Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:46:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11679.64 | 1029.47 | 1029.47 |
Net Site Energy | 11679.64 | 1029.47 | 1029.47 |
Total Source Energy | 24243.38 | 2136.87 | 2136.87 |
Net Source Energy | 24243.38 | 2136.87 | 2136.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2050.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 793.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 766.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 226.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.02 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 982.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 577.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 81.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 234.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2279.84 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5560.56 | 6119.07 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2050.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 793.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 766.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 226.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 577.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 81.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 234.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.76 | 2279.84 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 87.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.06 | 381.68 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 266.51 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 490.12 | 539.35 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 87.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.06 | 381.68 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 266.51 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 490.12 | 539.35 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5560.564 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5560.564 | 100.00 |
Total On-Site and Utility Electric Sources | 5560.564 | 100.00 |
Total Electricity End Uses | 5560.564 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 327.34 | 6.52 |
Air to Air Heat Recovery for Heating | 4697.02 | 93.48 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5024.36 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 273.67 |
Time Setpoint Not Met During Occupied Cooling | 414.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8042.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.4281 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 12.2063 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 12.2063 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 10.2688 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 6.3938 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 6.8961 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 6.8961 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:00 | 02-FEB-18:00 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 768806.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161734.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50900.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24684.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4726.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3530.11 | 178952.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2394.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 428348.13 | 1052007.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 768806.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 161734.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1860.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 24684.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4726.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3530.11 | 178952.56 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1091.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2222.61 | 0.00 | 0.00 | 0.00 |
Cooling | 2513.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2428.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 717.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.49 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3112.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1830.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 257.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 742.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.44 | 2471.34 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17610.31 | 6633.07 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 195.91 | 0.00 | 0.00 | 0.00 |
Cooling | 221.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 63.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 65.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1552.21 | 584.65 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 195.91 | 0.00 | 0.00 | 0.00 |
Cooling | 221.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 63.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 65.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1552.21 | 584.65 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.47 | 0.610325 | 0.562000 | 1.39 | 1.00 | 0.500000 | 0.000624 | 0.000197 | 1.39 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.321567 | 0.158935 | 0.562000 | 0.180721 | 0.562000 | 0.500000 | 0.002397 | 0.000117 | 0.194730 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.232504 | 0.254549 | 0.562000 | 0.130667 | 0.678798 | 0.500000 | 0.001497 | 0.000040 | 0.130667 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.216243 | 0.578763 | 0.562000 | 0.121529 | 1.00 | 0.500000 | 0.000658 | 0.000057 | 0.121529 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.100809 | 0.716270 | 0.562000 | 0.056655 | 1.00 | 0.500000 | 0.000532 | 0.000037 | 0.061605 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.069158 | 0.562000 | 1.92 | 0.562000 | 0.500000 | 0.021861 | 0.000272 | 1.92 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.38 | 0.104565 | 0.562000 | 0.773479 | 0.562000 | 0.500000 | 0.003644 | 0.000336 | 0.773479 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.72 | 0.211240 | 0.562000 | 2.65 | 0.563307 | 0.500000 | 0.001804 | 0.000808 | 2.65 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.562000 | 0.667041 | 1.00 | 0.500000 | 0.000381 | 0.000332 | 0.667041 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.18 | 0.115961 | 0.562000 | 1.22 | 0.562000 | 0.500000 | 0.003286 | 0.000310 | 1.22 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.29 | 0.110389 | 0.562000 | 1.29 | 0.562000 | 0.500000 | 0.003451 | 0.000320 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.35 | 0.700000 | 0.562000 | 1.32 | 0.562000 | 0.500000 | 0.011397 | 0.000214 | 1.32 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.594731 | 0.528035 | 0.562000 | 0.334239 | 1.00 | 0.500000 | 0.000722 | 0.000225 | 0.372552 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8929.18 | 0.000197 | 160.50 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5312.85 | 0.000117 | 115.16 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1795.93 | 0.000040 | 35.02 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2583.25 | 0.000057 | 53.15 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1680.69 | 0.000037 | 36.43 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12292.69 | 0.000272 | 220.91 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15185.93 | 0.000336 | 308.46 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 36592.43 | 0.000808 | 713.76 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 7884.02 | 0.000174 | 179.49 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 7905.73 | 0.000175 | 179.99 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 44442.20 | 0.000982 | 1011.80 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 44830.42 | 0.000990 | 1020.64 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 7845.60 | 0.000173 | 178.62 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 7867.21 | 0.000174 | 179.11 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15045.76 | 0.000332 | 312.82 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 2410.70 | 0.000053 | 54.88 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 2423.05 | 0.000054 | 55.16 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 11506.27 | 0.000254 | 261.95 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14046.97 | 0.000310 | 267.87 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14501.07 | 0.000320 | 275.86 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9695.18 | 0.000214 | 176.06 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10165.62 | 0.000225 | 220.35 |
VAV WITH REHEAT_HEATC | 313103.44 | 0.006918 | 3986.66 |
FLR_3_DOAS_HEATC | 30467.96 | 0.000673 | 387.94 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.11 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.09 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.26 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.39 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.989494 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.983266 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.288939 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.283896 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.09 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.11 | 0.000174 | 0.000437 |
ROOM_2_FLR_3 FAN COIL | 1.09 | 0.000175 | 0.000430 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.26 | 0.000982 | 0.002043 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.39 | 0.000990 | 0.002239 |
ROOM_5_FLR_3 FAN COIL | 0.989494 | 0.000173 | 0.000392 |
ROOM_6_FLR_3 FAN COIL | 0.983266 | 0.000174 | 0.000390 |
ROOM_1_FLR_6 FAN COIL | 0.288939 | 0.000053 | 0.000114 |
ROOM_2_FLR_6 FAN COIL | 0.283896 | 0.000054 | 0.000112 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.09 | 0.000254 | 0.000440 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.11 |
ROOM_2_FLR_3 FAN COILFAN | 1.09 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.26 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.39 |
ROOM_5_FLR_3 FAN COILFAN | 0.989494 |
ROOM_6_FLR_3 FAN COILFAN | 0.983266 |
ROOM_1_FLR_6 FAN COILFAN | 0.288939 |
ROOM_2_FLR_6 FAN COILFAN | 0.283896 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.09 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000437 | 1.11 | 0.008697 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000430 | 1.09 | 0.008700 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002043 | 5.26 | 0.008644 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002239 | 5.39 | 0.008910 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000392 | 0.989494 | 0.008724 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000390 | 0.983266 | 0.008726 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000114 | 0.288939 | 0.008690 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000112 | 0.283896 | 0.008693 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000440 | 1.09 | 0.008809 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.024997 | 0.012937 | 28.11 | 6.70 | 10.90 | 0.008683 | 699860.56 | 21.08 | |
FLR_3_DOAS_COOLC | 0.003132 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 87700.73 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.06 | 12.06 | 21.45 | 12.06 | 21.08 | 21.08 | 0.300000 | 0.572003 | 21.08 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.08 | 12.05 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 12.05 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 21.08 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024997 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.006918 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003132 | 0.000152 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000673 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.034726 | 8317.29 |
HEATSYS1 PUMP | 0.013886 | 3547.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.013886 | 1.67 |
COOLSYS1 | 0.034726 | 4.17 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.034726 | 2772.43 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 628514.15 | 628514.15 | 0.013886 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.034726 | 972249.25 | 972845.09 | 110.90 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.428 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.808 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 12.206 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.966 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 12.206 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.966 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.269 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.339 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 16677.861 | 8.428 | 156.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16677.861 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 818.691 | 12.206 | 75.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 818.691 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 948.048 | 12.206 | 75.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 948.048 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1511.554 | 9.203 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.554 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 578.329 | 6.103 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1957.675 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.675 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 13433.463 | 10.269 | 31.800 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13433.463 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.461 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2489.761 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.761 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.461 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.844 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.844 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 3437.844 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.844 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.924 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.924 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2635.028 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.028 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4874 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.884 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.22071239E-14 | -0.25891382E-15 | -0.17018650E-09 | -0.41695020E-16 |
25 | 8 | 0.24744598E-07 | 0.66649001E-13 | 0.40731198E-03 | -0.28135460E-09 |
26 | 7 | -0.13120292E-01 | 0.33703133E-08 | -0.24350396E-01 | 0.14918252E-03 |
27 | 6 | 0.42922440 | 0.11607716E-05 | 0.49237259 | -0.50291810E-02 |
28 | 5 | -5.4235101 | 0.42968024E-04 | -4.5968048 | 0.66072313E-01 |
29 | 4 | 34.033019 | 0.34874410E-03 | 22.047808 | -0.43580094 |
30 | 3 | -113.41739 | 0.75474606E-03 | -56.824750 | 1.5468526 |
31 | 2 | 199.30218 | 0.42189037E-03 | 78.976973 | -2.9351941 |
32 | 1 | -171.96619 | 0.44777434E-04 | -55.576854 | 2.7596376 |
33 | 0 | 57.057407 | 0.25325413E-06 | 15.506813 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 31 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
2 | RESWINDOW_U_0.37_SHGC_0.4 | 32 | 1 | VerySmooth | 2.102 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.55893E-002 | 0.31435 | 0.48047 | 0.48047 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11739 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 32432.92371 | 32432.92371 | 2.47060 | 2.47060 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.67733 | 1.53444E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 1936.94721 | 1936.94721 | 8.70432E-002 | 0.85413 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4220.42269 | 4220.42269 | 0.32157 | 0.32157 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4333.97666 | 4333.97666 | 0.19473 | 0.19473 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3051.78113 | 3051.78113 | 0.23250 | 0.23250 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53444E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1138.75934 | 1138.75934 | 5.11719E-002 | 9.16993E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2839.03421 | 2839.03421 | 0.21624 | 0.21624 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53444E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1972.21963 | 1972.21963 | 8.86244E-002 | 8.86244E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1323.50590 | 1323.50590 | 0.10081 | 0.10081 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53444E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1370.93121 | 1370.93121 | 6.16047E-002 | 6.16047E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44790.43344 | 44790.43344 | 3.41211 | 3.41211 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53444E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2652.31770 | 2652.31770 | 0.11918 | 0.23597 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18048.43992 | 18048.43992 | 1.37630 | 1.37630 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11297.50826 | 11297.50826 | 0.50762 | 0.67613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61921.86776 | 61921.86776 | 4.71898 | 4.71898 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23256.21167 | 23256.21167 | 1.04504 | 1.89326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10822.06845 | 10822.06845 | 1.11093 | 1.11093 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7884.35973 | 7884.35973 | 0.35636 | 0.35636 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10640.19424 | 10640.19424 | 1.09226 | 1.09226 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7906.07309 | 7906.07309 | 0.35734 | 0.35734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 51272.56149 | 51272.56149 | 5.26289 | 5.26289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 44443.14103 | 44443.14103 | 2.00884 | 2.00884 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 52464.43633 | 52464.43633 | 5.38567 | 5.38567 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 44831.36744 | 44831.36744 | 2.02639 | 2.02639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9639.04204 | 9639.04204 | 0.98949 | 0.98949 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7845.93617 | 7845.93617 | 0.35462 | 0.35462 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9578.36887 | 9578.36887 | 0.98327 | 0.98327 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7867.55497 | 7867.55497 | 0.35560 | 0.35560 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 12417.61239 | 12417.61239 | 0.94580 | 1.18691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11689.40589 | 11689.40589 | 0.52529 | 0.52529 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2814.68045 | 2814.68045 | 0.28894 | 0.28894 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2410.80353 | 2410.80353 | 0.10896 | 0.10896 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2765.55010 | 2765.55010 | 0.28390 | 0.28390 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2423.14639 | 2423.14639 | 0.10952 | 0.10952 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10569.67977 | 10569.67977 | 1.08504 | 1.08504 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11506.64772 | 11506.64772 | 0.52009 | 0.52009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28573.67006 | 28573.67006 | 2.17937 | 2.17937 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7882.98249 | 7882.98249 | 0.35424 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30016.65074 | 30016.65074 | 2.28939 | 2.28939 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8026.08046 | 8026.08046 | 0.36067 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30831.35035 | 30831.35035 | 2.35477 | 2.35477 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53444E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3049.21232 | 3049.21232 | 0.13700 | 0.36721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7808.26914 | 7808.26914 | 0.59473 | 0.59473 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8290.52049 | 8290.52049 | 0.37255 | 0.37255 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 372380.12 | 21.07911 | 21.07911 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 383022.29 | 7.73588 | 7.73588 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43559.48 | 15.19977 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101559.87 | 6.19771 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47060 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61033 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.38848 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.24257E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97279E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38848 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8929.17784 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97279E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.49884 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32157 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15894 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18072 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39720E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17381E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19473 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5312.84831 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17381E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.15518 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23250 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25455 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13067 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67880 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49676E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.96789E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13067 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1795.93053 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.96789E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 35.01940 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21624 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57876 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12153 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.58301E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.70737E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12153 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2583.24585 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70737E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.14611 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10081 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71627 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.66547E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.31922E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.71328E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.16047E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1680.69035 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.71328E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.42828 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.41211 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.91577E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91761 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18615E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71592E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.91761 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12292.69110 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71592E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.90551 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37630 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10457 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77348 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64366E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.35515E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77348 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15185.93057 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35515E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 308.46376 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.71898 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21124 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.65207 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56331 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80364E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.08465E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.65207 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36592.42910 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.08465E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 713.76147 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11093 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11093 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.11093 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74188E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.37311E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.37311E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.11093 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69746E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70996 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7884.01880 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74188E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.49342 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09226 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09226 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09226 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74667E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.30300E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.30300E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.09226 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70043E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70995 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7905.73118 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74667E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.98764 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.26289 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.26289 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.26289 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.81896E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.04281E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.04281E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.26289 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.64449E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.71074 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44442.20386 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.81896E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1011.79985 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.38567 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.38567 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.38567 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.90473E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.23912E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.23912E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.38567 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.90964E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70978 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44830.42281 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.90473E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1020.63679 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98949 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.98949 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.98949 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73339E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.92260E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.92260E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.98949 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.72417E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70990 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7845.59673 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73339E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.61883 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98327 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.98327 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.98327 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73816E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.89953E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.89953E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.98327 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.72575E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70990 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7867.21455 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73816E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.11091 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.66704 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32418E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66704 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15045.75861 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32418E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 312.81929 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28894 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28894 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28894 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.32616E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.13518E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.13518E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.28894 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69013E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70997 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2410.70374 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32616E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.88200 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28390 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28390 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28390 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.35342E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.11625E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.11625E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.28390 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69310E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70996 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2423.04610 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.35342E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.16294 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08504 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08504 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.08504 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.54217E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.39727E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.39727E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.08504 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.80902E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70972 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 11506.26544 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54217E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.95043 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17937 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11596 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22481 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28558E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.10351E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22481 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14046.97167 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.10351E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 267.87132 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28939 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11039 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28664 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45144E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.20383E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28664 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14501.07047 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20383E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.86436 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.35477 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32338 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56200 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13972E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14203E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32338 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9695.17668 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14203E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 176.05610 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59473 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52804 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33424 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.21543E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24597E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37255 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10165.62033 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24597E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.34510 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.05730 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.05730 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.45428 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.05730 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.07911 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.07911 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.57200 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.07911 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.07911 |
346 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 12.05026 |
347 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 12.05026 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 699860.56175 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.49974E-002 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 21.07911 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.29367E-002 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.11249 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.90394 |
355 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 313103.44403 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.91764E-003 |
358 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3986.65567 |
359 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 21.07911 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.49974E-002 |
361 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.90496E-005 |
362 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.91764E-003 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
365 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 87700.73147 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.13247E-003 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
373 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 30467.96244 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.73152E-004 |
376 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 387.93976 |
377 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.13247E-003 |
379 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.52018E-004 |
380 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73152E-004 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.47265E-002 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8317.29188 |
383 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
384 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
386 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
387 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.38863E-002 |
389 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.66635 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.38863E-002 |
391 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3547.75936 |
392 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 628514.15109 |
393 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 628514.15000 |
394 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.38863E-002 |
395 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.47265E-002 |
396 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.16718 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.47265E-002 |
398 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2772.43063 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.47265E-002 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 972249.25478 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 972845.09000 |
402 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 110.90434 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8979.86 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5343.48 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1807.69 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2599.09 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1690.38 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12362.48 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15279.95 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 36832.02 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 8507.94 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 8531.37 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 47959.31 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 48378.20 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 8466.48 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 8489.81 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15136.15 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2601.42 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2614.73 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 12416.52 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14121.34 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14578.04 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9749.69 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10224.22 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 190468.34 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 18534.39 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 18876.27 | 14849.11 | 4027.16 | 0.79 | 2283.84 | 23.16 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 18568.41 | 14603.80 | 3964.60 | 0.79 | 2246.32 | 22.78 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 88618.99 | 69981.23 | 18637.76 | 0.79 | 10745.97 | 108.99 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 94738.41 | 73446.73 | 21291.68 | 0.78 | 11371.42 | 115.34 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 16888.86 | 13260.30 | 3628.56 | 0.79 | 2041.15 | 20.70 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 16787.01 | 13178.85 | 3608.16 | 0.79 | 2028.71 | 20.58 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4903.36 | 3859.29 | 1044.07 | 0.79 | 593.44 | 6.02 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4820.20 | 3793.03 | 1027.17 | 0.79 | 583.30 | 5.92 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 18781.56 | 14659.20 | 4122.36 | 0.78 | 2262.43 | 22.95 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 663193.05 | 418911.88 | 244281.17 | 0.63 | 94555.86 | 959.04 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67062.26 | 41857.36 | 25204.89 | 0.62 | 8925.08 | 90.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7504844416E-002 | 2.2849307180E-002 | Pass | Pass | 2.6071841985E-003 | 4.3868544681E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5156282292E-003 | 1.0924469838E-003 | Pass | Pass | 6.5919020659E-002 | 0.1625266826 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7415438533E-002 | 2.5413039627E-002 | Pass | Pass | 1.5518019421E-002 | 4.2014217758E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7115262119E-003 | 5.9550610835E-003 | Pass | Pass | 8.6507277164E-002 | 0.1677600450 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1196009629E-004 | 3.1783055153E-004 | Pass | Pass | 0.1692115020 | 0.6792613494 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3571056934E-002 | 0.2235311893 | Pass | Pass | 1.8191860736E-002 | 4.9519248685E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7377949554E-003 | 2.2211699454E-002 | Pass | Pass | 0.1186385149 | 0.4556495136 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7445955663E-002 | 4.5056605468E-002 | Pass | Pass | 1.3966161205E-002 | 3.9179161270E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2632525696E-002 | 0.3182277529 | Pass | Pass | 0.2887219824 | 1.3368192524 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2640841375E-002 | 0.3221201407 | Pass | Pass | 0.3028313936 | 1.4581456589 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4233176016E-005 | 5.2570820772E-005 | Pass | Pass | 0.2610981167 | 1.1423851998 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0391660137E-002 | 0.1394380248 | Pass | Pass | 0.1379754473 | 0.3707707672 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2628097369E-002 | 0.3145246002 | Pass | Pass | 0.2725036829 | 1.2912438710 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2635371366E-002 | 0.3181348373 | Pass | Pass | 0.2889467930 | 1.3868888063 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.2307929682E-004 | 3.3771070248E-004 | Pass | Pass | 3.1258482068E-002 | 4.6499451651E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2651382002E-002 | 0.3374421326 | Pass | Pass | 0.1963078670 | 0.8358285649 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2640085556E-002 | 0.3399743216 | Pass | Pass | 0.2102856414 | 0.8957975005 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.9049720141E-002 | 0.2889573274 | Pass | Pass | 0.5784032849 | 3.3249062753 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4407824521E-002 | 8.1983942288E-002 | Pass | Pass | 8.5898281012E-003 | 2.4365424260E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4346398614E-002 | 6.6641561084E-002 | Pass | Pass | 9.4400530165E-003 | 3.0220629179E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4997412982E-002 | 0.1075387785 | Pass | Pass | 2.0572062972E-002 | 3.8567208729E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.8044590697E-004 | 5.7032962650E-004 | Pass | Pass | 0.1851286320 | 0.6712829981 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.394 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.394 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.394 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.102 | 0.394 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.085 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 432.93 | 2.087 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 781.15 | 2.084 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.4281 | 1978.83 | 16677.86 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 54.51 | 168.00 | 54.45 | 0.0000 | Y | 170.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 12.2063 | 67.07 | 818.69 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 9.01 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 12.2063 | 77.67 | 948.05 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 10.43 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 9.2031 | 164.24 | 1511.55 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.64 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 6.1031 | 94.76 | 578.33 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 3.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 5.8125 | 78.04 | 453.61 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.99 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 10.3656 | 188.86 | 1957.68 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.69 | 0.0000 | Y | 17.89 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 10.2688 | 1308.19 | 13433.46 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 56.90 | 0.0000 | Y | 143.49 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 4.5531 | 156.09 | 710.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 4.5531 | 156.07 | 710.61 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 4.5531 | 1863.81 | 8486.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 67.92 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 4.5531 | 1864.32 | 8488.51 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 67.94 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 4.5531 | 156.09 | 710.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 4.5531 | 156.07 | 710.61 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 6.3938 | 1557.62 | 9959.04 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 4.5531 | 39.02 | 177.67 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.42 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 4.5531 | 39.02 | 177.65 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.42 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 4.5531 | 220.77 | 1005.22 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 8.05 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 10.3656 | 331.66 | 3437.84 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.62 | 0.0000 | Y | 34.60 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 10.3656 | 331.66 | 3437.84 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.62 | 0.0000 | Y | 34.60 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.7219 | 103.30 | 1210.92 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 6.3938 | 412.12 | 2635.03 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8961 | 11345.29 | 78237.74 | 526.38 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.68 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.68 | 0.00 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 13433.46 | 940.34 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 13433.46 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 14423.55 | AstronomicalClock | - | 83.63 | 83.63 | 226.43 | |
Exterior Lighting Total | 14423.55 | 226.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 628514.15 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 972845.09 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12243.78 | 18876.27 | 14849.11 | 4027.16 | 0.79 | - | 2283.84 | 23.16 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12047.49 | 18568.41 | 14603.80 | 3964.60 | 0.79 | - | 2246.32 | 22.78 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 57194.30 | 88618.99 | 69981.23 | 18637.76 | 0.79 | - | 10745.97 | 108.99 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 62690.60 | 94738.41 | 73446.73 | 21291.68 | 0.78 | - | 11371.42 | 115.34 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10982.45 | 16888.86 | 13260.30 | 3628.56 | 0.79 | - | 2041.15 | 20.70 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10917.85 | 16787.01 | 13178.85 | 3608.16 | 0.79 | - | 2028.71 | 20.58 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3178.27 | 4903.36 | 3859.29 | 1044.07 | 0.79 | - | 593.44 | 6.02 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3125.25 | 4820.20 | 3793.03 | 1027.17 | 0.79 | - | 583.30 | 5.92 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12311.41 | 18781.56 | 14659.20 | 4122.36 | 0.78 | - | 2262.43 | 22.95 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 699860.56 | 663193.05 | 418911.88 | 244281.17 | 0.63 | - | 94555.86 | 959.04 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 87700.73 | 67062.26 | 41857.36 | 25204.89 | 0.62 | - | 8925.08 | 90.52 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8929.18 | 8979.86 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5312.85 | 5343.48 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1795.93 | 1807.69 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2583.25 | 2599.09 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1680.69 | 1690.38 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12292.69 | 12362.48 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15185.93 | 15279.95 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36592.43 | 36832.02 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7884.02 | 8507.94 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7905.73 | 8531.37 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44442.20 | 47959.31 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44830.42 | 48378.20 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7845.60 | 8466.48 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7867.21 | 8489.81 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15045.76 | 15136.15 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2410.70 | 2601.42 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2423.05 | 2614.73 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 11506.27 | 12416.52 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14046.97 | 14121.34 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14501.07 | 14578.04 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9695.18 | 9749.69 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10165.62 | 10224.22 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 313103.44 | 190468.34 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 30467.96 | 18534.39 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 781.69 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 768.56 | 703.64 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.26 | 3703.16 | 703.64 | 1.00 | 0.97 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.39 | 3789.55 | 703.64 | 1.00 | 0.97 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 696.24 | 703.64 | 1.00 | 1.20 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.98 | 691.86 | 703.64 | 1.00 | 1.20 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 203.31 | 703.64 | 1.00 | 1.74 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 199.76 | 703.64 | 1.00 | 1.75 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 763.47 | 703.64 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.08 | 47230.66 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.034726 | 8317.29 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.013886 | 3547.76 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.034726 | 2772.43 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 32432.92 | 32432.92 | 16.39 | 2.471 | 2.471 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00924 | 26.68 | 0.01534 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4220.42 | 4220.42 | 62.92 | 0.322 | 0.322 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00942 | 30.85 | 0.01534 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3051.78 | 3051.78 | 39.29 | 0.233 | 0.233 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00953 | 30.14 | 0.01534 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44790.43 | 44790.43 | 573.95 | 3.412 | 3.412 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01534 | 0.236 | 0.00 |
CAFE_FLR_1 | 18048.44 | 18048.44 | 95.56 | 1.376 | 1.376 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01044 | 30.85 | 0.01534 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61921.87 | 61921.87 | 47.33 | 4.719 | 4.719 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01015 | 30.93 | 0.01534 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 10822.07 | 10822.07 | 277.33 | 1.111 | 1.111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00870 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10640.19 | 10640.19 | 272.70 | 1.092 | 1.092 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00870 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 51272.56 | 51272.56 | 2090.72 | 5.263 | 5.263 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00864 | 30.93 | 0.01534 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 52464.44 | 52464.44 | 2138.74 | 5.386 | 5.386 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00891 | 31.20 | 0.01534 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9639.04 | 9639.04 | 247.02 | 0.989 | 0.989 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00872 | 25.37 | 0.01534 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9578.37 | 9578.37 | 245.49 | 0.983 | 0.983 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 21.11 | 21.11 | 0.00873 | 25.03 | 0.01534 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2814.68 | 2814.68 | 72.13 | 0.289 | 0.289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2765.55 | 2765.55 | 70.88 | 0.284 | 0.284 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10569.68 | 10569.68 | 430.88 | 1.085 | 1.085 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00881 | 30.93 | 0.01534 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28573.67 | 28573.67 | 86.15 | 2.179 | 2.179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01050 | 31.20 | 0.01534 | 1.187 | 0.00 |
DINING_FLR_6 | 30016.65 | 30016.65 | 90.50 | 2.289 | 2.289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01041 | 31.20 | 0.01534 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30831.35 | 30831.35 | 298.45 | 2.355 | 2.355 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 23.97 | 0.01002 | 25.97 | 0.01534 | 0.367 | 0.00 |
MECH_FLR_1 | 2839.03 | 2839.03 | 17.29 | 0.216 | 0.216 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00876 | 30.88 | 0.01534 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1323.51 | 1323.51 | 13.97 | 0.101 | 0.101 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 31.20 | 0.01534 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 12417.61 | 12417.61 | 31.89 | 0.946 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00869 | 31.11 | 0.01534 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7808.27 | 7808.27 | 18.95 | 0.595 | 0.595 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00863 | 31.20 | 0.01534 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1936.95 | 1936.95 | 0.98 | 0.087 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4333.98 | 4333.98 | 64.62 | 0.195 | 0.195 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00720 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1138.76 | 1138.76 | 14.66 | 0.051 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00734 | -26.20 | 0.00036 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2652.32 | 2652.32 | 33.99 | 0.119 | 0.236 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00716 | -26.20 | 0.00036 | 0.236 | 0.00 |
CAFE_FLR_1 | 11297.51 | 11297.51 | 59.82 | 0.508 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00722 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23256.21 | 23256.21 | 17.78 | 1.045 | 1.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00724 | -26.20 | 0.00036 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 7884.36 | 7884.36 | 202.05 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7906.07 | 7906.07 | 202.63 | 0.357 | 0.357 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 44443.14 | 44443.14 | 1812.24 | 2.009 | 2.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 44831.37 | 44831.37 | 1827.57 | 2.026 | 2.026 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00750 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7845.94 | 7845.94 | 201.06 | 0.355 | 0.355 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7867.55 | 7867.55 | 201.64 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2410.80 | 2410.80 | 61.78 | 0.109 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2423.15 | 2423.15 | 62.10 | 0.110 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00756 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11506.65 | 11506.65 | 469.07 | 0.520 | 0.520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7882.98 | 7882.98 | 23.77 | 0.354 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
DINING_FLR_6 | 8026.08 | 8026.08 | 24.20 | 0.361 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00767 | -26.20 | 0.00036 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 3049.21 | 3049.21 | 29.52 | 0.137 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00688 | -26.20 | 0.00036 | 0.367 | 0.00 |
MECH_FLR_1 | 1972.22 | 1972.22 | 12.01 | 0.089 | 0.089 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00718 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1370.93 | 1370.93 | 14.47 | 0.062 | 0.062 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00718 | -26.20 | 0.00036 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11689.41 | 11689.41 | 30.02 | 0.525 | 0.525 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00755 | -26.20 | 0.00036 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8290.52 | 8290.52 | 20.12 | 0.373 | 0.373 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.08 | 21.08 | 7.74 | 7.74 | 21.0791 | 12.0573 | 21.0791 | 0.5720 | 0.3000 |
FLR_3_DOAS | 15.20 | 2.05 | 6.20 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8929.178 | 8929.178 | 1.388476 | 0.00019728 | 160.499 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8979.86 | 8929.18 | 1.388476 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797448 | 49.1736 | 1936.95 | 0.00 | 8981.79 | 8981.79 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5312.848 | 5312.848 | 0.194730 | 0.00011738 | 115.155 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5343.48 | 5312.85 | 0.194730 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00719513 | 44.4273 | 4333.98 | 0.00 | 5346.79 | 5346.79 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1795.931 | 1795.931 | 0.130667 | 0.00003968 | 35.019 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1807.69 | 1795.93 | 0.130667 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00734322 | 45.3283 | 1138.76 | 0.00 | 1808.12 | 1808.12 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2583.246 | 2583.246 | 0.121529 | 0.00005707 | 53.146 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2599.09 | 2583.25 | 0.121529 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718407 | 44.3571 | 1972.22 | 0.00 | 2600.24 | 2600.24 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1680.690 | 1680.690 | 0.061605 | 0.00003713 | 36.428 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1690.38 | 1680.69 | 0.061605 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718383 | 44.3549 | 1370.93 | 0.00 | 1691.43 | 1691.43 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12292.691 | 12292.691 | 1.917607 | 0.00027159 | 220.906 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12362.48 | 12292.69 | 1.917607 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00715614 | 44.1874 | 2652.32 | 0.00 | 12365.12 | 12365.12 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15185.931 | 15185.931 | 0.773479 | 0.00033551 | 308.464 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15279.95 | 15185.93 | 0.773479 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00721816 | 44.5675 | 11297.51 | 0.00 | 15286.00 | 15286.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 36592.429 | 36592.429 | 2.652068 | 0.00080846 | 713.761 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36832.02 | 36592.43 | 2.652068 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00724008 | 44.6984 | 23256.21 | 0.00 | 36840.66 | 36840.66 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12243.783 | -999.000 | 1.110934 | 0.00043731 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12243.78 | 11711.82 | 1.110934 | 21.71 | 15.25 | 0.00869746 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869746 | 53.2096 | 10822.07 | 0.00 | 12795.13 | 11984.62 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7884.019 | 7884.019 | 0.356356 | 0.00017419 | 179.493 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8507.94 | 7884.02 | 0.356356 | 21.11 | 13.93 | 0.00746253 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746253 | 45.7441 | 7884.36 | 0.00 | 8511.01 | 8511.01 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12047.492 | -999.000 | 1.092265 | 0.00043030 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12047.49 | 11516.52 | 1.092265 | 21.71 | 15.25 | 0.00870043 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00870043 | 53.2276 | 10640.19 | 0.00 | 12589.79 | 11784.40 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7905.731 | 7905.731 | 0.357338 | 0.00017467 | 179.988 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8531.37 | 7905.73 | 0.357338 | 21.11 | 13.93 | 0.00746394 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746394 | 45.7527 | 7906.07 | 0.00 | 8534.45 | 8534.45 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 57194.302 | -999.000 | 5.262894 | 0.00204281 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 57194.30 | 55354.65 | 5.262894 | 21.71 | 15.20 | 0.00864449 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00864449 | 52.8876 | 51272.56 | 0.00 | 59787.44 | 56676.60 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 44442.204 | 44442.204 | 2.008842 | 0.00098190 | 1011.800 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47959.31 | 44442.20 | 2.008842 | 21.11 | 13.95 | 0.00749240 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749240 | 45.9234 | 44443.14 | 0.00 | 47977.03 | 47977.03 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62690.602 | -999.000 | 5.385666 | 0.00223912 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 62690.60 | 57291.94 | 5.385666 | 21.71 | 15.43 | 0.00890964 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 0.0000 | 21.11 | 0.00890964 | 54.4892 | 52464.44 | 0.00 | 65438.94 | 58502.21 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 44830.423 | 44830.423 | 2.026390 | 0.00099047 | 1020.637 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48378.20 | 44830.42 | 2.026390 | 21.11 | 13.96 | 0.00749638 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749638 | 45.9475 | 44831.37 | 0.00 | 48396.13 | 48396.13 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10982.449 | -999.000 | 0.989494 | 0.00039226 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 10982.45 | 10443.90 | 0.989494 | 21.71 | 15.27 | 0.00872417 | 12.80 | 11.67 | 0.00850000 | 25.37 | 0.01534436 | 21.50 | 0.0000 | 21.11 | 0.00872417 | 53.3709 | 9639.04 | 0.00 | 11475.30 | 10684.14 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7845.597 | 7845.597 | 0.354620 | 0.00017334 | 178.619 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8466.48 | 7845.60 | 0.354620 | 21.11 | 13.92 | 0.00746008 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746008 | 45.7293 | 7845.94 | 0.00 | 8469.54 | 8469.54 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10917.848 | -999.000 | 0.983266 | 0.00038995 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | 7/21 08:50:00 | 10917.85 | 10378.88 | 0.983266 | 21.71 | 15.28 | 0.00872575 | 12.80 | 11.67 | 0.00850000 | 25.03 | 0.01534436 | 21.41 | 0.0000 | 21.11 | 0.00872575 | 53.3804 | 9578.37 | 0.00 | 11407.70 | 10617.46 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7867.215 | 7867.215 | 0.355597 | 0.00017382 | 179.111 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8489.81 | 7867.21 | 0.355597 | 21.11 | 13.93 | 0.00746150 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746150 | 45.7379 | 7867.55 | 0.00 | 8492.87 | 8492.87 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15045.759 | 15045.759 | 0.667041 | 0.00033242 | 312.819 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15136.15 | 15045.76 | 0.667041 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00755343 | 46.6092 | 11689.41 | 0.00 | 15143.40 | 15143.40 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3178.274 | -999.000 | 0.288939 | 0.00011352 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3178.27 | 3045.09 | 0.288939 | 21.71 | 15.24 | 0.00869013 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869013 | 53.1654 | 2814.68 | 0.00 | 3321.53 | 3116.27 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2410.704 | 2410.704 | 0.108963 | 0.00005326 | 54.882 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2601.42 | 2410.70 | 0.108963 | 21.11 | 14.01 | 0.00755473 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755473 | 46.3025 | 2410.80 | 0.00 | 2602.42 | 2602.42 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3125.252 | -999.000 | 0.283896 | 0.00011162 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3125.25 | 2992.34 | 0.283896 | 21.71 | 15.25 | 0.00869310 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869310 | 53.1833 | 2765.55 | 0.00 | 3266.06 | 3062.18 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2423.046 | 2423.046 | 0.109521 | 0.00005353 | 55.163 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2614.73 | 2423.05 | 0.109521 | 21.11 | 14.01 | 0.00755691 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755691 | 46.3157 | 2423.15 | 0.00 | 2615.74 | 2615.74 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12311.408 | -999.000 | 1.085040 | 0.00043973 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 12311.41 | 11494.34 | 1.085040 | 21.71 | 15.35 | 0.00880902 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00880902 | 53.8830 | 10569.68 | 0.00 | 12857.97 | 11748.55 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11506.265 | 11506.265 | 0.520087 | 0.00025422 | 261.950 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12416.52 | 11506.27 | 0.520087 | 21.11 | 14.02 | 0.00756958 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00756958 | 46.3919 | 11506.65 | 0.00 | 12421.37 | 12421.37 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14046.972 | 14046.972 | 1.224806 | 0.00031035 | 267.871 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14121.34 | 14046.97 | 1.224806 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766060 | 47.2627 | 7882.98 | 0.00 | 14126.89 | 14126.89 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14501.070 | 14501.070 | 1.286638 | 0.00032038 | 275.864 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14578.04 | 14501.07 | 1.286638 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766640 | 47.2984 | 8026.08 | 0.00 | 14583.66 | 14583.66 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9695.177 | 9695.177 | 1.323379 | 0.00021420 | 176.056 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9749.69 | 9695.18 | 1.323379 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00688203 | 42.5196 | 3049.21 | 0.00 | 9752.08 | 9752.08 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10165.620 | 10165.620 | 0.372552 | 0.00022460 | 220.345 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.22 | 10165.62 | 0.372552 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771511 | 47.5949 | 8290.52 | 0.00 | 10230.56 | 10230.56 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 699860.562 | -999.000 | 21.079108 | 0.02499740 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 699860.56 | 429618.53 | 21.079108 | 28.11 | 20.63 | 0.01293674 | 10.90 | 10.89 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 57.1668 | 23.99 | 0.00955648 | 49.0096 | 276412.19 | 0.00 | 754116.06 | 441075.76 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 313103.444 | 313103.444 | 6.323733 | 0.00691764 | 3986.656 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 190468.34 | 313103.44 | 6.323733 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 190.5561 | 21.00 | 0.00748647 | 46.2018 | 85733.32 | 0.00 | 190028.85 | 190028.85 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 10.91 | 11.67 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 100.0000 | 21.11 | 0.00877754 | 53.6915 | 147280.25 | 0.00 | 93045.89 | 49604.71 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 0.615360 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3333 | 21.11 | 0.00749497 | 45.9390 | 137119.03 | 0.00 | 18491.63 | 18491.63 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8929.178 | 8929.178 | 1.388476 | 0.00019728 | 160.499 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.4006 | 1.420680 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8979.86 | 8929.18 | 1.0000 | 1.59474199 | 1.388476 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.19725915 | 60.00 | 49.00 | 11.00 | 0.000 | 8979.86 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797448 | 21.00 | 0.00797448 | 49.1736 | 1936.95 | 0.00 | 8981.79 | 8981.79 | 1.59474199 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.12 | 15.25 | 0.00800000 | 42566.9 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5312.848 | 5312.848 | 0.194730 | 0.00011738 | 115.155 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.8334 | 0.845303 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5343.48 | 5312.85 | 1.0000 | 0.22365878 | 0.194730 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.11736892 | 60.00 | 49.00 | 11.00 | 0.000 | 5343.48 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00719513 | 21.00 | 0.00719513 | 44.4273 | 4333.98 | 0.00 | 5346.79 | 5346.79 | 0.22365878 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1795.931 | 1795.931 | 0.130667 | 0.00003968 | 35.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.2819 | 0.285742 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1807.69 | 1795.93 | 1.0000 | 0.15007852 | 0.130667 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03967484 | 60.00 | 49.00 | 11.00 | 0.000 | 1807.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00734322 | 21.00 | 0.00734322 | 45.3283 | 1138.76 | 0.00 | 1808.12 | 1808.12 | 0.15007852 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.41 | 17.48 | 0.00800000 | 48982.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2583.246 | 2583.246 | 0.121529 | 0.00005707 | 53.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.4054 | 0.411008 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2599.09 | 2583.25 | 1.0000 | 0.13958230 | 0.121529 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05706784 | 60.00 | 49.00 | 11.00 | 0.000 | 2599.09 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718407 | 21.00 | 0.00718407 | 44.3571 | 1972.22 | 0.00 | 2600.24 | 2600.24 | 0.13958230 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.87 | 19.59 | 0.00800000 | 55563.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1680.690 | 1680.690 | 0.061605 | 0.00003713 | 36.428 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.2636 | 0.267407 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1690.38 | 1680.69 | 1.0000 | 0.07075648 | 0.061605 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03712901 | 60.00 | 49.00 | 11.00 | 0.000 | 1690.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718383 | 21.00 | 0.00718383 | 44.3549 | 1370.93 | 0.00 | 1691.43 | 1691.43 | 0.07075648 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12292.691 | 12292.691 | 1.917607 | 0.00027159 | 220.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.9281 | 1.955834 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12362.48 | 12292.69 | 1.0000 | 2.20247921 | 1.917607 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.27156428 | 60.00 | 49.00 | 11.00 | 0.000 | 12362.48 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00715614 | 21.00 | 0.00715614 | 44.1874 | 2652.32 | 0.00 | 12365.12 | 12365.12 | 2.20247921 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.11 | 15.25 | 0.00800000 | 42548.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15185.931 | 15185.931 | 0.773479 | 0.00033551 | 308.464 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 2.3832 | 2.416164 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15279.95 | 15185.93 | 1.0000 | 0.88838426 | 0.773479 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33548035 | 60.00 | 49.00 | 11.00 | 0.000 | 15279.95 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00721816 | 21.00 | 0.00721816 | 44.5675 | 11297.51 | 0.00 | 15286.00 | 15286.00 | 0.88838426 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 33.47 | 19.15 | 0.00800000 | 54141.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36592.429 | 36592.429 | 2.652068 | 0.00080846 | 713.761 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 5.7446 | 5.822053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36832.02 | 36592.43 | 1.0000 | 3.04604792 | 2.652068 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.80838254 | 60.00 | 49.00 | 11.00 | 0.000 | 36832.02 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00724008 | 21.00 | 0.00724008 | 44.6984 | 23256.21 | 0.00 | 36840.66 | 36840.66 | 3.04604792 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.46 | 17.50 | 0.00800000 | 49029.3 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12243.783 | -999.000 | 1.110934 | 0.00043731 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0081 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.110934 | 1.27596990 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 1.2593 | 1.259302 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12243.78 | 11711.82 | 1.0000 | 1.27596990 | 1.110934 | 21.71 | 15.25 | 0.00869746 | 43917.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.43726680 | 6.70 | 11.72 | 6.67 | 0.000 | 12243.78 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869746 | 21.11 | 0.00869746 | 53.2096 | 10822.07 | 0.00 | 12795.13 | 11984.62 | 1.27596990 | 21.71 | 15.73 | 0.00869746 | 43917.9 | 12.51 | 11.92 | 0.00844581 | 33890.1 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7884.019 | 7884.019 | 0.356356 | 0.00017419 | 179.493 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.110934 | 1.27596990 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.3270 | 1.254390 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8507.94 | 7884.02 | 1.0000 | 0.40929512 | 0.356356 | 21.11 | 13.93 | 0.00746253 | 40168.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17416999 | 60.00 | 49.00 | 11.00 | 0.000 | 8507.94 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746253 | 21.11 | 0.00746253 | 45.7441 | 7884.36 | 0.00 | 8511.01 | 8511.01 | 0.40929512 | 16.60 | 12.62 | 0.00746253 | 35574.0 | 37.01 | 19.85 | 0.00746253 | 56368.3 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12047.492 | -999.000 | 1.092265 | 0.00043030 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0137 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.092265 | 1.25452718 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 1.2391 | 1.239113 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12047.49 | 11516.52 | 1.0000 | 1.25452718 | 1.092265 | 21.71 | 15.25 | 0.00870043 | 43925.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.43025657 | 6.70 | 11.72 | 6.67 | 0.000 | 12047.49 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00870043 | 21.11 | 0.00870043 | 53.2276 | 10640.19 | 0.00 | 12589.79 | 11784.40 | 1.25452718 | 21.71 | 15.73 | 0.00870043 | 43925.4 | 12.51 | 11.92 | 0.00844610 | 33889.9 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7905.731 | 7905.731 | 0.357338 | 0.00017467 | 179.988 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.092265 | 1.25452718 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.3306 | 1.257845 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8531.37 | 7905.73 | 1.0000 | 0.41042231 | 0.357338 | 21.11 | 13.93 | 0.00746394 | 40171.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17464965 | 60.00 | 49.00 | 11.00 | 0.000 | 8531.37 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746394 | 21.11 | 0.00746394 | 45.7527 | 7906.07 | 0.00 | 8534.45 | 8534.45 | 0.41042231 | 16.60 | 12.62 | 0.00746394 | 35577.5 | 37.01 | 19.85 | 0.00746394 | 56371.9 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 57194.302 | -999.000 | 5.262894 | 0.00204281 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9097 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.262894 | 6.04472791 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 5.8827 | 5.882569 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 57194.30 | 55354.65 | 1.0000 | 6.04472791 | 5.262894 | 21.71 | 15.20 | 0.00864449 | 43784.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.04260142 | 6.70 | 11.72 | 6.67 | 0.000 | 57194.30 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00864449 | 21.11 | 0.00864449 | 52.8876 | 51272.56 | 0.00 | 59787.44 | 56676.60 | 6.04472791 | 21.71 | 15.68 | 0.00864449 | 43784.0 | 12.53 | 11.93 | 0.00844061 | 33893.2 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44442.204 | 44442.204 | 2.008842 | 0.00098190 | 1011.800 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.262894 | 6.04472791 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 7.4800 | 7.070995 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47959.31 | 44442.20 | 1.0000 | 2.30726729 | 2.008842 | 21.11 | 13.95 | 0.00749240 | 40244.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.98179603 | 60.00 | 49.00 | 11.00 | 0.000 | 47959.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749240 | 21.11 | 0.00749240 | 45.9234 | 44443.14 | 0.00 | 47977.03 | 47977.03 | 2.30726729 | 16.60 | 12.65 | 0.00749240 | 35649.6 | 37.01 | 19.87 | 0.00749240 | 56443.5 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62690.602 | -999.000 | 5.385666 | 0.00223912 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4026 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.385666 | 6.18573818 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 6.4480 | 6.447877 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 62690.60 | 57291.94 | 1.0000 | 6.18573818 | 5.385666 | 21.71 | 15.43 | 0.00890964 | 44456.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.23889282 | 6.70 | 11.72 | 6.67 | 0.000 | 62690.60 | 31.20 | 0.01534436 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00890964 | 21.11 | 0.00890964 | 54.4892 | 52464.44 | 0.00 | 65438.94 | 58502.21 | 6.18573818 | 21.71 | 15.91 | 0.00890964 | 44456.9 | 12.45 | 11.92 | 0.00846535 | 33877.9 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44830.423 | 44830.423 | 2.026390 | 0.00099047 | 1020.637 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.385666 | 6.18573818 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 7.5454 | 7.132763 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48378.20 | 44830.42 | 1.0000 | 2.32742211 | 2.026390 | 21.11 | 13.96 | 0.00749638 | 40254.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.99037237 | 60.00 | 49.00 | 11.00 | 0.000 | 48378.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749638 | 21.11 | 0.00749638 | 45.9475 | 44831.37 | 0.00 | 48396.13 | 48396.13 | 2.32742211 | 16.60 | 12.65 | 0.00749638 | 35659.7 | 37.01 | 19.87 | 0.00749638 | 56453.5 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10982.449 | -999.000 | 0.989494 | 0.00039226 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0578 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.989494 | 1.13648901 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 1.1296 | 1.129571 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 10982.45 | 10443.90 | 1.0000 | 1.13648901 | 0.989494 | 21.71 | 15.27 | 0.00872417 | 43985.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.39222030 | 6.70 | 11.72 | 6.67 | 0.000 | 10982.45 | 25.37 | 0.01534436 | 21.50 | 0.00000000 | 0.0000 | 21.11 | 0.00872417 | 21.11 | 0.00872417 | 53.3709 | 9639.04 | 0.00 | 11475.30 | 10684.14 | 1.13648901 | 21.71 | 15.75 | 0.00872417 | 43985.7 | 12.50 | 11.92 | 0.00844838 | 33888.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7845.597 | 7845.597 | 0.354620 | 0.00017334 | 178.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.989494 | 1.13648901 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.3205 | 1.248277 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8466.48 | 7845.60 | 1.0000 | 0.40730046 | 0.354620 | 21.11 | 13.92 | 0.00746008 | 40162.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17332119 | 60.00 | 49.00 | 11.00 | 0.000 | 8466.48 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746008 | 21.11 | 0.00746008 | 45.7293 | 7845.94 | 0.00 | 8469.54 | 8469.54 | 0.40730046 | 16.60 | 12.61 | 0.00746008 | 35567.8 | 37.01 | 19.84 | 0.00746008 | 56362.1 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10917.848 | -999.000 | 0.983266 | 0.00038995 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0607 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.983266 | 1.12933578 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 1.1229 | 1.122926 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | unknown | unknown | 7/21 08:50:00 | 10917.85 | 10378.88 | 1.0000 | 1.12933578 | 0.983266 | 21.71 | 15.28 | 0.00872575 | 43989.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.38991318 | 6.70 | 11.72 | 6.67 | 0.000 | 10917.85 | 25.03 | 0.01534436 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00872575 | 21.11 | 0.00872575 | 53.3804 | 9578.37 | 0.00 | 11407.70 | 10617.46 | 1.12933578 | 21.71 | 15.75 | 0.00872575 | 43989.7 | 12.50 | 11.92 | 0.00844853 | 33888.4 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7867.215 | 7867.215 | 0.355597 | 0.00017382 | 179.111 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.983266 | 1.12933578 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.3241 | 1.251716 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8489.81 | 7867.21 | 1.0000 | 0.40842274 | 0.355597 | 21.11 | 13.93 | 0.00746150 | 40165.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17379876 | 60.00 | 49.00 | 11.00 | 0.000 | 8489.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746150 | 21.11 | 0.00746150 | 45.7379 | 7867.55 | 0.00 | 8492.87 | 8492.87 | 0.40842274 | 16.60 | 12.61 | 0.00746150 | 35571.4 | 37.01 | 19.85 | 0.00746150 | 56365.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15045.759 | 15045.759 | 0.667041 | 0.00033242 | 312.819 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 2.3607 | 2.393862 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15136.15 | 15045.76 | 1.0000 | 0.76613367 | 0.667041 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33238374 | 60.00 | 49.00 | 11.00 | 0.000 | 15136.15 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00755343 | 21.00 | 0.00755343 | 46.6092 | 11689.41 | 0.00 | 15143.40 | 15143.40 | 0.76613367 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.98 | 19.94 | 0.00800000 | 56700.7 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3178.274 | -999.000 | 0.288939 | 0.00011352 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9945 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.288939 | 0.33186301 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 0.3269 | 0.326893 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3178.27 | 3045.09 | 1.0000 | 0.33186301 | 0.288939 | 21.71 | 15.24 | 0.00869013 | 43899.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.11350687 | 6.70 | 11.72 | 6.67 | 0.000 | 3178.27 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869013 | 21.11 | 0.00869013 | 53.1654 | 2814.68 | 0.00 | 3321.53 | 3116.27 | 0.33186301 | 21.71 | 15.72 | 0.00869013 | 43899.3 | 12.51 | 11.92 | 0.00844510 | 33890.5 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2410.704 | 2410.704 | 0.108963 | 0.00005326 | 54.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.288939 | 0.33186301 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.4057 | 0.383556 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2601.42 | 2410.70 | 1.0000 | 0.12515059 | 0.108963 | 21.11 | 14.01 | 0.00755473 | 40402.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05325612 | 60.00 | 49.00 | 11.00 | 0.000 | 2601.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755473 | 21.11 | 0.00755473 | 46.3025 | 2410.80 | 0.00 | 2602.42 | 2602.42 | 0.12515059 | 16.60 | 12.71 | 0.00755473 | 35807.4 | 37.01 | 19.91 | 0.00755473 | 56601.7 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3125.252 | -999.000 | 0.283896 | 0.00011162 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0000 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.283896 | 0.32607061 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 0.3214 | 0.321440 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3125.25 | 2992.34 | 1.0000 | 0.32607061 | 0.283896 | 21.71 | 15.25 | 0.00869310 | 43906.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.11161328 | 6.70 | 11.72 | 6.67 | 0.000 | 3125.25 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869310 | 21.11 | 0.00869310 | 53.1833 | 2765.55 | 0.00 | 3266.06 | 3062.18 | 0.32607061 | 21.71 | 15.72 | 0.00869310 | 43906.8 | 12.51 | 11.92 | 0.00844539 | 33890.4 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2423.046 | 2423.046 | 0.109521 | 0.00005353 | 55.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.283896 | 0.32607061 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 0.4078 | 0.385520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2614.73 | 2423.05 | 1.0000 | 0.12579134 | 0.109521 | 21.11 | 14.01 | 0.00755691 | 40408.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05352878 | 60.00 | 49.00 | 11.00 | 0.000 | 2614.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755691 | 21.11 | 0.00755691 | 46.3157 | 2423.15 | 0.00 | 2615.74 | 2615.74 | 0.12579134 | 16.60 | 12.71 | 0.00755691 | 35812.9 | 37.01 | 19.92 | 0.00755691 | 56607.2 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12311.408 | -999.000 | 1.085040 | 0.00043973 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2155 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.085040 | 1.24622922 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 1.2663 | 1.266257 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 12311.41 | 11494.34 | 1.0000 | 1.24622922 | 1.085040 | 21.71 | 15.35 | 0.00880902 | 44201.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.43968190 | 6.70 | 11.72 | 6.67 | 0.000 | 12311.41 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00880902 | 21.11 | 0.00880902 | 53.8830 | 10569.68 | 0.00 | 12857.97 | 11748.55 | 1.24622922 | 21.71 | 15.82 | 0.00880902 | 44201.1 | 12.48 | 11.92 | 0.00845633 | 33883.6 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11506.265 | 11506.265 | 0.520087 | 0.00025422 | 261.950 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.085040 | 1.24622922 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.9366 | 1.830709 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12416.52 | 11506.27 | 1.0000 | 0.59734900 | 0.520087 | 21.11 | 14.02 | 0.00756958 | 40440.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.25419094 | 60.00 | 49.00 | 11.00 | 0.000 | 12416.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756958 | 21.11 | 0.00756958 | 46.3919 | 11506.65 | 0.00 | 12421.37 | 12421.37 | 0.59734900 | 16.60 | 12.72 | 0.00756958 | 35845.0 | 37.01 | 19.93 | 0.00756958 | 56639.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14046.972 | 14046.972 | 1.224806 | 0.00031035 | 267.871 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 2.2025 | 2.234949 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14121.34 | 14046.97 | 1.0000 | 1.40675857 | 1.224806 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.31031902 | 60.00 | 49.00 | 11.00 | 0.000 | 14121.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766060 | 21.00 | 0.00766060 | 47.2627 | 7882.98 | 0.00 | 14126.89 | 14126.89 | 1.40675857 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.45 | 16.80 | 0.00800000 | 46976.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14501.070 | 14501.070 | 1.286638 | 0.00032038 | 275.864 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 2.2737 | 2.307199 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14578.04 | 14501.07 | 1.0000 | 1.47777530 | 1.286638 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.32035075 | 60.00 | 49.00 | 11.00 | 0.000 | 14578.04 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766640 | 21.00 | 0.00766640 | 47.2984 | 8026.08 | 0.00 | 14583.66 | 14583.66 | 1.47777530 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.28 | 16.74 | 0.00800000 | 46803.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9695.177 | 9695.177 | 1.323379 | 0.00021420 | 176.056 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.5206 | 1.542555 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9749.69 | 9695.18 | 1.0000 | 1.51997448 | 1.323379 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.21418123 | 60.00 | 49.00 | 11.00 | 0.000 | 9749.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.67 | 0.00688203 | 21.00 | 0.00688203 | 42.5196 | 3049.21 | 0.00 | 9752.08 | 9752.08 | 1.51997448 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.89 | 15.54 | 0.00800000 | 43350.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10165.620 | 10165.620 | 0.372552 | 0.00022460 | 220.345 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 1.5946 | 1.617405 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.22 | 10165.62 | 1.0000 | 0.42789729 | 0.372552 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.22457405 | 60.00 | 49.00 | 11.00 | 0.000 | 10224.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771511 | 21.00 | 0.00771511 | 47.5949 | 8290.52 | 0.00 | 10230.56 | 10230.56 | 0.42789729 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.7 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 699860.562 | -999.000 | 21.079108 | 0.02499740 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.8888 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.079108 | 24.21053289 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 71.9837 | 71.983656 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 699860.56 | 429618.53 | 1.0000 | 24.21053289 | 21.079108 | 28.11 | 20.63 | 0.01293674 | 61278.6 | 10.90 | 10.89 | 0.00868318 | 32387.0 | 24.99484769 | 6.70 | 11.72 | 6.67 | 47230.664 | 652629.90 | 31.20 | 0.01534436 | 23.10 | 12.05026000 | 57.1668 | 23.99 | 0.00972053 | 23.99 | 0.00955648 | 49.0096 | 276412.19 | 0.00 | 754116.06 | 441075.76 | 24.21053289 | 28.11 | 21.18 | 0.01293674 | 61278.6 | 10.41 | 10.37 | 0.00780640 | 30130.4 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 313103.444 | 313103.444 | 6.323733 | 0.00691764 | 3986.656 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.079108 | 24.21053289 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 29.7067 | 49.816451 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 190468.34 | 313103.44 | 1.0000 | 7.26315987 | 6.323733 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 6.91693233 | 60.00 | 49.00 | 11.00 | 0.000 | 190468.34 | -26.20 | 0.00036134 | -26.20 | 12.05026000 | 190.5561 | 20.98 | 0.00737164 | 21.00 | 0.00748647 | 46.2018 | 85733.32 | 0.00 | 190028.85 | 190028.85 | 7.26315987 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 34.72294821 | 13.37 | 6.70 | 6.67 | 972249.25 | 9.0204 | 9.020396 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 1.0000 | 2.35591662 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 11.67 | 0.00868318 | 34322.2 | 3.13214738 | 6.70 | 11.72 | 6.67 | 2194.880 | 85505.85 | 31.20 | 0.01534436 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00878642 | 21.11 | 0.00877754 | 53.6915 | 147280.25 | 0.00 | 93045.89 | 49604.71 | 2.35591662 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.82 | 10.78 | 0.00803030 | 31121.7 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 13.88483562 | 71.00 | 82.00 | 11.00 | 641163.25 | 2.8907 | 4.847618 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 1.0000 | 0.70677499 | 0.615360 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 0.67308373 | 60.00 | 49.00 | 11.00 | 0.000 | 18534.39 | -26.20 | 0.00036134 | -26.20 | 2.05119905 | 333.3333 | 21.11 | 0.00749543 | 21.11 | 0.00749497 | 45.9390 | 137119.03 | 0.00 | 18491.63 | 18491.63 | 0.70677499 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 12.05 | 21.08 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 268.00 | 8363.83 | 263.17 |
RETAIL_1_FLR_1 | 2540.17 | 8243.83 | 2318.50 |
RETAIL_2_FLR_1 | 626.00 | 8528.33 | 591.67 |
LAUNDRY_FLR_1 | 5721.67 | 3323.67 | 2140.50 |
CAFE_FLR_1 | 2272.50 | 7155.67 | 1447.17 |
LOBBY_FLR_1 | 934.33 | 7415.00 | 532.17 |
ROOM_1_FLR_3 | 3403.00 | 8426.33 | 3338.67 |
ROOM_2_FLR_3 | 3842.17 | 8523.33 | 3796.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2980.33 | 8760.00 | 2980.33 |
ROOM_5_FLR_3 | 3322.83 | 8384.17 | 3301.00 |
ROOM_6_FLR_3 | 3744.50 | 8509.00 | 3723.67 |
ROOM_1_FLR_6 | 3923.83 | 8285.67 | 3763.00 |
ROOM_2_FLR_6 | 4270.50 | 8378.00 | 4144.50 |
ROOM_3_MULT9_FLR_6 | 2819.50 | 8335.33 | 2780.50 |
BANQUET_FLR_6 | 3323.00 | 4229.17 | 778.17 |
DINING_FLR_6 | 4212.17 | 2871.83 | 617.67 |
KITCHEN_FLR_6 | 7966.33 | 6400.00 | 5994.67 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8750.00 | 8760.00 | 8042.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 200.83 | 0.00 | 200.83 | 0.00 |
RETAIL_1_FLR_1 | 199.00 | 0.00 | 199.00 | 0.00 |
RETAIL_2_FLR_1 | 201.17 | 0.00 | 201.17 | 0.00 |
LAUNDRY_FLR_1 | 149.33 | 114.67 | 149.33 | 114.67 |
CAFE_FLR_1 | 173.67 | 0.00 | 173.67 | 0.00 |
LOBBY_FLR_1 | 182.33 | 0.00 | 182.33 | 0.00 |
ROOM_1_FLR_3 | 56.17 | 0.50 | 56.17 | 0.50 |
ROOM_2_FLR_3 | 80.50 | 0.00 | 80.50 | 0.00 |
ROOM_3_MULT19_FLR_3 | 36.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 172.83 | 4.00 | 172.83 | 4.00 |
ROOM_5_FLR_3 | 73.33 | 0.33 | 73.33 | 0.33 |
ROOM_6_FLR_3 | 101.67 | 0.33 | 101.67 | 0.33 |
ROOM_1_FLR_6 | 65.83 | 2.17 | 65.83 | 2.17 |
ROOM_2_FLR_6 | 99.00 | 1.00 | 99.00 | 1.00 |
ROOM_3_MULT9_FLR_6 | 64.83 | 10.67 | 64.83 | 10.67 |
BANQUET_FLR_6 | 143.83 | 0.50 | 143.83 | 0.50 |
DINING_FLR_6 | 140.00 | 0.83 | 140.00 | 0.83 |
KITCHEN_FLR_6 | 125.50 | 325.67 | 125.50 | 325.67 |
MECH_FLR_1 | 256.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 280.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 278.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 254.17 | 0.00 | 0.00 | 0.00 |
Facility | 325.50 | 414.17 | 273.67 | 414.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.005 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.354 | 0.276 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.468 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.460 | 0.154 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 3.591 | 0.249 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.774 | 0.072 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.062 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.081 | 0.000 | 0.099 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.062 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.182 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.182 | 0.000 | 0.075 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.148 | 0.000 | 0.131 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.508 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.861 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.364 | 0.151 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.666 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.457 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.927 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 16.638 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 2.304 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.256 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.514 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.518 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.273 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.438 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.167 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
Electricity:Building | 2519.01 | 32386.38 | 03-JUN-05:00 | 155989.88 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 320.72 | 3678.09 | 02-JAN-02:10 | 24053.66 | 02-JAN-20:10 |
InteriorLights:Electricity | 766.89 | 6553.44 | 03-JUN-05:00 | 66976.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 170.46 | 1548.87 | 02-JAN-02:10 | 13939.86 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 766.89 | 6553.44 | 03-JUN-05:00 | 66976.13 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 19.20 | 226.21 | 02-JAN-02:10 | 1422.43 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 9.01 | 81.87 | 02-JAN-02:10 | 736.82 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 22.23 | 261.95 | 02-JAN-02:10 | 1647.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.43 | 94.80 | 02-JAN-02:10 | 853.24 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.85 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.91 | 81.05 | 02-JAN-02:10 | 512.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.31 | 30.07 | 02-JAN-02:10 | 270.66 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.93 | 1008.06 | 02-JAN-02:10 | 4981.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.99 | 45.36 | 02-JAN-02:10 | 408.24 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.23 | 322.63 | 03-JUN-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.89 | 119.42 | 03-JUN-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 292.50 | 3392.07 | 03-JUN-05:00 | 22119.33 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 143.50 | 1280.66 | 03-JUN-05:00 | 12090.12 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.98 | 253.36 | 01-JAN-02:10 | 1306.07 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.55 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.98 | 253.33 | 01-JAN-02:10 | 1305.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 296.68 | 4430.63 | 01-JAN-02:10 | 21465.35 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 67.93 | 424.31 | 01-JAN-11:10 | 6788.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 296.76 | 4431.84 | 01-JAN-02:10 | 21471.23 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 67.94 | 424.43 | 01-JAN-11:10 | 6790.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.98 | 253.36 | 01-JAN-02:10 | 1306.07 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.55 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.98 | 253.33 | 01-JAN-02:10 | 1305.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.49 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.50 | 63.34 | 01-JAN-02:10 | 326.52 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.42 | 8.88 | 01-JAN-11:10 | 142.14 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.49 | 63.33 | 01-JAN-02:10 | 326.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.42 | 8.88 | 01-JAN-11:10 | 142.12 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.14 | 524.82 | 01-JAN-02:10 | 2542.65 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.05 | 50.26 | 01-JAN-11:10 | 804.17 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.46 | 2524.33 | 03-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.60 | 275.03 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.46 | 2524.33 | 03-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.60 | 275.03 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.02 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.17 | 696.15 | 02-FEB-23:30 | 3339.88 | 03-OCT-07:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1019.84 | 2852.76 | 27-APR-00:20 | 214585.46 | 04-AUG-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.22 | 0.00 | 01-JAN-11:10 | 1972.35 | 05-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.85 | 429.73 | 02-FEB-06:00 | 1201.53 | 05-JUN-13:10 |
WaterSystems:Electricity | 90.76 | 1086.70 | 15-SEP-00:20 | 4748.58 | 03-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.70 | 15-SEP-00:20 | 4748.58 | 03-FEB-07:10 |
Fans:Electricity | 577.88 | 14156.50 | 16-APR-05:10 | 37691.90 | 02-JUN-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 844.84 | 14916.03 | 24-SEP-04:40 | 48940.67 | 19-SEP-21:10 |
ExteriorEquipment:Electricity | 982.92 | 6683.63 | 02-JAN-02:20 | 63148.16 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.46 | 553.68 | 17-JUN-05:00 | 1873.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
ElectricityPurchased:Plant | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
Cogeneration:ElectricityPurchased | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
ElectricityNet:Plant | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
Cogeneration:ElectricityNet | 5560.56 | 77845.22 | 21-SEP-02:50 | 428348.13 | 26-JUL-20:00 |
General:Fans:Electricity | 577.88 | 14156.50 | 16-APR-05:10 | 37691.90 | 02-JUN-22:00 |
ExteriorLights:Electricity | 226.43 | 0.00 | 01-JAN-08:00 | 14423.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 226.43 | 0.00 | 01-JAN-08:00 | 14423.55 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 234.50 | 0.00 | 19-MAR-11:20 | 10206.30 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 793.69 | 0.00 | 01-JAN-00:10 | 206061.74 | 04-AUG-15:20 |
General:Cooling:Electricity | 793.69 | 0.00 | 01-JAN-00:10 | 206061.74 | 04-AUG-15:20 |
Pumps:Electricity | 81.32 | 47.91 | 24-MAR-10:30 | 5635.42 | 06-JAN-11:00 |
General:Pumps:Electricity | 81.32 | 47.91 | 24-MAR-10:30 | 5635.42 | 06-JAN-11:00 |
WIRED_LTG_ELECTRICITY | 26.99 | 0.00 | 01-JAN-00:10 | 2357.56 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 6119.07 | 29335.85 | 19-APR-01:40 | 1052007.41 | 02-FEB-19:00 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 4330.22 | 15908.90 | 24-MAR-10:30 | 965214.18 | 02-FEB-22:00 |
WaterSystems:Gas | 2279.84 | 15908.90 | 02-JAN-16:10 | 181996.19 | 20-APR-20:40 |
Water Heater:WaterSystems:Gas | 2279.84 | 15908.90 | 02-JAN-16:10 | 181996.19 | 20-APR-20:40 |
Heating:Gas | 2050.38 | 0.00 | 24-FEB-13:20 | 811646.27 | 02-FEB-06:00 |
Boiler:Heating:Gas | 2050.38 | 0.00 | 24-FEB-13:20 | 811646.27 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2600.19 | 0.00 | 01-JAN-00:10 | 652544.00 | 26-JUL-18:30 |
PlantLoopCoolingDemand:HVAC | 2600.19 | 0.00 | 01-JAN-00:10 | 652544.00 | 26-JUL-18:30 |
CoolingCoils:PlantLoopCoolingDemand | 2600.19 | 0.00 | 01-JAN-00:10 | 652544.00 | 26-JUL-18:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:50 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22670.76 | 155853.25 | 02-JUN-14:00 | 2771087.09 | 26-JUL-18:10 |
EnergyTransfer:Building | 4911.51 | 74140.56 | 06-JAN-11:10 | 315218.92 | 05-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 711.24 | 8454.35 | 05-FEB-04:00 | 35683.33 | 11-JUN-10:40 |
Refrigeration:EnergyTransfer | 179.95 | 879.80 | 02-FEB-04:00 | 10450.57 | 03-OCT-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.98 | 439.90 | 02-FEB-04:00 | 5225.28 | 03-OCT-07:20 |
EnergyTransfer:Plant | 8573.61 | 20605.99 | 04-OCT-14:00 | 1541249.71 | 26-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.53 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.45 | 239.20 | 02-FEB-06:00 | 2554.59 | 05-JUN-13:10 |
PlantLoopHeatingDemand:Facility | 2408.83 | 9884.22 | 17-AUG-00:10 | 717398.41 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.74 | 9825.16 | 24-AUG-00:10 | 63670.15 | 21-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 847.74 | 9825.16 | 24-AUG-00:10 | 63670.15 | 21-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 398.38 | 6.80 | 05-FEB-23:40 | 39145.17 | 25-NOV-21:40 |
Heating:EnergyTransfer | 397.08 | 0.00 | 12-JAN-18:10 | 130300.45 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.40 | 0.00 | 01-JAN-00:10 | 8155.79 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 4424.45 | 17263.44 | 04-FEB-11:30 | 311613.67 | 05-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 397.99 | 0.00 | 31-JAN-11:50 | 39145.17 | 25-NOV-21:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.22 | 0.00 | 26-OCT-01:20 | 3937.38 | 20-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 7.07 | 0.00 | 02-JAN-09:40 | 2878.28 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 29.16 | 0.00 | 01-JAN-00:10 | 3937.38 | 20-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.30 | 0.48 | 06-FEB-09:50 | 1924.59 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 1308.34 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.19 | 0.00 | 06-JAN-10:50 | 1924.59 | 02-FEB-06:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 25.73 | 0.18 | 26-DEC-13:30 | 2017.62 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.24 | 0.00 | 01-JAN-00:10 | 2017.62 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 24.48 | 0.00 | 02-JAN-03:30 | 1462.63 | 30-JUN-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.88 | 0.00 | 16-DEC-21:30 | 1212.14 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.30 | 0.00 | 01-JAN-20:20 | 1212.14 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.58 | 0.00 | 01-JAN-00:10 | 656.12 | 29-JUN-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.94 | 3631.37 | 04-FEB-11:30 | 38647.19 | 05-JAN-21:40 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 323.98 | 04-FEB-11:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.94 | 3488.56 | 04-FEB-11:30 | 38647.19 | 05-JAN-21:40 |
EnergyTransfer:Zone:CAFE_FLR_1 | 194.19 | 0.30 | 27-FEB-14:20 | 14325.99 | 04-NOV-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.22 | 0.00 | 01-JAN-00:10 | 6401.54 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 192.97 | 0.00 | 01-JAN-14:10 | 14325.99 | 04-NOV-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 741.37 | 25.62 | 05-FEB-08:40 | 40633.36 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.81 | 0.00 | 01-JAN-00:10 | 21312.25 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 740.56 | 0.00 | 06-JAN-10:50 | 40633.36 | 02-FEB-06:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 63.16 | 0.00 | 22-SEP-02:40 | 10950.86 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 31.35 | 0.00 | 01-JAN-08:10 | 7893.06 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 31.81 | 0.00 | 01-JAN-00:10 | 10950.86 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 65.05 | 0.22 | 26-SEP-20:00 | 10768.46 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 36.93 | 0.00 | 01-JAN-08:10 | 8072.86 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.12 | 0.00 | 01-JAN-00:10 | 10768.46 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 309.73 | 0.19 | 24-NOV-17:40 | 52402.76 | 20-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 48.76 | 0.00 | 01-JAN-08:20 | 27867.25 | 10-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 260.97 | 0.00 | 01-JAN-00:10 | 52402.76 | 20-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 397.77 | 0.26 | 18-OCT-09:30 | 64542.14 | 18-JUN-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 104.08 | 0.00 | 01-JAN-08:10 | 45608.72 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 293.70 | 0.00 | 01-JAN-00:10 | 64542.14 | 18-JUN-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 62.21 | 0.06 | 08-APR-18:20 | 9531.09 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 31.33 | 0.00 | 01-JAN-08:10 | 7686.41 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 30.88 | 0.00 | 01-JAN-00:10 | 9531.09 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.05 | 0.17 | 08-OCT-20:50 | 9533.16 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 36.96 | 0.00 | 01-JAN-08:10 | 7936.60 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.09 | 0.00 | 01-JAN-00:10 | 9533.16 | 02-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 119.18 | 0.10 | 03-JAN-11:00 | 9258.18 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 25.32 | 0.00 | 02-JAN-10:40 | 9258.18 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 93.86 | 0.00 | 01-JAN-00:10 | 7283.88 | 30-JUN-19:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.83 | 0.04 | 03-JUN-23:00 | 3018.23 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.01 | 0.00 | 01-JAN-08:10 | 2338.26 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.83 | 0.00 | 01-JAN-00:10 | 3018.23 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.59 | 0.08 | 28-SEP-16:40 | 2983.79 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.76 | 0.00 | 01-JAN-08:10 | 2340.00 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.83 | 0.00 | 01-JAN-00:10 | 2983.79 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 86.80 | 0.13 | 21-APR-00:50 | 13029.47 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 31.99 | 0.00 | 01-JAN-08:10 | 10016.52 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.81 | 0.00 | 01-JAN-00:10 | 13029.47 | 07-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 420.76 | 72.97 | 31-JAN-13:30 | 22280.99 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.06 | 0.00 | 01-JAN-00:10 | 5399.97 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 420.70 | 0.00 | 31-JAN-11:40 | 22280.99 | 26-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 462.49 | 52.46 | 04-FEB-14:20 | 23757.35 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 5056.51 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 462.46 | 0.00 | 31-JAN-11:40 | 23757.35 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 621.26 | 6472.00 | 05-FEB-04:00 | 30613.69 | 29-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.63 | 0.06 | 10-FEB-23:20 | 6797.86 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 13.37 | 0.00 | 01-JAN-10:50 | 6797.86 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 57.26 | 0.00 | 01-JAN-00:10 | 4291.97 | 30-JUN-15:00 |
WaterSystems:EnergyTransfer | 847.74 | 9825.16 | 24-AUG-00:10 | 63670.15 | 21-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 847.74 | 9825.16 | 24-AUG-00:10 | 63670.15 | 21-FEB-08:00 |
EnergyTransfer:HVAC | 9185.64 | 2300.26 | 08-MAY-11:10 | 943706.63 | 26-JUL-18:30 |
HeatingCoils:EnergyTransfer | 1561.09 | 0.00 | 19-MAR-19:20 | 654750.43 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1561.09 | 0.00 | 19-MAR-19:20 | 654750.43 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1561.09 | 0.00 | 19-MAR-19:20 | 654750.43 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2600.19 | 0.00 | 01-JAN-00:10 | 652544.00 | 26-JUL-18:30 |
HeatRecoveryForHeating:EnergyTransfer | 4697.02 | 0.00 | 05-JAN-08:00 | 583143.46 | 05-JAN-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 327.34 | 0.00 | 01-JAN-00:10 | 332343.17 | 04-AUG-13:00 |
Boilers:EnergyTransfer | 1540.42 | 0.00 | 24-FEB-13:20 | 650736.03 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2650.89 | 0.00 | 01-JAN-00:10 | 658104.98 | 26-JUL-18:10 |
HeatRejection:EnergyTransfer | 3444.58 | 0.00 | 01-JAN-00:10 | 846856.07 | 26-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.396 | -397.986 | 0.000 | 0.000 | 147.646 | 170.465 | 150.259 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.779 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 7.067 | -29.157 | 0.000 | 0.000 | 15.998 | 9.010 | 10.186 | 20.506 | 0.000 | 0.254 | 0.000 | 0.000 | -14.220 | 0.000 | -11.710 | -7.933 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.106 | -34.191 | 0.000 | 0.000 | 17.655 | 10.434 | 11.795 | 0.000 | 0.000 | 0.057 | 0.000 | 0.000 | 0.000 | 0.000 | -2.562 | -3.294 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.001 | -595.941 | 0.000 | 0.000 | 11.666 | 4.992 | 658.148 | 0.000 | 0.000 | 0.201 | 0.000 | 0.000 | 0.000 | 0.000 | -8.044 | -71.022 |
CAFE_FLR_1 | 0.000 | 0.000 | 1.216 | -192.976 | 0.000 | 0.000 | 199.650 | 17.892 | 14.341 | 56.940 | 0.000 | 0.601 | 0.000 | 0.000 | -41.680 | 0.000 | -30.855 | -25.130 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.808 | -740.562 | 0.000 | 0.000 | 579.721 | 143.496 | 149.002 | 75.366 | 0.000 | 1.309 | 0.000 | 0.000 | -56.467 | 0.000 | -62.786 | -89.887 |
ROOM_1_FLR_3 | 31.351 | -16.429 | 0.000 | -15.382 | 0.000 | 0.000 | 9.781 | 5.689 | 12.292 | 39.378 | 0.000 | 0.630 | 0.000 | 0.000 | -34.206 | 0.000 | -14.352 | -18.751 |
ROOM_2_FLR_3 | 36.927 | -12.997 | 0.000 | -15.124 | 0.000 | 0.000 | 9.807 | 5.688 | 12.291 | 28.713 | 0.000 | 0.604 | 0.000 | 0.000 | -36.280 | 0.000 | -14.200 | -15.427 |
ROOM_3_MULT19_FLR_3 | 48.762 | -40.541 | 0.000 | -220.427 | 0.000 | 0.000 | 0.000 | 67.926 | 228.754 | 242.424 | 0.000 | 3.404 | 0.000 | 0.000 | -184.523 | 0.000 | -93.505 | -52.273 |
ROOM_4_MULT19_FLR_3 | 104.077 | -88.396 | 0.000 | -205.297 | 0.000 | 0.000 | 186.394 | 67.944 | 228.817 | 69.302 | 0.000 | 7.437 | 0.000 | 0.000 | -206.002 | 0.000 | -82.898 | -81.376 |
ROOM_5_FLR_3 | 31.328 | -15.418 | 0.000 | -15.458 | 0.000 | 0.000 | 9.777 | 5.689 | 12.292 | 38.040 | 0.000 | 0.632 | 0.000 | 0.000 | -33.590 | 0.000 | -14.397 | -18.895 |
ROOM_6_FLR_3 | 36.957 | -11.878 | 0.000 | -15.215 | 0.000 | 0.000 | 9.802 | 5.688 | 12.291 | 27.202 | 0.000 | 0.603 | 0.000 | 0.000 | -35.502 | 0.000 | -14.244 | -15.704 |
ROOM_1_FLR_6 | 11.005 | -4.996 | 0.000 | -3.830 | 0.000 | 0.000 | 2.447 | 1.422 | 3.073 | 9.786 | 0.000 | 0.169 | 0.000 | 0.000 | -8.575 | 0.000 | -3.627 | -6.874 |
ROOM_2_FLR_6 | 12.759 | -4.055 | 0.000 | -3.772 | 0.000 | 0.000 | 2.453 | 1.422 | 3.073 | 7.126 | 0.000 | 0.160 | 0.000 | 0.000 | -9.091 | 0.000 | -3.586 | -6.488 |
ROOM_3_MULT9_FLR_6 | 31.994 | -29.509 | 0.000 | -25.301 | 0.000 | 0.000 | 21.930 | 8.046 | 27.097 | 52.560 | 0.000 | 1.183 | 0.000 | 0.000 | -39.819 | 0.000 | -17.696 | -30.485 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.060 | -420.706 | 0.000 | 0.000 | 323.889 | 34.605 | 175.857 | 7.042 | 0.000 | 0.132 | 0.000 | 0.000 | -26.154 | 0.000 | -9.457 | -85.266 |
DINING_FLR_6 | 0.000 | 0.000 | 0.035 | -462.463 | 0.000 | 0.000 | 321.582 | 34.605 | 175.857 | 6.799 | 0.000 | 0.124 | 0.000 | 0.000 | -26.843 | 0.000 | -9.541 | -40.154 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -621.243 | 0.000 | 0.000 | 29.082 | 13.327 | 550.372 | 18.104 | 0.000 | 0.094 | 35.949 | 0.000 | -17.122 | 0.000 | -8.564 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 1.241 | -24.485 | 0.000 | 0.000 | 0.000 | 16.636 | 12.472 | 0.000 | 0.000 | 0.135 | 0.000 | 0.000 | 0.000 | 0.000 | -5.459 | -0.539 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.304 | -9.581 | 0.000 | 0.000 | 0.000 | 3.310 | 3.598 | 0.000 | 0.000 | 0.095 | 4.036 | 0.000 | 0.000 | 0.000 | -3.763 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 25.324 | -93.860 | 0.000 | 0.000 | 0.000 | 109.607 | 0.000 | 34.835 | 0.000 | 0.467 | 0.000 | 0.000 | -41.639 | 0.000 | -16.536 | -18.197 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 13.365 | -57.262 | 0.000 | 0.000 | 0.000 | 29.000 | 0.000 | 16.873 | 0.000 | 0.136 | 24.233 | 0.000 | -18.908 | 0.000 | -7.436 | -0.000 |
Total Facility | 345.159 | -224.219 | 51.922 | -4200.219 | 0.000 | 0.000 | 1899.279 | 766.892 | 2451.865 | 750.995 | 0.000 | 18.425 | 64.218 | 0.000 | -830.623 | 0.000 | -435.220 | -658.474 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-21:33 | 0.00 | 0.00 | 0.00 | -39502.37 | 0.00 | 0.00 | 5675.50 | 10842.11 | 8516.89 | 0.00 | 0.00 | 0.00 | 14467.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-OCT-12:50 | 0.00 | 0.00 | 0.00 | -3937.46 | 0.00 | 0.00 | 150.60 | 204.67 | 252.59 | 6801.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.41 | -3420.23 |
RETAIL_2_FLR_1 | 03-NOV-20:35 | 0.00 | 0.00 | 0.00 | -2400.64 | 0.00 | 0.00 | 681.92 | 758.44 | 752.15 | 0.00 | 0.00 | 0.00 | 294.28 | 0.00 | -0.00 | 0.00 | -86.13 | 0.00 |
LAUNDRY_FLR_1 | 03-NOV-20:35 | 0.00 | 0.00 | 0.00 | -44489.10 | 0.00 | 0.00 | 298.41 | 362.88 | 41967.83 | 0.00 | 0.00 | 0.00 | 2160.63 | 0.00 | -0.00 | 0.00 | -300.65 | 0.00 |
CAFE_FLR_1 | 23-OCT-15:08 | 0.00 | 0.00 | 0.00 | -15001.39 | 0.00 | 0.00 | 4947.70 | 298.55 | 355.63 | 8030.36 | 0.00 | 0.00 | 2306.14 | 0.00 | -0.00 | 0.00 | -936.99 | 0.00 |
LOBBY_FLR_1 | 03-NOV-20:35 | 0.00 | 0.00 | 0.00 | -50258.96 | 0.00 | 0.00 | 22579.92 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 12385.54 | 0.00 | -2856.89 | 0.00 | -2097.73 | 0.00 |
ROOM_1_FLR_3 | 25-JUN-15:02 | 0.00 | -12475.39 | 0.00 | -711.50 | 0.00 | 0.00 | 130.71 | 35.53 | 305.54 | 9312.42 | 0.00 | 242.36 | 3160.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 27-JUN-15:02 | 0.00 | -12268.01 | 0.00 | -712.09 | 0.00 | 0.00 | 235.28 | 45.48 | 273.90 | 8349.50 | 0.00 | 201.02 | 3874.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-OCT-12:30 | 0.00 | -42115.88 | 0.00 | -10286.04 | 0.00 | 0.00 | 0.00 | 424.31 | 5097.90 | 84082.15 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -266.70 | -36935.74 |
ROOM_4_MULT19_FLR_3 | 05-MAY-18:02 | 0.00 | -65340.27 | 0.00 | -9825.26 | 0.00 | 0.00 | 6374.79 | 6026.84 | 9610.21 | 5422.99 | 0.00 | 7383.09 | 40347.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 02-SEP-15:02 | 0.00 | -10979.58 | 0.00 | -702.54 | 0.00 | 0.00 | 130.71 | 35.53 | 305.54 | 2751.32 | 0.00 | 109.40 | 8349.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 07-SEP-15:02 | 0.00 | -10789.99 | 0.00 | -703.21 | 0.00 | 0.00 | 235.28 | 45.48 | 273.90 | 2214.62 | 0.00 | 232.40 | 8491.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-SEP-15:02 | 0.00 | -3212.88 | 0.00 | -176.06 | 0.00 | 0.00 | 58.82 | 11.37 | 68.48 | 2378.54 | 0.00 | 0.00 | 902.71 | 0.00 | -0.00 | 0.00 | -30.99 | 0.00 |
ROOM_2_FLR_6 | 19-JUL-15:02 | 0.00 | -3171.25 | 0.00 | -178.50 | 0.00 | 0.00 | 58.82 | 11.37 | 68.48 | 2101.07 | 0.00 | 165.90 | 944.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 06-SEP-15:02 | 0.00 | -12758.81 | 0.00 | -1179.12 | 0.00 | 0.00 | 529.39 | 64.33 | 603.86 | 6023.01 | 0.00 | 262.35 | 6454.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -33428.67 | 0.00 | 0.00 | 18001.39 | 515.68 | 2249.30 | 0.00 | 0.00 | 0.00 | 16455.89 | 0.00 | -2935.12 | 0.00 | -858.47 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -35438.11 | 0.00 | 0.00 | 17777.90 | 515.68 | 2249.30 | 0.00 | 0.00 | 0.00 | 18731.11 | 0.00 | -2973.31 | 0.00 | -862.56 | 0.00 |
KITCHEN_FLR_6 | 20-MAR-10:37 | 0.00 | 0.00 | 0.00 | -35206.12 | 0.00 | 0.00 | 301.63 | 302.73 | 24259.91 | 2250.50 | 0.00 | 0.00 | 8302.71 | 0.00 | -0.00 | 0.00 | -211.35 | 0.00 |
MECH_FLR_1 | 19-SEP-06:33 | 0.00 | 0.00 | 0.00 | -1777.20 | 0.00 | 0.00 | 0.00 | 755.78 | 530.18 | 0.00 | 0.00 | 0.00 | 656.23 | 0.00 | -0.00 | 0.00 | -164.99 | 0.00 |
STORAGE_FLR_1 | 19-SEP-06:33 | 0.00 | 0.00 | 0.00 | -802.58 | 0.00 | 0.00 | 0.00 | 150.37 | 152.94 | 0.00 | 0.00 | 0.00 | 611.03 | 0.00 | -0.00 | 0.00 | -111.76 | 0.00 |
CORRIDOR_FLR_3 | 23-OCT-15:08 | 0.00 | 0.00 | 0.00 | -8836.76 | 0.00 | 0.00 | 0.00 | 2489.76 | 0.00 | 3839.55 | 0.00 | 0.00 | 2951.48 | 0.00 | -0.00 | 0.00 | -444.03 | 0.00 |
CORRIDOR_FLR_6 | 23-OCT-15:08 | 0.00 | 0.00 | 0.00 | -4699.90 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 2045.87 | 0.00 | 0.00 | 2203.05 | 0.00 | -0.00 | 0.00 | -207.79 | 0.00 |
Total Facility | 07-SEP-18:02 | 0.00 | -143863.23 | 0.00 | -200764.18 | 0.00 | 0.00 | 70314.69 | 58486.15 | 122326.88 | 13673.72 | 0.00 | 4310.78 | 75515.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:21 | 0.00 | 0.00 | 8915.04 | -0.00 | 0.00 | 0.00 | 3378.69 | 3872.18 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19892.05 |
RETAIL_1_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 2977.72 | -0.00 | 0.00 | 0.00 | 420.13 | 409.35 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1493.51 | 0.00 | -1058.10 | -1688.60 |
RETAIL_2_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1398.93 | -0.00 | 0.00 | 0.00 | 391.87 | 237.01 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -207.30 | -2113.02 |
LAUNDRY_FLR_1 | 04-FEB-11:11 | 0.00 | 0.00 | 2869.52 | -0.00 | 0.00 | 0.00 | 268.41 | 113.40 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -655.50 | -18916.66 |
CAFE_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 7121.28 | -0.00 | 0.00 | 0.00 | 5228.85 | 851.59 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4353.78 | 0.00 | -2761.19 | -6696.39 |
LOBBY_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 23776.30 | -0.00 | 0.00 | 0.00 | 12595.77 | 3123.28 | 3694.97 | 23344.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5177.66 | -61357.31 |
ROOM_1_FLR_3 | 09-DEC-16:13 | 8235.18 | 352.43 | 0.00 | -352.43 | 0.00 | 0.00 | 148.44 | 35.53 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3574.83 | 0.00 | -1208.34 | -3941.53 |
ROOM_2_FLR_3 | 04-FEB-19:02 | 8293.90 | 265.60 | 0.00 | -265.60 | 0.00 | 0.00 | 353.87 | 568.49 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3931.44 | 0.00 | -1203.67 | -4597.35 |
ROOM_3_MULT19_FLR_3 | 10-DEC-06:00 | 27867.33 | 3281.81 | 0.00 | -3281.81 | 0.00 | 0.00 | 0.00 | 509.17 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21783.23 | 0.00 | -6880.13 | -3634.60 |
ROOM_4_MULT19_FLR_3 | 04-FEB-11:21 | 46115.67 | 2530.06 | 0.00 | -2530.06 | 0.00 | 0.00 | 3180.27 | 424.43 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13548.56 | 0.00 | -6840.59 | -35018.88 |
ROOM_5_FLR_3 | 04-FEB-19:02 | 7919.81 | 266.40 | 0.00 | -266.40 | 0.00 | 0.00 | 353.87 | 568.55 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3988.35 | 0.00 | -1204.10 | -4166.05 |
ROOM_6_FLR_3 | 04-FEB-16:02 | 8067.16 | 257.16 | 0.00 | -257.16 | 0.00 | 0.00 | 163.33 | 35.53 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3216.68 | 0.00 | -1186.88 | -4167.96 |
ROOM_1_FLR_6 | 09-DEC-16:13 | 2394.34 | 84.71 | 0.00 | -84.71 | 0.00 | 0.00 | 37.57 | 8.88 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -893.97 | 0.00 | -301.17 | -1322.04 |
ROOM_2_FLR_6 | 09-DEC-16:13 | 2391.12 | 83.00 | 0.00 | -83.00 | 0.00 | 0.00 | 37.83 | 8.88 | 76.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -920.09 | 0.00 | -300.41 | -1293.71 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 10213.56 | 516.95 | 0.00 | -516.95 | 0.00 | 0.00 | 342.84 | 50.26 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4204.58 | 0.00 | -1378.34 | -5697.29 |
BANQUET_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6733.35 | -0.00 | 0.00 | 0.00 | 7001.78 | 687.57 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1395.67 | 0.00 | -772.78 | -19002.14 |
DINING_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6522.23 | -0.00 | 0.00 | 0.00 | 6917.03 | 687.57 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1420.63 | 0.00 | -777.74 | -18676.37 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 2059.26 | -0.00 | 0.00 | 0.00 | 0.00 | 377.89 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -442.11 | -2304.31 |
STORAGE_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1226.12 | -0.00 | 0.00 | 0.00 | 0.00 | 75.18 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -306.88 | -1083.64 |
CORRIDOR_FLR_3 | 04-FEB-11:21 | 0.00 | 0.00 | 9425.64 | -0.00 | 0.00 | 0.00 | 0.00 | 2489.76 | 0.00 | 7040.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1482.26 | -17473.78 |
CORRIDOR_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6908.02 | -0.00 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 4150.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -619.88 | -11097.65 |
Total Facility | 04-FEB-11:21 | 50076.50 | 15467.94 | 76835.49 | -15467.94 | 0.00 | 0.00 | 39220.15 | 14187.44 | 76219.04 | 152991.44 | 0.00 | 0.00 | 0.00 | 0.00 | -21877.60 | 0.00 | -36583.69 | -351068.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.4543 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 21.0791 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.0573 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 12.0573 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4706 | 2.4706 | 1.3885 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3216 | 0.3216 | 0.1807 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2325 | 0.2325 | 0.1307 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4121 | 3.4121 | 1.9176 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3763 | 1.3763 | 0.7735 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7190 | 4.7190 | 2.6521 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1794 | 2.1794 | 1.2248 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2894 | 2.2894 | 1.2866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3548 | 2.3548 | 1.3234 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2162 | 0.2162 | 0.1215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1008 | 0.1008 | 0.0567 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6670 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5947 | 0.5947 | 0.3342 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.4543 | 21.0791 | 21.4543 | 12.0573 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3885 | 1.3885 | 1.3885 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1807 | 0.1807 | 0.1807 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1307 | 0.1307 | 0.1307 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9176 | 1.9176 | 1.9176 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7735 | 0.7735 | 0.7735 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6521 | 2.6521 | 2.6521 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2248 | 1.2248 | 1.2248 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2866 | 1.2866 | 1.2866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3234 | 1.3234 | 1.3234 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1215 | 0.1215 | 0.1215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0567 | 0.0567 | 0.0567 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6670 | 0.6670 | 0.6670 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3342 | 0.3342 | 0.3342 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.0573 | 12.0573 | 12.0573 | 12.0573 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 273.67 |
Number of hours cooling loads not met | 414.17 |
Number of hours not met | 687.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 2050.38 | 811646.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 793.69 | 206061.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 766.89 | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 226.43 | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.46 | 1873.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 577.88 | 37691.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 81.32 | 5635.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 234.50 | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4748.58 | 2279.84 | 181996.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.22 | 1972.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.85 | 1201.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.19 | 5560.56 |
Natural Gas | 1788.85 | 6119.07 |
Additional | 0.00 | 0.00 |
Total | 3595.04 | 11679.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.60 |
Space Heating | 0.00 |
Space Cooling | 69.96 |
Fans (All) | 50.94 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 490.12 |
Subtotal | 490.12 |
Natural Gas [MJ/m2] | |
Space Heating | 180.73 |
Service Water Heating | 200.95 |
Miscellaneous (All) | 539.35 |
Subtotal | 539.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.57 |
Space Heating | 17.56 |
Space Cooling | 6.80 |
Fans (All) | 4.95 |
Service Water Heating | 20.30 |
Receptacle Equipment | 30.26 |
Miscellaneous | 13.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2842. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.640639E+12 |
February | 0.000 | 0.451489E+12 |
March | 0.000 | 0.164095E+12 |
April | 0.000 | 0.718893E+11 |
May | 0.000 | 0.250027E+11 |
June | 0.000 | 0.153921E+11 |
July | 0.000 | 0.704129E+10 |
August | 0.000 | 0.844601E+10 |
September | 0.000 | 0.256951E+11 |
October | 0.000 | 0.544829E+11 |
November | 0.000 | 0.216074E+12 |
December | 0.000 | 0.370135E+12 |
Annual Sum or Average | 0.205038E+13 | |
Minimum of Months | 0.000 | 0.704129E+10 |
Maximum of Months | 0.000 | 0.640639E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348664E+11 | 39145.65 | 19-JAN-01:51 | -23.9 | -24.0 | 0.696041E+10 | 4682.89 | 04-JAN-22:10 | -17.1 | -17.4 |
February | 0.276626E+11 | 33846.05 | 02-FEB-06:02 | -36.7 | -36.8 | 0.559237E+10 | 4458.58 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.273448E+11 | 19835.81 | 24-MAR-08:62 | 8.48 | 5.58 | 0.677084E+10 | 4377.04 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.250357E+11 | 18683.40 | 07-APR-23:00 | 7.20 | 3.68 | 0.624291E+10 | 4072.31 | 27-APR-21:10 | 2.80 | 2.27 |
May | 0.285809E+11 | 18311.19 | 01-MAY-08:62 | 7.80 | 5.38 | 0.644490E+10 | 4181.81 | 17-MAY-21:19 | 8.90 | 7.13 |
June | 0.317477E+11 | 18253.47 | 02-JUN-23:10 | 8.72 | 7.86 | 0.629014E+10 | 4301.78 | 05-JUN-21:10 | 11.70 | 11.34 |
July | 0.360836E+11 | 18282.47 | 23-JUL-03:52 | 10.00 | 9.66 | 0.654309E+10 | 4177.38 | 11-JUL-21:10 | 15.92 | 14.61 |
August | 0.384691E+11 | 19554.89 | 07-AUG-05:08 | 8.80 | 7.95 | 0.707094E+10 | 4521.22 | 18-AUG-21:10 | 16.02 | 13.73 |
September | 0.376045E+11 | 25115.65 | 27-SEP-21:00 | 8.30 | 5.62 | 0.741712E+10 | 4927.43 | 26-SEP-21:49 | 7.30 | 6.23 |
October | 0.387622E+11 | 25137.60 | 19-OCT-20:38 | 7.77 | 5.23 | 0.813496E+10 | 4910.43 | 19-OCT-21:30 | 7.10 | 4.79 |
November | 0.368172E+11 | 39503.48 | 25-NOV-21:33 | -24.0 | -24.4 | 0.776819E+10 | 4837.07 | 06-NOV-02:09 | 11.10 | 9.38 |
December | 0.350109E+11 | 17658.27 | 01-DEC-22:00 | -3.9 | -4.7 | 0.797051E+10 | 4836.98 | 01-DEC-22:19 | -3.7 | -4.5 |
Annual Sum or Average | 0.397986E+12 | 0.832064E+11 | ||||||||
Minimum of Months | 0.250357E+11 | 17658.27 | -36.7 | -36.8 | 0.559237E+10 | 4072.31 | -17.1 | -17.4 | ||
Maximum of Months | 0.387622E+11 | 39503.48 | 10.00 | 9.66 | 0.813496E+10 | 4927.43 | 16.02 | 14.61 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325335E+09 | 1949.91 | 12-JAN-12:30 | 1.95 | 0.37 | 0.587444E+09 | 364.17 | 28-JAN-02:39 | -22.8 | -23.1 |
February | 0.585190E+09 | 3035.29 | 24-FEB-14:04 | 7.88 | 5.24 | 0.513493E+09 | 372.94 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.123444E+10 | 2355.35 | 20-MAR-10:31 | 9.43 | 6.42 | 0.630610E+09 | 408.56 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.203743E+10 | 2922.31 | 15-APR-13:20 | 28.67 | 20.38 | 0.618828E+09 | 428.92 | 18-APR-21:10 | 16.32 | 13.38 |
May | 0.336581E+10 | 2121.58 | 31-MAY-18:40 | 26.47 | 18.89 | 0.637017E+09 | 428.52 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.409635E+10 | 2253.45 | 26-JUN-18:40 | 28.87 | 21.99 | 0.636940E+09 | 454.50 | 26-JUN-21:10 | 25.40 | 21.25 |
July | 0.466856E+10 | 2222.49 | 30-JUL-13:20 | 26.87 | 20.17 | 0.661713E+09 | 443.67 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.466635E+10 | 2365.40 | 29-AUG-13:30 | 23.60 | 16.38 | 0.671488E+09 | 442.04 | 22-AUG-21:10 | 22.02 | 19.96 |
September | 0.384289E+10 | 3749.51 | 07-SEP-13:00 | 31.70 | 18.03 | 0.647364E+09 | 464.15 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.263444E+10 | 3937.38 | 20-OCT-12:50 | 21.68 | 12.53 | 0.645220E+09 | 440.56 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 0.117152E+10 | 3602.25 | 04-NOV-13:10 | 13.98 | 6.79 | 0.602511E+09 | 413.76 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.528885E+09 | 2988.61 | 03-DEC-13:00 | 5.60 | 2.40 | 0.622924E+09 | 364.15 | 11-DEC-23:00 | -20.0 | -20.3 |
Annual Sum or Average | 0.291572E+11 | 0.747555E+10 | ||||||||
Minimum of Months | 0.325335E+09 | 1949.91 | 1.95 | 0.37 | 0.513493E+09 | 364.15 | -22.8 | -23.1 | ||
Maximum of Months | 0.466856E+10 | 3937.38 | 31.70 | 21.99 | 0.671488E+09 | 464.15 | 25.40 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203540E+10 | 2152.26 | 05-JAN-21:22 | -23.6 | -23.9 | 0.709171E+09 | 519.15 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.210141E+10 | 1924.59 | 02-FEB-06:00 | -36.7 | -36.8 | 0.631238E+09 | 533.09 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.250767E+10 | 1921.24 | 24-MAR-08:62 | 8.48 | 5.58 | 0.799977E+09 | 554.55 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.273962E+10 | 1898.84 | 19-APR-03:10 | 8.62 | 7.46 | 0.802413E+09 | 569.53 | 19-APR-21:40 | 7.07 | 3.65 |
May | 0.320694E+10 | 1888.47 | 18-MAY-23:17 | 8.87 | 6.46 | 0.843754E+09 | 560.80 | 22-MAY-21:30 | 9.15 | 7.84 |
June | 0.344256E+10 | 1845.48 | 02-JUN-23:10 | 8.72 | 7.86 | 0.821159E+09 | 558.48 | 30-JUN-21:10 | 22.03 | 17.03 |
July | 0.373374E+10 | 1803.61 | 23-JUL-03:52 | 10.00 | 9.66 | 0.842683E+09 | 554.07 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.370259E+10 | 1846.40 | 07-AUG-05:08 | 8.80 | 7.95 | 0.857692E+09 | 559.40 | 04-AUG-21:10 | 18.30 | 17.90 |
September | 0.328747E+10 | 1981.61 | 19-SEP-06:33 | 6.83 | 6.04 | 0.836846E+09 | 569.51 | 08-SEP-21:10 | 17.38 | 14.80 |
October | 0.291026E+10 | 1991.58 | 25-OCT-01:12 | 8.57 | 5.29 | 0.853528E+09 | 568.43 | 19-OCT-21:30 | 7.10 | 4.79 |
November | 0.242411E+10 | 2400.89 | 03-NOV-20:35 | 6.67 | 3.97 | 0.770201E+09 | 568.72 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.209951E+10 | 1113.03 | 05-DEC-22:10 | -7.1 | -9.3 | 0.758196E+09 | 513.24 | 05-DEC-22:10 | -7.1 | -9.3 |
Annual Sum or Average | 0.341913E+11 | 0.952686E+10 | ||||||||
Minimum of Months | 0.203540E+10 | 1113.03 | -36.7 | -36.8 | 0.631238E+09 | 513.24 | -7.1 | -9.3 | ||
Maximum of Months | 0.373374E+10 | 2400.89 | 10.00 | 9.66 | 0.857692E+09 | 569.53 | 24.22 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543877E+09 | 992.23 | 19-JAN-08:00 | -28.3 | -28.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.810302E+09 | 992.55 | 02-FEB-07:20 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.141452E+10 | 1677.96 | 24-MAR-08:62 | 8.48 | 5.58 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.202197E+10 | 1630.49 | 19-APR-03:10 | 8.62 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.273079E+10 | 1615.44 | 18-MAY-23:17 | 8.87 | 6.46 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.302446E+10 | 1592.75 | 02-JUN-23:10 | 8.72 | 7.86 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.330937E+10 | 1577.35 | 23-JUL-03:52 | 10.00 | 9.66 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.326857E+10 | 1608.39 | 07-AUG-05:08 | 8.80 | 7.95 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.282289E+10 | 1777.22 | 19-SEP-06:33 | 6.83 | 6.04 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.235706E+10 | 1754.73 | 03-OCT-06:35 | 6.83 | 5.88 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.150396E+10 | 1385.42 | 07-NOV-03:42 | 10.60 | 9.72 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.677022E+09 | 841.68 | 04-DEC-22:10 | 1.78 | 0.08 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.244848E+11 | 0.00 | ||||||||
Minimum of Months | 0.543877E+09 | 841.68 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.330937E+10 | 1777.22 | 10.60 | 9.72 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23468880.19 | 356.34 | 13-JAN-22:00 | 2.20 | 0.77 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 76618880.09 | 367.82 | 24-FEB-22:10 | 1.93 | 1.42 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.368073E+09 | 761.60 | 24-MAR-08:62 | 8.48 | 5.58 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.727598E+09 | 752.46 | 19-APR-03:10 | 8.62 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.122354E+10 | 730.03 | 01-MAY-08:62 | 7.80 | 5.38 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.138305E+10 | 718.65 | 02-JUN-23:10 | 8.72 | 7.86 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.152137E+10 | 719.06 | 23-JUL-03:52 | 10.00 | 9.66 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.149882E+10 | 734.76 | 07-AUG-05:08 | 8.80 | 7.95 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.127503E+10 | 802.58 | 19-SEP-06:33 | 6.83 | 6.04 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.100254E+10 | 790.97 | 03-OCT-06:35 | 6.83 | 5.88 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.439809E+09 | 632.27 | 07-NOV-03:42 | 10.60 | 9.72 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 40588581.12 | 314.19 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.958050E+10 | 0.00 | ||||||||
Minimum of Months | 23468880.19 | 314.19 | 1.93 | 0.77 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.152137E+10 | 802.58 | 10.60 | 9.72 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477511E+11 | 40512.01 | 05-JAN-21:32 | -23.7 | -24.0 | 0.512503E+09 | 398.02 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.437832E+11 | 36380.35 | 24-FEB-21:00 | 2.20 | 1.49 | 0.456606E+09 | 399.74 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.492879E+11 | 39296.60 | 29-MAR-19:30 | 8.05 | 7.49 | 0.578877E+09 | 454.74 | 29-MAR-21:10 | 7.70 | 7.14 |
April | 0.487395E+11 | 41226.26 | 19-APR-20:00 | 8.90 | 4.89 | 0.557408E+09 | 428.42 | 19-APR-21:40 | 7.07 | 3.65 |
May | 0.520556E+11 | 40169.60 | 02-MAY-19:56 | 7.80 | 3.80 | 0.565759E+09 | 432.21 | 17-MAY-21:19 | 8.90 | 7.13 |
June | 0.513444E+11 | 38601.33 | 01-JUN-19:56 | 10.00 | 8.78 | 0.534913E+09 | 403.28 | 01-JUN-21:10 | 9.90 | 8.78 |
July | 0.532543E+11 | 38113.42 | 03-JUL-20:00 | 26.70 | 23.79 | 0.542800E+09 | 381.53 | 07-JUL-21:10 | 18.22 | 16.14 |
August | 0.533470E+11 | 38128.85 | 03-AUG-20:00 | 25.00 | 23.43 | 0.549029E+09 | 381.55 | 09-AUG-21:10 | 17.62 | 14.82 |
September | 0.505676E+11 | 41495.14 | 27-SEP-19:57 | 8.90 | 6.15 | 0.544722E+09 | 437.39 | 18-SEP-21:19 | 8.70 | 8.29 |
October | 0.506457E+11 | 40180.13 | 19-OCT-20:38 | 7.77 | 5.23 | 0.579892E+09 | 454.25 | 05-OCT-21:10 | 6.70 | 4.83 |
November | 0.476391E+11 | 44476.59 | 03-NOV-20:35 | 6.67 | 3.97 | 0.549127E+09 | 507.99 | 03-NOV-20:40 | 6.67 | 3.97 |
December | 0.475250E+11 | 35867.20 | 01-DEC-21:00 | -5.0 | -5.7 | 0.570860E+09 | 396.33 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.595940E+12 | 0.654250E+10 | ||||||||
Minimum of Months | 0.437832E+11 | 35867.20 | -23.7 | -24.0 | 0.456606E+09 | 381.53 | -3.8 | -4.6 | ||
Maximum of Months | 0.533470E+11 | 44476.59 | 26.70 | 23.79 | 0.579892E+09 | 507.99 | 18.22 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869068E+10 | 8531.65 | 12-JAN-12:30 | 1.95 | 0.37 | 0.795717E+10 | 5882.79 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.104297E+11 | 12790.87 | 24-FEB-14:02 | 7.88 | 5.24 | 0.721483E+10 | 6069.09 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.135719E+11 | 11782.81 | 24-MAR-01:02 | 8.80 | 5.42 | 0.901269E+10 | 6460.52 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.154246E+11 | 11571.28 | 15-APR-13:00 | 28.30 | 20.27 | 0.911004E+10 | 6461.46 | 19-APR-21:40 | 7.07 | 3.65 |
May | 0.190355E+11 | 11227.55 | 18-MAY-23:17 | 8.87 | 6.46 | 0.969477E+10 | 6455.02 | 13-MAY-23:49 | 10.28 | 10.23 |
June | 0.206754E+11 | 11005.55 | 02-JUN-01:12 | 9.27 | 8.90 | 0.953172E+10 | 6459.41 | 26-JUN-21:49 | 24.60 | 21.01 |
July | 0.225194E+11 | 10576.64 | 23-JUL-03:52 | 10.00 | 9.66 | 0.980633E+10 | 6440.97 | 25-JUL-21:40 | 25.77 | 21.14 |
August | 0.224961E+11 | 10866.22 | 07-AUG-02:12 | 9.23 | 8.05 | 0.100124E+11 | 6459.52 | 29-AUG-22:10 | 14.40 | 12.80 |
September | 0.201129E+11 | 12955.29 | 16-SEP-13:10 | 28.48 | 18.06 | 0.968699E+10 | 6461.77 | 06-SEP-22:19 | 17.97 | 15.65 |
October | 0.175893E+11 | 15000.94 | 23-OCT-15:08 | 8.02 | 3.52 | 0.970576E+10 | 6462.20 | 21-OCT-03:09 | 11.03 | 8.48 |
November | 0.126955E+11 | 14325.99 | 04-NOV-12:40 | 13.53 | 6.71 | 0.860773E+10 | 6459.82 | 06-NOV-04:10 | 10.60 | 9.72 |
December | 0.973300E+10 | 12121.27 | 03-DEC-12:50 | 5.50 | 2.39 | 0.846564E+10 | 5657.34 | 01-DEC-22:40 | -3.5 | -4.3 |
Annual Sum or Average | 0.192974E+12 | 0.108806E+12 | ||||||||
Minimum of Months | 0.869068E+10 | 8531.65 | 1.95 | 0.37 | 0.721483E+10 | 5657.34 | -3.5 | -4.3 | ||
Maximum of Months | 0.225194E+11 | 15000.94 | 28.48 | 20.27 | 0.100124E+11 | 6462.20 | 25.77 | 21.14 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477106E+11 | 44223.62 | 05-JAN-21:22 | -23.6 | -23.9 | 0.249223E+11 | 18480.83 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.470298E+11 | 40633.36 | 02-FEB-06:00 | -36.7 | -36.8 | 0.224860E+11 | 18831.51 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.552760E+11 | 41282.75 | 24-MAR-01:02 | 8.80 | 5.42 | 0.284551E+11 | 19185.97 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.589811E+11 | 40726.18 | 20-APR-20:03 | 7.80 | 2.93 | 0.283351E+11 | 19247.10 | 19-APR-21:30 | 7.25 | 3.75 |
May | 0.684211E+11 | 40189.37 | 18-MAY-23:17 | 8.87 | 6.46 | 0.298013E+11 | 19186.30 | 19-MAY-21:40 | 7.77 | 5.20 |
June | 0.725153E+11 | 39450.07 | 02-JUN-23:10 | 8.72 | 7.86 | 0.287994E+11 | 19185.65 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.780725E+11 | 38217.24 | 23-JUL-03:52 | 10.00 | 9.66 | 0.293873E+11 | 18965.06 | 28-JUL-22:10 | 19.22 | 17.09 |
August | 0.776907E+11 | 39295.47 | 07-AUG-05:08 | 8.80 | 7.95 | 0.299813E+11 | 19184.29 | 17-AUG-21:19 | 15.53 | 13.12 |
September | 0.698750E+11 | 40810.08 | 19-SEP-06:33 | 6.83 | 6.04 | 0.293684E+11 | 19239.32 | 25-SEP-21:49 | 10.00 | 6.67 |
October | 0.632142E+11 | 46182.00 | 19-OCT-22:33 | 6.93 | 4.64 | 0.302421E+11 | 19320.70 | 19-OCT-21:30 | 7.10 | 4.79 |
November | 0.537465E+11 | 50266.03 | 03-NOV-20:35 | 6.67 | 3.97 | 0.273278E+11 | 19185.93 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.480254E+11 | 24248.51 | 04-DEC-23:10 | 2.30 | 0.32 | 0.268628E+11 | 18151.93 | 05-DEC-23:10 | -6.8 | -9.1 |
Annual Sum or Average | 0.740558E+12 | 0.335969E+12 | ||||||||
Minimum of Months | 0.470298E+11 | 24248.51 | -36.7 | -36.8 | 0.224860E+11 | 18151.93 | -6.8 | -9.1 | ||
Maximum of Months | 0.780725E+11 | 50266.03 | 10.00 | 9.66 | 0.302421E+11 | 19320.70 | 19.22 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24285742.85 | 2678.03 | 12-JAN-16:02 | 2.62 | 1.03 | 92425881.39 | 56.69 | 05-JAN-22:19 | -24.1 | -24.4 |
February | 60158798.47 | 2954.72 | 24-FEB-16:02 | 8.12 | 5.75 | 83093442.49 | 56.69 | 28-FEB-01:49 | -16.0 | -16.5 |
March | 0.154699E+09 | 3079.94 | 25-MAR-15:01 | 18.72 | 10.43 | 94668838.54 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.541154E+09 | 3250.29 | 16-APR-18:02 | 26.42 | 19.76 | 92902520.49 | 56.69 | 17-APR-21:30 | 13.60 | 9.35 |
May | 0.858876E+09 | 3243.99 | 31-MAY-15:02 | 29.72 | 19.53 | 97557461.00 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.144847E+10 | 3296.54 | 25-JUN-15:02 | 32.20 | 22.41 | 95027826.67 | 56.70 | 26-JUN-21:49 | 24.60 | 21.01 |
July | 0.176990E+10 | 3286.36 | 29-JUL-15:02 | 28.12 | 19.76 | 98488602.65 | 56.70 | 03-JUL-21:30 | 23.85 | 22.71 |
August | 0.157802E+10 | 3289.13 | 22-AUG-15:02 | 30.00 | 22.35 | 98539788.52 | 56.70 | 03-AUG-21:10 | 24.32 | 23.15 |
September | 0.105761E+10 | 3258.61 | 20-SEP-15:02 | 22.12 | 11.87 | 94442593.31 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.326920E+09 | 3075.76 | 19-OCT-15:02 | 18.53 | 10.63 | 96026690.42 | 56.69 | 20-OCT-21:40 | 13.90 | 9.50 |
November | 99638725.56 | 3013.26 | 03-NOV-15:01 | 15.92 | 9.54 | 90923791.77 | 56.69 | 07-NOV-22:10 | 12.80 | 11.46 |
December | 33354876.15 | 2664.59 | 02-DEC-16:01 | 4.95 | 2.78 | 92891718.21 | 56.69 | 28-DEC-05:00 | -17.2 | -17.5 |
Annual Sum or Average | 0.795308E+10 | 0.112699E+10 | ||||||||
Minimum of Months | 24285742.85 | 2664.59 | 2.62 | 1.03 | 83093442.49 | 56.69 | -24.1 | -24.4 | ||
Maximum of Months | 0.176990E+10 | 3296.54 | 32.20 | 22.41 | 98539788.52 | 56.70 | 24.60 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9845208.57 | 749.16 | 12-JAN-16:03 | 2.62 | 1.03 | 91933138.87 | 56.69 | 19-JAN-02:20 | -24.3 | -24.4 |
February | 29336977.81 | 2681.47 | 24-FEB-16:02 | 8.12 | 5.75 | 81956700.60 | 56.69 | 28-FEB-00:49 | -15.5 | -16.0 |
March | 92029663.78 | 2907.48 | 25-MAR-15:01 | 18.72 | 10.43 | 93826909.35 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.440442E+09 | 3185.98 | 16-APR-18:02 | 26.42 | 19.76 | 92384603.43 | 56.69 | 17-APR-21:10 | 13.80 | 9.26 |
May | 0.791483E+09 | 3182.05 | 06-MAY-15:01 | 20.92 | 11.57 | 97325175.51 | 56.70 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.140735E+10 | 3244.83 | 27-JUN-15:02 | 30.50 | 21.67 | 94974253.19 | 56.70 | 13-JUN-21:10 | 24.40 | 20.44 |
July | 0.169867E+10 | 3212.89 | 05-JUL-18:02 | 26.52 | 21.26 | 98416382.37 | 56.70 | 05-JUL-21:19 | 22.07 | 20.22 |
August | 0.144477E+10 | 3210.33 | 02-AUG-18:02 | 27.62 | 22.31 | 98382435.77 | 56.69 | 03-AUG-02:00 | 23.90 | 22.63 |
September | 0.850807E+09 | 3235.54 | 06-SEP-15:02 | 32.02 | 20.85 | 93958560.56 | 56.69 | 10-SEP-23:10 | 22.70 | 17.29 |
October | 0.193533E+09 | 2872.31 | 19-OCT-15:02 | 18.53 | 10.63 | 94850609.66 | 56.69 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 57789682.25 | 2835.89 | 03-NOV-15:01 | 15.92 | 9.54 | 90247188.49 | 56.69 | 26-NOV-02:49 | -24.9 | -25.2 |
December | 14354409.02 | 669.56 | 02-DEC-16:03 | 4.95 | 2.78 | 92321257.80 | 56.69 | 28-DEC-03:30 | -15.8 | -16.1 |
Annual Sum or Average | 0.703041E+10 | 0.112058E+10 | ||||||||
Minimum of Months | 9845208.57 | 669.56 | 2.62 | 1.03 | 81956700.60 | 56.69 | -24.9 | -25.2 | ||
Maximum of Months | 0.169867E+10 | 3244.83 | 32.02 | 22.31 | 98416382.37 | 56.70 | 24.40 | 22.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58302609.95 | 360.38 | 30-JAN-11:30 | -26.1 | -26.4 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.101408E+09 | 356.34 | 01-FEB-13:10 | -26.7 | -27.0 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.148847E+09 | 358.55 | 24-MAR-13:30 | 12.75 | 6.48 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.235904E+09 | 549.25 | 18-APR-15:30 | 26.65 | 20.04 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.310166E+09 | 399.64 | 05-MAY-17:00 | 26.70 | 14.31 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.447332E+09 | 526.62 | 18-JUN-20:20 | 26.30 | 20.76 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.522758E+09 | 479.57 | 25-JUL-19:30 | 26.65 | 21.77 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.530743E+09 | 503.19 | 29-AUG-13:20 | 23.50 | 16.48 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.493902E+09 | 660.55 | 08-SEP-12:50 | 29.90 | 19.28 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.338387E+09 | 689.51 | 20-OCT-12:30 | 21.45 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.168755E+09 | 666.46 | 04-NOV-12:30 | 13.35 | 6.67 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 77293700.74 | 301.51 | 03-DEC-13:30 | 5.60 | 2.31 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.343380E+10 | 0.00 | ||||||||
Minimum of Months | 58302609.95 | 301.51 | -26.7 | -27.0 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.530743E+09 | 689.51 | 29.90 | 21.77 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28969012.49 | 402.34 | 30-JAN-08:61 | -29.3 | -29.5 | 91608584.18 | 56.69 | 27-JAN-22:40 | -21.7 | -22.0 |
February | 39617225.49 | 339.64 | 24-FEB-19:04 | 3.30 | 2.56 | 81105002.54 | 56.69 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.115907E+09 | 770.03 | 28-MAR-18:02 | 13.03 | 9.11 | 94796413.90 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.255409E+09 | 918.14 | 16-APR-18:02 | 26.42 | 19.76 | 92536671.33 | 56.69 | 17-APR-21:30 | 13.60 | 9.35 |
May | 0.494820E+09 | 989.01 | 05-MAY-18:02 | 25.22 | 13.54 | 96823629.74 | 56.69 | 15-MAY-21:00 | 12.20 | 11.83 |
June | 0.672202E+09 | 939.16 | 29-JUN-18:02 | 28.62 | 20.21 | 94341379.68 | 56.69 | 26-JUN-21:40 | 24.80 | 21.07 |
July | 0.738789E+09 | 921.61 | 02-JUL-18:02 | 28.12 | 21.01 | 97462443.74 | 56.69 | 03-JUL-21:19 | 24.03 | 22.76 |
August | 0.677867E+09 | 936.48 | 09-AUG-18:02 | 25.13 | 17.32 | 97417078.64 | 56.69 | 15-AUG-21:10 | 15.22 | 14.06 |
September | 0.474347E+09 | 926.87 | 08-SEP-18:02 | 25.55 | 17.45 | 93570660.29 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.217313E+09 | 765.12 | 01-OCT-08:62 | 10.72 | 8.44 | 95545278.65 | 56.69 | 10-OCT-21:10 | 10.67 | 9.78 |
November | 0.111915E+09 | 741.09 | 04-NOV-08:62 | 2.77 | 0.70 | 91214736.52 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 37301266.36 | 329.62 | 04-DEC-19:05 | 1.20 | -0.5 | 93257641.35 | 56.69 | 13-DEC-00:30 | -13.1 | -13.4 |
Annual Sum or Average | 0.386446E+10 | 0.111968E+10 | ||||||||
Minimum of Months | 28969012.49 | 329.62 | -29.3 | -29.5 | 81105002.54 | 56.69 | -21.7 | -22.0 | ||
Maximum of Months | 0.738789E+09 | 989.01 | 28.62 | 21.01 | 97462443.74 | 56.69 | 24.80 | 22.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22899862.17 | 583.04 | 30-JAN-08:61 | -29.3 | -29.5 | 92156970.73 | 56.69 | 30-JAN-00:10 | -25.7 | -25.9 |
February | 52347637.65 | 2464.72 | 24-FEB-09:02 | 3.07 | 0.60 | 82549804.11 | 56.69 | 05-FEB-04:19 | -16.7 | -17.2 |
March | 0.150035E+09 | 2659.71 | 28-MAR-15:01 | 16.93 | 10.62 | 94812648.86 | 56.69 | 19-MAR-23:10 | 14.22 | 11.44 |
April | 0.460118E+09 | 2878.12 | 18-APR-15:02 | 27.75 | 20.45 | 92952259.92 | 56.69 | 15-APR-23:40 | 20.20 | 16.32 |
May | 0.910422E+09 | 2884.34 | 06-MAY-15:01 | 20.92 | 11.57 | 98053630.46 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.145393E+10 | 2911.16 | 26-JUN-15:02 | 31.20 | 21.86 | 95333416.41 | 56.70 | 13-JUN-21:10 | 24.40 | 20.44 |
July | 0.170212E+10 | 2894.88 | 01-JUL-15:02 | 27.20 | 19.05 | 98804828.58 | 56.70 | 26-JUL-21:10 | 25.40 | 23.28 |
August | 0.150049E+10 | 2910.73 | 09-AUG-15:02 | 27.20 | 17.24 | 98795749.20 | 56.69 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.105283E+10 | 2920.51 | 02-SEP-15:02 | 26.78 | 17.24 | 94762226.24 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.289572E+09 | 2727.59 | 19-OCT-15:02 | 18.53 | 10.63 | 96175105.52 | 56.69 | 20-OCT-21:30 | 13.90 | 9.48 |
November | 89976388.21 | 2662.66 | 03-NOV-15:01 | 15.92 | 9.54 | 90894650.88 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 34534293.72 | 1013.64 | 03-DEC-09:02 | -1.5 | -1.7 | 92819253.84 | 56.69 | 10-DEC-03:00 | -21.7 | -22.1 |
Annual Sum or Average | 0.771929E+10 | 0.112811E+10 | ||||||||
Minimum of Months | 22899862.17 | 583.04 | -29.3 | -29.5 | 82549804.11 | 56.69 | -25.7 | -25.9 | ||
Maximum of Months | 0.170212E+10 | 2920.51 | 31.20 | 21.86 | 98804828.58 | 56.70 | 25.40 | 23.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9748726.53 | 577.78 | 30-JAN-08:61 | -29.3 | -29.5 | 91607362.32 | 56.69 | 19-JAN-23:40 | -23.1 | -23.4 |
February | 25159475.08 | 1895.46 | 24-FEB-09:02 | 3.07 | 0.60 | 81322040.51 | 56.69 | 18-FEB-01:19 | -15.2 | -15.6 |
March | 92851502.63 | 2485.68 | 28-MAR-08:62 | 5.37 | 3.26 | 93935535.64 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.365483E+09 | 2826.35 | 15-APR-18:02 | 27.85 | 18.46 | 92427922.32 | 56.69 | 18-APR-22:19 | 13.67 | 11.55 |
May | 0.839231E+09 | 2856.61 | 06-MAY-15:01 | 20.92 | 11.57 | 97850777.57 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.141044E+10 | 2865.72 | 26-JUN-15:02 | 31.20 | 21.86 | 95295144.44 | 56.70 | 26-JUN-21:40 | 24.80 | 21.07 |
July | 0.162729E+10 | 2853.27 | 02-JUL-18:02 | 28.12 | 21.01 | 98770605.86 | 56.69 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.136085E+10 | 2838.82 | 09-AUG-15:02 | 27.20 | 17.24 | 98701467.95 | 56.69 | 04-AUG-02:39 | 22.80 | 22.43 |
September | 0.834995E+09 | 2873.32 | 07-SEP-15:02 | 31.70 | 18.51 | 94378398.19 | 56.69 | 10-SEP-23:10 | 22.70 | 17.29 |
October | 0.149813E+09 | 2408.96 | 20-OCT-08:62 | 9.70 | 7.05 | 94939901.91 | 56.69 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 45391623.80 | 1157.79 | 04-NOV-08:62 | 2.77 | 0.70 | 90183947.75 | 56.69 | 24-NOV-04:40 | -15.0 | -15.3 |
December | 12193481.77 | 724.59 | 03-DEC-09:03 | -1.5 | -1.7 | 92310908.89 | 56.69 | 16-DEC-03:09 | -13.4 | -13.9 |
Annual Sum or Average | 0.677345E+10 | 0.112172E+10 | ||||||||
Minimum of Months | 9748726.53 | 577.78 | -29.3 | -29.5 | 81322040.51 | 56.69 | -23.1 | -23.4 | ||
Maximum of Months | 0.162729E+10 | 2873.32 | 31.70 | 21.86 | 98770605.86 | 56.70 | 24.80 | 22.43 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339034E+09 | 1286.47 | 31-JAN-04:00 | -31.1 | -31.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.453026E+09 | 2174.00 | 24-FEB-16:10 | 8.12 | 5.75 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.783424E+09 | 1973.10 | 20-MAR-10:34 | 9.43 | 6.42 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.163602E+10 | 2099.50 | 19-APR-03:10 | 8.62 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.294028E+10 | 1729.84 | 31-MAY-19:20 | 25.53 | 18.52 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.362067E+10 | 1931.14 | 22-JUN-01:53 | 10.00 | 9.40 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.414766E+10 | 1974.38 | 23-JUL-03:52 | 10.00 | 9.66 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.402531E+10 | 1778.09 | 16-AUG-06:05 | 9.97 | 9.97 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.308056E+10 | 1911.12 | 21-SEP-00:24 | 9.45 | 7.34 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.168322E+10 | 2209.20 | 23-OCT-15:08 | 8.02 | 3.52 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.632726E+09 | 1401.41 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.123021E+09 | 1072.48 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.234650E+11 | 0.00 | ||||||||
Minimum of Months | 0.123021E+09 | 1072.48 | -31.1 | -31.3 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.414766E+10 | 2209.20 | 25.53 | 18.52 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15286384.69 | 2356.90 | 12-JAN-16:02 | 2.62 | 1.03 | 92113992.27 | 56.69 | 31-JAN-23:49 | -23.7 | -24.0 |
February | 52292314.20 | 3062.25 | 24-FEB-16:02 | 8.12 | 5.75 | 82871076.32 | 56.69 | 16-FEB-01:00 | -13.9 | -14.4 |
March | 0.137299E+09 | 3180.52 | 25-MAR-15:01 | 18.72 | 10.43 | 94270418.35 | 56.70 | 19-MAR-23:10 | 14.22 | 11.44 |
April | 0.580444E+09 | 3377.63 | 16-APR-18:02 | 26.42 | 19.76 | 92731524.18 | 56.69 | 17-APR-21:19 | 13.70 | 9.31 |
May | 0.952987E+09 | 3370.93 | 06-MAY-15:01 | 20.92 | 11.57 | 97711787.31 | 56.70 | 27-MAY-02:39 | 14.40 | 13.71 |
June | 0.166624E+10 | 3373.26 | 13-JUN-18:02 | 27.62 | 21.57 | 95122834.90 | 56.70 | 02-JUN-21:40 | 10.17 | 8.67 |
July | 0.204017E+10 | 3384.22 | 25-JUL-15:02 | 28.98 | 22.96 | 98594454.50 | 56.70 | 03-JUL-21:00 | 23.30 | 22.56 |
August | 0.179236E+10 | 3383.45 | 28-AUG-15:02 | 27.30 | 22.46 | 98606951.20 | 56.70 | 02-AUG-21:19 | 24.23 | 21.62 |
September | 0.116115E+10 | 3389.04 | 20-SEP-15:02 | 22.12 | 11.87 | 94387900.52 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.316544E+09 | 3185.65 | 19-OCT-15:02 | 18.53 | 10.63 | 95728336.30 | 56.69 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 86080361.42 | 3125.42 | 03-NOV-15:01 | 15.92 | 9.54 | 90572658.74 | 56.69 | 24-NOV-02:00 | -13.9 | -14.2 |
December | 25335582.32 | 2088.48 | 02-DEC-16:01 | 4.95 | 2.78 | 92614155.11 | 56.69 | 16-DEC-04:49 | -14.3 | -14.7 |
Annual Sum or Average | 0.882619E+10 | 0.112533E+10 | ||||||||
Minimum of Months | 15286384.69 | 2088.48 | 2.62 | 1.03 | 82871076.32 | 56.69 | -23.7 | -24.0 | ||
Maximum of Months | 0.204017E+10 | 3389.04 | 28.98 | 22.96 | 98606951.20 | 56.70 | 24.23 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5572418.16 | 564.04 | 30-JAN-08:61 | -29.3 | -29.5 | 91590731.34 | 56.69 | 19-JAN-00:30 | -21.1 | -21.3 |
February | 19801545.41 | 2354.09 | 24-FEB-16:02 | 8.12 | 5.75 | 81731776.40 | 56.69 | 05-FEB-00:20 | -17.0 | -17.5 |
March | 72220711.18 | 2949.09 | 25-MAR-15:01 | 18.72 | 10.43 | 93520056.08 | 56.69 | 17-MAR-03:20 | -8.1 | -8.9 |
April | 0.466215E+09 | 3326.65 | 18-APR-15:02 | 27.75 | 20.45 | 92222677.88 | 56.69 | 15-APR-23:00 | 20.00 | 16.36 |
May | 0.875912E+09 | 3322.21 | 30-MAY-18:02 | 25.40 | 19.83 | 97511953.78 | 56.69 | 05-MAY-21:40 | 14.80 | 10.53 |
June | 0.162097E+10 | 3337.28 | 10-JUN-15:02 | 26.78 | 20.53 | 95092578.22 | 56.70 | 29-JUN-21:00 | 23.30 | 18.79 |
July | 0.196067E+10 | 3349.20 | 19-JUL-15:02 | 26.10 | 20.21 | 98568158.41 | 56.70 | 03-JUL-21:00 | 23.30 | 22.56 |
August | 0.164265E+10 | 3348.91 | 01-AUG-15:02 | 28.80 | 21.51 | 98526455.08 | 56.69 | 03-AUG-21:10 | 24.32 | 23.15 |
September | 0.933411E+09 | 3302.92 | 06-SEP-18:02 | 26.05 | 19.64 | 93954109.76 | 56.70 | 24-SEP-00:40 | 15.00 | 11.66 |
October | 0.175990E+09 | 2927.19 | 19-OCT-15:02 | 18.53 | 10.63 | 94457008.49 | 56.70 | 11-OCT-21:49 | 9.60 | 4.98 |
November | 45940505.38 | 2900.45 | 03-NOV-15:01 | 15.92 | 9.54 | 89945410.86 | 56.69 | 24-NOV-02:30 | -13.1 | -13.4 |
December | 7443747.68 | 374.10 | 01-DEC-16:05 | -2.1 | -4.2 | 92225568.59 | 56.69 | 29-DEC-01:10 | -9.0 | -9.4 |
Annual Sum or Average | 0.782680E+10 | 0.111935E+10 | ||||||||
Minimum of Months | 5572418.16 | 374.10 | -29.3 | -29.5 | 81731776.40 | 56.69 | -21.1 | -21.3 | ||
Maximum of Months | 0.196067E+10 | 3349.20 | 28.80 | 21.51 | 98568158.41 | 56.70 | 24.32 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92730324.38 | 1380.65 | 12-JAN-16:02 | 2.62 | 1.03 | 93618792.92 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.144066E+09 | 1399.57 | 08-FEB-16:02 | 2.02 | 0.66 | 84530161.33 | 56.69 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.204790E+09 | 1435.87 | 25-MAR-15:01 | 18.72 | 10.43 | 95828892.54 | 56.69 | 19-MAR-23:40 | 13.67 | 11.25 |
April | 0.378863E+09 | 1475.81 | 15-APR-15:02 | 30.00 | 19.17 | 93180943.74 | 56.69 | 14-APR-21:19 | 14.63 | 11.58 |
May | 0.582214E+09 | 1498.97 | 05-MAY-15:02 | 26.78 | 16.88 | 97778673.84 | 56.69 | 12-MAY-21:30 | 16.95 | 15.55 |
June | 0.878898E+09 | 1514.54 | 27-JUN-15:02 | 30.50 | 21.67 | 95108120.72 | 56.70 | 28-JUN-21:10 | 22.85 | 17.35 |
July | 0.105766E+10 | 1522.63 | 02-JUL-15:02 | 29.40 | 21.54 | 98481809.60 | 56.70 | 19-JUL-21:10 | 22.62 | 20.36 |
August | 0.105304E+10 | 1518.40 | 01-AUG-15:02 | 28.80 | 21.51 | 98566395.11 | 56.69 | 28-AUG-22:49 | 21.70 | 20.86 |
September | 0.865175E+09 | 1548.62 | 06-SEP-15:02 | 32.02 | 20.85 | 94783543.50 | 56.69 | 15-SEP-21:10 | 11.78 | 9.29 |
October | 0.497509E+09 | 1454.20 | 19-OCT-15:02 | 18.53 | 10.63 | 97100850.07 | 56.69 | 20-OCT-21:00 | 13.90 | 9.53 |
November | 0.200358E+09 | 1426.59 | 04-NOV-15:02 | 14.13 | 6.69 | 92193460.13 | 56.69 | 03-NOV-22:10 | 4.82 | 2.55 |
December | 0.134812E+09 | 1378.50 | 03-DEC-16:01 | 3.03 | 0.60 | 94393881.57 | 56.69 | 24-DEC-00:30 | -7.2 | -7.5 |
Annual Sum or Average | 0.609012E+10 | 0.113557E+10 | ||||||||
Minimum of Months | 92730324.38 | 1378.50 | 2.02 | 0.60 | 84530161.33 | 56.69 | -7.2 | -7.5 | ||
Maximum of Months | 0.105766E+10 | 1548.62 | 32.02 | 21.67 | 98566395.11 | 56.70 | 22.85 | 20.86 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293252E+11 | 33432.80 | 19-JAN-01:51 | -23.9 | -24.0 | 0.168322E+11 | 11347.85 | 13-JAN-04:19 | -2.4 | -3.1 |
February | 0.278549E+11 | 21797.72 | 02-FEB-06:00 | -36.7 | -36.8 | 0.150267E+11 | 11347.86 | 24-FEB-04:19 | 0.20 | -1.3 |
March | 0.321469E+11 | 22607.82 | 24-MAR-01:02 | 8.80 | 5.42 | 0.188377E+11 | 11608.53 | 28-MAR-23:00 | 8.30 | 7.15 |
April | 0.341903E+11 | 28987.61 | 07-APR-23:00 | 7.20 | 3.68 | 0.183571E+11 | 11887.70 | 19-APR-21:40 | 7.07 | 3.65 |
May | 0.391426E+11 | 24531.92 | 07-MAY-23:00 | 11.70 | 9.84 | 0.190352E+11 | 12005.66 | 17-MAY-21:19 | 8.90 | 7.13 |
June | 0.407341E+11 | 23704.65 | 01-JUN-22:48 | 9.40 | 8.81 | 0.184714E+11 | 11938.69 | 02-JUN-22:30 | 9.15 | 8.10 |
July | 0.429741E+11 | 22391.14 | 24-JUL-05:17 | 10.57 | 9.84 | 0.189738E+11 | 11437.04 | 22-JUL-04:00 | 12.20 | 11.27 |
August | 0.422607E+11 | 24908.02 | 06-AUG-23:00 | 9.40 | 8.21 | 0.190081E+11 | 11965.84 | 16-AUG-04:00 | 10.60 | 10.60 |
September | 0.378502E+11 | 23353.57 | 19-SEP-21:10 | 7.12 | 5.30 | 0.183611E+11 | 12454.17 | 26-SEP-21:49 | 7.30 | 6.23 |
October | 0.346441E+11 | 25004.71 | 03-OCT-23:20 | 8.43 | 6.72 | 0.189368E+11 | 12059.00 | 19-OCT-21:30 | 7.10 | 4.79 |
November | 0.308546E+11 | 24349.08 | 03-NOV-20:35 | 6.67 | 3.97 | 0.178066E+11 | 12020.89 | 07-NOV-05:00 | 10.60 | 9.72 |
December | 0.287254E+11 | 16248.49 | 04-DEC-23:00 | 2.20 | 0.30 | 0.181509E+11 | 11347.92 | 05-DEC-04:19 | 2.23 | 0.71 |
Annual Sum or Average | 0.420703E+12 | 0.217798E+12 | ||||||||
Minimum of Months | 0.278549E+11 | 16248.49 | -36.7 | -36.8 | 0.150267E+11 | 11347.85 | -2.4 | -3.1 | ||
Maximum of Months | 0.429741E+11 | 33432.80 | 11.70 | 9.84 | 0.190352E+11 | 12454.17 | 12.20 | 11.27 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324097E+11 | 35442.66 | 19-JAN-01:51 | -23.9 | -24.0 | 0.171760E+11 | 11347.91 | 17-JAN-00:20 | -3.7 | -3.8 |
February | 0.309304E+11 | 22752.97 | 02-FEB-06:00 | -36.7 | -36.8 | 0.152527E+11 | 11347.91 | 13-FEB-00:20 | -6.7 | -7.1 |
March | 0.359183E+11 | 25154.27 | 28-MAR-23:05 | 8.30 | 7.15 | 0.190669E+11 | 11689.43 | 28-MAR-21:40 | 9.27 | 7.38 |
April | 0.379185E+11 | 32040.41 | 07-APR-23:00 | 7.20 | 3.68 | 0.185150E+11 | 12030.22 | 19-APR-21:40 | 7.07 | 3.65 |
May | 0.429564E+11 | 26725.18 | 07-MAY-23:00 | 11.70 | 9.84 | 0.191646E+11 | 12178.39 | 17-MAY-21:19 | 8.90 | 7.13 |
June | 0.441355E+11 | 25118.32 | 22-JUN-00:58 | 10.60 | 9.90 | 0.185715E+11 | 12088.30 | 02-JUN-22:30 | 9.15 | 8.10 |
July | 0.463290E+11 | 23641.69 | 24-JUL-05:17 | 10.57 | 9.84 | 0.190737E+11 | 11440.64 | 22-JUL-04:00 | 12.20 | 11.27 |
August | 0.456535E+11 | 26968.46 | 06-AUG-23:00 | 9.40 | 8.21 | 0.191219E+11 | 11999.75 | 16-AUG-04:00 | 10.60 | 10.60 |
September | 0.413373E+11 | 24884.71 | 19-SEP-21:10 | 7.12 | 5.30 | 0.184837E+11 | 12621.59 | 26-SEP-21:49 | 7.30 | 6.23 |
October | 0.385265E+11 | 27664.82 | 03-OCT-23:20 | 8.43 | 6.72 | 0.191008E+11 | 12167.88 | 19-OCT-21:30 | 7.10 | 4.79 |
November | 0.343301E+11 | 27290.63 | 25-NOV-21:22 | -23.9 | -24.2 | 0.180534E+11 | 12092.92 | 07-NOV-05:00 | 10.60 | 9.72 |
December | 0.320149E+11 | 18285.75 | 04-DEC-23:00 | 2.20 | 0.30 | 0.185236E+11 | 11347.96 | 05-DEC-04:19 | 2.23 | 0.71 |
Annual Sum or Average | 0.462460E+12 | 0.220104E+12 | ||||||||
Minimum of Months | 0.309304E+11 | 18285.75 | -36.7 | -36.8 | 0.152527E+11 | 11347.91 | -6.7 | -7.1 | ||
Maximum of Months | 0.463290E+11 | 35442.66 | 11.70 | 9.90 | 0.191646E+11 | 12621.59 | 12.20 | 11.27 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466771E+11 | 28186.90 | 29-JAN-19:32 | -23.7 | -23.9 | 0.186349E+11 | 11336.12 | 14-JAN-18:00 | -9.4 | -10.4 |
February | 0.437116E+11 | 30539.71 | 24-FEB-16:10 | 8.12 | 5.75 | 0.168090E+11 | 11360.78 | 25-FEB-18:00 | 1.70 | 0.04 |
March | 0.504688E+11 | 35205.77 | 20-MAR-10:37 | 9.43 | 6.42 | 0.188139E+11 | 11415.69 | 18-MAR-17:49 | 9.63 | 7.95 |
April | 0.511468E+11 | 33988.67 | 26-APR-17:53 | 9.40 | 3.56 | 0.182195E+11 | 11384.48 | 26-APR-17:00 | 9.40 | 3.56 |
May | 0.558141E+11 | 30702.88 | 01-MAY-16:52 | 8.30 | 5.45 | 0.188230E+11 | 11351.80 | 13-MAY-17:10 | 11.78 | 11.04 |
June | 0.559142E+11 | 30617.03 | 11-JUN-10:40 | 29.67 | 22.03 | 0.181934E+11 | 11335.88 | 03-JUN-17:00 | 14.40 | 10.98 |
July | 0.583953E+11 | 30613.69 | 29-JUL-10:50 | 26.02 | 19.78 | 0.187778E+11 | 11319.65 | 15-JUL-17:19 | 23.70 | 17.75 |
August | 0.577466E+11 | 30223.81 | 27-AUG-10:40 | 25.53 | 19.85 | 0.187939E+11 | 11319.65 | 05-AUG-17:19 | 25.03 | 17.78 |
September | 0.539437E+11 | 32156.19 | 27-SEP-08:04 | 7.48 | 5.97 | 0.182067E+11 | 11390.96 | 30-SEP-17:19 | 7.97 | 2.49 |
October | 0.523743E+11 | 30931.47 | 23-OCT-15:08 | 8.02 | 3.52 | 0.188303E+11 | 11438.13 | 28-OCT-17:30 | 7.55 | 3.36 |
November | 0.479891E+11 | 29713.47 | 05-NOV-10:40 | 9.27 | 6.26 | 0.181743E+11 | 11395.95 | 04-NOV-17:49 | 5.97 | 2.43 |
December | 0.470785E+11 | 25843.73 | 03-DEC-11:50 | 4.90 | 2.33 | 0.187746E+11 | 11353.24 | 02-DEC-18:00 | 1.10 | 0.61 |
Annual Sum or Average | 0.621260E+12 | 0.221051E+12 | ||||||||
Minimum of Months | 0.437116E+11 | 25843.73 | -23.7 | -23.9 | 0.168090E+11 | 11319.65 | -9.4 | -10.4 | ||
Maximum of Months | 0.583953E+11 | 35205.77 | 29.67 | 22.03 | 0.188303E+11 | 11438.13 | 25.03 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197948E+09 | 2181.15 | 12-JAN-13:00 | 2.20 | 0.51 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.656136E+09 | 4551.42 | 24-FEB-16:10 | 8.12 | 5.75 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.240550E+10 | 4070.50 | 20-MAR-10:31 | 9.43 | 6.42 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.451208E+10 | 4401.70 | 19-APR-03:10 | 8.62 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.740813E+10 | 4487.36 | 01-MAY-16:52 | 8.30 | 5.45 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.865533E+10 | 4296.60 | 30-JUN-15:15 | 29.23 | 21.32 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.961763E+10 | 4252.58 | 03-JUL-18:20 | 29.03 | 24.12 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.924311E+10 | 4265.24 | 04-AUG-15:13 | 33.90 | 25.65 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.736110E+10 | 4527.32 | 19-SEP-06:33 | 6.83 | 6.04 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.473554E+10 | 4699.92 | 23-OCT-15:08 | 8.02 | 3.52 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.205222E+10 | 3339.50 | 06-NOV-01:12 | 11.10 | 9.10 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.417381E+09 | 2328.17 | 03-DEC-13:20 | 5.60 | 2.34 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.572621E+11 | 0.00 | ||||||||
Minimum of Months | 0.197948E+09 | 2181.15 | 2.20 | 0.51 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.961763E+10 | 4699.92 | 33.90 | 25.65 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1162450.53 | 1691.65 | 31-JAN-11:42 | -23.1 |
February | 0.394228E+09 | 8915.00 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 330983.05 | 3309.83 | 20-APR-22:32 | 7.20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.395722E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.394228E+09 | 8915.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232238E+10 | 2977.69 | 20-JAN-07:51 | -23.3 |
February | 0.114225E+10 | 2735.64 | 04-FEB-11:21 | -23.0 |
March | 0.600996E+09 | 1483.80 | 06-MAR-05:00 | -15.6 |
April | 0.203215E+09 | 1027.11 | 03-APR-06:10 | -7.1 |
May | 12575.55 | 41.92 | 01-MAY-17:45 | 7.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 5864401.88 | 332.97 | 30-SEP-06:30 | 0.60 |
October | 23854965.37 | 451.46 | 23-OCT-06:05 | -3.0 |
November | 0.798271E+09 | 2814.45 | 26-NOV-08:51 | -23.3 |
December | 0.196985E+10 | 2353.07 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.706670E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.232238E+10 | 2977.69 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38736973.97 | 1012.63 | 31-JAN-11:42 | -23.1 |
February | 61886953.02 | 1398.92 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 7613.38 | 76.13 | 20-APR-22:32 | 7.20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 5598596.48 | 659.56 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.106230E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 61886953.02 | 1398.92 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562922E+09 | 1537.16 | 31-JAN-11:42 | -23.1 |
February | 0.355524E+09 | 2059.26 | 04-FEB-11:21 | -23.0 |
March | 16263222.95 | 388.00 | 06-MAR-05:00 | -15.6 |
April | 65781.17 | 245.29 | 20-APR-22:32 | 7.20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.106589E+09 | 1179.08 | 26-NOV-09:02 | -22.7 |
December | 0.199585E+09 | 771.89 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.124095E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.562922E+09 | 2059.26 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870692E+09 | 983.37 | 31-JAN-11:42 | -23.1 |
February | 0.477218E+09 | 1226.12 | 04-FEB-11:21 | -23.0 |
March | 0.161917E+09 | 457.64 | 06-MAR-05:00 | -15.6 |
April | 23879370.91 | 218.71 | 03-APR-03:50 | -6.6 |
May | 7834.46 | 26.11 | 01-MAY-17:45 | 7.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.219238E+09 | 821.91 | 26-NOV-09:02 | -22.7 |
December | 0.551517E+09 | 696.15 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.230447E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.870692E+09 | 1226.12 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 300792.35 | 2643.29 | 06-JAN-10:41 | -23.2 |
February | 280075.34 | 2869.82 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 146378.55 | 2439.64 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 727246.24 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 300792.35 | 2869.82 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481833E+09 | 7121.10 | 20-JAN-07:51 | -23.3 |
February | 0.100786E+09 | 6135.03 | 04-FEB-11:21 | -23.0 |
March | 11923716.81 | 582.27 | 01-MAR-11:02 | -4.9 |
April | 599868.76 | 278.31 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.103120E+09 | 6802.56 | 26-NOV-08:51 | -23.3 |
December | 0.517618E+09 | 3856.88 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.121588E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.517618E+09 | 7121.10 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242100E+09 | 17130.95 | 31-JAN-11:42 | -23.1 |
February | 0.538698E+09 | 23776.05 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 27252865.58 | 12376.16 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.808050E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.538698E+09 | 23776.05 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214228E+10 | 2036.28 | 07-JAN-19:02 | -19.8 |
February | 0.142611E+10 | 2056.18 | 04-FEB-19:02 | -20.0 |
March | 0.797560E+09 | 1984.31 | 13-MAR-08:62 | -7.7 |
April | 0.332433E+09 | 1974.66 | 03-APR-08:62 | -5.9 |
May | 25709015.93 | 1764.84 | 02-MAY-08:62 | 4.08 |
June | 9621403.97 | 785.80 | 11-JUN-08:04 | 24.37 |
July | 919593.99 | 773.05 | 01-JUL-08:04 | 23.07 |
August | 1144175.29 | 570.69 | 09-AUG-08:03 | 21.05 |
September | 64671547.01 | 1837.22 | 29-SEP-08:62 | 5.05 |
October | 0.259109E+09 | 1869.74 | 23-OCT-08:62 | 0.70 |
November | 0.988214E+09 | 2024.39 | 26-NOV-16:13 | -13.9 |
December | 0.178992E+10 | 2058.80 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.783769E+10 | |||
Minimum of Months | 919593.99 | 570.69 | -20.0 | |
Maximum of Months | 0.214228E+10 | 2058.80 | 24.37 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249217E+10 | 2050.54 | 19-JAN-16:13 | -23.0 |
February | 0.170164E+10 | 2073.47 | 04-FEB-19:02 | -20.0 |
March | 0.934613E+09 | 1987.58 | 06-MAR-09:02 | -9.5 |
April | 0.373776E+09 | 1968.44 | 03-APR-08:62 | -5.9 |
May | 31783800.07 | 1765.02 | 02-MAY-08:62 | 4.08 |
June | 10438813.61 | 832.79 | 11-JUN-08:04 | 24.37 |
July | 956982.62 | 797.26 | 01-JUL-08:04 | 23.07 |
August | 1265899.53 | 664.22 | 09-AUG-08:03 | 21.05 |
September | 82232345.42 | 1839.74 | 29-SEP-08:62 | 5.05 |
October | 0.373267E+09 | 1885.53 | 23-OCT-08:62 | 0.70 |
November | 0.116943E+10 | 2035.40 | 26-NOV-09:02 | -22.7 |
December | 0.206007E+10 | 2055.23 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.923164E+10 | |||
Minimum of Months | 956982.62 | 664.22 | -23.0 | |
Maximum of Months | 0.249217E+10 | 2073.47 | 24.37 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237434E+09 | 360.82 | 19-JAN-01:42 | -23.5 |
February | 95129193.98 | 255.11 | 05-FEB-06:00 | -17.8 |
March | 49294767.23 | 201.18 | 05-MAR-06:00 | -8.9 |
April | 6386556.60 | 131.38 | 03-APR-05:00 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 64514953.22 | 322.24 | 28-NOV-05:00 | -21.7 |
December | 0.188847E+09 | 366.67 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.641607E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.5 | |
Maximum of Months | 0.237434E+09 | 366.67 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455729E+09 | 572.31 | 31-JAN-16:02 | -20.1 |
February | 0.282941E+09 | 606.78 | 04-FEB-11:21 | -23.0 |
March | 0.105543E+09 | 552.06 | 05-MAR-16:02 | -9.6 |
April | 19956242.54 | 524.73 | 03-APR-15:02 | -3.2 |
May | 620438.21 | 313.13 | 03-MAY-15:03 | 17.30 |
June | 231795.03 | 200.92 | 15-JUN-08:06 | 14.60 |
July | 102462.46 | 221.26 | 10-JUL-15:05 | 18.30 |
August | 96975.68 | 296.12 | 30-AUG-15:05 | 18.07 |
September | 523259.25 | 281.26 | 30-SEP-08:03 | 3.35 |
October | 4783677.87 | 493.02 | 23-OCT-08:62 | 0.70 |
November | 0.150486E+09 | 562.93 | 25-NOV-16:02 | -18.1 |
December | 0.348402E+09 | 564.42 | 10-DEC-16:02 | -17.9 |
Annual Sum or Average | 0.136942E+10 | |||
Minimum of Months | 96975.68 | 200.92 | -23.0 | |
Maximum of Months | 0.455729E+09 | 606.78 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212609E+10 | 1954.93 | 19-JAN-16:13 | -23.0 |
February | 0.143262E+10 | 1979.95 | 04-FEB-19:02 | -20.0 |
March | 0.780997E+09 | 1903.06 | 05-MAR-19:02 | -14.0 |
April | 0.360190E+09 | 1888.86 | 03-APR-08:62 | -5.9 |
May | 20660942.52 | 763.39 | 20-MAY-15:04 | 16.10 |
June | 6803266.12 | 614.13 | 02-JUN-18:03 | 13.90 |
July | 603727.98 | 482.79 | 07-JUL-18:05 | 22.62 |
August | 959151.71 | 541.46 | 30-AUG-15:05 | 18.07 |
September | 57420879.20 | 1668.12 | 27-SEP-18:01 | 9.90 |
October | 0.259821E+09 | 1782.23 | 26-OCT-08:62 | 1.28 |
November | 0.992091E+09 | 1937.65 | 26-NOV-16:13 | -13.9 |
December | 0.179372E+10 | 1970.63 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.783198E+10 | |||
Minimum of Months | 603727.98 | 482.79 | -23.0 | |
Maximum of Months | 0.212609E+10 | 1979.95 | 22.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247569E+10 | 1983.16 | 31-JAN-16:02 | -20.1 |
February | 0.171660E+10 | 2016.79 | 04-FEB-16:02 | -19.5 |
March | 0.919127E+09 | 1916.81 | 05-MAR-19:02 | -14.0 |
April | 0.408988E+09 | 1888.98 | 03-APR-08:62 | -5.9 |
May | 25985746.30 | 690.17 | 21-MAY-15:04 | 17.98 |
June | 7526680.84 | 595.01 | 02-JUN-18:03 | 13.90 |
July | 711775.23 | 471.61 | 07-JUL-18:05 | 22.62 |
August | 1523286.83 | 512.68 | 26-AUG-18:05 | 23.95 |
September | 72559598.01 | 1671.13 | 27-SEP-18:01 | 9.90 |
October | 0.368090E+09 | 1791.33 | 26-OCT-08:62 | 1.28 |
November | 0.117266E+10 | 1955.39 | 25-NOV-16:02 | -18.1 |
December | 0.206972E+10 | 1974.97 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.923918E+10 | |||
Minimum of Months | 711775.23 | 471.61 | -20.1 | |
Maximum of Months | 0.247569E+10 | 2016.79 | 23.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202122E+10 | 1844.34 | 31-JAN-11:42 | -23.1 |
February | 0.115680E+10 | 2356.40 | 04-FEB-11:21 | -23.0 |
March | 0.505916E+09 | 1190.17 | 06-MAR-04:50 | -15.7 |
April | 0.150884E+09 | 845.83 | 03-APR-04:00 | -6.7 |
May | 553082.04 | 94.51 | 01-MAY-17:45 | 7.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 10317999.47 | 365.71 | 30-SEP-05:00 | 0.00 |
October | 47830143.82 | 411.63 | 27-OCT-03:50 | 0.00 |
November | 0.750820E+09 | 1688.07 | 26-NOV-09:02 | -22.7 |
December | 0.168656E+10 | 1471.16 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.633090E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.202122E+10 | 2356.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288775E+10 | 2372.26 | 18-JAN-16:13 | -18.0 |
February | 0.189376E+10 | 2355.26 | 04-FEB-19:02 | -20.0 |
March | 0.117180E+10 | 2288.44 | 06-MAR-09:02 | -9.5 |
April | 0.516475E+09 | 2270.25 | 03-APR-08:62 | -5.9 |
May | 53773797.36 | 2044.25 | 02-MAY-08:62 | 4.08 |
June | 21367113.47 | 864.80 | 05-JUN-08:63 | 9.90 |
July | 783516.07 | 711.85 | 01-JUL-08:04 | 23.07 |
August | 981202.58 | 589.03 | 09-AUG-08:03 | 21.05 |
September | 0.119932E+09 | 2138.48 | 29-SEP-08:62 | 5.05 |
October | 0.452706E+09 | 2176.83 | 23-OCT-08:62 | 0.70 |
November | 0.142153E+10 | 2358.19 | 26-NOV-16:13 | -13.9 |
December | 0.246435E+10 | 2394.34 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.110052E+11 | |||
Minimum of Months | 783516.07 | 589.03 | -20.0 | |
Maximum of Months | 0.288775E+10 | 2394.34 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329697E+10 | 2386.42 | 19-JAN-16:13 | -23.0 |
February | 0.222931E+10 | 2381.29 | 04-FEB-19:13 | -20.0 |
March | 0.135642E+10 | 2295.24 | 06-MAR-09:02 | -9.5 |
April | 0.573281E+09 | 2263.04 | 03-APR-08:62 | -5.9 |
May | 63746787.41 | 2046.32 | 02-MAY-08:62 | 4.08 |
June | 23026130.41 | 908.33 | 05-JUN-08:63 | 9.90 |
July | 769455.74 | 636.74 | 01-JUL-08:04 | 23.07 |
August | 1176750.43 | 623.74 | 09-AUG-08:03 | 21.05 |
September | 0.147972E+09 | 2141.96 | 29-SEP-08:62 | 5.05 |
October | 0.613229E+09 | 2186.47 | 23-OCT-08:62 | 0.70 |
November | 0.165339E+10 | 2364.95 | 26-NOV-09:13 | -22.0 |
December | 0.279932E+10 | 2391.13 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.127586E+11 | |||
Minimum of Months | 769455.74 | 623.74 | -23.0 | |
Maximum of Months | 0.329697E+10 | 2391.13 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100971E+10 | 1121.20 | 26-JAN-16:13 | -11.5 |
February | 0.598816E+09 | 1104.26 | 28-FEB-19:02 | -15.7 |
March | 0.366227E+09 | 1095.75 | 13-MAR-08:62 | -7.7 |
April | 0.175174E+09 | 1092.06 | 03-APR-08:62 | -5.9 |
May | 8412074.93 | 848.73 | 02-MAY-08:62 | 4.08 |
June | 1468799.91 | 250.45 | 06-JUN-18:03 | 16.60 |
July | 220031.02 | 261.74 | 10-JUL-15:05 | 18.30 |
August | 481275.49 | 210.66 | 01-AUG-08:05 | 23.07 |
September | 19160895.03 | 1003.36 | 29-SEP-08:62 | 5.05 |
October | 70970373.89 | 1021.28 | 26-OCT-08:62 | 1.28 |
November | 0.437116E+09 | 1112.96 | 26-NOV-16:13 | -13.9 |
December | 0.867080E+09 | 1134.83 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.355483E+10 | |||
Minimum of Months | 220031.02 | 210.66 | -19.1 | |
Maximum of Months | 0.100971E+10 | 1134.83 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16065725.80 | 5150.73 | 31-JAN-11:42 | -23.1 |
February | 42921156.59 | 6733.13 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 582348.27 | 2671.41 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 59569230.66 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 42921156.59 | 6733.13 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12400605.89 | 5187.86 | 31-JAN-11:42 | -23.1 |
February | 22034548.97 | 6522.01 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 327371.23 | 2489.79 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 34762526.08 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 22034548.97 | 6522.01 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475757E+10 | 5522.64 | 31-JAN-11:42 | -23.1 |
February | 0.255845E+10 | 6908.00 | 04-FEB-11:21 | -23.0 |
March | 0.871076E+09 | 3021.07 | 06-MAR-04:50 | -15.7 |
April | 0.158251E+09 | 1502.18 | 03-APR-05:00 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3963681.05 | 383.17 | 30-SEP-04:50 | -0.1 |
October | 24751268.62 | 519.65 | 27-OCT-04:00 | 0.00 |
November | 0.142612E+10 | 5072.97 | 26-NOV-09:02 | -22.7 |
December | 0.356515E+10 | 4274.06 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.133653E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.475757E+10 | 6908.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.144724E+11 | 13939.86 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.130672E+11 | 13939.86 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.145225E+11 | 13939.86 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.139817E+11 | 13939.86 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.144975E+11 | 13939.86 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.140458E+11 | 13939.86 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.144333E+11 | 13939.86 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.145225E+11 | 13939.86 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.139817E+11 | 13939.86 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.144724E+11 | 13939.86 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.140346E+11 | 13939.86 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.144333E+11 | 13939.86 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.170465E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.130672E+11 | 13939.86 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.145225E+11 | 13939.86 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.764969E+09 | 736.82 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.690697E+09 | 736.82 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.767621E+09 | 736.82 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.739033E+09 | 736.82 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.766295E+09 | 736.82 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.742422E+09 | 736.82 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.762906E+09 | 736.82 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.767621E+09 | 736.82 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.739033E+09 | 736.82 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.764969E+09 | 736.82 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.741833E+09 | 736.82 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.762906E+09 | 736.82 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.901031E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.690697E+09 | 736.82 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.767621E+09 | 736.82 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.885837E+09 | 853.24 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.799830E+09 | 853.24 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.888909E+09 | 853.24 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.855803E+09 | 853.24 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.887373E+09 | 853.24 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.859728E+09 | 853.24 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.883448E+09 | 853.24 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.888909E+09 | 853.24 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.855803E+09 | 853.24 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.885837E+09 | 853.24 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.859045E+09 | 853.24 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.883448E+09 | 853.24 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.104340E+11 | 0.117953E+11 | ||||
Minimum of Months | 0.799830E+09 | 853.24 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.888909E+09 | 853.24 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.141237E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141726E+10 | 1360.40 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140856E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136448E+10 | 1360.40 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141237E+10 | 1360.40 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140856E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166358E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280997E+09 | 270.66 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.253715E+09 | 270.66 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.281971E+09 | 270.66 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.271470E+09 | 270.66 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.281484E+09 | 270.66 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.272715E+09 | 270.66 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.280239E+09 | 270.66 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.281971E+09 | 270.66 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.271470E+09 | 270.66 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.280997E+09 | 270.66 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.272498E+09 | 270.66 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.280239E+09 | 270.66 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.330977E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.253715E+09 | 270.66 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.281971E+09 | 270.66 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.423840E+09 | 408.24 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.382689E+09 | 408.24 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.425309E+09 | 408.24 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.409470E+09 | 408.24 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.424575E+09 | 408.24 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.411347E+09 | 408.24 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.422697E+09 | 408.24 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.425309E+09 | 408.24 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.409470E+09 | 408.24 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.423840E+09 | 408.24 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.411021E+09 | 408.24 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.422697E+09 | 408.24 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.499226E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.382689E+09 | 408.24 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.425309E+09 | 408.24 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161923E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.143591E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.153898E+10 | 1761.91 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.143387E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.142036E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.136216E+10 | 1761.91 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.140463E+10 | 1761.91 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.145214E+10 | 1761.91 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.146505E+10 | 1761.91 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.157343E+10 | 1761.91 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.155868E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.162774E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.178922E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.136216E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.162774E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123012E+11 | 12090.12 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.110739E+11 | 12090.12 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.122427E+11 | 12090.12 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.117328E+11 | 12090.12 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.120863E+11 | 12090.12 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.116896E+11 | 12090.12 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.120173E+11 | 12090.12 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.121409E+11 | 12090.12 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.117645E+11 | 12090.12 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122455E+11 | 12090.12 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119150E+11 | 12090.12 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122866E+11 | 12090.12 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.143496E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.110739E+11 | 12090.12 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123012E+11 | 12090.12 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75964402.59 | 89.33 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 68608505.50 | 89.33 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 75685198.85 | 89.33 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 73558970.85 | 89.33 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 75824800.72 | 89.33 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 73279767.11 | 89.33 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 76104004.46 | 89.33 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 75685198.85 | 89.33 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 73558970.85 | 89.33 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 75964402.59 | 89.33 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 73419368.98 | 89.33 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 76104004.46 | 89.33 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.893758E+09 | 0.300992E+10 | ||||
Minimum of Months | 68608505.50 | 89.33 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 76104004.46 | 89.33 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75985174.92 | 89.35 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 68627266.37 | 89.35 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 75705894.83 | 89.35 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 73579085.42 | 89.35 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 75845534.87 | 89.35 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 73299805.33 | 89.35 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 76124814.96 | 89.35 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 75705894.83 | 89.35 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 73579085.42 | 89.35 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 75985174.92 | 89.35 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 73439445.37 | 89.35 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 76124814.96 | 89.35 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.894002E+09 | 0.301074E+10 | ||||
Minimum of Months | 68627266.37 | 89.35 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 76124814.96 | 89.35 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.232638E+10 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233445E+10 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224751E+10 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233042E+10 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224751E+10 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232638E+10 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274017E+11 | ||||
Minimum of Months | 0.210051E+10 | 2240.79 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.79 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75985174.92 | 89.35 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 68627266.37 | 89.35 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 75705894.83 | 89.35 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 73579085.42 | 89.35 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 75845534.87 | 89.35 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 73299805.33 | 89.35 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 76124814.96 | 89.35 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 75705894.83 | 89.35 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 73579085.42 | 89.35 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 75985174.92 | 89.35 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 73439445.37 | 89.35 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 76124814.96 | 89.35 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.894002E+09 | 0.301074E+10 | ||||
Minimum of Months | 68627266.37 | 89.35 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 76124814.96 | 89.35 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303870E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271935E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296474E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280425E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.283984E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.273401E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.281773E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.287449E+10 | 3094.06 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283625E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299413E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293465E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.304656E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346047E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271935E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304656E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303870E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271935E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296474E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280425E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.283984E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.273401E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.281773E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.287449E+10 | 3094.06 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283625E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299413E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293465E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.304656E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346047E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271935E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304656E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113539E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113343E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109310E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113146E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133271E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.246212E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222307E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.247065E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246639E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238955E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245548E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237864E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246212E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245548E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290004E+11 | ||||
Minimum of Months | 0.222307E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.144724E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.130672E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.139817E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.144975E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.140458E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.144333E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.139817E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.144724E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.140346E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.144333E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.170465E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.130672E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.764969E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225488E+10 |
February | 0.179968E+10 | 0.690697E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168766E+10 |
March | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134935E+10 |
April | 0.192973E+10 | 0.739033E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8567708.92 | 0.894123E+09 |
May | 0.199475E+10 | 0.766295E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12908044.42 | 0.452065E+09 |
June | 0.193394E+10 | 0.742422E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72166295.22 | 0.218401E+09 |
July | 0.199054E+10 | 0.762906E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69088459.13 | 0.116700E+09 |
August | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60871424.86 | 0.169518E+09 |
September | 0.192973E+10 | 0.739033E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30247086.72 | 0.420411E+09 |
October | 0.199054E+10 | 0.764969E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.69 | 0.891523E+09 |
November | 0.192552E+10 | 0.741833E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133694E+10 |
December | 0.199054E+10 | 0.762906E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191847E+10 |
Annual Sum or Average | 0.234734E+11 | 0.901031E+10 | 0.101859E+11 | 0.253850E+09 | 0.117100E+11 | ||||
Minimum of Months | 0.179968E+10 | 0.690697E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116700E+09 |
Maximum of Months | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72166295.22 | 0.225488E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.885837E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476273E+09 |
February | 0.208403E+10 | 0.799830E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357068E+09 |
March | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291341E+09 |
April | 0.223463E+10 | 0.855803E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2257727.71 | 0.198583E+09 |
May | 0.230993E+10 | 0.887373E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2933435.38 | 0.108800E+09 |
June | 0.223950E+10 | 0.859728E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15164218.99 | 55847490.50 |
July | 0.230505E+10 | 0.883448E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14695408.84 | 33379278.39 |
August | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13865751.62 | 45345930.15 |
September | 0.223463E+10 | 0.855803E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8040633.23 | 99483497.70 |
October | 0.230505E+10 | 0.885837E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15156.97 | 0.199850E+09 |
November | 0.222975E+10 | 0.859045E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289654E+09 |
December | 0.230505E+10 | 0.883448E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406441E+09 |
Annual Sum or Average | 0.271823E+11 | 0.104340E+11 | 0.117953E+11 | 56972332.74 | 0.256207E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.799830E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33379278.39 |
Maximum of Months | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15164218.99 | 0.476273E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.423840E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148306E+10 |
February | 0.139600E+10 | 0.382689E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110726E+10 |
March | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934607E+09 |
April | 0.149688E+10 | 0.409470E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 7894165.98 | 0.632479E+09 |
May | 0.154732E+10 | 0.424575E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 9967346.00 | 0.339298E+09 |
June | 0.150015E+10 | 0.411347E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 51063836.69 | 0.168648E+09 |
July | 0.154405E+10 | 0.422697E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 51038298.91 | 95245562.50 |
August | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50108095.08 | 0.131536E+09 |
September | 0.149688E+10 | 0.409470E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 30365191.44 | 0.303518E+09 |
October | 0.154405E+10 | 0.423840E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 253406.50 | 0.626353E+09 |
November | 0.149361E+10 | 0.411021E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919675E+09 |
December | 0.154405E+10 | 0.422697E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130278E+10 |
Annual Sum or Average | 0.182082E+11 | 0.499226E+10 | 0.679373E+11 | 0.590211E+12 | 0.200690E+09 | 0.804446E+10 | |||
Minimum of Months | 0.139600E+10 | 0.382689E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95245562.50 |
Maximum of Months | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 51063836.69 | 0.148306E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.161923E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572619E+10 |
February | 0.236489E+11 | 0.143591E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432927E+10 |
March | 0.262677E+11 | 0.153898E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350217E+10 |
April | 0.253579E+11 | 0.143387E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21236828.67 | 0.238036E+10 |
May | 0.262123E+11 | 0.142036E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30223130.84 | 0.130718E+10 |
June | 0.254132E+11 | 0.136216E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169987E+09 | 0.678585E+09 |
July | 0.261570E+11 | 0.140463E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161873E+09 | 0.413416E+09 |
August | 0.262677E+11 | 0.145214E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143624E+09 | 0.556652E+09 |
September | 0.253579E+11 | 0.146505E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74521842.28 | 0.120445E+10 |
October | 0.261570E+11 | 0.157343E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240906E+10 |
November | 0.253025E+11 | 0.155868E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346429E+10 |
December | 0.261570E+11 | 0.162774E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488310E+10 |
Annual Sum or Average | 0.308456E+12 | 0.178922E+11 | 0.143409E+11 | 0.601466E+09 | 0.308547E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.136216E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413416E+09 |
Maximum of Months | 0.262677E+11 | 0.162774E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169987E+09 | 0.572619E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123012E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115270E+11 |
February | 0.702046E+11 | 0.110739E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869646E+10 |
March | 0.779788E+11 | 0.122427E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713166E+10 |
April | 0.752779E+11 | 0.117328E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51281243.46 | 0.487855E+10 |
May | 0.778146E+11 | 0.120863E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65847505.03 | 0.272377E+10 |
June | 0.754422E+11 | 0.116896E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352347E+09 | 0.142143E+10 |
July | 0.776503E+11 | 0.120173E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340401E+09 | 0.868717E+09 |
August | 0.779788E+11 | 0.121409E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316353E+09 | 0.116010E+10 |
September | 0.752779E+11 | 0.117645E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182390E+09 | 0.248152E+10 |
October | 0.776503E+11 | 0.122455E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65686.64 | 0.493797E+10 |
November | 0.751137E+11 | 0.119150E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707887E+10 |
December | 0.776503E+11 | 0.122866E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987965E+10 |
Annual Sum or Average | 0.915690E+12 | 0.143496E+12 | 0.149002E+12 | 0.130868E+10 | 0.627858E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.110739E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868717E+09 |
Maximum of Months | 0.779788E+11 | 0.123012E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352347E+09 | 0.115270E+11 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663778E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505923E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391901E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3144170.64 | 0.260819E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3486375.15 | 0.136880E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21700459.56 | 65623081.57 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20420437.77 | 34975047.64 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18944411.03 | 49117490.42 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11583861.35 | 0.120949E+09 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18387.29 | 0.257062E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388181E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555083E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 79298102.78 | 0.343029E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34975047.64 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21700459.56 | 0.663778E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661959E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502216E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388346E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3202388.49 | 0.258735E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3547221.50 | 0.136003E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21776862.69 | 65449904.78 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20577319.50 | 34838346.94 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19259388.24 | 48779932.97 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11902464.61 | 0.119407E+09 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38950.84 | 0.252386E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385409E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552434E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 80304595.86 | 0.340596E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34838346.94 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21776862.69 | 0.661959E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 75964402.59 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177951E+09 |
February | 0.00 | 68608505.50 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136488E+09 |
March | 0.00 | 75685198.85 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106723E+09 |
April | 0.00 | 73558970.85 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 651818.22 | 72436678.10 |
May | 0.00 | 75824800.72 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 652265.51 | 44382516.24 |
June | 0.00 | 73279767.11 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288852.99 | 23834159.54 |
July | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549991.20 | 15345527.85 |
August | 0.00 | 75685198.85 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3513357.29 | 19797034.87 |
September | 0.00 | 73558970.85 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2385948.97 | 39926662.70 |
October | 0.00 | 75964402.59 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77772966.37 |
November | 0.00 | 73419368.98 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106869E+09 |
December | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148999E+09 |
Annual Sum or Average | 0.00 | 0.893758E+09 | 0.300992E+10 | 15042234.17 | 0.970526E+09 | ||||
Minimum of Months | 0.00 | 68608505.50 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15345527.85 |
Maximum of Months | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288852.99 | 0.177951E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184881E+09 |
February | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139882E+09 |
March | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109437E+09 |
April | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 982981.37 | 72657047.72 |
May | 0.303504E+09 | 75845534.87 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1121628.50 | 37710166.28 |
June | 0.293842E+09 | 73299805.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6502331.21 | 18146635.06 |
July | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6352328.01 | 9489384.82 |
August | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5987074.56 | 13362102.27 |
September | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3679440.28 | 33379572.51 |
October | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27895.20 | 71145949.93 |
November | 0.293661E+09 | 73439445.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108563E+09 |
December | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155034E+09 |
Annual Sum or Average | 0.357224E+10 | 0.894002E+09 | 0.301074E+10 | 24653679.14 | 0.953688E+09 | ||||
Minimum of Months | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9489384.82 |
Maximum of Months | 0.303685E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6502331.21 | 0.184881E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663316E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505122E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393030E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3140275.63 | 0.261538E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3439708.38 | 0.138778E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21567256.96 | 66590643.06 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20299070.18 | 35806602.86 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18847176.12 | 49837278.73 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11553630.95 | 0.122051E+09 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20903.61 | 0.257894E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388053E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554770E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 78868021.83 | 0.343679E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35806602.86 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21567256.96 | 0.663316E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661536E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501212E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389358E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3153095.62 | 0.259525E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3444732.02 | 0.138048E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21583052.43 | 66470470.20 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20335733.05 | 35737454.61 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18914591.15 | 49613363.43 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11637725.84 | 0.120788E+09 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49557.18 | 0.253228E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385241E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552352E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 79118487.31 | 0.341311E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35737454.61 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21583052.43 | 0.661536E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664111E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506171E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391502E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084596.31 | 0.261218E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3373724.72 | 0.138476E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21244736.46 | 66603501.37 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19827424.61 | 35846584.99 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18472851.73 | 49994833.76 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11347831.29 | 0.121622E+09 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15297.03 | 0.257073E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388024E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555149E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 77366462.15 | 0.343579E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35846584.99 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21244736.46 | 0.664111E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662558E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502687E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388401E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3118808.34 | 0.259134E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3389596.30 | 0.137677E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21253890.16 | 66466403.12 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19859184.91 | 35770688.28 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18572978.28 | 49761085.90 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11517792.41 | 0.120118E+09 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37095.60 | 0.252033E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385528E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553309E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 77749346.00 | 0.341344E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35770688.28 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21253890.16 | 0.662558E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343570E+09 |
February | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262342E+09 |
March | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203606E+09 |
April | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1571858.95 | 0.134838E+09 |
May | 0.303504E+09 | 75845534.87 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1729755.51 | 71152281.68 |
June | 0.293842E+09 | 73299805.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10906460.32 | 34144730.12 |
July | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10187789.63 | 18231540.68 |
August | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9447111.16 | 25540464.18 |
September | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5759803.61 | 62941721.07 |
October | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 254.63 | 0.134048E+09 |
November | 0.293661E+09 | 73439445.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201741E+09 |
December | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287763E+09 |
Annual Sum or Average | 0.357224E+10 | 0.894002E+09 | 0.301074E+10 | 39603033.80 | 0.177992E+10 | ||||
Minimum of Months | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18231540.68 |
Maximum of Months | 0.303685E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10906460.32 | 0.343570E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303870E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170001E+10 |
February | 0.415303E+11 | 0.271935E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128822E+10 |
March | 0.461292E+11 | 0.296474E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107473E+10 |
April | 0.445315E+11 | 0.280425E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5944772.58 | 0.743757E+09 |
May | 0.460320E+11 | 0.283984E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5875895.29 | 0.429737E+09 |
June | 0.446286E+11 | 0.273401E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36063995.15 | 0.233009E+09 |
July | 0.459349E+11 | 0.281773E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30334064.51 | 0.153029E+09 |
August | 0.461292E+11 | 0.287449E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31608207.81 | 0.190631E+09 |
September | 0.445315E+11 | 0.283625E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21714055.01 | 0.380442E+09 |
October | 0.459349E+11 | 0.299413E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44394.15 | 0.736860E+09 |
November | 0.444343E+11 | 0.293465E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105673E+10 |
December | 0.459349E+11 | 0.304656E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147016E+10 |
Annual Sum or Average | 0.541686E+12 | 0.346047E+11 | 0.175857E+12 | 0.131585E+09 | 0.945732E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.271935E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153029E+09 |
Maximum of Months | 0.461292E+11 | 0.304656E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36063995.15 | 0.170001E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303870E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171172E+10 |
February | 0.415303E+11 | 0.271935E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129646E+10 |
March | 0.461292E+11 | 0.296474E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108423E+10 |
April | 0.445315E+11 | 0.280425E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5590927.62 | 0.750446E+09 |
May | 0.460320E+11 | 0.283984E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5422991.56 | 0.435064E+09 |
June | 0.446286E+11 | 0.273401E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34542167.89 | 0.235964E+09 |
July | 0.459349E+11 | 0.281773E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28344937.39 | 0.155369E+09 |
August | 0.461292E+11 | 0.287449E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29430469.95 | 0.193320E+09 |
September | 0.445315E+11 | 0.283625E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20531511.07 | 0.384612E+09 |
October | 0.459349E+11 | 0.299413E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20251.76 | 0.744172E+09 |
November | 0.444343E+11 | 0.293465E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106635E+10 |
December | 0.459349E+11 | 0.304656E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148325E+10 |
Annual Sum or Average | 0.541686E+12 | 0.346047E+11 | 0.175857E+12 | 0.123883E+09 | 0.954097E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.271935E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155369E+09 |
Maximum of Months | 0.461292E+11 | 0.304656E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34542167.89 | 0.171172E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153894E+10 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115903E+10 |
March | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976751E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4131536.90 | 0.675308E+09 |
May | 0.409635E+10 | 0.113343E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3920937.72 | 0.390576E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27950291.99 | 0.205536E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21268166.69 | 0.130716E+09 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21765454.30 | 0.167482E+09 |
September | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15202543.37 | 0.343955E+09 |
October | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672238E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961439E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134240E+10 |
Annual Sum or Average | 0.482041E+11 | 0.133271E+11 | 0.392709E+12 | 0.359593E+12 | 94238930.97 | 0.856438E+10 | |||
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130716E+09 |
Maximum of Months | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27950291.99 | 0.153894E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.141237E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104404E+10 |
February | 0.00 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770255E+09 |
March | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621387E+09 |
April | 0.00 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5707167.32 | 0.414770E+09 |
May | 0.00 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7078111.77 | 0.221661E+09 |
June | 0.00 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35346662.74 | 0.112205E+09 |
July | 0.00 | 0.140856E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34553263.21 | 64113330.79 |
August | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32681136.21 | 89508793.19 |
September | 0.00 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19564891.19 | 0.203777E+09 |
October | 0.00 | 0.141237E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120069.42 | 0.413723E+09 |
November | 0.00 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621061E+09 |
December | 0.00 | 0.140856E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882948E+09 |
Annual Sum or Average | 0.166358E+11 | 0.124715E+11 | 0.135051E+09 | 0.545945E+10 | |||||
Minimum of Months | 0.00 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64113330.79 |
Maximum of Months | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35346662.74 | 0.104404E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.280997E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725027E+09 |
February | 0.00 | 0.253715E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534451E+09 |
March | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429890E+09 |
April | 0.00 | 0.271470E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4006963.50 | 0.285172E+09 |
May | 0.00 | 0.281484E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5000092.27 | 0.149375E+09 |
June | 0.00 | 0.272715E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24890009.84 | 75351679.78 |
July | 0.00 | 0.280239E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24435037.74 | 42630468.92 |
August | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22984673.29 | 59745871.25 |
September | 0.00 | 0.271470E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13666705.03 | 0.137457E+09 |
October | 0.00 | 0.280997E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85038.49 | 0.281129E+09 |
November | 0.00 | 0.272498E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429007E+09 |
December | 0.00 | 0.280239E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613564E+09 |
Annual Sum or Average | 0.330977E+10 | 0.359769E+10 | 95068520.16 | 0.376280E+10 | |||||
Minimum of Months | 0.00 | 0.253715E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42630468.92 |
Maximum of Months | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24890009.84 | 0.725027E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806225E+09 |
February | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601446E+09 |
March | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476072E+09 |
April | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4614534.61 | 0.314198E+09 |
May | 0.00 | 0.233042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5935685.96 | 0.158761E+09 |
June | 0.00 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30352161.46 | 76721540.31 |
July | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30224113.97 | 40571571.16 |
August | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28825215.26 | 57361666.20 |
September | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16620907.53 | 0.143300E+09 |
October | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92947.11 | 0.306863E+09 |
November | 0.00 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472931E+09 |
December | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679533E+09 |
Annual Sum or Average | 0.274017E+11 | 0.116666E+09 | 0.413398E+10 | ||||||
Minimum of Months | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40571571.16 |
Maximum of Months | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30352161.46 | 0.806225E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142354E+10 |
February | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105295E+10 |
March | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847380E+09 |
April | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6267606.80 | 0.566678E+09 |
May | 0.00 | 0.246639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708930.57 | 0.302161E+09 |
June | 0.00 | 0.238955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36633842.96 | 0.157166E+09 |
July | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31698161.71 | 94147497.87 |
August | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33485948.80 | 0.123638E+09 |
September | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20907436.84 | 0.270254E+09 |
October | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47617.46 | 0.551990E+09 |
November | 0.00 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840616E+09 |
December | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120595E+10 |
Annual Sum or Average | 0.290004E+11 | 0.135750E+09 | 0.743647E+10 | ||||||
Minimum of Months | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94147497.87 |
Maximum of Months | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36633842.96 | 0.142354E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13939.86 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13939.86 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13939.86 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13939.86 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13939.86 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13939.86 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13939.86 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13939.86 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13939.86 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 13939.86 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13939.86 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13939.86 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 13939.86 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13939.86 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 736.82 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1231.23 | 30-JAN-12:30 |
February | 1169.53 | 01-FEB-00:10 | 736.82 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1322.71 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 736.82 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 985.19 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 736.82 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.17 | 15-APR-17:00 | 702.35 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 736.82 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 | 31-MAY-13:00 | 495.33 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 736.82 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.14 | 11-JUN-15:00 | 376.70 | 03-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 736.82 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.37 | 26-JUL-15:00 | 258.23 | 23-JUL-03:58 |
August | 1169.53 | 01-AUG-00:10 | 736.82 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.86 | 04-AUG-16:00 | 297.75 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 736.82 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.95 | 07-SEP-14:00 | 537.16 | 30-SEP-01:00 |
October | 1169.53 | 02-OCT-00:10 | 736.82 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 21-OCT-15:00 | 599.54 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 736.82 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1180.12 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 736.82 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1150.17 | 09-DEC-01:30 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 736.82 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.23 | |||||
Maximum of Months | 1169.53 | 736.82 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 221.14 | 1322.71 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 853.24 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.47 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 853.24 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 289.78 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 853.24 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 208.69 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 853.24 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 | 15-APR-16:00 | 149.85 | 03-APR-21:00 |
May | 1354.32 | 01-MAY-00:10 | 853.24 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.87 | 31-MAY-13:00 | 111.19 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 853.24 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.35 | 11-JUN-15:00 | 87.93 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 853.24 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 | 26-JUL-15:00 | 62.60 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 853.24 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 04-AUG-15:00 | 71.25 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 853.24 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 | 06-SEP-14:00 | 120.21 | 30-SEP-01:00 |
October | 1354.32 | 02-OCT-00:10 | 853.24 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 20-OCT-15:00 | 132.16 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 853.24 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 259.43 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 853.24 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 245.84 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 853.24 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 | |||||
Maximum of Months | 1354.32 | 853.24 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 289.78 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 408.24 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 821.61 | 05-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 408.24 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 801.53 | 02-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 408.24 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 664.48 | 05-MAR-23:00 |
April | 907.20 | 01-APR-00:10 | 408.24 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 124.46 | 15-APR-15:30 | 498.70 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 408.24 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 125.26 | 31-MAY-13:00 | 344.81 | 03-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 408.24 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 168.74 | 11-JUN-15:00 | 270.38 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 408.24 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 126.20 | 26-JUL-15:00 | 203.08 | 24-JUL-05:05 |
August | 907.20 | 01-AUG-00:10 | 408.24 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 176.57 | 04-AUG-15:00 | 235.82 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 408.24 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 156.10 | 07-SEP-14:00 | 372.80 | 29-SEP-06:00 |
October | 907.20 | 02-OCT-00:10 | 408.24 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 32.67 | 20-OCT-15:00 | 431.92 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 408.24 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 808.91 | 25-NOV-21:03 |
December | 907.20 | 01-DEC-00:10 | 408.24 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 800.53 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 203.08 | ||||||
Maximum of Months | 907.20 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.57 | 821.61 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3192.95 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3491.90 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2486.28 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.69 | 15-APR-16:00 | 1776.65 | 03-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.15 | 31-MAY-13:00 | 1342.52 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.67 | 11-JUN-15:00 | 1076.91 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.73 | 26-JUL-15:00 | 784.57 | 24-JUL-03:20 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 574.43 | 04-AUG-15:00 | 872.87 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.61 | 07-SEP-14:00 | 1433.48 | 30-SEP-01:00 |
October | 15368.40 | 02-OCT-00:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 1532.45 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3042.08 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2923.62 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.57 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 581.67 | 3491.90 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 12090.12 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6395.06 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 12090.12 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7027.94 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 12090.12 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 5087.73 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 12090.12 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 840.81 | 15-APR-16:00 | 3676.63 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 12090.12 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 897.23 | 31-MAY-13:00 | 2752.43 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 12090.12 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.81 | 11-JUN-15:00 | 2185.02 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 12090.12 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 879.95 | 26-JUL-15:00 | 1582.04 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 12090.12 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.32 | 04-AUG-15:00 | 1775.52 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 12090.12 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.57 | 06-SEP-14:00 | 2971.25 | 30-SEP-01:00 |
October | 45622.98 | 02-OCT-00:10 | 12090.12 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 | 20-OCT-15:00 | 3231.07 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 12090.12 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6236.98 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 12090.12 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5920.27 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | |||||
Maximum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.32 | 7027.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 412.34 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.58 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:10 | 111.81 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 394.86 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.73 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 460.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 408.31 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 456.17 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.78 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:10 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.97 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.37 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 393.00 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 456.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 89.33 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 110.27 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 89.33 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 125.76 | 02-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 89.33 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 76.44 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 89.33 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 15-APR-15:00 | 53.38 | 03-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 89.33 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 31-MAY-13:00 | 39.86 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 89.33 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 11-JUN-15:00 | 33.97 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 89.33 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 26-JUL-15:00 | 24.51 | 24-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 89.33 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 04-AUG-15:00 | 28.19 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 89.33 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 07-SEP-14:00 | 43.06 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 89.33 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 49.42 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 89.33 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 105.16 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 89.33 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 90.53 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 89.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | |||||
Maximum of Months | 0.00 | 89.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 125.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 89.35 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 111.05 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 89.35 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 125.22 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 89.35 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 81.16 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 89.35 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 15-APR-15:10 | 57.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 89.35 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 31-MAY-15:10 | 40.95 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 89.35 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 11-JUN-15:10 | 31.20 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 89.35 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 26-JUL-15:10 | 21.35 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 89.35 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 04-AUG-15:10 | 24.72 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 89.35 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 06-SEP-15:08 | 44.37 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 89.35 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 20-OCT-15:00 | 49.50 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 89.35 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 107.43 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 89.35 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.37 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 125.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 408.46 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 457.62 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.58 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:08 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:08 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 06-SEP-15:08 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 392.54 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.73 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 457.62 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 404.12 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 453.25 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.77 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:08 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:08 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-03:52 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:07 | 177.36 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 390.22 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 453.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 410.97 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 458.83 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.32 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.08 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 31-MAY-15:10 | 147.18 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.25 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 | 26-JUL-15:10 | 76.93 | 23-JUL-03:54 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.53 | 06-SEP-15:10 | 159.46 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 20-OCT-15:10 | 177.86 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 393.46 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.29 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 458.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 405.97 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 453.48 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.30 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.06 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 | 31-MAY-15:10 | 147.16 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.23 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 26-JUL-15:10 | 76.93 | 23-JUL-03:56 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 06-SEP-15:10 | 159.44 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:10 | 177.84 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 390.75 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.26 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 453.48 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 89.35 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 210.68 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 89.35 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 235.70 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 89.35 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 149.04 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 89.35 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-APR-16:10 | 106.45 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 89.35 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 31-MAY-15:10 | 75.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 89.35 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 11-JUN-15:10 | 57.42 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 89.35 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 26-JUL-15:10 | 39.36 | 23-JUL-03:52 |
August | 180.00 | 01-AUG-00:10 | 89.35 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 04-AUG-15:10 | 45.54 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 89.35 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 | 07-SEP-16:00 | 81.58 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 89.35 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 20-OCT-15:10 | 90.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 89.35 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 200.66 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 89.35 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.11 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | |||||
Maximum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 235.70 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 919.01 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1007.41 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 757.33 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.75 | 15-APR-16:00 | 557.24 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.66 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.61 | 11-JUN-15:00 | 322.82 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.86 | 26-JUL-15:00 | 236.27 | 23-JUL-03:58 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.99 | 04-AUG-15:00 | 265.90 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.97 | 06-SEP-14:00 | 439.68 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 20-OCT-15:00 | 485.40 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 893.78 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.27 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 156.99 | 1007.41 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 915.33 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1002.06 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 762.34 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 15-APR-16:00 | 559.68 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.38 | 11-JUN-15:00 | 322.83 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.77 | 26-JUL-15:00 | 237.86 | 23-JUL-03:58 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.67 | 04-AUG-15:00 | 265.90 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 | 06-SEP-14:00 | 439.69 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 | 20-OCT-15:00 | 485.41 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 892.87 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.86 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 154.67 | 1002.06 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 816.24 | 05-JAN-21:12 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 801.75 | 02-FEB-21:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 663.51 | 05-MAR-23:10 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 81.41 | 15-APR-15:40 | 500.88 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 81.87 | 31-MAY-13:00 | 353.40 | 03-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 125.89 | 11-JUN-15:00 | 282.15 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 82.54 | 26-JUL-15:40 | 217.34 | 24-JUL-05:03 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 133.73 | 04-AUG-15:40 | 237.18 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 112.49 | 06-SEP-14:40 | 374.97 | 29-SEP-23:10 |
October | 2401.70 | 02-OCT-00:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 434.41 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 806.59 | 25-NOV-21:03 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 791.56 | 09-DEC-08:04 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 217.34 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 133.73 | 816.24 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 592.58 | 30-JAN-08:00 |
February | 0.00 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 648.26 | 02-FEB-07:20 |
March | 0.00 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 455.21 | 06-MAR-01:00 |
April | 0.00 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.19 | 15-APR-16:40 | 324.50 | 03-APR-06:00 |
May | 0.00 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.84 | 31-MAY-13:00 | 230.19 | 03-MAY-03:00 |
June | 0.00 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.89 | 11-JUN-15:00 | 182.89 | 01-JUN-05:00 |
July | 0.00 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.59 | 26-JUL-15:00 | 129.34 | 23-JUL-03:52 |
August | 0.00 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.59 | 04-AUG-15:00 | 148.68 | 07-AUG-06:00 |
September | 0.00 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.12 | 06-SEP-14:00 | 253.26 | 30-SEP-01:00 |
October | 0.00 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 20-OCT-15:00 | 281.05 | 23-OCT-06:00 |
November | 0.00 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 584.98 | 26-NOV-07:00 |
December | 0.00 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 535.23 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.34 | ||||
Maximum of Months | 0.00 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 115.59 | 648.26 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 270.66 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 411.89 | 30-JAN-08:00 |
February | 0.00 | 270.66 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 452.28 | 02-FEB-06:10 |
March | 0.00 | 270.66 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 316.51 | 06-MAR-01:00 |
April | 0.00 | 270.66 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 15-APR-17:00 | 225.63 | 03-APR-06:00 |
May | 0.00 | 270.66 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.92 | 31-MAY-13:00 | 159.13 | 03-MAY-03:00 |
June | 0.00 | 270.66 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 | 11-JUN-15:00 | 125.69 | 01-JUN-05:00 |
July | 0.00 | 270.66 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.88 | 26-JUL-15:00 | 88.10 | 23-JUL-03:52 |
August | 0.00 | 270.66 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 04-AUG-15:00 | 101.29 | 07-AUG-06:00 |
September | 0.00 | 270.66 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 | 06-SEP-14:00 | 172.62 | 30-SEP-01:00 |
October | 0.00 | 270.66 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 20-OCT-15:00 | 192.63 | 23-OCT-06:00 |
November | 0.00 | 270.66 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 407.60 | 26-NOV-07:00 |
December | 0.00 | 270.66 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 371.72 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 270.66 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 | ||||
Maximum of Months | 0.00 | 270.66 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 | 452.28 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 471.30 | 31-JAN-04:00 |
February | 0.00 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 524.97 | 02-FEB-06:10 |
March | 0.00 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 350.62 | 06-MAR-01:00 |
April | 0.00 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 15-APR-17:00 | 250.04 | 03-APR-06:00 |
May | 0.00 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.97 | 31-MAY-13:00 | 176.45 | 03-MAY-03:00 |
June | 0.00 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.71 | 11-JUN-15:00 | 134.26 | 03-JUN-04:00 |
July | 0.00 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 | 26-JUL-15:00 | 91.88 | 23-JUL-04:00 |
August | 0.00 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 | 04-AUG-15:00 | 106.42 | 07-AUG-06:00 |
September | 0.00 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 | 06-SEP-14:00 | 191.30 | 30-SEP-01:00 |
October | 0.00 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 20-OCT-15:00 | 213.52 | 23-OCT-06:00 |
November | 0.00 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 455.90 | 26-NOV-07:00 |
December | 0.00 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 409.24 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.88 | |||
Maximum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 | 524.97 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 793.91 | 31-JAN-04:00 |
February | 0.00 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 870.38 | 02-FEB-06:02 |
March | 0.00 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 621.54 | 06-MAR-01:00 |
April | 0.00 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 | 15-APR-17:00 | 443.49 | 03-APR-06:00 |
May | 0.00 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.10 | 31-MAY-13:00 | 313.23 | 03-MAY-03:00 |
June | 0.00 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.44 | 11-JUN-15:00 | 248.18 | 01-JUN-05:00 |
July | 0.00 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 26-JUL-15:00 | 173.77 | 24-JUL-03:05 |
August | 0.00 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 | 04-AUG-15:00 | 196.81 | 07-AUG-06:00 |
September | 0.00 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.70 | 06-SEP-15:00 | 339.50 | 30-SEP-01:00 |
October | 0.00 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 20-OCT-15:00 | 378.84 | 23-OCT-06:00 |
November | 0.00 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 783.20 | 26-NOV-07:00 |
December | 0.00 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 725.36 | 09-DEC-01:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.77 | |||
Maximum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 | 870.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 39145.65 | 19-JAN-01:51 | 115018.92 | 23233.09 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33846.05 | 02-FEB-06:02 | 44729.58 | 30977.46 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19835.81 | 24-MAR-08:62 | 10223.90 | 24781.97 | 21292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18683.40 | 07-APR-23:00 | 34505.68 | 13939.86 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18311.19 | 01-MAY-08:62 | 12779.88 | 30977.46 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18253.47 | 02-JUN-23:10 | 34505.68 | 9293.24 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18282.47 | 23-JUL-03:52 | 44729.58 | 15488.73 | 15969.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19554.89 | 07-AUG-05:08 | 35783.66 | 24781.97 | 21292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25115.65 | 27-SEP-21:00 | 20447.81 | 24781.97 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25137.60 | 19-OCT-20:38 | 61343.42 | 74345.90 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39503.48 | 25-NOV-21:33 | 26837.75 | 32526.33 | 25550.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17658.27 | 01-DEC-22:00 | 10223.90 | 12390.98 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17658.27 | 10223.90 | 9293.24 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39503.48 | 115018.92 | 74345.90 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1949.91 | 12-JAN-12:30 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.11 |
February | 3035.29 | 24-FEB-14:04 | 1299.48 | 1023.36 | 1262.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.32 |
March | 2355.35 | 20-MAR-10:31 | 1819.27 | 1432.71 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.63 |
April | 2922.31 | 15-APR-13:20 | 389.84 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 100.40 | 0.00 |
May | 2121.58 | 31-MAY-18:40 | 909.64 | 654.95 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 0.00 |
June | 2253.45 | 26-JUN-18:40 | 909.64 | 654.95 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 119.53 | 0.00 |
July | 2222.49 | 30-JUL-13:20 | 259.90 | 163.74 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 78.94 | 0.00 |
August | 2365.40 | 29-AUG-13:30 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 |
September | 3749.51 | 07-SEP-13:00 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 166.43 | 0.00 |
October | 3937.38 | 20-OCT-12:50 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.41 |
November | 3602.25 | 04-NOV-13:10 | 389.84 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.42 |
December | 2988.61 | 03-DEC-13:00 | 389.84 | 245.61 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1949.91 | 259.90 | 163.74 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3937.38 | 1819.27 | 1432.71 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 166.43 | 522.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2152.26 | 05-JAN-21:22 | 6019.20 | 3792.19 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.43 |
February | 1924.59 | 02-FEB-06:00 | 1354.32 | 189.61 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.78 |
March | 1921.24 | 24-MAR-08:62 | 1203.84 | 1516.88 | 1671.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 |
April | 1898.84 | 19-APR-03:10 | 2708.64 | 189.61 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.69 |
May | 1888.47 | 18-MAY-23:17 | 4062.96 | 568.83 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.91 |
June | 1845.48 | 02-JUN-23:10 | 4062.96 | 568.83 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.45 |
July | 1803.61 | 23-JUL-03:52 | 5266.80 | 948.05 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 |
August | 1846.40 | 07-AUG-05:08 | 4213.44 | 1516.88 | 1671.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 |
September | 1981.61 | 19-SEP-06:33 | 5417.28 | 4266.22 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 |
October | 1991.58 | 25-OCT-01:12 | 6771.60 | 474.02 | 835.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.23 |
November | 2400.89 | 03-NOV-20:35 | 2407.68 | 1516.88 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 |
December | 1113.03 | 05-DEC-22:10 | 1354.32 | 568.83 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1113.03 | 1203.84 | 189.61 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 | |
Maximum of Months | 2400.89 | 6771.60 | 4266.22 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 992.23 | 19-JAN-08:00 | 0.00 | 755.78 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.28 |
February | 992.55 | 02-FEB-07:20 | 0.00 | 1511.55 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.26 |
March | 1677.96 | 24-MAR-08:62 | 0.00 | 2418.49 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.17 |
April | 1630.49 | 19-APR-03:10 | 0.00 | 302.31 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.26 |
May | 1615.44 | 18-MAY-23:17 | 0.00 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 |
June | 1592.75 | 02-JUN-23:10 | 0.00 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.70 |
July | 1577.35 | 23-JUL-03:52 | 0.00 | 1511.55 | 1325.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.34 |
August | 1608.39 | 07-AUG-05:08 | 0.00 | 2418.49 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.19 |
September | 1777.22 | 19-SEP-06:33 | 0.00 | 6801.99 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.99 |
October | 1754.73 | 03-OCT-06:35 | 0.00 | 4534.66 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.74 |
November | 1385.42 | 07-NOV-03:42 | 0.00 | 604.62 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.92 |
December | 841.68 | 04-DEC-22:10 | 0.00 | 906.93 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 841.68 | 0.00 | 302.31 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.92 | |
Maximum of Months | 1777.22 | 0.00 | 6801.99 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 356.34 | 13-JAN-22:00 | 0.00 | 240.58 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.13 |
February | 367.82 | 24-FEB-22:10 | 0.00 | 180.44 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.65 |
March | 761.60 | 24-MAR-08:62 | 0.00 | 481.17 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 |
April | 752.46 | 19-APR-03:10 | 0.00 | 60.15 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
May | 730.03 | 01-MAY-08:62 | 0.00 | 601.46 | 637.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 |
June | 718.65 | 02-JUN-23:10 | 0.00 | 180.44 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.84 |
July | 719.06 | 23-JUL-03:52 | 0.00 | 300.73 | 382.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 |
August | 734.76 | 07-AUG-05:08 | 0.00 | 481.17 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.47 |
September | 802.58 | 19-SEP-06:33 | 0.00 | 1353.29 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.76 |
October | 790.97 | 03-OCT-06:35 | 0.00 | 902.19 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 |
November | 632.27 | 07-NOV-03:42 | 0.00 | 120.29 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 |
December | 314.19 | 03-DEC-13:00 | 0.00 | 90.22 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 314.19 | 0.00 | 60.15 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 | |
Maximum of Months | 802.58 | 0.00 | 1353.29 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40512.01 | 05-JAN-21:32 | 4032.00 | 1814.42 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 791.18 |
February | 36380.35 | 24-FEB-21:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 345.54 |
March | 39296.60 | 29-MAR-19:30 | 1411.20 | 816.49 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 257.93 |
April | 41226.26 | 19-APR-20:00 | 1411.20 | 816.49 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 253.31 |
May | 40169.60 | 02-MAY-19:56 | 3528.00 | 2041.22 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 272.38 |
June | 38601.33 | 01-JUN-19:56 | 3528.00 | 2041.22 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 223.60 |
July | 38113.42 | 03-JUL-20:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.01 | 0.00 |
August | 38128.85 | 03-AUG-20:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
September | 41495.14 | 27-SEP-19:57 | 2116.80 | 1224.73 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 0.00 | 253.52 |
October | 40180.13 | 19-OCT-20:38 | 4838.40 | 2177.31 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 265.75 |
November | 44476.59 | 03-NOV-20:35 | 1612.80 | 725.77 | 8664.25 | 75271.41 | 0.00 | 0.00 | 0.00 | 0.00 | 300.65 |
December | 35867.20 | 01-DEC-21:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 467.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35867.20 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44476.59 | 4838.40 | 2177.31 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 38.01 | 791.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8531.65 | 12-JAN-12:30 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.07 |
February | 12790.87 | 24-FEB-14:02 | 17076.00 | 1492.73 | 1778.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.99 |
March | 11782.81 | 24-MAR-01:02 | 76842.00 | 978.84 | 1016.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.33 |
April | 11571.28 | 15-APR-13:00 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 233.81 | 0.00 |
May | 11227.55 | 18-MAY-23:17 | 46105.20 | 1174.61 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.27 |
June | 11005.55 | 02-JUN-01:12 | 76842.00 | 978.84 | 1016.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.38 |
July | 10576.64 | 23-JUL-03:52 | 59766.00 | 1957.68 | 1524.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.98 |
August | 10866.22 | 07-AUG-02:12 | 76842.00 | 978.84 | 1016.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.09 |
September | 12955.29 | 16-SEP-13:10 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 245.94 | 0.00 |
October | 15000.94 | 23-OCT-15:08 | 68304.00 | 2388.36 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.99 |
November | 14325.99 | 04-NOV-12:40 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.21 |
December | 12121.27 | 03-DEC-12:50 | 5122.80 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8531.65 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15000.94 | 76842.00 | 2388.36 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 245.94 | 1318.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 44223.62 | 05-JAN-21:22 | 202768.80 | 53733.85 | 47506.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6051.27 |
February | 40633.36 | 02-FEB-06:00 | 45622.98 | 2686.69 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7027.94 |
March | 41282.75 | 24-MAR-01:02 | 228114.90 | 6716.73 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.60 |
April | 40726.18 | 20-APR-20:03 | 243322.56 | 64480.62 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1896.24 |
May | 40189.37 | 18-MAY-23:17 | 136868.94 | 8060.08 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.43 |
June | 39450.07 | 02-JUN-23:10 | 136868.94 | 8060.08 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713.67 |
July | 38217.24 | 23-JUL-03:52 | 177422.70 | 13433.46 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.62 |
August | 39295.47 | 07-AUG-05:08 | 141938.16 | 21493.54 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.91 |
September | 40810.08 | 19-SEP-06:33 | 182491.92 | 56219.04 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1870.73 |
October | 46182.00 | 19-OCT-22:33 | 136868.94 | 12090.12 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1972.02 |
November | 50266.03 | 03-NOV-20:35 | 81107.52 | 21493.54 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2097.73 |
December | 24248.51 | 04-DEC-23:10 | 45622.98 | 4030.04 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2479.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24248.51 | 45622.98 | 2686.69 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.62 | |
Maximum of Months | 50266.03 | 243322.56 | 64480.62 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7027.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2678.03 | 12-JAN-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.59 |
February | 2954.72 | 24-FEB-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 |
March | 3079.94 | 25-MAR-15:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 |
April | 3250.29 | 16-APR-18:02 | 702.00 | 852.83 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 0.00 |
May | 3243.99 | 31-MAY-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 | 0.00 |
June | 3296.54 | 25-JUN-15:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 | 0.00 |
July | 3286.36 | 29-JUL-15:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 35.28 | 0.00 |
August | 3289.13 | 22-AUG-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 | 0.00 |
September | 3258.61 | 20-SEP-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 |
October | 3075.76 | 19-OCT-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.85 |
November | 3013.26 | 03-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.60 |
December | 2664.59 | 02-DEC-16:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2664.59 | 324.00 | 53.30 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3296.54 | 702.00 | 852.83 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 | 129.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 749.16 | 12-JAN-16:03 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.52 |
February | 2681.47 | 24-FEB-16:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.20 |
March | 2907.48 | 25-MAR-15:01 | 378.00 | 62.18 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 |
April | 3185.98 | 16-APR-18:02 | 702.00 | 852.73 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 0.00 |
May | 3182.05 | 06-MAY-15:01 | 378.00 | 62.18 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
June | 3244.83 | 27-JUN-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.26 | 0.00 |
July | 3212.89 | 05-JUL-18:02 | 831.60 | 756.80 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 0.00 |
August | 3210.33 | 02-AUG-18:02 | 831.60 | 756.80 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 | 0.00 |
September | 3235.54 | 06-SEP-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 0.00 |
October | 2872.31 | 19-OCT-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 |
November | 2835.89 | 03-NOV-15:01 | 680.40 | 79.59 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.18 |
December | 669.56 | 02-DEC-16:03 | 378.00 | 62.18 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 669.56 | 378.00 | 62.18 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3244.83 | 831.60 | 852.73 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 128.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 360.38 | 30-JAN-11:30 | 0.00 | 11.17 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.41 |
February | 356.34 | 01-FEB-13:10 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
March | 358.55 | 24-MAR-13:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 |
April | 549.25 | 18-APR-15:30 | 0.00 | 7.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
May | 399.64 | 05-MAY-17:00 | 0.00 | 7.82 | 131.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 | 0.00 |
June | 526.62 | 18-JUN-20:20 | 0.00 | 89.33 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
July | 479.57 | 25-JUL-19:30 | 0.00 | 89.33 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 |
August | 503.19 | 29-AUG-13:20 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
September | 660.55 | 08-SEP-12:50 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
October | 689.51 | 20-OCT-12:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
November | 666.46 | 04-NOV-12:30 | 0.00 | 5.58 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
December | 301.51 | 03-DEC-13:30 | 0.00 | 5.58 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 301.51 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 689.51 | 0.00 | 89.33 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 100.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 402.34 | 30-JAN-08:61 | 541.80 | 273.64 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 |
February | 339.64 | 24-FEB-19:04 | 693.00 | 396.50 | 632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 |
March | 770.03 | 28-MAR-18:02 | 693.00 | 396.50 | 632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 |
April | 918.14 | 16-APR-18:02 | 702.00 | 536.12 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
May | 989.01 | 05-MAY-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
June | 939.16 | 29-JUN-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 0.00 |
July | 921.61 | 02-JUL-18:02 | 702.00 | 536.12 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 0.00 |
August | 936.48 | 09-AUG-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
September | 926.87 | 08-SEP-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 0.00 |
October | 765.12 | 01-OCT-08:62 | 270.00 | 104.25 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
November | 741.09 | 04-NOV-08:62 | 324.00 | 125.09 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
December | 329.62 | 04-DEC-19:05 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 329.62 | 270.00 | 104.25 | 632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 989.01 | 831.60 | 536.12 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 108.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 583.04 | 30-JAN-08:61 | 541.80 | 435.30 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.78 |
February | 2464.72 | 24-FEB-09:02 | 216.00 | 373.11 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.22 |
March | 2659.71 | 28-MAR-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 |
April | 2878.12 | 18-APR-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 0.00 |
May | 2884.34 | 06-MAY-15:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 |
June | 2911.16 | 26-JUN-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 0.00 |
July | 2894.88 | 01-JUL-15:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 0.00 |
August | 2910.73 | 09-AUG-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
September | 2920.51 | 02-SEP-15:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 0.00 |
October | 2727.59 | 19-OCT-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.80 |
November | 2662.66 | 03-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.37 |
December | 1013.64 | 03-DEC-09:02 | 324.00 | 198.99 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 583.04 | 216.00 | 53.30 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2920.51 | 680.40 | 435.30 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 398.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 577.78 | 30-JAN-08:61 | 541.80 | 435.25 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.41 |
February | 1895.46 | 24-FEB-09:02 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 |
March | 2485.68 | 28-MAR-08:62 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.82 |
April | 2826.35 | 15-APR-18:02 | 702.00 | 852.73 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 | 0.00 |
May | 2856.61 | 06-MAY-15:01 | 378.00 | 62.18 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 |
June | 2865.72 | 26-JUN-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 54.81 | 0.00 |
July | 2853.27 | 02-JUL-18:02 | 702.00 | 852.73 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 35.61 | 0.00 |
August | 2838.82 | 09-AUG-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 0.00 |
September | 2873.32 | 07-SEP-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 0.00 |
October | 2408.96 | 20-OCT-08:62 | 180.00 | 310.89 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.64 |
November | 1157.79 | 04-NOV-08:62 | 324.00 | 198.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.61 |
December | 724.59 | 03-DEC-09:03 | 324.00 | 198.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 577.78 | 180.00 | 62.18 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2873.32 | 702.00 | 852.73 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 396.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1286.47 | 31-JAN-04:00 | 0.00 | 248.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.30 |
February | 2174.00 | 24-FEB-16:10 | 0.00 | 3734.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.21 |
March | 1973.10 | 20-MAR-10:34 | 0.00 | 4357.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.59 |
April | 2099.50 | 19-APR-03:10 | 0.00 | 497.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 |
May | 1729.84 | 31-MAY-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
June | 1931.14 | 22-JUN-01:53 | 0.00 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.04 |
July | 1974.38 | 23-JUL-03:52 | 0.00 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.80 |
August | 1778.09 | 16-AUG-06:05 | 0.00 | 4979.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 |
September | 1911.12 | 21-SEP-00:24 | 0.00 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.39 |
October | 2209.20 | 23-OCT-15:08 | 0.00 | 4979.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.01 |
November | 1401.41 | 03-NOV-14:00 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 |
December | 1072.48 | 03-DEC-13:00 | 0.00 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1072.48 | 0.00 | 248.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2209.20 | 0.00 | 4979.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 471.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2356.90 | 12-JAN-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.66 |
February | 3062.25 | 24-FEB-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.22 |
March | 3180.52 | 25-MAR-15:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 |
April | 3377.63 | 16-APR-18:02 | 702.00 | 852.83 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 0.00 |
May | 3370.93 | 06-MAY-15:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
June | 3373.26 | 13-JUN-18:02 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 0.00 |
July | 3384.22 | 25-JUL-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 | 0.00 |
August | 3383.45 | 28-AUG-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 | 0.00 |
September | 3389.04 | 20-SEP-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
October | 3185.65 | 19-OCT-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.16 |
November | 3125.42 | 03-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.98 |
December | 2088.48 | 02-DEC-16:01 | 378.00 | 62.19 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2088.48 | 378.00 | 62.19 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3389.04 | 831.60 | 852.83 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 | 129.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 564.04 | 30-JAN-08:61 | 541.80 | 435.25 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.81 |
February | 2354.09 | 24-FEB-16:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 |
March | 2949.09 | 25-MAR-15:01 | 378.00 | 62.18 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 |
April | 3326.65 | 18-APR-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 0.00 |
May | 3322.21 | 30-MAY-18:02 | 831.60 | 756.80 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 | 0.00 |
June | 3337.28 | 10-JUN-15:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 | 0.00 |
July | 3349.20 | 19-JUL-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 0.00 |
August | 3348.91 | 01-AUG-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 0.00 |
September | 3302.92 | 06-SEP-18:02 | 831.60 | 756.80 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 |
October | 2927.19 | 19-OCT-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 |
November | 2900.45 | 03-NOV-15:01 | 680.40 | 79.59 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 |
December | 374.10 | 01-DEC-16:05 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 374.10 | 324.00 | 53.30 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3349.20 | 831.60 | 756.80 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 390.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1380.65 | 12-JAN-16:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.68 |
February | 1399.57 | 08-FEB-16:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 |
March | 1435.87 | 25-MAR-15:01 | 378.00 | 39.09 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
April | 1475.81 | 15-APR-15:02 | 324.00 | 33.51 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
May | 1498.97 | 05-MAY-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 0.00 |
June | 1514.54 | 27-JUN-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 | 0.00 |
July | 1522.63 | 02-JUL-15:02 | 324.00 | 33.51 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 0.00 |
August | 1518.40 | 01-AUG-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.47 | 0.00 |
September | 1548.62 | 06-SEP-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 | 0.00 |
October | 1454.20 | 19-OCT-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
November | 1426.59 | 04-NOV-15:02 | 324.00 | 33.51 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
December | 1378.50 | 03-DEC-16:01 | 378.00 | 39.09 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1378.50 | 324.00 | 33.51 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1548.62 | 583.20 | 42.89 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 | 74.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33432.80 | 19-JAN-01:51 | 269887.68 | 5156.77 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.47 |
February | 21797.72 | 02-FEB-06:00 | 26988.77 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.41 |
March | 22607.82 | 24-MAR-01:02 | 134943.84 | 1718.92 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.20 |
April | 28987.61 | 07-APR-23:00 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.67 |
May | 24531.92 | 07-MAY-23:00 | 47980.03 | 2062.71 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.74 |
June | 23704.65 | 01-JUN-22:48 | 134943.84 | 5156.77 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.19 |
July | 22391.14 | 24-JUL-05:17 | 125947.58 | 6600.66 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.67 |
August | 24908.02 | 06-AUG-23:00 | 95960.06 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.04 |
September | 23353.57 | 19-SEP-21:10 | 53977.54 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.60 |
October | 25004.71 | 03-OCT-23:20 | 53977.54 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.82 |
November | 24349.08 | 03-NOV-20:35 | 47980.03 | 5500.55 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.50 |
December | 16248.49 | 04-DEC-23:00 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16248.49 | 26988.77 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.74 | |
Maximum of Months | 33432.80 | 269887.68 | 6600.66 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35442.66 | 19-JAN-01:51 | 269887.68 | 5156.77 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.56 |
February | 22752.97 | 02-FEB-06:00 | 26988.77 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.06 |
March | 25154.27 | 28-MAR-23:05 | 53977.54 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.65 |
April | 32040.41 | 07-APR-23:00 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.67 |
May | 26725.18 | 07-MAY-23:00 | 47980.03 | 2062.71 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.31 |
June | 25118.32 | 22-JUN-00:58 | 161932.61 | 3094.06 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.82 |
July | 23641.69 | 24-JUL-05:17 | 125947.58 | 6600.66 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.46 |
August | 26968.46 | 06-AUG-23:00 | 95960.06 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.56 |
September | 24884.71 | 19-SEP-21:10 | 53977.54 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.86 |
October | 27664.82 | 03-OCT-23:20 | 53977.54 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.65 |
November | 27290.63 | 25-NOV-21:22 | 125947.58 | 14438.94 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.99 |
December | 18285.75 | 04-DEC-23:00 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18285.75 | 26988.77 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.31 | |
Maximum of Months | 35442.66 | 269887.68 | 14438.94 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28186.90 | 29-JAN-19:32 | 8005.68 | 4238.24 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 780.12 |
February | 30539.71 | 24-FEB-16:10 | 8005.68 | 1816.39 | 89477.13 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 241.39 |
March | 35205.77 | 20-MAR-10:37 | 3735.98 | 2119.12 | 104389.99 | 131208.19 | 0.00 | 0.00 | 0.00 | 0.00 | 211.35 |
April | 33988.67 | 26-APR-17:53 | 5337.12 | 2906.22 | 59651.42 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 234.07 |
May | 30702.88 | 01-MAY-16:52 | 8005.68 | 1816.39 | 89477.13 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 241.17 |
June | 30617.03 | 11-JUN-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 77.30 | 0.00 |
July | 30613.69 | 29-JUL-10:50 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.30 | 0.00 |
August | 30223.81 | 27-AUG-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 |
September | 32156.19 | 27-SEP-08:04 | 2668.56 | 2421.85 | 74564.28 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 222.03 |
October | 30931.47 | 23-OCT-15:08 | 10674.24 | 2421.85 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 0.00 | 246.53 |
November | 29713.47 | 05-NOV-10:40 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 245.22 |
December | 25843.73 | 03-DEC-11:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 306.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25843.73 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35205.77 | 10674.24 | 4238.24 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 77.30 | 780.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2181.15 | 12-JAN-13:00 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.67 |
February | 4551.42 | 24-FEB-16:10 | 0.00 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.83 |
March | 4070.50 | 20-MAR-10:31 | 0.00 | 4611.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.71 |
April | 4401.70 | 19-APR-03:10 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.78 |
May | 4487.36 | 01-MAY-16:52 | 0.00 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.48 |
June | 4296.60 | 30-JUN-15:15 | 0.00 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 | 0.00 |
July | 4252.58 | 03-JUL-18:20 | 0.00 | 4216.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.06 | 0.00 |
August | 4265.24 | 04-AUG-15:13 | 0.00 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.34 | 0.00 |
September | 4527.32 | 19-SEP-06:33 | 0.00 | 11857.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 |
October | 4699.92 | 23-OCT-15:08 | 0.00 | 5270.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.79 |
November | 3339.50 | 06-NOV-01:12 | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.09 |
December | 2328.17 | 03-DEC-13:20 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2181.15 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4699.92 | 0.00 | 11857.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.34 | 284.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.419987E+12 | 265718.19 | 18-JAN-20:10 | 0.997367E+12 | 1004234.68 | 30-JAN-20:49 |
February | 0.376349E+12 | 266608.38 | 02-FEB-20:10 | 0.776277E+12 | 1052007.41 | 02-FEB-18:00 |
March | 0.412714E+12 | 271536.74 | 29-MAR-19:30 | 0.523037E+12 | 484777.15 | 05-MAR-19:10 |
April | 0.419934E+12 | 379692.85 | 16-APR-19:10 | 0.414216E+12 | 373787.03 | 02-APR-18:10 |
May | 0.462679E+12 | 381757.00 | 31-MAY-19:40 | 0.372065E+12 | 330599.58 | 19-MAY-20:49 |
June | 0.544034E+12 | 409059.94 | 26-JUN-19:00 | 0.344454E+12 | 325961.12 | 01-JUN-17:49 |
July | 0.612844E+12 | 428348.13 | 26-JUL-19:00 | 0.341186E+12 | 279620.39 | 03-JUL-17:19 |
August | 0.589604E+12 | 425364.38 | 03-AUG-19:40 | 0.340329E+12 | 279085.44 | 01-AUG-17:10 |
September | 0.478413E+12 | 381953.17 | 07-SEP-19:10 | 0.347804E+12 | 360616.19 | 29-SEP-16:49 |
October | 0.422144E+12 | 282599.57 | 20-OCT-19:30 | 0.391973E+12 | 365471.48 | 30-OCT-19:00 |
November | 0.403817E+12 | 275967.34 | 03-NOV-19:19 | 0.548941E+12 | 930698.60 | 25-NOV-21:40 |
December | 0.418045E+12 | 266546.68 | 04-DEC-20:49 | 0.721423E+12 | 610846.76 | 09-DEC-17:19 |
Annual Sum or Average | 0.556056E+13 | 0.611907E+13 | ||||
Minimum of Months | 0.376349E+12 | 265718.19 | 0.340329E+12 | 279085.44 | ||
Maximum of Months | 0.612844E+12 | 428348.13 | 0.997367E+12 | 1052007.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.655450E+11 | 0.239200E+11 | 0.148212E+12 | 0.834803E+11 | 0.522794E+11 | 0.622044E+10 | 0.00 | 0.294057E+09 | 0.00 | 0.00 | 0.273366E+11 | 0.770828E+10 | 0.00 |
February | 0.590771E+11 | 0.199305E+11 | 0.133859E+12 | 0.754016E+11 | 0.460484E+11 | 0.518215E+10 | 0.00 | 0.727333E+09 | 0.00 | 0.00 | 0.246854E+11 | 0.696670E+10 | 0.00 |
March | 0.653133E+11 | 0.197487E+11 | 0.148234E+12 | 0.834831E+11 | 0.482091E+11 | 0.519988E+10 | 0.00 | 0.399298E+10 | 0.00 | 0.00 | 0.256396E+11 | 0.770494E+10 | 0.00 |
April | 0.628103E+11 | 0.167371E+11 | 0.143397E+12 | 0.807866E+11 | 0.466558E+11 | 0.590639E+10 | 0.00 | 0.295098E+11 | 0.00 | 0.00 | 0.216146E+11 | 0.746513E+10 | 0.00 |
May | 0.647609E+11 | 0.152226E+11 | 0.148223E+12 | 0.834810E+11 | 0.479369E+11 | 0.762243E+10 | 0.00 | 0.702392E+11 | 0.00 | 0.00 | 0.122053E+11 | 0.770483E+10 | 0.00 |
June | 0.626399E+11 | 0.136908E+11 | 0.143446E+12 | 0.807892E+11 | 0.468707E+11 | 0.830247E+10 | 0.00 | 0.162821E+12 | 0.00 | 0.00 | 0.128853E+11 | 0.745767E+10 | 0.00 |
July | 0.645470E+11 | 0.145909E+11 | 0.148174E+12 | 0.834781E+11 | 0.478421E+11 | 0.919098E+10 | 0.00 | 0.220845E+12 | 0.00 | 0.00 | 0.111871E+11 | 0.771356E+10 | 0.00 |
August | 0.649441E+11 | 0.163823E+11 | 0.148234E+12 | 0.834828E+11 | 0.478216E+11 | 0.893589E+10 | 0.00 | 0.195744E+12 | 0.00 | 0.00 | 0.110506E+11 | 0.770533E+10 | 0.00 |
September | 0.629372E+11 | 0.180525E+11 | 0.143397E+12 | 0.807868E+11 | 0.470751E+11 | 0.748533E+10 | 0.00 | 0.920037E+11 | 0.00 | 0.00 | 0.141047E+11 | 0.746543E+10 | 0.00 |
October | 0.653543E+11 | 0.211074E+11 | 0.148212E+12 | 0.834801E+11 | 0.489918E+11 | 0.652806E+10 | 0.00 | 0.134404E+11 | 0.00 | 0.00 | 0.220946E+11 | 0.770447E+10 | 0.00 |
November | 0.634656E+11 | 0.225440E+11 | 0.143462E+12 | 0.807882E+11 | 0.479959E+11 | 0.536298E+10 | 0.00 | 0.339346E+10 | 0.00 | 0.00 | 0.243589E+11 | 0.744989E+10 | 0.00 |
December | 0.654970E+11 | 0.244998E+11 | 0.148174E+12 | 0.834790E+11 | 0.501488E+11 | 0.538196E+10 | 0.00 | 0.676070E+09 | 0.00 | 0.00 | 0.273366E+11 | 0.771354E+10 | 0.00 |
Annual Sum or Average | 0.766892E+12 | 0.226427E+12 | 0.174502E+13 | 0.982917E+12 | 0.577876E+12 | 0.813189E+11 | 0.00 | 0.793686E+12 | 0.234499E+12 | 0.907598E+11 | |||
Minimum of Months | 0.590771E+11 | 0.136908E+11 | 0.133859E+12 | 0.754016E+11 | 0.460484E+11 | 0.518215E+10 | 0.00 | 0.294057E+09 | 0.00 | 0.00 | 0.110506E+11 | 0.696670E+10 | 0.00 |
Maximum of Months | 0.655450E+11 | 0.244998E+11 | 0.148234E+12 | 0.834831E+11 | 0.522794E+11 | 0.919098E+10 | 0.00 | 0.220845E+12 | 0.00 | 0.00 | 0.273366E+11 | 0.771356E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.640639E+12 | 0.00 | 0.204810E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.451489E+12 | 0.00 | 0.187584E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.164095E+12 | 0.00 | 0.206903E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.718893E+11 | 0.00 | 0.195371E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.250027E+11 | 0.00 | 0.195084E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.153921E+11 | 0.00 | 0.181948E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.704129E+10 | 0.00 | 0.182324E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.844601E+10 | 0.00 | 0.179844E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.256951E+11 | 0.00 | 0.175153E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.544829E+11 | 0.00 | 0.185572E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.216074E+12 | 0.00 | 0.185775E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.370135E+12 | 0.00 | 0.199467E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.205038E+13 | 0.227984E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.704129E+10 | 0.00 | 0.175153E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.640639E+12 | 0.00 | 0.206903E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 66976.13 | 02-JAN-20:10 | 14423.55 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 63148.16 | 02-JAN-07:19 | 28402.49 | 18-JAN-19:10 | 5635.42 | 06-JAN-10:00 | 0.00 | 01-JAN-00:10 |
February | 66976.13 | 01-FEB-20:10 | 14423.55 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 63148.16 | 01-FEB-07:19 | 26252.58 | 28-FEB-19:10 | 4919.97 | 16-FEB-10:20 | 0.00 | 01-FEB-00:10 |
March | 66976.13 | 01-MAR-20:10 | 14423.55 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 63148.16 | 13-MAR-06:19 | 31610.35 | 29-MAR-20:49 | 4690.42 | 05-MAR-17:30 | 0.00 | 01-MAR-00:10 |
April | 66976.13 | 03-APR-19:10 | 14423.55 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 63148.01 | 14-APR-06:19 | 34668.50 | 19-APR-21:49 | 4131.93 | 03-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 66976.13 | 01-MAY-19:10 | 14423.55 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 63146.49 | 10-MAY-06:19 | 31201.05 | 22-MAY-21:19 | 4079.20 | 29-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 66976.13 | 01-JUN-19:10 | 14423.55 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 63146.92 | 13-JUN-06:19 | 37691.90 | 02-JUN-21:00 | 4443.43 | 26-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 66976.13 | 03-JUL-19:30 | 14423.55 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 63146.49 | 20-JUL-06:19 | 27614.06 | 05-JUL-18:19 | 5077.02 | 17-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 66976.13 | 01-AUG-19:30 | 14423.55 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 63146.76 | 25-AUG-06:19 | 26571.42 | 02-AUG-19:10 | 5158.29 | 28-AUG-20:30 | 0.00 | 01-AUG-00:10 |
September | 66976.13 | 01-SEP-19:10 | 14423.55 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 63148.16 | 21-SEP-06:19 | 37514.65 | 19-SEP-21:10 | 4093.42 | 11-SEP-19:40 | 0.00 | 01-SEP-00:10 |
October | 66976.13 | 02-OCT-19:10 | 14423.55 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 63148.16 | 02-OCT-06:19 | 35701.63 | 05-OCT-20:10 | 4138.93 | 05-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 66976.13 | 01-NOV-19:10 | 14423.55 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 63148.16 | 01-NOV-06:19 | 36039.04 | 05-NOV-21:40 | 5042.03 | 25-NOV-10:20 | 0.00 | 01-NOV-00:10 |
December | 66976.13 | 01-DEC-20:10 | 14423.55 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 63148.16 | 01-DEC-07:19 | 28531.09 | 11-DEC-19:19 | 4991.22 | 10-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 66976.13 | 14423.55 | 89475.41 | 63146.49 | 26252.58 | 4079.20 | 0.00 | |||||||
Maximum of Months | 66976.13 | 14423.55 | 89475.41 | 63148.16 | 37691.90 | 5635.42 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3752.70 | 12-JAN-16:10 | 0.00 | 0.00 | 10206.30 | 01-JAN-09:09 | 4744.96 | 30-JAN-07:30 | 0.00 |
February | 7463.33 | 08-FEB-16:10 | 0.00 | 0.00 | 10206.30 | 01-FEB-16:10 | 4748.58 | 03-FEB-07:10 | 0.00 |
March | 47003.84 | 19-MAR-15:09 | 0.00 | 0.00 | 10206.30 | 01-MAR-09:09 | 4738.37 | 08-MAR-19:10 | 0.00 |
April | 132012.57 | 16-APR-18:10 | 0.00 | 0.00 | 10206.30 | 01-APR-08:09 | 4738.73 | 14-APR-18:10 | 0.00 |
May | 128175.25 | 30-MAY-18:10 | 0.00 | 0.00 | 10206.30 | 02-MAY-15:09 | 4738.61 | 30-MAY-18:10 | 0.00 |
June | 184753.58 | 11-JUN-15:09 | 0.00 | 0.00 | 10206.30 | 01-JUN-23:19 | 4738.67 | 23-JUN-18:10 | 0.00 |
July | 188751.08 | 26-JUL-18:10 | 0.00 | 0.00 | 10206.30 | 01-JUL-15:09 | 4738.69 | 26-JUL-18:10 | 0.00 |
August | 206061.74 | 04-AUG-15:20 | 0.00 | 0.00 | 10206.30 | 01-AUG-08:09 | 4738.53 | 11-AUG-18:10 | 0.00 |
September | 148685.58 | 06-SEP-15:09 | 0.00 | 0.00 | 10206.30 | 01-SEP-15:09 | 4738.37 | 20-SEP-18:10 | 0.00 |
October | 85082.10 | 20-OCT-15:09 | 0.00 | 0.00 | 10206.30 | 03-OCT-17:10 | 4738.44 | 04-OCT-06:00 | 0.00 |
November | 32300.54 | 05-NOV-15:09 | 0.00 | 0.00 | 10206.30 | 01-NOV-08:09 | 4738.30 | 17-NOV-19:10 | 0.00 |
December | 8354.33 | 03-DEC-13:30 | 0.00 | 0.00 | 10206.30 | 01-DEC-09:09 | 4738.45 | 20-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 3752.70 | 0.00 | 0.00 | 10206.30 | 4738.30 | 0.00 | |||
Maximum of Months | 206061.74 | 0.00 | 0.00 | 10206.30 | 4748.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 265718.19 | 18-JAN-20:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 26001.56 | 2433.45 | 0.00 | 0.00 | 0.00 |
February | 266608.38 | 02-FEB-20:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 25865.73 | 3715.23 | 0.00 | 0.00 | 0.00 |
March | 271536.74 | 29-MAR-19:30 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 26930.93 | 3278.08 | 0.00 | 3731.99 | 0.00 |
April | 379692.85 | 16-APR-19:10 | 61416.81 | 87285.99 | 14423.55 | 50836.08 | 24394.39 | 3917.69 | 0.00 | 121761.60 | 0.00 |
May | 381757.00 | 31-MAY-19:40 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 24720.85 | 3848.87 | 0.00 | 115436.94 | 0.00 |
June | 409059.94 | 26-JUN-19:00 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 26373.25 | 4185.17 | 0.00 | 141086.56 | 0.00 |
July | 428348.13 | 26-JUL-19:00 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 24684.25 | 4726.86 | 0.00 | 161734.23 | 0.00 |
August | 425364.38 | 03-AUG-19:40 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 25519.82 | 4697.36 | 0.00 | 157653.29 | 0.00 |
September | 381953.17 | 07-SEP-19:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 24594.59 | 3777.21 | 0.00 | 115972.12 | 0.00 |
October | 282599.57 | 20-OCT-19:30 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 23662.23 | 2917.07 | 0.00 | 29121.32 | 0.00 |
November | 275967.34 | 03-NOV-19:19 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 29482.19 | 2909.13 | 0.00 | 6726.41 | 0.00 |
December | 266546.68 | 04-DEC-20:49 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 24386.56 | 3603.18 | 0.00 | 854.14 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 265718.19 | 61416.81 | 87285.99 | 14423.55 | 50836.08 | 23662.23 | 2433.45 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428348.13 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 29482.19 | 4726.86 | 0.00 | 161734.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 777474.74 | 31-JAN-03:00 | 0.00 | 180063.78 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 811646.27 | 02-FEB-05:00 | 0.00 | 180198.21 | 21-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 249373.09 | 05-MAR-23:00 | 0.00 | 180161.18 | 01-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 177068.41 | 03-APR-08:09 | 0.00 | 181996.19 | 20-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 101832.01 | 22-MAY-22:40 | 0.00 | 181303.94 | 19-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 101578.86 | 22-JUN-04:10 | 0.00 | 178155.87 | 01-JUN-18:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 61275.65 | 24-JUL-02:39 | 0.00 | 176117.08 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 97041.62 | 07-AUG-02:00 | 0.00 | 175501.44 | 01-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 114010.04 | 21-SEP-01:19 | 0.00 | 178062.31 | 26-SEP-18:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 119293.29 | 22-OCT-07:00 | 0.00 | 178011.63 | 28-OCT-18:10 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 761271.26 | 26-NOV-06:00 | 0.00 | 178662.94 | 03-NOV-17:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 376479.99 | 09-DEC-09:09 | 0.00 | 179183.65 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 61275.65 | 0.00 | 175501.44 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 811646.27 | 0.00 | 181996.19 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.83 | 18.99 | 61.83 | 18.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 139.00 | 15.82 | 139.00 | 15.82 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.83 | 16.80 | 200.83 | 16.80 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.00 | 18.99 | 139.00 | 18.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.50 | 16.38 | 80.50 | 16.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99.67 | 14.50 | 99.67 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.17 | 16.95 | 12.17 | 16.95 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 20.37 | 6.67 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.00 | 15.61 | 199.00 | 15.61 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.67 | 20.37 | 99.67 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.67 | 17.38 | 86.67 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 102.67 | 14.22 | 102.67 | 14.22 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.83 | 18.43 | 11.83 | 18.43 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.17 | 15.83 | 201.17 | 15.83 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.67 | 18.43 | 102.67 | 18.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 105.00 | 18.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 138.83 | 15.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.17 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.00 | 16.68 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.83 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 126.00 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 141.00 | 15.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13.83 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 280.83 | 16.91 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.00 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.50 | 9.83 | 68.50 | 9.83 | 1.83 | 24.62 | 1.83 | 24.62 |
February | 72.50 | 6.24 | 72.50 | 6.24 | 6.17 | 24.62 | 6.17 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 24.75 | 17.00 | 24.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 24.95 | 20.67 | 24.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.83 | 8.50 | 24.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.84 | 2.17 | 24.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.02 | 17.00 | 25.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 24.82 | 25.50 | 24.82 |
November | 8.33 | 11.21 | 8.33 | 11.21 | 12.33 | 24.84 | 12.33 | 24.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.60 | 3.50 | 24.60 |
Annual Sum or Average | 149.33 | 8.16 | 149.33 | 8.16 | 114.67 | 24.84 | 114.67 | 24.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.50 | 11.21 | 72.50 | 11.21 | 25.50 | 25.02 | 25.50 | 25.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.67 | 17.08 | 78.67 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.33 | 14.21 | 83.33 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 17.67 | 11.67 | 17.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 173.67 | 15.74 | 173.67 | 15.74 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.33 | 17.67 | 83.33 | 17.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.33 | 17.45 | 80.33 | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91.00 | 14.01 | 91.00 | 14.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.00 | 18.47 | 11.00 | 18.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 182.33 | 15.79 | 182.33 | 15.79 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.00 | 18.47 | 91.00 | 18.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 20.30 | 9.50 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.50 | 19.62 | 44.50 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
November | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.45 | 2.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.17 | 19.77 | 56.17 | 19.77 | 0.50 | 21.75 | 0.50 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.50 | 20.52 | 44.50 | 20.52 | 0.17 | 21.80 | 0.17 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 20.14 | 21.50 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56.17 | 19.14 | 56.17 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.50 | 0.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.42 | 2.33 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.50 | 19.45 | 80.50 | 19.45 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.17 | 20.50 | 56.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 18.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26.83 | 17.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.50 | 17.78 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.83 | 18.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.83 | 19.78 | 71.83 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.00 | 17.73 | 83.00 | 17.73 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.41 | 0.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.82 | 0.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.67 | 20.20 | 10.67 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.00 | 20.28 | 7.00 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.83 | 18.85 | 172.83 | 18.85 | 4.00 | 21.74 | 4.00 | 21.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.00 | 20.41 | 83.00 | 20.41 | 2.00 | 21.82 | 2.00 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 20.23 | 19.83 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51.33 | 19.24 | 51.33 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.46 | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.40 | 2.00 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.33 | 19.55 | 73.33 | 19.55 | 0.33 | 21.85 | 0.33 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.33 | 20.46 | 51.33 | 20.46 | 0.33 | 21.85 | 0.33 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.67 | 20.09 | 35.67 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62.33 | 18.77 | 62.33 | 18.77 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.49 | 1.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.35 | 2.33 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.67 | 19.29 | 101.67 | 19.29 | 0.33 | 21.84 | 0.33 | 21.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.33 | 20.49 | 62.33 | 20.49 | 0.33 | 21.84 | 0.33 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.83 | 19.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 153.50 | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.50 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 278.83 | 18.17 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.50 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.50 | 20.28 | 18.50 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.83 | 19.64 | 44.83 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.67 | 0.50 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.81 | 0.67 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.92 | 0.17 | 21.92 |
November | 0.17 | 20.46 | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.38 | 2.33 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.83 | 19.85 | 65.83 | 19.85 | 2.17 | 21.77 | 2.17 | 21.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.83 | 20.46 | 44.83 | 20.46 | 0.67 | 21.92 | 0.67 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 20.10 | 38.33 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56.67 | 19.04 | 56.67 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.80 | 0.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.47 | 1.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.32 | 2.67 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99.00 | 19.50 | 99.00 | 19.50 | 1.00 | 21.71 | 1.00 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.67 | 20.47 | 56.67 | 20.47 | 0.50 | 21.80 | 0.50 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 20.23 | 24.00 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37.17 | 19.61 | 37.17 | 19.61 | 0.17 | 21.69 | 0.17 | 21.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.91 | 3.17 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.07 | 2.50 | 22.07 |
November | 0.33 | 20.48 | 0.33 | 20.48 | 0.83 | 22.01 | 0.83 | 22.01 |
December | 3.33 | 20.37 | 3.33 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.83 | 19.88 | 64.83 | 19.88 | 10.67 | 21.89 | 10.67 | 21.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.17 | 20.48 | 37.17 | 20.48 | 3.17 | 22.07 | 3.17 | 22.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.50 | 16.43 | 51.50 | 16.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84.83 | 13.63 | 84.83 | 13.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.68 | 0.17 | 24.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
November | 7.50 | 18.13 | 7.50 | 18.13 | 0.17 | 24.68 | 0.17 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.83 | 14.86 | 143.83 | 14.86 | 0.50 | 24.64 | 0.50 | 24.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.83 | 18.13 | 84.83 | 18.13 | 0.17 | 24.68 | 0.17 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.50 | 16.30 | 49.50 | 16.30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.83 | 13.48 | 83.83 | 13.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 24.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.65 | 0.17 | 24.65 |
November | 6.67 | 18.10 | 6.67 | 18.10 | 0.17 | 24.74 | 0.17 | 24.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.00 | 14.70 | 140.00 | 14.70 | 0.83 | 24.67 | 0.83 | 24.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.83 | 18.10 | 83.83 | 18.10 | 0.33 | 24.74 | 0.33 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 12.65 | 50.17 | 12.65 | 1.50 | 24.68 | 1.50 | 24.68 |
February | 66.33 | 9.92 | 66.33 | 9.92 | 7.17 | 24.71 | 7.17 | 24.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 24.87 | 49.67 | 24.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 25.00 | 61.17 | 25.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 24.89 | 29.50 | 24.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.87 | 12.00 | 24.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.79 | 0.33 | 24.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 25.00 | 49.17 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 24.91 | 86.67 | 24.91 |
November | 9.00 | 13.22 | 9.00 | 13.22 | 25.00 | 24.94 | 25.00 | 24.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.67 | 3.50 | 24.67 |
Annual Sum or Average | 125.50 | 11.25 | 125.50 | 11.25 | 325.67 | 24.92 | 325.67 | 24.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.33 | 13.22 | 66.33 | 13.22 | 86.67 | 25.00 | 86.67 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.67 | 18.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 133.33 | 15.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.17 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.17 | 16.53 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.33 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.15 | 105.50 | 19.76 | 105.50 | 19.76 |
February | 672.00 | 20.85 | 157.67 | 16.42 | 157.67 | 16.42 |
March | 744.00 | 21.85 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.47 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.56 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 22.26 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 665.33 | 23.05 | 1.67 | 24.00 | 0.00 | 0.00 |
October | 542.50 | 23.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 580.00 | 23.60 | 3.17 | 23.99 | 0.00 | 0.00 |
December | 744.00 | 23.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8363.83 | 22.19 | 268.00 | 17.87 | 263.17 | 17.76 |
Minimum of Months | 542.50 | 20.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.76 | 157.67 | 24.00 | 157.67 | 19.76 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 20.55 | 616.33 | 20.39 | 616.33 | 20.39 |
February | 657.50 | 20.09 | 419.67 | 19.51 | 412.67 | 19.43 |
March | 728.00 | 21.16 | 276.83 | 21.04 | 273.17 | 21.00 |
April | 686.83 | 21.26 | 129.50 | 21.35 | 112.50 | 21.00 |
May | 741.67 | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 663.17 | 21.43 | 11.00 | 23.20 | 0.00 | 0.00 |
July | 688.50 | 21.56 | 5.50 | 23.16 | 0.00 | 0.00 |
August | 649.00 | 21.59 | 34.17 | 23.38 | 0.00 | 0.00 |
September | 593.17 | 21.48 | 86.17 | 23.63 | 4.00 | 21.00 |
October | 668.67 | 21.28 | 58.00 | 23.34 | 12.50 | 21.00 |
November | 697.33 | 21.04 | 320.83 | 20.97 | 308.17 | 20.84 |
December | 729.83 | 21.08 | 582.17 | 21.00 | 579.17 | 20.98 |
Annual Sum or Average | 8243.83 | 21.14 | 2540.17 | 20.81 | 2318.50 | 20.53 |
Minimum of Months | 593.17 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 741.67 | 21.59 | 616.33 | 23.63 | 616.33 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 291.67 | 19.91 | 291.67 | 19.91 |
February | 672.00 | 20.41 | 148.50 | 16.30 | 148.50 | 16.30 |
March | 744.00 | 21.82 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 713.33 | 22.16 | 0.17 | 23.67 | 0.00 | 0.00 |
May | 739.33 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 682.00 | 22.30 | 8.33 | 23.68 | 0.00 | 0.00 |
July | 695.17 | 22.26 | 2.00 | 23.63 | 0.00 | 0.00 |
August | 667.00 | 22.34 | 12.17 | 23.70 | 0.00 | 0.00 |
September | 668.50 | 22.52 | 11.67 | 23.80 | 0.00 | 0.00 |
October | 739.17 | 22.49 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 719.83 | 21.83 | 53.17 | 20.42 | 53.17 | 20.42 |
December | 744.00 | 21.41 | 98.33 | 21.00 | 98.33 | 21.00 |
Annual Sum or Average | 8528.33 | 21.88 | 626.00 | 19.48 | 591.67 | 19.23 |
Minimum of Months | 667.00 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.52 | 291.67 | 23.80 | 291.67 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.50 | 20.05 | 363.00 | 20.90 | 184.67 | 18.41 |
February | 331.00 | 18.61 | 384.67 | 20.03 | 188.83 | 16.58 |
March | 271.17 | 22.85 | 418.33 | 23.58 | 152.33 | 24.19 |
April | 265.00 | 23.08 | 469.67 | 23.29 | 172.33 | 24.16 |
May | 265.00 | 23.38 | 550.50 | 22.85 | 210.50 | 23.99 |
June | 223.17 | 23.51 | 555.50 | 22.49 | 193.00 | 23.90 |
July | 191.17 | 23.63 | 584.50 | 22.26 | 175.50 | 23.87 |
August | 208.67 | 23.64 | 585.17 | 22.34 | 192.33 | 23.86 |
September | 250.50 | 23.39 | 520.00 | 22.85 | 195.33 | 24.05 |
October | 268.50 | 23.19 | 521.50 | 23.36 | 183.50 | 24.17 |
November | 299.00 | 22.43 | 424.17 | 23.18 | 166.67 | 23.39 |
December | 323.00 | 22.41 | 344.67 | 23.71 | 125.50 | 24.14 |
Annual Sum or Average | 3323.67 | 22.25 | 5721.67 | 22.60 | 2140.50 | 22.83 |
Minimum of Months | 191.17 | 18.61 | 344.67 | 20.03 | 125.50 | 16.58 |
Maximum of Months | 427.50 | 23.64 | 585.17 | 23.71 | 210.50 | 24.19 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.67 | 20.72 | 399.67 | 20.24 | 397.67 | 20.22 |
February | 647.17 | 20.51 | 213.00 | 18.53 | 200.17 | 18.18 |
March | 694.83 | 21.70 | 73.00 | 21.52 | 59.33 | 21.00 |
April | 596.33 | 21.93 | 61.00 | 23.19 | 5.50 | 21.00 |
May | 650.17 | 22.22 | 59.50 | 23.18 | 44.00 | 23.10 |
June | 477.33 | 22.19 | 166.00 | 23.28 | 59.67 | 23.17 |
July | 506.50 | 22.30 | 260.50 | 23.19 | 141.83 | 23.16 |
August | 457.67 | 22.42 | 332.00 | 23.28 | 148.67 | 23.33 |
September | 432.67 | 22.40 | 227.17 | 23.56 | 35.83 | 23.53 |
October | 584.50 | 22.22 | 91.00 | 23.91 | 0.00 | 0.00 |
November | 665.50 | 21.55 | 126.50 | 21.27 | 101.67 | 20.62 |
December | 713.33 | 21.29 | 263.17 | 21.12 | 252.83 | 21.00 |
Annual Sum or Average | 7155.67 | 21.71 | 2272.50 | 21.92 | 1447.17 | 21.04 |
Minimum of Months | 432.67 | 20.51 | 59.50 | 18.53 | 0.00 | 0.00 |
Maximum of Months | 729.67 | 22.42 | 399.67 | 23.91 | 397.67 | 23.53 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 177.33 | 19.39 | 177.33 | 19.39 |
February | 672.00 | 20.85 | 137.17 | 16.36 | 137.17 | 16.36 |
March | 726.83 | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 651.50 | 22.45 | 10.67 | 23.73 | 0.00 | 0.00 |
May | 603.50 | 22.50 | 62.00 | 23.50 | 30.00 | 23.25 |
June | 491.50 | 22.33 | 90.17 | 23.56 | 18.17 | 23.23 |
July | 508.00 | 22.27 | 112.67 | 23.45 | 32.67 | 23.18 |
August | 485.67 | 22.37 | 175.00 | 23.57 | 54.00 | 23.37 |
September | 488.33 | 22.68 | 82.33 | 23.66 | 13.67 | 23.45 |
October | 647.17 | 22.83 | 9.50 | 23.92 | 0.00 | 0.00 |
November | 652.50 | 22.10 | 36.33 | 20.88 | 28.00 | 19.99 |
December | 744.00 | 21.81 | 41.17 | 21.00 | 41.17 | 21.00 |
Annual Sum or Average | 7415.00 | 22.08 | 934.33 | 21.49 | 532.17 | 19.85 |
Minimum of Months | 485.67 | 20.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.83 | 177.33 | 23.92 | 177.33 | 23.45 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 726.83 | 20.52 | 726.83 | 20.52 |
February | 672.00 | 20.59 | 588.00 | 20.48 | 588.00 | 20.48 |
March | 744.00 | 20.92 | 452.67 | 20.68 | 452.67 | 20.68 |
April | 703.17 | 21.11 | 208.83 | 20.66 | 204.50 | 20.61 |
May | 725.33 | 21.42 | 11.00 | 21.37 | 8.67 | 21.02 |
June | 655.50 | 21.41 | 20.00 | 22.49 | 5.83 | 21.61 |
July | 653.50 | 21.44 | 27.50 | 22.87 | 3.00 | 22.09 |
August | 657.00 | 21.44 | 27.67 | 22.20 | 15.50 | 21.60 |
September | 667.00 | 21.35 | 32.00 | 21.28 | 25.17 | 20.80 |
October | 740.83 | 21.21 | 135.83 | 20.82 | 135.83 | 20.82 |
November | 720.00 | 20.81 | 462.50 | 20.61 | 462.50 | 20.61 |
December | 744.00 | 20.63 | 710.17 | 20.60 | 710.17 | 20.60 |
Annual Sum or Average | 8426.33 | 21.06 | 3403.00 | 20.64 | 3338.67 | 20.59 |
Minimum of Months | 653.50 | 20.53 | 11.00 | 20.48 | 3.00 | 20.48 |
Maximum of Months | 744.00 | 21.44 | 726.83 | 22.87 | 726.83 | 22.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 743.67 | 20.44 | 743.67 | 20.44 |
February | 672.00 | 20.38 | 646.33 | 20.35 | 646.33 | 20.35 |
March | 744.00 | 20.73 | 522.50 | 20.57 | 522.50 | 20.57 |
April | 710.00 | 21.01 | 247.00 | 20.58 | 244.67 | 20.56 |
May | 732.17 | 21.38 | 13.33 | 21.03 | 12.33 | 20.92 |
June | 663.33 | 21.42 | 17.17 | 22.54 | 4.83 | 21.67 |
July | 670.50 | 21.46 | 23.17 | 22.81 | 3.00 | 21.99 |
August | 685.33 | 21.47 | 25.00 | 22.03 | 16.17 | 21.55 |
September | 694.00 | 21.31 | 44.00 | 20.73 | 42.67 | 20.67 |
October | 744.00 | 20.97 | 291.33 | 20.72 | 291.33 | 20.72 |
November | 720.00 | 20.66 | 524.83 | 20.53 | 524.83 | 20.53 |
December | 744.00 | 20.49 | 743.83 | 20.49 | 743.83 | 20.49 |
Annual Sum or Average | 8523.33 | 20.97 | 3842.17 | 20.53 | 3796.17 | 20.51 |
Minimum of Months | 663.33 | 20.38 | 13.33 | 20.35 | 3.00 | 20.35 |
Maximum of Months | 744.00 | 21.47 | 743.83 | 22.81 | 743.83 | 21.99 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 717.33 | 20.45 | 717.33 | 20.45 |
February | 672.00 | 20.35 | 538.83 | 20.16 | 538.83 | 20.16 |
March | 744.00 | 20.92 | 404.50 | 20.77 | 404.50 | 20.77 |
April | 720.00 | 21.11 | 141.17 | 20.78 | 141.17 | 20.78 |
May | 744.00 | 21.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.44 | 4.33 | 21.97 | 4.33 | 21.97 |
July | 744.00 | 21.45 | 6.50 | 22.06 | 6.50 | 22.06 |
August | 744.00 | 21.42 | 18.67 | 21.61 | 18.67 | 21.61 |
September | 720.00 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.10 | 37.50 | 20.66 | 37.50 | 20.66 |
November | 720.00 | 20.86 | 399.50 | 20.66 | 399.50 | 20.66 |
December | 744.00 | 20.65 | 712.00 | 20.63 | 712.00 | 20.63 |
Annual Sum or Average | 8760.00 | 21.04 | 2980.33 | 20.54 | 2980.33 | 20.54 |
Minimum of Months | 672.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.45 | 717.33 | 22.06 | 717.33 | 22.06 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 726.50 | 20.49 | 726.50 | 20.49 |
February | 672.00 | 20.54 | 582.67 | 20.44 | 582.67 | 20.44 |
March | 744.00 | 20.98 | 428.83 | 20.74 | 428.83 | 20.74 |
April | 704.00 | 21.16 | 220.83 | 20.66 | 220.17 | 20.65 |
May | 723.17 | 21.52 | 6.50 | 21.30 | 5.67 | 21.11 |
June | 643.67 | 21.45 | 9.00 | 22.33 | 3.50 | 21.52 |
July | 636.17 | 21.44 | 12.00 | 22.60 | 3.00 | 21.97 |
August | 648.00 | 21.46 | 16.00 | 21.90 | 12.17 | 21.62 |
September | 661.17 | 21.40 | 17.33 | 21.14 | 15.33 | 20.95 |
October | 744.00 | 21.27 | 129.33 | 20.91 | 129.33 | 20.91 |
November | 720.00 | 20.81 | 463.83 | 20.60 | 463.83 | 20.60 |
December | 744.00 | 20.61 | 710.00 | 20.59 | 710.00 | 20.59 |
Annual Sum or Average | 8384.17 | 21.08 | 3322.83 | 20.60 | 3301.00 | 20.59 |
Minimum of Months | 636.17 | 20.51 | 6.50 | 20.44 | 3.00 | 20.44 |
Maximum of Months | 744.00 | 21.52 | 726.50 | 22.60 | 726.50 | 21.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 741.83 | 20.42 | 741.83 | 20.42 |
February | 672.00 | 20.33 | 646.83 | 20.30 | 646.83 | 20.30 |
March | 744.00 | 20.78 | 503.83 | 20.62 | 503.83 | 20.62 |
April | 710.50 | 21.06 | 249.00 | 20.65 | 248.50 | 20.65 |
May | 732.33 | 21.50 | 10.33 | 21.23 | 9.50 | 21.11 |
June | 652.00 | 21.46 | 8.83 | 22.35 | 3.17 | 21.43 |
July | 655.00 | 21.49 | 12.50 | 22.48 | 3.50 | 21.72 |
August | 691.83 | 21.56 | 16.33 | 21.83 | 12.83 | 21.56 |
September | 699.33 | 21.42 | 27.33 | 20.96 | 26.00 | 20.90 |
October | 744.00 | 21.01 | 270.50 | 20.85 | 270.50 | 20.85 |
November | 720.00 | 20.65 | 516.50 | 20.52 | 516.50 | 20.52 |
December | 744.00 | 20.49 | 740.67 | 20.49 | 740.67 | 20.49 |
Annual Sum or Average | 8509.00 | 21.01 | 3744.50 | 20.52 | 3723.67 | 20.51 |
Minimum of Months | 652.00 | 20.33 | 8.83 | 20.30 | 3.17 | 20.30 |
Maximum of Months | 744.00 | 21.56 | 741.83 | 22.48 | 741.83 | 21.72 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 735.50 | 20.47 | 735.50 | 20.47 |
February | 672.00 | 20.53 | 617.83 | 20.46 | 617.83 | 20.46 |
March | 743.50 | 20.83 | 515.17 | 20.63 | 515.17 | 20.63 |
April | 699.33 | 21.07 | 278.17 | 20.71 | 269.33 | 20.63 |
May | 707.33 | 21.41 | 29.67 | 21.55 | 22.17 | 21.05 |
June | 623.17 | 21.34 | 44.17 | 22.75 | 10.00 | 21.74 |
July | 618.67 | 21.36 | 65.33 | 22.82 | 13.33 | 21.80 |
August | 620.83 | 21.35 | 67.67 | 22.48 | 26.67 | 21.56 |
September | 653.33 | 21.30 | 64.00 | 21.39 | 46.67 | 20.75 |
October | 740.17 | 21.15 | 261.00 | 20.82 | 261.00 | 20.82 |
November | 719.33 | 20.74 | 517.00 | 20.58 | 517.00 | 20.58 |
December | 744.00 | 20.57 | 728.33 | 20.55 | 728.33 | 20.55 |
Annual Sum or Average | 8285.67 | 20.99 | 3923.83 | 20.68 | 3763.00 | 20.58 |
Minimum of Months | 618.67 | 20.48 | 29.67 | 20.46 | 10.00 | 20.46 |
Maximum of Months | 744.00 | 21.41 | 735.50 | 22.82 | 735.50 | 21.80 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.40 | 744.00 | 20.40 | 744.00 | 20.40 |
February | 672.00 | 20.34 | 659.00 | 20.32 | 659.00 | 20.32 |
March | 744.00 | 20.66 | 577.67 | 20.53 | 577.67 | 20.53 |
April | 706.17 | 20.97 | 325.17 | 20.64 | 318.83 | 20.60 |
May | 716.17 | 21.39 | 32.83 | 21.34 | 27.00 | 20.99 |
June | 630.67 | 21.36 | 39.17 | 22.76 | 8.00 | 21.73 |
July | 630.50 | 21.39 | 59.50 | 22.76 | 13.33 | 21.77 |
August | 647.50 | 21.41 | 57.50 | 22.26 | 28.17 | 21.51 |
September | 679.00 | 21.28 | 73.00 | 20.90 | 65.83 | 20.67 |
October | 744.00 | 20.88 | 390.50 | 20.66 | 390.50 | 20.66 |
November | 720.00 | 20.60 | 568.17 | 20.50 | 568.17 | 20.50 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8378.00 | 20.91 | 4270.50 | 20.57 | 4144.50 | 20.50 |
Minimum of Months | 630.50 | 20.34 | 32.83 | 20.32 | 8.00 | 20.32 |
Maximum of Months | 744.00 | 21.41 | 744.00 | 22.76 | 744.00 | 21.77 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 628.67 | 20.65 | 628.67 | 20.65 |
February | 665.50 | 20.89 | 464.17 | 20.59 | 464.17 | 20.59 |
March | 738.83 | 21.16 | 375.17 | 20.79 | 375.17 | 20.79 |
April | 698.00 | 21.19 | 208.33 | 20.75 | 204.50 | 20.70 |
May | 722.67 | 21.47 | 1.00 | 20.57 | 1.00 | 20.57 |
June | 663.00 | 21.45 | 9.83 | 21.85 | 9.83 | 21.85 |
July | 655.17 | 21.44 | 11.00 | 22.11 | 11.00 | 22.11 |
August | 651.83 | 21.42 | 25.50 | 21.88 | 22.67 | 21.70 |
September | 648.33 | 21.37 | 41.33 | 22.49 | 14.00 | 20.93 |
October | 699.83 | 21.31 | 60.00 | 21.03 | 56.83 | 20.91 |
November | 707.17 | 21.04 | 385.67 | 20.74 | 383.83 | 20.73 |
December | 741.00 | 20.94 | 608.83 | 20.69 | 608.83 | 20.69 |
Annual Sum or Average | 8335.33 | 21.21 | 2819.50 | 20.74 | 2780.50 | 20.71 |
Minimum of Months | 648.33 | 20.86 | 1.00 | 20.57 | 1.00 | 20.57 |
Maximum of Months | 744.00 | 21.47 | 628.67 | 22.49 | 628.67 | 22.11 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 704.50 | 22.04 | 113.33 | 18.48 | 113.33 | 18.48 |
February | 543.50 | 21.37 | 120.33 | 15.82 | 120.33 | 15.82 |
March | 472.00 | 23.11 | 54.67 | 23.98 | 0.00 | 0.00 |
April | 256.33 | 23.07 | 166.67 | 23.87 | 5.50 | 23.95 |
May | 156.33 | 23.28 | 443.00 | 23.87 | 64.33 | 23.95 |
June | 96.83 | 23.77 | 597.17 | 23.80 | 81.50 | 23.97 |
July | 178.50 | 23.83 | 630.67 | 23.77 | 162.00 | 23.97 |
August | 178.67 | 23.74 | 575.33 | 23.80 | 153.00 | 23.96 |
September | 176.50 | 23.12 | 402.50 | 23.83 | 45.50 | 23.97 |
October | 287.83 | 23.02 | 101.67 | 23.96 | 0.00 | 0.00 |
November | 480.17 | 22.82 | 108.17 | 23.18 | 23.17 | 20.37 |
December | 698.00 | 22.91 | 9.50 | 21.03 | 9.50 | 21.03 |
Annual Sum or Average | 4229.17 | 22.71 | 3323.00 | 23.32 | 778.17 | 21.76 |
Minimum of Months | 96.83 | 21.37 | 9.50 | 15.82 | 0.00 | 0.00 |
Maximum of Months | 704.50 | 23.83 | 630.67 | 23.98 | 162.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 641.00 | 22.13 | 108.83 | 18.47 | 105.67 | 18.30 |
February | 435.67 | 21.05 | 120.17 | 15.97 | 111.83 | 15.38 |
March | 277.83 | 23.11 | 105.33 | 23.97 | 0.00 | 0.00 |
April | 115.33 | 23.13 | 276.17 | 23.90 | 1.17 | 23.94 |
May | 47.17 | 23.95 | 599.33 | 23.83 | 45.50 | 23.98 |
June | 56.00 | 23.98 | 684.50 | 23.78 | 56.00 | 23.98 |
July | 125.33 | 23.99 | 722.00 | 23.73 | 125.33 | 23.99 |
August | 121.67 | 23.97 | 694.50 | 23.72 | 121.67 | 23.97 |
September | 72.17 | 23.48 | 526.00 | 23.82 | 36.17 | 23.98 |
October | 117.33 | 23.07 | 222.50 | 23.97 | 0.00 | 0.00 |
November | 333.00 | 22.84 | 152.83 | 23.52 | 14.33 | 19.18 |
December | 529.33 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2871.83 | 22.63 | 4212.17 | 23.43 | 617.67 | 21.34 |
Minimum of Months | 47.17 | 21.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 641.00 | 23.99 | 722.00 | 23.97 | 125.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 534.33 | 22.16 | 587.00 | 22.81 | 418.17 | 22.38 |
February | 503.17 | 21.63 | 558.50 | 22.03 | 444.17 | 21.59 |
March | 545.50 | 23.95 | 633.67 | 24.02 | 493.33 | 24.14 |
April | 514.50 | 24.14 | 657.50 | 23.98 | 504.17 | 24.18 |
May | 547.67 | 24.08 | 733.83 | 23.83 | 547.67 | 24.08 |
June | 538.83 | 24.02 | 719.67 | 23.68 | 538.83 | 24.02 |
July | 557.33 | 23.98 | 743.33 | 23.60 | 557.33 | 23.98 |
August | 556.50 | 23.98 | 742.67 | 23.64 | 556.50 | 23.98 |
September | 521.83 | 24.11 | 708.00 | 23.80 | 521.83 | 24.11 |
October | 521.33 | 24.21 | 682.50 | 24.01 | 520.00 | 24.21 |
November | 521.50 | 23.69 | 619.33 | 23.81 | 467.83 | 23.89 |
December | 537.50 | 23.60 | 580.33 | 23.99 | 424.83 | 24.03 |
Annual Sum or Average | 6400.00 | 23.64 | 7966.33 | 23.63 | 5994.67 | 23.76 |
Minimum of Months | 503.17 | 21.63 | 558.50 | 22.03 | 418.17 | 21.59 |
Maximum of Months | 557.33 | 24.21 | 743.33 | 24.02 | 557.33 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15192 | 17.62720 | -0.2561 | 8.00841 |
February | 672.00000 | 20.84558 | 21.93347 | -0.5469 | 18.12564 |
March | 744.00000 | 21.85453 | 28.58785 | -0.2813 | 6.81251 |
April | 720.00000 | 21.42374 | 36.52904 | -0.3419 | 7.56353 |
May | 744.00000 | 21.40285 | 49.78024 | -1.4303 | 47.19837 |
June | 720.00000 | 21.46695 | 56.17437 | -1.3528 | 43.16793 |
July | 744.00000 | 21.55653 | 58.52263 | -1.2933 | 40.05615 |
August | 744.00000 | 22.26061 | 55.69206 | -1.0568 | 28.87522 |
September | 720.00000 | 23.11634 | 43.96925 | -0.8355 | 20.13507 |
October | 744.00000 | 23.80893 | 31.49412 | 0.24548 | 6.32814 |
November | 720.00000 | 23.66667 | 27.18851 | 0.17995 | 6.12618 |
December | 744.00000 | 23.57317 | 20.20675 | 0.10088 | 5.33326 |
Annual Sum or Average | 8760.00000 | 22.27055 | 37.39509 | -0.5724 | 19.83088 |
Minimum of Months | 672.00000 | 20.84558 | 17.62720 | -1.4303 | 5.33326 |
Maximum of Months | 744.00000 | 23.80893 | 58.52263 | 0.24548 | 47.19837 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56582 | 16.92433 | -0.7447 | 19.08075 |
February | 672.00000 | 20.16697 | 21.03721 | -0.7578 | 20.92620 |
March | 744.00000 | 21.21384 | 27.71025 | -0.4402 | 10.10746 |
April | 720.00000 | 21.35635 | 34.99099 | -0.3162 | 8.55551 |
May | 744.00000 | 21.26048 | 49.15167 | -1.3424 | 42.89909 |
June | 720.00000 | 21.55743 | 55.78993 | -1.1594 | 34.43241 |
July | 744.00000 | 21.65489 | 58.89983 | -1.0842 | 30.74323 |
August | 744.00000 | 21.78130 | 57.54852 | -1.0468 | 29.49003 |
September | 720.00000 | 21.84234 | 45.62258 | -1.1315 | 35.05601 |
October | 744.00000 | 21.54206 | 34.03090 | -0.2441 | 7.93151 |
November | 720.00000 | 21.12618 | 29.27435 | -0.4635 | 11.19113 |
December | 744.00000 | 21.13450 | 20.63271 | -0.5826 | 13.24865 |
Annual Sum or Average | 8760.00000 | 21.27366 | 37.72937 | -0.7764 | 21.97673 |
Minimum of Months | 672.00000 | 20.16697 | 16.92433 | -1.3424 | 7.93151 |
Maximum of Months | 744.00000 | 21.84234 | 58.89983 | -0.2441 | 42.89909 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77901 | 19.03130 | -0.5739 | 13.95324 |
February | 672.00000 | 20.40822 | 22.79279 | -0.6234 | 18.62676 |
March | 744.00000 | 21.82255 | 29.03579 | -0.2474 | 6.95694 |
April | 720.00000 | 22.17091 | 35.67231 | -0.1100 | 5.95506 |
May | 744.00000 | 22.31779 | 48.24123 | -1.0396 | 28.37947 |
June | 720.00000 | 22.36210 | 54.59404 | -0.9658 | 25.33355 |
July | 744.00000 | 22.33737 | 57.39664 | -0.9464 | 24.50732 |
August | 744.00000 | 22.45694 | 56.33515 | -0.9129 | 23.24112 |
September | 720.00000 | 22.59509 | 45.76285 | -0.9482 | 24.72294 |
October | 744.00000 | 22.50078 | 34.48094 | -0.0339 | 5.37653 |
November | 720.00000 | 21.82883 | 30.23878 | -0.2381 | 7.48643 |
December | 744.00000 | 21.40853 | 22.71293 | -0.4008 | 8.70934 |
Annual Sum or Average | 8760.00000 | 21.92452 | 38.11093 | -0.5866 | 16.08584 |
Minimum of Months | 672.00000 | 20.40822 | 19.03130 | -1.0396 | 5.37653 |
Maximum of Months | 744.00000 | 22.59509 | 57.39664 | -0.0339 | 28.37947 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26262 | 14.20326 | 0.12187 | 19.15836 |
February | 672.00000 | 20.74217 | 17.96686 | 0.04314 | 23.28635 |
March | 744.00000 | 22.75562 | 23.84007 | 0.55859 | 14.91628 |
April | 720.00000 | 22.69218 | 30.86975 | 0.60921 | 16.08366 |
May | 744.00000 | 22.41306 | 43.87185 | -0.1204 | 12.43587 |
June | 720.00000 | 22.16076 | 50.88841 | -0.1384 | 12.65799 |
July | 744.00000 | 21.99577 | 53.98795 | -0.1685 | 12.67619 |
August | 744.00000 | 22.06076 | 53.11538 | -0.1510 | 12.85443 |
September | 720.00000 | 22.37618 | 42.31680 | -0.1365 | 12.62142 |
October | 744.00000 | 22.78505 | 29.90472 | 0.63223 | 16.56629 |
November | 720.00000 | 22.55126 | 25.23056 | 0.51821 | 15.72390 |
December | 744.00000 | 22.64411 | 17.50807 | 0.45889 | 12.67240 |
Annual Sum or Average | 8760.00000 | 22.21265 | 33.73043 | 0.18649 | 15.08028 |
Minimum of Months | 672.00000 | 20.74217 | 14.20326 | -0.1685 | 12.43587 |
Maximum of Months | 744.00000 | 22.78505 | 53.98795 | 0.63223 | 23.28635 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77471 | 22.30148 | -0.5915 | 14.97151 |
February | 672.00000 | 20.63171 | 25.98125 | -0.5518 | 17.35500 |
March | 744.00000 | 21.82091 | 32.51719 | -0.2064 | 7.44047 |
April | 720.00000 | 22.16965 | 39.25180 | -0.0475 | 6.84667 |
May | 744.00000 | 22.34564 | 52.01536 | -0.9102 | 23.40869 |
June | 720.00000 | 22.49660 | 58.33026 | -0.7747 | 18.77235 |
July | 744.00000 | 22.51594 | 61.18632 | -0.7269 | 16.97256 |
August | 744.00000 | 22.68685 | 59.93483 | -0.6728 | 15.50970 |
September | 720.00000 | 22.80767 | 49.02659 | -0.7302 | 18.79021 |
October | 744.00000 | 22.54531 | 38.07413 | 0.06565 | 6.56883 |
November | 720.00000 | 21.71098 | 33.88976 | -0.2346 | 8.63038 |
December | 744.00000 | 21.38537 | 26.11687 | -0.4186 | 10.03558 |
Annual Sum or Average | 8760.00000 | 21.99877 | 41.64098 | -0.4831 | 13.75139 |
Minimum of Months | 672.00000 | 20.63171 | 22.30148 | -0.9102 | 6.56883 |
Maximum of Months | 744.00000 | 22.80767 | 61.18632 | 0.06565 | 23.40869 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09053 | 21.47648 | -0.4698 | 11.98632 |
February | 672.00000 | 20.85140 | 25.01670 | -0.4913 | 16.81021 |
March | 744.00000 | 22.27145 | 31.30114 | -0.1086 | 6.12602 |
April | 720.00000 | 22.55875 | 37.92751 | 0.01735 | 5.86932 |
May | 744.00000 | 22.70190 | 50.26396 | -0.8617 | 21.58877 |
June | 720.00000 | 22.67777 | 56.71117 | -0.8055 | 19.59237 |
July | 744.00000 | 22.60145 | 59.61621 | -0.8013 | 19.38745 |
August | 744.00000 | 22.74859 | 58.49993 | -0.7573 | 17.97021 |
September | 720.00000 | 22.94971 | 47.91281 | -0.7741 | 18.48754 |
October | 744.00000 | 22.96056 | 36.65582 | 0.11623 | 5.72583 |
November | 720.00000 | 22.25213 | 32.47206 | -0.1039 | 6.89819 |
December | 744.00000 | 21.80638 | 25.12604 | -0.2780 | 7.27723 |
Annual Sum or Average | 8760.00000 | 22.29752 | 40.33507 | -0.4430 | 13.11788 |
Minimum of Months | 672.00000 | 20.85140 | 21.47648 | -0.8617 | 5.72583 |
Maximum of Months | 744.00000 | 22.96056 | 59.61621 | 0.11623 | 21.58877 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53112 | 21.11269 | -0.8152 | 19.63301 |
February | 672.00000 | 20.58588 | 25.20371 | -0.7386 | 17.72363 |
March | 744.00000 | 20.91578 | 31.62078 | -0.5669 | 12.59080 |
April | 720.00000 | 21.16236 | 39.03776 | -0.3970 | 9.65838 |
May | 744.00000 | 21.45822 | 52.34246 | -1.3452 | 43.40256 |
June | 720.00000 | 21.56768 | 57.29228 | -1.2143 | 37.28123 |
July | 744.00000 | 21.64326 | 59.67351 | -1.1428 | 33.89859 |
August | 744.00000 | 21.63787 | 59.70586 | -1.1628 | 34.83970 |
September | 720.00000 | 21.48521 | 49.38187 | -1.3396 | 43.60527 |
October | 744.00000 | 21.22202 | 38.86493 | -0.3998 | 9.02436 |
November | 720.00000 | 20.81246 | 33.55575 | -0.6059 | 13.75160 |
December | 744.00000 | 20.63098 | 24.27351 | -0.7588 | 17.77660 |
Annual Sum or Average | 8760.00000 | 21.14097 | 41.09353 | -0.8749 | 24.46929 |
Minimum of Months | 672.00000 | 20.53112 | 21.11269 | -1.3452 | 9.02436 |
Maximum of Months | 744.00000 | 21.64326 | 59.70586 | -0.3970 | 43.60527 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.44150 | 21.24446 | -0.8662 | 21.51617 |
February | 672.00000 | 20.37827 | 25.47978 | -0.8162 | 20.32111 |
March | 744.00000 | 20.72598 | 31.94732 | -0.6306 | 14.09791 |
April | 720.00000 | 21.04292 | 39.37659 | -0.4381 | 10.23091 |
May | 744.00000 | 21.40622 | 52.54780 | -1.3711 | 44.61820 |
June | 720.00000 | 21.55328 | 57.38200 | -1.2236 | 37.66027 |
July | 744.00000 | 21.62658 | 59.91257 | -1.1550 | 34.36153 |
August | 744.00000 | 21.60076 | 60.25342 | -1.1877 | 35.82206 |
September | 720.00000 | 21.37782 | 50.09139 | -1.4008 | 46.39816 |
October | 744.00000 | 20.96537 | 39.38897 | -0.4858 | 10.34866 |
November | 720.00000 | 20.66059 | 33.83698 | -0.6631 | 15.17462 |
December | 744.00000 | 20.49458 | 24.47643 | -0.8154 | 19.61445 |
Annual Sum or Average | 8760.00000 | 21.02663 | 41.41628 | -0.9219 | 25.87578 |
Minimum of Months | 672.00000 | 20.37827 | 21.24446 | -1.4008 | 10.23091 |
Maximum of Months | 744.00000 | 21.62658 | 60.25342 | -0.4381 | 46.39816 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47247 | 19.87558 | -0.7687 | 18.24685 |
February | 672.00000 | 20.34491 | 23.88969 | -0.7594 | 19.07218 |
March | 744.00000 | 20.92457 | 30.47025 | -0.5520 | 11.74186 |
April | 720.00000 | 21.10905 | 38.08108 | -0.4299 | 9.27483 |
May | 744.00000 | 21.32753 | 50.53740 | -1.4368 | 47.62021 |
June | 720.00000 | 21.43660 | 56.40678 | -1.3343 | 42.36829 |
July | 744.00000 | 21.45315 | 59.59754 | -1.3025 | 40.70906 |
August | 744.00000 | 21.42275 | 59.22535 | -1.3248 | 41.81263 |
September | 720.00000 | 21.31047 | 48.70359 | -1.4608 | 48.92886 |
October | 744.00000 | 21.09753 | 37.78930 | -0.4408 | 9.19159 |
November | 720.00000 | 20.85775 | 32.17918 | -0.5653 | 12.35900 |
December | 744.00000 | 20.65145 | 23.13956 | -0.7000 | 15.79333 |
Annual Sum or Average | 8760.00000 | 21.03810 | 40.08141 | -0.9240 | 26.46721 |
Minimum of Months | 672.00000 | 20.34491 | 19.87558 | -1.4608 | 9.19159 |
Maximum of Months | 744.00000 | 21.45315 | 59.59754 | -0.4299 | 48.92886 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50885 | 21.10201 | -0.8183 | 19.77003 |
February | 672.00000 | 20.54462 | 25.18812 | -0.7494 | 18.17530 |
March | 744.00000 | 20.97603 | 31.51250 | -0.5514 | 12.23197 |
April | 720.00000 | 21.20268 | 38.88140 | -0.3978 | 9.71265 |
May | 744.00000 | 21.56607 | 51.68375 | -1.3029 | 41.37668 |
June | 720.00000 | 21.63158 | 56.63252 | -1.1922 | 36.32766 |
July | 744.00000 | 21.69710 | 59.27195 | -1.1306 | 33.43864 |
August | 744.00000 | 21.68382 | 59.10482 | -1.1560 | 34.56720 |
September | 720.00000 | 21.54975 | 49.02220 | -1.3168 | 42.51180 |
October | 744.00000 | 21.26659 | 38.80457 | -0.3923 | 8.86875 |
November | 720.00000 | 20.80530 | 33.55548 | -0.6084 | 13.81309 |
December | 744.00000 | 20.61452 | 24.28197 | -0.7622 | 17.87439 |
Annual Sum or Average | 8760.00000 | 21.17433 | 40.84007 | -0.8657 | 24.08718 |
Minimum of Months | 672.00000 | 20.50885 | 21.10201 | -1.3168 | 8.86875 |
Maximum of Months | 744.00000 | 21.69710 | 59.27195 | -0.3923 | 42.51180 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.42145 | 21.22411 | -0.8697 | 21.69783 |
February | 672.00000 | 20.32590 | 25.46176 | -0.8300 | 20.96248 |
March | 744.00000 | 20.78011 | 31.82472 | -0.6164 | 13.67493 |
April | 720.00000 | 21.08984 | 39.22222 | -0.4382 | 10.24035 |
May | 744.00000 | 21.52567 | 51.86114 | -1.3256 | 42.40333 |
June | 720.00000 | 21.62388 | 56.72363 | -1.1996 | 36.62445 |
July | 744.00000 | 21.69113 | 59.50955 | -1.1396 | 33.78336 |
August | 744.00000 | 21.66740 | 59.64903 | -1.1750 | 35.31429 |
September | 720.00000 | 21.47247 | 49.61488 | -1.3693 | 44.88515 |
October | 744.00000 | 21.00991 | 39.31036 | -0.4791 | 10.08061 |
November | 720.00000 | 20.65127 | 33.84271 | -0.6669 | 15.28842 |
December | 744.00000 | 20.49009 | 24.47640 | -0.8175 | 19.72502 |
Annual Sum or Average | 8760.00000 | 21.06687 | 41.14671 | -0.9111 | 25.41140 |
Minimum of Months | 672.00000 | 20.32590 | 21.22411 | -1.3693 | 10.08061 |
Maximum of Months | 744.00000 | 21.69113 | 59.64903 | -0.4382 | 44.88515 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47935 | 21.31511 | -0.8818 | 22.05631 |
February | 672.00000 | 20.53105 | 25.51836 | -0.7917 | 19.46026 |
March | 744.00000 | 20.82939 | 32.07268 | -0.6196 | 14.07853 |
April | 720.00000 | 21.12543 | 39.44889 | -0.4197 | 10.41809 |
May | 744.00000 | 21.49250 | 52.60302 | -1.3278 | 42.80243 |
June | 720.00000 | 21.59161 | 57.32837 | -1.1844 | 36.21067 |
July | 744.00000 | 21.66685 | 59.58469 | -1.1063 | 32.56300 |
August | 744.00000 | 21.65456 | 59.79012 | -1.1338 | 33.79473 |
September | 720.00000 | 21.47699 | 49.66165 | -1.3405 | 43.93289 |
October | 744.00000 | 21.15971 | 39.38802 | -0.4346 | 9.80297 |
November | 720.00000 | 20.73821 | 34.03318 | -0.6603 | 15.36638 |
December | 744.00000 | 20.56626 | 24.53853 | -0.8245 | 19.99509 |
Annual Sum or Average | 8760.00000 | 21.11272 | 41.36092 | -0.8945 | 25.07017 |
Minimum of Months | 672.00000 | 20.47935 | 21.31511 | -1.3405 | 9.80297 |
Maximum of Months | 744.00000 | 21.66685 | 59.79012 | -0.4197 | 43.93289 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.40497 | 21.42213 | -0.9313 | 24.03999 |
February | 672.00000 | 20.33804 | 25.78392 | -0.8691 | 22.21675 |
March | 744.00000 | 20.66349 | 32.38985 | -0.6809 | 15.59279 |
April | 720.00000 | 21.00775 | 39.80136 | -0.4623 | 11.03029 |
May | 744.00000 | 21.44778 | 52.81024 | -1.3527 | 43.94088 |
June | 720.00000 | 21.58338 | 57.40154 | -1.1921 | 36.51695 |
July | 744.00000 | 21.66081 | 59.80734 | -1.1154 | 32.89376 |
August | 744.00000 | 21.63573 | 60.32149 | -1.1539 | 34.55794 |
September | 720.00000 | 21.38094 | 50.39257 | -1.4006 | 46.63153 |
October | 744.00000 | 20.88333 | 39.96813 | -0.5281 | 11.39621 |
November | 720.00000 | 20.60139 | 34.30609 | -0.7166 | 16.85885 |
December | 744.00000 | 20.47237 | 24.70331 | -0.8745 | 21.76075 |
Annual Sum or Average | 8760.00000 | 21.01066 | 41.67971 | -0.9403 | 26.47356 |
Minimum of Months | 672.00000 | 20.33804 | 21.42213 | -1.4006 | 11.03029 |
Maximum of Months | 744.00000 | 21.66081 | 60.32149 | -0.4623 | 46.63153 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85566 | 22.50540 | -0.6948 | 16.51030 |
February | 672.00000 | 20.91110 | 26.32044 | -0.6157 | 14.65787 |
March | 744.00000 | 21.17481 | 32.50502 | -0.4852 | 11.27262 |
April | 720.00000 | 21.25665 | 39.75893 | -0.3808 | 9.53175 |
May | 744.00000 | 21.52504 | 52.05194 | -1.3415 | 43.32357 |
June | 720.00000 | 21.59488 | 57.18616 | -1.2369 | 38.32929 |
July | 744.00000 | 21.64997 | 59.63221 | -1.1765 | 35.47441 |
August | 744.00000 | 21.65086 | 58.82858 | -1.1800 | 35.75063 |
September | 720.00000 | 21.56257 | 49.15986 | -1.3036 | 42.14118 |
October | 744.00000 | 21.42978 | 39.48008 | -0.3151 | 8.27271 |
November | 720.00000 | 21.08318 | 34.45044 | -0.5085 | 11.94824 |
December | 744.00000 | 20.94661 | 25.48546 | -0.6440 | 15.40737 |
Annual Sum or Average | 8760.00000 | 21.30587 | 41.53091 | -0.8249 | 23.60355 |
Minimum of Months | 672.00000 | 20.85566 | 22.50540 | -1.3415 | 8.27271 |
Maximum of Months | 744.00000 | 21.65086 | 59.63221 | -0.3151 | 43.32357 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.14323 | 23.04175 | -0.2241 | 10.38758 |
February | 672.00000 | 21.87128 | 26.11862 | -0.2456 | 16.12647 |
March | 744.00000 | 23.40975 | 31.88131 | 0.18303 | 6.41961 |
April | 720.00000 | 23.57594 | 37.81838 | 0.30195 | 7.41880 |
May | 744.00000 | 23.61867 | 49.17482 | -0.4651 | 10.04334 |
June | 720.00000 | 23.63992 | 55.12349 | -0.3726 | 8.36528 |
July | 744.00000 | 23.60121 | 57.84660 | -0.3533 | 8.10239 |
August | 744.00000 | 23.54535 | 57.29208 | -0.3892 | 8.74448 |
September | 720.00000 | 23.57177 | 47.82726 | -0.4931 | 10.79327 |
October | 744.00000 | 23.57385 | 37.14368 | 0.28875 | 7.08717 |
November | 720.00000 | 23.19128 | 33.20383 | 0.13377 | 7.03548 |
December | 744.00000 | 22.97309 | 26.52981 | -0.0033 | 6.07975 |
Annual Sum or Average | 8760.00000 | 23.23447 | 40.33074 | -0.1360 | 8.82937 |
Minimum of Months | 672.00000 | 21.87128 | 23.04175 | -0.4931 | 6.07975 |
Maximum of Months | 744.00000 | 23.63992 | 57.84660 | 0.30195 | 16.12647 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.38688 | 22.30054 | -0.1266 | 10.00231 |
February | 672.00000 | 22.06799 | 25.25380 | -0.1577 | 16.24552 |
March | 744.00000 | 23.61652 | 30.86282 | 0.27422 | 7.07950 |
April | 720.00000 | 23.73732 | 36.80198 | 0.38014 | 8.37959 |
May | 744.00000 | 23.75123 | 48.15968 | -0.3661 | 8.14843 |
June | 720.00000 | 23.74743 | 54.20551 | -0.2884 | 7.05008 |
July | 744.00000 | 23.70238 | 56.95031 | -0.2741 | 6.91453 |
August | 744.00000 | 23.65907 | 56.36308 | -0.3048 | 7.34972 |
September | 720.00000 | 23.69897 | 46.87783 | -0.3988 | 8.80316 |
October | 744.00000 | 23.73782 | 36.10798 | 0.36793 | 8.04659 |
November | 720.00000 | 23.40592 | 32.23594 | 0.22583 | 7.54694 |
December | 744.00000 | 23.24742 | 25.65282 | 0.10376 | 6.10918 |
Annual Sum or Average | 8760.00000 | 23.40475 | 39.39468 | -0.0464 | 8.41487 |
Minimum of Months | 672.00000 | 22.06799 | 22.30054 | -0.3988 | 6.10918 |
Maximum of Months | 744.00000 | 23.75123 | 56.95031 | 0.38014 | 16.24552 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.56249 | 22.19201 | 0.54648 | 24.21250 |
February | 672.00000 | 22.06567 | 25.97029 | 0.48807 | 30.00116 |
March | 744.00000 | 23.77296 | 29.50841 | 0.95881 | 27.62960 |
April | 720.00000 | 23.85432 | 35.66924 | 1.06620 | 31.89093 |
May | 744.00000 | 23.80875 | 47.10154 | 0.61593 | 19.15696 |
June | 720.00000 | 23.67938 | 53.30444 | 0.66318 | 21.06221 |
July | 744.00000 | 23.59703 | 56.02534 | 0.67054 | 21.63516 |
August | 744.00000 | 23.64002 | 55.29676 | 0.66030 | 20.88047 |
September | 720.00000 | 23.77885 | 45.84087 | 0.59250 | 19.10006 |
October | 744.00000 | 23.89548 | 34.95045 | 1.06179 | 31.51052 |
November | 720.00000 | 23.58462 | 31.06960 | 0.90600 | 27.35007 |
December | 744.00000 | 23.59112 | 24.21559 | 0.81123 | 22.27094 |
Annual Sum or Average | 8760.00000 | 23.49495 | 38.49777 | 0.75501 | 24.68031 |
Minimum of Months | 672.00000 | 22.06567 | 22.19201 | 0.48807 | 19.10006 |
Maximum of Months | 744.00000 | 23.89548 | 56.02534 | 1.06620 | 31.89093 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.294057E+09 | 9912.30 | 12-JAN-19:05 | 58.14 | 0.936994E+09 | 0.00 | 0.123105E+10 | 0.25 | 3.19 | 01-JAN-20:20 | 0.00 | 0.00 |
February | 0.727333E+09 | 11564.59 | 24-FEB-16:05 | 126.21 | 0.231760E+10 | 0.00 | 0.304493E+10 | 0.60 | 3.19 | 07-FEB-06:20 | 0.00 | 0.00 |
March | 0.399298E+10 | 63323.30 | 19-MAR-15:02 | 280.71 | 0.122944E+11 | 0.00 | 0.162874E+11 | 1.20 | 3.19 | 03-MAR-00:03 | 0.00 | 0.00 |
April | 0.295098E+11 | 137887.41 | 16-APR-15:03 | 454.30 | 0.941424E+11 | 0.00 | 0.123652E+12 | 2.00 | 3.96 | 18-APR-08:62 | 0.00 | 0.00 |
May | 0.702392E+11 | 135356.35 | 30-MAY-18:03 | 688.68 | 0.220102E+12 | 0.00 | 0.290341E+12 | 2.89 | 4.03 | 29-MAY-18:03 | 0.00 | 0.00 |
June | 0.162821E+12 | 194657.43 | 11-JUN-15:03 | 698.94 | 0.542949E+12 | 0.00 | 0.705770E+12 | 3.16 | 4.12 | 12-JUN-18:02 | 0.00 | 0.00 |
July | 0.220845E+12 | 202603.14 | 26-JUL-18:03 | 744.00 | 0.769809E+12 | 0.00 | 0.990654E+12 | 3.39 | 4.28 | 20-JUL-08:62 | 0.00 | 0.00 |
August | 0.195744E+12 | 210262.76 | 04-AUG-15:03 | 743.47 | 0.668932E+12 | 0.00 | 0.864676E+12 | 3.31 | 4.31 | 04-AUG-18:03 | 0.00 | 0.00 |
September | 0.920037E+11 | 159264.92 | 06-SEP-15:02 | 653.99 | 0.285366E+12 | 0.00 | 0.377370E+12 | 2.83 | 4.01 | 10-SEP-08:62 | 0.00 | 0.00 |
October | 0.134404E+11 | 92801.81 | 20-OCT-15:02 | 540.55 | 0.412059E+11 | 0.00 | 0.546463E+11 | 2.30 | 3.47 | 20-OCT-15:02 | 0.00 | 0.00 |
November | 0.339346E+10 | 45165.35 | 03-NOV-15:01 | 270.18 | 0.106815E+11 | 0.00 | 0.140750E+11 | 1.19 | 3.19 | 04-NOV-17:03 | 0.00 | 0.00 |
December | 0.676070E+09 | 9050.64 | 04-DEC-19:05 | 103.41 | 0.215425E+10 | 0.00 | 0.283032E+10 | 0.44 | 3.19 | 01-DEC-06:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.793686E+12 | 5362.59 | 0.265089E+13 | 0.344458E+13 | 1.97 | |||||||
Minimum of Months | 0.294057E+09 | 9050.64 | 58.14 | 0.936994E+09 | 0.00 | 0.123105E+10 | 0.25 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.220845E+12 | 210262.76 | 744.00 | 0.769809E+12 | 0.00 | 0.990654E+12 | 3.39 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.502741E+12 | 0.00 | 744.00 | 623266.92 | 31-JAN-04:00 | 0.00 | 50.49 | 59.78 | 4.66 | 0.00 | 0.30 | 0.99 | 31-JAN-04:00 |
February | 0.348485E+12 | 0.00 | 671.83 | 650832.44 | 02-FEB-06:02 | 0.00 | 51.05 | 59.41 | 3.58 | 0.00 | 0.23 | 1.04 | 02-FEB-06:02 |
March | 0.115273E+12 | 0.00 | 739.55 | 203037.01 | 05-MAR-19:02 | 0.00 | 50.63 | 58.76 | 1.25 | 0.00 | 0.07 | 0.32 | 05-MAR-19:02 |
April | 0.475902E+11 | 0.00 | 674.17 | 167922.36 | 03-APR-08:03 | 0.00 | 49.54 | 57.42 | 0.58 | 0.00 | 0.03 | 0.27 | 03-APR-08:03 |
May | 0.161715E+11 | 0.00 | 592.80 | 96588.77 | 09-MAY-15:05 | 0.00 | 45.06 | 54.69 | 0.15 | 0.00 | 0.01 | 0.15 | 09-MAY-15:05 |
June | 0.100347E+11 | 0.00 | 490.50 | 83809.69 | 06-JUN-15:07 | 0.00 | 42.98 | 52.40 | 0.08 | 0.00 | 0.01 | 0.13 | 06-JUN-15:07 |
July | 0.463651E+10 | 0.00 | 446.20 | 111406.49 | 10-JUL-15:05 | 0.00 | 42.10 | 51.07 | 0.03 | 0.00 | 0.00 | 0.18 | 10-JUL-15:05 |
August | 0.565692E+10 | 0.00 | 456.22 | 82709.78 | 30-AUG-15:05 | 0.00 | 42.17 | 51.35 | 0.04 | 0.00 | 0.00 | 0.13 | 30-AUG-15:05 |
September | 0.166649E+11 | 0.00 | 523.77 | 116447.36 | 27-SEP-15:02 | 0.00 | 45.61 | 53.67 | 0.18 | 0.00 | 0.01 | 0.19 | 27-SEP-15:02 |
October | 0.349938E+11 | 0.00 | 687.93 | 155604.26 | 26-OCT-15:02 | 0.00 | 50.53 | 57.23 | 0.47 | 0.00 | 0.02 | 0.25 | 26-OCT-15:02 |
November | 0.158308E+12 | 0.00 | 710.21 | 610610.15 | 26-NOV-07:00 | 0.00 | 50.42 | 58.58 | 1.68 | 0.00 | 0.10 | 0.97 | 26-NOV-07:00 |
December | 0.279866E+12 | 0.00 | 743.67 | 315326.01 | 09-DEC-09:06 | 0.00 | 50.60 | 59.68 | 2.75 | 0.00 | 0.17 | 0.50 | 09-DEC-09:06 |
Annual Sum or Average | 0.154042E+13 | 7480.83 | 47.57 | 56.15 | 1.27 | 0.00 | 0.08 | ||||||
Minimum of Months | 0.463651E+10 | 0.00 | 446.20 | 82709.78 | 0.00 | 42.10 | 51.07 | 0.03 | 0.00 | 0.00 | 0.13 | ||
Maximum of Months | 0.502741E+12 | 0.00 | 744.00 | 650832.44 | 0.00 | 51.05 | 59.78 | 4.66 | 0.00 | 0.30 | 1.04 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4000649.20 | 0.00 | 1.05 | 4000649.20 | 0.00 | 0.00 | 0.00 | 0.00 | 12308.88 | 12-JAN-16:02 | 12308.88 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 86855857.76 | 0.00 | 14.43 | 86855857.76 | 0.00 | 0.00 | 0.00 | 0.00 | 13291.44 | 24-FEB-16:02 | 13291.44 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.288729E+09 | 0.00 | 57.89 | 0.261555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13701.84 | 25-MAR-15:01 | 13701.84 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.174334E+10 | 0.00 | 211.55 | 0.127133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14886.46 | 16-APR-08:62 | 14048.36 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.275442E+10 | 0.00 | 421.64 | 0.168454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15594.40 | 29-MAY-08:62 | 14032.27 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.557001E+10 | 0.00 | 536.60 | 0.309554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18710.98 | 26-JUN-08:62 | 14186.40 | 25-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.718822E+10 | 0.00 | 636.81 | 0.387256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17905.10 | 14-JUL-18:02 | 14193.60 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.622088E+10 | 0.00 | 638.03 | 0.320581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20310.06 | 03-AUG-08:61 | 14165.84 | 22-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.365302E+10 | 0.00 | 431.24 | 0.222926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15827.65 | 11-SEP-08:62 | 14126.88 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.796054E+09 | 0.00 | 138.14 | 0.687280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13693.30 | 19-OCT-15:02 | 13693.30 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.147071E+09 | 0.00 | 26.93 | 0.138080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13359.58 | 03-NOV-15:01 | 13359.58 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 5254387.57 | 0.00 | 1.35 | 5254387.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12106.14 | 02-DEC-16:01 | 12106.14 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284579E+11 | 3115.66 | 0.165421E+11 | ||||||||||||
Minimum of Months | 4000649.20 | 0.00 | 1.05 | 4000649.20 | 0.00 | 0.00 | 0.00 | 0.00 | 12106.14 | 12106.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.718822E+10 | 0.00 | 638.03 | 0.387256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20310.06 | 14193.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 440133.03 | 0.00 | 0.06 | 440133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2734.97 | 12-JAN-16:03 | 2734.97 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 24302356.86 | 0.00 | 6.73 | 24302356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12236.62 | 24-FEB-16:02 | 12236.62 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.121922E+09 | 0.00 | 33.99 | 0.109677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13017.23 | 25-MAR-15:01 | 13017.23 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.135779E+10 | 0.00 | 176.10 | 0.975426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14567.00 | 16-APR-08:62 | 13809.96 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.248425E+10 | 0.00 | 396.53 | 0.151010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15339.07 | 29-MAY-08:62 | 13759.01 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.537951E+10 | 0.00 | 525.69 | 0.298714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18367.28 | 26-JUN-08:62 | 13938.43 | 27-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.685031E+10 | 0.00 | 618.64 | 0.368230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17807.35 | 17-JUL-18:02 | 13771.63 | 01-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.559460E+10 | 0.00 | 602.17 | 0.284458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20004.77 | 03-AUG-08:61 | 13927.55 | 02-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.278194E+10 | 0.00 | 362.66 | 0.162316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15251.09 | 11-SEP-08:62 | 13926.25 | 02-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.363637E+09 | 0.00 | 71.21 | 0.307709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12996.97 | 19-OCT-15:02 | 12996.97 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 55787330.07 | 0.00 | 7.66 | 53583938.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12793.34 | 03-NOV-15:01 | 12793.34 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 584420.21 | 0.00 | 0.13 | 584420.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.96 | 02-DEC-16:03 | 2409.96 | 02-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250151E+11 | 2801.57 | 0.141190E+11 | ||||||||||||
Minimum of Months | 440133.03 | 0.00 | 0.06 | 440133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.96 | 2409.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.685031E+10 | 0.00 | 618.64 | 0.368230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20004.77 | 13938.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.157163E+09 | 0.00 | 6.15 | 0.157163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12256.09 | 08-FEB-14:30 | 12256.09 | 08-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.627910E+09 | 0.00 | 20.24 | 0.627910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20588.48 | 24-MAR-13:30 | 20588.48 | 24-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.412507E+10 | 0.00 | 86.84 | 0.280850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38997.79 | 16-APR-18:10 | 28847.84 | 15-APR-12:40 | 0.00 | 0.00 | 0.00 |
May | 0.340836E+10 | 0.00 | 173.33 | 0.151890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25743.34 | 31-MAY-19:10 | 15612.50 | 31-MAY-18:30 | 0.00 | 0.00 | 0.00 |
June | 0.133196E+11 | 0.00 | 369.75 | 0.554283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37521.18 | 18-JUN-20:30 | 26434.33 | 18-JUN-20:30 | 0.00 | 0.00 | 0.00 |
July | 0.183253E+11 | 0.00 | 466.62 | 0.728842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43602.39 | 25-JUL-21:00 | 25916.80 | 25-JUL-19:30 | 0.00 | 0.00 | 0.00 |
August | 0.195270E+11 | 0.00 | 464.71 | 0.924785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36964.01 | 03-AUG-08:00 | 28209.80 | 29-AUG-12:50 | 0.00 | 0.00 | 0.00 |
September | 0.182032E+11 | 0.00 | 362.02 | 0.126332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43793.00 | 08-SEP-12:40 | 35986.59 | 08-SEP-12:50 | 0.00 | 0.00 | 0.00 |
October | 0.792349E+10 | 0.00 | 172.37 | 0.770125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44337.04 | 20-OCT-12:30 | 44337.04 | 20-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.265004E+10 | 0.00 | 45.56 | 0.260677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45388.82 | 04-NOV-12:30 | 45388.82 | 04-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.331333E+09 | 0.00 | 11.42 | 0.331333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16092.09 | 03-DEC-13:30 | 16092.09 | 03-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885985E+11 | 2178.99 | 0.504641E+11 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195270E+11 | 0.00 | 466.62 | 0.126332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45388.82 | 45388.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 11232190.47 | 0.00 | 0.39 | 11232190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20685.31 | 12-JAN-19:05 | 20685.31 | 12-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 50010604.94 | 0.00 | 4.73 | 50010604.94 | 0.00 | 0.00 | 0.00 | 0.00 | 21420.87 | 24-FEB-19:04 | 21420.87 | 24-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.183068E+10 | 0.00 | 111.19 | 0.137987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59535.45 | 28-MAR-18:02 | 59535.45 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.944381E+10 | 0.00 | 262.37 | 0.642165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76376.32 | 18-APR-18:02 | 66999.85 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.261028E+11 | 0.00 | 507.05 | 0.163495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77878.21 | 30-MAY-18:02 | 72157.57 | 05-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.423761E+11 | 0.00 | 509.79 | 0.259002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95462.38 | 26-JUN-08:62 | 68296.24 | 29-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.501629E+11 | 0.00 | 527.42 | 0.287970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93783.22 | 16-JUL-18:02 | 67199.83 | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.446886E+11 | 0.00 | 525.08 | 0.249138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105282.69 | 03-AUG-08:61 | 68107.80 | 09-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.235340E+11 | 0.00 | 464.04 | 0.148235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79415.06 | 11-SEP-18:02 | 67458.68 | 08-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.508903E+10 | 0.00 | 273.70 | 0.370283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61569.59 | 02-OCT-15:01 | 60305.17 | 22-OCT-08:63 | 0.00 | 0.00 | 0.00 |
November | 0.218729E+10 | 0.00 | 115.93 | 0.115464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57138.24 | 04-NOV-08:62 | 57138.24 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 15752579.24 | 0.00 | 0.56 | 15752579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20609.58 | 04-DEC-19:05 | 20609.58 | 04-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205492E+12 | 3302.26 | 0.123520E+12 | ||||||||||||
Minimum of Months | 11232190.47 | 0.00 | 0.39 | 11232190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20609.58 | 20609.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.501629E+11 | 0.00 | 527.42 | 0.287970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105282.69 | 72157.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1158793.51 | 0.00 | 0.31 | 1158793.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.69 | 09-JAN-09:05 | 1920.69 | 09-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 52153245.33 | 0.00 | 11.01 | 52153245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11084.14 | 24-FEB-09:02 | 11084.14 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.238904E+09 | 0.00 | 64.12 | 0.213494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11852.83 | 28-MAR-15:01 | 11852.83 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.140773E+10 | 0.00 | 208.53 | 0.964261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13690.86 | 18-APR-18:02 | 12562.30 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.298235E+10 | 0.00 | 464.71 | 0.183565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13869.63 | 30-MAY-15:02 | 12491.03 | 06-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.565721E+10 | 0.00 | 566.36 | 0.315744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15122.03 | 30-JUN-08:62 | 12483.42 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.695174E+10 | 0.00 | 669.42 | 0.367765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16006.23 | 14-JUL-18:02 | 12481.16 | 01-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.596270E+10 | 0.00 | 653.15 | 0.303140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16270.01 | 03-AUG-08:61 | 12583.37 | 09-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.365773E+10 | 0.00 | 447.45 | 0.223127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14070.39 | 11-SEP-18:02 | 12646.88 | 02-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.615570E+09 | 0.00 | 147.43 | 0.528570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12142.39 | 19-OCT-15:02 | 12142.39 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.101149E+09 | 0.00 | 29.83 | 97461308.44 | 0.00 | 0.00 | 0.00 | 0.00 | 11865.52 | 04-NOV-15:02 | 11865.52 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 9791331.76 | 0.00 | 3.49 | 9791331.76 | 0.00 | 0.00 | 0.00 | 0.00 | 3971.84 | 03-DEC-09:02 | 3971.84 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276382E+11 | 3265.80 | 0.158003E+11 | ||||||||||||
Minimum of Months | 1158793.51 | 0.00 | 0.31 | 1158793.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.69 | 1920.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.695174E+10 | 0.00 | 669.42 | 0.367765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16270.01 | 12646.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 182261.45 | 0.00 | 0.03 | 182261.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.61 | 12-JAN-09:05 | 1822.61 | 12-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 9765544.36 | 0.00 | 2.87 | 9765544.36 | 0.00 | 0.00 | 0.00 | 0.00 | 8355.03 | 24-FEB-09:02 | 8355.03 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 95980290.32 | 0.00 | 32.04 | 85585614.21 | 0.00 | 0.00 | 0.00 | 0.00 | 11154.91 | 28-MAR-08:62 | 11154.91 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.105410E+10 | 0.00 | 165.13 | 0.709567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13997.00 | 15-APR-15:02 | 12421.03 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.269330E+10 | 0.00 | 426.48 | 0.164063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13993.23 | 30-MAY-15:02 | 12414.34 | 06-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.545036E+10 | 0.00 | 559.89 | 0.304931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15022.94 | 30-JUN-08:62 | 12327.23 | 30-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.659154E+10 | 0.00 | 661.70 | 0.348994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15980.85 | 17-JUL-18:02 | 12380.44 | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.529576E+10 | 0.00 | 629.29 | 0.265107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225.75 | 03-AUG-08:61 | 12313.36 | 09-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.273434E+10 | 0.00 | 388.44 | 0.158078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13871.47 | 11-SEP-18:02 | 12437.59 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.171567E+09 | 0.00 | 61.38 | 0.142011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11035.58 | 20-OCT-08:62 | 11035.58 | 20-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 16245742.50 | 0.00 | 4.63 | 14062507.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4728.38 | 04-NOV-08:62 | 4728.38 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 292157.75 | 0.00 | 0.06 | 292157.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.80 | 03-DEC-09:03 | 2632.80 | 03-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241134E+11 | 2931.92 | 0.133732E+11 | ||||||||||||
Minimum of Months | 182261.45 | 0.00 | 0.03 | 182261.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.61 | 1822.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.659154E+10 | 0.00 | 661.70 | 0.348994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16225.75 | 12437.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 958541.21 | 0.00 | 0.80 | 958541.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.24 | 12-JAN-16:02 | 2680.24 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 22405495.00 | 0.00 | 11.90 | 22405495.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3454.06 | 24-FEB-16:02 | 3454.06 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 67839866.92 | 0.00 | 47.79 | 61986169.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.73 | 25-MAR-15:01 | 3560.73 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.492522E+09 | 0.00 | 204.60 | 0.368683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.29 | 16-APR-08:62 | 3630.98 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.810903E+09 | 0.00 | 414.93 | 0.517951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4183.35 | 29-MAY-08:62 | 3633.49 | 06-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.165382E+10 | 0.00 | 550.46 | 0.961745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4962.48 | 26-JUN-08:62 | 3660.06 | 13-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.212296E+10 | 0.00 | 660.26 | 0.119659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4703.99 | 14-JUL-18:02 | 3688.79 | 25-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.182186E+10 | 0.00 | 651.80 | 0.990685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5386.20 | 03-AUG-08:61 | 3677.08 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.104518E+10 | 0.00 | 414.16 | 0.676827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4232.96 | 11-SEP-08:62 | 3671.18 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.205898E+09 | 0.00 | 115.00 | 0.180885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3558.47 | 19-OCT-15:02 | 3558.47 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 38712532.52 | 0.00 | 20.27 | 36624401.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3471.80 | 03-NOV-15:01 | 3471.80 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1024931.04 | 0.00 | 0.72 | 1024931.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2257.31 | 02-DEC-16:01 | 2257.31 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828409E+10 | 3092.69 | 0.501637E+10 | ||||||||||||
Minimum of Months | 958541.21 | 0.00 | 0.72 | 958541.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2257.31 | 2257.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212296E+10 | 0.00 | 660.26 | 0.119659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5386.20 | 3688.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 48382.24 | 0.00 | 0.06 | 48382.24 | 0.00 | 0.00 | 0.00 | 0.00 | 357.82 | 13-JAN-16:05 | 357.82 | 13-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 3982731.81 | 0.00 | 5.17 | 3982731.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2664.61 | 24-FEB-16:02 | 2664.61 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 23240708.01 | 0.00 | 25.49 | 20756124.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3327.44 | 25-MAR-15:01 | 3327.44 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.381025E+09 | 0.00 | 167.72 | 0.279363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3880.90 | 16-APR-08:62 | 3599.46 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.731695E+09 | 0.00 | 384.93 | 0.465597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4110.32 | 29-MAY-08:62 | 3576.52 | 30-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.160091E+10 | 0.00 | 544.48 | 0.931600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4865.62 | 26-JUN-08:62 | 3604.20 | 13-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.202861E+10 | 0.00 | 651.69 | 0.114204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4654.30 | 17-JUL-18:02 | 3597.22 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.164562E+10 | 0.00 | 628.95 | 0.882966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5306.07 | 03-AUG-08:61 | 3614.26 | 22-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.802950E+09 | 0.00 | 354.24 | 0.495035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4094.54 | 11-SEP-08:62 | 3608.25 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 86607619.73 | 0.00 | 62.90 | 74435491.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3377.22 | 02-OCT-15:01 | 3336.40 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 14126791.97 | 0.00 | 7.09 | 13458419.07 | 0.00 | 0.00 | 0.00 | 0.00 | 3293.56 | 03-NOV-15:01 | 3293.56 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 38740.12 | 0.00 | 0.05 | 38740.12 | 0.00 | 0.00 | 0.00 | 0.00 | 294.48 | 01-DEC-16:05 | 294.48 | 01-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.731885E+10 | 2832.77 | 0.430932E+10 | ||||||||||||
Minimum of Months | 38740.12 | 0.00 | 0.05 | 38740.12 | 0.00 | 0.00 | 0.00 | 0.00 | 294.48 | 294.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.202861E+10 | 0.00 | 651.69 | 0.114204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5306.07 | 3614.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.370910E+09 | 0.00 | 41.22 | 0.370910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13137.48 | 12-JAN-16:02 | 13137.48 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.671901E+09 | 0.00 | 73.81 | 0.671901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13144.78 | 24-FEB-16:02 | 13144.78 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.109966E+10 | 0.00 | 158.73 | 0.997380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13550.74 | 25-MAR-15:01 | 13550.74 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.262191E+10 | 0.00 | 263.84 | 0.195312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15195.50 | 18-APR-18:02 | 13668.29 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.410307E+10 | 0.00 | 492.34 | 0.241988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15684.74 | 30-MAY-18:02 | 13872.99 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.741342E+10 | 0.00 | 564.65 | 0.425512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19489.95 | 26-JUN-08:62 | 13890.89 | 30-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.958236E+10 | 0.00 | 648.36 | 0.530385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18591.34 | 16-JUL-18:02 | 14024.25 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.949536E+10 | 0.00 | 650.72 | 0.538752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21068.98 | 03-AUG-08:61 | 13979.40 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.683910E+10 | 0.00 | 512.24 | 0.489748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16095.58 | 11-SEP-08:62 | 14025.93 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.339720E+10 | 0.00 | 328.36 | 0.310937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13680.47 | 02-OCT-15:01 | 13541.66 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.112578E+10 | 0.00 | 132.86 | 0.100295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13154.62 | 05-NOV-15:02 | 13154.62 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.816764E+09 | 0.00 | 78.97 | 0.816764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13141.49 | 02-DEC-16:01 | 13141.49 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475374E+11 | 3946.10 | 0.311862E+11 | ||||||||||||
Minimum of Months | 0.370910E+09 | 0.00 | 41.22 | 0.370910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13137.48 | 13137.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.958236E+10 | 0.00 | 650.72 | 0.538752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21068.98 | 14025.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 27129571.09 | 0.00 | 20.48 | 27129571.09 | 0.00 | 0.00 | 0.00 | 0.00 | 6725.74 | 13-JAN-18:05 | 6725.74 | 13-JAN-18:05 | 0.00 | 0.00 | 0.00 |
February | 0.101641E+09 | 0.00 | 71.40 | 0.101641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6846.93 | 09-FEB-18:05 | 6846.93 | 09-FEB-18:05 | 0.00 | 0.00 | 0.00 |
March | 0.486427E+10 | 0.00 | 143.35 | 0.486427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96123.92 | 19-MAR-16:00 | 96123.92 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.590194E+11 | 0.00 | 280.59 | 0.455761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 296408.13 | 16-APR-20:10 | 204458.92 | 15-APR-17:10 | 0.00 | 0.00 | 0.00 |
May | 0.147833E+12 | 0.00 | 471.79 | 0.109617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 306935.04 | 30-MAY-19:40 | 208929.96 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.390311E+12 | 0.00 | 584.01 | 0.251312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 386462.83 | 26-JUN-06:15 | 229136.29 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.568481E+12 | 0.00 | 714.22 | 0.322969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 503815.16 | 03-JUL-21:50 | 226552.63 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.489447E+12 | 0.00 | 681.24 | 0.286721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 491229.06 | 04-AUG-06:00 | 229339.43 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.189158E+12 | 0.00 | 475.69 | 0.159568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 324196.64 | 11-SEP-19:20 | 223737.61 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.158020E+11 | 0.00 | 295.78 | 0.158020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164847.71 | 20-OCT-15:10 | 164847.71 | 20-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.185314E+10 | 0.00 | 138.84 | 0.185314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43956.73 | 03-NOV-14:20 | 43956.73 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 41389678.57 | 0.00 | 31.71 | 41389678.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5645.20 | 02-DEC-18:05 | 5645.20 | 02-DEC-18:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186694E+13 | 3909.09 | 0.119845E+13 | ||||||||||||
Minimum of Months | 27129571.09 | 0.00 | 20.48 | 27129571.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5645.20 | 5645.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.568481E+12 | 0.00 | 714.22 | 0.322969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 503815.16 | 229339.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.508253E+09 | 0.00 | 24.50 | 0.508253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14383.07 | 19-MAR-16:00 | 14383.07 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.833358E+10 | 0.00 | 116.17 | 0.653687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43547.89 | 18-APR-17:10 | 31035.04 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.198488E+11 | 0.00 | 344.83 | 0.151178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54494.68 | 29-MAY-14:20 | 31318.71 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.574063E+11 | 0.00 | 535.00 | 0.377158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64103.73 | 12-JUN-14:00 | 33958.35 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.840494E+11 | 0.00 | 693.67 | 0.492205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66044.53 | 27-JUL-00:10 | 31809.46 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.718932E+11 | 0.00 | 646.00 | 0.430399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71073.16 | 03-AUG-08:61 | 34406.20 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.267999E+11 | 0.00 | 377.67 | 0.234662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48659.22 | 11-SEP-08:62 | 32493.13 | 06-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.189034E+10 | 0.00 | 63.50 | 0.189034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25764.86 | 20-OCT-15:00 | 25764.86 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 69741438.72 | 0.00 | 10.00 | 69741438.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.19 | 03-NOV-14:00 | 4334.19 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270799E+12 | 2811.33 | 0.177565E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.840494E+11 | 0.00 | 693.67 | 0.492205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71073.16 | 34406.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.80 | 591.77 | 272.03 | 701.06 | 954.58 | 0.00 | 0.00 | 744.00 |
February | 931.56 | 632.07 | 299.49 | 765.48 | 760.92 | 0.00 | 0.00 | 672.00 |
March | 798.14 | 417.95 | 380.19 | 622.23 | 564.73 | 0.00 | 0.00 | 744.00 |
April | 711.24 | 325.93 | 385.30 | 544.04 | 402.93 | 0.00 | 0.00 | 720.00 |
May | 606.52 | 169.60 | 436.93 | 488.83 | 211.56 | 0.00 | 0.00 | 744.00 |
June | 578.99 | 115.55 | 463.44 | 537.59 | 126.88 | 0.00 | 0.00 | 720.00 |
July | 614.42 | 153.58 | 460.84 | 593.74 | 99.61 | 0.00 | 0.00 | 744.00 |
August | 680.89 | 235.73 | 445.16 | 691.28 | 127.21 | 0.00 | 0.00 | 744.00 |
September | 822.35 | 424.41 | 397.94 | 824.03 | 248.37 | 0.00 | 0.00 | 720.00 |
October | 886.38 | 558.94 | 327.44 | 854.59 | 413.03 | 0.00 | 0.00 | 744.00 |
November | 663.13 | 415.16 | 247.97 | 560.10 | 620.65 | 0.00 | 0.00 | 720.00 |
December | 705.87 | 534.51 | 171.36 | 626.58 | 897.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.51 | 379.87 | 357.64 | 650.23 | 450.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 578.99 | 115.55 | 171.36 | 488.83 | 99.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 931.56 | 632.07 | 463.44 | 854.59 | 954.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2432.41 | 1666.38 | 766.03 | 1960.54 | 2709.22 | 0.00 | 0.00 | 744.00 |
February | 2623.21 | 1779.87 | 843.34 | 2138.08 | 2186.33 | 0.00 | 0.00 | 672.00 |
March | 2247.50 | 1176.92 | 1070.58 | 1729.15 | 1641.16 | 0.00 | 0.00 | 744.00 |
April | 2002.79 | 917.81 | 1084.99 | 1509.14 | 1200.06 | 0.00 | 0.00 | 720.00 |
May | 1707.93 | 477.58 | 1230.35 | 1338.44 | 663.81 | 0.00 | 0.00 | 744.00 |
June | 1630.40 | 325.37 | 1305.02 | 1477.67 | 411.31 | 0.00 | 0.00 | 720.00 |
July | 1730.18 | 432.47 | 1297.71 | 1637.88 | 325.15 | 0.00 | 0.00 | 744.00 |
August | 1917.35 | 663.80 | 1253.55 | 1916.37 | 412.19 | 0.00 | 0.00 | 744.00 |
September | 2315.69 | 1195.11 | 1120.58 | 2292.25 | 766.72 | 0.00 | 0.00 | 720.00 |
October | 2495.99 | 1573.95 | 922.04 | 2378.73 | 1241.38 | 0.00 | 0.00 | 744.00 |
November | 1867.32 | 1169.06 | 698.26 | 1558.02 | 1798.24 | 0.00 | 0.00 | 720.00 |
December | 1987.68 | 1505.14 | 482.54 | 1750.18 | 2552.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2076.78 | 1069.70 | 1007.08 | 1805.56 | 1321.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1630.40 | 325.37 | 482.54 | 1338.44 | 325.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2623.21 | 1779.87 | 1305.02 | 2378.73 | 2709.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3159.84 | 2164.73 | 995.12 | 2581.45 | 3657.33 | 0.00 | 0.00 | 744.00 |
February | 3407.69 | 2312.15 | 1095.55 | 2828.77 | 2940.12 | 0.00 | 0.00 | 672.00 |
March | 2919.63 | 1528.89 | 1390.74 | 2284.06 | 2237.08 | 0.00 | 0.00 | 744.00 |
April | 2601.74 | 1192.28 | 1409.46 | 2000.75 | 1639.96 | 0.00 | 0.00 | 720.00 |
May | 2218.70 | 620.40 | 1598.30 | 1768.13 | 903.53 | 0.00 | 0.00 | 744.00 |
June | 2117.98 | 422.68 | 1695.30 | 1967.90 | 555.42 | 0.00 | 0.00 | 720.00 |
July | 2247.60 | 561.80 | 1685.80 | 2185.95 | 432.21 | 0.00 | 0.00 | 744.00 |
August | 2490.75 | 862.31 | 1628.44 | 2553.46 | 545.89 | 0.00 | 0.00 | 744.00 |
September | 3008.21 | 1552.52 | 1455.69 | 3045.20 | 1029.99 | 0.00 | 0.00 | 720.00 |
October | 3242.43 | 2044.65 | 1197.78 | 3137.13 | 1685.54 | 0.00 | 0.00 | 744.00 |
November | 2425.76 | 1518.67 | 907.08 | 2046.07 | 2457.37 | 0.00 | 0.00 | 720.00 |
December | 2582.11 | 1955.26 | 626.85 | 2305.75 | 3465.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2697.86 | 1389.60 | 1308.26 | 2389.86 | 1790.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 2117.98 | 422.68 | 626.85 | 1768.13 | 432.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3407.69 | 2312.15 | 1695.30 | 3137.13 | 3657.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.64 | 202.77 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 148.36 | 163.88 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 122.58 | 118.07 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.74 | 83.82 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 95.40 | 43.62 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 106.44 | 24.90 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 117.43 | 18.84 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 137.64 | 24.06 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 165.09 | 48.51 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 169.95 | 83.60 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 110.62 | 129.03 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.85 | 186.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 128.38 | 93.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 95.40 | 18.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 169.95 | 202.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 31.57 | 436.94 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 76.74 | 347.58 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 109.80 | 226.38 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 242.87 | 152.46 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 274.63 | 78.65 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 368.71 | 45.58 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 410.46 | 34.78 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 358.10 | 44.47 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 259.88 | 89.81 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 129.73 | 161.89 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 45.19 | 266.34 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 27.48 | 390.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 195.19 | 188.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 27.48 | 34.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 410.46 | 436.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.47 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.49 | 200.23 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 10.21 | 128.35 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 26.06 | 84.12 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 57.55 | 40.53 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 88.59 | 22.89 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 88.52 | 17.56 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 77.13 | 22.76 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 46.26 | 48.62 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.95 | 88.97 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 3.02 | 148.49 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 34.52 | 105.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 88.59 | 248.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 32.89 | 432.71 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 79.40 | 342.68 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 113.51 | 223.75 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 245.79 | 151.16 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 276.14 | 78.15 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 369.42 | 45.31 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 411.38 | 34.52 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 359.83 | 44.02 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 263.31 | 88.66 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 134.94 | 159.22 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 47.68 | 263.27 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 29.13 | 386.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 197.54 | 186.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 29.13 | 34.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 411.38 | 432.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.33 | 93.39 | 42.93 | 108.73 | 158.02 | 0.00 | 0.00 | 744.00 |
February | 147.02 | 99.75 | 47.27 | 118.19 | 129.14 | 0.00 | 0.00 | 672.00 |
March | 125.96 | 65.96 | 60.00 | 97.53 | 93.43 | 0.00 | 0.00 | 744.00 |
April | 112.25 | 51.44 | 60.81 | 86.41 | 67.63 | 0.00 | 0.00 | 720.00 |
May | 95.72 | 26.77 | 68.96 | 74.01 | 39.75 | 0.00 | 0.00 | 744.00 |
June | 91.38 | 18.24 | 73.14 | 82.80 | 24.81 | 0.00 | 0.00 | 720.00 |
July | 96.97 | 24.24 | 72.73 | 91.79 | 19.61 | 0.00 | 0.00 | 744.00 |
August | 107.46 | 37.20 | 70.26 | 107.71 | 24.67 | 0.00 | 0.00 | 744.00 |
September | 129.78 | 66.98 | 62.80 | 129.53 | 45.36 | 0.00 | 0.00 | 720.00 |
October | 139.89 | 88.21 | 51.68 | 132.71 | 73.92 | 0.00 | 0.00 | 744.00 |
November | 104.65 | 65.52 | 39.13 | 87.10 | 104.07 | 0.00 | 0.00 | 720.00 |
December | 111.40 | 84.36 | 27.04 | 98.31 | 146.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.39 | 59.95 | 56.44 | 101.15 | 76.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 91.38 | 18.24 | 27.04 | 74.01 | 19.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 147.02 | 99.75 | 73.14 | 132.71 | 158.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.86 | 0.00 | 21.86 | 0.00 | 203.97 | 0.00 | 0.00 | 744.00 |
February | 27.72 | 0.00 | 27.72 | 0.29 | 163.32 | 0.00 | 0.00 | 672.00 |
March | 41.55 | 0.00 | 41.55 | 7.82 | 105.42 | 0.00 | 0.00 | 744.00 |
April | 48.15 | 0.39 | 47.76 | 21.85 | 68.20 | 0.00 | 0.00 | 720.00 |
May | 62.60 | 2.37 | 60.24 | 48.13 | 32.39 | 0.00 | 0.00 | 744.00 |
June | 73.26 | 6.78 | 66.48 | 74.30 | 17.91 | 0.00 | 0.00 | 720.00 |
July | 68.71 | 4.73 | 63.98 | 74.96 | 13.16 | 0.00 | 0.00 | 744.00 |
August | 57.57 | 1.16 | 56.41 | 65.41 | 17.47 | 0.00 | 0.00 | 744.00 |
September | 44.06 | 0.04 | 44.02 | 39.00 | 38.81 | 0.00 | 0.00 | 720.00 |
October | 32.72 | 0.00 | 32.72 | 10.95 | 72.67 | 0.00 | 0.00 | 744.00 |
November | 22.89 | 0.00 | 22.89 | 2.21 | 122.97 | 0.00 | 0.00 | 720.00 |
December | 14.85 | 0.00 | 14.85 | 0.00 | 179.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.08 | 1.29 | 41.78 | 28.92 | 85.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.85 | 0.00 | 14.85 | 0.00 | 13.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.26 | 6.78 | 66.48 | 74.96 | 203.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 25.94 | 430.11 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 56.78 | 340.16 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 113.67 | 220.24 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 194.65 | 148.10 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 300.47 | 73.82 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.57 | 42.91 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 392.42 | 32.36 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 329.68 | 41.34 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 265.35 | 86.90 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 109.39 | 156.00 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 31.85 | 261.30 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.52 | 386.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 185.05 | 184.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.52 | 32.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 392.42 | 430.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.43 | 202.50 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 148.08 | 163.13 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 121.64 | 117.82 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.22 | 82.96 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 93.95 | 43.59 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 105.45 | 24.70 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 116.67 | 18.39 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 137.12 | 23.68 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 164.07 | 48.18 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 169.37 | 83.22 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 110.51 | 128.78 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.79 | 186.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 127.76 | 93.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 93.95 | 18.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 169.37 | 202.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.30 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.40 | 199.56 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 9.80 | 128.58 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.69 | 83.41 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 56.12 | 40.59 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 87.59 | 22.70 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 87.73 | 17.12 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 76.56 | 22.43 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 45.20 | 48.49 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.56 | 88.71 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.95 | 148.27 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 34.00 | 105.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 87.73 | 248.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 26.55 | 425.17 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 58.24 | 333.95 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 116.69 | 216.88 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 197.37 | 146.58 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 301.86 | 73.32 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 375.28 | 42.70 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 393.28 | 32.14 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 331.19 | 40.90 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 268.35 | 85.70 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 114.06 | 152.74 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 33.49 | 257.34 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.96 | 381.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 186.89 | 181.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.96 | 32.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 393.28 | 425.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.00 | 321.45 | 0.00 | 0.00 | 744.00 |
February | 43.87 | 0.00 | 43.87 | 0.39 | 253.73 | 0.00 | 0.00 | 672.00 |
March | 65.76 | 0.00 | 65.76 | 12.41 | 165.64 | 0.00 | 0.00 | 744.00 |
April | 76.21 | 0.61 | 75.60 | 35.19 | 106.36 | 0.00 | 0.00 | 720.00 |
May | 99.09 | 3.74 | 95.34 | 79.02 | 49.85 | 0.00 | 0.00 | 744.00 |
June | 115.95 | 10.73 | 105.22 | 120.34 | 27.67 | 0.00 | 0.00 | 720.00 |
July | 108.76 | 7.49 | 101.27 | 120.99 | 20.68 | 0.00 | 0.00 | 744.00 |
August | 91.13 | 1.84 | 89.29 | 105.50 | 27.37 | 0.00 | 0.00 | 744.00 |
September | 69.74 | 0.06 | 69.68 | 62.60 | 60.65 | 0.00 | 0.00 | 720.00 |
October | 51.79 | 0.00 | 51.79 | 17.42 | 113.56 | 0.00 | 0.00 | 744.00 |
November | 36.23 | 0.00 | 36.23 | 3.51 | 193.82 | 0.00 | 0.00 | 720.00 |
December | 23.50 | 0.00 | 23.50 | 0.00 | 284.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.18 | 2.05 | 66.13 | 46.73 | 134.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.50 | 0.00 | 23.50 | 0.00 | 20.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 115.95 | 10.73 | 105.22 | 120.99 | 321.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.00 | 118.50 | 0.00 | 0.00 | 744.00 |
February | 16.17 | 0.00 | 16.17 | 0.15 | 93.54 | 0.00 | 0.00 | 672.00 |
March | 24.24 | 0.00 | 24.24 | 4.58 | 61.06 | 0.00 | 0.00 | 744.00 |
April | 28.10 | 0.23 | 27.87 | 12.97 | 39.21 | 0.00 | 0.00 | 720.00 |
May | 36.53 | 1.38 | 35.15 | 29.13 | 18.38 | 0.00 | 0.00 | 744.00 |
June | 42.74 | 3.96 | 38.79 | 44.36 | 10.20 | 0.00 | 0.00 | 720.00 |
July | 40.09 | 2.76 | 37.33 | 44.60 | 7.63 | 0.00 | 0.00 | 744.00 |
August | 33.59 | 0.68 | 32.92 | 38.89 | 10.09 | 0.00 | 0.00 | 744.00 |
September | 25.71 | 0.02 | 25.69 | 23.08 | 22.36 | 0.00 | 0.00 | 720.00 |
October | 19.09 | 0.00 | 19.09 | 6.42 | 41.86 | 0.00 | 0.00 | 744.00 |
November | 13.35 | 0.00 | 13.35 | 1.29 | 71.45 | 0.00 | 0.00 | 720.00 |
December | 8.66 | 0.00 | 8.66 | 0.00 | 104.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.13 | 0.75 | 24.38 | 17.23 | 49.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.66 | 0.00 | 8.66 | 0.00 | 7.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 42.74 | 3.96 | 38.79 | 44.60 | 118.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.53 | 54.48 | 25.05 | 63.77 | 95.35 | 0.00 | 0.00 | 744.00 |
February | 85.76 | 58.19 | 27.57 | 70.25 | 75.52 | 0.00 | 0.00 | 672.00 |
March | 73.48 | 38.48 | 35.00 | 57.74 | 55.35 | 0.00 | 0.00 | 744.00 |
April | 65.48 | 30.01 | 35.47 | 51.76 | 38.66 | 0.00 | 0.00 | 720.00 |
May | 55.84 | 15.61 | 40.23 | 47.03 | 19.48 | 0.00 | 0.00 | 744.00 |
June | 53.31 | 10.64 | 42.67 | 52.78 | 10.93 | 0.00 | 0.00 | 720.00 |
July | 56.57 | 14.14 | 42.43 | 58.25 | 8.04 | 0.00 | 0.00 | 744.00 |
August | 62.69 | 21.70 | 40.98 | 67.46 | 10.45 | 0.00 | 0.00 | 744.00 |
September | 75.71 | 39.07 | 36.64 | 79.31 | 21.95 | 0.00 | 0.00 | 720.00 |
October | 81.61 | 51.46 | 30.15 | 80.62 | 38.67 | 0.00 | 0.00 | 744.00 |
November | 61.05 | 38.22 | 22.83 | 51.84 | 61.04 | 0.00 | 0.00 | 720.00 |
December | 64.99 | 49.21 | 15.78 | 57.83 | 88.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.90 | 34.97 | 32.93 | 61.51 | 43.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.31 | 10.64 | 15.78 | 47.03 | 8.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.76 | 58.19 | 42.67 | 80.62 | 95.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.85 | 147.87 | 67.98 | 173.09 | 258.79 | 0.00 | 0.00 | 744.00 |
February | 232.78 | 157.95 | 74.84 | 190.68 | 204.98 | 0.00 | 0.00 | 672.00 |
March | 199.44 | 104.44 | 95.00 | 156.73 | 150.24 | 0.00 | 0.00 | 744.00 |
April | 177.73 | 81.45 | 96.28 | 140.50 | 104.93 | 0.00 | 0.00 | 720.00 |
May | 151.56 | 42.38 | 109.18 | 127.66 | 52.87 | 0.00 | 0.00 | 744.00 |
June | 144.68 | 28.87 | 115.81 | 143.26 | 29.67 | 0.00 | 0.00 | 720.00 |
July | 153.54 | 38.38 | 115.16 | 158.10 | 21.83 | 0.00 | 0.00 | 744.00 |
August | 170.15 | 58.91 | 111.24 | 183.10 | 28.37 | 0.00 | 0.00 | 744.00 |
September | 205.49 | 106.05 | 99.44 | 215.27 | 59.57 | 0.00 | 0.00 | 720.00 |
October | 221.49 | 139.67 | 81.82 | 218.81 | 104.97 | 0.00 | 0.00 | 744.00 |
November | 165.71 | 103.74 | 61.96 | 140.72 | 165.66 | 0.00 | 0.00 | 720.00 |
December | 176.39 | 133.57 | 42.82 | 156.96 | 241.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.29 | 94.93 | 89.37 | 166.96 | 118.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 144.68 | 28.87 | 42.82 | 127.66 | 21.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 232.78 | 157.95 | 115.81 | 218.81 | 258.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 136.06 | 203.41 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 147.69 | 164.50 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 122.44 | 118.20 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 107.42 | 83.92 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 94.43 | 43.93 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 105.47 | 25.07 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 116.35 | 19.00 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 136.65 | 24.31 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 164.52 | 48.50 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 169.61 | 83.48 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 110.42 | 129.11 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 123.65 | 187.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 127.80 | 93.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 94.43 | 19.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 169.61 | 203.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 31.40 | 438.97 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 76.18 | 349.79 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 109.56 | 226.67 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 241.43 | 152.58 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 271.95 | 79.08 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 365.93 | 45.83 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 407.44 | 35.03 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 355.38 | 44.86 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 258.44 | 89.79 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 129.35 | 161.59 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 45.35 | 266.32 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 27.59 | 391.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 193.92 | 189.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 27.59 | 35.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 407.44 | 438.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 249.31 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.50 | 201.08 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 10.35 | 128.37 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 25.77 | 84.20 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 56.32 | 40.77 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 87.25 | 23.04 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 87.11 | 17.70 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 75.83 | 22.96 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 45.73 | 48.54 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 14.24 | 88.50 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 3.14 | 148.16 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 217.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 34.05 | 105.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 17.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 87.25 | 249.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 32.70 | 434.63 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 78.96 | 344.75 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 113.33 | 224.08 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 244.54 | 151.19 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 273.47 | 78.55 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 366.58 | 45.56 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 408.26 | 34.77 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 356.94 | 44.40 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 261.94 | 88.56 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 135.14 | 158.66 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 47.96 | 263.26 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 29.20 | 387.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 196.33 | 187.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 29.20 | 34.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 408.26 | 434.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.17 | 171.39 | 78.79 | 192.42 | 305.26 | 0.00 | 0.00 | 744.00 |
February | 269.80 | 183.06 | 86.74 | 210.09 | 247.79 | 0.00 | 0.00 | 672.00 |
March | 231.15 | 121.05 | 110.11 | 174.22 | 177.53 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 94.40 | 111.59 | 156.33 | 123.89 | 0.00 | 0.00 | 720.00 |
May | 175.66 | 49.12 | 126.54 | 139.39 | 63.86 | 0.00 | 0.00 | 744.00 |
June | 167.69 | 33.46 | 134.22 | 157.91 | 35.80 | 0.00 | 0.00 | 720.00 |
July | 177.95 | 44.48 | 133.47 | 174.51 | 26.38 | 0.00 | 0.00 | 744.00 |
August | 197.20 | 68.27 | 128.93 | 202.72 | 34.61 | 0.00 | 0.00 | 744.00 |
September | 238.17 | 122.92 | 115.25 | 240.30 | 71.62 | 0.00 | 0.00 | 720.00 |
October | 256.71 | 161.88 | 94.83 | 243.79 | 126.04 | 0.00 | 0.00 | 744.00 |
November | 192.05 | 120.24 | 71.82 | 156.84 | 195.33 | 0.00 | 0.00 | 720.00 |
December | 204.43 | 154.80 | 49.63 | 175.18 | 281.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.60 | 110.02 | 103.58 | 185.19 | 140.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 167.69 | 33.46 | 49.63 | 139.39 | 26.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 269.80 | 183.06 | 134.22 | 243.79 | 305.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1847.78 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.69 | 1484.05 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 49.65 | 1027.34 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 159.60 | 690.40 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 368.55 | 347.53 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 588.06 | 210.98 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 594.10 | 166.17 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 518.64 | 211.58 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 302.29 | 414.50 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 70.04 | 732.66 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 11.76 | 1179.00 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1676.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 223.29 | 829.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 166.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 594.10 | 1847.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1882.79 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.38 | 1516.51 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 44.39 | 1056.46 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 150.89 | 711.86 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 353.54 | 359.40 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 573.57 | 219.64 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 579.92 | 173.66 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 504.98 | 220.80 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 291.41 | 429.07 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 62.71 | 755.68 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 9.73 | 1210.96 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1715.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 215.59 | 851.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 173.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 579.92 | 1882.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 238.45 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.65 | 187.49 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 12.32 | 129.86 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 33.41 | 85.68 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 73.07 | 44.33 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 108.75 | 26.71 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 110.85 | 20.19 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 97.69 | 25.55 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 60.15 | 50.28 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 18.39 | 89.53 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 4.54 | 147.24 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 216.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 43.58 | 104.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 20.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 110.85 | 238.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 218.23 | 89.44 | 128.79 | 61.16 | 823.40 | 0.00 | 0.00 | 744.00 |
February | 290.57 | 127.90 | 162.68 | 128.18 | 633.96 | 0.00 | 0.00 | 672.00 |
March | 394.65 | 156.59 | 238.06 | 249.05 | 446.00 | 0.00 | 0.00 | 744.00 |
April | 481.67 | 209.93 | 271.73 | 428.01 | 307.91 | 0.00 | 0.00 | 720.00 |
May | 608.53 | 266.12 | 342.41 | 667.98 | 163.20 | 0.00 | 0.00 | 744.00 |
June | 668.73 | 291.27 | 377.46 | 828.82 | 100.93 | 0.00 | 0.00 | 720.00 |
July | 676.06 | 312.03 | 364.04 | 872.82 | 76.54 | 0.00 | 0.00 | 744.00 |
August | 570.03 | 245.65 | 324.38 | 741.72 | 95.68 | 0.00 | 0.00 | 744.00 |
September | 510.75 | 242.25 | 268.49 | 596.75 | 182.49 | 0.00 | 0.00 | 720.00 |
October | 323.41 | 134.61 | 188.80 | 252.95 | 315.32 | 0.00 | 0.00 | 744.00 |
November | 191.31 | 62.09 | 129.22 | 76.49 | 517.41 | 0.00 | 0.00 | 720.00 |
December | 147.64 | 63.22 | 84.42 | 38.36 | 761.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 424.12 | 183.68 | 240.44 | 413.42 | 367.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 147.64 | 62.09 | 84.42 | 38.36 | 76.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 676.06 | 312.03 | 377.46 | 872.82 | 823.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 141.89 | 195.27 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 156.52 | 155.03 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 128.10 | 119.54 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 116.84 | 85.17 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 110.88 | 46.77 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 126.14 | 28.50 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 139.55 | 21.25 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 158.21 | 26.60 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 181.07 | 50.03 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 179.93 | 85.07 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 115.84 | 129.04 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 127.43 | 185.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 140.12 | 93.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 110.88 | 21.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 181.07 | 195.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.63 | 0.00 | 34.63 | 0.00 | 324.40 | 0.00 | 0.00 | 744.00 |
February | 43.91 | 0.00 | 43.91 | 0.25 | 254.40 | 0.00 | 0.00 | 672.00 |
March | 65.82 | 0.00 | 65.82 | 11.07 | 169.70 | 0.00 | 0.00 | 744.00 |
April | 76.28 | 0.61 | 75.66 | 32.00 | 110.73 | 0.00 | 0.00 | 720.00 |
May | 99.17 | 3.75 | 95.42 | 72.72 | 54.24 | 0.00 | 0.00 | 744.00 |
June | 116.05 | 10.74 | 105.31 | 110.78 | 32.75 | 0.00 | 0.00 | 720.00 |
July | 108.85 | 7.49 | 101.35 | 110.82 | 26.04 | 0.00 | 0.00 | 744.00 |
August | 91.20 | 1.84 | 89.37 | 96.61 | 33.00 | 0.00 | 0.00 | 744.00 |
September | 69.80 | 0.06 | 69.74 | 57.15 | 65.79 | 0.00 | 0.00 | 720.00 |
October | 51.83 | 0.00 | 51.83 | 15.22 | 117.64 | 0.00 | 0.00 | 744.00 |
November | 36.26 | 0.00 | 36.26 | 2.90 | 197.85 | 0.00 | 0.00 | 720.00 |
December | 23.52 | 0.00 | 23.52 | 0.00 | 289.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.24 | 2.05 | 66.19 | 42.72 | 139.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 0.00 | 26.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.05 | 10.74 | 105.31 | 110.82 | 324.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.99 | 0.00 | 30.99 | 0.00 | 290.24 | 0.00 | 0.00 | 744.00 |
February | 39.29 | 0.00 | 39.29 | 0.23 | 227.61 | 0.00 | 0.00 | 672.00 |
March | 58.89 | 0.00 | 58.89 | 9.90 | 151.83 | 0.00 | 0.00 | 744.00 |
April | 68.24 | 0.55 | 67.70 | 28.63 | 99.07 | 0.00 | 0.00 | 720.00 |
May | 88.73 | 3.35 | 85.38 | 65.06 | 48.53 | 0.00 | 0.00 | 744.00 |
June | 103.83 | 9.61 | 94.22 | 99.12 | 29.30 | 0.00 | 0.00 | 720.00 |
July | 97.38 | 6.70 | 90.68 | 99.15 | 23.30 | 0.00 | 0.00 | 744.00 |
August | 81.60 | 1.64 | 79.96 | 86.44 | 29.53 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 0.06 | 62.39 | 51.14 | 58.86 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 0.00 | 46.37 | 13.61 | 105.25 | 0.00 | 0.00 | 744.00 |
November | 32.44 | 0.00 | 32.44 | 2.60 | 177.02 | 0.00 | 0.00 | 720.00 |
December | 21.04 | 0.00 | 21.04 | 0.00 | 258.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.05 | 1.83 | 59.22 | 38.22 | 124.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.00 | 23.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.83 | 9.61 | 94.22 | 99.15 | 290.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.83 | 436.27 | 200.55 | 505.28 | 768.90 | 0.00 | 0.00 | 744.00 |
February | 686.78 | 465.98 | 220.79 | 558.40 | 605.43 | 0.00 | 0.00 | 672.00 |
March | 588.42 | 308.13 | 280.29 | 454.04 | 453.04 | 0.00 | 0.00 | 744.00 |
April | 524.35 | 240.29 | 284.06 | 404.13 | 322.19 | 0.00 | 0.00 | 720.00 |
May | 447.15 | 125.03 | 322.12 | 358.92 | 170.23 | 0.00 | 0.00 | 744.00 |
June | 426.85 | 85.19 | 341.67 | 396.02 | 104.20 | 0.00 | 0.00 | 720.00 |
July | 452.98 | 113.22 | 339.75 | 437.68 | 81.69 | 0.00 | 0.00 | 744.00 |
August | 501.98 | 173.79 | 328.19 | 514.51 | 101.46 | 0.00 | 0.00 | 744.00 |
September | 606.27 | 312.89 | 293.38 | 617.77 | 191.02 | 0.00 | 0.00 | 720.00 |
October | 653.47 | 412.07 | 241.40 | 634.25 | 319.97 | 0.00 | 0.00 | 744.00 |
November | 488.88 | 306.07 | 182.81 | 408.19 | 498.84 | 0.00 | 0.00 | 720.00 |
December | 520.39 | 394.06 | 126.33 | 457.45 | 720.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.72 | 280.06 | 263.66 | 478.48 | 360.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 426.85 | 85.19 | 126.33 | 358.92 | 81.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 686.78 | 465.98 | 341.67 | 634.25 | 768.90 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.187771E+10 | 0.255674E+10 |
February | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.185185E+10 | 0.184082E+10 |
March | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.166659E+10 | 0.151259E+10 |
April | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.141014E+10 | 0.104440E+10 |
May | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.130929E+10 | 0.566635E+09 |
June | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.139343E+10 | 0.328863E+09 |
July | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.159028E+10 | 0.266786E+09 |
August | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.185153E+10 | 0.340728E+09 |
September | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.213589E+10 | 0.643780E+09 |
October | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.228894E+10 | 0.110625E+10 |
November | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.145177E+10 | 0.160873E+10 |
December | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.167824E+10 | 0.240378E+10 |
Annual Sum or Average | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.205057E+11 | 0.142201E+11 |
Minimum of Months | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.130929E+10 | 0.266786E+09 |
Maximum of Months | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.228894E+10 | 0.255674E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.525110E+10 | 0.725639E+10 |
February | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.517244E+10 | 0.528916E+10 |
March | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.463136E+10 | 0.439569E+10 |
April | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.391170E+10 | 0.311056E+10 |
May | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.358488E+10 | 0.177794E+10 |
June | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.383012E+10 | 0.106611E+10 |
July | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.438689E+10 | 0.870883E+09 |
August | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.513280E+10 | 0.110401E+10 |
September | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.594152E+10 | 0.198734E+10 |
October | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.637120E+10 | 0.332490E+10 |
November | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.403839E+10 | 0.466103E+10 |
December | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.468769E+10 | 0.683643E+10 |
Annual Sum or Average | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.569401E+11 | 0.416804E+11 |
Minimum of Months | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.358488E+10 | 0.870883E+09 |
Maximum of Months | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.637120E+10 | 0.725639E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.691416E+10 | 0.979580E+10 |
February | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.684335E+10 | 0.711274E+10 |
March | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.611763E+10 | 0.599180E+10 |
April | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.518595E+10 | 0.425078E+10 |
May | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.473577E+10 | 0.242002E+10 |
June | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.510079E+10 | 0.143965E+10 |
July | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.585485E+10 | 0.115762E+10 |
August | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.683918E+10 | 0.146211E+10 |
September | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.789317E+10 | 0.266973E+10 |
October | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.840249E+10 | 0.451455E+10 |
November | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.530341E+10 | 0.636950E+10 |
December | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.617573E+10 | 0.928290E+10 |
Annual Sum or Average | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.753665E+11 | 0.564672E+11 |
Minimum of Months | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.473577E+10 | 0.115762E+10 |
Maximum of Months | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.840249E+10 | 0.979580E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.365982E+09 | 0.543097E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.358923E+09 | 0.396452E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.328311E+09 | 0.316240E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.279268E+09 | 0.217269E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.255522E+09 | 0.116818E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.275900E+09 | 64536025.57 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.314523E+09 | 50454797.08 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.368644E+09 | 64443339.81 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.427914E+09 | 0.125733E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.455185E+09 | 0.223906E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.286738E+09 | 0.334435E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.331720E+09 | 0.500094E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.404863E+10 | 0.295348E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.255522E+09 | 50454797.08 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.455185E+09 | 0.543097E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 84567520.86 | 0.117031E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.185643E+09 | 0.840875E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.294076E+09 | 0.606326E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.629512E+09 | 0.395165E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.735563E+09 | 0.210659E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.955705E+09 | 0.118150E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109937E+10 | 93165406.85 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.959148E+09 | 0.119118E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.673601E+09 | 0.232792E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.347472E+09 | 0.433613E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.117131E+09 | 0.690360E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 73605979.11 | 0.104713E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.615539E+10 | 0.595767E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 73605979.11 | 93165406.85 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109937E+10 | 0.117031E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 9602.00 | 0.665498E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 1175697.55 | 0.484399E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 27338172.41 | 0.343765E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 67541355.76 | 0.218034E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.154144E+09 | 0.108569E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.229624E+09 | 59324484.13 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.237094E+09 | 47040101.96 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.206577E+09 | 60963455.07 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.119903E+09 | 0.126020E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 37375198.62 | 0.238301E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7823919.68 | 0.384899E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.582207E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.108860E+10 | 0.331902E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 47040101.96 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.237094E+09 | 0.665498E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 88094326.26 | 0.115897E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.192082E+09 | 0.829004E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.304014E+09 | 0.599293E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.637091E+09 | 0.391801E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.739610E+09 | 0.209315E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.957540E+09 | 0.117448E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.110183E+10 | 92449625.34 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.963756E+09 | 0.117893E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.682511E+09 | 0.229815E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.361429E+09 | 0.426468E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.123583E+09 | 0.682398E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 78011930.42 | 0.103611E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.622955E+10 | 0.589097E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 78011930.42 | 92449625.34 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.110183E+10 | 0.115897E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.291224E+09 | 0.423244E+09 |
February | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.285932E+09 | 0.312416E+09 |
March | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.261227E+09 | 0.250254E+09 |
April | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.223974E+09 | 0.175289E+09 |
May | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.198225E+09 | 0.106479E+09 |
June | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.214611E+09 | 64306425.70 |
July | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.245846E+09 | 52519944.36 |
August | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.288495E+09 | 66078913.69 |
September | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.335743E+09 | 0.117573E+09 |
October | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.355442E+09 | 0.197998E+09 |
November | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.225773E+09 | 0.269759E+09 |
December | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.263303E+09 | 0.392023E+09 |
Annual Sum or Average | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.318979E+10 | 0.242794E+10 |
Minimum of Months | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.198225E+09 | 52519944.36 |
Maximum of Months | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.355442E+09 | 0.423244E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.546306E+09 |
February | 67056690.67 | 0.00 | 67056690.67 | 707064.40 | 0.395094E+09 |
March | 0.111280E+09 | 941.15 | 0.111279E+09 | 20942885.02 | 0.282354E+09 |
April | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 56630984.75 | 0.176781E+09 |
May | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.128904E+09 | 86742506.09 |
June | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.192579E+09 | 46420051.68 |
July | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.200774E+09 | 35260932.68 |
August | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.175198E+09 | 46788706.31 |
September | 0.114208E+09 | 102488.46 | 0.114105E+09 | 0.101088E+09 | 0.100592E+09 |
October | 87633982.09 | 0.00 | 87633982.09 | 29330542.00 | 0.194642E+09 |
November | 59323427.52 | 0.00 | 59323427.52 | 5718085.34 | 0.318732E+09 |
December | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.480844E+09 |
Annual Sum or Average | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.911872E+09 | 0.271056E+10 |
Minimum of Months | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 35260932.68 |
Maximum of Months | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.200774E+09 | 0.546306E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 69479256.08 | 0.115201E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.137373E+09 | 0.822906E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.304455E+09 | 0.589892E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.504540E+09 | 0.383871E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.804766E+09 | 0.197710E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.970889E+09 | 0.111233E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105107E+10 | 86674145.80 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.883019E+09 | 0.110726E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.687780E+09 | 0.225253E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.292996E+09 | 0.417818E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 82546037.16 | 0.677278E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 46930246.20 | 0.103460E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.583584E+10 | 0.580997E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 46930246.20 | 86674145.80 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105107E+10 | 0.115201E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.365426E+09 | 0.542363E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.358240E+09 | 0.394638E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.325792E+09 | 0.315565E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.277907E+09 | 0.215030E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.251635E+09 | 0.116744E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.273336E+09 | 64025504.91 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.312485E+09 | 49245016.32 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.367267E+09 | 63418956.99 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.425257E+09 | 0.124886E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.453642E+09 | 0.222907E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.286437E+09 | 0.333810E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.331565E+09 | 0.499629E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.402899E+10 | 0.294226E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.251635E+09 | 49245016.32 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.453642E+09 | 0.542363E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 3791.85 | 0.665057E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 966856.70 | 0.482784E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 26235610.89 | 0.344383E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 66585984.18 | 0.216186E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.150304E+09 | 0.108717E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.227032E+09 | 58836845.02 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.234970E+09 | 45851956.23 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.205057E+09 | 60064346.33 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.117151E+09 | 0.125677E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 36326550.26 | 0.237596E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7636143.51 | 0.384317E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.582228E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.107227E+10 | 0.331170E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 45851956.23 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.234970E+09 | 0.665057E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 71114473.97 | 0.113877E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.140898E+09 | 0.807889E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.312532E+09 | 0.580895E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.511593E+09 | 0.379940E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.808498E+09 | 0.196378E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.972720E+09 | 0.110680E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105336E+10 | 86074768.48 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.887068E+09 | 0.109550E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.695572E+09 | 0.222136E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.305489E+09 | 0.409099E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 86799724.20 | 0.667032E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 48106618.96 | 0.102090E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.589376E+10 | 0.572935E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 48106618.96 | 86074768.48 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105336E+10 | 0.113877E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92689285.68 | 0.00 | 92689285.68 | 0.00 | 0.860968E+09 |
February | 0.106140E+09 | 0.00 | 0.106140E+09 | 952699.49 | 0.613832E+09 |
March | 0.176138E+09 | 1489.68 | 0.176137E+09 | 33247588.46 | 0.443639E+09 |
April | 0.197544E+09 | 1584139.79 | 0.195960E+09 | 91199904.87 | 0.275695E+09 |
May | 0.265400E+09 | 10027981.57 | 0.255372E+09 | 0.211655E+09 | 0.133518E+09 |
June | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.311925E+09 | 71724614.47 |
July | 0.291293E+09 | 20051601.33 | 0.271241E+09 | 0.324072E+09 | 55401973.70 |
August | 0.244082E+09 | 4919085.54 | 0.239163E+09 | 0.282563E+09 | 73298321.87 |
September | 0.180773E+09 | 162222.46 | 0.180610E+09 | 0.162262E+09 | 0.157194E+09 |
October | 0.138710E+09 | 0.00 | 0.138710E+09 | 46662309.14 | 0.304168E+09 |
November | 93899275.44 | 0.00 | 93899275.44 | 9085932.51 | 0.502375E+09 |
December | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 0.762637E+09 |
Annual Sum or Average | 0.215016E+10 | 64566489.21 | 0.208559E+10 | 0.147363E+10 | 0.425445E+10 |
Minimum of Months | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 55401973.70 |
Maximum of Months | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.324072E+09 | 0.860968E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34169108.66 | 0.00 | 34169108.66 | 0.00 | 0.317388E+09 |
February | 39127512.35 | 0.00 | 39127512.35 | 351204.48 | 0.226284E+09 |
March | 64931807.30 | 549.16 | 64931258.14 | 12256437.78 | 0.163544E+09 |
April | 72822870.96 | 583979.52 | 72238891.44 | 33620061.23 | 0.101633E+09 |
May | 97837340.20 | 3696729.23 | 94140610.97 | 78024700.28 | 49220100.32 |
June | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.114988E+09 | 26440662.78 |
July | 0.107383E+09 | 7391850.52 | 99990758.17 | 0.119466E+09 | 20423461.52 |
August | 89978876.20 | 1813378.61 | 88165497.59 | 0.104165E+09 | 27020796.48 |
September | 66640246.57 | 59801.92 | 66580444.66 | 59816618.81 | 57948371.65 |
October | 51134341.44 | 0.00 | 51134341.44 | 17201659.28 | 0.112129E+09 |
November | 34615160.99 | 0.00 | 34615160.99 | 3349450.94 | 0.185196E+09 |
December | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 0.281140E+09 |
Annual Sum or Average | 0.792636E+09 | 23801881.41 | 0.768834E+09 | 0.543239E+09 | 0.156837E+10 |
Minimum of Months | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 20423461.52 |
Maximum of Months | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.119466E+09 | 0.317388E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213005E+09 | 0.145924E+09 | 67080677.26 | 0.170805E+09 | 0.255379E+09 |
February | 0.207482E+09 | 0.140778E+09 | 66703954.00 | 0.169957E+09 | 0.182701E+09 |
March | 0.196812E+09 | 0.103063E+09 | 93749766.36 | 0.154663E+09 | 0.148256E+09 |
April | 0.169726E+09 | 77778998.96 | 91946673.79 | 0.134172E+09 | 0.100210E+09 |
May | 0.149563E+09 | 41821325.16 | 0.107741E+09 | 0.125978E+09 | 52173611.59 |
June | 0.138167E+09 | 27573501.09 | 0.110594E+09 | 0.136808E+09 | 28331391.26 |
July | 0.151510E+09 | 37870946.71 | 0.113640E+09 | 0.156015E+09 | 21537717.72 |
August | 0.167901E+09 | 58128357.07 | 0.109773E+09 | 0.180685E+09 | 27993483.27 |
September | 0.196242E+09 | 0.101279E+09 | 94962720.04 | 0.205580E+09 | 56884912.00 |
October | 0.218572E+09 | 0.137830E+09 | 80742463.40 | 0.215920E+09 | 0.103585E+09 |
November | 0.158245E+09 | 99071298.74 | 59174088.99 | 0.134380E+09 | 0.158203E+09 |
December | 0.174060E+09 | 0.131804E+09 | 42256009.05 | 0.154894E+09 | 0.237862E+09 |
Annual Sum or Average | 0.214129E+10 | 0.110292E+10 | 0.103836E+10 | 0.193986E+10 | 0.137312E+10 |
Minimum of Months | 0.138167E+09 | 27573501.09 | 42256009.05 | 0.125978E+09 | 21537717.72 |
Maximum of Months | 0.218572E+09 | 0.145924E+09 | 0.113640E+09 | 0.215920E+09 | 0.255379E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578139E+09 | 0.396068E+09 | 0.182071E+09 | 0.463600E+09 | 0.693151E+09 |
February | 0.563149E+09 | 0.382101E+09 | 0.181048E+09 | 0.461299E+09 | 0.495888E+09 |
March | 0.534189E+09 | 0.279733E+09 | 0.254456E+09 | 0.419786E+09 | 0.402398E+09 |
April | 0.460670E+09 | 0.211108E+09 | 0.249562E+09 | 0.364171E+09 | 0.271990E+09 |
May | 0.405943E+09 | 0.113512E+09 | 0.292432E+09 | 0.341929E+09 | 0.141610E+09 |
June | 0.375014E+09 | 74840121.99 | 0.300174E+09 | 0.371325E+09 | 76897190.94 |
July | 0.411230E+09 | 0.102789E+09 | 0.308441E+09 | 0.423456E+09 | 58457771.34 |
August | 0.455718E+09 | 0.157772E+09 | 0.297946E+09 | 0.490415E+09 | 75980039.54 |
September | 0.532641E+09 | 0.274893E+09 | 0.257748E+09 | 0.557987E+09 | 0.154397E+09 |
October | 0.593250E+09 | 0.374098E+09 | 0.219152E+09 | 0.586050E+09 | 0.281151E+09 |
November | 0.429510E+09 | 0.268900E+09 | 0.160611E+09 | 0.364736E+09 | 0.429395E+09 |
December | 0.472435E+09 | 0.357743E+09 | 0.114691E+09 | 0.420414E+09 | 0.645607E+09 |
Annual Sum or Average | 0.581189E+10 | 0.299356E+10 | 0.281833E+10 | 0.526517E+10 | 0.372692E+10 |
Minimum of Months | 0.375014E+09 | 74840121.99 | 0.114691E+09 | 0.341929E+09 | 58457771.34 |
Maximum of Months | 0.593250E+09 | 0.396068E+09 | 0.308441E+09 | 0.586050E+09 | 0.693151E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.364427E+09 | 0.544826E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.357290E+09 | 0.397954E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.327955E+09 | 0.316579E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.278444E+09 | 0.217526E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.252921E+09 | 0.117662E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.273381E+09 | 64987582.32 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.311643E+09 | 50876963.32 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.365999E+09 | 65108139.01 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.426438E+09 | 0.125721E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.454291E+09 | 0.223590E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.286215E+09 | 0.334665E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.331190E+09 | 0.500935E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.403019E+10 | 0.296043E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.252921E+09 | 50876963.32 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.454291E+09 | 0.544826E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 84089031.94 | 0.117574E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.184289E+09 | 0.846222E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.293433E+09 | 0.607106E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.625796E+09 | 0.395497E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.728381E+09 | 0.211814E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.948478E+09 | 0.118795E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109128E+10 | 93823355.78 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.951839E+09 | 0.120154E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.669886E+09 | 0.232729E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.346455E+09 | 0.432795E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.117540E+09 | 0.690301E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 73900341.32 | 0.104951E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.611537E+10 | 0.597449E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 73900341.32 | 93823355.78 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109128E+10 | 0.117574E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 15346.55 | 0.667752E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1218237.17 | 0.486464E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 27718714.81 | 0.343823E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 66786336.14 | 0.218244E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.150845E+09 | 0.109196E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.226157E+09 | 59713422.17 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.233315E+09 | 47399247.20 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.203098E+09 | 61502206.79 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.118535E+09 | 0.125822E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 38129209.05 | 0.237030E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 8131021.22 | 0.384021E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.583108E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.107395E+10 | 0.332407E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 47399247.20 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.233315E+09 | 0.667752E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 87595102.47 | 0.116411E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.191020E+09 | 0.834026E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.303555E+09 | 0.600163E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.633837E+09 | 0.391895E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.732457E+09 | 0.210385E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.950163E+09 | 0.118081E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109348E+10 | 93129749.85 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.956041E+09 | 0.118928E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.678936E+09 | 0.229541E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.361946E+09 | 0.424960E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.124300E+09 | 0.682380E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 78220908.55 | 0.103909E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.619155E+10 | 0.590669E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 78220908.55 | 93129749.85 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109348E+10 | 0.116411E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.515374E+09 | 0.817608E+09 |
February | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.508258E+09 | 0.599447E+09 |
March | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.466634E+09 | 0.475483E+09 |
April | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.405198E+09 | 0.321128E+09 |
May | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.373354E+09 | 0.171035E+09 |
June | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.409297E+09 | 92786363.13 |
July | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.467413E+09 | 70656228.93 |
August | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.542969E+09 | 92695919.54 |
September | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.622859E+09 | 0.185644E+09 |
October | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.652969E+09 | 0.337574E+09 |
November | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.406519E+09 | 0.506306E+09 |
December | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.469199E+09 | 0.754012E+09 |
Annual Sum or Average | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.584004E+10 | 0.442438E+10 |
Minimum of Months | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.373354E+09 | 70656228.93 |
Maximum of Months | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.652969E+09 | 0.817608E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.494909E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 1669237.51 | 0.359022E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.132989E+09 | 0.275164E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.413694E+09 | 0.178951E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.987124E+09 | 0.930824E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.152425E+10 | 0.546857E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.159125E+10 | 0.445083E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.138912E+10 | 0.566683E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.783545E+09 | 0.107437E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.187595E+09 | 0.196235E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 30488744.73 | 0.305596E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.449152E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.704172E+10 | 0.261541E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.445083E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.159125E+10 | 0.494909E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.504287E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 914370.73 | 0.366873E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.118883E+09 | 0.282963E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.391114E+09 | 0.184514E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.946923E+09 | 0.962612E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.148670E+10 | 0.569301E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.155327E+10 | 0.465135E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.135253E+10 | 0.591391E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.755340E+09 | 0.111216E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.167952E+09 | 0.202402E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 25229791.48 | 0.313882E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.459364E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.679885E+10 | 0.268434E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.465135E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.155327E+10 | 0.504287E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 24570.40 | 0.638655E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1579006.65 | 0.453578E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 32985730.77 | 0.347820E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 86586156.17 | 0.222085E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.195712E+09 | 0.118745E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.281887E+09 | 69228942.77 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.296902E+09 | 54072322.17 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.261647E+09 | 68438839.43 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.155912E+09 | 0.130332E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 49262735.77 | 0.239805E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 11774161.24 | 0.381656E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.579451E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.137427E+10 | 0.330387E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 54072322.17 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.296902E+09 | 0.638655E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.584511E+09 | 0.239563E+09 | 0.344948E+09 | 0.163817E+09 | 0.220539E+10 |
February | 0.702953E+09 | 0.309404E+09 | 0.393549E+09 | 0.310082E+09 | 0.153368E+10 |
March | 0.105704E+10 | 0.419414E+09 | 0.637627E+09 | 0.667043E+09 | 0.119458E+10 |
April | 0.124848E+10 | 0.544148E+09 | 0.704333E+09 | 0.110941E+10 | 0.798115E+09 |
May | 0.162988E+10 | 0.712773E+09 | 0.917103E+09 | 0.178912E+10 | 0.437111E+09 |
June | 0.173334E+10 | 0.754970E+09 | 0.978368E+09 | 0.214830E+10 | 0.261610E+09 |
July | 0.181076E+10 | 0.835731E+09 | 0.975034E+09 | 0.233777E+10 | 0.205001E+09 |
August | 0.152676E+10 | 0.657939E+09 | 0.868824E+09 | 0.198662E+10 | 0.256262E+09 |
September | 0.132385E+10 | 0.627922E+09 | 0.695933E+09 | 0.154679E+10 | 0.473010E+09 |
October | 0.866230E+09 | 0.360550E+09 | 0.505680E+09 | 0.677508E+09 | 0.844564E+09 |
November | 0.495872E+09 | 0.160945E+09 | 0.334927E+09 | 0.198267E+09 | 0.134112E+10 |
December | 0.395447E+09 | 0.169327E+09 | 0.226119E+09 | 0.102747E+09 | 0.203878E+10 |
Annual Sum or Average | 0.133751E+11 | 0.579269E+10 | 0.758245E+10 | 0.130375E+11 | 0.115892E+11 |
Minimum of Months | 0.395447E+09 | 0.160945E+09 | 0.226119E+09 | 0.102747E+09 | 0.205001E+09 |
Maximum of Months | 0.181076E+10 | 0.835731E+09 | 0.978368E+09 | 0.233777E+10 | 0.220539E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.380032E+09 | 0.523019E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.378661E+09 | 0.375058E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.343096E+09 | 0.320166E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.302860E+09 | 0.220767E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.296991E+09 | 0.125270E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.326956E+09 | 73867713.17 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.373777E+09 | 56914906.84 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.423750E+09 | 71256867.55 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.469346E+09 | 0.129665E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.481926E+09 | 0.227838E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.300248E+09 | 0.334467E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.341307E+09 | 0.496701E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.441895E+10 | 0.295499E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.296991E+09 | 56914906.84 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.481926E+09 | 0.523019E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92765322.83 | 0.00 | 92765322.83 | 0.00 | 0.868875E+09 |
February | 0.106227E+09 | 0.00 | 0.106227E+09 | 608395.61 | 0.615445E+09 |
March | 0.176283E+09 | 1490.90 | 0.176281E+09 | 29651533.33 | 0.454513E+09 |
April | 0.197706E+09 | 1585439.33 | 0.196121E+09 | 82948949.20 | 0.287018E+09 |
May | 0.265617E+09 | 10036207.97 | 0.255581E+09 | 0.194767E+09 | 0.145276E+09 |
June | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.287143E+09 | 84887360.01 |
July | 0.291532E+09 | 20068050.55 | 0.271464E+09 | 0.296821E+09 | 69754767.90 |
August | 0.244283E+09 | 4923120.89 | 0.239360E+09 | 0.258770E+09 | 88392319.55 |
September | 0.180921E+09 | 162355.54 | 0.180758E+09 | 0.148142E+09 | 0.170520E+09 |
October | 0.138824E+09 | 0.00 | 0.138824E+09 | 40757148.14 | 0.315090E+09 |
November | 93976305.19 | 0.00 | 93976305.19 | 7524739.19 | 0.512825E+09 |
December | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 0.774777E+09 |
Annual Sum or Average | 0.215192E+10 | 64619455.98 | 0.208730E+10 | 0.134713E+10 | 0.438737E+10 |
Minimum of Months | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 69754767.90 |
Maximum of Months | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.296821E+09 | 0.868875E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82997485.82 | 0.00 | 82997485.82 | 0.00 | 0.777373E+09 |
February | 95041552.99 | 0.00 | 95041552.99 | 544333.86 | 0.550640E+09 |
March | 0.157721E+09 | 1333.91 | 0.157719E+09 | 26529339.22 | 0.406655E+09 |
April | 0.176888E+09 | 1418498.57 | 0.175470E+09 | 74214739.14 | 0.256796E+09 |
May | 0.237649E+09 | 8979433.30 | 0.228670E+09 | 0.174259E+09 | 0.129979E+09 |
June | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.256908E+09 | 75949042.63 |
July | 0.260835E+09 | 17954960.87 | 0.242880E+09 | 0.265567E+09 | 62409855.14 |
August | 0.218561E+09 | 4404734.91 | 0.214156E+09 | 0.231523E+09 | 79084943.22 |
September | 0.161871E+09 | 145260.12 | 0.161725E+09 | 0.132543E+09 | 0.152564E+09 |
October | 0.124206E+09 | 0.00 | 0.124206E+09 | 36465574.87 | 0.281913E+09 |
November | 84080956.33 | 0.00 | 84080956.33 | 6732412.67 | 0.458827E+09 |
December | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 0.693179E+09 |
Annual Sum or Average | 0.192533E+10 | 57815272.11 | 0.186752E+10 | 0.120529E+10 | 0.392537E+10 |
Minimum of Months | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 62409855.14 |
Maximum of Months | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.265567E+09 | 0.777373E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170568E+10 | 0.116852E+10 | 0.537162E+09 | 0.135333E+10 | 0.205943E+10 |
February | 0.166146E+10 | 0.112731E+10 | 0.534145E+09 | 0.135089E+10 | 0.146467E+10 |
March | 0.157601E+10 | 0.825294E+09 | 0.750720E+09 | 0.121610E+10 | 0.121343E+10 |
April | 0.135911E+10 | 0.622831E+09 | 0.736281E+09 | 0.104750E+10 | 0.835105E+09 |
May | 0.119765E+10 | 0.334893E+09 | 0.862759E+09 | 0.961323E+09 | 0.455937E+09 |
June | 0.110640E+10 | 0.220800E+09 | 0.885601E+09 | 0.102649E+10 | 0.270076E+09 |
July | 0.121325E+10 | 0.303259E+09 | 0.909991E+09 | 0.117228E+10 | 0.218796E+09 |
August | 0.134450E+10 | 0.465474E+09 | 0.879028E+09 | 0.137806E+10 | 0.271745E+09 |
September | 0.157145E+10 | 0.811014E+09 | 0.760433E+09 | 0.160125E+10 | 0.495120E+09 |
October | 0.175026E+10 | 0.110370E+10 | 0.646561E+09 | 0.169879E+10 | 0.857020E+09 |
November | 0.126718E+10 | 0.793333E+09 | 0.473848E+09 | 0.105803E+10 | 0.129298E+10 |
December | 0.139382E+10 | 0.105545E+10 | 0.338373E+09 | 0.122525E+10 | 0.193015E+10 |
Annual Sum or Average | 0.171468E+11 | 0.883188E+10 | 0.831490E+10 | 0.150893E+11 | 0.113645E+11 |
Minimum of Months | 0.110640E+10 | 0.220800E+09 | 0.338373E+09 | 0.961323E+09 | 0.218796E+09 |
Maximum of Months | 0.175026E+10 | 0.116852E+10 | 0.909991E+09 | 0.169879E+10 | 0.205943E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 701.06 | 954.58 | 863.80 | 591.77 | 272.03 | 0.00 | 0.00 |
February | 765.48 | 760.92 | 931.56 | 632.07 | 299.49 | 0.00 | 0.00 |
March | 622.23 | 564.73 | 798.14 | 417.95 | 380.19 | 0.00 | 0.00 |
April | 544.04 | 402.93 | 711.24 | 325.93 | 385.30 | 0.00 | 0.00 |
May | 488.83 | 211.56 | 606.52 | 169.60 | 436.93 | 0.00 | 0.00 |
June | 537.59 | 126.88 | 578.99 | 115.55 | 463.44 | 0.00 | 0.00 |
July | 593.74 | 99.61 | 614.42 | 153.58 | 460.84 | 0.00 | 0.00 |
August | 691.28 | 127.21 | 680.89 | 235.73 | 445.16 | 0.00 | 0.00 |
September | 824.03 | 248.37 | 822.35 | 424.41 | 397.94 | 0.00 | 0.00 |
October | 854.59 | 413.03 | 886.38 | 558.94 | 327.44 | 0.00 | 0.00 |
November | 560.10 | 620.65 | 663.13 | 415.16 | 247.97 | 0.00 | 0.00 |
December | 626.58 | 897.47 | 705.87 | 534.51 | 171.36 | 0.00 | 0.00 |
Annual Sum or Average | 650.23 | 450.92 | 737.51 | 379.87 | 357.64 | 0.00 | 0.00 |
Minimum of Months | 488.83 | 99.61 | 578.99 | 115.55 | 171.36 | 0.00 | 0.00 |
Maximum of Months | 854.59 | 954.58 | 931.56 | 632.07 | 463.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1960.54 | 2709.22 | 2432.41 | 1666.38 | 766.03 | 0.00 | 0.00 |
February | 2138.08 | 2186.33 | 2623.21 | 1779.87 | 843.34 | 0.00 | 0.00 |
March | 1729.15 | 1641.16 | 2247.50 | 1176.92 | 1070.58 | 0.00 | 0.00 |
April | 1509.14 | 1200.06 | 2002.79 | 917.81 | 1084.99 | 0.00 | 0.00 |
May | 1338.44 | 663.81 | 1707.93 | 477.58 | 1230.35 | 0.00 | 0.00 |
June | 1477.67 | 411.31 | 1630.40 | 325.37 | 1305.02 | 0.00 | 0.00 |
July | 1637.88 | 325.15 | 1730.18 | 432.47 | 1297.71 | 0.00 | 0.00 |
August | 1916.37 | 412.19 | 1917.35 | 663.80 | 1253.55 | 0.00 | 0.00 |
September | 2292.25 | 766.72 | 2315.69 | 1195.11 | 1120.58 | 0.00 | 0.00 |
October | 2378.73 | 1241.38 | 2495.99 | 1573.95 | 922.04 | 0.00 | 0.00 |
November | 1558.02 | 1798.24 | 1867.32 | 1169.06 | 698.26 | 0.00 | 0.00 |
December | 1750.18 | 2552.43 | 1987.68 | 1505.14 | 482.54 | 0.00 | 0.00 |
Annual Sum or Average | 1805.56 | 1321.68 | 2076.78 | 1069.70 | 1007.08 | 0.00 | 0.00 |
Minimum of Months | 1338.44 | 325.15 | 1630.40 | 325.37 | 482.54 | 0.00 | 0.00 |
Maximum of Months | 2378.73 | 2709.22 | 2623.21 | 1779.87 | 1305.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2581.45 | 3657.33 | 3159.84 | 2164.73 | 995.12 | 0.00 | 0.00 |
February | 2828.77 | 2940.12 | 3407.69 | 2312.15 | 1095.55 | 0.00 | 0.00 |
March | 2284.06 | 2237.08 | 2919.63 | 1528.89 | 1390.74 | 0.00 | 0.00 |
April | 2000.75 | 1639.96 | 2601.74 | 1192.28 | 1409.46 | 0.00 | 0.00 |
May | 1768.13 | 903.53 | 2218.70 | 620.40 | 1598.30 | 0.00 | 0.00 |
June | 1967.90 | 555.42 | 2117.98 | 422.68 | 1695.30 | 0.00 | 0.00 |
July | 2185.95 | 432.21 | 2247.60 | 561.80 | 1685.80 | 0.00 | 0.00 |
August | 2553.46 | 545.89 | 2490.75 | 862.31 | 1628.44 | 0.00 | 0.00 |
September | 3045.20 | 1029.99 | 3008.21 | 1552.52 | 1455.69 | 0.00 | 0.00 |
October | 3137.13 | 1685.54 | 3242.43 | 2044.65 | 1197.78 | 0.00 | 0.00 |
November | 2046.07 | 2457.37 | 2425.76 | 1518.67 | 907.08 | 0.00 | 0.00 |
December | 2305.75 | 3465.84 | 2582.11 | 1955.26 | 626.85 | 0.00 | 0.00 |
Annual Sum or Average | 2389.86 | 1790.56 | 2697.86 | 1389.60 | 1308.26 | 0.00 | 0.00 |
Minimum of Months | 1768.13 | 432.21 | 2117.98 | 422.68 | 626.85 | 0.00 | 0.00 |
Maximum of Months | 3137.13 | 3657.33 | 3407.69 | 2312.15 | 1695.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.64 | 598.14 | 279.39 | 161.07 | 118.31 | 0.00 | 0.00 |
February | 192.99 | 479.35 | 342.80 | 202.99 | 139.81 | 0.00 | 0.00 |
March | 222.31 | 334.39 | 347.24 | 153.05 | 194.19 | 0.00 | 0.00 |
April | 346.89 | 232.56 | 417.83 | 201.64 | 216.19 | 0.00 | 0.00 |
May | 368.83 | 121.07 | 397.69 | 144.76 | 252.93 | 0.00 | 0.00 |
June | 474.76 | 70.09 | 439.45 | 163.38 | 276.06 | 0.00 | 0.00 |
July | 527.71 | 53.44 | 470.54 | 195.99 | 274.54 | 0.00 | 0.00 |
August | 495.46 | 68.25 | 439.37 | 186.08 | 253.29 | 0.00 | 0.00 |
September | 423.73 | 137.09 | 409.80 | 201.05 | 208.75 | 0.00 | 0.00 |
October | 294.62 | 240.44 | 348.40 | 187.80 | 160.60 | 0.00 | 0.00 |
November | 140.91 | 380.47 | 234.37 | 120.36 | 114.01 | 0.00 | 0.00 |
December | 124.01 | 550.35 | 218.97 | 143.18 | 75.79 | 0.00 | 0.00 |
Annual Sum or Average | 312.17 | 271.17 | 362.17 | 171.53 | 190.64 | 0.00 | 0.00 |
Minimum of Months | 124.01 | 53.44 | 218.97 | 120.36 | 75.79 | 0.00 | 0.00 |
Maximum of Months | 527.71 | 598.14 | 470.54 | 202.99 | 276.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.51 | 670.80 | 136.27 | 44.31 | 91.96 | 0.00 | 0.00 |
February | 66.11 | 529.14 | 193.64 | 78.28 | 115.36 | 0.00 | 0.00 |
March | 116.63 | 345.02 | 241.68 | 70.58 | 171.10 | 0.00 | 0.00 |
April | 268.49 | 231.92 | 337.68 | 137.81 | 199.86 | 0.00 | 0.00 |
May | 333.12 | 118.12 | 356.26 | 114.25 | 242.00 | 0.00 | 0.00 |
June | 456.95 | 67.14 | 416.76 | 149.06 | 267.70 | 0.00 | 0.00 |
July | 499.32 | 51.50 | 435.18 | 171.60 | 263.58 | 0.00 | 0.00 |
August | 436.78 | 66.61 | 376.98 | 141.02 | 235.96 | 0.00 | 0.00 |
September | 308.47 | 136.18 | 302.60 | 117.36 | 185.25 | 0.00 | 0.00 |
October | 145.53 | 244.83 | 214.39 | 77.51 | 136.88 | 0.00 | 0.00 |
November | 45.52 | 406.59 | 132.13 | 38.44 | 93.69 | 0.00 | 0.00 |
December | 21.79 | 596.87 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Annual Sum or Average | 227.62 | 287.61 | 270.48 | 98.19 | 172.30 | 0.00 | 0.00 |
Minimum of Months | 21.79 | 51.50 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Maximum of Months | 499.32 | 670.80 | 435.18 | 171.60 | 267.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.73 | 158.02 | 136.33 | 93.39 | 42.93 | 0.00 | 0.00 |
February | 118.19 | 129.14 | 147.02 | 99.75 | 47.27 | 0.00 | 0.00 |
March | 97.53 | 93.43 | 125.96 | 65.96 | 60.00 | 0.00 | 0.00 |
April | 86.41 | 67.63 | 112.25 | 51.44 | 60.81 | 0.00 | 0.00 |
May | 74.01 | 39.75 | 95.72 | 26.77 | 68.96 | 0.00 | 0.00 |
June | 82.80 | 24.81 | 91.38 | 18.24 | 73.14 | 0.00 | 0.00 |
July | 91.79 | 19.61 | 96.97 | 24.24 | 72.73 | 0.00 | 0.00 |
August | 107.71 | 24.67 | 107.46 | 37.20 | 70.26 | 0.00 | 0.00 |
September | 129.53 | 45.36 | 129.78 | 66.98 | 62.80 | 0.00 | 0.00 |
October | 132.71 | 73.92 | 139.89 | 88.21 | 51.68 | 0.00 | 0.00 |
November | 87.10 | 104.07 | 104.65 | 65.52 | 39.13 | 0.00 | 0.00 |
December | 98.31 | 146.36 | 111.40 | 84.36 | 27.04 | 0.00 | 0.00 |
Annual Sum or Average | 101.15 | 76.99 | 116.39 | 59.95 | 56.44 | 0.00 | 0.00 |
Minimum of Months | 74.01 | 19.61 | 91.38 | 18.24 | 27.04 | 0.00 | 0.00 |
Maximum of Months | 132.71 | 158.02 | 147.02 | 99.75 | 73.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 203.97 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
February | 0.29 | 163.32 | 27.72 | 0.00 | 27.72 | 0.00 | 0.00 |
March | 7.82 | 105.42 | 41.55 | 0.00 | 41.55 | 0.00 | 0.00 |
April | 21.85 | 68.20 | 48.15 | 0.39 | 47.76 | 0.00 | 0.00 |
May | 48.13 | 32.39 | 62.60 | 2.37 | 60.24 | 0.00 | 0.00 |
June | 74.30 | 17.91 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
July | 74.96 | 13.16 | 68.71 | 4.73 | 63.98 | 0.00 | 0.00 |
August | 65.41 | 17.47 | 57.57 | 1.16 | 56.41 | 0.00 | 0.00 |
September | 39.00 | 38.81 | 44.06 | 0.04 | 44.02 | 0.00 | 0.00 |
October | 10.95 | 72.67 | 32.72 | 0.00 | 32.72 | 0.00 | 0.00 |
November | 2.21 | 122.97 | 22.89 | 0.00 | 22.89 | 0.00 | 0.00 |
December | 0.00 | 179.53 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Annual Sum or Average | 28.92 | 85.95 | 43.08 | 1.29 | 41.78 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 13.16 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Maximum of Months | 74.96 | 203.97 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.10 | 595.33 | 279.47 | 161.45 | 118.02 | 0.00 | 0.00 |
February | 173.65 | 472.07 | 328.99 | 188.62 | 140.37 | 0.00 | 0.00 |
March | 226.76 | 329.51 | 354.66 | 160.70 | 193.96 | 0.00 | 0.00 |
April | 297.84 | 227.03 | 380.99 | 169.20 | 211.79 | 0.00 | 0.00 |
May | 390.99 | 113.98 | 423.71 | 166.42 | 257.29 | 0.00 | 0.00 |
June | 478.39 | 65.98 | 448.36 | 168.32 | 280.03 | 0.00 | 0.00 |
July | 508.08 | 49.73 | 459.01 | 186.20 | 272.81 | 0.00 | 0.00 |
August | 465.40 | 63.62 | 419.15 | 169.24 | 249.91 | 0.00 | 0.00 |
September | 427.52 | 133.19 | 417.44 | 204.78 | 212.67 | 0.00 | 0.00 |
October | 275.04 | 235.50 | 336.48 | 177.54 | 158.94 | 0.00 | 0.00 |
November | 128.06 | 375.78 | 226.43 | 112.94 | 113.49 | 0.00 | 0.00 |
December | 113.56 | 545.06 | 213.04 | 137.05 | 75.99 | 0.00 | 0.00 |
Annual Sum or Average | 301.56 | 266.28 | 357.42 | 166.73 | 190.70 | 0.00 | 0.00 |
Minimum of Months | 113.56 | 49.73 | 213.04 | 112.94 | 75.99 | 0.00 | 0.00 |
Maximum of Months | 508.08 | 595.33 | 459.01 | 204.78 | 280.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.66 | 661.59 | 136.36 | 44.69 | 91.67 | 0.00 | 0.00 |
February | 44.28 | 519.15 | 179.82 | 63.90 | 115.92 | 0.00 | 0.00 |
March | 117.54 | 336.52 | 249.11 | 78.24 | 170.87 | 0.00 | 0.00 |
April | 218.80 | 225.72 | 300.83 | 105.37 | 195.46 | 0.00 | 0.00 |
May | 355.98 | 111.92 | 382.28 | 135.92 | 246.36 | 0.00 | 0.00 |
June | 462.43 | 64.97 | 425.67 | 154.00 | 271.67 | 0.00 | 0.00 |
July | 480.79 | 49.04 | 423.65 | 161.81 | 261.85 | 0.00 | 0.00 |
August | 407.05 | 62.62 | 356.76 | 124.18 | 232.58 | 0.00 | 0.00 |
September | 311.06 | 131.70 | 310.25 | 121.09 | 189.17 | 0.00 | 0.00 |
October | 121.98 | 235.81 | 202.48 | 67.26 | 135.22 | 0.00 | 0.00 |
November | 30.34 | 399.52 | 124.19 | 31.02 | 93.16 | 0.00 | 0.00 |
December | 11.35 | 591.93 | 92.32 | 31.59 | 60.74 | 0.00 | 0.00 |
Annual Sum or Average | 215.64 | 281.44 | 265.74 | 93.39 | 172.35 | 0.00 | 0.00 |
Minimum of Months | 11.35 | 49.04 | 92.32 | 31.02 | 60.74 | 0.00 | 0.00 |
Maximum of Months | 480.79 | 661.59 | 425.67 | 161.81 | 271.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.55 | 732.78 | 342.74 | 202.36 | 140.39 | 0.00 | 0.00 |
February | 214.37 | 580.67 | 378.60 | 216.14 | 162.46 | 0.00 | 0.00 |
March | 220.49 | 421.32 | 362.93 | 142.92 | 220.01 | 0.00 | 0.00 |
April | 239.34 | 288.09 | 347.52 | 112.29 | 235.23 | 0.00 | 0.00 |
May | 282.29 | 140.02 | 343.02 | 63.12 | 279.90 | 0.00 | 0.00 |
June | 359.25 | 76.98 | 356.68 | 54.20 | 302.48 | 0.00 | 0.00 |
July | 381.18 | 57.41 | 358.95 | 62.76 | 296.19 | 0.00 | 0.00 |
August | 394.71 | 76.03 | 357.56 | 83.12 | 274.44 | 0.00 | 0.00 |
September | 379.79 | 164.04 | 376.66 | 145.21 | 231.44 | 0.00 | 0.00 |
October | 317.22 | 293.02 | 373.98 | 191.13 | 182.85 | 0.00 | 0.00 |
November | 173.30 | 467.91 | 276.34 | 141.96 | 134.37 | 0.00 | 0.00 |
December | 171.87 | 676.62 | 273.53 | 182.78 | 90.76 | 0.00 | 0.00 |
Annual Sum or Average | 276.15 | 330.09 | 345.51 | 132.70 | 212.81 | 0.00 | 0.00 |
Minimum of Months | 171.87 | 57.41 | 273.53 | 54.20 | 90.76 | 0.00 | 0.00 |
Maximum of Months | 394.71 | 732.78 | 378.60 | 216.14 | 302.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.75 | 600.68 | 279.62 | 161.20 | 118.41 | 0.00 | 0.00 |
February | 191.57 | 481.99 | 343.09 | 203.16 | 139.93 | 0.00 | 0.00 |
March | 221.92 | 334.79 | 347.52 | 153.17 | 194.35 | 0.00 | 0.00 |
April | 345.04 | 232.69 | 418.18 | 201.81 | 216.37 | 0.00 | 0.00 |
May | 365.11 | 121.75 | 398.02 | 144.88 | 253.14 | 0.00 | 0.00 |
June | 470.96 | 70.47 | 439.81 | 163.52 | 276.29 | 0.00 | 0.00 |
July | 523.59 | 53.82 | 470.92 | 196.15 | 274.77 | 0.00 | 0.00 |
August | 491.70 | 68.84 | 439.73 | 186.24 | 253.50 | 0.00 | 0.00 |
September | 421.72 | 137.04 | 410.13 | 201.21 | 208.92 | 0.00 | 0.00 |
October | 293.99 | 240.10 | 348.68 | 187.95 | 160.73 | 0.00 | 0.00 |
November | 140.98 | 380.65 | 234.56 | 120.46 | 114.10 | 0.00 | 0.00 |
December | 124.20 | 551.82 | 219.15 | 143.30 | 75.85 | 0.00 | 0.00 |
Annual Sum or Average | 310.30 | 271.91 | 362.46 | 171.67 | 190.80 | 0.00 | 0.00 |
Minimum of Months | 124.20 | 53.82 | 219.15 | 120.46 | 75.85 | 0.00 | 0.00 |
Maximum of Months | 523.59 | 600.68 | 470.92 | 203.16 | 276.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.38 | 673.60 | 136.38 | 44.34 | 92.04 | 0.00 | 0.00 |
February | 65.73 | 532.11 | 193.80 | 78.34 | 115.46 | 0.00 | 0.00 |
March | 116.61 | 345.37 | 241.88 | 70.64 | 171.24 | 0.00 | 0.00 |
April | 266.83 | 231.92 | 337.95 | 137.92 | 200.03 | 0.00 | 0.00 |
May | 329.19 | 118.72 | 356.55 | 114.35 | 242.20 | 0.00 | 0.00 |
June | 452.77 | 67.54 | 417.11 | 149.18 | 267.92 | 0.00 | 0.00 |
July | 494.80 | 51.90 | 435.53 | 171.74 | 263.79 | 0.00 | 0.00 |
August | 432.59 | 67.18 | 377.29 | 141.14 | 236.15 | 0.00 | 0.00 |
September | 306.53 | 135.96 | 302.85 | 117.45 | 185.40 | 0.00 | 0.00 |
October | 146.02 | 243.81 | 214.57 | 77.57 | 137.00 | 0.00 | 0.00 |
November | 46.01 | 406.33 | 132.24 | 38.47 | 93.76 | 0.00 | 0.00 |
December | 21.93 | 598.39 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Annual Sum or Average | 225.95 | 288.27 | 270.70 | 98.27 | 172.44 | 0.00 | 0.00 |
Minimum of Months | 21.93 | 51.90 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Maximum of Months | 494.80 | 673.60 | 435.53 | 171.74 | 267.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.42 | 305.26 | 250.17 | 171.39 | 78.79 | 0.00 | 0.00 |
February | 210.09 | 247.79 | 269.80 | 183.06 | 86.74 | 0.00 | 0.00 |
March | 174.22 | 177.53 | 231.15 | 121.05 | 110.11 | 0.00 | 0.00 |
April | 156.33 | 123.89 | 205.99 | 94.40 | 111.59 | 0.00 | 0.00 |
May | 139.39 | 63.86 | 175.66 | 49.12 | 126.54 | 0.00 | 0.00 |
June | 157.91 | 35.80 | 167.69 | 33.46 | 134.22 | 0.00 | 0.00 |
July | 174.51 | 26.38 | 177.95 | 44.48 | 133.47 | 0.00 | 0.00 |
August | 202.72 | 34.61 | 197.20 | 68.27 | 128.93 | 0.00 | 0.00 |
September | 240.30 | 71.62 | 238.17 | 122.92 | 115.25 | 0.00 | 0.00 |
October | 243.79 | 126.04 | 256.71 | 161.88 | 94.83 | 0.00 | 0.00 |
November | 156.84 | 195.33 | 192.05 | 120.24 | 71.82 | 0.00 | 0.00 |
December | 175.18 | 281.52 | 204.43 | 154.80 | 49.63 | 0.00 | 0.00 |
Annual Sum or Average | 185.19 | 140.30 | 213.60 | 110.02 | 103.58 | 0.00 | 0.00 |
Minimum of Months | 139.39 | 26.38 | 167.69 | 33.46 | 49.63 | 0.00 | 0.00 |
Maximum of Months | 243.79 | 305.26 | 269.80 | 183.06 | 134.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1847.78 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.69 | 1484.05 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 49.65 | 1027.34 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 159.60 | 690.40 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 368.55 | 347.53 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 588.06 | 210.98 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 594.10 | 166.17 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 518.64 | 211.58 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 302.29 | 414.50 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 70.04 | 732.66 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 11.76 | 1179.00 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1676.94 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 223.29 | 829.34 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 166.17 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 594.10 | 1847.78 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1882.79 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.38 | 1516.51 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 44.39 | 1056.46 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 150.89 | 711.86 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 353.54 | 359.40 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 573.57 | 219.64 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 579.92 | 173.66 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 504.98 | 220.80 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 291.41 | 429.07 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 62.71 | 755.68 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 9.73 | 1210.96 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1715.07 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 215.59 | 851.20 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 173.66 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 579.92 | 1882.79 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.09 | 1178.15 | 416.16 | 206.30 | 209.86 | 0.00 | 0.00 |
February | 221.62 | 912.76 | 509.21 | 252.71 | 256.49 | 0.00 | 0.00 |
March | 370.03 | 675.97 | 604.24 | 239.13 | 365.11 | 0.00 | 0.00 |
April | 571.60 | 472.10 | 682.35 | 274.78 | 407.57 | 0.00 | 0.00 |
May | 847.83 | 250.20 | 806.61 | 302.57 | 504.04 | 0.00 | 0.00 |
June | 1061.95 | 154.37 | 874.70 | 322.57 | 552.13 | 0.00 | 0.00 |
July | 1122.35 | 117.10 | 883.34 | 348.27 | 535.07 | 0.00 | 0.00 |
August | 996.23 | 146.44 | 776.51 | 293.65 | 482.86 | 0.00 | 0.00 |
September | 834.98 | 279.80 | 728.26 | 326.11 | 402.14 | 0.00 | 0.00 |
October | 443.89 | 482.54 | 539.38 | 244.99 | 294.39 | 0.00 | 0.00 |
November | 165.44 | 762.25 | 350.89 | 144.08 | 206.81 | 0.00 | 0.00 |
December | 105.83 | 1103.03 | 305.61 | 168.77 | 136.83 | 0.00 | 0.00 |
Annual Sum or Average | 574.09 | 542.93 | 623.64 | 260.32 | 363.33 | 0.00 | 0.00 |
Minimum of Months | 105.83 | 117.10 | 305.61 | 144.08 | 136.83 | 0.00 | 0.00 |
Maximum of Months | 1122.35 | 1178.15 | 883.34 | 348.27 | 552.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.01 | 1293.27 | 702.45 | 436.27 | 266.18 | 0.00 | 0.00 |
February | 490.27 | 1018.84 | 769.98 | 465.98 | 303.99 | 0.00 | 0.00 |
March | 457.85 | 757.40 | 713.12 | 308.13 | 404.99 | 0.00 | 0.00 |
April | 462.89 | 530.12 | 668.87 | 241.45 | 427.42 | 0.00 | 0.00 |
May | 495.68 | 271.98 | 635.05 | 132.13 | 502.92 | 0.00 | 0.00 |
June | 602.45 | 162.78 | 646.73 | 105.54 | 541.19 | 0.00 | 0.00 |
July | 645.74 | 129.12 | 659.21 | 127.42 | 531.79 | 0.00 | 0.00 |
August | 697.08 | 163.51 | 674.79 | 177.27 | 497.51 | 0.00 | 0.00 |
September | 725.21 | 314.82 | 738.52 | 313.01 | 425.51 | 0.00 | 0.00 |
October | 653.09 | 532.87 | 751.68 | 412.07 | 339.60 | 0.00 | 0.00 |
November | 377.52 | 837.53 | 557.58 | 306.07 | 251.51 | 0.00 | 0.00 |
December | 394.07 | 1205.32 | 564.95 | 394.06 | 170.89 | 0.00 | 0.00 |
Annual Sum or Average | 535.02 | 599.57 | 673.01 | 283.94 | 389.07 | 0.00 | 0.00 |
Minimum of Months | 377.52 | 129.12 | 557.58 | 105.54 | 170.89 | 0.00 | 0.00 |
Maximum of Months | 725.21 | 1293.27 | 769.98 | 465.98 | 541.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187771E+10 | 0.255674E+10 | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.00 | 0.00 |
February | 0.185185E+10 | 0.184082E+10 | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.00 | 0.00 |
March | 0.166659E+10 | 0.151259E+10 | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.00 | 0.00 |
April | 0.141014E+10 | 0.104440E+10 | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.00 | 0.00 |
May | 0.130929E+10 | 0.566635E+09 | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.00 | 0.00 |
June | 0.139343E+10 | 0.328863E+09 | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.00 | 0.00 |
July | 0.159028E+10 | 0.266786E+09 | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.00 | 0.00 |
August | 0.185153E+10 | 0.340728E+09 | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.00 | 0.00 |
September | 0.213589E+10 | 0.643780E+09 | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.00 | 0.00 |
October | 0.228894E+10 | 0.110625E+10 | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.00 | 0.00 |
November | 0.145177E+10 | 0.160873E+10 | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.00 | 0.00 |
December | 0.167824E+10 | 0.240378E+10 | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205057E+11 | 0.142201E+11 | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130929E+10 | 0.266786E+09 | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.00 | 0.00 |
Maximum of Months | 0.228894E+10 | 0.255674E+10 | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525110E+10 | 0.725639E+10 | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.00 | 0.00 |
February | 0.517244E+10 | 0.528916E+10 | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.00 | 0.00 |
March | 0.463136E+10 | 0.439569E+10 | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.00 | 0.00 |
April | 0.391170E+10 | 0.311056E+10 | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.00 | 0.00 |
May | 0.358488E+10 | 0.177794E+10 | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.383012E+10 | 0.106611E+10 | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.00 | 0.00 |
July | 0.438689E+10 | 0.870883E+09 | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.00 | 0.00 |
August | 0.513280E+10 | 0.110401E+10 | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.00 | 0.00 |
September | 0.594152E+10 | 0.198734E+10 | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.00 | 0.00 |
October | 0.637120E+10 | 0.332490E+10 | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.00 | 0.00 |
November | 0.403839E+10 | 0.466103E+10 | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.00 | 0.00 |
December | 0.468769E+10 | 0.683643E+10 | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.569401E+11 | 0.416804E+11 | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358488E+10 | 0.870883E+09 | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.637120E+10 | 0.725639E+10 | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691416E+10 | 0.979580E+10 | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.00 | 0.00 |
February | 0.684335E+10 | 0.711274E+10 | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.00 | 0.00 |
March | 0.611763E+10 | 0.599180E+10 | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.00 | 0.00 |
April | 0.518595E+10 | 0.425078E+10 | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.00 | 0.00 |
May | 0.473577E+10 | 0.242002E+10 | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.00 | 0.00 |
June | 0.510079E+10 | 0.143965E+10 | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.00 | 0.00 |
July | 0.585485E+10 | 0.115762E+10 | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.00 | 0.00 |
August | 0.683918E+10 | 0.146211E+10 | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.00 | 0.00 |
September | 0.789317E+10 | 0.266973E+10 | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.00 | 0.00 |
October | 0.840249E+10 | 0.451455E+10 | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.00 | 0.00 |
November | 0.530341E+10 | 0.636950E+10 | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.00 | 0.00 |
December | 0.617573E+10 | 0.928290E+10 | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.753665E+11 | 0.564672E+11 | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.00 | 0.00 |
Minimum of Months | 0.473577E+10 | 0.115762E+10 | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.00 | 0.00 |
Maximum of Months | 0.840249E+10 | 0.979580E+10 | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339199E+09 | 0.160205E+10 | 0.748309E+09 | 0.431415E+09 | 0.316894E+09 | 0.00 | 0.00 |
February | 0.466891E+09 | 0.115965E+10 | 0.829313E+09 | 0.491083E+09 | 0.338230E+09 | 0.00 | 0.00 |
March | 0.595441E+09 | 0.895620E+09 | 0.930041E+09 | 0.409925E+09 | 0.520116E+09 | 0.00 | 0.00 |
April | 0.899152E+09 | 0.602805E+09 | 0.108302E+10 | 0.522652E+09 | 0.560370E+09 | 0.00 | 0.00 |
May | 0.987882E+09 | 0.324274E+09 | 0.106517E+10 | 0.387727E+09 | 0.677444E+09 | 0.00 | 0.00 |
June | 0.123059E+10 | 0.181669E+09 | 0.113905E+10 | 0.423494E+09 | 0.715557E+09 | 0.00 | 0.00 |
July | 0.141341E+10 | 0.143147E+09 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
August | 0.132703E+10 | 0.182804E+09 | 0.117681E+10 | 0.498404E+09 | 0.678406E+09 | 0.00 | 0.00 |
September | 0.109832E+10 | 0.355331E+09 | 0.106219E+10 | 0.521121E+09 | 0.541072E+09 | 0.00 | 0.00 |
October | 0.789121E+09 | 0.643983E+09 | 0.933147E+09 | 0.503000E+09 | 0.430148E+09 | 0.00 | 0.00 |
November | 0.365251E+09 | 0.986178E+09 | 0.607482E+09 | 0.311969E+09 | 0.295513E+09 | 0.00 | 0.00 |
December | 0.332150E+09 | 0.147405E+10 | 0.586489E+09 | 0.383497E+09 | 0.202992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.984444E+10 | 0.855157E+10 | 0.114213E+11 | 0.540923E+10 | 0.601208E+10 | 0.00 | 0.00 |
Minimum of Months | 0.332150E+09 | 0.143147E+09 | 0.586489E+09 | 0.311969E+09 | 0.202992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141341E+10 | 0.160205E+10 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60292321.96 | 0.179666E+10 | 0.364990E+09 | 0.118673E+09 | 0.246317E+09 | 0.00 | 0.00 |
February | 0.159942E+09 | 0.128009E+10 | 0.468450E+09 | 0.189369E+09 | 0.279081E+09 | 0.00 | 0.00 |
March | 0.312389E+09 | 0.924095E+09 | 0.647318E+09 | 0.189044E+09 | 0.458274E+09 | 0.00 | 0.00 |
April | 0.695936E+09 | 0.601139E+09 | 0.875254E+09 | 0.357208E+09 | 0.518045E+09 | 0.00 | 0.00 |
May | 0.892238E+09 | 0.316368E+09 | 0.954195E+09 | 0.306014E+09 | 0.648181E+09 | 0.00 | 0.00 |
June | 0.118443E+10 | 0.174036E+09 | 0.108025E+10 | 0.386366E+09 | 0.693885E+09 | 0.00 | 0.00 |
July | 0.133739E+10 | 0.137950E+09 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
August | 0.116988E+10 | 0.178404E+09 | 0.100970E+10 | 0.377708E+09 | 0.631991E+09 | 0.00 | 0.00 |
September | 0.799549E+09 | 0.352971E+09 | 0.784351E+09 | 0.304189E+09 | 0.480163E+09 | 0.00 | 0.00 |
October | 0.389798E+09 | 0.655763E+09 | 0.574235E+09 | 0.207605E+09 | 0.366630E+09 | 0.00 | 0.00 |
November | 0.118000E+09 | 0.105389E+10 | 0.342478E+09 | 99641378.41 | 0.242837E+09 | 0.00 | 0.00 |
December | 58351123.46 | 0.159865E+10 | 0.263144E+09 | 0.101017E+09 | 0.162127E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.717819E+10 | 0.907002E+10 | 0.852994E+10 | 0.309645E+10 | 0.543350E+10 | 0.00 | 0.00 |
Minimum of Months | 58351123.46 | 0.137950E+09 | 0.263144E+09 | 99641378.41 | 0.162127E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133739E+10 | 0.179666E+10 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291224E+09 | 0.423244E+09 | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.00 | 0.00 |
February | 0.285932E+09 | 0.312416E+09 | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.00 | 0.00 |
March | 0.261227E+09 | 0.250254E+09 | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.00 | 0.00 |
April | 0.223974E+09 | 0.175289E+09 | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.00 | 0.00 |
May | 0.198225E+09 | 0.106479E+09 | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.00 | 0.00 |
June | 0.214611E+09 | 64306425.70 | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.00 | 0.00 |
July | 0.245846E+09 | 52519944.36 | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.00 | 0.00 |
August | 0.288495E+09 | 66078913.69 | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.00 | 0.00 |
September | 0.335743E+09 | 0.117573E+09 | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.00 | 0.00 |
October | 0.355442E+09 | 0.197998E+09 | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.00 | 0.00 |
November | 0.225773E+09 | 0.269759E+09 | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.00 | 0.00 |
December | 0.263303E+09 | 0.392023E+09 | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.318979E+10 | 0.242794E+10 | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.198225E+09 | 52519944.36 | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.00 | 0.00 |
Maximum of Months | 0.355442E+09 | 0.423244E+09 | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.546306E+09 | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.00 |
February | 707064.40 | 0.395094E+09 | 67056690.67 | 0.00 | 67056690.67 | 0.00 | 0.00 |
March | 20942885.02 | 0.282354E+09 | 0.111280E+09 | 941.15 | 0.111279E+09 | 0.00 | 0.00 |
April | 56630984.75 | 0.176781E+09 | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 0.00 | 0.00 |
May | 0.128904E+09 | 86742506.09 | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.00 | 0.00 |
June | 0.192579E+09 | 46420051.68 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
July | 0.200774E+09 | 35260932.68 | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.00 | 0.00 |
August | 0.175198E+09 | 46788706.31 | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.00 | 0.00 |
September | 0.101088E+09 | 0.100592E+09 | 0.114208E+09 | 102488.46 | 0.114105E+09 | 0.00 | 0.00 |
October | 29330542.00 | 0.194642E+09 | 87633982.09 | 0.00 | 87633982.09 | 0.00 | 0.00 |
November | 5718085.34 | 0.318732E+09 | 59323427.52 | 0.00 | 59323427.52 | 0.00 | 0.00 |
December | 0.00 | 0.480844E+09 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.911872E+09 | 0.271056E+10 | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 35260932.68 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Maximum of Months | 0.200774E+09 | 0.546306E+09 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335064E+09 | 0.159453E+10 | 0.748545E+09 | 0.432434E+09 | 0.316111E+09 | 0.00 | 0.00 |
February | 0.420090E+09 | 0.114202E+10 | 0.795886E+09 | 0.456300E+09 | 0.339586E+09 | 0.00 | 0.00 |
March | 0.607363E+09 | 0.882573E+09 | 0.949929E+09 | 0.430432E+09 | 0.519498E+09 | 0.00 | 0.00 |
April | 0.772008E+09 | 0.588462E+09 | 0.987526E+09 | 0.438565E+09 | 0.548961E+09 | 0.00 | 0.00 |
May | 0.104724E+10 | 0.305291E+09 | 0.113487E+10 | 0.445751E+09 | 0.689117E+09 | 0.00 | 0.00 |
June | 0.123999E+10 | 0.171028E+09 | 0.116214E+10 | 0.436297E+09 | 0.725840E+09 | 0.00 | 0.00 |
July | 0.136083E+10 | 0.133201E+09 | 0.122942E+10 | 0.498717E+09 | 0.730702E+09 | 0.00 | 0.00 |
August | 0.124653E+10 | 0.170389E+09 | 0.112265E+10 | 0.453303E+09 | 0.669350E+09 | 0.00 | 0.00 |
September | 0.110813E+10 | 0.345232E+09 | 0.108201E+10 | 0.530786E+09 | 0.551228E+09 | 0.00 | 0.00 |
October | 0.736664E+09 | 0.630751E+09 | 0.901231E+09 | 0.475534E+09 | 0.425696E+09 | 0.00 | 0.00 |
November | 0.331928E+09 | 0.974033E+09 | 0.586899E+09 | 0.292740E+09 | 0.294159E+09 | 0.00 | 0.00 |
December | 0.304158E+09 | 0.145990E+10 | 0.570618E+09 | 0.367081E+09 | 0.203537E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.951000E+10 | 0.839741E+10 | 0.112717E+11 | 0.525794E+10 | 0.601379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.304158E+09 | 0.133201E+09 | 0.570618E+09 | 0.292740E+09 | 0.203537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136083E+10 | 0.159453E+10 | 0.122942E+10 | 0.530786E+09 | 0.730702E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39278012.72 | 0.177199E+10 | 0.365226E+09 | 0.119692E+09 | 0.245534E+09 | 0.00 | 0.00 |
February | 0.107116E+09 | 0.125592E+10 | 0.435023E+09 | 0.154586E+09 | 0.280437E+09 | 0.00 | 0.00 |
March | 0.314818E+09 | 0.901328E+09 | 0.667206E+09 | 0.209551E+09 | 0.457655E+09 | 0.00 | 0.00 |
April | 0.567126E+09 | 0.585072E+09 | 0.779757E+09 | 0.273121E+09 | 0.506636E+09 | 0.00 | 0.00 |
May | 0.953465E+09 | 0.299758E+09 | 0.102389E+10 | 0.364038E+09 | 0.659854E+09 | 0.00 | 0.00 |
June | 0.119863E+10 | 0.168392E+09 | 0.110334E+10 | 0.399169E+09 | 0.704169E+09 | 0.00 | 0.00 |
July | 0.128774E+10 | 0.131337E+09 | 0.113471E+10 | 0.433385E+09 | 0.701329E+09 | 0.00 | 0.00 |
August | 0.109024E+10 | 0.167732E+09 | 0.955542E+09 | 0.332608E+09 | 0.622934E+09 | 0.00 | 0.00 |
September | 0.806270E+09 | 0.341360E+09 | 0.804173E+09 | 0.313854E+09 | 0.490319E+09 | 0.00 | 0.00 |
October | 0.326707E+09 | 0.631586E+09 | 0.542318E+09 | 0.180140E+09 | 0.362178E+09 | 0.00 | 0.00 |
November | 78631325.13 | 0.103554E+10 | 0.321895E+09 | 80412113.67 | 0.241483E+09 | 0.00 | 0.00 |
December | 30408908.94 | 0.158543E+10 | 0.247273E+09 | 84600328.40 | 0.162673E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.680043E+10 | 0.887546E+10 | 0.838036E+10 | 0.294516E+10 | 0.543520E+10 | 0.00 | 0.00 |
Minimum of Months | 30408908.94 | 0.131337E+09 | 0.247273E+09 | 80412113.67 | 0.162673E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128774E+10 | 0.177199E+10 | 0.113471E+10 | 0.433385E+09 | 0.704169E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470189E+09 | 0.196267E+10 | 0.918002E+09 | 0.541992E+09 | 0.376010E+09 | 0.00 | 0.00 |
February | 0.518604E+09 | 0.140475E+10 | 0.915899E+09 | 0.522880E+09 | 0.393019E+09 | 0.00 | 0.00 |
March | 0.590571E+09 | 0.112846E+10 | 0.972071E+09 | 0.382798E+09 | 0.589274E+09 | 0.00 | 0.00 |
April | 0.620363E+09 | 0.746728E+09 | 0.900763E+09 | 0.291055E+09 | 0.609707E+09 | 0.00 | 0.00 |
May | 0.756097E+09 | 0.375032E+09 | 0.918743E+09 | 0.169058E+09 | 0.749685E+09 | 0.00 | 0.00 |
June | 0.931172E+09 | 0.199519E+09 | 0.924524E+09 | 0.140489E+09 | 0.784035E+09 | 0.00 | 0.00 |
July | 0.102096E+10 | 0.153773E+09 | 0.961416E+09 | 0.168104E+09 | 0.793313E+09 | 0.00 | 0.00 |
August | 0.105718E+10 | 0.203647E+09 | 0.957681E+09 | 0.222633E+09 | 0.735048E+09 | 0.00 | 0.00 |
September | 0.984406E+09 | 0.425185E+09 | 0.976296E+09 | 0.376394E+09 | 0.599902E+09 | 0.00 | 0.00 |
October | 0.849637E+09 | 0.784836E+09 | 0.100167E+10 | 0.511928E+09 | 0.489739E+09 | 0.00 | 0.00 |
November | 0.449195E+09 | 0.121281E+10 | 0.716270E+09 | 0.367971E+09 | 0.348299E+09 | 0.00 | 0.00 |
December | 0.460326E+09 | 0.181226E+10 | 0.732636E+09 | 0.489548E+09 | 0.243088E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870870E+10 | 0.104097E+11 | 0.108960E+11 | 0.418485E+10 | 0.671112E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449195E+09 | 0.153773E+09 | 0.716270E+09 | 0.140489E+09 | 0.243088E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105718E+10 | 0.196267E+10 | 0.100167E+10 | 0.541992E+09 | 0.793313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336817E+09 | 0.160887E+10 | 0.748923E+09 | 0.431769E+09 | 0.317154E+09 | 0.00 | 0.00 |
February | 0.463436E+09 | 0.116603E+10 | 0.829993E+09 | 0.491486E+09 | 0.338508E+09 | 0.00 | 0.00 |
March | 0.594404E+09 | 0.896701E+09 | 0.930804E+09 | 0.410261E+09 | 0.520543E+09 | 0.00 | 0.00 |
April | 0.894343E+09 | 0.603125E+09 | 0.108391E+10 | 0.523081E+09 | 0.560830E+09 | 0.00 | 0.00 |
May | 0.977911E+09 | 0.326086E+09 | 0.106604E+10 | 0.388045E+09 | 0.678000E+09 | 0.00 | 0.00 |
June | 0.122073E+10 | 0.182656E+09 | 0.113998E+10 | 0.423841E+09 | 0.716144E+09 | 0.00 | 0.00 |
July | 0.140238E+10 | 0.144150E+09 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
August | 0.131696E+10 | 0.184387E+09 | 0.117778E+10 | 0.498813E+09 | 0.678963E+09 | 0.00 | 0.00 |
September | 0.109309E+10 | 0.355217E+09 | 0.106306E+10 | 0.521548E+09 | 0.541516E+09 | 0.00 | 0.00 |
October | 0.787433E+09 | 0.643073E+09 | 0.933913E+09 | 0.503412E+09 | 0.430500E+09 | 0.00 | 0.00 |
November | 0.365432E+09 | 0.986643E+09 | 0.607981E+09 | 0.312225E+09 | 0.295756E+09 | 0.00 | 0.00 |
December | 0.332648E+09 | 0.147800E+10 | 0.586970E+09 | 0.383812E+09 | 0.203158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.978559E+10 | 0.857495E+10 | 0.114307E+11 | 0.541366E+10 | 0.601701E+10 | 0.00 | 0.00 |
Minimum of Months | 0.332648E+09 | 0.144150E+09 | 0.586970E+09 | 0.312225E+09 | 0.203158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140238E+10 | 0.160887E+10 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59929416.06 | 0.180418E+10 | 0.365289E+09 | 0.118770E+09 | 0.246519E+09 | 0.00 | 0.00 |
February | 0.159018E+09 | 0.128727E+10 | 0.468835E+09 | 0.189524E+09 | 0.279310E+09 | 0.00 | 0.00 |
March | 0.312339E+09 | 0.925051E+09 | 0.647849E+09 | 0.189199E+09 | 0.458650E+09 | 0.00 | 0.00 |
April | 0.691629E+09 | 0.601145E+09 | 0.875972E+09 | 0.357501E+09 | 0.518470E+09 | 0.00 | 0.00 |
May | 0.881690E+09 | 0.317969E+09 | 0.954978E+09 | 0.306265E+09 | 0.648713E+09 | 0.00 | 0.00 |
June | 0.117358E+10 | 0.175053E+09 | 0.108114E+10 | 0.386683E+09 | 0.694454E+09 | 0.00 | 0.00 |
July | 0.132526E+10 | 0.138996E+09 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
August | 0.115865E+10 | 0.179942E+09 | 0.101053E+10 | 0.378018E+09 | 0.632509E+09 | 0.00 | 0.00 |
September | 0.794515E+09 | 0.352407E+09 | 0.784995E+09 | 0.304438E+09 | 0.480556E+09 | 0.00 | 0.00 |
October | 0.391098E+09 | 0.653013E+09 | 0.574706E+09 | 0.207776E+09 | 0.366931E+09 | 0.00 | 0.00 |
November | 0.119246E+09 | 0.105322E+10 | 0.342759E+09 | 99723118.67 | 0.243036E+09 | 0.00 | 0.00 |
December | 58741613.05 | 0.160272E+10 | 0.263360E+09 | 0.101100E+09 | 0.162260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.712569E+10 | 0.909096E+10 | 0.853694E+10 | 0.309899E+10 | 0.543795E+10 | 0.00 | 0.00 |
Minimum of Months | 58741613.05 | 0.138996E+09 | 0.263360E+09 | 99723118.67 | 0.162260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132526E+10 | 0.180418E+10 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515374E+09 | 0.817608E+09 | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.00 | 0.00 |
February | 0.508258E+09 | 0.599447E+09 | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.00 | 0.00 |
March | 0.466634E+09 | 0.475483E+09 | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.00 | 0.00 |
April | 0.405198E+09 | 0.321128E+09 | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.00 | 0.00 |
May | 0.373354E+09 | 0.171035E+09 | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.00 | 0.00 |
June | 0.409297E+09 | 92786363.13 | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.00 | 0.00 |
July | 0.467413E+09 | 70656228.93 | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.00 | 0.00 |
August | 0.542969E+09 | 92695919.54 | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.00 | 0.00 |
September | 0.622859E+09 | 0.185644E+09 | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.00 | 0.00 |
October | 0.652969E+09 | 0.337574E+09 | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.00 | 0.00 |
November | 0.406519E+09 | 0.506306E+09 | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.00 | 0.00 |
December | 0.469199E+09 | 0.754012E+09 | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.584004E+10 | 0.442438E+10 | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.373354E+09 | 70656228.93 | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.652969E+09 | 0.817608E+09 | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.494909E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 1669237.51 | 0.359022E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.132989E+09 | 0.275164E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.413694E+09 | 0.178951E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.987124E+09 | 0.930824E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.152425E+10 | 0.546857E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.159125E+10 | 0.445083E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.138912E+10 | 0.566683E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.783545E+09 | 0.107437E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.187595E+09 | 0.196235E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 30488744.73 | 0.305596E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.449152E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.704172E+10 | 0.261541E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.445083E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159125E+10 | 0.494909E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.504287E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 914370.73 | 0.366873E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.118883E+09 | 0.282963E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.391114E+09 | 0.184514E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.946923E+09 | 0.962612E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.148670E+10 | 0.569301E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.155327E+10 | 0.465135E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.135253E+10 | 0.591391E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.755340E+09 | 0.111216E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.167952E+09 | 0.202402E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 25229791.48 | 0.313882E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.459364E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.679885E+10 | 0.268434E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.465135E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.155327E+10 | 0.504287E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.332374E+09 | 0.315557E+10 | 0.111464E+10 | 0.552562E+09 | 0.562081E+09 | 0.00 | 0.00 |
February | 0.536150E+09 | 0.220814E+10 | 0.123187E+10 | 0.611366E+09 | 0.620503E+09 | 0.00 | 0.00 |
March | 0.991084E+09 | 0.181052E+10 | 0.161839E+10 | 0.640478E+09 | 0.977909E+09 | 0.00 | 0.00 |
April | 0.148158E+10 | 0.122369E+10 | 0.176864E+10 | 0.712232E+09 | 0.105641E+10 | 0.00 | 0.00 |
May | 0.227082E+10 | 0.670123E+09 | 0.216042E+10 | 0.810402E+09 | 0.135001E+10 | 0.00 | 0.00 |
June | 0.275256E+10 | 0.400125E+09 | 0.226721E+10 | 0.836098E+09 | 0.143111E+10 | 0.00 | 0.00 |
July | 0.300611E+10 | 0.313650E+09 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
August | 0.266830E+10 | 0.392235E+09 | 0.207979E+10 | 0.786509E+09 | 0.129328E+10 | 0.00 | 0.00 |
September | 0.216428E+10 | 0.725243E+09 | 0.188764E+10 | 0.845288E+09 | 0.104235E+10 | 0.00 | 0.00 |
October | 0.118892E+10 | 0.129243E+10 | 0.144467E+10 | 0.656187E+09 | 0.788485E+09 | 0.00 | 0.00 |
November | 0.428808E+09 | 0.197576E+10 | 0.909504E+09 | 0.373447E+09 | 0.536057E+09 | 0.00 | 0.00 |
December | 0.283468E+09 | 0.295434E+10 | 0.818534E+09 | 0.452039E+09 | 0.366494E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181045E+11 | 0.171218E+11 | 0.196673E+11 | 0.820941E+10 | 0.114578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283468E+09 | 0.313650E+09 | 0.818534E+09 | 0.373447E+09 | 0.366494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300611E+10 | 0.315557E+10 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111156E+10 | 0.346390E+10 | 0.188144E+10 | 0.116852E+10 | 0.712925E+09 | 0.00 | 0.00 |
February | 0.118607E+10 | 0.246478E+10 | 0.186272E+10 | 0.112731E+10 | 0.735414E+09 | 0.00 | 0.00 |
March | 0.122630E+10 | 0.202862E+10 | 0.191002E+10 | 0.825297E+09 | 0.108472E+10 | 0.00 | 0.00 |
April | 0.119981E+10 | 0.137406E+10 | 0.173371E+10 | 0.625835E+09 | 0.110787E+10 | 0.00 | 0.00 |
May | 0.132763E+10 | 0.728470E+09 | 0.170092E+10 | 0.353908E+09 | 0.134701E+10 | 0.00 | 0.00 |
June | 0.156154E+10 | 0.421916E+09 | 0.167632E+10 | 0.273554E+09 | 0.140276E+10 | 0.00 | 0.00 |
July | 0.172955E+10 | 0.345847E+09 | 0.176562E+10 | 0.341282E+09 | 0.142433E+10 | 0.00 | 0.00 |
August | 0.186707E+10 | 0.437943E+09 | 0.180735E+10 | 0.474802E+09 | 0.133254E+10 | 0.00 | 0.00 |
September | 0.187975E+10 | 0.816021E+09 | 0.191424E+10 | 0.811322E+09 | 0.110292E+10 | 0.00 | 0.00 |
October | 0.174923E+10 | 0.142725E+10 | 0.201329E+10 | 0.110370E+10 | 0.909592E+09 | 0.00 | 0.00 |
November | 0.978538E+09 | 0.217088E+10 | 0.144524E+10 | 0.793333E+09 | 0.651906E+09 | 0.00 | 0.00 |
December | 0.105547E+10 | 0.322833E+10 | 0.151317E+10 | 0.105545E+10 | 0.457722E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168725E+11 | 0.189080E+11 | 0.212240E+11 | 0.895431E+10 | 0.122697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.978538E+09 | 0.345847E+09 | 0.144524E+10 | 0.273554E+09 | 0.457722E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187975E+10 | 0.346390E+10 | 0.201329E+10 | 0.116852E+10 | 0.142433E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.510464E+11 | -.799019E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.153842E+10 | 58.97 | 0.00 | 0.00 |
February | 0.477406E+11 | -.736361E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.143823E+10 | 58.95 | 0.00 | 0.00 |
March | 0.520048E+11 | -.807781E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.155071E+10 | 58.97 | 0.00 | 0.00 |
April | 0.470335E+11 | -.750995E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151819E+10 | 58.97 | 0.00 | 0.00 |
May | 0.436091E+11 | -.729710E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.156959E+10 | 58.97 | 0.00 | 0.00 |
June | 0.371801E+11 | -.659567E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.152016E+10 | 59.06 | 0.00 | 0.00 |
July | 0.342463E+11 | -.642864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.156925E+10 | 59.11 | 0.00 | 0.00 |
August | 0.324301E+11 | -.626280E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154260E+10 | 59.18 | 0.00 | 0.00 |
September | 0.321899E+11 | -.613907E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.145712E+10 | 59.15 | 0.00 | 0.00 |
October | 0.366272E+11 | -.665896E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147426E+10 | 59.09 | 0.00 | 0.00 |
November | 0.402555E+11 | -.689013E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.142874E+10 | 59.00 | 0.00 | 0.00 |
December | 0.468430E+11 | -.760616E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147925E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.501206E+12 | -.848201E+12 | 8760.00 | -.180865E+11 | 59.03 | |||||
Minimum of Months | 0.321899E+11 | -.807781E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.156959E+10 | 58.95 | 0.00 | 0.00 |
Maximum of Months | 0.520048E+11 | -.613907E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.142874E+10 | 59.18 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770820E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165425238.7 | 81.21 | 0.00 | 0.00 |
February | 0.696665E+10 | -.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -150676724.9 | 81.21 | 0.00 | 0.00 |
March | 0.770482E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162009833.8 | 81.21 | 0.00 | 0.00 |
April | 0.746515E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156558168.4 | 81.21 | 0.00 | 0.00 |
May | 0.770471E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161908971.2 | 81.21 | 0.00 | 0.00 |
June | 0.745759E+10 | -.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157046222.5 | 81.21 | 0.00 | 0.00 |
July | 0.771336E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162514994.4 | 81.21 | 0.00 | 0.00 |
August | 0.770521E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162391505.7 | 81.21 | 0.00 | 0.00 |
September | 0.746537E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156768635.5 | 81.21 | 0.00 | 0.00 |
October | 0.770444E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161664073.3 | 81.21 | 0.00 | 0.00 |
November | 0.744974E+10 | -.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157293945.7 | 81.21 | 0.00 | 0.00 |
December | 0.771338E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162523129.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907586E+11 | -.888418E+11 | 8760.00 | -.191678E+10 | 81.21 | |||||
Minimum of Months | 0.696665E+10 | -.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165425238.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771338E+10 | -.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150676724.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.795290E+11 | -.783549E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117415E+10 | 61.11 | 0.00 | 0.00 |
February | 0.719854E+11 | -.709004E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108501E+10 | 60.70 | 0.00 | 0.00 |
March | 0.796075E+11 | -.784325E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117503E+10 | 60.84 | 0.00 | 0.00 |
April | 0.767519E+11 | -.755805E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.117147E+10 | 61.58 | 0.00 | 0.00 |
May | 0.788400E+11 | -.775978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124221E+10 | 62.61 | 0.00 | 0.00 |
June | 0.758247E+11 | -.745930E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.123174E+10 | 63.69 | 0.00 | 0.00 |
July | 0.779701E+11 | -.766747E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129537E+10 | 64.53 | 0.00 | 0.00 |
August | 0.777921E+11 | -.765066E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128551E+10 | 64.91 | 0.00 | 0.00 |
September | 0.753646E+11 | -.741512E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.121343E+10 | 64.72 | 0.00 | 0.00 |
October | 0.781926E+11 | -.769808E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121172E+10 | 64.01 | 0.00 | 0.00 |
November | 0.761165E+11 | -.749685E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.114804E+10 | 63.02 | 0.00 | 0.00 |
December | 0.791412E+11 | -.779857E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.115548E+10 | 61.91 | 0.00 | 0.00 |
Annual Sum or Average | 0.927116E+12 | -.912727E+12 | 8760.00 | -.143892E+11 | 62.81 | |||||
Minimum of Months | 0.719854E+11 | -.784325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129537E+10 | 60.70 | 0.00 | 0.00 |
Maximum of Months | 0.796075E+11 | -.709004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108501E+10 | 64.91 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.93 | 0.93 | 01-JAN-09:39 | 5932.51 | 37.80 | 207.17 | 248.17 | 3985.16 | 37.27 | 208.17 | 216.33 |
February | 226.83 | 0.93 | 0.93 | 01-FEB-07:49 | 7191.88 | 37.61 | 221.17 | 256.17 | 1525.40 | 28.83 | 206.83 | 230.50 |
March | 334.33 | 0.93 | 0.93 | 01-MAR-07:40 | 4015.40 | 25.90 | 188.83 | 328.67 | 693.16 | 22.05 | 229.33 | 279.50 |
April | 285.17 | 0.93 | 0.93 | 01-APR-06:49 | 1486.10 | 20.59 | 99.50 | 348.17 | 606.48 | 22.33 | 217.50 | 274.83 |
May | 428.67 | 0.93 | 0.93 | 01-MAY-05:00 | 1222.64 | 19.68 | 45.83 | 397.50 | 479.02 | 21.41 | 269.67 | 325.00 |
June | 400.67 | 0.93 | 0.93 | 01-JUN-05:19 | 1245.24 | 20.07 | 91.17 | 398.67 | 499.27 | 21.81 | 275.17 | 328.00 |
July | 414.00 | 0.93 | 0.93 | 01-JUL-05:40 | 1280.53 | 20.41 | 99.17 | 408.33 | 517.12 | 22.15 | 303.50 | 338.50 |
August | 410.83 | 0.93 | 0.93 | 01-AUG-05:00 | 1435.96 | 20.15 | 101.50 | 379.83 | 563.74 | 21.87 | 297.33 | 324.67 |
September | 326.50 | 0.93 | 0.93 | 01-SEP-06:10 | 2431.46 | 22.83 | 160.67 | 334.83 | 669.68 | 22.47 | 243.67 | 286.83 |
October | 325.17 | 0.93 | 0.93 | 01-OCT-06:40 | 6240.09 | 33.55 | 295.17 | 308.67 | 849.06 | 23.47 | 230.33 | 276.67 |
November | 254.83 | 0.93 | 0.93 | 01-NOV-07:40 | 4242.42 | 33.07 | 238.17 | 250.50 | 2039.70 | 30.51 | 220.50 | 218.33 |
December | 186.17 | 0.93 | 0.93 | 01-DEC-07:00 | 5142.07 | 37.90 | 180.17 | 224.50 | 4567.17 | 38.88 | 180.83 | 171.83 |
Annual Sum or Average | 3807.33 | 0.93 | 3065.82 | 25.79 | 1928.50 | 3884.00 | 1134.66 | 24.77 | 2882.83 | 3271.00 | ||
Minimum of Months | 186.17 | 0.93 | 0.93 | 1222.64 | 19.68 | 45.83 | 224.50 | 479.02 | 21.41 | 180.83 | 171.83 | |
Maximum of Months | 428.67 | 0.93 | 0.93 | 7191.88 | 37.90 | 295.17 | 408.33 | 4567.17 | 38.88 | 303.50 | 338.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.62 | 0.61 | 01-JAN-09:39 | 6416.74 | 37.89 | 207.17 | 257.50 | 4468.49 | 37.25 | 203.17 | 234.83 |
February | 226.83 | 0.62 | 0.61 | 01-FEB-07:49 | 7668.71 | 37.67 | 221.50 | 263.83 | 1998.22 | 28.57 | 195.83 | 247.50 |
March | 334.33 | 0.62 | 0.61 | 01-MAR-07:40 | 4362.67 | 26.14 | 195.17 | 340.50 | 1037.25 | 22.20 | 226.83 | 309.17 |
April | 285.17 | 0.62 | 0.61 | 01-APR-06:40 | 1820.93 | 20.83 | 107.50 | 360.33 | 940.22 | 22.42 | 217.17 | 327.50 |
May | 428.67 | 0.62 | 0.61 | 01-MAY-05:49 | 1443.82 | 20.27 | 102.67 | 412.17 | 699.35 | 21.81 | 287.17 | 370.83 |
June | 400.67 | 0.63 | 0.61 | 01-JUN-05:10 | 1465.40 | 20.64 | 150.67 | 412.83 | 718.58 | 22.19 | 300.67 | 376.33 |
July | 414.00 | 0.62 | 0.61 | 01-JUL-05:40 | 1516.01 | 20.93 | 163.67 | 422.83 | 751.71 | 22.48 | 323.50 | 387.00 |
August | 410.83 | 0.63 | 0.61 | 01-AUG-05:49 | 1695.83 | 20.61 | 145.33 | 392.50 | 822.58 | 22.16 | 312.67 | 362.00 |
September | 326.50 | 0.62 | 0.61 | 01-SEP-05:00 | 2782.69 | 23.03 | 160.17 | 344.17 | 1019.54 | 22.56 | 254.67 | 316.00 |
October | 325.17 | 0.62 | 0.61 | 01-OCT-06:40 | 6619.08 | 33.71 | 297.00 | 315.17 | 1228.11 | 23.51 | 227.83 | 295.67 |
November | 254.83 | 0.62 | 0.61 | 01-NOV-07:30 | 4569.71 | 33.19 | 240.00 | 259.50 | 2367.10 | 30.56 | 224.67 | 238.50 |
December | 186.17 | 0.62 | 0.61 | 01-DEC-07:49 | 5593.27 | 38.00 | 180.33 | 235.67 | 5014.66 | 38.95 | 180.83 | 205.33 |
Annual Sum or Average | 3807.33 | 0.62 | 3385.22 | 26.12 | 2171.17 | 4017.00 | 1452.73 | 24.95 | 2955.00 | 3670.67 | ||
Minimum of Months | 186.17 | 0.62 | 0.61 | 1443.82 | 20.27 | 102.67 | 235.67 | 699.35 | 21.81 | 180.83 | 205.33 | |
Maximum of Months | 428.67 | 0.63 | 0.61 | 7668.71 | 38.00 | 297.00 | 422.83 | 5014.66 | 38.95 | 323.50 | 387.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.82 | 0.80 | 01-JAN-09:39 | 426.55 | 15.27 | 0.00 | 228.33 | 208.04 | 18.77 | 0.17 | 114.83 |
February | 226.83 | 0.82 | 0.80 | 01-FEB-08:30 | 437.85 | 15.51 | 0.00 | 239.83 | 215.46 | 18.96 | 0.00 | 140.17 |
March | 334.33 | 0.81 | 0.80 | 01-MAR-07:40 | 615.19 | 16.80 | 0.00 | 327.00 | 275.71 | 20.02 | 3.33 | 255.17 |
April | 285.17 | 0.81 | 0.80 | 01-APR-06:49 | 699.12 | 17.97 | 0.00 | 358.67 | 332.82 | 21.19 | 105.17 | 288.50 |
May | 428.67 | 0.80 | 0.80 | 01-MAY-05:40 | 825.64 | 18.05 | 4.17 | 419.67 | 360.79 | 22.07 | 183.33 | 379.67 |
June | 400.67 | 0.81 | 0.80 | 01-JUN-04:00 | 1002.05 | 21.06 | 66.83 | 421.83 | 464.56 | 24.14 | 281.33 | 392.83 |
July | 414.00 | 0.80 | 0.80 | 01-JUL-05:40 | 936.54 | 20.61 | 53.83 | 429.67 | 433.82 | 23.29 | 275.00 | 400.67 |
August | 410.83 | 0.81 | 0.80 | 01-AUG-05:40 | 770.21 | 18.13 | 4.50 | 396.17 | 349.93 | 21.52 | 172.00 | 364.17 |
September | 326.50 | 0.81 | 0.80 | 01-SEP-05:00 | 618.06 | 17.50 | 0.00 | 338.50 | 297.04 | 20.70 | 39.00 | 280.00 |
October | 325.17 | 0.81 | 0.80 | 01-OCT-06:00 | 501.03 | 15.99 | 0.00 | 295.17 | 231.33 | 19.31 | 0.00 | 204.17 |
November | 254.83 | 0.81 | 0.80 | 01-NOV-07:40 | 438.96 | 15.06 | 0.00 | 235.00 | 194.35 | 18.37 | 0.00 | 118.33 |
December | 186.17 | 0.83 | 0.80 | 01-DEC-08:20 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 |
Annual Sum or Average | 3807.33 | 0.81 | 679.79 | 17.60 | 129.33 | 3883.17 | 313.86 | 20.92 | 1059.33 | 2972.67 | ||
Minimum of Months | 186.17 | 0.80 | 0.80 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 | |
Maximum of Months | 428.67 | 0.83 | 0.80 | 1002.05 | 21.06 | 66.83 | 429.67 | 464.56 | 24.14 | 281.33 | 400.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.82 | 0.80 | 01-JAN-09:39 | 426.55 | 15.27 | 0.00 | 228.33 | 208.04 | 18.77 | 0.17 | 114.83 |
February | 226.83 | 0.82 | 0.80 | 01-FEB-08:30 | 437.85 | 15.51 | 0.00 | 239.83 | 215.46 | 18.96 | 0.00 | 140.17 |
March | 334.33 | 0.81 | 0.80 | 01-MAR-07:40 | 615.19 | 16.80 | 0.00 | 327.00 | 275.71 | 20.02 | 3.33 | 255.17 |
April | 285.17 | 0.81 | 0.80 | 01-APR-06:49 | 699.12 | 17.97 | 0.00 | 358.67 | 332.82 | 21.19 | 105.17 | 288.50 |
May | 428.67 | 0.80 | 0.80 | 01-MAY-05:40 | 825.64 | 18.05 | 4.17 | 419.67 | 360.79 | 22.07 | 183.33 | 379.67 |
June | 400.67 | 0.81 | 0.80 | 01-JUN-04:00 | 1002.05 | 21.06 | 66.83 | 421.83 | 464.56 | 24.14 | 281.33 | 392.83 |
July | 414.00 | 0.80 | 0.80 | 01-JUL-05:40 | 936.54 | 20.61 | 53.83 | 429.67 | 433.82 | 23.29 | 275.00 | 400.67 |
August | 410.83 | 0.81 | 0.80 | 01-AUG-05:40 | 770.21 | 18.13 | 4.50 | 396.17 | 349.93 | 21.52 | 172.00 | 364.17 |
September | 326.50 | 0.81 | 0.80 | 01-SEP-05:00 | 618.06 | 17.50 | 0.00 | 338.50 | 297.04 | 20.70 | 39.00 | 280.00 |
October | 325.17 | 0.81 | 0.80 | 01-OCT-06:00 | 501.03 | 15.99 | 0.00 | 295.17 | 231.33 | 19.31 | 0.00 | 204.17 |
November | 254.83 | 0.81 | 0.80 | 01-NOV-07:40 | 438.96 | 15.06 | 0.00 | 235.00 | 194.35 | 18.37 | 0.00 | 118.33 |
December | 186.17 | 0.83 | 0.80 | 01-DEC-08:20 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 |
Annual Sum or Average | 3807.33 | 0.81 | 679.79 | 17.60 | 129.33 | 3883.17 | 313.86 | 20.92 | 1059.33 | 2972.67 | ||
Minimum of Months | 186.17 | 0.80 | 0.80 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 | |
Maximum of Months | 428.67 | 0.83 | 0.80 | 1002.05 | 21.06 | 66.83 | 429.67 | 464.56 | 24.14 | 281.33 | 400.67 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237122E+10 | 8217.50 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406190E+10 | 8648.99 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7485503.38 | 1158.76 | 19-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103427E+10 | 5704.61 | 18-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149377E+10 | 5702.67 | 29-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103128E+10 | 3929.34 | 26-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158095E+09 | 2519.64 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151420E+09 | 8044.66 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103094E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406190E+10 | 8648.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594723E+10 | 4772.76 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430020E+10 | 5033.66 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256370E+10 | 2614.45 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152443E+10 | 2159.29 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466850E+09 | 1668.12 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220055E+09 | 1539.71 | 02-JUN-02:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105282E+09 | 1288.74 | 23-JUL-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68115319.60 | 1378.64 | 07-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.380619E+09 | 2040.93 | 27-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.975544E+09 | 1917.31 | 03-OCT-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287837E+10 | 4668.76 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456096E+10 | 3328.39 | 09-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239914E+11 | |||||||
Minimum of Months | 68115319.60 | 1288.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594723E+10 | 5033.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.949323E+09 | 1665.96 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748186E+09 | 1754.96 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54341987.22 | 456.83 | 01-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11481887.27 | 324.62 | 03-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186336E+09 | 1630.38 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263078E+09 | 780.76 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221275E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.949323E+09 | 1754.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269733E+10 | 2408.49 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193635E+10 | 2538.95 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722216E+09 | 1149.33 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228778E+09 | 925.37 | 06-APR-15:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 835862.53 | 118.30 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806520E+09 | 2356.42 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156885E+10 | 1532.72 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.796089E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269733E+10 | 2538.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208883E+10 | 1502.02 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150617E+10 | 1584.10 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763559E+09 | 812.81 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316915E+09 | 574.37 | 03-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6267770.03 | 427.51 | 01-MAY-16:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2692527.77 | 148.85 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39536934.89 | 432.89 | 28-OCT-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.782269E+09 | 1469.31 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146214E+10 | 1046.38 | 12-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696838E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208883E+10 | 1584.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372165E+10 | 11312.74 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385580E+10 | 11906.73 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464025E+09 | 8329.38 | 24-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649392E+09 | 8243.59 | 19-APR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128298E+10 | 8100.97 | 06-MAY-02:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.242517E+10 | 8205.08 | 02-JUN-02:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325067E+10 | 6932.57 | 07-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.289438E+10 | 8205.53 | 07-AUG-02:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165328E+10 | 8234.61 | 05-SEP-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408005E+09 | 8369.83 | 25-OCT-01:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902936E+09 | 11074.79 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.553984E+09 | 3426.00 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220623E+11 | |||||||
Minimum of Months | 0.408005E+09 | 3426.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.385580E+10 | 11906.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.922548E+10 | 14141.25 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672461E+10 | 14904.81 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162968E+10 | 5426.59 | 01-MAR-11:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.890559E+09 | 5122.44 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42899356.75 | 1844.70 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50555368.28 | 4444.19 | 02-JUN-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51398265.80 | 1554.27 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15221906.09 | 1102.94 | 31-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70030670.21 | 5836.35 | 27-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167396E+09 | 5212.47 | 04-OCT-08:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272252E+10 | 13836.39 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.477640E+10 | 8684.40 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263667E+11 | |||||||
Minimum of Months | 15221906.09 | 1102.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.922548E+10 | 14904.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149445E+11 | 33945.39 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134410E+11 | 35759.02 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525086E+09 | 8077.09 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124280E+09 | 5388.78 | 03-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268299E+10 | 33220.29 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326502E+10 | 15390.75 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349828E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149445E+11 | 35759.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.927486E+10 | 8245.44 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654393E+10 | 8270.88 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362793E+10 | 8244.18 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165227E+10 | 8222.57 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.228711E+09 | 7653.31 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96873781.89 | 3475.02 | 11-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5288059.08 | 3434.23 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7406074.16 | 2652.88 | 09-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409528E+09 | 7796.50 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144029E+10 | 7915.78 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443325E+10 | 8243.64 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752384E+10 | 8244.76 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352442E+11 | |||||||
Minimum of Months | 5288059.08 | 2652.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.927486E+10 | 8270.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106167E+11 | 8211.27 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.760186E+10 | 8336.14 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420707E+10 | 8209.95 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183967E+10 | 8188.42 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266537E+09 | 7641.50 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102081E+09 | 3655.44 | 11-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5486497.94 | 3526.52 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8465915.20 | 3027.04 | 09-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.509705E+09 | 7788.74 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194928E+10 | 7943.76 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.516621E+10 | 8209.43 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.859790E+10 | 8210.57 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408709E+11 | |||||||
Minimum of Months | 5486497.94 | 3027.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106167E+11 | 8336.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.284035E+11 | 44632.40 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163826E+11 | 45505.34 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555370E+10 | 17627.97 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.932791E+09 | 12501.98 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777817E+10 | 43658.76 | 26-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182038E+11 | 29024.74 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772546E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284035E+11 | 45505.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489901E+11 | 44712.40 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355884E+11 | 46508.88 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141367E+11 | 44021.90 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452771E+10 | 42794.36 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172846E+09 | 27655.87 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41558835.92 | 19595.42 | 15-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21640426.56 | 22429.31 | 10-JUL-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33957126.85 | 26925.14 | 30-AUG-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.359463E+09 | 24713.11 | 30-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299910E+10 | 41059.16 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181203E+11 | 44207.06 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348989E+11 | 44211.41 | 23-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159891E+12 | |||||||
Minimum of Months | 21640426.56 | 19595.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489901E+11 | 46508.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.924379E+10 | 7884.25 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658708E+10 | 8025.04 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356958E+10 | 7882.85 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177384E+10 | 7862.34 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189375E+09 | 3254.32 | 20-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80639287.38 | 2668.31 | 02-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5350178.22 | 2342.51 | 07-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10728821.30 | 2519.14 | 26-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381677E+09 | 7150.90 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144780E+10 | 7519.51 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445986E+10 | 7882.19 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756434E+10 | 7883.48 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353141E+11 | |||||||
Minimum of Months | 5350178.22 | 2342.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.924379E+10 | 8025.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105866E+11 | 7916.77 | 31-JAN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767651E+10 | 8122.59 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414904E+10 | 7877.92 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200014E+10 | 7857.43 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226807E+09 | 3040.47 | 21-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86019401.13 | 2597.22 | 02-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6067591.53 | 2300.90 | 07-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14966159.31 | 2462.05 | 26-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471586E+09 | 7161.54 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194769E+10 | 7546.24 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520990E+10 | 7877.38 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865990E+10 | 7878.56 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410353E+11 | |||||||
Minimum of Months | 6067591.53 | 2300.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105866E+11 | 8122.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215847E+11 | 14041.02 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165594E+11 | 14803.63 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102527E+11 | 8941.04 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584243E+10 | 7570.18 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196467E+10 | 6036.09 | 17-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.785594E+09 | 5220.21 | 05-JUN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.265192E+09 | 3524.30 | 23-JUL-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.262706E+09 | 4043.74 | 07-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168281E+10 | 7174.68 | 27-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524344E+10 | 7241.01 | 25-OCT-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120228E+11 | 13736.76 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174206E+11 | 9807.61 | 12-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938870E+11 | |||||||
Minimum of Months | 0.262706E+09 | 3524.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.215847E+11 | 14803.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.303487E+10 | 2376.62 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209119E+10 | 2396.10 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127550E+10 | 2376.18 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598237E+09 | 2369.99 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93272604.55 | 2228.61 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38916631.61 | 967.58 | 05-JUN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1517572.69 | 799.07 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2841024.07 | 683.54 | 09-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164651E+09 | 2278.41 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557883E+09 | 2309.95 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153316E+10 | 2376.01 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252947E+10 | 2376.40 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119215E+11 | |||||||
Minimum of Months | 1517572.69 | 683.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303487E+10 | 2396.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342303E+10 | 2375.30 | 31-JAN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241335E+10 | 2422.68 | 02-FEB-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146639E+10 | 2367.58 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660258E+09 | 2361.42 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106734E+09 | 2226.83 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40989895.54 | 1013.80 | 05-JUN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1633369.88 | 726.44 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3308196.22 | 719.79 | 09-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199873E+09 | 2277.18 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.726621E+09 | 2301.69 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176356E+10 | 2367.42 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285388E+10 | 2367.83 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136596E+11 | |||||||
Minimum of Months | 1633369.88 | 719.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342303E+10 | 2422.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104524E+11 | 10287.65 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679015E+10 | 10338.94 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400830E+10 | 10285.47 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210131E+10 | 10259.45 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208196E+09 | 8274.75 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69859305.89 | 2788.73 | 06-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4328004.97 | 2981.83 | 10-JUL-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9321227.05 | 2684.65 | 01-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328299E+09 | 9630.37 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109176E+10 | 9748.33 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468795E+10 | 10284.75 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855324E+10 | 10286.69 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383051E+11 | |||||||
Minimum of Months | 4328004.97 | 2684.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104524E+11 | 10338.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392373E+10 | 12984.21 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421620E+10 | 13674.51 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540650E+09 | 12708.13 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26327239.75 | 1204.20 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870691E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421620E+10 | 13674.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394933E+10 | 13401.55 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421330E+10 | 14113.69 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538386E+09 | 13116.73 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870102E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421330E+10 | 14113.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245386E+10 | 8929.37 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267231E+10 | 9399.26 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 266116.64 | 887.06 | 24-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 127450.14 | 424.83 | 19-APR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 431492.55 | 1438.31 | 02-JUN-02:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17167.39 | 57.22 | 23-JUL-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 406844.66 | 1356.15 | 05-SEP-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1293529.53 | 2367.90 | 25-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348004E+09 | 8741.20 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 546972.62 | 284.56 | 10-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547727E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267231E+10 | 9399.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118666E+11 | 8956.98 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.848454E+10 | 9445.82 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422222E+10 | 5115.73 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182730E+10 | 3600.19 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91155601.75 | 1543.56 | 03-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7440723.06 | 862.31 | 06-JUN-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274846E+09 | 2688.42 | 27-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137191E+10 | 2750.76 | 03-OCT-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.519513E+10 | 8762.09 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875906E+10 | 6242.61 | 12-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421002E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118666E+11 | 9445.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255554E+12 | 316780.42 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166798E+12 | 330860.38 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.479304E+11 | 116008.10 | 05-MAR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185759E+11 | 109020.83 | 20-APR-22:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.963609E+10 | 81981.59 | 18-MAY-06:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.513846E+10 | 76439.04 | 03-JUN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.817499E+09 | 57878.55 | 24-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240104E+10 | 66209.27 | 07-AUG-02:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100596E+11 | 82513.51 | 15-SEP-06:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154867E+11 | 140589.01 | 19-OCT-21:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690719E+11 | 311028.86 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124365E+12 | 161728.59 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.725834E+12 | |||||||
Minimum of Months | 0.817499E+09 | 57878.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255554E+12 | 330860.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328701E+11 | 39125.72 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210404E+11 | 40983.23 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626738E+10 | 13278.21 | 06-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152675E+10 | 6753.90 | 03-APR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23924.55 | 0.39 | 30-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20331.40 | 0.39 | 08-JUN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19319.39 | 0.39 | 02-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26873.37 | 0.39 | 01-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6484317.86 | 737.42 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55810184.55 | 1912.95 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.875377E+10 | 38373.04 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175096E+11 | 19076.32 | 09-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.880304E+11 | |||||||
Minimum of Months | 19319.39 | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328701E+11 | 40983.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4000649.20 | 4000649.20 | 12308.88 | 12-JAN-16:02 | 12308.88 | 0.00 |
February | 0.00 | 0.00 | 86855857.76 | 86855857.76 | 13291.44 | 24-FEB-16:02 | 13291.44 | 0.00 |
March | 0.00 | 0.00 | 0.288729E+09 | 0.261555E+09 | 13701.84 | 25-MAR-15:01 | 13701.84 | 0.02 |
April | 0.00 | 0.00 | 0.174334E+10 | 0.127133E+10 | 14886.46 | 16-APR-08:62 | 11494.83 | 0.19 |
May | 0.00 | 0.00 | 0.275442E+10 | 0.168454E+10 | 15594.40 | 29-MAY-08:62 | 11316.90 | 0.47 |
June | 0.00 | 0.00 | 0.557001E+10 | 0.309554E+10 | 18710.98 | 26-JUN-08:62 | 11114.80 | 0.75 |
July | 0.00 | 0.00 | 0.718822E+10 | 0.387256E+10 | 17905.10 | 14-JUL-18:02 | 11444.87 | 0.86 |
August | 0.00 | 0.00 | 0.622088E+10 | 0.320581E+10 | 20310.06 | 03-AUG-08:61 | 10225.63 | 0.85 |
September | 0.00 | 0.00 | 0.365302E+10 | 0.222926E+10 | 15827.65 | 11-SEP-08:62 | 11115.51 | 0.52 |
October | 0.00 | 0.00 | 0.796054E+09 | 0.687280E+09 | 13693.30 | 19-OCT-15:02 | 13693.30 | 0.08 |
November | 0.00 | 0.00 | 0.147071E+09 | 0.138080E+09 | 13359.58 | 03-NOV-15:01 | 13359.58 | 0.01 |
December | 0.00 | 0.00 | 5254387.57 | 5254387.57 | 12106.14 | 02-DEC-16:01 | 12106.14 | 0.00 |
Annual Sum or Average | 0.284579E+11 | 0.165421E+11 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 4000649.20 | 4000649.20 | 12106.14 | 10225.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.718822E+10 | 0.387256E+10 | 20310.06 | 13701.84 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 440133.03 | 440133.03 | 2734.97 | 12-JAN-16:03 | 2734.97 | 0.00 |
February | 0.00 | 0.00 | 24302356.86 | 24302356.86 | 12236.62 | 24-FEB-16:02 | 12236.62 | 0.00 |
March | 0.00 | 0.00 | 0.121922E+09 | 0.109677E+09 | 13017.23 | 25-MAR-15:01 | 13017.23 | 0.01 |
April | 0.00 | 0.00 | 0.135779E+10 | 0.975426E+09 | 14567.00 | 16-APR-08:62 | 11367.94 | 0.16 |
May | 0.00 | 0.00 | 0.248425E+10 | 0.151010E+10 | 15339.07 | 29-MAY-08:62 | 11109.65 | 0.45 |
June | 0.00 | 0.00 | 0.537951E+10 | 0.298714E+10 | 18367.28 | 26-JUN-08:62 | 10956.85 | 0.73 |
July | 0.00 | 0.00 | 0.685031E+10 | 0.368230E+10 | 17807.35 | 17-JUL-18:02 | 11041.99 | 0.83 |
August | 0.00 | 0.00 | 0.559460E+10 | 0.284458E+10 | 20004.77 | 03-AUG-08:61 | 10041.77 | 0.80 |
September | 0.00 | 0.00 | 0.278194E+10 | 0.162316E+10 | 15251.09 | 11-SEP-08:62 | 11007.49 | 0.45 |
October | 0.00 | 0.00 | 0.363637E+09 | 0.307709E+09 | 12996.97 | 19-OCT-15:02 | 12996.97 | 0.04 |
November | 0.00 | 0.00 | 55787330.07 | 53583938.96 | 12793.34 | 03-NOV-15:01 | 12793.34 | 0.00 |
December | 0.00 | 0.00 | 584420.21 | 584420.21 | 2409.96 | 02-DEC-16:03 | 2409.96 | 0.00 |
Annual Sum or Average | 0.250151E+11 | 0.141190E+11 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 440133.03 | 440133.03 | 2409.96 | 2409.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.685031E+10 | 0.368230E+10 | 20004.77 | 13017.23 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.157163E+09 | 0.157163E+09 | 12256.09 | 08-FEB-14:30 | 12256.09 | 0.00 |
March | 0.00 | 0.00 | 0.627910E+09 | 0.627910E+09 | 20588.48 | 24-MAR-13:30 | 20588.48 | 0.00 |
April | 0.00 | 0.00 | 0.412507E+10 | 0.280850E+10 | 38997.79 | 16-APR-18:10 | 28224.84 | 0.08 |
May | 0.00 | 0.00 | 0.340836E+10 | 0.151890E+10 | 25743.34 | 31-MAY-19:10 | 14868.93 | 0.18 |
June | 0.00 | 0.00 | 0.133196E+11 | 0.554283E+10 | 37521.18 | 18-JUN-20:30 | 26434.33 | 0.51 |
July | 0.00 | 0.00 | 0.183253E+11 | 0.728842E+10 | 43602.39 | 25-JUL-21:00 | 24106.67 | 0.63 |
August | 0.00 | 0.00 | 0.195270E+11 | 0.924785E+10 | 36964.01 | 03-AUG-08:00 | 13365.02 | 0.61 |
September | 0.00 | 0.00 | 0.182032E+11 | 0.126332E+11 | 43793.00 | 08-SEP-12:40 | 35960.79 | 0.39 |
October | 0.00 | 0.00 | 0.792349E+10 | 0.770125E+10 | 44337.04 | 20-OCT-12:30 | 44337.04 | 0.03 |
November | 0.00 | 0.00 | 0.265004E+10 | 0.260677E+10 | 45388.82 | 04-NOV-12:30 | 45388.82 | 0.01 |
December | 0.00 | 0.00 | 0.331333E+09 | 0.331333E+09 | 16092.09 | 03-DEC-13:30 | 16092.09 | 0.00 |
Annual Sum or Average | 0.885985E+11 | 0.504641E+11 | 0.20 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195270E+11 | 0.126332E+11 | 45388.82 | 45388.82 | 0.63 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11232190.47 | 11232190.47 | 20685.31 | 12-JAN-19:05 | 20685.31 | 0.00 |
February | 0.00 | 0.00 | 50010604.94 | 50010604.94 | 21420.87 | 24-FEB-19:04 | 21420.87 | 0.00 |
March | 0.00 | 0.00 | 0.183068E+10 | 0.137987E+10 | 59535.45 | 28-MAR-18:02 | 59535.45 | 0.06 |
April | 0.00 | 0.00 | 0.944381E+10 | 0.642165E+10 | 76376.32 | 18-APR-18:02 | 62061.59 | 0.20 |
May | 0.00 | 0.00 | 0.261028E+11 | 0.163495E+11 | 77878.21 | 30-MAY-18:02 | 64082.70 | 0.52 |
June | 0.00 | 0.00 | 0.423761E+11 | 0.259002E+11 | 95462.38 | 26-JUN-08:62 | 53112.83 | 0.71 |
July | 0.00 | 0.00 | 0.501629E+11 | 0.287970E+11 | 93783.22 | 16-JUL-18:02 | 55125.00 | 0.71 |
August | 0.00 | 0.00 | 0.446886E+11 | 0.249138E+11 | 105282.69 | 03-AUG-08:61 | 48131.78 | 0.70 |
September | 0.00 | 0.00 | 0.235340E+11 | 0.148235E+11 | 79415.06 | 11-SEP-18:02 | 64186.70 | 0.49 |
October | 0.00 | 0.00 | 0.508903E+10 | 0.370283E+10 | 61569.59 | 02-OCT-15:01 | 55803.18 | 0.15 |
November | 0.00 | 0.00 | 0.218729E+10 | 0.115464E+10 | 57138.24 | 04-NOV-08:62 | 57138.24 | 0.11 |
December | 0.00 | 0.00 | 15752579.24 | 15752579.24 | 20609.58 | 04-DEC-19:05 | 20609.58 | 0.00 |
Annual Sum or Average | 0.205492E+12 | 0.123520E+12 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 11232190.47 | 11232190.47 | 20609.58 | 20609.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.501629E+11 | 0.287970E+11 | 105282.69 | 64186.70 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1158793.51 | 1158793.51 | 1920.69 | 09-JAN-09:05 | 1920.69 | 0.00 |
February | 0.00 | 0.00 | 52153245.33 | 52153245.33 | 11084.14 | 24-FEB-09:02 | 11084.14 | 0.00 |
March | 0.00 | 0.00 | 0.238904E+09 | 0.213494E+09 | 11852.83 | 28-MAR-15:01 | 11852.83 | 0.02 |
April | 0.00 | 0.00 | 0.140773E+10 | 0.964261E+09 | 13690.86 | 18-APR-18:02 | 11451.12 | 0.19 |
May | 0.00 | 0.00 | 0.298235E+10 | 0.183565E+10 | 13869.63 | 30-MAY-15:02 | 11873.59 | 0.51 |
June | 0.00 | 0.00 | 0.565721E+10 | 0.315744E+10 | 15122.03 | 30-JUN-08:62 | 10781.64 | 0.79 |
July | 0.00 | 0.00 | 0.695174E+10 | 0.367765E+10 | 16006.23 | 14-JUL-18:02 | 10233.49 | 0.90 |
August | 0.00 | 0.00 | 0.596270E+10 | 0.303140E+10 | 16270.01 | 03-AUG-08:61 | 10303.76 | 0.87 |
September | 0.00 | 0.00 | 0.365773E+10 | 0.223127E+10 | 14070.39 | 11-SEP-18:02 | 11643.96 | 0.54 |
October | 0.00 | 0.00 | 0.615570E+09 | 0.528570E+09 | 12142.39 | 19-OCT-15:02 | 12142.39 | 0.08 |
November | 0.00 | 0.00 | 0.101149E+09 | 97461308.44 | 11865.52 | 04-NOV-15:02 | 11865.52 | 0.01 |
December | 0.00 | 0.00 | 9791331.76 | 9791331.76 | 3971.84 | 03-DEC-09:02 | 3971.84 | 0.00 |
Annual Sum or Average | 0.276382E+11 | 0.158003E+11 | 0.33 | |||||
Minimum of Months | 0.00 | 0.00 | 1158793.51 | 1158793.51 | 1920.69 | 1920.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.695174E+10 | 0.367765E+10 | 16270.01 | 12142.39 | 0.90 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 182261.45 | 182261.45 | 1822.61 | 12-JAN-09:05 | 1822.61 | 0.00 |
February | 0.00 | 0.00 | 9765544.36 | 9765544.36 | 8355.03 | 24-FEB-09:02 | 8355.03 | 0.00 |
March | 0.00 | 0.00 | 95980290.32 | 85585614.21 | 11154.91 | 28-MAR-08:62 | 11154.91 | 0.01 |
April | 0.00 | 0.00 | 0.105410E+10 | 0.709567E+09 | 13997.00 | 15-APR-15:02 | 11676.63 | 0.16 |
May | 0.00 | 0.00 | 0.269330E+10 | 0.164063E+10 | 13993.23 | 30-MAY-15:02 | 11683.62 | 0.48 |
June | 0.00 | 0.00 | 0.545036E+10 | 0.304931E+10 | 15022.94 | 30-JUN-08:62 | 10720.16 | 0.78 |
July | 0.00 | 0.00 | 0.659154E+10 | 0.348994E+10 | 15980.85 | 17-JUL-18:02 | 10040.42 | 0.89 |
August | 0.00 | 0.00 | 0.529576E+10 | 0.265107E+10 | 16225.75 | 03-AUG-08:61 | 10208.57 | 0.84 |
September | 0.00 | 0.00 | 0.273434E+10 | 0.158078E+10 | 13871.47 | 11-SEP-18:02 | 11636.67 | 0.48 |
October | 0.00 | 0.00 | 0.171567E+09 | 0.142011E+09 | 11035.58 | 20-OCT-08:62 | 11035.58 | 0.04 |
November | 0.00 | 0.00 | 16245742.50 | 14062507.81 | 4728.38 | 04-NOV-08:62 | 4728.38 | 0.00 |
December | 0.00 | 0.00 | 292157.75 | 292157.75 | 2632.80 | 03-DEC-09:03 | 2632.80 | 0.00 |
Annual Sum or Average | 0.241134E+11 | 0.133732E+11 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 182261.45 | 182261.45 | 1822.61 | 1822.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.659154E+10 | 0.348994E+10 | 16225.75 | 11683.62 | 0.89 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 958541.21 | 958541.21 | 2680.24 | 12-JAN-16:02 | 2680.24 | 0.00 |
February | 0.00 | 0.00 | 22405495.00 | 22405495.00 | 3454.06 | 24-FEB-16:02 | 3454.06 | 0.00 |
March | 0.00 | 0.00 | 67839866.92 | 61986169.51 | 3560.73 | 25-MAR-15:01 | 3560.73 | 0.02 |
April | 0.00 | 0.00 | 0.492522E+09 | 0.368683E+09 | 3947.29 | 16-APR-08:62 | 2926.92 | 0.18 |
May | 0.00 | 0.00 | 0.810903E+09 | 0.517951E+09 | 4183.35 | 29-MAY-08:62 | 2910.31 | 0.47 |
June | 0.00 | 0.00 | 0.165382E+10 | 0.961745E+09 | 4962.48 | 26-JUN-08:62 | 2826.18 | 0.76 |
July | 0.00 | 0.00 | 0.212296E+10 | 0.119659E+10 | 4703.99 | 14-JUL-18:02 | 2942.33 | 0.89 |
August | 0.00 | 0.00 | 0.182186E+10 | 0.990685E+09 | 5386.20 | 03-AUG-08:61 | 2587.32 | 0.87 |
September | 0.00 | 0.00 | 0.104518E+10 | 0.676827E+09 | 4232.96 | 11-SEP-08:62 | 2824.53 | 0.50 |
October | 0.00 | 0.00 | 0.205898E+09 | 0.180885E+09 | 3558.47 | 19-OCT-15:02 | 3558.47 | 0.06 |
November | 0.00 | 0.00 | 38712532.52 | 36624401.06 | 3471.80 | 03-NOV-15:01 | 3471.80 | 0.01 |
December | 0.00 | 0.00 | 1024931.04 | 1024931.04 | 2257.31 | 02-DEC-16:01 | 2257.31 | 0.00 |
Annual Sum or Average | 0.828409E+10 | 0.501637E+10 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 958541.21 | 958541.21 | 2257.31 | 2257.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212296E+10 | 0.119659E+10 | 5386.20 | 3560.73 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48382.24 | 48382.24 | 357.82 | 13-JAN-16:05 | 357.82 | 0.00 |
February | 0.00 | 0.00 | 3982731.81 | 3982731.81 | 2664.61 | 24-FEB-16:02 | 2664.61 | 0.00 |
March | 0.00 | 0.00 | 23240708.01 | 20756124.82 | 3327.44 | 25-MAR-15:01 | 3327.44 | 0.01 |
April | 0.00 | 0.00 | 0.381025E+09 | 0.279363E+09 | 3880.90 | 16-APR-08:62 | 2893.26 | 0.15 |
May | 0.00 | 0.00 | 0.731695E+09 | 0.465597E+09 | 4110.32 | 29-MAY-08:62 | 2853.69 | 0.44 |
June | 0.00 | 0.00 | 0.160091E+10 | 0.931600E+09 | 4865.62 | 26-JUN-08:62 | 2785.73 | 0.76 |
July | 0.00 | 0.00 | 0.202861E+10 | 0.114204E+10 | 4654.30 | 17-JUL-18:02 | 2848.39 | 0.88 |
August | 0.00 | 0.00 | 0.164562E+10 | 0.882966E+09 | 5306.07 | 03-AUG-08:61 | 2536.15 | 0.84 |
September | 0.00 | 0.00 | 0.802950E+09 | 0.495035E+09 | 4094.54 | 11-SEP-08:62 | 2791.29 | 0.44 |
October | 0.00 | 0.00 | 86607619.73 | 74435491.25 | 3377.22 | 02-OCT-15:01 | 3042.07 | 0.04 |
November | 0.00 | 0.00 | 14126791.97 | 13458419.07 | 3293.56 | 03-NOV-15:01 | 3293.56 | 0.00 |
December | 0.00 | 0.00 | 38740.12 | 38740.12 | 294.48 | 01-DEC-16:05 | 294.48 | 0.00 |
Annual Sum or Average | 0.731885E+10 | 0.430932E+10 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 38740.12 | 38740.12 | 294.48 | 294.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202861E+10 | 0.114204E+10 | 5306.07 | 3327.44 | 0.88 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.370910E+09 | 0.370910E+09 | 13137.48 | 12-JAN-16:02 | 13137.48 | 0.00 |
February | 0.00 | 0.00 | 0.671901E+09 | 0.671901E+09 | 13144.78 | 24-FEB-16:02 | 13144.78 | 0.00 |
March | 0.00 | 0.00 | 0.109966E+10 | 0.997380E+09 | 13550.74 | 25-MAR-15:01 | 13550.74 | 0.06 |
April | 0.00 | 0.00 | 0.262191E+10 | 0.195312E+10 | 15195.50 | 18-APR-18:02 | 12671.63 | 0.23 |
May | 0.00 | 0.00 | 0.410307E+10 | 0.241988E+10 | 15684.74 | 30-MAY-18:02 | 12752.46 | 0.55 |
June | 0.00 | 0.00 | 0.741342E+10 | 0.425512E+10 | 19489.95 | 26-JUN-08:62 | 10483.25 | 0.78 |
July | 0.00 | 0.00 | 0.958236E+10 | 0.530385E+10 | 18591.34 | 16-JUL-18:02 | 10976.52 | 0.87 |
August | 0.00 | 0.00 | 0.949536E+10 | 0.538752E+10 | 21068.98 | 03-AUG-08:61 | 9614.90 | 0.87 |
September | 0.00 | 0.00 | 0.683910E+10 | 0.489748E+10 | 16095.58 | 11-SEP-08:62 | 10929.68 | 0.59 |
October | 0.00 | 0.00 | 0.339720E+10 | 0.310937E+10 | 13680.47 | 02-OCT-15:01 | 12466.52 | 0.15 |
November | 0.00 | 0.00 | 0.112578E+10 | 0.100295E+10 | 13154.62 | 05-NOV-15:02 | 13154.62 | 0.09 |
December | 0.00 | 0.00 | 0.816764E+09 | 0.816764E+09 | 13141.49 | 02-DEC-16:01 | 13141.49 | 0.00 |
Annual Sum or Average | 0.475374E+11 | 0.311862E+11 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 0.370910E+09 | 0.370910E+09 | 13137.48 | 9614.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.958236E+10 | 0.538752E+10 | 21068.98 | 13550.74 | 0.87 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 27129571.09 | 27129571.09 | 6725.74 | 13-JAN-18:05 | 6725.74 | 0.00 |
February | 0.00 | 0.00 | 0.101641E+09 | 0.101641E+09 | 6846.93 | 09-FEB-18:05 | 6846.93 | 0.00 |
March | 0.00 | 0.00 | 0.486427E+10 | 0.486427E+10 | 96123.92 | 19-MAR-16:00 | 96123.92 | 0.02 |
April | 0.00 | 0.00 | 0.590194E+11 | 0.455761E+11 | 296408.13 | 16-APR-20:10 | 179543.55 | 0.13 |
May | 0.00 | 0.00 | 0.147833E+12 | 0.109617E+12 | 306935.04 | 30-MAY-19:40 | 185127.42 | 0.47 |
June | 0.00 | 0.00 | 0.390311E+12 | 0.251312E+12 | 386462.83 | 26-JUN-06:15 | 156177.16 | 0.78 |
July | 0.00 | 0.00 | 0.568481E+12 | 0.322969E+12 | 503815.16 | 03-JUL-21:50 | 190007.68 | 0.96 |
August | 0.00 | 0.00 | 0.489447E+12 | 0.286721E+12 | 491229.06 | 04-AUG-06:00 | 162978.86 | 0.89 |
September | 0.00 | 0.00 | 0.189158E+12 | 0.159568E+12 | 324196.64 | 11-SEP-19:20 | 188570.99 | 0.48 |
October | 0.00 | 0.00 | 0.158020E+11 | 0.158020E+11 | 164847.71 | 20-OCT-15:10 | 164847.71 | 0.04 |
November | 0.00 | 0.00 | 0.185314E+10 | 0.185314E+10 | 43956.73 | 03-NOV-14:20 | 43956.73 | 0.04 |
December | 0.00 | 0.00 | 41389678.57 | 41389678.57 | 5645.20 | 02-DEC-18:05 | 5645.20 | 0.00 |
Annual Sum or Average | 0.186694E+13 | 0.119845E+13 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 27129571.09 | 27129571.09 | 5645.20 | 5645.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.568481E+12 | 0.322969E+12 | 503815.16 | 190007.68 | 0.96 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.508253E+09 | 0.508253E+09 | 14383.07 | 19-MAR-16:00 | 14383.07 | 0.01 |
April | 0.00 | 0.00 | 0.833358E+10 | 0.653687E+10 | 43547.89 | 18-APR-17:10 | 28083.30 | 0.12 |
May | 0.00 | 0.00 | 0.198488E+11 | 0.151178E+11 | 54494.68 | 29-MAY-14:20 | 26805.09 | 0.39 |
June | 0.00 | 0.00 | 0.574063E+11 | 0.377158E+11 | 64103.73 | 12-JUN-14:00 | 26564.58 | 0.74 |
July | 0.00 | 0.00 | 0.840494E+11 | 0.492205E+11 | 66044.53 | 27-JUL-00:10 | 24684.23 | 0.93 |
August | 0.00 | 0.00 | 0.718932E+11 | 0.430399E+11 | 71073.16 | 03-AUG-08:61 | 29363.78 | 0.85 |
September | 0.00 | 0.00 | 0.267999E+11 | 0.234662E+11 | 48659.22 | 11-SEP-08:62 | 25676.48 | 0.45 |
October | 0.00 | 0.00 | 0.189034E+10 | 0.189034E+10 | 25764.86 | 20-OCT-15:00 | 25764.86 | 0.03 |
November | 0.00 | 0.00 | 69741438.72 | 69741438.72 | 4334.19 | 03-NOV-14:00 | 4334.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.270799E+12 | 0.177565E+12 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.840494E+11 | 0.492205E+11 | 71073.16 | 29363.78 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31415.43 | 64800.25 | 31-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 32044.72 | 65204.94 | 23-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31740.19 | 77294.16 | 24-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30545.84 | 74121.16 | 17-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28817.95 | 67519.59 | 17-MAY-06:32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26885.46 | 66877.65 | 02-JUN-06:11 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25366.88 | 54454.89 | 24-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24642.37 | 56886.02 | 07-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24972.13 | 57284.91 | 28-SEP-07:51 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26231.76 | 60298.55 | 30-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28111.60 | 61597.94 | 07-NOV-07:13 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29974.38 | 62311.74 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 28374.14 | ||||
Minimum of Months | 0.00 | 0.00 | 24642.37 | 54454.89 | ||
Maximum of Months | 0.00 | 0.00 | 32044.72 | 77294.16 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 187701.88 | 623266.92 | 31-JAN-04:00 |
February | 0.01 | 37.59 | 24-FEB-13:20 | 144049.74 | 650832.44 | 02-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 43037.91 | 203037.01 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18360.41 | 167922.36 | 03-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6037.75 | 96588.77 | 09-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3871.43 | 83809.69 | 06-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1731.08 | 111406.49 | 10-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2112.05 | 82709.78 | 30-AUG-15:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6429.37 | 116447.36 | 27-SEP-15:02 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 13065.17 | 155604.26 | 26-OCT-15:02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 61075.79 | 610610.15 | 26-NOV-07:00 |
December | 0.00 | 25.77 | 03-DEC-13:03 | 104490.14 | 315326.01 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 48846.46 | ||||
Minimum of Months | 0.00 | 0.00 | 1731.08 | 82709.78 | ||
Maximum of Months | 0.01 | 37.59 | 187701.88 | 650832.44 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 349.83 | 31584.89 | 12-JAN-19:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 958.00 | 36849.81 | 24-FEB-16:05 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 4590.22 | 186790.01 | 19-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36320.39 | 491863.90 | 16-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82176.58 | 501158.16 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 209471.03 | 601012.07 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 287413.77 | 711199.20 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 249750.75 | 667670.03 | 04-AUG-08:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 110095.06 | 508304.73 | 11-SEP-08:62 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15384.52 | 322153.88 | 20-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 4120.95 | 137602.16 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 804.31 | 28839.27 | 04-DEC-19:05 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 84059.22 | 0.00 | ||||
Minimum of Months | 349.83 | 28839.27 | 0.00 | 0.00 | ||
Maximum of Months | 287413.77 | 711199.20 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587767E+10 | 0.92 | 2194.47 | 01-JAN-02:63 | 0.92 |
February | 0.530887E+10 | 0.92 | 2194.47 | 01-FEB-00:03 | 0.93 |
March | 0.587767E+10 | 0.92 | 2194.47 | 01-MAR-04:10 | 0.92 |
April | 0.568807E+10 | 0.92 | 2194.47 | 01-APR-15:02 | 0.92 |
May | 0.587767E+10 | 0.91 | 2194.47 | 02-MAY-18:02 | 0.92 |
June | 0.568807E+10 | 0.91 | 2194.47 | 01-JUN-08:62 | 0.92 |
July | 0.587767E+10 | 0.91 | 2194.47 | 01-JUL-08:61 | 0.91 |
August | 0.587767E+10 | 0.91 | 2194.47 | 01-AUG-08:62 | 0.91 |
September | 0.568807E+10 | 0.91 | 2194.47 | 01-SEP-15:02 | 0.91 |
October | 0.587767E+10 | 0.92 | 2194.47 | 01-OCT-15:03 | 0.92 |
November | 0.568807E+10 | 0.92 | 2194.47 | 03-NOV-20:07 | 0.92 |
December | 0.587767E+10 | 0.92 | 2194.47 | 01-DEC-09:02 | 0.92 |
Annual Sum or Average | 0.692049E+11 | 0.92 | |||
Minimum of Months | 0.530887E+10 | 0.91 | 2194.47 | 0.91 | |
Maximum of Months | 0.587767E+10 | 0.92 | 2194.47 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352663E+11 | 0.89 | 20058.59 | 12-JAN-22:00 | 1.13 |
February | 0.325166E+11 | 0.89 | 20552.41 | 24-FEB-21:10 | 1.14 |
March | 0.377410E+11 | 0.92 | 34164.02 | 23-MAR-21:07 | 1.56 |
April | 0.370887E+11 | 0.92 | 34616.15 | 19-APR-19:55 | 1.58 |
May | 0.380402E+11 | 0.92 | 32245.90 | 22-MAY-21:15 | 1.50 |
June | 0.355351E+11 | 0.90 | 34000.90 | 02-JUN-22:00 | 1.55 |
July | 0.355845E+11 | 0.88 | 23448.11 | 24-JUL-05:32 | 1.23 |
August | 0.359833E+11 | 0.89 | 25693.42 | 17-AUG-05:20 | 1.30 |
September | 0.365129E+11 | 0.91 | 41433.55 | 19-SEP-21:05 | 1.77 |
October | 0.394649E+11 | 0.94 | 42502.16 | 19-OCT-21:20 | 1.80 |
November | 0.367855E+11 | 0.92 | 43091.82 | 03-NOV-20:30 | 1.81 |
December | 0.363390E+11 | 0.90 | 21180.80 | 04-DEC-22:00 | 1.17 |
Annual Sum or Average | 0.436858E+12 | 0.91 | |||
Minimum of Months | 0.325166E+11 | 0.88 | 20058.59 | 1.13 | |
Maximum of Months | 0.394649E+11 | 0.94 | 43091.82 | 1.81 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:03 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:10 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:05 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:03 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:05 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.721440E+09 | 0.55 | 781.69 | 01-JAN-09:02 | 0.60 |
February | 0.519567E+09 | 0.51 | 781.69 | 01-FEB-02:00 | 0.61 |
March | 0.287270E+09 | 0.45 | 781.69 | 01-MAR-09:02 | 0.61 |
April | 0.245258E+09 | 0.46 | 781.69 | 01-APR-08:62 | 0.60 |
May | 0.191839E+09 | 0.46 | 781.69 | 02-MAY-08:62 | 0.60 |
June | 0.296097E+09 | 0.50 | 781.69 | 01-JUN-08:62 | 0.60 |
July | 0.351655E+09 | 0.51 | 781.69 | 01-JUL-08:61 | 0.60 |
August | 0.313396E+09 | 0.52 | 781.69 | 01-AUG-08:62 | 0.60 |
September | 0.246011E+09 | 0.49 | 781.69 | 01-SEP-15:02 | 0.60 |
October | 0.194601E+09 | 0.44 | 781.69 | 01-OCT-15:02 | 0.60 |
November | 0.346797E+09 | 0.48 | 781.69 | 01-NOV-08:62 | 0.60 |
December | 0.522001E+09 | 0.52 | 781.69 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.423593E+10 | 0.49 | |||
Minimum of Months | 0.191839E+09 | 0.44 | 781.69 | 0.60 | |
Maximum of Months | 0.721440E+09 | 0.55 | 781.69 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.818869E+09 | 0.58 | 768.56 | 01-JAN-09:02 | 0.60 |
February | 0.589453E+09 | 0.54 | 768.56 | 01-FEB-00:01 | 0.61 |
March | 0.309828E+09 | 0.48 | 768.56 | 01-MAR-09:02 | 0.61 |
April | 0.233712E+09 | 0.45 | 768.56 | 01-APR-08:62 | 0.60 |
May | 0.178651E+09 | 0.45 | 768.56 | 02-MAY-08:62 | 0.60 |
June | 0.287025E+09 | 0.49 | 768.56 | 01-JUN-08:62 | 0.60 |
July | 0.334693E+09 | 0.50 | 768.56 | 01-JUL-08:61 | 0.60 |
August | 0.282003E+09 | 0.49 | 768.56 | 01-AUG-08:62 | 0.60 |
September | 0.208953E+09 | 0.46 | 768.56 | 01-SEP-15:02 | 0.60 |
October | 0.202285E+09 | 0.43 | 768.56 | 01-OCT-15:02 | 0.60 |
November | 0.390369E+09 | 0.50 | 768.56 | 01-NOV-08:62 | 0.60 |
December | 0.577867E+09 | 0.56 | 768.56 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.441371E+10 | 0.49 | |||
Minimum of Months | 0.178651E+09 | 0.43 | 768.56 | 0.60 | |
Maximum of Months | 0.818869E+09 | 0.58 | 768.56 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195860E+10 | 0.43 | 3703.16 | 06-JAN-04:50 | 0.61 |
February | 0.130524E+10 | 0.27 | 3703.16 | 01-FEB-03:00 | 0.61 |
March | 0.436263E+09 | 0.18 | 971.30 | 24-MAR-13:30 | 0.60 |
April | 0.264016E+09 | 0.12 | 1909.61 | 17-APR-12:20 | 0.60 |
May | 0.186556E+09 | 0.14 | 913.34 | 31-MAY-18:30 | 0.60 |
June | 0.591743E+09 | 0.31 | 1611.30 | 18-JUN-20:20 | 0.60 |
July | 0.769514E+09 | 0.38 | 1161.65 | 25-JUL-19:30 | 0.60 |
August | 0.822425E+09 | 0.37 | 1670.78 | 29-AUG-13:10 | 0.60 |
September | 0.867012E+09 | 0.30 | 2096.16 | 08-SEP-12:50 | 0.60 |
October | 0.432761E+09 | 0.14 | 2220.41 | 20-OCT-12:30 | 0.60 |
November | 0.708519E+09 | 0.23 | 3703.16 | 26-NOV-05:50 | 0.61 |
December | 0.116655E+10 | 0.37 | 2124.33 | 10-DEC-06:00 | 0.61 |
Annual Sum or Average | 0.950920E+10 | 0.27 | |||
Minimum of Months | 0.186556E+09 | 0.12 | 913.34 | 0.60 | |
Maximum of Months | 0.195860E+10 | 0.43 | 3703.16 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.365625E+10 | 0.50 | 3789.55 | 01-JAN-16:02 | 0.60 |
February | 0.271761E+10 | 0.47 | 3789.55 | 01-FEB-00:01 | 0.61 |
March | 0.115391E+10 | 0.43 | 3789.55 | 01-MAR-09:02 | 0.61 |
April | 0.950394E+09 | 0.43 | 3789.55 | 01-APR-15:02 | 0.61 |
May | 0.136289E+10 | 0.43 | 3789.55 | 02-MAY-18:02 | 0.60 |
June | 0.203406E+10 | 0.43 | 3789.55 | 01-JUN-08:62 | 0.60 |
July | 0.225668E+10 | 0.43 | 3789.55 | 01-JUL-08:61 | 0.60 |
August | 0.201075E+10 | 0.42 | 3789.55 | 01-AUG-08:62 | 0.60 |
September | 0.126993E+10 | 0.43 | 3789.55 | 01-SEP-15:02 | 0.60 |
October | 0.685085E+09 | 0.43 | 3789.55 | 01-OCT-08:62 | 0.60 |
November | 0.146773E+10 | 0.44 | 3789.55 | 09-NOV-16:02 | 0.60 |
December | 0.233801E+10 | 0.46 | 3789.55 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.219033E+11 | 0.44 | |||
Minimum of Months | 0.685085E+09 | 0.42 | 3789.55 | 0.60 | |
Maximum of Months | 0.365625E+10 | 0.50 | 3789.55 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.684695E+09 | 0.55 | 696.24 | 01-JAN-09:02 | 0.60 |
February | 0.491263E+09 | 0.51 | 696.24 | 01-FEB-00:12 | 0.61 |
March | 0.260262E+09 | 0.45 | 696.24 | 01-MAR-09:02 | 0.61 |
April | 0.218539E+09 | 0.47 | 696.24 | 01-APR-08:62 | 0.60 |
May | 0.195421E+09 | 0.48 | 696.24 | 01-MAY-08:62 | 0.60 |
June | 0.291230E+09 | 0.53 | 696.24 | 01-JUN-08:62 | 0.60 |
July | 0.332651E+09 | 0.54 | 696.24 | 01-JUL-08:61 | 0.60 |
August | 0.288027E+09 | 0.53 | 696.24 | 01-AUG-08:62 | 0.60 |
September | 0.236859E+09 | 0.51 | 696.24 | 01-SEP-15:02 | 0.60 |
October | 0.172211E+09 | 0.44 | 696.24 | 01-OCT-08:62 | 0.60 |
November | 0.326624E+09 | 0.48 | 696.24 | 01-NOV-08:62 | 0.60 |
December | 0.492747E+09 | 0.52 | 696.24 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.399053E+10 | 0.50 | |||
Minimum of Months | 0.172211E+09 | 0.44 | 696.24 | 0.60 | |
Maximum of Months | 0.684695E+09 | 0.55 | 696.24 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.778854E+09 | 0.58 | 691.86 | 01-JAN-09:02 | 0.60 |
February | 0.569199E+09 | 0.54 | 691.86 | 01-FEB-00:01 | 0.61 |
March | 0.286537E+09 | 0.46 | 691.86 | 01-MAR-09:02 | 0.61 |
April | 0.213732E+09 | 0.46 | 691.86 | 01-APR-08:62 | 0.60 |
May | 0.182635E+09 | 0.46 | 691.86 | 01-MAY-08:62 | 0.60 |
June | 0.282051E+09 | 0.52 | 691.86 | 01-JUN-08:62 | 0.60 |
July | 0.315349E+09 | 0.54 | 691.86 | 01-JUL-08:61 | 0.60 |
August | 0.257277E+09 | 0.52 | 691.86 | 01-AUG-08:62 | 0.60 |
September | 0.196995E+09 | 0.48 | 691.86 | 01-SEP-15:02 | 0.60 |
October | 0.178969E+09 | 0.43 | 691.86 | 01-OCT-08:62 | 0.60 |
November | 0.367730E+09 | 0.50 | 691.86 | 01-NOV-08:62 | 0.60 |
December | 0.560888E+09 | 0.57 | 691.86 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.419022E+10 | 0.50 | |||
Minimum of Months | 0.178969E+09 | 0.43 | 691.86 | 0.60 | |
Maximum of Months | 0.778854E+09 | 0.58 | 691.86 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217033E+09 | 0.57 | 203.31 | 01-JAN-09:02 | 0.60 |
February | 0.149176E+09 | 0.53 | 203.31 | 01-FEB-01:25 | 0.61 |
March | 87403448.43 | 0.47 | 203.31 | 01-MAR-09:02 | 0.60 |
April | 73379719.44 | 0.48 | 203.31 | 01-APR-08:62 | 0.60 |
May | 57278287.21 | 0.47 | 203.31 | 02-MAY-08:62 | 0.60 |
June | 89683774.70 | 0.52 | 203.31 | 02-JUN-18:02 | 0.60 |
July | 0.105974E+09 | 0.54 | 203.31 | 01-JUL-08:61 | 0.60 |
August | 92349626.86 | 0.53 | 203.31 | 01-AUG-08:62 | 0.60 |
September | 72813255.18 | 0.50 | 203.31 | 01-SEP-15:02 | 0.60 |
October | 59273409.40 | 0.44 | 203.31 | 01-OCT-15:02 | 0.60 |
November | 0.108124E+09 | 0.50 | 203.31 | 01-NOV-08:62 | 0.60 |
December | 0.162094E+09 | 0.54 | 203.31 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.127458E+10 | 0.51 | |||
Minimum of Months | 57278287.21 | 0.44 | 203.31 | 0.60 | |
Maximum of Months | 0.217033E+09 | 0.57 | 203.31 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.243936E+09 | 0.59 | 199.76 | 01-JAN-09:02 | 0.60 |
February | 0.168539E+09 | 0.56 | 199.76 | 01-FEB-00:01 | 0.61 |
March | 95023709.17 | 0.50 | 199.76 | 01-MAR-09:02 | 0.60 |
April | 69960029.42 | 0.47 | 199.76 | 01-APR-08:62 | 0.60 |
May | 53582130.13 | 0.46 | 199.76 | 02-MAY-08:62 | 0.60 |
June | 87198552.88 | 0.51 | 199.76 | 02-JUN-18:02 | 0.60 |
July | 0.101297E+09 | 0.53 | 199.76 | 01-JUL-08:61 | 0.60 |
August | 83512675.65 | 0.52 | 199.76 | 01-AUG-08:62 | 0.60 |
September | 62204715.33 | 0.47 | 199.76 | 01-SEP-15:02 | 0.60 |
October | 61430652.36 | 0.43 | 199.76 | 01-OCT-08:62 | 0.60 |
November | 0.119788E+09 | 0.52 | 199.76 | 01-NOV-08:62 | 0.60 |
December | 0.186135E+09 | 0.58 | 199.76 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.133261E+10 | 0.51 | |||
Minimum of Months | 53582130.13 | 0.43 | 199.76 | 0.60 | |
Maximum of Months | 0.243936E+09 | 0.59 | 199.76 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.687764E+09 | 0.51 | 763.47 | 01-JAN-09:02 | 0.60 |
February | 0.477335E+09 | 0.48 | 763.47 | 01-FEB-02:15 | 0.61 |
March | 0.305860E+09 | 0.48 | 763.47 | 01-MAR-09:02 | 0.61 |
April | 0.286161E+09 | 0.48 | 763.47 | 01-APR-08:62 | 0.60 |
May | 0.242166E+09 | 0.47 | 763.47 | 01-MAY-15:02 | 0.60 |
June | 0.364605E+09 | 0.51 | 763.47 | 01-JUN-08:62 | 0.60 |
July | 0.443989E+09 | 0.52 | 763.47 | 01-JUL-08:61 | 0.60 |
August | 0.442898E+09 | 0.53 | 763.47 | 01-AUG-08:62 | 0.60 |
September | 0.389434E+09 | 0.51 | 763.47 | 01-SEP-15:02 | 0.60 |
October | 0.294519E+09 | 0.49 | 763.47 | 01-OCT-15:02 | 0.60 |
November | 0.362786E+09 | 0.48 | 763.47 | 01-NOV-15:02 | 0.60 |
December | 0.557819E+09 | 0.53 | 763.47 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.485533E+10 | 0.50 | |||
Minimum of Months | 0.242166E+09 | 0.47 | 763.47 | 0.60 | |
Maximum of Months | 0.687764E+09 | 0.53 | 763.47 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.551159E+10 | 0.496043E+10 | 3667.32 | 05-JAN-23:03 | 3300.59 | 3300.59 | 49.96 | 13.73 |
February | 0.380588E+10 | 0.342529E+10 | 3667.32 | 01-FEB-00:01 | 3300.59 | 3300.59 | 49.97 | 13.79 |
March | 0.226128E+10 | 0.203515E+10 | 2413.39 | 05-MAR-24:00 | 2172.05 | 2172.05 | 50.72 | 5.07 |
April | 0.109900E+10 | 0.989098E+09 | 2026.58 | 03-APR-08:62 | 1823.92 | 1823.92 | 48.83 | 3.60 |
May | 0.309802E+09 | 0.278822E+09 | 1726.97 | 02-MAY-21:53 | 1554.27 | 1554.27 | 50.34 | 2.80 |
June | 0.164291E+09 | 0.147862E+09 | 1102.50 | 03-JUN-08:07 | 992.25 | 992.25 | 48.74 | 1.55 |
July | 64751990.70 | 58276791.63 | 1020.88 | 10-JUL-15:05 | 918.79 | 918.79 | 38.51 | 1.42 |
August | 77072470.95 | 69365223.85 | 947.55 | 07-AUG-03:00 | 852.80 | 852.80 | 44.17 | 1.30 |
September | 0.360582E+09 | 0.324524E+09 | 1505.63 | 28-SEP-08:03 | 1355.06 | 1355.06 | 52.77 | 2.31 |
October | 0.968253E+09 | 0.871428E+09 | 1961.84 | 05-OCT-22:38 | 1765.66 | 1765.66 | 52.06 | 3.40 |
November | 0.253537E+10 | 0.228183E+10 | 3667.32 | 26-NOV-03:20 | 3300.59 | 3300.59 | 49.76 | 13.76 |
December | 0.422080E+10 | 0.379872E+10 | 2758.75 | 09-DEC-09:02 | 2482.88 | 2482.88 | 50.67 | 7.77 |
Annual Sum or Average | 0.213787E+11 | 0.192408E+11 | ||||||
Minimum of Months | 64751990.70 | 58276791.63 | 947.55 | 852.80 | 852.80 | 38.51 | 1.30 | |
Maximum of Months | 0.551159E+10 | 0.496043E+10 | 3667.32 | 3300.59 | 3300.59 | 52.77 | 13.79 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 209639.05 | 188675.14 | 32.24 | 12-JAN-19:05 | 29.02 | 29.02 | 8.39 | 2.52 |
February | 718622.46 | 646760.22 | 32.83 | 24-FEB-19:04 | 29.55 | 29.55 | 8.39 | 2.55 |
March | 8552632.98 | 7697369.68 | 324.96 | 19-MAR-15:02 | 292.46 | 292.46 | 7.97 | 8.61 |
April | 0.148967E+09 | 0.134070E+09 | 1186.65 | 16-APR-20:20 | 1067.99 | 1067.99 | 7.28 | 15.53 |
May | 0.310800E+09 | 0.279720E+09 | 1188.32 | 29-MAY-18:02 | 1069.49 | 1069.49 | 7.48 | 15.54 |
June | 0.103801E+10 | 0.934212E+09 | 1625.29 | 26-JUN-06:15 | 1462.76 | 1462.76 | 7.35 | 17.78 |
July | 0.157223E+10 | 0.141501E+10 | 2256.68 | 17-JUL-18:50 | 2031.01 | 2031.01 | 7.27 | 20.43 |
August | 0.131009E+10 | 0.117908E+10 | 2337.95 | 28-AUG-20:30 | 2104.16 | 2104.16 | 7.43 | 20.74 |
September | 0.473301E+09 | 0.425971E+09 | 1284.49 | 11-SEP-08:62 | 1156.05 | 1156.05 | 7.38 | 16.07 |
October | 36407941.43 | 32767147.29 | 591.72 | 11-OCT-15:02 | 532.55 | 532.55 | 7.90 | 11.39 |
November | 6832873.44 | 6149586.10 | 156.21 | 03-NOV-15:01 | 140.59 | 140.59 | 8.32 | 6.00 |
December | 739635.15 | 665671.64 | 27.69 | 04-DEC-19:05 | 24.92 | 24.92 | 8.39 | 2.30 |
Annual Sum or Average | 0.490687E+10 | 0.441618E+10 | ||||||
Minimum of Months | 209639.05 | 188675.14 | 27.69 | 24.92 | 24.92 | 7.27 | 2.30 | |
Maximum of Months | 0.157223E+10 | 0.141501E+10 | 2337.95 | 2104.16 | 2104.16 | 8.39 | 20.74 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 46.82 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 46.40 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 46.96 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.08 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 49.32 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 50.90 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.94 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.02 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.25 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.80 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.00 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.34 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.40 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.25 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.580325E+09 | 0.522293E+09 | 2772.43 | 01-JAN-09:03 | 2495.19 | 2495.19 | 8.46 | 34.72 |
February | 0.125965E+10 | 0.113369E+10 | 2772.43 | 04-FEB-16:02 | 2495.19 | 2495.19 | 8.42 | 34.72 |
March | 0.280174E+10 | 0.252156E+10 | 2772.43 | 01-MAR-09:07 | 2495.19 | 2495.19 | 8.40 | 34.72 |
April | 0.453425E+10 | 0.408083E+10 | 2772.43 | 01-APR-01:10 | 2495.19 | 2495.19 | 8.39 | 34.72 |
May | 0.687351E+10 | 0.618616E+10 | 2772.43 | 01-MAY-00:03 | 2495.19 | 2495.19 | 8.42 | 34.72 |
June | 0.697599E+10 | 0.627839E+10 | 2772.43 | 01-JUN-00:10 | 2495.19 | 2495.19 | 8.69 | 34.72 |
July | 0.742568E+10 | 0.668311E+10 | 2772.43 | 01-JUL-00:10 | 2495.19 | 2495.19 | 9.21 | 34.72 |
August | 0.742041E+10 | 0.667837E+10 | 2772.43 | 01-AUG-00:10 | 2495.19 | 2495.19 | 9.86 | 34.72 |
September | 0.652727E+10 | 0.587454E+10 | 2772.43 | 01-SEP-00:10 | 2495.19 | 2495.19 | 9.23 | 34.72 |
October | 0.539508E+10 | 0.485557E+10 | 2772.43 | 01-OCT-00:05 | 2495.19 | 2495.19 | 8.39 | 34.72 |
November | 0.269660E+10 | 0.242694E+10 | 2772.43 | 01-NOV-00:05 | 2495.19 | 2495.19 | 8.39 | 34.72 |
December | 0.103210E+10 | 0.928894E+09 | 2772.43 | 01-DEC-00:03 | 2495.19 | 2495.19 | 8.39 | 34.72 |
Annual Sum or Average | 0.535226E+11 | 0.481704E+11 | ||||||
Minimum of Months | 0.580325E+09 | 0.522293E+09 | 2772.43 | 2495.19 | 2495.19 | 8.39 | 34.72 | |
Maximum of Months | 0.742568E+10 | 0.668311E+10 | 2772.43 | 2495.19 | 2495.19 | 9.86 | 34.72 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.82 | 59.87 | 31415.43 | 64800.25 | 31-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.40 | 58.87 | 32044.72 | 65204.94 | 23-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 46.96 | 58.71 | 31740.19 | 77294.16 | 24-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.08 | 58.38 | 30545.84 | 74121.16 | 17-APR-06:41 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 49.32 | 58.10 | 28817.95 | 67519.59 | 17-MAY-06:32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 50.90 | 58.23 | 26885.46 | 66877.65 | 02-JUN-06:11 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.94 | 58.90 | 25366.88 | 54454.89 | 24-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.02 | 58.64 | 24642.37 | 56886.02 | 07-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.25 | 58.86 | 24972.13 | 57284.91 | 28-SEP-07:51 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.80 | 59.61 | 26231.76 | 60298.55 | 30-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.00 | 59.86 | 28111.60 | 61597.94 | 07-NOV-07:13 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.34 | 59.90 | 29974.38 | 62311.74 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 28374.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.40 | 58.10 | 24642.37 | 54454.89 | ||
Maximum of Months | 0.00 | 0.00 | 52.25 | 59.90 | 32044.72 | 77294.16 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52.28 | 59.36 | 187701.88 | 623266.92 | 31-JAN-04:00 |
February | 0.01 | 37.59 | 24-FEB-13:20 | 57.74 | 57.74 | 144049.74 | 650832.44 | 02-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.02 | 60.00 | 43037.91 | 203037.01 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.97 | 59.09 | 18360.41 | 167922.36 | 03-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 49.86 | 57.52 | 6037.75 | 96588.77 | 09-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 46.69 | 57.22 | 3871.43 | 83809.69 | 06-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.16 | 57.22 | 1731.08 | 111406.49 | 10-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 41.04 | 57.22 | 2112.05 | 82709.78 | 30-AUG-15:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40.75 | 57.22 | 6429.37 | 116447.36 | 27-SEP-15:02 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 54.13 | 58.24 | 13065.17 | 155604.26 | 26-OCT-15:02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.47 | 58.61 | 61075.79 | 610610.15 | 26-NOV-07:00 |
December | 0.00 | 25.77 | 03-DEC-13:03 | 57.97 | 57.97 | 104490.14 | 315326.01 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 48846.46 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.75 | 57.22 | 1731.08 | 82709.78 | ||
Maximum of Months | 0.01 | 37.59 | 57.97 | 60.00 | 187701.88 | 650832.44 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 349.83 | 31584.89 | 12-JAN-19:05 | 8.59 | 8.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 958.00 | 36849.81 | 24-FEB-16:05 | 8.62 | 8.37 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 4590.22 | 186790.01 | 19-MAR-15:02 | 9.23 | 7.95 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36320.39 | 491863.90 | 16-APR-18:03 | 10.12 | 6.74 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82176.58 | 501158.16 | 30-MAY-18:03 | 10.34 | 6.90 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 209471.03 | 601012.07 | 11-JUN-15:03 | 10.83 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 287413.77 | 711199.20 | 26-JUL-18:03 | 11.59 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 249750.75 | 667670.03 | 04-AUG-08:03 | 11.43 | 6.84 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 110095.06 | 508304.73 | 11-SEP-08:62 | 10.83 | 7.33 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15384.52 | 322153.88 | 20-OCT-15:02 | 9.48 | 7.26 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 4120.95 | 137602.16 | 03-NOV-15:01 | 9.27 | 8.32 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 804.31 | 28839.27 | 04-DEC-19:05 | 8.57 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 84059.22 | 0.00 | ||||||
Minimum of Months | 349.83 | 28839.27 | 8.57 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 287413.77 | 711199.20 | 11.59 | 8.37 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.06 | 95.85 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 95.85 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 95.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.03 | 6.50 |
February | 0.00 | 0.00 |
March | 0.08 | 3.25 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 7.58 |
September | 0.00 | 0.00 |
October | 0.42 | 2.17 |
November | 0.06 | 5.41 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 3.45 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.42 | 7.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 3.76 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 7.52 |
November | 0.06 | 6.27 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.22 | 5.80 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 7.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 1.68 |
February | 0.11 | 2.24 |
March | 6.63 | 4.98 |
April | 13.32 | 5.00 |
May | 11.09 | 6.36 |
June | 6.37 | 6.30 |
July | 2.32 | 6.33 |
August | 6.23 | 7.45 |
September | 17.17 | 5.65 |
October | 18.16 | 4.71 |
November | 8.59 | 5.85 |
December | 0.00 | 0.00 |
Annual Sum or Average | 90.08 | 5.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 18.16 | 7.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 58.93 |
February | 0.25 | 56.92 |
March | 0.97 | 90.51 |
April | 1.47 | 63.90 |
May | 1.86 | 109.38 |
June | 1.29 | 91.35 |
July | 1.28 | 67.27 |
August | 1.00 | 69.96 |
September | 1.51 | 92.56 |
October | 1.56 | 94.88 |
November | 0.92 | 64.03 |
December | 0.00 | 0.00 |
Annual Sum or Average | 12.59 | 83.28 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.86 | 109.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 129.26 |
February | 0.17 | 126.73 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 295.70 |
September | 0.00 | 0.00 |
October | 0.12 | 253.46 |
November | 0.04 | 211.22 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.89 | 165.80 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.46 | 295.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.12 | 0.59 |
February | 3.21 | 0.65 |
March | 2.39 | 0.65 |
April | 1.45 | 0.75 |
May | 0.83 | 0.81 |
June | 1.13 | 0.54 |
July | 1.32 | 0.65 |
August | 1.25 | 0.60 |
September | 1.04 | 0.53 |
October | 0.56 | 0.81 |
November | 2.06 | 0.62 |
December | 5.61 | 0.67 |
Annual Sum or Average | 24.97 | 0.64 |
Minimum of Months | 0.56 | 0.53 |
Maximum of Months | 5.61 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.79 | 0.64 |
February | 3.00 | 0.68 |
March | 2.76 | 0.61 |
April | 1.76 | 0.73 |
May | 1.17 | 0.77 |
June | 1.07 | 0.59 |
July | 1.07 | 0.67 |
August | 1.22 | 0.60 |
September | 0.64 | 0.78 |
October | 0.25 | 0.70 |
November | 2.00 | 0.60 |
December | 5.36 | 0.62 |
Annual Sum or Average | 23.08 | 0.65 |
Minimum of Months | 0.25 | 0.59 |
Maximum of Months | 5.36 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.06 | 0.00 |
April | 0.17 | 0.00 |
May | 0.22 | 0.00 |
June | 0.17 | 0.00 |
July | 0.00 | 0.00 |
August | 0.17 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.86 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.22 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 6.43 | 0.68 |
February | 1.32 | 0.64 |
March | 0.00 | 0.00 |
April | 0.08 | 0.81 |
May | 0.47 | 0.80 |
June | 0.58 | 0.79 |
July | 1.31 | 0.80 |
August | 0.94 | 0.86 |
September | 0.62 | 0.81 |
October | 0.00 | 0.00 |
November | 1.49 | 0.67 |
December | 4.21 | 0.69 |
Annual Sum or Average | 17.46 | 0.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.43 | 0.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.18 | 0.61 |
February | 2.86 | 0.68 |
March | 1.75 | 0.62 |
April | 1.26 | 0.64 |
May | 2.72 | 0.56 |
June | 2.94 | 0.60 |
July | 4.43 | 0.65 |
August | 4.11 | 0.64 |
September | 1.65 | 0.64 |
October | 0.22 | 0.49 |
November | 2.06 | 0.60 |
December | 6.01 | 0.67 |
Annual Sum or Average | 34.21 | 0.63 |
Minimum of Months | 0.22 | 0.49 |
Maximum of Months | 6.01 | 0.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.67 | 0.64 |
February | 3.10 | 0.64 |
March | 1.75 | 0.61 |
April | 1.29 | 0.61 |
May | 2.53 | 0.53 |
June | 3.25 | 0.61 |
July | 4.53 | 0.61 |
August | 4.49 | 0.59 |
September | 2.10 | 0.59 |
October | 0.17 | 0.81 |
November | 1.93 | 0.56 |
December | 5.93 | 0.61 |
Annual Sum or Average | 34.72 | 0.60 |
Minimum of Months | 0.17 | 0.53 |
Maximum of Months | 5.93 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.39 | 0.50 |
February | 1.96 | 0.65 |
March | 1.56 | 0.62 |
April | 1.38 | 0.72 |
May | 0.94 | 0.62 |
June | 1.75 | 0.53 |
July | 1.94 | 0.54 |
August | 1.57 | 0.58 |
September | 1.08 | 0.46 |
October | 0.69 | 0.77 |
November | 1.12 | 0.59 |
December | 3.19 | 0.61 |
Annual Sum or Average | 19.59 | 0.59 |
Minimum of Months | 0.69 | 0.46 |
Maximum of Months | 3.19 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.04 | 0.67 |
February | 1.35 | 0.66 |
March | 1.26 | 0.62 |
April | 1.53 | 0.73 |
May | 0.89 | 0.71 |
June | 1.71 | 0.53 |
July | 1.99 | 0.54 |
August | 1.36 | 0.59 |
September | 0.46 | 0.77 |
October | 1.25 | 0.71 |
November | 1.12 | 0.53 |
December | 1.58 | 0.63 |
Annual Sum or Average | 15.55 | 0.63 |
Minimum of Months | 0.46 | 0.53 |
Maximum of Months | 1.99 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.24 | 0.67 |
February | 2.46 | 0.69 |
March | 2.18 | 0.65 |
April | 0.71 | 0.65 |
May | 1.15 | 0.70 |
June | 2.33 | 0.67 |
July | 2.53 | 0.69 |
August | 2.94 | 0.63 |
September | 1.67 | 0.55 |
October | 0.94 | 0.78 |
November | 1.88 | 0.60 |
December | 4.40 | 0.63 |
Annual Sum or Average | 26.44 | 0.65 |
Minimum of Months | 0.71 | 0.55 |
Maximum of Months | 4.40 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.76 | 143.75 |
February | 0.25 | 99.96 |
March | 0.39 | 162.43 |
April | 1.29 | 105.60 |
May | 0.93 | 127.93 |
June | 0.14 | 119.95 |
July | 0.22 | 174.93 |
August | 0.08 | 99.96 |
September | 1.94 | 177.43 |
October | 1.19 | 126.11 |
November | 0.85 | 98.87 |
December | 0.08 | 224.91 |
Annual Sum or Average | 8.14 | 137.04 |
Minimum of Months | 0.08 | 98.87 |
Maximum of Months | 1.94 | 224.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.51 | 112.32 |
February | 0.25 | 99.96 |
March | 0.78 | 162.43 |
April | 1.53 | 144.94 |
May | 1.11 | 161.18 |
June | 0.25 | 224.91 |
July | 0.00 | 0.00 |
August | 0.11 | 224.91 |
September | 2.71 | 180.78 |
October | 1.90 | 169.09 |
November | 1.13 | 124.40 |
December | 0.00 | 0.00 |
Annual Sum or Average | 10.28 | 159.76 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.71 | 224.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 14.45 |
February | 0.38 | 8.69 |
March | 6.78 | 11.28 |
April | 13.51 | 12.45 |
May | 10.38 | 13.84 |
June | 5.87 | 16.32 |
July | 1.57 | 17.50 |
August | 2.81 | 18.34 |
September | 17.07 | 12.89 |
October | 22.10 | 10.85 |
November | 8.21 | 13.07 |
December | 0.00 | 0.00 |
Annual Sum or Average | 89.07 | 12.79 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 22.10 | 18.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.341277E+12 | 0.00 | 27129571.09 | 0.352663E+11 | 0.00 | 0.00 |
February | 0.239518E+12 | 0.00 | 0.101641E+09 | 0.325166E+11 | 0.00 | 0.00 |
March | 0.691356E+11 | 0.00 | 0.486427E+10 | 0.377410E+11 | 0.00 | 0.00 |
April | 0.310258E+11 | 0.00 | 0.590194E+11 | 0.370887E+11 | 0.00 | 0.00 |
May | 0.149847E+11 | 0.00 | 0.147833E+12 | 0.380402E+11 | 0.00 | 0.00 |
June | 0.965899E+10 | 0.00 | 0.390311E+12 | 0.355351E+11 | 0.00 | 0.00 |
July | 0.464815E+10 | 0.00 | 0.568481E+12 | 0.355845E+11 | 0.00 | 0.00 |
August | 0.564147E+10 | 0.00 | 0.489447E+12 | 0.359833E+11 | 0.00 | 0.00 |
September | 0.141243E+11 | 0.00 | 0.189158E+12 | 0.365129E+11 | 0.00 | 0.00 |
October | 0.236947E+11 | 0.00 | 0.158020E+11 | 0.394649E+11 | 0.00 | 0.00 |
November | 0.988302E+11 | 0.00 | 0.185314E+10 | 0.367855E+11 | 0.00 | 0.00 |
December | 0.167022E+12 | 0.00 | 41389678.57 | 0.363390E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.101956E+13 | 0.00 | 0.186694E+13 | 0.436858E+12 | 0.00 | 0.00 |
Minimum of Months | 0.464815E+10 | 0.00 | 27129571.09 | 0.325166E+11 | 0.00 | 0.00 |
Maximum of Months | 0.341277E+12 | 0.00 | 0.568481E+12 | 0.394649E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.328701E+11 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
February | 0.210404E+11 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
March | 0.626738E+10 | 0.00 | 0.508253E+09 | 0.587767E+10 | 0.00 | 0.00 |
April | 0.152675E+10 | 0.00 | 0.833358E+10 | 0.568807E+10 | 0.00 | 0.00 |
May | 23924.55 | 0.00 | 0.198488E+11 | 0.587767E+10 | 0.00 | 0.00 |
June | 20331.40 | 0.00 | 0.574063E+11 | 0.568807E+10 | 0.00 | 0.00 |
July | 19319.39 | 0.00 | 0.840494E+11 | 0.587767E+10 | 0.00 | 0.00 |
August | 26873.37 | 0.00 | 0.718932E+11 | 0.587767E+10 | 0.00 | 0.00 |
September | 6484317.86 | 0.00 | 0.267999E+11 | 0.568807E+10 | 0.00 | 0.00 |
October | 55810184.55 | 0.00 | 0.189034E+10 | 0.587767E+10 | 0.00 | 0.00 |
November | 0.875377E+10 | 0.00 | 69741438.72 | 0.568807E+10 | 0.00 | 0.00 |
December | 0.175096E+11 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.880304E+11 | 0.00 | 0.270799E+12 | 0.692049E+11 | 0.00 | 0.00 |
Minimum of Months | 19319.39 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.328701E+11 | 0.00 | 0.840494E+11 | 0.587767E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.352663E+11 | 27129571.09 | 0.341277E+12 | 0.759581E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325166E+11 | 0.101641E+09 | 0.239518E+12 | 0.557580E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377410E+11 | 0.486427E+10 | 0.691356E+11 | 0.556125E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370887E+11 | 0.590194E+11 | 0.310258E+11 | 0.327262E+12 | 0.845921E+10 | 0.00 | 0.00 | 0.00 |
May | 0.380402E+11 | 0.147833E+12 | 0.149847E+11 | 0.773166E+11 | 0.100577E+11 | 0.00 | 0.00 | 0.00 |
June | 0.355351E+11 | 0.390311E+12 | 0.965899E+10 | 0.233726E+11 | 0.699041E+11 | 0.00 | 0.00 | 0.00 |
July | 0.355845E+11 | 0.568481E+12 | 0.464815E+10 | 0.305322E+10 | 0.865693E+11 | 0.00 | 0.00 | 0.00 |
August | 0.359833E+11 | 0.489447E+12 | 0.564147E+10 | 0.616631E+10 | 0.783470E+11 | 0.00 | 0.00 | 0.00 |
September | 0.365129E+11 | 0.189158E+12 | 0.141243E+11 | 0.851729E+11 | 0.151931E+11 | 0.00 | 0.00 | 0.00 |
October | 0.394649E+11 | 0.158020E+11 | 0.236947E+11 | 0.287294E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367855E+11 | 0.185314E+10 | 0.988302E+11 | 0.503007E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363390E+11 | 41389678.57 | 0.167022E+12 | 0.794849E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436858E+12 | 0.186694E+13 | 0.101956E+13 | 0.398078E+13 | 0.268530E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325166E+11 | 27129571.09 | 0.464815E+10 | 0.305322E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394649E+11 | 0.568481E+12 | 0.341277E+12 | 0.794849E+12 | 0.865693E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587767E+10 | 0.00 | 0.328701E+11 | 0.134382E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.00 | 0.210404E+11 | 0.972395E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.508253E+09 | 0.626738E+10 | 0.971541E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.833358E+10 | 0.152675E+10 | 0.594905E+11 | 0.194215E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.198488E+11 | 23924.55 | 0.176121E+11 | 0.187569E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.574063E+11 | 20331.40 | 0.623157E+10 | 0.152116E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.840494E+11 | 19319.39 | 0.874479E+09 | 0.189347E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.718932E+11 | 26873.37 | 0.205318E+10 | 0.164723E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.267999E+11 | 6484317.86 | 0.187944E+11 | 0.437436E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.189034E+10 | 55810184.55 | 0.555035E+11 | 279905.44 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 69741438.72 | 0.875377E+10 | 0.895451E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.00 | 0.175096E+11 | 0.137355E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.270799E+12 | 0.880304E+11 | 0.716235E+12 | 0.588111E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530887E+10 | 0.00 | 19319.39 | 0.874479E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.840494E+11 | 0.328701E+11 | 0.137355E+12 | 0.189347E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.352663E+11 | 0.341277E+12 | 27129571.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325166E+11 | 0.239518E+12 | 0.101641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377410E+11 | 0.691356E+11 | 0.486427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370887E+11 | 0.310258E+11 | 0.590194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.380402E+11 | 0.149847E+11 | 0.147833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355351E+11 | 0.965899E+10 | 0.390311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.355845E+11 | 0.464815E+10 | 0.568481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.359833E+11 | 0.564147E+10 | 0.489447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365129E+11 | 0.141243E+11 | 0.189158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394649E+11 | 0.236947E+11 | 0.158020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367855E+11 | 0.988302E+11 | 0.185314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363390E+11 | 0.167022E+12 | 41389678.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436858E+12 | 0.101956E+13 | 0.186694E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.325166E+11 | 0.464815E+10 | 27129571.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394649E+11 | 0.341277E+12 | 0.568481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.587767E+10 | 0.328701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.210404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.626738E+10 | 0.508253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.152675E+10 | 0.833358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 23924.55 | 0.198488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 20331.40 | 0.574063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 19319.39 | 0.840494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 26873.37 | 0.718932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 6484317.86 | 0.267999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 55810184.55 | 0.189034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.875377E+10 | 69741438.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.175096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.880304E+11 | 0.270799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530887E+10 | 19319.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.328701E+11 | 0.840494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605560E+11 | 0.00 | 0.00 | 107047.97 | 0.00 | 0.153269E+11 | 0.104819E+10 | 0.00 | 0.99 |
February | 0.363860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268479E+11 | 0.00 | 0.00 | 0.98 |
March | 0.494633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 0.417759E+11 | 0.00 | 13183464.02 | 0.00 | 0.877917E+09 | 0.00 | 0.00 | 104719.96 | 0.97 |
May | 0.366986E+11 | 0.00 | 727183.25 | 0.00 | 0.134270E+10 | 0.00 | 0.00 | 31.09 | 1.01 |
June | 0.196979E+11 | 0.00 | 0.00 | 0.00 | 0.894972E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.100260E+11 | 0.00 | 0.00 | 0.00 | 0.152247E+11 | 0.00 | 0.00 | 0.00 | 1.03 |
August | 0.154600E+11 | 0.00 | 0.00 | 0.00 | 0.121715E+11 | 0.00 | 0.00 | 0.00 | 1.03 |
September | 0.204736E+11 | 0.00 | 0.00 | 14581263.76 | 0.132013E+10 | 0.00 | 0.131864E+11 | 0.00 | 1.02 |
October | 0.810393E+10 | 0.00 | 0.00 | 54949841.92 | 0.00 | 0.00 | 0.431490E+11 | 0.00 | 1.02 |
November | 0.165849E+11 | 0.00 | 0.00 | 42761847.14 | 0.00 | 0.00 | 0.382177E+11 | 0.00 | 1.02 |
December | 0.264741E+11 | 0.00 | 0.00 | 17457747.60 | 0.00 | 0.00 | 0.319916E+11 | 0.00 | 0.99 |
Annual Sum or Average | 0.341700E+12 | 0.00 | 13910647.28 | 0.129858E+09 | 0.398867E+11 | 0.421748E+11 | 0.127593E+12 | 104751.05 | 1.00 |
Minimum of Months | 0.810393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.605560E+11 | 0.00 | 13183464.02 | 54949841.92 | 0.152247E+11 | 0.268479E+11 | 0.431490E+11 | 104719.96 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106392E+10 | 0.00 | 0.00 | 35319.41 | 0.00 | 0.886132E+10 | 88138603.23 | 0.00 | 2.33 |
February | 0.166975E+10 | 0.00 | 0.00 | 203610.62 | 0.00 | 0.644902E+10 | 0.127142E+09 | 0.00 | 2.32 |
March | 0.347887E+10 | 0.00 | 0.00 | 131986.48 | 0.00 | 0.281943E+10 | 0.141470E+09 | 0.00 | 2.30 |
April | 0.397615E+10 | 77430948.79 | 0.00 | 63423.42 | 40398852.28 | 0.139907E+10 | 62167085.52 | 0.00 | 2.30 |
May | 0.477602E+10 | 4107843.13 | 0.00 | 236.56 | 0.170750E+09 | 0.00 | 593860.62 | 0.00 | 2.38 |
June | 0.256306E+10 | 0.224380E+09 | 0.00 | 1162.24 | 0.940495E+09 | 0.00 | 775605.69 | 0.00 | 2.40 |
July | 0.130496E+10 | 0.277921E+09 | 0.00 | 0.00 | 0.170369E+10 | 0.00 | 0.00 | 0.00 | 2.43 |
August | 0.200682E+10 | 0.370402E+09 | 0.00 | 40136.24 | 0.121382E+10 | 0.00 | 5376594.80 | 0.00 | 2.43 |
September | 0.397634E+10 | 0.132526E+09 | 0.00 | 535066.07 | 56098819.01 | 0.115477E+09 | 0.198680E+09 | 0.00 | 2.40 |
October | 0.538221E+10 | 0.00 | 0.00 | 1564407.67 | 0.00 | 0.355359E+09 | 0.645623E+09 | 0.00 | 2.33 |
November | 0.316243E+10 | 0.00 | 0.00 | 410029.06 | 0.00 | 0.348290E+10 | 0.237803E+09 | 0.00 | 2.31 |
December | 0.128697E+10 | 0.00 | 0.00 | 192740.75 | 0.00 | 0.601504E+10 | 0.212529E+09 | 0.00 | 2.31 |
Annual Sum or Average | 0.346475E+11 | 0.108677E+10 | 0.00 | 3178118.52 | 0.412525E+10 | 0.294976E+11 | 0.172030E+10 | 0.00 | 2.35 |
Minimum of Months | 0.106392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
Maximum of Months | 0.538221E+10 | 0.370402E+09 | 0.00 | 1564407.67 | 0.170369E+10 | 0.886132E+10 | 0.645623E+09 | 0.00 | 2.43 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224073E+10 | 0.00 | 0.00 | 1.46 |
February | 0.362564E+10 | 0.00 | 0.00 | 202.83 | 0.00 | 0.231980E+10 | 5398770.48 | 0.00 | 1.45 |
March | 0.459761E+10 | 0.00 | 0.00 | 17620.79 | 0.00 | 0.00 | 57284724.03 | 0.00 | 1.44 |
April | 0.373925E+10 | 4083486.68 | 0.00 | 126036.40 | 79786336.10 | 0.00 | 0.193789E+09 | 0.00 | 1.44 |
May | 0.317532E+10 | 3263335.92 | 0.00 | 77517.11 | 0.123164E+09 | 0.00 | 0.278255E+09 | 0.00 | 1.49 |
June | 0.168837E+10 | 56466111.63 | 0.00 | 83432.92 | 0.785777E+09 | 0.00 | 0.165287E+09 | 0.00 | 1.50 |
July | 0.902566E+09 | 0.193101E+09 | 0.00 | 39048.91 | 0.123967E+10 | 0.00 | 40926631.62 | 0.00 | 1.52 |
August | 0.119815E+10 | 0.115700E+09 | 0.00 | 196780.55 | 0.102974E+10 | 0.00 | 0.256568E+09 | 0.00 | 1.52 |
September | 0.266773E+10 | 9686866.65 | 0.00 | 317740.61 | 0.114549E+09 | 0.00 | 0.432489E+09 | 0.00 | 1.48 |
October | 0.405960E+10 | 0.00 | 0.00 | 223769.69 | 0.00 | 0.00 | 0.477624E+09 | 0.00 | 1.43 |
November | 0.445134E+10 | 0.00 | 0.00 | 70770.21 | 0.00 | 0.357823E+09 | 0.137067E+09 | 0.00 | 1.44 |
December | 0.542309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
Annual Sum or Average | 0.405278E+11 | 0.382301E+09 | 0.00 | 1152920.01 | 0.337269E+10 | 0.491834E+10 | 0.204469E+10 | 0.00 | 1.47 |
Minimum of Months | 0.902566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
Maximum of Months | 0.542309E+10 | 0.193101E+09 | 0.00 | 317740.61 | 0.123967E+10 | 0.231980E+10 | 0.477624E+09 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480635E+10 | 0.00 | 0.00 | 0.64 |
February | 0.264525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288940E+10 | 0.00 | 0.00 | 0.63 |
March | 0.405412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275235E+09 | 0.00 | 0.00 | 0.63 |
April | 0.365125E+10 | 0.00 | 0.00 | 0.00 | 78004116.12 | 5247295.99 | 0.00 | 0.00 | 0.63 |
May | 0.321211E+10 | 0.00 | 0.00 | 0.00 | 0.117586E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
June | 0.172409E+10 | 0.00 | 0.00 | 0.00 | 0.783338E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.877543E+09 | 0.00 | 0.00 | 0.00 | 0.133257E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.135316E+10 | 0.00 | 0.00 | 0.00 | 0.106533E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.288336E+10 | 0.00 | 0.00 | 0.00 | 0.115547E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.422002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.365324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946195E+09 | 0.00 | 0.00 | 0.63 |
December | 0.339834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164547E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.335997E+11 | 0.00 | 0.00 | 0.00 | 0.349237E+10 | 0.105679E+11 | 0.00 | 0.00 | 0.64 |
Minimum of Months | 0.877543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.422002E+10 | 0.00 | 0.00 | 0.00 | 0.133257E+10 | 0.480635E+10 | 0.00 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300967E+10 | 0.00 | 0.00 | 0.52 |
February | 0.437125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214304E+10 | 0.00 | 0.00 | 0.51 |
March | 0.111427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904009E+09 | 0.00 | 0.00 | 0.51 |
April | 0.149993E+10 | 0.00 | 0.00 | 0.00 | 36364321.70 | 0.204674E+09 | 0.00 | 0.00 | 0.51 |
May | 0.149743E+10 | 0.00 | 0.00 | 0.00 | 54816593.05 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.803745E+09 | 0.00 | 0.00 | 0.00 | 0.365180E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.409097E+09 | 0.00 | 0.00 | 0.00 | 0.621222E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.630821E+09 | 0.00 | 0.00 | 0.00 | 0.496642E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.134418E+10 | 0.00 | 0.00 | 0.00 | 53866174.88 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.196731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.124557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898612E+09 | 0.00 | 0.00 | 0.51 |
December | 0.307719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204363E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.113866E+11 | 0.00 | 0.00 | 0.00 | 0.162809E+10 | 0.920364E+10 | 0.00 | 0.00 | 0.52 |
Minimum of Months | 0.129395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.196731E+10 | 0.00 | 0.00 | 0.00 | 0.621222E+09 | 0.300967E+10 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359650E+10 | 0.00 | 0.00 | 79232373.21 | 0.00 | 0.242789E+11 | 0.875144E+11 | 0.00 | 23.33 |
February | 0.189301E+10 | 0.00 | 0.00 | 71707433.32 | 0.00 | 0.254391E+11 | 0.669734E+11 | 0.00 | 23.18 |
March | 0.500817E+09 | 0.00 | 0.00 | 97556898.40 | 0.00 | 0.00 | 0.767459E+11 | 0.00 | 23.50 |
April | 0.440431E+09 | 0.122198E+10 | 0.00 | 97397807.13 | 34613826.47 | 0.00 | 0.647614E+11 | 0.00 | 23.35 |
May | 0.812178E+09 | 0.188243E+10 | 0.00 | 92833818.49 | 42968045.95 | 0.00 | 0.559487E+11 | 0.00 | 23.94 |
June | 0.516404E+09 | 0.126440E+11 | 0.00 | 53853282.62 | 0.263944E+09 | 0.00 | 0.292589E+11 | 0.00 | 23.51 |
July | 0.182012E+09 | 0.221069E+11 | 0.00 | 30935945.83 | 0.349208E+09 | 0.00 | 0.142756E+11 | 0.00 | 23.47 |
August | 0.521650E+09 | 0.175245E+11 | 0.00 | 44753581.31 | 0.282669E+09 | 0.00 | 0.224180E+11 | 0.00 | 23.73 |
September | 0.488788E+09 | 0.183187E+10 | 0.00 | 90128634.26 | 53715778.79 | 0.00 | 0.505808E+11 | 0.00 | 23.60 |
October | 0.100391E+10 | 0.00 | 0.00 | 0.106411E+09 | 0.00 | 0.00 | 0.745850E+11 | 0.00 | 23.24 |
November | 0.151299E+10 | 0.00 | 0.00 | 94448701.77 | 0.00 | 0.291184E+10 | 0.767980E+11 | 0.00 | 23.32 |
December | 0.799743E+09 | 0.00 | 0.00 | 90295884.29 | 0.00 | 0.00 | 0.880439E+11 | 0.00 | 23.32 |
Annual Sum or Average | 0.122684E+11 | 0.572117E+11 | 0.00 | 0.949555E+09 | 0.102712E+10 | 0.526299E+11 | 0.707904E+12 | 0.00 | 23.46 |
Minimum of Months | 0.182012E+09 | 0.00 | 0.00 | 30935945.83 | 0.00 | 0.00 | 0.142756E+11 | 0.00 | 23.18 |
Maximum of Months | 0.359650E+10 | 0.221069E+11 | 0.00 | 0.106411E+09 | 0.349208E+09 | 0.254391E+11 | 0.880439E+11 | 0.00 | 23.94 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254538E+11 | 0.00 | 0.00 | 506286.41 | 0.00 | 0.163935E+11 | 0.101025E+10 | 0.00 | 3.55 |
February | 0.194146E+11 | 0.00 | 0.00 | 1603261.18 | 0.00 | 0.136140E+11 | 0.226122E+10 | 0.00 | 3.54 |
March | 0.217822E+11 | 0.00 | 0.00 | 3191553.35 | 0.00 | 0.454697E+09 | 0.533036E+10 | 0.00 | 3.51 |
April | 0.156196E+11 | 0.407566E+09 | 0.00 | 5465308.66 | 93474419.26 | 48702429.85 | 0.761162E+10 | 0.00 | 3.52 |
May | 0.964798E+10 | 0.245077E+09 | 0.00 | 7056508.85 | 0.503307E+09 | 0.00 | 0.107910E+11 | 0.00 | 3.64 |
June | 0.471429E+10 | 0.306610E+10 | 0.00 | 5948275.45 | 0.191971E+10 | 0.00 | 0.625290E+10 | 0.00 | 3.66 |
July | 0.139317E+10 | 0.510012E+10 | 0.00 | 4714300.79 | 0.338112E+10 | 0.00 | 0.418732E+10 | 0.00 | 3.71 |
August | 0.182549E+10 | 0.404577E+10 | 0.00 | 8653927.95 | 0.273464E+10 | 0.00 | 0.677863E+10 | 0.00 | 3.72 |
September | 0.772380E+10 | 0.650331E+09 | 0.00 | 12300003.92 | 0.115133E+09 | 0.00 | 0.106673E+11 | 0.00 | 3.65 |
October | 0.137038E+11 | 0.00 | 0.00 | 14294515.99 | 0.00 | 0.00 | 0.136088E+11 | 0.00 | 3.55 |
November | 0.210525E+11 | 0.00 | 0.00 | 5036889.40 | 0.00 | 0.259984E+10 | 0.581570E+10 | 0.00 | 3.52 |
December | 0.249506E+11 | 0.00 | 0.00 | 1457653.73 | 0.00 | 0.538478E+10 | 0.183644E+10 | 0.00 | 3.51 |
Annual Sum or Average | 0.167282E+12 | 0.135150E+11 | 0.00 | 70228485.67 | 0.874739E+10 | 0.384955E+11 | 0.761515E+11 | 0.00 | 3.59 |
Minimum of Months | 0.139317E+10 | 0.00 | 0.00 | 506286.41 | 0.00 | 0.00 | 0.101025E+10 | 0.00 | 3.51 |
Maximum of Months | 0.254538E+11 | 0.510012E+10 | 0.00 | 14294515.99 | 0.338112E+10 | 0.163935E+11 | 0.136088E+11 | 0.00 | 3.72 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104102E+12 | 0.00 | 0.00 | 370089.14 | 0.00 | 0.416833E+11 | 0.115688E+10 | 0.00 | 1.76 |
February | 0.721631E+11 | 0.00 | 0.00 | 1099204.76 | 0.00 | 0.449735E+11 | 0.364263E+10 | 0.00 | 1.75 |
March | 0.801317E+11 | 0.00 | 0.00 | 7383862.41 | 0.00 | 0.00 | 0.143824E+11 | 0.00 | 1.74 |
April | 0.568738E+11 | 0.150131E+09 | 0.00 | 16783818.15 | 0.155212E+10 | 0.00 | 0.230908E+11 | 0.00 | 1.74 |
May | 0.362177E+11 | 0.121757E+09 | 0.00 | 23926478.43 | 0.244427E+10 | 0.00 | 0.339557E+11 | 0.00 | 1.80 |
June | 0.176649E+11 | 0.413879E+10 | 0.00 | 15928120.36 | 0.129557E+11 | 0.00 | 0.199686E+11 | 0.00 | 1.81 |
July | 0.732601E+10 | 0.991233E+10 | 0.00 | 8885820.36 | 0.191677E+11 | 0.00 | 0.118154E+11 | 0.00 | 1.84 |
August | 0.901134E+10 | 0.616180E+10 | 0.00 | 21225653.71 | 0.170866E+11 | 0.00 | 0.205224E+11 | 0.00 | 1.84 |
September | 0.292849E+11 | 0.447612E+09 | 0.00 | 32798801.07 | 0.207392E+10 | 0.00 | 0.339449E+11 | 0.00 | 1.80 |
October | 0.542505E+11 | 0.00 | 0.00 | 26860276.92 | 0.00 | 0.00 | 0.382133E+11 | 0.00 | 1.73 |
November | 0.767583E+11 | 0.00 | 0.00 | 14200967.87 | 0.00 | 0.594099E+10 | 0.178120E+11 | 0.00 | 1.74 |
December | 0.107882E+12 | 0.00 | 0.00 | 430632.91 | 0.00 | 0.00 | 0.218627E+10 | 0.00 | 1.74 |
Annual Sum or Average | 0.651667E+12 | 0.209324E+11 | 0.00 | 0.169894E+09 | 0.552803E+11 | 0.925978E+11 | 0.220691E+12 | 0.00 | 1.77 |
Minimum of Months | 0.732601E+10 | 0.00 | 0.00 | 370089.14 | 0.00 | 0.00 | 0.115688E+10 | 0.00 | 1.73 |
Maximum of Months | 0.107882E+12 | 0.991233E+10 | 0.00 | 32798801.07 | 0.191677E+11 | 0.449735E+11 | 0.382133E+11 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229541E+09 | 0.00 | 0.00 | 37740.72 | 0.00 | 0.261235E+10 | 3021235.34 | 0.00 | 0.47 |
February | 0.237716E+09 | 0.00 | 0.00 | 489286.33 | 0.00 | 0.218002E+10 | 41586536.75 | 0.00 | 0.47 |
March | 0.378723E+09 | 0.00 | 0.00 | 1418061.34 | 0.00 | 0.108203E+10 | 0.190688E+09 | 0.00 | 0.47 |
April | 0.305921E+09 | 34677440.94 | 392.59 | 4568656.07 | 2186485.24 | 0.649686E+09 | 0.427774E+09 | 1131.64 | 0.47 |
May | 0.263894E+09 | 44503011.57 | 145876.69 | 6717561.34 | 10973230.05 | 0.166152E+09 | 0.808725E+09 | 3783.05 | 0.47 |
June | 0.120275E+09 | 0.354488E+09 | 287840.32 | 4484784.97 | 34168412.42 | 82233694.42 | 0.418317E+09 | 17092.36 | 0.48 |
July | 27128684.65 | 0.563001E+09 | 436812.43 | 3366096.60 | 56777410.88 | 386009.39 | 0.252281E+09 | 16600.04 | 0.48 |
August | 36635076.91 | 0.415199E+09 | 399731.15 | 4359398.51 | 60524122.10 | 514928.93 | 0.401927E+09 | 16448.43 | 0.48 |
September | 0.215944E+09 | 73607853.26 | 8230.76 | 5679052.71 | 4840679.75 | 0.246762E+09 | 0.601189E+09 | 604.16 | 0.47 |
October | 0.406988E+09 | 0.00 | 0.00 | 3568860.01 | 0.00 | 0.763744E+09 | 0.458259E+09 | 0.00 | 0.47 |
November | 0.339036E+09 | 0.00 | 0.00 | 770030.42 | 0.00 | 0.126337E+10 | 0.161389E+09 | 0.00 | 0.47 |
December | 0.242918E+09 | 0.00 | 0.00 | 61275.76 | 0.00 | 0.164334E+10 | 5424542.10 | 0.00 | 0.47 |
Annual Sum or Average | 0.280472E+10 | 0.148548E+10 | 1278883.94 | 35520804.79 | 0.169470E+09 | 0.106906E+11 | 0.377058E+10 | 55659.67 | 0.47 |
Minimum of Months | 27128684.65 | 0.00 | 0.00 | 37740.72 | 0.00 | 386009.39 | 3021235.34 | 0.00 | 0.47 |
Maximum of Months | 0.406988E+09 | 0.563001E+09 | 436812.43 | 6717561.34 | 60524122.10 | 0.261235E+10 | 0.808725E+09 | 17092.36 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91288886.97 | 0.00 | 0.00 | 5348.04 | 0.00 | 0.275317E+10 | 492419.57 | 0.00 | 0.47 |
February | 0.168506E+09 | 0.00 | 0.00 | 158678.51 | 0.00 | 0.227310E+10 | 18042564.49 | 0.00 | 0.47 |
March | 0.339950E+09 | 0.00 | 0.00 | 649735.08 | 0.00 | 0.121217E+10 | 0.100088E+09 | 0.00 | 0.47 |
April | 0.322498E+09 | 31596059.20 | 18.21 | 3484520.02 | 5267866.98 | 0.692585E+09 | 0.369383E+09 | 1506.02 | 0.47 |
May | 0.271060E+09 | 37900896.20 | 144590.94 | 6073698.27 | 17575345.43 | 0.192977E+09 | 0.775378E+09 | 5068.80 | 0.47 |
June | 0.123133E+09 | 0.350651E+09 | 286820.04 | 4373977.06 | 38005048.72 | 85940726.20 | 0.411863E+09 | 18112.64 | 0.48 |
July | 28688628.26 | 0.551841E+09 | 439842.59 | 3256680.57 | 67932704.32 | 386009.39 | 0.250831E+09 | 18271.68 | 0.48 |
August | 41347107.17 | 0.397790E+09 | 397541.73 | 3973674.46 | 77933347.44 | 538069.72 | 0.397577E+09 | 18637.85 | 0.48 |
September | 0.243694E+09 | 69071503.74 | 21125.25 | 4404492.96 | 9361376.76 | 0.302710E+09 | 0.518765E+09 | 3362.18 | 0.47 |
October | 0.445186E+09 | 0.00 | 0.00 | 1677469.17 | 0.00 | 0.894676E+09 | 0.291019E+09 | 0.00 | 0.47 |
November | 0.293491E+09 | 0.00 | 0.00 | 305763.00 | 0.00 | 0.140667E+10 | 64098864.15 | 0.00 | 0.47 |
December | 0.130627E+09 | 0.00 | 0.00 | 7985.70 | 0.00 | 0.176085E+10 | 262190.79 | 0.00 | 0.47 |
Annual Sum or Average | 0.249947E+10 | 0.143885E+10 | 1289938.77 | 28372022.83 | 0.216076E+09 | 0.115758E+11 | 0.319780E+10 | 64959.17 | 0.47 |
Minimum of Months | 28688628.26 | 0.00 | 0.00 | 5348.04 | 0.00 | 386009.39 | 262190.79 | 0.00 | 0.47 |
Maximum of Months | 0.445186E+09 | 0.551841E+09 | 439842.59 | 6073698.27 | 77933347.44 | 0.275317E+10 | 0.775378E+09 | 18637.85 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270765E+11 | 0.00 | 0.00 | 0.53 |
February | 0.154769E+11 | 0.00 | 0.00 | 716293.23 | 0.00 | 0.176577E+11 | 0.213704E+09 | 0.00 | 0.53 |
March | 0.160088E+11 | 0.00 | 0.00 | 3188231.05 | 0.00 | 0.551060E+10 | 0.886132E+09 | 0.00 | 0.54 |
April | 0.159732E+11 | 0.496448E+09 | 0.00 | 8151594.57 | 3358543.35 | 0.101920E+10 | 0.181672E+10 | 0.00 | 0.54 |
May | 0.123345E+11 | 0.744858E+09 | 0.00 | 12448626.08 | 9294979.76 | 0.00 | 0.453889E+10 | 0.00 | 0.54 |
June | 0.537726E+10 | 0.506860E+10 | 0.00 | 13776131.93 | 0.204785E+09 | 0.00 | 0.308667E+10 | 0.00 | 0.54 |
July | 0.241857E+10 | 0.817487E+10 | 0.00 | 8690821.51 | 0.233971E+09 | 0.00 | 0.141174E+10 | 0.00 | 0.54 |
August | 0.265651E+10 | 0.622759E+10 | 0.00 | 16834526.58 | 0.227716E+09 | 0.00 | 0.333858E+10 | 0.00 | 0.54 |
September | 0.867483E+10 | 0.105431E+10 | 0.00 | 35580445.53 | 9386010.56 | 0.00 | 0.579044E+10 | 0.00 | 0.54 |
October | 0.159762E+11 | 0.00 | 0.00 | 37353767.44 | 0.00 | 0.00 | 0.612005E+10 | 0.00 | 0.54 |
November | 0.144614E+11 | 0.00 | 0.00 | 10659186.46 | 0.00 | 0.767224E+10 | 0.177897E+10 | 0.00 | 0.53 |
December | 0.107642E+11 | 0.00 | 0.00 | 1260033.11 | 0.00 | 0.144213E+11 | 0.460719E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.131617E+12 | 0.217667E+11 | 0.00 | 0.148660E+09 | 0.688512E+09 | 0.733575E+11 | 0.294426E+11 | 0.00 | 0.54 |
Minimum of Months | 0.241857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.160088E+11 | 0.817487E+10 | 0.00 | 37353767.44 | 0.233971E+09 | 0.270765E+11 | 0.612005E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.523057E+10 | 0.00 | 0.00 | 329543.32 | 0.00 | 0.330481E+11 | 0.291706E+09 | 0.00 | 0.53 |
February | 0.463560E+10 | 0.00 | 0.00 | 1453074.78 | 0.00 | 0.271646E+11 | 0.154742E+10 | 0.00 | 0.53 |
March | 0.602248E+10 | 0.00 | 0.00 | 13524280.40 | 0.00 | 0.954256E+10 | 0.683018E+10 | 0.00 | 0.54 |
April | 0.492407E+10 | 0.230899E+09 | 0.00 | 34618577.54 | 0.268907E+09 | 0.320682E+10 | 0.106517E+11 | 0.00 | 0.54 |
May | 0.393566E+10 | 0.312502E+09 | 463050.96 | 77143765.33 | 0.441180E+09 | 42643036.60 | 0.128304E+11 | 8159.82 | 0.54 |
June | 0.180096E+10 | 0.369019E+10 | 1888286.20 | 50817745.64 | 0.158128E+10 | 16574115.03 | 0.660935E+10 | 29698.98 | 0.54 |
July | 0.457665E+09 | 0.581370E+10 | 1828788.02 | 33895645.33 | 0.259328E+10 | 1684008.48 | 0.334575E+10 | 34704.14 | 0.54 |
August | 0.622841E+09 | 0.397077E+10 | 1261667.02 | 44636255.89 | 0.248326E+10 | 3556321.98 | 0.534089E+10 | 14318.35 | 0.54 |
September | 0.343232E+10 | 0.618951E+09 | 439857.51 | 58709138.53 | 0.444275E+09 | 0.107961E+09 | 0.109019E+11 | 27285.43 | 0.54 |
October | 0.605372E+10 | 0.00 | 0.00 | 33120252.13 | 0.00 | 0.173085E+10 | 0.143159E+11 | 0.00 | 0.54 |
November | 0.588252E+10 | 0.00 | 0.00 | 14340529.05 | 0.00 | 0.117230E+11 | 0.630341E+10 | 0.00 | 0.54 |
December | 0.600049E+10 | 0.00 | 0.00 | 403020.45 | 0.00 | 0.193093E+11 | 0.337303E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.489989E+11 | 0.146370E+11 | 5881649.72 | 0.362992E+09 | 0.781218E+10 | 0.105898E+12 | 0.793059E+11 | 114166.73 | 0.54 |
Minimum of Months | 0.457665E+09 | 0.00 | 0.00 | 329543.32 | 0.00 | 1684008.48 | 0.291706E+09 | 0.00 | 0.53 |
Maximum of Months | 0.605372E+10 | 0.581370E+10 | 1888286.20 | 77143765.33 | 0.259328E+10 | 0.330481E+11 | 0.143159E+11 | 34704.14 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206369E+09 | 0.00 | 0.00 | 19491.45 | 0.00 | 0.263278E+10 | 5782939.01 | 0.00 | 0.47 |
February | 0.249480E+09 | 0.00 | 0.00 | 255697.39 | 0.00 | 0.217876E+10 | 31313767.01 | 0.00 | 0.47 |
March | 0.382409E+09 | 0.00 | 0.00 | 1199635.82 | 0.00 | 0.106625E+10 | 0.202996E+09 | 0.00 | 0.47 |
April | 0.306346E+09 | 35072398.38 | 18033.88 | 3732436.39 | 1773192.29 | 0.653146E+09 | 0.424725E+09 | 1825.86 | 0.47 |
May | 0.226205E+09 | 51684640.15 | 36387.31 | 7998116.08 | 3900062.36 | 0.130029E+09 | 0.881256E+09 | 4811.55 | 0.47 |
June | 0.102626E+09 | 0.364699E+09 | 178742.19 | 5291687.10 | 24075428.67 | 63898275.51 | 0.453495E+09 | 8637.04 | 0.48 |
July | 17725564.23 | 0.580452E+09 | 281294.48 | 3933950.18 | 39484335.84 | 160604.25 | 0.261342E+09 | 14021.91 | 0.48 |
August | 24369719.38 | 0.419908E+09 | 418073.78 | 4833500.28 | 55792685.58 | 3786192.08 | 0.410447E+09 | 20707.87 | 0.48 |
September | 0.200692E+09 | 74600131.54 | 25114.73 | 6469046.96 | 3826943.89 | 0.232443E+09 | 0.629970E+09 | 5177.77 | 0.47 |
October | 0.408892E+09 | 0.00 | 0.00 | 2916530.55 | 0.00 | 0.765983E+09 | 0.454768E+09 | 0.00 | 0.47 |
November | 0.336106E+09 | 0.00 | 0.00 | 607725.27 | 0.00 | 0.126073E+10 | 0.167123E+09 | 0.00 | 0.47 |
December | 0.244579E+09 | 0.00 | 0.00 | 57936.01 | 0.00 | 0.163284E+10 | 14266804.59 | 0.00 | 0.47 |
Annual Sum or Average | 0.270580E+10 | 0.152642E+10 | 957646.37 | 37315753.49 | 0.128853E+09 | 0.106208E+11 | 0.393748E+10 | 55182.01 | 0.47 |
Minimum of Months | 17725564.23 | 0.00 | 0.00 | 19491.45 | 0.00 | 160604.25 | 5782939.01 | 0.00 | 0.47 |
Maximum of Months | 0.408892E+09 | 0.580452E+09 | 418073.78 | 7998116.08 | 55792685.58 | 0.263278E+10 | 0.881256E+09 | 20707.87 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92433146.63 | 0.00 | 0.00 | 2284.78 | 0.00 | 0.275220E+10 | 321576.65 | 0.00 | 0.47 |
February | 0.176759E+09 | 0.00 | 0.00 | 66267.25 | 0.00 | 0.227108E+10 | 11907132.83 | 0.00 | 0.47 |
March | 0.362873E+09 | 0.00 | 0.00 | 514706.99 | 0.00 | 0.117365E+10 | 0.115815E+09 | 0.00 | 0.47 |
April | 0.318638E+09 | 34301047.42 | 44373.14 | 2781144.93 | 2517572.70 | 0.718640E+09 | 0.347890E+09 | 2457.16 | 0.47 |
May | 0.256424E+09 | 47721835.31 | 107183.09 | 7284123.32 | 7789874.60 | 0.150156E+09 | 0.831624E+09 | 7008.36 | 0.47 |
June | 0.105723E+09 | 0.363080E+09 | 178205.78 | 5168555.28 | 25692491.56 | 65894671.28 | 0.448524E+09 | 10754.90 | 0.48 |
July | 18020560.57 | 0.575337E+09 | 316347.58 | 3824432.97 | 44560266.23 | 220382.57 | 0.261097E+09 | 17332.59 | 0.48 |
August | 31112177.55 | 0.411772E+09 | 574794.17 | 4413278.34 | 63761661.94 | 6004042.80 | 0.401906E+09 | 30970.99 | 0.48 |
September | 0.231149E+09 | 72588339.61 | 134180.15 | 4975019.26 | 5719046.42 | 0.291950E+09 | 0.541500E+09 | 15801.75 | 0.47 |
October | 0.446519E+09 | 0.00 | 0.00 | 964999.20 | 0.00 | 0.902039E+09 | 0.283036E+09 | 0.00 | 0.47 |
November | 0.283893E+09 | 0.00 | 0.00 | 114329.01 | 0.00 | 0.142643E+10 | 54125051.41 | 0.00 | 0.47 |
December | 0.111469E+09 | 0.00 | 0.00 | 4783.34 | 0.00 | 0.177938E+10 | 888816.03 | 0.00 | 0.47 |
Annual Sum or Average | 0.243501E+10 | 0.150480E+10 | 1355083.92 | 30113924.66 | 0.150041E+09 | 0.115376E+11 | 0.329864E+10 | 84325.74 | 0.47 |
Minimum of Months | 18020560.57 | 0.00 | 0.00 | 2284.78 | 0.00 | 220382.57 | 321576.65 | 0.00 | 0.47 |
Maximum of Months | 0.446519E+09 | 0.575337E+09 | 574794.17 | 7284123.32 | 63761661.94 | 0.275220E+10 | 0.831624E+09 | 30970.99 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355899E+11 | 0.00 | 0.00 | 0.48 |
February | 0.370414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266742E+11 | 0.00 | 0.00 | 0.48 |
March | 0.121918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115710E+11 | 0.00 | 0.00 | 0.47 |
April | 0.151508E+11 | 0.00 | 0.00 | 0.00 | 0.428146E+09 | 0.491882E+10 | 0.00 | 0.00 | 0.47 |
May | 0.175179E+11 | 0.00 | 0.00 | 0.00 | 0.645399E+09 | 0.112605E+09 | 0.00 | 0.00 | 0.49 |
June | 0.946312E+10 | 0.00 | 0.00 | 0.00 | 0.429956E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.481662E+10 | 0.00 | 0.00 | 0.00 | 0.731414E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.742716E+10 | 0.00 | 0.00 | 0.00 | 0.584735E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.152511E+11 | 0.00 | 0.00 | 0.00 | 0.634209E+09 | 0.574950E+09 | 0.00 | 0.00 | 0.49 |
October | 0.203768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278582E+10 | 0.00 | 0.00 | 0.47 |
November | 0.101619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150833E+11 | 0.00 | 0.00 | 0.47 |
December | 0.320224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244820E+11 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.120632E+12 | 0.00 | 0.00 | 0.00 | 0.191688E+11 | 0.121793E+12 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.136880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.203768E+11 | 0.00 | 0.00 | 0.00 | 0.731414E+10 | 0.355899E+11 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33359069.47 | 0.00 | 0.00 | 8620.08 | 0.00 | 0.677385E+09 | 485132.77 | 0.00 | 0.47 |
February | 46293924.64 | 0.00 | 0.00 | 116656.31 | 0.00 | 0.560891E+09 | 7650205.35 | 0.00 | 0.47 |
March | 86104266.64 | 0.00 | 0.00 | 321239.40 | 0.00 | 0.293790E+09 | 32997879.92 | 0.00 | 0.47 |
April | 69928991.03 | 8773930.76 | 239.79 | 1215490.27 | 442050.79 | 0.177595E+09 | 98248017.65 | 141.27 | 0.47 |
May | 61683666.56 | 12318176.96 | 12813.40 | 1800395.46 | 1574773.64 | 61499957.55 | 0.186388E+09 | 711.34 | 0.47 |
June | 28622885.69 | 90244960.82 | 47526.50 | 1226386.46 | 6945369.87 | 27887452.99 | 98590952.40 | 2511.69 | 0.48 |
July | 6141569.11 | 0.143479E+09 | 90180.89 | 880963.99 | 11485293.27 | 84005.20 | 63684023.73 | 3484.52 | 0.48 |
August | 8426543.45 | 0.107315E+09 | 78685.39 | 1119093.47 | 11638053.12 | 1092147.19 | 0.100221E+09 | 2648.90 | 0.48 |
September | 52682383.37 | 18646377.25 | 415.71 | 1474591.44 | 967500.69 | 81354556.97 | 0.131882E+09 | 48.34 | 0.47 |
October | 0.102265E+09 | 0.00 | 0.00 | 871886.83 | 0.00 | 0.217691E+09 | 87311622.83 | 0.00 | 0.47 |
November | 71091464.43 | 0.00 | 0.00 | 177972.35 | 0.00 | 0.351594E+09 | 18278072.37 | 0.00 | 0.47 |
December | 49368804.31 | 0.00 | 0.00 | 11920.04 | 0.00 | 0.422966E+09 | 589149.45 | 0.00 | 0.47 |
Annual Sum or Average | 0.615969E+09 | 0.380778E+09 | 229861.68 | 9225216.10 | 33053041.38 | 0.287383E+10 | 0.826326E+09 | 9546.06 | 0.47 |
Minimum of Months | 6141569.11 | 0.00 | 0.00 | 8620.08 | 0.00 | 84005.20 | 485132.77 | 0.00 | 0.47 |
Maximum of Months | 0.102265E+09 | 0.143479E+09 | 90180.89 | 1800395.46 | 11638053.12 | 0.677385E+09 | 0.186388E+09 | 3484.52 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13190408.15 | 0.00 | 0.00 | 643.78 | 0.00 | 0.698021E+09 | 25910.42 | 0.00 | 0.47 |
February | 28347150.44 | 0.00 | 0.00 | 28273.58 | 0.00 | 0.582674E+09 | 3902333.68 | 0.00 | 0.47 |
March | 67362995.51 | 0.00 | 0.00 | 127952.28 | 0.00 | 0.325357E+09 | 20365853.67 | 0.00 | 0.47 |
April | 74194085.48 | 8368621.45 | 65.29 | 910277.85 | 847360.10 | 0.192018E+09 | 79865214.02 | 315.77 | 0.47 |
May | 65531486.85 | 11636998.36 | 12806.15 | 1625251.74 | 2255952.24 | 67357899.64 | 0.176857E+09 | 718.59 | 0.47 |
June | 29196108.40 | 89955524.26 | 47749.71 | 1197502.97 | 7234411.07 | 29303900.37 | 96630165.80 | 2683.84 | 0.48 |
July | 6506823.26 | 0.142864E+09 | 101945.75 | 852786.60 | 12088773.00 | 79092.26 | 63351859.91 | 3581.15 | 0.48 |
August | 9670715.78 | 0.105085E+09 | 78004.75 | 1018292.01 | 13868043.85 | 1213693.98 | 98956279.27 | 3329.55 | 0.48 |
September | 60229455.93 | 18075804.10 | 5582.86 | 1136136.96 | 1532416.03 | 94632714.20 | 0.111395E+09 | 538.99 | 0.47 |
October | 0.110619E+09 | 0.00 | 0.00 | 367173.71 | 0.00 | 0.250436E+09 | 46718087.11 | 0.00 | 0.47 |
November | 57142481.41 | 0.00 | 0.00 | 66021.03 | 0.00 | 0.377968E+09 | 5964569.11 | 0.00 | 0.47 |
December | 17962286.88 | 0.00 | 0.00 | 570.45 | 0.00 | 0.454948E+09 | 25515.69 | 0.00 | 0.47 |
Annual Sum or Average | 0.539953E+09 | 0.375986E+09 | 246154.51 | 7330882.97 | 37826956.29 | 0.307401E+10 | 0.704058E+09 | 11167.88 | 0.47 |
Minimum of Months | 6506823.26 | 0.00 | 0.00 | 570.45 | 0.00 | 79092.26 | 25515.69 | 0.00 | 0.47 |
Maximum of Months | 0.110619E+09 | 0.142864E+09 | 101945.75 | 1625251.74 | 13868043.85 | 0.698021E+09 | 0.176857E+09 | 3581.15 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.672368E+09 | 0.00 | 0.00 | 1440855.60 | 0.00 | 0.365395E+10 | 0.239821E+09 | 0.00 | 0.53 |
February | 0.733550E+09 | 0.00 | 0.00 | 2595427.05 | 0.00 | 0.288686E+10 | 0.326222E+09 | 0.00 | 0.54 |
March | 0.487387E+09 | 0.00 | 0.00 | 4715668.86 | 0.00 | 0.146165E+10 | 0.699912E+09 | 0.00 | 0.54 |
April | 0.425803E+09 | 56124623.95 | 8804.89 | 6984842.78 | 3053784.37 | 0.884132E+09 | 0.911439E+09 | 425.77 | 0.54 |
May | 0.379472E+09 | 79334912.36 | 20675.15 | 10211140.16 | 9949581.15 | 0.152677E+09 | 0.145728E+10 | 2454.92 | 0.54 |
June | 0.188427E+09 | 0.571059E+09 | 190174.10 | 6184085.43 | 53225206.92 | 40163255.98 | 0.769164E+09 | 5165.77 | 0.54 |
July | 41620724.37 | 0.905972E+09 | 293444.06 | 4486805.57 | 89507888.93 | 299735.61 | 0.408211E+09 | 11068.12 | 0.54 |
August | 51642283.33 | 0.676217E+09 | 185881.56 | 6587084.14 | 88035673.69 | 3642539.42 | 0.650066E+09 | 5493.72 | 0.54 |
September | 0.272546E+09 | 0.120196E+09 | 36202.07 | 11476585.76 | 5728351.35 | 0.193000E+09 | 0.124018E+10 | 2647.50 | 0.54 |
October | 0.454801E+09 | 0.00 | 0.00 | 13853277.17 | 0.00 | 0.640874E+09 | 0.151155E+10 | 0.00 | 0.54 |
November | 0.520536E+09 | 0.00 | 0.00 | 4637256.40 | 0.00 | 0.160106E+10 | 0.706790E+09 | 0.00 | 0.54 |
December | 0.368297E+09 | 0.00 | 0.00 | 2843798.66 | 0.00 | 0.233254E+10 | 0.333528E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.459645E+10 | 0.240890E+10 | 735181.82 | 76016827.56 | 0.249500E+09 | 0.138508E+11 | 0.925417E+10 | 27255.79 | 0.54 |
Minimum of Months | 41620724.37 | 0.00 | 0.00 | 1440855.60 | 0.00 | 299735.61 | 0.239821E+09 | 0.00 | 0.53 |
Maximum of Months | 0.733550E+09 | 0.905972E+09 | 293444.06 | 13853277.17 | 89507888.93 | 0.365395E+10 | 0.151155E+10 | 11068.12 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280395E+11 | 0.00 | 0.00 | 20585812.87 | 0.00 | 0.116509E+11 | 0.287100E+11 | 0.00 | 4.22 |
February | 0.114889E+11 | 0.00 | 0.00 | 25942031.32 | 0.00 | 0.192115E+11 | 0.262101E+11 | 0.00 | 4.27 |
March | 0.697244E+10 | 0.00 | 0.00 | 47997307.27 | 0.00 | 0.00 | 0.395008E+11 | 0.00 | 4.38 |
April | 0.235724E+10 | 0.735819E+09 | 0.00 | 61396217.52 | 57200144.69 | 0.00 | 0.387914E+11 | 0.00 | 4.54 |
May | 0.481704E+09 | 0.113971E+10 | 0.00 | 72138649.13 | 57968148.78 | 0.00 | 0.369124E+11 | 0.00 | 4.78 |
June | 0.283042E+09 | 0.799558E+10 | 0.00 | 47317410.50 | 0.245223E+09 | 0.00 | 0.199612E+11 | 0.00 | 4.74 |
July | 37033302.70 | 0.138053E+11 | 0.00 | 31782927.86 | 0.404532E+09 | 0.00 | 0.100191E+11 | 0.00 | 4.70 |
August | 0.132194E+09 | 0.107158E+11 | 0.00 | 41896354.16 | 0.484748E+09 | 0.00 | 0.158246E+11 | 0.00 | 4.75 |
September | 0.111787E+10 | 0.112244E+10 | 0.00 | 62662402.13 | 63868912.77 | 0.00 | 0.320182E+11 | 0.00 | 4.67 |
October | 0.288178E+10 | 0.00 | 0.00 | 62877450.42 | 0.00 | 0.00 | 0.442386E+11 | 0.00 | 4.48 |
November | 0.103394E+11 | 0.00 | 0.00 | 44155619.64 | 0.00 | 0.169747E+10 | 0.370458E+11 | 0.00 | 4.36 |
December | 0.179532E+11 | 0.00 | 0.00 | 28568064.96 | 0.00 | 0.00 | 0.337525E+11 | 0.00 | 4.20 |
Annual Sum or Average | 0.820842E+11 | 0.355147E+11 | 0.00 | 0.547320E+09 | 0.131354E+10 | 0.325599E+11 | 0.362985E+12 | 0.00 | 4.51 |
Minimum of Months | 37033302.70 | 0.00 | 0.00 | 20585812.87 | 0.00 | 0.00 | 0.100191E+11 | 0.00 | 4.20 |
Maximum of Months | 0.280395E+11 | 0.138053E+11 | 0.00 | 72138649.13 | 0.484748E+09 | 0.192115E+11 | 0.442386E+11 | 0.00 | 4.78 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252088E+11 | 0.00 | 0.00 | 28915531.67 | 0.00 | 0.117085E+11 | 0.356702E+11 | 0.00 | 4.50 |
February | 0.746003E+10 | 0.00 | 0.00 | 36082508.94 | 0.00 | 0.198306E+11 | 0.335772E+11 | 0.00 | 4.59 |
March | 0.258022E+10 | 0.00 | 0.00 | 64271411.48 | 0.00 | 0.00 | 0.480808E+11 | 0.00 | 4.77 |
April | 0.666033E+09 | 0.809286E+09 | 0.00 | 77778935.83 | 28933165.58 | 0.00 | 0.443477E+11 | 0.00 | 4.94 |
May | 0.113412E+09 | 0.124064E+10 | 0.00 | 87382177.34 | 28272728.66 | 0.00 | 0.406738E+11 | 0.00 | 5.18 |
June | 49055503.81 | 0.865224E+10 | 0.00 | 56057125.21 | 0.108256E+09 | 0.00 | 0.219116E+11 | 0.00 | 5.09 |
July | 19527399.89 | 0.149096E+11 | 0.00 | 36194885.47 | 0.221827E+09 | 0.00 | 0.108276E+11 | 0.00 | 5.02 |
August | 78807519.77 | 0.116364E+11 | 0.00 | 48247724.22 | 0.281051E+09 | 0.00 | 0.171177E+11 | 0.00 | 5.08 |
September | 0.321332E+09 | 0.120652E+10 | 0.00 | 76805736.68 | 47939084.79 | 0.00 | 0.357548E+11 | 0.00 | 5.04 |
October | 0.882845E+09 | 0.00 | 0.00 | 82541066.20 | 0.00 | 0.00 | 0.506948E+11 | 0.00 | 4.89 |
November | 0.706431E+10 | 0.00 | 0.00 | 58508501.27 | 0.00 | 0.154480E+10 | 0.444560E+11 | 0.00 | 4.72 |
December | 0.123698E+11 | 0.00 | 0.00 | 39914079.49 | 0.00 | 0.00 | 0.430239E+11 | 0.00 | 4.51 |
Annual Sum or Average | 0.568142E+11 | 0.384547E+11 | 0.00 | 0.692700E+09 | 0.716278E+09 | 0.330839E+11 | 0.426136E+12 | 0.00 | 4.86 |
Minimum of Months | 19527399.89 | 0.00 | 0.00 | 28915531.67 | 0.00 | 0.00 | 0.108276E+11 | 0.00 | 4.50 |
Maximum of Months | 0.252088E+11 | 0.149096E+11 | 0.00 | 87382177.34 | 0.281051E+09 | 0.198306E+11 | 0.506948E+11 | 0.00 | 5.18 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.415507E+10 | 0.00 | 0.00 | 99435697.81 | 0.00 | 0.126001E+11 | 0.766466E+11 | 0.00 | 19.33 |
February | 0.362584E+10 | 0.00 | 0.00 | 90646192.21 | 0.00 | 0.161800E+11 | 0.570321E+11 | 0.00 | 19.71 |
March | 4091085.77 | 0.00 | 0.00 | 0.127098E+09 | 0.00 | 0.00 | 0.680941E+11 | 0.00 | 20.81 |
April | 0.00 | 0.125163E+10 | 0.00 | 0.128596E+09 | 0.00 | 0.00 | 0.575227E+11 | 0.00 | 20.82 |
May | 2661628.15 | 0.188960E+10 | 0.00 | 0.124953E+09 | 0.00 | 0.00 | 0.486065E+11 | 0.00 | 21.13 |
June | 6770975.53 | 0.120452E+11 | 0.00 | 74925604.98 | 0.00 | 0.00 | 0.252084E+11 | 0.00 | 20.49 |
July | 1990333.60 | 0.200816E+11 | 0.00 | 41625518.49 | 0.00 | 0.00 | 0.113436E+11 | 0.00 | 20.17 |
August | 14714753.47 | 0.162583E+11 | 0.00 | 59238617.32 | 0.00 | 0.00 | 0.180882E+11 | 0.00 | 20.28 |
September | 4228137.77 | 0.183366E+10 | 0.00 | 0.121097E+09 | 0.00 | 0.00 | 0.433742E+11 | 0.00 | 20.57 |
October | 24579199.89 | 0.00 | 0.00 | 0.147399E+09 | 0.00 | 0.00 | 0.666144E+11 | 0.00 | 20.69 |
November | 0.291487E+09 | 0.00 | 0.00 | 0.119599E+09 | 0.00 | 0.218909E+10 | 0.677097E+11 | 0.00 | 20.34 |
December | 67911771.35 | 0.00 | 0.00 | 0.111871E+09 | 0.00 | 0.00 | 0.765790E+11 | 0.00 | 20.00 |
Annual Sum or Average | 0.819935E+10 | 0.533600E+11 | 0.00 | 0.124648E+10 | 0.00 | 0.309692E+11 | 0.616820E+12 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 41625518.49 | 0.00 | 0.00 | 0.113436E+11 | 0.00 | 19.33 |
Maximum of Months | 0.415507E+10 | 0.200816E+11 | 0.00 | 0.147399E+09 | 0.00 | 0.161800E+11 | 0.766466E+11 | 0.00 | 21.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175051E+11 | 0.00 | 0.00 | 0.91 |
February | 0.309300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121289E+11 | 0.00 | 0.00 | 0.90 |
March | 0.721570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469129E+10 | 0.00 | 0.00 | 0.90 |
April | 0.852693E+10 | 0.00 | 0.00 | 0.00 | 0.214534E+09 | 0.152951E+10 | 0.00 | 0.00 | 0.90 |
May | 0.883423E+10 | 0.00 | 0.00 | 0.00 | 0.323395E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
June | 0.474176E+10 | 0.225390E+09 | 0.00 | 0.00 | 0.192902E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.241350E+10 | 0.212670E+09 | 0.00 | 0.00 | 0.345228E+10 | 0.00 | 0.00 | 0.00 | 0.95 |
August | 0.372158E+10 | 81440751.26 | 0.00 | 0.00 | 0.284853E+10 | 0.00 | 0.00 | 0.00 | 0.95 |
September | 0.782303E+10 | 28315275.87 | 0.00 | 0.00 | 0.289472E+09 | 0.107064E+09 | 0.00 | 0.00 | 0.93 |
October | 0.110892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517067E+09 | 0.00 | 0.00 | 0.89 |
November | 0.659770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605208E+10 | 0.00 | 0.00 | 0.90 |
December | 0.195246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119195E+11 | 0.00 | 0.00 | 0.90 |
Annual Sum or Average | 0.670232E+11 | 0.547816E+09 | 0.00 | 0.00 | 0.905723E+10 | 0.544505E+11 | 0.00 | 0.00 | 0.92 |
Minimum of Months | 0.101405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.110892E+11 | 0.225390E+09 | 0.00 | 0.00 | 0.345228E+10 | 0.175051E+11 | 0.00 | 0.00 | 0.95 |