Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:50
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2020-06-03 19:50:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 15129.60 | 1333.56 | 1333.56 |
Net Site Energy | 15129.60 | 1333.56 | 1333.56 |
Total Source Energy | 34392.09 | 3031.40 | 3031.40 |
Net Source Energy | 34392.09 | 3031.40 | 3031.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2511.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1353.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1395.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 246.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.31 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1011.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2108.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 168.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 438.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.79 | 2192.23 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 73.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8637.35 | 6492.25 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2511.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1353.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1395.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 246.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 33.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2108.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 168.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 438.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.79 | 2192.23 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 328.02 | 414.57 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 288.61 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 761.32 | 572.24 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 328.02 | 414.57 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 288.61 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 761.32 | 572.24 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8637.351 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8637.351 | 100.00 |
Total On-Site and Utility Electric Sources | 8637.351 | 100.00 |
Total Electricity End Uses | 8637.351 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 449.70 | 7.41 |
Air to Air Heat Recovery for Heating | 5620.70 | 92.59 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6070.40 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 633.50 |
Time Setpoint Not Met During Occupied Cooling | 151.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6638.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| Environment |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 10.1931 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 15.2897 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 15.2897 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 15.2897 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.1545 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.1159 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 13.2510 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 11.2124 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 11.8403 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 11.8403 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 11.8403 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 5.0966 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 11.8403 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 11.8403 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 11.8403 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 13.2510 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 13.2510 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 12.2317 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 5.0966 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 10.4431 | 7.60 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 10.4431 | 7.60 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-18:10 | 21-DEC-17:40 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 474867.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 241680.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 98435.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 51433.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81770.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8649.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 18703.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4576.77 | 173585.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2852.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 587719.45 | 738065.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 474867.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 241680.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 98435.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1573.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 971.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 81770.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 8649.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 18703.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4576.77 | 173585.50 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1164.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1045.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2722.10 | 0.00 | 0.00 | 0.00 |
Cooling | 4287.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4419.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 779.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.39 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3202.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6678.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 532.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1388.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.54 | 2376.38 | 0.00 | 0.00 | 0.00 |
Refrigeration | 231.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 27354.49 | 7037.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 239.93 | 0.00 | 0.00 | 0.00 |
Cooling | 377.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 389.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 282.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 588.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 122.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 209.46 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2411.09 | 620.31 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 239.93 | 0.00 | 0.00 | 0.00 |
Cooling | 377.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 389.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 282.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 588.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 122.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 209.46 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2411.09 | 620.31 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.19 | 0.472197 | 0.988000 | 3.15 | 1.00 | 0.500000 | 0.000807 | 0.000299 | 3.15 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.394676 | 0.129494 | 0.988000 | 0.389940 | 0.988000 | 0.500000 | 0.002942 | 0.000114 | 0.389940 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.297073 | 0.199223 | 0.988000 | 0.293508 | 0.988000 | 0.500000 | 0.001912 | 0.000047 | 0.293508 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.334542 | 0.374103 | 0.988000 | 0.330528 | 0.997608 | 0.500000 | 0.001018 | 0.000064 | 0.330528 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.139811 | 0.516460 | 0.988000 | 0.138133 | 1.00 | 0.500000 | 0.000738 | 0.000036 | 0.138133 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.02 | 0.058688 | 0.988000 | 3.97 | 0.988000 | 0.500000 | 0.025762 | 0.000420 | 3.97 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.71 | 0.084263 | 0.988000 | 1.69 | 0.988000 | 0.500000 | 0.004522 | 0.000362 | 1.69 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.75 | 0.173421 | 0.988000 | 5.68 | 0.988000 | 0.500000 | 0.002197 | 0.000943 | 5.68 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.988000 | 1.17 | 1.00 | 0.500000 | 0.000381 | 0.000319 | 1.17 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.79 | 0.090739 | 0.988000 | 2.75 | 0.988000 | 0.500000 | 0.004199 | 0.000415 | 2.75 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.92 | 0.086441 | 0.988000 | 2.89 | 0.988000 | 0.500000 | 0.004408 | 0.000431 | 2.89 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.82 | 0.700000 | 0.988000 | 2.79 | 0.988000 | 0.500000 | 0.013672 | 0.000303 | 2.79 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.769440 | 0.408139 | 0.988000 | 0.760207 | 1.00 | 0.500000 | 0.000934 | 0.000239 | 0.760207 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 13521.73 | 0.000299 | 239.27 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5153.73 | 0.000114 | 101.65 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2148.93 | 0.000047 | 39.60 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2901.74 | 0.000064 | 54.57 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1632.23 | 0.000036 | 31.86 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19030.46 | 0.000420 | 338.99 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 16370.02 | 0.000362 | 311.91 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 42694.75 | 0.000943 | 788.99 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 6212.54 | 0.000137 | 141.44 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 6218.92 | 0.000137 | 141.58 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 35428.68 | 0.000783 | 806.59 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 35552.20 | 0.000785 | 809.40 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 6212.54 | 0.000137 | 141.44 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 6218.92 | 0.000137 | 141.58 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14424.66 | 0.000319 | 282.52 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1994.47 | 0.000044 | 45.41 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1999.07 | 0.000044 | 45.51 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9670.53 | 0.000214 | 220.16 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 18790.09 | 0.000415 | 343.97 |
DINING_FLR_6 VAV BOX REHEAT COIL | 19493.18 | 0.000431 | 356.45 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 13722.12 | 0.000303 | 244.84 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10829.92 | 0.000239 | 215.36 |
VAV WITH REHEAT_HEATC | 265175.91 | 0.005859 | 3548.61 |
FLR_3_DOAS_HEATC | 20912.17 | 0.000462 | 279.85 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.45 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.44 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 7.55 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 8.13 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.27 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.26 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.392385 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.388629 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.49 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.45 | 0.000137 | 0.000520 |
ROOM_2_FLR_3 FAN COIL | 1.44 | 0.000137 | 0.000515 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.55 | 0.000783 | 0.002694 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.13 | 0.000785 | 0.003019 |
ROOM_5_FLR_3 FAN COIL | 1.27 | 0.000137 | 0.000455 |
ROOM_6_FLR_3 FAN COIL | 1.26 | 0.000137 | 0.000453 |
ROOM_1_FLR_6 FAN COIL | 0.392385 | 0.000044 | 0.000140 |
ROOM_2_FLR_6 FAN COIL | 0.388629 | 0.000044 | 0.000139 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.49 | 0.000214 | 0.000541 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.45 |
ROOM_2_FLR_3 FAN COILFAN | 1.44 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 7.55 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 8.13 |
ROOM_5_FLR_3 FAN COILFAN | 1.27 |
ROOM_6_FLR_3 FAN COILFAN | 1.26 |
ROOM_1_FLR_6 FAN COILFAN | 0.392385 |
ROOM_2_FLR_6 FAN COILFAN | 0.388629 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.49 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000520 | 1.45 | 0.008517 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000515 | 1.44 | 0.008517 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002694 | 7.55 | 0.008454 | 22.81 | 6.70 | 12.80 | 0.008454 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.003019 | 8.13 | 0.008668 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000455 | 1.27 | 0.008518 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000453 | 1.26 | 0.008518 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000140 | 0.392385 | 0.008516 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000139 | 0.388629 | 0.008516 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000541 | 1.49 | 0.008586 | 22.81 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.021528 | 0.005430 | 33.90 | 6.70 | 10.54 | 0.005430 | 602722.19 | 26.01 | |
FLR_3_DOAS_COOLC | 0.001612 | 0.005430 | 33.90 | 6.70 | 10.54 | 0.005430 | 45130.47 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 26.01 | 26.01 | 26.33 | 26.01 | 26.01 | 26.01 | 0.300000 | 1.00 | 26.01 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.01 | 26.00 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 26.00 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 26.01 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.021528 | 0.000022 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.005859 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001612 | 0.000295 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000462 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.031616 | 7572.33 |
HEATSYS1 PUMP | 0.012733 | 3253.08 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.012733 | 1.53 |
COOLSYS1 | 0.031616 | 3.79 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.031616 | 2524.11 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 576309.53 | 576309.53 | 0.012733 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.031616 | 885166.69 | 885858.80 | 100.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 10.193 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.573 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 15.290 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.050 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 15.290 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.050 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 15.290 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.670 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 8.154 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.844 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.116 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.646 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 13.251 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.631 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 11.212 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.282 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 5.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.097 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 11.840 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 18.590 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 11.840 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.360 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 13.251 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 81.071 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 13.251 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 81.071 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.232 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.648 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 5.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 20170.425 | 10.193 | 189.395 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 20170.425 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1025.498 | 15.290 | 94.699 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1025.498 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1187.531 | 15.290 | 94.699 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1187.531 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 2511.222 | 15.290 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2511.222 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 772.713 | 8.154 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 772.713 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 477.279 | 6.116 | 56.819 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 477.279 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2502.616 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2502.616 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 14667.927 | 11.212 | 34.722 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14667.927 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 290.370 | 11.840 | 193.580 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.370 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 290.449 | 11.840 | 193.633 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.449 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 1984.622 | 5.097 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.622 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 462.032 | 11.840 | 308.022 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 462.032 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 461.978 | 11.840 | 307.986 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 461.978 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 290.449 | 11.840 | 193.633 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 290.449 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 4394.805 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4394.805 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 4394.805 | 13.251 | 17.587 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4394.805 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1263.592 | 12.232 | 56.821 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1263.592 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2100.415 | 5.097 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2100.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4744 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.941 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.31219756E-14 | -0.25237900E-15 | -0.17078023E-09 | -0.40080417E-16 |
25 | 8 | 0.24827770E-07 | 0.64895754E-13 | 0.40814970E-03 | -0.28230026E-09 |
26 | 7 | -0.13145170E-01 | 0.32788080E-08 | -0.24386180E-01 | 0.14946539E-03 |
27 | 6 | 0.42990022 | 0.11289000E-05 | 0.49294528 | -0.50371474E-02 |
28 | 5 | -5.4301032 | 0.41776872E-04 | -4.6011904 | 0.66154067E-01 |
29 | 4 | 34.062169 | 0.33899226E-03 | 22.064921 | -0.43618800 |
30 | 3 | -113.47938 | 0.73347792E-03 | -56.858567 | 1.5477483 |
31 | 2 | 199.36357 | 0.40991987E-03 | 79.008039 | -2.9361691 |
32 | 1 | -171.98885 | 0.43498902E-04 | -55.585984 | 2.7600347 |
33 | 0 | 57.057407 | 0.24596459E-06 | 15.505383 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 31 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
2 | RESWINDOW_U_0.39_SHGC_0.4 | 32 | 1 | VerySmooth | 2.216 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.35607E-002 | 0.31435 | 0.47829 | 0.47829 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.12023 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35674.43000 | 35674.43000 | 3.19331 | 3.19331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 26.77133 | 5.43031E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4409.04062 | 4409.04062 | 0.39468 | 0.39468 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.43030E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3485.29510 | 3485.29510 | 0.18402 | 0.18402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3318.42485 | 3318.42485 | 0.29707 | 0.29707 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 32.61733 | 5.43030E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 892.52780 | 892.52780 | 4.71292E-002 | 9.16993E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3737.98231 | 3737.98231 | 0.33454 | 0.33454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.01200 | 5.43030E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1487.33319 | 1487.33319 | 7.85373E-002 | 7.85373E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1562.16770 | 1562.16770 | 0.13981 | 0.13981 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1041.12986 | 1041.12986 | 5.49757E-002 | 5.77430E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44921.25896 | 44921.25896 | 4.02083 | 4.02083 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.43030E-003 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2033.11305 | 2033.11305 | 0.10735 | 0.23597 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19062.03169 | 19062.03169 | 1.70789 | 1.70789 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.43030E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9149.64824 | 9149.64824 | 0.48310 | 0.67613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64188.98388 | 64188.98388 | 5.74807 | 5.74807 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.43030E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 18389.32652 | 18389.32652 | 0.97102 | 1.89326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12037.64226 | 12037.64226 | 1.45188 | 1.45188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6212.75503 | 6212.75503 | 0.32997 | 0.32997 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11916.26099 | 11916.26099 | 1.43724 | 1.43724 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6219.13668 | 6219.13668 | 0.33031 | 0.33031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 62629.14458 | 62629.14458 | 7.55360 | 7.55360 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 35429.27263 | 35429.27263 | 1.88179 | 1.88179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 67378.93155 | 67378.93155 | 8.12714 | 8.12714 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 35552.78955 | 35552.78955 | 1.88835 | 1.88835 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10537.15866 | 10537.15866 | 1.27091 | 1.27091 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.43031E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6212.75503 | 6212.75503 | 0.32997 | 0.32997 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10483.78116 | 10483.78116 | 1.26447 | 1.26447 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.43031E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6219.13668 | 6219.13668 | 0.33031 | 0.33031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 11081.07854 | 11081.07854 | 0.99174 | 1.18691 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 33.30800 | 5.43030E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9402.81473 | 9402.81473 | 0.49652 | 0.49652 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3253.28438 | 3253.28438 | 0.39238 | 0.39238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1994.53134 | 1994.53134 | 0.10593 | 0.10593 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3222.14211 | 3222.14211 | 0.38863 | 0.38863 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1999.13756 | 1999.13756 | 0.10618 | 0.10618 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12322.14864 | 12322.14864 | 1.48625 | 1.48625 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.43030E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9670.78458 | 9670.78458 | 0.51364 | 0.51364 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31074.40706 | 31074.40706 | 2.78518 | 2.78518 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.43030E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7003.48985 | 7003.48985 | 0.36981 | 1.18734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32619.99164 | 32619.99164 | 2.92365 | 2.92365 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.43030E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7120.75000 | 7120.75000 | 0.37600 | 1.18734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31468.95142 | 31468.95142 | 2.82468 | 2.82468 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.43030E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1811.20786 | 1811.20786 | 9.56227E-002 | 0.36721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8597.23653 | 8597.23653 | 0.76944 | 0.76944 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90000 | 5.43030E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7573.40110 | 7573.40110 | 0.39991 | 0.39991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 538785.43 | 25.99797 | 25.99797 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 262006.72 | 7.70979 | 7.70979 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42509.33 | 22.31490 | 2.05120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69707.24 | 5.81646 | 2.05120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.19331 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47220 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.15499 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.06867E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.98746E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.15499 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13521.73339 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.98746E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.27351 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.39468 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12949 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38994 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94221E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13865E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38994 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5153.72879 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13865E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 101.65322 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29707 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19922 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29351 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.91243E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.74780E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29351 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2148.92884 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.74780E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.60471 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.33454 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37410 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33053 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99761 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01844E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.41103E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33053 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2901.73615 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.41103E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.56965 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13981 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51646 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13813 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.37715E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60621E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13813 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1632.23047 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60621E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.85501 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.02083 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.86878E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.97258 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57615E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20455E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.97258 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19030.46221 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20455E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 338.98882 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70789 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.42634E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68740 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.52153E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.61676E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.68740 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16370.01869 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61676E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 311.90878 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.74807 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17342 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.67909 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19696E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43288E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.67909 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 42694.75454 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43288E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 788.99430 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45188 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.45188 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.45188 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.37259E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.19913E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.19913E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.45188 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51681E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6212.54269 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37259E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.43868 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43724 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.43724 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.43724 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.37400E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.14689E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.14689E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.43724 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51695E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6218.92406 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37400E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.58394 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.55360 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.55360 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 7.55360 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.82753E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69353E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.69353E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 7.55360 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.45436E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80846 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.45436E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 35428.68247 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.82753E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 806.58579 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.12714 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.12714 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 8.12714 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.85482E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.01913E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.01913E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 8.12714 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.66799E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80711 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 35552.19749 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.85482E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 809.39735 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27091 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.27091 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.27091 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.37259E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.55235E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.55235E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.27091 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51795E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6212.54269 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37259E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.43868 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26447 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26447 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.26447 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.37400E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52943E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.52943E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.26447 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51808E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6218.92406 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37400E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.58394 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17266 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18695E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17266 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14424.66396 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18695E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.52348 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39238 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.39238 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.39238 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.40653E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.40469E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.40469E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.39238 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51558E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1994.46658 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.40653E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.40549 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38863 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38863 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.38863 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.41671E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.39128E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.39128E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.38863 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51571E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80802 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1999.07264 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41671E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.51033 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48625 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.48625 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.48625 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.13659E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.41273E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 5.41273E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.48625 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.58561E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 22.80751 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 9670.53340 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13659E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.15555 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.78518 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.07386E-002 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.75175 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19887E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.15144E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.75175 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18790.09049 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.15144E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.97081 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.92365 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.64408E-002 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.88857 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.40764E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.30678E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.88857 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19493.17511 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30678E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 356.45270 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.82468 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79078 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98800 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36716E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03173E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.79078 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13722.11837 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03173E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.83939 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76944 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40814 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98800 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76021 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.33504E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.39274E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76021 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10829.92133 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39274E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 215.36329 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.01014 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.01014 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.32605 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.01014 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.01014 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.01014 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.01014 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.01014 |
346 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.99797 |
347 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.99797 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 602722.19252 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.15278E-002 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 26.01014 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 5.43030E-003 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 33.90000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.54137 |
355 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 5.43030E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 265175.91222 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.85874E-003 |
358 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3548.60691 |
359 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 26.01014 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.15278E-002 |
361 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.21198E-005 |
362 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.85874E-003 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 45130.46586 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.61196E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 5.43030E-003 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 33.90000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.54137 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 5.43030E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20912.17262 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.62029E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 279.84850 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.61196E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.95412E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.62029E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.16161E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7572.32748 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.27329E-002 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.52794 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.27329E-002 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3253.08116 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 576309.53327 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 576309.53000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.27329E-002 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.16161E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.79393 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.16161E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2524.10916 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.16161E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 885166.69256 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 885858.80000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 100.98790 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 13600.99 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5187.90 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2161.23 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2917.93 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1643.14 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19141.52 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 16460.52 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 42938.77 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6706.17 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6713.06 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 38243.65 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 38376.97 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6706.17 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6713.06 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14520.77 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2152.88 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2157.85 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 10438.59 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 18897.98 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 19605.17 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 13802.11 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10900.48 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 174701.40 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 13777.22 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 26282.76 | 18400.74 | 7882.03 | 0.70 | 5351.09 | 54.27 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 26018.32 | 18215.38 | 7802.94 | 0.70 | 5297.04 | 53.73 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 136980.04 | 95881.63 | 41098.41 | 0.70 | 28860.13 | 292.72 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 150517.22 | 104105.60 | 46411.62 | 0.69 | 29526.62 | 299.48 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 23010.70 | 16108.40 | 6902.30 | 0.70 | 4683.44 | 47.50 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 22894.57 | 16026.94 | 6867.63 | 0.70 | 4659.65 | 47.26 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 7101.82 | 4972.54 | 2129.28 | 0.70 | 1446.39 | 14.67 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 7033.97 | 4924.98 | 2108.99 | 0.70 | 1432.52 | 14.53 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 27192.30 | 18929.77 | 8262.53 | 0.70 | 5442.59 | 55.20 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 726967.91 | 422029.09 | 304938.82 | 0.58 | 111647.23 | 1132.39 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 52559.35 | 31349.81 | 21209.54 | 0.60 | 6662.86 | 67.58 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 3.82 | 13.05 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 5.8080148668E-003 | 1.4404599195E-002 | Pass | Pass | 1.2560240443E-002 | 3.2102343681E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7656153214E-002 | 8.1985247000E-002 | Pass | Pass | 0.1094278327 | 0.2035930860 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7306570043E-003 | 1.1319593878E-002 | Pass | Pass | 1.7729680869E-002 | 2.8547075489E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2271421037E-004 | 6.9946282097E-004 | Pass | Pass | 3.2323972050E-002 | 5.7139381252E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.0524075205E-004 | 6.3965088121E-004 | Pass | Pass | 0.1969530798 | 0.4221211985 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7100685809E-002 | 0.1438552138 | Pass | Pass | 1.8986514535E-002 | 5.3847844623E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4331767358E-002 | 7.1118503138E-002 | Pass | Pass | 2.2899199470E-002 | 3.5211425494E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6849162878E-002 | 2.7161497698E-002 | Pass | Pass | 1.6248569168E-002 | 2.8358874731E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4862790853E-002 | 0.1996540827 | Pass | Pass | 0.1380558456 | 0.4207119765 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.7503661354E-002 | 0.2193379794 | Pass | Pass | 0.3393947832 | 1.5208355588 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.1059116055E-002 | 4.9208932461E-002 | Pass | Pass | 3.6730936292E-002 | 5.0921211880E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0687647024E-002 | 3.9269012994E-002 | Pass | Pass | 8.7261412955E-002 | 0.1336834673 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3735418264E-002 | 0.2618543760 | Pass | Pass | 0.1822220096 | 0.5689352727 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.3232081315E-002 | 0.1848136719 | Pass | Pass | 0.2316015159 | 0.8969232632 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0352454663E-003 | 3.3165469836E-003 | Pass | Pass | 0.2270514440 | 1.2622317015 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.4872200691E-002 | 0.2091457376 | Pass | Pass | 1.3991115533 | 11.6096435180 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.4793256022E-002 | 0.2769804500 | Pass | Pass | 0.2234783352 | 0.7217659788 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9045526192E-002 | 0.3128012165 | Pass | Pass | 0.1851428977 | 0.5193086717 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2287546838E-002 | 6.7358497349E-002 | Pass | Pass | 1.2571707143E-002 | 3.4553675855E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5816002160E-002 | 6.9639789181E-002 | Pass | Pass | 1.1900298942E-002 | 3.0512364407E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3962898623E-002 | 0.1455749890 | Pass | Pass | 1.7255922782E-002 | 3.0011605132E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1012078391E-003 | 8.1235396982E-004 | Pass | Pass | 0.3299286614 | 1.8139201161 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.159 | 0.394 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.159 | 0.394 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.159 | 0.394 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.216 | 0.394 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.216 | 0.394 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.216 | 0.394 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.394 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.394 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.199 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 432.93 | 2.201 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 781.15 | 2.198 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 10.1931 | 1978.83 | 20170.43 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 55.03 | 168.00 | 54.96 | 0.0000 | Y | 208.11 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 15.2897 | 67.07 | 1025.50 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.29 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 15.2897 | 77.67 | 1187.53 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.07 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 15.2897 | 164.24 | 2511.22 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 27.64 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 8.1545 | 94.76 | 772.71 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 4.42 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 6.1159 | 78.04 | 477.28 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.25 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 13.2510 | 188.86 | 2502.62 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 27.54 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 11.2124 | 1308.19 | 14667.93 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 161.43 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 11.8403 | 156.09 | 1848.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 11.8403 | 156.07 | 1847.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 11.8403 | 1863.81 | 22068.10 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 286.71 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 11.8403 | 1864.32 | 22074.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 286.79 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 11.8403 | 156.09 | 1848.13 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 11.8403 | 156.07 | 1847.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.01 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 5.0966 | 1557.62 | 7938.49 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 87.37 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 11.8403 | 39.02 | 462.03 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.00 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 11.8403 | 39.02 | 461.98 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.00 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 11.8403 | 220.77 | 2614.04 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 33.96 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 13.2510 | 331.66 | 4394.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 48.37 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 13.2510 | 331.66 | 4394.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 48.37 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 12.2317 | 103.30 | 1263.59 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.91 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 5.0966 | 412.12 | 2100.42 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 23.12 |
Interior Lighting Total | 10.4431 | 11345.29 | 118479.68 | 661.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15665.55 | AstronomicalClock | - | 83.67 | 83.67 | 246.05 | |
Exterior Lighting Total | 15665.55 | 246.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 576309.53 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 885858.80 | 2.80 | 3.82 | 13.05 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 14556.45 | 26282.76 | 18400.74 | 7882.03 | 0.70 | - | 5351.09 | 54.27 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 14410.18 | 26018.32 | 18215.38 | 7802.94 | 0.70 | - | 5297.04 | 53.73 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 75413.12 | 136980.04 | 95881.63 | 41098.41 | 0.70 | - | 28860.13 | 292.72 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 84529.06 | 150517.22 | 104105.60 | 46411.62 | 0.69 | - | 29526.62 | 299.48 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12745.62 | 23010.70 | 16108.40 | 6902.30 | 0.70 | - | 4683.44 | 47.50 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12681.43 | 22894.57 | 16026.94 | 6867.63 | 0.70 | - | 4659.65 | 47.26 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3932.82 | 7101.82 | 4972.54 | 2129.28 | 0.70 | - | 1446.39 | 14.67 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3895.30 | 7033.97 | 4924.98 | 2108.99 | 0.70 | - | 1432.52 | 14.53 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 15154.48 | 27192.30 | 18929.77 | 8262.53 | 0.70 | - | 5442.59 | 55.20 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 602722.19 | 726967.91 | 422029.09 | 304938.82 | 0.58 | - | 111647.23 | 1132.39 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 45130.47 | 52559.35 | 31349.81 | 21209.54 | 0.60 | - | 6662.86 | 67.58 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 13521.73 | 13600.99 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5153.73 | 5187.90 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2148.93 | 2161.23 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2901.74 | 2917.93 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1632.23 | 1643.14 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19030.46 | 19141.52 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16370.02 | 16460.52 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 42694.75 | 42938.77 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6212.54 | 6706.17 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6218.92 | 6713.06 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 35428.68 | 38243.65 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 35552.20 | 38376.97 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6212.54 | 6706.17 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6218.92 | 6713.06 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14424.66 | 14520.77 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1994.47 | 2152.88 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1999.07 | 2157.85 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 9670.53 | 10438.59 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 18790.09 | 18897.98 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19493.18 | 19605.17 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13722.12 | 13802.11 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10829.92 | 10900.48 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 265175.91 | 174701.40 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20912.17 | 13777.22 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.45 | 2458.22 | 1693.12 | 1.00 | 0.46 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.44 | 2433.43 | 1693.12 | 1.00 | 0.47 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 7.55 | 12789.19 | 1693.12 | 1.00 | 0.39 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 8.13 | 13760.26 | 1693.12 | 1.00 | 0.39 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.27 | 2151.80 | 1693.12 | 1.00 | 0.48 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.26 | 2140.90 | 1693.12 | 1.00 | 0.48 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 0.39 | 664.36 | 1693.12 | 1.00 | 0.64 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 0.39 | 658.00 | 1693.12 | 1.00 | 0.65 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.16 | 270.90 | 1.49 | 2516.41 | 1693.12 | 1.00 | 0.46 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.01 | 58279.33 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.031616 | 7572.33 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.012733 | 3253.08 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.031616 | 2524.11 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35674.43 | 35674.43 | 18.03 | 3.193 | 3.193 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 24.00 | 24.00 | 0.00918 | 26.77 | 0.00543 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4409.04 | 4409.04 | 65.74 | 0.395 | 0.395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00890 | 33.65 | 0.00543 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3318.42 | 3318.42 | 42.73 | 0.297 | 0.297 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00931 | 32.62 | 0.00543 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44921.26 | 44921.26 | 575.62 | 4.021 | 4.021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00853 | 33.90 | 0.00543 | 0.236 | 0.00 |
CAFE_FLR_1 | 19062.03 | 19062.03 | 100.93 | 1.708 | 1.708 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01006 | 33.65 | 0.00543 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64188.98 | 64188.98 | 49.07 | 5.748 | 5.748 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00992 | 33.90 | 0.00543 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 12037.64 | 12037.64 | 308.48 | 1.452 | 1.452 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11916.26 | 11916.26 | 305.41 | 1.437 | 1.437 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 62629.14 | 62629.14 | 2553.81 | 7.554 | 7.554 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00845 | 33.75 | 0.00543 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 67378.93 | 67378.93 | 2746.74 | 8.127 | 8.127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00867 | 33.75 | 0.00543 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10537.16 | 10537.16 | 270.03 | 1.271 | 1.271 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00852 | 25.76 | 0.00543 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10483.78 | 10483.78 | 268.69 | 1.264 | 1.264 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00852 | 25.76 | 0.00543 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 3253.28 | 3253.28 | 83.37 | 0.392 | 0.392 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3222.14 | 3222.14 | 82.58 | 0.389 | 0.389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12322.15 | 12322.15 | 502.32 | 1.486 | 1.486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00859 | 33.90 | 0.00543 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31074.41 | 31074.41 | 93.69 | 2.785 | 2.785 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01029 | 33.90 | 0.00543 | 1.187 | 0.00 |
DINING_FLR_6 | 32619.99 | 32619.99 | 98.35 | 2.924 | 2.924 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01021 | 33.90 | 0.00543 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 31468.95 | 31468.95 | 304.62 | 2.825 | 2.825 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01003 | 32.57 | 0.00543 | 0.367 | 0.00 |
MECH_FLR_1 | 3737.98 | 3737.98 | 22.76 | 0.335 | 0.335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00842 | 33.01 | 0.00543 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1562.17 | 1562.17 | 16.49 | 0.140 | 0.140 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00838 | 33.75 | 0.00543 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11081.08 | 11081.08 | 28.46 | 0.992 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00842 | 33.31 | 0.00543 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8597.24 | 8597.24 | 20.86 | 0.769 | 0.769 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00845 | 33.90 | 0.00543 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3485.30 | 3485.30 | 51.96 | 0.184 | 0.184 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00724 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 892.53 | 892.53 | 11.49 | 0.047 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00737 | -17.90 | 0.00096 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2033.11 | 2033.11 | 26.05 | 0.107 | 0.236 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -17.90 | 0.00096 | 0.236 | 0.00 |
CAFE_FLR_1 | 9149.65 | 9149.65 | 48.45 | 0.483 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00727 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 18389.33 | 18389.33 | 14.06 | 0.971 | 1.893 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00727 | -17.90 | 0.00096 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 6212.76 | 6212.76 | 159.21 | 0.330 | 0.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6219.14 | 6219.14 | 159.39 | 0.330 | 0.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 35429.27 | 35429.27 | 1444.69 | 1.882 | 1.882 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 35552.79 | 35552.79 | 1449.33 | 1.888 | 1.888 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6212.76 | 6212.76 | 159.21 | 0.330 | 0.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6219.14 | 6219.14 | 159.39 | 0.330 | 0.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1994.53 | 1994.53 | 51.11 | 0.106 | 0.106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1999.14 | 1999.14 | 51.24 | 0.106 | 0.106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9670.78 | 9670.78 | 394.23 | 0.514 | 0.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7003.49 | 7003.49 | 21.12 | 0.370 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 1.187 | 0.00 |
DINING_FLR_6 | 7120.75 | 7120.75 | 21.47 | 0.376 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 1811.21 | 1811.21 | 17.53 | 0.096 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00623 | -17.90 | 0.00096 | 0.367 | 0.00 |
MECH_FLR_1 | 1487.33 | 1487.33 | 9.06 | 0.079 | 0.079 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00719 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1041.13 | 1041.13 | 10.99 | 0.055 | 0.058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00719 | -17.90 | 0.00096 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9402.81 | 9402.81 | 24.15 | 0.497 | 0.497 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -17.90 | 0.00096 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7573.40 | 7573.40 | 18.38 | 0.400 | 0.400 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.00 | 26.00 | 7.71 | 7.71 | 26.0101 | 26.0101 | 26.0101 | 1.0000 | 0.3000 |
FLR_3_DOAS | 22.31 | 2.05 | 5.82 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 13521.733 | 13521.733 | 3.154987 | 0.00029875 | 239.274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 13600.99 | 13521.73 | 3.154987 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13601.93 | 13601.93 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5153.729 | 5153.729 | 0.389940 | 0.00011387 | 101.653 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5187.90 | 5153.73 | 0.389940 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00724256 | 38.0536 | 3485.30 | 0.00 | 5188.51 | 5188.51 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2148.929 | 2148.929 | 0.293508 | 0.00004748 | 39.605 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2161.23 | 2148.93 | 0.293508 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00736688 | 38.6969 | 892.53 | 0.00 | 2161.49 | 2161.49 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2901.736 | 2901.736 | 0.330528 | 0.00006411 | 54.570 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2917.93 | 2901.74 | 0.330528 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00718687 | 37.7621 | 1487.33 | 0.00 | 2918.35 | 2918.35 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1632.230 | 1632.230 | 0.138133 | 0.00003606 | 31.855 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1643.14 | 1632.23 | 0.138133 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00719177 | 37.7877 | 1041.13 | 0.00 | 1643.30 | 1643.30 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19030.462 | 19030.462 | 3.972581 | 0.00042045 | 338.989 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19141.52 | 19030.46 | 3.972581 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00717153 | 37.6835 | 2033.11 | 0.00 | 19143.01 | 19143.01 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 16370.019 | 16370.019 | 1.687396 | 0.00036168 | 311.909 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16460.52 | 16370.02 | 1.687396 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00726883 | 38.1898 | 9149.65 | 0.00 | 16463.18 | 16463.18 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 42694.755 | 42694.755 | 5.679093 | 0.00094329 | 788.994 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42938.77 | 42694.75 | 5.679093 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00727379 | 38.2137 | 18389.33 | 0.00 | 42944.07 | 42944.07 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14556.448 | -999.000 | 1.451883 | 0.00051991 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 14556.45 | 14514.01 | 1.451883 | 22.81 | 13.84 | 0.00851681 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851681 | 44.3517 | 12037.64 | 0.00 | 18089.92 | 16899.81 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6212.543 | 6212.543 | 0.329971 | 0.00013726 | 141.439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6706.17 | 6212.54 | 0.329971 | 21.11 | 12.37 | 0.00748416 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00748416 | 39.0397 | 6212.76 | 0.00 | 6706.64 | 6706.64 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 14410.182 | -999.000 | 1.437244 | 0.00051469 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 14410.18 | 14367.82 | 1.437244 | 22.81 | 13.84 | 0.00851695 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851695 | 44.3525 | 11916.26 | 0.00 | 17908.07 | 16729.42 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6218.924 | 6218.924 | 0.330310 | 0.00013740 | 141.584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6713.06 | 6218.92 | 0.330310 | 21.11 | 12.37 | 0.00748469 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00748469 | 39.0425 | 6219.14 | 0.00 | 6713.53 | 6713.53 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75413.125 | -999.000 | 7.553598 | 0.00269353 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 75413.12 | 75413.12 | 7.553598 | 22.81 | 13.79 | 0.00845436 | 12.80 | 10.21 | 0.00845436 | 33.75 | 0.00543030 | 14.95 | 0.0000 | 21.11 | 0.00845436 | 44.0302 | 62629.14 | 0.00 | 93874.95 | 88371.06 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 35428.682 | 35428.682 | 1.881790 | 0.00078275 | 806.586 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38243.65 | 35428.68 | 1.881790 | 21.11 | 12.40 | 0.00751798 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00751798 | 39.2130 | 35429.27 | 0.00 | 38246.68 | 38246.68 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 84529.060 | -999.000 | 8.127137 | 0.00301913 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 84529.06 | 82128.70 | 8.127137 | 22.81 | 13.97 | 0.00866799 | 12.80 | 10.21 | 0.00850000 | 33.75 | 0.00543030 | 14.95 | 0.0000 | 21.11 | 0.00866799 | 45.1294 | 67378.93 | 0.00 | 104603.14 | 94723.67 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 35552.197 | 35552.197 | 1.888351 | 0.00078548 | 809.397 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38376.97 | 35552.20 | 1.888351 | 21.11 | 12.41 | 0.00751941 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00751941 | 39.2204 | 35552.79 | 0.00 | 38380.02 | 38380.02 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12745.617 | -999.000 | 1.270906 | 0.00045524 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 12745.62 | 12705.93 | 1.270906 | 22.81 | 13.85 | 0.00851795 | 12.80 | 10.21 | 0.00850000 | 25.76 | 0.00543031 | 12.23 | 0.0000 | 21.11 | 0.00851795 | 44.3576 | 10537.16 | 0.00 | 15838.98 | 14793.39 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6212.543 | 6212.543 | 0.329971 | 0.00013726 | 141.439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6706.17 | 6212.54 | 0.329971 | 21.11 | 12.37 | 0.00748416 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00748416 | 39.0397 | 6212.76 | 0.00 | 6706.64 | 6706.64 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12681.433 | -999.000 | 1.264468 | 0.00045294 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 12681.43 | 12641.68 | 1.264468 | 22.81 | 13.85 | 0.00851808 | 12.80 | 10.21 | 0.00850000 | 25.76 | 0.00543031 | 12.23 | 0.0000 | 21.11 | 0.00851808 | 44.3582 | 10483.78 | 0.00 | 15759.16 | 14718.47 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6218.924 | 6218.924 | 0.330310 | 0.00013740 | 141.584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6713.06 | 6218.92 | 0.330310 | 21.11 | 12.37 | 0.00748469 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00748469 | 39.0425 | 6219.14 | 0.00 | 6713.53 | 6713.53 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14424.664 | 14424.664 | 1.172663 | 0.00031870 | 282.523 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14520.77 | 14424.66 | 1.172663 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00757928 | 39.7988 | 9402.81 | 0.00 | 14522.29 | 14522.29 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3932.821 | -999.000 | 0.392385 | 0.00014047 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3932.82 | 3922.19 | 0.392385 | 22.81 | 13.84 | 0.00851558 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851558 | 44.3454 | 3253.28 | 0.00 | 4887.66 | 4567.29 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1994.467 | 1994.467 | 0.105933 | 0.00004407 | 45.405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2152.88 | 1994.47 | 0.105933 | 21.11 | 12.47 | 0.00759159 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00759159 | 39.5934 | 1994.53 | 0.00 | 2153.09 | 2153.09 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3895.296 | -999.000 | 0.388629 | 0.00013913 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3895.30 | 3884.68 | 0.388629 | 22.81 | 13.84 | 0.00851571 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851571 | 44.3461 | 3222.14 | 0.00 | 4841.01 | 4523.57 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1999.073 | 1999.073 | 0.106178 | 0.00004417 | 45.510 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2157.85 | 1999.07 | 0.106178 | 21.11 | 12.47 | 0.00759251 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00759251 | 39.5981 | 1999.14 | 0.00 | 2158.06 | 2158.06 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15154.483 | -999.000 | 1.486251 | 0.00054127 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 15154.48 | 14932.08 | 1.486251 | 22.81 | 13.90 | 0.00858561 | 12.80 | 10.21 | 0.00850000 | 33.90 | 0.00543030 | 15.00 | 0.0000 | 21.11 | 0.00858561 | 44.7060 | 12322.15 | 0.00 | 18798.22 | 17310.98 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9670.533 | 9670.533 | 0.513642 | 0.00021366 | 220.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10438.59 | 9670.53 | 0.513642 | 21.11 | 12.49 | 0.00761103 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00761103 | 39.6932 | 9670.78 | 0.00 | 10439.68 | 10439.68 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18790.090 | 18790.090 | 2.751754 | 0.00041514 | 343.971 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 18897.98 | 18790.09 | 2.751754 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770924 | 40.4732 | 7003.49 | 0.00 | 18900.09 | 18900.09 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19493.175 | 19493.175 | 2.888569 | 0.00043068 | 356.453 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 19605.17 | 19493.18 | 2.888569 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771383 | 40.4973 | 7120.75 | 0.00 | 19607.33 | 19607.33 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13722.118 | 13722.118 | 2.790784 | 0.00030317 | 244.839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 13802.11 | 13722.12 | 2.790784 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00623254 | 32.8053 | 1811.21 | 0.00 | 13803.21 | 13803.21 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10829.921 | 10829.921 | 0.760207 | 0.00023927 | 215.363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10900.48 | 10829.92 | 0.760207 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776253 | 40.7495 | 7573.40 | 0.00 | 10901.90 | 10901.90 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 602722.193 | -999.000 | 26.010142 | 0.02152784 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 602722.19 | 602722.19 | 26.010142 | 33.90 | 15.00 | 0.00543030 | 10.54 | 6.13 | 0.00543030 | 33.90 | 0.00543030 | 15.00 | 99.9532 | 23.99 | 0.00941530 | 41.1013 | 290235.29 | 0.00 | 661579.97 | 661579.97 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 265175.912 | 265175.912 | 7.803043 | 0.00585874 | 3548.607 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 174701.40 | 265175.91 | 7.803043 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.23 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.1773 | 21.00 | 0.00749591 | 39.3671 | 68786.48 | 0.00 | 174336.23 | 174336.23 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45130.466 | -999.000 | 2.051199 | 0.00161196 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 45130.47 | 45130.47 | 2.051199 | 33.90 | 15.00 | 0.00543030 | 10.54 | 7.12 | 0.00543030 | 33.90 | 0.00543030 | 15.00 | 100.0000 | 21.11 | 0.00856443 | 44.5967 | 182321.32 | 0.00 | 49768.56 | 49768.56 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20912.173 | 20912.173 | 0.615360 | 0.00046203 | 279.848 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13777.22 | 20912.17 | 0.615360 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.23 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3333 | 21.11 | 0.00751958 | 39.2213 | 109510.30 | 0.00 | 13748.42 | 13748.42 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 13521.733 | 13521.733 | 3.154987 | 0.00029875 | 239.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 2.3135 | 2.346262 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 13600.99 | 13521.73 | 1.0000 | 3.08380248 | 3.154987 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.29871570 | 60.00 | 49.00 | 11.00 | 0.000 | 13600.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13601.93 | 13601.93 | 3.08380248 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5153.729 | 5153.729 | 0.389940 | 0.00011387 | 101.653 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.8824 | 0.894264 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5187.90 | 5153.73 | 1.0000 | 0.38114223 | 0.389940 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.11385372 | 60.00 | 49.00 | 11.00 | 0.000 | 5187.90 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00724256 | 21.00 | 0.00724256 | 38.0536 | 3485.30 | 0.00 | 5188.51 | 5188.51 | 0.38114223 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.95 | 18.00 | 0.00800000 | 50547.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2148.929 | 2148.929 | 0.293508 | 0.00004748 | 39.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.3676 | 0.372878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2161.23 | 2148.93 | 1.0000 | 0.28688550 | 0.293508 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04747311 | 60.00 | 49.00 | 11.00 | 0.000 | 2161.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00736688 | 21.00 | 0.00736688 | 38.6969 | 892.53 | 0.00 | 2161.49 | 2161.49 | 0.28688550 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.99 | 15.93 | 0.00800000 | 44469.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2901.736 | 2901.736 | 0.330528 | 0.00006411 | 54.570 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.4963 | 0.503503 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2917.93 | 2901.74 | 1.0000 | 0.32307035 | 0.330528 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.06410377 | 60.00 | 49.00 | 11.00 | 0.000 | 2917.93 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00718687 | 21.00 | 0.00718687 | 37.7621 | 1487.33 | 0.00 | 2918.35 | 2918.35 | 0.32307035 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 25.46 | 16.46 | 0.00800000 | 45967.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1632.230 | 1632.230 | 0.138133 | 0.00003606 | 31.855 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.2795 | 0.283221 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1643.14 | 1632.23 | 1.0000 | 0.13501633 | 0.138133 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.03605846 | 60.00 | 49.00 | 11.00 | 0.000 | 1643.14 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00719177 | 21.00 | 0.00719177 | 37.7877 | 1041.13 | 0.00 | 1643.30 | 1643.30 | 0.13501633 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.54 | 17.52 | 0.00800000 | 49105.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19030.462 | 19030.462 | 3.972581 | 0.00042045 | 338.989 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 3.2559 | 3.302125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19141.52 | 19030.46 | 1.0000 | 3.88294973 | 3.972581 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.42041192 | 60.00 | 49.00 | 11.00 | 0.000 | 19141.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00717153 | 21.00 | 0.00717153 | 37.6835 | 2033.11 | 0.00 | 19143.01 | 19143.01 | 3.88294973 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.43 | 15.00 | 0.00800000 | 41864.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16370.019 | 16370.019 | 1.687396 | 0.00036168 | 311.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 2.7998 | 2.840491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16460.52 | 16370.02 | 1.0000 | 1.64932458 | 1.687396 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.36163867 | 60.00 | 49.00 | 11.00 | 0.000 | 16460.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00726883 | 21.00 | 0.00726883 | 38.1898 | 9149.65 | 0.00 | 16463.18 | 16463.18 | 1.64932458 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.39 | 16.78 | 0.00800000 | 46916.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42694.755 | 42694.755 | 5.679093 | 0.00094329 | 788.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 7.3037 | 7.408303 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42938.77 | 42694.75 | 1.0000 | 5.55095938 | 5.679093 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.94319221 | 60.00 | 49.00 | 11.00 | 0.000 | 42938.77 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00727379 | 21.00 | 0.00727379 | 38.2137 | 18389.33 | 0.00 | 42944.07 | 42944.07 | 5.55095938 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.19 | 16.00 | 0.00800000 | 44671.1 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14556.448 | -999.000 | 1.451883 | 0.00051991 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6723 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.451883 | 1.41912551 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 1.6445 | 1.644456 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 14556.45 | 14514.01 | 1.0000 | 1.41912551 | 1.451883 | 22.81 | 13.84 | 0.00851681 | 44579.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.51985984 | 6.70 | 11.72 | 6.67 | 0.000 | 14556.45 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851681 | 21.11 | 0.00851681 | 44.3517 | 12037.64 | 0.00 | 18089.92 | 16899.81 | 1.41912551 | 22.81 | 15.96 | 0.00851681 | 44579.5 | 11.14 | 11.08 | 0.00818424 | 31832.3 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6212.543 | 6212.543 | 0.329971 | 0.00013726 | 141.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.451883 | 1.41912551 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.1407 | 1.077987 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6706.17 | 6212.54 | 1.0000 | 0.32252604 | 0.329971 | 21.11 | 12.37 | 0.00748416 | 40223.5 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13724454 | 60.00 | 49.00 | 11.00 | 0.000 | 6706.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748416 | 21.11 | 0.00748416 | 39.0397 | 6212.76 | 0.00 | 6706.64 | 6706.64 | 0.32252604 | 16.60 | 12.64 | 0.00748416 | 35628.7 | 37.01 | 19.86 | 0.00748416 | 56422.8 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14410.182 | -999.000 | 1.437244 | 0.00051469 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6726 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.437244 | 1.40481589 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 1.6280 | 1.627932 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 14410.18 | 14367.82 | 1.0000 | 1.40481589 | 1.437244 | 22.81 | 13.84 | 0.00851695 | 44579.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.51463621 | 6.70 | 11.72 | 6.67 | 0.000 | 14410.18 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851695 | 21.11 | 0.00851695 | 44.3525 | 11916.26 | 0.00 | 17908.07 | 16729.42 | 1.40481589 | 22.81 | 15.96 | 0.00851695 | 44579.9 | 11.14 | 11.08 | 0.00818423 | 31832.3 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6218.924 | 6218.924 | 0.330310 | 0.00013740 | 141.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.437244 | 1.40481589 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.1419 | 1.079094 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6713.06 | 6218.92 | 1.0000 | 0.32285733 | 0.330310 | 21.11 | 12.37 | 0.00748469 | 40224.9 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13738551 | 60.00 | 49.00 | 11.00 | 0.000 | 6713.06 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748469 | 21.11 | 0.00748469 | 39.0425 | 6219.14 | 0.00 | 6713.53 | 6713.53 | 0.32285733 | 16.60 | 12.64 | 0.00748469 | 35630.1 | 37.01 | 19.86 | 0.00748469 | 56424.2 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75413.125 | -999.000 | 7.553598 | 0.00269353 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5562 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 7.553598 | 7.38317085 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 8.5197 | 8.519493 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | 75413.12 | 75413.12 | 1.0000 | 7.38317085 | 7.553598 | 22.81 | 13.79 | 0.00845436 | 44421.1 | 12.80 | 10.21 | 0.00845436 | 34322.2 | 2.69325701 | 6.70 | 11.72 | 6.67 | 0.000 | 75413.12 | 33.75 | 0.00543030 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00845436 | 21.11 | 0.00845436 | 44.0302 | 62629.14 | 0.00 | 93874.95 | 88371.06 | 7.38317085 | 22.81 | 15.91 | 0.00845436 | 44421.1 | 11.08 | 11.03 | 0.00815872 | 31706.4 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35428.682 | 35428.682 | 1.881790 | 0.00078275 | 806.586 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 7.553598 | 7.38317085 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 6.5050 | 6.147509 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38243.65 | 35428.68 | 1.0000 | 1.83933265 | 1.881790 | 21.11 | 12.40 | 0.00751798 | 40309.8 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.78267360 | 60.00 | 49.00 | 11.00 | 0.000 | 38243.65 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00751798 | 21.11 | 0.00751798 | 39.2130 | 35429.27 | 0.00 | 38246.68 | 38246.68 | 1.83933265 | 16.60 | 12.67 | 0.00751798 | 35714.3 | 37.01 | 19.89 | 0.00751798 | 56508.1 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 84529.060 | -999.000 | 8.127137 | 0.00301913 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9534 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 8.127137 | 7.94376973 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 9.5495 | 9.549329 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | 84529.06 | 82128.70 | 1.0000 | 7.94376973 | 8.127137 | 22.81 | 13.97 | 0.00866799 | 44963.1 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 3.01881782 | 6.70 | 11.72 | 6.67 | 0.000 | 84529.06 | 33.75 | 0.00543030 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00866799 | 21.11 | 0.00866799 | 45.1294 | 67378.93 | 0.00 | 104603.14 | 94723.67 | 7.94376973 | 22.81 | 16.09 | 0.00866799 | 44963.1 | 11.13 | 11.07 | 0.00817479 | 31795.2 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35552.197 | 35552.197 | 1.888351 | 0.00078548 | 809.397 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 8.127137 | 7.94376973 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 6.5277 | 6.168941 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38376.97 | 35552.20 | 1.0000 | 1.84574512 | 1.888351 | 21.11 | 12.41 | 0.00751941 | 40313.5 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.78540223 | 60.00 | 49.00 | 11.00 | 0.000 | 38376.97 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00751941 | 21.11 | 0.00751941 | 39.2204 | 35552.79 | 0.00 | 38380.02 | 38380.02 | 1.84574512 | 16.60 | 12.67 | 0.00751941 | 35718.0 | 37.01 | 19.89 | 0.00751941 | 56511.8 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12745.617 | -999.000 | 1.270906 | 0.00045524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6745 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.270906 | 1.24223131 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 1.4399 | 1.439885 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 12745.62 | 12705.93 | 1.0000 | 1.24223131 | 1.270906 | 22.81 | 13.85 | 0.00851795 | 44582.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.45518897 | 6.70 | 11.72 | 6.67 | 0.000 | 12745.62 | 25.76 | 0.00543031 | 12.23 | 0.00000000 | 0.0000 | 21.11 | 0.00851795 | 21.11 | 0.00851795 | 44.3576 | 10537.16 | 0.00 | 15838.98 | 14793.39 | 1.24223131 | 22.81 | 15.96 | 0.00851795 | 44582.5 | 11.14 | 11.08 | 0.00818417 | 31832.0 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6212.543 | 6212.543 | 0.329971 | 0.00013726 | 141.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.270906 | 1.24223131 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.1407 | 1.077987 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6706.17 | 6212.54 | 1.0000 | 0.32252604 | 0.329971 | 21.11 | 12.37 | 0.00748416 | 40223.5 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13724454 | 60.00 | 49.00 | 11.00 | 0.000 | 6706.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748416 | 21.11 | 0.00748416 | 39.0397 | 6212.76 | 0.00 | 6706.64 | 6706.64 | 0.32252604 | 16.60 | 12.64 | 0.00748416 | 35628.7 | 37.01 | 19.86 | 0.00748416 | 56422.8 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12681.433 | -999.000 | 1.264468 | 0.00045294 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6747 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.264468 | 1.23593858 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 1.4327 | 1.432634 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 12681.43 | 12641.68 | 1.0000 | 1.23593858 | 1.264468 | 22.81 | 13.85 | 0.00851808 | 44582.8 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.45289673 | 6.70 | 11.72 | 6.67 | 0.000 | 12681.43 | 25.76 | 0.00543031 | 12.23 | 0.00000000 | 0.0000 | 21.11 | 0.00851808 | 21.11 | 0.00851808 | 44.3582 | 10483.78 | 0.00 | 15759.16 | 14718.47 | 1.23593858 | 22.81 | 15.96 | 0.00851808 | 44582.8 | 11.14 | 11.08 | 0.00818416 | 31832.0 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6218.924 | 6218.924 | 0.330310 | 0.00013740 | 141.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.264468 | 1.23593858 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.1419 | 1.079094 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6713.06 | 6218.92 | 1.0000 | 0.32285733 | 0.330310 | 21.11 | 12.37 | 0.00748469 | 40224.9 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13738551 | 60.00 | 49.00 | 11.00 | 0.000 | 6713.06 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00748469 | 21.11 | 0.00748469 | 39.0425 | 6219.14 | 0.00 | 6713.53 | 6713.53 | 0.32285733 | 16.60 | 12.64 | 0.00748469 | 35630.1 | 37.01 | 19.86 | 0.00748469 | 56424.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14424.664 | 14424.664 | 1.172663 | 0.00031870 | 282.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 2.4699 | 2.502937 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14520.77 | 14424.66 | 1.0000 | 1.14620452 | 1.172663 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.31866281 | 60.00 | 49.00 | 11.00 | 0.000 | 14520.77 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00757928 | 21.00 | 0.00757928 | 39.7988 | 9402.81 | 0.00 | 14522.29 | 14522.29 | 1.14620452 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.02 | 17.69 | 0.00800000 | 49604.6 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3932.821 | -999.000 | 0.392385 | 0.00014047 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6700 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.392385 | 0.38353174 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 0.4443 | 0.444295 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 3932.82 | 3922.19 | 1.0000 | 0.38353174 | 0.392385 | 22.81 | 13.84 | 0.00851558 | 44576.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.14045432 | 6.70 | 11.72 | 6.67 | 0.000 | 3932.82 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851558 | 21.11 | 0.00851558 | 44.3454 | 3253.28 | 0.00 | 4887.66 | 4567.29 | 0.38353174 | 22.81 | 15.96 | 0.00851558 | 44576.4 | 11.14 | 11.08 | 0.00818431 | 31832.6 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1994.467 | 1994.467 | 0.105933 | 0.00004407 | 45.405 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.392385 | 0.38353174 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.3662 | 0.346076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2152.88 | 1994.47 | 1.0000 | 0.10354336 | 0.105933 | 21.11 | 12.47 | 0.00759159 | 40496.4 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04406081 | 60.00 | 49.00 | 11.00 | 0.000 | 2152.88 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00759159 | 21.11 | 0.00759159 | 39.5934 | 1994.53 | 0.00 | 2153.09 | 2153.09 | 0.10354336 | 16.60 | 12.74 | 0.00759159 | 35900.7 | 37.01 | 19.94 | 0.00759159 | 56694.8 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3895.296 | -999.000 | 0.388629 | 0.00013913 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6703 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.388629 | 0.37986038 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 0.4401 | 0.440055 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 3895.30 | 3884.68 | 1.0000 | 0.37986038 | 0.388629 | 22.81 | 13.84 | 0.00851571 | 44576.7 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.13911416 | 6.70 | 11.72 | 6.67 | 0.000 | 3895.30 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851571 | 21.11 | 0.00851571 | 44.3461 | 3222.14 | 0.00 | 4841.01 | 4523.57 | 0.37986038 | 22.81 | 15.96 | 0.00851571 | 44576.7 | 11.14 | 11.08 | 0.00818431 | 31832.6 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1999.073 | 1999.073 | 0.106178 | 0.00004417 | 45.510 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.388629 | 0.37986038 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 0.3670 | 0.346875 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2157.85 | 1999.07 | 1.0000 | 0.10378249 | 0.106178 | 21.11 | 12.47 | 0.00759251 | 40498.8 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04416256 | 60.00 | 49.00 | 11.00 | 0.000 | 2157.85 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00759251 | 21.11 | 0.00759251 | 39.5981 | 1999.14 | 0.00 | 2158.06 | 2158.06 | 0.10378249 | 16.60 | 12.74 | 0.00759251 | 35903.1 | 37.01 | 19.94 | 0.00759251 | 56697.2 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15154.483 | -999.000 | 1.486251 | 0.00054127 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8002 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.486251 | 1.45271717 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 1.7120 | 1.712017 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | 15154.48 | 14932.08 | 1.0000 | 1.45271717 | 1.486251 | 22.81 | 13.90 | 0.00858561 | 44754.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.54121770 | 6.70 | 11.72 | 6.67 | 0.000 | 15154.48 | 33.90 | 0.00543030 | 15.00 | 0.00000000 | 0.0000 | 21.11 | 0.00858561 | 21.11 | 0.00858561 | 44.7060 | 12322.15 | 0.00 | 18798.22 | 17310.98 | 1.45271717 | 22.81 | 16.02 | 0.00858561 | 44754.0 | 11.13 | 11.07 | 0.00817962 | 31814.0 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9670.533 | 9670.533 | 0.513642 | 0.00021366 | 220.156 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.486251 | 1.45271717 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.7755 | 1.678010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10438.59 | 9670.53 | 1.0000 | 0.50205279 | 0.513642 | 21.11 | 12.49 | 0.00761103 | 40546.0 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.21363682 | 60.00 | 49.00 | 11.00 | 0.000 | 10438.59 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00761103 | 21.11 | 0.00761103 | 39.6932 | 9670.78 | 0.00 | 10439.68 | 10439.68 | 0.50205279 | 16.60 | 12.76 | 0.00761103 | 35949.9 | 37.01 | 19.96 | 0.00761103 | 56743.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18790.090 | 18790.090 | 2.751754 | 0.00041514 | 343.971 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 3.2144 | 3.260416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 18897.98 | 18790.09 | 1.0000 | 2.68966794 | 2.751754 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.41510174 | 60.00 | 49.00 | 11.00 | 0.000 | 18897.98 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00770924 | 21.00 | 0.00770924 | 40.4732 | 7003.49 | 0.00 | 18900.09 | 18900.09 | 2.68966794 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.49 | 15.75 | 0.00800000 | 43961.7 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19493.175 | 19493.175 | 2.888569 | 0.00043068 | 356.453 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 3.3347 | 3.382414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 19605.17 | 19493.18 | 1.0000 | 2.82339595 | 2.888569 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.43063395 | 60.00 | 49.00 | 11.00 | 0.000 | 19605.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00771383 | 21.00 | 0.00771383 | 40.4973 | 7120.75 | 0.00 | 19607.33 | 19607.33 | 2.82339595 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.41 | 15.72 | 0.00800000 | 43879.3 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13722.118 | 13722.118 | 2.790784 | 0.00030317 | 244.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 2.3477 | 2.381033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 13802.11 | 13722.12 | 1.0000 | 2.72781697 | 2.790784 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.30314251 | 60.00 | 49.00 | 11.00 | 0.000 | 13802.11 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.46 | 0.00623254 | 21.00 | 0.00623254 | 32.8053 | 1811.21 | 0.00 | 13803.21 | 13803.21 | 2.72781697 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.56 | 15.05 | 0.00800000 | 41994.9 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10829.921 | 10829.921 | 0.760207 | 0.00023927 | 215.363 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 1.8541 | 1.879185 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10900.48 | 10829.92 | 1.0000 | 0.74305506 | 0.760207 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.23924947 | 60.00 | 49.00 | 11.00 | 0.000 | 10900.48 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00776253 | 21.00 | 0.00776253 | 40.7495 | 7573.40 | 0.00 | 10901.90 | 10901.90 | 0.74305506 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.99 | 18.34 | 0.00800000 | 51606.5 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 602722.193 | -999.000 | 26.010142 | 0.02152784 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1014.9347 | 1004.8586 | 0.9774 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 26.010142 | 25.42329102 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 68.0914 | 68.091377 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 602722.19 | 602722.19 | 1.0000 | 25.42329102 | 26.010142 | 33.90 | 15.00 | 0.00543030 | 47987.2 | 10.54 | 6.13 | 0.00543030 | 24279.7 | 21.52564414 | 6.70 | 11.72 | 6.67 | 58279.328 | 544442.86 | 33.90 | 0.00543030 | 15.00 | 25.99797000 | 99.9532 | 23.99 | 0.00955591 | 23.99 | 0.00941530 | 41.1013 | 290235.29 | 0.00 | 661579.97 | 661579.97 | 25.42329102 | 33.90 | 17.20 | 0.00543030 | 47987.2 | 8.26 | 6.68 | 0.00543030 | 21964.6 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 265175.912 | 265175.912 | 7.803043 | 0.00585874 | 3548.607 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 26.010142 | 25.42329102 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 29.7158 | 46.012758 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 174701.40 | 265175.91 | 1.0000 | 7.62698731 | 7.803043 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 5.85814010 | 60.00 | 49.00 | 11.00 | 0.000 | 174701.40 | -17.90 | 0.00095524 | -17.90 | 25.99797000 | 333.1773 | 18.61 | 0.00647182 | 21.00 | 0.00749591 | 39.3671 | 68786.48 | 0.00 | 174336.23 | 174336.23 | 7.62698731 | 16.60 | 5.28 | 0.00095524 | 19098.8 | 39.31 | 15.17 | 0.00095524 | 41956.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45130.466 | -999.000 | 2.051199 | 0.00161196 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1014.9347 | 1004.8586 | 0.9774 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.00491910 | 4197.9300 | 999.8980 | 31.61287815 | 13.37 | 6.70 | 6.67 | 885166.69 | 5.0985 | 5.098527 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 45130.47 | 45130.47 | 1.0000 | 2.00491910 | 2.051199 | 33.90 | 15.00 | 0.00543030 | 47987.2 | 10.54 | 7.12 | 0.00543030 | 26572.0 | 1.61179124 | 6.70 | 11.72 | 6.67 | 2194.880 | 42935.59 | 33.90 | 0.00543030 | 15.00 | 2.05119905 | 100.0000 | 21.11 | 0.00855718 | 21.11 | 0.00856443 | 44.5967 | 182321.32 | 0.00 | 49768.56 | 49768.56 | 2.00491910 | 33.90 | 17.20 | 0.00543030 | 47987.2 | 9.44 | 7.25 | 0.00543030 | 23163.9 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20912.173 | 20912.173 | 0.615360 | 0.00046203 | 279.848 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.00491910 | 4197.9300 | 999.8980 | 12.73155604 | 71.00 | 82.00 | 11.00 | 587907.99 | 2.3434 | 3.628636 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13777.22 | 20912.17 | 1.0000 | 0.60147573 | 0.615360 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 0.46198177 | 60.00 | 49.00 | 11.00 | 0.000 | 13777.22 | -17.90 | 0.00095524 | -17.90 | 2.05119905 | 333.3333 | 21.11 | 0.00752174 | 21.11 | 0.00751958 | 39.2213 | 109510.30 | 0.00 | 13748.42 | 13748.42 | 0.60147573 | 16.60 | 5.28 | 0.00095524 | 19098.8 | 39.31 | 15.17 | 0.00095524 | 41956.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 26.00 | 26.01 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 645.17 | 8760.00 | 645.17 |
RETAIL_1_FLR_1 | 1558.33 | 8357.33 | 1407.83 |
RETAIL_2_FLR_1 | 164.67 | 8760.00 | 164.67 |
LAUNDRY_FLR_1 | 2389.83 | 5776.83 | 960.67 |
CAFE_FLR_1 | 657.67 | 8383.83 | 530.83 |
LOBBY_FLR_1 | 99.83 | 8760.00 | 99.83 |
ROOM_1_FLR_3 | 1516.83 | 8490.00 | 1498.00 |
ROOM_2_FLR_3 | 2297.00 | 8592.33 | 2281.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1101.00 | 8760.00 | 1101.00 |
ROOM_5_FLR_3 | 1513.50 | 8465.83 | 1490.00 |
ROOM_6_FLR_3 | 2268.67 | 8554.50 | 2246.67 |
ROOM_1_FLR_6 | 2229.67 | 8153.83 | 2141.50 |
ROOM_2_FLR_6 | 2989.83 | 8346.67 | 2923.50 |
ROOM_3_MULT9_FLR_6 | 1185.17 | 7943.83 | 1117.83 |
BANQUET_FLR_6 | 99.67 | 8760.00 | 99.67 |
DINING_FLR_6 | 28.00 | 8758.00 | 28.00 |
KITCHEN_FLR_6 | 6406.83 | 6617.83 | 4671.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 7594.33 | 8760.00 | 6638.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 584.17 | 0.00 | 584.17 | 0.00 |
RETAIL_1_FLR_1 | 45.83 | 1.83 | 45.83 | 1.83 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 31.33 | 0.00 | 31.33 |
CAFE_FLR_1 | 1.17 | 0.00 | 1.17 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.17 | 0.00 | 0.17 | 0.00 |
ROOM_2_FLR_3 | 0.33 | 0.00 | 0.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4.50 | 0.33 | 4.50 | 0.33 |
ROOM_5_FLR_3 | 0.67 | 0.17 | 0.67 | 0.17 |
ROOM_6_FLR_3 | 1.00 | 0.17 | 1.00 | 0.17 |
ROOM_1_FLR_6 | 0.17 | 0.17 | 0.17 | 0.17 |
ROOM_2_FLR_6 | 0.67 | 0.17 | 0.67 | 0.17 |
ROOM_3_MULT9_FLR_6 | 0.50 | 0.50 | 0.50 | 0.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 117.83 | 0.00 | 117.83 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 20.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 22.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 65.67 | 0.00 | 0.00 | 0.00 |
Facility | 657.17 | 151.83 | 633.50 | 151.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 2.365 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.312 | 0.273 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 3.452 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 46.522 | 0.151 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 8.167 | 0.245 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.00 | 422.44 | 5183.56 | 3.967 | 0.070 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.179 | 0.000 | 0.063 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.534 | 0.080 | 0.000 | 0.100 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.179 | 0.000 | 0.063 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.078 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.471 | 0.179 | 0.000 | 0.075 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.535 | 0.146 | 0.000 | 0.124 |
BANQUET_FLR_6 | 144.93 | 249.90 | 1010.89 | 9.867 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.93 | 249.90 | 1010.89 | 10.359 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 32.320 | 0.149 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 2.304 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.180 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 3.367 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 45.275 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 7.961 | 0.005 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.00 | 422.44 | 5183.56 | 3.868 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.521 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.522 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.93 | 249.90 | 1010.89 | 9.618 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.93 | 249.90 | 1010.89 | 10.096 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 31.444 | 0.003 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
Electricity:Building | 3164.99 | 38600.85 | 02-JAN-02:10 | 200309.15 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 358.37 | 4020.20 | 02-JAN-02:10 | 27132.60 | 02-JAN-20:10 |
InteriorLights:Electricity | 1395.41 | 12235.54 | 02-JAN-02:10 | 110670.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 208.12 | 1890.98 | 02-JAN-02:10 | 17018.80 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1395.41 | 12235.54 | 02-JAN-02:10 | 110670.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 21.47 | 246.89 | 02-JAN-02:10 | 1608.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.29 | 102.55 | 02-JAN-02:10 | 922.95 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 24.86 | 285.90 | 02-JAN-02:10 | 1862.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.07 | 118.75 | 02-JAN-02:10 | 1068.78 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 40.11 | 427.85 | 02-JAN-02:10 | 3099.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 27.64 | 251.12 | 02-JAN-02:10 | 2260.10 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 8.02 | 91.16 | 02-JAN-02:10 | 603.79 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 4.42 | 40.18 | 02-JAN-02:10 | 361.63 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.19 | 1010.42 | 02-JAN-02:10 | 5002.35 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.25 | 47.73 | 02-JAN-02:10 | 429.55 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 41.88 | 453.48 | 02-JAN-02:10 | 3217.63 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 27.54 | 250.26 | 02-JAN-02:10 | 2252.35 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 310.43 | 3578.21 | 02-JAN-02:10 | 23230.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 161.43 | 1466.79 | 02-JAN-02:10 | 13201.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 36.30 | 414.01 | 01-JAN-02:10 | 2585.65 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.01 | 203.29 | 01-JAN-02:10 | 1848.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 36.30 | 413.96 | 01-JAN-02:10 | 2585.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.01 | 203.27 | 01-JAN-02:10 | 1847.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 515.47 | 6348.95 | 01-JAN-02:10 | 35793.21 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 286.72 | 2427.49 | 01-JAN-02:10 | 22068.10 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 515.61 | 6350.69 | 01-JAN-02:10 | 35803.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 286.80 | 2428.15 | 01-JAN-02:10 | 22074.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 36.30 | 414.01 | 01-JAN-02:10 | 2585.65 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.01 | 203.29 | 01-JAN-02:10 | 1848.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 36.30 | 413.96 | 01-JAN-02:10 | 2585.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.01 | 203.27 | 01-JAN-02:10 | 1847.91 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 87.37 | 793.85 | 02-JAN-02:10 | 7144.64 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 87.37 | 793.85 | 02-JAN-02:10 | 7144.64 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 9.08 | 103.50 | 01-JAN-02:10 | 646.41 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.00 | 50.82 | 01-JAN-02:10 | 462.03 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 9.07 | 103.49 | 01-JAN-02:10 | 646.34 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.00 | 50.82 | 01-JAN-02:10 | 461.98 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 61.06 | 752.06 | 01-JAN-02:10 | 4239.83 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 33.96 | 287.54 | 01-JAN-02:10 | 2614.04 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 224.23 | 2688.78 | 02-JAN-02:10 | 10703.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 48.37 | 439.48 | 02-JAN-02:10 | 3955.32 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 224.23 | 2688.78 | 02-JAN-02:10 | 10703.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 48.37 | 439.48 | 02-JAN-02:10 | 3955.32 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 472.20 | 6790.65 | 02-JAN-02:10 | 19337.58 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.91 | 126.36 | 02-JAN-02:10 | 1137.23 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 23.12 | 210.04 | 02-JAN-02:10 | 1890.37 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 23.12 | 210.04 | 02-JAN-02:10 | 1890.37 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.31 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 73.20 | 1220.92 | 28-SEP-22:30 | 3635.71 | 21-APR-07:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 1667.65 | 3363.31 | 25-FEB-01:10 | 271067.11 | 26-JUN-15:10 |
LowTempRefrigeration:Refrigeration:Electricity | 22.12 | 0.00 | 01-JAN-11:10 | 1932.99 | 21-OCT-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 32.81 | 935.72 | 07-MAR-02:10 | 1173.51 | 22-MAY-13:10 |
WaterSystems:Electricity | 90.79 | 1087.06 | 03-NOV-02:50 | 4739.88 | 27-DEC-07:10 |
Water Heater:WaterSystems:Electricity | 90.79 | 1087.06 | 03-NOV-02:50 | 4739.88 | 27-DEC-07:10 |
Fans:Electricity | 2108.82 | 61766.75 | 29-JUL-05:10 | 94938.49 | 21-DEC-09:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2580.50 | 62631.01 | 29-JUL-05:10 | 114805.26 | 21-DEC-09:20 |
ExteriorEquipment:Electricity | 1011.27 | 7639.31 | 02-JAN-02:20 | 63968.34 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 33.10 | 556.81 | 02-JAN-02:20 | 1934.93 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
ElectricityPurchased:Plant | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
Cogeneration:ElectricityPurchased | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
ElectricityNet:Plant | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
Cogeneration:ElectricityNet | 8637.35 | 140086.62 | 23-AUG-02:20 | 587719.45 | 26-JUN-18:10 |
General:Fans:Electricity | 2108.82 | 61766.75 | 29-JUL-05:10 | 94938.49 | 21-DEC-09:20 |
ExteriorLights:Electricity | 246.05 | 0.00 | 01-JAN-07:30 | 15665.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 246.05 | 0.00 | 01-JAN-07:30 | 15665.55 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.63 | 971.40 | 01-JAN-00:10 | 971.40 | 01-JAN-00:10 |
HeatRecovery:Electricity | 438.57 | 0.00 | 09-JAN-10:10 | 18703.56 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1353.92 | 0.00 | 01-JAN-01:20 | 257987.98 | 26-JUN-15:10 |
General:Cooling:Electricity | 1353.92 | 0.00 | 01-JAN-01:20 | 257987.98 | 26-JUN-15:10 |
Pumps:Electricity | 168.00 | 340.22 | 25-OCT-17:40 | 10433.36 | 23-JUL-15:10 |
General:Pumps:Electricity | 168.00 | 340.22 | 25-OCT-17:40 | 10433.36 | 23-JUL-15:10 |
WIRED_LTG_ELECTRICITY | 49.12 | 0.00 | 01-JAN-00:10 | 3895.60 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 6492.25 | 74475.07 | 09-OCT-24:00 | 738065.64 | 21-DEC-17:40 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 4703.39 | 31843.71 | 07-NOV-09:00 | 648453.43 | 21-DEC-17:40 |
WaterSystems:Gas | 2192.23 | 18467.44 | 01-JAN-11:20 | 180929.78 | 08-FEB-21:20 |
Water Heater:WaterSystems:Gas | 2192.23 | 18467.44 | 01-JAN-11:20 | 180929.78 | 08-FEB-21:20 |
Heating:Gas | 2511.16 | 2611.67 | 11-OCT-18:20 | 485079.17 | 23-DEC-07:10 |
Boiler:Heating:Gas | 2511.16 | 2611.67 | 11-OCT-18:20 | 485079.17 | 23-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4341.05 | 0.00 | 01-JAN-01:20 | 713525.92 | 30-JUL-16:20 |
PlantLoopCoolingDemand:HVAC | 4341.05 | 0.00 | 01-JAN-01:20 | 713525.92 | 30-JUL-16:20 |
CoolingCoils:PlantLoopCoolingDemand | 4341.05 | 0.00 | 01-JAN-01:20 | 713525.92 | 30-JUL-16:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 31102.74 | 274726.11 | 23-MAR-13:40 | 2901851.22 | 26-JUN-15:10 |
EnergyTransfer:Building | 5981.01 | 86174.42 | 07-FEB-15:00 | 387833.88 | 02-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 752.36 | 10160.68 | 22-DEC-04:00 | 34872.94 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 181.77 | 3584.24 | 28-SEP-22:30 | 10286.11 | 22-AUG-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.88 | 1792.12 | 28-SEP-22:30 | 5143.05 | 22-AUG-07:30 |
EnergyTransfer:Plant | 12922.73 | 59882.40 | 22-NOV-24:00 | 1701006.58 | 30-JUL-16:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.58 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 65.31 | 1757.16 | 07-MAR-02:10 | 2470.52 | 22-MAY-13:10 |
PlantLoopHeatingDemand:Facility | 2575.09 | 27044.12 | 13-SEP-22:10 | 424473.11 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 787.56 | 9378.42 | 21-AUG-00:10 | 58212.81 | 13-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 787.56 | 9378.42 | 21-AUG-00:10 | 58212.81 | 13-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 484.27 | 8046.12 | 05-MAR-16:00 | 25808.10 | 12-SEP-21:00 |
Heating:EnergyTransfer | 112.43 | 0.00 | 01-JAN-08:40 | 89720.58 | 21-DEC-09:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5777.70 | 61440.54 | 20-DEC-15:00 | 384129.51 | 02-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 484.27 | 8046.12 | 05-MAR-16:00 | 25808.10 | 12-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.95 | 0.02 | 30-JAN-01:10 | 4480.61 | 20-JAN-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.67 | 0.00 | 01-JAN-00:10 | 1850.05 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.29 | 0.00 | 01-JAN-04:10 | 4480.61 | 20-JAN-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.82 | 155.02 | 21-DEC-10:20 | 2468.53 | 26-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.82 | 155.02 | 21-DEC-10:20 | 2468.53 | 26-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 33.44 | 0.24 | 05-FEB-17:40 | 2717.39 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 277.39 | 23-DEC-06:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.38 | 0.00 | 05-JAN-01:50 | 2717.39 | 26-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 9.95 | 0.01 | 22-OCT-23:30 | 1010.38 | 26-JUN-19:20 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.86 | 0.00 | 01-JAN-00:10 | 430.71 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.09 | 0.00 | 01-JAN-01:50 | 1010.38 | 26-JUN-19:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.44 | 8611.12 | 23-DEC-06:00 | 38375.66 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 608.44 | 8611.12 | 23-DEC-06:00 | 38375.66 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 265.52 | 0.10 | 02-APR-12:40 | 17008.77 | 20-JAN-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 2762.44 | 20-DEC-11:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 265.29 | 0.00 | 04-JAN-11:40 | 17008.77 | 20-JAN-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 930.15 | 2346.30 | 20-DEC-11:10 | 47910.59 | 17-JUL-21:20 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 930.15 | 2346.30 | 20-DEC-11:10 | 47910.59 | 17-JUL-21:20 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 61.46 | 0.05 | 27-APR-05:10 | 12333.48 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.42 | 0.00 | 01-JAN-08:10 | 6367.82 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.03 | 0.00 | 01-JAN-00:10 | 12333.48 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.53 | 0.02 | 20-APR-03:10 | 12267.42 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.37 | 0.00 | 01-JAN-08:10 | 6439.04 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 41.16 | 0.00 | 01-JAN-00:10 | 12267.42 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 619.79 | 0.04 | 21-DEC-17:00 | 78657.36 | 20-JAN-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 2.71 | 0.00 | 01-JAN-00:10 | 19076.04 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 617.08 | 0.00 | 05-JAN-04:40 | 78657.36 | 20-JAN-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 524.67 | 1.08 | 17-JAN-05:20 | 77411.39 | 08-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 14.70 | 0.00 | 01-JAN-00:10 | 34927.33 | 24-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 509.97 | 0.00 | 02-JAN-16:30 | 77411.39 | 08-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 64.58 | 0.08 | 08-JAN-17:00 | 11671.66 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.62 | 0.00 | 01-JAN-07:50 | 6317.38 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 53.96 | 0.00 | 01-JAN-00:10 | 11671.66 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 58.60 | 0.07 | 02-OCT-01:00 | 11718.68 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.62 | 0.00 | 01-JAN-08:10 | 6660.84 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 43.97 | 0.00 | 01-JAN-00:10 | 11718.68 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 129.15 | 0.07 | 26-NOV-04:40 | 9755.17 | 26-JUN-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 9.43 | 0.00 | 01-JAN-00:10 | 4044.56 | 22-DEC-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 119.73 | 0.00 | 01-JAN-02:30 | 9755.17 | 26-JUN-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.00 | 0.01 | 27-JAN-23:00 | 3588.23 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.46 | 0.00 | 01-JAN-08:10 | 2101.76 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 14.55 | 0.00 | 01-JAN-00:10 | 3588.23 | 16-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.83 | 0.05 | 18-JAN-17:40 | 3574.29 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.88 | 0.00 | 01-JAN-08:10 | 2141.08 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.94 | 0.00 | 01-JAN-00:10 | 3574.29 | 26-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 117.11 | 0.00 | 09-JAN-03:20 | 18313.46 | 05-NOV-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 10.14 | 0.00 | 01-JAN-00:10 | 9060.05 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 106.97 | 0.00 | 01-JAN-02:30 | 18313.46 | 05-NOV-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 514.64 | 5744.33 | 20-DEC-11:10 | 24739.87 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 514.64 | 5744.33 | 20-DEC-11:10 | 24739.87 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 551.89 | 7012.12 | 20-DEC-11:10 | 26053.55 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 551.89 | 7012.12 | 20-DEC-11:10 | 26053.55 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 661.48 | 8016.09 | 22-DEC-04:00 | 29881.71 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 74.87 | 0.02 | 02-OCT-06:20 | 6543.40 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 11.25 | 0.00 | 01-JAN-08:40 | 4017.85 | 22-DEC-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 63.61 | 0.00 | 01-JAN-00:10 | 6543.40 | 28-SEP-13:30 |
WaterSystems:EnergyTransfer | 787.56 | 9378.42 | 21-AUG-00:10 | 58212.81 | 13-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 787.56 | 9378.42 | 21-AUG-00:10 | 58212.81 | 13-FEB-07:30 |
EnergyTransfer:HVAC | 12198.99 | 33825.10 | 30-SEP-18:00 | 1180947.04 | 22-DEC-03:00 |
HeatingCoils:EnergyTransfer | 1787.54 | 1995.28 | 11-OCT-18:20 | 385148.64 | 21-DEC-09:20 |
PlantLoopHeatingDemand:HVAC | 1787.54 | 1995.28 | 11-OCT-18:20 | 385148.64 | 21-DEC-09:20 |
HeatingCoils:PlantLoopHeatingDemand | 1787.54 | 1995.28 | 11-OCT-18:20 | 385148.64 | 21-DEC-09:20 |
CoolingCoils:EnergyTransfer | 4341.05 | 0.00 | 01-JAN-01:20 | 713525.92 | 30-JUL-16:20 |
HeatRecoveryForHeating:EnergyTransfer | 5620.70 | 0.00 | 09-JAN-10:10 | 845826.59 | 22-DEC-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 449.70 | 0.00 | 01-JAN-00:10 | 351405.64 | 16-AUG-14:00 |
Boilers:EnergyTransfer | 1762.50 | 1568.97 | 11-OCT-18:20 | 383535.14 | 23-DEC-07:10 |
Chillers:EnergyTransfer | 4463.94 | 0.00 | 01-JAN-01:20 | 719954.43 | 30-JUL-16:20 |
HeatRejection:EnergyTransfer | 5817.86 | 0.00 | 01-JAN-01:20 | 897484.28 | 26-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -484.274 | 0.000 | 0.000 | 158.603 | 208.116 | 150.259 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -32.704 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 2.669 | -42.285 | 0.000 | 0.000 | 16.111 | 11.286 | 10.186 | 30.778 | 0.000 | 0.557 | 0.000 | 0.000 | -12.360 | 0.000 | -7.773 | -9.170 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -42.817 | 0.000 | 0.000 | 18.663 | 13.070 | 11.795 | 0.000 | 0.000 | 0.119 | 0.788 | 0.000 | 0.000 | 0.000 | -1.617 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -608.443 | 0.000 | 0.000 | 12.310 | 5.253 | 658.148 | 0.000 | 0.000 | 0.393 | 0.000 | 0.000 | 0.000 | 0.000 | -5.076 | -62.585 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.238 | -265.287 | 0.000 | 0.000 | 211.464 | 27.543 | 14.341 | 86.453 | 0.000 | 1.420 | 0.002 | 0.000 | -34.764 | 0.000 | -19.592 | -21.817 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -930.151 | 0.000 | 0.000 | 626.413 | 161.431 | 149.002 | 114.895 | 0.000 | 2.843 | 0.001 | 0.000 | -46.146 | 0.000 | -38.944 | -39.343 |
ROOM_1_FLR_3 | 10.423 | -33.805 | 0.000 | -17.230 | 0.000 | 0.000 | 9.702 | 24.012 | 12.292 | 54.057 | 0.000 | 0.777 | 0.000 | 0.000 | -29.736 | 0.000 | -9.768 | -20.724 |
ROOM_2_FLR_3 | 14.371 | -24.247 | 0.000 | -16.915 | 0.000 | 0.000 | 9.739 | 24.009 | 12.291 | 36.068 | 0.000 | 0.762 | 0.001 | 0.000 | -30.559 | 0.000 | -9.639 | -15.881 |
ROOM_3_MULT19_FLR_3 | 2.709 | -350.163 | 0.000 | -266.915 | 0.000 | 0.000 | 0.000 | 286.718 | 228.754 | 361.269 | 0.000 | 3.939 | 0.027 | 0.000 | -175.004 | 0.000 | -71.512 | -19.794 |
ROOM_4_MULT19_FLR_3 | 14.695 | -279.484 | 0.000 | -230.490 | 0.000 | 0.000 | 184.789 | 286.797 | 228.817 | 83.315 | 0.000 | 7.355 | 0.003 | 0.000 | -172.570 | 0.000 | -58.180 | -65.043 |
ROOM_5_FLR_3 | 10.620 | -36.634 | 0.000 | -17.322 | 0.000 | 0.000 | 9.690 | 24.012 | 12.292 | 56.827 | 0.000 | 0.773 | 0.000 | 0.000 | -29.243 | 0.000 | -9.817 | -21.198 |
ROOM_6_FLR_3 | 14.624 | -26.965 | 0.000 | -17.008 | 0.000 | 0.000 | 9.728 | 24.009 | 12.291 | 38.588 | 0.000 | 0.757 | 0.001 | 0.000 | -29.824 | 0.000 | -9.685 | -16.513 |
ROOM_1_FLR_6 | 4.455 | -10.249 | 0.000 | -4.299 | 0.000 | 0.000 | 2.427 | 6.003 | 3.073 | 13.420 | 0.000 | 0.202 | 0.000 | 0.000 | -7.442 | 0.000 | -2.473 | -5.117 |
ROOM_2_FLR_6 | 5.885 | -7.720 | 0.000 | -4.224 | 0.000 | 0.000 | 2.436 | 6.002 | 3.073 | 8.931 | 0.000 | 0.197 | 0.000 | 0.000 | -7.632 | 0.000 | -2.441 | -4.506 |
ROOM_3_MULT9_FLR_6 | 10.136 | -78.998 | 0.000 | -27.972 | 0.000 | 0.000 | 21.775 | 33.963 | 27.097 | 78.914 | 0.000 | 1.250 | 0.001 | 0.000 | -34.935 | 0.000 | -12.158 | -19.070 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -514.646 | 0.000 | 0.000 | 364.568 | 48.368 | 175.857 | 9.909 | 0.000 | 0.395 | 0.000 | 0.000 | -19.589 | 0.000 | -5.692 | -59.170 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -551.891 | 0.000 | 0.000 | 363.694 | 48.368 | 175.857 | 9.751 | 0.000 | 0.394 | 0.000 | 0.000 | -19.976 | 0.000 | -5.708 | -20.490 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -661.471 | 0.000 | 0.000 | 31.021 | 13.907 | 556.656 | 26.778 | 0.000 | 0.273 | 52.486 | 0.000 | -14.152 | 0.000 | -5.497 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.059 | -33.377 | 0.000 | 0.000 | 0.000 | 27.638 | 12.472 | 0.000 | 0.000 | 0.261 | 0.000 | 0.000 | 0.000 | 0.000 | -3.548 | -3.505 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.862 | -9.089 | 0.000 | 0.000 | 0.000 | 4.422 | 3.598 | 0.000 | 0.000 | 0.182 | 2.490 | 0.000 | 0.000 | 0.000 | -2.465 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 9.428 | -119.725 | 0.000 | 0.000 | 0.000 | 87.369 | 0.000 | 51.927 | 0.000 | 0.797 | 16.591 | 0.000 | -35.443 | 0.000 | -10.945 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 11.253 | -63.612 | 0.000 | 0.000 | 0.000 | 23.117 | 0.000 | 25.919 | 0.000 | 0.348 | 23.628 | 0.000 | -15.791 | 0.000 | -4.861 | -0.001 |
Total Facility | 87.920 | -848.265 | 24.509 | -4929.442 | 0.000 | 0.000 | 2053.132 | 1395.412 | 2458.149 | 1087.799 | 0.000 | 23.992 | 96.021 | 0.000 | -715.166 | 0.000 | -297.393 | -436.632 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-SEP-21:00 | 0.00 | 0.00 | 0.00 | -25809.60 | 0.00 | 0.00 | 7042.00 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5941.71 |
RETAIL_1_FLR_1 | 20-JAN-13:10 | 0.00 | 0.00 | 0.00 | -4479.72 | 0.00 | 0.00 | 147.15 | 256.37 | 252.59 | 8028.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -64.03 | -4141.03 |
RETAIL_2_FLR_1 | 26-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2468.03 | 0.00 | 0.00 | 817.60 | 950.02 | 752.15 | 0.00 | 0.00 | 29.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -81.08 |
LAUNDRY_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -38377.33 | 0.00 | 0.00 | 448.37 | 429.55 | 44299.38 | 0.00 | 0.00 | 120.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6920.64 |
CAFE_FLR_1 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | -17003.70 | 0.00 | 0.00 | 2103.66 | 625.65 | 355.63 | 23034.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -98.97 | -9016.89 |
LOBBY_FLR_1 | 17-JUL-21:10 | 0.00 | 0.00 | 0.00 | -47936.89 | 0.00 | 0.00 | 31022.25 | 8800.76 | 7389.94 | 692.87 | 0.00 | 680.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -649.07 |
ROOM_1_FLR_3 | 01-JUL-18:01 | 0.00 | -17730.71 | 0.00 | -584.32 | 0.00 | 0.00 | 283.22 | 1848.13 | 516.26 | 9300.45 | 0.00 | 115.57 | 6251.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-18:01 | 0.00 | -17565.14 | 0.00 | -584.89 | 0.00 | 0.00 | 283.22 | 1847.91 | 516.20 | 9741.83 | 0.00 | 115.36 | 5645.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-JAN-12:30 | 0.00 | -70150.50 | 0.00 | -8502.68 | 0.00 | 0.00 | 0.00 | 6179.07 | 5097.90 | 102060.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -344.35 | -34339.61 |
ROOM_4_MULT19_FLR_3 | 08-JUL-15:01 | 0.00 | -102883.27 | 0.00 | -8233.82 | 0.00 | 0.00 | 2483.54 | 7284.46 | 5687.67 | 15754.49 | 0.00 | 9156.53 | 70750.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:61 | 0.00 | -15693.20 | 0.00 | -592.99 | 0.00 | 0.00 | 130.71 | 1034.95 | 653.23 | 11253.46 | 0.00 | 76.22 | 3137.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 01-JUL-08:61 | 0.00 | -15626.22 | 0.00 | -593.60 | 0.00 | 0.00 | 130.71 | 1034.83 | 653.15 | 11244.98 | 0.00 | 76.00 | 3080.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 16-AUG-15:01 | 0.00 | -4812.31 | 0.00 | -147.05 | 0.00 | 0.00 | 58.82 | 129.37 | 68.48 | 2750.92 | 0.00 | 73.29 | 1878.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 16-AUG-15:01 | 0.00 | -4759.35 | 0.00 | -146.78 | 0.00 | 0.00 | 58.82 | 129.35 | 68.48 | 2701.76 | 0.00 | 73.38 | 1874.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11-FEB-16:01 | 0.00 | -18145.75 | 0.00 | -1884.38 | 0.00 | 0.00 | 294.11 | 862.63 | 673.54 | 3572.58 | 0.00 | 0.00 | 15533.77 | 0.00 | -0.00 | 0.00 | -906.50 | 0.00 |
BANQUET_FLR_6 | 26-JUN-21:15 | 0.00 | 0.00 | 0.00 | -24764.08 | 0.00 | 0.00 | 17788.53 | 2636.88 | 6747.90 | 150.20 | 0.00 | 74.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2634.02 |
DINING_FLR_6 | 26-JUN-21:15 | 0.00 | 0.00 | 0.00 | -26079.47 | 0.00 | 0.00 | 17757.25 | 2636.88 | 6747.90 | 133.67 | 0.00 | 74.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1270.41 |
KITCHEN_FLR_6 | 26-JUN-18:07 | 0.00 | 0.00 | 0.00 | -29899.35 | 0.00 | 0.00 | 1121.02 | 1010.87 | 21959.95 | 1188.48 | 0.00 | 159.49 | 4459.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2717.51 | 0.00 | 0.00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 98.77 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -480.80 |
STORAGE_FLR_1 | 26-JUN-19:20 | 0.00 | 0.00 | 0.00 | -1010.41 | 0.00 | 0.00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 79.89 | 326.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 26-JUN-19:10 | 0.00 | 0.00 | 0.00 | -9755.34 | 0.00 | 0.00 | 0.00 | 7144.64 | 0.00 | 2246.78 | 0.00 | 358.96 | 4.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 28-SEP-13:30 | 0.00 | 0.00 | 0.00 | -6543.06 | 0.00 | 0.00 | 0.00 | 525.10 | 0.00 | 4602.79 | 0.00 | 104.24 | 1310.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-18:01 | 0.00 | -225809.72 | 0.00 | -231098.09 | 0.00 | 0.00 | 79368.37 | 98435.01 | 122526.13 | 41308.84 | 0.00 | 7017.40 | 108252.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 21-DEC-08:10 | 0.00 | 0.00 | 1861.33 | -0.00 | 0.00 | 0.00 | 382.34 | 410.20 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1951.15 | 0.00 | -864.98 | -198.59 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-09:30 | 0.00 | 0.00 | 2808.59 | -0.00 | 0.00 | 0.00 | 2430.19 | 1001.05 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3980.37 | 0.00 | -2234.16 | -533.34 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-FEB-16:02 | 8075.80 | 256.70 | 0.00 | -256.70 | 0.00 | 0.00 | 293.98 | 517.48 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1253.56 | 0.00 | -327.10 | -7580.53 |
ROOM_2_FLR_3 | 26-DEC-16:01 | 8067.71 | 273.93 | 0.00 | -273.93 | 0.00 | 0.00 | 289.92 | 517.42 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -968.82 | 0.00 | -240.50 | -7939.62 |
ROOM_3_MULT19_FLR_3 | 21-DEC-05:00 | 19076.05 | 19257.73 | 0.00 | -19257.73 | 0.00 | 0.00 | 0.00 | 2427.49 | 3921.46 | 0.00 | 0.00 | 0.00 | 3594.16 | 0.00 | -24021.81 | 0.00 | -4997.34 | 0.00 |
ROOM_4_MULT19_FLR_3 | 04-DEC-16:03 | 47239.30 | 4910.92 | 0.00 | -4910.92 | 0.00 | 0.00 | 4833.45 | 6180.76 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3202.94 | 0.00 | -12241.82 | -47908.05 |
ROOM_5_FLR_3 | 07-FEB-16:02 | 7696.84 | 254.26 | 0.00 | -254.26 | 0.00 | 0.00 | 293.98 | 517.48 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1253.47 | 0.00 | -326.16 | -7202.60 |
ROOM_6_FLR_3 | 07-FEB-16:02 | 7687.85 | 254.13 | 0.00 | -254.13 | 0.00 | 0.00 | 293.98 | 517.42 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1243.76 | 0.00 | -326.08 | -7203.30 |
ROOM_1_FLR_6 | 26-DEC-16:01 | 2406.34 | 65.22 | 0.00 | -65.22 | 0.00 | 0.00 | 73.50 | 129.37 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -234.92 | 0.00 | -59.25 | -2383.52 |
ROOM_2_FLR_6 | 26-DEC-16:01 | 2407.85 | 64.93 | 0.00 | -64.93 | 0.00 | 0.00 | 73.50 | 129.35 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.02 | 0.00 | -59.13 | -2390.02 |
ROOM_3_MULT9_FLR_6 | 07-FEB-16:02 | 10556.38 | 407.95 | 0.00 | -407.95 | 0.00 | 0.00 | 661.47 | 731.93 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1449.41 | 0.00 | -377.04 | -10727.20 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 23-DEC-06:00 | 0.00 | 0.00 | 277.39 | -0.00 | 0.00 | 0.00 | 0.00 | 251.12 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -434.28 | -270.96 |
STORAGE_FLR_1 | 22-DEC-05:00 | 0.00 | 0.00 | 430.71 | -0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -292.31 | -229.57 |
CORRIDOR_FLR_3 | 22-DEC-06:00 | 0.00 | 0.00 | 4044.60 | -0.00 | 0.00 | 0.00 | 0.00 | 1587.70 | 0.00 | 0.00 | 0.00 | 0.00 | 597.97 | 0.00 | -4937.21 | 0.00 | -1293.06 | 0.00 |
CORRIDOR_FLR_6 | 22-DEC-06:00 | 0.00 | 0.00 | 4017.89 | -0.00 | 0.00 | 0.00 | 0.00 | 420.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2167.31 | 0.00 | -565.02 | -1705.64 |
Total Facility | 07-FEB-16:02 | -2870.92 | 103354.71 | 5017.36 | -103354.71 | 0.00 | 0.00 | 57782.43 | 30864.20 | 77528.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30333.10 | 0.00 | -9717.72 | -128271.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.3261 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 26.0101 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.0101 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 26.0101 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1933 | 3.1933 | 3.1550 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3947 | 0.3947 | 0.3899 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2971 | 0.2971 | 0.2935 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0208 | 4.0208 | 3.9726 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7079 | 1.7079 | 1.6874 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7481 | 5.7481 | 5.6791 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7852 | 2.7852 | 2.7518 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9237 | 2.9237 | 2.8886 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8247 | 2.8247 | 2.7908 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3345 | 0.3345 | 0.3305 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1398 | 0.1398 | 0.1381 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 1.1727 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7694 | 0.7694 | 0.7602 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.3261 | 26.0101 | 26.3261 | 26.0101 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1550 | 3.1550 | 3.1550 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3899 | 0.3899 | 0.3899 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2935 | 0.2935 | 0.2935 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9726 | 3.9726 | 3.9726 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6874 | 1.6874 | 1.6874 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6791 | 5.6791 | 5.6791 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7518 | 2.7518 | 2.7518 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8886 | 2.8886 | 2.8886 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7908 | 2.7908 | 2.7908 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3305 | 0.3305 | 0.3305 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1381 | 0.1381 | 0.1381 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1727 | 1.1727 | 1.1727 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7602 | 0.7602 | 0.7602 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.0101 | 26.0101 | 26.0101 | 26.0101 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 633.50 |
Number of hours cooling loads not met | 151.83 |
Number of hours not met | 785.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 2511.16 | 485079.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1353.92 | 257987.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1395.41 | 110670.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 246.05 | 15665.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 33.10 | 1934.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.63 | 971.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2108.82 | 94938.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 168.00 | 10433.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 438.57 | 18703.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.79 | 4739.88 | 2192.23 | 180929.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.12 | 1932.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.81 | 1173.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1824.51 | 8637.35 |
Natural Gas | 1788.85 | 6492.25 |
Additional | 0.00 | 0.00 |
Total | 3613.36 | 15129.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 122.99 |
Space Heating | 0.00 |
Space Cooling | 119.34 |
Fans (All) | 185.88 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 761.32 |
Subtotal | 761.32 |
Natural Gas [MJ/m2] | |
Space Heating | 221.34 |
Service Water Heating | 193.23 |
Miscellaneous (All) | 572.24 |
Subtotal | 572.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.22 |
Space Heating | 16.60 |
Space Cooling | 8.95 |
Fans (All) | 13.94 |
Service Water Heating | 15.09 |
Receptacle Equipment | 23.40 |
Miscellaneous | 12.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 3599. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2869. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.257753E+12 |
February | 0.000 | 0.252984E+12 |
March | 0.000 | 0.218168E+12 |
April | 0.000 | 0.198898E+12 |
May | 0.000 | 0.168328E+12 |
June | 0.000 | 0.170841E+12 |
July | 0.000 | 0.181663E+12 |
August | 0.000 | 0.172305E+12 |
September | 0.000 | 0.153569E+12 |
October | 0.000 | 0.187619E+12 |
November | 0.000 | 0.203967E+12 |
December | 0.000 | 0.345070E+12 |
Annual Sum or Average | 0.251116E+13 | |
Minimum of Months | 0.000 | 0.153569E+12 |
Maximum of Months | 0.000 | 0.345070E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393823E+11 | 18765.64 | 27-JAN-22:00 | 3.00 | 3.00 | 0.615469E+10 | 3819.60 | 13-JAN-22:10 | -6.3 | -7.8 |
February | 0.336345E+11 | 18476.75 | 23-FEB-22:00 | 1.00 | 1.00 | 0.555010E+10 | 3789.57 | 01-FEB-22:10 | -7.8 | -7.9 |
March | 0.353428E+11 | 19398.21 | 15-MAR-21:00 | 13.00 | 3.05 | 0.613214E+10 | 3757.45 | 01-MAR-22:10 | -4.2 | -4.2 |
April | 0.347175E+11 | 20182.10 | 12-APR-19:20 | 14.33 | 5.46 | 0.591612E+10 | 3756.23 | 05-APR-21:10 | 5.00 | 1.33 |
May | 0.360215E+11 | 20290.56 | 12-MAY-20:00 | 15.00 | 4.98 | 0.605344E+10 | 3745.78 | 02-MAY-21:10 | 3.20 | 0.33 |
June | 0.378127E+11 | 20686.67 | 09-JUN-21:00 | 15.50 | 9.99 | 0.579217E+10 | 3580.67 | 09-JUN-01:39 | 9.37 | 5.91 |
July | 0.396440E+11 | 20692.12 | 03-JUL-21:00 | 16.00 | 9.75 | 0.594386E+10 | 3584.03 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.435170E+11 | 23476.69 | 17-AUG-21:00 | 19.00 | 9.33 | 0.606045E+10 | 3649.95 | 22-AUG-21:10 | 15.00 | 11.41 |
September | 0.461746E+11 | 25808.10 | 12-SEP-21:00 | 23.30 | 12.96 | 0.592923E+10 | 3930.59 | 22-SEP-21:10 | 8.90 | 3.53 |
October | 0.473888E+11 | 23772.09 | 10-OCT-18:10 | 18.83 | 5.87 | 0.631280E+10 | 3971.27 | 20-OCT-21:10 | 10.17 | 1.47 |
November | 0.454432E+11 | 21654.89 | 09-NOV-09:00 | 16.00 | 7.73 | 0.612617E+10 | 3967.95 | 17-NOV-22:10 | 6.00 | 2.20 |
December | 0.451941E+11 | 19655.02 | 02-DEC-18:10 | 13.50 | 4.23 | 0.627822E+10 | 3940.55 | 01-DEC-22:10 | 6.00 | 1.08 |
Annual Sum or Average | 0.484273E+12 | 0.722494E+11 | ||||||||
Minimum of Months | 0.336345E+11 | 18476.75 | 1.00 | 1.00 | 0.555010E+10 | 3580.67 | -7.8 | -7.9 | ||
Maximum of Months | 0.473888E+11 | 25808.10 | 23.30 | 12.96 | 0.631280E+10 | 3971.27 | 15.00 | 11.41 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301753E+10 | 4480.61 | 20-JAN-13:10 | 21.00 | 6.93 | 0.631923E+09 | 364.26 | 14-JAN-03:00 | -17.0 | -17.0 |
February | 0.242759E+10 | 4293.40 | 18-FEB-13:30 | 20.00 | 7.70 | 0.569574E+09 | 364.28 | 02-FEB-05:30 | -9.0 | -9.0 |
March | 0.264807E+10 | 3966.61 | 14-MAR-12:50 | 23.67 | 7.77 | 0.626945E+09 | 364.29 | 27-MAR-04:30 | 1.50 | -2.3 |
April | 0.186367E+10 | 3370.81 | 07-APR-13:00 | 21.00 | 8.51 | 0.600837E+09 | 364.26 | 17-APR-04:49 | -8.0 | -8.6 |
May | 0.320310E+10 | 2636.98 | 06-MAY-13:30 | 25.00 | 10.45 | 0.620805E+09 | 364.32 | 01-MAY-00:49 | 5.57 | 1.95 |
June | 0.481438E+10 | 3226.06 | 26-JUN-18:10 | 37.33 | 15.05 | 0.601889E+09 | 364.27 | 10-JUN-03:49 | 10.08 | 5.60 |
July | 0.506959E+10 | 3184.06 | 18-JUL-12:50 | 34.83 | 13.63 | 0.619483E+09 | 364.26 | 17-JUL-02:00 | 20.00 | 9.34 |
August | 0.517501E+10 | 3469.16 | 31-AUG-12:40 | 30.00 | 12.21 | 0.622481E+09 | 364.50 | 01-AUG-00:00 | 19.10 | 7.50 |
September | 0.495230E+10 | 4076.77 | 28-SEP-13:00 | 30.50 | 11.26 | 0.603503E+09 | 364.20 | 22-SEP-01:00 | -1.2 | -1.9 |
October | 0.347009E+10 | 4148.86 | 10-OCT-12:50 | 23.83 | 7.89 | 0.628586E+09 | 371.08 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.314196E+10 | 4382.74 | 07-NOV-13:30 | 21.00 | 7.16 | 0.611796E+09 | 364.27 | 27-NOV-03:49 | -6.7 | -6.7 |
December | 0.250179E+10 | 4236.92 | 02-DEC-13:00 | 21.00 | 7.10 | 0.624627E+09 | 364.29 | 19-DEC-02:00 | -16.0 | -16.0 |
Annual Sum or Average | 0.422851E+11 | 0.736245E+10 | ||||||||
Minimum of Months | 0.186367E+10 | 2636.98 | 20.00 | 6.93 | 0.569574E+09 | 364.20 | -17.0 | -17.0 | ||
Maximum of Months | 0.517501E+10 | 4480.61 | 37.33 | 15.05 | 0.631923E+09 | 371.08 | 20.00 | 9.34 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330431E+10 | 1833.20 | 20-JAN-22:00 | 8.00 | 2.06 | 0.723881E+09 | 464.78 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.285058E+10 | 1806.02 | 17-FEB-22:00 | 7.00 | 3.15 | 0.653924E+09 | 459.63 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.329952E+10 | 2123.85 | 14-MAR-18:03 | 17.67 | 5.74 | 0.728372E+09 | 464.76 | 10-MAR-22:10 | 8.83 | 2.52 |
April | 0.310997E+10 | 2094.99 | 20-APR-19:00 | 17.00 | 8.16 | 0.701608E+09 | 457.42 | 11-APR-21:10 | 9.67 | 3.08 |
May | 0.371484E+10 | 2381.09 | 10-MAY-21:00 | 21.00 | 8.14 | 0.724802E+09 | 461.91 | 18-MAY-21:10 | 6.83 | 4.27 |
June | 0.413846E+10 | 2468.53 | 26-JUN-21:00 | 28.80 | 11.20 | 0.698275E+09 | 441.81 | 09-JUN-22:10 | 13.30 | 8.82 |
July | 0.424753E+10 | 2450.04 | 24-JUL-21:00 | 24.00 | 16.59 | 0.718210E+09 | 446.85 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.425153E+10 | 2462.03 | 16-AUG-21:00 | 26.00 | 10.44 | 0.721319E+09 | 437.89 | 21-AUG-21:10 | 16.00 | 14.22 |
September | 0.401509E+10 | 2440.19 | 12-SEP-21:00 | 23.30 | 12.96 | 0.698757E+09 | 455.83 | 15-SEP-21:10 | 12.28 | 6.12 |
October | 0.354968E+10 | 2195.78 | 10-OCT-18:15 | 18.67 | 5.77 | 0.726504E+09 | 469.64 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.329190E+10 | 1859.92 | 06-NOV-19:10 | 13.33 | 3.88 | 0.701213E+09 | 465.28 | 07-NOV-22:10 | 7.00 | 1.99 |
December | 0.304380E+10 | 1785.98 | 04-DEC-22:00 | 7.00 | 0.66 | 0.722178E+09 | 457.36 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.428172E+11 | 0.851904E+10 | ||||||||
Minimum of Months | 0.285058E+10 | 1785.98 | 7.00 | 0.66 | 0.653924E+09 | 437.89 | 6.83 | 0.70 | ||
Maximum of Months | 0.425153E+10 | 2468.53 | 28.80 | 16.59 | 0.728372E+09 | 469.64 | 16.00 | 14.22 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199107E+10 | 1844.60 | 20-JAN-22:00 | 8.00 | 2.06 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.164735E+10 | 1818.99 | 27-FEB-21:00 | 4.00 | 0.38 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.229382E+10 | 2266.78 | 14-MAR-20:00 | 16.00 | 4.97 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.230661E+10 | 2247.14 | 20-APR-19:30 | 16.00 | 8.09 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.319256E+10 | 2479.34 | 31-MAY-20:00 | 19.00 | 12.32 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.389818E+10 | 2717.39 | 26-JUN-20:00 | 32.70 | 13.62 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.404503E+10 | 2716.61 | 18-JUL-20:00 | 26.00 | 13.89 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.392445E+10 | 2701.90 | 16-AUG-20:00 | 29.00 | 11.88 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.353740E+10 | 2612.52 | 12-SEP-20:00 | 23.80 | 13.33 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.263213E+10 | 2292.67 | 10-OCT-19:30 | 16.50 | 4.82 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.215474E+10 | 1873.86 | 09-NOV-21:00 | 9.00 | 7.27 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.175310E+10 | 1827.04 | 04-DEC-21:00 | 7.00 | 0.66 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.333764E+11 | 0.00 | ||||||||
Minimum of Months | 0.164735E+10 | 1818.99 | 4.00 | 0.38 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.404503E+10 | 2717.39 | 32.70 | 13.89 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259540E+09 | 532.74 | 20-JAN-22:00 | 8.00 | 2.06 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.199580E+09 | 460.44 | 18-FEB-22:00 | 10.00 | 3.82 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.421233E+09 | 651.46 | 14-MAR-20:00 | 16.00 | 4.97 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.442388E+09 | 632.86 | 20-APR-20:00 | 15.00 | 7.95 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.951530E+09 | 751.10 | 31-MAY-19:10 | 22.33 | 13.49 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.145195E+10 | 1010.38 | 26-JUN-19:20 | 34.57 | 14.18 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.151872E+10 | 974.10 | 17-JUL-20:00 | 30.00 | 13.85 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.143119E+10 | 945.17 | 16-AUG-20:00 | 29.00 | 11.88 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.120867E+10 | 834.08 | 12-SEP-20:00 | 23.80 | 13.33 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.617707E+09 | 677.43 | 11-OCT-20:50 | 10.17 | 4.70 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.361259E+09 | 574.86 | 09-NOV-22:00 | 8.00 | 6.33 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.224871E+09 | 491.49 | 04-DEC-22:00 | 7.00 | 0.66 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.908863E+10 | 0.00 | ||||||||
Minimum of Months | 0.199580E+09 | 460.44 | 7.00 | 0.66 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.151872E+10 | 1010.38 | 34.57 | 14.18 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501697E+11 | 36035.65 | 20-JAN-21:00 | 7.00 | 1.59 | 0.515323E+09 | 398.27 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.451513E+11 | 35943.37 | 17-FEB-21:00 | 7.00 | 3.15 | 0.465755E+09 | 396.77 | 27-FEB-22:10 | 2.00 | -0.7 |
March | 0.508482E+11 | 37021.88 | 14-MAR-20:00 | 16.00 | 4.97 | 0.517043E+09 | 399.39 | 10-MAR-22:10 | 8.83 | 2.52 |
April | 0.491310E+11 | 36773.96 | 20-APR-20:00 | 15.00 | 7.95 | 0.496620E+09 | 397.89 | 11-APR-21:10 | 9.67 | 3.08 |
May | 0.522690E+11 | 37542.78 | 31-MAY-19:30 | 21.00 | 13.07 | 0.502887E+09 | 398.52 | 18-MAY-21:10 | 6.83 | 4.27 |
June | 0.522030E+11 | 38375.66 | 26-JUN-20:00 | 32.70 | 13.62 | 0.461615E+09 | 357.93 | 09-JUN-21:10 | 15.13 | 9.81 |
July | 0.537728E+11 | 38321.17 | 17-JUL-20:00 | 30.00 | 13.85 | 0.469962E+09 | 361.76 | 05-JUL-21:10 | 14.50 | 9.05 |
August | 0.538596E+11 | 38289.66 | 16-AUG-20:00 | 29.00 | 11.88 | 0.474332E+09 | 359.64 | 22-AUG-21:10 | 15.00 | 11.41 |
September | 0.513533E+11 | 38095.78 | 12-SEP-20:00 | 23.80 | 13.33 | 0.469628E+09 | 394.72 | 22-SEP-21:10 | 8.90 | 3.53 |
October | 0.511302E+11 | 36685.92 | 04-OCT-20:00 | 13.00 | 6.05 | 0.512046E+09 | 399.66 | 20-OCT-21:10 | 10.17 | 1.47 |
November | 0.489219E+11 | 36089.09 | 08-NOV-21:00 | 7.00 | 4.42 | 0.498556E+09 | 398.28 | 07-NOV-22:10 | 7.00 | 1.99 |
December | 0.496302E+11 | 35814.65 | 01-DEC-21:00 | 5.00 | 0.55 | 0.514167E+09 | 396.57 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.608440E+12 | 0.589793E+10 | ||||||||
Minimum of Months | 0.451513E+11 | 35814.65 | 5.00 | 0.55 | 0.461615E+09 | 357.93 | 2.00 | -0.7 | ||
Maximum of Months | 0.538596E+11 | 38375.66 | 32.70 | 13.85 | 0.517043E+09 | 399.66 | 15.13 | 11.41 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212510E+11 | 17008.77 | 20-JAN-13:00 | 21.00 | 6.93 | 0.831373E+10 | 5318.25 | 20-JAN-22:19 | 7.67 | 1.90 |
February | 0.177771E+11 | 16769.59 | 18-FEB-13:20 | 20.00 | 7.71 | 0.749068E+10 | 5237.24 | 17-FEB-22:19 | 7.00 | 3.15 |
March | 0.196895E+11 | 15237.86 | 14-MAR-12:50 | 23.67 | 7.77 | 0.827925E+10 | 5260.97 | 13-MAR-22:10 | 10.17 | 1.84 |
April | 0.170709E+11 | 12865.32 | 07-APR-12:30 | 20.50 | 8.10 | 0.792457E+10 | 5107.65 | 07-APR-22:10 | 10.83 | 6.15 |
May | 0.217408E+11 | 12591.98 | 10-MAY-21:05 | 20.33 | 7.89 | 0.818354E+10 | 5066.62 | 25-MAY-21:19 | 9.00 | 6.80 |
June | 0.255231E+11 | 13990.67 | 26-JUN-21:10 | 28.17 | 11.13 | 0.791315E+10 | 4928.07 | 09-JUN-22:10 | 13.30 | 8.82 |
July | 0.266645E+11 | 14042.61 | 17-JUL-21:20 | 28.00 | 13.30 | 0.814379E+10 | 5007.14 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.271104E+11 | 14030.55 | 16-AUG-21:15 | 25.33 | 11.67 | 0.817813E+10 | 4893.17 | 12-AUG-23:19 | 11.00 | 7.35 |
September | 0.262762E+11 | 15544.99 | 28-SEP-12:50 | 30.42 | 11.27 | 0.793039E+10 | 5135.32 | 25-SEP-22:10 | 11.42 | 4.97 |
October | 0.221568E+11 | 15942.73 | 07-OCT-12:40 | 23.00 | 9.44 | 0.830544E+10 | 5352.43 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.211423E+11 | 16867.29 | 05-NOV-12:00 | 20.00 | 5.59 | 0.806397E+10 | 5269.01 | 07-NOV-22:19 | 7.00 | 1.99 |
December | 0.188828E+11 | 16696.90 | 02-DEC-13:00 | 21.00 | 7.10 | 0.826590E+10 | 5136.45 | 01-DEC-22:19 | 6.00 | 1.08 |
Annual Sum or Average | 0.265285E+12 | 0.969926E+11 | ||||||||
Minimum of Months | 0.170709E+11 | 12591.98 | 20.00 | 5.59 | 0.749068E+10 | 4893.17 | 6.00 | 1.08 | ||
Maximum of Months | 0.271104E+11 | 17008.77 | 30.42 | 13.30 | 0.831373E+10 | 5352.43 | 13.30 | 8.82 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.741942E+11 | 38589.48 | 20-JAN-13:00 | 21.00 | 6.93 | 0.246106E+11 | 15973.83 | 20-JAN-22:19 | 7.67 | 1.90 |
February | 0.643001E+11 | 39895.16 | 18-FEB-13:10 | 20.00 | 7.71 | 0.221884E+11 | 15773.26 | 17-FEB-22:19 | 7.00 | 3.15 |
March | 0.724851E+11 | 41485.25 | 14-MAR-18:10 | 17.67 | 5.74 | 0.247978E+11 | 15949.68 | 10-MAR-22:19 | 8.67 | 2.43 |
April | 0.675879E+11 | 40863.53 | 19-APR-18:40 | 17.33 | 8.44 | 0.238810E+11 | 15694.76 | 06-APR-21:49 | 8.67 | 2.17 |
May | 0.787959E+11 | 46277.27 | 10-MAY-21:00 | 21.00 | 8.14 | 0.247086E+11 | 15792.90 | 18-MAY-21:19 | 6.67 | 4.12 |
June | 0.866750E+11 | 47893.26 | 26-JUN-21:10 | 28.17 | 11.13 | 0.235807E+11 | 15249.82 | 09-JUN-22:10 | 13.30 | 8.82 |
July | 0.899386E+11 | 47933.01 | 17-JUL-21:10 | 28.50 | 13.41 | 0.242371E+11 | 15443.39 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.901880E+11 | 47847.00 | 16-AUG-21:15 | 25.33 | 11.67 | 0.243390E+11 | 14974.79 | 22-AUG-21:19 | 15.00 | 11.51 |
September | 0.857647E+11 | 47526.31 | 12-SEP-21:10 | 22.93 | 12.79 | 0.237188E+11 | 15616.31 | 25-SEP-22:10 | 11.42 | 4.97 |
October | 0.772932E+11 | 42766.88 | 10-OCT-18:10 | 18.83 | 5.87 | 0.247984E+11 | 16111.29 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.733234E+11 | 40917.94 | 05-NOV-10:00 | 18.00 | 6.29 | 0.238993E+11 | 15961.27 | 07-NOV-22:19 | 7.00 | 1.99 |
December | 0.695998E+11 | 40973.37 | 17-DEC-12:50 | 17.67 | 5.66 | 0.245168E+11 | 15727.65 | 04-DEC-22:19 | 7.33 | 0.74 |
Annual Sum or Average | 0.930146E+12 | 0.289277E+12 | ||||||||
Minimum of Months | 0.643001E+11 | 38589.48 | 17.33 | 5.66 | 0.221884E+11 | 14974.79 | 6.67 | 0.74 | ||
Maximum of Months | 0.901880E+11 | 47933.01 | 28.50 | 13.41 | 0.247984E+11 | 16111.29 | 15.00 | 11.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469617E+09 | 4477.75 | 14-JAN-16:01 | -4.7 | -4.7 | 96581049.37 | 56.69 | 20-JAN-22:00 | 7.00 | 1.58 |
February | 0.455057E+09 | 4520.66 | 11-FEB-16:01 | -9.2 | -9.4 | 86817218.52 | 56.69 | 21-FEB-22:10 | 2.67 | 2.67 |
March | 0.713350E+09 | 4540.17 | 13-MAR-15:01 | 23.00 | 6.93 | 96528282.28 | 56.69 | 31-MAR-21:30 | 9.35 | 3.97 |
April | 0.543531E+09 | 4509.27 | 07-APR-15:01 | 21.00 | 7.77 | 93139350.74 | 56.69 | 11-APR-21:10 | 9.67 | 3.08 |
May | 0.109753E+10 | 4486.32 | 05-MAY-15:01 | 22.83 | 10.78 | 98290800.65 | 56.70 | 31-MAY-22:10 | 17.20 | 10.84 |
June | 0.204376E+10 | 4566.83 | 26-JUN-15:01 | 39.30 | 15.61 | 95732269.34 | 56.70 | 14-JUN-21:49 | 21.47 | 10.59 |
July | 0.197849E+10 | 4578.73 | 01-JUL-18:01 | 27.67 | 10.43 | 98844180.68 | 56.70 | 14-JUL-21:49 | 23.00 | 12.39 |
August | 0.196488E+10 | 4575.46 | 16-AUG-15:01 | 36.17 | 16.15 | 98880360.62 | 56.70 | 15-AUG-21:40 | 22.33 | 12.51 |
September | 0.165640E+10 | 4570.39 | 28-SEP-15:01 | 29.50 | 11.00 | 95451513.81 | 56.70 | 01-SEP-21:10 | 17.02 | 12.14 |
October | 0.907674E+09 | 4569.90 | 11-OCT-15:01 | 25.67 | 9.28 | 97043537.47 | 56.69 | 05-OCT-21:00 | 14.00 | 5.74 |
November | 0.572356E+09 | 4527.11 | 05-NOV-15:01 | 20.67 | 6.55 | 93679591.22 | 56.69 | 08-NOV-22:00 | 7.00 | 3.59 |
December | 0.355985E+09 | 4401.05 | 02-DEC-16:01 | 17.33 | 5.82 | 95653623.45 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.127586E+11 | 0.114664E+10 | ||||||||
Minimum of Months | 0.355985E+09 | 4401.05 | -9.2 | -9.4 | 86817218.52 | 56.69 | 2.67 | 0.70 | ||
Maximum of Months | 0.204376E+10 | 4578.73 | 39.30 | 16.15 | 98880360.62 | 56.70 | 23.00 | 12.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167538E+09 | 4354.38 | 23-JAN-16:01 | 18.17 | 6.11 | 94584394.37 | 56.69 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.190356E+09 | 4357.40 | 25-FEB-16:01 | 12.00 | 3.88 | 85365746.51 | 56.69 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.455077E+09 | 4436.19 | 13-MAR-15:01 | 23.00 | 6.93 | 95721404.45 | 56.69 | 14-MAR-22:40 | 12.33 | 3.66 |
April | 0.442191E+09 | 4436.32 | 07-APR-15:01 | 21.00 | 7.77 | 92752918.79 | 56.69 | 20-APR-21:30 | 14.00 | 7.95 |
May | 0.103922E+10 | 4437.84 | 15-MAY-15:01 | 23.83 | 10.82 | 98180671.17 | 56.70 | 31-MAY-22:10 | 17.20 | 10.84 |
June | 0.201489E+10 | 4525.37 | 27-JUN-18:01 | 32.02 | 14.31 | 95733430.05 | 56.70 | 14-JUN-21:40 | 21.83 | 11.13 |
July | 0.193185E+10 | 4537.48 | 01-JUL-18:01 | 27.67 | 10.43 | 98837123.07 | 56.70 | 14-JUL-21:40 | 23.00 | 12.39 |
August | 0.181363E+10 | 4524.77 | 16-AUG-15:01 | 36.17 | 16.15 | 98810780.71 | 56.70 | 03-AUG-21:49 | 21.83 | 16.38 |
September | 0.135926E+10 | 4497.00 | 10-SEP-15:01 | 31.70 | 12.47 | 95189822.66 | 56.69 | 27-SEP-21:30 | 14.70 | 5.31 |
October | 0.541068E+09 | 4473.38 | 11-OCT-15:01 | 25.67 | 9.28 | 96139699.92 | 56.69 | 20-OCT-21:40 | 10.67 | 1.74 |
November | 0.217477E+09 | 4396.04 | 07-NOV-16:01 | 20.00 | 6.99 | 92112475.23 | 56.69 | 07-NOV-23:10 | 7.17 | 2.01 |
December | 0.117671E+09 | 4297.37 | 02-DEC-16:01 | 17.33 | 5.82 | 94113825.17 | 56.69 | 04-DEC-22:49 | 7.83 | 0.84 |
Annual Sum or Average | 0.102902E+11 | 0.113754E+10 | ||||||||
Minimum of Months | 0.117671E+09 | 4297.37 | 12.00 | 3.88 | 85365746.51 | 56.69 | 7.00 | 0.84 | ||
Maximum of Months | 0.201489E+10 | 4537.48 | 36.17 | 16.15 | 98837123.07 | 56.70 | 23.00 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773343E+09 | 1034.97 | 20-JAN-12:30 | 20.50 | 7.25 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.588198E+09 | 961.07 | 18-FEB-12:50 | 19.67 | 7.56 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.564432E+09 | 849.99 | 11-MAR-12:50 | 16.83 | 5.45 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.371340E+09 | 536.33 | 08-APR-12:40 | 16.00 | 5.12 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.525526E+09 | 440.74 | 31-MAY-17:12 | 26.67 | 14.51 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.735715E+09 | 578.93 | 30-JUN-20:20 | 26.60 | 11.13 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.792347E+09 | 631.86 | 02-JUL-18:40 | 26.67 | 12.20 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.818394E+09 | 663.23 | 02-AUG-18:03 | 26.67 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.846662E+09 | 850.87 | 28-SEP-12:30 | 30.25 | 11.29 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.746542E+09 | 906.57 | 10-OCT-12:30 | 23.50 | 7.87 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.732171E+09 | 1001.54 | 07-NOV-11:53 | 20.00 | 7.54 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.624813E+09 | 982.00 | 17-DEC-12:10 | 16.33 | 5.29 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.811948E+10 | 0.00 | ||||||||
Minimum of Months | 0.371340E+09 | 440.74 | 16.00 | 5.12 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.846662E+09 | 1034.97 | 30.25 | 15.46 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261781E+09 | 1350.08 | 21-JAN-09:01 | 13.00 | 3.73 | 95386756.33 | 56.69 | 20-JAN-23:40 | 7.00 | 1.58 |
February | 0.219062E+09 | 1348.12 | 19-FEB-09:01 | 5.17 | 2.81 | 85974929.53 | 56.69 | 19-FEB-01:10 | 10.00 | 3.47 |
March | 0.381582E+09 | 1382.86 | 14-MAR-15:01 | 22.83 | 7.46 | 96281588.30 | 56.69 | 15-MAR-02:00 | 13.00 | 4.57 |
April | 0.435796E+09 | 1391.50 | 27-APR-15:01 | 20.83 | 10.38 | 93467883.01 | 56.69 | 26-APR-21:30 | 6.50 | 5.17 |
May | 0.721392E+09 | 1448.21 | 18-MAY-15:01 | 22.33 | 11.63 | 97977836.48 | 56.69 | 31-MAY-21:10 | 17.88 | 12.23 |
June | 0.973640E+09 | 1458.77 | 29-JUN-18:01 | 24.72 | 13.51 | 95480457.47 | 56.70 | 30-JUN-22:10 | 24.98 | 10.75 |
July | 0.102125E+10 | 1462.10 | 08-JUL-15:01 | 26.33 | 12.92 | 98616368.17 | 56.70 | 18-JUL-21:49 | 24.00 | 12.36 |
August | 0.932243E+09 | 1455.53 | 19-AUG-18:01 | 25.67 | 13.33 | 98524692.76 | 56.70 | 03-AUG-21:49 | 21.83 | 16.38 |
September | 0.777164E+09 | 1452.81 | 11-SEP-15:01 | 29.22 | 13.47 | 94879195.55 | 56.69 | 08-SEP-21:10 | 21.60 | 10.27 |
October | 0.455736E+09 | 1401.88 | 11-OCT-15:01 | 25.67 | 9.28 | 96537232.70 | 56.69 | 02-OCT-21:10 | 3.00 | 3.00 |
November | 0.302381E+09 | 1357.67 | 09-NOV-19:01 | 11.67 | 7.18 | 92752286.99 | 56.69 | 09-NOV-22:40 | 8.00 | 6.69 |
December | 0.228116E+09 | 1333.43 | 03-DEC-09:01 | 9.50 | 2.23 | 94920711.41 | 56.69 | 26-DEC-22:10 | 2.17 | -1.5 |
Annual Sum or Average | 0.671015E+10 | 0.114080E+10 | ||||||||
Minimum of Months | 0.219062E+09 | 1333.43 | 5.17 | 2.23 | 85974929.53 | 56.69 | 2.17 | -1.5 | ||
Maximum of Months | 0.102125E+10 | 1462.10 | 29.22 | 13.51 | 98616368.17 | 56.70 | 24.98 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454946E+09 | 3973.08 | 22-JAN-09:01 | 1.33 | 0.33 | 96829811.94 | 56.69 | 20-JAN-22:00 | 7.00 | 1.58 |
February | 0.483710E+09 | 4002.27 | 11-FEB-09:01 | -6.0 | -6.0 | 87094580.87 | 56.69 | 22-FEB-22:10 | 2.83 | 2.42 |
March | 0.747822E+09 | 3986.95 | 11-MAR-09:01 | 13.17 | 4.39 | 96870420.23 | 56.69 | 14-MAR-22:30 | 12.50 | 3.75 |
April | 0.622455E+09 | 3939.91 | 19-APR-08:62 | 16.33 | 7.18 | 93530972.87 | 56.69 | 07-APR-21:49 | 11.17 | 6.30 |
May | 0.118603E+10 | 3969.94 | 17-MAY-08:62 | 22.50 | 11.06 | 98668550.04 | 56.69 | 24-MAY-21:10 | 14.83 | 10.24 |
June | 0.214755E+10 | 4049.77 | 30-JUN-08:61 | 27.57 | 12.55 | 95991294.17 | 56.70 | 14-JUN-21:00 | 21.10 | 10.07 |
July | 0.218870E+10 | 4071.51 | 01-JUL-08:61 | 26.00 | 9.43 | 99052952.43 | 56.70 | 14-JUL-21:49 | 23.00 | 12.39 |
August | 0.214293E+10 | 4040.26 | 19-AUG-08:61 | 21.50 | 10.16 | 99163253.99 | 56.70 | 24-AUG-21:49 | 17.50 | 14.46 |
September | 0.173606E+10 | 4016.53 | 09-SEP-08:61 | 24.45 | 11.74 | 95718715.43 | 56.69 | 05-SEP-21:49 | 17.52 | 11.60 |
October | 0.878240E+09 | 3976.76 | 11-OCT-15:01 | 25.67 | 9.28 | 97276163.73 | 56.69 | 11-OCT-21:00 | 8.00 | 4.09 |
November | 0.544270E+09 | 3972.59 | 07-NOV-09:01 | 14.00 | 4.06 | 93756679.94 | 56.69 | 08-NOV-22:00 | 7.00 | 3.59 |
December | 0.356447E+09 | 3951.04 | 18-DEC-09:01 | 0.50 | -1.8 | 95810429.69 | 56.69 | 01-DEC-22:49 | 6.00 | 1.08 |
Annual Sum or Average | 0.134892E+11 | 0.114976E+10 | ||||||||
Minimum of Months | 0.356447E+09 | 3939.91 | -6.0 | -6.0 | 87094580.87 | 56.69 | 2.83 | 1.08 | ||
Maximum of Months | 0.218870E+10 | 4071.51 | 27.57 | 12.55 | 99163253.99 | 56.70 | 23.00 | 14.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163675E+09 | 3858.45 | 20-JAN-09:01 | 10.67 | 3.17 | 94530228.88 | 56.69 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.217568E+09 | 3926.18 | 23-FEB-09:01 | 1.50 | 0.96 | 85557016.82 | 56.69 | 27-FEB-22:10 | 2.00 | -0.7 |
March | 0.474051E+09 | 3938.03 | 11-MAR-09:01 | 13.17 | 4.39 | 96126259.33 | 56.69 | 14-MAR-21:49 | 13.00 | 3.98 |
April | 0.513980E+09 | 3916.58 | 19-APR-08:62 | 16.33 | 7.18 | 93220500.76 | 56.69 | 19-APR-21:40 | 12.67 | 6.52 |
May | 0.112404E+10 | 3951.00 | 17-MAY-08:62 | 22.50 | 11.06 | 98586435.75 | 56.69 | 31-MAY-21:30 | 17.65 | 11.71 |
June | 0.211599E+10 | 4033.40 | 30-JUN-08:61 | 27.57 | 12.55 | 95988637.73 | 56.70 | 14-JUN-21:49 | 21.47 | 10.59 |
July | 0.213980E+10 | 4054.91 | 01-JUL-08:61 | 26.00 | 9.43 | 99047815.73 | 56.70 | 10-JUL-21:40 | 23.00 | 12.03 |
August | 0.198760E+10 | 4019.92 | 19-AUG-08:61 | 21.50 | 10.16 | 99145006.14 | 56.69 | 25-AUG-22:30 | 23.00 | 16.10 |
September | 0.142659E+10 | 3994.73 | 09-SEP-08:61 | 24.45 | 11.74 | 95594104.43 | 56.70 | 06-SEP-21:10 | 20.42 | 11.60 |
October | 0.498327E+09 | 3915.12 | 08-OCT-08:61 | 14.50 | 7.40 | 96493799.35 | 56.69 | 10-OCT-21:30 | 13.50 | 4.19 |
November | 0.210552E+09 | 3894.77 | 07-NOV-09:01 | 14.00 | 4.06 | 91960669.82 | 56.69 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 0.121429E+09 | 3818.64 | 02-DEC-09:01 | 11.75 | 4.07 | 94026647.03 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.109936E+11 | 0.114028E+10 | ||||||||
Minimum of Months | 0.121429E+09 | 3818.64 | 1.50 | 0.96 | 85557016.82 | 56.69 | 2.00 | -0.7 | ||
Maximum of Months | 0.213980E+10 | 4054.91 | 27.57 | 12.55 | 99145006.14 | 56.70 | 23.00 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152967E+10 | 2389.36 | 20-JAN-13:40 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.126466E+10 | 2321.80 | 18-FEB-14:00 | 20.00 | 7.70 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.170485E+10 | 2391.74 | 14-MAR-13:20 | 23.67 | 7.76 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.140324E+10 | 1973.67 | 20-APR-18:15 | 17.00 | 8.37 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.275178E+10 | 2261.12 | 31-MAY-18:30 | 24.50 | 14.05 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.409485E+10 | 2438.79 | 26-JUN-19:10 | 35.03 | 14.30 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.428030E+10 | 2411.95 | 15-JUL-18:50 | 32.17 | 12.76 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.416403E+10 | 2422.51 | 16-AUG-18:30 | 32.50 | 14.30 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.372902E+10 | 2422.95 | 28-SEP-13:40 | 30.50 | 11.26 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.224470E+10 | 2422.16 | 11-OCT-14:00 | 27.00 | 9.69 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.165509E+10 | 2412.83 | 07-NOV-14:00 | 22.00 | 7.30 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.110913E+10 | 2306.11 | 02-DEC-13:30 | 21.00 | 7.10 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.299313E+11 | 0.00 | ||||||||
Minimum of Months | 0.110913E+10 | 1973.67 | 17.00 | 6.93 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.428030E+10 | 2438.79 | 35.03 | 14.30 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447818E+09 | 4816.77 | 23-JAN-16:01 | 18.17 | 6.11 | 96227314.47 | 56.69 | 27-JAN-22:10 | 3.00 | 3.00 |
February | 0.452526E+09 | 4820.17 | 17-FEB-16:01 | 13.83 | 6.77 | 86604045.75 | 56.69 | 17-FEB-22:40 | 7.00 | 3.15 |
March | 0.759864E+09 | 4903.52 | 13-MAR-15:01 | 23.00 | 6.93 | 96328423.45 | 56.69 | 14-MAR-22:10 | 12.83 | 3.93 |
April | 0.588257E+09 | 4852.17 | 07-APR-15:01 | 21.00 | 7.77 | 92967035.12 | 56.69 | 07-APR-21:00 | 11.00 | 6.29 |
May | 0.126607E+10 | 4845.28 | 15-MAY-15:01 | 23.83 | 10.82 | 98416599.11 | 56.70 | 23-MAY-00:00 | 10.00 | 8.79 |
June | 0.247346E+10 | 4948.78 | 26-JUN-15:01 | 39.30 | 15.61 | 95814144.53 | 56.70 | 10-JUN-04:00 | 9.40 | 4.46 |
July | 0.239185E+10 | 4945.86 | 01-JUL-18:01 | 27.67 | 10.43 | 98918052.59 | 56.70 | 14-JUL-21:00 | 23.00 | 12.39 |
August | 0.237690E+10 | 4959.31 | 16-AUG-15:01 | 36.17 | 16.15 | 98945121.97 | 56.70 | 23-AUG-03:00 | 12.00 | 9.06 |
September | 0.191881E+10 | 4939.24 | 28-SEP-15:01 | 29.50 | 11.00 | 95449917.86 | 56.70 | 15-SEP-04:49 | 8.90 | 3.87 |
October | 0.976509E+09 | 4930.44 | 11-OCT-15:01 | 25.67 | 9.28 | 96912313.94 | 56.70 | 10-OCT-04:00 | 9.00 | 5.34 |
November | 0.570738E+09 | 4881.85 | 05-NOV-15:01 | 20.67 | 6.55 | 93443980.46 | 56.70 | 07-NOV-00:40 | 5.33 | 0.49 |
December | 0.325229E+09 | 4741.02 | 02-DEC-16:01 | 17.33 | 5.82 | 95245796.38 | 56.69 | 04-DEC-22:30 | 7.50 | 0.77 |
Annual Sum or Average | 0.145480E+11 | 0.114527E+10 | ||||||||
Minimum of Months | 0.325229E+09 | 4741.02 | 13.83 | 5.82 | 86604045.75 | 56.69 | 3.00 | 0.49 | ||
Maximum of Months | 0.247346E+10 | 4959.31 | 39.30 | 16.15 | 98945121.97 | 56.70 | 23.00 | 12.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143676E+09 | 4676.16 | 23-JAN-16:01 | 18.17 | 6.11 | 94198888.60 | 56.69 | 19-JAN-22:10 | 7.67 | 1.93 |
February | 0.175900E+09 | 4682.20 | 25-FEB-16:01 | 12.00 | 3.88 | 85190125.63 | 56.69 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.481142E+09 | 4789.70 | 13-MAR-15:01 | 23.00 | 6.93 | 95594445.69 | 56.69 | 10-MAR-22:10 | 8.83 | 2.52 |
April | 0.473552E+09 | 4774.42 | 07-APR-15:01 | 21.00 | 7.77 | 92640422.27 | 56.69 | 20-APR-21:40 | 14.00 | 7.95 |
May | 0.119971E+10 | 4795.79 | 15-MAY-15:01 | 23.83 | 10.82 | 98352465.93 | 56.70 | 29-MAY-03:00 | 10.00 | 8.79 |
June | 0.244377E+10 | 4903.29 | 26-JUN-15:01 | 39.30 | 15.61 | 95821133.02 | 56.70 | 14-JUN-21:00 | 21.10 | 10.07 |
July | 0.234293E+10 | 4905.46 | 01-JUL-18:01 | 27.67 | 10.43 | 98919917.22 | 56.70 | 06-JUL-21:10 | 20.33 | 10.96 |
August | 0.221220E+10 | 4906.07 | 16-AUG-15:01 | 36.17 | 16.15 | 98911650.45 | 56.70 | 25-AUG-23:10 | 22.00 | 16.05 |
September | 0.159224E+10 | 4860.50 | 10-SEP-15:01 | 31.70 | 12.47 | 95284002.43 | 56.70 | 26-SEP-04:00 | 12.20 | 4.42 |
October | 0.575543E+09 | 4821.77 | 11-OCT-15:01 | 25.67 | 9.28 | 96166964.08 | 56.69 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.205865E+09 | 4734.65 | 07-NOV-16:01 | 20.00 | 6.99 | 91872893.37 | 56.69 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 96769941.51 | 4615.22 | 02-DEC-16:01 | 17.33 | 5.82 | 93731831.49 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.119433E+11 | 0.113668E+10 | ||||||||
Minimum of Months | 96769941.51 | 4615.22 | 12.00 | 3.88 | 85190125.63 | 56.69 | 7.00 | 0.70 | ||
Maximum of Months | 0.244377E+10 | 4906.07 | 39.30 | 16.15 | 98919917.22 | 56.70 | 22.00 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.970136E+09 | 2208.74 | 14-JAN-16:01 | -4.7 | -4.7 | 97728309.51 | 56.69 | 27-JAN-22:49 | 3.00 | 3.00 |
February | 0.750640E+09 | 2225.57 | 11-FEB-16:01 | -9.2 | -9.4 | 87774406.75 | 56.69 | 19-FEB-01:49 | 10.00 | 3.47 |
March | 0.735880E+09 | 2185.44 | 13-MAR-15:01 | 23.00 | 6.93 | 97023580.49 | 56.69 | 15-MAR-01:39 | 12.33 | 3.88 |
April | 0.436166E+09 | 2136.69 | 07-APR-15:01 | 21.00 | 7.77 | 93459075.27 | 56.69 | 27-APR-22:10 | 10.83 | 8.18 |
May | 0.771015E+09 | 2144.83 | 16-MAY-15:01 | 27.00 | 11.80 | 98394497.49 | 56.69 | 23-MAY-21:00 | 13.00 | 10.62 |
June | 0.128472E+10 | 2164.35 | 26-JUN-15:01 | 39.30 | 15.61 | 95769979.50 | 56.70 | 14-JUN-21:10 | 22.93 | 12.76 |
July | 0.137433E+10 | 2164.28 | 08-JUL-15:01 | 26.33 | 12.92 | 98895445.98 | 56.70 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.141279E+10 | 2166.81 | 16-AUG-15:01 | 36.17 | 16.15 | 98945880.72 | 56.70 | 14-AUG-21:10 | 25.83 | 10.40 |
September | 0.137723E+10 | 2184.74 | 28-SEP-15:01 | 29.50 | 11.00 | 95566478.77 | 56.69 | 09-SEP-23:00 | 18.80 | 10.31 |
October | 0.102473E+10 | 2195.69 | 11-OCT-15:01 | 25.67 | 9.28 | 97397452.22 | 56.69 | 11-OCT-02:20 | 11.67 | 4.35 |
November | 0.980474E+09 | 2201.19 | 05-NOV-15:01 | 20.67 | 6.55 | 94659331.15 | 56.69 | 09-NOV-23:10 | 8.00 | 6.95 |
December | 0.767572E+09 | 2155.67 | 10-DEC-16:01 | -1.4 | -4.3 | 97138550.27 | 56.69 | 14-DEC-22:30 | 1.50 | -1.8 |
Annual Sum or Average | 0.118857E+11 | 0.115275E+10 | ||||||||
Minimum of Months | 0.436166E+09 | 2136.69 | -9.2 | -9.4 | 87774406.75 | 56.69 | 1.50 | -1.8 | ||
Maximum of Months | 0.141279E+10 | 2225.57 | 39.30 | 16.15 | 98945880.72 | 56.70 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384299E+11 | 19224.38 | 20-JAN-23:00 | 7.00 | 1.58 | 0.150408E+11 | 9967.19 | 20-JAN-23:10 | 7.00 | 1.58 |
February | 0.346540E+11 | 19087.12 | 17-FEB-23:00 | 7.00 | 3.15 | 0.135787E+11 | 9902.33 | 17-FEB-23:10 | 7.00 | 3.08 |
March | 0.407332E+11 | 20760.61 | 14-MAR-18:10 | 17.67 | 5.74 | 0.153144E+11 | 10114.19 | 16-MAR-22:10 | 9.83 | 4.12 |
April | 0.402462E+11 | 21316.67 | 20-APR-22:00 | 14.00 | 7.94 | 0.148312E+11 | 10067.60 | 12-APR-22:10 | 9.50 | 3.96 |
May | 0.459694E+11 | 23669.03 | 10-MAY-21:10 | 20.33 | 7.89 | 0.153687E+11 | 10150.07 | 25-MAY-22:10 | 9.00 | 6.88 |
June | 0.495548E+11 | 24765.78 | 26-JUN-21:15 | 27.53 | 11.05 | 0.143413E+11 | 9772.48 | 09-JUN-22:10 | 13.30 | 8.82 |
July | 0.512170E+11 | 24693.83 | 17-JUL-21:20 | 28.00 | 13.30 | 0.146314E+11 | 9911.93 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.505829E+11 | 24623.36 | 16-AUG-22:00 | 24.00 | 13.66 | 0.147142E+11 | 9513.87 | 22-AUG-22:10 | 15.00 | 11.72 |
September | 0.463276E+11 | 24243.24 | 12-SEP-21:20 | 22.57 | 12.61 | 0.144485E+11 | 9981.85 | 22-SEP-22:10 | 9.40 | 3.39 |
October | 0.415591E+11 | 21070.80 | 10-OCT-18:10 | 18.83 | 5.87 | 0.152652E+11 | 10109.34 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.382074E+11 | 19544.15 | 09-NOV-23:00 | 8.00 | 6.87 | 0.146319E+11 | 10032.58 | 09-NOV-23:10 | 8.00 | 6.95 |
December | 0.371622E+11 | 19163.10 | 04-DEC-23:00 | 8.00 | 0.87 | 0.149524E+11 | 9955.79 | 04-DEC-23:10 | 7.83 | 0.78 |
Annual Sum or Average | 0.514644E+12 | 0.177118E+12 | ||||||||
Minimum of Months | 0.346540E+11 | 19087.12 | 7.00 | 0.87 | 0.135787E+11 | 9513.87 | 7.00 | 0.78 | ||
Maximum of Months | 0.512170E+11 | 24765.78 | 28.00 | 13.66 | 0.153687E+11 | 10150.07 | 15.00 | 11.72 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415171E+11 | 20470.54 | 20-JAN-23:00 | 7.00 | 1.58 | 0.151381E+11 | 10068.66 | 20-JAN-23:10 | 7.00 | 1.58 |
February | 0.374673E+11 | 20329.19 | 17-FEB-23:00 | 7.00 | 3.15 | 0.136695E+11 | 10004.19 | 17-FEB-23:10 | 7.00 | 3.08 |
March | 0.439467E+11 | 21990.46 | 14-MAR-22:00 | 13.00 | 4.03 | 0.154254E+11 | 10213.22 | 16-MAR-22:10 | 9.83 | 4.12 |
April | 0.434058E+11 | 22589.74 | 20-APR-22:00 | 14.00 | 7.94 | 0.149409E+11 | 10170.07 | 28-APR-22:10 | 9.00 | 7.74 |
May | 0.492543E+11 | 24995.52 | 10-MAY-21:10 | 20.33 | 7.89 | 0.154536E+11 | 10254.41 | 25-MAY-22:10 | 9.00 | 6.88 |
June | 0.526544E+11 | 26081.22 | 26-JUN-21:15 | 27.53 | 11.05 | 0.143615E+11 | 9835.50 | 09-JUN-22:10 | 13.30 | 8.82 |
July | 0.543743E+11 | 26011.89 | 17-JUL-21:20 | 28.00 | 13.30 | 0.146485E+11 | 9976.66 | 05-JUL-22:10 | 12.17 | 7.77 |
August | 0.537257E+11 | 25914.95 | 16-AUG-21:15 | 25.33 | 11.67 | 0.147306E+11 | 9569.15 | 22-AUG-22:10 | 15.00 | 11.72 |
September | 0.493522E+11 | 25514.26 | 12-SEP-21:20 | 22.57 | 12.61 | 0.144846E+11 | 10077.60 | 22-SEP-22:10 | 9.40 | 3.39 |
October | 0.447147E+11 | 22333.48 | 05-OCT-22:00 | 14.00 | 5.74 | 0.153638E+11 | 10195.26 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.412031E+11 | 20803.29 | 09-NOV-23:00 | 8.00 | 6.87 | 0.147314E+11 | 10132.62 | 09-NOV-23:10 | 8.00 | 6.95 |
December | 0.402733E+11 | 20406.99 | 04-DEC-23:00 | 8.00 | 0.87 | 0.150441E+11 | 10057.64 | 04-DEC-23:10 | 7.83 | 0.78 |
Annual Sum or Average | 0.551889E+12 | 0.177992E+12 | ||||||||
Minimum of Months | 0.374673E+11 | 20329.19 | 7.00 | 0.87 | 0.136695E+11 | 9569.15 | 7.00 | 0.78 | ||
Maximum of Months | 0.543743E+11 | 26081.22 | 28.00 | 13.30 | 0.154536E+11 | 10254.41 | 15.00 | 11.72 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527337E+11 | 28565.39 | 20-JAN-11:50 | 19.67 | 7.38 | 0.186460E+11 | 11362.08 | 21-JAN-18:00 | 8.00 | 3.20 |
February | 0.475163E+11 | 28468.13 | 18-FEB-11:50 | 17.83 | 6.75 | 0.168443E+11 | 11367.18 | 25-FEB-18:00 | 7.00 | 2.76 |
March | 0.542554E+11 | 29236.24 | 14-MAR-10:50 | 21.00 | 6.94 | 0.186535E+11 | 11365.95 | 25-MAR-17:00 | 7.00 | 4.42 |
April | 0.527812E+11 | 29022.13 | 19-APR-10:50 | 20.67 | 8.02 | 0.180462E+11 | 11367.74 | 29-APR-17:00 | 8.00 | 6.34 |
May | 0.577465E+11 | 29311.58 | 16-MAY-10:50 | 24.83 | 11.28 | 0.186121E+11 | 11339.81 | 27-MAY-17:00 | 13.00 | 8.49 |
June | 0.592337E+11 | 29900.35 | 26-JUN-18:07 | 37.33 | 15.05 | 0.179504E+11 | 11279.00 | 24-JUN-17:00 | 30.50 | 12.45 |
July | 0.610352E+11 | 29881.71 | 23-JUL-10:50 | 29.83 | 15.93 | 0.185367E+11 | 11282.08 | 15-JUL-17:00 | 33.00 | 13.20 |
August | 0.608694E+11 | 29842.63 | 06-AUG-10:50 | 29.50 | 15.91 | 0.185459E+11 | 11275.29 | 26-AUG-17:40 | 30.33 | 11.56 |
September | 0.572928E+11 | 29472.17 | 09-SEP-10:50 | 31.23 | 12.81 | 0.179626E+11 | 11328.58 | 30-SEP-17:00 | 12.70 | 11.29 |
October | 0.548293E+11 | 29330.59 | 07-OCT-10:50 | 20.67 | 9.06 | 0.186376E+11 | 11365.71 | 28-OCT-17:00 | 9.00 | 4.52 |
November | 0.515827E+11 | 28759.38 | 07-NOV-11:50 | 19.33 | 7.22 | 0.180450E+11 | 11360.30 | 04-NOV-17:00 | 4.30 | 3.92 |
December | 0.516007E+11 | 28311.58 | 02-DEC-11:50 | 19.50 | 6.87 | 0.186325E+11 | 11351.47 | 30-DEC-18:00 | 1.00 | 0.07 |
Annual Sum or Average | 0.661477E+12 | 0.219113E+12 | ||||||||
Minimum of Months | 0.475163E+11 | 28311.58 | 17.83 | 6.75 | 0.168443E+11 | 11275.29 | 1.00 | 0.07 | ||
Maximum of Months | 0.610352E+11 | 29900.35 | 37.33 | 15.93 | 0.186535E+11 | 11367.74 | 33.00 | 13.20 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244475E+10 | 6222.23 | 20-JAN-13:40 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.219134E+10 | 6037.22 | 18-FEB-13:40 | 20.00 | 7.70 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.322860E+10 | 6336.95 | 14-MAR-13:10 | 23.83 | 7.81 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.288546E+10 | 5656.37 | 12-APR-12:40 | 20.33 | 7.61 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.622318E+10 | 6060.25 | 16-MAY-12:30 | 27.00 | 11.92 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.977880E+10 | 6501.16 | 26-JUN-14:40 | 38.83 | 15.46 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.100408E+11 | 6461.69 | 23-JUL-13:20 | 34.33 | 16.28 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.976438E+10 | 6496.29 | 16-AUG-15:40 | 36.67 | 16.26 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.800877E+10 | 6543.40 | 28-SEP-13:30 | 30.50 | 11.26 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.430910E+10 | 6342.80 | 10-OCT-13:30 | 24.50 | 8.28 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.295501E+10 | 6297.59 | 07-NOV-13:40 | 21.33 | 7.21 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.178199E+10 | 5360.10 | 01-DEC-13:30 | 21.50 | 7.82 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.636122E+11 | 0.00 | ||||||||
Minimum of Months | 0.178199E+10 | 5360.10 | 20.00 | 6.93 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.100408E+11 | 6543.40 | 38.83 | 16.28 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299350E+09 | 1517.12 | 05-JAN-09:10 | -17.0 |
February | 0.496390E+09 | 1457.39 | 12-FEB-05:40 | -19.3 |
March | 0.360212E+09 | 1438.03 | 19-MAR-08:10 | -13.0 |
April | 0.275373E+09 | 1078.99 | 03-APR-04:00 | -8.0 |
May | 4147727.78 | 165.45 | 03-MAY-02:00 | -1.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 6179083.00 | 347.62 | 22-SEP-06:05 | -1.4 |
October | 0.292455E+09 | 1286.20 | 31-OCT-15:00 | -8.0 |
November | 0.270449E+09 | 1321.36 | 30-NOV-04:50 | -13.2 |
December | 0.664168E+09 | 1861.35 | 21-DEC-08:10 | -20.0 |
Annual Sum or Average | 0.266872E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.664168E+09 | 1861.35 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5740308.89 | 163.26 | 06-JAN-04:20 | -10.7 |
February | 5886611.94 | 157.34 | 13-FEB-05:00 | -11.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 104825.49 | 33.70 | 03-APR-04:00 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 613461.02 | 96.57 | 31-OCT-04:00 | -8.0 |
November | 2500824.00 | 145.69 | 30-NOV-05:00 | -13.0 |
December | 44149507.92 | 277.39 | 23-DEC-06:00 | -22.0 |
Annual Sum or Average | 58995539.25 | |||
Minimum of Months | 0.00 | 0.00 | -22.0 | |
Maximum of Months | 44149507.92 | 277.39 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135683E+09 | 356.76 | 05-JAN-05:00 | -17.0 |
February | 0.182495E+09 | 359.24 | 12-FEB-05:40 | -19.3 |
March | 84430847.75 | 324.02 | 05-MAR-06:00 | -12.0 |
April | 53553733.71 | 283.88 | 03-APR-04:00 | -8.0 |
May | 470815.45 | 34.05 | 03-MAY-03:50 | 2.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 366006.62 | 46.03 | 22-SEP-03:50 | -0.2 |
October | 57834679.48 | 316.92 | 31-OCT-03:50 | -8.0 |
November | 87957102.32 | 348.45 | 30-NOV-05:00 | -13.0 |
December | 0.259615E+09 | 430.71 | 22-DEC-05:00 | -21.0 |
Annual Sum or Average | 0.862407E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.259615E+09 | 430.71 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18657651.94 | 2025.42 | 05-JAN-09:10 | -17.0 |
February | 36243805.03 | 1503.70 | 05-FEB-16:00 | -6.0 |
March | 2982723.90 | 326.32 | 19-MAR-12:20 | -0.7 |
April | 3929132.90 | 522.90 | 03-APR-08:10 | -4.8 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 53393957.02 | 1398.58 | 31-OCT-14:00 | -7.0 |
November | 7680675.89 | 1091.75 | 29-NOV-09:05 | -9.0 |
December | 0.115298E+09 | 2808.87 | 21-DEC-09:30 | -20.0 |
Annual Sum or Average | 0.238186E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.115298E+09 | 2808.87 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353656E+09 | 1923.53 | 30-JAN-09:01 | -2.0 |
February | 0.444346E+09 | 2018.94 | 07-FEB-16:02 | 5.83 |
March | 0.322124E+09 | 1996.42 | 20-MAR-15:01 | 1.83 |
April | 0.248246E+09 | 1975.38 | 03-APR-15:01 | 2.83 |
May | 20679126.29 | 1387.48 | 14-MAY-08:03 | 14.50 |
June | 1187265.03 | 1032.38 | 09-JUN-08:03 | 14.77 |
July | 1208249.12 | 1087.82 | 13-JUL-08:03 | 22.17 |
August | 1630523.14 | 1178.14 | 02-AUG-08:03 | 20.00 |
September | 10967289.20 | 1917.11 | 22-SEP-08:62 | 2.57 |
October | 0.235032E+09 | 1987.48 | 25-OCT-08:61 | 4.50 |
November | 0.305761E+09 | 1964.86 | 10-NOV-16:01 | 0.83 |
December | 0.660899E+09 | 2006.73 | 26-DEC-16:01 | 9.67 |
Annual Sum or Average | 0.260574E+10 | |||
Minimum of Months | 1187265.03 | 1032.38 | -2.0 | |
Maximum of Months | 0.660899E+09 | 2018.94 | 22.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.599609E+09 | 1983.68 | 08-JAN-09:01 | 6.17 |
February | 0.618330E+09 | 2013.25 | 07-FEB-16:02 | 5.83 |
March | 0.388783E+09 | 1992.11 | 20-MAR-15:01 | 1.83 |
April | 0.272945E+09 | 1975.82 | 03-APR-15:01 | 2.83 |
May | 22742349.62 | 1368.03 | 14-MAY-08:03 | 14.50 |
June | 1095061.75 | 989.05 | 09-JUN-08:03 | 14.77 |
July | 1206694.88 | 1071.71 | 13-JUL-08:03 | 22.17 |
August | 1753138.53 | 1162.45 | 24-AUG-08:03 | 15.00 |
September | 14168353.20 | 1917.85 | 22-SEP-08:62 | 2.57 |
October | 0.283392E+09 | 2000.26 | 25-OCT-08:61 | 4.50 |
November | 0.459523E+09 | 1970.90 | 15-NOV-09:01 | 5.33 |
December | 0.929350E+09 | 2016.92 | 26-DEC-16:01 | 9.67 |
Annual Sum or Average | 0.359290E+10 | |||
Minimum of Months | 1095061.75 | 989.05 | 1.83 | |
Maximum of Months | 0.929350E+09 | 2016.92 | 22.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1611497.49 | 100.69 | 06-JAN-04:30 | -10.0 |
February | 8033215.68 | 136.48 | 07-FEB-05:00 | -7.0 |
March | 117.04 | 0.20 | 22-MAR-04:00 | -2.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 2013681.91 | 67.38 | 31-OCT-24:00 | -5.8 |
November | 2296792.45 | 102.51 | 01-NOV-02:70 | -4.2 |
December | 21695040.21 | 251.00 | 21-DEC-05:00 | -18.0 |
Annual Sum or Average | 35650344.78 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 21695040.21 | 251.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31328946.25 | 587.02 | 15-JAN-16:01 | 6.50 |
February | 36965687.49 | 587.30 | 07-FEB-16:02 | 5.83 |
March | 7307175.39 | 553.31 | 20-MAR-15:01 | 1.83 |
April | 2904042.34 | 510.63 | 16-APR-15:02 | -3.0 |
May | 1059308.35 | 547.02 | 27-MAY-15:04 | 16.50 |
June | 324743.46 | 370.09 | 27-JUN-08:04 | 24.00 |
July | 331814.30 | 477.23 | 06-JUL-08:04 | 24.50 |
August | 360911.68 | 431.56 | 11-AUG-08:04 | 25.67 |
September | 844873.90 | 523.66 | 30-SEP-15:04 | 17.20 |
October | 9620790.97 | 558.56 | 24-OCT-15:01 | 2.00 |
November | 18011004.89 | 576.08 | 30-NOV-16:01 | 2.50 |
December | 84299423.77 | 621.57 | 04-DEC-16:03 | 16.17 |
Annual Sum or Average | 0.193359E+09 | |||
Minimum of Months | 324743.46 | 370.09 | -3.0 | |
Maximum of Months | 84299423.77 | 621.57 | 25.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370444E+09 | 1832.84 | 31-JAN-09:02 | -1.8 |
February | 0.468661E+09 | 1924.20 | 07-FEB-16:02 | 5.83 |
March | 0.313915E+09 | 1900.28 | 20-MAR-15:01 | 1.83 |
April | 0.237857E+09 | 1889.27 | 03-APR-15:01 | 2.83 |
May | 18899636.40 | 1100.11 | 02-MAY-15:03 | 10.83 |
June | 121941.41 | 571.32 | 17-JUN-08:04 | 17.28 |
July | 245815.28 | 326.65 | 28-JUL-15:04 | 20.83 |
August | 222921.89 | 672.33 | 15-AUG-08:04 | 14.17 |
September | 8778797.52 | 1519.40 | 22-SEP-08:62 | 2.57 |
October | 0.237361E+09 | 1891.68 | 24-OCT-15:01 | 2.00 |
November | 0.325801E+09 | 1866.08 | 10-NOV-16:01 | 0.83 |
December | 0.672770E+09 | 1893.98 | 26-DEC-16:01 | 9.67 |
Annual Sum or Average | 0.265508E+10 | |||
Minimum of Months | 121941.41 | 326.65 | -1.8 | |
Maximum of Months | 0.672770E+09 | 1924.20 | 20.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622929E+09 | 1904.79 | 06-JAN-16:01 | 2.33 |
February | 0.642198E+09 | 1921.96 | 07-FEB-16:02 | 5.83 |
March | 0.373223E+09 | 1898.56 | 20-MAR-15:01 | 1.83 |
April | 0.262480E+09 | 1893.44 | 03-APR-15:01 | 2.83 |
May | 21156949.24 | 1080.75 | 08-MAY-18:03 | 12.83 |
June | 127557.56 | 525.35 | 17-JUN-08:04 | 17.28 |
July | 258027.50 | 348.82 | 28-JUL-15:04 | 20.83 |
August | 287274.18 | 664.35 | 15-AUG-08:04 | 14.17 |
September | 11627851.58 | 1737.32 | 22-SEP-08:62 | 2.57 |
October | 0.288416E+09 | 1900.34 | 24-OCT-15:01 | 2.00 |
November | 0.494145E+09 | 1914.95 | 30-NOV-16:01 | 2.50 |
December | 0.939289E+09 | 1907.69 | 08-DEC-16:01 | 4.83 |
Annual Sum or Average | 0.365614E+10 | |||
Minimum of Months | 127557.56 | 348.82 | 1.83 | |
Maximum of Months | 0.939289E+09 | 1921.96 | 20.83 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280012E+09 | 862.58 | 06-JAN-04:50 | -8.7 |
February | 0.457326E+09 | 863.90 | 07-FEB-05:00 | -7.0 |
March | 0.308421E+09 | 825.78 | 19-MAR-08:10 | -13.0 |
April | 0.205476E+09 | 792.54 | 03-APR-04:00 | -8.0 |
May | 8500917.21 | 241.75 | 01-MAY-04:00 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 3089820.07 | 242.42 | 22-SEP-05:00 | -1.7 |
October | 0.227427E+09 | 827.85 | 31-OCT-15:40 | -8.0 |
November | 0.253604E+09 | 846.04 | 30-NOV-05:00 | -13.0 |
December | 0.613150E+09 | 1011.14 | 22-DEC-06:00 | -21.0 |
Annual Sum or Average | 0.235701E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.613150E+09 | 1011.14 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650471E+09 | 2319.87 | 30-JAN-09:01 | -2.0 |
February | 0.740049E+09 | 2404.32 | 07-FEB-16:02 | 5.83 |
March | 0.544643E+09 | 2386.48 | 22-MAR-08:61 | 2.67 |
April | 0.430322E+09 | 2364.26 | 03-APR-15:01 | 2.83 |
May | 46772040.67 | 1844.26 | 02-MAY-08:62 | 3.35 |
June | 1013615.92 | 1051.77 | 09-JUN-08:03 | 14.77 |
July | 1019165.67 | 1103.07 | 13-JUL-08:03 | 22.17 |
August | 1550556.86 | 1176.97 | 24-AUG-08:03 | 15.00 |
September | 21212680.96 | 2296.03 | 22-SEP-08:62 | 2.57 |
October | 0.410354E+09 | 2382.32 | 25-OCT-08:61 | 4.50 |
November | 0.543617E+09 | 2363.99 | 10-NOV-16:01 | 0.83 |
December | 0.106426E+10 | 2406.34 | 26-DEC-16:01 | 9.67 |
Annual Sum or Average | 0.445529E+10 | |||
Minimum of Months | 1013615.92 | 1051.77 | -2.0 | |
Maximum of Months | 0.106426E+10 | 2406.34 | 22.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100453E+10 | 2377.81 | 08-JAN-09:01 | 6.17 |
February | 0.982905E+09 | 2399.59 | 07-FEB-16:02 | 5.83 |
March | 0.644344E+09 | 2381.81 | 22-MAR-08:61 | 2.67 |
April | 0.467451E+09 | 2366.98 | 03-APR-15:01 | 2.83 |
May | 51221138.78 | 1821.08 | 02-MAY-08:62 | 3.35 |
June | 918456.68 | 1073.44 | 09-JUN-08:03 | 14.77 |
July | 1000737.67 | 1066.26 | 13-JUL-08:03 | 22.17 |
August | 1606661.71 | 1160.80 | 24-AUG-08:03 | 15.00 |
September | 27453807.67 | 2298.66 | 22-SEP-08:62 | 2.57 |
October | 0.491603E+09 | 2392.88 | 25-OCT-08:61 | 4.50 |
November | 0.777999E+09 | 2366.65 | 10-NOV-16:01 | 0.83 |
December | 0.143368E+10 | 2407.85 | 26-DEC-16:01 | 9.67 |
Annual Sum or Average | 0.588471E+10 | |||
Minimum of Months | 918456.68 | 1066.26 | 0.83 | |
Maximum of Months | 0.143368E+10 | 2407.85 | 22.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123616E+09 | 1097.06 | 31-JAN-09:02 | -1.8 |
February | 0.196688E+09 | 1172.93 | 07-FEB-16:02 | 5.83 |
March | 0.161097E+09 | 1149.48 | 20-MAR-15:01 | 1.83 |
April | 0.127759E+09 | 1134.61 | 03-APR-15:01 | 2.83 |
May | 9316601.84 | 638.76 | 02-MAY-08:62 | 3.35 |
June | 567007.51 | 643.97 | 09-JUN-08:03 | 14.77 |
July | 456582.63 | 399.61 | 24-JUL-08:04 | 25.33 |
August | 424772.81 | 364.64 | 05-AUG-08:04 | 22.33 |
September | 3603577.30 | 999.25 | 22-SEP-08:62 | 2.57 |
October | 0.119285E+09 | 1136.06 | 24-OCT-15:01 | 2.00 |
November | 0.117259E+09 | 1115.45 | 01-NOV-08:62 | -2.0 |
December | 0.266128E+09 | 1063.99 | 09-DEC-09:02 | -2.8 |
Annual Sum or Average | 0.112620E+10 | |||
Minimum of Months | 424772.81 | 364.64 | -2.8 | |
Maximum of Months | 0.266128E+09 | 1172.93 | 25.33 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179643E+10 | 3431.59 | 05-JAN-06:00 | -17.0 |
February | 0.206552E+10 | 3403.70 | 12-FEB-05:40 | -19.3 |
March | 0.127842E+10 | 3117.30 | 05-MAR-06:10 | -11.8 |
April | 0.876124E+09 | 2985.48 | 03-APR-04:00 | -8.0 |
May | 61847370.79 | 1003.63 | 03-MAY-05:00 | 1.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 35077450.33 | 1315.71 | 22-SEP-05:00 | -1.7 |
October | 0.972023E+09 | 3057.23 | 31-OCT-05:00 | -8.0 |
November | 0.136922E+10 | 3283.72 | 30-NOV-05:00 | -13.0 |
December | 0.279822E+10 | 4017.85 | 22-DEC-06:00 | -21.0 |
Annual Sum or Average | 0.112529E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.279822E+10 | 4017.85 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.176689E+11 | 17018.80 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.159534E+11 | 17018.80 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.177302E+11 | 17018.80 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.170699E+11 | 17018.80 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.176995E+11 | 17018.80 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.171481E+11 | 17018.80 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.176213E+11 | 17018.80 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.177302E+11 | 17018.80 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.170699E+11 | 17018.80 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.176689E+11 | 17018.80 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.171345E+11 | 17018.80 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.176213E+11 | 17018.80 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.208116E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.159534E+11 | 17018.80 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.177302E+11 | 17018.80 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.958205E+09 | 922.95 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.865172E+09 | 922.95 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.961528E+09 | 922.95 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.925717E+09 | 922.95 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.959866E+09 | 922.95 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.929963E+09 | 922.95 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.955621E+09 | 922.95 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.961528E+09 | 922.95 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.925717E+09 | 922.95 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.958205E+09 | 922.95 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.929224E+09 | 922.95 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.955621E+09 | 922.95 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.112864E+11 | 0.101859E+11 | ||||
Minimum of Months | 0.865172E+09 | 922.95 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.961528E+09 | 922.95 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.110961E+10 | 1068.78 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.100187E+10 | 1068.78 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.111345E+10 | 1068.78 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.107198E+10 | 1068.78 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.111153E+10 | 1068.78 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.107690E+10 | 1068.78 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.110661E+10 | 1068.78 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.111345E+10 | 1068.78 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.107198E+10 | 1068.78 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.110961E+10 | 1068.78 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.107605E+10 | 1068.78 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.110661E+10 | 1068.78 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.130697E+11 | 0.117953E+11 | ||||
Minimum of Months | 0.100187E+10 | 1068.78 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.111345E+10 | 1068.78 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.234644E+10 | 2260.10 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.211862E+10 | 2260.10 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.235457E+10 | 2260.10 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.226688E+10 | 2260.10 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.235050E+10 | 2260.10 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.227728E+10 | 2260.10 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.234011E+10 | 2260.10 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.235457E+10 | 2260.10 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.226688E+10 | 2260.10 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.234644E+10 | 2260.10 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.227547E+10 | 2260.10 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.234011E+10 | 2260.10 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.276379E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.211862E+10 | 2260.10 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.235457E+10 | 2260.10 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.375444E+09 | 361.63 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.338992E+09 | 361.63 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.376746E+09 | 361.63 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.362715E+09 | 361.63 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.376095E+09 | 361.63 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.364378E+09 | 361.63 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.374431E+09 | 361.63 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.376746E+09 | 361.63 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.362715E+09 | 361.63 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.375444E+09 | 361.63 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.364089E+09 | 361.63 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.374431E+09 | 361.63 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.442222E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.338992E+09 | 361.63 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.376746E+09 | 361.63 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.445960E+09 | 429.55 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.402661E+09 | 429.55 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.447506E+09 | 429.55 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.430840E+09 | 429.55 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.446733E+09 | 429.55 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.432815E+09 | 429.55 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.444757E+09 | 429.55 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.447506E+09 | 429.55 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.430840E+09 | 429.55 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.445960E+09 | 429.55 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.432472E+09 | 429.55 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.444757E+09 | 429.55 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.525281E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.402661E+09 | 429.55 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.447506E+09 | 429.55 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.233839E+10 | 2252.35 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.211136E+10 | 2252.35 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.234650E+10 | 2252.35 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.225911E+10 | 2252.35 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.234245E+10 | 2252.35 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.226947E+10 | 2252.35 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.233209E+10 | 2252.35 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.234650E+10 | 2252.35 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.225911E+10 | 2252.35 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.233839E+10 | 2252.35 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.226767E+10 | 2252.35 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.233209E+10 | 2252.35 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.275431E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.211136E+10 | 2252.35 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.234650E+10 | 2252.35 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.137054E+11 | 13201.13 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.123747E+11 | 13201.13 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.137529E+11 | 13201.13 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.132407E+11 | 13201.13 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.137292E+11 | 13201.13 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.133015E+11 | 13201.13 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.136685E+11 | 13201.13 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.137529E+11 | 13201.13 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.132407E+11 | 13201.13 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.137054E+11 | 13201.13 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.132909E+11 | 13201.13 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.136685E+11 | 13201.13 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.161431E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.123747E+11 | 13201.13 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.137529E+11 | 13201.13 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.320927E+09 | 290.37 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.289828E+09 | 290.37 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.318376E+09 | 290.37 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.310986E+09 | 290.37 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.319652E+09 | 290.37 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.308435E+09 | 290.37 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.322202E+09 | 290.37 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.318376E+09 | 290.37 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.310986E+09 | 290.37 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.320927E+09 | 290.37 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.309711E+09 | 290.37 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.322202E+09 | 290.37 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.377261E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.289828E+09 | 290.37 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.322202E+09 | 290.37 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.321015E+09 | 290.45 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.289908E+09 | 290.45 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.318463E+09 | 290.45 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.311071E+09 | 290.45 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.319739E+09 | 290.45 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.308520E+09 | 290.45 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.322290E+09 | 290.45 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.318463E+09 | 290.45 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.311071E+09 | 290.45 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.321015E+09 | 290.45 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.309795E+09 | 290.45 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.322290E+09 | 290.45 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.377364E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.289908E+09 | 290.45 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.322290E+09 | 290.45 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.185439E+10 | 1786.16 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.167435E+10 | 1786.16 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.186082E+10 | 1786.16 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.179152E+10 | 1786.16 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.185761E+10 | 1786.16 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.179973E+10 | 1786.16 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.184939E+10 | 1786.16 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.186082E+10 | 1786.16 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.179152E+10 | 1786.16 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.185439E+10 | 1786.16 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.179831E+10 | 1786.16 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.184939E+10 | 1786.16 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.218422E+11 | ||||
Minimum of Months | 0.167435E+10 | 1786.16 | 0.00 | 0.00 | |
Maximum of Months | 0.186082E+10 | 1786.16 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510655E+09 | 462.03 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.461171E+09 | 462.03 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.506596E+09 | 462.03 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.494837E+09 | 462.03 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.508626E+09 | 462.03 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.490778E+09 | 462.03 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.512684E+09 | 462.03 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.506596E+09 | 462.03 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.494837E+09 | 462.03 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.510655E+09 | 462.03 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.492808E+09 | 462.03 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.512684E+09 | 462.03 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.600293E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.461171E+09 | 462.03 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.512684E+09 | 462.03 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.510595E+09 | 461.98 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.461117E+09 | 461.98 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.506537E+09 | 461.98 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.494779E+09 | 461.98 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.508566E+09 | 461.98 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.490721E+09 | 461.98 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.512624E+09 | 461.98 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.506537E+09 | 461.98 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.494779E+09 | 461.98 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.510595E+09 | 461.98 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.492750E+09 | 461.98 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.512624E+09 | 461.98 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.600222E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.461117E+09 | 461.98 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.512624E+09 | 461.98 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.321015E+09 | 290.45 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.289908E+09 | 290.45 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.318463E+09 | 290.45 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.311071E+09 | 290.45 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.319739E+09 | 290.45 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.308520E+09 | 290.45 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.322290E+09 | 290.45 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.318463E+09 | 290.45 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.311071E+09 | 290.45 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.321015E+09 | 290.45 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.309795E+09 | 290.45 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.322290E+09 | 290.45 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.377364E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.289908E+09 | 290.45 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.322290E+09 | 290.45 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.410642E+10 | 3955.32 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.370772E+10 | 3955.32 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.412066E+10 | 3955.32 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.396719E+10 | 3955.32 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.411354E+10 | 3955.32 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.398539E+10 | 3955.32 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.409534E+10 | 3955.32 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.412066E+10 | 3955.32 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.396719E+10 | 3955.32 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.410642E+10 | 3955.32 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.398222E+10 | 3955.32 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.409534E+10 | 3955.32 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.483681E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.370772E+10 | 3955.32 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.412066E+10 | 3955.32 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.410642E+10 | 3955.32 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.370772E+10 | 3955.32 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.412066E+10 | 3955.32 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.396719E+10 | 3955.32 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.411354E+10 | 3955.32 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.398539E+10 | 3955.32 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.409534E+10 | 3955.32 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.412066E+10 | 3955.32 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.396719E+10 | 3955.32 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.410642E+10 | 3955.32 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.398222E+10 | 3955.32 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.409534E+10 | 3955.32 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.483681E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.370772E+10 | 3955.32 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.412066E+10 | 3955.32 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.118068E+10 | 1137.23 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.106604E+10 | 1137.23 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.118477E+10 | 1137.23 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.114064E+10 | 1137.23 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.118272E+10 | 1137.23 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.114588E+10 | 1137.23 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.117749E+10 | 1137.23 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.118477E+10 | 1137.23 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.114064E+10 | 1137.23 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.118068E+10 | 1137.23 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.114497E+10 | 1137.23 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.117749E+10 | 1137.23 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.139068E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.106604E+10 | 1137.23 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.118477E+10 | 1137.23 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.196259E+10 | 1890.37 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.177204E+10 | 1890.37 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196939E+10 | 1890.37 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189604E+10 | 1890.37 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196599E+10 | 1890.37 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190474E+10 | 1890.37 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195729E+10 | 1890.37 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196939E+10 | 1890.37 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189604E+10 | 1890.37 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.196259E+10 | 1890.37 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.190323E+10 | 1890.37 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195729E+10 | 1890.37 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.231166E+11 | ||||
Minimum of Months | 0.177204E+10 | 1890.37 | 0.00 | 0.00 | |
Maximum of Months | 0.196939E+10 | 1890.37 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.176689E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.159534E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.170699E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.176995E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.171481E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.176213E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.170699E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.176689E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.171345E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.176213E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.208116E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.159534E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.177302E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.958205E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112724E+10 |
February | 0.179968E+10 | 0.865172E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107600E+10 |
March | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 478439.25 | 0.887541E+09 |
April | 0.192973E+10 | 0.925717E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171010.29 | 0.781625E+09 |
May | 0.199475E+10 | 0.959866E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19793410.80 | 0.407002E+09 |
June | 0.193394E+10 | 0.929963E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155211E+09 | 0.103966E+09 |
July | 0.199054E+10 | 0.955621E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166652E+09 | 84779085.09 |
August | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137451E+09 | 0.105800E+09 |
September | 0.192973E+10 | 0.925717E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75305396.16 | 0.211454E+09 |
October | 0.199054E+10 | 0.958205E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087881.63 | 0.772047E+09 |
November | 0.192552E+10 | 0.929224E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970483E+09 |
December | 0.199054E+10 | 0.955621E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124463E+10 |
Annual Sum or Average | 0.234734E+11 | 0.112864E+11 | 0.101859E+11 | 0.557151E+09 | 0.777257E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.865172E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84779085.09 |
Maximum of Months | 0.199896E+10 | 0.961528E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166652E+09 | 0.124463E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.110961E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232656E+09 |
February | 0.208403E+10 | 0.100187E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222806E+09 |
March | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 242673.17 | 0.185362E+09 |
April | 0.223463E+10 | 0.107198E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35928.69 | 0.164554E+09 |
May | 0.230993E+10 | 0.111153E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4154013.98 | 86008397.73 |
June | 0.223950E+10 | 0.107690E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32526869.22 | 21897746.23 |
July | 0.230505E+10 | 0.110661E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34950548.53 | 17850683.60 |
August | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28949666.12 | 22262054.49 |
September | 0.223463E+10 | 0.107198E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16760338.97 | 44577025.80 |
October | 0.230505E+10 | 0.110961E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 889485.28 | 0.160281E+09 |
November | 0.222975E+10 | 0.107605E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46766.80 | 0.200003E+09 |
December | 0.230505E+10 | 0.110661E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23428.13 | 0.258962E+09 |
Annual Sum or Average | 0.271823E+11 | 0.130697E+11 | 0.117953E+11 | 0.118580E+09 | 0.161722E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.100187E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17850683.60 |
Maximum of Months | 0.231480E+10 | 0.111345E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34950548.53 | 0.258962E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.445960E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 46235.29 | 0.730594E+09 |
February | 0.139600E+10 | 0.402661E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698997E+09 |
March | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 1163197.89 | 0.584285E+09 |
April | 0.149688E+10 | 0.430840E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 454207.92 | 0.518958E+09 |
May | 0.154732E+10 | 0.446733E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 15836037.81 | 0.273391E+09 |
June | 0.150015E+10 | 0.432815E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.105208E+09 | 65701122.51 |
July | 0.154405E+10 | 0.444757E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.113947E+09 | 52018736.15 |
August | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 94539132.98 | 65875364.29 |
September | 0.149688E+10 | 0.430840E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 57453562.23 | 0.140016E+09 |
October | 0.154405E+10 | 0.445960E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 3702173.19 | 0.505369E+09 |
November | 0.149361E+10 | 0.432472E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 440054.23 | 0.629254E+09 |
December | 0.154405E+10 | 0.444757E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 237998.71 | 0.811676E+09 |
Annual Sum or Average | 0.182082E+11 | 0.525281E+10 | 0.679373E+11 | 0.590211E+12 | 0.393028E+09 | 0.507614E+10 | |||
Minimum of Months | 0.139600E+10 | 0.402661E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52018736.15 |
Maximum of Months | 0.155059E+10 | 0.447506E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.113947E+09 | 0.811676E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.233839E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283525E+10 |
February | 0.236489E+11 | 0.211136E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270844E+10 |
March | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2106449.62 | 0.223772E+10 |
April | 0.253579E+11 | 0.225911E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 431455.56 | 0.197469E+10 |
May | 0.262123E+11 | 0.234245E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49935987.84 | 0.102969E+10 |
June | 0.254132E+11 | 0.226947E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391574E+09 | 0.262678E+09 |
July | 0.261570E+11 | 0.233209E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420474E+09 | 0.214224E+09 |
August | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348416E+09 | 0.267242E+09 |
September | 0.253579E+11 | 0.225911E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199409E+09 | 0.535470E+09 |
October | 0.261570E+11 | 0.233839E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8077088.63 | 0.194467E+10 |
November | 0.253025E+11 | 0.226767E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4875.27 | 0.244092E+10 |
December | 0.261570E+11 | 0.233209E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651.82 | 0.314124E+10 |
Annual Sum or Average | 0.308456E+12 | 0.275431E+11 | 0.143409E+11 | 0.142043E+10 | 0.195922E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.211136E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214224E+09 |
Maximum of Months | 0.262677E+11 | 0.234650E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420474E+09 | 0.314124E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.137054E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559667E+10 |
February | 0.702046E+11 | 0.123747E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535495E+10 |
March | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5820479.89 | 0.446291E+10 |
April | 0.752779E+11 | 0.132407E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 860024.08 | 0.396268E+10 |
May | 0.778146E+11 | 0.137292E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99607064.04 | 0.208205E+10 |
June | 0.754422E+11 | 0.133015E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779806E+09 | 0.528615E+09 |
July | 0.776503E+11 | 0.136685E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837741E+09 | 0.430413E+09 |
August | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693975E+09 | 0.536194E+09 |
September | 0.752779E+11 | 0.132407E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401830E+09 | 0.108080E+10 |
October | 0.776503E+11 | 0.137054E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21330890.18 | 0.386603E+10 |
November | 0.751137E+11 | 0.132909E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1120926.43 | 0.481793E+10 |
December | 0.776503E+11 | 0.136685E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 561501.91 | 0.622502E+10 |
Annual Sum or Average | 0.915690E+12 | 0.161431E+12 | 0.149002E+12 | 0.284265E+10 | 0.389443E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.123747E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430413E+09 |
Maximum of Months | 0.779788E+11 | 0.137529E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837741E+09 | 0.622502E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331092E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315598E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98296.42 | 0.263091E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233720E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3332108.94 | 0.126715E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37327350.59 | 32914182.75 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40021145.29 | 27013511.44 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32650959.24 | 34104326.71 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17192983.42 | 66043795.79 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 594015.73 | 0.228934E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285157E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365350E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 0.131217E+09 | 0.230973E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27013511.44 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40021145.29 | 0.365350E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324525E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310523E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104389.31 | 0.260280E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232305E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3374142.90 | 0.126354E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37333808.56 | 32905523.19 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40041221.08 | 27000002.84 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32746394.17 | 33980494.49 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17410408.69 | 65423922.76 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 657035.13 | 0.226134E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280113E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.29 | 0.360248E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 0.131668E+09 | 0.227979E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27000002.84 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40041221.08 | 0.360248E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.320927E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98027953.87 |
February | 0.00 | 0.289828E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91128280.53 |
March | 0.00 | 0.318376E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1644.66 | 76889335.57 |
April | 0.00 | 0.310986E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69832728.48 |
May | 0.00 | 0.319652E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592166.15 | 42124971.24 |
June | 0.00 | 0.308435E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8371765.05 | 13786017.99 |
July | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8928207.68 | 12163838.34 |
August | 0.00 | 0.318376E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7244302.25 | 14580097.24 |
September | 0.00 | 0.310986E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3712467.79 | 24111799.58 |
October | 0.00 | 0.320927E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98934.64 | 69511985.26 |
November | 0.00 | 0.309711E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84688140.67 |
December | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105616E+09 |
Annual Sum or Average | 0.00 | 0.377261E+10 | 0.300992E+10 | 28949488.22 | 0.702461E+09 | ||||
Minimum of Months | 0.00 | 0.289828E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12163838.34 |
Maximum of Months | 0.00 | 0.322202E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8928207.68 | 0.105616E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91181727.93 |
February | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87172074.43 |
March | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41246.21 | 73209655.66 |
April | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65483925.49 |
May | 0.303504E+09 | 0.319739E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1012357.28 | 35223921.11 |
June | 0.293842E+09 | 0.308520E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10576756.55 | 9132771.47 |
July | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11312482.24 | 7502917.21 |
August | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9317903.49 | 9426858.03 |
September | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5046832.19 | 18209349.72 |
October | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 214093.06 | 63510659.22 |
November | 0.293661E+09 | 0.309795E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78645440.80 |
December | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.87 | 0.101154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.377364E+10 | 0.301074E+10 | 37523754.90 | 0.639853E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7502917.21 |
Maximum of Months | 0.303685E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11312482.24 | 0.101154E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331676E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316291E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98335.13 | 0.264282E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235098E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264127.12 | 0.127881E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37157846.86 | 33386849.16 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39779388.48 | 27315231.85 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32526359.73 | 34692016.41 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17152463.92 | 66642474.41 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592912.28 | 0.229608E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285347E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365678E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 0.130571E+09 | 0.231790E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27315231.85 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39779388.48 | 0.365678E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324374E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311088E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98530.45 | 0.261931E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234079E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3269055.25 | 0.127621E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37158142.76 | 33378786.70 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39782506.12 | 27304640.42 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32544685.23 | 34659052.40 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17202496.69 | 66355822.42 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 599477.70 | 0.227328E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279661E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3532.47 | 0.359920E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 0.130658E+09 | 0.228770E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27304640.42 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39782506.12 | 0.359920E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331200E+09 |
February | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315933E+09 |
March | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92891.88 | 0.263496E+09 |
April | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234236E+09 |
May | 0.303504E+09 | 0.508626E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3191996.84 | 0.127971E+09 |
June | 0.293842E+09 | 0.490778E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36798121.10 | 33505261.04 |
July | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39439846.55 | 27556288.71 |
August | 0.303685E+09 | 0.506596E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32166204.85 | 34729085.13 |
September | 0.293479E+09 | 0.494837E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16891288.19 | 66681872.28 |
October | 0.303322E+09 | 0.510655E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 573657.12 | 0.229545E+09 |
November | 0.293661E+09 | 0.492808E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285501E+09 |
December | 0.303141E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365238E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600293E+10 | 0.307301E+10 | 0.129154E+09 | 0.231559E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461171E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27556288.71 |
Maximum of Months | 0.303685E+09 | 0.512684E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39439846.55 | 0.365238E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324416E+09 |
February | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310938E+09 |
March | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93067.10 | 0.260903E+09 |
April | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233040E+09 |
May | 0.303504E+09 | 0.508566E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3202847.96 | 0.127733E+09 |
June | 0.293842E+09 | 0.490721E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36793150.06 | 33507106.40 |
July | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39441359.77 | 27553564.88 |
August | 0.303685E+09 | 0.506537E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32200715.26 | 34663739.48 |
September | 0.293479E+09 | 0.494779E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16992218.64 | 66251608.11 |
October | 0.303322E+09 | 0.510595E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 594218.46 | 0.227151E+09 |
November | 0.293661E+09 | 0.492750E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280453E+09 |
December | 0.303141E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360111E+09 |
Annual Sum or Average | 0.357224E+10 | 0.600222E+10 | 0.307265E+10 | 0.129318E+09 | 0.228672E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.461117E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27553564.88 |
Maximum of Months | 0.303685E+09 | 0.512624E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39441359.77 | 0.360111E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171435E+09 |
February | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163311E+09 |
March | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46860.29 | 0.135965E+09 |
April | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120725E+09 |
May | 0.303504E+09 | 0.319739E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1634890.13 | 65554851.65 |
June | 0.293842E+09 | 0.308520E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18851751.16 | 17105176.54 |
July | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20186003.85 | 14077753.04 |
August | 0.303685E+09 | 0.318463E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16452482.49 | 17770603.79 |
September | 0.293479E+09 | 0.311071E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8623073.49 | 34274342.10 |
October | 0.303322E+09 | 0.321015E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 290428.92 | 0.118134E+09 |
November | 0.293661E+09 | 0.309795E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147768E+09 |
December | 0.303141E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189712E+09 |
Annual Sum or Average | 0.357224E+10 | 0.377364E+10 | 0.301074E+10 | 66085490.34 | 0.119583E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.289908E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14077753.04 |
Maximum of Months | 0.303685E+09 | 0.322290E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20186003.85 | 0.189712E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810485E+09 |
February | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775408E+09 |
March | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 772196.68 | 0.651555E+09 |
April | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103928.80 | 0.581314E+09 |
May | 0.460320E+11 | 0.411354E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13687276.59 | 0.313119E+09 |
June | 0.446286E+11 | 0.398539E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108360E+09 | 82430455.36 |
July | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116569E+09 | 66976084.28 |
August | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96364601.44 | 82739083.67 |
September | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55879775.99 | 0.163277E+09 |
October | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2914372.04 | 0.565597E+09 |
November | 0.444343E+11 | 0.398222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138739.19 | 0.699413E+09 |
December | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64807.58 | 0.899690E+09 |
Annual Sum or Average | 0.541686E+12 | 0.483681E+11 | 0.175857E+12 | 0.394854E+09 | 0.569200E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66976084.28 |
Maximum of Months | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116569E+09 | 0.899690E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812308E+09 |
February | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777126E+09 |
March | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 772522.32 | 0.653667E+09 |
April | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104048.62 | 0.583443E+09 |
May | 0.460320E+11 | 0.411354E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13678853.52 | 0.314698E+09 |
June | 0.446286E+11 | 0.398539E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108226E+09 | 82644501.85 |
July | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116441E+09 | 67147034.86 |
August | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96233018.12 | 82895254.25 |
September | 0.445315E+11 | 0.396719E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55844241.19 | 0.163886E+09 |
October | 0.459349E+11 | 0.410642E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2915132.35 | 0.567458E+09 |
November | 0.444343E+11 | 0.398222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138789.99 | 0.701309E+09 |
December | 0.459349E+11 | 0.409534E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64736.53 | 0.901409E+09 |
Annual Sum or Average | 0.541686E+12 | 0.483681E+11 | 0.175857E+12 | 0.394417E+09 | 0.570799E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.370772E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67147034.86 |
Maximum of Months | 0.461292E+11 | 0.412066E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116441E+09 | 0.901409E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.118068E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778105E+09 |
February | 0.369574E+10 | 0.106604E+10 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743199E+09 |
March | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 228734.32 | 0.631412E+09 |
April | 0.396281E+10 | 0.114064E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6837.21 | 0.565529E+09 |
May | 0.409635E+10 | 0.118272E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7365861.56 | 0.309789E+09 |
June | 0.397146E+10 | 0.114588E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 76692148.78 | 79561691.04 |
July | 0.408770E+10 | 0.117749E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 83201413.91 | 65615065.49 |
August | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 67318060.09 | 83396539.63 |
September | 0.396281E+10 | 0.114064E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 36752892.98 | 0.160193E+09 |
October | 0.408770E+10 | 0.118068E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1383569.75 | 0.549488E+09 |
November | 0.395417E+10 | 0.114497E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9733.71 | 0.674816E+09 |
December | 0.408770E+10 | 0.117749E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3615.17 | 0.855840E+09 |
Annual Sum or Average | 0.482041E+11 | 0.139068E+11 | 0.398993E+12 | 0.359593E+12 | 0.272963E+09 | 0.549694E+10 | |||
Minimum of Months | 0.369574E+10 | 0.106604E+10 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65615065.49 |
Maximum of Months | 0.410499E+10 | 0.118477E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 83201413.91 | 0.855840E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.234644E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510787E+09 |
February | 0.00 | 0.211862E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489314E+09 |
March | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 534564.25 | 0.406480E+09 |
April | 0.00 | 0.226688E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79082.17 | 0.361049E+09 |
May | 0.00 | 0.235050E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9146373.13 | 0.188263E+09 |
June | 0.00 | 0.227728E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71717341.27 | 48045250.19 |
July | 0.00 | 0.234011E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77006361.85 | 39174632.20 |
August | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63816491.69 | 48880144.14 |
September | 0.00 | 0.226688E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36912582.28 | 97479237.50 |
October | 0.00 | 0.234644E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1958689.53 | 0.351061E+09 |
November | 0.00 | 0.227547E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102904.58 | 0.438789E+09 |
December | 0.00 | 0.234011E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51620.52 | 0.568705E+09 |
Annual Sum or Average | 0.276379E+11 | 0.124715E+11 | 0.261326E+09 | 0.354803E+10 | |||||
Minimum of Months | 0.00 | 0.211862E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39174632.20 |
Maximum of Months | 0.00 | 0.235457E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77006361.85 | 0.568705E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.375444E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355031E+09 |
February | 0.00 | 0.338992E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340153E+09 |
March | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 371649.41 | 0.282512E+09 |
April | 0.00 | 0.362715E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54978.18 | 0.250943E+09 |
May | 0.00 | 0.376095E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6359581.21 | 0.130745E+09 |
June | 0.00 | 0.364378E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49871169.31 | 33392752.43 |
July | 0.00 | 0.374431E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53544496.30 | 27229066.14 |
August | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44371594.23 | 33980752.79 |
September | 0.00 | 0.362715E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25665118.23 | 67734237.10 |
October | 0.00 | 0.375444E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1361885.86 | 0.243923E+09 |
November | 0.00 | 0.364089E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71590.29 | 0.304987E+09 |
December | 0.00 | 0.374431E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35891.53 | 0.394611E+09 |
Annual Sum or Average | 0.442222E+10 | 0.359769E+10 | 0.181708E+09 | 0.246524E+10 | |||||
Minimum of Months | 0.00 | 0.338992E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27229066.14 |
Maximum of Months | 0.00 | 0.376746E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53544496.30 | 0.394611E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.185439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393787E+09 |
February | 0.00 | 0.167435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377101E+09 |
March | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394456.75 | 0.313433E+09 |
April | 0.00 | 0.179152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57031.60 | 0.278449E+09 |
May | 0.00 | 0.185761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6932947.12 | 0.145362E+09 |
June | 0.00 | 0.179973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54751680.04 | 37310717.58 |
July | 0.00 | 0.184939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58810352.30 | 30495269.67 |
August | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48718667.55 | 38016381.50 |
September | 0.00 | 0.179152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28085751.45 | 75437062.70 |
October | 0.00 | 0.185439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1451106.34 | 0.270728E+09 |
November | 0.00 | 0.179831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65064.45 | 0.338370E+09 |
December | 0.00 | 0.184939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36576.87 | 0.437650E+09 |
Annual Sum or Average | 0.218422E+11 | 0.199304E+09 | 0.273614E+10 | ||||||
Minimum of Months | 0.00 | 0.167435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30495269.67 |
Maximum of Months | 0.00 | 0.186082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58810352.30 | 0.437650E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.196259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698599E+09 |
February | 0.00 | 0.177204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669373E+09 |
March | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631845.33 | 0.556847E+09 |
April | 0.00 | 0.189604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91513.12 | 0.494800E+09 |
May | 0.00 | 0.196599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12017455.80 | 0.258999E+09 |
June | 0.00 | 0.190474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95737774.52 | 66940607.90 |
July | 0.00 | 0.195729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102924E+09 | 54882280.68 |
August | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84873749.10 | 68320568.74 |
September | 0.00 | 0.189604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48813214.97 | 0.134737E+09 |
October | 0.00 | 0.196259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2467979.73 | 0.481264E+09 |
November | 0.00 | 0.190323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113317.14 | 0.600856E+09 |
December | 0.00 | 0.195729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57069.68 | 0.775034E+09 |
Annual Sum or Average | 0.231166E+11 | 0.347728E+09 | 0.486065E+10 | ||||||
Minimum of Months | 0.00 | 0.177204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54882280.68 |
Maximum of Months | 0.00 | 0.196939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102924E+09 | 0.775034E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 17018.80 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 17018.80 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 17018.80 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 17018.80 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 17018.80 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 17018.80 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 17018.80 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 17018.80 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 17018.80 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 17018.80 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 17018.80 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 17018.80 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 922.95 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 866.30 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 922.95 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 897.90 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 922.95 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.69 | 14-MAR-15:00 | 784.82 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 922.95 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 | 19-APR-13:10 | 614.11 | 17-APR-03:00 |
May | 1169.53 | 01-MAY-00:10 | 922.95 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.15 | 17-MAY-13:10 | 451.89 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 922.95 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.94 | 26-JUN-15:00 | 289.98 | 09-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 922.95 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.13 | 16-JUL-13:00 | 238.98 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 922.95 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.08 | 16-AUG-16:00 | 198.85 | 12-AUG-24:00 |
September | 1169.53 | 01-SEP-00:10 | 922.95 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.17 | 10-SEP-16:00 | 470.88 | 22-SEP-06:00 |
October | 1169.53 | 02-OCT-00:10 | 922.95 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.44 | 10-OCT-16:50 | 659.12 | 30-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 922.95 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 773.52 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 922.95 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 955.10 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 922.95 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.85 | |||||
Maximum of Months | 1169.53 | 922.95 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 332.94 | 955.10 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1068.78 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 181.82 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 1068.78 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 189.86 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 1068.78 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 | 14-MAR-13:00 | 165.79 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 1068.78 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 19-APR-13:10 | 128.89 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1068.78 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 17-MAY-13:10 | 94.83 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 1068.78 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 | 26-JUN-15:00 | 60.86 | 09-JUN-04:50 |
July | 1354.32 | 01-JUL-00:10 | 1068.78 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.52 | 16-JUL-13:00 | 50.14 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 1068.78 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.19 | 16-AUG-14:00 | 42.00 | 12-AUG-23:10 |
September | 1354.32 | 01-SEP-00:10 | 1068.78 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.45 | 10-SEP-13:00 | 98.81 | 22-SEP-05:40 |
October | 1354.32 | 02-OCT-00:10 | 1068.78 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 11-OCT-14:00 | 138.31 | 30-OCT-06:20 |
November | 1354.32 | 01-NOV-00:10 | 1068.78 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 07-NOV-14:10 | 162.30 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 1068.78 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 01-DEC-14:00 | 205.44 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 1068.78 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | |||||
Maximum of Months | 1354.32 | 1068.78 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 | 205.44 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 429.55 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 8.31 | 20-JAN-14:00 | 587.09 | 05-JAN-19:05 |
February | 907.20 | 01-FEB-00:10 | 429.55 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 583.74 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 429.55 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 44.74 | 14-MAR-13:00 | 509.79 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 429.55 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 21.42 | 19-APR-14:00 | 396.23 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 429.55 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 104.75 | 17-MAY-13:00 | 291.52 | 03-MAY-02:00 |
June | 907.20 | 01-JUN-00:10 | 429.55 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 222.49 | 26-JUN-15:00 | 187.07 | 09-JUN-04:30 |
July | 907.20 | 01-JUL-00:10 | 429.55 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 200.73 | 16-JUL-13:00 | 154.22 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 429.55 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 195.96 | 16-AUG-14:00 | 133.97 | 12-AUG-22:00 |
September | 907.20 | 01-SEP-00:10 | 429.55 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 152.52 | 10-SEP-14:00 | 327.55 | 21-SEP-20:00 |
October | 907.20 | 02-OCT-00:10 | 429.55 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 80.58 | 11-OCT-14:00 | 442.26 | 31-OCT-20:00 |
November | 907.20 | 01-NOV-00:10 | 429.55 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 21.12 | 06-NOV-14:00 | 546.28 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 429.55 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 21.77 | 01-DEC-14:00 | 648.18 | 21-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 | ||||||
Maximum of Months | 907.20 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 222.49 | 648.18 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2252.35 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2186.81 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 2252.35 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2283.54 | 12-FEB-05:00 |
March | 15368.40 | 01-MAR-00:10 | 2252.35 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.71 | 14-MAR-13:00 | 1993.73 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2252.35 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 19-APR-13:50 | 1550.17 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 2252.35 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.52 | 17-MAY-13:10 | 1140.71 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 2252.35 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 840.14 | 26-JUN-15:00 | 732.01 | 09-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 2252.35 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.69 | 16-JUL-13:00 | 602.92 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2252.35 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.97 | 16-AUG-14:00 | 512.29 | 12-AUG-23:10 |
September | 15368.40 | 01-SEP-00:10 | 2252.35 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.79 | 10-SEP-13:40 | 1188.46 | 22-SEP-05:00 |
October | 15368.40 | 02-OCT-00:10 | 2252.35 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.30 | 11-OCT-14:00 | 1663.77 | 30-OCT-06:10 |
November | 15368.40 | 01-NOV-00:10 | 2252.35 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 07-NOV-15:00 | 1951.69 | 29-NOV-21:00 |
December | 15368.40 | 01-DEC-00:10 | 2252.35 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 02-DEC-15:00 | 2470.70 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 2252.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.29 | |||||
Maximum of Months | 15368.40 | 2252.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 840.14 | 2470.70 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 13201.13 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4360.16 | 05-JAN-19:00 |
February | 45622.98 | 01-FEB-00:10 | 13201.13 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4553.54 | 12-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 13201.13 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.24 | 14-MAR-13:00 | 3976.32 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 13201.13 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.16 | 19-APR-13:10 | 3091.11 | 17-APR-03:00 |
May | 45622.98 | 01-MAY-00:10 | 13201.13 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 750.77 | 17-MAY-13:10 | 2274.16 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 13201.13 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.50 | 26-JUN-15:00 | 1494.30 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 13201.13 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.30 | 16-JUL-13:00 | 1202.66 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 13201.13 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.58 | 16-AUG-14:00 | 1040.76 | 12-AUG-23:50 |
September | 45622.98 | 01-SEP-00:10 | 13201.13 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.93 | 09-SEP-13:00 | 2369.86 | 22-SEP-06:00 |
October | 45622.98 | 02-OCT-00:10 | 13201.13 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 563.73 | 11-OCT-14:00 | 3317.27 | 30-OCT-07:30 |
November | 45622.98 | 01-NOV-00:10 | 13201.13 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 07-NOV-15:00 | 3892.51 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 13201.13 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 | 01-DEC-14:00 | 4927.10 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 13201.13 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.76 | |||||
Maximum of Months | 45622.98 | 13201.13 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.50 | 4927.10 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.27 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 266.95 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 13-MAR-15:09 | 233.22 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.49 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 31-MAY-15:09 | 133.76 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 26-JUN-15:10 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 16-JUL-15:06 | 71.14 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 16-AUG-16:00 | 59.34 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 10-SEP-16:00 | 139.35 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 11-OCT-15:10 | 194.70 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.33 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 288.78 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 288.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.25 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 266.93 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 13-MAR-15:10 | 233.20 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.48 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 31-MAY-15:07 | 133.75 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.56 | 26-JUN-15:10 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 16-JUL-15:06 | 71.13 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.88 | 16-AUG-16:00 | 59.34 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 10-SEP-16:00 | 139.33 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 11-OCT-15:07 | 194.68 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.31 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 01-DEC-13:20 | 288.75 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.56 | 288.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 290.37 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.39 | 05-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 290.37 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 70.46 | 12-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 290.37 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 14-MAR-13:00 | 61.14 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 290.37 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.78 | 17-APR-03:00 |
May | 0.00 | 01-MAY-00:10 | 290.37 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 17-MAY-13:00 | 38.49 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 290.37 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 26-JUN-15:00 | 27.29 | 09-JUN-04:30 |
July | 0.00 | 01-JUL-00:10 | 290.37 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.48 | 16-JUL-13:00 | 23.29 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 290.37 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 16-AUG-16:00 | 20.18 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 290.37 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.16 | 10-SEP-13:00 | 40.58 | 21-SEP-22:00 |
October | 0.00 | 01-OCT-00:10 | 290.37 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 11-OCT-14:00 | 51.79 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 290.37 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 60.64 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 290.37 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.52 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 290.37 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | |||||
Maximum of Months | 0.00 | 290.37 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 76.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 290.45 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 70.67 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 290.45 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 74.50 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 290.45 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 13-MAR-16:00 | 65.09 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 290.45 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 50.65 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 290.45 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 31-MAY-15:09 | 37.33 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 290.45 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 26-JUN-15:07 | 24.04 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 290.45 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 16-JUL-15:07 | 19.85 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 290.45 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 16-AUG-16:00 | 16.56 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 290.45 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 10-SEP-16:00 | 38.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 290.45 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 11-OCT-15:10 | 54.34 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 290.45 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 63.72 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 290.45 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 01-DEC-14:00 | 80.59 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | |||||
Maximum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 80.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.27 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 266.95 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 13-MAR-16:00 | 233.22 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.49 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 31-MAY-15:10 | 133.76 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 26-JUN-15:06 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 16-JUL-15:06 | 71.14 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 16-AUG-16:00 | 63.25 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 | 10-SEP-16:00 | 139.35 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 11-OCT-15:06 | 194.70 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.33 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 288.78 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 288.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.25 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 266.93 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 13-MAR-16:00 | 233.20 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.48 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 31-MAY-15:10 | 133.75 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.56 | 26-JUN-15:06 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 16-JUL-15:06 | 71.13 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.88 | 16-AUG-16:00 | 63.24 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 10-SEP-16:00 | 139.34 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 11-OCT-15:10 | 194.68 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.31 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 01-DEC-14:00 | 288.74 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.56 | 288.74 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 462.03 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.72 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 462.03 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 267.41 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 462.03 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 13-MAR-15:10 | 233.66 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 462.03 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.91 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 462.03 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 | 31-MAY-15:10 | 134.15 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 462.03 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 | 26-JUN-15:10 | 86.52 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 462.03 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 16-JUL-15:07 | 71.50 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 462.03 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.59 | 16-AUG-16:00 | 59.70 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 462.03 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 10-SEP-16:00 | 139.75 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 462.03 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 11-OCT-15:10 | 195.12 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 462.03 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.77 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 462.03 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.25 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | |||||
Maximum of Months | 180.00 | 462.03 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 | 289.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 461.98 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.70 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 461.98 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 267.39 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 461.98 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 13-MAR-15:06 | 233.64 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 461.98 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.89 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 461.98 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 | 31-MAY-15:10 | 134.14 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 461.98 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.27 | 26-JUN-15:10 | 86.51 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 461.98 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.06 | 16-JUL-15:07 | 71.50 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 461.98 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 | 16-AUG-16:00 | 59.70 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 461.98 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 10-SEP-16:00 | 139.73 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 461.98 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 11-OCT-15:07 | 195.10 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 461.98 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.75 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 461.98 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.22 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | |||||
Maximum of Months | 180.00 | 461.98 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.27 | 289.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 290.45 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 129.80 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 290.45 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 136.80 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 290.45 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 13-MAR-16:00 | 119.54 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 290.45 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 93.06 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 290.45 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 31-MAY-15:09 | 68.63 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 290.45 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 | 26-JUN-15:10 | 44.26 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 290.45 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 16-JUL-15:10 | 36.58 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 290.45 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 16-AUG-16:00 | 30.54 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 290.45 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 10-SEP-16:00 | 71.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 290.45 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 11-OCT-15:10 | 99.82 | 30-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 290.45 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 117.03 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 290.45 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 147.98 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | |||||
Maximum of Months | 180.00 | 290.45 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 | 147.98 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3955.32 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 623.71 | 05-JAN-19:00 |
February | 26988.77 | 01-FEB-00:10 | 3955.32 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 651.42 | 12-FEB-05:00 |
March | 26988.77 | 01-MAR-00:10 | 3955.32 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 | 14-MAR-13:00 | 571.22 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3955.32 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 19-APR-13:50 | 447.24 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3955.32 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.72 | 17-MAY-13:00 | 336.47 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 3955.32 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.70 | 26-JUN-15:00 | 224.12 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3955.32 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.19 | 16-JUL-13:00 | 177.83 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3955.32 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.06 | 16-AUG-14:00 | 158.94 | 12-AUG-23:10 |
September | 26988.77 | 01-SEP-00:10 | 3955.32 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 | 10-SEP-13:00 | 348.88 | 22-SEP-05:00 |
October | 26988.77 | 02-OCT-00:10 | 3955.32 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.99 | 11-OCT-14:00 | 478.38 | 30-OCT-04:30 |
November | 26988.77 | 01-NOV-00:10 | 3955.32 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 07-NOV-13:55 | 562.63 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 3955.32 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 01-DEC-14:00 | 704.65 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 | |||||
Maximum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 237.70 | 704.65 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3955.32 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 623.77 | 05-JAN-19:00 |
February | 26988.77 | 01-FEB-00:10 | 3955.32 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 651.35 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3955.32 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 14-MAR-13:00 | 572.31 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3955.32 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 19-APR-13:50 | 447.88 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3955.32 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 17-MAY-13:00 | 337.34 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 3955.32 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.75 | 26-JUN-15:00 | 224.38 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3955.32 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.09 | 16-JUL-13:00 | 178.01 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3955.32 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.09 | 16-AUG-14:00 | 159.89 | 12-AUG-23:10 |
September | 26988.77 | 01-SEP-00:10 | 3955.32 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.18 | 10-SEP-13:00 | 349.39 | 22-SEP-05:00 |
October | 26988.77 | 02-OCT-00:10 | 3955.32 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.12 | 11-OCT-14:00 | 478.89 | 30-OCT-04:30 |
November | 26988.77 | 01-NOV-00:10 | 3955.32 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 07-NOV-14:30 | 564.66 | 29-NOV-21:00 |
December | 26988.77 | 01-DEC-00:10 | 3955.32 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 01-DEC-14:00 | 704.60 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.89 | |||||
Maximum of Months | 26988.77 | 3955.32 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 237.75 | 704.60 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1137.23 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 598.42 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1137.23 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 587.69 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1137.23 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 19.77 | 14-MAR-13:00 | 523.28 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1137.23 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 3.35 | 19-APR-14:00 | 406.09 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1137.23 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.60 | 17-MAY-14:00 | 301.18 | 02-MAY-06:20 |
June | 2401.70 | 01-JUN-00:10 | 1137.23 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 198.17 | 26-JUN-15:00 | 199.83 | 09-JUN-05:20 |
July | 2401.70 | 01-JUL-00:10 | 1137.23 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 171.94 | 16-JUL-13:00 | 154.94 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1137.23 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 175.30 | 16-AUG-14:00 | 154.96 | 12-AUG-22:50 |
September | 2401.70 | 01-SEP-00:10 | 1137.23 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 129.24 | 10-SEP-14:00 | 325.84 | 22-SEP-06:10 |
October | 2401.70 | 02-OCT-00:10 | 1137.23 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 62.49 | 11-OCT-14:00 | 447.22 | 30-OCT-08:00 |
November | 2401.70 | 01-NOV-00:10 | 1137.23 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.32 | 07-NOV-15:00 | 537.59 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1137.23 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 4.27 | 02-DEC-15:00 | 649.60 | 21-DEC-18:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1137.23 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 154.94 | ||||||
Maximum of Months | 2401.70 | 1137.23 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 198.17 | 649.60 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2260.10 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 400.29 | 05-JAN-19:00 |
February | 0.00 | 2260.10 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 418.01 | 12-FEB-07:00 |
March | 0.00 | 2260.10 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 14-MAR-13:00 | 365.04 | 19-MAR-07:00 |
April | 0.00 | 2260.10 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 19-APR-13:50 | 283.75 | 17-APR-03:00 |
May | 0.00 | 2260.10 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 17-MAY-13:00 | 208.77 | 03-MAY-02:00 |
June | 0.00 | 2260.10 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.86 | 26-JUN-15:00 | 133.97 | 09-JUN-04:30 |
July | 0.00 | 2260.10 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.47 | 16-JUL-13:00 | 110.37 | 02-JUL-05:00 |
August | 0.00 | 2260.10 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.73 | 16-AUG-16:00 | 91.86 | 12-AUG-23:40 |
September | 0.00 | 2260.10 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 09-SEP-13:00 | 217.55 | 22-SEP-06:00 |
October | 0.00 | 2260.10 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.75 | 11-OCT-14:00 | 304.52 | 30-OCT-07:50 |
November | 0.00 | 2260.10 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 07-NOV-14:00 | 357.36 | 29-NOV-21:00 |
December | 0.00 | 2260.10 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 01-DEC-14:00 | 448.32 | 22-DEC-03:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.86 | ||||
Maximum of Months | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 153.86 | 448.32 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 361.63 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 277.87 | 05-JAN-19:00 |
February | 0.00 | 361.63 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 289.02 | 12-FEB-05:00 |
March | 0.00 | 361.63 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 14-MAR-13:00 | 253.82 | 19-MAR-07:00 |
April | 0.00 | 361.63 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 19-APR-13:50 | 197.29 | 17-APR-03:00 |
May | 0.00 | 361.63 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.92 | 17-MAY-13:00 | 145.16 | 03-MAY-02:00 |
June | 0.00 | 361.63 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.97 | 26-JUN-15:00 | 93.15 | 09-JUN-04:20 |
July | 0.00 | 361.63 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 | 16-JUL-13:00 | 76.75 | 02-JUL-05:00 |
August | 0.00 | 361.63 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.68 | 16-AUG-14:00 | 63.88 | 12-AUG-24:00 |
September | 0.00 | 361.63 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.58 | 09-SEP-13:00 | 151.27 | 22-SEP-05:50 |
October | 0.00 | 361.63 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 11-OCT-14:00 | 211.73 | 30-OCT-06:20 |
November | 0.00 | 361.63 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 07-NOV-14:30 | 248.46 | 29-NOV-21:00 |
December | 0.00 | 361.63 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 01-DEC-14:00 | 309.31 | 22-DEC-03:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 | ||||
Maximum of Months | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 106.97 | 309.31 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1786.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 307.84 | 05-JAN-19:00 |
February | 0.00 | 1786.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 320.77 | 12-FEB-07:00 |
March | 0.00 | 1786.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 14-MAR-13:00 | 280.20 | 19-MAR-07:00 |
April | 0.00 | 1786.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 19-APR-13:10 | 218.62 | 17-APR-06:00 |
May | 0.00 | 1786.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.75 | 17-MAY-13:00 | 160.93 | 03-MAY-02:00 |
June | 0.00 | 1786.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.97 | 26-JUN-15:00 | 103.37 | 09-JUN-05:00 |
July | 0.00 | 1786.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.94 | 16-JUL-13:00 | 85.23 | 02-JUL-05:00 |
August | 0.00 | 1786.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 16-AUG-16:00 | 70.97 | 12-AUG-23:40 |
September | 0.00 | 1786.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.22 | 10-SEP-13:00 | 167.69 | 22-SEP-05:00 |
October | 0.00 | 1786.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 | 11-OCT-14:00 | 234.60 | 30-OCT-07:40 |
November | 0.00 | 1786.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 06-NOV-13:00 | 275.25 | 29-NOV-21:00 |
December | 0.00 | 1786.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 01-DEC-14:00 | 342.53 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | |||
Maximum of Months | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.97 | 342.53 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1890.37 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 543.54 | 05-JAN-19:00 |
February | 0.00 | 1890.37 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 563.67 | 12-FEB-05:00 |
March | 0.00 | 1890.37 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 14-MAR-13:00 | 496.54 | 19-MAR-07:00 |
April | 0.00 | 1890.37 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 19-APR-13:50 | 387.79 | 17-APR-03:00 |
May | 0.00 | 1890.37 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.66 | 17-MAY-13:00 | 285.63 | 03-MAY-02:00 |
June | 0.00 | 1890.37 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 | 26-JUN-15:00 | 183.73 | 09-JUN-05:00 |
July | 0.00 | 1890.37 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.29 | 16-JUL-13:00 | 151.62 | 02-JUL-05:00 |
August | 0.00 | 1890.37 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 | 16-AUG-16:00 | 126.37 | 12-AUG-23:50 |
September | 0.00 | 1890.37 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.65 | 10-SEP-14:00 | 297.59 | 22-SEP-05:30 |
October | 0.00 | 1890.37 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.84 | 11-OCT-14:00 | 416.07 | 30-OCT-07:30 |
November | 0.00 | 1890.37 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 | 07-NOV-15:00 | 488.02 | 29-NOV-21:00 |
December | 0.00 | 1890.37 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 01-DEC-14:00 | 600.17 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1890.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.37 | |||
Maximum of Months | 0.00 | 1890.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 | 600.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18765.64 | 27-JAN-22:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18476.75 | 23-FEB-22:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19398.21 | 15-MAR-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20182.10 | 12-APR-19:20 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20290.56 | 12-MAY-20:00 | 8945.92 | 17018.80 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20686.67 | 09-JUN-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20692.12 | 03-JUL-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23476.69 | 17-AUG-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25808.10 | 12-SEP-21:00 | 10223.90 | 15127.82 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23772.09 | 10-OCT-18:10 | 62621.41 | 105894.73 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21654.89 | 09-NOV-09:00 | 5111.95 | 7563.91 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19655.02 | 02-DEC-18:10 | 30671.71 | 45383.46 | 29809.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18476.75 | 5111.95 | 7563.91 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25808.10 | 62621.41 | 105894.73 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4480.61 | 20-JAN-13:10 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 |
February | 4293.40 | 18-FEB-13:30 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 |
March | 3966.61 | 14-MAR-12:50 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 0.00 |
April | 3370.81 | 07-APR-13:00 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 |
May | 2636.98 | 06-MAY-13:30 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 0.00 |
June | 3226.06 | 26-JUN-18:10 | 5457.82 | 4922.39 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 294.38 | 0.00 |
July | 3184.06 | 18-JUL-12:50 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 253.45 | 0.00 |
August | 3469.16 | 31-AUG-12:40 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 | 0.00 |
September | 4076.77 | 28-SEP-13:00 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.67 | 0.00 |
October | 4148.86 | 10-OCT-12:50 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
November | 4382.74 | 07-NOV-13:30 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 |
December | 4236.92 | 02-DEC-13:00 | 389.84 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2636.98 | 259.90 | 256.37 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4480.61 | 5457.82 | 4922.39 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 294.38 | 78.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1833.20 | 20-JAN-22:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 |
February | 1806.02 | 17-FEB-22:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 |
March | 2123.85 | 14-MAR-18:03 | 7373.52 | 6650.17 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
April | 2094.99 | 20-APR-19:00 | 1053.36 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
May | 2381.09 | 10-MAY-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
June | 2468.53 | 26-JUN-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 0.00 |
July | 2450.04 | 24-JUL-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 0.00 |
August | 2462.03 | 16-AUG-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 0.00 |
September | 2440.19 | 12-SEP-21:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 |
October | 2195.78 | 10-OCT-18:15 | 2106.72 | 1900.05 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 |
November | 1859.92 | 06-NOV-19:10 | 7373.52 | 6650.17 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 |
December | 1785.98 | 04-DEC-22:00 | 1203.84 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1785.98 | 1053.36 | 950.02 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2468.53 | 7373.52 | 6650.17 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 62.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1844.60 | 20-JAN-22:00 | 0.00 | 2008.98 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.34 |
February | 1818.99 | 27-FEB-21:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.98 |
March | 2266.78 | 14-MAR-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.87 |
April | 2247.14 | 20-APR-19:30 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 |
May | 2479.34 | 31-MAY-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 |
June | 2717.39 | 26-JUN-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 98.77 | 0.00 |
July | 2716.61 | 18-JUL-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 0.00 |
August | 2701.90 | 16-AUG-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 | 0.00 |
September | 2612.52 | 12-SEP-20:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 0.00 |
October | 2292.67 | 10-OCT-19:30 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 |
November | 1873.86 | 09-NOV-21:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.77 |
December | 1827.04 | 04-DEC-21:00 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1818.99 | 0.00 | 2008.98 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2717.39 | 0.00 | 2260.10 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 98.77 | 158.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 532.74 | 20-JAN-22:00 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.73 |
February | 460.44 | 18-FEB-22:00 | 0.00 | 281.27 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 |
March | 651.46 | 14-MAR-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 |
April | 632.86 | 20-APR-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
May | 751.10 | 31-MAY-19:10 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
June | 1010.38 | 26-JUN-19:20 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 0.00 |
July | 974.10 | 17-JUL-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 | 0.00 |
August | 945.17 | 16-AUG-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 47.87 | 0.00 |
September | 834.08 | 12-SEP-20:00 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 |
October | 677.43 | 11-OCT-20:50 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 |
November | 574.86 | 09-NOV-22:00 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.30 |
December | 491.49 | 04-DEC-22:00 | 0.00 | 321.45 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 460.44 | 0.00 | 281.27 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1010.38 | 0.00 | 361.63 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 88.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36035.65 | 20-JAN-21:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 227.25 |
February | 35943.37 | 17-FEB-21:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 229.23 |
March | 37021.88 | 14-MAR-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 |
April | 36773.96 | 20-APR-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 108.10 |
May | 37542.78 | 31-MAY-19:30 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 |
June | 38375.66 | 26-JUN-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.68 | 0.00 |
July | 38321.17 | 17-JUL-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 90.06 | 0.00 |
August | 38289.66 | 16-AUG-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.81 | 0.00 |
September | 38095.78 | 12-SEP-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.77 | 0.00 |
October | 36685.92 | 04-OCT-20:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 140.63 |
November | 36089.09 | 08-NOV-21:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 227.39 |
December | 35814.65 | 01-DEC-21:00 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 254.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35814.65 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38375.66 | 705.60 | 429.55 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.68 | 254.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17008.77 | 20-JAN-13:00 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 |
February | 16769.59 | 18-FEB-13:20 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.06 |
March | 15237.86 | 14-MAR-12:50 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 81.31 | 0.00 |
April | 12865.32 | 07-APR-12:30 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 |
May | 12591.98 | 10-MAY-21:05 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 |
June | 13990.67 | 26-JUN-21:10 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 329.66 | 0.00 |
July | 14042.61 | 17-JUL-21:20 | 15368.40 | 1501.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 323.56 | 0.00 |
August | 14030.55 | 16-AUG-21:15 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 197.70 | 0.00 |
September | 15544.99 | 28-SEP-12:50 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 390.53 | 0.00 |
October | 15942.73 | 07-OCT-12:40 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
November | 16867.29 | 05-NOV-12:00 | 5122.80 | 750.78 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 |
December | 16696.90 | 02-DEC-13:00 | 5122.80 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12591.98 | 3415.20 | 625.65 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17008.77 | 30736.80 | 3003.14 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 390.53 | 156.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38589.48 | 20-JAN-13:00 | 10138.44 | 3666.98 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
February | 39895.16 | 18-FEB-13:10 | 15207.66 | 3666.98 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 |
March | 41485.25 | 14-MAR-18:10 | 248391.78 | 82140.39 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.44 |
April | 40863.53 | 19-APR-18:40 | 35484.54 | 11734.34 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.82 |
May | 46277.27 | 10-MAY-21:00 | 40553.76 | 11734.34 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
June | 47893.26 | 26-JUN-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 644.01 | 0.00 |
July | 47933.01 | 17-JUL-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 680.15 | 0.00 |
August | 47847.00 | 16-AUG-21:15 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 383.39 | 0.00 |
September | 47526.31 | 12-SEP-21:10 | 91245.96 | 17601.51 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 167.16 | 0.00 |
October | 42766.88 | 10-OCT-18:10 | 248391.78 | 82140.39 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.33 |
November | 40917.94 | 05-NOV-10:00 | 25346.10 | 4400.38 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.16 |
December | 40973.37 | 17-DEC-12:50 | 15207.66 | 4400.38 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 38589.48 | 10138.44 | 3666.98 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47933.01 | 248391.78 | 82140.39 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 680.15 | 357.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4477.75 | 14-JAN-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.41 |
February | 4520.66 | 11-FEB-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.35 |
March | 4540.17 | 13-MAR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
April | 4509.27 | 07-APR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
May | 4486.32 | 05-MAY-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
June | 4566.83 | 26-JUN-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 90.14 | 0.00 |
July | 4578.73 | 01-JUL-18:01 | 819.00 | 3234.23 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 | 0.00 |
August | 4575.46 | 16-AUG-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 | 0.00 |
September | 4570.39 | 28-SEP-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 | 0.00 |
October | 4569.90 | 11-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 0.00 |
November | 4527.11 | 05-NOV-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
December | 4401.05 | 02-DEC-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4401.05 | 378.00 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4578.73 | 819.00 | 3234.23 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 90.14 | 193.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4354.38 | 23-JAN-16:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 |
February | 4357.40 | 25-FEB-16:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 |
March | 4436.19 | 13-MAR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
April | 4436.32 | 07-APR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
May | 4437.84 | 15-MAY-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 0.00 |
June | 4525.37 | 27-JUN-18:01 | 970.20 | 2878.13 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 | 0.00 |
July | 4537.48 | 01-JUL-18:01 | 819.00 | 3233.85 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 0.00 |
August | 4524.77 | 16-AUG-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 0.00 |
September | 4497.00 | 10-SEP-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 0.00 |
October | 4473.38 | 11-OCT-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 0.00 |
November | 4396.04 | 07-NOV-16:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
December | 4297.37 | 02-DEC-16:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4297.37 | 378.00 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4537.48 | 970.20 | 3233.85 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 58.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1034.97 | 20-JAN-12:30 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
February | 961.07 | 18-FEB-12:50 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 |
March | 849.99 | 11-MAR-12:50 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
April | 536.33 | 08-APR-12:40 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
May | 440.74 | 31-MAY-17:12 | 0.00 | 778.19 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 0.00 |
June | 578.93 | 30-JUN-20:20 | 0.00 | 258.43 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
July | 631.86 | 02-JUL-18:40 | 0.00 | 290.37 | 126.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
August | 663.23 | 02-AUG-18:03 | 0.00 | 1550.57 | 758.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 |
September | 850.87 | 28-SEP-12:30 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 0.00 |
October | 906.57 | 10-OCT-12:30 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
November | 1001.54 | 07-NOV-11:53 | 0.00 | 243.91 | 201.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
December | 982.00 | 17-DEC-12:10 | 0.00 | 95.82 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 440.74 | 0.00 | 81.30 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1034.97 | 0.00 | 1550.57 | 758.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 11.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1350.08 | 21-JAN-09:01 | 378.00 | 1138.56 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
February | 1348.12 | 19-FEB-09:01 | 378.00 | 1138.56 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 |
March | 1382.86 | 14-MAR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
April | 1391.50 | 27-APR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
May | 1448.21 | 18-MAY-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 1458.77 | 29-JUN-18:01 | 970.20 | 1809.50 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.00 |
July | 1462.10 | 08-JUL-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
August | 1455.53 | 19-AUG-18:01 | 819.00 | 2033.14 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 | 0.00 |
September | 1452.81 | 11-SEP-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 0.00 |
October | 1401.88 | 11-OCT-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
November | 1357.67 | 09-NOV-19:01 | 970.20 | 1809.50 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 |
December | 1333.43 | 03-DEC-09:01 | 378.00 | 1138.56 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1333.43 | 378.00 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1462.10 | 970.20 | 2033.14 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 27.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3973.08 | 22-JAN-09:01 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.81 |
February | 4002.27 | 11-FEB-09:01 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.20 |
March | 3986.95 | 11-MAR-09:01 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 |
April | 3939.91 | 19-APR-08:62 | 216.00 | 1219.77 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 |
May | 3969.94 | 17-MAY-08:62 | 216.00 | 1219.77 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 | 0.00 |
June | 4049.77 | 30-JUN-08:61 | 252.00 | 1423.06 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 | 0.00 |
July | 4071.51 | 01-JUL-08:61 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 0.00 |
August | 4040.26 | 19-AUG-08:61 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
September | 4016.53 | 09-SEP-08:61 | 378.00 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 0.00 |
October | 3976.76 | 11-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 | 0.00 |
November | 3972.59 | 07-NOV-09:01 | 252.00 | 1423.06 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 |
December | 3951.04 | 18-DEC-09:01 | 252.00 | 1423.06 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3939.91 | 216.00 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4071.51 | 680.40 | 1811.17 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 | 172.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3858.45 | 20-JAN-09:01 | 252.00 | 1422.89 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 |
February | 3926.18 | 23-FEB-09:01 | 252.00 | 1422.89 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.08 |
March | 3938.03 | 11-MAR-09:01 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 |
April | 3916.58 | 19-APR-08:62 | 216.00 | 1219.62 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
May | 3951.00 | 17-MAY-08:62 | 216.00 | 1219.62 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
June | 4033.40 | 30-JUN-08:61 | 252.00 | 1422.89 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 0.00 |
July | 4054.91 | 01-JUL-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 0.00 |
August | 4019.92 | 19-AUG-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
September | 3994.73 | 09-SEP-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 0.00 |
October | 3915.12 | 08-OCT-08:61 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
November | 3894.77 | 07-NOV-09:01 | 252.00 | 1422.89 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 |
December | 3818.64 | 02-DEC-09:01 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3818.64 | 216.00 | 1219.62 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4054.91 | 378.00 | 1810.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 123.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2389.36 | 20-JAN-13:40 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
February | 2321.80 | 18-FEB-14:00 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 |
March | 2391.74 | 14-MAR-13:20 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 0.00 |
April | 1973.67 | 20-APR-18:15 | 0.00 | 3175.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 |
May | 2261.12 | 31-MAY-18:30 | 0.00 | 1587.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
June | 2438.79 | 26-JUN-19:10 | 0.00 | 1786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 0.00 |
July | 2411.95 | 15-JUL-18:50 | 0.00 | 1389.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.81 | 0.00 |
August | 2422.51 | 16-AUG-18:30 | 0.00 | 1587.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.36 | 0.00 |
September | 2422.95 | 28-SEP-13:40 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.60 | 0.00 |
October | 2422.16 | 11-OCT-14:00 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 | 0.00 |
November | 2412.83 | 07-NOV-14:00 | 0.00 | 992.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
December | 2306.11 | 02-DEC-13:30 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1973.67 | 0.00 | 496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2438.79 | 0.00 | 3175.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 27.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4816.77 | 23-JAN-16:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 |
February | 4820.17 | 17-FEB-16:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 |
March | 4903.52 | 13-MAR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 0.00 |
April | 4852.17 | 07-APR-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
May | 4845.28 | 15-MAY-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 | 0.00 |
June | 4948.78 | 26-JUN-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 89.53 | 0.00 |
July | 4945.86 | 01-JUL-18:01 | 819.00 | 3234.23 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 | 0.00 |
August | 4959.31 | 16-AUG-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 0.00 |
September | 4939.24 | 28-SEP-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 | 0.00 |
October | 4930.44 | 11-OCT-15:01 | 680.40 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 |
November | 4881.85 | 05-NOV-15:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
December | 4741.02 | 02-DEC-16:01 | 378.00 | 1067.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4741.02 | 378.00 | 905.58 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4959.31 | 819.00 | 3234.23 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 89.53 | 48.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4676.16 | 23-JAN-16:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
February | 4682.20 | 25-FEB-16:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 |
March | 4789.70 | 13-MAR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
April | 4774.42 | 07-APR-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
May | 4795.79 | 15-MAY-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 0.00 |
June | 4903.29 | 26-JUN-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 89.52 | 0.00 |
July | 4905.46 | 01-JUL-18:01 | 819.00 | 3233.85 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 0.00 |
August | 4906.07 | 16-AUG-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 | 0.00 |
September | 4860.50 | 10-SEP-15:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 50.75 | 0.00 |
October | 4821.77 | 11-OCT-15:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
November | 4734.65 | 07-NOV-16:01 | 680.40 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
December | 4615.22 | 02-DEC-16:01 | 378.00 | 1067.17 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4615.22 | 378.00 | 905.48 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4906.07 | 819.00 | 3233.85 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 89.52 | 58.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2208.74 | 14-JAN-16:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.18 |
February | 2225.57 | 11-FEB-16:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.72 |
March | 2185.44 | 13-MAR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.00 |
April | 2136.69 | 07-APR-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
May | 2144.83 | 16-MAY-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
June | 2164.35 | 26-JUN-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 0.00 |
July | 2164.28 | 08-JUL-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
August | 2166.81 | 16-AUG-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 0.00 |
September | 2184.74 | 28-SEP-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
October | 2195.69 | 11-OCT-15:01 | 680.40 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 0.00 |
November | 2201.19 | 05-NOV-15:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
December | 2155.67 | 10-DEC-16:01 | 378.00 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2136.69 | 378.00 | 569.28 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2225.57 | 680.40 | 670.94 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 100.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19224.38 | 20-JAN-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.29 |
February | 19087.12 | 17-FEB-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.41 |
March | 20760.61 | 14-MAR-18:10 | 146938.85 | 24610.91 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 |
April | 21316.67 | 20-APR-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.72 |
May | 23669.03 | 10-MAY-21:10 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 |
June | 24765.78 | 26-JUN-21:15 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 | 0.00 |
July | 24693.83 | 17-JUL-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 81.92 | 0.00 |
August | 24623.36 | 16-AUG-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 0.00 |
September | 24243.24 | 12-SEP-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 0.00 |
October | 21070.80 | 10-OCT-18:10 | 146938.85 | 24610.91 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 |
November | 19544.15 | 09-NOV-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.67 |
December | 19163.10 | 04-DEC-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 19087.12 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24765.78 | 146938.85 | 24610.91 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 81.92 | 226.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20470.54 | 20-JAN-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.74 |
February | 20329.19 | 17-FEB-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.90 |
March | 21990.46 | 14-MAR-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.40 |
April | 22589.74 | 20-APR-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.76 |
May | 24995.52 | 10-MAY-21:10 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 |
June | 26081.22 | 26-JUN-21:15 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 | 0.00 |
July | 26011.89 | 17-JUL-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 0.00 |
August | 25914.95 | 16-AUG-21:15 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 45.96 | 0.00 |
September | 25514.26 | 12-SEP-21:20 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
October | 22333.48 | 05-OCT-22:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.47 |
November | 20803.29 | 09-NOV-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.09 |
December | 20406.99 | 04-DEC-23:00 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20329.19 | 26988.77 | 2636.88 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26081.22 | 53977.54 | 5273.77 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 227.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28565.39 | 20-JAN-11:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 |
February | 28468.13 | 18-FEB-11:50 | 800.57 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 |
March | 29236.24 | 14-MAR-10:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
April | 29022.13 | 19-APR-10:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.26 |
May | 29311.58 | 16-MAY-10:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
June | 29900.35 | 26-JUN-18:07 | 11207.95 | 6065.24 | 90672.63 | 89971.33 | 0.00 | 0.00 | 0.00 | 159.49 | 0.00 |
July | 29881.71 | 23-JUL-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 75.01 | 0.00 |
August | 29842.63 | 06-AUG-10:50 | 800.57 | 379.08 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 71.36 | 0.00 |
September | 29472.17 | 09-SEP-10:50 | 800.57 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 92.15 | 0.00 |
October | 29330.59 | 07-OCT-10:50 | 800.57 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 |
November | 28759.38 | 07-NOV-11:50 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 55.05 |
December | 28311.58 | 02-DEC-11:50 | 800.57 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 49.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 28311.58 | 533.71 | 315.90 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29900.35 | 11207.95 | 6065.24 | 90672.63 | 89971.33 | 0.00 | 0.00 | 0.00 | 159.49 | 77.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6222.23 | 20-JAN-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
February | 6037.22 | 18-FEB-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 |
March | 6336.95 | 14-MAR-13:10 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 0.00 |
April | 5656.37 | 12-APR-12:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
May | 6060.25 | 16-MAY-12:30 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 | 0.00 |
June | 6501.16 | 26-JUN-14:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.28 | 0.00 |
July | 6461.69 | 23-JUL-13:20 | 0.00 | 420.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.67 | 0.00 |
August | 6496.29 | 16-AUG-15:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.85 | 0.00 |
September | 6543.40 | 28-SEP-13:30 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.24 | 0.00 |
October | 6342.80 | 10-OCT-13:30 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 |
November | 6297.59 | 07-NOV-13:40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
December | 5360.10 | 01-DEC-13:30 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5360.10 | 0.00 | 420.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6543.40 | 0.00 | 525.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.28 | 14.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.652552E+12 | 391175.54 | 20-JAN-20:19 | 0.605720E+12 | 652395.73 | 05-JAN-17:49 |
February | 0.583774E+12 | 385804.27 | 17-FEB-20:49 | 0.568869E+12 | 522672.46 | 05-FEB-17:40 |
March | 0.653723E+12 | 411649.08 | 14-MAR-19:10 | 0.566853E+12 | 516470.77 | 04-MAR-17:19 |
April | 0.628327E+12 | 413812.75 | 20-APR-19:10 | 0.531591E+12 | 442681.69 | 02-APR-16:40 |
May | 0.715107E+12 | 487390.87 | 31-MAY-19:19 | 0.506434E+12 | 360027.42 | 21-MAY-16:49 |
June | 0.858203E+12 | 587719.45 | 26-JUN-18:10 | 0.492519E+12 | 349935.26 | 18-JUN-17:40 |
July | 0.911361E+12 | 544889.06 | 17-JUL-19:30 | 0.509577E+12 | 352178.60 | 30-JUL-16:19 |
August | 0.882172E+12 | 546700.96 | 16-AUG-19:10 | 0.499043E+12 | 352732.28 | 06-AUG-17:49 |
September | 0.787091E+12 | 511815.44 | 12-SEP-19:10 | 0.471141E+12 | 355731.13 | 24-SEP-16:00 |
October | 0.676424E+12 | 424327.11 | 10-OCT-19:10 | 0.520184E+12 | 525116.96 | 31-OCT-16:10 |
November | 0.636320E+12 | 394295.22 | 06-NOV-20:19 | 0.531171E+12 | 563515.69 | 29-NOV-17:00 |
December | 0.652298E+12 | 386577.01 | 04-DEC-20:19 | 0.689144E+12 | 738065.64 | 21-DEC-17:40 |
Annual Sum or Average | 0.863735E+13 | 0.649225E+13 | ||||
Minimum of Months | 0.583774E+12 | 385804.27 | 0.471141E+12 | 349935.26 | ||
Maximum of Months | 0.911361E+12 | 587719.45 | 0.689144E+12 | 738065.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.118590E+12 | 0.252748E+11 | 0.148746E+12 | 0.858883E+11 | 0.177771E+12 | 0.944849E+10 | 0.00 | 0.263690E+11 | 0.00 | 0.00 | 0.465270E+11 | 0.770737E+10 | 0.00 |
February | 0.107087E+12 | 0.212801E+11 | 0.134341E+12 | 0.775767E+11 | 0.160928E+12 | 0.788423E+10 | 0.00 | 0.188462E+11 | 0.00 | 0.00 | 0.432445E+11 | 0.696470E+10 | 0.00 |
March | 0.118306E+12 | 0.213741E+11 | 0.148768E+12 | 0.858913E+11 | 0.175559E+12 | 0.101693E+11 | 0.00 | 0.373240E+11 | 0.00 | 0.00 | 0.423972E+11 | 0.770768E+10 | 0.00 |
April | 0.114747E+12 | 0.184697E+11 | 0.143913E+12 | 0.831176E+11 | 0.167675E+12 | 0.100704E+11 | 0.00 | 0.364865E+11 | 0.00 | 0.00 | 0.403484E+11 | 0.746802E+10 | 0.00 |
May | 0.118448E+12 | 0.171632E+11 | 0.148757E+12 | 0.858898E+11 | 0.176477E+12 | 0.158874E+11 | 0.00 | 0.108274E+12 | 0.00 | 0.00 | 0.302702E+11 | 0.770862E+10 | 0.00 |
June | 0.114519E+12 | 0.155935E+11 | 0.143963E+12 | 0.831203E+11 | 0.177662E+12 | 0.212270E+11 | 0.00 | 0.262172E+12 | 0.00 | 0.00 | 0.264684E+11 | 0.746213E+10 | 0.00 |
July | 0.118676E+12 | 0.165710E+11 | 0.148708E+12 | 0.858871E+11 | 0.183737E+12 | 0.226086E+11 | 0.00 | 0.292546E+12 | 0.00 | 0.00 | 0.287203E+11 | 0.771807E+10 | 0.00 |
August | 0.118306E+12 | 0.182347E+11 | 0.148768E+12 | 0.858913E+11 | 0.182916E+12 | 0.220691E+11 | 0.00 | 0.266793E+12 | 0.00 | 0.00 | 0.252610E+11 | 0.770997E+10 | 0.00 |
September | 0.114747E+12 | 0.197198E+11 | 0.143913E+12 | 0.831176E+11 | 0.175531E+12 | 0.186962E+11 | 0.00 | 0.192141E+12 | 0.00 | 0.00 | 0.257692E+11 | 0.746998E+10 | 0.00 |
October | 0.118590E+12 | 0.226618E+11 | 0.148746E+12 | 0.858884E+11 | 0.177729E+12 | 0.118214E+11 | 0.00 | 0.581353E+11 | 0.00 | 0.00 | 0.389200E+11 | 0.770788E+10 | 0.00 |
November | 0.114717E+12 | 0.238837E+11 | 0.143978E+12 | 0.831185E+11 | 0.171487E+12 | 0.947837E+10 | 0.00 | 0.324044E+11 | 0.00 | 0.00 | 0.437738E+11 | 0.745197E+10 | 0.00 |
December | 0.118676E+12 | 0.258200E+11 | 0.148708E+12 | 0.858871E+11 | 0.181347E+12 | 0.864109E+10 | 0.00 | 0.224326E+11 | 0.00 | 0.00 | 0.468749E+11 | 0.771592E+10 | 0.00 |
Annual Sum or Average | 0.139541E+13 | 0.246046E+12 | 0.175131E+13 | 0.101127E+13 | 0.210882E+13 | 0.168002E+12 | 0.00 | 0.135392E+13 | 0.438575E+12 | 0.907923E+11 | |||
Minimum of Months | 0.107087E+12 | 0.155935E+11 | 0.134341E+12 | 0.775767E+11 | 0.160928E+12 | 0.788423E+10 | 0.00 | 0.188462E+11 | 0.00 | 0.00 | 0.252610E+11 | 0.696470E+10 | 0.00 |
Maximum of Months | 0.118676E+12 | 0.258200E+11 | 0.148768E+12 | 0.858913E+11 | 0.183737E+12 | 0.226086E+11 | 0.00 | 0.292546E+12 | 0.00 | 0.00 | 0.468749E+11 | 0.771807E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.257753E+12 | 0.00 | 0.196048E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.252984E+12 | 0.00 | 0.178680E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.218168E+12 | 0.00 | 0.196647E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.198898E+12 | 0.00 | 0.185737E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.168328E+12 | 0.00 | 0.186128E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.170841E+12 | 0.00 | 0.174564E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.181663E+12 | 0.00 | 0.176094E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.172305E+12 | 0.00 | 0.174700E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.153569E+12 | 0.00 | 0.170617E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.187619E+12 | 0.00 | 0.180647E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.203967E+12 | 0.00 | 0.180113E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.345070E+12 | 0.00 | 0.192253E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.251116E+13 | 0.219223E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.153569E+12 | 0.00 | 0.170617E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.345070E+12 | 0.00 | 0.196647E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 110670.55 | 02-JAN-20:10 | 15665.55 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 63968.34 | 02-JAN-07:19 | 87021.00 | 05-JAN-09:09 | 8488.75 | 20-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 110670.55 | 01-FEB-20:10 | 15665.55 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 63968.34 | 01-FEB-07:19 | 83938.17 | 05-FEB-16:10 | 8125.35 | 18-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 110670.55 | 01-MAR-20:10 | 15665.55 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 63968.34 | 01-MAR-07:19 | 79284.23 | 04-MAR-16:10 | 8967.02 | 14-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 110670.55 | 03-APR-19:10 | 15665.55 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 63968.34 | 03-APR-06:19 | 75870.10 | 08-APR-18:10 | 8768.26 | 07-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 110670.55 | 01-MAY-19:10 | 15665.55 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 63968.34 | 01-MAY-06:19 | 81948.47 | 31-MAY-18:19 | 9986.99 | 31-MAY-09:50 | 0.00 | 01-MAY-00:10 |
June | 110670.55 | 01-JUN-19:10 | 15665.55 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 63968.34 | 01-JUN-06:19 | 87204.02 | 05-JUN-18:19 | 9994.09 | 06-JUN-08:50 | 0.00 | 01-JUN-00:10 |
July | 110670.55 | 03-JUL-19:10 | 15665.55 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 63968.34 | 03-JUL-06:19 | 84683.51 | 18-JUL-18:19 | 10433.36 | 23-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 110670.55 | 01-AUG-19:10 | 15665.55 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 63968.34 | 01-AUG-06:19 | 89360.13 | 02-AUG-18:19 | 10115.60 | 10-AUG-09:00 | 0.00 | 01-AUG-00:10 |
September | 110670.55 | 01-SEP-19:10 | 15665.55 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 63968.34 | 01-SEP-06:19 | 84340.89 | 13-SEP-15:20 | 10222.74 | 03-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 110670.55 | 02-OCT-19:10 | 15665.55 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 63968.34 | 02-OCT-06:19 | 86308.94 | 31-OCT-15:09 | 9158.01 | 09-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 110670.55 | 01-NOV-19:10 | 15665.55 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 63968.34 | 01-NOV-06:19 | 80600.88 | 28-NOV-16:10 | 8789.53 | 05-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 110670.55 | 01-DEC-20:10 | 15665.55 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 63968.34 | 01-DEC-07:19 | 94938.49 | 21-DEC-09:20 | 8498.22 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 110670.55 | 15665.55 | 89674.66 | 63968.34 | 75870.10 | 8125.35 | 0.00 | |||||||
Maximum of Months | 110670.55 | 15665.55 | 89674.66 | 63968.34 | 94938.49 | 10433.36 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 105016.92 | 20-JAN-12:00 | 0.00 | 0.00 | 18703.56 | 01-JAN-00:10 | 4739.34 | 18-JAN-07:10 | 0.00 |
February | 95057.06 | 18-FEB-13:09 | 0.00 | 0.00 | 18703.56 | 01-FEB-00:10 | 4739.24 | 14-FEB-07:10 | 0.00 |
March | 124254.27 | 13-MAR-15:09 | 0.00 | 0.00 | 18703.56 | 01-MAR-00:10 | 4739.39 | 15-MAR-06:10 | 0.00 |
April | 105562.49 | 07-APR-15:09 | 0.00 | 0.00 | 18703.56 | 01-APR-00:10 | 4738.87 | 19-APR-06:10 | 0.00 |
May | 148081.12 | 31-MAY-15:20 | 0.00 | 0.00 | 18703.56 | 01-MAY-00:10 | 4739.34 | 10-MAY-06:10 | 0.00 |
June | 257987.98 | 26-JUN-15:09 | 0.00 | 0.00 | 18703.56 | 01-JUN-08:00 | 4739.33 | 08-JUN-06:10 | 0.00 |
July | 221721.72 | 16-JUL-15:09 | 0.00 | 0.00 | 18703.56 | 01-JUL-00:10 | 4739.66 | 27-JUL-06:10 | 0.00 |
August | 224019.83 | 16-AUG-15:09 | 0.00 | 0.00 | 18703.56 | 01-AUG-11:39 | 4739.73 | 17-AUG-06:10 | 0.00 |
September | 184230.17 | 10-SEP-15:09 | 0.00 | 0.00 | 18703.56 | 01-SEP-03:09 | 4739.78 | 14-SEP-06:10 | 0.00 |
October | 145930.56 | 11-OCT-15:09 | 0.00 | 0.00 | 18703.56 | 01-OCT-00:10 | 4739.39 | 18-OCT-06:10 | 0.00 |
November | 110911.24 | 05-NOV-15:09 | 0.00 | 0.00 | 18703.56 | 01-NOV-00:10 | 4739.67 | 09-NOV-07:10 | 0.00 |
December | 105416.99 | 02-DEC-14:00 | 0.00 | 0.00 | 18703.56 | 01-DEC-00:10 | 4739.88 | 27-DEC-07:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 95057.06 | 0.00 | 0.00 | 18703.56 | 4738.87 | 0.00 | |||
Maximum of Months | 257987.98 | 0.00 | 0.00 | 18703.56 | 4739.88 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 391175.54 | 20-JAN-20:19 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 69312.37 | 5713.61 | 0.00 | 24127.44 | 0.00 |
February | 385804.27 | 17-FEB-20:49 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 68153.14 | 5416.33 | 0.00 | 19997.18 | 0.00 |
March | 411649.08 | 14-MAR-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 69855.31 | 6966.85 | 0.00 | 61695.39 | 0.00 |
April | 413812.75 | 20-APR-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 68806.07 | 6960.68 | 0.00 | 64415.08 | 0.00 |
May | 487390.87 | 31-MAY-19:19 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 74752.07 | 8788.09 | 0.00 | 111360.76 | 0.00 |
June | 587719.45 | 26-JUN-18:10 | 98435.01 | 79617.06 | 0.00 | 51433.44 | 81770.47 | 8649.71 | 0.00 | 241680.49 | 0.00 |
July | 544889.06 | 17-JUL-19:30 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 76399.04 | 8473.94 | 0.00 | 167723.56 | 0.00 |
August | 546700.96 | 16-AUG-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 76702.77 | 8359.05 | 0.00 | 169265.03 | 0.00 |
September | 511815.44 | 12-SEP-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 76989.13 | 8289.53 | 0.00 | 134751.36 | 0.00 |
October | 424327.11 | 10-OCT-19:10 | 110670.55 | 88971.67 | 15665.55 | 51766.85 | 70577.48 | 7407.10 | 0.00 | 73342.09 | 0.00 |
November | 394295.22 | 06-NOV-20:19 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 69861.75 | 5824.48 | 0.00 | 25909.23 | 0.00 |
December | 386577.01 | 04-DEC-20:19 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 68276.13 | 5438.04 | 0.00 | 20290.33 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 385804.27 | 98435.01 | 79617.06 | 0.00 | 51433.44 | 68153.14 | 5416.33 | 0.00 | 19997.18 | 0.00 | |
Maximum of Months | 587719.45 | 110670.55 | 88971.67 | 15665.55 | 51782.11 | 81770.47 | 8788.09 | 0.00 | 241680.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 418389.39 | 05-JAN-09:09 | 0.00 | 180878.61 | 31-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 379223.96 | 12-FEB-07:10 | 0.00 | 180929.78 | 08-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 330090.79 | 19-MAR-08:09 | 0.00 | 180862.57 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 228645.10 | 03-APR-08:09 | 0.00 | 180255.73 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 120324.74 | 04-MAY-09:09 | 0.00 | 179418.11 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 115382.67 | 20-JUN-08:09 | 0.00 | 178438.67 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 122108.27 | 31-JUL-08:09 | 0.00 | 177619.76 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 119243.84 | 21-AUG-08:09 | 0.00 | 177212.96 | 29-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 123870.42 | 06-SEP-08:09 | 0.00 | 177643.21 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 295487.21 | 30-OCT-08:09 | 0.00 | 178486.21 | 30-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 300602.25 | 29-NOV-17:00 | 0.00 | 179469.42 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 485079.17 | 23-DEC-07:10 | 0.00 | 180326.54 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 115382.67 | 0.00 | 177212.96 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 485079.17 | 0.00 | 180929.78 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17.83 | 20.31 | 17.83 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15.50 | 20.36 | 15.50 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 115.33 | 20.28 | 115.33 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 212.50 | 20.28 | 212.50 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 217.00 | 20.28 | 217.00 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6.00 | 20.40 | 6.00 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.17 | 20.28 | 584.17 | 20.28 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.00 | 20.40 | 217.00 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.42 | 1.33 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 1.33 | 24.65 |
December | 44.50 | 20.11 | 44.50 | 20.11 | 0.50 | 24.58 | 0.50 | 24.58 |
Annual Sum or Average | 45.83 | 20.12 | 45.83 | 20.12 | 1.83 | 24.63 | 1.83 | 24.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.50 | 20.42 | 44.50 | 20.42 | 1.33 | 24.65 | 1.33 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20.83 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.83 | 20.35 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.83 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.61 | 4.17 | 24.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.60 | 2.83 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.62 | 4.83 | 24.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.61 | 3.50 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.63 | 3.33 | 24.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.58 | 0.33 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.63 | 4.50 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.61 | 5.00 | 24.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.60 | 2.83 | 24.60 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 24.62 | 31.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.37 | 1.17 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.37 | 1.17 | 20.37 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.37 | 1.17 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.35 | 0.67 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.44 | 0.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.40 | 0.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.23 | 3.00 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.50 | 20.29 | 4.50 | 20.29 | 0.33 | 21.68 | 0.33 | 21.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 20.53 | 3.00 | 20.53 | 0.17 | 21.68 | 0.17 | 21.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.51 | 0.67 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.51 | 0.67 | 20.51 | 0.17 | 21.70 | 0.17 | 21.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.51 | 0.67 | 20.51 | 0.17 | 21.70 | 0.17 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.47 | 1.00 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.47 | 1.00 | 20.47 | 0.17 | 21.72 | 0.17 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.47 | 1.00 | 20.47 | 0.17 | 21.72 | 0.17 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22.00 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.00 | 20.32 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.00 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.51 | 0.17 | 20.51 | 0.17 | 21.81 | 0.17 | 21.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.51 | 0.17 | 20.51 | 0.17 | 21.81 | 0.17 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.53 | 0.67 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.53 | 0.67 | 20.53 | 0.17 | 21.84 | 0.17 | 21.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.53 | 0.67 | 20.53 | 0.17 | 21.84 | 0.17 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.44 | 0.50 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.44 | 0.50 | 20.44 | 0.50 | 21.69 | 0.50 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.44 | 0.50 | 20.44 | 0.33 | 21.69 | 0.33 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.66 | 15.50 | 24.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 24.70 | 16.17 | 24.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 24.70 | 17.50 | 24.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 24.71 | 20.33 | 24.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 24.72 | 9.17 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.64 | 0.50 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 24.69 | 14.83 | 24.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.68 | 17.33 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.66 | 6.50 | 24.66 |
Annual Sum or Average | 0.00 | 0.00 | 117.83 | 24.69 | 117.83 | 24.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 24.72 | 20.33 | 24.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63.83 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.67 | 20.11 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.83 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 26.67 | 20.83 | 26.67 | 20.83 |
February | 672.00 | 21.05 | 73.33 | 20.95 | 73.33 | 20.95 |
March | 744.00 | 20.99 | 125.83 | 20.74 | 125.83 | 20.74 |
April | 720.00 | 20.98 | 78.67 | 20.67 | 78.67 | 20.67 |
May | 744.00 | 20.84 | 98.00 | 20.39 | 98.00 | 20.39 |
June | 720.00 | 20.69 | 109.50 | 20.29 | 109.50 | 20.29 |
July | 744.00 | 20.67 | 79.83 | 20.30 | 79.83 | 20.30 |
August | 744.00 | 20.84 | 34.17 | 20.53 | 34.17 | 20.53 |
September | 720.00 | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.28 | 2.33 | 20.87 | 2.33 | 20.87 |
December | 744.00 | 21.21 | 16.83 | 21.00 | 16.83 | 21.00 |
Annual Sum or Average | 8760.00 | 20.99 | 645.17 | 20.57 | 645.17 | 20.57 |
Minimum of Months | 672.00 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.28 | 125.83 | 21.00 | 125.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 655.67 | 21.12 | 193.33 | 21.65 | 149.17 | 20.97 |
February | 609.17 | 21.13 | 254.00 | 21.23 | 233.17 | 20.99 |
March | 716.50 | 21.09 | 223.33 | 21.01 | 222.50 | 21.00 |
April | 720.00 | 21.01 | 187.00 | 21.00 | 187.00 | 21.00 |
May | 744.00 | 21.00 | 24.33 | 21.00 | 24.33 | 21.00 |
June | 720.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 710.83 | 21.08 | 10.33 | 21.00 | 10.33 | 21.00 |
October | 679.33 | 21.12 | 128.33 | 21.10 | 122.83 | 21.00 |
November | 632.83 | 21.12 | 179.67 | 21.77 | 132.00 | 21.00 |
December | 681.00 | 21.03 | 358.00 | 21.14 | 326.50 | 20.86 |
Annual Sum or Average | 8357.33 | 21.06 | 1558.33 | 21.25 | 1407.83 | 20.96 |
Minimum of Months | 609.17 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.13 | 358.00 | 21.77 | 326.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 17.67 | 21.00 | 17.67 | 21.00 |
February | 672.00 | 21.06 | 28.67 | 21.00 | 28.67 | 21.00 |
March | 744.00 | 21.07 | 2.83 | 21.00 | 2.83 | 21.00 |
April | 720.00 | 21.06 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.05 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.08 | 11.33 | 21.00 | 11.33 | 21.00 |
November | 720.00 | 21.07 | 2.67 | 21.00 | 2.67 | 21.00 |
December | 744.00 | 21.05 | 101.50 | 21.00 | 101.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.05 | 164.67 | 21.00 | 164.67 | 21.00 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.08 | 101.50 | 21.00 | 101.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 548.17 | 21.49 | 166.67 | 23.14 | 96.00 | 23.87 |
February | 504.50 | 21.47 | 145.50 | 23.20 | 84.00 | 23.89 |
March | 544.67 | 21.48 | 166.33 | 23.14 | 98.00 | 23.86 |
April | 494.17 | 21.47 | 173.50 | 22.88 | 94.00 | 23.72 |
May | 441.83 | 21.25 | 225.33 | 22.14 | 83.33 | 23.41 |
June | 397.33 | 20.61 | 263.33 | 21.38 | 56.50 | 22.37 |
July | 415.67 | 20.51 | 272.83 | 21.33 | 53.00 | 22.37 |
August | 409.67 | 20.56 | 288.17 | 21.35 | 60.00 | 22.32 |
September | 427.17 | 20.81 | 198.50 | 21.78 | 59.00 | 22.91 |
October | 508.33 | 21.45 | 174.33 | 22.93 | 94.17 | 23.81 |
November | 507.00 | 21.52 | 166.67 | 23.10 | 97.00 | 23.86 |
December | 578.33 | 21.41 | 148.67 | 23.30 | 85.67 | 23.90 |
Annual Sum or Average | 5776.83 | 21.21 | 2389.83 | 22.29 | 960.67 | 23.49 |
Minimum of Months | 397.33 | 20.51 | 145.50 | 21.33 | 53.00 | 22.32 |
Maximum of Months | 578.33 | 21.52 | 288.17 | 23.30 | 98.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 654.83 | 21.13 | 100.67 | 21.89 | 60.33 | 21.00 |
February | 605.33 | 21.13 | 134.83 | 21.28 | 117.33 | 21.00 |
March | 726.33 | 21.11 | 50.33 | 21.00 | 50.33 | 21.00 |
April | 720.00 | 21.03 | 55.00 | 21.00 | 55.00 | 21.00 |
May | 744.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.00 | 0.50 | 21.00 | 0.50 | 21.00 |
July | 744.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.00 | 1.50 | 21.01 | 1.50 | 21.01 |
September | 718.00 | 21.04 | 0.33 | 21.00 | 0.33 | 21.00 |
October | 693.50 | 21.16 | 60.33 | 21.04 | 59.33 | 21.00 |
November | 632.33 | 21.14 | 94.17 | 22.00 | 52.50 | 21.01 |
December | 681.50 | 21.09 | 160.00 | 21.37 | 133.67 | 20.98 |
Annual Sum or Average | 8383.83 | 21.07 | 657.67 | 21.43 | 530.83 | 21.00 |
Minimum of Months | 605.33 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.16 | 160.00 | 22.00 | 133.67 | 21.01 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.12 | 7.67 | 21.00 | 7.67 | 21.00 |
February | 672.00 | 21.10 | 16.50 | 21.00 | 16.50 | 21.00 |
March | 744.00 | 21.14 | 1.33 | 21.00 | 1.33 | 21.00 |
April | 720.00 | 21.12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.13 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.03 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.02 | 0.33 | 21.09 | 0.33 | 21.09 |
September | 720.00 | 21.08 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.17 | 5.17 | 21.00 | 5.17 | 21.00 |
November | 720.00 | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.10 | 68.83 | 21.00 | 68.83 | 21.00 |
Annual Sum or Average | 8760.00 | 21.10 | 99.83 | 21.00 | 99.83 | 21.00 |
Minimum of Months | 672.00 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.17 | 68.83 | 21.09 | 68.83 | 21.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.00 | 21.34 | 177.67 | 20.81 | 177.67 | 20.81 |
February | 667.50 | 21.25 | 249.33 | 20.75 | 249.33 | 20.75 |
March | 739.17 | 21.26 | 206.83 | 20.65 | 206.83 | 20.65 |
April | 719.67 | 21.24 | 171.83 | 20.62 | 171.83 | 20.62 |
May | 735.50 | 21.57 | 9.00 | 21.14 | 8.67 | 21.05 |
June | 659.50 | 21.58 | 11.33 | 22.54 | 3.00 | 21.40 |
July | 681.33 | 21.57 | 13.67 | 21.89 | 9.67 | 21.43 |
August | 686.17 | 21.57 | 9.33 | 22.10 | 4.17 | 21.20 |
September | 685.00 | 21.59 | 5.83 | 21.21 | 4.83 | 20.90 |
October | 725.17 | 21.33 | 117.67 | 20.46 | 117.67 | 20.46 |
November | 709.33 | 21.34 | 160.67 | 20.72 | 160.67 | 20.72 |
December | 743.67 | 21.18 | 383.67 | 20.77 | 383.67 | 20.77 |
Annual Sum or Average | 8490.00 | 21.40 | 1516.83 | 20.75 | 1498.00 | 20.72 |
Minimum of Months | 659.50 | 21.18 | 5.83 | 20.46 | 3.00 | 20.46 |
Maximum of Months | 743.67 | 21.59 | 383.67 | 22.54 | 383.67 | 21.43 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 384.33 | 20.66 | 384.33 | 20.66 |
February | 672.00 | 20.91 | 381.50 | 20.63 | 381.50 | 20.63 |
March | 744.00 | 21.09 | 291.17 | 20.65 | 291.17 | 20.65 |
April | 720.00 | 21.15 | 192.00 | 20.59 | 192.00 | 20.59 |
May | 738.50 | 21.55 | 10.00 | 21.06 | 10.00 | 21.06 |
June | 665.00 | 21.59 | 10.83 | 22.55 | 2.83 | 21.49 |
July | 690.50 | 21.59 | 15.50 | 21.69 | 12.17 | 21.34 |
August | 704.33 | 21.60 | 8.83 | 21.78 | 5.00 | 21.12 |
September | 706.67 | 21.59 | 5.67 | 20.92 | 5.67 | 20.92 |
October | 743.33 | 21.19 | 149.17 | 20.53 | 149.17 | 20.53 |
November | 720.00 | 21.04 | 285.00 | 20.66 | 285.00 | 20.66 |
December | 744.00 | 20.86 | 563.00 | 20.69 | 563.00 | 20.69 |
Annual Sum or Average | 8592.33 | 21.25 | 2297.00 | 20.67 | 2281.83 | 20.65 |
Minimum of Months | 665.00 | 20.86 | 5.67 | 20.53 | 2.83 | 20.53 |
Maximum of Months | 744.00 | 21.60 | 563.00 | 22.55 | 563.00 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 200.33 | 20.76 | 200.33 | 20.76 |
February | 672.00 | 21.03 | 291.83 | 20.78 | 291.83 | 20.78 |
March | 744.00 | 21.22 | 76.67 | 20.84 | 76.67 | 20.84 |
April | 720.00 | 21.29 | 31.17 | 20.78 | 31.17 | 20.78 |
May | 744.00 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.65 | 0.33 | 21.29 | 0.33 | 21.29 |
July | 744.00 | 21.66 | 2.83 | 21.97 | 2.83 | 21.97 |
August | 744.00 | 21.62 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.27 | 64.83 | 20.57 | 64.83 | 20.57 |
November | 720.00 | 21.14 | 110.17 | 20.67 | 110.17 | 20.67 |
December | 744.00 | 20.99 | 322.83 | 20.72 | 322.83 | 20.72 |
Annual Sum or Average | 8760.00 | 21.34 | 1101.00 | 20.74 | 1101.00 | 20.74 |
Minimum of Months | 672.00 | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.66 | 322.83 | 21.97 | 322.83 | 21.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 172.83 | 20.84 | 172.83 | 20.84 |
February | 670.00 | 21.31 | 258.00 | 20.78 | 258.00 | 20.78 |
March | 743.00 | 21.35 | 200.17 | 20.68 | 200.17 | 20.68 |
April | 716.17 | 21.32 | 162.83 | 20.68 | 162.83 | 20.68 |
May | 737.67 | 21.65 | 9.00 | 21.11 | 9.00 | 21.11 |
June | 658.00 | 21.61 | 7.00 | 22.58 | 0.83 | 21.93 |
July | 660.00 | 21.55 | 11.50 | 22.01 | 6.83 | 21.53 |
August | 652.33 | 21.53 | 12.50 | 22.66 | 1.50 | 21.11 |
September | 683.33 | 21.63 | 5.67 | 21.47 | 4.00 | 20.93 |
October | 739.00 | 21.41 | 121.67 | 20.51 | 121.67 | 20.51 |
November | 718.33 | 21.38 | 164.83 | 20.74 | 164.83 | 20.74 |
December | 744.00 | 21.20 | 387.50 | 20.80 | 387.50 | 20.80 |
Annual Sum or Average | 8465.83 | 21.44 | 1513.50 | 20.78 | 1490.00 | 20.75 |
Minimum of Months | 652.33 | 21.20 | 5.67 | 20.51 | 0.83 | 20.51 |
Maximum of Months | 744.00 | 21.65 | 387.50 | 22.66 | 387.50 | 21.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.93 | 388.83 | 20.70 | 388.83 | 20.70 |
February | 672.00 | 20.95 | 370.33 | 20.66 | 370.33 | 20.66 |
March | 744.00 | 21.20 | 260.17 | 20.73 | 260.17 | 20.73 |
April | 716.50 | 21.26 | 187.17 | 20.68 | 187.17 | 20.68 |
May | 737.83 | 21.64 | 9.67 | 21.11 | 9.67 | 21.11 |
June | 661.00 | 21.62 | 7.17 | 22.59 | 0.83 | 21.88 |
July | 671.83 | 21.58 | 12.33 | 21.98 | 7.50 | 21.49 |
August | 692.00 | 21.63 | 12.67 | 22.46 | 2.83 | 21.12 |
September | 708.67 | 21.67 | 5.83 | 21.24 | 4.83 | 20.94 |
October | 742.67 | 21.27 | 155.83 | 20.62 | 155.83 | 20.62 |
November | 720.00 | 21.00 | 303.17 | 20.69 | 303.17 | 20.69 |
December | 744.00 | 20.84 | 555.50 | 20.70 | 555.50 | 20.70 |
Annual Sum or Average | 8554.50 | 21.29 | 2268.67 | 20.71 | 2246.67 | 20.69 |
Minimum of Months | 661.00 | 20.84 | 5.83 | 20.62 | 0.83 | 20.62 |
Maximum of Months | 744.00 | 21.67 | 555.50 | 22.59 | 555.50 | 21.88 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.00 | 21.26 | 302.17 | 20.84 | 302.17 | 20.84 |
February | 662.67 | 21.19 | 327.83 | 20.78 | 327.83 | 20.78 |
March | 730.33 | 21.20 | 304.17 | 20.72 | 304.17 | 20.72 |
April | 714.17 | 21.20 | 232.00 | 20.61 | 232.00 | 20.61 |
May | 714.33 | 21.55 | 23.17 | 21.17 | 21.33 | 21.01 |
June | 598.83 | 21.42 | 34.33 | 22.82 | 4.67 | 21.48 |
July | 609.83 | 21.39 | 42.67 | 22.42 | 17.67 | 21.42 |
August | 614.33 | 21.39 | 30.33 | 22.63 | 7.33 | 21.39 |
September | 632.50 | 21.46 | 18.50 | 21.86 | 10.50 | 20.96 |
October | 710.00 | 21.27 | 181.33 | 20.59 | 180.67 | 20.58 |
November | 697.33 | 21.26 | 251.83 | 20.77 | 251.83 | 20.77 |
December | 738.50 | 21.09 | 481.33 | 20.76 | 481.33 | 20.76 |
Annual Sum or Average | 8153.83 | 21.30 | 2229.67 | 20.84 | 2141.50 | 20.75 |
Minimum of Months | 598.83 | 21.09 | 18.50 | 20.59 | 4.67 | 20.58 |
Maximum of Months | 738.50 | 21.55 | 481.33 | 22.82 | 481.33 | 21.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 507.00 | 20.67 | 507.00 | 20.67 |
February | 672.00 | 20.87 | 453.00 | 20.65 | 453.00 | 20.65 |
March | 743.00 | 21.07 | 386.17 | 20.68 | 386.17 | 20.68 |
April | 718.17 | 21.13 | 253.67 | 20.60 | 253.67 | 20.60 |
May | 720.17 | 21.55 | 26.83 | 21.14 | 25.00 | 21.01 |
June | 605.00 | 21.44 | 32.17 | 22.81 | 4.50 | 21.41 |
July | 617.67 | 21.42 | 37.67 | 22.22 | 19.67 | 21.39 |
August | 645.50 | 21.47 | 24.67 | 22.31 | 9.67 | 21.34 |
September | 678.67 | 21.55 | 18.83 | 21.34 | 15.00 | 20.94 |
October | 738.50 | 21.19 | 231.00 | 20.62 | 231.00 | 20.62 |
November | 720.00 | 20.99 | 387.67 | 20.69 | 387.67 | 20.69 |
December | 744.00 | 20.78 | 631.17 | 20.66 | 631.17 | 20.66 |
Annual Sum or Average | 8346.67 | 21.18 | 2989.83 | 20.72 | 2923.50 | 20.67 |
Minimum of Months | 605.00 | 20.78 | 18.83 | 20.60 | 4.50 | 20.60 |
Maximum of Months | 744.00 | 21.55 | 631.17 | 22.81 | 631.17 | 21.41 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 646.00 | 21.27 | 126.33 | 21.17 | 108.50 | 20.81 |
February | 599.33 | 21.22 | 189.67 | 20.80 | 186.50 | 20.76 |
March | 697.33 | 21.25 | 184.67 | 20.65 | 184.67 | 20.65 |
April | 717.83 | 21.32 | 165.83 | 20.69 | 165.83 | 20.69 |
May | 741.83 | 21.62 | 9.50 | 21.05 | 9.50 | 21.05 |
June | 669.33 | 21.59 | 1.17 | 21.86 | 1.17 | 21.86 |
July | 665.00 | 21.53 | 4.00 | 22.06 | 4.00 | 22.06 |
August | 639.67 | 21.45 | 6.83 | 22.85 | 1.50 | 21.13 |
September | 615.17 | 21.43 | 8.83 | 22.88 | 1.50 | 20.64 |
October | 646.33 | 21.16 | 121.00 | 20.73 | 110.50 | 20.48 |
November | 625.50 | 21.27 | 130.00 | 21.18 | 109.50 | 20.78 |
December | 680.50 | 21.27 | 237.33 | 20.92 | 234.67 | 20.89 |
Annual Sum or Average | 7943.83 | 21.37 | 1185.17 | 20.89 | 1117.83 | 20.75 |
Minimum of Months | 599.33 | 21.16 | 1.17 | 20.65 | 1.17 | 20.48 |
Maximum of Months | 741.83 | 21.62 | 237.33 | 22.88 | 234.67 | 22.06 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 5.50 | 21.00 | 5.50 | 21.00 |
February | 672.00 | 21.32 | 3.50 | 21.01 | 3.50 | 21.01 |
March | 744.00 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.20 | 4.50 | 21.73 | 4.50 | 21.73 |
July | 744.00 | 21.15 | 2.17 | 21.37 | 2.17 | 21.37 |
August | 744.00 | 21.16 | 7.83 | 21.51 | 7.83 | 21.51 |
September | 720.00 | 21.26 | 1.00 | 21.56 | 1.00 | 21.56 |
October | 744.00 | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.29 | 75.17 | 21.00 | 75.17 | 21.00 |
Annual Sum or Average | 8760.00 | 21.32 | 99.67 | 21.09 | 99.67 | 21.09 |
Minimum of Months | 672.00 | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.46 | 75.17 | 21.73 | 75.17 | 21.73 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 672.00 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 744.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 719.83 | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 742.33 | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 719.83 | 21.21 | 3.00 | 21.81 | 3.00 | 21.81 |
July | 744.00 | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.16 | 3.17 | 21.52 | 3.17 | 21.52 |
September | 720.00 | 21.28 | 0.83 | 21.56 | 0.83 | 21.56 |
October | 744.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.33 | 21.00 | 21.00 | 21.00 | 21.00 |
Annual Sum or Average | 8758.00 | 21.36 | 28.00 | 21.16 | 28.00 | 21.16 |
Minimum of Months | 672.00 | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.50 | 21.00 | 21.81 | 21.00 | 21.81 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 583.33 | 22.92 | 528.33 | 23.54 | 394.33 | 23.81 |
February | 528.50 | 22.94 | 474.67 | 23.60 | 353.17 | 23.88 |
March | 587.33 | 22.91 | 535.17 | 23.51 | 402.67 | 23.77 |
April | 567.00 | 22.90 | 524.33 | 23.45 | 394.33 | 23.71 |
May | 584.83 | 22.59 | 557.50 | 22.96 | 423.00 | 23.19 |
June | 531.17 | 22.23 | 549.33 | 22.35 | 411.00 | 22.58 |
July | 532.67 | 22.19 | 569.17 | 22.26 | 412.00 | 22.54 |
August | 527.33 | 22.26 | 571.00 | 22.32 | 417.33 | 22.59 |
September | 520.00 | 22.23 | 529.17 | 22.50 | 364.83 | 22.75 |
October | 570.83 | 22.80 | 539.83 | 23.33 | 392.17 | 23.61 |
November | 558.83 | 22.91 | 516.17 | 23.50 | 379.50 | 23.79 |
December | 526.00 | 22.74 | 512.17 | 23.42 | 326.67 | 23.77 |
Annual Sum or Average | 6617.83 | 22.64 | 6406.83 | 23.04 | 4671.00 | 23.31 |
Minimum of Months | 520.00 | 22.19 | 474.67 | 22.26 | 326.67 | 22.54 |
Maximum of Months | 587.33 | 22.94 | 571.00 | 23.60 | 423.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06356 | 22.13004 | -0.4737 | 9.75793 |
February | 672.00000 | 21.04732 | 19.95036 | -0.4967 | 10.22239 |
March | 744.00000 | 20.98739 | 20.25715 | -0.5147 | 10.63518 |
April | 720.00000 | 20.98238 | 25.49144 | -0.4841 | 9.99477 |
May | 744.00000 | 20.83867 | 32.13206 | -1.6939 | 61.35012 |
June | 720.00000 | 20.68869 | 39.89985 | -1.6868 | 60.93997 |
July | 744.00000 | 20.66932 | 41.96382 | -1.6790 | 60.53971 |
August | 744.00000 | 20.84023 | 41.90056 | -1.6052 | 56.59368 |
September | 720.00000 | 20.98872 | 30.98535 | -1.6018 | 56.43026 |
October | 744.00000 | 21.25202 | 23.63635 | -0.3970 | 8.40756 |
November | 720.00000 | 21.27888 | 23.74541 | -0.3912 | 8.30581 |
December | 744.00000 | 21.21284 | 16.06526 | -0.4566 | 9.44096 |
Annual Sum or Average | 8760.00000 | 20.98704 | 28.22716 | -0.9596 | 30.34200 |
Minimum of Months | 672.00000 | 20.66932 | 16.06526 | -1.6939 | 8.30581 |
Maximum of Months | 744.00000 | 21.27888 | 41.96382 | -0.3912 | 61.35012 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41241 | 21.32061 | -0.3506 | 9.96509 |
February | 672.00000 | 21.35296 | 19.23196 | -0.4035 | 10.58103 |
March | 744.00000 | 21.17072 | 19.72485 | -0.4476 | 10.24770 |
April | 720.00000 | 21.01071 | 25.05072 | -0.4830 | 10.20185 |
May | 744.00000 | 21.00085 | 31.46663 | -1.5536 | 53.81369 |
June | 720.00000 | 21.00093 | 38.90824 | -1.4169 | 46.47832 |
July | 744.00000 | 21.00073 | 40.95934 | -1.4003 | 45.60545 |
August | 744.00000 | 21.01384 | 41.21307 | -1.3891 | 45.04235 |
September | 720.00000 | 21.10603 | 30.44171 | -1.4220 | 47.16184 |
October | 744.00000 | 21.28760 | 23.25844 | -0.3623 | 9.35925 |
November | 720.00000 | 21.41736 | 23.20466 | -0.3323 | 9.68436 |
December | 744.00000 | 21.25622 | 15.56742 | -0.4576 | 11.89125 |
Annual Sum or Average | 8760.00000 | 21.16807 | 27.57665 | -0.8376 | 25.93350 |
Minimum of Months | 672.00000 | 21.00073 | 15.56742 | -1.5536 | 9.35925 |
Maximum of Months | 744.00000 | 21.41736 | 41.21307 | -0.3323 | 53.81369 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06065 | 22.47289 | -0.4358 | 9.06166 |
February | 672.00000 | 21.05578 | 20.27568 | -0.4563 | 9.45380 |
March | 744.00000 | 21.07302 | 20.54923 | -0.4466 | 9.24602 |
April | 720.00000 | 21.05838 | 25.74842 | -0.4237 | 8.86727 |
May | 744.00000 | 21.05406 | 32.11974 | -1.5376 | 52.95753 |
June | 720.00000 | 21.01292 | 39.58591 | -1.4805 | 49.86832 |
July | 744.00000 | 21.00831 | 41.58205 | -1.4721 | 49.40657 |
August | 744.00000 | 21.00926 | 41.91082 | -1.4695 | 49.27123 |
September | 720.00000 | 21.03137 | 31.27553 | -1.5273 | 52.39624 |
October | 744.00000 | 21.08426 | 24.21899 | -0.4119 | 8.64930 |
November | 720.00000 | 21.07006 | 24.36721 | -0.4193 | 8.77034 |
December | 744.00000 | 21.04548 | 16.54439 | -0.4853 | 10.01883 |
Annual Sum or Average | 8760.00000 | 21.04693 | 28.43390 | -0.8831 | 26.59922 |
Minimum of Months | 672.00000 | 21.00831 | 16.54439 | -1.5376 | 8.64930 |
Maximum of Months | 744.00000 | 21.08426 | 41.91082 | -0.4119 | 52.95753 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.49063 | 20.17684 | 0.24796 | 9.35885 |
February | 672.00000 | 21.48974 | 17.99873 | 0.23160 | 9.24098 |
March | 744.00000 | 21.47250 | 18.30164 | 0.24364 | 9.36302 |
April | 720.00000 | 21.43474 | 23.41686 | 0.26440 | 9.47815 |
May | 744.00000 | 21.22264 | 30.02818 | -0.6113 | 18.12878 |
June | 720.00000 | 20.79683 | 38.21839 | -0.6647 | 18.40041 |
July | 744.00000 | 20.72290 | 40.45024 | -0.6800 | 18.79878 |
August | 744.00000 | 20.76233 | 40.66512 | -0.6656 | 18.45339 |
September | 720.00000 | 20.93320 | 29.66064 | -0.6890 | 19.43077 |
October | 744.00000 | 21.41450 | 21.98851 | 0.25816 | 9.37267 |
November | 720.00000 | 21.48033 | 22.03880 | 0.26301 | 9.57288 |
December | 744.00000 | 21.47055 | 14.38212 | 0.19852 | 8.84826 |
Annual Sum or Average | 8760.00000 | 21.22275 | 26.49254 | -0.1358 | 13.22534 |
Minimum of Months | 672.00000 | 20.72290 | 14.38212 | -0.6890 | 8.84826 |
Maximum of Months | 744.00000 | 21.49063 | 40.66512 | 0.26440 | 19.43077 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34046 | 23.94719 | -0.2747 | 8.33927 |
February | 672.00000 | 21.29498 | 21.84546 | -0.3250 | 8.88262 |
March | 744.00000 | 21.14652 | 22.29116 | -0.3636 | 8.47036 |
April | 720.00000 | 21.02738 | 27.56663 | -0.3913 | 8.47911 |
May | 744.00000 | 21.02019 | 33.96305 | -1.4370 | 47.55288 |
June | 720.00000 | 21.00430 | 41.40267 | -1.3133 | 41.03049 |
July | 744.00000 | 21.00353 | 43.42098 | -1.2956 | 40.13632 |
August | 744.00000 | 21.00345 | 43.72029 | -1.2867 | 39.69480 |
September | 720.00000 | 21.04427 | 33.06671 | -1.3321 | 42.22462 |
October | 744.00000 | 21.23586 | 25.85289 | -0.2864 | 7.80059 |
November | 720.00000 | 21.35221 | 25.81359 | -0.2554 | 8.12228 |
December | 744.00000 | 21.25090 | 18.16341 | -0.3674 | 9.57991 |
Annual Sum or Average | 8760.00000 | 21.14283 | 30.13504 | -0.7466 | 22.61152 |
Minimum of Months | 672.00000 | 21.00345 | 18.16341 | -1.4370 | 7.80059 |
Maximum of Months | 744.00000 | 21.35221 | 43.72029 | -0.2554 | 47.55288 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12322 | 23.78856 | -0.3804 | 8.16144 |
February | 672.00000 | 21.10239 | 21.61858 | -0.4071 | 8.60865 |
March | 744.00000 | 21.13808 | 21.89208 | -0.3968 | 8.39176 |
April | 720.00000 | 21.12115 | 27.05365 | -0.3789 | 8.15591 |
May | 744.00000 | 21.12645 | 33.40089 | -1.4692 | 49.27238 |
June | 720.00000 | 21.02748 | 40.95530 | -1.4222 | 46.74031 |
July | 744.00000 | 21.01885 | 42.96419 | -1.4118 | 46.18053 |
August | 744.00000 | 21.01917 | 43.29071 | -1.4088 | 46.01975 |
September | 720.00000 | 21.07728 | 32.62028 | -1.4541 | 48.44231 |
October | 744.00000 | 21.16620 | 25.52207 | -0.3550 | 7.78035 |
November | 720.00000 | 21.15140 | 25.65350 | -0.3595 | 7.85156 |
December | 744.00000 | 21.09866 | 17.89854 | -0.4339 | 9.08672 |
Annual Sum or Average | 8760.00000 | 21.09752 | 29.76786 | -0.8257 | 24.65322 |
Minimum of Months | 672.00000 | 21.01885 | 17.89854 | -1.4692 | 7.78035 |
Maximum of Months | 744.00000 | 21.16620 | 43.29071 | -0.3550 | 49.27238 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35168 | 26.09707 | -0.4320 | 10.15493 |
February | 672.00000 | 21.26071 | 23.88273 | -0.4755 | 11.19096 |
March | 744.00000 | 21.27336 | 24.87932 | -0.4430 | 10.35305 |
April | 720.00000 | 21.23970 | 29.88176 | -0.4282 | 9.88982 |
May | 744.00000 | 21.58467 | 35.59565 | -1.3766 | 45.09649 |
June | 720.00000 | 21.69918 | 40.50286 | -1.2071 | 36.91938 |
July | 744.00000 | 21.70162 | 42.39855 | -1.2069 | 36.88797 |
August | 744.00000 | 21.69218 | 42.54471 | -1.2108 | 37.08034 |
September | 720.00000 | 21.66861 | 34.18422 | -1.2925 | 41.19971 |
October | 744.00000 | 21.37697 | 28.53159 | -0.3727 | 9.47789 |
November | 720.00000 | 21.36562 | 28.15146 | -0.4060 | 9.81547 |
December | 744.00000 | 21.17844 | 20.40880 | -0.5411 | 12.57142 |
Annual Sum or Average | 8760.00000 | 21.45047 | 31.46425 | -0.7847 | 22.62565 |
Minimum of Months | 672.00000 | 21.17844 | 20.40880 | -1.3766 | 9.47789 |
Maximum of Months | 744.00000 | 21.70162 | 42.54471 | -0.3727 | 45.09649 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.93668 | 26.65503 | -0.5840 | 12.80349 |
February | 672.00000 | 20.90937 | 24.29053 | -0.6040 | 13.53275 |
March | 744.00000 | 21.09410 | 25.05602 | -0.5146 | 11.39313 |
April | 720.00000 | 21.14626 | 30.02474 | -0.4621 | 10.32521 |
May | 744.00000 | 21.55895 | 35.65729 | -1.3924 | 45.83911 |
June | 720.00000 | 21.69811 | 40.54209 | -1.2103 | 37.03419 |
July | 744.00000 | 21.69931 | 42.47942 | -1.2122 | 37.09393 |
August | 744.00000 | 21.67764 | 42.78111 | -1.2314 | 37.93375 |
September | 720.00000 | 21.61197 | 34.34504 | -1.3467 | 43.62415 |
October | 744.00000 | 21.19277 | 28.75034 | -0.4529 | 10.23817 |
November | 720.00000 | 21.03532 | 28.61979 | -0.5344 | 11.73478 |
December | 744.00000 | 20.85788 | 20.73517 | -0.6662 | 15.14504 |
Annual Sum or Average | 8760.00000 | 21.28699 | 31.70310 | -0.8526 | 23.95702 |
Minimum of Months | 672.00000 | 20.85788 | 20.73517 | -1.3924 | 10.23817 |
Maximum of Months | 744.00000 | 21.69931 | 42.78111 | -0.4529 | 45.83911 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.07132 | 24.51012 | -0.5191 | 10.89618 |
February | 672.00000 | 21.03236 | 22.17535 | -0.5463 | 11.57120 |
March | 744.00000 | 21.21584 | 22.90698 | -0.4728 | 9.84673 |
April | 720.00000 | 21.29429 | 27.89628 | -0.4132 | 8.80829 |
May | 744.00000 | 21.53135 | 33.67595 | -1.4292 | 47.37333 |
June | 720.00000 | 21.64636 | 38.95035 | -1.3161 | 41.70507 |
July | 744.00000 | 21.65849 | 40.89345 | -1.2975 | 40.82152 |
August | 744.00000 | 21.62096 | 40.80080 | -1.3256 | 42.12404 |
September | 720.00000 | 21.55227 | 32.49508 | -1.4188 | 46.86256 |
October | 744.00000 | 21.27186 | 26.70560 | -0.4279 | 9.12302 |
November | 720.00000 | 21.14088 | 26.52729 | -0.4821 | 10.08867 |
December | 744.00000 | 20.99193 | 18.63222 | -0.5835 | 12.57232 |
Annual Sum or Average | 8760.00000 | 21.33735 | 29.72290 | -0.8546 | 24.39288 |
Minimum of Months | 672.00000 | 20.99193 | 18.63222 | -1.4292 | 8.80829 |
Maximum of Months | 744.00000 | 21.65849 | 40.89345 | -0.4132 | 47.37333 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38812 | 26.06745 | -0.4266 | 10.02442 |
February | 672.00000 | 21.30870 | 23.84501 | -0.4637 | 11.07480 |
March | 744.00000 | 21.34821 | 24.82739 | -0.4208 | 10.05660 |
April | 720.00000 | 21.33034 | 29.76854 | -0.3980 | 9.55040 |
May | 744.00000 | 21.66457 | 35.34889 | -1.3387 | 43.26097 |
June | 720.00000 | 21.74302 | 40.12894 | -1.1795 | 35.69143 |
July | 744.00000 | 21.73762 | 41.95063 | -1.1735 | 35.44051 |
August | 744.00000 | 21.73897 | 41.94829 | -1.1769 | 35.64258 |
September | 720.00000 | 21.71156 | 34.04716 | -1.2681 | 40.06593 |
October | 744.00000 | 21.41966 | 28.48677 | -0.3641 | 9.40161 |
November | 720.00000 | 21.37797 | 28.14638 | -0.4077 | 9.82231 |
December | 744.00000 | 21.19872 | 20.38760 | -0.5374 | 12.44951 |
Annual Sum or Average | 8760.00000 | 21.49836 | 31.28745 | -0.7648 | 21.94126 |
Minimum of Months | 672.00000 | 21.19872 | 20.38760 | -1.3387 | 9.40161 |
Maximum of Months | 744.00000 | 21.74302 | 41.95063 | -0.3641 | 43.26097 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92598 | 26.65313 | -0.5887 | 12.78733 |
February | 672.00000 | 20.94856 | 24.19497 | -0.5935 | 13.35005 |
March | 744.00000 | 21.19941 | 24.94374 | -0.4856 | 10.87144 |
April | 720.00000 | 21.26380 | 29.86313 | -0.4264 | 9.88155 |
May | 744.00000 | 21.64804 | 35.39541 | -1.3520 | 43.87823 |
June | 720.00000 | 21.74243 | 40.17921 | -1.1828 | 35.82143 |
July | 744.00000 | 21.73665 | 42.03555 | -1.1785 | 35.63554 |
August | 744.00000 | 21.73558 | 42.13150 | -1.1936 | 36.31753 |
September | 720.00000 | 21.68912 | 34.10848 | -1.3115 | 41.95643 |
October | 744.00000 | 21.27311 | 28.61901 | -0.4371 | 10.02798 |
November | 720.00000 | 21.00475 | 28.64952 | -0.5455 | 11.88802 |
December | 744.00000 | 20.83578 | 20.72322 | -0.6713 | 15.16989 |
Annual Sum or Average | 8760.00000 | 21.33576 | 31.49868 | -0.8321 | 23.19329 |
Minimum of Months | 672.00000 | 20.83578 | 20.72322 | -1.3520 | 9.88155 |
Maximum of Months | 744.00000 | 21.74243 | 42.13150 | -0.4264 | 43.87823 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29348 | 26.40334 | -0.4776 | 11.32041 |
February | 672.00000 | 21.21879 | 24.12188 | -0.5162 | 12.39006 |
March | 744.00000 | 21.23590 | 25.15846 | -0.4704 | 11.26905 |
April | 720.00000 | 21.21101 | 30.20633 | -0.4496 | 10.70077 |
May | 744.00000 | 21.61397 | 35.76919 | -1.3530 | 44.23270 |
June | 720.00000 | 21.71681 | 40.42122 | -1.1545 | 34.87867 |
July | 744.00000 | 21.71707 | 42.26167 | -1.1577 | 34.96455 |
August | 744.00000 | 21.70623 | 42.48395 | -1.1625 | 35.22408 |
September | 720.00000 | 21.67213 | 34.32757 | -1.2653 | 40.24797 |
October | 744.00000 | 21.35417 | 28.84325 | -0.3911 | 10.21790 |
November | 720.00000 | 21.32394 | 28.49094 | -0.4407 | 10.80025 |
December | 744.00000 | 21.10545 | 20.62482 | -0.5971 | 14.20247 |
Annual Sum or Average | 8760.00000 | 21.43194 | 31.63474 | -0.7881 | 22.60306 |
Minimum of Months | 672.00000 | 21.10545 | 20.62482 | -1.3530 | 10.21790 |
Maximum of Months | 744.00000 | 21.71707 | 42.48395 | -0.3911 | 44.23270 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86480 | 26.99542 | -0.6386 | 14.34988 |
February | 672.00000 | 20.87326 | 24.53423 | -0.6485 | 14.88610 |
March | 744.00000 | 21.07199 | 25.31794 | -0.5417 | 12.35876 |
April | 720.00000 | 21.13287 | 30.32972 | -0.4817 | 11.11750 |
May | 744.00000 | 21.59861 | 35.81299 | -1.3665 | 44.84009 |
June | 720.00000 | 21.71725 | 40.45965 | -1.1570 | 34.95625 |
July | 744.00000 | 21.71671 | 42.33468 | -1.1622 | 35.12369 |
August | 744.00000 | 21.69964 | 42.70306 | -1.1804 | 35.91426 |
September | 720.00000 | 21.63655 | 34.44663 | -1.3144 | 42.34550 |
October | 744.00000 | 21.19970 | 29.02800 | -0.4688 | 10.94516 |
November | 720.00000 | 20.99390 | 28.97027 | -0.5751 | 12.90942 |
December | 744.00000 | 20.78313 | 20.97538 | -0.7271 | 17.07625 |
Annual Sum or Average | 8760.00000 | 21.27627 | 31.86668 | -0.8566 | 23.96034 |
Minimum of Months | 672.00000 | 20.78313 | 20.97538 | -1.3665 | 10.94516 |
Maximum of Months | 744.00000 | 21.71725 | 42.70306 | -0.4688 | 44.84009 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53803 | 27.02202 | -0.3139 | 9.22980 |
February | 672.00000 | 21.44460 | 24.94151 | -0.3758 | 10.29385 |
March | 744.00000 | 21.37915 | 25.82426 | -0.3946 | 10.01112 |
April | 720.00000 | 21.32485 | 30.55490 | -0.4078 | 9.72835 |
May | 744.00000 | 21.62437 | 35.91458 | -1.3752 | 45.14639 |
June | 720.00000 | 21.70848 | 40.51713 | -1.2301 | 38.06692 |
July | 744.00000 | 21.71334 | 42.18883 | -1.2106 | 37.19928 |
August | 744.00000 | 21.70710 | 41.99471 | -1.2072 | 37.14890 |
September | 720.00000 | 21.69538 | 34.30549 | -1.2578 | 39.95674 |
October | 744.00000 | 21.44124 | 29.37420 | -0.3194 | 9.30813 |
November | 720.00000 | 21.53979 | 29.02426 | -0.2982 | 9.01593 |
December | 744.00000 | 21.44992 | 21.54745 | -0.4072 | 10.71015 |
Annual Sum or Average | 8760.00000 | 21.54781 | 31.97332 | -0.7354 | 22.22639 |
Minimum of Months | 672.00000 | 21.32485 | 21.54745 | -1.3752 | 9.01593 |
Maximum of Months | 744.00000 | 21.71334 | 42.18883 | -0.2982 | 45.14639 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32747 | 24.37769 | -0.3212 | 7.44284 |
February | 672.00000 | 21.32073 | 22.22132 | -0.3361 | 7.64801 |
March | 744.00000 | 21.42073 | 22.42716 | -0.2840 | 6.96783 |
April | 720.00000 | 21.44700 | 27.44024 | -0.2373 | 6.54008 |
May | 744.00000 | 21.46080 | 33.66063 | -1.2354 | 37.27408 |
June | 720.00000 | 21.20172 | 41.34963 | -1.2083 | 35.81073 |
July | 744.00000 | 21.14667 | 43.43700 | -1.2150 | 36.11697 |
August | 744.00000 | 21.15625 | 43.73391 | -1.2198 | 36.34619 |
September | 720.00000 | 21.26384 | 33.13774 | -1.2822 | 39.51056 |
October | 744.00000 | 21.42977 | 26.01070 | -0.2509 | 6.62077 |
November | 720.00000 | 21.36785 | 26.21681 | -0.2881 | 7.00919 |
December | 744.00000 | 21.28941 | 18.57780 | -0.3802 | 8.35384 |
Annual Sum or Average | 8760.00000 | 21.31933 | 30.26165 | -0.6904 | 19.70701 |
Minimum of Months | 672.00000 | 21.14667 | 18.57780 | -1.2822 | 6.54008 |
Maximum of Months | 744.00000 | 21.46080 | 43.73391 | -0.2373 | 39.51056 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37405 | 24.13240 | -0.2771 | 6.92721 |
February | 672.00000 | 21.36906 | 21.97839 | -0.2912 | 7.09656 |
March | 744.00000 | 21.47531 | 22.17692 | -0.2378 | 6.50085 |
April | 720.00000 | 21.50400 | 27.17064 | -0.1905 | 6.15802 |
May | 744.00000 | 21.50248 | 33.39696 | -1.1760 | 34.43158 |
June | 720.00000 | 21.21146 | 41.13373 | -1.1632 | 33.65737 |
July | 744.00000 | 21.15475 | 43.22527 | -1.1711 | 34.00640 |
August | 744.00000 | 21.16402 | 43.52180 | -1.1759 | 34.22800 |
September | 720.00000 | 21.28138 | 32.91618 | -1.2341 | 37.11805 |
October | 744.00000 | 21.47781 | 25.75631 | -0.2073 | 6.23502 |
November | 720.00000 | 21.41806 | 25.96154 | -0.2436 | 6.55170 |
December | 744.00000 | 21.33291 | 18.34948 | -0.3357 | 7.71845 |
Annual Sum or Average | 8760.00000 | 21.35535 | 30.02244 | -0.6441 | 18.45132 |
Minimum of Months | 672.00000 | 21.15475 | 18.34948 | -1.2341 | 6.15802 |
Maximum of Months | 744.00000 | 21.50400 | 43.52180 | -0.1905 | 37.11805 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.83937 | 23.99691 | 0.70600 | 21.16769 |
February | 672.00000 | 22.87462 | 22.05643 | 0.70001 | 21.20847 |
March | 744.00000 | 22.83753 | 22.34958 | 0.72515 | 21.56119 |
April | 720.00000 | 22.81100 | 26.96874 | 0.75350 | 22.34135 |
May | 744.00000 | 22.48731 | 33.23980 | 0.07791 | 14.34018 |
June | 720.00000 | 22.03121 | 40.97558 | 0.05778 | 12.76903 |
July | 744.00000 | 21.96955 | 42.96699 | 0.04418 | 12.62615 |
August | 744.00000 | 22.02035 | 43.17193 | 0.05626 | 12.61615 |
September | 720.00000 | 22.11633 | 33.18550 | -0.0138 | 12.85571 |
October | 744.00000 | 22.72511 | 25.81396 | 0.72991 | 21.35835 |
November | 720.00000 | 22.82522 | 25.71764 | 0.72499 | 21.63911 |
December | 744.00000 | 22.72343 | 18.90251 | 0.62174 | 18.59896 |
Annual Sum or Average | 8760.00000 | 22.51968 | 29.99095 | 0.43033 | 17.73239 |
Minimum of Months | 672.00000 | 21.96955 | 18.90251 | -0.0138 | 12.61615 |
Maximum of Months | 744.00000 | 22.87462 | 43.17193 | 0.75350 | 22.34135 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.263690E+11 | 110373.73 | 23-JAN-16:01 | 472.34 | 0.807901E+11 | 0.00 | 0.107159E+12 | 1.88 | 4.08 | 20-JAN-16:01 | 0.00 | 0.00 |
February | 0.188462E+11 | 98758.88 | 18-FEB-16:01 | 362.93 | 0.569715E+11 | 0.00 | 0.758177E+11 | 1.60 | 3.96 | 18-FEB-16:01 | 0.00 | 0.00 |
March | 0.373240E+11 | 146033.86 | 13-MAR-15:01 | 505.27 | 0.117767E+12 | 0.00 | 0.155091E+12 | 2.03 | 4.04 | 15-MAR-15:01 | 0.00 | 0.00 |
April | 0.364865E+11 | 126561.86 | 27-APR-15:01 | 523.17 | 0.113314E+12 | 0.00 | 0.149800E+12 | 2.16 | 3.98 | 19-APR-18:01 | 0.00 | 0.00 |
May | 0.108274E+12 | 164743.20 | 16-MAY-15:01 | 734.17 | 0.351391E+12 | 0.00 | 0.459665E+12 | 3.03 | 4.00 | 18-MAY-08:61 | 0.00 | 0.00 |
June | 0.262172E+12 | 286680.93 | 26-JUN-15:03 | 720.00 | 0.861307E+12 | 0.00 | 0.112348E+13 | 3.27 | 4.33 | 18-JUN-08:62 | 0.00 | 0.00 |
July | 0.292546E+12 | 242489.27 | 16-JUL-15:03 | 744.00 | 0.990844E+12 | 0.00 | 0.128339E+13 | 3.38 | 4.41 | 30-JUL-18:01 | 0.00 | 0.00 |
August | 0.266793E+12 | 250730.02 | 16-AUG-15:03 | 744.00 | 0.894789E+12 | 0.00 | 0.116158E+13 | 3.32 | 4.32 | 04-AUG-02:00 | 0.00 | 0.00 |
September | 0.192141E+12 | 204985.72 | 10-SEP-15:03 | 714.03 | 0.636788E+12 | 0.00 | 0.828928E+12 | 3.18 | 4.13 | 01-SEP-18:01 | 0.00 | 0.00 |
October | 0.581353E+11 | 165733.08 | 11-OCT-15:01 | 582.77 | 0.187745E+12 | 0.00 | 0.245880E+12 | 2.37 | 4.05 | 08-OCT-15:01 | 0.00 | 0.00 |
November | 0.324044E+11 | 134050.09 | 05-NOV-15:01 | 480.05 | 0.101882E+12 | 0.00 | 0.134286E+12 | 1.99 | 4.03 | 07-NOV-16:01 | 0.00 | 0.00 |
December | 0.224326E+11 | 105416.99 | 02-DEC-15:00 | 386.38 | 0.703469E+11 | 0.00 | 0.927795E+11 | 1.55 | 3.94 | 17-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.135392E+13 | 6969.11 | 0.446394E+13 | 0.581786E+13 | 2.49 | |||||||
Minimum of Months | 0.188462E+11 | 98758.88 | 362.93 | 0.569715E+11 | 0.00 | 0.758177E+11 | 1.55 | 3.94 | 0.00 | 0.00 | ||
Maximum of Months | 0.292546E+12 | 286680.93 | 744.00 | 0.990844E+12 | 0.00 | 0.128339E+13 | 3.38 | 4.41 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.184461E+12 | 0.00 | 744.00 | 339718.33 | 05-JAN-09:03 | 0.00 | 48.98 | 60.00 | 1.54 | 0.00 | 0.12 | 0.59 | 05-JAN-09:03 |
February | 0.183597E+12 | 0.00 | 672.00 | 297733.29 | 12-FEB-07:10 | 0.00 | 49.08 | 60.00 | 1.74 | 0.00 | 0.13 | 0.52 | 12-FEB-07:10 |
March | 0.153384E+12 | 0.00 | 744.00 | 276066.40 | 19-MAR-08:03 | 0.00 | 48.64 | 60.00 | 1.29 | 0.00 | 0.10 | 0.48 | 19-MAR-08:03 |
April | 0.138600E+12 | 0.00 | 720.00 | 204745.04 | 03-APR-08:62 | 0.00 | 48.35 | 60.00 | 1.18 | 0.00 | 0.09 | 0.36 | 03-APR-08:62 |
May | 0.113714E+12 | 0.00 | 744.00 | 107280.39 | 04-MAY-08:03 | 0.00 | 47.26 | 60.00 | 0.87 | 0.00 | 0.07 | 0.19 | 04-MAY-08:03 |
June | 0.116405E+12 | 0.00 | 720.00 | 113807.38 | 13-JUN-08:04 | 0.00 | 48.44 | 60.00 | 0.97 | 0.00 | 0.08 | 0.20 | 13-JUN-08:04 |
July | 0.124320E+12 | 0.00 | 744.00 | 131703.97 | 10-JUL-08:04 | 0.00 | 48.40 | 60.00 | 1.01 | 0.00 | 0.08 | 0.23 | 10-JUL-08:04 |
August | 0.117408E+12 | 0.00 | 744.00 | 121849.76 | 11-AUG-08:04 | 0.00 | 47.33 | 60.00 | 0.92 | 0.00 | 0.08 | 0.21 | 11-AUG-08:04 |
September | 0.103325E+12 | 0.00 | 720.00 | 144411.52 | 18-SEP-08:03 | 0.00 | 46.44 | 60.00 | 0.81 | 0.00 | 0.07 | 0.25 | 18-SEP-08:03 |
October | 0.129329E+12 | 0.00 | 744.00 | 251097.45 | 30-OCT-08:03 | 0.00 | 47.73 | 60.00 | 1.06 | 0.00 | 0.08 | 0.44 | 30-OCT-08:03 |
November | 0.142244E+12 | 0.00 | 720.00 | 243263.85 | 29-NOV-09:03 | 0.00 | 48.78 | 60.00 | 1.25 | 0.00 | 0.10 | 0.42 | 29-NOV-09:03 |
December | 0.255712E+12 | 0.00 | 744.00 | 384873.80 | 21-DEC-09:06 | 0.00 | 48.96 | 60.00 | 2.14 | 0.00 | 0.17 | 0.67 | 21-DEC-09:06 |
Annual Sum or Average | 0.176250E+13 | 8760.00 | 48.19 | 60.00 | 1.23 | 0.00 | 0.10 | ||||||
Minimum of Months | 0.103325E+12 | 0.00 | 672.00 | 107280.39 | 0.00 | 46.44 | 60.00 | 0.81 | 0.00 | 0.07 | 0.19 | ||
Maximum of Months | 0.255712E+12 | 0.00 | 744.00 | 384873.80 | 0.00 | 49.08 | 60.00 | 2.14 | 0.00 | 0.17 | 0.67 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.134985E+10 | 0.00 | 212.77 | 0.134616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21629.10 | 10-JAN-16:01 | 21629.10 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.136334E+10 | 0.00 | 186.19 | 0.136168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21604.42 | 23-FEB-16:01 | 21604.42 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.247013E+10 | 0.00 | 286.41 | 0.246700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21619.37 | 25-MAR-18:01 | 21619.37 | 25-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.175860E+10 | 0.00 | 250.03 | 0.163022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21630.12 | 26-APR-15:01 | 21630.12 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.391587E+10 | 0.00 | 517.80 | 0.305291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21627.70 | 27-MAY-18:01 | 21627.70 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.825506E+10 | 0.00 | 657.30 | 0.606944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22134.80 | 18-JUN-08:62 | 21633.75 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.799495E+10 | 0.00 | 681.13 | 0.541698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22552.86 | 27-JUL-18:01 | 21634.91 | 06-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.793032E+10 | 0.00 | 680.19 | 0.538732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22013.06 | 05-AUG-08:61 | 21635.32 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.627977E+10 | 0.00 | 626.81 | 0.521283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21632.29 | 14-SEP-15:01 | 21632.29 | 14-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.329171E+10 | 0.00 | 368.60 | 0.320361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21639.76 | 03-OCT-15:01 | 21639.76 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.182444E+10 | 0.00 | 254.18 | 0.181053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21617.13 | 12-NOV-16:01 | 21617.13 | 12-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.964346E+09 | 0.00 | 158.93 | 0.964346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21583.96 | 29-DEC-16:01 | 21583.96 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473984E+11 | 4880.33 | 0.379230E+11 | ||||||||||||
Minimum of Months | 0.964346E+09 | 0.00 | 158.93 | 0.964346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21583.96 | 21583.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.825506E+10 | 0.00 | 681.13 | 0.606944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22552.86 | 21639.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.284285E+09 | 0.00 | 64.93 | 0.284285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21386.10 | 22-JAN-16:01 | 21386.10 | 22-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.421459E+09 | 0.00 | 74.07 | 0.421270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21386.17 | 23-FEB-16:01 | 21386.17 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.141956E+10 | 0.00 | 193.04 | 0.141895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21401.43 | 25-MAR-18:01 | 21401.43 | 25-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.135255E+10 | 0.00 | 198.09 | 0.124409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21412.42 | 26-APR-15:01 | 21412.42 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.366306E+10 | 0.00 | 497.57 | 0.283000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21409.79 | 27-MAY-18:01 | 21409.79 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.812202E+10 | 0.00 | 654.78 | 0.596728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21881.81 | 18-JUN-08:62 | 21415.92 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.777615E+10 | 0.00 | 676.85 | 0.526212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22280.50 | 27-JUL-18:01 | 21416.92 | 06-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.722382E+10 | 0.00 | 664.00 | 0.485959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21743.72 | 05-AUG-08:61 | 21417.35 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.495653E+10 | 0.00 | 575.09 | 0.401186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21414.59 | 14-SEP-15:01 | 21414.59 | 14-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.176302E+10 | 0.00 | 232.19 | 0.171433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21420.60 | 03-OCT-15:01 | 21420.60 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.481408E+09 | 0.00 | 102.25 | 0.474340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21397.30 | 14-NOV-16:01 | 21397.30 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.153110E+09 | 0.00 | 47.52 | 0.153110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21355.91 | 03-DEC-16:01 | 21355.91 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376170E+11 | 3980.38 | 0.286412E+11 | ||||||||||||
Minimum of Months | 0.153110E+09 | 0.00 | 47.52 | 0.153110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21355.91 | 21355.91 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.812202E+10 | 0.00 | 676.85 | 0.596728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22280.50 | 21420.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.372402E+11 | 0.00 | 385.23 | 0.372402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78220.25 | 20-JAN-12:30 | 78220.25 | 20-JAN-12:30 | 0.00 | 0.00 | 0.00 |
February | 0.257669E+11 | 0.00 | 284.07 | 0.257669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72472.98 | 18-FEB-12:40 | 72472.98 | 18-FEB-12:40 | 0.00 | 0.00 | 0.00 |
March | 0.248884E+11 | 0.00 | 321.52 | 0.248884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64369.41 | 11-MAR-12:50 | 64369.41 | 11-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.101931E+11 | 0.00 | 240.73 | 0.985003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37729.94 | 08-APR-12:40 | 37729.94 | 08-APR-12:40 | 0.00 | 0.00 | 0.00 |
May | 0.236529E+11 | 0.00 | 547.27 | 0.203970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28991.28 | 18-MAY-17:04 | 27414.93 | 31-MAY-17:12 | 0.00 | 0.00 | 0.00 |
June | 0.407663E+11 | 0.00 | 693.47 | 0.310796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39033.14 | 30-JUN-20:20 | 39033.14 | 30-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.451325E+11 | 0.00 | 717.83 | 0.340253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43433.04 | 02-JUL-18:40 | 43433.04 | 02-JUL-18:40 | 0.00 | 0.00 | 0.00 |
August | 0.471382E+11 | 0.00 | 719.80 | 0.348939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48089.18 | 02-AUG-18:05 | 46759.25 | 02-AUG-18:03 | 0.00 | 0.00 | 0.00 |
September | 0.495724E+11 | 0.00 | 667.92 | 0.460413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62575.63 | 28-SEP-12:30 | 62575.63 | 28-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.413815E+11 | 0.00 | 443.08 | 0.413729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67236.83 | 10-OCT-12:30 | 67236.83 | 10-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.378198E+11 | 0.00 | 380.28 | 0.378198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75652.76 | 07-NOV-11:53 | 75652.76 | 07-NOV-11:53 | 0.00 | 0.00 | 0.00 |
December | 0.267182E+11 | 0.00 | 264.64 | 0.267182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75654.07 | 17-DEC-12:10 | 75654.07 | 17-DEC-12:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410270E+12 | 5665.84 | 0.370093E+12 | ||||||||||||
Minimum of Months | 0.101931E+11 | 0.00 | 240.73 | 0.985003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28991.28 | 27414.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.495724E+11 | 0.00 | 719.80 | 0.460413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78220.25 | 78220.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.738979E+10 | 0.00 | 218.97 | 0.738979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117243.82 | 21-JAN-09:01 | 117243.82 | 21-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.601203E+10 | 0.00 | 165.34 | 0.601203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117046.40 | 19-FEB-09:01 | 117046.40 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.166268E+11 | 0.00 | 337.48 | 0.164999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118978.80 | 16-MAR-18:01 | 118978.80 | 16-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.211975E+11 | 0.00 | 400.47 | 0.190335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119294.65 | 08-APR-18:01 | 119294.65 | 08-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.461356E+11 | 0.00 | 531.60 | 0.388960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121833.80 | 25-MAY-18:01 | 121833.80 | 25-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.693569E+11 | 0.00 | 583.39 | 0.550159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123032.40 | 18-JUN-08:62 | 121865.32 | 01-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.737941E+11 | 0.00 | 619.40 | 0.565498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130213.35 | 31-JUL-18:01 | 121865.94 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.663342E+11 | 0.00 | 582.20 | 0.492843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121873.85 | 21-AUG-15:01 | 121873.85 | 21-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.496594E+11 | 0.00 | 531.55 | 0.433945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121862.21 | 11-SEP-18:01 | 121862.21 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.226608E+11 | 0.00 | 418.93 | 0.214197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120010.66 | 01-OCT-18:01 | 120010.66 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.106588E+11 | 0.00 | 278.29 | 0.103732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117581.34 | 09-NOV-19:01 | 117581.34 | 09-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.590463E+10 | 0.00 | 195.75 | 0.590463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116017.24 | 03-DEC-09:01 | 116017.24 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395731E+12 | 4863.36 | 0.329773E+12 | ||||||||||||
Minimum of Months | 0.590463E+10 | 0.00 | 165.34 | 0.590463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116017.24 | 116017.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.737941E+11 | 0.00 | 619.40 | 0.565498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130213.35 | 121873.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.128635E+10 | 0.00 | 209.26 | 0.128466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18931.49 | 19-JAN-09:01 | 18931.49 | 19-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.147052E+10 | 0.00 | 200.47 | 0.146996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18928.66 | 23-FEB-09:01 | 18928.66 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.257415E+10 | 0.00 | 303.34 | 0.256518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18918.21 | 31-MAR-08:61 | 18918.21 | 31-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.207478E+10 | 0.00 | 279.38 | 0.191424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18927.69 | 09-APR-08:62 | 18927.69 | 09-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.430487E+10 | 0.00 | 557.59 | 0.341808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18942.07 | 18-MAY-08:61 | 18942.07 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.876288E+10 | 0.00 | 695.85 | 0.650467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18938.99 | 29-JUN-18:01 | 18938.99 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.899762E+10 | 0.00 | 713.12 | 0.639088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20014.56 | 31-JUL-18:01 | 18939.65 | 21-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.880613E+10 | 0.00 | 716.07 | 0.608756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18939.82 | 23-AUG-18:01 | 18939.82 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.663218E+10 | 0.00 | 646.70 | 0.557126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18938.85 | 12-SEP-18:01 | 18938.85 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.315590E+10 | 0.00 | 373.29 | 0.306633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18942.57 | 03-OCT-15:01 | 18942.57 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.170373E+10 | 0.00 | 256.12 | 0.168883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18939.39 | 19-NOV-09:01 | 18939.39 | 19-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.947382E+09 | 0.00 | 153.51 | 0.947382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18908.64 | 02-DEC-09:01 | 18908.64 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507165E+11 | 5104.68 | 0.409090E+11 | ||||||||||||
Minimum of Months | 0.947382E+09 | 0.00 | 153.51 | 0.947382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18908.64 | 18908.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.899762E+10 | 0.00 | 716.07 | 0.650467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20014.56 | 18942.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.245696E+09 | 0.00 | 58.15 | 0.245696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18804.84 | 20-JAN-09:01 | 18804.84 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.509370E+09 | 0.00 | 84.78 | 0.509370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18833.01 | 23-FEB-09:01 | 18833.01 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.146217E+10 | 0.00 | 198.41 | 0.145527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18822.52 | 31-MAR-08:61 | 18822.52 | 31-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.163267E+10 | 0.00 | 226.22 | 0.148978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18831.98 | 09-APR-08:62 | 18831.98 | 09-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.403487E+10 | 0.00 | 542.35 | 0.318039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18845.14 | 18-MAY-08:61 | 18845.14 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.861646E+10 | 0.00 | 694.47 | 0.640535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18856.70 | 20-JUN-18:01 | 18843.26 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.876704E+10 | 0.00 | 712.04 | 0.621668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19984.57 | 31-JUL-18:01 | 18844.21 | 21-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.808706E+10 | 0.00 | 712.15 | 0.551788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18843.89 | 23-AUG-18:01 | 18843.89 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.525450E+10 | 0.00 | 616.27 | 0.431332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18842.81 | 12-SEP-18:01 | 18842.81 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.155358E+10 | 0.00 | 244.89 | 0.150195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18845.89 | 04-OCT-08:61 | 18845.89 | 04-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.461549E+09 | 0.00 | 90.14 | 0.454408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18844.60 | 19-NOV-09:01 | 18844.60 | 19-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.149486E+09 | 0.00 | 42.33 | 0.149486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18748.99 | 02-DEC-09:01 | 18748.99 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407744E+11 | 4222.20 | 0.314396E+11 | ||||||||||||
Minimum of Months | 0.149486E+09 | 0.00 | 42.33 | 0.149486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18748.99 | 18748.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.876704E+10 | 0.00 | 712.15 | 0.640535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19984.57 | 18845.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.341589E+09 | 0.00 | 177.35 | 0.341452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845.15 | 10-JAN-16:01 | 5845.15 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.363850E+09 | 0.00 | 161.35 | 0.363610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5838.18 | 23-FEB-16:01 | 5838.18 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.696577E+09 | 0.00 | 255.69 | 0.696440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5842.55 | 25-MAR-18:01 | 5842.55 | 25-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.510418E+09 | 0.00 | 232.22 | 0.478301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845.41 | 26-APR-15:01 | 5845.41 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.118186E+10 | 0.00 | 518.99 | 0.950132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5847.90 | 25-MAY-18:01 | 5847.90 | 25-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.256269E+10 | 0.00 | 675.53 | 0.193485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6135.90 | 18-JUN-08:62 | 5846.08 | 09-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.248261E+10 | 0.00 | 697.23 | 0.174011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6213.89 | 30-JUL-08:61 | 5846.22 | 06-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.246290E+10 | 0.00 | 692.73 | 0.174372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6054.87 | 05-AUG-08:61 | 5846.78 | 08-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.187099E+10 | 0.00 | 623.32 | 0.157527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5845.95 | 12-SEP-18:01 | 5845.95 | 12-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.924313E+09 | 0.00 | 342.86 | 0.899379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5847.97 | 03-OCT-15:01 | 5847.97 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.481029E+09 | 0.00 | 225.16 | 0.477756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5842.02 | 12-NOV-16:01 | 5842.02 | 12-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.234928E+09 | 0.00 | 131.24 | 0.234928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.84 | 29-DEC-16:01 | 5832.84 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141138E+11 | 4733.67 | 0.114360E+11 | ||||||||||||
Minimum of Months | 0.234928E+09 | 0.00 | 131.24 | 0.234928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.84 | 5832.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.256269E+10 | 0.00 | 697.23 | 0.193485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6213.89 | 5847.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 69390885.61 | 0.00 | 46.89 | 69342847.36 | 0.00 | 0.00 | 0.00 | 0.00 | 5782.42 | 22-JAN-16:01 | 5782.42 | 22-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.110933E+09 | 0.00 | 62.57 | 0.110933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5782.52 | 23-FEB-16:01 | 5782.52 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.407454E+09 | 0.00 | 174.97 | 0.407396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5786.62 | 25-MAR-18:01 | 5786.62 | 25-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.392364E+09 | 0.00 | 190.47 | 0.365097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5789.51 | 26-APR-15:01 | 5789.51 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.110956E+10 | 0.00 | 497.08 | 0.887184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5788.75 | 27-MAY-18:01 | 5788.75 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 0.00 | 675.15 | 0.190796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6070.54 | 18-JUN-08:62 | 5790.01 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.242569E+10 | 0.00 | 696.66 | 0.169709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6146.19 | 30-JUL-08:61 | 5790.28 | 06-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.227127E+10 | 0.00 | 686.07 | 0.159127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5986.59 | 05-AUG-08:61 | 5790.82 | 23-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.150789E+10 | 0.00 | 591.43 | 0.124458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5790.02 | 14-SEP-15:01 | 5790.02 | 14-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.498763E+09 | 0.00 | 215.66 | 0.486247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5791.86 | 03-OCT-15:01 | 5791.86 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.130336E+09 | 0.00 | 83.07 | 0.128864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5785.56 | 14-NOV-16:01 | 5785.56 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 35895650.62 | 0.00 | 34.17 | 35895650.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5774.33 | 03-DEC-16:01 | 5774.33 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114878E+11 | 3954.21 | 0.893186E+10 | ||||||||||||
Minimum of Months | 35895650.62 | 0.00 | 34.17 | 35895650.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5774.33 | 5774.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.252825E+10 | 0.00 | 696.66 | 0.190796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6146.19 | 5791.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.798786E+10 | 0.00 | 390.59 | 0.796999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22210.12 | 10-JAN-16:01 | 22210.12 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.608189E+10 | 0.00 | 316.40 | 0.605552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22200.44 | 25-FEB-09:01 | 22200.44 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.600038E+10 | 0.00 | 370.36 | 0.597454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22195.90 | 25-MAR-15:01 | 22195.90 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.314313E+10 | 0.00 | 310.24 | 0.287699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22213.58 | 26-APR-15:01 | 22213.58 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.608747E+10 | 0.00 | 567.35 | 0.489981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22207.87 | 25-MAY-15:01 | 22207.87 | 25-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.115027E+11 | 0.00 | 666.24 | 0.866410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22878.16 | 18-JUN-08:62 | 22214.33 | 29-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.125202E+11 | 0.00 | 690.84 | 0.908584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24220.17 | 31-JUL-18:01 | 22213.61 | 18-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.129347E+11 | 0.00 | 691.74 | 0.947983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22356.40 | 29-AUG-18:01 | 22212.98 | 25-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.120254E+11 | 0.00 | 652.21 | 0.106445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22213.83 | 14-SEP-15:01 | 22213.83 | 14-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.882915E+10 | 0.00 | 461.61 | 0.860218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22202.49 | 01-OCT-18:01 | 22202.49 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.827121E+10 | 0.00 | 418.24 | 0.821274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22213.00 | 19-NOV-09:01 | 22213.00 | 19-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.610088E+10 | 0.00 | 304.54 | 0.610088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22182.31 | 30-DEC-16:01 | 22182.31 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101485E+12 | 5840.36 | 0.885670E+11 | ||||||||||||
Minimum of Months | 0.314313E+10 | 0.00 | 304.54 | 0.287699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22182.31 | 22182.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129347E+11 | 0.00 | 691.74 | 0.106445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24220.17 | 22214.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.177937E+11 | 0.00 | 69.81 | 0.177937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 267813.14 | 20-JAN-14:00 | 267813.14 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.982622E+10 | 0.00 | 43.32 | 0.982622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236080.35 | 18-FEB-14:00 | 236080.35 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.516207E+11 | 0.00 | 142.42 | 0.516207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 291508.01 | 14-MAR-13:00 | 291508.01 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.608423E+11 | 0.00 | 147.12 | 0.608423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 274383.92 | 20-APR-13:00 | 274383.92 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.229532E+12 | 0.00 | 404.41 | 0.229532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 329989.66 | 17-MAY-13:00 | 329989.66 | 17-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.631884E+12 | 0.00 | 702.00 | 0.598189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484627.87 | 18-JUN-08:50 | 413541.80 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.742446E+12 | 0.00 | 724.67 | 0.657403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 559495.75 | 28-JUL-17:00 | 393457.39 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.662058E+12 | 0.00 | 724.17 | 0.609320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560760.60 | 05-AUG-15:00 | 397119.51 | 16-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.449365E+12 | 0.00 | 597.24 | 0.449081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 362312.83 | 09-SEP-13:00 | 362312.83 | 09-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.897172E+11 | 0.00 | 212.75 | 0.897172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 316830.31 | 11-OCT-14:00 | 316830.31 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.318983E+11 | 0.00 | 95.29 | 0.318983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 278396.71 | 07-NOV-13:55 | 278396.71 | 07-NOV-13:55 | 0.00 | 0.00 | 0.00 |
December | 0.230866E+11 | 0.00 | 65.22 | 0.230866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 277347.50 | 01-DEC-14:00 | 277347.50 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300007E+13 | 3928.41 | 0.282831E+13 | ||||||||||||
Minimum of Months | 0.982622E+10 | 0.00 | 43.32 | 0.982622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236080.35 | 236080.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.742446E+12 | 0.00 | 724.67 | 0.657403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560760.60 | 413541.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.806315E+09 | 0.00 | 29.33 | 0.806315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18767.96 | 20-JAN-14:00 | 18767.96 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.433304E+09 | 0.00 | 16.50 | 0.433304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15782.69 | 18-FEB-14:00 | 15782.69 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.272107E+10 | 0.00 | 84.83 | 0.272107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24819.62 | 14-MAR-13:00 | 24819.62 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.323793E+10 | 0.00 | 97.83 | 0.323793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20848.64 | 20-APR-13:00 | 20848.64 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.153487E+11 | 0.00 | 301.17 | 0.153487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35043.29 | 17-MAY-13:00 | 35043.29 | 17-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.524485E+11 | 0.00 | 663.67 | 0.511615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56144.72 | 26-JUN-15:00 | 56144.72 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.610428E+11 | 0.00 | 705.67 | 0.566776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52970.15 | 30-JUL-14:00 | 51277.17 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.522589E+11 | 0.00 | 691.50 | 0.503634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51453.17 | 16-AUG-14:00 | 51453.17 | 16-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.348520E+11 | 0.00 | 522.67 | 0.348520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42552.60 | 10-SEP-13:00 | 42552.60 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.528180E+10 | 0.00 | 132.33 | 0.528180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30910.17 | 11-OCT-14:00 | 30910.17 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.173877E+10 | 0.00 | 48.00 | 0.173877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20786.14 | 07-NOV-15:00 | 20786.14 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.121687E+10 | 0.00 | 37.33 | 0.121687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20807.49 | 02-DEC-15:00 | 20807.49 | 02-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231387E+12 | 3330.83 | 0.223839E+12 | ||||||||||||
Minimum of Months | 0.433304E+09 | 0.00 | 16.50 | 0.433304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15782.69 | 15782.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.610428E+11 | 0.00 | 705.67 | 0.566776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56144.72 | 56144.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1415.33 | 1165.11 | 250.22 | 1516.15 | 610.02 | 0.00 | 0.00 | 744.00 |
February | 1339.92 | 1065.53 | 274.39 | 1345.19 | 648.44 | 0.00 | 0.00 | 672.00 |
March | 1006.33 | 665.21 | 341.12 | 923.21 | 511.45 | 0.00 | 0.00 | 744.00 |
April | 658.61 | 272.42 | 386.20 | 479.45 | 455.91 | 0.00 | 0.00 | 720.00 |
May | 598.46 | 115.01 | 483.46 | 493.10 | 245.90 | 0.00 | 0.00 | 744.00 |
June | 544.00 | 98.04 | 445.96 | 596.63 | 105.66 | 0.00 | 0.00 | 720.00 |
July | 561.96 | 95.63 | 466.33 | 639.34 | 89.68 | 0.00 | 0.00 | 744.00 |
August | 715.04 | 294.09 | 420.95 | 734.61 | 106.89 | 0.00 | 0.00 | 744.00 |
September | 939.54 | 528.15 | 411.39 | 1013.58 | 192.56 | 0.00 | 0.00 | 720.00 |
October | 1109.57 | 786.35 | 323.22 | 1148.81 | 484.74 | 0.00 | 0.00 | 744.00 |
November | 1359.55 | 1084.48 | 275.07 | 1472.43 | 569.26 | 0.00 | 0.00 | 720.00 |
December | 1297.05 | 1049.97 | 247.08 | 1373.91 | 699.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 959.96 | 599.01 | 360.95 | 975.97 | 391.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 544.00 | 95.63 | 247.08 | 479.45 | 89.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1415.33 | 1165.11 | 483.46 | 1516.15 | 699.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3985.48 | 3280.87 | 704.62 | 4264.61 | 1716.51 | 0.00 | 0.00 | 744.00 |
February | 3773.14 | 3000.48 | 772.66 | 3782.15 | 1825.96 | 0.00 | 0.00 | 672.00 |
March | 2833.76 | 1873.19 | 960.57 | 2594.48 | 1444.08 | 0.00 | 0.00 | 744.00 |
April | 1854.61 | 767.10 | 1087.51 | 1339.61 | 1288.36 | 0.00 | 0.00 | 720.00 |
May | 1685.23 | 323.85 | 1361.38 | 1375.52 | 688.59 | 0.00 | 0.00 | 744.00 |
June | 1531.85 | 276.07 | 1255.79 | 1670.51 | 289.58 | 0.00 | 0.00 | 720.00 |
July | 1582.44 | 269.28 | 1313.16 | 1790.65 | 246.10 | 0.00 | 0.00 | 744.00 |
August | 2013.50 | 828.14 | 1185.37 | 2059.20 | 293.93 | 0.00 | 0.00 | 744.00 |
September | 2645.68 | 1487.24 | 1158.44 | 2850.75 | 536.24 | 0.00 | 0.00 | 720.00 |
October | 3124.48 | 2214.30 | 910.17 | 3234.80 | 1367.36 | 0.00 | 0.00 | 744.00 |
November | 3828.41 | 3053.82 | 774.59 | 4142.45 | 1603.38 | 0.00 | 0.00 | 720.00 |
December | 3652.40 | 2956.65 | 695.75 | 3861.87 | 1975.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2703.18 | 1686.78 | 1016.40 | 2741.41 | 1102.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1531.85 | 269.28 | 695.75 | 1339.61 | 246.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3985.48 | 3280.87 | 1361.38 | 4264.61 | 1975.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5177.37 | 4262.04 | 915.34 | 5654.57 | 2265.66 | 0.00 | 0.00 | 744.00 |
February | 4901.52 | 3897.79 | 1003.73 | 5020.23 | 2419.61 | 0.00 | 0.00 | 672.00 |
March | 3681.22 | 2433.38 | 1247.84 | 3441.63 | 1925.86 | 0.00 | 0.00 | 744.00 |
April | 2409.25 | 996.51 | 1412.74 | 1779.86 | 1729.79 | 0.00 | 0.00 | 720.00 |
May | 2189.21 | 420.70 | 1768.52 | 1839.51 | 927.52 | 0.00 | 0.00 | 744.00 |
June | 1989.97 | 358.62 | 1631.34 | 2240.74 | 384.78 | 0.00 | 0.00 | 720.00 |
July | 2055.68 | 349.81 | 1705.87 | 2398.43 | 325.35 | 0.00 | 0.00 | 744.00 |
August | 2615.65 | 1075.79 | 1539.86 | 2752.24 | 386.25 | 0.00 | 0.00 | 744.00 |
September | 3436.89 | 1932.01 | 1504.89 | 3787.04 | 706.46 | 0.00 | 0.00 | 720.00 |
October | 4058.87 | 2876.51 | 1182.37 | 4291.38 | 1815.20 | 0.00 | 0.00 | 744.00 |
November | 4973.32 | 3967.08 | 1006.24 | 5493.99 | 2119.25 | 0.00 | 0.00 | 720.00 |
December | 4744.68 | 3840.85 | 903.82 | 5112.32 | 2616.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 3511.59 | 2191.22 | 1320.36 | 3643.31 | 1463.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1989.97 | 349.81 | 903.82 | 1779.86 | 325.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 5177.37 | 4262.04 | 1768.52 | 5654.57 | 2616.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.27 | 229.89 | 49.37 | 300.70 | 125.89 | 0.00 | 0.00 | 744.00 |
February | 264.39 | 210.25 | 54.14 | 265.79 | 135.62 | 0.00 | 0.00 | 672.00 |
March | 198.56 | 131.26 | 67.31 | 181.67 | 107.98 | 0.00 | 0.00 | 744.00 |
April | 129.95 | 53.75 | 76.20 | 93.01 | 97.46 | 0.00 | 0.00 | 720.00 |
May | 118.09 | 22.69 | 95.39 | 94.10 | 53.06 | 0.00 | 0.00 | 744.00 |
June | 107.34 | 19.34 | 87.99 | 115.04 | 22.51 | 0.00 | 0.00 | 720.00 |
July | 110.88 | 18.87 | 92.01 | 123.91 | 19.01 | 0.00 | 0.00 | 744.00 |
August | 141.09 | 58.03 | 83.06 | 143.18 | 22.69 | 0.00 | 0.00 | 744.00 |
September | 185.38 | 104.21 | 81.17 | 199.33 | 40.42 | 0.00 | 0.00 | 720.00 |
October | 218.93 | 155.16 | 63.78 | 227.31 | 101.39 | 0.00 | 0.00 | 744.00 |
November | 268.26 | 213.98 | 54.28 | 292.05 | 118.13 | 0.00 | 0.00 | 720.00 |
December | 255.93 | 207.17 | 48.75 | 271.24 | 146.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.41 | 118.19 | 71.22 | 191.86 | 82.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 107.34 | 18.87 | 48.75 | 93.01 | 19.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.27 | 229.89 | 95.39 | 300.70 | 146.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.75 | 114.56 | 66.19 | 130.60 | 263.21 | 0.00 | 0.00 | 744.00 |
February | 218.32 | 135.42 | 82.89 | 162.57 | 271.13 | 0.00 | 0.00 | 672.00 |
March | 254.63 | 140.28 | 114.36 | 215.45 | 202.66 | 0.00 | 0.00 | 744.00 |
April | 240.16 | 101.74 | 138.42 | 194.20 | 177.72 | 0.00 | 0.00 | 720.00 |
May | 293.60 | 103.68 | 189.92 | 290.38 | 96.02 | 0.00 | 0.00 | 744.00 |
June | 358.41 | 172.28 | 186.13 | 440.44 | 41.74 | 0.00 | 0.00 | 720.00 |
July | 291.71 | 106.49 | 185.22 | 362.24 | 35.32 | 0.00 | 0.00 | 744.00 |
August | 305.49 | 150.96 | 154.53 | 371.76 | 41.72 | 0.00 | 0.00 | 744.00 |
September | 271.85 | 130.80 | 141.04 | 310.37 | 75.86 | 0.00 | 0.00 | 720.00 |
October | 227.62 | 130.10 | 97.52 | 207.42 | 193.23 | 0.00 | 0.00 | 744.00 |
November | 186.92 | 113.53 | 73.39 | 143.28 | 236.31 | 0.00 | 0.00 | 720.00 |
December | 150.77 | 89.04 | 61.73 | 95.96 | 302.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 248.42 | 123.92 | 124.50 | 244.08 | 160.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.77 | 89.04 | 61.73 | 95.96 | 35.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 358.41 | 172.28 | 189.92 | 440.44 | 302.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.03 | 0.00 | 29.03 | 3.75 | 146.26 | 0.00 | 0.00 | 744.00 |
February | 36.49 | 0.00 | 36.49 | 4.26 | 152.05 | 0.00 | 0.00 | 672.00 |
March | 49.67 | 0.00 | 49.66 | 16.59 | 112.50 | 0.00 | 0.00 | 744.00 |
April | 62.43 | 0.40 | 62.02 | 26.65 | 96.71 | 0.00 | 0.00 | 720.00 |
May | 85.28 | 2.85 | 82.43 | 64.71 | 49.67 | 0.00 | 0.00 | 744.00 |
June | 93.49 | 10.44 | 83.05 | 105.81 | 20.40 | 0.00 | 0.00 | 720.00 |
July | 88.68 | 6.04 | 82.63 | 106.68 | 17.70 | 0.00 | 0.00 | 744.00 |
August | 70.60 | 1.90 | 68.70 | 82.62 | 21.71 | 0.00 | 0.00 | 744.00 |
September | 59.12 | 0.05 | 59.08 | 61.65 | 40.21 | 0.00 | 0.00 | 720.00 |
October | 42.30 | 0.00 | 42.30 | 18.91 | 104.27 | 0.00 | 0.00 | 744.00 |
November | 32.11 | 0.00 | 32.11 | 6.46 | 130.43 | 0.00 | 0.00 | 720.00 |
December | 27.16 | 0.00 | 27.16 | 3.26 | 168.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.47 | 1.81 | 54.65 | 42.00 | 88.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.16 | 0.00 | 27.16 | 3.26 | 17.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.49 | 10.44 | 83.05 | 106.68 | 168.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.75 | 114.56 | 66.19 | 136.96 | 255.95 | 0.00 | 0.00 | 744.00 |
February | 218.32 | 135.42 | 82.89 | 168.95 | 265.29 | 0.00 | 0.00 | 672.00 |
March | 254.63 | 140.28 | 114.36 | 220.35 | 200.12 | 0.00 | 0.00 | 744.00 |
April | 240.16 | 101.74 | 138.42 | 196.70 | 176.50 | 0.00 | 0.00 | 720.00 |
May | 293.60 | 103.68 | 189.92 | 291.43 | 95.59 | 0.00 | 0.00 | 744.00 |
June | 358.41 | 172.28 | 186.13 | 440.78 | 41.50 | 0.00 | 0.00 | 720.00 |
July | 291.71 | 106.49 | 185.22 | 362.73 | 35.09 | 0.00 | 0.00 | 744.00 |
August | 305.49 | 150.96 | 154.53 | 373.30 | 41.26 | 0.00 | 0.00 | 744.00 |
September | 271.85 | 130.80 | 141.04 | 313.76 | 74.70 | 0.00 | 0.00 | 720.00 |
October | 227.62 | 130.10 | 97.52 | 212.80 | 190.50 | 0.00 | 0.00 | 744.00 |
November | 186.92 | 113.53 | 73.39 | 149.74 | 230.72 | 0.00 | 0.00 | 720.00 |
December | 150.77 | 89.04 | 61.73 | 101.37 | 296.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 248.42 | 123.92 | 124.50 | 247.75 | 158.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.77 | 89.04 | 61.73 | 101.37 | 35.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 358.41 | 172.28 | 189.92 | 440.78 | 296.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.37 | 183.88 | 39.49 | 236.65 | 109.90 | 0.00 | 0.00 | 744.00 |
February | 211.47 | 168.16 | 43.30 | 209.53 | 114.82 | 0.00 | 0.00 | 672.00 |
March | 158.82 | 104.98 | 53.84 | 143.30 | 92.26 | 0.00 | 0.00 | 744.00 |
April | 103.94 | 42.99 | 60.95 | 72.53 | 85.53 | 0.00 | 0.00 | 720.00 |
May | 94.45 | 18.15 | 76.30 | 72.20 | 49.90 | 0.00 | 0.00 | 744.00 |
June | 85.85 | 15.47 | 70.38 | 89.87 | 23.54 | 0.00 | 0.00 | 720.00 |
July | 88.69 | 15.09 | 73.60 | 96.33 | 20.89 | 0.00 | 0.00 | 744.00 |
August | 112.85 | 46.41 | 66.43 | 112.03 | 24.30 | 0.00 | 0.00 | 744.00 |
September | 148.28 | 83.35 | 64.93 | 156.78 | 39.78 | 0.00 | 0.00 | 720.00 |
October | 175.11 | 124.10 | 51.01 | 179.39 | 89.87 | 0.00 | 0.00 | 744.00 |
November | 214.56 | 171.15 | 43.41 | 230.55 | 103.34 | 0.00 | 0.00 | 720.00 |
December | 204.70 | 165.71 | 38.99 | 213.63 | 124.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.50 | 94.54 | 56.96 | 150.73 | 73.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 85.85 | 15.09 | 38.99 | 72.20 | 20.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 223.37 | 183.88 | 76.30 | 236.65 | 124.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.23 | 0.00 | 23.23 | 2.74 | 120.58 | 0.00 | 0.00 | 744.00 |
February | 29.20 | 0.00 | 29.20 | 3.34 | 124.41 | 0.00 | 0.00 | 672.00 |
March | 39.74 | 0.00 | 39.74 | 13.58 | 92.15 | 0.00 | 0.00 | 744.00 |
April | 49.95 | 0.32 | 49.63 | 21.61 | 79.80 | 0.00 | 0.00 | 720.00 |
May | 68.23 | 2.28 | 65.95 | 53.43 | 40.11 | 0.00 | 0.00 | 744.00 |
June | 74.80 | 8.35 | 66.45 | 88.12 | 15.80 | 0.00 | 0.00 | 720.00 |
July | 70.95 | 4.83 | 66.12 | 88.19 | 13.82 | 0.00 | 0.00 | 744.00 |
August | 56.49 | 1.52 | 54.97 | 69.03 | 16.92 | 0.00 | 0.00 | 744.00 |
September | 47.30 | 0.04 | 47.27 | 51.59 | 31.92 | 0.00 | 0.00 | 720.00 |
October | 33.84 | 0.00 | 33.84 | 15.86 | 85.22 | 0.00 | 0.00 | 744.00 |
November | 25.69 | 0.00 | 25.69 | 5.08 | 107.27 | 0.00 | 0.00 | 720.00 |
December | 21.73 | 0.00 | 21.73 | 2.41 | 139.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 45.18 | 1.45 | 43.73 | 34.76 | 72.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.73 | 0.00 | 21.73 | 2.41 | 13.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.80 | 8.35 | 66.45 | 88.19 | 139.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.22 | 103.51 | 65.71 | 111.62 | 258.69 | 0.00 | 0.00 | 744.00 |
February | 226.81 | 143.55 | 83.27 | 172.13 | 270.10 | 0.00 | 0.00 | 672.00 |
March | 273.23 | 159.49 | 113.74 | 232.79 | 198.46 | 0.00 | 0.00 | 744.00 |
April | 278.93 | 135.86 | 143.07 | 237.59 | 173.35 | 0.00 | 0.00 | 720.00 |
May | 326.95 | 136.85 | 190.09 | 326.94 | 89.94 | 0.00 | 0.00 | 744.00 |
June | 397.80 | 208.75 | 189.06 | 486.57 | 37.78 | 0.00 | 0.00 | 720.00 |
July | 361.09 | 171.56 | 189.53 | 447.23 | 33.04 | 0.00 | 0.00 | 744.00 |
August | 365.16 | 201.18 | 163.98 | 442.58 | 40.08 | 0.00 | 0.00 | 744.00 |
September | 304.37 | 165.46 | 138.91 | 344.92 | 71.48 | 0.00 | 0.00 | 720.00 |
October | 220.22 | 120.77 | 99.45 | 192.97 | 189.03 | 0.00 | 0.00 | 744.00 |
November | 170.90 | 96.32 | 74.59 | 118.42 | 234.47 | 0.00 | 0.00 | 720.00 |
December | 148.25 | 85.44 | 62.81 | 89.30 | 300.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 270.41 | 143.98 | 126.42 | 267.37 | 157.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 148.25 | 85.44 | 62.81 | 89.30 | 33.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 397.80 | 208.75 | 190.09 | 486.57 | 300.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.27 | 229.89 | 49.37 | 300.13 | 125.42 | 0.00 | 0.00 | 744.00 |
February | 264.39 | 210.25 | 54.14 | 264.75 | 135.04 | 0.00 | 0.00 | 672.00 |
March | 198.56 | 131.26 | 67.31 | 180.28 | 107.60 | 0.00 | 0.00 | 744.00 |
April | 129.95 | 53.75 | 76.20 | 91.57 | 97.49 | 0.00 | 0.00 | 720.00 |
May | 118.09 | 22.69 | 95.39 | 92.74 | 53.09 | 0.00 | 0.00 | 744.00 |
June | 107.34 | 19.34 | 87.99 | 113.80 | 22.46 | 0.00 | 0.00 | 720.00 |
July | 110.88 | 18.87 | 92.01 | 122.41 | 19.08 | 0.00 | 0.00 | 744.00 |
August | 141.09 | 58.03 | 83.06 | 141.58 | 22.59 | 0.00 | 0.00 | 744.00 |
September | 185.38 | 104.21 | 81.17 | 198.23 | 40.25 | 0.00 | 0.00 | 720.00 |
October | 218.93 | 155.16 | 63.78 | 226.58 | 100.91 | 0.00 | 0.00 | 744.00 |
November | 268.26 | 213.98 | 54.28 | 291.70 | 117.56 | 0.00 | 0.00 | 720.00 |
December | 255.93 | 207.17 | 48.75 | 270.75 | 145.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.41 | 118.19 | 71.22 | 190.80 | 82.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 107.34 | 18.87 | 48.75 | 91.57 | 19.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.27 | 229.89 | 95.39 | 300.13 | 145.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.03 | 0.00 | 29.03 | 3.49 | 145.82 | 0.00 | 0.00 | 744.00 |
February | 36.49 | 0.00 | 36.49 | 3.78 | 152.07 | 0.00 | 0.00 | 672.00 |
March | 49.67 | 0.00 | 49.66 | 15.53 | 112.77 | 0.00 | 0.00 | 744.00 |
April | 62.43 | 0.40 | 62.02 | 25.29 | 97.06 | 0.00 | 0.00 | 720.00 |
May | 85.28 | 2.85 | 82.43 | 63.30 | 49.67 | 0.00 | 0.00 | 744.00 |
June | 93.49 | 10.44 | 83.05 | 104.38 | 20.13 | 0.00 | 0.00 | 720.00 |
July | 88.68 | 6.04 | 82.63 | 105.04 | 17.62 | 0.00 | 0.00 | 744.00 |
August | 70.60 | 1.90 | 68.70 | 80.88 | 21.61 | 0.00 | 0.00 | 744.00 |
September | 59.12 | 0.05 | 59.08 | 60.40 | 40.25 | 0.00 | 0.00 | 720.00 |
October | 42.30 | 0.00 | 42.30 | 18.28 | 104.12 | 0.00 | 0.00 | 744.00 |
November | 32.11 | 0.00 | 32.11 | 6.10 | 129.63 | 0.00 | 0.00 | 720.00 |
December | 27.16 | 0.00 | 27.16 | 3.03 | 167.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.47 | 1.81 | 54.65 | 41.01 | 87.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.16 | 0.00 | 27.16 | 3.03 | 17.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.49 | 10.44 | 83.05 | 105.04 | 167.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.22 | 103.51 | 65.71 | 115.79 | 248.62 | 0.00 | 0.00 | 744.00 |
February | 226.81 | 143.55 | 83.27 | 175.87 | 261.57 | 0.00 | 0.00 | 672.00 |
March | 273.23 | 159.49 | 113.74 | 236.71 | 195.36 | 0.00 | 0.00 | 744.00 |
April | 278.93 | 135.86 | 143.07 | 239.71 | 172.07 | 0.00 | 0.00 | 720.00 |
May | 326.95 | 136.85 | 190.09 | 327.90 | 89.53 | 0.00 | 0.00 | 744.00 |
June | 397.80 | 208.75 | 189.06 | 487.02 | 37.65 | 0.00 | 0.00 | 720.00 |
July | 361.09 | 171.56 | 189.53 | 447.75 | 32.89 | 0.00 | 0.00 | 744.00 |
August | 365.16 | 201.18 | 163.98 | 443.94 | 39.64 | 0.00 | 0.00 | 744.00 |
September | 304.37 | 165.46 | 138.91 | 347.81 | 70.36 | 0.00 | 0.00 | 720.00 |
October | 220.22 | 120.77 | 99.45 | 197.77 | 186.08 | 0.00 | 0.00 | 744.00 |
November | 170.90 | 96.32 | 74.59 | 122.92 | 226.49 | 0.00 | 0.00 | 720.00 |
December | 148.25 | 85.44 | 62.81 | 92.97 | 292.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 270.41 | 143.98 | 126.42 | 270.13 | 153.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 148.25 | 85.44 | 62.81 | 92.97 | 32.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 397.80 | 208.75 | 190.09 | 487.02 | 292.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.77 | 0.00 | 36.77 | 4.52 | 188.94 | 0.00 | 0.00 | 744.00 |
February | 46.21 | 0.00 | 46.21 | 5.55 | 194.79 | 0.00 | 0.00 | 672.00 |
March | 62.90 | 0.00 | 62.89 | 22.77 | 142.10 | 0.00 | 0.00 | 744.00 |
April | 79.06 | 0.51 | 78.55 | 36.57 | 121.80 | 0.00 | 0.00 | 720.00 |
May | 108.00 | 3.61 | 104.39 | 89.99 | 60.37 | 0.00 | 0.00 | 744.00 |
June | 118.40 | 13.22 | 105.18 | 146.11 | 22.81 | 0.00 | 0.00 | 720.00 |
July | 112.30 | 7.65 | 104.65 | 146.35 | 19.64 | 0.00 | 0.00 | 744.00 |
August | 89.41 | 2.41 | 87.01 | 114.90 | 24.47 | 0.00 | 0.00 | 744.00 |
September | 74.88 | 0.06 | 74.82 | 85.84 | 47.65 | 0.00 | 0.00 | 720.00 |
October | 53.57 | 0.00 | 53.57 | 26.48 | 131.41 | 0.00 | 0.00 | 744.00 |
November | 40.67 | 0.00 | 40.67 | 8.29 | 167.10 | 0.00 | 0.00 | 720.00 |
December | 34.40 | 0.00 | 34.40 | 3.89 | 218.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 71.51 | 2.29 | 69.22 | 57.91 | 111.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.40 | 0.00 | 34.40 | 3.89 | 19.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.40 | 13.22 | 105.18 | 146.35 | 218.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.55 | 0.00 | 13.55 | 1.67 | 69.65 | 0.00 | 0.00 | 744.00 |
February | 17.04 | 0.00 | 17.04 | 2.05 | 71.81 | 0.00 | 0.00 | 672.00 |
March | 23.19 | 0.00 | 23.19 | 8.39 | 52.38 | 0.00 | 0.00 | 744.00 |
April | 29.15 | 0.19 | 28.96 | 13.48 | 44.90 | 0.00 | 0.00 | 720.00 |
May | 39.81 | 1.33 | 38.48 | 33.17 | 22.25 | 0.00 | 0.00 | 744.00 |
June | 43.65 | 4.87 | 38.77 | 53.86 | 8.41 | 0.00 | 0.00 | 720.00 |
July | 41.40 | 2.82 | 38.58 | 53.95 | 7.24 | 0.00 | 0.00 | 744.00 |
August | 32.96 | 0.89 | 32.07 | 42.36 | 9.02 | 0.00 | 0.00 | 744.00 |
September | 27.60 | 0.02 | 27.58 | 31.64 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 19.75 | 0.00 | 19.75 | 9.76 | 48.44 | 0.00 | 0.00 | 744.00 |
November | 14.99 | 0.00 | 14.99 | 3.06 | 61.60 | 0.00 | 0.00 | 720.00 |
December | 12.68 | 0.00 | 12.68 | 1.43 | 80.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 26.36 | 0.85 | 25.52 | 21.35 | 40.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 12.68 | 0.00 | 12.68 | 1.43 | 7.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 43.65 | 4.87 | 38.77 | 53.95 | 80.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.30 | 107.27 | 23.04 | 142.43 | 58.25 | 0.00 | 0.00 | 744.00 |
February | 123.36 | 98.10 | 25.26 | 126.08 | 62.91 | 0.00 | 0.00 | 672.00 |
March | 92.65 | 61.24 | 31.41 | 86.72 | 49.74 | 0.00 | 0.00 | 744.00 |
April | 60.64 | 25.08 | 35.56 | 45.00 | 44.80 | 0.00 | 0.00 | 720.00 |
May | 55.10 | 10.59 | 44.51 | 47.03 | 23.51 | 0.00 | 0.00 | 744.00 |
June | 50.08 | 9.03 | 41.06 | 58.16 | 9.18 | 0.00 | 0.00 | 720.00 |
July | 51.74 | 8.80 | 42.93 | 62.07 | 7.68 | 0.00 | 0.00 | 744.00 |
August | 65.83 | 27.08 | 38.76 | 70.93 | 9.24 | 0.00 | 0.00 | 744.00 |
September | 86.50 | 48.62 | 37.87 | 96.65 | 17.32 | 0.00 | 0.00 | 720.00 |
October | 102.15 | 72.40 | 29.76 | 108.42 | 46.50 | 0.00 | 0.00 | 744.00 |
November | 125.17 | 99.84 | 25.33 | 138.42 | 54.57 | 0.00 | 0.00 | 720.00 |
December | 119.41 | 96.67 | 22.75 | 128.14 | 68.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.38 | 55.15 | 33.23 | 92.32 | 37.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 50.08 | 8.80 | 22.75 | 45.00 | 7.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.30 | 107.27 | 44.51 | 142.43 | 68.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.67 | 291.14 | 62.53 | 386.57 | 158.09 | 0.00 | 0.00 | 744.00 |
February | 334.83 | 266.26 | 68.57 | 342.21 | 170.74 | 0.00 | 0.00 | 672.00 |
March | 251.47 | 166.23 | 85.24 | 235.37 | 135.01 | 0.00 | 0.00 | 744.00 |
April | 164.58 | 68.07 | 96.51 | 122.15 | 121.60 | 0.00 | 0.00 | 720.00 |
May | 149.55 | 28.74 | 120.81 | 127.66 | 63.82 | 0.00 | 0.00 | 744.00 |
June | 135.94 | 24.50 | 111.44 | 157.86 | 24.92 | 0.00 | 0.00 | 720.00 |
July | 140.43 | 23.90 | 116.53 | 168.46 | 20.84 | 0.00 | 0.00 | 744.00 |
August | 178.68 | 73.49 | 105.19 | 192.53 | 25.08 | 0.00 | 0.00 | 744.00 |
September | 234.78 | 131.98 | 102.80 | 262.32 | 47.00 | 0.00 | 0.00 | 720.00 |
October | 277.27 | 196.50 | 80.77 | 294.29 | 126.22 | 0.00 | 0.00 | 744.00 |
November | 339.73 | 271.00 | 68.74 | 375.69 | 148.11 | 0.00 | 0.00 | 720.00 |
December | 324.11 | 262.37 | 61.74 | 347.79 | 184.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 239.88 | 149.68 | 90.20 | 250.56 | 101.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 135.94 | 23.90 | 61.74 | 122.15 | 20.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 353.67 | 291.14 | 120.81 | 386.57 | 184.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.49 | 230.08 | 49.41 | 300.09 | 125.50 | 0.00 | 0.00 | 744.00 |
February | 264.60 | 210.42 | 54.19 | 264.80 | 135.86 | 0.00 | 0.00 | 672.00 |
March | 198.73 | 131.36 | 67.36 | 181.00 | 108.05 | 0.00 | 0.00 | 744.00 |
April | 130.06 | 53.80 | 76.26 | 92.43 | 97.57 | 0.00 | 0.00 | 720.00 |
May | 118.18 | 22.71 | 95.47 | 92.80 | 53.55 | 0.00 | 0.00 | 744.00 |
June | 107.43 | 19.36 | 88.07 | 113.53 | 22.81 | 0.00 | 0.00 | 720.00 |
July | 110.97 | 18.88 | 92.09 | 122.44 | 19.32 | 0.00 | 0.00 | 744.00 |
August | 141.20 | 58.08 | 83.13 | 141.79 | 23.06 | 0.00 | 0.00 | 744.00 |
September | 185.54 | 104.30 | 81.24 | 198.25 | 40.68 | 0.00 | 0.00 | 720.00 |
October | 219.11 | 155.28 | 63.83 | 226.47 | 101.47 | 0.00 | 0.00 | 744.00 |
November | 268.48 | 214.16 | 54.32 | 291.13 | 118.07 | 0.00 | 0.00 | 720.00 |
December | 256.14 | 207.34 | 48.79 | 270.37 | 146.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.57 | 118.29 | 71.28 | 190.84 | 82.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 107.43 | 18.88 | 48.79 | 92.43 | 19.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.49 | 230.08 | 95.47 | 300.09 | 146.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.90 | 114.66 | 66.24 | 130.02 | 261.86 | 0.00 | 0.00 | 744.00 |
February | 218.50 | 135.53 | 82.96 | 161.41 | 271.26 | 0.00 | 0.00 | 672.00 |
March | 254.84 | 140.39 | 114.45 | 213.94 | 202.64 | 0.00 | 0.00 | 744.00 |
April | 240.36 | 101.83 | 138.53 | 192.44 | 177.73 | 0.00 | 0.00 | 720.00 |
May | 293.84 | 103.76 | 190.07 | 287.03 | 96.69 | 0.00 | 0.00 | 744.00 |
June | 358.70 | 172.42 | 186.28 | 436.68 | 42.29 | 0.00 | 0.00 | 720.00 |
July | 291.95 | 106.58 | 185.37 | 358.81 | 35.88 | 0.00 | 0.00 | 744.00 |
August | 305.74 | 151.08 | 154.66 | 368.22 | 42.37 | 0.00 | 0.00 | 744.00 |
September | 272.07 | 130.91 | 141.16 | 307.91 | 76.29 | 0.00 | 0.00 | 720.00 |
October | 227.80 | 130.20 | 97.60 | 205.93 | 193.19 | 0.00 | 0.00 | 744.00 |
November | 187.07 | 113.62 | 73.45 | 142.31 | 235.89 | 0.00 | 0.00 | 720.00 |
December | 150.90 | 89.11 | 61.78 | 95.69 | 302.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 248.63 | 124.02 | 124.61 | 242.05 | 160.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.90 | 89.11 | 61.78 | 95.69 | 35.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 358.70 | 172.42 | 190.07 | 436.68 | 302.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.06 | 0.00 | 29.06 | 3.80 | 145.03 | 0.00 | 0.00 | 744.00 |
February | 36.52 | 0.00 | 36.52 | 4.13 | 151.67 | 0.00 | 0.00 | 672.00 |
March | 49.71 | 0.00 | 49.70 | 16.18 | 112.31 | 0.00 | 0.00 | 744.00 |
April | 62.48 | 0.40 | 62.07 | 25.94 | 96.62 | 0.00 | 0.00 | 720.00 |
May | 85.35 | 2.85 | 82.49 | 63.06 | 49.98 | 0.00 | 0.00 | 744.00 |
June | 93.56 | 10.45 | 83.12 | 104.00 | 20.70 | 0.00 | 0.00 | 720.00 |
July | 88.75 | 6.05 | 82.70 | 104.94 | 18.02 | 0.00 | 0.00 | 744.00 |
August | 70.66 | 1.90 | 68.76 | 80.80 | 22.07 | 0.00 | 0.00 | 744.00 |
September | 59.17 | 0.05 | 59.13 | 60.41 | 40.43 | 0.00 | 0.00 | 720.00 |
October | 42.33 | 0.00 | 42.33 | 18.36 | 104.24 | 0.00 | 0.00 | 744.00 |
November | 32.14 | 0.00 | 32.14 | 6.34 | 129.74 | 0.00 | 0.00 | 720.00 |
December | 27.18 | 0.00 | 27.18 | 3.35 | 167.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.51 | 1.81 | 54.70 | 41.16 | 87.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.18 | 0.00 | 27.18 | 3.35 | 18.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.56 | 10.45 | 83.12 | 104.94 | 167.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.90 | 114.66 | 66.24 | 137.13 | 254.27 | 0.00 | 0.00 | 744.00 |
February | 218.50 | 135.53 | 82.96 | 168.30 | 265.25 | 0.00 | 0.00 | 672.00 |
March | 254.84 | 140.39 | 114.45 | 218.99 | 199.98 | 0.00 | 0.00 | 744.00 |
April | 240.36 | 101.83 | 138.53 | 194.92 | 176.47 | 0.00 | 0.00 | 720.00 |
May | 293.84 | 103.76 | 190.07 | 288.00 | 96.25 | 0.00 | 0.00 | 744.00 |
June | 358.70 | 172.42 | 186.28 | 436.99 | 42.05 | 0.00 | 0.00 | 720.00 |
July | 291.95 | 106.58 | 185.37 | 359.26 | 35.66 | 0.00 | 0.00 | 744.00 |
August | 305.74 | 151.08 | 154.66 | 369.64 | 41.91 | 0.00 | 0.00 | 744.00 |
September | 272.07 | 130.91 | 141.16 | 311.12 | 75.12 | 0.00 | 0.00 | 720.00 |
October | 227.80 | 130.20 | 97.60 | 211.35 | 190.34 | 0.00 | 0.00 | 744.00 |
November | 187.07 | 113.62 | 73.45 | 149.28 | 229.94 | 0.00 | 0.00 | 720.00 |
December | 150.90 | 89.11 | 61.78 | 101.68 | 295.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 248.63 | 124.02 | 124.61 | 245.89 | 158.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.90 | 89.11 | 61.78 | 101.68 | 35.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 358.70 | 172.42 | 190.07 | 436.99 | 295.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 409.91 | 337.44 | 72.47 | 432.82 | 189.77 | 0.00 | 0.00 | 744.00 |
February | 388.07 | 308.60 | 79.47 | 382.23 | 204.32 | 0.00 | 0.00 | 672.00 |
March | 291.45 | 192.66 | 98.79 | 262.25 | 161.08 | 0.00 | 0.00 | 744.00 |
April | 190.75 | 78.90 | 111.85 | 134.32 | 144.83 | 0.00 | 0.00 | 720.00 |
May | 173.33 | 33.31 | 140.02 | 137.58 | 78.06 | 0.00 | 0.00 | 744.00 |
June | 157.55 | 28.39 | 129.16 | 171.09 | 32.08 | 0.00 | 0.00 | 720.00 |
July | 162.75 | 27.70 | 135.06 | 182.91 | 27.46 | 0.00 | 0.00 | 744.00 |
August | 207.09 | 85.17 | 121.91 | 210.47 | 32.90 | 0.00 | 0.00 | 744.00 |
September | 272.11 | 152.96 | 119.15 | 290.79 | 59.65 | 0.00 | 0.00 | 720.00 |
October | 321.35 | 227.74 | 93.61 | 329.41 | 151.81 | 0.00 | 0.00 | 744.00 |
November | 393.75 | 314.08 | 79.67 | 420.95 | 178.44 | 0.00 | 0.00 | 720.00 |
December | 375.65 | 304.09 | 71.56 | 388.65 | 222.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 278.02 | 173.48 | 104.54 | 278.04 | 123.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 157.55 | 27.70 | 71.56 | 134.32 | 27.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 409.91 | 337.44 | 140.02 | 432.82 | 222.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.38 | 0.00 | 203.38 | 24.55 | 1037.44 | 0.00 | 0.00 | 744.00 |
February | 255.62 | 0.00 | 255.62 | 29.62 | 1078.77 | 0.00 | 0.00 | 672.00 |
March | 347.93 | 0.02 | 347.91 | 120.82 | 798.30 | 0.00 | 0.00 | 744.00 |
April | 437.34 | 2.83 | 434.50 | 192.90 | 691.82 | 0.00 | 0.00 | 720.00 |
May | 597.41 | 19.97 | 577.43 | 481.62 | 349.61 | 0.00 | 0.00 | 744.00 |
June | 654.93 | 73.12 | 581.80 | 796.82 | 132.55 | 0.00 | 0.00 | 720.00 |
July | 621.22 | 42.32 | 578.90 | 799.64 | 114.32 | 0.00 | 0.00 | 744.00 |
August | 494.60 | 13.32 | 481.29 | 626.88 | 139.99 | 0.00 | 0.00 | 744.00 |
September | 414.19 | 0.32 | 413.86 | 468.85 | 269.95 | 0.00 | 0.00 | 720.00 |
October | 296.33 | 0.00 | 296.33 | 142.76 | 737.68 | 0.00 | 0.00 | 744.00 |
November | 224.95 | 0.00 | 224.95 | 45.11 | 925.02 | 0.00 | 0.00 | 720.00 |
December | 190.29 | 0.00 | 190.29 | 21.30 | 1207.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 395.58 | 12.69 | 382.88 | 314.20 | 621.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 190.29 | 0.00 | 190.29 | 21.30 | 114.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 654.93 | 73.12 | 581.80 | 799.64 | 1207.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.38 | 0.00 | 203.38 | 23.06 | 1053.83 | 0.00 | 0.00 | 744.00 |
February | 255.62 | 0.00 | 255.62 | 28.05 | 1095.78 | 0.00 | 0.00 | 672.00 |
March | 347.93 | 0.02 | 347.91 | 116.88 | 813.88 | 0.00 | 0.00 | 744.00 |
April | 437.34 | 2.83 | 434.50 | 187.76 | 706.71 | 0.00 | 0.00 | 720.00 |
May | 597.41 | 19.97 | 577.43 | 473.21 | 359.21 | 0.00 | 0.00 | 744.00 |
June | 654.93 | 73.12 | 581.80 | 787.95 | 138.10 | 0.00 | 0.00 | 720.00 |
July | 621.22 | 42.32 | 578.90 | 790.88 | 119.68 | 0.00 | 0.00 | 744.00 |
August | 494.60 | 13.32 | 481.29 | 618.94 | 146.12 | 0.00 | 0.00 | 744.00 |
September | 414.19 | 0.32 | 413.86 | 462.26 | 278.55 | 0.00 | 0.00 | 720.00 |
October | 296.33 | 0.00 | 296.33 | 138.76 | 752.06 | 0.00 | 0.00 | 744.00 |
November | 224.95 | 0.00 | 224.95 | 43.17 | 941.25 | 0.00 | 0.00 | 720.00 |
December | 190.29 | 0.00 | 190.29 | 20.18 | 1225.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 395.58 | 12.69 | 382.88 | 309.20 | 633.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 190.29 | 0.00 | 190.29 | 20.18 | 119.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 654.93 | 73.12 | 581.80 | 790.88 | 1225.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.06 | 0.00 | 29.06 | 6.19 | 136.73 | 0.00 | 0.00 | 744.00 |
February | 36.52 | 0.00 | 36.52 | 6.28 | 145.11 | 0.00 | 0.00 | 672.00 |
March | 49.71 | 0.00 | 49.70 | 22.28 | 108.21 | 0.00 | 0.00 | 744.00 |
April | 62.48 | 0.40 | 62.07 | 34.16 | 94.47 | 0.00 | 0.00 | 720.00 |
May | 85.35 | 2.85 | 82.49 | 84.21 | 48.87 | 0.00 | 0.00 | 744.00 |
June | 93.56 | 10.45 | 83.12 | 134.13 | 19.74 | 0.00 | 0.00 | 720.00 |
July | 88.75 | 6.05 | 82.70 | 134.90 | 17.39 | 0.00 | 0.00 | 744.00 |
August | 70.66 | 1.90 | 68.76 | 109.08 | 19.95 | 0.00 | 0.00 | 744.00 |
September | 59.17 | 0.05 | 59.13 | 83.65 | 36.45 | 0.00 | 0.00 | 720.00 |
October | 42.33 | 0.00 | 42.33 | 27.18 | 98.25 | 0.00 | 0.00 | 744.00 |
November | 32.14 | 0.00 | 32.14 | 10.07 | 121.97 | 0.00 | 0.00 | 720.00 |
December | 27.18 | 0.00 | 27.18 | 4.92 | 161.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.51 | 1.81 | 54.70 | 55.03 | 83.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.18 | 0.00 | 27.18 | 4.92 | 17.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.56 | 10.45 | 83.12 | 134.90 | 161.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 338.69 | 207.18 | 131.51 | 253.21 | 475.75 | 0.00 | 0.00 | 744.00 |
February | 453.97 | 287.31 | 166.66 | 372.11 | 512.69 | 0.00 | 0.00 | 672.00 |
March | 546.88 | 319.22 | 227.65 | 508.02 | 385.16 | 0.00 | 0.00 | 744.00 |
April | 558.28 | 271.92 | 286.35 | 518.68 | 343.79 | 0.00 | 0.00 | 720.00 |
May | 654.38 | 273.91 | 380.47 | 737.46 | 181.01 | 0.00 | 0.00 | 744.00 |
June | 796.20 | 417.80 | 378.39 | 1084.95 | 75.02 | 0.00 | 0.00 | 720.00 |
July | 722.72 | 343.37 | 379.35 | 1007.24 | 66.21 | 0.00 | 0.00 | 744.00 |
August | 730.86 | 402.65 | 328.20 | 994.14 | 75.24 | 0.00 | 0.00 | 744.00 |
September | 609.19 | 331.17 | 278.02 | 787.57 | 133.24 | 0.00 | 0.00 | 720.00 |
October | 440.76 | 241.72 | 199.04 | 436.22 | 359.20 | 0.00 | 0.00 | 744.00 |
November | 342.06 | 192.77 | 149.29 | 270.16 | 436.19 | 0.00 | 0.00 | 720.00 |
December | 296.71 | 171.01 | 125.71 | 201.31 | 572.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 541.22 | 288.18 | 253.04 | 598.70 | 300.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 296.71 | 171.01 | 125.71 | 201.31 | 66.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 796.20 | 417.80 | 380.47 | 1084.95 | 572.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 279.49 | 230.08 | 49.41 | 314.46 | 118.86 | 0.00 | 0.00 | 744.00 |
February | 264.60 | 210.42 | 54.19 | 276.44 | 130.68 | 0.00 | 0.00 | 672.00 |
March | 198.73 | 131.36 | 67.36 | 191.97 | 104.07 | 0.00 | 0.00 | 744.00 |
April | 130.06 | 53.80 | 76.26 | 101.97 | 95.22 | 0.00 | 0.00 | 720.00 |
May | 118.18 | 22.71 | 95.47 | 113.51 | 51.85 | 0.00 | 0.00 | 744.00 |
June | 107.43 | 19.36 | 88.07 | 142.59 | 21.38 | 0.00 | 0.00 | 720.00 |
July | 110.97 | 18.88 | 92.09 | 151.65 | 18.34 | 0.00 | 0.00 | 744.00 |
August | 141.20 | 58.08 | 83.13 | 169.67 | 20.54 | 0.00 | 0.00 | 744.00 |
September | 185.54 | 104.30 | 81.24 | 223.34 | 36.73 | 0.00 | 0.00 | 720.00 |
October | 219.11 | 155.28 | 63.83 | 241.03 | 95.71 | 0.00 | 0.00 | 744.00 |
November | 268.48 | 214.16 | 54.32 | 305.27 | 111.73 | 0.00 | 0.00 | 720.00 |
December | 256.14 | 207.34 | 48.79 | 281.39 | 141.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 189.57 | 118.29 | 71.28 | 209.07 | 78.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 107.43 | 18.88 | 48.79 | 101.97 | 18.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.49 | 230.08 | 95.47 | 314.46 | 141.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.80 | 0.00 | 36.80 | 3.95 | 190.12 | 0.00 | 0.00 | 744.00 |
February | 46.25 | 0.00 | 46.25 | 4.81 | 196.72 | 0.00 | 0.00 | 672.00 |
March | 62.95 | 0.00 | 62.95 | 21.21 | 143.37 | 0.00 | 0.00 | 744.00 |
April | 79.13 | 0.51 | 78.61 | 34.95 | 123.07 | 0.00 | 0.00 | 720.00 |
May | 108.09 | 3.61 | 104.47 | 87.41 | 61.40 | 0.00 | 0.00 | 744.00 |
June | 118.49 | 13.23 | 105.26 | 143.17 | 23.67 | 0.00 | 0.00 | 720.00 |
July | 112.39 | 7.66 | 104.74 | 143.46 | 20.56 | 0.00 | 0.00 | 744.00 |
August | 89.49 | 2.41 | 87.08 | 111.87 | 25.47 | 0.00 | 0.00 | 744.00 |
September | 74.94 | 0.06 | 74.88 | 83.44 | 48.60 | 0.00 | 0.00 | 720.00 |
October | 53.61 | 0.00 | 53.61 | 24.74 | 132.73 | 0.00 | 0.00 | 744.00 |
November | 40.70 | 0.00 | 40.70 | 7.38 | 168.72 | 0.00 | 0.00 | 720.00 |
December | 34.43 | 0.00 | 34.43 | 3.47 | 219.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 71.57 | 2.30 | 69.27 | 56.12 | 112.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.43 | 0.00 | 34.43 | 3.47 | 20.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 118.49 | 13.23 | 105.26 | 143.46 | 219.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.92 | 0.00 | 32.92 | 3.54 | 170.10 | 0.00 | 0.00 | 744.00 |
February | 41.38 | 0.00 | 41.38 | 4.31 | 176.00 | 0.00 | 0.00 | 672.00 |
March | 56.32 | 0.00 | 56.32 | 18.98 | 128.27 | 0.00 | 0.00 | 744.00 |
April | 70.79 | 0.46 | 70.34 | 31.27 | 110.11 | 0.00 | 0.00 | 720.00 |
May | 96.71 | 3.23 | 93.47 | 78.20 | 54.94 | 0.00 | 0.00 | 744.00 |
June | 106.02 | 11.84 | 94.18 | 128.09 | 21.18 | 0.00 | 0.00 | 720.00 |
July | 100.56 | 6.85 | 93.71 | 128.36 | 18.40 | 0.00 | 0.00 | 744.00 |
August | 80.06 | 2.16 | 77.91 | 100.09 | 22.79 | 0.00 | 0.00 | 744.00 |
September | 67.05 | 0.05 | 66.99 | 74.66 | 43.48 | 0.00 | 0.00 | 720.00 |
October | 47.97 | 0.00 | 47.97 | 22.14 | 118.76 | 0.00 | 0.00 | 744.00 |
November | 36.41 | 0.00 | 36.41 | 6.60 | 150.95 | 0.00 | 0.00 | 720.00 |
December | 30.80 | 0.00 | 30.80 | 3.10 | 196.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 64.03 | 2.05 | 61.98 | 50.21 | 100.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 30.80 | 0.00 | 30.80 | 3.10 | 18.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 106.02 | 11.84 | 94.18 | 128.36 | 196.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1043.44 | 858.96 | 184.47 | 1132.26 | 467.87 | 0.00 | 0.00 | 744.00 |
February | 987.84 | 785.55 | 202.29 | 1000.51 | 507.52 | 0.00 | 0.00 | 672.00 |
March | 741.90 | 490.42 | 251.49 | 687.60 | 402.14 | 0.00 | 0.00 | 744.00 |
April | 485.55 | 200.84 | 284.72 | 355.40 | 363.33 | 0.00 | 0.00 | 720.00 |
May | 441.21 | 84.79 | 356.42 | 369.48 | 192.39 | 0.00 | 0.00 | 744.00 |
June | 401.05 | 72.28 | 328.78 | 457.36 | 76.47 | 0.00 | 0.00 | 720.00 |
July | 414.30 | 70.50 | 343.80 | 488.58 | 64.50 | 0.00 | 0.00 | 744.00 |
August | 527.15 | 216.81 | 310.34 | 559.52 | 77.26 | 0.00 | 0.00 | 744.00 |
September | 692.66 | 389.37 | 303.29 | 766.22 | 141.82 | 0.00 | 0.00 | 720.00 |
October | 818.02 | 579.72 | 238.29 | 860.93 | 376.23 | 0.00 | 0.00 | 744.00 |
November | 1002.31 | 799.52 | 202.80 | 1099.49 | 440.11 | 0.00 | 0.00 | 720.00 |
December | 956.23 | 774.08 | 182.15 | 1017.30 | 547.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 707.72 | 441.61 | 266.10 | 731.38 | 303.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 401.05 | 70.50 | 182.15 | 355.40 | 64.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1043.44 | 858.96 | 356.42 | 1132.26 | 547.73 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379083E+10 | 0.312063E+10 | 0.670201E+09 | 0.406085E+10 | 0.163387E+10 |
February | 0.324154E+10 | 0.257774E+10 | 0.663800E+09 | 0.325428E+10 | 0.156870E+10 |
March | 0.269536E+10 | 0.178170E+10 | 0.913657E+09 | 0.247274E+10 | 0.136986E+10 |
April | 0.170713E+10 | 0.706102E+09 | 0.100103E+10 | 0.124273E+10 | 0.118173E+10 |
May | 0.160292E+10 | 0.308030E+09 | 0.129489E+10 | 0.132071E+10 | 0.658614E+09 |
June | 0.141004E+10 | 0.254111E+09 | 0.115592E+10 | 0.154647E+10 | 0.273877E+09 |
July | 0.150515E+10 | 0.256126E+09 | 0.124902E+10 | 0.171240E+10 | 0.240211E+09 |
August | 0.191516E+10 | 0.787688E+09 | 0.112747E+10 | 0.196758E+10 | 0.286284E+09 |
September | 0.243529E+10 | 0.136897E+10 | 0.106632E+10 | 0.262721E+10 | 0.499107E+09 |
October | 0.297187E+10 | 0.210615E+10 | 0.865719E+09 | 0.307697E+10 | 0.129832E+10 |
November | 0.352396E+10 | 0.281096E+10 | 0.712994E+09 | 0.381653E+10 | 0.147553E+10 |
December | 0.347401E+10 | 0.281224E+10 | 0.661772E+09 | 0.367988E+10 | 0.187360E+10 |
Annual Sum or Average | 0.302733E+11 | 0.188905E+11 | 0.113828E+11 | 0.307783E+11 | 0.123597E+11 |
Minimum of Months | 0.141004E+10 | 0.254111E+09 | 0.661772E+09 | 0.124273E+10 | 0.240211E+09 |
Maximum of Months | 0.379083E+10 | 0.312063E+10 | 0.129489E+10 | 0.406085E+10 | 0.187360E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106747E+11 | 0.878748E+10 | 0.188724E+10 | 0.114223E+11 | 0.459749E+10 |
February | 0.912797E+10 | 0.725875E+10 | 0.186922E+10 | 0.914979E+10 | 0.441735E+10 |
March | 0.758995E+10 | 0.501715E+10 | 0.257280E+10 | 0.694906E+10 | 0.386784E+10 |
April | 0.480716E+10 | 0.198834E+10 | 0.281882E+10 | 0.347226E+10 | 0.333942E+10 |
May | 0.451372E+10 | 0.867393E+09 | 0.364633E+10 | 0.368419E+10 | 0.184433E+10 |
June | 0.397057E+10 | 0.715561E+09 | 0.325501E+10 | 0.432997E+10 | 0.750592E+09 |
July | 0.423840E+10 | 0.721233E+09 | 0.351717E+10 | 0.479607E+10 | 0.659150E+09 |
August | 0.539296E+10 | 0.221808E+10 | 0.317489E+10 | 0.551537E+10 | 0.787253E+09 |
September | 0.685761E+10 | 0.385493E+10 | 0.300269E+10 | 0.738915E+10 | 0.138994E+10 |
October | 0.836860E+10 | 0.593079E+10 | 0.243781E+10 | 0.866408E+10 | 0.366233E+10 |
November | 0.992324E+10 | 0.791549E+10 | 0.200774E+10 | 0.107372E+11 | 0.415596E+10 |
December | 0.978259E+10 | 0.791909E+10 | 0.186351E+10 | 0.103436E+11 | 0.529208E+10 |
Annual Sum or Average | 0.852475E+11 | 0.531943E+11 | 0.320532E+11 | 0.864531E+11 | 0.347637E+11 |
Minimum of Months | 0.397057E+10 | 0.715561E+09 | 0.186351E+10 | 0.347226E+10 | 0.659150E+09 |
Maximum of Months | 0.106747E+11 | 0.878748E+10 | 0.364633E+10 | 0.114223E+11 | 0.529208E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138671E+11 | 0.114154E+11 | 0.245163E+10 | 0.151452E+11 | 0.606834E+10 |
February | 0.118578E+11 | 0.942953E+10 | 0.242822E+10 | 0.121449E+11 | 0.585351E+10 |
March | 0.985977E+10 | 0.651756E+10 | 0.334221E+10 | 0.921807E+10 | 0.515821E+10 |
April | 0.624478E+10 | 0.258296E+10 | 0.366181E+10 | 0.461339E+10 | 0.448361E+10 |
May | 0.586358E+10 | 0.112679E+10 | 0.473679E+10 | 0.492693E+10 | 0.248426E+10 |
June | 0.515799E+10 | 0.929554E+09 | 0.422844E+10 | 0.580800E+10 | 0.997342E+09 |
July | 0.550592E+10 | 0.936923E+09 | 0.456900E+10 | 0.642395E+10 | 0.871419E+09 |
August | 0.700577E+10 | 0.288141E+10 | 0.412436E+10 | 0.737159E+10 | 0.103454E+10 |
September | 0.890843E+10 | 0.500777E+10 | 0.390066E+10 | 0.981601E+10 | 0.183113E+10 |
October | 0.108713E+11 | 0.770444E+10 | 0.316685E+10 | 0.114940E+11 | 0.486182E+10 |
November | 0.128908E+11 | 0.102827E+11 | 0.260817E+10 | 0.142404E+11 | 0.549310E+10 |
December | 0.127081E+11 | 0.102873E+11 | 0.242080E+10 | 0.136928E+11 | 0.700913E+10 |
Annual Sum or Average | 0.110741E+12 | 0.691024E+11 | 0.416390E+11 | 0.114895E+12 | 0.461464E+11 |
Minimum of Months | 0.515799E+10 | 0.929554E+09 | 0.242080E+10 | 0.461339E+10 | 0.871419E+09 |
Maximum of Months | 0.138671E+11 | 0.114154E+11 | 0.473679E+10 | 0.151452E+11 | 0.700913E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.747984E+09 | 0.615744E+09 | 0.132240E+09 | 0.805394E+09 | 0.337172E+09 |
February | 0.639602E+09 | 0.508625E+09 | 0.130977E+09 | 0.642994E+09 | 0.328091E+09 |
March | 0.531832E+09 | 0.351555E+09 | 0.180278E+09 | 0.486590E+09 | 0.289217E+09 |
April | 0.336841E+09 | 0.139324E+09 | 0.197517E+09 | 0.241070E+09 | 0.252605E+09 |
May | 0.316279E+09 | 60778728.94 | 0.255501E+09 | 0.252035E+09 | 0.142127E+09 |
June | 0.278220E+09 | 50139771.17 | 0.228080E+09 | 0.298188E+09 | 58335724.00 |
July | 0.296987E+09 | 50537227.78 | 0.246450E+09 | 0.331889E+09 | 50929331.18 |
August | 0.377888E+09 | 0.155422E+09 | 0.222466E+09 | 0.383489E+09 | 60781091.95 |
September | 0.480517E+09 | 0.270117E+09 | 0.210400E+09 | 0.516661E+09 | 0.104766E+09 |
October | 0.586393E+09 | 0.415574E+09 | 0.170819E+09 | 0.608824E+09 | 0.271558E+09 |
November | 0.695327E+09 | 0.554643E+09 | 0.140684E+09 | 0.756985E+09 | 0.306197E+09 |
December | 0.685472E+09 | 0.554895E+09 | 0.130577E+09 | 0.726477E+09 | 0.391966E+09 |
Annual Sum or Average | 0.597334E+10 | 0.372736E+10 | 0.224599E+10 | 0.605060E+10 | 0.259375E+10 |
Minimum of Months | 0.278220E+09 | 50139771.17 | 0.130577E+09 | 0.241070E+09 | 50929331.18 |
Maximum of Months | 0.747984E+09 | 0.615744E+09 | 0.255501E+09 | 0.805394E+09 | 0.391966E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484129E+09 | 0.306849E+09 | 0.177279E+09 | 0.349801E+09 | 0.704974E+09 |
February | 0.528156E+09 | 0.327617E+09 | 0.200539E+09 | 0.393284E+09 | 0.655920E+09 |
March | 0.682012E+09 | 0.375719E+09 | 0.306293E+09 | 0.577054E+09 | 0.542802E+09 |
April | 0.622502E+09 | 0.263721E+09 | 0.358780E+09 | 0.503370E+09 | 0.460651E+09 |
May | 0.786368E+09 | 0.277695E+09 | 0.508673E+09 | 0.777749E+09 | 0.257175E+09 |
June | 0.929000E+09 | 0.446552E+09 | 0.482448E+09 | 0.114162E+10 | 0.108199E+09 |
July | 0.781321E+09 | 0.285222E+09 | 0.496099E+09 | 0.970231E+09 | 94600205.58 |
August | 0.818218E+09 | 0.404327E+09 | 0.413891E+09 | 0.995723E+09 | 0.111755E+09 |
September | 0.704624E+09 | 0.339044E+09 | 0.365580E+09 | 0.804475E+09 | 0.196620E+09 |
October | 0.609645E+09 | 0.348451E+09 | 0.261194E+09 | 0.555563E+09 | 0.517542E+09 |
November | 0.484494E+09 | 0.294275E+09 | 0.190220E+09 | 0.371374E+09 | 0.612512E+09 |
December | 0.403828E+09 | 0.238487E+09 | 0.165341E+09 | 0.257031E+09 | 0.811285E+09 |
Annual Sum or Average | 0.783430E+10 | 0.390796E+10 | 0.392634E+10 | 0.769727E+10 | 0.507404E+10 |
Minimum of Months | 0.403828E+09 | 0.238487E+09 | 0.165341E+09 | 0.257031E+09 | 94600205.58 |
Maximum of Months | 0.929000E+09 | 0.446552E+09 | 0.508673E+09 | 0.114162E+10 | 0.811285E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77758234.20 | 0.00 | 77758234.20 | 10044355.99 | 0.391741E+09 |
February | 88274729.39 | 0.00 | 88274729.39 | 10313291.70 | 0.367837E+09 |
March | 0.133024E+09 | 6541.53 | 0.133017E+09 | 44435623.24 | 0.301316E+09 |
April | 0.161814E+09 | 1048792.62 | 0.160765E+09 | 69086209.94 | 0.250662E+09 |
May | 0.228407E+09 | 7637006.39 | 0.220770E+09 | 0.173323E+09 | 0.133042E+09 |
June | 0.242320E+09 | 27055478.52 | 0.215265E+09 | 0.274261E+09 | 52883051.98 |
July | 0.237510E+09 | 16181376.19 | 0.221329E+09 | 0.285727E+09 | 47399693.05 |
August | 0.189101E+09 | 5091150.63 | 0.184010E+09 | 0.221297E+09 | 58136802.27 |
September | 0.153247E+09 | 119727.22 | 0.153128E+09 | 0.159785E+09 | 0.104223E+09 |
October | 0.113296E+09 | 0.00 | 0.113296E+09 | 50642301.02 | 0.279282E+09 |
November | 83231841.04 | 0.00 | 83231841.04 | 16746655.63 | 0.338071E+09 |
December | 72752556.39 | 0.00 | 72752556.39 | 8730729.98 | 0.450808E+09 |
Annual Sum or Average | 0.178074E+10 | 57140073.09 | 0.172360E+10 | 0.132439E+10 | 0.277540E+10 |
Minimum of Months | 72752556.39 | 0.00 | 72752556.39 | 8730729.98 | 47399693.05 |
Maximum of Months | 0.242320E+09 | 27055478.52 | 0.221329E+09 | 0.285727E+09 | 0.450808E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484129E+09 | 0.306849E+09 | 0.177279E+09 | 0.366839E+09 | 0.685526E+09 |
February | 0.528156E+09 | 0.327617E+09 | 0.200539E+09 | 0.408733E+09 | 0.641781E+09 |
March | 0.682012E+09 | 0.375719E+09 | 0.306293E+09 | 0.590187E+09 | 0.536005E+09 |
April | 0.622502E+09 | 0.263721E+09 | 0.358780E+09 | 0.509856E+09 | 0.457489E+09 |
May | 0.786368E+09 | 0.277695E+09 | 0.508673E+09 | 0.780558E+09 | 0.256029E+09 |
June | 0.929000E+09 | 0.446552E+09 | 0.482448E+09 | 0.114251E+10 | 0.107578E+09 |
July | 0.781321E+09 | 0.285222E+09 | 0.496099E+09 | 0.971533E+09 | 93998297.63 |
August | 0.818218E+09 | 0.404327E+09 | 0.413891E+09 | 0.999837E+09 | 0.110511E+09 |
September | 0.704624E+09 | 0.339044E+09 | 0.365580E+09 | 0.813255E+09 | 0.193632E+09 |
October | 0.609645E+09 | 0.348451E+09 | 0.261194E+09 | 0.569973E+09 | 0.510240E+09 |
November | 0.484494E+09 | 0.294275E+09 | 0.190220E+09 | 0.388133E+09 | 0.598033E+09 |
December | 0.403828E+09 | 0.238487E+09 | 0.165341E+09 | 0.271513E+09 | 0.793708E+09 |
Annual Sum or Average | 0.783430E+10 | 0.390796E+10 | 0.392634E+10 | 0.781293E+10 | 0.498453E+10 |
Minimum of Months | 0.403828E+09 | 0.238487E+09 | 0.165341E+09 | 0.271513E+09 | 93998297.63 |
Maximum of Months | 0.929000E+09 | 0.446552E+09 | 0.508673E+09 | 0.114251E+10 | 0.793708E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598268E+09 | 0.492497E+09 | 0.105771E+09 | 0.633854E+09 | 0.294364E+09 |
February | 0.511580E+09 | 0.406819E+09 | 0.104761E+09 | 0.506890E+09 | 0.277781E+09 |
March | 0.425381E+09 | 0.281188E+09 | 0.144193E+09 | 0.383813E+09 | 0.247117E+09 |
April | 0.269419E+09 | 0.111437E+09 | 0.157982E+09 | 0.188002E+09 | 0.221696E+09 |
May | 0.252973E+09 | 48613315.27 | 0.204360E+09 | 0.193372E+09 | 0.133646E+09 |
June | 0.222532E+09 | 40103841.36 | 0.182428E+09 | 0.232937E+09 | 61022831.39 |
July | 0.237542E+09 | 40421743.43 | 0.197121E+09 | 0.258002E+09 | 55964196.64 |
August | 0.302250E+09 | 0.124313E+09 | 0.177938E+09 | 0.300060E+09 | 65086395.48 |
September | 0.384337E+09 | 0.216051E+09 | 0.168287E+09 | 0.406362E+09 | 0.103099E+09 |
October | 0.469021E+09 | 0.332393E+09 | 0.136628E+09 | 0.480466E+09 | 0.240717E+09 |
November | 0.556151E+09 | 0.443626E+09 | 0.112525E+09 | 0.597593E+09 | 0.267865E+09 |
December | 0.548269E+09 | 0.443828E+09 | 0.104441E+09 | 0.572182E+09 | 0.334331E+09 |
Annual Sum or Average | 0.477772E+10 | 0.298129E+10 | 0.179643E+10 | 0.475353E+10 | 0.230269E+10 |
Minimum of Months | 0.222532E+09 | 40103841.36 | 0.104441E+09 | 0.188002E+09 | 55964196.64 |
Maximum of Months | 0.598268E+09 | 0.492497E+09 | 0.204360E+09 | 0.633854E+09 | 0.334331E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62214833.19 | 0.00 | 62214833.19 | 7333758.76 | 0.322967E+09 |
February | 70629144.56 | 0.00 | 70629144.56 | 8086096.38 | 0.300967E+09 |
March | 0.106433E+09 | 5233.92 | 0.106428E+09 | 36383164.32 | 0.246811E+09 |
April | 0.129468E+09 | 839145.32 | 0.128629E+09 | 56014143.28 | 0.206832E+09 |
May | 0.182749E+09 | 6110414.98 | 0.176639E+09 | 0.143113E+09 | 0.107431E+09 |
June | 0.193882E+09 | 21647251.90 | 0.172235E+09 | 0.228413E+09 | 40958804.91 |
July | 0.190033E+09 | 12946816.89 | 0.177087E+09 | 0.236211E+09 | 37003309.58 |
August | 0.151301E+09 | 4073460.39 | 0.147228E+09 | 0.184892E+09 | 45316062.37 |
September | 0.122614E+09 | 95794.47 | 0.122518E+09 | 0.133711E+09 | 82737200.18 |
October | 90649055.63 | 0.00 | 90649055.63 | 42481662.41 | 0.228260E+09 |
November | 66594299.12 | 0.00 | 66594299.12 | 13167986.20 | 0.278040E+09 |
December | 58209760.13 | 0.00 | 58209760.13 | 6447626.58 | 0.373340E+09 |
Annual Sum or Average | 0.142478E+10 | 45718117.87 | 0.137906E+10 | 0.109625E+10 | 0.227066E+10 |
Minimum of Months | 58209760.13 | 0.00 | 58209760.13 | 6447626.58 | 37003309.58 |
Maximum of Months | 0.193882E+09 | 21647251.90 | 0.177087E+09 | 0.236211E+09 | 0.373340E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.453236E+09 | 0.277245E+09 | 0.175991E+09 | 0.298975E+09 | 0.692863E+09 |
February | 0.548707E+09 | 0.347271E+09 | 0.201436E+09 | 0.416409E+09 | 0.653433E+09 |
March | 0.731829E+09 | 0.427182E+09 | 0.304647E+09 | 0.623495E+09 | 0.531560E+09 |
April | 0.722987E+09 | 0.352150E+09 | 0.370837E+09 | 0.615826E+09 | 0.449320E+09 |
May | 0.875693E+09 | 0.366544E+09 | 0.509149E+09 | 0.875680E+09 | 0.240903E+09 |
June | 0.103110E+10 | 0.541067E+09 | 0.490032E+09 | 0.126118E+10 | 97919838.21 |
July | 0.967141E+09 | 0.459498E+09 | 0.507643E+09 | 0.119786E+10 | 88491613.13 |
August | 0.978031E+09 | 0.538831E+09 | 0.439200E+09 | 0.118540E+10 | 0.107357E+09 |
September | 0.788924E+09 | 0.428881E+09 | 0.360043E+09 | 0.894038E+09 | 0.185282E+09 |
October | 0.589829E+09 | 0.323473E+09 | 0.266356E+09 | 0.516861E+09 | 0.506305E+09 |
November | 0.442981E+09 | 0.249649E+09 | 0.193331E+09 | 0.306933E+09 | 0.607747E+09 |
December | 0.397061E+09 | 0.228841E+09 | 0.168220E+09 | 0.239177E+09 | 0.805673E+09 |
Annual Sum or Average | 0.852752E+10 | 0.454063E+10 | 0.398689E+10 | 0.843184E+10 | 0.496685E+10 |
Minimum of Months | 0.397061E+09 | 0.228841E+09 | 0.168220E+09 | 0.239177E+09 | 88491613.13 |
Maximum of Months | 0.103110E+10 | 0.541067E+09 | 0.509149E+09 | 0.126118E+10 | 0.805673E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.747984E+09 | 0.615744E+09 | 0.132240E+09 | 0.803881E+09 | 0.335932E+09 |
February | 0.639602E+09 | 0.508625E+09 | 0.130977E+09 | 0.640482E+09 | 0.326682E+09 |
March | 0.531832E+09 | 0.351555E+09 | 0.180278E+09 | 0.482859E+09 | 0.288200E+09 |
April | 0.336841E+09 | 0.139324E+09 | 0.197517E+09 | 0.237348E+09 | 0.252691E+09 |
May | 0.316279E+09 | 60778728.94 | 0.255501E+09 | 0.248390E+09 | 0.142201E+09 |
June | 0.278220E+09 | 50139771.17 | 0.228080E+09 | 0.294957E+09 | 58220652.04 |
July | 0.296987E+09 | 50537227.78 | 0.246450E+09 | 0.327867E+09 | 51112737.88 |
August | 0.377888E+09 | 0.155422E+09 | 0.222466E+09 | 0.379216E+09 | 60515077.72 |
September | 0.480517E+09 | 0.270117E+09 | 0.210400E+09 | 0.513816E+09 | 0.104317E+09 |
October | 0.586393E+09 | 0.415574E+09 | 0.170819E+09 | 0.606872E+09 | 0.270279E+09 |
November | 0.695327E+09 | 0.554643E+09 | 0.140684E+09 | 0.756077E+09 | 0.304711E+09 |
December | 0.685472E+09 | 0.554895E+09 | 0.130577E+09 | 0.725176E+09 | 0.390935E+09 |
Annual Sum or Average | 0.597334E+10 | 0.372736E+10 | 0.224599E+10 | 0.601694E+10 | 0.258580E+10 |
Minimum of Months | 0.278220E+09 | 50139771.17 | 0.130577E+09 | 0.237348E+09 | 51112737.88 |
Maximum of Months | 0.747984E+09 | 0.615744E+09 | 0.255501E+09 | 0.803881E+09 | 0.390935E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77758234.20 | 0.00 | 77758234.20 | 9348539.92 | 0.390556E+09 |
February | 88274729.39 | 0.00 | 88274729.39 | 9151173.40 | 0.367879E+09 |
March | 0.133024E+09 | 6541.53 | 0.133017E+09 | 41605249.93 | 0.302043E+09 |
April | 0.161814E+09 | 1048792.62 | 0.160765E+09 | 65552924.74 | 0.251574E+09 |
May | 0.228407E+09 | 7637006.39 | 0.220770E+09 | 0.169542E+09 | 0.133042E+09 |
June | 0.242320E+09 | 27055478.52 | 0.215265E+09 | 0.270563E+09 | 52166392.18 |
July | 0.237510E+09 | 16181376.19 | 0.221329E+09 | 0.281349E+09 | 47198919.13 |
August | 0.189101E+09 | 5091150.63 | 0.184010E+09 | 0.216641E+09 | 57887328.22 |
September | 0.153247E+09 | 119727.22 | 0.153128E+09 | 0.156568E+09 | 0.104334E+09 |
October | 0.113296E+09 | 0.00 | 0.113296E+09 | 48957681.30 | 0.278885E+09 |
November | 83231841.04 | 0.00 | 83231841.04 | 15804977.38 | 0.335994E+09 |
December | 72752556.39 | 0.00 | 72752556.39 | 8117677.97 | 0.449770E+09 |
Annual Sum or Average | 0.178074E+10 | 57140073.09 | 0.172360E+10 | 0.129320E+10 | 0.277133E+10 |
Minimum of Months | 72752556.39 | 0.00 | 72752556.39 | 8117677.97 | 47198919.13 |
Maximum of Months | 0.242320E+09 | 27055478.52 | 0.221329E+09 | 0.281349E+09 | 0.449770E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.453236E+09 | 0.277245E+09 | 0.175991E+09 | 0.310126E+09 | 0.665916E+09 |
February | 0.548707E+09 | 0.347271E+09 | 0.201436E+09 | 0.425473E+09 | 0.632788E+09 |
March | 0.731829E+09 | 0.427182E+09 | 0.304647E+09 | 0.634006E+09 | 0.523265E+09 |
April | 0.722987E+09 | 0.352150E+09 | 0.370837E+09 | 0.621318E+09 | 0.446018E+09 |
May | 0.875693E+09 | 0.366544E+09 | 0.509149E+09 | 0.878244E+09 | 0.239807E+09 |
June | 0.103110E+10 | 0.541067E+09 | 0.490032E+09 | 0.126236E+10 | 97595215.31 |
July | 0.967141E+09 | 0.459498E+09 | 0.507643E+09 | 0.119926E+10 | 88084965.93 |
August | 0.978031E+09 | 0.538831E+09 | 0.439200E+09 | 0.118905E+10 | 0.106162E+09 |
September | 0.788924E+09 | 0.428881E+09 | 0.360043E+09 | 0.901535E+09 | 0.182382E+09 |
October | 0.589829E+09 | 0.323473E+09 | 0.266356E+09 | 0.529707E+09 | 0.498410E+09 |
November | 0.442981E+09 | 0.249649E+09 | 0.193331E+09 | 0.318607E+09 | 0.587067E+09 |
December | 0.397061E+09 | 0.228841E+09 | 0.168220E+09 | 0.249006E+09 | 0.782165E+09 |
Annual Sum or Average | 0.852752E+10 | 0.454063E+10 | 0.398689E+10 | 0.851870E+10 | 0.484966E+10 |
Minimum of Months | 0.397061E+09 | 0.228841E+09 | 0.168220E+09 | 0.249006E+09 | 88084965.93 |
Maximum of Months | 0.103110E+10 | 0.541067E+09 | 0.509149E+09 | 0.126236E+10 | 0.782165E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98475897.34 | 0.00 | 98475897.34 | 12110206.56 | 0.506064E+09 |
February | 0.111794E+09 | 0.00 | 0.111794E+09 | 13426102.23 | 0.471227E+09 |
March | 0.168466E+09 | 8284.44 | 0.168458E+09 | 60975397.34 | 0.380593E+09 |
April | 0.204927E+09 | 1328229.68 | 0.203599E+09 | 94793376.50 | 0.315698E+09 |
May | 0.289262E+09 | 9671786.73 | 0.279591E+09 | 0.241024E+09 | 0.161691E+09 |
June | 0.306883E+09 | 34264056.43 | 0.272619E+09 | 0.378723E+09 | 59128300.07 |
July | 0.300792E+09 | 20492691.95 | 0.280299E+09 | 0.391994E+09 | 52593713.37 |
August | 0.239485E+09 | 6447621.03 | 0.233037E+09 | 0.307753E+09 | 65535427.83 |
September | 0.194078E+09 | 151626.96 | 0.193926E+09 | 0.222502E+09 | 0.123507E+09 |
October | 0.143483E+09 | 0.00 | 0.143483E+09 | 70921822.30 | 0.351971E+09 |
November | 0.105408E+09 | 0.00 | 0.105408E+09 | 21484858.61 | 0.433119E+09 |
December | 92136522.24 | 0.00 | 92136522.24 | 10409744.69 | 0.584261E+09 |
Annual Sum or Average | 0.225519E+10 | 72364297.23 | 0.218283E+10 | 0.182612E+10 | 0.350539E+10 |
Minimum of Months | 92136522.24 | 0.00 | 92136522.24 | 10409744.69 | 52593713.37 |
Maximum of Months | 0.306883E+09 | 34264056.43 | 0.280299E+09 | 0.391994E+09 | 0.584261E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36302293.32 | 0.00 | 36302293.32 | 4464323.58 | 0.186556E+09 |
February | 41212035.65 | 0.00 | 41212035.65 | 4949417.21 | 0.173713E+09 |
March | 62103532.85 | 3053.99 | 62100478.86 | 22478056.25 | 0.140302E+09 |
April | 75544586.01 | 489640.46 | 75054945.56 | 34944763.66 | 0.116379E+09 |
May | 0.106634E+09 | 3565421.07 | 0.103069E+09 | 88851319.48 | 59605929.65 |
June | 0.113130E+09 | 12631149.96 | 0.100499E+09 | 0.139613E+09 | 21797139.72 |
July | 0.110884E+09 | 7554454.79 | 0.103330E+09 | 0.144505E+09 | 19388220.48 |
August | 88284070.84 | 2376860.09 | 85907210.75 | 0.113450E+09 | 24159072.31 |
September | 71545208.71 | 55895.98 | 71489312.73 | 82023590.73 | 45529897.54 |
October | 52893633.85 | 0.00 | 52893633.85 | 26144720.34 | 0.129751E+09 |
November | 38857707.34 | 0.00 | 38857707.34 | 7920208.50 | 0.159666E+09 |
December | 33965337.17 | 0.00 | 33965337.17 | 3837462.93 | 0.215383E+09 |
Annual Sum or Average | 0.831357E+09 | 26676476.33 | 0.804680E+09 | 0.673182E+09 | 0.129223E+10 |
Minimum of Months | 33965337.17 | 0.00 | 33965337.17 | 3837462.93 | 19388220.48 |
Maximum of Months | 0.113130E+09 | 12631149.96 | 0.103330E+09 | 0.144505E+09 | 0.215383E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.349006E+09 | 0.287304E+09 | 61702713.33 | 0.381475E+09 | 0.156006E+09 |
February | 0.298436E+09 | 0.237322E+09 | 61113455.30 | 0.305018E+09 | 0.152183E+09 |
March | 0.248151E+09 | 0.164034E+09 | 84116767.22 | 0.232263E+09 | 0.133227E+09 |
April | 0.157168E+09 | 65007971.75 | 92160518.23 | 0.116649E+09 | 0.116129E+09 |
May | 0.147575E+09 | 28359110.00 | 0.119216E+09 | 0.125978E+09 | 62978652.62 |
June | 0.129816E+09 | 23395015.18 | 0.106421E+09 | 0.150754E+09 | 23799365.65 |
July | 0.138573E+09 | 23580466.83 | 0.114993E+09 | 0.166236E+09 | 20563435.75 |
August | 0.176321E+09 | 72519298.88 | 0.103802E+09 | 0.189992E+09 | 24752223.95 |
September | 0.224207E+09 | 0.126035E+09 | 98171856.46 | 0.250512E+09 | 44881388.24 |
October | 0.273609E+09 | 0.193905E+09 | 79703281.78 | 0.290404E+09 | 0.124557E+09 |
November | 0.324437E+09 | 0.258794E+09 | 65642509.24 | 0.358772E+09 | 0.141438E+09 |
December | 0.319839E+09 | 0.258912E+09 | 60926696.54 | 0.343199E+09 | 0.182365E+09 |
Annual Sum or Average | 0.278714E+10 | 0.173917E+10 | 0.104797E+10 | 0.291125E+10 | 0.118288E+10 |
Minimum of Months | 0.129816E+09 | 23395015.18 | 60926696.54 | 0.116649E+09 | 20563435.75 |
Maximum of Months | 0.349006E+09 | 0.287304E+09 | 0.119216E+09 | 0.381475E+09 | 0.182365E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947275E+09 | 0.779801E+09 | 0.167474E+09 | 0.103540E+10 | 0.423433E+09 |
February | 0.810016E+09 | 0.644142E+09 | 0.165874E+09 | 0.827881E+09 | 0.413055E+09 |
March | 0.673532E+09 | 0.445222E+09 | 0.228310E+09 | 0.630409E+09 | 0.361605E+09 |
April | 0.426587E+09 | 0.176445E+09 | 0.250142E+09 | 0.316609E+09 | 0.315198E+09 |
May | 0.400548E+09 | 76972425.27 | 0.323575E+09 | 0.341929E+09 | 0.170937E+09 |
June | 0.352348E+09 | 63498856.54 | 0.288849E+09 | 0.409177E+09 | 64596346.43 |
July | 0.376116E+09 | 64002210.26 | 0.312113E+09 | 0.451197E+09 | 55813370.78 |
August | 0.478572E+09 | 0.196832E+09 | 0.281739E+09 | 0.515677E+09 | 67182598.75 |
September | 0.608545E+09 | 0.342086E+09 | 0.266458E+09 | 0.679941E+09 | 0.121817E+09 |
October | 0.742630E+09 | 0.526299E+09 | 0.216331E+09 | 0.788217E+09 | 0.338074E+09 |
November | 0.880588E+09 | 0.702421E+09 | 0.178167E+09 | 0.973780E+09 | 0.383891E+09 |
December | 0.868107E+09 | 0.702740E+09 | 0.165368E+09 | 0.931511E+09 | 0.494975E+09 |
Annual Sum or Average | 0.756486E+10 | 0.472046E+10 | 0.284440E+10 | 0.790173E+10 | 0.321058E+10 |
Minimum of Months | 0.352348E+09 | 63498856.54 | 0.165368E+09 | 0.316609E+09 | 55813370.78 |
Maximum of Months | 0.947275E+09 | 0.779801E+09 | 0.323575E+09 | 0.103540E+10 | 0.494975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.748598E+09 | 0.616249E+09 | 0.132349E+09 | 0.803766E+09 | 0.336144E+09 |
February | 0.640127E+09 | 0.509042E+09 | 0.131085E+09 | 0.640611E+09 | 0.328663E+09 |
March | 0.532268E+09 | 0.351843E+09 | 0.180425E+09 | 0.484780E+09 | 0.289412E+09 |
April | 0.337117E+09 | 0.139438E+09 | 0.197679E+09 | 0.239586E+09 | 0.252895E+09 |
May | 0.316539E+09 | 60828588.44 | 0.255710E+09 | 0.248554E+09 | 0.143441E+09 |
June | 0.278448E+09 | 50180903.05 | 0.228267E+09 | 0.294273E+09 | 59119347.15 |
July | 0.297231E+09 | 50578685.72 | 0.246652E+09 | 0.327945E+09 | 51756219.15 |
August | 0.378198E+09 | 0.155550E+09 | 0.222649E+09 | 0.379759E+09 | 61758170.39 |
September | 0.480911E+09 | 0.270339E+09 | 0.210573E+09 | 0.513860E+09 | 0.105449E+09 |
October | 0.586874E+09 | 0.415915E+09 | 0.170959E+09 | 0.606571E+09 | 0.271769E+09 |
November | 0.695897E+09 | 0.555098E+09 | 0.140799E+09 | 0.754596E+09 | 0.306030E+09 |
December | 0.686035E+09 | 0.555350E+09 | 0.130684E+09 | 0.724169E+09 | 0.392053E+09 |
Annual Sum or Average | 0.597824E+10 | 0.373041E+10 | 0.224783E+10 | 0.601847E+10 | 0.259849E+10 |
Minimum of Months | 0.278448E+09 | 50180903.05 | 0.130684E+09 | 0.239586E+09 | 51756219.15 |
Maximum of Months | 0.748598E+09 | 0.616249E+09 | 0.255710E+09 | 0.803766E+09 | 0.392053E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484526E+09 | 0.307101E+09 | 0.177425E+09 | 0.348256E+09 | 0.701354E+09 |
February | 0.528589E+09 | 0.327886E+09 | 0.200703E+09 | 0.390484E+09 | 0.656227E+09 |
March | 0.682572E+09 | 0.376028E+09 | 0.306544E+09 | 0.573012E+09 | 0.542740E+09 |
April | 0.623012E+09 | 0.263938E+09 | 0.359075E+09 | 0.498797E+09 | 0.460674E+09 |
May | 0.787013E+09 | 0.277923E+09 | 0.509090E+09 | 0.768770E+09 | 0.258971E+09 |
June | 0.929762E+09 | 0.446919E+09 | 0.482844E+09 | 0.113187E+10 | 0.109609E+09 |
July | 0.781962E+09 | 0.285456E+09 | 0.496506E+09 | 0.961045E+09 | 96103629.61 |
August | 0.818889E+09 | 0.404659E+09 | 0.414230E+09 | 0.986251E+09 | 0.113480E+09 |
September | 0.705202E+09 | 0.339322E+09 | 0.365880E+09 | 0.798092E+09 | 0.197752E+09 |
October | 0.610145E+09 | 0.348737E+09 | 0.261408E+09 | 0.551576E+09 | 0.517442E+09 |
November | 0.484892E+09 | 0.294516E+09 | 0.190376E+09 | 0.368860E+09 | 0.611431E+09 |
December | 0.404159E+09 | 0.238682E+09 | 0.165477E+09 | 0.256284E+09 | 0.809930E+09 |
Annual Sum or Average | 0.784072E+10 | 0.391117E+10 | 0.392956E+10 | 0.763330E+10 | 0.507571E+10 |
Minimum of Months | 0.404159E+09 | 0.238682E+09 | 0.165477E+09 | 0.256284E+09 | 96103629.61 |
Maximum of Months | 0.929762E+09 | 0.446919E+09 | 0.509090E+09 | 0.113187E+10 | 0.809930E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77822022.74 | 0.00 | 77822022.74 | 10186151.07 | 0.388457E+09 |
February | 88347145.08 | 0.00 | 88347145.08 | 9995294.70 | 0.366928E+09 |
March | 0.133133E+09 | 6546.90 | 0.133126E+09 | 43342656.91 | 0.300823E+09 |
April | 0.161947E+09 | 1049653.00 | 0.160897E+09 | 67228944.81 | 0.250444E+09 |
May | 0.228594E+09 | 7643271.37 | 0.220951E+09 | 0.168890E+09 | 0.133864E+09 |
June | 0.242519E+09 | 27077673.33 | 0.215441E+09 | 0.269565E+09 | 53667122.35 |
July | 0.237705E+09 | 16194650.49 | 0.221510E+09 | 0.281082E+09 | 48277719.19 |
August | 0.189256E+09 | 5095327.12 | 0.184161E+09 | 0.216428E+09 | 59119160.54 |
September | 0.153373E+09 | 119825.43 | 0.153253E+09 | 0.156581E+09 | 0.104792E+09 |
October | 0.113389E+09 | 0.00 | 0.113389E+09 | 49172901.52 | 0.279191E+09 |
November | 83300119.83 | 0.00 | 83300119.83 | 16424861.23 | 0.336277E+09 |
December | 72812238.56 | 0.00 | 72812238.56 | 8985110.69 | 0.448511E+09 |
Annual Sum or Average | 0.178220E+10 | 57186947.64 | 0.172501E+10 | 0.129788E+10 | 0.277035E+10 |
Minimum of Months | 72812238.56 | 0.00 | 72812238.56 | 8985110.69 | 48277719.19 |
Maximum of Months | 0.242519E+09 | 27077673.33 | 0.221510E+09 | 0.281082E+09 | 0.448511E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484526E+09 | 0.307101E+09 | 0.177425E+09 | 0.367289E+09 | 0.681038E+09 |
February | 0.528589E+09 | 0.327886E+09 | 0.200703E+09 | 0.407153E+09 | 0.641690E+09 |
March | 0.682572E+09 | 0.376028E+09 | 0.306544E+09 | 0.586543E+09 | 0.535636E+09 |
April | 0.623012E+09 | 0.263938E+09 | 0.359075E+09 | 0.505231E+09 | 0.457401E+09 |
May | 0.787013E+09 | 0.277923E+09 | 0.509090E+09 | 0.771377E+09 | 0.257793E+09 |
June | 0.929762E+09 | 0.446919E+09 | 0.482844E+09 | 0.113267E+10 | 0.109003E+09 |
July | 0.781962E+09 | 0.285456E+09 | 0.496506E+09 | 0.962234E+09 | 95509006.06 |
August | 0.818889E+09 | 0.404659E+09 | 0.414230E+09 | 0.990041E+09 | 0.112244E+09 |
September | 0.705202E+09 | 0.339322E+09 | 0.365880E+09 | 0.806429E+09 | 0.194706E+09 |
October | 0.610145E+09 | 0.348737E+09 | 0.261408E+09 | 0.566084E+09 | 0.509811E+09 |
November | 0.484892E+09 | 0.294516E+09 | 0.190376E+09 | 0.386922E+09 | 0.596013E+09 |
December | 0.404159E+09 | 0.238682E+09 | 0.165477E+09 | 0.272345E+09 | 0.791858E+09 |
Annual Sum or Average | 0.784072E+10 | 0.391117E+10 | 0.392956E+10 | 0.775432E+10 | 0.498270E+10 |
Minimum of Months | 0.404159E+09 | 0.238682E+09 | 0.165477E+09 | 0.272345E+09 | 95509006.06 |
Maximum of Months | 0.929762E+09 | 0.446919E+09 | 0.509090E+09 | 0.113267E+10 | 0.791858E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109789E+10 | 0.903788E+09 | 0.194102E+09 | 0.115927E+10 | 0.508281E+09 |
February | 0.938808E+09 | 0.746560E+09 | 0.192248E+09 | 0.924700E+09 | 0.494303E+09 |
March | 0.780623E+09 | 0.516012E+09 | 0.264611E+09 | 0.702416E+09 | 0.431446E+09 |
April | 0.494414E+09 | 0.204499E+09 | 0.289915E+09 | 0.348158E+09 | 0.375394E+09 |
May | 0.464235E+09 | 89210962.68 | 0.375024E+09 | 0.368482E+09 | 0.209066E+09 |
June | 0.408371E+09 | 73595110.21 | 0.334776E+09 | 0.443455E+09 | 83153099.95 |
July | 0.435917E+09 | 74178496.66 | 0.361739E+09 | 0.489916E+09 | 73548780.35 |
August | 0.554664E+09 | 0.228128E+09 | 0.326536E+09 | 0.563714E+09 | 88122343.07 |
September | 0.705303E+09 | 0.396477E+09 | 0.308825E+09 | 0.753718E+09 | 0.154624E+09 |
October | 0.860707E+09 | 0.609980E+09 | 0.250727E+09 | 0.882299E+09 | 0.406610E+09 |
November | 0.102060E+10 | 0.814105E+09 | 0.206496E+09 | 0.109109E+10 | 0.462506E+09 |
December | 0.100614E+10 | 0.814475E+09 | 0.191661E+09 | 0.104097E+10 | 0.594604E+09 |
Annual Sum or Average | 0.876767E+10 | 0.547101E+10 | 0.329666E+10 | 0.876819E+10 | 0.388166E+10 |
Minimum of Months | 0.408371E+09 | 73595110.21 | 0.191661E+09 | 0.348158E+09 | 73548780.35 |
Maximum of Months | 0.109789E+10 | 0.903788E+09 | 0.375024E+09 | 0.115927E+10 | 0.594604E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544734E+09 | 0.00 | 0.544734E+09 | 65766262.34 | 0.277867E+10 |
February | 0.618407E+09 | 0.00 | 0.618407E+09 | 71660106.32 | 0.260976E+10 |
March | 0.931894E+09 | 45826.56 | 0.931848E+09 | 0.323598E+09 | 0.213817E+10 |
April | 0.113358E+10 | 7347292.69 | 0.112624E+10 | 0.499996E+09 | 0.179319E+10 |
May | 0.160010E+10 | 53500873.27 | 0.154660E+10 | 0.128998E+10 | 0.936396E+09 |
June | 0.169757E+10 | 0.189537E+09 | 0.150803E+10 | 0.206536E+10 | 0.343577E+09 |
July | 0.166387E+10 | 0.113358E+09 | 0.155051E+10 | 0.214175E+10 | 0.306201E+09 |
August | 0.132475E+10 | 35665939.04 | 0.128908E+10 | 0.167903E+10 | 0.374956E+09 |
September | 0.107357E+10 | 838746.27 | 0.107273E+10 | 0.121526E+10 | 0.699709E+09 |
October | 0.793695E+09 | 0.00 | 0.793695E+09 | 0.382364E+09 | 0.197581E+10 |
November | 0.583079E+09 | 0.00 | 0.583079E+09 | 0.116919E+09 | 0.239766E+10 |
December | 0.509666E+09 | 0.00 | 0.509666E+09 | 57061024.27 | 0.323503E+10 |
Annual Sum or Average | 0.124749E+11 | 0.400293E+09 | 0.120746E+11 | 0.990873E+10 | 0.195891E+11 |
Minimum of Months | 0.509666E+09 | 0.00 | 0.509666E+09 | 57061024.27 | 0.306201E+09 |
Maximum of Months | 0.169757E+10 | 0.189537E+09 | 0.155051E+10 | 0.214175E+10 | 0.323503E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544734E+09 | 0.00 | 0.544734E+09 | 61772043.89 | 0.282257E+10 |
February | 0.618407E+09 | 0.00 | 0.618407E+09 | 67864023.07 | 0.265092E+10 |
March | 0.931894E+09 | 45826.56 | 0.931848E+09 | 0.313051E+09 | 0.217990E+10 |
April | 0.113358E+10 | 7347292.69 | 0.112624E+10 | 0.486666E+09 | 0.183178E+10 |
May | 0.160010E+10 | 53500873.27 | 0.154660E+10 | 0.126746E+10 | 0.962111E+09 |
June | 0.169757E+10 | 0.189537E+09 | 0.150803E+10 | 0.204235E+10 | 0.357960E+09 |
July | 0.166387E+10 | 0.113358E+09 | 0.155051E+10 | 0.211830E+10 | 0.320561E+09 |
August | 0.132475E+10 | 35665939.04 | 0.128908E+10 | 0.165777E+10 | 0.391379E+09 |
September | 0.107357E+10 | 838746.27 | 0.107273E+10 | 0.119819E+10 | 0.722001E+09 |
October | 0.793695E+09 | 0.00 | 0.793695E+09 | 0.371664E+09 | 0.201433E+10 |
November | 0.583079E+09 | 0.00 | 0.583079E+09 | 0.111893E+09 | 0.243973E+10 |
December | 0.509666E+09 | 0.00 | 0.509666E+09 | 54059187.21 | 0.328232E+10 |
Annual Sum or Average | 0.124749E+11 | 0.400293E+09 | 0.120746E+11 | 0.975104E+10 | 0.199756E+11 |
Minimum of Months | 0.509666E+09 | 0.00 | 0.509666E+09 | 54059187.21 | 0.320561E+09 |
Maximum of Months | 0.169757E+10 | 0.189537E+09 | 0.155051E+10 | 0.211830E+10 | 0.328232E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77822022.74 | 0.00 | 77822022.74 | 16567900.50 | 0.366222E+09 |
February | 88347145.08 | 0.00 | 88347145.08 | 15190524.85 | 0.351049E+09 |
March | 0.133133E+09 | 6546.90 | 0.133126E+09 | 59671783.14 | 0.289828E+09 |
April | 0.161947E+09 | 1049653.00 | 0.160897E+09 | 88529887.19 | 0.244856E+09 |
May | 0.228594E+09 | 7643271.37 | 0.220951E+09 | 0.225551E+09 | 0.130882E+09 |
June | 0.242519E+09 | 27077673.33 | 0.215441E+09 | 0.347673E+09 | 51170154.02 |
July | 0.237705E+09 | 16194650.49 | 0.221510E+09 | 0.361308E+09 | 46573422.77 |
August | 0.189256E+09 | 5095327.12 | 0.184161E+09 | 0.292167E+09 | 53430801.40 |
September | 0.153373E+09 | 119825.43 | 0.153253E+09 | 0.216827E+09 | 94472595.69 |
October | 0.113389E+09 | 0.00 | 0.113389E+09 | 72792281.68 | 0.263149E+09 |
November | 83300119.83 | 0.00 | 83300119.83 | 26112475.99 | 0.316156E+09 |
December | 72812238.56 | 0.00 | 72812238.56 | 13179293.46 | 0.432734E+09 |
Annual Sum or Average | 0.178220E+10 | 57186947.64 | 0.172501E+10 | 0.173557E+10 | 0.264052E+10 |
Minimum of Months | 72812238.56 | 0.00 | 72812238.56 | 13179293.46 | 46573422.77 |
Maximum of Months | 0.242519E+09 | 27077673.33 | 0.221510E+09 | 0.361308E+09 | 0.432734E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.907152E+09 | 0.554905E+09 | 0.352246E+09 | 0.678192E+09 | 0.127425E+10 |
February | 0.109824E+10 | 0.695062E+09 | 0.403173E+09 | 0.900198E+09 | 0.124031E+10 |
March | 0.146476E+10 | 0.855005E+09 | 0.609751E+09 | 0.136068E+10 | 0.103162E+10 |
April | 0.144706E+10 | 0.704828E+09 | 0.742229E+09 | 0.134442E+10 | 0.891096E+09 |
May | 0.175270E+10 | 0.733637E+09 | 0.101906E+10 | 0.197522E+10 | 0.484810E+09 |
June | 0.206374E+10 | 0.108295E+10 | 0.980798E+09 | 0.281219E+10 | 0.194453E+09 |
July | 0.193573E+10 | 0.919685E+09 | 0.101605E+10 | 0.269780E+10 | 0.177335E+09 |
August | 0.195753E+10 | 0.107847E+10 | 0.879058E+09 | 0.266271E+10 | 0.201536E+09 |
September | 0.157903E+10 | 0.858404E+09 | 0.720626E+09 | 0.204139E+10 | 0.345352E+09 |
October | 0.118054E+10 | 0.647431E+09 | 0.533111E+09 | 0.116836E+10 | 0.962077E+09 |
November | 0.886625E+09 | 0.499673E+09 | 0.386953E+09 | 0.700267E+09 | 0.113060E+10 |
December | 0.794718E+09 | 0.458026E+09 | 0.336692E+09 | 0.539186E+09 | 0.153207E+10 |
Annual Sum or Average | 0.170678E+11 | 0.908807E+10 | 0.797974E+10 | 0.188806E+11 | 0.946551E+10 |
Minimum of Months | 0.794718E+09 | 0.458026E+09 | 0.336692E+09 | 0.539186E+09 | 0.177335E+09 |
Maximum of Months | 0.206374E+10 | 0.108295E+10 | 0.101906E+10 | 0.281219E+10 | 0.153207E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.748598E+09 | 0.616249E+09 | 0.132349E+09 | 0.842243E+09 | 0.318353E+09 |
February | 0.640127E+09 | 0.509042E+09 | 0.131085E+09 | 0.668760E+09 | 0.316137E+09 |
March | 0.532268E+09 | 0.351843E+09 | 0.180425E+09 | 0.514179E+09 | 0.278735E+09 |
April | 0.337117E+09 | 0.139438E+09 | 0.197679E+09 | 0.264303E+09 | 0.246802E+09 |
May | 0.316539E+09 | 60828588.44 | 0.255710E+09 | 0.304025E+09 | 0.138868E+09 |
June | 0.278448E+09 | 50180903.05 | 0.228267E+09 | 0.369586E+09 | 55417666.27 |
July | 0.297231E+09 | 50578685.72 | 0.246652E+09 | 0.406191E+09 | 49115724.13 |
August | 0.378198E+09 | 0.155550E+09 | 0.222649E+09 | 0.454441E+09 | 55016121.44 |
September | 0.480911E+09 | 0.270339E+09 | 0.210573E+09 | 0.578902E+09 | 95203271.96 |
October | 0.586874E+09 | 0.415915E+09 | 0.170959E+09 | 0.645562E+09 | 0.256359E+09 |
November | 0.695897E+09 | 0.555098E+09 | 0.140799E+09 | 0.791257E+09 | 0.289609E+09 |
December | 0.686035E+09 | 0.555350E+09 | 0.130684E+09 | 0.753672E+09 | 0.377981E+09 |
Annual Sum or Average | 0.597824E+10 | 0.373041E+10 | 0.224783E+10 | 0.659312E+10 | 0.247760E+10 |
Minimum of Months | 0.278448E+09 | 50180903.05 | 0.130684E+09 | 0.264303E+09 | 49115724.13 |
Maximum of Months | 0.748598E+09 | 0.616249E+09 | 0.255710E+09 | 0.842243E+09 | 0.377981E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98556681.50 | 0.00 | 98556681.50 | 10586850.67 | 0.509227E+09 |
February | 0.111886E+09 | 0.00 | 0.111886E+09 | 11643025.67 | 0.475902E+09 |
March | 0.168604E+09 | 8291.24 | 0.168596E+09 | 56814918.84 | 0.383992E+09 |
April | 0.205095E+09 | 1329319.29 | 0.203766E+09 | 90584342.96 | 0.318990E+09 |
May | 0.289500E+09 | 9679720.93 | 0.279820E+09 | 0.234113E+09 | 0.164467E+09 |
June | 0.307135E+09 | 34292164.77 | 0.272843E+09 | 0.371086E+09 | 61356285.13 |
July | 0.301038E+09 | 20509503.02 | 0.280529E+09 | 0.384253E+09 | 55073779.75 |
August | 0.239681E+09 | 6452910.30 | 0.233229E+09 | 0.299626E+09 | 68230112.72 |
September | 0.194237E+09 | 151751.35 | 0.194086E+09 | 0.216288E+09 | 0.125964E+09 |
October | 0.143600E+09 | 0.00 | 0.143600E+09 | 66268374.99 | 0.355509E+09 |
November | 0.105494E+09 | 0.00 | 0.105494E+09 | 19128041.64 | 0.437315E+09 |
December | 92212105.94 | 0.00 | 92212105.94 | 9283650.13 | 0.587682E+09 |
Annual Sum or Average | 0.225704E+10 | 72423660.89 | 0.218462E+10 | 0.176967E+10 | 0.354371E+10 |
Minimum of Months | 92212105.94 | 0.00 | 92212105.94 | 9283650.13 | 55073779.75 |
Maximum of Months | 0.307135E+09 | 34292164.77 | 0.280529E+09 | 0.384253E+09 | 0.587682E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88179036.37 | 0.00 | 88179036.37 | 9472095.41 | 0.455595E+09 |
February | 0.100105E+09 | 0.00 | 0.100105E+09 | 10417059.18 | 0.425788E+09 |
March | 0.150851E+09 | 7418.20 | 0.150843E+09 | 50832523.16 | 0.343559E+09 |
April | 0.183499E+09 | 1189347.01 | 0.182310E+09 | 81046154.86 | 0.285402E+09 |
May | 0.259017E+09 | 8660482.99 | 0.250356E+09 | 0.209462E+09 | 0.147149E+09 |
June | 0.274795E+09 | 30681329.75 | 0.244114E+09 | 0.332012E+09 | 54895700.78 |
July | 0.269340E+09 | 18349930.06 | 0.250990E+09 | 0.343793E+09 | 49274719.42 |
August | 0.214444E+09 | 5773443.30 | 0.208670E+09 | 0.268076E+09 | 61045740.37 |
September | 0.173785E+09 | 135772.51 | 0.173649E+09 | 0.193513E+09 | 0.112701E+09 |
October | 0.128480E+09 | 0.00 | 0.128480E+09 | 59290566.20 | 0.318075E+09 |
November | 94386190.92 | 0.00 | 94386190.92 | 17113931.33 | 0.391268E+09 |
December | 82502520.57 | 0.00 | 82502520.57 | 8306116.94 | 0.525786E+09 |
Annual Sum or Average | 0.201938E+10 | 64797723.81 | 0.195459E+10 | 0.158333E+10 | 0.317054E+10 |
Minimum of Months | 82502520.57 | 0.00 | 82502520.57 | 8306116.94 | 49274719.42 |
Maximum of Months | 0.274795E+09 | 30681329.75 | 0.250990E+09 | 0.343793E+09 | 0.525786E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279474E+10 | 0.230064E+10 | 0.494097E+09 | 0.303264E+10 | 0.125315E+10 |
February | 0.238979E+10 | 0.190041E+10 | 0.489378E+09 | 0.242043E+10 | 0.122778E+10 |
March | 0.198712E+10 | 0.131353E+10 | 0.673582E+09 | 0.184167E+10 | 0.107708E+10 |
April | 0.125856E+10 | 0.520564E+09 | 0.737994E+09 | 0.921199E+09 | 0.941759E+09 |
May | 0.118173E+10 | 0.227091E+09 | 0.954642E+09 | 0.989616E+09 | 0.515292E+09 |
June | 0.103953E+10 | 0.187340E+09 | 0.852190E+09 | 0.118549E+10 | 0.198209E+09 |
July | 0.110965E+10 | 0.188825E+09 | 0.920826E+09 | 0.130861E+10 | 0.172756E+09 |
August | 0.141193E+10 | 0.580713E+09 | 0.831214E+09 | 0.149862E+10 | 0.206929E+09 |
September | 0.179539E+10 | 0.100925E+10 | 0.786131E+09 | 0.198604E+10 | 0.367588E+09 |
October | 0.219098E+10 | 0.155274E+10 | 0.638240E+09 | 0.230591E+10 | 0.100769E+10 |
November | 0.259799E+10 | 0.207235E+10 | 0.525646E+09 | 0.284988E+10 | 0.114077E+10 |
December | 0.256117E+10 | 0.207329E+10 | 0.487883E+09 | 0.272474E+10 | 0.146703E+10 |
Annual Sum or Average | 0.223186E+11 | 0.139267E+11 | 0.839182E+10 | 0.230648E+11 | 0.957603E+10 |
Minimum of Months | 0.103953E+10 | 0.187340E+09 | 0.487883E+09 | 0.921199E+09 | 0.172756E+09 |
Maximum of Months | 0.279474E+10 | 0.230064E+10 | 0.954642E+09 | 0.303264E+10 | 0.146703E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1516.15 | 610.02 | 1415.33 | 1165.11 | 250.22 | 0.00 | 0.00 |
February | 1345.19 | 648.44 | 1339.92 | 1065.53 | 274.39 | 0.00 | 0.00 |
March | 923.21 | 511.45 | 1006.33 | 665.21 | 341.12 | 0.00 | 0.00 |
April | 479.45 | 455.91 | 658.61 | 272.42 | 386.20 | 0.00 | 0.00 |
May | 493.10 | 245.90 | 598.46 | 115.01 | 483.46 | 0.00 | 0.00 |
June | 596.63 | 105.66 | 544.00 | 98.04 | 445.96 | 0.00 | 0.00 |
July | 639.34 | 89.68 | 561.96 | 95.63 | 466.33 | 0.00 | 0.00 |
August | 734.61 | 106.89 | 715.04 | 294.09 | 420.95 | 0.00 | 0.00 |
September | 1013.58 | 192.56 | 939.54 | 528.15 | 411.39 | 0.00 | 0.00 |
October | 1148.81 | 484.74 | 1109.57 | 786.35 | 323.22 | 0.00 | 0.00 |
November | 1472.43 | 569.26 | 1359.55 | 1084.48 | 275.07 | 0.00 | 0.00 |
December | 1373.91 | 699.52 | 1297.05 | 1049.97 | 247.08 | 0.00 | 0.00 |
Annual Sum or Average | 975.97 | 391.92 | 959.96 | 599.01 | 360.95 | 0.00 | 0.00 |
Minimum of Months | 479.45 | 89.68 | 544.00 | 95.63 | 247.08 | 0.00 | 0.00 |
Maximum of Months | 1516.15 | 699.52 | 1415.33 | 1165.11 | 483.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4264.61 | 1716.51 | 3985.48 | 3280.87 | 704.62 | 0.00 | 0.00 |
February | 3782.15 | 1825.96 | 3773.14 | 3000.48 | 772.66 | 0.00 | 0.00 |
March | 2594.48 | 1444.08 | 2833.76 | 1873.19 | 960.57 | 0.00 | 0.00 |
April | 1339.61 | 1288.36 | 1854.61 | 767.10 | 1087.51 | 0.00 | 0.00 |
May | 1375.52 | 688.59 | 1685.23 | 323.85 | 1361.38 | 0.00 | 0.00 |
June | 1670.51 | 289.58 | 1531.85 | 276.07 | 1255.79 | 0.00 | 0.00 |
July | 1790.65 | 246.10 | 1582.44 | 269.28 | 1313.16 | 0.00 | 0.00 |
August | 2059.20 | 293.93 | 2013.50 | 828.14 | 1185.37 | 0.00 | 0.00 |
September | 2850.75 | 536.24 | 2645.68 | 1487.24 | 1158.44 | 0.00 | 0.00 |
October | 3234.80 | 1367.36 | 3124.48 | 2214.30 | 910.17 | 0.00 | 0.00 |
November | 4142.45 | 1603.38 | 3828.41 | 3053.82 | 774.59 | 0.00 | 0.00 |
December | 3861.87 | 1975.84 | 3652.40 | 2956.65 | 695.75 | 0.00 | 0.00 |
Annual Sum or Average | 2741.41 | 1102.35 | 2703.18 | 1686.78 | 1016.40 | 0.00 | 0.00 |
Minimum of Months | 1339.61 | 246.10 | 1531.85 | 269.28 | 695.75 | 0.00 | 0.00 |
Maximum of Months | 4264.61 | 1975.84 | 3985.48 | 3280.87 | 1361.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5654.57 | 2265.66 | 5177.37 | 4262.04 | 915.34 | 0.00 | 0.00 |
February | 5020.23 | 2419.61 | 4901.52 | 3897.79 | 1003.73 | 0.00 | 0.00 |
March | 3441.63 | 1925.86 | 3681.22 | 2433.38 | 1247.84 | 0.00 | 0.00 |
April | 1779.86 | 1729.79 | 2409.25 | 996.51 | 1412.74 | 0.00 | 0.00 |
May | 1839.51 | 927.52 | 2189.21 | 420.70 | 1768.52 | 0.00 | 0.00 |
June | 2240.74 | 384.78 | 1989.97 | 358.62 | 1631.34 | 0.00 | 0.00 |
July | 2398.43 | 325.35 | 2055.68 | 349.81 | 1705.87 | 0.00 | 0.00 |
August | 2752.24 | 386.25 | 2615.65 | 1075.79 | 1539.86 | 0.00 | 0.00 |
September | 3787.04 | 706.46 | 3436.89 | 1932.01 | 1504.89 | 0.00 | 0.00 |
October | 4291.38 | 1815.20 | 4058.87 | 2876.51 | 1182.37 | 0.00 | 0.00 |
November | 5493.99 | 2119.25 | 4973.32 | 3967.08 | 1006.24 | 0.00 | 0.00 |
December | 5112.32 | 2616.91 | 4744.68 | 3840.85 | 903.82 | 0.00 | 0.00 |
Annual Sum or Average | 3643.31 | 1463.29 | 3511.59 | 2191.22 | 1320.36 | 0.00 | 0.00 |
Minimum of Months | 1779.86 | 325.35 | 1989.97 | 349.81 | 903.82 | 0.00 | 0.00 |
Maximum of Months | 5654.57 | 2616.91 | 5177.37 | 4262.04 | 1768.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.18 | 366.98 | 460.02 | 344.46 | 115.56 | 0.00 | 0.00 |
February | 411.43 | 389.83 | 482.70 | 345.67 | 137.04 | 0.00 | 0.00 |
March | 391.15 | 304.67 | 453.20 | 271.53 | 181.66 | 0.00 | 0.00 |
April | 284.25 | 272.22 | 370.12 | 155.50 | 214.62 | 0.00 | 0.00 |
May | 383.23 | 147.84 | 411.68 | 126.37 | 285.31 | 0.00 | 0.00 |
June | 555.30 | 64.07 | 465.75 | 191.62 | 274.12 | 0.00 | 0.00 |
July | 486.04 | 54.22 | 402.59 | 125.36 | 277.24 | 0.00 | 0.00 |
August | 514.58 | 64.06 | 446.57 | 208.99 | 237.59 | 0.00 | 0.00 |
September | 509.17 | 115.75 | 457.23 | 235.02 | 222.21 | 0.00 | 0.00 |
October | 431.62 | 291.50 | 446.55 | 285.25 | 161.30 | 0.00 | 0.00 |
November | 422.67 | 341.78 | 455.18 | 327.51 | 127.66 | 0.00 | 0.00 |
December | 343.95 | 425.99 | 406.70 | 296.21 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 428.53 | 235.73 | 437.84 | 242.11 | 195.72 | 0.00 | 0.00 |
Minimum of Months | 284.25 | 54.22 | 370.12 | 125.36 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 555.30 | 425.99 | 482.70 | 345.67 | 285.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 132.07 | 393.56 | 209.78 | 114.56 | 95.22 | 0.00 | 0.00 |
February | 163.40 | 407.52 | 254.81 | 135.42 | 119.38 | 0.00 | 0.00 |
March | 232.26 | 307.94 | 304.30 | 140.28 | 164.02 | 0.00 | 0.00 |
April | 220.78 | 270.63 | 302.59 | 102.15 | 200.44 | 0.00 | 0.00 |
May | 355.31 | 144.43 | 378.87 | 106.53 | 272.34 | 0.00 | 0.00 |
June | 545.12 | 60.43 | 451.90 | 182.72 | 269.18 | 0.00 | 0.00 |
July | 468.48 | 51.86 | 380.39 | 112.53 | 267.86 | 0.00 | 0.00 |
August | 455.63 | 62.68 | 376.09 | 152.86 | 223.23 | 0.00 | 0.00 |
September | 374.98 | 114.49 | 330.97 | 130.85 | 200.12 | 0.00 | 0.00 |
October | 229.40 | 292.46 | 269.92 | 130.10 | 139.82 | 0.00 | 0.00 |
November | 149.78 | 354.72 | 219.03 | 113.53 | 105.50 | 0.00 | 0.00 |
December | 96.84 | 456.86 | 177.93 | 89.04 | 88.89 | 0.00 | 0.00 |
Annual Sum or Average | 285.93 | 242.25 | 304.89 | 125.73 | 179.16 | 0.00 | 0.00 |
Minimum of Months | 96.84 | 51.86 | 177.93 | 89.04 | 88.89 | 0.00 | 0.00 |
Maximum of Months | 545.12 | 456.86 | 451.90 | 182.72 | 272.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.65 | 109.90 | 223.37 | 183.88 | 39.49 | 0.00 | 0.00 |
February | 209.53 | 114.82 | 211.47 | 168.16 | 43.30 | 0.00 | 0.00 |
March | 143.30 | 92.26 | 158.82 | 104.98 | 53.84 | 0.00 | 0.00 |
April | 72.53 | 85.53 | 103.94 | 42.99 | 60.95 | 0.00 | 0.00 |
May | 72.20 | 49.90 | 94.45 | 18.15 | 76.30 | 0.00 | 0.00 |
June | 89.87 | 23.54 | 85.85 | 15.47 | 70.38 | 0.00 | 0.00 |
July | 96.33 | 20.89 | 88.69 | 15.09 | 73.60 | 0.00 | 0.00 |
August | 112.03 | 24.30 | 112.85 | 46.41 | 66.43 | 0.00 | 0.00 |
September | 156.78 | 39.78 | 148.28 | 83.35 | 64.93 | 0.00 | 0.00 |
October | 179.39 | 89.87 | 175.11 | 124.10 | 51.01 | 0.00 | 0.00 |
November | 230.55 | 103.34 | 214.56 | 171.15 | 43.41 | 0.00 | 0.00 |
December | 213.63 | 124.82 | 204.70 | 165.71 | 38.99 | 0.00 | 0.00 |
Annual Sum or Average | 150.73 | 73.02 | 151.50 | 94.54 | 56.96 | 0.00 | 0.00 |
Minimum of Months | 72.20 | 20.89 | 85.85 | 15.09 | 38.99 | 0.00 | 0.00 |
Maximum of Months | 236.65 | 124.82 | 223.37 | 183.88 | 76.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.74 | 120.58 | 23.23 | 0.00 | 23.23 | 0.00 | 0.00 |
February | 3.34 | 124.41 | 29.20 | 0.00 | 29.20 | 0.00 | 0.00 |
March | 13.58 | 92.15 | 39.74 | 0.00 | 39.74 | 0.00 | 0.00 |
April | 21.61 | 79.80 | 49.95 | 0.32 | 49.63 | 0.00 | 0.00 |
May | 53.43 | 40.11 | 68.23 | 2.28 | 65.95 | 0.00 | 0.00 |
June | 88.12 | 15.80 | 74.80 | 8.35 | 66.45 | 0.00 | 0.00 |
July | 88.19 | 13.82 | 70.95 | 4.83 | 66.12 | 0.00 | 0.00 |
August | 69.03 | 16.92 | 56.49 | 1.52 | 54.97 | 0.00 | 0.00 |
September | 51.59 | 31.92 | 47.30 | 0.04 | 47.27 | 0.00 | 0.00 |
October | 15.86 | 85.22 | 33.84 | 0.00 | 33.84 | 0.00 | 0.00 |
November | 5.08 | 107.27 | 25.69 | 0.00 | 25.69 | 0.00 | 0.00 |
December | 2.41 | 139.39 | 21.73 | 0.00 | 21.73 | 0.00 | 0.00 |
Annual Sum or Average | 34.76 | 72.00 | 45.18 | 1.45 | 43.73 | 0.00 | 0.00 |
Minimum of Months | 2.41 | 13.82 | 21.73 | 0.00 | 21.73 | 0.00 | 0.00 |
Maximum of Months | 88.19 | 139.39 | 74.80 | 8.35 | 66.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 390.95 | 363.30 | 448.48 | 333.40 | 115.08 | 0.00 | 0.00 |
February | 420.03 | 388.29 | 491.20 | 353.79 | 137.41 | 0.00 | 0.00 |
March | 408.02 | 301.01 | 471.80 | 290.75 | 181.05 | 0.00 | 0.00 |
April | 324.73 | 266.41 | 408.88 | 189.61 | 219.27 | 0.00 | 0.00 |
May | 415.44 | 138.80 | 445.03 | 159.54 | 285.49 | 0.00 | 0.00 |
June | 598.21 | 58.09 | 505.14 | 228.09 | 277.05 | 0.00 | 0.00 |
July | 568.33 | 50.81 | 471.97 | 190.43 | 281.55 | 0.00 | 0.00 |
August | 583.07 | 61.58 | 506.24 | 259.20 | 247.04 | 0.00 | 0.00 |
September | 541.31 | 109.89 | 489.75 | 269.67 | 220.08 | 0.00 | 0.00 |
October | 417.16 | 287.55 | 439.15 | 275.93 | 163.22 | 0.00 | 0.00 |
November | 398.00 | 339.91 | 439.16 | 310.30 | 128.86 | 0.00 | 0.00 |
December | 339.68 | 426.39 | 404.17 | 292.61 | 111.56 | 0.00 | 0.00 |
Annual Sum or Average | 450.49 | 231.82 | 459.82 | 262.18 | 197.64 | 0.00 | 0.00 |
Minimum of Months | 324.73 | 50.81 | 404.17 | 159.54 | 111.56 | 0.00 | 0.00 |
Maximum of Months | 598.21 | 426.39 | 506.24 | 353.79 | 285.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.17 | 383.33 | 198.25 | 103.51 | 94.74 | 0.00 | 0.00 |
February | 168.04 | 402.02 | 263.30 | 143.55 | 119.75 | 0.00 | 0.00 |
March | 244.40 | 300.29 | 322.90 | 159.49 | 163.41 | 0.00 | 0.00 |
April | 260.36 | 264.50 | 341.36 | 136.26 | 205.09 | 0.00 | 0.00 |
May | 388.92 | 136.93 | 412.22 | 139.70 | 272.52 | 0.00 | 0.00 |
June | 591.17 | 57.54 | 491.29 | 219.18 | 272.11 | 0.00 | 0.00 |
July | 552.65 | 50.36 | 449.77 | 177.60 | 272.17 | 0.00 | 0.00 |
August | 524.25 | 60.67 | 435.76 | 203.08 | 232.68 | 0.00 | 0.00 |
September | 405.84 | 108.23 | 363.49 | 165.51 | 197.98 | 0.00 | 0.00 |
October | 211.55 | 285.71 | 262.52 | 120.77 | 141.75 | 0.00 | 0.00 |
November | 121.36 | 348.46 | 203.01 | 96.32 | 106.70 | 0.00 | 0.00 |
December | 85.80 | 449.75 | 175.41 | 85.44 | 89.97 | 0.00 | 0.00 |
Annual Sum or Average | 305.90 | 236.43 | 326.87 | 145.79 | 181.08 | 0.00 | 0.00 |
Minimum of Months | 85.80 | 50.36 | 175.41 | 85.44 | 89.97 | 0.00 | 0.00 |
Maximum of Months | 591.17 | 449.75 | 491.29 | 219.18 | 272.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 500.66 | 440.41 | 534.30 | 398.41 | 135.89 | 0.00 | 0.00 |
February | 450.85 | 475.20 | 521.44 | 364.36 | 157.07 | 0.00 | 0.00 |
March | 349.23 | 375.21 | 430.20 | 227.47 | 202.73 | 0.00 | 0.00 |
April | 216.88 | 332.78 | 333.42 | 93.85 | 239.57 | 0.00 | 0.00 |
May | 297.39 | 169.48 | 352.46 | 44.27 | 308.19 | 0.00 | 0.00 |
June | 414.22 | 63.55 | 348.06 | 51.62 | 296.45 | 0.00 | 0.00 |
July | 429.72 | 54.28 | 345.86 | 43.17 | 302.69 | 0.00 | 0.00 |
August | 420.55 | 67.64 | 366.88 | 103.86 | 263.02 | 0.00 | 0.00 |
September | 476.29 | 129.36 | 423.76 | 180.68 | 243.07 | 0.00 | 0.00 |
October | 435.84 | 349.47 | 452.74 | 268.89 | 183.85 | 0.00 | 0.00 |
November | 505.54 | 411.47 | 520.56 | 370.84 | 149.72 | 0.00 | 0.00 |
December | 445.36 | 515.56 | 490.61 | 359.04 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 411.65 | 280.97 | 426.13 | 207.97 | 218.16 | 0.00 | 0.00 |
Minimum of Months | 216.88 | 54.28 | 333.42 | 43.17 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 505.54 | 515.56 | 534.30 | 398.41 | 308.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 408.43 | 365.67 | 460.40 | 344.74 | 115.66 | 0.00 | 0.00 |
February | 409.40 | 390.30 | 483.10 | 345.95 | 137.15 | 0.00 | 0.00 |
March | 388.89 | 304.64 | 453.57 | 271.76 | 181.81 | 0.00 | 0.00 |
April | 281.84 | 272.26 | 370.42 | 155.62 | 214.80 | 0.00 | 0.00 |
May | 378.51 | 148.93 | 412.02 | 126.48 | 285.54 | 0.00 | 0.00 |
June | 550.00 | 64.88 | 466.13 | 191.78 | 274.35 | 0.00 | 0.00 |
July | 481.12 | 55.07 | 402.92 | 125.46 | 277.46 | 0.00 | 0.00 |
August | 509.61 | 65.02 | 446.94 | 209.16 | 237.78 | 0.00 | 0.00 |
September | 505.59 | 116.42 | 457.61 | 235.21 | 222.40 | 0.00 | 0.00 |
October | 429.33 | 291.59 | 446.92 | 285.49 | 161.43 | 0.00 | 0.00 |
November | 420.92 | 341.45 | 455.55 | 327.78 | 127.77 | 0.00 | 0.00 |
December | 343.16 | 425.87 | 407.03 | 296.46 | 110.57 | 0.00 | 0.00 |
Annual Sum or Average | 425.55 | 236.00 | 438.20 | 242.31 | 195.88 | 0.00 | 0.00 |
Minimum of Months | 281.84 | 55.07 | 370.42 | 125.46 | 110.57 | 0.00 | 0.00 |
Maximum of Months | 550.00 | 425.87 | 483.10 | 345.95 | 285.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 132.35 | 390.72 | 209.96 | 114.66 | 95.30 | 0.00 | 0.00 |
February | 162.53 | 407.02 | 255.02 | 135.53 | 119.48 | 0.00 | 0.00 |
March | 230.37 | 307.50 | 304.55 | 140.40 | 164.15 | 0.00 | 0.00 |
April | 218.20 | 270.43 | 302.84 | 102.23 | 200.61 | 0.00 | 0.00 |
May | 350.17 | 145.34 | 379.18 | 106.62 | 272.57 | 0.00 | 0.00 |
June | 539.51 | 61.28 | 452.27 | 182.87 | 269.40 | 0.00 | 0.00 |
July | 463.27 | 52.75 | 380.70 | 112.62 | 268.08 | 0.00 | 0.00 |
August | 450.13 | 63.67 | 376.40 | 152.98 | 223.41 | 0.00 | 0.00 |
September | 371.06 | 115.08 | 331.24 | 130.96 | 200.28 | 0.00 | 0.00 |
October | 227.28 | 292.15 | 270.14 | 130.20 | 139.93 | 0.00 | 0.00 |
November | 149.13 | 353.20 | 219.21 | 113.62 | 105.58 | 0.00 | 0.00 |
December | 97.37 | 455.43 | 178.08 | 89.11 | 88.97 | 0.00 | 0.00 |
Annual Sum or Average | 283.20 | 242.00 | 305.14 | 125.84 | 179.31 | 0.00 | 0.00 |
Minimum of Months | 97.37 | 52.75 | 178.08 | 89.11 | 88.97 | 0.00 | 0.00 |
Maximum of Months | 539.51 | 455.43 | 452.27 | 182.87 | 272.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.82 | 189.77 | 409.91 | 337.44 | 72.47 | 0.00 | 0.00 |
February | 382.23 | 204.32 | 388.07 | 308.60 | 79.47 | 0.00 | 0.00 |
March | 262.25 | 161.08 | 291.45 | 192.66 | 98.79 | 0.00 | 0.00 |
April | 134.32 | 144.83 | 190.75 | 78.90 | 111.85 | 0.00 | 0.00 |
May | 137.58 | 78.06 | 173.33 | 33.31 | 140.02 | 0.00 | 0.00 |
June | 171.09 | 32.08 | 157.55 | 28.39 | 129.16 | 0.00 | 0.00 |
July | 182.91 | 27.46 | 162.75 | 27.70 | 135.06 | 0.00 | 0.00 |
August | 210.47 | 32.90 | 207.09 | 85.17 | 121.91 | 0.00 | 0.00 |
September | 290.79 | 59.65 | 272.11 | 152.96 | 119.15 | 0.00 | 0.00 |
October | 329.41 | 151.81 | 321.35 | 227.74 | 93.61 | 0.00 | 0.00 |
November | 420.95 | 178.44 | 393.75 | 314.08 | 79.67 | 0.00 | 0.00 |
December | 388.65 | 222.00 | 375.65 | 304.09 | 71.56 | 0.00 | 0.00 |
Annual Sum or Average | 278.04 | 123.09 | 278.02 | 173.48 | 104.54 | 0.00 | 0.00 |
Minimum of Months | 134.32 | 27.46 | 157.55 | 27.70 | 71.56 | 0.00 | 0.00 |
Maximum of Months | 432.82 | 222.00 | 409.91 | 337.44 | 140.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.55 | 1037.44 | 203.38 | 0.00 | 203.38 | 0.00 | 0.00 |
February | 29.62 | 1078.77 | 255.62 | 0.00 | 255.62 | 0.00 | 0.00 |
March | 120.82 | 798.30 | 347.93 | 0.02 | 347.91 | 0.00 | 0.00 |
April | 192.90 | 691.82 | 437.34 | 2.83 | 434.50 | 0.00 | 0.00 |
May | 481.62 | 349.61 | 597.41 | 19.97 | 577.43 | 0.00 | 0.00 |
June | 796.82 | 132.55 | 654.93 | 73.12 | 581.80 | 0.00 | 0.00 |
July | 799.64 | 114.32 | 621.22 | 42.32 | 578.90 | 0.00 | 0.00 |
August | 626.88 | 139.99 | 494.60 | 13.32 | 481.29 | 0.00 | 0.00 |
September | 468.85 | 269.95 | 414.19 | 0.32 | 413.86 | 0.00 | 0.00 |
October | 142.76 | 737.68 | 296.33 | 0.00 | 296.33 | 0.00 | 0.00 |
November | 45.11 | 925.02 | 224.95 | 0.00 | 224.95 | 0.00 | 0.00 |
December | 21.30 | 1207.82 | 190.29 | 0.00 | 190.29 | 0.00 | 0.00 |
Annual Sum or Average | 314.20 | 621.17 | 395.58 | 12.69 | 382.88 | 0.00 | 0.00 |
Minimum of Months | 21.30 | 114.32 | 190.29 | 0.00 | 190.29 | 0.00 | 0.00 |
Maximum of Months | 799.64 | 1207.82 | 654.93 | 73.12 | 581.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.06 | 1053.83 | 203.38 | 0.00 | 203.38 | 0.00 | 0.00 |
February | 28.05 | 1095.78 | 255.62 | 0.00 | 255.62 | 0.00 | 0.00 |
March | 116.88 | 813.88 | 347.93 | 0.02 | 347.91 | 0.00 | 0.00 |
April | 187.76 | 706.71 | 437.34 | 2.83 | 434.50 | 0.00 | 0.00 |
May | 473.21 | 359.21 | 597.41 | 19.97 | 577.43 | 0.00 | 0.00 |
June | 787.95 | 138.10 | 654.93 | 73.12 | 581.80 | 0.00 | 0.00 |
July | 790.88 | 119.68 | 621.22 | 42.32 | 578.90 | 0.00 | 0.00 |
August | 618.94 | 146.12 | 494.60 | 13.32 | 481.29 | 0.00 | 0.00 |
September | 462.26 | 278.55 | 414.19 | 0.32 | 413.86 | 0.00 | 0.00 |
October | 138.76 | 752.06 | 296.33 | 0.00 | 296.33 | 0.00 | 0.00 |
November | 43.17 | 941.25 | 224.95 | 0.00 | 224.95 | 0.00 | 0.00 |
December | 20.18 | 1225.48 | 190.29 | 0.00 | 190.29 | 0.00 | 0.00 |
Annual Sum or Average | 309.20 | 633.42 | 395.58 | 12.69 | 382.88 | 0.00 | 0.00 |
Minimum of Months | 20.18 | 119.68 | 190.29 | 0.00 | 190.29 | 0.00 | 0.00 |
Maximum of Months | 790.88 | 1225.48 | 654.93 | 73.12 | 581.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 534.77 | 692.26 | 647.24 | 437.26 | 209.98 | 0.00 | 0.00 |
February | 622.24 | 755.90 | 755.09 | 497.73 | 257.36 | 0.00 | 0.00 |
March | 712.58 | 587.75 | 795.31 | 450.59 | 344.72 | 0.00 | 0.00 |
April | 648.02 | 526.69 | 750.82 | 326.12 | 424.69 | 0.00 | 0.00 |
May | 930.70 | 277.24 | 857.91 | 299.47 | 558.44 | 0.00 | 0.00 |
June | 1360.23 | 114.71 | 997.19 | 447.61 | 549.58 | 0.00 | 0.00 |
July | 1293.08 | 101.22 | 922.44 | 368.30 | 554.14 | 0.00 | 0.00 |
August | 1272.14 | 114.99 | 942.72 | 462.63 | 480.09 | 0.00 | 0.00 |
September | 1092.34 | 204.19 | 853.90 | 435.52 | 418.38 | 0.00 | 0.00 |
October | 699.91 | 548.65 | 702.21 | 397.01 | 305.20 | 0.00 | 0.00 |
November | 564.63 | 649.02 | 642.68 | 406.93 | 235.75 | 0.00 | 0.00 |
December | 445.39 | 832.47 | 580.03 | 378.35 | 201.68 | 0.00 | 0.00 |
Annual Sum or Average | 849.11 | 448.75 | 787.30 | 408.28 | 379.01 | 0.00 | 0.00 |
Minimum of Months | 445.39 | 101.22 | 580.03 | 299.47 | 201.68 | 0.00 | 0.00 |
Maximum of Months | 1360.23 | 832.47 | 997.19 | 497.73 | 558.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1088.53 | 776.88 | 1113.15 | 858.96 | 254.19 | 0.00 | 0.00 |
February | 971.61 | 842.22 | 1075.47 | 785.55 | 289.92 | 0.00 | 0.00 |
March | 721.43 | 667.41 | 861.18 | 490.42 | 370.75 | 0.00 | 0.00 |
April | 421.08 | 595.97 | 635.48 | 201.81 | 433.67 | 0.00 | 0.00 |
May | 534.31 | 307.95 | 646.00 | 91.63 | 554.37 | 0.00 | 0.00 |
June | 725.27 | 117.97 | 625.56 | 97.34 | 528.22 | 0.00 | 0.00 |
July | 758.35 | 101.41 | 627.25 | 85.01 | 542.24 | 0.00 | 0.00 |
August | 771.16 | 125.21 | 696.70 | 221.38 | 475.33 | 0.00 | 0.00 |
September | 924.04 | 233.62 | 834.65 | 389.48 | 445.16 | 0.00 | 0.00 |
October | 902.96 | 622.87 | 919.60 | 579.72 | 339.87 | 0.00 | 0.00 |
November | 1083.19 | 729.50 | 1079.43 | 799.52 | 279.91 | 0.00 | 0.00 |
December | 970.76 | 910.34 | 1021.46 | 774.08 | 247.39 | 0.00 | 0.00 |
Annual Sum or Average | 821.88 | 500.73 | 843.32 | 445.97 | 397.36 | 0.00 | 0.00 |
Minimum of Months | 421.08 | 101.41 | 625.56 | 85.01 | 247.39 | 0.00 | 0.00 |
Maximum of Months | 1088.53 | 910.34 | 1113.15 | 858.96 | 554.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.406085E+10 | 0.163387E+10 | 0.379083E+10 | 0.312063E+10 | 0.670201E+09 | 0.00 | 0.00 |
February | 0.325428E+10 | 0.156870E+10 | 0.324154E+10 | 0.257774E+10 | 0.663800E+09 | 0.00 | 0.00 |
March | 0.247274E+10 | 0.136986E+10 | 0.269536E+10 | 0.178170E+10 | 0.913657E+09 | 0.00 | 0.00 |
April | 0.124273E+10 | 0.118173E+10 | 0.170713E+10 | 0.706102E+09 | 0.100103E+10 | 0.00 | 0.00 |
May | 0.132071E+10 | 0.658614E+09 | 0.160292E+10 | 0.308030E+09 | 0.129489E+10 | 0.00 | 0.00 |
June | 0.154647E+10 | 0.273877E+09 | 0.141004E+10 | 0.254111E+09 | 0.115592E+10 | 0.00 | 0.00 |
July | 0.171240E+10 | 0.240211E+09 | 0.150515E+10 | 0.256126E+09 | 0.124902E+10 | 0.00 | 0.00 |
August | 0.196758E+10 | 0.286284E+09 | 0.191516E+10 | 0.787688E+09 | 0.112747E+10 | 0.00 | 0.00 |
September | 0.262721E+10 | 0.499107E+09 | 0.243529E+10 | 0.136897E+10 | 0.106632E+10 | 0.00 | 0.00 |
October | 0.307697E+10 | 0.129832E+10 | 0.297187E+10 | 0.210615E+10 | 0.865719E+09 | 0.00 | 0.00 |
November | 0.381653E+10 | 0.147553E+10 | 0.352396E+10 | 0.281096E+10 | 0.712994E+09 | 0.00 | 0.00 |
December | 0.367988E+10 | 0.187360E+10 | 0.347401E+10 | 0.281224E+10 | 0.661772E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.307783E+11 | 0.123597E+11 | 0.302733E+11 | 0.188905E+11 | 0.113828E+11 | 0.00 | 0.00 |
Minimum of Months | 0.124273E+10 | 0.240211E+09 | 0.141004E+10 | 0.254111E+09 | 0.661772E+09 | 0.00 | 0.00 |
Maximum of Months | 0.406085E+10 | 0.187360E+10 | 0.379083E+10 | 0.312063E+10 | 0.129489E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114223E+11 | 0.459749E+10 | 0.106747E+11 | 0.878748E+10 | 0.188724E+10 | 0.00 | 0.00 |
February | 0.914979E+10 | 0.441735E+10 | 0.912797E+10 | 0.725875E+10 | 0.186922E+10 | 0.00 | 0.00 |
March | 0.694906E+10 | 0.386784E+10 | 0.758995E+10 | 0.501715E+10 | 0.257280E+10 | 0.00 | 0.00 |
April | 0.347226E+10 | 0.333942E+10 | 0.480716E+10 | 0.198834E+10 | 0.281882E+10 | 0.00 | 0.00 |
May | 0.368419E+10 | 0.184433E+10 | 0.451372E+10 | 0.867393E+09 | 0.364633E+10 | 0.00 | 0.00 |
June | 0.432997E+10 | 0.750592E+09 | 0.397057E+10 | 0.715561E+09 | 0.325501E+10 | 0.00 | 0.00 |
July | 0.479607E+10 | 0.659150E+09 | 0.423840E+10 | 0.721233E+09 | 0.351717E+10 | 0.00 | 0.00 |
August | 0.551537E+10 | 0.787253E+09 | 0.539296E+10 | 0.221808E+10 | 0.317489E+10 | 0.00 | 0.00 |
September | 0.738915E+10 | 0.138994E+10 | 0.685761E+10 | 0.385493E+10 | 0.300269E+10 | 0.00 | 0.00 |
October | 0.866408E+10 | 0.366233E+10 | 0.836860E+10 | 0.593079E+10 | 0.243781E+10 | 0.00 | 0.00 |
November | 0.107372E+11 | 0.415596E+10 | 0.992324E+10 | 0.791549E+10 | 0.200774E+10 | 0.00 | 0.00 |
December | 0.103436E+11 | 0.529208E+10 | 0.978259E+10 | 0.791909E+10 | 0.186351E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.864531E+11 | 0.347637E+11 | 0.852475E+11 | 0.531943E+11 | 0.320532E+11 | 0.00 | 0.00 |
Minimum of Months | 0.347226E+10 | 0.659150E+09 | 0.397057E+10 | 0.715561E+09 | 0.186351E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114223E+11 | 0.529208E+10 | 0.106747E+11 | 0.878748E+10 | 0.364633E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151452E+11 | 0.606834E+10 | 0.138671E+11 | 0.114154E+11 | 0.245163E+10 | 0.00 | 0.00 |
February | 0.121449E+11 | 0.585351E+10 | 0.118578E+11 | 0.942953E+10 | 0.242822E+10 | 0.00 | 0.00 |
March | 0.921807E+10 | 0.515821E+10 | 0.985977E+10 | 0.651756E+10 | 0.334221E+10 | 0.00 | 0.00 |
April | 0.461339E+10 | 0.448361E+10 | 0.624478E+10 | 0.258296E+10 | 0.366181E+10 | 0.00 | 0.00 |
May | 0.492693E+10 | 0.248426E+10 | 0.586358E+10 | 0.112679E+10 | 0.473679E+10 | 0.00 | 0.00 |
June | 0.580800E+10 | 0.997342E+09 | 0.515799E+10 | 0.929554E+09 | 0.422844E+10 | 0.00 | 0.00 |
July | 0.642395E+10 | 0.871419E+09 | 0.550592E+10 | 0.936923E+09 | 0.456900E+10 | 0.00 | 0.00 |
August | 0.737159E+10 | 0.103454E+10 | 0.700577E+10 | 0.288141E+10 | 0.412436E+10 | 0.00 | 0.00 |
September | 0.981601E+10 | 0.183113E+10 | 0.890843E+10 | 0.500777E+10 | 0.390066E+10 | 0.00 | 0.00 |
October | 0.114940E+11 | 0.486182E+10 | 0.108713E+11 | 0.770444E+10 | 0.316685E+10 | 0.00 | 0.00 |
November | 0.142404E+11 | 0.549310E+10 | 0.128908E+11 | 0.102827E+11 | 0.260817E+10 | 0.00 | 0.00 |
December | 0.136928E+11 | 0.700913E+10 | 0.127081E+11 | 0.102873E+11 | 0.242080E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114895E+12 | 0.461464E+11 | 0.110741E+12 | 0.691024E+11 | 0.416390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.461339E+10 | 0.871419E+09 | 0.515799E+10 | 0.929554E+09 | 0.242080E+10 | 0.00 | 0.00 |
Maximum of Months | 0.151452E+11 | 0.700913E+10 | 0.138671E+11 | 0.114154E+11 | 0.473679E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109596E+10 | 0.982909E+09 | 0.123211E+10 | 0.922593E+09 | 0.309520E+09 | 0.00 | 0.00 |
February | 0.995340E+09 | 0.943073E+09 | 0.116776E+10 | 0.836242E+09 | 0.331516E+09 | 0.00 | 0.00 |
March | 0.104764E+10 | 0.816020E+09 | 0.121384E+10 | 0.727274E+09 | 0.486571E+09 | 0.00 | 0.00 |
April | 0.736784E+09 | 0.705601E+09 | 0.959342E+09 | 0.403045E+09 | 0.556297E+09 | 0.00 | 0.00 |
May | 0.102644E+10 | 0.395962E+09 | 0.110265E+10 | 0.338474E+09 | 0.764174E+09 | 0.00 | 0.00 |
June | 0.143935E+10 | 0.166076E+09 | 0.120722E+10 | 0.496692E+09 | 0.710528E+09 | 0.00 | 0.00 |
July | 0.130181E+10 | 0.145216E+09 | 0.107831E+10 | 0.335760E+09 | 0.742549E+09 | 0.00 | 0.00 |
August | 0.137824E+10 | 0.171566E+09 | 0.119611E+10 | 0.559749E+09 | 0.636357E+09 | 0.00 | 0.00 |
September | 0.131978E+10 | 0.300027E+09 | 0.118514E+10 | 0.609161E+09 | 0.575980E+09 | 0.00 | 0.00 |
October | 0.115605E+10 | 0.780762E+09 | 0.119604E+10 | 0.764025E+09 | 0.432013E+09 | 0.00 | 0.00 |
November | 0.109555E+10 | 0.885900E+09 | 0.117982E+10 | 0.848918E+09 | 0.330904E+09 | 0.00 | 0.00 |
December | 0.921232E+09 | 0.114098E+10 | 0.108930E+10 | 0.793382E+09 | 0.295918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135142E+11 | 0.743409E+10 | 0.138076E+11 | 0.763532E+10 | 0.617233E+10 | 0.00 | 0.00 |
Minimum of Months | 0.736784E+09 | 0.145216E+09 | 0.959342E+09 | 0.335760E+09 | 0.295918E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143935E+10 | 0.114098E+10 | 0.123211E+10 | 0.922593E+09 | 0.764174E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.353738E+09 | 0.105412E+10 | 0.561887E+09 | 0.306849E+09 | 0.255038E+09 | 0.00 | 0.00 |
February | 0.395301E+09 | 0.985873E+09 | 0.616431E+09 | 0.327617E+09 | 0.288814E+09 | 0.00 | 0.00 |
March | 0.622095E+09 | 0.824793E+09 | 0.815036E+09 | 0.375726E+09 | 0.439310E+09 | 0.00 | 0.00 |
April | 0.572253E+09 | 0.701461E+09 | 0.784316E+09 | 0.264770E+09 | 0.519545E+09 | 0.00 | 0.00 |
May | 0.951653E+09 | 0.386843E+09 | 0.101477E+10 | 0.285332E+09 | 0.729443E+09 | 0.00 | 0.00 |
June | 0.141295E+10 | 0.156643E+09 | 0.117132E+10 | 0.473608E+09 | 0.697713E+09 | 0.00 | 0.00 |
July | 0.125477E+10 | 0.138907E+09 | 0.101883E+10 | 0.301404E+09 | 0.717428E+09 | 0.00 | 0.00 |
August | 0.122037E+10 | 0.167884E+09 | 0.100732E+10 | 0.409418E+09 | 0.597901E+09 | 0.00 | 0.00 |
September | 0.971941E+09 | 0.296757E+09 | 0.857871E+09 | 0.339164E+09 | 0.518707E+09 | 0.00 | 0.00 |
October | 0.614430E+09 | 0.783337E+09 | 0.722941E+09 | 0.348451E+09 | 0.374490E+09 | 0.00 | 0.00 |
November | 0.388219E+09 | 0.919443E+09 | 0.567726E+09 | 0.294275E+09 | 0.273452E+09 | 0.00 | 0.00 |
December | 0.259384E+09 | 0.122366E+10 | 0.476580E+09 | 0.238487E+09 | 0.238094E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.901711E+10 | 0.763972E+10 | 0.961503E+10 | 0.396510E+10 | 0.564993E+10 | 0.00 | 0.00 |
Minimum of Months | 0.259384E+09 | 0.138907E+09 | 0.476580E+09 | 0.238487E+09 | 0.238094E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141295E+10 | 0.122366E+10 | 0.117132E+10 | 0.473608E+09 | 0.729443E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633854E+09 | 0.294364E+09 | 0.598268E+09 | 0.492497E+09 | 0.105771E+09 | 0.00 | 0.00 |
February | 0.506890E+09 | 0.277781E+09 | 0.511580E+09 | 0.406819E+09 | 0.104761E+09 | 0.00 | 0.00 |
March | 0.383813E+09 | 0.247117E+09 | 0.425381E+09 | 0.281188E+09 | 0.144193E+09 | 0.00 | 0.00 |
April | 0.188002E+09 | 0.221696E+09 | 0.269419E+09 | 0.111437E+09 | 0.157982E+09 | 0.00 | 0.00 |
May | 0.193372E+09 | 0.133646E+09 | 0.252973E+09 | 48613315.27 | 0.204360E+09 | 0.00 | 0.00 |
June | 0.232937E+09 | 61022831.39 | 0.222532E+09 | 40103841.36 | 0.182428E+09 | 0.00 | 0.00 |
July | 0.258002E+09 | 55964196.64 | 0.237542E+09 | 40421743.43 | 0.197121E+09 | 0.00 | 0.00 |
August | 0.300060E+09 | 65086395.48 | 0.302250E+09 | 0.124313E+09 | 0.177938E+09 | 0.00 | 0.00 |
September | 0.406362E+09 | 0.103099E+09 | 0.384337E+09 | 0.216051E+09 | 0.168287E+09 | 0.00 | 0.00 |
October | 0.480466E+09 | 0.240717E+09 | 0.469021E+09 | 0.332393E+09 | 0.136628E+09 | 0.00 | 0.00 |
November | 0.597593E+09 | 0.267865E+09 | 0.556151E+09 | 0.443626E+09 | 0.112525E+09 | 0.00 | 0.00 |
December | 0.572182E+09 | 0.334331E+09 | 0.548269E+09 | 0.443828E+09 | 0.104441E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.475353E+10 | 0.230269E+10 | 0.477772E+10 | 0.298129E+10 | 0.179643E+10 | 0.00 | 0.00 |
Minimum of Months | 0.188002E+09 | 55964196.64 | 0.222532E+09 | 40103841.36 | 0.104441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.633854E+09 | 0.334331E+09 | 0.598268E+09 | 0.492497E+09 | 0.204360E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7333758.76 | 0.322967E+09 | 62214833.19 | 0.00 | 62214833.19 | 0.00 | 0.00 |
February | 8086096.38 | 0.300967E+09 | 70629144.56 | 0.00 | 70629144.56 | 0.00 | 0.00 |
March | 36383164.32 | 0.246811E+09 | 0.106433E+09 | 5233.92 | 0.106428E+09 | 0.00 | 0.00 |
April | 56014143.28 | 0.206832E+09 | 0.129468E+09 | 839145.32 | 0.128629E+09 | 0.00 | 0.00 |
May | 0.143113E+09 | 0.107431E+09 | 0.182749E+09 | 6110414.98 | 0.176639E+09 | 0.00 | 0.00 |
June | 0.228413E+09 | 40958804.91 | 0.193882E+09 | 21647251.90 | 0.172235E+09 | 0.00 | 0.00 |
July | 0.236211E+09 | 37003309.58 | 0.190033E+09 | 12946816.89 | 0.177087E+09 | 0.00 | 0.00 |
August | 0.184892E+09 | 45316062.37 | 0.151301E+09 | 4073460.39 | 0.147228E+09 | 0.00 | 0.00 |
September | 0.133711E+09 | 82737200.18 | 0.122614E+09 | 95794.47 | 0.122518E+09 | 0.00 | 0.00 |
October | 42481662.41 | 0.228260E+09 | 90649055.63 | 0.00 | 90649055.63 | 0.00 | 0.00 |
November | 13167986.20 | 0.278040E+09 | 66594299.12 | 0.00 | 66594299.12 | 0.00 | 0.00 |
December | 6447626.58 | 0.373340E+09 | 58209760.13 | 0.00 | 58209760.13 | 0.00 | 0.00 |
Annual Sum or Average | 0.109625E+10 | 0.227066E+10 | 0.142478E+10 | 45718117.87 | 0.137906E+10 | 0.00 | 0.00 |
Minimum of Months | 6447626.58 | 37003309.58 | 58209760.13 | 0.00 | 58209760.13 | 0.00 | 0.00 |
Maximum of Months | 0.236211E+09 | 0.373340E+09 | 0.193882E+09 | 21647251.90 | 0.177087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104713E+10 | 0.973066E+09 | 0.120122E+10 | 0.892989E+09 | 0.308232E+09 | 0.00 | 0.00 |
February | 0.101613E+10 | 0.939349E+09 | 0.118831E+10 | 0.855896E+09 | 0.332413E+09 | 0.00 | 0.00 |
March | 0.109283E+10 | 0.806237E+09 | 0.126366E+10 | 0.778737E+09 | 0.484925E+09 | 0.00 | 0.00 |
April | 0.841695E+09 | 0.690533E+09 | 0.105983E+10 | 0.491474E+09 | 0.568353E+09 | 0.00 | 0.00 |
May | 0.111272E+10 | 0.371754E+09 | 0.119197E+10 | 0.427323E+09 | 0.764649E+09 | 0.00 | 0.00 |
June | 0.155055E+10 | 0.150558E+09 | 0.130932E+10 | 0.591207E+09 | 0.718112E+09 | 0.00 | 0.00 |
July | 0.152222E+10 | 0.136096E+09 | 0.126413E+10 | 0.510036E+09 | 0.754093E+09 | 0.00 | 0.00 |
August | 0.156169E+10 | 0.164939E+09 | 0.135592E+10 | 0.694253E+09 | 0.661666E+09 | 0.00 | 0.00 |
September | 0.140308E+10 | 0.284823E+09 | 0.126944E+10 | 0.698998E+09 | 0.570443E+09 | 0.00 | 0.00 |
October | 0.111733E+10 | 0.770178E+09 | 0.117622E+10 | 0.739047E+09 | 0.437175E+09 | 0.00 | 0.00 |
November | 0.103160E+10 | 0.881053E+09 | 0.113831E+10 | 0.804292E+09 | 0.334015E+09 | 0.00 | 0.00 |
December | 0.909791E+09 | 0.114205E+10 | 0.108253E+10 | 0.783737E+09 | 0.298797E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142068E+11 | 0.731063E+10 | 0.145009E+11 | 0.826799E+10 | 0.623287E+10 | 0.00 | 0.00 |
Minimum of Months | 0.841695E+09 | 0.136096E+09 | 0.105983E+10 | 0.427323E+09 | 0.298797E+09 | 0.00 | 0.00 |
Maximum of Months | 0.156169E+10 | 0.114205E+10 | 0.135592E+10 | 0.892989E+09 | 0.764649E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289710E+09 | 0.102671E+10 | 0.530994E+09 | 0.277245E+09 | 0.253750E+09 | 0.00 | 0.00 |
February | 0.406526E+09 | 0.972568E+09 | 0.636981E+09 | 0.347271E+09 | 0.289711E+09 | 0.00 | 0.00 |
March | 0.654608E+09 | 0.804304E+09 | 0.864853E+09 | 0.427189E+09 | 0.437664E+09 | 0.00 | 0.00 |
April | 0.674856E+09 | 0.685576E+09 | 0.884800E+09 | 0.353199E+09 | 0.531602E+09 | 0.00 | 0.00 |
May | 0.104168E+10 | 0.366747E+09 | 0.110410E+10 | 0.374181E+09 | 0.729918E+09 | 0.00 | 0.00 |
June | 0.153230E+10 | 0.149135E+09 | 0.127342E+10 | 0.568123E+09 | 0.705297E+09 | 0.00 | 0.00 |
July | 0.148022E+10 | 0.134891E+09 | 0.120465E+10 | 0.475680E+09 | 0.728972E+09 | 0.00 | 0.00 |
August | 0.140414E+10 | 0.162503E+09 | 0.116713E+10 | 0.543922E+09 | 0.623210E+09 | 0.00 | 0.00 |
September | 0.105193E+10 | 0.280540E+09 | 0.942171E+09 | 0.429000E+09 | 0.513171E+09 | 0.00 | 0.00 |
October | 0.566609E+09 | 0.765239E+09 | 0.703125E+09 | 0.323473E+09 | 0.379652E+09 | 0.00 | 0.00 |
November | 0.314560E+09 | 0.903208E+09 | 0.526213E+09 | 0.249649E+09 | 0.276563E+09 | 0.00 | 0.00 |
December | 0.229813E+09 | 0.120462E+10 | 0.469814E+09 | 0.228841E+09 | 0.240973E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.964695E+10 | 0.745604E+10 | 0.103083E+11 | 0.459777E+10 | 0.571048E+10 | 0.00 | 0.00 |
Minimum of Months | 0.229813E+09 | 0.134891E+09 | 0.469814E+09 | 0.228841E+09 | 0.240973E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153230E+10 | 0.120462E+10 | 0.127342E+10 | 0.568123E+09 | 0.729918E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134098E+10 | 0.117959E+10 | 0.143106E+10 | 0.106710E+10 | 0.363955E+09 | 0.00 | 0.00 |
February | 0.109069E+10 | 0.114960E+10 | 0.126146E+10 | 0.881464E+09 | 0.379994E+09 | 0.00 | 0.00 |
March | 0.935369E+09 | 0.100497E+10 | 0.115225E+10 | 0.609267E+09 | 0.542985E+09 | 0.00 | 0.00 |
April | 0.562159E+09 | 0.862567E+09 | 0.864228E+09 | 0.243271E+09 | 0.620957E+09 | 0.00 | 0.00 |
May | 0.796517E+09 | 0.453947E+09 | 0.944019E+09 | 0.118569E+09 | 0.825450E+09 | 0.00 | 0.00 |
June | 0.107367E+10 | 0.164722E+09 | 0.902178E+09 | 0.133789E+09 | 0.768389E+09 | 0.00 | 0.00 |
July | 0.115096E+10 | 0.145383E+09 | 0.926365E+09 | 0.115630E+09 | 0.810735E+09 | 0.00 | 0.00 |
August | 0.112641E+10 | 0.181168E+09 | 0.982662E+09 | 0.278176E+09 | 0.704486E+09 | 0.00 | 0.00 |
September | 0.123454E+10 | 0.335301E+09 | 0.109838E+10 | 0.468329E+09 | 0.630046E+09 | 0.00 | 0.00 |
October | 0.116734E+10 | 0.936010E+09 | 0.121261E+10 | 0.720204E+09 | 0.492411E+09 | 0.00 | 0.00 |
November | 0.131036E+10 | 0.106652E+10 | 0.134929E+10 | 0.961215E+09 | 0.388075E+09 | 0.00 | 0.00 |
December | 0.119285E+10 | 0.138088E+10 | 0.131405E+10 | 0.961652E+09 | 0.352396E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129818E+11 | 0.886065E+10 | 0.134385E+11 | 0.655867E+10 | 0.687988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.562159E+09 | 0.145383E+09 | 0.864228E+09 | 0.115630E+09 | 0.352396E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134098E+10 | 0.138088E+10 | 0.143106E+10 | 0.106710E+10 | 0.825450E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109393E+10 | 0.979409E+09 | 0.123312E+10 | 0.923350E+09 | 0.309773E+09 | 0.00 | 0.00 |
February | 0.990422E+09 | 0.944217E+09 | 0.116872E+10 | 0.836928E+09 | 0.331788E+09 | 0.00 | 0.00 |
March | 0.104160E+10 | 0.815960E+09 | 0.121484E+10 | 0.727871E+09 | 0.486970E+09 | 0.00 | 0.00 |
April | 0.730525E+09 | 0.705711E+09 | 0.960129E+09 | 0.403376E+09 | 0.556754E+09 | 0.00 | 0.00 |
May | 0.101380E+10 | 0.398889E+09 | 0.110355E+10 | 0.338751E+09 | 0.764801E+09 | 0.00 | 0.00 |
June | 0.142560E+10 | 0.168181E+09 | 0.120821E+10 | 0.497099E+09 | 0.711111E+09 | 0.00 | 0.00 |
July | 0.128862E+10 | 0.147492E+09 | 0.107919E+10 | 0.336035E+09 | 0.743158E+09 | 0.00 | 0.00 |
August | 0.136493E+10 | 0.174157E+09 | 0.119709E+10 | 0.560209E+09 | 0.636879E+09 | 0.00 | 0.00 |
September | 0.131050E+10 | 0.301748E+09 | 0.118611E+10 | 0.609661E+09 | 0.576452E+09 | 0.00 | 0.00 |
October | 0.114992E+10 | 0.780987E+09 | 0.119702E+10 | 0.764652E+09 | 0.432367E+09 | 0.00 | 0.00 |
November | 0.109102E+10 | 0.885026E+09 | 0.118079E+10 | 0.849614E+09 | 0.331175E+09 | 0.00 | 0.00 |
December | 0.919126E+09 | 0.114066E+10 | 0.109019E+10 | 0.794033E+09 | 0.296161E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134200E+11 | 0.744243E+10 | 0.138190E+11 | 0.764158E+10 | 0.617739E+10 | 0.00 | 0.00 |
Minimum of Months | 0.730525E+09 | 0.147492E+09 | 0.960129E+09 | 0.336035E+09 | 0.296161E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142560E+10 | 0.114066E+10 | 0.123312E+10 | 0.923350E+09 | 0.764801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.354478E+09 | 0.104650E+10 | 0.562348E+09 | 0.307101E+09 | 0.255247E+09 | 0.00 | 0.00 |
February | 0.393187E+09 | 0.984656E+09 | 0.616936E+09 | 0.327886E+09 | 0.289051E+09 | 0.00 | 0.00 |
March | 0.617026E+09 | 0.823599E+09 | 0.815705E+09 | 0.376034E+09 | 0.439670E+09 | 0.00 | 0.00 |
April | 0.565568E+09 | 0.700952E+09 | 0.784959E+09 | 0.264987E+09 | 0.519972E+09 | 0.00 | 0.00 |
May | 0.937900E+09 | 0.389290E+09 | 0.101561E+10 | 0.285566E+09 | 0.730041E+09 | 0.00 | 0.00 |
June | 0.139841E+10 | 0.158843E+09 | 0.117228E+10 | 0.473996E+09 | 0.698285E+09 | 0.00 | 0.00 |
July | 0.124082E+10 | 0.141287E+09 | 0.101967E+10 | 0.301651E+09 | 0.718016E+09 | 0.00 | 0.00 |
August | 0.120563E+10 | 0.170529E+09 | 0.100815E+10 | 0.409754E+09 | 0.598391E+09 | 0.00 | 0.00 |
September | 0.961799E+09 | 0.298287E+09 | 0.858575E+09 | 0.339442E+09 | 0.519133E+09 | 0.00 | 0.00 |
October | 0.608747E+09 | 0.782493E+09 | 0.723534E+09 | 0.348737E+09 | 0.374798E+09 | 0.00 | 0.00 |
November | 0.386557E+09 | 0.915499E+09 | 0.568192E+09 | 0.294516E+09 | 0.273676E+09 | 0.00 | 0.00 |
December | 0.260793E+09 | 0.121983E+10 | 0.476971E+09 | 0.238682E+09 | 0.238289E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.893092E+10 | 0.763176E+10 | 0.962292E+10 | 0.396835E+10 | 0.565457E+10 | 0.00 | 0.00 |
Minimum of Months | 0.260793E+09 | 0.141287E+09 | 0.476971E+09 | 0.238682E+09 | 0.238289E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139841E+10 | 0.121983E+10 | 0.117228E+10 | 0.473996E+09 | 0.730041E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115927E+10 | 0.508281E+09 | 0.109789E+10 | 0.903788E+09 | 0.194102E+09 | 0.00 | 0.00 |
February | 0.924700E+09 | 0.494303E+09 | 0.938808E+09 | 0.746560E+09 | 0.192248E+09 | 0.00 | 0.00 |
March | 0.702416E+09 | 0.431446E+09 | 0.780623E+09 | 0.516012E+09 | 0.264611E+09 | 0.00 | 0.00 |
April | 0.348158E+09 | 0.375394E+09 | 0.494414E+09 | 0.204499E+09 | 0.289915E+09 | 0.00 | 0.00 |
May | 0.368482E+09 | 0.209066E+09 | 0.464235E+09 | 89210962.68 | 0.375024E+09 | 0.00 | 0.00 |
June | 0.443455E+09 | 83153099.95 | 0.408371E+09 | 73595110.21 | 0.334776E+09 | 0.00 | 0.00 |
July | 0.489916E+09 | 73548780.35 | 0.435917E+09 | 74178496.66 | 0.361739E+09 | 0.00 | 0.00 |
August | 0.563714E+09 | 88122343.07 | 0.554664E+09 | 0.228128E+09 | 0.326536E+09 | 0.00 | 0.00 |
September | 0.753718E+09 | 0.154624E+09 | 0.705303E+09 | 0.396477E+09 | 0.308825E+09 | 0.00 | 0.00 |
October | 0.882299E+09 | 0.406610E+09 | 0.860707E+09 | 0.609980E+09 | 0.250727E+09 | 0.00 | 0.00 |
November | 0.109109E+10 | 0.462506E+09 | 0.102060E+10 | 0.814105E+09 | 0.206496E+09 | 0.00 | 0.00 |
December | 0.104097E+10 | 0.594604E+09 | 0.100614E+10 | 0.814475E+09 | 0.191661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876819E+10 | 0.388166E+10 | 0.876767E+10 | 0.547101E+10 | 0.329666E+10 | 0.00 | 0.00 |
Minimum of Months | 0.348158E+09 | 73548780.35 | 0.408371E+09 | 73595110.21 | 0.191661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115927E+10 | 0.594604E+09 | 0.109789E+10 | 0.903788E+09 | 0.375024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 65766262.34 | 0.277867E+10 | 0.544734E+09 | 0.00 | 0.544734E+09 | 0.00 | 0.00 |
February | 71660106.32 | 0.260976E+10 | 0.618407E+09 | 0.00 | 0.618407E+09 | 0.00 | 0.00 |
March | 0.323598E+09 | 0.213817E+10 | 0.931894E+09 | 45826.56 | 0.931848E+09 | 0.00 | 0.00 |
April | 0.499996E+09 | 0.179319E+10 | 0.113358E+10 | 7347292.69 | 0.112624E+10 | 0.00 | 0.00 |
May | 0.128998E+10 | 0.936396E+09 | 0.160010E+10 | 53500873.27 | 0.154660E+10 | 0.00 | 0.00 |
June | 0.206536E+10 | 0.343577E+09 | 0.169757E+10 | 0.189537E+09 | 0.150803E+10 | 0.00 | 0.00 |
July | 0.214175E+10 | 0.306201E+09 | 0.166387E+10 | 0.113358E+09 | 0.155051E+10 | 0.00 | 0.00 |
August | 0.167903E+10 | 0.374956E+09 | 0.132475E+10 | 35665939.04 | 0.128908E+10 | 0.00 | 0.00 |
September | 0.121526E+10 | 0.699709E+09 | 0.107357E+10 | 838746.27 | 0.107273E+10 | 0.00 | 0.00 |
October | 0.382364E+09 | 0.197581E+10 | 0.793695E+09 | 0.00 | 0.793695E+09 | 0.00 | 0.00 |
November | 0.116919E+09 | 0.239766E+10 | 0.583079E+09 | 0.00 | 0.583079E+09 | 0.00 | 0.00 |
December | 57061024.27 | 0.323503E+10 | 0.509666E+09 | 0.00 | 0.509666E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990873E+10 | 0.195891E+11 | 0.124749E+11 | 0.400293E+09 | 0.120746E+11 | 0.00 | 0.00 |
Minimum of Months | 57061024.27 | 0.306201E+09 | 0.509666E+09 | 0.00 | 0.509666E+09 | 0.00 | 0.00 |
Maximum of Months | 0.214175E+10 | 0.323503E+10 | 0.169757E+10 | 0.189537E+09 | 0.155051E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 61772043.89 | 0.282257E+10 | 0.544734E+09 | 0.00 | 0.544734E+09 | 0.00 | 0.00 |
February | 67864023.07 | 0.265092E+10 | 0.618407E+09 | 0.00 | 0.618407E+09 | 0.00 | 0.00 |
March | 0.313051E+09 | 0.217990E+10 | 0.931894E+09 | 45826.56 | 0.931848E+09 | 0.00 | 0.00 |
April | 0.486666E+09 | 0.183178E+10 | 0.113358E+10 | 7347292.69 | 0.112624E+10 | 0.00 | 0.00 |
May | 0.126746E+10 | 0.962111E+09 | 0.160010E+10 | 53500873.27 | 0.154660E+10 | 0.00 | 0.00 |
June | 0.204235E+10 | 0.357960E+09 | 0.169757E+10 | 0.189537E+09 | 0.150803E+10 | 0.00 | 0.00 |
July | 0.211830E+10 | 0.320561E+09 | 0.166387E+10 | 0.113358E+09 | 0.155051E+10 | 0.00 | 0.00 |
August | 0.165777E+10 | 0.391379E+09 | 0.132475E+10 | 35665939.04 | 0.128908E+10 | 0.00 | 0.00 |
September | 0.119819E+10 | 0.722001E+09 | 0.107357E+10 | 838746.27 | 0.107273E+10 | 0.00 | 0.00 |
October | 0.371664E+09 | 0.201433E+10 | 0.793695E+09 | 0.00 | 0.793695E+09 | 0.00 | 0.00 |
November | 0.111893E+09 | 0.243973E+10 | 0.583079E+09 | 0.00 | 0.583079E+09 | 0.00 | 0.00 |
December | 54059187.21 | 0.328232E+10 | 0.509666E+09 | 0.00 | 0.509666E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975104E+10 | 0.199756E+11 | 0.124749E+11 | 0.400293E+09 | 0.120746E+11 | 0.00 | 0.00 |
Minimum of Months | 54059187.21 | 0.320561E+09 | 0.509666E+09 | 0.00 | 0.509666E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211830E+10 | 0.328232E+10 | 0.169757E+10 | 0.189537E+09 | 0.155051E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143232E+10 | 0.185414E+10 | 0.173357E+10 | 0.117115E+10 | 0.562417E+09 | 0.00 | 0.00 |
February | 0.150533E+10 | 0.182867E+10 | 0.182671E+10 | 0.120410E+10 | 0.622605E+09 | 0.00 | 0.00 |
March | 0.190857E+10 | 0.157423E+10 | 0.213016E+10 | 0.120685E+10 | 0.923302E+09 | 0.00 | 0.00 |
April | 0.167967E+10 | 0.136517E+10 | 0.194612E+10 | 0.845316E+09 | 0.110080E+10 | 0.00 | 0.00 |
May | 0.249278E+10 | 0.742553E+09 | 0.229783E+10 | 0.802109E+09 | 0.149572E+10 | 0.00 | 0.00 |
June | 0.352573E+10 | 0.297321E+09 | 0.258471E+10 | 0.116020E+10 | 0.142451E+10 | 0.00 | 0.00 |
July | 0.346337E+10 | 0.271101E+09 | 0.247067E+10 | 0.986459E+09 | 0.148421E+10 | 0.00 | 0.00 |
August | 0.340731E+10 | 0.307981E+09 | 0.252498E+10 | 0.123912E+10 | 0.128587E+10 | 0.00 | 0.00 |
September | 0.283135E+10 | 0.529256E+09 | 0.221331E+10 | 0.112886E+10 | 0.108445E+10 | 0.00 | 0.00 |
October | 0.187463E+10 | 0.146950E+10 | 0.188081E+10 | 0.106335E+10 | 0.817459E+09 | 0.00 | 0.00 |
November | 0.146352E+10 | 0.168225E+10 | 0.166582E+10 | 0.105477E+10 | 0.611052E+09 | 0.00 | 0.00 |
December | 0.119295E+10 | 0.222970E+10 | 0.155356E+10 | 0.101338E+10 | 0.540189E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.267775E+11 | 0.141519E+11 | 0.248283E+11 | 0.128757E+11 | 0.119526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.119295E+10 | 0.271101E+09 | 0.155356E+10 | 0.802109E+09 | 0.540189E+09 | 0.00 | 0.00 |
Maximum of Months | 0.352573E+10 | 0.222970E+10 | 0.258471E+10 | 0.123912E+10 | 0.149572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291551E+10 | 0.208078E+10 | 0.298147E+10 | 0.230064E+10 | 0.680833E+09 | 0.00 | 0.00 |
February | 0.235051E+10 | 0.203749E+10 | 0.260178E+10 | 0.190041E+10 | 0.701369E+09 | 0.00 | 0.00 |
March | 0.193229E+10 | 0.178760E+10 | 0.230657E+10 | 0.131355E+10 | 0.993021E+09 | 0.00 | 0.00 |
April | 0.109143E+10 | 0.154475E+10 | 0.164715E+10 | 0.523083E+09 | 0.112407E+10 | 0.00 | 0.00 |
May | 0.143110E+10 | 0.824821E+09 | 0.173025E+10 | 0.245431E+09 | 0.148482E+10 | 0.00 | 0.00 |
June | 0.187989E+10 | 0.305771E+09 | 0.162146E+10 | 0.252314E+09 | 0.136915E+10 | 0.00 | 0.00 |
July | 0.203116E+10 | 0.271606E+09 | 0.168003E+10 | 0.227685E+09 | 0.145235E+10 | 0.00 | 0.00 |
August | 0.206548E+10 | 0.335368E+09 | 0.186605E+10 | 0.592939E+09 | 0.127311E+10 | 0.00 | 0.00 |
September | 0.239512E+10 | 0.605531E+09 | 0.216341E+10 | 0.100954E+10 | 0.115387E+10 | 0.00 | 0.00 |
October | 0.241849E+10 | 0.166829E+10 | 0.246306E+10 | 0.155274E+10 | 0.910320E+09 | 0.00 | 0.00 |
November | 0.280763E+10 | 0.189086E+10 | 0.279787E+10 | 0.207235E+10 | 0.725526E+09 | 0.00 | 0.00 |
December | 0.260007E+10 | 0.243824E+10 | 0.273589E+10 | 0.207329E+10 | 0.662597E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259187E+11 | 0.157911E+11 | 0.265950E+11 | 0.140640E+11 | 0.125310E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109143E+10 | 0.271606E+09 | 0.162146E+10 | 0.227685E+09 | 0.662597E+09 | 0.00 | 0.00 |
Maximum of Months | 0.291551E+10 | 0.243824E+10 | 0.298147E+10 | 0.230064E+10 | 0.148482E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.40 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.31 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.51 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.44 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.23 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.78 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.33 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.32 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.39 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.23 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.93 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.71 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.86 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.46 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.89 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.59 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.86 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.32 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.01 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.69 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.06 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.90 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.93 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.32 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.3 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.44 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.29 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.21 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.8 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.21 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.52 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.95 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 7.98 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.48 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.84 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.63 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.73 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.79 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.51 | 196.33 | 4.00 |
September | 14.93 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.69 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.31 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.90 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.52 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.73 | 29.40 | 16.00 | 9.80 | 20.51 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.48 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.72 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.63 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.91 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.89 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.39 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.05 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.05 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.63 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.391058E+11 | -.737992E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159163E+10 | 59.15 | 0.00 | 0.00 |
February | 0.362605E+11 | -.675163E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.143911E+10 | 59.18 | 0.00 | 0.00 |
March | 0.390076E+11 | -.737036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159647E+10 | 59.19 | 0.00 | 0.00 |
April | 0.346394E+11 | -.684749E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.154684E+10 | 59.23 | 0.00 | 0.00 |
May | 0.315448E+11 | -.668539E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.161057E+10 | 59.38 | 0.00 | 0.00 |
June | 0.264449E+11 | -.609434E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.157330E+10 | 59.60 | 0.00 | 0.00 |
July | 0.241719E+11 | -.600786E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.163270E+10 | 59.74 | 0.00 | 0.00 |
August | 0.231485E+11 | -.591461E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.162742E+10 | 59.79 | 0.00 | 0.00 |
September | 0.235521E+11 | -.583020E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.156584E+10 | 59.71 | 0.00 | 0.00 |
October | 0.275154E+11 | -.631728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.160078E+10 | 59.56 | 0.00 | 0.00 |
November | 0.307816E+11 | -.649489E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.154087E+10 | 59.38 | 0.00 | 0.00 |
December | 0.360432E+11 | -.709942E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159000E+10 | 59.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.372216E+12 | -.787934E+12 | 8760.00 | -.189155E+11 | 59.43 | |||||
Minimum of Months | 0.231485E+11 | -.737992E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.163270E+10 | 59.15 | 0.00 | 0.00 |
Maximum of Months | 0.391058E+11 | -.583020E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.143911E+10 | 59.79 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770745E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164665425.4 | 81.21 | 0.00 | 0.00 |
February | 0.696461E+10 | -.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148637774.2 | 81.21 | 0.00 | 0.00 |
March | 0.770747E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164670746.8 | 81.21 | 0.00 | 0.00 |
April | 0.746801E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159432617.6 | 81.21 | 0.00 | 0.00 |
May | 0.770845E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165654478.4 | 81.21 | 0.00 | 0.00 |
June | 0.746209E+10 | -.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -161547261.7 | 81.21 | 0.00 | 0.00 |
July | 0.771797E+10 | -.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167106750.5 | 81.21 | 0.00 | 0.00 |
August | 0.770979E+10 | -.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166965917.8 | 81.21 | 0.00 | 0.00 |
September | 0.746992E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -161323340.4 | 81.21 | 0.00 | 0.00 |
October | 0.770776E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164988606.4 | 81.21 | 0.00 | 0.00 |
November | 0.745182E+10 | -.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159391784.1 | 81.21 | 0.00 | 0.00 |
December | 0.771584E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164991095.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907912E+11 | -.888418E+11 | 8760.00 | -.194938E+10 | 81.21 | |||||
Minimum of Months | 0.696461E+10 | -.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167106750.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771797E+10 | -.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148637774.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.789146E+11 | -.776661E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124849E+10 | 62.48 | 0.00 | 0.00 |
February | 0.713616E+11 | -.702401E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.112151E+10 | 62.24 | 0.00 | 0.00 |
March | 0.788902E+11 | -.776406E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124963E+10 | 62.44 | 0.00 | 0.00 |
April | 0.760721E+11 | -.748428E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122936E+10 | 63.13 | 0.00 | 0.00 |
May | 0.782150E+11 | -.769141E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130086E+10 | 64.00 | 0.00 | 0.00 |
June | 0.753145E+11 | -.740262E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128832E+10 | 64.86 | 0.00 | 0.00 |
July | 0.775425E+11 | -.761920E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135050E+10 | 65.47 | 0.00 | 0.00 |
August | 0.774422E+11 | -.760903E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135186E+10 | 65.69 | 0.00 | 0.00 |
September | 0.750535E+11 | -.737568E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.129670E+10 | 65.44 | 0.00 | 0.00 |
October | 0.778483E+11 | -.765358E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131257E+10 | 64.80 | 0.00 | 0.00 |
November | 0.757177E+11 | -.744725E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.124518E+10 | 63.96 | 0.00 | 0.00 |
December | 0.786321E+11 | -.773703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.126178E+10 | 63.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.921004E+12 | -.905748E+12 | 8760.00 | -.152567E+11 | 63.97 | |||||
Minimum of Months | 0.713616E+11 | -.776661E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.135186E+10 | 62.24 | 0.00 | 0.00 |
Maximum of Months | 0.789146E+11 | -.702401E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.112151E+10 | 65.69 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | ||||||||||
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717076E+10 | 9220.46 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.798972E+10 | 9179.17 | 18-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120508E+11 | 9225.94 | 14-MAR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115198E+11 | 9227.36 | 20-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169129E+11 | 9231.03 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221162E+11 | 9231.91 | 16-JUN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.230581E+11 | 9232.09 | 23-JUL-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197637E+11 | 9232.05 | 21-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125623E+11 | 9231.56 | 06-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.369998E+10 | 9227.42 | 09-OCT-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196108E+10 | 9225.92 | 07-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264733E+10 | 9226.30 | 01-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141453E+12 | |||||||
Minimum of Months | 0.196108E+10 | 9179.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230581E+11 | 9232.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.339616E+10 | 3349.12 | 06-JAN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349690E+10 | 3349.12 | 05-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375664E+10 | 3349.03 | 19-MAR-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.415275E+10 | 3159.56 | 03-APR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351028E+10 | 2251.01 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.290565E+10 | 1903.99 | 03-JUN-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302396E+10 | 1972.89 | 29-JUL-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.282552E+10 | 1963.36 | 01-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.242948E+10 | 2432.82 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317070E+10 | 3348.96 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312597E+10 | 3349.04 | 29-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412031E+10 | 3348.46 | 20-DEC-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399143E+11 | |||||||
Minimum of Months | 0.242948E+10 | 1903.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415275E+10 | 3349.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102436E+10 | 1253.85 | 05-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102783E+10 | 1302.37 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117635E+10 | 1274.41 | 19-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124906E+10 | 1323.90 | 19-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137843E+10 | 1384.61 | 04-MAY-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168296E+10 | 1314.52 | 23-JUN-10:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185183E+10 | 1366.63 | 28-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176831E+10 | 1366.26 | 23-AUG-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148179E+10 | 1335.51 | 19-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107244E+10 | 1264.19 | 31-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.960701E+09 | 1150.97 | 28-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127677E+10 | 1391.06 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159508E+11 | |||||||
Minimum of Months | 0.960701E+09 | 1150.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185183E+10 | 1391.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283559E+10 | 1880.03 | 06-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268034E+10 | 1879.90 | 06-FEB-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268577E+10 | 1738.01 | 20-MAR-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255495E+10 | 1797.25 | 03-APR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250050E+10 | 1717.71 | 04-MAY-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264416E+10 | 1593.17 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281359E+10 | 1632.51 | 30-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.284346E+10 | 1756.05 | 01-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262512E+10 | 1749.59 | 24-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250552E+10 | 1860.64 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257909E+10 | 1879.69 | 30-NOV-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310422E+10 | 1879.52 | 21-DEC-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323723E+11 | |||||||
Minimum of Months | 0.250050E+10 | 1593.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310422E+10 | 1880.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188854E+10 | 1060.27 | 06-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178782E+10 | 1060.23 | 06-FEB-01:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174187E+10 | 1060.17 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164088E+10 | 1020.84 | 03-APR-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142488E+10 | 795.79 | 04-MAY-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128179E+10 | 688.14 | 03-JUN-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134737E+10 | 718.92 | 30-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139714E+10 | 766.46 | 01-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136620E+10 | 785.12 | 23-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158343E+10 | 1054.02 | 31-OCT-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170190E+10 | 1060.24 | 29-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203062E+10 | 1060.15 | 25-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191924E+11 | |||||||
Minimum of Months | 0.128179E+10 | 688.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203062E+10 | 1060.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129913E+11 | 12979.76 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115071E+11 | 12921.75 | 18-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139798E+11 | 12987.55 | 14-MAR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137369E+11 | 12989.79 | 20-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184479E+11 | 12995.57 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243405E+11 | 12996.96 | 16-JUN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.257224E+11 | 12997.19 | 23-JUL-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249663E+11 | 12997.14 | 21-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220159E+11 | 12996.26 | 01-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149392E+11 | 12990.02 | 07-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128656E+11 | 12987.51 | 07-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133554E+11 | 12988.11 | 01-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208868E+12 | |||||||
Minimum of Months | 0.115071E+11 | 12921.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257224E+11 | 12997.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.491685E+10 | 10606.32 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.553112E+10 | 10501.95 | 05-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638572E+10 | 9363.06 | 19-MAR-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786992E+10 | 9520.27 | 03-APR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.740357E+10 | 7875.32 | 31-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.792518E+10 | 7574.56 | 05-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.839873E+10 | 7806.14 | 28-JUL-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749151E+10 | 7686.78 | 30-AUG-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.539965E+10 | 7652.82 | 06-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.516126E+10 | 10388.85 | 31-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454886E+10 | 10084.63 | 29-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699927E+10 | 10606.45 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780316E+11 | |||||||
Minimum of Months | 0.454886E+10 | 7574.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.839873E+10 | 10606.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105493E+11 | 24290.54 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114175E+11 | 25513.42 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151428E+11 | 23853.38 | 19-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177137E+11 | 22880.66 | 02-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208960E+11 | 25664.90 | 04-MAY-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262294E+11 | 24461.33 | 01-JUN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282919E+11 | 26132.16 | 28-JUL-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.264948E+11 | 25214.48 | 27-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213172E+11 | 24716.16 | 03-SEP-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134212E+11 | 24720.29 | 31-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101923E+11 | 22881.13 | 28-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148413E+11 | 27639.63 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216507E+12 | |||||||
Minimum of Months | 0.101923E+11 | 22880.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282919E+11 | 27639.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.192813E+10 | 7056.07 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224897E+10 | 7055.71 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158840E+10 | 7058.44 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123810E+10 | 7055.70 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129085E+09 | 4441.41 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4632529.79 | 3687.48 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4874960.43 | 3993.25 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6329153.34 | 4310.93 | 02-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61714712.08 | 6868.89 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118169E+10 | 7057.22 | 23-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158757E+10 | 7057.46 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317768E+10 | 7053.45 | 19-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131572E+11 | |||||||
Minimum of Months | 4632529.79 | 3687.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317768E+10 | 7058.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288941E+10 | 7042.46 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296054E+10 | 7040.82 | 08-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186514E+10 | 7043.37 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134454E+10 | 7040.55 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141370E+09 | 4635.43 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4279154.22 | 3530.09 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4888562.79 | 3943.32 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6970828.24 | 4253.03 | 02-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80213730.48 | 6873.87 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139920E+10 | 7042.08 | 23-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222247E+10 | 7042.36 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419498E+10 | 7040.51 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171140E+11 | |||||||
Minimum of Months | 4279154.22 | 3530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419498E+10 | 7043.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.986412E+09 | 18202.87 | 06-JAN-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250954E+10 | 18495.46 | 07-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335225E+09 | 8096.24 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134236E+09 | 6733.39 | 17-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992760E+09 | 14339.13 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967286E+09 | 17098.65 | 30-NOV-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572696E+10 | 30845.24 | 22-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116524E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.572696E+10 | 30845.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.944756E+10 | 40107.49 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107783E+11 | 39991.33 | 12-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410055E+10 | 39688.79 | 04-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207154E+10 | 39029.48 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98496736.42 | 33409.06 | 27-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31648276.82 | 26373.57 | 27-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29295035.73 | 32367.98 | 10-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36248349.99 | 30594.61 | 11-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103963E+09 | 31970.04 | 30-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284080E+10 | 40108.71 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580555E+10 | 40105.91 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161671E+11 | 40100.23 | 22-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515111E+11 | |||||||
Minimum of Months | 29295035.73 | 26373.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161671E+11 | 40108.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201895E+10 | 6785.54 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236258E+10 | 6783.85 | 08-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156813E+10 | 6786.46 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121640E+10 | 6783.57 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122525E+09 | 3995.41 | 02-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 672451.29 | 2155.95 | 17-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1253140.81 | 1430.08 | 28-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1055234.75 | 2451.87 | 15-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54487514.03 | 5400.07 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122100E+10 | 6785.15 | 23-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168716E+10 | 6785.44 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325551E+10 | 6782.87 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135097E+11 | |||||||
Minimum of Months | 672451.29 | 1430.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.325551E+10 | 6786.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300254E+10 | 6779.76 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307221E+10 | 6778.04 | 08-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183094E+10 | 6780.72 | 20-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132319E+10 | 6778.44 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135372E+09 | 3900.89 | 08-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 737263.15 | 2001.99 | 17-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1324748.50 | 1508.03 | 28-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1384701.73 | 2430.58 | 15-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71061430.57 | 6273.09 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144453E+10 | 6779.37 | 23-OCT-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238330E+10 | 6779.64 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427387E+10 | 6777.91 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175405E+11 | |||||||
Minimum of Months | 737263.15 | 1508.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427387E+10 | 6780.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121043E+11 | 9371.34 | 06-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120890E+11 | 9371.71 | 08-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120673E+11 | 9374.03 | 20-MAR-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124392E+11 | 9371.72 | 03-APR-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.919720E+10 | 7238.22 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683588E+10 | 5678.27 | 22-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.721478E+10 | 6074.17 | 29-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.735845E+10 | 6277.98 | 01-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695973E+10 | 7237.79 | 22-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101391E+11 | 9371.85 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111825E+11 | 9372.85 | 01-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149876E+11 | 9370.41 | 25-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122575E+12 | |||||||
Minimum of Months | 0.683588E+10 | 5678.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149876E+11 | 9374.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.751718E+09 | 2152.39 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835252E+09 | 2151.86 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.605655E+09 | 2152.69 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.479041E+09 | 2151.81 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60135176.92 | 1806.18 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1027204.38 | 942.69 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1021002.53 | 1013.65 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1563567.90 | 1049.42 | 24-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26664850.68 | 2123.15 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460814E+09 | 2152.11 | 24-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617191E+09 | 2152.35 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115759E+10 | 2151.55 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499768E+10 | |||||||
Minimum of Months | 1021002.53 | 942.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115759E+10 | 2152.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108677E+10 | 2149.38 | 11-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107062E+10 | 2148.71 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.701620E+09 | 2149.56 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516025E+09 | 2148.68 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65283135.32 | 1726.72 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 923106.20 | 962.73 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1001566.66 | 983.05 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1716750.12 | 1038.56 | 24-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33778532.10 | 2126.03 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.541335E+09 | 2149.18 | 24-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.844986E+09 | 2149.22 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149355E+10 | 2148.91 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.635761E+10 | |||||||
Minimum of Months | 923106.20 | 962.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149355E+10 | 2149.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188653E+10 | 9591.89 | 04-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259458E+10 | 9594.54 | 04-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202140E+10 | 9597.77 | 24-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165678E+10 | 9594.25 | 02-APR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155819E+09 | 5627.98 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6645125.59 | 5450.42 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5082075.00 | 3744.33 | 24-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4670128.76 | 3453.62 | 05-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60525558.38 | 8373.53 | 22-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148321E+10 | 9596.71 | 24-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164155E+10 | 9597.47 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339267E+10 | 9589.67 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149095E+11 | |||||||
Minimum of Months | 4670128.76 | 3453.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.339267E+10 | 9597.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414095E+10 | 8915.68 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348989E+10 | 7875.58 | 26-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380805E+10 | 8744.66 | 14-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341185E+10 | 8336.24 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.480723E+10 | 8480.57 | 04-MAY-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.641353E+10 | 8101.08 | 05-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.703344E+10 | 9010.38 | 28-JUL-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.698567E+10 | 9254.57 | 27-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.690036E+10 | 9171.10 | 19-SEP-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433999E+10 | 8921.54 | 11-OCT-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380738E+10 | 9322.26 | 05-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516068E+10 | 9983.61 | 01-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602990E+11 | |||||||
Minimum of Months | 0.341185E+10 | 7875.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.703344E+10 | 9983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352546E+10 | 8788.50 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290574E+10 | 7739.59 | 26-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322493E+10 | 8393.75 | 14-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.284414E+10 | 8185.45 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.436466E+10 | 8082.54 | 07-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616616E+10 | 7864.34 | 19-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.683129E+10 | 8893.41 | 28-JUL-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.676187E+10 | 9257.15 | 27-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664981E+10 | 8983.66 | 19-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383278E+10 | 8794.20 | 11-OCT-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327124E+10 | 9333.57 | 05-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448493E+10 | 9987.39 | 01-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548630E+11 | |||||||
Minimum of Months | 0.284414E+10 | 7739.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.683129E+10 | 9987.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182277E+10 | 5864.33 | 05-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173329E+10 | 5988.12 | 12-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159272E+10 | 5395.98 | 19-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145626E+10 | 5176.77 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148760E+10 | 6341.91 | 11-MAY-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355413E+10 | 9367.06 | 14-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.422050E+10 | 9369.07 | 17-JUL-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400088E+10 | 9367.83 | 03-AUG-01:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287436E+10 | 9343.24 | 13-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147924E+10 | 5324.32 | 31-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166720E+10 | 5800.79 | 30-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206860E+10 | 6851.69 | 22-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279575E+11 | |||||||
Minimum of Months | 0.145626E+10 | 5176.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422050E+10 | 9369.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104135E+11 | 7039.59 | 06-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.980774E+10 | 7039.89 | 08-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.950156E+10 | 7039.23 | 19-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.916155E+10 | 7039.74 | 03-APR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.691470E+10 | 5064.14 | 03-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528588E+10 | 4149.97 | 30-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.574622E+10 | 4210.40 | 26-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.583390E+10 | 4358.19 | 01-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.621498E+10 | 5378.56 | 22-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.847666E+10 | 7039.82 | 31-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.929660E+10 | 7039.42 | 29-NOV-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119269E+11 | 7039.06 | 10-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.985803E+11 | |||||||
Minimum of Months | 0.528588E+10 | 4149.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119269E+11 | 7039.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.381352E+11 | 163563.73 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371687E+11 | 172469.72 | 12-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150693E+11 | 135520.46 | 19-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.524243E+10 | 63474.94 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416697E+09 | 16751.58 | 21-MAY-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24546468.95 | 15982.90 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29677972.80 | 16219.85 | 05-JUL-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36868963.98 | 16332.50 | 12-AUG-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337430E+09 | 18718.52 | 30-SEP-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127126E+11 | 84876.74 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165834E+11 | 117212.66 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797922E+11 | 198180.13 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205549E+12 | |||||||
Minimum of Months | 24546468.95 | 15982.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.797922E+11 | 198180.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.481087E+11 | 25315.53 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450771E+11 | 25582.31 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388507E+11 | 24395.81 | 19-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356866E+11 | 22274.31 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148001E+11 | 20240.78 | 03-MAY-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727046E+09 | 15890.72 | 09-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.582751E+09 | 10983.68 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563369E+09 | 6996.23 | 23-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521359E+10 | 20447.75 | 22-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330779E+11 | 22840.92 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428489E+11 | 24231.58 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491377E+11 | 26372.61 | 22-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314675E+12 | |||||||
Minimum of Months | 0.563369E+09 | 6996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491377E+11 | 26372.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134985E+10 | 0.134616E+10 | 21629.10 | 10-JAN-16:01 | 21629.10 | 0.00 |
February | 0.00 | 0.00 | 0.136334E+10 | 0.136168E+10 | 21604.42 | 23-FEB-16:01 | 21604.42 | 0.00 |
March | 0.00 | 0.00 | 0.247013E+10 | 0.246700E+10 | 21619.37 | 25-MAR-18:01 | 21619.37 | 0.00 |
April | 0.00 | 0.00 | 0.175860E+10 | 0.163022E+10 | 21630.12 | 26-APR-15:01 | 21630.12 | 0.07 |
May | 0.00 | 0.00 | 0.391587E+10 | 0.305291E+10 | 21627.70 | 27-MAY-18:01 | 21627.70 | 0.31 |
June | 0.00 | 0.00 | 0.825506E+10 | 0.606944E+10 | 22134.80 | 18-JUN-08:62 | 17467.13 | 0.55 |
July | 0.00 | 0.00 | 0.799495E+10 | 0.541698E+10 | 22552.86 | 27-JUL-18:01 | 17775.92 | 0.61 |
August | 0.00 | 0.00 | 0.793032E+10 | 0.538732E+10 | 22013.06 | 05-AUG-08:61 | 17911.07 | 0.61 |
September | 0.00 | 0.00 | 0.627977E+10 | 0.521283E+10 | 21632.29 | 14-SEP-15:01 | 21632.29 | 0.31 |
October | 0.00 | 0.00 | 0.329171E+10 | 0.320361E+10 | 21639.76 | 03-OCT-15:01 | 21639.76 | 0.04 |
November | 0.00 | 0.00 | 0.182444E+10 | 0.181053E+10 | 21617.13 | 12-NOV-16:01 | 21617.13 | 0.01 |
December | 0.00 | 0.00 | 0.964346E+09 | 0.964346E+09 | 21583.96 | 29-DEC-16:01 | 21583.96 | 0.00 |
Annual Sum or Average | 0.473984E+11 | 0.379230E+11 | 0.21 | |||||
Minimum of Months | 0.00 | 0.00 | 0.964346E+09 | 0.964346E+09 | 21583.96 | 17467.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.825506E+10 | 0.606944E+10 | 22552.86 | 21639.76 | 0.61 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.284285E+09 | 0.284285E+09 | 21386.10 | 22-JAN-16:01 | 21386.10 | 0.00 |
February | 0.00 | 0.00 | 0.421459E+09 | 0.421270E+09 | 21386.17 | 23-FEB-16:01 | 21386.17 | 0.00 |
March | 0.00 | 0.00 | 0.141956E+10 | 0.141895E+10 | 21401.43 | 25-MAR-18:01 | 21401.43 | 0.00 |
April | 0.00 | 0.00 | 0.135255E+10 | 0.124409E+10 | 21412.42 | 26-APR-15:01 | 21412.42 | 0.06 |
May | 0.00 | 0.00 | 0.366306E+10 | 0.283000E+10 | 21409.79 | 27-MAY-18:01 | 21409.79 | 0.30 |
June | 0.00 | 0.00 | 0.812202E+10 | 0.596728E+10 | 21881.81 | 18-JUN-08:62 | 17356.18 | 0.54 |
July | 0.00 | 0.00 | 0.777615E+10 | 0.526212E+10 | 22280.50 | 27-JUL-18:01 | 17619.43 | 0.60 |
August | 0.00 | 0.00 | 0.722382E+10 | 0.485959E+10 | 21743.72 | 05-AUG-08:61 | 17739.50 | 0.59 |
September | 0.00 | 0.00 | 0.495653E+10 | 0.401186E+10 | 21414.59 | 14-SEP-15:01 | 21414.59 | 0.30 |
October | 0.00 | 0.00 | 0.176302E+10 | 0.171433E+10 | 21420.60 | 03-OCT-15:01 | 21420.60 | 0.02 |
November | 0.00 | 0.00 | 0.481408E+09 | 0.474340E+09 | 21397.30 | 14-NOV-16:01 | 21397.30 | 0.00 |
December | 0.00 | 0.00 | 0.153110E+09 | 0.153110E+09 | 21355.91 | 03-DEC-16:01 | 21355.91 | 0.00 |
Annual Sum or Average | 0.376170E+11 | 0.286412E+11 | 0.20 | |||||
Minimum of Months | 0.00 | 0.00 | 0.153110E+09 | 0.153110E+09 | 21355.91 | 17356.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.812202E+10 | 0.596728E+10 | 22280.50 | 21420.60 | 0.60 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.372402E+11 | 0.372402E+11 | 78220.25 | 20-JAN-12:30 | 78220.25 | 0.00 |
February | 0.00 | 0.00 | 0.257669E+11 | 0.257669E+11 | 72472.98 | 18-FEB-12:40 | 72472.98 | 0.00 |
March | 0.00 | 0.00 | 0.248884E+11 | 0.248884E+11 | 64369.41 | 11-MAR-12:50 | 64369.41 | 0.00 |
April | 0.00 | 0.00 | 0.101931E+11 | 0.985003E+10 | 37729.94 | 08-APR-12:40 | 37729.94 | 0.02 |
May | 0.00 | 0.00 | 0.236529E+11 | 0.203970E+11 | 28991.28 | 18-MAY-17:04 | 19895.58 | 0.16 |
June | 0.00 | 0.00 | 0.407663E+11 | 0.310796E+11 | 39033.14 | 30-JUN-20:20 | 39033.14 | 0.43 |
July | 0.00 | 0.00 | 0.451325E+11 | 0.340253E+11 | 43433.04 | 02-JUL-18:40 | 43433.04 | 0.43 |
August | 0.00 | 0.00 | 0.471382E+11 | 0.348939E+11 | 48089.18 | 02-AUG-18:05 | 37029.30 | 0.53 |
September | 0.00 | 0.00 | 0.495724E+11 | 0.460413E+11 | 62575.63 | 28-SEP-12:30 | 62575.63 | 0.18 |
October | 0.00 | 0.00 | 0.413815E+11 | 0.413729E+11 | 67236.83 | 10-OCT-12:30 | 67236.83 | 0.00 |
November | 0.00 | 0.00 | 0.378198E+11 | 0.378198E+11 | 75652.76 | 07-NOV-11:53 | 75652.76 | 0.00 |
December | 0.00 | 0.00 | 0.267182E+11 | 0.267182E+11 | 75654.07 | 17-DEC-12:10 | 75654.07 | 0.00 |
Annual Sum or Average | 0.410270E+12 | 0.370093E+12 | 0.15 | |||||
Minimum of Months | 0.00 | 0.00 | 0.101931E+11 | 0.985003E+10 | 28991.28 | 19895.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.495724E+11 | 0.460413E+11 | 78220.25 | 78220.25 | 0.53 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.738979E+10 | 0.738979E+10 | 117243.82 | 21-JAN-09:01 | 117243.82 | 0.00 |
February | 0.00 | 0.00 | 0.601203E+10 | 0.601203E+10 | 117046.40 | 19-FEB-09:01 | 117046.40 | 0.00 |
March | 0.00 | 0.00 | 0.166268E+11 | 0.164999E+11 | 118978.80 | 16-MAR-18:01 | 118978.80 | 0.01 |
April | 0.00 | 0.00 | 0.211975E+11 | 0.190335E+11 | 119294.65 | 08-APR-18:01 | 119294.65 | 0.11 |
May | 0.00 | 0.00 | 0.461356E+11 | 0.388960E+11 | 121833.80 | 25-MAY-18:01 | 121833.80 | 0.29 |
June | 0.00 | 0.00 | 0.693569E+11 | 0.550159E+11 | 123032.40 | 18-JUN-08:62 | 99508.17 | 0.46 |
July | 0.00 | 0.00 | 0.737941E+11 | 0.565498E+11 | 130213.35 | 31-JUL-18:01 | 97613.73 | 0.52 |
August | 0.00 | 0.00 | 0.663342E+11 | 0.492843E+11 | 121873.85 | 21-AUG-15:01 | 121873.85 | 0.51 |
September | 0.00 | 0.00 | 0.496594E+11 | 0.433945E+11 | 121862.21 | 11-SEP-18:01 | 121862.21 | 0.25 |
October | 0.00 | 0.00 | 0.226608E+11 | 0.214197E+11 | 120010.66 | 01-OCT-18:01 | 120010.66 | 0.07 |
November | 0.00 | 0.00 | 0.106588E+11 | 0.103732E+11 | 117581.34 | 09-NOV-19:01 | 117581.34 | 0.01 |
December | 0.00 | 0.00 | 0.590463E+10 | 0.590463E+10 | 116017.24 | 03-DEC-09:01 | 116017.24 | 0.00 |
Annual Sum or Average | 0.395731E+12 | 0.329773E+12 | 0.19 | |||||
Minimum of Months | 0.00 | 0.00 | 0.590463E+10 | 0.590463E+10 | 116017.24 | 97613.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.737941E+11 | 0.565498E+11 | 130213.35 | 121873.85 | 0.52 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128635E+10 | 0.128466E+10 | 18931.49 | 19-JAN-09:01 | 18931.49 | 0.00 |
February | 0.00 | 0.00 | 0.147052E+10 | 0.146996E+10 | 18928.66 | 23-FEB-09:01 | 18928.66 | 0.00 |
March | 0.00 | 0.00 | 0.257415E+10 | 0.256518E+10 | 18918.21 | 31-MAR-08:61 | 18918.21 | 0.01 |
April | 0.00 | 0.00 | 0.207478E+10 | 0.191424E+10 | 18927.69 | 09-APR-08:62 | 18927.69 | 0.08 |
May | 0.00 | 0.00 | 0.430487E+10 | 0.341808E+10 | 18942.07 | 18-MAY-08:61 | 18942.07 | 0.32 |
June | 0.00 | 0.00 | 0.876288E+10 | 0.650467E+10 | 18938.99 | 29-JUN-18:01 | 18938.99 | 0.59 |
July | 0.00 | 0.00 | 0.899762E+10 | 0.639088E+10 | 20014.56 | 31-JUL-18:01 | 15430.17 | 0.64 |
August | 0.00 | 0.00 | 0.880613E+10 | 0.608756E+10 | 18939.82 | 23-AUG-18:01 | 18939.82 | 0.65 |
September | 0.00 | 0.00 | 0.663218E+10 | 0.557126E+10 | 18938.85 | 12-SEP-18:01 | 18938.85 | 0.32 |
October | 0.00 | 0.00 | 0.315590E+10 | 0.306633E+10 | 18942.57 | 03-OCT-15:01 | 18942.57 | 0.04 |
November | 0.00 | 0.00 | 0.170373E+10 | 0.168883E+10 | 18939.39 | 19-NOV-09:01 | 18939.39 | 0.01 |
December | 0.00 | 0.00 | 0.947382E+09 | 0.947382E+09 | 18908.64 | 02-DEC-09:01 | 18908.64 | 0.00 |
Annual Sum or Average | 0.507165E+11 | 0.409090E+11 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 0.947382E+09 | 0.947382E+09 | 18908.64 | 15430.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.899762E+10 | 0.650467E+10 | 20014.56 | 18942.57 | 0.65 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.245696E+09 | 0.245696E+09 | 18804.84 | 20-JAN-09:01 | 18804.84 | 0.00 |
February | 0.00 | 0.00 | 0.509370E+09 | 0.509370E+09 | 18833.01 | 23-FEB-09:01 | 18833.01 | 0.00 |
March | 0.00 | 0.00 | 0.146217E+10 | 0.145527E+10 | 18822.52 | 31-MAR-08:61 | 18822.52 | 0.00 |
April | 0.00 | 0.00 | 0.163267E+10 | 0.148978E+10 | 18831.98 | 09-APR-08:62 | 18831.98 | 0.07 |
May | 0.00 | 0.00 | 0.403487E+10 | 0.318039E+10 | 18845.14 | 18-MAY-08:61 | 18845.14 | 0.31 |
June | 0.00 | 0.00 | 0.861646E+10 | 0.640535E+10 | 18856.70 | 20-JUN-18:01 | 15899.92 | 0.58 |
July | 0.00 | 0.00 | 0.876704E+10 | 0.621668E+10 | 19984.57 | 31-JUL-18:01 | 15314.21 | 0.64 |
August | 0.00 | 0.00 | 0.808706E+10 | 0.551788E+10 | 18843.89 | 23-AUG-18:01 | 18843.89 | 0.65 |
September | 0.00 | 0.00 | 0.525450E+10 | 0.431332E+10 | 18842.81 | 12-SEP-18:01 | 18842.81 | 0.31 |
October | 0.00 | 0.00 | 0.155358E+10 | 0.150195E+10 | 18845.89 | 04-OCT-08:61 | 18845.89 | 0.03 |
November | 0.00 | 0.00 | 0.461549E+09 | 0.454408E+09 | 18844.60 | 19-NOV-09:01 | 18844.60 | 0.00 |
December | 0.00 | 0.00 | 0.149486E+09 | 0.149486E+09 | 18748.99 | 02-DEC-09:01 | 18748.99 | 0.00 |
Annual Sum or Average | 0.407744E+11 | 0.314396E+11 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 0.149486E+09 | 0.149486E+09 | 18748.99 | 15314.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.876704E+10 | 0.640535E+10 | 19984.57 | 18845.89 | 0.65 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.341589E+09 | 0.341452E+09 | 5845.15 | 10-JAN-16:01 | 5845.15 | 0.00 |
February | 0.00 | 0.00 | 0.363850E+09 | 0.363610E+09 | 5838.18 | 23-FEB-16:01 | 5838.18 | 0.00 |
March | 0.00 | 0.00 | 0.696577E+09 | 0.696440E+09 | 5842.55 | 25-MAR-18:01 | 5842.55 | 0.00 |
April | 0.00 | 0.00 | 0.510418E+09 | 0.478301E+09 | 5845.41 | 26-APR-15:01 | 5845.41 | 0.06 |
May | 0.00 | 0.00 | 0.118186E+10 | 0.950132E+09 | 5847.90 | 25-MAY-18:01 | 5847.90 | 0.31 |
June | 0.00 | 0.00 | 0.256269E+10 | 0.193485E+10 | 6135.90 | 18-JUN-08:62 | 4693.90 | 0.56 |
July | 0.00 | 0.00 | 0.248261E+10 | 0.174011E+10 | 6213.89 | 30-JUL-08:61 | 4739.42 | 0.63 |
August | 0.00 | 0.00 | 0.246290E+10 | 0.174372E+10 | 6054.87 | 05-AUG-08:61 | 4825.93 | 0.62 |
September | 0.00 | 0.00 | 0.187099E+10 | 0.157527E+10 | 5845.95 | 12-SEP-18:01 | 5845.95 | 0.32 |
October | 0.00 | 0.00 | 0.924313E+09 | 0.899379E+09 | 5847.97 | 03-OCT-15:01 | 5847.97 | 0.04 |
November | 0.00 | 0.00 | 0.481029E+09 | 0.477756E+09 | 5842.02 | 12-NOV-16:01 | 5842.02 | 0.01 |
December | 0.00 | 0.00 | 0.234928E+09 | 0.234928E+09 | 5832.84 | 29-DEC-16:01 | 5832.84 | 0.00 |
Annual Sum or Average | 0.141138E+11 | 0.114360E+11 | 0.21 | |||||
Minimum of Months | 0.00 | 0.00 | 0.234928E+09 | 0.234928E+09 | 5832.84 | 4693.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.256269E+10 | 0.193485E+10 | 6213.89 | 5847.97 | 0.63 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 69390885.61 | 69342847.36 | 5782.42 | 22-JAN-16:01 | 5782.42 | 0.00 |
February | 0.00 | 0.00 | 0.110933E+09 | 0.110933E+09 | 5782.52 | 23-FEB-16:01 | 5782.52 | 0.00 |
March | 0.00 | 0.00 | 0.407454E+09 | 0.407396E+09 | 5786.62 | 25-MAR-18:01 | 5786.62 | 0.00 |
April | 0.00 | 0.00 | 0.392364E+09 | 0.365097E+09 | 5789.51 | 26-APR-15:01 | 5789.51 | 0.05 |
May | 0.00 | 0.00 | 0.110956E+10 | 0.887184E+09 | 5788.75 | 27-MAY-18:01 | 5788.75 | 0.30 |
June | 0.00 | 0.00 | 0.252825E+10 | 0.190796E+10 | 6070.54 | 18-JUN-08:62 | 4666.21 | 0.57 |
July | 0.00 | 0.00 | 0.242569E+10 | 0.169709E+10 | 6146.19 | 30-JUL-08:61 | 4697.50 | 0.63 |
August | 0.00 | 0.00 | 0.227127E+10 | 0.159127E+10 | 5986.59 | 05-AUG-08:61 | 4785.28 | 0.61 |
September | 0.00 | 0.00 | 0.150789E+10 | 0.124458E+10 | 5790.02 | 14-SEP-15:01 | 5790.02 | 0.31 |
October | 0.00 | 0.00 | 0.498763E+09 | 0.486247E+09 | 5791.86 | 03-OCT-15:01 | 5791.86 | 0.02 |
November | 0.00 | 0.00 | 0.130336E+09 | 0.128864E+09 | 5785.56 | 14-NOV-16:01 | 5785.56 | 0.00 |
December | 0.00 | 0.00 | 35895650.62 | 35895650.62 | 5774.33 | 03-DEC-16:01 | 5774.33 | 0.00 |
Annual Sum or Average | 0.114878E+11 | 0.893186E+10 | 0.21 | |||||
Minimum of Months | 0.00 | 0.00 | 35895650.62 | 35895650.62 | 5774.33 | 4666.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.252825E+10 | 0.190796E+10 | 6146.19 | 5791.86 | 0.63 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.798786E+10 | 0.796999E+10 | 22210.12 | 10-JAN-16:01 | 22210.12 | 0.01 |
February | 0.00 | 0.00 | 0.608189E+10 | 0.605552E+10 | 22200.44 | 25-FEB-09:01 | 22200.44 | 0.01 |
March | 0.00 | 0.00 | 0.600038E+10 | 0.597454E+10 | 22195.90 | 25-MAR-15:01 | 22195.90 | 0.01 |
April | 0.00 | 0.00 | 0.314313E+10 | 0.287699E+10 | 22213.58 | 26-APR-15:01 | 22213.58 | 0.10 |
May | 0.00 | 0.00 | 0.608747E+10 | 0.489981E+10 | 22207.87 | 25-MAY-15:01 | 22207.87 | 0.34 |
June | 0.00 | 0.00 | 0.115027E+11 | 0.866410E+10 | 22878.16 | 18-JUN-08:62 | 17843.27 | 0.56 |
July | 0.00 | 0.00 | 0.125202E+11 | 0.908584E+10 | 24220.17 | 31-JUL-18:01 | 17822.68 | 0.62 |
August | 0.00 | 0.00 | 0.129347E+11 | 0.947983E+10 | 22356.40 | 29-AUG-18:01 | 18129.18 | 0.63 |
September | 0.00 | 0.00 | 0.120254E+11 | 0.106445E+11 | 22213.83 | 14-SEP-15:01 | 22213.83 | 0.33 |
October | 0.00 | 0.00 | 0.882915E+10 | 0.860218E+10 | 22202.49 | 01-OCT-18:01 | 22202.49 | 0.08 |
November | 0.00 | 0.00 | 0.827121E+10 | 0.821274E+10 | 22213.00 | 19-NOV-09:01 | 22213.00 | 0.02 |
December | 0.00 | 0.00 | 0.610088E+10 | 0.610088E+10 | 22182.31 | 30-DEC-16:01 | 22182.31 | 0.00 |
Annual Sum or Average | 0.101485E+12 | 0.885670E+11 | 0.23 | |||||
Minimum of Months | 0.00 | 0.00 | 0.314313E+10 | 0.287699E+10 | 22182.31 | 17822.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129347E+11 | 0.106445E+11 | 24220.17 | 22213.83 | 0.63 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177937E+11 | 0.177937E+11 | 267813.14 | 20-JAN-14:00 | 267813.14 | 0.00 |
February | 0.00 | 0.00 | 0.982622E+10 | 0.982622E+10 | 236080.35 | 18-FEB-14:00 | 236080.35 | 0.00 |
March | 0.00 | 0.00 | 0.516207E+11 | 0.516207E+11 | 291508.01 | 14-MAR-13:00 | 291508.01 | 0.00 |
April | 0.00 | 0.00 | 0.608423E+11 | 0.608423E+11 | 274383.92 | 20-APR-13:00 | 274383.92 | 0.01 |
May | 0.00 | 0.00 | 0.229532E+12 | 0.229532E+12 | 329989.66 | 17-MAY-13:00 | 329989.66 | 0.12 |
June | 0.00 | 0.00 | 0.631884E+12 | 0.598189E+12 | 484627.87 | 18-JUN-08:50 | 268107.74 | 0.46 |
July | 0.00 | 0.00 | 0.742446E+12 | 0.657403E+12 | 559495.75 | 28-JUL-17:00 | 240465.42 | 0.47 |
August | 0.00 | 0.00 | 0.662058E+12 | 0.609320E+12 | 560760.60 | 05-AUG-15:00 | 240506.85 | 0.55 |
September | 0.00 | 0.00 | 0.449365E+12 | 0.449081E+12 | 362312.83 | 09-SEP-13:00 | 362312.83 | 0.17 |
October | 0.00 | 0.00 | 0.897172E+11 | 0.897172E+11 | 316830.31 | 11-OCT-14:00 | 316830.31 | 0.00 |
November | 0.00 | 0.00 | 0.318983E+11 | 0.318983E+11 | 278396.71 | 07-NOV-13:55 | 278396.71 | 0.00 |
December | 0.00 | 0.00 | 0.230866E+11 | 0.230866E+11 | 277347.50 | 01-DEC-14:00 | 277347.50 | 0.00 |
Annual Sum or Average | 0.300007E+13 | 0.282831E+13 | 0.15 | |||||
Minimum of Months | 0.00 | 0.00 | 0.982622E+10 | 0.982622E+10 | 236080.35 | 236080.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.742446E+12 | 0.657403E+12 | 560760.60 | 362312.83 | 0.55 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.806315E+09 | 0.806315E+09 | 18767.96 | 20-JAN-14:00 | 18767.96 | 0.00 |
February | 0.00 | 0.00 | 0.433304E+09 | 0.433304E+09 | 15782.69 | 18-FEB-14:00 | 15782.69 | 0.00 |
March | 0.00 | 0.00 | 0.272107E+10 | 0.272107E+10 | 24819.62 | 14-MAR-13:00 | 24819.62 | 0.00 |
April | 0.00 | 0.00 | 0.323793E+10 | 0.323793E+10 | 20848.64 | 20-APR-13:00 | 20848.64 | 0.01 |
May | 0.00 | 0.00 | 0.153487E+11 | 0.153487E+11 | 35043.29 | 17-MAY-13:00 | 35043.29 | 0.07 |
June | 0.00 | 0.00 | 0.524485E+11 | 0.511615E+11 | 56144.72 | 26-JUN-15:00 | 56144.72 | 0.40 |
July | 0.00 | 0.00 | 0.610428E+11 | 0.566776E+11 | 52970.15 | 30-JUL-14:00 | 35663.82 | 0.44 |
August | 0.00 | 0.00 | 0.522589E+11 | 0.503634E+11 | 51453.17 | 16-AUG-14:00 | 51453.17 | 0.50 |
September | 0.00 | 0.00 | 0.348520E+11 | 0.348520E+11 | 42552.60 | 10-SEP-13:00 | 42552.60 | 0.13 |
October | 0.00 | 0.00 | 0.528180E+10 | 0.528180E+10 | 30910.17 | 11-OCT-14:00 | 30910.17 | 0.00 |
November | 0.00 | 0.00 | 0.173877E+10 | 0.173877E+10 | 20786.14 | 07-NOV-15:00 | 20786.14 | 0.00 |
December | 0.00 | 0.00 | 0.121687E+10 | 0.121687E+10 | 20807.49 | 02-DEC-15:00 | 20807.49 | 0.00 |
Annual Sum or Average | 0.231387E+12 | 0.223839E+12 | 0.13 | |||||
Minimum of Months | 0.00 | 0.00 | 0.433304E+09 | 0.433304E+09 | 15782.69 | 15782.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.610428E+11 | 0.566776E+11 | 56144.72 | 56144.72 | 0.50 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28851.45 | 59585.97 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 29169.20 | 59863.24 | 13-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 28752.62 | 59551.11 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27589.06 | 57662.97 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25900.22 | 55046.07 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24118.83 | 51831.95 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22808.01 | 49007.46 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 22390.85 | 47649.80 | 01-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22922.26 | 49191.16 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 24249.55 | 52085.20 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25997.31 | 55241.81 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27632.16 | 57920.92 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 25845.73 | ||||
Minimum of Months | 0.00 | 0.00 | 22390.85 | 47649.80 | ||
Maximum of Months | 0.00 | 0.00 | 29169.20 | 59863.24 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 68869.89 | 339718.33 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 75891.47 | 297733.29 | 12-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 57266.91 | 276066.40 | 19-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53472.05 | 204745.04 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 42455.76 | 107280.39 | 04-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44909.19 | 113807.38 | 13-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 46415.80 | 131703.97 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 43834.97 | 121849.76 | 11-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39863.22 | 144411.52 | 18-SEP-08:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 48286.09 | 251097.45 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54878.10 | 243263.85 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 95472.08 | 384873.80 | 21-DEC-09:06 |
Annual Sum or Average | 0.00 | 55888.45 | ||||
Minimum of Months | 0.00 | 0.00 | 39863.22 | 107280.39 | ||
Maximum of Months | 0.00 | 0.00 | 95472.08 | 384873.80 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 30163.57 | 449544.46 | 23-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 23549.71 | 390622.82 | 18-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 43969.07 | 558902.49 | 13-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 43716.78 | 499395.84 | 27-APR-15:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131194.23 | 572558.06 | 16-MAY-15:01 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 332294.45 | 711987.66 | 26-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369938.83 | 793077.22 | 31-JUL-18:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 334076.11 | 795104.44 | 05-AUG-15:01 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 245674.27 | 649768.29 | 28-SEP-15:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 70095.91 | 599214.70 | 11-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 39306.36 | 537618.20 | 05-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26264.52 | 381476.22 | 02-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 141550.46 | 0.00 | ||||
Minimum of Months | 23549.71 | 381476.22 | 0.00 | 0.00 | ||
Maximum of Months | 369938.83 | 795104.44 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587767E+10 | 1.08 | 2194.47 | 05-JAN-02:70 | 1.09 |
February | 0.530887E+10 | 1.08 | 2194.47 | 02-FEB-16:03 | 1.09 |
March | 0.587767E+10 | 1.08 | 2194.47 | 06-MAR-16:03 | 1.09 |
April | 0.568807E+10 | 1.08 | 2194.47 | 07-APR-08:62 | 1.08 |
May | 0.587767E+10 | 1.08 | 2194.47 | 01-MAY-15:02 | 1.09 |
June | 0.568807E+10 | 1.08 | 2194.47 | 01-JUN-08:62 | 1.07 |
July | 0.587767E+10 | 1.07 | 2194.47 | 01-JUL-08:61 | 1.08 |
August | 0.587767E+10 | 1.07 | 2194.47 | 01-AUG-15:30 | 1.08 |
September | 0.568807E+10 | 1.08 | 2194.47 | 01-SEP-15:15 | 1.07 |
October | 0.587767E+10 | 1.08 | 2194.47 | 01-OCT-08:62 | 1.08 |
November | 0.568807E+10 | 1.08 | 2194.47 | 04-NOV-18:01 | 1.08 |
December | 0.587767E+10 | 1.08 | 2194.47 | 02-DEC-16:01 | 1.08 |
Annual Sum or Average | 0.692049E+11 | 1.08 | |||
Minimum of Months | 0.530887E+10 | 1.07 | 2194.47 | 1.07 | |
Maximum of Months | 0.587767E+10 | 1.08 | 2194.47 | 1.09 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156033E+12 | 2.26 | 58256.02 | 01-JAN-00:05 | 2.26 |
February | 0.140933E+12 | 2.27 | 58256.02 | 01-FEB-00:03 | 2.26 |
March | 0.156033E+12 | 2.27 | 58256.02 | 01-MAR-00:03 | 2.26 |
April | 0.151000E+12 | 2.26 | 58256.02 | 01-APR-00:10 | 2.26 |
May | 0.156033E+12 | 2.26 | 58256.02 | 01-MAY-00:05 | 2.25 |
June | 0.151000E+12 | 2.25 | 58256.02 | 01-JUN-00:10 | 2.25 |
July | 0.156033E+12 | 2.25 | 58256.02 | 01-JUL-00:10 | 2.26 |
August | 0.156033E+12 | 2.25 | 58256.02 | 01-AUG-00:10 | 2.24 |
September | 0.151000E+12 | 2.26 | 58256.02 | 01-SEP-00:10 | 2.25 |
October | 0.156033E+12 | 2.26 | 58256.02 | 01-OCT-00:05 | 2.25 |
November | 0.151000E+12 | 2.26 | 58256.02 | 01-NOV-00:10 | 2.26 |
December | 0.156033E+12 | 2.27 | 58256.02 | 01-DEC-00:03 | 2.26 |
Annual Sum or Average | 0.183716E+13 | 2.26 | |||
Minimum of Months | 0.140933E+12 | 2.25 | 58256.02 | 2.24 | |
Maximum of Months | 0.156033E+12 | 2.27 | 58256.02 | 2.26 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.79 | 184.35 | 01-JAN-00:05 | 0.79 |
February | 0.445990E+09 | 0.79 | 184.35 | 01-FEB-00:03 | 0.79 |
March | 0.493775E+09 | 0.79 | 184.35 | 01-MAR-00:03 | 0.79 |
April | 0.477847E+09 | 0.79 | 184.35 | 01-APR-00:10 | 0.79 |
May | 0.493775E+09 | 0.79 | 184.35 | 01-MAY-00:05 | 0.79 |
June | 0.477847E+09 | 0.79 | 184.35 | 01-JUN-00:10 | 0.78 |
July | 0.493775E+09 | 0.78 | 184.35 | 01-JUL-00:10 | 0.79 |
August | 0.493775E+09 | 0.78 | 184.35 | 01-AUG-00:10 | 0.78 |
September | 0.477847E+09 | 0.79 | 184.35 | 01-SEP-00:10 | 0.79 |
October | 0.493775E+09 | 0.79 | 184.35 | 01-OCT-00:05 | 0.78 |
November | 0.477847E+09 | 0.79 | 184.35 | 01-NOV-00:10 | 0.79 |
December | 0.493775E+09 | 0.79 | 184.35 | 01-DEC-00:03 | 0.79 |
Annual Sum or Average | 0.581380E+10 | 0.79 | |||
Minimum of Months | 0.445990E+09 | 0.78 | 184.35 | 0.78 | |
Maximum of Months | 0.493775E+09 | 0.79 | 184.35 | 0.79 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.56 | 1474.84 | 01-JAN-07:10 | 0.79 |
February | 0.252728E+10 | 0.56 | 1474.84 | 01-FEB-07:10 | 0.79 |
March | 0.279806E+10 | 0.56 | 1474.84 | 01-MAR-07:05 | 0.79 |
April | 0.270780E+10 | 0.56 | 1474.84 | 01-APR-06:10 | 0.79 |
May | 0.279806E+10 | 0.56 | 1474.84 | 01-MAY-06:05 | 0.79 |
June | 0.270780E+10 | 0.55 | 1474.84 | 01-JUN-06:05 | 0.78 |
July | 0.279806E+10 | 0.55 | 1474.84 | 01-JUL-06:10 | 0.79 |
August | 0.279806E+10 | 0.55 | 1474.84 | 01-AUG-06:05 | 0.78 |
September | 0.270780E+10 | 0.56 | 1474.84 | 01-SEP-06:05 | 0.78 |
October | 0.279806E+10 | 0.56 | 1474.84 | 01-OCT-06:10 | 0.79 |
November | 0.270780E+10 | 0.56 | 1474.84 | 01-NOV-06:10 | 0.79 |
December | 0.279806E+10 | 0.56 | 1474.84 | 01-DEC-07:05 | 0.79 |
Annual Sum or Average | 0.329449E+11 | 0.56 | |||
Minimum of Months | 0.252728E+10 | 0.55 | 1474.84 | 0.78 | |
Maximum of Months | 0.279806E+10 | 0.56 | 1474.84 | 0.79 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.710539E+09 | 1.39 | 2458.22 | 01-JAN-16:01 | 1.71 |
February | 0.745500E+09 | 1.41 | 2458.22 | 01-FEB-09:02 | 1.71 |
March | 0.741738E+09 | 1.40 | 2458.22 | 01-MAR-19:01 | 1.71 |
April | 0.589922E+09 | 1.34 | 2458.22 | 02-APR-08:62 | 1.71 |
May | 0.543677E+09 | 1.39 | 2458.22 | 01-MAY-18:01 | 1.71 |
June | 0.958953E+09 | 1.55 | 2458.22 | 01-JUN-15:01 | 1.70 |
July | 0.910975E+09 | 1.56 | 2458.22 | 01-JUL-08:61 | 1.71 |
August | 0.908822E+09 | 1.56 | 2458.22 | 01-AUG-15:01 | 1.71 |
September | 0.777160E+09 | 1.55 | 2458.22 | 01-SEP-15:01 | 1.69 |
October | 0.736210E+09 | 1.48 | 2458.22 | 01-OCT-15:01 | 1.70 |
November | 0.664676E+09 | 1.41 | 2458.22 | 01-NOV-08:62 | 1.71 |
December | 0.101471E+10 | 1.40 | 2458.22 | 01-DEC-16:01 | 1.71 |
Annual Sum or Average | 0.930288E+10 | 1.45 | |||
Minimum of Months | 0.543677E+09 | 1.34 | 2458.22 | 1.69 | |
Maximum of Months | 0.101471E+10 | 1.56 | 2458.22 | 1.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.817069E+09 | 1.28 | 2433.43 | 01-JAN-09:01 | 1.71 |
February | 0.801249E+09 | 1.34 | 2433.43 | 01-FEB-09:02 | 1.71 |
March | 0.687509E+09 | 1.31 | 2433.43 | 01-MAR-09:01 | 1.71 |
April | 0.568568E+09 | 1.28 | 2433.43 | 01-APR-15:02 | 1.71 |
May | 0.517697E+09 | 1.36 | 2433.43 | 01-MAY-18:01 | 1.71 |
June | 0.944958E+09 | 1.55 | 2433.43 | 01-JUN-15:01 | 1.70 |
July | 0.887448E+09 | 1.55 | 2433.43 | 01-JUL-08:61 | 1.71 |
August | 0.835011E+09 | 1.52 | 2433.43 | 01-AUG-15:01 | 1.71 |
September | 0.639119E+09 | 1.45 | 2433.43 | 01-SEP-15:01 | 1.69 |
October | 0.623044E+09 | 1.32 | 2433.43 | 01-OCT-15:01 | 1.70 |
November | 0.676053E+09 | 1.30 | 2433.43 | 01-NOV-08:62 | 1.71 |
December | 0.116902E+10 | 1.35 | 2433.43 | 01-DEC-09:01 | 1.71 |
Annual Sum or Average | 0.916674E+10 | 1.38 | |||
Minimum of Months | 0.517697E+09 | 1.28 | 2433.43 | 1.69 | |
Maximum of Months | 0.116902E+10 | 1.55 | 2433.43 | 1.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.415748E+10 | 0.95 | 8066.01 | 20-JAN-12:30 | 1.71 |
February | 0.333106E+10 | 0.94 | 7531.13 | 18-FEB-12:40 | 1.71 |
March | 0.274733E+10 | 0.80 | 6784.73 | 11-MAR-12:50 | 1.71 |
April | 0.117052E+10 | 0.60 | 3640.70 | 08-APR-12:40 | 1.72 |
May | 0.261587E+10 | 1.25 | 2962.49 | 31-MAY-17:15 | 1.70 |
June | 0.414378E+10 | 1.64 | 3752.82 | 30-JUN-20:20 | 1.71 |
July | 0.448365E+10 | 1.64 | 4146.31 | 02-JUL-18:40 | 1.71 |
August | 0.473034E+10 | 1.64 | 6499.58 | 02-AUG-18:05 | 1.70 |
September | 0.513287E+10 | 1.58 | 6617.32 | 28-SEP-12:30 | 1.71 |
October | 0.459213E+10 | 1.10 | 7047.88 | 10-OCT-12:30 | 1.71 |
November | 0.421112E+10 | 0.98 | 7831.18 | 07-NOV-11:53 | 1.72 |
December | 0.411873E+10 | 0.82 | 7955.03 | 22-DEC-04:00 | 1.72 |
Annual Sum or Average | 0.454349E+11 | 1.16 | |||
Minimum of Months | 0.117052E+10 | 0.60 | 2962.49 | 1.70 | |
Maximum of Months | 0.513287E+10 | 1.64 | 8066.01 | 1.72 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.359342E+10 | 1.22 | 13760.26 | 02-JAN-16:02 | 1.71 |
February | 0.362536E+10 | 1.21 | 13760.26 | 01-FEB-09:02 | 1.71 |
March | 0.326431E+10 | 1.21 | 13760.26 | 02-MAR-09:01 | 1.71 |
April | 0.323480E+10 | 1.21 | 13760.26 | 02-APR-15:02 | 1.71 |
May | 0.538252E+10 | 1.23 | 13760.26 | 01-MAY-15:02 | 1.71 |
June | 0.787460E+10 | 1.38 | 13760.26 | 01-JUN-08:62 | 1.69 |
July | 0.829977E+10 | 1.42 | 13760.26 | 01-JUL-08:61 | 1.71 |
August | 0.735845E+10 | 1.33 | 13760.26 | 01-AUG-15:01 | 1.71 |
September | 0.583052E+10 | 1.27 | 13760.26 | 01-SEP-08:62 | 1.69 |
October | 0.356369E+10 | 1.21 | 13760.26 | 01-OCT-08:62 | 1.70 |
November | 0.304008E+10 | 1.21 | 13760.26 | 01-NOV-08:62 | 1.71 |
December | 0.560364E+10 | 1.27 | 13760.26 | 01-DEC-19:01 | 1.71 |
Annual Sum or Average | 0.606712E+11 | 1.27 | |||
Minimum of Months | 0.304008E+10 | 1.21 | 13760.26 | 1.69 | |
Maximum of Months | 0.829977E+10 | 1.42 | 13760.26 | 1.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.686582E+09 | 1.38 | 2151.80 | 01-JAN-09:01 | 1.71 |
February | 0.727017E+09 | 1.43 | 2151.80 | 01-FEB-09:02 | 1.71 |
March | 0.705658E+09 | 1.43 | 2151.80 | 01-MAR-09:01 | 1.71 |
April | 0.581608E+09 | 1.38 | 2151.80 | 01-APR-15:02 | 1.71 |
May | 0.571509E+09 | 1.47 | 2151.80 | 03-MAY-08:61 | 1.71 |
June | 0.998509E+09 | 1.64 | 2151.80 | 01-JUN-08:62 | 1.69 |
July | 0.101462E+10 | 1.63 | 2151.80 | 01-JUL-08:61 | 1.71 |
August | 0.992484E+09 | 1.64 | 2151.80 | 01-AUG-08:62 | 1.70 |
September | 0.802156E+09 | 1.59 | 2151.80 | 01-SEP-08:62 | 1.69 |
October | 0.694227E+09 | 1.51 | 2151.80 | 01-OCT-08:62 | 1.70 |
November | 0.639130E+09 | 1.41 | 2151.80 | 01-NOV-08:62 | 1.71 |
December | 0.967629E+09 | 1.39 | 2151.80 | 01-DEC-09:01 | 1.71 |
Annual Sum or Average | 0.938113E+10 | 1.49 | |||
Minimum of Months | 0.571509E+09 | 1.38 | 2151.80 | 1.69 | |
Maximum of Months | 0.101462E+10 | 1.64 | 2151.80 | 1.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.772265E+09 | 1.25 | 2140.90 | 01-JAN-16:01 | 1.71 |
February | 0.768689E+09 | 1.33 | 2140.90 | 01-FEB-09:02 | 1.71 |
March | 0.641737E+09 | 1.32 | 2140.90 | 01-MAR-09:01 | 1.71 |
April | 0.556516E+09 | 1.31 | 2140.90 | 01-APR-15:02 | 1.71 |
May | 0.545262E+09 | 1.45 | 2140.90 | 03-MAY-08:61 | 1.71 |
June | 0.983741E+09 | 1.64 | 2140.90 | 01-JUN-08:62 | 1.69 |
July | 0.990947E+09 | 1.63 | 2140.90 | 01-JUL-08:61 | 1.71 |
August | 0.919692E+09 | 1.63 | 2140.90 | 01-AUG-08:62 | 1.70 |
September | 0.660024E+09 | 1.55 | 2140.90 | 01-SEP-08:62 | 1.69 |
October | 0.570048E+09 | 1.33 | 2140.90 | 01-OCT-08:62 | 1.70 |
November | 0.657692E+09 | 1.27 | 2140.90 | 01-NOV-08:62 | 1.71 |
December | 0.110694E+10 | 1.33 | 2140.90 | 02-DEC-09:01 | 1.71 |
Annual Sum or Average | 0.917355E+10 | 1.42 | |||
Minimum of Months | 0.545262E+09 | 1.25 | 2140.90 | 1.69 | |
Maximum of Months | 0.110694E+10 | 1.64 | 2140.90 | 1.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229059E+09 | 1.39 | 664.36 | 01-JAN-16:01 | 1.71 |
February | 0.233700E+09 | 1.43 | 664.36 | 01-FEB-09:02 | 1.71 |
March | 0.230799E+09 | 1.46 | 664.36 | 01-MAR-09:01 | 1.71 |
April | 0.185325E+09 | 1.39 | 664.36 | 01-APR-15:02 | 1.71 |
May | 0.166992E+09 | 1.47 | 664.36 | 01-MAY-18:01 | 1.71 |
June | 0.295642E+09 | 1.60 | 664.36 | 01-JUN-15:01 | 1.70 |
July | 0.280643E+09 | 1.59 | 664.36 | 01-JUL-08:61 | 1.71 |
August | 0.279525E+09 | 1.59 | 664.36 | 01-AUG-15:01 | 1.71 |
September | 0.230052E+09 | 1.57 | 664.36 | 01-SEP-15:01 | 1.70 |
October | 0.225831E+09 | 1.51 | 664.36 | 01-OCT-15:01 | 1.70 |
November | 0.209237E+09 | 1.43 | 664.36 | 01-NOV-08:62 | 1.71 |
December | 0.316508E+09 | 1.42 | 664.36 | 01-DEC-16:01 | 1.71 |
Annual Sum or Average | 0.288331E+10 | 1.49 | |||
Minimum of Months | 0.166992E+09 | 1.39 | 664.36 | 1.70 | |
Maximum of Months | 0.316508E+09 | 1.60 | 664.36 | 1.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264971E+09 | 1.32 | 658.00 | 01-JAN-09:01 | 1.71 |
February | 0.253732E+09 | 1.39 | 658.00 | 01-FEB-09:02 | 1.71 |
March | 0.218120E+09 | 1.37 | 658.00 | 01-MAR-09:01 | 1.71 |
April | 0.179415E+09 | 1.34 | 658.00 | 01-APR-15:02 | 1.71 |
May | 0.160215E+09 | 1.44 | 658.00 | 01-MAY-18:01 | 1.71 |
June | 0.292157E+09 | 1.60 | 658.00 | 01-JUN-15:01 | 1.70 |
July | 0.274712E+09 | 1.59 | 658.00 | 01-JUL-08:61 | 1.71 |
August | 0.259568E+09 | 1.57 | 658.00 | 01-AUG-15:01 | 1.71 |
September | 0.193643E+09 | 1.51 | 658.00 | 01-SEP-15:01 | 1.69 |
October | 0.196591E+09 | 1.37 | 658.00 | 01-OCT-15:01 | 1.70 |
November | 0.218727E+09 | 1.34 | 658.00 | 01-NOV-08:62 | 1.71 |
December | 0.368312E+09 | 1.40 | 658.00 | 01-DEC-09:01 | 1.71 |
Annual Sum or Average | 0.288017E+10 | 1.44 | |||
Minimum of Months | 0.160215E+09 | 1.32 | 658.00 | 1.69 | |
Maximum of Months | 0.368312E+09 | 1.60 | 658.00 | 1.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133733E+10 | 1.53 | 2516.41 | 01-JAN-09:01 | 1.71 |
February | 0.122619E+10 | 1.53 | 2516.41 | 01-FEB-09:02 | 1.71 |
March | 0.111972E+10 | 1.47 | 2516.41 | 01-MAR-16:02 | 1.71 |
April | 0.735288E+09 | 1.39 | 2516.41 | 02-APR-08:62 | 1.71 |
May | 0.770727E+09 | 1.46 | 2516.41 | 02-MAY-15:01 | 1.71 |
June | 0.129656E+10 | 1.58 | 2516.41 | 01-JUN-08:62 | 1.69 |
July | 0.139149E+10 | 1.58 | 2516.41 | 01-JUL-08:61 | 1.71 |
August | 0.142974E+10 | 1.58 | 2516.41 | 01-AUG-15:01 | 1.71 |
September | 0.139207E+10 | 1.58 | 2516.41 | 01-SEP-15:01 | 1.70 |
October | 0.132530E+10 | 1.52 | 2516.41 | 01-OCT-08:62 | 1.70 |
November | 0.129748E+10 | 1.53 | 2516.41 | 01-NOV-08:62 | 1.71 |
December | 0.147913E+10 | 1.48 | 2516.41 | 01-DEC-09:01 | 1.71 |
Annual Sum or Average | 0.148010E+11 | 1.52 | |||
Minimum of Months | 0.735288E+09 | 1.39 | 2516.41 | 1.69 | |
Maximum of Months | 0.147913E+10 | 1.58 | 2516.41 | 1.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.263516E+10 | 0.237164E+10 | 2556.17 | 05-JAN-09:03 | 2300.55 | 2300.55 | 49.13 | 7.47 |
February | 0.263178E+10 | 0.236860E+10 | 2486.86 | 12-FEB-07:10 | 2238.17 | 2238.17 | 49.26 | 6.63 |
March | 0.233786E+10 | 0.210407E+10 | 2376.45 | 19-MAR-07:00 | 2138.80 | 2138.80 | 49.39 | 5.64 |
April | 0.214262E+10 | 0.192836E+10 | 2115.16 | 02-APR-15:03 | 1903.65 | 1903.65 | 48.94 | 4.21 |
May | 0.170833E+10 | 0.153750E+10 | 1484.31 | 20-MAY-15:04 | 1335.88 | 1335.88 | 49.64 | 2.34 |
June | 0.184411E+10 | 0.165970E+10 | 1485.92 | 22-JUN-08:04 | 1337.33 | 1337.33 | 48.43 | 2.34 |
July | 0.196352E+10 | 0.176716E+10 | 1633.35 | 10-JUL-08:04 | 1470.01 | 1470.01 | 48.29 | 2.69 |
August | 0.180058E+10 | 0.162052E+10 | 1543.29 | 07-AUG-08:05 | 1388.96 | 1388.96 | 48.69 | 2.47 |
September | 0.154286E+10 | 0.138857E+10 | 1589.27 | 18-SEP-08:03 | 1430.35 | 1430.35 | 46.63 | 2.58 |
October | 0.193354E+10 | 0.174019E+10 | 2323.58 | 31-OCT-08:62 | 2091.23 | 2091.23 | 49.01 | 5.27 |
November | 0.218564E+10 | 0.196708E+10 | 2298.15 | 29-NOV-09:03 | 2068.34 | 2068.34 | 48.63 | 5.12 |
December | 0.311429E+10 | 0.280286E+10 | 2658.23 | 23-DEC-07:20 | 2392.41 | 2392.41 | 49.72 | 8.82 |
Annual Sum or Average | 0.258403E+11 | 0.232563E+11 | ||||||
Minimum of Months | 0.154286E+10 | 0.138857E+10 | 1484.31 | 1335.88 | 1335.88 | 46.63 | 2.34 | |
Maximum of Months | 0.311429E+10 | 0.280286E+10 | 2658.23 | 2392.41 | 2392.41 | 49.72 | 8.82 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.239294E+10 | 0.215364E+10 | 5411.96 | 23-JAN-16:01 | 4870.76 | 4870.76 | 6.72 | 13.27 |
February | 0.183866E+10 | 0.165480E+10 | 5260.32 | 18-FEB-16:01 | 4734.29 | 4734.29 | 6.72 | 12.30 |
March | 0.311187E+10 | 0.280068E+10 | 5708.11 | 14-MAR-15:01 | 5137.30 | 5137.30 | 6.72 | 15.76 |
April | 0.304967E+10 | 0.274471E+10 | 5553.70 | 07-APR-15:01 | 4998.33 | 4998.33 | 6.72 | 14.34 |
May | 0.737952E+10 | 0.664157E+10 | 6636.35 | 31-MAY-15:01 | 5972.72 | 5972.72 | 6.72 | 26.35 |
June | 0.127163E+11 | 0.114446E+11 | 6847.29 | 15-JUN-18:30 | 6162.56 | 6162.56 | 6.72 | 27.64 |
July | 0.137562E+11 | 0.123806E+11 | 7061.62 | 23-JUL-15:02 | 6355.46 | 6355.46 | 6.72 | 28.73 |
August | 0.133796E+11 | 0.120417E+11 | 6633.95 | 24-AUG-16:20 | 5970.56 | 5970.56 | 6.72 | 26.33 |
September | 0.105409E+11 | 0.948683E+10 | 6592.47 | 03-SEP-15:50 | 5933.22 | 5933.22 | 6.72 | 26.04 |
October | 0.446404E+10 | 0.401763E+10 | 5775.84 | 07-OCT-15:01 | 5198.26 | 5198.26 | 6.72 | 16.50 |
November | 0.280641E+10 | 0.252577E+10 | 5636.77 | 05-NOV-15:01 | 5073.09 | 5073.09 | 6.72 | 15.06 |
December | 0.188758E+10 | 0.169882E+10 | 5166.52 | 02-DEC-16:01 | 4649.86 | 4649.86 | 6.72 | 11.77 |
Annual Sum or Average | 0.773237E+11 | 0.695914E+11 | ||||||
Minimum of Months | 0.183866E+10 | 0.165480E+10 | 5166.52 | 4649.86 | 4649.86 | 6.72 | 11.77 | |
Maximum of Months | 0.137562E+11 | 0.123806E+11 | 7061.62 | 6355.46 | 6355.46 | 6.72 | 28.73 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.88 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.13 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.42 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.95 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.88 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.90 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.34 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.42 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.77 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.65 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.31 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.22 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.42 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.77 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.429209E+10 | 0.386288E+10 | 2524.11 | 01-JAN-00:05 | 2271.70 | 2271.70 | 6.72 | 31.61 |
February | 0.329789E+10 | 0.296810E+10 | 2524.11 | 01-FEB-09:05 | 2271.70 | 2271.70 | 6.76 | 31.61 |
March | 0.459125E+10 | 0.413212E+10 | 2524.11 | 01-MAR-00:15 | 2271.70 | 2271.70 | 6.72 | 31.61 |
April | 0.475398E+10 | 0.427858E+10 | 2524.11 | 01-APR-00:10 | 2271.70 | 2271.70 | 6.82 | 31.61 |
May | 0.667122E+10 | 0.600410E+10 | 2524.11 | 01-MAY-00:05 | 2271.70 | 2271.70 | 6.78 | 31.61 |
June | 0.654249E+10 | 0.588824E+10 | 2524.11 | 01-JUN-00:10 | 2271.70 | 2271.70 | 7.84 | 31.61 |
July | 0.676057E+10 | 0.608452E+10 | 2524.11 | 01-JUL-00:10 | 2271.70 | 2271.70 | 9.41 | 31.61 |
August | 0.676057E+10 | 0.608452E+10 | 2524.11 | 01-AUG-00:10 | 2271.70 | 2271.70 | 9.71 | 31.61 |
September | 0.648822E+10 | 0.583940E+10 | 2524.11 | 01-SEP-00:10 | 2271.70 | 2271.70 | 8.54 | 31.61 |
October | 0.529551E+10 | 0.476596E+10 | 2524.11 | 01-OCT-00:05 | 2271.70 | 2271.70 | 6.94 | 31.61 |
November | 0.436215E+10 | 0.392593E+10 | 2524.11 | 01-NOV-08:05 | 2271.70 | 2271.70 | 6.78 | 31.61 |
December | 0.351091E+10 | 0.315982E+10 | 2524.11 | 01-DEC-06:03 | 2271.70 | 2271.70 | 6.75 | 31.61 |
Annual Sum or Average | 0.633268E+11 | 0.569942E+11 | ||||||
Minimum of Months | 0.329789E+10 | 0.296810E+10 | 2524.11 | 2271.70 | 2271.70 | 6.72 | 31.61 | |
Maximum of Months | 0.676057E+10 | 0.608452E+10 | 2524.11 | 2271.70 | 2271.70 | 9.71 | 31.61 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.88 | 59.92 | 28851.45 | 59585.97 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.13 | 59.88 | 29169.20 | 59863.24 | 13-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.42 | 58.11 | 28752.62 | 59551.11 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.95 | 58.54 | 27589.06 | 57662.97 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.88 | 59.68 | 25900.22 | 55046.07 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.90 | 59.89 | 24118.83 | 51831.95 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.34 | 59.99 | 22808.01 | 49007.46 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.42 | 59.83 | 22390.85 | 47649.80 | 01-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.77 | 60.23 | 22922.26 | 49191.16 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.65 | 59.01 | 24249.55 | 52085.20 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.31 | 59.26 | 25997.31 | 55241.81 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.22 | 58.13 | 27632.16 | 57920.92 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 25845.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.42 | 58.11 | 22390.85 | 47649.80 | ||
Maximum of Months | 0.00 | 0.00 | 53.77 | 60.23 | 29169.20 | 59863.24 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50.89 | 60.00 | 68869.89 | 339718.33 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.98 | 60.00 | 75891.47 | 297733.29 | 12-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.74 | 60.00 | 57266.91 | 276066.40 | 19-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 47.49 | 60.00 | 53472.05 | 204745.04 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.01 | 60.00 | 42455.76 | 107280.39 | 04-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 50.21 | 60.00 | 44909.19 | 113807.38 | 13-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 50.10 | 60.00 | 46415.80 | 131703.97 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 49.90 | 60.00 | 43834.97 | 121849.76 | 11-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 49.54 | 60.00 | 39863.22 | 144411.52 | 18-SEP-08:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 44.24 | 60.00 | 48286.09 | 251097.45 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.53 | 60.00 | 54878.10 | 243263.85 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.98 | 60.00 | 95472.08 | 384873.80 | 21-DEC-09:06 |
Annual Sum or Average | 0.00 | 55888.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.24 | 60.00 | 39863.22 | 107280.39 | ||
Maximum of Months | 0.00 | 0.00 | 51.98 | 60.00 | 95472.08 | 384873.80 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 30163.57 | 449544.46 | 23-JAN-16:01 | 10.09 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 23549.71 | 390622.82 | 18-FEB-16:01 | 9.65 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 43969.07 | 558902.49 | 13-MAR-15:01 | 10.92 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 43716.78 | 499395.84 | 27-APR-15:01 | 10.47 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131194.23 | 572558.06 | 16-MAY-15:01 | 11.02 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 332294.45 | 711987.66 | 26-JUN-15:03 | 12.08 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369938.83 | 793077.22 | 31-JUL-18:01 | 12.69 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 334076.11 | 795104.44 | 05-AUG-15:01 | 12.71 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 245674.27 | 649768.29 | 28-SEP-15:01 | 11.61 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 70095.91 | 599214.70 | 11-OCT-15:01 | 11.22 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 39306.36 | 537618.20 | 05-NOV-15:01 | 10.76 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26264.52 | 381476.22 | 02-DEC-15:00 | 9.58 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 141550.46 | 0.00 | ||||||
Minimum of Months | 23549.71 | 381476.22 | 9.58 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 369938.83 | 795104.44 | 12.71 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.22 | 0.51 |
February | 1.74 | 0.67 |
March | 2.71 | 0.63 |
April | 1.47 | 0.69 |
May | 2.28 | 0.76 |
June | 2.25 | 0.49 |
July | 3.01 | 0.53 |
August | 2.04 | 0.50 |
September | 2.67 | 0.49 |
October | 2.14 | 0.66 |
November | 1.61 | 0.55 |
December | 1.49 | 0.54 |
Annual Sum or Average | 24.62 | 0.58 |
Minimum of Months | 1.22 | 0.49 |
Maximum of Months | 3.01 | 0.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.51 | 0.62 |
February | 2.54 | 0.63 |
March | 2.62 | 0.62 |
April | 1.58 | 0.67 |
May | 2.25 | 0.77 |
June | 2.33 | 0.50 |
July | 3.22 | 0.54 |
August | 1.58 | 0.58 |
September | 1.37 | 0.69 |
October | 0.89 | 0.73 |
November | 1.29 | 0.51 |
December | 2.74 | 0.70 |
Annual Sum or Average | 24.94 | 0.62 |
Minimum of Months | 0.89 | 0.50 |
Maximum of Months | 3.22 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.38 | 0.60 |
February | 0.12 | 0.80 |
March | 0.08 | 0.81 |
April | 0.22 | 0.81 |
May | 1.49 | 0.78 |
June | 2.33 | 0.78 |
July | 2.86 | 0.77 |
August | 2.74 | 0.80 |
September | 2.12 | 0.79 |
October | 0.28 | 0.70 |
November | 0.22 | 0.75 |
December | 2.26 | 0.63 |
Annual Sum or Average | 15.11 | 0.75 |
Minimum of Months | 0.08 | 0.60 |
Maximum of Months | 2.86 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.21 | 0.47 |
February | 1.76 | 0.60 |
March | 2.35 | 0.55 |
April | 2.29 | 0.51 |
May | 3.31 | 0.55 |
June | 1.61 | 0.55 |
July | 1.60 | 0.64 |
August | 1.68 | 0.67 |
September | 2.22 | 0.69 |
October | 2.57 | 0.59 |
November | 1.44 | 0.50 |
December | 1.38 | 0.53 |
Annual Sum or Average | 23.42 | 0.57 |
Minimum of Months | 1.21 | 0.47 |
Maximum of Months | 3.31 | 0.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.60 | 0.72 |
February | 1.82 | 0.68 |
March | 1.82 | 0.61 |
April | 2.50 | 0.48 |
May | 3.31 | 0.55 |
June | 1.87 | 0.57 |
July | 1.78 | 0.62 |
August | 2.65 | 0.63 |
September | 4.18 | 0.61 |
October | 1.03 | 0.62 |
November | 1.18 | 0.67 |
December | 1.86 | 0.76 |
Annual Sum or Average | 25.60 | 0.61 |
Minimum of Months | 1.03 | 0.48 |
Maximum of Months | 4.18 | 0.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.87 | 0.61 |
February | 2.11 | 0.72 |
March | 2.83 | 0.64 |
April | 1.35 | 0.70 |
May | 2.12 | 0.68 |
June | 2.24 | 0.46 |
July | 2.85 | 0.52 |
August | 2.21 | 0.43 |
September | 1.72 | 0.47 |
October | 1.29 | 0.67 |
November | 1.96 | 0.62 |
December | 2.35 | 0.66 |
Annual Sum or Average | 24.90 | 0.59 |
Minimum of Months | 1.29 | 0.43 |
Maximum of Months | 2.85 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.06 | 0.56 |
February | 1.29 | 0.61 |
March | 2.79 | 0.63 |
April | 1.26 | 0.72 |
May | 2.01 | 0.68 |
June | 2.24 | 0.47 |
July | 2.85 | 0.52 |
August | 2.21 | 0.49 |
September | 1.75 | 0.56 |
October | 1.10 | 0.76 |
November | 1.32 | 0.63 |
December | 2.31 | 0.68 |
Annual Sum or Average | 23.18 | 0.60 |
Minimum of Months | 1.10 | 0.47 |
Maximum of Months | 2.85 | 0.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.56 | 0.77 |
February | 1.86 | 0.75 |
March | 2.07 | 0.63 |
April | 1.88 | 0.57 |
May | 1.67 | 0.64 |
June | 2.26 | 0.50 |
July | 3.36 | 0.53 |
August | 2.44 | 0.52 |
September | 1.43 | 0.71 |
October | 1.85 | 0.69 |
November | 2.08 | 0.74 |
December | 1.07 | 0.70 |
Annual Sum or Average | 23.53 | 0.63 |
Minimum of Months | 1.07 | 0.50 |
Maximum of Months | 3.36 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.17 | 174.93 |
April | 0.08 | 174.93 |
May | 0.17 | 174.93 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 174.93 |
October | 0.25 | 174.93 |
November | 0.25 | 174.93 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 174.93 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 174.93 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 174.93 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.114915E+12 | 0.00 | 0.177937E+11 | 0.156033E+12 | 0.00 | 0.00 |
February | 0.112633E+12 | 0.00 | 0.982622E+10 | 0.140933E+12 | 0.00 | 0.00 |
March | 0.102184E+12 | 0.00 | 0.516207E+11 | 0.156033E+12 | 0.00 | 0.00 |
April | 0.949933E+11 | 0.00 | 0.608423E+11 | 0.151000E+12 | 0.00 | 0.00 |
May | 0.996626E+11 | 0.00 | 0.229532E+12 | 0.156033E+12 | 0.00 | 0.00 |
June | 0.117406E+12 | 0.00 | 0.631884E+12 | 0.151000E+12 | 0.00 | 0.00 |
July | 0.125584E+12 | 0.00 | 0.742446E+12 | 0.156033E+12 | 0.00 | 0.00 |
August | 0.118528E+12 | 0.00 | 0.662058E+12 | 0.156033E+12 | 0.00 | 0.00 |
September | 0.991344E+11 | 0.00 | 0.449365E+12 | 0.151000E+12 | 0.00 | 0.00 |
October | 0.865342E+11 | 0.00 | 0.897172E+11 | 0.156033E+12 | 0.00 | 0.00 |
November | 0.837438E+11 | 0.00 | 0.318983E+11 | 0.151000E+12 | 0.00 | 0.00 |
December | 0.166796E+12 | 0.00 | 0.230866E+11 | 0.156033E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.132211E+13 | 0.00 | 0.300007E+13 | 0.183716E+13 | 0.00 | 0.00 |
Minimum of Months | 0.837438E+11 | 0.00 | 0.982622E+10 | 0.140933E+12 | 0.00 | 0.00 |
Maximum of Months | 0.166796E+12 | 0.00 | 0.742446E+12 | 0.156033E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.481087E+11 | 0.00 | 0.806315E+09 | 0.587767E+10 | 0.00 | 0.00 |
February | 0.450771E+11 | 0.00 | 0.433304E+09 | 0.530887E+10 | 0.00 | 0.00 |
March | 0.388507E+11 | 0.00 | 0.272107E+10 | 0.587767E+10 | 0.00 | 0.00 |
April | 0.356866E+11 | 0.00 | 0.323793E+10 | 0.568807E+10 | 0.00 | 0.00 |
May | 0.148001E+11 | 0.00 | 0.153487E+11 | 0.587767E+10 | 0.00 | 0.00 |
June | 0.727046E+09 | 0.00 | 0.524485E+11 | 0.568807E+10 | 0.00 | 0.00 |
July | 0.582751E+09 | 0.00 | 0.610428E+11 | 0.587767E+10 | 0.00 | 0.00 |
August | 0.563369E+09 | 0.00 | 0.522589E+11 | 0.587767E+10 | 0.00 | 0.00 |
September | 0.521359E+10 | 0.00 | 0.348520E+11 | 0.568807E+10 | 0.00 | 0.00 |
October | 0.330779E+11 | 0.00 | 0.528180E+10 | 0.587767E+10 | 0.00 | 0.00 |
November | 0.428489E+11 | 0.00 | 0.173877E+10 | 0.568807E+10 | 0.00 | 0.00 |
December | 0.491377E+11 | 0.00 | 0.121687E+10 | 0.587767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.314675E+12 | 0.00 | 0.231387E+12 | 0.692049E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563369E+09 | 0.00 | 0.433304E+09 | 0.530887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.491377E+11 | 0.00 | 0.610428E+11 | 0.587767E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156033E+12 | 0.177937E+11 | 0.114915E+12 | 0.916759E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140933E+12 | 0.982622E+10 | 0.112633E+12 | 0.893442E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156033E+12 | 0.516207E+11 | 0.102184E+12 | 0.671035E+12 | 0.396768E+09 | 0.00 | 0.00 | 0.00 |
April | 0.151000E+12 | 0.608423E+11 | 0.949933E+11 | 0.578147E+12 | 51146500.32 | 0.00 | 0.00 | 0.00 |
May | 0.156033E+12 | 0.229532E+12 | 0.996626E+11 | 0.170563E+12 | 0.121289E+11 | 0.00 | 0.00 | 0.00 |
June | 0.151000E+12 | 0.631884E+12 | 0.117406E+12 | 0.926814E+10 | 0.127119E+12 | 0.00 | 0.00 | 0.00 |
July | 0.156033E+12 | 0.742446E+12 | 0.125584E+12 | 0.841067E+10 | 0.144395E+12 | 0.00 | 0.00 | 0.00 |
August | 0.156033E+12 | 0.662058E+12 | 0.118528E+12 | 0.510586E+10 | 0.108565E+12 | 0.00 | 0.00 | 0.00 |
September | 0.151000E+12 | 0.449365E+12 | 0.991344E+11 | 0.641751E+11 | 0.550021E+11 | 0.00 | 0.00 | 0.00 |
October | 0.156033E+12 | 0.897172E+11 | 0.865342E+11 | 0.532957E+12 | 0.200982E+10 | 0.00 | 0.00 | 0.00 |
November | 0.151000E+12 | 0.318983E+11 | 0.837438E+11 | 0.765936E+12 | 21506460.75 | 0.00 | 0.00 | 0.00 |
December | 0.156033E+12 | 0.230866E+11 | 0.166796E+12 | 0.100490E+13 | 7955408.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183716E+13 | 0.300007E+13 | 0.132211E+13 | 0.562070E+13 | 0.449697E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140933E+12 | 0.982622E+10 | 0.837438E+11 | 0.510586E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156033E+12 | 0.742446E+12 | 0.166796E+12 | 0.100490E+13 | 0.144395E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587767E+10 | 0.806315E+09 | 0.481087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.433304E+09 | 0.450771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.272107E+10 | 0.388507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.323793E+10 | 0.356866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.153487E+11 | 0.148001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.524485E+11 | 0.727046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.610428E+11 | 0.582751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.522589E+11 | 0.563369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.348520E+11 | 0.521359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.528180E+10 | 0.330779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.173877E+10 | 0.428489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.121687E+10 | 0.491377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.231387E+12 | 0.314675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530887E+10 | 0.433304E+09 | 0.563369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.610428E+11 | 0.491377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156033E+12 | 0.114915E+12 | 0.177937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140933E+12 | 0.112633E+12 | 0.982622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156033E+12 | 0.102184E+12 | 0.516207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151000E+12 | 0.949933E+11 | 0.608423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156033E+12 | 0.996626E+11 | 0.229532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151000E+12 | 0.117406E+12 | 0.631884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156033E+12 | 0.125584E+12 | 0.742446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156033E+12 | 0.118528E+12 | 0.662058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151000E+12 | 0.991344E+11 | 0.449365E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156033E+12 | 0.865342E+11 | 0.897172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151000E+12 | 0.837438E+11 | 0.318983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156033E+12 | 0.166796E+12 | 0.230866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183716E+13 | 0.132211E+13 | 0.300007E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140933E+12 | 0.837438E+11 | 0.982622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156033E+12 | 0.166796E+12 | 0.742446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.587767E+10 | 0.481087E+11 | 0.806315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.450771E+11 | 0.433304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.388507E+11 | 0.272107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.356866E+11 | 0.323793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.148001E+11 | 0.153487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.727046E+09 | 0.524485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.582751E+09 | 0.610428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.563369E+09 | 0.522589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.521359E+10 | 0.348520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.330779E+11 | 0.528180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.428489E+11 | 0.173877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.491377E+11 | 0.121687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.314675E+12 | 0.231387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530887E+10 | 0.563369E+09 | 0.433304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.491377E+11 | 0.610428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41222630.63 | 0.00 | 0.00 | 2.38 |
February | 0.728468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36710004.48 | 0.00 | 0.00 | 2.37 |
March | 0.739939E+11 | 0.00 | 6090090.10 | 0.00 | 0.00 | 0.603357E+09 | 0.00 | 100942.87 | 2.37 |
April | 0.694920E+11 | 0.00 | 1348370.43 | 0.00 | 0.00 | 0.446385E+09 | 0.00 | 17966.07 | 2.37 |
May | 0.562627E+11 | 0.00 | 0.429954E+09 | 0.00 | 9650781.11 | 0.151014E+10 | 0.00 | 8639213.60 | 2.36 |
June | 0.204356E+11 | 0.00 | 0.513196E+10 | 0.00 | 0.150714E+10 | 0.235643E+09 | 0.00 | 45999646.72 | 2.36 |
July | 0.144359E+11 | 0.00 | 0.662860E+10 | 0.00 | 0.369066E+10 | 0.126724E+09 | 0.00 | 49608981.87 | 2.35 |
August | 0.202691E+11 | 0.00 | 0.559978E+09 | 0.00 | 0.631529E+10 | 0.124297E+09 | 0.00 | 15696572.07 | 2.36 |
September | 0.355745E+11 | 0.00 | 85896520.18 | 0.00 | 0.222506E+10 | 17572948.22 | 0.00 | 1863297.30 | 2.35 |
October | 0.715899E+11 | 0.00 | 225314.95 | 0.00 | 60849503.51 | 1628013.75 | 0.00 | 738.92 | 2.36 |
November | 0.741220E+11 | 0.00 | 0.00 | 0.00 | 39929.38 | 471220.31 | 0.00 | 0.00 | 2.38 |
December | 0.842137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
Annual Sum or Average | 0.673126E+12 | 0.00 | 0.128441E+11 | 0.00 | 0.138087E+11 | 0.314415E+10 | 0.00 | 0.121927E+09 | 2.37 |
Minimum of Months | 0.144359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
Maximum of Months | 0.842137E+11 | 0.00 | 0.662860E+10 | 0.00 | 0.631529E+10 | 0.151014E+10 | 0.00 | 49608981.87 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.629171E+10 | 0.00 | 0.00 | 1637407.34 | 0.00 | 0.244834E+10 | 0.113931E+10 | 0.00 | 5.35 |
February | 0.489805E+10 | 0.00 | 0.00 | 1059962.93 | 0.00 | 0.317803E+10 | 0.931620E+09 | 0.00 | 5.33 |
March | 0.599663E+10 | 690593.20 | 0.00 | 425814.87 | 74586.84 | 0.291518E+10 | 0.307610E+09 | 0.00 | 5.33 |
April | 0.621267E+10 | 0.00 | 0.00 | 0.00 | 168872.21 | 0.243136E+10 | 0.00 | 0.00 | 5.33 |
May | 0.693835E+10 | 0.00 | 0.00 | 0.00 | 55400671.18 | 0.202086E+09 | 0.00 | 0.00 | 5.30 |
June | 0.255486E+10 | 0.00 | 0.00 | 0.00 | 0.826243E+09 | 0.00 | 0.00 | 0.00 | 5.30 |
July | 0.179987E+10 | 0.00 | 0.00 | 0.00 | 0.128154E+10 | 0.00 | 0.00 | 0.00 | 5.29 |
August | 0.252052E+10 | 0.00 | 0.00 | 0.00 | 0.851689E+09 | 0.00 | 0.00 | 0.00 | 5.29 |
September | 0.428134E+10 | 52667557.85 | 0.00 | 47508.70 | 0.233185E+09 | 0.109221E+09 | 8392169.73 | 0.00 | 5.28 |
October | 0.645986E+10 | 6738104.41 | 0.00 | 797334.71 | 810522.32 | 0.184337E+10 | 0.544325E+09 | 0.00 | 5.31 |
November | 0.604941E+10 | 4935.07 | 0.00 | 1821032.19 | 0.00 | 0.206083E+10 | 0.105121E+10 | 0.00 | 5.33 |
December | 0.559865E+10 | 0.00 | 0.00 | 1442610.80 | 0.00 | 0.402258E+10 | 0.788117E+09 | 0.00 | 5.31 |
Annual Sum or Average | 0.596019E+11 | 60101190.53 | 0.00 | 7231671.54 | 0.324911E+10 | 0.192110E+11 | 0.477059E+10 | 0.00 | 5.31 |
Minimum of Months | 0.179987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
Maximum of Months | 0.693835E+10 | 52667557.85 | 0.00 | 1821032.19 | 0.128154E+10 | 0.402258E+10 | 0.113931E+10 | 0.00 | 5.35 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 |
February | 0.678034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
March | 0.693977E+10 | 0.00 | 0.00 | 0.00 | 575950.50 | 0.00 | 0.00 | 0.00 | 3.47 |
April | 0.650635E+10 | 0.00 | 0.00 | 0.00 | 127110.00 | 0.00 | 0.00 | 0.00 | 3.46 |
May | 0.537460E+10 | 0.00 | 0.00 | 0.00 | 41700048.45 | 0.00 | 0.00 | 0.00 | 3.45 |
June | 0.192304E+10 | 0.00 | 0.00 | 0.00 | 0.621913E+09 | 0.00 | 0.00 | 0.00 | 3.45 |
July | 0.135476E+10 | 0.00 | 0.00 | 0.00 | 0.964614E+09 | 0.00 | 0.00 | 0.00 | 3.44 |
August | 0.189720E+10 | 0.00 | 0.00 | 0.00 | 0.641065E+09 | 0.00 | 0.00 | 0.00 | 3.44 |
September | 0.331112E+10 | 0.00 | 0.00 | 0.00 | 0.215161E+09 | 0.00 | 0.00 | 0.00 | 3.43 |
October | 0.666015E+10 | 0.00 | 0.00 | 0.00 | 5681846.34 | 0.00 | 0.00 | 0.00 | 3.45 |
November | 0.689560E+10 | 0.00 | 0.00 | 0.00 | 3714.62 | 0.00 | 0.00 | 0.00 | 3.46 |
December | 0.783408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311448.51 | 0.00 | 0.00 | 3.45 |
Annual Sum or Average | 0.629130E+11 | 0.00 | 0.00 | 0.00 | 0.249084E+10 | 311448.51 | 0.00 | 0.00 | 3.45 |
Minimum of Months | 0.135476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Maximum of Months | 0.783408E+10 | 0.00 | 0.00 | 0.00 | 0.964614E+09 | 311448.51 | 0.00 | 0.00 | 3.47 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.809366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280221E+09 | 0.00 | 0.00 | 1.85 |
February | 0.736358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271963E+09 | 0.00 | 0.00 | 1.84 |
March | 0.781508E+10 | 0.00 | 0.00 | 0.00 | 648595.11 | 0.00 | 0.00 | 0.00 | 1.84 |
April | 0.730607E+10 | 0.00 | 0.00 | 0.00 | 143142.38 | 20921270.14 | 0.00 | 0.00 | 1.84 |
May | 0.605250E+10 | 0.00 | 0.00 | 0.00 | 46959673.06 | 0.00 | 0.00 | 0.00 | 1.83 |
June | 0.216560E+10 | 0.00 | 0.00 | 0.00 | 0.700355E+09 | 0.00 | 0.00 | 0.00 | 1.83 |
July | 0.152563E+10 | 0.00 | 0.00 | 0.00 | 0.108628E+10 | 0.00 | 0.00 | 0.00 | 1.83 |
August | 0.213649E+10 | 0.00 | 0.00 | 0.00 | 0.721923E+09 | 0.00 | 0.00 | 0.00 | 1.83 |
September | 0.372875E+10 | 0.00 | 0.00 | 0.00 | 0.242300E+09 | 0.00 | 0.00 | 0.00 | 1.83 |
October | 0.745636E+10 | 0.00 | 0.00 | 0.00 | 6398497.27 | 43835887.67 | 0.00 | 0.00 | 1.83 |
November | 0.764010E+10 | 0.00 | 0.00 | 0.00 | 4183.15 | 0.125242E+09 | 0.00 | 0.00 | 1.84 |
December | 0.739495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142759E+10 | 0.00 | 0.00 | 1.83 |
Annual Sum or Average | 0.686788E+11 | 0.00 | 0.00 | 0.00 | 0.280501E+10 | 0.216977E+10 | 0.00 | 0.00 | 1.84 |
Minimum of Months | 0.152563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
Maximum of Months | 0.809366E+10 | 0.00 | 0.00 | 0.00 | 0.108628E+10 | 0.142759E+10 | 0.00 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147819E+10 | 0.00 | 0.00 | 1.34 |
February | 0.149895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169206E+10 | 0.00 | 0.00 | 1.33 |
March | 0.217361E+10 | 0.00 | 0.00 | 0.00 | 271058.40 | 0.109243E+10 | 0.00 | 0.00 | 1.34 |
April | 0.232761E+10 | 0.00 | 0.00 | 0.00 | 59821.52 | 0.734459E+09 | 0.00 | 0.00 | 1.33 |
May | 0.249240E+10 | 0.00 | 0.00 | 0.00 | 19625208.00 | 37032804.43 | 0.00 | 0.00 | 1.33 |
June | 0.905038E+09 | 0.00 | 0.00 | 0.00 | 0.292690E+09 | 0.00 | 0.00 | 0.00 | 1.33 |
July | 0.637587E+09 | 0.00 | 0.00 | 0.00 | 0.453974E+09 | 0.00 | 0.00 | 0.00 | 1.32 |
August | 0.892874E+09 | 0.00 | 0.00 | 0.00 | 0.301703E+09 | 0.00 | 0.00 | 0.00 | 1.33 |
September | 0.154244E+10 | 0.00 | 0.00 | 0.00 | 0.101261E+09 | 15866868.99 | 0.00 | 0.00 | 1.32 |
October | 0.256297E+10 | 0.00 | 0.00 | 0.00 | 2674035.65 | 0.571486E+09 | 0.00 | 0.00 | 1.33 |
November | 0.223654E+10 | 0.00 | 0.00 | 0.00 | 1748.20 | 0.100873E+10 | 0.00 | 0.00 | 1.33 |
December | 0.168925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199783E+10 | 0.00 | 0.00 | 1.33 |
Annual Sum or Average | 0.209807E+11 | 0.00 | 0.00 | 0.00 | 0.117226E+10 | 0.862810E+10 | 0.00 | 0.00 | 1.33 |
Minimum of Months | 0.637587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Maximum of Months | 0.256297E+10 | 0.00 | 0.00 | 0.00 | 0.453974E+09 | 0.199783E+10 | 0.00 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175313E+10 | 0.00 | 0.00 | 72010490.91 | 0.00 | 0.00 | 0.989197E+11 | 0.00 | 46.87 |
February | 0.161406E+10 | 0.00 | 0.00 | 64580063.58 | 0.00 | 0.00 | 0.901771E+11 | 0.00 | 46.69 |
March | 0.136620E+10 | 7795398.69 | 0.00 | 72567822.76 | 0.00 | 0.00 | 0.925843E+11 | 0.00 | 46.77 |
April | 0.932479E+09 | 1720413.68 | 0.00 | 68791362.27 | 0.00 | 0.00 | 0.871327E+11 | 0.00 | 46.72 |
May | 0.530807E+09 | 0.542062E+09 | 0.00 | 67482768.40 | 22341758.55 | 0.00 | 0.721877E+11 | 0.00 | 46.46 |
June | 0.146300E+09 | 0.804684E+10 | 0.00 | 33788001.84 | 0.370648E+09 | 0.00 | 0.258480E+11 | 0.00 | 46.35 |
July | 0.115344E+09 | 0.125802E+11 | 0.00 | 28753038.76 | 0.475644E+09 | 0.00 | 0.181923E+11 | 0.00 | 46.22 |
August | 0.193167E+09 | 0.833279E+10 | 0.00 | 36287318.39 | 0.343932E+09 | 0.00 | 0.254488E+11 | 0.00 | 46.26 |
September | 0.259503E+09 | 0.276514E+10 | 0.00 | 52385190.07 | 0.147038E+09 | 0.00 | 0.445125E+11 | 0.00 | 46.17 |
October | 0.125191E+10 | 73918181.89 | 0.00 | 71957881.27 | 2984706.88 | 0.00 | 0.889015E+11 | 0.00 | 46.49 |
November | 0.141983E+10 | 50276.82 | 0.00 | 70394345.03 | 0.00 | 0.00 | 0.919381E+11 | 0.00 | 46.74 |
December | 0.203538E+10 | 0.00 | 0.00 | 70529700.41 | 0.00 | 0.00 | 0.104027E+12 | 0.00 | 46.52 |
Annual Sum or Average | 0.116181E+11 | 0.323506E+11 | 0.00 | 0.709528E+09 | 0.136259E+10 | 0.00 | 0.839870E+12 | 0.00 | 46.52 |
Minimum of Months | 0.115344E+09 | 0.00 | 0.00 | 28753038.76 | 0.00 | 0.00 | 0.181923E+11 | 0.00 | 46.17 |
Maximum of Months | 0.203538E+10 | 0.125802E+11 | 0.00 | 72567822.76 | 0.475644E+09 | 0.00 | 0.104027E+12 | 0.00 | 46.87 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356904E+11 | 0.00 | 0.00 | 4980334.31 | 0.00 | 0.620649E+09 | 0.643389E+10 | 0.00 | 8.22 |
February | 0.331738E+11 | 0.00 | 0.00 | 3404067.85 | 0.00 | 0.740749E+09 | 0.506264E+10 | 0.00 | 8.19 |
March | 0.366951E+11 | 2988418.12 | 0.00 | 1333704.23 | 322761.15 | 0.153568E+09 | 0.304718E+10 | 0.00 | 8.20 |
April | 0.366799E+11 | 0.00 | 0.00 | 19961.30 | 730764.18 | 0.246818E+09 | 0.478728E+09 | 0.00 | 8.19 |
May | 0.306403E+11 | 0.00 | 0.00 | 4798.71 | 0.239736E+09 | 0.00 | 0.258612E+09 | 0.00 | 8.15 |
June | 0.106414E+11 | 0.117127E+09 | 0.00 | 75402.32 | 0.345829E+10 | 0.00 | 0.414227E+09 | 0.00 | 8.15 |
July | 0.750232E+10 | 0.130555E+09 | 0.00 | 59210.15 | 0.541508E+10 | 0.00 | 0.286212E+09 | 0.00 | 8.13 |
August | 0.106120E+11 | 0.149605E+09 | 0.00 | 71139.42 | 0.353592E+10 | 0.00 | 0.295094E+09 | 0.00 | 8.13 |
September | 0.179369E+11 | 0.229258E+09 | 0.00 | 244466.38 | 0.100772E+10 | 0.00 | 0.109875E+10 | 0.00 | 8.12 |
October | 0.325167E+11 | 29184032.13 | 0.00 | 2554219.61 | 3481295.35 | 0.955626E+09 | 0.481477E+10 | 0.00 | 8.16 |
November | 0.330055E+11 | 21355.62 | 0.00 | 5187928.09 | 0.00 | 0.325384E+09 | 0.630821E+10 | 0.00 | 8.20 |
December | 0.388938E+11 | 0.00 | 0.00 | 4025127.86 | 0.00 | 0.203532E+10 | 0.410731E+10 | 0.00 | 8.16 |
Annual Sum or Average | 0.323988E+12 | 0.658738E+09 | 0.00 | 21960360.23 | 0.136613E+11 | 0.507812E+10 | 0.326056E+11 | 0.00 | 8.17 |
Minimum of Months | 0.750232E+10 | 0.00 | 0.00 | 4798.71 | 0.00 | 0.00 | 0.258612E+09 | 0.00 | 8.12 |
Maximum of Months | 0.388938E+11 | 0.229258E+09 | 0.00 | 5187928.09 | 0.541508E+10 | 0.203532E+10 | 0.643389E+10 | 0.00 | 8.22 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
February | 0.131193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
March | 0.134278E+12 | 0.00 | 0.00 | 0.00 | 11144090.06 | 0.00 | 0.00 | 0.00 | 3.98 |
April | 0.125892E+12 | 0.00 | 0.00 | 0.00 | 2459456.63 | 0.00 | 0.00 | 0.00 | 3.98 |
May | 0.103993E+12 | 0.00 | 0.00 | 0.00 | 0.806856E+09 | 0.00 | 0.00 | 0.00 | 3.96 |
June | 0.372090E+11 | 0.00 | 0.00 | 0.00 | 0.120334E+11 | 0.00 | 0.00 | 0.00 | 3.96 |
July | 0.262133E+11 | 0.00 | 0.00 | 0.00 | 0.186643E+11 | 0.00 | 0.00 | 0.00 | 3.95 |
August | 0.367089E+11 | 0.00 | 0.00 | 0.00 | 0.124040E+11 | 0.00 | 0.00 | 0.00 | 3.95 |
September | 0.640670E+11 | 0.00 | 0.00 | 0.00 | 0.416317E+10 | 0.00 | 0.00 | 0.00 | 3.94 |
October | 0.128867E+12 | 0.00 | 0.00 | 0.00 | 0.109938E+09 | 0.00 | 0.00 | 0.00 | 3.96 |
November | 0.133423E+12 | 0.00 | 0.00 | 0.00 | 71874.37 | 0.00 | 0.00 | 0.00 | 3.98 |
December | 0.151540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 48229842.35 | 0.00 | 0.00 | 3.96 |
Annual Sum or Average | 0.121726E+13 | 0.00 | 0.00 | 0.00 | 0.481954E+11 | 48229842.35 | 0.00 | 0.00 | 3.97 |
Minimum of Months | 0.262133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
Maximum of Months | 0.151540E+12 | 0.00 | 0.00 | 0.00 | 0.186643E+11 | 48229842.35 | 0.00 | 0.00 | 3.99 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.604915E+09 | 0.00 | 0.00 | 4507087.11 | 0.00 | 0.203514E+10 | 0.113116E+10 | 0.00 | 0.47 |
February | 0.580487E+09 | 0.00 | 0.00 | 4324821.91 | 0.00 | 0.195796E+10 | 0.986560E+09 | 0.00 | 0.47 |
March | 0.564267E+09 | 0.00 | 0.00 | 6970857.82 | 0.00 | 0.149470E+10 | 0.103037E+10 | 0.00 | 0.47 |
April | 0.567233E+09 | 0.00 | 0.00 | 5276543.82 | 0.00 | 0.131582E+10 | 0.921389E+09 | 0.00 | 0.47 |
May | 0.244888E+09 | 15670498.12 | 0.00 | 9263256.18 | 355941.09 | 0.211599E+09 | 0.124566E+10 | 0.00 | 0.47 |
June | 27714457.03 | 0.307026E+09 | 80369.10 | 6229123.98 | 15112862.22 | 427057.26 | 0.443273E+09 | 7939.16 | 0.47 |
July | 17180167.64 | 0.393729E+09 | 180194.48 | 5220366.16 | 24885582.61 | 281361.74 | 0.342158E+09 | 21569.35 | 0.47 |
August | 41020459.44 | 0.284944E+09 | 36382.61 | 6453884.80 | 11003149.60 | 743138.87 | 0.417870E+09 | 8452.85 | 0.47 |
September | 89963586.37 | 0.102828E+09 | 10566.65 | 9258141.98 | 3856509.08 | 78104685.91 | 0.801561E+09 | 3275.70 | 0.47 |
October | 0.375083E+09 | 1597200.18 | 0.00 | 8514216.37 | 17103.52 | 0.113396E+10 | 0.125170E+10 | 0.00 | 0.47 |
November | 0.544099E+09 | 0.00 | 0.00 | 5555407.50 | 0.00 | 0.159902E+10 | 0.116288E+10 | 0.00 | 0.47 |
December | 0.678460E+09 | 0.00 | 0.00 | 3182756.17 | 0.00 | 0.261894E+10 | 0.722360E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.433531E+10 | 0.110580E+10 | 307512.85 | 74756463.82 | 55231148.13 | 0.124467E+11 | 0.104569E+11 | 41237.06 | 0.47 |
Minimum of Months | 17180167.64 | 0.00 | 0.00 | 3182756.17 | 0.00 | 281361.74 | 0.342158E+09 | 0.00 | 0.47 |
Maximum of Months | 0.678460E+09 | 0.393729E+09 | 180194.48 | 9263256.18 | 24885582.61 | 0.261894E+10 | 0.125170E+10 | 21569.35 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799753E+09 | 0.00 | 0.00 | 1371922.81 | 0.00 | 0.261784E+10 | 0.356753E+09 | 0.00 | 0.47 |
February | 0.688992E+09 | 0.00 | 0.00 | 1638520.95 | 0.00 | 0.244278E+10 | 0.395921E+09 | 0.00 | 0.47 |
March | 0.633752E+09 | 0.00 | 0.00 | 4399406.23 | 0.00 | 0.172413E+10 | 0.734024E+09 | 0.00 | 0.47 |
April | 0.607485E+09 | 0.00 | 0.00 | 4221411.15 | 0.00 | 0.144332E+10 | 0.754694E+09 | 0.00 | 0.47 |
May | 0.260950E+09 | 15653581.51 | 0.00 | 8766131.28 | 372857.70 | 0.230559E+09 | 0.121113E+10 | 0.00 | 0.47 |
June | 28121529.13 | 0.306438E+09 | 68496.13 | 6175841.52 | 15713253.27 | 436777.92 | 0.442910E+09 | 7445.76 | 0.47 |
July | 17466143.18 | 0.391111E+09 | 179556.16 | 5156325.05 | 27503558.41 | 281361.74 | 0.341936E+09 | 22207.67 | 0.47 |
August | 46428305.35 | 0.282819E+09 | 52924.75 | 5985978.16 | 13110564.69 | 743138.87 | 0.412930E+09 | 9554.84 | 0.47 |
September | 0.112309E+09 | 0.100609E+09 | 8679.94 | 7567169.91 | 6075424.97 | 0.107210E+09 | 0.751802E+09 | 5162.41 | 0.47 |
October | 0.502371E+09 | 1597200.18 | 0.00 | 4980728.50 | 17103.52 | 0.142670E+10 | 0.835204E+09 | 0.00 | 0.47 |
November | 0.667936E+09 | 0.00 | 0.00 | 1947394.76 | 0.00 | 0.211058E+10 | 0.531092E+09 | 0.00 | 0.47 |
December | 0.676161E+09 | 0.00 | 0.00 | 845723.35 | 0.00 | 0.311354E+10 | 0.232391E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.504172E+10 | 0.109823E+10 | 309656.99 | 53056553.66 | 62792762.57 | 0.152181E+11 | 0.700079E+10 | 44370.68 | 0.47 |
Minimum of Months | 17466143.18 | 0.00 | 0.00 | 845723.35 | 0.00 | 281361.74 | 0.232391E+09 | 0.00 | 0.47 |
Maximum of Months | 0.799753E+09 | 0.391111E+09 | 179556.16 | 8766131.28 | 27503558.41 | 0.311354E+10 | 0.121113E+10 | 22207.67 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243818E+11 | 0.00 | 0.00 | 0.112377E+09 | 0.00 | 0.865877E+09 | 0.258296E+11 | 0.00 | 0.54 |
February | 0.265209E+11 | 0.00 | 0.00 | 79066445.77 | 0.00 | 0.306892E+10 | 0.181803E+11 | 0.00 | 0.54 |
March | 0.270632E+11 | 0.00 | 0.00 | 75393825.82 | 0.00 | 12892152.10 | 0.148270E+11 | 0.00 | 0.54 |
April | 0.273354E+11 | 0.00 | 0.00 | 35703921.03 | 0.00 | 0.00 | 0.107218E+11 | 0.00 | 0.54 |
May | 0.647426E+10 | 0.217280E+09 | 0.00 | 77520531.44 | 0.00 | 0.00 | 0.166508E+11 | 0.00 | 0.54 |
June | 0.250017E+09 | 0.436863E+10 | 0.00 | 48693278.97 | 0.00 | 0.00 | 0.617699E+10 | 0.00 | 0.54 |
July | 0.169145E+09 | 0.567814E+10 | 0.00 | 41678192.77 | 0.00 | 0.00 | 0.473553E+10 | 0.00 | 0.53 |
August | 0.111506E+09 | 0.401284E+10 | 0.00 | 59588536.05 | 103026.47 | 0.00 | 0.614793E+10 | 0.00 | 0.54 |
September | 0.147469E+10 | 0.144658E+10 | 0.00 | 95756254.17 | 0.00 | 0.00 | 0.117009E+11 | 0.00 | 0.53 |
October | 0.156375E+11 | 21886070.74 | 0.00 | 0.117477E+09 | 0.00 | 0.133843E+10 | 0.204511E+11 | 0.00 | 0.54 |
November | 0.220205E+11 | 0.00 | 0.00 | 0.112863E+09 | 0.00 | 0.102888E+10 | 0.217345E+11 | 0.00 | 0.54 |
December | 0.303000E+11 | 0.00 | 0.00 | 80255210.12 | 0.00 | 0.717312E+10 | 0.169880E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.181739E+12 | 0.157453E+11 | 0.00 | 0.936374E+09 | 103026.47 | 0.134881E+11 | 0.174144E+12 | 0.00 | 0.54 |
Minimum of Months | 0.111506E+09 | 0.00 | 0.00 | 35703921.03 | 0.00 | 0.00 | 0.473553E+10 | 0.00 | 0.53 |
Maximum of Months | 0.303000E+11 | 0.567814E+10 | 0.00 | 0.117477E+09 | 103026.47 | 0.717312E+10 | 0.258296E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122190E+11 | 0.00 | 0.00 | 34818906.09 | 0.00 | 0.106790E+11 | 0.282568E+11 | 0.00 | 0.54 |
February | 0.116912E+11 | 0.00 | 0.00 | 28193422.23 | 0.00 | 0.134224E+11 | 0.227074E+11 | 0.00 | 0.54 |
March | 0.100148E+11 | 0.00 | 0.00 | 59325343.95 | 0.00 | 0.340204E+10 | 0.285023E+11 | 0.00 | 0.54 |
April | 0.907140E+10 | 0.00 | 0.00 | 69636397.61 | 0.00 | 0.115312E+10 | 0.277988E+11 | 0.00 | 0.54 |
May | 0.413460E+10 | 0.188223E+09 | 209697.39 | 0.118892E+09 | 28822982.70 | 37516078.06 | 0.189116E+11 | 24587.92 | 0.53 |
June | 0.434634E+09 | 0.378459E+10 | 1838791.47 | 76239594.18 | 0.582044E+09 | 2723716.34 | 0.596210E+10 | 158109.21 | 0.53 |
July | 0.277014E+09 | 0.484074E+10 | 1208756.71 | 66294365.40 | 0.835975E+09 | 1763409.57 | 0.460128E+10 | 208326.11 | 0.53 |
August | 0.753134E+09 | 0.350789E+10 | 789285.12 | 74703795.42 | 0.504182E+09 | 5037613.70 | 0.548615E+10 | 84660.04 | 0.53 |
September | 0.175129E+10 | 0.116152E+10 | 1926955.27 | 95369985.17 | 0.282950E+09 | 19164248.92 | 0.114055E+11 | 183811.55 | 0.53 |
October | 0.873199E+10 | 10527504.11 | 149095.73 | 72988631.23 | 11174209.46 | 0.272637E+10 | 0.260131E+11 | 35261.44 | 0.53 |
November | 0.106762E+11 | 0.00 | 0.00 | 44320290.30 | 0.00 | 0.549121E+10 | 0.286851E+11 | 0.00 | 0.54 |
December | 0.126307E+11 | 0.00 | 0.00 | 28598909.41 | 0.00 | 0.178205E+11 | 0.240616E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.823860E+11 | 0.134935E+11 | 6122581.68 | 0.769382E+09 | 0.224515E+10 | 0.547608E+11 | 0.232392E+12 | 694756.26 | 0.53 |
Minimum of Months | 0.277014E+09 | 0.00 | 0.00 | 28193422.23 | 0.00 | 1763409.57 | 0.460128E+10 | 0.00 | 0.53 |
Maximum of Months | 0.126307E+11 | 0.484074E+10 | 1926955.27 | 0.118892E+09 | 0.835975E+09 | 0.178205E+11 | 0.286851E+11 | 208326.11 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.602629E+09 | 0.00 | 0.00 | 4526142.13 | 0.00 | 0.208994E+10 | 0.107862E+10 | 0.00 | 0.47 |
February | 0.552651E+09 | 0.00 | 0.00 | 4860165.25 | 0.00 | 0.194625E+10 | 0.102556E+10 | 0.00 | 0.47 |
March | 0.529381E+09 | 0.00 | 0.00 | 7503399.24 | 0.00 | 0.143716E+10 | 0.112227E+10 | 0.00 | 0.47 |
April | 0.510192E+09 | 0.00 | 0.00 | 6093840.30 | 0.00 | 0.127329E+10 | 0.102014E+10 | 0.00 | 0.47 |
May | 0.186840E+09 | 15456335.13 | 0.00 | 10647592.67 | 570104.08 | 0.189170E+09 | 0.132475E+10 | 0.00 | 0.47 |
June | 7593763.42 | 0.311402E+09 | 50181.03 | 8506765.85 | 10774404.26 | 93909.69 | 0.461449E+09 | 841.44 | 0.47 |
July | 7193938.62 | 0.404096E+09 | 148194.76 | 6717917.66 | 14566477.73 | 79672.93 | 0.350848E+09 | 5047.83 | 0.47 |
August | 14609474.30 | 0.288084E+09 | 45056.10 | 9210660.09 | 7862348.06 | 220163.97 | 0.442047E+09 | 781.90 | 0.47 |
September | 64446274.08 | 0.102483E+09 | 0.00 | 10946679.16 | 4215723.58 | 79488730.84 | 0.824006E+09 | 59.96 | 0.47 |
October | 0.346416E+09 | 1597200.18 | 0.00 | 8729328.57 | 17103.52 | 0.117147E+10 | 0.124264E+10 | 0.00 | 0.47 |
November | 0.532951E+09 | 0.00 | 0.00 | 5454278.20 | 0.00 | 0.164108E+10 | 0.113207E+10 | 0.00 | 0.47 |
December | 0.685361E+09 | 0.00 | 0.00 | 3297847.69 | 0.00 | 0.261897E+10 | 0.715315E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.404026E+10 | 0.112312E+10 | 243431.89 | 86494616.81 | 38006161.23 | 0.124472E+11 | 0.107397E+11 | 6731.13 | 0.47 |
Minimum of Months | 7193938.62 | 0.00 | 0.00 | 3297847.69 | 0.00 | 79672.93 | 0.350848E+09 | 0.00 | 0.47 |
Maximum of Months | 0.685361E+09 | 0.404096E+09 | 148194.76 | 10946679.16 | 14566477.73 | 0.261897E+10 | 0.132475E+10 | 5047.83 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.801642E+09 | 0.00 | 0.00 | 1131489.11 | 0.00 | 0.259161E+10 | 0.381330E+09 | 0.00 | 0.47 |
February | 0.678524E+09 | 0.00 | 0.00 | 1946532.81 | 0.00 | 0.237245E+10 | 0.476411E+09 | 0.00 | 0.47 |
March | 0.613709E+09 | 0.00 | 0.00 | 4631400.38 | 0.00 | 0.166229E+10 | 0.815682E+09 | 0.00 | 0.47 |
April | 0.559555E+09 | 0.00 | 0.00 | 4941507.60 | 0.00 | 0.138240E+10 | 0.862822E+09 | 0.00 | 0.47 |
May | 0.202697E+09 | 15421692.84 | 0.00 | 10107191.30 | 604746.37 | 0.214165E+09 | 0.128444E+10 | 0.00 | 0.47 |
June | 7654542.20 | 0.311122E+09 | 50093.19 | 8439379.18 | 11054194.05 | 93909.69 | 0.461456E+09 | 929.28 | 0.47 |
July | 7593063.88 | 0.403066E+09 | 147326.75 | 6652407.57 | 15597051.25 | 147338.39 | 0.350447E+09 | 5915.84 | 0.47 |
August | 16006189.90 | 0.286950E+09 | 67333.57 | 8691888.69 | 8972596.59 | 220163.97 | 0.441169E+09 | 2168.87 | 0.47 |
September | 78378102.38 | 0.100755E+09 | 5132.19 | 9075334.37 | 5937732.17 | 96838314.68 | 0.794596E+09 | 631.41 | 0.47 |
October | 0.497305E+09 | 1597200.18 | 0.00 | 4781028.08 | 17103.52 | 0.143897E+10 | 0.828202E+09 | 0.00 | 0.47 |
November | 0.689650E+09 | 0.00 | 0.00 | 1756507.02 | 0.00 | 0.216095E+10 | 0.459196E+09 | 0.00 | 0.47 |
December | 0.675497E+09 | 0.00 | 0.00 | 762474.00 | 0.00 | 0.310583E+10 | 0.240851E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.482821E+10 | 0.111891E+10 | 269885.70 | 62917140.10 | 42183423.96 | 0.150260E+11 | 0.739660E+10 | 9645.41 | 0.47 |
Minimum of Months | 7593063.88 | 0.00 | 0.00 | 762474.00 | 0.00 | 93909.69 | 0.240851E+09 | 0.00 | 0.47 |
Maximum of Months | 0.801642E+09 | 0.403066E+09 | 147326.75 | 10107191.30 | 15597051.25 | 0.310583E+10 | 0.128444E+10 | 5915.84 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100078E+11 | 0.00 | 0.00 | 0.90 |
February | 0.152863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118034E+11 | 0.00 | 0.00 | 0.90 |
March | 0.175988E+11 | 0.00 | 0.00 | 0.00 | 2301116.89 | 0.101279E+11 | 0.00 | 0.00 | 0.90 |
April | 0.185731E+11 | 0.00 | 0.00 | 0.00 | 507847.40 | 0.742198E+10 | 0.00 | 0.00 | 0.90 |
May | 0.207859E+11 | 0.00 | 0.00 | 0.00 | 0.166606E+09 | 0.687425E+09 | 0.00 | 0.00 | 0.89 |
June | 0.768321E+10 | 0.00 | 0.00 | 0.00 | 0.248475E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.541272E+10 | 0.00 | 0.00 | 0.00 | 0.385396E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.757994E+10 | 0.00 | 0.00 | 0.00 | 0.256127E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
September | 0.129868E+11 | 0.00 | 0.00 | 0.00 | 0.859642E+09 | 0.242204E+09 | 0.00 | 0.00 | 0.89 |
October | 0.203422E+11 | 0.00 | 0.00 | 0.00 | 22700896.23 | 0.626738E+10 | 0.00 | 0.00 | 0.89 |
November | 0.189615E+11 | 0.00 | 0.00 | 0.00 | 14841.17 | 0.858878E+10 | 0.00 | 0.00 | 0.90 |
December | 0.145823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167187E+11 | 0.00 | 0.00 | 0.89 |
Annual Sum or Average | 0.179494E+12 | 0.00 | 0.00 | 0.00 | 0.995176E+10 | 0.718655E+11 | 0.00 | 0.00 | 0.89 |
Minimum of Months | 0.541272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.207859E+11 | 0.00 | 0.00 | 0.00 | 0.385396E+10 | 0.167187E+11 | 0.00 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151521E+09 | 0.00 | 0.00 | 1081254.40 | 0.00 | 0.587584E+09 | 0.203743E+09 | 0.00 | 0.47 |
February | 0.133559E+09 | 0.00 | 0.00 | 1086800.03 | 0.00 | 0.558245E+09 | 0.189441E+09 | 0.00 | 0.47 |
March | 0.114406E+09 | 0.00 | 0.00 | 1886125.37 | 0.00 | 0.445927E+09 | 0.211858E+09 | 0.00 | 0.47 |
April | 0.125571E+09 | 0.00 | 0.00 | 1458557.24 | 0.00 | 0.388624E+09 | 0.186776E+09 | 0.00 | 0.47 |
May | 50065784.32 | 3932861.47 | 0.00 | 2630160.24 | 73748.33 | 85292171.84 | 0.289864E+09 | 0.00 | 0.47 |
June | 6162142.51 | 78158113.24 | 17084.72 | 1737144.49 | 2380668.27 | 99979.84 | 0.111412E+09 | 969.57 | 0.47 |
July | 3836856.23 | 0.100954E+09 | 12573.30 | 1430912.10 | 3734303.39 | 61554.41 | 85880664.01 | 3465.18 | 0.47 |
August | 9299141.06 | 72267672.43 | 4318.69 | 1810168.42 | 1724489.43 | 178074.54 | 0.105235E+09 | 1590.10 | 0.47 |
September | 21175711.23 | 26009332.27 | 1010.88 | 2547334.30 | 663319.89 | 28646510.29 | 0.192352E+09 | 1023.80 | 0.47 |
October | 73189968.49 | 399761.47 | 0.00 | 2298497.18 | 3814.46 | 0.367193E+09 | 0.249633E+09 | 0.00 | 0.47 |
November | 0.124754E+09 | 0.00 | 0.00 | 1394970.03 | 0.00 | 0.480209E+09 | 0.221532E+09 | 0.00 | 0.47 |
December | 0.152700E+09 | 0.00 | 0.00 | 748249.94 | 0.00 | 0.721495E+09 | 0.130792E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.966240E+09 | 0.281721E+09 | 34987.57 | 20110173.72 | 8580343.77 | 0.366356E+10 | 0.217852E+10 | 7048.66 | 0.47 |
Minimum of Months | 3836856.23 | 0.00 | 0.00 | 748249.94 | 0.00 | 61554.41 | 85880664.01 | 0.00 | 0.47 |
Maximum of Months | 0.152700E+09 | 0.100954E+09 | 17084.72 | 2630160.24 | 3734303.39 | 0.721495E+09 | 0.289864E+09 | 3465.18 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170414E+09 | 0.00 | 0.00 | 307673.54 | 0.00 | 0.718723E+09 | 54484994.00 | 0.00 | 0.47 |
February | 0.146557E+09 | 0.00 | 0.00 | 396425.76 | 0.00 | 0.663433E+09 | 71945687.00 | 0.00 | 0.47 |
March | 0.132174E+09 | 0.00 | 0.00 | 1203481.92 | 0.00 | 0.495659E+09 | 0.145040E+09 | 0.00 | 0.47 |
April | 0.134326E+09 | 0.00 | 0.00 | 1170691.89 | 0.00 | 0.415314E+09 | 0.151618E+09 | 0.00 | 0.47 |
May | 53418231.18 | 3930614.70 | 0.00 | 2496339.99 | 75995.10 | 92585220.95 | 0.279353E+09 | 0.00 | 0.47 |
June | 6161473.81 | 78118886.75 | 13432.40 | 1722749.71 | 2423828.49 | 99854.17 | 0.111427E+09 | 688.16 | 0.47 |
July | 3865420.37 | 0.100749E+09 | 18328.67 | 1414958.95 | 3933021.25 | 61554.41 | 85868053.02 | 3479.08 | 0.47 |
August | 9677462.42 | 72031068.22 | 4203.60 | 1684957.98 | 1961093.64 | 178713.96 | 0.104981E+09 | 1705.19 | 0.47 |
September | 25437130.77 | 25625464.94 | 752.08 | 2102149.64 | 1047187.21 | 39917149.37 | 0.177266E+09 | 1282.59 | 0.47 |
October | 0.105412E+09 | 399300.05 | 0.00 | 1350767.13 | 4275.88 | 0.423715E+09 | 0.161836E+09 | 0.00 | 0.47 |
November | 0.150013E+09 | 0.00 | 0.00 | 480997.55 | 0.00 | 0.595474E+09 | 81921078.21 | 0.00 | 0.47 |
December | 0.135913E+09 | 0.00 | 0.00 | 195172.97 | 0.00 | 0.832877E+09 | 36749971.47 | 0.00 | 0.47 |
Annual Sum or Average | 0.107337E+10 | 0.280854E+09 | 36716.76 | 14526367.04 | 9445401.57 | 0.427804E+10 | 0.146249E+10 | 7155.02 | 0.47 |
Minimum of Months | 3865420.37 | 0.00 | 0.00 | 195172.97 | 0.00 | 61554.41 | 36749971.47 | 0.00 | 0.47 |
Maximum of Months | 0.170414E+09 | 0.100749E+09 | 18328.67 | 2496339.99 | 3933021.25 | 0.832877E+09 | 0.279353E+09 | 3479.08 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.653921E+09 | 0.00 | 0.00 | 21453680.71 | 0.00 | 0.201156E+10 | 0.337500E+10 | 0.00 | 0.54 |
February | 0.582397E+09 | 0.00 | 0.00 | 16585010.12 | 0.00 | 0.229751E+10 | 0.276986E+10 | 0.00 | 0.54 |
March | 0.708627E+09 | 0.00 | 0.00 | 15721243.71 | 0.00 | 0.196115E+10 | 0.228564E+10 | 0.00 | 0.54 |
April | 0.848031E+09 | 0.00 | 0.00 | 8868130.93 | 0.00 | 0.171400E+10 | 0.194011E+10 | 0.00 | 0.54 |
May | 0.331797E+09 | 24866655.71 | 987.23 | 14623597.45 | 862678.91 | 0.226128E+09 | 0.217513E+10 | 195.14 | 0.53 |
June | 41718203.34 | 0.494129E+09 | 201956.12 | 9561797.90 | 22978463.37 | 1300292.45 | 0.714279E+09 | 27971.27 | 0.53 |
July | 25898637.45 | 0.642219E+09 | 331818.67 | 8245681.12 | 29824479.98 | 189650.85 | 0.551418E+09 | 35071.96 | 0.53 |
August | 59005480.94 | 0.460893E+09 | 32788.87 | 10851627.39 | 14283754.14 | 1015184.50 | 0.677433E+09 | 7387.90 | 0.53 |
September | 0.113217E+09 | 0.166930E+09 | 18452.20 | 17657799.91 | 4352290.58 | 80495506.36 | 0.136024E+10 | 4273.64 | 0.53 |
October | 0.544334E+09 | 2570466.89 | 0.00 | 21596459.80 | 21304.65 | 0.127440E+10 | 0.260573E+10 | 0.00 | 0.53 |
November | 0.575478E+09 | 0.00 | 0.00 | 22078288.06 | 0.00 | 0.161620E+10 | 0.310297E+10 | 0.00 | 0.54 |
December | 0.783215E+09 | 0.00 | 0.00 | 16776099.18 | 0.00 | 0.290713E+10 | 0.275173E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.526764E+10 | 0.179161E+10 | 586003.08 | 0.184019E+09 | 72322971.64 | 0.140911E+11 | 0.243095E+11 | 74899.93 | 0.53 |
Minimum of Months | 25898637.45 | 0.00 | 0.00 | 8245681.12 | 0.00 | 189650.85 | 0.551418E+09 | 0.00 | 0.53 |
Maximum of Months | 0.848031E+09 | 0.642219E+09 | 331818.67 | 22078288.06 | 29824479.98 | 0.290713E+10 | 0.337500E+10 | 35071.96 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.395703E+11 | 0.00 | 0.00 | 7923292.97 | 0.00 | 0.00 | 0.301371E+11 | 0.00 | 9.93 |
February | 0.354238E+11 | 0.00 | 0.00 | 6806997.66 | 0.00 | 0.00 | 0.281378E+11 | 0.00 | 9.89 |
March | 0.318456E+11 | 0.00 | 0.00 | 10832312.75 | 5399769.60 | 0.00 | 0.332068E+11 | 0.00 | 9.91 |
April | 0.273288E+11 | 0.00 | 0.00 | 11363331.63 | 1191707.81 | 0.00 | 0.336595E+11 | 0.00 | 9.91 |
May | 0.157428E+11 | 71981429.30 | 0.00 | 14204502.90 | 0.318973E+09 | 0.00 | 0.346320E+11 | 0.00 | 9.86 |
June | 0.288377E+10 | 0.185421E+10 | 0.00 | 10300098.13 | 0.397647E+10 | 0.00 | 0.151352E+11 | 0.00 | 9.85 |
July | 0.166679E+10 | 0.323778E+10 | 0.00 | 8418071.25 | 0.580587E+10 | 0.00 | 0.110262E+11 | 0.00 | 9.82 |
August | 0.424073E+10 | 0.255286E+10 | 0.00 | 8610911.54 | 0.345739E+10 | 0.00 | 0.135377E+11 | 0.00 | 9.83 |
September | 0.801971E+10 | 0.426030E+09 | 0.00 | 10839385.46 | 0.159119E+10 | 0.00 | 0.230126E+11 | 0.00 | 9.81 |
October | 0.279487E+11 | 3364452.35 | 0.00 | 11109590.36 | 49905161.89 | 0.00 | 0.344818E+11 | 0.00 | 9.86 |
November | 0.342355E+11 | 0.00 | 0.00 | 8610360.86 | 34826.09 | 0.00 | 0.304049E+11 | 0.00 | 9.90 |
December | 0.463545E+11 | 0.00 | 0.00 | 6837995.31 | 0.00 | 0.00 | 0.270892E+11 | 0.00 | 9.86 |
Annual Sum or Average | 0.275261E+12 | 0.814623E+10 | 0.00 | 0.115857E+09 | 0.152064E+11 | 0.00 | 0.314461E+12 | 0.00 | 9.87 |
Minimum of Months | 0.166679E+10 | 0.00 | 0.00 | 6806997.66 | 0.00 | 0.00 | 0.110262E+11 | 0.00 | 9.81 |
Maximum of Months | 0.463545E+11 | 0.323778E+10 | 0.00 | 14204502.90 | 0.580587E+10 | 0.00 | 0.346320E+11 | 0.00 | 9.93 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371590E+11 | 0.00 | 0.00 | 10398741.86 | 0.00 | 0.00 | 0.360121E+11 | 0.00 | 10.42 |
February | 0.337344E+11 | 0.00 | 0.00 | 9040424.98 | 0.00 | 0.00 | 0.329855E+11 | 0.00 | 10.38 |
March | 0.290484E+11 | 0.00 | 0.00 | 14083683.66 | 5668241.56 | 0.00 | 0.392356E+11 | 0.00 | 10.41 |
April | 0.254757E+11 | 0.00 | 0.00 | 14810356.50 | 1250958.51 | 0.00 | 0.385420E+11 | 0.00 | 10.40 |
May | 0.137682E+11 | 0.138540E+09 | 0.00 | 17849529.07 | 0.271852E+09 | 0.00 | 0.391083E+11 | 0.00 | 10.35 |
June | 0.183615E+10 | 0.271983E+10 | 0.00 | 12247547.75 | 0.340075E+10 | 0.00 | 0.170773E+11 | 0.00 | 10.34 |
July | 0.114214E+10 | 0.457097E+10 | 0.00 | 10061193.65 | 0.492231E+10 | 0.00 | 0.121807E+11 | 0.00 | 10.31 |
August | 0.323212E+10 | 0.333530E+10 | 0.00 | 10314074.53 | 0.297377E+10 | 0.00 | 0.154289E+11 | 0.00 | 10.31 |
September | 0.661310E+10 | 0.711054E+09 | 0.00 | 13265428.91 | 0.140647E+10 | 0.00 | 0.259602E+11 | 0.00 | 10.29 |
October | 0.264700E+11 | 3531730.06 | 0.00 | 14355120.48 | 52386404.22 | 0.00 | 0.390618E+11 | 0.00 | 10.35 |
November | 0.313953E+11 | 0.00 | 0.00 | 11274021.37 | 36557.61 | 0.00 | 0.364568E+11 | 0.00 | 10.40 |
December | 0.432139E+11 | 0.00 | 0.00 | 9015037.81 | 0.00 | 0.00 | 0.338796E+11 | 0.00 | 10.35 |
Annual Sum or Average | 0.253088E+12 | 0.114792E+11 | 0.00 | 0.146715E+09 | 0.130345E+11 | 0.00 | 0.365929E+12 | 0.00 | 10.36 |
Minimum of Months | 0.114214E+10 | 0.00 | 0.00 | 9015037.81 | 0.00 | 0.00 | 0.121807E+11 | 0.00 | 10.29 |
Maximum of Months | 0.432139E+11 | 0.457097E+10 | 0.00 | 17849529.07 | 0.492231E+10 | 0.00 | 0.392356E+11 | 0.00 | 10.42 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.109976E+09 | 0.00 | 0.00 | 0.707548E+11 | 0.00 | 32.58 |
February | 0.00 | 0.00 | 0.00 | 0.101470E+09 | 0.00 | 0.00 | 0.645264E+11 | 0.00 | 32.48 |
March | 0.00 | 5476357.49 | 0.00 | 0.112856E+09 | 0.00 | 0.00 | 0.660366E+11 | 0.00 | 32.52 |
April | 0.00 | 1208610.45 | 0.00 | 0.105771E+09 | 0.00 | 0.00 | 0.619045E+11 | 0.00 | 32.49 |
May | 0.00 | 0.396500E+09 | 0.00 | 0.100625E+09 | 0.00 | 0.00 | 0.510751E+11 | 0.00 | 32.27 |
June | 0.00 | 0.591339E+10 | 0.00 | 43190406.67 | 0.00 | 0.00 | 0.182436E+11 | 0.00 | 32.17 |
July | 0.00 | 0.917192E+10 | 0.00 | 34816739.88 | 0.00 | 0.00 | 0.128467E+11 | 0.00 | 32.08 |
August | 0.00 | 0.609549E+10 | 0.00 | 49342324.22 | 0.00 | 0.00 | 0.179902E+11 | 0.00 | 32.10 |
September | 0.00 | 0.204584E+10 | 0.00 | 71291327.10 | 0.00 | 0.00 | 0.314225E+11 | 0.00 | 32.04 |
October | 0.00 | 54025166.42 | 0.00 | 0.110330E+09 | 0.00 | 0.00 | 0.633460E+11 | 0.00 | 32.31 |
November | 0.00 | 35320.04 | 0.00 | 0.107889E+09 | 0.00 | 0.00 | 0.656201E+11 | 0.00 | 32.50 |
December | 28966680.88 | 0.00 | 0.00 | 0.105751E+09 | 0.00 | 0.00 | 0.744745E+11 | 0.00 | 32.32 |
Annual Sum or Average | 28966680.88 | 0.236839E+11 | 0.00 | 0.105331E+10 | 0.00 | 0.00 | 0.598241E+12 | 0.00 | 32.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34816739.88 | 0.00 | 0.00 | 0.128467E+11 | 0.00 | 32.04 |
Maximum of Months | 28966680.88 | 0.917192E+10 | 0.00 | 0.112856E+09 | 0.00 | 0.00 | 0.744745E+11 | 0.00 | 32.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.814102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111187E+11 | 0.00 | 0.00 | 2.20 |
February | 0.736866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101929E+11 | 0.00 | 0.00 | 2.19 |
March | 0.951334E+10 | 0.00 | 0.00 | 0.00 | 1491755.20 | 0.846118E+10 | 0.00 | 0.00 | 2.20 |
April | 0.979982E+10 | 0.00 | 0.00 | 0.00 | 329224.48 | 0.705212E+10 | 0.00 | 0.00 | 2.20 |
May | 0.129769E+11 | 0.00 | 0.00 | 0.00 | 0.108006E+09 | 0.943739E+09 | 0.00 | 0.00 | 2.19 |
June | 0.498083E+10 | 0.00 | 0.00 | 0.00 | 0.161080E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
July | 0.350892E+10 | 0.00 | 0.00 | 0.00 | 0.249842E+10 | 0.00 | 0.00 | 0.00 | 2.18 |
August | 0.491388E+10 | 0.00 | 0.00 | 0.00 | 0.166041E+10 | 0.00 | 0.00 | 0.00 | 2.18 |
September | 0.810622E+10 | 0.00 | 0.00 | 0.00 | 0.557284E+09 | 0.469839E+09 | 0.00 | 0.00 | 2.18 |
October | 0.106824E+11 | 0.00 | 0.00 | 0.00 | 14716410.14 | 0.656793E+10 | 0.00 | 0.00 | 2.19 |
November | 0.913759E+10 | 0.00 | 0.00 | 0.00 | 9621.15 | 0.872254E+10 | 0.00 | 0.00 | 2.20 |
December | 0.623011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140615E+11 | 0.00 | 0.00 | 2.19 |
Annual Sum or Average | 0.953596E+11 | 0.00 | 0.00 | 0.00 | 0.645147E+10 | 0.675905E+11 | 0.00 | 0.00 | 2.19 |
Minimum of Months | 0.350892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 |
Maximum of Months | 0.129769E+11 | 0.00 | 0.00 | 0.00 | 0.249842E+10 | 0.140615E+11 | 0.00 | 0.00 | 2.20 |