26-NOV-09:01 | -22.7 |
December | 0.150209E+10 | 2225.66 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.649673E+10 | |||
Minimum of Months | 539047.33 | 662.84 | -22.9 | |
Maximum of Months | 0.189531E+10 | 2248.52 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224084E+10 | 2251.25 | 31-JAN-16:02 | -20.1 |
February | 0.158197E+10 | 2295.93 | 04-FEB-16:02 | -19.5 |
March | 0.689988E+09 | 2172.86 | 06-MAR-16:01 | -0.7 |
April | 0.274244E+09 | 2153.81 | 21-APR-15:01 | -0.5 |
May | 13982114.78 | 832.70 | 07-MAY-15:04 | 17.70 |
June | 2577723.53 | 720.14 | 06-JUN-15:04 | 16.28 |
July | 624302.40 | 725.97 | 11-JUL-15:04 | 17.77 |
August | 1068213.78 | 826.14 | 30-AUG-15:04 | 18.07 |
September | 36917513.53 | 1095.52 | 24-SEP-15:03 | 15.92 |
October | 0.209026E+09 | 2082.83 | 26-OCT-08:62 | 1.28 |
November | 0.935372E+09 | 2257.58 | 26-NOV-09:01 | -22.7 |
December | 0.175385E+10 | 2232.18 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.774046E+10 | |||
Minimum of Months | 624302.40 | 720.14 | -22.7 | |
Maximum of Months | 0.224084E+10 | 2295.93 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235100E+10 | 2525.39 | 31-JAN-12:25 | -22.0 |
February | 0.167825E+10 | 3641.24 | 04-FEB-14:00 | -20.0 |
March | 0.592558E+09 | 1058.29 | 06-MAR-05:00 | -15.6 |
April | 0.189421E+09 | 894.14 | 03-APR-04:00 | -6.7 |
May | 1817472.44 | 132.26 | 02-MAY-03:50 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 13594134.79 | 394.96 | 30-SEP-05:00 | 0.00 |
October | 69768884.21 | 436.79 | 27-OCT-03:50 | 0.00 |
November | 0.902921E+09 | 2059.12 | 26-NOV-09:02 | -22.7 |
December | 0.182708E+10 | 1288.96 | 12-DEC-05:00 | -20.0 |
Annual Sum or Average | 0.762640E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.7 | |
Maximum of Months | 0.235100E+10 | 3641.24 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252138E+10 | 2660.90 | 18-JAN-16:02 | -17.9 |
February | 0.159379E+10 | 2622.82 | 04-FEB-19:02 | -20.0 |
March | 0.904687E+09 | 2582.77 | 01-MAR-16:02 | -3.9 |
April | 0.358298E+09 | 2577.45 | 21-APR-15:01 | -0.5 |
May | 26289189.57 | 2479.99 | 02-MAY-08:61 | 4.08 |
June | 7775284.03 | 836.63 | 15-JUN-08:03 | 14.60 |
July | 900531.61 | 645.50 | 29-JUL-08:04 | 22.48 |
August | 880317.99 | 742.53 | 07-AUG-08:03 | 15.47 |
September | 64155635.95 | 2468.01 | 30-SEP-08:62 | 3.35 |
October | 0.268652E+09 | 2536.57 | 27-OCT-08:61 | 3.15 |
November | 0.113000E+10 | 2709.13 | 26-NOV-09:01 | -22.7 |
December | 0.210434E+10 | 2684.87 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.898116E+10 | |||
Minimum of Months | 880317.99 | 645.50 | -22.7 | |
Maximum of Months | 0.252138E+10 | 2709.13 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292988E+10 | 2675.21 | 19-JAN-16:02 | -22.9 |
February | 0.192326E+10 | 2643.28 | 04-FEB-19:02 | -20.0 |
March | 0.105781E+10 | 2585.38 | 07-MAR-09:01 | -4.9 |
April | 0.402500E+09 | 2572.67 | 21-APR-15:01 | -0.5 |
May | 32201058.80 | 2479.18 | 02-MAY-08:61 | 4.08 |
June | 8580036.39 | 847.20 | 15-JUN-08:03 | 14.60 |
July | 893074.72 | 688.93 | 29-JUL-08:04 | 22.48 |
August | 953981.12 | 743.17 | 07-AUG-08:03 | 15.47 |
September | 80290536.79 | 2472.94 | 30-SEP-08:62 | 3.35 |
October | 0.382947E+09 | 2553.37 | 27-OCT-08:61 | 3.15 |
November | 0.133375E+10 | 2718.11 | 26-NOV-09:01 | -22.7 |
December | 0.242279E+10 | 2687.98 | 11-DEC-16:13 | -20.2 |
Annual Sum or Average | 0.105759E+11 | |||
Minimum of Months | 893074.72 | 688.93 | -22.9 | |
Maximum of Months | 0.292988E+10 | 2718.11 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.812760E+09 | 1286.96 | 26-JAN-16:02 | -11.6 |
February | 0.455066E+09 | 1261.19 | 28-FEB-19:02 | -15.7 |
March | 0.245767E+09 | 1259.59 | 01-MAR-16:02 | -3.9 |
April | 0.100973E+09 | 1246.56 | 02-APR-15:02 | 0.60 |
May | 2803982.83 | 504.98 | 09-MAY-15:04 | 17.62 |
June | 566617.29 | 463.25 | 02-JUN-18:04 | 13.90 |
July | 182708.42 | 259.33 | 07-JUL-08:05 | 22.30 |
August | 303836.39 | 343.03 | 06-AUG-08:05 | 12.80 |
September | 8368141.63 | 691.72 | 29-SEP-08:62 | 5.05 |
October | 31529746.22 | 1198.46 | 26-OCT-08:62 | 1.28 |
November | 0.309333E+09 | 1292.63 | 26-NOV-09:01 | -22.7 |
December | 0.677596E+09 | 1296.04 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.264525E+10 | |||
Minimum of Months | 182708.42 | 259.33 | -22.7 | |
Maximum of Months | 0.812760E+09 | 1296.04 | 22.30 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182679E+09 | 13457.01 | 06-JAN-10:41 | -23.2 |
February | 0.214774E+09 | 13876.00 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 5026488.86 | 5556.48 | 26-NOV-09:02 | -22.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.402480E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.214774E+09 | 13876.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178006E+09 | 14558.58 | 06-JAN-10:41 | -23.2 |
February | 0.184547E+09 | 14103.34 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 5574904.65 | 6204.29 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.368128E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.184547E+09 | 14558.58 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 261509.90 | 3954.55 | 06-JAN-10:41 | -23.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 159417.89 | 2656.96 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 420927.79 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 261509.90 | 3954.55 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652161E+10 | 8408.98 | 31-JAN-11:52 | -22.8 |
February | 0.397471E+10 | 10856.50 | 04-FEB-11:31 | -22.8 |
March | 0.175369E+10 | 3719.75 | 06-MAR-05:00 | -15.6 |
April | 0.552735E+09 | 2292.28 | 03-APR-04:50 | -7.1 |
May | 14872931.52 | 589.13 | 03-MAY-05:00 | 1.10 |
June | 300537.93 | 94.61 | 03-JUN-04:30 | 5.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 47025022.88 | 1086.68 | 30-SEP-04:50 | -0.1 |
October | 0.289160E+09 | 1240.83 | 08-OCT-05:00 | -0.6 |
November | 0.246000E+10 | 7012.28 | 26-NOV-09:02 | -22.7 |
December | 0.501943E+10 | 4254.16 | 10-DEC-06:10 | -22.6 |
Annual Sum or Average | 0.206335E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.652161E+10 | 10856.50 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.176689E+11 | 17018.80 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.159534E+11 | 17018.80 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.177302E+11 | 17018.80 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.170699E+11 | 17018.80 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.176995E+11 | 17018.80 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.171481E+11 | 17018.80 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.176213E+11 | 17018.80 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.177302E+11 | 17018.80 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.170699E+11 | 17018.80 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.176689E+11 | 17018.80 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.171345E+11 | 17018.80 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.176213E+11 | 17018.80 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.208116E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.159534E+11 | 17018.80 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.177302E+11 | 17018.80 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.958205E+09 | 922.95 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.865172E+09 | 922.95 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.961528E+09 | 922.95 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.925717E+09 | 922.95 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.959866E+09 | 922.95 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.929963E+09 | 922.95 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.955621E+09 | 922.95 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.961528E+09 | 922.95 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.925717E+09 | 922.95 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.958205E+09 | 922.95 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.929224E+09 | 922.95 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.955621E+09 | 922.95 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.112864E+11 | 0.101859E+11 | ||||
Minimum of Months | 0.865172E+09 | 922.95 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.961528E+09 | 922.95 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.110961E+10 | 1068.78 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.100187E+10 | 1068.78 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.111345E+10 | 1068.78 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.107198E+10 | 1068.78 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.111153E+10 | 1068.78 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.107690E+10 | 1068.78 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.110661E+10 | 1068.78 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.111345E+10 | 1068.78 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.107198E+10 | 1068.78 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.110961E+10 | 1068.78 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.107605E+10 | 1068.78 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.110661E+10 | 1068.78 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.130697E+11 | 0.117953E+11 | ||||
Minimum of Months | 0.100187E+10 | 1068.78 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.111345E+10 | 1068.78 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.234644E+10 | 2260.10 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.211862E+10 | 2260.10 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.235457E+10 | 2260.10 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.226688E+10 | 2260.10 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.235050E+10 | 2260.10 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.227728E+10 | 2260.10 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.234011E+10 | 2260.10 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.235457E+10 | 2260.10 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.226688E+10 | 2260.10 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.234644E+10 | 2260.10 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.227547E+10 | 2260.10 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.234011E+10 | 2260.10 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.276379E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.211862E+10 | 2260.10 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.235457E+10 | 2260.10 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.375444E+09 | 361.63 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.338992E+09 | 361.63 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.376746E+09 | 361.63 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.362715E+09 | 361.63 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.376095E+09 | 361.63 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.364378E+09 | 361.63 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.374431E+09 | 361.63 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.376746E+09 | 361.63 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.362715E+09 | 361.63 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.375444E+09 | 361.63 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.364089E+09 | 361.63 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.374431E+09 | 361.63 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.442222E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.338992E+09 | 361.63 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.376746E+09 | 361.63 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.445960E+09 | 429.55 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.402661E+09 | 429.55 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.447506E+09 | 429.55 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.430840E+09 | 429.55 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.446733E+09 | 429.55 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.432815E+09 | 429.55 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.444757E+09 | 429.55 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.447506E+09 | 429.55 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.430840E+09 | 429.55 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.445960E+09 | 429.55 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.432472E+09 | 429.55 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.444757E+09 | 429.55 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.525281E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.402661E+09 | 429.55 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.447506E+09 | 429.55 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.233839E+10 | 2252.35 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.211136E+10 | 2252.35 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.234650E+10 | 2252.35 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.225911E+10 | 2252.35 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.234245E+10 | 2252.35 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.226947E+10 | 2252.35 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.233209E+10 | 2252.35 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.234650E+10 | 2252.35 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.225911E+10 | 2252.35 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.233839E+10 | 2252.35 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.226767E+10 | 2252.35 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.233209E+10 | 2252.35 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.275431E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.211136E+10 | 2252.35 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.234650E+10 | 2252.35 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.137054E+11 | 13201.13 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.123747E+11 | 13201.13 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.137529E+11 | 13201.13 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.132407E+11 | 13201.13 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.137292E+11 | 13201.13 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.133015E+11 | 13201.13 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.136685E+11 | 13201.13 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.137529E+11 | 13201.13 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.132407E+11 | 13201.13 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.137054E+11 | 13201.13 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.132909E+11 | 13201.13 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.136685E+11 | 13201.13 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.161431E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.123747E+11 | 13201.13 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.137529E+11 | 13201.13 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.320927E+09 | 290.37 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.289828E+09 | 290.37 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.318376E+09 | 290.37 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.310986E+09 | 290.37 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.319652E+09 | 290.37 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.308435E+09 | 290.37 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.322202E+09 | 290.37 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.318376E+09 | 290.37 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.310986E+09 | 290.37 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.320927E+09 | 290.37 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.309711E+09 | 290.37 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.322202E+09 | 290.37 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.377261E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.289828E+09 | 290.37 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.322202E+09 | 290.37 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.321015E+09 | 290.45 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.289908E+09 | 290.45 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.318463E+09 | 290.45 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.311071E+09 | 290.45 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.319739E+09 | 290.45 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.308520E+09 | 290.45 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.322290E+09 | 290.45 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.318463E+09 | 290.45 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.311071E+09 | 290.45 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.321015E+09 | 290.45 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.309795E+09 | 290.45 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.322290E+09 | 290.45 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.377364E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.289908E+09 | 290.45 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.322290E+09 | 290.45 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.185439E+10 | 1786.16 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.167435E+10 | 1786.16 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.186082E+10 | 1786.16 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.179152E+10 | 1786.16 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.185761E+10 | 1786.16 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.179973E+10 | 1786.16 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.184939E+10 | 1786.16 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.186082E+10 | 1786.16 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.179152E+10 | 1786.16 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.185439E+10 | 1786.16 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.179831E+10 | 1786.16 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.184939E+10 | 1786.16 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.218422E+11 | ||||
Minimum of Months | 0.167435E+10 | 1786.16 | 0.00 | 0.00 | |
Maximum of Months | 0.186082E+10 | 1786.16 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.321015E+09 | 290.45 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.289908E+09 | 290.45 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.318463E+09 | 290.45 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.311071E+09 | 290.45 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.319739E+09 | 290.45 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.308520E+09 | 290.45 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.322290E+09 | 290.45 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.318463E+09 | 290.45 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.311071E+09 | 290.45 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.321015E+09 | 290.45 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.309795E+09 | 290.45 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.322290E+09 | 290.45 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.377364E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.289908E+09 | 290.45 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.322290E+09 | 290.45 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.410642E+10 | 3955.32 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.370772E+10 | 3955.32 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.412066E+10 | 3955.32 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.396719E+10 | 3955.32 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.411354E+10 | 3955.32 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.398539E+10 | 3955.32 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.409534E+10 | 3955.32 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.412066E+10 | 3955.32 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.396719E+10 | 3955.32 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.410642E+10 | 3955.32 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.398222E+10 | 3955.32 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.409534E+10 | 3955.32 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.483681E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.370772E+10 | 3955.32 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.412066E+10 | 3955.32 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.410642E+10 | 3955.32 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.370772E+10 | 3955.32 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.412066E+10 | 3955.32 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.396719E+10 | 3955.32 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.411354E+10 | 3955.32 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.398539E+10 | 3955.32 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.409534E+10 | 3955.32 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.412066E+10 | 3955.32 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.396719E+10 | 3955.32 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.410642E+10 | 3955.32 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.398222E+10 | 3955.32 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.409534E+10 | 3955.32 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.483681E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.370772E+10 | 3955.32 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.412066E+10 | 3955.32 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.118068E+10 | 1137.23 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.106604E+10 | 1137.23 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.118477E+10 | 1137.23 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.114064E+10 | 1137.23 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.118272E+10 | 1137.23 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.114588E+10 | 1137.23 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.117749E+10 | 1137.23 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.118477E+10 | 1137.23 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.114064E+10 | 1137.23 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.118068E+10 | 1137.23 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.114497E+10 | 1137.23 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.117749E+10 | 1137.23 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.139068E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.106604E+10 | 1137.23 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.118477E+10 | 1137.23 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.196259E+10 | 1890.37 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.177204E+10 | 1890.37 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196939E+10 | 1890.37 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189604E+10 | 1890.37 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196599E+10 | 1890.37 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190474E+10 | 1890.37 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195729E+10 | 1890.37 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196939E+10 | 1890.37 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189604E+10 | 1890.37 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.196259E+10 | 1890.37 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.190323E+10 | 1890.37 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195729E+10 | 1890.37 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.231166E+11 | ||||
Minimum of Months | 0.177204E+10 | 1890.37 | 0.00 | 0.00 | |
Maximum of Months | 0.196939E+10 | 1890.37 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.176689E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.159534E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.170699E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.176995E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.171481E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.176213E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.170699E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.176689E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.171345E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.176213E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.208116E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.159534E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.958205E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219325E+10 |
February | 0.179968E+10 | 0.865172E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160559E+10 |
March | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133780E+10 |
April | 0.192973E+10 | 0.925717E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13903238.37 | 0.879715E+09 |
May | 0.199475E+10 | 0.959866E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18013128.17 | 0.441558E+09 |
June | 0.193394E+10 | 0.929963E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95221375.79 | 0.209552E+09 |
July | 0.199054E+10 | 0.955621E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97748764.66 | 0.106572E+09 |
August | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90441591.98 | 0.152956E+09 |
September | 0.192973E+10 | 0.925717E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49989413.64 | 0.395845E+09 |
October | 0.199054E+10 | 0.958205E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55412.72 | 0.865975E+09 |
November | 0.192552E+10 | 0.929224E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131981E+10 |
December | 0.199054E+10 | 0.955621E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190895E+10 |
Annual Sum or Average | 0.234734E+11 | 0.112864E+11 | 0.101859E+11 | 0.365373E+09 | 0.114176E+11 | ||||
Minimum of Months | 0.179968E+10 | 0.865172E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106572E+09 |
Maximum of Months | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97748764.66 | 0.219325E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.110961E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460704E+09 |
February | 0.208403E+10 | 0.100187E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333333E+09 |
March | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280932E+09 |
April | 0.223463E+10 | 0.107198E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3002046.06 | 0.185182E+09 |
May | 0.230993E+10 | 0.111153E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3774699.46 | 93342685.05 |
June | 0.223950E+10 | 0.107690E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19939239.69 | 44237041.45 |
July | 0.230505E+10 | 0.110661E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20478138.62 | 22444238.95 |
August | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19010280.26 | 32368239.97 |
September | 0.223463E+10 | 0.107198E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11215095.61 | 83535345.50 |
October | 0.230505E+10 | 0.110961E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82332.72 | 0.181118E+09 |
November | 0.222975E+10 | 0.107605E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277234E+09 |
December | 0.230505E+10 | 0.110661E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400920E+09 |
Annual Sum or Average | 0.271823E+11 | 0.130697E+11 | 0.117953E+11 | 77501832.42 | 0.239535E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.100187E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22444238.95 |
Maximum of Months | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20478138.62 | 0.460704E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.445960E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139798E+10 |
February | 0.139600E+10 | 0.402661E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101978E+10 |
March | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882757E+09 |
April | 0.149688E+10 | 0.430840E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 10099542.91 | 0.583922E+09 |
May | 0.154732E+10 | 0.446733E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 13463040.60 | 0.296270E+09 |
June | 0.150015E+10 | 0.432815E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 65926278.30 | 0.138074E+09 |
July | 0.154405E+10 | 0.444757E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 69559755.17 | 67082041.20 |
August | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 64860606.53 | 0.100251E+09 |
September | 0.149688E+10 | 0.430840E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 37921344.34 | 0.264412E+09 |
October | 0.154405E+10 | 0.445960E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 422440.53 | 0.573376E+09 |
November | 0.149361E+10 | 0.432472E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864884E+09 |
December | 0.154405E+10 | 0.444757E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125259E+10 |
Annual Sum or Average | 0.182082E+11 | 0.525281E+10 | 0.679373E+11 | 0.590211E+12 | 0.262253E+09 | 0.744138E+10 | |||
Minimum of Months | 0.139600E+10 | 0.402661E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67082041.20 |
Maximum of Months | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 69559755.17 | 0.139798E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.233839E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554027E+10 |
February | 0.236489E+11 | 0.211136E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406180E+10 |
March | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337565E+10 |
April | 0.253579E+11 | 0.225911E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35966727.39 | 0.222155E+10 |
May | 0.262123E+11 | 0.234245E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45444991.07 | 0.111720E+10 |
June | 0.254132E+11 | 0.226947E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240241E+09 | 0.529774E+09 |
July | 0.261570E+11 | 0.233209E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246598E+09 | 0.269111E+09 |
August | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228803E+09 | 0.387210E+09 |
September | 0.253579E+11 | 0.225911E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133562E+09 | 0.100078E+10 |
October | 0.261570E+11 | 0.233839E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 512413.33 | 0.218326E+10 |
November | 0.253025E+11 | 0.226767E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333260E+10 |
December | 0.261570E+11 | 0.233209E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482508E+10 |
Annual Sum or Average | 0.308456E+12 | 0.275431E+11 | 0.143409E+11 | 0.931128E+09 | 0.288443E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.211136E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269111E+09 |
Maximum of Months | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246598E+09 | 0.554027E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.137054E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110700E+11 |
February | 0.702046E+11 | 0.123747E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804029E+10 |
March | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674935E+10 |
April | 0.752779E+11 | 0.132407E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71992487.55 | 0.445645E+10 |
May | 0.778146E+11 | 0.137292E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90568387.58 | 0.225682E+10 |
June | 0.754422E+11 | 0.133015E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478184E+09 | 0.107010E+10 |
July | 0.776503E+11 | 0.136685E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491091E+09 | 0.540527E+09 |
August | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455748E+09 | 0.784143E+09 |
September | 0.752779E+11 | 0.132407E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269004E+09 | 0.201954E+10 |
October | 0.776503E+11 | 0.137054E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1974368.16 | 0.436618E+10 |
November | 0.751137E+11 | 0.132909E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666205E+10 |
December | 0.776503E+11 | 0.136685E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961927E+10 |
Annual Sum or Average | 0.915690E+12 | 0.161431E+12 | 0.149002E+12 | 0.185856E+10 | 0.576347E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.123747E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540527E+09 |
Maximum of Months | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491091E+09 | 0.110700E+11 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664729E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507906E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393939E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3137850.19 | 0.262499E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3458641.02 | 0.138445E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21600984.50 | 66379337.89 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20301970.89 | 35425264.29 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18856169.81 | 49592212.39 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11550623.04 | 0.121966E+09 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20063.29 | 0.259201E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389919E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556191E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 78926302.74 | 0.344619E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35425264.29 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21600984.50 | 0.664729E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662902E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504236E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390179E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3168212.68 | 0.260592E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3480790.82 | 0.137711E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21624799.34 | 66231586.73 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20371578.69 | 35342727.13 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18991489.71 | 49353663.25 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11732756.99 | 0.120680E+09 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22446.91 | 0.254898E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386971E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552910E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 79392075.13 | 0.342201E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35342727.13 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21624799.34 | 0.662902E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.320927E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181176E+09 |
February | 0.00 | 0.289828E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143244E+09 |
March | 0.00 | 0.318376E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113904E+09 |
April | 0.00 | 0.310986E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 651805.62 | 79935281.28 |
May | 0.00 | 0.319652E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 652261.76 | 46824906.63 |
June | 0.00 | 0.308435E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288803.82 | 24830170.25 |
July | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549845.13 | 15866722.75 |
August | 0.00 | 0.318376E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3513270.67 | 20241573.65 |
September | 0.00 | 0.310986E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2385945.50 | 41450671.60 |
October | 0.00 | 0.320927E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81421272.71 |
November | 0.00 | 0.309711E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113194E+09 |
December | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153303E+09 |
Annual Sum or Average | 0.00 | 0.377261E+10 | 0.300992E+10 | 15041932.49 | 0.101539E+10 | ||||
Minimum of Months | 0.00 | 0.289828E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15866722.75 |
Maximum of Months | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288803.82 | 0.181176E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186271E+09 |
February | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142260E+09 |
March | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110427E+09 |
April | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 922160.50 | 73486810.97 |
May | 0.303504E+09 | 0.319739E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1027471.70 | 38376355.78 |
June | 0.293842E+09 | 0.308520E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6207906.64 | 18470061.16 |
July | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5934509.12 | 9718732.98 |
August | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5567798.98 | 13613051.50 |
September | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3440157.20 | 33869227.38 |
October | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15359.07 | 72079853.54 |
November | 0.293661E+09 | 0.309795E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109560E+09 |
December | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155923E+09 |
Annual Sum or Average | 0.357224E+10 | 0.377364E+10 | 0.301074E+10 | 23115363.19 | 0.964054E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9718732.98 |
Maximum of Months | 0.303685E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6207906.64 | 0.186271E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664557E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507308E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395081E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3132696.33 | 0.263257E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3431451.87 | 0.140013E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21524336.87 | 67183585.88 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20230860.62 | 36068507.50 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18772188.05 | 50216908.84 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11529652.02 | 0.122948E+09 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21292.22 | 0.259993E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389788E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555885E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 78642477.98 | 0.345230E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36068507.50 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21524336.87 | 0.664557E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662811E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503354E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391346E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3141133.98 | 0.261361E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3434502.42 | 0.139546E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21530923.33 | 67095134.27 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20248316.58 | 36035893.76 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18806092.04 | 50102809.60 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11572738.56 | 0.121972E+09 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32788.24 | 0.255703E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386794E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552767E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 78766495.14 | 0.342889E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36035893.76 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21530923.33 | 0.662811E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665216E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509013E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393570E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3078551.35 | 0.262946E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3363525.11 | 0.140022E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21200175.09 | 67395189.50 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19777508.78 | 36267889.96 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18410543.26 | 50429086.40 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11322902.31 | 0.122755E+09 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18013.55 | 0.259555E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389683E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556153E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 77171219.46 | 0.345301E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36267889.96 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21200175.09 | 0.665216E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663997E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506107E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390012E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3097886.99 | 0.261075E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3368841.96 | 0.139461E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21205486.23 | 67301044.49 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19794468.50 | 36233886.08 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18464571.17 | 50314141.09 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11424181.13 | 0.121591E+09 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20000.43 | 0.254904E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386920E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553599E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 77375436.41 | 0.343152E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36233886.08 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21205486.23 | 0.663997E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344771E+09 |
February | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264110E+09 |
March | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204468E+09 |
April | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1570273.43 | 0.135644E+09 |
May | 0.303504E+09 | 0.319739E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1723017.38 | 71862269.02 |
June | 0.293842E+09 | 0.308520E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10868748.77 | 34544811.88 |
July | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10144048.72 | 18467082.56 |
August | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9414774.40 | 25770467.43 |
September | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5765190.86 | 63378254.10 |
October | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.18 | 0.134805E+09 |
November | 0.293661E+09 | 0.309795E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202690E+09 |
December | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288345E+09 |
Annual Sum or Average | 0.357224E+10 | 0.377364E+10 | 0.301074E+10 | 39487064.73 | 0.178886E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18467082.56 |
Maximum of Months | 0.303685E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10868748.77 | 0.344771E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158913E+10 |
February | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116517E+10 |
March | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986040E+09 |
April | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9962587.98 | 0.659222E+09 |
May | 0.460320E+11 | 0.411354E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12327839.31 | 0.344051E+09 |
June | 0.446286E+11 | 0.398539E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65309017.63 | 0.166439E+09 |
July | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66530827.59 | 86805104.70 |
August | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62291777.27 | 0.124182E+09 |
September | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37208599.16 | 0.305515E+09 |
October | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256263.80 | 0.647160E+09 |
November | 0.444343E+11 | 0.398222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970046E+09 |
December | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139015E+10 |
Annual Sum or Average | 0.541686E+12 | 0.483681E+11 | 0.175857E+12 | 0.253887E+09 | 0.843391E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86805104.70 |
Maximum of Months | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66530827.59 | 0.158913E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158893E+10 |
February | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116574E+10 |
March | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989036E+09 |
April | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9948101.70 | 0.662085E+09 |
May | 0.460320E+11 | 0.411354E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12309813.38 | 0.346089E+09 |
June | 0.446286E+11 | 0.398539E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65169364.12 | 0.167308E+09 |
July | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66364427.27 | 87065388.17 |
August | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62222266.77 | 0.124670E+09 |
September | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37180896.28 | 0.307073E+09 |
October | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256142.42 | 0.650211E+09 |
November | 0.444343E+11 | 0.398222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972349E+09 |
December | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139234E+10 |
Annual Sum or Average | 0.541686E+12 | 0.483681E+11 | 0.175857E+12 | 0.253451E+09 | 0.845290E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87065388.17 |
Maximum of Months | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66364427.27 | 0.158893E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.118068E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144993E+10 |
February | 0.369574E+10 | 0.106604E+10 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107437E+10 |
March | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939573E+09 |
April | 0.396281E+10 | 0.114064E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6223568.69 | 0.637141E+09 |
May | 0.409635E+10 | 0.118272E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6819504.99 | 0.343761E+09 |
June | 0.397146E+10 | 0.114588E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 42871385.35 | 0.166047E+09 |
July | 0.408770E+10 | 0.117749E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 39104530.10 | 87163765.01 |
August | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 38493774.78 | 0.122270E+09 |
September | 0.396281E+10 | 0.114064E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 23351172.69 | 0.301049E+09 |
October | 0.408770E+10 | 0.118068E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 81621.15 | 0.631826E+09 |
November | 0.395417E+10 | 0.114497E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916312E+09 |
December | 0.408770E+10 | 0.117749E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130100E+10 |
Annual Sum or Average | 0.482041E+11 | 0.139068E+11 | 0.398993E+12 | 0.359593E+12 | 0.156946E+09 | 0.797044E+10 | |||
Minimum of Months | 0.369574E+10 | 0.106604E+10 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87163765.01 |
Maximum of Months | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 42871385.35 | 0.144993E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.234644E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101468E+10 |
February | 0.00 | 0.211862E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726074E+09 |
March | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617405E+09 |
April | 0.00 | 0.226688E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6610467.93 | 0.406248E+09 |
May | 0.00 | 0.235050E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8324521.35 | 0.204209E+09 |
June | 0.00 | 0.227728E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43999512.10 | 96867127.17 |
July | 0.00 | 0.234011E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45173946.06 | 49227294.77 |
August | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41910056.08 | 70698960.74 |
September | 0.00 | 0.226688E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24717764.23 | 0.182695E+09 |
October | 0.00 | 0.234644E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 181290.37 | 0.396847E+09 |
November | 0.00 | 0.227547E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609439E+09 |
December | 0.00 | 0.234011E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882325E+09 |
Annual Sum or Average | 0.276379E+11 | 0.124715E+11 | 0.170918E+09 | 0.525672E+10 | |||||
Minimum of Months | 0.00 | 0.211862E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49227294.77 |
Maximum of Months | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45173946.06 | 0.101468E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.375444E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705882E+09 |
February | 0.00 | 0.338992E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505562E+09 |
March | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429243E+09 |
April | 0.00 | 0.362715E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4596161.15 | 0.282387E+09 |
May | 0.00 | 0.376095E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5787829.27 | 0.141846E+09 |
June | 0.00 | 0.364378E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30596097.97 | 67312032.22 |
July | 0.00 | 0.374431E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31409465.28 | 34226568.55 |
August | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29139772.16 | 49128871.38 |
September | 0.00 | 0.362715E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17186232.64 | 0.126878E+09 |
October | 0.00 | 0.375444E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 126051.22 | 0.275790E+09 |
November | 0.00 | 0.364089E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423550E+09 |
December | 0.00 | 0.374431E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613000E+09 |
Annual Sum or Average | 0.442222E+10 | 0.359769E+10 | 0.118842E+09 | 0.365481E+10 | |||||
Minimum of Months | 0.00 | 0.338992E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34226568.55 |
Maximum of Months | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31409465.28 | 0.705882E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.185439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789747E+09 |
February | 0.00 | 0.167435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578488E+09 |
March | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475917E+09 |
April | 0.00 | 0.179152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5035021.12 | 0.313334E+09 |
May | 0.00 | 0.185761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6312979.36 | 0.157788E+09 |
June | 0.00 | 0.179973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33527452.60 | 75035299.56 |
July | 0.00 | 0.184939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34334416.92 | 38356189.57 |
August | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31871312.95 | 54896908.52 |
September | 0.00 | 0.179152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18827987.14 | 0.141096E+09 |
October | 0.00 | 0.185439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134261.20 | 0.306109E+09 |
November | 0.00 | 0.179831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470201E+09 |
December | 0.00 | 0.184939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677613E+09 |
Annual Sum or Average | 0.218422E+11 | 0.130043E+09 | 0.407858E+10 | ||||||
Minimum of Months | 0.00 | 0.167435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38356189.57 |
Maximum of Months | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34334416.92 | 0.789747E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.196259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138936E+10 |
February | 0.00 | 0.177204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100342E+10 |
March | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844806E+09 |
April | 0.00 | 0.189604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8776826.55 | 0.556809E+09 |
May | 0.00 | 0.196599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10929576.65 | 0.281350E+09 |
June | 0.00 | 0.190474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58210869.08 | 0.134191E+09 |
July | 0.00 | 0.195729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59387241.18 | 69096475.36 |
August | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55277692.40 | 98496288.08 |
September | 0.00 | 0.189604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32339585.56 | 0.251492E+09 |
October | 0.00 | 0.196259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224775.84 | 0.544186E+09 |
November | 0.00 | 0.190323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833547E+09 |
December | 0.00 | 0.195729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120395E+10 |
Annual Sum or Average | 0.231166E+11 | 0.225147E+09 | 0.721070E+10 | ||||||
Minimum of Months | 0.00 | 0.177204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69096475.36 |
Maximum of Months | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59387241.18 | 0.138936E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 17018.80 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 17018.80 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 17018.80 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 17018.80 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 17018.80 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 17018.80 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 17018.80 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 17018.80 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 17018.80 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 17018.80 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 17018.80 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 17018.80 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 922.95 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1182.32 | 05-JAN-20:55 |
February | 1169.53 | 01-FEB-00:10 | 922.95 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1113.14 | 05-FEB-23:55 |
March | 1169.53 | 01-MAR-00:10 | 922.95 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 985.35 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 922.95 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.69 | 15-APR-16:10 | 702.22 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 922.95 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.92 | 31-MAY-13:00 | 495.28 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 922.95 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.55 | 11-JUN-15:00 | 376.74 | 03-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 922.95 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.37 | 26-JUL-15:10 | 256.69 | 23-JUL-04:00 |
August | 1169.53 | 01-AUG-00:10 | 922.95 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.49 | 04-AUG-15:00 | 297.66 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 922.95 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.51 | 06-SEP-15:00 | 537.15 | 30-SEP-01:00 |
October | 1169.53 | 02-OCT-00:10 | 922.95 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 20-OCT-15:00 | 599.56 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 922.95 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1168.78 | 25-NOV-20:53 |
December | 1169.53 | 01-DEC-00:10 | 922.95 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1150.01 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 922.95 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.69 | |||||
Maximum of Months | 1169.53 | 922.95 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 273.49 | 1182.32 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1068.78 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 248.82 | 05-JAN-21:03 |
February | 1354.32 | 01-FEB-00:10 | 1068.78 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 233.87 | 05-FEB-23:55 |
March | 1354.32 | 01-MAR-00:10 | 1068.78 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 206.75 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 1068.78 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 15-APR-16:20 | 147.40 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1068.78 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 31-MAY-13:00 | 103.95 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 1068.78 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.89 | 11-JUN-15:00 | 79.07 | 03-JUN-04:00 |
July | 1354.32 | 01-JUL-00:10 | 1068.78 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 26-JUL-15:30 | 53.86 | 23-JUL-04:00 |
August | 1354.32 | 01-AUG-00:10 | 1068.78 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 04-AUG-15:00 | 62.48 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 1068.78 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 07-SEP-14:00 | 112.72 | 30-SEP-01:00 |
October | 1354.32 | 02-OCT-00:10 | 1068.78 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 20-OCT-15:00 | 125.83 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 1068.78 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 245.95 | 25-NOV-21:01 |
December | 1354.32 | 01-DEC-00:10 | 1068.78 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 243.10 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 1068.78 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 | |||||
Maximum of Months | 1354.32 | 1068.78 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 248.82 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 429.55 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 817.36 | 05-JAN-20:50 |
February | 907.20 | 01-FEB-00:10 | 429.55 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 758.97 | 05-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 429.55 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 643.40 | 05-MAR-21:00 |
April | 907.20 | 01-APR-00:10 | 429.55 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 133.44 | 15-APR-16:00 | 487.86 | 03-APR-21:00 |
May | 907.20 | 01-MAY-00:10 | 429.55 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 133.50 | 31-MAY-13:00 | 326.33 | 01-MAY-21:00 |
June | 907.20 | 01-JUN-00:10 | 429.55 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 182.62 | 11-JUN-15:00 | 243.13 | 03-JUN-04:00 |
July | 907.20 | 01-JUL-00:10 | 429.55 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 135.14 | 26-JUL-15:00 | 165.77 | 23-JUL-04:00 |
August | 907.20 | 01-AUG-00:10 | 429.55 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 184.50 | 04-AUG-15:00 | 192.08 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 429.55 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 164.26 | 06-SEP-14:00 | 346.64 | 30-SEP-01:00 |
October | 907.20 | 02-OCT-00:10 | 429.55 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 41.84 | 20-OCT-15:00 | 401.72 | 31-OCT-21:00 |
November | 907.20 | 01-NOV-00:10 | 429.55 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 788.26 | 25-NOV-20:50 |
December | 907.20 | 01-DEC-00:10 | 429.55 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 798.63 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 165.77 | ||||||
Maximum of Months | 907.20 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 184.50 | 817.36 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2252.35 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2987.86 | 07-JAN-02:28 |
February | 15368.40 | 01-FEB-00:10 | 2252.35 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2879.51 | 05-FEB-23:55 |
March | 15368.40 | 01-MAR-00:10 | 2252.35 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2486.60 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 2252.35 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.41 | 15-APR-15:40 | 1772.77 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2252.35 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.58 | 31-MAY-13:00 | 1250.35 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 2252.35 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.80 | 11-JUN-15:00 | 951.07 | 03-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 2252.35 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 493.11 | 26-JUL-15:30 | 651.30 | 24-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2252.35 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.16 | 04-AUG-15:02 | 751.64 | 07-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 2252.35 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.65 | 06-SEP-15:00 | 1355.44 | 30-SEP-01:00 |
October | 15368.40 | 02-OCT-00:10 | 2252.35 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.60 | 20-OCT-15:00 | 1513.47 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 2252.35 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2950.56 | 25-NOV-21:00 |
December | 15368.40 | 01-DEC-00:10 | 2252.35 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2923.81 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 2252.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.30 | |||||
Maximum of Months | 15368.40 | 2252.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 690.16 | 2987.86 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 13201.13 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5967.47 | 05-JAN-21:03 |
February | 45622.98 | 01-FEB-00:10 | 13201.13 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5719.51 | 05-FEB-23:55 |
March | 45622.98 | 01-MAR-00:10 | 13201.13 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4958.92 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 13201.13 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 969.97 | 15-APR-15:30 | 3534.61 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 13201.13 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 976.23 | 31-MAY-13:00 | 2502.11 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 13201.13 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1316.31 | 11-JUN-15:00 | 1927.72 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 13201.13 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 983.41 | 26-JUL-15:00 | 1329.76 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 13201.13 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.47 | 04-AUG-15:10 | 1524.51 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 13201.13 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.52 | 07-SEP-14:00 | 2717.66 | 30-SEP-01:00 |
October | 45622.98 | 02-OCT-00:10 | 13201.13 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.48 | 20-OCT-15:00 | 3017.64 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 13201.13 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5897.39 | 25-NOV-21:01 |
December | 45622.98 | 01-DEC-00:10 | 13201.13 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5830.65 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 13201.13 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.76 | |||||
Maximum of Months | 45622.98 | 13201.13 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.47 | 5967.47 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 418.45 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 467.86 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 290.79 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:10 | 111.81 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 06-SEP-15:10 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.20 | 26-NOV-06:55 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.73 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 467.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 415.41 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 464.01 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 290.78 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:10 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:08 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.36 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.16 | 26-NOV-06:55 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 464.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 290.37 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 112.02 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 290.37 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 128.55 | 02-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 290.37 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 77.53 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 290.37 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 15-APR-15:00 | 56.95 | 03-APR-21:00 |
May | 0.00 | 01-MAY-00:10 | 290.37 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 31-MAY-13:00 | 43.36 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 290.37 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 11-JUN-15:00 | 34.79 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 290.37 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 26-JUL-15:00 | 25.32 | 24-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 290.37 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 04-AUG-15:00 | 28.99 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 290.37 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 07-SEP-14:00 | 46.67 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 290.37 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 51.78 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 290.37 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 105.37 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 290.37 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 92.61 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 290.37 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 | |||||
Maximum of Months | 0.00 | 290.37 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 128.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 290.45 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 115.63 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 290.45 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 131.41 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 290.45 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 81.16 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 290.45 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 15-APR-15:08 | 57.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 290.45 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 31-MAY-15:10 | 40.95 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 290.45 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 11-JUN-15:10 | 31.20 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 290.45 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 26-JUL-15:10 | 21.35 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 290.45 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 04-AUG-15:10 | 24.72 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 290.45 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 06-SEP-15:08 | 44.37 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 290.45 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 20-OCT-15:08 | 49.50 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 290.45 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 110.29 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 290.45 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.37 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 131.41 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 415.20 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 464.92 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:08 | 111.81 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.59 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:08 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.19 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.74 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 464.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 411.86 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.93 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 290.78 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:08 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:08 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.57 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:08 | 177.36 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.16 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 460.93 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.91 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 476.81 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.33 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.08 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 31-MAY-15:10 | 147.18 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.25 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 | 26-JUL-15:10 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 04-AUG-15:10 | 89.02 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 06-SEP-15:10 | 159.46 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 20-OCT-15:10 | 177.86 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.78 | 26-NOV-06:55 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.30 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 476.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 419.32 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 472.70 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 291.29 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.06 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 | 31-MAY-15:10 | 147.16 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.23 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 26-JUL-15:10 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 06-SEP-15:10 | 159.44 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:10 | 177.84 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 395.73 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.25 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 472.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 290.45 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 214.82 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 290.45 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 243.93 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 290.45 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 149.04 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 290.45 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-APR-15:50 | 106.45 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 290.45 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 31-MAY-15:10 | 75.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 290.45 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 11-JUN-15:10 | 57.42 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 290.45 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 26-JUL-15:10 | 39.36 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 290.45 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 04-AUG-15:10 | 45.54 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 290.45 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 06-SEP-15:10 | 81.58 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 290.45 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 20-OCT-15:10 | 90.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 290.45 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 202.48 | 26-NOV-06:55 |
December | 180.00 | 01-DEC-00:10 | 290.45 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.11 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | |||||
Maximum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 243.93 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3955.32 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 853.89 | 05-JAN-20:50 |
February | 26988.77 | 01-FEB-00:10 | 3955.32 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 821.36 | 05-FEB-23:55 |
March | 26988.77 | 01-MAR-00:10 | 3955.32 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 716.08 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 3955.32 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.85 | 15-APR-15:30 | 515.32 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3955.32 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | 31-MAY-13:00 | 374.55 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3955.32 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.22 | 11-JUN-15:00 | 290.83 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3955.32 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.73 | 26-JUL-15:20 | 204.97 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3955.32 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.83 | 04-AUG-15:03 | 233.57 | 07-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3955.32 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.99 | 06-SEP-14:20 | 404.25 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 3955.32 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 20-OCT-15:00 | 444.34 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3955.32 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 841.83 | 25-NOV-21:01 |
December | 26988.77 | 01-DEC-00:10 | 3955.32 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 843.76 | 08-DEC-23:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.97 | |||||
Maximum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.83 | 853.89 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3955.32 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 856.43 | 05-JAN-20:50 |
February | 26988.77 | 01-FEB-00:10 | 3955.32 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 821.35 | 05-FEB-23:55 |
March | 26988.77 | 01-MAR-00:10 | 3955.32 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 717.54 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 3955.32 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.84 | 15-APR-15:40 | 516.10 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3955.32 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.66 | 31-MAY-13:00 | 375.58 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3955.32 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.19 | 11-JUN-15:00 | 291.10 | 01-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3955.32 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.72 | 26-JUL-15:30 | 205.21 | 24-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3955.32 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.83 | 04-AUG-15:02 | 234.47 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3955.32 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.98 | 06-SEP-14:40 | 405.63 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 3955.32 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 20-OCT-15:00 | 445.53 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3955.32 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 842.01 | 25-NOV-21:01 |
December | 26988.77 | 01-DEC-00:10 | 3955.32 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 845.59 | 08-DEC-23:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.21 | |||||
Maximum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.83 | 856.43 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1137.23 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 811.13 | 05-JAN-19:07 |
February | 2401.70 | 01-FEB-00:10 | 1137.23 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 754.21 | 05-FEB-22:00 |
March | 2401.70 | 01-MAR-00:10 | 1137.23 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 643.68 | 05-MAR-23:40 |
April | 2401.70 | 01-APR-00:10 | 1137.23 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 106.56 | 15-APR-15:00 | 480.77 | 03-APR-21:00 |
May | 2401.70 | 01-MAY-00:10 | 1137.23 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 107.60 | 31-MAY-15:00 | 331.12 | 02-MAY-07:10 |
June | 2401.70 | 01-JUN-00:10 | 1137.23 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 150.95 | 11-JUN-15:00 | 251.66 | 01-JUN-18:00 |
July | 2401.70 | 01-JUL-00:10 | 1137.23 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 109.96 | 26-JUL-15:00 | 172.44 | 24-JUL-05:20 |
August | 2401.70 | 01-AUG-00:10 | 1137.23 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 157.96 | 04-AUG-15:00 | 215.32 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1137.23 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 141.63 | 06-SEP-14:00 | 359.98 | 29-SEP-22:50 |
October | 2401.70 | 02-OCT-00:10 | 1137.23 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 18.27 | 20-OCT-15:00 | 401.62 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1137.23 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 793.65 | 25-NOV-20:50 |
December | 2401.70 | 01-DEC-00:10 | 1137.23 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 779.65 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1137.23 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 172.44 | ||||||
Maximum of Months | 2401.70 | 1137.23 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 157.96 | 811.13 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2260.10 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 547.43 | 05-JAN-21:03 |
February | 0.00 | 2260.10 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 520.24 | 02-FEB-06:10 |
March | 0.00 | 2260.10 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 455.22 | 06-MAR-01:00 |
April | 0.00 | 2260.10 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 15-APR-15:03 | 324.51 | 03-APR-06:00 |
May | 0.00 | 2260.10 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.60 | 31-MAY-13:00 | 228.87 | 03-MAY-03:00 |
June | 0.00 | 2260.10 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 11-JUN-15:00 | 174.05 | 03-JUN-04:00 |
July | 0.00 | 2260.10 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.28 | 26-JUL-15:07 | 118.58 | 23-JUL-04:00 |
August | 0.00 | 2260.10 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.38 | 04-AUG-15:00 | 137.57 | 07-AUG-06:00 |
September | 0.00 | 2260.10 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.68 | 07-SEP-14:00 | 248.17 | 30-SEP-01:00 |
October | 0.00 | 2260.10 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 20-OCT-15:00 | 277.03 | 23-OCT-06:00 |
November | 0.00 | 2260.10 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 541.91 | 25-NOV-21:01 |
December | 0.00 | 2260.10 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 533.46 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.58 | ||||
Maximum of Months | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 126.38 | 547.43 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 361.63 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 379.85 | 05-JAN-21:03 |
February | 0.00 | 361.63 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 372.71 | 02-FEB-06:03 |
March | 0.00 | 361.63 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 316.51 | 06-MAR-01:00 |
April | 0.00 | 361.63 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.92 | 15-APR-15:00 | 225.64 | 03-APR-06:00 |
May | 0.00 | 361.63 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 | 31-MAY-13:00 | 159.13 | 03-MAY-03:00 |
June | 0.00 | 361.63 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 11-JUN-15:00 | 121.02 | 03-JUN-04:00 |
July | 0.00 | 361.63 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.77 | 26-JUL-15:20 | 82.46 | 23-JUL-04:00 |
August | 0.00 | 361.63 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 | 04-AUG-15:00 | 95.66 | 07-AUG-06:00 |
September | 0.00 | 361.63 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 | 07-SEP-14:00 | 172.56 | 30-SEP-01:00 |
October | 0.00 | 361.63 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 20-OCT-15:00 | 192.62 | 23-OCT-06:00 |
November | 0.00 | 361.63 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 376.47 | 25-NOV-21:01 |
December | 0.00 | 361.63 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 369.48 | 08-DEC-23:57 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.46 | ||||
Maximum of Months | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 | 379.85 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1786.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 435.80 | 30-JAN-08:00 |
February | 0.00 | 1786.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 472.46 | 02-FEB-06:03 |
March | 0.00 | 1786.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 350.62 | 06-MAR-01:00 |
April | 0.00 | 1786.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.18 | 15-APR-15:00 | 250.03 | 03-APR-06:00 |
May | 0.00 | 1786.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.62 | 31-MAY-13:00 | 176.45 | 03-MAY-03:00 |
June | 0.00 | 1786.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.64 | 11-JUN-15:00 | 134.27 | 03-JUN-04:00 |
July | 0.00 | 1786.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 | 26-JUL-15:10 | 91.59 | 23-JUL-04:00 |
August | 0.00 | 1786.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 | 04-AUG-15:00 | 106.20 | 07-AUG-06:00 |
September | 0.00 | 1786.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.60 | 07-SEP-14:00 | 191.29 | 30-SEP-01:00 |
October | 0.00 | 1786.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 20-OCT-15:00 | 213.51 | 23-OCT-06:00 |
November | 0.00 | 1786.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 432.43 | 26-NOV-06:55 |
December | 0.00 | 1786.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 409.02 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | |||
Maximum of Months | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 | 472.46 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1890.37 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 745.22 | 05-JAN-20:53 |
February | 0.00 | 1890.37 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 734.65 | 02-FEB-06:00 |
March | 0.00 | 1890.37 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 621.58 | 06-MAR-01:00 |
April | 0.00 | 1890.37 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 15-APR-15:05 | 443.50 | 03-APR-06:00 |
May | 0.00 | 1890.37 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.44 | 31-MAY-15:00 | 313.23 | 03-MAY-03:00 |
June | 0.00 | 1890.37 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.22 | 11-JUN-15:00 | 238.54 | 03-JUN-04:00 |
July | 0.00 | 1890.37 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 | 26-JUL-15:00 | 162.97 | 23-JUL-04:00 |
August | 0.00 | 1890.37 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.50 | 04-AUG-16:00 | 188.84 | 07-AUG-06:00 |
September | 0.00 | 1890.37 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.25 | 06-SEP-15:00 | 339.48 | 30-SEP-01:00 |
October | 0.00 | 1890.37 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 20-OCT-15:00 | 378.84 | 23-OCT-06:00 |
November | 0.00 | 1890.37 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 738.06 | 25-NOV-21:01 |
December | 0.00 | 1890.37 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 725.35 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1890.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 | |||
Maximum of Months | 0.00 | 1890.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.50 | 745.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 67059.34 | 19-JAN-01:51 | 115018.92 | 28364.66 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53609.09 | 01-FEB-08:00 | 5111.95 | 9454.89 | 6387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18396.60 | 28-MAR-20:00 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18059.53 | 12-APR-19:30 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19334.37 | 10-MAY-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21016.63 | 06-JUN-19:30 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22309.17 | 10-JUL-20:00 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24194.90 | 25-AUG-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25605.09 | 07-SEP-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22823.61 | 20-OCT-18:10 | 53675.50 | 90766.91 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64916.66 | 25-NOV-21:32 | 53675.50 | 79421.05 | 51101.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19270.18 | 01-DEC-22:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18059.53 | 5111.95 | 9454.89 | 6387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67059.34 | 115018.92 | 90766.91 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3661.13 | 19-JAN-01:51 | 11695.32 | 1538.25 | 1804.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.54 |
February | 2846.06 | 08-FEB-13:30 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.94 |
March | 3029.71 | 25-MAR-14:10 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 |
April | 3595.89 | 15-APR-13:20 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 141.14 | 0.00 |
May | 2859.24 | 05-MAY-13:00 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 0.00 |
June | 3112.97 | 26-JUN-18:07 | 5457.82 | 4922.39 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 190.34 | 0.00 |
July | 3157.42 | 30-JUL-12:00 | 389.84 | 307.65 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 124.81 | 0.00 |
August | 3353.75 | 29-AUG-13:30 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 0.00 |
September | 3821.11 | 07-SEP-13:10 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 196.33 | 0.00 |
October | 3949.38 | 20-OCT-13:10 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
November | 3468.47 | 04-NOV-13:10 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.22 |
December | 2967.89 | 03-DEC-13:00 | 389.84 | 307.65 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2846.06 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3949.38 | 11695.32 | 4922.39 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 196.33 | 1082.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5049.65 | 19-JAN-01:51 | 13543.20 | 1781.30 | 2089.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.22 |
February | 3643.40 | 01-FEB-00:01 | 9480.24 | 1662.54 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.22 |
March | 1909.97 | 19-MAR-21:00 | 1203.84 | 712.52 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
April | 2287.79 | 18-APR-19:10 | 2106.72 | 2137.56 | 1587.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 |
May | 2392.28 | 31-MAY-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
June | 2420.08 | 26-JUN-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 0.00 |
July | 2414.29 | 03-JUL-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 0.00 |
August | 2401.65 | 02-AUG-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 | 0.00 |
September | 2412.89 | 07-SEP-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 0.00 |
October | 2046.33 | 20-OCT-18:10 | 6320.16 | 5700.15 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 |
November | 4722.98 | 25-NOV-21:32 | 6320.16 | 4987.63 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.16 |
December | 1626.54 | 01-DEC-22:03 | 4062.96 | 2137.56 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1626.54 | 1203.84 | 712.52 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5049.65 | 13543.20 | 5700.15 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 235.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5252.13 | 19-JAN-01:51 | 0.00 | 3766.83 | 2209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.47 |
February | 3487.39 | 01-FEB-08:00 | 0.00 | 1255.61 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.27 |
March | 1904.84 | 28-MAR-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
April | 2440.57 | 18-APR-19:50 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 |
May | 2637.83 | 31-MAY-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 34.35 | 0.00 |
June | 2680.86 | 26-JUN-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.49 | 0.00 |
July | 2671.40 | 03-JUL-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 0.00 |
August | 2667.81 | 03-AUG-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 40.09 | 0.00 |
September | 2636.68 | 07-SEP-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 | 0.00 |
October | 2178.80 | 20-OCT-19:40 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 |
November | 5043.32 | 25-NOV-21:32 | 0.00 | 10547.13 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.94 |
December | 1546.13 | 04-DEC-21:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1546.13 | 0.00 | 1255.61 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5252.13 | 0.00 | 10547.13 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 57.49 | 523.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1689.37 | 19-JAN-01:51 | 0.00 | 602.72 | 637.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.15 |
February | 1003.46 | 01-FEB-07:15 | 0.00 | 401.81 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.43 |
March | 481.06 | 28-MAR-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.27 |
April | 760.15 | 16-APR-20:00 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 0.00 |
May | 851.13 | 31-MAY-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 | 0.00 |
June | 953.50 | 26-JUN-19:50 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 | 0.00 |
July | 919.18 | 03-JUL-19:10 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 49.14 | 0.00 |
August | 893.62 | 03-AUG-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 0.00 |
September | 844.16 | 07-SEP-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 | 0.00 |
October | 589.37 | 20-OCT-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 |
November | 1608.29 | 25-NOV-21:32 | 0.00 | 1687.61 | 1223.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.17 |
December | 160.72 | 04-DEC-22:00 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 160.72 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1689.37 | 0.00 | 1687.61 | 1223.53 | 0.00 | 0.00 | 0.00 | 0.00 | 49.14 | 366.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54228.11 | 05-JAN-21:51 | 5644.80 | 2672.76 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 622.58 |
February | 38073.27 | 01-FEB-22:00 | 806.40 | 381.82 | 4332.13 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 584.97 |
March | 36192.46 | 28-MAR-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 185.50 |
April | 37289.53 | 18-APR-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 68.24 |
May | 38121.72 | 31-MAY-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 26.36 | 0.00 |
June | 38211.65 | 26-JUN-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 59.07 | 0.00 |
July | 38107.21 | 03-JUL-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 58.75 | 0.00 |
August | 38123.60 | 03-AUG-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 34.77 | 0.00 |
September | 38131.47 | 07-SEP-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.48 | 0.00 |
October | 36597.35 | 20-OCT-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 127.19 |
November | 56941.19 | 25-NOV-21:21 | 7056.00 | 3340.95 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 641.76 |
December | 35194.36 | 04-DEC-21:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 347.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35194.36 | 705.60 | 381.82 | 4332.13 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56941.19 | 7056.00 | 3340.95 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 59.07 | 641.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23269.17 | 19-JAN-01:51 | 153684.00 | 3753.92 | 2540.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2751.32 |
February | 16541.77 | 01-FEB-00:01 | 107578.80 | 3503.66 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2510.77 |
March | 12460.90 | 25-MAR-14:00 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 |
April | 14282.29 | 15-APR-13:00 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 379.02 | 0.00 |
May | 13375.45 | 31-MAY-21:05 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 | 0.00 |
June | 13904.54 | 26-JUN-21:20 | 15368.40 | 1501.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 230.17 | 0.00 |
July | 13894.43 | 25-JUL-21:20 | 15368.40 | 1501.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 268.45 | 0.00 |
August | 13801.49 | 02-AUG-21:10 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 182.57 | 0.00 |
September | 14786.98 | 16-SEP-13:10 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 375.76 | 0.00 |
October | 15230.54 | 20-OCT-12:50 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 |
November | 19628.03 | 25-NOV-21:21 | 119532.00 | 17518.31 | 8128.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.80 |
December | 12361.63 | 03-DEC-13:00 | 5122.80 | 750.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12361.63 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23269.17 | 153684.00 | 17518.31 | 8128.62 | 0.00 | 0.00 | 0.00 | 0.00 | 379.02 | 2751.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 98639.19 | 19-JAN-01:51 | 456229.80 | 22001.89 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5655.10 |
February | 71055.69 | 01-FEB-00:01 | 319360.86 | 20535.10 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5055.58 |
March | 38540.29 | 19-MAR-21:00 | 40553.76 | 8800.76 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.25 |
April | 44964.12 | 16-APR-20:10 | 81107.52 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 233.62 | 0.00 |
May | 46887.68 | 31-MAY-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 71.54 | 0.00 |
June | 47550.57 | 26-JUN-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 460.98 | 0.00 |
July | 47291.23 | 25-JUL-21:20 | 45622.98 | 8800.76 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 520.06 | 0.00 |
August | 47193.90 | 03-AUG-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 342.46 | 0.00 |
September | 47364.45 | 07-SEP-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 133.41 | 0.00 |
October | 40478.72 | 20-OCT-18:10 | 212907.24 | 70406.05 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.03 |
November | 88293.92 | 25-NOV-21:21 | 354845.40 | 102675.49 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5589.78 |
December | 32963.02 | 04-DEC-23:00 | 45622.98 | 8800.76 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 32963.02 | 40553.76 | 8800.76 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98639.19 | 456229.80 | 102675.49 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 520.06 | 5655.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3340.30 | 12-JAN-16:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.08 |
February | 3573.97 | 25-FEB-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.82 |
March | 3604.76 | 25-MAR-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
April | 3625.16 | 19-APR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 |
May | 3705.20 | 06-MAY-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 |
June | 3547.58 | 29-JUN-15:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 | 0.00 |
July | 3565.34 | 05-JUL-15:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 | 0.00 |
August | 3568.74 | 04-AUG-15:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 70.29 | 0.00 |
September | 3718.29 | 20-SEP-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
October | 3638.58 | 19-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
November | 3649.68 | 04-NOV-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 |
December | 3375.34 | 02-DEC-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3340.30 | 378.00 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3718.29 | 680.40 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 70.29 | 131.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 686.30 | 12-JAN-19:04 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 |
February | 3350.85 | 24-FEB-16:02 | 583.20 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.86 |
March | 3521.47 | 25-MAR-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 |
April | 3551.36 | 19-APR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.99 |
May | 3643.45 | 06-MAY-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 |
June | 3520.02 | 30-JUN-15:02 | 583.20 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 42.91 | 0.00 |
July | 3514.23 | 04-JUL-18:02 | 702.00 | 2771.87 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 0.00 |
August | 3494.92 | 10-AUG-18:02 | 831.60 | 2466.96 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 | 0.00 |
September | 3630.95 | 20-SEP-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
October | 3525.28 | 19-OCT-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
November | 3525.35 | 04-NOV-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.90 |
December | 693.94 | 01-DEC-16:03 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 686.30 | 378.00 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3643.45 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 42.91 | 164.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 370.29 | 30-JAN-10:40 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.87 |
February | 496.78 | 08-FEB-13:40 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 |
March | 568.23 | 24-MAR-12:50 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
April | 677.29 | 15-APR-12:50 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 0.00 |
May | 547.28 | 05-MAY-17:17 | 0.00 | 778.19 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.00 |
June | 694.37 | 18-JUN-20:20 | 0.00 | 290.37 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
July | 632.88 | 25-JUL-19:30 | 0.00 | 290.37 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 |
August | 597.33 | 29-AUG-13:20 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
September | 749.17 | 17-SEP-13:20 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
October | 824.70 | 20-OCT-12:30 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
November | 820.66 | 04-NOV-12:20 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 |
December | 591.21 | 03-DEC-13:00 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 370.29 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 824.70 | 0.00 | 778.19 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 101.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 685.19 | 01-JAN-09:02 | 324.00 | 975.91 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
February | 1038.44 | 25-FEB-09:02 | 270.00 | 813.26 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 |
March | 1104.49 | 25-MAR-18:02 | 702.00 | 1742.69 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 |
April | 1153.46 | 30-APR-18:01 | 819.00 | 2033.14 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
May | 1168.98 | 06-MAY-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
June | 1139.94 | 16-JUN-18:02 | 831.60 | 1551.00 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
July | 1145.47 | 18-JUL-18:02 | 831.60 | 1551.00 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
August | 1148.36 | 09-AUG-15:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 |
September | 1147.39 | 07-SEP-15:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 0.00 |
October | 1089.52 | 29-OCT-18:01 | 819.00 | 2033.14 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 |
November | 1079.16 | 03-NOV-18:02 | 831.60 | 1551.00 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
December | 753.70 | 02-DEC-09:01 | 378.00 | 1138.56 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 685.19 | 270.00 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1168.98 | 831.60 | 2033.14 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 48.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 957.08 | 12-JAN-09:03 | 252.00 | 1423.06 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 |
February | 3130.30 | 24-FEB-09:01 | 252.00 | 1423.06 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.37 |
March | 3253.57 | 24-MAR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
April | 3274.68 | 30-APR-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 |
May | 3325.62 | 06-MAY-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
June | 3261.05 | 09-JUN-08:62 | 216.00 | 1219.77 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
July | 3219.66 | 01-JUL-08:61 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
August | 3223.53 | 11-AUG-15:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 0.00 |
September | 3342.33 | 20-SEP-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
October | 3281.55 | 19-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 |
November | 3278.75 | 04-NOV-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
December | 2251.66 | 03-DEC-09:02 | 324.00 | 1552.43 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 957.08 | 216.00 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3342.33 | 680.40 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 180.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 751.93 | 13-JAN-19:04 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.59 |
February | 3002.35 | 24-FEB-09:01 | 252.00 | 1422.89 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.00 |
March | 3123.48 | 28-MAR-08:62 | 216.00 | 1219.62 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.43 |
April | 3244.05 | 30-APR-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
May | 3297.02 | 06-MAY-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 |
June | 3212.56 | 24-JUN-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
July | 3206.74 | 01-JUL-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
August | 3174.28 | 09-AUG-08:62 | 216.00 | 1219.62 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 |
September | 3273.50 | 20-SEP-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
October | 2865.46 | 08-OCT-08:62 | 270.00 | 1293.54 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.70 |
November | 2060.44 | 04-NOV-08:62 | 270.00 | 1293.54 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.98 |
December | 826.69 | 02-DEC-09:03 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 751.93 | 216.00 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3297.02 | 970.20 | 2878.13 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 149.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4793.90 | 19-JAN-08:00 | 0.00 | 992.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.11 |
February | 4827.93 | 02-FEB-06:03 | 0.00 | 3175.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.46 |
March | 1661.05 | 24-MAR-13:40 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 |
April | 2446.27 | 15-APR-18:03 | 0.00 | 8335.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 | 0.00 |
May | 2464.01 | 31-MAY-18:30 | 0.00 | 1587.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 0.00 |
June | 2731.01 | 26-JUN-19:10 | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 | 0.00 |
July | 2617.05 | 03-JUL-19:10 | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 | 0.00 |
August | 2464.87 | 04-AUG-15:05 | 0.00 | 2976.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.90 | 0.00 |
September | 2749.00 | 08-SEP-13:30 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.42 | 0.00 |
October | 2282.93 | 20-OCT-14:00 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 0.00 |
November | 4875.23 | 26-NOV-06:55 | 0.00 | 1190.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.43 |
December | 1272.77 | 03-DEC-13:00 | 0.00 | 595.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1272.77 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4875.23 | 0.00 | 8335.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.90 | 472.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3452.05 | 12-JAN-16:02 | 583.20 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.76 |
February | 3716.79 | 25-FEB-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.00 |
March | 3748.11 | 25-MAR-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 |
April | 3789.00 | 19-APR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 |
May | 3873.09 | 06-MAY-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
June | 3765.43 | 25-JUN-18:02 | 702.00 | 2772.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 | 0.00 |
July | 3724.59 | 13-JUL-18:02 | 831.60 | 2467.25 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 | 0.00 |
August | 3679.61 | 11-AUG-18:02 | 831.60 | 2467.25 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 0.00 |
September | 3888.08 | 20-SEP-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
October | 3792.17 | 19-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 |
November | 3810.82 | 04-NOV-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 |
December | 3477.71 | 02-DEC-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3452.05 | 378.00 | 776.21 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3888.08 | 831.60 | 2772.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 | 130.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 885.65 | 12-JAN-16:03 | 583.20 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.96 |
February | 3415.61 | 24-FEB-16:02 | 583.20 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
March | 3643.38 | 24-MAR-18:01 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
April | 3706.64 | 19-APR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.43 |
May | 3806.01 | 06-MAY-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
June | 3716.77 | 25-JUN-18:02 | 702.00 | 2771.87 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 0.00 |
July | 3680.98 | 13-JUL-18:02 | 831.60 | 2466.96 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
August | 3655.81 | 13-AUG-15:02 | 324.00 | 914.72 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
September | 3790.79 | 20-SEP-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 |
October | 3641.59 | 19-OCT-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 |
November | 3651.88 | 04-NOV-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 |
December | 750.16 | 02-DEC-16:03 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 750.16 | 324.00 | 776.12 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3806.01 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 128.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1728.47 | 12-JAN-16:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 |
February | 1750.10 | 08-FEB-16:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 |
March | 1754.46 | 24-MAR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 |
April | 1748.40 | 19-APR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 |
May | 1772.54 | 06-MAY-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
June | 1694.82 | 11-JUN-15:02 | 324.00 | 575.09 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | 0.00 |
July | 1714.76 | 13-JUL-15:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 0.00 |
August | 1709.44 | 14-AUG-15:02 | 583.20 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.00 |
September | 1805.49 | 20-SEP-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
October | 1777.60 | 19-OCT-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 |
November | 1791.19 | 04-NOV-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 |
December | 1731.18 | 01-DEC-16:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1694.82 | 324.00 | 487.95 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1805.49 | 680.40 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | 90.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 47322.58 | 19-JAN-01:51 | 269887.68 | 6592.21 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.96 |
February | 34379.16 | 01-FEB-00:01 | 188921.38 | 6152.73 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.97 |
March | 20012.06 | 19-MAR-21:00 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 |
April | 22720.00 | 16-APR-21:00 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
May | 23827.52 | 31-MAY-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
June | 24094.86 | 26-JUN-21:30 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 | 0.00 |
July | 24022.48 | 25-JUL-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 0.00 |
August | 23941.76 | 03-AUG-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 0.00 |
September | 23718.55 | 07-SEP-21:30 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
October | 20602.15 | 20-OCT-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.64 |
November | 40537.44 | 25-NOV-21:21 | 209912.64 | 30763.64 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.46 |
December | 18137.88 | 04-DEC-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18137.88 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47322.58 | 269887.68 | 30763.64 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 797.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49998.41 | 19-JAN-01:51 | 269887.68 | 6592.21 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.97 |
February | 36359.29 | 01-FEB-00:01 | 188921.38 | 6152.73 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.76 |
March | 21283.19 | 19-MAR-21:00 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.27 |
April | 23970.83 | 16-APR-21:00 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 0.00 |
May | 25152.43 | 31-MAY-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 |
June | 25421.89 | 26-JUN-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 0.00 |
July | 25339.28 | 25-JUL-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 55.53 | 0.00 |
August | 25251.67 | 03-AUG-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 | 0.00 |
September | 25009.55 | 07-SEP-21:30 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
October | 21870.71 | 20-OCT-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 |
November | 42891.57 | 25-NOV-21:21 | 209912.64 | 30763.64 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.67 |
December | 19380.80 | 04-DEC-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 19380.80 | 23990.02 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49998.41 | 269887.68 | 30763.64 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 55.53 | 797.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41984.49 | 19-JAN-01:51 | 24017.04 | 1895.39 | 56652.02 | 14995.22 | 0.00 | 0.00 | 0.00 | 0.00 | 633.99 |
February | 30054.60 | 01-FEB-00:01 | 16811.93 | 1769.03 | 39656.41 | 10496.65 | 0.00 | 0.00 | 0.00 | 0.00 | 566.13 |
March | 27773.59 | 19-MAR-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 149.91 |
April | 29324.58 | 18-APR-10:40 | 1601.14 | 947.69 | 45336.32 | 56232.08 | 0.00 | 0.00 | 0.00 | 39.43 | 0.00 |
May | 29469.62 | 29-MAY-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 17.76 | 0.00 |
June | 29818.72 | 11-JUN-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 89.20 | 0.00 |
July | 29742.37 | 02-JUL-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 61.24 | 0.00 |
August | 29501.89 | 11-AUG-10:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 54.53 | 0.00 |
September | 29666.03 | 08-SEP-10:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 69.92 | 0.00 |
October | 28224.81 | 01-OCT-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 114.22 |
November | 43977.32 | 25-NOV-21:21 | 18679.92 | 8845.14 | 151121.06 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 668.32 |
December | 25741.36 | 03-DEC-11:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 303.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25741.36 | 533.71 | 315.90 | 15112.11 | 10496.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43977.32 | 24017.04 | 8845.14 | 151121.06 | 112464.16 | 0.00 | 0.00 | 0.00 | 89.20 | 668.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6507.27 | 19-JAN-01:51 | 0.00 | 3150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.96 |
February | 3491.57 | 24-FEB-13:50 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.33 |
March | 3788.18 | 19-MAR-13:00 | 0.00 | 420.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 |
April | 5409.07 | 15-APR-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.84 | 0.00 |
May | 5409.32 | 31-MAY-13:50 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.62 | 0.00 |
June | 5534.98 | 30-JUN-14:30 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 0.00 |
July | 5507.19 | 29-JUL-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 0.00 |
August | 5568.35 | 04-AUG-14:50 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.84 | 0.00 |
September | 5792.21 | 07-SEP-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.04 | 0.00 |
October | 5314.69 | 20-OCT-13:10 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
November | 6000.80 | 25-NOV-21:32 | 0.00 | 8821.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.07 |
December | 2775.89 | 03-DEC-12:50 | 0.00 | 630.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2775.89 | 0.00 | 420.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6507.27 | 0.00 | 8821.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.84 | 714.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.605401E+12 | 369653.82 | 30-JAN-20:10 | 0.120237E+13 | 1171279.59 | 30-JAN-19:30 |
February | 0.545567E+12 | 374872.30 | 02-FEB-20:19 | 0.919975E+12 | 1219350.34 | 02-FEB-20:49 |
March | 0.602777E+12 | 389374.33 | 19-MAR-19:19 | 0.613257E+12 | 542366.84 | 05-MAR-17:00 |
April | 0.626855E+12 | 556490.89 | 16-APR-19:10 | 0.512142E+12 | 394193.06 | 01-APR-16:49 |
May | 0.719778E+12 | 544405.31 | 31-MAY-19:40 | 0.506471E+12 | 360691.72 | 14-MAY-16:00 |
June | 0.848756E+12 | 587727.93 | 26-JUN-19:00 | 0.500008E+12 | 355696.95 | 12-JUN-16:00 |
July | 0.964916E+12 | 627943.55 | 26-JUL-18:10 | 0.523986E+12 | 360571.90 | 09-JUL-16:40 |
August | 0.925943E+12 | 615205.26 | 03-AUG-19:49 | 0.508076E+12 | 353168.53 | 31-AUG-16:00 |
September | 0.737065E+12 | 542320.60 | 07-SEP-19:10 | 0.463680E+12 | 354120.25 | 04-SEP-17:10 |
October | 0.628483E+12 | 404784.21 | 20-OCT-19:30 | 0.457615E+12 | 344490.81 | 01-OCT-16:00 |
November | 0.585783E+12 | 377464.65 | 03-NOV-19:30 | 0.642781E+12 | 1076800.42 | 25-NOV-21:00 |
December | 0.600773E+12 | 355611.56 | 04-DEC-20:49 | 0.837433E+12 | 717361.01 | 11-DEC-17:19 |
Annual Sum or Average | 0.839210E+13 | 0.768780E+13 | ||||
Minimum of Months | 0.545567E+12 | 355611.56 | 0.457615E+12 | 344490.81 | ||
Maximum of Months | 0.964916E+12 | 627943.55 | 0.120237E+13 | 1219350.34 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.118590E+12 | 0.259797E+11 | 0.148746E+12 | 0.858883E+11 | 0.157756E+12 | 0.773925E+10 | 0.00 | 0.920487E+09 | 0.00 | 0.00 | 0.461367E+11 | 0.771387E+10 | 0.00 |
February | 0.107087E+12 | 0.216467E+11 | 0.134341E+12 | 0.775767E+11 | 0.140472E+12 | 0.742663E+10 | 0.00 | 0.306754E+10 | 0.00 | 0.00 | 0.416718E+11 | 0.697199E+10 | 0.00 |
March | 0.118306E+12 | 0.214493E+11 | 0.148768E+12 | 0.858913E+11 | 0.147141E+12 | 0.999399E+10 | 0.00 | 0.136903E+11 | 0.00 | 0.00 | 0.435802E+11 | 0.770755E+10 | 0.00 |
April | 0.114747E+12 | 0.181783E+11 | 0.143913E+12 | 0.831176E+11 | 0.143518E+12 | 0.138762E+11 | 0.00 | 0.584903E+11 | 0.00 | 0.00 | 0.374798E+11 | 0.746798E+10 | 0.00 |
May | 0.118448E+12 | 0.165334E+11 | 0.148757E+12 | 0.858898E+11 | 0.151229E+12 | 0.216270E+11 | 0.00 | 0.140503E+12 | 0.00 | 0.00 | 0.227715E+11 | 0.770843E+10 | 0.00 |
June | 0.114519E+12 | 0.148697E+11 | 0.143963E+12 | 0.831203E+11 | 0.150672E+12 | 0.267006E+11 | 0.00 | 0.276475E+12 | 0.00 | 0.00 | 0.248696E+11 | 0.746164E+10 | 0.00 |
July | 0.118676E+12 | 0.158473E+11 | 0.148708E+12 | 0.858871E+11 | 0.157186E+12 | 0.313114E+11 | 0.00 | 0.370628E+12 | 0.00 | 0.00 | 0.226895E+11 | 0.771796E+10 | 0.00 |
August | 0.118306E+12 | 0.177929E+11 | 0.148768E+12 | 0.858913E+11 | 0.156115E+12 | 0.297525E+11 | 0.00 | 0.333539E+12 | 0.00 | 0.00 | 0.217760E+11 | 0.770988E+10 | 0.00 |
September | 0.114747E+12 | 0.196070E+11 | 0.143913E+12 | 0.831176E+11 | 0.148268E+12 | 0.216529E+11 | 0.00 | 0.165329E+12 | 0.00 | 0.00 | 0.268697E+11 | 0.746910E+10 | 0.00 |
October | 0.118590E+12 | 0.229250E+11 | 0.148746E+12 | 0.858884E+11 | 0.148478E+12 | 0.142862E+11 | 0.00 | 0.362691E+11 | 0.00 | 0.00 | 0.393093E+11 | 0.770746E+10 | 0.00 |
November | 0.114717E+12 | 0.244853E+11 | 0.143978E+12 | 0.831185E+11 | 0.144118E+12 | 0.938032E+10 | 0.00 | 0.114819E+11 | 0.00 | 0.00 | 0.410479E+11 | 0.745283E+10 | 0.00 |
December | 0.118676E+12 | 0.266095E+11 | 0.148708E+12 | 0.858871E+11 | 0.151536E+12 | 0.709669E+10 | 0.00 | 0.221770E+10 | 0.00 | 0.00 | 0.461367E+11 | 0.771627E+10 | 0.00 |
Annual Sum or Average | 0.139541E+13 | 0.245924E+12 | 0.175131E+13 | 0.101127E+13 | 0.179649E+13 | 0.200844E+12 | 0.00 | 0.141261E+13 | 0.414339E+12 | 0.908050E+11 | |||
Minimum of Months | 0.107087E+12 | 0.148697E+11 | 0.134341E+12 | 0.775767E+11 | 0.140472E+12 | 0.709669E+10 | 0.00 | 0.920487E+09 | 0.00 | 0.00 | 0.217760E+11 | 0.697199E+10 | 0.00 |
Maximum of Months | 0.118676E+12 | 0.266095E+11 | 0.148768E+12 | 0.858913E+11 | 0.157756E+12 | 0.313114E+11 | 0.00 | 0.370628E+12 | 0.00 | 0.00 | 0.461367E+11 | 0.771796E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.845233E+12 | 0.00 | 0.205221E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.594724E+12 | 0.00 | 0.188047E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.254000E+12 | 0.00 | 0.207218E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.169527E+12 | 0.00 | 0.195660E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.159121E+12 | 0.00 | 0.195372E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.170811E+12 | 0.00 | 0.182084E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.189699E+12 | 0.00 | 0.182467E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.176084E+12 | 0.00 | 0.179954E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.141395E+12 | 0.00 | 0.175329E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.119853E+12 | 0.00 | 0.185844E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.309576E+12 | 0.00 | 0.186114E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.485706E+12 | 0.00 | 0.199906E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.361573E+13 | 0.228322E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.119853E+12 | 0.00 | 0.175329E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.845233E+12 | 0.00 | 0.207218E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 110670.55 | 02-JAN-20:10 | 15665.55 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 63968.34 | 02-JAN-07:19 | 84057.13 | 31-JAN-04:00 | 7398.11 | 07-JAN-09:00 | 0.00 | 01-JAN-00:10 |
February | 110670.55 | 01-FEB-20:10 | 15665.55 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 63968.34 | 01-FEB-07:19 | 85392.81 | 02-FEB-07:10 | 7365.99 | 04-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 110670.55 | 01-MAR-20:10 | 15665.55 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 63968.34 | 01-MAR-07:19 | 64380.70 | 02-MAR-16:10 | 10948.59 | 19-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 110670.55 | 03-APR-19:10 | 15665.55 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 63968.34 | 03-APR-06:19 | 77546.78 | 18-APR-15:30 | 13193.67 | 18-APR-09:00 | 0.00 | 01-APR-00:10 |
May | 110670.55 | 01-MAY-19:10 | 15665.55 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 63968.34 | 01-MAY-06:19 | 73945.79 | 31-MAY-18:30 | 13514.81 | 30-MAY-09:30 | 0.00 | 01-MAY-00:10 |
June | 110670.55 | 01-JUN-19:10 | 15665.55 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 63968.34 | 01-JUN-06:19 | 75657.03 | 18-JUN-20:19 | 13783.25 | 13-JUN-09:09 | 0.00 | 01-JUN-00:10 |
July | 110670.55 | 03-JUL-19:10 | 15665.55 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 63968.34 | 03-JUL-06:19 | 75593.56 | 01-JUL-18:19 | 13828.09 | 20-JUL-08:09 | 0.00 | 01-JUL-00:10 |
August | 110670.55 | 01-AUG-19:10 | 15665.55 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 63968.34 | 01-AUG-06:19 | 75222.24 | 05-AUG-15:30 | 13741.09 | 04-AUG-09:09 | 0.00 | 01-AUG-00:10 |
September | 110670.55 | 01-SEP-19:10 | 15665.55 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 63968.34 | 01-SEP-06:19 | 73864.97 | 17-SEP-16:10 | 13198.29 | 11-SEP-09:20 | 0.00 | 01-SEP-00:10 |
October | 110670.55 | 02-OCT-19:10 | 15665.55 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 63968.34 | 02-OCT-06:19 | 71187.52 | 20-OCT-15:09 | 12824.55 | 20-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 110670.55 | 01-NOV-19:10 | 15665.55 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 63968.34 | 01-NOV-06:19 | 79518.24 | 26-NOV-07:10 | 10539.41 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 110670.55 | 01-DEC-20:10 | 15665.55 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 63968.34 | 01-DEC-07:19 | 75201.02 | 09-DEC-16:10 | 6978.34 | 07-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 110670.55 | 15665.55 | 89674.66 | 63968.34 | 64380.70 | 6978.34 | 0.00 | |||||||
Maximum of Months | 110670.55 | 15665.55 | 89674.66 | 63968.34 | 85392.81 | 13828.09 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7730.42 | 13-JAN-12:39 | 0.00 | 0.00 | 17225.46 | 01-JAN-00:10 | 4753.58 | 30-JAN-07:10 | 0.00 |
February | 19064.72 | 25-FEB-16:10 | 0.00 | 0.00 | 17225.46 | 01-FEB-00:10 | 4757.79 | 02-FEB-07:19 | 0.00 |
March | 92039.29 | 19-MAR-15:09 | 0.00 | 0.00 | 17225.46 | 01-MAR-00:10 | 4738.84 | 27-MAR-06:30 | 0.00 |
April | 203695.73 | 16-APR-15:09 | 0.00 | 0.00 | 17225.46 | 01-APR-00:10 | 4739.06 | 03-APR-06:30 | 0.00 |
May | 197792.21 | 31-MAY-15:09 | 0.00 | 0.00 | 17225.46 | 01-MAY-00:10 | 4738.95 | 24-MAY-06:10 | 0.00 |
June | 295937.32 | 11-JUN-15:09 | 0.00 | 0.00 | 17225.46 | 01-JUN-00:00 | 4739.62 | 29-JUN-06:10 | 0.00 |
July | 291654.85 | 26-JUL-15:09 | 0.00 | 0.00 | 17225.46 | 01-JUL-08:20 | 4739.75 | 13-JUL-06:10 | 0.00 |
August | 322225.98 | 04-AUG-15:00 | 0.00 | 0.00 | 17225.46 | 01-AUG-08:09 | 4739.64 | 10-AUG-06:10 | 0.00 |
September | 229948.75 | 06-SEP-15:09 | 0.00 | 0.00 | 17225.46 | 01-SEP-05:00 | 4739.52 | 20-SEP-06:10 | 0.00 |
October | 134497.41 | 20-OCT-15:09 | 0.00 | 0.00 | 17225.46 | 01-OCT-00:10 | 4738.62 | 30-OCT-06:30 | 0.00 |
November | 70821.32 | 05-NOV-15:09 | 0.00 | 0.00 | 17225.46 | 01-NOV-00:10 | 4739.41 | 21-NOV-07:10 | 0.00 |
December | 22772.71 | 03-DEC-13:39 | 0.00 | 0.00 | 17225.46 | 01-DEC-00:10 | 4739.15 | 11-DEC-07:00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 7730.42 | 0.00 | 0.00 | 17225.46 | 4738.62 | 0.00 | |||
Maximum of Months | 322225.98 | 0.00 | 0.00 | 17225.46 | 4757.79 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 369653.82 | 30-JAN-20:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 75651.15 | 3986.65 | 0.00 | 0.00 | 0.00 |
February | 374872.30 | 02-FEB-20:19 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 80778.15 | 4015.63 | 0.00 | 0.00 | 0.00 |
March | 389374.33 | 19-MAR-19:19 | 104492.97 | 87485.24 | 15665.55 | 51722.33 | 58946.23 | 9070.41 | 0.00 | 56134.24 | 0.00 |
April | 556490.89 | 16-APR-19:10 | 104492.97 | 87485.24 | 15665.55 | 51714.81 | 72972.44 | 12528.89 | 0.00 | 188431.47 | 0.00 |
May | 544405.31 | 31-MAY-19:40 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 69302.47 | 12298.00 | 0.00 | 171877.18 | 0.00 |
June | 587727.93 | 26-JUN-19:00 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 71386.82 | 12515.45 | 0.00 | 212881.88 | 0.00 |
July | 627943.55 | 26-JUL-18:10 | 98435.01 | 79617.06 | 0.00 | 51433.44 | 69481.26 | 13070.54 | 0.00 | 291127.24 | 0.00 |
August | 615205.26 | 03-AUG-19:49 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 70136.71 | 12705.20 | 0.00 | 241145.15 | 0.00 |
September | 542320.60 | 07-SEP-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 67591.31 | 12019.00 | 0.00 | 171740.74 | 0.00 |
October | 404784.21 | 20-OCT-19:30 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 61290.92 | 8897.98 | 0.00 | 61344.05 | 0.00 |
November | 377464.65 | 03-NOV-19:30 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 59067.67 | 7007.45 | 0.00 | 20843.33 | 0.00 |
December | 355611.56 | 04-DEC-20:49 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 55386.00 | 5151.89 | 0.00 | 3958.69 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 355611.56 | 98435.01 | 79617.06 | 0.00 | 51433.44 | 55386.00 | 3986.65 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 627943.55 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 80778.15 | 13070.54 | 0.00 | 291127.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 956913.25 | 31-JAN-03:00 | 0.00 | 182675.82 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 999812.26 | 02-FEB-05:00 | 0.00 | 182781.20 | 03-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 302672.75 | 05-MAR-23:00 | 0.00 | 182736.97 | 01-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 235466.28 | 03-APR-08:09 | 0.00 | 182094.05 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 118506.60 | 30-MAY-09:09 | 0.00 | 181086.29 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 125697.67 | 13-JUN-09:09 | 0.00 | 179832.29 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 125821.41 | 20-JUL-09:09 | 0.00 | 178669.25 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 126177.84 | 31-AUG-08:09 | 0.00 | 178083.93 | 01-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 126177.90 | 18-SEP-08:09 | 0.00 | 178408.16 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 116094.11 | 21-OCT-15:09 | 0.00 | 179411.91 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 924326.22 | 26-NOV-06:00 | 0.00 | 180644.85 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 487212.33 | 09-DEC-09:09 | 0.00 | 181776.45 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 116094.11 | 0.00 | 178083.93 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 999812.26 | 0.00 | 182781.20 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.17 | 16.79 | 184.17 | 16.79 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182.50 | 11.13 | 182.50 | 11.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.00 | 20.41 | 3.00 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54.83 | 20.17 | 54.83 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 104.33 | 20.25 | 104.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 132.50 | 20.31 | 132.50 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33.83 | 20.39 | 33.83 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21.83 | 17.88 | 21.83 | 17.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 717.00 | 16.98 | 717.00 | 16.98 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.17 | 20.41 | 184.17 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.33 | 13.70 | 131.33 | 13.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 122.00 | 9.29 | 122.00 | 9.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23.83 | 15.50 | 23.83 | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28.50 | 20.19 | 28.50 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 305.67 | 12.69 | 305.67 | 12.69 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.33 | 20.19 | 131.33 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.00 | 13.76 | 131.00 | 13.76 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 135.17 | 9.19 | 135.17 | 9.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22.00 | 15.88 | 22.00 | 15.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 288.17 | 11.78 | 288.17 | 11.78 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 135.17 | 15.88 | 135.17 | 15.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.00 | 16.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 162.00 | 10.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35.33 | 17.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 385.33 | 13.67 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.00 | 17.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.33 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 163.17 | 10.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50.83 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.33 | 14.13 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 191.33 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.83 | 2.94 | 82.83 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84.67 | -1.5 | 84.67 | -1.5 | 0.67 | 24.57 | 0.67 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.60 | 2.67 | 24.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.62 | 4.67 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.62 | 1.67 | 24.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.61 | 3.33 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.61 | 6.33 | 24.61 |
November | 11.33 | 4.34 | 11.33 | 4.34 | 1.67 | 24.61 | 1.67 | 24.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 178.83 | 0.93 | 178.83 | 0.93 | 21.33 | 24.61 | 21.33 | 24.61 |
Minimum of Months | 0.00 | -1.5 | 0.00 | -1.5 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.67 | 4.34 | 84.67 | 4.34 | 6.33 | 24.62 | 6.33 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.67 | 11.16 | 96.67 | 11.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94.33 | 6.37 | 94.33 | 6.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17.33 | 13.81 | 17.33 | 13.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.33 | 9.21 | 208.33 | 9.21 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.67 | 13.81 | 96.67 | 13.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 126.83 | 13.82 | 126.83 | 13.82 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 117.17 | 8.13 | 117.17 | 8.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21.17 | 15.83 | 21.17 | 15.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.17 | 11.47 | 265.17 | 11.47 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.83 | 15.83 | 126.83 | 15.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.34 | 0.83 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27.17 | 19.90 | 27.17 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.00 | 19.91 | 28.00 | 19.91 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.17 | 20.34 | 27.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.20 | 1.67 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42.50 | 19.63 | 42.50 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.33 | 19.66 | 44.33 | 19.66 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.50 | 20.55 | 42.50 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 20.30 | 8.83 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42.00 | 19.98 | 42.00 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.40 | 0.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.36 | 0.83 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.00 | 20.04 | 52.00 | 20.04 | 2.00 | 21.72 | 2.00 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.00 | 20.40 | 42.00 | 20.40 | 0.83 | 21.77 | 0.83 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.49 | 2.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38.83 | 19.61 | 38.83 | 19.61 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.50 | 19.67 | 41.50 | 19.67 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.83 | 20.52 | 38.83 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 20.29 | 7.67 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51.00 | 19.30 | 51.00 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.51 | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.17 | 19.43 | 59.17 | 19.43 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 20.51 | 51.00 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 296.33 | 18.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184.00 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61.00 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54.00 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 595.33 | 17.58 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.37 | 0.67 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.50 | 20.40 | 3.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.33 | 20.40 | 4.33 | 20.40 | 1.17 | 21.72 | 1.17 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.55 | 3.50 | 20.55 | 0.50 | 21.77 | 0.50 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.28 | 1.50 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14.83 | 20.24 | 14.83 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.83 | 20.25 | 16.83 | 20.25 | 0.50 | 21.70 | 0.50 | 21.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.83 | 20.52 | 14.83 | 20.52 | 0.33 | 21.74 | 0.33 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.38 | 0.67 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.00 | 20.43 | 4.00 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.03 | 1.17 | 22.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.95 | 0.83 | 21.95 |
December | 0.50 | 20.49 | 0.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.17 | 20.43 | 5.17 | 20.43 | 5.67 | 21.85 | 5.67 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.49 | 4.00 | 20.49 | 2.33 | 22.03 | 2.33 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.67 | 11.56 | 101.67 | 11.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93.17 | 5.24 | 93.17 | 5.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.67 | 12.01 | 12.67 | 12.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 207.50 | 8.75 | 207.50 | 8.75 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.67 | 12.01 | 101.67 | 12.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.17 | 11.05 | 99.17 | 11.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92.17 | 4.81 | 92.17 | 4.81 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.67 | 11.70 | 12.67 | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.00 | 8.27 | 204.00 | 8.27 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.17 | 11.70 | 99.17 | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.17 | 5.36 | 82.17 | 5.36 | 0.33 | 24.64 | 0.33 | 24.64 |
February | 83.50 | 0.82 | 83.50 | 0.82 | 3.17 | 24.65 | 3.17 | 24.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.69 | 17.33 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 24.73 | 28.00 | 24.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.74 | 6.00 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.67 | 2.50 | 24.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.69 | 12.00 | 24.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 24.67 | 29.67 | 24.67 |
November | 11.83 | 6.15 | 11.83 | 6.15 | 6.67 | 24.68 | 6.67 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
Annual Sum or Average | 177.50 | 3.28 | 177.50 | 3.28 | 106.33 | 24.69 | 106.33 | 24.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.50 | 6.15 | 83.50 | 6.15 | 29.67 | 24.74 | 29.67 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.83 | 16.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 153.17 | 10.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45.17 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.17 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.33 | 14.33 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.83 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.00 | 402.83 | 19.07 | 402.83 | 19.07 |
February | 672.00 | 18.34 | 280.00 | 14.56 | 280.00 | 14.56 |
March | 744.00 | 21.01 | 135.33 | 21.00 | 135.33 | 21.00 |
April | 720.00 | 20.90 | 76.17 | 20.83 | 76.17 | 20.83 |
May | 744.00 | 20.82 | 11.83 | 20.35 | 11.83 | 20.35 |
June | 720.00 | 20.77 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 20.82 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.10 | 65.67 | 19.95 | 65.67 | 19.95 |
December | 744.00 | 21.15 | 73.17 | 21.00 | 73.17 | 21.00 |
Annual Sum or Average | 8760.00 | 20.69 | 1045.00 | 18.44 | 1045.00 | 18.44 |
Minimum of Months | 672.00 | 18.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.23 | 402.83 | 21.00 | 402.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.70 | 650.00 | 19.49 | 650.00 | 19.49 |
February | 667.67 | 18.88 | 488.50 | 18.07 | 488.50 | 18.07 |
March | 744.00 | 21.03 | 347.17 | 21.00 | 347.17 | 21.00 |
April | 718.67 | 21.02 | 177.33 | 21.00 | 177.33 | 21.00 |
May | 744.00 | 21.00 | 8.50 | 21.00 | 8.50 | 21.00 |
June | 720.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 21.04 | 19.33 | 21.28 | 16.00 | 21.00 |
October | 728.83 | 21.09 | 81.67 | 21.05 | 79.83 | 21.00 |
November | 712.83 | 20.84 | 375.67 | 20.65 | 374.00 | 20.64 |
December | 741.83 | 20.98 | 614.67 | 20.94 | 614.67 | 20.94 |
Annual Sum or Average | 8711.33 | 20.73 | 2762.83 | 20.07 | 2756.00 | 20.06 |
Minimum of Months | 667.67 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.09 | 650.00 | 21.28 | 650.00 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.73 | 441.50 | 18.84 | 441.50 | 18.84 |
February | 672.00 | 18.64 | 227.00 | 13.97 | 227.00 | 13.97 |
March | 744.00 | 21.04 | 37.33 | 21.00 | 37.33 | 21.00 |
April | 720.00 | 21.06 | 3.67 | 21.00 | 3.67 | 21.00 |
May | 744.00 | 21.05 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.03 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.05 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 20.88 | 114.00 | 20.01 | 114.00 | 20.01 |
December | 744.00 | 21.01 | 218.50 | 21.00 | 218.50 | 21.00 |
Annual Sum or Average | 8760.00 | 20.73 | 1042.00 | 18.45 | 1042.00 | 18.45 |
Minimum of Months | 672.00 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.07 | 441.50 | 21.00 | 441.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 620.33 | 18.81 | 216.17 | 15.29 | 148.83 | 11.93 |
February | 549.00 | 17.87 | 205.50 | 13.00 | 154.17 | 9.84 |
March | 555.33 | 21.50 | 168.83 | 23.13 | 96.33 | 23.90 |
April | 480.50 | 21.45 | 192.67 | 22.60 | 91.00 | 23.69 |
May | 365.67 | 21.38 | 277.67 | 21.90 | 91.00 | 23.26 |
June | 352.00 | 20.89 | 294.83 | 21.50 | 72.33 | 22.71 |
July | 371.17 | 20.58 | 320.33 | 21.30 | 57.17 | 22.32 |
August | 390.50 | 20.74 | 320.83 | 21.41 | 68.67 | 22.51 |
September | 393.33 | 21.19 | 254.50 | 21.90 | 77.00 | 23.36 |
October | 493.17 | 21.55 | 191.00 | 22.86 | 100.50 | 23.80 |
November | 519.00 | 21.09 | 184.17 | 21.73 | 98.33 | 21.51 |
December | 600.67 | 21.36 | 141.17 | 23.33 | 73.00 | 23.96 |
Annual Sum or Average | 5690.67 | 20.62 | 2767.67 | 20.80 | 1128.33 | 19.84 |
Minimum of Months | 352.00 | 17.87 | 141.17 | 13.00 | 57.17 | 9.84 |
Maximum of Months | 620.33 | 21.55 | 320.83 | 23.33 | 154.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.73 | 520.33 | 19.17 | 520.33 | 19.17 |
February | 666.83 | 18.95 | 281.67 | 16.09 | 281.67 | 16.09 |
March | 744.00 | 21.02 | 145.17 | 21.00 | 145.17 | 21.00 |
April | 720.00 | 21.02 | 25.33 | 21.00 | 25.33 | 21.00 |
May | 744.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 712.67 | 21.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 731.17 | 21.09 | 0.17 | 21.01 | 0.17 | 21.01 |
November | 712.17 | 20.85 | 169.00 | 20.28 | 167.33 | 20.25 |
December | 740.83 | 21.03 | 384.83 | 21.00 | 384.83 | 21.00 |
Annual Sum or Average | 8723.67 | 20.74 | 1526.50 | 19.39 | 1524.83 | 19.39 |
Minimum of Months | 666.83 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.09 | 520.33 | 21.01 | 520.33 | 21.01 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.79 | 335.83 | 18.29 | 335.83 | 18.29 |
February | 672.00 | 18.78 | 169.17 | 12.07 | 169.17 | 12.07 |
March | 744.00 | 21.08 | 2.83 | 21.00 | 2.83 | 21.00 |
April | 720.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.06 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.05 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.14 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 20.92 | 77.33 | 19.58 | 77.33 | 19.58 |
December | 744.00 | 21.02 | 133.83 | 21.00 | 133.83 | 21.00 |
Annual Sum or Average | 8760.00 | 20.78 | 719.00 | 17.48 | 719.00 | 17.48 |
Minimum of Months | 672.00 | 18.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.14 | 335.83 | 21.00 | 335.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.58 | 712.00 | 20.55 | 712.00 | 20.55 |
February | 672.00 | 20.69 | 531.33 | 20.53 | 531.33 | 20.53 |
March | 743.17 | 21.02 | 381.17 | 20.73 | 381.17 | 20.73 |
April | 700.50 | 21.20 | 146.17 | 20.73 | 139.17 | 20.62 |
May | 716.00 | 21.49 | 4.67 | 22.92 | 0.00 | 0.00 |
June | 642.50 | 21.43 | 24.50 | 22.81 | 3.50 | 22.04 |
July | 639.17 | 21.43 | 35.17 | 22.91 | 2.67 | 22.10 |
August | 640.33 | 21.43 | 27.33 | 22.63 | 8.33 | 21.95 |
September | 660.67 | 21.40 | 20.17 | 21.91 | 11.00 | 20.95 |
October | 739.67 | 21.33 | 56.33 | 20.85 | 56.33 | 20.85 |
November | 718.83 | 20.91 | 417.50 | 20.66 | 417.50 | 20.66 |
December | 744.00 | 20.69 | 685.00 | 20.63 | 685.00 | 20.63 |
Annual Sum or Average | 8360.83 | 21.12 | 3041.33 | 20.69 | 2948.00 | 20.62 |
Minimum of Months | 639.17 | 20.58 | 4.67 | 20.53 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.49 | 712.00 | 22.92 | 712.00 | 22.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 742.00 | 20.49 | 742.00 | 20.49 |
February | 672.00 | 20.49 | 621.00 | 20.43 | 621.00 | 20.43 |
March | 744.00 | 20.83 | 459.83 | 20.60 | 459.83 | 20.60 |
April | 707.67 | 21.11 | 175.00 | 20.65 | 170.83 | 20.60 |
May | 723.17 | 21.46 | 4.17 | 22.55 | 0.50 | 20.66 |
June | 651.00 | 21.45 | 20.83 | 22.80 | 2.50 | 21.94 |
July | 653.67 | 21.46 | 30.50 | 22.88 | 2.33 | 21.92 |
August | 669.67 | 21.49 | 20.50 | 22.60 | 6.67 | 21.98 |
September | 687.83 | 21.39 | 17.00 | 21.15 | 14.67 | 20.92 |
October | 743.67 | 21.10 | 133.33 | 20.75 | 133.33 | 20.75 |
November | 720.00 | 20.75 | 475.83 | 20.57 | 475.83 | 20.57 |
December | 744.00 | 20.52 | 739.00 | 20.52 | 739.00 | 20.52 |
Annual Sum or Average | 8460.67 | 21.03 | 3439.00 | 20.58 | 3368.50 | 20.53 |
Minimum of Months | 651.00 | 20.49 | 4.17 | 20.43 | 0.50 | 20.43 |
Maximum of Months | 744.00 | 21.49 | 742.00 | 22.88 | 742.00 | 21.98 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.72 | 605.67 | 20.63 | 605.67 | 20.63 |
February | 672.00 | 20.80 | 372.50 | 20.56 | 372.50 | 20.56 |
March | 744.00 | 21.11 | 205.33 | 20.87 | 205.33 | 20.87 |
April | 720.00 | 21.29 | 14.83 | 20.82 | 14.83 | 20.82 |
May | 744.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.57 | 3.17 | 22.12 | 3.17 | 22.12 |
July | 744.00 | 21.59 | 4.83 | 22.21 | 4.83 | 22.21 |
August | 744.00 | 21.56 | 11.33 | 22.01 | 11.33 | 22.01 |
September | 720.00 | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.28 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.05 | 228.33 | 20.75 | 228.33 | 20.75 |
December | 744.00 | 20.82 | 558.67 | 20.72 | 558.67 | 20.72 |
Annual Sum or Average | 8760.00 | 21.23 | 2004.67 | 20.70 | 2004.67 | 20.70 |
Minimum of Months | 672.00 | 20.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.59 | 605.67 | 22.21 | 605.67 | 22.21 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 710.00 | 20.54 | 710.00 | 20.54 |
February | 672.00 | 20.66 | 536.83 | 20.51 | 536.83 | 20.51 |
March | 744.00 | 21.09 | 351.83 | 20.78 | 351.83 | 20.78 |
April | 702.50 | 21.25 | 159.50 | 20.70 | 158.83 | 20.69 |
May | 711.50 | 21.57 | 1.00 | 22.71 | 0.00 | 0.00 |
June | 626.00 | 21.44 | 8.50 | 22.60 | 2.00 | 21.89 |
July | 609.83 | 21.39 | 11.83 | 22.65 | 2.00 | 21.93 |
August | 628.50 | 21.44 | 10.67 | 22.31 | 6.50 | 22.03 |
September | 656.33 | 21.45 | 6.67 | 21.54 | 4.67 | 21.11 |
October | 744.00 | 21.38 | 49.67 | 20.99 | 49.67 | 20.99 |
November | 720.00 | 20.90 | 425.17 | 20.66 | 425.17 | 20.66 |
December | 744.00 | 20.67 | 680.17 | 20.62 | 680.17 | 20.62 |
Annual Sum or Average | 8302.67 | 21.14 | 2951.83 | 20.64 | 2927.67 | 20.62 |
Minimum of Months | 609.83 | 20.57 | 1.00 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.57 | 710.00 | 22.71 | 710.00 | 22.03 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 739.83 | 20.48 | 739.83 | 20.48 |
February | 672.00 | 20.44 | 621.67 | 20.39 | 621.67 | 20.39 |
March | 744.00 | 20.89 | 437.17 | 20.67 | 437.17 | 20.67 |
April | 706.33 | 21.16 | 174.83 | 20.66 | 174.33 | 20.66 |
May | 722.50 | 21.56 | 1.00 | 22.71 | 0.00 | 0.00 |
June | 635.00 | 21.46 | 7.50 | 22.70 | 1.17 | 21.89 |
July | 630.83 | 21.45 | 12.00 | 22.66 | 2.00 | 22.08 |
August | 666.00 | 21.53 | 10.33 | 22.26 | 6.50 | 21.96 |
September | 688.17 | 21.47 | 8.83 | 21.39 | 7.00 | 21.11 |
October | 744.00 | 21.15 | 96.33 | 20.93 | 96.33 | 20.93 |
November | 720.00 | 20.74 | 473.83 | 20.55 | 473.83 | 20.55 |
December | 744.00 | 20.51 | 737.00 | 20.51 | 737.00 | 20.51 |
Annual Sum or Average | 8416.83 | 21.06 | 3320.33 | 20.55 | 3296.83 | 20.53 |
Minimum of Months | 630.83 | 20.44 | 1.00 | 20.39 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.56 | 739.83 | 22.71 | 739.83 | 22.08 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 727.67 | 20.52 | 727.67 | 20.52 |
February | 672.00 | 20.68 | 577.33 | 20.57 | 577.33 | 20.57 |
March | 743.00 | 20.94 | 459.50 | 20.68 | 459.50 | 20.68 |
April | 693.83 | 21.15 | 219.17 | 20.78 | 207.67 | 20.65 |
May | 690.00 | 21.46 | 17.00 | 22.26 | 6.17 | 21.00 |
June | 611.33 | 21.36 | 51.17 | 22.93 | 6.83 | 21.90 |
July | 603.17 | 21.34 | 72.67 | 23.01 | 6.00 | 22.06 |
August | 607.83 | 21.34 | 68.83 | 22.76 | 16.33 | 21.79 |
September | 645.33 | 21.35 | 51.67 | 22.24 | 21.17 | 20.91 |
October | 737.50 | 21.28 | 142.50 | 20.88 | 142.17 | 20.88 |
November | 717.67 | 20.82 | 465.00 | 20.61 | 465.00 | 20.61 |
December | 744.00 | 20.62 | 711.17 | 20.58 | 711.17 | 20.58 |
Annual Sum or Average | 8209.67 | 21.06 | 3563.67 | 20.77 | 3347.00 | 20.62 |
Minimum of Months | 603.17 | 20.53 | 17.00 | 20.52 | 6.00 | 20.52 |
Maximum of Months | 744.00 | 21.46 | 727.67 | 23.01 | 727.67 | 22.06 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 743.83 | 20.47 | 743.83 | 20.47 |
February | 672.00 | 20.52 | 644.33 | 20.49 | 644.33 | 20.49 |
March | 744.00 | 20.75 | 519.83 | 20.57 | 519.83 | 20.57 |
April | 701.50 | 21.07 | 250.83 | 20.69 | 243.33 | 20.61 |
May | 702.67 | 21.46 | 17.67 | 21.94 | 9.33 | 21.03 |
June | 617.50 | 21.38 | 44.83 | 22.89 | 6.17 | 21.81 |
July | 612.67 | 21.37 | 61.67 | 22.96 | 5.83 | 22.00 |
August | 625.83 | 21.39 | 55.67 | 22.68 | 15.33 | 21.80 |
September | 669.50 | 21.34 | 45.83 | 21.36 | 34.00 | 20.78 |
October | 743.50 | 21.04 | 264.33 | 20.75 | 264.33 | 20.75 |
November | 720.00 | 20.68 | 524.83 | 20.53 | 524.83 | 20.53 |
December | 744.00 | 20.49 | 743.83 | 20.49 | 743.83 | 20.49 |
Annual Sum or Average | 8297.17 | 20.98 | 3917.50 | 20.65 | 3755.00 | 20.54 |
Minimum of Months | 612.67 | 20.47 | 17.67 | 20.47 | 5.83 | 20.47 |
Maximum of Months | 744.00 | 21.46 | 743.83 | 22.96 | 743.83 | 22.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.00 | 20.97 | 602.67 | 20.74 | 602.67 | 20.74 |
February | 662.17 | 21.06 | 401.17 | 20.76 | 401.17 | 20.76 |
March | 735.00 | 21.24 | 262.50 | 20.81 | 262.50 | 20.81 |
April | 691.67 | 21.27 | 142.33 | 20.84 | 136.17 | 20.73 |
May | 709.50 | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 639.33 | 21.45 | 6.67 | 22.09 | 6.67 | 22.09 |
July | 632.33 | 21.41 | 6.67 | 22.33 | 6.67 | 22.33 |
August | 630.67 | 21.40 | 24.00 | 22.26 | 17.00 | 21.82 |
September | 638.67 | 21.40 | 36.00 | 22.97 | 5.00 | 20.99 |
October | 691.00 | 21.38 | 23.17 | 21.50 | 18.00 | 20.97 |
November | 705.33 | 21.14 | 317.00 | 20.78 | 314.83 | 20.76 |
December | 737.33 | 20.98 | 562.50 | 20.71 | 562.50 | 20.71 |
Annual Sum or Average | 8216.00 | 21.26 | 2384.67 | 20.82 | 2333.17 | 20.77 |
Minimum of Months | 630.67 | 20.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 743.00 | 21.52 | 602.67 | 22.97 | 602.67 | 22.33 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.90 | 265.50 | 17.38 | 265.50 | 17.38 |
February | 672.00 | 19.11 | 139.17 | 10.43 | 139.17 | 10.43 |
March | 744.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 743.33 | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.35 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.44 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.58 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.26 | 54.67 | 18.92 | 54.67 | 18.92 |
December | 744.00 | 21.29 | 61.67 | 21.00 | 61.67 | 21.00 |
Annual Sum or Average | 8759.33 | 21.09 | 521.00 | 16.11 | 521.00 | 16.11 |
Minimum of Months | 672.00 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.58 | 265.50 | 21.00 | 265.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.89 | 175.67 | 15.37 | 175.67 | 15.37 |
February | 672.00 | 19.13 | 135.33 | 9.97 | 135.33 | 9.97 |
March | 743.83 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 719.83 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 727.83 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 710.50 | 21.35 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 740.83 | 21.30 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 717.17 | 21.47 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 742.33 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 717.50 | 21.31 | 26.00 | 16.48 | 26.00 | 16.48 |
December | 744.00 | 21.34 | 33.17 | 21.00 | 33.17 | 21.00 |
Annual Sum or Average | 8723.83 | 21.12 | 370.17 | 13.98 | 370.17 | 13.98 |
Minimum of Months | 672.00 | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.64 | 175.67 | 21.00 | 175.67 | 21.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.17 | 19.29 | 489.67 | 20.24 | 259.00 | 17.92 |
February | 490.33 | 18.97 | 485.50 | 19.54 | 326.67 | 17.92 |
March | 566.83 | 22.93 | 531.83 | 23.56 | 380.17 | 23.85 |
April | 574.67 | 22.92 | 529.00 | 23.44 | 410.50 | 23.68 |
May | 605.67 | 22.70 | 567.17 | 23.01 | 464.67 | 23.20 |
June | 542.50 | 22.46 | 556.33 | 22.58 | 431.50 | 22.83 |
July | 536.33 | 22.24 | 574.83 | 22.30 | 425.67 | 22.56 |
August | 538.33 | 22.25 | 573.00 | 22.34 | 422.83 | 22.59 |
September | 558.67 | 22.60 | 544.50 | 22.88 | 420.50 | 23.12 |
October | 599.17 | 22.99 | 546.50 | 23.54 | 427.17 | 23.77 |
November | 512.50 | 22.41 | 512.33 | 23.01 | 334.83 | 23.13 |
December | 452.83 | 22.54 | 502.17 | 23.31 | 245.83 | 23.78 |
Annual Sum or Average | 6439.00 | 22.10 | 6412.83 | 22.51 | 4549.33 | 22.54 |
Minimum of Months | 452.83 | 18.97 | 485.50 | 19.54 | 245.83 | 17.92 |
Maximum of Months | 605.67 | 22.99 | 574.83 | 23.56 | 464.67 | 23.85 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.99932 | 13.94944 | -0.7654 | 20.39527 |
February | 672.00000 | 18.33927 | 18.48369 | -1.1329 | 28.32040 |
March | 744.00000 | 21.01164 | 24.74663 | -0.4945 | 10.17800 |
April | 720.00000 | 20.90314 | 33.17584 | -0.4791 | 9.86631 |
May | 744.00000 | 20.82216 | 47.73608 | -1.6272 | 57.79274 |
June | 720.00000 | 20.77020 | 54.07072 | -1.5909 | 55.83713 |
July | 744.00000 | 20.82289 | 55.82419 | -1.5481 | 53.51619 |
August | 744.00000 | 20.91590 | 55.10965 | -1.5033 | 51.08696 |
September | 720.00000 | 21.06872 | 45.27024 | -1.4998 | 50.90130 |
October | 744.00000 | 21.23205 | 32.21248 | -0.3546 | 7.71231 |
November | 720.00000 | 21.10443 | 26.29416 | -0.4224 | 9.38254 |
December | 744.00000 | 21.14978 | 16.95616 | -0.4720 | 9.73455 |
Annual Sum or Average | 8760.00000 | 20.69441 | 35.40944 | -0.9896 | 30.39859 |
Minimum of Months | 672.00000 | 18.33927 | 13.94944 | -1.6272 | 7.71231 |
Maximum of Months | 744.00000 | 21.23205 | 55.82419 | -0.3546 | 57.79274 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.70190 | 13.34896 | -0.9513 | 25.04888 |
February | 672.00000 | 18.90888 | 17.54224 | -1.0571 | 25.08887 |
March | 744.00000 | 21.02772 | 24.12419 | -0.5090 | 10.94599 |
April | 720.00000 | 21.01967 | 32.39273 | -0.4181 | 9.23245 |
May | 744.00000 | 21.00083 | 46.97118 | -1.4547 | 48.51879 |
June | 720.00000 | 21.00091 | 53.68798 | -1.3661 | 43.81914 |
July | 744.00000 | 21.00105 | 56.07135 | -1.3266 | 41.71932 |
August | 744.00000 | 21.00516 | 55.45393 | -1.3262 | 41.74775 |
September | 720.00000 | 21.07749 | 44.88096 | -1.4018 | 46.15990 |
October | 744.00000 | 21.12776 | 31.86814 | -0.3675 | 8.59108 |
November | 720.00000 | 20.86015 | 25.95630 | -0.5529 | 12.92293 |
December | 744.00000 | 20.99097 | 16.41897 | -0.6413 | 14.38138 |
Annual Sum or Average | 8760.00000 | 20.73894 | 34.98817 | -0.9470 | 27.35910 |
Minimum of Months | 672.00000 | 18.90888 | 13.34896 | -1.4547 | 8.59108 |
Maximum of Months | 744.00000 | 21.12776 | 56.07135 | -0.3675 | 48.51879 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.72710 | 14.33144 | -0.8348 | 22.11264 |
February | 672.00000 | 18.63721 | 18.54193 | -1.0422 | 24.23126 |
March | 744.00000 | 21.04030 | 25.11907 | -0.4451 | 9.27326 |
April | 720.00000 | 21.05631 | 33.26265 | -0.3770 | 8.14627 |
May | 744.00000 | 21.05322 | 47.59769 | -1.4467 | 48.05572 |
June | 720.00000 | 21.02545 | 53.96089 | -1.4039 | 45.74187 |
July | 744.00000 | 21.01013 | 56.05519 | -1.3892 | 44.95035 |
August | 744.00000 | 21.02369 | 55.54761 | -1.3891 | 44.95398 |
September | 720.00000 | 21.05295 | 45.77299 | -1.4502 | 48.24328 |
October | 744.00000 | 21.07291 | 32.92069 | -0.3707 | 7.97117 |
November | 720.00000 | 20.87589 | 26.95096 | -0.4777 | 10.78879 |
December | 744.00000 | 21.00847 | 17.48631 | -0.5216 | 10.75209 |
Annual Sum or Average | 8760.00000 | 20.72923 | 35.72164 | -0.9281 | 27.11295 |
Minimum of Months | 672.00000 | 18.63721 | 14.33144 | -1.4502 | 7.97117 |
Maximum of Months | 744.00000 | 21.07291 | 56.05519 | -0.3707 | 48.24328 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.36019 | 12.25725 | -0.3209 | 18.35330 |
February | 672.00000 | 18.57400 | 16.36808 | -0.4631 | 20.49288 |
March | 744.00000 | 21.49765 | 22.41514 | 0.25537 | 9.53732 |
April | 720.00000 | 21.39983 | 30.62213 | 0.29868 | 9.69354 |
May | 744.00000 | 21.23694 | 45.01597 | -0.5185 | 15.65594 |
June | 720.00000 | 20.95320 | 51.95825 | -0.5520 | 15.69960 |
July | 744.00000 | 20.78806 | 54.41251 | -0.5873 | 15.99714 |
August | 744.00000 | 20.87387 | 53.70121 | -0.5644 | 15.81498 |
September | 720.00000 | 21.15364 | 43.51417 | -0.5551 | 16.45477 |
October | 744.00000 | 21.47348 | 30.12420 | 0.31433 | 10.03429 |
November | 720.00000 | 21.19900 | 24.26695 | 0.19259 | 10.97384 |
December | 744.00000 | 21.47142 | 14.94397 | 0.17504 | 8.54706 |
Annual Sum or Average | 8760.00000 | 20.84655 | 33.39213 | -0.1920 | 13.89204 |
Minimum of Months | 672.00000 | 18.57400 | 12.25725 | -0.5873 | 8.54706 |
Maximum of Months | 744.00000 | 21.49765 | 54.41251 | 0.31433 | 20.49288 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.73377 | 16.12094 | -0.8519 | 22.07813 |
February | 672.00000 | 18.97188 | 20.17443 | -0.9477 | 22.10211 |
March | 744.00000 | 21.02477 | 27.15485 | -0.4134 | 9.00145 |
April | 720.00000 | 21.02320 | 35.36431 | -0.3272 | 7.71528 |
May | 744.00000 | 21.01933 | 49.78461 | -1.3373 | 42.32122 |
June | 720.00000 | 21.00763 | 56.29047 | -1.2577 | 38.22291 |
July | 744.00000 | 21.00267 | 58.48228 | -1.2243 | 36.51337 |
August | 744.00000 | 21.00914 | 57.94841 | -1.2205 | 36.36182 |
September | 720.00000 | 21.03750 | 47.88150 | -1.3006 | 40.71085 |
October | 744.00000 | 21.11102 | 34.89794 | -0.2796 | 7.16581 |
November | 720.00000 | 20.87152 | 28.92989 | -0.4562 | 10.84649 |
December | 744.00000 | 21.03355 | 19.46800 | -0.5365 | 11.60841 |
Annual Sum or Average | 8760.00000 | 20.74896 | 37.80393 | -0.8454 | 23.72680 |
Minimum of Months | 672.00000 | 18.97188 | 16.12094 | -1.3373 | 7.16581 |
Maximum of Months | 744.00000 | 21.11102 | 58.48228 | -0.2796 | 42.32122 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.78817 | 15.80706 | -0.7938 | 20.98208 |
February | 672.00000 | 18.78247 | 19.88591 | -0.9833 | 23.02120 |
March | 744.00000 | 21.07764 | 26.68535 | -0.4021 | 8.54835 |
April | 720.00000 | 21.10648 | 34.80852 | -0.3314 | 7.50960 |
May | 744.00000 | 21.11137 | 49.09657 | -1.3798 | 44.50518 |
June | 720.00000 | 21.05604 | 55.54131 | -1.3413 | 42.44310 |
July | 744.00000 | 21.01755 | 57.71591 | -1.3325 | 41.96747 |
August | 744.00000 | 21.04963 | 57.15098 | -1.3246 | 41.57089 |
September | 720.00000 | 21.10595 | 47.29054 | -1.3783 | 44.43021 |
October | 744.00000 | 21.14414 | 34.42869 | -0.3149 | 7.19895 |
November | 720.00000 | 20.91918 | 28.48162 | -0.4349 | 10.05673 |
December | 744.00000 | 21.02138 | 19.09919 | -0.4887 | 10.08029 |
Annual Sum or Average | 8760.00000 | 20.77820 | 37.26017 | -0.8746 | 25.20064 |
Minimum of Months | 672.00000 | 18.78247 | 15.80706 | -1.3798 | 7.19895 |
Maximum of Months | 744.00000 | 21.14414 | 57.71591 | -0.3149 | 44.50518 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57891 | 21.05193 | -0.7871 | 18.70668 |
February | 672.00000 | 20.69497 | 25.01700 | -0.7003 | 16.55958 |
March | 744.00000 | 21.02530 | 31.20583 | -0.5173 | 11.51293 |
April | 720.00000 | 21.25664 | 38.37130 | -0.3532 | 8.92972 |
May | 744.00000 | 21.54707 | 50.70422 | -1.2919 | 40.85405 |
June | 720.00000 | 21.61728 | 55.58262 | -1.1791 | 35.66207 |
July | 744.00000 | 21.67551 | 57.67263 | -1.1174 | 32.83006 |
August | 744.00000 | 21.66980 | 57.63578 | -1.1369 | 33.73799 |
September | 720.00000 | 21.54549 | 48.22329 | -1.2949 | 41.41567 |
October | 744.00000 | 21.33875 | 38.28087 | -0.3475 | 8.25128 |
November | 720.00000 | 20.90885 | 33.18122 | -0.5598 | 12.67816 |
December | 744.00000 | 20.68867 | 24.16373 | -0.7224 | 16.68345 |
Annual Sum or Average | 8760.00000 | 21.21521 | 40.17368 | -0.8350 | 23.18933 |
Minimum of Months | 672.00000 | 20.57891 | 21.05193 | -1.2949 | 8.25128 |
Maximum of Months | 744.00000 | 21.67551 | 57.67263 | -0.3475 | 41.41567 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48734 | 21.20026 | -0.8388 | 20.51682 |
February | 672.00000 | 20.48738 | 25.30070 | -0.7782 | 18.96965 |
March | 744.00000 | 20.82534 | 31.53225 | -0.5832 | 12.91690 |
April | 720.00000 | 21.14913 | 38.68795 | -0.3913 | 9.37286 |
May | 744.00000 | 21.50539 | 50.90934 | -1.3142 | 41.86145 |
June | 720.00000 | 21.60749 | 55.64594 | -1.1871 | 35.97558 |
July | 744.00000 | 21.66690 | 57.89176 | -1.1270 | 33.18915 |
August | 744.00000 | 21.64863 | 58.14211 | -1.1570 | 34.50793 |
September | 720.00000 | 21.46110 | 48.89215 | -1.3484 | 43.79851 |
October | 744.00000 | 21.10396 | 38.76205 | -0.4280 | 9.23918 |
November | 720.00000 | 20.74799 | 33.46555 | -0.6190 | 14.03508 |
December | 744.00000 | 20.51947 | 24.39910 | -0.7863 | 18.62454 |
Annual Sum or Average | 8760.00000 | 21.10434 | 40.48523 | -0.8806 | 24.44698 |
Minimum of Months | 672.00000 | 20.48734 | 21.20026 | -1.3484 | 9.23918 |
Maximum of Months | 744.00000 | 21.66690 | 58.14211 | -0.3913 | 43.79851 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.71826 | 19.75085 | -0.6792 | 15.24636 |
February | 672.00000 | 20.80193 | 23.65984 | -0.6168 | 13.72824 |
March | 744.00000 | 21.11471 | 29.85234 | -0.4704 | 9.91833 |
April | 720.00000 | 21.28849 | 37.03492 | -0.3558 | 8.03646 |
May | 744.00000 | 21.48047 | 48.38642 | -1.3558 | 43.53998 |
June | 720.00000 | 21.56674 | 53.93103 | -1.2655 | 39.12771 |
July | 744.00000 | 21.58594 | 56.84212 | -1.2346 | 37.61898 |
August | 744.00000 | 21.56038 | 56.39322 | -1.2555 | 38.59776 |
September | 720.00000 | 21.46278 | 46.87386 | -1.3770 | 44.66824 |
October | 744.00000 | 21.28335 | 36.80654 | -0.3639 | 7.91483 |
November | 720.00000 | 21.05318 | 31.37380 | -0.4847 | 10.45149 |
December | 744.00000 | 20.81619 | 22.91772 | -0.6276 | 13.61248 |
Annual Sum or Average | 8760.00000 | 21.22994 | 38.73509 | -0.8421 | 23.59676 |
Minimum of Months | 672.00000 | 20.71826 | 19.75085 | -1.3770 | 7.91483 |
Maximum of Months | 744.00000 | 21.58594 | 56.84212 | -0.3558 | 44.66824 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57034 | 21.04197 | -0.7872 | 18.71809 |
February | 672.00000 | 20.66476 | 24.99238 | -0.7089 | 16.90324 |
March | 744.00000 | 21.08606 | 31.10814 | -0.5015 | 11.18115 |
April | 720.00000 | 21.29914 | 38.22332 | -0.3530 | 8.96773 |
May | 744.00000 | 21.63526 | 49.99383 | -1.2566 | 39.20340 |
June | 720.00000 | 21.66834 | 54.86164 | -1.1617 | 34.92101 |
July | 744.00000 | 21.71584 | 57.21002 | -1.1097 | 32.55131 |
August | 744.00000 | 21.70965 | 57.01524 | -1.1322 | 33.55227 |
September | 720.00000 | 21.60250 | 47.85469 | -1.2747 | 40.45591 |
October | 744.00000 | 21.38116 | 38.22978 | -0.3402 | 8.12676 |
November | 720.00000 | 20.90142 | 33.18464 | -0.5625 | 12.72756 |
December | 744.00000 | 20.67250 | 24.16666 | -0.7260 | 16.76226 |
Annual Sum or Average | 8760.00000 | 21.24562 | 39.90480 | -0.8270 | 22.87235 |
Minimum of Months | 672.00000 | 20.57034 | 21.04197 | -1.2747 | 8.12676 |
Maximum of Months | 744.00000 | 21.71584 | 57.21002 | -0.3402 | 40.45591 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48300 | 21.17767 | -0.8389 | 20.55280 |
February | 672.00000 | 20.44155 | 25.27966 | -0.7908 | 19.51357 |
March | 744.00000 | 20.88745 | 31.41552 | -0.5672 | 12.46586 |
April | 720.00000 | 21.19355 | 38.53045 | -0.3914 | 9.38303 |
May | 744.00000 | 21.60982 | 50.14612 | -1.2744 | 39.98098 |
June | 720.00000 | 21.66305 | 54.94260 | -1.1682 | 35.17464 |
July | 744.00000 | 21.71305 | 57.42489 | -1.1176 | 32.84770 |
August | 744.00000 | 21.70138 | 57.51415 | -1.1484 | 34.17387 |
September | 720.00000 | 21.54441 | 48.38981 | -1.3205 | 42.45709 |
October | 744.00000 | 21.14645 | 38.72537 | -0.4209 | 9.00193 |
November | 720.00000 | 20.73780 | 33.47566 | -0.6227 | 14.12997 |
December | 744.00000 | 20.51175 | 24.39229 | -0.7890 | 18.74795 |
Annual Sum or Average | 8760.00000 | 21.14019 | 40.19908 | -0.8714 | 24.05925 |
Minimum of Months | 672.00000 | 20.44155 | 21.17767 | -1.3205 | 9.00193 |
Maximum of Months | 744.00000 | 21.71305 | 57.51415 | -0.3914 | 42.45709 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53380 | 21.29386 | -0.8440 | 20.67336 |
February | 672.00000 | 20.68354 | 25.35455 | -0.7300 | 17.27639 |
March | 744.00000 | 20.94083 | 31.67042 | -0.5667 | 12.83995 |
April | 720.00000 | 21.22242 | 38.77950 | -0.3711 | 9.57982 |
May | 744.00000 | 21.57897 | 50.84720 | -1.2687 | 40.01442 |
June | 720.00000 | 21.63991 | 55.39047 | -1.1430 | 34.32845 |
July | 744.00000 | 21.69351 | 57.29801 | -1.0762 | 31.31167 |
August | 744.00000 | 21.68265 | 57.43831 | -1.1028 | 32.48422 |
September | 720.00000 | 21.54337 | 48.39177 | -1.2860 | 41.29963 |
October | 744.00000 | 21.29510 | 38.80479 | -0.3733 | 8.81811 |
November | 720.00000 | 20.83064 | 33.72640 | -0.6107 | 14.13165 |
December | 744.00000 | 20.61853 | 24.46425 | -0.7872 | 18.77335 |
Annual Sum or Average | 8760.00000 | 21.19144 | 40.36957 | -0.8475 | 23.49669 |
Minimum of Months | 672.00000 | 20.53380 | 21.29386 | -1.2860 | 8.81811 |
Maximum of Months | 744.00000 | 21.69351 | 57.43831 | -0.3711 | 41.29963 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47355 | 21.41180 | -0.8914 | 22.44452 |
February | 672.00000 | 20.51710 | 25.62328 | -0.8028 | 19.49339 |
March | 744.00000 | 20.75146 | 32.00489 | -0.6329 | 14.34658 |
April | 720.00000 | 21.11804 | 39.09097 | -0.4106 | 10.05238 |
May | 744.00000 | 21.54830 | 51.02506 | -1.2888 | 40.90125 |
June | 720.00000 | 21.63442 | 55.44079 | -1.1497 | 34.58235 |
July | 744.00000 | 21.69070 | 57.46877 | -1.0843 | 31.59524 |
August | 744.00000 | 21.67321 | 57.90198 | -1.1198 | 33.10461 |
September | 720.00000 | 21.47115 | 49.03410 | -1.3379 | 43.57451 |
October | 744.00000 | 21.04167 | 39.33738 | -0.4619 | 10.02085 |
November | 720.00000 | 20.67940 | 34.01772 | -0.6704 | 15.59152 |
December | 744.00000 | 20.48743 | 24.66904 | -0.8457 | 20.71359 |
Annual Sum or Average | 8760.00000 | 21.09377 | 40.66670 | -0.8921 | 24.73086 |
Minimum of Months | 672.00000 | 20.47355 | 21.41180 | -1.3379 | 10.02085 |
Maximum of Months | 744.00000 | 21.69070 | 57.90198 | -0.4106 | 43.57451 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97183 | 22.36583 | -0.6426 | 15.01498 |
February | 672.00000 | 21.09796 | 26.06754 | -0.5461 | 12.66403 |
March | 744.00000 | 21.26479 | 31.95954 | -0.4379 | 10.35468 |
April | 720.00000 | 21.34437 | 38.78102 | -0.3364 | 8.77069 |
May | 744.00000 | 21.60297 | 49.96848 | -1.2884 | 40.80081 |
June | 720.00000 | 21.64441 | 54.96677 | -1.1968 | 36.47592 |
July | 744.00000 | 21.68091 | 57.29258 | -1.1449 | 34.09030 |
August | 744.00000 | 21.67989 | 56.48980 | -1.1496 | 34.41865 |
September | 720.00000 | 21.61077 | 47.61404 | -1.2593 | 39.99742 |
October | 744.00000 | 21.51031 | 38.54538 | -0.2718 | 7.71416 |
November | 720.00000 | 21.18563 | 33.75758 | -0.4590 | 10.92463 |
December | 744.00000 | 21.00521 | 25.32397 | -0.6040 | 14.35009 |
Annual Sum or Average | 8760.00000 | 21.38491 | 40.33914 | -0.7796 | 22.18824 |
Minimum of Months | 672.00000 | 20.97183 | 22.36583 | -1.2884 | 7.71416 |
Maximum of Months | 744.00000 | 21.68091 | 57.29258 | -0.2718 | 40.80081 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.89698 | 16.72928 | -0.7399 | 19.69316 |
February | 672.00000 | 19.10594 | 20.62787 | -0.8729 | 20.61997 |
March | 744.00000 | 21.47761 | 27.39207 | -0.2591 | 6.85648 |
April | 720.00000 | 21.54484 | 35.30037 | -0.1609 | 5.96612 |
May | 744.00000 | 21.52053 | 49.23645 | -1.1242 | 32.02163 |
June | 720.00000 | 21.34837 | 55.66337 | -1.1048 | 30.99426 |
July | 744.00000 | 21.22070 | 57.90599 | -1.1223 | 31.69456 |
August | 744.00000 | 21.29285 | 57.29537 | -1.1149 | 31.42118 |
September | 720.00000 | 21.43589 | 47.66854 | -1.1678 | 34.02752 |
October | 744.00000 | 21.57781 | 34.92407 | -0.1633 | 5.91982 |
November | 720.00000 | 21.25806 | 29.13607 | -0.3096 | 8.67154 |
December | 744.00000 | 21.29241 | 20.07998 | -0.3943 | 8.56433 |
Annual Sum or Average | 8760.00000 | 21.09377 | 37.75641 | -0.7101 | 19.69438 |
Minimum of Months | 672.00000 | 19.10594 | 16.72928 | -1.1678 | 5.91982 |
Maximum of Months | 744.00000 | 21.57781 | 57.90599 | -0.1609 | 34.02752 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.89609 | 16.47278 | -0.7062 | 19.01489 |
February | 672.00000 | 19.12463 | 20.36538 | -0.8333 | 19.88674 |
March | 744.00000 | 21.54279 | 27.06835 | -0.2094 | 6.41346 |
April | 720.00000 | 21.61023 | 34.95893 | -0.1122 | 5.70907 |
May | 744.00000 | 21.56682 | 48.88530 | -1.0628 | 29.29964 |
June | 720.00000 | 21.37212 | 55.35047 | -1.0534 | 28.73086 |
July | 744.00000 | 21.23057 | 57.62746 | -1.0771 | 29.65643 |
August | 744.00000 | 21.30562 | 57.00864 | -1.0681 | 29.33187 |
September | 720.00000 | 21.47259 | 47.34965 | -1.1112 | 31.42612 |
October | 744.00000 | 21.64518 | 34.57323 | -0.1142 | 5.66915 |
November | 720.00000 | 21.31042 | 28.81321 | -0.2631 | 8.23705 |
December | 744.00000 | 21.33836 | 19.79766 | -0.3478 | 7.88069 |
Annual Sum or Average | 8760.00000 | 21.13079 | 37.44886 | -0.6622 | 18.42513 |
Minimum of Months | 672.00000 | 19.12463 | 16.47278 | -1.1112 | 5.66915 |
Maximum of Months | 744.00000 | 21.64518 | 57.62746 | -0.1122 | 31.42612 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57540 | 19.15127 | 0.07596 | 23.73862 |
February | 672.00000 | 19.98723 | 23.52314 | -0.0042 | 28.79637 |
March | 744.00000 | 22.86942 | 26.90588 | 0.73049 | 21.84458 |
April | 720.00000 | 22.82025 | 34.32114 | 0.81108 | 24.22469 |
May | 744.00000 | 22.54430 | 47.63257 | 0.19151 | 15.23021 |
June | 720.00000 | 22.22651 | 54.11152 | 0.16844 | 13.90680 |
July | 744.00000 | 22.00449 | 56.58990 | 0.12339 | 12.83842 |
August | 744.00000 | 22.03658 | 56.09492 | 0.11324 | 12.61598 |
September | 720.00000 | 22.43138 | 46.40011 | 0.13847 | 14.33238 |
October | 744.00000 | 22.89144 | 33.78895 | 0.81614 | 24.38768 |
November | 720.00000 | 22.47062 | 28.90227 | 0.63179 | 21.61068 |
December | 744.00000 | 22.62379 | 20.55031 | 0.56496 | 16.61803 |
Annual Sum or Average | 8760.00000 | 22.13702 | 37.40500 | 0.36565 | 19.10689 |
Minimum of Months | 672.00000 | 19.98723 | 19.15127 | -0.0042 | 12.61598 |
Maximum of Months | 744.00000 | 22.89144 | 56.58990 | 0.81614 | 28.79637 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.920487E+09 | 10256.95 | 12-JAN-16:05 | 88.92 | 0.271314E+10 | 0.00 | 0.363363E+10 | 0.35 | 2.95 | 01-JAN-19:07 | 0.00 | 0.00 |
February | 0.306754E+10 | 29142.89 | 25-FEB-16:01 | 183.23 | 0.904158E+10 | 0.00 | 0.121091E+11 | 0.80 | 2.95 | 06-FEB-16:15 | 0.00 | 0.00 |
March | 0.136903E+11 | 105238.87 | 25-MAR-15:01 | 406.56 | 0.394381E+11 | 0.00 | 0.531284E+11 | 1.60 | 3.25 | 25-MAR-15:01 | 0.00 | 0.00 |
April | 0.584903E+11 | 215579.30 | 16-APR-15:03 | 547.34 | 0.183507E+12 | 0.00 | 0.241997E+12 | 2.26 | 3.95 | 18-APR-08:62 | 0.00 | 0.00 |
May | 0.140503E+12 | 209971.63 | 31-MAY-15:03 | 741.76 | 0.440091E+12 | 0.00 | 0.580594E+12 | 2.99 | 4.02 | 11-MAY-18:02 | 0.00 | 0.00 |
June | 0.276475E+12 | 307879.23 | 11-JUN-15:03 | 717.54 | 0.926262E+12 | 0.00 | 0.120274E+13 | 3.21 | 4.10 | 14-JUN-08:62 | 0.00 | 0.00 |
July | 0.370628E+12 | 308938.28 | 26-JUL-18:03 | 744.00 | 0.129527E+13 | 0.00 | 0.166589E+13 | 3.42 | 4.13 | 06-JUL-08:62 | 0.00 | 0.00 |
August | 0.333539E+12 | 331698.77 | 04-AUG-15:03 | 744.00 | 0.114642E+13 | 0.00 | 0.147996E+13 | 3.33 | 4.17 | 26-AUG-08:62 | 0.00 | 0.00 |
September | 0.165329E+12 | 244133.24 | 06-SEP-15:03 | 703.08 | 0.514815E+12 | 0.00 | 0.680144E+12 | 2.94 | 3.97 | 10-SEP-08:62 | 0.00 | 0.00 |
October | 0.362691E+11 | 146226.47 | 20-OCT-15:02 | 665.47 | 0.105318E+12 | 0.00 | 0.141587E+12 | 2.62 | 3.45 | 20-OCT-15:02 | 0.00 | 0.00 |
November | 0.114819E+11 | 89068.90 | 03-NOV-15:01 | 367.58 | 0.335009E+11 | 0.00 | 0.449828E+11 | 1.50 | 3.03 | 03-NOV-15:01 | 0.00 | 0.00 |
December | 0.221770E+10 | 22772.71 | 03-DEC-13:40 | 144.48 | 0.653667E+10 | 0.00 | 0.875437E+10 | 0.57 | 2.95 | 01-DEC-10:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141261E+13 | 6053.98 | 0.470291E+13 | 0.611552E+13 | 2.14 | |||||||
Minimum of Months | 0.920487E+09 | 10256.95 | 88.92 | 0.271314E+10 | 0.00 | 0.363363E+10 | 0.35 | 2.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.370628E+12 | 331698.77 | 744.00 | 0.129527E+13 | 0.00 | 0.166589E+13 | 3.42 | 4.17 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.659792E+12 | 0.00 | 744.00 | 773273.26 | 31-JAN-04:00 | 0.00 | 49.83 | 60.00 | 5.65 | 0.00 | 0.36 | 1.13 | 31-JAN-04:00 |
February | 0.460012E+12 | 0.00 | 672.00 | 813757.25 | 02-FEB-06:03 | 0.00 | 50.24 | 60.01 | 4.24 | 0.00 | 0.28 | 1.18 | 02-FEB-06:03 |
March | 0.179546E+12 | 0.00 | 744.00 | 278874.90 | 05-MAR-19:02 | 0.00 | 48.88 | 60.00 | 1.51 | 0.00 | 0.10 | 0.41 | 05-MAR-19:02 |
April | 0.111392E+12 | 0.00 | 720.00 | 233081.74 | 03-APR-08:62 | 0.00 | 48.28 | 60.00 | 0.93 | 0.00 | 0.06 | 0.34 | 03-APR-08:62 |
May | 0.103627E+12 | 0.00 | 744.00 | 116324.33 | 23-MAY-08:05 | 0.00 | 47.11 | 60.00 | 0.78 | 0.00 | 0.06 | 0.17 | 23-MAY-08:05 |
June | 0.113063E+12 | 0.00 | 720.00 | 120755.94 | 20-JUN-08:05 | 0.00 | 47.57 | 60.00 | 0.90 | 0.00 | 0.06 | 0.18 | 20-JUN-08:05 |
July | 0.126893E+12 | 0.00 | 744.00 | 114469.86 | 25-JUL-08:05 | 0.00 | 47.40 | 60.00 | 0.98 | 0.00 | 0.07 | 0.17 | 25-JUL-08:05 |
August | 0.117303E+12 | 0.00 | 744.00 | 119901.94 | 21-AUG-08:05 | 0.00 | 46.41 | 60.00 | 0.88 | 0.00 | 0.06 | 0.17 | 21-AUG-08:05 |
September | 0.916001E+11 | 0.00 | 720.00 | 135548.09 | 08-SEP-08:05 | 0.00 | 45.96 | 60.00 | 0.68 | 0.00 | 0.05 | 0.20 | 08-SEP-08:05 |
October | 0.744929E+11 | 0.00 | 744.00 | 118568.62 | 28-OCT-15:03 | 0.00 | 46.74 | 60.00 | 0.56 | 0.00 | 0.04 | 0.17 | 28-OCT-15:03 |
November | 0.224787E+12 | 0.00 | 720.00 | 744109.25 | 26-NOV-07:00 | 0.00 | 48.48 | 60.00 | 1.95 | 0.00 | 0.13 | 1.08 | 26-NOV-07:00 |
December | 0.367435E+12 | 0.00 | 744.00 | 406497.40 | 09-DEC-09:03 | 0.00 | 49.67 | 60.00 | 3.21 | 0.00 | 0.20 | 0.59 | 09-DEC-09:03 |
Annual Sum or Average | 0.262994E+13 | 8760.00 | 48.03 | 60.00 | 1.85 | 0.00 | 0.12 | ||||||
Minimum of Months | 0.744929E+11 | 0.00 | 672.00 | 114469.86 | 0.00 | 45.96 | 60.00 | 0.56 | 0.00 | 0.04 | 0.17 | ||
Maximum of Months | 0.659792E+12 | 0.00 | 744.00 | 813757.25 | 0.00 | 50.24 | 60.01 | 5.65 | 0.00 | 0.36 | 1.18 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 9663933.20 | 0.00 | 1.83 | 9663933.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.99 | 12-JAN-16:02 | 16672.99 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.144253E+09 | 0.00 | 25.40 | 0.143381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17332.97 | 24-FEB-16:02 | 17332.97 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.570067E+09 | 0.00 | 107.11 | 0.451983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17341.22 | 28-MAR-15:01 | 17341.22 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.252977E+10 | 0.00 | 274.72 | 0.179435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19120.11 | 16-APR-08:62 | 17338.00 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.426008E+10 | 0.00 | 503.22 | 0.240284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19878.72 | 11-MAY-18:02 | 17340.90 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.723259E+10 | 0.00 | 580.57 | 0.395814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22069.88 | 26-JUN-08:62 | 16723.63 | 15-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.911058E+10 | 0.00 | 661.27 | 0.489973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21292.61 | 14-JUL-18:02 | 16754.30 | 05-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.810286E+10 | 0.00 | 661.30 | 0.414180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23757.42 | 03-AUG-08:61 | 16725.00 | 20-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.495569E+10 | 0.00 | 493.71 | 0.290298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19760.33 | 11-SEP-08:62 | 17341.56 | 19-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.142900E+10 | 0.00 | 241.96 | 0.107275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18203.41 | 02-OCT-15:01 | 17336.22 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.316580E+09 | 0.00 | 80.04 | 0.206901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17321.69 | 04-NOV-15:01 | 17321.69 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 16110715.80 | 0.00 | 3.60 | 16110715.80 | 0.00 | 0.00 | 0.00 | 0.00 | 16624.94 | 02-DEC-16:01 | 16624.94 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386772E+11 | 3634.71 | 0.220006E+11 | ||||||||||||
Minimum of Months | 9663933.20 | 0.00 | 1.83 | 9663933.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16624.94 | 16624.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.911058E+10 | 0.00 | 661.30 | 0.489973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23757.42 | 17341.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1350940.78 | 0.00 | 0.47 | 1350940.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2656.21 | 12-JAN-19:04 | 2656.21 | 12-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 49574147.57 | 0.00 | 8.41 | 49574147.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16602.43 | 24-FEB-16:02 | 16602.43 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.295245E+09 | 0.00 | 64.26 | 0.223509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17072.23 | 25-MAR-15:01 | 17072.23 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.203569E+10 | 0.00 | 232.59 | 0.142208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18702.43 | 16-APR-08:62 | 17079.75 | 19-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.392505E+10 | 0.00 | 478.82 | 0.217996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19550.75 | 11-MAY-18:02 | 17083.83 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.701710E+10 | 0.00 | 571.77 | 0.384083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21686.28 | 26-JUN-08:62 | 16482.20 | 30-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.873239E+10 | 0.00 | 647.93 | 0.467579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21265.17 | 17-JUL-18:02 | 16482.54 | 04-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.740510E+10 | 0.00 | 635.29 | 0.372469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23461.25 | 03-AUG-08:61 | 16467.72 | 10-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.392799E+10 | 0.00 | 435.37 | 0.218057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19059.27 | 11-SEP-08:62 | 17083.53 | 19-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.738907E+09 | 0.00 | 142.80 | 0.514661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17671.94 | 02-OCT-15:01 | 17056.20 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.135437E+09 | 0.00 | 42.89 | 78159584.87 | 0.00 | 0.00 | 0.00 | 0.00 | 17062.44 | 04-NOV-15:01 | 17062.44 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2000354.15 | 0.00 | 0.44 | 2000354.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2706.65 | 01-DEC-16:03 | 2706.65 | 01-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342658E+11 | 3261.04 | 0.188932E+11 | ||||||||||||
Minimum of Months | 1350940.78 | 0.00 | 0.44 | 1350940.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2656.21 | 2656.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.873239E+10 | 0.00 | 647.93 | 0.467579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23461.25 | 17083.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.356507E+09 | 0.00 | 12.96 | 0.356507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14380.09 | 13-JAN-12:30 | 14380.09 | 13-JAN-12:30 | 0.00 | 0.00 | 0.00 |
February | 0.264277E+10 | 0.00 | 62.58 | 0.264277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33287.86 | 08-FEB-13:40 | 33287.86 | 08-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.718778E+10 | 0.00 | 166.83 | 0.669778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39168.36 | 24-MAR-12:50 | 39168.36 | 24-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.144409E+11 | 0.00 | 273.03 | 0.107074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56417.85 | 16-APR-19:05 | 39480.10 | 16-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.232175E+11 | 0.00 | 537.38 | 0.128711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42331.06 | 31-MAY-19:10 | 31375.53 | 05-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.343857E+11 | 0.00 | 610.46 | 0.159841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52985.54 | 18-JUN-20:50 | 36691.95 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 |
July | 0.424971E+11 | 0.00 | 673.07 | 0.192870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60555.39 | 25-JUL-21:00 | 37192.73 | 02-JUL-19:20 | 0.00 | 0.00 | 0.00 |
August | 0.433549E+11 | 0.00 | 674.85 | 0.211944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54441.07 | 02-AUG-19:30 | 38064.09 | 02-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.373449E+11 | 0.00 | 566.79 | 0.258868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53801.10 | 17-SEP-13:20 | 45134.32 | 20-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.254670E+11 | 0.00 | 447.58 | 0.233623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58806.86 | 20-OCT-12:30 | 58806.86 | 20-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.868390E+10 | 0.00 | 179.41 | 0.754607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61388.57 | 04-NOV-12:20 | 61388.57 | 04-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 0.249538E+10 | 0.00 | 41.61 | 0.249538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42309.95 | 03-DEC-13:00 | 42309.95 | 03-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242074E+12 | 4246.55 | 0.149032E+12 | ||||||||||||
Minimum of Months | 0.356507E+09 | 0.00 | 12.96 | 0.356507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14380.09 | 14380.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.433549E+11 | 0.00 | 674.85 | 0.258868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61388.57 | 61388.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.566043E+09 | 0.00 | 35.48 | 0.566043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54927.63 | 01-JAN-09:02 | 54927.63 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.229232E+10 | 0.00 | 106.15 | 0.229232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90294.94 | 25-FEB-09:02 | 90294.94 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.103624E+11 | 0.00 | 277.57 | 0.849607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93891.57 | 25-MAR-18:02 | 93891.57 | 25-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.249310E+11 | 0.00 | 426.34 | 0.188655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106475.78 | 18-APR-18:02 | 96518.25 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.493293E+11 | 0.00 | 529.51 | 0.320925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109716.49 | 11-MAY-18:02 | 95896.66 | 21-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.667973E+11 | 0.00 | 537.99 | 0.425844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128745.64 | 26-JUN-08:62 | 92815.78 | 16-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.767373E+11 | 0.00 | 555.30 | 0.469858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126942.19 | 17-JUL-18:02 | 93351.98 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.705773E+11 | 0.00 | 542.54 | 0.419438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139960.80 | 03-AUG-08:61 | 93655.32 | 09-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.449165E+11 | 0.00 | 510.31 | 0.297373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107932.19 | 11-SEP-08:62 | 94688.71 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.217649E+11 | 0.00 | 476.74 | 0.176045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97113.33 | 02-OCT-15:01 | 92126.74 | 29-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.100721E+11 | 0.00 | 255.55 | 0.703904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92157.54 | 08-NOV-19:03 | 92045.46 | 03-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.803017E+09 | 0.00 | 54.81 | 0.803017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60736.40 | 02-DEC-09:01 | 60736.40 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379149E+12 | 4308.27 | 0.249010E+12 | ||||||||||||
Minimum of Months | 0.566043E+09 | 0.00 | 35.48 | 0.566043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54927.63 | 54927.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.767373E+11 | 0.00 | 555.30 | 0.469858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139960.80 | 96518.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4945074.08 | 0.00 | 2.92 | 4945074.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3845.13 | 12-JAN-09:03 | 3845.13 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 87339784.17 | 0.00 | 16.85 | 87290101.33 | 0.00 | 0.00 | 0.00 | 0.00 | 15105.21 | 24-FEB-09:01 | 15105.21 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.526881E+09 | 0.00 | 121.44 | 0.405730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15650.49 | 28-MAR-15:01 | 15650.49 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.212588E+10 | 0.00 | 272.42 | 0.141771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17008.46 | 16-APR-08:62 | 15649.25 | 23-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.454888E+10 | 0.00 | 552.16 | 0.257750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17755.65 | 11-MAY-18:02 | 15650.38 | 03-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.734374E+10 | 0.00 | 615.55 | 0.405193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18487.76 | 14-JUN-08:62 | 15111.73 | 09-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.886274E+10 | 0.00 | 693.54 | 0.471232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19159.27 | 20-JUL-08:62 | 15107.77 | 01-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.781092E+10 | 0.00 | 678.48 | 0.396505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20042.66 | 31-AUG-18:02 | 15121.65 | 29-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.498041E+10 | 0.00 | 520.60 | 0.291623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17720.90 | 10-SEP-08:62 | 15650.70 | 19-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.122928E+10 | 0.00 | 255.19 | 0.909263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16130.59 | 02-OCT-15:01 | 15645.84 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.277072E+09 | 0.00 | 84.06 | 0.177969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15632.39 | 04-NOV-15:01 | 15632.39 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 26064877.92 | 0.00 | 7.48 | 26064877.92 | 0.00 | 0.00 | 0.00 | 0.00 | 10415.98 | 03-DEC-09:02 | 10415.98 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378242E+11 | 3820.68 | 0.212520E+11 | ||||||||||||
Minimum of Months | 4945074.08 | 0.00 | 2.92 | 4945074.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3845.13 | 3845.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.886274E+10 | 0.00 | 693.54 | 0.471232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20042.66 | 15650.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1016550.22 | 0.00 | 0.17 | 1016550.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2934.12 | 13-JAN-19:04 | 2934.12 | 13-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 21693340.36 | 0.00 | 6.36 | 21693340.36 | 0.00 | 0.00 | 0.00 | 0.00 | 14568.71 | 24-FEB-09:01 | 14568.71 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.256946E+09 | 0.00 | 67.50 | 0.184916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15228.15 | 28-MAR-08:62 | 15228.15 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.165094E+10 | 0.00 | 228.00 | 0.106508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16824.09 | 18-APR-18:02 | 15564.99 | 23-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.418432E+10 | 0.00 | 515.11 | 0.235067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17629.91 | 11-MAY-18:02 | 15566.64 | 19-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.711193E+10 | 0.00 | 609.70 | 0.392466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18307.74 | 30-JUN-08:61 | 14868.67 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.847049E+10 | 0.00 | 688.42 | 0.449703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19210.03 | 17-JUL-18:02 | 15028.23 | 23-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.708219E+10 | 0.00 | 664.03 | 0.352634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19527.77 | 31-AUG-08:62 | 14961.68 | 09-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.389720E+10 | 0.00 | 464.09 | 0.214907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17543.17 | 10-SEP-08:62 | 15490.85 | 20-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.504619E+09 | 0.00 | 141.21 | 0.318378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15693.47 | 02-OCT-15:01 | 14294.04 | 08-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 70311320.68 | 0.00 | 41.29 | 34574407.04 | 0.00 | 0.00 | 0.00 | 0.00 | 9557.42 | 04-NOV-08:62 | 9557.42 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 2214795.08 | 0.00 | 0.97 | 2214795.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3271.55 | 02-DEC-09:03 | 3271.55 | 02-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332539E+11 | 3426.84 | 0.180756E+11 | ||||||||||||
Minimum of Months | 1016550.22 | 0.00 | 0.17 | 1016550.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2934.12 | 2934.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.847049E+10 | 0.00 | 688.42 | 0.449703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19527.77 | 15566.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2214906.17 | 0.00 | 1.97 | 2214906.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.93 | 12-JAN-16:02 | 4340.93 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 36973949.82 | 0.00 | 19.31 | 36900287.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.30 | 24-FEB-16:02 | 4531.30 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.136434E+09 | 0.00 | 86.19 | 0.110868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4533.39 | 28-MAR-15:01 | 4533.39 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.717783E+09 | 0.00 | 256.50 | 0.524037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5094.55 | 16-APR-08:62 | 4533.08 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.124819E+10 | 0.00 | 510.21 | 0.737851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5263.56 | 29-MAY-08:62 | 4533.16 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.216974E+10 | 0.00 | 592.09 | 0.125830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5850.90 | 26-JUN-08:62 | 4366.34 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.273299E+10 | 0.00 | 679.83 | 0.155285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5755.82 | 20-JUL-08:62 | 4378.88 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.240895E+10 | 0.00 | 675.78 | 0.130667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6307.63 | 03-AUG-08:61 | 4366.53 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.143998E+10 | 0.00 | 479.41 | 0.904036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5314.79 | 11-SEP-08:62 | 4533.60 | 19-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.364463E+09 | 0.00 | 203.11 | 0.279135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.02 | 02-OCT-15:01 | 4532.07 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 73443802.35 | 0.00 | 57.71 | 53069663.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4528.27 | 04-NOV-15:01 | 4528.27 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2952340.16 | 0.00 | 2.41 | 2952340.16 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.51 | 02-DEC-16:01 | 4316.51 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113341E+11 | 3564.51 | 0.676889E+10 | ||||||||||||
Minimum of Months | 2214906.17 | 0.00 | 1.97 | 2214906.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.51 | 4316.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.273299E+10 | 0.00 | 679.83 | 0.155285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6307.63 | 4533.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 491728.22 | 0.00 | 0.42 | 491728.22 | 0.00 | 0.00 | 0.00 | 0.00 | 883.87 | 12-JAN-16:03 | 883.87 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 10648003.45 | 0.00 | 8.59 | 10601921.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4270.62 | 24-FEB-16:02 | 4270.62 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 64194330.11 | 0.00 | 50.28 | 48554190.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4461.51 | 24-MAR-18:01 | 4461.51 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.576830E+09 | 0.00 | 222.74 | 0.413248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5004.08 | 16-APR-08:62 | 4463.20 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.115148E+10 | 0.00 | 484.93 | 0.675841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5183.52 | 29-MAY-08:62 | 4464.09 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.211088E+10 | 0.00 | 586.36 | 0.122391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5746.81 | 26-JUN-08:62 | 4288.23 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.263082E+10 | 0.00 | 675.38 | 0.149315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5604.85 | 20-JUL-08:62 | 4295.09 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.221779E+10 | 0.00 | 664.69 | 0.118493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6226.90 | 03-AUG-08:61 | 4299.73 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.115510E+10 | 0.00 | 433.48 | 0.688140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5143.82 | 11-SEP-08:62 | 4464.20 | 19-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.178700E+09 | 0.00 | 118.55 | 0.127891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4667.93 | 02-OCT-15:01 | 4439.40 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 27745851.10 | 0.00 | 27.17 | 18216461.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4457.16 | 04-NOV-15:01 | 4457.16 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 702853.01 | 0.00 | 0.58 | 702853.01 | 0.00 | 0.00 | 0.00 | 0.00 | 739.23 | 02-DEC-16:03 | 739.23 | 02-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101254E+11 | 3273.17 | 0.588567E+10 | ||||||||||||
Minimum of Months | 491728.22 | 0.00 | 0.42 | 491728.22 | 0.00 | 0.00 | 0.00 | 0.00 | 739.23 | 739.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.263082E+10 | 0.00 | 675.38 | 0.149315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6226.90 | 4464.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.605339E+09 | 0.00 | 61.32 | 0.605339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17962.16 | 13-JAN-16:01 | 17962.16 | 13-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.114345E+10 | 0.00 | 108.14 | 0.113438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17969.74 | 24-FEB-16:02 | 17969.74 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.202235E+10 | 0.00 | 228.59 | 0.173466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17972.83 | 23-MAR-15:01 | 17972.83 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.409414E+10 | 0.00 | 338.92 | 0.300985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19946.74 | 16-APR-08:62 | 17975.41 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.674847E+10 | 0.00 | 566.17 | 0.392388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20573.74 | 29-MAY-18:02 | 17972.96 | 06-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.103497E+11 | 0.00 | 611.72 | 0.601194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24008.10 | 26-JUN-08:62 | 17123.81 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.129244E+11 | 0.00 | 668.33 | 0.731946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22968.28 | 20-JUL-08:62 | 17341.37 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.127979E+11 | 0.00 | 669.63 | 0.736733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25772.43 | 03-AUG-08:61 | 17362.19 | 08-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.945863E+10 | 0.00 | 572.08 | 0.655700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21084.34 | 11-SEP-08:62 | 17974.76 | 20-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.528485E+10 | 0.00 | 439.45 | 0.452446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18886.44 | 02-OCT-15:01 | 17974.85 | 24-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.194549E+10 | 0.00 | 205.12 | 0.154638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17959.02 | 04-NOV-15:01 | 17959.02 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.119956E+10 | 0.00 | 99.51 | 0.119956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17965.59 | 02-DEC-16:01 | 17965.59 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.685744E+11 | 4568.98 | 0.449342E+11 | ||||||||||||
Minimum of Months | 0.605339E+09 | 0.00 | 61.32 | 0.605339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17959.02 | 17123.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129244E+11 | 0.00 | 669.63 | 0.736733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25772.43 | 17975.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 211.60 | 0.00 | 0.14 | 211.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 12-JAN-19:04 | 0.45 | 12-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 664.06 | 0.00 | 0.42 | 664.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 | 24-FEB-19:05 | 0.56 | 24-FEB-19:05 | 0.00 | 0.00 | 0.00 |
March | 0.111124E+11 | 0.00 | 39.75 | 0.111124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190870.38 | 19-MAR-16:00 | 190870.38 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.111495E+12 | 0.00 | 155.82 | 0.861502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 473943.59 | 16-APR-21:50 | 330946.98 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.304031E+12 | 0.00 | 444.87 | 0.218328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 545747.01 | 30-MAY-09:30 | 331155.20 | 31-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.703371E+12 | 0.00 | 582.88 | 0.453017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 635738.29 | 18-JUN-22:00 | 362540.31 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.101431E+13 | 0.00 | 725.83 | 0.584779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 749196.57 | 26-JUL-19:00 | 337588.14 | 26-JUL-15:50 | 0.00 | 0.00 | 0.00 |
August | 0.889374E+12 | 0.00 | 695.83 | 0.522751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 745089.11 | 04-AUG-13:00 | 372391.20 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.358204E+12 | 0.00 | 433.88 | 0.293823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 554077.30 | 11-SEP-22:55 | 352755.93 | 06-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.347880E+11 | 0.00 | 110.96 | 0.344424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276540.56 | 20-OCT-15:00 | 276540.56 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.608886E+10 | 0.00 | 45.62 | 0.608886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100836.91 | 03-NOV-14:00 | 100836.91 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 183.28 | 0.00 | 0.13 | 183.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 04-DEC-19:04 | 0.43 | 04-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343278E+13 | 3236.14 | 0.221049E+13 | ||||||||||||
Minimum of Months | 183.28 | 0.00 | 0.13 | 183.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101431E+13 | 0.00 | 725.83 | 0.584779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 749196.57 | 372391.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.508255E+09 | 0.00 | 24.50 | 0.508255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14383.08 | 19-MAR-16:00 | 14383.08 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.824908E+10 | 0.00 | 116.17 | 0.656204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46188.78 | 16-APR-10:08 | 31588.75 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.197730E+11 | 0.00 | 344.83 | 0.151498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56501.34 | 29-MAY-14:00 | 31636.83 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.568394E+11 | 0.00 | 535.00 | 0.378315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64404.98 | 12-JUN-13:50 | 34019.99 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.831602E+11 | 0.00 | 693.67 | 0.493807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66044.57 | 27-JUL-00:10 | 32071.20 | 26-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.712235E+11 | 0.00 | 646.00 | 0.432003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71793.13 | 31-AUG-18:02 | 34455.14 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.266698E+11 | 0.00 | 377.67 | 0.235580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48659.26 | 11-SEP-08:62 | 32964.23 | 06-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.189297E+10 | 0.00 | 63.50 | 0.189297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26355.69 | 20-OCT-15:00 | 26355.69 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 69740718.45 | 0.00 | 10.00 | 69740718.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.28 | 03-NOV-14:00 | 4334.28 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268386E+12 | 2811.33 | 0.178153E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.831602E+11 | 0.00 | 693.67 | 0.493807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71793.13 | 34455.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.80 | 591.77 | 272.03 | 712.04 | 929.74 | 0.00 | 0.00 | 744.00 |
February | 931.56 | 632.07 | 299.49 | 784.03 | 725.69 | 0.00 | 0.00 | 672.00 |
March | 798.14 | 417.95 | 380.19 | 627.93 | 559.55 | 0.00 | 0.00 | 744.00 |
April | 711.24 | 325.93 | 385.30 | 552.71 | 394.07 | 0.00 | 0.00 | 720.00 |
May | 606.52 | 169.60 | 436.93 | 496.16 | 203.92 | 0.00 | 0.00 | 744.00 |
June | 578.99 | 115.55 | 463.44 | 553.14 | 116.77 | 0.00 | 0.00 | 720.00 |
July | 614.42 | 153.58 | 460.84 | 611.08 | 88.11 | 0.00 | 0.00 | 744.00 |
August | 680.89 | 235.73 | 445.16 | 710.95 | 112.87 | 0.00 | 0.00 | 744.00 |
September | 822.35 | 424.41 | 397.94 | 842.17 | 231.75 | 0.00 | 0.00 | 720.00 |
October | 886.38 | 558.94 | 327.44 | 865.38 | 401.00 | 0.00 | 0.00 | 744.00 |
November | 663.13 | 415.16 | 247.97 | 565.24 | 610.14 | 0.00 | 0.00 | 720.00 |
December | 705.87 | 534.51 | 171.36 | 630.17 | 892.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.51 | 379.87 | 357.64 | 661.96 | 437.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 578.99 | 115.55 | 171.36 | 496.16 | 88.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 931.56 | 632.07 | 463.44 | 865.38 | 929.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2432.41 | 1666.38 | 766.03 | 1998.68 | 2622.64 | 0.00 | 0.00 | 744.00 |
February | 2623.21 | 1779.87 | 843.34 | 2199.56 | 2052.58 | 0.00 | 0.00 | 672.00 |
March | 2247.50 | 1176.92 | 1070.58 | 1757.66 | 1576.68 | 0.00 | 0.00 | 744.00 |
April | 2002.79 | 917.81 | 1084.99 | 1548.39 | 1109.37 | 0.00 | 0.00 | 720.00 |
May | 1707.93 | 477.58 | 1230.35 | 1385.84 | 567.88 | 0.00 | 0.00 | 744.00 |
June | 1630.40 | 325.37 | 1305.02 | 1548.77 | 321.31 | 0.00 | 0.00 | 720.00 |
July | 1730.18 | 432.47 | 1297.71 | 1713.08 | 238.54 | 0.00 | 0.00 | 744.00 |
August | 1917.35 | 663.80 | 1253.55 | 1994.37 | 309.64 | 0.00 | 0.00 | 744.00 |
September | 2315.69 | 1195.11 | 1120.58 | 2367.00 | 646.22 | 0.00 | 0.00 | 720.00 |
October | 2495.99 | 1573.95 | 922.04 | 2429.75 | 1127.30 | 0.00 | 0.00 | 744.00 |
November | 1867.32 | 1169.06 | 698.26 | 1582.63 | 1720.31 | 0.00 | 0.00 | 720.00 |
December | 1987.68 | 1505.14 | 482.54 | 1766.76 | 2521.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2076.78 | 1069.70 | 1007.08 | 1855.95 | 1230.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1630.40 | 325.37 | 482.54 | 1385.84 | 238.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2623.21 | 1779.87 | 1305.02 | 2429.75 | 2622.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3159.84 | 2164.73 | 995.12 | 2630.49 | 3506.87 | 0.00 | 0.00 | 744.00 |
February | 3407.69 | 2312.15 | 1095.55 | 2913.76 | 2713.23 | 0.00 | 0.00 | 672.00 |
March | 2919.63 | 1528.89 | 1390.74 | 2323.07 | 2105.96 | 0.00 | 0.00 | 744.00 |
April | 2601.74 | 1192.28 | 1409.46 | 2053.03 | 1485.84 | 0.00 | 0.00 | 720.00 |
May | 2218.70 | 620.40 | 1598.30 | 1848.50 | 764.35 | 0.00 | 0.00 | 744.00 |
June | 2117.98 | 422.68 | 1695.30 | 2069.62 | 431.87 | 0.00 | 0.00 | 720.00 |
July | 2247.60 | 561.80 | 1685.80 | 2288.49 | 316.90 | 0.00 | 0.00 | 744.00 |
August | 2490.75 | 862.31 | 1628.44 | 2655.11 | 411.63 | 0.00 | 0.00 | 744.00 |
September | 3008.21 | 1552.52 | 1455.69 | 3137.64 | 861.74 | 0.00 | 0.00 | 720.00 |
October | 3242.43 | 2044.65 | 1197.78 | 3215.63 | 1502.39 | 0.00 | 0.00 | 744.00 |
November | 2425.76 | 1518.67 | 907.08 | 2087.88 | 2300.97 | 0.00 | 0.00 | 720.00 |
December | 2582.11 | 1955.26 | 626.85 | 2325.87 | 3369.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2697.86 | 1389.60 | 1308.26 | 2460.09 | 1643.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 2117.98 | 422.68 | 626.85 | 1848.50 | 316.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3407.69 | 2312.15 | 1695.30 | 3215.63 | 3506.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.49 | 202.91 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 148.16 | 164.36 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 121.86 | 118.81 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.19 | 84.53 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 94.68 | 44.00 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 106.09 | 25.14 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 117.21 | 18.95 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 137.38 | 24.20 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 164.68 | 48.87 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 169.15 | 84.39 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 110.10 | 129.75 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.53 | 187.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 127.94 | 94.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 94.68 | 18.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 169.15 | 202.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 31.39 | 437.33 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 76.45 | 348.63 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 108.54 | 227.90 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 241.85 | 153.79 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 273.30 | 79.35 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 368.12 | 46.05 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 410.12 | 35.01 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 357.69 | 44.74 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 259.14 | 90.52 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 128.40 | 163.57 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 44.48 | 267.99 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 27.17 | 392.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 194.47 | 189.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 27.17 | 35.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 410.12 | 437.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.69 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.43 | 200.80 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 9.73 | 129.22 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.48 | 84.89 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 56.77 | 40.92 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 88.24 | 23.12 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 88.29 | 17.67 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 76.80 | 22.90 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 45.74 | 49.05 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.23 | 90.02 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.80 | 149.41 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 34.16 | 105.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 88.29 | 248.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 32.80 | 433.13 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 79.15 | 343.70 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 112.28 | 225.11 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 244.62 | 152.55 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 274.69 | 78.88 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 368.77 | 45.79 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 410.95 | 34.76 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 359.22 | 44.32 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 262.30 | 89.47 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 133.33 | 161.02 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 46.95 | 264.72 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 28.94 | 387.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 196.75 | 187.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 28.94 | 34.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 410.95 | 433.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.33 | 93.39 | 42.93 | 107.46 | 161.97 | 0.00 | 0.00 | 744.00 |
February | 147.02 | 99.75 | 47.27 | 115.88 | 137.53 | 0.00 | 0.00 | 672.00 |
March | 125.96 | 65.96 | 60.00 | 94.49 | 100.87 | 0.00 | 0.00 | 744.00 |
April | 112.25 | 51.44 | 60.81 | 83.60 | 75.93 | 0.00 | 0.00 | 720.00 |
May | 95.72 | 26.77 | 68.96 | 72.39 | 42.28 | 0.00 | 0.00 | 744.00 |
June | 91.38 | 18.24 | 73.14 | 81.94 | 26.03 | 0.00 | 0.00 | 720.00 |
July | 96.97 | 24.24 | 72.73 | 91.18 | 20.35 | 0.00 | 0.00 | 744.00 |
August | 107.46 | 37.20 | 70.26 | 107.22 | 25.41 | 0.00 | 0.00 | 744.00 |
September | 129.78 | 66.98 | 62.80 | 128.76 | 47.24 | 0.00 | 0.00 | 720.00 |
October | 139.89 | 88.21 | 51.68 | 131.09 | 77.84 | 0.00 | 0.00 | 744.00 |
November | 104.65 | 65.52 | 39.13 | 85.08 | 111.69 | 0.00 | 0.00 | 720.00 |
December | 111.40 | 84.36 | 27.04 | 96.99 | 151.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.39 | 59.95 | 56.44 | 99.59 | 81.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 91.38 | 18.24 | 27.04 | 72.39 | 20.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 147.02 | 99.75 | 73.14 | 131.09 | 161.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.86 | 0.00 | 21.86 | 0.00 | 206.52 | 0.00 | 0.00 | 744.00 |
February | 27.72 | 0.00 | 27.72 | 0.22 | 167.63 | 0.00 | 0.00 | 672.00 |
March | 41.55 | 0.00 | 41.55 | 7.18 | 107.34 | 0.00 | 0.00 | 744.00 |
April | 48.15 | 0.39 | 47.76 | 20.98 | 69.64 | 0.00 | 0.00 | 720.00 |
May | 62.60 | 2.37 | 60.24 | 47.00 | 32.97 | 0.00 | 0.00 | 744.00 |
June | 73.26 | 6.78 | 66.48 | 73.27 | 18.37 | 0.00 | 0.00 | 720.00 |
July | 68.71 | 4.73 | 63.98 | 73.90 | 13.57 | 0.00 | 0.00 | 744.00 |
August | 57.57 | 1.16 | 56.41 | 64.34 | 17.92 | 0.00 | 0.00 | 744.00 |
September | 44.06 | 0.04 | 44.02 | 38.03 | 39.59 | 0.00 | 0.00 | 720.00 |
October | 32.72 | 0.00 | 32.72 | 10.09 | 74.16 | 0.00 | 0.00 | 744.00 |
November | 22.89 | 0.00 | 22.89 | 1.95 | 125.20 | 0.00 | 0.00 | 720.00 |
December | 14.85 | 0.00 | 14.85 | 0.00 | 181.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.08 | 1.29 | 41.78 | 28.25 | 87.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.85 | 0.00 | 14.85 | 0.00 | 13.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.26 | 6.78 | 66.48 | 73.90 | 206.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 25.91 | 430.84 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 56.63 | 341.46 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 112.60 | 221.95 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 193.65 | 149.56 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 299.41 | 74.50 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.17 | 43.38 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 392.29 | 32.61 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 329.37 | 41.64 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 264.74 | 87.62 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 108.10 | 157.68 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 31.39 | 263.17 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.45 | 387.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 184.50 | 185.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.45 | 32.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 392.29 | 430.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.26 | 202.73 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 147.86 | 163.68 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 120.93 | 118.58 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 106.71 | 83.76 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 93.40 | 43.98 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 105.22 | 24.96 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 116.57 | 18.52 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 136.94 | 23.84 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 163.75 | 48.57 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 168.61 | 84.04 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 109.98 | 129.49 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.46 | 186.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 127.37 | 93.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 93.40 | 18.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 168.61 | 202.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.66 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.35 | 200.18 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 9.31 | 129.52 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.15 | 84.23 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 55.46 | 40.98 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 87.36 | 22.94 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 87.62 | 17.24 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 76.33 | 22.59 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 44.79 | 48.96 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 12.85 | 89.80 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.72 | 149.18 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 33.70 | 105.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 87.62 | 248.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 26.51 | 425.86 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 58.01 | 335.05 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 115.51 | 218.41 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 196.25 | 148.06 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 300.62 | 74.06 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.84 | 43.17 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 393.10 | 32.40 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 330.76 | 41.23 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 267.51 | 86.53 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 112.45 | 154.56 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 32.94 | 258.98 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.90 | 381.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 186.23 | 182.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.90 | 32.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 393.10 | 425.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.00 | 314.32 | 0.00 | 0.00 | 744.00 |
February | 43.87 | 0.00 | 43.87 | 0.41 | 242.62 | 0.00 | 0.00 | 672.00 |
March | 65.76 | 0.00 | 65.76 | 12.43 | 165.59 | 0.00 | 0.00 | 744.00 |
April | 76.21 | 0.61 | 75.60 | 35.47 | 106.04 | 0.00 | 0.00 | 720.00 |
May | 99.09 | 3.74 | 95.34 | 79.27 | 49.51 | 0.00 | 0.00 | 744.00 |
June | 115.95 | 10.73 | 105.22 | 121.86 | 26.86 | 0.00 | 0.00 | 720.00 |
July | 108.76 | 7.49 | 101.27 | 122.85 | 19.55 | 0.00 | 0.00 | 744.00 |
August | 91.13 | 1.84 | 89.29 | 107.05 | 26.28 | 0.00 | 0.00 | 744.00 |
September | 69.74 | 0.06 | 69.68 | 63.68 | 59.58 | 0.00 | 0.00 | 720.00 |
October | 51.79 | 0.00 | 51.79 | 17.54 | 113.39 | 0.00 | 0.00 | 744.00 |
November | 36.23 | 0.00 | 36.23 | 3.53 | 192.56 | 0.00 | 0.00 | 720.00 |
December | 23.50 | 0.00 | 23.50 | 0.00 | 283.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.18 | 2.05 | 66.13 | 47.29 | 132.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.50 | 0.00 | 23.50 | 0.00 | 19.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 115.95 | 10.73 | 105.22 | 122.85 | 314.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.00 | 115.87 | 0.00 | 0.00 | 744.00 |
February | 16.17 | 0.00 | 16.17 | 0.15 | 89.44 | 0.00 | 0.00 | 672.00 |
March | 24.24 | 0.00 | 24.24 | 4.58 | 61.04 | 0.00 | 0.00 | 744.00 |
April | 28.10 | 0.23 | 27.87 | 13.07 | 39.09 | 0.00 | 0.00 | 720.00 |
May | 36.53 | 1.38 | 35.15 | 29.22 | 18.25 | 0.00 | 0.00 | 744.00 |
June | 42.74 | 3.96 | 38.79 | 44.92 | 9.90 | 0.00 | 0.00 | 720.00 |
July | 40.09 | 2.76 | 37.33 | 45.29 | 7.21 | 0.00 | 0.00 | 744.00 |
August | 33.59 | 0.68 | 32.92 | 39.46 | 9.69 | 0.00 | 0.00 | 744.00 |
September | 25.71 | 0.02 | 25.69 | 23.47 | 21.97 | 0.00 | 0.00 | 720.00 |
October | 19.09 | 0.00 | 19.09 | 6.47 | 41.80 | 0.00 | 0.00 | 744.00 |
November | 13.35 | 0.00 | 13.35 | 1.30 | 70.99 | 0.00 | 0.00 | 720.00 |
December | 8.66 | 0.00 | 8.66 | 0.00 | 104.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.13 | 0.75 | 24.38 | 17.43 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.66 | 0.00 | 8.66 | 0.00 | 7.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 42.74 | 3.96 | 38.79 | 45.29 | 115.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.53 | 54.48 | 25.05 | 64.43 | 93.41 | 0.00 | 0.00 | 744.00 |
February | 85.76 | 58.19 | 27.57 | 71.55 | 72.77 | 0.00 | 0.00 | 672.00 |
March | 73.48 | 38.48 | 35.00 | 57.76 | 55.33 | 0.00 | 0.00 | 744.00 |
April | 65.48 | 30.01 | 35.47 | 51.87 | 38.54 | 0.00 | 0.00 | 720.00 |
May | 55.84 | 15.61 | 40.23 | 47.12 | 19.34 | 0.00 | 0.00 | 744.00 |
June | 53.31 | 10.64 | 42.67 | 53.33 | 10.61 | 0.00 | 0.00 | 720.00 |
July | 56.57 | 14.14 | 42.43 | 58.92 | 7.60 | 0.00 | 0.00 | 744.00 |
August | 62.69 | 21.70 | 40.98 | 68.02 | 10.03 | 0.00 | 0.00 | 744.00 |
September | 75.71 | 39.07 | 36.64 | 79.72 | 21.55 | 0.00 | 0.00 | 720.00 |
October | 81.61 | 51.46 | 30.15 | 80.68 | 38.62 | 0.00 | 0.00 | 744.00 |
November | 61.05 | 38.22 | 22.83 | 51.92 | 60.63 | 0.00 | 0.00 | 720.00 |
December | 64.99 | 49.21 | 15.78 | 57.87 | 88.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.90 | 34.97 | 32.93 | 61.88 | 42.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.31 | 10.64 | 15.78 | 47.12 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.76 | 58.19 | 42.67 | 80.68 | 93.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.85 | 147.87 | 67.98 | 174.88 | 253.53 | 0.00 | 0.00 | 744.00 |
February | 232.78 | 157.95 | 74.84 | 194.20 | 197.50 | 0.00 | 0.00 | 672.00 |
March | 199.44 | 104.44 | 95.00 | 156.76 | 150.19 | 0.00 | 0.00 | 744.00 |
April | 177.73 | 81.45 | 96.28 | 140.79 | 104.60 | 0.00 | 0.00 | 720.00 |
May | 151.56 | 42.38 | 109.18 | 127.90 | 52.50 | 0.00 | 0.00 | 744.00 |
June | 144.68 | 28.87 | 115.81 | 144.75 | 28.80 | 0.00 | 0.00 | 720.00 |
July | 153.54 | 38.38 | 115.16 | 159.92 | 20.63 | 0.00 | 0.00 | 744.00 |
August | 170.15 | 58.91 | 111.24 | 184.62 | 27.23 | 0.00 | 0.00 | 744.00 |
September | 205.49 | 106.05 | 99.44 | 216.38 | 58.49 | 0.00 | 0.00 | 720.00 |
October | 221.49 | 139.67 | 81.82 | 218.98 | 104.83 | 0.00 | 0.00 | 744.00 |
November | 165.71 | 103.74 | 61.96 | 140.92 | 164.56 | 0.00 | 0.00 | 720.00 |
December | 176.39 | 133.57 | 42.82 | 157.07 | 240.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.29 | 94.93 | 89.37 | 167.97 | 116.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 144.68 | 28.87 | 42.82 | 127.90 | 20.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 232.78 | 157.95 | 115.81 | 218.98 | 253.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 135.75 | 203.96 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 147.08 | 165.80 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 121.62 | 119.05 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 106.72 | 84.79 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 93.55 | 44.51 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 104.93 | 25.51 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 115.96 | 19.28 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 136.22 | 24.63 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 163.90 | 49.12 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 168.57 | 84.52 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 109.81 | 130.00 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 123.29 | 187.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 127.19 | 94.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 93.55 | 19.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 168.57 | 203.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 31.14 | 440.33 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 75.54 | 352.80 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 108.07 | 228.39 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 240.12 | 154.23 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 270.30 | 80.12 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 364.97 | 46.65 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 406.78 | 35.57 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 354.62 | 45.47 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 257.30 | 90.98 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 127.57 | 163.77 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 44.48 | 268.26 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 27.22 | 393.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 192.93 | 190.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 27.22 | 35.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 406.78 | 440.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.00 | 250.24 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.45 | 203.11 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 9.82 | 129.32 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 25.03 | 85.16 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 55.32 | 41.35 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 86.69 | 23.46 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 86.70 | 17.98 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 75.33 | 23.29 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 44.97 | 49.26 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 13.31 | 89.82 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 2.86 | 149.20 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 218.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 33.57 | 106.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 17.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 86.70 | 250.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 32.55 | 436.25 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 78.46 | 348.18 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 112.02 | 225.59 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 243.03 | 152.89 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 271.64 | 79.63 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 365.58 | 46.38 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 407.54 | 35.33 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 356.04 | 45.04 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 260.46 | 89.85 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 133.06 | 160.87 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 47.16 | 264.97 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 29.04 | 388.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 195.30 | 188.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 29.04 | 35.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 407.54 | 436.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.17 | 171.39 | 78.79 | 191.64 | 306.81 | 0.00 | 0.00 | 744.00 |
February | 269.80 | 183.06 | 86.74 | 209.01 | 250.19 | 0.00 | 0.00 | 672.00 |
March | 231.15 | 121.05 | 110.11 | 173.24 | 178.93 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 94.40 | 111.59 | 155.49 | 125.42 | 0.00 | 0.00 | 720.00 |
May | 175.66 | 49.12 | 126.54 | 138.18 | 64.75 | 0.00 | 0.00 | 744.00 |
June | 167.69 | 33.46 | 134.22 | 157.00 | 36.50 | 0.00 | 0.00 | 720.00 |
July | 177.95 | 44.48 | 133.47 | 173.78 | 26.89 | 0.00 | 0.00 | 744.00 |
August | 197.20 | 68.27 | 128.93 | 202.05 | 35.14 | 0.00 | 0.00 | 744.00 |
September | 238.17 | 122.92 | 115.25 | 239.63 | 72.51 | 0.00 | 0.00 | 720.00 |
October | 256.71 | 161.88 | 94.83 | 242.85 | 127.33 | 0.00 | 0.00 | 744.00 |
November | 192.05 | 120.24 | 71.82 | 156.05 | 197.05 | 0.00 | 0.00 | 720.00 |
December | 204.43 | 154.80 | 49.63 | 174.76 | 282.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.60 | 110.02 | 103.58 | 184.35 | 141.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 167.69 | 33.46 | 49.63 | 138.18 | 26.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 269.80 | 183.06 | 134.22 | 242.85 | 306.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1715.03 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 2.00 | 1322.42 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 65.03 | 933.85 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 190.32 | 607.29 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 425.85 | 289.77 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 664.36 | 158.38 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 673.11 | 112.10 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 586.23 | 152.86 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 347.78 | 341.41 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 92.82 | 644.95 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 18.11 | 1076.11 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1582.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 257.01 | 742.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 112.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 673.11 | 1715.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1729.77 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 1.74 | 1339.00 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 62.15 | 950.88 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 185.41 | 621.92 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 417.33 | 299.05 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 655.39 | 164.75 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 664.63 | 117.38 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 578.28 | 159.19 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 341.56 | 351.80 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 88.69 | 660.45 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 16.83 | 1093.67 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1601.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 252.51 | 754.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 117.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 664.63 | 1729.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.02 | 221.27 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.78 | 169.63 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 13.53 | 123.10 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 35.92 | 79.23 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 78.48 | 38.89 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 116.80 | 22.01 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 120.04 | 15.46 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 106.27 | 20.12 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 65.66 | 44.13 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 20.53 | 83.06 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 5.36 | 138.40 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 207.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 47.23 | 96.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 15.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 120.04 | 221.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 218.23 | 89.44 | 128.79 | 68.91 | 767.20 | 0.00 | 0.00 | 744.00 |
February | 290.57 | 127.90 | 162.68 | 136.98 | 575.96 | 0.00 | 0.00 | 672.00 |
March | 394.65 | 156.59 | 238.06 | 256.27 | 423.47 | 0.00 | 0.00 | 744.00 |
April | 481.67 | 209.93 | 271.73 | 439.60 | 285.77 | 0.00 | 0.00 | 720.00 |
May | 608.53 | 266.12 | 342.41 | 689.83 | 144.24 | 0.00 | 0.00 | 744.00 |
June | 668.73 | 291.27 | 377.46 | 859.34 | 83.52 | 0.00 | 0.00 | 720.00 |
July | 676.06 | 312.03 | 364.04 | 907.43 | 58.90 | 0.00 | 0.00 | 744.00 |
August | 570.03 | 245.65 | 324.38 | 774.71 | 76.00 | 0.00 | 0.00 | 744.00 |
September | 510.75 | 242.25 | 268.49 | 618.95 | 160.86 | 0.00 | 0.00 | 720.00 |
October | 323.41 | 134.61 | 188.80 | 263.28 | 293.44 | 0.00 | 0.00 | 744.00 |
November | 191.31 | 62.09 | 129.22 | 82.16 | 486.87 | 0.00 | 0.00 | 720.00 |
December | 147.64 | 63.22 | 84.42 | 40.23 | 731.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 424.12 | 183.68 | 240.44 | 429.75 | 339.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 147.64 | 62.09 | 84.42 | 40.23 | 58.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 676.06 | 312.03 | 377.46 | 907.43 | 767.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 146.47 | 182.77 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 161.84 | 142.47 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 130.00 | 113.48 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 119.50 | 78.81 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 116.07 | 41.06 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 133.85 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 148.45 | 16.17 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 166.62 | 20.90 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 186.73 | 43.94 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 182.60 | 79.09 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 117.98 | 121.49 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 128.84 | 178.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 144.83 | 86.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 116.07 | 16.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 186.73 | 182.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.63 | 0.00 | 34.63 | 0.00 | 314.95 | 0.00 | 0.00 | 744.00 |
February | 43.91 | 0.00 | 43.91 | 0.30 | 239.64 | 0.00 | 0.00 | 672.00 |
March | 65.82 | 0.00 | 65.82 | 11.62 | 168.07 | 0.00 | 0.00 | 744.00 |
April | 76.28 | 0.61 | 75.66 | 34.01 | 107.93 | 0.00 | 0.00 | 720.00 |
May | 99.17 | 3.75 | 95.42 | 76.94 | 50.73 | 0.00 | 0.00 | 744.00 |
June | 116.05 | 10.74 | 105.31 | 119.26 | 27.82 | 0.00 | 0.00 | 720.00 |
July | 108.85 | 7.49 | 101.35 | 120.24 | 20.36 | 0.00 | 0.00 | 744.00 |
August | 91.20 | 1.84 | 89.37 | 104.58 | 27.27 | 0.00 | 0.00 | 744.00 |
September | 69.80 | 0.06 | 69.74 | 61.74 | 60.80 | 0.00 | 0.00 | 720.00 |
October | 51.83 | 0.00 | 51.83 | 16.31 | 115.23 | 0.00 | 0.00 | 744.00 |
November | 36.26 | 0.00 | 36.26 | 3.18 | 194.78 | 0.00 | 0.00 | 720.00 |
December | 23.52 | 0.00 | 23.52 | 0.00 | 287.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.24 | 2.05 | 66.19 | 45.96 | 134.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 0.00 | 20.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.05 | 10.74 | 105.31 | 120.24 | 314.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.99 | 0.00 | 30.99 | 0.00 | 281.79 | 0.00 | 0.00 | 744.00 |
February | 39.29 | 0.00 | 39.29 | 0.26 | 214.41 | 0.00 | 0.00 | 672.00 |
March | 58.89 | 0.00 | 58.89 | 10.39 | 150.37 | 0.00 | 0.00 | 744.00 |
April | 68.24 | 0.55 | 67.70 | 30.43 | 96.57 | 0.00 | 0.00 | 720.00 |
May | 88.73 | 3.35 | 85.38 | 68.84 | 45.39 | 0.00 | 0.00 | 744.00 |
June | 103.83 | 9.61 | 94.22 | 106.70 | 24.89 | 0.00 | 0.00 | 720.00 |
July | 97.38 | 6.70 | 90.68 | 107.58 | 18.22 | 0.00 | 0.00 | 744.00 |
August | 81.60 | 1.64 | 79.96 | 93.57 | 24.40 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 0.06 | 62.39 | 55.24 | 54.40 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 0.00 | 46.37 | 14.59 | 103.10 | 0.00 | 0.00 | 744.00 |
November | 32.44 | 0.00 | 32.44 | 2.85 | 174.27 | 0.00 | 0.00 | 720.00 |
December | 21.04 | 0.00 | 21.04 | 0.00 | 257.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.05 | 1.83 | 59.22 | 41.12 | 120.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.00 | 18.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.83 | 9.61 | 94.22 | 107.58 | 281.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.83 | 436.27 | 200.55 | 512.82 | 748.82 | 0.00 | 0.00 | 744.00 |
February | 686.78 | 465.98 | 220.79 | 572.15 | 576.18 | 0.00 | 0.00 | 672.00 |
March | 588.42 | 308.13 | 280.29 | 456.52 | 448.84 | 0.00 | 0.00 | 744.00 |
April | 524.35 | 240.29 | 284.06 | 410.45 | 314.00 | 0.00 | 0.00 | 720.00 |
May | 447.15 | 125.03 | 322.12 | 370.84 | 159.06 | 0.00 | 0.00 | 744.00 |
June | 426.85 | 85.19 | 341.67 | 419.92 | 88.22 | 0.00 | 0.00 | 720.00 |
July | 452.98 | 113.22 | 339.75 | 464.33 | 63.65 | 0.00 | 0.00 | 744.00 |
August | 501.98 | 173.79 | 328.19 | 537.47 | 83.66 | 0.00 | 0.00 | 744.00 |
September | 606.27 | 312.89 | 293.38 | 631.79 | 176.34 | 0.00 | 0.00 | 720.00 |
October | 653.47 | 412.07 | 241.40 | 638.98 | 314.03 | 0.00 | 0.00 | 744.00 |
November | 488.88 | 306.07 | 182.81 | 410.56 | 491.02 | 0.00 | 0.00 | 720.00 |
December | 520.39 | 394.06 | 126.33 | 458.42 | 716.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.72 | 280.06 | 263.66 | 489.92 | 347.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 426.85 | 85.19 | 126.33 | 370.84 | 63.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 686.78 | 465.98 | 341.67 | 638.98 | 748.82 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.190712E+10 | 0.249022E+10 |
February | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.189672E+10 | 0.175559E+10 |
March | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.168185E+10 | 0.149870E+10 |
April | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.143264E+10 | 0.102143E+10 |
May | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.132892E+10 | 0.546167E+09 |
June | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.143374E+10 | 0.302669E+09 |
July | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.163672E+10 | 0.235993E+09 |
August | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.190421E+10 | 0.302307E+09 |
September | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.218289E+10 | 0.600696E+09 |
October | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.231782E+10 | 0.107404E+10 |
November | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.146510E+10 | 0.158148E+10 |
December | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.168785E+10 | 0.239142E+10 |
Annual Sum or Average | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.208756E+11 | 0.138007E+11 |
Minimum of Months | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.132892E+10 | 0.235993E+09 |
Maximum of Months | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.231782E+10 | 0.249022E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.535327E+10 | 0.702447E+10 |
February | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.532117E+10 | 0.496561E+10 |
March | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.470772E+10 | 0.422298E+10 |
April | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.401343E+10 | 0.287548E+10 |
May | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.371184E+10 | 0.152102E+10 |
June | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.401441E+10 | 0.832826E+09 |
July | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.458831E+10 | 0.638892E+09 |
August | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.534172E+10 | 0.829340E+09 |
September | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.613525E+10 | 0.167499E+10 |
October | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.650783E+10 | 0.301936E+10 |
November | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.410219E+10 | 0.445903E+10 |
December | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.473209E+10 | 0.675446E+10 |
Annual Sum or Average | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.585292E+11 | 0.388185E+11 |
Minimum of Months | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.371184E+10 | 0.638892E+09 |
Maximum of Months | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.650783E+10 | 0.702447E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.704549E+10 | 0.939279E+10 |
February | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.704896E+10 | 0.656385E+10 |
March | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.622211E+10 | 0.564061E+10 |
April | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.532145E+10 | 0.385130E+10 |
May | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.495103E+10 | 0.204723E+10 |
June | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.536445E+10 | 0.111941E+10 |
July | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.612948E+10 | 0.848797E+09 |
August | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.711145E+10 | 0.110252E+10 |
September | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.813276E+10 | 0.223364E+10 |
October | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.861275E+10 | 0.402400E+10 |
November | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.541178E+10 | 0.596411E+10 |
December | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.622961E+10 | 0.902583E+10 |
Annual Sum or Average | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.775813E+11 | 0.518141E+11 |
Minimum of Months | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.495103E+10 | 0.848797E+09 |
Maximum of Months | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.861275E+10 | 0.939279E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.365565E+09 | 0.543478E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.358421E+09 | 0.397620E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.326395E+09 | 0.318220E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.277832E+09 | 0.219090E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.253598E+09 | 0.117853E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.274989E+09 | 65172742.82 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.313941E+09 | 50751886.60 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.367966E+09 | 64804701.42 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.426863E+09 | 0.126676E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.453054E+09 | 0.226022E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.285368E+09 | 0.336302E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.330852E+09 | 0.501195E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.403484E+10 | 0.296718E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.253598E+09 | 50751886.60 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.453054E+09 | 0.543478E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 84079251.73 | 0.117134E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.184949E+09 | 0.843397E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.290719E+09 | 0.610395E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.626871E+09 | 0.398627E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.732009E+09 | 0.212523E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.954173E+09 | 0.119366E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109848E+10 | 93765030.06 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.958035E+09 | 0.119832E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.671689E+09 | 0.234636E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.343905E+09 | 0.438106E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.115288E+09 | 0.694624E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 72760461.58 | 0.105007E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.613296E+10 | 0.598668E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 72760461.58 | 93765030.06 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109848E+10 | 0.117134E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 2543.57 | 0.666091E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 1047961.25 | 0.485770E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 26054350.51 | 0.346106E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 66055314.67 | 0.220038E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.152054E+09 | 0.109590E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.228710E+09 | 59933385.65 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.236465E+09 | 47326994.23 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.205705E+09 | 61341725.61 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.118571E+09 | 0.127140E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 35429917.72 | 0.241111E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7251204.21 | 0.387258E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.583350E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.107735E+10 | 0.333506E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 47326994.23 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.236465E+09 | 0.666091E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 87862895.40 | 0.116008E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.191472E+09 | 0.831476E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.300720E+09 | 0.602948E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.634050E+09 | 0.395416E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.735727E+09 | 0.211282E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.955860E+09 | 0.118684E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.110070E+10 | 93091451.54 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.962134E+09 | 0.118706E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.679884E+09 | 0.231904E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.357104E+09 | 0.431271E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.121687E+09 | 0.686146E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 77521956.24 | 0.103787E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.620472E+10 | 0.591888E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 77521956.24 | 93091451.54 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.110070E+10 | 0.116008E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.287815E+09 | 0.433810E+09 |
February | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.280329E+09 | 0.332711E+09 |
March | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.253090E+09 | 0.270178E+09 |
April | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.216685E+09 | 0.196798E+09 |
May | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.193896E+09 | 0.113240E+09 |
June | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.212391E+09 | 67472955.34 |
July | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.244211E+09 | 54513442.32 |
August | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.287184E+09 | 68050870.34 |
September | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.333752E+09 | 0.122453E+09 |
October | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.351108E+09 | 0.208484E+09 |
November | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.220520E+09 | 0.289489E+09 |
December | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.259766E+09 | 0.406191E+09 |
Annual Sum or Average | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.314075E+10 | 0.256339E+10 |
Minimum of Months | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.193896E+09 | 54513442.32 |
Maximum of Months | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.351108E+09 | 0.433810E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.553154E+09 |
February | 67056690.67 | 0.00 | 67056690.67 | 530290.49 | 0.405531E+09 |
March | 0.111280E+09 | 941.15 | 0.111279E+09 | 19236814.09 | 0.287493E+09 |
April | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 54391958.99 | 0.180499E+09 |
May | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.125873E+09 | 88298392.00 |
June | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.189925E+09 | 47602997.43 |
July | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.197935E+09 | 36342113.89 |
August | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.172326E+09 | 47992522.81 |
September | 0.114208E+09 | 102488.46 | 0.114105E+09 | 98579286.18 | 0.102617E+09 |
October | 87633982.09 | 0.00 | 87633982.09 | 27030823.64 | 0.198643E+09 |
November | 59323427.52 | 0.00 | 59323427.52 | 5062510.23 | 0.324520E+09 |
December | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.486298E+09 |
Annual Sum or Average | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.890891E+09 | 0.275899E+10 |
Minimum of Months | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 36342113.89 |
Maximum of Months | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.197935E+09 | 0.553154E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 69385923.39 | 0.115396E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.137007E+09 | 0.826069E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.301578E+09 | 0.594469E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.501944E+09 | 0.387662E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.801933E+09 | 0.199552E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.969844E+09 | 0.112432E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105072E+10 | 87335778.70 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.882183E+09 | 0.111531E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.686219E+09 | 0.227105E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.289527E+09 | 0.422338E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 81370951.19 | 0.682128E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 46733664.84 | 0.103808E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.581844E+10 | 0.584266E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 46733664.84 | 87335778.70 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105072E+10 | 0.115396E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.364961E+09 | 0.542995E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.357693E+09 | 0.395964E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.323902E+09 | 0.317616E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.276587E+09 | 0.217100E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.250154E+09 | 0.117785E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.272725E+09 | 64687899.25 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.312210E+09 | 49603966.66 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.366768E+09 | 63855429.24 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.424448E+09 | 0.125905E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.451593E+09 | 0.225089E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.285069E+09 | 0.335650E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.330672E+09 | 0.500678E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.401678E+10 | 0.295693E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.250154E+09 | 49603966.66 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.451593E+09 | 0.542995E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 197.88 | 0.666003E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 836362.10 | 0.484271E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 24941217.55 | 0.346907E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 65196433.18 | 0.218334E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.148557E+09 | 0.109748E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.226425E+09 | 59456047.49 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.234693E+09 | 46180127.57 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.204445E+09 | 60495140.75 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.116102E+09 | 0.126893E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 34424929.46 | 0.240513E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7060433.96 | 0.386685E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.583340E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.106268E+10 | 0.332883E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 46180127.57 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.234693E+09 | 0.666003E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 70995518.81 | 0.114061E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.140330E+09 | 0.810560E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.309372E+09 | 0.584984E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.508669E+09 | 0.383784E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.805190E+09 | 0.198352E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.971590E+09 | 0.111898E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105289E+10 | 86767048.75 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.885912E+09 | 0.110444E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.693394E+09 | 0.224279E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.301180E+09 | 0.413964E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 85392200.17 | 0.671278E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 47944592.23 | 0.102288E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.587286E+10 | 0.575980E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 47944592.23 | 86767048.75 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105289E+10 | 0.114061E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92689285.68 | 0.00 | 92689285.68 | 0.00 | 0.841882E+09 |
February | 0.106140E+09 | 0.00 | 0.106140E+09 | 997422.04 | 0.586957E+09 |
March | 0.176138E+09 | 1489.68 | 0.176137E+09 | 33305827.93 | 0.443521E+09 |
April | 0.197544E+09 | 1584139.79 | 0.195960E+09 | 91926646.45 | 0.274845E+09 |
May | 0.265400E+09 | 10027981.57 | 0.255372E+09 | 0.212324E+09 | 0.132601E+09 |
June | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.315874E+09 | 69623001.15 |
July | 0.291293E+09 | 20051601.33 | 0.271241E+09 | 0.329041E+09 | 52355538.02 |
August | 0.244082E+09 | 4919085.54 | 0.239163E+09 | 0.286724E+09 | 70389361.84 |
September | 0.180773E+09 | 162222.46 | 0.180610E+09 | 0.165057E+09 | 0.154441E+09 |
October | 0.138710E+09 | 0.00 | 0.138710E+09 | 46985525.55 | 0.303704E+09 |
November | 93899275.44 | 0.00 | 93899275.44 | 9156406.18 | 0.499117E+09 |
December | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 0.760105E+09 |
Annual Sum or Average | 0.215016E+10 | 64566489.21 | 0.208559E+10 | 0.149139E+10 | 0.418954E+10 |
Minimum of Months | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 52355538.02 |
Maximum of Months | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.329041E+09 | 0.841882E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34169108.66 | 0.00 | 34169108.66 | 0.00 | 0.310353E+09 |
February | 39127512.35 | 0.00 | 39127512.35 | 367691.06 | 0.216377E+09 |
March | 64931807.30 | 549.16 | 64931258.14 | 12277907.26 | 0.163500E+09 |
April | 72822870.96 | 583979.52 | 72238891.44 | 33887968.26 | 0.101319E+09 |
May | 97837340.20 | 3696729.23 | 94140610.97 | 78271450.44 | 48882260.81 |
June | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.116444E+09 | 25665921.09 |
July | 0.107383E+09 | 7391850.52 | 99990758.17 | 0.121298E+09 | 19300419.19 |
August | 89978876.20 | 1813378.61 | 88165497.59 | 0.105698E+09 | 25948433.37 |
September | 66640246.57 | 59801.92 | 66580444.66 | 60846921.28 | 56933531.59 |
October | 51134341.44 | 0.00 | 51134341.44 | 17320810.24 | 0.111958E+09 |
November | 34615160.99 | 0.00 | 34615160.99 | 3375430.45 | 0.183995E+09 |
December | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 0.280206E+09 |
Annual Sum or Average | 0.792636E+09 | 23801881.41 | 0.768834E+09 | 0.549789E+09 | 0.154444E+10 |
Minimum of Months | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 19300419.19 |
Maximum of Months | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.121298E+09 | 0.310353E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213005E+09 | 0.145924E+09 | 67080677.26 | 0.172576E+09 | 0.250183E+09 |
February | 0.207482E+09 | 0.140778E+09 | 66703954.00 | 0.173094E+09 | 0.176033E+09 |
March | 0.196812E+09 | 0.103063E+09 | 93749766.36 | 0.154696E+09 | 0.148208E+09 |
April | 0.169726E+09 | 77778998.96 | 91946673.79 | 0.134453E+09 | 99889330.60 |
May | 0.149563E+09 | 41821325.16 | 0.107741E+09 | 0.126213E+09 | 51808795.03 |
June | 0.138167E+09 | 27573501.09 | 0.110594E+09 | 0.138234E+09 | 27503235.77 |
July | 0.151510E+09 | 37870946.71 | 0.113640E+09 | 0.157809E+09 | 20359468.82 |
August | 0.167901E+09 | 58128357.07 | 0.109773E+09 | 0.182187E+09 | 26866477.97 |
September | 0.196242E+09 | 0.101279E+09 | 94962720.04 | 0.206641E+09 | 55860754.39 |
October | 0.218572E+09 | 0.137830E+09 | 80742463.40 | 0.216094E+09 | 0.103444E+09 |
November | 0.158245E+09 | 99071298.74 | 59174088.99 | 0.134579E+09 | 0.157148E+09 |
December | 0.174060E+09 | 0.131804E+09 | 42256009.05 | 0.155000E+09 | 0.237024E+09 |
Annual Sum or Average | 0.214129E+10 | 0.110292E+10 | 0.103836E+10 | 0.195158E+10 | 0.135433E+10 |
Minimum of Months | 0.138167E+09 | 27573501.09 | 42256009.05 | 0.126213E+09 | 20359468.82 |
Maximum of Months | 0.218572E+09 | 0.145924E+09 | 0.113640E+09 | 0.216094E+09 | 0.250183E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578139E+09 | 0.396068E+09 | 0.182071E+09 | 0.468408E+09 | 0.679047E+09 |
February | 0.563149E+09 | 0.382101E+09 | 0.181048E+09 | 0.469813E+09 | 0.477790E+09 |
March | 0.534189E+09 | 0.279733E+09 | 0.254456E+09 | 0.419877E+09 | 0.402267E+09 |
April | 0.460670E+09 | 0.211108E+09 | 0.249562E+09 | 0.364932E+09 | 0.271120E+09 |
May | 0.405943E+09 | 0.113512E+09 | 0.292432E+09 | 0.342569E+09 | 0.140620E+09 |
June | 0.375014E+09 | 74840121.99 | 0.300174E+09 | 0.375195E+09 | 74649407.55 |
July | 0.411230E+09 | 0.102789E+09 | 0.308441E+09 | 0.428326E+09 | 55259762.83 |
August | 0.455718E+09 | 0.157772E+09 | 0.297946E+09 | 0.494493E+09 | 72921116.63 |
September | 0.532641E+09 | 0.274893E+09 | 0.257748E+09 | 0.560867E+09 | 0.151618E+09 |
October | 0.593250E+09 | 0.374098E+09 | 0.219152E+09 | 0.586524E+09 | 0.280767E+09 |
November | 0.429510E+09 | 0.268900E+09 | 0.160611E+09 | 0.365274E+09 | 0.426532E+09 |
December | 0.472435E+09 | 0.357743E+09 | 0.114691E+09 | 0.420702E+09 | 0.643333E+09 |
Annual Sum or Average | 0.581189E+10 | 0.299356E+10 | 0.281833E+10 | 0.529698E+10 | 0.367592E+10 |
Minimum of Months | 0.375014E+09 | 74840121.99 | 0.114691E+09 | 0.342569E+09 | 55259762.83 |
Maximum of Months | 0.593250E+09 | 0.396068E+09 | 0.308441E+09 | 0.586524E+09 | 0.679047E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.363602E+09 | 0.546286E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.355826E+09 | 0.401114E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.325750E+09 | 0.318867E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.276628E+09 | 0.219788E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.250570E+09 | 0.119205E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.271977E+09 | 66117357.41 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.310593E+09 | 51630245.49 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.364855E+09 | 65968640.65 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.424839E+09 | 0.127327E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.451505E+09 | 0.226384E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.284637E+09 | 0.336949E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.330223E+09 | 0.502188E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.401100E+10 | 0.298183E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.250570E+09 | 51630245.49 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.451505E+09 | 0.546286E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 83404839.75 | 0.117938E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.182754E+09 | 0.853498E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.289453E+09 | 0.611712E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.622401E+09 | 0.399769E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.723962E+09 | 0.214580E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.946002E+09 | 0.120914E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108951E+10 | 95273507.28 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.949826E+09 | 0.121774E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.666910E+09 | 0.235820E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.341675E+09 | 0.438636E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.115300E+09 | 0.695335E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 72902394.25 | 0.105280E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.608410E+10 | 0.601949E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 72902394.25 | 95273507.28 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108951E+10 | 0.117938E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 11404.11 | 0.670235E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1098361.69 | 0.491358E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 26292819.84 | 0.346383E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 64881948.59 | 0.220739E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.148179E+09 | 0.110748E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.224712E+09 | 60819279.70 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.232209E+09 | 48144701.27 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.201769E+09 | 62384591.92 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.116574E+09 | 0.127671E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 35646612.83 | 0.240574E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 7418993.22 | 0.386730E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.584472E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.105879E+10 | 0.335026E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 48144701.27 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.232209E+09 | 0.670235E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 87194276.16 | 0.116844E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.189807E+09 | 0.842314E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.300038E+09 | 0.604215E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.629945E+09 | 0.396280E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.727555E+09 | 0.213287E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.947574E+09 | 0.120224E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109155E+10 | 94616474.31 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.953630E+09 | 0.120647E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.675123E+09 | 0.232895E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.356396E+09 | 0.430872E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.122226E+09 | 0.686794E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 77787518.53 | 0.104127E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.615882E+10 | 0.595185E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 77787518.53 | 94616474.31 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109155E+10 | 0.116844E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.513290E+09 | 0.821756E+09 |
February | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.505645E+09 | 0.605252E+09 |
March | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.463998E+09 | 0.479248E+09 |
April | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.403038E+09 | 0.325086E+09 |
May | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.370108E+09 | 0.173417E+09 |
June | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.406956E+09 | 94614841.59 |
July | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.465463E+09 | 72031009.95 |
August | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.541160E+09 | 94131139.84 |
September | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.621129E+09 | 0.187956E+09 |
October | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.650436E+09 | 0.341031E+09 |
November | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.404482E+09 | 0.510753E+09 |
December | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.468088E+09 | 0.757290E+09 |
Annual Sum or Average | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.581379E+10 | 0.446257E+10 |
Minimum of Months | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.370108E+09 | 72031009.95 |
Maximum of Months | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.650436E+09 | 0.821756E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.459355E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 4842533.83 | 0.319921E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.174164E+09 | 0.250123E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.493301E+09 | 0.157411E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.114061E+10 | 0.776109E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.172203E+10 | 0.410523E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.180285E+10 | 0.300248E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.157015E+10 | 0.409414E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.901437E+09 | 0.884945E+09 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.248597E+09 | 0.172742E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 46949053.80 | 0.278929E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.423871E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.810493E+10 | 0.234047E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.300248E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.180285E+10 | 0.459355E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.463301E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 4205703.77 | 0.323930E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.166467E+09 | 0.254685E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.480585E+09 | 0.161202E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.111777E+10 | 0.800984E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.169876E+10 | 0.427035E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.178014E+10 | 0.314381E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.154886E+10 | 0.426383E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.885314E+09 | 0.911877E+09 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.237536E+09 | 0.176896E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 43617587.66 | 0.283479E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.428874E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.796325E+10 | 0.238043E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.314381E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.178014E+10 | 0.463301E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 46715.72 | 0.592638E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1890953.71 | 0.410377E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 36229926.55 | 0.329719E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 93114917.55 | 0.205354E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.210205E+09 | 0.104167E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.302753E+09 | 57055945.73 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.321528E+09 | 41414267.38 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.284623E+09 | 53902671.00 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.170198E+09 | 0.114377E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 54993399.26 | 0.222462E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 13900830.00 | 0.358737E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 5437.14 | 0.556625E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.148949E+10 | 0.304683E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 5437.14 | 41414267.38 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.321528E+09 | 0.592638E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.584511E+09 | 0.239563E+09 | 0.344948E+09 | 0.184570E+09 | 0.205486E+10 |
February | 0.702953E+09 | 0.309404E+09 | 0.393549E+09 | 0.331391E+09 | 0.139336E+10 |
March | 0.105704E+10 | 0.419414E+09 | 0.637627E+09 | 0.686392E+09 | 0.113423E+10 |
April | 0.124848E+10 | 0.544148E+09 | 0.704333E+09 | 0.113944E+10 | 0.740721E+09 |
May | 0.162988E+10 | 0.712773E+09 | 0.917103E+09 | 0.184764E+10 | 0.386330E+09 |
June | 0.173334E+10 | 0.754970E+09 | 0.978368E+09 | 0.222740E+10 | 0.216493E+09 |
July | 0.181076E+10 | 0.835731E+09 | 0.975034E+09 | 0.243045E+10 | 0.157755E+09 |
August | 0.152676E+10 | 0.657939E+09 | 0.868824E+09 | 0.207499E+10 | 0.203561E+09 |
September | 0.132385E+10 | 0.627922E+09 | 0.695933E+09 | 0.160431E+10 | 0.416951E+09 |
October | 0.866230E+09 | 0.360550E+09 | 0.505680E+09 | 0.705172E+09 | 0.785953E+09 |
November | 0.495872E+09 | 0.160945E+09 | 0.334927E+09 | 0.212964E+09 | 0.126196E+10 |
December | 0.395447E+09 | 0.169327E+09 | 0.226119E+09 | 0.107741E+09 | 0.195863E+10 |
Annual Sum or Average | 0.133751E+11 | 0.579269E+10 | 0.758245E+10 | 0.135525E+11 | 0.107108E+11 |
Minimum of Months | 0.395447E+09 | 0.160945E+09 | 0.226119E+09 | 0.107741E+09 | 0.157755E+09 |
Maximum of Months | 0.181076E+10 | 0.835731E+09 | 0.978368E+09 | 0.243045E+10 | 0.205486E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.392316E+09 | 0.489532E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.391518E+09 | 0.344654E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.348189E+09 | 0.303948E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.309752E+09 | 0.204278E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.310885E+09 | 0.109972E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.346943E+09 | 60598116.92 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.397603E+09 | 43322577.98 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.446281E+09 | 55968385.07 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.484007E+09 | 0.113881E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.489079E+09 | 0.211835E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.305802E+09 | 0.314890E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.345094E+09 | 0.477760E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.456747E+10 | 0.273064E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.305802E+09 | 43322577.98 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.489079E+09 | 0.489532E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92765322.83 | 0.00 | 92765322.83 | 0.00 | 0.843573E+09 |
February | 0.106227E+09 | 0.00 | 0.106227E+09 | 715509.64 | 0.579744E+09 |
March | 0.176283E+09 | 1490.90 | 0.176281E+09 | 31111938.74 | 0.450149E+09 |
April | 0.197706E+09 | 1585439.33 | 0.196121E+09 | 88157734.25 | 0.279761E+09 |
May | 0.265617E+09 | 10036207.97 | 0.255581E+09 | 0.206084E+09 | 0.135868E+09 |
June | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.309125E+09 | 72109677.98 |
July | 0.291532E+09 | 20068050.55 | 0.271464E+09 | 0.322043E+09 | 54531252.92 |
August | 0.244283E+09 | 4923120.89 | 0.239360E+09 | 0.280120E+09 | 73046289.71 |
September | 0.180921E+09 | 162355.54 | 0.180758E+09 | 0.160038E+09 | 0.157600E+09 |
October | 0.138824E+09 | 0.00 | 0.138824E+09 | 43689439.32 | 0.308640E+09 |
November | 93976305.19 | 0.00 | 93976305.19 | 8244473.95 | 0.504871E+09 |
December | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 0.770015E+09 |
Annual Sum or Average | 0.215192E+10 | 64619455.98 | 0.208730E+10 | 0.144933E+10 | 0.422991E+10 |
Minimum of Months | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 54531252.92 |
Maximum of Months | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.322043E+09 | 0.843573E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82997485.82 | 0.00 | 82997485.82 | 0.00 | 0.754736E+09 |
February | 95041552.99 | 0.00 | 95041552.99 | 640169.19 | 0.518698E+09 |
March | 0.157721E+09 | 1333.91 | 0.157719E+09 | 27835969.47 | 0.402750E+09 |
April | 0.176888E+09 | 1418498.57 | 0.175470E+09 | 78875058.86 | 0.250303E+09 |
May | 0.237649E+09 | 8979433.30 | 0.228670E+09 | 0.184384E+09 | 0.121562E+09 |
June | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.276575E+09 | 64516802.11 |
July | 0.260835E+09 | 17954960.87 | 0.242880E+09 | 0.288133E+09 | 48789318.61 |
August | 0.218561E+09 | 4404734.91 | 0.214156E+09 | 0.250624E+09 | 65354792.17 |
September | 0.161871E+09 | 145260.12 | 0.161725E+09 | 0.143186E+09 | 0.141006E+09 |
October | 0.124206E+09 | 0.00 | 0.124206E+09 | 39089106.90 | 0.276141E+09 |
November | 84080956.33 | 0.00 | 84080956.33 | 7376362.08 | 0.451710E+09 |
December | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 0.688918E+09 |
Annual Sum or Average | 0.192533E+10 | 57815272.11 | 0.186752E+10 | 0.129672E+10 | 0.378448E+10 |
Minimum of Months | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 48789318.61 |
Maximum of Months | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.288133E+09 | 0.754736E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170568E+10 | 0.116852E+10 | 0.537162E+09 | 0.137355E+10 | 0.200564E+10 |
February | 0.166146E+10 | 0.112731E+10 | 0.534145E+09 | 0.138416E+10 | 0.139390E+10 |
March | 0.157601E+10 | 0.825294E+09 | 0.750720E+09 | 0.122273E+10 | 0.120217E+10 |
April | 0.135911E+10 | 0.622831E+09 | 0.736281E+09 | 0.106388E+10 | 0.813901E+09 |
May | 0.119765E+10 | 0.334893E+09 | 0.862759E+09 | 0.993251E+09 | 0.426031E+09 |
June | 0.110640E+10 | 0.220800E+09 | 0.885601E+09 | 0.108844E+10 | 0.228670E+09 |
July | 0.121325E+10 | 0.303259E+09 | 0.909991E+09 | 0.124367E+10 | 0.170492E+09 |
August | 0.134450E+10 | 0.465474E+09 | 0.879028E+09 | 0.143957E+10 | 0.224066E+09 |
September | 0.157145E+10 | 0.811014E+09 | 0.760433E+09 | 0.163759E+10 | 0.457062E+09 |
October | 0.175026E+10 | 0.110370E+10 | 0.646561E+09 | 0.171145E+10 | 0.841095E+09 |
November | 0.126718E+10 | 0.793333E+09 | 0.473848E+09 | 0.106417E+10 | 0.127272E+10 |
December | 0.139382E+10 | 0.105545E+10 | 0.338373E+09 | 0.122782E+10 | 0.191822E+10 |
Annual Sum or Average | 0.171468E+11 | 0.883188E+10 | 0.831490E+10 | 0.154503E+11 | 0.109540E+11 |
Minimum of Months | 0.110640E+10 | 0.220800E+09 | 0.338373E+09 | 0.993251E+09 | 0.170492E+09 |
Maximum of Months | 0.175026E+10 | 0.116852E+10 | 0.909991E+09 | 0.171145E+10 | 0.200564E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 712.04 | 929.74 | 863.80 | 591.77 | 272.03 | 0.00 | 0.00 |
February | 784.03 | 725.69 | 931.56 | 632.07 | 299.49 | 0.00 | 0.00 |
March | 627.93 | 559.55 | 798.14 | 417.95 | 380.19 | 0.00 | 0.00 |
April | 552.71 | 394.07 | 711.24 | 325.93 | 385.30 | 0.00 | 0.00 |
May | 496.16 | 203.92 | 606.52 | 169.60 | 436.93 | 0.00 | 0.00 |
June | 553.14 | 116.77 | 578.99 | 115.55 | 463.44 | 0.00 | 0.00 |
July | 611.08 | 88.11 | 614.42 | 153.58 | 460.84 | 0.00 | 0.00 |
August | 710.95 | 112.87 | 680.89 | 235.73 | 445.16 | 0.00 | 0.00 |
September | 842.17 | 231.75 | 822.35 | 424.41 | 397.94 | 0.00 | 0.00 |
October | 865.38 | 401.00 | 886.38 | 558.94 | 327.44 | 0.00 | 0.00 |
November | 565.24 | 610.14 | 663.13 | 415.16 | 247.97 | 0.00 | 0.00 |
December | 630.17 | 892.85 | 705.87 | 534.51 | 171.36 | 0.00 | 0.00 |
Annual Sum or Average | 661.96 | 437.62 | 737.51 | 379.87 | 357.64 | 0.00 | 0.00 |
Minimum of Months | 496.16 | 88.11 | 578.99 | 115.55 | 171.36 | 0.00 | 0.00 |
Maximum of Months | 865.38 | 929.74 | 931.56 | 632.07 | 463.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1998.68 | 2622.64 | 2432.41 | 1666.38 | 766.03 | 0.00 | 0.00 |
February | 2199.56 | 2052.58 | 2623.21 | 1779.87 | 843.34 | 0.00 | 0.00 |
March | 1757.66 | 1576.68 | 2247.50 | 1176.92 | 1070.58 | 0.00 | 0.00 |
April | 1548.39 | 1109.37 | 2002.79 | 917.81 | 1084.99 | 0.00 | 0.00 |
May | 1385.84 | 567.88 | 1707.93 | 477.58 | 1230.35 | 0.00 | 0.00 |
June | 1548.77 | 321.31 | 1630.40 | 325.37 | 1305.02 | 0.00 | 0.00 |
July | 1713.08 | 238.54 | 1730.18 | 432.47 | 1297.71 | 0.00 | 0.00 |
August | 1994.37 | 309.64 | 1917.35 | 663.80 | 1253.55 | 0.00 | 0.00 |
September | 2367.00 | 646.22 | 2315.69 | 1195.11 | 1120.58 | 0.00 | 0.00 |
October | 2429.75 | 1127.30 | 2495.99 | 1573.95 | 922.04 | 0.00 | 0.00 |
November | 1582.63 | 1720.31 | 1867.32 | 1169.06 | 698.26 | 0.00 | 0.00 |
December | 1766.76 | 2521.83 | 1987.68 | 1505.14 | 482.54 | 0.00 | 0.00 |
Annual Sum or Average | 1855.95 | 1230.93 | 2076.78 | 1069.70 | 1007.08 | 0.00 | 0.00 |
Minimum of Months | 1385.84 | 238.54 | 1630.40 | 325.37 | 482.54 | 0.00 | 0.00 |
Maximum of Months | 2429.75 | 2622.64 | 2623.21 | 1779.87 | 1305.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2630.49 | 3506.87 | 3159.84 | 2164.73 | 995.12 | 0.00 | 0.00 |
February | 2913.76 | 2713.23 | 3407.69 | 2312.15 | 1095.55 | 0.00 | 0.00 |
March | 2323.07 | 2105.96 | 2919.63 | 1528.89 | 1390.74 | 0.00 | 0.00 |
April | 2053.03 | 1485.84 | 2601.74 | 1192.28 | 1409.46 | 0.00 | 0.00 |
May | 1848.50 | 764.35 | 2218.70 | 620.40 | 1598.30 | 0.00 | 0.00 |
June | 2069.62 | 431.87 | 2117.98 | 422.68 | 1695.30 | 0.00 | 0.00 |
July | 2288.49 | 316.90 | 2247.60 | 561.80 | 1685.80 | 0.00 | 0.00 |
August | 2655.11 | 411.63 | 2490.75 | 862.31 | 1628.44 | 0.00 | 0.00 |
September | 3137.64 | 861.74 | 3008.21 | 1552.52 | 1455.69 | 0.00 | 0.00 |
October | 3215.63 | 1502.39 | 3242.43 | 2044.65 | 1197.78 | 0.00 | 0.00 |
November | 2087.88 | 2300.97 | 2425.76 | 1518.67 | 907.08 | 0.00 | 0.00 |
December | 2325.87 | 3369.86 | 2582.11 | 1955.26 | 626.85 | 0.00 | 0.00 |
Annual Sum or Average | 2460.09 | 1643.01 | 2697.86 | 1389.60 | 1308.26 | 0.00 | 0.00 |
Minimum of Months | 1848.50 | 316.90 | 2117.98 | 422.68 | 626.85 | 0.00 | 0.00 |
Maximum of Months | 3215.63 | 3506.87 | 3407.69 | 2312.15 | 1695.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.21 | 598.57 | 279.39 | 161.07 | 118.31 | 0.00 | 0.00 |
February | 192.41 | 480.79 | 342.80 | 202.99 | 139.81 | 0.00 | 0.00 |
March | 220.15 | 336.45 | 347.24 | 153.05 | 194.19 | 0.00 | 0.00 |
April | 345.29 | 234.57 | 417.83 | 201.64 | 216.19 | 0.00 | 0.00 |
May | 366.78 | 122.14 | 397.69 | 144.76 | 252.93 | 0.00 | 0.00 |
June | 473.83 | 70.81 | 439.45 | 163.38 | 276.06 | 0.00 | 0.00 |
July | 527.17 | 53.79 | 470.54 | 195.99 | 274.54 | 0.00 | 0.00 |
August | 494.80 | 68.66 | 439.37 | 186.08 | 253.29 | 0.00 | 0.00 |
September | 422.58 | 138.15 | 409.80 | 201.05 | 208.75 | 0.00 | 0.00 |
October | 292.36 | 242.77 | 348.40 | 187.80 | 160.60 | 0.00 | 0.00 |
November | 139.49 | 382.65 | 234.37 | 120.36 | 114.01 | 0.00 | 0.00 |
December | 123.10 | 551.58 | 218.97 | 143.18 | 75.79 | 0.00 | 0.00 |
Annual Sum or Average | 310.93 | 272.44 | 362.17 | 171.53 | 190.64 | 0.00 | 0.00 |
Minimum of Months | 123.10 | 53.79 | 218.97 | 120.36 | 75.79 | 0.00 | 0.00 |
Maximum of Months | 527.17 | 598.57 | 470.54 | 202.99 | 276.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.39 | 671.40 | 136.27 | 44.31 | 91.96 | 0.00 | 0.00 |
February | 65.73 | 530.65 | 193.64 | 78.28 | 115.36 | 0.00 | 0.00 |
March | 114.80 | 347.13 | 241.68 | 70.58 | 171.10 | 0.00 | 0.00 |
April | 266.70 | 234.04 | 337.68 | 137.81 | 199.86 | 0.00 | 0.00 |
May | 330.89 | 119.23 | 356.26 | 114.25 | 242.00 | 0.00 | 0.00 |
June | 455.95 | 67.85 | 416.76 | 149.06 | 267.70 | 0.00 | 0.00 |
July | 498.66 | 51.85 | 435.18 | 171.60 | 263.58 | 0.00 | 0.00 |
August | 435.85 | 67.05 | 376.98 | 141.02 | 235.96 | 0.00 | 0.00 |
September | 306.94 | 137.41 | 302.60 | 117.36 | 185.25 | 0.00 | 0.00 |
October | 143.10 | 247.58 | 214.39 | 77.51 | 136.88 | 0.00 | 0.00 |
November | 44.47 | 408.85 | 132.13 | 38.44 | 93.69 | 0.00 | 0.00 |
December | 21.55 | 597.90 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Annual Sum or Average | 226.43 | 288.96 | 270.48 | 98.19 | 172.30 | 0.00 | 0.00 |
Minimum of Months | 21.55 | 51.85 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Maximum of Months | 498.66 | 671.40 | 435.18 | 171.60 | 267.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.46 | 161.97 | 136.33 | 93.39 | 42.93 | 0.00 | 0.00 |
February | 115.88 | 137.53 | 147.02 | 99.75 | 47.27 | 0.00 | 0.00 |
March | 94.49 | 100.87 | 125.96 | 65.96 | 60.00 | 0.00 | 0.00 |
April | 83.60 | 75.93 | 112.25 | 51.44 | 60.81 | 0.00 | 0.00 |
May | 72.39 | 42.28 | 95.72 | 26.77 | 68.96 | 0.00 | 0.00 |
June | 81.94 | 26.03 | 91.38 | 18.24 | 73.14 | 0.00 | 0.00 |
July | 91.18 | 20.35 | 96.97 | 24.24 | 72.73 | 0.00 | 0.00 |
August | 107.22 | 25.41 | 107.46 | 37.20 | 70.26 | 0.00 | 0.00 |
September | 128.76 | 47.24 | 129.78 | 66.98 | 62.80 | 0.00 | 0.00 |
October | 131.09 | 77.84 | 139.89 | 88.21 | 51.68 | 0.00 | 0.00 |
November | 85.08 | 111.69 | 104.65 | 65.52 | 39.13 | 0.00 | 0.00 |
December | 96.99 | 151.65 | 111.40 | 84.36 | 27.04 | 0.00 | 0.00 |
Annual Sum or Average | 99.59 | 81.28 | 116.39 | 59.95 | 56.44 | 0.00 | 0.00 |
Minimum of Months | 72.39 | 20.35 | 91.38 | 18.24 | 27.04 | 0.00 | 0.00 |
Maximum of Months | 131.09 | 161.97 | 147.02 | 99.75 | 73.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 206.52 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
February | 0.22 | 167.63 | 27.72 | 0.00 | 27.72 | 0.00 | 0.00 |
March | 7.18 | 107.34 | 41.55 | 0.00 | 41.55 | 0.00 | 0.00 |
April | 20.98 | 69.64 | 48.15 | 0.39 | 47.76 | 0.00 | 0.00 |
May | 47.00 | 32.97 | 62.60 | 2.37 | 60.24 | 0.00 | 0.00 |
June | 73.27 | 18.37 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
July | 73.90 | 13.57 | 68.71 | 4.73 | 63.98 | 0.00 | 0.00 |
August | 64.34 | 17.92 | 57.57 | 1.16 | 56.41 | 0.00 | 0.00 |
September | 38.03 | 39.59 | 44.06 | 0.04 | 44.02 | 0.00 | 0.00 |
October | 10.09 | 74.16 | 32.72 | 0.00 | 32.72 | 0.00 | 0.00 |
November | 1.95 | 125.20 | 22.89 | 0.00 | 22.89 | 0.00 | 0.00 |
December | 0.00 | 181.56 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Annual Sum or Average | 28.25 | 87.49 | 43.08 | 1.29 | 41.78 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 13.57 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Maximum of Months | 73.90 | 206.52 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.67 | 596.08 | 279.47 | 161.45 | 118.02 | 0.00 | 0.00 |
February | 173.02 | 473.67 | 328.99 | 188.62 | 140.37 | 0.00 | 0.00 |
March | 224.68 | 331.69 | 354.66 | 160.70 | 193.96 | 0.00 | 0.00 |
April | 296.27 | 229.23 | 380.99 | 169.20 | 211.79 | 0.00 | 0.00 |
May | 389.37 | 115.04 | 423.71 | 166.42 | 257.29 | 0.00 | 0.00 |
June | 477.75 | 66.70 | 448.36 | 168.32 | 280.03 | 0.00 | 0.00 |
July | 507.84 | 50.11 | 459.01 | 186.20 | 272.81 | 0.00 | 0.00 |
August | 464.90 | 64.08 | 419.15 | 169.24 | 249.91 | 0.00 | 0.00 |
September | 426.59 | 134.28 | 417.44 | 204.78 | 212.67 | 0.00 | 0.00 |
October | 272.80 | 237.82 | 336.48 | 177.54 | 158.94 | 0.00 | 0.00 |
November | 126.76 | 378.05 | 226.43 | 112.94 | 113.49 | 0.00 | 0.00 |
December | 112.75 | 546.35 | 213.04 | 137.05 | 75.99 | 0.00 | 0.00 |
Annual Sum or Average | 300.47 | 267.63 | 357.42 | 166.73 | 190.70 | 0.00 | 0.00 |
Minimum of Months | 112.75 | 50.11 | 213.04 | 112.94 | 75.99 | 0.00 | 0.00 |
Maximum of Months | 507.84 | 596.08 | 459.01 | 204.78 | 280.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.62 | 662.63 | 136.36 | 44.69 | 91.67 | 0.00 | 0.00 |
February | 43.97 | 520.85 | 179.82 | 63.90 | 115.92 | 0.00 | 0.00 |
March | 115.78 | 338.89 | 249.11 | 78.24 | 170.87 | 0.00 | 0.00 |
April | 217.08 | 227.98 | 300.83 | 105.37 | 195.46 | 0.00 | 0.00 |
May | 354.07 | 113.01 | 382.28 | 135.92 | 246.36 | 0.00 | 0.00 |
June | 461.76 | 65.68 | 425.67 | 154.00 | 271.67 | 0.00 | 0.00 |
July | 480.51 | 49.42 | 423.65 | 161.81 | 261.85 | 0.00 | 0.00 |
August | 406.39 | 63.12 | 356.76 | 124.18 | 232.58 | 0.00 | 0.00 |
September | 309.78 | 132.96 | 310.25 | 121.09 | 189.17 | 0.00 | 0.00 |
October | 119.55 | 238.61 | 202.48 | 67.26 | 135.22 | 0.00 | 0.00 |
November | 29.53 | 402.02 | 124.19 | 31.02 | 93.16 | 0.00 | 0.00 |
December | 11.28 | 593.07 | 92.32 | 31.59 | 60.74 | 0.00 | 0.00 |
Annual Sum or Average | 214.64 | 282.91 | 265.74 | 93.39 | 172.35 | 0.00 | 0.00 |
Minimum of Months | 11.28 | 49.42 | 92.32 | 31.02 | 60.74 | 0.00 | 0.00 |
Maximum of Months | 480.51 | 662.63 | 425.67 | 161.81 | 271.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.55 | 717.37 | 342.74 | 202.36 | 140.39 | 0.00 | 0.00 |
February | 222.96 | 558.97 | 378.60 | 216.14 | 162.46 | 0.00 | 0.00 |
March | 220.57 | 421.19 | 362.93 | 142.92 | 220.01 | 0.00 | 0.00 |
April | 240.12 | 287.18 | 347.52 | 112.29 | 235.23 | 0.00 | 0.00 |
May | 282.96 | 139.05 | 343.02 | 63.12 | 279.90 | 0.00 | 0.00 |
June | 363.42 | 74.73 | 356.68 | 54.20 | 302.48 | 0.00 | 0.00 |
July | 386.25 | 54.26 | 358.95 | 62.76 | 296.19 | 0.00 | 0.00 |
August | 398.92 | 72.99 | 357.56 | 83.12 | 274.44 | 0.00 | 0.00 |
September | 382.79 | 161.12 | 376.66 | 145.21 | 231.44 | 0.00 | 0.00 |
October | 317.67 | 292.63 | 373.98 | 191.13 | 182.85 | 0.00 | 0.00 |
November | 173.70 | 464.75 | 276.34 | 141.96 | 134.37 | 0.00 | 0.00 |
December | 172.09 | 674.24 | 273.53 | 182.78 | 90.76 | 0.00 | 0.00 |
Annual Sum or Average | 278.75 | 325.50 | 345.51 | 132.70 | 212.81 | 0.00 | 0.00 |
Minimum of Months | 172.09 | 54.26 | 273.53 | 54.20 | 90.76 | 0.00 | 0.00 |
Maximum of Months | 398.92 | 717.37 | 378.60 | 216.14 | 302.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.97 | 602.37 | 279.62 | 161.20 | 118.41 | 0.00 | 0.00 |
February | 189.99 | 485.97 | 343.09 | 203.16 | 139.93 | 0.00 | 0.00 |
March | 219.41 | 337.16 | 347.52 | 153.17 | 194.35 | 0.00 | 0.00 |
April | 342.98 | 235.16 | 418.18 | 201.81 | 216.37 | 0.00 | 0.00 |
May | 362.56 | 123.34 | 398.02 | 144.88 | 253.14 | 0.00 | 0.00 |
June | 469.47 | 71.72 | 439.81 | 163.52 | 276.29 | 0.00 | 0.00 |
July | 522.53 | 54.64 | 470.92 | 196.15 | 274.77 | 0.00 | 0.00 |
August | 490.52 | 69.77 | 439.73 | 186.24 | 253.50 | 0.00 | 0.00 |
September | 419.93 | 138.83 | 410.13 | 201.21 | 208.92 | 0.00 | 0.00 |
October | 291.00 | 243.15 | 348.68 | 187.95 | 160.73 | 0.00 | 0.00 |
November | 139.34 | 383.30 | 234.56 | 120.46 | 114.10 | 0.00 | 0.00 |
December | 123.17 | 553.23 | 219.15 | 143.30 | 75.85 | 0.00 | 0.00 |
Annual Sum or Average | 308.58 | 273.89 | 362.46 | 171.67 | 190.80 | 0.00 | 0.00 |
Minimum of Months | 123.17 | 54.64 | 219.15 | 120.46 | 75.85 | 0.00 | 0.00 |
Maximum of Months | 522.53 | 602.37 | 470.92 | 203.16 | 276.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.19 | 676.11 | 136.38 | 44.34 | 92.04 | 0.00 | 0.00 |
February | 65.02 | 537.40 | 193.80 | 78.34 | 115.46 | 0.00 | 0.00 |
March | 114.65 | 347.73 | 241.88 | 70.64 | 171.24 | 0.00 | 0.00 |
April | 264.53 | 234.51 | 337.95 | 137.92 | 200.03 | 0.00 | 0.00 |
May | 326.35 | 120.37 | 356.55 | 114.35 | 242.20 | 0.00 | 0.00 |
June | 451.20 | 68.78 | 417.11 | 149.18 | 267.92 | 0.00 | 0.00 |
July | 493.66 | 52.72 | 435.53 | 171.74 | 263.79 | 0.00 | 0.00 |
August | 431.19 | 68.15 | 377.29 | 141.14 | 236.15 | 0.00 | 0.00 |
September | 304.29 | 137.96 | 302.85 | 117.45 | 185.40 | 0.00 | 0.00 |
October | 142.88 | 247.20 | 214.57 | 77.57 | 137.00 | 0.00 | 0.00 |
November | 44.84 | 408.99 | 132.24 | 38.47 | 93.76 | 0.00 | 0.00 |
December | 21.72 | 599.66 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Annual Sum or Average | 224.38 | 290.48 | 270.70 | 98.27 | 172.44 | 0.00 | 0.00 |
Minimum of Months | 21.72 | 52.72 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Maximum of Months | 493.66 | 676.11 | 435.53 | 171.74 | 267.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 191.64 | 306.81 | 250.17 | 171.39 | 78.79 | 0.00 | 0.00 |
February | 209.01 | 250.19 | 269.80 | 183.06 | 86.74 | 0.00 | 0.00 |
March | 173.24 | 178.93 | 231.15 | 121.05 | 110.11 | 0.00 | 0.00 |
April | 155.49 | 125.42 | 205.99 | 94.40 | 111.59 | 0.00 | 0.00 |
May | 138.18 | 64.75 | 175.66 | 49.12 | 126.54 | 0.00 | 0.00 |
June | 157.00 | 36.50 | 167.69 | 33.46 | 134.22 | 0.00 | 0.00 |
July | 173.78 | 26.89 | 177.95 | 44.48 | 133.47 | 0.00 | 0.00 |
August | 202.05 | 35.14 | 197.20 | 68.27 | 128.93 | 0.00 | 0.00 |
September | 239.63 | 72.51 | 238.17 | 122.92 | 115.25 | 0.00 | 0.00 |
October | 242.85 | 127.33 | 256.71 | 161.88 | 94.83 | 0.00 | 0.00 |
November | 156.05 | 197.05 | 192.05 | 120.24 | 71.82 | 0.00 | 0.00 |
December | 174.76 | 282.74 | 204.43 | 154.80 | 49.63 | 0.00 | 0.00 |
Annual Sum or Average | 184.35 | 141.51 | 213.60 | 110.02 | 103.58 | 0.00 | 0.00 |
Minimum of Months | 138.18 | 26.89 | 167.69 | 33.46 | 49.63 | 0.00 | 0.00 |
Maximum of Months | 242.85 | 306.81 | 269.80 | 183.06 | 134.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1715.03 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 2.00 | 1322.42 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 65.03 | 933.85 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 190.32 | 607.29 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 425.85 | 289.77 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 664.36 | 158.38 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 673.11 | 112.10 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 586.23 | 152.86 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 347.78 | 341.41 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 92.82 | 644.95 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 18.11 | 1076.11 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1582.55 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 257.01 | 742.16 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 112.10 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 673.11 | 1715.03 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1729.77 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 1.74 | 1339.00 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 62.15 | 950.88 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 185.41 | 621.92 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 417.33 | 299.05 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 655.39 | 164.75 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 664.63 | 117.38 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 578.28 | 159.19 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 341.56 | 351.80 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 88.69 | 660.45 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 16.83 | 1093.67 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1601.23 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 252.51 | 754.83 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 117.38 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 664.63 | 1729.77 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 143.94 | 1099.77 | 416.16 | 206.30 | 209.86 | 0.00 | 0.00 |
February | 247.16 | 835.61 | 509.21 | 252.71 | 256.49 | 0.00 | 0.00 |
March | 381.66 | 641.92 | 604.24 | 239.13 | 365.11 | 0.00 | 0.00 |
April | 589.25 | 438.03 | 682.35 | 274.78 | 407.57 | 0.00 | 0.00 |
May | 881.10 | 220.90 | 806.61 | 302.57 | 504.04 | 0.00 | 0.00 |
June | 1108.79 | 127.71 | 874.70 | 322.57 | 552.13 | 0.00 | 0.00 |
July | 1175.40 | 90.01 | 883.34 | 348.27 | 535.07 | 0.00 | 0.00 |
August | 1046.78 | 116.20 | 776.51 | 293.65 | 482.86 | 0.00 | 0.00 |
September | 868.98 | 246.56 | 728.26 | 326.11 | 402.14 | 0.00 | 0.00 |
October | 459.87 | 449.04 | 539.38 | 244.99 | 294.39 | 0.00 | 0.00 |
November | 175.46 | 716.71 | 350.89 | 144.08 | 206.81 | 0.00 | 0.00 |
December | 111.33 | 1059.72 | 305.61 | 168.77 | 136.83 | 0.00 | 0.00 |
Annual Sum or Average | 601.09 | 502.12 | 623.64 | 260.32 | 363.33 | 0.00 | 0.00 |
Minimum of Months | 111.33 | 90.01 | 305.61 | 144.08 | 136.83 | 0.00 | 0.00 |
Maximum of Months | 1175.40 | 1099.77 | 883.34 | 348.27 | 552.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.04 | 1258.77 | 702.45 | 436.27 | 266.18 | 0.00 | 0.00 |
February | 511.49 | 969.01 | 769.98 | 465.98 | 303.99 | 0.00 | 0.00 |
March | 461.67 | 750.42 | 713.12 | 308.13 | 404.99 | 0.00 | 0.00 |
April | 473.09 | 516.71 | 668.87 | 241.45 | 427.42 | 0.00 | 0.00 |
May | 515.63 | 254.18 | 635.05 | 132.13 | 502.92 | 0.00 | 0.00 |
June | 643.05 | 138.09 | 646.73 | 105.54 | 541.19 | 0.00 | 0.00 |
July | 690.70 | 100.79 | 659.21 | 127.42 | 531.79 | 0.00 | 0.00 |
August | 735.21 | 134.91 | 674.79 | 177.27 | 497.51 | 0.00 | 0.00 |
September | 748.00 | 290.77 | 738.52 | 313.01 | 425.51 | 0.00 | 0.00 |
October | 660.46 | 522.94 | 751.68 | 412.07 | 339.60 | 0.00 | 0.00 |
November | 380.84 | 824.33 | 557.58 | 306.07 | 251.51 | 0.00 | 0.00 |
December | 395.44 | 1197.91 | 564.95 | 394.06 | 170.89 | 0.00 | 0.00 |
Annual Sum or Average | 553.73 | 578.21 | 673.01 | 283.94 | 389.07 | 0.00 | 0.00 |
Minimum of Months | 380.84 | 100.79 | 557.58 | 105.54 | 170.89 | 0.00 | 0.00 |
Maximum of Months | 748.00 | 1258.77 | 769.98 | 465.98 | 541.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.190712E+10 | 0.249022E+10 | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.00 | 0.00 |
February | 0.189672E+10 | 0.175559E+10 | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.00 | 0.00 |
March | 0.168185E+10 | 0.149870E+10 | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.00 | 0.00 |
April | 0.143264E+10 | 0.102143E+10 | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.00 | 0.00 |
May | 0.132892E+10 | 0.546167E+09 | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.00 | 0.00 |
June | 0.143374E+10 | 0.302669E+09 | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.00 | 0.00 |
July | 0.163672E+10 | 0.235993E+09 | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.00 | 0.00 |
August | 0.190421E+10 | 0.302307E+09 | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.00 | 0.00 |
September | 0.218289E+10 | 0.600696E+09 | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.00 | 0.00 |
October | 0.231782E+10 | 0.107404E+10 | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.00 | 0.00 |
November | 0.146510E+10 | 0.158148E+10 | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.00 | 0.00 |
December | 0.168785E+10 | 0.239142E+10 | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208756E+11 | 0.138007E+11 | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132892E+10 | 0.235993E+09 | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231782E+10 | 0.249022E+10 | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.535327E+10 | 0.702447E+10 | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.00 | 0.00 |
February | 0.532117E+10 | 0.496561E+10 | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.00 | 0.00 |
March | 0.470772E+10 | 0.422298E+10 | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.00 | 0.00 |
April | 0.401343E+10 | 0.287548E+10 | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.00 | 0.00 |
May | 0.371184E+10 | 0.152102E+10 | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.401441E+10 | 0.832826E+09 | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.00 | 0.00 |
July | 0.458831E+10 | 0.638892E+09 | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.00 | 0.00 |
August | 0.534172E+10 | 0.829340E+09 | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.00 | 0.00 |
September | 0.613525E+10 | 0.167499E+10 | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.00 | 0.00 |
October | 0.650783E+10 | 0.301936E+10 | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.00 | 0.00 |
November | 0.410219E+10 | 0.445903E+10 | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.00 | 0.00 |
December | 0.473209E+10 | 0.675446E+10 | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585292E+11 | 0.388185E+11 | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.371184E+10 | 0.638892E+09 | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.650783E+10 | 0.702447E+10 | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704549E+10 | 0.939279E+10 | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.00 | 0.00 |
February | 0.704896E+10 | 0.656385E+10 | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.00 | 0.00 |
March | 0.622211E+10 | 0.564061E+10 | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.00 | 0.00 |
April | 0.532145E+10 | 0.385130E+10 | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.00 | 0.00 |
May | 0.495103E+10 | 0.204723E+10 | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.00 | 0.00 |
June | 0.536445E+10 | 0.111941E+10 | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.00 | 0.00 |
July | 0.612948E+10 | 0.848797E+09 | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.00 | 0.00 |
August | 0.711145E+10 | 0.110252E+10 | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.00 | 0.00 |
September | 0.813276E+10 | 0.223364E+10 | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.00 | 0.00 |
October | 0.861275E+10 | 0.402400E+10 | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.00 | 0.00 |
November | 0.541178E+10 | 0.596411E+10 | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.00 | 0.00 |
December | 0.622961E+10 | 0.902583E+10 | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.775813E+11 | 0.518141E+11 | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.00 | 0.00 |
Minimum of Months | 0.495103E+10 | 0.848797E+09 | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.00 | 0.00 |
Maximum of Months | 0.861275E+10 | 0.939279E+10 | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338031E+09 | 0.160320E+10 | 0.748309E+09 | 0.431415E+09 | 0.316894E+09 | 0.00 | 0.00 |
February | 0.465480E+09 | 0.116313E+10 | 0.829313E+09 | 0.491083E+09 | 0.338230E+09 | 0.00 | 0.00 |
March | 0.589658E+09 | 0.901158E+09 | 0.930041E+09 | 0.409925E+09 | 0.520116E+09 | 0.00 | 0.00 |
April | 0.894989E+09 | 0.608003E+09 | 0.108302E+10 | 0.522652E+09 | 0.560370E+09 | 0.00 | 0.00 |
May | 0.982377E+09 | 0.327146E+09 | 0.106517E+10 | 0.387727E+09 | 0.677444E+09 | 0.00 | 0.00 |
June | 0.122815E+10 | 0.183531E+09 | 0.113905E+10 | 0.423494E+09 | 0.715557E+09 | 0.00 | 0.00 |
July | 0.141196E+10 | 0.144059E+09 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
August | 0.132526E+10 | 0.183897E+09 | 0.117681E+10 | 0.498404E+09 | 0.678406E+09 | 0.00 | 0.00 |
September | 0.109533E+10 | 0.358092E+09 | 0.106219E+10 | 0.521121E+09 | 0.541072E+09 | 0.00 | 0.00 |
October | 0.783065E+09 | 0.650234E+09 | 0.933147E+09 | 0.503000E+09 | 0.430148E+09 | 0.00 | 0.00 |
November | 0.361558E+09 | 0.991828E+09 | 0.607482E+09 | 0.311969E+09 | 0.295513E+09 | 0.00 | 0.00 |
December | 0.329711E+09 | 0.147736E+10 | 0.586489E+09 | 0.383497E+09 | 0.202992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980558E+10 | 0.859164E+10 | 0.114213E+11 | 0.540923E+10 | 0.601208E+10 | 0.00 | 0.00 |
Minimum of Months | 0.329711E+09 | 0.144059E+09 | 0.586489E+09 | 0.311969E+09 | 0.202992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141196E+10 | 0.160320E+10 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59974363.98 | 0.179828E+10 | 0.364990E+09 | 0.118673E+09 | 0.246317E+09 | 0.00 | 0.00 |
February | 0.159016E+09 | 0.128374E+10 | 0.468450E+09 | 0.189369E+09 | 0.279081E+09 | 0.00 | 0.00 |
March | 0.307481E+09 | 0.929760E+09 | 0.647318E+09 | 0.189044E+09 | 0.458274E+09 | 0.00 | 0.00 |
April | 0.691282E+09 | 0.606631E+09 | 0.875254E+09 | 0.357208E+09 | 0.518045E+09 | 0.00 | 0.00 |
May | 0.886251E+09 | 0.319342E+09 | 0.954195E+09 | 0.306014E+09 | 0.648181E+09 | 0.00 | 0.00 |
June | 0.118183E+10 | 0.175878E+09 | 0.108025E+10 | 0.386366E+09 | 0.693885E+09 | 0.00 | 0.00 |
July | 0.133562E+10 | 0.138874E+09 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
August | 0.116739E+10 | 0.179596E+09 | 0.100970E+10 | 0.377708E+09 | 0.631991E+09 | 0.00 | 0.00 |
September | 0.795588E+09 | 0.356178E+09 | 0.784351E+09 | 0.304189E+09 | 0.480163E+09 | 0.00 | 0.00 |
October | 0.383268E+09 | 0.663116E+09 | 0.574235E+09 | 0.207605E+09 | 0.366630E+09 | 0.00 | 0.00 |
November | 0.115274E+09 | 0.105974E+10 | 0.342478E+09 | 99641378.41 | 0.242837E+09 | 0.00 | 0.00 |
December | 57711962.77 | 0.160141E+10 | 0.263144E+09 | 0.101017E+09 | 0.162127E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.714068E+10 | 0.911255E+10 | 0.852994E+10 | 0.309645E+10 | 0.543350E+10 | 0.00 | 0.00 |
Minimum of Months | 57711962.77 | 0.138874E+09 | 0.263144E+09 | 99641378.41 | 0.162127E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133562E+10 | 0.179828E+10 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287815E+09 | 0.433810E+09 | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.00 | 0.00 |
February | 0.280329E+09 | 0.332711E+09 | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.00 | 0.00 |
March | 0.253090E+09 | 0.270178E+09 | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.00 | 0.00 |
April | 0.216685E+09 | 0.196798E+09 | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.00 | 0.00 |
May | 0.193896E+09 | 0.113240E+09 | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.00 | 0.00 |
June | 0.212391E+09 | 67472955.34 | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.00 | 0.00 |
July | 0.244211E+09 | 54513442.32 | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.00 | 0.00 |
August | 0.287184E+09 | 68050870.34 | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.00 | 0.00 |
September | 0.333752E+09 | 0.122453E+09 | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.00 | 0.00 |
October | 0.351108E+09 | 0.208484E+09 | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.00 | 0.00 |
November | 0.220520E+09 | 0.289489E+09 | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.00 | 0.00 |
December | 0.259766E+09 | 0.406191E+09 | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.314075E+10 | 0.256339E+10 | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.193896E+09 | 54513442.32 | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.00 | 0.00 |
Maximum of Months | 0.351108E+09 | 0.433810E+09 | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.553154E+09 | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.00 |
February | 530290.49 | 0.405531E+09 | 67056690.67 | 0.00 | 67056690.67 | 0.00 | 0.00 |
March | 19236814.09 | 0.287493E+09 | 0.111280E+09 | 941.15 | 0.111279E+09 | 0.00 | 0.00 |
April | 54391958.99 | 0.180499E+09 | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 0.00 | 0.00 |
May | 0.125873E+09 | 88298392.00 | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.00 | 0.00 |
June | 0.189925E+09 | 47602997.43 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
July | 0.197935E+09 | 36342113.89 | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.00 | 0.00 |
August | 0.172326E+09 | 47992522.81 | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.00 | 0.00 |
September | 98579286.18 | 0.102617E+09 | 0.114208E+09 | 102488.46 | 0.114105E+09 | 0.00 | 0.00 |
October | 27030823.64 | 0.198643E+09 | 87633982.09 | 0.00 | 87633982.09 | 0.00 | 0.00 |
November | 5062510.23 | 0.324520E+09 | 59323427.52 | 0.00 | 59323427.52 | 0.00 | 0.00 |
December | 0.00 | 0.486298E+09 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.890891E+09 | 0.275899E+10 | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 36342113.89 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Maximum of Months | 0.197935E+09 | 0.553154E+09 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333919E+09 | 0.159653E+10 | 0.748545E+09 | 0.432434E+09 | 0.316111E+09 | 0.00 | 0.00 |
February | 0.418572E+09 | 0.114591E+10 | 0.795886E+09 | 0.456300E+09 | 0.339586E+09 | 0.00 | 0.00 |
March | 0.601794E+09 | 0.888398E+09 | 0.949929E+09 | 0.430432E+09 | 0.519498E+09 | 0.00 | 0.00 |
April | 0.767929E+09 | 0.594160E+09 | 0.987526E+09 | 0.438565E+09 | 0.548961E+09 | 0.00 | 0.00 |
May | 0.104288E+10 | 0.308125E+09 | 0.113487E+10 | 0.445751E+09 | 0.689117E+09 | 0.00 | 0.00 |
June | 0.123832E+10 | 0.172875E+09 | 0.116214E+10 | 0.436297E+09 | 0.725840E+09 | 0.00 | 0.00 |
July | 0.136020E+10 | 0.134217E+09 | 0.122942E+10 | 0.498717E+09 | 0.730702E+09 | 0.00 | 0.00 |
August | 0.124519E+10 | 0.171624E+09 | 0.112265E+10 | 0.453303E+09 | 0.669350E+09 | 0.00 | 0.00 |
September | 0.110571E+10 | 0.348056E+09 | 0.108201E+10 | 0.530786E+09 | 0.551228E+09 | 0.00 | 0.00 |
October | 0.730675E+09 | 0.636982E+09 | 0.901231E+09 | 0.475534E+09 | 0.425696E+09 | 0.00 | 0.00 |
November | 0.328562E+09 | 0.979900E+09 | 0.586899E+09 | 0.292740E+09 | 0.294159E+09 | 0.00 | 0.00 |
December | 0.301985E+09 | 0.146334E+10 | 0.570618E+09 | 0.367081E+09 | 0.203537E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.947575E+10 | 0.844011E+10 | 0.112717E+11 | 0.525794E+10 | 0.601379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.301985E+09 | 0.134217E+09 | 0.570618E+09 | 0.292740E+09 | 0.203537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136020E+10 | 0.159653E+10 | 0.122942E+10 | 0.530786E+09 | 0.730702E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39155215.54 | 0.177478E+10 | 0.365226E+09 | 0.119692E+09 | 0.245534E+09 | 0.00 | 0.00 |
February | 0.106371E+09 | 0.126004E+10 | 0.435023E+09 | 0.154586E+09 | 0.280437E+09 | 0.00 | 0.00 |
March | 0.310110E+09 | 0.907687E+09 | 0.667206E+09 | 0.209551E+09 | 0.457655E+09 | 0.00 | 0.00 |
April | 0.562678E+09 | 0.590930E+09 | 0.779757E+09 | 0.273121E+09 | 0.506636E+09 | 0.00 | 0.00 |
May | 0.948335E+09 | 0.302690E+09 | 0.102389E+10 | 0.364038E+09 | 0.659854E+09 | 0.00 | 0.00 |
June | 0.119689E+10 | 0.170232E+09 | 0.110334E+10 | 0.399169E+09 | 0.704169E+09 | 0.00 | 0.00 |
July | 0.128699E+10 | 0.132361E+09 | 0.113471E+10 | 0.433385E+09 | 0.701329E+09 | 0.00 | 0.00 |
August | 0.108847E+10 | 0.169049E+09 | 0.955542E+09 | 0.332608E+09 | 0.622934E+09 | 0.00 | 0.00 |
September | 0.802945E+09 | 0.344620E+09 | 0.804173E+09 | 0.313854E+09 | 0.490319E+09 | 0.00 | 0.00 |
October | 0.320208E+09 | 0.639081E+09 | 0.542318E+09 | 0.180140E+09 | 0.362178E+09 | 0.00 | 0.00 |
November | 76531139.23 | 0.104204E+10 | 0.321895E+09 | 80412113.67 | 0.241483E+09 | 0.00 | 0.00 |
December | 30212326.70 | 0.158849E+10 | 0.247273E+09 | 84600328.40 | 0.162673E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.676890E+10 | 0.892199E+10 | 0.838036E+10 | 0.294516E+10 | 0.543520E+10 | 0.00 | 0.00 |
Minimum of Months | 30212326.70 | 0.132361E+09 | 0.247273E+09 | 80412113.67 | 0.162673E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128699E+10 | 0.177478E+10 | 0.113471E+10 | 0.433385E+09 | 0.704169E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480916E+09 | 0.192140E+10 | 0.918002E+09 | 0.541992E+09 | 0.376010E+09 | 0.00 | 0.00 |
February | 0.539379E+09 | 0.135226E+10 | 0.915899E+09 | 0.522880E+09 | 0.393019E+09 | 0.00 | 0.00 |
March | 0.590779E+09 | 0.112812E+10 | 0.972071E+09 | 0.382798E+09 | 0.589274E+09 | 0.00 | 0.00 |
April | 0.622403E+09 | 0.744377E+09 | 0.900763E+09 | 0.291055E+09 | 0.609707E+09 | 0.00 | 0.00 |
May | 0.757885E+09 | 0.372419E+09 | 0.918743E+09 | 0.169058E+09 | 0.749685E+09 | 0.00 | 0.00 |
June | 0.941997E+09 | 0.193692E+09 | 0.924524E+09 | 0.140489E+09 | 0.784035E+09 | 0.00 | 0.00 |
July | 0.103454E+10 | 0.145341E+09 | 0.961416E+09 | 0.168104E+09 | 0.793313E+09 | 0.00 | 0.00 |
August | 0.106848E+10 | 0.195499E+09 | 0.957681E+09 | 0.222633E+09 | 0.735048E+09 | 0.00 | 0.00 |
September | 0.992183E+09 | 0.417623E+09 | 0.976296E+09 | 0.376394E+09 | 0.599902E+09 | 0.00 | 0.00 |
October | 0.850844E+09 | 0.783792E+09 | 0.100167E+10 | 0.511928E+09 | 0.489739E+09 | 0.00 | 0.00 |
November | 0.450225E+09 | 0.120463E+10 | 0.716270E+09 | 0.367971E+09 | 0.348299E+09 | 0.00 | 0.00 |
December | 0.460916E+09 | 0.180588E+10 | 0.732636E+09 | 0.489548E+09 | 0.243088E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.879054E+10 | 0.102650E+11 | 0.108960E+11 | 0.418485E+10 | 0.671112E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450225E+09 | 0.145341E+09 | 0.716270E+09 | 0.140489E+09 | 0.243088E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106848E+10 | 0.192140E+10 | 0.100167E+10 | 0.541992E+09 | 0.793313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.334714E+09 | 0.161338E+10 | 0.748923E+09 | 0.431769E+09 | 0.317154E+09 | 0.00 | 0.00 |
February | 0.459623E+09 | 0.117566E+10 | 0.829993E+09 | 0.491486E+09 | 0.338508E+09 | 0.00 | 0.00 |
March | 0.587667E+09 | 0.903043E+09 | 0.930804E+09 | 0.410261E+09 | 0.520543E+09 | 0.00 | 0.00 |
April | 0.889010E+09 | 0.609539E+09 | 0.108391E+10 | 0.523081E+09 | 0.560830E+09 | 0.00 | 0.00 |
May | 0.971092E+09 | 0.330346E+09 | 0.106604E+10 | 0.388045E+09 | 0.678000E+09 | 0.00 | 0.00 |
June | 0.121686E+10 | 0.185907E+09 | 0.113998E+10 | 0.423841E+09 | 0.716144E+09 | 0.00 | 0.00 |
July | 0.139956E+10 | 0.146360E+09 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
August | 0.131381E+10 | 0.186872E+09 | 0.117778E+10 | 0.498813E+09 | 0.678963E+09 | 0.00 | 0.00 |
September | 0.108846E+10 | 0.359858E+09 | 0.106306E+10 | 0.521548E+09 | 0.541516E+09 | 0.00 | 0.00 |
October | 0.779424E+09 | 0.651264E+09 | 0.933913E+09 | 0.503412E+09 | 0.430500E+09 | 0.00 | 0.00 |
November | 0.361157E+09 | 0.993505E+09 | 0.607981E+09 | 0.312225E+09 | 0.295756E+09 | 0.00 | 0.00 |
December | 0.329905E+09 | 0.148177E+10 | 0.586970E+09 | 0.383812E+09 | 0.203158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973127E+10 | 0.863749E+10 | 0.114307E+11 | 0.541366E+10 | 0.601701E+10 | 0.00 | 0.00 |
Minimum of Months | 0.329905E+09 | 0.146360E+09 | 0.586970E+09 | 0.312225E+09 | 0.203158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139956E+10 | 0.161338E+10 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59434072.21 | 0.181090E+10 | 0.365289E+09 | 0.118770E+09 | 0.246519E+09 | 0.00 | 0.00 |
February | 0.157301E+09 | 0.130007E+10 | 0.468835E+09 | 0.189524E+09 | 0.279310E+09 | 0.00 | 0.00 |
March | 0.307083E+09 | 0.931350E+09 | 0.647849E+09 | 0.189199E+09 | 0.458650E+09 | 0.00 | 0.00 |
April | 0.685661E+09 | 0.607853E+09 | 0.875972E+09 | 0.357501E+09 | 0.518470E+09 | 0.00 | 0.00 |
May | 0.874095E+09 | 0.322396E+09 | 0.954978E+09 | 0.306265E+09 | 0.648713E+09 | 0.00 | 0.00 |
June | 0.116952E+10 | 0.178280E+09 | 0.108114E+10 | 0.386683E+09 | 0.694454E+09 | 0.00 | 0.00 |
July | 0.132221E+10 | 0.141215E+09 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
August | 0.115491E+10 | 0.182539E+09 | 0.101053E+10 | 0.378018E+09 | 0.632509E+09 | 0.00 | 0.00 |
September | 0.788722E+09 | 0.357591E+09 | 0.784995E+09 | 0.304438E+09 | 0.480556E+09 | 0.00 | 0.00 |
October | 0.382702E+09 | 0.662106E+09 | 0.574706E+09 | 0.207776E+09 | 0.366931E+09 | 0.00 | 0.00 |
November | 0.116214E+09 | 0.106009E+10 | 0.342759E+09 | 99723118.67 | 0.243036E+09 | 0.00 | 0.00 |
December | 58188079.18 | 0.160614E+10 | 0.263360E+09 | 0.101100E+09 | 0.162260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.707604E+10 | 0.916053E+10 | 0.853694E+10 | 0.309899E+10 | 0.543795E+10 | 0.00 | 0.00 |
Minimum of Months | 58188079.18 | 0.141215E+09 | 0.263360E+09 | 99723118.67 | 0.162260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132221E+10 | 0.181090E+10 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.513290E+09 | 0.821756E+09 | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.00 | 0.00 |
February | 0.505645E+09 | 0.605252E+09 | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.00 | 0.00 |
March | 0.463998E+09 | 0.479248E+09 | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.00 | 0.00 |
April | 0.403038E+09 | 0.325086E+09 | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.00 | 0.00 |
May | 0.370108E+09 | 0.173417E+09 | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.00 | 0.00 |
June | 0.406956E+09 | 94614841.59 | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.00 | 0.00 |
July | 0.465463E+09 | 72031009.95 | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.00 | 0.00 |
August | 0.541160E+09 | 94131139.84 | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.00 | 0.00 |
September | 0.621129E+09 | 0.187956E+09 | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.00 | 0.00 |
October | 0.650436E+09 | 0.341031E+09 | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.00 | 0.00 |
November | 0.404482E+09 | 0.510753E+09 | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.00 | 0.00 |
December | 0.468088E+09 | 0.757290E+09 | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.581379E+10 | 0.446257E+10 | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370108E+09 | 72031009.95 | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.650436E+09 | 0.821756E+09 | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.459355E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 4842533.83 | 0.319921E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.174164E+09 | 0.250123E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.493301E+09 | 0.157411E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.114061E+10 | 0.776109E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.172203E+10 | 0.410523E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.180285E+10 | 0.300248E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.157015E+10 | 0.409414E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.901437E+09 | 0.884945E+09 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.248597E+09 | 0.172742E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 46949053.80 | 0.278929E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.423871E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810493E+10 | 0.234047E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.300248E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180285E+10 | 0.459355E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.463301E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 4205703.77 | 0.323930E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.166467E+09 | 0.254685E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.480585E+09 | 0.161202E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.111777E+10 | 0.800984E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.169876E+10 | 0.427035E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.178014E+10 | 0.314381E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.154886E+10 | 0.426383E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.885314E+09 | 0.911877E+09 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.237536E+09 | 0.176896E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 43617587.66 | 0.283479E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.428874E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.796325E+10 | 0.238043E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.314381E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178014E+10 | 0.463301E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.385541E+09 | 0.294563E+10 | 0.111464E+10 | 0.552562E+09 | 0.562081E+09 | 0.00 | 0.00 |
February | 0.597925E+09 | 0.202152E+10 | 0.123187E+10 | 0.611366E+09 | 0.620503E+09 | 0.00 | 0.00 |
March | 0.102224E+10 | 0.171933E+10 | 0.161839E+10 | 0.640478E+09 | 0.977909E+09 | 0.00 | 0.00 |
April | 0.152733E+10 | 0.113538E+10 | 0.176864E+10 | 0.712232E+09 | 0.105641E+10 | 0.00 | 0.00 |
May | 0.235993E+10 | 0.591667E+09 | 0.216042E+10 | 0.810402E+09 | 0.135001E+10 | 0.00 | 0.00 |
June | 0.287399E+10 | 0.331031E+09 | 0.226721E+10 | 0.836098E+09 | 0.143111E+10 | 0.00 | 0.00 |
July | 0.314818E+10 | 0.241089E+09 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
August | 0.280369E+10 | 0.311237E+09 | 0.207979E+10 | 0.786509E+09 | 0.129328E+10 | 0.00 | 0.00 |
September | 0.225239E+10 | 0.639092E+09 | 0.188764E+10 | 0.845288E+09 | 0.104235E+10 | 0.00 | 0.00 |
October | 0.123171E+10 | 0.120271E+10 | 0.144467E+10 | 0.656187E+09 | 0.788485E+09 | 0.00 | 0.00 |
November | 0.454785E+09 | 0.185770E+10 | 0.909504E+09 | 0.373447E+09 | 0.536057E+09 | 0.00 | 0.00 |
December | 0.298177E+09 | 0.283835E+10 | 0.818534E+09 | 0.452039E+09 | 0.366494E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189559E+11 | 0.158347E+11 | 0.196673E+11 | 0.820941E+10 | 0.114578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298177E+09 | 0.241089E+09 | 0.818534E+09 | 0.373447E+09 | 0.366494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.314818E+10 | 0.294563E+10 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114110E+10 | 0.337150E+10 | 0.188144E+10 | 0.116852E+10 | 0.712925E+09 | 0.00 | 0.00 |
February | 0.123741E+10 | 0.234424E+10 | 0.186272E+10 | 0.112731E+10 | 0.735414E+09 | 0.00 | 0.00 |
March | 0.123653E+10 | 0.200992E+10 | 0.191002E+10 | 0.825297E+09 | 0.108472E+10 | 0.00 | 0.00 |
April | 0.122624E+10 | 0.133930E+10 | 0.173371E+10 | 0.625835E+09 | 0.110787E+10 | 0.00 | 0.00 |
May | 0.138105E+10 | 0.680797E+09 | 0.170092E+10 | 0.353908E+09 | 0.134701E+10 | 0.00 | 0.00 |
June | 0.166678E+10 | 0.357934E+09 | 0.167632E+10 | 0.273554E+09 | 0.140276E+10 | 0.00 | 0.00 |
July | 0.184998E+10 | 0.269946E+09 | 0.176562E+10 | 0.341282E+09 | 0.142433E+10 | 0.00 | 0.00 |
August | 0.196920E+10 | 0.361350E+09 | 0.180735E+10 | 0.474802E+09 | 0.133254E+10 | 0.00 | 0.00 |
September | 0.193881E+10 | 0.753668E+09 | 0.191424E+10 | 0.811322E+09 | 0.110292E+10 | 0.00 | 0.00 |
October | 0.176899E+10 | 0.140064E+10 | 0.201329E+10 | 0.110370E+10 | 0.909592E+09 | 0.00 | 0.00 |
November | 0.987139E+09 | 0.213665E+10 | 0.144524E+10 | 0.793333E+09 | 0.651906E+09 | 0.00 | 0.00 |
December | 0.105915E+10 | 0.320849E+10 | 0.151317E+10 | 0.105545E+10 | 0.457722E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174624E+11 | 0.182344E+11 | 0.212240E+11 | 0.895431E+10 | 0.122697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.987139E+09 | 0.269946E+09 | 0.144524E+10 | 0.273554E+09 | 0.457722E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196920E+10 | 0.337150E+10 | 0.201329E+10 | 0.116852E+10 | 0.142433E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.458564E+11 | -.799424E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.163145E+10 | 59.04 | 0.00 | 0.00 |
February | 0.430995E+11 | -.736831E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.153586E+10 | 59.03 | 0.00 | 0.00 |
March | 0.467630E+11 | -.808165E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.158867E+10 | 59.03 | 0.00 | 0.00 |
April | 0.419389E+11 | -.751645E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.154443E+10 | 59.10 | 0.00 | 0.00 |
May | 0.383208E+11 | -.730669E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.160305E+10 | 59.19 | 0.00 | 0.00 |
June | 0.319818E+11 | -.660304E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.155917E+10 | 59.33 | 0.00 | 0.00 |
July | 0.288507E+11 | -.643799E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.161678E+10 | 59.52 | 0.00 | 0.00 |
August | 0.270104E+11 | -.626952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.161587E+10 | 59.59 | 0.00 | 0.00 |
September | 0.270043E+11 | -.614727E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.155625E+10 | 59.55 | 0.00 | 0.00 |
October | 0.313280E+11 | -.666712E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159420E+10 | 59.38 | 0.00 | 0.00 |
November | 0.351983E+11 | -.689925E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.154249E+10 | 59.25 | 0.00 | 0.00 |
December | 0.416684E+11 | -.761495E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.158746E+10 | 59.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.439020E+12 | -.849065E+12 | 8760.00 | -.189757E+11 | 59.26 | |||||
Minimum of Months | 0.270043E+11 | -.808165E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.163145E+10 | 59.03 | 0.00 | 0.00 |
Maximum of Months | 0.467630E+11 | -.614727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.153586E+10 | 59.59 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.771384E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171050368.3 | 81.21 | 0.00 | 0.00 |
February | 0.697195E+10 | -.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155985374.8 | 81.21 | 0.00 | 0.00 |
March | 0.770739E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164580902.1 | 81.21 | 0.00 | 0.00 |
April | 0.746798E+10 | -.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159404604.0 | 81.21 | 0.00 | 0.00 |
May | 0.770827E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165494169.0 | 81.21 | 0.00 | 0.00 |
June | 0.746155E+10 | -.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -161020237.5 | 81.21 | 0.00 | 0.00 |
July | 0.771788E+10 | -.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167012013.1 | 81.21 | 0.00 | 0.00 |
August | 0.770975E+10 | -.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166926821.0 | 81.21 | 0.00 | 0.00 |
September | 0.746906E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160464722.7 | 81.21 | 0.00 | 0.00 |
October | 0.770729E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164517628.3 | 81.21 | 0.00 | 0.00 |
November | 0.745279E+10 | -.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160357736.9 | 81.21 | 0.00 | 0.00 |
December | 0.771611E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165275835.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.908039E+11 | -.888418E+11 | 8760.00 | -.196209E+10 | 81.21 | |||||
Minimum of Months | 0.697195E+10 | -.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -171050368.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771788E+10 | -.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155985374.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.795376E+11 | -.782983E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.123929E+10 | 61.11 | 0.00 | 0.00 |
February | 0.720253E+11 | -.708719E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.115335E+10 | 60.70 | 0.00 | 0.00 |
March | 0.796051E+11 | -.784046E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120058E+10 | 60.84 | 0.00 | 0.00 |
April | 0.767431E+11 | -.755563E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118671E+10 | 61.59 | 0.00 | 0.00 |
May | 0.788386E+11 | -.775789E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125976E+10 | 62.62 | 0.00 | 0.00 |
June | 0.758243E+11 | -.745722E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125211E+10 | 63.70 | 0.00 | 0.00 |
July | 0.779706E+11 | -.766531E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131753E+10 | 64.53 | 0.00 | 0.00 |
August | 0.777965E+11 | -.764703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132621E+10 | 64.91 | 0.00 | 0.00 |
September | 0.753693E+11 | -.740957E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127355E+10 | 64.73 | 0.00 | 0.00 |
October | 0.781990E+11 | -.769090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128999E+10 | 64.03 | 0.00 | 0.00 |
November | 0.761248E+11 | -.749014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122334E+10 | 63.04 | 0.00 | 0.00 |
December | 0.791488E+11 | -.779197E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122910E+10 | 61.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.927183E+12 | -.912231E+12 | 8760.00 | -.149515E+11 | 62.82 | |||||
Minimum of Months | 0.720253E+11 | -.784046E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.132621E+10 | 60.70 | 0.00 | 0.00 |
Maximum of Months | 0.796051E+11 | -.708719E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.115335E+10 | 64.91 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145942E+11 | 14984.69 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153487E+11 | 15724.21 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143525E+11 | 10401.32 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183525E+11 | 10509.37 | 14-APR-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214753E+11 | 10509.36 | 05-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.225283E+11 | 10509.34 | 11-JUN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239204E+11 | 10509.27 | 02-JUL-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191331E+11 | 10509.33 | 04-AUG-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109162E+11 | 10509.31 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278949E+10 | 10508.93 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388798E+10 | 14686.05 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295012E+10 | 5362.55 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170249E+12 | |||||||
Minimum of Months | 0.278949E+10 | 5362.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239204E+11 | 15724.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848913E+10 | 5886.89 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657240E+10 | 6186.38 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500045E+10 | 3585.03 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397558E+10 | 3090.10 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.348895E+10 | 2145.14 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317096E+10 | 1994.39 | 13-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323915E+10 | 1984.15 | 20-JUL-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.301569E+10 | 1963.35 | 31-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287833E+10 | 2523.63 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343645E+10 | 2630.58 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538782E+10 | 5766.39 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688534E+10 | 3880.00 | 12-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555403E+11 | |||||||
Minimum of Months | 0.287833E+10 | 1963.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848913E+10 | 6186.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274365E+10 | 2300.56 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213299E+10 | 2415.33 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136009E+10 | 1188.62 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117718E+10 | 1231.40 | 18-APR-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132136E+10 | 1333.14 | 26-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152304E+10 | 1336.36 | 14-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174227E+10 | 1321.44 | 09-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164218E+10 | 1306.12 | 31-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128249E+10 | 1274.10 | 05-SEP-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100188E+10 | 1274.07 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154910E+10 | 2254.27 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186513E+10 | 1491.42 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193413E+11 | |||||||
Minimum of Months | 0.100188E+10 | 1188.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274365E+10 | 2415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495748E+10 | 3265.88 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399997E+10 | 3429.94 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303274E+10 | 2091.74 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256002E+10 | 1780.56 | 03-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246967E+10 | 1719.59 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.255560E+10 | 1656.84 | 10-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283776E+10 | 1651.73 | 07-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.273812E+10 | 1605.55 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243962E+10 | 1665.74 | 11-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237001E+10 | 1679.47 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316085E+10 | 3199.78 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.389546E+10 | 2160.09 | 13-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370173E+11 | |||||||
Minimum of Months | 0.237001E+10 | 1605.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495748E+10 | 3429.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313820E+10 | 1902.82 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254234E+10 | 1999.37 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202624E+10 | 1225.41 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161980E+10 | 1013.29 | 03-APR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139038E+10 | 749.78 | 04-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128826E+10 | 711.56 | 10-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137238E+10 | 694.69 | 11-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135633E+10 | 701.65 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134262E+10 | 811.89 | 30-SEP-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153861E+10 | 847.14 | 28-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206617E+10 | 1863.95 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260381E+10 | 1255.14 | 13-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222852E+11 | |||||||
Minimum of Months | 0.128826E+10 | 694.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313820E+10 | 1999.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177561E+11 | 18903.82 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158373E+11 | 19836.89 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125740E+11 | 13121.38 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139243E+11 | 13257.61 | 18-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188320E+11 | 13257.68 | 05-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.223664E+11 | 13257.62 | 14-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.256251E+11 | 13257.57 | 02-JUL-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245489E+11 | 13257.64 | 04-AUG-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193090E+11 | 13257.61 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132601E+11 | 13257.13 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133602E+11 | 18527.02 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128893E+11 | 12555.77 | 11-DEC-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210283E+12 | |||||||
Minimum of Months | 0.125740E+11 | 12555.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256251E+11 | 19836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199580E+11 | 18110.86 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151132E+11 | 19022.75 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917130E+10 | 9459.81 | 01-MAR-11:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.744767E+10 | 9207.92 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743316E+10 | 7730.14 | 26-MAY-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.796756E+10 | 8402.64 | 14-JUN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.895342E+10 | 8514.72 | 06-JUL-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789777E+10 | 8448.11 | 31-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.584534E+10 | 7705.78 | 13-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544963E+10 | 7622.43 | 26-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108235E+11 | 17743.45 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141981E+11 | 11967.64 | 12-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120259E+12 | |||||||
Minimum of Months | 0.544963E+10 | 7622.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199580E+11 | 19022.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.456326E+11 | 46065.07 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355148E+11 | 48364.62 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185748E+11 | 23146.51 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170335E+11 | 23357.09 | 18-APR-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205005E+11 | 25523.05 | 14-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243697E+11 | 26469.64 | 14-JUN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284182E+11 | 26162.81 | 20-JUL-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261497E+11 | 26162.99 | 31-AUG-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188913E+11 | 25188.81 | 18-SEP-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125320E+11 | 23356.23 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225478E+11 | 45137.83 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271835E+11 | 29516.21 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297348E+12 | |||||||
Minimum of Months | 0.125320E+11 | 23146.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.456326E+11 | 48364.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.759799E+10 | 8295.83 | 09-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.539471E+10 | 8347.21 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247369E+10 | 8295.25 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100218E+10 | 8294.28 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98233990.47 | 6121.07 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37685540.74 | 3351.35 | 22-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5099059.88 | 2761.40 | 30-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5448160.28 | 3052.72 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196880E+09 | 7657.17 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.752013E+09 | 8134.49 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318948E+10 | 8295.41 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577764E+10 | 8296.66 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265310E+11 | |||||||
Minimum of Months | 5099059.88 | 2761.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.759799E+10 | 8347.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.878053E+10 | 8269.39 | 09-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632037E+10 | 8301.99 | 03-FEB-11:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291369E+10 | 8268.80 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113253E+10 | 8267.80 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117889E+09 | 6805.66 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40177114.19 | 3320.58 | 15-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5263162.67 | 2842.01 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5972039.16 | 2921.87 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248413E+09 | 8056.56 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107864E+10 | 8147.71 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377646E+10 | 8268.94 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669042E+10 | 8270.22 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311104E+11 | |||||||
Minimum of Months | 5263162.67 | 2842.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878053E+10 | 8301.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128206E+11 | 42404.92 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.839704E+10 | 46503.33 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.900921E+09 | 10467.54 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193995E+10 | 31738.75 | 26-NOV-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.594647E+10 | 20978.59 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300050E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128206E+11 | 46503.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298848E+11 | 46791.29 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209525E+11 | 46787.35 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437975E+10 | 45785.78 | 01-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752717E+09 | 44883.46 | 03-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56832113.28 | 36122.43 | 18-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37561825.23 | 26771.90 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15620545.40 | 15725.38 | 25-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19364102.40 | 27249.71 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99266160.92 | 37876.50 | 24-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298771E+09 | 27791.48 | 30-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.765102E+10 | 46788.60 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169492E+11 | 46787.36 | 12-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810975E+11 | |||||||
Minimum of Months | 15620545.40 | 15725.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298848E+11 | 46791.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.758172E+10 | 7980.04 | 17-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546780E+10 | 8005.65 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245080E+10 | 7979.45 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110179E+10 | 7978.45 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85736422.94 | 3196.59 | 16-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28785889.70 | 3036.82 | 04-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2974675.39 | 2898.43 | 11-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5512367.80 | 2680.94 | 30-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183136E+09 | 3082.91 | 24-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766669E+09 | 7787.99 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323691E+10 | 7979.61 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584457E+10 | 7979.50 | 19-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267564E+11 | |||||||
Minimum of Months | 2974675.39 | 2680.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758172E+10 | 8005.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.878017E+10 | 7978.94 | 17-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642201E+10 | 8103.29 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288903E+10 | 7978.38 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124855E+10 | 7977.35 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103635E+09 | 3282.32 | 07-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31164307.37 | 2833.64 | 06-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3526796.79 | 2903.39 | 11-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7560668.45 | 3281.31 | 30-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224495E+09 | 4161.68 | 24-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107658E+10 | 7818.84 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381748E+10 | 7978.54 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677695E+10 | 7979.77 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313812E+11 | |||||||
Minimum of Months | 3526796.79 | 2833.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878017E+10 | 8103.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299322E+11 | 17175.00 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248061E+11 | 18043.23 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194310E+11 | 11340.24 | 01-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150791E+11 | 10848.71 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126586E+11 | 7816.17 | 02-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114986E+11 | 7639.18 | 10-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120525E+11 | 7488.29 | 07-JUL-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119196E+11 | 7666.67 | 26-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118049E+11 | 8865.21 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144745E+11 | 9033.82 | 27-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209095E+11 | 16825.35 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260905E+11 | 11342.57 | 14-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210657E+12 | |||||||
Minimum of Months | 0.114986E+11 | 7488.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.299322E+11 | 18043.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244334E+10 | 2405.58 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163144E+10 | 2405.99 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.909816E+09 | 2405.52 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384981E+09 | 2404.89 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42275334.27 | 2330.70 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15069470.35 | 801.02 | 15-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1075343.11 | 673.51 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1219399.55 | 718.90 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83346077.99 | 2365.55 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314558E+09 | 2390.03 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112446E+10 | 2405.66 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199387E+10 | 2405.74 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894544E+10 | |||||||
Minimum of Months | 1075343.11 | 673.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.244334E+10 | 2405.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279422E+10 | 2399.79 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192298E+10 | 2400.38 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106080E+10 | 2399.90 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430091E+09 | 2399.59 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49401471.85 | 2331.19 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16180104.23 | 811.93 | 15-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1072535.12 | 714.04 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1356166.41 | 722.32 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102341E+09 | 2367.10 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430177E+09 | 2396.50 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131437E+10 | 2400.53 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228822E+10 | 2399.96 | 31-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104112E+11 | |||||||
Minimum of Months | 1072535.12 | 714.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279422E+10 | 2400.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.797131E+10 | 10658.62 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497997E+10 | 10654.67 | 27-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256747E+10 | 10656.42 | 01-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117468E+10 | 10644.64 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75442319.83 | 4658.11 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17479372.37 | 4238.71 | 02-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2567032.23 | 2836.92 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5440925.16 | 3235.18 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140032E+09 | 6133.93 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.496507E+09 | 10326.62 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315184E+10 | 10656.39 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.628649E+10 | 10657.70 | 30-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268692E+11 | |||||||
Minimum of Months | 2567032.23 | 2836.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.797131E+10 | 10658.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120742E+11 | 18647.07 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997451E+10 | 19574.49 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286942E+10 | 7106.78 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259888E+10 | 8027.48 | 10-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.384499E+10 | 7835.80 | 04-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.487500E+10 | 8450.39 | 14-JUN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.611115E+10 | 8733.60 | 31-JUL-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627058E+10 | 8546.45 | 31-AUG-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457813E+10 | 8450.32 | 18-SEP-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248341E+10 | 8350.91 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448819E+10 | 18272.93 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.495696E+10 | 8249.67 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651254E+11 | |||||||
Minimum of Months | 0.248341E+10 | 7106.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120742E+11 | 19574.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116334E+11 | 19346.29 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951915E+10 | 20308.18 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224655E+10 | 6787.40 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209867E+10 | 7759.34 | 10-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341215E+10 | 7659.19 | 28-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.456966E+10 | 8346.77 | 14-JUN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587215E+10 | 8559.12 | 31-JUL-10:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.600466E+10 | 8453.93 | 31-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423749E+10 | 8346.71 | 18-SEP-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196830E+10 | 8236.06 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393346E+10 | 18958.22 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418899E+10 | 7778.26 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596846E+11 | |||||||
Minimum of Months | 0.196830E+10 | 6787.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116334E+11 | 20308.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.627582E+10 | 13980.91 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594556E+10 | 14671.55 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169612E+10 | 5651.68 | 06-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157054E+10 | 8840.62 | 16-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180324E+10 | 7104.80 | 31-MAY-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.312129E+10 | 9642.27 | 26-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.402182E+10 | 9803.61 | 07-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345881E+10 | 9586.47 | 04-AUG-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237471E+10 | 9803.56 | 11-SEP-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132272E+10 | 5011.10 | 02-OCT-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233509E+10 | 13702.05 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228094E+10 | 6635.45 | 10-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362066E+11 | |||||||
Minimum of Months | 0.132272E+10 | 5011.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.627582E+10 | 14671.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172029E+11 | 10919.38 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134351E+11 | 11477.05 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.988313E+10 | 7190.01 | 06-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.705059E+10 | 5772.54 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.528668E+10 | 4079.10 | 03-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.438429E+10 | 3596.31 | 03-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455875E+10 | 3515.05 | 10-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.474714E+10 | 3489.47 | 31-AUG-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.523647E+10 | 4572.59 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.697439E+10 | 4727.06 | 08-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107343E+11 | 10695.10 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140587E+11 | 7191.00 | 13-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103552E+12 | |||||||
Minimum of Months | 0.438429E+10 | 3489.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172029E+11 | 11477.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351388E+12 | 416523.84 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222828E+12 | 436299.76 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544881E+11 | 155090.19 | 05-MAR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106128E+11 | 73571.06 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.595162E+09 | 21982.78 | 03-MAY-21:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317810E+09 | 20783.88 | 06-JUN-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25003648.62 | 19037.65 | 24-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76153921.91 | 17442.03 | 17-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.492432E+09 | 22036.67 | 15-SEP-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796735E+09 | 33927.00 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857057E+11 | 408509.30 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173545E+12 | 221080.74 | 09-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.900871E+12 | |||||||
Minimum of Months | 25003648.62 | 17442.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351388E+12 | 436299.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316912E+11 | 39125.72 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193808E+11 | 40983.23 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494833E+10 | 12923.92 | 06-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811655E+09 | 5656.06 | 03-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31109.57 | 0.39 | 16-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25762.36 | 0.39 | 07-JUN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26940.99 | 0.39 | 21-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29611.72 | 0.39 | 24-AUG-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23899.58 | 0.39 | 11-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8164184.05 | 1126.92 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749999E+10 | 38373.04 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159374E+11 | 18782.93 | 09-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802777E+11 | |||||||
Minimum of Months | 23899.58 | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316912E+11 | 40983.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9663933.20 | 9663933.20 | 16672.99 | 12-JAN-16:02 | 16672.99 | 0.00 |
February | 0.00 | 0.00 | 0.144253E+09 | 0.143381E+09 | 17332.97 | 24-FEB-16:02 | 17332.97 | 0.00 |
March | 0.00 | 0.00 | 0.570067E+09 | 0.451983E+09 | 17341.22 | 28-MAR-15:01 | 17341.22 | 0.06 |
April | 0.00 | 0.00 | 0.252977E+10 | 0.179435E+10 | 19120.11 | 16-APR-08:62 | 14702.13 | 0.25 |
May | 0.00 | 0.00 | 0.426008E+10 | 0.240284E+10 | 19878.72 | 11-MAY-18:02 | 13943.70 | 0.60 |
June | 0.00 | 0.00 | 0.723259E+10 | 0.395814E+10 | 22069.88 | 26-JUN-08:62 | 13702.91 | 0.81 |
July | 0.00 | 0.00 | 0.911058E+10 | 0.489973E+10 | 21292.61 | 14-JUL-18:02 | 14132.88 | 0.89 |
August | 0.00 | 0.00 | 0.810286E+10 | 0.414180E+10 | 23757.42 | 03-AUG-08:61 | 12724.24 | 0.89 |
September | 0.00 | 0.00 | 0.495569E+10 | 0.290298E+10 | 19760.33 | 11-SEP-08:62 | 14121.36 | 0.62 |
October | 0.00 | 0.00 | 0.142900E+10 | 0.107275E+10 | 18203.41 | 02-OCT-15:01 | 15810.02 | 0.17 |
November | 0.00 | 0.00 | 0.316580E+09 | 0.206901E+09 | 17321.69 | 04-NOV-15:01 | 17321.69 | 0.08 |
December | 0.00 | 0.00 | 16110715.80 | 16110715.80 | 16624.94 | 02-DEC-16:01 | 16624.94 | 0.00 |
Annual Sum or Average | 0.386772E+11 | 0.220006E+11 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 9663933.20 | 9663933.20 | 16624.94 | 12724.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.911058E+10 | 0.489973E+10 | 23757.42 | 17341.22 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1350940.78 | 1350940.78 | 2656.21 | 12-JAN-19:04 | 2656.21 | 0.00 |
February | 0.00 | 0.00 | 49574147.57 | 49574147.57 | 16602.43 | 24-FEB-16:02 | 16602.43 | 0.00 |
March | 0.00 | 0.00 | 0.295245E+09 | 0.223509E+09 | 17072.23 | 25-MAR-15:01 | 17072.23 | 0.04 |
April | 0.00 | 0.00 | 0.203569E+10 | 0.142208E+10 | 18702.43 | 16-APR-08:62 | 14617.64 | 0.22 |
May | 0.00 | 0.00 | 0.392505E+10 | 0.217996E+10 | 19550.75 | 11-MAY-18:02 | 13741.54 | 0.58 |
June | 0.00 | 0.00 | 0.701710E+10 | 0.384083E+10 | 21686.28 | 26-JUN-08:62 | 13532.19 | 0.79 |
July | 0.00 | 0.00 | 0.873239E+10 | 0.467579E+10 | 21265.17 | 17-JUL-18:02 | 13767.11 | 0.87 |
August | 0.00 | 0.00 | 0.740510E+10 | 0.372469E+10 | 23461.25 | 03-AUG-08:61 | 12503.95 | 0.85 |
September | 0.00 | 0.00 | 0.392799E+10 | 0.218057E+10 | 19059.27 | 11-SEP-08:62 | 14037.24 | 0.56 |
October | 0.00 | 0.00 | 0.738907E+09 | 0.514661E+09 | 17671.94 | 02-OCT-15:01 | 15186.68 | 0.12 |
November | 0.00 | 0.00 | 0.135437E+09 | 78159584.87 | 17062.44 | 04-NOV-15:01 | 17062.44 | 0.05 |
December | 0.00 | 0.00 | 2000354.15 | 2000354.15 | 2706.65 | 01-DEC-16:03 | 2706.65 | 0.00 |
Annual Sum or Average | 0.342658E+11 | 0.188932E+11 | 0.34 | |||||
Minimum of Months | 0.00 | 0.00 | 1350940.78 | 1350940.78 | 2656.21 | 2656.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.873239E+10 | 0.467579E+10 | 23461.25 | 17072.23 | 0.87 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.356507E+09 | 0.356507E+09 | 14380.09 | 13-JAN-12:30 | 14380.09 | 0.00 |
February | 0.00 | 0.00 | 0.264277E+10 | 0.264277E+10 | 33287.86 | 08-FEB-13:40 | 33287.86 | 0.00 |
March | 0.00 | 0.00 | 0.718778E+10 | 0.669778E+10 | 39168.36 | 24-MAR-12:50 | 39168.36 | 0.04 |
April | 0.00 | 0.00 | 0.144409E+11 | 0.107074E+11 | 56417.85 | 16-APR-19:05 | 37006.86 | 0.19 |
May | 0.00 | 0.00 | 0.232175E+11 | 0.128711E+11 | 42331.06 | 31-MAY-19:10 | 29496.90 | 0.52 |
June | 0.00 | 0.00 | 0.343857E+11 | 0.159841E+11 | 52985.54 | 18-JUN-20:50 | 30703.44 | 0.85 |
July | 0.00 | 0.00 | 0.424971E+11 | 0.192870E+11 | 60555.39 | 25-JUL-21:00 | 29817.85 | 0.90 |
August | 0.00 | 0.00 | 0.433549E+11 | 0.211944E+11 | 54441.07 | 02-AUG-19:30 | 34670.33 | 0.90 |
September | 0.00 | 0.00 | 0.373449E+11 | 0.258868E+11 | 53801.10 | 17-SEP-13:20 | 41933.35 | 0.58 |
October | 0.00 | 0.00 | 0.254670E+11 | 0.233623E+11 | 58806.86 | 20-OCT-12:30 | 58806.86 | 0.13 |
November | 0.00 | 0.00 | 0.868390E+10 | 0.754607E+10 | 61388.57 | 04-NOV-12:20 | 61388.57 | 0.10 |
December | 0.00 | 0.00 | 0.249538E+10 | 0.249538E+10 | 42309.95 | 03-DEC-13:00 | 42309.95 | 0.00 |
Annual Sum or Average | 0.242074E+12 | 0.149032E+12 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 0.356507E+09 | 0.356507E+09 | 14380.09 | 14380.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.433549E+11 | 0.258868E+11 | 61388.57 | 61388.57 | 0.90 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.566043E+09 | 0.566043E+09 | 54927.63 | 01-JAN-09:02 | 54927.63 | 0.00 |
February | 0.00 | 0.00 | 0.229232E+10 | 0.229232E+10 | 90294.94 | 25-FEB-09:02 | 90294.94 | 0.00 |
March | 0.00 | 0.00 | 0.103624E+11 | 0.849607E+10 | 93891.57 | 25-MAR-18:02 | 93891.57 | 0.12 |
April | 0.00 | 0.00 | 0.249310E+11 | 0.188655E+11 | 106475.78 | 18-APR-18:02 | 87463.73 | 0.28 |
May | 0.00 | 0.00 | 0.493293E+11 | 0.320925E+11 | 109716.49 | 11-MAY-18:02 | 78427.22 | 0.60 |
June | 0.00 | 0.00 | 0.667973E+11 | 0.425844E+11 | 128745.64 | 26-JUN-08:62 | 75625.52 | 0.75 |
July | 0.00 | 0.00 | 0.767373E+11 | 0.469858E+11 | 126942.19 | 17-JUL-18:02 | 76610.79 | 0.75 |
August | 0.00 | 0.00 | 0.705773E+11 | 0.419438E+11 | 139960.80 | 03-AUG-08:61 | 69273.14 | 0.73 |
September | 0.00 | 0.00 | 0.449165E+11 | 0.297373E+11 | 107932.19 | 11-SEP-08:62 | 80802.13 | 0.59 |
October | 0.00 | 0.00 | 0.217649E+11 | 0.176045E+11 | 97113.33 | 02-OCT-15:01 | 84815.93 | 0.24 |
November | 0.00 | 0.00 | 0.100721E+11 | 0.703904E+10 | 92157.54 | 08-NOV-19:03 | 87965.99 | 0.17 |
December | 0.00 | 0.00 | 0.803017E+09 | 0.803017E+09 | 60736.40 | 02-DEC-09:01 | 60736.40 | 0.00 |
Annual Sum or Average | 0.379149E+12 | 0.249010E+12 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 0.566043E+09 | 0.566043E+09 | 54927.63 | 54927.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.767373E+11 | 0.469858E+11 | 139960.80 | 93891.57 | 0.75 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4945074.08 | 4945074.08 | 3845.13 | 12-JAN-09:03 | 3845.13 | 0.00 |
February | 0.00 | 0.00 | 87339784.17 | 87290101.33 | 15105.21 | 24-FEB-09:01 | 15105.21 | 0.00 |
March | 0.00 | 0.00 | 0.526881E+09 | 0.405730E+09 | 15650.49 | 28-MAR-15:01 | 15650.49 | 0.07 |
April | 0.00 | 0.00 | 0.212588E+10 | 0.141771E+10 | 17008.46 | 16-APR-08:62 | 13963.72 | 0.25 |
May | 0.00 | 0.00 | 0.454888E+10 | 0.257750E+10 | 17755.65 | 11-MAY-18:02 | 12292.35 | 0.66 |
June | 0.00 | 0.00 | 0.734374E+10 | 0.405193E+10 | 18487.76 | 14-JUN-08:62 | 11937.14 | 0.85 |
July | 0.00 | 0.00 | 0.886274E+10 | 0.471232E+10 | 19159.27 | 20-JUL-08:62 | 11632.07 | 0.93 |
August | 0.00 | 0.00 | 0.781092E+10 | 0.396505E+10 | 20042.66 | 31-AUG-18:02 | 12200.20 | 0.91 |
September | 0.00 | 0.00 | 0.498041E+10 | 0.291623E+10 | 17720.90 | 10-SEP-08:62 | 13359.98 | 0.65 |
October | 0.00 | 0.00 | 0.122928E+10 | 0.909263E+09 | 16130.59 | 02-OCT-15:01 | 13784.68 | 0.17 |
November | 0.00 | 0.00 | 0.277072E+09 | 0.177969E+09 | 15632.39 | 04-NOV-15:01 | 15632.39 | 0.08 |
December | 0.00 | 0.00 | 26064877.92 | 26064877.92 | 10415.98 | 03-DEC-09:02 | 10415.98 | 0.00 |
Annual Sum or Average | 0.378242E+11 | 0.212520E+11 | 0.38 | |||||
Minimum of Months | 0.00 | 0.00 | 4945074.08 | 4945074.08 | 3845.13 | 3845.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.886274E+10 | 0.471232E+10 | 20042.66 | 15650.49 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1016550.22 | 1016550.22 | 2934.12 | 13-JAN-19:04 | 2934.12 | 0.00 |
February | 0.00 | 0.00 | 21693340.36 | 21693340.36 | 14568.71 | 24-FEB-09:01 | 14568.71 | 0.00 |
March | 0.00 | 0.00 | 0.256946E+09 | 0.184916E+09 | 15228.15 | 28-MAR-08:62 | 15228.15 | 0.04 |
April | 0.00 | 0.00 | 0.165094E+10 | 0.106508E+10 | 16824.09 | 18-APR-18:02 | 13936.55 | 0.22 |
May | 0.00 | 0.00 | 0.418432E+10 | 0.235067E+10 | 17629.91 | 11-MAY-18:02 | 12228.42 | 0.62 |
June | 0.00 | 0.00 | 0.711193E+10 | 0.392466E+10 | 18307.74 | 30-JUN-08:61 | 13145.10 | 0.85 |
July | 0.00 | 0.00 | 0.847049E+10 | 0.449703E+10 | 19210.03 | 17-JUL-18:02 | 12649.34 | 0.93 |
August | 0.00 | 0.00 | 0.708219E+10 | 0.352634E+10 | 19527.77 | 31-AUG-08:62 | 10646.85 | 0.89 |
September | 0.00 | 0.00 | 0.389720E+10 | 0.214907E+10 | 17543.17 | 10-SEP-08:62 | 13301.74 | 0.60 |
October | 0.00 | 0.00 | 0.504619E+09 | 0.318378E+09 | 15693.47 | 02-OCT-15:01 | 13187.89 | 0.12 |
November | 0.00 | 0.00 | 70311320.68 | 34574407.04 | 9557.42 | 04-NOV-08:62 | 9557.42 | 0.05 |
December | 0.00 | 0.00 | 2214795.08 | 2214795.08 | 3271.55 | 02-DEC-09:03 | 3271.55 | 0.00 |
Annual Sum or Average | 0.332539E+11 | 0.180756E+11 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 1016550.22 | 1016550.22 | 2934.12 | 2934.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.847049E+10 | 0.449703E+10 | 19527.77 | 15228.15 | 0.93 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2214906.17 | 2214906.17 | 4340.93 | 12-JAN-16:02 | 4340.93 | 0.00 |
February | 0.00 | 0.00 | 36973949.82 | 36900287.54 | 4531.30 | 24-FEB-16:02 | 4531.30 | 0.00 |
March | 0.00 | 0.00 | 0.136434E+09 | 0.110868E+09 | 4533.39 | 28-MAR-15:01 | 4533.39 | 0.05 |
April | 0.00 | 0.00 | 0.717783E+09 | 0.524037E+09 | 5094.55 | 16-APR-08:62 | 3783.15 | 0.24 |
May | 0.00 | 0.00 | 0.124819E+10 | 0.737851E+09 | 5263.56 | 29-MAY-08:62 | 3799.42 | 0.61 |
June | 0.00 | 0.00 | 0.216974E+10 | 0.125830E+10 | 5850.90 | 26-JUN-08:62 | 3534.54 | 0.82 |
July | 0.00 | 0.00 | 0.273299E+10 | 0.155285E+10 | 5755.82 | 20-JUL-08:62 | 3275.09 | 0.91 |
August | 0.00 | 0.00 | 0.240895E+10 | 0.130667E+10 | 6307.63 | 03-AUG-08:61 | 3267.79 | 0.91 |
September | 0.00 | 0.00 | 0.143998E+10 | 0.904036E+09 | 5314.79 | 11-SEP-08:62 | 3639.13 | 0.61 |
October | 0.00 | 0.00 | 0.364463E+09 | 0.279135E+09 | 4760.02 | 02-OCT-15:01 | 4132.16 | 0.16 |
November | 0.00 | 0.00 | 73443802.35 | 53069663.45 | 4528.27 | 04-NOV-15:01 | 4528.27 | 0.06 |
December | 0.00 | 0.00 | 2952340.16 | 2952340.16 | 4316.51 | 02-DEC-16:01 | 4316.51 | 0.00 |
Annual Sum or Average | 0.113341E+11 | 0.676889E+10 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 2214906.17 | 2214906.17 | 4316.51 | 3267.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273299E+10 | 0.155285E+10 | 6307.63 | 4533.39 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 491728.22 | 491728.22 | 883.87 | 12-JAN-16:03 | 883.87 | 0.00 |
February | 0.00 | 0.00 | 10648003.45 | 10601921.20 | 4270.62 | 24-FEB-16:02 | 4270.62 | 0.00 |
March | 0.00 | 0.00 | 64194330.11 | 48554190.85 | 4461.51 | 24-MAR-18:01 | 4461.51 | 0.03 |
April | 0.00 | 0.00 | 0.576830E+09 | 0.413248E+09 | 5004.08 | 16-APR-08:62 | 3764.13 | 0.21 |
May | 0.00 | 0.00 | 0.115148E+10 | 0.675841E+09 | 5183.52 | 29-MAY-08:62 | 3731.93 | 0.58 |
June | 0.00 | 0.00 | 0.211088E+10 | 0.122391E+10 | 5746.81 | 26-JUN-08:62 | 3489.29 | 0.81 |
July | 0.00 | 0.00 | 0.263082E+10 | 0.149315E+10 | 5604.85 | 20-JUL-08:62 | 3153.15 | 0.91 |
August | 0.00 | 0.00 | 0.221779E+10 | 0.118493E+10 | 6226.90 | 03-AUG-08:61 | 3209.24 | 0.89 |
September | 0.00 | 0.00 | 0.115510E+10 | 0.688140E+09 | 5143.82 | 11-SEP-08:62 | 3614.86 | 0.56 |
October | 0.00 | 0.00 | 0.178700E+09 | 0.127891E+09 | 4667.93 | 02-OCT-15:01 | 4039.01 | 0.10 |
November | 0.00 | 0.00 | 27745851.10 | 18216461.49 | 4457.16 | 04-NOV-15:01 | 4457.16 | 0.03 |
December | 0.00 | 0.00 | 702853.01 | 702853.01 | 739.23 | 02-DEC-16:03 | 739.23 | 0.00 |
Annual Sum or Average | 0.101254E+11 | 0.588567E+10 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 491728.22 | 491728.22 | 739.23 | 739.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.263082E+10 | 0.149315E+10 | 6226.90 | 4461.51 | 0.91 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.605339E+09 | 0.605339E+09 | 17962.16 | 13-JAN-16:01 | 17962.16 | 0.00 |
February | 0.00 | 0.00 | 0.114345E+10 | 0.113438E+10 | 17969.74 | 24-FEB-16:02 | 17969.74 | 0.00 |
March | 0.00 | 0.00 | 0.202235E+10 | 0.173466E+10 | 17972.83 | 23-MAR-15:01 | 17972.83 | 0.11 |
April | 0.00 | 0.00 | 0.409414E+10 | 0.300985E+10 | 19946.74 | 16-APR-08:62 | 15068.70 | 0.29 |
May | 0.00 | 0.00 | 0.674847E+10 | 0.392388E+10 | 20573.74 | 29-MAY-18:02 | 15515.39 | 0.68 |
June | 0.00 | 0.00 | 0.103497E+11 | 0.601194E+10 | 24008.10 | 26-JUN-08:62 | 13635.83 | 0.85 |
July | 0.00 | 0.00 | 0.129244E+11 | 0.731946E+10 | 22968.28 | 20-JUL-08:62 | 12826.14 | 0.90 |
August | 0.00 | 0.00 | 0.127979E+11 | 0.736733E+10 | 25772.43 | 03-AUG-08:61 | 12617.44 | 0.90 |
September | 0.00 | 0.00 | 0.945863E+10 | 0.655700E+10 | 21084.34 | 11-SEP-08:62 | 14544.84 | 0.70 |
October | 0.00 | 0.00 | 0.528485E+10 | 0.452446E+10 | 18886.44 | 02-OCT-15:01 | 16396.83 | 0.28 |
November | 0.00 | 0.00 | 0.194549E+10 | 0.154638E+10 | 17959.02 | 04-NOV-15:01 | 17959.02 | 0.17 |
December | 0.00 | 0.00 | 0.119956E+10 | 0.119956E+10 | 17965.59 | 02-DEC-16:01 | 17965.59 | 0.00 |
Annual Sum or Average | 0.685744E+11 | 0.449342E+11 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 0.605339E+09 | 0.605339E+09 | 17959.02 | 12617.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129244E+11 | 0.736733E+10 | 25772.43 | 17972.83 | 0.90 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 211.60 | 211.60 | 0.45 | 12-JAN-19:04 | 0.45 | 0.00 |
February | 0.00 | 0.00 | 664.06 | 664.06 | 0.56 | 24-FEB-19:05 | 0.56 | 0.00 |
March | 0.00 | 0.00 | 0.111124E+11 | 0.111124E+11 | 190870.38 | 19-MAR-16:00 | 190870.38 | 0.02 |
April | 0.00 | 0.00 | 0.111495E+12 | 0.861502E+11 | 473943.59 | 16-APR-21:50 | 255517.97 | 0.17 |
May | 0.00 | 0.00 | 0.304031E+12 | 0.218328E+12 | 545747.01 | 30-MAY-09:30 | 253869.45 | 0.49 |
June | 0.00 | 0.00 | 0.703371E+12 | 0.453017E+12 | 635738.29 | 18-JUN-22:00 | 260972.77 | 0.81 |
July | 0.00 | 0.00 | 0.101431E+13 | 0.584779E+12 | 749196.57 | 26-JUL-19:00 | 326446.99 | 0.98 |
August | 0.00 | 0.00 | 0.889374E+12 | 0.522751E+12 | 745089.11 | 04-AUG-13:00 | 353630.44 | 0.92 |
September | 0.00 | 0.00 | 0.358204E+12 | 0.293823E+12 | 554077.30 | 11-SEP-22:55 | 247538.11 | 0.51 |
October | 0.00 | 0.00 | 0.347880E+11 | 0.344424E+11 | 276540.56 | 20-OCT-15:00 | 276540.56 | 0.07 |
November | 0.00 | 0.00 | 0.608886E+10 | 0.608886E+10 | 100836.91 | 03-NOV-14:00 | 100836.91 | 0.05 |
December | 0.00 | 0.00 | 183.28 | 183.28 | 0.43 | 04-DEC-19:04 | 0.43 | 0.00 |
Annual Sum or Average | 0.343278E+13 | 0.221049E+13 | 0.34 | |||||
Minimum of Months | 0.00 | 0.00 | 183.28 | 183.28 | 0.43 | 0.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101431E+13 | 0.584779E+12 | 749196.57 | 353630.44 | 0.98 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.508255E+09 | 0.508255E+09 | 14383.08 | 19-MAR-16:00 | 14383.08 | 0.01 |
April | 0.00 | 0.00 | 0.824908E+10 | 0.656204E+10 | 46188.78 | 16-APR-10:08 | 25661.30 | 0.14 |
May | 0.00 | 0.00 | 0.197730E+11 | 0.151498E+11 | 56501.34 | 29-MAY-14:00 | 27704.30 | 0.40 |
June | 0.00 | 0.00 | 0.568394E+11 | 0.378315E+11 | 64404.98 | 12-JUN-13:50 | 27210.91 | 0.74 |
July | 0.00 | 0.00 | 0.831602E+11 | 0.493807E+11 | 66044.57 | 27-JUL-00:10 | 24684.24 | 0.93 |
August | 0.00 | 0.00 | 0.712235E+11 | 0.432003E+11 | 71793.13 | 31-AUG-18:02 | 27636.67 | 0.86 |
September | 0.00 | 0.00 | 0.266698E+11 | 0.235580E+11 | 48659.26 | 11-SEP-08:62 | 25676.50 | 0.46 |
October | 0.00 | 0.00 | 0.189297E+10 | 0.189297E+10 | 26355.69 | 20-OCT-15:00 | 26355.69 | 0.04 |
November | 0.00 | 0.00 | 69740718.45 | 69740718.45 | 4334.28 | 03-NOV-14:00 | 4334.28 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.268386E+12 | 0.178153E+12 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.831602E+11 | 0.493807E+11 | 71793.13 | 27704.30 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31317.70 | 64825.44 | 31-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 31939.96 | 65221.09 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 31660.84 | 65093.99 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30384.17 | 63256.22 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28525.71 | 60298.96 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26499.46 | 56351.77 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24768.97 | 52645.92 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24029.86 | 50578.62 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24391.11 | 51785.01 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25831.92 | 55018.41 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27766.06 | 58906.31 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29749.30 | 62273.98 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 28049.20 | ||||
Minimum of Months | 0.00 | 0.00 | 24029.86 | 50578.62 | ||
Maximum of Months | 0.00 | 0.00 | 31939.96 | 65221.09 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 246338.08 | 773273.26 | 31-JAN-04:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 190150.36 | 813757.25 | 02-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 67034.75 | 278874.90 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 42975.29 | 233081.74 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 38689.77 | 116324.33 | 23-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 43620.05 | 120755.94 | 20-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 47376.46 | 114469.86 | 25-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 43796.00 | 119901.94 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35339.56 | 135548.09 | 08-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27812.45 | 118568.62 | 28-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 86723.22 | 744109.25 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 137184.66 | 406497.40 | 09-DEC-09:03 |
Annual Sum or Average | 0.00 | 83394.93 | ||||
Minimum of Months | 0.00 | 0.00 | 27812.45 | 114469.86 | ||
Maximum of Months | 0.00 | 0.00 | 246338.08 | 813757.25 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1012.97 | 30232.39 | 12-JAN-16:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3737.42 | 85898.73 | 25-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 14724.52 | 341729.13 | 25-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 70797.41 | 718300.76 | 18-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 164311.32 | 720166.81 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 357354.06 | 909777.77 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 483596.90 | 1030803.42 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 428022.72 | 1002274.91 | 04-AUG-08:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 198616.74 | 728924.81 | 06-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 39321.32 | 504238.62 | 20-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 12924.74 | 269735.66 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2440.51 | 67122.61 | 03-DEC-13:40 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 149128.15 | 0.00 | ||||
Minimum of Months | 1012.97 | 30232.39 | 0.00 | 0.00 | ||
Maximum of Months | 483596.90 | 1030803.42 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587767E+10 | 0.92 | 2194.47 | 01-JAN-09:02 | 0.92 |
February | 0.530887E+10 | 0.92 | 2194.47 | 01-FEB-00:04 | 0.93 |
March | 0.587767E+10 | 0.92 | 2194.47 | 01-MAR-03:00 | 0.92 |
April | 0.568807E+10 | 0.92 | 2194.47 | 01-APR-15:02 | 0.92 |
May | 0.587767E+10 | 0.91 | 2194.47 | 01-MAY-21:10 | 0.92 |
June | 0.568807E+10 | 0.91 | 2194.47 | 01-JUN-01:20 | 0.91 |
July | 0.587767E+10 | 0.91 | 2194.47 | 01-JUL-03:50 | 0.91 |
August | 0.587767E+10 | 0.91 | 2194.47 | 01-AUG-03:30 | 0.91 |
September | 0.568807E+10 | 0.91 | 2194.47 | 01-SEP-05:15 | 0.91 |
October | 0.587767E+10 | 0.92 | 2194.47 | 01-OCT-14:50 | 0.92 |
November | 0.568807E+10 | 0.92 | 2194.47 | 01-NOV-18:15 | 0.92 |
December | 0.587767E+10 | 0.92 | 2194.47 | 02-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.692049E+11 | 0.92 | |||
Minimum of Months | 0.530887E+10 | 0.91 | 2194.47 | 0.91 | |
Maximum of Months | 0.587767E+10 | 0.92 | 2194.47 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130993E+12 | 1.93 | 48907.04 | 01-JAN-00:05 | 1.93 |
February | 0.118316E+12 | 1.93 | 48907.04 | 01-FEB-00:01 | 1.94 |
March | 0.130993E+12 | 1.93 | 48907.04 | 01-MAR-00:05 | 1.93 |
April | 0.126767E+12 | 1.92 | 48907.04 | 01-APR-00:10 | 1.93 |
May | 0.130993E+12 | 1.91 | 48907.04 | 01-MAY-00:05 | 1.92 |
June | 0.126767E+12 | 1.91 | 48907.04 | 01-JUN-00:10 | 1.92 |
July | 0.130993E+12 | 1.91 | 48907.04 | 01-JUL-00:10 | 1.91 |
August | 0.130993E+12 | 1.91 | 48907.04 | 01-AUG-00:10 | 1.91 |
September | 0.126766E+12 | 1.92 | 48907.04 | 01-SEP-00:10 | 1.91 |
October | 0.130992E+12 | 1.92 | 48907.04 | 01-OCT-00:05 | 1.93 |
November | 0.126767E+12 | 1.93 | 48907.04 | 01-NOV-00:10 | 1.93 |
December | 0.130993E+12 | 1.93 | 48907.04 | 01-DEC-00:03 | 1.93 |
Annual Sum or Average | 0.154233E+13 | 1.92 | |||
Minimum of Months | 0.118316E+12 | 1.91 | 48907.04 | 1.91 | |
Maximum of Months | 0.130993E+12 | 1.93 | 48907.04 | 1.94 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.67 | 184.35 | 01-JAN-00:05 | 0.67 |
February | 0.445990E+09 | 0.67 | 184.35 | 01-FEB-00:01 | 0.68 |
March | 0.493775E+09 | 0.67 | 184.35 | 01-MAR-00:05 | 0.67 |
April | 0.477847E+09 | 0.67 | 184.35 | 01-APR-00:10 | 0.67 |
May | 0.493775E+09 | 0.67 | 184.35 | 01-MAY-00:05 | 0.67 |
June | 0.477847E+09 | 0.67 | 184.35 | 01-JUN-00:10 | 0.67 |
July | 0.493775E+09 | 0.67 | 184.35 | 01-JUL-00:10 | 0.67 |
August | 0.493775E+09 | 0.67 | 184.35 | 01-AUG-00:10 | 0.67 |
September | 0.477847E+09 | 0.67 | 184.35 | 01-SEP-00:10 | 0.67 |
October | 0.493775E+09 | 0.67 | 184.35 | 01-OCT-00:05 | 0.67 |
November | 0.477847E+09 | 0.67 | 184.35 | 01-NOV-00:10 | 0.67 |
December | 0.493775E+09 | 0.67 | 184.35 | 01-DEC-00:03 | 0.67 |
Annual Sum or Average | 0.581380E+10 | 0.67 | |||
Minimum of Months | 0.445990E+09 | 0.67 | 184.35 | 0.67 | |
Maximum of Months | 0.493775E+09 | 0.67 | 184.35 | 0.68 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.48 | 1474.84 | 01-JAN-07:10 | 0.67 |
February | 0.252728E+10 | 0.48 | 1474.84 | 01-FEB-07:03 | 0.68 |
March | 0.279806E+10 | 0.48 | 1474.84 | 01-MAR-07:05 | 0.67 |
April | 0.270780E+10 | 0.47 | 1474.84 | 01-APR-06:10 | 0.67 |
May | 0.279806E+10 | 0.47 | 1474.84 | 01-MAY-06:05 | 0.67 |
June | 0.270780E+10 | 0.47 | 1474.84 | 01-JUN-06:05 | 0.67 |
July | 0.279806E+10 | 0.47 | 1474.84 | 01-JUL-06:10 | 0.66 |
August | 0.279806E+10 | 0.47 | 1474.84 | 01-AUG-06:10 | 0.66 |
September | 0.270780E+10 | 0.47 | 1474.84 | 01-SEP-06:05 | 0.67 |
October | 0.279806E+10 | 0.47 | 1474.84 | 01-OCT-06:10 | 0.67 |
November | 0.270780E+10 | 0.47 | 1474.84 | 01-NOV-06:05 | 0.67 |
December | 0.279806E+10 | 0.48 | 1474.84 | 01-DEC-07:05 | 0.67 |
Annual Sum or Average | 0.329449E+11 | 0.47 | |||
Minimum of Months | 0.252728E+10 | 0.47 | 1474.84 | 0.66 | |
Maximum of Months | 0.279806E+10 | 0.48 | 1474.84 | 0.68 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144138E+10 | 1.27 | 2056.30 | 01-JAN-09:02 | 1.45 |
February | 0.117239E+10 | 1.18 | 2056.30 | 01-FEB-05:50 | 1.46 |
March | 0.595639E+09 | 1.09 | 2056.30 | 01-MAR-09:02 | 1.46 |
April | 0.553426E+09 | 1.13 | 2056.30 | 01-APR-08:62 | 1.45 |
May | 0.542477E+09 | 1.14 | 2056.30 | 01-MAY-15:02 | 1.45 |
June | 0.800311E+09 | 1.23 | 2056.30 | 01-JUN-08:62 | 1.44 |
July | 0.954267E+09 | 1.28 | 2056.30 | 01-JUL-08:61 | 1.44 |
August | 0.860169E+09 | 1.28 | 2056.30 | 01-AUG-08:62 | 1.44 |
September | 0.639631E+09 | 1.21 | 2056.30 | 01-SEP-15:02 | 1.45 |
October | 0.411802E+09 | 1.09 | 2056.30 | 01-OCT-15:02 | 1.45 |
November | 0.687274E+09 | 1.12 | 2056.30 | 03-NOV-15:01 | 1.45 |
December | 0.107397E+10 | 1.21 | 2056.30 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.973274E+10 | 1.19 | |||
Minimum of Months | 0.411802E+09 | 1.09 | 2056.30 | 1.44 | |
Maximum of Months | 0.144138E+10 | 1.28 | 2056.30 | 1.46 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168929E+10 | 1.37 | 2025.23 | 01-JAN-09:02 | 1.45 |
February | 0.133161E+10 | 1.25 | 2025.23 | 01-FEB-03:20 | 1.46 |
March | 0.628745E+09 | 1.10 | 2025.23 | 01-MAR-09:02 | 1.46 |
April | 0.518626E+09 | 1.10 | 2025.23 | 01-APR-08:62 | 1.45 |
May | 0.507845E+09 | 1.11 | 2025.23 | 02-MAY-15:01 | 1.45 |
June | 0.778129E+09 | 1.22 | 2025.23 | 01-JUN-08:62 | 1.44 |
July | 0.916067E+09 | 1.26 | 2025.23 | 01-JUL-08:61 | 1.44 |
August | 0.788530E+09 | 1.23 | 2025.23 | 01-AUG-08:62 | 1.44 |
September | 0.541334E+09 | 1.14 | 2025.23 | 01-SEP-15:02 | 1.45 |
October | 0.392946E+09 | 1.03 | 2025.23 | 01-OCT-15:02 | 1.45 |
November | 0.759575E+09 | 1.14 | 2025.23 | 03-NOV-15:01 | 1.45 |
December | 0.121122E+10 | 1.32 | 2025.23 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.100639E+11 | 1.19 | |||
Minimum of Months | 0.392946E+09 | 1.03 | 2025.23 | 1.44 | |
Maximum of Months | 0.168929E+10 | 1.37 | 2025.23 | 1.46 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.266063E+10 | 0.60 | 10690.88 | 19-JAN-05:00 | 1.46 |
February | 0.209783E+10 | 0.34 | 11279.64 | 02-FEB-03:50 | 1.47 |
March | 0.107643E+10 | 0.44 | 3615.90 | 24-MAR-12:50 | 1.45 |
April | 0.156038E+10 | 0.55 | 5352.60 | 15-APR-13:00 | 1.44 |
May | 0.253825E+10 | 1.04 | 3370.54 | 05-MAY-17:20 | 1.45 |
June | 0.334483E+10 | 1.22 | 5583.12 | 18-JUN-20:20 | 1.44 |
July | 0.385786E+10 | 1.30 | 5365.41 | 25-JUL-21:00 | 1.44 |
August | 0.396866E+10 | 1.31 | 3690.26 | 02-AUG-19:10 | 1.44 |
September | 0.389093E+10 | 1.14 | 5941.72 | 17-SEP-13:20 | 1.44 |
October | 0.292297E+10 | 0.87 | 6525.54 | 01-OCT-13:30 | 1.45 |
November | 0.142402E+10 | 0.49 | 6641.57 | 04-NOV-12:20 | 1.46 |
December | 0.149730E+10 | 0.51 | 5001.81 | 03-DEC-13:00 | 1.46 |
Annual Sum or Average | 0.308401E+11 | 0.82 | |||
Minimum of Months | 0.107643E+10 | 0.34 | 3370.54 | 1.44 | |
Maximum of Months | 0.396866E+10 | 1.31 | 11279.64 | 1.47 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.643575E+10 | 1.11 | 11440.55 | 01-JAN-16:02 | 1.46 |
February | 0.522293E+10 | 1.09 | 11440.55 | 01-FEB-02:00 | 1.46 |
March | 0.248953E+10 | 1.03 | 11440.55 | 01-MAR-09:02 | 1.46 |
April | 0.324546E+10 | 1.03 | 11440.55 | 01-APR-08:62 | 1.46 |
May | 0.533112E+10 | 1.03 | 11440.55 | 01-MAY-08:62 | 1.45 |
June | 0.700710E+10 | 1.08 | 11440.55 | 01-JUN-08:62 | 1.45 |
July | 0.767402E+10 | 1.08 | 11440.55 | 01-JUL-08:61 | 1.44 |
August | 0.704382E+10 | 1.05 | 11440.55 | 01-AUG-08:62 | 1.44 |
September | 0.497875E+10 | 1.04 | 11440.55 | 01-SEP-08:62 | 1.44 |
October | 0.286775E+10 | 1.03 | 11440.55 | 01-OCT-08:62 | 1.45 |
November | 0.301448E+10 | 1.03 | 11440.55 | 01-NOV-15:02 | 1.45 |
December | 0.357062E+10 | 1.05 | 11440.55 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.588813E+11 | 1.05 | |||
Minimum of Months | 0.248953E+10 | 1.03 | 11440.55 | 1.44 | |
Maximum of Months | 0.767402E+10 | 1.11 | 11440.55 | 1.46 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140432E+10 | 1.28 | 1851.64 | 01-JAN-09:02 | 1.45 |
February | 0.110362E+10 | 1.17 | 1851.64 | 01-FEB-03:10 | 1.46 |
March | 0.547588E+09 | 1.09 | 1851.64 | 01-MAR-09:02 | 1.46 |
April | 0.498566E+09 | 1.13 | 1851.64 | 01-APR-08:62 | 1.45 |
May | 0.557019E+09 | 1.21 | 1851.64 | 01-MAY-08:62 | 1.45 |
June | 0.785226E+09 | 1.29 | 1851.64 | 01-JUN-08:62 | 1.45 |
July | 0.900433E+09 | 1.35 | 1851.64 | 01-JUL-08:61 | 1.44 |
August | 0.796945E+09 | 1.32 | 1851.64 | 01-AUG-08:62 | 1.44 |
September | 0.620703E+09 | 1.25 | 1851.64 | 01-SEP-15:02 | 1.45 |
October | 0.371163E+09 | 1.10 | 1851.64 | 01-OCT-08:62 | 1.45 |
November | 0.651493E+09 | 1.12 | 1851.64 | 03-NOV-15:01 | 1.45 |
December | 0.101967E+10 | 1.21 | 1851.64 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.925674E+10 | 1.21 | |||
Minimum of Months | 0.371163E+09 | 1.09 | 1851.64 | 1.44 | |
Maximum of Months | 0.140432E+10 | 1.35 | 1851.64 | 1.46 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164005E+10 | 1.37 | 1841.43 | 01-JAN-09:02 | 1.45 |
February | 0.127307E+10 | 1.24 | 1841.43 | 01-FEB-01:25 | 1.46 |
March | 0.578230E+09 | 1.08 | 1841.43 | 01-MAR-09:02 | 1.46 |
April | 0.469760E+09 | 1.10 | 1841.43 | 01-APR-08:62 | 1.45 |
May | 0.517597E+09 | 1.16 | 1841.43 | 01-MAY-08:62 | 1.45 |
June | 0.763010E+09 | 1.29 | 1841.43 | 01-JUN-08:62 | 1.45 |
July | 0.859812E+09 | 1.34 | 1841.43 | 01-JUL-08:61 | 1.44 |
August | 0.725983E+09 | 1.30 | 1841.43 | 01-AUG-08:62 | 1.44 |
September | 0.513382E+09 | 1.18 | 1841.43 | 01-SEP-15:02 | 1.45 |
October | 0.345328E+09 | 1.03 | 1841.43 | 01-OCT-08:62 | 1.45 |
November | 0.718005E+09 | 1.15 | 1841.43 | 09-NOV-16:02 | 1.45 |
December | 0.116096E+10 | 1.34 | 1841.43 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.956520E+10 | 1.21 | |||
Minimum of Months | 0.345328E+09 | 1.03 | 1841.43 | 1.44 | |
Maximum of Months | 0.164005E+10 | 1.37 | 1841.43 | 1.46 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438389E+09 | 1.34 | 537.99 | 01-JAN-09:02 | 1.45 |
February | 0.309284E+09 | 1.24 | 537.99 | 01-FEB-09:02 | 1.46 |
March | 0.181423E+09 | 1.11 | 537.99 | 01-MAR-09:02 | 1.46 |
April | 0.168005E+09 | 1.16 | 537.99 | 01-APR-08:62 | 1.45 |
May | 0.160370E+09 | 1.19 | 537.99 | 01-MAY-15:02 | 1.45 |
June | 0.242621E+09 | 1.27 | 537.99 | 01-JUN-08:62 | 1.44 |
July | 0.291014E+09 | 1.32 | 537.99 | 01-JUL-08:61 | 1.44 |
August | 0.257148E+09 | 1.32 | 537.99 | 01-AUG-08:62 | 1.43 |
September | 0.188982E+09 | 1.23 | 537.99 | 01-SEP-15:02 | 1.45 |
October | 0.123932E+09 | 1.09 | 537.99 | 01-OCT-15:02 | 1.45 |
November | 0.211112E+09 | 1.16 | 537.99 | 03-NOV-15:01 | 1.45 |
December | 0.333839E+09 | 1.27 | 537.99 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.290612E+10 | 1.23 | |||
Minimum of Months | 0.123932E+09 | 1.09 | 537.99 | 1.43 | |
Maximum of Months | 0.438389E+09 | 1.34 | 537.99 | 1.46 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.505900E+09 | 1.41 | 529.63 | 01-JAN-09:02 | 1.45 |
February | 0.355458E+09 | 1.31 | 529.63 | 01-FEB-09:02 | 1.46 |
March | 0.193899E+09 | 1.17 | 529.63 | 01-MAR-09:02 | 1.46 |
April | 0.157205E+09 | 1.13 | 529.63 | 01-APR-08:62 | 1.45 |
May | 0.150240E+09 | 1.16 | 529.63 | 02-MAY-08:61 | 1.45 |
June | 0.236793E+09 | 1.26 | 529.63 | 01-JUN-08:62 | 1.44 |
July | 0.279820E+09 | 1.31 | 529.63 | 01-JUL-08:61 | 1.44 |
August | 0.236858E+09 | 1.29 | 529.63 | 01-AUG-08:62 | 1.43 |
September | 0.160759E+09 | 1.18 | 529.63 | 01-SEP-15:02 | 1.45 |
October | 0.120027E+09 | 1.03 | 529.63 | 01-OCT-15:02 | 1.45 |
November | 0.234880E+09 | 1.20 | 529.63 | 03-NOV-15:01 | 1.45 |
December | 0.371048E+09 | 1.38 | 529.63 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.300289E+10 | 1.24 | |||
Minimum of Months | 0.120027E+09 | 1.03 | 529.63 | 1.43 | |
Maximum of Months | 0.505900E+09 | 1.41 | 529.63 | 1.46 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137791E+10 | 1.19 | 2112.84 | 01-JAN-09:02 | 1.45 |
February | 0.100816E+10 | 1.14 | 2112.84 | 01-FEB-09:02 | 1.46 |
March | 0.687781E+09 | 1.16 | 2112.84 | 01-MAR-09:02 | 1.46 |
April | 0.706219E+09 | 1.17 | 2112.84 | 01-APR-15:02 | 1.46 |
May | 0.761713E+09 | 1.19 | 2112.84 | 01-MAY-15:02 | 1.45 |
June | 0.107340E+10 | 1.26 | 2112.84 | 01-JUN-08:62 | 1.45 |
July | 0.129096E+10 | 1.30 | 2112.84 | 01-JUL-08:61 | 1.44 |
August | 0.127501E+10 | 1.30 | 2112.84 | 01-AUG-08:62 | 1.43 |
September | 0.109398E+10 | 1.27 | 2112.84 | 01-SEP-15:02 | 1.45 |
October | 0.760495E+09 | 1.20 | 2112.84 | 01-OCT-08:62 | 1.45 |
November | 0.776958E+09 | 1.14 | 2112.84 | 01-NOV-15:02 | 1.45 |
December | 0.113482E+10 | 1.24 | 2112.84 | 01-DEC-09:01 | 1.45 |
Annual Sum or Average | 0.119474E+11 | 1.21 | |||
Minimum of Months | 0.687781E+09 | 1.14 | 2112.84 | 1.43 | |
Maximum of Months | 0.137791E+10 | 1.30 | 2112.84 | 1.46 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.630987E+10 | 0.567889E+10 | 4007.28 | 06-JAN-09:13 | 3606.55 | 3606.55 | 48.35 | 15.01 |
February | 0.441436E+10 | 0.397292E+10 | 4007.28 | 01-FEB-01:15 | 3606.55 | 3606.55 | 48.50 | 15.02 |
March | 0.275649E+10 | 0.248084E+10 | 2601.11 | 06-MAR-05:00 | 2341.00 | 2341.00 | 50.47 | 5.37 |
April | 0.178736E+10 | 0.160863E+10 | 2295.21 | 03-APR-08:62 | 2065.69 | 2065.69 | 46.69 | 4.19 |
May | 0.158481E+10 | 0.142633E+10 | 1583.44 | 09-MAY-15:04 | 1425.10 | 1425.10 | 49.29 | 2.40 |
June | 0.175614E+10 | 0.158053E+10 | 1562.71 | 20-JUN-08:05 | 1406.43 | 1406.43 | 47.75 | 2.36 |
July | 0.195240E+10 | 0.175716E+10 | 1497.15 | 25-JUL-08:05 | 1347.44 | 1347.44 | 47.72 | 2.23 |
August | 0.175093E+10 | 0.157584E+10 | 1497.82 | 21-AUG-08:05 | 1348.04 | 1348.04 | 47.15 | 2.23 |
September | 0.135179E+10 | 0.121661E+10 | 1595.97 | 08-SEP-08:05 | 1436.37 | 1436.37 | 46.63 | 2.43 |
October | 0.116805E+10 | 0.105124E+10 | 1619.54 | 21-OCT-15:04 | 1457.59 | 1457.59 | 49.43 | 2.47 |
November | 0.287566E+10 | 0.258809E+10 | 4001.86 | 26-NOV-07:45 | 3601.68 | 3601.68 | 48.56 | 14.99 |
December | 0.475798E+10 | 0.428218E+10 | 3101.91 | 09-DEC-09:02 | 2791.72 | 2791.72 | 50.05 | 9.66 |
Annual Sum or Average | 0.324658E+11 | 0.292193E+11 | ||||||
Minimum of Months | 0.116805E+10 | 0.105124E+10 | 1497.15 | 1347.44 | 1347.44 | 46.63 | 2.23 | |
Maximum of Months | 0.630987E+10 | 0.567889E+10 | 4007.28 | 3606.55 | 3606.55 | 50.47 | 15.02 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.126371E+09 | 0.113733E+09 | 1904.15 | 16-JAN-09:02 | 1713.74 | 1713.74 | 6.72 | 2.67 |
February | 0.475740E+09 | 0.428166E+09 | 3705.94 | 25-FEB-16:01 | 3335.34 | 3335.34 | 6.72 | 5.74 |
March | 0.173826E+10 | 0.156443E+10 | 6752.94 | 19-MAR-15:01 | 6077.64 | 6077.64 | 6.72 | 13.68 |
April | 0.473397E+10 | 0.426057E+10 | 8506.15 | 18-APR-15:02 | 7655.53 | 7655.53 | 6.72 | 25.32 |
May | 0.101147E+11 | 0.910320E+10 | 8604.34 | 29-MAY-18:40 | 7743.91 | 7743.91 | 6.72 | 26.64 |
June | 0.153411E+11 | 0.138070E+11 | 8890.72 | 11-JUN-15:02 | 8001.65 | 8001.65 | 6.72 | 30.80 |
July | 0.194020E+11 | 0.174618E+11 | 9206.09 | 26-JUL-18:03 | 8285.48 | 8285.48 | 6.72 | 34.63 |
August | 0.180445E+11 | 0.162401E+11 | 9051.84 | 04-AUG-16:00 | 8146.66 | 8146.66 | 6.72 | 32.91 |
September | 0.108887E+11 | 0.979986E+10 | 8626.46 | 11-SEP-19:40 | 7763.82 | 7763.82 | 6.72 | 26.95 |
October | 0.419858E+10 | 0.377872E+10 | 8376.97 | 20-OCT-15:50 | 7539.27 | 7539.27 | 6.72 | 23.76 |
November | 0.152455E+10 | 0.137209E+10 | 6586.17 | 05-NOV-15:01 | 5927.56 | 5927.56 | 6.72 | 13.07 |
December | 0.301755E+09 | 0.271580E+09 | 2578.35 | 03-DEC-09:02 | 2320.51 | 2320.51 | 6.72 | 3.74 |
Annual Sum or Average | 0.868903E+11 | 0.782012E+11 | ||||||
Minimum of Months | 0.126371E+09 | 0.113733E+09 | 1904.15 | 1713.74 | 1713.74 | 6.72 | 2.67 | |
Maximum of Months | 0.194020E+11 | 0.174618E+11 | 9206.09 | 8285.48 | 8285.48 | 6.72 | 34.63 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 46.98 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 47.02 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 47.83 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.16 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 49.99 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.33 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.54 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.05 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.18 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.14 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.25 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.23 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.98 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.33 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.117470E+10 | 0.105723E+10 | 3669.62 | 01-JAN-09:02 | 3302.65 | 3302.65 | 6.84 | 45.96 |
February | 0.242064E+10 | 0.217857E+10 | 3669.62 | 02-FEB-16:05 | 3302.65 | 3302.65 | 6.72 | 45.96 |
March | 0.537093E+10 | 0.483384E+10 | 3669.62 | 01-MAR-09:05 | 3302.65 | 3302.65 | 6.72 | 45.96 |
April | 0.723074E+10 | 0.650766E+10 | 3669.62 | 01-APR-00:10 | 3302.65 | 3302.65 | 6.73 | 45.96 |
May | 0.979916E+10 | 0.881924E+10 | 3669.62 | 01-MAY-00:05 | 3302.65 | 3302.65 | 6.80 | 45.96 |
June | 0.947917E+10 | 0.853125E+10 | 3669.62 | 01-JUN-00:10 | 3302.65 | 3302.65 | 7.31 | 45.96 |
July | 0.982870E+10 | 0.884583E+10 | 3669.62 | 01-JUL-00:10 | 3302.65 | 3302.65 | 8.74 | 45.96 |
August | 0.982870E+10 | 0.884583E+10 | 3669.62 | 01-AUG-00:10 | 3302.65 | 3302.65 | 9.45 | 45.96 |
September | 0.928816E+10 | 0.835935E+10 | 3669.62 | 01-SEP-00:10 | 3302.65 | 3302.65 | 8.28 | 45.96 |
October | 0.879130E+10 | 0.791217E+10 | 3669.62 | 01-OCT-00:05 | 3302.65 | 3302.65 | 6.75 | 45.96 |
November | 0.485594E+10 | 0.437035E+10 | 3669.62 | 01-NOV-00:10 | 3302.65 | 3302.65 | 6.73 | 45.96 |
December | 0.190864E+10 | 0.171778E+10 | 3669.62 | 01-DEC-07:05 | 3302.65 | 3302.65 | 6.72 | 45.96 |
Annual Sum or Average | 0.799768E+11 | 0.719791E+11 | ||||||
Minimum of Months | 0.117470E+10 | 0.105723E+10 | 3669.62 | 3302.65 | 3302.65 | 6.72 | 45.96 | |
Maximum of Months | 0.982870E+10 | 0.884583E+10 | 3669.62 | 3302.65 | 3302.65 | 9.45 | 45.96 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.98 | 59.90 | 31317.70 | 64825.44 | 31-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 47.02 | 59.78 | 31939.96 | 65221.09 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 47.83 | 59.80 | 31660.84 | 65093.99 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.16 | 58.50 | 30384.17 | 63256.22 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 49.99 | 58.29 | 28525.71 | 60298.96 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.33 | 59.97 | 26499.46 | 56351.77 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.54 | 58.45 | 24768.97 | 52645.92 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.05 | 58.69 | 24029.86 | 50578.62 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.18 | 58.80 | 24391.11 | 51785.01 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.14 | 58.85 | 25831.92 | 55018.41 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.25 | 59.66 | 27766.06 | 58906.31 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.23 | 59.01 | 29749.30 | 62273.98 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 28049.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.98 | 58.29 | 24029.86 | 50578.62 | ||
Maximum of Months | 0.00 | 0.00 | 52.33 | 59.97 | 31939.96 | 65221.09 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50.48 | 60.00 | 246338.08 | 773273.26 | 31-JAN-04:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 48.70 | 60.00 | 190150.36 | 813757.25 | 02-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.94 | 60.00 | 67034.75 | 278874.90 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.79 | 60.00 | 42975.29 | 233081.74 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 44.22 | 60.00 | 38689.77 | 116324.33 | 23-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 49.85 | 60.00 | 43620.05 | 120755.94 | 20-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 50.20 | 60.00 | 47376.46 | 114469.86 | 25-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 49.24 | 60.00 | 43796.00 | 119901.94 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 47.77 | 60.00 | 35339.56 | 135548.09 | 08-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 49.80 | 60.00 | 27812.45 | 118568.62 | 28-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 50.58 | 60.00 | 86723.22 | 744109.25 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.55 | 60.00 | 137184.66 | 406497.40 | 09-DEC-09:03 |
Annual Sum or Average | 0.00 | 83394.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.22 | 60.00 | 27812.45 | 114469.86 | ||
Maximum of Months | 0.00 | 0.00 | 52.55 | 60.00 | 246338.08 | 813757.25 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1012.97 | 30232.39 | 12-JAN-16:05 | 6.86 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3737.42 | 85898.73 | 25-FEB-16:01 | 7.15 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 14724.52 | 341729.13 | 25-MAR-15:01 | 8.47 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 70797.41 | 718300.76 | 18-APR-15:03 | 10.43 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 164311.32 | 720166.81 | 30-MAY-18:03 | 10.44 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 357354.06 | 909777.77 | 11-JUN-15:03 | 11.43 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 483596.90 | 1030803.42 | 26-JUL-18:03 | 12.05 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 428022.72 | 1002274.91 | 04-AUG-08:03 | 11.91 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 198616.74 | 728924.81 | 06-SEP-15:03 | 10.48 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 39321.32 | 504238.62 | 20-OCT-15:02 | 9.32 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 12924.74 | 269735.66 | 03-NOV-15:01 | 8.10 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2440.51 | 67122.61 | 03-DEC-13:40 | 7.05 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 149128.15 | 0.00 | ||||||
Minimum of Months | 1012.97 | 30232.39 | 6.86 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 483596.90 | 1030803.42 | 12.05 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 34.61 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.22 | 34.61 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.22 | 34.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.37 | 5.60 |
February | 0.06 | 3.25 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.42 | 5.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.37 | 5.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.29 | 4.01 |
February | 0.06 | 3.76 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.34 | 3.97 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.29 | 4.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.14 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.14 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.14 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.53 | 58.71 |
February | 0.31 | 54.33 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.84 | 57.12 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.53 | 58.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.09 | 189.25 |
February | 0.11 | 253.46 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 211.22 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.37 | 197.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.09 | 253.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.08 | 0.62 |
February | 2.08 | 0.70 |
March | 1.57 | 0.69 |
April | 1.22 | 0.70 |
May | 0.76 | 0.64 |
June | 2.08 | 0.55 |
July | 1.86 | 0.54 |
August | 1.46 | 0.57 |
September | 1.04 | 0.53 |
October | 0.68 | 0.81 |
November | 2.10 | 0.67 |
December | 4.93 | 0.66 |
Annual Sum or Average | 23.88 | 0.63 |
Minimum of Months | 0.68 | 0.53 |
Maximum of Months | 4.93 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.21 | 0.59 |
February | 1.75 | 0.69 |
March | 1.61 | 0.70 |
April | 1.29 | 0.77 |
May | 0.51 | 0.78 |
June | 1.96 | 0.56 |
July | 1.44 | 0.59 |
August | 1.18 | 0.63 |
September | 0.51 | 0.81 |
October | 0.29 | 0.81 |
November | 2.06 | 0.61 |
December | 4.81 | 0.63 |
Annual Sum or Average | 20.62 | 0.64 |
Minimum of Months | 0.29 | 0.56 |
Maximum of Months | 4.81 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.08 | 0.00 |
May | 0.04 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.29 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.90 | 0.57 |
February | 0.61 | 0.74 |
March | 0.06 | 0.81 |
April | 0.39 | 0.81 |
May | 0.93 | 0.75 |
June | 1.93 | 0.77 |
July | 2.72 | 0.77 |
August | 1.76 | 0.78 |
September | 1.22 | 0.80 |
October | 0.08 | 0.81 |
November | 0.17 | 0.62 |
December | 0.78 | 0.56 |
Annual Sum or Average | 12.56 | 0.73 |
Minimum of Months | 0.06 | 0.56 |
Maximum of Months | 2.72 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.64 | 0.67 |
February | 1.79 | 0.68 |
March | 1.29 | 0.61 |
April | 1.19 | 0.57 |
May | 2.92 | 0.55 |
June | 3.03 | 0.57 |
July | 2.68 | 0.65 |
August | 3.44 | 0.67 |
September | 1.64 | 0.58 |
October | 0.74 | 0.39 |
November | 1.89 | 0.66 |
December | 4.83 | 0.67 |
Annual Sum or Average | 29.08 | 0.62 |
Minimum of Months | 0.74 | 0.39 |
Maximum of Months | 4.83 | 0.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.74 | 0.60 |
February | 1.81 | 0.62 |
March | 1.21 | 0.66 |
April | 1.43 | 0.55 |
May | 3.17 | 0.54 |
June | 3.11 | 0.56 |
July | 3.06 | 0.63 |
August | 4.31 | 0.63 |
September | 2.87 | 0.59 |
October | 0.00 | 0.00 |
November | 2.32 | 0.62 |
December | 4.50 | 0.61 |
Annual Sum or Average | 31.51 | 0.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.50 | 0.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.39 | 0.55 |
February | 1.26 | 0.60 |
March | 1.07 | 0.72 |
April | 0.94 | 0.67 |
May | 0.83 | 0.57 |
June | 2.38 | 0.51 |
July | 2.12 | 0.40 |
August | 2.07 | 0.46 |
September | 1.25 | 0.51 |
October | 0.72 | 0.81 |
November | 1.72 | 0.63 |
December | 2.99 | 0.66 |
Annual Sum or Average | 19.75 | 0.57 |
Minimum of Months | 0.72 | 0.40 |
Maximum of Months | 2.99 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.24 | 0.56 |
February | 1.12 | 0.66 |
March | 0.90 | 0.75 |
April | 1.24 | 0.70 |
May | 0.72 | 0.60 |
June | 2.40 | 0.51 |
July | 2.10 | 0.44 |
August | 1.58 | 0.53 |
September | 0.62 | 0.61 |
October | 0.71 | 0.65 |
November | 1.35 | 0.62 |
December | 1.64 | 0.59 |
Annual Sum or Average | 15.63 | 0.58 |
Minimum of Months | 0.62 | 0.44 |
Maximum of Months | 2.40 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.36 | 0.62 |
February | 1.06 | 0.69 |
March | 1.37 | 0.67 |
April | 1.46 | 0.66 |
May | 1.50 | 0.65 |
June | 2.76 | 0.56 |
July | 2.31 | 0.55 |
August | 2.46 | 0.55 |
September | 1.51 | 0.54 |
October | 1.53 | 0.65 |
November | 1.28 | 0.63 |
December | 2.83 | 0.56 |
Annual Sum or Average | 22.43 | 0.60 |
Minimum of Months | 1.06 | 0.54 |
Maximum of Months | 2.83 | 0.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.41 | 97.69 |
February | 0.33 | 118.70 |
March | 0.08 | 174.93 |
April | 0.17 | 174.93 |
May | 0.08 | 174.93 |
June | 0.08 | 174.93 |
July | 0.00 | 0.00 |
August | 0.08 | 174.93 |
September | 0.08 | 174.93 |
October | 0.42 | 174.93 |
November | 0.25 | 174.93 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.99 | 149.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.42 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.32 | 97.10 |
February | 0.33 | 118.70 |
March | 0.08 | 174.93 |
April | 0.17 | 174.93 |
May | 0.08 | 174.93 |
June | 0.08 | 174.93 |
July | 0.00 | 0.00 |
August | 0.08 | 174.93 |
September | 0.08 | 174.93 |
October | 0.42 | 174.93 |
November | 0.25 | 174.93 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.91 | 151.88 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.42 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.17 | 5.56 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 5.56 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 5.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.545776E+12 | 0.00 | 211.60 | 0.130993E+12 | 0.00 | 0.00 |
February | 0.383570E+12 | 0.00 | 664.06 | 0.118316E+12 | 0.00 | 0.00 |
March | 0.156706E+12 | 0.00 | 0.111124E+11 | 0.130993E+12 | 0.00 | 0.00 |
April | 0.105101E+12 | 0.00 | 0.111495E+12 | 0.126767E+12 | 0.00 | 0.00 |
May | 0.104512E+12 | 0.00 | 0.304031E+12 | 0.130993E+12 | 0.00 | 0.00 |
June | 0.114536E+12 | 0.00 | 0.703371E+12 | 0.126767E+12 | 0.00 | 0.00 |
July | 0.128750E+12 | 0.00 | 0.101431E+13 | 0.130993E+12 | 0.00 | 0.00 |
August | 0.118959E+12 | 0.00 | 0.889374E+12 | 0.130993E+12 | 0.00 | 0.00 |
September | 0.916290E+11 | 0.00 | 0.358204E+12 | 0.126766E+12 | 0.00 | 0.00 |
October | 0.703982E+11 | 0.00 | 0.347880E+11 | 0.130992E+12 | 0.00 | 0.00 |
November | 0.190890E+12 | 0.00 | 0.608886E+10 | 0.126767E+12 | 0.00 | 0.00 |
December | 0.297592E+12 | 0.00 | 183.28 | 0.130993E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.230842E+13 | 0.00 | 0.343278E+13 | 0.154233E+13 | 0.00 | 0.00 |
Minimum of Months | 0.703982E+11 | 0.00 | 183.28 | 0.118316E+12 | 0.00 | 0.00 |
Maximum of Months | 0.545776E+12 | 0.00 | 0.101431E+13 | 0.130993E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.316912E+11 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
February | 0.193808E+11 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
March | 0.494833E+10 | 0.00 | 0.508255E+09 | 0.587767E+10 | 0.00 | 0.00 |
April | 0.811655E+09 | 0.00 | 0.824908E+10 | 0.568807E+10 | 0.00 | 0.00 |
May | 31109.57 | 0.00 | 0.197730E+11 | 0.587767E+10 | 0.00 | 0.00 |
June | 25762.36 | 0.00 | 0.568394E+11 | 0.568807E+10 | 0.00 | 0.00 |
July | 26940.99 | 0.00 | 0.831602E+11 | 0.587767E+10 | 0.00 | 0.00 |
August | 29611.72 | 0.00 | 0.712235E+11 | 0.587767E+10 | 0.00 | 0.00 |
September | 23899.58 | 0.00 | 0.266698E+11 | 0.568807E+10 | 0.00 | 0.00 |
October | 8164184.05 | 0.00 | 0.189297E+10 | 0.587767E+10 | 0.00 | 0.00 |
November | 0.749999E+10 | 0.00 | 69740718.45 | 0.568807E+10 | 0.00 | 0.00 |
December | 0.159374E+11 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.802777E+11 | 0.00 | 0.268386E+12 | 0.692049E+11 | 0.00 | 0.00 |
Minimum of Months | 23899.58 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.316912E+11 | 0.00 | 0.831602E+11 | 0.587767E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130993E+12 | 211.60 | 0.545776E+12 | 0.133127E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118316E+12 | 664.06 | 0.383570E+12 | 0.949013E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130993E+12 | 0.111124E+11 | 0.156706E+12 | 0.940610E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126767E+12 | 0.111495E+12 | 0.105101E+12 | 0.550996E+12 | 0.265517E+11 | 0.00 | 0.00 | 0.00 |
May | 0.130993E+12 | 0.304031E+12 | 0.104512E+12 | 0.135335E+12 | 0.362135E+11 | 0.00 | 0.00 | 0.00 |
June | 0.126767E+12 | 0.703371E+12 | 0.114536E+12 | 0.418200E+11 | 0.207716E+12 | 0.00 | 0.00 | 0.00 |
July | 0.130993E+12 | 0.101431E+13 | 0.128750E+12 | 0.352594E+10 | 0.278472E+12 | 0.00 | 0.00 | 0.00 |
August | 0.130993E+12 | 0.889374E+12 | 0.118959E+12 | 0.986134E+10 | 0.239745E+12 | 0.00 | 0.00 | 0.00 |
September | 0.126766E+12 | 0.358204E+12 | 0.916290E+11 | 0.152378E+12 | 0.598776E+11 | 0.00 | 0.00 | 0.00 |
October | 0.130992E+12 | 0.347880E+11 | 0.703982E+11 | 0.496435E+12 | 0.133527E+09 | 0.00 | 0.00 | 0.00 |
November | 0.126767E+12 | 0.608886E+10 | 0.190890E+12 | 0.859896E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130993E+12 | 183.28 | 0.297592E+12 | 0.136684E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154233E+13 | 0.343278E+13 | 0.230842E+13 | 0.683798E+13 | 0.848710E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118316E+12 | 183.28 | 0.703982E+11 | 0.352594E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130993E+12 | 0.101431E+13 | 0.545776E+12 | 0.136684E+13 | 0.278472E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587767E+10 | 0.00 | 0.316912E+11 | 0.135583E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.00 | 0.193808E+11 | 0.987259E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.508255E+09 | 0.494833E+10 | 0.980235E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.824908E+10 | 0.811655E+09 | 0.595913E+11 | 0.202844E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.197730E+11 | 31109.57 | 0.171797E+11 | 0.195927E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.568394E+11 | 25762.36 | 0.596072E+10 | 0.158074E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.831602E+11 | 26940.99 | 0.814792E+09 | 0.198586E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.712235E+11 | 29611.72 | 0.193503E+10 | 0.172218E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.266698E+11 | 23899.58 | 0.184212E+11 | 0.460750E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.189297E+10 | 8164184.05 | 0.549673E+11 | 132511.93 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 69740718.45 | 0.749999E+10 | 0.904155E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.00 | 0.159374E+11 | 0.138899E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.268386E+12 | 0.802777E+11 | 0.720517E+12 | 0.614830E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530887E+10 | 0.00 | 23899.58 | 0.814792E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.831602E+11 | 0.316912E+11 | 0.138899E+12 | 0.198586E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.130993E+12 | 0.545776E+12 | 211.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118316E+12 | 0.383570E+12 | 664.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130993E+12 | 0.156706E+12 | 0.111124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126767E+12 | 0.105101E+12 | 0.111495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130993E+12 | 0.104512E+12 | 0.304031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126767E+12 | 0.114536E+12 | 0.703371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130993E+12 | 0.128750E+12 | 0.101431E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130993E+12 | 0.118959E+12 | 0.889374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126766E+12 | 0.916290E+11 | 0.358204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130992E+12 | 0.703982E+11 | 0.347880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126767E+12 | 0.190890E+12 | 0.608886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130993E+12 | 0.297592E+12 | 183.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154233E+13 | 0.230842E+13 | 0.343278E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118316E+12 | 0.703982E+11 | 183.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130993E+12 | 0.545776E+12 | 0.101431E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.587767E+10 | 0.316912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.193808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.494833E+10 | 0.508255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.811655E+09 | 0.824908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 31109.57 | 0.197730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 25762.36 | 0.568394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 26940.99 | 0.831602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 29611.72 | 0.712235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 23899.58 | 0.266698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 8164184.05 | 0.189297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.749999E+10 | 69740718.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.159374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.802777E+11 | 0.268386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530887E+10 | 23899.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.316912E+11 | 0.831602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.746854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496796E+11 | 0.00 | 0.00 | 2.00 |
February | 0.549738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441418E+11 | 0.00 | 0.00 | 1.99 |
March | 0.788366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216038E+09 | 0.00 | 0.00 | 2.02 |
April | 0.624343E+11 | 0.00 | 0.245047E+10 | 0.00 | 0.277358E+09 | 0.235233E+10 | 0.00 | 13335936.22 | 2.01 |
May | 0.483186E+11 | 0.00 | 0.363640E+10 | 0.00 | 0.102402E+10 | 0.192808E+10 | 0.00 | 21789959.24 | 2.02 |
June | 0.250117E+11 | 0.00 | 0.123302E+11 | 0.00 | 0.133737E+11 | 0.498727E+09 | 0.00 | 35971830.87 | 2.02 |
July | 0.916292E+10 | 0.00 | 0.925144E+10 | 0.00 | 0.320628E+11 | 18109237.85 | 0.00 | 23548858.77 | 2.02 |
August | 0.160266E+11 | 0.00 | 0.121728E+10 | 0.00 | 0.328897E+11 | 7447381.62 | 0.00 | 5974643.56 | 2.02 |
September | 0.436702E+11 | 0.00 | 0.102522E+09 | 0.00 | 0.573603E+10 | 3940814.48 | 0.00 | 610323.39 | 2.02 |
October | 0.719090E+11 | 0.00 | 0.00 | 0.00 | 3060978.19 | 0.00 | 0.00 | 0.00 | 2.01 |
November | 0.763466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646900E+10 | 0.00 | 0.00 | 2.01 |
December | 0.935293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
Annual Sum or Average | 0.654905E+12 | 0.00 | 0.289883E+11 | 0.00 | 0.853667E+11 | 0.105315E+12 | 0.00 | 0.101232E+09 | 2.01 |
Minimum of Months | 0.916292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
Maximum of Months | 0.935293E+11 | 0.00 | 0.123302E+11 | 0.00 | 0.328897E+11 | 0.496796E+11 | 0.00 | 35971830.87 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145862E+10 | 0.00 | 0.00 | 284.02 | 0.00 | 0.138659E+11 | 5374448.66 | 0.00 | 4.46 |
February | 0.239463E+10 | 0.00 | 0.00 | 29983.35 | 0.00 | 0.975525E+10 | 67631144.53 | 0.00 | 4.47 |
March | 0.501532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472916E+10 | 0.00 | 0.00 | 4.51 |
April | 0.563968E+10 | 17210756.63 | 0.00 | 0.00 | 0.320681E+09 | 0.234629E+10 | 0.00 | 0.00 | 4.50 |
May | 0.612984E+10 | 0.00 | 0.00 | 0.00 | 0.577155E+09 | 63836460.71 | 0.00 | 0.00 | 4.52 |
June | 0.314455E+10 | 0.00 | 0.00 | 0.00 | 0.317285E+10 | 0.00 | 0.00 | 0.00 | 4.53 |
July | 0.113170E+10 | 0.00 | 0.00 | 0.00 | 0.509552E+10 | 0.00 | 0.00 | 0.00 | 4.53 |
August | 0.197645E+10 | 0.00 | 0.00 | 0.00 | 0.420495E+10 | 0.00 | 0.00 | 0.00 | 4.53 |
September | 0.517774E+10 | 0.103033E+09 | 0.00 | 239.60 | 0.616735E+09 | 0.205626E+09 | 149468.50 | 0.00 | 4.52 |
October | 0.763617E+10 | 360280.97 | 0.00 | 130685.84 | 17032.29 | 0.983118E+09 | 0.244488E+09 | 0.00 | 4.50 |
November | 0.455335E+10 | 0.00 | 0.00 | 77901.30 | 0.00 | 0.555302E+10 | 0.101868E+09 | 0.00 | 4.50 |
December | 0.201404E+10 | 0.00 | 0.00 | 19595.04 | 0.00 | 0.946901E+10 | 45875613.92 | 0.00 | 4.47 |
Annual Sum or Average | 0.462721E+11 | 0.120604E+09 | 0.00 | 258689.15 | 0.139879E+11 | 0.469712E+11 | 0.465387E+09 | 0.00 | 4.50 |
Minimum of Months | 0.113170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
Maximum of Months | 0.763617E+10 | 0.103033E+09 | 0.00 | 130685.84 | 0.509552E+10 | 0.138659E+11 | 0.244488E+09 | 0.00 | 4.53 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.721817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413745E+10 | 0.00 | 0.00 | 2.86 |
February | 0.544698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360315E+10 | 0.00 | 0.00 | 2.85 |
March | 0.721821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
April | 0.591559E+10 | 0.00 | 0.00 | 0.00 | 0.250293E+09 | 0.00 | 0.00 | 0.00 | 2.88 |
May | 0.458796E+10 | 0.00 | 0.00 | 0.00 | 0.427527E+09 | 0.00 | 0.00 | 0.00 | 2.89 |
June | 0.232932E+10 | 0.00 | 0.00 | 0.00 | 0.235028E+10 | 0.00 | 0.00 | 0.00 | 2.90 |
July | 0.838309E+09 | 0.00 | 0.00 | 0.00 | 0.377450E+10 | 0.00 | 0.00 | 0.00 | 2.90 |
August | 0.146405E+10 | 0.00 | 0.00 | 0.00 | 0.311482E+10 | 0.00 | 0.00 | 0.00 | 2.90 |
September | 0.398783E+10 | 0.00 | 0.00 | 0.00 | 0.533167E+09 | 0.00 | 0.00 | 0.00 | 2.89 |
October | 0.656593E+10 | 0.00 | 0.00 | 0.00 | 279494.40 | 0.00 | 0.00 | 0.00 | 2.88 |
November | 0.691363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648172E+09 | 0.00 | 0.00 | 2.88 |
December | 0.854005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
Annual Sum or Average | 0.610260E+11 | 0.00 | 0.00 | 0.00 | 0.104509E+11 | 0.838877E+10 | 0.00 | 0.00 | 2.88 |
Minimum of Months | 0.838309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
Maximum of Months | 0.854005E+10 | 0.00 | 0.00 | 0.00 | 0.377450E+10 | 0.413745E+10 | 0.00 | 0.00 | 2.90 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877046E+10 | 0.00 | 0.00 | 1.53 |
February | 0.520149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505531E+10 | 0.00 | 0.00 | 1.53 |
March | 0.780390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376727E+09 | 0.00 | 0.00 | 1.55 |
April | 0.668491E+10 | 0.00 | 0.00 | 0.00 | 0.283665E+09 | 19429456.08 | 0.00 | 0.00 | 1.54 |
May | 0.519969E+10 | 0.00 | 0.00 | 0.00 | 0.484531E+09 | 0.00 | 0.00 | 0.00 | 1.55 |
June | 0.263990E+10 | 0.00 | 0.00 | 0.00 | 0.266365E+10 | 0.00 | 0.00 | 0.00 | 1.55 |
July | 0.950083E+09 | 0.00 | 0.00 | 0.00 | 0.427777E+10 | 0.00 | 0.00 | 0.00 | 1.55 |
August | 0.165926E+10 | 0.00 | 0.00 | 0.00 | 0.353012E+10 | 0.00 | 0.00 | 0.00 | 1.55 |
September | 0.451954E+10 | 0.00 | 0.00 | 0.00 | 0.604256E+09 | 0.00 | 0.00 | 0.00 | 1.55 |
October | 0.744138E+10 | 0.00 | 0.00 | 0.00 | 316760.06 | 0.00 | 0.00 | 0.00 | 1.54 |
November | 0.676987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180016E+10 | 0.00 | 0.00 | 1.54 |
December | 0.705488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262383E+10 | 0.00 | 0.00 | 1.53 |
Annual Sum or Average | 0.600241E+11 | 0.00 | 0.00 | 0.00 | 0.118443E+11 | 0.186459E+11 | 0.00 | 0.00 | 1.54 |
Minimum of Months | 0.950083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
Maximum of Months | 0.780390E+10 | 0.00 | 0.00 | 0.00 | 0.427777E+10 | 0.877046E+10 | 0.00 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76700202.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524177E+10 | 0.00 | 0.00 | 1.10 |
February | 0.328830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390985E+10 | 0.00 | 0.00 | 1.09 |
March | 0.133226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204843E+10 | 0.00 | 0.00 | 1.11 |
April | 0.198421E+10 | 0.00 | 0.00 | 0.00 | 0.117226E+09 | 0.786390E+09 | 0.00 | 0.00 | 1.10 |
May | 0.213471E+10 | 0.00 | 0.00 | 0.00 | 0.200235E+09 | 14081158.28 | 0.00 | 0.00 | 1.11 |
June | 0.109095E+10 | 0.00 | 0.00 | 0.00 | 0.110077E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
July | 0.392626E+09 | 0.00 | 0.00 | 0.00 | 0.176781E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 0.685696E+09 | 0.00 | 0.00 | 0.00 | 0.145884E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.182447E+10 | 0.00 | 0.00 | 0.00 | 0.249712E+09 | 43256541.12 | 0.00 | 0.00 | 1.11 |
October | 0.279384E+10 | 0.00 | 0.00 | 0.00 | 130902.65 | 0.281350E+09 | 0.00 | 0.00 | 1.10 |
November | 0.134939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219222E+10 | 0.00 | 0.00 | 1.10 |
December | 0.147460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385232E+10 | 0.00 | 0.00 | 1.10 |
Annual Sum or Average | 0.141411E+11 | 0.00 | 0.00 | 0.00 | 0.489472E+10 | 0.183697E+11 | 0.00 | 0.00 | 1.10 |
Minimum of Months | 76700202.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
Maximum of Months | 0.279384E+10 | 0.00 | 0.00 | 0.00 | 0.176781E+10 | 0.524177E+10 | 0.00 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.584077E+10 | 0.00 | 0.00 | 54148728.54 | 0.00 | 0.406145E+11 | 0.109146E+12 | 0.00 | 38.89 |
February | 0.277880E+10 | 0.00 | 0.00 | 50588543.95 | 0.00 | 0.395228E+11 | 0.817196E+11 | 0.00 | 38.93 |
March | 0.174330E+10 | 0.00 | 0.00 | 67098092.85 | 0.00 | 0.00 | 0.972265E+11 | 0.00 | 39.47 |
April | 0.108538E+10 | 0.324603E+10 | 0.00 | 60517174.23 | 0.181947E+09 | 0.00 | 0.799955E+11 | 0.00 | 39.31 |
May | 0.936336E+09 | 0.559971E+10 | 0.00 | 55792112.38 | 0.255651E+09 | 0.00 | 0.618998E+11 | 0.00 | 39.45 |
June | 0.368051E+09 | 0.309043E+11 | 0.00 | 28322882.70 | 0.128487E+10 | 0.00 | 0.315224E+11 | 0.00 | 39.45 |
July | 87450471.33 | 0.499139E+11 | 0.00 | 12068346.10 | 0.178123E+10 | 0.00 | 0.113819E+11 | 0.00 | 39.42 |
August | 95864671.19 | 0.411865E+11 | 0.00 | 21155813.44 | 0.147362E+10 | 0.00 | 0.199344E+11 | 0.00 | 39.44 |
September | 0.597026E+09 | 0.695247E+10 | 0.00 | 49291687.45 | 0.349724E+09 | 0.00 | 0.540446E+11 | 0.00 | 39.40 |
October | 0.992895E+09 | 3655124.48 | 0.00 | 67766651.34 | 172796.04 | 0.00 | 0.890233E+11 | 0.00 | 39.31 |
November | 0.244959E+10 | 0.00 | 0.00 | 63031690.78 | 0.00 | 0.566773E+10 | 0.955344E+11 | 0.00 | 39.29 |
December | 0.352889E+10 | 0.00 | 0.00 | 63261264.96 | 0.00 | 0.00 | 0.113531E+12 | 0.00 | 39.05 |
Annual Sum or Average | 0.205044E+11 | 0.137807E+12 | 0.00 | 0.593043E+09 | 0.532722E+10 | 0.858051E+11 | 0.844959E+12 | 0.00 | 39.29 |
Minimum of Months | 87450471.33 | 0.00 | 0.00 | 12068346.10 | 0.00 | 0.00 | 0.113819E+11 | 0.00 | 38.89 |
Maximum of Months | 0.584077E+10 | 0.499139E+11 | 0.00 | 67766651.34 | 0.178123E+10 | 0.406145E+11 | 0.113531E+12 | 0.00 | 39.47 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387731E+11 | 0.00 | 0.00 | 8399.28 | 0.00 | 0.276069E+11 | 46396421.40 | 0.00 | 6.87 |
February | 0.322793E+11 | 0.00 | 0.00 | 155143.11 | 0.00 | 0.201962E+11 | 0.464368E+09 | 0.00 | 6.88 |
March | 0.415409E+11 | 0.00 | 0.00 | 3938.65 | 0.00 | 0.636162E+09 | 46894113.34 | 0.00 | 6.95 |
April | 0.345420E+11 | 87851277.60 | 0.00 | 0.00 | 0.137627E+10 | 62110744.72 | 0.00 | 0.00 | 6.93 |
May | 0.268380E+11 | 0.00 | 0.00 | 0.00 | 0.250088E+10 | 0.00 | 0.00 | 0.00 | 6.96 |
June | 0.136257E+11 | 37952046.75 | 0.00 | 0.00 | 0.137104E+11 | 0.00 | 0.00 | 0.00 | 6.97 |
July | 0.490381E+10 | 59638680.27 | 0.00 | 0.00 | 0.220199E+11 | 0.00 | 0.00 | 0.00 | 6.97 |
August | 0.855611E+10 | 57675852.06 | 0.00 | 13.23 | 0.181629E+11 | 0.00 | 8060678.89 | 0.00 | 6.97 |
September | 0.231474E+11 | 0.386854E+09 | 0.00 | 7654.32 | 0.273198E+10 | 0.00 | 0.179991E+09 | 0.00 | 6.95 |
October | 0.368822E+11 | 1190471.43 | 0.00 | 494759.02 | 444471.49 | 0.00 | 0.152565E+10 | 0.00 | 6.93 |
November | 0.389957E+11 | 0.00 | 0.00 | 313118.12 | 0.00 | 0.460343E+10 | 0.634350E+09 | 0.00 | 6.92 |
December | 0.408086E+11 | 0.00 | 0.00 | 134922.92 | 0.00 | 0.866321E+10 | 0.484292E+09 | 0.00 | 6.88 |
Annual Sum or Average | 0.340893E+12 | 0.631163E+09 | 0.00 | 1117948.64 | 0.605027E+11 | 0.617680E+11 | 0.339000E+10 | 0.00 | 6.93 |
Minimum of Months | 0.490381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
Maximum of Months | 0.415409E+11 | 0.386854E+09 | 0.00 | 494759.02 | 0.220199E+11 | 0.276069E+11 | 0.152565E+10 | 0.00 | 6.97 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737331E+11 | 0.00 | 0.00 | 3.32 |
February | 0.108429E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688538E+11 | 0.00 | 0.00 | 3.32 |
March | 0.141398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
April | 0.115881E+12 | 0.00 | 0.00 | 0.00 | 0.490300E+10 | 0.00 | 0.00 | 0.00 | 3.35 |
May | 0.898738E+11 | 0.00 | 0.00 | 0.00 | 0.837485E+10 | 0.00 | 0.00 | 0.00 | 3.37 |
June | 0.456292E+11 | 0.00 | 0.00 | 0.00 | 0.460398E+11 | 0.00 | 0.00 | 0.00 | 3.37 |
July | 0.164217E+11 | 0.00 | 0.00 | 0.00 | 0.739389E+11 | 0.00 | 0.00 | 0.00 | 3.37 |
August | 0.286793E+11 | 0.00 | 0.00 | 0.00 | 0.610162E+11 | 0.00 | 0.00 | 0.00 | 3.37 |
September | 0.781178E+11 | 0.00 | 0.00 | 0.00 | 0.104442E+11 | 0.00 | 0.00 | 0.00 | 3.36 |
October | 0.128620E+12 | 0.00 | 0.00 | 0.00 | 5475025.72 | 0.00 | 0.00 | 0.00 | 3.35 |
November | 0.136705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114237E+11 | 0.00 | 0.00 | 3.35 |
December | 0.167291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Annual Sum or Average | 0.120576E+13 | 0.00 | 0.00 | 0.00 | 0.204722E+12 | 0.154011E+12 | 0.00 | 0.00 | 3.35 |
Minimum of Months | 0.164217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
Maximum of Months | 0.167291E+12 | 0.00 | 0.00 | 0.00 | 0.739389E+11 | 0.737331E+11 | 0.00 | 0.00 | 3.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303303E+09 | 0.00 | 0.00 | 79994.01 | 0.00 | 0.257061E+10 | 6697801.95 | 0.00 | 0.47 |
February | 0.297169E+09 | 0.00 | 0.00 | 626065.95 | 0.00 | 0.217677E+10 | 78177463.37 | 0.00 | 0.47 |
March | 0.414405E+09 | 0.00 | 0.00 | 2185535.80 | 0.00 | 0.989817E+09 | 0.326619E+09 | 0.00 | 0.47 |
April | 0.334690E+09 | 40202932.45 | 1626.86 | 5256906.96 | 2315775.99 | 0.542920E+09 | 0.597414E+09 | 1586.48 | 0.47 |
May | 0.243062E+09 | 60889207.77 | 65752.88 | 8435421.29 | 8841153.14 | 88297025.82 | 0.876244E+09 | 2362.69 | 0.47 |
June | 0.113413E+09 | 0.406126E+09 | 225660.92 | 5265220.73 | 34393154.58 | 33734195.08 | 0.437189E+09 | 18272.07 | 0.48 |
July | 21260445.24 | 0.655106E+09 | 463903.35 | 3421543.40 | 55855308.80 | 359353.82 | 0.218381E+09 | 22558.50 | 0.48 |
August | 27956790.38 | 0.497881E+09 | 359747.03 | 4618551.62 | 50442834.87 | 365077.59 | 0.350961E+09 | 18798.64 | 0.48 |
September | 0.200976E+09 | 87649530.14 | 0.00 | 6532803.65 | 4967200.16 | 0.151899E+09 | 0.693119E+09 | 0.00 | 0.47 |
October | 0.397036E+09 | 0.00 | 0.00 | 4579417.09 | 0.00 | 0.520638E+09 | 0.763483E+09 | 0.00 | 0.47 |
November | 0.381243E+09 | 0.00 | 0.00 | 1251953.75 | 0.00 | 0.116260E+10 | 0.282804E+09 | 0.00 | 0.47 |
December | 0.301566E+09 | 0.00 | 0.00 | 158413.06 | 0.00 | 0.160520E+10 | 14689669.58 | 0.00 | 0.47 |
Annual Sum or Average | 0.303608E+10 | 0.174785E+10 | 1116691.04 | 42411827.31 | 0.156815E+09 | 0.984322E+10 | 0.464578E+10 | 63578.39 | 0.47 |
Minimum of Months | 21260445.24 | 0.00 | 0.00 | 79994.01 | 0.00 | 359353.82 | 6697801.95 | 0.00 | 0.47 |
Maximum of Months | 0.414405E+09 | 0.655106E+09 | 463903.35 | 8435421.29 | 55855308.80 | 0.257061E+10 | 0.876244E+09 | 22558.50 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126201E+09 | 0.00 | 0.00 | 17964.99 | 0.00 | 0.275311E+10 | 1369667.78 | 0.00 | 0.47 |
February | 0.236393E+09 | 0.00 | 0.00 | 241455.61 | 0.00 | 0.229072E+10 | 25390372.91 | 0.00 | 0.47 |
March | 0.413029E+09 | 0.00 | 0.00 | 1232468.21 | 0.00 | 0.108500E+10 | 0.233764E+09 | 0.00 | 0.47 |
April | 0.361405E+09 | 38468175.71 | 8882.09 | 4238227.80 | 4042363.96 | 0.598658E+09 | 0.515980E+09 | 2500.02 | 0.47 |
May | 0.260987E+09 | 56274688.82 | 65445.54 | 7841031.91 | 13455672.08 | 0.105170E+09 | 0.842041E+09 | 2670.03 | 0.47 |
June | 0.116114E+09 | 0.403225E+09 | 225169.26 | 5150261.73 | 37294086.81 | 37965993.11 | 0.430371E+09 | 18763.74 | 0.48 |
July | 23280681.26 | 0.649709E+09 | 482424.50 | 3331645.84 | 61232296.07 | 359353.82 | 0.216450E+09 | 24042.15 | 0.48 |
August | 33612660.34 | 0.487906E+09 | 415314.46 | 4280249.10 | 60359008.30 | 382928.75 | 0.345626E+09 | 21932.00 | 0.48 |
September | 0.237620E+09 | 84489199.96 | 4925.92 | 5299567.15 | 8121696.31 | 0.198874E+09 | 0.610733E+09 | 908.10 | 0.47 |
October | 0.463817E+09 | 0.00 | 0.00 | 2574977.11 | 0.00 | 0.711901E+09 | 0.507443E+09 | 0.00 | 0.47 |
November | 0.353189E+09 | 0.00 | 0.00 | 666812.56 | 0.00 | 0.127680E+10 | 0.197242E+09 | 0.00 | 0.47 |
December | 0.176208E+09 | 0.00 | 0.00 | 27026.76 | 0.00 | 0.174339E+10 | 1988597.06 | 0.00 | 0.47 |
Annual Sum or Average | 0.280186E+10 | 0.172007E+10 | 1202161.77 | 34901688.76 | 0.184505E+09 | 0.108023E+11 | 0.392840E+10 | 70816.05 | 0.47 |
Minimum of Months | 23280681.26 | 0.00 | 0.00 | 17964.99 | 0.00 | 359353.82 | 1369667.78 | 0.00 | 0.47 |
Maximum of Months | 0.463817E+09 | 0.649709E+09 | 482424.50 | 7841031.91 | 61232296.07 | 0.275311E+10 | 0.842041E+09 | 24042.15 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222427E+11 | 0.00 | 0.00 | 1458705.51 | 0.00 | 0.161936E+11 | 0.617579E+09 | 0.00 | 0.53 |
February | 0.217309E+11 | 0.00 | 0.00 | 9240238.04 | 0.00 | 0.103990E+11 | 0.246988E+10 | 0.00 | 0.54 |
March | 0.160259E+11 | 0.00 | 0.00 | 24641723.05 | 0.00 | 0.127283E+10 | 0.617229E+10 | 0.00 | 0.54 |
April | 0.118752E+11 | 0.576451E+09 | 0.00 | 33897749.94 | 43565.25 | 0.00 | 0.815991E+10 | 0.00 | 0.54 |
May | 0.381768E+10 | 0.946299E+09 | 0.00 | 65600111.87 | 0.00 | 0.00 | 0.126033E+11 | 0.00 | 0.54 |
June | 0.141714E+10 | 0.595732E+10 | 0.00 | 39436149.81 | 18358176.34 | 0.00 | 0.653700E+10 | 0.00 | 0.54 |
July | 0.366327E+09 | 0.963337E+10 | 0.00 | 21378118.37 | 12146083.00 | 0.00 | 0.291251E+10 | 0.00 | 0.54 |
August | 0.285185E+09 | 0.742271E+10 | 0.00 | 34912427.69 | 16375015.12 | 0.00 | 0.488468E+10 | 0.00 | 0.54 |
September | 0.300901E+10 | 0.125566E+10 | 0.00 | 69269956.68 | 0.00 | 0.00 | 0.111915E+11 | 0.00 | 0.54 |
October | 0.718309E+10 | 0.00 | 0.00 | 80168355.59 | 0.00 | 0.00 | 0.155913E+11 | 0.00 | 0.54 |
November | 0.151671E+11 | 0.00 | 0.00 | 29515923.15 | 0.00 | 0.269294E+10 | 0.689236E+10 | 0.00 | 0.54 |
December | 0.170322E+11 | 0.00 | 0.00 | 7945507.89 | 0.00 | 0.723933E+10 | 0.177299E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.120152E+12 | 0.257918E+11 | 0.00 | 0.417465E+09 | 46922839.72 | 0.377977E+11 | 0.798052E+11 | 0.00 | 0.54 |
Minimum of Months | 0.285185E+09 | 0.00 | 0.00 | 1458705.51 | 0.00 | 0.00 | 0.617579E+09 | 0.00 | 0.53 |
Maximum of Months | 0.222427E+11 | 0.963337E+10 | 0.00 | 80168355.59 | 18358176.34 | 0.161936E+11 | 0.155913E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799878E+10 | 0.00 | 0.00 | 4426563.85 | 0.00 | 0.275738E+11 | 0.347827E+10 | 0.00 | 0.53 |
February | 0.579637E+10 | 0.00 | 0.00 | 12180551.53 | 0.00 | 0.212949E+11 | 0.750560E+10 | 0.00 | 0.54 |
March | 0.641808E+10 | 0.00 | 0.00 | 37572691.43 | 0.00 | 0.445128E+10 | 0.125887E+11 | 0.00 | 0.54 |
April | 0.540218E+10 | 0.401823E+09 | 575990.79 | 63493854.93 | 0.174090E+09 | 0.432921E+09 | 0.141705E+11 | 6039.99 | 0.54 |
May | 0.395735E+10 | 0.552583E+09 | 398459.69 | 0.107721E+09 | 0.393315E+09 | 23005235.60 | 0.123985E+11 | 2456.13 | 0.54 |
June | 0.174236E+10 | 0.494171E+10 | 1302014.41 | 64843932.37 | 0.103263E+10 | 12530070.19 | 0.617383E+10 | 48080.63 | 0.54 |
July | 0.387174E+09 | 0.775558E+10 | 2798244.23 | 38808554.46 | 0.188709E+10 | 301717.75 | 0.287393E+10 | 43270.13 | 0.54 |
August | 0.528333E+09 | 0.557712E+10 | 989028.34 | 52550080.23 | 0.186094E+10 | 1904230.27 | 0.462199E+10 | 31359.10 | 0.54 |
September | 0.348243E+10 | 0.933101E+09 | 1404770.91 | 80500932.73 | 0.321102E+09 | 36459896.75 | 0.106703E+11 | 52457.37 | 0.54 |
October | 0.634929E+10 | 0.00 | 0.00 | 68787388.21 | 0.00 | 90239751.99 | 0.163462E+11 | 0.00 | 0.54 |
November | 0.664218E+10 | 0.00 | 0.00 | 33225750.95 | 0.00 | 0.700070E+10 | 0.111058E+11 | 0.00 | 0.54 |
December | 0.668574E+10 | 0.00 | 0.00 | 6580221.28 | 0.00 | 0.142211E+11 | 0.513907E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.553903E+11 | 0.201619E+11 | 7468508.36 | 0.570692E+09 | 0.566917E+10 | 0.751392E+11 | 0.107073E+12 | 183663.35 | 0.54 |
Minimum of Months | 0.387174E+09 | 0.00 | 0.00 | 4426563.85 | 0.00 | 301717.75 | 0.287393E+10 | 0.00 | 0.53 |
Maximum of Months | 0.799878E+10 | 0.775558E+10 | 2798244.23 | 0.107721E+09 | 0.188709E+10 | 0.275738E+11 | 0.163462E+11 | 52457.37 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274050E+09 | 0.00 | 0.00 | 35570.68 | 0.00 | 0.259604E+10 | 10571684.86 | 0.00 | 0.47 |
February | 0.316837E+09 | 0.00 | 0.00 | 375209.71 | 0.00 | 0.216909E+10 | 66445531.57 | 0.00 | 0.47 |
March | 0.406659E+09 | 0.00 | 0.00 | 1863636.64 | 0.00 | 0.967954E+09 | 0.356551E+09 | 0.00 | 0.47 |
April | 0.327286E+09 | 40838011.54 | 3114.56 | 4440950.51 | 1680221.22 | 0.557017E+09 | 0.591537E+09 | 574.48 | 0.47 |
May | 0.182587E+09 | 65643474.73 | 92576.48 | 9428405.49 | 4060251.77 | 74954783.92 | 0.949069E+09 | 2173.49 | 0.48 |
June | 87860054.44 | 0.419234E+09 | 173838.65 | 5872305.83 | 21349502.84 | 17721981.20 | 0.478147E+09 | 5130.15 | 0.48 |
July | 14357757.15 | 0.674930E+09 | 301169.62 | 3927691.56 | 36207091.38 | 209202.59 | 0.224927E+09 | 9316.40 | 0.48 |
August | 17846113.71 | 0.508472E+09 | 428223.73 | 4928072.59 | 39784030.48 | 298717.38 | 0.360829E+09 | 18275.25 | 0.48 |
September | 0.166024E+09 | 89459261.25 | 13342.59 | 7140935.22 | 3142865.88 | 0.148403E+09 | 0.730959E+09 | 1260.58 | 0.47 |
October | 0.379021E+09 | 0.00 | 0.00 | 4049562.40 | 0.00 | 0.528081E+09 | 0.774585E+09 | 0.00 | 0.47 |
November | 0.381250E+09 | 0.00 | 0.00 | 1081570.55 | 0.00 | 0.116049E+10 | 0.285073E+09 | 0.00 | 0.47 |
December | 0.300047E+09 | 0.00 | 0.00 | 131524.18 | 0.00 | 0.159572E+10 | 25715099.38 | 0.00 | 0.47 |
Annual Sum or Average | 0.285383E+10 | 0.179858E+10 | 1012265.64 | 43275435.36 | 0.106224E+09 | 0.981598E+10 | 0.485441E+10 | 36730.35 | 0.47 |
Minimum of Months | 14357757.15 | 0.00 | 0.00 | 35570.68 | 0.00 | 209202.59 | 10571684.86 | 0.00 | 0.47 |
Maximum of Months | 0.406659E+09 | 0.674930E+09 | 428223.73 | 9428405.49 | 39784030.48 | 0.259604E+10 | 0.949069E+09 | 18275.25 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127001E+09 | 0.00 | 0.00 | 13324.54 | 0.00 | 0.275229E+10 | 1391237.08 | 0.00 | 0.47 |
February | 0.243443E+09 | 0.00 | 0.00 | 119702.71 | 0.00 | 0.228943E+10 | 19746966.46 | 0.00 | 0.47 |
March | 0.424924E+09 | 0.00 | 0.00 | 971968.79 | 0.00 | 0.105885E+10 | 0.248286E+09 | 0.00 | 0.47 |
April | 0.365172E+09 | 39685946.59 | 23512.25 | 3423782.94 | 2811569.80 | 0.603728E+09 | 0.507957E+09 | 893.16 | 0.47 |
May | 0.216253E+09 | 64972920.49 | 136297.91 | 8724496.95 | 4685708.73 | 91288240.86 | 0.899773E+09 | 3549.34 | 0.48 |
June | 92731395.93 | 0.417669E+09 | 206738.21 | 5738737.12 | 22880361.29 | 22482621.10 | 0.468648E+09 | 6445.16 | 0.48 |
July | 14621836.12 | 0.672149E+09 | 346592.70 | 3842067.67 | 38939745.24 | 209202.59 | 0.224749E+09 | 11689.69 | 0.48 |
August | 22067634.79 | 0.503161E+09 | 579396.87 | 4560251.54 | 44937388.40 | 331024.80 | 0.356943E+09 | 25081.76 | 0.48 |
September | 0.220788E+09 | 87573968.68 | 116101.24 | 5726606.15 | 4921220.38 | 0.172656E+09 | 0.653357E+09 | 5440.00 | 0.47 |
October | 0.469058E+09 | 0.00 | 0.00 | 1810626.11 | 0.00 | 0.718589E+09 | 0.496279E+09 | 0.00 | 0.47 |
November | 0.354477E+09 | 0.00 | 0.00 | 393567.65 | 0.00 | 0.127475E+10 | 0.198281E+09 | 0.00 | 0.47 |
December | 0.156917E+09 | 0.00 | 0.00 | 27112.30 | 0.00 | 0.176114E+10 | 3527255.30 | 0.00 | 0.47 |
Annual Sum or Average | 0.270745E+10 | 0.178521E+10 | 1408639.18 | 35352244.48 | 0.119176E+09 | 0.107457E+11 | 0.407894E+10 | 53099.12 | 0.47 |
Minimum of Months | 14621836.12 | 0.00 | 0.00 | 13324.54 | 0.00 | 209202.59 | 1391237.08 | 0.00 | 0.47 |
Maximum of Months | 0.469058E+09 | 0.672149E+09 | 579396.87 | 8724496.95 | 44937388.40 | 0.275229E+10 | 0.899773E+09 | 25081.76 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523792E+11 | 0.00 | 0.00 | 0.88 |
February | 0.368978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393684E+11 | 0.00 | 0.00 | 0.88 |
March | 0.157741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185683E+11 | 0.00 | 0.00 | 0.89 |
April | 0.197151E+11 | 0.00 | 0.00 | 0.00 | 0.119083E+10 | 0.842974E+10 | 0.00 | 0.00 | 0.89 |
May | 0.215033E+11 | 0.00 | 0.00 | 0.00 | 0.203406E+10 | 0.325003E+09 | 0.00 | 0.00 | 0.89 |
June | 0.110823E+11 | 0.00 | 0.00 | 0.00 | 0.111820E+11 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.398846E+10 | 0.00 | 0.00 | 0.00 | 0.179581E+11 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.696557E+10 | 0.00 | 0.00 | 0.00 | 0.148195E+11 | 0.00 | 0.00 | 0.00 | 0.89 |
September | 0.179439E+11 | 0.00 | 0.00 | 0.00 | 0.253667E+10 | 0.102921E+10 | 0.00 | 0.00 | 0.89 |
October | 0.261040E+11 | 0.00 | 0.00 | 0.00 | 1329761.97 | 0.513497E+10 | 0.00 | 0.00 | 0.89 |
November | 0.124623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235148E+11 | 0.00 | 0.00 | 0.89 |
December | 0.322221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374091E+11 | 0.00 | 0.00 | 0.88 |
Annual Sum or Average | 0.144099E+12 | 0.00 | 0.00 | 0.00 | 0.497225E+11 | 0.186159E+12 | 0.00 | 0.00 | 0.89 |
Minimum of Months | 0.164790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
Maximum of Months | 0.261040E+11 | 0.00 | 0.00 | 0.00 | 0.179581E+11 | 0.523792E+11 | 0.00 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47951372.77 | 0.00 | 0.00 | 18406.45 | 0.00 | 0.671002E+09 | 1202318.53 | 0.00 | 0.47 |
February | 60564826.74 | 0.00 | 0.00 | 150170.42 | 0.00 | 0.561992E+09 | 15478764.32 | 0.00 | 0.47 |
March | 96694437.79 | 0.00 | 0.00 | 511558.75 | 0.00 | 0.270128E+09 | 65922562.78 | 0.00 | 0.47 |
April | 75387163.89 | 10132986.74 | 516.00 | 1410364.75 | 496690.37 | 0.159352E+09 | 0.133921E+09 | 287.34 | 0.47 |
May | 52632274.11 | 15933104.53 | 9918.43 | 2330580.23 | 1505981.65 | 34935720.83 | 0.214111E+09 | 614.51 | 0.48 |
June | 24896157.75 | 0.103651E+09 | 61827.85 | 1473107.24 | 6475177.34 | 15044436.56 | 0.105987E+09 | 2898.14 | 0.48 |
July | 4923409.99 | 0.166833E+09 | 95935.88 | 928778.26 | 10928444.75 | 86772.68 | 54916555.90 | 4762.34 | 0.48 |
August | 6537536.50 | 0.127234E+09 | 61885.98 | 1245529.60 | 9876491.97 | 93706.88 | 88098619.92 | 3068.29 | 0.48 |
September | 46177006.60 | 22154488.59 | 0.00 | 1756639.70 | 999693.98 | 55085523.90 | 0.160113E+09 | 0.00 | 0.47 |
October | 99103639.34 | 0.00 | 0.00 | 1133261.27 | 0.00 | 0.174766E+09 | 0.146431E+09 | 0.00 | 0.47 |
November | 84562001.48 | 0.00 | 0.00 | 284191.35 | 0.00 | 0.318851E+09 | 53277261.76 | 0.00 | 0.47 |
December | 57542955.64 | 0.00 | 0.00 | 33904.32 | 0.00 | 0.420586E+09 | 2240521.56 | 0.00 | 0.47 |
Annual Sum or Average | 0.656973E+09 | 0.445938E+09 | 230084.14 | 11276492.36 | 30282480.07 | 0.268192E+10 | 0.104170E+10 | 11630.62 | 0.47 |
Minimum of Months | 4923409.99 | 0.00 | 0.00 | 18406.45 | 0.00 | 86772.68 | 1202318.53 | 0.00 | 0.47 |
Maximum of Months | 99103639.34 | 0.166833E+09 | 95935.88 | 2330580.23 | 10928444.75 | 0.671002E+09 | 0.214111E+09 | 4762.34 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19365136.33 | 0.00 | 0.00 | 6066.61 | 0.00 | 0.700417E+09 | 386151.33 | 0.00 | 0.47 |
February | 43323298.20 | 0.00 | 0.00 | 48833.64 | 0.00 | 0.589471E+09 | 5343410.56 | 0.00 | 0.47 |
March | 84373082.49 | 0.00 | 0.00 | 264236.37 | 0.00 | 0.308978E+09 | 39641336.31 | 0.00 | 0.47 |
April | 82506100.56 | 9858270.57 | 2334.43 | 1127780.22 | 769364.35 | 0.172006E+09 | 0.114431E+09 | 511.10 | 0.47 |
May | 58257098.35 | 15584592.58 | 9905.03 | 2166408.27 | 1854493.60 | 39283239.44 | 0.204303E+09 | 627.90 | 0.48 |
June | 26199923.43 | 0.103247E+09 | 54312.87 | 1443346.74 | 6886597.16 | 15848108.53 | 0.103909E+09 | 2824.08 | 0.48 |
July | 5082695.65 | 0.166364E+09 | 97663.99 | 906145.00 | 11395829.21 | 81286.54 | 54785389.65 | 4828.69 | 0.48 |
August | 7290278.53 | 0.125778E+09 | 64082.07 | 1159198.12 | 11329679.42 | 91269.40 | 87434646.86 | 3557.95 | 0.48 |
September | 55339814.42 | 21635653.38 | 1401.67 | 1430427.60 | 1517070.69 | 66228280.91 | 0.140133E+09 | 56.83 | 0.47 |
October | 0.116005E+09 | 0.00 | 0.00 | 600948.22 | 0.00 | 0.215501E+09 | 89326597.25 | 0.00 | 0.47 |
November | 73659886.41 | 0.00 | 0.00 | 132761.08 | 0.00 | 0.349510E+09 | 33671537.44 | 0.00 | 0.47 |
December | 26159061.80 | 0.00 | 0.00 | 8994.10 | 0.00 | 0.453732E+09 | 503723.95 | 0.00 | 0.47 |
Annual Sum or Average | 0.597561E+09 | 0.442467E+09 | 229700.07 | 9295145.95 | 33753034.42 | 0.291115E+10 | 0.873869E+09 | 12406.57 | 0.47 |
Minimum of Months | 5082695.65 | 0.00 | 0.00 | 6066.61 | 0.00 | 81286.54 | 386151.33 | 0.00 | 0.47 |
Maximum of Months | 0.116005E+09 | 0.166364E+09 | 97663.99 | 2166408.27 | 11395829.21 | 0.700417E+09 | 0.204303E+09 | 4828.69 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.760683E+09 | 0.00 | 0.00 | 2088688.59 | 0.00 | 0.349193E+10 | 0.370268E+09 | 0.00 | 0.53 |
February | 0.800991E+09 | 0.00 | 0.00 | 3525202.22 | 0.00 | 0.277308E+10 | 0.520844E+09 | 0.00 | 0.54 |
March | 0.511015E+09 | 0.00 | 0.00 | 6363674.79 | 0.00 | 0.123079E+10 | 0.103421E+10 | 0.00 | 0.54 |
April | 0.453608E+09 | 65513523.11 | 17872.74 | 8316413.27 | 2737330.93 | 0.661153E+09 | 0.125352E+10 | 401.29 | 0.54 |
May | 0.308074E+09 | 0.101237E+09 | 63986.14 | 13372067.22 | 10757306.33 | 60382675.56 | 0.157053E+10 | 3656.55 | 0.54 |
June | 0.150640E+09 | 0.656811E+09 | 141579.88 | 7675281.28 | 50689607.05 | 12550178.87 | 0.775742E+09 | 4167.66 | 0.54 |
July | 35005956.86 | 0.105770E+10 | 197642.18 | 4794379.84 | 84327533.49 | 313277.89 | 0.350702E+09 | 11182.83 | 0.54 |
August | 42526870.08 | 0.810102E+09 | 212561.54 | 7143067.52 | 70623474.78 | 2572768.32 | 0.564113E+09 | 6410.47 | 0.54 |
September | 0.253024E+09 | 0.143223E+09 | 59882.92 | 12867933.11 | 5409360.02 | 0.104631E+09 | 0.131931E+10 | 4168.45 | 0.54 |
October | 0.445537E+09 | 0.00 | 0.00 | 14437316.52 | 0.00 | 0.412967E+09 | 0.183351E+10 | 0.00 | 0.54 |
November | 0.550799E+09 | 0.00 | 0.00 | 5845832.16 | 0.00 | 0.144186E+10 | 0.936193E+09 | 0.00 | 0.54 |
December | 0.424798E+09 | 0.00 | 0.00 | 3543427.29 | 0.00 | 0.219682E+10 | 0.459996E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.473670E+10 | 0.283458E+10 | 693525.40 | 89973283.82 | 0.224545E+09 | 0.123891E+11 | 0.109889E+11 | 29987.26 | 0.54 |
Minimum of Months | 35005956.86 | 0.00 | 0.00 | 2088688.59 | 0.00 | 313277.89 | 0.350702E+09 | 0.00 | 0.53 |
Maximum of Months | 0.800991E+09 | 0.105770E+10 | 212561.54 | 14437316.52 | 84327533.49 | 0.349193E+10 | 0.183351E+10 | 11182.83 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.587118E+11 | 0.00 | 0.00 | 2390690.81 | 0.00 | 0.309249E+11 | 0.143612E+11 | 0.00 | 7.97 |
February | 0.362386E+11 | 0.00 | 0.00 | 4081682.72 | 0.00 | 0.283450E+11 | 0.182979E+11 | 0.00 | 7.98 |
March | 0.365740E+11 | 0.00 | 0.00 | 8227003.08 | 0.00 | 0.00 | 0.295257E+11 | 0.00 | 8.07 |
April | 0.262275E+11 | 0.390720E+09 | 0.00 | 10389301.07 | 0.190158E+10 | 0.00 | 0.279400E+11 | 0.00 | 8.05 |
May | 0.165584E+11 | 0.791336E+09 | 0.00 | 12109923.82 | 0.312417E+10 | 0.00 | 0.254482E+11 | 0.00 | 8.08 |
June | 0.776401E+10 | 0.844845E+10 | 0.00 | 6818682.71 | 0.130766E+11 | 0.00 | 0.135623E+11 | 0.00 | 8.09 |
July | 0.194561E+10 | 0.153533E+11 | 0.00 | 3145401.42 | 0.192155E+11 | 0.00 | 0.572889E+10 | 0.00 | 8.09 |
August | 0.322343E+10 | 0.111421E+11 | 0.00 | 5767577.04 | 0.173849E+11 | 0.00 | 0.101793E+11 | 0.00 | 8.09 |
September | 0.153198E+11 | 0.157430E+10 | 0.00 | 9573249.20 | 0.330870E+10 | 0.00 | 0.211931E+11 | 0.00 | 8.07 |
October | 0.304527E+11 | 0.00 | 0.00 | 11074386.13 | 2559746.42 | 0.00 | 0.296702E+11 | 0.00 | 8.04 |
November | 0.406667E+11 | 0.00 | 0.00 | 7283457.85 | 0.00 | 0.415755E+10 | 0.244231E+11 | 0.00 | 8.04 |
December | 0.543828E+11 | 0.00 | 0.00 | 3851064.37 | 0.00 | 0.00 | 0.238274E+11 | 0.00 | 7.98 |
Annual Sum or Average | 0.328065E+12 | 0.377002E+11 | 0.00 | 84712420.22 | 0.580140E+11 | 0.634274E+11 | 0.244157E+12 | 0.00 | 8.05 |
Minimum of Months | 0.194561E+10 | 0.00 | 0.00 | 2390690.81 | 0.00 | 0.00 | 0.572889E+10 | 0.00 | 7.97 |
Maximum of Months | 0.587118E+11 | 0.153533E+11 | 0.00 | 12109923.82 | 0.192155E+11 | 0.309249E+11 | 0.296702E+11 | 0.00 | 8.09 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573286E+11 | 0.00 | 0.00 | 3592051.67 | 0.00 | 0.320924E+11 | 0.199303E+11 | 0.00 | 8.38 |
February | 0.356680E+11 | 0.00 | 0.00 | 5852159.23 | 0.00 | 0.289211E+11 | 0.225579E+11 | 0.00 | 8.39 |
March | 0.349826E+11 | 0.00 | 0.00 | 11301679.63 | 0.00 | 0.00 | 0.345176E+11 | 0.00 | 8.49 |
April | 0.241266E+11 | 0.593648E+09 | 0.00 | 13769322.06 | 0.181668E+10 | 0.00 | 0.328269E+11 | 0.00 | 8.46 |
May | 0.136566E+11 | 0.115087E+10 | 0.00 | 15466357.56 | 0.296622E+10 | 0.00 | 0.305101E+11 | 0.00 | 8.50 |
June | 0.635516E+10 | 0.992836E+10 | 0.00 | 8477026.70 | 0.127049E+11 | 0.00 | 0.160678E+11 | 0.00 | 8.51 |
July | 0.158019E+10 | 0.175615E+11 | 0.00 | 3825741.55 | 0.187870E+11 | 0.00 | 0.648892E+10 | 0.00 | 8.50 |
August | 0.291315E+10 | 0.134056E+11 | 0.00 | 6949540.13 | 0.165901E+11 | 0.00 | 0.111787E+11 | 0.00 | 8.51 |
September | 0.132723E+11 | 0.196727E+10 | 0.00 | 12183052.33 | 0.316714E+10 | 0.00 | 0.251185E+11 | 0.00 | 8.49 |
October | 0.262431E+11 | 0.00 | 0.00 | 14802193.50 | 2691536.23 | 0.00 | 0.369722E+11 | 0.00 | 8.46 |
November | 0.397796E+11 | 0.00 | 0.00 | 9784582.86 | 0.00 | 0.437670E+10 | 0.286542E+11 | 0.00 | 8.45 |
December | 0.534035E+11 | 0.00 | 0.00 | 5679390.66 | 0.00 | 0.00 | 0.288317E+11 | 0.00 | 8.40 |
Annual Sum or Average | 0.309309E+12 | 0.446073E+11 | 0.00 | 0.111683E+09 | 0.560348E+11 | 0.653902E+11 | 0.293655E+12 | 0.00 | 8.46 |
Minimum of Months | 0.158019E+10 | 0.00 | 0.00 | 3592051.67 | 0.00 | 0.00 | 0.648892E+10 | 0.00 | 8.38 |
Maximum of Months | 0.573286E+11 | 0.175615E+11 | 0.00 | 15466357.56 | 0.187870E+11 | 0.320924E+11 | 0.369722E+11 | 0.00 | 8.51 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116592E+10 | 0.00 | 0.00 | 77590595.33 | 0.00 | 0.287165E+11 | 0.795694E+11 | 0.00 | 27.04 |
February | 0.522777E+09 | 0.00 | 0.00 | 76840194.87 | 0.00 | 0.276717E+11 | 0.591211E+11 | 0.00 | 27.12 |
March | 0.00 | 0.00 | 0.00 | 0.103034E+09 | 0.00 | 0.00 | 0.697517E+11 | 0.00 | 27.52 |
April | 0.00 | 0.241231E+10 | 0.00 | 95618233.72 | 0.00 | 0.00 | 0.571986E+11 | 0.00 | 27.43 |
May | 0.00 | 0.412048E+10 | 0.00 | 85292585.47 | 0.00 | 0.00 | 0.442648E+11 | 0.00 | 27.47 |
June | 0.00 | 0.226519E+11 | 0.00 | 42378844.69 | 0.00 | 0.00 | 0.224437E+11 | 0.00 | 27.43 |
July | 0.00 | 0.363784E+11 | 0.00 | 17127990.90 | 0.00 | 0.00 | 0.806244E+10 | 0.00 | 27.40 |
August | 0.00 | 0.300204E+11 | 0.00 | 26681893.40 | 0.00 | 0.00 | 0.140843E+11 | 0.00 | 27.41 |
September | 0.00 | 0.513863E+10 | 0.00 | 74338771.15 | 0.00 | 0.00 | 0.384850E+11 | 0.00 | 27.43 |
October | 0.00 | 2693748.37 | 0.00 | 0.103757E+09 | 0.00 | 0.00 | 0.634928E+11 | 0.00 | 27.44 |
November | 0.162519E+09 | 0.00 | 0.00 | 94110969.28 | 0.00 | 0.421574E+10 | 0.686084E+11 | 0.00 | 27.36 |
December | 39905513.81 | 0.00 | 0.00 | 94477243.90 | 0.00 | 0.00 | 0.823252E+11 | 0.00 | 27.16 |
Annual Sum or Average | 0.189113E+10 | 0.100725E+12 | 0.00 | 0.891249E+09 | 0.00 | 0.606040E+11 | 0.607408E+12 | 0.00 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17127990.90 | 0.00 | 0.00 | 0.806244E+10 | 0.00 | 27.04 |
Maximum of Months | 0.116592E+10 | 0.363784E+11 | 0.00 | 0.103757E+09 | 0.00 | 0.287165E+11 | 0.823252E+11 | 0.00 | 27.52 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.694818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251613E+11 | 0.00 | 0.00 | 1.59 |
February | 0.157492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190317E+11 | 0.00 | 0.00 | 1.59 |
March | 0.650719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992826E+10 | 0.00 | 0.00 | 1.61 |
April | 0.898185E+10 | 0.00 | 0.00 | 0.00 | 0.569903E+09 | 0.448762E+10 | 0.00 | 0.00 | 1.60 |
May | 0.100762E+11 | 0.00 | 0.00 | 0.00 | 0.973455E+09 | 0.370373E+09 | 0.00 | 0.00 | 1.61 |
June | 0.527082E+10 | 0.00 | 0.00 | 0.00 | 0.535146E+10 | 32919498.79 | 0.00 | 0.00 | 1.61 |
July | 0.190878E+10 | 0.00 | 0.00 | 0.00 | 0.859433E+10 | 0.00 | 0.00 | 0.00 | 1.61 |
August | 0.333356E+10 | 0.00 | 0.00 | 0.00 | 0.709226E+10 | 0.00 | 0.00 | 0.00 | 1.62 |
September | 0.837932E+10 | 0.00 | 0.00 | 0.00 | 0.121399E+10 | 0.700744E+09 | 0.00 | 0.00 | 1.61 |
October | 0.117731E+11 | 0.00 | 0.00 | 0.00 | 636392.76 | 0.317719E+10 | 0.00 | 0.00 | 1.60 |
November | 0.554709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116707E+11 | 0.00 | 0.00 | 1.60 |
December | 0.137888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180663E+11 | 0.00 | 0.00 | 1.59 |
Annual Sum or Average | 0.654264E+11 | 0.00 | 0.00 | 0.00 | 0.237960E+11 | 0.926271E+11 | 0.00 | 0.00 | 1.61 |
Minimum of Months | 0.694818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
Maximum of Months | 0.117731E+11 | 0.00 | 0.00 | 0.00 | 0.859433E+10 | 0.251613E+11 | 0.00 | 0.00 | 1.62 |