Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:50:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10639.60 | 937.80 | 937.80 |
Net Site Energy | 10639.60 | 937.80 | 937.80 |
Total Source Energy | 24063.37 | 2121.00 | 2121.00 |
Net Source Energy | 24063.37 | 2121.00 | 2121.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 708.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1236.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 767.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 226.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.02 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 982.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 573.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 85.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 246.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2126.52 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6015.38 | 4624.22 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 708.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1236.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 767.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 226.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 573.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 85.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 246.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.75 | 2126.52 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 87.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.02 | 249.92 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 267.62 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 530.21 | 407.59 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 87.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.02 | 249.92 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 267.62 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 530.21 | 407.59 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6015.380 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6015.380 | 100.00 |
Total On-Site and Utility Electric Sources | 6015.380 | 100.00 |
Total Electricity End Uses | 6015.380 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 802.16 | 20.82 |
Air to Air Heat Recovery for Heating | 3051.32 | 79.18 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3853.47 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.83 |
Time Setpoint Not Met During Occupied Cooling | 467.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7529.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.4281 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 12.2063 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 12.2063 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 10.2688 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 6.3938 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 6.8961 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 6.8961 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-19:00 | 14-JAN-17:30 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 184849.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188434.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50900.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26958.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5206.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3535.10 | 170207.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2395.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 457808.91 | 444669.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 184849.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 188434.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1860.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26958.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5206.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3535.10 | 170207.20 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 768.39 | 0.00 | 0.00 | 0.00 |
Cooling | 3914.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2429.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 717.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.49 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3112.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1816.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 270.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 781.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2305.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19050.71 | 5012.66 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 67.73 | 0.00 | 0.00 | 0.00 |
Cooling | 345.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.18 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1679.17 | 441.83 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 67.73 | 0.00 | 0.00 | 0.00 |
Cooling | 345.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.18 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1679.17 | 441.83 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.42 | 0.623955 | 0.580000 | 1.40 | 1.00 | 0.500000 | 0.000611 | 0.000163 | 1.40 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.310648 | 0.164522 | 0.580000 | 0.180176 | 0.580000 | 0.500000 | 0.002316 | 0.000090 | 0.180176 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.229861 | 0.257476 | 0.580000 | 0.133319 | 0.686603 | 0.500000 | 0.001480 | 0.000036 | 0.133319 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.215528 | 0.580683 | 0.580000 | 0.125006 | 1.00 | 0.500000 | 0.000656 | 0.000049 | 0.125006 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.101417 | 0.711974 | 0.580000 | 0.058822 | 1.00 | 0.500000 | 0.000535 | 0.000030 | 0.058822 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.26 | 0.072344 | 0.580000 | 1.89 | 0.580000 | 0.500000 | 0.020898 | 0.000267 | 1.89 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.32 | 0.109176 | 0.580000 | 0.764542 | 0.580000 | 0.500000 | 0.003490 | 0.000269 | 0.764542 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.55 | 0.219157 | 0.580000 | 2.64 | 0.584419 | 0.500000 | 0.001738 | 0.000691 | 2.64 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.580000 | 0.688405 | 1.00 | 0.500000 | 0.000381 | 0.000278 | 0.688405 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119599 | 0.580000 | 1.23 | 0.580000 | 0.500000 | 0.003186 | 0.000269 | 1.23 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113934 | 0.580000 | 1.29 | 0.580000 | 0.500000 | 0.003344 | 0.000279 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.24 | 0.700000 | 0.580000 | 1.30 | 0.580000 | 0.500000 | 0.010862 | 0.000190 | 1.30 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.596653 | 0.526335 | 0.580000 | 0.346059 | 1.00 | 0.500000 | 0.000724 | 0.000173 | 0.346059 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7397.15 | 0.000163 | 130.90 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4095.97 | 0.000090 | 84.57 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1613.80 | 0.000036 | 30.81 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2218.73 | 0.000049 | 44.18 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1345.87 | 0.000030 | 27.82 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12086.37 | 0.000267 | 216.43 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12173.93 | 0.000269 | 239.59 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 31264.69 | 0.000691 | 595.05 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 5919.99 | 0.000131 | 134.78 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 5938.05 | 0.000131 | 135.19 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 33616.75 | 0.000743 | 765.35 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 33969.95 | 0.000751 | 773.39 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 5885.98 | 0.000130 | 134.01 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 5903.98 | 0.000130 | 134.42 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12578.92 | 0.000278 | 251.38 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1787.44 | 0.000039 | 40.69 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1796.64 | 0.000040 | 40.90 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 8524.09 | 0.000188 | 194.06 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12187.63 | 0.000269 | 226.98 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12624.95 | 0.000279 | 234.77 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8596.21 | 0.000190 | 154.29 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7828.57 | 0.000173 | 161.49 |
VAV WITH REHEAT_HEATC | 202847.70 | 0.004482 | 2846.63 |
FLR_3_DOAS_HEATC | 20392.24 | 0.000451 | 286.17 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.03 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.02 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.11 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.44 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.932285 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.924669 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.271686 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.267020 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.06 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.03 | 0.000131 | 0.000424 |
ROOM_2_FLR_3 FAN COIL | 1.02 | 0.000131 | 0.000417 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.11 | 0.000743 | 0.002060 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.44 | 0.000751 | 0.002339 |
ROOM_5_FLR_3 FAN COIL | 0.932285 | 0.000130 | 0.000384 |
ROOM_6_FLR_3 FAN COIL | 0.924669 | 0.000130 | 0.000381 |
ROOM_1_FLR_6 FAN COIL | 0.271686 | 0.000039 | 0.000111 |
ROOM_2_FLR_6 FAN COIL | 0.267020 | 0.000040 | 0.000109 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.06 | 0.000188 | 0.000447 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.03 |
ROOM_2_FLR_3 FAN COILFAN | 1.02 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.11 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.44 |
ROOM_5_FLR_3 FAN COILFAN | 0.932285 |
ROOM_6_FLR_3 FAN COILFAN | 0.924669 |
ROOM_1_FLR_6 FAN COILFAN | 0.271686 |
ROOM_2_FLR_6 FAN COILFAN | 0.267020 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.06 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000424 | 1.03 | 0.008683 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000417 | 1.02 | 0.008686 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002060 | 5.11 | 0.008621 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002339 | 5.44 | 0.008868 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000384 | 0.932285 | 0.008704 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000381 | 0.924669 | 0.008706 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000111 | 0.271686 | 0.008674 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000109 | 0.267020 | 0.008678 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000447 | 1.06 | 0.008779 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.024437 | 0.012293 | 28.78 | 6.70 | 10.99 | 0.008281 | 684170.52 | 20.40 | |
FLR_3_DOAS_COOLC | 0.003072 | 0.014097 | 32.03 | 6.70 | 10.99 | 0.008281 | 86019.67 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.04 | 12.04 | 20.76 | 12.04 | 20.40 | 20.40 | 0.300000 | 0.590169 | 20.40 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.40 | 12.05 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 12.05 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 20.40 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024437 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004482 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003072 | 0.000155 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000451 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.034183 | 8187.13 |
HEATSYS1 PUMP | 0.010000 | 2554.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.010000 | 1.20 |
COOLSYS1 | 0.034183 | 4.10 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.034183 | 2729.04 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 452595.59 | 452595.59 | 0.010000 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.034183 | 957033.56 | 957616.22 | 109.17 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.428 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.808 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 12.206 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.966 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 12.206 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.966 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.269 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.339 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 16677.861 | 8.428 | 156.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16677.861 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 818.691 | 12.206 | 75.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 818.691 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 948.048 | 12.206 | 75.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 948.048 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1511.554 | 9.203 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.554 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 578.329 | 6.103 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1957.675 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.675 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 13433.463 | 10.269 | 31.800 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13433.463 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.461 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2489.761 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.761 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.652 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.652 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.461 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.844 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.844 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 3437.844 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.844 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.924 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.924 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2635.028 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.028 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
25 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
26 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
27 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
28 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
29 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
30 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
31 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
32 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
33 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 31 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
2 | RESWINDOW_U_0.39_SHGC_0.4 | 32 | 1 | VerySmooth | 2.216 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.35607E-002 | 0.31435 | 0.47829 | 0.47829 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.12023 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33244.85694 | 33244.85694 | 2.41663 | 2.41663 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 28.94267 | 1.40969E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4272.63084 | 4272.63084 | 0.31065 | 0.31065 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3146.93817 | 3146.93817 | 0.13494 | 0.13494 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3161.70962 | 3161.70962 | 0.22986 | 0.22986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.40969E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 911.11779 | 911.11779 | 3.90708E-002 | 9.16993E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2965.25902 | 2965.25902 | 0.21553 | 0.21553 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.40969E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1560.06834 | 1560.06834 | 6.68992E-002 | 6.68992E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1395.30747 | 1395.30747 | 0.10142 | 0.10142 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 32.02600 | 1.40969E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1035.95556 | 1035.95556 | 4.44239E-002 | 5.77430E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44869.91047 | 44869.91047 | 3.26181 | 3.26181 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2119.57026 | 2119.57026 | 9.08881E-002 | 0.23597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18115.59915 | 18115.59915 | 1.31818 | 1.31818 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8146.62516 | 8146.62516 | 0.34932 | 0.67613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62546.61238 | 62546.61238 | 4.54851 | 4.54851 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17364.15232 | 17364.15232 | 0.74461 | 1.89326 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10562.77489 | 10562.77489 | 1.03472 | 1.03472 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5919.98913 | 5919.98913 | 0.25535 | 0.25535 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10389.69513 | 10389.69513 | 1.01776 | 1.01776 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5938.04289 | 5938.04289 | 0.25613 | 0.25613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 52190.35948 | 52190.35948 | 5.11209 | 5.11209 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33617.22690 | 33617.22690 | 1.45004 | 1.45004 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 55538.58536 | 55538.58536 | 5.44047 | 5.44047 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.40969E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33970.43028 | 33970.43028 | 1.46527 | 1.46527 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9517.09888 | 9517.09888 | 0.93229 | 0.93229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5885.97493 | 5885.97493 | 0.25388 | 0.25388 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9439.34058 | 9439.34058 | 0.92467 | 0.92467 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5903.97195 | 5903.97195 | 0.25466 | 0.25466 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 13056.26320 | 13056.26320 | 0.94897 | 1.18691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 31.80400 | 1.40969E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8949.15464 | 8949.15464 | 0.38377 | 0.47458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2773.47180 | 2773.47180 | 0.27169 | 0.27169 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1787.43335 | 1787.43335 | 7.70973E-002 | 7.70973E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2725.84070 | 2725.84070 | 0.26702 | 0.26702 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1796.63966 | 1796.63966 | 7.74944E-002 | 7.74944E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10868.40362 | 10868.40362 | 1.06467 | 1.06467 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8524.08520 | 8524.08520 | 0.36767 | 0.36767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29033.38273 | 29033.38273 | 2.11308 | 2.11308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5724.58646 | 5724.58646 | 0.24548 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30477.70386 | 30477.70386 | 2.21816 | 2.21816 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5840.51424 | 5840.51424 | 0.25045 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30792.88301 | 30792.88301 | 2.24426 | 2.24426 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.40969E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1758.54142 | 1758.54142 | 7.53974E-002 | 0.36721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8208.91354 | 8208.91354 | 0.59665 | 0.59665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.40969E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6003.43486 | 6003.43486 | 0.25744 | 0.25744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 394307.05 | 20.40389 | 20.40389 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 248032.15 | 7.48466 | 7.48466 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 47696.01 | 15.28371 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 67974.13 | 4.45755 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41663 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62396 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.40165 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.10621E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63431E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.40165 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7397.14919 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63431E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 130.89608 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31065 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16452 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18018 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31580E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.04955E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18018 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4095.97438 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.04955E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.56702 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22986 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25748 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13332 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68660 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47975E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.56549E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13332 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1613.80006 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.56549E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.80565 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21553 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58068 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12501 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.56124E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.90202E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12501 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2218.73128 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.90202E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.18261 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10142 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71197 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.88221E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.35132E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.97353E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.88221E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1345.86909 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.97353E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 27.81918 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.26181 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.23443E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89185 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08985E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67034E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89185 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12086.37019 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67034E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.42831 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31818 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10918 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76454 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48979E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.68968E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76454 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12173.92767 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68968E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.58721 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.54851 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21916 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.63814 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58442 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73848E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.90755E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.63814 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31264.68842 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.90755E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 595.05005 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03472 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03472 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.03472 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30795E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.23997E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.23997E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.03472 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68339E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68266 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5919.99455 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30795E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.78144 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01776 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01776 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.01776 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.31194E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.17354E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.17354E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.01776 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68613E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68265 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5938.04833 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31194E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 135.19239 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.11209 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.11209 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.11209 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.42721E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.06032E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.06032E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.11209 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.62139E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68338 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 33616.74678 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.42721E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 765.35358 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.44047 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.44047 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.44047 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.50524E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.33890E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.33890E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.44047 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.86779E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68248 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 33969.94545 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.50524E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 773.39340 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93229 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93229 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.93229 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30044E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.84140E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.84140E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.93229 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70418E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68261 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5885.98032 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30044E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.00718 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92467 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92467 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.92467 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30441E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.81163E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.81163E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.92467 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70578E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68261 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5903.97735 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30441E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.41684 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68841 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.77916E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68841 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12578.91580 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77916E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.37892 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27169 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27169 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27169 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.94912E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.11064E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.11064E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.27169 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67447E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68267 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1787.43508 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.94912E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.69341 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26702 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26702 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.26702 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.96946E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.09249E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.09249E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.26702 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67763E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68266 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1796.64139 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.96946E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.90297 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06467 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06467 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06467 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.88329E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.47419E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.47419E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.06467 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.77933E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68243 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 8524.09286 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88329E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.06199 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11308 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11960 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22558 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18563E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69271E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22558 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12187.62550 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69271E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 226.97520 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21816 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11393 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28653 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34406E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78933E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28653 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12624.95268 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78933E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 234.77122 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24426 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30167 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08623E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89923E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30167 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8596.21347 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89923E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 154.28853 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59665 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52633 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34606 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.23874E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72963E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34606 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7828.56909 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72963E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 161.49220 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.04175 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.04175 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.76164 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.04175 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.40389 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.40389 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.59017 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.40389 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.40389 |
346 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 12.05026 |
347 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 12.05026 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 684170.52074 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.44370E-002 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 20.40389 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.22929E-002 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.77923 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.98854 |
355 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 202847.70227 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.48167E-003 |
358 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 2846.63162 |
359 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 20.40389 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.44370E-002 |
361 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.94865E-005 |
362 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48167E-003 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
365 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 86019.67144 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.07242E-003 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.40969E-002 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 32.02600 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.99443 |
373 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20392.24032 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.50542E-004 |
376 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 286.17133 |
377 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.07242E-003 |
379 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54989E-004 |
380 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50542E-004 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.41830E-002 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8187.12636 |
383 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
384 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
386 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
387 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 9.99955E-003 |
389 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.19995 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 9.99955E-003 |
391 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2554.75592 |
392 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 452595.59153 |
393 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 452595.59000 |
394 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 9.99955E-003 |
395 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.41830E-002 |
396 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.10196 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.41830E-002 |
398 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2729.04212 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.41830E-002 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 957033.56476 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 957616.22000 |
402 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 109.16825 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7439.59 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4120.75 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1622.24 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2232.64 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1354.00 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12154.84 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12252.29 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31428.70 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6388.08 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6407.56 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 36274.81 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 36655.88 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6351.38 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6370.80 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12657.42 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 1928.72 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 1938.65 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9197.84 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12254.14 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12693.94 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8644.80 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7875.95 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 143911.01 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 14467.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 17424.61 | 14021.17 | 3403.44 | 0.80 | 1952.07 | 19.80 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 17147.20 | 13795.48 | 3351.71 | 0.80 | 1920.89 | 19.48 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 85163.49 | 68809.60 | 16353.89 | 0.81 | 9552.87 | 96.89 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 94483.63 | 75152.82 | 19330.80 | 0.80 | 10551.05 | 107.01 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 15755.91 | 12661.29 | 3094.61 | 0.80 | 1764.42 | 17.90 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 15631.47 | 12560.00 | 3071.48 | 0.80 | 1750.43 | 17.75 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4568.13 | 3678.01 | 890.12 | 0.81 | 511.86 | 5.19 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4492.13 | 3616.08 | 876.06 | 0.80 | 503.31 | 5.10 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 18223.21 | 14574.08 | 3649.13 | 0.80 | 2037.93 | 20.67 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 654019.97 | 425026.82 | 228993.15 | 0.65 | 95885.24 | 972.52 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67719.12 | 43589.11 | 24130.01 | 0.64 | 9176.10 | 93.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.4 | N/A | 2.216 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7237736793E-002 | 2.2310341847E-002 | Pass | Pass | 2.4244586987E-003 | 3.9821497045E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4055338588E-003 | 1.9350556510E-002 | Pass | Pass | 0.3873987351 | 1.6306821205 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.2100878487E-003 | 1.7096232023E-002 | Pass | Pass | 2.4306921058E-002 | 4.9539406731E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1156284575E-004 | 3.7979771983E-004 | Pass | Pass | 0.6217819505 | 4.1438487083 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7650516728E-004 | 3.9613318756E-004 | Pass | Pass | 2.3901405190E-002 | 3.1106926781E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.5672746641E-002 | 0.2236061962 | Pass | Pass | 1.8436871869E-002 | 5.0230190848E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0425289800E-002 | 7.1080608034E-002 | Pass | Pass | 7.2940893847E-002 | 0.1383410177 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7764246361E-002 | 3.9569087390E-002 | Pass | Pass | 1.7200742965E-002 | 3.9920592403E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4714939713E-002 | 0.2912420507 | Pass | Pass | 0.4042733799 | 1.8906539430 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2645630544E-002 | 0.3057787614 | Pass | Pass | 0.2714726784 | 1.3295745496 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.9630703010E-002 | 5.0668985697E-002 | Pass | Pass | 0.4173966338 | 3.9473574689 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9312055921E-002 | 0.1626266699 | Pass | Pass | 8.7633864801E-002 | 0.2868921597 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.6008423973E-002 | 0.2443383504 | Pass | Pass | 0.2418186291 | 0.8161972868 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.2003387431E-002 | 0.2709839890 | Pass | Pass | 0.4374140346 | 3.1534344566 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8002725844E-004 | 4.4579127132E-004 | Pass | Pass | 0.1704957750 | 0.5286004261 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2622731790E-002 | 0.3148134119 | Pass | Pass | 0.6346590869 | 3.2852899709 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2646840448E-002 | 0.3225628871 | Pass | Pass | 0.1249664955 | 0.4228690484 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.3949854524E-002 | 0.1998404858 | Pass | Pass | 0.1335464899 | 0.5673919808 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0080187748E-002 | 9.3965944576E-002 | Pass | Pass | 7.2377128831E-003 | 1.8130385954E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4855693160E-002 | 8.2601140470E-002 | Pass | Pass | 7.3764955326E-003 | 1.9248410278E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7730092745E-002 | 0.1264226326 | Pass | Pass | 2.0961371056E-002 | 3.6720358127E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.9351135118E-004 | 5.3677826843E-004 | Pass | Pass | 0.1353142596 | 0.4363531154 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.159 | 0.394 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.159 | 0.394 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.159 | 0.394 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.216 | 0.394 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.216 | 0.394 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.216 | 0.394 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.394 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.394 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.199 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 432.93 | 2.201 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 781.15 | 2.198 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.4281 | 1978.83 | 16677.86 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 54.51 | 168.00 | 54.45 | 0.0000 | Y | 170.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 12.2063 | 67.07 | 818.69 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 9.01 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 12.2063 | 77.67 | 948.05 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 10.43 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 9.2031 | 164.24 | 1511.55 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.64 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 6.1031 | 94.76 | 578.33 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 3.31 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 5.8125 | 78.04 | 453.61 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.99 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 10.3656 | 188.86 | 1957.68 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.78 | 0.0000 | Y | 17.93 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 10.2688 | 1308.19 | 13433.46 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 56.92 | 0.0000 | Y | 143.53 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 4.5531 | 156.09 | 710.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 4.5531 | 156.07 | 710.61 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 4.5531 | 1863.81 | 8486.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 67.92 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 4.5531 | 1864.32 | 8488.51 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 67.94 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 4.5531 | 156.09 | 710.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 4.5531 | 156.07 | 710.61 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.69 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 6.3938 | 1557.62 | 9959.04 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 4.5531 | 39.02 | 177.67 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.42 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 4.5531 | 39.02 | 177.65 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.42 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 4.5531 | 220.77 | 1005.22 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 8.05 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 10.3656 | 331.66 | 3437.84 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.67 | 0.0000 | Y | 34.64 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 10.3656 | 331.66 | 3437.84 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.67 | 0.0000 | Y | 34.64 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.7219 | 103.30 | 1210.92 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 6.3938 | 412.12 | 2635.03 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8961 | 11345.29 | 78237.74 | 526.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.68 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.68 | 0.00 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 13433.46 | 940.34 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 13433.46 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 14423.55 | AstronomicalClock | - | 83.64 | 83.64 | 226.46 | |
Exterior Lighting Total | 14423.55 | 226.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 452595.59 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 957616.22 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11871.02 | 17424.61 | 14021.17 | 3403.44 | 0.80 | - | 1952.07 | 19.80 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11685.02 | 17147.20 | 13795.48 | 3351.71 | 0.80 | - | 1920.89 | 19.48 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 57684.62 | 85163.49 | 68809.60 | 16353.89 | 0.81 | - | 9552.87 | 96.89 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 65484.28 | 94483.63 | 75152.82 | 19330.80 | 0.80 | - | 10551.05 | 107.01 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10755.08 | 15755.91 | 12661.29 | 3094.61 | 0.80 | - | 1764.42 | 17.90 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10671.74 | 15631.47 | 12560.00 | 3071.48 | 0.80 | - | 1750.43 | 17.75 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3109.57 | 4568.13 | 3678.01 | 890.12 | 0.81 | - | 511.86 | 5.19 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3058.74 | 4492.13 | 3616.08 | 876.06 | 0.80 | - | 503.31 | 5.10 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12526.78 | 18223.21 | 14574.08 | 3649.13 | 0.80 | - | 2037.93 | 20.67 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 684170.52 | 654019.97 | 425026.82 | 228993.15 | 0.65 | - | 95885.24 | 972.52 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 86019.67 | 67719.12 | 43589.11 | 24130.01 | 0.64 | - | 9176.10 | 93.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7397.15 | 7439.59 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4095.97 | 4120.75 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1613.80 | 1622.24 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2218.73 | 2232.64 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1345.87 | 1354.00 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12086.37 | 12154.84 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12173.93 | 12252.29 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31264.69 | 31428.70 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5919.99 | 6388.08 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5938.05 | 6407.56 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 33616.75 | 36274.81 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 33969.95 | 36655.88 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5885.98 | 6351.38 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5903.98 | 6370.80 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12578.92 | 12657.42 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1787.44 | 1928.72 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1796.64 | 1938.65 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 8524.09 | 9197.84 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12187.63 | 12254.14 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12624.95 | 12693.94 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8596.21 | 8644.80 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7828.57 | 7875.95 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 202847.70 | 143911.01 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20392.24 | 14467.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 728.06 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 716.13 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.11 | 3597.05 | 703.64 | 1.00 | 0.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.44 | 3828.11 | 703.64 | 1.00 | 0.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 655.99 | 703.64 | 1.00 | 1.21 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.92 | 650.63 | 703.64 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 191.17 | 703.64 | 1.00 | 1.79 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 187.88 | 703.64 | 1.00 | 1.80 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 749.14 | 703.64 | 1.00 | 1.18 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.40 | 45717.74 | 2240.64 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.034183 | 8187.13 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.010000 | 2554.76 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.034183 | 2729.04 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33244.86 | 33244.86 | 16.80 | 2.417 | 2.417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00923 | 28.94 | 0.01410 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4272.63 | 4272.63 | 63.70 | 0.311 | 0.311 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00935 | 31.85 | 0.01410 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3161.71 | 3161.71 | 40.71 | 0.230 | 0.230 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00948 | 31.46 | 0.01410 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44869.91 | 44869.91 | 574.96 | 3.262 | 3.262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 32.10 | 0.01410 | 0.236 | 0.00 |
CAFE_FLR_1 | 18115.60 | 18115.60 | 95.92 | 1.318 | 1.318 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01040 | 31.85 | 0.01410 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62546.61 | 62546.61 | 47.81 | 4.549 | 4.549 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01011 | 31.92 | 0.01410 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 10562.77 | 10562.77 | 270.69 | 1.035 | 1.035 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00868 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10389.70 | 10389.70 | 266.28 | 1.018 | 1.018 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00869 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 52190.36 | 52190.36 | 2128.15 | 5.112 | 5.112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00862 | 31.92 | 0.01410 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 55538.59 | 55538.59 | 2264.06 | 5.440 | 5.440 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00887 | 32.10 | 0.01410 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9517.10 | 9517.10 | 243.89 | 0.932 | 0.932 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00870 | 28.24 | 0.01410 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9439.34 | 9439.34 | 241.93 | 0.925 | 0.925 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00871 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2773.47 | 2773.47 | 71.07 | 0.272 | 0.272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00867 | 31.26 | 0.01410 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2725.84 | 2725.84 | 69.86 | 0.267 | 0.267 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00868 | 31.16 | 0.01410 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10868.40 | 10868.40 | 443.06 | 1.065 | 1.065 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00878 | 31.92 | 0.01410 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29033.38 | 29033.38 | 87.54 | 2.113 | 2.113 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01047 | 32.10 | 0.01410 | 1.187 | 0.00 |
DINING_FLR_6 | 30477.70 | 30477.70 | 91.90 | 2.218 | 2.218 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01037 | 32.10 | 0.01410 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30792.88 | 30792.88 | 298.08 | 2.244 | 2.244 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01010 | 31.43 | 0.01410 | 0.367 | 0.00 |
MECH_FLR_1 | 2965.26 | 2965.26 | 18.05 | 0.216 | 0.216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00871 | 31.46 | 0.01410 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1395.31 | 1395.31 | 14.72 | 0.101 | 0.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 32.03 | 0.01410 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 13056.26 | 13056.26 | 33.53 | 0.949 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00865 | 31.80 | 0.01410 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8208.91 | 8208.91 | 19.92 | 0.597 | 0.597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00861 | 32.10 | 0.01410 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3146.94 | 3146.94 | 46.92 | 0.135 | 0.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00711 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 911.12 | 911.12 | 11.73 | 0.039 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00733 | -10.70 | 0.00150 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2119.57 | 2119.57 | 27.16 | 0.091 | 0.236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 0.236 | 0.00 |
CAFE_FLR_1 | 8146.63 | 8146.63 | 43.14 | 0.349 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00713 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17364.15 | 17364.15 | 13.27 | 0.745 | 1.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 5919.99 | 5919.99 | 151.71 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5938.04 | 5938.04 | 152.19 | 0.256 | 0.256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00742 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33617.23 | 33617.23 | 1370.80 | 1.450 | 1.450 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33970.43 | 33970.43 | 1384.82 | 1.465 | 1.465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5885.97 | 5885.97 | 150.84 | 0.254 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5903.97 | 5903.97 | 151.32 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1787.43 | 1787.43 | 45.81 | 0.077 | 0.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1796.64 | 1796.64 | 46.05 | 0.077 | 0.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8524.09 | 8524.09 | 347.49 | 0.368 | 0.368 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00752 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5724.59 | 5724.59 | 17.26 | 0.245 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.187 | 0.00 |
DINING_FLR_6 | 5840.51 | 5840.51 | 17.61 | 0.250 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00762 | -10.70 | 0.00150 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 1758.54 | 1758.54 | 17.02 | 0.075 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00595 | -10.70 | 0.00150 | 0.367 | 0.00 |
MECH_FLR_1 | 1560.07 | 1560.07 | 9.50 | 0.067 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1035.96 | 1035.96 | 10.93 | 0.044 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00712 | -10.70 | 0.00150 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 8949.15 | 8949.15 | 22.98 | 0.384 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 6003.43 | 6003.43 | 14.57 | 0.257 | 0.257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.40 | 20.40 | 7.48 | 7.48 | 20.4039 | 12.0417 | 20.4039 | 0.5902 | 0.3000 |
FLR_3_DOAS | 15.28 | 2.05 | 4.46 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7397.149 | 7397.149 | 1.401646 | 0.00016343 | 130.896 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7439.59 | 7397.15 | 1.401646 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7441.02 | 7441.02 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4095.974 | 4095.974 | 0.180176 | 0.00009050 | 84.567 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4120.75 | 4095.97 | 0.180176 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00710583 | 45.9840 | 3146.94 | 0.00 | 4122.91 | 4122.91 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1613.800 | 1613.800 | 0.133319 | 0.00003565 | 30.806 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1622.24 | 1613.80 | 0.133319 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732622 | 47.3906 | 911.12 | 0.00 | 1622.98 | 1622.98 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2218.731 | 2218.731 | 0.125006 | 0.00004902 | 44.183 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2232.64 | 2218.73 | 0.125006 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715844 | 46.3176 | 1560.07 | 0.00 | 2233.47 | 2233.47 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1345.869 | 1345.869 | 0.058822 | 0.00002974 | 27.819 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1354.00 | 1345.87 | 0.058822 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00712424 | 46.0990 | 1035.96 | 0.00 | 1354.72 | 1354.72 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12086.370 | 12086.370 | 1.891853 | 0.00026703 | 216.428 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12154.84 | 12086.37 | 1.891853 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00713833 | 46.1903 | 2119.57 | 0.00 | 12157.69 | 12157.69 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12173.928 | 12173.928 | 0.764542 | 0.00026897 | 239.587 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12252.29 | 12173.93 | 0.764542 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00712530 | 46.1082 | 8146.63 | 0.00 | 12256.14 | 12256.14 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31264.688 | 31264.688 | 2.638135 | 0.00069076 | 595.050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31428.70 | 31264.69 | 2.638135 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00717428 | 46.4192 | 17364.15 | 0.00 | 31442.71 | 31442.71 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11871.018 | -999.000 | 1.034716 | 0.00042400 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11871.02 | 11357.12 | 1.034716 | 21.68 | 15.70 | 0.00868339 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868339 | 55.6701 | 10562.77 | 0.00 | 11890.56 | 11204.72 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5919.995 | 5919.995 | 0.255347 | 0.00013080 | 134.781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6388.08 | 5919.99 | 0.255347 | 21.11 | 14.33 | 0.00741380 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741380 | 47.6268 | 5919.99 | 0.00 | 6390.80 | 6390.80 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11685.021 | -999.000 | 1.017762 | 0.00041735 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11685.02 | 11171.96 | 1.017762 | 21.68 | 15.70 | 0.00868613 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868613 | 55.6874 | 10389.70 | 0.00 | 11704.24 | 11022.45 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5938.048 | 5938.048 | 0.256125 | 0.00013119 | 135.192 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6407.56 | 5938.05 | 0.256125 | 21.11 | 14.33 | 0.00741546 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741546 | 47.6374 | 5938.04 | 0.00 | 6410.29 | 6410.29 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 57684.624 | -999.000 | 5.112091 | 0.00206032 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 57684.62 | 56007.34 | 5.112091 | 21.68 | 15.64 | 0.00862139 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01409688 | 23.05 | 0.0000 | 21.11 | 0.00862139 | 55.2758 | 52190.36 | 0.00 | 57781.27 | 55208.65 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33616.747 | 33616.747 | 1.450040 | 0.00074272 | 765.354 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36274.81 | 33616.75 | 1.450040 | 21.11 | 14.37 | 0.00744944 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00744944 | 47.8511 | 33617.23 | 0.00 | 36290.60 | 36290.60 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 65484.284 | -999.000 | 5.440473 | 0.00233890 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 65484.28 | 60036.23 | 5.440473 | 21.68 | 15.86 | 0.00886779 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | 0.0000 | 21.11 | 0.00886779 | 56.8356 | 55538.59 | 0.00 | 65586.87 | 59372.58 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33969.945 | 33969.945 | 1.465275 | 0.00075052 | 773.393 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36655.88 | 33969.95 | 1.465275 | 21.11 | 14.37 | 0.00745455 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00745455 | 47.8835 | 33970.43 | 0.00 | 36671.90 | 36671.90 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10755.085 | -999.000 | 0.932285 | 0.00038414 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 10755.08 | 10239.25 | 0.932285 | 21.68 | 15.72 | 0.00870418 | 12.80 | 12.09 | 0.00850000 | 28.24 | 0.01409687 | 22.02 | 0.0000 | 21.11 | 0.00870418 | 55.8016 | 9517.10 | 0.00 | 10772.68 | 10104.69 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5885.980 | 5885.980 | 0.253880 | 0.00013004 | 134.007 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6351.38 | 5885.98 | 0.253880 | 21.11 | 14.33 | 0.00741072 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741072 | 47.6073 | 5885.97 | 0.00 | 6354.08 | 6354.08 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10671.744 | -999.000 | 0.924669 | 0.00038116 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 10671.74 | 10156.09 | 0.924669 | 21.68 | 15.72 | 0.00870578 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00870578 | 55.8117 | 9439.34 | 0.00 | 10689.20 | 10022.83 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5903.977 | 5903.977 | 0.254656 | 0.00013044 | 134.417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6370.80 | 5903.98 | 0.254656 | 21.11 | 14.33 | 0.00741239 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741239 | 47.6179 | 5903.97 | 0.00 | 6373.51 | 6373.51 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12578.916 | 12578.916 | 0.688405 | 0.00027792 | 251.379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12657.42 | 12578.92 | 0.688405 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00751979 | 48.6273 | 8949.15 | 0.00 | 12662.31 | 12662.31 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3109.566 | -999.000 | 0.271686 | 0.00011106 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 3109.57 | 2981.23 | 0.271686 | 21.68 | 15.69 | 0.00867447 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01409687 | 22.87 | 0.0000 | 21.11 | 0.00867447 | 55.6137 | 2773.47 | 0.00 | 3114.70 | 2940.87 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1787.435 | 1787.435 | 0.077097 | 0.00003949 | 40.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1928.72 | 1787.44 | 0.077097 | 21.11 | 14.42 | 0.00750686 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00750686 | 48.2175 | 1787.43 | 0.00 | 1929.59 | 1929.59 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3058.742 | -999.000 | 0.267020 | 0.00010925 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3058.74 | 2930.32 | 0.267020 | 21.68 | 15.69 | 0.00867763 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00867763 | 55.6336 | 2725.84 | 0.00 | 3063.78 | 2890.77 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1796.641 | 1796.641 | 0.077494 | 0.00003969 | 40.903 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1938.65 | 1796.64 | 0.077494 | 21.11 | 14.42 | 0.00750924 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00750924 | 48.2326 | 1796.64 | 0.00 | 1939.52 | 1939.52 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12526.780 | -999.000 | 1.064671 | 0.00044742 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 12526.78 | 11719.10 | 1.064671 | 21.68 | 15.78 | 0.00877933 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01409688 | 23.05 | 0.0000 | 21.11 | 0.00877933 | 56.2770 | 10868.40 | 0.00 | 12546.86 | 11576.56 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8524.093 | 8524.093 | 0.367673 | 0.00018833 | 194.062 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 9197.84 | 8524.09 | 0.367673 | 21.11 | 14.43 | 0.00752262 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00752262 | 48.3170 | 8524.09 | 0.00 | 9202.02 | 9202.02 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12187.625 | 12187.625 | 1.225585 | 0.00026927 | 226.975 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12254.14 | 12187.63 | 1.225585 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761498 | 49.2359 | 5724.59 | 0.00 | 12258.68 | 12258.68 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12624.953 | 12624.953 | 1.286534 | 0.00027893 | 234.771 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12693.94 | 12624.95 | 1.286534 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762218 | 49.2821 | 5840.51 | 0.00 | 12698.58 | 12698.58 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8596.213 | 8596.213 | 1.301668 | 0.00018992 | 154.289 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8644.80 | 8596.21 | 1.301668 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00594954 | 38.5783 | 1758.54 | 0.00 | 8646.89 | 8646.89 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7828.569 | 7828.569 | 0.346059 | 0.00017296 | 161.492 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7875.95 | 7828.57 | 0.346059 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767512 | 49.6199 | 6003.43 | 0.00 | 7880.05 | 7880.05 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 684170.521 | -999.000 | 20.403889 | 0.02443699 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 684170.52 | 435360.58 | 20.403889 | 28.78 | 20.91 | 0.01229288 | 10.99 | 10.99 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 59.0586 | 23.99 | 0.00952917 | 51.2123 | 280484.68 | 0.00 | 744024.35 | 464677.70 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 202847.702 | 202847.702 | 6.121167 | 0.00448167 | 2846.632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 143911.01 | 202847.70 | 6.121167 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 196.8621 | 21.00 | 0.00740491 | 47.8943 | 61932.87 | 0.00 | 143741.40 | 143741.40 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86019.671 | -999.000 | 2.051199 | 0.00307242 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86019.67 | 50571.42 | 2.051199 | 32.03 | 23.08 | 0.01409687 | 10.99 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 100.0000 | 21.11 | 0.00874771 | 56.0756 | 155743.82 | 0.00 | 92041.54 | 54055.96 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14467.35 | 20392.24 | 0.615360 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3333 | 21.11 | 0.00745237 | 47.8698 | 103343.54 | 0.00 | 14450.29 | 14450.29 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7397.149 | 7397.149 | 1.401646 | 0.00016343 | 130.896 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.6113 | 1.634384 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7439.59 | 7397.15 | 1.0000 | 1.68701352 | 1.401646 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.16341430 | 60.00 | 49.00 | 11.00 | 0.000 | 7439.59 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7441.02 | 7441.02 | 1.68701352 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4095.974 | 4095.974 | 0.180176 | 0.00009050 | 84.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.8925 | 0.904997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4120.75 | 4095.97 | 1.0000 | 0.21685885 | 0.180176 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.09048632 | 60.00 | 49.00 | 11.00 | 0.000 | 4120.75 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00710583 | 21.00 | 0.00710583 | 45.9840 | 3146.94 | 0.00 | 4122.91 | 4122.91 | 0.21685885 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.24 | 19.71 | 0.00800000 | 55946.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1613.800 | 1613.800 | 0.133319 | 0.00003565 | 30.806 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.3514 | 0.356566 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1622.24 | 1613.80 | 1.0000 | 0.16046243 | 0.133319 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03565130 | 60.00 | 49.00 | 11.00 | 0.000 | 1622.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00732622 | 21.00 | 0.00732622 | 47.3906 | 911.12 | 0.00 | 1622.98 | 1622.98 | 0.16046243 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.52 | 16.83 | 0.00800000 | 47049.1 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2218.731 | 2218.731 | 0.125006 | 0.00004902 | 44.183 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.4836 | 0.490224 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2232.64 | 2218.73 | 1.0000 | 0.15045669 | 0.125006 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.04901516 | 60.00 | 49.00 | 11.00 | 0.000 | 2232.64 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00715844 | 21.00 | 0.00715844 | 46.3176 | 1560.07 | 0.00 | 2233.47 | 2233.47 | 0.15045669 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.16 | 18.40 | 0.00800000 | 51779.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1345.869 | 1345.869 | 0.058822 | 0.00002974 | 27.819 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.2933 | 0.297367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1354.00 | 1345.87 | 1.0000 | 0.07079800 | 0.058822 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.02973230 | 60.00 | 49.00 | 11.00 | 0.000 | 1354.00 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00712424 | 21.00 | 0.00712424 | 46.0990 | 1035.96 | 0.00 | 1354.72 | 1354.72 | 0.07079800 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.37 | 19.74 | 0.00800000 | 56069.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12086.370 | 12086.370 | 1.891853 | 0.00026703 | 216.428 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 2.6326 | 2.670457 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12154.84 | 12086.37 | 1.0000 | 2.27702435 | 1.891853 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26700634 | 60.00 | 49.00 | 11.00 | 0.000 | 12154.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00713833 | 21.00 | 0.00713833 | 46.1903 | 2119.57 | 0.00 | 12157.69 | 12157.69 | 2.27702435 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.84 | 15.15 | 0.00800000 | 42274.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12173.928 | 12173.928 | 0.764542 | 0.00026897 | 239.587 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 2.6537 | 2.689803 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12252.29 | 12173.93 | 1.0000 | 0.92019904 | 0.764542 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26894062 | 60.00 | 49.00 | 11.00 | 0.000 | 12252.29 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00712530 | 21.00 | 0.00712530 | 46.1082 | 8146.63 | 0.00 | 12256.14 | 12256.14 | 0.92019904 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.66 | 17.90 | 0.00800000 | 50253.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31264.688 | 31264.688 | 2.638135 | 0.00069076 | 595.050 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 6.8071 | 6.907864 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31428.70 | 31264.69 | 1.0000 | 3.17524646 | 2.638135 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.69068462 | 60.00 | 49.00 | 11.00 | 0.000 | 31428.70 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00717428 | 21.00 | 0.00717428 | 46.4192 | 17364.15 | 0.00 | 31442.71 | 31442.71 | 3.17524646 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.31 | 16.76 | 0.00800000 | 46837.2 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11871.018 | -999.000 | 1.034716 | 0.00042400 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9820 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.034716 | 1.24537910 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 1.2404 | 1.240374 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 11871.02 | 11357.12 | 1.0000 | 1.24537910 | 1.034716 | 21.68 | 15.70 | 0.00868339 | 43854.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.42395409 | 6.70 | 11.72 | 6.67 | 0.000 | 11871.02 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868339 | 21.11 | 0.00868339 | 55.6701 | 10562.77 | 0.00 | 11890.56 | 11204.72 | 1.24537910 | 21.68 | 15.70 | 0.00868339 | 43854.2 | 12.87 | 12.09 | 0.00846528 | 34306.5 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5919.995 | 5919.995 | 0.255347 | 0.00013080 | 134.781 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.034716 | 1.24537910 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.3836 | 1.308010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6388.08 | 5919.99 | 1.0000 | 0.30733394 | 0.255347 | 21.11 | 14.33 | 0.00741380 | 40044.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13078170 | 60.00 | 49.00 | 11.00 | 0.000 | 6388.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741380 | 21.11 | 0.00741380 | 47.6268 | 5919.99 | 0.00 | 6390.80 | 6390.80 | 0.30733394 | 16.60 | 12.57 | 0.00741380 | 35450.6 | 37.01 | 19.81 | 0.00741380 | 56244.9 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11685.021 | -999.000 | 1.017762 | 0.00041735 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9871 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.017762 | 1.22497339 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 1.2210 | 1.220940 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 11685.02 | 11171.96 | 1.0000 | 1.22497339 | 1.017762 | 21.68 | 15.70 | 0.00868613 | 43861.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.41731149 | 6.70 | 11.72 | 6.67 | 0.000 | 11685.02 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868613 | 21.11 | 0.00868613 | 55.6874 | 10389.70 | 0.00 | 11704.24 | 11022.45 | 1.22497339 | 21.68 | 15.71 | 0.00868613 | 43861.2 | 12.87 | 12.09 | 0.00846570 | 34306.5 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5938.048 | 5938.048 | 0.256125 | 0.00013119 | 135.192 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.017762 | 1.22497339 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.3878 | 1.311999 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6407.56 | 5938.05 | 1.0000 | 0.30827119 | 0.256125 | 21.11 | 14.33 | 0.00741546 | 40048.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13118054 | 60.00 | 49.00 | 11.00 | 0.000 | 6407.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741546 | 21.11 | 0.00741546 | 47.6374 | 5938.04 | 0.00 | 6410.29 | 6410.29 | 0.30827119 | 16.60 | 12.57 | 0.00741546 | 35454.8 | 37.01 | 19.81 | 0.00741546 | 56249.1 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 57684.624 | -999.000 | 5.112091 | 0.00206032 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8667 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.112091 | 6.15288690 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 6.0274 | 6.027327 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 57684.62 | 56007.34 | 1.0000 | 6.15288690 | 5.112091 | 21.68 | 15.64 | 0.00862139 | 43697.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.06011245 | 6.70 | 11.72 | 6.67 | 0.000 | 57684.62 | 31.92 | 0.01409688 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00862139 | 21.11 | 0.00862139 | 55.2758 | 52190.36 | 0.00 | 57781.27 | 55208.65 | 6.15288690 | 21.68 | 15.65 | 0.00862139 | 43697.4 | 12.89 | 12.09 | 0.00845579 | 34306.5 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33616.747 | 33616.747 | 1.450040 | 0.00074272 | 765.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.112091 | 6.15288690 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 7.8567 | 7.427546 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36274.81 | 33616.75 | 1.0000 | 1.74526063 | 1.450040 | 21.11 | 14.37 | 0.00744944 | 40135.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.74264518 | 60.00 | 49.00 | 11.00 | 0.000 | 36274.81 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00744944 | 21.11 | 0.00744944 | 47.8511 | 33617.23 | 0.00 | 36290.60 | 36290.60 | 1.74526063 | 16.60 | 12.60 | 0.00744944 | 35540.8 | 37.01 | 19.84 | 0.00744944 | 56334.6 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65484.284 | -999.000 | 5.440473 | 0.00233890 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3248 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.440473 | 6.54812618 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 6.8424 | 6.842295 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 65484.28 | 60036.23 | 1.0000 | 6.54812618 | 5.440473 | 21.68 | 15.86 | 0.00886779 | 44322.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.33866461 | 6.70 | 11.72 | 6.67 | 0.000 | 65484.28 | 32.10 | 0.01409687 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00886779 | 21.11 | 0.00886779 | 56.8356 | 55538.59 | 0.00 | 65586.87 | 59372.58 | 6.54812618 | 21.68 | 15.87 | 0.00886779 | 44322.7 | 12.80 | 12.09 | 0.00849190 | 34306.5 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33969.945 | 33969.945 | 1.465275 | 0.00075052 | 773.393 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.440473 | 6.54812618 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 7.9393 | 7.505585 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36655.88 | 33969.95 | 1.0000 | 1.76359743 | 1.465275 | 21.11 | 14.37 | 0.00745455 | 40148.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.75044787 | 60.00 | 49.00 | 11.00 | 0.000 | 36655.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00745455 | 21.11 | 0.00745455 | 47.8835 | 33970.43 | 0.00 | 36671.90 | 36671.90 | 1.76359743 | 16.60 | 12.61 | 0.00745455 | 35553.8 | 37.01 | 19.84 | 0.00745455 | 56347.6 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10755.085 | -999.000 | 0.932285 | 0.00038414 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0206 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.932285 | 1.12209410 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 1.1238 | 1.123773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | 10755.08 | 10239.25 | 1.0000 | 1.12209410 | 0.932285 | 21.68 | 15.72 | 0.00870418 | 43907.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38410035 | 6.70 | 11.72 | 6.67 | 0.000 | 10755.08 | 28.24 | 0.01409687 | 22.02 | 0.00000000 | 0.0000 | 21.11 | 0.00870418 | 21.11 | 0.00870418 | 55.8016 | 9517.10 | 0.00 | 10772.68 | 10104.69 | 1.12209410 | 21.68 | 15.72 | 0.00870418 | 43907.0 | 12.86 | 12.09 | 0.00846840 | 34306.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5885.980 | 5885.980 | 0.253880 | 0.00013004 | 134.007 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.932285 | 1.12209410 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.3756 | 1.300494 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6351.38 | 5885.98 | 1.0000 | 0.30556811 | 0.253880 | 21.11 | 14.33 | 0.00741072 | 40036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13003028 | 60.00 | 49.00 | 11.00 | 0.000 | 6351.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741072 | 21.11 | 0.00741072 | 47.6073 | 5885.97 | 0.00 | 6354.08 | 6354.08 | 0.30556811 | 16.60 | 12.56 | 0.00741072 | 35442.8 | 37.01 | 19.81 | 0.00741072 | 56237.1 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10671.744 | -999.000 | 0.924669 | 0.00038116 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0236 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.924669 | 1.11292668 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 1.1151 | 1.115065 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 10671.74 | 10156.09 | 1.0000 | 1.11292668 | 0.924669 | 21.68 | 15.72 | 0.00870578 | 43911.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38112396 | 6.70 | 11.72 | 6.67 | 0.000 | 10671.74 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00870578 | 21.11 | 0.00870578 | 55.8117 | 9439.34 | 0.00 | 10689.20 | 10022.83 | 1.11292668 | 21.68 | 15.72 | 0.00870578 | 43911.1 | 12.86 | 12.09 | 0.00846864 | 34306.5 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5903.977 | 5903.977 | 0.254656 | 0.00013044 | 134.417 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.924669 | 1.11292668 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.3798 | 1.304471 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6370.80 | 5903.98 | 1.0000 | 0.30650241 | 0.254656 | 21.11 | 14.33 | 0.00741239 | 40040.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13042786 | 60.00 | 49.00 | 11.00 | 0.000 | 6370.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741239 | 21.11 | 0.00741239 | 47.6179 | 5903.97 | 0.00 | 6373.51 | 6373.51 | 0.30650241 | 16.60 | 12.57 | 0.00741239 | 35447.0 | 37.01 | 19.81 | 0.00741239 | 56241.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12578.916 | 12578.916 | 0.688405 | 0.00027792 | 251.379 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 2.7415 | 2.779284 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12657.42 | 12578.92 | 1.0000 | 0.82856100 | 0.688405 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27788742 | 60.00 | 49.00 | 11.00 | 0.000 | 12657.42 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00751979 | 21.00 | 0.00751979 | 48.6273 | 8949.15 | 0.00 | 12662.31 | 12662.31 | 0.82856100 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.59 | 18.54 | 0.00800000 | 52217.0 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3109.566 | -999.000 | 0.271686 | 0.00011106 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9654 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.271686 | 0.32699955 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 0.3249 | 0.324911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | 3109.57 | 2981.23 | 1.0000 | 0.32699955 | 0.271686 | 21.68 | 15.69 | 0.00867447 | 43831.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11105308 | 6.70 | 11.72 | 6.67 | 0.000 | 3109.57 | 31.26 | 0.01409687 | 22.87 | 0.00000000 | 0.0000 | 21.11 | 0.00867447 | 21.11 | 0.00867447 | 55.6137 | 2773.47 | 0.00 | 3114.70 | 2940.87 | 0.32699955 | 21.68 | 15.70 | 0.00867447 | 43831.6 | 12.87 | 12.09 | 0.00846393 | 34306.5 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1787.435 | 1787.435 | 0.077097 | 0.00003949 | 40.693 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.271686 | 0.32699955 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.4177 | 0.394930 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1928.72 | 1787.44 | 1.0000 | 0.09279395 | 0.077097 | 21.11 | 14.42 | 0.00750686 | 40280.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03948717 | 60.00 | 49.00 | 11.00 | 0.000 | 1928.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750686 | 21.11 | 0.00750686 | 48.2175 | 1787.43 | 0.00 | 1929.59 | 1929.59 | 0.09279395 | 16.60 | 12.66 | 0.00750686 | 35686.2 | 37.01 | 19.88 | 0.00750686 | 56480.5 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3058.742 | -999.000 | 0.267020 | 0.00010925 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9713 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.267020 | 0.32138375 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 0.3196 | 0.319601 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 3058.74 | 2930.32 | 1.0000 | 0.32138375 | 0.267020 | 21.68 | 15.69 | 0.00867763 | 43839.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.10923799 | 6.70 | 11.72 | 6.67 | 0.000 | 3058.74 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00867763 | 21.11 | 0.00867763 | 55.6336 | 2725.84 | 0.00 | 3063.78 | 2890.77 | 0.32138375 | 21.68 | 15.70 | 0.00867763 | 43839.6 | 12.87 | 12.09 | 0.00846441 | 34306.5 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1796.641 | 1796.641 | 0.077494 | 0.00003969 | 40.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.267020 | 0.32138375 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 0.4199 | 0.396964 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1938.65 | 1796.64 | 1.0000 | 0.09327189 | 0.077494 | 21.11 | 14.42 | 0.00750924 | 40286.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03969055 | 60.00 | 49.00 | 11.00 | 0.000 | 1938.65 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750924 | 21.11 | 0.00750924 | 48.2326 | 1796.64 | 0.00 | 1939.52 | 1939.52 | 0.09327189 | 16.60 | 12.66 | 0.00750924 | 35692.2 | 37.01 | 19.88 | 0.00750924 | 56486.5 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12526.780 | -999.000 | 1.064671 | 0.00044742 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1603 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.064671 | 1.28143212 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 1.3089 | 1.308893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 12526.78 | 11719.10 | 1.0000 | 1.28143212 | 1.064671 | 21.68 | 15.78 | 0.00877933 | 44097.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.44737355 | 6.70 | 11.72 | 6.67 | 0.000 | 12526.78 | 31.92 | 0.01409688 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00877933 | 21.11 | 0.00877933 | 56.2770 | 10868.40 | 0.00 | 12546.86 | 11576.56 | 1.28143212 | 21.68 | 15.79 | 0.00877933 | 44097.8 | 12.84 | 12.09 | 0.00847942 | 34306.5 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8524.093 | 8524.093 | 0.367673 | 0.00018833 | 194.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.064671 | 1.28143212 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.9921 | 1.883380 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 9197.84 | 8524.09 | 1.0000 | 0.44252937 | 0.367673 | 21.11 | 14.43 | 0.00752262 | 40321.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.18831020 | 60.00 | 49.00 | 11.00 | 0.000 | 9197.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752262 | 21.11 | 0.00752262 | 48.3170 | 8524.09 | 0.00 | 9202.02 | 9202.02 | 0.44252937 | 16.60 | 12.67 | 0.00752262 | 35726.1 | 37.01 | 19.89 | 0.00752262 | 56520.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12187.625 | 12187.625 | 1.225585 | 0.00026927 | 226.975 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 2.6541 | 2.692829 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12254.14 | 12187.63 | 1.0000 | 1.47510772 | 1.225585 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26924322 | 60.00 | 49.00 | 11.00 | 0.000 | 12254.14 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00761498 | 21.00 | 0.00761498 | 49.2359 | 5724.59 | 0.00 | 12258.68 | 12258.68 | 1.47510772 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.75 | 16.21 | 0.00800000 | 45245.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12624.953 | 12624.953 | 1.286534 | 0.00027893 | 234.771 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 2.7494 | 2.789456 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12693.94 | 12624.95 | 1.0000 | 1.54846550 | 1.286534 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27890445 | 60.00 | 49.00 | 11.00 | 0.000 | 12693.94 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00762218 | 21.00 | 0.00762218 | 49.2821 | 5840.51 | 0.00 | 12698.58 | 12698.58 | 1.54846550 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.64 | 16.17 | 0.00800000 | 45135.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8596.213 | 8596.213 | 1.301668 | 0.00018992 | 154.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.8724 | 1.899314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8644.80 | 8596.21 | 1.0000 | 1.56668109 | 1.301668 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.18990346 | 60.00 | 49.00 | 11.00 | 0.000 | 8644.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.42 | 0.00594954 | 21.00 | 0.00594954 | 38.5783 | 1758.54 | 0.00 | 8646.89 | 8646.89 | 1.56668109 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.01 | 15.21 | 0.00800000 | 42454.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7828.569 | 7828.569 | 0.346059 | 0.00017296 | 161.492 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 1.7058 | 1.729705 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7875.95 | 7828.57 | 1.0000 | 0.41651449 | 0.346059 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.17294502 | 60.00 | 49.00 | 11.00 | 0.000 | 7875.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00767512 | 21.00 | 0.00767512 | 49.6199 | 6003.43 | 0.00 | 7880.05 | 7880.05 | 0.41651449 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.15 | 19.68 | 0.00800000 | 55853.8 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 684170.521 | -999.000 | 20.403889 | 0.02443699 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.6918 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.403889 | 24.55801871 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 71.4887 | 71.488665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 684170.52 | 435360.58 | 1.0000 | 24.55801871 | 20.403889 | 28.78 | 20.91 | 0.01229288 | 60319.9 | 10.99 | 10.99 | 0.00828082 | 32473.3 | 24.43449294 | 6.70 | 11.72 | 6.67 | 45717.742 | 638452.78 | 32.10 | 0.01409687 | 23.10 | 12.05026000 | 59.0586 | 23.99 | 0.00969030 | 23.99 | 0.00952917 | 51.2123 | 280484.68 | 0.00 | 744024.35 | 464677.70 | 24.55801871 | 28.78 | 20.92 | 0.01229288 | 60319.9 | 10.37 | 10.32 | 0.00777938 | 30023.3 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 202847.702 | 202847.702 | 6.121167 | 0.00448167 | 2846.632 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.403889 | 24.55801871 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 31.1695 | 44.818753 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 143911.01 | 202847.70 | 1.0000 | 7.36740561 | 6.121167 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 4.48121494 | 60.00 | 49.00 | 11.00 | 0.000 | 143911.01 | -10.70 | 0.00150390 | -10.70 | 12.05026000 | 196.8621 | 18.52 | 0.00632152 | 21.00 | 0.00740491 | 47.8943 | 61932.87 | 0.00 | 143741.40 | 143741.40 | 7.36740561 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86019.671 | -999.000 | 2.051199 | 0.00307242 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0454 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 34.17953445 | 13.37 | 6.70 | 6.67 | 957033.56 | 8.9882 | 8.988156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86019.67 | 50571.42 | 1.0000 | 2.46881288 | 2.051199 | 32.03 | 23.08 | 0.01409687 | 68275.7 | 10.99 | 12.09 | 0.00828082 | 34322.2 | 3.07210994 | 6.70 | 11.72 | 6.67 | 2194.880 | 83824.79 | 32.03 | 0.01409687 | 23.08 | 2.05119905 | 100.0000 | 21.11 | 0.00874760 | 21.11 | 0.00874771 | 56.0756 | 155743.82 | 0.00 | 92041.54 | 54055.96 | 2.46881288 | 32.03 | 23.09 | 0.01409687 | 68275.7 | 10.79 | 10.73 | 0.00799366 | 30994.0 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 9.99852649 | 71.00 | 82.00 | 11.00 | 461704.26 | 3.1335 | 4.505621 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14467.35 | 20392.24 | 1.0000 | 0.74064386 | 0.615360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.45049567 | 60.00 | 49.00 | 11.00 | 0.000 | 14467.35 | -10.70 | 0.00150390 | -10.70 | 2.05119905 | 333.3333 | 21.11 | 0.00745087 | 21.11 | 0.00745237 | 47.8698 | 103343.54 | 0.00 | 14450.29 | 14450.29 | 0.74064386 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 12.05 | 20.40 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 27.17 | 8285.33 | 0.00 |
RETAIL_1_FLR_1 | 1411.33 | 7993.67 | 1061.33 |
RETAIL_2_FLR_1 | 65.50 | 8600.50 | 53.33 |
LAUNDRY_FLR_1 | 5167.83 | 3029.83 | 1810.33 |
CAFE_FLR_1 | 1411.17 | 6540.33 | 158.33 |
LOBBY_FLR_1 | 253.33 | 7840.67 | 5.17 |
ROOM_1_FLR_3 | 2385.17 | 8334.33 | 2308.50 |
ROOM_2_FLR_3 | 2964.00 | 8450.33 | 2910.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1937.33 | 8760.00 | 1937.33 |
ROOM_5_FLR_3 | 2264.33 | 8301.83 | 2246.17 |
ROOM_6_FLR_3 | 2829.50 | 8447.33 | 2811.83 |
ROOM_1_FLR_6 | 3006.17 | 8150.67 | 2815.17 |
ROOM_2_FLR_6 | 3442.67 | 8268.67 | 3305.00 |
ROOM_3_MULT9_FLR_6 | 1665.50 | 8187.33 | 1601.17 |
BANQUET_FLR_6 | 3236.00 | 3423.50 | 185.00 |
DINING_FLR_6 | 4342.00 | 1967.83 | 103.17 |
KITCHEN_FLR_6 | 7941.17 | 6407.67 | 6162.17 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8724.50 | 8760.00 | 7529.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 116.50 | 0.00 | 116.50 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 2.00 | 3.00 | 2.00 | 3.00 |
ROOM_2_FLR_3 | 4.17 | 1.17 | 4.17 | 1.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 5.50 | 13.00 | 5.50 | 13.00 |
ROOM_5_FLR_3 | 2.83 | 3.50 | 2.83 | 3.50 |
ROOM_6_FLR_3 | 7.17 | 3.17 | 7.17 | 3.17 |
ROOM_1_FLR_6 | 2.00 | 12.00 | 2.00 | 12.00 |
ROOM_2_FLR_6 | 4.00 | 7.67 | 4.00 | 7.67 |
ROOM_3_MULT9_FLR_6 | 1.50 | 27.83 | 1.50 | 27.83 |
BANQUET_FLR_6 | 0.00 | 1.50 | 0.00 | 1.50 |
DINING_FLR_6 | 0.00 | 2.50 | 0.00 | 2.50 |
KITCHEN_FLR_6 | 0.00 | 378.00 | 0.00 | 378.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 9.83 | 467.33 | 9.83 | 467.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.019 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.362 | 0.270 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.506 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 22.974 | 0.150 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 3.573 | 0.243 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.774 | 0.070 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.177 | 0.000 | 0.088 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.177 | 0.000 | 0.085 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.079 | 0.000 | 0.135 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.177 | 0.000 | 0.088 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.177 | 0.000 | 0.085 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.177 | 0.000 | 0.107 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.177 | 0.000 | 0.103 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.144 | 0.000 | 0.169 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.439 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.773 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 19.653 | 0.148 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.670 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.493 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.964 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 17.313 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 2.341 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.235 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.453 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.514 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.453 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.306 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.631 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.591 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
Electricity:Building | 2519.15 | 32386.38 | 20-MAY-05:00 | 155989.88 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 320.72 | 3678.09 | 02-JAN-02:10 | 24053.66 | 02-JAN-20:10 |
InteriorLights:Electricity | 767.03 | 6553.44 | 20-MAY-05:00 | 66976.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 170.46 | 1548.87 | 02-JAN-02:10 | 13939.86 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 767.03 | 6553.44 | 20-MAY-05:00 | 66976.13 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 19.20 | 226.21 | 02-JAN-02:10 | 1422.43 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 9.01 | 81.87 | 02-JAN-02:10 | 736.82 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 22.23 | 261.95 | 02-JAN-02:10 | 1647.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 10.43 | 94.80 | 02-JAN-02:10 | 853.24 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.85 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.91 | 81.05 | 02-JAN-02:10 | 512.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.31 | 30.07 | 02-JAN-02:10 | 270.66 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.93 | 1008.06 | 02-JAN-02:10 | 4981.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.99 | 45.36 | 02-JAN-02:10 | 408.24 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.27 | 322.63 | 20-MAY-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.93 | 119.42 | 20-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 292.54 | 3392.07 | 20-MAY-05:00 | 22119.33 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 143.53 | 1280.66 | 20-MAY-05:00 | 12090.12 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.98 | 253.36 | 01-JAN-02:10 | 1306.07 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.55 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.98 | 253.33 | 01-JAN-02:10 | 1305.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 296.68 | 4430.63 | 01-JAN-02:10 | 21465.35 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 67.93 | 424.31 | 01-JAN-11:10 | 6788.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 296.76 | 4431.84 | 01-JAN-02:10 | 21471.23 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 67.94 | 424.43 | 01-JAN-11:10 | 6790.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.98 | 253.36 | 01-JAN-02:10 | 1306.07 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.55 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.98 | 253.33 | 01-JAN-02:10 | 1305.92 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.69 | 35.53 | 01-JAN-11:10 | 568.49 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.50 | 63.34 | 01-JAN-02:10 | 326.52 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.42 | 8.88 | 01-JAN-11:10 | 142.14 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.49 | 63.33 | 01-JAN-02:10 | 326.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.42 | 8.88 | 01-JAN-11:10 | 142.12 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.14 | 524.82 | 01-JAN-02:10 | 2542.65 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.05 | 50.26 | 01-JAN-11:10 | 804.17 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.49 | 2524.33 | 20-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.64 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.49 | 2524.33 | 20-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.64 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.02 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.67 | 1114.64 | 11-FEB-23:30 | 3353.91 | 17-NOV-08:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1466.79 | 2740.71 | 18-OCT-02:20 | 201433.51 | 04-AUG-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.35 | 0.00 | 01-JAN-11:10 | 1987.07 | 31-OCT-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.23 | 932.83 | 06-FEB-04:10 | 1234.82 | 08-OCT-09:50 |
WaterSystems:Electricity | 90.75 | 1086.62 | 15-MAY-00:30 | 4738.74 | 04-OCT-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.62 | 15-MAY-00:30 | 4738.74 | 04-OCT-18:10 |
Fans:Electricity | 573.44 | 14446.09 | 10-SEP-05:10 | 44795.79 | 18-OCT-20:30 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 852.53 | 15368.33 | 10-SEP-05:30 | 52518.56 | 18-OCT-20:30 |
ExteriorEquipment:Electricity | 982.92 | 6683.63 | 02-JAN-02:20 | 63148.16 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.46 | 553.69 | 10-JUN-05:00 | 1873.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
ElectricityPurchased:Plant | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
Cogeneration:ElectricityPurchased | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
ElectricityNet:Plant | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
Cogeneration:ElectricityNet | 6015.38 | 74624.79 | 01-NOV-01:10 | 457808.91 | 03-AUG-20:00 |
General:Fans:Electricity | 573.44 | 14446.09 | 10-SEP-05:10 | 44795.79 | 18-OCT-20:30 |
ExteriorLights:Electricity | 226.46 | 0.00 | 01-JAN-07:30 | 14423.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 226.46 | 0.00 | 01-JAN-07:30 | 14423.55 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 246.63 | 0.00 | 02-MAR-15:40 | 10206.30 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1236.15 | 0.00 | 01-JAN-00:10 | 192130.39 | 16-AUG-15:20 |
General:Cooling:Electricity | 1236.15 | 0.00 | 01-JAN-00:10 | 192130.39 | 16-AUG-15:20 |
Pumps:Electricity | 85.31 | 47.91 | 03-MAR-19:00 | 5443.62 | 24-JUN-18:30 |
General:Pumps:Electricity | 85.31 | 47.91 | 03-MAR-19:00 | 5443.62 | 24-JUN-18:30 |
WIRED_LTG_ELECTRICITY | 27.00 | 0.00 | 01-JAN-00:10 | 2357.56 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4624.22 | 31354.88 | 17-OCT-02:20 | 444669.20 | 14-JAN-17:30 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 2835.37 | 15908.90 | 26-JUN-07:10 | 385233.22 | 05-FEB-23:40 |
WaterSystems:Gas | 2126.52 | 15908.90 | 17-JAN-11:40 | 178891.13 | 18-JAN-21:10 |
Water Heater:WaterSystems:Gas | 2126.52 | 15908.90 | 17-JAN-11:40 | 178891.13 | 18-JAN-21:10 |
Heating:Gas | 708.85 | 0.00 | 03-MAR-11:30 | 231070.53 | 06-FEB-07:10 |
Boiler:Heating:Gas | 708.85 | 0.00 | 03-MAR-11:30 | 231070.53 | 06-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4212.45 | 0.00 | 01-JAN-00:10 | 716633.59 | 03-AUG-20:00 |
PlantLoopCoolingDemand:HVAC | 4212.45 | 0.00 | 01-JAN-00:10 | 716633.59 | 03-AUG-20:00 |
CoolingCoils:PlantLoopCoolingDemand | 4212.45 | 0.00 | 01-JAN-00:10 | 716633.59 | 03-AUG-20:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 28-MAR-18:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 28-MAR-18:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 18-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 18-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 24852.16 | 157400.05 | 17-APR-13:10 | 2924829.40 | 03-AUG-20:10 |
EnergyTransfer:Building | 5172.35 | 76665.54 | 13-JAN-12:10 | 328147.34 | 03-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 727.80 | 10814.18 | 06-FEB-04:00 | 35740.27 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 182.35 | 3977.75 | 06-FEB-04:00 | 10488.61 | 17-NOV-08:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.17 | 1988.88 | 06-FEB-04:00 | 5244.30 | 17-NOV-08:20 |
EnergyTransfer:Plant | 11113.30 | 18611.21 | 27-OCT-01:20 | 1663747.22 | 03-AUG-20:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.60 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.58 | 1748.49 | 06-FEB-04:10 | 2654.45 | 08-OCT-09:50 |
PlantLoopHeatingDemand:Facility | 1244.11 | 9004.38 | 16-SEP-00:10 | 243359.23 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 743.52 | 8501.67 | 31-JUL-00:10 | 56368.54 | 09-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 743.52 | 8501.67 | 31-JUL-00:10 | 56368.54 | 09-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 434.35 | 2180.80 | 03-APR-17:30 | 22962.85 | 27-OCT-19:40 |
Heating:EnergyTransfer | 149.30 | 0.00 | 12-JAN-18:20 | 91048.29 | 14-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4931.87 | 73303.51 | 08-JAN-16:00 | 325162.76 | 21-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 434.35 | 2180.80 | 03-APR-17:30 | 22962.85 | 27-OCT-19:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.09 | 0.01 | 23-FEB-15:10 | 3702.72 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.76 | 0.00 | 01-JAN-08:40 | 1522.34 | 06-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.33 | 0.00 | 01-JAN-00:10 | 3702.72 | 04-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.42 | 189.43 | 26-DEC-19:20 | 1834.09 | 24-AUG-20:30 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 30.67 | 07-NOV-08:20 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.42 | 189.43 | 26-DEC-19:20 | 1834.09 | 24-AUG-20:30 |
EnergyTransfer:Zone:MECH_FLR_1 | 29.82 | 0.19 | 14-FEB-01:10 | 1590.98 | 24-AUG-20:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.09 | 0.00 | 01-JAN-07:50 | 489.42 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.73 | 0.00 | 01-JAN-00:10 | 1590.98 | 24-AUG-20:30 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.63 | 0.02 | 06-DEC-12:30 | 725.89 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.47 | 0.00 | 03-JAN-18:20 | 489.87 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.16 | 0.00 | 01-JAN-00:10 | 725.89 | 04-AUG-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.48 | 8918.13 | 02-JAN-05:00 | 38437.41 | 27-OCT-19:50 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.48 | 8918.13 | 02-JAN-05:00 | 38437.41 | 27-OCT-19:50 |
EnergyTransfer:Zone:CAFE_FLR_1 | 224.65 | 3.19 | 11-DEC-14:50 | 13377.69 | 30-SEP-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 1104.72 | 14-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 224.62 | 0.00 | 02-JAN-07:10 | 13377.69 | 30-SEP-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 810.17 | 5397.27 | 03-APR-17:30 | 37121.94 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 226.38 | 03-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 810.17 | 5397.27 | 03-APR-17:30 | 37121.94 | 04-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.09 | 0.21 | 30-APR-07:00 | 11183.78 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 15.50 | 0.00 | 01-JAN-08:10 | 6024.49 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.59 | 0.00 | 01-JAN-00:10 | 11183.78 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.18 | 0.19 | 06-DEC-15:30 | 10601.68 | 22-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.63 | 0.00 | 01-JAN-08:10 | 6100.98 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 36.55 | 0.00 | 01-JAN-00:10 | 10601.68 | 22-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 361.74 | 0.04 | 13-JAN-22:10 | 53301.06 | 04-OCT-12:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 5.86 | 0.00 | 01-JAN-08:10 | 15167.13 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 355.89 | 0.00 | 01-JAN-00:10 | 53301.06 | 04-OCT-12:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 410.18 | 0.21 | 05-DEC-09:30 | 63848.39 | 26-JUN-15:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 35.23 | 0.00 | 01-JAN-08:10 | 33995.71 | 06-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 374.96 | 0.00 | 01-JAN-00:10 | 63848.39 | 26-JUN-15:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 56.23 | 0.13 | 31-OCT-16:50 | 10171.03 | 14-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 15.32 | 0.00 | 01-JAN-08:10 | 6075.55 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 40.91 | 0.00 | 01-JAN-00:10 | 10171.03 | 14-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 54.90 | 0.06 | 04-NOV-23:20 | 10144.37 | 14-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 19.28 | 0.00 | 01-JAN-08:10 | 6166.90 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 35.62 | 0.00 | 01-JAN-00:10 | 10144.37 | 14-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 126.00 | 0.06 | 24-MAR-00:40 | 7868.81 | 24-AUG-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.22 | 0.00 | 01-JAN-10:20 | 3843.86 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 117.79 | 0.00 | 01-JAN-00:10 | 7868.81 | 24-AUG-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.41 | 0.01 | 19-NOV-14:30 | 3033.35 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.74 | 0.00 | 01-JAN-08:10 | 1884.13 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.67 | 0.00 | 01-JAN-00:10 | 3033.35 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.38 | 0.04 | 30-SEP-02:40 | 2953.77 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.08 | 0.00 | 01-JAN-08:10 | 1882.92 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.30 | 0.00 | 01-JAN-00:10 | 2953.77 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 88.23 | 0.09 | 10-MAR-10:50 | 12553.33 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.69 | 0.00 | 01-JAN-08:10 | 8260.69 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 75.55 | 0.00 | 01-JAN-00:10 | 12553.33 | 16-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 444.04 | 6277.55 | 13-JAN-12:10 | 22832.41 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 444.04 | 6277.55 | 13-JAN-12:10 | 22832.41 | 04-AUG-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 485.89 | 7255.81 | 13-JAN-12:10 | 24269.00 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 485.89 | 7255.81 | 13-JAN-12:10 | 24269.00 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 636.62 | 8825.31 | 06-FEB-04:00 | 30680.13 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 77.66 | 0.01 | 09-DEC-00:50 | 4597.60 | 18-AUG-13:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.42 | 0.00 | 01-JAN-09:30 | 2847.76 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 75.24 | 0.00 | 01-JAN-00:10 | 4597.60 | 18-AUG-13:40 |
WaterSystems:EnergyTransfer | 743.52 | 8501.67 | 31-JUL-00:10 | 56368.54 | 09-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 743.52 | 8501.67 | 31-JUL-00:10 | 56368.54 | 09-FEB-07:30 |
EnergyTransfer:HVAC | 8566.51 | 2546.73 | 05-APR-11:10 | 957514.65 | 03-AUG-20:00 |
HeatingCoils:EnergyTransfer | 500.58 | 0.00 | 03-MAR-11:30 | 189943.11 | 14-JAN-16:10 |
PlantLoopHeatingDemand:HVAC | 500.58 | 0.00 | 03-MAR-11:30 | 189943.11 | 14-JAN-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 500.58 | 0.00 | 03-MAR-11:30 | 189943.11 | 14-JAN-16:10 |
CoolingCoils:EnergyTransfer | 4212.45 | 0.00 | 01-JAN-00:10 | 716633.59 | 03-AUG-20:00 |
HeatRecoveryForHeating:EnergyTransfer | 3051.32 | 0.00 | 02-MAR-15:40 | 493486.29 | 06-FEB-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 802.16 | 0.00 | 01-JAN-00:10 | 309035.67 | 08-JUL-12:00 |
Boilers:EnergyTransfer | 491.43 | 0.00 | 03-MAR-11:30 | 185650.31 | 06-FEB-07:10 |
Chillers:EnergyTransfer | 4275.51 | 0.00 | 01-JAN-00:10 | 720387.39 | 03-AUG-20:00 |
HeatRejection:EnergyTransfer | 5511.66 | 0.00 | 01-JAN-00:10 | 908822.09 | 03-AUG-20:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -434.350 | 0.000 | 0.000 | 145.950 | 170.465 | 150.259 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -32.324 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.764 | -37.330 | 0.000 | 0.000 | 15.833 | 9.010 | 10.186 | 22.319 | 0.000 | 0.514 | 0.000 | 0.000 | -9.763 | 0.000 | -7.591 | -4.942 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -38.422 | 0.000 | 0.000 | 17.611 | 10.434 | 11.795 | 0.000 | 0.000 | 0.109 | 0.143 | 0.000 | 0.000 | 0.000 | -1.671 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -602.486 | 0.000 | 0.000 | 11.648 | 4.992 | 658.148 | 0.000 | 0.000 | 0.382 | 0.000 | 0.000 | 0.000 | 0.000 | -5.345 | -67.339 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.029 | -224.620 | 0.000 | 0.000 | 196.841 | 17.927 | 14.341 | 61.936 | 0.000 | 1.139 | 0.000 | 0.000 | -29.292 | 0.000 | -20.452 | -17.849 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -810.169 | 0.000 | 0.000 | 575.930 | 143.534 | 149.002 | 82.424 | 0.000 | 2.452 | 0.000 | 0.000 | -39.562 | 0.000 | -41.622 | -61.990 |
ROOM_1_FLR_3 | 15.499 | -25.604 | 0.000 | -15.987 | 0.000 | 0.000 | 9.742 | 5.689 | 12.292 | 43.566 | 0.000 | 1.249 | 0.000 | 0.000 | -22.645 | 0.000 | -9.412 | -14.389 |
ROOM_2_FLR_3 | 19.631 | -20.869 | 0.000 | -15.683 | 0.000 | 0.000 | 9.770 | 5.688 | 12.291 | 31.858 | 0.000 | 1.232 | 0.000 | 0.000 | -23.396 | 0.000 | -9.274 | -11.247 |
ROOM_3_MULT19_FLR_3 | 5.856 | -114.312 | 0.000 | -241.574 | 0.000 | 0.000 | 0.000 | 67.926 | 228.754 | 264.966 | 0.000 | 6.388 | 0.004 | 0.000 | -127.928 | 0.000 | -69.577 | -20.498 |
ROOM_4_MULT19_FLR_3 | 35.227 | -161.730 | 0.000 | -213.220 | 0.000 | 0.000 | 185.537 | 67.944 | 228.817 | 85.522 | 0.000 | 14.794 | 0.000 | 0.000 | -132.535 | 0.000 | -56.920 | -53.435 |
ROOM_5_FLR_3 | 15.318 | -24.842 | 0.000 | -16.067 | 0.000 | 0.000 | 9.735 | 5.689 | 12.292 | 42.936 | 0.000 | 1.244 | 0.000 | 0.000 | -22.327 | 0.000 | -9.440 | -14.538 |
ROOM_6_FLR_3 | 19.276 | -19.848 | 0.000 | -15.773 | 0.000 | 0.000 | 9.763 | 5.688 | 12.291 | 30.920 | 0.000 | 1.225 | 0.000 | 0.000 | -22.778 | 0.000 | -9.305 | -11.457 |
ROOM_1_FLR_6 | 5.744 | -7.683 | 0.000 | -3.984 | 0.000 | 0.000 | 2.437 | 1.422 | 3.073 | 10.816 | 0.000 | 0.332 | 0.000 | 0.000 | -5.655 | 0.000 | -2.391 | -4.112 |
ROOM_2_FLR_6 | 7.077 | -6.384 | 0.000 | -3.914 | 0.000 | 0.000 | 2.443 | 1.422 | 3.073 | 7.895 | 0.000 | 0.326 | 0.000 | 0.000 | -5.838 | 0.000 | -2.357 | -3.744 |
ROOM_3_MULT9_FLR_6 | 12.687 | -49.283 | 0.000 | -26.262 | 0.000 | 0.000 | 21.841 | 8.046 | 27.097 | 57.908 | 0.000 | 2.277 | 0.000 | 0.000 | -26.654 | 0.000 | -11.977 | -15.680 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -444.045 | 0.000 | 0.000 | 320.767 | 34.638 | 175.857 | 8.691 | 0.000 | 0.251 | 0.000 | 0.000 | -18.030 | 0.000 | -6.425 | -71.704 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -485.894 | 0.000 | 0.000 | 318.510 | 34.638 | 175.857 | 8.399 | 0.000 | 0.239 | 0.000 | 0.000 | -18.681 | 0.000 | -6.504 | -26.563 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -636.604 | 0.000 | 0.000 | 28.911 | 13.327 | 550.372 | 20.342 | 0.000 | 0.199 | 41.233 | 0.000 | -11.930 | 0.000 | -5.851 | -0.002 |
MECH_FLR_1 | 0.000 | 0.000 | 0.091 | -29.731 | 0.000 | 0.000 | 0.000 | 16.636 | 12.472 | 0.000 | 0.000 | 0.260 | 3.768 | 0.000 | 0.000 | 0.000 | -3.495 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.467 | -12.159 | 0.000 | 0.000 | 0.000 | 3.310 | 3.598 | 0.000 | 0.000 | 0.183 | 7.007 | 0.000 | 0.000 | 0.000 | -2.406 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 8.216 | -117.786 | 0.000 | 0.000 | 0.000 | 109.607 | 0.000 | 40.743 | 0.000 | 0.912 | 0.001 | 0.000 | -27.681 | 0.000 | -10.577 | -3.435 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 2.420 | -75.236 | 0.000 | 0.000 | 0.000 | 29.000 | 0.000 | 19.314 | 0.000 | 0.277 | 41.780 | 0.000 | -12.771 | 0.000 | -4.785 | -0.001 |
Total Facility | 136.315 | -430.555 | 12.987 | -4501.296 | 0.000 | 0.000 | 1883.268 | 767.031 | 2451.865 | 840.557 | 0.000 | 35.985 | 93.939 | 0.000 | -557.468 | 0.000 | -297.376 | -435.248 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-NOV-06:28 | 0.00 | 0.00 | 0.00 | -27188.99 | 0.00 | 0.00 | 5188.17 | 6195.49 | 5323.05 | 0.00 | 0.00 | 0.00 | 10482.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 03-DEC-11:36 | 0.00 | 0.00 | 0.00 | -3717.84 | 0.00 | 0.00 | 225.90 | 245.61 | 288.68 | 7041.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -416.36 | -3667.28 |
RETAIL_2_FLR_1 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | -2122.32 | 0.00 | 0.00 | 381.90 | 474.02 | 501.43 | 0.00 | 0.00 | 0.00 | 841.32 | 0.00 | -0.00 | 0.00 | -76.36 | 0.00 |
LAUNDRY_FLR_1 | 18-OCT-20:30 | 0.00 | 0.00 | 0.00 | -41680.75 | 0.00 | 0.00 | 404.59 | 362.88 | 41967.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -285.69 | -768.87 |
CAFE_FLR_1 | 03-DEC-11:36 | 0.00 | 0.00 | 0.00 | -15881.56 | 0.00 | 0.00 | 2968.61 | 358.25 | 406.43 | 19748.60 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1054.34 | -6546.00 |
LOBBY_FLR_1 | 11-APR-22:03 | 0.00 | 0.00 | 0.00 | -48292.28 | 0.00 | 0.00 | 25724.53 | 4030.04 | 4222.82 | 0.00 | 0.00 | 0.00 | 19222.93 | 0.00 | -2907.35 | 0.00 | -2000.69 | 0.00 |
ROOM_1_FLR_3 | 04-AUG-15:02 | 0.00 | -11764.69 | 0.00 | -753.09 | 0.00 | 0.00 | 235.28 | 45.48 | 273.93 | 8118.33 | 0.00 | 219.71 | 3625.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 26-JUN-15:02 | 0.00 | -11558.78 | 0.00 | -751.32 | 0.00 | 0.00 | 235.28 | 45.48 | 273.90 | 9203.47 | 0.00 | 115.00 | 2436.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:00 | 0.00 | -42468.80 | 0.00 | -10829.11 | 0.00 | 0.00 | 0.00 | 424.31 | 5097.90 | 72782.33 | 0.00 | 147.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25154.15 |
ROOM_4_MULT19_FLR_3 | 01-SEP-18:02 | 0.00 | -63158.24 | 0.00 | -10032.33 | 0.00 | 0.00 | 6497.78 | 6026.84 | 9610.21 | 3320.50 | 0.00 | 722.13 | 47013.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUL-08:62 | 0.00 | -10585.91 | 0.00 | -761.86 | 0.00 | 0.00 | 87.14 | 248.74 | 453.05 | 10140.42 | 0.00 | 137.32 | 281.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 18-AUG-08:62 | 0.00 | -10514.13 | 0.00 | -759.68 | 0.00 | 0.00 | 87.14 | 248.71 | 452.99 | 10049.73 | 0.00 | 139.49 | 295.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 15-AUG-18:02 | 0.00 | -3083.89 | 0.00 | -189.65 | 0.00 | 0.00 | 83.87 | 126.15 | 129.07 | 1199.17 | 0.00 | 117.25 | 1618.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 02-AUG-15:02 | 0.00 | -3045.00 | 0.00 | -190.38 | 0.00 | 0.00 | 58.82 | 11.37 | 68.48 | 2440.34 | 0.00 | 50.69 | 605.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 07-SEP-15:02 | 0.00 | -12365.37 | 0.00 | -1239.87 | 0.00 | 0.00 | 529.38 | 64.33 | 603.86 | 4036.18 | 0.00 | 1747.66 | 6623.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 11-APR-22:27 | 0.00 | 0.00 | 0.00 | -29423.92 | 0.00 | 0.00 | 15511.54 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 7542.54 | 0.00 | -1130.31 | 0.00 | -279.11 | 0.00 |
DINING_FLR_6 | 07-NOV-23:52 | 0.00 | 0.00 | 0.00 | -31846.67 | 0.00 | 0.00 | 15654.82 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 9775.68 | 0.00 | -1081.13 | 0.00 | -281.95 | 0.00 |
KITCHEN_FLR_6 | 20-FEB-10:52 | 0.00 | 0.00 | 0.00 | -35661.94 | 0.00 | 0.00 | 753.22 | 363.28 | 24259.91 | 961.27 | 0.00 | 0.00 | 9554.94 | 0.00 | -0.00 | 0.00 | -230.67 | 0.00 |
MECH_FLR_1 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | -1857.10 | 0.00 | 0.00 | 0.00 | 755.78 | 530.18 | 0.00 | 0.00 | 0.00 | 729.62 | 0.00 | -0.00 | 0.00 | -158.47 | 0.00 |
STORAGE_FLR_1 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | -847.15 | 0.00 | 0.00 | 0.00 | 150.37 | 152.94 | 0.00 | 0.00 | 0.00 | 651.10 | 0.00 | -0.00 | 0.00 | -107.25 | 0.00 |
CORRIDOR_FLR_3 | 08-OCT-10:15 | 0.00 | 0.00 | 0.00 | -9056.45 | 0.00 | 0.00 | 0.00 | 2987.71 | 0.00 | 6485.44 | 0.00 | 0.00 | 21.56 | 0.00 | -0.00 | 0.00 | -438.26 | 0.00 |
CORRIDOR_FLR_6 | 29-NOV-12:02 | 0.00 | 0.00 | 0.00 | -4855.79 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 4569.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -204.18 | -168.76 |
Total Facility | 10-JUL-18:02 | 0.00 | -141960.27 | 0.00 | -205057.67 | 0.00 | 0.00 | 71290.69 | 57047.62 | 122326.88 | 37303.27 | 0.00 | 5145.05 | 53904.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 06-FEB-07:15 | 0.00 | 0.00 | 1523.40 | -0.00 | 0.00 | 0.00 | 360.88 | 409.35 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1075.14 | 0.00 | -890.44 | -761.05 |
RETAIL_2_FLR_1 | 29-OCT-08:52 | 0.00 | 0.00 | 120.34 | -0.00 | 0.00 | 0.00 | 480.16 | 284.41 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -77.39 | -1141.81 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 14-JAN-17:00 | 0.00 | 0.00 | 1104.75 | -0.00 | 0.00 | 0.00 | 3528.30 | 489.42 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3314.99 | 0.00 | -1788.54 | -374.56 |
LOBBY_FLR_1 | 03-JAN-09:10 | 0.00 | 0.00 | 1358.25 | -0.00 | 0.00 | 0.00 | 6868.52 | 5122.63 | 5278.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2090.22 | 0.00 | -1537.81 | -14999.89 |
ROOM_1_FLR_3 | 14-JAN-16:13 | 6660.77 | 373.46 | 0.00 | -373.46 | 0.00 | 0.00 | 148.26 | 35.53 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2608.89 | 0.00 | -818.93 | -3722.28 |
ROOM_2_FLR_3 | 02-JAN-09:02 | 6654.57 | 284.71 | 0.00 | -284.71 | 0.00 | 0.00 | 108.88 | 248.71 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1888.40 | 0.00 | -931.37 | -4645.39 |
ROOM_3_MULT19_FLR_3 | 02-JAN-05:10 | 15167.28 | 3440.01 | 0.00 | -3440.01 | 0.00 | 0.00 | 0.00 | 933.48 | 3921.46 | 0.00 | 0.00 | 0.00 | 2102.81 | 0.00 | -16924.14 | 0.00 | -5200.88 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:02 | 35717.85 | 3750.70 | 0.00 | -3750.70 | 0.00 | 0.00 | 5585.69 | 543.26 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12775.89 | 0.00 | -4199.81 | -29970.40 |
ROOM_5_FLR_3 | 14-JAN-16:13 | 6416.07 | 367.46 | 0.00 | -367.46 | 0.00 | 0.00 | 148.47 | 35.53 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2650.01 | 0.00 | -816.47 | -3439.14 |
ROOM_6_FLR_3 | 14-JAN-16:13 | 6417.92 | 365.42 | 0.00 | -365.42 | 0.00 | 0.00 | 148.76 | 35.53 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2664.19 | 0.00 | -815.57 | -3427.95 |
ROOM_1_FLR_6 | 14-JAN-16:13 | 1946.23 | 90.74 | 0.00 | -90.74 | 0.00 | 0.00 | 37.31 | 8.88 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -649.39 | 0.00 | -204.17 | -1215.26 |
ROOM_2_FLR_6 | 14-JAN-16:13 | 1942.81 | 90.05 | 0.00 | -90.05 | 0.00 | 0.00 | 37.41 | 8.88 | 76.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.50 | 0.00 | -203.87 | -1208.12 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:13 | 8505.45 | 565.88 | 0.00 | -565.88 | 0.00 | 0.00 | 338.05 | 50.26 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3030.80 | 0.00 | -935.07 | -5601.43 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 489.43 | -0.00 | 0.00 | 0.00 | 0.00 | 151.16 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.33 | -404.98 |
STORAGE_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 489.88 | -0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -286.68 | -284.25 |
CORRIDOR_FLR_3 | 02-JAN-05:00 | 0.00 | 0.00 | 3843.97 | -0.00 | 0.00 | 0.00 | 0.00 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 453.49 | 0.00 | -4031.27 | 0.00 | -1262.09 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-05:10 | 0.00 | 0.00 | 2847.81 | -0.00 | 0.00 | 0.00 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1800.32 | 0.00 | -560.69 | -1013.80 |
Total Facility | 14-JAN-16:13 | 9780.46 | 86923.80 | 8266.90 | -86923.80 | 0.00 | 0.00 | 33249.19 | 14957.19 | 78718.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60861.24 | 0.00 | -23233.01 | -60877.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.7616 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 20.4039 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.0417 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 12.0417 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4166 | 2.4166 | 1.4016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3106 | 0.3106 | 0.1802 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2299 | 0.2299 | 0.1333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2618 | 3.2618 | 1.8919 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3182 | 1.3182 | 0.7645 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5485 | 4.5485 | 2.6381 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1131 | 2.1131 | 1.2256 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2182 | 2.2182 | 1.2865 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2443 | 2.2443 | 1.3017 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2155 | 0.2155 | 0.1250 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1014 | 0.1014 | 0.0588 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5967 | 0.5967 | 0.3461 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.7616 | 20.4039 | 20.7616 | 12.0417 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4016 | 1.4016 | 1.4016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1802 | 0.1802 | 0.1802 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1333 | 0.1333 | 0.1333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8919 | 1.8919 | 1.8919 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7645 | 0.7645 | 0.7645 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6381 | 2.6381 | 2.6381 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2256 | 1.2256 | 1.2256 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2865 | 1.2865 | 1.2865 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3017 | 1.3017 | 1.3017 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1250 | 0.1250 | 0.1250 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0588 | 0.0588 | 0.0588 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6884 | 0.6884 | 0.6884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3461 | 0.3461 | 0.3461 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.0417 | 12.0417 | 12.0417 | 12.0417 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 9.83 |
Number of hours cooling loads not met | 467.33 |
Number of hours not met | 477.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 708.85 | 231070.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1236.15 | 192130.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 767.03 | 66976.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 226.46 | 14423.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.46 | 1873.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 573.44 | 44795.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 85.31 | 5443.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 246.63 | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.74 | 2126.52 | 178891.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.35 | 1987.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.23 | 1234.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.69 | 6015.38 |
Natural Gas | 1788.85 | 4624.22 |
Additional | 0.00 | 0.00 |
Total | 3595.55 | 10639.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.61 |
Space Heating | 0.00 |
Space Cooling | 108.96 |
Fans (All) | 50.54 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 530.21 |
Subtotal | 530.21 |
Natural Gas [MJ/m2] | |
Space Heating | 62.48 |
Service Water Heating | 187.44 |
Miscellaneous (All) | 407.59 |
Subtotal | 407.59 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.21 |
Space Heating | 6.66 |
Space Cooling | 11.62 |
Fans (All) | 5.39 |
Service Water Heating | 20.84 |
Receptacle Equipment | 33.21 |
Miscellaneous | 15.07 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2842. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.169080E+12 |
February | 0.000 | 0.151553E+12 |
March | 0.000 | 0.707999E+11 |
April | 0.000 | 0.469323E+11 |
May | 0.000 | 0.218968E+11 |
June | 0.000 | 0.126067E+11 |
July | 0.000 | 0.974367E+10 |
August | 0.000 | 0.804058E+10 |
September | 0.000 | 0.119040E+11 |
October | 0.000 | 0.267074E+11 |
November | 0.000 | 0.733076E+11 |
December | 0.000 | 0.106276E+12 |
Annual Sum or Average | 0.708849E+12 | |
Minimum of Months | 0.000 | 0.804058E+10 |
Maximum of Months | 0.000 | 0.169080E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349618E+11 | 22326.31 | 18-JAN-07:10 | 8.40 | 8.15 | 0.774053E+10 | 4836.97 | 20-JAN-22:10 | 3.72 | 3.02 |
February | 0.299266E+11 | 21701.61 | 20-FEB-10:52 | 8.30 | 3.19 | 0.672773E+10 | 4798.25 | 01-FEB-22:10 | 4.90 | 2.78 |
March | 0.319267E+11 | 22207.59 | 31-MAR-18:17 | 7.80 | 7.80 | 0.723108E+10 | 4555.57 | 01-MAR-22:10 | 5.50 | 4.48 |
April | 0.309211E+11 | 20381.56 | 23-APR-06:07 | 8.48 | 5.81 | 0.669984E+10 | 4467.07 | 20-APR-21:10 | 9.40 | 7.15 |
May | 0.326336E+11 | 19100.93 | 02-MAY-05:44 | 8.80 | 5.34 | 0.651096E+10 | 4334.77 | 01-MAY-21:10 | 9.50 | 5.24 |
June | 0.348513E+11 | 15904.83 | 22-JUN-20:30 | 26.40 | 16.43 | 0.615098E+10 | 4036.05 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.388428E+11 | 16014.95 | 14-JUL-21:00 | 21.70 | 20.88 | 0.638102E+10 | 4013.32 | 14-JUL-21:10 | 21.70 | 20.94 |
August | 0.409274E+11 | 17225.86 | 24-AUG-20:30 | 26.40 | 15.68 | 0.670851E+10 | 4225.23 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.404249E+11 | 19944.08 | 24-SEP-05:13 | 10.40 | 8.70 | 0.692874E+10 | 4698.71 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.417511E+11 | 25965.29 | 18-OCT-20:33 | 8.67 | 6.08 | 0.790003E+10 | 4890.62 | 30-OCT-21:40 | 8.50 | 4.05 |
November | 0.392582E+11 | 27189.75 | 05-NOV-06:28 | 8.30 | 5.80 | 0.788032E+10 | 4918.18 | 16-NOV-22:00 | 9.40 | 7.72 |
December | 0.379235E+11 | 26056.00 | 04-DEC-20:50 | 8.90 | 7.96 | 0.804263E+10 | 4854.34 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.434349E+12 | 0.849024E+11 | ||||||||
Minimum of Months | 0.299266E+11 | 15904.83 | 7.80 | 3.19 | 0.615098E+10 | 4013.32 | 3.72 | 2.78 | ||
Maximum of Months | 0.417511E+11 | 27189.75 | 26.40 | 20.88 | 0.804263E+10 | 4918.18 | 22.52 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837648E+09 | 3295.00 | 17-JAN-13:20 | 10.37 | 5.43 | 0.623972E+09 | 370.21 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.102418E+10 | 2467.87 | 20-FEB-10:52 | 8.30 | 3.19 | 0.566298E+09 | 364.14 | 06-FEB-02:09 | -13.4 | -14.8 |
March | 0.180620E+10 | 3376.66 | 07-MAR-13:30 | 9.70 | 4.79 | 0.634256E+09 | 411.60 | 03-MAR-22:19 | 10.40 | 6.33 |
April | 0.241142E+10 | 2544.80 | 07-APR-12:40 | 26.33 | 16.04 | 0.613226E+09 | 425.60 | 11-APR-21:49 | 8.48 | 1.27 |
May | 0.356403E+10 | 2153.81 | 30-MAY-15:10 | 28.30 | 17.25 | 0.633539E+09 | 414.39 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.461457E+10 | 2334.70 | 19-JUN-19:20 | 31.13 | 22.28 | 0.630366E+09 | 458.60 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.534150E+10 | 2366.90 | 08-JUL-12:40 | 31.47 | 25.92 | 0.675481E+09 | 459.05 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.554905E+10 | 3116.90 | 30-AUG-11:42 | 26.32 | 14.53 | 0.702966E+09 | 478.51 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.462898E+10 | 3465.13 | 30-SEP-12:40 | 20.40 | 12.34 | 0.645492E+09 | 460.69 | 01-SEP-21:10 | 26.60 | 18.07 |
October | 0.434931E+10 | 3702.72 | 04-OCT-12:10 | 24.50 | 18.62 | 0.674598E+09 | 441.38 | 04-OCT-21:10 | 17.12 | 15.79 |
November | 0.195906E+10 | 3193.33 | 02-NOV-12:40 | 15.40 | 8.12 | 0.612823E+09 | 414.91 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 0.124418E+10 | 3718.02 | 03-DEC-11:36 | 7.23 | 2.91 | 0.627497E+09 | 370.74 | 04-DEC-23:19 | 8.13 | 7.50 |
Annual Sum or Average | 0.373301E+11 | 0.764051E+10 | ||||||||
Minimum of Months | 0.837648E+09 | 2153.81 | 7.23 | 2.91 | 0.566298E+09 | 364.14 | -13.4 | -14.8 | ||
Maximum of Months | 0.554905E+10 | 3718.02 | 31.47 | 25.92 | 0.702966E+09 | 478.51 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241931E+10 | 1879.15 | 18-JAN-07:10 | 8.40 | 8.15 | 0.765516E+09 | 524.29 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.224248E+10 | 1911.74 | 20-FEB-10:52 | 8.30 | 3.19 | 0.696555E+09 | 515.89 | 02-FEB-22:10 | -2.3 | -5.7 |
March | 0.277727E+10 | 1986.40 | 31-MAR-18:17 | 7.80 | 7.80 | 0.809495E+09 | 555.18 | 28-MAR-21:19 | 8.13 | 5.72 |
April | 0.292881E+10 | 1988.05 | 11-APR-22:27 | 7.75 | 1.07 | 0.793036E+09 | 569.93 | 11-APR-22:10 | 8.12 | 1.14 |
May | 0.341905E+10 | 1869.40 | 13-MAY-23:30 | 9.70 | 7.75 | 0.816739E+09 | 541.72 | 01-MAY-21:10 | 9.50 | 5.24 |
June | 0.378076E+10 | 1760.99 | 19-JUN-21:10 | 28.72 | 20.61 | 0.790091E+09 | 544.08 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.411201E+10 | 1782.41 | 10-JUL-21:10 | 27.12 | 20.10 | 0.825939E+09 | 551.00 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.417883E+10 | 1834.09 | 24-AUG-20:30 | 26.40 | 15.68 | 0.850464E+09 | 560.21 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.371839E+10 | 1814.51 | 30-SEP-00:42 | 10.68 | 9.43 | 0.798306E+09 | 552.91 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.349210E+10 | 2122.38 | 19-OCT-06:18 | 7.77 | 6.89 | 0.854413E+09 | 566.89 | 30-OCT-21:30 | 8.60 | 3.95 |
November | 0.274581E+10 | 2076.11 | 07-NOV-23:52 | 7.80 | 6.70 | 0.785523E+09 | 559.78 | 06-NOV-22:19 | 7.93 | 5.52 |
December | 0.260665E+10 | 2000.67 | 20-DEC-09:40 | 7.57 | 4.72 | 0.785052E+09 | 527.68 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.384215E+11 | 0.957113E+10 | ||||||||
Minimum of Months | 0.224248E+10 | 1760.99 | 7.57 | 1.07 | 0.696555E+09 | 515.89 | -2.3 | -5.7 | ||
Maximum of Months | 0.417883E+10 | 2122.38 | 28.72 | 20.61 | 0.854413E+09 | 569.93 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109509E+10 | 1522.51 | 24-JAN-09:06 | 9.60 | 9.60 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.945716E+09 | 984.74 | 20-FEB-10:48 | 8.12 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.183636E+10 | 1753.87 | 31-MAR-18:17 | 7.80 | 7.80 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.229717E+10 | 1671.68 | 11-APR-22:27 | 7.75 | 1.07 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.292897E+10 | 1606.91 | 13-MAY-23:30 | 9.70 | 7.75 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.338762E+10 | 1526.62 | 22-JUN-20:30 | 26.40 | 16.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.373720E+10 | 1568.33 | 10-JUL-21:10 | 27.12 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.375765E+10 | 1590.98 | 24-AUG-20:30 | 26.40 | 15.68 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.327232E+10 | 1529.97 | 01-SEP-21:00 | 26.70 | 18.21 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.292358E+10 | 1857.10 | 19-OCT-06:18 | 7.77 | 6.89 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.201583E+10 | 1813.44 | 08-NOV-07:42 | 7.52 | 6.77 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.153365E+10 | 1774.53 | 20-DEC-09:40 | 7.57 | 4.72 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.297311E+11 | 0.00 | ||||||||
Minimum of Months | 0.945716E+09 | 984.74 | 7.52 | 1.07 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.375765E+10 | 1857.10 | 27.12 | 20.10 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185375E+09 | 584.73 | 24-JAN-20:25 | 8.60 | 6.55 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.154580E+09 | 461.72 | 20-FEB-10:48 | 8.12 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.570721E+09 | 717.12 | 27-MAR-07:00 | 8.30 | 8.30 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.923670E+09 | 753.02 | 11-APR-22:27 | 7.75 | 1.07 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.132008E+10 | 741.05 | 16-MAY-01:10 | 9.32 | 6.69 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.157413E+10 | 692.57 | 19-JUN-21:10 | 28.72 | 20.61 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.174832E+10 | 714.30 | 10-JUL-21:10 | 27.12 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.175683E+10 | 725.89 | 04-AUG-21:10 | 31.55 | 23.91 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.151413E+10 | 700.25 | 24-SEP-05:13 | 10.40 | 8.70 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.133687E+10 | 847.15 | 19-OCT-06:18 | 7.77 | 6.89 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.737579E+09 | 826.27 | 08-NOV-07:42 | 7.52 | 6.77 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.336288E+09 | 479.66 | 03-DEC-11:36 | 7.23 | 2.91 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.121586E+11 | 0.00 | ||||||||
Minimum of Months | 0.154580E+09 | 461.72 | 7.23 | 1.07 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.175683E+10 | 847.15 | 31.55 | 23.91 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482697E+11 | 39654.61 | 23-JAN-20:34 | 10.00 | 10.00 | 0.568535E+09 | 401.08 | 23-JAN-22:30 | 10.60 | 10.26 |
February | 0.436129E+11 | 35990.08 | 17-FEB-21:00 | 1.10 | -0.7 | 0.513460E+09 | 396.50 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.496918E+11 | 40416.22 | 31-MAR-20:55 | 7.80 | 7.80 | 0.575221E+09 | 436.38 | 06-MAR-22:10 | 9.82 | 5.93 |
April | 0.489956E+11 | 40924.95 | 20-APR-19:55 | 8.90 | 7.00 | 0.551241E+09 | 493.70 | 17-APR-21:10 | 8.22 | 8.02 |
May | 0.521269E+11 | 39495.82 | 01-MAY-20:37 | 9.40 | 5.23 | 0.553134E+09 | 440.41 | 01-MAY-21:19 | 9.60 | 5.24 |
June | 0.516439E+11 | 38263.79 | 19-JUN-20:00 | 30.00 | 21.99 | 0.520354E+09 | 381.53 | 08-JUN-21:10 | 18.22 | 13.29 |
July | 0.538742E+11 | 38252.80 | 10-JUL-20:00 | 28.30 | 20.23 | 0.532291E+09 | 381.50 | 11-JUL-21:30 | 22.80 | 17.56 |
August | 0.542757E+11 | 38415.53 | 04-AUG-20:00 | 32.20 | 24.20 | 0.536635E+09 | 381.58 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.511871E+11 | 38145.59 | 14-SEP-19:30 | 26.65 | 17.01 | 0.523450E+09 | 381.70 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.518124E+11 | 41684.72 | 18-OCT-20:30 | 8.30 | 5.99 | 0.560246E+09 | 432.61 | 30-OCT-21:40 | 8.50 | 4.05 |
November | 0.482473E+11 | 40990.61 | 16-NOV-20:48 | 8.22 | 6.55 | 0.554688E+09 | 463.31 | 16-NOV-22:00 | 9.40 | 7.72 |
December | 0.487473E+11 | 40931.87 | 04-DEC-20:27 | 8.90 | 7.87 | 0.570980E+09 | 435.87 | 26-DEC-19:30 | 7.20 | 3.57 |
Annual Sum or Average | 0.602485E+12 | 0.656023E+10 | ||||||||
Minimum of Months | 0.436129E+11 | 35990.08 | 1.10 | -0.7 | 0.513460E+09 | 381.50 | 2.02 | 0.23 | ||
Maximum of Months | 0.542757E+11 | 41684.72 | 32.20 | 24.20 | 0.575221E+09 | 493.70 | 22.80 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128527E+11 | 13908.17 | 19-JAN-12:34 | 8.67 | 4.08 | 0.872865E+10 | 6185.06 | 23-JAN-23:19 | 10.40 | 10.17 |
February | 0.125579E+11 | 12916.72 | 19-FEB-12:06 | 7.88 | 4.16 | 0.797597E+10 | 5911.54 | 22-FEB-22:40 | 2.20 | -0.7 |
March | 0.157971E+11 | 14010.46 | 07-MAR-13:30 | 9.70 | 4.79 | 0.932635E+10 | 6461.01 | 15-MAR-21:19 | 9.63 | 3.16 |
April | 0.167355E+11 | 11311.87 | 11-APR-22:27 | 7.75 | 1.07 | 0.914546E+10 | 6665.13 | 11-APR-21:49 | 8.48 | 1.27 |
May | 0.198341E+11 | 10915.57 | 17-MAY-04:00 | 10.00 | 8.82 | 0.951680E+10 | 6412.40 | 03-MAY-04:10 | 11.70 | 9.65 |
June | 0.222754E+11 | 10898.38 | 19-JUN-21:20 | 28.53 | 20.49 | 0.930353E+10 | 6459.69 | 19-JUN-21:49 | 27.98 | 20.13 |
July | 0.245855E+11 | 10867.80 | 10-JUL-21:20 | 27.03 | 20.01 | 0.980203E+10 | 6459.69 | 10-JUL-21:49 | 26.78 | 19.71 |
August | 0.251975E+11 | 11793.05 | 04-AUG-21:10 | 31.55 | 23.91 | 0.101158E+11 | 6461.93 | 17-AUG-22:19 | 26.70 | 20.71 |
September | 0.225148E+11 | 13377.69 | 30-SEP-12:30 | 20.30 | 12.31 | 0.951926E+10 | 6462.03 | 01-SEP-22:19 | 26.10 | 17.20 |
October | 0.218868E+11 | 14944.38 | 08-OCT-11:13 | 9.80 | 4.63 | 0.101591E+11 | 6462.70 | 27-OCT-21:40 | 7.20 | 3.62 |
November | 0.159134E+11 | 13626.83 | 29-NOV-12:24 | 8.30 | 4.74 | 0.904293E+10 | 6453.17 | 06-NOV-22:30 | 7.75 | 5.44 |
December | 0.144681E+11 | 15882.99 | 03-DEC-11:36 | 7.23 | 2.91 | 0.897911E+10 | 6290.48 | 04-DEC-23:19 | 8.13 | 7.50 |
Annual Sum or Average | 0.224619E+12 | 0.111615E+12 | ||||||||
Minimum of Months | 0.125579E+11 | 10867.80 | 7.23 | 1.07 | 0.797597E+10 | 5911.54 | 2.20 | -0.7 | ||
Maximum of Months | 0.251975E+11 | 15882.99 | 31.55 | 23.91 | 0.101591E+11 | 6665.13 | 27.98 | 20.71 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540349E+11 | 38808.96 | 18-JAN-07:10 | 8.40 | 8.15 | 0.274912E+11 | 18761.02 | 23-JAN-23:19 | 10.40 | 10.17 |
February | 0.499520E+11 | 40076.74 | 20-FEB-10:52 | 8.30 | 3.19 | 0.250218E+11 | 18377.42 | 22-FEB-23:10 | 2.20 | -0.6 |
March | 0.596501E+11 | 40684.64 | 31-MAR-18:17 | 7.80 | 7.80 | 0.289676E+11 | 19185.69 | 03-MAR-22:19 | 10.40 | 6.33 |
April | 0.619730E+11 | 48293.36 | 11-APR-22:03 | 8.12 | 1.14 | 0.282320E+11 | 19898.45 | 11-APR-22:10 | 8.12 | 1.14 |
May | 0.713058E+11 | 38993.18 | 16-MAY-01:10 | 9.32 | 6.69 | 0.289537E+11 | 19166.55 | 01-MAY-21:40 | 9.80 | 5.25 |
June | 0.775931E+11 | 35735.93 | 19-JUN-21:10 | 28.72 | 20.61 | 0.277487E+11 | 18760.12 | 19-JUN-22:10 | 27.62 | 20.12 |
July | 0.839665E+11 | 36112.43 | 10-JUL-21:10 | 27.12 | 20.10 | 0.288802E+11 | 18956.64 | 10-JUL-22:10 | 26.52 | 19.57 |
August | 0.849435E+11 | 37121.94 | 04-AUG-21:10 | 31.55 | 23.91 | 0.295754E+11 | 19181.95 | 04-AUG-21:19 | 30.90 | 23.98 |
September | 0.768659E+11 | 43710.56 | 29-SEP-23:53 | 11.10 | 9.60 | 0.281343E+11 | 19183.22 | 29-SEP-21:19 | 13.30 | 10.90 |
October | 0.733891E+11 | 47761.26 | 27-OCT-21:30 | 7.20 | 3.62 | 0.302642E+11 | 19277.61 | 27-OCT-21:40 | 7.20 | 3.62 |
November | 0.593415E+11 | 43269.98 | 07-NOV-23:52 | 7.80 | 6.70 | 0.282285E+11 | 19185.76 | 06-NOV-22:19 | 7.93 | 5.52 |
December | 0.571500E+11 | 41594.02 | 20-DEC-09:40 | 7.57 | 4.72 | 0.282617E+11 | 18966.08 | 04-DEC-22:19 | 7.97 | 7.49 |
Annual Sum or Average | 0.810165E+12 | 0.339759E+12 | ||||||||
Minimum of Months | 0.499520E+11 | 35735.93 | 7.20 | 1.14 | 0.250218E+11 | 18377.42 | 2.20 | -0.6 | ||
Maximum of Months | 0.849435E+11 | 48293.36 | 31.55 | 23.91 | 0.302642E+11 | 19898.45 | 30.90 | 23.98 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65720758.46 | 2736.24 | 17-JAN-16:02 | 9.45 | 4.57 | 93527608.46 | 56.69 | 16-JAN-02:20 | -4.1 | -5.7 |
February | 82612663.14 | 2734.55 | 02-FEB-16:02 | 4.13 | -1.9 | 84967628.08 | 56.69 | 13-FEB-03:20 | -8.5 | -10.5 |
March | 0.263679E+09 | 2826.56 | 07-MAR-16:01 | 7.93 | 4.56 | 95595549.54 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.523183E+09 | 3006.06 | 10-APR-15:01 | 20.00 | 11.49 | 93252909.16 | 56.69 | 10-APR-21:10 | 12.93 | 6.24 |
May | 0.987411E+09 | 3069.32 | 31-MAY-15:02 | 25.82 | 19.49 | 97688274.90 | 56.69 | 10-MAY-21:19 | 17.77 | 11.43 |
June | 0.164248E+10 | 3099.26 | 26-JUN-15:02 | 27.02 | 19.73 | 95405644.38 | 56.70 | 22-JUN-21:30 | 25.55 | 16.07 |
July | 0.207788E+10 | 3109.01 | 13-JUL-15:02 | 30.32 | 24.43 | 98820912.27 | 56.70 | 06-JUL-21:40 | 25.60 | 23.63 |
August | 0.223264E+10 | 3129.22 | 04-AUG-15:02 | 31.02 | 25.37 | 98930179.37 | 56.70 | 01-AUG-21:30 | 26.10 | 22.18 |
September | 0.135335E+10 | 3096.53 | 07-SEP-15:02 | 26.60 | 22.96 | 94962334.46 | 56.70 | 01-SEP-21:19 | 26.50 | 17.93 |
October | 0.924351E+09 | 2930.12 | 02-OCT-15:02 | 22.88 | 16.76 | 97597782.62 | 56.69 | 05-OCT-22:49 | 19.32 | 18.42 |
November | 0.166830E+09 | 2821.24 | 02-NOV-15:01 | 16.60 | 8.89 | 91965794.68 | 56.69 | 02-NOV-21:40 | 12.07 | 6.86 |
December | 78025454.30 | 2698.18 | 17-DEC-16:02 | 9.82 | 4.15 | 93959349.38 | 56.69 | 04-DEC-23:49 | 7.88 | 7.49 |
Annual Sum or Average | 0.103982E+11 | 0.113667E+10 | ||||||||
Minimum of Months | 65720758.46 | 2698.18 | 4.13 | -1.9 | 84967628.08 | 56.69 | -8.5 | -10.5 | ||
Maximum of Months | 0.223264E+10 | 3129.22 | 31.02 | 25.37 | 98930179.37 | 56.70 | 26.50 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39374527.71 | 1574.18 | 17-JAN-16:02 | 9.45 | 4.57 | 92786903.06 | 56.69 | 03-JAN-00:30 | -3.9 | -6.5 |
February | 42347899.26 | 2438.83 | 20-FEB-16:02 | 7.12 | 4.39 | 83994406.28 | 56.69 | 08-FEB-05:19 | -6.5 | -8.3 |
March | 0.169287E+09 | 2723.35 | 07-MAR-16:01 | 7.93 | 4.56 | 94646215.53 | 56.69 | 27-MAR-21:30 | 13.60 | 10.45 |
April | 0.425927E+09 | 2947.17 | 10-APR-15:01 | 20.00 | 11.49 | 92811866.87 | 56.69 | 27-APR-21:10 | 14.40 | 13.08 |
May | 0.935139E+09 | 3052.17 | 31-MAY-15:02 | 25.82 | 19.49 | 97551227.27 | 56.69 | 31-MAY-00:30 | 18.35 | 16.25 |
June | 0.160480E+10 | 3077.36 | 26-JUN-15:02 | 27.02 | 19.73 | 95370692.72 | 56.70 | 22-JUN-21:30 | 25.55 | 16.07 |
July | 0.201949E+10 | 3060.09 | 13-JUL-15:02 | 30.32 | 24.43 | 98805302.74 | 56.70 | 06-JUL-21:40 | 25.60 | 23.63 |
August | 0.206145E+10 | 3076.18 | 01-AUG-15:02 | 30.50 | 22.66 | 98860953.07 | 56.70 | 17-AUG-21:30 | 27.50 | 21.04 |
September | 0.112769E+10 | 3034.94 | 06-SEP-15:02 | 26.02 | 20.14 | 94566015.35 | 56.69 | 14-SEP-21:10 | 24.13 | 17.20 |
October | 0.580672E+09 | 2915.65 | 04-OCT-15:02 | 23.72 | 19.11 | 96535084.42 | 56.69 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 88208536.22 | 2652.86 | 03-NOV-15:02 | 16.83 | 10.86 | 90982591.19 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 43892027.70 | 944.39 | 17-DEC-16:02 | 9.82 | 4.15 | 92901409.99 | 56.69 | 08-DEC-04:19 | 4.27 | 1.19 |
Annual Sum or Average | 0.913829E+10 | 0.112981E+10 | ||||||||
Minimum of Months | 39374527.71 | 944.39 | 7.12 | 4.15 | 83994406.28 | 56.69 | -6.5 | -8.3 | ||
Maximum of Months | 0.206145E+10 | 3077.36 | 30.50 | 24.43 | 98860953.07 | 56.70 | 27.50 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119349E+09 | 192.69 | 19-JAN-14:30 | 9.15 | 3.63 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.161732E+09 | 323.45 | 03-FEB-12:30 | -1.4 | -4.9 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.222149E+09 | 407.57 | 03-MAR-13:30 | 14.70 | 8.31 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.259579E+09 | 494.45 | 08-APR-12:30 | 23.60 | 16.17 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.335173E+09 | 419.29 | 30-MAY-16:40 | 26.50 | 18.20 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.489763E+09 | 469.24 | 26-JUN-15:30 | 26.65 | 19.49 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.692702E+09 | 529.34 | 21-JUL-18:00 | 26.70 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.760447E+09 | 524.75 | 30-AUG-12:30 | 26.95 | 15.10 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.581207E+09 | 644.40 | 30-SEP-12:30 | 20.30 | 12.31 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.585391E+09 | 701.33 | 04-OCT-12:00 | 24.40 | 18.64 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.277846E+09 | 609.90 | 02-NOV-12:30 | 15.30 | 8.09 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.197396E+09 | 503.71 | 17-DEC-13:00 | 12.20 | 4.93 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.468273E+10 | 0.00 | ||||||||
Minimum of Months | 0.119349E+09 | 192.69 | -1.4 | -4.9 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.760447E+09 | 701.33 | 26.95 | 22.65 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69209708.53 | 391.43 | 22-JAN-09:02 | 5.10 | 4.57 | 94090499.93 | 56.69 | 23-JAN-22:10 | 10.60 | 10.26 |
February | 57043607.49 | 469.02 | 20-FEB-09:02 | 5.87 | 1.95 | 84959795.64 | 56.69 | 23-FEB-22:10 | 4.50 | 3.57 |
March | 0.156347E+09 | 785.86 | 28-MAR-18:01 | 10.00 | 6.78 | 95206650.57 | 56.69 | 30-MAR-21:10 | 5.60 | 5.08 |
April | 0.316299E+09 | 862.48 | 08-APR-15:02 | 20.95 | 14.83 | 92881564.50 | 56.69 | 07-APR-22:10 | 18.22 | 13.38 |
May | 0.546769E+09 | 932.78 | 30-MAY-15:02 | 28.30 | 17.25 | 96933415.40 | 56.69 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.748237E+09 | 953.12 | 22-JUN-18:02 | 28.72 | 17.26 | 94448528.53 | 56.69 | 19-JUN-21:49 | 27.98 | 20.13 |
July | 0.929868E+09 | 959.81 | 10-JUL-18:02 | 29.82 | 20.53 | 98131219.39 | 57.87 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.877930E+09 | 962.12 | 24-AUG-18:02 | 30.82 | 18.14 | 98017968.63 | 56.69 | 17-AUG-21:30 | 27.50 | 21.04 |
September | 0.607941E+09 | 963.03 | 01-SEP-18:02 | 27.70 | 17.42 | 93797314.62 | 56.69 | 05-SEP-21:10 | 23.90 | 20.41 |
October | 0.378042E+09 | 844.83 | 02-OCT-18:02 | 20.82 | 15.40 | 96117148.33 | 56.69 | 06-OCT-21:10 | 13.30 | 8.55 |
November | 0.171880E+09 | 768.51 | 05-NOV-08:62 | 9.08 | 6.31 | 92104914.68 | 56.69 | 09-NOV-22:40 | 12.20 | 12.20 |
December | 74082127.65 | 499.21 | 25-DEC-09:02 | 10.50 | 10.21 | 94275512.97 | 56.69 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.493365E+10 | 0.113096E+10 | ||||||||
Minimum of Months | 57043607.49 | 391.43 | 5.10 | 1.95 | 84959795.64 | 56.69 | 4.50 | 2.50 | ||
Maximum of Months | 0.929868E+09 | 963.03 | 30.82 | 20.53 | 98131219.39 | 57.87 | 27.98 | 23.68 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73606822.08 | 2256.63 | 19-JAN-09:02 | 4.97 | 3.19 | 93523058.04 | 56.69 | 05-JAN-03:49 | -7.2 | -9.0 |
February | 88117269.06 | 2387.03 | 25-FEB-09:02 | -2.0 | -5.2 | 85062731.96 | 56.69 | 09-FEB-04:19 | -8.3 | -10.0 |
March | 0.235012E+09 | 2543.34 | 03-MAR-09:02 | 10.78 | 6.52 | 95625304.71 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.522261E+09 | 2684.61 | 10-APR-15:01 | 20.00 | 11.49 | 93488962.05 | 56.69 | 06-APR-21:30 | 16.40 | 13.46 |
May | 0.101620E+10 | 2771.58 | 29-MAY-08:61 | 24.27 | 16.70 | 97979888.75 | 56.69 | 31-MAY-00:30 | 18.35 | 16.25 |
June | 0.153236E+10 | 2799.66 | 01-JUN-15:02 | 29.32 | 16.60 | 95502894.40 | 56.70 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.203134E+10 | 2836.74 | 14-JUL-08:62 | 27.98 | 20.72 | 98959729.70 | 56.70 | 13-JUL-21:00 | 26.70 | 23.40 |
August | 0.219483E+10 | 2816.07 | 18-AUG-08:62 | 28.07 | 19.64 | 99128645.00 | 56.70 | 04-AUG-23:10 | 28.30 | 23.47 |
September | 0.135804E+10 | 2783.12 | 01-SEP-18:02 | 27.70 | 17.42 | 95139463.45 | 56.69 | 01-SEP-22:10 | 26.10 | 17.29 |
October | 0.874257E+09 | 2681.69 | 04-OCT-15:02 | 23.72 | 19.11 | 97810371.37 | 56.69 | 12-OCT-22:10 | 15.60 | 15.53 |
November | 0.203795E+09 | 2552.71 | 02-NOV-15:01 | 16.60 | 8.89 | 92171149.96 | 56.69 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 97900769.39 | 2398.20 | 17-DEC-09:02 | 6.05 | 2.93 | 94018980.83 | 56.69 | 23-DEC-00:20 | 3.17 | 2.67 |
Annual Sum or Average | 0.102277E+11 | 0.113841E+10 | ||||||||
Minimum of Months | 73606822.08 | 2256.63 | -2.0 | -5.2 | 85062731.96 | 56.69 | -8.3 | -10.0 | ||
Maximum of Months | 0.219483E+10 | 2836.74 | 29.32 | 20.72 | 99128645.00 | 56.70 | 28.30 | 23.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37798835.38 | 700.19 | 26-JAN-09:03 | 0.87 | -1.8 | 92791944.75 | 56.69 | 06-JAN-01:19 | -5.4 | -7.1 |
February | 42419581.73 | 2238.31 | 25-FEB-09:02 | -2.0 | -5.2 | 84065733.50 | 56.69 | 14-FEB-02:39 | -5.0 | -7.1 |
March | 0.147303E+09 | 2468.33 | 03-MAR-09:02 | 10.78 | 6.52 | 94629955.27 | 56.69 | 27-MAR-21:19 | 13.87 | 10.66 |
April | 0.425535E+09 | 2627.77 | 08-APR-15:02 | 20.95 | 14.83 | 93044784.45 | 56.69 | 10-APR-21:10 | 12.93 | 6.24 |
May | 0.962428E+09 | 2750.03 | 29-MAY-08:61 | 24.27 | 16.70 | 97863862.34 | 56.69 | 31-MAY-00:10 | 18.72 | 16.36 |
June | 0.149339E+10 | 2772.44 | 04-JUN-08:62 | 22.38 | 12.50 | 95475857.50 | 56.69 | 22-JUN-21:19 | 25.73 | 16.09 |
July | 0.197218E+10 | 2816.74 | 14-JUL-08:62 | 27.98 | 20.72 | 98944623.57 | 56.70 | 27-JUL-21:10 | 23.53 | 22.29 |
August | 0.201980E+10 | 2818.28 | 18-AUG-08:62 | 28.07 | 19.64 | 99094693.07 | 56.70 | 21-AUG-21:40 | 27.97 | 23.28 |
September | 0.112351E+10 | 2714.29 | 01-SEP-15:02 | 30.22 | 17.48 | 94848020.86 | 56.69 | 07-SEP-00:10 | 22.20 | 20.63 |
October | 0.528283E+09 | 2508.91 | 04-OCT-15:02 | 23.72 | 19.11 | 96677753.41 | 56.69 | 05-OCT-23:49 | 18.98 | 18.21 |
November | 0.107069E+09 | 1998.45 | 04-NOV-08:62 | 12.57 | 9.41 | 91184485.43 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 45969374.33 | 1158.69 | 17-DEC-09:02 | 6.05 | 2.93 | 92950978.68 | 56.69 | 15-DEC-04:19 | -2.8 | -5.1 |
Annual Sum or Average | 0.890569E+10 | 0.113157E+10 | ||||||||
Minimum of Months | 37798835.38 | 700.19 | -2.0 | -5.2 | 84065733.50 | 56.69 | -5.4 | -7.1 | ||
Maximum of Months | 0.201980E+10 | 2818.28 | 30.22 | 20.72 | 99094693.07 | 56.70 | 27.97 | 23.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303531E+09 | 1400.01 | 19-JAN-12:50 | 9.03 | 4.13 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.445769E+09 | 1351.36 | 20-FEB-10:48 | 8.12 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.120155E+10 | 1840.79 | 24-MAR-15:05 | 9.90 | 5.67 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.195470E+10 | 2118.97 | 11-APR-22:27 | 7.75 | 1.07 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.315029E+10 | 1842.15 | 30-MAY-19:20 | 21.13 | 15.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.413577E+10 | 1895.65 | 22-JUN-19:30 | 27.25 | 16.77 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.471784E+10 | 1927.73 | 11-JUL-18:30 | 25.80 | 16.55 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.479433E+10 | 1967.20 | 24-AUG-19:10 | 29.03 | 16.36 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.383854E+10 | 1893.86 | 30-SEP-00:42 | 10.68 | 9.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.321969E+10 | 2264.16 | 08-OCT-10:15 | 8.67 | 3.75 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.114923E+10 | 1931.17 | 06-NOV-22:39 | 7.57 | 5.35 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.535239E+09 | 1694.87 | 20-DEC-10:00 | 8.30 | 4.99 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.294465E+11 | 0.00 | ||||||||
Minimum of Months | 0.303531E+09 | 1351.36 | 7.57 | 1.07 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.479433E+10 | 2264.16 | 29.03 | 16.77 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53160792.29 | 2862.22 | 17-JAN-16:02 | 9.45 | 4.57 | 93145877.59 | 56.69 | 31-JAN-04:40 | -7.6 | -10.0 |
February | 74034847.02 | 2852.45 | 02-FEB-16:02 | 4.13 | -1.9 | 84620933.24 | 56.69 | 08-FEB-00:20 | -5.6 | -7.6 |
March | 0.263575E+09 | 2958.89 | 07-MAR-16:01 | 7.93 | 4.56 | 95345649.16 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.561954E+09 | 3150.33 | 10-APR-15:01 | 20.00 | 11.49 | 93171383.64 | 56.69 | 07-APR-23:49 | 17.30 | 13.10 |
May | 0.111083E+10 | 3184.50 | 27-MAY-15:02 | 21.70 | 11.92 | 97855195.05 | 56.70 | 03-MAY-02:09 | 12.92 | 8.50 |
June | 0.190468E+10 | 3246.86 | 15-JUN-15:02 | 26.52 | 22.44 | 95549565.74 | 56.70 | 19-JUN-22:00 | 26.70 | 20.62 |
July | 0.243036E+10 | 3241.96 | 06-JUL-18:02 | 27.85 | 24.19 | 98922382.10 | 56.70 | 03-JUL-21:10 | 25.00 | 20.65 |
August | 0.256991E+10 | 3273.29 | 15-AUG-18:02 | 26.42 | 20.40 | 99013370.30 | 56.70 | 03-AUG-22:10 | 25.50 | 24.62 |
September | 0.152397E+10 | 3180.62 | 01-SEP-18:02 | 27.70 | 17.42 | 95075149.09 | 56.70 | 01-SEP-21:49 | 26.20 | 17.52 |
October | 0.964461E+09 | 2989.50 | 30-OCT-15:01 | 16.52 | 8.25 | 97574619.97 | 56.70 | 11-OCT-01:30 | 13.05 | 13.05 |
November | 0.147352E+09 | 2949.16 | 02-NOV-15:01 | 16.60 | 8.89 | 91585440.68 | 56.69 | 03-NOV-23:40 | 13.13 | 10.60 |
December | 62606100.91 | 2838.41 | 17-DEC-16:02 | 9.82 | 4.15 | 93531328.28 | 56.69 | 31-DEC-03:20 | -0.8 | -3.4 |
Annual Sum or Average | 0.116669E+11 | 0.113539E+10 | ||||||||
Minimum of Months | 53160792.29 | 2838.41 | 4.13 | -1.9 | 84620933.24 | 56.69 | -7.6 | -10.0 | ||
Maximum of Months | 0.256991E+10 | 3273.29 | 27.85 | 24.19 | 99013370.30 | 56.70 | 26.70 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22988699.59 | 882.59 | 17-JAN-16:02 | 9.45 | 4.57 | 92530346.29 | 56.69 | 11-JAN-03:39 | -3.5 | -5.5 |
February | 29794272.60 | 2017.56 | 20-FEB-16:02 | 7.12 | 4.39 | 83745836.01 | 56.69 | 06-FEB-02:20 | -13.5 | -14.9 |
March | 0.158945E+09 | 2837.34 | 07-MAR-16:01 | 7.93 | 4.56 | 94365693.79 | 56.69 | 27-MAR-22:40 | 12.07 | 9.31 |
April | 0.452659E+09 | 3084.68 | 10-APR-15:01 | 20.00 | 11.49 | 92753409.28 | 56.69 | 27-APR-01:39 | 13.30 | 11.49 |
May | 0.105188E+10 | 3131.59 | 27-MAY-15:02 | 21.70 | 11.92 | 97751910.56 | 56.70 | 26-MAY-03:09 | 15.10 | 11.02 |
June | 0.186530E+10 | 3188.41 | 18-JUN-15:02 | 26.02 | 22.47 | 95538330.87 | 56.70 | 19-JUN-22:00 | 26.70 | 20.62 |
July | 0.236992E+10 | 3209.71 | 19-JUL-15:02 | 27.70 | 23.77 | 98917562.05 | 56.70 | 20-JUL-21:49 | 26.78 | 24.77 |
August | 0.238669E+10 | 3235.24 | 02-AUG-15:02 | 30.50 | 25.54 | 98957441.77 | 56.70 | 03-AUG-21:00 | 25.60 | 24.70 |
September | 0.126812E+10 | 3200.64 | 07-SEP-15:02 | 26.60 | 22.96 | 94782832.63 | 56.69 | 01-SEP-02:39 | 22.60 | 20.76 |
October | 0.590211E+09 | 3076.51 | 04-OCT-15:02 | 23.72 | 19.11 | 96540424.10 | 56.70 | 22-OCT-00:00 | 15.60 | 14.90 |
November | 72201930.95 | 2773.44 | 03-NOV-15:02 | 16.83 | 10.86 | 90624560.08 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 29534017.28 | 692.70 | 08-DEC-16:03 | 5.92 | 1.75 | 92551826.38 | 56.69 | 07-DEC-00:20 | -0.8 | -2.8 |
Annual Sum or Average | 0.102982E+11 | 0.112906E+10 | ||||||||
Minimum of Months | 22988699.59 | 692.70 | 5.92 | 1.75 | 83745836.01 | 56.69 | -13.5 | -14.9 | ||
Maximum of Months | 0.238669E+10 | 3235.24 | 30.50 | 25.54 | 98957441.77 | 56.70 | 26.78 | 24.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168319E+09 | 1365.88 | 17-JAN-16:02 | 9.45 | 4.57 | 95056719.20 | 56.69 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.210250E+09 | 1360.39 | 02-FEB-16:02 | 4.13 | -1.9 | 86674197.95 | 56.69 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.318729E+09 | 1374.02 | 15-MAR-15:02 | 14.90 | 6.01 | 96440066.79 | 56.69 | 03-MAR-22:00 | 10.00 | 6.11 |
April | 0.403277E+09 | 1444.75 | 10-APR-15:01 | 20.00 | 11.49 | 93652469.36 | 56.69 | 07-APR-22:30 | 18.05 | 13.32 |
May | 0.639358E+09 | 1489.42 | 31-MAY-15:02 | 25.82 | 19.49 | 97783377.62 | 56.69 | 22-MAY-21:19 | 15.40 | 13.04 |
June | 0.102117E+10 | 1489.84 | 23-JUN-15:02 | 27.88 | 19.52 | 95366164.99 | 56.70 | 19-JUN-21:19 | 28.53 | 20.49 |
July | 0.137933E+10 | 1498.86 | 17-JUL-15:02 | 29.72 | 20.95 | 98920162.67 | 56.70 | 28-JUL-21:10 | 24.40 | 21.22 |
August | 0.149407E+10 | 1511.48 | 11-AUG-15:02 | 27.70 | 22.99 | 99027506.76 | 56.70 | 22-AUG-21:10 | 25.40 | 15.35 |
September | 0.112051E+10 | 1511.04 | 07-SEP-15:02 | 26.60 | 22.96 | 95205319.18 | 56.70 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.102728E+10 | 1490.84 | 04-OCT-15:02 | 23.72 | 19.11 | 98144748.97 | 56.69 | 05-OCT-22:49 | 19.32 | 18.42 |
November | 0.350284E+09 | 1390.17 | 02-NOV-15:01 | 16.60 | 8.89 | 93550576.23 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 0.261526E+09 | 1360.92 | 17-DEC-16:02 | 9.82 | 4.15 | 95625416.20 | 56.69 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.839409E+10 | 0.114545E+10 | ||||||||
Minimum of Months | 0.168319E+09 | 1360.39 | 4.13 | -1.9 | 86674197.95 | 56.69 | 2.02 | 0.23 | ||
Maximum of Months | 0.149407E+10 | 1511.48 | 29.72 | 22.99 | 99027506.76 | 56.70 | 28.53 | 21.22 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313916E+11 | 22218.44 | 23-JAN-23:17 | 10.40 | 10.17 | 0.184479E+11 | 11931.41 | 23-JAN-23:19 | 10.40 | 10.17 |
February | 0.282569E+11 | 21705.83 | 19-FEB-10:41 | 8.03 | 4.73 | 0.166701E+11 | 11347.96 | 17-FEB-04:19 | 1.50 | -1.3 |
March | 0.339837E+11 | 24406.58 | 03-MAR-23:50 | 9.08 | 6.07 | 0.189135E+11 | 11810.98 | 28-MAR-21:19 | 8.13 | 5.72 |
April | 0.354152E+11 | 29425.54 | 11-APR-22:27 | 7.75 | 1.07 | 0.183148E+11 | 12906.52 | 11-APR-22:10 | 8.12 | 1.14 |
May | 0.400264E+11 | 23314.06 | 16-MAY-01:10 | 9.32 | 6.69 | 0.188801E+11 | 11862.81 | 17-MAY-01:49 | 10.68 | 9.43 |
June | 0.420039E+11 | 22455.89 | 19-JUN-21:10 | 28.72 | 20.61 | 0.182547E+11 | 11347.84 | 07-JUN-22:19 | 22.43 | 16.89 |
July | 0.449349E+11 | 22459.05 | 10-JUL-21:10 | 27.12 | 20.10 | 0.188430E+11 | 11347.81 | 05-JUL-22:19 | 22.20 | 21.37 |
August | 0.447647E+11 | 22832.41 | 04-AUG-21:10 | 31.55 | 23.91 | 0.189531E+11 | 11347.63 | 08-AUG-03:20 | 15.93 | 13.21 |
September | 0.402886E+11 | 24169.11 | 30-SEP-03:50 | 10.68 | 9.69 | 0.180887E+11 | 11528.68 | 30-SEP-00:00 | 10.60 | 9.39 |
October | 0.380393E+11 | 26183.05 | 18-OCT-22:04 | 7.70 | 5.66 | 0.187737E+11 | 11828.70 | 30-OCT-21:40 | 8.50 | 4.05 |
November | 0.328746E+11 | 28807.96 | 07-NOV-23:52 | 7.80 | 6.70 | 0.181482E+11 | 12240.20 | 27-NOV-23:40 | 8.50 | 5.97 |
December | 0.320629E+11 | 23925.24 | 04-DEC-23:31 | 7.97 | 7.49 | 0.186317E+11 | 11683.07 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.444043E+12 | 0.220919E+12 | ||||||||
Minimum of Months | 0.282569E+11 | 21705.83 | 7.70 | 1.07 | 0.166701E+11 | 11347.63 | 1.50 | -1.3 | ||
Maximum of Months | 0.449349E+11 | 29425.54 | 31.55 | 23.91 | 0.189531E+11 | 12906.52 | 22.43 | 21.37 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349002E+11 | 24269.71 | 23-JAN-23:17 | 10.40 | 10.17 | 0.187558E+11 | 12039.29 | 23-JAN-23:19 | 10.40 | 10.17 |
February | 0.313823E+11 | 24373.89 | 20-FEB-10:48 | 8.12 | 3.14 | 0.169497E+11 | 11348.02 | 13-FEB-00:20 | -7.4 | -9.7 |
March | 0.377873E+11 | 27028.71 | 31-MAR-18:17 | 7.80 | 7.80 | 0.191085E+11 | 12018.66 | 28-MAR-02:49 | 10.10 | 8.12 |
April | 0.391555E+11 | 31272.65 | 11-APR-22:27 | 7.75 | 1.07 | 0.184807E+11 | 13064.64 | 11-APR-21:49 | 8.48 | 1.27 |
May | 0.437976E+11 | 25362.55 | 16-MAY-01:10 | 9.32 | 6.69 | 0.190395E+11 | 11922.92 | 17-MAY-01:49 | 10.68 | 9.43 |
June | 0.453238E+11 | 24070.18 | 19-JUN-21:10 | 28.72 | 20.61 | 0.183923E+11 | 11347.85 | 07-JUN-22:19 | 22.43 | 16.89 |
July | 0.481681E+11 | 23888.25 | 07-JUL-22:00 | 28.30 | 24.27 | 0.189662E+11 | 11347.82 | 18-JUL-22:19 | 22.20 | 20.80 |
August | 0.479386E+11 | 24269.00 | 04-AUG-21:10 | 31.55 | 23.91 | 0.190610E+11 | 11347.65 | 08-AUG-03:20 | 15.93 | 13.21 |
September | 0.436065E+11 | 25453.20 | 30-SEP-03:50 | 10.68 | 9.69 | 0.182582E+11 | 11585.52 | 30-SEP-00:00 | 10.60 | 9.39 |
October | 0.416320E+11 | 28691.85 | 18-OCT-22:04 | 7.70 | 5.66 | 0.189351E+11 | 11903.83 | 27-OCT-21:40 | 7.20 | 3.62 |
November | 0.364966E+11 | 31848.20 | 07-NOV-23:52 | 7.80 | 6.70 | 0.183563E+11 | 12362.92 | 27-NOV-23:19 | 8.70 | 6.01 |
December | 0.357021E+11 | 25373.85 | 04-DEC-23:31 | 7.97 | 7.49 | 0.188734E+11 | 11791.81 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.485891E+12 | 0.223177E+12 | ||||||||
Minimum of Months | 0.313823E+11 | 23888.25 | 7.70 | 1.07 | 0.169497E+11 | 11347.65 | -7.4 | -9.7 | ||
Maximum of Months | 0.481681E+11 | 31848.20 | 31.55 | 24.27 | 0.191085E+11 | 13064.64 | 22.43 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490429E+11 | 34789.16 | 17-JAN-11:39 | 8.87 | 4.85 | 0.187898E+11 | 11358.22 | 21-JAN-18:00 | 7.20 | 6.67 |
February | 0.444654E+11 | 35660.18 | 20-FEB-10:52 | 8.30 | 3.19 | 0.169683E+11 | 11357.92 | 18-FEB-18:00 | 2.80 | 1.19 |
March | 0.515382E+11 | 32471.94 | 24-MAR-15:05 | 9.90 | 5.67 | 0.188225E+11 | 11491.88 | 25-MAR-17:49 | 7.30 | 7.02 |
April | 0.517616E+11 | 32580.01 | 15-APR-18:10 | 9.40 | 9.40 | 0.182184E+11 | 11485.48 | 03-APR-17:40 | 7.07 | 3.70 |
May | 0.559917E+11 | 30336.77 | 29-MAY-10:40 | 27.43 | 17.90 | 0.187998E+11 | 11352.25 | 13-MAY-17:00 | 12.80 | 8.06 |
June | 0.561368E+11 | 30992.25 | 01-JUN-18:07 | 27.70 | 16.08 | 0.181538E+11 | 11319.62 | 17-JUN-17:19 | 22.60 | 20.38 |
July | 0.591418E+11 | 30680.13 | 08-JUL-10:50 | 30.82 | 25.25 | 0.187422E+11 | 11319.66 | 01-JUL-17:19 | 22.60 | 19.99 |
August | 0.593538E+11 | 31921.56 | 25-AUG-17:06 | 26.52 | 14.93 | 0.187546E+11 | 11319.63 | 19-AUG-17:19 | 24.43 | 18.16 |
September | 0.551416E+11 | 30282.61 | 04-SEP-10:50 | 25.60 | 17.63 | 0.181591E+11 | 11319.61 | 30-SEP-17:19 | 17.77 | 12.97 |
October | 0.546869E+11 | 30840.63 | 08-OCT-10:15 | 8.67 | 3.75 | 0.188050E+11 | 11425.19 | 07-OCT-17:40 | 10.97 | 4.70 |
November | 0.496156E+11 | 32190.75 | 05-NOV-20:02 | 7.80 | 4.81 | 0.182098E+11 | 11458.50 | 16-NOV-18:30 | 8.30 | 5.12 |
December | 0.497449E+11 | 31707.91 | 25-DEC-16:08 | 9.40 | 7.15 | 0.187993E+11 | 11360.57 | 16-DEC-18:00 | 6.70 | 2.69 |
Annual Sum or Average | 0.636621E+12 | 0.221223E+12 | ||||||||
Minimum of Months | 0.444654E+11 | 30282.61 | 7.80 | 3.19 | 0.169683E+11 | 11319.61 | 2.80 | 1.19 | ||
Maximum of Months | 0.593538E+11 | 35660.18 | 30.82 | 25.25 | 0.188225E+11 | 11491.88 | 24.43 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143865E+10 | 4472.80 | 17-JAN-11:39 | 8.87 | 4.85 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.153274E+10 | 3331.33 | 20-FEB-10:52 | 8.30 | 3.19 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.389305E+10 | 4027.12 | 24-MAR-15:05 | 9.90 | 5.67 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.568101E+10 | 4686.40 | 14-APR-16:50 | 8.40 | 5.43 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.812980E+10 | 4361.73 | 13-MAY-23:30 | 9.70 | 7.75 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.986042E+10 | 4450.18 | 19-JUN-14:40 | 33.67 | 23.40 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.110080E+11 | 4588.29 | 10-JUL-14:00 | 32.80 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.110140E+11 | 4597.60 | 18-AUG-13:40 | 33.30 | 20.44 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.919743E+10 | 4438.31 | 01-SEP-13:40 | 30.93 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.764839E+10 | 4739.33 | 08-OCT-10:15 | 8.67 | 3.75 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.382177E+10 | 4855.83 | 29-NOV-12:02 | 8.30 | 4.68 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.201077E+10 | 4773.18 | 16-DEC-12:13 | 8.17 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.752360E+11 | 0.00 | ||||||||
Minimum of Months | 0.143865E+10 | 3331.33 | 8.17 | 3.13 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.110140E+11 | 4855.83 | 33.67 | 23.40 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692611E+09 | 1523.31 | 02-JAN-07:20 | -11.5 |
February | 0.534588E+09 | 1523.36 | 06-FEB-07:15 | -13.1 |
March | 0.117841E+09 | 685.32 | 18-MAR-06:30 | -1.7 |
April | 16698752.71 | 731.62 | 06-APR-05:26 | 9.70 |
May | 25461.59 | 163.03 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 86202.66 | 352.59 | 18-OCT-22:20 | 7.60 |
November | 78661820.82 | 762.20 | 23-NOV-05:50 | -3.9 |
December | 0.323561E+09 | 834.80 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 0.176407E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.692611E+09 | 1523.36 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32992.94 | 85.01 | 03-JAN-09:10 | 8.58 |
February | 5934.71 | 29.67 | 16-FEB-12:20 | 8.30 |
March | 3247.90 | 27.07 | 11-MAR-11:04 | 8.68 |
April | 20625.12 | 30.04 | 20-APR-14:35 | 8.50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 23603.03 | 120.33 | 29-OCT-08:52 | 7.80 |
November | 50814.39 | 92.02 | 07-NOV-08:17 | 7.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 137218.09 | |||
Minimum of Months | 0.00 | 0.00 | 5.97 | |
Maximum of Months | 50814.39 | 120.33 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39382352.72 | 489.42 | 02-JAN-05:00 | -12.2 |
February | 50333763.47 | 456.40 | 06-FEB-05:00 | -13.3 |
March | 190948.76 | 145.95 | 11-MAR-11:04 | 8.68 |
April | 303541.12 | 114.92 | 03-APR-16:12 | 8.53 |
May | 7147.14 | 74.38 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 114458.82 | 274.38 | 29-OCT-08:52 | 7.80 |
November | 424767.77 | 232.41 | 07-NOV-08:17 | 7.57 |
December | 147327.47 | 88.42 | 17-DEC-18:27 | 8.05 |
Annual Sum or Average | 90904307.28 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 50333763.47 | 489.42 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204558E+09 | 489.87 | 02-JAN-05:00 | -12.2 |
February | 0.203201E+09 | 470.18 | 06-FEB-05:00 | -13.3 |
March | 13250376.48 | 136.81 | 23-MAR-04:00 | -5.0 |
April | 214332.25 | 55.39 | 03-APR-16:12 | 8.53 |
May | 7506.65 | 53.97 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 78484.99 | 151.19 | 29-OCT-08:52 | 7.80 |
November | 13327653.72 | 173.17 | 24-NOV-05:00 | -3.9 |
December | 32161896.45 | 235.14 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.466799E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.204558E+09 | 489.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27767083.96 | 1104.72 | 14-JAN-17:00 | -6.1 |
February | 466337.08 | 277.53 | 06-FEB-07:10 | -13.2 |
March | 55899.84 | 339.02 | 31-MAR-17:18 | 7.80 |
April | 173767.95 | 346.11 | 04-APR-08:21 | 8.30 |
May | 8136.33 | 122.06 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 273337.97 | 416.29 | 28-NOV-17:41 | 8.40 |
December | 21084.87 | 31.95 | 11-DEC-15:00 | 1.10 |
Annual Sum or Average | 28765647.99 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 27767083.96 | 1104.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 159431.88 | 1358.25 | 03-JAN-09:10 | 8.58 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 126775.86 | 591.41 | 28-NOV-12:37 | 8.67 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 286207.73 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 159431.88 | 1358.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107863E+10 | 1665.19 | 14-JAN-16:13 | -6.1 |
February | 0.890573E+09 | 1653.15 | 06-FEB-19:02 | -8.2 |
March | 0.402702E+09 | 1585.31 | 17-MAR-08:62 | -1.1 |
April | 0.167331E+09 | 1495.62 | 21-APR-15:02 | 7.30 |
May | 8924458.13 | 877.37 | 29-MAY-08:04 | 24.27 |
June | 869707.93 | 704.61 | 11-JUN-15:04 | 18.90 |
July | 937058.38 | 698.18 | 02-JUL-08:05 | 24.60 |
August | 728152.85 | 543.67 | 19-AUG-08:05 | 22.30 |
September | 2349418.87 | 718.77 | 30-SEP-08:03 | 14.18 |
October | 33246786.55 | 1319.98 | 31-OCT-15:02 | 13.30 |
November | 0.456321E+09 | 1570.08 | 25-NOV-09:02 | -0.3 |
December | 0.831988E+09 | 1629.54 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.387460E+10 | |||
Minimum of Months | 728152.85 | 543.67 | -8.2 | |
Maximum of Months | 0.107863E+10 | 1665.19 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129366E+10 | 1663.65 | 02-JAN-09:02 | -10.3 |
February | 0.115038E+10 | 1660.75 | 06-FEB-09:13 | -11.8 |
March | 0.517876E+09 | 1584.03 | 17-MAR-08:62 | -1.1 |
April | 0.194321E+09 | 1494.06 | 21-APR-15:02 | 7.30 |
May | 9857150.38 | 934.55 | 29-MAY-08:04 | 24.27 |
June | 922234.18 | 712.43 | 11-JUN-15:04 | 18.90 |
July | 914301.19 | 691.43 | 29-JUL-08:05 | 24.08 |
August | 728066.73 | 595.38 | 22-AUG-08:05 | 26.88 |
September | 2346258.70 | 603.54 | 25-SEP-15:03 | 18.03 |
October | 68477224.86 | 1453.49 | 29-OCT-08:62 | 6.88 |
November | 0.607263E+09 | 1595.56 | 24-NOV-09:02 | -1.5 |
December | 0.106085E+10 | 1635.07 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.490760E+10 | |||
Minimum of Months | 728066.73 | 595.38 | -11.8 | |
Maximum of Months | 0.129366E+10 | 1663.65 | 26.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51210651.89 | 199.57 | 02-JAN-05:10 | -12.1 |
February | 10715252.31 | 143.08 | 07-FEB-06:00 | -9.4 |
March | 1294842.19 | 71.76 | 01-MAR-06:00 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 1127.69 | 0.81 | 29-NOV-05:10 | 3.90 |
December | 13830351.99 | 135.32 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 77052226.07 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 51210651.89 | 199.57 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155418E+09 | 468.39 | 02-JAN-16:02 | -6.0 |
February | 0.157280E+09 | 469.97 | 06-FEB-16:02 | -7.1 |
March | 26094745.10 | 437.03 | 16-MAR-15:02 | 0.68 |
April | 1084168.37 | 403.06 | 01-APR-15:02 | 6.28 |
May | 588068.68 | 389.68 | 03-MAY-15:07 | 15.92 |
June | 86403.85 | 277.56 | 06-JUN-15:05 | 18.98 |
July | 49230.05 | 117.07 | 12-JUL-08:07 | 26.28 |
August | 84006.53 | 201.26 | 30-AUG-08:05 | 22.30 |
September | 260153.30 | 198.71 | 24-SEP-15:05 | 17.70 |
October | 917112.53 | 332.31 | 21-OCT-18:03 | 17.12 |
November | 33212287.20 | 440.17 | 22-NOV-16:02 | 0.60 |
December | 88436027.44 | 454.54 | 31-DEC-16:02 | -3.1 |
Annual Sum or Average | 0.463511E+09 | |||
Minimum of Months | 49230.05 | 117.07 | -7.1 | |
Maximum of Months | 0.157280E+09 | 469.97 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107194E+10 | 1604.02 | 14-JAN-16:13 | -6.1 |
February | 0.867075E+09 | 1589.71 | 06-FEB-19:02 | -8.2 |
March | 0.424789E+09 | 1526.93 | 17-MAR-08:62 | -1.1 |
April | 0.168304E+09 | 1448.13 | 01-APR-15:02 | 6.28 |
May | 9600147.29 | 705.72 | 04-MAY-08:63 | 11.20 |
June | 393819.91 | 480.08 | 06-JUN-15:05 | 18.98 |
July | 88758.54 | 522.61 | 31-JUL-08:05 | 25.68 |
August | 73777.38 | 528.93 | 06-AUG-08:05 | 22.12 |
September | 1450514.53 | 501.23 | 23-SEP-08:04 | 13.30 |
October | 35639619.31 | 1159.04 | 31-OCT-15:02 | 13.30 |
November | 0.428919E+09 | 1514.00 | 25-NOV-09:02 | -0.3 |
December | 0.821216E+09 | 1575.05 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.382949E+10 | |||
Minimum of Months | 73777.38 | 480.08 | -8.2 | |
Maximum of Months | 0.107194E+10 | 1604.02 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128127E+10 | 1604.48 | 14-JAN-16:13 | -6.1 |
February | 0.111858E+10 | 1598.48 | 06-FEB-19:02 | -8.2 |
March | 0.545940E+09 | 1528.94 | 17-MAR-08:62 | -1.1 |
April | 0.196425E+09 | 1452.72 | 01-APR-15:02 | 6.28 |
May | 11261098.81 | 839.05 | 02-MAY-15:04 | 16.88 |
June | 421009.36 | 446.53 | 06-JUN-15:05 | 18.98 |
July | 101134.34 | 549.33 | 31-JUL-08:05 | 25.68 |
August | 86155.58 | 422.03 | 06-AUG-08:05 | 22.12 |
September | 2074148.14 | 530.38 | 17-SEP-15:04 | 20.28 |
October | 71164873.74 | 1350.48 | 31-OCT-08:62 | 7.38 |
November | 0.558290E+09 | 1532.60 | 23-NOV-19:02 | -0.7 |
December | 0.103324E+10 | 1582.76 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.481885E+10 | |||
Minimum of Months | 86155.58 | 422.03 | -8.2 | |
Maximum of Months | 0.128127E+10 | 1604.48 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.735110E+09 | 960.97 | 02-JAN-05:00 | -12.2 |
February | 0.558703E+09 | 960.91 | 06-FEB-05:00 | -13.3 |
March | 0.139288E+09 | 608.25 | 17-MAR-04:00 | -1.7 |
April | 31065254.04 | 759.92 | 06-APR-05:26 | 9.70 |
May | 51583.77 | 163.11 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 371603.43 | 465.99 | 29-OCT-08:52 | 7.80 |
November | 0.150473E+09 | 689.08 | 24-NOV-05:00 | -3.9 |
December | 0.439028E+09 | 703.34 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 0.205409E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.735110E+09 | 960.97 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152741E+10 | 1946.23 | 14-JAN-16:13 | -6.1 |
February | 0.128336E+10 | 1922.65 | 06-FEB-19:13 | -8.1 |
March | 0.626216E+09 | 1831.71 | 17-MAR-08:62 | -1.1 |
April | 0.278433E+09 | 1739.27 | 21-APR-15:02 | 7.30 |
May | 20976816.47 | 1045.28 | 01-MAY-08:62 | 12.48 |
June | 501338.19 | 524.13 | 26-JUN-08:05 | 24.08 |
July | 631769.57 | 639.95 | 01-JUL-08:05 | 24.18 |
August | 548894.55 | 522.96 | 19-AUG-08:05 | 22.30 |
September | 3337680.11 | 642.91 | 25-SEP-15:04 | 18.03 |
October | 73920282.72 | 1660.39 | 29-OCT-08:62 | 6.88 |
November | 0.706091E+09 | 1825.35 | 25-NOV-09:02 | -0.3 |
December | 0.122301E+10 | 1884.90 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.574443E+10 | |||
Minimum of Months | 501338.19 | 522.96 | -8.1 | |
Maximum of Months | 0.152741E+10 | 1946.23 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179419E+10 | 1942.81 | 14-JAN-16:13 | -6.1 |
February | 0.160111E+10 | 1940.12 | 06-FEB-09:13 | -11.8 |
March | 0.777066E+09 | 1832.85 | 22-MAR-08:62 | -2.0 |
April | 0.316269E+09 | 1738.30 | 03-APR-08:62 | 5.68 |
May | 23276516.13 | 1139.28 | 01-MAY-08:62 | 12.48 |
June | 519596.07 | 504.57 | 26-JUN-08:05 | 24.08 |
July | 603495.35 | 660.27 | 01-JUL-08:05 | 24.18 |
August | 510570.02 | 510.86 | 19-AUG-08:05 | 22.30 |
September | 4144505.43 | 649.62 | 23-SEP-15:05 | 16.60 |
October | 0.135389E+09 | 1701.66 | 29-OCT-08:62 | 6.88 |
November | 0.909534E+09 | 1842.25 | 24-NOV-09:02 | -1.5 |
December | 0.151461E+10 | 1895.06 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.707722E+10 | |||
Minimum of Months | 510570.02 | 504.57 | -11.8 | |
Maximum of Months | 0.179419E+10 | 1942.81 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443651E+09 | 945.04 | 14-JAN-16:13 | -6.1 |
February | 0.318633E+09 | 917.74 | 06-FEB-19:02 | -8.2 |
March | 0.151974E+09 | 894.89 | 16-MAR-15:02 | 0.68 |
April | 63514362.49 | 847.44 | 21-APR-15:02 | 7.30 |
May | 1967794.79 | 401.60 | 02-MAY-18:05 | 14.72 |
June | 194565.16 | 325.64 | 06-JUN-15:05 | 18.98 |
July | 94268.01 | 194.81 | 15-JUL-08:06 | 20.60 |
August | 167959.47 | 326.37 | 09-AUG-08:05 | 24.27 |
September | 220230.93 | 340.77 | 03-SEP-08:05 | 21.38 |
October | 3378589.05 | 227.80 | 29-OCT-08:04 | 6.88 |
November | 0.121565E+09 | 862.68 | 25-NOV-09:02 | -0.3 |
December | 0.304345E+09 | 892.29 | 27-DEC-16:02 | 1.75 |
Annual Sum or Average | 0.140971E+10 | |||
Minimum of Months | 94268.01 | 194.81 | -8.2 | |
Maximum of Months | 0.443651E+09 | 945.04 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.982799E+09 | 2847.76 | 02-JAN-05:10 | -12.1 |
February | 0.871949E+09 | 2840.24 | 06-FEB-05:00 | -13.3 |
March | 0.114334E+09 | 1201.48 | 23-MAR-05:00 | -5.0 |
April | 3198367.16 | 1063.06 | 06-APR-05:26 | 9.70 |
May | 56200.73 | 318.01 | 01-MAY-06:12 | 8.13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 489510.24 | 848.29 | 29-OCT-08:52 | 7.80 |
November | 0.132363E+09 | 1335.24 | 23-NOV-06:00 | -3.9 |
December | 0.314526E+09 | 1188.53 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.241972E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.982799E+09 | 2847.76 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.144724E+11 | 13939.86 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.130672E+11 | 13939.86 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.145225E+11 | 13939.86 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.139817E+11 | 13939.86 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.144975E+11 | 13939.86 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.140458E+11 | 13939.86 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.144333E+11 | 13939.86 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.145225E+11 | 13939.86 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.139817E+11 | 13939.86 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.144724E+11 | 13939.86 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.140346E+11 | 13939.86 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.144333E+11 | 13939.86 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.170465E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.130672E+11 | 13939.86 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.145225E+11 | 13939.86 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.764969E+09 | 736.82 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.690697E+09 | 736.82 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.767621E+09 | 736.82 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.739033E+09 | 736.82 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.766295E+09 | 736.82 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.742422E+09 | 736.82 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.762906E+09 | 736.82 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.767621E+09 | 736.82 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.739033E+09 | 736.82 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.764969E+09 | 736.82 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.741833E+09 | 736.82 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.762906E+09 | 736.82 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.901031E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.690697E+09 | 736.82 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.767621E+09 | 736.82 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.885837E+09 | 853.24 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.799830E+09 | 853.24 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.888909E+09 | 853.24 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.855803E+09 | 853.24 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.887373E+09 | 853.24 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.859728E+09 | 853.24 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.883448E+09 | 853.24 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.888909E+09 | 853.24 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.855803E+09 | 853.24 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.885837E+09 | 853.24 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.859045E+09 | 853.24 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.883448E+09 | 853.24 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.104340E+11 | 0.117953E+11 | ||||
Minimum of Months | 0.799830E+09 | 853.24 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.888909E+09 | 853.24 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.141237E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141726E+10 | 1360.40 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140856E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136448E+10 | 1360.40 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141237E+10 | 1360.40 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140856E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166358E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280997E+09 | 270.66 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.253715E+09 | 270.66 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.281971E+09 | 270.66 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.271470E+09 | 270.66 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.281484E+09 | 270.66 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.272715E+09 | 270.66 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.280239E+09 | 270.66 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.281971E+09 | 270.66 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.271470E+09 | 270.66 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.280997E+09 | 270.66 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.272498E+09 | 270.66 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.280239E+09 | 270.66 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.330977E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.253715E+09 | 270.66 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.281971E+09 | 270.66 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.423840E+09 | 408.24 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.382689E+09 | 408.24 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.425309E+09 | 408.24 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.409470E+09 | 408.24 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.424575E+09 | 408.24 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.411347E+09 | 408.24 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.422697E+09 | 408.24 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.425309E+09 | 408.24 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.409470E+09 | 408.24 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.423840E+09 | 408.24 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.411021E+09 | 408.24 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.422697E+09 | 408.24 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.499226E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.382689E+09 | 408.24 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.425309E+09 | 408.24 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161485E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.142581E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154497E+10 | 1761.91 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.144251E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.143969E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.137213E+10 | 1761.91 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.141436E+10 | 1761.91 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.147542E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.146934E+10 | 1761.91 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.157215E+10 | 1761.91 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.154686E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.160913E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.179272E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.137213E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.161485E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.122961E+11 | 12090.12 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.110622E+11 | 12090.12 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.122472E+11 | 12090.12 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.117416E+11 | 12090.12 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.121070E+11 | 12090.12 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.117060E+11 | 12090.12 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.120347E+11 | 12090.12 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.121655E+11 | 12090.12 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.117719E+11 | 12090.12 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122427E+11 | 12090.12 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.118991E+11 | 12090.12 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122602E+11 | 12090.12 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.143534E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.110622E+11 | 12090.12 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.122961E+11 | 12090.12 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75964402.59 | 89.33 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 68608505.50 | 89.33 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 75685198.85 | 89.33 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 73558970.85 | 89.33 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 75824800.72 | 89.33 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 73279767.11 | 89.33 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 76104004.46 | 89.33 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 75685198.85 | 89.33 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 73558970.85 | 89.33 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 75964402.59 | 89.33 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 73419368.98 | 89.33 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 76104004.46 | 89.33 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.893758E+09 | 0.300992E+10 | ||||
Minimum of Months | 68608505.50 | 89.33 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 76104004.46 | 89.33 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75985174.92 | 89.35 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 68627266.37 | 89.35 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 75705894.83 | 89.35 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 73579085.42 | 89.35 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 75845534.87 | 89.35 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 73299805.33 | 89.35 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 76124814.96 | 89.35 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 75705894.83 | 89.35 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 73579085.42 | 89.35 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 75985174.92 | 89.35 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 73439445.37 | 89.35 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 76124814.96 | 89.35 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.894002E+09 | 0.301074E+10 | ||||
Minimum of Months | 68627266.37 | 89.35 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 76124814.96 | 89.35 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.232638E+10 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233445E+10 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224751E+10 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233042E+10 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224751E+10 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232638E+10 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274017E+11 | ||||
Minimum of Months | 0.210051E+10 | 2240.79 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.79 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120874E+09 | 142.14 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.109169E+09 | 142.14 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.120429E+09 | 142.14 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.117046E+09 | 142.14 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.120651E+09 | 142.14 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.116602E+09 | 142.14 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.121096E+09 | 142.14 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.120429E+09 | 142.14 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.117046E+09 | 142.14 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.120874E+09 | 142.14 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.116824E+09 | 142.14 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.121096E+09 | 142.14 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.142214E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.109169E+09 | 142.14 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.121096E+09 | 142.14 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120859E+09 | 142.12 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.109156E+09 | 142.12 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.120415E+09 | 142.12 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.117032E+09 | 142.12 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.120637E+09 | 142.12 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.116588E+09 | 142.12 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.121082E+09 | 142.12 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.120415E+09 | 142.12 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.117032E+09 | 142.12 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.120859E+09 | 142.12 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.116810E+09 | 142.12 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.121082E+09 | 142.12 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.142197E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.109156E+09 | 142.12 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.121082E+09 | 142.12 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 75985174.92 | 89.35 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 68627266.37 | 89.35 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 75705894.83 | 89.35 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 73579085.42 | 89.35 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 75845534.87 | 89.35 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 73299805.33 | 89.35 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 76124814.96 | 89.35 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 75705894.83 | 89.35 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 73579085.42 | 89.35 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 75985174.92 | 89.35 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 73439445.37 | 89.35 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 76124814.96 | 89.35 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.894002E+09 | 0.301074E+10 | ||||
Minimum of Months | 68627266.37 | 89.35 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 76124814.96 | 89.35 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303438E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270892E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296991E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281203E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285840E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.274883E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282922E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289614E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283920E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.298998E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.292073E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302987E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346376E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270892E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303438E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303438E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270892E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296991E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281203E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285840E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.274883E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282922E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289614E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283920E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.298998E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.292073E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302987E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346376E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270892E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303438E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113539E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113343E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109310E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113146E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133271E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.246212E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222307E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.247065E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246639E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238955E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245548E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237864E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246212E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245548E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290004E+11 | ||||
Minimum of Months | 0.222307E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.144724E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.130672E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.139817E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.144975E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.140458E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.144333E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.139817E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.144724E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.140346E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.144333E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.170465E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.130672E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.145225E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.764969E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135858E+10 |
February | 0.179968E+10 | 0.690697E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130926E+10 |
March | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61088.32 | 0.104936E+10 |
April | 0.192973E+10 | 0.739033E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1984436.44 | 0.657030E+09 |
May | 0.199475E+10 | 0.766295E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16096285.39 | 0.349763E+09 |
June | 0.193394E+10 | 0.742422E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83681380.23 | 71347432.25 |
July | 0.199054E+10 | 0.762906E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198452E+09 | 3697254.80 |
August | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176996E+09 | 24072700.93 |
September | 0.192973E+10 | 0.739033E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36439110.07 | 0.153961E+09 |
October | 0.199054E+10 | 0.764969E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 584987.85 | 0.523916E+09 |
November | 0.192552E+10 | 0.741833E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898405E+09 |
December | 0.199054E+10 | 0.762906E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119184E+10 |
Annual Sum or Average | 0.234734E+11 | 0.901031E+10 | 0.101859E+11 | 0.514295E+09 | 0.759123E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.690697E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3697254.80 |
Maximum of Months | 0.199896E+10 | 0.767621E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198452E+09 | 0.135858E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.885837E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289698E+09 |
February | 0.208403E+10 | 0.799830E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278841E+09 |
March | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8737.25 | 0.228992E+09 |
April | 0.223463E+10 | 0.855803E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702192.10 | 0.148702E+09 |
May | 0.230993E+10 | 0.887373E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3665214.37 | 84292944.42 |
June | 0.223950E+10 | 0.859728E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17152696.36 | 21412033.23 |
July | 0.230505E+10 | 0.883448E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39254125.28 | 2217162.40 |
August | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38470417.87 | 8233492.50 |
September | 0.223463E+10 | 0.855803E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8767491.88 | 37536408.10 |
October | 0.230505E+10 | 0.885837E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 618392.88 | 0.116861E+09 |
November | 0.222975E+10 | 0.859045E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197535E+09 |
December | 0.230505E+10 | 0.883448E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256622E+09 |
Annual Sum or Average | 0.271823E+11 | 0.104340E+11 | 0.117953E+11 | 0.108639E+09 | 0.167094E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.799830E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2217162.40 |
Maximum of Months | 0.231480E+10 | 0.888909E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39254125.28 | 0.289698E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.423840E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939499E+09 |
February | 0.139600E+10 | 0.382689E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898327E+09 |
March | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50973.77 | 0.735968E+09 |
April | 0.149688E+10 | 0.409470E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2568667.39 | 0.477676E+09 |
May | 0.154732E+10 | 0.424575E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 11932437.76 | 0.266532E+09 |
June | 0.150015E+10 | 0.411347E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 57389657.59 | 65801432.61 |
July | 0.154405E+10 | 0.422697E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.135116E+09 | 6872031.58 |
August | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.136592E+09 | 21243844.02 |
September | 0.149688E+10 | 0.409470E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 34022756.68 | 0.115327E+09 |
October | 0.154405E+10 | 0.423840E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 3835594.75 | 0.354553E+09 |
November | 0.149361E+10 | 0.411021E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633947E+09 |
December | 0.154405E+10 | 0.422697E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828988E+09 |
Annual Sum or Average | 0.182082E+11 | 0.499226E+10 | 0.679373E+11 | 0.590211E+12 | 0.381508E+09 | 0.534473E+10 | |||
Minimum of Months | 0.139600E+10 | 0.382689E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6872031.58 |
Maximum of Months | 0.155059E+10 | 0.425309E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.136592E+09 | 0.939499E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.161485E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350359E+10 |
February | 0.236489E+11 | 0.142581E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338339E+10 |
March | 0.262677E+11 | 0.154497E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15664.28 | 0.278396E+10 |
April | 0.253579E+11 | 0.144251E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4518836.18 | 0.180313E+10 |
May | 0.262123E+11 | 0.143969E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37523299.89 | 0.103521E+10 |
June | 0.254132E+11 | 0.137213E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187581E+09 | 0.280727E+09 |
July | 0.261570E+11 | 0.141436E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425347E+09 | 40175921.81 |
August | 0.262677E+11 | 0.147542E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405149E+09 | 0.114320E+09 |
September | 0.253579E+11 | 0.146934E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77727343.74 | 0.500931E+09 |
October | 0.261570E+11 | 0.157215E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1547105.99 | 0.149153E+10 |
November | 0.253025E+11 | 0.154686E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240405E+10 |
December | 0.261570E+11 | 0.160913E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311075E+10 |
Annual Sum or Average | 0.308456E+12 | 0.179272E+11 | 0.143409E+11 | 0.113941E+10 | 0.204518E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.137213E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40175921.81 |
Maximum of Months | 0.262677E+11 | 0.161485E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425347E+09 | 0.350359E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.122961E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712565E+10 |
February | 0.702046E+11 | 0.110622E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685283E+10 |
March | 0.779788E+11 | 0.122472E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80078.92 | 0.566577E+10 |
April | 0.752779E+11 | 0.117416E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14367204.66 | 0.371100E+10 |
May | 0.778146E+11 | 0.121070E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82097748.55 | 0.214665E+10 |
June | 0.754422E+11 | 0.117060E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389794E+09 | 0.588799E+09 |
July | 0.776503E+11 | 0.120347E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881638E+09 | 83585517.11 |
August | 0.779788E+11 | 0.121655E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882003E+09 | 0.234600E+09 |
September | 0.752779E+11 | 0.117719E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192101E+09 | 0.998220E+09 |
October | 0.776503E+11 | 0.122427E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10372927.15 | 0.294996E+10 |
November | 0.751137E+11 | 0.118991E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492083E+10 |
December | 0.776503E+11 | 0.122602E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634429E+10 |
Annual Sum or Average | 0.915690E+12 | 0.143534E+12 | 0.149002E+12 | 0.245245E+10 | 0.416222E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.110622E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83585517.11 |
Maximum of Months | 0.779788E+11 | 0.122961E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882003E+09 | 0.712565E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392141E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378979E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17309.12 | 0.305148E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 738899.13 | 0.194011E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3866666.84 | 0.107733E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22849893.82 | 23233564.39 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60884418.80 | 1153770.27 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61155833.33 | 6596621.31 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13226268.25 | 44488372.95 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497606.52 | 0.145018E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259150E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343262E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 0.163237E+09 | 0.220091E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153770.27 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61155833.33 | 0.392141E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388715E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374681E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17327.78 | 0.301017E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 839637.61 | 0.192220E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3895903.57 | 0.107165E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22915071.55 | 23145895.45 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60936923.47 | 1149600.71 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61387626.81 | 6561168.49 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13556338.01 | 43288098.16 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 628507.62 | 0.140991E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254937E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338757E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 0.164177E+09 | 0.217263E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149600.71 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61387626.81 | 0.388715E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 75964402.59 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104276E+09 |
February | 0.00 | 68608505.50 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104565E+09 |
March | 0.00 | 75685198.85 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86178698.04 |
April | 0.00 | 73558970.85 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121902.91 | 56639628.99 |
May | 0.00 | 75824800.72 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 689042.98 | 36414615.39 |
June | 0.00 | 73279767.11 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3970106.78 | 11688667.22 |
July | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10538793.67 | 2060315.94 |
August | 0.00 | 75685198.85 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11537013.67 | 4521296.96 |
September | 0.00 | 73558970.85 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1856906.44 | 18587722.84 |
October | 0.00 | 75964402.59 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46876.57 | 48865769.34 |
November | 0.00 | 73419368.98 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75605304.16 |
December | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94547643.18 |
Annual Sum or Average | 0.00 | 0.893758E+09 | 0.300992E+10 | 28760643.02 | 0.643951E+09 | ||||
Minimum of Months | 0.00 | 68608505.50 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2060315.94 |
Maximum of Months | 0.00 | 76104004.46 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11537013.67 | 0.104565E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109813E+09 |
February | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105533E+09 |
March | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4835.00 | 84729135.21 |
April | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 283750.16 | 53860395.46 |
May | 0.303504E+09 | 75845534.87 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1224673.84 | 29528949.02 |
June | 0.293842E+09 | 73299805.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6896605.86 | 6123532.74 |
July | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17631815.77 | 305880.09 |
August | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17908087.10 | 1803612.13 |
September | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4232337.50 | 11805154.93 |
October | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 306231.49 | 39066738.07 |
November | 0.293661E+09 | 73439445.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72233327.86 |
December | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95915066.94 |
Annual Sum or Average | 0.357224E+10 | 0.894002E+09 | 0.301074E+10 | 48488336.72 | 0.610718E+09 | ||||
Minimum of Months | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305880.09 |
Maximum of Months | 0.303685E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17908087.10 | 0.109813E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392146E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379328E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17326.02 | 0.305968E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734003.31 | 0.195332E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3795135.75 | 0.108977E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22650996.64 | 23508899.31 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60520402.84 | 1177775.17 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60877900.77 | 6859621.58 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13148521.37 | 45034385.25 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485135.93 | 0.145887E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259823E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343401E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 0.162229E+09 | 0.220744E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177775.17 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60877900.77 | 0.392146E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388731E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374876E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17326.43 | 0.301782E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 746459.95 | 0.193591E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3801391.25 | 0.108541E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22692897.02 | 23455856.18 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60551903.32 | 1173552.51 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60958211.13 | 6843137.65 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13299971.52 | 44176434.54 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543640.93 | 0.141826E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255669E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338833E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 0.162612E+09 | 0.217950E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173552.51 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60958211.13 | 0.388731E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391872E+09 |
February | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378756E+09 |
March | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15340.41 | 0.305337E+09 |
April | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 707100.72 | 0.194881E+09 |
May | 0.303504E+09 | 0.120651E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3716483.05 | 0.109409E+09 |
June | 0.293842E+09 | 0.116602E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22160785.73 | 24175628.63 |
July | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59580484.02 | 1245139.07 |
August | 0.303685E+09 | 0.120429E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60043095.51 | 6840340.73 |
September | 0.293479E+09 | 0.117046E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12703713.28 | 45421026.22 |
October | 0.303322E+09 | 0.120874E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 450591.00 | 0.146004E+09 |
November | 0.293661E+09 | 0.116824E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258914E+09 |
December | 0.303141E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342896E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142214E+10 | 0.307301E+10 | 0.159378E+09 | 0.220575E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109169E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245139.07 |
Maximum of Months | 0.303685E+09 | 0.121096E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60043095.51 | 0.391872E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388967E+09 |
February | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374858E+09 |
March | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15350.02 | 0.301071E+09 |
April | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 758934.93 | 0.193100E+09 |
May | 0.303504E+09 | 0.120637E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3725920.42 | 0.108963E+09 |
June | 0.293842E+09 | 0.116588E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22173778.56 | 24134876.24 |
July | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59594455.82 | 1241345.71 |
August | 0.303685E+09 | 0.120415E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60177505.86 | 6801907.44 |
September | 0.293479E+09 | 0.117032E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12859752.45 | 44483656.60 |
October | 0.303322E+09 | 0.120859E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 544776.44 | 0.142096E+09 |
November | 0.293661E+09 | 0.116810E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254741E+09 |
December | 0.303141E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338677E+09 |
Annual Sum or Average | 0.357224E+10 | 0.142197E+10 | 0.307265E+10 | 0.159850E+09 | 0.217914E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.109156E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241345.71 |
Maximum of Months | 0.303685E+09 | 0.121082E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60177505.86 | 0.388967E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204498E+09 |
February | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197980E+09 |
March | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7860.54 | 0.158718E+09 |
April | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357721.00 | 0.100845E+09 |
May | 0.303504E+09 | 75845534.87 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1911709.05 | 56039221.16 |
June | 0.293842E+09 | 73299805.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11378202.12 | 12174051.11 |
July | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30489699.80 | 633002.05 |
August | 0.303685E+09 | 75705894.83 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30715906.01 | 3504394.33 |
September | 0.293479E+09 | 73579085.42 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6450389.55 | 23442779.47 |
October | 0.303322E+09 | 75985174.92 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 209375.40 | 75681687.15 |
November | 0.293661E+09 | 73439445.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136235E+09 |
December | 0.303141E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179524E+09 |
Annual Sum or Average | 0.357224E+10 | 0.894002E+09 | 0.301074E+10 | 81520863.48 | 0.114928E+10 | ||||
Minimum of Months | 0.273974E+09 | 68627266.37 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633002.05 |
Maximum of Months | 0.303685E+09 | 76124814.96 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30715906.01 | 0.204498E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303438E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107951E+10 |
February | 0.415303E+11 | 0.270892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103055E+10 |
March | 0.461292E+11 | 0.296991E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862011E+09 |
April | 0.445315E+11 | 0.281203E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1383679.16 | 0.579206E+09 |
May | 0.460320E+11 | 0.285840E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6731954.93 | 0.354999E+09 |
June | 0.446286E+11 | 0.274883E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36311439.38 | 0.118261E+09 |
July | 0.459349E+11 | 0.282922E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88685260.59 | 26724919.40 |
August | 0.461292E+11 | 0.289614E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97744877.40 | 48361461.39 |
September | 0.445315E+11 | 0.283920E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18885906.31 | 0.174916E+09 |
October | 0.459349E+11 | 0.298998E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1323916.65 | 0.445948E+09 |
November | 0.444343E+11 | 0.292073E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744867E+09 |
December | 0.459349E+11 | 0.302987E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959213E+09 |
Annual Sum or Average | 0.541686E+12 | 0.346376E+11 | 0.175857E+12 | 0.251067E+09 | 0.642456E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.270892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26724919.40 |
Maximum of Months | 0.461292E+11 | 0.303438E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97744877.40 | 0.107951E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303438E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109125E+10 |
February | 0.415303E+11 | 0.270892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104107E+10 |
March | 0.461292E+11 | 0.296991E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870797E+09 |
April | 0.445315E+11 | 0.281203E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1208058.97 | 0.586394E+09 |
May | 0.460320E+11 | 0.285840E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6043561.55 | 0.361249E+09 |
June | 0.446286E+11 | 0.274883E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34025449.57 | 0.121503E+09 |
July | 0.459349E+11 | 0.282922E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84844931.02 | 27643121.12 |
August | 0.461292E+11 | 0.289614E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94303420.94 | 49317501.61 |
September | 0.445315E+11 | 0.283920E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17250791.44 | 0.179742E+09 |
October | 0.459349E+11 | 0.298998E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1053026.40 | 0.452485E+09 |
November | 0.444343E+11 | 0.292073E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753602E+09 |
December | 0.459349E+11 | 0.302987E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969218E+09 |
Annual Sum or Average | 0.541686E+12 | 0.346376E+11 | 0.175857E+12 | 0.238729E+09 | 0.650427E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.270892E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27643121.12 |
Maximum of Months | 0.461292E+11 | 0.303438E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94303420.94 | 0.109125E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987335E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940531E+09 |
March | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786573E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 621604.44 | 0.531255E+09 |
May | 0.409635E+10 | 0.113343E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4081612.30 | 0.324318E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 26552326.44 | 0.101503E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 74652438.67 | 15392910.19 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 81444423.50 | 34739429.52 |
September | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 11727394.54 | 0.158366E+09 |
October | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 109788.91 | 0.411610E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683382E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876136E+09 |
Annual Sum or Average | 0.482041E+11 | 0.133271E+11 | 0.392709E+12 | 0.359593E+12 | 0.199190E+09 | 0.585114E+10 | |||
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15392910.19 |
Maximum of Months | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 81444423.50 | 0.987335E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.141237E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624227E+09 |
February | 0.00 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599559E+09 |
March | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36570.80 | 0.479772E+09 |
April | 0.00 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1934825.20 | 0.304914E+09 |
May | 0.00 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8790216.33 | 0.168325E+09 |
June | 0.00 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40410538.74 | 38812678.94 |
July | 0.00 | 0.140856E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92476276.38 | 2911801.32 |
August | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91737791.82 | 14251264.96 |
September | 0.00 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22961545.88 | 71307543.68 |
October | 0.00 | 0.141237E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117786.71 | 0.232818E+09 |
November | 0.00 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413303E+09 |
December | 0.00 | 0.140856E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545069E+09 |
Annual Sum or Average | 0.166358E+11 | 0.124715E+11 | 0.260466E+09 | 0.349527E+10 | |||||
Minimum of Months | 0.00 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2911801.32 |
Maximum of Months | 0.00 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92476276.38 | 0.624227E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.280997E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433219E+09 |
February | 0.00 | 0.253715E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416263E+09 |
March | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25420.11 | 0.331262E+09 |
April | 0.00 | 0.271470E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1358519.65 | 0.208698E+09 |
May | 0.00 | 0.281484E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6162588.38 | 0.113424E+09 |
June | 0.00 | 0.272715E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28520770.06 | 25353619.82 |
July | 0.00 | 0.280239E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65206775.86 | 1812463.96 |
August | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64466722.60 | 9370457.62 |
September | 0.00 | 0.271470E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16275189.27 | 47496359.95 |
October | 0.00 | 0.280997E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437274.83 | 0.157678E+09 |
November | 0.00 | 0.272498E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283911E+09 |
December | 0.00 | 0.280239E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377712E+09 |
Annual Sum or Average | 0.330977E+10 | 0.359769E+10 | 0.183453E+09 | 0.240620E+10 | |||||
Minimum of Months | 0.00 | 0.253715E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1812463.96 |
Maximum of Months | 0.00 | 0.281971E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65206775.86 | 0.433219E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480333E+09 |
February | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461485E+09 |
March | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25933.06 | 0.367251E+09 |
April | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498637.71 | 0.230273E+09 |
May | 0.00 | 0.233042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6957770.01 | 0.122871E+09 |
June | 0.00 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34801083.99 | 24575552.65 |
July | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82439142.60 | 1213342.64 |
August | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80032382.25 | 7820727.34 |
September | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20589407.53 | 48959067.87 |
October | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1638836.96 | 0.167652E+09 |
November | 0.00 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312866E+09 |
December | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418935E+09 |
Annual Sum or Average | 0.274017E+11 | 0.227983E+09 | 0.264423E+10 | ||||||
Minimum of Months | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1213342.64 |
Maximum of Months | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82439142.60 | 0.480333E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853319E+09 |
February | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820265E+09 |
March | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23328.68 | 0.656965E+09 |
April | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748829.87 | 0.418007E+09 |
May | 0.00 | 0.246639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7829872.98 | 0.233645E+09 |
June | 0.00 | 0.238955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41001559.86 | 59227904.25 |
July | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100682E+09 | 5368371.55 |
August | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101779E+09 | 21088741.24 |
September | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22307404.65 | 99096208.92 |
October | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1259795.72 | 0.313114E+09 |
November | 0.00 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559729E+09 |
December | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745090E+09 |
Annual Sum or Average | 0.290004E+11 | 0.276632E+09 | 0.478492E+10 | ||||||
Minimum of Months | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5368371.55 |
Maximum of Months | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101779E+09 | 0.853319E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13939.86 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13939.86 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13939.86 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13939.86 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13939.86 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13939.86 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13939.86 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13939.86 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13939.86 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 13939.86 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13939.86 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13939.86 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 13939.86 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13939.86 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 736.82 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 888.82 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 736.82 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 916.72 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 736.82 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.52 | 27-MAR-16:00 | 676.93 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 736.82 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 | 08-APR-10:00 | 477.32 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 736.82 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 | 30-MAY-13:00 | 370.71 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 736.82 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.94 | 19-JUN-12:00 | 185.42 | 03-JUN-03:40 |
July | 1169.53 | 01-JUL-00:10 | 736.82 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.50 | 07-JUL-12:00 | 63.98 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 736.82 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.42 | 24-AUG-16:00 | 144.73 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 736.82 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.26 | 01-SEP-14:00 | 274.63 | 30-SEP-00:50 |
October | 1169.53 | 02-OCT-00:10 | 736.82 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.16 | 25-OCT-12:30 | 480.24 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 736.82 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 659.31 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 736.82 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 767.76 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 736.82 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 | |||||
Maximum of Months | 1169.53 | 736.82 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 309.94 | 916.72 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 853.24 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.29 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 853.24 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 192.41 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 853.24 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27-MAR-16:00 | 146.05 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 853.24 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | 07-APR-13:00 | 104.77 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 853.24 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 30-MAY-13:00 | 83.28 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 853.24 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 | 19-JUN-12:00 | 46.11 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 853.24 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.65 | 07-JUL-12:00 | 17.90 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 853.24 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.95 | 24-AUG-15:00 | 37.05 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 853.24 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 | 01-SEP-14:00 | 65.03 | 30-SEP-00:50 |
October | 1354.32 | 02-OCT-00:10 | 853.24 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 25-OCT-11:00 | 107.85 | 29-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 853.24 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 140.92 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 853.24 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 163.29 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 853.24 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | |||||
Maximum of Months | 1354.32 | 853.24 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 | 192.41 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 408.24 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 614.19 | 02-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 408.24 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 627.54 | 06-FEB-07:20 |
March | 907.20 | 01-MAR-00:10 | 408.24 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 18.05 | 27-MAR-16:00 | 480.35 | 23-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 408.24 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 84.18 | 07-APR-13:00 | 352.75 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 408.24 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 132.61 | 30-MAY-13:00 | 270.93 | 01-MAY-20:15 |
June | 907.20 | 01-JUN-00:10 | 408.24 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 224.86 | 19-JUN-12:00 | 152.32 | 02-JUN-06:10 |
July | 907.20 | 01-JUL-00:10 | 408.24 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 186.82 | 07-JUL-12:00 | 69.96 | 01-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 408.24 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 185.58 | 24-AUG-15:25 | 108.78 | 08-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 408.24 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 146.22 | 01-SEP-14:00 | 210.34 | 24-SEP-06:10 |
October | 907.20 | 02-OCT-00:10 | 408.24 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 59.64 | 04-OCT-13:00 | 355.36 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 408.24 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 472.25 | 24-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 408.24 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 536.13 | 31-DEC-23:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | ||||||
Maximum of Months | 907.20 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 224.86 | 627.54 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2252.45 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2314.05 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 27-MAR-16:00 | 1752.34 | 23-MAR-04:30 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.58 | 08-APR-10:00 | 1253.90 | 01-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.06 | 30-MAY-13:00 | 1023.03 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 806.34 | 19-JUN-12:00 | 591.09 | 03-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.32 | 07-JUL-12:00 | 237.12 | 01-JUL-23:30 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.62 | 24-AUG-15:00 | 483.40 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.30 | 01-SEP-14:00 | 824.37 | 30-SEP-00:50 |
October | 15368.40 | 02-OCT-00:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.66 | 25-OCT-11:40 | 1273.58 | 29-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1699.20 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1937.77 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.12 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 806.34 | 2314.05 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 12090.12 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4562.17 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 12090.12 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4707.82 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 12090.12 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 | 27-MAR-16:00 | 3603.10 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 12090.12 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.38 | 07-APR-13:00 | 2591.21 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 12090.12 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 976.26 | 30-MAY-13:00 | 2106.00 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 12090.12 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.34 | 19-JUN-12:00 | 1192.95 | 03-JUN-03:10 |
July | 45622.98 | 01-JUL-00:10 | 12090.12 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1354.05 | 07-JUL-12:00 | 480.60 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 12090.12 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.60 | 24-AUG-15:00 | 979.40 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 12090.12 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.17 | 01-SEP-14:00 | 1639.68 | 30-SEP-00:50 |
October | 45622.98 | 02-OCT-00:10 | 12090.12 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.93 | 25-OCT-11:00 | 2658.34 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 12090.12 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3493.98 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 12090.12 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4000.64 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.60 | |||||
Maximum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.34 | 4707.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.16 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 55.58 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:10 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 04-OCT-15:10 | 142.34 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.88 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.54 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.70 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-16:00 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 55.58 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:10 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 25-OCT-11:00 | 142.32 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 89.33 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 68.64 | 02-JAN-05:00 |
February | 0.00 | 01-FEB-00:10 | 89.33 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 70.75 | 06-FEB-03:00 |
March | 0.00 | 01-MAR-00:10 | 89.33 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 53.11 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 89.33 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 07-APR-13:00 | 38.24 | 12-APR-06:20 |
May | 0.00 | 01-MAY-00:10 | 89.33 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 30-MAY-13:00 | 30.68 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 89.33 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 19-JUN-12:00 | 18.57 | 02-JUN-06:00 |
July | 0.00 | 01-JUL-00:10 | 89.33 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 07-JUL-12:00 | 9.13 | 02-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 89.33 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 24-AUG-15:00 | 15.73 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 89.33 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 01-SEP-14:00 | 25.28 | 30-SEP-00:55 |
October | 0.00 | 01-OCT-00:10 | 89.33 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 04-OCT-13:00 | 41.88 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 89.33 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 52.33 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 89.33 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58.53 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 89.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | |||||
Maximum of Months | 0.00 | 89.33 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 70.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 89.35 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 73.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 89.35 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 75.56 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 89.35 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27-MAR-16:00 | 55.86 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 89.35 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 08-APR-10:00 | 39.48 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 89.35 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 | 30-MAY-13:00 | 30.72 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 89.35 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 19-JUN-12:00 | 15.51 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 89.35 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 10-JUL-15:10 | 5.55 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 89.35 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 24-AUG-15:10 | 12.17 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 89.35 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 01-SEP-15:10 | 22.48 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 89.35 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 25-OCT-11:00 | 39.72 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 89.35 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 54.42 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 89.35 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63.32 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | |||||
Maximum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 75.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 60.70 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:10 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:08 | 142.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.89 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.53 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.70 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-16:00 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 60.76 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:08 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:08 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:10 | 142.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.14 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.10 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.14 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.26 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.14 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 27-MAR-16:00 | 200.67 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.14 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 08-APR-10:00 | 141.95 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.14 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-16:00 | 110.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.14 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 19-JUN-12:00 | 56.02 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 142.14 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 10-JUL-15:10 | 20.30 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.14 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 24-AUG-16:00 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.14 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 | 01-SEP-15:10 | 81.01 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.14 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 04-OCT-15:10 | 142.82 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.14 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.48 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.14 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.40 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | |||||
Maximum of Months | 180.00 | 142.14 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 271.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 142.12 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.08 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 142.12 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.23 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 142.12 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 27-MAR-16:00 | 200.65 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 142.12 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 | 08-APR-10:00 | 141.93 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 142.12 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-16:00 | 110.54 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 142.12 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 19-JUN-12:00 | 56.01 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 142.12 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 10-JUL-15:10 | 20.29 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 142.12 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 24-AUG-15:10 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 142.12 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 01-SEP-15:10 | 81.01 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 142.12 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 04-OCT-15:10 | 142.80 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 142.12 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.46 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 142.12 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.38 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | |||||
Maximum of Months | 180.00 | 142.12 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 271.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 89.35 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 135.11 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 89.35 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 138.77 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 89.35 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 27-MAR-16:00 | 102.66 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 89.35 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 08-APR-10:00 | 72.62 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 89.35 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 30-MAY-16:00 | 56.56 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 89.35 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 19-JUN-12:00 | 28.66 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 89.35 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 | 10-JUL-15:10 | 10.38 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 89.35 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 24-AUG-16:00 | 22.54 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 89.35 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 14-SEP-16:00 | 41.45 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 89.35 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 02-OCT-16:00 | 73.06 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 89.35 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 100.01 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 89.35 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 116.34 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | |||||
Maximum of Months | 180.00 | 89.35 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 138.77 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 687.01 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 704.33 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 540.59 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.49 | 07-APR-13:00 | 399.20 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.77 | 30-MAY-13:00 | 321.44 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.06 | 19-JUN-12:00 | 186.60 | 03-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.42 | 07-JUL-12:00 | 88.13 | 01-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.05 | 01-SEP-14:00 | 244.33 | 24-SEP-05:50 |
October | 26988.77 | 02-OCT-00:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 25-OCT-11:00 | 400.66 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 525.94 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.55 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.13 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 218.06 | 704.33 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 691.20 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 708.51 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 543.52 | 23-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 | 07-APR-13:00 | 399.21 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.70 | 30-MAY-13:00 | 321.45 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.19 | 19-JUN-12:00 | 186.60 | 03-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.25 | 07-JUL-12:00 | 89.82 | 02-JUL-05:10 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.87 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.21 | 01-SEP-14:00 | 248.63 | 24-SEP-06:00 |
October | 26988.77 | 02-OCT-00:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 25-OCT-11:00 | 401.66 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 529.81 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.56 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 214.19 | 708.51 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 617.52 | 02-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 630.15 | 06-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 486.76 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 38.35 | 07-APR-13:00 | 357.24 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.73 | 30-MAY-13:00 | 284.65 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 179.95 | 19-JUN-12:00 | 163.21 | 03-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 141.54 | 07-JUL-12:00 | 79.05 | 02-JUL-05:20 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 140.57 | 24-AUG-15:50 | 135.15 | 08-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 101.08 | 01-SEP-14:00 | 225.15 | 24-SEP-05:17 |
October | 2401.70 | 02-OCT-00:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 13.49 | 04-OCT-13:00 | 359.46 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 475.32 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 545.60 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 179.95 | 630.15 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 412.33 | 02-JAN-05:00 |
February | 0.00 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 423.65 | 06-FEB-03:00 |
March | 0.00 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 27-MAR-16:00 | 312.76 | 23-MAR-06:00 |
April | 0.00 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 | 07-APR-13:00 | 220.55 | 03-APR-06:00 |
May | 0.00 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.20 | 30-MAY-13:00 | 171.48 | 01-MAY-05:00 |
June | 0.00 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 19-JUN-12:00 | 91.95 | 03-JUN-03:00 |
July | 0.00 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.72 | 07-JUL-12:00 | 34.15 | 02-JUL-03:00 |
August | 0.00 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.71 | 24-AUG-15:00 | 74.09 | 08-AUG-05:00 |
September | 0.00 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.42 | 01-SEP-14:00 | 128.26 | 30-SEP-00:55 |
October | 0.00 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 04-OCT-13:00 | 225.58 | 09-OCT-06:00 |
November | 0.00 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 304.61 | 24-NOV-07:00 |
December | 0.00 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 354.75 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | ||||
Maximum of Months | 0.00 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 423.65 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 270.66 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 286.68 | 02-JAN-05:00 |
February | 0.00 | 270.66 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 294.56 | 06-FEB-03:00 |
March | 0.00 | 270.66 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 27-MAR-16:00 | 217.45 | 23-MAR-06:00 |
April | 0.00 | 270.66 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 | 07-APR-13:00 | 153.35 | 03-APR-06:00 |
May | 0.00 | 270.66 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.84 | 30-MAY-13:00 | 119.08 | 01-MAY-05:00 |
June | 0.00 | 270.66 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 19-JUN-12:00 | 63.06 | 03-JUN-03:00 |
July | 0.00 | 270.66 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.87 | 07-JUL-12:00 | 22.98 | 02-JUL-03:00 |
August | 0.00 | 270.66 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.09 | 24-AUG-15:00 | 50.72 | 08-AUG-05:00 |
September | 0.00 | 270.66 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 | 01-SEP-14:00 | 87.36 | 30-SEP-00:55 |
October | 0.00 | 270.66 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 25-OCT-11:00 | 154.29 | 09-OCT-06:00 |
November | 0.00 | 270.66 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 211.79 | 24-NOV-07:00 |
December | 0.00 | 270.66 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.65 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 270.66 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.98 | ||||
Maximum of Months | 0.00 | 270.66 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 294.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 315.52 | 02-JAN-05:00 |
February | 0.00 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 325.03 | 06-FEB-03:00 |
March | 0.00 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 27-MAR-16:00 | 241.01 | 23-MAR-06:00 |
April | 0.00 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 07-APR-13:00 | 170.07 | 03-APR-06:00 |
May | 0.00 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 30-MAY-13:00 | 132.14 | 01-MAY-05:00 |
June | 0.00 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.97 | 19-JUN-12:00 | 66.26 | 03-JUN-03:00 |
July | 0.00 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.67 | 07-JUL-12:00 | 23.10 | 02-JUL-05:00 |
August | 0.00 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.53 | 24-AUG-16:00 | 51.79 | 08-AUG-05:00 |
September | 0.00 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.81 | 01-SEP-14:00 | 96.45 | 24-SEP-06:00 |
October | 0.00 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | 25-OCT-11:00 | 171.10 | 09-OCT-06:00 |
November | 0.00 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 234.74 | 24-NOV-07:00 |
December | 0.00 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 273.32 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | |||
Maximum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.97 | 325.03 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 562.28 | 02-JAN-05:00 |
February | 0.00 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 578.57 | 06-FEB-03:00 |
March | 0.00 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27-MAR-16:00 | 427.58 | 23-MAR-06:00 |
April | 0.00 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.18 | 07-APR-13:00 | 301.95 | 03-APR-06:00 |
May | 0.00 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.12 | 30-MAY-13:00 | 234.83 | 01-MAY-05:00 |
June | 0.00 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.18 | 19-JUN-12:00 | 126.23 | 03-JUN-03:00 |
July | 0.00 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.12 | 07-JUL-12:00 | 47.44 | 02-JUL-03:00 |
August | 0.00 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.10 | 24-AUG-16:00 | 99.51 | 08-AUG-05:00 |
September | 0.00 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.81 | 14-SEP-14:00 | 171.65 | 24-SEP-06:00 |
October | 0.00 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 25-OCT-11:00 | 303.82 | 09-OCT-06:00 |
November | 0.00 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 416.46 | 24-NOV-07:00 |
December | 0.00 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 484.78 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.44 | |||
Maximum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.18 | 578.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22326.31 | 18-JAN-07:10 | 10223.90 | 15488.73 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21701.61 | 20-FEB-10:52 | 31949.70 | 23233.09 | 21292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22207.59 | 31-MAR-18:17 | 26837.75 | 37172.95 | 28744.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20381.56 | 23-APR-06:07 | 26837.75 | 18586.48 | 15969.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19100.93 | 02-MAY-05:44 | 44729.58 | 30977.46 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15904.83 | 22-JUN-20:30 | 10223.90 | 12390.98 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.95 | 14-JUL-21:00 | 10223.90 | 12390.98 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17225.86 | 24-AUG-20:30 | 10223.90 | 12390.98 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19944.08 | 24-SEP-05:13 | 62621.41 | 32526.33 | 29809.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25965.29 | 18-OCT-20:33 | 71567.33 | 86736.89 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27189.75 | 05-NOV-06:28 | 80513.24 | 55759.43 | 47907.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26056.00 | 04-DEC-20:50 | 35783.66 | 55759.43 | 40455.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15904.83 | 10223.90 | 12390.98 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27189.75 | 80513.24 | 86736.89 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3295.00 | 17-JAN-13:20 | 519.79 | 409.35 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.72 |
February | 2467.87 | 20-FEB-10:52 | 3248.70 | 1228.04 | 1443.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.51 |
March | 3376.66 | 07-MAR-13:30 | 519.79 | 409.35 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.59 |
April | 2544.80 | 07-APR-12:40 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 53.40 | 0.00 |
May | 2153.81 | 30-MAY-15:10 | 3898.44 | 1228.04 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 | 0.00 |
June | 2334.70 | 19-JUN-19:20 | 909.64 | 736.82 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 176.64 | 0.00 |
July | 2366.90 | 08-JUL-12:40 | 389.84 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 181.38 | 0.00 |
August | 3116.90 | 30-AUG-11:42 | 1299.48 | 1023.36 | 1262.95 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 | 0.00 |
September | 3465.13 | 30-SEP-12:40 | 389.84 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
October | 3702.72 | 04-OCT-12:10 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
November | 3193.33 | 02-NOV-12:40 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.48 |
December | 3718.02 | 03-DEC-11:36 | 3118.75 | 1964.86 | 2309.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2153.81 | 259.90 | 204.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3718.02 | 3898.44 | 1964.86 | 2309.40 | 0.00 | 0.00 | 0.00 | 0.00 | 181.38 | 416.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1879.15 | 18-JAN-07:10 | 1203.84 | 948.05 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 |
February | 1911.74 | 20-FEB-10:52 | 3762.00 | 1422.07 | 1671.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
March | 1986.40 | 31-MAR-18:17 | 3160.08 | 2275.31 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 |
April | 1988.05 | 11-APR-22:27 | 5417.28 | 1137.66 | 1337.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.71 |
May | 1869.40 | 13-MAY-23:30 | 2708.64 | 379.22 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 |
June | 1760.99 | 19-JUN-21:10 | 1354.32 | 568.83 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 0.00 |
July | 1782.41 | 10-JUL-21:10 | 1354.32 | 568.83 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 0.00 |
August | 1834.09 | 24-AUG-20:30 | 1203.84 | 758.44 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 0.00 |
September | 1814.51 | 30-SEP-00:42 | 8125.92 | 1137.66 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 |
October | 2122.38 | 19-OCT-06:18 | 6019.20 | 4740.24 | 5014.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.36 |
November | 2076.11 | 07-NOV-23:52 | 13543.20 | 2844.14 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.68 |
December | 2000.67 | 20-DEC-09:40 | 601.92 | 758.44 | 835.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1760.99 | 601.92 | 379.22 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2122.38 | 13543.20 | 4740.24 | 5014.30 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 80.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1522.51 | 24-JAN-09:06 | 0.00 | 3023.11 | 2209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.06 |
February | 984.74 | 20-FEB-10:48 | 0.00 | 4534.66 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.40 |
March | 1753.87 | 31-MAR-18:17 | 0.00 | 3627.73 | 2385.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.25 |
April | 1671.68 | 11-APR-22:27 | 0.00 | 1813.86 | 1413.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.52 |
May | 1606.91 | 13-MAY-23:30 | 0.00 | 604.62 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.69 |
June | 1526.62 | 22-JUN-20:30 | 0.00 | 1209.24 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 0.00 |
July | 1568.33 | 10-JUL-21:10 | 0.00 | 906.93 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 0.00 |
August | 1590.98 | 24-AUG-20:30 | 0.00 | 1209.24 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 | 0.00 |
September | 1529.97 | 01-SEP-21:00 | 0.00 | 1209.24 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 | 0.00 |
October | 1857.10 | 19-OCT-06:18 | 0.00 | 7557.77 | 5301.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.47 |
November | 1813.44 | 08-NOV-07:42 | 0.00 | 3778.88 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 |
December | 1774.53 | 20-DEC-09:40 | 0.00 | 1209.24 | 883.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 984.74 | 0.00 | 604.62 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1857.10 | 0.00 | 7557.77 | 5301.77 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 163.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 584.73 | 24-JAN-20:25 | 0.00 | 541.32 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.11 |
February | 461.72 | 20-FEB-10:48 | 0.00 | 902.19 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 |
March | 717.12 | 27-MAR-07:00 | 0.00 | 751.83 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.47 |
April | 753.02 | 11-APR-22:27 | 0.00 | 360.88 | 407.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.95 |
May | 741.05 | 16-MAY-01:10 | 0.00 | 60.15 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 |
June | 692.57 | 19-JUN-21:10 | 0.00 | 180.44 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 | 0.00 |
July | 714.30 | 10-JUL-21:10 | 0.00 | 180.44 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 0.00 |
August | 725.89 | 04-AUG-21:10 | 0.00 | 180.44 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 63.47 | 0.00 |
September | 700.25 | 24-SEP-05:13 | 0.00 | 631.54 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.80 |
October | 847.15 | 19-OCT-06:18 | 0.00 | 1503.65 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.25 |
November | 826.27 | 08-NOV-07:42 | 0.00 | 751.83 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.30 |
December | 479.66 | 03-DEC-11:36 | 0.00 | 721.75 | 815.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 461.72 | 0.00 | 60.15 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 847.15 | 0.00 | 1503.65 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 63.47 | 109.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39654.61 | 23-JAN-20:34 | 3528.00 | 2041.22 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 242.63 |
February | 35990.08 | 17-FEB-21:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 386.75 |
March | 40416.22 | 31-MAR-20:55 | 4838.40 | 2177.31 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 268.66 |
April | 40924.95 | 20-APR-19:55 | 2822.40 | 1632.98 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 0.00 | 265.36 |
May | 39495.82 | 01-MAY-20:37 | 2419.20 | 1088.65 | 12996.38 | 112907.11 | 0.00 | 0.00 | 0.00 | 0.00 | 253.34 |
June | 38263.79 | 19-JUN-20:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 87.98 | 0.00 |
July | 38252.80 | 10-JUL-20:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
August | 38415.53 | 04-AUG-20:00 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 119.23 | 0.00 |
September | 38145.59 | 14-SEP-19:30 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 43.78 | 0.00 |
October | 41684.72 | 18-OCT-20:30 | 1612.80 | 725.77 | 8664.25 | 75271.41 | 0.00 | 0.00 | 0.00 | 0.00 | 285.69 |
November | 40990.61 | 16-NOV-20:48 | 3528.00 | 2041.22 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 276.04 |
December | 40931.87 | 04-DEC-20:27 | 4233.60 | 2449.47 | 27436.80 | 238359.46 | 0.00 | 0.00 | 0.00 | 0.00 | 260.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35990.08 | 705.60 | 408.24 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41684.72 | 4838.40 | 2449.47 | 27436.80 | 238359.46 | 0.00 | 0.00 | 0.00 | 119.23 | 386.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13908.17 | 19-JAN-12:34 | 17076.00 | 1492.73 | 1778.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.34 |
February | 12916.72 | 19-FEB-12:06 | 51228.00 | 3582.55 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.13 |
March | 14010.46 | 07-MAR-13:30 | 6830.40 | 597.09 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.43 |
April | 11311.87 | 11-APR-22:27 | 61473.60 | 2349.21 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.15 |
May | 10915.57 | 17-MAY-04:00 | 61473.60 | 783.07 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.26 |
June | 10898.38 | 19-JUN-21:20 | 15368.40 | 1174.61 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 261.78 | 0.00 |
July | 10867.80 | 10-JUL-21:20 | 15368.40 | 1174.61 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 175.80 | 0.00 |
August | 11793.05 | 04-AUG-21:10 | 15368.40 | 1174.61 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 0.00 |
September | 13377.69 | 30-SEP-12:30 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.34 |
October | 14944.38 | 08-OCT-11:13 | 35859.60 | 2507.78 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.55 |
November | 13626.83 | 29-NOV-12:24 | 34152.00 | 2985.45 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.79 |
December | 15882.99 | 03-DEC-11:36 | 40982.40 | 2866.04 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10867.80 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15882.99 | 61473.60 | 3582.55 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 1054.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38808.96 | 18-JAN-07:10 | 40553.76 | 13433.46 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.97 |
February | 40076.74 | 20-FEB-10:52 | 126730.50 | 18739.68 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1725.76 |
March | 40684.64 | 31-MAR-18:17 | 106453.62 | 32240.31 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.77 |
April | 48293.36 | 11-APR-22:03 | 273737.88 | 24180.23 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.69 |
May | 38993.18 | 16-MAY-01:10 | 91245.96 | 2686.69 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.67 |
June | 35735.93 | 19-JUN-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 571.59 | 0.00 |
July | 36112.43 | 10-JUL-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 375.60 | 0.00 |
August | 37121.94 | 04-AUG-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 858.18 | 0.00 |
September | 43710.56 | 29-SEP-23:53 | 136868.94 | 8060.08 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.07 |
October | 47761.26 | 27-OCT-21:30 | 319360.86 | 56420.54 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2090.67 |
November | 43269.98 | 07-NOV-23:52 | 456229.80 | 40300.39 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1943.72 |
December | 41594.02 | 20-DEC-09:40 | 20276.88 | 9994.50 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35735.93 | 20276.88 | 2686.69 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48293.36 | 456229.80 | 56420.54 | 51729.60 | 0.00 | 0.00 | 0.00 | 0.00 | 858.18 | 2090.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2736.24 | 17-JAN-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.99 |
February | 2734.55 | 02-FEB-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.52 |
March | 2826.56 | 07-MAR-16:01 | 777.60 | 90.97 | 547.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.91 |
April | 3006.06 | 10-APR-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
May | 3069.32 | 31-MAY-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 0.00 |
June | 3099.26 | 26-JUN-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 0.00 |
July | 3109.01 | 13-JUL-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 0.00 |
August | 3129.22 | 04-AUG-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.93 | 0.00 |
September | 3096.53 | 07-SEP-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 | 0.00 |
October | 2930.12 | 02-OCT-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
November | 2821.24 | 02-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 |
December | 2698.18 | 17-DEC-16:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2698.18 | 324.00 | 53.30 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3129.22 | 777.60 | 90.97 | 547.87 | 0.00 | 0.00 | 0.00 | 0.00 | 54.93 | 132.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1574.18 | 17-JAN-16:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.71 |
February | 2438.83 | 20-FEB-16:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.11 |
March | 2723.35 | 07-MAR-16:01 | 777.60 | 90.96 | 547.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 |
April | 2947.17 | 10-APR-15:01 | 680.40 | 79.59 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 |
May | 3052.17 | 31-MAY-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
June | 3077.36 | 26-JUN-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 0.00 |
July | 3060.09 | 13-JUL-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 0.00 |
August | 3076.18 | 01-AUG-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 | 0.00 |
September | 3034.94 | 06-SEP-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 0.00 |
October | 2915.65 | 04-OCT-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 0.00 |
November | 2652.86 | 03-NOV-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 |
December | 944.39 | 17-DEC-16:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 944.39 | 324.00 | 53.30 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3077.36 | 777.60 | 90.96 | 547.81 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 | 104.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 192.69 | 19-JAN-14:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 |
February | 323.45 | 03-FEB-12:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.60 |
March | 407.57 | 03-MAR-13:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 |
April | 494.45 | 08-APR-12:30 | 0.00 | 5.58 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
May | 419.29 | 30-MAY-16:40 | 0.00 | 7.82 | 131.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
June | 469.24 | 26-JUN-15:30 | 0.00 | 7.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
July | 529.34 | 21-JUL-18:00 | 0.00 | 60.30 | 131.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 0.00 |
August | 524.75 | 30-AUG-12:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 |
September | 644.40 | 30-SEP-12:30 | 0.00 | 5.58 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
October | 701.33 | 04-OCT-12:00 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
November | 609.90 | 02-NOV-12:30 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
December | 503.71 | 17-DEC-13:00 | 0.00 | 5.58 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 192.69 | 0.00 | 5.58 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 701.33 | 0.00 | 60.30 | 131.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 51.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 391.43 | 22-JAN-09:02 | 324.00 | 125.09 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.94 |
February | 469.02 | 20-FEB-09:02 | 270.00 | 104.25 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
March | 785.86 | 28-MAR-18:01 | 1108.80 | 634.40 | 1011.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 |
April | 862.48 | 08-APR-15:02 | 324.00 | 33.51 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
May | 932.78 | 30-MAY-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 0.00 |
June | 953.12 | 22-JUN-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 | 0.00 |
July | 959.81 | 10-JUL-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
August | 962.12 | 24-AUG-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 0.00 |
September | 963.03 | 01-SEP-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 |
October | 844.83 | 02-OCT-18:02 | 831.60 | 475.80 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
November | 768.51 | 05-NOV-08:62 | 216.00 | 83.40 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 |
December | 499.21 | 25-DEC-09:02 | 270.00 | 104.25 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 391.43 | 216.00 | 33.51 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 963.03 | 1108.80 | 634.40 | 1011.60 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 32.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2256.63 | 19-JAN-09:02 | 216.00 | 373.11 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 |
February | 2387.03 | 25-FEB-09:02 | 324.00 | 198.99 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 |
March | 2543.34 | 03-MAR-09:02 | 216.00 | 373.11 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.21 |
April | 2684.61 | 10-APR-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 |
May | 2771.58 | 29-MAY-08:61 | 378.00 | 232.16 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
June | 2799.66 | 01-JUN-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 0.00 |
July | 2836.74 | 14-JUL-08:62 | 216.00 | 373.11 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 0.00 |
August | 2816.07 | 18-AUG-08:62 | 216.00 | 373.11 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 |
September | 2783.12 | 01-SEP-18:02 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 34.22 | 0.00 |
October | 2681.69 | 04-OCT-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
November | 2552.71 | 02-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.66 |
December | 2398.20 | 17-DEC-09:02 | 324.00 | 198.99 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2256.63 | 216.00 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2836.74 | 831.60 | 756.88 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 179.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 700.19 | 26-JAN-09:03 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.97 |
February | 2238.31 | 25-FEB-09:02 | 324.00 | 198.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.91 |
March | 2468.33 | 03-MAR-09:02 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 |
April | 2627.77 | 08-APR-15:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 |
May | 2750.03 | 29-MAY-08:61 | 378.00 | 232.13 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 0.00 |
June | 2772.44 | 04-JUN-08:62 | 324.00 | 198.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
July | 2816.74 | 14-JUL-08:62 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 0.00 |
August | 2818.28 | 18-AUG-08:62 | 216.00 | 373.07 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 | 0.00 |
September | 2714.29 | 01-SEP-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 0.00 |
October | 2508.91 | 04-OCT-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 0.00 |
November | 1998.45 | 04-NOV-08:62 | 270.00 | 165.81 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.23 |
December | 1158.69 | 17-DEC-09:02 | 324.00 | 198.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 700.19 | 216.00 | 53.30 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2818.28 | 583.20 | 373.07 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 174.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1400.01 | 19-JAN-12:50 | 0.00 | 3112.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.32 |
February | 1351.36 | 20-FEB-10:48 | 0.00 | 7469.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.03 |
March | 1840.79 | 24-MAR-15:05 | 0.00 | 3734.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.04 |
April | 2118.97 | 11-APR-22:27 | 0.00 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.49 |
May | 1842.15 | 30-MAY-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
June | 1895.65 | 22-JUN-19:30 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 0.00 |
July | 1927.73 | 11-JUL-18:30 | 0.00 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 | 0.00 |
August | 1967.20 | 24-AUG-19:10 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 | 0.00 |
September | 1893.86 | 30-SEP-00:42 | 0.00 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.41 |
October | 2264.16 | 08-OCT-10:15 | 0.00 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.56 |
November | 1931.17 | 06-NOV-22:39 | 0.00 | 10457.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.76 |
December | 1694.87 | 20-DEC-10:00 | 0.00 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1351.36 | 0.00 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2264.16 | 0.00 | 10457.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 | 118.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2862.22 | 17-JAN-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.42 |
February | 2852.45 | 02-FEB-16:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.79 |
March | 2958.89 | 07-MAR-16:01 | 777.60 | 90.97 | 547.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 |
April | 3150.33 | 10-APR-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
May | 3184.50 | 27-MAY-15:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
June | 3246.86 | 15-JUN-15:02 | 583.20 | 68.23 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 0.00 |
July | 3241.96 | 06-JUL-18:02 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 | 0.00 |
August | 3273.29 | 15-AUG-18:02 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 | 0.00 |
September | 3180.62 | 01-SEP-18:02 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 0.00 |
October | 2989.50 | 30-OCT-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 |
November | 2949.16 | 02-NOV-15:01 | 680.40 | 79.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.35 |
December | 2838.41 | 17-DEC-16:02 | 324.00 | 53.30 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2838.41 | 324.00 | 53.30 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3273.29 | 831.60 | 756.88 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 132.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 882.59 | 17-JAN-16:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 |
February | 2017.56 | 20-FEB-16:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.31 |
March | 2837.34 | 07-MAR-16:01 | 777.60 | 90.96 | 547.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.33 |
April | 3084.68 | 10-APR-15:01 | 680.40 | 79.59 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
May | 3131.59 | 27-MAY-15:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
June | 3188.41 | 18-JUN-15:02 | 324.00 | 53.30 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 |
July | 3209.71 | 19-JUL-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 0.00 |
August | 3235.24 | 02-AUG-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 | 0.00 |
September | 3200.64 | 07-SEP-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 0.00 |
October | 3076.51 | 04-OCT-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
November | 2773.44 | 03-NOV-15:02 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
December | 692.70 | 08-DEC-16:03 | 583.20 | 68.22 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 692.70 | 324.00 | 53.30 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3235.24 | 777.60 | 90.96 | 547.81 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 | 110.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1365.88 | 17-JAN-16:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 |
February | 1360.39 | 02-FEB-16:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 |
March | 1374.02 | 15-MAR-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
April | 1444.75 | 10-APR-15:01 | 680.40 | 50.04 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 |
May | 1489.42 | 31-MAY-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 | 0.00 |
June | 1489.84 | 23-JUN-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
July | 1498.86 | 17-JUL-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 |
August | 1511.48 | 11-AUG-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 0.00 |
September | 1511.04 | 07-SEP-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 0.00 |
October | 1490.84 | 04-OCT-15:02 | 583.20 | 42.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
November | 1390.17 | 02-NOV-15:01 | 680.40 | 50.04 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
December | 1360.92 | 17-DEC-16:02 | 324.00 | 33.51 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1360.39 | 324.00 | 33.51 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1511.48 | 680.40 | 50.04 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 69.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22218.44 | 23-JAN-23:17 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.97 |
February | 21705.83 | 19-FEB-10:41 | 104956.32 | 5775.58 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.03 |
March | 24406.58 | 03-MAR-23:50 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.26 |
April | 29425.54 | 11-APR-22:27 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.11 |
May | 23314.06 | 16-MAY-01:10 | 53977.54 | 687.57 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.38 |
June | 22455.89 | 19-JUN-21:10 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
July | 22459.05 | 10-JUL-21:10 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 0.00 |
August | 22832.41 | 04-AUG-21:10 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 0.00 |
September | 24169.11 | 30-SEP-03:50 | 80966.30 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.18 |
October | 26183.05 | 18-OCT-22:04 | 134943.84 | 5156.77 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.63 |
November | 28807.96 | 07-NOV-23:52 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.41 |
December | 23925.24 | 04-DEC-23:31 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21705.83 | 26988.77 | 687.57 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29425.54 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 283.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24269.71 | 23-JAN-23:17 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.05 |
February | 24373.89 | 20-FEB-10:48 | 149937.60 | 8250.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.73 |
March | 27028.71 | 31-MAR-18:17 | 62973.79 | 8250.82 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.05 |
April | 31272.65 | 11-APR-22:27 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.61 |
May | 25362.55 | 16-MAY-01:10 | 53977.54 | 687.57 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.66 |
June | 24070.18 | 19-JUN-21:10 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.75 | 0.00 |
July | 23888.25 | 07-JUL-22:00 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 | 0.00 |
August | 24269.00 | 04-AUG-21:10 | 26988.77 | 2062.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 0.00 |
September | 25453.20 | 30-SEP-03:50 | 80966.30 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.76 |
October | 28691.85 | 18-OCT-22:04 | 134943.84 | 5156.77 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.06 |
November | 31848.20 | 07-NOV-23:52 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.95 |
December | 25373.85 | 04-DEC-23:31 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 |
Annual Sum or Average | |||||||||||
Minimum of Months | 23888.25 | 26988.77 | 687.57 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31848.20 | 269887.68 | 10313.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 284.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34789.16 | 17-JAN-11:39 | 3735.98 | 2119.12 | 104389.99 | 131208.19 | 0.00 | 0.00 | 0.00 | 0.00 | 245.35 |
February | 35660.18 | 20-FEB-10:52 | 6671.40 | 1816.39 | 74564.28 | 93720.13 | 0.00 | 0.00 | 0.00 | 0.00 | 230.67 |
March | 32471.94 | 24-MAR-15:05 | 8005.68 | 1816.39 | 89477.13 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 230.31 |
April | 32580.01 | 15-APR-18:10 | 8005.68 | 4238.24 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 239.79 |
May | 30336.77 | 29-MAY-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 49.36 | 0.00 |
June | 30992.25 | 01-JUN-18:07 | 11207.95 | 5812.44 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 51.39 | 0.00 |
July | 30680.13 | 08-JUL-10:50 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.32 | 0.00 |
August | 31921.56 | 25-AUG-17:06 | 10674.24 | 5812.44 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 29.58 | 0.00 |
September | 30282.61 | 04-SEP-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 22.51 | 0.00 |
October | 30840.63 | 08-OCT-10:15 | 3202.27 | 1453.11 | 59651.42 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.42 |
November | 32190.75 | 05-NOV-20:02 | 21348.48 | 7265.55 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 247.35 |
December | 31707.91 | 25-DEC-16:08 | 4803.41 | 1453.11 | 89477.13 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 210.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 30282.61 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35660.18 | 21348.48 | 7265.55 | 149128.56 | 179942.65 | 0.00 | 0.00 | 0.00 | 98.32 | 250.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4472.80 | 17-JAN-11:39 | 0.00 | 4611.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.57 |
February | 3331.33 | 20-FEB-10:52 | 0.00 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.04 |
March | 4027.12 | 24-MAR-15:05 | 0.00 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 |
April | 4686.40 | 14-APR-16:50 | 0.00 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.17 |
May | 4361.73 | 13-MAY-23:30 | 0.00 | 1054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.43 |
June | 4450.18 | 19-JUN-14:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 | 0.00 |
July | 4588.29 | 10-JUL-14:00 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.73 | 0.00 |
August | 4597.60 | 18-AUG-13:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.98 | 0.00 |
September | 4438.31 | 01-SEP-13:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.24 | 0.00 |
October | 4739.33 | 08-OCT-10:15 | 0.00 | 3162.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.79 |
November | 4855.83 | 29-NOV-12:02 | 0.00 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.18 |
December | 4773.18 | 16-DEC-12:13 | 0.00 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3331.33 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4855.83 | 0.00 | 4611.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 | 204.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.415901E+12 | 269302.07 | 23-JAN-20:30 | 0.513501E+12 | 444669.20 | 14-JAN-17:30 |
February | 0.374394E+12 | 265561.35 | 23-FEB-20:00 | 0.463934E+12 | 437046.61 | 05-FEB-19:10 |
March | 0.414564E+12 | 289667.21 | 27-MAR-18:10 | 0.414844E+12 | 382082.03 | 25-MAR-17:49 |
April | 0.414122E+12 | 339841.54 | 07-APR-19:10 | 0.374209E+12 | 400324.29 | 14-APR-17:40 |
May | 0.473048E+12 | 362885.20 | 31-MAY-19:19 | 0.353389E+12 | 289874.70 | 01-MAY-19:00 |
June | 0.618834E+12 | 424479.66 | 19-JUN-19:30 | 0.327180E+12 | 278396.77 | 01-JUN-17:19 |
July | 0.737321E+12 | 456562.51 | 20-JUL-19:00 | 0.330127E+12 | 285205.22 | 11-JUL-17:00 |
August | 0.699646E+12 | 457808.91 | 03-AUG-19:00 | 0.327506E+12 | 282052.96 | 30-AUG-17:30 |
September | 0.561545E+12 | 412008.26 | 07-SEP-19:10 | 0.323158E+12 | 280552.02 | 26-SEP-17:40 |
October | 0.482654E+12 | 355348.20 | 05-OCT-19:10 | 0.353722E+12 | 361684.66 | 27-OCT-19:30 |
November | 0.405666E+12 | 276510.58 | 06-NOV-20:19 | 0.396121E+12 | 356468.09 | 27-NOV-22:19 |
December | 0.417686E+12 | 271026.44 | 04-DEC-20:40 | 0.446534E+12 | 395133.51 | 31-DEC-17:00 |
Annual Sum or Average | 0.601538E+13 | 0.462422E+13 | ||||
Minimum of Months | 0.374394E+12 | 265561.35 | 0.323158E+12 | 278396.77 | ||
Maximum of Months | 0.737321E+12 | 457808.91 | 0.513501E+12 | 444669.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.655268E+11 | 0.234354E+11 | 0.148212E+12 | 0.834802E+11 | 0.492345E+11 | 0.484599E+10 | 0.00 | 0.119407E+10 | 0.00 | 0.00 | 0.270859E+11 | 0.770499E+10 | 0.00 |
February | 0.590345E+11 | 0.196535E+11 | 0.133859E+12 | 0.754015E+11 | 0.441367E+11 | 0.457469E+10 | 0.00 | 0.146334E+10 | 0.00 | 0.00 | 0.246501E+11 | 0.696279E+10 | 0.00 |
March | 0.653341E+11 | 0.196795E+11 | 0.148234E+12 | 0.834832E+11 | 0.484027E+11 | 0.549124E+10 | 0.00 | 0.576320E+10 | 0.00 | 0.00 | 0.252499E+11 | 0.770477E+10 | 0.00 |
April | 0.628433E+11 | 0.169621E+11 | 0.143397E+12 | 0.807867E+11 | 0.467710E+11 | 0.623403E+10 | 0.00 | 0.265792E+11 | 0.00 | 0.00 | 0.180060E+11 | 0.746516E+10 | 0.00 |
May | 0.648381E+11 | 0.156813E+11 | 0.148223E+12 | 0.834811E+11 | 0.477452E+11 | 0.789609E+10 | 0.00 | 0.835877E+11 | 0.00 | 0.00 | 0.862018E+10 | 0.770514E+10 | 0.00 |
June | 0.626959E+11 | 0.142014E+11 | 0.143446E+12 | 0.807893E+11 | 0.462833E+11 | 0.909873E+10 | 0.00 | 0.232014E+12 | 0.00 | 0.00 | 0.177353E+11 | 0.745818E+10 | 0.00 |
July | 0.645971E+11 | 0.151101E+11 | 0.148174E+12 | 0.834781E+11 | 0.495094E+11 | 0.103469E+11 | 0.00 | 0.326668E+12 | 0.00 | 0.00 | 0.264677E+11 | 0.771397E+10 | 0.00 |
August | 0.650353E+11 | 0.166852E+11 | 0.148234E+12 | 0.834829E+11 | 0.497762E+11 | 0.980048E+10 | 0.00 | 0.291265E+12 | 0.00 | 0.00 | 0.223808E+11 | 0.770582E+10 | 0.00 |
September | 0.629547E+11 | 0.181304E+11 | 0.143397E+12 | 0.807868E+11 | 0.459107E+11 | 0.853079E+10 | 0.00 | 0.176988E+12 | 0.00 | 0.00 | 0.122739E+11 | 0.746601E+10 | 0.00 |
October | 0.653419E+11 | 0.208997E+11 | 0.148212E+12 | 0.834801E+11 | 0.488581E+11 | 0.773767E+10 | 0.00 | 0.808577E+11 | 0.00 | 0.00 | 0.142959E+11 | 0.770498E+10 | 0.00 |
November | 0.634100E+11 | 0.221286E+11 | 0.143462E+12 | 0.807881E+11 | 0.477409E+11 | 0.554643E+10 | 0.00 | 0.731619E+10 | 0.00 | 0.00 | 0.227700E+11 | 0.744925E+10 | 0.00 |
December | 0.654187E+11 | 0.238941E+11 | 0.148174E+12 | 0.834789E+11 | 0.490671E+11 | 0.520626E+10 | 0.00 | 0.245270E+10 | 0.00 | 0.00 | 0.270960E+11 | 0.771307E+10 | 0.00 |
Annual Sum or Average | 0.767031E+12 | 0.226461E+12 | 0.174502E+13 | 0.982917E+12 | 0.573436E+12 | 0.853093E+11 | 0.00 | 0.123615E+13 | 0.246632E+12 | 0.907542E+11 | |||
Minimum of Months | 0.590345E+11 | 0.142014E+11 | 0.133859E+12 | 0.754015E+11 | 0.441367E+11 | 0.457469E+10 | 0.00 | 0.119407E+10 | 0.00 | 0.00 | 0.862018E+10 | 0.696279E+10 | 0.00 |
Maximum of Months | 0.655268E+11 | 0.238941E+11 | 0.148234E+12 | 0.834832E+11 | 0.497762E+11 | 0.103469E+11 | 0.00 | 0.326668E+12 | 0.00 | 0.00 | 0.270960E+11 | 0.771397E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.169080E+12 | 0.00 | 0.192503E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.151553E+12 | 0.00 | 0.175177E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.707999E+11 | 0.00 | 0.192005E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.469323E+11 | 0.00 | 0.180321E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.218968E+11 | 0.00 | 0.179514E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.126067E+11 | 0.00 | 0.167459E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.974367E+10 | 0.00 | 0.168563E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.804058E+10 | 0.00 | 0.167426E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.119040E+11 | 0.00 | 0.164298E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.267074E+11 | 0.00 | 0.175097E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.733076E+11 | 0.00 | 0.175722E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.106276E+12 | 0.00 | 0.188437E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.708849E+12 | 0.212652E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.804058E+10 | 0.00 | 0.164298E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.169080E+12 | 0.00 | 0.192503E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 66976.13 | 02-JAN-20:10 | 14423.55 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 63148.16 | 02-JAN-07:19 | 27638.41 | 23-JAN-21:30 | 4201.99 | 19-JAN-09:00 | 0.00 | 01-JAN-00:10 |
February | 66976.13 | 01-FEB-20:10 | 14423.55 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 63148.16 | 01-FEB-07:19 | 26503.84 | 06-FEB-19:10 | 4400.11 | 06-FEB-10:09 | 0.00 | 01-FEB-00:10 |
March | 66976.13 | 01-MAR-20:10 | 14423.55 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 63148.16 | 13-MAR-06:19 | 38980.43 | 03-MAR-22:00 | 4097.42 | 25-MAR-21:00 | 0.00 | 01-MAR-00:10 |
April | 66976.13 | 03-APR-19:10 | 14423.55 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 63147.11 | 14-APR-06:19 | 34651.38 | 11-APR-21:00 | 4106.94 | 12-APR-22:49 | 0.00 | 01-APR-00:10 |
May | 66976.13 | 01-MAY-19:10 | 14423.55 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 63147.11 | 04-MAY-06:19 | 30201.26 | 01-MAY-20:30 | 4088.62 | 31-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 66976.13 | 01-JUN-19:19 | 14423.55 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 63146.49 | 16-JUN-06:19 | 27924.62 | 01-JUN-19:19 | 5443.62 | 24-JUN-18:30 | 0.00 | 01-JUN-00:10 |
July | 66976.13 | 03-JUL-19:30 | 14423.55 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 63146.92 | 24-JUL-06:19 | 28206.45 | 11-JUL-18:19 | 5340.64 | 05-JUL-20:49 | 0.00 | 01-JUL-00:10 |
August | 66976.13 | 01-AUG-19:10 | 14423.55 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 63146.92 | 16-AUG-06:19 | 30810.40 | 24-AUG-20:19 | 5206.68 | 03-AUG-19:00 | 0.00 | 01-AUG-00:10 |
September | 66976.13 | 01-SEP-19:10 | 14423.55 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 63147.73 | 27-SEP-06:19 | 26117.36 | 07-SEP-18:10 | 4757.17 | 14-SEP-06:30 | 0.00 | 01-SEP-00:10 |
October | 66976.13 | 02-OCT-19:10 | 14423.55 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 63148.16 | 06-OCT-06:19 | 44795.79 | 18-OCT-20:30 | 4309.89 | 24-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 66976.13 | 01-NOV-19:10 | 14423.55 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 63148.16 | 01-NOV-06:19 | 34880.97 | 06-NOV-21:49 | 4258.59 | 27-NOV-07:00 | 0.00 | 01-NOV-00:10 |
December | 66976.13 | 01-DEC-20:10 | 14423.55 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 63148.16 | 01-DEC-07:19 | 31187.37 | 04-DEC-23:10 | 4098.43 | 31-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 66976.13 | 14423.55 | 89475.41 | 63146.49 | 26117.36 | 4088.62 | 0.00 | |||||||
Maximum of Months | 66976.13 | 14423.55 | 89475.41 | 63148.16 | 44795.79 | 5443.62 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5543.12 | 17-JAN-16:10 | 0.00 | 0.00 | 10206.30 | 01-JAN-09:09 | 4738.24 | 31-JAN-19:10 | 0.00 |
February | 7740.70 | 03-FEB-12:39 | 0.00 | 0.00 | 10206.30 | 01-FEB-09:09 | 4738.53 | 06-FEB-19:10 | 0.00 |
March | 76606.84 | 27-MAR-15:00 | 0.00 | 0.00 | 10206.30 | 01-MAR-08:50 | 4738.55 | 28-MAR-06:19 | 0.00 |
April | 100486.03 | 07-APR-16:49 | 0.00 | 0.00 | 10206.30 | 01-APR-15:09 | 4738.72 | 07-APR-18:10 | 0.00 |
May | 121608.77 | 31-MAY-15:09 | 0.00 | 0.00 | 10206.30 | 28-MAY-15:09 | 4738.57 | 05-MAY-18:10 | 0.00 |
June | 178865.03 | 19-JUN-16:00 | 0.00 | 0.00 | 10206.30 | 01-JUN-15:09 | 4738.15 | 29-JUN-18:10 | 0.00 |
July | 186770.45 | 20-JUL-19:00 | 0.00 | 0.00 | 10206.30 | 01-JUL-08:09 | 4738.50 | 06-JUL-06:10 | 0.00 |
August | 192130.39 | 16-AUG-15:20 | 0.00 | 0.00 | 10206.30 | 01-AUG-07:10 | 4738.43 | 15-AUG-18:19 | 0.00 |
September | 157132.40 | 07-SEP-18:10 | 0.00 | 0.00 | 10206.30 | 01-SEP-07:10 | 4738.30 | 08-SEP-06:10 | 0.00 |
October | 119299.58 | 05-OCT-15:09 | 0.00 | 0.00 | 10206.30 | 02-OCT-15:09 | 4738.74 | 04-OCT-18:10 | 0.00 |
November | 51681.40 | 04-NOV-11:50 | 0.00 | 0.00 | 10206.30 | 05-NOV-13:39 | 4738.09 | 08-NOV-07:49 | 0.00 |
December | 13756.71 | 17-DEC-14:00 | 0.00 | 0.00 | 10206.30 | 01-DEC-09:09 | 4738.45 | 15-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 5543.12 | 0.00 | 0.00 | 10206.30 | 4738.09 | 0.00 | |||
Maximum of Months | 192130.39 | 0.00 | 0.00 | 10206.30 | 4738.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 269302.07 | 23-JAN-20:30 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 26462.01 | 3348.22 | 0.00 | 1742.66 | 0.00 |
February | 265561.35 | 23-FEB-20:00 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 23244.01 | 3218.39 | 0.00 | 1392.58 | 0.00 |
March | 289667.21 | 27-MAR-18:10 | 59510.80 | 79417.81 | 14423.55 | 50574.86 | 20567.18 | 3131.60 | 0.00 | 54937.82 | 0.00 |
April | 339841.54 | 07-APR-19:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 22007.18 | 3515.41 | 0.00 | 86084.63 | 0.00 |
May | 362885.20 | 31-MAY-19:19 | 66976.13 | 88772.42 | 14423.55 | 50899.35 | 23442.92 | 3857.45 | 0.00 | 99343.09 | 0.00 |
June | 424479.66 | 19-JUN-19:30 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 25284.51 | 4134.24 | 0.00 | 157569.02 | 0.00 |
July | 456562.51 | 20-JUL-19:00 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 27736.22 | 4846.10 | 0.00 | 186770.45 | 0.00 |
August | 457808.91 | 03-AUG-19:00 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 26958.04 | 5206.68 | 0.00 | 188434.70 | 0.00 |
September | 412008.26 | 07-SEP-19:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 25494.56 | 4472.16 | 0.00 | 144709.51 | 0.00 |
October | 355348.20 | 05-OCT-19:10 | 66976.13 | 88772.42 | 14423.55 | 50891.06 | 21113.95 | 3701.67 | 0.00 | 94650.06 | 0.00 |
November | 276510.58 | 06-NOV-20:19 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 31031.17 | 3126.55 | 0.00 | 4694.61 | 0.00 |
December | 271026.44 | 04-DEC-20:40 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 28561.52 | 3264.35 | 0.00 | 1864.27 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 265561.35 | 59510.80 | 79417.81 | 14423.55 | 50574.86 | 20567.18 | 3126.55 | 0.00 | 1392.58 | 0.00 | |
Maximum of Months | 457808.91 | 66976.13 | 88772.42 | 14423.55 | 50900.13 | 31031.17 | 5206.68 | 0.00 | 188434.70 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 228902.50 | 02-JAN-09:09 | 0.00 | 178891.13 | 18-JAN-21:10 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 231070.53 | 06-FEB-07:10 | 0.00 | 177761.75 | 07-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 140050.87 | 25-MAR-21:00 | 0.00 | 178834.48 | 03-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 143557.15 | 12-APR-22:49 | 0.00 | 178106.95 | 14-APR-17:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 95465.50 | 01-MAY-00:00 | 0.00 | 175922.63 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 32461.21 | 10-JUN-10:50 | 0.00 | 174811.10 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 19125.08 | 01-JUL-01:30 | 0.00 | 173913.67 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 41113.21 | 30-AUG-15:50 | 0.00 | 173629.67 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 91153.81 | 24-SEP-05:30 | 0.00 | 174163.96 | 28-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 155785.87 | 18-OCT-22:19 | 0.00 | 177732.14 | 27-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 144790.61 | 26-NOV-23:49 | 0.00 | 178122.15 | 06-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 180456.80 | 31-DEC-23:00 | 0.00 | 178345.47 | 26-DEC-21:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 19125.08 | 0.00 | 173629.67 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 231070.53 | 0.00 | 178891.13 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.88 | 9.83 | 24.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.60 | 4.50 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 24.84 | 21.83 | 24.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 25.11 | 27.33 | 25.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.35 | 2.17 | 25.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.95 | 11.67 | 24.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 24.99 | 26.67 | 24.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.82 | 12.50 | 24.82 |
Annual Sum or Average | 0.00 | 0.00 | 116.50 | 24.95 | 116.50 | 24.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 25.35 | 27.33 | 25.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.49 | 1.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.54 | 0.50 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.51 | 2.00 | 20.51 | 3.00 | 21.75 | 3.00 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.55 | 1.17 | 20.55 | 1.17 | 21.83 | 1.17 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.49 | 2.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.50 | 1.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.17 | 20.50 | 4.17 | 20.50 | 1.17 | 21.72 | 1.17 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.54 | 2.33 | 20.54 | 0.33 | 21.79 | 0.33 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.23 | 2.33 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 20.33 | 2.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.82 | 6.67 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.78 | 4.00 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.46 | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.50 | 20.30 | 5.50 | 20.30 | 13.00 | 21.80 | 13.00 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.55 | 2.67 | 20.55 | 6.67 | 21.84 | 6.67 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.53 | 0.83 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.50 | 2.83 | 20.50 | 3.50 | 21.75 | 3.50 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.53 | 1.67 | 20.53 | 1.17 | 21.85 | 1.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.49 | 3.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.83 | 20.52 | 2.83 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.52 | 0.67 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.17 | 20.51 | 7.17 | 20.51 | 3.17 | 21.75 | 3.17 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.55 | 3.33 | 20.55 | 1.17 | 21.82 | 1.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.47 | 1.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.54 | 0.50 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.75 | 1.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.82 | 4.67 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.86 | 1.83 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.50 | 2.00 | 20.50 | 12.00 | 21.81 | 12.00 | 21.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.54 | 1.17 | 20.54 | 4.67 | 21.89 | 4.67 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.46 | 2.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.47 | 1.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.77 | 3.00 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 20.47 | 4.00 | 20.47 | 7.67 | 21.76 | 7.67 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.53 | 2.17 | 20.53 | 3.00 | 21.77 | 3.00 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.39 | 0.83 | 20.39 | 0.17 | 21.67 | 0.17 | 21.67 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.90 | 0.50 | 21.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.76 | 5.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.83 | 7.00 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.90 | 5.50 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.89 | 5.83 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
December | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.44 | 1.50 | 20.44 | 27.83 | 21.84 | 27.83 | 21.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.52 | 0.83 | 20.52 | 7.00 | 21.90 | 7.00 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.07 | 0.67 | 25.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.80 | 0.33 | 24.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.65 | 0.17 | 24.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.84 | 0.17 | 24.84 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 24.88 | 1.50 | 24.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.07 | 0.67 | 25.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.17 | 24.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.95 | 1.17 | 24.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.81 | 0.50 | 24.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.33 | 24.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.90 | 0.33 | 24.90 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 24.85 | 2.50 | 24.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.95 | 1.17 | 24.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.90 | 31.00 | 24.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.77 | 15.17 | 24.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 | 24.90 | 70.67 | 24.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 25.07 | 86.67 | 25.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 24.81 | 10.00 | 24.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.81 | 0.33 | 24.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 25.05 | 50.33 | 25.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 83.00 | 24.97 | 83.00 | 24.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 24.93 | 30.83 | 24.93 |
Annual Sum or Average | 0.00 | 0.00 | 378.00 | 24.97 | 378.00 | 24.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 25.07 | 86.67 | 25.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 23.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 672.00 | 22.84 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 744.00 | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.49 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.27 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.34 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 564.17 | 23.38 | 17.17 | 23.95 | 0.00 | 0.00 |
November | 452.67 | 23.77 | 10.00 | 23.92 | 0.00 | 0.00 |
December | 720.33 | 23.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8285.33 | 22.42 | 27.17 | 23.94 | 0.00 | |
Minimum of Months | 452.67 | 21.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.77 | 17.17 | 23.95 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.00 | 21.11 | 329.50 | 21.02 | 327.00 | 21.00 |
February | 651.50 | 21.15 | 294.50 | 21.00 | 294.50 | 21.00 |
March | 714.33 | 21.20 | 97.83 | 21.17 | 92.17 | 21.00 |
April | 707.67 | 21.22 | 18.83 | 22.00 | 12.00 | 21.00 |
May | 744.00 | 21.21 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 707.00 | 21.43 | 1.50 | 23.23 | 0.00 | 0.00 |
July | 656.67 | 21.74 | 21.17 | 23.21 | 0.00 | 0.00 |
August | 506.83 | 21.82 | 121.17 | 23.52 | 0.00 | 0.00 |
September | 598.50 | 21.49 | 68.33 | 23.77 | 0.00 | 0.00 |
October | 582.67 | 21.59 | 102.83 | 23.85 | 0.00 | 0.00 |
November | 680.33 | 21.21 | 86.83 | 21.45 | 73.67 | 21.00 |
December | 713.17 | 21.14 | 268.83 | 21.08 | 262.00 | 21.00 |
Annual Sum or Average | 7993.67 | 21.34 | 1411.33 | 21.67 | 1061.33 | 21.00 |
Minimum of Months | 506.83 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.82 | 329.50 | 23.85 | 327.00 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.48 | 26.67 | 21.00 | 26.67 | 21.00 |
February | 672.00 | 21.54 | 25.50 | 21.00 | 25.50 | 21.00 |
March | 744.00 | 21.93 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 712.33 | 21.98 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 714.33 | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 674.33 | 22.30 | 9.17 | 23.72 | 0.00 | 0.00 |
September | 702.33 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 709.33 | 22.47 | 3.00 | 23.64 | 0.00 | 0.00 |
November | 719.83 | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.71 | 1.17 | 21.00 | 1.17 | 21.00 |
Annual Sum or Average | 8600.50 | 21.97 | 65.50 | 21.50 | 53.33 | 21.00 |
Minimum of Months | 672.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.47 | 26.67 | 23.72 | 26.67 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.83 | 22.47 | 382.17 | 23.52 | 135.83 | 24.17 |
February | 284.50 | 22.43 | 305.67 | 23.68 | 115.67 | 24.14 |
March | 276.83 | 22.84 | 431.83 | 23.47 | 154.67 | 24.21 |
April | 272.00 | 22.95 | 445.83 | 23.29 | 163.00 | 24.20 |
May | 276.00 | 22.87 | 424.50 | 22.96 | 173.33 | 23.96 |
June | 206.17 | 23.11 | 420.33 | 22.49 | 149.17 | 23.91 |
July | 184.00 | 23.35 | 512.83 | 22.18 | 149.17 | 23.90 |
August | 187.50 | 23.39 | 540.67 | 22.17 | 155.17 | 23.89 |
September | 222.83 | 22.99 | 414.83 | 22.62 | 151.50 | 23.92 |
October | 253.67 | 23.06 | 487.00 | 22.94 | 171.50 | 24.02 |
November | 261.00 | 22.96 | 424.67 | 23.45 | 155.67 | 24.21 |
December | 276.50 | 22.64 | 377.50 | 23.60 | 135.67 | 24.18 |
Annual Sum or Average | 3029.83 | 22.88 | 5167.83 | 22.98 | 1810.33 | 24.06 |
Minimum of Months | 184.00 | 22.43 | 305.67 | 22.17 | 115.67 | 23.89 |
Maximum of Months | 328.83 | 23.39 | 540.67 | 23.68 | 173.33 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 713.83 | 21.51 | 81.67 | 21.36 | 71.83 | 21.00 |
February | 631.00 | 21.62 | 56.17 | 21.86 | 40.00 | 21.00 |
March | 682.17 | 21.98 | 26.33 | 23.90 | 0.00 | 0.00 |
April | 664.33 | 22.09 | 18.83 | 23.41 | 0.00 | 0.00 |
May | 698.33 | 22.11 | 14.17 | 23.11 | 6.50 | 22.85 |
June | 534.17 | 22.00 | 56.17 | 23.32 | 0.17 | 22.83 |
July | 360.17 | 22.05 | 205.33 | 23.29 | 0.00 | 0.00 |
August | 197.33 | 22.06 | 371.50 | 23.34 | 0.00 | 0.00 |
September | 381.50 | 22.09 | 201.67 | 23.44 | 1.50 | 22.87 |
October | 363.83 | 22.62 | 297.83 | 23.65 | 29.00 | 23.55 |
November | 620.17 | 21.98 | 45.83 | 23.81 | 1.17 | 22.66 |
December | 693.50 | 21.73 | 35.67 | 23.30 | 8.17 | 21.00 |
Annual Sum or Average | 6540.33 | 21.94 | 1411.17 | 23.26 | 158.33 | 21.58 |
Minimum of Months | 197.33 | 21.51 | 14.17 | 21.36 | 0.00 | 0.00 |
Maximum of Months | 713.83 | 22.62 | 371.50 | 23.90 | 71.83 | 23.55 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.00 | 4.17 | 21.00 | 4.17 | 21.00 |
February | 672.00 | 22.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 732.50 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 684.17 | 22.46 | 0.67 | 23.65 | 0.00 | 0.00 |
May | 688.00 | 22.32 | 3.33 | 23.62 | 0.00 | 0.00 |
June | 641.50 | 22.19 | 8.83 | 23.57 | 0.00 | 0.00 |
July | 585.67 | 22.23 | 45.83 | 23.58 | 0.00 | 0.00 |
August | 518.83 | 22.35 | 80.00 | 23.64 | 0.00 | 0.00 |
September | 607.00 | 22.34 | 27.67 | 23.62 | 0.00 | 0.00 |
October | 547.67 | 22.79 | 76.67 | 23.69 | 1.00 | 23.63 |
November | 676.67 | 22.52 | 6.17 | 23.88 | 0.00 | 0.00 |
December | 742.67 | 22.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7840.67 | 22.32 | 253.33 | 23.60 | 5.17 | 21.51 |
Minimum of Months | 518.83 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.79 | 80.00 | 23.88 | 4.17 | 23.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.74 | 590.67 | 20.62 | 590.67 | 20.62 |
February | 672.00 | 20.85 | 538.17 | 20.72 | 538.17 | 20.72 |
March | 744.00 | 21.09 | 254.17 | 20.69 | 254.17 | 20.69 |
April | 711.67 | 21.24 | 70.83 | 20.49 | 70.83 | 20.49 |
May | 730.83 | 21.45 | 1.50 | 22.94 | 0.00 | 0.00 |
June | 650.83 | 21.48 | 16.17 | 22.67 | 5.00 | 22.04 |
July | 628.17 | 21.43 | 36.33 | 22.82 | 9.83 | 22.23 |
August | 620.67 | 21.41 | 28.17 | 22.97 | 3.50 | 22.24 |
September | 665.17 | 21.46 | 10.50 | 22.41 | 5.00 | 21.57 |
October | 703.00 | 21.42 | 19.67 | 21.74 | 12.33 | 20.89 |
November | 720.00 | 21.04 | 261.67 | 20.71 | 261.67 | 20.71 |
December | 744.00 | 20.84 | 557.33 | 20.70 | 557.33 | 20.70 |
Annual Sum or Average | 8334.33 | 21.19 | 2385.17 | 20.77 | 2308.50 | 20.69 |
Minimum of Months | 620.67 | 20.74 | 1.50 | 20.49 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.48 | 590.67 | 22.97 | 590.67 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 673.00 | 20.52 | 673.00 | 20.52 |
February | 672.00 | 20.61 | 638.83 | 20.58 | 638.83 | 20.58 |
March | 744.00 | 20.88 | 355.33 | 20.58 | 355.33 | 20.58 |
April | 717.17 | 21.15 | 103.17 | 20.51 | 103.17 | 20.51 |
May | 734.00 | 21.43 | 0.67 | 22.89 | 0.00 | 0.00 |
June | 657.67 | 21.49 | 12.67 | 22.63 | 4.33 | 22.05 |
July | 640.33 | 21.46 | 33.17 | 22.79 | 10.17 | 22.22 |
August | 650.00 | 21.48 | 22.17 | 22.92 | 3.67 | 22.27 |
September | 694.33 | 21.45 | 7.33 | 22.15 | 4.50 | 21.60 |
October | 732.83 | 21.27 | 56.67 | 20.86 | 56.67 | 20.86 |
November | 720.00 | 20.81 | 365.83 | 20.55 | 365.83 | 20.55 |
December | 744.00 | 20.61 | 695.17 | 20.58 | 695.17 | 20.58 |
Annual Sum or Average | 8450.33 | 21.09 | 2964.00 | 20.62 | 2910.67 | 20.57 |
Minimum of Months | 640.33 | 20.57 | 0.67 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.49 | 695.17 | 22.92 | 695.17 | 22.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 491.67 | 20.68 | 491.67 | 20.68 |
February | 672.00 | 20.80 | 530.17 | 20.72 | 530.17 | 20.72 |
March | 744.00 | 21.01 | 209.50 | 20.80 | 209.50 | 20.80 |
April | 720.00 | 21.18 | 14.00 | 20.94 | 14.00 | 20.94 |
May | 744.00 | 21.35 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.46 | 13.50 | 22.00 | 13.50 | 22.00 |
July | 744.00 | 21.57 | 30.83 | 22.06 | 30.83 | 22.06 |
August | 744.00 | 21.53 | 11.50 | 22.08 | 11.50 | 22.08 |
September | 720.00 | 21.36 | 8.33 | 21.80 | 8.33 | 21.80 |
October | 744.00 | 21.22 | 1.83 | 21.09 | 1.83 | 21.09 |
November | 720.00 | 21.02 | 164.17 | 20.72 | 164.17 | 20.72 |
December | 744.00 | 20.86 | 461.83 | 20.72 | 461.83 | 20.72 |
Annual Sum or Average | 8760.00 | 21.18 | 1937.33 | 20.76 | 1937.33 | 20.76 |
Minimum of Months | 672.00 | 20.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.57 | 530.17 | 22.08 | 530.17 | 22.08 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.74 | 582.17 | 20.63 | 582.17 | 20.63 |
February | 672.00 | 20.87 | 524.83 | 20.75 | 524.83 | 20.75 |
March | 744.00 | 21.13 | 245.50 | 20.73 | 245.50 | 20.73 |
April | 714.00 | 21.31 | 72.67 | 20.55 | 72.67 | 20.55 |
May | 725.67 | 21.51 | 0.33 | 22.48 | 0.00 | 0.00 |
June | 661.50 | 21.53 | 7.17 | 22.32 | 5.00 | 22.17 |
July | 605.17 | 21.38 | 16.00 | 22.51 | 9.83 | 22.32 |
August | 596.67 | 21.37 | 10.00 | 22.69 | 2.83 | 22.28 |
September | 671.17 | 21.51 | 8.33 | 21.92 | 6.33 | 21.65 |
October | 703.67 | 21.47 | 11.33 | 21.12 | 11.00 | 21.10 |
November | 720.00 | 21.07 | 238.67 | 20.71 | 238.67 | 20.71 |
December | 744.00 | 20.85 | 547.33 | 20.71 | 547.33 | 20.71 |
Annual Sum or Average | 8301.83 | 21.22 | 2264.33 | 20.73 | 2246.17 | 20.71 |
Minimum of Months | 596.67 | 20.74 | 0.33 | 20.55 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.53 | 582.17 | 22.69 | 582.17 | 22.32 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 663.17 | 20.51 | 663.17 | 20.51 |
February | 672.00 | 20.62 | 634.17 | 20.59 | 634.17 | 20.59 |
March | 744.00 | 20.92 | 332.83 | 20.65 | 332.83 | 20.65 |
April | 719.00 | 21.23 | 98.67 | 20.59 | 98.67 | 20.59 |
May | 728.17 | 21.50 | 0.33 | 22.48 | 0.00 | 0.00 |
June | 673.17 | 21.56 | 7.17 | 22.31 | 4.83 | 22.11 |
July | 615.67 | 21.41 | 16.33 | 22.56 | 9.67 | 22.32 |
August | 641.33 | 21.49 | 9.67 | 22.69 | 3.17 | 22.37 |
September | 702.83 | 21.53 | 7.67 | 21.92 | 5.83 | 21.68 |
October | 743.17 | 21.35 | 53.33 | 21.01 | 53.33 | 21.01 |
November | 720.00 | 20.85 | 326.33 | 20.56 | 326.33 | 20.56 |
December | 744.00 | 20.61 | 679.83 | 20.57 | 679.83 | 20.57 |
Annual Sum or Average | 8447.33 | 21.13 | 2829.50 | 20.61 | 2811.83 | 20.59 |
Minimum of Months | 615.67 | 20.57 | 0.33 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.56 | 679.83 | 22.69 | 679.83 | 22.37 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 663.00 | 20.59 | 663.00 | 20.59 |
February | 672.00 | 20.77 | 591.67 | 20.68 | 591.67 | 20.68 |
March | 744.00 | 21.04 | 320.00 | 20.65 | 320.00 | 20.65 |
April | 703.83 | 21.20 | 141.17 | 20.65 | 140.00 | 20.63 |
May | 708.17 | 21.44 | 6.33 | 22.52 | 1.83 | 21.11 |
June | 612.00 | 21.41 | 42.67 | 22.73 | 12.00 | 21.85 |
July | 592.00 | 21.34 | 72.50 | 22.95 | 16.17 | 22.27 |
August | 585.83 | 21.32 | 67.17 | 23.11 | 5.33 | 22.40 |
September | 636.00 | 21.40 | 29.17 | 22.65 | 8.50 | 21.51 |
October | 688.83 | 21.37 | 78.00 | 21.41 | 62.17 | 20.96 |
November | 720.00 | 20.96 | 360.83 | 20.66 | 360.83 | 20.66 |
December | 744.00 | 20.76 | 633.67 | 20.66 | 633.67 | 20.66 |
Annual Sum or Average | 8150.67 | 21.12 | 3006.17 | 20.83 | 2815.17 | 20.67 |
Minimum of Months | 585.83 | 20.66 | 6.33 | 20.59 | 1.83 | 20.59 |
Maximum of Months | 744.00 | 21.44 | 663.00 | 23.11 | 663.00 | 22.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 709.50 | 20.49 | 709.50 | 20.49 |
February | 672.00 | 20.55 | 654.00 | 20.54 | 654.00 | 20.54 |
March | 744.00 | 20.82 | 427.33 | 20.55 | 427.33 | 20.55 |
April | 712.17 | 21.12 | 179.33 | 20.64 | 179.33 | 20.64 |
May | 716.00 | 21.43 | 7.83 | 22.15 | 3.67 | 21.11 |
June | 617.83 | 21.42 | 39.00 | 22.71 | 11.17 | 21.81 |
July | 596.33 | 21.35 | 64.17 | 22.92 | 15.83 | 22.28 |
August | 607.50 | 21.38 | 50.33 | 23.03 | 5.50 | 22.25 |
September | 668.50 | 21.43 | 19.00 | 22.36 | 8.50 | 21.51 |
October | 726.33 | 21.26 | 112.33 | 20.90 | 110.33 | 20.87 |
November | 720.00 | 20.74 | 451.67 | 20.53 | 451.67 | 20.53 |
December | 744.00 | 20.54 | 728.17 | 20.53 | 728.17 | 20.53 |
Annual Sum or Average | 8268.67 | 21.03 | 3442.67 | 20.66 | 3305.00 | 20.56 |
Minimum of Months | 596.33 | 20.52 | 7.83 | 20.49 | 3.67 | 20.49 |
Maximum of Months | 744.00 | 21.43 | 728.17 | 23.03 | 728.17 | 22.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.00 | 21.04 | 424.83 | 20.73 | 424.83 | 20.73 |
February | 672.00 | 21.23 | 369.00 | 20.84 | 369.00 | 20.84 |
March | 732.50 | 21.26 | 175.17 | 20.78 | 175.17 | 20.78 |
April | 704.83 | 21.32 | 51.83 | 20.64 | 51.50 | 20.62 |
May | 733.17 | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 653.67 | 21.49 | 18.50 | 22.15 | 18.50 | 22.15 |
July | 630.00 | 21.44 | 32.33 | 22.29 | 32.33 | 22.29 |
August | 614.50 | 21.39 | 14.67 | 22.27 | 13.83 | 22.21 |
September | 621.00 | 21.38 | 29.83 | 22.91 | 8.83 | 21.91 |
October | 646.00 | 21.36 | 43.33 | 23.25 | 1.17 | 21.45 |
November | 704.00 | 21.31 | 132.17 | 20.89 | 132.17 | 20.89 |
December | 736.67 | 21.15 | 373.83 | 20.78 | 373.83 | 20.78 |
Annual Sum or Average | 8187.33 | 21.32 | 1665.50 | 20.95 | 1601.17 | 20.85 |
Minimum of Months | 614.50 | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.00 | 21.50 | 424.83 | 23.25 | 424.83 | 22.29 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 560.33 | 22.95 | 15.50 | 23.97 | 0.00 | 0.00 |
February | 535.00 | 22.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 368.50 | 23.02 | 83.67 | 23.99 | 0.00 | 0.00 |
April | 245.17 | 22.89 | 233.50 | 23.93 | 1.67 | 23.99 |
May | 198.00 | 22.80 | 385.67 | 23.88 | 37.00 | 23.99 |
June | 124.33 | 22.93 | 511.83 | 23.76 | 45.83 | 23.97 |
July | 12.33 | 22.33 | 615.50 | 23.70 | 0.00 | 0.00 |
August | 31.33 | 22.75 | 595.67 | 23.73 | 6.50 | 23.99 |
September | 177.67 | 22.61 | 414.33 | 23.80 | 28.83 | 23.96 |
October | 312.17 | 22.97 | 271.67 | 23.86 | 59.67 | 23.97 |
November | 367.83 | 22.96 | 99.00 | 23.96 | 5.50 | 23.97 |
December | 490.83 | 22.97 | 9.67 | 24.02 | 0.00 | 0.00 |
Annual Sum or Average | 3423.50 | 22.93 | 3236.00 | 23.80 | 185.00 | 23.97 |
Minimum of Months | 12.33 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 560.33 | 23.02 | 615.50 | 24.02 | 59.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 401.50 | 23.02 | 67.00 | 23.98 | 0.00 | 0.00 |
February | 406.33 | 23.09 | 18.17 | 23.99 | 0.00 | 0.00 |
March | 185.00 | 23.02 | 210.50 | 23.97 | 0.00 | 0.00 |
April | 97.33 | 23.00 | 357.17 | 23.92 | 0.33 | 24.00 |
May | 63.00 | 23.20 | 532.50 | 23.85 | 23.67 | 23.99 |
June | 26.83 | 23.07 | 603.33 | 23.73 | 11.33 | 23.99 |
July | 0.67 | 22.36 | 717.83 | 23.67 | 0.00 | 0.00 |
August | 1.17 | 23.99 | 683.17 | 23.70 | 1.17 | 23.99 |
September | 81.67 | 22.82 | 518.50 | 23.77 | 19.17 | 23.99 |
October | 153.33 | 23.16 | 361.83 | 23.83 | 43.00 | 23.99 |
November | 210.00 | 23.01 | 221.83 | 23.96 | 4.50 | 23.99 |
December | 341.00 | 23.03 | 50.17 | 23.99 | 0.00 | 0.00 |
Annual Sum or Average | 1967.83 | 23.04 | 4342.00 | 23.79 | 103.17 | 23.99 |
Minimum of Months | 0.67 | 22.36 | 18.17 | 23.67 | 0.00 | 0.00 |
Maximum of Months | 406.33 | 23.99 | 717.83 | 23.99 | 43.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 551.67 | 23.83 | 603.50 | 24.01 | 478.17 | 24.11 |
February | 509.17 | 23.76 | 533.00 | 24.02 | 430.00 | 24.08 |
March | 533.50 | 24.11 | 652.83 | 24.02 | 511.00 | 24.20 |
April | 515.33 | 24.22 | 670.00 | 23.97 | 514.33 | 24.23 |
May | 547.17 | 24.02 | 718.00 | 23.74 | 547.17 | 24.02 |
June | 532.33 | 23.98 | 688.50 | 23.57 | 532.00 | 23.98 |
July | 549.67 | 23.98 | 713.17 | 23.52 | 549.67 | 23.98 |
August | 550.50 | 23.98 | 720.67 | 23.53 | 550.50 | 23.98 |
September | 525.50 | 23.98 | 686.83 | 23.61 | 525.50 | 23.98 |
October | 535.67 | 24.11 | 704.17 | 23.83 | 534.50 | 24.11 |
November | 518.17 | 24.14 | 637.50 | 24.02 | 498.33 | 24.22 |
December | 539.00 | 23.94 | 613.00 | 24.02 | 491.00 | 24.12 |
Annual Sum or Average | 6407.67 | 24.01 | 7941.17 | 23.81 | 6162.17 | 24.08 |
Minimum of Months | 509.17 | 23.76 | 533.00 | 23.52 | 430.00 | 23.98 |
Maximum of Months | 551.67 | 24.22 | 720.67 | 24.02 | 550.50 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.25422 | 27.20832 | 0.07072 | 5.30752 |
February | 672.00000 | 22.84413 | 23.52820 | -0.0582 | 5.24657 |
March | 744.00000 | 22.50760 | 33.04444 | -0.0826 | 5.32484 |
April | 720.00000 | 22.08639 | 40.45685 | -0.1394 | 5.63978 |
May | 744.00000 | 21.49039 | 49.22548 | -1.3872 | 44.96177 |
June | 720.00000 | 21.27308 | 56.58192 | -1.4036 | 45.76369 |
July | 744.00000 | 21.33872 | 58.56190 | -1.3561 | 43.26014 |
August | 744.00000 | 21.76546 | 56.03180 | -1.2155 | 36.14984 |
September | 720.00000 | 22.42506 | 51.39081 | -1.0133 | 27.02223 |
October | 744.00000 | 23.46640 | 42.05326 | 0.24045 | 6.42013 |
November | 720.00000 | 23.82916 | 32.84066 | 0.26466 | 6.57095 |
December | 744.00000 | 23.67873 | 26.56246 | 0.17812 | 5.76602 |
Annual Sum or Average | 8760.00000 | 22.49478 | 41.56223 | -0.4945 | 19.88959 |
Minimum of Months | 672.00000 | 21.27308 | 23.52820 | -1.4036 | 5.24657 |
Maximum of Months | 744.00000 | 23.82916 | 58.56190 | 0.26466 | 45.76369 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15246 | 28.45299 | -0.4796 | 10.64583 |
February | 672.00000 | 21.22592 | 23.66224 | -0.4629 | 10.52857 |
March | 744.00000 | 21.30502 | 33.63446 | -0.3431 | 8.50052 |
April | 720.00000 | 21.26076 | 40.94352 | -0.2859 | 7.45263 |
May | 744.00000 | 21.21403 | 49.10123 | -1.3519 | 43.27100 |
June | 720.00000 | 21.45869 | 56.97590 | -1.1603 | 34.00940 |
July | 744.00000 | 21.88054 | 59.46872 | -0.9722 | 25.98120 |
August | 744.00000 | 22.27682 | 55.85550 | -0.8444 | 21.92696 |
September | 720.00000 | 21.82068 | 53.20863 | -1.0547 | 30.88191 |
October | 744.00000 | 22.05558 | 44.49030 | 0.01132 | 7.18733 |
November | 720.00000 | 21.34813 | 36.02952 | -0.3120 | 8.26762 |
December | 744.00000 | 21.24890 | 28.35821 | -0.4253 | 9.89440 |
Annual Sum or Average | 8760.00000 | 21.52358 | 42.62322 | -0.6408 | 18.25417 |
Minimum of Months | 672.00000 | 21.15246 | 23.66224 | -1.3519 | 7.18733 |
Maximum of Months | 744.00000 | 22.27682 | 59.46872 | 0.01132 | 43.27100 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.47641 | 30.08445 | -0.3297 | 7.68755 |
February | 672.00000 | 21.54404 | 25.42623 | -0.3371 | 7.73114 |
March | 744.00000 | 21.93047 | 34.56477 | -0.1779 | 6.09598 |
April | 720.00000 | 22.05139 | 41.14873 | -0.0992 | 5.66598 |
May | 744.00000 | 21.99848 | 48.70401 | -1.1346 | 32.67379 |
June | 720.00000 | 21.99160 | 55.74577 | -1.0677 | 29.59731 |
July | 744.00000 | 22.17004 | 57.78962 | -0.9826 | 25.93389 |
August | 744.00000 | 22.41028 | 55.56994 | -0.9091 | 23.04396 |
September | 720.00000 | 22.13216 | 53.25862 | -1.0368 | 28.29228 |
October | 744.00000 | 22.51718 | 45.03188 | 0.05984 | 5.45335 |
November | 720.00000 | 22.02100 | 36.70691 | -0.1408 | 5.94241 |
December | 744.00000 | 21.71360 | 29.80510 | -0.2670 | 6.81174 |
Annual Sum or Average | 8760.00000 | 21.99953 | 42.91994 | -0.5363 | 15.45238 |
Minimum of Months | 672.00000 | 21.47641 | 25.42623 | -1.1346 | 5.45335 |
Maximum of Months | 744.00000 | 22.51718 | 57.78962 | 0.05984 | 32.67379 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59346 | 24.57168 | 0.49997 | 13.63452 |
February | 672.00000 | 22.58491 | 20.31155 | 0.47296 | 13.01606 |
March | 744.00000 | 22.67218 | 29.28891 | 0.57814 | 15.44133 |
April | 720.00000 | 22.54086 | 36.21480 | 0.60877 | 16.28380 |
May | 744.00000 | 22.16167 | 44.19332 | -0.2056 | 13.21944 |
June | 720.00000 | 21.87148 | 51.64396 | -0.2277 | 13.27863 |
July | 744.00000 | 21.81063 | 54.09080 | -0.2178 | 12.90909 |
August | 744.00000 | 21.85063 | 52.68861 | -0.2025 | 12.93871 |
September | 720.00000 | 21.94876 | 49.51957 | -0.2240 | 13.13721 |
October | 744.00000 | 22.35163 | 41.42129 | 0.61883 | 16.47323 |
November | 720.00000 | 22.66395 | 31.57357 | 0.59331 | 15.79424 |
December | 744.00000 | 22.64550 | 24.53386 | 0.52331 | 13.94761 |
Annual Sum or Average | 8760.00000 | 22.30626 | 38.44308 | 0.23337 | 14.17739 |
Minimum of Months | 672.00000 | 21.81063 | 20.31155 | -0.2277 | 12.90909 |
Maximum of Months | 744.00000 | 22.67218 | 54.09080 | 0.61883 | 16.47323 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59449 | 33.62915 | -0.2735 | 7.67722 |
February | 672.00000 | 21.74450 | 28.89490 | -0.2407 | 7.46344 |
March | 744.00000 | 22.11544 | 38.15428 | -0.0686 | 6.28799 |
April | 720.00000 | 22.17415 | 44.80776 | 0.00262 | 5.94052 |
May | 744.00000 | 22.17398 | 52.32394 | -0.9566 | 25.11412 |
June | 720.00000 | 22.26717 | 59.52049 | -0.8185 | 19.98065 |
July | 744.00000 | 22.55542 | 61.72987 | -0.6724 | 15.24340 |
August | 744.00000 | 22.87758 | 58.99596 | -0.5622 | 12.52220 |
September | 720.00000 | 22.63525 | 56.26343 | -0.7007 | 17.10500 |
October | 744.00000 | 23.09002 | 47.80286 | 0.32445 | 8.42923 |
November | 720.00000 | 22.20234 | 40.19346 | -0.0274 | 6.43550 |
December | 744.00000 | 21.86379 | 33.28958 | -0.1848 | 7.00337 |
Annual Sum or Average | 8760.00000 | 22.27837 | 46.40084 | -0.3487 | 11.62584 |
Minimum of Months | 672.00000 | 21.59449 | 28.89490 | -0.9566 | 5.94052 |
Maximum of Months | 744.00000 | 23.09002 | 61.72987 | 0.32445 | 25.11412 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.99917 | 32.35596 | -0.1747 | 6.26584 |
February | 672.00000 | 22.08396 | 27.80282 | -0.1759 | 6.18778 |
March | 744.00000 | 22.45068 | 36.77038 | -0.0205 | 5.58086 |
April | 720.00000 | 22.51480 | 43.26028 | 0.04602 | 5.64546 |
May | 744.00000 | 22.40414 | 50.76664 | -0.9525 | 25.12215 |
June | 720.00000 | 22.30822 | 57.97851 | -0.9083 | 23.28501 |
July | 744.00000 | 22.45791 | 60.17745 | -0.8280 | 20.21687 |
August | 744.00000 | 22.65797 | 58.06397 | -0.7667 | 18.10797 |
September | 720.00000 | 22.50800 | 55.35353 | -0.8556 | 21.25320 |
October | 744.00000 | 22.98395 | 47.09781 | 0.21642 | 6.39343 |
November | 720.00000 | 22.59301 | 38.72481 | 0.03144 | 5.68595 |
December | 744.00000 | 22.28168 | 32.01538 | -0.0993 | 5.75919 |
Annual Sum or Average | 8760.00000 | 22.43938 | 45.13060 | -0.3751 | 12.49365 |
Minimum of Months | 672.00000 | 21.99917 | 27.80282 | -0.9525 | 5.58086 |
Maximum of Months | 744.00000 | 22.98395 | 60.17745 | 0.21642 | 25.12215 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74211 | 32.74707 | -0.6401 | 14.18193 |
February | 672.00000 | 20.85067 | 27.39827 | -0.6284 | 13.90373 |
March | 744.00000 | 21.08984 | 37.89134 | -0.4529 | 9.98286 |
April | 720.00000 | 21.25680 | 45.26039 | -0.3303 | 8.12954 |
May | 744.00000 | 21.48161 | 52.74024 | -1.3218 | 42.20199 |
June | 720.00000 | 21.64149 | 58.95345 | -1.1548 | 34.39478 |
July | 744.00000 | 21.70236 | 60.90473 | -1.0917 | 31.68834 |
August | 744.00000 | 21.70406 | 57.30610 | -1.0954 | 31.95863 |
September | 720.00000 | 21.59294 | 57.03860 | -1.2156 | 37.32485 |
October | 744.00000 | 21.51728 | 49.81406 | -0.1899 | 6.88773 |
November | 720.00000 | 21.03811 | 41.11450 | -0.4672 | 10.22067 |
December | 744.00000 | 20.83934 | 32.76259 | -0.5994 | 13.06858 |
Annual Sum or Average | 8760.00000 | 21.29061 | 46.26660 | -0.7665 | 21.20677 |
Minimum of Months | 672.00000 | 20.74211 | 27.39827 | -1.3218 | 6.88773 |
Maximum of Months | 744.00000 | 21.70406 | 60.90473 | -0.1899 | 42.20199 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57036 | 33.01284 | -0.7021 | 15.95664 |
February | 672.00000 | 20.60971 | 27.71983 | -0.7153 | 16.29807 |
March | 744.00000 | 20.87807 | 38.25570 | -0.5242 | 11.29066 |
April | 720.00000 | 21.15456 | 45.54694 | -0.3662 | 8.51405 |
May | 744.00000 | 21.45001 | 52.84942 | -1.3384 | 42.96731 |
June | 720.00000 | 21.63287 | 59.02719 | -1.1617 | 34.66281 |
July | 744.00000 | 21.69898 | 61.10712 | -1.0979 | 31.91539 |
August | 744.00000 | 21.68915 | 57.87759 | -1.1156 | 32.72260 |
September | 720.00000 | 21.50778 | 57.85483 | -1.2674 | 39.52639 |
October | 744.00000 | 21.29744 | 51.30981 | -0.2707 | 7.33927 |
November | 720.00000 | 20.81233 | 41.59636 | -0.5446 | 11.77896 |
December | 744.00000 | 20.60825 | 33.13871 | -0.6788 | 15.12439 |
Annual Sum or Average | 8760.00000 | 21.16235 | 46.71507 | -0.8158 | 22.37703 |
Minimum of Months | 672.00000 | 20.57036 | 27.71983 | -1.3384 | 7.33927 |
Maximum of Months | 744.00000 | 21.69898 | 61.10712 | -0.2707 | 42.96731 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.81028 | 31.38608 | -0.5928 | 12.77085 |
February | 672.00000 | 20.80190 | 26.25675 | -0.6258 | 13.55030 |
March | 744.00000 | 21.00780 | 36.71517 | -0.4822 | 10.06640 |
April | 720.00000 | 21.18325 | 43.94978 | -0.3655 | 7.99592 |
May | 744.00000 | 21.34913 | 50.79800 | -1.4193 | 46.67613 |
June | 720.00000 | 21.46280 | 58.61469 | -1.2986 | 40.55785 |
July | 744.00000 | 21.57242 | 61.37756 | -1.2302 | 37.32676 |
August | 744.00000 | 21.53023 | 58.19138 | -1.2702 | 39.22790 |
September | 720.00000 | 21.36118 | 56.40243 | -1.3724 | 44.23151 |
October | 744.00000 | 21.21560 | 49.75653 | -0.3133 | 7.34290 |
November | 720.00000 | 21.01866 | 39.82480 | -0.4608 | 9.71491 |
December | 744.00000 | 20.85958 | 31.50494 | -0.5737 | 12.10693 |
Annual Sum or Average | 8760.00000 | 21.18336 | 45.50838 | -0.8350 | 23.52183 |
Minimum of Months | 672.00000 | 20.80190 | 26.25675 | -1.4193 | 7.34290 |
Maximum of Months | 744.00000 | 21.57242 | 61.37756 | -0.3133 | 46.67613 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74186 | 32.72916 | -0.6383 | 14.09531 |
February | 672.00000 | 20.86935 | 27.35434 | -0.6206 | 13.63482 |
March | 744.00000 | 21.13108 | 37.84857 | -0.4480 | 9.88109 |
April | 720.00000 | 21.32874 | 45.03490 | -0.3134 | 8.00710 |
May | 744.00000 | 21.55198 | 52.45948 | -1.2956 | 41.02428 |
June | 720.00000 | 21.66808 | 59.13265 | -1.1552 | 34.37635 |
July | 744.00000 | 21.72368 | 60.76246 | -1.0879 | 31.51936 |
August | 744.00000 | 21.73352 | 57.10305 | -1.0877 | 31.62276 |
September | 720.00000 | 21.62731 | 56.81963 | -1.2030 | 36.75024 |
October | 744.00000 | 21.56347 | 49.74238 | -0.1827 | 6.84091 |
November | 720.00000 | 21.07410 | 41.01463 | -0.4520 | 9.97593 |
December | 744.00000 | 20.84608 | 32.74231 | -0.5947 | 12.93908 |
Annual Sum or Average | 8760.00000 | 21.32419 | 46.16708 | -0.7574 | 20.93334 |
Minimum of Months | 672.00000 | 20.74186 | 27.35434 | -1.2956 | 6.84091 |
Maximum of Months | 744.00000 | 21.73352 | 60.76246 | -0.1827 | 41.02428 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57070 | 32.99242 | -0.7005 | 15.92768 |
February | 672.00000 | 20.61998 | 27.67352 | -0.7090 | 16.11344 |
March | 744.00000 | 20.91633 | 38.19173 | -0.5202 | 11.09922 |
April | 720.00000 | 21.23433 | 45.28050 | -0.3477 | 8.30986 |
May | 744.00000 | 21.52877 | 52.54666 | -1.3101 | 41.66602 |
June | 720.00000 | 21.66274 | 59.21563 | -1.1613 | 34.61240 |
July | 744.00000 | 21.72147 | 60.97165 | -1.0937 | 31.73861 |
August | 744.00000 | 21.72797 | 57.59784 | -1.1053 | 32.29192 |
September | 720.00000 | 21.57123 | 57.48585 | -1.2470 | 38.57311 |
October | 744.00000 | 21.34603 | 50.94595 | -0.2650 | 7.22829 |
November | 720.00000 | 20.85143 | 41.49191 | -0.5276 | 11.40932 |
December | 744.00000 | 20.61167 | 33.11335 | -0.6744 | 15.03982 |
Annual Sum or Average | 8760.00000 | 21.20017 | 46.56499 | -0.8058 | 22.03577 |
Minimum of Months | 672.00000 | 20.57070 | 27.67352 | -1.3101 | 7.22829 |
Maximum of Months | 744.00000 | 21.72797 | 60.97165 | -0.2650 | 41.66602 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.66333 | 33.19542 | -0.6952 | 15.81619 |
February | 672.00000 | 20.77270 | 27.73733 | -0.6832 | 15.51984 |
March | 744.00000 | 21.03620 | 38.40397 | -0.4857 | 10.84394 |
April | 720.00000 | 21.24390 | 45.72902 | -0.3408 | 8.57358 |
May | 744.00000 | 21.51845 | 53.12958 | -1.2966 | 41.25294 |
June | 720.00000 | 21.67383 | 58.76386 | -1.1143 | 32.85264 |
July | 744.00000 | 21.72032 | 60.27118 | -1.0509 | 30.17009 |
August | 744.00000 | 21.71985 | 56.90713 | -1.0569 | 30.56781 |
September | 720.00000 | 21.61419 | 57.21198 | -1.1889 | 36.34782 |
October | 744.00000 | 21.51083 | 50.32016 | -0.1922 | 7.13880 |
November | 720.00000 | 20.96261 | 41.70739 | -0.5088 | 11.26875 |
December | 744.00000 | 20.75620 | 33.21765 | -0.6528 | 14.55702 |
Annual Sum or Average | 8760.00000 | 21.26891 | 46.48715 | -0.7728 | 21.27833 |
Minimum of Months | 672.00000 | 20.66333 | 27.73733 | -1.2966 | 7.13880 |
Maximum of Months | 744.00000 | 21.72032 | 60.27118 | -0.1922 | 41.25294 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51804 | 33.44182 | -0.7539 | 17.61814 |
February | 672.00000 | 20.55415 | 28.05278 | -0.7680 | 18.00774 |
March | 744.00000 | 20.81770 | 38.79414 | -0.5611 | 12.29154 |
April | 720.00000 | 21.14542 | 46.02028 | -0.3773 | 8.96159 |
May | 744.00000 | 21.49465 | 53.22091 | -1.3117 | 41.90890 |
June | 720.00000 | 21.67082 | 58.81139 | -1.1195 | 33.04072 |
July | 744.00000 | 21.71903 | 60.44078 | -1.0563 | 30.35422 |
August | 744.00000 | 21.71007 | 57.42718 | -1.0758 | 31.24481 |
September | 720.00000 | 21.55356 | 57.99276 | -1.2354 | 38.24864 |
October | 744.00000 | 21.29993 | 51.87999 | -0.2748 | 7.64731 |
November | 720.00000 | 20.73873 | 42.21635 | -0.5888 | 12.97242 |
December | 744.00000 | 20.53987 | 33.59338 | -0.7316 | 16.76672 |
Annual Sum or Average | 8760.00000 | 21.15027 | 46.92999 | -0.8215 | 22.44849 |
Minimum of Months | 672.00000 | 20.51804 | 28.05278 | -1.3117 | 7.64731 |
Maximum of Months | 744.00000 | 21.71903 | 60.44078 | -0.2748 | 41.90890 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05913 | 33.64169 | -0.5272 | 11.93745 |
February | 672.00000 | 21.23403 | 28.42411 | -0.4896 | 11.32487 |
March | 744.00000 | 21.28747 | 38.64156 | -0.3868 | 9.22206 |
April | 720.00000 | 21.36493 | 45.71123 | -0.3048 | 7.91375 |
May | 744.00000 | 21.52418 | 52.62237 | -1.3297 | 42.65697 |
June | 720.00000 | 21.64804 | 59.08107 | -1.1801 | 35.55888 |
July | 744.00000 | 21.71892 | 60.85699 | -1.1059 | 32.31902 |
August | 744.00000 | 21.72052 | 56.91122 | -1.1086 | 32.62610 |
September | 720.00000 | 21.64177 | 55.87760 | -1.1862 | 36.27619 |
October | 744.00000 | 21.61406 | 49.14786 | -0.1337 | 6.83318 |
November | 720.00000 | 21.35720 | 41.59499 | -0.3463 | 8.56039 |
December | 744.00000 | 21.16850 | 33.56318 | -0.4746 | 10.95551 |
Annual Sum or Average | 8760.00000 | 21.44599 | 46.44042 | -0.7159 | 20.57378 |
Minimum of Months | 672.00000 | 21.05913 | 28.42411 | -1.3297 | 6.83318 |
Maximum of Months | 744.00000 | 21.72052 | 60.85699 | -0.1337 | 42.65697 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.19281 | 33.01902 | 0.12683 | 6.20827 |
February | 672.00000 | 23.18836 | 28.92662 | 0.09790 | 5.99799 |
March | 744.00000 | 23.47193 | 36.97503 | 0.25468 | 6.88503 |
April | 720.00000 | 23.52780 | 42.86688 | 0.33795 | 7.82298 |
May | 744.00000 | 23.47601 | 49.75283 | -0.4988 | 10.95049 |
June | 720.00000 | 23.43973 | 56.33160 | -0.4168 | 9.35771 |
July | 744.00000 | 23.52217 | 58.19149 | -0.3515 | 8.07807 |
August | 744.00000 | 23.52143 | 56.97249 | -0.3637 | 8.30994 |
September | 720.00000 | 23.34030 | 54.86212 | -0.4897 | 10.91423 |
October | 744.00000 | 23.42584 | 47.70548 | 0.35973 | 8.26684 |
November | 720.00000 | 23.42536 | 39.07351 | 0.25622 | 6.98219 |
December | 744.00000 | 23.31311 | 32.78713 | 0.16328 | 6.20094 |
Annual Sum or Average | 8760.00000 | 23.40518 | 44.88076 | -0.0444 | 8.00587 |
Minimum of Months | 672.00000 | 23.18836 | 28.92662 | -0.4988 | 5.99799 |
Maximum of Months | 744.00000 | 23.52780 | 58.19149 | 0.35973 | 10.95049 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.43481 | 32.02827 | 0.22499 | 6.73335 |
February | 672.00000 | 23.42898 | 28.00887 | 0.19525 | 6.40719 |
March | 744.00000 | 23.65649 | 35.91064 | 0.33867 | 7.76792 |
April | 720.00000 | 23.69148 | 41.80775 | 0.41582 | 8.92209 |
May | 744.00000 | 23.62836 | 48.69595 | -0.3942 | 8.76387 |
June | 720.00000 | 23.56749 | 55.35730 | -0.3274 | 7.78005 |
July | 744.00000 | 23.62940 | 57.30434 | -0.2727 | 6.92357 |
August | 744.00000 | 23.62061 | 56.12219 | -0.2884 | 7.14763 |
September | 720.00000 | 23.48795 | 53.84687 | -0.3923 | 8.88629 |
October | 744.00000 | 23.57361 | 46.68023 | 0.43024 | 9.31123 |
November | 720.00000 | 23.61692 | 38.01846 | 0.34167 | 7.88129 |
December | 744.00000 | 23.52338 | 31.76039 | 0.25392 | 6.80422 |
Annual Sum or Average | 8760.00000 | 23.57258 | 43.88691 | 0.04293 | 7.78219 |
Minimum of Months | 672.00000 | 23.42898 | 28.00887 | -0.3942 | 6.40719 |
Maximum of Months | 744.00000 | 23.69148 | 57.30434 | 0.43024 | 9.31123 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.68054 | 30.57779 | 0.91301 | 25.98784 |
February | 672.00000 | 23.65303 | 26.64175 | 0.88542 | 24.97674 |
March | 744.00000 | 23.82672 | 34.56650 | 1.02582 | 30.24834 |
April | 720.00000 | 23.86444 | 40.67509 | 1.11278 | 33.93954 |
May | 744.00000 | 23.68925 | 47.63076 | 0.58107 | 18.63206 |
June | 720.00000 | 23.48676 | 54.38328 | 0.60761 | 20.94925 |
July | 744.00000 | 23.43257 | 56.58072 | 0.63514 | 22.25710 |
August | 744.00000 | 23.46537 | 55.28679 | 0.64230 | 22.22488 |
September | 720.00000 | 23.52260 | 52.62420 | 0.57957 | 19.78800 |
October | 744.00000 | 23.75779 | 45.37470 | 1.13850 | 35.06624 |
November | 720.00000 | 23.83726 | 36.72816 | 1.03675 | 30.68519 |
December | 744.00000 | 23.72687 | 30.41511 | 0.93714 | 26.54675 |
Annual Sum or Average | 8760.00000 | 23.66183 | 42.71697 | 0.84097 | 25.94539 |
Minimum of Months | 672.00000 | 23.43257 | 26.64175 | 0.57957 | 18.63206 |
Maximum of Months | 744.00000 | 23.86444 | 56.58072 | 1.13850 | 35.06624 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.119407E+10 | 9206.57 | 19-JAN-19:04 | 252.61 | 0.380483E+10 | 0.00 | 0.499890E+10 | 1.08 | 3.19 | 01-JAN-09:40 | 0.00 | 0.00 |
February | 0.146334E+10 | 12014.86 | 20-FEB-09:02 | 257.87 | 0.466283E+10 | 0.00 | 0.612617E+10 | 1.22 | 3.19 | 01-FEB-01:10 | 0.00 | 0.00 |
March | 0.576320E+10 | 81586.37 | 27-MAR-15:02 | 432.62 | 0.179550E+11 | 0.00 | 0.237182E+11 | 1.85 | 3.60 | 27-MAR-15:02 | 0.00 | 0.00 |
April | 0.265792E+11 | 103390.96 | 07-APR-15:03 | 544.79 | 0.801251E+11 | 0.00 | 0.106704E+12 | 2.37 | 3.57 | 16-APR-18:02 | 0.00 | 0.00 |
May | 0.835877E+11 | 125268.99 | 31-MAY-15:03 | 732.44 | 0.256546E+12 | 0.00 | 0.340134E+12 | 3.04 | 4.13 | 19-MAY-18:03 | 0.00 | 0.00 |
June | 0.232014E+12 | 185133.83 | 19-JUN-18:03 | 720.00 | 0.823411E+12 | 0.00 | 0.105543E+13 | 3.46 | 4.30 | 18-JUN-08:62 | 0.00 | 0.00 |
July | 0.326668E+12 | 186770.45 | 20-JUL-20:00 | 744.00 | 0.118245E+13 | 0.00 | 0.150912E+13 | 3.61 | 4.27 | 23-JUL-18:02 | 0.00 | 0.00 |
August | 0.291265E+12 | 199314.63 | 16-AUG-15:03 | 744.00 | 0.100066E+13 | 0.00 | 0.129193E+13 | 3.39 | 4.25 | 06-AUG-18:02 | 0.00 | 0.00 |
September | 0.176988E+12 | 163306.95 | 22-SEP-18:03 | 719.19 | 0.605583E+12 | 0.00 | 0.782571E+12 | 3.28 | 4.29 | 22-SEP-18:03 | 0.00 | 0.00 |
October | 0.808577E+11 | 128921.47 | 05-OCT-15:02 | 694.49 | 0.269762E+12 | 0.00 | 0.350620E+12 | 3.00 | 4.20 | 05-OCT-18:02 | 0.00 | 0.00 |
November | 0.731619E+10 | 55577.55 | 04-NOV-15:01 | 436.63 | 0.227341E+11 | 0.00 | 0.300503E+11 | 1.92 | 3.19 | 01-NOV-04:10 | 0.00 | 0.00 |
December | 0.245270E+10 | 15134.57 | 12-DEC-19:05 | 345.79 | 0.781538E+10 | 0.00 | 0.102681E+11 | 1.48 | 3.19 | 01-DEC-08:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123615E+13 | 6624.44 | 0.427551E+13 | 0.551166E+13 | 2.48 | |||||||
Minimum of Months | 0.119407E+10 | 9206.57 | 252.61 | 0.380483E+10 | 0.00 | 0.499890E+10 | 1.08 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.326668E+12 | 199314.63 | 744.00 | 0.118245E+13 | 0.00 | 0.150912E+13 | 3.61 | 4.30 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.123235E+12 | 0.00 | 744.00 | 192431.98 | 02-JAN-09:05 | 0.00 | 50.28 | 58.68 | 1.30 | 0.00 | 0.10 | 0.43 | 02-JAN-09:05 |
February | 0.110094E+12 | 0.00 | 672.00 | 191502.21 | 06-FEB-09:02 | 0.00 | 50.65 | 58.87 | 1.22 | 0.00 | 0.10 | 0.42 | 06-FEB-09:02 |
March | 0.467287E+11 | 0.00 | 731.27 | 128445.57 | 22-MAR-08:03 | 0.00 | 49.72 | 57.84 | 0.56 | 0.00 | 0.04 | 0.28 | 22-MAR-08:03 |
April | 0.310905E+11 | 0.00 | 663.90 | 118615.37 | 02-APR-18:05 | 0.00 | 46.27 | 56.25 | 0.34 | 0.00 | 0.03 | 0.26 | 02-APR-18:05 |
May | 0.142671E+11 | 0.00 | 607.75 | 95690.75 | 03-MAY-15:07 | 0.00 | 42.83 | 54.61 | 0.11 | 0.00 | 0.01 | 0.21 | 03-MAY-15:07 |
June | 0.792458E+10 | 0.00 | 510.51 | 100402.60 | 06-JUN-15:05 | 0.00 | 42.66 | 52.91 | 0.05 | 0.00 | 0.01 | 0.22 | 06-JUN-15:05 |
July | 0.620837E+10 | 0.00 | 464.77 | 33655.07 | 05-JUL-08:06 | 0.00 | 43.49 | 51.83 | 0.05 | 0.00 | 0.01 | 0.07 | 05-JUL-08:06 |
August | 0.519023E+10 | 0.00 | 454.53 | 40106.52 | 08-AUG-08:05 | 0.00 | 44.07 | 51.97 | 0.04 | 0.00 | 0.00 | 0.09 | 08-AUG-08:05 |
September | 0.758268E+10 | 0.00 | 523.94 | 87503.11 | 26-SEP-15:05 | 0.00 | 42.89 | 53.29 | 0.06 | 0.00 | 0.01 | 0.19 | 26-SEP-15:05 |
October | 0.176563E+11 | 0.00 | 572.29 | 113513.90 | 10-OCT-05:33 | 0.00 | 45.47 | 54.35 | 0.17 | 0.00 | 0.01 | 0.25 | 10-OCT-05:33 |
November | 0.490550E+11 | 0.00 | 697.79 | 145322.76 | 16-NOV-16:02 | 0.00 | 49.33 | 57.50 | 0.59 | 0.00 | 0.04 | 0.32 | 16-NOV-16:02 |
December | 0.724000E+11 | 0.00 | 743.84 | 140337.08 | 31-DEC-24:00 | 0.00 | 50.88 | 58.33 | 0.90 | 0.00 | 0.06 | 0.31 | 31-DEC-24:00 |
Annual Sum or Average | 0.491433E+12 | 7386.59 | 46.52 | 55.51 | 0.44 | 0.00 | 0.03 | ||||||
Minimum of Months | 0.519023E+10 | 0.00 | 454.53 | 33655.07 | 0.00 | 42.66 | 51.83 | 0.04 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.123235E+12 | 0.00 | 744.00 | 192431.98 | 0.00 | 50.88 | 58.87 | 1.30 | 0.00 | 0.10 | 0.43 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 34692130.13 | 0.00 | 8.73 | 34277188.94 | 0.00 | 0.00 | 0.00 | 0.00 | 12290.27 | 17-JAN-16:02 | 12290.27 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 88825834.65 | 0.00 | 15.99 | 88825834.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12277.06 | 02-FEB-16:02 | 12277.06 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.620682E+09 | 0.00 | 95.78 | 0.573107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12918.84 | 27-MAR-15:02 | 12296.82 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.147575E+10 | 0.00 | 242.92 | 0.106473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12855.23 | 09-APR-15:02 | 12810.84 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.308186E+10 | 0.00 | 475.58 | 0.208831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13982.82 | 31-MAY-18:02 | 13062.23 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.651703E+10 | 0.00 | 608.30 | 0.351413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17908.57 | 25-JUN-08:62 | 13165.26 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.907903E+10 | 0.00 | 675.20 | 0.472592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18639.62 | 22-JUL-08:62 | 13243.36 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.922301E+10 | 0.00 | 683.74 | 0.532697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17800.15 | 03-AUG-08:62 | 13272.01 | 11-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.487502E+10 | 0.00 | 576.66 | 0.265414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17470.48 | 22-SEP-18:03 | 13115.98 | 05-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.309349E+10 | 0.00 | 466.95 | 0.186319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14851.65 | 05-OCT-18:02 | 12556.39 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.242932E+09 | 0.00 | 79.14 | 0.194450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12472.38 | 03-NOV-15:02 | 12472.38 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 43234815.20 | 0.00 | 13.56 | 42732438.51 | 0.00 | 0.00 | 0.00 | 0.00 | 12180.73 | 17-DEC-16:02 | 12180.73 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383756E+11 | 3942.55 | 0.221708E+11 | ||||||||||||
Minimum of Months | 34692130.13 | 0.00 | 8.73 | 34277188.94 | 0.00 | 0.00 | 0.00 | 0.00 | 12180.73 | 12180.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.922301E+10 | 0.00 | 683.74 | 0.532697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18639.62 | 13272.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4155308.93 | 0.00 | 1.73 | 3786972.93 | 0.00 | 0.00 | 0.00 | 0.00 | 6629.23 | 17-JAN-16:02 | 6629.23 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 15957946.01 | 0.00 | 7.02 | 15957946.01 | 0.00 | 0.00 | 0.00 | 0.00 | 11067.02 | 20-FEB-16:02 | 11067.02 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.324615E+09 | 0.00 | 54.11 | 0.292157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12396.91 | 27-MAR-15:02 | 12088.44 | 11-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.111387E+10 | 0.00 | 192.51 | 0.805007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12735.18 | 09-APR-15:02 | 12605.61 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.286274E+10 | 0.00 | 459.46 | 0.192862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13711.99 | 31-MAY-08:62 | 12941.31 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.633346E+10 | 0.00 | 600.61 | 0.341749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17019.81 | 25-JUN-08:62 | 13064.82 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.878587E+10 | 0.00 | 669.58 | 0.455621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18350.42 | 22-JUL-08:62 | 13062.06 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.841936E+10 | 0.00 | 665.80 | 0.476287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17242.24 | 03-AUG-08:62 | 13038.05 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.386042E+10 | 0.00 | 506.98 | 0.200324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17176.42 | 22-SEP-18:03 | 12846.00 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.163761E+10 | 0.00 | 314.98 | 0.917657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13934.71 | 05-OCT-18:02 | 12432.25 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 51060292.54 | 0.00 | 19.80 | 43447902.05 | 0.00 | 0.00 | 0.00 | 0.00 | 11921.40 | 03-NOV-15:02 | 11921.40 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 1895150.34 | 0.00 | 0.58 | 1685244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.84 | 17-DEC-16:02 | 3655.84 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334110E+11 | 3493.15 | 0.187481E+11 | ||||||||||||
Minimum of Months | 1895150.34 | 0.00 | 0.58 | 1685244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.84 | 3655.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.878587E+10 | 0.00 | 669.58 | 0.476287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18350.42 | 13064.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.107691E+09 | 0.00 | 7.96 | 0.107691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7099.73 | 19-JAN-14:30 | 7099.73 | 19-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.634911E+09 | 0.00 | 23.31 | 0.634911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17476.77 | 03-FEB-12:30 | 17476.77 | 03-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.117347E+10 | 0.00 | 42.83 | 0.117347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24074.66 | 03-MAR-13:30 | 24074.66 | 03-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.265227E+10 | 0.00 | 82.59 | 0.189950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30800.54 | 08-APR-12:20 | 27819.61 | 08-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.387190E+10 | 0.00 | 179.80 | 0.234930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24714.22 | 31-MAY-15:10 | 17379.79 | 30-MAY-16:40 | 0.00 | 0.00 | 0.00 |
June | 0.141817E+11 | 0.00 | 399.48 | 0.570833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40757.39 | 25-JUN-16:10 | 24050.33 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.333055E+11 | 0.00 | 618.97 | 0.142490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53882.38 | 22-JUL-16:05 | 26097.15 | 30-JUL-17:15 | 0.00 | 0.00 | 0.00 |
August | 0.372275E+11 | 0.00 | 646.47 | 0.206009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51748.86 | 03-AUG-20:20 | 28589.53 | 30-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.224441E+11 | 0.00 | 442.43 | 0.139405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48194.67 | 07-SEP-16:20 | 40462.88 | 30-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.243141E+11 | 0.00 | 398.31 | 0.195866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47308.66 | 04-OCT-12:00 | 44501.12 | 30-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.500820E+10 | 0.00 | 111.14 | 0.480164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40525.11 | 02-NOV-12:30 | 40525.11 | 02-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.235965E+10 | 0.00 | 48.67 | 0.235965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32118.10 | 17-DEC-13:00 | 32118.10 | 17-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147281E+12 | 3001.94 | 0.874115E+11 | ||||||||||||
Minimum of Months | 0.107691E+09 | 0.00 | 7.96 | 0.107691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7099.73 | 7099.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.372275E+11 | 0.00 | 646.47 | 0.206009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53882.38 | 44501.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.226330E+09 | 0.00 | 27.19 | 0.104444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26802.37 | 22-JAN-09:02 | 21929.89 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 90328206.52 | 0.00 | 14.19 | 87941228.23 | 0.00 | 0.00 | 0.00 | 0.00 | 32993.55 | 20-FEB-09:02 | 32993.55 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.228894E+10 | 0.00 | 154.90 | 0.166995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59377.03 | 28-MAR-18:01 | 59377.03 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.108915E+11 | 0.00 | 368.21 | 0.698765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64371.38 | 09-APR-15:02 | 63062.08 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.281777E+11 | 0.00 | 523.49 | 0.190060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78082.76 | 31-MAY-18:02 | 67556.38 | 30-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.497857E+11 | 0.00 | 512.00 | 0.294147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97974.99 | 25-JUN-18:02 | 69197.57 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.697690E+11 | 0.00 | 534.39 | 0.412618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104381.12 | 22-JUL-08:62 | 69435.73 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.597473E+11 | 0.00 | 530.33 | 0.368761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99769.93 | 31-AUG-18:02 | 69705.14 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.350362E+11 | 0.00 | 507.26 | 0.195801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98684.71 | 07-SEP-18:02 | 70119.30 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.157470E+11 | 0.00 | 458.15 | 0.809042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76169.99 | 05-OCT-18:02 | 61835.54 | 02-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.316070E+10 | 0.00 | 195.08 | 0.206982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60227.41 | 05-NOV-08:62 | 60227.41 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.192919E+09 | 0.00 | 24.19 | 0.150192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35697.41 | 25-DEC-09:02 | 32308.57 | 25-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275114E+12 | 3849.38 | 0.165299E+12 | ||||||||||||
Minimum of Months | 90328206.52 | 0.00 | 14.19 | 87941228.23 | 0.00 | 0.00 | 0.00 | 0.00 | 26802.37 | 21929.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.697690E+11 | 0.00 | 534.39 | 0.412618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104381.12 | 70119.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 55265411.34 | 0.00 | 14.56 | 54884469.44 | 0.00 | 0.00 | 0.00 | 0.00 | 10080.24 | 19-JAN-09:02 | 10080.24 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 93570124.58 | 0.00 | 20.99 | 93514507.53 | 0.00 | 0.00 | 0.00 | 0.00 | 10604.78 | 19-FEB-09:02 | 10604.78 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.480280E+09 | 0.00 | 95.42 | 0.450466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11279.07 | 27-MAR-15:02 | 11115.60 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.145027E+10 | 0.00 | 262.66 | 0.101145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11657.16 | 09-APR-15:02 | 11572.69 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.322650E+10 | 0.00 | 502.83 | 0.220601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13541.10 | 31-MAY-18:02 | 11760.14 | 27-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.599790E+10 | 0.00 | 626.69 | 0.320099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15503.32 | 25-JUN-18:02 | 11985.03 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.889216E+10 | 0.00 | 693.95 | 0.462078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16602.50 | 22-JUL-08:62 | 11927.19 | 11-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.909794E+10 | 0.00 | 704.16 | 0.520402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15843.07 | 31-AUG-18:02 | 11982.05 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.490434E+10 | 0.00 | 598.03 | 0.272205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15791.85 | 22-SEP-18:03 | 11973.16 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.288485E+10 | 0.00 | 464.18 | 0.173364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13799.25 | 25-OCT-08:62 | 11434.37 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.368518E+09 | 0.00 | 92.75 | 0.301309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11203.04 | 03-NOV-15:02 | 11203.04 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.105481E+09 | 0.00 | 26.87 | 0.105182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10669.74 | 17-DEC-09:02 | 10669.74 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375571E+11 | 4103.08 | 0.217043E+11 | ||||||||||||
Minimum of Months | 55265411.34 | 0.00 | 14.56 | 54884469.44 | 0.00 | 0.00 | 0.00 | 0.00 | 10080.24 | 10080.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.909794E+10 | 0.00 | 704.16 | 0.520402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16602.50 | 11985.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 3494534.22 | 0.00 | 1.63 | 3174949.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2513.97 | 26-JAN-09:03 | 2513.97 | 26-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 16252887.58 | 0.00 | 5.53 | 16252887.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10012.44 | 19-FEB-09:02 | 10012.44 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.218163E+09 | 0.00 | 51.56 | 0.202442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10904.35 | 03-MAR-09:02 | 10904.35 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.108878E+10 | 0.00 | 204.10 | 0.755630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11442.59 | 09-APR-15:02 | 11359.86 | 08-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.300136E+10 | 0.00 | 468.16 | 0.204672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12996.25 | 31-MAY-18:02 | 11666.18 | 27-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.580389E+10 | 0.00 | 617.82 | 0.309817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15428.35 | 25-JUN-18:02 | 11726.63 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.859947E+10 | 0.00 | 690.46 | 0.445998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16482.68 | 22-JUL-08:62 | 11726.96 | 11-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.828735E+10 | 0.00 | 698.67 | 0.466425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15926.46 | 31-AUG-18:02 | 11754.54 | 18-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.385328E+10 | 0.00 | 520.82 | 0.205094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15729.94 | 07-SEP-18:02 | 11603.95 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.142913E+10 | 0.00 | 294.39 | 0.770987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.71 | 25-OCT-08:62 | 10841.10 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 97995018.40 | 0.00 | 34.08 | 75917832.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9060.95 | 04-NOV-08:62 | 9060.95 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 5121257.20 | 0.00 | 3.11 | 4982446.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4723.22 | 17-DEC-09:02 | 4723.22 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324043E+11 | 3590.33 | 0.181494E+11 | ||||||||||||
Minimum of Months | 3494534.22 | 0.00 | 1.63 | 3174949.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2513.97 | 2513.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.859947E+10 | 0.00 | 698.67 | 0.466425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16482.68 | 11754.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 8751799.37 | 0.00 | 6.67 | 8671580.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.45 | 17-JAN-16:02 | 3223.45 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 23969166.45 | 0.00 | 15.17 | 23966343.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.98 | 20-FEB-16:02 | 3223.98 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.168421E+09 | 0.00 | 89.24 | 0.155680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3431.98 | 27-MAR-15:02 | 3225.20 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.423115E+09 | 0.00 | 227.42 | 0.316731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3359.98 | 10-APR-15:01 | 3359.98 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.918573E+09 | 0.00 | 476.18 | 0.649539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3785.53 | 31-MAY-08:62 | 3425.76 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.196126E+10 | 0.00 | 639.49 | 0.110735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832.60 | 25-JUN-08:62 | 3452.16 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.272733E+10 | 0.00 | 691.26 | 0.150510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4977.18 | 22-JUL-08:62 | 3475.98 | 16-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.271581E+10 | 0.00 | 695.00 | 0.165896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4697.64 | 03-AUG-08:62 | 3495.19 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.143369E+10 | 0.00 | 572.91 | 0.823169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4739.49 | 22-SEP-18:03 | 3466.83 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.841948E+09 | 0.00 | 430.71 | 0.527689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.05 | 05-OCT-18:02 | 3275.74 | 02-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 56477934.44 | 0.00 | 61.41 | 46191801.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3271.21 | 03-NOV-15:02 | 3271.21 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 8358712.39 | 0.00 | 9.21 | 8271176.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.41 | 17-DEC-16:02 | 3222.41 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112877E+11 | 3914.67 | 0.683132E+10 | ||||||||||||
Minimum of Months | 8358712.39 | 0.00 | 6.67 | 8271176.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.41 | 3222.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.272733E+10 | 0.00 | 695.00 | 0.165896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4977.18 | 3495.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 455451.96 | 0.00 | 0.88 | 398152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 844.51 | 17-JAN-16:02 | 844.51 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 1820659.88 | 0.00 | 4.54 | 1816146.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.90 | 20-FEB-16:02 | 2251.90 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 81440844.42 | 0.00 | 50.05 | 72663083.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3272.71 | 27-MAR-15:02 | 3168.15 | 11-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.319553E+09 | 0.00 | 181.85 | 0.238046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3321.06 | 16-APR-18:02 | 3321.06 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.856379E+09 | 0.00 | 451.25 | 0.602727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.10 | 31-MAY-08:62 | 3368.27 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.191156E+10 | 0.00 | 635.91 | 0.107914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4571.68 | 25-JUN-08:62 | 3382.85 | 07-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.265039E+10 | 0.00 | 689.70 | 0.145505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4895.30 | 22-JUL-08:62 | 3408.71 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.249986E+10 | 0.00 | 689.14 | 0.149193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4523.28 | 03-AUG-08:62 | 3395.12 | 02-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.114783E+10 | 0.00 | 511.82 | 0.627445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4656.86 | 22-SEP-18:03 | 3437.12 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.444763E+09 | 0.00 | 278.03 | 0.259995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3767.44 | 05-OCT-18:02 | 3278.38 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 11896204.26 | 0.00 | 15.67 | 10425463.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3138.27 | 03-NOV-15:02 | 3138.27 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 454654.29 | 0.00 | 0.44 | 429746.21 | 0.00 | 0.00 | 0.00 | 0.00 | 620.47 | 08-DEC-16:03 | 620.47 | 08-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992639E+10 | 3509.30 | 0.584007E+10 | ||||||||||||
Minimum of Months | 454654.29 | 0.00 | 0.44 | 398152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 620.47 | 620.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.265039E+10 | 0.00 | 689.70 | 0.149193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4895.30 | 3437.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.918616E+09 | 0.00 | 95.77 | 0.918056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12800.00 | 17-JAN-16:02 | 12800.00 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.121591E+10 | 0.00 | 147.91 | 0.121579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12801.36 | 20-FEB-16:02 | 12801.36 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.194291E+10 | 0.00 | 215.17 | 0.182995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13721.56 | 27-MAR-15:02 | 12808.34 | 28-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.248191E+10 | 0.00 | 315.11 | 0.180513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13441.22 | 27-APR-15:02 | 13340.94 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.426113E+10 | 0.00 | 531.59 | 0.281466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16182.53 | 31-MAY-18:02 | 13556.33 | 27-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.911214E+10 | 0.00 | 615.10 | 0.504865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19358.41 | 25-JUN-08:62 | 13702.56 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.137853E+11 | 0.00 | 680.71 | 0.781681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20111.71 | 21-JUL-08:62 | 13736.26 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.139661E+11 | 0.00 | 687.49 | 0.897643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19441.43 | 03-AUG-08:62 | 13772.63 | 11-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.956815E+10 | 0.00 | 624.17 | 0.618115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19339.48 | 22-SEP-18:03 | 13574.08 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.853089E+10 | 0.00 | 592.98 | 0.638102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16064.72 | 05-OCT-18:02 | 13356.69 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.219309E+10 | 0.00 | 237.66 | 0.194612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12988.24 | 03-NOV-15:02 | 12988.24 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.165194E+10 | 0.00 | 147.49 | 0.165045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12797.85 | 16-DEC-16:01 | 12797.85 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696281E+11 | 4891.15 | 0.465842E+11 | ||||||||||||
Minimum of Months | 0.918616E+09 | 0.00 | 95.77 | 0.918056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12797.85 | 12797.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139661E+11 | 0.00 | 687.49 | 0.897643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20111.71 | 13772.63 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.212584E+09 | 0.00 | 164.75 | 0.212584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8856.44 | 21-JAN-19:30 | 8856.44 | 21-JAN-19:30 | 0.00 | 0.00 | 0.00 |
February | 0.201468E+09 | 0.00 | 159.57 | 0.201468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8642.35 | 20-FEB-10:56 | 8642.35 | 20-FEB-10:56 | 0.00 | 0.00 | 0.00 |
March | 0.612803E+10 | 0.00 | 254.16 | 0.540477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198352.77 | 27-MAR-13:00 | 159069.17 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.470231E+11 | 0.00 | 320.53 | 0.457603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 242994.98 | 09-APR-11:00 | 211207.24 | 07-APR-16:50 | 0.00 | 0.00 | 0.00 |
May | 0.176419E+12 | 0.00 | 562.48 | 0.142571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310419.14 | 31-MAY-17:20 | 213609.25 | 29-MAY-09:00 | 0.00 | 0.00 | 0.00 |
June | 0.617531E+12 | 0.00 | 717.56 | 0.355495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484633.62 | 24-JUN-18:03 | 282813.62 | 22-JUN-18:15 | 0.00 | 0.00 | 0.00 |
July | 0.881567E+12 | 0.00 | 744.00 | 0.472566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484799.26 | 05-JUL-20:10 | 251580.48 | 11-JUL-18:07 | 0.00 | 0.00 | 0.00 |
August | 0.731925E+12 | 0.00 | 744.00 | 0.460386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 463333.30 | 03-AUG-20:00 | 311534.30 | 24-AUG-18:25 | 0.00 | 0.00 | 0.00 |
September | 0.444639E+12 | 0.00 | 677.23 | 0.292547E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 467975.21 | 22-SEP-17:40 | 258369.24 | 14-SEP-18:40 | 0.00 | 0.00 | 0.00 |
October | 0.180079E+12 | 0.00 | 464.15 | 0.107711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310873.74 | 25-OCT-09:30 | 187123.84 | 25-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.707298E+10 | 0.00 | 213.65 | 0.612666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122727.80 | 10-NOV-08:00 | 80179.28 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.390687E+09 | 0.00 | 247.93 | 0.390687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25064.78 | 17-DEC-19:10 | 25064.78 | 17-DEC-19:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309319E+13 | 5270.01 | 0.188937E+13 | ||||||||||||
Minimum of Months | 0.201468E+09 | 0.00 | 159.57 | 0.201468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8642.35 | 8642.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.881567E+12 | 0.00 | 744.00 | 0.472566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484799.26 | 311534.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.689508E+09 | 0.00 | 19.83 | 0.588199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32555.93 | 27-MAR-13:00 | 24950.44 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.632347E+10 | 0.00 | 144.69 | 0.616292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40026.79 | 09-APR-11:00 | 29603.00 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.231938E+11 | 0.00 | 446.00 | 0.195867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51576.65 | 31-MAY-17:07 | 32423.10 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.970001E+11 | 0.00 | 707.83 | 0.554313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81187.73 | 24-JUN-17:40 | 37150.71 | 19-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.135406E+12 | 0.00 | 744.00 | 0.744891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77209.19 | 30-JUL-07:20 | 35345.29 | 07-JUL-12:00 | 0.00 | 0.00 | 0.00 |
August | 0.109874E+12 | 0.00 | 744.00 | 0.709867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74172.47 | 06-AUG-07:20 | 35359.82 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.668118E+11 | 0.00 | 641.83 | 0.447103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77970.79 | 22-SEP-17:30 | 33118.31 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.243756E+11 | 0.00 | 337.83 | 0.147820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52097.06 | 24-OCT-14:00 | 28704.82 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.604778E+09 | 0.00 | 33.00 | 0.540994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12356.09 | 10-NOV-08:00 | 10811.53 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464280E+12 | 3819.02 | 0.287278E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135406E+12 | 0.00 | 744.00 | 0.744891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81187.73 | 37150.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.64 | 458.46 | 240.18 | 622.31 | 632.93 | 0.00 | 0.00 | 744.00 |
February | 924.91 | 614.83 | 310.07 | 814.86 | 633.11 | 0.00 | 0.00 | 672.00 |
March | 819.44 | 451.21 | 368.23 | 689.78 | 450.63 | 0.00 | 0.00 | 744.00 |
April | 651.97 | 263.73 | 388.24 | 504.42 | 310.02 | 0.00 | 0.00 | 720.00 |
May | 559.93 | 114.57 | 445.36 | 466.69 | 170.03 | 0.00 | 0.00 | 744.00 |
June | 528.68 | 81.36 | 447.32 | 543.51 | 67.46 | 0.00 | 0.00 | 720.00 |
July | 550.12 | 92.77 | 457.35 | 635.43 | 20.42 | 0.00 | 0.00 | 744.00 |
August | 736.83 | 271.73 | 465.10 | 796.71 | 48.00 | 0.00 | 0.00 | 744.00 |
September | 777.78 | 390.55 | 387.22 | 818.67 | 119.71 | 0.00 | 0.00 | 720.00 |
October | 1099.54 | 689.70 | 409.84 | 1164.44 | 275.53 | 0.00 | 0.00 | 744.00 |
November | 761.08 | 456.59 | 304.49 | 724.83 | 439.24 | 0.00 | 0.00 | 720.00 |
December | 754.69 | 535.99 | 218.70 | 713.76 | 569.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.75 | 367.20 | 370.54 | 707.73 | 309.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 528.68 | 81.36 | 218.70 | 466.69 | 20.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1099.54 | 689.70 | 465.10 | 1164.44 | 633.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.33 | 1291.00 | 676.33 | 1733.75 | 1831.45 | 0.00 | 0.00 | 744.00 |
February | 2604.47 | 1731.32 | 873.15 | 2269.69 | 1833.72 | 0.00 | 0.00 | 672.00 |
March | 2307.48 | 1270.58 | 1036.90 | 1917.83 | 1343.55 | 0.00 | 0.00 | 744.00 |
April | 1835.89 | 742.64 | 1093.25 | 1391.79 | 947.10 | 0.00 | 0.00 | 720.00 |
May | 1576.72 | 322.61 | 1254.11 | 1276.02 | 540.41 | 0.00 | 0.00 | 744.00 |
June | 1488.73 | 229.11 | 1259.62 | 1494.74 | 233.03 | 0.00 | 0.00 | 720.00 |
July | 1549.09 | 261.23 | 1287.87 | 1752.77 | 85.53 | 0.00 | 0.00 | 744.00 |
August | 2074.87 | 765.17 | 1309.70 | 2215.84 | 165.34 | 0.00 | 0.00 | 744.00 |
September | 2190.16 | 1099.77 | 1090.40 | 2277.64 | 393.43 | 0.00 | 0.00 | 720.00 |
October | 3096.22 | 1942.15 | 1154.08 | 3246.16 | 854.47 | 0.00 | 0.00 | 744.00 |
November | 2143.16 | 1285.72 | 857.44 | 2011.39 | 1312.06 | 0.00 | 0.00 | 720.00 |
December | 2125.17 | 1509.32 | 615.85 | 1987.82 | 1667.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2077.44 | 1034.02 | 1043.42 | 1963.98 | 928.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1488.73 | 229.11 | 615.85 | 1276.02 | 85.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3096.22 | 1942.15 | 1309.70 | 3246.16 | 1833.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2555.67 | 1677.08 | 878.59 | 2288.59 | 2496.21 | 0.00 | 0.00 | 744.00 |
February | 3383.36 | 2249.09 | 1134.27 | 3004.06 | 2482.59 | 0.00 | 0.00 | 672.00 |
March | 2997.55 | 1650.56 | 1346.99 | 2541.58 | 1823.96 | 0.00 | 0.00 | 744.00 |
April | 2384.93 | 964.73 | 1420.20 | 1844.84 | 1292.20 | 0.00 | 0.00 | 720.00 |
May | 2048.25 | 419.09 | 1629.17 | 1697.04 | 732.45 | 0.00 | 0.00 | 744.00 |
June | 1933.94 | 297.62 | 1636.32 | 2002.02 | 307.35 | 0.00 | 0.00 | 720.00 |
July | 2012.36 | 339.35 | 1673.01 | 2359.23 | 107.45 | 0.00 | 0.00 | 744.00 |
August | 2695.37 | 994.00 | 1701.37 | 2985.50 | 205.74 | 0.00 | 0.00 | 744.00 |
September | 2845.15 | 1428.66 | 1416.49 | 3046.45 | 509.20 | 0.00 | 0.00 | 720.00 |
October | 4022.17 | 2522.96 | 1499.21 | 4321.96 | 1119.43 | 0.00 | 0.00 | 744.00 |
November | 2784.09 | 1670.23 | 1113.86 | 2657.09 | 1787.32 | 0.00 | 0.00 | 720.00 |
December | 2760.71 | 1960.70 | 800.02 | 2623.92 | 2272.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2698.72 | 1343.25 | 1355.46 | 2613.64 | 1254.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1933.94 | 297.62 | 800.02 | 1697.04 | 107.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4022.17 | 2522.96 | 1701.37 | 4321.96 | 2496.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.85 | 90.46 | 47.39 | 123.20 | 129.74 | 0.00 | 0.00 | 744.00 |
February | 182.50 | 121.31 | 61.18 | 161.34 | 130.24 | 0.00 | 0.00 | 672.00 |
March | 161.69 | 89.03 | 72.66 | 136.51 | 93.05 | 0.00 | 0.00 | 744.00 |
April | 128.64 | 52.04 | 76.60 | 99.55 | 63.92 | 0.00 | 0.00 | 720.00 |
May | 110.48 | 22.61 | 87.88 | 90.54 | 35.08 | 0.00 | 0.00 | 744.00 |
June | 104.32 | 16.05 | 88.26 | 106.72 | 12.75 | 0.00 | 0.00 | 720.00 |
July | 108.55 | 18.30 | 90.24 | 128.78 | 2.85 | 0.00 | 0.00 | 744.00 |
August | 145.39 | 53.62 | 91.77 | 163.23 | 7.36 | 0.00 | 0.00 | 744.00 |
September | 153.47 | 77.06 | 76.40 | 164.00 | 22.00 | 0.00 | 0.00 | 720.00 |
October | 216.95 | 136.09 | 80.87 | 232.64 | 52.72 | 0.00 | 0.00 | 744.00 |
November | 150.17 | 90.09 | 60.08 | 144.35 | 88.32 | 0.00 | 0.00 | 720.00 |
December | 148.91 | 105.76 | 43.15 | 142.04 | 115.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.57 | 72.45 | 73.11 | 141.04 | 62.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.32 | 16.05 | 43.15 | 90.54 | 2.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 216.95 | 136.09 | 91.77 | 232.64 | 130.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.46 | 42.07 | 60.39 | 45.60 | 264.03 | 0.00 | 0.00 | 744.00 |
February | 150.50 | 66.05 | 84.45 | 77.87 | 267.23 | 0.00 | 0.00 | 672.00 |
March | 223.56 | 103.62 | 119.95 | 166.45 | 171.68 | 0.00 | 0.00 | 744.00 |
April | 242.80 | 103.76 | 139.04 | 213.39 | 116.37 | 0.00 | 0.00 | 720.00 |
May | 283.60 | 107.79 | 175.81 | 290.31 | 63.19 | 0.00 | 0.00 | 744.00 |
June | 309.86 | 125.03 | 184.83 | 363.79 | 23.18 | 0.00 | 0.00 | 720.00 |
July | 289.90 | 108.93 | 180.98 | 373.47 | 5.26 | 0.00 | 0.00 | 744.00 |
August | 320.77 | 148.31 | 172.46 | 409.96 | 13.65 | 0.00 | 0.00 | 744.00 |
September | 228.24 | 99.65 | 128.59 | 254.87 | 41.12 | 0.00 | 0.00 | 720.00 |
October | 226.45 | 110.31 | 116.14 | 215.87 | 100.52 | 0.00 | 0.00 | 744.00 |
November | 106.64 | 31.16 | 75.49 | 53.96 | 176.33 | 0.00 | 0.00 | 720.00 |
December | 94.21 | 40.67 | 53.53 | 42.27 | 239.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.37 | 90.82 | 124.55 | 209.92 | 122.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.21 | 31.16 | 53.53 | 42.27 | 5.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 320.77 | 148.31 | 184.83 | 409.96 | 267.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.52 | 0.00 | 26.52 | 0.74 | 146.64 | 0.00 | 0.00 | 744.00 |
February | 36.29 | 0.00 | 36.29 | 2.07 | 150.70 | 0.00 | 0.00 | 672.00 |
March | 50.34 | 0.00 | 50.34 | 13.40 | 96.84 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 0.25 | 60.33 | 32.17 | 63.27 | 0.00 | 0.00 | 720.00 |
May | 80.57 | 2.94 | 77.63 | 65.11 | 32.54 | 0.00 | 0.00 | 744.00 |
June | 84.99 | 4.51 | 80.48 | 92.64 | 11.83 | 0.00 | 0.00 | 720.00 |
July | 82.50 | 3.21 | 79.29 | 108.64 | 2.71 | 0.00 | 0.00 | 744.00 |
August | 72.96 | 0.96 | 71.99 | 97.14 | 6.97 | 0.00 | 0.00 | 744.00 |
September | 54.94 | 0.03 | 54.91 | 55.52 | 21.62 | 0.00 | 0.00 | 720.00 |
October | 47.51 | 0.00 | 47.51 | 30.98 | 53.90 | 0.00 | 0.00 | 744.00 |
November | 33.32 | 0.00 | 33.32 | 7.61 | 95.91 | 0.00 | 0.00 | 720.00 |
December | 23.13 | 0.00 | 23.13 | 0.57 | 132.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.58 | 1.00 | 53.58 | 42.49 | 67.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.13 | 0.00 | 23.13 | 0.57 | 2.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.99 | 4.51 | 80.48 | 108.64 | 150.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.46 | 42.07 | 60.39 | 48.21 | 260.56 | 0.00 | 0.00 | 744.00 |
February | 150.50 | 66.05 | 84.45 | 81.81 | 262.63 | 0.00 | 0.00 | 672.00 |
March | 223.56 | 103.62 | 119.95 | 171.09 | 169.18 | 0.00 | 0.00 | 744.00 |
April | 242.80 | 103.76 | 139.04 | 216.09 | 115.26 | 0.00 | 0.00 | 720.00 |
May | 283.60 | 107.79 | 175.81 | 291.38 | 62.85 | 0.00 | 0.00 | 744.00 |
June | 309.86 | 125.03 | 184.83 | 364.35 | 23.03 | 0.00 | 0.00 | 720.00 |
July | 289.90 | 108.93 | 180.98 | 374.09 | 5.19 | 0.00 | 0.00 | 744.00 |
August | 320.77 | 148.31 | 172.46 | 411.68 | 13.34 | 0.00 | 0.00 | 744.00 |
September | 228.24 | 99.65 | 128.59 | 258.04 | 40.16 | 0.00 | 0.00 | 720.00 |
October | 226.45 | 110.31 | 116.14 | 221.97 | 98.01 | 0.00 | 0.00 | 744.00 |
November | 106.64 | 31.16 | 75.49 | 58.01 | 172.90 | 0.00 | 0.00 | 720.00 |
December | 94.21 | 40.67 | 53.53 | 45.41 | 234.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.37 | 90.82 | 124.55 | 212.78 | 120.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.21 | 31.16 | 53.53 | 45.41 | 5.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 320.77 | 148.31 | 184.83 | 411.68 | 262.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.26 | 72.35 | 37.91 | 98.18 | 101.06 | 0.00 | 0.00 | 744.00 |
February | 145.97 | 97.03 | 48.94 | 127.37 | 105.57 | 0.00 | 0.00 | 672.00 |
March | 129.32 | 71.21 | 58.11 | 108.38 | 77.08 | 0.00 | 0.00 | 744.00 |
April | 102.89 | 41.62 | 61.27 | 78.84 | 54.10 | 0.00 | 0.00 | 720.00 |
May | 88.37 | 18.08 | 70.29 | 70.13 | 32.77 | 0.00 | 0.00 | 744.00 |
June | 83.44 | 12.84 | 70.60 | 82.72 | 14.59 | 0.00 | 0.00 | 720.00 |
July | 86.82 | 14.64 | 72.18 | 98.91 | 5.38 | 0.00 | 0.00 | 744.00 |
August | 116.29 | 42.88 | 73.40 | 127.03 | 9.41 | 0.00 | 0.00 | 744.00 |
September | 122.75 | 61.64 | 61.11 | 128.06 | 23.85 | 0.00 | 0.00 | 720.00 |
October | 173.53 | 108.85 | 64.68 | 182.82 | 50.44 | 0.00 | 0.00 | 744.00 |
November | 120.11 | 72.06 | 48.06 | 112.58 | 76.08 | 0.00 | 0.00 | 720.00 |
December | 119.11 | 84.59 | 34.52 | 111.95 | 93.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.43 | 57.95 | 58.48 | 110.55 | 53.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.44 | 12.84 | 34.52 | 70.13 | 5.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.53 | 108.85 | 73.40 | 182.82 | 105.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.22 | 0.00 | 21.22 | 0.37 | 122.20 | 0.00 | 0.00 | 744.00 |
February | 29.04 | 0.00 | 29.04 | 1.43 | 124.34 | 0.00 | 0.00 | 672.00 |
March | 40.28 | 0.00 | 40.28 | 10.66 | 78.97 | 0.00 | 0.00 | 744.00 |
April | 48.47 | 0.20 | 48.27 | 26.62 | 51.38 | 0.00 | 0.00 | 720.00 |
May | 64.46 | 2.35 | 62.11 | 54.51 | 25.80 | 0.00 | 0.00 | 744.00 |
June | 68.00 | 3.61 | 64.39 | 78.18 | 8.72 | 0.00 | 0.00 | 720.00 |
July | 66.01 | 2.57 | 63.44 | 91.41 | 1.71 | 0.00 | 0.00 | 744.00 |
August | 58.37 | 0.77 | 57.60 | 82.68 | 4.85 | 0.00 | 0.00 | 744.00 |
September | 43.96 | 0.02 | 43.93 | 47.15 | 16.64 | 0.00 | 0.00 | 720.00 |
October | 38.01 | 0.00 | 38.01 | 26.28 | 42.77 | 0.00 | 0.00 | 744.00 |
November | 26.66 | 0.00 | 26.66 | 5.75 | 80.15 | 0.00 | 0.00 | 720.00 |
December | 18.51 | 0.00 | 18.51 | 0.32 | 110.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.67 | 0.80 | 42.87 | 35.68 | 55.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.51 | 0.00 | 18.51 | 0.32 | 1.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 68.00 | 3.61 | 64.39 | 91.41 | 124.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.18 | 41.23 | 61.95 | 42.62 | 259.36 | 0.00 | 0.00 | 744.00 |
February | 160.18 | 74.60 | 85.59 | 83.00 | 257.63 | 0.00 | 0.00 | 672.00 |
March | 205.70 | 87.42 | 118.28 | 145.64 | 172.29 | 0.00 | 0.00 | 744.00 |
April | 246.25 | 108.09 | 138.16 | 213.39 | 112.60 | 0.00 | 0.00 | 720.00 |
May | 297.25 | 118.44 | 178.81 | 304.64 | 61.02 | 0.00 | 0.00 | 744.00 |
June | 276.02 | 99.96 | 176.06 | 321.52 | 22.00 | 0.00 | 0.00 | 720.00 |
July | 276.86 | 99.66 | 177.20 | 358.08 | 4.95 | 0.00 | 0.00 | 744.00 |
August | 312.35 | 140.92 | 171.44 | 398.70 | 12.72 | 0.00 | 0.00 | 744.00 |
September | 233.68 | 105.28 | 128.40 | 258.81 | 39.24 | 0.00 | 0.00 | 720.00 |
October | 211.10 | 95.56 | 115.54 | 194.16 | 97.64 | 0.00 | 0.00 | 744.00 |
November | 130.75 | 50.25 | 80.50 | 77.67 | 171.10 | 0.00 | 0.00 | 720.00 |
December | 102.23 | 48.25 | 53.99 | 47.31 | 233.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.30 | 89.24 | 124.06 | 204.63 | 119.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.23 | 41.23 | 53.99 | 42.62 | 4.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 312.35 | 140.92 | 178.81 | 398.70 | 259.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.85 | 90.46 | 47.39 | 122.88 | 129.56 | 0.00 | 0.00 | 744.00 |
February | 182.50 | 121.31 | 61.18 | 160.59 | 129.94 | 0.00 | 0.00 | 672.00 |
March | 161.69 | 89.03 | 72.66 | 135.64 | 92.20 | 0.00 | 0.00 | 744.00 |
April | 128.64 | 52.04 | 76.60 | 98.43 | 63.48 | 0.00 | 0.00 | 720.00 |
May | 110.48 | 22.61 | 87.88 | 89.24 | 34.62 | 0.00 | 0.00 | 744.00 |
June | 104.32 | 16.05 | 88.26 | 106.62 | 12.32 | 0.00 | 0.00 | 720.00 |
July | 108.55 | 18.30 | 90.24 | 128.60 | 2.71 | 0.00 | 0.00 | 744.00 |
August | 145.39 | 53.62 | 91.77 | 162.77 | 7.10 | 0.00 | 0.00 | 744.00 |
September | 153.47 | 77.06 | 76.40 | 163.33 | 21.71 | 0.00 | 0.00 | 720.00 |
October | 216.95 | 136.09 | 80.87 | 232.03 | 52.18 | 0.00 | 0.00 | 744.00 |
November | 150.17 | 90.09 | 60.08 | 143.59 | 88.39 | 0.00 | 0.00 | 720.00 |
December | 148.91 | 105.76 | 43.15 | 141.62 | 115.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.57 | 72.45 | 73.11 | 140.42 | 62.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.32 | 16.05 | 43.15 | 89.24 | 2.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 216.95 | 136.09 | 91.77 | 232.03 | 129.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.52 | 0.00 | 26.52 | 0.63 | 146.64 | 0.00 | 0.00 | 744.00 |
February | 36.29 | 0.00 | 36.29 | 1.89 | 150.86 | 0.00 | 0.00 | 672.00 |
March | 50.34 | 0.00 | 50.34 | 12.72 | 96.16 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 0.25 | 60.33 | 31.14 | 63.01 | 0.00 | 0.00 | 720.00 |
May | 80.57 | 2.94 | 77.63 | 63.85 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 84.99 | 4.51 | 80.48 | 92.60 | 11.46 | 0.00 | 0.00 | 720.00 |
July | 82.50 | 3.21 | 79.29 | 108.47 | 2.57 | 0.00 | 0.00 | 744.00 |
August | 72.96 | 0.96 | 71.99 | 96.62 | 6.72 | 0.00 | 0.00 | 744.00 |
September | 54.94 | 0.03 | 54.91 | 54.69 | 21.40 | 0.00 | 0.00 | 720.00 |
October | 47.51 | 0.00 | 47.51 | 30.26 | 53.23 | 0.00 | 0.00 | 744.00 |
November | 33.32 | 0.00 | 33.32 | 7.15 | 96.29 | 0.00 | 0.00 | 720.00 |
December | 23.13 | 0.00 | 23.13 | 0.47 | 132.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.58 | 1.00 | 53.58 | 41.98 | 67.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.13 | 0.00 | 23.13 | 0.47 | 2.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.99 | 4.51 | 80.48 | 108.47 | 150.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.18 | 41.23 | 61.95 | 44.01 | 254.71 | 0.00 | 0.00 | 744.00 |
February | 160.18 | 74.60 | 85.59 | 85.29 | 251.26 | 0.00 | 0.00 | 672.00 |
March | 205.70 | 87.42 | 118.28 | 149.60 | 169.05 | 0.00 | 0.00 | 744.00 |
April | 246.25 | 108.09 | 138.16 | 215.87 | 111.37 | 0.00 | 0.00 | 720.00 |
May | 297.25 | 118.44 | 178.81 | 305.63 | 60.66 | 0.00 | 0.00 | 744.00 |
June | 276.02 | 99.96 | 176.06 | 322.07 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 276.86 | 99.66 | 177.20 | 358.70 | 4.89 | 0.00 | 0.00 | 744.00 |
August | 312.35 | 140.92 | 171.44 | 400.30 | 12.42 | 0.00 | 0.00 | 744.00 |
September | 233.68 | 105.28 | 128.40 | 261.63 | 38.26 | 0.00 | 0.00 | 720.00 |
October | 211.10 | 95.56 | 115.54 | 199.89 | 94.73 | 0.00 | 0.00 | 744.00 |
November | 130.75 | 50.25 | 80.50 | 81.05 | 167.17 | 0.00 | 0.00 | 720.00 |
December | 102.23 | 48.25 | 53.99 | 48.88 | 227.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.30 | 89.24 | 124.06 | 206.92 | 117.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.23 | 41.23 | 53.99 | 44.01 | 4.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 312.35 | 140.92 | 178.81 | 400.30 | 254.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.59 | 0.00 | 33.59 | 0.47 | 194.28 | 0.00 | 0.00 | 744.00 |
February | 45.96 | 0.00 | 45.96 | 2.10 | 197.93 | 0.00 | 0.00 | 672.00 |
March | 63.75 | 0.00 | 63.75 | 16.73 | 124.09 | 0.00 | 0.00 | 744.00 |
April | 76.72 | 0.31 | 76.40 | 43.40 | 79.70 | 0.00 | 0.00 | 720.00 |
May | 102.03 | 3.72 | 98.31 | 89.61 | 39.54 | 0.00 | 0.00 | 744.00 |
June | 107.64 | 5.71 | 101.93 | 127.52 | 13.13 | 0.00 | 0.00 | 720.00 |
July | 104.48 | 4.07 | 100.41 | 148.00 | 2.57 | 0.00 | 0.00 | 744.00 |
August | 92.39 | 1.22 | 91.17 | 132.30 | 7.81 | 0.00 | 0.00 | 744.00 |
September | 69.58 | 0.04 | 69.54 | 76.29 | 25.69 | 0.00 | 0.00 | 720.00 |
October | 60.16 | 0.00 | 60.16 | 41.88 | 67.23 | 0.00 | 0.00 | 744.00 |
November | 42.20 | 0.00 | 42.20 | 9.15 | 126.25 | 0.00 | 0.00 | 720.00 |
December | 29.30 | 0.00 | 29.30 | 0.43 | 176.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 69.12 | 1.26 | 67.85 | 57.70 | 87.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.30 | 0.00 | 29.30 | 0.43 | 2.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.64 | 5.71 | 101.93 | 148.00 | 197.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.38 | 0.00 | 12.38 | 0.17 | 71.62 | 0.00 | 0.00 | 744.00 |
February | 16.94 | 0.00 | 16.94 | 0.78 | 72.97 | 0.00 | 0.00 | 672.00 |
March | 23.50 | 0.00 | 23.50 | 6.17 | 45.75 | 0.00 | 0.00 | 744.00 |
April | 28.28 | 0.12 | 28.17 | 16.00 | 29.38 | 0.00 | 0.00 | 720.00 |
May | 37.61 | 1.37 | 36.24 | 33.03 | 14.58 | 0.00 | 0.00 | 744.00 |
June | 39.68 | 2.11 | 37.57 | 47.01 | 4.84 | 0.00 | 0.00 | 720.00 |
July | 38.51 | 1.50 | 37.02 | 54.56 | 0.95 | 0.00 | 0.00 | 744.00 |
August | 34.06 | 0.45 | 33.61 | 48.77 | 2.88 | 0.00 | 0.00 | 744.00 |
September | 25.65 | 0.01 | 25.63 | 28.12 | 9.47 | 0.00 | 0.00 | 720.00 |
October | 22.18 | 0.00 | 22.18 | 15.44 | 24.79 | 0.00 | 0.00 | 744.00 |
November | 15.56 | 0.00 | 15.56 | 3.37 | 46.54 | 0.00 | 0.00 | 720.00 |
December | 10.80 | 0.00 | 10.80 | 0.16 | 64.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.48 | 0.47 | 25.01 | 21.27 | 32.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.80 | 0.00 | 10.80 | 0.16 | 0.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 39.68 | 2.11 | 37.57 | 54.56 | 72.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.32 | 42.21 | 22.11 | 57.58 | 62.13 | 0.00 | 0.00 | 744.00 |
February | 85.15 | 56.61 | 28.55 | 75.71 | 61.73 | 0.00 | 0.00 | 672.00 |
March | 75.44 | 41.54 | 33.90 | 64.73 | 43.30 | 0.00 | 0.00 | 744.00 |
April | 60.02 | 24.28 | 35.74 | 48.04 | 29.29 | 0.00 | 0.00 | 720.00 |
May | 51.55 | 10.55 | 41.00 | 45.03 | 15.45 | 0.00 | 0.00 | 744.00 |
June | 48.67 | 7.49 | 41.18 | 53.66 | 5.09 | 0.00 | 0.00 | 720.00 |
July | 50.65 | 8.54 | 42.11 | 64.14 | 0.97 | 0.00 | 0.00 | 744.00 |
August | 67.84 | 25.02 | 42.82 | 80.00 | 2.94 | 0.00 | 0.00 | 744.00 |
September | 71.61 | 35.96 | 35.65 | 79.48 | 9.36 | 0.00 | 0.00 | 720.00 |
October | 101.23 | 63.50 | 37.73 | 111.16 | 23.68 | 0.00 | 0.00 | 744.00 |
November | 70.07 | 42.04 | 28.03 | 68.02 | 41.78 | 0.00 | 0.00 | 720.00 |
December | 69.48 | 49.35 | 20.13 | 66.58 | 55.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.92 | 33.81 | 34.11 | 67.84 | 29.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 48.67 | 7.49 | 20.13 | 45.03 | 0.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.23 | 63.50 | 42.82 | 111.16 | 62.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.58 | 114.56 | 60.02 | 156.29 | 168.63 | 0.00 | 0.00 | 744.00 |
February | 231.12 | 153.64 | 77.48 | 205.50 | 167.54 | 0.00 | 0.00 | 672.00 |
March | 204.77 | 112.75 | 92.01 | 175.69 | 117.54 | 0.00 | 0.00 | 744.00 |
April | 162.92 | 65.90 | 97.02 | 130.40 | 79.50 | 0.00 | 0.00 | 720.00 |
May | 139.92 | 28.63 | 111.29 | 122.23 | 41.94 | 0.00 | 0.00 | 744.00 |
June | 132.11 | 20.33 | 111.78 | 145.64 | 13.82 | 0.00 | 0.00 | 720.00 |
July | 137.47 | 23.18 | 114.29 | 174.09 | 2.62 | 0.00 | 0.00 | 744.00 |
August | 184.12 | 67.90 | 116.22 | 217.13 | 7.99 | 0.00 | 0.00 | 744.00 |
September | 194.36 | 97.59 | 96.76 | 215.72 | 25.41 | 0.00 | 0.00 | 720.00 |
October | 274.76 | 172.35 | 102.41 | 301.72 | 64.28 | 0.00 | 0.00 | 744.00 |
November | 190.18 | 114.10 | 76.09 | 184.61 | 113.41 | 0.00 | 0.00 | 720.00 |
December | 188.59 | 133.94 | 54.65 | 180.71 | 150.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.35 | 91.76 | 92.59 | 184.13 | 78.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 132.11 | 20.33 | 54.65 | 122.23 | 2.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 274.76 | 172.35 | 116.22 | 301.72 | 168.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.96 | 90.54 | 47.43 | 122.95 | 129.41 | 0.00 | 0.00 | 744.00 |
February | 182.65 | 121.41 | 61.23 | 160.95 | 130.07 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 89.10 | 72.72 | 136.04 | 93.08 | 0.00 | 0.00 | 744.00 |
April | 128.75 | 52.08 | 76.67 | 99.04 | 64.00 | 0.00 | 0.00 | 720.00 |
May | 110.57 | 22.62 | 87.95 | 89.33 | 35.42 | 0.00 | 0.00 | 744.00 |
June | 104.40 | 16.07 | 88.33 | 105.34 | 13.01 | 0.00 | 0.00 | 720.00 |
July | 108.63 | 18.32 | 90.32 | 127.48 | 2.93 | 0.00 | 0.00 | 744.00 |
August | 145.51 | 53.66 | 91.85 | 162.25 | 7.39 | 0.00 | 0.00 | 744.00 |
September | 153.59 | 77.12 | 76.47 | 162.88 | 22.19 | 0.00 | 0.00 | 720.00 |
October | 217.13 | 136.20 | 80.93 | 231.55 | 52.73 | 0.00 | 0.00 | 744.00 |
November | 150.30 | 90.17 | 60.13 | 144.05 | 87.83 | 0.00 | 0.00 | 720.00 |
December | 149.03 | 105.85 | 43.19 | 141.86 | 115.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.69 | 72.51 | 73.17 | 140.28 | 62.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.40 | 16.07 | 43.19 | 89.33 | 2.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 217.13 | 136.20 | 91.85 | 231.55 | 130.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.55 | 42.11 | 60.44 | 45.67 | 263.41 | 0.00 | 0.00 | 744.00 |
February | 150.62 | 66.10 | 84.52 | 77.58 | 267.11 | 0.00 | 0.00 | 672.00 |
March | 223.75 | 103.70 | 120.05 | 165.33 | 171.47 | 0.00 | 0.00 | 744.00 |
April | 243.00 | 103.85 | 139.15 | 211.66 | 116.25 | 0.00 | 0.00 | 720.00 |
May | 283.84 | 107.88 | 175.96 | 287.14 | 63.55 | 0.00 | 0.00 | 744.00 |
June | 310.11 | 125.13 | 184.98 | 360.24 | 23.58 | 0.00 | 0.00 | 720.00 |
July | 290.14 | 109.02 | 181.13 | 370.19 | 5.41 | 0.00 | 0.00 | 744.00 |
August | 321.03 | 148.43 | 172.60 | 407.18 | 13.69 | 0.00 | 0.00 | 744.00 |
September | 228.43 | 99.73 | 128.69 | 252.53 | 41.39 | 0.00 | 0.00 | 720.00 |
October | 226.64 | 110.40 | 116.23 | 214.22 | 100.44 | 0.00 | 0.00 | 744.00 |
November | 106.73 | 31.18 | 75.55 | 53.91 | 175.36 | 0.00 | 0.00 | 720.00 |
December | 94.28 | 40.71 | 53.58 | 42.41 | 238.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.55 | 90.90 | 124.65 | 208.27 | 122.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.28 | 31.18 | 53.58 | 42.41 | 5.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.03 | 148.43 | 184.98 | 407.18 | 267.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.54 | 0.00 | 26.54 | 0.80 | 146.14 | 0.00 | 0.00 | 744.00 |
February | 36.32 | 0.00 | 36.32 | 2.13 | 150.54 | 0.00 | 0.00 | 672.00 |
March | 50.38 | 0.00 | 50.38 | 13.38 | 96.69 | 0.00 | 0.00 | 744.00 |
April | 60.63 | 0.25 | 60.38 | 31.67 | 63.19 | 0.00 | 0.00 | 720.00 |
May | 80.63 | 2.94 | 77.69 | 63.63 | 32.78 | 0.00 | 0.00 | 744.00 |
June | 85.06 | 4.51 | 80.55 | 91.00 | 12.05 | 0.00 | 0.00 | 720.00 |
July | 82.56 | 3.21 | 79.35 | 106.97 | 2.81 | 0.00 | 0.00 | 744.00 |
August | 73.02 | 0.96 | 72.05 | 95.83 | 6.99 | 0.00 | 0.00 | 744.00 |
September | 54.98 | 0.03 | 54.95 | 54.38 | 21.78 | 0.00 | 0.00 | 720.00 |
October | 47.55 | 0.00 | 47.55 | 30.58 | 53.75 | 0.00 | 0.00 | 744.00 |
November | 33.35 | 0.00 | 33.35 | 7.73 | 95.08 | 0.00 | 0.00 | 720.00 |
December | 23.15 | 0.00 | 23.15 | 0.64 | 131.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.62 | 1.00 | 53.62 | 41.84 | 67.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.64 | 2.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.06 | 4.51 | 80.55 | 106.97 | 150.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.55 | 42.11 | 60.44 | 48.34 | 260.05 | 0.00 | 0.00 | 744.00 |
February | 150.62 | 66.10 | 84.52 | 81.74 | 262.63 | 0.00 | 0.00 | 672.00 |
March | 223.75 | 103.70 | 120.05 | 170.37 | 168.82 | 0.00 | 0.00 | 744.00 |
April | 243.00 | 103.85 | 139.15 | 214.48 | 115.06 | 0.00 | 0.00 | 720.00 |
May | 283.84 | 107.88 | 175.96 | 288.17 | 63.20 | 0.00 | 0.00 | 744.00 |
June | 310.11 | 125.13 | 184.98 | 360.73 | 23.44 | 0.00 | 0.00 | 720.00 |
July | 290.14 | 109.02 | 181.13 | 370.77 | 5.34 | 0.00 | 0.00 | 744.00 |
August | 321.03 | 148.43 | 172.60 | 408.85 | 13.37 | 0.00 | 0.00 | 744.00 |
September | 228.43 | 99.73 | 128.69 | 255.57 | 40.40 | 0.00 | 0.00 | 720.00 |
October | 226.64 | 110.40 | 116.23 | 220.64 | 97.67 | 0.00 | 0.00 | 744.00 |
November | 106.73 | 31.18 | 75.55 | 58.26 | 171.76 | 0.00 | 0.00 | 720.00 |
December | 94.28 | 40.71 | 53.58 | 45.80 | 233.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.55 | 90.90 | 124.65 | 211.24 | 120.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.28 | 31.18 | 53.58 | 45.80 | 5.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.03 | 148.43 | 184.98 | 408.85 | 262.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.34 | 132.78 | 69.56 | 174.38 | 196.58 | 0.00 | 0.00 | 744.00 |
February | 267.87 | 178.07 | 89.80 | 228.56 | 197.82 | 0.00 | 0.00 | 672.00 |
March | 237.32 | 130.68 | 106.64 | 195.58 | 139.73 | 0.00 | 0.00 | 744.00 |
April | 188.82 | 76.38 | 112.44 | 143.91 | 94.70 | 0.00 | 0.00 | 720.00 |
May | 162.17 | 33.18 | 128.99 | 132.72 | 50.96 | 0.00 | 0.00 | 744.00 |
June | 153.12 | 23.56 | 129.55 | 158.49 | 17.76 | 0.00 | 0.00 | 720.00 |
July | 159.32 | 26.87 | 132.46 | 191.22 | 3.67 | 0.00 | 0.00 | 744.00 |
August | 213.40 | 78.70 | 134.70 | 241.56 | 10.06 | 0.00 | 0.00 | 744.00 |
September | 225.26 | 113.11 | 112.15 | 238.85 | 32.43 | 0.00 | 0.00 | 720.00 |
October | 318.45 | 199.75 | 118.70 | 336.38 | 79.10 | 0.00 | 0.00 | 744.00 |
November | 220.42 | 132.24 | 88.19 | 205.33 | 135.21 | 0.00 | 0.00 | 720.00 |
December | 218.57 | 155.23 | 63.34 | 201.51 | 175.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.66 | 106.35 | 107.32 | 204.03 | 93.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 153.12 | 23.56 | 63.34 | 132.72 | 3.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 318.45 | 199.75 | 134.70 | 336.38 | 197.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.79 | 0.00 | 185.79 | 0.70 | 1197.75 | 0.00 | 0.00 | 744.00 |
February | 254.25 | 0.00 | 254.25 | 6.18 | 1212.86 | 0.00 | 0.00 | 672.00 |
March | 352.66 | 0.01 | 352.65 | 67.98 | 804.35 | 0.00 | 0.00 | 744.00 |
April | 424.37 | 1.73 | 422.64 | 195.42 | 541.66 | 0.00 | 0.00 | 720.00 |
May | 564.40 | 20.60 | 543.80 | 421.70 | 289.01 | 0.00 | 0.00 | 744.00 |
June | 595.42 | 31.60 | 563.82 | 622.74 | 129.36 | 0.00 | 0.00 | 720.00 |
July | 577.93 | 22.50 | 555.43 | 721.54 | 51.18 | 0.00 | 0.00 | 744.00 |
August | 511.09 | 6.75 | 504.35 | 648.27 | 82.99 | 0.00 | 0.00 | 744.00 |
September | 384.87 | 0.22 | 384.65 | 368.82 | 212.83 | 0.00 | 0.00 | 720.00 |
October | 332.81 | 0.00 | 332.81 | 195.95 | 458.94 | 0.00 | 0.00 | 744.00 |
November | 233.43 | 0.00 | 233.43 | 34.74 | 820.32 | 0.00 | 0.00 | 720.00 |
December | 162.06 | 0.00 | 162.06 | 0.92 | 1102.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 382.33 | 6.99 | 375.34 | 275.60 | 571.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 162.06 | 0.00 | 162.06 | 0.70 | 51.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 595.42 | 31.60 | 563.82 | 721.54 | 1212.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.79 | 0.00 | 185.79 | 0.39 | 1234.89 | 0.00 | 0.00 | 744.00 |
February | 254.25 | 0.00 | 254.25 | 4.70 | 1248.33 | 0.00 | 0.00 | 672.00 |
March | 352.66 | 0.01 | 352.65 | 61.14 | 830.87 | 0.00 | 0.00 | 744.00 |
April | 424.37 | 1.73 | 422.64 | 183.89 | 561.46 | 0.00 | 0.00 | 720.00 |
May | 564.40 | 20.60 | 543.80 | 404.82 | 301.21 | 0.00 | 0.00 | 744.00 |
June | 595.42 | 31.60 | 563.82 | 606.53 | 138.15 | 0.00 | 0.00 | 720.00 |
July | 577.93 | 22.50 | 555.43 | 706.27 | 57.61 | 0.00 | 0.00 | 744.00 |
August | 511.09 | 6.75 | 504.35 | 633.80 | 89.56 | 0.00 | 0.00 | 744.00 |
September | 384.87 | 0.22 | 384.65 | 355.63 | 226.28 | 0.00 | 0.00 | 720.00 |
October | 332.81 | 0.00 | 332.81 | 185.62 | 476.78 | 0.00 | 0.00 | 744.00 |
November | 233.43 | 0.00 | 233.43 | 30.66 | 850.01 | 0.00 | 0.00 | 720.00 |
December | 162.06 | 0.00 | 162.06 | 0.65 | 1137.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 382.33 | 6.99 | 375.34 | 266.32 | 592.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 162.06 | 0.00 | 162.06 | 0.39 | 57.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 595.42 | 31.60 | 563.82 | 706.27 | 1248.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.54 | 0.00 | 26.54 | 1.07 | 152.47 | 0.00 | 0.00 | 744.00 |
February | 36.32 | 0.00 | 36.32 | 2.41 | 155.20 | 0.00 | 0.00 | 672.00 |
March | 50.38 | 0.00 | 50.38 | 15.13 | 100.91 | 0.00 | 0.00 | 744.00 |
April | 60.63 | 0.25 | 60.38 | 39.19 | 68.42 | 0.00 | 0.00 | 720.00 |
May | 80.63 | 2.94 | 77.69 | 78.94 | 37.06 | 0.00 | 0.00 | 744.00 |
June | 85.06 | 4.51 | 80.55 | 112.01 | 15.22 | 0.00 | 0.00 | 720.00 |
July | 82.56 | 3.21 | 79.35 | 129.93 | 4.99 | 0.00 | 0.00 | 744.00 |
August | 73.02 | 0.96 | 72.05 | 117.60 | 8.78 | 0.00 | 0.00 | 744.00 |
September | 54.98 | 0.03 | 54.95 | 70.91 | 23.81 | 0.00 | 0.00 | 720.00 |
October | 47.55 | 0.00 | 47.55 | 39.07 | 55.17 | 0.00 | 0.00 | 744.00 |
November | 33.35 | 0.00 | 33.35 | 9.04 | 101.86 | 0.00 | 0.00 | 720.00 |
December | 23.15 | 0.00 | 23.15 | 0.76 | 138.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.62 | 1.00 | 53.62 | 51.67 | 71.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.76 | 4.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.06 | 4.51 | 80.55 | 129.93 | 155.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.52 | 82.52 | 123.99 | 92.70 | 534.32 | 0.00 | 0.00 | 744.00 |
February | 320.61 | 149.30 | 171.30 | 177.77 | 521.83 | 0.00 | 0.00 | 672.00 |
March | 411.70 | 174.97 | 236.73 | 312.35 | 361.94 | 0.00 | 0.00 | 744.00 |
April | 492.87 | 216.34 | 276.53 | 464.17 | 246.89 | 0.00 | 0.00 | 720.00 |
May | 594.95 | 237.06 | 357.89 | 665.88 | 139.99 | 0.00 | 0.00 | 744.00 |
June | 552.45 | 200.07 | 352.38 | 714.80 | 58.43 | 0.00 | 0.00 | 720.00 |
July | 554.14 | 199.47 | 354.67 | 795.90 | 19.58 | 0.00 | 0.00 | 744.00 |
August | 625.17 | 282.04 | 343.13 | 877.96 | 33.52 | 0.00 | 0.00 | 744.00 |
September | 467.70 | 210.72 | 256.99 | 584.55 | 88.26 | 0.00 | 0.00 | 720.00 |
October | 422.51 | 191.26 | 231.25 | 436.57 | 200.74 | 0.00 | 0.00 | 744.00 |
November | 261.70 | 100.57 | 161.12 | 173.85 | 356.86 | 0.00 | 0.00 | 720.00 |
December | 204.62 | 96.56 | 108.05 | 103.13 | 477.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 426.92 | 178.61 | 248.31 | 451.83 | 251.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 204.62 | 82.52 | 108.05 | 92.70 | 19.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 625.17 | 282.04 | 357.89 | 877.96 | 534.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.96 | 90.54 | 47.43 | 126.33 | 134.77 | 0.00 | 0.00 | 744.00 |
February | 182.65 | 121.41 | 61.23 | 165.52 | 132.99 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 89.10 | 72.72 | 142.12 | 96.73 | 0.00 | 0.00 | 744.00 |
April | 128.75 | 52.08 | 76.67 | 107.66 | 68.83 | 0.00 | 0.00 | 720.00 |
May | 110.57 | 22.62 | 87.95 | 103.95 | 39.07 | 0.00 | 0.00 | 744.00 |
June | 104.40 | 16.07 | 88.33 | 125.31 | 16.20 | 0.00 | 0.00 | 720.00 |
July | 108.63 | 18.32 | 90.32 | 149.65 | 5.27 | 0.00 | 0.00 | 744.00 |
August | 145.51 | 53.66 | 91.85 | 184.19 | 9.05 | 0.00 | 0.00 | 744.00 |
September | 153.59 | 77.12 | 76.47 | 181.11 | 23.94 | 0.00 | 0.00 | 720.00 |
October | 217.13 | 136.20 | 80.93 | 245.75 | 54.17 | 0.00 | 0.00 | 744.00 |
November | 150.30 | 90.17 | 60.13 | 149.74 | 93.11 | 0.00 | 0.00 | 720.00 |
December | 149.03 | 105.85 | 43.19 | 145.82 | 120.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.69 | 72.51 | 73.17 | 152.28 | 65.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.40 | 16.07 | 43.19 | 103.95 | 5.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 217.13 | 136.20 | 91.85 | 245.75 | 134.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.61 | 0.00 | 33.61 | 0.28 | 198.76 | 0.00 | 0.00 | 744.00 |
February | 46.00 | 0.00 | 46.00 | 1.66 | 202.68 | 0.00 | 0.00 | 672.00 |
March | 63.81 | 0.00 | 63.80 | 14.63 | 128.21 | 0.00 | 0.00 | 744.00 |
April | 76.78 | 0.31 | 76.47 | 39.94 | 83.46 | 0.00 | 0.00 | 720.00 |
May | 102.12 | 3.73 | 98.39 | 83.43 | 43.16 | 0.00 | 0.00 | 744.00 |
June | 107.73 | 5.72 | 102.01 | 117.67 | 17.65 | 0.00 | 0.00 | 720.00 |
July | 104.56 | 4.07 | 100.49 | 133.99 | 5.89 | 0.00 | 0.00 | 744.00 |
August | 92.47 | 1.22 | 91.25 | 119.43 | 11.62 | 0.00 | 0.00 | 744.00 |
September | 69.63 | 0.04 | 69.59 | 69.59 | 30.32 | 0.00 | 0.00 | 720.00 |
October | 60.21 | 0.00 | 60.21 | 37.67 | 71.72 | 0.00 | 0.00 | 744.00 |
November | 42.23 | 0.00 | 42.23 | 7.79 | 130.54 | 0.00 | 0.00 | 720.00 |
December | 29.32 | 0.00 | 29.32 | 0.31 | 180.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 69.17 | 1.26 | 67.91 | 52.54 | 91.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.28 | 5.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.73 | 5.72 | 102.01 | 133.99 | 202.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.07 | 0.00 | 30.07 | 0.25 | 177.83 | 0.00 | 0.00 | 744.00 |
February | 41.16 | 0.00 | 41.16 | 1.48 | 181.34 | 0.00 | 0.00 | 672.00 |
March | 57.09 | 0.00 | 57.09 | 13.09 | 114.71 | 0.00 | 0.00 | 744.00 |
April | 68.70 | 0.28 | 68.42 | 35.74 | 74.67 | 0.00 | 0.00 | 720.00 |
May | 91.36 | 3.33 | 88.03 | 74.64 | 38.62 | 0.00 | 0.00 | 744.00 |
June | 96.38 | 5.12 | 91.27 | 105.28 | 15.80 | 0.00 | 0.00 | 720.00 |
July | 93.55 | 3.64 | 89.91 | 119.88 | 5.27 | 0.00 | 0.00 | 744.00 |
August | 82.73 | 1.09 | 81.64 | 106.85 | 10.39 | 0.00 | 0.00 | 744.00 |
September | 62.30 | 0.04 | 62.27 | 62.26 | 27.13 | 0.00 | 0.00 | 720.00 |
October | 53.87 | 0.00 | 53.87 | 33.70 | 64.16 | 0.00 | 0.00 | 744.00 |
November | 37.79 | 0.00 | 37.79 | 6.97 | 116.79 | 0.00 | 0.00 | 720.00 |
December | 26.23 | 0.00 | 26.23 | 0.27 | 161.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.89 | 1.13 | 60.76 | 47.01 | 81.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 26.23 | 0.00 | 26.23 | 0.25 | 5.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 96.38 | 5.12 | 91.27 | 119.88 | 181.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.06 | 337.99 | 177.07 | 454.30 | 507.13 | 0.00 | 0.00 | 744.00 |
February | 681.87 | 453.28 | 228.60 | 597.53 | 503.13 | 0.00 | 0.00 | 672.00 |
March | 604.12 | 332.65 | 271.47 | 508.85 | 357.79 | 0.00 | 0.00 | 744.00 |
April | 480.65 | 194.43 | 286.22 | 373.76 | 246.21 | 0.00 | 0.00 | 720.00 |
May | 412.80 | 84.46 | 328.34 | 343.32 | 135.88 | 0.00 | 0.00 | 744.00 |
June | 389.76 | 59.98 | 329.78 | 401.31 | 55.40 | 0.00 | 0.00 | 720.00 |
July | 405.57 | 68.39 | 337.18 | 472.67 | 17.85 | 0.00 | 0.00 | 744.00 |
August | 543.22 | 200.33 | 342.89 | 603.08 | 35.25 | 0.00 | 0.00 | 744.00 |
September | 573.40 | 287.93 | 285.48 | 615.58 | 88.91 | 0.00 | 0.00 | 720.00 |
October | 810.62 | 508.47 | 302.15 | 873.70 | 202.14 | 0.00 | 0.00 | 744.00 |
November | 561.10 | 336.61 | 224.48 | 535.28 | 344.65 | 0.00 | 0.00 | 720.00 |
December | 556.39 | 395.15 | 161.23 | 525.57 | 452.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.89 | 270.72 | 273.18 | 525.30 | 244.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.76 | 59.98 | 161.23 | 343.32 | 17.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 810.62 | 508.47 | 342.89 | 873.70 | 507.13 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187124E+10 | 0.122794E+10 | 0.643298E+09 | 0.166680E+10 | 0.169524E+10 |
February | 0.223753E+10 | 0.148740E+10 | 0.750132E+09 | 0.197130E+10 | 0.153162E+10 |
March | 0.219478E+10 | 0.120852E+10 | 0.986255E+09 | 0.184751E+10 | 0.120697E+10 |
April | 0.168989E+10 | 0.683582E+09 | 0.100631E+10 | 0.130745E+10 | 0.803560E+09 |
May | 0.149971E+10 | 0.306852E+09 | 0.119286E+10 | 0.124997E+10 | 0.455414E+09 |
June | 0.137034E+10 | 0.210887E+09 | 0.115945E+10 | 0.140877E+10 | 0.174866E+09 |
July | 0.147343E+10 | 0.248468E+09 | 0.122497E+10 | 0.170193E+10 | 54690538.96 |
August | 0.197353E+10 | 0.727800E+09 | 0.124573E+10 | 0.213391E+10 | 0.128570E+09 |
September | 0.201599E+10 | 0.101231E+10 | 0.100368E+10 | 0.212200E+10 | 0.310284E+09 |
October | 0.294500E+10 | 0.184729E+10 | 0.109771E+10 | 0.311883E+10 | 0.737982E+09 |
November | 0.197273E+10 | 0.118348E+10 | 0.789250E+09 | 0.187876E+10 | 0.113852E+10 |
December | 0.202137E+10 | 0.143560E+10 | 0.585767E+09 | 0.191173E+10 | 0.152569E+10 |
Annual Sum or Average | 0.232656E+11 | 0.115801E+11 | 0.116854E+11 | 0.223190E+11 | 0.976341E+10 |
Minimum of Months | 0.137034E+10 | 0.210887E+09 | 0.585767E+09 | 0.124997E+10 | 54690538.96 |
Maximum of Months | 0.294500E+10 | 0.184729E+10 | 0.124573E+10 | 0.311883E+10 | 0.169524E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.526929E+10 | 0.345781E+10 | 0.181148E+10 | 0.464367E+10 | 0.490534E+10 |
February | 0.630074E+10 | 0.418842E+10 | 0.211232E+10 | 0.549083E+10 | 0.443614E+10 |
March | 0.618035E+10 | 0.340312E+10 | 0.277723E+10 | 0.513672E+10 | 0.359856E+10 |
April | 0.475863E+10 | 0.192492E+10 | 0.283371E+10 | 0.360752E+10 | 0.245488E+10 |
May | 0.422310E+10 | 0.864076E+09 | 0.335902E+10 | 0.341769E+10 | 0.144744E+10 |
June | 0.385879E+10 | 0.593843E+09 | 0.326494E+10 | 0.387438E+10 | 0.604017E+09 |
July | 0.414909E+10 | 0.699668E+09 | 0.344942E+10 | 0.469462E+10 | 0.229094E+09 |
August | 0.555733E+10 | 0.204944E+10 | 0.350789E+10 | 0.593490E+10 | 0.442847E+09 |
September | 0.567690E+10 | 0.285060E+10 | 0.282631E+10 | 0.590364E+10 | 0.101977E+10 |
October | 0.829292E+10 | 0.520184E+10 | 0.309108E+10 | 0.869451E+10 | 0.228860E+10 |
November | 0.555507E+10 | 0.333260E+10 | 0.222247E+10 | 0.521353E+10 | 0.340086E+10 |
December | 0.569205E+10 | 0.404257E+10 | 0.164948E+10 | 0.532417E+10 | 0.446490E+10 |
Annual Sum or Average | 0.655143E+11 | 0.326089E+11 | 0.329054E+11 | 0.619362E+11 | 0.292925E+11 |
Minimum of Months | 0.385879E+10 | 0.593843E+09 | 0.164948E+10 | 0.341769E+10 | 0.229094E+09 |
Maximum of Months | 0.829292E+10 | 0.520184E+10 | 0.350789E+10 | 0.869451E+10 | 0.490534E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.684511E+10 | 0.449189E+10 | 0.235322E+10 | 0.612976E+10 | 0.668585E+10 |
February | 0.818502E+10 | 0.544100E+10 | 0.274403E+10 | 0.726743E+10 | 0.600588E+10 |
March | 0.802863E+10 | 0.442085E+10 | 0.360778E+10 | 0.680737E+10 | 0.488530E+10 |
April | 0.618173E+10 | 0.250058E+10 | 0.368115E+10 | 0.478183E+10 | 0.334939E+10 |
May | 0.548604E+10 | 0.112248E+10 | 0.436356E+10 | 0.454536E+10 | 0.196179E+10 |
June | 0.501278E+10 | 0.771436E+09 | 0.424135E+10 | 0.518924E+10 | 0.796643E+09 |
July | 0.538991E+10 | 0.908909E+09 | 0.448100E+10 | 0.631897E+10 | 0.287800E+09 |
August | 0.721928E+10 | 0.266233E+10 | 0.455695E+10 | 0.799637E+10 | 0.551046E+09 |
September | 0.737462E+10 | 0.370309E+10 | 0.367153E+10 | 0.789640E+10 | 0.131985E+10 |
October | 0.107730E+11 | 0.675749E+10 | 0.401548E+10 | 0.115759E+11 | 0.299829E+10 |
November | 0.721636E+10 | 0.432923E+10 | 0.288712E+10 | 0.688717E+10 | 0.463272E+10 |
December | 0.739430E+10 | 0.525153E+10 | 0.214277E+10 | 0.702792E+10 | 0.608764E+10 |
Annual Sum or Average | 0.851068E+11 | 0.423608E+11 | 0.427459E+11 | 0.824238E+11 | 0.395622E+11 |
Minimum of Months | 0.501278E+10 | 0.771436E+09 | 0.214277E+10 | 0.454536E+10 | 0.287800E+09 |
Maximum of Months | 0.107730E+11 | 0.675749E+10 | 0.455695E+10 | 0.115759E+11 | 0.668585E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369222E+09 | 0.242291E+09 | 0.126932E+09 | 0.329977E+09 | 0.347501E+09 |
February | 0.441497E+09 | 0.293485E+09 | 0.148012E+09 | 0.390306E+09 | 0.315087E+09 |
March | 0.433061E+09 | 0.238459E+09 | 0.194602E+09 | 0.365627E+09 | 0.249227E+09 |
April | 0.333440E+09 | 0.134881E+09 | 0.198560E+09 | 0.258036E+09 | 0.165671E+09 |
May | 0.295915E+09 | 60546334.37 | 0.235369E+09 | 0.242492E+09 | 93969930.28 |
June | 0.270387E+09 | 41610922.52 | 0.228776E+09 | 0.276623E+09 | 33038080.62 |
July | 0.290729E+09 | 49026188.83 | 0.241703E+09 | 0.344913E+09 | 7644251.04 |
August | 0.389405E+09 | 0.143605E+09 | 0.245800E+09 | 0.437196E+09 | 19708112.03 |
September | 0.397784E+09 | 0.199743E+09 | 0.198041E+09 | 0.425088E+09 | 57034540.52 |
October | 0.581090E+09 | 0.364496E+09 | 0.216594E+09 | 0.623113E+09 | 0.141203E+09 |
November | 0.389247E+09 | 0.233517E+09 | 0.155730E+09 | 0.374151E+09 | 0.228923E+09 |
December | 0.398845E+09 | 0.283265E+09 | 0.115580E+09 | 0.380436E+09 | 0.309882E+09 |
Annual Sum or Average | 0.459062E+10 | 0.228493E+10 | 0.230570E+10 | 0.444796E+10 | 0.196889E+10 |
Minimum of Months | 0.270387E+09 | 41610922.52 | 0.115580E+09 | 0.242492E+09 | 7644251.04 |
Maximum of Months | 0.581090E+09 | 0.364496E+09 | 0.245800E+09 | 0.623113E+09 | 0.347501E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274439E+09 | 0.112682E+09 | 0.161757E+09 | 0.122134E+09 | 0.707167E+09 |
February | 0.364088E+09 | 0.159789E+09 | 0.204299E+09 | 0.188376E+09 | 0.646480E+09 |
March | 0.598796E+09 | 0.277523E+09 | 0.321273E+09 | 0.445824E+09 | 0.459819E+09 |
April | 0.629334E+09 | 0.268953E+09 | 0.360381E+09 | 0.553101E+09 | 0.301621E+09 |
May | 0.759606E+09 | 0.288709E+09 | 0.470897E+09 | 0.777560E+09 | 0.169245E+09 |
June | 0.803149E+09 | 0.324077E+09 | 0.479072E+09 | 0.942945E+09 | 60081061.69 |
July | 0.776478E+09 | 0.291750E+09 | 0.484729E+09 | 0.100030E+10 | 14100721.24 |
August | 0.859147E+09 | 0.397227E+09 | 0.461921E+09 | 0.109804E+10 | 36561942.97 |
September | 0.591596E+09 | 0.258296E+09 | 0.333300E+09 | 0.660615E+09 | 0.106594E+09 |
October | 0.606525E+09 | 0.295462E+09 | 0.311063E+09 | 0.578189E+09 | 0.269222E+09 |
November | 0.276418E+09 | 80756499.71 | 0.195662E+09 | 0.139872E+09 | 0.457051E+09 |
December | 0.252323E+09 | 0.108939E+09 | 0.143384E+09 | 0.113208E+09 | 0.640891E+09 |
Annual Sum or Average | 0.679190E+10 | 0.286416E+10 | 0.392774E+10 | 0.662016E+10 | 0.386884E+10 |
Minimum of Months | 0.252323E+09 | 80756499.71 | 0.143384E+09 | 0.113208E+09 | 14100721.24 |
Maximum of Months | 0.859147E+09 | 0.397227E+09 | 0.484729E+09 | 0.109804E+10 | 0.707167E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71032979.27 | 0.00 | 71032979.27 | 1968772.14 | 0.392755E+09 |
February | 87798621.79 | 0.00 | 87798621.79 | 5004210.04 | 0.364574E+09 |
March | 0.134831E+09 | 2680.57 | 0.134829E+09 | 35882188.16 | 0.259385E+09 |
April | 0.157017E+09 | 640006.32 | 0.156377E+09 | 83383591.22 | 0.163999E+09 |
May | 0.215787E+09 | 7874871.82 | 0.207913E+09 | 0.174401E+09 | 87142633.41 |
June | 0.220304E+09 | 11691944.98 | 0.208612E+09 | 0.240125E+09 | 30666385.49 |
July | 0.220959E+09 | 8600659.13 | 0.212359E+09 | 0.290969E+09 | 7263005.41 |
August | 0.195406E+09 | 2579465.32 | 0.192826E+09 | 0.260184E+09 | 18674172.80 |
September | 0.142400E+09 | 80917.76 | 0.142319E+09 | 0.143904E+09 | 56030282.78 |
October | 0.127242E+09 | 0.00 | 0.127242E+09 | 82969416.14 | 0.144377E+09 |
November | 86368820.55 | 0.00 | 86368820.55 | 19716507.66 | 0.248605E+09 |
December | 61959633.27 | 0.00 | 61959633.27 | 1528275.38 | 0.354437E+09 |
Annual Sum or Average | 0.172111E+10 | 31470545.90 | 0.168964E+10 | 0.134004E+10 | 0.212791E+10 |
Minimum of Months | 61959633.27 | 0.00 | 61959633.27 | 1528275.38 | 7263005.41 |
Maximum of Months | 0.220959E+09 | 11691944.98 | 0.212359E+09 | 0.290969E+09 | 0.392755E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274439E+09 | 0.112682E+09 | 0.161757E+09 | 0.129121E+09 | 0.697887E+09 |
February | 0.364088E+09 | 0.159789E+09 | 0.204299E+09 | 0.197919E+09 | 0.635349E+09 |
March | 0.598796E+09 | 0.277523E+09 | 0.321273E+09 | 0.458253E+09 | 0.453124E+09 |
April | 0.629334E+09 | 0.268953E+09 | 0.360381E+09 | 0.560102E+09 | 0.298742E+09 |
May | 0.759606E+09 | 0.288709E+09 | 0.470897E+09 | 0.780424E+09 | 0.168329E+09 |
June | 0.803149E+09 | 0.324077E+09 | 0.479072E+09 | 0.944386E+09 | 59683102.65 |
July | 0.776478E+09 | 0.291750E+09 | 0.484729E+09 | 0.100197E+10 | 13907150.86 |
August | 0.859147E+09 | 0.397227E+09 | 0.461921E+09 | 0.110265E+10 | 35719309.41 |
September | 0.591596E+09 | 0.258296E+09 | 0.333300E+09 | 0.668845E+09 | 0.104095E+09 |
October | 0.606525E+09 | 0.295462E+09 | 0.311063E+09 | 0.594527E+09 | 0.262498E+09 |
November | 0.276418E+09 | 80756499.71 | 0.195662E+09 | 0.150361E+09 | 0.448170E+09 |
December | 0.252323E+09 | 0.108939E+09 | 0.143384E+09 | 0.121621E+09 | 0.629295E+09 |
Annual Sum or Average | 0.679190E+10 | 0.286416E+10 | 0.392774E+10 | 0.671019E+10 | 0.380680E+10 |
Minimum of Months | 0.252323E+09 | 80756499.71 | 0.143384E+09 | 0.121621E+09 | 13907150.86 |
Maximum of Months | 0.859147E+09 | 0.397227E+09 | 0.484729E+09 | 0.110265E+10 | 0.697887E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295319E+09 | 0.193794E+09 | 0.101525E+09 | 0.262960E+09 | 0.270671E+09 |
February | 0.353127E+09 | 0.234741E+09 | 0.118386E+09 | 0.308138E+09 | 0.255405E+09 |
March | 0.346380E+09 | 0.190729E+09 | 0.155651E+09 | 0.290295E+09 | 0.206456E+09 |
April | 0.266699E+09 | 0.107883E+09 | 0.158816E+09 | 0.204349E+09 | 0.140231E+09 |
May | 0.236685E+09 | 48427436.58 | 0.188257E+09 | 0.187849E+09 | 87778730.22 |
June | 0.216267E+09 | 33282119.10 | 0.182985E+09 | 0.214416E+09 | 37813749.59 |
July | 0.232537E+09 | 39213152.63 | 0.193324E+09 | 0.264912E+09 | 14420058.62 |
August | 0.311462E+09 | 0.114861E+09 | 0.196601E+09 | 0.340237E+09 | 25217090.42 |
September | 0.318164E+09 | 0.159763E+09 | 0.158401E+09 | 0.331938E+09 | 61818532.38 |
October | 0.464780E+09 | 0.291539E+09 | 0.173240E+09 | 0.489660E+09 | 0.135102E+09 |
November | 0.311336E+09 | 0.186777E+09 | 0.124559E+09 | 0.291803E+09 | 0.197197E+09 |
December | 0.319013E+09 | 0.226567E+09 | 92445660.92 | 0.299835E+09 | 0.251158E+09 |
Annual Sum or Average | 0.367177E+10 | 0.182758E+10 | 0.184419E+10 | 0.348639E+10 | 0.168327E+10 |
Minimum of Months | 0.216267E+09 | 33282119.10 | 92445660.92 | 0.187849E+09 | 14420058.62 |
Maximum of Months | 0.464780E+09 | 0.291539E+09 | 0.196601E+09 | 0.489660E+09 | 0.270671E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56833916.07 | 0.00 | 56833916.07 | 1002423.82 | 0.327299E+09 |
February | 70248208.00 | 0.00 | 70248208.00 | 3471059.77 | 0.300807E+09 |
March | 0.107879E+09 | 2144.74 | 0.107877E+09 | 28548208.06 | 0.211515E+09 |
April | 0.125630E+09 | 512072.92 | 0.125118E+09 | 69006833.90 | 0.133188E+09 |
May | 0.172653E+09 | 6300732.54 | 0.166352E+09 | 0.145991E+09 | 69109652.33 |
June | 0.176266E+09 | 9354795.85 | 0.166911E+09 | 0.202634E+09 | 22607249.29 |
July | 0.176791E+09 | 6881439.35 | 0.169909E+09 | 0.244833E+09 | 4590424.23 |
August | 0.156345E+09 | 2063845.80 | 0.154281E+09 | 0.221438E+09 | 12999248.07 |
September | 0.113935E+09 | 64742.79 | 0.113870E+09 | 0.122209E+09 | 43137929.33 |
October | 0.101807E+09 | 0.00 | 0.101807E+09 | 70375547.27 | 0.114565E+09 |
November | 69104215.38 | 0.00 | 69104215.38 | 14916829.74 | 0.207738E+09 |
December | 49574277.10 | 0.00 | 49574277.10 | 866806.89 | 0.296329E+09 |
Annual Sum or Average | 0.137707E+10 | 25179774.00 | 0.135189E+10 | 0.112529E+10 | 0.174388E+10 |
Minimum of Months | 49574277.10 | 0.00 | 49574277.10 | 866806.89 | 4590424.23 |
Maximum of Months | 0.176791E+09 | 9354795.85 | 0.169909E+09 | 0.244833E+09 | 0.327299E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276359E+09 | 0.110431E+09 | 0.165927E+09 | 0.114166E+09 | 0.694665E+09 |
February | 0.387514E+09 | 0.180460E+09 | 0.207053E+09 | 0.200793E+09 | 0.623257E+09 |
March | 0.550936E+09 | 0.234143E+09 | 0.316792E+09 | 0.390080E+09 | 0.461457E+09 |
April | 0.638279E+09 | 0.280168E+09 | 0.358111E+09 | 0.553114E+09 | 0.291867E+09 |
May | 0.796159E+09 | 0.317237E+09 | 0.478921E+09 | 0.815943E+09 | 0.163445E+09 |
June | 0.715441E+09 | 0.259097E+09 | 0.456344E+09 | 0.833384E+09 | 57024821.72 |
July | 0.741547E+09 | 0.266926E+09 | 0.474621E+09 | 0.959071E+09 | 13258127.02 |
August | 0.836605E+09 | 0.377432E+09 | 0.459174E+09 | 0.106788E+10 | 34068950.76 |
September | 0.605692E+09 | 0.272886E+09 | 0.332806E+09 | 0.670848E+09 | 0.101698E+09 |
October | 0.565403E+09 | 0.255942E+09 | 0.309461E+09 | 0.520029E+09 | 0.261514E+09 |
November | 0.338905E+09 | 0.130247E+09 | 0.208658E+09 | 0.201316E+09 | 0.443492E+09 |
December | 0.273816E+09 | 0.129221E+09 | 0.144595E+09 | 0.126715E+09 | 0.625061E+09 |
Annual Sum or Average | 0.672665E+10 | 0.281419E+10 | 0.391246E+10 | 0.645334E+10 | 0.377081E+10 |
Minimum of Months | 0.273816E+09 | 0.110431E+09 | 0.144595E+09 | 0.114166E+09 | 13258127.02 |
Maximum of Months | 0.836605E+09 | 0.377432E+09 | 0.478921E+09 | 0.106788E+10 | 0.694665E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369222E+09 | 0.242291E+09 | 0.126932E+09 | 0.329123E+09 | 0.347003E+09 |
February | 0.441497E+09 | 0.293485E+09 | 0.148012E+09 | 0.388499E+09 | 0.314358E+09 |
March | 0.433061E+09 | 0.238459E+09 | 0.194602E+09 | 0.363303E+09 | 0.246953E+09 |
April | 0.333440E+09 | 0.134881E+09 | 0.198560E+09 | 0.255141E+09 | 0.164550E+09 |
May | 0.295915E+09 | 60546334.37 | 0.235369E+09 | 0.239018E+09 | 92736534.41 |
June | 0.270387E+09 | 41610922.52 | 0.228776E+09 | 0.276364E+09 | 31939482.29 |
July | 0.290729E+09 | 49026188.83 | 0.241703E+09 | 0.344451E+09 | 7247128.63 |
August | 0.389405E+09 | 0.143605E+09 | 0.245800E+09 | 0.435954E+09 | 19018936.39 |
September | 0.397784E+09 | 0.199743E+09 | 0.198041E+09 | 0.423351E+09 | 56284711.84 |
October | 0.581090E+09 | 0.364496E+09 | 0.216594E+09 | 0.621460E+09 | 0.139756E+09 |
November | 0.389247E+09 | 0.233517E+09 | 0.155730E+09 | 0.372180E+09 | 0.229114E+09 |
December | 0.398845E+09 | 0.283265E+09 | 0.115580E+09 | 0.379307E+09 | 0.309515E+09 |
Annual Sum or Average | 0.459062E+10 | 0.228493E+10 | 0.230570E+10 | 0.442815E+10 | 0.195848E+10 |
Minimum of Months | 0.270387E+09 | 41610922.52 | 0.115580E+09 | 0.239018E+09 | 7247128.63 |
Maximum of Months | 0.581090E+09 | 0.364496E+09 | 0.245800E+09 | 0.621460E+09 | 0.347003E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71032979.27 | 0.00 | 71032979.27 | 1679699.91 | 0.392751E+09 |
February | 87798621.79 | 0.00 | 87798621.79 | 4579301.23 | 0.364960E+09 |
March | 0.134831E+09 | 2680.57 | 0.134829E+09 | 34069266.58 | 0.257562E+09 |
April | 0.157017E+09 | 640006.32 | 0.156377E+09 | 80721962.55 | 0.163313E+09 |
May | 0.215787E+09 | 7874871.82 | 0.207913E+09 | 0.171004E+09 | 86123747.46 |
June | 0.220304E+09 | 11691944.98 | 0.208612E+09 | 0.240026E+09 | 29710889.77 |
July | 0.220959E+09 | 8600659.13 | 0.212359E+09 | 0.290523E+09 | 6874343.52 |
August | 0.195406E+09 | 2579465.32 | 0.192826E+09 | 0.258798E+09 | 18004441.90 |
September | 0.142400E+09 | 80917.76 | 0.142319E+09 | 0.141761E+09 | 55467085.70 |
October | 0.127242E+09 | 0.00 | 0.127242E+09 | 81043652.60 | 0.142560E+09 |
November | 86368820.55 | 0.00 | 86368820.55 | 18537057.08 | 0.249587E+09 |
December | 61959633.27 | 0.00 | 61959633.27 | 1268905.55 | 0.354605E+09 |
Annual Sum or Average | 0.172111E+10 | 31470545.90 | 0.168964E+10 | 0.132401E+10 | 0.212152E+10 |
Minimum of Months | 61959633.27 | 0.00 | 61959633.27 | 1268905.55 | 6874343.52 |
Maximum of Months | 0.220959E+09 | 11691944.98 | 0.212359E+09 | 0.290523E+09 | 0.392751E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276359E+09 | 0.110431E+09 | 0.165927E+09 | 0.117878E+09 | 0.682217E+09 |
February | 0.387514E+09 | 0.180460E+09 | 0.207053E+09 | 0.206329E+09 | 0.607839E+09 |
March | 0.550936E+09 | 0.234143E+09 | 0.316792E+09 | 0.400680E+09 | 0.452780E+09 |
April | 0.638279E+09 | 0.280168E+09 | 0.358111E+09 | 0.559540E+09 | 0.288665E+09 |
May | 0.796159E+09 | 0.317237E+09 | 0.478921E+09 | 0.818595E+09 | 0.162461E+09 |
June | 0.715441E+09 | 0.259097E+09 | 0.456344E+09 | 0.834813E+09 | 56659804.16 |
July | 0.741547E+09 | 0.266926E+09 | 0.474621E+09 | 0.960750E+09 | 13094400.18 |
August | 0.836605E+09 | 0.377432E+09 | 0.459174E+09 | 0.107217E+10 | 33254382.18 |
September | 0.605692E+09 | 0.272886E+09 | 0.332806E+09 | 0.678153E+09 | 99170897.21 |
October | 0.565403E+09 | 0.255942E+09 | 0.309461E+09 | 0.535375E+09 | 0.253719E+09 |
November | 0.338905E+09 | 0.130247E+09 | 0.208658E+09 | 0.210087E+09 | 0.433300E+09 |
December | 0.273816E+09 | 0.129221E+09 | 0.144595E+09 | 0.130912E+09 | 0.609241E+09 |
Annual Sum or Average | 0.672665E+10 | 0.281419E+10 | 0.391246E+10 | 0.652528E+10 | 0.369240E+10 |
Minimum of Months | 0.273816E+09 | 0.110431E+09 | 0.144595E+09 | 0.117878E+09 | 13094400.18 |
Maximum of Months | 0.836605E+09 | 0.377432E+09 | 0.478921E+09 | 0.107217E+10 | 0.682217E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89958786.31 | 0.00 | 89958786.31 | 1252978.35 | 0.520364E+09 |
February | 0.111191E+09 | 0.00 | 0.111191E+09 | 5089770.77 | 0.478831E+09 |
March | 0.170755E+09 | 3394.77 | 0.170752E+09 | 44801503.10 | 0.332368E+09 |
April | 0.198852E+09 | 810527.62 | 0.198042E+09 | 0.112495E+09 | 0.206591E+09 |
May | 0.273281E+09 | 9973028.28 | 0.263308E+09 | 0.240012E+09 | 0.105914E+09 |
June | 0.279001E+09 | 14807110.60 | 0.264193E+09 | 0.330520E+09 | 34031104.67 |
July | 0.279831E+09 | 10892192.11 | 0.268939E+09 | 0.396409E+09 | 6874589.83 |
August | 0.247469E+09 | 3266730.08 | 0.244202E+09 | 0.354354E+09 | 20930742.60 |
September | 0.180340E+09 | 102477.24 | 0.180238E+09 | 0.197746E+09 | 66580791.94 |
October | 0.161143E+09 | 0.00 | 0.161143E+09 | 0.112178E+09 | 0.180079E+09 |
November | 0.109381E+09 | 0.00 | 0.109381E+09 | 23722704.01 | 0.327241E+09 |
December | 78467966.10 | 0.00 | 78467966.10 | 1143424.59 | 0.471786E+09 |
Annual Sum or Average | 0.217967E+10 | 39855460.70 | 0.213982E+10 | 0.181972E+10 | 0.275159E+10 |
Minimum of Months | 78467966.10 | 0.00 | 78467966.10 | 1143424.59 | 6874589.83 |
Maximum of Months | 0.279831E+09 | 14807110.60 | 0.268939E+09 | 0.396409E+09 | 0.520364E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33162533.53 | 0.00 | 33162533.53 | 461899.70 | 0.191828E+09 |
February | 40989759.54 | 0.00 | 40989759.54 | 1876300.26 | 0.176517E+09 |
March | 62947521.07 | 1251.45 | 62946269.62 | 16515689.13 | 0.122525E+09 |
April | 73305102.21 | 298794.04 | 73006308.17 | 41470407.38 | 76157951.53 |
May | 0.100743E+09 | 3676471.18 | 97066309.93 | 88478246.11 | 39044235.86 |
June | 0.102851E+09 | 5458514.08 | 97392637.47 | 0.121843E+09 | 12545274.30 |
July | 0.103157E+09 | 4015313.02 | 99141995.32 | 0.146133E+09 | 2534258.46 |
August | 91227314.35 | 1204251.97 | 90023062.38 | 0.130630E+09 | 7715938.39 |
September | 66480944.15 | 37777.35 | 66443166.80 | 72897307.84 | 24544436.80 |
October | 59404151.36 | 0.00 | 59404151.36 | 41353504.37 | 66384564.13 |
November | 40322240.98 | 0.00 | 40322240.98 | 8745170.98 | 0.120635E+09 |
December | 28926541.41 | 0.00 | 28926541.41 | 421513.65 | 0.173920E+09 |
Annual Sum or Average | 0.803517E+09 | 14692373.10 | 0.788825E+09 | 0.670826E+09 | 0.101435E+10 |
Minimum of Months | 28926541.41 | 0.00 | 28926541.41 | 421513.65 | 2534258.46 |
Maximum of Months | 0.103157E+09 | 5458514.08 | 99141995.32 | 0.146133E+09 | 0.191828E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172278E+09 | 0.113052E+09 | 59225872.13 | 0.154227E+09 | 0.166408E+09 |
February | 0.206001E+09 | 0.136939E+09 | 69061666.91 | 0.183168E+09 | 0.149329E+09 |
March | 0.202065E+09 | 0.111264E+09 | 90800538.83 | 0.173373E+09 | 0.115988E+09 |
April | 0.155582E+09 | 62934711.94 | 92647121.25 | 0.124533E+09 | 75922950.81 |
May | 0.138073E+09 | 28250675.63 | 0.109822E+09 | 0.120613E+09 | 41384168.94 |
June | 0.126162E+09 | 19415488.77 | 0.106746E+09 | 0.139081E+09 | 13198366.23 |
July | 0.135653E+09 | 22875422.15 | 0.112778E+09 | 0.171798E+09 | 2589077.22 |
August | 0.181695E+09 | 67005630.63 | 0.114689E+09 | 0.214262E+09 | 7879798.35 |
September | 0.185604E+09 | 93199279.81 | 92405158.22 | 0.206008E+09 | 24263007.50 |
October | 0.271134E+09 | 0.170073E+09 | 0.101062E+09 | 0.297735E+09 | 63427668.73 |
November | 0.181621E+09 | 0.108958E+09 | 72663060.32 | 0.176301E+09 | 0.108303E+09 |
December | 0.186100E+09 | 0.132170E+09 | 53929189.00 | 0.178327E+09 | 0.148109E+09 |
Annual Sum or Average | 0.214197E+10 | 0.106614E+10 | 0.107583E+10 | 0.213943E+10 | 0.916802E+09 |
Minimum of Months | 0.126162E+09 | 19415488.77 | 53929189.00 | 0.120613E+09 | 2589077.22 |
Maximum of Months | 0.271134E+09 | 0.170073E+09 | 0.114689E+09 | 0.297735E+09 | 0.166408E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.467597E+09 | 0.306846E+09 | 0.160751E+09 | 0.418603E+09 | 0.451666E+09 |
February | 0.559128E+09 | 0.371680E+09 | 0.187447E+09 | 0.497157E+09 | 0.405309E+09 |
March | 0.548445E+09 | 0.301993E+09 | 0.246451E+09 | 0.470570E+09 | 0.314814E+09 |
April | 0.422281E+09 | 0.170818E+09 | 0.251463E+09 | 0.338007E+09 | 0.206070E+09 |
May | 0.374758E+09 | 76678112.22 | 0.298080E+09 | 0.327369E+09 | 0.112325E+09 |
June | 0.342429E+09 | 52697607.87 | 0.289731E+09 | 0.377495E+09 | 35823065.62 |
July | 0.368190E+09 | 62088574.78 | 0.306102E+09 | 0.466294E+09 | 7027285.16 |
August | 0.493157E+09 | 0.181867E+09 | 0.311290E+09 | 0.581551E+09 | 21387384.50 |
September | 0.503768E+09 | 0.252962E+09 | 0.250807E+09 | 0.559147E+09 | 65854765.25 |
October | 0.735914E+09 | 0.461612E+09 | 0.274302E+09 | 0.808113E+09 | 0.172156E+09 |
November | 0.492957E+09 | 0.295735E+09 | 0.197222E+09 | 0.478517E+09 | 0.293956E+09 |
December | 0.505112E+09 | 0.358738E+09 | 0.146375E+09 | 0.484016E+09 | 0.401999E+09 |
Annual Sum or Average | 0.581374E+10 | 0.289371E+10 | 0.292002E+10 | 0.580684E+10 | 0.248839E+10 |
Minimum of Months | 0.342429E+09 | 52697607.87 | 0.146375E+09 | 0.327369E+09 | 7027285.16 |
Maximum of Months | 0.735914E+09 | 0.461612E+09 | 0.311290E+09 | 0.808113E+09 | 0.451666E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369525E+09 | 0.242489E+09 | 0.127036E+09 | 0.329312E+09 | 0.346603E+09 |
February | 0.441859E+09 | 0.293726E+09 | 0.148133E+09 | 0.389382E+09 | 0.314670E+09 |
March | 0.433416E+09 | 0.238655E+09 | 0.194762E+09 | 0.364366E+09 | 0.249298E+09 |
April | 0.333714E+09 | 0.134991E+09 | 0.198723E+09 | 0.256703E+09 | 0.165892E+09 |
May | 0.296158E+09 | 60596003.23 | 0.235562E+09 | 0.239267E+09 | 94870196.91 |
June | 0.270609E+09 | 41645057.81 | 0.228964E+09 | 0.273049E+09 | 33711501.91 |
July | 0.290968E+09 | 49066407.20 | 0.241902E+09 | 0.341450E+09 | 7854629.32 |
August | 0.389725E+09 | 0.143723E+09 | 0.246002E+09 | 0.434583E+09 | 19785234.40 |
September | 0.398110E+09 | 0.199907E+09 | 0.198204E+09 | 0.422190E+09 | 57518274.01 |
October | 0.581567E+09 | 0.364795E+09 | 0.216771E+09 | 0.620191E+09 | 0.141237E+09 |
November | 0.389567E+09 | 0.233709E+09 | 0.155858E+09 | 0.373375E+09 | 0.227659E+09 |
December | 0.399172E+09 | 0.283498E+09 | 0.115675E+09 | 0.379968E+09 | 0.308474E+09 |
Annual Sum or Average | 0.459439E+10 | 0.228680E+10 | 0.230759E+10 | 0.442384E+10 | 0.196757E+10 |
Minimum of Months | 0.270609E+09 | 41645057.81 | 0.115675E+09 | 0.239267E+09 | 7854629.32 |
Maximum of Months | 0.581567E+09 | 0.364795E+09 | 0.246002E+09 | 0.620191E+09 | 0.346603E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274664E+09 | 0.112774E+09 | 0.161890E+09 | 0.122316E+09 | 0.705507E+09 |
February | 0.364386E+09 | 0.159920E+09 | 0.204466E+09 | 0.187693E+09 | 0.646191E+09 |
March | 0.599288E+09 | 0.277751E+09 | 0.321537E+09 | 0.442808E+09 | 0.459267E+09 |
April | 0.629850E+09 | 0.269174E+09 | 0.360676E+09 | 0.548624E+09 | 0.301308E+09 |
May | 0.760229E+09 | 0.288945E+09 | 0.471284E+09 | 0.769082E+09 | 0.170214E+09 |
June | 0.803808E+09 | 0.324343E+09 | 0.479465E+09 | 0.933746E+09 | 61121023.67 |
July | 0.777115E+09 | 0.291989E+09 | 0.485127E+09 | 0.991517E+09 | 14494990.04 |
August | 0.859852E+09 | 0.397553E+09 | 0.462300E+09 | 0.109058E+10 | 36663700.73 |
September | 0.592081E+09 | 0.258508E+09 | 0.333573E+09 | 0.654561E+09 | 0.107288E+09 |
October | 0.607022E+09 | 0.295704E+09 | 0.311318E+09 | 0.573777E+09 | 0.269021E+09 |
November | 0.276645E+09 | 80822747.87 | 0.195822E+09 | 0.139734E+09 | 0.454522E+09 |
December | 0.252530E+09 | 0.109028E+09 | 0.143502E+09 | 0.113593E+09 | 0.637973E+09 |
Annual Sum or Average | 0.679747E+10 | 0.286651E+10 | 0.393096E+10 | 0.656803E+10 | 0.386357E+10 |
Minimum of Months | 0.252530E+09 | 80822747.87 | 0.143502E+09 | 0.113593E+09 | 14494990.04 |
Maximum of Months | 0.859852E+09 | 0.397553E+09 | 0.485127E+09 | 0.109058E+10 | 0.705507E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71091250.78 | 0.00 | 71091250.78 | 2144878.21 | 0.391426E+09 |
February | 87870646.91 | 0.00 | 87870646.91 | 5160363.03 | 0.364180E+09 |
March | 0.134942E+09 | 2682.76 | 0.134939E+09 | 35835316.35 | 0.258986E+09 |
April | 0.157146E+09 | 640531.34 | 0.156505E+09 | 82085271.83 | 0.163793E+09 |
May | 0.215965E+09 | 7881331.93 | 0.208083E+09 | 0.170430E+09 | 87807433.04 |
June | 0.220484E+09 | 11701536.40 | 0.208783E+09 | 0.235870E+09 | 31241049.09 |
July | 0.221141E+09 | 8607714.63 | 0.212533E+09 | 0.286505E+09 | 7534796.58 |
August | 0.195566E+09 | 2581581.37 | 0.192984E+09 | 0.256677E+09 | 18731627.56 |
September | 0.142517E+09 | 80984.14 | 0.142436E+09 | 0.140966E+09 | 56463231.04 |
October | 0.127346E+09 | 0.00 | 0.127346E+09 | 81917352.48 | 0.143972E+09 |
November | 86439672.74 | 0.00 | 86439672.74 | 20041174.06 | 0.246457E+09 |
December | 62010461.52 | 0.00 | 62010461.52 | 1701783.14 | 0.351983E+09 |
Annual Sum or Average | 0.172252E+10 | 31496362.59 | 0.169102E+10 | 0.131933E+10 | 0.212257E+10 |
Minimum of Months | 62010461.52 | 0.00 | 62010461.52 | 1701783.14 | 7534796.58 |
Maximum of Months | 0.221141E+09 | 11701536.40 | 0.212533E+09 | 0.286505E+09 | 0.391426E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274664E+09 | 0.112774E+09 | 0.161890E+09 | 0.129466E+09 | 0.696505E+09 |
February | 0.364386E+09 | 0.159920E+09 | 0.204466E+09 | 0.197747E+09 | 0.635344E+09 |
March | 0.599288E+09 | 0.277751E+09 | 0.321537E+09 | 0.456327E+09 | 0.452172E+09 |
April | 0.629850E+09 | 0.269174E+09 | 0.360676E+09 | 0.555936E+09 | 0.298243E+09 |
May | 0.760229E+09 | 0.288945E+09 | 0.471284E+09 | 0.771845E+09 | 0.169274E+09 |
June | 0.803808E+09 | 0.324343E+09 | 0.479465E+09 | 0.935002E+09 | 60752340.41 |
July | 0.777115E+09 | 0.291989E+09 | 0.485127E+09 | 0.993059E+09 | 14312315.35 |
August | 0.859852E+09 | 0.397553E+09 | 0.462300E+09 | 0.109506E+10 | 35818864.34 |
September | 0.592081E+09 | 0.258508E+09 | 0.333573E+09 | 0.662445E+09 | 0.104712E+09 |
October | 0.607022E+09 | 0.295704E+09 | 0.311318E+09 | 0.590966E+09 | 0.261611E+09 |
November | 0.276645E+09 | 80822747.87 | 0.195822E+09 | 0.151019E+09 | 0.445211E+09 |
December | 0.252530E+09 | 0.109028E+09 | 0.143502E+09 | 0.122661E+09 | 0.626524E+09 |
Annual Sum or Average | 0.679747E+10 | 0.286651E+10 | 0.393096E+10 | 0.666153E+10 | 0.380048E+10 |
Minimum of Months | 0.252530E+09 | 80822747.87 | 0.143502E+09 | 0.122661E+09 | 14312315.35 |
Maximum of Months | 0.859852E+09 | 0.397553E+09 | 0.485127E+09 | 0.109506E+10 | 0.696505E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541944E+09 | 0.355634E+09 | 0.186310E+09 | 0.467070E+09 | 0.526507E+09 |
February | 0.648029E+09 | 0.430777E+09 | 0.217251E+09 | 0.552927E+09 | 0.478575E+09 |
March | 0.635647E+09 | 0.350010E+09 | 0.285637E+09 | 0.523830E+09 | 0.374244E+09 |
April | 0.489423E+09 | 0.197978E+09 | 0.291446E+09 | 0.373008E+09 | 0.245456E+09 |
May | 0.434344E+09 | 88869854.15 | 0.345474E+09 | 0.355473E+09 | 0.136493E+09 |
June | 0.396874E+09 | 61076473.97 | 0.335798E+09 | 0.410800E+09 | 46023334.53 |
July | 0.426732E+09 | 71960595.08 | 0.354772E+09 | 0.512164E+09 | 9831959.48 |
August | 0.571569E+09 | 0.210784E+09 | 0.360785E+09 | 0.646992E+09 | 26946751.98 |
September | 0.583867E+09 | 0.293183E+09 | 0.290684E+09 | 0.619100E+09 | 84058523.02 |
October | 0.852923E+09 | 0.535007E+09 | 0.317916E+09 | 0.900958E+09 | 0.211862E+09 |
November | 0.571337E+09 | 0.342756E+09 | 0.228581E+09 | 0.532210E+09 | 0.350462E+09 |
December | 0.585425E+09 | 0.415776E+09 | 0.169648E+09 | 0.539736E+09 | 0.471150E+09 |
Annual Sum or Average | 0.673811E+10 | 0.335381E+10 | 0.338430E+10 | 0.643427E+10 | 0.296161E+10 |
Minimum of Months | 0.396874E+09 | 61076473.97 | 0.169648E+09 | 0.355473E+09 | 9831959.48 |
Maximum of Months | 0.852923E+09 | 0.535007E+09 | 0.360785E+09 | 0.900958E+09 | 0.526507E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497620E+09 | 0.00 | 0.497620E+09 | 1882178.79 | 0.320805E+10 |
February | 0.615071E+09 | 0.00 | 0.615071E+09 | 14951129.22 | 0.293415E+10 |
March | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.182065E+09 | 0.215437E+10 |
April | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.506527E+09 | 0.140397E+10 |
May | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.112947E+10 | 0.774074E+09 |
June | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.161414E+10 | 0.335303E+09 |
July | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.193257E+10 | 0.137081E+09 |
August | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.173633E+10 | 0.222287E+09 |
September | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.955974E+09 | 0.551658E+09 |
October | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.524844E+09 | 0.122924E+10 |
November | 0.605055E+09 | 0.00 | 0.605055E+09 | 90035012.99 | 0.212627E+10 |
December | 0.434057E+09 | 0.00 | 0.434057E+09 | 2468492.88 | 0.295360E+10 |
Annual Sum or Average | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.869126E+10 | 0.180301E+11 |
Minimum of Months | 0.434057E+09 | 0.00 | 0.434057E+09 | 1882178.79 | 0.137081E+09 |
Maximum of Months | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.193257E+10 | 0.320805E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497620E+09 | 0.00 | 0.497620E+09 | 1049760.50 | 0.330752E+10 |
February | 0.615071E+09 | 0.00 | 0.615071E+09 | 11360051.33 | 0.301997E+10 |
March | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.163760E+09 | 0.222541E+10 |
April | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.476637E+09 | 0.145532E+10 |
May | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.108427E+10 | 0.806774E+09 |
June | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.157213E+10 | 0.358087E+09 |
July | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.189169E+10 | 0.154299E+09 |
August | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.169757E+10 | 0.239883E+09 |
September | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.921799E+09 | 0.586527E+09 |
October | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.497171E+09 | 0.127700E+10 |
November | 0.605055E+09 | 0.00 | 0.605055E+09 | 79476699.77 | 0.220323E+10 |
December | 0.434057E+09 | 0.00 | 0.434057E+09 | 1752674.14 | 0.304728E+10 |
Annual Sum or Average | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.839866E+10 | 0.186813E+11 |
Minimum of Months | 0.434057E+09 | 0.00 | 0.434057E+09 | 1049760.50 | 0.154299E+09 |
Maximum of Months | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.189169E+10 | 0.330752E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71091250.78 | 0.00 | 71091250.78 | 2876608.88 | 0.408386E+09 |
February | 87870646.91 | 0.00 | 87870646.91 | 5842014.51 | 0.375470E+09 |
March | 0.134942E+09 | 2682.76 | 0.134939E+09 | 40525775.03 | 0.270278E+09 |
April | 0.157146E+09 | 640531.34 | 0.156505E+09 | 0.101572E+09 | 0.177343E+09 |
May | 0.215965E+09 | 7881331.93 | 0.208083E+09 | 0.211435E+09 | 99259635.28 |
June | 0.220484E+09 | 11701536.40 | 0.208783E+09 | 0.290319E+09 | 39447253.17 |
July | 0.221141E+09 | 8607714.63 | 0.212533E+09 | 0.348000E+09 | 13362486.12 |
August | 0.195566E+09 | 2581581.37 | 0.192984E+09 | 0.314992E+09 | 23519317.76 |
September | 0.142517E+09 | 80984.14 | 0.142436E+09 | 0.183790E+09 | 61723493.67 |
October | 0.127346E+09 | 0.00 | 0.127346E+09 | 0.104656E+09 | 0.147773E+09 |
November | 86439672.74 | 0.00 | 86439672.74 | 23422400.88 | 0.264030E+09 |
December | 62010461.52 | 0.00 | 62010461.52 | 2043893.69 | 0.370135E+09 |
Annual Sum or Average | 0.172252E+10 | 31496362.59 | 0.169102E+10 | 0.162947E+10 | 0.225073E+10 |
Minimum of Months | 62010461.52 | 0.00 | 62010461.52 | 2043893.69 | 13362486.12 |
Maximum of Months | 0.221141E+09 | 11701536.40 | 0.212533E+09 | 0.348000E+09 | 0.408386E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.553131E+09 | 0.221028E+09 | 0.332103E+09 | 0.248292E+09 | 0.143112E+10 |
February | 0.775608E+09 | 0.361191E+09 | 0.414417E+09 | 0.430062E+09 | 0.126242E+10 |
March | 0.110270E+10 | 0.468638E+09 | 0.634059E+09 | 0.836591E+09 | 0.969432E+09 |
April | 0.127751E+10 | 0.560756E+09 | 0.716758E+09 | 0.120313E+10 | 0.639950E+09 |
May | 0.159351E+10 | 0.634950E+09 | 0.958560E+09 | 0.178348E+10 | 0.374945E+09 |
June | 0.143195E+10 | 0.518583E+09 | 0.913372E+09 | 0.185275E+10 | 0.151440E+09 |
July | 0.148421E+10 | 0.534252E+09 | 0.949954E+09 | 0.213173E+10 | 52436655.50 |
August | 0.167446E+10 | 0.755429E+09 | 0.919036E+09 | 0.235152E+10 | 89768644.57 |
September | 0.121229E+10 | 0.546180E+09 | 0.666111E+09 | 0.151515E+10 | 0.228783E+09 |
October | 0.113165E+10 | 0.512267E+09 | 0.619386E+09 | 0.116930E+10 | 0.537652E+09 |
November | 0.678317E+09 | 0.260689E+09 | 0.417628E+09 | 0.450628E+09 | 0.924977E+09 |
December | 0.548042E+09 | 0.258636E+09 | 0.289406E+09 | 0.276224E+09 | 0.127950E+10 |
Annual Sum or Average | 0.134634E+11 | 0.563260E+10 | 0.783079E+10 | 0.142489E+11 | 0.794242E+10 |
Minimum of Months | 0.548042E+09 | 0.221028E+09 | 0.289406E+09 | 0.248292E+09 | 52436655.50 |
Maximum of Months | 0.167446E+10 | 0.755429E+09 | 0.958560E+09 | 0.235152E+10 | 0.143112E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369525E+09 | 0.242489E+09 | 0.127036E+09 | 0.338361E+09 | 0.360973E+09 |
February | 0.441859E+09 | 0.293726E+09 | 0.148133E+09 | 0.400438E+09 | 0.321728E+09 |
March | 0.433416E+09 | 0.238655E+09 | 0.194762E+09 | 0.380656E+09 | 0.259094E+09 |
April | 0.333714E+09 | 0.134991E+09 | 0.198723E+09 | 0.279054E+09 | 0.178419E+09 |
May | 0.296158E+09 | 60596003.23 | 0.235562E+09 | 0.278412E+09 | 0.104655E+09 |
June | 0.270609E+09 | 41645057.81 | 0.228964E+09 | 0.324810E+09 | 42001077.89 |
July | 0.290968E+09 | 49066407.20 | 0.241902E+09 | 0.400836E+09 | 14114082.21 |
August | 0.389725E+09 | 0.143723E+09 | 0.246002E+09 | 0.493325E+09 | 24241452.57 |
September | 0.398110E+09 | 0.199907E+09 | 0.198204E+09 | 0.469429E+09 | 62062235.29 |
October | 0.581567E+09 | 0.364795E+09 | 0.216771E+09 | 0.658226E+09 | 0.145100E+09 |
November | 0.389567E+09 | 0.233709E+09 | 0.155858E+09 | 0.388114E+09 | 0.241345E+09 |
December | 0.399172E+09 | 0.283498E+09 | 0.115675E+09 | 0.390555E+09 | 0.321521E+09 |
Annual Sum or Average | 0.459439E+10 | 0.228680E+10 | 0.230759E+10 | 0.480221E+10 | 0.207525E+10 |
Minimum of Months | 0.270609E+09 | 41645057.81 | 0.115675E+09 | 0.278412E+09 | 14114082.21 |
Maximum of Months | 0.581567E+09 | 0.364795E+09 | 0.246002E+09 | 0.658226E+09 | 0.360973E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90032583.51 | 0.00 | 90032583.51 | 754897.19 | 0.532351E+09 |
February | 0.111283E+09 | 0.00 | 0.111283E+09 | 4009405.40 | 0.490334E+09 |
March | 0.170896E+09 | 3397.55 | 0.170892E+09 | 39179672.03 | 0.343389E+09 |
April | 0.199015E+09 | 811192.53 | 0.198204E+09 | 0.103535E+09 | 0.216328E+09 |
May | 0.273505E+09 | 9981209.60 | 0.263524E+09 | 0.223450E+09 | 0.115611E+09 |
June | 0.279229E+09 | 14819257.53 | 0.264410E+09 | 0.304997E+09 | 45759906.40 |
July | 0.280061E+09 | 10901127.46 | 0.269159E+09 | 0.358876E+09 | 15776599.68 |
August | 0.247672E+09 | 3269409.92 | 0.244403E+09 | 0.319881E+09 | 31110685.32 |
September | 0.180488E+09 | 102561.31 | 0.180386E+09 | 0.180369E+09 | 78585523.92 |
October | 0.161276E+09 | 0.00 | 0.161276E+09 | 0.100899E+09 | 0.192085E+09 |
November | 0.109470E+09 | 0.00 | 0.109470E+09 | 20186273.77 | 0.338352E+09 |
December | 78532336.87 | 0.00 | 78532336.87 | 819210.80 | 0.484191E+09 |
Annual Sum or Average | 0.218146E+10 | 39888155.91 | 0.214157E+10 | 0.165696E+10 | 0.288387E+10 |
Minimum of Months | 78532336.87 | 0.00 | 78532336.87 | 754897.19 | 15776599.68 |
Maximum of Months | 0.280061E+09 | 14819257.53 | 0.269159E+09 | 0.358876E+09 | 0.532351E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80552493.60 | 0.00 | 80552493.60 | 675409.38 | 0.476292E+09 |
February | 99564990.69 | 0.00 | 99564990.69 | 3587230.21 | 0.438703E+09 |
March | 0.152901E+09 | 3039.80 | 0.152898E+09 | 35054201.02 | 0.307231E+09 |
April | 0.178060E+09 | 725777.03 | 0.177334E+09 | 92633536.21 | 0.193550E+09 |
May | 0.244706E+09 | 8930226.05 | 0.235776E+09 | 0.199921E+09 | 0.103437E+09 |
June | 0.249828E+09 | 13258845.86 | 0.236569E+09 | 0.272882E+09 | 40941561.64 |
July | 0.250571E+09 | 9753280.05 | 0.240818E+09 | 0.321088E+09 | 14115383.51 |
August | 0.221593E+09 | 2925153.44 | 0.218668E+09 | 0.286199E+09 | 27834848.03 |
September | 0.161484E+09 | 91761.99 | 0.161392E+09 | 0.161377E+09 | 70310766.01 |
October | 0.144294E+09 | 0.00 | 0.144294E+09 | 90274924.13 | 0.171859E+09 |
November | 97943574.05 | 0.00 | 97943574.05 | 18060735.63 | 0.302725E+09 |
December | 70263179.36 | 0.00 | 70263179.36 | 732951.00 | 0.433186E+09 |
Annual Sum or Average | 0.195176E+10 | 35688084.23 | 0.191607E+10 | 0.148249E+10 | 0.258019E+10 |
Minimum of Months | 70263179.36 | 0.00 | 70263179.36 | 675409.38 | 14115383.51 |
Maximum of Months | 0.250571E+09 | 13258845.86 | 0.240818E+09 | 0.321088E+09 | 0.476292E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137955E+10 | 0.905285E+09 | 0.474263E+09 | 0.121681E+10 | 0.135830E+10 |
February | 0.164959E+10 | 0.109657E+10 | 0.553025E+09 | 0.144556E+10 | 0.121717E+10 |
March | 0.161807E+10 | 0.890969E+09 | 0.727103E+09 | 0.136291E+10 | 0.958300E+09 |
April | 0.124585E+10 | 0.503962E+09 | 0.741890E+09 | 0.968793E+09 | 0.638181E+09 |
May | 0.110564E+10 | 0.226223E+09 | 0.879422E+09 | 0.919539E+09 | 0.363952E+09 |
June | 0.101026E+10 | 0.155473E+09 | 0.854791E+09 | 0.104018E+10 | 0.143592E+09 |
July | 0.108627E+10 | 0.183180E+09 | 0.903090E+09 | 0.126600E+10 | 47801310.89 |
August | 0.145496E+10 | 0.536561E+09 | 0.918397E+09 | 0.161528E+10 | 94406419.74 |
September | 0.148626E+10 | 0.746312E+09 | 0.739953E+09 | 0.159558E+10 | 0.230467E+09 |
October | 0.217116E+10 | 0.136189E+10 | 0.809272E+09 | 0.234013E+10 | 0.541406E+09 |
November | 0.145437E+10 | 0.872504E+09 | 0.581864E+09 | 0.138744E+10 | 0.893326E+09 |
December | 0.149023E+10 | 0.105838E+10 | 0.431849E+09 | 0.140770E+10 | 0.121073E+10 |
Annual Sum or Average | 0.171522E+11 | 0.853731E+10 | 0.861492E+10 | 0.165659E+11 | 0.769764E+10 |
Minimum of Months | 0.101026E+10 | 0.155473E+09 | 0.431849E+09 | 0.919539E+09 | 47801310.89 |
Maximum of Months | 0.217116E+10 | 0.136189E+10 | 0.918397E+09 | 0.234013E+10 | 0.135830E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 622.31 | 632.93 | 698.64 | 458.46 | 240.18 | 0.00 | 0.00 |
February | 814.86 | 633.11 | 924.91 | 614.83 | 310.07 | 0.00 | 0.00 |
March | 689.78 | 450.63 | 819.44 | 451.21 | 368.23 | 0.00 | 0.00 |
April | 504.42 | 310.02 | 651.97 | 263.73 | 388.24 | 0.00 | 0.00 |
May | 466.69 | 170.03 | 559.93 | 114.57 | 445.36 | 0.00 | 0.00 |
June | 543.51 | 67.46 | 528.68 | 81.36 | 447.32 | 0.00 | 0.00 |
July | 635.43 | 20.42 | 550.12 | 92.77 | 457.35 | 0.00 | 0.00 |
August | 796.71 | 48.00 | 736.83 | 271.73 | 465.10 | 0.00 | 0.00 |
September | 818.67 | 119.71 | 777.78 | 390.55 | 387.22 | 0.00 | 0.00 |
October | 1164.44 | 275.53 | 1099.54 | 689.70 | 409.84 | 0.00 | 0.00 |
November | 724.83 | 439.24 | 761.08 | 456.59 | 304.49 | 0.00 | 0.00 |
December | 713.76 | 569.63 | 754.69 | 535.99 | 218.70 | 0.00 | 0.00 |
Annual Sum or Average | 707.73 | 309.60 | 737.75 | 367.20 | 370.54 | 0.00 | 0.00 |
Minimum of Months | 466.69 | 20.42 | 528.68 | 81.36 | 218.70 | 0.00 | 0.00 |
Maximum of Months | 1164.44 | 633.11 | 1099.54 | 689.70 | 465.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1733.75 | 1831.45 | 1967.33 | 1291.00 | 676.33 | 0.00 | 0.00 |
February | 2269.69 | 1833.72 | 2604.47 | 1731.32 | 873.15 | 0.00 | 0.00 |
March | 1917.83 | 1343.55 | 2307.48 | 1270.58 | 1036.90 | 0.00 | 0.00 |
April | 1391.79 | 947.10 | 1835.89 | 742.64 | 1093.25 | 0.00 | 0.00 |
May | 1276.02 | 540.41 | 1576.72 | 322.61 | 1254.11 | 0.00 | 0.00 |
June | 1494.74 | 233.03 | 1488.73 | 229.11 | 1259.62 | 0.00 | 0.00 |
July | 1752.77 | 85.53 | 1549.09 | 261.23 | 1287.87 | 0.00 | 0.00 |
August | 2215.84 | 165.34 | 2074.87 | 765.17 | 1309.70 | 0.00 | 0.00 |
September | 2277.64 | 393.43 | 2190.16 | 1099.77 | 1090.40 | 0.00 | 0.00 |
October | 3246.16 | 854.47 | 3096.22 | 1942.15 | 1154.08 | 0.00 | 0.00 |
November | 2011.39 | 1312.06 | 2143.16 | 1285.72 | 857.44 | 0.00 | 0.00 |
December | 1987.82 | 1667.00 | 2125.17 | 1509.32 | 615.85 | 0.00 | 0.00 |
Annual Sum or Average | 1963.98 | 928.86 | 2077.44 | 1034.02 | 1043.42 | 0.00 | 0.00 |
Minimum of Months | 1276.02 | 85.53 | 1488.73 | 229.11 | 615.85 | 0.00 | 0.00 |
Maximum of Months | 3246.16 | 1833.72 | 3096.22 | 1942.15 | 1309.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2288.59 | 2496.21 | 2555.67 | 1677.08 | 878.59 | 0.00 | 0.00 |
February | 3004.06 | 2482.59 | 3383.36 | 2249.09 | 1134.27 | 0.00 | 0.00 |
March | 2541.58 | 1823.96 | 2997.55 | 1650.56 | 1346.99 | 0.00 | 0.00 |
April | 1844.84 | 1292.20 | 2384.93 | 964.73 | 1420.20 | 0.00 | 0.00 |
May | 1697.04 | 732.45 | 2048.25 | 419.09 | 1629.17 | 0.00 | 0.00 |
June | 2002.02 | 307.35 | 1933.94 | 297.62 | 1636.32 | 0.00 | 0.00 |
July | 2359.23 | 107.45 | 2012.36 | 339.35 | 1673.01 | 0.00 | 0.00 |
August | 2985.50 | 205.74 | 2695.37 | 994.00 | 1701.37 | 0.00 | 0.00 |
September | 3046.45 | 509.20 | 2845.15 | 1428.66 | 1416.49 | 0.00 | 0.00 |
October | 4321.96 | 1119.43 | 4022.17 | 2522.96 | 1499.21 | 0.00 | 0.00 |
November | 2657.09 | 1787.32 | 2784.09 | 1670.23 | 1113.86 | 0.00 | 0.00 |
December | 2623.92 | 2272.86 | 2760.71 | 1960.70 | 800.02 | 0.00 | 0.00 |
Annual Sum or Average | 2613.64 | 1254.51 | 2698.72 | 1343.25 | 1355.46 | 0.00 | 0.00 |
Minimum of Months | 1697.04 | 107.45 | 1933.94 | 297.62 | 800.02 | 0.00 | 0.00 |
Maximum of Months | 4321.96 | 2496.21 | 4022.17 | 2522.96 | 1701.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 153.84 | 378.81 | 240.32 | 132.53 | 107.78 | 0.00 | 0.00 |
February | 219.91 | 378.18 | 333.00 | 187.37 | 145.63 | 0.00 | 0.00 |
March | 297.27 | 259.03 | 385.25 | 192.65 | 192.61 | 0.00 | 0.00 |
April | 310.94 | 178.29 | 371.44 | 155.80 | 215.64 | 0.00 | 0.00 |
May | 379.63 | 97.06 | 394.09 | 130.40 | 263.69 | 0.00 | 0.00 |
June | 470.22 | 35.63 | 414.17 | 141.08 | 273.09 | 0.00 | 0.00 |
July | 502.23 | 8.10 | 398.45 | 127.23 | 271.22 | 0.00 | 0.00 |
August | 573.16 | 20.98 | 466.16 | 201.92 | 264.23 | 0.00 | 0.00 |
September | 418.56 | 62.82 | 381.71 | 176.71 | 204.99 | 0.00 | 0.00 |
October | 446.98 | 151.70 | 443.40 | 246.40 | 197.00 | 0.00 | 0.00 |
November | 191.23 | 257.57 | 256.82 | 121.25 | 135.57 | 0.00 | 0.00 |
December | 168.65 | 339.33 | 243.12 | 146.43 | 96.69 | 0.00 | 0.00 |
Annual Sum or Average | 345.37 | 179.52 | 360.94 | 163.28 | 197.66 | 0.00 | 0.00 |
Minimum of Months | 153.84 | 8.10 | 240.32 | 121.25 | 96.69 | 0.00 | 0.00 |
Maximum of Months | 573.16 | 378.81 | 466.16 | 246.40 | 273.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.18 | 401.44 | 128.98 | 42.07 | 86.91 | 0.00 | 0.00 |
February | 75.89 | 405.34 | 186.79 | 66.05 | 120.74 | 0.00 | 0.00 |
March | 178.48 | 260.01 | 273.91 | 103.62 | 170.29 | 0.00 | 0.00 |
April | 246.48 | 176.75 | 303.38 | 104.01 | 199.37 | 0.00 | 0.00 |
May | 355.76 | 94.65 | 364.17 | 110.73 | 253.44 | 0.00 | 0.00 |
June | 456.69 | 34.56 | 394.85 | 129.54 | 265.31 | 0.00 | 0.00 |
July | 482.65 | 7.83 | 372.40 | 112.14 | 260.26 | 0.00 | 0.00 |
August | 508.78 | 20.26 | 393.73 | 149.27 | 244.45 | 0.00 | 0.00 |
September | 313.30 | 61.52 | 283.18 | 99.68 | 183.49 | 0.00 | 0.00 |
October | 251.37 | 150.33 | 273.96 | 110.31 | 163.64 | 0.00 | 0.00 |
November | 62.84 | 266.04 | 139.96 | 31.16 | 108.81 | 0.00 | 0.00 |
December | 40.35 | 361.65 | 117.34 | 40.67 | 76.67 | 0.00 | 0.00 |
Annual Sum or Average | 252.55 | 185.47 | 269.95 | 91.82 | 178.13 | 0.00 | 0.00 |
Minimum of Months | 40.35 | 7.83 | 117.34 | 31.16 | 76.67 | 0.00 | 0.00 |
Maximum of Months | 508.78 | 405.34 | 394.85 | 149.27 | 265.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 98.18 | 101.06 | 110.26 | 72.35 | 37.91 | 0.00 | 0.00 |
February | 127.37 | 105.57 | 145.97 | 97.03 | 48.94 | 0.00 | 0.00 |
March | 108.38 | 77.08 | 129.32 | 71.21 | 58.11 | 0.00 | 0.00 |
April | 78.84 | 54.10 | 102.89 | 41.62 | 61.27 | 0.00 | 0.00 |
May | 70.13 | 32.77 | 88.37 | 18.08 | 70.29 | 0.00 | 0.00 |
June | 82.72 | 14.59 | 83.44 | 12.84 | 70.60 | 0.00 | 0.00 |
July | 98.91 | 5.38 | 86.82 | 14.64 | 72.18 | 0.00 | 0.00 |
August | 127.03 | 9.41 | 116.29 | 42.88 | 73.40 | 0.00 | 0.00 |
September | 128.06 | 23.85 | 122.75 | 61.64 | 61.11 | 0.00 | 0.00 |
October | 182.82 | 50.44 | 173.53 | 108.85 | 64.68 | 0.00 | 0.00 |
November | 112.58 | 76.08 | 120.11 | 72.06 | 48.06 | 0.00 | 0.00 |
December | 111.95 | 93.77 | 119.11 | 84.59 | 34.52 | 0.00 | 0.00 |
Annual Sum or Average | 110.55 | 53.38 | 116.43 | 57.95 | 58.48 | 0.00 | 0.00 |
Minimum of Months | 70.13 | 5.38 | 83.44 | 12.84 | 34.52 | 0.00 | 0.00 |
Maximum of Months | 182.82 | 105.57 | 173.53 | 108.85 | 73.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.37 | 122.20 | 21.22 | 0.00 | 21.22 | 0.00 | 0.00 |
February | 1.43 | 124.34 | 29.04 | 0.00 | 29.04 | 0.00 | 0.00 |
March | 10.66 | 78.97 | 40.28 | 0.00 | 40.28 | 0.00 | 0.00 |
April | 26.62 | 51.38 | 48.47 | 0.20 | 48.27 | 0.00 | 0.00 |
May | 54.51 | 25.80 | 64.46 | 2.35 | 62.11 | 0.00 | 0.00 |
June | 78.18 | 8.72 | 68.00 | 3.61 | 64.39 | 0.00 | 0.00 |
July | 91.41 | 1.71 | 66.01 | 2.57 | 63.44 | 0.00 | 0.00 |
August | 82.68 | 4.85 | 58.37 | 0.77 | 57.60 | 0.00 | 0.00 |
September | 47.15 | 16.64 | 43.96 | 0.02 | 43.93 | 0.00 | 0.00 |
October | 26.28 | 42.77 | 38.01 | 0.00 | 38.01 | 0.00 | 0.00 |
November | 5.75 | 80.15 | 26.66 | 0.00 | 26.66 | 0.00 | 0.00 |
December | 0.32 | 110.64 | 18.51 | 0.00 | 18.51 | 0.00 | 0.00 |
Annual Sum or Average | 35.68 | 55.30 | 43.67 | 0.80 | 42.87 | 0.00 | 0.00 |
Minimum of Months | 0.32 | 1.71 | 18.51 | 0.00 | 18.51 | 0.00 | 0.00 |
Maximum of Months | 91.41 | 124.34 | 68.00 | 3.61 | 64.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.73 | 376.14 | 241.03 | 131.69 | 109.34 | 0.00 | 0.00 |
February | 228.46 | 372.44 | 342.68 | 195.91 | 146.77 | 0.00 | 0.00 |
March | 277.44 | 260.65 | 367.38 | 176.45 | 190.93 | 0.00 | 0.00 |
April | 308.97 | 173.23 | 374.89 | 160.13 | 214.76 | 0.00 | 0.00 |
May | 392.21 | 93.98 | 407.73 | 141.05 | 266.69 | 0.00 | 0.00 |
June | 427.64 | 33.82 | 380.34 | 116.01 | 264.32 | 0.00 | 0.00 |
July | 486.61 | 7.58 | 385.41 | 117.96 | 267.44 | 0.00 | 0.00 |
August | 561.23 | 19.58 | 457.74 | 194.53 | 263.21 | 0.00 | 0.00 |
September | 421.41 | 60.22 | 387.14 | 182.34 | 204.80 | 0.00 | 0.00 |
October | 424.80 | 148.43 | 428.05 | 231.65 | 196.41 | 0.00 | 0.00 |
November | 216.71 | 254.95 | 280.92 | 140.34 | 140.58 | 0.00 | 0.00 |
December | 175.84 | 335.84 | 251.14 | 154.00 | 97.14 | 0.00 | 0.00 |
Annual Sum or Average | 340.37 | 177.00 | 358.87 | 161.69 | 197.18 | 0.00 | 0.00 |
Minimum of Months | 152.73 | 7.58 | 241.03 | 116.01 | 97.14 | 0.00 | 0.00 |
Maximum of Months | 561.23 | 376.14 | 457.74 | 231.65 | 267.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 37.19 | 393.90 | 129.70 | 41.23 | 88.47 | 0.00 | 0.00 |
February | 74.09 | 389.02 | 196.47 | 74.60 | 121.88 | 0.00 | 0.00 |
March | 157.27 | 260.17 | 256.04 | 87.42 | 168.62 | 0.00 | 0.00 |
April | 243.95 | 171.31 | 306.83 | 108.34 | 198.49 | 0.00 | 0.00 |
May | 368.87 | 92.21 | 377.82 | 121.38 | 256.43 | 0.00 | 0.00 |
June | 414.44 | 33.09 | 361.01 | 104.47 | 256.54 | 0.00 | 0.00 |
July | 467.16 | 7.44 | 359.36 | 102.87 | 256.49 | 0.00 | 0.00 |
August | 496.84 | 19.05 | 385.31 | 141.88 | 243.43 | 0.00 | 0.00 |
September | 315.35 | 58.69 | 288.62 | 105.31 | 183.30 | 0.00 | 0.00 |
October | 228.02 | 145.83 | 258.60 | 95.56 | 163.05 | 0.00 | 0.00 |
November | 83.05 | 258.31 | 164.07 | 50.25 | 113.82 | 0.00 | 0.00 |
December | 41.08 | 351.59 | 125.36 | 48.25 | 77.12 | 0.00 | 0.00 |
Annual Sum or Average | 245.12 | 180.58 | 267.88 | 90.24 | 177.64 | 0.00 | 0.00 |
Minimum of Months | 37.19 | 7.44 | 125.36 | 41.23 | 77.12 | 0.00 | 0.00 |
Maximum of Months | 496.84 | 393.90 | 385.31 | 141.88 | 256.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 189.58 | 471.73 | 284.87 | 156.77 | 128.10 | 0.00 | 0.00 |
February | 255.85 | 471.91 | 379.18 | 210.24 | 168.94 | 0.00 | 0.00 |
March | 260.25 | 327.62 | 367.46 | 154.29 | 213.17 | 0.00 | 0.00 |
April | 237.56 | 217.59 | 327.94 | 90.61 | 237.33 | 0.00 | 0.00 |
May | 289.08 | 110.69 | 331.11 | 44.27 | 286.84 | 0.00 | 0.00 |
June | 373.30 | 36.36 | 328.10 | 35.64 | 292.46 | 0.00 | 0.00 |
July | 440.72 | 7.03 | 331.11 | 37.29 | 293.82 | 0.00 | 0.00 |
August | 478.14 | 21.57 | 378.42 | 94.59 | 283.83 | 0.00 | 0.00 |
September | 399.51 | 69.82 | 361.19 | 133.60 | 227.58 | 0.00 | 0.00 |
October | 468.37 | 178.15 | 458.33 | 235.84 | 222.49 | 0.00 | 0.00 |
November | 254.20 | 317.03 | 318.01 | 156.13 | 161.88 | 0.00 | 0.00 |
December | 221.95 | 420.55 | 298.17 | 183.28 | 114.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.99 | 219.44 | 346.87 | 127.30 | 219.57 | 0.00 | 0.00 |
Minimum of Months | 189.58 | 7.03 | 284.87 | 35.64 | 114.88 | 0.00 | 0.00 |
Maximum of Months | 478.14 | 471.91 | 458.33 | 235.84 | 293.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 153.77 | 377.97 | 240.51 | 132.64 | 107.87 | 0.00 | 0.00 |
February | 219.30 | 377.94 | 333.27 | 187.52 | 145.75 | 0.00 | 0.00 |
March | 295.60 | 258.79 | 385.57 | 192.80 | 192.76 | 0.00 | 0.00 |
April | 308.62 | 178.17 | 371.75 | 155.93 | 215.82 | 0.00 | 0.00 |
May | 375.15 | 97.65 | 394.41 | 130.50 | 263.91 | 0.00 | 0.00 |
June | 465.25 | 36.25 | 414.51 | 141.20 | 273.31 | 0.00 | 0.00 |
July | 497.65 | 8.32 | 398.78 | 127.34 | 271.44 | 0.00 | 0.00 |
August | 569.39 | 21.03 | 466.54 | 202.09 | 264.45 | 0.00 | 0.00 |
September | 415.07 | 63.24 | 382.02 | 176.86 | 205.16 | 0.00 | 0.00 |
October | 444.26 | 151.65 | 443.77 | 246.60 | 197.17 | 0.00 | 0.00 |
November | 191.01 | 256.23 | 257.03 | 121.35 | 135.68 | 0.00 | 0.00 |
December | 168.92 | 338.01 | 243.32 | 146.55 | 96.77 | 0.00 | 0.00 |
Annual Sum or Average | 342.98 | 179.33 | 361.23 | 163.41 | 197.82 | 0.00 | 0.00 |
Minimum of Months | 153.77 | 8.32 | 240.51 | 121.35 | 96.77 | 0.00 | 0.00 |
Maximum of Months | 569.39 | 377.97 | 466.54 | 246.60 | 273.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.47 | 400.52 | 129.09 | 42.11 | 86.99 | 0.00 | 0.00 |
February | 75.98 | 405.27 | 186.94 | 66.10 | 120.84 | 0.00 | 0.00 |
March | 177.67 | 259.44 | 274.13 | 103.70 | 170.43 | 0.00 | 0.00 |
April | 244.30 | 176.40 | 303.62 | 104.10 | 199.53 | 0.00 | 0.00 |
May | 351.02 | 95.20 | 364.47 | 110.82 | 253.65 | 0.00 | 0.00 |
June | 451.42 | 35.19 | 395.17 | 129.65 | 265.53 | 0.00 | 0.00 |
July | 477.66 | 8.08 | 372.71 | 112.23 | 260.48 | 0.00 | 0.00 |
August | 504.63 | 20.31 | 394.05 | 149.39 | 244.66 | 0.00 | 0.00 |
September | 309.66 | 61.88 | 283.41 | 99.76 | 183.65 | 0.00 | 0.00 |
October | 249.57 | 149.77 | 274.18 | 110.40 | 163.78 | 0.00 | 0.00 |
November | 63.27 | 264.12 | 140.08 | 31.18 | 108.90 | 0.00 | 0.00 |
December | 40.98 | 359.88 | 117.44 | 40.71 | 76.73 | 0.00 | 0.00 |
Annual Sum or Average | 250.36 | 185.11 | 270.17 | 91.90 | 178.27 | 0.00 | 0.00 |
Minimum of Months | 40.98 | 8.08 | 117.44 | 31.18 | 76.73 | 0.00 | 0.00 |
Maximum of Months | 504.63 | 405.27 | 395.17 | 149.39 | 265.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.38 | 196.58 | 202.34 | 132.78 | 69.56 | 0.00 | 0.00 |
February | 228.56 | 197.82 | 267.87 | 178.07 | 89.80 | 0.00 | 0.00 |
March | 195.58 | 139.73 | 237.32 | 130.68 | 106.64 | 0.00 | 0.00 |
April | 143.91 | 94.70 | 188.82 | 76.38 | 112.44 | 0.00 | 0.00 |
May | 132.72 | 50.96 | 162.17 | 33.18 | 128.99 | 0.00 | 0.00 |
June | 158.49 | 17.76 | 153.12 | 23.56 | 129.55 | 0.00 | 0.00 |
July | 191.22 | 3.67 | 159.32 | 26.87 | 132.46 | 0.00 | 0.00 |
August | 241.56 | 10.06 | 213.40 | 78.70 | 134.70 | 0.00 | 0.00 |
September | 238.85 | 32.43 | 225.26 | 113.11 | 112.15 | 0.00 | 0.00 |
October | 336.38 | 79.10 | 318.45 | 199.75 | 118.70 | 0.00 | 0.00 |
November | 205.33 | 135.21 | 220.42 | 132.24 | 88.19 | 0.00 | 0.00 |
December | 201.51 | 175.91 | 218.57 | 155.23 | 63.34 | 0.00 | 0.00 |
Annual Sum or Average | 204.03 | 93.91 | 213.66 | 106.35 | 107.32 | 0.00 | 0.00 |
Minimum of Months | 132.72 | 3.67 | 153.12 | 23.56 | 63.34 | 0.00 | 0.00 |
Maximum of Months | 336.38 | 197.82 | 318.45 | 199.75 | 134.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.70 | 1197.75 | 185.79 | 0.00 | 185.79 | 0.00 | 0.00 |
February | 6.18 | 1212.86 | 254.25 | 0.00 | 254.25 | 0.00 | 0.00 |
March | 67.98 | 804.35 | 352.66 | 0.01 | 352.65 | 0.00 | 0.00 |
April | 195.42 | 541.66 | 424.37 | 1.73 | 422.64 | 0.00 | 0.00 |
May | 421.70 | 289.01 | 564.40 | 20.60 | 543.80 | 0.00 | 0.00 |
June | 622.74 | 129.36 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
July | 721.54 | 51.18 | 577.93 | 22.50 | 555.43 | 0.00 | 0.00 |
August | 648.27 | 82.99 | 511.09 | 6.75 | 504.35 | 0.00 | 0.00 |
September | 368.82 | 212.83 | 384.87 | 0.22 | 384.65 | 0.00 | 0.00 |
October | 195.95 | 458.94 | 332.81 | 0.00 | 332.81 | 0.00 | 0.00 |
November | 34.74 | 820.32 | 233.43 | 0.00 | 233.43 | 0.00 | 0.00 |
December | 0.92 | 1102.75 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Annual Sum or Average | 275.60 | 571.73 | 382.33 | 6.99 | 375.34 | 0.00 | 0.00 |
Minimum of Months | 0.70 | 51.18 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Maximum of Months | 721.54 | 1212.86 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.39 | 1234.89 | 185.79 | 0.00 | 185.79 | 0.00 | 0.00 |
February | 4.70 | 1248.33 | 254.25 | 0.00 | 254.25 | 0.00 | 0.00 |
March | 61.14 | 830.87 | 352.66 | 0.01 | 352.65 | 0.00 | 0.00 |
April | 183.89 | 561.46 | 424.37 | 1.73 | 422.64 | 0.00 | 0.00 |
May | 404.82 | 301.21 | 564.40 | 20.60 | 543.80 | 0.00 | 0.00 |
June | 606.53 | 138.15 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
July | 706.27 | 57.61 | 577.93 | 22.50 | 555.43 | 0.00 | 0.00 |
August | 633.80 | 89.56 | 511.09 | 6.75 | 504.35 | 0.00 | 0.00 |
September | 355.63 | 226.28 | 384.87 | 0.22 | 384.65 | 0.00 | 0.00 |
October | 185.62 | 476.78 | 332.81 | 0.00 | 332.81 | 0.00 | 0.00 |
November | 30.66 | 850.01 | 233.43 | 0.00 | 233.43 | 0.00 | 0.00 |
December | 0.65 | 1137.72 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Annual Sum or Average | 266.32 | 592.38 | 382.33 | 6.99 | 375.34 | 0.00 | 0.00 |
Minimum of Months | 0.39 | 57.61 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Maximum of Months | 706.27 | 1248.33 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 188.81 | 790.27 | 371.02 | 173.06 | 197.97 | 0.00 | 0.00 |
February | 307.38 | 771.70 | 539.57 | 270.72 | 268.86 | 0.00 | 0.00 |
March | 461.78 | 551.78 | 623.90 | 264.07 | 359.83 | 0.00 | 0.00 |
April | 606.07 | 379.20 | 682.24 | 268.67 | 413.57 | 0.00 | 0.00 |
May | 846.72 | 214.08 | 786.15 | 262.63 | 523.52 | 0.00 | 0.00 |
June | 951.43 | 89.16 | 741.92 | 220.65 | 521.26 | 0.00 | 0.00 |
July | 1075.40 | 29.75 | 745.34 | 221.00 | 524.34 | 0.00 | 0.00 |
August | 1179.57 | 51.17 | 843.70 | 336.67 | 507.03 | 0.00 | 0.00 |
September | 835.51 | 134.96 | 676.28 | 287.87 | 388.41 | 0.00 | 0.00 |
October | 718.88 | 307.57 | 687.19 | 327.46 | 359.73 | 0.00 | 0.00 |
November | 321.12 | 540.33 | 445.34 | 190.74 | 254.60 | 0.00 | 0.00 |
December | 219.58 | 705.82 | 376.80 | 202.41 | 174.39 | 0.00 | 0.00 |
Annual Sum or Average | 645.05 | 378.30 | 627.23 | 252.12 | 375.11 | 0.00 | 0.00 |
Minimum of Months | 188.81 | 29.75 | 371.02 | 173.06 | 174.39 | 0.00 | 0.00 |
Maximum of Months | 1179.57 | 790.27 | 843.70 | 336.67 | 524.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 416.88 | 845.76 | 578.75 | 337.99 | 240.76 | 0.00 | 0.00 |
February | 557.38 | 843.86 | 769.03 | 453.28 | 315.75 | 0.00 | 0.00 |
March | 531.31 | 595.45 | 725.01 | 332.65 | 392.36 | 0.00 | 0.00 |
April | 448.90 | 403.80 | 626.13 | 195.02 | 431.11 | 0.00 | 0.00 |
May | 499.86 | 216.15 | 606.28 | 91.52 | 514.76 | 0.00 | 0.00 |
June | 623.06 | 87.66 | 593.87 | 70.81 | 523.06 | 0.00 | 0.00 |
July | 726.25 | 28.72 | 603.68 | 76.10 | 527.58 | 0.00 | 0.00 |
August | 829.22 | 57.12 | 718.42 | 202.64 | 515.78 | 0.00 | 0.00 |
September | 747.22 | 146.15 | 705.34 | 288.00 | 417.33 | 0.00 | 0.00 |
October | 941.90 | 334.84 | 924.71 | 508.47 | 416.23 | 0.00 | 0.00 |
November | 532.60 | 574.55 | 641.12 | 336.61 | 304.51 | 0.00 | 0.00 |
December | 486.35 | 754.74 | 611.94 | 395.15 | 216.79 | 0.00 | 0.00 |
Annual Sum or Average | 612.45 | 404.95 | 674.96 | 273.11 | 401.84 | 0.00 | 0.00 |
Minimum of Months | 416.88 | 28.72 | 578.75 | 70.81 | 216.79 | 0.00 | 0.00 |
Maximum of Months | 941.90 | 845.76 | 924.71 | 508.47 | 527.58 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166680E+10 | 0.169524E+10 | 0.187124E+10 | 0.122794E+10 | 0.643298E+09 | 0.00 | 0.00 |
February | 0.197130E+10 | 0.153162E+10 | 0.223753E+10 | 0.148740E+10 | 0.750132E+09 | 0.00 | 0.00 |
March | 0.184751E+10 | 0.120697E+10 | 0.219478E+10 | 0.120852E+10 | 0.986255E+09 | 0.00 | 0.00 |
April | 0.130745E+10 | 0.803560E+09 | 0.168989E+10 | 0.683582E+09 | 0.100631E+10 | 0.00 | 0.00 |
May | 0.124997E+10 | 0.455414E+09 | 0.149971E+10 | 0.306852E+09 | 0.119286E+10 | 0.00 | 0.00 |
June | 0.140877E+10 | 0.174866E+09 | 0.137034E+10 | 0.210887E+09 | 0.115945E+10 | 0.00 | 0.00 |
July | 0.170193E+10 | 54690538.96 | 0.147343E+10 | 0.248468E+09 | 0.122497E+10 | 0.00 | 0.00 |
August | 0.213391E+10 | 0.128570E+09 | 0.197353E+10 | 0.727800E+09 | 0.124573E+10 | 0.00 | 0.00 |
September | 0.212200E+10 | 0.310284E+09 | 0.201599E+10 | 0.101231E+10 | 0.100368E+10 | 0.00 | 0.00 |
October | 0.311883E+10 | 0.737982E+09 | 0.294500E+10 | 0.184729E+10 | 0.109771E+10 | 0.00 | 0.00 |
November | 0.187876E+10 | 0.113852E+10 | 0.197273E+10 | 0.118348E+10 | 0.789250E+09 | 0.00 | 0.00 |
December | 0.191173E+10 | 0.152569E+10 | 0.202137E+10 | 0.143560E+10 | 0.585767E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223190E+11 | 0.976341E+10 | 0.232656E+11 | 0.115801E+11 | 0.116854E+11 | 0.00 | 0.00 |
Minimum of Months | 0.124997E+10 | 54690538.96 | 0.137034E+10 | 0.210887E+09 | 0.585767E+09 | 0.00 | 0.00 |
Maximum of Months | 0.311883E+10 | 0.169524E+10 | 0.294500E+10 | 0.184729E+10 | 0.124573E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464367E+10 | 0.490534E+10 | 0.526929E+10 | 0.345781E+10 | 0.181148E+10 | 0.00 | 0.00 |
February | 0.549083E+10 | 0.443614E+10 | 0.630074E+10 | 0.418842E+10 | 0.211232E+10 | 0.00 | 0.00 |
March | 0.513672E+10 | 0.359856E+10 | 0.618035E+10 | 0.340312E+10 | 0.277723E+10 | 0.00 | 0.00 |
April | 0.360752E+10 | 0.245488E+10 | 0.475863E+10 | 0.192492E+10 | 0.283371E+10 | 0.00 | 0.00 |
May | 0.341769E+10 | 0.144744E+10 | 0.422310E+10 | 0.864076E+09 | 0.335902E+10 | 0.00 | 0.00 |
June | 0.387438E+10 | 0.604017E+09 | 0.385879E+10 | 0.593843E+09 | 0.326494E+10 | 0.00 | 0.00 |
July | 0.469462E+10 | 0.229094E+09 | 0.414909E+10 | 0.699668E+09 | 0.344942E+10 | 0.00 | 0.00 |
August | 0.593490E+10 | 0.442847E+09 | 0.555733E+10 | 0.204944E+10 | 0.350789E+10 | 0.00 | 0.00 |
September | 0.590364E+10 | 0.101977E+10 | 0.567690E+10 | 0.285060E+10 | 0.282631E+10 | 0.00 | 0.00 |
October | 0.869451E+10 | 0.228860E+10 | 0.829292E+10 | 0.520184E+10 | 0.309108E+10 | 0.00 | 0.00 |
November | 0.521353E+10 | 0.340086E+10 | 0.555507E+10 | 0.333260E+10 | 0.222247E+10 | 0.00 | 0.00 |
December | 0.532417E+10 | 0.446490E+10 | 0.569205E+10 | 0.404257E+10 | 0.164948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.619362E+11 | 0.292925E+11 | 0.655143E+11 | 0.326089E+11 | 0.329054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.341769E+10 | 0.229094E+09 | 0.385879E+10 | 0.593843E+09 | 0.164948E+10 | 0.00 | 0.00 |
Maximum of Months | 0.869451E+10 | 0.490534E+10 | 0.829292E+10 | 0.520184E+10 | 0.350789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612976E+10 | 0.668585E+10 | 0.684511E+10 | 0.449189E+10 | 0.235322E+10 | 0.00 | 0.00 |
February | 0.726743E+10 | 0.600588E+10 | 0.818502E+10 | 0.544100E+10 | 0.274403E+10 | 0.00 | 0.00 |
March | 0.680737E+10 | 0.488530E+10 | 0.802863E+10 | 0.442085E+10 | 0.360778E+10 | 0.00 | 0.00 |
April | 0.478183E+10 | 0.334939E+10 | 0.618173E+10 | 0.250058E+10 | 0.368115E+10 | 0.00 | 0.00 |
May | 0.454536E+10 | 0.196179E+10 | 0.548604E+10 | 0.112248E+10 | 0.436356E+10 | 0.00 | 0.00 |
June | 0.518924E+10 | 0.796643E+09 | 0.501278E+10 | 0.771436E+09 | 0.424135E+10 | 0.00 | 0.00 |
July | 0.631897E+10 | 0.287800E+09 | 0.538991E+10 | 0.908909E+09 | 0.448100E+10 | 0.00 | 0.00 |
August | 0.799637E+10 | 0.551046E+09 | 0.721928E+10 | 0.266233E+10 | 0.455695E+10 | 0.00 | 0.00 |
September | 0.789640E+10 | 0.131985E+10 | 0.737462E+10 | 0.370309E+10 | 0.367153E+10 | 0.00 | 0.00 |
October | 0.115759E+11 | 0.299829E+10 | 0.107730E+11 | 0.675749E+10 | 0.401548E+10 | 0.00 | 0.00 |
November | 0.688717E+10 | 0.463272E+10 | 0.721636E+10 | 0.432923E+10 | 0.288712E+10 | 0.00 | 0.00 |
December | 0.702792E+10 | 0.608764E+10 | 0.739430E+10 | 0.525153E+10 | 0.214277E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.824238E+11 | 0.395622E+11 | 0.851068E+11 | 0.423608E+11 | 0.427459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454536E+10 | 0.287800E+09 | 0.501278E+10 | 0.771436E+09 | 0.214277E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115759E+11 | 0.668585E+10 | 0.107730E+11 | 0.675749E+10 | 0.455695E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412058E+09 | 0.101462E+10 | 0.643661E+09 | 0.354972E+09 | 0.288689E+09 | 0.00 | 0.00 |
February | 0.531997E+09 | 0.914882E+09 | 0.805584E+09 | 0.453274E+09 | 0.352310E+09 | 0.00 | 0.00 |
March | 0.796200E+09 | 0.693794E+09 | 0.103186E+10 | 0.515982E+09 | 0.515875E+09 | 0.00 | 0.00 |
April | 0.805964E+09 | 0.462120E+09 | 0.962774E+09 | 0.403834E+09 | 0.558940E+09 | 0.00 | 0.00 |
May | 0.101680E+10 | 0.259962E+09 | 0.105552E+10 | 0.349255E+09 | 0.706266E+09 | 0.00 | 0.00 |
June | 0.121880E+10 | 92349689.79 | 0.107354E+10 | 0.365688E+09 | 0.707848E+09 | 0.00 | 0.00 |
July | 0.134516E+10 | 21698731.34 | 0.106721E+10 | 0.340776E+09 | 0.726432E+09 | 0.00 | 0.00 |
August | 0.153516E+10 | 56187706.03 | 0.124855E+10 | 0.540832E+09 | 0.707721E+09 | 0.00 | 0.00 |
September | 0.108491E+10 | 0.162831E+09 | 0.989380E+09 | 0.458039E+09 | 0.531341E+09 | 0.00 | 0.00 |
October | 0.119720E+10 | 0.406323E+09 | 0.118761E+10 | 0.659958E+09 | 0.527656E+09 | 0.00 | 0.00 |
November | 0.495658E+09 | 0.667610E+09 | 0.665665E+09 | 0.314274E+09 | 0.351392E+09 | 0.00 | 0.00 |
December | 0.451720E+09 | 0.908849E+09 | 0.651168E+09 | 0.392204E+09 | 0.258964E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108916E+11 | 0.566122E+10 | 0.113825E+11 | 0.514909E+10 | 0.623343E+10 | 0.00 | 0.00 |
Minimum of Months | 0.412058E+09 | 21698731.34 | 0.643661E+09 | 0.314274E+09 | 0.258964E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153516E+10 | 0.101462E+10 | 0.124855E+10 | 0.659958E+09 | 0.726432E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115661E+09 | 0.107521E+10 | 0.345472E+09 | 0.112682E+09 | 0.232790E+09 | 0.00 | 0.00 |
February | 0.183589E+09 | 0.980588E+09 | 0.451886E+09 | 0.159789E+09 | 0.292097E+09 | 0.00 | 0.00 |
March | 0.478050E+09 | 0.696423E+09 | 0.733628E+09 | 0.277526E+09 | 0.456102E+09 | 0.00 | 0.00 |
April | 0.638883E+09 | 0.458139E+09 | 0.786351E+09 | 0.269593E+09 | 0.516757E+09 | 0.00 | 0.00 |
May | 0.952866E+09 | 0.253512E+09 | 0.975394E+09 | 0.296583E+09 | 0.678810E+09 | 0.00 | 0.00 |
June | 0.118373E+10 | 89572243.59 | 0.102345E+10 | 0.335769E+09 | 0.687683E+09 | 0.00 | 0.00 |
July | 0.129274E+10 | 20966507.47 | 0.997438E+09 | 0.300350E+09 | 0.697088E+09 | 0.00 | 0.00 |
August | 0.136271E+10 | 54263275.56 | 0.105455E+10 | 0.399806E+09 | 0.654747E+09 | 0.00 | 0.00 |
September | 0.812078E+09 | 0.159454E+09 | 0.733996E+09 | 0.258377E+09 | 0.475619E+09 | 0.00 | 0.00 |
October | 0.673260E+09 | 0.402639E+09 | 0.733766E+09 | 0.295462E+09 | 0.438304E+09 | 0.00 | 0.00 |
November | 0.162876E+09 | 0.689573E+09 | 0.362787E+09 | 80756499.71 | 0.282030E+09 | 0.00 | 0.00 |
December | 0.108066E+09 | 0.968649E+09 | 0.314283E+09 | 0.108939E+09 | 0.205344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.796451E+10 | 0.584899E+10 | 0.851301E+10 | 0.289563E+10 | 0.561737E+10 | 0.00 | 0.00 |
Minimum of Months | 0.108066E+09 | 20966507.47 | 0.314283E+09 | 80756499.71 | 0.205344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136271E+10 | 0.107521E+10 | 0.105455E+10 | 0.399806E+09 | 0.697088E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262960E+09 | 0.270671E+09 | 0.295319E+09 | 0.193794E+09 | 0.101525E+09 | 0.00 | 0.00 |
February | 0.308138E+09 | 0.255405E+09 | 0.353127E+09 | 0.234741E+09 | 0.118386E+09 | 0.00 | 0.00 |
March | 0.290295E+09 | 0.206456E+09 | 0.346380E+09 | 0.190729E+09 | 0.155651E+09 | 0.00 | 0.00 |
April | 0.204349E+09 | 0.140231E+09 | 0.266699E+09 | 0.107883E+09 | 0.158816E+09 | 0.00 | 0.00 |
May | 0.187849E+09 | 87778730.22 | 0.236685E+09 | 48427436.58 | 0.188257E+09 | 0.00 | 0.00 |
June | 0.214416E+09 | 37813749.59 | 0.216267E+09 | 33282119.10 | 0.182985E+09 | 0.00 | 0.00 |
July | 0.264912E+09 | 14420058.62 | 0.232537E+09 | 39213152.63 | 0.193324E+09 | 0.00 | 0.00 |
August | 0.340237E+09 | 25217090.42 | 0.311462E+09 | 0.114861E+09 | 0.196601E+09 | 0.00 | 0.00 |
September | 0.331938E+09 | 61818532.38 | 0.318164E+09 | 0.159763E+09 | 0.158401E+09 | 0.00 | 0.00 |
October | 0.489660E+09 | 0.135102E+09 | 0.464780E+09 | 0.291539E+09 | 0.173240E+09 | 0.00 | 0.00 |
November | 0.291803E+09 | 0.197197E+09 | 0.311336E+09 | 0.186777E+09 | 0.124559E+09 | 0.00 | 0.00 |
December | 0.299835E+09 | 0.251158E+09 | 0.319013E+09 | 0.226567E+09 | 92445660.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.348639E+10 | 0.168327E+10 | 0.367177E+10 | 0.182758E+10 | 0.184419E+10 | 0.00 | 0.00 |
Minimum of Months | 0.187849E+09 | 14420058.62 | 0.216267E+09 | 33282119.10 | 92445660.92 | 0.00 | 0.00 |
Maximum of Months | 0.489660E+09 | 0.270671E+09 | 0.464780E+09 | 0.291539E+09 | 0.196601E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1002423.82 | 0.327299E+09 | 56833916.07 | 0.00 | 56833916.07 | 0.00 | 0.00 |
February | 3471059.77 | 0.300807E+09 | 70248208.00 | 0.00 | 70248208.00 | 0.00 | 0.00 |
March | 28548208.06 | 0.211515E+09 | 0.107879E+09 | 2144.74 | 0.107877E+09 | 0.00 | 0.00 |
April | 69006833.90 | 0.133188E+09 | 0.125630E+09 | 512072.92 | 0.125118E+09 | 0.00 | 0.00 |
May | 0.145991E+09 | 69109652.33 | 0.172653E+09 | 6300732.54 | 0.166352E+09 | 0.00 | 0.00 |
June | 0.202634E+09 | 22607249.29 | 0.176266E+09 | 9354795.85 | 0.166911E+09 | 0.00 | 0.00 |
July | 0.244833E+09 | 4590424.23 | 0.176791E+09 | 6881439.35 | 0.169909E+09 | 0.00 | 0.00 |
August | 0.221438E+09 | 12999248.07 | 0.156345E+09 | 2063845.80 | 0.154281E+09 | 0.00 | 0.00 |
September | 0.122209E+09 | 43137929.33 | 0.113935E+09 | 64742.79 | 0.113870E+09 | 0.00 | 0.00 |
October | 70375547.27 | 0.114565E+09 | 0.101807E+09 | 0.00 | 0.101807E+09 | 0.00 | 0.00 |
November | 14916829.74 | 0.207738E+09 | 69104215.38 | 0.00 | 69104215.38 | 0.00 | 0.00 |
December | 866806.89 | 0.296329E+09 | 49574277.10 | 0.00 | 49574277.10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112529E+10 | 0.174388E+10 | 0.137707E+10 | 25179774.00 | 0.135189E+10 | 0.00 | 0.00 |
Minimum of Months | 866806.89 | 4590424.23 | 49574277.10 | 0.00 | 49574277.10 | 0.00 | 0.00 |
Maximum of Months | 0.244833E+09 | 0.327299E+09 | 0.176791E+09 | 9354795.85 | 0.169909E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.409081E+09 | 0.100746E+10 | 0.645581E+09 | 0.352722E+09 | 0.292859E+09 | 0.00 | 0.00 |
February | 0.552693E+09 | 0.901017E+09 | 0.829010E+09 | 0.473946E+09 | 0.355065E+09 | 0.00 | 0.00 |
March | 0.743108E+09 | 0.698135E+09 | 0.983997E+09 | 0.472602E+09 | 0.511394E+09 | 0.00 | 0.00 |
April | 0.800855E+09 | 0.449018E+09 | 0.971719E+09 | 0.415049E+09 | 0.556670E+09 | 0.00 | 0.00 |
May | 0.105049E+10 | 0.251714E+09 | 0.109207E+10 | 0.377784E+09 | 0.714290E+09 | 0.00 | 0.00 |
June | 0.110845E+10 | 87670406.55 | 0.985829E+09 | 0.300708E+09 | 0.685120E+09 | 0.00 | 0.00 |
July | 0.130333E+10 | 20313933.23 | 0.103228E+10 | 0.315952E+09 | 0.716325E+09 | 0.00 | 0.00 |
August | 0.150320E+10 | 52452847.86 | 0.122601E+10 | 0.521037E+09 | 0.704974E+09 | 0.00 | 0.00 |
September | 0.109230E+10 | 0.156085E+09 | 0.100348E+10 | 0.472629E+09 | 0.530847E+09 | 0.00 | 0.00 |
October | 0.113778E+10 | 0.397564E+09 | 0.114649E+10 | 0.620438E+09 | 0.526055E+09 | 0.00 | 0.00 |
November | 0.561719E+09 | 0.660828E+09 | 0.728152E+09 | 0.363764E+09 | 0.364388E+09 | 0.00 | 0.00 |
December | 0.470964E+09 | 0.899518E+09 | 0.672661E+09 | 0.412486E+09 | 0.260175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107340E+11 | 0.558178E+10 | 0.113173E+11 | 0.509912E+10 | 0.621816E+10 | 0.00 | 0.00 |
Minimum of Months | 0.409081E+09 | 20313933.23 | 0.645581E+09 | 0.300708E+09 | 0.260175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150320E+10 | 0.100746E+10 | 0.122601E+10 | 0.620438E+09 | 0.716325E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 99599575.79 | 0.105501E+10 | 0.347392E+09 | 0.110431E+09 | 0.236960E+09 | 0.00 | 0.00 |
February | 0.179231E+09 | 0.941122E+09 | 0.475312E+09 | 0.180460E+09 | 0.294852E+09 | 0.00 | 0.00 |
March | 0.421244E+09 | 0.696835E+09 | 0.685767E+09 | 0.234146E+09 | 0.451621E+09 | 0.00 | 0.00 |
April | 0.632308E+09 | 0.444023E+09 | 0.795296E+09 | 0.280808E+09 | 0.514488E+09 | 0.00 | 0.00 |
May | 0.987988E+09 | 0.246974E+09 | 0.101195E+10 | 0.325112E+09 | 0.686834E+09 | 0.00 | 0.00 |
June | 0.107423E+10 | 85766226.69 | 0.935745E+09 | 0.270789E+09 | 0.664956E+09 | 0.00 | 0.00 |
July | 0.125123E+10 | 19929147.75 | 0.962507E+09 | 0.275527E+09 | 0.686980E+09 | 0.00 | 0.00 |
August | 0.133072E+10 | 51014160.21 | 0.103201E+10 | 0.380011E+09 | 0.652000E+09 | 0.00 | 0.00 |
September | 0.817392E+09 | 0.152117E+09 | 0.748092E+09 | 0.272966E+09 | 0.475125E+09 | 0.00 | 0.00 |
October | 0.610737E+09 | 0.390597E+09 | 0.692644E+09 | 0.255942E+09 | 0.436703E+09 | 0.00 | 0.00 |
November | 0.215277E+09 | 0.669539E+09 | 0.425273E+09 | 0.130247E+09 | 0.295026E+09 | 0.00 | 0.00 |
December | 0.110023E+09 | 0.941688E+09 | 0.335775E+09 | 0.129221E+09 | 0.206554E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.772999E+10 | 0.569462E+10 | 0.844776E+10 | 0.284566E+10 | 0.560210E+10 | 0.00 | 0.00 |
Minimum of Months | 99599575.79 | 19929147.75 | 0.335775E+09 | 0.110431E+09 | 0.206554E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133072E+10 | 0.105501E+10 | 0.103201E+10 | 0.380011E+09 | 0.686980E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.507763E+09 | 0.126348E+10 | 0.762996E+09 | 0.419897E+09 | 0.343098E+09 | 0.00 | 0.00 |
February | 0.618947E+09 | 0.114164E+10 | 0.917310E+09 | 0.508619E+09 | 0.408690E+09 | 0.00 | 0.00 |
March | 0.697064E+09 | 0.877499E+09 | 0.984212E+09 | 0.413262E+09 | 0.570950E+09 | 0.00 | 0.00 |
April | 0.615745E+09 | 0.563982E+09 | 0.850020E+09 | 0.234862E+09 | 0.615158E+09 | 0.00 | 0.00 |
May | 0.774265E+09 | 0.296460E+09 | 0.886854E+09 | 0.118578E+09 | 0.768276E+09 | 0.00 | 0.00 |
June | 0.967592E+09 | 94251112.87 | 0.850442E+09 | 92378721.32 | 0.758063E+09 | 0.00 | 0.00 |
July | 0.118043E+10 | 18817616.73 | 0.886832E+09 | 99871502.06 | 0.786961E+09 | 0.00 | 0.00 |
August | 0.128066E+10 | 57780909.42 | 0.101355E+10 | 0.253344E+09 | 0.760205E+09 | 0.00 | 0.00 |
September | 0.103552E+10 | 0.180966E+09 | 0.936194E+09 | 0.346301E+09 | 0.589893E+09 | 0.00 | 0.00 |
October | 0.125449E+10 | 0.477154E+09 | 0.122760E+10 | 0.631684E+09 | 0.595911E+09 | 0.00 | 0.00 |
November | 0.658894E+09 | 0.821744E+09 | 0.824281E+09 | 0.404693E+09 | 0.419588E+09 | 0.00 | 0.00 |
December | 0.594483E+09 | 0.112639E+10 | 0.798606E+09 | 0.490908E+09 | 0.307699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101858E+11 | 0.692017E+10 | 0.109389E+11 | 0.401440E+10 | 0.692449E+10 | 0.00 | 0.00 |
Minimum of Months | 0.507763E+09 | 18817616.73 | 0.762996E+09 | 92378721.32 | 0.307699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128066E+10 | 0.126348E+10 | 0.122760E+10 | 0.631684E+09 | 0.786961E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.411864E+09 | 0.101234E+10 | 0.644189E+09 | 0.355264E+09 | 0.288926E+09 | 0.00 | 0.00 |
February | 0.530527E+09 | 0.914314E+09 | 0.806245E+09 | 0.453646E+09 | 0.352599E+09 | 0.00 | 0.00 |
March | 0.791746E+09 | 0.693137E+09 | 0.103270E+10 | 0.516406E+09 | 0.516298E+09 | 0.00 | 0.00 |
April | 0.799939E+09 | 0.461812E+09 | 0.963564E+09 | 0.404165E+09 | 0.559399E+09 | 0.00 | 0.00 |
May | 0.100481E+10 | 0.261542E+09 | 0.105639E+10 | 0.349541E+09 | 0.706846E+09 | 0.00 | 0.00 |
June | 0.120592E+10 | 93961064.81 | 0.107442E+10 | 0.365988E+09 | 0.708429E+09 | 0.00 | 0.00 |
July | 0.133291E+10 | 22290993.39 | 0.106808E+10 | 0.341055E+09 | 0.727028E+09 | 0.00 | 0.00 |
August | 0.152505E+10 | 56336751.90 | 0.124958E+10 | 0.541276E+09 | 0.708301E+09 | 0.00 | 0.00 |
September | 0.107587E+10 | 0.163927E+09 | 0.990192E+09 | 0.458415E+09 | 0.531777E+09 | 0.00 | 0.00 |
October | 0.118990E+10 | 0.406191E+09 | 0.118859E+10 | 0.660500E+09 | 0.528089E+09 | 0.00 | 0.00 |
November | 0.495088E+09 | 0.664158E+09 | 0.666211E+09 | 0.314531E+09 | 0.351680E+09 | 0.00 | 0.00 |
December | 0.452449E+09 | 0.905334E+09 | 0.651703E+09 | 0.392526E+09 | 0.259177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108161E+11 | 0.565535E+10 | 0.113919E+11 | 0.515331E+10 | 0.623855E+10 | 0.00 | 0.00 |
Minimum of Months | 0.411864E+09 | 22290993.39 | 0.644189E+09 | 0.314531E+09 | 0.259177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152505E+10 | 0.101234E+10 | 0.124958E+10 | 0.660500E+09 | 0.727028E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116429E+09 | 0.107275E+10 | 0.345755E+09 | 0.112774E+09 | 0.232981E+09 | 0.00 | 0.00 |
February | 0.183818E+09 | 0.980434E+09 | 0.452257E+09 | 0.159920E+09 | 0.292337E+09 | 0.00 | 0.00 |
March | 0.475883E+09 | 0.694878E+09 | 0.734230E+09 | 0.277754E+09 | 0.456476E+09 | 0.00 | 0.00 |
April | 0.633217E+09 | 0.457230E+09 | 0.786996E+09 | 0.269815E+09 | 0.517181E+09 | 0.00 | 0.00 |
May | 0.940176E+09 | 0.254982E+09 | 0.976194E+09 | 0.296827E+09 | 0.679367E+09 | 0.00 | 0.00 |
June | 0.117008E+10 | 91201176.41 | 0.102429E+10 | 0.336045E+09 | 0.688247E+09 | 0.00 | 0.00 |
July | 0.127936E+10 | 21643899.68 | 0.998256E+09 | 0.300597E+09 | 0.697659E+09 | 0.00 | 0.00 |
August | 0.135160E+10 | 54409897.22 | 0.105542E+10 | 0.400134E+09 | 0.655284E+09 | 0.00 | 0.00 |
September | 0.802641E+09 | 0.160404E+09 | 0.734598E+09 | 0.258589E+09 | 0.476009E+09 | 0.00 | 0.00 |
October | 0.668445E+09 | 0.401145E+09 | 0.734368E+09 | 0.295704E+09 | 0.438664E+09 | 0.00 | 0.00 |
November | 0.164002E+09 | 0.684610E+09 | 0.363085E+09 | 80822747.87 | 0.282262E+09 | 0.00 | 0.00 |
December | 0.109755E+09 | 0.963899E+09 | 0.314541E+09 | 0.109028E+09 | 0.205512E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789540E+10 | 0.583759E+10 | 0.851999E+10 | 0.289801E+10 | 0.562198E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109755E+09 | 21643899.68 | 0.314541E+09 | 80822747.87 | 0.205512E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135160E+10 | 0.107275E+10 | 0.105542E+10 | 0.400134E+09 | 0.697659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.467070E+09 | 0.526507E+09 | 0.541944E+09 | 0.355634E+09 | 0.186310E+09 | 0.00 | 0.00 |
February | 0.552927E+09 | 0.478575E+09 | 0.648029E+09 | 0.430777E+09 | 0.217251E+09 | 0.00 | 0.00 |
March | 0.523830E+09 | 0.374244E+09 | 0.635647E+09 | 0.350010E+09 | 0.285637E+09 | 0.00 | 0.00 |
April | 0.373008E+09 | 0.245456E+09 | 0.489423E+09 | 0.197978E+09 | 0.291446E+09 | 0.00 | 0.00 |
May | 0.355473E+09 | 0.136493E+09 | 0.434344E+09 | 88869854.15 | 0.345474E+09 | 0.00 | 0.00 |
June | 0.410800E+09 | 46023334.53 | 0.396874E+09 | 61076473.97 | 0.335798E+09 | 0.00 | 0.00 |
July | 0.512164E+09 | 9831959.48 | 0.426732E+09 | 71960595.08 | 0.354772E+09 | 0.00 | 0.00 |
August | 0.646992E+09 | 26946751.98 | 0.571569E+09 | 0.210784E+09 | 0.360785E+09 | 0.00 | 0.00 |
September | 0.619100E+09 | 84058523.02 | 0.583867E+09 | 0.293183E+09 | 0.290684E+09 | 0.00 | 0.00 |
October | 0.900958E+09 | 0.211862E+09 | 0.852923E+09 | 0.535007E+09 | 0.317916E+09 | 0.00 | 0.00 |
November | 0.532210E+09 | 0.350462E+09 | 0.571337E+09 | 0.342756E+09 | 0.228581E+09 | 0.00 | 0.00 |
December | 0.539736E+09 | 0.471150E+09 | 0.585425E+09 | 0.415776E+09 | 0.169648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.643427E+10 | 0.296161E+10 | 0.673811E+10 | 0.335381E+10 | 0.338430E+10 | 0.00 | 0.00 |
Minimum of Months | 0.355473E+09 | 9831959.48 | 0.396874E+09 | 61076473.97 | 0.169648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.900958E+09 | 0.526507E+09 | 0.852923E+09 | 0.535007E+09 | 0.360785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1882178.79 | 0.320805E+10 | 0.497620E+09 | 0.00 | 0.497620E+09 | 0.00 | 0.00 |
February | 14951129.22 | 0.293415E+10 | 0.615071E+09 | 0.00 | 0.615071E+09 | 0.00 | 0.00 |
March | 0.182065E+09 | 0.215437E+10 | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.00 | 0.00 |
April | 0.506527E+09 | 0.140397E+10 | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.00 | 0.00 |
May | 0.112947E+10 | 0.774074E+09 | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.00 | 0.00 |
June | 0.161414E+10 | 0.335303E+09 | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.00 | 0.00 |
July | 0.193257E+10 | 0.137081E+09 | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.00 | 0.00 |
August | 0.173633E+10 | 0.222287E+09 | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.00 | 0.00 |
September | 0.955974E+09 | 0.551658E+09 | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.00 | 0.00 |
October | 0.524844E+09 | 0.122924E+10 | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.00 | 0.00 |
November | 90035012.99 | 0.212627E+10 | 0.605055E+09 | 0.00 | 0.605055E+09 | 0.00 | 0.00 |
December | 2468492.88 | 0.295360E+10 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.869126E+10 | 0.180301E+11 | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.00 | 0.00 |
Minimum of Months | 1882178.79 | 0.137081E+09 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193257E+10 | 0.320805E+10 | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1049760.50 | 0.330752E+10 | 0.497620E+09 | 0.00 | 0.497620E+09 | 0.00 | 0.00 |
February | 11360051.33 | 0.301997E+10 | 0.615071E+09 | 0.00 | 0.615071E+09 | 0.00 | 0.00 |
March | 0.163760E+09 | 0.222541E+10 | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.00 | 0.00 |
April | 0.476637E+09 | 0.145532E+10 | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.00 | 0.00 |
May | 0.108427E+10 | 0.806774E+09 | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.00 | 0.00 |
June | 0.157213E+10 | 0.358087E+09 | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.00 | 0.00 |
July | 0.189169E+10 | 0.154299E+09 | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.00 | 0.00 |
August | 0.169757E+10 | 0.239883E+09 | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.00 | 0.00 |
September | 0.921799E+09 | 0.586527E+09 | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.00 | 0.00 |
October | 0.497171E+09 | 0.127700E+10 | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.00 | 0.00 |
November | 79476699.77 | 0.220323E+10 | 0.605055E+09 | 0.00 | 0.605055E+09 | 0.00 | 0.00 |
December | 1752674.14 | 0.304728E+10 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.839866E+10 | 0.186813E+11 | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.00 | 0.00 |
Minimum of Months | 1049760.50 | 0.154299E+09 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189169E+10 | 0.330752E+10 | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.505714E+09 | 0.211666E+10 | 0.993748E+09 | 0.463517E+09 | 0.530230E+09 | 0.00 | 0.00 |
February | 0.743620E+09 | 0.186689E+10 | 0.130534E+10 | 0.654917E+09 | 0.650420E+09 | 0.00 | 0.00 |
March | 0.123684E+10 | 0.147787E+10 | 0.167106E+10 | 0.707295E+09 | 0.963760E+09 | 0.00 | 0.00 |
April | 0.157093E+10 | 0.982887E+09 | 0.176837E+10 | 0.696388E+09 | 0.107199E+10 | 0.00 | 0.00 |
May | 0.226786E+10 | 0.573386E+09 | 0.210563E+10 | 0.703427E+09 | 0.140220E+10 | 0.00 | 0.00 |
June | 0.246610E+10 | 0.231111E+09 | 0.192305E+10 | 0.571929E+09 | 0.135112E+10 | 0.00 | 0.00 |
July | 0.288034E+10 | 79690122.89 | 0.199631E+10 | 0.591926E+09 | 0.140439E+10 | 0.00 | 0.00 |
August | 0.315936E+10 | 0.137048E+09 | 0.225976E+10 | 0.901733E+09 | 0.135802E+10 | 0.00 | 0.00 |
September | 0.216563E+10 | 0.349824E+09 | 0.175292E+10 | 0.746168E+09 | 0.100675E+10 | 0.00 | 0.00 |
October | 0.192544E+10 | 0.823787E+09 | 0.184057E+10 | 0.877062E+09 | 0.963503E+09 | 0.00 | 0.00 |
November | 0.832338E+09 | 0.140053E+10 | 0.115432E+10 | 0.494398E+09 | 0.659925E+09 | 0.00 | 0.00 |
December | 0.588129E+09 | 0.189047E+10 | 0.100922E+10 | 0.542133E+09 | 0.467091E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203423E+11 | 0.119302E+11 | 0.197803E+11 | 0.795089E+10 | 0.118294E+11 | 0.00 | 0.00 |
Minimum of Months | 0.505714E+09 | 79690122.89 | 0.993748E+09 | 0.463517E+09 | 0.467091E+09 | 0.00 | 0.00 |
Maximum of Months | 0.315936E+10 | 0.211666E+10 | 0.225976E+10 | 0.901733E+09 | 0.140439E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111657E+10 | 0.226528E+10 | 0.155013E+10 | 0.905285E+09 | 0.644848E+09 | 0.00 | 0.00 |
February | 0.134841E+10 | 0.204147E+10 | 0.186044E+10 | 0.109657E+10 | 0.763873E+09 | 0.00 | 0.00 |
March | 0.142306E+10 | 0.159484E+10 | 0.194187E+10 | 0.890975E+09 | 0.105089E+10 | 0.00 | 0.00 |
April | 0.116355E+10 | 0.104665E+10 | 0.162293E+10 | 0.505499E+09 | 0.111743E+10 | 0.00 | 0.00 |
May | 0.133883E+10 | 0.578923E+09 | 0.162386E+10 | 0.245134E+09 | 0.137872E+10 | 0.00 | 0.00 |
June | 0.161498E+10 | 0.227207E+09 | 0.153932E+10 | 0.183552E+09 | 0.135577E+10 | 0.00 | 0.00 |
July | 0.194520E+10 | 76929640.27 | 0.161690E+10 | 0.203834E+09 | 0.141307E+10 | 0.00 | 0.00 |
August | 0.222099E+10 | 0.152984E+09 | 0.192422E+10 | 0.542756E+09 | 0.138147E+10 | 0.00 | 0.00 |
September | 0.193679E+10 | 0.378824E+09 | 0.182824E+10 | 0.746506E+09 | 0.108173E+10 | 0.00 | 0.00 |
October | 0.252278E+10 | 0.896831E+09 | 0.247673E+10 | 0.136189E+10 | 0.111484E+10 | 0.00 | 0.00 |
November | 0.138051E+10 | 0.148923E+10 | 0.166178E+10 | 0.872504E+09 | 0.789278E+09 | 0.00 | 0.00 |
December | 0.130264E+10 | 0.202150E+10 | 0.163903E+10 | 0.105838E+10 | 0.580644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193143E+11 | 0.127707E+11 | 0.212854E+11 | 0.861288E+10 | 0.126726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111657E+10 | 76929640.27 | 0.153932E+10 | 0.183552E+09 | 0.580644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252278E+10 | 0.226528E+10 | 0.247673E+10 | 0.136189E+10 | 0.141307E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.419861E+11 | -.715413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.149430E+10 | 59.02 | 0.00 | 0.00 |
February | 0.386360E+11 | -.652647E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.136419E+10 | 58.99 | 0.00 | 0.00 |
March | 0.411005E+11 | -.706890E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.152494E+10 | 59.00 | 0.00 | 0.00 |
April | 0.359872E+11 | -.648755E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.149523E+10 | 59.06 | 0.00 | 0.00 |
May | 0.321841E+11 | -.623701E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157235E+10 | 59.12 | 0.00 | 0.00 |
June | 0.265506E+11 | -.560807E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.153630E+10 | 59.26 | 0.00 | 0.00 |
July | 0.241446E+11 | -.548927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159183E+10 | 59.43 | 0.00 | 0.00 |
August | 0.233241E+11 | -.541490E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157515E+10 | 59.46 | 0.00 | 0.00 |
September | 0.242374E+11 | -.539795E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.149244E+10 | 59.33 | 0.00 | 0.00 |
October | 0.289397E+11 | -.594395E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.149332E+10 | 59.20 | 0.00 | 0.00 |
November | 0.328631E+11 | -.620458E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.142731E+10 | 59.13 | 0.00 | 0.00 |
December | 0.387316E+11 | -.685369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147830E+10 | 59.06 | 0.00 | 0.00 |
Annual Sum or Average | 0.388685E+12 | -.743865E+12 | 8760.00 | -.180457E+11 | 59.17 | |||||
Minimum of Months | 0.233241E+11 | -.715413E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.159183E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.419861E+11 | -.539795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136419E+10 | 59.46 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770505E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162265082.6 | 81.21 | 0.00 | 0.00 |
February | 0.696260E+10 | -.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146634216.8 | 81.21 | 0.00 | 0.00 |
March | 0.770467E+10 | -.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161852511.5 | 81.21 | 0.00 | 0.00 |
April | 0.746513E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156530264.6 | 81.21 | 0.00 | 0.00 |
May | 0.770505E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162251599.8 | 81.21 | 0.00 | 0.00 |
June | 0.745809E+10 | -.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157572491.3 | 81.21 | 0.00 | 0.00 |
July | 0.771381E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162976183.1 | 81.21 | 0.00 | 0.00 |
August | 0.770568E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162883322.6 | 81.21 | 0.00 | 0.00 |
September | 0.746605E+10 | -.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157471685.7 | 81.21 | 0.00 | 0.00 |
October | 0.770483E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162052827.0 | 81.21 | 0.00 | 0.00 |
November | 0.744904E+10 | -.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156596010.2 | 81.21 | 0.00 | 0.00 |
December | 0.771299E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162137290.8 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907530E+11 | -.888418E+11 | 8760.00 | -.191122E+10 | 81.21 | |||||
Minimum of Months | 0.696260E+10 | -.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162976183.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771381E+10 | -.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146634216.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.786909E+11 | -.774943E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.119661E+10 | 62.95 | 0.00 | 0.00 |
February | 0.711398E+11 | -.700531E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108672E+10 | 62.76 | 0.00 | 0.00 |
March | 0.785973E+11 | -.773742E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122311E+10 | 63.09 | 0.00 | 0.00 |
April | 0.757208E+11 | -.745003E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122048E+10 | 63.93 | 0.00 | 0.00 |
May | 0.777758E+11 | -.764656E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131019E+10 | 64.96 | 0.00 | 0.00 |
June | 0.748371E+11 | -.735344E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.130267E+10 | 65.93 | 0.00 | 0.00 |
July | 0.770285E+11 | -.756646E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136393E+10 | 66.59 | 0.00 | 0.00 |
August | 0.769464E+11 | -.755903E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135618E+10 | 66.76 | 0.00 | 0.00 |
September | 0.746241E+11 | -.733417E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128245E+10 | 66.39 | 0.00 | 0.00 |
October | 0.774769E+11 | -.762075E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.126940E+10 | 65.58 | 0.00 | 0.00 |
November | 0.754310E+11 | -.742422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118886E+10 | 64.59 | 0.00 | 0.00 |
December | 0.783860E+11 | -.771832E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120276E+10 | 63.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.916655E+12 | -.901651E+12 | 8760.00 | -.150034E+11 | 64.77 | |||||
Minimum of Months | 0.711398E+11 | -.774943E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.136393E+10 | 62.76 | 0.00 | 0.00 |
Maximum of Months | 0.786909E+11 | -.700531E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108672E+10 | 66.76 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.93 | 0.93 | 01-JAN-07:49 | 5723.45 | 37.01 | 196.83 | 248.83 | 2734.20 | 33.79 | 187.67 | 189.50 |
February | 216.00 | 0.93 | 0.93 | 01-FEB-07:40 | 8380.42 | 37.63 | 208.33 | 260.00 | 1188.77 | 27.29 | 206.17 | 227.33 |
March | 275.00 | 0.93 | 0.93 | 01-MAR-06:00 | 4052.20 | 25.76 | 162.00 | 328.83 | 736.00 | 22.65 | 209.17 | 263.00 |
April | 261.17 | 0.93 | 0.93 | 01-APR-06:10 | 1442.23 | 20.46 | 80.00 | 345.67 | 588.14 | 22.21 | 202.83 | 281.50 |
May | 372.00 | 0.93 | 0.93 | 01-MAY-05:40 | 1305.02 | 20.17 | 113.00 | 397.17 | 518.46 | 21.90 | 243.00 | 320.17 |
June | 351.83 | 0.93 | 0.93 | 01-JUN-05:10 | 1237.50 | 20.08 | 85.67 | 387.67 | 499.67 | 21.84 | 249.00 | 321.50 |
July | 365.17 | 0.93 | 0.93 | 01-JUL-05:19 | 1379.83 | 20.24 | 116.67 | 396.67 | 546.73 | 21.99 | 266.50 | 325.50 |
August | 389.17 | 0.93 | 0.93 | 01-AUG-05:40 | 1477.50 | 20.52 | 149.00 | 375.17 | 598.29 | 22.26 | 307.50 | 325.17 |
September | 285.33 | 0.93 | 0.93 | 01-SEP-05:00 | 1644.17 | 20.63 | 93.00 | 328.67 | 664.23 | 22.42 | 236.00 | 276.50 |
October | 305.50 | 0.93 | 0.93 | 01-OCT-14:39 | 8341.01 | 36.02 | 285.00 | 310.00 | 1016.91 | 24.99 | 277.00 | 282.17 |
November | 240.83 | 0.93 | 0.93 | 01-NOV-06:49 | 5680.28 | 36.46 | 235.00 | 260.17 | 1510.30 | 29.92 | 223.33 | 229.67 |
December | 211.17 | 0.93 | 0.93 | 01-DEC-07:30 | 5314.33 | 37.99 | 208.00 | 248.50 | 4105.63 | 37.97 | 207.17 | 208.33 |
Annual Sum or Average | 3472.67 | 0.93 | 3441.23 | 26.37 | 1932.50 | 3887.33 | 1062.67 | 24.89 | 2815.33 | 3250.33 | ||
Minimum of Months | 199.50 | 0.93 | 0.93 | 1237.50 | 20.08 | 80.00 | 248.50 | 499.67 | 21.84 | 187.67 | 189.50 | |
Maximum of Months | 389.17 | 0.93 | 0.93 | 8380.42 | 37.99 | 285.00 | 397.17 | 4105.63 | 37.97 | 307.50 | 325.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.62 | 0.61 | 01-JAN-07:40 | 6159.86 | 37.07 | 197.00 | 260.50 | 3171.07 | 33.75 | 189.50 | 221.00 |
February | 216.00 | 0.62 | 0.61 | 01-FEB-07:40 | 8879.91 | 37.71 | 208.33 | 269.33 | 1687.62 | 26.95 | 193.83 | 246.67 |
March | 275.00 | 0.62 | 0.61 | 01-MAR-06:49 | 4460.35 | 25.89 | 152.00 | 337.50 | 1142.38 | 22.65 | 215.00 | 307.67 |
April | 261.17 | 0.62 | 0.61 | 01-APR-05:00 | 1757.61 | 20.75 | 85.00 | 358.17 | 902.63 | 22.34 | 236.83 | 320.67 |
May | 372.00 | 0.62 | 0.61 | 01-MAY-05:40 | 1531.80 | 20.76 | 147.17 | 411.83 | 744.36 | 22.29 | 271.50 | 372.33 |
June | 351.83 | 0.62 | 0.61 | 01-JUN-04:00 | 1454.36 | 20.67 | 148.17 | 404.83 | 715.69 | 22.24 | 278.67 | 362.00 |
July | 365.17 | 0.62 | 0.61 | 01-JUL-05:10 | 1610.78 | 20.82 | 162.83 | 414.00 | 776.74 | 22.38 | 294.00 | 368.17 |
August | 389.17 | 0.63 | 0.61 | 01-AUG-05:19 | 1768.77 | 20.89 | 177.67 | 385.00 | 888.59 | 22.46 | 320.33 | 358.67 |
September | 285.33 | 0.62 | 0.61 | 01-SEP-05:00 | 2008.54 | 20.80 | 103.33 | 340.50 | 1027.47 | 22.44 | 233.83 | 308.00 |
October | 305.50 | 0.62 | 0.61 | 01-OCT-14:39 | 8839.95 | 36.08 | 278.33 | 317.17 | 1514.11 | 24.81 | 283.33 | 300.00 |
November | 240.83 | 0.62 | 0.61 | 01-NOV-06:49 | 6087.20 | 36.53 | 235.00 | 267.83 | 1913.44 | 29.82 | 228.00 | 250.33 |
December | 211.17 | 0.63 | 0.61 | 01-DEC-07:30 | 5748.33 | 38.05 | 208.00 | 256.67 | 4537.54 | 37.98 | 204.67 | 233.67 |
Annual Sum or Average | 3472.67 | 0.62 | 3785.05 | 26.66 | 2102.83 | 4023.33 | 1405.24 | 25.01 | 2949.50 | 3649.17 | ||
Minimum of Months | 199.50 | 0.62 | 0.61 | 1454.36 | 20.67 | 85.00 | 256.67 | 715.69 | 22.24 | 189.50 | 221.00 | |
Maximum of Months | 389.17 | 0.63 | 0.61 | 8879.91 | 38.05 | 278.33 | 414.00 | 4537.54 | 37.98 | 320.33 | 372.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.82 | 0.80 | 01-JAN-08:09 | 432.52 | 15.16 | 0.00 | 231.67 | 208.59 | 18.57 | 0.00 | 115.83 |
February | 216.00 | 0.82 | 0.80 | 01-FEB-08:09 | 444.58 | 15.86 | 0.00 | 247.33 | 227.92 | 19.32 | 0.00 | 154.17 |
March | 275.00 | 0.81 | 0.80 | 01-MAR-06:00 | 609.54 | 17.21 | 0.00 | 325.50 | 293.94 | 20.45 | 27.50 | 241.83 |
April | 261.17 | 0.81 | 0.80 | 01-APR-06:10 | 671.56 | 17.80 | 0.00 | 356.00 | 323.87 | 21.03 | 84.50 | 300.33 |
May | 372.00 | 0.80 | 0.80 | 01-MAY-05:40 | 922.26 | 18.49 | 0.00 | 418.17 | 411.96 | 22.39 | 249.83 | 373.00 |
June | 351.83 | 0.80 | 0.80 | 01-JUN-04:00 | 1023.93 | 19.61 | 29.00 | 410.33 | 445.06 | 23.43 | 264.00 | 376.00 |
July | 365.17 | 0.80 | 0.80 | 01-JUL-04:00 | 1029.06 | 18.55 | 0.00 | 419.50 | 443.93 | 23.07 | 270.83 | 376.83 |
August | 389.17 | 0.81 | 0.80 | 01-AUG-05:10 | 815.66 | 18.24 | 0.00 | 387.83 | 377.42 | 21.47 | 222.83 | 355.67 |
September | 285.33 | 0.81 | 0.80 | 01-SEP-05:00 | 615.42 | 17.42 | 0.00 | 334.00 | 300.70 | 20.68 | 50.33 | 271.00 |
October | 305.50 | 0.81 | 0.80 | 01-OCT-14:39 | 556.67 | 16.98 | 0.00 | 302.17 | 285.23 | 20.34 | 0.17 | 245.83 |
November | 240.83 | 0.81 | 0.80 | 01-NOV-06:00 | 486.01 | 15.72 | 0.00 | 248.67 | 227.84 | 19.04 | 0.00 | 155.00 |
December | 211.17 | 0.83 | 0.80 | 01-DEC-07:00 | 342.50 | 14.26 | 0.00 | 219.50 | 172.15 | 17.83 | 0.00 | 72.17 |
Annual Sum or Average | 3472.67 | 0.81 | 707.50 | 17.40 | 29.00 | 3900.67 | 328.06 | 20.97 | 1170.00 | 3037.67 | ||
Minimum of Months | 199.50 | 0.80 | 0.80 | 342.50 | 14.26 | 0.00 | 219.50 | 172.15 | 17.83 | 0.00 | 72.17 | |
Maximum of Months | 389.17 | 0.83 | 0.80 | 1029.06 | 19.61 | 29.00 | 419.50 | 445.06 | 23.43 | 270.83 | 376.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.82 | 0.80 | 01-JAN-08:09 | 432.52 | 15.16 | 0.00 | 231.67 | 208.59 | 18.57 | 0.00 | 115.83 |
February | 216.00 | 0.82 | 0.80 | 01-FEB-08:09 | 444.58 | 15.86 | 0.00 | 247.33 | 227.92 | 19.32 | 0.00 | 154.17 |
March | 275.00 | 0.81 | 0.80 | 01-MAR-06:00 | 609.54 | 17.21 | 0.00 | 325.50 | 293.94 | 20.45 | 27.50 | 241.83 |
April | 261.17 | 0.81 | 0.80 | 01-APR-06:10 | 671.56 | 17.80 | 0.00 | 356.00 | 323.87 | 21.03 | 84.50 | 300.33 |
May | 372.00 | 0.80 | 0.80 | 01-MAY-05:40 | 922.26 | 18.49 | 0.00 | 418.17 | 411.96 | 22.39 | 249.83 | 373.00 |
June | 351.83 | 0.80 | 0.80 | 01-JUN-04:00 | 1023.93 | 19.61 | 29.00 | 410.33 | 445.06 | 23.43 | 264.00 | 376.00 |
July | 365.17 | 0.80 | 0.80 | 01-JUL-04:00 | 1029.06 | 18.55 | 0.00 | 419.50 | 443.93 | 23.07 | 270.83 | 376.83 |
August | 389.17 | 0.81 | 0.80 | 01-AUG-05:10 | 815.66 | 18.24 | 0.00 | 387.83 | 377.42 | 21.47 | 222.83 | 355.67 |
September | 285.33 | 0.81 | 0.80 | 01-SEP-05:00 | 615.42 | 17.42 | 0.00 | 334.00 | 300.70 | 20.68 | 50.33 | 271.00 |
October | 305.50 | 0.81 | 0.80 | 01-OCT-14:39 | 556.67 | 16.98 | 0.00 | 302.17 | 285.23 | 20.34 | 0.17 | 245.83 |
November | 240.83 | 0.81 | 0.80 | 01-NOV-06:00 | 486.01 | 15.72 | 0.00 | 248.67 | 227.84 | 19.04 | 0.00 | 155.00 |
December | 211.17 | 0.83 | 0.80 | 01-DEC-07:00 | 342.50 | 14.26 | 0.00 | 219.50 | 172.15 | 17.83 | 0.00 | 72.17 |
Annual Sum or Average | 3472.67 | 0.81 | 707.50 | 17.40 | 29.00 | 3900.67 | 328.06 | 20.97 | 1170.00 | 3037.67 | ||
Minimum of Months | 199.50 | 0.80 | 0.80 | 342.50 | 14.26 | 0.00 | 219.50 | 172.15 | 17.83 | 0.00 | 72.17 | |
Maximum of Months | 389.17 | 0.83 | 0.80 | 1029.06 | 19.61 | 29.00 | 419.50 | 445.06 | 23.43 | 270.83 | 376.83 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33147276.53 | 1927.32 | 10-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.988485E+09 | 4721.60 | 30-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169690E+10 | 4304.02 | 18-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.520151E+09 | 2895.90 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5953207.51 | 834.86 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324464E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169690E+10 | 4721.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311596E+10 | 2666.18 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249730E+10 | 2666.18 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172598E+10 | 2206.59 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111020E+10 | 2015.99 | 23-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592889E+09 | 1706.40 | 04-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191363E+09 | 551.82 | 07-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44462648.61 | 462.33 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20794113.63 | 373.23 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.254577E+09 | 1660.75 | 24-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242578E+09 | 1951.62 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147487E+10 | 2025.12 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242610E+10 | 2018.79 | 31-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136971E+11 | |||||||
Minimum of Months | 20794113.63 | 373.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311596E+10 | 2666.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130783E+09 | 604.69 | 03-JAN-12:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93158849.92 | 481.54 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8117904.05 | 280.68 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1863184.05 | 119.02 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2808477.02 | 87.93 | 25-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2736563.65 | 147.91 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3429050.35 | 138.62 | 17-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6144475.26 | 329.03 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48980683.68 | 686.69 | 25-DEC-16:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298022E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130783E+09 | 686.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115379E+10 | 1309.77 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110306E+10 | 1276.55 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446834E+09 | 966.60 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136291E+09 | 943.11 | 20-APR-16:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26588919.44 | 459.37 | 04-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 535161.21 | 44.45 | 12-JUN-15:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2965468.24 | 140.45 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269891E+09 | 936.43 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687951E+09 | 1166.41 | 20-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382790E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115379E+10 | 1309.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105175E+10 | 876.00 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.983661E+09 | 856.30 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.495848E+09 | 641.24 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190931E+09 | 563.62 | 20-APR-16:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36402607.62 | 336.33 | 04-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 781252.39 | 35.62 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4610339.42 | 184.83 | 24-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 453004.61 | 46.63 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319364E+09 | 582.79 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729765E+09 | 620.52 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381356E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105175E+10 | 876.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610220E+09 | 4396.26 | 24-JAN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576583E+09 | 3497.32 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.571882E+09 | 7860.22 | 28-MAR-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109648E+10 | 8168.64 | 14-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213977E+10 | 8022.27 | 16-MAY-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.471754E+10 | 7716.52 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.534570E+10 | 7716.52 | 24-JUL-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.494026E+10 | 7716.49 | 12-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400655E+10 | 7845.64 | 30-SEP-04:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181025E+10 | 7980.37 | 17-OCT-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.509262E+09 | 5017.63 | 14-NOV-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.547065E+09 | 8122.76 | 20-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268716E+11 | |||||||
Minimum of Months | 0.509262E+09 | 3497.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.534570E+10 | 8168.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215045E+10 | 6326.82 | 24-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133868E+10 | 5287.44 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.760789E+09 | 5428.37 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394118E+09 | 5797.00 | 20-APR-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256865E+09 | 2477.00 | 24-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128544E+09 | 1615.83 | 13-JUN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10062568.58 | 959.80 | 24-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5255835.90 | 864.86 | 07-AUG-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136604E+09 | 1935.11 | 22-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34022991.80 | 1241.86 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.438249E+09 | 4329.16 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133592E+10 | 5058.75 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698956E+10 | |||||||
Minimum of Months | 5255835.90 | 864.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.215045E+10 | 6326.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.991440E+09 | 9212.58 | 08-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518764E+09 | 7187.08 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54106029.50 | 4119.86 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2867276.48 | 885.77 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4259725.09 | 1294.67 | 24-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22861752.88 | 2072.42 | 12-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29388997.06 | 2013.31 | 22-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33831499.70 | 4419.42 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363641E+09 | 6301.76 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202116E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.991440E+09 | 9212.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480002E+10 | 6742.93 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399520E+10 | 6742.27 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207528E+10 | 6566.79 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981187E+09 | 6268.90 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122319E+09 | 3681.63 | 29-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5345913.48 | 3115.59 | 11-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4980792.13 | 3163.75 | 02-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4147068.96 | 2581.56 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26752073.08 | 3062.35 | 30-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267102E+09 | 5700.20 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227284E+10 | 6532.63 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384240E+10 | 6706.42 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183976E+11 | |||||||
Minimum of Months | 4147068.96 | 2581.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480002E+10 | 6742.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565101E+10 | 6723.83 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502166E+10 | 6723.13 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256826E+10 | 6577.75 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111842E+10 | 6262.62 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131925E+09 | 3900.12 | 29-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5604490.76 | 3154.40 | 11-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4818889.72 | 3145.53 | 29-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4105417.08 | 2777.87 | 22-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38769969.60 | 2694.31 | 25-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491646E+09 | 6222.06 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293390E+10 | 6578.99 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476419E+10 | 6687.41 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227343E+11 | |||||||
Minimum of Months | 4105417.08 | 2694.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565101E+10 | 6723.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.622151E+10 | 17605.32 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159840E+10 | 13466.90 | 07-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190280E+09 | 8258.79 | 01-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29218095.41 | 3150.23 | 29-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206588E+10 | 12894.24 | 31-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101053E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.622151E+10 | 17605.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198170E+11 | 37557.05 | 14-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193684E+11 | 37650.13 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669712E+10 | 35776.24 | 17-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125782E+10 | 33967.19 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89187303.93 | 31714.58 | 03-MAY-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21066033.13 | 26110.75 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13426412.89 | 16315.16 | 12-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18773365.08 | 21530.28 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56719140.89 | 20677.16 | 24-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583226E+09 | 30635.87 | 21-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640844E+10 | 35811.39 | 22-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147227E+11 | 36676.80 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690538E+11 | |||||||
Minimum of Months | 13426412.89 | 16315.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198170E+11 | 37650.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.478107E+10 | 6503.81 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391170E+10 | 6501.88 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216875E+10 | 6334.64 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.977121E+09 | 6054.63 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136233E+09 | 3220.01 | 04-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3207743.31 | 2296.60 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 736067.70 | 2520.77 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 487337.35 | 2543.50 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20966892.34 | 2255.95 | 23-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290053E+09 | 4990.47 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215839E+10 | 6297.36 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380319E+10 | 6468.60 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182519E+11 | |||||||
Minimum of Months | 487337.35 | 2255.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.478107E+10 | 6503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561860E+10 | 6500.36 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491647E+10 | 6498.40 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268917E+10 | 6331.36 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111779E+10 | 6065.95 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151239E+09 | 3586.71 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3301708.31 | 2171.37 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 820567.56 | 2624.52 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 582397.93 | 2131.55 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37009793.95 | 2559.30 | 27-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.515728E+09 | 5827.52 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273799E+10 | 6320.22 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467381E+10 | 6465.18 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224625E+11 | |||||||
Minimum of Months | 582397.93 | 2131.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561860E+10 | 6500.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138062E+11 | 8560.78 | 18-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113919E+11 | 8179.41 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805046E+10 | 8653.98 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519061E+10 | 8482.78 | 25-APR-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290254E+10 | 7653.73 | 04-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110311E+10 | 3262.24 | 13-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.340923E+09 | 3008.04 | 01-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122876E+09 | 1703.91 | 07-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169960E+10 | 6636.99 | 24-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199900E+10 | 7311.17 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799926E+10 | 8397.14 | 26-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117151E+11 | 7470.43 | 25-DEC-16:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663216E+11 | |||||||
Minimum of Months | 0.122876E+09 | 1703.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138062E+11 | 8653.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163272E+10 | 1949.12 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137870E+10 | 1948.88 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741509E+09 | 1908.77 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.359932E+09 | 1832.39 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50282361.53 | 1123.74 | 04-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1017623.90 | 630.16 | 26-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 878926.43 | 738.19 | 01-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 787018.57 | 626.92 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10718789.91 | 719.16 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118354E+09 | 1800.78 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818740E+09 | 1905.20 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134427E+10 | 1938.48 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645790E+10 | |||||||
Minimum of Months | 787018.57 | 626.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163272E+10 | 1949.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189662E+10 | 1944.80 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168925E+10 | 1944.57 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897786E+09 | 1904.59 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404933E+09 | 1830.51 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54398907.51 | 1215.82 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1027782.99 | 610.51 | 26-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 828131.20 | 757.26 | 01-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 751348.72 | 618.18 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16833849.99 | 710.09 | 23-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202135E+09 | 1826.14 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103386E+10 | 1903.11 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163663E+10 | 1934.21 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783506E+10 | |||||||
Minimum of Months | 751348.72 | 610.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189662E+10 | 1944.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483514E+10 | 8674.05 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356322E+10 | 8671.43 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203936E+10 | 8414.47 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100212E+10 | 8061.14 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94289394.09 | 4037.55 | 02-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4815300.73 | 3572.15 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2586909.10 | 2550.88 | 15-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3157019.85 | 3708.94 | 09-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9459163.62 | 3829.31 | 03-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122515E+09 | 2543.45 | 29-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168316E+10 | 8227.93 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353732E+10 | 8492.10 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168971E+11 | |||||||
Minimum of Months | 2586909.10 | 2543.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.483514E+10 | 8674.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 158881.50 | 529.60 | 28-MAR-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 545109.79 | 1817.03 | 26-APR-01:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 870553.89 | 1182.39 | 16-MAY-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84562.22 | 92.10 | 30-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 55261.51 | 92.10 | 24-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 109121.18 | 133.03 | 22-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 664655.10 | 1736.12 | 17-OCT-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2488145.19 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 870553.89 | 1817.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.563240E+10 | 5095.12 | 02-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486954E+10 | 5095.10 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252648E+10 | 3795.28 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105129E+10 | 3419.08 | 23-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183495E+09 | 2877.07 | 04-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75298038.85 | 2641.38 | 24-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270847E+09 | 3455.47 | 19-OCT-06:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243966E+10 | 3609.06 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441581E+10 | 3468.40 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214648E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563240E+10 | 5095.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.368397E+11 | 97472.89 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384649E+11 | 107467.47 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125288E+11 | 95344.04 | 24-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152823E+11 | 103690.37 | 14-APR-17:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.653138E+10 | 90345.47 | 01-MAY-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137220E+09 | 10087.24 | 10-JUN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17820357.36 | 6854.23 | 11-JUL-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144350E+09 | 21912.83 | 25-AUG-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125578E+10 | 56361.93 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110281E+11 | 108648.90 | 18-OCT-22:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161727E+11 | 108235.37 | 07-NOV-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104929E+11 | 96347.88 | 17-DEC-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148896E+12 | |||||||
Minimum of Months | 17820357.36 | 6854.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.384649E+11 | 108648.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461578E+10 | 10799.51 | 02-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464180E+10 | 11907.35 | 06-FEB-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517017E+09 | 4510.18 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12238.37 | 0.40 | 27-APR-15:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45926.17 | 0.41 | 12-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32464.01 | 0.42 | 12-JUN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16941.73 | 0.42 | 24-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16468.03 | 0.41 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32266.82 | 0.42 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71080.03 | 73.03 | 12-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356845E+09 | 4004.39 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807206E+09 | 7375.35 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109389E+11 | |||||||
Minimum of Months | 12238.37 | 0.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464180E+10 | 11907.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 34692130.13 | 34277188.94 | 12290.27 | 17-JAN-16:02 | 12290.27 | 0.00 |
February | 0.00 | 0.00 | 88825834.65 | 88825834.65 | 12277.06 | 02-FEB-16:02 | 12277.06 | 0.00 |
March | 0.00 | 0.00 | 0.620682E+09 | 0.573107E+09 | 12918.84 | 27-MAR-15:02 | 11329.33 | 0.03 |
April | 0.00 | 0.00 | 0.147575E+10 | 0.106473E+10 | 12855.23 | 09-APR-15:02 | 11648.92 | 0.24 |
May | 0.00 | 0.00 | 0.308186E+10 | 0.208831E+10 | 13982.82 | 31-MAY-18:02 | 11838.02 | 0.50 |
June | 0.00 | 0.00 | 0.651703E+10 | 0.351413E+10 | 17908.57 | 25-JUN-08:62 | 9998.96 | 0.81 |
July | 0.00 | 0.00 | 0.907903E+10 | 0.472592E+10 | 18639.62 | 22-JUL-08:62 | 9855.69 | 0.91 |
August | 0.00 | 0.00 | 0.922301E+10 | 0.532697E+10 | 17800.15 | 03-AUG-08:62 | 10475.44 | 0.92 |
September | 0.00 | 0.00 | 0.487502E+10 | 0.265414E+10 | 17470.48 | 22-SEP-18:03 | 8455.00 | 0.75 |
October | 0.00 | 0.00 | 0.309349E+10 | 0.186319E+10 | 14851.65 | 05-OCT-18:02 | 10601.31 | 0.47 |
November | 0.00 | 0.00 | 0.242932E+09 | 0.194450E+09 | 12472.38 | 03-NOV-15:02 | 12472.38 | 0.05 |
December | 0.00 | 0.00 | 43234815.20 | 42732438.51 | 12180.73 | 17-DEC-16:02 | 12180.73 | 0.00 |
Annual Sum or Average | 0.383756E+11 | 0.221708E+11 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 34692130.13 | 34277188.94 | 12180.73 | 8455.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.922301E+10 | 0.532697E+10 | 18639.62 | 12472.38 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4155308.93 | 3786972.93 | 6629.23 | 17-JAN-16:02 | 6629.23 | 0.00 |
February | 0.00 | 0.00 | 15957946.01 | 15957946.01 | 11067.02 | 20-FEB-16:02 | 11067.02 | 0.00 |
March | 0.00 | 0.00 | 0.324615E+09 | 0.292157E+09 | 12396.91 | 27-MAR-15:02 | 10676.33 | 0.02 |
April | 0.00 | 0.00 | 0.111387E+10 | 0.805007E+09 | 12735.18 | 09-APR-15:02 | 11414.52 | 0.20 |
May | 0.00 | 0.00 | 0.286274E+10 | 0.192862E+10 | 13711.99 | 31-MAY-08:62 | 11387.80 | 0.48 |
June | 0.00 | 0.00 | 0.633346E+10 | 0.341749E+10 | 17019.81 | 25-JUN-08:62 | 10184.33 | 0.80 |
July | 0.00 | 0.00 | 0.878587E+10 | 0.455621E+10 | 18350.42 | 22-JUL-08:62 | 9693.35 | 0.90 |
August | 0.00 | 0.00 | 0.841936E+10 | 0.476287E+10 | 17242.24 | 03-AUG-08:62 | 10474.94 | 0.89 |
September | 0.00 | 0.00 | 0.386042E+10 | 0.200324E+10 | 17176.42 | 22-SEP-18:03 | 8284.19 | 0.67 |
October | 0.00 | 0.00 | 0.163761E+10 | 0.917657E+09 | 13934.71 | 05-OCT-18:02 | 10501.17 | 0.34 |
November | 0.00 | 0.00 | 51060292.54 | 43447902.05 | 11921.40 | 03-NOV-15:02 | 11921.40 | 0.01 |
December | 0.00 | 0.00 | 1895150.34 | 1685244.42 | 3655.84 | 17-DEC-16:02 | 3655.84 | 0.00 |
Annual Sum or Average | 0.334110E+11 | 0.187481E+11 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 1895150.34 | 1685244.42 | 3655.84 | 3655.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.878587E+10 | 0.476287E+10 | 18350.42 | 11921.40 | 0.90 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.107691E+09 | 0.107691E+09 | 7099.73 | 19-JAN-14:30 | 7099.73 | 0.00 |
February | 0.00 | 0.00 | 0.634911E+09 | 0.634911E+09 | 17476.77 | 03-FEB-12:30 | 17476.77 | 0.00 |
March | 0.00 | 0.00 | 0.117347E+10 | 0.117347E+10 | 24074.66 | 03-MAR-13:30 | 24074.66 | 0.00 |
April | 0.00 | 0.00 | 0.265227E+10 | 0.189950E+10 | 30800.54 | 08-APR-12:20 | 27651.43 | 0.07 |
May | 0.00 | 0.00 | 0.387190E+10 | 0.234930E+10 | 24714.22 | 31-MAY-15:10 | 14735.96 | 0.12 |
June | 0.00 | 0.00 | 0.141817E+11 | 0.570833E+10 | 40757.39 | 25-JUN-16:10 | 18701.13 | 0.52 |
July | 0.00 | 0.00 | 0.333055E+11 | 0.142490E+11 | 53882.38 | 22-JUL-16:05 | 23505.13 | 0.83 |
August | 0.00 | 0.00 | 0.372275E+11 | 0.206009E+11 | 51748.86 | 03-AUG-20:20 | 24399.21 | 0.86 |
September | 0.00 | 0.00 | 0.224441E+11 | 0.139405E+11 | 48194.67 | 07-SEP-16:20 | 23339.00 | 0.54 |
October | 0.00 | 0.00 | 0.243141E+11 | 0.195866E+11 | 47308.66 | 04-OCT-12:00 | 42396.71 | 0.31 |
November | 0.00 | 0.00 | 0.500820E+10 | 0.480164E+10 | 40525.11 | 02-NOV-12:30 | 40525.11 | 0.03 |
December | 0.00 | 0.00 | 0.235965E+10 | 0.235965E+10 | 32118.10 | 17-DEC-13:00 | 32118.10 | 0.00 |
Annual Sum or Average | 0.147281E+12 | 0.874115E+11 | 0.28 | |||||
Minimum of Months | 0.00 | 0.00 | 0.107691E+09 | 0.107691E+09 | 7099.73 | 7099.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.372275E+11 | 0.206009E+11 | 53882.38 | 42396.71 | 0.86 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.226330E+09 | 0.104444E+09 | 26802.37 | 22-JAN-09:02 | 21929.89 | 0.02 |
February | 0.00 | 0.00 | 90328206.52 | 87941228.23 | 32993.55 | 20-FEB-09:02 | 32993.55 | 0.00 |
March | 0.00 | 0.00 | 0.228894E+10 | 0.166995E+10 | 59377.03 | 28-MAR-18:01 | 59377.03 | 0.09 |
April | 0.00 | 0.00 | 0.108915E+11 | 0.698765E+10 | 64371.38 | 09-APR-15:02 | 57899.28 | 0.34 |
May | 0.00 | 0.00 | 0.281777E+11 | 0.190060E+11 | 78082.76 | 31-MAY-18:02 | 58883.00 | 0.53 |
June | 0.00 | 0.00 | 0.497857E+11 | 0.294147E+11 | 97974.99 | 25-JUN-18:02 | 53541.00 | 0.68 |
July | 0.00 | 0.00 | 0.697690E+11 | 0.412618E+11 | 104381.12 | 22-JUL-08:62 | 51196.73 | 0.72 |
August | 0.00 | 0.00 | 0.597473E+11 | 0.368761E+11 | 99769.93 | 31-AUG-18:02 | 52448.36 | 0.71 |
September | 0.00 | 0.00 | 0.350362E+11 | 0.195801E+11 | 98684.71 | 07-SEP-18:02 | 53307.67 | 0.66 |
October | 0.00 | 0.00 | 0.157470E+11 | 0.809042E+10 | 76169.99 | 05-OCT-18:02 | 51893.98 | 0.44 |
November | 0.00 | 0.00 | 0.316070E+10 | 0.206982E+10 | 60227.41 | 05-NOV-08:62 | 60227.41 | 0.14 |
December | 0.00 | 0.00 | 0.192919E+09 | 0.150192E+09 | 35697.41 | 25-DEC-09:02 | 32308.57 | 0.01 |
Annual Sum or Average | 0.275114E+12 | 0.165299E+12 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 90328206.52 | 87941228.23 | 26802.37 | 21929.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.697690E+11 | 0.412618E+11 | 104381.12 | 60227.41 | 0.72 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 55265411.34 | 54884469.44 | 10080.24 | 19-JAN-09:02 | 10080.24 | 0.00 |
February | 0.00 | 0.00 | 93570124.58 | 93514507.53 | 10604.78 | 19-FEB-09:02 | 10604.78 | 0.00 |
March | 0.00 | 0.00 | 0.480280E+09 | 0.450466E+09 | 11279.07 | 27-MAR-15:02 | 9600.42 | 0.02 |
April | 0.00 | 0.00 | 0.145027E+10 | 0.101145E+10 | 11657.16 | 09-APR-15:02 | 10499.55 | 0.27 |
May | 0.00 | 0.00 | 0.322650E+10 | 0.220601E+10 | 13541.10 | 31-MAY-18:02 | 10179.91 | 0.52 |
June | 0.00 | 0.00 | 0.599790E+10 | 0.320099E+10 | 15503.32 | 25-JUN-18:02 | 9480.53 | 0.83 |
July | 0.00 | 0.00 | 0.889216E+10 | 0.462078E+10 | 16602.50 | 22-JUL-08:62 | 9062.19 | 0.93 |
August | 0.00 | 0.00 | 0.909794E+10 | 0.520402E+10 | 15843.07 | 31-AUG-18:02 | 9286.18 | 0.95 |
September | 0.00 | 0.00 | 0.490434E+10 | 0.272205E+10 | 15791.85 | 22-SEP-18:03 | 7592.90 | 0.79 |
October | 0.00 | 0.00 | 0.288485E+10 | 0.173364E+10 | 13799.25 | 25-OCT-08:62 | 9576.20 | 0.46 |
November | 0.00 | 0.00 | 0.368518E+09 | 0.301309E+09 | 11203.04 | 03-NOV-15:02 | 11203.04 | 0.05 |
December | 0.00 | 0.00 | 0.105481E+09 | 0.105182E+09 | 10669.74 | 17-DEC-09:02 | 10669.74 | 0.00 |
Annual Sum or Average | 0.375571E+11 | 0.217043E+11 | 0.40 | |||||
Minimum of Months | 0.00 | 0.00 | 55265411.34 | 54884469.44 | 10080.24 | 7592.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.909794E+10 | 0.520402E+10 | 16602.50 | 11203.04 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3494534.22 | 3174949.50 | 2513.97 | 26-JAN-09:03 | 2513.97 | 0.00 |
February | 0.00 | 0.00 | 16252887.58 | 16252887.58 | 10012.44 | 19-FEB-09:02 | 10012.44 | 0.00 |
March | 0.00 | 0.00 | 0.218163E+09 | 0.202442E+09 | 10904.35 | 03-MAR-09:02 | 10904.35 | 0.01 |
April | 0.00 | 0.00 | 0.108878E+10 | 0.755630E+09 | 11442.59 | 09-APR-15:02 | 10212.45 | 0.21 |
May | 0.00 | 0.00 | 0.300136E+10 | 0.204672E+10 | 12996.25 | 31-MAY-18:02 | 10348.36 | 0.50 |
June | 0.00 | 0.00 | 0.580389E+10 | 0.309817E+10 | 15428.35 | 25-JUN-18:02 | 9376.32 | 0.82 |
July | 0.00 | 0.00 | 0.859947E+10 | 0.445998E+10 | 16482.68 | 22-JUL-08:62 | 8983.23 | 0.93 |
August | 0.00 | 0.00 | 0.828735E+10 | 0.466425E+10 | 15926.46 | 31-AUG-18:02 | 9085.53 | 0.94 |
September | 0.00 | 0.00 | 0.385328E+10 | 0.205094E+10 | 15729.94 | 07-SEP-18:02 | 9229.92 | 0.69 |
October | 0.00 | 0.00 | 0.142913E+10 | 0.770987E+09 | 13591.71 | 25-OCT-08:62 | 9306.88 | 0.32 |
November | 0.00 | 0.00 | 97995018.40 | 75917832.83 | 9060.95 | 04-NOV-08:62 | 9060.95 | 0.02 |
December | 0.00 | 0.00 | 5121257.20 | 4982446.47 | 4723.22 | 17-DEC-09:02 | 4723.22 | 0.00 |
Annual Sum or Average | 0.324043E+11 | 0.181494E+11 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 3494534.22 | 3174949.50 | 2513.97 | 2513.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859947E+10 | 0.466425E+10 | 16482.68 | 10904.35 | 0.94 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8751799.37 | 8671580.51 | 3223.45 | 17-JAN-16:02 | 3223.45 | 0.00 |
February | 0.00 | 0.00 | 23969166.45 | 23966343.15 | 3223.98 | 20-FEB-16:02 | 3223.98 | 0.00 |
March | 0.00 | 0.00 | 0.168421E+09 | 0.155680E+09 | 3431.98 | 27-MAR-15:02 | 3037.51 | 0.02 |
April | 0.00 | 0.00 | 0.423115E+09 | 0.316731E+09 | 3359.98 | 10-APR-15:01 | 3359.98 | 0.22 |
May | 0.00 | 0.00 | 0.918573E+09 | 0.649539E+09 | 3785.53 | 31-MAY-08:62 | 3046.09 | 0.49 |
June | 0.00 | 0.00 | 0.196126E+10 | 0.110735E+10 | 4832.60 | 25-JUN-08:62 | 2538.02 | 0.85 |
July | 0.00 | 0.00 | 0.272733E+10 | 0.150510E+10 | 4977.18 | 22-JUL-08:62 | 2527.96 | 0.93 |
August | 0.00 | 0.00 | 0.271581E+10 | 0.165896E+10 | 4697.64 | 03-AUG-08:62 | 2728.26 | 0.93 |
September | 0.00 | 0.00 | 0.143369E+10 | 0.823169E+09 | 4739.49 | 22-SEP-18:03 | 2158.64 | 0.75 |
October | 0.00 | 0.00 | 0.841948E+09 | 0.527689E+09 | 3997.05 | 05-OCT-18:02 | 2793.04 | 0.44 |
November | 0.00 | 0.00 | 56477934.44 | 46191801.97 | 3271.21 | 03-NOV-15:02 | 3271.21 | 0.04 |
December | 0.00 | 0.00 | 8358712.39 | 8271176.40 | 3222.41 | 17-DEC-16:02 | 3222.41 | 0.00 |
Annual Sum or Average | 0.112877E+11 | 0.683132E+10 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 8358712.39 | 8271176.40 | 3222.41 | 2158.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.272733E+10 | 0.165896E+10 | 4977.18 | 3359.98 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 455451.96 | 398152.55 | 844.51 | 17-JAN-16:02 | 844.51 | 0.00 |
February | 0.00 | 0.00 | 1820659.88 | 1816146.41 | 2251.90 | 20-FEB-16:02 | 2251.90 | 0.00 |
March | 0.00 | 0.00 | 81440844.42 | 72663083.61 | 3272.71 | 27-MAR-15:02 | 2832.90 | 0.02 |
April | 0.00 | 0.00 | 0.319553E+09 | 0.238046E+09 | 3321.06 | 16-APR-18:02 | 3321.06 | 0.18 |
May | 0.00 | 0.00 | 0.856379E+09 | 0.602727E+09 | 3716.10 | 31-MAY-08:62 | 3001.32 | 0.47 |
June | 0.00 | 0.00 | 0.191156E+10 | 0.107914E+10 | 4571.68 | 25-JUN-08:62 | 2606.78 | 0.85 |
July | 0.00 | 0.00 | 0.265039E+10 | 0.145505E+10 | 4895.30 | 22-JUL-08:62 | 2485.14 | 0.93 |
August | 0.00 | 0.00 | 0.249986E+10 | 0.149193E+10 | 4523.28 | 03-AUG-08:62 | 2741.35 | 0.93 |
September | 0.00 | 0.00 | 0.114783E+10 | 0.627445E+09 | 4656.86 | 22-SEP-18:03 | 2113.52 | 0.67 |
October | 0.00 | 0.00 | 0.444763E+09 | 0.259995E+09 | 3767.44 | 05-OCT-18:02 | 2778.24 | 0.31 |
November | 0.00 | 0.00 | 11896204.26 | 10425463.86 | 3138.27 | 03-NOV-15:02 | 3138.27 | 0.01 |
December | 0.00 | 0.00 | 454654.29 | 429746.21 | 620.47 | 08-DEC-16:03 | 620.47 | 0.00 |
Annual Sum or Average | 0.992639E+10 | 0.584007E+10 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 454654.29 | 398152.55 | 620.47 | 620.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.265039E+10 | 0.149193E+10 | 4895.30 | 3321.06 | 0.93 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.918616E+09 | 0.918056E+09 | 12800.00 | 17-JAN-16:02 | 12800.00 | 0.00 |
February | 0.00 | 0.00 | 0.121591E+10 | 0.121579E+10 | 12801.36 | 20-FEB-16:02 | 12801.36 | 0.00 |
March | 0.00 | 0.00 | 0.194291E+10 | 0.182995E+10 | 13721.56 | 27-MAR-15:02 | 12415.70 | 0.06 |
April | 0.00 | 0.00 | 0.248191E+10 | 0.180513E+10 | 13441.22 | 27-APR-15:02 | 12458.75 | 0.30 |
May | 0.00 | 0.00 | 0.426113E+10 | 0.281466E+10 | 16182.53 | 31-MAY-18:02 | 11427.10 | 0.57 |
June | 0.00 | 0.00 | 0.911214E+10 | 0.504865E+10 | 19358.41 | 25-JUN-08:62 | 10048.62 | 0.83 |
July | 0.00 | 0.00 | 0.137853E+11 | 0.781681E+10 | 20111.71 | 21-JUL-08:62 | 9896.74 | 0.91 |
August | 0.00 | 0.00 | 0.139661E+11 | 0.897643E+10 | 19441.43 | 03-AUG-08:62 | 10417.74 | 0.92 |
September | 0.00 | 0.00 | 0.956815E+10 | 0.618115E+10 | 19339.48 | 22-SEP-18:03 | 8531.58 | 0.83 |
October | 0.00 | 0.00 | 0.853089E+10 | 0.638102E+10 | 16064.72 | 05-OCT-18:02 | 10594.06 | 0.55 |
November | 0.00 | 0.00 | 0.219309E+10 | 0.194612E+10 | 12988.24 | 03-NOV-15:02 | 12988.24 | 0.13 |
December | 0.00 | 0.00 | 0.165194E+10 | 0.165045E+10 | 12797.85 | 16-DEC-16:01 | 12797.85 | 0.00 |
Annual Sum or Average | 0.696281E+11 | 0.465842E+11 | 0.43 | |||||
Minimum of Months | 0.00 | 0.00 | 0.918616E+09 | 0.918056E+09 | 12797.85 | 8531.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139661E+11 | 0.897643E+10 | 20111.71 | 12988.24 | 0.92 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.212584E+09 | 0.212584E+09 | 8856.44 | 21-JAN-19:30 | 8856.44 | 0.01 |
February | 0.00 | 0.00 | 0.201468E+09 | 0.201468E+09 | 8642.35 | 20-FEB-10:56 | 8642.35 | 0.00 |
March | 0.00 | 0.00 | 0.612803E+10 | 0.540477E+10 | 198352.77 | 27-MAR-13:00 | 131748.61 | 0.05 |
April | 0.00 | 0.00 | 0.470231E+11 | 0.457603E+11 | 242994.98 | 09-APR-11:00 | 152396.02 | 0.20 |
May | 0.00 | 0.00 | 0.176419E+12 | 0.142571E+12 | 310419.14 | 31-MAY-17:20 | 166703.56 | 0.46 |
June | 0.00 | 0.00 | 0.617531E+12 | 0.355495E+12 | 484633.62 | 24-JUN-18:03 | 177011.66 | 0.91 |
July | 0.00 | 0.00 | 0.881567E+12 | 0.472566E+12 | 484799.26 | 05-JUL-20:10 | 196163.95 | 1.00 |
August | 0.00 | 0.00 | 0.731925E+12 | 0.460386E+12 | 463333.30 | 03-AUG-20:00 | 218906.97 | 0.98 |
September | 0.00 | 0.00 | 0.444639E+12 | 0.292547E+12 | 467975.21 | 22-SEP-17:40 | 165731.06 | 0.82 |
October | 0.00 | 0.00 | 0.180079E+12 | 0.107711E+12 | 310873.74 | 25-OCT-09:30 | 159493.85 | 0.46 |
November | 0.00 | 0.00 | 0.707298E+10 | 0.612666E+10 | 122727.80 | 10-NOV-08:00 | 45304.29 | 0.04 |
December | 0.00 | 0.00 | 0.390687E+09 | 0.390687E+09 | 25064.78 | 17-DEC-19:10 | 25064.78 | 0.00 |
Annual Sum or Average | 0.309319E+13 | 0.188937E+13 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 0.201468E+09 | 0.201468E+09 | 8642.35 | 8642.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.881567E+12 | 0.472566E+12 | 484799.26 | 218906.97 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.689508E+09 | 0.588199E+09 | 32555.93 | 27-MAR-13:00 | 21428.09 | 0.02 |
April | 0.00 | 0.00 | 0.632347E+10 | 0.616292E+10 | 40026.79 | 09-APR-11:00 | 24732.38 | 0.14 |
May | 0.00 | 0.00 | 0.231938E+11 | 0.195867E+11 | 51576.65 | 31-MAY-17:07 | 27125.24 | 0.37 |
June | 0.00 | 0.00 | 0.970001E+11 | 0.554313E+11 | 81187.73 | 24-JUN-17:40 | 28247.42 | 0.91 |
July | 0.00 | 0.00 | 0.135406E+12 | 0.744891E+11 | 77209.19 | 30-JUL-07:20 | 27707.96 | 1.00 |
August | 0.00 | 0.00 | 0.109874E+12 | 0.709867E+11 | 74172.47 | 06-AUG-07:20 | 27261.35 | 0.99 |
September | 0.00 | 0.00 | 0.668118E+11 | 0.447103E+11 | 77970.79 | 22-SEP-17:30 | 27037.62 | 0.80 |
October | 0.00 | 0.00 | 0.243756E+11 | 0.147820E+11 | 52097.06 | 24-OCT-14:00 | 26079.42 | 0.41 |
November | 0.00 | 0.00 | 0.604778E+09 | 0.540994E+09 | 12356.09 | 10-NOV-08:00 | 4465.56 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.464280E+12 | 0.287278E+12 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135406E+12 | 0.744891E+11 | 81187.73 | 28247.42 | 1.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 28214.11 | 66601.35 | 18-JAN-07:22 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28531.24 | 57925.99 | 10-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27915.59 | 65572.97 | 28-MAR-06:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26449.53 | 61441.00 | 05-APR-06:36 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 24636.64 | 60267.49 | 02-MAY-06:22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22766.18 | 48252.68 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21360.66 | 45030.00 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21039.00 | 44052.23 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21850.62 | 46829.95 | 20-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 23398.61 | 53739.30 | 09-OCT-08:21 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25257.74 | 60477.33 | 05-NOV-07:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27030.64 | 61642.63 | 25-DEC-08:38 |
Annual Sum or Average | 0.00 | 24849.45 | ||||
Minimum of Months | 0.00 | 0.00 | 21039.00 | 44052.23 | ||
Maximum of Months | 0.00 | 0.00 | 28531.24 | 66601.35 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 46010.74 | 192431.98 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 45508.58 | 191502.21 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17446.50 | 128445.57 | 22-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11994.79 | 118615.37 | 02-APR-18:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 5326.74 | 95690.75 | 03-MAY-15:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3057.32 | 100402.60 | 06-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2317.94 | 33655.07 | 05-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1937.81 | 40106.52 | 08-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2925.42 | 87503.11 | 26-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 6592.10 | 113513.90 | 10-OCT-05:33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 18925.54 | 145322.76 | 16-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27031.07 | 140337.08 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 15583.24 | ||||
Minimum of Months | 0.00 | 0.00 | 1937.81 | 33655.07 | ||
Maximum of Months | 0.00 | 0.00 | 46010.74 | 192431.98 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1420.56 | 29336.16 | 19-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1927.43 | 38284.58 | 20-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 6703.63 | 293345.40 | 27-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 30912.48 | 347508.59 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95783.32 | 510311.69 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 317673.91 | 766306.07 | 24-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 441477.20 | 729390.83 | 14-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 373603.90 | 720387.39 | 03-AUG-20:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 233635.40 | 700434.73 | 22-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 100717.54 | 526728.47 | 24-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 8770.88 | 164811.94 | 04-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2917.93 | 48225.33 | 12-DEC-19:05 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 135575.60 | 0.00 | ||||
Minimum of Months | 1420.56 | 29336.16 | 0.00 | 0.00 | ||
Maximum of Months | 441477.20 | 766306.07 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587767E+10 | 0.88 | 2194.47 | 04-JAN-09:15 | 0.88 |
February | 0.530887E+10 | 0.88 | 2194.47 | 06-FEB-02:30 | 0.88 |
March | 0.587767E+10 | 0.88 | 2194.47 | 03-MAR-09:02 | 0.88 |
April | 0.568807E+10 | 0.88 | 2194.47 | 02-APR-08:62 | 0.88 |
May | 0.587767E+10 | 0.87 | 2194.47 | 01-MAY-15:03 | 0.88 |
June | 0.568807E+10 | 0.87 | 2194.47 | 01-JUN-20:40 | 0.87 |
July | 0.587767E+10 | 0.87 | 2194.47 | 01-JUL-15:30 | 0.87 |
August | 0.587767E+10 | 0.87 | 2194.47 | 01-AUG-06:20 | 0.87 |
September | 0.568807E+10 | 0.87 | 2194.47 | 01-SEP-19:00 | 0.87 |
October | 0.587767E+10 | 0.87 | 2194.47 | 03-OCT-15:15 | 0.87 |
November | 0.568807E+10 | 0.88 | 2194.47 | 23-NOV-19:05 | 0.88 |
December | 0.587767E+10 | 0.88 | 2194.47 | 02-DEC-19:03 | 0.88 |
Annual Sum or Average | 0.692049E+11 | 0.87 | |||
Minimum of Months | 0.530887E+10 | 0.87 | 2194.47 | 0.87 | |
Maximum of Months | 0.587767E+10 | 0.88 | 2194.47 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.377369E+11 | 0.89 | 26243.49 | 23-JAN-21:05 | 1.29 |
February | 0.340362E+11 | 0.89 | 23004.95 | 19-FEB-12:20 | 1.20 |
March | 0.388898E+11 | 0.91 | 35276.49 | 03-MAR-23:00 | 1.56 |
April | 0.376871E+11 | 0.90 | 36143.63 | 11-APR-22:02 | 1.59 |
May | 0.375621E+11 | 0.88 | 28141.41 | 01-MAY-20:33 | 1.35 |
June | 0.345859E+11 | 0.86 | 20446.99 | 22-JUN-19:10 | 1.11 |
July | 0.355732E+11 | 0.86 | 18717.62 | 11-JUL-18:03 | 1.05 |
August | 0.358133E+11 | 0.86 | 22148.98 | 24-AUG-20:20 | 1.16 |
September | 0.346807E+11 | 0.86 | 24469.97 | 29-SEP-23:53 | 1.24 |
October | 0.381620E+11 | 0.89 | 41758.20 | 18-OCT-20:25 | 1.73 |
November | 0.383059E+11 | 0.91 | 38859.40 | 06-NOV-22:05 | 1.65 |
December | 0.383773E+11 | 0.90 | 35949.21 | 04-DEC-23:05 | 1.57 |
Annual Sum or Average | 0.441410E+12 | 0.89 | |||
Minimum of Months | 0.340362E+11 | 0.86 | 18717.62 | 1.05 | |
Maximum of Months | 0.388898E+11 | 0.91 | 41758.20 | 1.73 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:03 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:03 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:03 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.26 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.366607E+09 | 0.45 | 728.06 | 01-JAN-09:02 | 0.58 |
February | 0.315872E+09 | 0.44 | 728.06 | 01-FEB-09:02 | 0.58 |
March | 0.231668E+09 | 0.42 | 728.06 | 01-MAR-09:02 | 0.58 |
April | 0.198292E+09 | 0.43 | 728.06 | 01-APR-08:62 | 0.58 |
May | 0.211179E+09 | 0.45 | 728.06 | 01-MAY-15:02 | 0.58 |
June | 0.320949E+09 | 0.48 | 728.06 | 01-JUN-08:62 | 0.57 |
July | 0.403540E+09 | 0.52 | 728.06 | 01-JUL-08:62 | 0.57 |
August | 0.436027E+09 | 0.53 | 728.06 | 01-AUG-08:61 | 0.57 |
September | 0.259183E+09 | 0.48 | 728.06 | 01-SEP-08:61 | 0.57 |
October | 0.210897E+09 | 0.47 | 728.06 | 02-OCT-15:02 | 0.57 |
November | 0.220130E+09 | 0.42 | 728.06 | 01-NOV-08:62 | 0.57 |
December | 0.311848E+09 | 0.44 | 728.06 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.348619E+10 | 0.46 | |||
Minimum of Months | 0.198292E+09 | 0.42 | 728.06 | 0.57 | |
Maximum of Months | 0.436027E+09 | 0.53 | 728.06 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.422697E+09 | 0.48 | 716.13 | 01-JAN-09:02 | 0.58 |
February | 0.380329E+09 | 0.47 | 716.13 | 01-FEB-09:02 | 0.58 |
March | 0.244454E+09 | 0.42 | 716.13 | 01-MAR-09:02 | 0.58 |
April | 0.185909E+09 | 0.42 | 716.13 | 01-APR-08:62 | 0.58 |
May | 0.199263E+09 | 0.44 | 716.13 | 01-MAY-15:02 | 0.58 |
June | 0.311796E+09 | 0.48 | 716.13 | 01-JUN-08:62 | 0.57 |
July | 0.390465E+09 | 0.51 | 716.13 | 01-JUL-08:62 | 0.57 |
August | 0.398255E+09 | 0.51 | 716.13 | 01-AUG-08:61 | 0.57 |
September | 0.209733E+09 | 0.45 | 716.13 | 01-SEP-08:61 | 0.57 |
October | 0.154698E+09 | 0.42 | 716.13 | 02-OCT-15:02 | 0.57 |
November | 0.251574E+09 | 0.42 | 716.13 | 01-NOV-08:62 | 0.57 |
December | 0.363120E+09 | 0.46 | 716.13 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.351229E+10 | 0.46 | |||
Minimum of Months | 0.154698E+09 | 0.42 | 716.13 | 0.57 | |
Maximum of Months | 0.422697E+09 | 0.51 | 716.13 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.503512E+09 | 0.21 | 1001.79 | 02-JAN-05:10 | 0.58 |
February | 0.179680E+09 | 0.09 | 853.06 | 03-FEB-12:30 | 0.58 |
March | 86024191.35 | 0.04 | 1092.75 | 03-MAR-13:30 | 0.58 |
April | 0.139583E+09 | 0.07 | 1181.74 | 08-APR-12:30 | 0.57 |
May | 0.224880E+09 | 0.14 | 938.41 | 30-MAY-16:40 | 0.57 |
June | 0.611200E+09 | 0.32 | 1107.88 | 26-JUN-16:20 | 0.57 |
July | 0.123687E+10 | 0.48 | 1866.63 | 22-JUL-16:05 | 0.57 |
August | 0.145170E+10 | 0.50 | 1797.15 | 31-AUG-16:20 | 0.57 |
September | 0.103617E+10 | 0.35 | 3348.59 | 30-SEP-12:30 | 0.57 |
October | 0.125137E+10 | 0.31 | 2318.29 | 30-OCT-13:00 | 0.58 |
November | 0.277952E+09 | 0.09 | 2244.59 | 04-NOV-13:00 | 0.57 |
December | 0.313295E+09 | 0.12 | 1814.75 | 17-DEC-13:00 | 0.58 |
Annual Sum or Average | 0.731224E+10 | 0.23 | |||
Minimum of Months | 86024191.35 | 0.04 | 853.06 | 0.57 | |
Maximum of Months | 0.145170E+10 | 0.50 | 3348.59 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157637E+10 | 0.41 | 3828.11 | 01-JAN-09:02 | 0.58 |
February | 0.150627E+10 | 0.41 | 3828.11 | 01-FEB-09:02 | 0.58 |
March | 0.845388E+09 | 0.41 | 3828.11 | 01-MAR-16:02 | 0.58 |
April | 0.839523E+09 | 0.41 | 3828.11 | 01-APR-15:02 | 0.58 |
May | 0.150321E+10 | 0.41 | 3828.11 | 01-MAY-08:62 | 0.58 |
June | 0.225683E+10 | 0.41 | 3828.11 | 01-JUN-08:62 | 0.57 |
July | 0.305137E+10 | 0.41 | 3828.11 | 01-JUL-08:62 | 0.57 |
August | 0.272900E+10 | 0.41 | 3828.11 | 01-AUG-08:61 | 0.57 |
September | 0.164214E+10 | 0.41 | 3828.11 | 01-SEP-08:61 | 0.57 |
October | 0.920840E+09 | 0.41 | 3828.11 | 01-OCT-08:63 | 0.57 |
November | 0.833773E+09 | 0.41 | 3828.11 | 02-NOV-18:02 | 0.58 |
December | 0.128269E+10 | 0.41 | 3828.11 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.189874E+11 | 0.41 | |||
Minimum of Months | 0.833773E+09 | 0.41 | 3828.11 | 0.57 | |
Maximum of Months | 0.305137E+10 | 0.41 | 3828.11 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345853E+09 | 0.44 | 655.99 | 01-JAN-09:02 | 0.58 |
February | 0.288873E+09 | 0.44 | 655.99 | 01-FEB-16:02 | 0.58 |
March | 0.213277E+09 | 0.42 | 655.99 | 01-MAR-09:02 | 0.58 |
April | 0.185648E+09 | 0.44 | 655.99 | 01-APR-08:62 | 0.58 |
May | 0.215614E+09 | 0.47 | 655.99 | 01-MAY-08:62 | 0.57 |
June | 0.289639E+09 | 0.50 | 655.99 | 01-JUN-08:62 | 0.57 |
July | 0.389983E+09 | 0.53 | 655.99 | 01-JUL-08:62 | 0.57 |
August | 0.424166E+09 | 0.54 | 655.99 | 01-AUG-08:61 | 0.57 |
September | 0.255165E+09 | 0.50 | 655.99 | 01-SEP-08:61 | 0.57 |
October | 0.196446E+09 | 0.48 | 655.99 | 02-OCT-08:62 | 0.57 |
November | 0.203712E+09 | 0.41 | 655.99 | 01-NOV-15:02 | 0.58 |
December | 0.289824E+09 | 0.44 | 655.99 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.329820E+10 | 0.47 | |||
Minimum of Months | 0.185648E+09 | 0.41 | 655.99 | 0.57 | |
Maximum of Months | 0.424166E+09 | 0.54 | 655.99 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.409038E+09 | 0.48 | 650.63 | 01-JAN-09:02 | 0.58 |
February | 0.357376E+09 | 0.47 | 650.63 | 01-FEB-09:02 | 0.58 |
March | 0.230408E+09 | 0.42 | 650.63 | 01-MAR-09:02 | 0.58 |
April | 0.174419E+09 | 0.42 | 650.63 | 01-APR-08:62 | 0.58 |
May | 0.202679E+09 | 0.45 | 650.63 | 01-MAY-08:62 | 0.57 |
June | 0.280279E+09 | 0.49 | 650.63 | 01-JUN-08:62 | 0.57 |
July | 0.375960E+09 | 0.53 | 650.63 | 01-JUL-08:62 | 0.57 |
August | 0.384817E+09 | 0.54 | 650.63 | 01-AUG-08:61 | 0.57 |
September | 0.203569E+09 | 0.46 | 650.63 | 01-SEP-08:61 | 0.57 |
October | 0.137968E+09 | 0.41 | 650.63 | 02-OCT-08:62 | 0.57 |
November | 0.225685E+09 | 0.42 | 650.63 | 04-NOV-08:62 | 0.57 |
December | 0.336010E+09 | 0.46 | 650.63 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.331821E+10 | 0.46 | |||
Minimum of Months | 0.137968E+09 | 0.41 | 650.63 | 0.57 | |
Maximum of Months | 0.409038E+09 | 0.54 | 650.63 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117672E+09 | 0.47 | 191.17 | 01-JAN-09:02 | 0.58 |
February | 99582665.19 | 0.46 | 191.17 | 01-FEB-09:02 | 0.58 |
March | 69853723.07 | 0.43 | 191.17 | 01-MAR-09:02 | 0.58 |
April | 59370412.60 | 0.44 | 191.17 | 01-APR-08:62 | 0.58 |
May | 62778841.90 | 0.46 | 191.17 | 01-MAY-15:02 | 0.58 |
June | 96888308.63 | 0.51 | 191.17 | 01-JUN-08:62 | 0.57 |
July | 0.121750E+09 | 0.53 | 191.17 | 01-JUL-08:62 | 0.57 |
August | 0.129040E+09 | 0.53 | 191.17 | 01-AUG-08:61 | 0.57 |
September | 75540517.94 | 0.49 | 191.17 | 01-SEP-08:61 | 0.57 |
October | 60233197.63 | 0.47 | 191.17 | 02-OCT-15:02 | 0.57 |
November | 67157182.08 | 0.43 | 191.17 | 01-NOV-08:62 | 0.57 |
December | 95405455.55 | 0.46 | 191.17 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.105527E+10 | 0.48 | |||
Minimum of Months | 59370412.60 | 0.43 | 191.17 | 0.57 | |
Maximum of Months | 0.129040E+09 | 0.53 | 191.17 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136658E+09 | 0.52 | 187.88 | 01-JAN-09:02 | 0.58 |
February | 0.120874E+09 | 0.50 | 187.88 | 01-FEB-09:02 | 0.58 |
March | 73034436.34 | 0.43 | 187.88 | 01-MAR-09:02 | 0.58 |
April | 56007894.81 | 0.43 | 187.88 | 01-APR-08:62 | 0.58 |
May | 59749235.07 | 0.45 | 187.88 | 01-MAY-15:02 | 0.58 |
June | 94615997.52 | 0.51 | 187.88 | 01-JUN-08:62 | 0.57 |
July | 0.118496E+09 | 0.53 | 187.88 | 01-JUL-08:62 | 0.57 |
August | 0.119138E+09 | 0.53 | 187.88 | 01-AUG-08:61 | 0.57 |
September | 62094494.80 | 0.46 | 187.88 | 01-SEP-08:61 | 0.57 |
October | 46099595.76 | 0.42 | 187.88 | 02-OCT-15:02 | 0.57 |
November | 77635400.51 | 0.45 | 187.88 | 01-NOV-08:62 | 0.57 |
December | 0.111161E+09 | 0.50 | 187.88 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.107556E+10 | 0.48 | |||
Minimum of Months | 46099595.76 | 0.42 | 187.88 | 0.57 | |
Maximum of Months | 0.136658E+09 | 0.53 | 187.88 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.373455E+09 | 0.45 | 749.14 | 01-JAN-16:02 | 0.58 |
February | 0.307173E+09 | 0.47 | 749.14 | 01-FEB-16:02 | 0.58 |
March | 0.273077E+09 | 0.46 | 749.14 | 01-MAR-16:02 | 0.58 |
April | 0.233154E+09 | 0.45 | 749.14 | 01-APR-08:62 | 0.58 |
May | 0.258136E+09 | 0.46 | 749.14 | 01-MAY-15:02 | 0.58 |
June | 0.423233E+09 | 0.49 | 749.14 | 01-JUN-08:62 | 0.57 |
July | 0.601993E+09 | 0.52 | 749.14 | 01-JUL-08:62 | 0.57 |
August | 0.645057E+09 | 0.53 | 749.14 | 01-AUG-08:61 | 0.57 |
September | 0.474456E+09 | 0.50 | 749.14 | 01-SEP-08:61 | 0.57 |
October | 0.471774E+09 | 0.51 | 749.14 | 02-OCT-15:02 | 0.57 |
November | 0.265365E+09 | 0.45 | 749.14 | 01-NOV-15:02 | 0.58 |
December | 0.340699E+09 | 0.46 | 749.14 | 01-DEC-19:02 | 0.58 |
Annual Sum or Average | 0.466757E+10 | 0.48 | |||
Minimum of Months | 0.233154E+09 | 0.45 | 749.14 | 0.57 | |
Maximum of Months | 0.645057E+09 | 0.53 | 749.14 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.223493E+10 | 0.201144E+10 | 1861.45 | 02-JAN-07:05 | 1675.31 | 1675.31 | 50.45 | 4.39 |
February | 0.192361E+10 | 0.173125E+10 | 1895.92 | 06-FEB-07:05 | 1706.33 | 1706.33 | 50.41 | 4.66 |
March | 0.109826E+10 | 0.988433E+09 | 1503.77 | 25-MAR-18:02 | 1353.39 | 1353.39 | 46.78 | 2.73 |
April | 0.653724E+09 | 0.588352E+09 | 1474.13 | 15-APR-15:02 | 1326.72 | 1326.72 | 50.20 | 2.64 |
May | 0.221597E+09 | 0.199437E+09 | 1312.66 | 01-MAY-06:16 | 1181.39 | 1181.39 | 50.98 | 2.18 |
June | 0.116774E+09 | 0.105097E+09 | 896.07 | 06-JUN-15:05 | 806.46 | 806.46 | 38.81 | 1.30 |
July | 0.102710E+09 | 92439175.18 | 529.52 | 05-JUL-08:06 | 476.57 | 476.57 | 45.74 | 0.70 |
August | 87690595.46 | 78921535.92 | 676.03 | 21-AUG-08:05 | 608.43 | 608.43 | 48.03 | 0.93 |
September | 0.116131E+09 | 0.104517E+09 | 1167.17 | 24-SEP-05:30 | 1050.46 | 1050.46 | 49.06 | 1.84 |
October | 0.354004E+09 | 0.318603E+09 | 1453.35 | 18-OCT-22:20 | 1308.02 | 1308.02 | 47.32 | 2.58 |
November | 0.111407E+10 | 0.100267E+10 | 1641.81 | 16-NOV-16:02 | 1477.63 | 1477.63 | 46.73 | 3.23 |
December | 0.167724E+10 | 0.150952E+10 | 1680.94 | 31-DEC-24:00 | 1512.84 | 1512.84 | 50.09 | 3.39 |
Annual Sum or Average | 0.970074E+10 | 0.873067E+10 | ||||||
Minimum of Months | 87690595.46 | 78921535.92 | 529.52 | 476.57 | 476.57 | 38.81 | 0.70 | |
Maximum of Months | 0.223493E+10 | 0.201144E+10 | 1895.92 | 1706.33 | 1706.33 | 50.98 | 4.66 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 982866.37 | 884579.73 | 28.08 | 19-JAN-19:04 | 25.27 | 25.27 | 8.39 | 2.31 |
February | 1683125.39 | 1514812.85 | 45.48 | 20-FEB-09:02 | 40.93 | 40.93 | 8.39 | 3.07 |
March | 14333273.75 | 12899946.38 | 464.21 | 27-MAR-15:02 | 417.79 | 417.79 | 7.79 | 10.10 |
April | 0.103856E+09 | 93470093.84 | 864.25 | 16-APR-15:02 | 777.83 | 777.83 | 7.48 | 13.39 |
May | 0.350239E+09 | 0.315216E+09 | 1418.14 | 31-MAY-18:03 | 1276.33 | 1276.33 | 7.49 | 16.62 |
June | 0.178410E+10 | 0.160569E+10 | 2917.04 | 24-JUN-18:03 | 2625.34 | 2625.34 | 7.32 | 22.52 |
July | 0.280639E+10 | 0.252575E+10 | 2600.49 | 14-JUL-18:03 | 2340.44 | 2340.44 | 7.32 | 21.48 |
August | 0.227501E+10 | 0.204751E+10 | 2429.73 | 03-AUG-20:00 | 2186.76 | 2186.76 | 6.81 | 20.88 |
September | 0.122472E+10 | 0.110225E+10 | 2331.49 | 22-SEP-18:03 | 2098.34 | 2098.34 | 7.42 | 20.52 |
October | 0.432309E+09 | 0.389078E+09 | 1692.80 | 24-OCT-15:02 | 1523.52 | 1523.52 | 7.48 | 17.93 |
November | 18505975.02 | 16655377.52 | 356.09 | 04-NOV-15:01 | 320.48 | 320.48 | 8.14 | 8.92 |
December | 3456396.47 | 3110756.83 | 38.22 | 18-DEC-10:50 | 34.40 | 34.40 | 8.39 | 2.77 |
Annual Sum or Average | 0.901558E+10 | 0.811402E+10 | ||||||
Minimum of Months | 982866.37 | 884579.73 | 28.08 | 25.27 | 25.27 | 6.81 | 2.31 | |
Maximum of Months | 0.280639E+10 | 0.252575E+10 | 2917.04 | 2625.34 | 2625.34 | 8.39 | 22.52 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 47.65 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.60 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.28 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.98 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 50.87 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.12 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.79 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.56 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.13 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:03 | 14.37 | 14.37 | 51.37 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.78 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.11 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.65 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.56 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.248176E+10 | 0.223359E+10 | 2729.04 | 01-JAN-09:03 | 2456.14 | 2456.14 | 8.41 | 34.18 |
February | 0.253351E+10 | 0.228016E+10 | 2729.04 | 01-FEB-00:03 | 2456.14 | 2456.14 | 8.39 | 34.18 |
March | 0.425033E+10 | 0.382530E+10 | 2729.04 | 01-MAR-00:03 | 2456.14 | 2456.14 | 8.39 | 34.18 |
April | 0.535228E+10 | 0.481705E+10 | 2729.04 | 01-APR-01:10 | 2456.14 | 2456.14 | 8.39 | 34.18 |
May | 0.719594E+10 | 0.647634E+10 | 2729.04 | 01-MAY-00:03 | 2456.14 | 2456.14 | 8.43 | 34.18 |
June | 0.707368E+10 | 0.636631E+10 | 2729.04 | 01-JUN-00:10 | 2456.14 | 2456.14 | 9.46 | 34.18 |
July | 0.730947E+10 | 0.657852E+10 | 2729.04 | 01-JUL-00:10 | 2456.14 | 2456.14 | 10.30 | 34.18 |
August | 0.730947E+10 | 0.657852E+10 | 2729.04 | 01-AUG-00:10 | 2456.14 | 2456.14 | 9.79 | 34.18 |
September | 0.706576E+10 | 0.635919E+10 | 2729.04 | 01-SEP-00:10 | 2456.14 | 2456.14 | 9.59 | 34.18 |
October | 0.682304E+10 | 0.614074E+10 | 2729.04 | 01-OCT-00:03 | 2456.14 | 2456.14 | 8.46 | 34.18 |
November | 0.428967E+10 | 0.386070E+10 | 2729.04 | 01-NOV-00:05 | 2456.14 | 2456.14 | 8.40 | 34.18 |
December | 0.339725E+10 | 0.305752E+10 | 2729.04 | 01-DEC-00:03 | 2456.14 | 2456.14 | 8.39 | 34.18 |
Annual Sum or Average | 0.650822E+11 | 0.585739E+11 | ||||||
Minimum of Months | 0.248176E+10 | 0.223359E+10 | 2729.04 | 2456.14 | 2456.14 | 8.39 | 34.18 | |
Maximum of Months | 0.730947E+10 | 0.657852E+10 | 2729.04 | 2456.14 | 2456.14 | 10.30 | 34.18 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47.65 | 59.92 | 28214.11 | 66601.35 | 18-JAN-07:22 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.60 | 59.12 | 28531.24 | 57925.99 | 10-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.28 | 58.63 | 27915.59 | 65572.97 | 28-MAR-06:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.98 | 58.15 | 26449.53 | 61441.00 | 05-APR-06:36 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 50.87 | 58.22 | 24636.64 | 60267.49 | 02-MAY-06:22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.12 | 58.36 | 22766.18 | 48252.68 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.79 | 58.69 | 21360.66 | 45030.00 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.56 | 59.34 | 21039.00 | 44052.23 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.13 | 58.91 | 21850.62 | 46829.95 | 20-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 51.37 | 58.19 | 23398.61 | 53739.30 | 09-OCT-08:21 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.78 | 58.44 | 25257.74 | 60477.33 | 05-NOV-07:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.11 | 59.41 | 27030.64 | 61642.63 | 25-DEC-08:38 |
Annual Sum or Average | 0.00 | 24849.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.65 | 58.15 | 21039.00 | 44052.23 | ||
Maximum of Months | 0.00 | 0.00 | 53.56 | 59.92 | 28531.24 | 66601.35 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 50.29 | 60.00 | 46010.74 | 192431.98 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.73 | 59.06 | 45508.58 | 191502.21 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.06 | 57.97 | 17446.50 | 128445.57 | 22-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.23 | 58.01 | 11994.79 | 118615.37 | 02-APR-18:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 50.30 | 57.22 | 5326.74 | 95690.75 | 03-MAY-15:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 45.06 | 57.22 | 3057.32 | 100402.60 | 06-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.03 | 57.22 | 2317.94 | 33655.07 | 05-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 40.44 | 57.22 | 1937.81 | 40106.52 | 08-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40.99 | 57.22 | 2925.42 | 87503.11 | 26-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 44.25 | 44.25 | 6592.10 | 113513.90 | 10-OCT-05:33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.52 | 57.22 | 18925.54 | 145322.76 | 16-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.78 | 57.89 | 27031.07 | 140337.08 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 15583.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.44 | 44.25 | 1937.81 | 33655.07 | ||
Maximum of Months | 0.00 | 0.00 | 52.52 | 60.00 | 46010.74 | 192431.98 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1420.56 | 29336.16 | 19-JAN-19:04 | 8.57 | 8.37 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1927.43 | 38284.58 | 20-FEB-09:02 | 8.64 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 6703.63 | 293345.40 | 27-MAR-15:02 | 9.78 | 7.73 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 30912.48 | 347508.59 | 07-APR-15:03 | 9.29 | 6.87 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95783.32 | 510311.69 | 31-MAY-18:03 | 11.04 | 7.48 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 317673.91 | 766306.07 | 24-JUN-18:03 | 12.66 | 7.30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 441477.20 | 729390.83 | 14-JUL-18:03 | 12.40 | 7.30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 373603.90 | 720387.39 | 03-AUG-20:00 | 11.82 | 6.79 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 233635.40 | 700434.73 | 22-SEP-18:03 | 12.33 | 7.43 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 100717.54 | 526728.47 | 24-OCT-15:02 | 11.15 | 7.47 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 8770.88 | 164811.94 | 04-NOV-15:01 | 9.26 | 8.11 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2917.93 | 48225.33 | 12-DEC-19:05 | 8.71 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 135575.60 | 0.00 | ||||||
Minimum of Months | 1420.56 | 29336.16 | 8.57 | 6.79 | 0.00 | 0.00 | ||
Maximum of Months | 441477.20 | 766306.07 | 12.66 | 8.37 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.19 | 42.60 |
Annual Sum or Average | 0.19 | 42.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.19 | 42.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.12 | 3.40 |
April | 0.28 | 6.56 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.75 | 8.54 |
November | 0.00 | 0.00 |
December | 0.25 | 4.09 |
Annual Sum or Average | 1.40 | 6.92 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.75 | 8.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 6.27 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.25 | 11.29 |
November | 0.00 | 0.00 |
December | 0.19 | 5.02 |
Annual Sum or Average | 0.53 | 8.18 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 11.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 5.06 | 3.99 |
February | 0.27 | 1.74 |
March | 12.34 | 4.51 |
April | 17.58 | 5.27 |
May | 9.16 | 6.65 |
June | 0.03 | 1.68 |
July | 0.00 | 0.00 |
August | 0.42 | 2.18 |
September | 2.69 | 6.59 |
October | 17.88 | 5.57 |
November | 19.49 | 4.87 |
December | 4.98 | 3.96 |
Annual Sum or Average | 89.89 | 5.15 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 19.49 | 6.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.81 | 82.93 |
February | 0.00 | 0.00 |
March | 1.12 | 87.07 |
April | 1.61 | 98.23 |
May | 1.51 | 67.49 |
June | 1.42 | 56.92 |
July | 1.67 | 56.92 |
August | 1.75 | 54.21 |
September | 1.69 | 83.51 |
October | 1.97 | 110.03 |
November | 1.39 | 93.15 |
December | 0.54 | 60.93 |
Annual Sum or Average | 15.49 | 78.55 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.97 | 110.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 211.22 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 211.22 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.25 | 380.19 |
November | 0.12 | 267.54 |
December | 0.19 | 168.97 |
Annual Sum or Average | 0.79 | 263.10 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 380.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.44 | 0.68 |
February | 3.06 | 0.71 |
March | 0.90 | 0.77 |
April | 1.17 | 0.75 |
May | 1.74 | 0.77 |
June | 2.24 | 0.61 |
July | 3.90 | 0.56 |
August | 3.67 | 0.44 |
September | 2.58 | 0.57 |
October | 1.60 | 0.63 |
November | 0.58 | 0.71 |
December | 1.08 | 0.75 |
Annual Sum or Average | 25.96 | 0.63 |
Minimum of Months | 0.58 | 0.44 |
Maximum of Months | 3.90 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.24 | 0.59 |
February | 3.40 | 0.65 |
March | 0.82 | 0.68 |
April | 1.21 | 0.77 |
May | 1.50 | 0.80 |
June | 2.21 | 0.63 |
July | 3.82 | 0.56 |
August | 2.62 | 0.50 |
September | 1.21 | 0.76 |
October | 0.56 | 0.81 |
November | 0.81 | 0.60 |
December | 2.06 | 0.59 |
Annual Sum or Average | 24.44 | 0.63 |
Minimum of Months | 0.56 | 0.50 |
Maximum of Months | 4.24 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 0.25 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.08 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.24 | 0.70 |
February | 1.32 | 0.67 |
March | 0.00 | 0.00 |
April | 0.08 | 0.81 |
May | 0.00 | 0.00 |
June | 1.08 | 0.85 |
July | 2.60 | 0.86 |
August | 1.90 | 0.88 |
September | 0.39 | 0.90 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.06 | 0.45 |
Annual Sum or Average | 8.67 | 0.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.60 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.74 | 0.69 |
February | 1.65 | 0.79 |
March | 0.28 | 0.48 |
April | 1.35 | 0.40 |
May | 2.76 | 0.51 |
June | 3.86 | 0.60 |
July | 5.14 | 0.66 |
August | 4.21 | 0.65 |
September | 3.15 | 0.53 |
October | 2.39 | 0.39 |
November | 0.31 | 0.65 |
December | 0.92 | 0.79 |
Annual Sum or Average | 28.75 | 0.60 |
Minimum of Months | 0.28 | 0.39 |
Maximum of Months | 5.14 | 0.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.15 | 0.59 |
February | 2.83 | 0.64 |
March | 0.75 | 0.66 |
April | 1.17 | 0.49 |
May | 2.54 | 0.48 |
June | 3.90 | 0.59 |
July | 5.47 | 0.65 |
August | 5.89 | 0.60 |
September | 2.74 | 0.52 |
October | 0.22 | 0.30 |
November | 0.38 | 0.75 |
December | 1.15 | 0.77 |
Annual Sum or Average | 31.19 | 0.59 |
Minimum of Months | 0.22 | 0.30 |
Maximum of Months | 5.89 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.19 | 0.63 |
February | 2.65 | 0.69 |
March | 1.03 | 0.70 |
April | 1.01 | 0.68 |
May | 2.11 | 0.62 |
June | 2.64 | 0.54 |
July | 4.62 | 0.52 |
August | 4.35 | 0.43 |
September | 2.57 | 0.52 |
October | 2.29 | 0.67 |
November | 0.78 | 0.68 |
December | 1.13 | 0.75 |
Annual Sum or Average | 28.37 | 0.58 |
Minimum of Months | 0.78 | 0.43 |
Maximum of Months | 4.62 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.92 | 0.54 |
February | 1.74 | 0.63 |
March | 1.74 | 0.68 |
April | 1.40 | 0.75 |
May | 2.28 | 0.64 |
June | 2.72 | 0.55 |
July | 4.79 | 0.51 |
August | 3.69 | 0.45 |
September | 1.62 | 0.66 |
October | 0.75 | 0.81 |
November | 1.34 | 0.59 |
December | 2.53 | 0.59 |
Annual Sum or Average | 27.52 | 0.58 |
Minimum of Months | 0.75 | 0.45 |
Maximum of Months | 4.79 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.79 | 0.60 |
February | 0.83 | 0.61 |
March | 0.78 | 0.54 |
April | 0.64 | 0.43 |
May | 1.36 | 0.53 |
June | 3.25 | 0.61 |
July | 5.40 | 0.59 |
August | 4.82 | 0.49 |
September | 2.76 | 0.58 |
October | 2.59 | 0.64 |
November | 0.88 | 0.44 |
December | 0.96 | 0.55 |
Annual Sum or Average | 26.07 | 0.57 |
Minimum of Months | 0.64 | 0.43 |
Maximum of Months | 5.40 | 0.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.74 | 120.70 |
February | 0.00 | 0.00 |
March | 2.06 | 159.45 |
April | 1.74 | 152.37 |
May | 1.00 | 124.95 |
June | 0.92 | 99.96 |
July | 0.75 | 99.96 |
August | 0.75 | 88.85 |
September | 0.92 | 99.96 |
October | 0.61 | 94.28 |
November | 1.24 | 110.91 |
December | 0.60 | 108.06 |
Annual Sum or Average | 11.32 | 122.99 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.06 | 159.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 113.11 |
February | 0.00 | 0.00 |
March | 1.77 | 150.76 |
April | 1.42 | 186.47 |
May | 0.71 | 154.35 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.25 | 66.64 |
September | 0.33 | 99.96 |
October | 0.57 | 144.57 |
November | 1.60 | 134.82 |
December | 0.43 | 115.98 |
Annual Sum or Average | 7.35 | 145.48 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.77 | 186.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.73 | 9.53 |
February | 0.37 | 5.83 |
March | 13.18 | 11.59 |
April | 20.22 | 12.45 |
May | 9.58 | 14.53 |
June | 0.33 | 15.57 |
July | 0.00 | 0.00 |
August | 0.38 | 11.12 |
September | 1.58 | 18.77 |
October | 18.37 | 13.62 |
November | 20.47 | 11.46 |
December | 3.43 | 10.78 |
Annual Sum or Average | 92.65 | 12.43 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 20.47 | 18.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 0.08 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.654828E+11 | 0.00 | 0.212584E+09 | 0.377369E+11 | 0.00 | 0.00 |
February | 0.618375E+11 | 0.00 | 0.201468E+09 | 0.340362E+11 | 0.00 | 0.00 |
March | 0.271695E+11 | 0.00 | 0.612803E+10 | 0.388898E+11 | 0.00 | 0.00 |
April | 0.244907E+11 | 0.00 | 0.470231E+11 | 0.376871E+11 | 0.00 | 0.00 |
May | 0.136664E+11 | 0.00 | 0.176419E+12 | 0.375621E+11 | 0.00 | 0.00 |
June | 0.800167E+10 | 0.00 | 0.617531E+12 | 0.345859E+11 | 0.00 | 0.00 |
July | 0.627918E+10 | 0.00 | 0.881567E+12 | 0.355732E+11 | 0.00 | 0.00 |
August | 0.523949E+10 | 0.00 | 0.731925E+12 | 0.358133E+11 | 0.00 | 0.00 |
September | 0.746891E+10 | 0.00 | 0.444639E+12 | 0.346807E+11 | 0.00 | 0.00 |
October | 0.153860E+11 | 0.00 | 0.180079E+12 | 0.381620E+11 | 0.00 | 0.00 |
November | 0.296633E+11 | 0.00 | 0.707298E+10 | 0.383059E+11 | 0.00 | 0.00 |
December | 0.327632E+11 | 0.00 | 0.390687E+09 | 0.383773E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.297448E+12 | 0.00 | 0.309319E+13 | 0.441410E+12 | 0.00 | 0.00 |
Minimum of Months | 0.523949E+10 | 0.00 | 0.201468E+09 | 0.340362E+11 | 0.00 | 0.00 |
Maximum of Months | 0.654828E+11 | 0.00 | 0.881567E+12 | 0.388898E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.461578E+10 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
February | 0.464180E+10 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
March | 0.517017E+09 | 0.00 | 0.689508E+09 | 0.587767E+10 | 0.00 | 0.00 |
April | 12238.37 | 0.00 | 0.632347E+10 | 0.568807E+10 | 0.00 | 0.00 |
May | 45926.17 | 0.00 | 0.231938E+11 | 0.587767E+10 | 0.00 | 0.00 |
June | 32464.01 | 0.00 | 0.970001E+11 | 0.568807E+10 | 0.00 | 0.00 |
July | 16941.73 | 0.00 | 0.135406E+12 | 0.587767E+10 | 0.00 | 0.00 |
August | 16468.03 | 0.00 | 0.109874E+12 | 0.587767E+10 | 0.00 | 0.00 |
September | 32266.82 | 0.00 | 0.668118E+11 | 0.568807E+10 | 0.00 | 0.00 |
October | 71080.03 | 0.00 | 0.243756E+11 | 0.587767E+10 | 0.00 | 0.00 |
November | 0.356845E+09 | 0.00 | 0.604778E+09 | 0.568807E+10 | 0.00 | 0.00 |
December | 0.807206E+09 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109389E+11 | 0.00 | 0.464280E+12 | 0.692049E+11 | 0.00 | 0.00 |
Minimum of Months | 12238.37 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.464180E+10 | 0.00 | 0.135406E+12 | 0.587767E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.377369E+11 | 0.212584E+09 | 0.654828E+11 | 0.564959E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340362E+11 | 0.201468E+09 | 0.618375E+11 | 0.557212E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388898E+11 | 0.612803E+10 | 0.271695E+11 | 0.394068E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376871E+11 | 0.470231E+11 | 0.244907E+11 | 0.167390E+12 | 0.381183E+09 | 0.00 | 0.00 | 0.00 |
May | 0.375621E+11 | 0.176419E+12 | 0.136664E+11 | 0.228825E+11 | 0.551600E+10 | 0.00 | 0.00 | 0.00 |
June | 0.345859E+11 | 0.617531E+12 | 0.800167E+10 | 0.204004E+09 | 0.921405E+11 | 0.00 | 0.00 | 0.00 |
July | 0.355732E+11 | 0.881567E+12 | 0.627918E+10 | 0.00 | 0.295535E+12 | 0.00 | 0.00 | 0.00 |
August | 0.358133E+11 | 0.731925E+12 | 0.523949E+10 | 1989824.90 | 0.220509E+12 | 0.00 | 0.00 | 0.00 |
September | 0.346807E+11 | 0.444639E+12 | 0.746891E+10 | 0.368319E+10 | 0.452290E+11 | 0.00 | 0.00 | 0.00 |
October | 0.381620E+11 | 0.180079E+12 | 0.153860E+11 | 0.790719E+11 | 0.297455E+10 | 0.00 | 0.00 | 0.00 |
November | 0.383059E+11 | 0.707298E+10 | 0.296633E+11 | 0.295439E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383773E+11 | 0.390687E+09 | 0.327632E+11 | 0.499231E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441410E+12 | 0.309319E+13 | 0.297448E+12 | 0.258414E+13 | 0.662285E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.340362E+11 | 0.201468E+09 | 0.523949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388898E+11 | 0.881567E+12 | 0.654828E+11 | 0.564959E+12 | 0.295535E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587767E+10 | 0.00 | 0.461578E+10 | 0.978137E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.00 | 0.464180E+10 | 0.959960E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.689508E+09 | 0.517017E+09 | 0.700688E+11 | 455101.44 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.632347E+10 | 12238.37 | 0.340268E+11 | 0.157233E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.231938E+11 | 45926.17 | 0.725618E+10 | 0.125180E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.970001E+11 | 32464.01 | 0.137978E+09 | 0.179549E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.135406E+12 | 16941.73 | 36802.26 | 0.612173E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.109874E+12 | 16468.03 | 82002201.09 | 0.476811E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.668118E+11 | 32266.82 | 0.146162E+10 | 0.109441E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.243756E+11 | 71080.03 | 0.178185E+11 | 0.663379E+09 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.604778E+09 | 0.356845E+09 | 0.557428E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.00 | 0.807206E+09 | 0.867705E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.464280E+12 | 0.109389E+11 | 0.467175E+12 | 0.139870E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530887E+10 | 0.00 | 12238.37 | 36802.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.135406E+12 | 0.464180E+10 | 0.978137E+11 | 0.612173E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.377369E+11 | 0.654828E+11 | 0.212584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340362E+11 | 0.618375E+11 | 0.201468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388898E+11 | 0.271695E+11 | 0.612803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376871E+11 | 0.244907E+11 | 0.470231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375621E+11 | 0.136664E+11 | 0.176419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.345859E+11 | 0.800167E+10 | 0.617531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.355732E+11 | 0.627918E+10 | 0.881567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358133E+11 | 0.523949E+10 | 0.731925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346807E+11 | 0.746891E+10 | 0.444639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.381620E+11 | 0.153860E+11 | 0.180079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383059E+11 | 0.296633E+11 | 0.707298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383773E+11 | 0.327632E+11 | 0.390687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441410E+12 | 0.297448E+12 | 0.309319E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.340362E+11 | 0.523949E+10 | 0.201468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388898E+11 | 0.654828E+11 | 0.881567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.587767E+10 | 0.461578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.464180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.517017E+09 | 0.689508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 12238.37 | 0.632347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 45926.17 | 0.231938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 32464.01 | 0.970001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 16941.73 | 0.135406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 16468.03 | 0.109874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 32266.82 | 0.668118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 71080.03 | 0.243756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.356845E+09 | 0.604778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.807206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.109389E+11 | 0.464280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530887E+10 | 12238.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.464180E+10 | 0.135406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412726E+11 | 0.00 | 0.00 | 6090185.81 | 0.00 | 0.00 | 0.922290E+10 | 0.00 | 0.99 |
February | 0.450742E+11 | 0.00 | 0.00 | 469081.94 | 0.00 | 0.00 | 0.106292E+10 | 0.00 | 0.99 |
March | 0.484312E+11 | 0.00 | 0.00 | 0.00 | 8526328.70 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 0.444789E+11 | 0.00 | 0.00 | 0.00 | 52878943.46 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 0.352084E+11 | 0.00 | 0.00 | 0.00 | 0.785123E+09 | 0.00 | 0.00 | 0.00 | 1.04 |
June | 0.686201E+10 | 0.00 | 0.00 | 0.00 | 0.188788E+11 | 0.00 | 0.00 | 0.00 | 1.03 |
July | 0.220968E+09 | 0.00 | 0.00 | 0.00 | 0.372628E+11 | 0.00 | 0.00 | 0.00 | 1.02 |
August | 0.361767E+10 | 0.00 | 0.00 | 0.00 | 0.236129E+11 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 0.164280E+11 | 0.00 | 0.00 | 119601.90 | 0.101157E+11 | 0.00 | 0.485760E+09 | 0.00 | 1.04 |
October | 0.155545E+11 | 70115450.78 | 0.00 | 28686493.07 | 0.167618E+10 | 0.00 | 0.228759E+11 | 0.00 | 1.04 |
November | 0.638270E+10 | 0.00 | 0.00 | 64206458.34 | 0.00 | 0.00 | 0.452763E+11 | 0.00 | 1.05 |
December | 0.159466E+11 | 0.00 | 0.00 | 30440268.10 | 0.00 | 0.00 | 0.339946E+11 | 0.00 | 1.02 |
Annual Sum or Average | 0.279478E+12 | 70115450.78 | 0.00 | 0.130012E+09 | 0.923930E+11 | 0.00 | 0.112918E+12 | 0.00 | 1.02 |
Minimum of Months | 0.220968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
Maximum of Months | 0.484312E+11 | 70115450.78 | 0.00 | 64206458.34 | 0.372628E+11 | 0.00 | 0.452763E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278619E+10 | 0.00 | 0.00 | 253872.35 | 0.00 | 0.354641E+10 | 0.171384E+09 | 0.00 | 2.30 |
February | 0.289870E+10 | 0.00 | 0.00 | 211239.27 | 0.00 | 0.282474E+10 | 0.210921E+09 | 0.00 | 2.31 |
March | 0.481953E+10 | 0.00 | 0.00 | 481187.39 | 1096025.49 | 0.111307E+10 | 0.320768E+09 | 0.00 | 2.29 |
April | 0.533473E+10 | 2191296.09 | 0.00 | 46385.32 | 4616549.45 | 0.348926E+09 | 33879995.95 | 0.00 | 2.33 |
May | 0.452573E+10 | 0.00 | 0.00 | 0.00 | 0.100924E+09 | 176913.21 | 0.00 | 0.00 | 2.42 |
June | 0.882005E+09 | 66629182.74 | 0.00 | 467.31 | 0.236016E+10 | 0.00 | 78445.13 | 0.00 | 2.41 |
July | 28071398.16 | 0.582103E+09 | 0.00 | 2187.21 | 0.420788E+10 | 0.00 | 330957.26 | 0.00 | 2.38 |
August | 0.453513E+09 | 0.119875E+10 | 0.00 | 61369.73 | 0.183736E+10 | 0.00 | 11465816.56 | 0.00 | 2.39 |
September | 0.207803E+10 | 0.235845E+09 | 0.00 | 484916.47 | 0.107065E+10 | 0.00 | 0.101705E+09 | 0.00 | 2.44 |
October | 0.420294E+10 | 0.158240E+09 | 0.00 | 1565276.25 | 84935778.62 | 0.00 | 0.684215E+09 | 0.00 | 2.44 |
November | 0.515023E+10 | 0.00 | 0.00 | 514295.83 | 0.00 | 0.766614E+09 | 0.331405E+09 | 0.00 | 2.31 |
December | 0.359153E+10 | 0.00 | 0.00 | 546868.66 | 0.00 | 0.237765E+10 | 0.323772E+09 | 0.00 | 2.32 |
Annual Sum or Average | 0.367512E+11 | 0.224376E+10 | 0.00 | 4168065.79 | 0.966762E+10 | 0.109776E+11 | 0.218993E+10 | 0.00 | 2.36 |
Minimum of Months | 28071398.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 |
Maximum of Months | 0.533473E+10 | 0.119875E+10 | 0.00 | 1565276.25 | 0.420788E+10 | 0.354641E+10 | 0.684215E+09 | 0.00 | 2.44 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.480228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
February | 0.438844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
March | 0.454881E+10 | 0.00 | 0.00 | 9056.27 | 810992.56 | 0.00 | 57778089.64 | 0.00 | 1.46 |
April | 0.412946E+10 | 0.00 | 0.00 | 29996.58 | 5029647.70 | 0.00 | 0.102154E+09 | 0.00 | 1.49 |
May | 0.324451E+10 | 1052517.94 | 0.00 | 22255.17 | 73625451.16 | 0.00 | 0.104363E+09 | 0.00 | 1.55 |
June | 0.632748E+09 | 45007702.77 | 0.00 | 22150.17 | 0.175067E+10 | 0.00 | 19918437.42 | 0.00 | 1.54 |
July | 20771136.47 | 0.247091E+09 | 0.00 | 1298.34 | 0.329721E+10 | 0.00 | 245208.42 | 0.00 | 1.52 |
August | 0.316706E+09 | 0.310931E+09 | 0.00 | 62314.49 | 0.193504E+10 | 0.00 | 27330363.74 | 0.00 | 1.53 |
September | 0.152115E+10 | 55270599.17 | 0.00 | 42659.81 | 0.906900E+09 | 0.00 | 87599990.19 | 0.00 | 1.55 |
October | 0.319214E+10 | 3832941.02 | 0.00 | 217819.41 | 0.162268E+09 | 0.00 | 0.373311E+09 | 0.00 | 1.52 |
November | 0.449690E+10 | 0.00 | 0.00 | 42216.31 | 0.00 | 0.00 | 0.108498E+09 | 0.00 | 1.47 |
December | 0.462322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
Annual Sum or Average | 0.359171E+11 | 0.663186E+09 | 0.00 | 449766.55 | 0.813156E+10 | 0.00 | 0.881198E+09 | 0.00 | 1.51 |
Minimum of Months | 20771136.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Maximum of Months | 0.480228E+10 | 0.310931E+09 | 0.00 | 217819.41 | 0.329721E+10 | 0.00 | 0.373311E+09 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535046E+09 | 0.00 | 0.00 | 0.65 |
February | 0.349842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616373E+09 | 0.00 | 0.00 | 0.65 |
March | 0.431935E+10 | 0.00 | 0.00 | 0.00 | 760422.59 | 0.00 | 0.00 | 0.00 | 0.65 |
April | 0.396686E+10 | 0.00 | 0.00 | 0.00 | 4716020.79 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 0.314007E+10 | 0.00 | 0.00 | 0.00 | 70021376.36 | 0.00 | 0.00 | 0.00 | 0.68 |
June | 0.611990E+09 | 0.00 | 0.00 | 0.00 | 0.168371E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 19707074.58 | 0.00 | 0.00 | 0.00 | 0.332329E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.322642E+09 | 0.00 | 0.00 | 0.00 | 0.210593E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.150847E+10 | 0.00 | 0.00 | 0.00 | 0.902174E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.334265E+10 | 0.00 | 0.00 | 0.00 | 0.155743E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
November | 0.431510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3158465.43 | 0.00 | 0.00 | 0.65 |
December | 0.433159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3347501.29 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.333446E+11 | 0.00 | 0.00 | 0.00 | 0.824634E+10 | 0.115792E+10 | 0.00 | 0.00 | 0.67 |
Minimum of Months | 19707074.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.433159E+10 | 0.00 | 0.00 | 0.00 | 0.332329E+10 | 0.616373E+09 | 0.00 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.993572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112525E+10 | 0.00 | 0.00 | 0.53 |
February | 0.850324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108591E+10 | 0.00 | 0.00 | 0.53 |
March | 0.182858E+10 | 0.00 | 0.00 | 0.00 | 357819.90 | 0.203908E+09 | 0.00 | 0.00 | 0.53 |
April | 0.186662E+10 | 0.00 | 0.00 | 0.00 | 2219142.46 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.147757E+10 | 0.00 | 0.00 | 0.00 | 32948838.95 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.287974E+09 | 0.00 | 0.00 | 0.00 | 0.792275E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 9273242.84 | 0.00 | 0.00 | 0.00 | 0.156379E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.151821E+09 | 0.00 | 0.00 | 0.00 | 0.990952E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.709817E+09 | 0.00 | 0.00 | 0.00 | 0.424522E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.157290E+10 | 0.00 | 0.00 | 0.00 | 73285662.85 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.186878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163196E+09 | 0.00 | 0.00 | 0.53 |
December | 0.161432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425503E+09 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.132315E+11 | 0.00 | 0.00 | 0.00 | 0.388035E+10 | 0.300377E+10 | 0.00 | 0.00 | 0.54 |
Minimum of Months | 9273242.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.186878E+10 | 0.00 | 0.00 | 0.00 | 0.156379E+10 | 0.112525E+10 | 0.00 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.966561E+09 | 0.00 | 0.00 | 92274399.37 | 0.00 | 0.00 | 0.748946E+11 | 0.00 | 22.88 |
February | 0.781154E+09 | 0.00 | 0.00 | 79142788.92 | 0.00 | 0.00 | 0.684080E+11 | 0.00 | 23.01 |
March | 0.640788E+09 | 11508300.22 | 0.00 | 99921708.01 | 0.00 | 0.00 | 0.726782E+11 | 0.00 | 22.88 |
April | 0.821205E+09 | 69950442.97 | 0.00 | 0.106175E+09 | 1422216.78 | 0.00 | 0.664099E+11 | 0.00 | 23.19 |
May | 0.100599E+10 | 0.105792E+10 | 0.00 | 82799351.65 | 31830752.28 | 0.00 | 0.509958E+11 | 0.00 | 23.58 |
June | 64067563.12 | 0.261770E+11 | 0.00 | 24194773.22 | 0.445337E+09 | 0.00 | 0.980734E+10 | 0.00 | 22.89 |
July | 7814798.29 | 0.514677E+11 | 0.00 | 1001807.46 | 0.100100E+10 | 0.00 | 0.290702E+09 | 0.00 | 22.37 |
August | 43368384.06 | 0.326429E+11 | 0.00 | 14850912.49 | 0.809394E+09 | 0.00 | 0.493272E+10 | 0.00 | 22.58 |
September | 0.552428E+09 | 0.140084E+11 | 0.00 | 47372353.08 | 0.265611E+09 | 0.00 | 0.237726E+11 | 0.00 | 23.10 |
October | 0.112079E+10 | 0.231122E+10 | 0.00 | 90149669.53 | 0.102996E+09 | 0.00 | 0.544806E+11 | 0.00 | 23.30 |
November | 0.819321E+09 | 0.00 | 0.00 | 0.108208E+09 | 0.00 | 0.00 | 0.723754E+11 | 0.00 | 22.96 |
December | 0.576575E+09 | 0.00 | 0.00 | 95376671.98 | 0.00 | 0.00 | 0.726090E+11 | 0.00 | 22.97 |
Annual Sum or Average | 0.740005E+10 | 0.127747E+12 | 0.00 | 0.841468E+09 | 0.265760E+10 | 0.00 | 0.571655E+12 | 0.00 | 22.97 |
Minimum of Months | 7814798.29 | 0.00 | 0.00 | 1001807.46 | 0.00 | 0.00 | 0.290702E+09 | 0.00 | 22.37 |
Maximum of Months | 0.112079E+10 | 0.514677E+11 | 0.00 | 0.108208E+09 | 0.100100E+10 | 0.00 | 0.748946E+11 | 0.00 | 23.58 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241416E+11 | 0.00 | 0.00 | 2126960.30 | 0.00 | 0.505157E+09 | 0.295369E+10 | 0.00 | 3.47 |
February | 0.216780E+11 | 0.00 | 0.00 | 2287593.11 | 0.00 | 46126376.13 | 0.348614E+10 | 0.00 | 3.50 |
March | 0.180050E+11 | 3053886.26 | 0.00 | 5751892.55 | 1596888.28 | 0.00 | 0.854281E+10 | 0.00 | 3.47 |
April | 0.154539E+11 | 19605107.21 | 0.00 | 4357587.61 | 9238261.72 | 0.00 | 0.881660E+10 | 0.00 | 3.53 |
May | 0.980529E+10 | 92287363.74 | 0.00 | 5180570.81 | 0.335966E+09 | 0.00 | 0.939447E+10 | 0.00 | 3.66 |
June | 0.114205E+10 | 0.495731E+10 | 0.00 | 2894138.93 | 0.534054E+10 | 0.00 | 0.259801E+10 | 0.00 | 3.65 |
July | 23884111.43 | 0.130191E+11 | 0.00 | 256523.48 | 0.730666E+10 | 0.00 | 96388609.57 | 0.00 | 3.60 |
August | 0.352930E+09 | 0.985978E+10 | 0.00 | 3580715.90 | 0.302957E+10 | 0.00 | 0.161711E+10 | 0.00 | 3.62 |
September | 0.321934E+10 | 0.338061E+10 | 0.00 | 8679425.72 | 0.213724E+10 | 0.00 | 0.601948E+10 | 0.00 | 3.68 |
October | 0.572390E+10 | 0.795665E+09 | 0.00 | 20830281.15 | 0.185390E+09 | 0.00 | 0.150555E+11 | 0.00 | 3.67 |
November | 0.176627E+11 | 0.00 | 0.00 | 6941073.23 | 0.00 | 0.00 | 0.887140E+10 | 0.00 | 3.50 |
December | 0.216875E+11 | 0.00 | 0.00 | 4214626.67 | 0.00 | 5450287.79 | 0.505382E+10 | 0.00 | 3.52 |
Annual Sum or Average | 0.138896E+12 | 0.321274E+11 | 0.00 | 67101389.46 | 0.183462E+11 | 0.556734E+09 | 0.725055E+11 | 0.00 | 3.57 |
Minimum of Months | 23884111.43 | 0.00 | 0.00 | 256523.48 | 0.00 | 0.00 | 96388609.57 | 0.00 | 3.47 |
Maximum of Months | 0.241416E+11 | 0.130191E+11 | 0.00 | 20830281.15 | 0.730666E+10 | 0.505157E+09 | 0.150555E+11 | 0.00 | 3.68 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905129E+11 | 0.00 | 0.00 | 1386906.29 | 0.00 | 0.00 | 0.451369E+10 | 0.00 | 1.73 |
February | 0.824189E+11 | 0.00 | 0.00 | 1121844.72 | 0.00 | 0.00 | 0.441880E+10 | 0.00 | 1.74 |
March | 0.745813E+11 | 0.00 | 0.00 | 8371833.92 | 16048001.23 | 0.00 | 0.166177E+11 | 0.00 | 1.72 |
April | 0.618842E+11 | 0.00 | 0.00 | 11699914.44 | 99527168.14 | 0.00 | 0.219073E+11 | 0.00 | 1.76 |
May | 0.467404E+11 | 57232055.73 | 0.00 | 9284864.39 | 0.142050E+10 | 0.00 | 0.195255E+11 | 0.00 | 1.82 |
June | 0.766021E+10 | 0.731773E+10 | 0.00 | 3419188.26 | 0.282153E+11 | 0.00 | 0.525184E+10 | 0.00 | 1.82 |
July | 0.112761E+09 | 0.200627E+11 | 0.00 | 364227.11 | 0.500723E+11 | 0.00 | 0.302774E+09 | 0.00 | 1.79 |
August | 0.252457E+10 | 0.149808E+11 | 0.00 | 5261188.24 | 0.294641E+11 | 0.00 | 0.427923E+10 | 0.00 | 1.80 |
September | 0.202911E+11 | 0.575993E+10 | 0.00 | 8809941.86 | 0.132796E+11 | 0.00 | 0.115455E+11 | 0.00 | 1.83 |
October | 0.365557E+11 | 0.303011E+09 | 0.00 | 30943770.56 | 0.298381E+10 | 0.00 | 0.342171E+11 | 0.00 | 1.80 |
November | 0.696320E+11 | 0.00 | 0.00 | 12797999.52 | 0.00 | 0.00 | 0.216091E+11 | 0.00 | 1.74 |
December | 0.816147E+11 | 0.00 | 0.00 | 3347243.97 | 0.00 | 0.00 | 0.987403E+10 | 0.00 | 1.74 |
Annual Sum or Average | 0.574529E+12 | 0.484814E+11 | 0.00 | 96808923.29 | 0.125551E+12 | 0.00 | 0.154062E+12 | 0.00 | 1.77 |
Minimum of Months | 0.112761E+09 | 0.00 | 0.00 | 364227.11 | 0.00 | 0.00 | 0.302774E+09 | 0.00 | 1.72 |
Maximum of Months | 0.905129E+11 | 0.200627E+11 | 0.00 | 30943770.56 | 0.500723E+11 | 0.00 | 0.342171E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345591E+09 | 0.00 | 0.00 | 309584.82 | 0.00 | 0.121062E+10 | 35525950.85 | 0.00 | 0.47 |
February | 0.355979E+09 | 0.00 | 0.00 | 557890.31 | 0.00 | 0.110032E+10 | 56935775.61 | 0.00 | 0.47 |
March | 0.409274E+09 | 2227.27 | 0.00 | 2848148.04 | 130870.78 | 0.884097E+09 | 0.321980E+09 | 0.00 | 0.47 |
April | 0.344777E+09 | 1417818.55 | 0.00 | 5329375.99 | 1607915.47 | 0.530457E+09 | 0.596352E+09 | 0.00 | 0.47 |
May | 0.231457E+09 | 23883229.81 | 16275.60 | 8300659.43 | 6788778.58 | 82463623.42 | 0.899795E+09 | 1889.09 | 0.47 |
June | 18479507.48 | 0.636588E+09 | 702551.73 | 3351730.50 | 82700733.91 | 224395.95 | 0.193405E+09 | 21320.78 | 0.48 |
July | 117948.25 | 0.124753E+10 | 833385.68 | 91788.86 | 87710325.65 | 451.57 | 2113300.02 | 34417.29 | 0.48 |
August | 5624787.26 | 0.883255E+09 | 511932.58 | 1851273.76 | 57368251.86 | 61204.99 | 77051423.07 | 22809.99 | 0.48 |
September | 79381173.66 | 0.322998E+09 | 527133.47 | 5051544.45 | 52785258.96 | 10881956.55 | 0.459682E+09 | 21021.67 | 0.47 |
October | 0.223083E+09 | 64065772.75 | 59251.20 | 7044213.57 | 7098830.73 | 0.187454E+09 | 0.854771E+09 | 5792.34 | 0.47 |
November | 0.425684E+09 | 0.00 | 0.00 | 1310155.82 | 0.00 | 0.894714E+09 | 0.287908E+09 | 0.00 | 0.47 |
December | 0.380715E+09 | 0.00 | 0.00 | 391097.36 | 0.00 | 0.111870E+10 | 61991786.25 | 0.00 | 0.47 |
Annual Sum or Average | 0.282016E+10 | 0.317974E+10 | 2650530.26 | 36437462.93 | 0.296191E+09 | 0.602000E+10 | 0.384751E+10 | 107251.17 | 0.47 |
Minimum of Months | 117948.25 | 0.00 | 0.00 | 91788.86 | 0.00 | 451.57 | 2113300.02 | 0.00 | 0.47 |
Maximum of Months | 0.425684E+09 | 0.124753E+10 | 833385.68 | 8300659.43 | 87710325.65 | 0.121062E+10 | 0.899795E+09 | 34417.29 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280978E+09 | 0.00 | 0.00 | 54892.99 | 0.00 | 0.130387E+10 | 7146669.61 | 0.00 | 0.47 |
February | 0.273797E+09 | 0.00 | 0.00 | 137422.50 | 0.00 | 0.121550E+10 | 24359551.59 | 0.00 | 0.47 |
March | 0.437556E+09 | 2227.27 | 0.00 | 1509910.42 | 130870.78 | 0.996090E+09 | 0.183043E+09 | 0.00 | 0.47 |
April | 0.365889E+09 | 1053347.07 | 0.00 | 4199841.70 | 1972386.95 | 0.587532E+09 | 0.519295E+09 | 0.00 | 0.47 |
May | 0.242054E+09 | 23839549.67 | 16155.74 | 7813400.07 | 6832458.72 | 92442502.26 | 0.879707E+09 | 2008.96 | 0.47 |
June | 18992534.54 | 0.630635E+09 | 702156.04 | 3271075.72 | 88652989.78 | 250865.94 | 0.192946E+09 | 21716.48 | 0.48 |
July | 117948.25 | 0.124304E+10 | 761547.61 | 91323.09 | 92269697.23 | 451.57 | 2113765.78 | 33529.06 | 0.48 |
August | 6222950.01 | 0.874629E+09 | 519330.56 | 1627157.52 | 65986246.59 | 11318.81 | 76727262.74 | 23505.10 | 0.48 |
September | 98910279.48 | 0.311476E+09 | 663222.41 | 3755881.12 | 64171272.84 | 11494716.33 | 0.440836E+09 | 20835.24 | 0.47 |
October | 0.299664E+09 | 44022562.55 | 65108.11 | 3984817.53 | 27137600.51 | 0.332888E+09 | 0.635816E+09 | 4375.85 | 0.47 |
November | 0.433648E+09 | 0.00 | 0.00 | 360271.12 | 0.00 | 0.105148E+10 | 0.124126E+09 | 0.00 | 0.47 |
December | 0.336365E+09 | 0.00 | 0.00 | 29266.50 | 0.00 | 0.122212E+10 | 3282191.82 | 0.00 | 0.47 |
Annual Sum or Average | 0.279419E+10 | 0.312870E+10 | 2727520.46 | 26835260.27 | 0.347154E+09 | 0.681368E+10 | 0.308940E+10 | 105970.68 | 0.47 |
Minimum of Months | 117948.25 | 0.00 | 0.00 | 29266.50 | 0.00 | 451.57 | 2113765.78 | 0.00 | 0.47 |
Maximum of Months | 0.437556E+09 | 0.124304E+10 | 761547.61 | 7813400.07 | 92269697.23 | 0.130387E+10 | 0.879707E+09 | 33529.06 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155731E+11 | 0.00 | 0.00 | 1112817.59 | 0.00 | 0.561952E+10 | 0.390600E+09 | 0.00 | 0.53 |
February | 0.177520E+11 | 0.00 | 0.00 | 2851866.33 | 0.00 | 0.184926E+10 | 0.919365E+09 | 0.00 | 0.53 |
March | 0.199478E+11 | 965136.56 | 0.00 | 6364762.18 | 839352.43 | 0.192562E+09 | 0.179216E+10 | 0.00 | 0.53 |
April | 0.177674E+11 | 41021666.74 | 0.00 | 10180349.83 | 0.00 | 0.00 | 0.224588E+10 | 0.00 | 0.54 |
May | 0.123253E+11 | 0.379273E+09 | 0.00 | 17035569.49 | 36811513.92 | 0.00 | 0.422525E+10 | 0.00 | 0.54 |
June | 0.178656E+10 | 0.843891E+10 | 0.00 | 9736882.15 | 0.132273E+10 | 0.00 | 0.112483E+10 | 0.00 | 0.54 |
July | 0.00 | 0.176477E+11 | 0.00 | 672002.78 | 0.466711E+09 | 0.00 | 30828908.61 | 0.00 | 0.54 |
August | 0.286921E+09 | 0.127122E+11 | 0.00 | 12438669.97 | 47625220.38 | 0.00 | 0.847459E+09 | 0.00 | 0.54 |
September | 0.340409E+10 | 0.485919E+10 | 0.00 | 34611178.34 | 0.242956E+09 | 0.00 | 0.408572E+10 | 0.00 | 0.54 |
October | 0.690694E+10 | 0.936179E+09 | 0.00 | 71221546.01 | 29523318.48 | 0.00 | 0.102719E+11 | 0.00 | 0.54 |
November | 0.171991E+11 | 0.00 | 0.00 | 22991098.54 | 0.00 | 14289512.90 | 0.458615E+10 | 0.00 | 0.54 |
December | 0.169656E+11 | 0.00 | 0.00 | 11169389.25 | 0.00 | 0.225000E+10 | 0.194744E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.129915E+12 | 0.450155E+11 | 0.00 | 0.200386E+09 | 0.214719E+10 | 0.992564E+10 | 0.324676E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 672002.78 | 0.00 | 0.00 | 30828908.61 | 0.00 | 0.53 |
Maximum of Months | 0.199478E+11 | 0.176477E+11 | 0.00 | 71221546.01 | 0.132273E+10 | 0.561952E+10 | 0.102719E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.581081E+10 | 0.00 | 0.00 | 4455712.60 | 0.00 | 0.122896E+11 | 0.347939E+10 | 0.00 | 0.53 |
February | 0.567406E+10 | 0.00 | 0.00 | 2599307.00 | 0.00 | 0.122028E+11 | 0.264396E+10 | 0.00 | 0.53 |
March | 0.614011E+10 | 30196.36 | 0.00 | 21034067.91 | 1774292.63 | 0.434594E+10 | 0.114318E+11 | 0.00 | 0.53 |
April | 0.525102E+10 | 9317288.81 | 0.00 | 54332398.32 | 31704377.93 | 0.224353E+09 | 0.144937E+11 | 0.00 | 0.54 |
May | 0.379625E+10 | 0.214429E+09 | 248769.53 | 84770161.35 | 0.201403E+09 | 36355496.99 | 0.126502E+11 | 3815.88 | 0.54 |
June | 0.357874E+09 | 0.709092E+10 | 2019458.31 | 29585718.11 | 0.266864E+10 | 936696.45 | 0.253273E+10 | 51420.38 | 0.54 |
July | 1599094.26 | 0.141052E+11 | 2135658.27 | 1060325.94 | 0.400709E+10 | 0.00 | 28841491.19 | 37011.07 | 0.54 |
August | 0.101391E+09 | 0.974586E+10 | 3535208.24 | 15153667.55 | 0.301041E+10 | 162904.99 | 0.103011E+10 | 39804.38 | 0.54 |
September | 0.146554E+10 | 0.362063E+10 | 1230723.87 | 42596516.00 | 0.148027E+10 | 11157916.42 | 0.600513E+10 | 14872.01 | 0.54 |
October | 0.428966E+10 | 0.436590E+09 | 2269350.03 | 53320157.11 | 0.526820E+09 | 99605787.85 | 0.128074E+11 | 22407.74 | 0.54 |
November | 0.611443E+10 | 0.00 | 0.00 | 26062785.39 | 0.00 | 0.399389E+10 | 0.116881E+11 | 0.00 | 0.54 |
December | 0.592782E+10 | 0.00 | 0.00 | 4992063.93 | 0.00 | 0.105167E+11 | 0.472475E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.449306E+11 | 0.352229E+11 | 11439168.25 | 0.339963E+09 | 0.119281E+11 | 0.437215E+11 | 0.835162E+11 | 169331.46 | 0.54 |
Minimum of Months | 1599094.26 | 0.00 | 0.00 | 1060325.94 | 0.00 | 0.00 | 28841491.19 | 0.00 | 0.53 |
Maximum of Months | 0.614011E+10 | 0.141052E+11 | 3535208.24 | 84770161.35 | 0.400709E+10 | 0.122896E+11 | 0.144937E+11 | 51420.38 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353645E+09 | 0.00 | 0.00 | 295006.04 | 0.00 | 0.119379E+10 | 44313668.84 | 0.00 | 0.47 |
February | 0.366978E+09 | 0.00 | 0.00 | 496073.58 | 0.00 | 0.107276E+10 | 73558008.84 | 0.00 | 0.47 |
March | 0.415624E+09 | 2227.27 | 0.00 | 2413951.76 | 130870.78 | 0.888147E+09 | 0.312015E+09 | 0.00 | 0.47 |
April | 0.324624E+09 | 2231223.83 | 0.00 | 5568875.95 | 794510.18 | 0.504487E+09 | 0.642236E+09 | 0.00 | 0.47 |
May | 0.178244E+09 | 25114470.39 | 18072.01 | 9018246.16 | 5557072.14 | 0.101935E+09 | 0.932819E+09 | 558.54 | 0.47 |
June | 10732032.07 | 0.637652E+09 | 354246.97 | 3789664.30 | 81995316.82 | 183255.14 | 0.200755E+09 | 10402.93 | 0.48 |
July | 2493.58 | 0.126667E+10 | 206715.90 | 144200.57 | 69230381.27 | 0.00 | 2176794.54 | 3233.54 | 0.48 |
August | 1634420.73 | 0.898047E+09 | 66142.47 | 2210420.36 | 43042478.07 | 0.00 | 80743847.99 | 2852.55 | 0.48 |
September | 63249628.36 | 0.327335E+09 | 383450.44 | 5809374.25 | 48601967.93 | 9719568.98 | 0.476218E+09 | 10893.39 | 0.47 |
October | 0.201761E+09 | 65750560.67 | 64660.90 | 7159717.37 | 5409602.39 | 0.207758E+09 | 0.855673E+09 | 4823.06 | 0.47 |
November | 0.427689E+09 | 0.00 | 0.00 | 1905591.98 | 0.00 | 0.851640E+09 | 0.328382E+09 | 0.00 | 0.47 |
December | 0.386861E+09 | 0.00 | 0.00 | 586519.15 | 0.00 | 0.108786E+10 | 86491729.08 | 0.00 | 0.47 |
Annual Sum or Average | 0.273104E+10 | 0.322280E+10 | 1093288.70 | 39397641.48 | 0.254762E+09 | 0.591829E+10 | 0.403538E+10 | 32764.01 | 0.47 |
Minimum of Months | 2493.58 | 0.00 | 0.00 | 144200.57 | 0.00 | 0.00 | 2176794.54 | 0.00 | 0.47 |
Maximum of Months | 0.427689E+09 | 0.126667E+10 | 383450.44 | 9018246.16 | 81995316.82 | 0.119379E+10 | 0.932819E+09 | 10893.39 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.270715E+09 | 0.00 | 0.00 | 42286.96 | 0.00 | 0.130978E+10 | 11505903.41 | 0.00 | 0.47 |
February | 0.281274E+09 | 0.00 | 0.00 | 122301.09 | 0.00 | 0.120852E+10 | 23882725.17 | 0.00 | 0.47 |
March | 0.437800E+09 | 2227.27 | 0.00 | 1221837.03 | 130870.78 | 0.996495E+09 | 0.182683E+09 | 0.00 | 0.47 |
April | 0.369478E+09 | 1353870.17 | 0.00 | 4333142.67 | 1671189.17 | 0.566996E+09 | 0.536109E+09 | 674.67 | 0.47 |
May | 0.210113E+09 | 24917338.02 | 18229.30 | 8442203.71 | 5754204.50 | 0.114777E+09 | 0.888684E+09 | 401.25 | 0.47 |
June | 11068083.21 | 0.631494E+09 | 483073.48 | 3683128.15 | 88024443.27 | 173518.33 | 0.200536E+09 | 11189.69 | 0.48 |
July | 2493.58 | 0.126365E+10 | 328926.70 | 142999.89 | 72128142.37 | 0.00 | 2177995.23 | 3624.58 | 0.48 |
August | 1954618.54 | 0.891568E+09 | 75982.62 | 1985125.18 | 49511295.73 | 0.00 | 80648945.36 | 3277.46 | 0.48 |
September | 86334684.72 | 0.321106E+09 | 592447.26 | 4408679.95 | 54617747.57 | 13315875.69 | 0.450938E+09 | 15490.01 | 0.47 |
October | 0.313337E+09 | 43585285.54 | 210687.60 | 3751043.62 | 27424698.71 | 0.343007E+09 | 0.612257E+09 | 8975.17 | 0.47 |
November | 0.428686E+09 | 0.00 | 0.00 | 647894.76 | 0.00 | 0.100171E+10 | 0.178569E+09 | 0.00 | 0.47 |
December | 0.335999E+09 | 0.00 | 0.00 | 74673.04 | 0.00 | 0.120742E+10 | 18310572.42 | 0.00 | 0.47 |
Annual Sum or Average | 0.274676E+10 | 0.317767E+10 | 1709346.96 | 28855316.06 | 0.299263E+09 | 0.676219E+10 | 0.318630E+10 | 43632.82 | 0.47 |
Minimum of Months | 2493.58 | 0.00 | 0.00 | 42286.96 | 0.00 | 0.00 | 2177995.23 | 0.00 | 0.47 |
Maximum of Months | 0.437800E+09 | 0.126365E+10 | 592447.26 | 8442203.71 | 88024443.27 | 0.130978E+10 | 0.888684E+09 | 15490.01 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.776658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170304E+11 | 0.00 | 0.00 | 0.49 |
February | 0.890099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137591E+11 | 0.00 | 0.00 | 0.49 |
March | 0.179640E+11 | 0.00 | 0.00 | 0.00 | 4187627.05 | 0.582256E+10 | 0.00 | 0.00 | 0.49 |
April | 0.198827E+11 | 0.00 | 0.00 | 0.00 | 25971001.34 | 0.196266E+10 | 0.00 | 0.00 | 0.50 |
May | 0.172865E+11 | 0.00 | 0.00 | 0.00 | 0.385606E+09 | 5742818.60 | 0.00 | 0.00 | 0.52 |
June | 0.337021E+10 | 0.00 | 0.00 | 0.00 | 0.927213E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.108526E+09 | 0.00 | 0.00 | 0.00 | 0.183013E+11 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.177678E+10 | 0.00 | 0.00 | 0.00 | 0.115973E+11 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.830711E+10 | 0.00 | 0.00 | 0.00 | 0.496825E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.184079E+11 | 0.00 | 0.00 | 0.00 | 0.857675E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.178029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597762E+10 | 0.00 | 0.00 | 0.49 |
December | 0.103873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134851E+11 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.131962E+12 | 0.00 | 0.00 | 0.00 | 0.454124E+11 | 0.580431E+11 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.108526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.198827E+11 | 0.00 | 0.00 | 0.00 | 0.183013E+11 | 0.170304E+11 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71276080.19 | 0.00 | 0.00 | 71825.56 | 0.00 | 0.320384E+09 | 6279043.88 | 0.00 | 0.47 |
February | 76904195.83 | 0.00 | 0.00 | 134701.00 | 0.00 | 0.290485E+09 | 10925073.32 | 0.00 | 0.47 |
March | 95823835.67 | 1922.07 | 0.00 | 740311.96 | 31352.44 | 0.241643E+09 | 66342437.83 | 0.00 | 0.47 |
April | 81410124.14 | 422539.33 | 0.00 | 1442723.45 | 333894.17 | 0.151599E+09 | 0.134777E+09 | 0.00 | 0.47 |
May | 50004938.50 | 6121733.17 | 8591.18 | 2313507.26 | 1541611.29 | 37264324.40 | 0.215921E+09 | 607.63 | 0.47 |
June | 3859569.17 | 0.164756E+09 | 80069.77 | 941585.59 | 15164371.61 | 56098.99 | 49007807.98 | 2467.82 | 0.48 |
July | 20930.07 | 0.316105E+09 | 161302.05 | 23514.53 | 17754638.05 | 112.89 | 536314.68 | 5702.47 | 0.48 |
August | 1391867.52 | 0.223404E+09 | 60826.21 | 500897.90 | 11820546.65 | 4436.42 | 19249970.44 | 4202.48 | 0.47 |
September | 18076104.27 | 82319691.90 | 89666.70 | 1392114.65 | 11670093.56 | 4513574.61 | 0.114767E+09 | 3365.74 | 0.47 |
October | 55039973.34 | 16379988.27 | 7153.49 | 1749816.19 | 1419828.15 | 71296000.88 | 0.190002E+09 | 441.85 | 0.47 |
November | 0.102581E+09 | 0.00 | 0.00 | 284083.44 | 0.00 | 0.244156E+09 | 55381881.52 | 0.00 | 0.47 |
December | 83392319.53 | 0.00 | 0.00 | 82178.54 | 0.00 | 0.297491E+09 | 9484645.16 | 0.00 | 0.47 |
Annual Sum or Average | 0.639781E+09 | 0.809512E+09 | 407609.40 | 9677260.07 | 59736335.92 | 0.165889E+10 | 0.872675E+09 | 16787.99 | 0.47 |
Minimum of Months | 20930.07 | 0.00 | 0.00 | 23514.53 | 0.00 | 112.89 | 536314.68 | 0.00 | 0.47 |
Maximum of Months | 0.102581E+09 | 0.316105E+09 | 161302.05 | 2313507.26 | 17754638.05 | 0.320384E+09 | 0.215921E+09 | 5702.47 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44761664.70 | 0.00 | 0.00 | 8013.91 | 0.00 | 0.351951E+09 | 1290513.31 | 0.00 | 0.47 |
February | 53689186.98 | 0.00 | 0.00 | 19844.43 | 0.00 | 0.319491E+09 | 5249154.37 | 0.00 | 0.47 |
March | 0.102382E+09 | 556.82 | 0.00 | 372115.64 | 32717.70 | 0.265675E+09 | 36120598.18 | 0.00 | 0.47 |
April | 88290447.26 | 346907.53 | 0.00 | 1122106.91 | 409525.97 | 0.163826E+09 | 0.115991E+09 | 0.00 | 0.47 |
May | 55080596.34 | 6114317.19 | 8593.90 | 2175653.31 | 1549027.27 | 40357101.45 | 0.207891E+09 | 604.92 | 0.47 |
June | 3967682.75 | 0.164327E+09 | 79978.82 | 921251.42 | 15593203.78 | 59352.46 | 48916775.10 | 2558.77 | 0.48 |
July | 20930.07 | 0.315660E+09 | 155798.60 | 23332.70 | 18205790.82 | 112.89 | 536496.52 | 5425.41 | 0.48 |
August | 1427535.11 | 0.222629E+09 | 61074.28 | 444146.19 | 12596079.63 | 2829.70 | 19272661.27 | 3954.41 | 0.48 |
September | 23148524.55 | 80779962.40 | 99218.77 | 1030955.70 | 13199508.69 | 7177884.01 | 0.107392E+09 | 4128.05 | 0.47 |
October | 74921141.65 | 12262624.55 | 15703.77 | 955408.52 | 5527416.21 | 0.110336E+09 | 0.131875E+09 | 1667.21 | 0.47 |
November | 94292573.23 | 0.00 | 0.00 | 77945.78 | 0.00 | 0.290660E+09 | 17372903.59 | 0.00 | 0.47 |
December | 61254551.06 | 0.00 | 0.00 | 6531.81 | 0.00 | 0.328609E+09 | 579469.84 | 0.00 | 0.47 |
Annual Sum or Average | 0.603237E+09 | 0.802120E+09 | 420368.15 | 7157306.31 | 67113270.08 | 0.187815E+10 | 0.692487E+09 | 18338.76 | 0.47 |
Minimum of Months | 20930.07 | 0.00 | 0.00 | 6531.81 | 0.00 | 112.89 | 536496.52 | 0.00 | 0.47 |
Maximum of Months | 0.102382E+09 | 0.315660E+09 | 155798.60 | 2175653.31 | 18205790.82 | 0.351951E+09 | 0.207891E+09 | 5425.41 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492446E+09 | 0.00 | 0.00 | 3869557.57 | 0.00 | 0.161853E+10 | 0.441188E+09 | 0.00 | 0.53 |
February | 0.421537E+09 | 0.00 | 0.00 | 4696224.27 | 0.00 | 0.134705E+10 | 0.657129E+09 | 0.00 | 0.54 |
March | 0.482704E+09 | 213689.49 | 0.00 | 8022365.89 | 0.00 | 0.103484E+10 | 0.107246E+10 | 0.00 | 0.53 |
April | 0.475341E+09 | 3635835.63 | 0.00 | 9039733.68 | 1221993.32 | 0.579382E+09 | 0.130743E+10 | 0.00 | 0.54 |
May | 0.325734E+09 | 37869732.31 | 58294.92 | 11854356.92 | 11343446.04 | 46620085.64 | 0.157774E+10 | 1731.43 | 0.54 |
June | 30697700.91 | 0.103087E+10 | 314213.29 | 4472983.87 | 0.124790E+09 | 168203.24 | 0.310583E+09 | 11552.24 | 0.54 |
July | 189366.43 | 0.201251E+10 | 733107.31 | 142717.52 | 0.131879E+09 | 724.99 | 3397562.14 | 7107.56 | 0.54 |
August | 8839815.44 | 0.142407E+10 | 450947.12 | 2949862.79 | 86501226.14 | 82886.38 | 0.123935E+09 | 8831.05 | 0.54 |
September | 0.107613E+09 | 0.529100E+09 | 386836.69 | 10584051.05 | 74711957.52 | 1494121.62 | 0.771359E+09 | 3061.16 | 0.54 |
October | 0.230585E+09 | 0.108348E+09 | 46723.81 | 19712267.41 | 5963566.90 | 92808921.82 | 0.169966E+10 | 1564.32 | 0.54 |
November | 0.502866E+09 | 0.00 | 0.00 | 8773990.09 | 0.00 | 0.903933E+09 | 0.116867E+10 | 0.00 | 0.54 |
December | 0.468841E+09 | 0.00 | 0.00 | 6220832.03 | 0.00 | 0.135334E+10 | 0.679070E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.354739E+10 | 0.514662E+10 | 1990123.14 | 90338943.10 | 0.436411E+09 | 0.697825E+10 | 0.981263E+10 | 33847.75 | 0.54 |
Minimum of Months | 189366.43 | 0.00 | 0.00 | 142717.52 | 0.00 | 724.99 | 3397562.14 | 0.00 | 0.53 |
Maximum of Months | 0.502866E+09 | 0.201251E+10 | 733107.31 | 19712267.41 | 0.131879E+09 | 0.161853E+10 | 0.169966E+10 | 11552.24 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114150E+11 | 0.00 | 0.00 | 37203660.09 | 0.00 | 0.00 | 0.341324E+11 | 0.00 | 4.26 |
February | 0.938652E+10 | 0.00 | 0.00 | 32216377.44 | 0.00 | 0.00 | 0.320117E+11 | 0.00 | 4.26 |
March | 0.446008E+10 | 7455336.39 | 0.00 | 53465163.65 | 0.00 | 0.00 | 0.408458E+11 | 0.00 | 4.37 |
April | 0.210395E+10 | 43388023.81 | 0.00 | 66721631.14 | 2848794.59 | 0.00 | 0.405335E+11 | 0.00 | 4.54 |
May | 0.640760E+09 | 0.650994E+09 | 0.00 | 64569035.72 | 39712908.30 | 0.00 | 0.331334E+11 | 0.00 | 4.66 |
June | 69320874.19 | 0.162956E+11 | 0.00 | 22106270.31 | 0.622744E+09 | 0.00 | 0.634173E+10 | 0.00 | 4.50 |
July | 2845093.51 | 0.328563E+11 | 0.00 | 1067358.75 | 0.841523E+09 | 0.00 | 0.194928E+09 | 0.00 | 4.43 |
August | 35758003.21 | 0.207562E+11 | 0.00 | 14926764.30 | 0.708527E+09 | 0.00 | 0.326720E+10 | 0.00 | 4.47 |
September | 0.475785E+09 | 0.831639E+10 | 0.00 | 36683688.27 | 0.683537E+09 | 0.00 | 0.151814E+11 | 0.00 | 4.51 |
October | 0.165802E+10 | 0.131999E+10 | 0.00 | 60123970.43 | 0.211281E+09 | 0.00 | 0.338982E+11 | 0.00 | 4.54 |
November | 0.558041E+10 | 0.00 | 0.00 | 55286066.27 | 0.00 | 0.00 | 0.397375E+11 | 0.00 | 4.40 |
December | 0.851582E+10 | 0.00 | 0.00 | 41739209.37 | 0.00 | 0.00 | 0.355779E+11 | 0.00 | 4.30 |
Annual Sum or Average | 0.443443E+11 | 0.802463E+11 | 0.00 | 0.486109E+09 | 0.311017E+10 | 0.00 | 0.314855E+12 | 0.00 | 4.44 |
Minimum of Months | 2845093.51 | 0.00 | 0.00 | 1067358.75 | 0.00 | 0.00 | 0.194928E+09 | 0.00 | 4.26 |
Maximum of Months | 0.114150E+11 | 0.328563E+11 | 0.00 | 66721631.14 | 0.841523E+09 | 0.00 | 0.408458E+11 | 0.00 | 4.66 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.610671E+10 | 0.00 | 0.00 | 51317407.02 | 0.00 | 0.00 | 0.429799E+11 | 0.00 | 4.58 |
February | 0.547400E+10 | 0.00 | 0.00 | 44595858.35 | 0.00 | 0.00 | 0.390797E+11 | 0.00 | 4.59 |
March | 0.159294E+10 | 7826093.67 | 0.00 | 71007937.66 | 0.00 | 0.00 | 0.477605E+11 | 0.00 | 4.75 |
April | 0.632602E+09 | 47720563.49 | 0.00 | 85922901.64 | 823587.11 | 0.00 | 0.458790E+11 | 0.00 | 4.93 |
May | 0.267698E+09 | 0.707751E+09 | 0.00 | 79691028.93 | 20138952.63 | 0.00 | 0.364203E+11 | 0.00 | 5.03 |
June | 37654490.96 | 0.175537E+11 | 0.00 | 25978691.79 | 0.430997E+09 | 0.00 | 0.687091E+10 | 0.00 | 4.80 |
July | 908499.07 | 0.351686E+11 | 0.00 | 1197181.59 | 0.587040E+09 | 0.00 | 0.208398E+09 | 0.00 | 4.70 |
August | 16953841.41 | 0.223102E+11 | 0.00 | 16998542.63 | 0.431697E+09 | 0.00 | 0.351204E+10 | 0.00 | 4.75 |
September | 0.268272E+09 | 0.924633E+10 | 0.00 | 44927651.55 | 0.280996E+09 | 0.00 | 0.166372E+11 | 0.00 | 4.82 |
October | 0.688354E+09 | 0.144904E+10 | 0.00 | 75127313.63 | 0.163987E+09 | 0.00 | 0.378777E+11 | 0.00 | 4.90 |
November | 0.183214E+10 | 0.00 | 0.00 | 74595957.12 | 0.00 | 0.00 | 0.474220E+11 | 0.00 | 4.77 |
December | 0.275950E+10 | 0.00 | 0.00 | 57172497.54 | 0.00 | 0.00 | 0.450948E+11 | 0.00 | 4.65 |
Annual Sum or Average | 0.196777E+11 | 0.864911E+11 | 0.00 | 0.628533E+09 | 0.191568E+10 | 0.00 | 0.369743E+12 | 0.00 | 4.77 |
Minimum of Months | 908499.07 | 0.00 | 0.00 | 1197181.59 | 0.00 | 0.00 | 0.208398E+09 | 0.00 | 4.58 |
Maximum of Months | 0.610671E+10 | 0.351686E+11 | 0.00 | 85922901.64 | 0.587040E+09 | 0.00 | 0.477605E+11 | 0.00 | 5.03 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21775804.78 | 0.00 | 0.00 | 0.124177E+09 | 0.00 | 0.00 | 0.654392E+11 | 0.00 | 19.74 |
February | 14052315.95 | 0.00 | 0.00 | 0.105283E+09 | 0.00 | 0.00 | 0.600547E+11 | 0.00 | 19.94 |
March | 0.00 | 10074823.13 | 0.00 | 0.135615E+09 | 0.00 | 0.00 | 0.640349E+11 | 0.00 | 20.10 |
April | 4701803.55 | 70770432.17 | 0.00 | 0.147680E+09 | 0.00 | 0.00 | 0.576831E+11 | 0.00 | 20.20 |
May | 23325166.72 | 0.105335E+10 | 0.00 | 0.116584E+09 | 0.00 | 0.00 | 0.430266E+11 | 0.00 | 20.19 |
June | 163828.88 | 0.224914E+11 | 0.00 | 33741011.00 | 4700330.15 | 0.00 | 0.770488E+10 | 0.00 | 18.98 |
July | 0.00 | 0.444885E+11 | 0.00 | 1530632.99 | 1934175.23 | 0.00 | 0.225566E+09 | 0.00 | 18.64 |
August | 0.00 | 0.290810E+11 | 0.00 | 20493554.93 | 3952607.11 | 0.00 | 0.370778E+10 | 0.00 | 18.90 |
September | 10449863.82 | 0.118666E+11 | 0.00 | 70970064.18 | 7105966.99 | 0.00 | 0.197065E+11 | 0.00 | 19.23 |
October | 13272160.74 | 0.223232E+10 | 0.00 | 0.125941E+09 | 0.00 | 0.00 | 0.471778E+11 | 0.00 | 19.95 |
November | 4711352.24 | 0.00 | 0.00 | 0.147807E+09 | 0.00 | 0.00 | 0.633418E+11 | 0.00 | 20.00 |
December | 0.00 | 0.00 | 0.00 | 0.125934E+09 | 0.00 | 0.00 | 0.634956E+11 | 0.00 | 19.99 |
Annual Sum or Average | 92452296.68 | 0.111294E+12 | 0.00 | 0.115575E+10 | 17693079.48 | 0.00 | 0.495598E+12 | 0.00 | 19.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1530632.99 | 0.00 | 0.00 | 0.225566E+09 | 0.00 | 18.64 |
Maximum of Months | 23325166.72 | 0.444885E+11 | 0.00 | 0.147807E+09 | 7105966.99 | 0.00 | 0.654392E+11 | 0.00 | 20.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.663680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582853E+10 | 0.00 | 0.00 | 0.93 |
February | 0.588171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550942E+10 | 0.00 | 0.00 | 0.94 |
March | 0.105893E+11 | 0.00 | 0.00 | 0.00 | 2105104.34 | 0.136816E+10 | 0.00 | 0.00 | 0.93 |
April | 0.108620E+11 | 0.00 | 0.00 | 0.00 | 13055524.52 | 0.119555E+09 | 0.00 | 0.00 | 0.95 |
May | 0.869277E+10 | 0.00 | 0.00 | 0.00 | 0.193843E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 0.169419E+10 | 0.00 | 0.00 | 0.00 | 0.466107E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
July | 54555780.58 | 0.211317E+09 | 0.00 | 0.00 | 0.898867E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
August | 0.893182E+09 | 0.380874E+09 | 0.00 | 0.00 | 0.544903E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
September | 0.417595E+10 | 0.00 | 0.00 | 0.00 | 0.249752E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
October | 0.925357E+10 | 0.00 | 0.00 | 0.00 | 0.431150E+09 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 0.108402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111419E+10 | 0.00 | 0.00 | 0.93 |
December | 0.841233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358823E+10 | 0.00 | 0.00 | 0.94 |
Annual Sum or Average | 0.779866E+11 | 0.592191E+09 | 0.00 | 0.00 | 0.222364E+11 | 0.175281E+11 | 0.00 | 0.00 | 0.96 |
Minimum of Months | 54555780.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
Maximum of Months | 0.108620E+11 | 0.380874E+09 | 0.00 | 0.00 | 0.898867E+10 | 0.582853E+10 | 0.00 | 0.00 | 0.99 |