Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:45
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:45:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10727.74 | 945.57 | 945.57 |
Net Site Energy | 10727.74 | 945.57 | 945.57 |
Total Source Energy | 23985.85 | 2114.17 | 2114.17 |
Net Source Energy | 23985.85 | 2114.17 | 2114.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 879.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 818.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.02 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 973.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 548.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 82.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 215.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2126.59 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5932.30 | 4795.43 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 879.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 818.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 163.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 548.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 82.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 215.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.76 | 2126.59 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.31 | 265.01 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 264.01 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.89 | 422.68 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.31 | 265.01 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 264.01 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.89 | 422.68 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5932.303 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5932.303 | 100.00 |
Total On-Site and Utility Electric Sources | 5932.303 | 100.00 |
Total Electricity End Uses | 5932.303 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 779.06 | 20.55 |
Air to Air Heat Recovery for Heating | 3012.22 | 79.45 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3791.28 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.50 |
Time Setpoint Not Met During Occupied Cooling | 258.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7438.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:45 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 7.2656 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 10.2688 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 10.2688 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.4563 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.1656 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 9.0094 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 10.2688 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 7.4594 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 7.4594 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 7.4594 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 7.4594 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 7.4594 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.0094 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.0094 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 10.2688 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 6.3938 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 7.6469 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 7.6469 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-19:10 | 06-FEB-19:10 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 185256.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 192755.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 73068.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50343.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24891.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4577.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3549.17 | 174750.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1869.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 460423.49 | 447627.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 185256.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 192755.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 73068.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1304.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 24891.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4577.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3549.17 | 174750.54 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1092.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 953.91 | 0.00 | 0.00 | 0.00 |
Cooling | 3903.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2593.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 516.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.49 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3082.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1738.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 261.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 682.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2305.22 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18787.60 | 5198.25 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.08 | 0.00 | 0.00 | 0.00 |
Cooling | 344.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 228.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 60.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.19 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1655.98 | 458.19 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.08 | 0.00 | 0.00 | 0.00 |
Cooling | 344.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 228.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 60.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.19 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1655.98 | 458.19 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.25 | 0.669290 | 0.594000 | 1.34 | 1.00 | 0.500000 | 0.000569 | 0.000156 | 1.34 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.291794 | 0.175152 | 0.594000 | 0.173326 | 0.594000 | 0.500000 | 0.002175 | 0.000090 | 0.173326 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.219407 | 0.269744 | 0.594000 | 0.130328 | 0.719318 | 0.500000 | 0.001412 | 0.000035 | 0.130328 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.164920 | 0.758873 | 0.594000 | 0.097963 | 1.00 | 0.500000 | 0.000502 | 0.000046 | 0.097963 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.091462 | 0.789469 | 0.594000 | 0.054329 | 1.00 | 0.500000 | 0.000483 | 0.000031 | 0.054329 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.25 | 0.072552 | 0.594000 | 1.93 | 0.594000 | 0.500000 | 0.020839 | 0.000272 | 1.93 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.28 | 0.112621 | 0.594000 | 0.759041 | 0.594000 | 0.500000 | 0.003383 | 0.000268 | 0.759041 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.49 | 0.221881 | 0.594000 | 2.67 | 0.594000 | 0.500000 | 0.001717 | 0.000694 | 2.67 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.594000 | 0.705022 | 1.00 | 0.500000 | 0.000381 | 0.000280 | 0.705022 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.08 | 0.121552 | 0.594000 | 1.24 | 0.594000 | 0.500000 | 0.003134 | 0.000270 | 1.24 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.18 | 0.115801 | 0.594000 | 1.30 | 0.594000 | 0.500000 | 0.003290 | 0.000280 | 1.30 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.22 | 0.700000 | 0.594000 | 1.32 | 0.594000 | 0.500000 | 0.010753 | 0.000192 | 1.32 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.582226 | 0.539377 | 0.594000 | 0.345842 | 1.00 | 0.500000 | 0.000706 | 0.000173 | 0.345842 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7062.55 | 0.000156 | 124.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4059.93 | 0.000090 | 84.27 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1598.11 | 0.000035 | 30.56 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2079.86 | 0.000046 | 42.45 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1387.77 | 0.000031 | 29.30 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12297.83 | 0.000272 | 220.16 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12145.11 | 0.000268 | 239.14 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 31433.15 | 0.000694 | 597.75 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 5919.99 | 0.000131 | 134.78 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 5938.05 | 0.000131 | 135.19 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 33616.75 | 0.000743 | 765.35 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 33969.95 | 0.000751 | 773.39 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 5885.98 | 0.000130 | 134.01 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 5903.98 | 0.000130 | 134.42 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12666.53 | 0.000280 | 252.60 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1787.44 | 0.000039 | 40.69 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1796.64 | 0.000040 | 40.90 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 8524.09 | 0.000188 | 194.06 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12237.29 | 0.000270 | 227.81 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12676.66 | 0.000280 | 235.64 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8690.78 | 0.000192 | 155.95 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7827.43 | 0.000173 | 161.48 |
VAV WITH REHEAT_HEATC | 198079.92 | 0.004376 | 2779.72 |
FLR_3_DOAS_HEATC | 20392.24 | 0.000451 | 286.17 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.01 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 0.998606 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.46 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.85 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.912117 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.906199 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.266289 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.262079 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.09 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.01 | 0.000131 | 0.000416 |
ROOM_2_FLR_3 FAN COIL | 0.998606 | 0.000131 | 0.000410 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.46 | 0.000743 | 0.002195 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.85 | 0.000751 | 0.002498 |
ROOM_5_FLR_3 FAN COIL | 0.912117 | 0.000130 | 0.000376 |
ROOM_6_FLR_3 FAN COIL | 0.906199 | 0.000130 | 0.000374 |
ROOM_1_FLR_6 FAN COIL | 0.266289 | 0.000039 | 0.000109 |
ROOM_2_FLR_6 FAN COIL | 0.262079 | 0.000040 | 0.000107 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.09 | 0.000188 | 0.000456 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.01 |
ROOM_2_FLR_3 FAN COILFAN | 0.998606 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.46 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.85 |
ROOM_5_FLR_3 FAN COILFAN | 0.912117 |
ROOM_6_FLR_3 FAN COILFAN | 0.906199 |
ROOM_1_FLR_6 FAN COILFAN | 0.266289 |
ROOM_2_FLR_6 FAN COILFAN | 0.262079 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.09 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000416 | 1.01 | 0.008687 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000410 | 0.998606 | 0.008690 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002195 | 5.46 | 0.008614 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002498 | 5.85 | 0.008843 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000376 | 0.912117 | 0.008709 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000374 | 0.906199 | 0.008710 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000109 | 0.266289 | 0.008678 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000107 | 0.262079 | 0.008681 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000456 | 1.09 | 0.008774 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.024125 | 0.012367 | 28.89 | 6.70 | 10.99 | 0.008281 | 675437.63 | 19.92 | |
FLR_3_DOAS_COOLC | 0.003079 | 0.014097 | 32.10 | 6.70 | 10.99 | 0.008281 | 86208.04 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.06 | 12.06 | 20.30 | 12.06 | 19.92 | 19.92 | 0.300000 | 0.605076 | 19.92 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 19.92 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 12.05 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 19.92 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024125 | 0.000020 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004376 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003079 | 0.000155 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000451 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.034145 | 8178.08 |
HEATSYS1 PUMP | 0.009898 | 2528.69 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.009898 | 1.19 |
COOLSYS1 | 0.034145 | 4.10 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.034145 | 2726.03 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 447978.01 | 447978.01 | 0.009898 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.034145 | 955976.17 | 956549.46 | 109.05 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 7.266 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.646 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 10.269 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 21.029 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 10.269 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 21.029 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.456 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 7.146 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.166 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 601.696 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.009 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.389 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.269 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.339 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.009 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.829 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.009 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.829 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.269 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2944.756 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 14377.467 | 7.266 | 135.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14377.467 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 688.740 | 10.269 | 63.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 688.740 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 797.564 | 10.269 | 63.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 797.564 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 684.177 | 4.166 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 422.272 | 4.456 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 422.272 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 325.084 | 4.166 | 38.700 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 325.084 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1701.531 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1701.531 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 13433.463 | 10.269 | 31.800 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13433.463 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 182.933 | 7.459 | 121.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.933 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 182.983 | 7.459 | 121.989 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.983 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2489.761 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.761 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 182.983 | 7.459 | 121.989 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.983 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2988.032 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2988.032 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2988.032 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2988.032 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1060.810 | 10.269 | 47.703 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1060.810 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2635.028 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.028 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
25 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
26 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
27 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
28 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
29 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
30 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
31 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
32 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
33 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 31 | 1 | VerySmooth | 2.159 | 0.355 | 0.274 | 0.361 |
2 | RESWINDOW_U_0.39_SHGC_0.36 | 32 | 1 | VerySmooth | 2.216 | 0.355 | 0.274 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.35607E-002 | 0.27318 | 0.51670 | 0.51670 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.12023 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 30992.93099 | 30992.93099 | 2.25294 | 2.25294 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 28.80700 | 1.40969E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4013.30109 | 4013.30109 | 0.29179 | 0.29179 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3146.97403 | 3146.97403 | 0.13494 | 0.13494 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3017.90948 | 3017.90948 | 0.21941 | 0.21941 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.40969E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 911.19194 | 911.19194 | 3.90740E-002 | 9.16993E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2268.99095 | 2268.99095 | 0.16492 | 0.16492 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.40969E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1563.68432 | 1563.68432 | 6.70543E-002 | 6.70543E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1258.34189 | 1258.34189 | 9.14622E-002 | 9.14622E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 32.02600 | 1.40969E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1101.51205 | 1101.51205 | 4.72351E-002 | 5.77430E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44741.55458 | 44741.55458 | 3.25248 | 3.25248 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.40969E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2119.64650 | 2119.64650 | 9.08914E-002 | 0.23597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17561.24931 | 17561.24931 | 1.27785 | 1.27785 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8146.78241 | 8146.78241 | 0.34932 | 0.67613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61778.81760 | 61778.81760 | 4.49268 | 4.49268 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17371.82128 | 17371.82128 | 0.74493 | 1.89326 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10354.58978 | 10354.58978 | 1.01432 | 1.01432 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5919.98913 | 5919.98913 | 0.25535 | 0.25535 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10194.14052 | 10194.14052 | 0.99861 | 0.99861 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5938.04289 | 5938.04289 | 0.25613 | 0.25613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 55716.15995 | 55716.15995 | 5.45744 | 5.45744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33617.22690 | 33617.22690 | 1.45004 | 1.45004 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 59698.37315 | 59698.37315 | 5.84795 | 5.84795 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.40969E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33970.43028 | 33970.43028 | 1.46527 | 1.46527 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9311.20667 | 9311.20667 | 0.91212 | 0.91212 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5885.97493 | 5885.97493 | 0.25388 | 0.25388 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9250.79432 | 9250.79432 | 0.90620 | 0.90620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5903.97195 | 5903.97195 | 0.25466 | 0.25466 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 12784.99963 | 12784.99963 | 0.92925 | 1.18691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 31.80400 | 1.40969E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8949.15464 | 8949.15464 | 0.38377 | 0.47458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2718.37860 | 2718.37860 | 0.26629 | 0.26629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1787.43335 | 1787.43335 | 7.70973E-002 | 7.70973E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2675.40357 | 2675.40357 | 0.26208 | 0.26208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1796.63966 | 1796.63966 | 7.74944E-002 | 7.74944E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11081.39387 | 11081.39387 | 1.08553 | 1.08553 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8524.08520 | 8524.08520 | 0.36767 | 0.36767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28566.77660 | 28566.77660 | 2.07913 | 2.07913 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5724.58646 | 5724.58646 | 0.24548 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29986.04368 | 29986.04368 | 2.18239 | 2.18239 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5840.51424 | 5840.51424 | 0.25045 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30482.76622 | 30482.76622 | 2.22167 | 2.22167 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.40969E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1758.54142 | 1758.54142 | 7.53974E-002 | 0.36721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8010.42389 | 8010.42389 | 0.58223 | 0.58223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.40969E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6003.43486 | 6003.43486 | 0.25744 | 0.25744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 387828.42 | 19.92431 | 19.92431 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 248037.34 | 7.48482 | 7.48482 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 47879.59 | 16.05259 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 67974.13 | 4.45755 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25294 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66929 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33824 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.69260E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56038E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33824 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7062.55186 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56038E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 124.97522 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29179 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17515 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17333 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17525E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.96991E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17333 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4059.92730 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.96991E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.26856 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21941 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26974 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13033 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71932 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41245E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53082E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13033 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1598.10610 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53082E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.56214 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.16492 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75887 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.79625E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.02061E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.59519E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.79625E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2079.85504 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59519E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.45278 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.14622E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78947 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.43285E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.82603E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.06612E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.43285E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1387.77407 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.06612E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.30376 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.25248 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.25518E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93198 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08387E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71705E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93198 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12297.82665 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71705E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.15978 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27785 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11262 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75904 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38302E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.68331E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75904 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12145.10664 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68331E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.13654 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.49268 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22188 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.66865 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71714E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.94477E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.66865 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31433.14919 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.94477E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 597.75417 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01432 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01432 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.01432 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30795E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.16035E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.16035E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.01432 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68695E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68265 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5919.99455 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30795E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.78144 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99861 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99861 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.99861 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.31194E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.09878E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.09878E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.99861 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68961E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68264 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5938.04833 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31194E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 135.19239 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.45744 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.45744 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.45744 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.42721E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.19500E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.19500E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.45744 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.61381E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68339 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 33616.74678 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.42721E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 765.35358 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.84795 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.84795 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.84795 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.50524E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.49802E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.49802E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.84795 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.84263E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68251 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 33969.94545 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.50524E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 773.39340 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91212 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91212 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.91212 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30044E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.76271E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.76271E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.91212 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70861E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68260 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5885.98032 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30044E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.00718 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90620 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.90620 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.90620 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.30441E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.73978E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.73978E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.90620 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71012E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68260 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5903.97735 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30441E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.41684 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.70502 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79852E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70502 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12666.53072 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79852E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.60351 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26629 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26629 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.26629 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.94912E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.08957E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.08957E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.26629 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67788E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68266 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1787.43508 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.94912E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.69341 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26208 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26208 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.26208 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.96946E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.07322E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.07322E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.26208 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68091E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68266 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1796.64139 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.96946E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.90297 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08553 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08553 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.08553 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.88329E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.55577E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.55577E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.08553 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.77418E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68244 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 8524.09286 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88329E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.06199 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07913 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12155 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23500 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13445E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70368E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23500 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12237.28589 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70368E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.80822 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18239 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11580 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29634 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29013E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80075E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29634 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12676.66131 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80075E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 235.64138 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22167 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31967 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07530E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92012E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31967 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8690.77922 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92012E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 155.95480 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58223 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53938 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34584 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.06371E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72937E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34584 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7827.42760 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72937E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 161.48225 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.05573 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.05573 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.29584 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.05573 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 19.92431 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.92431 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.60508 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.92431 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.92431 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 12.05026 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 675437.62862 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.41251E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 19.92431 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.23665E-002 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.89426 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.98878 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 198079.92306 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.37633E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 2779.72373 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 19.92431 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.41251E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.97384E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.37633E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 86208.04375 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.07915E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.40969E-002 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 32.10000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.99443 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20392.24032 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.50542E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 286.17133 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.07915E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54650E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50542E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.41453E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8178.08068 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 9.89753E-003 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.18770 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 9.89753E-003 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2528.69115 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 447978.00709 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 447978.01000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 9.89753E-003 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.41453E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.09743 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.41453E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2726.02689 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.41453E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 955976.17113 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 956549.46000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 109.04664 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7103.07 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4084.06 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1606.44 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2092.55 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1395.89 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12367.52 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12223.24 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31598.20 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6388.08 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6407.56 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 36274.81 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 36655.88 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6351.38 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6370.80 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12745.79 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 1928.72 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 1938.65 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9197.84 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12304.09 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12745.95 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8739.91 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7874.80 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 140528.50 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 14467.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 17091.68 | 13750.08 | 3341.60 | 0.80 | 1914.64 | 19.42 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 16834.56 | 13540.89 | 3293.68 | 0.80 | 1885.74 | 19.13 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 90795.02 | 73397.03 | 17397.99 | 0.81 | 10186.22 | 103.31 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 101146.51 | 80575.62 | 20570.89 | 0.80 | 11299.49 | 114.61 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 15426.76 | 12393.24 | 3033.52 | 0.80 | 1727.41 | 17.52 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 15330.62 | 12314.81 | 3015.81 | 0.80 | 1716.60 | 17.41 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4480.03 | 3606.28 | 873.76 | 0.80 | 501.95 | 5.09 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4411.52 | 3550.42 | 861.10 | 0.80 | 494.25 | 5.01 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 18564.36 | 14851.72 | 3712.64 | 0.80 | 2076.26 | 21.06 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 640313.64 | 415787.18 | 224526.46 | 0.65 | 93746.06 | 950.82 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67743.86 | 43600.34 | 24143.52 | 0.64 | 9176.64 | 93.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.39_SHGC_0.36 | N/A | 2.216 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6472100379E-002 | 2.0649731780E-002 | Pass | Pass | 2.3484393628E-003 | 3.8686105655E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6870651249E-003 | 1.6635163541E-003 | Pass | Pass | 0.2895162611 | 1.6428242240 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.3800600459E-003 | 1.3702027827E-002 | Pass | Pass | 2.6887751058E-002 | 5.6530600172E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0532365375E-004 | 3.3227453300E-004 | Pass | Pass | 0.1176980287 | 0.3796990899 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6014158984E-004 | 4.1294277765E-004 | Pass | Pass | 1.6979309309E-002 | 2.1765523891E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.5360560406E-002 | 0.2178199968 | Pass | Pass | 1.8472252797E-002 | 5.0565319050E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4291740141E-002 | 6.3674719631E-002 | Pass | Pass | 9.5874473553E-002 | 0.1897331217 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5578648268E-002 | 3.7401453394E-002 | Pass | Pass | 1.9190271177E-002 | 5.4162916367E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2710448791E-002 | 0.2803398874 | Pass | Pass | 0.1068270076 | 0.4762766375 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2646573822E-002 | 0.3028063524 | Pass | Pass | 0.1428318591 | 0.6159487865 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.5411841979E-002 | 5.8864706917E-002 | Pass | Pass | 7.4704884729E-003 | 7.0577830117E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8924436046E-002 | 0.1204908186 | Pass | Pass | 6.8366761530E-002 | 0.1780009162 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3981357469E-002 | 0.2358210957 | Pass | Pass | 0.1312692901 | 0.5814629549 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.0295595086E-002 | 0.2621323477 | Pass | Pass | 0.1369425562 | 0.6678368865 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0613467241E-004 | 1.1283961876E-003 | Pass | Pass | 6.9811238590E-002 | 0.1110355640 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2635643870E-002 | 0.3111866069 | Pass | Pass | 0.1202451370 | 0.3119494609 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2670093637E-002 | 0.3187859179 | Pass | Pass | 0.1691847227 | 0.8508298012 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.1612071167E-002 | 0.1783308151 | Pass | Pass | 4.9856310292E-002 | 0.1377515426 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0102258639E-002 | 9.5700927211E-002 | Pass | Pass | 7.3543635915E-003 | 1.8396841809E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6195504528E-002 | 8.7338081521E-002 | Pass | Pass | 7.1305268104E-003 | 1.7390482677E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9547097522E-002 | 0.1291687828 | Pass | Pass | 2.0892094479E-002 | 3.6491067719E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7966514296E-004 | 5.3309394162E-004 | Pass | Pass | 0.1542032696 | 0.6332271119 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.159 | 0.355 | 0.361 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.159 | 0.355 | 0.361 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.159 | 0.355 | 0.361 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.355 | 0.361 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.355 | 0.361 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.355 | 0.361 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.355 | 0.361 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.216 | 0.355 | 0.361 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.216 | 0.355 | 0.361 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.355 | 0.361 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.355 | 0.361 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.216 | 0.355 | 0.361 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.216 | 0.355 | 0.361 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.355 | 0.361 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.355 | 0.361 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.216 | 0.355 | 0.361 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.216 | 0.355 | 0.361 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.39_SHGC_0.36 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.216 | 0.355 | 0.361 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.355 | 0.361 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.159 | 0.355 | 0.361 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.355 | 0.361 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.355 | 0.361 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.159 | 0.355 | 0.361 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.38_SHGC_0.36 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.159 | 0.355 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.199 | 0.355 | 0.361 | ||||||||||||
North Total or Average | 432.93 | 2.201 | 0.355 | 0.361 | ||||||||||||
Non-North Total or Average | 781.15 | 2.198 | 0.355 | 0.361 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.2656 | 1978.83 | 14377.47 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.52 | 168.00 | 52.46 | 0.0000 | Y | 141.59 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 10.2688 | 67.07 | 688.74 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.58 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 10.2688 | 77.67 | 797.56 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.78 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 4.1656 | 164.24 | 684.18 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.4563 | 94.76 | 422.27 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 2.42 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 4.1656 | 78.04 | 325.08 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.58 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 9.0094 | 188.86 | 1701.53 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.87 | 0.0000 | Y | 15.61 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 10.2688 | 1308.19 | 13433.46 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 56.94 | 0.0000 | Y | 143.59 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 7.4594 | 156.09 | 1164.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 7.4594 | 156.07 | 1164.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 7.4594 | 1863.81 | 13902.90 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 111.28 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 7.4594 | 1864.32 | 13906.70 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 111.31 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 7.4594 | 156.09 | 1164.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 7.4594 | 156.07 | 1164.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 6.3938 | 1557.62 | 9959.04 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 7.4594 | 39.02 | 291.08 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.33 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 7.4594 | 39.02 | 291.05 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.33 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 7.4594 | 220.77 | 1646.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 13.18 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 9.0094 | 331.66 | 2988.03 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.73 | 0.0000 | Y | 30.14 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 9.0094 | 331.66 | 2988.03 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.73 | 0.0000 | Y | 30.14 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 10.2688 | 103.30 | 1060.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.67 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 6.3938 | 412.12 | 2635.03 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 7.6469 | 11345.29 | 86756.83 | 477.39 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1701.53 | 663.60 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1701.53 | 0.00 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 13433.46 | 940.34 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 13433.46 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2988.03 | 597.61 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2988.03 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2988.03 | 597.61 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2988.03 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 10390.54 | AstronomicalClock | - | 83.64 | 83.64 | 163.14 | |
Exterior Lighting Total | 10390.54 | 163.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 447978.01 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 956549.46 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11648.09 | 17091.68 | 13750.08 | 3341.60 | 0.80 | - | 1914.64 | 19.42 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11475.72 | 16834.56 | 13540.89 | 3293.68 | 0.80 | - | 1885.74 | 19.13 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 61455.20 | 90795.02 | 73397.03 | 17397.99 | 0.81 | - | 10186.22 | 103.31 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 69939.23 | 101146.51 | 80575.62 | 20570.89 | 0.80 | - | 11299.49 | 114.61 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10534.78 | 15426.76 | 12393.24 | 3033.52 | 0.80 | - | 1727.41 | 17.52 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10470.60 | 15330.62 | 12314.81 | 3015.81 | 0.80 | - | 1716.60 | 17.41 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3050.58 | 4480.03 | 3606.28 | 873.76 | 0.80 | - | 501.95 | 5.09 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3004.77 | 4411.52 | 3550.42 | 861.10 | 0.80 | - | 494.25 | 5.01 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12755.17 | 18564.36 | 14851.72 | 3712.64 | 0.80 | - | 2076.26 | 21.06 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 675437.63 | 640313.64 | 415787.18 | 224526.46 | 0.65 | - | 93746.06 | 950.82 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 86208.04 | 67743.86 | 43600.34 | 24143.52 | 0.64 | - | 9176.64 | 93.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7062.55 | 7103.07 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4059.93 | 4084.06 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1598.11 | 1606.44 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2079.86 | 2092.55 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1387.77 | 1395.89 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12297.83 | 12367.52 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12145.11 | 12223.24 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31433.15 | 31598.20 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5919.99 | 6388.08 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5938.05 | 6407.56 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 33616.75 | 36274.81 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 33969.95 | 36655.88 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5885.98 | 6351.38 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5903.98 | 6370.80 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12666.53 | 12745.79 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1787.44 | 1928.72 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1796.64 | 1938.65 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 8524.09 | 9197.84 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12237.29 | 12304.09 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12676.66 | 12745.95 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8690.78 | 8739.91 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7827.43 | 7874.80 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 198079.92 | 140528.50 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20392.24 | 14467.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 713.71 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 702.66 | 703.64 | 1.00 | 1.20 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.46 | 3840.06 | 703.64 | 1.00 | 0.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.85 | 4114.83 | 703.64 | 1.00 | 0.96 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 641.80 | 703.64 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 637.63 | 703.64 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 187.37 | 703.64 | 1.00 | 1.80 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 184.41 | 703.64 | 1.00 | 1.81 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 763.82 | 703.64 | 1.00 | 1.18 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 19.92 | 44643.18 | 2240.64 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.034145 | 8178.08 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.009898 | 2528.69 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.034145 | 2726.03 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 30992.93 | 30992.93 | 15.66 | 2.253 | 2.253 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00928 | 28.81 | 0.01410 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4013.30 | 4013.30 | 59.84 | 0.292 | 0.292 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00940 | 31.85 | 0.01410 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3017.91 | 3017.91 | 38.86 | 0.219 | 0.219 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00952 | 31.46 | 0.01410 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44741.55 | 44741.55 | 573.32 | 3.252 | 3.252 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00856 | 32.10 | 0.01410 | 0.236 | 0.00 |
CAFE_FLR_1 | 17561.25 | 17561.25 | 92.98 | 1.278 | 1.278 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01046 | 31.85 | 0.01410 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61778.82 | 61778.82 | 47.22 | 4.493 | 4.493 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01013 | 31.98 | 0.01410 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 10354.59 | 10354.59 | 265.35 | 1.014 | 1.014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00869 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10194.14 | 10194.14 | 261.27 | 0.999 | 0.999 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00869 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 55716.16 | 55716.16 | 2271.92 | 5.457 | 5.457 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00861 | 31.98 | 0.01410 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 59698.37 | 59698.37 | 2433.63 | 5.848 | 5.848 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00884 | 32.10 | 0.01410 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9311.21 | 9311.21 | 238.61 | 0.912 | 0.912 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00871 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9250.79 | 9250.79 | 237.09 | 0.906 | 0.906 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00871 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2718.38 | 2718.38 | 69.66 | 0.266 | 0.266 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00868 | 31.26 | 0.01410 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2675.40 | 2675.40 | 68.57 | 0.262 | 0.262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00868 | 31.16 | 0.01410 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11081.39 | 11081.39 | 451.74 | 1.086 | 1.086 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00877 | 31.98 | 0.01410 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28566.78 | 28566.78 | 86.13 | 2.079 | 2.079 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01050 | 32.10 | 0.01410 | 1.187 | 0.00 |
DINING_FLR_6 | 29986.04 | 29986.04 | 90.41 | 2.182 | 2.182 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01041 | 32.10 | 0.01410 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30482.77 | 30482.77 | 295.08 | 2.222 | 2.222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 31.43 | 0.01410 | 0.367 | 0.00 |
MECH_FLR_1 | 2268.99 | 2268.99 | 13.81 | 0.165 | 0.165 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00877 | 31.36 | 0.01410 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1258.34 | 1258.34 | 13.28 | 0.091 | 0.091 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00884 | 32.03 | 0.01410 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 12785.00 | 12785.00 | 32.83 | 0.929 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00865 | 31.80 | 0.01410 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8010.42 | 8010.42 | 19.44 | 0.582 | 0.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00861 | 32.10 | 0.01410 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3146.97 | 3146.97 | 46.92 | 0.135 | 0.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00711 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 911.19 | 911.19 | 11.73 | 0.039 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00733 | -10.70 | 0.00150 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2119.65 | 2119.65 | 27.16 | 0.091 | 0.236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 0.236 | 0.00 |
CAFE_FLR_1 | 8146.78 | 8146.78 | 43.14 | 0.349 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00713 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17371.82 | 17371.82 | 13.28 | 0.745 | 1.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 5919.99 | 5919.99 | 151.71 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5938.04 | 5938.04 | 152.19 | 0.256 | 0.256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00742 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33617.23 | 33617.23 | 1370.80 | 1.450 | 1.450 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33970.43 | 33970.43 | 1384.82 | 1.465 | 1.465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5885.97 | 5885.97 | 150.84 | 0.254 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5903.97 | 5903.97 | 151.32 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00741 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1787.43 | 1787.43 | 45.81 | 0.077 | 0.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1796.64 | 1796.64 | 46.05 | 0.077 | 0.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8524.09 | 8524.09 | 347.49 | 0.368 | 0.368 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00752 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5724.59 | 5724.59 | 17.26 | 0.245 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.187 | 0.00 |
DINING_FLR_6 | 5840.51 | 5840.51 | 17.61 | 0.250 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00762 | -10.70 | 0.00150 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 1758.54 | 1758.54 | 17.02 | 0.075 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00595 | -10.70 | 0.00150 | 0.367 | 0.00 |
MECH_FLR_1 | 1563.68 | 1563.68 | 9.52 | 0.067 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1101.51 | 1101.51 | 11.62 | 0.047 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 8949.15 | 8949.15 | 22.98 | 0.384 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 6003.43 | 6003.43 | 14.57 | 0.257 | 0.257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 19.92 | 19.92 | 7.48 | 7.48 | 19.9243 | 12.0557 | 19.9243 | 0.6051 | 0.3000 |
FLR_3_DOAS | 16.05 | 2.05 | 4.46 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7062.552 | 7062.552 | 1.338244 | 0.00015604 | 124.975 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7103.07 | 7062.55 | 1.338244 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7104.44 | 7104.44 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4059.927 | 4059.927 | 0.173326 | 0.00008970 | 84.269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4084.06 | 4059.93 | 0.173326 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00710584 | 45.9840 | 3146.97 | 0.00 | 4086.29 | 4086.29 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1598.106 | 1598.106 | 0.130328 | 0.00003531 | 30.562 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1606.44 | 1598.11 | 0.130328 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732627 | 47.3909 | 911.19 | 0.00 | 1607.19 | 1607.19 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2079.855 | 2079.855 | 0.097963 | 0.00004595 | 42.453 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2092.55 | 2079.86 | 0.097963 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716014 | 46.3285 | 1563.68 | 0.00 | 2093.55 | 2093.55 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1387.774 | 1387.774 | 0.054329 | 0.00003066 | 29.304 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1395.89 | 1387.77 | 0.054329 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716973 | 46.3900 | 1101.51 | 0.00 | 1396.75 | 1396.75 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12297.827 | 12297.827 | 1.931976 | 0.00027171 | 220.160 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12367.52 | 12297.83 | 1.931976 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00713835 | 46.1905 | 2119.65 | 0.00 | 12370.40 | 12370.40 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12145.107 | 12145.107 | 0.759041 | 0.00026833 | 239.137 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12223.24 | 12145.11 | 0.759041 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00712531 | 46.1083 | 8146.78 | 0.00 | 12227.11 | 12227.11 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31433.149 | 31433.149 | 2.668650 | 0.00069448 | 597.754 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31598.20 | 31433.15 | 2.668650 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00717460 | 46.4213 | 17371.82 | 0.00 | 31612.20 | 31612.20 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11648.085 | -999.000 | 1.014323 | 0.00041603 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11648.09 | 11134.49 | 1.014323 | 21.68 | 15.70 | 0.00868695 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868695 | 55.6926 | 10354.59 | 0.00 | 11667.24 | 10985.61 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5919.995 | 5919.995 | 0.255347 | 0.00013080 | 134.781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6388.08 | 5919.99 | 0.255347 | 21.11 | 14.33 | 0.00741380 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741380 | 47.6268 | 5919.99 | 0.00 | 6390.80 | 6390.80 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11475.718 | -999.000 | 0.998606 | 0.00040988 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11475.72 | 10962.84 | 0.998606 | 21.68 | 15.70 | 0.00868961 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868961 | 55.7095 | 10194.14 | 0.00 | 11494.57 | 10816.64 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5938.048 | 5938.048 | 0.256125 | 0.00013119 | 135.192 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6407.56 | 5938.05 | 0.256125 | 21.11 | 14.33 | 0.00741546 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741546 | 47.6374 | 5938.04 | 0.00 | 6410.29 | 6410.29 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 61455.197 | -999.000 | 5.457444 | 0.00219500 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 61455.20 | 59776.75 | 5.457444 | 21.68 | 15.64 | 0.00861381 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01409687 | 23.07 | 0.0000 | 21.11 | 0.00861381 | 55.2278 | 55716.16 | 0.00 | 61558.39 | 58918.05 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 33616.747 | 33616.747 | 1.450040 | 0.00074272 | 765.354 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36274.81 | 33616.75 | 1.450040 | 21.11 | 14.37 | 0.00744944 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00744944 | 47.8511 | 33617.23 | 0.00 | 36290.60 | 36290.60 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 69939.234 | -999.000 | 5.847953 | 0.00249802 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 69939.23 | 64487.51 | 5.847953 | 21.68 | 15.84 | 0.00884263 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | 0.0000 | 21.11 | 0.00884263 | 56.6766 | 59698.37 | 0.00 | 70049.50 | 63754.63 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33969.945 | 33969.945 | 1.465275 | 0.00075052 | 773.393 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36655.88 | 33969.95 | 1.465275 | 21.11 | 14.37 | 0.00745455 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00745455 | 47.8835 | 33970.43 | 0.00 | 36671.90 | 36671.90 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10534.777 | -999.000 | 0.912117 | 0.00037627 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 10534.78 | 10019.08 | 0.912117 | 21.68 | 15.72 | 0.00870861 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00870861 | 55.8296 | 9311.21 | 0.00 | 10551.99 | 9888.00 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5885.980 | 5885.980 | 0.253880 | 0.00013004 | 134.007 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6351.38 | 5885.98 | 0.253880 | 21.11 | 14.33 | 0.00741072 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741072 | 47.6073 | 5885.97 | 0.00 | 6354.08 | 6354.08 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10470.597 | -999.000 | 0.906199 | 0.00037398 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 10470.60 | 9954.52 | 0.906199 | 21.68 | 15.72 | 0.00871012 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00871012 | 55.8392 | 9250.79 | 0.00 | 10487.70 | 9824.48 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5903.977 | 5903.977 | 0.254656 | 0.00013044 | 134.417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6370.80 | 5903.98 | 0.254656 | 21.11 | 14.33 | 0.00741239 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00741239 | 47.6179 | 5903.97 | 0.00 | 6373.51 | 6373.51 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12666.531 | 12666.531 | 0.705022 | 0.00027985 | 252.604 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12745.79 | 12666.53 | 0.705022 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00751979 | 48.6273 | 8949.15 | 0.00 | 12750.59 | 12750.59 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3050.575 | -999.000 | 0.266289 | 0.00010896 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 3050.58 | 2922.32 | 0.266289 | 21.68 | 15.69 | 0.00867788 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01409687 | 22.87 | 0.0000 | 21.11 | 0.00867788 | 55.6353 | 2718.38 | 0.00 | 3055.60 | 2882.89 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1787.435 | 1787.435 | 0.077097 | 0.00003949 | 40.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1928.72 | 1787.44 | 0.077097 | 21.11 | 14.42 | 0.00750686 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00750686 | 48.2175 | 1787.43 | 0.00 | 1929.59 | 1929.59 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3004.773 | -999.000 | 0.262079 | 0.00010732 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3004.77 | 2876.38 | 0.262079 | 21.68 | 15.69 | 0.00868091 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868091 | 55.6544 | 2675.40 | 0.00 | 3009.72 | 2837.69 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1796.641 | 1796.641 | 0.077494 | 0.00003969 | 40.903 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1938.65 | 1796.64 | 0.077494 | 21.11 | 14.42 | 0.00750924 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00750924 | 48.2326 | 1796.64 | 0.00 | 1939.52 | 1939.52 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12755.172 | -999.000 | 1.085535 | 0.00045558 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 12755.17 | 11946.97 | 1.085535 | 21.68 | 15.78 | 0.00877418 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01409687 | 23.07 | 0.0000 | 21.11 | 0.00877418 | 56.2444 | 11081.39 | 0.00 | 12775.65 | 11800.88 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8524.093 | 8524.093 | 0.367673 | 0.00018833 | 194.062 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 9197.84 | 8524.09 | 0.367673 | 21.11 | 14.43 | 0.00752262 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00752262 | 48.3170 | 8524.09 | 0.00 | 9202.02 | 9202.02 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12237.286 | 12237.286 | 1.235002 | 0.00027037 | 227.808 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12304.09 | 12237.29 | 1.235002 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761498 | 49.2359 | 5724.59 | 0.00 | 12308.64 | 12308.64 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12676.661 | 12676.661 | 1.296339 | 0.00028008 | 235.641 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12745.95 | 12676.66 | 1.296339 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762218 | 49.2821 | 5840.51 | 0.00 | 12750.60 | 12750.60 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8690.779 | 8690.779 | 1.319670 | 0.00019201 | 155.955 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8739.91 | 8690.78 | 1.319670 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00594954 | 38.5783 | 1758.54 | 0.00 | 8742.02 | 8742.02 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7827.428 | 7827.428 | 0.345842 | 0.00017294 | 161.482 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7874.80 | 7827.43 | 0.345842 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767512 | 49.6199 | 6003.43 | 0.00 | 7878.90 | 7878.90 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 675437.629 | -999.000 | 19.924312 | 0.02412507 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 675437.63 | 427963.11 | 19.924312 | 28.89 | 21.00 | 0.01236655 | 10.99 | 10.99 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 60.4802 | 23.99 | 0.00954960 | 51.3206 | 273901.91 | 0.00 | 733890.33 | 456661.97 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 198079.923 | 198079.923 | 5.977293 | 0.00437633 | 2779.724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 140528.50 | 198079.92 | 5.977293 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 201.6006 | 21.00 | 0.00740529 | 47.8967 | 62010.06 | 0.00 | 140362.86 | 140362.86 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86208.044 | -999.000 | 2.051199 | 0.00307915 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86208.04 | 50755.10 | 2.051199 | 32.10 | 23.10 | 0.01409687 | 10.99 | 12.09 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 100.0000 | 21.11 | 0.00873202 | 55.9764 | 163560.71 | 0.00 | 92230.31 | 54243.56 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14467.35 | 20392.24 | 0.615360 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3333 | 21.11 | 0.00745237 | 47.8698 | 103343.54 | 0.00 | 14450.29 | 14450.29 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7062.552 | 7062.552 | 1.338244 | 0.00015604 | 124.975 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.5543 | 1.576540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7103.07 | 7062.55 | 1.0000 | 1.61070436 | 1.338244 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.15602254 | 60.00 | 49.00 | 11.00 | 0.000 | 7103.07 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7104.44 | 7104.44 | 1.61070436 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4059.927 | 4059.927 | 0.173326 | 0.00008970 | 84.269 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.8937 | 0.906278 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4084.06 | 4059.93 | 1.0000 | 0.20861374 | 0.173326 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.08968998 | 60.00 | 49.00 | 11.00 | 0.000 | 4084.06 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00710584 | 21.00 | 0.00710584 | 45.9840 | 3146.97 | 0.00 | 4086.29 | 4086.29 | 0.20861374 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.81 | 19.88 | 0.00800000 | 56522.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1598.106 | 1598.106 | 0.130328 | 0.00003531 | 30.562 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.3515 | 0.356738 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1606.44 | 1598.11 | 1.0000 | 0.15686166 | 0.130328 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03530460 | 60.00 | 49.00 | 11.00 | 0.000 | 1606.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00732627 | 21.00 | 0.00732627 | 47.3909 | 911.19 | 0.00 | 1607.19 | 1607.19 | 0.15686166 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.65 | 16.87 | 0.00800000 | 47180.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2079.855 | 2079.855 | 0.097963 | 0.00004595 | 42.453 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.4579 | 0.464276 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2092.55 | 2079.86 | 1.0000 | 0.11790719 | 0.097963 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.04594717 | 60.00 | 49.00 | 11.00 | 0.000 | 2092.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00716014 | 21.00 | 0.00716014 | 46.3285 | 1563.68 | 0.00 | 2093.55 | 2093.55 | 0.11790719 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.01 | 19.32 | 0.00800000 | 54690.6 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1387.774 | 1387.774 | 0.054329 | 0.00003066 | 29.304 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.3055 | 0.309786 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1395.89 | 1387.77 | 1.0000 | 0.06538954 | 0.054329 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03065804 | 60.00 | 49.00 | 11.00 | 0.000 | 1395.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00716973 | 21.00 | 0.00716973 | 46.3900 | 1101.51 | 0.00 | 1396.75 | 1396.75 | 0.06538954 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 37.55 | 20.41 | 0.00800000 | 58295.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12297.827 | 12297.827 | 1.931976 | 0.00027171 | 220.160 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.7063 | 2.745185 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12367.52 | 12297.83 | 1.0000 | 2.32531635 | 1.931976 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27167774 | 60.00 | 49.00 | 11.00 | 0.000 | 12367.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00713835 | 21.00 | 0.00713835 | 46.1905 | 2119.65 | 0.00 | 12370.40 | 12370.40 | 2.32531635 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.82 | 15.14 | 0.00800000 | 42254.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12145.107 | 12145.107 | 0.759041 | 0.00026833 | 239.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.6747 | 2.711094 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12223.24 | 12145.11 | 1.0000 | 0.91357777 | 0.759041 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26830392 | 60.00 | 49.00 | 11.00 | 0.000 | 12223.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00712531 | 21.00 | 0.00712531 | 46.1083 | 8146.78 | 0.00 | 12227.11 | 12227.11 | 0.91357777 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.73 | 17.92 | 0.00800000 | 50318.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31433.149 | 31433.149 | 2.668650 | 0.00069448 | 597.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 6.9144 | 7.016672 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31598.20 | 31433.15 | 1.0000 | 3.21197366 | 2.668650 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.69440618 | 60.00 | 49.00 | 11.00 | 0.000 | 31598.20 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00717460 | 21.00 | 0.00717460 | 46.4213 | 17371.82 | 0.00 | 31612.20 | 31612.20 | 3.21197366 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.25 | 16.74 | 0.00800000 | 46776.7 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11648.085 | -999.000 | 1.014323 | 0.00041603 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9886 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.014323 | 1.22083417 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 1.2184 | 1.218427 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 11648.09 | 11134.49 | 1.0000 | 1.22083417 | 1.014323 | 21.68 | 15.70 | 0.00868695 | 43863.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.41599240 | 6.70 | 11.72 | 6.67 | 0.000 | 11648.09 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868695 | 21.11 | 0.00868695 | 55.6926 | 10354.59 | 0.00 | 11667.24 | 10985.61 | 1.22083417 | 21.68 | 15.71 | 0.00868695 | 43863.3 | 12.87 | 12.09 | 0.00846582 | 34306.5 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5919.995 | 5919.995 | 0.255347 | 0.00013080 | 134.781 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.014323 | 1.22083417 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.3978 | 1.321492 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6388.08 | 5919.99 | 1.0000 | 0.30733394 | 0.255347 | 21.11 | 14.33 | 0.00741380 | 40044.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13078170 | 60.00 | 49.00 | 11.00 | 0.000 | 6388.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741380 | 21.11 | 0.00741380 | 47.6268 | 5919.99 | 0.00 | 6390.80 | 6390.80 | 0.30733394 | 16.60 | 12.57 | 0.00741380 | 35450.6 | 37.01 | 19.81 | 0.00741380 | 56244.9 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11475.718 | -999.000 | 0.998606 | 0.00040988 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9936 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.998606 | 1.20191753 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 1.2004 | 1.200396 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 11475.72 | 10962.84 | 1.0000 | 1.20191753 | 0.998606 | 21.68 | 15.70 | 0.00868961 | 43870.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.40983658 | 6.70 | 11.72 | 6.67 | 0.000 | 11475.72 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868961 | 21.11 | 0.00868961 | 55.7095 | 10194.14 | 0.00 | 11494.57 | 10816.64 | 1.20191753 | 21.68 | 15.71 | 0.00868961 | 43870.0 | 12.87 | 12.09 | 0.00846622 | 34306.5 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5938.048 | 5938.048 | 0.256125 | 0.00013119 | 135.192 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.998606 | 1.20191753 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.4021 | 1.325522 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6407.56 | 5938.05 | 1.0000 | 0.30827119 | 0.256125 | 21.11 | 14.33 | 0.00741546 | 40048.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13118054 | 60.00 | 49.00 | 11.00 | 0.000 | 6407.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741546 | 21.11 | 0.00741546 | 47.6374 | 5938.04 | 0.00 | 6410.29 | 6410.29 | 0.30827119 | 16.60 | 12.57 | 0.00741546 | 35454.8 | 37.01 | 19.81 | 0.00741546 | 56249.1 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 61455.197 | -999.000 | 5.457444 | 0.00219500 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8526 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.457444 | 6.56855229 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 6.4285 | 6.428408 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | 61455.20 | 59776.75 | 1.0000 | 6.56855229 | 5.457444 | 21.68 | 15.64 | 0.00861381 | 43678.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.19477233 | 6.70 | 11.72 | 6.67 | 0.000 | 61455.20 | 31.98 | 0.01409687 | 23.07 | 0.00000000 | 0.0000 | 21.11 | 0.00861381 | 21.11 | 0.00861381 | 55.2278 | 55716.16 | 0.00 | 61558.39 | 58918.05 | 6.56855229 | 21.68 | 15.64 | 0.00861381 | 43678.2 | 12.90 | 12.09 | 0.00845461 | 34306.5 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33616.747 | 33616.747 | 1.450040 | 0.00074272 | 765.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.457444 | 6.56855229 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 7.9377 | 7.504107 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36274.81 | 33616.75 | 1.0000 | 1.74526063 | 1.450040 | 21.11 | 14.37 | 0.00744944 | 40135.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.74264518 | 60.00 | 49.00 | 11.00 | 0.000 | 36274.81 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00744944 | 21.11 | 0.00744944 | 47.8511 | 33617.23 | 0.00 | 36290.60 | 36290.60 | 1.74526063 | 16.60 | 12.60 | 0.00744944 | 35540.8 | 37.01 | 19.84 | 0.00744944 | 56334.6 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69939.234 | -999.000 | 5.847953 | 0.00249802 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2780 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.847953 | 7.03856650 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 7.3160 | 7.315865 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 69939.23 | 64487.51 | 1.0000 | 7.03856650 | 5.847953 | 21.68 | 15.84 | 0.00884263 | 44258.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.49776591 | 6.70 | 11.72 | 6.67 | 0.000 | 69939.23 | 32.10 | 0.01409687 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00884263 | 21.11 | 0.00884263 | 56.6766 | 59698.37 | 0.00 | 70049.50 | 63754.63 | 7.03856650 | 21.68 | 15.84 | 0.00884263 | 44258.8 | 12.81 | 12.09 | 0.00848841 | 34306.5 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33969.945 | 33969.945 | 1.465275 | 0.00075052 | 773.393 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.847953 | 7.03856650 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 8.0211 | 7.582949 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 36655.88 | 33969.95 | 1.0000 | 1.76359743 | 1.465275 | 21.11 | 14.37 | 0.00745455 | 40148.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.75044787 | 60.00 | 49.00 | 11.00 | 0.000 | 36655.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00745455 | 21.11 | 0.00745455 | 47.8835 | 33970.43 | 0.00 | 36671.90 | 36671.90 | 1.76359743 | 16.60 | 12.61 | 0.00745455 | 35553.8 | 37.01 | 19.84 | 0.00745455 | 56347.6 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10534.777 | -999.000 | 0.912117 | 0.00037627 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0289 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.912117 | 1.09781959 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 1.1020 | 1.101971 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 10534.78 | 10019.08 | 1.0000 | 1.09781959 | 0.912117 | 21.68 | 15.72 | 0.00870861 | 43918.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.37623241 | 6.70 | 11.72 | 6.67 | 0.000 | 10534.78 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00870861 | 21.11 | 0.00870861 | 55.8296 | 9311.21 | 0.00 | 10551.99 | 9888.00 | 1.09781959 | 21.68 | 15.73 | 0.00870861 | 43918.3 | 12.86 | 12.09 | 0.00846906 | 34306.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5885.980 | 5885.980 | 0.253880 | 0.00013004 | 134.007 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.912117 | 1.09781959 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.3898 | 1.313899 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6351.38 | 5885.98 | 1.0000 | 0.30556811 | 0.253880 | 21.11 | 14.33 | 0.00741072 | 40036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13003028 | 60.00 | 49.00 | 11.00 | 0.000 | 6351.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741072 | 21.11 | 0.00741072 | 47.6073 | 5885.97 | 0.00 | 6354.08 | 6354.08 | 0.30556811 | 16.60 | 12.56 | 0.00741072 | 35442.8 | 37.01 | 19.81 | 0.00741072 | 56237.1 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10470.597 | -999.000 | 0.906199 | 0.00037398 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0317 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.906199 | 1.09069657 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 1.0953 | 1.095258 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 10470.60 | 9954.52 | 1.0000 | 1.09069657 | 0.906199 | 21.68 | 15.72 | 0.00871012 | 43922.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.37394033 | 6.70 | 11.72 | 6.67 | 0.000 | 10470.60 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00871012 | 21.11 | 0.00871012 | 55.8392 | 9250.79 | 0.00 | 10487.70 | 9824.48 | 1.09069657 | 21.68 | 15.73 | 0.00871012 | 43922.1 | 12.86 | 12.09 | 0.00846929 | 34306.5 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5903.977 | 5903.977 | 0.254656 | 0.00013044 | 134.417 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.906199 | 1.09069657 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.3941 | 1.317917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 6370.80 | 5903.98 | 1.0000 | 0.30650241 | 0.254656 | 21.11 | 14.33 | 0.00741239 | 40040.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13042786 | 60.00 | 49.00 | 11.00 | 0.000 | 6370.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00741239 | 21.11 | 0.00741239 | 47.6179 | 5903.97 | 0.00 | 6373.51 | 6373.51 | 0.30650241 | 16.60 | 12.57 | 0.00741239 | 35447.0 | 37.01 | 19.81 | 0.00741239 | 56241.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12666.531 | 12666.531 | 0.705022 | 0.00027985 | 252.604 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.7891 | 2.827489 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12745.79 | 12666.53 | 1.0000 | 0.84856075 | 0.705022 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27982297 | 60.00 | 49.00 | 11.00 | 0.000 | 12745.79 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00751979 | 21.00 | 0.00751979 | 48.6273 | 8949.15 | 0.00 | 12750.59 | 12750.59 | 0.84856075 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.34 | 18.45 | 0.00800000 | 51960.9 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3050.575 | -999.000 | 0.266289 | 0.00010896 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9718 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.266289 | 0.32050408 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 0.3191 | 0.319100 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | 3050.58 | 2922.32 | 1.0000 | 0.32050408 | 0.266289 | 21.68 | 15.69 | 0.00867788 | 43840.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.10894633 | 6.70 | 11.72 | 6.67 | 0.000 | 3050.58 | 31.26 | 0.01409687 | 22.87 | 0.00000000 | 0.0000 | 21.11 | 0.00867788 | 21.11 | 0.00867788 | 55.6353 | 2718.38 | 0.00 | 3055.60 | 2882.89 | 0.32050408 | 21.68 | 15.70 | 0.00867788 | 43840.3 | 12.87 | 12.09 | 0.00846445 | 34306.5 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1787.435 | 1787.435 | 0.077097 | 0.00003949 | 40.693 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.266289 | 0.32050408 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.4220 | 0.399001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1928.72 | 1787.44 | 1.0000 | 0.09279395 | 0.077097 | 21.11 | 14.42 | 0.00750686 | 40280.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03948717 | 60.00 | 49.00 | 11.00 | 0.000 | 1928.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750686 | 21.11 | 0.00750686 | 48.2175 | 1787.43 | 0.00 | 1929.59 | 1929.59 | 0.09279395 | 16.60 | 12.66 | 0.00750686 | 35686.2 | 37.01 | 19.88 | 0.00750686 | 56480.5 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3004.773 | -999.000 | 0.262079 | 0.00010732 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9774 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.262079 | 0.31543722 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 0.3143 | 0.314309 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 3004.77 | 2876.38 | 1.0000 | 0.31543722 | 0.262079 | 21.68 | 15.69 | 0.00868091 | 43847.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.10731058 | 6.70 | 11.72 | 6.67 | 0.000 | 3004.77 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868091 | 21.11 | 0.00868091 | 55.6544 | 2675.40 | 0.00 | 3009.72 | 2837.69 | 0.31543722 | 21.68 | 15.70 | 0.00868091 | 43847.9 | 12.87 | 12.09 | 0.00846491 | 34306.5 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1796.641 | 1796.641 | 0.077494 | 0.00003969 | 40.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.262079 | 0.31543722 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 0.4242 | 0.401056 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1938.65 | 1796.64 | 1.0000 | 0.09327189 | 0.077494 | 21.11 | 14.42 | 0.00750924 | 40286.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03969055 | 60.00 | 49.00 | 11.00 | 0.000 | 1938.65 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00750924 | 21.11 | 0.00750924 | 48.2326 | 1796.64 | 0.00 | 1939.52 | 1939.52 | 0.09327189 | 16.60 | 12.66 | 0.00750924 | 35692.2 | 37.01 | 19.88 | 0.00750924 | 56486.5 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12755.172 | -999.000 | 1.085535 | 0.00045558 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1508 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.085535 | 1.30654392 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 1.3343 | 1.334231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | 12755.17 | 11946.97 | 1.0000 | 1.30654392 | 1.085535 | 21.68 | 15.78 | 0.00877418 | 44084.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.45553022 | 6.70 | 11.72 | 6.67 | 0.000 | 12755.17 | 31.98 | 0.01409687 | 23.07 | 0.00000000 | 0.0000 | 21.11 | 0.00877418 | 21.11 | 0.00877418 | 56.2444 | 11081.39 | 0.00 | 12775.65 | 11800.88 | 1.30654392 | 21.68 | 15.78 | 0.00877418 | 44084.7 | 12.84 | 12.09 | 0.00847868 | 34306.5 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8524.093 | 8524.093 | 0.367673 | 0.00018833 | 194.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.085535 | 1.30654392 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.0127 | 1.902793 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 9197.84 | 8524.09 | 1.0000 | 0.44252937 | 0.367673 | 21.11 | 14.43 | 0.00752262 | 40321.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.18831020 | 60.00 | 49.00 | 11.00 | 0.000 | 9197.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752262 | 21.11 | 0.00752262 | 48.3170 | 8524.09 | 0.00 | 9202.02 | 9202.02 | 0.44252937 | 16.60 | 12.67 | 0.00752262 | 35726.1 | 37.01 | 19.89 | 0.00752262 | 56520.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12237.286 | 12237.286 | 1.235002 | 0.00027037 | 227.808 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.6924 | 2.731671 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12304.09 | 12237.29 | 1.0000 | 1.48644208 | 1.235002 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27034030 | 60.00 | 49.00 | 11.00 | 0.000 | 12304.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00761498 | 21.00 | 0.00761498 | 49.2359 | 5724.59 | 0.00 | 12308.64 | 12308.64 | 1.48644208 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.72 | 16.20 | 0.00800000 | 45215.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12676.661 | 12676.661 | 1.296339 | 0.00028008 | 235.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 2.7891 | 2.829751 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12745.95 | 12676.66 | 1.0000 | 1.56026736 | 1.296339 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.28004677 | 60.00 | 49.00 | 11.00 | 0.000 | 12745.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00762218 | 21.00 | 0.00762218 | 49.2821 | 5840.51 | 0.00 | 12750.60 | 12750.60 | 1.56026736 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.61 | 16.16 | 0.00800000 | 45106.8 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8690.779 | 8690.779 | 1.319670 | 0.00019201 | 155.955 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.9125 | 1.940001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8739.91 | 8690.78 | 1.0000 | 1.58834846 | 1.319670 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.19199256 | 60.00 | 49.00 | 11.00 | 0.000 | 8739.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.42 | 0.00594954 | 21.00 | 0.00594954 | 38.5783 | 1758.54 | 0.00 | 8742.02 | 8742.02 | 1.58834846 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.00 | 15.21 | 0.00800000 | 42438.6 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7827.428 | 7827.428 | 0.345842 | 0.00017294 | 161.482 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 1.7232 | 1.747279 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7874.80 | 7827.43 | 1.0000 | 0.41625399 | 0.345842 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.17291981 | 60.00 | 49.00 | 11.00 | 0.000 | 7874.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00767512 | 21.00 | 0.00767512 | 49.6199 | 6003.43 | 0.00 | 7878.90 | 7878.90 | 0.41625399 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.16 | 19.68 | 0.00800000 | 55862.9 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 675437.629 | -999.000 | 19.924312 | 0.02412507 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.8288 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.924312 | 23.98080137 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 70.6542 | 70.654233 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 675437.63 | 427963.11 | 1.0000 | 23.98080137 | 19.924312 | 28.89 | 21.00 | 0.01236655 | 60626.3 | 10.99 | 10.99 | 0.00828082 | 32473.6 | 24.12260609 | 6.70 | 11.72 | 6.67 | 44643.182 | 630794.45 | 32.10 | 0.01409687 | 23.10 | 12.05026000 | 60.4802 | 23.99 | 0.00971850 | 23.99 | 0.00954960 | 51.3206 | 273901.91 | 0.00 | 733890.33 | 456661.97 | 23.98080137 | 28.89 | 21.00 | 0.01236655 | 60626.3 | 10.37 | 10.32 | 0.00777946 | 30023.1 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 198079.923 | 198079.923 | 5.977293 | 0.00437633 | 2779.724 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.924312 | 23.98080137 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 30.7506 | 44.216439 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 140528.50 | 198079.92 | 1.0000 | 7.19424041 | 5.977293 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 4.37588743 | 60.00 | 49.00 | 11.00 | 0.000 | 140528.50 | -10.70 | 0.00150390 | -10.70 | 12.05026000 | 201.6006 | 18.52 | 0.00632199 | 21.00 | 0.00740529 | 47.8967 | 62010.06 | 0.00 | 140362.86 | 140362.86 | 7.19424041 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86208.044 | -999.000 | 2.051199 | 0.00307915 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0454 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 34.14177066 | 13.37 | 6.70 | 6.67 | 955976.17 | 9.0178 | 9.017803 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86208.04 | 50755.10 | 1.0000 | 2.46881288 | 2.051199 | 32.10 | 23.10 | 0.01409687 | 68352.0 | 10.99 | 12.09 | 0.00828082 | 34322.2 | 3.07883747 | 6.70 | 11.72 | 6.67 | 2194.880 | 84013.16 | 32.10 | 0.01409687 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00873678 | 21.11 | 0.00873202 | 55.9764 | 163560.71 | 0.00 | 92230.31 | 54243.56 | 2.46881288 | 32.10 | 23.11 | 0.01409687 | 68352.0 | 10.79 | 10.73 | 0.00799347 | 30993.8 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 9.89651702 | 71.00 | 82.00 | 11.00 | 456993.74 | 3.1658 | 4.552063 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14467.35 | 20392.24 | 1.0000 | 0.74064386 | 0.615360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.45049567 | 60.00 | 49.00 | 11.00 | 0.000 | 14467.35 | -10.70 | 0.00150390 | -10.70 | 2.05119905 | 333.3333 | 21.11 | 0.00745087 | 21.11 | 0.00745237 | 47.8698 | 103343.54 | 0.00 | 14450.29 | 14450.29 | 0.74064386 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 19.92 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003539 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003539 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 9.67 | 8442.33 | 0.00 |
RETAIL_1_FLR_1 | 1468.17 | 8216.17 | 1259.50 |
RETAIL_2_FLR_1 | 83.17 | 8680.67 | 83.17 |
LAUNDRY_FLR_1 | 4761.17 | 3177.17 | 1726.17 |
CAFE_FLR_1 | 1057.83 | 7001.50 | 194.67 |
LOBBY_FLR_1 | 129.00 | 8181.00 | 6.67 |
ROOM_1_FLR_3 | 2064.17 | 8360.83 | 2036.50 |
ROOM_2_FLR_3 | 2668.67 | 8458.33 | 2644.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1138.00 | 8760.00 | 1138.00 |
ROOM_5_FLR_3 | 1989.17 | 8391.17 | 1979.33 |
ROOM_6_FLR_3 | 2565.17 | 8524.00 | 2554.17 |
ROOM_1_FLR_6 | 2736.67 | 8158.00 | 2617.83 |
ROOM_2_FLR_6 | 3200.33 | 8266.17 | 3115.17 |
ROOM_3_MULT9_FLR_6 | 1325.50 | 8226.33 | 1281.67 |
BANQUET_FLR_6 | 2900.67 | 3819.33 | 173.00 |
DINING_FLR_6 | 4035.50 | 2371.50 | 104.50 |
KITCHEN_FLR_6 | 7815.33 | 6412.50 | 6122.83 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8704.50 | 8760.00 | 7438.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 44.00 | 0.00 | 44.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 2.17 | 1.33 | 2.17 | 1.33 |
ROOM_2_FLR_3 | 4.50 | 0.17 | 4.50 | 0.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.83 | 30.33 | 1.83 | 30.33 |
ROOM_5_FLR_3 | 2.83 | 1.17 | 2.83 | 1.17 |
ROOM_6_FLR_3 | 8.00 | 1.33 | 8.00 | 1.33 |
ROOM_1_FLR_6 | 1.83 | 8.33 | 1.83 | 8.33 |
ROOM_2_FLR_6 | 3.67 | 4.67 | 3.67 | 4.67 |
ROOM_3_MULT9_FLR_6 | 1.50 | 18.17 | 1.50 | 18.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 177.00 | 0.00 | 177.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 9.50 | 258.83 | 9.50 | 258.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 1.018 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.377 | 0.270 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.545 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.580 | 0.150 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 3.710 | 0.243 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.00 | 422.44 | 5183.56 | 1.882 | 0.070 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.177 | 0.000 | 0.088 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.177 | 0.000 | 0.085 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.402 | 0.079 | 0.000 | 0.136 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.178 | 0.000 | 0.088 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.177 | 0.000 | 0.085 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.178 | 0.000 | 0.107 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.177 | 0.000 | 0.103 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.145 | 0.000 | 0.170 |
BANQUET_FLR_6 | 144.93 | 249.90 | 1010.89 | 4.643 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.93 | 249.90 | 1010.89 | 4.984 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.661 | 0.148 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 0.977 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.285 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.483 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.948 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 3.556 | 0.005 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.00 | 422.44 | 5183.56 | 1.806 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.93 | 249.90 | 1010.89 | 4.290 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.93 | 249.90 | 1010.89 | 4.509 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 14.792 | 0.003 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
Electricity:Building | 2571.06 | 32700.73 | 10-JUN-05:00 | 162081.79 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 291.85 | 3415.73 | 02-JAN-02:10 | 21692.39 | 02-JAN-20:10 |
InteriorLights:Electricity | 818.95 | 6867.78 | 10-JUN-05:00 | 73068.04 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 141.59 | 1286.51 | 02-JAN-02:10 | 11578.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 818.95 | 6867.78 | 10-JUN-05:00 | 73068.04 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.77 | 213.21 | 02-JAN-02:10 | 1305.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.58 | 68.87 | 02-JAN-02:10 | 619.87 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.57 | 246.90 | 02-JAN-02:10 | 1511.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.78 | 79.76 | 02-JAN-02:10 | 717.81 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.01 | 72.94 | 02-JAN-02:10 | 439.78 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.42 | 21.96 | 02-JAN-02:10 | 197.62 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.52 | 995.20 | 02-JAN-02:10 | 4865.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.58 | 32.51 | 02-JAN-02:10 | 292.58 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 29.95 | 307.01 | 10-JUN-05:00 | 2496.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 15.61 | 103.79 | 10-JUN-05:00 | 1531.38 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 292.59 | 3392.07 | 20-MAY-05:00 | 22119.33 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 143.59 | 1280.66 | 20-MAY-05:00 | 12090.12 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.61 | 280.58 | 01-JAN-02:10 | 1668.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.32 | 58.22 | 01-JAN-11:10 | 931.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.61 | 280.55 | 01-JAN-02:10 | 1668.78 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.32 | 58.21 | 01-JAN-11:10 | 931.35 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 340.04 | 4755.63 | 01-JAN-02:10 | 24847.43 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 111.28 | 695.15 | 01-JAN-11:10 | 11122.32 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 340.13 | 4756.94 | 01-JAN-02:10 | 24854.23 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 111.31 | 695.34 | 01-JAN-11:10 | 11125.36 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.61 | 280.58 | 01-JAN-02:10 | 1668.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.32 | 58.22 | 01-JAN-11:10 | 931.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.61 | 280.55 | 01-JAN-02:10 | 1668.78 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.32 | 58.21 | 01-JAN-11:10 | 931.35 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.40 | 70.14 | 01-JAN-02:10 | 417.24 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.33 | 14.55 | 01-JAN-11:10 | 232.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.40 | 70.14 | 01-JAN-02:10 | 417.19 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.33 | 14.55 | 01-JAN-11:10 | 232.84 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 40.28 | 563.32 | 01-JAN-02:10 | 2943.26 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.18 | 82.34 | 01-JAN-11:10 | 1317.48 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 206.00 | 2488.34 | 20-MAY-05:00 | 9437.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.14 | 239.04 | 20-MAY-05:00 | 2689.23 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 206.00 | 2488.34 | 20-MAY-05:00 | 9437.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.14 | 239.04 | 20-MAY-05:00 | 2689.23 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 452.51 | 6238.01 | 02-JAN-02:10 | 18899.03 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 11.67 | 106.08 | 02-JAN-02:10 | 954.73 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.02 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.58 | 1114.65 | 14-DEC-23:30 | 3259.08 | 13-OCT-06:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1460.57 | 2791.31 | 13-APR-02:10 | 203326.02 | 04-AUG-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 20.31 | 0.00 | 01-JAN-11:10 | 1935.52 | 24-MAR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.17 | 930.61 | 06-FEB-04:10 | 1198.43 | 30-APR-13:10 |
WaterSystems:Electricity | 90.76 | 1086.72 | 09-NOV-01:20 | 4738.76 | 10-APR-18:10 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.72 | 09-NOV-01:20 | 4738.76 | 10-APR-18:10 |
Fans:Electricity | 548.85 | 13894.99 | 04-MAY-14:00 | 29140.92 | 24-AUG-20:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 787.08 | 14518.49 | 04-MAY-14:00 | 39076.83 | 30-OCT-20:30 |
ExteriorEquipment:Electricity | 973.29 | 6518.85 | 02-JAN-02:20 | 62600.61 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.84 | 388.93 | 20-MAY-05:00 | 1321.13 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
ElectricityPurchased:Plant | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
Cogeneration:ElectricityPurchased | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
ElectricityNet:Plant | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
Cogeneration:ElectricityNet | 5932.30 | 69980.02 | 24-JAN-02:20 | 460423.49 | 04-AUG-19:10 |
General:Fans:Electricity | 548.85 | 13894.99 | 04-MAY-14:00 | 29140.92 | 24-AUG-20:20 |
ExteriorLights:Electricity | 163.14 | 0.00 | 01-JAN-07:30 | 10390.54 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 163.14 | 0.00 | 01-JAN-07:30 | 10390.54 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 215.39 | 0.00 | 03-JAN-11:10 | 10206.30 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1232.65 | 0.00 | 01-JAN-00:10 | 192755.16 | 04-AUG-19:10 |
General:Cooling:Electricity | 1232.65 | 0.00 | 01-JAN-00:10 | 192755.16 | 04-AUG-19:10 |
Pumps:Electricity | 82.68 | 61.49 | 03-APR-17:10 | 5496.94 | 24-JUN-18:50 |
General:Pumps:Electricity | 82.68 | 61.49 | 03-APR-17:10 | 5496.94 | 24-JUN-18:50 |
WIRED_LTG_ELECTRICITY | 28.83 | 0.00 | 01-JAN-00:10 | 2572.00 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4795.43 | 32343.50 | 11-SEP-00:10 | 447627.20 | 06-FEB-19:10 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 3006.58 | 15908.90 | 26-JUN-07:10 | 388013.20 | 05-FEB-24:00 |
WaterSystems:Gas | 2126.59 | 15908.90 | 10-JAN-16:10 | 177769.58 | 09-FEB-21:50 |
Water Heater:WaterSystems:Gas | 2126.59 | 15908.90 | 10-JAN-16:10 | 177769.58 | 09-FEB-21:50 |
Heating:Gas | 879.99 | 0.00 | 27-MAR-20:20 | 230358.92 | 06-FEB-09:10 |
Boiler:Heating:Gas | 879.99 | 0.00 | 27-MAR-20:20 | 230358.92 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4169.28 | 0.00 | 01-JAN-00:10 | 714933.60 | 24-JUN-18:20 |
PlantLoopCoolingDemand:HVAC | 4169.28 | 0.00 | 01-JAN-00:10 | 714933.60 | 24-JUN-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 4169.28 | 0.00 | 01-JAN-00:10 | 714933.60 | 24-JUN-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 10-APR-06:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 10-APR-06:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 24667.59 | 148886.85 | 04-MAY-11:30 | 2865672.39 | 03-AUG-20:10 |
EnergyTransfer:Building | 4968.82 | 82325.57 | 27-FEB-11:10 | 314015.02 | 19-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 723.95 | 10807.01 | 06-FEB-04:00 | 35476.67 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 181.98 | 3963.83 | 06-FEB-04:00 | 10344.58 | 13-OCT-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.99 | 1981.92 | 06-FEB-04:00 | 5172.29 | 13-OCT-06:30 |
EnergyTransfer:Plant | 11127.26 | 21149.30 | 19-OCT-01:00 | 1632045.18 | 24-JUN-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.59 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.40 | 1741.82 | 06-FEB-04:10 | 2545.29 | 30-APR-13:10 |
PlantLoopHeatingDemand:Facility | 1354.46 | 8936.39 | 16-SEP-00:10 | 234429.30 | 06-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 743.51 | 8489.16 | 31-JUL-00:10 | 56380.25 | 06-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 743.51 | 8489.16 | 31-JUL-00:10 | 56380.25 | 06-FEB-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 407.66 | 8431.79 | 21-MAY-14:30 | 19360.65 | 22-NOV-22:00 |
Heating:EnergyTransfer | 127.57 | 0.00 | 17-JAN-11:10 | 78997.60 | 14-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4750.26 | 68329.63 | 08-JAN-15:00 | 310408.10 | 19-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 407.66 | 8431.79 | 21-MAY-14:30 | 19360.65 | 22-NOV-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.32 | 0.01 | 11-DEC-22:00 | 3153.26 | 13-OCT-12:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.16 | 0.00 | 01-JAN-09:00 | 1564.39 | 06-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 34.17 | 0.00 | 01-JAN-00:10 | 3153.26 | 13-OCT-12:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.93 | 251.75 | 08-JAN-16:00 | 1759.89 | 24-AUG-20:30 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.93 | 251.75 | 08-JAN-16:00 | 1759.89 | 24-AUG-20:30 |
EnergyTransfer:Zone:MECH_FLR_1 | 22.11 | 0.03 | 09-JAN-13:30 | 1240.62 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.34 | 0.00 | 01-JAN-20:10 | 618.62 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.77 | 0.00 | 01-JAN-00:10 | 1240.62 | 18-AUG-21:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.31 | 0.01 | 25-JAN-10:30 | 671.66 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.89 | 0.00 | 03-JAN-19:10 | 552.32 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.42 | 0.00 | 01-JAN-00:10 | 671.66 | 04-AUG-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 600.97 | 8861.67 | 02-JAN-05:00 | 38277.18 | 04-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 600.97 | 8861.67 | 02-JAN-05:00 | 38277.18 | 04-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 217.86 | 4.25 | 11-DEC-14:10 | 11653.04 | 30-SEP-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 1205.58 | 14-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 217.82 | 0.00 | 02-JAN-07:10 | 11653.04 | 30-SEP-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 806.02 | 7425.66 | 08-JAN-15:50 | 36755.02 | 24-AUG-20:30 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 806.02 | 7425.66 | 08-JAN-15:50 | 36755.02 | 24-AUG-20:30 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 53.03 | 0.00 | 01-JAN-08:10 | 10613.26 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.83 | 0.00 | 01-JAN-08:10 | 6007.74 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.20 | 0.00 | 01-JAN-00:10 | 10613.26 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 52.50 | 0.00 | 01-JAN-08:10 | 10113.29 | 12-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.69 | 0.00 | 01-JAN-08:10 | 6079.99 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 33.81 | 0.00 | 01-JAN-00:10 | 10113.29 | 12-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 256.41 | 0.00 | 01-JAN-00:10 | 45981.14 | 04-OCT-12:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 256.41 | 0.00 | 01-JAN-00:10 | 45981.14 | 04-OCT-12:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 404.46 | 0.00 | 01-JAN-08:10 | 67050.47 | 29-MAY-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.22 | 0.00 | 01-JAN-08:10 | 34727.01 | 06-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 382.24 | 0.00 | 01-JAN-00:10 | 67050.47 | 29-MAY-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.19 | 0.00 | 01-JAN-08:10 | 9698.77 | 14-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 14.62 | 0.00 | 01-JAN-08:10 | 6060.29 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.57 | 0.00 | 01-JAN-00:10 | 9698.77 | 14-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 51.30 | 0.00 | 01-JAN-08:10 | 9618.37 | 14-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 18.35 | 0.00 | 01-JAN-08:10 | 6141.10 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 32.96 | 0.00 | 01-JAN-00:10 | 9618.37 | 14-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 122.88 | 0.37 | 12-DEC-20:40 | 7869.39 | 24-AUG-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.59 | 0.00 | 03-JAN-20:00 | 3814.87 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 114.28 | 0.00 | 01-JAN-00:10 | 7869.39 | 24-AUG-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.47 | 0.00 | 01-JAN-08:10 | 2922.30 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.57 | 0.00 | 01-JAN-08:10 | 1871.48 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.91 | 0.00 | 01-JAN-00:10 | 2922.30 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.54 | 0.00 | 01-JAN-08:10 | 2841.64 | 22-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.82 | 0.00 | 01-JAN-08:10 | 1870.88 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.73 | 0.00 | 01-JAN-00:10 | 2841.64 | 22-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 82.91 | 0.00 | 01-JAN-08:10 | 12620.65 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 11.73 | 0.00 | 01-JAN-08:10 | 8314.47 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 71.18 | 0.00 | 01-JAN-00:10 | 12620.65 | 06-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 440.10 | 8372.83 | 06-FEB-15:00 | 22421.60 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 440.10 | 8372.83 | 06-FEB-15:00 | 22421.60 | 04-AUG-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 481.32 | 9415.55 | 06-FEB-15:00 | 23891.32 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 481.32 | 9415.55 | 06-FEB-15:00 | 23891.32 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 632.96 | 8825.09 | 06-FEB-04:00 | 30416.50 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 75.57 | 0.00 | 28-FEB-12:10 | 4523.41 | 18-AUG-13:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 2.73 | 0.00 | 01-JAN-09:50 | 2861.38 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 72.84 | 0.00 | 01-JAN-00:10 | 4523.41 | 18-AUG-13:50 |
WaterSystems:EnergyTransfer | 743.51 | 8489.16 | 31-JUL-00:10 | 56380.25 | 06-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 743.51 | 8489.16 | 31-JUL-00:10 | 56380.25 | 06-FEB-07:10 |
EnergyTransfer:HVAC | 8571.51 | 4597.48 | 05-APR-14:10 | 961066.01 | 03-AUG-20:00 |
HeatingCoils:EnergyTransfer | 610.95 | 0.00 | 27-MAR-20:20 | 185855.26 | 06-FEB-09:10 |
PlantLoopHeatingDemand:HVAC | 610.95 | 0.00 | 27-MAR-20:20 | 185855.26 | 06-FEB-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 610.95 | 0.00 | 27-MAR-20:20 | 185855.26 | 06-FEB-09:10 |
CoolingCoils:EnergyTransfer | 4169.28 | 0.00 | 01-JAN-00:10 | 714933.60 | 24-JUN-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 3012.22 | 0.00 | 03-JAN-11:10 | 468990.12 | 06-FEB-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 779.06 | 0.00 | 01-JAN-00:10 | 301776.69 | 08-JUL-12:10 |
Boilers:EnergyTransfer | 601.06 | 0.00 | 27-MAR-20:20 | 186042.18 | 06-FEB-09:10 |
Chillers:EnergyTransfer | 4229.52 | 0.00 | 01-JAN-00:10 | 715408.06 | 24-JUN-18:20 |
HeatRejection:EnergyTransfer | 5462.18 | 0.00 | 01-JAN-00:10 | 885183.80 | 24-JUN-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -407.661 | 0.000 | 0.000 | 146.923 | 141.590 | 150.259 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -31.111 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 2.157 | -34.166 | 0.000 | 0.000 | 15.886 | 7.580 | 10.186 | 19.484 | 0.000 | 0.530 | 0.000 | 0.000 | -9.793 | 0.000 | -7.541 | -4.323 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.928 | 0.000 | 0.000 | 17.738 | 8.778 | 11.795 | 0.000 | 0.000 | 0.112 | 0.158 | 0.000 | 0.000 | 0.000 | -1.653 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -600.973 | 0.000 | 0.000 | 11.705 | 3.578 | 658.148 | 0.000 | 0.000 | 0.385 | 0.000 | 0.000 | 0.000 | 0.000 | -5.299 | -67.543 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.037 | -217.824 | 0.000 | 0.000 | 198.181 | 15.608 | 14.341 | 54.037 | 0.000 | 1.190 | 0.000 | 0.000 | -29.301 | 0.000 | -20.236 | -16.034 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -806.021 | 0.000 | 0.000 | 580.789 | 143.591 | 149.002 | 71.926 | 0.000 | 2.555 | 0.000 | 0.000 | -39.576 | 0.000 | -41.132 | -61.134 |
ROOM_1_FLR_3 | 14.828 | -26.555 | 0.000 | -11.644 | 0.000 | 0.000 | 9.727 | 9.320 | 12.292 | 37.861 | 0.000 | 1.238 | 0.000 | 0.000 | -22.940 | 0.000 | -9.474 | -14.654 |
ROOM_2_FLR_3 | 18.688 | -22.228 | 0.000 | -11.585 | 0.000 | 0.000 | 9.752 | 9.318 | 12.291 | 27.771 | 0.000 | 1.218 | 0.000 | 0.000 | -23.850 | 0.000 | -9.347 | -12.029 |
ROOM_3_MULT19_FLR_3 | 0.000 | -241.392 | 0.000 | -15.019 | 0.000 | 0.000 | 0.000 | 111.282 | 228.754 | 208.454 | 0.000 | 0.575 | 0.027 | 0.000 | -167.949 | 0.000 | -63.953 | -60.752 |
ROOM_4_MULT19_FLR_3 | 22.222 | -224.570 | 0.000 | -157.651 | 0.000 | 0.000 | 184.645 | 111.313 | 228.817 | 73.221 | 0.000 | 14.211 | 0.000 | 0.000 | -136.962 | 0.000 | -58.350 | -56.894 |
ROOM_5_FLR_3 | 14.624 | -25.908 | 0.000 | -11.656 | 0.000 | 0.000 | 9.722 | 9.320 | 12.292 | 37.263 | 0.000 | 1.237 | 0.000 | 0.000 | -22.616 | 0.000 | -9.501 | -14.776 |
ROOM_6_FLR_3 | 18.349 | -21.352 | 0.000 | -11.602 | 0.000 | 0.000 | 9.746 | 9.318 | 12.291 | 26.857 | 0.000 | 1.216 | 0.000 | 0.000 | -23.217 | 0.000 | -9.377 | -12.229 |
ROOM_1_FLR_6 | 5.568 | -7.997 | 0.000 | -2.909 | 0.000 | 0.000 | 2.434 | 2.330 | 3.073 | 9.391 | 0.000 | 0.331 | 0.000 | 0.000 | -5.727 | 0.000 | -2.405 | -4.087 |
ROOM_2_FLR_6 | 6.818 | -6.829 | 0.000 | -2.896 | 0.000 | 0.000 | 2.440 | 2.330 | 3.073 | 6.874 | 0.000 | 0.324 | 0.000 | 0.000 | -5.949 | 0.000 | -2.373 | -3.811 |
ROOM_3_MULT9_FLR_6 | 11.726 | -52.352 | 0.000 | -18.825 | 0.000 | 0.000 | 21.803 | 13.182 | 27.097 | 50.231 | 0.000 | 2.264 | 0.000 | 0.000 | -27.046 | 0.000 | -12.100 | -15.980 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -440.103 | 0.000 | 0.000 | 321.896 | 30.140 | 175.857 | 7.554 | 0.000 | 0.259 | 0.000 | 0.000 | -18.304 | 0.000 | -6.390 | -70.910 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -481.322 | 0.000 | 0.000 | 319.374 | 30.140 | 175.857 | 7.269 | 0.000 | 0.246 | 0.000 | 0.000 | -18.986 | 0.000 | -6.475 | -26.103 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -632.939 | 0.000 | 0.000 | 29.023 | 11.675 | 550.372 | 17.901 | 0.000 | 0.201 | 41.585 | 0.000 | -11.993 | 0.000 | -5.825 | -0.001 |
MECH_FLR_1 | 0.000 | 0.000 | 0.336 | -21.772 | 0.000 | 0.000 | 0.000 | 7.530 | 12.472 | 0.000 | 0.000 | 0.255 | 4.655 | 0.000 | 0.000 | 0.000 | -3.476 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.887 | -10.425 | 0.000 | 0.000 | 0.000 | 2.417 | 3.598 | 0.000 | 0.000 | 0.182 | 5.738 | 0.000 | 0.000 | 0.000 | -2.397 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 8.594 | -114.282 | 0.000 | 0.000 | 0.000 | 109.607 | 0.000 | 35.409 | 0.000 | 0.941 | 0.002 | 0.000 | -28.014 | 0.000 | -10.561 | -1.693 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 2.731 | -72.843 | 0.000 | 0.000 | 0.000 | 29.000 | 0.000 | 16.740 | 0.000 | 0.289 | 41.720 | 0.000 | -12.877 | 0.000 | -4.761 | -0.001 |
Total Facility | 112.823 | -629.182 | 14.742 | -4121.044 | 0.000 | 0.000 | 1891.784 | 818.946 | 2451.865 | 708.243 | 0.000 | 29.760 | 93.886 | 0.000 | -605.100 | 0.000 | -292.627 | -474.068 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-NOV-22:00 | 0.00 | 0.00 | 0.00 | -19361.33 | 0.00 | 0.00 | 5924.41 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6436.65 |
RETAIL_1_FLR_1 | 13-OCT-12:30 | 0.00 | 0.00 | 0.00 | -3153.25 | 0.00 | 0.00 | 150.60 | 172.19 | 252.59 | 5369.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -41.09 | -2750.39 |
RETAIL_2_FLR_1 | 24-AUG-20:30 | 0.00 | 0.00 | 0.00 | -1759.90 | 0.00 | 0.00 | 708.30 | 638.05 | 752.15 | 0.00 | 0.00 | 13.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -351.75 |
LAUNDRY_FLR_1 | 04-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38277.12 | 0.00 | 0.00 | 408.89 | 292.58 | 44299.38 | 0.00 | 0.00 | 119.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6842.94 |
CAFE_FLR_1 | 30-SEP-12:30 | 0.00 | 0.00 | 0.00 | -11652.82 | 0.00 | 0.00 | 2968.65 | 259.48 | 355.63 | 14039.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -221.35 | -5748.81 |
LOBBY_FLR_1 | 24-AUG-20:30 | 0.00 | 0.00 | 0.00 | -36757.11 | 0.00 | 0.00 | 23505.28 | 10746.77 | 9501.36 | 15.20 | 0.00 | 291.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7303.24 |
ROOM_1_FLR_3 | 04-AUG-15:02 | 0.00 | -11449.71 | 0.00 | -751.55 | 0.00 | 0.00 | 235.28 | 74.52 | 273.93 | 7286.42 | 0.00 | 220.22 | 4110.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 16-AUG-15:02 | 0.00 | -11335.59 | 0.00 | -751.81 | 0.00 | 0.00 | 235.28 | 74.51 | 273.90 | 7381.81 | 0.00 | 245.71 | 3876.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:00 | 0.00 | -45981.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.15 | 5097.90 | 62799.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -334.12 | -22277.35 |
ROOM_4_MULT19_FLR_3 | 11-JUL-18:02 | 0.00 | -68472.21 | 0.00 | -10318.54 | 0.00 | 0.00 | 6374.47 | 9873.76 | 9610.21 | 6845.27 | 0.00 | 552.19 | 45534.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUL-08:62 | 0.00 | -10398.04 | 0.00 | -760.11 | 0.00 | 0.00 | 87.14 | 407.51 | 453.05 | 9165.16 | 0.00 | 138.00 | 907.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 22-AUG-08:62 | 0.00 | -10248.58 | 0.00 | -760.05 | 0.00 | 0.00 | 87.14 | 407.46 | 452.99 | 9358.67 | 0.00 | 108.41 | 593.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 02-AUG-15:02 | 0.00 | -3028.74 | 0.00 | -190.03 | 0.00 | 0.00 | 58.82 | 18.63 | 68.48 | 2229.14 | 0.00 | 50.82 | 792.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 02-AUG-15:02 | 0.00 | -2957.16 | 0.00 | -190.04 | 0.00 | 0.00 | 58.82 | 18.63 | 68.48 | 2181.71 | 0.00 | 50.83 | 768.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 24-AUG-15:02 | 0.00 | -12694.93 | 0.00 | -1225.61 | 0.00 | 0.00 | 529.36 | 105.40 | 603.86 | 4327.91 | 0.00 | 330.01 | 8024.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -22423.67 | 0.00 | 0.00 | 15645.51 | 1792.82 | 6747.90 | 407.67 | 0.00 | 120.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2291.07 |
DINING_FLR_6 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -23893.62 | 0.00 | 0.00 | 15645.38 | 1792.82 | 6747.90 | 390.86 | 0.00 | 120.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -804.18 |
KITCHEN_FLR_6 | 22-AUG-17:56 | 0.00 | 0.00 | 0.00 | -31521.04 | 0.00 | 0.00 | 765.40 | 636.49 | 26759.11 | 590.24 | 0.00 | 50.71 | 2719.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -1240.60 | 0.00 | 0.00 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 18.62 | 192.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -671.65 | 0.00 | 0.00 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 63.35 | 298.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 24-AUG-19:10 | 0.00 | 0.00 | 0.00 | -7867.74 | 0.00 | 0.00 | 0.00 | 8963.14 | 0.00 | 639.09 | 0.00 | 233.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1967.97 |
CORRIDOR_FLR_6 | 18-AUG-13:50 | 0.00 | 0.00 | 0.00 | -4523.43 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 2188.25 | 0.00 | 137.33 | 1539.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-18:02 | 0.00 | -154653.60 | 0.00 | -189116.80 | 0.00 | 0.00 | 71662.52 | 62671.50 | 122326.88 | 32803.44 | 0.00 | 4708.21 | 49597.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 06-FEB-07:15 | 0.00 | 0.00 | 1565.23 | -0.00 | 0.00 | 0.00 | 362.54 | 344.37 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.93 | 0.00 | -887.80 | -695.42 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 14-JAN-17:00 | 0.00 | 0.00 | 1205.60 | -0.00 | 0.00 | 0.00 | 3528.15 | 425.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3310.66 | 0.00 | -1788.58 | -415.52 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JAN-16:13 | 6615.04 | 373.58 | 0.00 | -373.58 | 0.00 | 0.00 | 148.35 | 58.22 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2621.00 | 0.00 | -818.67 | -3687.48 |
ROOM_2_FLR_3 | 06-FEB-16:12 | 6619.31 | 379.16 | 0.00 | -379.16 | 0.00 | 0.00 | 266.38 | 74.51 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2340.43 | 0.00 | -830.11 | -4063.56 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:02 | 36492.99 | 3802.89 | 0.00 | -3802.89 | 0.00 | 0.00 | 5580.23 | 890.03 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13117.71 | 0.00 | -4206.84 | -30737.99 |
ROOM_5_FLR_3 | 14-JAN-16:13 | 6365.71 | 367.42 | 0.00 | -367.42 | 0.00 | 0.00 | 148.57 | 58.22 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2662.02 | 0.00 | -816.15 | -3399.86 |
ROOM_6_FLR_3 | 14-JAN-16:13 | 6370.87 | 365.50 | 0.00 | -365.50 | 0.00 | 0.00 | 148.84 | 58.21 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2676.40 | 0.00 | -815.31 | -3391.71 |
ROOM_1_FLR_6 | 14-JAN-16:13 | 1932.32 | 90.68 | 0.00 | -90.68 | 0.00 | 0.00 | 37.35 | 14.55 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -652.26 | 0.00 | -204.07 | -1204.28 |
ROOM_2_FLR_6 | 06-FEB-16:12 | 1932.41 | 92.70 | 0.00 | -92.70 | 0.00 | 0.00 | 66.64 | 18.63 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -586.21 | 0.00 | -207.19 | -1292.76 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:13 | 8567.60 | 570.41 | 0.00 | -570.41 | 0.00 | 0.00 | 337.41 | 82.34 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3048.23 | 0.00 | -936.00 | -5676.65 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 618.64 | -0.00 | 0.00 | 0.00 | 0.00 | 68.42 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.32 | -451.46 |
STORAGE_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 552.34 | -0.00 | 0.00 | 0.00 | 0.00 | 21.96 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -286.01 | -339.27 |
CORRIDOR_FLR_3 | 02-JAN-05:00 | 0.00 | 0.00 | 3814.98 | -0.00 | 0.00 | 0.00 | 0.00 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 479.05 | 0.00 | -4028.69 | 0.00 | -1261.24 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-05:10 | 0.00 | 0.00 | 2861.43 | -0.00 | 0.00 | 0.00 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1798.40 | 0.00 | -560.17 | -1029.87 |
Total Facility | 14-JAN-16:13 | -1268.94 | 82332.17 | 8694.32 | -82332.17 | 0.00 | 0.00 | 33276.21 | 14321.33 | 78718.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60975.48 | 0.00 | -23087.51 | -49678.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.2958 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 19.9243 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.0557 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 12.0557 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2529 | 2.2529 | 1.3382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2918 | 0.2918 | 0.1733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2194 | 0.2194 | 0.1303 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2525 | 3.2525 | 1.9320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2778 | 1.2778 | 0.7590 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4927 | 4.4927 | 2.6686 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0791 | 2.0791 | 1.2350 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1824 | 2.1824 | 1.2963 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2217 | 2.2217 | 1.3197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1649 | 0.1649 | 0.0980 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0915 | 0.0915 | 0.0543 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.7050 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5822 | 0.5822 | 0.3458 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.2958 | 19.9243 | 20.2958 | 12.0557 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3382 | 1.3382 | 1.3382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1733 | 0.1733 | 0.1733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1303 | 0.1303 | 0.1303 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9320 | 1.9320 | 1.9320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7590 | 0.7590 | 0.7590 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6686 | 2.6686 | 2.6686 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2350 | 1.2350 | 1.2350 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2963 | 1.2963 | 1.2963 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3197 | 1.3197 | 1.3197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0980 | 0.0980 | 0.0980 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0543 | 0.0543 | 0.0543 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7050 | 0.7050 | 0.7050 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3458 | 0.3458 | 0.3458 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.0557 | 12.0557 | 12.0557 | 12.0557 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:45:23
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 9.50 |
Number of hours cooling loads not met | 258.83 |
Number of hours not met | 268.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 879.99 | 230358.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1232.65 | 192755.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 818.95 | 73068.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 163.14 | 10390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.84 | 1321.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 548.85 | 29140.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 82.68 | 5496.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 215.39 | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4738.76 | 2126.59 | 177769.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.31 | 1935.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.17 | 1198.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.60 | 5932.30 |
Natural Gas | 1788.85 | 4795.43 |
Additional | 0.00 | 0.00 |
Total | 3595.45 | 10727.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.18 |
Space Heating | 0.00 |
Space Cooling | 108.65 |
Fans (All) | 48.38 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 522.89 |
Subtotal | 522.89 |
Natural Gas [MJ/m2] | |
Space Heating | 77.56 |
Service Water Heating | 187.44 |
Miscellaneous (All) | 422.68 |
Subtotal | 422.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.63 |
Space Heating | 8.20 |
Space Cooling | 11.49 |
Fans (All) | 5.12 |
Service Water Heating | 20.67 |
Receptacle Equipment | 32.94 |
Miscellaneous | 13.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2739. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.178464E+12 |
February | 0.000 | 0.155385E+12 |
March | 0.000 | 0.876374E+11 |
April | 0.000 | 0.793821E+11 |
May | 0.000 | 0.439296E+11 |
June | 0.000 | 0.157291E+11 |
July | 0.000 | 0.122657E+11 |
August | 0.000 | 0.991744E+10 |
September | 0.000 | 0.194780E+11 |
October | 0.000 | 0.569456E+11 |
November | 0.000 | 0.111491E+12 |
December | 0.000 | 0.109365E+12 |
Annual Sum or Average | 0.879991E+12 | |
Minimum of Months | 0.000 | 0.991744E+10 |
Maximum of Months | 0.000 | 0.178464E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328401E+11 | 13627.74 | 23-JAN-22:10 | 10.60 | 10.26 | 0.762711E+10 | 4768.41 | 20-JAN-22:10 | 3.72 | 3.02 |
February | 0.279683E+11 | 13301.54 | 01-FEB-22:10 | 4.90 | 2.78 | 0.662578E+10 | 4714.82 | 01-FEB-22:10 | 4.90 | 2.78 |
March | 0.298597E+11 | 14330.36 | 27-MAR-18:40 | 18.50 | 13.64 | 0.708698E+10 | 4462.78 | 01-MAR-22:10 | 5.50 | 4.48 |
April | 0.289302E+11 | 15021.89 | 07-APR-20:10 | 21.32 | 14.58 | 0.654921E+10 | 4320.66 | 04-APR-21:10 | 8.40 | 6.25 |
May | 0.303155E+11 | 14299.34 | 09-MAY-19:00 | 21.10 | 14.08 | 0.641785E+10 | 4151.94 | 01-MAY-21:10 | 9.50 | 5.24 |
June | 0.325706E+11 | 15084.48 | 22-JUN-20:30 | 26.40 | 16.43 | 0.611463E+10 | 3990.27 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.364961E+11 | 15117.92 | 13-JUL-21:10 | 27.12 | 23.29 | 0.634275E+10 | 3969.03 | 14-JUL-21:10 | 21.70 | 20.94 |
August | 0.386554E+11 | 16152.98 | 24-AUG-20:30 | 26.40 | 15.68 | 0.664287E+10 | 4162.65 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.382304E+11 | 16748.47 | 27-SEP-19:40 | 20.77 | 15.39 | 0.685924E+10 | 4626.69 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.393569E+11 | 18871.03 | 31-OCT-21:00 | 13.90 | 12.26 | 0.781884E+10 | 4837.03 | 30-OCT-22:10 | 8.22 | 4.04 |
November | 0.368534E+11 | 19360.65 | 22-NOV-22:00 | -1.1 | -3.3 | 0.784506E+10 | 4837.00 | 29-NOV-22:19 | 4.13 | 3.66 |
December | 0.355835E+11 | 18505.93 | 01-DEC-22:00 | 1.10 | -2.0 | 0.799852E+10 | 4837.07 | 19-DEC-23:10 | 4.60 | 3.30 |
Annual Sum or Average | 0.407660E+12 | 0.839288E+11 | ||||||||
Minimum of Months | 0.279683E+11 | 13301.54 | -1.1 | -3.3 | 0.611463E+10 | 3969.03 | 3.72 | 2.78 | ||
Maximum of Months | 0.393569E+11 | 19360.65 | 27.12 | 23.29 | 0.799852E+10 | 4837.07 | 22.52 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661412E+09 | 2122.66 | 17-JAN-13:10 | 10.18 | 5.49 | 0.622494E+09 | 364.14 | 04-JAN-04:49 | -2.6 | -4.7 |
February | 0.807352E+09 | 1745.33 | 02-FEB-13:30 | 6.15 | 0.23 | 0.564271E+09 | 364.13 | 06-FEB-01:00 | -13.3 | -14.8 |
March | 0.150985E+10 | 2392.80 | 03-MAR-13:20 | 14.60 | 8.22 | 0.629670E+09 | 403.28 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.214401E+10 | 2297.52 | 08-APR-12:40 | 23.33 | 16.14 | 0.608284E+09 | 415.15 | 07-APR-21:10 | 19.22 | 13.75 |
May | 0.331019E+10 | 2042.15 | 30-MAY-15:10 | 28.30 | 17.25 | 0.629927E+09 | 410.28 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.438392E+10 | 2229.87 | 19-JUN-19:20 | 31.13 | 22.28 | 0.627458E+09 | 455.73 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.510108E+10 | 2248.25 | 08-JUL-12:40 | 31.47 | 25.92 | 0.672202E+09 | 455.73 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.527040E+10 | 2356.83 | 22-AUG-13:00 | 30.60 | 18.59 | 0.696983E+09 | 475.06 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.432523E+10 | 2855.21 | 30-SEP-12:40 | 20.40 | 12.34 | 0.638868E+09 | 455.09 | 01-SEP-21:10 | 26.60 | 18.07 |
October | 0.394966E+10 | 3153.26 | 13-OCT-12:30 | 22.25 | 17.93 | 0.663640E+09 | 433.75 | 04-OCT-21:10 | 17.12 | 15.79 |
November | 0.168880E+10 | 2651.44 | 02-NOV-12:40 | 15.40 | 8.12 | 0.608472E+09 | 406.01 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 0.101434E+10 | 2780.28 | 17-DEC-12:40 | 12.20 | 4.78 | 0.625443E+09 | 364.12 | 28-DEC-03:39 | 1.30 | -0.3 |
Annual Sum or Average | 0.341663E+11 | 0.758771E+10 | ||||||||
Minimum of Months | 0.661412E+09 | 1745.33 | 6.15 | 0.23 | 0.564271E+09 | 364.12 | -13.3 | -14.8 | ||
Maximum of Months | 0.527040E+10 | 3153.26 | 31.47 | 25.92 | 0.696983E+09 | 475.06 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228637E+10 | 1166.21 | 19-JAN-22:10 | 5.60 | 1.05 | 0.757597E+09 | 513.41 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.210873E+10 | 1140.57 | 22-FEB-22:10 | 2.20 | -0.9 | 0.688438E+09 | 505.94 | 02-FEB-22:10 | -2.3 | -5.7 |
March | 0.265701E+10 | 1390.22 | 27-MAR-19:00 | 18.30 | 13.17 | 0.796134E+09 | 535.10 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.282227E+10 | 1616.24 | 07-APR-20:10 | 21.32 | 14.58 | 0.778889E+09 | 533.81 | 11-APR-21:10 | 9.22 | 1.64 |
May | 0.330041E+10 | 1630.92 | 31-MAY-21:00 | 20.60 | 17.62 | 0.805983E+09 | 532.00 | 11-MAY-21:10 | 12.20 | 10.07 |
June | 0.365806E+10 | 1701.99 | 19-JUN-21:10 | 28.72 | 20.61 | 0.783348E+09 | 537.49 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.398259E+10 | 1721.95 | 10-JUL-21:10 | 27.12 | 20.10 | 0.818867E+09 | 544.05 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.403891E+10 | 1759.89 | 24-AUG-20:30 | 26.40 | 15.68 | 0.841615E+09 | 553.01 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.358532E+10 | 1711.78 | 01-SEP-21:10 | 26.60 | 18.07 | 0.788495E+09 | 541.77 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.336211E+10 | 1605.99 | 05-OCT-21:10 | 18.90 | 17.74 | 0.837770E+09 | 548.16 | 30-OCT-21:10 | 8.80 | 3.74 |
November | 0.264172E+10 | 1364.27 | 03-NOV-21:10 | 12.80 | 10.16 | 0.771375E+09 | 537.38 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 0.248429E+10 | 1180.22 | 18-DEC-22:10 | 2.20 | 0.94 | 0.775315E+09 | 516.38 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.369278E+11 | 0.944383E+10 | ||||||||
Minimum of Months | 0.210873E+10 | 1140.57 | 2.20 | -0.9 | 0.688438E+09 | 505.94 | -2.3 | -5.7 | ||
Maximum of Months | 0.403891E+10 | 1759.89 | 28.72 | 20.61 | 0.841615E+09 | 553.01 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537063E+09 | 710.92 | 23-JAN-22:10 | 10.60 | 10.26 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.444481E+09 | 674.90 | 24-FEB-22:10 | 0.32 | -3.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.116321E+10 | 935.86 | 27-MAR-17:40 | 19.63 | 14.87 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.165912E+10 | 1079.63 | 07-APR-20:10 | 21.32 | 14.58 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.226633E+10 | 1127.76 | 31-MAY-21:00 | 20.60 | 17.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.267081E+10 | 1190.81 | 22-JUN-20:30 | 26.40 | 16.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.295963E+10 | 1225.98 | 10-JUL-21:10 | 27.12 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.297026E+10 | 1240.62 | 18-AUG-21:10 | 24.82 | 17.57 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.256820E+10 | 1187.48 | 01-SEP-21:10 | 26.60 | 18.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.226654E+10 | 1072.17 | 05-OCT-21:10 | 18.90 | 17.74 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.139904E+10 | 919.33 | 04-NOV-13:00 | 17.80 | 12.72 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.866927E+09 | 703.67 | 19-DEC-22:10 | 5.40 | 2.50 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.217716E+11 | 0.00 | ||||||||
Minimum of Months | 0.444481E+09 | 674.90 | 0.32 | -3.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.297026E+10 | 1240.62 | 27.12 | 20.10 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83172854.00 | 354.66 | 19-JAN-22:00 | 5.60 | 1.05 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 60671454.30 | 229.16 | 23-FEB-22:00 | 4.40 | 3.44 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.365469E+09 | 500.23 | 27-MAR-18:50 | 18.40 | 13.40 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.728237E+09 | 577.40 | 07-APR-20:10 | 21.32 | 14.58 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.118067E+10 | 600.06 | 31-MAY-21:00 | 20.60 | 17.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.145513E+10 | 640.62 | 19-JUN-21:10 | 28.72 | 20.61 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.162188E+10 | 660.84 | 10-JUL-21:10 | 27.12 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.162538E+10 | 671.66 | 04-AUG-21:10 | 31.55 | 23.91 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.138825E+10 | 639.17 | 01-SEP-21:10 | 26.60 | 18.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.120177E+10 | 580.63 | 05-OCT-13:50 | 23.22 | 18.90 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.550865E+09 | 505.05 | 04-NOV-13:00 | 17.80 | 12.72 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.163040E+09 | 361.84 | 19-DEC-22:10 | 5.40 | 2.50 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.104245E+11 | 0.00 | ||||||||
Minimum of Months | 60671454.30 | 229.16 | 4.40 | 1.05 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.162538E+10 | 671.66 | 31.55 | 23.91 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481686E+11 | 35953.63 | 19-JAN-21:00 | 3.90 | 0.78 | 0.563312E+09 | 397.71 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.434914E+11 | 35828.05 | 17-FEB-21:00 | 1.10 | -0.7 | 0.509638E+09 | 396.06 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.495761E+11 | 36897.23 | 27-MAR-20:00 | 16.10 | 12.01 | 0.568703E+09 | 399.65 | 15-MAR-21:10 | 9.82 | 3.27 |
April | 0.488945E+11 | 37580.52 | 07-APR-20:00 | 21.70 | 14.71 | 0.543792E+09 | 401.50 | 11-APR-21:10 | 9.22 | 1.64 |
May | 0.519917E+11 | 37740.43 | 31-MAY-20:00 | 20.00 | 17.80 | 0.548009E+09 | 400.19 | 01-MAY-21:10 | 9.50 | 5.24 |
June | 0.515082E+11 | 38126.64 | 19-JUN-20:00 | 30.00 | 21.99 | 0.518219E+09 | 381.53 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.537286E+11 | 38113.79 | 10-JUL-20:00 | 28.30 | 20.23 | 0.530055E+09 | 381.50 | 11-JUL-21:30 | 22.80 | 17.56 |
August | 0.541103E+11 | 38277.18 | 04-AUG-20:00 | 32.20 | 24.20 | 0.534507E+09 | 381.58 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.510299E+11 | 37987.28 | 01-SEP-20:00 | 26.70 | 17.85 | 0.520394E+09 | 381.68 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.516615E+11 | 37550.52 | 04-OCT-20:00 | 18.90 | 16.05 | 0.553752E+09 | 401.25 | 26-OCT-21:10 | 8.22 | 3.58 |
November | 0.481632E+11 | 36904.36 | 03-NOV-20:00 | 12.80 | 10.92 | 0.546959E+09 | 399.69 | 01-NOV-21:10 | 9.90 | 5.48 |
December | 0.486483E+11 | 36006.68 | 19-DEC-21:00 | 8.30 | 3.93 | 0.565778E+09 | 397.47 | 20-DEC-22:10 | 4.32 | 1.21 |
Annual Sum or Average | 0.600972E+12 | 0.650312E+10 | ||||||||
Minimum of Months | 0.434914E+11 | 35828.05 | 1.10 | -0.7 | 0.509638E+09 | 381.50 | 2.02 | 0.23 | ||
Maximum of Months | 0.541103E+11 | 38277.18 | 32.20 | 24.20 | 0.568703E+09 | 401.50 | 22.80 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122673E+11 | 8987.63 | 17-JAN-13:00 | 10.00 | 5.55 | 0.865019E+10 | 5979.72 | 19-JAN-22:40 | 5.60 | 1.05 |
February | 0.118724E+11 | 8104.91 | 20-FEB-13:00 | 9.40 | 4.35 | 0.788105E+10 | 5816.73 | 22-FEB-22:40 | 2.20 | -0.7 |
March | 0.151349E+11 | 9813.40 | 03-MAR-13:10 | 14.50 | 8.12 | 0.919085E+10 | 6372.36 | 03-MAR-22:40 | 10.20 | 6.22 |
April | 0.162821E+11 | 10012.90 | 08-APR-12:40 | 23.33 | 16.14 | 0.900396E+10 | 6208.64 | 07-APR-22:10 | 18.22 | 13.38 |
May | 0.194132E+11 | 9676.10 | 31-MAY-21:20 | 20.37 | 17.53 | 0.940771E+10 | 6117.58 | 15-MAY-22:10 | 10.60 | 7.46 |
June | 0.218595E+11 | 10530.79 | 19-JUN-21:20 | 28.53 | 20.49 | 0.923524E+10 | 6458.54 | 19-JUN-21:40 | 28.17 | 20.25 |
July | 0.241568E+11 | 10475.82 | 10-JUL-21:30 | 26.95 | 19.91 | 0.972509E+10 | 6449.22 | 10-JUL-21:40 | 26.87 | 19.81 |
August | 0.246533E+11 | 11442.15 | 04-AUG-21:10 | 31.55 | 23.91 | 0.100097E+11 | 6462.07 | 04-AUG-22:19 | 28.30 | 23.79 |
September | 0.219194E+11 | 11653.04 | 30-SEP-12:30 | 20.30 | 12.31 | 0.939601E+10 | 6459.84 | 01-SEP-21:00 | 26.10 | 17.38 |
October | 0.210314E+11 | 11503.40 | 13-OCT-12:30 | 22.25 | 17.93 | 0.997948E+10 | 6428.38 | 13-OCT-21:40 | 14.80 | 14.80 |
November | 0.153749E+11 | 10858.14 | 04-NOV-12:30 | 17.80 | 12.60 | 0.890814E+10 | 6362.03 | 02-NOV-22:10 | 11.60 | 6.69 |
December | 0.138573E+11 | 11637.63 | 17-DEC-12:40 | 12.20 | 4.78 | 0.888731E+10 | 5932.84 | 18-DEC-22:40 | 2.20 | 0.71 |
Annual Sum or Average | 0.217823E+12 | 0.110275E+12 | ||||||||
Minimum of Months | 0.118724E+11 | 8104.91 | 9.40 | 4.35 | 0.788105E+10 | 5816.73 | 2.20 | -0.7 | ||
Maximum of Months | 0.246533E+11 | 11653.04 | 31.55 | 23.91 | 0.100097E+11 | 6462.07 | 28.30 | 23.79 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535268E+11 | 26111.76 | 19-JAN-22:10 | 5.60 | 1.05 | 0.271785E+11 | 18469.68 | 19-JAN-23:10 | 5.60 | 1.05 |
February | 0.491911E+11 | 25470.08 | 22-FEB-22:10 | 2.20 | -0.9 | 0.247066E+11 | 18128.47 | 22-FEB-23:10 | 2.20 | -0.6 |
March | 0.591888E+11 | 29904.15 | 27-MAR-19:00 | 18.30 | 13.17 | 0.285038E+11 | 19127.95 | 03-MAR-23:10 | 9.82 | 6.11 |
April | 0.618062E+11 | 34201.07 | 07-APR-20:20 | 20.93 | 14.44 | 0.277334E+11 | 18830.20 | 11-APR-21:40 | 8.67 | 1.36 |
May | 0.711511E+11 | 34313.51 | 31-MAY-21:10 | 20.48 | 17.57 | 0.285272E+11 | 18775.55 | 15-MAY-22:10 | 10.60 | 7.46 |
June | 0.774721E+11 | 35875.93 | 22-JUN-20:30 | 26.40 | 16.43 | 0.274523E+11 | 18565.04 | 19-JUN-22:10 | 27.62 | 20.12 |
July | 0.838863E+11 | 36136.36 | 10-JUL-21:10 | 27.12 | 20.10 | 0.285583E+11 | 18749.14 | 10-JUL-22:10 | 26.52 | 19.57 |
August | 0.846767E+11 | 36755.02 | 24-AUG-20:30 | 26.40 | 15.68 | 0.291959E+11 | 19033.01 | 04-AUG-21:30 | 30.25 | 24.02 |
September | 0.764789E+11 | 36005.59 | 01-SEP-21:10 | 26.60 | 18.07 | 0.277339E+11 | 18966.00 | 29-SEP-22:10 | 13.12 | 10.81 |
October | 0.728151E+11 | 34109.13 | 05-OCT-21:10 | 18.90 | 17.74 | 0.296628E+11 | 19183.90 | 30-OCT-21:40 | 8.50 | 4.05 |
November | 0.591449E+11 | 29765.27 | 03-NOV-21:10 | 12.80 | 10.16 | 0.277321E+11 | 19154.91 | 02-NOV-22:10 | 11.60 | 6.69 |
December | 0.566787E+11 | 26274.06 | 18-DEC-22:10 | 2.20 | 0.94 | 0.279159E+11 | 18478.66 | 18-DEC-23:10 | 2.30 | 0.66 |
Annual Sum or Average | 0.806017E+12 | 0.334901E+12 | ||||||||
Minimum of Months | 0.491911E+11 | 25470.08 | 2.20 | -0.9 | 0.247066E+11 | 18128.47 | 2.20 | -0.6 | ||
Maximum of Months | 0.846767E+11 | 36755.02 | 27.12 | 20.10 | 0.296628E+11 | 19183.90 | 30.25 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16580144.27 | 2701.16 | 19-JAN-16:01 | 8.22 | 2.83 | 93756305.39 | 56.69 | 06-JAN-04:19 | -6.9 | -8.1 |
February | 29452991.61 | 2709.34 | 22-FEB-16:01 | 4.22 | -0.4 | 85135624.83 | 56.69 | 06-FEB-23:19 | -8.3 | -10.2 |
March | 0.182248E+09 | 2737.57 | 27-MAR-18:01 | 18.80 | 14.34 | 95902033.16 | 56.69 | 27-MAR-21:19 | 13.87 | 10.66 |
April | 0.448996E+09 | 2835.66 | 10-APR-18:02 | 19.22 | 9.98 | 93626503.41 | 56.69 | 27-APR-21:40 | 14.40 | 12.93 |
May | 0.920154E+09 | 2994.58 | 20-MAY-18:01 | 22.02 | 11.69 | 98145874.47 | 56.69 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.156959E+10 | 3025.31 | 26-JUN-15:02 | 27.02 | 19.73 | 95713149.89 | 56.70 | 22-JUN-21:49 | 25.18 | 16.03 |
July | 0.200431E+10 | 3022.72 | 13-JUL-15:02 | 30.32 | 24.43 | 99029598.51 | 56.70 | 20-JUL-21:49 | 26.78 | 24.77 |
August | 0.213215E+10 | 3050.09 | 04-AUG-15:02 | 31.02 | 25.37 | 99109774.17 | 56.70 | 01-AUG-22:10 | 26.02 | 21.69 |
September | 0.128299E+10 | 3019.99 | 07-SEP-15:02 | 26.60 | 22.96 | 95358934.77 | 56.70 | 01-SEP-21:40 | 26.30 | 17.66 |
October | 0.833814E+09 | 2868.04 | 02-OCT-15:02 | 22.88 | 16.76 | 97961248.58 | 56.69 | 24-OCT-22:10 | 17.70 | 17.02 |
November | 0.106944E+09 | 2765.92 | 02-NOV-15:01 | 16.60 | 8.89 | 92368641.61 | 56.69 | 02-NOV-21:30 | 12.25 | 6.92 |
December | 22734141.75 | 2702.35 | 17-DEC-16:01 | 9.82 | 4.15 | 94255640.69 | 56.69 | 22-DEC-04:19 | -3.5 | -6.1 |
Annual Sum or Average | 0.954997E+10 | 0.114036E+10 | ||||||||
Minimum of Months | 16580144.27 | 2701.16 | 4.22 | -0.4 | 85135624.83 | 56.69 | -8.3 | -10.2 | ||
Maximum of Months | 0.213215E+10 | 3050.09 | 31.02 | 25.37 | 99109774.17 | 56.70 | 26.78 | 24.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5616459.85 | 2220.99 | 17-JAN-16:02 | 9.45 | 4.57 | 93003778.27 | 56.69 | 03-JAN-01:10 | -3.7 | -6.0 |
February | 8876850.64 | 2438.79 | 20-FEB-16:02 | 7.12 | 4.39 | 84166715.00 | 56.69 | 13-FEB-01:49 | -7.8 | -10.0 |
March | 0.103500E+09 | 2651.54 | 11-MAR-16:02 | 11.20 | 5.38 | 95018495.44 | 56.69 | 27-MAR-21:00 | 12.80 | 9.84 |
April | 0.361667E+09 | 2863.51 | 07-APR-15:02 | 25.60 | 15.96 | 93265978.93 | 56.69 | 27-APR-21:19 | 14.40 | 13.03 |
May | 0.871379E+09 | 2979.22 | 31-MAY-15:02 | 25.82 | 19.49 | 98050473.18 | 56.69 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.153379E+10 | 3011.24 | 26-JUN-15:02 | 27.02 | 19.73 | 95701227.29 | 56.70 | 22-JUN-21:49 | 25.18 | 16.03 |
July | 0.195011E+10 | 3014.05 | 13-JUL-15:02 | 30.32 | 24.43 | 99024769.09 | 56.70 | 20-JUL-21:40 | 26.87 | 24.85 |
August | 0.197737E+10 | 3021.63 | 16-AUG-15:02 | 32.02 | 25.34 | 99080360.73 | 56.70 | 03-AUG-21:49 | 25.68 | 24.72 |
September | 0.107676E+10 | 2974.43 | 06-SEP-15:02 | 26.02 | 20.14 | 95133301.74 | 56.69 | 21-SEP-21:19 | 21.50 | 20.44 |
October | 0.519823E+09 | 2903.42 | 25-OCT-15:01 | 23.03 | 10.38 | 97103395.29 | 56.69 | 05-OCT-21:49 | 18.90 | 17.51 |
November | 39061812.55 | 2673.85 | 02-NOV-15:01 | 16.60 | 8.89 | 91418518.10 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 5575050.58 | 1907.75 | 17-DEC-16:01 | 9.82 | 4.15 | 93185133.02 | 56.69 | 11-DEC-00:20 | 1.83 | 1.34 |
Annual Sum or Average | 0.845353E+10 | 0.113415E+10 | ||||||||
Minimum of Months | 5575050.58 | 1907.75 | 7.12 | 4.15 | 84166715.00 | 56.69 | -7.8 | -10.0 | ||
Maximum of Months | 0.197737E+10 | 3021.63 | 32.02 | 25.34 | 99080360.73 | 56.70 | 26.87 | 24.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8766207.33 | 144.20 | 31-JAN-15:15 | -1.5 | -5.7 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 26762364.23 | 265.15 | 03-FEB-12:30 | -1.4 | -4.9 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 62057591.69 | 333.77 | 03-MAR-13:30 | 14.70 | 8.31 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.135256E+09 | 427.68 | 07-APR-12:30 | 26.15 | 15.88 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.268066E+09 | 296.45 | 29-MAY-19:10 | 24.82 | 18.11 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.439846E+09 | 373.23 | 19-JUN-20:20 | 29.63 | 21.57 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.576883E+09 | 368.07 | 08-JUL-08:00 | 28.30 | 24.27 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.645632E+09 | 429.53 | 30-AUG-12:40 | 27.03 | 15.26 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.508069E+09 | 555.76 | 28-SEP-12:30 | 23.05 | 14.06 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.507094E+09 | 605.02 | 04-OCT-12:00 | 24.40 | 18.64 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.137307E+09 | 536.96 | 02-NOV-12:30 | 15.30 | 8.09 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 58132537.68 | 409.60 | 17-DEC-13:00 | 12.20 | 4.93 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.337387E+10 | 0.00 | ||||||||
Minimum of Months | 8766207.33 | 144.20 | -1.5 | -5.7 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.645632E+09 | 605.02 | 29.63 | 24.27 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50788606.78 | 816.11 | 21-JAN-09:02 | 1.97 | 1.97 | 94899716.49 | 56.69 | 23-JAN-22:30 | 10.60 | 10.26 |
February | 37475848.85 | 830.91 | 20-FEB-09:02 | 5.87 | 1.95 | 85660967.35 | 56.69 | 22-FEB-22:10 | 2.20 | -0.9 |
March | 0.164737E+09 | 888.15 | 28-MAR-18:02 | 10.00 | 6.78 | 96166531.30 | 56.69 | 03-MAR-22:00 | 10.00 | 6.11 |
April | 0.336460E+09 | 990.85 | 07-APR-15:02 | 25.60 | 15.96 | 93955752.66 | 56.69 | 10-APR-21:30 | 12.20 | 5.61 |
May | 0.563565E+09 | 1028.19 | 20-MAY-18:01 | 22.02 | 11.69 | 98094328.65 | 56.69 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.760096E+09 | 1029.94 | 22-JUN-18:02 | 28.72 | 17.26 | 95491404.25 | 56.69 | 19-JUN-22:10 | 27.62 | 20.12 |
July | 0.945869E+09 | 1036.72 | 11-JUL-18:02 | 26.73 | 16.70 | 98943320.19 | 57.84 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.893722E+09 | 1029.26 | 24-AUG-18:02 | 30.82 | 18.14 | 98925748.01 | 56.69 | 17-AUG-21:49 | 26.97 | 20.75 |
September | 0.628274E+09 | 1023.08 | 10-SEP-18:01 | 21.52 | 11.56 | 95050119.45 | 56.69 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.401971E+09 | 968.78 | 25-OCT-15:01 | 23.03 | 10.38 | 97306370.90 | 56.69 | 25-OCT-21:00 | 16.10 | 7.73 |
November | 0.183584E+09 | 874.37 | 03-NOV-15:02 | 16.83 | 10.86 | 93060460.65 | 56.69 | 09-NOV-22:10 | 12.20 | 12.20 |
December | 62902488.55 | 823.89 | 17-DEC-09:02 | 6.05 | 2.93 | 95146721.18 | 56.69 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.502945E+10 | 0.114270E+10 | ||||||||
Minimum of Months | 37475848.85 | 816.11 | 1.97 | 1.95 | 85660967.35 | 56.69 | 2.20 | -0.9 | ||
Maximum of Months | 0.945869E+09 | 1036.72 | 30.82 | 18.14 | 98943320.19 | 57.84 | 27.62 | 23.68 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21907382.94 | 2221.18 | 17-JAN-16:02 | 9.45 | 4.57 | 93766911.75 | 56.69 | 05-JAN-03:30 | -7.2 | -9.0 |
February | 31496516.05 | 2353.88 | 25-FEB-09:02 | -2.0 | -5.2 | 85246711.92 | 56.69 | 09-FEB-03:39 | -8.3 | -10.0 |
March | 0.151811E+09 | 2464.47 | 29-MAR-08:62 | 4.60 | 2.26 | 95958286.85 | 56.69 | 27-MAR-21:19 | 13.87 | 10.66 |
April | 0.447434E+09 | 2637.12 | 07-APR-15:02 | 25.60 | 15.96 | 93866007.81 | 56.69 | 06-APR-22:10 | 15.73 | 13.11 |
May | 0.947208E+09 | 2692.84 | 20-MAY-18:01 | 22.02 | 11.69 | 98367459.63 | 56.69 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.147046E+10 | 2743.84 | 26-JUN-08:61 | 24.08 | 18.29 | 95791220.08 | 56.69 | 22-JUN-21:49 | 25.18 | 16.03 |
July | 0.196611E+10 | 2789.45 | 14-JUL-08:62 | 27.98 | 20.72 | 99090917.88 | 56.70 | 17-JUL-22:10 | 25.00 | 22.24 |
August | 0.210074E+10 | 2774.17 | 22-AUG-08:62 | 26.88 | 18.43 | 99213574.71 | 56.70 | 01-AUG-22:10 | 26.02 | 21.69 |
September | 0.128846E+10 | 2720.90 | 06-SEP-08:61 | 24.18 | 18.62 | 95496620.42 | 56.69 | 01-SEP-22:10 | 26.10 | 17.29 |
October | 0.789531E+09 | 2646.81 | 04-OCT-15:02 | 23.72 | 19.11 | 98156167.32 | 56.69 | 11-OCT-21:49 | 16.10 | 14.77 |
November | 0.138178E+09 | 2505.50 | 02-NOV-15:01 | 16.60 | 8.89 | 92582480.06 | 56.69 | 02-NOV-21:40 | 12.07 | 6.86 |
December | 38009705.72 | 2391.03 | 17-DEC-09:02 | 6.05 | 2.93 | 94324578.12 | 56.69 | 11-DEC-00:20 | 1.83 | 1.34 |
Annual Sum or Average | 0.939136E+10 | 0.114186E+10 | ||||||||
Minimum of Months | 21907382.94 | 2221.18 | -2.0 | -5.2 | 85246711.92 | 56.69 | -8.3 | -10.0 | ||
Maximum of Months | 0.210074E+10 | 2789.45 | 27.98 | 20.72 | 99213574.71 | 56.70 | 26.10 | 22.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5477918.90 | 802.21 | 19-JAN-09:02 | 4.97 | 3.19 | 93018642.87 | 56.69 | 06-JAN-01:30 | -5.3 | -7.1 |
February | 8641887.55 | 2219.85 | 25-FEB-09:02 | -2.0 | -5.2 | 84256073.75 | 56.69 | 13-FEB-00:20 | -7.4 | -9.7 |
March | 79874289.42 | 2445.42 | 29-MAR-08:62 | 4.60 | 2.26 | 95012535.49 | 56.69 | 27-MAR-21:19 | 13.87 | 10.66 |
April | 0.357423E+09 | 2644.68 | 07-APR-15:02 | 25.60 | 15.96 | 93522474.98 | 56.69 | 07-APR-22:10 | 18.22 | 13.38 |
May | 0.896080E+09 | 2700.33 | 29-MAY-15:02 | 25.50 | 17.02 | 98302021.04 | 56.69 | 26-MAY-21:10 | 17.70 | 11.66 |
June | 0.143366E+10 | 2733.13 | 26-JUN-08:61 | 24.08 | 18.29 | 95781395.98 | 56.69 | 07-JUN-21:10 | 23.72 | 16.73 |
July | 0.191121E+10 | 2725.52 | 12-JUL-08:62 | 26.28 | 18.77 | 99086128.43 | 56.70 | 17-JUL-21:40 | 25.00 | 22.24 |
August | 0.194258E+10 | 2752.21 | 22-AUG-08:62 | 26.88 | 18.43 | 99203165.62 | 56.70 | 03-AUG-22:10 | 25.50 | 24.62 |
September | 0.107340E+10 | 2670.71 | 06-SEP-08:61 | 24.18 | 18.62 | 95347957.94 | 56.69 | 01-SEP-21:40 | 26.30 | 17.66 |
October | 0.468023E+09 | 2634.11 | 25-OCT-15:01 | 23.03 | 10.38 | 97311774.86 | 56.69 | 05-OCT-21:30 | 18.90 | 17.62 |
November | 54451499.19 | 2274.76 | 04-NOV-08:62 | 12.57 | 9.41 | 91627508.21 | 56.69 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 8040447.54 | 1933.41 | 17-DEC-09:02 | 6.05 | 2.93 | 93239777.36 | 56.69 | 15-DEC-04:19 | -2.8 | -5.1 |
Annual Sum or Average | 0.823886E+10 | 0.113571E+10 | ||||||||
Minimum of Months | 5477918.90 | 802.21 | -2.0 | -5.2 | 84256073.75 | 56.69 | -7.4 | -9.7 | ||
Maximum of Months | 0.194258E+10 | 2752.21 | 26.88 | 18.77 | 99203165.62 | 56.70 | 26.30 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256571E+09 | 1164.17 | 17-JAN-13:30 | 10.55 | 5.36 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.369990E+09 | 1161.71 | 20-FEB-13:00 | 9.40 | 4.35 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.109707E+10 | 1569.40 | 27-MAR-18:20 | 18.70 | 14.10 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.186621E+10 | 1828.20 | 08-APR-11:40 | 23.87 | 16.09 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.307227E+10 | 1862.08 | 30-MAY-19:20 | 21.13 | 15.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.405746E+10 | 1921.19 | 22-JUN-19:10 | 27.62 | 16.77 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.467376E+10 | 1932.03 | 10-JUL-20:00 | 28.30 | 20.23 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.475292E+10 | 1967.35 | 24-AUG-19:10 | 29.03 | 16.36 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.375844E+10 | 1901.27 | 01-SEP-21:10 | 26.60 | 18.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.310096E+10 | 1863.00 | 04-OCT-14:00 | 24.40 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.108778E+10 | 1617.85 | 04-NOV-12:50 | 17.80 | 12.68 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.477089E+09 | 1300.13 | 17-DEC-13:00 | 12.20 | 4.93 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.285705E+11 | 0.00 | ||||||||
Minimum of Months | 0.256571E+09 | 1161.71 | 9.40 | 4.35 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.475292E+10 | 1967.35 | 29.03 | 20.23 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14134941.35 | 2823.60 | 19-JAN-16:01 | 8.22 | 2.83 | 93279153.07 | 56.69 | 31-JAN-04:19 | -7.4 | -9.9 |
February | 28471408.93 | 2817.86 | 22-FEB-16:01 | 4.22 | -0.4 | 84719786.91 | 56.69 | 09-FEB-00:00 | -7.8 | -9.7 |
March | 0.184090E+09 | 2880.11 | 27-MAR-18:01 | 18.80 | 14.34 | 95588374.96 | 56.69 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.487638E+09 | 2967.39 | 10-APR-18:02 | 19.22 | 9.98 | 93505292.88 | 56.70 | 28-APR-23:40 | 10.00 | 7.10 |
May | 0.104762E+10 | 3139.73 | 20-MAY-18:01 | 22.02 | 11.69 | 98242805.12 | 56.70 | 12-MAY-02:30 | 11.70 | 9.89 |
June | 0.183914E+10 | 3175.85 | 25-JUN-15:02 | 26.60 | 22.70 | 95775077.00 | 56.70 | 23-JUN-21:49 | 22.80 | 21.14 |
July | 0.236964E+10 | 3167.70 | 13-JUL-18:02 | 27.12 | 23.28 | 99074400.45 | 56.70 | 21-JUL-22:10 | 25.50 | 23.96 |
August | 0.248485E+10 | 3218.71 | 02-AUG-15:02 | 30.50 | 25.54 | 99150152.15 | 56.70 | 08-AUG-02:30 | 16.10 | 13.31 |
September | 0.146350E+10 | 3129.53 | 14-SEP-18:02 | 27.70 | 18.24 | 95401489.42 | 56.70 | 18-SEP-04:00 | 17.80 | 16.39 |
October | 0.878766E+09 | 2927.89 | 30-OCT-15:01 | 16.52 | 8.25 | 97909596.83 | 56.70 | 17-OCT-22:19 | 9.23 | 3.92 |
November | 92282702.85 | 2889.99 | 02-NOV-15:01 | 16.60 | 8.89 | 91932311.21 | 56.69 | 03-NOV-21:30 | 12.80 | 10.23 |
December | 16686803.20 | 2823.36 | 17-DEC-16:01 | 9.82 | 4.15 | 93738216.14 | 56.69 | 31-DEC-03:30 | -0.9 | -3.4 |
Annual Sum or Average | 0.109068E+11 | 0.113832E+10 | ||||||||
Minimum of Months | 14134941.35 | 2817.86 | 4.22 | -0.4 | 84719786.91 | 56.69 | -7.8 | -9.9 | ||
Maximum of Months | 0.248485E+10 | 3218.71 | 30.50 | 25.54 | 99150152.15 | 56.70 | 25.50 | 23.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2461646.99 | 1535.35 | 17-JAN-16:02 | 9.45 | 4.57 | 92651942.57 | 56.69 | 08-JAN-00:49 | -4.4 | -7.0 |
February | 5012522.45 | 2466.24 | 20-FEB-16:02 | 7.12 | 4.39 | 83854750.05 | 56.69 | 14-FEB-00:20 | -3.7 | -6.1 |
March | 98037923.68 | 2805.38 | 27-MAR-18:01 | 18.80 | 14.34 | 94681436.92 | 56.69 | 27-MAR-21:19 | 13.87 | 10.66 |
April | 0.389719E+09 | 2926.39 | 07-APR-15:02 | 25.60 | 15.96 | 93159505.89 | 56.70 | 27-APR-01:49 | 13.30 | 11.63 |
May | 0.992686E+09 | 3096.06 | 20-MAY-18:01 | 22.02 | 11.69 | 98180525.28 | 56.70 | 03-MAY-00:30 | 12.20 | 7.93 |
June | 0.180262E+10 | 3137.61 | 15-JUN-15:02 | 26.52 | 22.44 | 95772367.60 | 56.70 | 23-JUN-21:00 | 22.80 | 21.20 |
July | 0.231396E+10 | 3129.33 | 13-JUL-18:02 | 27.12 | 23.28 | 99073216.93 | 56.70 | 21-JUL-21:00 | 25.60 | 23.90 |
August | 0.232000E+10 | 3147.19 | 02-AUG-15:02 | 30.50 | 25.54 | 99119858.61 | 56.70 | 14-AUG-21:40 | 24.60 | 21.35 |
September | 0.123178E+10 | 3112.55 | 07-SEP-15:02 | 26.60 | 22.96 | 95245433.98 | 56.70 | 01-SEP-21:30 | 26.40 | 17.80 |
October | 0.536500E+09 | 3008.03 | 04-OCT-15:02 | 23.72 | 19.11 | 97080320.62 | 56.69 | 05-OCT-21:40 | 18.90 | 17.57 |
November | 28975861.62 | 2760.94 | 02-NOV-15:01 | 16.60 | 8.89 | 90990632.39 | 56.70 | 03-NOV-21:40 | 12.80 | 10.26 |
December | 3459649.73 | 983.23 | 17-DEC-16:01 | 9.82 | 4.15 | 92725874.08 | 56.69 | 29-DEC-04:19 | -1.1 | -2.9 |
Annual Sum or Average | 0.972522E+10 | 0.113254E+10 | ||||||||
Minimum of Months | 2461646.99 | 983.23 | 7.12 | 4.15 | 83854750.05 | 56.69 | -4.4 | -7.0 | ||
Maximum of Months | 0.232000E+10 | 3147.19 | 30.50 | 25.54 | 99119858.61 | 56.70 | 26.40 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113540E+09 | 1384.47 | 19-JAN-16:01 | 8.22 | 2.83 | 95401312.83 | 56.69 | 19-JAN-22:30 | 5.60 | 1.05 |
February | 0.151655E+09 | 1375.81 | 02-FEB-16:02 | 4.13 | -1.9 | 86913416.89 | 56.69 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.258555E+09 | 1389.53 | 15-MAR-15:02 | 14.90 | 6.01 | 96833690.49 | 56.69 | 03-MAR-23:10 | 9.82 | 6.11 |
April | 0.366868E+09 | 1420.07 | 16-APR-15:01 | 21.60 | 13.93 | 94140152.63 | 56.69 | 07-APR-22:30 | 18.05 | 13.32 |
May | 0.628395E+09 | 1491.14 | 31-MAY-15:02 | 25.82 | 19.49 | 98332318.35 | 56.69 | 09-MAY-21:19 | 19.43 | 13.94 |
June | 0.101266E+10 | 1523.32 | 15-JUN-15:02 | 26.52 | 22.44 | 95724641.25 | 56.70 | 19-JUN-21:19 | 28.53 | 20.49 |
July | 0.137250E+10 | 1526.82 | 10-JUL-18:02 | 29.82 | 20.53 | 99102593.20 | 56.70 | 20-JUL-21:10 | 27.12 | 25.09 |
August | 0.146573E+10 | 1546.65 | 24-AUG-15:02 | 33.90 | 20.12 | 99178467.53 | 56.70 | 22-AUG-21:10 | 25.40 | 15.35 |
September | 0.108069E+10 | 1523.93 | 05-SEP-15:02 | 26.02 | 21.54 | 95558621.89 | 56.70 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.953639E+09 | 1505.57 | 04-OCT-15:02 | 23.72 | 19.11 | 98459388.54 | 56.69 | 04-OCT-22:00 | 17.80 | 16.06 |
November | 0.299803E+09 | 1407.93 | 02-NOV-15:01 | 16.60 | 8.89 | 94003704.11 | 56.69 | 06-NOV-22:10 | 8.12 | 5.60 |
December | 0.204846E+09 | 1389.20 | 17-DEC-16:01 | 9.82 | 4.15 | 95996512.40 | 56.69 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.790887E+10 | 0.114964E+10 | ||||||||
Minimum of Months | 0.113540E+09 | 1375.81 | 4.13 | -1.9 | 86913416.89 | 56.69 | 2.02 | 0.23 | ||
Maximum of Months | 0.146573E+10 | 1546.65 | 33.90 | 22.44 | 99178467.53 | 56.70 | 28.53 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311800E+11 | 17354.83 | 23-JAN-23:00 | 10.60 | 10.26 | 0.183406E+11 | 11347.90 | 27-JAN-00:20 | 1.10 | 0.39 |
February | 0.280290E+11 | 16696.56 | 23-FEB-23:00 | 5.00 | 4.23 | 0.165767E+11 | 11347.91 | 24-FEB-04:19 | 4.60 | 4.19 |
March | 0.336639E+11 | 18348.64 | 27-MAR-21:30 | 13.60 | 10.45 | 0.188312E+11 | 11348.14 | 27-MAR-00:20 | 8.90 | 8.42 |
April | 0.350794E+11 | 19485.59 | 07-APR-21:40 | 18.67 | 13.55 | 0.182340E+11 | 11348.17 | 24-APR-00:20 | 8.70 | 7.51 |
May | 0.395869E+11 | 20564.07 | 31-MAY-22:00 | 19.90 | 17.34 | 0.188046E+11 | 11348.08 | 15-MAY-00:20 | 10.20 | 7.19 |
June | 0.416169E+11 | 22010.97 | 19-JUN-21:10 | 28.72 | 20.61 | 0.181494E+11 | 11347.87 | 20-JUN-22:19 | 20.60 | 17.70 |
July | 0.445335E+11 | 22039.38 | 10-JUL-21:10 | 27.12 | 20.10 | 0.187349E+11 | 11347.85 | 11-JUL-22:19 | 22.43 | 17.95 |
August | 0.443412E+11 | 22421.60 | 04-AUG-21:10 | 31.55 | 23.91 | 0.188574E+11 | 11347.92 | 25-AUG-22:19 | 20.73 | 14.43 |
September | 0.399414E+11 | 21221.52 | 01-SEP-22:00 | 26.10 | 17.38 | 0.179811E+11 | 11347.98 | 29-SEP-03:20 | 11.87 | 8.31 |
October | 0.376610E+11 | 19342.49 | 05-OCT-22:00 | 18.90 | 17.45 | 0.186813E+11 | 11348.01 | 31-OCT-03:20 | 4.80 | 1.49 |
November | 0.326366E+11 | 18276.32 | 03-NOV-22:00 | 12.80 | 10.33 | 0.180556E+11 | 11348.17 | 03-NOV-03:20 | 9.23 | 6.61 |
December | 0.318305E+11 | 17139.39 | 04-DEC-23:00 | 8.30 | 7.50 | 0.185438E+11 | 11347.98 | 01-DEC-00:20 | 6.03 | 3.50 |
Annual Sum or Average | 0.440100E+12 | 0.219790E+12 | ||||||||
Minimum of Months | 0.280290E+11 | 16696.56 | 5.00 | 4.23 | 0.165767E+11 | 11347.85 | 1.10 | 0.39 | ||
Maximum of Months | 0.445335E+11 | 22421.60 | 31.55 | 23.91 | 0.188574E+11 | 11348.17 | 22.43 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345941E+11 | 19416.28 | 23-JAN-23:00 | 10.60 | 10.26 | 0.186721E+11 | 11348.07 | 30-JAN-00:20 | -3.1 | -4.5 |
February | 0.310775E+11 | 18700.79 | 23-FEB-23:00 | 5.00 | 4.23 | 0.168798E+11 | 11348.05 | 27-FEB-00:20 | -0.9 | -4.5 |
March | 0.374004E+11 | 20372.32 | 27-MAR-21:10 | 14.13 | 10.86 | 0.190447E+11 | 11348.17 | 27-MAR-00:20 | 8.90 | 8.42 |
April | 0.387655E+11 | 21371.68 | 07-APR-21:10 | 19.22 | 13.75 | 0.184120E+11 | 11348.20 | 24-APR-00:20 | 8.70 | 7.51 |
May | 0.433310E+11 | 22229.11 | 31-MAY-22:00 | 19.90 | 17.34 | 0.189780E+11 | 11348.09 | 15-MAY-00:20 | 10.20 | 7.19 |
June | 0.448902E+11 | 23671.22 | 19-JUN-21:10 | 28.72 | 20.61 | 0.183208E+11 | 11347.89 | 20-JUN-22:19 | 20.60 | 17.70 |
July | 0.477334E+11 | 23528.32 | 07-JUL-22:00 | 28.30 | 24.27 | 0.188835E+11 | 11347.86 | 11-JUL-22:19 | 22.43 | 17.95 |
August | 0.475004E+11 | 23891.32 | 04-AUG-21:10 | 31.55 | 23.91 | 0.189858E+11 | 11347.93 | 25-AUG-22:19 | 20.73 | 14.43 |
September | 0.432317E+11 | 22797.41 | 01-SEP-22:00 | 26.10 | 17.38 | 0.181776E+11 | 11348.00 | 29-SEP-03:20 | 11.87 | 8.31 |
October | 0.412329E+11 | 21079.17 | 05-OCT-22:00 | 18.90 | 17.45 | 0.188672E+11 | 11348.05 | 31-OCT-03:20 | 4.80 | 1.49 |
November | 0.361850E+11 | 20175.12 | 03-NOV-22:00 | 12.80 | 10.33 | 0.182758E+11 | 11348.20 | 03-NOV-03:20 | 9.23 | 6.61 |
December | 0.353772E+11 | 19166.72 | 04-DEC-23:00 | 8.30 | 7.50 | 0.188147E+11 | 11348.04 | 12-DEC-04:19 | 1.10 | 0.63 |
Annual Sum or Average | 0.481319E+12 | 0.222312E+12 | ||||||||
Minimum of Months | 0.310775E+11 | 18700.79 | 5.00 | 4.23 | 0.168798E+11 | 11347.86 | -3.1 | -4.5 | ||
Maximum of Months | 0.477334E+11 | 23891.32 | 31.55 | 24.27 | 0.190447E+11 | 11348.20 | 22.43 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488077E+11 | 25588.58 | 17-JAN-11:50 | 9.13 | 4.90 | 0.187829E+11 | 11360.50 | 21-JAN-18:00 | 7.20 | 6.67 |
February | 0.441900E+11 | 25979.24 | 19-FEB-11:50 | 7.88 | 4.26 | 0.169643E+11 | 11360.31 | 18-FEB-18:00 | 2.80 | 1.19 |
March | 0.512469E+11 | 27387.68 | 27-MAR-18:03 | 18.80 | 14.34 | 0.188114E+11 | 11369.91 | 25-MAR-17:00 | 7.20 | 6.98 |
April | 0.514898E+11 | 29466.34 | 08-APR-10:50 | 23.35 | 15.94 | 0.182024E+11 | 11368.24 | 15-APR-17:00 | 9.40 | 9.40 |
May | 0.556154E+11 | 30070.58 | 29-MAY-10:40 | 27.43 | 17.90 | 0.187902E+11 | 11354.06 | 13-MAY-17:00 | 12.80 | 8.06 |
June | 0.557769E+11 | 30858.93 | 01-JUN-18:07 | 27.70 | 16.08 | 0.181480E+11 | 11319.62 | 17-JUN-17:19 | 22.60 | 20.38 |
July | 0.587691E+11 | 30416.50 | 08-JUL-10:50 | 30.82 | 25.25 | 0.187357E+11 | 11319.66 | 01-JUL-17:19 | 22.60 | 19.99 |
August | 0.589474E+11 | 31516.39 | 22-AUG-17:56 | 27.80 | 16.19 | 0.187483E+11 | 11319.66 | 19-AUG-17:19 | 24.43 | 18.16 |
September | 0.547985E+11 | 29965.55 | 04-SEP-10:50 | 25.60 | 17.63 | 0.181524E+11 | 11319.62 | 02-SEP-17:19 | 22.93 | 18.76 |
October | 0.543777E+11 | 29050.87 | 22-OCT-10:50 | 20.40 | 16.65 | 0.187901E+11 | 11373.14 | 28-OCT-17:00 | 8.30 | 2.79 |
November | 0.494213E+11 | 28105.32 | 04-NOV-10:45 | 17.02 | 11.61 | 0.181933E+11 | 11361.65 | 18-NOV-18:00 | 5.00 | 1.73 |
December | 0.495178E+11 | 26374.21 | 17-DEC-11:50 | 11.93 | 4.45 | 0.187922E+11 | 11360.46 | 16-DEC-18:00 | 6.70 | 2.69 |
Annual Sum or Average | 0.632958E+12 | 0.221111E+12 | ||||||||
Minimum of Months | 0.441900E+11 | 25588.58 | 7.88 | 4.26 | 0.169643E+11 | 11319.62 | 2.80 | 1.19 | ||
Maximum of Months | 0.589474E+11 | 31516.39 | 30.82 | 25.25 | 0.188114E+11 | 11373.14 | 24.43 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124444E+10 | 2640.98 | 17-JAN-14:00 | 11.10 | 5.13 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.133045E+10 | 2548.33 | 20-FEB-13:40 | 9.07 | 4.46 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.361064E+10 | 3636.25 | 27-MAR-13:40 | 20.93 | 16.67 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.546490E+10 | 4027.89 | 08-APR-13:30 | 21.70 | 15.67 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.797092E+10 | 4233.17 | 31-MAY-13:50 | 27.02 | 20.39 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.972495E+10 | 4384.45 | 19-JUN-14:40 | 33.67 | 23.40 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.108682E+11 | 4523.28 | 10-JUL-14:00 | 32.80 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.108602E+11 | 4523.41 | 18-AUG-13:50 | 33.30 | 20.48 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.902510E+10 | 4349.11 | 01-SEP-13:50 | 31.02 | 17.49 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.740074E+10 | 4087.61 | 04-OCT-13:40 | 24.60 | 18.81 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.355998E+10 | 3516.36 | 04-NOV-12:50 | 17.80 | 12.68 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.178257E+10 | 2817.60 | 17-DEC-13:20 | 12.20 | 5.04 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.728431E+11 | 0.00 | ||||||||
Minimum of Months | 0.124444E+10 | 2548.33 | 9.07 | 4.46 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.108682E+11 | 4523.41 | 33.67 | 23.40 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.808822E+09 | 1559.51 | 02-JAN-07:20 | -11.5 |
February | 0.646152E+09 | 1565.18 | 06-FEB-07:15 | -13.1 |
March | 0.162857E+09 | 744.00 | 18-MAR-06:20 | -1.7 |
April | 29069538.25 | 366.66 | 01-APR-06:10 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.109458E+09 | 830.89 | 23-NOV-06:00 | -3.9 |
December | 0.400175E+09 | 902.27 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.215653E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.808822E+09 | 1565.18 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152328E+09 | 618.62 | 02-JAN-05:00 | -12.2 |
February | 0.171618E+09 | 589.68 | 06-FEB-05:00 | -13.3 |
March | 4115851.66 | 128.59 | 18-MAR-05:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 4131434.51 | 175.55 | 24-NOV-05:00 | -3.9 |
December | 4180322.73 | 196.93 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.336374E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.171618E+09 | 618.62 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345802E+09 | 552.32 | 02-JAN-05:00 | -12.2 |
February | 0.342846E+09 | 550.18 | 06-FEB-05:00 | -13.3 |
March | 53462196.20 | 230.22 | 23-MAR-04:00 | -5.0 |
April | 1281870.28 | 41.83 | 21-APR-14:50 | 7.20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 40500681.02 | 256.23 | 24-NOV-05:00 | -3.9 |
December | 0.102694E+09 | 314.64 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.886586E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.345802E+09 | 552.32 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34614560.79 | 1205.58 | 14-JAN-17:00 | -6.1 |
February | 2590671.12 | 461.85 | 06-FEB-07:10 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 256821.49 | 159.79 | 11-DEC-15:00 | 1.10 |
Annual Sum or Average | 37462053.40 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 34614560.79 | 1205.58 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104058E+10 | 1653.78 | 14-JAN-16:13 | -6.1 |
February | 0.872785E+09 | 1639.14 | 06-FEB-16:12 | -7.0 |
March | 0.384177E+09 | 1569.55 | 17-MAR-08:62 | -1.1 |
April | 0.152817E+09 | 1478.74 | 21-APR-15:02 | 7.30 |
May | 8270181.90 | 1099.09 | 03-MAY-15:04 | 15.92 |
June | 1206444.32 | 1100.63 | 22-JUN-08:04 | 24.60 |
July | 588172.04 | 754.64 | 17-JUL-08:05 | 26.38 |
August | 1014464.59 | 931.93 | 23-AUG-08:04 | 22.30 |
September | 2405576.59 | 1223.59 | 25-SEP-15:04 | 18.03 |
October | 32038918.36 | 1072.65 | 23-OCT-15:04 | 18.80 |
November | 0.421719E+09 | 1550.79 | 25-NOV-09:02 | -0.3 |
December | 0.789429E+09 | 1617.25 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.370703E+10 | |||
Minimum of Months | 588172.04 | 754.64 | -7.0 | |
Maximum of Months | 0.104058E+10 | 1653.78 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124501E+10 | 1652.47 | 02-JAN-09:02 | -10.3 |
February | 0.111986E+10 | 1654.83 | 06-FEB-16:12 | -7.0 |
March | 0.488857E+09 | 1570.66 | 17-MAR-08:62 | -1.1 |
April | 0.176808E+09 | 1477.35 | 21-APR-15:02 | 7.30 |
May | 9072852.86 | 1203.51 | 03-MAY-15:04 | 15.92 |
June | 1142239.56 | 1136.44 | 22-JUN-08:04 | 24.60 |
July | 498008.61 | 729.20 | 11-JUL-08:05 | 22.98 |
August | 941528.61 | 1061.98 | 30-AUG-08:04 | 22.30 |
September | 2951250.63 | 1016.59 | 24-SEP-15:04 | 17.70 |
October | 63074828.17 | 1424.70 | 28-OCT-08:62 | 6.28 |
November | 0.558535E+09 | 1584.61 | 24-NOV-09:02 | -1.5 |
December | 0.100531E+10 | 1622.42 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.467206E+10 | |||
Minimum of Months | 498008.61 | 729.20 | -10.3 | |
Maximum of Months | 0.124501E+10 | 1654.83 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105040E+09 | 475.97 | 02-JAN-16:02 | -6.0 |
February | 0.110801E+09 | 480.17 | 06-FEB-16:02 | -7.1 |
March | 11586338.53 | 436.16 | 16-MAR-15:02 | 0.68 |
April | 1016360.36 | 369.65 | 19-APR-15:04 | 10.92 |
May | 495429.82 | 427.30 | 03-MAY-15:06 | 15.92 |
June | 101526.49 | 152.22 | 11-JUN-18:07 | 18.40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 39781.26 | 116.14 | 20-AUG-15:07 | 27.43 |
September | 223835.39 | 319.64 | 23-SEP-15:06 | 16.60 |
October | 1098344.57 | 423.28 | 30-OCT-15:04 | 16.52 |
November | 18166496.29 | 440.59 | 24-NOV-16:02 | 1.20 |
December | 43833512.63 | 455.54 | 31-DEC-16:02 | -3.1 |
Annual Sum or Average | 0.292403E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.1 | |
Maximum of Months | 0.110801E+09 | 480.17 | 27.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103301E+10 | 1591.44 | 14-JAN-16:13 | -6.1 |
February | 0.848362E+09 | 1572.83 | 05-FEB-19:02 | -9.1 |
March | 0.401311E+09 | 1514.32 | 16-MAR-15:02 | 0.68 |
April | 0.153267E+09 | 1429.54 | 01-APR-15:02 | 6.28 |
May | 8914053.64 | 999.14 | 03-MAY-15:04 | 15.92 |
June | 594989.48 | 617.27 | 16-JUN-08:05 | 20.87 |
July | 29457.58 | 193.74 | 24-JUL-08:05 | 22.07 |
August | 78768.64 | 380.28 | 07-AUG-08:05 | 20.28 |
September | 1815336.69 | 740.63 | 23-SEP-15:04 | 16.60 |
October | 34328494.41 | 963.20 | 29-OCT-15:05 | 13.90 |
November | 0.396709E+09 | 1493.67 | 25-NOV-09:02 | -0.3 |
December | 0.777520E+09 | 1561.51 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.365594E+10 | |||
Minimum of Months | 29457.58 | 193.74 | -9.1 | |
Maximum of Months | 0.103301E+10 | 1591.44 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123498E+10 | 1592.73 | 14-JAN-16:13 | -6.1 |
February | 0.109042E+10 | 1590.71 | 06-FEB-16:12 | -7.0 |
March | 0.511503E+09 | 1518.28 | 16-MAR-15:02 | 0.68 |
April | 0.177010E+09 | 1434.37 | 01-APR-15:02 | 6.28 |
May | 10369041.52 | 1158.86 | 03-MAY-15:04 | 15.92 |
June | 584620.08 | 628.31 | 11-JUN-18:05 | 18.40 |
July | 35598.20 | 217.01 | 24-JUL-08:05 | 22.07 |
August | 95999.64 | 547.15 | 07-AUG-08:05 | 20.28 |
September | 2317759.03 | 1057.98 | 25-SEP-15:04 | 18.03 |
October | 64904464.25 | 1113.50 | 10-OCT-15:04 | 19.32 |
November | 0.514216E+09 | 1520.03 | 23-NOV-19:02 | -0.7 |
December | 0.980724E+09 | 1569.97 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.458716E+10 | |||
Minimum of Months | 35598.20 | 217.01 | -7.0 | |
Maximum of Months | 0.123498E+10 | 1592.73 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.760724E+09 | 953.72 | 02-JAN-05:00 | -12.2 |
February | 0.597081E+09 | 953.42 | 06-FEB-05:00 | -13.3 |
March | 0.152198E+09 | 622.11 | 17-MAR-04:00 | -1.7 |
April | 32201579.14 | 358.26 | 01-APR-05:00 | 2.80 |
May | 9454.98 | 15.76 | 01-MAY-04:00 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 16911.30 | 18.11 | 28-OCT-05:00 | 3.90 |
November | 0.155505E+09 | 697.01 | 24-NOV-05:00 | -3.9 |
December | 0.450650E+09 | 695.53 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 0.214839E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.760724E+09 | 953.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149229E+10 | 1932.34 | 14-JAN-16:13 | -6.1 |
February | 0.127055E+10 | 1913.61 | 06-FEB-16:12 | -7.0 |
March | 0.606001E+09 | 1819.28 | 17-MAR-08:62 | -1.1 |
April | 0.259105E+09 | 1729.64 | 21-APR-15:02 | 7.30 |
May | 17879613.80 | 1201.21 | 03-MAY-15:04 | 15.92 |
June | 1079093.06 | 996.51 | 22-JUN-08:04 | 24.60 |
July | 343004.00 | 540.11 | 11-JUL-08:05 | 22.98 |
August | 904703.85 | 1082.15 | 30-AUG-08:04 | 22.30 |
September | 3205504.11 | 993.45 | 23-SEP-15:04 | 16.60 |
October | 69459425.59 | 1175.82 | 29-OCT-08:62 | 6.88 |
November | 0.665889E+09 | 1812.83 | 25-NOV-09:02 | -0.3 |
December | 0.118111E+10 | 1870.82 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.556781E+10 | |||
Minimum of Months | 343004.00 | 540.11 | -7.0 | |
Maximum of Months | 0.149229E+10 | 1932.34 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174855E+10 | 1929.70 | 14-JAN-16:13 | -6.1 |
February | 0.157271E+10 | 1932.41 | 06-FEB-16:12 | -7.0 |
March | 0.744928E+09 | 1820.23 | 22-MAR-08:62 | -2.0 |
April | 0.292135E+09 | 1728.21 | 21-APR-15:02 | 7.30 |
May | 19713992.03 | 1352.57 | 03-MAY-15:04 | 15.92 |
June | 1043365.91 | 967.92 | 22-JUN-08:04 | 24.60 |
July | 285247.36 | 548.42 | 11-JUL-08:05 | 22.98 |
August | 839485.31 | 1088.98 | 23-AUG-08:04 | 22.30 |
September | 4073873.17 | 1168.24 | 25-SEP-15:04 | 18.03 |
October | 0.122080E+09 | 1688.46 | 28-OCT-08:62 | 6.28 |
November | 0.852085E+09 | 1830.01 | 24-NOV-09:02 | -1.5 |
December | 0.145959E+10 | 1880.17 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.681803E+10 | |||
Minimum of Months | 285247.36 | 548.42 | -7.0 | |
Maximum of Months | 0.174855E+10 | 1932.41 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414777E+09 | 951.96 | 14-JAN-16:13 | -6.1 |
February | 0.305956E+09 | 914.71 | 26-FEB-16:02 | -1.6 |
March | 0.137921E+09 | 900.64 | 16-MAR-15:02 | 0.68 |
April | 53576888.54 | 843.99 | 21-APR-15:02 | 7.30 |
May | 1899594.77 | 556.25 | 23-MAY-15:05 | 15.68 |
June | 229468.11 | 309.86 | 01-JUN-08:05 | 19.13 |
July | 81125.57 | 156.83 | 05-JUL-08:06 | 22.98 |
August | 160190.93 | 424.22 | 08-AUG-08:05 | 21.47 |
September | 486114.07 | 418.63 | 23-SEP-15:06 | 16.60 |
October | 3451433.02 | 443.77 | 28-OCT-18:05 | 8.22 |
November | 0.105674E+09 | 857.98 | 25-NOV-09:02 | -0.3 |
December | 0.278703E+09 | 897.82 | 27-DEC-16:02 | 1.75 |
Annual Sum or Average | 0.130292E+10 | |||
Minimum of Months | 81125.57 | 156.83 | -6.1 | |
Maximum of Months | 0.414777E+09 | 951.96 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108296E+10 | 2861.38 | 02-JAN-05:10 | -12.1 |
February | 0.985770E+09 | 2854.14 | 06-FEB-05:00 | -13.3 |
March | 0.139967E+09 | 1295.14 | 23-MAR-05:00 | -5.0 |
April | 4394467.57 | 254.91 | 02-APR-04:50 | 3.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 172225.97 | 69.58 | 29-OCT-04:50 | 2.70 |
November | 0.150492E+09 | 1393.60 | 23-NOV-06:00 | -3.9 |
December | 0.367641E+09 | 1253.86 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.273140E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.108296E+10 | 2861.38 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120209E+11 | 11578.59 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.108538E+11 | 11578.59 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.120626E+11 | 11578.59 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.116133E+11 | 11578.59 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.120417E+11 | 11578.59 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.116666E+11 | 11578.59 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.119885E+11 | 11578.59 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.120626E+11 | 11578.59 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.116133E+11 | 11578.59 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.120209E+11 | 11578.59 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.116573E+11 | 11578.59 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.119885E+11 | 11578.59 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.141590E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.108538E+11 | 11578.59 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.120626E+11 | 11578.59 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.643545E+09 | 619.87 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.581063E+09 | 619.87 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.645777E+09 | 619.87 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.621726E+09 | 619.87 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.644661E+09 | 619.87 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.624577E+09 | 619.87 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.641810E+09 | 619.87 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.645777E+09 | 619.87 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.621726E+09 | 619.87 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.643545E+09 | 619.87 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.624081E+09 | 619.87 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.641810E+09 | 619.87 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.758010E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.581063E+09 | 619.87 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.645777E+09 | 619.87 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.745228E+09 | 717.81 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.672873E+09 | 717.81 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.747812E+09 | 717.81 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.719961E+09 | 717.81 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.746520E+09 | 717.81 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.723263E+09 | 717.81 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.743218E+09 | 717.81 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.747812E+09 | 717.81 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.719961E+09 | 717.81 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.745228E+09 | 717.81 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.722689E+09 | 717.81 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.743218E+09 | 717.81 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.877778E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.672873E+09 | 717.81 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.747812E+09 | 717.81 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577213E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641498E+09 | 615.76 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640390E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617606E+09 | 615.76 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639281E+09 | 615.76 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752987E+10 | 0.124715E+11 | ||||
Minimum of Months | 0.577213E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.205172E+09 | 197.62 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.185252E+09 | 197.62 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.205884E+09 | 197.62 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.198216E+09 | 197.62 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.205528E+09 | 197.62 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.199125E+09 | 197.62 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.204619E+09 | 197.62 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.205884E+09 | 197.62 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.198216E+09 | 197.62 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.205172E+09 | 197.62 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.198967E+09 | 197.62 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.204619E+09 | 197.62 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.241666E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.185252E+09 | 197.62 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.205884E+09 | 197.62 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303752E+09 | 292.58 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.274260E+09 | 292.58 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.304805E+09 | 292.58 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.293453E+09 | 292.58 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.304278E+09 | 292.58 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.294799E+09 | 292.58 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.302933E+09 | 292.58 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.304805E+09 | 292.58 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.293453E+09 | 292.58 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.303752E+09 | 292.58 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.294565E+09 | 292.58 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.302933E+09 | 292.58 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.357779E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.274260E+09 | 292.58 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.304805E+09 | 292.58 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.140530E+10 | 1531.38 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.124046E+10 | 1531.38 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.134531E+10 | 1531.38 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.125636E+10 | 1531.38 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.125392E+10 | 1531.38 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.119603E+10 | 1531.38 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.123323E+10 | 1531.38 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.128521E+10 | 1531.38 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.127938E+10 | 1531.38 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.136783E+10 | 1531.38 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.134570E+10 | 1531.38 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.139968E+10 | 1531.38 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.156084E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.119603E+10 | 1531.38 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.140530E+10 | 1531.38 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.122996E+11 | 12090.12 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.110645E+11 | 12090.12 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.122511E+11 | 12090.12 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.117478E+11 | 12090.12 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.121131E+11 | 12090.12 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.117136E+11 | 12090.12 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.120437E+11 | 12090.12 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.121716E+11 | 12090.12 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.117774E+11 | 12090.12 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122447E+11 | 12090.12 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119013E+11 | 12090.12 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122627E+11 | 12090.12 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.143591E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.110645E+11 | 12090.12 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.122996E+11 | 12090.12 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124452E+09 | 146.35 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.112401E+09 | 146.35 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.123995E+09 | 146.35 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.120512E+09 | 146.35 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.124224E+09 | 146.35 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.120054E+09 | 146.35 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124681E+09 | 146.35 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.123995E+09 | 146.35 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.120512E+09 | 146.35 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.124452E+09 | 146.35 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.120283E+09 | 146.35 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124681E+09 | 146.35 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.146424E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.112401E+09 | 146.35 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.124681E+09 | 146.35 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124486E+09 | 146.39 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.112432E+09 | 146.39 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.124029E+09 | 146.39 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.120544E+09 | 146.39 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.124258E+09 | 146.39 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.120087E+09 | 146.39 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124715E+09 | 146.39 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.124029E+09 | 146.39 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.120544E+09 | 146.39 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.124486E+09 | 146.39 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.120316E+09 | 146.39 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124715E+09 | 146.39 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.146464E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.112432E+09 | 146.39 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.124715E+09 | 146.39 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.232638E+10 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233445E+10 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224751E+10 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233042E+10 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224751E+10 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232638E+10 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274017E+11 | ||||
Minimum of Months | 0.210051E+10 | 2240.79 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.79 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124486E+09 | 146.39 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.112432E+09 | 146.39 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.124029E+09 | 146.39 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.120544E+09 | 146.39 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.124258E+09 | 146.39 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.120087E+09 | 146.39 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124715E+09 | 146.39 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.124029E+09 | 146.39 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.120544E+09 | 146.39 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.124486E+09 | 146.39 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.120316E+09 | 146.39 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124715E+09 | 146.39 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.146464E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.112432E+09 | 146.39 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.124715E+09 | 146.39 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.264055E+10 | 2689.23 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.235717E+10 | 2689.23 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.258370E+10 | 2689.23 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244736E+10 | 2689.23 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.248627E+10 | 2689.23 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.239199E+10 | 2689.23 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.246281E+10 | 2689.23 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251925E+10 | 2689.23 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.247135E+10 | 2689.23 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260131E+10 | 2689.23 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.254070E+10 | 2689.23 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.263740E+10 | 2689.23 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.301399E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.235717E+10 | 2689.23 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.264055E+10 | 2689.23 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.264055E+10 | 2689.23 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.235717E+10 | 2689.23 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.258370E+10 | 2689.23 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.244736E+10 | 2689.23 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.248627E+10 | 2689.23 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.239199E+10 | 2689.23 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.246281E+10 | 2689.23 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.251925E+10 | 2689.23 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.247135E+10 | 2689.23 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260131E+10 | 2689.23 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.254070E+10 | 2689.23 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.263740E+10 | 2689.23 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.301399E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.235717E+10 | 2689.23 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.264055E+10 | 2689.23 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.991199E+09 | 954.73 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.894963E+09 | 954.73 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.994636E+09 | 954.73 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.957593E+09 | 954.73 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.992918E+09 | 954.73 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.961985E+09 | 954.73 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.988526E+09 | 954.73 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.994636E+09 | 954.73 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.957593E+09 | 954.73 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.991199E+09 | 954.73 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.961221E+09 | 954.73 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.988526E+09 | 954.73 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.116750E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.894963E+09 | 954.73 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.994636E+09 | 954.73 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.246212E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222307E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.247065E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246639E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238955E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245548E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237864E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246212E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245548E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290004E+11 | ||||
Minimum of Months | 0.222307E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.120209E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.108538E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.116133E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.120417E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.116666E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.119885E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.116133E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.120209E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.116573E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.119885E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.141590E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.108538E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.643545E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135551E+10 |
February | 0.179968E+10 | 0.581063E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130516E+10 |
March | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75674.80 | 0.104293E+10 |
April | 0.192973E+10 | 0.621726E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2441000.97 | 0.651293E+09 |
May | 0.199475E+10 | 0.644661E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17086896.79 | 0.346790E+09 |
June | 0.193394E+10 | 0.624577E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85864977.06 | 70365489.01 |
July | 0.199054E+10 | 0.641810E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202114E+09 | 3624903.22 |
August | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182954E+09 | 23396120.45 |
September | 0.192973E+10 | 0.621726E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39132855.00 | 0.149439E+09 |
October | 0.199054E+10 | 0.643545E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 714590.52 | 0.512685E+09 |
November | 0.192552E+10 | 0.624081E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892242E+09 |
December | 0.199054E+10 | 0.641810E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118796E+10 |
Annual Sum or Average | 0.234734E+11 | 0.758010E+10 | 0.101859E+11 | 0.530384E+09 | 0.754140E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.581063E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3624903.22 |
Maximum of Months | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202114E+09 | 0.135551E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.745228E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288410E+09 |
February | 0.208403E+10 | 0.672873E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277503E+09 |
March | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12848.94 | 0.226696E+09 |
April | 0.223463E+10 | 0.719961E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 761221.07 | 0.146381E+09 |
May | 0.230993E+10 | 0.746520E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3816453.78 | 82740925.49 |
June | 0.223950E+10 | 0.723263E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17606071.45 | 20804828.91 |
July | 0.230505E+10 | 0.743218E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40195637.05 | 2039400.03 |
August | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39516318.87 | 7884430.29 |
September | 0.223463E+10 | 0.719961E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9282873.15 | 36476806.01 |
October | 0.230505E+10 | 0.745228E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 734677.25 | 0.114196E+09 |
November | 0.222975E+10 | 0.722689E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195084E+09 |
December | 0.230505E+10 | 0.743218E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254962E+09 |
Annual Sum or Average | 0.271823E+11 | 0.877778E+10 | 0.117953E+11 | 0.111926E+09 | 0.165318E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.672873E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039400.03 |
Maximum of Months | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40195637.05 | 0.288410E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.303752E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934469E+09 |
February | 0.139600E+10 | 0.274260E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894672E+09 |
March | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 51328.46 | 0.730100E+09 |
April | 0.149688E+10 | 0.293453E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2588885.64 | 0.471355E+09 |
May | 0.154732E+10 | 0.304278E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 12025509.69 | 0.263008E+09 |
June | 0.150015E+10 | 0.294799E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 57861011.42 | 64616582.93 |
July | 0.154405E+10 | 0.302933E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.136576E+09 | 6641420.12 |
August | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.137777E+09 | 20728909.23 |
September | 0.149688E+10 | 0.293453E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 34379170.89 | 0.113501E+09 |
October | 0.154405E+10 | 0.303752E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 3837176.21 | 0.349222E+09 |
November | 0.149361E+10 | 0.294565E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626940E+09 |
December | 0.154405E+10 | 0.302933E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824170E+09 |
Annual Sum or Average | 0.182082E+11 | 0.357779E+10 | 0.679373E+11 | 0.590211E+12 | 0.385096E+09 | 0.529942E+10 | |||
Minimum of Months | 0.139600E+10 | 0.274260E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6641420.12 |
Maximum of Months | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.137777E+09 | 0.934469E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.140530E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348665E+10 |
February | 0.236489E+11 | 0.124046E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336264E+10 |
March | 0.262677E+11 | 0.134531E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44189.19 | 0.275703E+10 |
April | 0.253579E+11 | 0.125636E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5748370.06 | 0.177619E+10 |
May | 0.262123E+11 | 0.125392E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40436705.32 | 0.101849E+10 |
June | 0.254132E+11 | 0.119603E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194685E+09 | 0.274866E+09 |
July | 0.261570E+11 | 0.123323E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438543E+09 | 38321295.60 |
August | 0.262677E+11 | 0.128521E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422685E+09 | 0.110446E+09 |
September | 0.253579E+11 | 0.127938E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85783046.56 | 0.484485E+09 |
October | 0.261570E+11 | 0.136783E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1975126.38 | 0.145834E+10 |
November | 0.253025E+11 | 0.134570E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237660E+10 |
December | 0.261570E+11 | 0.139968E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309164E+10 |
Annual Sum or Average | 0.308456E+12 | 0.156084E+11 | 0.143409E+11 | 0.118990E+10 | 0.202357E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.119603E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38321295.60 |
Maximum of Months | 0.262677E+11 | 0.140530E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438543E+09 | 0.348665E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.122996E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708603E+10 |
February | 0.702046E+11 | 0.110645E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681265E+10 |
March | 0.779788E+11 | 0.122511E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168975.32 | 0.560688E+10 |
April | 0.752779E+11 | 0.117478E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16309524.74 | 0.365154E+10 |
May | 0.778146E+11 | 0.121131E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87355261.35 | 0.210273E+10 |
June | 0.754422E+11 | 0.117136E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404623E+09 | 0.569869E+09 |
July | 0.776503E+11 | 0.120437E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911364E+09 | 76459121.15 |
August | 0.779788E+11 | 0.121716E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914244E+09 | 0.223052E+09 |
September | 0.752779E+11 | 0.117774E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207413E+09 | 0.966358E+09 |
October | 0.776503E+11 | 0.122447E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13518995.01 | 0.287870E+10 |
November | 0.751137E+11 | 0.119013E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485753E+10 |
December | 0.776503E+11 | 0.122627E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630069E+10 |
Annual Sum or Average | 0.915690E+12 | 0.143591E+12 | 0.149002E+12 | 0.255500E+10 | 0.411325E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.110645E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76459121.15 |
Maximum of Months | 0.779788E+11 | 0.122996E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914244E+09 | 0.708603E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392864E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379457E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17327.31 | 0.306089E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 731699.14 | 0.195227E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3814052.74 | 0.109184E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22585425.22 | 23948248.08 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60441744.00 | 1240067.98 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60904608.43 | 6801510.52 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13043857.04 | 45441533.38 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 490710.66 | 0.145993E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260413E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344198E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 0.162029E+09 | 0.221086E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240067.98 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60904608.43 | 0.392864E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389442E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375240E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17325.64 | 0.302248E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769964.70 | 0.193695E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3821367.46 | 0.108767E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22600152.67 | 23907048.37 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60454687.44 | 1237234.49 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60979514.36 | 6772732.89 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13142722.82 | 44672638.62 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 538016.27 | 0.142741E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256378E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339689E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 0.162324E+09 | 0.218479E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237234.49 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60979514.36 | 0.389442E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124452E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111093E+09 |
February | 0.00 | 0.112401E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122266E+09 |
March | 0.00 | 0.123995E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108676E+09 |
April | 0.00 | 0.120512E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78622930.57 |
May | 0.00 | 0.124224E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124835.48 | 55955583.70 |
June | 0.00 | 0.120054E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1100785.61 | 26159506.46 |
July | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2575043.66 | 11176977.33 |
August | 0.00 | 0.123995E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3486007.08 | 13526537.61 |
September | 0.00 | 0.120512E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 272883.46 | 34428162.16 |
October | 0.00 | 0.124452E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67357531.66 |
November | 0.00 | 0.120283E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96884199.60 |
December | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115340E+09 |
Annual Sum or Average | 0.00 | 0.146424E+10 | 0.300992E+10 | 7559555.28 | 0.841486E+09 | ||||
Minimum of Months | 0.00 | 0.112401E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11176977.33 |
Maximum of Months | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3486007.08 | 0.122266E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110635E+09 |
February | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106241E+09 |
March | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4835.68 | 85660242.36 |
April | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 230437.02 | 54814106.83 |
May | 0.303504E+09 | 0.124258E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1087960.13 | 30463451.86 |
June | 0.293842E+09 | 0.120087E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6399998.80 | 6582804.98 |
July | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16957185.77 | 343626.96 |
August | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17173909.00 | 1886042.44 |
September | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3751645.63 | 12470882.76 |
October | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175330.65 | 40051928.81 |
November | 0.293661E+09 | 0.120316E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73153355.41 |
December | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96780323.35 |
Annual Sum or Average | 0.357224E+10 | 0.146464E+10 | 0.301074E+10 | 45781302.68 | 0.619083E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343626.96 |
Maximum of Months | 0.303685E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17173909.00 | 0.110635E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392933E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379869E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17325.89 | 0.306957E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 729275.52 | 0.196431E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3781218.14 | 0.110064E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22498328.15 | 24147976.77 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60261857.79 | 1259522.29 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60766105.10 | 6969150.63 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13011980.67 | 45841517.87 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485530.49 | 0.146754E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261122E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344380E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 0.161552E+09 | 0.221673E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1259522.29 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60766105.10 | 0.392933E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389498E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375507E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17326.08 | 0.303026E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734070.77 | 0.195076E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3783882.07 | 0.109814E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22512913.86 | 24125288.46 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60273645.74 | 1256506.95 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60809397.66 | 6957786.94 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13061331.20 | 45377680.06 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503812.88 | 0.143750E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257135E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339798E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 0.161696E+09 | 0.219132E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256506.95 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60809397.66 | 0.389498E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392269E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379012E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15343.15 | 0.306084E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705220.18 | 0.195978E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3700747.41 | 0.110659E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22034214.76 | 24717543.30 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59291279.82 | 1336445.72 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59894100.04 | 7035095.64 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12626051.38 | 46282015.46 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 453372.30 | 0.146940E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260006E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343543E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 0.158720E+09 | 0.221386E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1336445.72 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59894100.04 | 0.392269E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389365E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375217E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15364.83 | 0.302126E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 717164.01 | 0.194474E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3703867.09 | 0.110383E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22037454.62 | 24702382.17 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59295508.69 | 1333875.37 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59961541.62 | 7004462.05 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12682167.45 | 45759422.34 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 482649.08 | 0.143801E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255960E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339257E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 0.158896E+09 | 0.218938E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1333875.37 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59961541.62 | 0.389365E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205060E+09 |
February | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198328E+09 |
March | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7859.93 | 0.159314E+09 |
April | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357494.08 | 0.101587E+09 |
May | 0.303504E+09 | 0.124258E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1894509.08 | 56844614.56 |
June | 0.293842E+09 | 0.120087E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11270776.73 | 12582373.26 |
July | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30297131.39 | 689315.08 |
August | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30614135.26 | 3614342.91 |
September | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6421024.03 | 23903545.58 |
October | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216533.81 | 76094477.05 |
November | 0.293661E+09 | 0.120316E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136921E+09 |
December | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180097E+09 |
Annual Sum or Average | 0.357224E+10 | 0.146464E+10 | 0.301074E+10 | 81079464.31 | 0.115504E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689315.08 |
Maximum of Months | 0.303685E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30614135.26 | 0.205060E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.264055E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107565E+10 |
February | 0.415303E+11 | 0.235717E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102742E+10 |
March | 0.461292E+11 | 0.258370E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858398E+09 |
April | 0.445315E+11 | 0.244736E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1472424.30 | 0.575606E+09 |
May | 0.460320E+11 | 0.248627E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7206685.38 | 0.352288E+09 |
June | 0.446286E+11 | 0.239199E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37726690.21 | 0.116139E+09 |
July | 0.459349E+11 | 0.246281E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91346442.61 | 25762111.51 |
August | 0.461292E+11 | 0.251925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100264E+09 | 47475368.46 |
September | 0.445315E+11 | 0.247135E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19901651.35 | 0.172377E+09 |
October | 0.459349E+11 | 0.260131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1507057.83 | 0.442191E+09 |
November | 0.444343E+11 | 0.254070E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740769E+09 |
December | 0.459349E+11 | 0.263740E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956028E+09 |
Annual Sum or Average | 0.541686E+12 | 0.301399E+11 | 0.175857E+12 | 0.259425E+09 | 0.639010E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.235717E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25762111.51 |
Maximum of Months | 0.461292E+11 | 0.264055E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100264E+09 | 0.107565E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.264055E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108788E+10 |
February | 0.415303E+11 | 0.235717E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103844E+10 |
March | 0.461292E+11 | 0.258370E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867691E+09 |
April | 0.445315E+11 | 0.244736E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1286290.92 | 0.583261E+09 |
May | 0.460320E+11 | 0.248627E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6451215.88 | 0.358885E+09 |
June | 0.446286E+11 | 0.239199E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35237330.65 | 0.119937E+09 |
July | 0.459349E+11 | 0.246281E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87197067.79 | 26970130.75 |
August | 0.461292E+11 | 0.251925E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96559658.73 | 48669718.67 |
September | 0.445315E+11 | 0.247135E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18117193.34 | 0.177682E+09 |
October | 0.459349E+11 | 0.260131E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1171510.99 | 0.449462E+09 |
November | 0.444343E+11 | 0.254070E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749872E+09 |
December | 0.459349E+11 | 0.263740E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966656E+09 |
Annual Sum or Average | 0.541686E+12 | 0.301399E+11 | 0.175857E+12 | 0.246020E+09 | 0.647540E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.235717E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26970130.75 |
Maximum of Months | 0.461292E+11 | 0.264055E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96559658.73 | 0.108788E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.991199E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985451E+09 |
February | 0.369574E+10 | 0.894963E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939645E+09 |
March | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783487E+09 |
April | 0.396281E+10 | 0.957593E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 617422.99 | 0.526598E+09 |
May | 0.409635E+10 | 0.992918E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4085180.39 | 0.322419E+09 |
June | 0.397146E+10 | 0.961985E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 26752840.01 | 0.100625E+09 |
July | 0.408770E+10 | 0.988526E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 75471985.13 | 15008084.74 |
August | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 82056652.27 | 34206599.20 |
September | 0.396281E+10 | 0.957593E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 11902111.00 | 0.157312E+09 |
October | 0.408770E+10 | 0.991199E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 109635.00 | 0.407674E+09 |
November | 0.395417E+10 | 0.961221E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678640E+09 |
December | 0.408770E+10 | 0.988526E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874292E+09 |
Annual Sum or Average | 0.482041E+11 | 0.116750E+11 | 0.392709E+12 | 0.359593E+12 | 0.200996E+09 | 0.582536E+10 | |||
Minimum of Months | 0.369574E+10 | 0.894963E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15008084.74 |
Maximum of Months | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 82056652.27 | 0.985451E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623355E+09 |
February | 0.00 | 0.577213E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598885E+09 |
March | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36559.95 | 0.477363E+09 |
April | 0.00 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1983727.65 | 0.301720E+09 |
May | 0.00 | 0.640390E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8748625.29 | 0.165708E+09 |
June | 0.00 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39394868.52 | 39175402.88 |
July | 0.00 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90017368.60 | 3162254.57 |
August | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89943476.77 | 14694525.76 |
September | 0.00 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22503879.08 | 70808860.64 |
October | 0.00 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2189977.09 | 0.228076E+09 |
November | 0.00 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409261E+09 |
December | 0.00 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543724E+09 |
Annual Sum or Average | 0.752987E+10 | 0.124715E+11 | 0.254818E+09 | 0.347593E+10 | |||||
Minimum of Months | 0.00 | 0.577213E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3162254.57 |
Maximum of Months | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90017368.60 | 0.623355E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.205172E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433179E+09 |
February | 0.00 | 0.185252E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416261E+09 |
March | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25422.52 | 0.330843E+09 |
April | 0.00 | 0.198216E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1403375.68 | 0.207572E+09 |
May | 0.00 | 0.205528E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6188772.10 | 0.111906E+09 |
June | 0.00 | 0.199125E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28245441.51 | 25185555.67 |
July | 0.00 | 0.204619E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64455540.37 | 1847407.28 |
August | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64139167.20 | 9340143.75 |
September | 0.00 | 0.198216E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16458357.76 | 46686550.45 |
October | 0.00 | 0.205172E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575185.21 | 0.153953E+09 |
November | 0.00 | 0.198967E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282343E+09 |
December | 0.00 | 0.204619E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377638E+09 |
Annual Sum or Average | 0.241666E+10 | 0.359769E+10 | 0.182491E+09 | 0.239675E+10 | |||||
Minimum of Months | 0.00 | 0.185252E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1847407.28 |
Maximum of Months | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64455540.37 | 0.433179E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480289E+09 |
February | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461456E+09 |
March | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25937.02 | 0.367015E+09 |
April | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1542963.35 | 0.229910E+09 |
May | 0.00 | 0.233042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7125271.51 | 0.122526E+09 |
June | 0.00 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35634791.99 | 24250069.44 |
July | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84684961.61 | 1154826.21 |
August | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82861919.84 | 7412260.42 |
September | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21505777.00 | 48486229.17 |
October | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1802726.48 | 0.166313E+09 |
November | 0.00 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312648E+09 |
December | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418879E+09 |
Annual Sum or Average | 0.274017E+11 | 0.235184E+09 | 0.264034E+10 | ||||||
Minimum of Months | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1154826.21 |
Maximum of Months | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84684961.61 | 0.480289E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853037E+09 |
February | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819868E+09 |
March | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30282.19 | 0.655109E+09 |
April | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1900785.33 | 0.414987E+09 |
May | 0.00 | 0.246639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8361429.76 | 0.230244E+09 |
June | 0.00 | 0.238955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42930917.09 | 56730390.39 |
July | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104585E+09 | 4748365.57 |
August | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105696E+09 | 19990517.68 |
September | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24214762.30 | 96259598.43 |
October | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1523480.72 | 0.307748E+09 |
November | 0.00 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557964E+09 |
December | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744546E+09 |
Annual Sum or Average | 0.290004E+11 | 0.289243E+09 | 0.476123E+10 | ||||||
Minimum of Months | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4748365.57 |
Maximum of Months | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105696E+09 | 0.853037E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 11578.59 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 11578.59 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 11578.59 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 11578.59 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 11578.59 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 11578.59 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 11578.59 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 11578.59 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 11578.59 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 11578.59 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 11578.59 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 11578.59 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 619.87 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 887.52 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 619.87 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 915.11 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 619.87 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27-MAR-16:00 | 676.91 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 619.87 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.10 | 08-APR-10:00 | 477.33 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 619.87 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.93 | 30-MAY-13:00 | 370.68 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 619.87 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.94 | 19-JUN-12:00 | 185.43 | 03-JUN-03:30 |
July | 1169.53 | 01-JUL-00:10 | 619.87 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.26 | 07-JUL-12:00 | 63.96 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 619.87 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.70 | 24-AUG-16:00 | 144.67 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 619.87 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.56 | 01-SEP-14:00 | 270.27 | 24-SEP-06:00 |
October | 1169.53 | 02-OCT-00:10 | 619.87 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 | 25-OCT-11:40 | 480.22 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 619.87 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 659.22 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 619.87 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 767.73 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 619.87 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 | |||||
Maximum of Months | 1169.53 | 619.87 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 311.94 | 915.11 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 717.81 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.29 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 717.81 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 192.41 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 717.81 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27-MAR-16:00 | 145.31 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 717.81 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 07-APR-13:00 | 104.11 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 717.81 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.76 | 30-MAY-13:00 | 82.87 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 717.81 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | 19-JUN-12:00 | 45.60 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 717.81 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 07-JUL-12:00 | 17.58 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 717.81 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 | 24-AUG-15:00 | 36.77 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 717.81 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 | 01-SEP-14:00 | 63.14 | 30-SEP-01:00 |
October | 1354.32 | 02-OCT-00:10 | 717.81 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 | 25-OCT-11:00 | 106.84 | 29-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 717.81 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 140.29 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 717.81 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 162.78 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 717.81 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | |||||
Maximum of Months | 1354.32 | 717.81 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | 192.41 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 292.58 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 613.69 | 02-JAN-07:20 |
February | 907.20 | 01-FEB-00:10 | 292.58 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 627.29 | 06-FEB-07:20 |
March | 907.20 | 01-MAR-00:10 | 292.58 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 18.06 | 27-MAR-16:00 | 479.89 | 23-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 292.58 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 84.22 | 07-APR-13:00 | 352.28 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 292.58 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 132.66 | 30-MAY-13:00 | 268.19 | 01-MAY-05:20 |
June | 907.20 | 01-JUN-00:10 | 292.58 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 224.85 | 19-JUN-12:00 | 151.99 | 02-JUN-06:20 |
July | 907.20 | 01-JUL-00:10 | 292.58 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 186.77 | 07-JUL-12:00 | 69.96 | 01-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 292.58 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 185.56 | 24-AUG-16:00 | 106.70 | 08-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 292.58 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 146.27 | 01-SEP-14:00 | 206.18 | 24-SEP-06:10 |
October | 907.20 | 02-OCT-00:10 | 292.58 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 59.61 | 04-OCT-13:00 | 352.31 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 292.58 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 471.89 | 24-NOV-07:20 |
December | 907.20 | 01-DEC-00:10 | 292.58 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 536.13 | 31-DEC-23:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | ||||||
Maximum of Months | 907.20 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 224.85 | 627.29 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1531.38 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2252.21 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1531.38 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2314.26 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 1531.38 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 | 27-MAR-16:00 | 1745.38 | 23-MAR-04:30 |
April | 15368.40 | 01-APR-00:10 | 1531.38 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.91 | 08-APR-10:00 | 1251.45 | 01-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1531.38 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.63 | 30-MAY-13:00 | 1020.76 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1531.38 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 814.48 | 19-JUN-12:00 | 583.30 | 03-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1531.38 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 648.42 | 07-JUL-12:00 | 233.99 | 01-JUL-23:30 |
August | 15368.40 | 01-AUG-00:10 | 1531.38 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.64 | 24-AUG-15:00 | 481.13 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1531.38 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.49 | 01-SEP-14:00 | 799.44 | 30-SEP-01:00 |
October | 15368.40 | 02-OCT-00:10 | 1531.38 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | 25-OCT-11:40 | 1265.13 | 09-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 1531.38 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1694.06 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1531.38 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1937.70 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1531.38 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.99 | |||||
Maximum of Months | 15368.40 | 1531.38 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 814.48 | 2314.26 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 12090.12 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4552.40 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 12090.12 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4695.43 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 12090.12 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.06 | 27-MAR-16:00 | 3586.25 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 12090.12 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.42 | 07-APR-13:00 | 2575.22 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 12090.12 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 994.90 | 30-MAY-13:00 | 2092.94 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 12090.12 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.93 | 19-JUN-12:00 | 1175.30 | 03-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 12090.12 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370.44 | 07-JUL-12:00 | 469.21 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 12090.12 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.36 | 24-AUG-15:00 | 968.37 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 12090.12 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.69 | 01-SEP-14:00 | 1592.39 | 30-SEP-01:00 |
October | 45622.98 | 02-OCT-00:10 | 12090.12 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.34 | 25-OCT-11:00 | 2634.65 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 12090.12 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3479.57 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 12090.12 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3989.01 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.21 | |||||
Maximum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.93 | 4695.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.16 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 55.58 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:10 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 04-OCT-15:10 | 142.34 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.88 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.54 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.70 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-16:00 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 55.58 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:10 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.61 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:10 | 142.32 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 146.35 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 68.74 | 31-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 146.35 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 77.43 | 05-FEB-24:00 |
March | 0.00 | 01-MAR-00:10 | 146.35 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 62.21 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 146.35 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.84 | 12-APR-06:20 |
May | 0.00 | 01-MAY-00:10 | 146.35 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 30-MAY-13:00 | 39.90 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 146.35 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 19-JUN-12:00 | 26.41 | 03-JUN-03:00 |
July | 0.00 | 01-JUL-00:10 | 146.35 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 07-JUL-12:00 | 16.33 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 146.35 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 24-AUG-15:00 | 23.15 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 146.35 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 01-SEP-14:00 | 32.89 | 24-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 146.35 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 50.40 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 146.35 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 61.58 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 146.35 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 64.38 | 22-DEC-07:20 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 146.35 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | |||||
Maximum of Months | 0.00 | 146.35 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 77.43 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 146.39 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 73.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 146.39 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 75.56 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 146.39 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27-MAR-16:00 | 55.86 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 146.39 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 08-APR-10:00 | 39.48 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 146.39 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 30-MAY-15:50 | 30.72 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 146.39 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 19-JUN-12:00 | 15.51 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 146.39 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 10-JUL-15:10 | 5.55 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 146.39 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 24-AUG-15:10 | 12.17 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 146.39 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 01-SEP-15:10 | 22.48 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 146.39 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 04-OCT-13:00 | 39.72 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 146.39 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 54.42 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 146.39 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63.32 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | |||||
Maximum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 75.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 60.88 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:08 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:08 | 142.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.89 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.53 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.70 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27-MAR-16:00 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-15:50 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 60.88 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:08 | 19.87 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:08 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:10 | 142.32 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.10 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.26 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 27-MAR-16:00 | 200.67 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 08-APR-10:00 | 141.95 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-16:00 | 110.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 19-JUN-12:00 | 56.02 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 10-JUL-15:10 | 20.30 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 24-AUG-15:50 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 01-SEP-15:10 | 81.01 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 04-OCT-15:10 | 142.82 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.48 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.40 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 271.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.08 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.23 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 27-MAR-16:00 | 200.65 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 | 08-APR-10:00 | 141.93 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-16:00 | 110.54 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 19-JUN-12:00 | 56.01 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.34 | 10-JUL-15:10 | 20.29 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 24-AUG-15:50 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 01-SEP-15:10 | 81.00 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 04-OCT-15:10 | 142.80 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 195.46 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.38 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 271.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 146.39 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 135.11 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 146.39 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 138.77 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 146.39 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 27-MAR-16:00 | 102.66 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 146.39 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 08-APR-10:00 | 72.62 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 146.39 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 30-MAY-16:00 | 56.56 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 146.39 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 19-JUN-12:00 | 28.66 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 146.39 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 | 10-JUL-15:10 | 10.38 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 146.39 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 24-AUG-16:00 | 22.54 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 146.39 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 | 01-SEP-15:10 | 41.45 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 146.39 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 02-OCT-16:00 | 73.06 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 146.39 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 100.01 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 146.39 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 116.34 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | |||||
Maximum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 138.77 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2689.23 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 685.69 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2689.23 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 703.00 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2689.23 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 539.32 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 2689.23 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.57 | 07-APR-13:00 | 398.92 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2689.23 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.26 | 30-MAY-13:00 | 321.44 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2689.23 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.30 | 19-JUN-12:00 | 186.63 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2689.23 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.58 | 07-JUL-12:00 | 88.13 | 01-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2689.23 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.69 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2689.23 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.35 | 01-SEP-14:00 | 248.70 | 24-SEP-06:00 |
October | 26988.77 | 02-OCT-00:10 | 2689.23 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.07 | 25-OCT-11:00 | 399.66 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2689.23 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 524.70 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2689.23 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.26 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.13 | |||||
Maximum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 220.30 | 703.00 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2689.23 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 689.89 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2689.23 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 707.23 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2689.23 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 542.77 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 2689.23 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 07-APR-13:00 | 399.21 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2689.23 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.96 | 30-MAY-13:00 | 321.45 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2689.23 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 19-JUN-12:00 | 186.63 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2689.23 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.32 | 07-JUL-12:00 | 88.18 | 02-JUL-05:10 |
August | 26988.77 | 01-AUG-00:10 | 2689.23 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.06 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2689.23 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 01-SEP-14:00 | 248.70 | 24-SEP-06:00 |
October | 26988.77 | 02-OCT-00:10 | 2689.23 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 25-OCT-11:00 | 401.65 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2689.23 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 528.54 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2689.23 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.56 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.18 | |||||
Maximum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 707.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 954.73 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 617.24 | 02-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 954.73 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 629.75 | 06-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 954.73 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 486.74 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 954.73 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 38.35 | 07-APR-13:00 | 357.24 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 954.73 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.73 | 30-MAY-13:00 | 284.52 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 954.73 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 179.95 | 19-JUN-12:00 | 162.28 | 03-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 954.73 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 141.54 | 07-JUL-12:00 | 78.81 | 01-JUL-23:00 |
August | 2401.70 | 01-AUG-00:10 | 954.73 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 140.59 | 24-AUG-15:40 | 135.11 | 08-AUG-05:10 |
September | 2401.70 | 01-SEP-00:10 | 954.73 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 101.08 | 01-SEP-14:00 | 222.54 | 24-SEP-06:00 |
October | 2401.70 | 02-OCT-00:10 | 954.73 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 13.49 | 04-OCT-13:00 | 359.44 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 954.73 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 475.32 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 954.73 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 545.60 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 954.73 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | ||||||
Maximum of Months | 2401.70 | 954.73 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 179.95 | 629.75 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 412.32 | 02-JAN-05:00 |
February | 0.00 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 423.64 | 06-FEB-03:00 |
March | 0.00 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 27-MAR-16:00 | 312.76 | 23-MAR-06:00 |
April | 0.00 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 | 07-APR-13:00 | 220.55 | 03-APR-06:00 |
May | 0.00 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.46 | 30-MAY-13:00 | 171.26 | 01-MAY-05:00 |
June | 0.00 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.37 | 19-JUN-12:00 | 92.19 | 03-JUN-03:00 |
July | 0.00 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.38 | 07-JUL-12:00 | 35.02 | 02-JUL-03:00 |
August | 0.00 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.56 | 24-AUG-15:00 | 75.23 | 08-AUG-05:00 |
September | 0.00 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.57 | 01-SEP-14:00 | 128.46 | 24-SEP-06:00 |
October | 0.00 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 04-OCT-13:00 | 223.24 | 09-OCT-06:00 |
November | 0.00 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 304.61 | 24-NOV-07:00 |
December | 0.00 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 354.73 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | ||||
Maximum of Months | 0.00 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 154.37 | 423.64 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 197.62 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 286.01 | 02-JAN-05:00 |
February | 0.00 | 197.62 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 294.55 | 06-FEB-03:00 |
March | 0.00 | 197.62 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 27-MAR-16:00 | 217.46 | 23-MAR-06:00 |
April | 0.00 | 197.62 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 | 07-APR-13:00 | 153.35 | 03-APR-06:00 |
May | 0.00 | 197.62 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 30-MAY-13:00 | 119.08 | 01-MAY-05:00 |
June | 0.00 | 197.62 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.72 | 19-JUN-12:00 | 62.56 | 03-JUN-03:00 |
July | 0.00 | 197.62 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.27 | 07-JUL-12:00 | 22.96 | 02-JUL-03:00 |
August | 0.00 | 197.62 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 24-AUG-15:00 | 50.68 | 08-AUG-05:00 |
September | 0.00 | 197.62 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 01-SEP-14:00 | 86.86 | 24-SEP-06:00 |
October | 0.00 | 197.62 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 04-OCT-13:00 | 154.28 | 09-OCT-06:00 |
November | 0.00 | 197.62 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 211.80 | 24-NOV-07:00 |
December | 0.00 | 197.62 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.65 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 197.62 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | ||||
Maximum of Months | 0.00 | 197.62 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 106.72 | 294.55 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 315.31 | 02-JAN-05:00 |
February | 0.00 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 324.84 | 06-FEB-03:00 |
March | 0.00 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 27-MAR-16:00 | 241.01 | 23-MAR-06:00 |
April | 0.00 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 07-APR-13:00 | 170.07 | 03-APR-06:00 |
May | 0.00 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 | 30-MAY-13:00 | 132.14 | 01-MAY-05:00 |
June | 0.00 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 19-JUN-12:00 | 66.26 | 03-JUN-05:00 |
July | 0.00 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.69 | 07-JUL-12:00 | 23.10 | 02-JUL-05:00 |
August | 0.00 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.34 | 24-AUG-16:00 | 51.79 | 08-AUG-05:00 |
September | 0.00 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.30 | 01-SEP-14:00 | 96.45 | 24-SEP-06:00 |
October | 0.00 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 25-OCT-11:00 | 171.11 | 09-OCT-06:00 |
November | 0.00 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 234.74 | 24-NOV-07:00 |
December | 0.00 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 273.31 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | |||
Maximum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 324.84 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 561.77 | 02-JAN-05:00 |
February | 0.00 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 578.58 | 06-FEB-03:00 |
March | 0.00 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 27-MAR-16:00 | 427.59 | 23-MAR-06:00 |
April | 0.00 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 | 07-APR-13:00 | 301.95 | 03-APR-06:00 |
May | 0.00 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.41 | 30-MAY-13:00 | 234.83 | 01-MAY-05:00 |
June | 0.00 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.02 | 19-JUN-12:00 | 124.45 | 03-JUN-03:00 |
July | 0.00 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.08 | 07-JUL-12:00 | 45.95 | 02-JUL-03:00 |
August | 0.00 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.50 | 24-AUG-16:00 | 98.24 | 08-AUG-05:00 |
September | 0.00 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 14-SEP-14:00 | 171.64 | 24-SEP-06:00 |
October | 0.00 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 | 25-OCT-11:00 | 303.82 | 09-OCT-06:00 |
November | 0.00 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 416.46 | 24-NOV-07:00 |
December | 0.00 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 484.75 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | |||
Maximum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.02 | 578.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13627.74 | 23-JAN-22:10 | 11501.89 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13301.54 | 01-FEB-22:10 | 11501.89 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14330.36 | 27-MAR-18:40 | 8945.92 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15021.89 | 07-APR-20:10 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14299.34 | 09-MAY-19:00 | 8945.92 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15084.48 | 22-JUN-20:30 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15117.92 | 13-JUL-21:10 | 11501.89 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16152.98 | 24-AUG-20:30 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16748.47 | 27-SEP-19:40 | 8945.92 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18871.03 | 31-OCT-21:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19360.65 | 22-NOV-22:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18505.93 | 01-DEC-22:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13301.54 | 8945.92 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19360.65 | 11501.89 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2122.66 | 17-JAN-13:10 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.63 |
February | 1745.33 | 02-FEB-13:30 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.23 |
March | 2392.80 | 03-MAR-13:20 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.19 |
April | 2297.52 | 08-APR-12:40 | 389.84 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
May | 2042.15 | 30-MAY-15:10 | 3898.44 | 1033.11 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 135.35 | 0.00 |
June | 2229.87 | 19-JUN-19:20 | 909.64 | 619.87 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 178.35 | 0.00 |
July | 2248.25 | 08-JUL-12:40 | 389.84 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 184.44 | 0.00 |
August | 2356.83 | 22-AUG-13:00 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 152.32 | 0.00 |
September | 2855.21 | 30-SEP-12:40 | 389.84 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
October | 3153.26 | 13-OCT-12:30 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.09 |
November | 2651.44 | 02-NOV-12:40 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.48 |
December | 2780.28 | 17-DEC-12:40 | 389.84 | 206.62 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1745.33 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3153.26 | 3898.44 | 1033.11 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 184.44 | 432.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1166.21 | 19-JAN-22:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.58 |
February | 1140.57 | 22-FEB-22:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.91 |
March | 1390.22 | 27-MAR-19:00 | 1053.36 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
April | 1616.24 | 07-APR-20:10 | 1203.84 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
May | 1630.92 | 31-MAY-21:00 | 1203.84 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.29 |
June | 1701.99 | 19-JUN-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 0.00 |
July | 1721.95 | 10-JUL-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 0.00 |
August | 1759.89 | 24-AUG-20:30 | 1203.84 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 0.00 |
September | 1711.78 | 01-SEP-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 |
October | 1605.99 | 05-OCT-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 |
November | 1364.27 | 03-NOV-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 |
December | 1180.22 | 18-DEC-22:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1140.57 | 1053.36 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1759.89 | 1354.32 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 109.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 710.92 | 23-JAN-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.52 |
February | 674.90 | 24-FEB-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.45 |
March | 935.86 | 27-MAR-17:40 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
April | 1079.63 | 07-APR-20:10 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
May | 1127.76 | 31-MAY-21:00 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 |
June | 1190.81 | 22-JUN-20:30 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 |
July | 1225.98 | 10-JUL-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 0.00 |
August | 1240.62 | 18-AUG-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 0.00 |
September | 1187.48 | 01-SEP-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 | 0.00 |
October | 1072.17 | 05-OCT-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 |
November | 919.33 | 04-NOV-13:00 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 |
December | 703.67 | 19-DEC-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 674.90 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1240.62 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 243.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 354.66 | 19-JAN-22:00 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.15 |
February | 229.16 | 23-FEB-22:00 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.52 |
March | 500.23 | 27-MAR-18:50 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
April | 577.40 | 07-APR-20:10 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 600.06 | 31-MAY-21:00 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
June | 640.62 | 19-JUN-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 46.74 | 0.00 |
July | 660.84 | 10-JUL-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 | 0.00 |
August | 671.66 | 04-AUG-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 0.00 |
September | 639.17 | 01-SEP-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 0.00 |
October | 580.63 | 05-OCT-13:50 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 | 0.00 |
November | 505.05 | 04-NOV-13:00 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 |
December | 361.84 | 19-DEC-22:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 229.16 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 671.66 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 131.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35953.63 | 19-JAN-21:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 333.11 |
February | 35828.05 | 17-FEB-21:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 386.52 |
March | 36897.23 | 27-MAR-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 |
April | 37580.52 | 07-APR-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
May | 37740.43 | 31-MAY-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 |
June | 38126.64 | 19-JUN-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 87.98 | 0.00 |
July | 38113.79 | 10-JUL-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
August | 38277.18 | 04-AUG-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 119.23 | 0.00 |
September | 37987.28 | 01-SEP-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 39.73 | 0.00 |
October | 37550.52 | 04-OCT-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 77.72 |
November | 36904.36 | 03-NOV-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 |
December | 36006.68 | 19-DEC-21:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 258.18 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35828.05 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38277.18 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 119.23 | 386.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8987.63 | 17-JAN-13:00 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.60 |
February | 8104.91 | 20-FEB-13:00 | 5122.80 | 311.38 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.20 |
March | 9813.40 | 03-MAR-13:10 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.14 |
April | 10012.90 | 08-APR-12:40 | 5122.80 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 |
May | 9676.10 | 31-MAY-21:20 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.95 |
June | 10530.79 | 19-JUN-21:20 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 262.36 | 0.00 |
July | 10475.82 | 10-JUL-21:30 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 171.89 | 0.00 |
August | 11442.15 | 04-AUG-21:10 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 0.00 |
September | 11653.04 | 30-SEP-12:30 | 5122.80 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.35 |
October | 11503.40 | 13-OCT-12:30 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 |
November | 10858.14 | 04-NOV-12:30 | 5122.80 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.71 |
December | 11637.63 | 17-DEC-12:40 | 5122.80 | 311.38 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8104.91 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11653.04 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 891.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26111.76 | 19-JAN-22:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2232.14 |
February | 25470.08 | 22-FEB-22:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2668.41 |
March | 29904.15 | 27-MAR-19:00 | 35484.54 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.01 |
April | 34201.07 | 07-APR-20:20 | 40553.76 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.94 |
May | 34313.51 | 31-MAY-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.74 |
June | 35875.93 | 22-JUN-20:30 | 40553.76 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 321.12 | 0.00 |
July | 36136.36 | 10-JUL-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 389.50 | 0.00 |
August | 36755.02 | 24-AUG-20:30 | 40553.76 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 291.75 | 0.00 |
September | 36005.59 | 01-SEP-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 331.92 | 0.00 |
October | 34109.13 | 05-OCT-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.37 |
November | 29765.27 | 03-NOV-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1346.21 |
December | 26274.06 | 18-DEC-22:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2694.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25470.08 | 35484.54 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36755.02 | 45622.98 | 10746.77 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 389.50 | 2694.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2701.16 | 19-JAN-16:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.44 |
February | 2709.34 | 22-FEB-16:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.64 |
March | 2737.57 | 27-MAR-18:01 | 970.20 | 1446.67 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 |
April | 2835.66 | 10-APR-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 |
May | 2994.58 | 20-MAY-18:01 | 819.00 | 1630.05 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
June | 3025.31 | 26-JUN-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 0.00 |
July | 3022.72 | 13-JUL-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.26 | 0.00 |
August | 3050.09 | 04-AUG-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 | 0.00 |
September | 3019.99 | 07-SEP-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 | 0.00 |
October | 2868.04 | 02-OCT-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
November | 2765.92 | 02-NOV-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 |
December | 2702.35 | 17-DEC-16:01 | 378.00 | 101.88 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2701.16 | 378.00 | 101.88 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3050.09 | 970.20 | 1630.05 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 | 133.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2220.99 | 17-JAN-16:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.07 |
February | 2438.79 | 20-FEB-16:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.72 |
March | 2651.54 | 11-MAR-16:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.90 |
April | 2863.51 | 07-APR-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 0.00 |
May | 2979.22 | 31-MAY-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 0.00 |
June | 3011.24 | 26-JUN-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 |
July | 3014.05 | 13-JUL-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.37 | 0.00 |
August | 3021.63 | 16-AUG-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 | 0.00 |
September | 2974.43 | 06-SEP-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 0.00 |
October | 2903.42 | 25-OCT-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
November | 2673.85 | 02-NOV-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 |
December | 1907.75 | 17-DEC-16:01 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1907.75 | 324.00 | 87.31 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3021.63 | 680.40 | 130.39 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 | 102.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 144.20 | 31-JAN-15:15 | 0.00 | 18.29 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.28 |
February | 265.15 | 03-FEB-12:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 |
March | 333.77 | 03-MAR-13:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
April | 427.68 | 07-APR-12:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
May | 296.45 | 29-MAY-19:10 | 0.00 | 146.35 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
June | 373.23 | 19-JUN-20:20 | 0.00 | 129.88 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
July | 368.07 | 08-JUL-08:00 | 0.00 | 82.32 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
August | 429.53 | 30-AUG-12:40 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
September | 555.76 | 28-SEP-12:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 |
October | 605.02 | 04-OCT-12:00 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 |
November | 536.96 | 02-NOV-12:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 |
December | 409.60 | 17-DEC-13:00 | 0.00 | 9.15 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 144.20 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 605.02 | 0.00 | 146.35 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 59.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 816.11 | 21-JAN-09:02 | 270.00 | 170.78 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 |
February | 830.91 | 20-FEB-09:02 | 270.00 | 170.78 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 |
March | 888.15 | 28-MAR-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 |
April | 990.85 | 07-APR-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 0.00 |
May | 1028.19 | 20-MAY-18:01 | 819.00 | 1024.70 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 |
June | 1029.94 | 22-JUN-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 0.00 |
July | 1036.72 | 11-JUL-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 0.00 |
August | 1029.26 | 24-AUG-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 |
September | 1023.08 | 10-SEP-18:01 | 819.00 | 1024.70 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
October | 968.78 | 25-OCT-15:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
November | 874.37 | 03-NOV-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 |
December | 823.89 | 17-DEC-09:02 | 324.00 | 204.94 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 816.11 | 270.00 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1036.72 | 831.60 | 1024.70 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 40.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2221.18 | 17-JAN-16:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.66 |
February | 2353.88 | 25-FEB-09:02 | 324.00 | 326.01 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 |
March | 2464.47 | 29-MAR-08:62 | 216.00 | 611.27 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.91 |
April | 2637.12 | 07-APR-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 |
May | 2692.84 | 20-MAY-18:01 | 819.00 | 1630.05 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
June | 2743.84 | 26-JUN-08:61 | 252.00 | 713.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 0.00 |
July | 2789.45 | 14-JUL-08:62 | 216.00 | 611.27 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 0.00 |
August | 2774.17 | 22-AUG-08:62 | 216.00 | 611.27 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 0.00 |
September | 2720.90 | 06-SEP-08:61 | 252.00 | 713.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
October | 2646.81 | 04-OCT-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
November | 2505.50 | 02-NOV-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 |
December | 2391.03 | 17-DEC-09:02 | 324.00 | 326.01 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2221.18 | 216.00 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2789.45 | 819.00 | 1630.05 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 180.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 802.21 | 19-JAN-09:02 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.52 |
February | 2219.85 | 25-FEB-09:02 | 324.00 | 325.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.97 |
March | 2445.42 | 29-MAR-08:62 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.79 |
April | 2644.68 | 07-APR-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 0.00 |
May | 2700.33 | 29-MAY-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 0.00 |
June | 2733.13 | 26-JUN-08:61 | 252.00 | 713.06 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 0.00 |
July | 2725.52 | 12-JUL-08:62 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 0.00 |
August | 2752.21 | 22-AUG-08:62 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 0.00 |
September | 2670.71 | 06-SEP-08:61 | 252.00 | 713.06 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 0.00 |
October | 2634.11 | 25-OCT-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
November | 2274.76 | 04-NOV-08:62 | 324.00 | 325.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 |
December | 1933.41 | 17-DEC-09:02 | 324.00 | 325.97 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 802.21 | 216.00 | 87.31 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2752.21 | 680.40 | 713.06 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 175.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1164.17 | 17-JAN-13:30 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.27 |
February | 1161.71 | 20-FEB-13:00 | 0.00 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.29 |
March | 1569.40 | 27-MAR-18:20 | 0.00 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
April | 1828.20 | 08-APR-11:40 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
May | 1862.08 | 30-MAY-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
June | 1921.19 | 22-JUN-19:10 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 | 0.00 |
July | 1932.03 | 10-JUL-20:00 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 0.00 |
August | 1967.35 | 24-AUG-19:10 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.37 | 0.00 |
September | 1901.27 | 01-SEP-21:10 | 0.00 | 1493.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.66 | 0.00 |
October | 1863.00 | 04-OCT-14:00 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 0.00 |
November | 1617.85 | 04-NOV-12:50 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 |
December | 1300.13 | 17-DEC-13:00 | 0.00 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1161.71 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1967.35 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.37 | 100.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2823.60 | 19-JAN-16:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.89 |
February | 2817.86 | 22-FEB-16:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.70 |
March | 2880.11 | 27-MAR-18:01 | 970.20 | 1446.67 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 |
April | 2967.39 | 10-APR-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
May | 3139.73 | 20-MAY-18:01 | 819.00 | 1630.05 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 |
June | 3175.85 | 25-JUN-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 | 0.00 |
July | 3167.70 | 13-JUL-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | 0.00 |
August | 3218.71 | 02-AUG-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 | 0.00 |
September | 3129.53 | 14-SEP-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 34.11 | 0.00 |
October | 2927.89 | 30-OCT-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 |
November | 2889.99 | 02-NOV-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 |
December | 2823.36 | 17-DEC-16:01 | 378.00 | 101.88 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2817.86 | 324.00 | 87.32 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3218.71 | 970.20 | 1630.05 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 | 133.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1535.35 | 17-JAN-16:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 |
February | 2466.24 | 20-FEB-16:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 |
March | 2805.38 | 27-MAR-18:01 | 970.20 | 1446.50 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
April | 2926.39 | 07-APR-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
May | 3096.06 | 20-MAY-18:01 | 819.00 | 1629.86 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 |
June | 3137.61 | 15-JUN-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 0.00 |
July | 3129.33 | 13-JUL-18:02 | 831.60 | 1239.86 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 | 0.00 |
August | 3147.19 | 02-AUG-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 0.00 |
September | 3112.55 | 07-SEP-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 0.00 |
October | 3008.03 | 04-OCT-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 0.00 |
November | 2760.94 | 02-NOV-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
December | 983.23 | 17-DEC-16:01 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 983.23 | 324.00 | 87.31 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3147.19 | 970.20 | 1629.86 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 101.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1384.47 | 19-JAN-16:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 |
February | 1375.81 | 02-FEB-16:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.20 |
March | 1389.53 | 15-MAR-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 |
April | 1420.07 | 16-APR-15:01 | 378.00 | 64.04 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
May | 1491.14 | 31-MAY-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
June | 1523.32 | 15-JUN-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
July | 1526.82 | 10-JUL-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
August | 1546.65 | 24-AUG-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 0.00 |
September | 1523.93 | 05-SEP-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
October | 1505.57 | 04-OCT-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 0.00 |
November | 1407.93 | 02-NOV-15:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 |
December | 1389.20 | 17-DEC-16:01 | 378.00 | 64.04 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1375.81 | 378.00 | 64.04 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1546.65 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 69.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17354.83 | 23-JAN-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.81 |
February | 16696.56 | 23-FEB-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.13 |
March | 18348.64 | 27-MAR-21:30 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.23 |
April | 19485.59 | 07-APR-21:40 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.80 |
May | 20564.07 | 31-MAY-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 |
June | 22010.97 | 19-JUN-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
July | 22039.38 | 10-JUL-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 0.00 |
August | 22421.60 | 04-AUG-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 0.00 |
September | 21221.52 | 01-SEP-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
October | 19342.49 | 05-OCT-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.70 |
November | 18276.32 | 03-NOV-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.25 |
December | 17139.39 | 04-DEC-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16696.56 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22421.60 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 337.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19416.28 | 23-JAN-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.82 |
February | 18700.79 | 23-FEB-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.14 |
March | 20372.32 | 27-MAR-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.61 |
April | 21371.68 | 07-APR-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.36 |
May | 22229.11 | 31-MAY-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 |
June | 23671.22 | 19-JUN-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
July | 23528.32 | 07-JUL-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 | 0.00 |
August | 23891.32 | 04-AUG-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 0.00 |
September | 22797.41 | 01-SEP-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
October | 21079.17 | 05-OCT-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 |
November | 20175.12 | 03-NOV-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.25 |
December | 19166.72 | 04-DEC-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18700.79 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23891.32 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 337.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25588.58 | 17-JAN-11:50 | 533.71 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 252.95 |
February | 25979.24 | 19-FEB-11:50 | 800.57 | 318.24 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 275.67 |
March | 27387.68 | 27-MAR-18:03 | 13075.94 | 5940.53 | 104389.99 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 |
April | 29466.34 | 08-APR-10:50 | 1601.14 | 530.40 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
May | 30070.58 | 29-MAY-10:40 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
June | 30858.93 | 01-JUN-18:07 | 11207.95 | 5091.89 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 51.41 | 0.00 |
July | 30416.50 | 08-JUL-10:50 | 800.57 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.32 | 0.00 |
August | 31516.39 | 22-AUG-17:56 | 6671.40 | 3182.43 | 74564.28 | 112464.16 | 0.00 | 0.00 | 0.00 | 50.71 | 0.00 |
September | 29965.55 | 04-SEP-10:50 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.46 | 0.00 |
October | 29050.87 | 22-OCT-10:50 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 55.82 |
November | 28105.32 | 04-NOV-10:45 | 1601.14 | 530.40 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 109.96 |
December | 26374.21 | 17-DEC-11:50 | 800.57 | 318.24 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 200.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25588.58 | 533.71 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31516.39 | 13075.94 | 5940.53 | 104389.99 | 112464.16 | 0.00 | 0.00 | 0.00 | 98.32 | 275.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2640.98 | 17-JAN-14:00 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.69 |
February | 2548.33 | 20-FEB-13:40 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.34 |
March | 3636.25 | 27-MAR-13:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
April | 4027.89 | 08-APR-13:30 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 |
May | 4233.17 | 31-MAY-13:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 | 0.00 |
June | 4384.45 | 19-JUN-14:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.38 | 0.00 |
July | 4523.28 | 10-JUL-14:00 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.79 | 0.00 |
August | 4523.41 | 18-AUG-13:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.33 | 0.00 |
September | 4349.11 | 01-SEP-13:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 | 0.00 |
October | 4087.61 | 04-OCT-13:40 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 0.00 |
November | 3516.36 | 04-NOV-12:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
December | 2817.60 | 17-DEC-13:20 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2548.33 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4523.41 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.38 | 193.34 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.406253E+12 | 268584.20 | 23-JAN-20:49 | 0.522870E+12 | 432389.46 | 14-JAN-17:30 |
February | 0.367982E+12 | 266980.19 | 23-FEB-20:00 | 0.467774E+12 | 447627.20 | 06-FEB-19:10 |
March | 0.408094E+12 | 293866.29 | 27-MAR-19:10 | 0.431710E+12 | 396364.98 | 28-MAR-17:49 |
April | 0.408768E+12 | 342435.25 | 07-APR-19:10 | 0.406683E+12 | 387041.17 | 24-APR-17:00 |
May | 0.471001E+12 | 365692.09 | 31-MAY-19:19 | 0.375428E+12 | 386420.80 | 01-MAY-19:19 |
June | 0.613903E+12 | 427339.41 | 19-JUN-19:30 | 0.330324E+12 | 278719.01 | 06-JUN-17:30 |
July | 0.726900E+12 | 451095.93 | 20-JUL-19:49 | 0.332629E+12 | 285393.40 | 11-JUL-17:49 |
August | 0.690219E+12 | 460423.49 | 04-AUG-19:10 | 0.329383E+12 | 282309.00 | 22-AUG-16:19 |
September | 0.556387E+12 | 409532.21 | 22-SEP-18:10 | 0.330757E+12 | 281017.15 | 26-SEP-17:10 |
October | 0.477016E+12 | 362148.39 | 05-OCT-19:10 | 0.383966E+12 | 389619.46 | 08-OCT-17:00 |
November | 0.396903E+12 | 276332.45 | 06-NOV-20:00 | 0.434307E+12 | 403683.57 | 06-NOV-18:00 |
December | 0.408878E+12 | 270195.43 | 19-DEC-20:00 | 0.449603E+12 | 412776.91 | 31-DEC-19:10 |
Annual Sum or Average | 0.593230E+13 | 0.479543E+13 | ||||
Minimum of Months | 0.367982E+12 | 266980.19 | 0.329383E+12 | 278719.01 | ||
Maximum of Months | 0.726900E+12 | 460423.49 | 0.522870E+12 | 447627.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.699067E+11 | 0.168825E+11 | 0.148212E+12 | 0.826626E+11 | 0.460363E+11 | 0.376321E+10 | 0.00 | 0.981377E+09 | 0.00 | 0.00 | 0.249287E+11 | 0.770524E+10 | 0.00 |
February | 0.630022E+11 | 0.141581E+11 | 0.133859E+12 | 0.746630E+11 | 0.416643E+11 | 0.377483E+10 | 0.00 | 0.143377E+10 | 0.00 | 0.00 | 0.238099E+11 | 0.696273E+10 | 0.00 |
March | 0.696925E+11 | 0.141768E+11 | 0.148234E+12 | 0.826646E+11 | 0.458781E+11 | 0.502998E+10 | 0.00 | 0.707875E+10 | 0.00 | 0.00 | 0.224232E+11 | 0.770498E+10 | 0.00 |
April | 0.671460E+11 | 0.122193E+11 | 0.143397E+12 | 0.799956E+11 | 0.446252E+11 | 0.654620E+10 | 0.00 | 0.294602E+11 | 0.00 | 0.00 | 0.128498E+11 | 0.746541E+10 | 0.00 |
May | 0.692642E+11 | 0.112966E+11 | 0.148223E+12 | 0.826632E+11 | 0.463109E+11 | 0.818411E+10 | 0.00 | 0.874257E+11 | 0.00 | 0.00 | 0.466468E+10 | 0.770529E+10 | 0.00 |
June | 0.669750E+11 | 0.102305E+11 | 0.143446E+12 | 0.799974E+11 | 0.453531E+11 | 0.914553E+10 | 0.00 | 0.229139E+12 | 0.00 | 0.00 | 0.170491E+11 | 0.745826E+10 | 0.00 |
July | 0.690930E+11 | 0.108851E+11 | 0.148174E+12 | 0.826612E+11 | 0.482561E+11 | 0.102822E+11 | 0.00 | 0.318723E+12 | 0.00 | 0.00 | 0.258591E+11 | 0.771406E+10 | 0.00 |
August | 0.694239E+11 | 0.120198E+11 | 0.148234E+12 | 0.826644E+11 | 0.484092E+11 | 0.974621E+10 | 0.00 | 0.285313E+12 | 0.00 | 0.00 | 0.214257E+11 | 0.770590E+10 | 0.00 |
September | 0.672466E+11 | 0.130609E+11 | 0.143397E+12 | 0.799957E+11 | 0.446804E+11 | 0.859706E+10 | 0.00 | 0.176439E+12 | 0.00 | 0.00 | 0.104014E+11 | 0.746611E+10 | 0.00 |
October | 0.697359E+11 | 0.150559E+11 | 0.148212E+12 | 0.826625E+11 | 0.466398E+11 | 0.815437E+10 | 0.00 | 0.844139E+11 | 0.00 | 0.00 | 0.918357E+10 | 0.770521E+10 | 0.00 |
November | 0.676321E+11 | 0.159412E+11 | 0.143462E+12 | 0.799966E+11 | 0.449414E+11 | 0.555517E+10 | 0.00 | 0.968468E+10 | 0.00 | 0.00 | 0.172017E+11 | 0.744955E+10 | 0.00 |
December | 0.698276E+11 | 0.172130E+11 | 0.148174E+12 | 0.826617E+11 | 0.460528E+11 | 0.389977E+10 | 0.00 | 0.255980E+10 | 0.00 | 0.00 | 0.255973E+11 | 0.771321E+10 | 0.00 |
Annual Sum or Average | 0.818946E+12 | 0.163140E+12 | 0.174502E+13 | 0.973288E+12 | 0.548847E+12 | 0.826786E+11 | 0.00 | 0.123265E+13 | 0.215394E+12 | 0.907560E+11 | |||
Minimum of Months | 0.630022E+11 | 0.102305E+11 | 0.133859E+12 | 0.746630E+11 | 0.416643E+11 | 0.376321E+10 | 0.00 | 0.981377E+09 | 0.00 | 0.00 | 0.466468E+10 | 0.696273E+10 | 0.00 |
Maximum of Months | 0.699067E+11 | 0.172130E+11 | 0.148234E+12 | 0.826646E+11 | 0.484092E+11 | 0.102822E+11 | 0.00 | 0.318723E+12 | 0.00 | 0.00 | 0.258591E+11 | 0.771406E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.178464E+12 | 0.00 | 0.192488E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.155385E+12 | 0.00 | 0.175185E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.876374E+11 | 0.00 | 0.192034E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.793821E+11 | 0.00 | 0.180345E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.439296E+11 | 0.00 | 0.179520E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.157291E+11 | 0.00 | 0.167481E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.122657E+11 | 0.00 | 0.168543E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.991744E+10 | 0.00 | 0.167427E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.194780E+11 | 0.00 | 0.164324E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.569456E+11 | 0.00 | 0.175102E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.111491E+12 | 0.00 | 0.175724E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.109365E+12 | 0.00 | 0.188417E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.879991E+12 | 0.212659E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.991744E+10 | 0.00 | 0.164324E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.178464E+12 | 0.00 | 0.192488E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 73068.04 | 02-JAN-20:10 | 10390.54 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 62600.61 | 02-JAN-07:19 | 24299.39 | 02-JAN-19:10 | 4145.62 | 11-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 73068.04 | 01-FEB-20:10 | 10390.54 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 62600.61 | 01-FEB-07:19 | 24782.15 | 06-FEB-19:19 | 4466.58 | 06-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 73068.04 | 01-MAR-20:10 | 10390.54 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 62600.61 | 13-MAR-06:19 | 25898.73 | 28-MAR-18:10 | 4159.65 | 06-MAR-07:19 | 0.00 | 01-MAR-00:10 |
April | 73068.04 | 03-APR-19:10 | 10390.54 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 62599.95 | 14-APR-06:19 | 26794.37 | 28-APR-18:10 | 4135.47 | 22-APR-22:40 | 0.00 | 01-APR-00:10 |
May | 73068.04 | 01-MAY-19:10 | 10390.54 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 62599.95 | 04-MAY-06:19 | 27398.78 | 11-MAY-18:10 | 4138.73 | 31-MAY-18:19 | 0.00 | 01-MAY-00:10 |
June | 73068.04 | 01-JUN-19:19 | 10390.54 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 62599.55 | 16-JUN-06:19 | 27989.12 | 22-JUN-20:19 | 5496.94 | 24-JUN-18:49 | 0.00 | 01-JUN-00:10 |
July | 73068.04 | 03-JUL-19:19 | 10390.54 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 62599.95 | 24-JUL-06:19 | 27822.40 | 11-JUL-18:19 | 5394.89 | 05-JUL-20:19 | 0.00 | 01-JUL-00:10 |
August | 73068.04 | 01-AUG-19:10 | 10390.54 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 62599.95 | 16-AUG-06:19 | 29140.92 | 24-AUG-20:19 | 5037.64 | 10-AUG-20:00 | 0.00 | 01-AUG-00:10 |
September | 73068.04 | 01-SEP-19:10 | 10390.54 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 62600.52 | 27-SEP-06:19 | 25497.83 | 07-SEP-18:10 | 5106.08 | 22-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 73068.04 | 02-OCT-19:10 | 10390.54 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 62600.61 | 06-OCT-06:19 | 27556.42 | 30-OCT-20:30 | 4297.33 | 24-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 73068.04 | 01-NOV-19:10 | 10390.54 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 62600.61 | 01-NOV-06:19 | 27126.77 | 01-NOV-20:00 | 4162.25 | 16-NOV-23:40 | 0.00 | 01-NOV-00:10 |
December | 73068.04 | 01-DEC-20:10 | 10390.54 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 62600.61 | 01-DEC-07:19 | 25165.22 | 04-DEC-21:00 | 4149.87 | 19-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 73068.04 | 10390.54 | 89475.41 | 62599.55 | 24299.39 | 4135.47 | 0.00 | |||||||
Maximum of Months | 73068.04 | 10390.54 | 89475.41 | 62600.61 | 29140.92 | 5496.94 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6175.85 | 17-JAN-16:10 | 0.00 | 0.00 | 10206.30 | 01-JAN-09:09 | 4738.17 | 09-JAN-19:10 | 0.00 |
February | 8787.46 | 03-FEB-12:39 | 0.00 | 0.00 | 10206.30 | 01-FEB-09:09 | 4738.49 | 03-FEB-19:10 | 0.00 |
March | 77244.40 | 27-MAR-15:00 | 0.00 | 0.00 | 10206.30 | 05-MAR-16:10 | 4738.27 | 03-MAR-19:10 | 0.00 |
April | 99273.95 | 07-APR-15:09 | 0.00 | 0.00 | 10206.30 | 01-APR-15:09 | 4738.76 | 10-APR-18:10 | 0.00 |
May | 119033.27 | 31-MAY-15:20 | 0.00 | 0.00 | 10206.30 | 28-MAY-15:09 | 4738.51 | 08-MAY-18:10 | 0.00 |
June | 176521.59 | 19-JUN-16:00 | 0.00 | 0.00 | 10206.30 | 01-JUN-15:09 | 4738.31 | 22-JUN-18:10 | 0.00 |
July | 180977.92 | 20-JUL-19:00 | 0.00 | 0.00 | 10206.30 | 01-JUL-08:09 | 4738.41 | 27-JUL-18:10 | 0.00 |
August | 192755.16 | 04-AUG-19:10 | 0.00 | 0.00 | 10206.30 | 01-AUG-08:09 | 4738.27 | 03-AUG-18:10 | 0.00 |
September | 160401.36 | 22-SEP-18:10 | 0.00 | 0.00 | 10206.30 | 01-SEP-08:09 | 4738.29 | 14-SEP-18:10 | 0.00 |
October | 121939.26 | 05-OCT-15:09 | 0.00 | 0.00 | 10206.30 | 04-OCT-15:09 | 4738.61 | 20-OCT-18:10 | 0.00 |
November | 54322.46 | 10-NOV-09:00 | 0.00 | 0.00 | 10206.30 | 06-NOV-09:09 | 4738.52 | 24-NOV-19:10 | 0.00 |
December | 13553.80 | 17-DEC-12:00 | 0.00 | 0.00 | 10206.30 | 01-DEC-09:09 | 4738.46 | 22-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 6175.85 | 0.00 | 0.00 | 10206.30 | 4738.17 | 0.00 | |||
Maximum of Months | 192755.16 | 0.00 | 0.00 | 10206.30 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 268584.20 | 23-JAN-20:49 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 23016.85 | 3146.41 | 0.00 | 3146.20 | 0.00 |
February | 266980.19 | 23-FEB-20:00 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 22684.40 | 3220.45 | 0.00 | 2007.30 | 0.00 |
March | 293866.29 | 27-MAR-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 20198.64 | 3042.77 | 0.00 | 41792.43 | 0.00 |
April | 342435.25 | 07-APR-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 21852.49 | 3551.44 | 0.00 | 87367.96 | 0.00 |
May | 365692.09 | 31-MAY-19:19 | 73068.04 | 88772.42 | 10390.54 | 50350.88 | 23358.02 | 3947.49 | 0.00 | 100701.51 | 0.00 |
June | 427339.41 | 19-JUN-19:30 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 24929.54 | 4171.51 | 0.00 | 159243.01 | 0.00 |
July | 451095.93 | 20-JUL-19:49 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 26487.89 | 4809.81 | 0.00 | 180530.13 | 0.00 |
August | 460423.49 | 04-AUG-19:10 | 73068.04 | 88772.42 | 10390.54 | 50343.95 | 24891.00 | 4577.89 | 0.00 | 192755.16 | 0.00 |
September | 409532.21 | 22-SEP-18:10 | 64910.82 | 79417.81 | 10390.54 | 50121.48 | 23355.87 | 5106.08 | 0.00 | 160401.36 | 0.00 |
October | 362148.39 | 05-OCT-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 21552.14 | 3988.84 | 0.00 | 99019.67 | 0.00 |
November | 276332.45 | 06-NOV-20:00 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 25382.58 | 2878.82 | 0.00 | 8807.22 | 0.00 |
December | 270195.43 | 19-DEC-20:00 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 24114.91 | 3017.65 | 0.00 | 4659.92 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 266980.19 | 64910.82 | 79417.81 | 10390.54 | 50121.48 | 20198.64 | 2878.82 | 0.00 | 2007.30 | 0.00 | |
Maximum of Months | 460423.49 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 26487.89 | 5106.08 | 0.00 | 192755.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 225392.30 | 02-JAN-09:09 | 0.00 | 177727.86 | 30-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 230358.92 | 06-FEB-09:09 | 0.00 | 177769.58 | 09-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 136444.77 | 21-MAR-15:20 | 0.00 | 177616.87 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 143172.73 | 18-APR-17:40 | 0.00 | 176862.97 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 133122.68 | 04-MAY-03:00 | 0.00 | 175899.05 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 25843.92 | 10-JUN-10:00 | 0.00 | 174807.16 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 21045.21 | 19-JUL-01:19 | 0.00 | 173913.63 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 36109.08 | 20-AUG-13:00 | 0.00 | 173628.37 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 126699.81 | 24-SEP-05:00 | 0.00 | 174164.66 | 28-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 133657.43 | 02-OCT-03:30 | 0.00 | 175167.00 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 157016.93 | 12-NOV-09:09 | 0.00 | 176280.75 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 169425.17 | 31-DEC-23:00 | 0.00 | 177193.89 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 21045.21 | 0.00 | 173628.37 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 230358.92 | 0.00 | 177769.58 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.60 | 3.83 | 24.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.60 | 3.50 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 24.62 | 9.67 | 24.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.64 | 8.33 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.65 | 1.00 | 24.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.67 | 3.83 | 24.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.61 | 7.50 | 24.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.61 | 6.33 | 24.61 |
Annual Sum or Average | 0.00 | 0.00 | 44.00 | 24.62 | 44.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 24.67 | 9.67 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.48 | 1.17 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.53 | 0.67 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 20.51 | 2.17 | 20.51 | 1.33 | 21.71 | 1.33 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.55 | 1.17 | 20.55 | 0.50 | 21.72 | 0.50 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.49 | 2.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.83 | 20.51 | 1.83 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.50 | 20.50 | 4.50 | 20.50 | 0.17 | 21.69 | 0.17 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.54 | 2.33 | 20.54 | 0.17 | 21.69 | 0.17 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.42 | 1.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.73 | 1.67 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.76 | 5.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 21.76 | 12.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.74 | 7.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.78 | 2.50 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 20.40 | 1.83 | 20.40 | 30.33 | 21.75 | 30.33 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.42 | 1.17 | 20.42 | 12.67 | 21.78 | 12.67 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.53 | 0.83 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.50 | 2.83 | 20.50 | 1.17 | 21.73 | 1.17 | 21.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.53 | 1.67 | 20.53 | 0.50 | 21.75 | 0.50 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.49 | 3.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.00 | 20.52 | 3.00 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.55 | 0.50 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.53 | 1.00 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.00 | 20.51 | 8.00 | 20.51 | 1.33 | 21.73 | 1.33 | 21.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.55 | 3.33 | 20.55 | 0.50 | 21.83 | 0.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.78 | 0.83 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.69 | 1.00 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.74 | 1.17 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.78 | 3.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 20.48 | 1.83 | 20.48 | 8.33 | 21.76 | 8.33 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.54 | 1.00 | 20.54 | 3.17 | 21.79 | 3.17 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.44 | 1.83 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.47 | 1.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.68 | 0.67 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.72 | 2.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.67 | 20.46 | 3.67 | 20.46 | 4.67 | 21.72 | 4.67 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.52 | 1.83 | 20.52 | 2.17 | 21.77 | 2.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.42 | 0.83 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.69 | 1.00 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.79 | 2.67 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.78 | 5.33 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.85 | 3.50 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.85 | 3.50 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
December | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.46 | 1.50 | 20.46 | 18.17 | 21.80 | 18.17 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.52 | 0.83 | 20.52 | 5.33 | 21.89 | 5.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 24.66 | 16.33 | 24.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.68 | 15.17 | 24.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 24.72 | 41.33 | 24.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 24.72 | 37.17 | 24.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.63 | 4.17 | 24.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 24.72 | 17.17 | 24.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 24.68 | 26.67 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 24.67 | 18.83 | 24.67 |
Annual Sum or Average | 0.00 | 0.00 | 177.00 | 24.70 | 177.00 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 24.72 | 41.33 | 24.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 672.00 | 22.69 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 744.00 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.87 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.36 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 621.33 | 23.28 | 4.67 | 23.96 | 0.00 | 0.00 |
November | 540.17 | 23.72 | 5.00 | 23.95 | 0.00 | 0.00 |
December | 728.83 | 23.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8442.33 | 22.33 | 9.67 | 23.96 | 0.00 | |
Minimum of Months | 540.17 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.72 | 5.00 | 23.96 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.83 | 21.08 | 362.33 | 21.00 | 362.33 | 21.00 |
February | 666.83 | 21.14 | 337.33 | 21.00 | 337.33 | 21.00 |
March | 728.00 | 21.15 | 129.83 | 21.05 | 127.67 | 21.00 |
April | 712.83 | 21.14 | 22.50 | 21.35 | 19.33 | 21.00 |
May | 744.00 | 21.15 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 710.17 | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 682.17 | 21.72 | 5.67 | 23.20 | 0.00 | 0.00 |
August | 556.00 | 21.83 | 74.00 | 23.41 | 0.00 | 0.00 |
September | 634.50 | 21.48 | 44.67 | 23.68 | 0.00 | 0.00 |
October | 619.67 | 21.53 | 72.00 | 23.81 | 0.00 | 0.00 |
November | 698.83 | 21.18 | 100.50 | 21.18 | 94.50 | 21.00 |
December | 725.33 | 21.12 | 319.33 | 21.01 | 318.33 | 21.00 |
Annual Sum or Average | 8216.17 | 21.31 | 1468.17 | 21.37 | 1259.50 | 21.00 |
Minimum of Months | 556.00 | 21.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.83 | 362.33 | 23.81 | 362.33 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 38.50 | 21.00 | 38.50 | 21.00 |
February | 672.00 | 21.44 | 41.83 | 21.00 | 41.83 | 21.00 |
March | 744.00 | 21.77 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.87 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.87 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 718.00 | 21.90 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 726.33 | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 700.50 | 22.23 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 715.00 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 732.83 | 22.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.59 | 2.83 | 21.00 | 2.83 | 21.00 |
Annual Sum or Average | 8680.67 | 21.85 | 83.17 | 21.00 | 83.17 | 21.00 |
Minimum of Months | 672.00 | 21.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.30 | 41.83 | 21.00 | 41.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.00 | 22.34 | 346.50 | 23.55 | 132.83 | 24.13 |
February | 317.67 | 22.29 | 293.83 | 23.66 | 112.83 | 24.14 |
March | 288.17 | 22.65 | 388.00 | 23.48 | 147.00 | 24.14 |
April | 275.33 | 22.72 | 386.17 | 23.29 | 151.17 | 24.07 |
May | 290.50 | 22.66 | 396.00 | 22.96 | 163.00 | 23.95 |
June | 206.67 | 23.02 | 400.17 | 22.49 | 143.83 | 23.91 |
July | 185.17 | 23.27 | 489.33 | 22.17 | 145.17 | 23.90 |
August | 187.00 | 23.29 | 508.33 | 22.18 | 147.33 | 23.91 |
September | 231.00 | 22.86 | 392.67 | 22.62 | 147.67 | 23.92 |
October | 263.17 | 22.83 | 427.83 | 22.98 | 160.83 | 23.98 |
November | 283.67 | 22.64 | 378.67 | 23.43 | 144.00 | 24.10 |
December | 297.83 | 22.48 | 353.67 | 23.58 | 130.50 | 24.15 |
Annual Sum or Average | 3177.17 | 22.70 | 4761.17 | 22.97 | 1726.17 | 24.02 |
Minimum of Months | 185.17 | 22.29 | 293.83 | 22.17 | 112.83 | 23.90 |
Maximum of Months | 351.00 | 23.29 | 508.33 | 23.66 | 163.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.67 | 21.45 | 91.83 | 21.14 | 87.67 | 21.00 |
February | 647.17 | 21.53 | 65.17 | 21.18 | 61.33 | 21.00 |
March | 712.00 | 21.88 | 10.17 | 23.90 | 0.00 | 0.00 |
April | 692.67 | 21.95 | 7.00 | 23.25 | 0.00 | 0.00 |
May | 721.67 | 22.02 | 9.50 | 23.00 | 5.67 | 22.80 |
June | 582.67 | 21.98 | 35.83 | 23.34 | 0.17 | 22.78 |
July | 410.17 | 22.00 | 156.50 | 23.32 | 0.00 | 0.00 |
August | 255.83 | 22.06 | 273.00 | 23.32 | 0.00 | 0.00 |
September | 448.67 | 22.08 | 134.33 | 23.31 | 1.00 | 22.80 |
October | 433.50 | 22.52 | 225.33 | 23.52 | 24.33 | 23.44 |
November | 662.83 | 21.91 | 18.67 | 23.77 | 1.00 | 22.58 |
December | 707.67 | 21.65 | 30.50 | 22.66 | 13.50 | 21.00 |
Annual Sum or Average | 7001.50 | 21.88 | 1057.83 | 23.03 | 194.67 | 21.38 |
Minimum of Months | 255.83 | 21.45 | 7.00 | 21.14 | 0.00 | 0.00 |
Maximum of Months | 726.67 | 22.52 | 273.00 | 23.90 | 87.67 | 23.44 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.88 | 6.50 | 21.00 | 6.50 | 21.00 |
February | 672.00 | 21.95 | 0.17 | 21.00 | 0.17 | 21.00 |
March | 742.67 | 22.27 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 709.67 | 22.30 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 718.00 | 22.21 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 670.67 | 22.12 | 3.83 | 23.54 | 0.00 | 0.00 |
July | 635.67 | 22.18 | 25.00 | 23.55 | 0.00 | 0.00 |
August | 572.17 | 22.27 | 46.00 | 23.59 | 0.00 | 0.00 |
September | 654.00 | 22.25 | 10.00 | 23.55 | 0.00 | 0.00 |
October | 618.83 | 22.61 | 37.50 | 23.63 | 0.00 | 0.00 |
November | 699.33 | 22.36 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8181.00 | 22.21 | 129.00 | 23.46 | 6.67 | 21.00 |
Minimum of Months | 572.17 | 21.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.61 | 46.00 | 23.63 | 6.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 543.17 | 20.64 | 543.17 | 20.64 |
February | 672.00 | 20.88 | 494.33 | 20.73 | 494.33 | 20.73 |
March | 744.00 | 21.14 | 194.33 | 20.74 | 194.33 | 20.74 |
April | 713.00 | 21.31 | 38.83 | 20.55 | 38.83 | 20.55 |
May | 731.83 | 21.54 | 3.33 | 22.25 | 3.33 | 22.25 |
June | 650.50 | 21.54 | 16.50 | 22.44 | 12.33 | 22.30 |
July | 633.33 | 21.48 | 29.67 | 22.62 | 17.50 | 22.38 |
August | 630.67 | 21.47 | 15.17 | 22.78 | 5.50 | 22.41 |
September | 670.83 | 21.54 | 13.67 | 22.32 | 12.00 | 22.23 |
October | 706.67 | 21.48 | 3.33 | 21.89 | 3.33 | 21.89 |
November | 720.00 | 21.11 | 215.50 | 20.75 | 215.50 | 20.75 |
December | 744.00 | 20.89 | 496.33 | 20.72 | 496.33 | 20.72 |
Annual Sum or Average | 8360.83 | 21.25 | 2064.17 | 20.77 | 2036.50 | 20.74 |
Minimum of Months | 630.67 | 20.78 | 3.33 | 20.55 | 3.33 | 20.55 |
Maximum of Months | 744.00 | 21.54 | 543.17 | 22.78 | 543.17 | 22.41 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.61 | 633.67 | 20.53 | 633.67 | 20.53 |
February | 672.00 | 20.64 | 609.67 | 20.59 | 609.67 | 20.59 |
March | 744.00 | 20.94 | 286.50 | 20.59 | 286.50 | 20.59 |
April | 717.17 | 21.23 | 58.67 | 20.54 | 58.67 | 20.54 |
May | 734.33 | 21.52 | 3.33 | 22.27 | 3.33 | 22.27 |
June | 658.67 | 21.56 | 15.33 | 22.44 | 11.83 | 22.31 |
July | 643.67 | 21.50 | 30.00 | 22.63 | 18.50 | 22.41 |
August | 655.83 | 21.53 | 14.33 | 22.70 | 6.17 | 22.33 |
September | 694.00 | 21.55 | 14.17 | 22.33 | 13.00 | 22.26 |
October | 730.67 | 21.37 | 31.33 | 21.04 | 31.33 | 21.04 |
November | 720.00 | 20.89 | 298.33 | 20.57 | 298.33 | 20.57 |
December | 744.00 | 20.66 | 673.33 | 20.61 | 673.33 | 20.61 |
Annual Sum or Average | 8458.33 | 21.16 | 2668.67 | 20.64 | 2644.33 | 20.62 |
Minimum of Months | 643.67 | 20.61 | 3.33 | 20.53 | 3.33 | 20.53 |
Maximum of Months | 744.00 | 21.56 | 673.33 | 22.70 | 673.33 | 22.41 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.96 | 343.50 | 20.79 | 343.50 | 20.79 |
February | 672.00 | 20.94 | 373.00 | 20.80 | 373.00 | 20.80 |
March | 744.00 | 21.18 | 68.17 | 20.88 | 68.17 | 20.88 |
April | 720.00 | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.56 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.66 | 18.67 | 22.27 | 18.67 | 22.27 |
July | 744.00 | 21.71 | 34.00 | 22.32 | 34.00 | 22.32 |
August | 744.00 | 21.69 | 14.17 | 22.37 | 14.17 | 22.37 |
September | 720.00 | 21.59 | 9.00 | 22.13 | 9.00 | 22.13 |
October | 744.00 | 21.43 | 1.17 | 21.73 | 1.17 | 21.73 |
November | 720.00 | 21.20 | 73.00 | 20.84 | 73.00 | 20.84 |
December | 744.00 | 21.02 | 203.33 | 20.76 | 203.33 | 20.76 |
Annual Sum or Average | 8760.00 | 21.36 | 1138.00 | 20.90 | 1138.00 | 20.90 |
Minimum of Months | 672.00 | 20.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.71 | 373.00 | 22.37 | 373.00 | 22.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.78 | 537.50 | 20.65 | 537.50 | 20.65 |
February | 672.00 | 20.90 | 475.33 | 20.75 | 475.33 | 20.75 |
March | 744.00 | 21.18 | 191.67 | 20.77 | 191.67 | 20.77 |
April | 717.50 | 21.38 | 38.50 | 20.55 | 38.50 | 20.55 |
May | 732.50 | 21.59 | 2.50 | 22.03 | 2.50 | 22.03 |
June | 677.00 | 21.62 | 15.67 | 22.33 | 15.50 | 22.34 |
July | 620.83 | 21.45 | 19.33 | 22.55 | 15.17 | 22.47 |
August | 619.00 | 21.45 | 8.33 | 22.63 | 3.83 | 22.47 |
September | 681.67 | 21.59 | 14.83 | 22.25 | 13.83 | 22.22 |
October | 718.67 | 21.55 | 4.00 | 21.97 | 4.00 | 21.97 |
November | 720.00 | 21.14 | 195.67 | 20.75 | 195.67 | 20.75 |
December | 744.00 | 20.90 | 485.83 | 20.73 | 485.83 | 20.73 |
Annual Sum or Average | 8391.17 | 21.29 | 1989.17 | 20.77 | 1979.33 | 20.76 |
Minimum of Months | 619.00 | 20.78 | 2.50 | 20.55 | 2.50 | 20.55 |
Maximum of Months | 744.00 | 21.62 | 537.50 | 22.63 | 537.50 | 22.47 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.61 | 631.00 | 20.53 | 631.00 | 20.53 |
February | 672.00 | 20.66 | 601.83 | 20.60 | 601.83 | 20.60 |
March | 744.00 | 20.98 | 283.17 | 20.70 | 283.17 | 20.70 |
April | 719.33 | 21.31 | 50.67 | 20.58 | 50.67 | 20.58 |
May | 737.83 | 21.59 | 2.33 | 22.05 | 2.33 | 22.05 |
June | 686.33 | 21.64 | 16.17 | 22.39 | 14.83 | 22.36 |
July | 642.50 | 21.51 | 20.50 | 22.57 | 15.83 | 22.48 |
August | 660.67 | 21.56 | 8.33 | 22.69 | 4.00 | 22.56 |
September | 710.33 | 21.63 | 14.50 | 22.23 | 13.83 | 22.20 |
October | 743.00 | 21.45 | 25.83 | 21.20 | 25.83 | 21.20 |
November | 720.00 | 20.93 | 266.17 | 20.57 | 266.17 | 20.57 |
December | 744.00 | 20.66 | 644.67 | 20.60 | 644.67 | 20.60 |
Annual Sum or Average | 8524.00 | 21.20 | 2565.17 | 20.64 | 2554.17 | 20.63 |
Minimum of Months | 642.50 | 20.61 | 2.33 | 20.53 | 2.33 | 20.53 |
Maximum of Months | 744.00 | 21.64 | 644.67 | 22.69 | 644.67 | 22.56 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 632.67 | 20.59 | 632.67 | 20.59 |
February | 672.00 | 20.79 | 577.17 | 20.69 | 577.17 | 20.69 |
March | 744.00 | 21.07 | 288.17 | 20.67 | 288.17 | 20.67 |
April | 703.67 | 21.26 | 94.50 | 20.62 | 94.33 | 20.62 |
May | 710.00 | 21.51 | 12.17 | 22.11 | 8.67 | 21.75 |
June | 610.17 | 21.44 | 38.33 | 22.59 | 17.00 | 22.08 |
July | 592.33 | 21.36 | 56.50 | 22.83 | 20.17 | 22.38 |
August | 589.33 | 21.35 | 48.33 | 22.99 | 7.83 | 22.42 |
September | 637.67 | 21.46 | 29.67 | 22.45 | 18.50 | 22.08 |
October | 690.83 | 21.43 | 50.83 | 21.35 | 45.00 | 21.12 |
November | 720.00 | 21.02 | 307.50 | 20.69 | 307.50 | 20.69 |
December | 744.00 | 20.79 | 600.83 | 20.68 | 600.83 | 20.68 |
Annual Sum or Average | 8158.00 | 21.17 | 2736.67 | 20.81 | 2617.83 | 20.71 |
Minimum of Months | 589.33 | 20.68 | 12.17 | 20.59 | 7.83 | 20.59 |
Maximum of Months | 744.00 | 21.51 | 632.67 | 22.99 | 632.67 | 22.42 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 696.00 | 20.50 | 696.00 | 20.50 |
February | 672.00 | 20.57 | 648.17 | 20.55 | 648.17 | 20.55 |
March | 744.00 | 20.87 | 377.00 | 20.56 | 377.00 | 20.56 |
April | 711.83 | 21.20 | 134.67 | 20.64 | 134.67 | 20.64 |
May | 717.00 | 21.51 | 11.00 | 22.08 | 8.33 | 21.78 |
June | 615.83 | 21.46 | 33.83 | 22.53 | 16.00 | 22.03 |
July | 596.83 | 21.38 | 52.17 | 22.80 | 19.83 | 22.38 |
August | 609.00 | 21.41 | 35.50 | 22.92 | 8.00 | 22.39 |
September | 668.00 | 21.52 | 23.50 | 22.21 | 19.33 | 22.03 |
October | 723.67 | 21.35 | 85.67 | 21.01 | 85.00 | 21.00 |
November | 720.00 | 20.80 | 393.33 | 20.55 | 393.33 | 20.55 |
December | 744.00 | 20.57 | 709.50 | 20.55 | 709.50 | 20.55 |
Annual Sum or Average | 8266.17 | 21.08 | 3200.33 | 20.66 | 3115.17 | 20.59 |
Minimum of Months | 596.83 | 20.54 | 11.00 | 20.50 | 8.00 | 20.50 |
Maximum of Months | 744.00 | 21.52 | 709.50 | 22.92 | 709.50 | 22.39 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.83 | 21.10 | 364.00 | 20.76 | 364.00 | 20.76 |
February | 672.00 | 21.27 | 310.67 | 20.84 | 310.67 | 20.84 |
March | 738.33 | 21.33 | 119.50 | 20.83 | 119.50 | 20.83 |
April | 706.83 | 21.41 | 19.33 | 20.47 | 19.33 | 20.47 |
May | 734.33 | 21.59 | 1.00 | 21.70 | 1.00 | 21.70 |
June | 659.00 | 21.56 | 25.67 | 22.26 | 25.67 | 22.26 |
July | 634.33 | 21.49 | 35.00 | 22.42 | 35.00 | 22.42 |
August | 619.17 | 21.44 | 16.00 | 22.37 | 15.50 | 22.34 |
September | 627.33 | 21.46 | 23.00 | 22.73 | 12.83 | 22.25 |
October | 651.67 | 21.43 | 36.50 | 23.20 | 3.33 | 21.88 |
November | 706.00 | 21.39 | 75.83 | 20.96 | 75.83 | 20.96 |
December | 737.50 | 21.21 | 299.00 | 20.79 | 299.00 | 20.79 |
Annual Sum or Average | 8226.33 | 21.39 | 1325.50 | 20.99 | 1281.67 | 20.91 |
Minimum of Months | 619.17 | 21.10 | 1.00 | 20.47 | 1.00 | 20.47 |
Maximum of Months | 739.83 | 21.59 | 364.00 | 23.20 | 364.00 | 22.42 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 592.33 | 22.90 | 13.67 | 23.98 | 0.00 | 0.00 |
February | 565.17 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 411.00 | 22.96 | 62.33 | 23.99 | 0.00 | 0.00 |
April | 273.50 | 22.79 | 193.50 | 23.93 | 2.00 | 23.96 |
May | 230.50 | 22.74 | 347.50 | 23.87 | 36.50 | 23.99 |
June | 152.00 | 22.71 | 469.50 | 23.76 | 38.67 | 23.95 |
July | 31.67 | 22.33 | 566.83 | 23.70 | 0.33 | 23.82 |
August | 65.00 | 22.49 | 540.00 | 23.75 | 5.33 | 23.96 |
September | 219.83 | 22.50 | 373.17 | 23.81 | 26.83 | 23.92 |
October | 345.33 | 22.86 | 243.00 | 23.88 | 58.17 | 23.95 |
November | 403.33 | 22.88 | 83.00 | 23.97 | 5.17 | 23.95 |
December | 529.67 | 22.96 | 8.17 | 23.99 | 0.00 | 0.00 |
Annual Sum or Average | 3819.33 | 22.86 | 2900.67 | 23.80 | 173.00 | 23.95 |
Minimum of Months | 31.67 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 592.33 | 22.96 | 566.83 | 23.99 | 58.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.83 | 22.97 | 52.83 | 23.97 | 0.00 | 0.00 |
February | 438.50 | 23.06 | 15.00 | 23.99 | 0.00 | 0.00 |
March | 238.17 | 22.97 | 182.83 | 23.97 | 0.00 | 0.00 |
April | 146.00 | 22.92 | 329.50 | 23.91 | 0.50 | 24.00 |
May | 99.00 | 22.94 | 498.17 | 23.84 | 23.83 | 23.99 |
June | 45.00 | 22.86 | 562.67 | 23.73 | 13.50 | 23.99 |
July | 5.17 | 22.31 | 682.17 | 23.64 | 0.00 | 0.00 |
August | 7.33 | 22.79 | 651.83 | 23.68 | 1.33 | 23.99 |
September | 120.17 | 22.67 | 488.33 | 23.76 | 19.17 | 23.98 |
October | 213.00 | 22.98 | 340.83 | 23.83 | 43.83 | 23.99 |
November | 258.83 | 22.93 | 184.83 | 23.95 | 2.33 | 23.99 |
December | 359.50 | 22.96 | 46.50 | 23.98 | 0.00 | 0.00 |
Annual Sum or Average | 2371.50 | 22.96 | 4035.50 | 23.78 | 104.50 | 23.99 |
Minimum of Months | 5.17 | 22.31 | 15.00 | 23.64 | 0.00 | 0.00 |
Maximum of Months | 440.83 | 23.06 | 682.17 | 23.99 | 43.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 554.50 | 23.76 | 597.00 | 23.99 | 472.50 | 24.07 |
February | 513.17 | 23.72 | 530.00 | 24.02 | 425.17 | 24.08 |
March | 537.67 | 24.02 | 642.00 | 23.97 | 508.67 | 24.13 |
April | 513.50 | 24.09 | 664.00 | 23.86 | 510.33 | 24.10 |
May | 544.33 | 24.01 | 711.50 | 23.71 | 544.17 | 24.01 |
June | 531.00 | 23.98 | 675.50 | 23.59 | 530.33 | 23.98 |
July | 547.33 | 23.98 | 692.00 | 23.56 | 547.33 | 23.98 |
August | 548.00 | 23.98 | 705.00 | 23.55 | 547.83 | 23.98 |
September | 523.83 | 23.98 | 670.83 | 23.63 | 523.83 | 23.98 |
October | 533.00 | 24.03 | 694.50 | 23.76 | 530.83 | 24.04 |
November | 520.67 | 23.99 | 626.83 | 23.93 | 495.17 | 24.09 |
December | 545.50 | 23.87 | 606.17 | 24.00 | 486.67 | 24.09 |
Annual Sum or Average | 6412.50 | 23.95 | 7815.33 | 23.79 | 6122.83 | 24.04 |
Minimum of Months | 513.17 | 23.72 | 530.00 | 23.55 | 425.17 | 23.98 |
Maximum of Months | 554.50 | 24.09 | 711.50 | 24.02 | 547.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.10065 | 27.15841 | 0.02741 | 5.20254 |
February | 672.00000 | 22.69005 | 23.50129 | -0.1014 | 5.38174 |
March | 744.00000 | 22.30546 | 33.19905 | -0.1365 | 5.55984 |
April | 720.00000 | 21.86523 | 40.70995 | -0.1976 | 6.01901 |
May | 744.00000 | 21.36509 | 49.47183 | -1.4375 | 47.59162 |
June | 720.00000 | 21.22790 | 56.81410 | -1.4268 | 46.99062 |
July | 744.00000 | 21.28979 | 58.80120 | -1.3805 | 44.52989 |
August | 744.00000 | 21.67241 | 56.41742 | -1.2535 | 38.01915 |
September | 720.00000 | 22.32722 | 51.72638 | -1.0531 | 28.70959 |
October | 744.00000 | 23.35309 | 42.15612 | 0.20702 | 6.11775 |
November | 720.00000 | 23.76890 | 32.70333 | 0.24262 | 6.34270 |
December | 744.00000 | 23.61374 | 26.58285 | 0.15630 | 5.62191 |
Annual Sum or Average | 8760.00000 | 22.38002 | 41.70970 | -0.5321 | 20.61499 |
Minimum of Months | 672.00000 | 21.22790 | 23.50129 | -1.4375 | 5.20254 |
Maximum of Months | 744.00000 | 23.76890 | 58.80120 | 0.24262 | 47.59162 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10694 | 28.12008 | -0.5078 | 11.02786 |
February | 672.00000 | 21.15804 | 23.42189 | -0.4989 | 10.96398 |
March | 744.00000 | 21.20713 | 33.51139 | -0.3845 | 8.83549 |
April | 720.00000 | 21.16156 | 40.83496 | -0.3248 | 7.76384 |
May | 744.00000 | 21.15164 | 49.10140 | -1.3892 | 45.16104 |
June | 720.00000 | 21.40600 | 57.23120 | -1.1911 | 35.38774 |
July | 744.00000 | 21.82001 | 59.81665 | -1.0051 | 27.20639 |
August | 744.00000 | 22.16923 | 56.29172 | -0.8950 | 23.46383 |
September | 720.00000 | 21.70224 | 53.56459 | -1.1118 | 32.92246 |
October | 744.00000 | 21.87915 | 44.64412 | -0.0477 | 6.98471 |
November | 720.00000 | 21.25025 | 35.76621 | -0.3528 | 8.54310 |
December | 744.00000 | 21.19019 | 28.20163 | -0.4558 | 10.20624 |
Annual Sum or Average | 8760.00000 | 21.43638 | 42.65211 | -0.6812 | 19.08207 |
Minimum of Months | 672.00000 | 21.10694 | 23.42189 | -1.3892 | 6.98471 |
Maximum of Months | 744.00000 | 22.16923 | 59.81665 | -0.0477 | 45.16104 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38527 | 29.83762 | -0.3594 | 8.06086 |
February | 672.00000 | 21.43902 | 25.24952 | -0.3703 | 8.17866 |
March | 744.00000 | 21.76513 | 34.57664 | -0.2235 | 6.44217 |
April | 720.00000 | 21.87134 | 41.22797 | -0.1475 | 5.90068 |
May | 744.00000 | 21.87168 | 48.87196 | -1.1840 | 34.94578 |
June | 720.00000 | 21.90801 | 56.03360 | -1.1022 | 31.10844 |
July | 744.00000 | 22.08395 | 58.10013 | -1.0179 | 27.38258 |
August | 744.00000 | 22.30293 | 55.93378 | -0.9519 | 24.69860 |
September | 720.00000 | 22.00944 | 53.59252 | -1.0851 | 30.36418 |
October | 744.00000 | 22.31210 | 45.21175 | 0.00488 | 5.39910 |
November | 720.00000 | 21.83648 | 36.60847 | -0.1913 | 6.24570 |
December | 744.00000 | 21.59425 | 29.74623 | -0.3018 | 7.18160 |
Annual Sum or Average | 8760.00000 | 21.86801 | 43.01777 | -0.5786 | 16.36987 |
Minimum of Months | 672.00000 | 21.38527 | 25.24952 | -1.1840 | 5.39910 |
Maximum of Months | 744.00000 | 22.31210 | 58.10013 | 0.00488 | 34.94578 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.47695 | 24.32880 | 0.46775 | 12.97844 |
February | 672.00000 | 22.49170 | 20.06632 | 0.44569 | 12.53093 |
March | 744.00000 | 22.53458 | 29.19597 | 0.54116 | 14.57205 |
April | 720.00000 | 22.38535 | 36.12331 | 0.56788 | 15.19062 |
May | 744.00000 | 22.07452 | 44.16593 | -0.2403 | 13.53470 |
June | 720.00000 | 21.82918 | 51.69100 | -0.2469 | 13.36638 |
July | 744.00000 | 21.76850 | 54.13931 | -0.2370 | 12.99260 |
August | 744.00000 | 21.80833 | 52.74243 | -0.2224 | 13.01365 |
September | 720.00000 | 21.89393 | 49.55149 | -0.2484 | 13.32127 |
October | 744.00000 | 22.22477 | 41.29027 | 0.58356 | 15.63403 |
November | 720.00000 | 22.49192 | 31.39034 | 0.54799 | 14.68856 |
December | 744.00000 | 22.53250 | 24.39995 | 0.49252 | 13.31699 |
Annual Sum or Average | 8760.00000 | 22.20768 | 38.36351 | 0.20284 | 13.76764 |
Minimum of Months | 672.00000 | 21.76850 | 20.06632 | -0.2484 | 12.53093 |
Maximum of Months | 744.00000 | 22.53458 | 54.13931 | 0.58356 | 15.63403 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.49512 | 33.33922 | -0.3107 | 7.92018 |
February | 672.00000 | 21.60895 | 28.69809 | -0.2888 | 7.73323 |
March | 744.00000 | 21.95405 | 38.10381 | -0.1209 | 6.26633 |
April | 720.00000 | 21.99622 | 44.81546 | -0.0505 | 5.88207 |
May | 744.00000 | 22.05209 | 52.40534 | -1.0090 | 27.24146 |
June | 720.00000 | 22.18190 | 59.76092 | -0.8573 | 21.36709 |
July | 744.00000 | 22.45888 | 62.02040 | -0.7147 | 16.50387 |
August | 744.00000 | 22.74014 | 59.38979 | -0.6207 | 13.92801 |
September | 720.00000 | 22.47596 | 56.63350 | -0.7688 | 18.91231 |
October | 744.00000 | 22.88322 | 47.99323 | 0.25991 | 7.55387 |
November | 720.00000 | 22.03045 | 40.03102 | -0.0814 | 6.35727 |
December | 744.00000 | 21.74946 | 33.18546 | -0.2246 | 7.12849 |
Annual Sum or Average | 8760.00000 | 22.13948 | 46.46665 | -0.3994 | 12.26000 |
Minimum of Months | 672.00000 | 21.49512 | 28.69809 | -1.0090 | 5.88207 |
Maximum of Months | 744.00000 | 22.88322 | 62.02040 | 0.25991 | 27.24146 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.88235 | 31.96902 | -0.2078 | 6.49077 |
February | 672.00000 | 21.95263 | 27.47633 | -0.2132 | 6.46939 |
March | 744.00000 | 22.27377 | 36.61990 | -0.0672 | 5.65942 |
April | 720.00000 | 22.32076 | 43.19073 | -0.0038 | 5.61887 |
May | 744.00000 | 22.25127 | 50.80089 | -1.0067 | 27.31430 |
June | 720.00000 | 22.19722 | 58.13768 | -0.9474 | 24.81321 |
July | 744.00000 | 22.33968 | 60.35728 | -0.8694 | 21.71687 |
August | 744.00000 | 22.51740 | 58.30571 | -0.8163 | 19.80632 |
September | 720.00000 | 22.35457 | 55.56587 | -0.9104 | 23.28814 |
October | 744.00000 | 22.75470 | 47.15333 | 0.15686 | 5.97709 |
November | 720.00000 | 22.39428 | 38.48222 | -0.0207 | 5.66414 |
December | 744.00000 | 22.15092 | 31.79461 | -0.1348 | 5.89550 |
Annual Sum or Average | 8760.00000 | 22.28480 | 45.08947 | -0.4212 | 13.26395 |
Minimum of Months | 672.00000 | 21.88235 | 27.47633 | -1.0067 | 5.61887 |
Maximum of Months | 744.00000 | 22.75470 | 60.35728 | 0.15686 | 27.31430 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77917 | 36.69423 | -0.6111 | 13.37514 |
February | 672.00000 | 20.87776 | 31.66720 | -0.6023 | 13.19678 |
March | 744.00000 | 21.13833 | 41.26820 | -0.4279 | 9.47811 |
April | 720.00000 | 21.32326 | 47.54680 | -0.3069 | 7.78860 |
May | 744.00000 | 21.56206 | 53.88440 | -1.2973 | 41.03396 |
June | 720.00000 | 21.69649 | 59.34423 | -1.1437 | 33.94041 |
July | 744.00000 | 21.73135 | 61.06604 | -1.0897 | 31.59521 |
August | 744.00000 | 21.72896 | 57.49863 | -1.0971 | 31.97415 |
September | 720.00000 | 21.65617 | 57.59279 | -1.2005 | 36.61405 |
October | 744.00000 | 21.56922 | 51.25589 | -0.1765 | 6.74231 |
November | 720.00000 | 21.10631 | 44.13462 | -0.4365 | 9.60583 |
December | 744.00000 | 20.88760 | 36.74721 | -0.5678 | 12.24153 |
Annual Sum or Average | 8760.00000 | 21.34066 | 48.31805 | -0.7473 | 20.67844 |
Minimum of Months | 672.00000 | 20.77917 | 31.66720 | -1.2973 | 6.74231 |
Maximum of Months | 744.00000 | 21.73135 | 61.06604 | -0.1765 | 41.03396 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.60766 | 37.03794 | -0.6707 | 15.00696 |
February | 672.00000 | 20.64144 | 32.07992 | -0.6849 | 15.37714 |
March | 744.00000 | 20.94161 | 41.66268 | -0.4936 | 10.60393 |
April | 720.00000 | 21.23886 | 47.82701 | -0.3378 | 8.09492 |
May | 744.00000 | 21.53982 | 53.97708 | -1.3109 | 41.64708 |
June | 720.00000 | 21.69335 | 59.42918 | -1.1487 | 34.13908 |
July | 744.00000 | 21.73023 | 61.30072 | -1.0947 | 31.78091 |
August | 744.00000 | 21.72305 | 58.09931 | -1.1128 | 32.58691 |
September | 720.00000 | 21.60806 | 58.42299 | -1.2389 | 38.23382 |
October | 744.00000 | 21.39546 | 52.86669 | -0.2435 | 7.10319 |
November | 720.00000 | 20.89034 | 44.68122 | -0.5092 | 10.96042 |
December | 744.00000 | 20.65640 | 37.21846 | -0.6445 | 14.10927 |
Annual Sum or Average | 8760.00000 | 21.22548 | 48.81123 | -0.7915 | 21.67505 |
Minimum of Months | 672.00000 | 20.60766 | 32.07992 | -1.3109 | 7.10319 |
Maximum of Months | 744.00000 | 21.73023 | 61.30072 | -0.2435 | 41.64708 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.95990 | 35.50690 | -0.5287 | 11.16170 |
February | 672.00000 | 20.94471 | 30.86906 | -0.5615 | 11.85329 |
March | 744.00000 | 21.17973 | 40.15158 | -0.4159 | 8.79882 |
April | 720.00000 | 21.38022 | 45.81639 | -0.3059 | 7.25239 |
May | 744.00000 | 21.55539 | 51.05523 | -1.3516 | 43.36198 |
June | 720.00000 | 21.65643 | 58.35610 | -1.2382 | 37.91145 |
July | 744.00000 | 21.71323 | 61.14320 | -1.1852 | 35.49077 |
August | 744.00000 | 21.69167 | 57.93914 | -1.2189 | 37.03790 |
September | 720.00000 | 21.59130 | 56.09211 | -1.2993 | 40.79647 |
October | 744.00000 | 21.42892 | 50.45952 | -0.2567 | 6.80349 |
November | 720.00000 | 21.19649 | 42.70855 | -0.3963 | 8.53234 |
December | 744.00000 | 21.01932 | 35.70361 | -0.5057 | 10.46378 |
Annual Sum or Average | 8760.00000 | 21.36213 | 47.24456 | -0.7733 | 21.68039 |
Minimum of Months | 672.00000 | 20.94471 | 30.86906 | -1.3516 | 6.80349 |
Maximum of Months | 744.00000 | 21.71323 | 61.14320 | -0.2567 | 43.36198 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78218 | 36.67313 | -0.6088 | 13.27990 |
February | 672.00000 | 20.90008 | 31.61217 | -0.5939 | 12.93297 |
March | 744.00000 | 21.18220 | 41.21631 | -0.4221 | 9.37711 |
April | 720.00000 | 21.38856 | 47.23217 | -0.2919 | 7.68614 |
May | 744.00000 | 21.61077 | 53.48384 | -1.2784 | 40.19466 |
June | 720.00000 | 21.71252 | 59.38648 | -1.1471 | 34.05630 |
July | 744.00000 | 21.74230 | 60.71545 | -1.0902 | 31.59101 |
August | 744.00000 | 21.74562 | 57.10315 | -1.0944 | 31.84768 |
September | 720.00000 | 21.67991 | 57.26486 | -1.1919 | 36.21743 |
October | 744.00000 | 21.60924 | 51.09955 | -0.1708 | 6.70728 |
November | 720.00000 | 21.14422 | 44.01693 | -0.4216 | 9.39245 |
December | 744.00000 | 20.89655 | 36.72117 | -0.5627 | 12.11671 |
Annual Sum or Average | 8760.00000 | 21.36875 | 48.13574 | -0.7404 | 20.49654 |
Minimum of Months | 672.00000 | 20.78218 | 31.61217 | -1.2784 | 6.70728 |
Maximum of Months | 744.00000 | 21.74562 | 60.71545 | -0.1708 | 40.19466 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.61001 | 37.01343 | -0.6688 | 14.96469 |
February | 672.00000 | 20.65575 | 32.03098 | -0.6782 | 15.17762 |
March | 744.00000 | 20.98062 | 41.58551 | -0.4890 | 10.41822 |
April | 720.00000 | 21.31592 | 47.47258 | -0.3205 | 7.93097 |
May | 744.00000 | 21.59773 | 53.55604 | -1.2896 | 40.68586 |
June | 720.00000 | 21.71043 | 59.50267 | -1.1518 | 34.24030 |
July | 744.00000 | 21.74124 | 60.93349 | -1.0952 | 31.78334 |
August | 744.00000 | 21.74239 | 57.63490 | -1.1094 | 32.43096 |
September | 720.00000 | 21.65150 | 57.92780 | -1.2252 | 37.59565 |
October | 744.00000 | 21.45066 | 52.32162 | -0.2374 | 7.01476 |
November | 720.00000 | 20.93079 | 44.53899 | -0.4928 | 10.63218 |
December | 744.00000 | 20.66153 | 37.18085 | -0.6401 | 14.02224 |
Annual Sum or Average | 8760.00000 | 21.25734 | 48.56748 | -0.7839 | 21.44622 |
Minimum of Months | 672.00000 | 20.61001 | 32.03098 | -1.2896 | 7.01476 |
Maximum of Months | 744.00000 | 21.74239 | 60.93349 | -0.2374 | 40.68586 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68381 | 37.43721 | -0.6684 | 15.01148 |
February | 672.00000 | 20.78738 | 32.20371 | -0.6590 | 14.81223 |
March | 744.00000 | 21.07476 | 42.08672 | -0.4614 | 10.30680 |
April | 720.00000 | 21.30352 | 48.32994 | -0.3167 | 8.18920 |
May | 744.00000 | 21.58603 | 54.36395 | -1.2741 | 40.17706 |
June | 720.00000 | 21.71131 | 58.95487 | -1.1084 | 32.58012 |
July | 744.00000 | 21.74114 | 60.16001 | -1.0514 | 30.13520 |
August | 744.00000 | 21.73855 | 56.89832 | -1.0595 | 30.58074 |
September | 720.00000 | 21.66637 | 57.66647 | -1.1759 | 35.70964 |
October | 744.00000 | 21.56005 | 51.85505 | -0.1777 | 6.95745 |
November | 720.00000 | 21.02165 | 45.08347 | -0.4778 | 10.59549 |
December | 744.00000 | 20.78961 | 37.46819 | -0.6232 | 13.71359 |
Annual Sum or Average | 8760.00000 | 21.30829 | 48.63315 | -0.7551 | 20.76802 |
Minimum of Months | 672.00000 | 20.68381 | 32.20371 | -1.2741 | 6.95745 |
Maximum of Months | 744.00000 | 21.74114 | 60.16001 | -0.1777 | 40.17706 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53851 | 37.76992 | -0.7245 | 16.67082 |
February | 672.00000 | 20.57458 | 32.62395 | -0.7391 | 17.06926 |
March | 744.00000 | 20.87228 | 42.52434 | -0.5307 | 11.56647 |
April | 720.00000 | 21.22257 | 48.62041 | -0.3480 | 8.50300 |
May | 744.00000 | 21.57170 | 54.44913 | -1.2859 | 40.68280 |
June | 720.00000 | 21.71028 | 59.00951 | -1.1126 | 32.73664 |
July | 744.00000 | 21.74046 | 60.32673 | -1.0561 | 30.30108 |
August | 744.00000 | 21.73289 | 57.41411 | -1.0752 | 31.15852 |
September | 720.00000 | 21.63443 | 58.51276 | -1.2104 | 37.11553 |
October | 744.00000 | 21.39394 | 53.56276 | -0.2460 | 7.37187 |
November | 720.00000 | 20.80492 | 45.69079 | -0.5534 | 12.10533 |
December | 744.00000 | 20.56987 | 37.96082 | -0.6996 | 15.75313 |
Annual Sum or Average | 8760.00000 | 21.20072 | 49.13073 | -0.7989 | 21.78192 |
Minimum of Months | 672.00000 | 20.53851 | 32.62395 | -1.2859 | 7.37187 |
Maximum of Months | 744.00000 | 21.74046 | 60.32673 | -0.2460 | 40.68280 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.11529 | 37.85571 | -0.4936 | 11.13488 |
February | 672.00000 | 21.27236 | 33.11540 | -0.4599 | 10.66464 |
March | 744.00000 | 21.34727 | 42.17480 | -0.3577 | 8.69390 |
April | 720.00000 | 21.44341 | 47.76396 | -0.2777 | 7.54933 |
May | 744.00000 | 21.61003 | 53.44610 | -1.2991 | 41.22006 |
June | 720.00000 | 21.70460 | 59.10914 | -1.1635 | 34.85591 |
July | 744.00000 | 21.74556 | 60.56120 | -1.1011 | 32.09624 |
August | 744.00000 | 21.74307 | 56.80538 | -1.1070 | 32.49698 |
September | 720.00000 | 21.69500 | 56.12526 | -1.1744 | 35.67118 |
October | 744.00000 | 21.65583 | 50.38997 | -0.1244 | 6.69757 |
November | 720.00000 | 21.42948 | 44.44753 | -0.3168 | 8.10942 |
December | 744.00000 | 21.22621 | 37.83183 | -0.4404 | 10.21572 |
Annual Sum or Average | 8760.00000 | 21.50011 | 48.38801 | -0.6945 | 20.00932 |
Minimum of Months | 672.00000 | 21.11529 | 33.11540 | -1.2991 | 6.69757 |
Maximum of Months | 744.00000 | 21.74556 | 60.56120 | -0.1244 | 41.22006 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.11289 | 32.70242 | 0.10202 | 6.13211 |
February | 672.00000 | 23.11675 | 28.63523 | 0.07486 | 5.95504 |
March | 744.00000 | 23.39574 | 36.85533 | 0.23103 | 6.70688 |
April | 720.00000 | 23.44593 | 42.79877 | 0.31306 | 7.55554 |
May | 744.00000 | 23.40603 | 49.81774 | -0.5298 | 11.71748 |
June | 720.00000 | 23.35802 | 56.51673 | -0.4509 | 10.06450 |
July | 744.00000 | 23.44055 | 58.37210 | -0.3855 | 8.68220 |
August | 744.00000 | 23.44466 | 57.15514 | -0.3961 | 8.91532 |
September | 720.00000 | 23.25889 | 55.01109 | -0.5235 | 11.71556 |
October | 744.00000 | 23.34054 | 47.67418 | 0.33369 | 7.96796 |
November | 720.00000 | 23.33498 | 38.85449 | 0.22904 | 6.77701 |
December | 744.00000 | 23.24612 | 32.60197 | 0.14237 | 6.11307 |
Annual Sum or Average | 8760.00000 | 23.32654 | 44.84319 | -0.0724 | 8.20111 |
Minimum of Months | 672.00000 | 23.11289 | 28.63523 | -0.5298 | 5.95504 |
Maximum of Months | 744.00000 | 23.44593 | 58.37210 | 0.33369 | 11.71748 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36492 | 31.74162 | 0.20223 | 6.57547 |
February | 672.00000 | 23.36882 | 27.74716 | 0.17475 | 6.29765 |
March | 744.00000 | 23.59086 | 35.79259 | 0.31737 | 7.52284 |
April | 720.00000 | 23.62018 | 41.71495 | 0.39320 | 8.59278 |
May | 744.00000 | 23.56741 | 48.73348 | -0.4220 | 9.31591 |
June | 720.00000 | 23.50321 | 55.52000 | -0.3557 | 8.26452 |
July | 744.00000 | 23.56123 | 57.46413 | -0.3020 | 7.34680 |
August | 744.00000 | 23.55507 | 56.28203 | -0.3168 | 7.58352 |
September | 720.00000 | 23.42087 | 53.97178 | -0.4210 | 9.45522 |
October | 744.00000 | 23.50559 | 46.61704 | 0.40852 | 8.99189 |
November | 720.00000 | 23.53458 | 37.79533 | 0.31604 | 7.58456 |
December | 744.00000 | 23.46938 | 31.60151 | 0.23580 | 6.66538 |
Annual Sum or Average | 8760.00000 | 23.50614 | 43.84161 | 0.01832 | 7.85562 |
Minimum of Months | 672.00000 | 23.36492 | 27.74716 | -0.4220 | 6.29765 |
Maximum of Months | 744.00000 | 23.62018 | 57.46413 | 0.40852 | 9.45522 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.63632 | 30.23583 | 0.89522 | 25.32331 |
February | 672.00000 | 23.63042 | 26.36685 | 0.87205 | 24.55117 |
March | 744.00000 | 23.75386 | 34.32449 | 1.00023 | 29.15664 |
April | 720.00000 | 23.75022 | 40.35199 | 1.07679 | 32.28589 |
May | 744.00000 | 23.64347 | 47.51218 | 0.55419 | 18.26798 |
June | 720.00000 | 23.45922 | 54.48051 | 0.58826 | 20.67725 |
July | 744.00000 | 23.40256 | 56.66720 | 0.61484 | 21.96005 |
August | 744.00000 | 23.43690 | 55.37715 | 0.62162 | 21.89016 |
September | 720.00000 | 23.49161 | 52.66076 | 0.55912 | 19.54598 |
October | 744.00000 | 23.66411 | 45.09081 | 1.10746 | 33.76453 |
November | 720.00000 | 23.72016 | 36.30770 | 1.00059 | 29.08757 |
December | 744.00000 | 23.68316 | 30.17324 | 0.92017 | 25.90763 |
Annual Sum or Average | 8760.00000 | 23.60581 | 42.55646 | 0.81722 | 25.20469 |
Minimum of Months | 672.00000 | 23.40256 | 26.36685 | 0.55419 | 18.26798 |
Maximum of Months | 744.00000 | 23.75386 | 56.66720 | 1.10746 | 33.76453 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.981377E+09 | 11255.09 | 19-JAN-19:02 | 149.45 | 0.312709E+10 | 0.00 | 0.410847E+10 | 0.64 | 3.19 | 04-JAN-10:08 | 0.00 | 0.00 |
February | 0.143377E+10 | 15367.82 | 19-FEB-16:02 | 177.82 | 0.456863E+10 | 0.00 | 0.600240E+10 | 0.84 | 3.19 | 01-FEB-16:50 | 0.00 | 0.00 |
March | 0.707875E+10 | 82657.81 | 27-MAR-15:01 | 380.95 | 0.221277E+11 | 0.00 | 0.292065E+11 | 1.63 | 3.63 | 27-MAR-15:01 | 0.00 | 0.00 |
April | 0.294602E+11 | 103818.64 | 07-APR-15:03 | 556.83 | 0.890048E+11 | 0.00 | 0.118465E+12 | 2.42 | 3.57 | 07-APR-18:03 | 0.00 | 0.00 |
May | 0.874257E+11 | 124576.15 | 31-MAY-18:03 | 740.75 | 0.268470E+12 | 0.00 | 0.355895E+12 | 3.07 | 4.21 | 19-MAY-18:02 | 0.00 | 0.00 |
June | 0.229139E+12 | 185359.51 | 19-JUN-18:03 | 720.00 | 0.807493E+12 | 0.00 | 0.103663E+13 | 3.44 | 4.31 | 18-JUN-08:03 | 0.00 | 0.00 |
July | 0.318723E+12 | 182852.92 | 20-JUL-18:03 | 744.00 | 0.114496E+13 | 0.00 | 0.146368E+13 | 3.58 | 4.29 | 15-JUL-08:03 | 0.00 | 0.00 |
August | 0.285313E+12 | 199448.21 | 04-AUG-18:03 | 744.00 | 0.972694E+12 | 0.00 | 0.125801E+13 | 3.37 | 4.29 | 06-AUG-18:03 | 0.00 | 0.00 |
September | 0.176439E+12 | 171216.10 | 22-SEP-18:03 | 720.00 | 0.598634E+12 | 0.00 | 0.775074E+12 | 3.27 | 4.31 | 22-SEP-18:03 | 0.00 | 0.00 |
October | 0.844139E+11 | 130651.38 | 05-OCT-15:03 | 713.58 | 0.280034E+12 | 0.00 | 0.364448E+12 | 3.08 | 4.26 | 05-OCT-18:03 | 0.00 | 0.00 |
November | 0.968468E+10 | 62693.68 | 04-NOV-15:03 | 418.31 | 0.302532E+11 | 0.00 | 0.399379E+11 | 1.84 | 3.19 | 01-NOV-19:00 | 0.00 | 0.00 |
December | 0.255980E+10 | 16665.75 | 20-DEC-09:02 | 222.78 | 0.815665E+10 | 0.00 | 0.107165E+11 | 0.95 | 3.19 | 01-DEC-22:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123265E+13 | 6288.47 | 0.422952E+13 | 0.546218E+13 | 2.35 | |||||||
Minimum of Months | 0.981377E+09 | 11255.09 | 149.45 | 0.312709E+10 | 0.00 | 0.410847E+10 | 0.64 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.318723E+12 | 199448.21 | 744.00 | 0.114496E+13 | 0.00 | 0.146368E+13 | 3.58 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.128490E+12 | 0.00 | 744.00 | 194455.84 | 02-JAN-09:05 | 0.00 | 49.72 | 58.68 | 1.23 | 0.00 | 0.11 | 0.43 | 02-JAN-09:05 |
February | 0.112964E+12 | 0.00 | 672.00 | 197743.25 | 06-FEB-09:04 | 0.00 | 50.44 | 58.87 | 1.21 | 0.00 | 0.10 | 0.44 | 06-FEB-09:04 |
March | 0.576191E+11 | 0.00 | 741.22 | 132651.35 | 17-MAR-08:62 | 0.00 | 48.97 | 58.00 | 0.58 | 0.00 | 0.05 | 0.30 | 17-MAR-08:62 |
April | 0.515667E+11 | 0.00 | 683.99 | 117087.28 | 14-APR-15:05 | 0.00 | 45.45 | 56.65 | 0.44 | 0.00 | 0.04 | 0.26 | 14-APR-15:05 |
May | 0.283764E+11 | 0.00 | 653.72 | 87859.20 | 01-MAY-22:40 | 0.00 | 42.36 | 55.57 | 0.19 | 0.00 | 0.02 | 0.20 | 01-MAY-22:40 |
June | 0.983613E+10 | 0.00 | 540.78 | 47890.43 | 06-JUN-08:06 | 0.00 | 43.21 | 53.71 | 0.07 | 0.00 | 0.01 | 0.11 | 06-JUN-08:06 |
July | 0.768605E+10 | 0.00 | 493.16 | 26520.74 | 24-JUL-08:05 | 0.00 | 43.39 | 52.37 | 0.06 | 0.00 | 0.01 | 0.06 | 24-JUL-08:05 |
August | 0.623281E+10 | 0.00 | 476.76 | 35739.97 | 07-AUG-08:05 | 0.00 | 43.83 | 52.26 | 0.05 | 0.00 | 0.01 | 0.08 | 07-AUG-08:05 |
September | 0.122750E+11 | 0.00 | 553.15 | 78877.01 | 24-SEP-06:00 | 0.00 | 42.40 | 53.82 | 0.08 | 0.00 | 0.01 | 0.18 | 24-SEP-06:00 |
October | 0.380708E+11 | 0.00 | 610.55 | 116894.63 | 09-OCT-08:06 | 0.00 | 44.04 | 54.79 | 0.28 | 0.00 | 0.03 | 0.26 | 09-OCT-08:06 |
November | 0.739053E+11 | 0.00 | 715.39 | 139165.33 | 27-NOV-16:04 | 0.00 | 47.89 | 57.70 | 0.71 | 0.00 | 0.06 | 0.31 | 27-NOV-16:04 |
December | 0.740374E+11 | 0.00 | 744.00 | 145866.88 | 31-DEC-19:02 | 0.00 | 50.36 | 58.34 | 0.83 | 0.00 | 0.06 | 0.33 | 31-DEC-19:02 |
Annual Sum or Average | 0.601059E+12 | 7628.74 | 45.98 | 55.88 | 0.47 | 0.00 | 0.04 | ||||||
Minimum of Months | 0.623281E+10 | 0.00 | 476.76 | 26520.74 | 0.00 | 42.36 | 52.26 | 0.05 | 0.00 | 0.01 | 0.06 | ||
Maximum of Months | 0.128490E+12 | 0.00 | 744.00 | 197743.25 | 0.00 | 50.44 | 58.87 | 1.23 | 0.00 | 0.11 | 0.44 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 28898596.61 | 0.00 | 7.60 | 28526698.20 | 0.00 | 0.00 | 0.00 | 0.00 | 12061.86 | 17-JAN-16:02 | 12061.86 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 73258719.12 | 0.00 | 14.33 | 73146591.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12062.55 | 20-FEB-16:02 | 12062.55 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.575742E+09 | 0.00 | 99.09 | 0.512410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14025.03 | 27-MAR-15:01 | 12065.67 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.151121E+10 | 0.00 | 255.50 | 0.102333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12950.50 | 09-APR-08:62 | 12485.94 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.326378E+10 | 0.00 | 504.48 | 0.208739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15318.34 | 18-MAY-15:01 | 12815.72 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.685726E+10 | 0.00 | 647.16 | 0.362071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17968.51 | 25-JUN-08:62 | 12951.36 | 07-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.948181E+10 | 0.00 | 702.67 | 0.487793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18471.86 | 21-JUL-08:62 | 12987.71 | 16-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.944617E+10 | 0.00 | 702.66 | 0.539345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17366.87 | 03-AUG-08:62 | 13010.35 | 17-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.515818E+10 | 0.00 | 607.44 | 0.273573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18905.12 | 22-SEP-18:02 | 12761.69 | 05-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.317581E+10 | 0.00 | 480.67 | 0.184728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15285.66 | 25-OCT-08:62 | 12310.24 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.264122E+09 | 0.00 | 87.27 | 0.193131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12184.51 | 02-NOV-15:01 | 12184.51 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 39052614.98 | 0.00 | 12.98 | 38354453.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12056.01 | 17-DEC-16:01 | 12056.01 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398753E+11 | 4121.85 | 0.224314E+11 | ||||||||||||
Minimum of Months | 28898596.61 | 0.00 | 7.60 | 28526698.20 | 0.00 | 0.00 | 0.00 | 0.00 | 12056.01 | 12056.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.948181E+10 | 0.00 | 702.67 | 0.539345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18905.12 | 13010.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4599852.99 | 0.00 | 1.39 | 4145933.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10010.52 | 17-JAN-16:02 | 10010.52 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 12354744.52 | 0.00 | 4.49 | 12294039.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11094.62 | 20-FEB-16:02 | 11094.62 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.305720E+09 | 0.00 | 56.98 | 0.265946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13567.97 | 27-MAR-15:01 | 11877.54 | 07-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.117028E+10 | 0.00 | 208.25 | 0.793289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13337.65 | 09-APR-15:01 | 12296.47 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.305439E+10 | 0.00 | 488.77 | 0.194283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15075.07 | 18-MAY-15:01 | 12649.74 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.668157E+10 | 0.00 | 641.93 | 0.352507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17443.03 | 27-JUN-08:62 | 12807.20 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.921357E+10 | 0.00 | 700.82 | 0.471333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18211.12 | 21-JUL-08:62 | 12797.49 | 16-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.872785E+10 | 0.00 | 696.91 | 0.487818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17131.24 | 16-AUG-08:62 | 12805.19 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.422205E+10 | 0.00 | 553.96 | 0.214162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18607.19 | 22-SEP-18:02 | 12608.57 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.181993E+10 | 0.00 | 344.98 | 0.968959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14890.35 | 23-OCT-15:01 | 12412.87 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 62587473.09 | 0.00 | 26.48 | 50858003.75 | 0.00 | 0.00 | 0.00 | 0.00 | 11910.38 | 02-NOV-15:01 | 11910.38 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2169409.53 | 0.00 | 0.74 | 1903519.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8405.47 | 17-DEC-16:01 | 8405.47 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352771E+11 | 3725.70 | 0.192984E+11 | ||||||||||||
Minimum of Months | 2169409.53 | 0.00 | 0.74 | 1903519.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8405.47 | 8405.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.921357E+10 | 0.00 | 700.82 | 0.487818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18607.19 | 12807.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2236953.90 | 0.00 | 0.67 | 2236953.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.73 | 31-JAN-14:40 | 1084.73 | 31-JAN-14:40 | 0.00 | 0.00 | 0.00 |
February | 0.117233E+10 | 0.00 | 34.55 | 0.117233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21007.74 | 03-FEB-12:30 | 21007.74 | 03-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.376560E+10 | 0.00 | 124.82 | 0.335736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26384.00 | 03-MAR-13:30 | 26384.00 | 03-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.961636E+10 | 0.00 | 289.54 | 0.603928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35586.41 | 07-APR-12:30 | 31460.94 | 08-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.202198E+11 | 0.00 | 576.89 | 0.118869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25225.62 | 29-MAY-19:10 | 19477.48 | 28-MAY-08:00 | 0.00 | 0.00 | 0.00 |
June | 0.364208E+11 | 0.00 | 707.26 | 0.174730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32608.45 | 19-JUN-19:10 | 24087.36 | 19-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.501910E+11 | 0.00 | 742.67 | 0.252493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36657.69 | 08-JUL-08:00 | 24053.29 | 08-JUL-08:00 | 0.00 | 0.00 | 0.00 |
August | 0.541123E+11 | 0.00 | 742.97 | 0.313922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37733.59 | 16-AUG-12:30 | 31118.18 | 30-AUG-12:40 | 0.00 | 0.00 | 0.00 |
September | 0.408324E+11 | 0.00 | 691.83 | 0.247547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44538.11 | 14-SEP-13:30 | 36478.69 | 30-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.398803E+11 | 0.00 | 652.21 | 0.296943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48994.52 | 04-OCT-12:10 | 45529.77 | 30-OCT-12:50 | 0.00 | 0.00 | 0.00 |
November | 0.979186E+10 | 0.00 | 231.53 | 0.852904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42776.57 | 02-NOV-12:30 | 42776.57 | 02-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.356727E+10 | 0.00 | 89.92 | 0.356727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32325.54 | 17-DEC-13:00 | 32325.54 | 17-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269572E+12 | 4884.85 | 0.163118E+12 | ||||||||||||
Minimum of Months | 2236953.90 | 0.00 | 0.67 | 2236953.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.73 | 1084.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.541123E+11 | 0.00 | 742.97 | 0.313922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48994.52 | 45529.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.890610E+09 | 0.00 | 62.29 | 0.540329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66059.71 | 24-JAN-09:02 | 64207.83 | 21-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.525304E+09 | 0.00 | 47.90 | 0.498444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65192.12 | 20-FEB-09:02 | 65192.12 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.528552E+10 | 0.00 | 236.45 | 0.403005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74959.28 | 27-MAR-15:01 | 68080.96 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.166632E+11 | 0.00 | 416.18 | 0.114293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76862.12 | 08-APR-15:01 | 72570.41 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.359183E+11 | 0.00 | 551.52 | 0.246562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87644.68 | 31-MAY-18:02 | 75508.36 | 30-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.594178E+11 | 0.00 | 593.34 | 0.352983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108622.57 | 27-JUN-08:62 | 75603.88 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.809628E+11 | 0.00 | 653.39 | 0.469154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114964.48 | 21-JUL-08:62 | 76179.10 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.700013E+11 | 0.00 | 637.73 | 0.427145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106825.25 | 31-AUG-18:02 | 75493.08 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.445069E+11 | 0.00 | 550.30 | 0.263300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114826.38 | 22-SEP-18:02 | 74948.77 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.237591E+11 | 0.00 | 487.16 | 0.140727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88618.28 | 06-OCT-08:62 | 70693.69 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.667967E+10 | 0.00 | 269.05 | 0.451366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78491.06 | 10-NOV-09:02 | 67356.19 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.915113E+09 | 0.00 | 79.67 | 0.757254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64272.30 | 10-DEC-09:02 | 64272.30 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345525E+12 | 4584.98 | 0.211756E+12 | ||||||||||||
Minimum of Months | 0.525304E+09 | 0.00 | 47.90 | 0.498444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64272.30 | 64207.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.809628E+11 | 0.00 | 653.39 | 0.469154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114964.48 | 76179.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 40148841.17 | 0.00 | 13.15 | 37815322.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.84 | 17-JAN-16:02 | 9965.84 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 68849771.67 | 0.00 | 18.74 | 68647350.92 | 0.00 | 0.00 | 0.00 | 0.00 | 10573.26 | 19-FEB-09:02 | 10573.26 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.434088E+09 | 0.00 | 98.47 | 0.388378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12384.20 | 27-MAR-15:01 | 10881.18 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.149384E+10 | 0.00 | 277.07 | 0.973797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11799.46 | 09-APR-15:01 | 11253.17 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.341025E+10 | 0.00 | 528.46 | 0.219347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13679.09 | 18-MAY-15:01 | 11554.24 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.639369E+10 | 0.00 | 658.12 | 0.334963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15612.64 | 21-JUN-18:02 | 11663.96 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.933148E+10 | 0.00 | 712.00 | 0.483462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16469.24 | 21-JUL-08:62 | 11615.91 | 14-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.934717E+10 | 0.00 | 716.81 | 0.533349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15539.69 | 31-AUG-18:02 | 11650.54 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.519553E+10 | 0.00 | 623.42 | 0.281071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17060.67 | 22-SEP-18:02 | 11623.90 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.300267E+10 | 0.00 | 487.60 | 0.172448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13827.39 | 25-OCT-08:62 | 11286.77 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.373008E+09 | 0.00 | 104.18 | 0.274291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10986.77 | 02-NOV-15:01 | 10986.77 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 82578896.92 | 0.00 | 22.73 | 78491768.07 | 0.00 | 0.00 | 0.00 | 0.00 | 10654.69 | 17-DEC-09:02 | 10654.69 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391733E+11 | 4260.75 | 0.220678E+11 | ||||||||||||
Minimum of Months | 40148841.17 | 0.00 | 13.15 | 37815322.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.84 | 9965.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.934717E+10 | 0.00 | 716.81 | 0.533349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17060.67 | 11663.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 3109490.32 | 0.00 | 1.56 | 1968164.69 | 0.00 | 0.00 | 0.00 | 0.00 | 3042.16 | 19-JAN-09:02 | 2515.96 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 12006653.00 | 0.00 | 3.85 | 11933693.82 | 0.00 | 0.00 | 0.00 | 0.00 | 10059.06 | 19-FEB-09:02 | 10059.06 | 19-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.195297E+09 | 0.00 | 54.62 | 0.170525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12006.77 | 27-MAR-15:01 | 10811.90 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.114106E+10 | 0.00 | 229.92 | 0.726408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12109.88 | 09-APR-15:01 | 11374.89 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.319350E+10 | 0.00 | 506.21 | 0.204727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13608.62 | 18-MAY-15:01 | 11487.14 | 29-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.620975E+10 | 0.00 | 654.01 | 0.324188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15507.62 | 21-JUN-18:02 | 11556.81 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.906322E+10 | 0.00 | 710.18 | 0.466828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16385.43 | 21-JUL-08:62 | 11488.06 | 11-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.862105E+10 | 0.00 | 712.56 | 0.480360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15653.95 | 16-AUG-08:62 | 11567.87 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.422525E+10 | 0.00 | 574.64 | 0.217573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16944.32 | 22-SEP-18:02 | 11431.64 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.160547E+10 | 0.00 | 340.93 | 0.811951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13923.45 | 25-OCT-08:62 | 11301.30 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.102832E+09 | 0.00 | 41.22 | 65364330.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10447.21 | 11-NOV-09:02 | 10150.36 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 6378061.03 | 0.00 | 2.42 | 5557952.18 | 0.00 | 0.00 | 0.00 | 0.00 | 8590.27 | 17-DEC-09:02 | 8590.27 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343789E+11 | 3832.11 | 0.187305E+11 | ||||||||||||
Minimum of Months | 3109490.32 | 0.00 | 1.56 | 1968164.69 | 0.00 | 0.00 | 0.00 | 0.00 | 3042.16 | 2515.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.906322E+10 | 0.00 | 712.56 | 0.480360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16944.32 | 11567.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 7322483.58 | 0.00 | 5.96 | 7125752.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.05 | 17-JAN-16:02 | 3163.05 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 18855955.48 | 0.00 | 13.87 | 18832654.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.23 | 20-FEB-16:02 | 3163.23 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.154485E+09 | 0.00 | 94.59 | 0.137354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.86 | 27-MAR-15:01 | 3165.49 | 27-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.430432E+09 | 0.00 | 240.46 | 0.301602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3514.50 | 09-APR-08:62 | 3273.90 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.970985E+09 | 0.00 | 507.08 | 0.649124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4003.59 | 18-MAY-15:01 | 3360.25 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.205365E+10 | 0.00 | 663.47 | 0.114781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4811.51 | 25-JUN-08:62 | 3382.47 | 25-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.283815E+10 | 0.00 | 711.65 | 0.156601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4926.34 | 21-JUL-08:62 | 3390.62 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.278637E+10 | 0.00 | 708.31 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4644.18 | 27-AUG-08:62 | 3394.98 | 05-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.151653E+10 | 0.00 | 604.02 | 0.857171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5089.28 | 22-SEP-18:02 | 3399.54 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.867477E+09 | 0.00 | 443.10 | 0.522918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4091.01 | 25-OCT-08:62 | 3208.57 | 25-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 60075281.65 | 0.00 | 65.53 | 45198645.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3195.13 | 02-NOV-15:01 | 3195.13 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 7704635.83 | 0.00 | 7.71 | 7573338.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3162.22 | 17-DEC-16:01 | 3162.22 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117120E+11 | 4065.76 | 0.695686E+10 | ||||||||||||
Minimum of Months | 7322483.58 | 0.00 | 5.96 | 7125752.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3162.22 | 3162.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.283815E+10 | 0.00 | 711.65 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5089.28 | 3399.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 667528.07 | 0.00 | 1.00 | 538285.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.68 | 17-JAN-16:02 | 1620.68 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 1261233.35 | 0.00 | 2.08 | 1255692.62 | 0.00 | 0.00 | 0.00 | 0.00 | 2824.38 | 20-FEB-16:02 | 2824.38 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 75450831.41 | 0.00 | 53.68 | 64568439.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3608.24 | 27-MAR-15:01 | 3113.88 | 07-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.334408E+09 | 0.00 | 197.36 | 0.232217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3441.28 | 09-APR-08:62 | 3223.30 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.911303E+09 | 0.00 | 483.88 | 0.606890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3949.65 | 18-MAY-15:01 | 3308.39 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.200751E+10 | 0.00 | 661.82 | 0.111954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4671.49 | 27-JUN-08:62 | 3341.99 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.276804E+10 | 0.00 | 710.53 | 0.151867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4854.27 | 21-JUL-08:62 | 3364.59 | 27-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.259411E+10 | 0.00 | 705.35 | 0.154363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4605.62 | 16-AUG-08:62 | 3368.53 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.125494E+10 | 0.00 | 558.71 | 0.670509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5013.64 | 22-SEP-18:02 | 3348.16 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.496666E+09 | 0.00 | 316.24 | 0.270689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3974.09 | 25-OCT-08:62 | 3208.39 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 13165788.14 | 0.00 | 15.75 | 10980764.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3101.07 | 02-NOV-15:01 | 3101.07 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 681492.19 | 0.00 | 0.66 | 553406.99 | 0.00 | 0.00 | 0.00 | 0.00 | 955.47 | 17-DEC-16:01 | 955.47 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104582E+11 | 3707.05 | 0.604003E+10 | ||||||||||||
Minimum of Months | 667528.07 | 0.00 | 0.66 | 538285.41 | 0.00 | 0.00 | 0.00 | 0.00 | 955.47 | 955.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.276804E+10 | 0.00 | 710.53 | 0.154363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5013.64 | 3368.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.830357E+09 | 0.00 | 97.14 | 0.827363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13053.94 | 17-JAN-16:02 | 13053.94 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.110698E+10 | 0.00 | 149.52 | 0.110672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13054.62 | 20-FEB-16:02 | 13054.62 | 20-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.188435E+10 | 0.00 | 228.21 | 0.170407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14332.30 | 27-MAR-15:01 | 13057.76 | 03-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.270132E+10 | 0.00 | 338.82 | 0.186882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14068.55 | 27-APR-15:01 | 13129.44 | 16-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.493860E+10 | 0.00 | 569.59 | 0.312372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16620.27 | 31-MAY-18:02 | 13860.01 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.101064E+11 | 0.00 | 652.30 | 0.558266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20143.96 | 27-JUN-08:62 | 13979.71 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.149035E+11 | 0.00 | 708.73 | 0.848217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20916.36 | 21-JUL-08:62 | 14074.80 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.147463E+11 | 0.00 | 707.56 | 0.942605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19634.85 | 03-AUG-08:62 | 14090.16 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.101484E+11 | 0.00 | 646.62 | 0.644305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21403.11 | 22-SEP-18:02 | 13960.24 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.858906E+10 | 0.00 | 604.14 | 0.626811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17142.10 | 05-OCT-18:02 | 13594.73 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.222805E+10 | 0.00 | 255.16 | 0.186995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14716.22 | 10-NOV-09:02 | 13185.46 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.156655E+10 | 0.00 | 157.10 | 0.155860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13054.31 | 17-DEC-09:02 | 13054.31 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737498E+11 | 5114.88 | 0.482613E+11 | ||||||||||||
Minimum of Months | 0.830357E+09 | 0.00 | 97.14 | 0.827363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13053.94 | 13053.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.149035E+11 | 0.00 | 708.73 | 0.942605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21403.11 | 14090.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.580398E+10 | 0.00 | 35.17 | 0.506547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199471.62 | 27-MAR-13:00 | 159204.73 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.467937E+11 | 0.00 | 184.67 | 0.454914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 246203.80 | 09-APR-11:00 | 210817.89 | 07-APR-16:50 | 0.00 | 0.00 | 0.00 |
May | 0.176930E+12 | 0.00 | 532.04 | 0.142369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317327.60 | 31-MAY-17:15 | 211357.33 | 29-MAY-09:00 | 0.00 | 0.00 | 0.00 |
June | 0.622615E+12 | 0.00 | 716.83 | 0.354073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 504991.96 | 24-JUN-18:03 | 281631.47 | 22-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.889791E+12 | 0.00 | 744.00 | 0.471676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 513583.93 | 05-JUL-20:20 | 249952.56 | 11-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.736942E+12 | 0.00 | 744.00 | 0.459243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 485447.99 | 03-AUG-20:00 | 305527.92 | 24-AUG-18:25 | 0.00 | 0.00 | 0.00 |
September | 0.446440E+12 | 0.00 | 673.17 | 0.291767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 482731.89 | 22-SEP-17:40 | 255694.79 | 14-SEP-18:40 | 0.00 | 0.00 | 0.00 |
October | 0.180362E+12 | 0.00 | 398.33 | 0.106602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315951.04 | 25-OCT-09:30 | 187198.50 | 25-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.674918E+10 | 0.00 | 48.00 | 0.579243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123617.44 | 10-NOV-08:00 | 79415.51 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311243E+13 | 4076.21 | 0.188208E+13 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.889791E+12 | 0.00 | 744.00 | 0.471676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 513583.93 | 305527.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.267193E+09 | 0.00 | 15.00 | 0.233221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19217.11 | 27-MAR-13:00 | 14115.98 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.214739E+10 | 0.00 | 99.83 | 0.211170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20012.53 | 09-APR-10:00 | 17833.34 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.886479E+10 | 0.00 | 325.33 | 0.743665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28281.36 | 31-MAY-08:61 | 19211.13 | 30-MAY-12:20 | 0.00 | 0.00 | 0.00 |
June | 0.414139E+11 | 0.00 | 557.83 | 0.235291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46837.99 | 24-JUN-18:03 | 21971.88 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 |
July | 0.585410E+11 | 0.00 | 589.00 | 0.319923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46341.16 | 21-JUL-08:62 | 20966.28 | 07-JUL-12:20 | 0.00 | 0.00 | 0.00 |
August | 0.477072E+11 | 0.00 | 589.00 | 0.303814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42954.91 | 05-AUG-18:02 | 20969.79 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.280954E+11 | 0.00 | 496.50 | 0.187665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46319.05 | 14-SEP-08:62 | 19563.76 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.988544E+10 | 0.00 | 251.50 | 0.572323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30498.40 | 03-OCT-15:02 | 17223.10 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.209433E+09 | 0.00 | 19.17 | 0.180063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7314.80 | 10-NOV-08:00 | 6399.28 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197132E+12 | 2943.17 | 0.120354E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.585410E+11 | 0.00 | 589.00 | 0.319923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46837.99 | 21971.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 607.15 | 398.42 | 208.73 | 540.09 | 636.65 | 0.00 | 0.00 | 744.00 |
February | 803.78 | 534.32 | 269.47 | 703.12 | 638.45 | 0.00 | 0.00 | 672.00 |
March | 712.13 | 392.12 | 320.00 | 586.85 | 455.45 | 0.00 | 0.00 | 744.00 |
April | 566.59 | 229.19 | 337.40 | 426.47 | 312.71 | 0.00 | 0.00 | 720.00 |
May | 486.60 | 99.56 | 387.04 | 404.17 | 170.20 | 0.00 | 0.00 | 744.00 |
June | 459.45 | 70.71 | 388.74 | 483.90 | 66.72 | 0.00 | 0.00 | 720.00 |
July | 478.08 | 80.62 | 397.46 | 573.12 | 19.60 | 0.00 | 0.00 | 744.00 |
August | 640.34 | 236.14 | 404.19 | 707.83 | 46.53 | 0.00 | 0.00 | 744.00 |
September | 675.92 | 339.41 | 336.51 | 713.57 | 117.75 | 0.00 | 0.00 | 720.00 |
October | 955.55 | 599.38 | 356.17 | 1018.35 | 271.99 | 0.00 | 0.00 | 744.00 |
November | 661.41 | 396.80 | 264.62 | 633.18 | 439.63 | 0.00 | 0.00 | 720.00 |
December | 655.86 | 465.80 | 190.06 | 624.83 | 572.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.13 | 319.12 | 322.02 | 617.84 | 310.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 459.45 | 70.71 | 190.06 | 404.17 | 19.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 955.55 | 599.38 | 404.19 | 1018.35 | 638.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1709.69 | 1121.93 | 587.76 | 1503.81 | 1838.68 | 0.00 | 0.00 | 744.00 |
February | 2263.40 | 1504.60 | 758.81 | 1957.05 | 1844.21 | 0.00 | 0.00 | 672.00 |
March | 2005.30 | 1104.19 | 901.11 | 1630.55 | 1353.98 | 0.00 | 0.00 | 744.00 |
April | 1595.47 | 645.39 | 950.08 | 1176.20 | 951.40 | 0.00 | 0.00 | 720.00 |
May | 1370.24 | 280.36 | 1089.88 | 1104.08 | 539.39 | 0.00 | 0.00 | 744.00 |
June | 1293.77 | 199.10 | 1094.67 | 1329.78 | 230.55 | 0.00 | 0.00 | 720.00 |
July | 1346.23 | 227.02 | 1119.21 | 1579.95 | 82.07 | 0.00 | 0.00 | 744.00 |
August | 1803.15 | 664.97 | 1138.18 | 1968.35 | 160.58 | 0.00 | 0.00 | 744.00 |
September | 1903.35 | 955.75 | 947.60 | 1984.83 | 386.65 | 0.00 | 0.00 | 720.00 |
October | 2690.75 | 1687.81 | 1002.94 | 2837.11 | 843.31 | 0.00 | 0.00 | 744.00 |
November | 1862.50 | 1117.35 | 745.15 | 1755.77 | 1308.74 | 0.00 | 0.00 | 720.00 |
December | 1846.86 | 1311.67 | 535.20 | 1738.63 | 1671.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1805.39 | 898.61 | 906.78 | 1713.51 | 929.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1293.77 | 199.10 | 535.20 | 1104.08 | 82.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2690.75 | 1687.81 | 1138.18 | 2837.11 | 1844.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2220.99 | 1457.45 | 763.54 | 1983.04 | 2505.78 | 0.00 | 0.00 | 744.00 |
February | 2940.29 | 1954.56 | 985.73 | 2587.31 | 2498.67 | 0.00 | 0.00 | 672.00 |
March | 2605.00 | 1434.41 | 1170.59 | 2160.21 | 1838.51 | 0.00 | 0.00 | 744.00 |
April | 2072.61 | 838.39 | 1234.21 | 1558.38 | 1298.08 | 0.00 | 0.00 | 720.00 |
May | 1780.02 | 364.21 | 1415.82 | 1469.03 | 729.96 | 0.00 | 0.00 | 744.00 |
June | 1680.68 | 258.65 | 1422.04 | 1782.65 | 303.05 | 0.00 | 0.00 | 720.00 |
July | 1748.83 | 294.91 | 1453.92 | 2129.35 | 102.17 | 0.00 | 0.00 | 744.00 |
August | 2342.40 | 863.83 | 1478.57 | 2654.85 | 199.53 | 0.00 | 0.00 | 744.00 |
September | 2472.56 | 1241.57 | 1230.99 | 2655.60 | 500.96 | 0.00 | 0.00 | 720.00 |
October | 3495.44 | 2192.56 | 1302.88 | 3780.89 | 1105.24 | 0.00 | 0.00 | 744.00 |
November | 2419.49 | 1451.50 | 967.99 | 2317.92 | 1781.85 | 0.00 | 0.00 | 720.00 |
December | 2399.18 | 1703.93 | 695.25 | 2293.38 | 2279.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2345.30 | 1167.35 | 1177.96 | 2280.75 | 1254.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1680.68 | 258.65 | 695.25 | 1469.03 | 102.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3495.44 | 2192.56 | 1478.57 | 3780.89 | 2505.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.80 | 78.61 | 41.18 | 106.42 | 131.14 | 0.00 | 0.00 | 744.00 |
February | 158.60 | 105.43 | 53.17 | 138.58 | 131.93 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 77.37 | 63.14 | 115.54 | 94.86 | 0.00 | 0.00 | 744.00 |
April | 111.80 | 45.22 | 66.57 | 83.44 | 65.22 | 0.00 | 0.00 | 720.00 |
May | 96.01 | 19.65 | 76.37 | 77.55 | 35.57 | 0.00 | 0.00 | 744.00 |
June | 90.66 | 13.95 | 76.70 | 94.51 | 12.84 | 0.00 | 0.00 | 720.00 |
July | 94.33 | 15.91 | 78.42 | 116.03 | 2.83 | 0.00 | 0.00 | 744.00 |
August | 126.35 | 46.59 | 79.75 | 145.03 | 7.32 | 0.00 | 0.00 | 744.00 |
September | 133.37 | 66.97 | 66.40 | 142.35 | 22.18 | 0.00 | 0.00 | 720.00 |
October | 188.54 | 118.27 | 70.28 | 202.74 | 53.03 | 0.00 | 0.00 | 744.00 |
November | 130.51 | 78.29 | 52.21 | 125.30 | 89.34 | 0.00 | 0.00 | 720.00 |
December | 129.41 | 91.91 | 37.50 | 123.77 | 116.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.50 | 62.97 | 63.54 | 122.60 | 63.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.66 | 13.95 | 37.50 | 77.55 | 2.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.54 | 118.27 | 79.75 | 202.74 | 131.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.05 | 36.56 | 52.48 | 37.08 | 269.17 | 0.00 | 0.00 | 744.00 |
February | 130.79 | 57.40 | 73.39 | 64.09 | 272.95 | 0.00 | 0.00 | 672.00 |
March | 194.29 | 90.05 | 104.24 | 141.11 | 175.51 | 0.00 | 0.00 | 744.00 |
April | 211.00 | 90.17 | 120.83 | 183.72 | 118.78 | 0.00 | 0.00 | 720.00 |
May | 246.46 | 93.68 | 152.79 | 253.27 | 63.86 | 0.00 | 0.00 | 744.00 |
June | 269.28 | 108.66 | 160.62 | 323.24 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 251.94 | 94.66 | 157.28 | 335.50 | 5.21 | 0.00 | 0.00 | 744.00 |
August | 278.76 | 128.89 | 149.88 | 368.15 | 13.57 | 0.00 | 0.00 | 744.00 |
September | 198.35 | 86.60 | 111.75 | 225.14 | 41.46 | 0.00 | 0.00 | 720.00 |
October | 196.80 | 95.87 | 100.93 | 187.21 | 101.43 | 0.00 | 0.00 | 744.00 |
November | 92.68 | 27.08 | 65.60 | 43.36 | 180.23 | 0.00 | 0.00 | 720.00 |
December | 81.87 | 35.35 | 46.52 | 34.04 | 243.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.17 | 78.93 | 108.24 | 183.85 | 124.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.87 | 27.08 | 46.52 | 34.04 | 5.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.76 | 128.89 | 160.62 | 368.15 | 272.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.05 | 0.00 | 23.05 | 0.21 | 149.81 | 0.00 | 0.00 | 744.00 |
February | 31.54 | 0.00 | 31.54 | 1.10 | 154.51 | 0.00 | 0.00 | 672.00 |
March | 43.75 | 0.00 | 43.75 | 9.41 | 99.56 | 0.00 | 0.00 | 744.00 |
April | 52.64 | 0.21 | 52.43 | 25.66 | 64.91 | 0.00 | 0.00 | 720.00 |
May | 70.02 | 2.56 | 67.46 | 54.96 | 32.99 | 0.00 | 0.00 | 744.00 |
June | 73.86 | 3.92 | 69.94 | 81.80 | 11.86 | 0.00 | 0.00 | 720.00 |
July | 71.69 | 2.79 | 68.90 | 98.17 | 2.68 | 0.00 | 0.00 | 744.00 |
August | 63.40 | 0.84 | 62.57 | 87.92 | 6.94 | 0.00 | 0.00 | 744.00 |
September | 47.74 | 0.03 | 47.72 | 48.35 | 21.88 | 0.00 | 0.00 | 720.00 |
October | 41.29 | 0.00 | 41.29 | 25.26 | 54.64 | 0.00 | 0.00 | 744.00 |
November | 28.96 | 0.00 | 28.96 | 5.25 | 98.42 | 0.00 | 0.00 | 720.00 |
December | 20.10 | 0.00 | 20.10 | 0.21 | 135.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.43 | 0.87 | 46.56 | 36.78 | 68.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.10 | 0.00 | 20.10 | 0.21 | 2.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.86 | 3.92 | 69.94 | 98.17 | 154.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.05 | 36.56 | 52.48 | 39.21 | 265.54 | 0.00 | 0.00 | 744.00 |
February | 130.79 | 57.40 | 73.39 | 67.40 | 268.25 | 0.00 | 0.00 | 672.00 |
March | 194.29 | 90.05 | 104.24 | 145.10 | 172.98 | 0.00 | 0.00 | 744.00 |
April | 211.00 | 90.17 | 120.83 | 185.99 | 117.71 | 0.00 | 0.00 | 720.00 |
May | 246.46 | 93.68 | 152.79 | 254.17 | 63.54 | 0.00 | 0.00 | 744.00 |
June | 269.28 | 108.66 | 160.62 | 323.70 | 23.14 | 0.00 | 0.00 | 720.00 |
July | 251.94 | 94.66 | 157.28 | 336.03 | 5.14 | 0.00 | 0.00 | 744.00 |
August | 278.76 | 128.89 | 149.88 | 369.59 | 13.29 | 0.00 | 0.00 | 744.00 |
September | 198.35 | 86.60 | 111.75 | 227.69 | 40.60 | 0.00 | 0.00 | 720.00 |
October | 196.80 | 95.87 | 100.93 | 192.40 | 99.08 | 0.00 | 0.00 | 744.00 |
November | 92.68 | 27.08 | 65.60 | 46.77 | 176.67 | 0.00 | 0.00 | 720.00 |
December | 81.87 | 35.35 | 46.52 | 36.68 | 239.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.17 | 78.93 | 108.24 | 186.25 | 122.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.87 | 27.08 | 46.52 | 36.68 | 5.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.76 | 128.89 | 160.62 | 369.59 | 268.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.82 | 62.88 | 32.94 | 83.15 | 109.12 | 0.00 | 0.00 | 744.00 |
February | 126.85 | 84.33 | 42.53 | 103.23 | 126.75 | 0.00 | 0.00 | 672.00 |
March | 112.39 | 61.88 | 50.50 | 84.60 | 101.33 | 0.00 | 0.00 | 744.00 |
April | 89.42 | 36.17 | 53.25 | 56.89 | 76.78 | 0.00 | 0.00 | 720.00 |
May | 76.80 | 15.71 | 61.08 | 48.88 | 49.31 | 0.00 | 0.00 | 744.00 |
June | 72.51 | 11.16 | 61.35 | 60.31 | 26.56 | 0.00 | 0.00 | 720.00 |
July | 75.45 | 12.72 | 62.73 | 75.00 | 15.04 | 0.00 | 0.00 | 744.00 |
August | 101.06 | 37.27 | 63.79 | 99.22 | 19.60 | 0.00 | 0.00 | 744.00 |
September | 106.67 | 53.57 | 53.11 | 100.89 | 38.26 | 0.00 | 0.00 | 720.00 |
October | 150.80 | 94.59 | 56.21 | 150.18 | 66.82 | 0.00 | 0.00 | 744.00 |
November | 104.38 | 62.62 | 41.76 | 90.17 | 98.89 | 0.00 | 0.00 | 720.00 |
December | 103.51 | 73.51 | 30.00 | 91.46 | 116.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 101.18 | 50.36 | 50.82 | 86.97 | 70.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.51 | 11.16 | 30.00 | 48.88 | 15.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.80 | 94.59 | 63.79 | 150.18 | 126.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.44 | 0.00 | 18.44 | 0.07 | 125.94 | 0.00 | 0.00 | 744.00 |
February | 25.24 | 0.00 | 25.24 | 0.65 | 128.55 | 0.00 | 0.00 | 672.00 |
March | 35.00 | 0.00 | 35.00 | 7.11 | 82.18 | 0.00 | 0.00 | 744.00 |
April | 42.12 | 0.17 | 41.95 | 20.79 | 53.32 | 0.00 | 0.00 | 720.00 |
May | 56.02 | 2.04 | 53.98 | 45.49 | 26.42 | 0.00 | 0.00 | 744.00 |
June | 59.10 | 3.14 | 55.96 | 68.42 | 8.94 | 0.00 | 0.00 | 720.00 |
July | 57.36 | 2.23 | 55.13 | 82.00 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 50.73 | 0.67 | 50.06 | 74.15 | 4.98 | 0.00 | 0.00 | 744.00 |
September | 38.20 | 0.02 | 38.18 | 40.51 | 17.16 | 0.00 | 0.00 | 720.00 |
October | 33.03 | 0.00 | 33.03 | 20.99 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 23.17 | 0.00 | 23.17 | 3.81 | 83.16 | 0.00 | 0.00 | 720.00 |
December | 16.09 | 0.00 | 16.09 | 0.10 | 114.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 37.95 | 0.69 | 37.25 | 30.55 | 57.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.09 | 0.00 | 16.09 | 0.07 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.10 | 3.14 | 55.96 | 82.00 | 128.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.67 | 35.83 | 53.84 | 33.84 | 264.42 | 0.00 | 0.00 | 744.00 |
February | 139.21 | 64.83 | 74.38 | 67.62 | 263.08 | 0.00 | 0.00 | 672.00 |
March | 178.76 | 75.97 | 102.79 | 122.69 | 176.28 | 0.00 | 0.00 | 744.00 |
April | 214.00 | 93.93 | 120.07 | 183.19 | 114.88 | 0.00 | 0.00 | 720.00 |
May | 258.32 | 102.93 | 155.39 | 266.01 | 61.63 | 0.00 | 0.00 | 744.00 |
June | 239.87 | 86.87 | 153.00 | 285.39 | 22.12 | 0.00 | 0.00 | 720.00 |
July | 240.61 | 86.61 | 154.00 | 322.00 | 4.90 | 0.00 | 0.00 | 744.00 |
August | 271.45 | 122.46 | 148.99 | 358.14 | 12.63 | 0.00 | 0.00 | 744.00 |
September | 203.08 | 91.49 | 111.58 | 228.39 | 39.47 | 0.00 | 0.00 | 720.00 |
October | 183.45 | 83.04 | 100.41 | 167.23 | 98.36 | 0.00 | 0.00 | 744.00 |
November | 113.63 | 43.67 | 69.96 | 63.22 | 174.48 | 0.00 | 0.00 | 720.00 |
December | 88.84 | 41.93 | 46.92 | 37.86 | 237.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.37 | 77.55 | 107.82 | 178.74 | 121.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.84 | 35.83 | 46.92 | 33.84 | 4.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 271.45 | 122.46 | 155.39 | 358.14 | 264.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.80 | 78.61 | 41.18 | 106.11 | 130.98 | 0.00 | 0.00 | 744.00 |
February | 158.60 | 105.43 | 53.17 | 137.85 | 131.66 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 77.37 | 63.14 | 114.73 | 94.11 | 0.00 | 0.00 | 744.00 |
April | 111.80 | 45.22 | 66.57 | 82.45 | 64.87 | 0.00 | 0.00 | 720.00 |
May | 96.01 | 19.65 | 76.37 | 76.46 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 90.66 | 13.95 | 76.70 | 94.45 | 12.45 | 0.00 | 0.00 | 720.00 |
July | 94.33 | 15.91 | 78.42 | 115.93 | 2.69 | 0.00 | 0.00 | 744.00 |
August | 126.35 | 46.59 | 79.75 | 144.67 | 7.08 | 0.00 | 0.00 | 744.00 |
September | 133.37 | 66.97 | 66.40 | 141.80 | 21.93 | 0.00 | 0.00 | 720.00 |
October | 188.54 | 118.27 | 70.28 | 202.17 | 52.52 | 0.00 | 0.00 | 744.00 |
November | 130.51 | 78.29 | 52.21 | 124.59 | 89.43 | 0.00 | 0.00 | 720.00 |
December | 129.41 | 91.91 | 37.50 | 123.36 | 116.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.50 | 62.97 | 63.54 | 122.04 | 62.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.66 | 13.95 | 37.50 | 76.46 | 2.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.54 | 118.27 | 79.75 | 202.17 | 131.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.05 | 0.00 | 23.05 | 0.17 | 149.88 | 0.00 | 0.00 | 744.00 |
February | 31.54 | 0.00 | 31.54 | 0.97 | 154.74 | 0.00 | 0.00 | 672.00 |
March | 43.75 | 0.00 | 43.75 | 8.85 | 99.04 | 0.00 | 0.00 | 744.00 |
April | 52.64 | 0.21 | 52.43 | 24.75 | 64.73 | 0.00 | 0.00 | 720.00 |
May | 70.02 | 2.56 | 67.46 | 53.88 | 32.64 | 0.00 | 0.00 | 744.00 |
June | 73.86 | 3.92 | 69.94 | 81.80 | 11.52 | 0.00 | 0.00 | 720.00 |
July | 71.69 | 2.79 | 68.90 | 98.08 | 2.54 | 0.00 | 0.00 | 744.00 |
August | 63.40 | 0.84 | 62.57 | 87.54 | 6.71 | 0.00 | 0.00 | 744.00 |
September | 47.74 | 0.03 | 47.72 | 47.70 | 21.71 | 0.00 | 0.00 | 720.00 |
October | 41.29 | 0.00 | 41.29 | 24.59 | 54.08 | 0.00 | 0.00 | 744.00 |
November | 28.96 | 0.00 | 28.96 | 4.90 | 98.88 | 0.00 | 0.00 | 720.00 |
December | 20.10 | 0.00 | 20.10 | 0.17 | 135.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.43 | 0.87 | 46.56 | 36.36 | 68.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.10 | 0.00 | 20.10 | 0.17 | 2.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.86 | 3.92 | 69.94 | 98.08 | 154.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.67 | 35.83 | 53.84 | 34.75 | 259.57 | 0.00 | 0.00 | 744.00 |
February | 139.21 | 64.83 | 74.38 | 69.33 | 256.66 | 0.00 | 0.00 | 672.00 |
March | 178.76 | 75.97 | 102.79 | 125.91 | 172.91 | 0.00 | 0.00 | 744.00 |
April | 214.00 | 93.93 | 120.07 | 185.22 | 113.70 | 0.00 | 0.00 | 720.00 |
May | 258.32 | 102.93 | 155.39 | 266.82 | 61.29 | 0.00 | 0.00 | 744.00 |
June | 239.87 | 86.87 | 153.00 | 285.85 | 21.98 | 0.00 | 0.00 | 720.00 |
July | 240.61 | 86.61 | 154.00 | 322.54 | 4.85 | 0.00 | 0.00 | 744.00 |
August | 271.45 | 122.46 | 148.99 | 359.51 | 12.35 | 0.00 | 0.00 | 744.00 |
September | 203.08 | 91.49 | 111.58 | 230.68 | 38.60 | 0.00 | 0.00 | 720.00 |
October | 183.45 | 83.04 | 100.41 | 171.95 | 95.65 | 0.00 | 0.00 | 744.00 |
November | 113.63 | 43.67 | 69.96 | 65.87 | 170.31 | 0.00 | 0.00 | 720.00 |
December | 88.84 | 41.93 | 46.92 | 38.98 | 231.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.37 | 77.55 | 107.82 | 180.56 | 119.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.84 | 35.83 | 46.92 | 34.75 | 4.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 271.45 | 122.46 | 155.39 | 359.51 | 259.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.19 | 0.00 | 29.19 | 0.10 | 198.27 | 0.00 | 0.00 | 744.00 |
February | 39.94 | 0.00 | 39.94 | 1.06 | 202.83 | 0.00 | 0.00 | 672.00 |
March | 55.40 | 0.00 | 55.40 | 11.86 | 127.49 | 0.00 | 0.00 | 744.00 |
April | 66.67 | 0.27 | 66.40 | 35.29 | 81.55 | 0.00 | 0.00 | 720.00 |
May | 88.67 | 3.24 | 85.43 | 76.78 | 39.89 | 0.00 | 0.00 | 744.00 |
June | 93.54 | 4.96 | 88.58 | 113.85 | 13.00 | 0.00 | 0.00 | 720.00 |
July | 90.80 | 3.53 | 87.26 | 135.20 | 2.41 | 0.00 | 0.00 | 744.00 |
August | 80.29 | 1.06 | 79.23 | 121.29 | 7.49 | 0.00 | 0.00 | 744.00 |
September | 60.46 | 0.03 | 60.43 | 67.72 | 25.65 | 0.00 | 0.00 | 720.00 |
October | 52.29 | 0.00 | 52.29 | 35.04 | 67.56 | 0.00 | 0.00 | 744.00 |
November | 36.67 | 0.00 | 36.67 | 6.55 | 129.08 | 0.00 | 0.00 | 720.00 |
December | 25.46 | 0.00 | 25.46 | 0.16 | 179.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.07 | 1.10 | 58.97 | 50.75 | 88.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.46 | 0.00 | 25.46 | 0.10 | 2.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.54 | 4.96 | 88.58 | 135.20 | 202.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.76 | 0.00 | 10.76 | 0.04 | 73.09 | 0.00 | 0.00 | 744.00 |
February | 14.72 | 0.00 | 14.72 | 0.39 | 74.77 | 0.00 | 0.00 | 672.00 |
March | 20.42 | 0.00 | 20.42 | 4.37 | 47.00 | 0.00 | 0.00 | 744.00 |
April | 24.58 | 0.10 | 24.48 | 13.01 | 30.06 | 0.00 | 0.00 | 720.00 |
May | 32.69 | 1.19 | 31.49 | 28.30 | 14.71 | 0.00 | 0.00 | 744.00 |
June | 34.48 | 1.83 | 32.65 | 41.97 | 4.79 | 0.00 | 0.00 | 720.00 |
July | 33.47 | 1.30 | 32.17 | 49.84 | 0.89 | 0.00 | 0.00 | 744.00 |
August | 29.60 | 0.39 | 29.21 | 44.71 | 2.76 | 0.00 | 0.00 | 744.00 |
September | 22.29 | 0.01 | 22.28 | 24.97 | 9.45 | 0.00 | 0.00 | 720.00 |
October | 19.27 | 0.00 | 19.27 | 12.92 | 24.91 | 0.00 | 0.00 | 744.00 |
November | 13.52 | 0.00 | 13.52 | 2.41 | 47.59 | 0.00 | 0.00 | 720.00 |
December | 9.39 | 0.00 | 9.39 | 0.06 | 66.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.14 | 0.40 | 21.74 | 18.71 | 32.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.39 | 0.00 | 9.39 | 0.04 | 0.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.48 | 1.83 | 32.65 | 49.84 | 74.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 55.90 | 36.68 | 19.22 | 49.70 | 62.75 | 0.00 | 0.00 | 744.00 |
February | 74.00 | 49.19 | 24.81 | 64.98 | 62.53 | 0.00 | 0.00 | 672.00 |
March | 65.56 | 36.10 | 29.46 | 54.85 | 44.13 | 0.00 | 0.00 | 744.00 |
April | 52.16 | 21.10 | 31.06 | 40.49 | 29.84 | 0.00 | 0.00 | 720.00 |
May | 44.80 | 9.17 | 35.63 | 38.94 | 15.61 | 0.00 | 0.00 | 744.00 |
June | 42.30 | 6.51 | 35.79 | 47.95 | 5.07 | 0.00 | 0.00 | 720.00 |
July | 44.01 | 7.42 | 36.59 | 58.33 | 0.91 | 0.00 | 0.00 | 744.00 |
August | 58.95 | 21.74 | 37.21 | 71.67 | 2.82 | 0.00 | 0.00 | 744.00 |
September | 62.23 | 31.25 | 30.98 | 69.42 | 9.33 | 0.00 | 0.00 | 720.00 |
October | 87.97 | 55.18 | 32.79 | 97.16 | 23.68 | 0.00 | 0.00 | 744.00 |
November | 60.89 | 36.53 | 24.36 | 59.13 | 42.16 | 0.00 | 0.00 | 720.00 |
December | 60.38 | 42.88 | 17.50 | 58.02 | 55.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.03 | 29.38 | 29.65 | 59.23 | 29.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 42.30 | 6.51 | 17.50 | 38.94 | 0.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.97 | 55.18 | 37.21 | 97.16 | 62.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.72 | 99.56 | 52.16 | 134.91 | 170.32 | 0.00 | 0.00 | 744.00 |
February | 200.85 | 133.52 | 67.34 | 176.38 | 169.73 | 0.00 | 0.00 | 672.00 |
March | 177.95 | 97.99 | 79.96 | 148.87 | 119.77 | 0.00 | 0.00 | 744.00 |
April | 141.58 | 57.27 | 84.31 | 109.89 | 81.00 | 0.00 | 0.00 | 720.00 |
May | 121.60 | 24.88 | 96.72 | 105.70 | 42.37 | 0.00 | 0.00 | 744.00 |
June | 114.81 | 17.67 | 97.14 | 130.15 | 13.75 | 0.00 | 0.00 | 720.00 |
July | 119.46 | 20.15 | 99.32 | 158.33 | 2.47 | 0.00 | 0.00 | 744.00 |
August | 160.01 | 59.01 | 101.00 | 194.53 | 7.66 | 0.00 | 0.00 | 744.00 |
September | 168.90 | 84.81 | 84.09 | 188.43 | 25.33 | 0.00 | 0.00 | 720.00 |
October | 238.78 | 149.78 | 89.00 | 263.72 | 64.26 | 0.00 | 0.00 | 744.00 |
November | 165.28 | 99.15 | 66.12 | 160.50 | 114.43 | 0.00 | 0.00 | 720.00 |
December | 163.89 | 116.40 | 47.49 | 157.49 | 151.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 160.21 | 79.74 | 80.47 | 160.76 | 79.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 17.67 | 47.49 | 105.70 | 2.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 238.78 | 149.78 | 101.00 | 263.72 | 170.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.90 | 78.68 | 41.22 | 106.20 | 130.71 | 0.00 | 0.00 | 744.00 |
February | 158.73 | 105.51 | 53.21 | 138.23 | 131.68 | 0.00 | 0.00 | 672.00 |
March | 140.63 | 77.43 | 63.19 | 115.13 | 94.82 | 0.00 | 0.00 | 744.00 |
April | 111.89 | 45.26 | 66.63 | 82.94 | 65.29 | 0.00 | 0.00 | 720.00 |
May | 96.09 | 19.66 | 76.43 | 76.37 | 35.94 | 0.00 | 0.00 | 744.00 |
June | 90.73 | 13.96 | 76.77 | 93.17 | 13.12 | 0.00 | 0.00 | 720.00 |
July | 94.41 | 15.92 | 78.49 | 114.70 | 2.92 | 0.00 | 0.00 | 744.00 |
August | 126.45 | 46.63 | 79.82 | 144.02 | 7.38 | 0.00 | 0.00 | 744.00 |
September | 133.48 | 67.02 | 66.45 | 141.27 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 188.70 | 118.36 | 70.33 | 201.66 | 53.07 | 0.00 | 0.00 | 744.00 |
November | 130.61 | 78.36 | 52.26 | 124.99 | 88.81 | 0.00 | 0.00 | 720.00 |
December | 129.52 | 91.98 | 37.53 | 123.62 | 116.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.61 | 63.02 | 63.59 | 121.85 | 63.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.73 | 13.96 | 37.53 | 76.37 | 2.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.70 | 118.36 | 79.82 | 201.66 | 131.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.12 | 36.59 | 52.53 | 37.17 | 268.32 | 0.00 | 0.00 | 744.00 |
February | 130.90 | 57.45 | 73.45 | 63.86 | 272.66 | 0.00 | 0.00 | 672.00 |
March | 194.45 | 90.12 | 104.33 | 140.02 | 175.18 | 0.00 | 0.00 | 744.00 |
April | 211.18 | 90.25 | 120.93 | 181.98 | 118.61 | 0.00 | 0.00 | 720.00 |
May | 246.67 | 93.75 | 152.91 | 250.18 | 64.27 | 0.00 | 0.00 | 744.00 |
June | 269.50 | 108.75 | 160.75 | 319.81 | 23.72 | 0.00 | 0.00 | 720.00 |
July | 252.15 | 94.74 | 157.41 | 332.20 | 5.39 | 0.00 | 0.00 | 744.00 |
August | 278.99 | 128.99 | 150.00 | 365.31 | 13.67 | 0.00 | 0.00 | 744.00 |
September | 198.51 | 86.67 | 111.84 | 222.83 | 41.77 | 0.00 | 0.00 | 720.00 |
October | 196.96 | 95.95 | 101.01 | 185.51 | 101.40 | 0.00 | 0.00 | 744.00 |
November | 92.75 | 27.10 | 65.66 | 43.28 | 179.15 | 0.00 | 0.00 | 720.00 |
December | 81.94 | 35.38 | 46.56 | 34.21 | 242.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.32 | 78.99 | 108.33 | 182.21 | 124.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.94 | 27.10 | 46.56 | 34.21 | 5.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.99 | 128.99 | 160.75 | 365.31 | 272.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.07 | 0.00 | 23.07 | 0.25 | 149.16 | 0.00 | 0.00 | 744.00 |
February | 31.57 | 0.00 | 31.57 | 1.15 | 154.24 | 0.00 | 0.00 | 672.00 |
March | 43.78 | 0.00 | 43.78 | 9.38 | 99.34 | 0.00 | 0.00 | 744.00 |
April | 52.69 | 0.21 | 52.47 | 25.15 | 64.81 | 0.00 | 0.00 | 720.00 |
May | 70.07 | 2.56 | 67.52 | 53.52 | 33.27 | 0.00 | 0.00 | 744.00 |
June | 73.92 | 3.92 | 70.00 | 80.23 | 12.10 | 0.00 | 0.00 | 720.00 |
July | 71.75 | 2.79 | 68.96 | 96.49 | 2.79 | 0.00 | 0.00 | 744.00 |
August | 63.45 | 0.84 | 62.62 | 86.59 | 6.99 | 0.00 | 0.00 | 744.00 |
September | 47.78 | 0.03 | 47.76 | 47.24 | 22.08 | 0.00 | 0.00 | 720.00 |
October | 41.32 | 0.00 | 41.32 | 24.82 | 54.54 | 0.00 | 0.00 | 744.00 |
November | 28.98 | 0.00 | 28.98 | 5.34 | 97.51 | 0.00 | 0.00 | 720.00 |
December | 20.12 | 0.00 | 20.12 | 0.25 | 134.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 0.87 | 46.60 | 36.11 | 68.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.12 | 0.00 | 20.12 | 0.25 | 2.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.92 | 3.92 | 70.00 | 96.49 | 154.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.12 | 36.59 | 52.53 | 39.36 | 264.82 | 0.00 | 0.00 | 744.00 |
February | 130.90 | 57.45 | 73.45 | 67.37 | 268.11 | 0.00 | 0.00 | 672.00 |
March | 194.45 | 90.12 | 104.33 | 144.39 | 172.51 | 0.00 | 0.00 | 744.00 |
April | 211.18 | 90.25 | 120.93 | 184.35 | 117.48 | 0.00 | 0.00 | 720.00 |
May | 246.67 | 93.75 | 152.91 | 251.03 | 63.94 | 0.00 | 0.00 | 744.00 |
June | 269.50 | 108.75 | 160.75 | 320.21 | 23.59 | 0.00 | 0.00 | 720.00 |
July | 252.15 | 94.74 | 157.41 | 332.69 | 5.32 | 0.00 | 0.00 | 744.00 |
August | 278.99 | 128.99 | 150.00 | 366.72 | 13.38 | 0.00 | 0.00 | 744.00 |
September | 198.51 | 86.67 | 111.84 | 225.28 | 40.89 | 0.00 | 0.00 | 720.00 |
October | 196.96 | 95.95 | 101.01 | 190.98 | 98.83 | 0.00 | 0.00 | 744.00 |
November | 92.75 | 27.10 | 65.66 | 46.99 | 175.40 | 0.00 | 0.00 | 720.00 |
December | 81.94 | 35.38 | 46.56 | 37.09 | 238.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.32 | 78.99 | 108.33 | 184.72 | 122.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.94 | 27.10 | 46.56 | 37.09 | 5.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.99 | 128.99 | 160.75 | 366.72 | 268.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.84 | 115.39 | 60.45 | 150.04 | 198.95 | 0.00 | 0.00 | 744.00 |
February | 232.79 | 154.75 | 78.04 | 195.57 | 200.58 | 0.00 | 0.00 | 672.00 |
March | 206.24 | 113.57 | 92.68 | 165.04 | 142.77 | 0.00 | 0.00 | 744.00 |
April | 164.09 | 66.38 | 97.72 | 120.23 | 97.00 | 0.00 | 0.00 | 720.00 |
May | 140.93 | 28.84 | 112.09 | 113.28 | 51.95 | 0.00 | 0.00 | 744.00 |
June | 133.06 | 20.48 | 112.59 | 140.03 | 18.05 | 0.00 | 0.00 | 720.00 |
July | 138.46 | 23.35 | 115.11 | 172.04 | 3.71 | 0.00 | 0.00 | 744.00 |
August | 185.45 | 68.39 | 117.06 | 214.49 | 10.11 | 0.00 | 0.00 | 744.00 |
September | 195.76 | 98.30 | 97.46 | 207.17 | 32.79 | 0.00 | 0.00 | 720.00 |
October | 276.74 | 173.59 | 103.15 | 292.80 | 79.64 | 0.00 | 0.00 | 744.00 |
November | 191.56 | 114.92 | 76.64 | 177.77 | 136.96 | 0.00 | 0.00 | 720.00 |
December | 189.95 | 134.90 | 55.04 | 175.07 | 178.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.68 | 92.42 | 93.26 | 176.98 | 95.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 133.06 | 20.48 | 55.04 | 113.28 | 3.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 276.74 | 173.59 | 117.06 | 292.80 | 200.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.46 | 0.00 | 161.46 | 0.10 | 1215.99 | 0.00 | 0.00 | 744.00 |
February | 220.95 | 0.00 | 220.95 | 2.27 | 1237.29 | 0.00 | 0.00 | 672.00 |
March | 306.47 | 0.01 | 306.47 | 45.87 | 823.35 | 0.00 | 0.00 | 744.00 |
April | 368.80 | 1.50 | 367.30 | 156.05 | 552.63 | 0.00 | 0.00 | 720.00 |
May | 490.49 | 17.90 | 472.59 | 356.20 | 292.26 | 0.00 | 0.00 | 744.00 |
June | 517.45 | 27.46 | 489.99 | 550.12 | 128.65 | 0.00 | 0.00 | 720.00 |
July | 502.25 | 19.55 | 482.70 | 650.21 | 49.91 | 0.00 | 0.00 | 744.00 |
August | 444.16 | 5.86 | 438.30 | 585.32 | 82.12 | 0.00 | 0.00 | 744.00 |
September | 334.47 | 0.19 | 334.28 | 323.24 | 212.47 | 0.00 | 0.00 | 720.00 |
October | 289.22 | 0.00 | 289.22 | 161.08 | 461.91 | 0.00 | 0.00 | 744.00 |
November | 202.86 | 0.00 | 202.86 | 23.95 | 834.01 | 0.00 | 0.00 | 720.00 |
December | 140.84 | 0.00 | 140.84 | 0.30 | 1118.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 332.26 | 6.08 | 326.19 | 239.55 | 580.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.84 | 0.00 | 140.84 | 0.10 | 49.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 517.45 | 27.46 | 489.99 | 650.21 | 1237.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.46 | 0.00 | 161.46 | 0.03 | 1253.84 | 0.00 | 0.00 | 744.00 |
February | 220.95 | 0.00 | 220.95 | 1.45 | 1274.07 | 0.00 | 0.00 | 672.00 |
March | 306.47 | 0.01 | 306.47 | 40.22 | 851.69 | 0.00 | 0.00 | 744.00 |
April | 368.80 | 1.50 | 367.30 | 145.16 | 573.72 | 0.00 | 0.00 | 720.00 |
May | 490.49 | 17.90 | 472.59 | 339.59 | 305.37 | 0.00 | 0.00 | 744.00 |
June | 517.45 | 27.46 | 489.99 | 533.47 | 138.11 | 0.00 | 0.00 | 720.00 |
July | 502.25 | 19.55 | 482.70 | 634.42 | 56.70 | 0.00 | 0.00 | 744.00 |
August | 444.16 | 5.86 | 438.30 | 570.44 | 89.08 | 0.00 | 0.00 | 744.00 |
September | 334.47 | 0.19 | 334.28 | 309.99 | 226.84 | 0.00 | 0.00 | 720.00 |
October | 289.22 | 0.00 | 289.22 | 151.04 | 481.27 | 0.00 | 0.00 | 744.00 |
November | 202.86 | 0.00 | 202.86 | 20.63 | 864.87 | 0.00 | 0.00 | 720.00 |
December | 140.84 | 0.00 | 140.84 | 0.18 | 1154.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 332.26 | 6.08 | 326.19 | 230.50 | 602.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.84 | 0.00 | 140.84 | 0.03 | 56.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 517.45 | 27.46 | 489.99 | 634.42 | 1274.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.07 | 0.00 | 23.07 | 0.47 | 154.81 | 0.00 | 0.00 | 744.00 |
February | 31.57 | 0.00 | 31.57 | 1.45 | 158.52 | 0.00 | 0.00 | 672.00 |
March | 43.78 | 0.00 | 43.78 | 11.33 | 102.81 | 0.00 | 0.00 | 744.00 |
April | 52.69 | 0.21 | 52.47 | 32.99 | 68.98 | 0.00 | 0.00 | 720.00 |
May | 70.07 | 2.56 | 67.52 | 69.06 | 37.05 | 0.00 | 0.00 | 744.00 |
June | 73.92 | 3.92 | 70.00 | 101.27 | 15.08 | 0.00 | 0.00 | 720.00 |
July | 71.75 | 2.79 | 68.96 | 119.48 | 4.83 | 0.00 | 0.00 | 744.00 |
August | 63.45 | 0.84 | 62.62 | 108.42 | 8.64 | 0.00 | 0.00 | 744.00 |
September | 47.78 | 0.03 | 47.76 | 64.05 | 23.66 | 0.00 | 0.00 | 720.00 |
October | 41.32 | 0.00 | 41.32 | 33.75 | 55.02 | 0.00 | 0.00 | 744.00 |
November | 28.98 | 0.00 | 28.98 | 6.92 | 102.93 | 0.00 | 0.00 | 720.00 |
December | 20.12 | 0.00 | 20.12 | 0.40 | 140.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 0.87 | 46.60 | 46.10 | 72.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.12 | 0.00 | 20.12 | 0.40 | 4.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.92 | 3.92 | 70.00 | 119.48 | 158.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.47 | 71.72 | 107.76 | 73.86 | 541.12 | 0.00 | 0.00 | 744.00 |
February | 278.62 | 129.75 | 148.87 | 145.81 | 530.93 | 0.00 | 0.00 | 672.00 |
March | 357.79 | 152.06 | 205.73 | 265.88 | 366.74 | 0.00 | 0.00 | 744.00 |
April | 428.32 | 188.01 | 240.31 | 404.29 | 247.88 | 0.00 | 0.00 | 720.00 |
May | 517.04 | 206.02 | 311.02 | 588.69 | 139.48 | 0.00 | 0.00 | 744.00 |
June | 480.10 | 173.87 | 306.23 | 642.56 | 57.86 | 0.00 | 0.00 | 720.00 |
July | 481.57 | 173.35 | 308.23 | 723.38 | 18.96 | 0.00 | 0.00 | 744.00 |
August | 543.30 | 245.11 | 298.19 | 796.06 | 32.91 | 0.00 | 0.00 | 744.00 |
September | 406.46 | 183.12 | 223.33 | 523.47 | 87.49 | 0.00 | 0.00 | 720.00 |
October | 367.18 | 166.21 | 200.97 | 382.42 | 199.38 | 0.00 | 0.00 | 744.00 |
November | 227.43 | 87.40 | 140.02 | 144.49 | 358.23 | 0.00 | 0.00 | 720.00 |
December | 177.82 | 83.92 | 93.90 | 83.18 | 483.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 371.01 | 155.22 | 215.79 | 399.58 | 253.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 177.82 | 71.72 | 93.90 | 73.86 | 18.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 543.30 | 245.11 | 311.02 | 796.06 | 541.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.90 | 78.68 | 41.22 | 109.49 | 135.62 | 0.00 | 0.00 | 744.00 |
February | 158.73 | 105.51 | 53.21 | 142.56 | 134.37 | 0.00 | 0.00 | 672.00 |
March | 140.63 | 77.43 | 63.19 | 121.03 | 97.84 | 0.00 | 0.00 | 744.00 |
April | 111.89 | 45.26 | 66.63 | 91.78 | 69.24 | 0.00 | 0.00 | 720.00 |
May | 96.09 | 19.66 | 76.43 | 91.15 | 39.08 | 0.00 | 0.00 | 744.00 |
June | 90.73 | 13.96 | 76.77 | 113.16 | 16.08 | 0.00 | 0.00 | 720.00 |
July | 94.41 | 15.92 | 78.49 | 136.90 | 5.11 | 0.00 | 0.00 | 744.00 |
August | 126.45 | 46.63 | 79.82 | 165.88 | 8.90 | 0.00 | 0.00 | 744.00 |
September | 133.48 | 67.02 | 66.45 | 159.46 | 23.79 | 0.00 | 0.00 | 720.00 |
October | 188.70 | 118.36 | 70.33 | 215.86 | 53.86 | 0.00 | 0.00 | 744.00 |
November | 130.61 | 78.36 | 52.26 | 130.95 | 93.07 | 0.00 | 0.00 | 720.00 |
December | 129.52 | 91.98 | 37.53 | 127.61 | 120.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.61 | 63.02 | 63.59 | 133.86 | 66.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.73 | 13.96 | 37.53 | 91.15 | 5.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.70 | 118.36 | 79.82 | 215.86 | 135.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.21 | 0.00 | 29.21 | 0.06 | 202.60 | 0.00 | 0.00 | 744.00 |
February | 39.98 | 0.00 | 39.98 | 0.77 | 207.39 | 0.00 | 0.00 | 672.00 |
March | 55.45 | 0.00 | 55.45 | 10.21 | 131.46 | 0.00 | 0.00 | 744.00 |
April | 66.73 | 0.27 | 66.45 | 32.36 | 85.00 | 0.00 | 0.00 | 720.00 |
May | 88.74 | 3.24 | 85.50 | 71.23 | 43.24 | 0.00 | 0.00 | 744.00 |
June | 93.62 | 4.97 | 88.65 | 104.49 | 17.28 | 0.00 | 0.00 | 720.00 |
July | 90.87 | 3.54 | 87.33 | 121.22 | 5.56 | 0.00 | 0.00 | 744.00 |
August | 80.36 | 1.06 | 79.30 | 108.31 | 11.25 | 0.00 | 0.00 | 744.00 |
September | 60.51 | 0.03 | 60.48 | 61.45 | 29.94 | 0.00 | 0.00 | 720.00 |
October | 52.33 | 0.00 | 52.33 | 31.39 | 71.61 | 0.00 | 0.00 | 744.00 |
November | 36.70 | 0.00 | 36.70 | 5.54 | 133.08 | 0.00 | 0.00 | 720.00 |
December | 25.48 | 0.00 | 25.48 | 0.11 | 184.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.11 | 1.10 | 59.02 | 45.90 | 92.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.48 | 0.00 | 25.48 | 0.06 | 5.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.62 | 4.97 | 88.65 | 121.22 | 207.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.14 | 0.00 | 26.14 | 0.05 | 181.26 | 0.00 | 0.00 | 744.00 |
February | 35.77 | 0.00 | 35.77 | 0.68 | 185.56 | 0.00 | 0.00 | 672.00 |
March | 49.61 | 0.00 | 49.61 | 9.14 | 117.61 | 0.00 | 0.00 | 744.00 |
April | 59.70 | 0.24 | 59.46 | 28.95 | 76.05 | 0.00 | 0.00 | 720.00 |
May | 79.40 | 2.90 | 76.50 | 63.73 | 38.69 | 0.00 | 0.00 | 744.00 |
June | 83.76 | 4.45 | 79.32 | 93.49 | 15.46 | 0.00 | 0.00 | 720.00 |
July | 81.30 | 3.16 | 78.14 | 108.46 | 4.97 | 0.00 | 0.00 | 744.00 |
August | 71.90 | 0.95 | 70.95 | 96.90 | 10.06 | 0.00 | 0.00 | 744.00 |
September | 54.14 | 0.03 | 54.11 | 54.98 | 26.78 | 0.00 | 0.00 | 720.00 |
October | 46.82 | 0.00 | 46.82 | 28.08 | 64.07 | 0.00 | 0.00 | 744.00 |
November | 32.84 | 0.00 | 32.84 | 4.96 | 119.07 | 0.00 | 0.00 | 720.00 |
December | 22.80 | 0.00 | 22.80 | 0.10 | 164.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 0.98 | 52.80 | 41.07 | 83.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.80 | 0.00 | 22.80 | 0.05 | 4.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 83.76 | 4.45 | 79.32 | 108.46 | 185.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 447.61 | 293.73 | 153.88 | 391.81 | 511.79 | 0.00 | 0.00 | 744.00 |
February | 592.58 | 393.92 | 198.66 | 512.48 | 509.35 | 0.00 | 0.00 | 672.00 |
March | 525.01 | 289.09 | 235.92 | 431.08 | 363.80 | 0.00 | 0.00 | 744.00 |
April | 417.71 | 168.97 | 248.74 | 314.88 | 249.70 | 0.00 | 0.00 | 720.00 |
May | 358.74 | 73.40 | 285.34 | 296.29 | 136.22 | 0.00 | 0.00 | 744.00 |
June | 338.72 | 52.13 | 286.59 | 357.01 | 54.44 | 0.00 | 0.00 | 720.00 |
July | 352.46 | 59.44 | 293.02 | 426.26 | 16.90 | 0.00 | 0.00 | 744.00 |
August | 472.08 | 174.09 | 297.99 | 536.11 | 34.17 | 0.00 | 0.00 | 744.00 |
September | 498.31 | 250.22 | 248.09 | 536.49 | 87.69 | 0.00 | 0.00 | 720.00 |
October | 704.46 | 441.88 | 262.58 | 763.38 | 200.77 | 0.00 | 0.00 | 744.00 |
November | 487.62 | 292.53 | 195.09 | 465.22 | 346.83 | 0.00 | 0.00 | 720.00 |
December | 483.53 | 343.41 | 140.12 | 457.76 | 456.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 472.67 | 235.26 | 237.40 | 457.37 | 245.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 338.72 | 52.13 | 140.12 | 296.29 | 16.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 704.46 | 441.88 | 297.99 | 763.38 | 511.79 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162619E+10 | 0.106714E+10 | 0.559054E+09 | 0.144657E+10 | 0.170520E+10 |
February | 0.194451E+10 | 0.129262E+10 | 0.651898E+09 | 0.170098E+10 | 0.154455E+10 |
March | 0.190736E+10 | 0.105026E+10 | 0.857099E+09 | 0.157182E+10 | 0.121988E+10 |
April | 0.146859E+10 | 0.594063E+09 | 0.874529E+09 | 0.110541E+10 | 0.810538E+09 |
May | 0.130332E+10 | 0.266668E+09 | 0.103665E+10 | 0.108252E+10 | 0.455852E+09 |
June | 0.119089E+10 | 0.183270E+09 | 0.100762E+10 | 0.125428E+10 | 0.172927E+09 |
July | 0.128048E+10 | 0.215929E+09 | 0.106455E+10 | 0.153505E+10 | 52503381.77 |
August | 0.171508E+10 | 0.632490E+09 | 0.108259E+10 | 0.189585E+10 | 0.124624E+09 |
September | 0.175199E+10 | 0.879741E+09 | 0.872245E+09 | 0.184956E+10 | 0.305216E+09 |
October | 0.255933E+10 | 0.160538E+10 | 0.953957E+09 | 0.272755E+10 | 0.728503E+09 |
November | 0.171439E+10 | 0.102849E+10 | 0.685893E+09 | 0.164121E+10 | 0.113952E+10 |
December | 0.175666E+10 | 0.124760E+10 | 0.509057E+09 | 0.167353E+10 | 0.153338E+10 |
Annual Sum or Average | 0.202188E+11 | 0.100636E+11 | 0.101551E+11 | 0.194843E+11 | 0.979269E+10 |
Minimum of Months | 0.119089E+10 | 0.183270E+09 | 0.509057E+09 | 0.108252E+10 | 52503381.77 |
Maximum of Months | 0.255933E+10 | 0.160538E+10 | 0.108259E+10 | 0.272755E+10 | 0.170520E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.457924E+10 | 0.300499E+10 | 0.157426E+10 | 0.402779E+10 | 0.492473E+10 |
February | 0.547562E+10 | 0.363992E+10 | 0.183570E+10 | 0.473451E+10 | 0.446151E+10 |
March | 0.537100E+10 | 0.295746E+10 | 0.241353E+10 | 0.436726E+10 | 0.362649E+10 |
April | 0.413546E+10 | 0.167284E+10 | 0.246262E+10 | 0.304871E+10 | 0.246604E+10 |
May | 0.367006E+10 | 0.750920E+09 | 0.291914E+10 | 0.295718E+10 | 0.144470E+10 |
June | 0.335345E+10 | 0.516075E+09 | 0.283738E+10 | 0.344680E+10 | 0.597573E+09 |
July | 0.360574E+10 | 0.608043E+09 | 0.299770E+10 | 0.423173E+10 | 0.219807E+09 |
August | 0.482956E+10 | 0.178105E+10 | 0.304851E+10 | 0.527203E+10 | 0.430101E+09 |
September | 0.493348E+10 | 0.247729E+10 | 0.245619E+10 | 0.514469E+10 | 0.100219E+10 |
October | 0.720691E+10 | 0.452063E+10 | 0.268628E+10 | 0.759891E+10 | 0.225872E+10 |
November | 0.482760E+10 | 0.289617E+10 | 0.193143E+10 | 0.455096E+10 | 0.339224E+10 |
December | 0.494664E+10 | 0.351317E+10 | 0.143347E+10 | 0.465676E+10 | 0.447699E+10 |
Annual Sum or Average | 0.569348E+11 | 0.283386E+11 | 0.285962E+11 | 0.540373E+11 | 0.293011E+11 |
Minimum of Months | 0.335345E+10 | 0.516075E+09 | 0.143347E+10 | 0.295718E+10 | 0.219807E+09 |
Maximum of Months | 0.720691E+10 | 0.452063E+10 | 0.304851E+10 | 0.759891E+10 | 0.492473E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.594870E+10 | 0.390365E+10 | 0.204505E+10 | 0.531137E+10 | 0.671149E+10 |
February | 0.711314E+10 | 0.472846E+10 | 0.238468E+10 | 0.625923E+10 | 0.604478E+10 |
March | 0.697723E+10 | 0.384192E+10 | 0.313532E+10 | 0.578591E+10 | 0.492428E+10 |
April | 0.537220E+10 | 0.217312E+10 | 0.319908E+10 | 0.403933E+10 | 0.336463E+10 |
May | 0.476761E+10 | 0.975488E+09 | 0.379212E+10 | 0.393466E+10 | 0.195514E+10 |
June | 0.435633E+10 | 0.670411E+09 | 0.368592E+10 | 0.462063E+10 | 0.785513E+09 |
July | 0.468407E+10 | 0.789882E+09 | 0.389418E+10 | 0.570326E+10 | 0.273665E+09 |
August | 0.627388E+10 | 0.231369E+10 | 0.396019E+10 | 0.711076E+10 | 0.534429E+09 |
September | 0.640887E+10 | 0.321815E+10 | 0.319072E+10 | 0.688331E+10 | 0.129849E+10 |
October | 0.936219E+10 | 0.587256E+10 | 0.348963E+10 | 0.101267E+11 | 0.296026E+10 |
November | 0.627133E+10 | 0.376229E+10 | 0.250904E+10 | 0.600804E+10 | 0.461856E+10 |
December | 0.642597E+10 | 0.456381E+10 | 0.186216E+10 | 0.614259E+10 | 0.610435E+10 |
Annual Sum or Average | 0.739615E+11 | 0.368134E+11 | 0.371481E+11 | 0.719258E+11 | 0.395756E+11 |
Minimum of Months | 0.435633E+10 | 0.670411E+09 | 0.186216E+10 | 0.393466E+10 | 0.273665E+09 |
Maximum of Months | 0.936219E+10 | 0.587256E+10 | 0.396019E+10 | 0.101267E+11 | 0.671149E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320870E+09 | 0.210561E+09 | 0.110309E+09 | 0.285035E+09 | 0.351243E+09 |
February | 0.383680E+09 | 0.255051E+09 | 0.128629E+09 | 0.335243E+09 | 0.319163E+09 |
March | 0.376349E+09 | 0.207231E+09 | 0.169118E+09 | 0.309468E+09 | 0.254065E+09 |
April | 0.289774E+09 | 0.117217E+09 | 0.172557E+09 | 0.216286E+09 | 0.169054E+09 |
May | 0.257163E+09 | 52617425.58 | 0.204546E+09 | 0.207706E+09 | 95283686.55 |
June | 0.234979E+09 | 36161720.47 | 0.198817E+09 | 0.244961E+09 | 33269688.07 |
July | 0.252657E+09 | 42605912.80 | 0.210051E+09 | 0.310769E+09 | 7569779.07 |
August | 0.338410E+09 | 0.124799E+09 | 0.213611E+09 | 0.388452E+09 | 19607021.33 |
September | 0.345692E+09 | 0.173585E+09 | 0.172106E+09 | 0.368978E+09 | 57489751.28 |
October | 0.504993E+09 | 0.316763E+09 | 0.188229E+09 | 0.543019E+09 | 0.142025E+09 |
November | 0.338273E+09 | 0.202937E+09 | 0.135336E+09 | 0.324778E+09 | 0.231577E+09 |
December | 0.346614E+09 | 0.246170E+09 | 0.100444E+09 | 0.331509E+09 | 0.313338E+09 |
Annual Sum or Average | 0.398945E+10 | 0.198570E+10 | 0.200375E+10 | 0.386620E+10 | 0.199368E+10 |
Minimum of Months | 0.234979E+09 | 36161720.47 | 0.100444E+09 | 0.207706E+09 | 7569779.07 |
Maximum of Months | 0.504993E+09 | 0.316763E+09 | 0.213611E+09 | 0.543019E+09 | 0.351243E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238500E+09 | 97925523.83 | 0.140574E+09 | 99314617.80 | 0.720936E+09 |
February | 0.316408E+09 | 0.138864E+09 | 0.177545E+09 | 0.155037E+09 | 0.660331E+09 |
March | 0.520380E+09 | 0.241180E+09 | 0.279200E+09 | 0.377947E+09 | 0.470088E+09 |
April | 0.546919E+09 | 0.233732E+09 | 0.313187E+09 | 0.476189E+09 | 0.307882E+09 |
May | 0.660131E+09 | 0.250900E+09 | 0.409231E+09 | 0.678370E+09 | 0.171055E+09 |
June | 0.697972E+09 | 0.281637E+09 | 0.416334E+09 | 0.837849E+09 | 60354203.07 |
July | 0.674794E+09 | 0.253543E+09 | 0.421251E+09 | 0.898603E+09 | 13951693.54 |
August | 0.746637E+09 | 0.345207E+09 | 0.401429E+09 | 0.986057E+09 | 36358602.10 |
September | 0.514123E+09 | 0.224471E+09 | 0.289652E+09 | 0.583574E+09 | 0.107456E+09 |
October | 0.527097E+09 | 0.256769E+09 | 0.270327E+09 | 0.501431E+09 | 0.271665E+09 |
November | 0.240219E+09 | 70180947.51 | 0.170039E+09 | 0.112377E+09 | 0.467145E+09 |
December | 0.219280E+09 | 94672763.34 | 0.124607E+09 | 91176519.59 | 0.653077E+09 |
Annual Sum or Average | 0.590246E+10 | 0.248908E+10 | 0.341338E+10 | 0.579793E+10 | 0.394030E+10 |
Minimum of Months | 0.219280E+09 | 70180947.51 | 0.124607E+09 | 91176519.59 | 13951693.54 |
Maximum of Months | 0.746637E+09 | 0.345207E+09 | 0.421251E+09 | 0.986057E+09 | 0.720936E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61730780.89 | 0.00 | 61730780.89 | 562386.74 | 0.401239E+09 |
February | 76300861.09 | 0.00 | 76300861.09 | 2653683.23 | 0.373787E+09 |
March | 0.117174E+09 | 2329.53 | 0.117172E+09 | 25197919.79 | 0.266663E+09 |
April | 0.136455E+09 | 556193.62 | 0.135898E+09 | 66520163.00 | 0.168244E+09 |
May | 0.187529E+09 | 6843609.71 | 0.180685E+09 | 0.147216E+09 | 88353290.38 |
June | 0.191453E+09 | 10160814.05 | 0.181293E+09 | 0.212016E+09 | 30745689.18 |
July | 0.192023E+09 | 7474350.78 | 0.184549E+09 | 0.262935E+09 | 7165836.98 |
August | 0.169816E+09 | 2241668.73 | 0.167574E+09 | 0.235488E+09 | 18587356.20 |
September | 0.123752E+09 | 70321.09 | 0.123681E+09 | 0.125322E+09 | 56723789.51 |
October | 0.110579E+09 | 0.00 | 0.110579E+09 | 67647184.39 | 0.146346E+09 |
November | 75058300.98 | 0.00 | 75058300.98 | 13617512.24 | 0.255115E+09 |
December | 53845644.44 | 0.00 | 53845644.44 | 566626.96 | 0.362463E+09 |
Annual Sum or Average | 0.149572E+10 | 27349287.52 | 0.146837E+10 | 0.115974E+10 | 0.217543E+10 |
Minimum of Months | 53845644.44 | 0.00 | 53845644.44 | 562386.74 | 7165836.98 |
Maximum of Months | 0.192023E+09 | 10160814.05 | 0.184549E+09 | 0.262935E+09 | 0.401239E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238500E+09 | 97925523.83 | 0.140574E+09 | 0.105016E+09 | 0.711210E+09 |
February | 0.316408E+09 | 0.138864E+09 | 0.177545E+09 | 0.163061E+09 | 0.648954E+09 |
March | 0.520380E+09 | 0.241180E+09 | 0.279200E+09 | 0.388631E+09 | 0.463307E+09 |
April | 0.546919E+09 | 0.233732E+09 | 0.313187E+09 | 0.482085E+09 | 0.305112E+09 |
May | 0.660131E+09 | 0.250900E+09 | 0.409231E+09 | 0.680777E+09 | 0.170195E+09 |
June | 0.697972E+09 | 0.281637E+09 | 0.416334E+09 | 0.839020E+09 | 59984059.46 |
July | 0.674794E+09 | 0.253543E+09 | 0.421251E+09 | 0.900017E+09 | 13771615.42 |
August | 0.746637E+09 | 0.345207E+09 | 0.401429E+09 | 0.989909E+09 | 35585942.67 |
September | 0.514123E+09 | 0.224471E+09 | 0.289652E+09 | 0.590185E+09 | 0.105237E+09 |
October | 0.527097E+09 | 0.256769E+09 | 0.270327E+09 | 0.515332E+09 | 0.265378E+09 |
November | 0.240219E+09 | 70180947.51 | 0.170039E+09 | 0.121232E+09 | 0.457924E+09 |
December | 0.219280E+09 | 94672763.34 | 0.124607E+09 | 98230599.61 | 0.641002E+09 |
Annual Sum or Average | 0.590246E+10 | 0.248908E+10 | 0.341338E+10 | 0.587350E+10 | 0.387766E+10 |
Minimum of Months | 0.219280E+09 | 70180947.51 | 0.124607E+09 | 98230599.61 | 13771615.42 |
Maximum of Months | 0.746637E+09 | 0.345207E+09 | 0.421251E+09 | 0.989909E+09 | 0.711210E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256645E+09 | 0.168415E+09 | 88229912.29 | 0.222711E+09 | 0.292263E+09 |
February | 0.306883E+09 | 0.204001E+09 | 0.102882E+09 | 0.249728E+09 | 0.306635E+09 |
March | 0.301019E+09 | 0.165752E+09 | 0.135267E+09 | 0.226598E+09 | 0.271402E+09 |
April | 0.231773E+09 | 93755041.77 | 0.138018E+09 | 0.147461E+09 | 0.199009E+09 |
May | 0.205690E+09 | 42085570.78 | 0.163604E+09 | 0.130924E+09 | 0.132066E+09 |
June | 0.187945E+09 | 28923624.25 | 0.159022E+09 | 0.156334E+09 | 68837556.83 |
July | 0.202085E+09 | 34077953.05 | 0.168007E+09 | 0.200884E+09 | 40285761.35 |
August | 0.270674E+09 | 99819567.05 | 0.170855E+09 | 0.265746E+09 | 52491886.78 |
September | 0.276498E+09 | 0.138841E+09 | 0.137658E+09 | 0.261509E+09 | 99179036.18 |
October | 0.403914E+09 | 0.253360E+09 | 0.150554E+09 | 0.402235E+09 | 0.178958E+09 |
November | 0.270565E+09 | 0.162317E+09 | 0.108248E+09 | 0.233713E+09 | 0.256332E+09 |
December | 0.277236E+09 | 0.196897E+09 | 80339342.33 | 0.244974E+09 | 0.312396E+09 |
Annual Sum or Average | 0.319093E+10 | 0.158824E+10 | 0.160268E+10 | 0.274282E+10 | 0.220986E+10 |
Minimum of Months | 0.187945E+09 | 28923624.25 | 80339342.33 | 0.130924E+09 | 40285761.35 |
Maximum of Months | 0.403914E+09 | 0.253360E+09 | 0.170855E+09 | 0.402235E+09 | 0.312396E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49391170.92 | 0.00 | 49391170.92 | 185943.44 | 0.337327E+09 |
February | 61048780.16 | 0.00 | 61048780.16 | 1573438.84 | 0.310996E+09 |
March | 93751937.54 | 1863.87 | 93750073.66 | 19033109.83 | 0.220106E+09 |
April | 0.109178E+09 | 445013.88 | 0.108733E+09 | 53880507.28 | 0.138196E+09 |
May | 0.150043E+09 | 5475613.50 | 0.144567E+09 | 0.121834E+09 | 70759550.51 |
June | 0.153183E+09 | 8129728.74 | 0.145053E+09 | 0.177340E+09 | 23171007.57 |
July | 0.153639E+09 | 5980273.24 | 0.147659E+09 | 0.219638E+09 | 4753742.71 |
August | 0.135871E+09 | 1793572.70 | 0.134077E+09 | 0.198605E+09 | 13344486.18 |
September | 99014499.97 | 56264.33 | 98958235.64 | 0.105001E+09 | 44479747.24 |
October | 88474560.91 | 0.00 | 88474560.91 | 56213368.87 | 0.117541E+09 |
November | 60054600.30 | 0.00 | 60054600.30 | 9867386.36 | 0.215553E+09 |
December | 43082225.59 | 0.00 | 43082225.59 | 258333.93 | 0.305908E+09 |
Annual Sum or Average | 0.119673E+10 | 21882330.26 | 0.117485E+10 | 0.963429E+09 | 0.180214E+10 |
Minimum of Months | 43082225.59 | 0.00 | 43082225.59 | 185943.44 | 4753742.71 |
Maximum of Months | 0.153639E+09 | 8129728.74 | 0.147659E+09 | 0.219638E+09 | 0.337327E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240168E+09 | 95969669.36 | 0.144198E+09 | 90649458.28 | 0.708221E+09 |
February | 0.336766E+09 | 0.156828E+09 | 0.179938E+09 | 0.163577E+09 | 0.636449E+09 |
March | 0.478787E+09 | 0.203481E+09 | 0.275306E+09 | 0.328609E+09 | 0.472156E+09 |
April | 0.554692E+09 | 0.243479E+09 | 0.311214E+09 | 0.474816E+09 | 0.297781E+09 |
May | 0.691897E+09 | 0.275693E+09 | 0.416204E+09 | 0.712487E+09 | 0.165081E+09 |
June | 0.621750E+09 | 0.225167E+09 | 0.396583E+09 | 0.739730E+09 | 57329714.29 |
July | 0.644437E+09 | 0.231970E+09 | 0.412467E+09 | 0.862449E+09 | 13129279.26 |
August | 0.727047E+09 | 0.328005E+09 | 0.399042E+09 | 0.959233E+09 | 33841456.70 |
September | 0.526373E+09 | 0.237150E+09 | 0.289223E+09 | 0.591979E+09 | 0.102301E+09 |
October | 0.491360E+09 | 0.222425E+09 | 0.268935E+09 | 0.447905E+09 | 0.263454E+09 |
November | 0.294523E+09 | 0.113190E+09 | 0.181333E+09 | 0.163868E+09 | 0.452241E+09 |
December | 0.237958E+09 | 0.112299E+09 | 0.125659E+09 | 0.101407E+09 | 0.637179E+09 |
Annual Sum or Average | 0.584576E+10 | 0.244566E+10 | 0.340010E+10 | 0.563671E+10 | 0.383916E+10 |
Minimum of Months | 0.237958E+09 | 95969669.36 | 0.125659E+09 | 90649458.28 | 13129279.26 |
Maximum of Months | 0.727047E+09 | 0.328005E+09 | 0.416204E+09 | 0.959233E+09 | 0.708221E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320870E+09 | 0.210561E+09 | 0.110309E+09 | 0.284203E+09 | 0.350821E+09 |
February | 0.383680E+09 | 0.255051E+09 | 0.128629E+09 | 0.333486E+09 | 0.318507E+09 |
March | 0.376349E+09 | 0.207231E+09 | 0.169118E+09 | 0.307285E+09 | 0.252067E+09 |
April | 0.289774E+09 | 0.117217E+09 | 0.172557E+09 | 0.213711E+09 | 0.168141E+09 |
May | 0.257163E+09 | 52617425.58 | 0.204546E+09 | 0.204788E+09 | 94168738.55 |
June | 0.234979E+09 | 36161720.47 | 0.198817E+09 | 0.244826E+09 | 32262591.33 |
July | 0.252657E+09 | 42605912.80 | 0.210051E+09 | 0.310497E+09 | 7207780.72 |
August | 0.338410E+09 | 0.124799E+09 | 0.213611E+09 | 0.387496E+09 | 18965409.79 |
September | 0.345692E+09 | 0.173585E+09 | 0.172106E+09 | 0.367550E+09 | 56841371.28 |
October | 0.504993E+09 | 0.316763E+09 | 0.188229E+09 | 0.541497E+09 | 0.140682E+09 |
November | 0.338273E+09 | 0.202937E+09 | 0.135336E+09 | 0.322949E+09 | 0.231812E+09 |
December | 0.346614E+09 | 0.246170E+09 | 0.100444E+09 | 0.330416E+09 | 0.313016E+09 |
Annual Sum or Average | 0.398945E+10 | 0.198570E+10 | 0.200375E+10 | 0.384870E+10 | 0.198449E+10 |
Minimum of Months | 0.234979E+09 | 36161720.47 | 0.100444E+09 | 0.204788E+09 | 7207780.72 |
Maximum of Months | 0.504993E+09 | 0.316763E+09 | 0.213611E+09 | 0.541497E+09 | 0.350821E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61730780.89 | 0.00 | 61730780.89 | 450713.54 | 0.401441E+09 |
February | 76300861.09 | 0.00 | 76300861.09 | 2356819.90 | 0.374350E+09 |
March | 0.117174E+09 | 2329.53 | 0.117172E+09 | 23701680.17 | 0.265268E+09 |
April | 0.136455E+09 | 556193.62 | 0.135898E+09 | 64146392.17 | 0.167781E+09 |
May | 0.187529E+09 | 6843609.71 | 0.180685E+09 | 0.144309E+09 | 87423241.79 |
June | 0.191453E+09 | 10160814.05 | 0.181293E+09 | 0.212033E+09 | 29857579.64 |
July | 0.192023E+09 | 7474350.78 | 0.184549E+09 | 0.262686E+09 | 6810179.53 |
August | 0.169816E+09 | 2241668.73 | 0.167574E+09 | 0.234464E+09 | 17961540.01 |
September | 0.123752E+09 | 70321.09 | 0.123681E+09 | 0.123640E+09 | 56269996.94 |
October | 0.110579E+09 | 0.00 | 0.110579E+09 | 65849533.83 | 0.144847E+09 |
November | 75058300.98 | 0.00 | 75058300.98 | 12706609.28 | 0.256303E+09 |
December | 53845644.44 | 0.00 | 53845644.44 | 445950.21 | 0.362806E+09 |
Annual Sum or Average | 0.149572E+10 | 27349287.52 | 0.146837E+10 | 0.114679E+10 | 0.217112E+10 |
Minimum of Months | 53845644.44 | 0.00 | 53845644.44 | 445950.21 | 6810179.53 |
Maximum of Months | 0.192023E+09 | 10160814.05 | 0.184549E+09 | 0.262686E+09 | 0.401441E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240168E+09 | 95969669.36 | 0.144198E+09 | 93069001.69 | 0.695243E+09 |
February | 0.336766E+09 | 0.156828E+09 | 0.179938E+09 | 0.167727E+09 | 0.620912E+09 |
March | 0.478787E+09 | 0.203481E+09 | 0.275306E+09 | 0.337248E+09 | 0.463127E+09 |
April | 0.554692E+09 | 0.243479E+09 | 0.311214E+09 | 0.480087E+09 | 0.294722E+09 |
May | 0.691897E+09 | 0.275693E+09 | 0.416204E+09 | 0.714639E+09 | 0.164160E+09 |
June | 0.621750E+09 | 0.225167E+09 | 0.396583E+09 | 0.740928E+09 | 56985083.47 |
July | 0.644437E+09 | 0.231970E+09 | 0.412467E+09 | 0.863890E+09 | 12977924.39 |
August | 0.727047E+09 | 0.328005E+09 | 0.399042E+09 | 0.962916E+09 | 33088216.79 |
September | 0.526373E+09 | 0.237150E+09 | 0.289223E+09 | 0.597934E+09 | 0.100048E+09 |
October | 0.491360E+09 | 0.222425E+09 | 0.268935E+09 | 0.460553E+09 | 0.256192E+09 |
November | 0.294523E+09 | 0.113190E+09 | 0.181333E+09 | 0.170733E+09 | 0.441432E+09 |
December | 0.237958E+09 | 0.112299E+09 | 0.125659E+09 | 0.104407E+09 | 0.621014E+09 |
Annual Sum or Average | 0.584576E+10 | 0.244566E+10 | 0.340010E+10 | 0.569413E+10 | 0.375990E+10 |
Minimum of Months | 0.237958E+09 | 95969669.36 | 0.125659E+09 | 93069001.69 | 12977924.39 |
Maximum of Months | 0.727047E+09 | 0.328005E+09 | 0.416204E+09 | 0.962916E+09 | 0.695243E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78178139.00 | 0.00 | 78178139.00 | 276513.31 | 0.531055E+09 |
February | 96630226.25 | 0.00 | 96630226.25 | 2560574.94 | 0.490696E+09 |
March | 0.148394E+09 | 2950.20 | 0.148391E+09 | 31756791.42 | 0.341464E+09 |
April | 0.172811E+09 | 704384.12 | 0.172107E+09 | 91478958.34 | 0.211386E+09 |
May | 0.237493E+09 | 8666999.89 | 0.228826E+09 | 0.205647E+09 | 0.106848E+09 |
June | 0.242464E+09 | 12868029.88 | 0.229596E+09 | 0.295108E+09 | 33693691.33 |
July | 0.243185E+09 | 9465793.66 | 0.233720E+09 | 0.362126E+09 | 6455474.91 |
August | 0.215061E+09 | 2838932.01 | 0.212222E+09 | 0.324858E+09 | 20048130.89 |
September | 0.156724E+09 | 89057.23 | 0.156635E+09 | 0.175542E+09 | 66479364.86 |
October | 0.140041E+09 | 0.00 | 0.140041E+09 | 93849112.10 | 0.180960E+09 |
November | 95056602.27 | 0.00 | 95056602.27 | 16977493.44 | 0.334582E+09 |
December | 68192111.22 | 0.00 | 68192111.22 | 425179.52 | 0.481198E+09 |
Annual Sum or Average | 0.189423E+10 | 34636147.00 | 0.185959E+10 | 0.160061E+10 | 0.280486E+10 |
Minimum of Months | 68192111.22 | 0.00 | 68192111.22 | 276513.31 | 6455474.91 |
Maximum of Months | 0.243185E+09 | 12868029.88 | 0.233720E+09 | 0.362126E+09 | 0.531055E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 28819699.14 | 0.00 | 28819699.14 | 101934.26 | 0.195769E+09 |
February | 35621902.54 | 0.00 | 35621902.54 | 943933.95 | 0.180891E+09 |
March | 54704162.36 | 1087.57 | 54703074.79 | 11706868.26 | 0.125878E+09 |
April | 63705355.58 | 259665.15 | 63445690.43 | 33722931.89 | 77925638.66 |
May | 87549904.44 | 3195015.03 | 84354889.40 | 75809939.09 | 39388438.94 |
June | 89382171.01 | 4743688.64 | 84638482.37 | 0.108789E+09 | 12420889.77 |
July | 89648234.72 | 3489483.49 | 86158751.23 | 0.133495E+09 | 2379755.35 |
August | 79280545.61 | 1046547.89 | 78233997.72 | 0.119756E+09 | 7390571.17 |
September | 57774862.31 | 32830.18 | 57742032.13 | 64712083.57 | 24507046.58 |
October | 51624818.34 | 0.00 | 51624818.34 | 34596668.70 | 66709351.09 |
November | 35041799.58 | 0.00 | 35041799.58 | 6258607.07 | 0.123341E+09 |
December | 25138435.81 | 0.00 | 25138435.81 | 156738.78 | 0.177389E+09 |
Annual Sum or Average | 0.698292E+09 | 12768317.95 | 0.685524E+09 | 0.590049E+09 | 0.103399E+10 |
Minimum of Months | 25138435.81 | 0.00 | 25138435.81 | 101934.26 | 2379755.35 |
Maximum of Months | 89648234.72 | 4743688.64 | 86158751.23 | 0.133495E+09 | 0.195769E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149717E+09 | 98246975.53 | 51469885.86 | 0.133127E+09 | 0.168075E+09 |
February | 0.179024E+09 | 0.119006E+09 | 60017623.81 | 0.157207E+09 | 0.151281E+09 |
March | 0.175603E+09 | 96693315.15 | 78909658.94 | 0.146908E+09 | 0.118191E+09 |
April | 0.135207E+09 | 54693030.66 | 80514420.21 | 0.104947E+09 | 77354613.58 |
May | 0.119991E+09 | 24551078.75 | 95440189.24 | 0.104310E+09 | 41809302.57 |
June | 0.109640E+09 | 16872913.05 | 92767131.95 | 0.124287E+09 | 13130046.05 |
July | 0.117889E+09 | 19879747.22 | 98008828.48 | 0.156241E+09 | 2441330.61 |
August | 0.157901E+09 | 58230837.92 | 99670033.13 | 0.191961E+09 | 7555868.59 |
September | 0.161298E+09 | 80994270.27 | 80304143.70 | 0.179948E+09 | 24193067.76 |
October | 0.235628E+09 | 0.147801E+09 | 87827048.88 | 0.260237E+09 | 63412407.47 |
November | 0.157837E+09 | 94689424.36 | 63147392.96 | 0.153277E+09 | 0.109280E+09 |
December | 0.161729E+09 | 0.114862E+09 | 46866835.43 | 0.155412E+09 | 0.149594E+09 |
Annual Sum or Average | 0.186146E+10 | 0.926520E+09 | 0.934943E+09 | 0.186786E+10 | 0.926318E+09 |
Minimum of Months | 0.109640E+09 | 16872913.05 | 46866835.43 | 0.104310E+09 | 2441330.61 |
Maximum of Months | 0.235628E+09 | 0.147801E+09 | 99670033.13 | 0.260237E+09 | 0.168075E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406362E+09 | 0.266662E+09 | 0.139700E+09 | 0.361335E+09 | 0.456190E+09 |
February | 0.485907E+09 | 0.323007E+09 | 0.162900E+09 | 0.426693E+09 | 0.410608E+09 |
March | 0.476622E+09 | 0.262445E+09 | 0.214177E+09 | 0.398739E+09 | 0.320794E+09 |
April | 0.366981E+09 | 0.148448E+09 | 0.218533E+09 | 0.284848E+09 | 0.209956E+09 |
May | 0.325681E+09 | 66636649.53 | 0.259044E+09 | 0.283118E+09 | 0.113479E+09 |
June | 0.297586E+09 | 45796537.30 | 0.251789E+09 | 0.337339E+09 | 35637630.67 |
July | 0.319974E+09 | 53957700.28 | 0.266016E+09 | 0.424071E+09 | 6626270.64 |
August | 0.428575E+09 | 0.158050E+09 | 0.270525E+09 | 0.521022E+09 | 20508172.86 |
September | 0.437797E+09 | 0.219835E+09 | 0.217962E+09 | 0.488416E+09 | 65664934.48 |
October | 0.639541E+09 | 0.401161E+09 | 0.238381E+09 | 0.706336E+09 | 0.172114E+09 |
November | 0.428401E+09 | 0.257006E+09 | 0.171395E+09 | 0.416024E+09 | 0.296609E+09 |
December | 0.438965E+09 | 0.311759E+09 | 0.127206E+09 | 0.421820E+09 | 0.406028E+09 |
Annual Sum or Average | 0.505239E+10 | 0.251476E+10 | 0.253763E+10 | 0.506976E+10 | 0.251422E+10 |
Minimum of Months | 0.297586E+09 | 45796537.30 | 0.127206E+09 | 0.283118E+09 | 6626270.64 |
Maximum of Months | 0.639541E+09 | 0.401161E+09 | 0.270525E+09 | 0.706336E+09 | 0.456190E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321134E+09 | 0.210734E+09 | 0.110400E+09 | 0.284440E+09 | 0.350083E+09 |
February | 0.383995E+09 | 0.255261E+09 | 0.128734E+09 | 0.334407E+09 | 0.318552E+09 |
March | 0.376658E+09 | 0.207401E+09 | 0.169256E+09 | 0.308351E+09 | 0.253968E+09 |
April | 0.290012E+09 | 0.117313E+09 | 0.172699E+09 | 0.214975E+09 | 0.169221E+09 |
May | 0.257374E+09 | 52660590.00 | 0.204713E+09 | 0.204547E+09 | 96258286.12 |
June | 0.235171E+09 | 36191385.54 | 0.198980E+09 | 0.241496E+09 | 33994416.19 |
July | 0.252864E+09 | 42640864.33 | 0.210223E+09 | 0.307218E+09 | 7826110.27 |
August | 0.338688E+09 | 0.124902E+09 | 0.213786E+09 | 0.385731E+09 | 19762984.57 |
September | 0.345975E+09 | 0.173728E+09 | 0.172248E+09 | 0.366165E+09 | 58029514.21 |
October | 0.505407E+09 | 0.317023E+09 | 0.188384E+09 | 0.540113E+09 | 0.142148E+09 |
November | 0.338550E+09 | 0.203103E+09 | 0.135447E+09 | 0.323967E+09 | 0.230194E+09 |
December | 0.346898E+09 | 0.246372E+09 | 0.100527E+09 | 0.331110E+09 | 0.311702E+09 |
Annual Sum or Average | 0.399273E+10 | 0.198733E+10 | 0.200540E+10 | 0.384252E+10 | 0.199174E+10 |
Minimum of Months | 0.235171E+09 | 36191385.54 | 0.100527E+09 | 0.204547E+09 | 7826110.27 |
Maximum of Months | 0.505407E+09 | 0.317023E+09 | 0.213786E+09 | 0.540113E+09 | 0.350083E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238695E+09 | 98005856.50 | 0.140689E+09 | 99565026.69 | 0.718657E+09 |
February | 0.316668E+09 | 0.138978E+09 | 0.177690E+09 | 0.154483E+09 | 0.659622E+09 |
March | 0.520807E+09 | 0.241378E+09 | 0.279429E+09 | 0.375040E+09 | 0.469196E+09 |
April | 0.547367E+09 | 0.233924E+09 | 0.313443E+09 | 0.471680E+09 | 0.307448E+09 |
May | 0.660673E+09 | 0.251106E+09 | 0.409566E+09 | 0.670081E+09 | 0.172140E+09 |
June | 0.698544E+09 | 0.281869E+09 | 0.416676E+09 | 0.828946E+09 | 61481995.92 |
July | 0.675347E+09 | 0.253751E+09 | 0.421596E+09 | 0.889768E+09 | 14430462.84 |
August | 0.747249E+09 | 0.345491E+09 | 0.401759E+09 | 0.978442E+09 | 36608176.71 |
September | 0.514545E+09 | 0.224655E+09 | 0.289890E+09 | 0.577565E+09 | 0.108267E+09 |
October | 0.527529E+09 | 0.256980E+09 | 0.270549E+09 | 0.496877E+09 | 0.271594E+09 |
November | 0.240417E+09 | 70238520.06 | 0.170178E+09 | 0.112176E+09 | 0.464352E+09 |
December | 0.219460E+09 | 94750427.63 | 0.124709E+09 | 91625970.88 | 0.649578E+09 |
Annual Sum or Average | 0.590730E+10 | 0.249113E+10 | 0.341618E+10 | 0.574625E+10 | 0.393338E+10 |
Minimum of Months | 0.219460E+09 | 70238520.06 | 0.124709E+09 | 91625970.88 | 14430462.84 |
Maximum of Months | 0.747249E+09 | 0.345491E+09 | 0.421596E+09 | 0.978442E+09 | 0.718657E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61781421.40 | 0.00 | 61781421.40 | 671063.80 | 0.399520E+09 |
February | 76363454.09 | 0.00 | 76363454.09 | 2772735.38 | 0.373130E+09 |
March | 0.117271E+09 | 2331.44 | 0.117268E+09 | 25122318.46 | 0.266061E+09 |
April | 0.136567E+09 | 556649.89 | 0.136010E+09 | 65183791.72 | 0.167982E+09 |
May | 0.187683E+09 | 6849223.83 | 0.180833E+09 | 0.143343E+09 | 89103868.25 |
June | 0.191611E+09 | 10169149.42 | 0.181441E+09 | 0.207951E+09 | 31371516.54 |
July | 0.192181E+09 | 7480482.32 | 0.184700E+09 | 0.258440E+09 | 7484579.64 |
August | 0.169955E+09 | 2243507.67 | 0.167712E+09 | 0.231918E+09 | 18726313.42 |
September | 0.123853E+09 | 70378.78 | 0.123783E+09 | 0.122444E+09 | 57224164.74 |
October | 0.110669E+09 | 0.00 | 0.110669E+09 | 66472668.56 | 0.146090E+09 |
November | 75119874.64 | 0.00 | 75119874.64 | 13843637.08 | 0.252747E+09 |
December | 53889816.42 | 0.00 | 53889816.42 | 670539.90 | 0.359592E+09 |
Annual Sum or Average | 0.149694E+10 | 27371723.36 | 0.146957E+10 | 0.113883E+10 | 0.216903E+10 |
Minimum of Months | 53889816.42 | 0.00 | 53889816.42 | 670539.90 | 7484579.64 |
Maximum of Months | 0.192181E+09 | 10169149.42 | 0.184700E+09 | 0.258440E+09 | 0.399520E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238695E+09 | 98005856.50 | 0.140689E+09 | 0.105433E+09 | 0.709292E+09 |
February | 0.316668E+09 | 0.138978E+09 | 0.177690E+09 | 0.162985E+09 | 0.648617E+09 |
March | 0.520807E+09 | 0.241378E+09 | 0.279429E+09 | 0.386727E+09 | 0.462058E+09 |
April | 0.547367E+09 | 0.233924E+09 | 0.313443E+09 | 0.477836E+09 | 0.304496E+09 |
May | 0.660673E+09 | 0.251106E+09 | 0.409566E+09 | 0.672360E+09 | 0.171263E+09 |
June | 0.698544E+09 | 0.281869E+09 | 0.416676E+09 | 0.829997E+09 | 61137222.53 |
July | 0.675347E+09 | 0.253751E+09 | 0.421596E+09 | 0.891078E+09 | 14259802.60 |
August | 0.747249E+09 | 0.345491E+09 | 0.401759E+09 | 0.982214E+09 | 35834924.40 |
September | 0.514545E+09 | 0.224655E+09 | 0.289890E+09 | 0.583933E+09 | 0.105991E+09 |
October | 0.527529E+09 | 0.256980E+09 | 0.270549E+09 | 0.511514E+09 | 0.264718E+09 |
November | 0.240417E+09 | 70238520.06 | 0.170178E+09 | 0.121804E+09 | 0.454642E+09 |
December | 0.219460E+09 | 94750427.63 | 0.124709E+09 | 99328587.01 | 0.637634E+09 |
Annual Sum or Average | 0.590730E+10 | 0.249113E+10 | 0.341618E+10 | 0.582521E+10 | 0.386994E+10 |
Minimum of Months | 0.219460E+09 | 70238520.06 | 0.124709E+09 | 99328587.01 | 14259802.60 |
Maximum of Months | 0.747249E+09 | 0.345491E+09 | 0.421596E+09 | 0.982214E+09 | 0.709292E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.470973E+09 | 0.309061E+09 | 0.161912E+09 | 0.401865E+09 | 0.532869E+09 |
February | 0.563165E+09 | 0.374364E+09 | 0.188801E+09 | 0.473118E+09 | 0.485240E+09 |
March | 0.552405E+09 | 0.304174E+09 | 0.248231E+09 | 0.442039E+09 | 0.382398E+09 |
April | 0.425330E+09 | 0.172051E+09 | 0.253279E+09 | 0.311624E+09 | 0.251425E+09 |
May | 0.377464E+09 | 77231809.09 | 0.300232E+09 | 0.303403E+09 | 0.139151E+09 |
June | 0.344901E+09 | 53078140.20 | 0.291823E+09 | 0.362965E+09 | 46796588.47 |
July | 0.370849E+09 | 62536919.79 | 0.308312E+09 | 0.460793E+09 | 9932019.38 |
August | 0.496718E+09 | 0.183180E+09 | 0.313538E+09 | 0.574479E+09 | 27078734.61 |
September | 0.507406E+09 | 0.254789E+09 | 0.252618E+09 | 0.536982E+09 | 84998897.28 |
October | 0.741228E+09 | 0.464945E+09 | 0.276283E+09 | 0.784242E+09 | 0.213295E+09 |
November | 0.496517E+09 | 0.297870E+09 | 0.198647E+09 | 0.460781E+09 | 0.355003E+09 |
December | 0.508760E+09 | 0.361328E+09 | 0.147432E+09 | 0.468913E+09 | 0.476932E+09 |
Annual Sum or Average | 0.585572E+10 | 0.291461E+10 | 0.294111E+10 | 0.558120E+10 | 0.300512E+10 |
Minimum of Months | 0.344901E+09 | 53078140.20 | 0.147432E+09 | 0.303403E+09 | 9932019.38 |
Maximum of Months | 0.741228E+09 | 0.464945E+09 | 0.313538E+09 | 0.784242E+09 | 0.532869E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432454E+09 | 0.00 | 0.432454E+09 | 275707.62 | 0.325690E+10 |
February | 0.534524E+09 | 0.00 | 0.534524E+09 | 5494014.34 | 0.299325E+10 |
March | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.122860E+09 | 0.220527E+10 |
April | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.404469E+09 | 0.143242E+10 |
May | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.954052E+09 | 0.782800E+09 |
June | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.142591E+10 | 0.333465E+09 |
July | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.174153E+10 | 0.133680E+09 |
August | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.156773E+10 | 0.219940E+09 |
September | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.837836E+09 | 0.550719E+09 |
October | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.431427E+09 | 0.123719E+10 |
November | 0.525819E+09 | 0.00 | 0.525819E+09 | 62091317.45 | 0.216174E+10 |
December | 0.377214E+09 | 0.00 | 0.377214E+09 | 809932.51 | 0.299620E+10 |
Annual Sum or Average | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.755448E+10 | 0.183036E+11 |
Minimum of Months | 0.377214E+09 | 0.00 | 0.377214E+09 | 275707.62 | 0.133680E+09 |
Maximum of Months | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.174153E+10 | 0.325690E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432454E+09 | 0.00 | 0.432454E+09 | 88199.28 | 0.335829E+10 |
February | 0.534524E+09 | 0.00 | 0.534524E+09 | 3509217.56 | 0.308223E+10 |
March | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.107727E+09 | 0.228118E+10 |
April | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.376267E+09 | 0.148708E+10 |
May | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.909569E+09 | 0.817916E+09 |
June | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.138276E+10 | 0.357974E+09 |
July | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.169924E+10 | 0.151861E+09 |
August | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.152787E+10 | 0.238603E+09 |
September | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.803489E+09 | 0.587973E+09 |
October | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.404540E+09 | 0.128904E+10 |
November | 0.525819E+09 | 0.00 | 0.525819E+09 | 53485653.14 | 0.224174E+10 |
December | 0.377214E+09 | 0.00 | 0.377214E+09 | 478982.24 | 0.309219E+10 |
Annual Sum or Average | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.726902E+10 | 0.189861E+11 |
Minimum of Months | 0.377214E+09 | 0.00 | 0.377214E+09 | 88199.28 | 0.151861E+09 |
Maximum of Months | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.169924E+10 | 0.335829E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61781421.40 | 0.00 | 61781421.40 | 1257279.28 | 0.414639E+09 |
February | 76363454.09 | 0.00 | 76363454.09 | 3505366.34 | 0.383488E+09 |
March | 0.117271E+09 | 2331.44 | 0.117268E+09 | 30344537.68 | 0.275373E+09 |
April | 0.136567E+09 | 556649.89 | 0.136010E+09 | 85517101.13 | 0.178790E+09 |
May | 0.187683E+09 | 6849223.83 | 0.180833E+09 | 0.184975E+09 | 99239380.14 |
June | 0.191611E+09 | 10169149.42 | 0.181441E+09 | 0.262496E+09 | 39084866.73 |
July | 0.192181E+09 | 7480482.32 | 0.184700E+09 | 0.320017E+09 | 12934024.67 |
August | 0.169955E+09 | 2243507.67 | 0.167712E+09 | 0.290395E+09 | 23128003.01 |
September | 0.123853E+09 | 70378.78 | 0.123783E+09 | 0.166017E+09 | 61336447.66 |
October | 0.110669E+09 | 0.00 | 0.110669E+09 | 90390765.90 | 0.147375E+09 |
November | 75119874.64 | 0.00 | 75119874.64 | 17924688.00 | 0.266791E+09 |
December | 53889816.42 | 0.00 | 53889816.42 | 1082521.40 | 0.375911E+09 |
Annual Sum or Average | 0.149694E+10 | 27371723.36 | 0.146957E+10 | 0.145392E+10 | 0.227809E+10 |
Minimum of Months | 53889816.42 | 0.00 | 53889816.42 | 1082521.40 | 12934024.67 |
Maximum of Months | 0.192181E+09 | 10169149.42 | 0.184700E+09 | 0.320017E+09 | 0.414639E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480696E+09 | 0.192083E+09 | 0.288612E+09 | 0.197821E+09 | 0.144933E+10 |
February | 0.674037E+09 | 0.313891E+09 | 0.360146E+09 | 0.352754E+09 | 0.128442E+10 |
March | 0.958292E+09 | 0.407267E+09 | 0.551025E+09 | 0.712134E+09 | 0.982284E+09 |
April | 0.111022E+10 | 0.487322E+09 | 0.622894E+09 | 0.104791E+10 | 0.642506E+09 |
May | 0.138483E+10 | 0.551800E+09 | 0.833031E+09 | 0.157675E+10 | 0.373583E+09 |
June | 0.124443E+10 | 0.450671E+09 | 0.793760E+09 | 0.166552E+10 | 0.149978E+09 |
July | 0.128984E+10 | 0.464288E+09 | 0.825552E+09 | 0.193750E+10 | 50790782.77 |
August | 0.145518E+10 | 0.656501E+09 | 0.798682E+09 | 0.213218E+10 | 88147301.92 |
September | 0.105353E+10 | 0.474654E+09 | 0.578880E+09 | 0.135684E+10 | 0.226779E+09 |
October | 0.983456E+09 | 0.445182E+09 | 0.538274E+09 | 0.102428E+10 | 0.534011E+09 |
November | 0.589487E+09 | 0.226550E+09 | 0.362937E+09 | 0.374515E+09 | 0.928521E+09 |
December | 0.476272E+09 | 0.224766E+09 | 0.251506E+09 | 0.222799E+09 | 0.129506E+10 |
Annual Sum or Average | 0.117003E+11 | 0.489498E+10 | 0.680530E+10 | 0.126010E+11 | 0.800542E+10 |
Minimum of Months | 0.476272E+09 | 0.192083E+09 | 0.251506E+09 | 0.197821E+09 | 50790782.77 |
Maximum of Months | 0.145518E+10 | 0.656501E+09 | 0.833031E+09 | 0.213218E+10 | 0.144933E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321134E+09 | 0.210734E+09 | 0.110400E+09 | 0.293249E+09 | 0.363255E+09 |
February | 0.383995E+09 | 0.255261E+09 | 0.128734E+09 | 0.344889E+09 | 0.325064E+09 |
March | 0.376658E+09 | 0.207401E+09 | 0.169256E+09 | 0.324157E+09 | 0.262060E+09 |
April | 0.290012E+09 | 0.117313E+09 | 0.172699E+09 | 0.237891E+09 | 0.179479E+09 |
May | 0.257374E+09 | 52660590.00 | 0.204713E+09 | 0.244128E+09 | 0.104667E+09 |
June | 0.235171E+09 | 36191385.54 | 0.198980E+09 | 0.293319E+09 | 41690515.47 |
July | 0.252864E+09 | 42640864.33 | 0.210223E+09 | 0.366683E+09 | 13685163.37 |
August | 0.338688E+09 | 0.124902E+09 | 0.213786E+09 | 0.444295E+09 | 23840064.79 |
September | 0.345975E+09 | 0.173728E+09 | 0.172248E+09 | 0.413320E+09 | 61657596.67 |
October | 0.505407E+09 | 0.317023E+09 | 0.188384E+09 | 0.578167E+09 | 0.144251E+09 |
November | 0.338550E+09 | 0.203103E+09 | 0.135447E+09 | 0.339422E+09 | 0.241244E+09 |
December | 0.346898E+09 | 0.246372E+09 | 0.100527E+09 | 0.341779E+09 | 0.323671E+09 |
Annual Sum or Average | 0.399273E+10 | 0.198733E+10 | 0.200540E+10 | 0.422130E+10 | 0.208456E+10 |
Minimum of Months | 0.235171E+09 | 36191385.54 | 0.100527E+09 | 0.237891E+09 | 13685163.37 |
Maximum of Months | 0.505407E+09 | 0.317023E+09 | 0.213786E+09 | 0.578167E+09 | 0.363255E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78242272.01 | 0.00 | 78242272.01 | 157822.05 | 0.542641E+09 |
February | 96709496.33 | 0.00 | 96709496.33 | 1851984.52 | 0.501728E+09 |
March | 0.148516E+09 | 2952.62 | 0.148513E+09 | 27357134.14 | 0.352090E+09 |
April | 0.172953E+09 | 704961.96 | 0.172248E+09 | 83879163.15 | 0.220324E+09 |
May | 0.237688E+09 | 8674109.82 | 0.229014E+09 | 0.190777E+09 | 0.115820E+09 |
June | 0.242663E+09 | 12878586.10 | 0.229784E+09 | 0.270842E+09 | 44780070.59 |
July | 0.243385E+09 | 9473558.87 | 0.233911E+09 | 0.324678E+09 | 14888844.00 |
August | 0.215238E+09 | 2841260.91 | 0.212397E+09 | 0.290092E+09 | 30128729.66 |
September | 0.156852E+09 | 89130.29 | 0.156763E+09 | 0.159273E+09 | 77595433.27 |
October | 0.140156E+09 | 0.00 | 0.140156E+09 | 84074306.88 | 0.191797E+09 |
November | 95134581.43 | 0.00 | 95134581.43 | 14358679.58 | 0.344949E+09 |
December | 68248052.24 | 0.00 | 68248052.24 | 307108.21 | 0.492850E+09 |
Annual Sum or Average | 0.189578E+10 | 34664560.57 | 0.186112E+10 | 0.144765E+10 | 0.292959E+10 |
Minimum of Months | 68248052.24 | 0.00 | 68248052.24 | 157822.05 | 14888844.00 |
Maximum of Months | 0.243385E+09 | 12878586.10 | 0.233911E+09 | 0.324678E+09 | 0.542641E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70003657.22 | 0.00 | 70003657.22 | 141203.99 | 0.485500E+09 |
February | 86526352.80 | 0.00 | 86526352.80 | 1656977.57 | 0.448898E+09 |
March | 0.132878E+09 | 2641.72 | 0.132875E+09 | 24476531.57 | 0.315016E+09 |
April | 0.154742E+09 | 630732.14 | 0.154111E+09 | 75047005.09 | 0.197125E+09 |
May | 0.212661E+09 | 7760758.92 | 0.204900E+09 | 0.170689E+09 | 0.103624E+09 |
June | 0.217111E+09 | 11522519.78 | 0.205589E+09 | 0.242323E+09 | 40064898.82 |
July | 0.217757E+09 | 8476029.02 | 0.209281E+09 | 0.290490E+09 | 13321105.14 |
August | 0.192574E+09 | 2542086.90 | 0.190032E+09 | 0.259546E+09 | 26956288.58 |
September | 0.140336E+09 | 79745.20 | 0.140257E+09 | 0.142502E+09 | 69424928.15 |
October | 0.125398E+09 | 0.00 | 0.125398E+09 | 75221600.92 | 0.171601E+09 |
November | 85117270.47 | 0.00 | 85117270.47 | 12846765.03 | 0.308627E+09 |
December | 61061790.93 | 0.00 | 61061790.93 | 274770.88 | 0.440942E+09 |
Annual Sum or Average | 0.169617E+10 | 31014513.69 | 0.166515E+10 | 0.129522E+10 | 0.262110E+10 |
Minimum of Months | 61061790.93 | 0.00 | 61061790.93 | 141203.99 | 13321105.14 |
Maximum of Months | 0.217757E+09 | 11522519.78 | 0.209281E+09 | 0.290490E+09 | 0.485500E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119889E+10 | 0.786732E+09 | 0.412155E+09 | 0.104942E+10 | 0.137078E+10 |
February | 0.143357E+10 | 0.952964E+09 | 0.480603E+09 | 0.123979E+10 | 0.123221E+10 |
March | 0.140618E+10 | 0.774291E+09 | 0.631885E+09 | 0.115461E+10 | 0.974411E+09 |
April | 0.108270E+10 | 0.437965E+09 | 0.644735E+09 | 0.816167E+09 | 0.647229E+09 |
May | 0.960854E+09 | 0.196598E+09 | 0.764256E+09 | 0.793590E+09 | 0.364861E+09 |
June | 0.877965E+09 | 0.135113E+09 | 0.742851E+09 | 0.925381E+09 | 0.141096E+09 |
July | 0.944016E+09 | 0.159191E+09 | 0.784825E+09 | 0.114170E+10 | 45275839.69 |
August | 0.126442E+10 | 0.466295E+09 | 0.798128E+09 | 0.143592E+10 | 91520946.69 |
September | 0.129163E+10 | 0.648578E+09 | 0.643051E+09 | 0.139058E+10 | 0.227298E+09 |
October | 0.188683E+10 | 0.118354E+10 | 0.703293E+09 | 0.204464E+10 | 0.537750E+09 |
November | 0.126391E+10 | 0.758245E+09 | 0.505665E+09 | 0.120585E+10 | 0.898986E+09 |
December | 0.129508E+10 | 0.919780E+09 | 0.375296E+09 | 0.122607E+10 | 0.122159E+10 |
Annual Sum or Average | 0.149060E+11 | 0.741929E+10 | 0.748674E+10 | 0.144237E+11 | 0.775301E+10 |
Minimum of Months | 0.877965E+09 | 0.135113E+09 | 0.375296E+09 | 0.793590E+09 | 45275839.69 |
Maximum of Months | 0.188683E+10 | 0.118354E+10 | 0.798128E+09 | 0.204464E+10 | 0.137078E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 540.09 | 636.65 | 607.15 | 398.42 | 208.73 | 0.00 | 0.00 |
February | 703.12 | 638.45 | 803.78 | 534.32 | 269.47 | 0.00 | 0.00 |
March | 586.85 | 455.45 | 712.13 | 392.12 | 320.00 | 0.00 | 0.00 |
April | 426.47 | 312.71 | 566.59 | 229.19 | 337.40 | 0.00 | 0.00 |
May | 404.17 | 170.20 | 486.60 | 99.56 | 387.04 | 0.00 | 0.00 |
June | 483.90 | 66.72 | 459.45 | 70.71 | 388.74 | 0.00 | 0.00 |
July | 573.12 | 19.60 | 478.08 | 80.62 | 397.46 | 0.00 | 0.00 |
August | 707.83 | 46.53 | 640.34 | 236.14 | 404.19 | 0.00 | 0.00 |
September | 713.57 | 117.75 | 675.92 | 339.41 | 336.51 | 0.00 | 0.00 |
October | 1018.35 | 271.99 | 955.55 | 599.38 | 356.17 | 0.00 | 0.00 |
November | 633.18 | 439.63 | 661.41 | 396.80 | 264.62 | 0.00 | 0.00 |
December | 624.83 | 572.50 | 655.86 | 465.80 | 190.06 | 0.00 | 0.00 |
Annual Sum or Average | 617.84 | 310.52 | 641.13 | 319.12 | 322.02 | 0.00 | 0.00 |
Minimum of Months | 404.17 | 19.60 | 459.45 | 70.71 | 190.06 | 0.00 | 0.00 |
Maximum of Months | 1018.35 | 638.45 | 955.55 | 599.38 | 404.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1503.81 | 1838.68 | 1709.69 | 1121.93 | 587.76 | 0.00 | 0.00 |
February | 1957.05 | 1844.21 | 2263.40 | 1504.60 | 758.81 | 0.00 | 0.00 |
March | 1630.55 | 1353.98 | 2005.30 | 1104.19 | 901.11 | 0.00 | 0.00 |
April | 1176.20 | 951.40 | 1595.47 | 645.39 | 950.08 | 0.00 | 0.00 |
May | 1104.08 | 539.39 | 1370.24 | 280.36 | 1089.88 | 0.00 | 0.00 |
June | 1329.78 | 230.55 | 1293.77 | 199.10 | 1094.67 | 0.00 | 0.00 |
July | 1579.95 | 82.07 | 1346.23 | 227.02 | 1119.21 | 0.00 | 0.00 |
August | 1968.35 | 160.58 | 1803.15 | 664.97 | 1138.18 | 0.00 | 0.00 |
September | 1984.83 | 386.65 | 1903.35 | 955.75 | 947.60 | 0.00 | 0.00 |
October | 2837.11 | 843.31 | 2690.75 | 1687.81 | 1002.94 | 0.00 | 0.00 |
November | 1755.77 | 1308.74 | 1862.50 | 1117.35 | 745.15 | 0.00 | 0.00 |
December | 1738.63 | 1671.52 | 1846.86 | 1311.67 | 535.20 | 0.00 | 0.00 |
Annual Sum or Average | 1713.51 | 929.13 | 1805.39 | 898.61 | 906.78 | 0.00 | 0.00 |
Minimum of Months | 1104.08 | 82.07 | 1293.77 | 199.10 | 535.20 | 0.00 | 0.00 |
Maximum of Months | 2837.11 | 1844.21 | 2690.75 | 1687.81 | 1138.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1983.04 | 2505.78 | 2220.99 | 1457.45 | 763.54 | 0.00 | 0.00 |
February | 2587.31 | 2498.67 | 2940.29 | 1954.56 | 985.73 | 0.00 | 0.00 |
March | 2160.21 | 1838.51 | 2605.00 | 1434.41 | 1170.59 | 0.00 | 0.00 |
April | 1558.38 | 1298.08 | 2072.61 | 838.39 | 1234.21 | 0.00 | 0.00 |
May | 1469.03 | 729.96 | 1780.02 | 364.21 | 1415.82 | 0.00 | 0.00 |
June | 1782.65 | 303.05 | 1680.68 | 258.65 | 1422.04 | 0.00 | 0.00 |
July | 2129.35 | 102.17 | 1748.83 | 294.91 | 1453.92 | 0.00 | 0.00 |
August | 2654.85 | 199.53 | 2342.40 | 863.83 | 1478.57 | 0.00 | 0.00 |
September | 2655.60 | 500.96 | 2472.56 | 1241.57 | 1230.99 | 0.00 | 0.00 |
October | 3780.89 | 1105.24 | 3495.44 | 2192.56 | 1302.88 | 0.00 | 0.00 |
November | 2317.92 | 1781.85 | 2419.49 | 1451.50 | 967.99 | 0.00 | 0.00 |
December | 2293.38 | 2279.10 | 2399.18 | 1703.93 | 695.25 | 0.00 | 0.00 |
Annual Sum or Average | 2280.75 | 1254.93 | 2345.30 | 1167.35 | 1177.96 | 0.00 | 0.00 |
Minimum of Months | 1469.03 | 102.17 | 1680.68 | 258.65 | 695.25 | 0.00 | 0.00 |
Maximum of Months | 3780.89 | 2505.78 | 3495.44 | 2192.56 | 1478.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.82 | 383.63 | 208.84 | 115.18 | 93.67 | 0.00 | 0.00 |
February | 181.17 | 383.40 | 289.39 | 162.83 | 126.56 | 0.00 | 0.00 |
March | 250.14 | 263.85 | 334.80 | 167.42 | 167.38 | 0.00 | 0.00 |
April | 265.00 | 181.85 | 322.80 | 135.40 | 187.40 | 0.00 | 0.00 |
May | 329.51 | 98.13 | 342.48 | 113.32 | 229.16 | 0.00 | 0.00 |
June | 417.43 | 35.80 | 359.93 | 122.61 | 237.33 | 0.00 | 0.00 |
July | 451.51 | 8.02 | 346.27 | 110.57 | 235.70 | 0.00 | 0.00 |
August | 513.15 | 20.86 | 405.11 | 175.48 | 229.63 | 0.00 | 0.00 |
September | 367.15 | 63.29 | 331.72 | 153.57 | 178.15 | 0.00 | 0.00 |
October | 388.06 | 152.56 | 385.34 | 214.13 | 171.21 | 0.00 | 0.00 |
November | 160.09 | 261.01 | 223.18 | 105.37 | 117.81 | 0.00 | 0.00 |
December | 140.44 | 343.44 | 211.28 | 127.26 | 84.02 | 0.00 | 0.00 |
Annual Sum or Average | 300.14 | 181.86 | 313.67 | 141.89 | 171.78 | 0.00 | 0.00 |
Minimum of Months | 126.82 | 8.02 | 208.84 | 105.37 | 84.02 | 0.00 | 0.00 |
Maximum of Months | 513.15 | 383.63 | 405.11 | 214.13 | 237.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.37 | 409.29 | 112.09 | 36.56 | 75.53 | 0.00 | 0.00 |
February | 60.20 | 414.46 | 162.33 | 57.40 | 104.93 | 0.00 | 0.00 |
March | 148.06 | 266.09 | 238.04 | 90.05 | 147.99 | 0.00 | 0.00 |
April | 209.70 | 180.66 | 263.65 | 90.39 | 173.26 | 0.00 | 0.00 |
May | 308.39 | 95.78 | 316.48 | 96.23 | 220.25 | 0.00 | 0.00 |
June | 405.22 | 34.73 | 343.14 | 112.58 | 230.57 | 0.00 | 0.00 |
July | 434.12 | 7.74 | 323.63 | 97.45 | 226.18 | 0.00 | 0.00 |
August | 457.46 | 20.18 | 342.16 | 129.72 | 212.44 | 0.00 | 0.00 |
September | 275.76 | 62.20 | 246.09 | 86.63 | 159.47 | 0.00 | 0.00 |
October | 215.92 | 151.98 | 238.08 | 95.87 | 142.21 | 0.00 | 0.00 |
November | 49.00 | 272.06 | 121.63 | 27.08 | 94.56 | 0.00 | 0.00 |
December | 31.04 | 368.80 | 101.97 | 35.35 | 66.63 | 0.00 | 0.00 |
Annual Sum or Average | 220.15 | 189.07 | 234.59 | 79.80 | 154.80 | 0.00 | 0.00 |
Minimum of Months | 31.04 | 7.74 | 101.97 | 27.08 | 66.63 | 0.00 | 0.00 |
Maximum of Months | 457.46 | 414.46 | 343.14 | 129.72 | 230.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.15 | 109.12 | 95.82 | 62.88 | 32.94 | 0.00 | 0.00 |
February | 103.23 | 126.75 | 126.85 | 84.33 | 42.53 | 0.00 | 0.00 |
March | 84.60 | 101.33 | 112.39 | 61.88 | 50.50 | 0.00 | 0.00 |
April | 56.89 | 76.78 | 89.42 | 36.17 | 53.25 | 0.00 | 0.00 |
May | 48.88 | 49.31 | 76.80 | 15.71 | 61.08 | 0.00 | 0.00 |
June | 60.31 | 26.56 | 72.51 | 11.16 | 61.35 | 0.00 | 0.00 |
July | 75.00 | 15.04 | 75.45 | 12.72 | 62.73 | 0.00 | 0.00 |
August | 99.22 | 19.60 | 101.06 | 37.27 | 63.79 | 0.00 | 0.00 |
September | 100.89 | 38.26 | 106.67 | 53.57 | 53.11 | 0.00 | 0.00 |
October | 150.18 | 66.82 | 150.80 | 94.59 | 56.21 | 0.00 | 0.00 |
November | 90.17 | 98.89 | 104.38 | 62.62 | 41.76 | 0.00 | 0.00 |
December | 91.46 | 116.64 | 103.51 | 73.51 | 30.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.97 | 70.07 | 101.18 | 50.36 | 50.82 | 0.00 | 0.00 |
Minimum of Months | 48.88 | 15.04 | 72.51 | 11.16 | 30.00 | 0.00 | 0.00 |
Maximum of Months | 150.18 | 126.75 | 150.80 | 94.59 | 63.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.07 | 125.94 | 18.44 | 0.00 | 18.44 | 0.00 | 0.00 |
February | 0.65 | 128.55 | 25.24 | 0.00 | 25.24 | 0.00 | 0.00 |
March | 7.11 | 82.18 | 35.00 | 0.00 | 35.00 | 0.00 | 0.00 |
April | 20.79 | 53.32 | 42.12 | 0.17 | 41.95 | 0.00 | 0.00 |
May | 45.49 | 26.42 | 56.02 | 2.04 | 53.98 | 0.00 | 0.00 |
June | 68.42 | 8.94 | 59.10 | 3.14 | 55.96 | 0.00 | 0.00 |
July | 82.00 | 1.77 | 57.36 | 2.23 | 55.13 | 0.00 | 0.00 |
August | 74.15 | 4.98 | 50.73 | 0.67 | 50.06 | 0.00 | 0.00 |
September | 40.51 | 17.16 | 38.20 | 0.02 | 38.18 | 0.00 | 0.00 |
October | 20.99 | 43.88 | 33.03 | 0.00 | 33.03 | 0.00 | 0.00 |
November | 3.81 | 83.16 | 23.17 | 0.00 | 23.17 | 0.00 | 0.00 |
December | 0.10 | 114.21 | 16.09 | 0.00 | 16.09 | 0.00 | 0.00 |
Annual Sum or Average | 30.55 | 57.15 | 37.95 | 0.69 | 37.25 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 1.77 | 16.09 | 0.00 | 16.09 | 0.00 | 0.00 |
Maximum of Months | 82.00 | 128.55 | 59.10 | 3.14 | 55.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.24 | 380.69 | 209.47 | 114.45 | 95.02 | 0.00 | 0.00 |
February | 187.95 | 377.22 | 297.80 | 170.25 | 127.55 | 0.00 | 0.00 |
March | 232.72 | 265.70 | 319.27 | 153.34 | 165.93 | 0.00 | 0.00 |
April | 262.56 | 176.68 | 325.80 | 139.16 | 186.64 | 0.00 | 0.00 |
May | 340.63 | 94.95 | 354.34 | 122.58 | 231.76 | 0.00 | 0.00 |
June | 379.30 | 34.03 | 330.53 | 100.82 | 229.71 | 0.00 | 0.00 |
July | 437.85 | 7.51 | 334.94 | 102.52 | 232.42 | 0.00 | 0.00 |
August | 502.55 | 19.45 | 397.80 | 169.06 | 228.74 | 0.00 | 0.00 |
September | 369.40 | 60.60 | 336.44 | 158.46 | 177.98 | 0.00 | 0.00 |
October | 367.83 | 149.32 | 372.00 | 201.31 | 170.69 | 0.00 | 0.00 |
November | 182.16 | 258.26 | 244.13 | 121.96 | 122.17 | 0.00 | 0.00 |
December | 146.56 | 340.10 | 218.25 | 133.84 | 84.42 | 0.00 | 0.00 |
Annual Sum or Average | 295.40 | 179.28 | 311.87 | 140.52 | 171.36 | 0.00 | 0.00 |
Minimum of Months | 125.24 | 7.51 | 209.47 | 100.82 | 84.42 | 0.00 | 0.00 |
Maximum of Months | 502.55 | 380.69 | 397.80 | 201.31 | 232.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.39 | 401.93 | 112.72 | 35.83 | 76.89 | 0.00 | 0.00 |
February | 56.80 | 397.90 | 170.75 | 64.83 | 105.92 | 0.00 | 0.00 |
March | 129.06 | 266.25 | 222.51 | 75.97 | 146.53 | 0.00 | 0.00 |
April | 206.58 | 175.05 | 266.65 | 94.15 | 172.50 | 0.00 | 0.00 |
May | 319.94 | 93.18 | 328.34 | 105.49 | 222.85 | 0.00 | 0.00 |
June | 367.41 | 33.26 | 313.74 | 90.79 | 222.95 | 0.00 | 0.00 |
July | 420.60 | 7.37 | 312.30 | 89.40 | 222.90 | 0.00 | 0.00 |
August | 446.94 | 18.95 | 334.85 | 123.30 | 211.55 | 0.00 | 0.00 |
September | 277.32 | 59.24 | 250.82 | 91.52 | 159.30 | 0.00 | 0.00 |
October | 194.12 | 147.32 | 224.74 | 83.04 | 141.69 | 0.00 | 0.00 |
November | 65.08 | 263.50 | 142.59 | 43.67 | 98.92 | 0.00 | 0.00 |
December | 30.63 | 358.80 | 108.95 | 41.93 | 67.02 | 0.00 | 0.00 |
Annual Sum or Average | 212.91 | 184.06 | 232.80 | 78.42 | 154.38 | 0.00 | 0.00 |
Minimum of Months | 27.39 | 7.37 | 108.95 | 35.83 | 67.02 | 0.00 | 0.00 |
Maximum of Months | 446.94 | 401.93 | 334.85 | 123.30 | 222.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.67 | 477.35 | 247.56 | 136.24 | 111.32 | 0.00 | 0.00 |
February | 211.89 | 478.95 | 329.52 | 182.71 | 146.81 | 0.00 | 0.00 |
March | 215.85 | 334.28 | 319.34 | 134.09 | 185.25 | 0.00 | 0.00 |
April | 198.29 | 222.06 | 284.99 | 78.74 | 206.25 | 0.00 | 0.00 |
May | 249.08 | 111.92 | 287.75 | 38.47 | 249.28 | 0.00 | 0.00 |
June | 333.43 | 36.12 | 285.14 | 30.97 | 254.16 | 0.00 | 0.00 |
July | 401.63 | 6.60 | 287.74 | 32.40 | 255.34 | 0.00 | 0.00 |
August | 432.15 | 20.68 | 328.86 | 82.20 | 246.66 | 0.00 | 0.00 |
September | 350.44 | 69.66 | 313.89 | 116.11 | 197.78 | 0.00 | 0.00 |
October | 406.75 | 178.32 | 398.31 | 204.96 | 193.35 | 0.00 | 0.00 |
November | 215.91 | 320.57 | 276.36 | 135.69 | 140.68 | 0.00 | 0.00 |
December | 187.91 | 425.52 | 259.12 | 159.28 | 99.84 | 0.00 | 0.00 |
Annual Sum or Average | 280.70 | 222.08 | 301.45 | 110.63 | 190.82 | 0.00 | 0.00 |
Minimum of Months | 157.67 | 6.60 | 247.56 | 30.97 | 99.84 | 0.00 | 0.00 |
Maximum of Months | 432.15 | 478.95 | 398.31 | 204.96 | 255.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.84 | 382.49 | 209.02 | 115.27 | 93.75 | 0.00 | 0.00 |
February | 180.68 | 382.93 | 289.63 | 162.96 | 126.66 | 0.00 | 0.00 |
March | 248.59 | 263.44 | 335.08 | 167.55 | 167.52 | 0.00 | 0.00 |
April | 262.69 | 181.68 | 323.06 | 135.51 | 187.55 | 0.00 | 0.00 |
May | 325.13 | 98.79 | 342.76 | 113.41 | 229.35 | 0.00 | 0.00 |
June | 412.62 | 36.47 | 360.23 | 122.71 | 237.52 | 0.00 | 0.00 |
July | 446.88 | 8.29 | 346.55 | 110.66 | 235.89 | 0.00 | 0.00 |
August | 509.28 | 21.00 | 405.44 | 175.62 | 229.82 | 0.00 | 0.00 |
September | 363.72 | 63.79 | 331.99 | 153.70 | 178.29 | 0.00 | 0.00 |
October | 385.30 | 152.61 | 385.65 | 214.31 | 171.35 | 0.00 | 0.00 |
November | 159.86 | 259.55 | 223.37 | 105.46 | 117.91 | 0.00 | 0.00 |
December | 140.80 | 341.87 | 211.45 | 127.36 | 84.09 | 0.00 | 0.00 |
Annual Sum or Average | 297.79 | 181.62 | 313.93 | 142.01 | 171.92 | 0.00 | 0.00 |
Minimum of Months | 126.84 | 8.29 | 209.02 | 105.46 | 84.09 | 0.00 | 0.00 |
Maximum of Months | 509.28 | 382.93 | 405.44 | 214.31 | 237.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.69 | 408.06 | 112.19 | 36.59 | 75.59 | 0.00 | 0.00 |
February | 60.35 | 414.18 | 162.46 | 57.45 | 105.02 | 0.00 | 0.00 |
March | 147.27 | 265.35 | 238.23 | 90.12 | 148.11 | 0.00 | 0.00 |
April | 207.47 | 180.26 | 263.86 | 90.46 | 173.40 | 0.00 | 0.00 |
May | 303.75 | 96.41 | 316.74 | 96.31 | 220.43 | 0.00 | 0.00 |
June | 400.16 | 35.41 | 343.42 | 112.67 | 230.76 | 0.00 | 0.00 |
July | 429.10 | 8.04 | 323.90 | 97.53 | 226.37 | 0.00 | 0.00 |
August | 453.25 | 20.32 | 342.45 | 129.83 | 212.62 | 0.00 | 0.00 |
September | 272.20 | 62.65 | 246.30 | 86.70 | 159.60 | 0.00 | 0.00 |
October | 213.98 | 151.56 | 238.28 | 95.95 | 142.33 | 0.00 | 0.00 |
November | 49.37 | 269.95 | 121.73 | 27.10 | 94.64 | 0.00 | 0.00 |
December | 31.69 | 366.68 | 102.06 | 35.38 | 66.68 | 0.00 | 0.00 |
Annual Sum or Average | 217.97 | 188.64 | 234.79 | 79.86 | 154.93 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 8.04 | 102.06 | 27.10 | 66.68 | 0.00 | 0.00 |
Maximum of Months | 453.25 | 414.18 | 343.42 | 129.83 | 230.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.04 | 198.95 | 175.84 | 115.39 | 60.45 | 0.00 | 0.00 |
February | 195.57 | 200.58 | 232.79 | 154.75 | 78.04 | 0.00 | 0.00 |
March | 165.04 | 142.77 | 206.24 | 113.57 | 92.68 | 0.00 | 0.00 |
April | 120.23 | 97.00 | 164.09 | 66.38 | 97.72 | 0.00 | 0.00 |
May | 113.28 | 51.95 | 140.93 | 28.84 | 112.09 | 0.00 | 0.00 |
June | 140.03 | 18.05 | 133.06 | 20.48 | 112.59 | 0.00 | 0.00 |
July | 172.04 | 3.71 | 138.46 | 23.35 | 115.11 | 0.00 | 0.00 |
August | 214.49 | 10.11 | 185.45 | 68.39 | 117.06 | 0.00 | 0.00 |
September | 207.17 | 32.79 | 195.76 | 98.30 | 97.46 | 0.00 | 0.00 |
October | 292.80 | 79.64 | 276.74 | 173.59 | 103.15 | 0.00 | 0.00 |
November | 177.77 | 136.96 | 191.56 | 114.92 | 76.64 | 0.00 | 0.00 |
December | 175.07 | 178.07 | 189.95 | 134.90 | 55.04 | 0.00 | 0.00 |
Annual Sum or Average | 176.98 | 95.29 | 185.68 | 92.42 | 93.26 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 3.71 | 133.06 | 20.48 | 55.04 | 0.00 | 0.00 |
Maximum of Months | 292.80 | 200.58 | 276.74 | 173.59 | 117.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.10 | 1215.99 | 161.46 | 0.00 | 161.46 | 0.00 | 0.00 |
February | 2.27 | 1237.29 | 220.95 | 0.00 | 220.95 | 0.00 | 0.00 |
March | 45.87 | 823.35 | 306.47 | 0.01 | 306.47 | 0.00 | 0.00 |
April | 156.05 | 552.63 | 368.80 | 1.50 | 367.30 | 0.00 | 0.00 |
May | 356.20 | 292.26 | 490.49 | 17.90 | 472.59 | 0.00 | 0.00 |
June | 550.12 | 128.65 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
July | 650.21 | 49.91 | 502.25 | 19.55 | 482.70 | 0.00 | 0.00 |
August | 585.32 | 82.12 | 444.16 | 5.86 | 438.30 | 0.00 | 0.00 |
September | 323.24 | 212.47 | 334.47 | 0.19 | 334.28 | 0.00 | 0.00 |
October | 161.08 | 461.91 | 289.22 | 0.00 | 289.22 | 0.00 | 0.00 |
November | 23.95 | 834.01 | 202.86 | 0.00 | 202.86 | 0.00 | 0.00 |
December | 0.30 | 1118.65 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Annual Sum or Average | 239.55 | 580.40 | 332.26 | 6.08 | 326.19 | 0.00 | 0.00 |
Minimum of Months | 0.10 | 49.91 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Maximum of Months | 650.21 | 1237.29 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.03 | 1253.84 | 161.46 | 0.00 | 161.46 | 0.00 | 0.00 |
February | 1.45 | 1274.07 | 220.95 | 0.00 | 220.95 | 0.00 | 0.00 |
March | 40.22 | 851.69 | 306.47 | 0.01 | 306.47 | 0.00 | 0.00 |
April | 145.16 | 573.72 | 368.80 | 1.50 | 367.30 | 0.00 | 0.00 |
May | 339.59 | 305.37 | 490.49 | 17.90 | 472.59 | 0.00 | 0.00 |
June | 533.47 | 138.11 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
July | 634.42 | 56.70 | 502.25 | 19.55 | 482.70 | 0.00 | 0.00 |
August | 570.44 | 89.08 | 444.16 | 5.86 | 438.30 | 0.00 | 0.00 |
September | 309.99 | 226.84 | 334.47 | 0.19 | 334.28 | 0.00 | 0.00 |
October | 151.04 | 481.27 | 289.22 | 0.00 | 289.22 | 0.00 | 0.00 |
November | 20.63 | 864.87 | 202.86 | 0.00 | 202.86 | 0.00 | 0.00 |
December | 0.18 | 1154.49 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Annual Sum or Average | 230.50 | 602.04 | 332.26 | 6.08 | 326.19 | 0.00 | 0.00 |
Minimum of Months | 0.03 | 56.70 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Maximum of Months | 634.42 | 1274.07 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.37 | 797.11 | 322.44 | 150.39 | 172.04 | 0.00 | 0.00 |
February | 246.50 | 780.49 | 468.91 | 235.26 | 233.65 | 0.00 | 0.00 |
March | 388.83 | 557.99 | 542.20 | 229.49 | 312.71 | 0.00 | 0.00 |
April | 523.83 | 380.87 | 592.90 | 233.48 | 359.41 | 0.00 | 0.00 |
May | 746.72 | 213.43 | 683.20 | 228.24 | 454.96 | 0.00 | 0.00 |
June | 856.26 | 88.29 | 644.76 | 191.76 | 453.00 | 0.00 | 0.00 |
July | 979.68 | 28.82 | 647.73 | 192.06 | 455.67 | 0.00 | 0.00 |
August | 1070.17 | 50.25 | 733.21 | 292.58 | 440.63 | 0.00 | 0.00 |
September | 745.83 | 133.79 | 587.72 | 250.17 | 337.54 | 0.00 | 0.00 |
October | 629.33 | 305.55 | 597.20 | 284.57 | 312.62 | 0.00 | 0.00 |
November | 269.35 | 541.23 | 387.02 | 165.76 | 221.26 | 0.00 | 0.00 |
December | 178.66 | 712.18 | 327.46 | 175.90 | 151.55 | 0.00 | 0.00 |
Annual Sum or Average | 567.63 | 380.29 | 545.09 | 219.10 | 325.99 | 0.00 | 0.00 |
Minimum of Months | 149.37 | 28.82 | 322.44 | 150.39 | 151.55 | 0.00 | 0.00 |
Maximum of Months | 1070.17 | 797.11 | 733.21 | 292.58 | 455.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 350.91 | 854.65 | 502.96 | 293.73 | 209.23 | 0.00 | 0.00 |
February | 466.88 | 855.25 | 668.32 | 393.92 | 274.40 | 0.00 | 0.00 |
March | 443.50 | 605.94 | 630.07 | 289.09 | 340.98 | 0.00 | 0.00 |
April | 375.47 | 410.04 | 544.13 | 169.48 | 374.65 | 0.00 | 0.00 |
May | 429.97 | 216.88 | 526.88 | 79.54 | 447.35 | 0.00 | 0.00 |
June | 553.91 | 86.08 | 516.10 | 61.54 | 454.56 | 0.00 | 0.00 |
July | 655.66 | 27.16 | 524.63 | 66.14 | 458.49 | 0.00 | 0.00 |
August | 741.21 | 55.37 | 624.34 | 176.10 | 448.24 | 0.00 | 0.00 |
September | 652.70 | 144.20 | 612.97 | 250.29 | 362.68 | 0.00 | 0.00 |
October | 819.25 | 332.84 | 803.61 | 441.88 | 361.73 | 0.00 | 0.00 |
November | 455.75 | 579.01 | 557.16 | 292.53 | 264.63 | 0.00 | 0.00 |
December | 415.66 | 762.41 | 531.80 | 343.41 | 188.40 | 0.00 | 0.00 |
Annual Sum or Average | 530.82 | 408.33 | 586.57 | 237.35 | 349.22 | 0.00 | 0.00 |
Minimum of Months | 350.91 | 27.16 | 502.96 | 61.54 | 188.40 | 0.00 | 0.00 |
Maximum of Months | 819.25 | 855.25 | 803.61 | 441.88 | 458.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144657E+10 | 0.170520E+10 | 0.162619E+10 | 0.106714E+10 | 0.559054E+09 | 0.00 | 0.00 |
February | 0.170098E+10 | 0.154455E+10 | 0.194451E+10 | 0.129262E+10 | 0.651898E+09 | 0.00 | 0.00 |
March | 0.157182E+10 | 0.121988E+10 | 0.190736E+10 | 0.105026E+10 | 0.857099E+09 | 0.00 | 0.00 |
April | 0.110541E+10 | 0.810538E+09 | 0.146859E+10 | 0.594063E+09 | 0.874529E+09 | 0.00 | 0.00 |
May | 0.108252E+10 | 0.455852E+09 | 0.130332E+10 | 0.266668E+09 | 0.103665E+10 | 0.00 | 0.00 |
June | 0.125428E+10 | 0.172927E+09 | 0.119089E+10 | 0.183270E+09 | 0.100762E+10 | 0.00 | 0.00 |
July | 0.153505E+10 | 52503381.77 | 0.128048E+10 | 0.215929E+09 | 0.106455E+10 | 0.00 | 0.00 |
August | 0.189585E+10 | 0.124624E+09 | 0.171508E+10 | 0.632490E+09 | 0.108259E+10 | 0.00 | 0.00 |
September | 0.184956E+10 | 0.305216E+09 | 0.175199E+10 | 0.879741E+09 | 0.872245E+09 | 0.00 | 0.00 |
October | 0.272755E+10 | 0.728503E+09 | 0.255933E+10 | 0.160538E+10 | 0.953957E+09 | 0.00 | 0.00 |
November | 0.164121E+10 | 0.113952E+10 | 0.171439E+10 | 0.102849E+10 | 0.685893E+09 | 0.00 | 0.00 |
December | 0.167353E+10 | 0.153338E+10 | 0.175666E+10 | 0.124760E+10 | 0.509057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194843E+11 | 0.979269E+10 | 0.202188E+11 | 0.100636E+11 | 0.101551E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108252E+10 | 52503381.77 | 0.119089E+10 | 0.183270E+09 | 0.509057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272755E+10 | 0.170520E+10 | 0.255933E+10 | 0.160538E+10 | 0.108259E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.402779E+10 | 0.492473E+10 | 0.457924E+10 | 0.300499E+10 | 0.157426E+10 | 0.00 | 0.00 |
February | 0.473451E+10 | 0.446151E+10 | 0.547562E+10 | 0.363992E+10 | 0.183570E+10 | 0.00 | 0.00 |
March | 0.436726E+10 | 0.362649E+10 | 0.537100E+10 | 0.295746E+10 | 0.241353E+10 | 0.00 | 0.00 |
April | 0.304871E+10 | 0.246604E+10 | 0.413546E+10 | 0.167284E+10 | 0.246262E+10 | 0.00 | 0.00 |
May | 0.295718E+10 | 0.144470E+10 | 0.367006E+10 | 0.750920E+09 | 0.291914E+10 | 0.00 | 0.00 |
June | 0.344680E+10 | 0.597573E+09 | 0.335345E+10 | 0.516075E+09 | 0.283738E+10 | 0.00 | 0.00 |
July | 0.423173E+10 | 0.219807E+09 | 0.360574E+10 | 0.608043E+09 | 0.299770E+10 | 0.00 | 0.00 |
August | 0.527203E+10 | 0.430101E+09 | 0.482956E+10 | 0.178105E+10 | 0.304851E+10 | 0.00 | 0.00 |
September | 0.514469E+10 | 0.100219E+10 | 0.493348E+10 | 0.247729E+10 | 0.245619E+10 | 0.00 | 0.00 |
October | 0.759891E+10 | 0.225872E+10 | 0.720691E+10 | 0.452063E+10 | 0.268628E+10 | 0.00 | 0.00 |
November | 0.455096E+10 | 0.339224E+10 | 0.482760E+10 | 0.289617E+10 | 0.193143E+10 | 0.00 | 0.00 |
December | 0.465676E+10 | 0.447699E+10 | 0.494664E+10 | 0.351317E+10 | 0.143347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540373E+11 | 0.293011E+11 | 0.569348E+11 | 0.283386E+11 | 0.285962E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295718E+10 | 0.219807E+09 | 0.335345E+10 | 0.516075E+09 | 0.143347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.759891E+10 | 0.492473E+10 | 0.720691E+10 | 0.452063E+10 | 0.304851E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.531137E+10 | 0.671149E+10 | 0.594870E+10 | 0.390365E+10 | 0.204505E+10 | 0.00 | 0.00 |
February | 0.625923E+10 | 0.604478E+10 | 0.711314E+10 | 0.472846E+10 | 0.238468E+10 | 0.00 | 0.00 |
March | 0.578591E+10 | 0.492428E+10 | 0.697723E+10 | 0.384192E+10 | 0.313532E+10 | 0.00 | 0.00 |
April | 0.403933E+10 | 0.336463E+10 | 0.537220E+10 | 0.217312E+10 | 0.319908E+10 | 0.00 | 0.00 |
May | 0.393466E+10 | 0.195514E+10 | 0.476761E+10 | 0.975488E+09 | 0.379212E+10 | 0.00 | 0.00 |
June | 0.462063E+10 | 0.785513E+09 | 0.435633E+10 | 0.670411E+09 | 0.368592E+10 | 0.00 | 0.00 |
July | 0.570326E+10 | 0.273665E+09 | 0.468407E+10 | 0.789882E+09 | 0.389418E+10 | 0.00 | 0.00 |
August | 0.711076E+10 | 0.534429E+09 | 0.627388E+10 | 0.231369E+10 | 0.396019E+10 | 0.00 | 0.00 |
September | 0.688331E+10 | 0.129849E+10 | 0.640887E+10 | 0.321815E+10 | 0.319072E+10 | 0.00 | 0.00 |
October | 0.101267E+11 | 0.296026E+10 | 0.936219E+10 | 0.587256E+10 | 0.348963E+10 | 0.00 | 0.00 |
November | 0.600804E+10 | 0.461856E+10 | 0.627133E+10 | 0.376229E+10 | 0.250904E+10 | 0.00 | 0.00 |
December | 0.614259E+10 | 0.610435E+10 | 0.642597E+10 | 0.456381E+10 | 0.186216E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.719258E+11 | 0.395756E+11 | 0.739615E+11 | 0.368134E+11 | 0.371481E+11 | 0.00 | 0.00 |
Minimum of Months | 0.393466E+10 | 0.273665E+09 | 0.435633E+10 | 0.670411E+09 | 0.186216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101267E+11 | 0.671149E+10 | 0.936219E+10 | 0.587256E+10 | 0.396019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339680E+09 | 0.102751E+10 | 0.559370E+09 | 0.308487E+09 | 0.250883E+09 | 0.00 | 0.00 |
February | 0.438297E+09 | 0.927511E+09 | 0.700088E+09 | 0.393915E+09 | 0.306173E+09 | 0.00 | 0.00 |
March | 0.669966E+09 | 0.706704E+09 | 0.896729E+09 | 0.448411E+09 | 0.448318E+09 | 0.00 | 0.00 |
April | 0.686887E+09 | 0.471348E+09 | 0.836693E+09 | 0.350949E+09 | 0.485744E+09 | 0.00 | 0.00 |
May | 0.882570E+09 | 0.262832E+09 | 0.917294E+09 | 0.303518E+09 | 0.613776E+09 | 0.00 | 0.00 |
June | 0.108197E+10 | 92783050.14 | 0.932950E+09 | 0.317799E+09 | 0.615151E+09 | 0.00 | 0.00 |
July | 0.120932E+10 | 21471903.73 | 0.927451E+09 | 0.296149E+09 | 0.631301E+09 | 0.00 | 0.00 |
August | 0.137442E+10 | 55877397.56 | 0.108505E+10 | 0.470007E+09 | 0.615040E+09 | 0.00 | 0.00 |
September | 0.951657E+09 | 0.164051E+09 | 0.859815E+09 | 0.398056E+09 | 0.461759E+09 | 0.00 | 0.00 |
October | 0.103938E+10 | 0.408624E+09 | 0.103209E+10 | 0.573533E+09 | 0.458556E+09 | 0.00 | 0.00 |
November | 0.414958E+09 | 0.676526E+09 | 0.578492E+09 | 0.273118E+09 | 0.305375E+09 | 0.00 | 0.00 |
December | 0.376145E+09 | 0.919876E+09 | 0.565894E+09 | 0.340843E+09 | 0.225051E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.946526E+10 | 0.573511E+10 | 0.989191E+10 | 0.447478E+10 | 0.541713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.339680E+09 | 21471903.73 | 0.559370E+09 | 0.273118E+09 | 0.225051E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137442E+10 | 0.102751E+10 | 0.108505E+10 | 0.573533E+09 | 0.631301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 89381302.10 | 0.109625E+10 | 0.300230E+09 | 97925523.83 | 0.202305E+09 | 0.00 | 0.00 |
February | 0.145627E+09 | 0.100265E+10 | 0.392709E+09 | 0.138864E+09 | 0.253845E+09 | 0.00 | 0.00 |
March | 0.396563E+09 | 0.712704E+09 | 0.637555E+09 | 0.241182E+09 | 0.396372E+09 | 0.00 | 0.00 |
April | 0.543531E+09 | 0.468282E+09 | 0.683373E+09 | 0.234288E+09 | 0.449085E+09 | 0.00 | 0.00 |
May | 0.825995E+09 | 0.256550E+09 | 0.847660E+09 | 0.257744E+09 | 0.589916E+09 | 0.00 | 0.00 |
June | 0.105034E+10 | 90029352.71 | 0.889425E+09 | 0.291798E+09 | 0.597627E+09 | 0.00 | 0.00 |
July | 0.116274E+10 | 20727141.74 | 0.866817E+09 | 0.261018E+09 | 0.605800E+09 | 0.00 | 0.00 |
August | 0.122527E+10 | 54046671.64 | 0.916453E+09 | 0.347449E+09 | 0.569004E+09 | 0.00 | 0.00 |
September | 0.714768E+09 | 0.161221E+09 | 0.637875E+09 | 0.224541E+09 | 0.413334E+09 | 0.00 | 0.00 |
October | 0.578327E+09 | 0.407072E+09 | 0.637675E+09 | 0.256769E+09 | 0.380906E+09 | 0.00 | 0.00 |
November | 0.126998E+09 | 0.705187E+09 | 0.315278E+09 | 70180947.51 | 0.245097E+09 | 0.00 | 0.00 |
December | 83136535.35 | 0.987805E+09 | 0.273126E+09 | 94672763.34 | 0.178453E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.694267E+10 | 0.596253E+10 | 0.739818E+10 | 0.251643E+10 | 0.488174E+10 | 0.00 | 0.00 |
Minimum of Months | 83136535.35 | 20727141.74 | 0.273126E+09 | 70180947.51 | 0.178453E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122527E+10 | 0.109625E+10 | 0.916453E+09 | 0.347449E+09 | 0.605800E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222711E+09 | 0.292263E+09 | 0.256645E+09 | 0.168415E+09 | 88229912.29 | 0.00 | 0.00 |
February | 0.249728E+09 | 0.306635E+09 | 0.306883E+09 | 0.204001E+09 | 0.102882E+09 | 0.00 | 0.00 |
March | 0.226598E+09 | 0.271402E+09 | 0.301019E+09 | 0.165752E+09 | 0.135267E+09 | 0.00 | 0.00 |
April | 0.147461E+09 | 0.199009E+09 | 0.231773E+09 | 93755041.77 | 0.138018E+09 | 0.00 | 0.00 |
May | 0.130924E+09 | 0.132066E+09 | 0.205690E+09 | 42085570.78 | 0.163604E+09 | 0.00 | 0.00 |
June | 0.156334E+09 | 68837556.83 | 0.187945E+09 | 28923624.25 | 0.159022E+09 | 0.00 | 0.00 |
July | 0.200884E+09 | 40285761.35 | 0.202085E+09 | 34077953.05 | 0.168007E+09 | 0.00 | 0.00 |
August | 0.265746E+09 | 52491886.78 | 0.270674E+09 | 99819567.05 | 0.170855E+09 | 0.00 | 0.00 |
September | 0.261509E+09 | 99179036.18 | 0.276498E+09 | 0.138841E+09 | 0.137658E+09 | 0.00 | 0.00 |
October | 0.402235E+09 | 0.178958E+09 | 0.403914E+09 | 0.253360E+09 | 0.150554E+09 | 0.00 | 0.00 |
November | 0.233713E+09 | 0.256332E+09 | 0.270565E+09 | 0.162317E+09 | 0.108248E+09 | 0.00 | 0.00 |
December | 0.244974E+09 | 0.312396E+09 | 0.277236E+09 | 0.196897E+09 | 80339342.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.274282E+10 | 0.220986E+10 | 0.319093E+10 | 0.158824E+10 | 0.160268E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130924E+09 | 40285761.35 | 0.187945E+09 | 28923624.25 | 80339342.33 | 0.00 | 0.00 |
Maximum of Months | 0.402235E+09 | 0.312396E+09 | 0.403914E+09 | 0.253360E+09 | 0.170855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 185943.44 | 0.337327E+09 | 49391170.92 | 0.00 | 49391170.92 | 0.00 | 0.00 |
February | 1573438.84 | 0.310996E+09 | 61048780.16 | 0.00 | 61048780.16 | 0.00 | 0.00 |
March | 19033109.83 | 0.220106E+09 | 93751937.54 | 1863.87 | 93750073.66 | 0.00 | 0.00 |
April | 53880507.28 | 0.138196E+09 | 0.109178E+09 | 445013.88 | 0.108733E+09 | 0.00 | 0.00 |
May | 0.121834E+09 | 70759550.51 | 0.150043E+09 | 5475613.50 | 0.144567E+09 | 0.00 | 0.00 |
June | 0.177340E+09 | 23171007.57 | 0.153183E+09 | 8129728.74 | 0.145053E+09 | 0.00 | 0.00 |
July | 0.219638E+09 | 4753742.71 | 0.153639E+09 | 5980273.24 | 0.147659E+09 | 0.00 | 0.00 |
August | 0.198605E+09 | 13344486.18 | 0.135871E+09 | 1793572.70 | 0.134077E+09 | 0.00 | 0.00 |
September | 0.105001E+09 | 44479747.24 | 99014499.97 | 56264.33 | 98958235.64 | 0.00 | 0.00 |
October | 56213368.87 | 0.117541E+09 | 88474560.91 | 0.00 | 88474560.91 | 0.00 | 0.00 |
November | 9867386.36 | 0.215553E+09 | 60054600.30 | 0.00 | 60054600.30 | 0.00 | 0.00 |
December | 258333.93 | 0.305908E+09 | 43082225.59 | 0.00 | 43082225.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.963429E+09 | 0.180214E+10 | 0.119673E+10 | 21882330.26 | 0.117485E+10 | 0.00 | 0.00 |
Minimum of Months | 185943.44 | 4753742.71 | 43082225.59 | 0.00 | 43082225.59 | 0.00 | 0.00 |
Maximum of Months | 0.219638E+09 | 0.337327E+09 | 0.153639E+09 | 8129728.74 | 0.147659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335441E+09 | 0.101963E+10 | 0.561038E+09 | 0.306531E+09 | 0.254507E+09 | 0.00 | 0.00 |
February | 0.454681E+09 | 0.912574E+09 | 0.720446E+09 | 0.411880E+09 | 0.308567E+09 | 0.00 | 0.00 |
March | 0.623324E+09 | 0.711653E+09 | 0.855136E+09 | 0.410712E+09 | 0.444424E+09 | 0.00 | 0.00 |
April | 0.680564E+09 | 0.457959E+09 | 0.844467E+09 | 0.360696E+09 | 0.483771E+09 | 0.00 | 0.00 |
May | 0.912331E+09 | 0.254305E+09 | 0.949060E+09 | 0.328311E+09 | 0.620749E+09 | 0.00 | 0.00 |
June | 0.983157E+09 | 88193178.86 | 0.856728E+09 | 0.261329E+09 | 0.595400E+09 | 0.00 | 0.00 |
July | 0.117273E+10 | 20121536.25 | 0.897094E+09 | 0.274576E+09 | 0.622518E+09 | 0.00 | 0.00 |
August | 0.134603E+10 | 52107772.80 | 0.106546E+10 | 0.452804E+09 | 0.612653E+09 | 0.00 | 0.00 |
September | 0.957472E+09 | 0.157086E+09 | 0.872065E+09 | 0.410735E+09 | 0.461330E+09 | 0.00 | 0.00 |
October | 0.985208E+09 | 0.399942E+09 | 0.996353E+09 | 0.539188E+09 | 0.457165E+09 | 0.00 | 0.00 |
November | 0.472168E+09 | 0.669404E+09 | 0.632796E+09 | 0.316127E+09 | 0.316669E+09 | 0.00 | 0.00 |
December | 0.392549E+09 | 0.910921E+09 | 0.584572E+09 | 0.358469E+09 | 0.226103E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931566E+10 | 0.565390E+10 | 0.983521E+10 | 0.443136E+10 | 0.540386E+10 | 0.00 | 0.00 |
Minimum of Months | 0.335441E+09 | 20121536.25 | 0.561038E+09 | 0.261329E+09 | 0.226103E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134603E+10 | 0.101963E+10 | 0.106546E+10 | 0.539188E+09 | 0.622518E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 73365627.88 | 0.107653E+10 | 0.301899E+09 | 95969669.36 | 0.205929E+09 | 0.00 | 0.00 |
February | 0.137413E+09 | 0.962590E+09 | 0.413067E+09 | 0.156828E+09 | 0.256239E+09 | 0.00 | 0.00 |
March | 0.345678E+09 | 0.713124E+09 | 0.595962E+09 | 0.203483E+09 | 0.392479E+09 | 0.00 | 0.00 |
April | 0.535461E+09 | 0.453730E+09 | 0.691147E+09 | 0.244035E+09 | 0.447112E+09 | 0.00 | 0.00 |
May | 0.856935E+09 | 0.249571E+09 | 0.879426E+09 | 0.282537E+09 | 0.596889E+09 | 0.00 | 0.00 |
June | 0.952320E+09 | 86201258.46 | 0.813203E+09 | 0.235328E+09 | 0.577876E+09 | 0.00 | 0.00 |
July | 0.112654E+10 | 19750859.61 | 0.836461E+09 | 0.239445E+09 | 0.597016E+09 | 0.00 | 0.00 |
August | 0.119708E+10 | 50745558.36 | 0.896863E+09 | 0.330246E+09 | 0.566617E+09 | 0.00 | 0.00 |
September | 0.718809E+09 | 0.153552E+09 | 0.650125E+09 | 0.237220E+09 | 0.412905E+09 | 0.00 | 0.00 |
October | 0.519939E+09 | 0.394575E+09 | 0.601938E+09 | 0.222425E+09 | 0.379514E+09 | 0.00 | 0.00 |
November | 0.168695E+09 | 0.682989E+09 | 0.369581E+09 | 0.113190E+09 | 0.256391E+09 | 0.00 | 0.00 |
December | 82044288.57 | 0.961012E+09 | 0.291803E+09 | 0.112299E+09 | 0.179505E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.671427E+10 | 0.580437E+10 | 0.734147E+10 | 0.247300E+10 | 0.486847E+10 | 0.00 | 0.00 |
Minimum of Months | 73365627.88 | 19750859.61 | 0.291803E+09 | 95969669.36 | 0.179505E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119708E+10 | 0.107653E+10 | 0.896863E+09 | 0.330246E+09 | 0.597016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422299E+09 | 0.127855E+10 | 0.663077E+09 | 0.364909E+09 | 0.298168E+09 | 0.00 | 0.00 |
February | 0.512609E+09 | 0.115868E+10 | 0.797182E+09 | 0.442013E+09 | 0.355170E+09 | 0.00 | 0.00 |
March | 0.578120E+09 | 0.895335E+09 | 0.855323E+09 | 0.359143E+09 | 0.496181E+09 | 0.00 | 0.00 |
April | 0.513962E+09 | 0.575587E+09 | 0.738705E+09 | 0.204105E+09 | 0.534600E+09 | 0.00 | 0.00 |
May | 0.667129E+09 | 0.299769E+09 | 0.770715E+09 | 0.103050E+09 | 0.667666E+09 | 0.00 | 0.00 |
June | 0.864261E+09 | 93620651.80 | 0.739071E+09 | 80281168.88 | 0.658790E+09 | 0.00 | 0.00 |
July | 0.107571E+10 | 17683914.92 | 0.770696E+09 | 86792724.65 | 0.683903E+09 | 0.00 | 0.00 |
August | 0.115748E+10 | 55380512.23 | 0.880818E+09 | 0.220167E+09 | 0.660651E+09 | 0.00 | 0.00 |
September | 0.908328E+09 | 0.180554E+09 | 0.813594E+09 | 0.300951E+09 | 0.512643E+09 | 0.00 | 0.00 |
October | 0.108943E+10 | 0.477611E+09 | 0.106683E+10 | 0.548961E+09 | 0.517873E+09 | 0.00 | 0.00 |
November | 0.559629E+09 | 0.830905E+09 | 0.716337E+09 | 0.351696E+09 | 0.364641E+09 | 0.00 | 0.00 |
December | 0.503309E+09 | 0.113970E+10 | 0.694024E+09 | 0.426621E+09 | 0.267404E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.885227E+10 | 0.700338E+10 | 0.950638E+10 | 0.348869E+10 | 0.601769E+10 | 0.00 | 0.00 |
Minimum of Months | 0.422299E+09 | 17683914.92 | 0.663077E+09 | 80281168.88 | 0.267404E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115748E+10 | 0.127855E+10 | 0.106683E+10 | 0.548961E+09 | 0.683903E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339738E+09 | 0.102447E+10 | 0.559829E+09 | 0.308740E+09 | 0.251089E+09 | 0.00 | 0.00 |
February | 0.437106E+09 | 0.926389E+09 | 0.700663E+09 | 0.394238E+09 | 0.306424E+09 | 0.00 | 0.00 |
March | 0.665827E+09 | 0.705599E+09 | 0.897465E+09 | 0.448779E+09 | 0.448686E+09 | 0.00 | 0.00 |
April | 0.680903E+09 | 0.470917E+09 | 0.837379E+09 | 0.351237E+09 | 0.486142E+09 | 0.00 | 0.00 |
May | 0.870819E+09 | 0.264589E+09 | 0.918047E+09 | 0.303767E+09 | 0.614280E+09 | 0.00 | 0.00 |
June | 0.106950E+10 | 94532314.07 | 0.933716E+09 | 0.318060E+09 | 0.615656E+09 | 0.00 | 0.00 |
July | 0.119692E+10 | 22193278.61 | 0.928211E+09 | 0.296392E+09 | 0.631819E+09 | 0.00 | 0.00 |
August | 0.136406E+10 | 56254021.67 | 0.108594E+10 | 0.470392E+09 | 0.615545E+09 | 0.00 | 0.00 |
September | 0.942765E+09 | 0.165331E+09 | 0.860520E+09 | 0.398383E+09 | 0.462137E+09 | 0.00 | 0.00 |
October | 0.103199E+10 | 0.408738E+09 | 0.103294E+10 | 0.574003E+09 | 0.458933E+09 | 0.00 | 0.00 |
November | 0.414347E+09 | 0.672751E+09 | 0.578967E+09 | 0.273342E+09 | 0.305625E+09 | 0.00 | 0.00 |
December | 0.377125E+09 | 0.915670E+09 | 0.566358E+09 | 0.341122E+09 | 0.225236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.939109E+10 | 0.572744E+10 | 0.990003E+10 | 0.447846E+10 | 0.542157E+10 | 0.00 | 0.00 |
Minimum of Months | 0.339738E+09 | 22193278.61 | 0.559829E+09 | 0.273342E+09 | 0.225236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136406E+10 | 0.102447E+10 | 0.108594E+10 | 0.574003E+09 | 0.631819E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 90241609.32 | 0.109295E+10 | 0.300477E+09 | 98005856.50 | 0.202471E+09 | 0.00 | 0.00 |
February | 0.145992E+09 | 0.100198E+10 | 0.393031E+09 | 0.138978E+09 | 0.254054E+09 | 0.00 | 0.00 |
March | 0.394451E+09 | 0.710720E+09 | 0.638078E+09 | 0.241380E+09 | 0.396698E+09 | 0.00 | 0.00 |
April | 0.537763E+09 | 0.467222E+09 | 0.683934E+09 | 0.234481E+09 | 0.449453E+09 | 0.00 | 0.00 |
May | 0.813555E+09 | 0.258219E+09 | 0.848355E+09 | 0.257955E+09 | 0.590400E+09 | 0.00 | 0.00 |
June | 0.103722E+10 | 91778718.26 | 0.890155E+09 | 0.292038E+09 | 0.598117E+09 | 0.00 | 0.00 |
July | 0.114931E+10 | 21535090.13 | 0.867528E+09 | 0.261232E+09 | 0.606297E+09 | 0.00 | 0.00 |
August | 0.121399E+10 | 54421456.84 | 0.917205E+09 | 0.347734E+09 | 0.569471E+09 | 0.00 | 0.00 |
September | 0.705539E+09 | 0.162377E+09 | 0.638398E+09 | 0.224725E+09 | 0.413673E+09 | 0.00 | 0.00 |
October | 0.573113E+09 | 0.405935E+09 | 0.638198E+09 | 0.256980E+09 | 0.381218E+09 | 0.00 | 0.00 |
November | 0.127974E+09 | 0.699715E+09 | 0.315536E+09 | 70238520.06 | 0.245298E+09 | 0.00 | 0.00 |
December | 84879243.97 | 0.982107E+09 | 0.273350E+09 | 94750427.63 | 0.178599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.687403E+10 | 0.594896E+10 | 0.740425E+10 | 0.251850E+10 | 0.488575E+10 | 0.00 | 0.00 |
Minimum of Months | 84879243.97 | 21535090.13 | 0.273350E+09 | 70238520.06 | 0.178599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121399E+10 | 0.109295E+10 | 0.917205E+09 | 0.347734E+09 | 0.606297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401865E+09 | 0.532869E+09 | 0.470973E+09 | 0.309061E+09 | 0.161912E+09 | 0.00 | 0.00 |
February | 0.473118E+09 | 0.485240E+09 | 0.563165E+09 | 0.374364E+09 | 0.188801E+09 | 0.00 | 0.00 |
March | 0.442039E+09 | 0.382398E+09 | 0.552405E+09 | 0.304174E+09 | 0.248231E+09 | 0.00 | 0.00 |
April | 0.311624E+09 | 0.251425E+09 | 0.425330E+09 | 0.172051E+09 | 0.253279E+09 | 0.00 | 0.00 |
May | 0.303403E+09 | 0.139151E+09 | 0.377464E+09 | 77231809.09 | 0.300232E+09 | 0.00 | 0.00 |
June | 0.362965E+09 | 46796588.47 | 0.344901E+09 | 53078140.20 | 0.291823E+09 | 0.00 | 0.00 |
July | 0.460793E+09 | 9932019.38 | 0.370849E+09 | 62536919.79 | 0.308312E+09 | 0.00 | 0.00 |
August | 0.574479E+09 | 27078734.61 | 0.496718E+09 | 0.183180E+09 | 0.313538E+09 | 0.00 | 0.00 |
September | 0.536982E+09 | 84998897.28 | 0.507406E+09 | 0.254789E+09 | 0.252618E+09 | 0.00 | 0.00 |
October | 0.784242E+09 | 0.213295E+09 | 0.741228E+09 | 0.464945E+09 | 0.276283E+09 | 0.00 | 0.00 |
November | 0.460781E+09 | 0.355003E+09 | 0.496517E+09 | 0.297870E+09 | 0.198647E+09 | 0.00 | 0.00 |
December | 0.468913E+09 | 0.476932E+09 | 0.508760E+09 | 0.361328E+09 | 0.147432E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.558120E+10 | 0.300512E+10 | 0.585572E+10 | 0.291461E+10 | 0.294111E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303403E+09 | 9932019.38 | 0.344901E+09 | 53078140.20 | 0.147432E+09 | 0.00 | 0.00 |
Maximum of Months | 0.784242E+09 | 0.532869E+09 | 0.741228E+09 | 0.464945E+09 | 0.313538E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 275707.62 | 0.325690E+10 | 0.432454E+09 | 0.00 | 0.432454E+09 | 0.00 | 0.00 |
February | 5494014.34 | 0.299325E+10 | 0.534524E+09 | 0.00 | 0.534524E+09 | 0.00 | 0.00 |
March | 0.122860E+09 | 0.220527E+10 | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.00 | 0.00 |
April | 0.404469E+09 | 0.143242E+10 | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.00 | 0.00 |
May | 0.954052E+09 | 0.782800E+09 | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.00 | 0.00 |
June | 0.142591E+10 | 0.333465E+09 | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.00 | 0.00 |
July | 0.174153E+10 | 0.133680E+09 | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.00 | 0.00 |
August | 0.156773E+10 | 0.219940E+09 | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.00 | 0.00 |
September | 0.837836E+09 | 0.550719E+09 | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.00 | 0.00 |
October | 0.431427E+09 | 0.123719E+10 | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.00 | 0.00 |
November | 62091317.45 | 0.216174E+10 | 0.525819E+09 | 0.00 | 0.525819E+09 | 0.00 | 0.00 |
December | 809932.51 | 0.299620E+10 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.755448E+10 | 0.183036E+11 | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.00 | 0.00 |
Minimum of Months | 275707.62 | 0.133680E+09 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174153E+10 | 0.325690E+10 | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 88199.28 | 0.335829E+10 | 0.432454E+09 | 0.00 | 0.432454E+09 | 0.00 | 0.00 |
February | 3509217.56 | 0.308223E+10 | 0.534524E+09 | 0.00 | 0.534524E+09 | 0.00 | 0.00 |
March | 0.107727E+09 | 0.228118E+10 | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.00 | 0.00 |
April | 0.376267E+09 | 0.148708E+10 | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.00 | 0.00 |
May | 0.909569E+09 | 0.817916E+09 | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.00 | 0.00 |
June | 0.138276E+10 | 0.357974E+09 | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.00 | 0.00 |
July | 0.169924E+10 | 0.151861E+09 | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.00 | 0.00 |
August | 0.152787E+10 | 0.238603E+09 | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.00 | 0.00 |
September | 0.803489E+09 | 0.587973E+09 | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.00 | 0.00 |
October | 0.404540E+09 | 0.128904E+10 | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.00 | 0.00 |
November | 53485653.14 | 0.224174E+10 | 0.525819E+09 | 0.00 | 0.525819E+09 | 0.00 | 0.00 |
December | 478982.24 | 0.309219E+10 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.726902E+10 | 0.189861E+11 | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.00 | 0.00 |
Minimum of Months | 88199.28 | 0.151861E+09 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169924E+10 | 0.335829E+10 | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400077E+09 | 0.213497E+10 | 0.863611E+09 | 0.402817E+09 | 0.460794E+09 | 0.00 | 0.00 |
February | 0.596323E+09 | 0.188815E+10 | 0.113440E+10 | 0.569152E+09 | 0.565244E+09 | 0.00 | 0.00 |
March | 0.104143E+10 | 0.149452E+10 | 0.145222E+10 | 0.614671E+09 | 0.837550E+09 | 0.00 | 0.00 |
April | 0.135776E+10 | 0.987211E+09 | 0.153679E+10 | 0.605192E+09 | 0.931603E+09 | 0.00 | 0.00 |
May | 0.200002E+10 | 0.571652E+09 | 0.182989E+10 | 0.611309E+09 | 0.121858E+10 | 0.00 | 0.00 |
June | 0.221943E+10 | 0.228854E+09 | 0.167121E+10 | 0.497032E+09 | 0.117418E+10 | 0.00 | 0.00 |
July | 0.262398E+10 | 77188978.00 | 0.173488E+10 | 0.514410E+09 | 0.122048E+10 | 0.00 | 0.00 |
August | 0.286635E+10 | 0.134597E+09 | 0.196383E+10 | 0.783646E+09 | 0.118018E+10 | 0.00 | 0.00 |
September | 0.193319E+10 | 0.346789E+09 | 0.152336E+10 | 0.648453E+09 | 0.874910E+09 | 0.00 | 0.00 |
October | 0.168558E+10 | 0.818385E+09 | 0.159953E+10 | 0.762206E+09 | 0.837327E+09 | 0.00 | 0.00 |
November | 0.698168E+09 | 0.140286E+10 | 0.100316E+10 | 0.429653E+09 | 0.573504E+09 | 0.00 | 0.00 |
December | 0.478511E+09 | 0.190749E+10 | 0.877060E+09 | 0.471138E+09 | 0.405923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179008E+11 | 0.119927E+11 | 0.171899E+11 | 0.690968E+10 | 0.102803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.400077E+09 | 77188978.00 | 0.863611E+09 | 0.402817E+09 | 0.405923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286635E+10 | 0.213497E+10 | 0.196383E+10 | 0.783646E+09 | 0.122048E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.939877E+09 | 0.228908E+10 | 0.134713E+10 | 0.786732E+09 | 0.560401E+09 | 0.00 | 0.00 |
February | 0.112948E+10 | 0.206903E+10 | 0.161680E+10 | 0.952964E+09 | 0.663839E+09 | 0.00 | 0.00 |
March | 0.118787E+10 | 0.162294E+10 | 0.168757E+10 | 0.774297E+09 | 0.913273E+09 | 0.00 | 0.00 |
April | 0.973229E+09 | 0.106281E+10 | 0.141040E+10 | 0.439301E+09 | 0.971094E+09 | 0.00 | 0.00 |
May | 0.115163E+10 | 0.580883E+09 | 0.141120E+10 | 0.213033E+09 | 0.119817E+10 | 0.00 | 0.00 |
June | 0.143574E+10 | 0.223131E+09 | 0.133774E+10 | 0.159514E+09 | 0.117822E+10 | 0.00 | 0.00 |
July | 0.175611E+10 | 72732271.53 | 0.140516E+10 | 0.177141E+09 | 0.122802E+10 | 0.00 | 0.00 |
August | 0.198525E+10 | 0.148302E+09 | 0.167223E+10 | 0.471678E+09 | 0.120056E+10 | 0.00 | 0.00 |
September | 0.169180E+10 | 0.373766E+09 | 0.158882E+10 | 0.648747E+09 | 0.940071E+09 | 0.00 | 0.00 |
October | 0.219428E+10 | 0.891489E+09 | 0.215239E+10 | 0.118354E+10 | 0.968846E+09 | 0.00 | 0.00 |
November | 0.118130E+10 | 0.150081E+10 | 0.144416E+10 | 0.758245E+09 | 0.685917E+09 | 0.00 | 0.00 |
December | 0.111331E+10 | 0.204204E+10 | 0.142439E+10 | 0.919780E+09 | 0.504605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167399E+11 | 0.128770E+11 | 0.184980E+11 | 0.748497E+10 | 0.110130E+11 | 0.00 | 0.00 |
Minimum of Months | 0.939877E+09 | 72732271.53 | 0.133774E+10 | 0.159514E+09 | 0.504605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.219428E+10 | 0.228908E+10 | 0.215239E+10 | 0.118354E+10 | 0.122802E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.419753E+11 | -.715262E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.149958E+10 | 58.99 | 0.00 | 0.00 |
February | 0.386453E+11 | -.652677E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.137014E+10 | 58.99 | 0.00 | 0.00 |
March | 0.411175E+11 | -.706957E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.153363E+10 | 59.01 | 0.00 | 0.00 |
April | 0.359887E+11 | -.648671E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.150383E+10 | 59.05 | 0.00 | 0.00 |
May | 0.322038E+11 | -.623827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157937E+10 | 59.16 | 0.00 | 0.00 |
June | 0.265675E+11 | -.560932E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.153950E+10 | 59.30 | 0.00 | 0.00 |
July | 0.241290E+11 | -.548781E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159198E+10 | 59.39 | 0.00 | 0.00 |
August | 0.233247E+11 | -.541457E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157911E+10 | 59.46 | 0.00 | 0.00 |
September | 0.242575E+11 | -.539923E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.149830E+10 | 59.38 | 0.00 | 0.00 |
October | 0.289433E+11 | -.594378E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.149836E+10 | 59.21 | 0.00 | 0.00 |
November | 0.328533E+11 | -.620343E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.142882E+10 | 59.10 | 0.00 | 0.00 |
December | 0.387195E+11 | -.685240E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.148038E+10 | 59.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.388725E+12 | -.743845E+12 | 8760.00 | -.181030E+11 | 59.18 | |||||
Minimum of Months | 0.233247E+11 | -.715262E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.159198E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.419753E+11 | -.539923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.137014E+10 | 59.46 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770518E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162393168.9 | 81.21 | 0.00 | 0.00 |
February | 0.696266E+10 | -.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146692404.2 | 81.21 | 0.00 | 0.00 |
March | 0.770487E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162064870.9 | 81.21 | 0.00 | 0.00 |
April | 0.746544E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156848357.6 | 81.21 | 0.00 | 0.00 |
May | 0.770518E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162382626.5 | 81.21 | 0.00 | 0.00 |
June | 0.745817E+10 | -.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157648564.0 | 81.21 | 0.00 | 0.00 |
July | 0.771390E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163062893.7 | 81.21 | 0.00 | 0.00 |
August | 0.770576E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162964392.8 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157559855.6 | 81.21 | 0.00 | 0.00 |
October | 0.770510E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162320761.2 | 81.21 | 0.00 | 0.00 |
November | 0.744935E+10 | -.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156926534.7 | 81.21 | 0.00 | 0.00 |
December | 0.771312E+10 | -.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162261966.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907549E+11 | -.888417E+11 | 8760.00 | -.191313E+10 | 81.21 | |||||
Minimum of Months | 0.696266E+10 | -.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163062893.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771390E+10 | -.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146692404.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.786884E+11 | -.774871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120129E+10 | 62.95 | 0.00 | 0.00 |
February | 0.711405E+11 | -.700495E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.109096E+10 | 62.76 | 0.00 | 0.00 |
March | 0.785954E+11 | -.773661E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122925E+10 | 63.09 | 0.00 | 0.00 |
April | 0.757180E+11 | -.744910E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122700E+10 | 63.93 | 0.00 | 0.00 |
May | 0.777765E+11 | -.764625E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131400E+10 | 64.96 | 0.00 | 0.00 |
June | 0.748373E+11 | -.735333E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.130400E+10 | 65.93 | 0.00 | 0.00 |
July | 0.770288E+11 | -.756633E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136542E+10 | 66.59 | 0.00 | 0.00 |
August | 0.769468E+11 | -.755878E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135901E+10 | 66.76 | 0.00 | 0.00 |
September | 0.746246E+11 | -.733392E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128533E+10 | 66.39 | 0.00 | 0.00 |
October | 0.774749E+11 | -.762020E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127285E+10 | 65.58 | 0.00 | 0.00 |
November | 0.754253E+11 | -.742346E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.119064E+10 | 64.59 | 0.00 | 0.00 |
December | 0.783854E+11 | -.771806E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120475E+10 | 63.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.916642E+12 | -.901597E+12 | 8760.00 | -.150445E+11 | 64.77 | |||||
Minimum of Months | 0.711405E+11 | -.774871E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.136542E+10 | 62.76 | 0.00 | 0.00 |
Maximum of Months | 0.786884E+11 | -.700495E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.109096E+10 | 66.76 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.93 | 0.93 | 01-JAN-07:49 | 5151.17 | 36.73 | 196.33 | 242.83 | 2460.85 | 33.50 | 185.50 | 185.33 |
February | 216.00 | 0.93 | 0.93 | 01-FEB-07:40 | 7542.45 | 37.35 | 208.17 | 257.67 | 1069.96 | 26.96 | 196.33 | 220.67 |
March | 275.00 | 0.93 | 0.93 | 01-MAR-06:00 | 3647.04 | 25.41 | 142.83 | 324.17 | 662.46 | 22.29 | 200.67 | 249.83 |
April | 261.17 | 0.93 | 0.93 | 01-APR-06:19 | 1298.05 | 20.07 | 36.83 | 339.33 | 529.38 | 21.83 | 191.17 | 269.17 |
May | 372.00 | 0.93 | 0.93 | 01-MAY-05:40 | 1174.55 | 19.78 | 16.17 | 392.17 | 466.65 | 21.52 | 231.50 | 306.67 |
June | 351.83 | 0.93 | 0.93 | 01-JUN-05:19 | 1113.78 | 19.68 | 21.17 | 382.00 | 449.73 | 21.45 | 236.33 | 308.17 |
July | 365.17 | 0.93 | 0.93 | 01-JUL-05:30 | 1241.88 | 19.85 | 52.83 | 389.67 | 492.09 | 21.61 | 248.33 | 312.67 |
August | 389.17 | 0.93 | 0.93 | 01-AUG-05:49 | 1329.79 | 20.14 | 81.67 | 370.67 | 538.50 | 21.88 | 296.33 | 315.17 |
September | 285.33 | 0.93 | 0.93 | 01-SEP-06:10 | 1479.80 | 20.25 | 50.83 | 324.17 | 597.86 | 22.04 | 220.33 | 266.67 |
October | 305.50 | 0.93 | 0.93 | 01-OCT-14:39 | 7506.98 | 35.73 | 278.33 | 307.17 | 915.29 | 24.65 | 272.33 | 277.50 |
November | 240.83 | 0.93 | 0.93 | 01-NOV-06:49 | 5112.31 | 36.17 | 234.83 | 257.17 | 1359.33 | 29.61 | 220.00 | 224.50 |
December | 211.17 | 0.93 | 0.93 | 01-DEC-07:30 | 4782.96 | 37.72 | 207.67 | 245.00 | 3695.13 | 37.69 | 204.50 | 201.17 |
Annual Sum or Average | 3472.67 | 0.93 | 3097.16 | 26.02 | 1527.67 | 3832.00 | 956.45 | 24.53 | 2703.33 | 3137.50 | ||
Minimum of Months | 199.50 | 0.93 | 0.93 | 1113.78 | 19.68 | 16.17 | 242.83 | 449.73 | 21.45 | 185.50 | 185.33 | |
Maximum of Months | 389.17 | 0.93 | 0.93 | 7542.45 | 37.72 | 278.33 | 392.17 | 3695.13 | 37.69 | 296.33 | 315.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.63 | 0.61 | 01-JAN-07:40 | 5545.08 | 36.79 | 196.50 | 257.17 | 2855.17 | 33.46 | 186.00 | 213.17 |
February | 216.00 | 0.62 | 0.61 | 01-FEB-07:40 | 7993.30 | 37.43 | 208.17 | 267.00 | 1520.24 | 26.66 | 184.17 | 243.33 |
March | 275.00 | 0.62 | 0.61 | 01-MAR-06:49 | 4015.44 | 25.57 | 135.50 | 334.50 | 1029.27 | 22.33 | 190.50 | 302.17 |
April | 261.17 | 0.62 | 0.61 | 01-APR-06:10 | 1582.72 | 20.42 | 63.00 | 354.33 | 813.24 | 22.01 | 193.00 | 314.67 |
May | 372.00 | 0.62 | 0.61 | 01-MAY-05:40 | 1379.25 | 20.41 | 106.00 | 407.33 | 670.55 | 21.95 | 252.00 | 364.83 |
June | 351.83 | 0.62 | 0.61 | 01-JUN-05:10 | 1309.52 | 20.33 | 102.83 | 400.67 | 644.72 | 21.90 | 257.33 | 355.67 |
July | 365.17 | 0.62 | 0.61 | 01-JUL-05:10 | 1450.34 | 20.48 | 118.33 | 410.00 | 699.70 | 22.04 | 278.17 | 359.33 |
August | 389.17 | 0.63 | 0.61 | 01-AUG-05:30 | 1592.69 | 20.56 | 139.17 | 381.17 | 800.54 | 22.13 | 302.83 | 352.33 |
September | 285.33 | 0.62 | 0.61 | 01-SEP-05:00 | 1808.69 | 20.47 | 75.00 | 337.17 | 925.73 | 22.12 | 211.50 | 302.17 |
October | 305.50 | 0.62 | 0.61 | 01-OCT-14:39 | 7957.33 | 35.79 | 277.17 | 315.67 | 1364.07 | 24.51 | 277.17 | 297.50 |
November | 240.83 | 0.62 | 0.61 | 01-NOV-06:49 | 5479.59 | 36.25 | 234.83 | 265.00 | 1723.22 | 29.53 | 220.17 | 247.33 |
December | 211.17 | 0.63 | 0.61 | 01-DEC-07:30 | 5174.69 | 37.77 | 207.83 | 254.50 | 4084.98 | 37.70 | 203.67 | 228.83 |
Annual Sum or Average | 3472.67 | 0.62 | 3407.49 | 26.35 | 1864.33 | 3984.50 | 1265.67 | 24.69 | 2756.50 | 3581.33 | ||
Minimum of Months | 199.50 | 0.62 | 0.61 | 1309.52 | 20.33 | 63.00 | 254.50 | 644.72 | 21.90 | 184.17 | 213.17 | |
Maximum of Months | 389.17 | 0.63 | 0.61 | 7993.30 | 37.77 | 277.17 | 410.00 | 4084.98 | 37.70 | 302.83 | 364.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.82 | 0.80 | 01-JAN-08:09 | 389.29 | 14.73 | 0.00 | 221.83 | 187.75 | 18.15 | 0.00 | 90.67 |
February | 216.00 | 0.82 | 0.80 | 01-FEB-08:09 | 400.15 | 15.43 | 0.00 | 241.33 | 205.15 | 18.91 | 0.00 | 130.83 |
March | 275.00 | 0.81 | 0.80 | 01-MAR-06:00 | 548.62 | 16.81 | 0.00 | 321.50 | 264.58 | 20.07 | 4.17 | 221.67 |
April | 261.17 | 0.81 | 0.80 | 01-APR-06:10 | 604.45 | 17.42 | 0.00 | 351.83 | 291.52 | 20.66 | 38.67 | 284.67 |
May | 372.00 | 0.80 | 0.80 | 01-MAY-05:40 | 830.09 | 18.13 | 0.00 | 415.17 | 370.82 | 22.04 | 179.00 | 363.00 |
June | 351.83 | 0.80 | 0.80 | 01-JUN-04:00 | 921.60 | 19.25 | 28.67 | 407.50 | 400.61 | 23.09 | 228.50 | 369.67 |
July | 365.17 | 0.80 | 0.80 | 01-JUL-04:00 | 926.21 | 18.18 | 0.00 | 415.67 | 399.60 | 22.73 | 229.83 | 370.17 |
August | 389.17 | 0.81 | 0.80 | 01-AUG-05:19 | 734.14 | 17.87 | 0.00 | 385.33 | 339.72 | 21.11 | 159.67 | 348.50 |
September | 285.33 | 0.81 | 0.80 | 01-SEP-05:00 | 553.92 | 17.03 | 0.00 | 329.00 | 270.67 | 20.30 | 12.00 | 253.67 |
October | 305.50 | 0.81 | 0.80 | 01-OCT-14:39 | 501.04 | 16.58 | 0.00 | 296.83 | 256.74 | 19.96 | 0.00 | 229.83 |
November | 240.83 | 0.81 | 0.80 | 01-NOV-07:10 | 437.44 | 15.29 | 0.00 | 244.67 | 205.09 | 18.62 | 0.00 | 130.50 |
December | 211.17 | 0.83 | 0.80 | 01-DEC-08:09 | 308.28 | 13.80 | 0.00 | 210.00 | 154.95 | 17.38 | 0.00 | 45.50 |
Annual Sum or Average | 3472.67 | 0.81 | 636.79 | 17.01 | 28.67 | 3840.67 | 295.30 | 20.59 | 851.83 | 2838.67 | ||
Minimum of Months | 199.50 | 0.80 | 0.80 | 308.28 | 13.80 | 0.00 | 210.00 | 154.95 | 17.38 | 0.00 | 45.50 | |
Maximum of Months | 389.17 | 0.83 | 0.80 | 926.21 | 19.25 | 28.67 | 415.67 | 400.61 | 23.09 | 229.83 | 370.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.82 | 0.80 | 01-JAN-08:09 | 389.29 | 14.73 | 0.00 | 221.83 | 187.75 | 18.15 | 0.00 | 90.67 |
February | 216.00 | 0.82 | 0.80 | 01-FEB-08:09 | 400.15 | 15.43 | 0.00 | 241.33 | 205.15 | 18.91 | 0.00 | 130.83 |
March | 275.00 | 0.81 | 0.80 | 01-MAR-06:00 | 548.62 | 16.81 | 0.00 | 321.50 | 264.58 | 20.07 | 4.17 | 221.67 |
April | 261.17 | 0.81 | 0.80 | 01-APR-06:10 | 604.45 | 17.42 | 0.00 | 351.83 | 291.52 | 20.66 | 38.67 | 284.67 |
May | 372.00 | 0.80 | 0.80 | 01-MAY-05:40 | 830.09 | 18.13 | 0.00 | 415.17 | 370.82 | 22.04 | 179.17 | 363.00 |
June | 351.83 | 0.80 | 0.80 | 01-JUN-04:00 | 921.60 | 19.25 | 28.67 | 407.50 | 400.61 | 23.09 | 228.50 | 369.67 |
July | 365.17 | 0.80 | 0.80 | 01-JUL-04:00 | 926.21 | 18.18 | 0.00 | 415.67 | 399.60 | 22.73 | 229.83 | 370.17 |
August | 389.17 | 0.81 | 0.80 | 01-AUG-05:19 | 734.14 | 17.87 | 0.00 | 385.33 | 339.72 | 21.11 | 159.67 | 348.50 |
September | 285.33 | 0.81 | 0.80 | 01-SEP-05:00 | 553.92 | 17.03 | 0.00 | 329.00 | 270.67 | 20.30 | 12.00 | 253.67 |
October | 305.50 | 0.81 | 0.80 | 01-OCT-14:39 | 501.04 | 16.58 | 0.00 | 296.83 | 256.74 | 19.96 | 0.00 | 229.83 |
November | 240.83 | 0.81 | 0.80 | 01-NOV-07:10 | 437.44 | 15.29 | 0.00 | 244.67 | 205.09 | 18.62 | 0.00 | 130.50 |
December | 211.17 | 0.83 | 0.80 | 01-DEC-08:09 | 308.28 | 13.80 | 0.00 | 210.00 | 154.95 | 17.38 | 0.00 | 45.50 |
Annual Sum or Average | 3472.67 | 0.81 | 636.79 | 17.01 | 28.67 | 3840.67 | 295.30 | 20.59 | 852.00 | 2838.67 | ||
Minimum of Months | 199.50 | 0.80 | 0.80 | 308.28 | 13.80 | 0.00 | 210.00 | 154.95 | 17.38 | 0.00 | 45.50 | |
Maximum of Months | 389.17 | 0.83 | 0.80 | 926.21 | 19.25 | 28.67 | 415.67 | 400.61 | 23.09 | 229.83 | 370.17 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106846E+09 | 2958.82 | 10-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145281E+10 | 4508.33 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213097E+10 | 4506.41 | 18-JUN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.869381E+09 | 3263.44 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16473280.89 | 1329.66 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457647E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213097E+10 | 4508.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326882E+10 | 2642.93 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267479E+10 | 2642.97 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189632E+10 | 1882.87 | 18-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125665E+10 | 1509.53 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.681326E+09 | 985.14 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.210114E+09 | 565.16 | 07-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45487191.04 | 466.39 | 01-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24116531.97 | 378.27 | 07-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286547E+09 | 787.71 | 27-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317587E+09 | 1062.71 | 29-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163814E+10 | 1968.68 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256360E+10 | 2043.42 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148635E+11 | |||||||
Minimum of Months | 24116531.97 | 378.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326882E+10 | 2642.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181162E+09 | 605.09 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134413E+09 | 533.19 | 06-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20884892.82 | 348.66 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8877953.03 | 203.93 | 16-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11528135.86 | 163.56 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5706100.41 | 183.86 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6903549.89 | 187.79 | 17-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17113333.18 | 378.03 | 26-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70308474.26 | 431.45 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456897E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181162E+09 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134798E+10 | 1261.58 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128656E+10 | 1232.61 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623995E+09 | 774.23 | 18-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.243969E+09 | 480.30 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37936767.67 | 233.82 | 04-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2065144.33 | 114.64 | 26-SEP-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 507080.15 | 56.92 | 31-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386691E+09 | 819.44 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871137E+09 | 838.66 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480084E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134798E+10 | 1261.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122168E+10 | 903.94 | 02-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114595E+10 | 903.94 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668010E+09 | 587.10 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309412E+09 | 400.97 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67700858.05 | 208.14 | 04-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 484131.26 | 23.12 | 06-JUN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7870818.16 | 134.95 | 26-SEP-15:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15475033.31 | 201.80 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458870E+09 | 613.40 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.897892E+09 | 670.56 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479335E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122168E+10 | 903.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715579E+09 | 3818.65 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680175E+09 | 3818.64 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685315E+09 | 3764.75 | 27-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129485E+10 | 5664.60 | 28-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.263861E+10 | 6436.28 | 30-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.541043E+10 | 7851.68 | 22-JUN-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.610307E+10 | 7851.42 | 24-JUL-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.569908E+10 | 7851.41 | 11-AUG-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.466782E+10 | 7851.42 | 14-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220959E+10 | 7268.70 | 06-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631664E+09 | 4125.22 | 10-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.639706E+09 | 3063.39 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313759E+11 | |||||||
Minimum of Months | 0.631664E+09 | 3063.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610307E+10 | 7851.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242959E+10 | 6189.19 | 14-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158771E+10 | 5437.34 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959925E+09 | 4567.42 | 16-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.528239E+09 | 3448.87 | 21-APR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351848E+09 | 2640.26 | 24-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174918E+09 | 1890.12 | 13-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17697551.02 | 1174.86 | 24-JUL-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10667380.13 | 1333.54 | 07-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172053E+09 | 2273.21 | 18-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62890076.07 | 1677.65 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.625464E+09 | 3777.51 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149809E+10 | 5153.32 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.841909E+10 | |||||||
Minimum of Months | 10667380.13 | 1174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242959E+10 | 6189.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138986E+10 | 10118.64 | 08-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.832150E+09 | 7884.94 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147942E+09 | 5205.54 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34230790.37 | 2573.49 | 30-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66423532.83 | 2472.39 | 24-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88249557.16 | 3246.32 | 12-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88276335.21 | 3277.99 | 17-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77326173.56 | 5426.13 | 26-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543736E+09 | 7048.83 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326820E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138986E+10 | 10118.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.463061E+10 | 6703.79 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391318E+10 | 6702.94 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200443E+10 | 6522.03 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.921744E+09 | 6190.12 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112118E+09 | 4355.93 | 30-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6072526.72 | 4506.86 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3189218.25 | 3376.36 | 17-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4851249.17 | 3849.47 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23242851.92 | 4859.84 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259852E+09 | 4333.04 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213786E+10 | 6445.50 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366411E+10 | 6667.76 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176813E+11 | |||||||
Minimum of Months | 3189218.25 | 3376.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.463061E+10 | 6703.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.541691E+10 | 6686.15 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486256E+10 | 6685.34 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245278E+10 | 6511.47 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104288E+10 | 6181.33 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120832E+09 | 4723.82 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5765656.15 | 4645.07 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2764308.83 | 3293.24 | 11-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4577458.18 | 4357.02 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34365973.29 | 4061.36 | 24-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.459661E+09 | 5987.54 | 28-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273144E+10 | 6539.47 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451397E+10 | 6650.25 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216485E+11 | |||||||
Minimum of Months | 2764308.83 | 3293.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.541691E+10 | 6686.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150756E+11 | 38241.54 | 02-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151152E+11 | 38484.57 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424923E+10 | 36050.03 | 17-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694562E+09 | 29723.46 | 19-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85764146.66 | 33506.71 | 03-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20702123.15 | 17597.16 | 11-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 151625.27 | 1516.25 | 16-JUL-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8121871.23 | 16032.29 | 20-AUG-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46250850.56 | 27851.55 | 23-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347842E+09 | 33485.09 | 30-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.414344E+10 | 36099.95 | 22-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.985318E+10 | 36949.01 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496400E+11 | |||||||
Minimum of Months | 151625.27 | 1516.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151152E+11 | 38484.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461082E+10 | 6459.71 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382829E+10 | 6457.66 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207883E+10 | 6268.75 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914363E+09 | 5971.67 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125641E+09 | 3968.42 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3432092.22 | 2860.89 | 16-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 294171.46 | 1244.58 | 24-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 461085.01 | 1938.49 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19388992.42 | 3223.70 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280606E+09 | 3833.12 | 29-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203164E+10 | 6207.94 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362031E+10 | 6425.00 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175141E+11 | |||||||
Minimum of Months | 294171.46 | 1244.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461082E+10 | 6459.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.538929E+10 | 6459.52 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.476475E+10 | 6457.50 | 05-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255244E+10 | 6287.57 | 17-MAR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103635E+10 | 5985.34 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138583E+09 | 4601.00 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3443329.03 | 2835.15 | 11-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358729.97 | 1333.82 | 24-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 590290.62 | 2587.37 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31218860.21 | 4306.85 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474644E+09 | 4549.47 | 10-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255240E+10 | 6271.06 | 23-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443271E+10 | 6424.87 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213768E+11 | |||||||
Minimum of Months | 358729.97 | 1333.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.538929E+10 | 6459.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144572E+11 | 8234.81 | 14-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121113E+11 | 8235.45 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.893185E+10 | 7134.69 | 17-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.604126E+10 | 6079.46 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365042E+10 | 4715.56 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171925E+10 | 3549.05 | 12-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.735834E+09 | 3397.71 | 01-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411777E+09 | 2531.67 | 07-AUG-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231305E+10 | 4228.32 | 27-SEP-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287659E+10 | 4714.92 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877578E+10 | 7422.58 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123313E+11 | 7413.30 | 31-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743557E+11 | |||||||
Minimum of Months | 0.411777E+09 | 2531.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144572E+11 | 8235.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158699E+10 | 1936.70 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135780E+10 | 1936.44 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720258E+09 | 1896.53 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339745E+09 | 1812.54 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44748327.58 | 1177.95 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1469939.07 | 1033.74 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 493651.60 | 643.59 | 11-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1106555.89 | 1112.16 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8857301.50 | 1045.53 | 23-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112755E+09 | 1260.21 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776741E+09 | 1883.71 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129538E+10 | 1926.25 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624635E+10 | |||||||
Minimum of Months | 493651.60 | 643.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158699E+10 | 1936.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183112E+10 | 1933.14 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164595E+10 | 1932.88 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.862845E+09 | 1893.09 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379500E+09 | 1809.33 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48122447.55 | 1330.06 | 03-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1432279.56 | 1052.47 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 422436.84 | 652.12 | 11-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1017998.30 | 1120.37 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13545723.57 | 1170.87 | 25-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184413E+09 | 1795.52 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.970918E+09 | 1890.99 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156617E+10 | 1922.75 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.750547E+10 | |||||||
Minimum of Months | 422436.84 | 652.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183112E+10 | 1933.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.456154E+10 | 8726.25 | 14-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343952E+10 | 8688.38 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189376E+10 | 8456.41 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882449E+09 | 8039.38 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77822621.91 | 5141.75 | 23-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5121612.17 | 3458.65 | 01-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2289202.47 | 2244.75 | 05-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2977483.80 | 4545.71 | 08-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10911979.57 | 4261.96 | 23-SEP-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119468E+09 | 4394.28 | 28-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151036E+10 | 8196.28 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327820E+10 | 8491.85 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157844E+11 | |||||||
Minimum of Months | 2289202.47 | 2244.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.456154E+10 | 8726.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1748858.41 | 322.57 | 30-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1614584.55 | 322.57 | 24-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 870589.44 | 212.75 | 27-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1702524.44 | 392.07 | 22-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5936556.83 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1748858.41 | 392.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595135E+10 | 5094.36 | 02-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517228E+10 | 5094.37 | 06-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284739E+10 | 3566.63 | 23-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128500E+10 | 2535.46 | 02-APR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281926E+09 | 1664.24 | 01-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 587094.39 | 128.00 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118556E+09 | 1058.32 | 24-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452059E+09 | 2346.56 | 29-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278587E+10 | 3664.99 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470333E+10 | 3531.84 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235983E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595135E+10 | 5094.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549704E+11 | 98766.21 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485081E+11 | 108919.34 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249717E+11 | 91317.62 | 03-MAR-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350578E+11 | 91342.71 | 22-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187463E+11 | 88838.98 | 01-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201207E+09 | 10349.69 | 10-JUN-10:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26013089.52 | 7921.42 | 11-JUL-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146227E+09 | 23928.44 | 25-AUG-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.458805E+10 | 72972.29 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304110E+11 | 95360.80 | 07-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.427282E+11 | 94450.95 | 16-NOV-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189801E+11 | 89586.50 | 17-DEC-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279335E+12 | |||||||
Minimum of Months | 26013089.52 | 7921.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.549704E+11 | 108919.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151991E+10 | 5780.68 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172416E+10 | 6499.83 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126425E+09 | 2705.64 | 17-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1251.68 | 0.24 | 28-APR-01:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18418.98 | 17.79 | 30-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9283.65 | 0.25 | 14-JUN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6498.93 | 0.25 | 12-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17502.57 | 34.87 | 08-AUG-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9321.47 | 0.25 | 07-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7958.86 | 4.71 | 12-OCT-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137014E+09 | 1717.57 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194698E+09 | 3437.67 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370227E+10 | |||||||
Minimum of Months | 1251.68 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172416E+10 | 6499.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28898596.61 | 28526698.20 | 12061.86 | 17-JAN-16:02 | 12061.86 | 0.00 |
February | 0.00 | 0.00 | 73258719.12 | 73146591.11 | 12062.55 | 20-FEB-16:02 | 12062.55 | 0.00 |
March | 0.00 | 0.00 | 0.575742E+09 | 0.512410E+09 | 14025.03 | 27-MAR-15:01 | 11081.66 | 0.04 |
April | 0.00 | 0.00 | 0.151121E+10 | 0.102333E+10 | 12950.50 | 09-APR-08:62 | 10303.54 | 0.28 |
May | 0.00 | 0.00 | 0.326378E+10 | 0.208739E+10 | 15318.34 | 18-MAY-15:01 | 10067.00 | 0.56 |
June | 0.00 | 0.00 | 0.685726E+10 | 0.362071E+10 | 17968.51 | 25-JUN-08:62 | 9562.76 | 0.87 |
July | 0.00 | 0.00 | 0.948181E+10 | 0.487793E+10 | 18471.86 | 21-JUL-08:62 | 9543.21 | 0.94 |
August | 0.00 | 0.00 | 0.944617E+10 | 0.539345E+10 | 17366.87 | 03-AUG-08:62 | 10331.14 | 0.94 |
September | 0.00 | 0.00 | 0.515818E+10 | 0.273573E+10 | 18905.12 | 22-SEP-18:02 | 8408.62 | 0.81 |
October | 0.00 | 0.00 | 0.317581E+10 | 0.184728E+10 | 15285.66 | 25-OCT-08:62 | 9150.54 | 0.49 |
November | 0.00 | 0.00 | 0.264122E+09 | 0.193131E+09 | 12184.51 | 02-NOV-15:01 | 12184.51 | 0.07 |
December | 0.00 | 0.00 | 39052614.98 | 38354453.11 | 12056.01 | 17-DEC-16:01 | 12056.01 | 0.00 |
Annual Sum or Average | 0.398753E+11 | 0.224314E+11 | 0.42 | |||||
Minimum of Months | 0.00 | 0.00 | 28898596.61 | 28526698.20 | 12056.01 | 8408.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.948181E+10 | 0.539345E+10 | 18905.12 | 12184.51 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4599852.99 | 4145933.98 | 10010.52 | 17-JAN-16:02 | 10010.52 | 0.00 |
February | 0.00 | 0.00 | 12354744.52 | 12294039.59 | 11094.62 | 20-FEB-16:02 | 11094.62 | 0.00 |
March | 0.00 | 0.00 | 0.305720E+09 | 0.265946E+09 | 13567.97 | 27-MAR-15:01 | 10552.58 | 0.02 |
April | 0.00 | 0.00 | 0.117028E+10 | 0.793289E+09 | 13337.65 | 09-APR-15:01 | 10738.98 | 0.23 |
May | 0.00 | 0.00 | 0.305439E+10 | 0.194283E+10 | 15075.07 | 18-MAY-15:01 | 9851.62 | 0.55 |
June | 0.00 | 0.00 | 0.668157E+10 | 0.352507E+10 | 17443.03 | 27-JUN-08:62 | 9363.47 | 0.86 |
July | 0.00 | 0.00 | 0.921357E+10 | 0.471333E+10 | 18211.12 | 21-JUL-08:62 | 9388.36 | 0.94 |
August | 0.00 | 0.00 | 0.872785E+10 | 0.487818E+10 | 17131.24 | 16-AUG-08:62 | 9894.14 | 0.94 |
September | 0.00 | 0.00 | 0.422205E+10 | 0.214162E+10 | 18607.19 | 22-SEP-18:02 | 8252.98 | 0.74 |
October | 0.00 | 0.00 | 0.181993E+10 | 0.968959E+09 | 14890.35 | 23-OCT-15:01 | 9374.46 | 0.38 |
November | 0.00 | 0.00 | 62587473.09 | 50858003.75 | 11910.38 | 02-NOV-15:01 | 11910.38 | 0.02 |
December | 0.00 | 0.00 | 2169409.53 | 1903519.71 | 8405.47 | 17-DEC-16:01 | 8405.47 | 0.00 |
Annual Sum or Average | 0.352771E+11 | 0.192984E+11 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 2169409.53 | 1903519.71 | 8405.47 | 8252.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.921357E+10 | 0.487818E+10 | 18607.19 | 11910.38 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2236953.90 | 2236953.90 | 1084.73 | 31-JAN-14:40 | 1084.73 | 0.00 |
February | 0.00 | 0.00 | 0.117233E+10 | 0.117233E+10 | 21007.74 | 03-FEB-12:30 | 21007.74 | 0.00 |
March | 0.00 | 0.00 | 0.376560E+10 | 0.335736E+10 | 26384.00 | 03-MAR-13:30 | 26384.00 | 0.04 |
April | 0.00 | 0.00 | 0.961636E+10 | 0.603928E+10 | 35586.41 | 07-APR-12:30 | 31043.06 | 0.27 |
May | 0.00 | 0.00 | 0.202198E+11 | 0.118869E+11 | 25225.62 | 29-MAY-19:10 | 15904.72 | 0.57 |
June | 0.00 | 0.00 | 0.364208E+11 | 0.174730E+11 | 32608.45 | 19-JUN-19:10 | 23924.66 | 0.96 |
July | 0.00 | 0.00 | 0.501910E+11 | 0.252493E+11 | 36657.69 | 08-JUL-08:00 | 24053.29 | 1.00 |
August | 0.00 | 0.00 | 0.541123E+11 | 0.313922E+11 | 37733.59 | 16-AUG-12:30 | 28911.71 | 1.00 |
September | 0.00 | 0.00 | 0.408324E+11 | 0.247547E+11 | 44538.11 | 14-SEP-13:30 | 36173.08 | 0.89 |
October | 0.00 | 0.00 | 0.398803E+11 | 0.296943E+11 | 48994.52 | 04-OCT-12:10 | 38698.53 | 0.58 |
November | 0.00 | 0.00 | 0.979186E+10 | 0.852904E+10 | 42776.57 | 02-NOV-12:30 | 42776.57 | 0.10 |
December | 0.00 | 0.00 | 0.356727E+10 | 0.356727E+10 | 32325.54 | 17-DEC-13:00 | 32325.54 | 0.00 |
Annual Sum or Average | 0.269572E+12 | 0.163118E+12 | 0.45 | |||||
Minimum of Months | 0.00 | 0.00 | 2236953.90 | 2236953.90 | 1084.73 | 1084.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.541123E+11 | 0.313922E+11 | 48994.52 | 42776.57 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.890610E+09 | 0.540329E+09 | 66059.71 | 24-JAN-09:02 | 59432.58 | 0.04 |
February | 0.00 | 0.00 | 0.525304E+09 | 0.498444E+09 | 65192.12 | 20-FEB-09:02 | 65192.12 | 0.01 |
March | 0.00 | 0.00 | 0.528552E+10 | 0.403005E+10 | 74959.28 | 27-MAR-15:01 | 64186.48 | 0.14 |
April | 0.00 | 0.00 | 0.166632E+11 | 0.114293E+11 | 76862.12 | 08-APR-15:01 | 69755.06 | 0.40 |
May | 0.00 | 0.00 | 0.359183E+11 | 0.246562E+11 | 87644.68 | 31-MAY-18:02 | 64434.69 | 0.60 |
June | 0.00 | 0.00 | 0.594178E+11 | 0.352983E+11 | 108622.57 | 27-JUN-08:62 | 53737.56 | 0.79 |
July | 0.00 | 0.00 | 0.809628E+11 | 0.469154E+11 | 114964.48 | 21-JUL-08:62 | 52839.51 | 0.88 |
August | 0.00 | 0.00 | 0.700013E+11 | 0.427145E+11 | 106825.25 | 31-AUG-18:02 | 56278.30 | 0.86 |
September | 0.00 | 0.00 | 0.445069E+11 | 0.263300E+11 | 114826.38 | 22-SEP-18:02 | 48582.15 | 0.72 |
October | 0.00 | 0.00 | 0.237591E+11 | 0.140727E+11 | 88618.28 | 06-OCT-08:62 | 53389.00 | 0.45 |
November | 0.00 | 0.00 | 0.667967E+10 | 0.451366E+10 | 78491.06 | 10-NOV-09:02 | 55796.67 | 0.22 |
December | 0.00 | 0.00 | 0.915113E+09 | 0.757254E+09 | 64272.30 | 10-DEC-09:02 | 64272.30 | 0.02 |
Annual Sum or Average | 0.345525E+12 | 0.211756E+12 | 0.43 | |||||
Minimum of Months | 0.00 | 0.00 | 0.525304E+09 | 0.498444E+09 | 64272.30 | 48582.15 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.809628E+11 | 0.469154E+11 | 114964.48 | 69755.06 | 0.88 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 40148841.17 | 37815322.70 | 9965.84 | 17-JAN-16:02 | 9965.84 | 0.00 |
February | 0.00 | 0.00 | 68849771.67 | 68647350.92 | 10573.26 | 19-FEB-09:02 | 10573.26 | 0.00 |
March | 0.00 | 0.00 | 0.434088E+09 | 0.388378E+09 | 12384.20 | 27-MAR-15:01 | 9542.83 | 0.04 |
April | 0.00 | 0.00 | 0.149384E+10 | 0.973797E+09 | 11799.46 | 09-APR-15:01 | 10065.00 | 0.31 |
May | 0.00 | 0.00 | 0.341025E+10 | 0.219347E+10 | 13679.09 | 18-MAY-15:01 | 9215.91 | 0.59 |
June | 0.00 | 0.00 | 0.639369E+10 | 0.334963E+10 | 15612.64 | 21-JUN-18:02 | 8655.80 | 0.88 |
July | 0.00 | 0.00 | 0.933148E+10 | 0.483462E+10 | 16469.24 | 21-JUL-08:62 | 8734.30 | 0.96 |
August | 0.00 | 0.00 | 0.934717E+10 | 0.533349E+10 | 15539.69 | 31-AUG-18:02 | 9074.05 | 0.96 |
September | 0.00 | 0.00 | 0.519553E+10 | 0.281071E+10 | 17060.67 | 22-SEP-18:02 | 7543.45 | 0.83 |
October | 0.00 | 0.00 | 0.300267E+10 | 0.172448E+10 | 13827.39 | 25-OCT-08:62 | 9196.64 | 0.50 |
November | 0.00 | 0.00 | 0.373008E+09 | 0.274291E+09 | 10986.77 | 02-NOV-15:01 | 10986.77 | 0.08 |
December | 0.00 | 0.00 | 82578896.92 | 78491768.07 | 10654.69 | 17-DEC-09:02 | 10654.69 | 0.00 |
Annual Sum or Average | 0.391733E+11 | 0.220678E+11 | 0.43 | |||||
Minimum of Months | 0.00 | 0.00 | 40148841.17 | 37815322.70 | 9965.84 | 7543.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.934717E+10 | 0.533349E+10 | 17060.67 | 10986.77 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3109490.32 | 1968164.69 | 3042.16 | 19-JAN-09:02 | 2515.96 | 0.00 |
February | 0.00 | 0.00 | 12006653.00 | 11933693.82 | 10059.06 | 19-FEB-09:02 | 10059.06 | 0.00 |
March | 0.00 | 0.00 | 0.195297E+09 | 0.170525E+09 | 12006.77 | 27-MAR-15:01 | 9053.76 | 0.02 |
April | 0.00 | 0.00 | 0.114106E+10 | 0.726408E+09 | 12109.88 | 09-APR-15:01 | 9787.05 | 0.26 |
May | 0.00 | 0.00 | 0.319350E+10 | 0.204727E+10 | 13608.62 | 18-MAY-15:01 | 9149.18 | 0.57 |
June | 0.00 | 0.00 | 0.620975E+10 | 0.324188E+10 | 15507.62 | 21-JUN-18:02 | 8606.13 | 0.87 |
July | 0.00 | 0.00 | 0.906322E+10 | 0.466828E+10 | 16385.43 | 21-JUL-08:62 | 8667.90 | 0.95 |
August | 0.00 | 0.00 | 0.862105E+10 | 0.480360E+10 | 15653.95 | 16-AUG-08:62 | 8971.00 | 0.96 |
September | 0.00 | 0.00 | 0.422525E+10 | 0.217573E+10 | 16944.32 | 22-SEP-18:02 | 7470.04 | 0.77 |
October | 0.00 | 0.00 | 0.160547E+10 | 0.811951E+09 | 13923.45 | 25-OCT-08:62 | 9032.19 | 0.38 |
November | 0.00 | 0.00 | 0.102832E+09 | 65364330.85 | 10447.21 | 11-NOV-09:02 | 9676.62 | 0.04 |
December | 0.00 | 0.00 | 6378061.03 | 5557952.18 | 8590.27 | 17-DEC-09:02 | 8590.27 | 0.00 |
Annual Sum or Average | 0.343789E+11 | 0.187305E+11 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 3109490.32 | 1968164.69 | 3042.16 | 2515.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.906322E+10 | 0.480360E+10 | 16944.32 | 10059.06 | 0.96 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7322483.58 | 7125752.62 | 3163.05 | 17-JAN-16:02 | 3163.05 | 0.00 |
February | 0.00 | 0.00 | 18855955.48 | 18832654.23 | 3163.23 | 20-FEB-16:02 | 3163.23 | 0.00 |
March | 0.00 | 0.00 | 0.154485E+09 | 0.137354E+09 | 3699.86 | 27-MAR-15:01 | 2893.34 | 0.04 |
April | 0.00 | 0.00 | 0.430432E+09 | 0.301602E+09 | 3514.50 | 09-APR-08:62 | 2593.02 | 0.26 |
May | 0.00 | 0.00 | 0.970985E+09 | 0.649124E+09 | 4003.59 | 18-MAY-15:01 | 2662.28 | 0.57 |
June | 0.00 | 0.00 | 0.205365E+10 | 0.114781E+10 | 4811.51 | 25-JUN-08:62 | 2444.06 | 0.89 |
July | 0.00 | 0.00 | 0.283815E+10 | 0.156601E+10 | 4926.34 | 21-JUL-08:62 | 2449.15 | 0.96 |
August | 0.00 | 0.00 | 0.278637E+10 | 0.169614E+10 | 4644.18 | 27-AUG-08:62 | 2478.29 | 0.95 |
September | 0.00 | 0.00 | 0.151653E+10 | 0.857171E+09 | 5089.28 | 22-SEP-18:02 | 2149.37 | 0.81 |
October | 0.00 | 0.00 | 0.867477E+09 | 0.522918E+09 | 4091.01 | 25-OCT-08:62 | 2301.91 | 0.47 |
November | 0.00 | 0.00 | 60075281.65 | 45198645.53 | 3195.13 | 02-NOV-15:01 | 3195.13 | 0.05 |
December | 0.00 | 0.00 | 7704635.83 | 7573338.06 | 3162.22 | 17-DEC-16:01 | 3162.22 | 0.00 |
Annual Sum or Average | 0.117120E+11 | 0.695686E+10 | 0.42 | |||||
Minimum of Months | 0.00 | 0.00 | 7322483.58 | 7125752.62 | 3162.22 | 2149.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283815E+10 | 0.169614E+10 | 5089.28 | 3195.13 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 667528.07 | 538285.41 | 1620.68 | 17-JAN-16:02 | 1620.68 | 0.00 |
February | 0.00 | 0.00 | 1261233.35 | 1255692.62 | 2824.38 | 20-FEB-16:02 | 2824.38 | 0.00 |
March | 0.00 | 0.00 | 75450831.41 | 64568439.28 | 3608.24 | 27-MAR-15:01 | 2790.60 | 0.02 |
April | 0.00 | 0.00 | 0.334408E+09 | 0.232217E+09 | 3441.28 | 09-APR-08:62 | 2519.74 | 0.22 |
May | 0.00 | 0.00 | 0.911303E+09 | 0.606890E+09 | 3949.65 | 18-MAY-15:01 | 2616.90 | 0.55 |
June | 0.00 | 0.00 | 0.200751E+10 | 0.111954E+10 | 4671.49 | 27-JUN-08:62 | 2392.20 | 0.89 |
July | 0.00 | 0.00 | 0.276804E+10 | 0.151867E+10 | 4854.27 | 21-JUL-08:62 | 2409.49 | 0.96 |
August | 0.00 | 0.00 | 0.259411E+10 | 0.154363E+10 | 4605.62 | 16-AUG-08:62 | 2522.26 | 0.95 |
September | 0.00 | 0.00 | 0.125494E+10 | 0.670509E+09 | 5013.64 | 22-SEP-18:02 | 2111.99 | 0.74 |
October | 0.00 | 0.00 | 0.496666E+09 | 0.270689E+09 | 3974.09 | 25-OCT-08:62 | 2174.69 | 0.36 |
November | 0.00 | 0.00 | 13165788.14 | 10980764.58 | 3101.07 | 02-NOV-15:01 | 3101.07 | 0.01 |
December | 0.00 | 0.00 | 681492.19 | 553406.99 | 955.47 | 17-DEC-16:01 | 955.47 | 0.00 |
Annual Sum or Average | 0.104582E+11 | 0.604003E+10 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 667528.07 | 538285.41 | 955.47 | 955.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.276804E+10 | 0.154363E+10 | 5013.64 | 3101.07 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.830357E+09 | 0.827363E+09 | 13053.94 | 17-JAN-16:02 | 13053.94 | 0.00 |
February | 0.00 | 0.00 | 0.110698E+10 | 0.110672E+10 | 13054.62 | 20-FEB-16:02 | 13054.62 | 0.00 |
March | 0.00 | 0.00 | 0.188435E+10 | 0.170407E+10 | 14332.30 | 27-MAR-15:01 | 12470.21 | 0.09 |
April | 0.00 | 0.00 | 0.270132E+10 | 0.186882E+10 | 14068.55 | 27-APR-15:01 | 12497.31 | 0.36 |
May | 0.00 | 0.00 | 0.493860E+10 | 0.312372E+10 | 16620.27 | 31-MAY-18:02 | 11567.21 | 0.66 |
June | 0.00 | 0.00 | 0.101064E+11 | 0.558266E+10 | 20143.96 | 27-JUN-08:62 | 9748.80 | 0.88 |
July | 0.00 | 0.00 | 0.149035E+11 | 0.848217E+10 | 20916.36 | 21-JUL-08:62 | 9819.33 | 0.95 |
August | 0.00 | 0.00 | 0.147463E+11 | 0.942605E+10 | 19634.85 | 03-AUG-08:62 | 10718.32 | 0.95 |
September | 0.00 | 0.00 | 0.101484E+11 | 0.644305E+10 | 21403.11 | 22-SEP-18:02 | 8711.62 | 0.87 |
October | 0.00 | 0.00 | 0.858906E+10 | 0.626811E+10 | 17142.10 | 05-OCT-18:02 | 10883.21 | 0.58 |
November | 0.00 | 0.00 | 0.222805E+10 | 0.186995E+10 | 14716.22 | 10-NOV-09:02 | 10121.40 | 0.18 |
December | 0.00 | 0.00 | 0.156655E+10 | 0.155860E+10 | 13054.31 | 17-DEC-09:02 | 13054.31 | 0.01 |
Annual Sum or Average | 0.737498E+11 | 0.482613E+11 | 0.46 | |||||
Minimum of Months | 0.00 | 0.00 | 0.830357E+09 | 0.827363E+09 | 13053.94 | 8711.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149035E+11 | 0.942605E+10 | 21403.11 | 13054.62 | 0.95 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.580398E+10 | 0.506547E+10 | 199471.62 | 27-MAR-13:00 | 131133.96 | 0.02 |
April | 0.00 | 0.00 | 0.467937E+11 | 0.454914E+11 | 246203.80 | 09-APR-11:00 | 152334.25 | 0.17 |
May | 0.00 | 0.00 | 0.176930E+12 | 0.142369E+12 | 317327.60 | 31-MAY-17:15 | 166751.25 | 0.44 |
June | 0.00 | 0.00 | 0.622615E+12 | 0.354073E+12 | 504991.96 | 24-JUN-18:03 | 175920.69 | 0.91 |
July | 0.00 | 0.00 | 0.889791E+12 | 0.471676E+12 | 513583.93 | 05-JUL-20:20 | 192900.19 | 1.00 |
August | 0.00 | 0.00 | 0.736942E+12 | 0.459243E+12 | 485447.99 | 03-AUG-20:00 | 218135.01 | 0.98 |
September | 0.00 | 0.00 | 0.446440E+12 | 0.291767E+12 | 482731.89 | 22-SEP-17:40 | 166083.79 | 0.81 |
October | 0.00 | 0.00 | 0.180362E+12 | 0.106602E+12 | 315951.04 | 25-OCT-09:30 | 159346.09 | 0.45 |
November | 0.00 | 0.00 | 0.674918E+10 | 0.579243E+10 | 123617.44 | 10-NOV-08:00 | 45655.16 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.311243E+13 | 0.188208E+13 | 0.40 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.889791E+12 | 0.471676E+12 | 513583.93 | 218135.01 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.267193E+09 | 0.233221E+09 | 19217.11 | 27-MAR-13:00 | 12683.11 | 0.01 |
April | 0.00 | 0.00 | 0.214739E+10 | 0.211170E+10 | 20012.53 | 09-APR-10:00 | 13721.29 | 0.10 |
May | 0.00 | 0.00 | 0.886479E+10 | 0.743665E+10 | 28281.36 | 31-MAY-08:61 | 16855.08 | 0.29 |
June | 0.00 | 0.00 | 0.414139E+11 | 0.235291E+11 | 46837.99 | 24-JUN-18:03 | 16308.83 | 0.72 |
July | 0.00 | 0.00 | 0.585410E+11 | 0.319923E+11 | 46341.16 | 21-JUL-08:62 | 18223.12 | 0.79 |
August | 0.00 | 0.00 | 0.477072E+11 | 0.303814E+11 | 42954.91 | 05-AUG-18:02 | 17636.81 | 0.79 |
September | 0.00 | 0.00 | 0.280954E+11 | 0.187665E+11 | 46319.05 | 14-SEP-08:62 | 16578.81 | 0.62 |
October | 0.00 | 0.00 | 0.988544E+10 | 0.572323E+10 | 30498.40 | 03-OCT-15:02 | 16949.06 | 0.30 |
November | 0.00 | 0.00 | 0.209433E+09 | 0.180063E+09 | 7314.80 | 10-NOV-08:00 | 2643.17 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.197132E+12 | 0.120354E+12 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.585410E+11 | 0.319923E+11 | 46837.99 | 18223.12 | 0.79 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 28261.68 | 57871.66 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28527.77 | 57954.76 | 07-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27920.99 | 57484.26 | 02-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26481.66 | 55095.37 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 24580.70 | 51982.23 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22717.71 | 48204.76 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21426.90 | 45030.06 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21035.83 | 44052.74 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21781.72 | 46083.30 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 23404.67 | 49590.96 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25313.57 | 53266.99 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27057.52 | 56196.89 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24854.67 | ||||
Minimum of Months | 0.00 | 0.00 | 21035.83 | 44052.74 | ||
Maximum of Months | 0.00 | 0.00 | 28527.77 | 57954.76 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47972.58 | 194455.84 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46694.76 | 197743.25 | 06-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 21512.52 | 132651.35 | 17-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19894.55 | 117087.28 | 14-APR-15:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10594.52 | 87859.20 | 01-MAY-22:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3794.80 | 47890.43 | 06-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2869.64 | 26520.74 | 24-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2327.06 | 35739.97 | 07-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 4735.74 | 78877.01 | 24-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 14214.00 | 116894.63 | 09-OCT-08:06 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28512.83 | 139165.33 | 27-NOV-16:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27642.40 | 145866.88 | 31-DEC-19:02 |
Annual Sum or Average | 0.00 | 19059.47 | ||||
Minimum of Months | 0.00 | 0.00 | 2327.06 | 26520.74 | ||
Maximum of Months | 0.00 | 0.00 | 47972.58 | 197743.25 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1167.52 | 35863.61 | 19-JAN-19:02 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1888.49 | 48968.56 | 19-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 8261.55 | 299987.71 | 27-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 34338.25 | 349799.87 | 07-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 100235.03 | 513272.65 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 311532.84 | 770321.74 | 24-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 427479.18 | 734404.09 | 14-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 363162.37 | 695940.22 | 03-AUG-20:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 230954.54 | 737977.72 | 22-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 104552.59 | 537346.45 | 24-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 11671.77 | 193781.81 | 02-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3045.34 | 53104.34 | 20-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 134117.29 | 0.00 | ||||
Minimum of Months | 1167.52 | 35863.61 | 0.00 | 0.00 | ||
Maximum of Months | 427479.18 | 770321.74 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270916E+10 | 0.69 | 1298.89 | 01-JAN-19:13 | 0.88 |
February | 0.244698E+10 | 0.70 | 1298.89 | 01-FEB-19:02 | 0.88 |
March | 0.270916E+10 | 0.69 | 1298.89 | 04-MAR-16:02 | 0.87 |
April | 0.262177E+10 | 0.69 | 1298.89 | 07-APR-15:25 | 0.87 |
May | 0.270916E+10 | 0.69 | 1298.89 | 11-MAY-15:30 | 0.87 |
June | 0.262177E+10 | 0.69 | 1298.89 | 02-JUN-18:15 | 0.88 |
July | 0.270916E+10 | 0.69 | 1298.89 | 01-JUL-16:00 | 0.87 |
August | 0.270916E+10 | 0.69 | 1298.89 | 01-AUG-15:30 | 0.87 |
September | 0.262177E+10 | 0.69 | 1298.89 | 03-SEP-15:25 | 0.87 |
October | 0.270916E+10 | 0.69 | 1298.89 | 14-OCT-15:15 | 0.87 |
November | 0.262177E+10 | 0.69 | 1298.89 | 03-NOV-15:05 | 0.88 |
December | 0.270916E+10 | 0.69 | 1298.89 | 01-DEC-09:02 | 0.88 |
Annual Sum or Average | 0.318982E+11 | 0.69 | |||
Minimum of Months | 0.244698E+10 | 0.69 | 1298.89 | 0.87 | |
Maximum of Months | 0.270916E+10 | 0.70 | 1298.89 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.385451E+11 | 0.92 | 20871.87 | 23-JAN-21:10 | 1.14 |
February | 0.348290E+11 | 0.92 | 20589.85 | 23-FEB-21:30 | 1.13 |
March | 0.394840E+11 | 0.93 | 21587.99 | 28-MAR-20:10 | 1.16 |
April | 0.380455E+11 | 0.92 | 21692.22 | 11-APR-20:10 | 1.18 |
May | 0.381053E+11 | 0.90 | 21769.75 | 01-MAY-21:00 | 1.17 |
June | 0.353781E+11 | 0.88 | 20819.31 | 22-JUN-19:00 | 1.13 |
July | 0.364013E+11 | 0.88 | 19033.16 | 11-JUL-18:03 | 1.07 |
August | 0.366231E+11 | 0.88 | 21050.65 | 24-AUG-20:20 | 1.14 |
September | 0.354162E+11 | 0.88 | 19885.39 | 29-SEP-20:10 | 1.10 |
October | 0.383315E+11 | 0.91 | 23494.90 | 30-OCT-21:00 | 1.23 |
November | 0.384025E+11 | 0.93 | 23360.69 | 01-NOV-21:00 | 1.22 |
December | 0.390187E+11 | 0.92 | 22017.97 | 04-DEC-22:00 | 1.17 |
Annual Sum or Average | 0.448580E+12 | 0.91 | |||
Minimum of Months | 0.348290E+11 | 0.88 | 19033.16 | 1.07 | |
Maximum of Months | 0.394840E+11 | 0.93 | 23494.90 | 1.23 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:03 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:03 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:05 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.350247E+09 | 0.44 | 713.71 | 01-JAN-09:02 | 0.58 |
February | 0.305537E+09 | 0.44 | 713.71 | 01-FEB-09:02 | 0.58 |
March | 0.221083E+09 | 0.42 | 713.71 | 01-MAR-16:01 | 0.58 |
April | 0.192685E+09 | 0.44 | 713.71 | 01-APR-08:62 | 0.57 |
May | 0.214846E+09 | 0.46 | 713.71 | 01-MAY-15:02 | 0.58 |
June | 0.329073E+09 | 0.51 | 713.71 | 01-JUN-08:62 | 0.57 |
July | 0.413141E+09 | 0.54 | 713.71 | 01-JUL-08:62 | 0.57 |
August | 0.437910E+09 | 0.54 | 713.71 | 01-AUG-08:62 | 0.57 |
September | 0.266815E+09 | 0.50 | 713.71 | 01-SEP-08:62 | 0.57 |
October | 0.209158E+09 | 0.48 | 713.71 | 02-OCT-15:02 | 0.57 |
November | 0.209572E+09 | 0.42 | 713.71 | 01-NOV-15:02 | 0.58 |
December | 0.296114E+09 | 0.43 | 713.71 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.344618E+10 | 0.47 | |||
Minimum of Months | 0.192685E+09 | 0.42 | 713.71 | 0.57 | |
Maximum of Months | 0.437910E+09 | 0.54 | 713.71 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401369E+09 | 0.46 | 702.66 | 01-JAN-09:02 | 0.58 |
February | 0.365282E+09 | 0.47 | 702.66 | 01-FEB-09:02 | 0.58 |
March | 0.232766E+09 | 0.41 | 702.66 | 01-MAR-09:02 | 0.57 |
April | 0.180647E+09 | 0.42 | 702.66 | 01-APR-08:62 | 0.57 |
May | 0.202806E+09 | 0.45 | 702.66 | 01-MAY-15:02 | 0.58 |
June | 0.320481E+09 | 0.51 | 702.66 | 01-JUN-08:62 | 0.57 |
July | 0.401065E+09 | 0.54 | 702.66 | 01-JUL-08:62 | 0.57 |
August | 0.402822E+09 | 0.54 | 702.66 | 01-AUG-08:62 | 0.57 |
September | 0.220573E+09 | 0.47 | 702.66 | 01-SEP-08:62 | 0.57 |
October | 0.157147E+09 | 0.43 | 702.66 | 02-OCT-15:02 | 0.57 |
November | 0.234881E+09 | 0.41 | 702.66 | 01-NOV-08:62 | 0.57 |
December | 0.341514E+09 | 0.45 | 702.66 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.346135E+10 | 0.46 | |||
Minimum of Months | 0.157147E+09 | 0.41 | 702.66 | 0.57 | |
Maximum of Months | 0.402822E+09 | 0.54 | 702.66 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 262680.68 | 0.00 | 120.20 | 31-JAN-14:40 | 0.58 |
February | 56824871.48 | 0.03 | 856.27 | 03-FEB-12:30 | 0.58 |
March | 0.188933E+09 | 0.10 | 1017.34 | 03-MAR-13:30 | 0.58 |
April | 0.457547E+09 | 0.23 | 1185.09 | 08-APR-12:30 | 0.57 |
May | 0.941625E+09 | 0.44 | 861.63 | 29-MAY-19:10 | 0.57 |
June | 0.139666E+10 | 0.56 | 1038.11 | 19-JUN-20:20 | 0.57 |
July | 0.172828E+10 | 0.57 | 1050.20 | 08-JUL-08:00 | 0.57 |
August | 0.190327E+10 | 0.57 | 1166.31 | 30-AUG-12:40 | 0.57 |
September | 0.160911E+10 | 0.55 | 2128.02 | 30-SEP-12:30 | 0.57 |
October | 0.168153E+10 | 0.50 | 2187.78 | 10-OCT-12:40 | 0.57 |
November | 0.463653E+09 | 0.19 | 2217.81 | 04-NOV-12:30 | 0.57 |
December | 0.163554E+09 | 0.07 | 1196.12 | 17-DEC-13:00 | 0.58 |
Annual Sum or Average | 0.105913E+11 | 0.32 | |||
Minimum of Months | 262680.68 | 0.00 | 120.20 | 0.57 | |
Maximum of Months | 0.190327E+10 | 0.57 | 2217.81 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135153E+10 | 0.41 | 4114.83 | 01-JAN-16:02 | 0.58 |
February | 0.129072E+10 | 0.41 | 4114.83 | 01-FEB-16:02 | 0.58 |
March | 0.853659E+09 | 0.41 | 4114.83 | 01-MAR-09:02 | 0.58 |
April | 0.110489E+10 | 0.41 | 4114.83 | 01-APR-08:62 | 0.57 |
May | 0.193364E+10 | 0.43 | 4114.83 | 01-MAY-08:62 | 0.57 |
June | 0.273366E+10 | 0.47 | 4114.83 | 01-JUN-08:62 | 0.57 |
July | 0.356258E+10 | 0.50 | 4114.83 | 01-JUL-08:62 | 0.57 |
August | 0.322376E+10 | 0.49 | 4114.83 | 01-AUG-08:62 | 0.57 |
September | 0.210506E+10 | 0.44 | 4114.83 | 01-SEP-08:62 | 0.57 |
October | 0.126838E+10 | 0.41 | 4114.83 | 01-OCT-08:62 | 0.57 |
November | 0.884304E+09 | 0.41 | 4114.83 | 01-NOV-08:62 | 0.57 |
December | 0.104513E+10 | 0.41 | 4114.83 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.213573E+11 | 0.43 | |||
Minimum of Months | 0.853659E+09 | 0.41 | 4114.83 | 0.57 | |
Maximum of Months | 0.356258E+10 | 0.50 | 4114.83 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.328486E+09 | 0.44 | 641.80 | 01-JAN-09:02 | 0.58 |
February | 0.279139E+09 | 0.43 | 641.80 | 01-FEB-16:02 | 0.58 |
March | 0.202897E+09 | 0.42 | 641.80 | 01-MAR-09:02 | 0.57 |
April | 0.179779E+09 | 0.45 | 641.80 | 01-APR-08:62 | 0.57 |
May | 0.216999E+09 | 0.48 | 641.80 | 01-MAY-08:62 | 0.57 |
June | 0.300323E+09 | 0.52 | 641.80 | 01-JUN-08:62 | 0.57 |
July | 0.399788E+09 | 0.55 | 641.80 | 01-JUL-08:62 | 0.57 |
August | 0.425604E+09 | 0.55 | 641.80 | 01-AUG-08:62 | 0.57 |
September | 0.261209E+09 | 0.51 | 641.80 | 01-SEP-08:62 | 0.57 |
October | 0.197784E+09 | 0.49 | 641.80 | 02-OCT-08:62 | 0.57 |
November | 0.193932E+09 | 0.42 | 641.80 | 01-NOV-08:62 | 0.57 |
December | 0.273800E+09 | 0.43 | 641.80 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.325974E+10 | 0.47 | |||
Minimum of Months | 0.179779E+09 | 0.42 | 641.80 | 0.57 | |
Maximum of Months | 0.425604E+09 | 0.55 | 641.80 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386463E+09 | 0.47 | 637.63 | 01-JAN-09:02 | 0.58 |
February | 0.343735E+09 | 0.47 | 637.63 | 01-FEB-09:02 | 0.58 |
March | 0.217986E+09 | 0.41 | 637.63 | 01-MAR-09:02 | 0.57 |
April | 0.169138E+09 | 0.43 | 637.63 | 01-APR-08:62 | 0.57 |
May | 0.205700E+09 | 0.47 | 637.63 | 01-MAY-08:62 | 0.57 |
June | 0.292141E+09 | 0.52 | 637.63 | 01-JUN-08:62 | 0.57 |
July | 0.386981E+09 | 0.55 | 637.63 | 01-JUL-08:62 | 0.57 |
August | 0.390528E+09 | 0.55 | 637.63 | 01-AUG-08:62 | 0.57 |
September | 0.215459E+09 | 0.49 | 637.63 | 01-SEP-08:62 | 0.57 |
October | 0.141730E+09 | 0.43 | 637.63 | 02-OCT-08:62 | 0.57 |
November | 0.211206E+09 | 0.42 | 637.63 | 02-NOV-08:62 | 0.57 |
December | 0.316869E+09 | 0.45 | 637.63 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.327794E+10 | 0.47 | |||
Minimum of Months | 0.141730E+09 | 0.41 | 637.63 | 0.57 | |
Maximum of Months | 0.390528E+09 | 0.55 | 637.63 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113371E+09 | 0.46 | 187.37 | 01-JAN-09:02 | 0.58 |
February | 96860082.76 | 0.46 | 187.37 | 01-FEB-09:02 | 0.58 |
March | 66802614.21 | 0.43 | 187.37 | 01-MAR-09:02 | 0.57 |
April | 57657722.90 | 0.45 | 187.37 | 01-APR-08:62 | 0.57 |
May | 64499314.49 | 0.48 | 187.37 | 01-MAY-15:02 | 0.58 |
June | 99065844.50 | 0.53 | 187.37 | 01-JUN-08:62 | 0.57 |
July | 0.124736E+09 | 0.55 | 187.37 | 01-JUL-08:62 | 0.57 |
August | 0.130696E+09 | 0.55 | 187.37 | 01-AUG-08:62 | 0.57 |
September | 77907166.45 | 0.51 | 187.37 | 01-SEP-08:62 | 0.57 |
October | 59525598.49 | 0.48 | 187.37 | 02-OCT-15:02 | 0.57 |
November | 63726844.74 | 0.42 | 187.37 | 01-NOV-15:02 | 0.58 |
December | 91230324.48 | 0.45 | 187.37 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.104608E+10 | 0.48 | |||
Minimum of Months | 57657722.90 | 0.42 | 187.37 | 0.57 | |
Maximum of Months | 0.130696E+09 | 0.55 | 187.37 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130913E+09 | 0.51 | 184.41 | 01-JAN-09:02 | 0.58 |
February | 0.116840E+09 | 0.49 | 184.41 | 01-FEB-09:02 | 0.58 |
March | 69695123.32 | 0.43 | 184.41 | 01-MAR-09:02 | 0.57 |
April | 54417139.07 | 0.43 | 184.41 | 01-APR-08:62 | 0.57 |
May | 61194793.19 | 0.47 | 184.41 | 01-MAY-15:02 | 0.58 |
June | 96996061.26 | 0.53 | 184.41 | 01-JUN-08:62 | 0.57 |
July | 0.121667E+09 | 0.55 | 184.41 | 01-JUL-08:62 | 0.57 |
August | 0.121346E+09 | 0.54 | 184.41 | 01-AUG-08:62 | 0.57 |
September | 65688279.80 | 0.49 | 184.41 | 01-SEP-08:62 | 0.57 |
October | 46223950.80 | 0.44 | 184.41 | 02-OCT-15:02 | 0.57 |
November | 72792027.65 | 0.44 | 184.41 | 01-NOV-08:62 | 0.57 |
December | 0.105465E+09 | 0.48 | 184.41 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.106324E+10 | 0.48 | |||
Minimum of Months | 46223950.80 | 0.43 | 184.41 | 0.57 | |
Maximum of Months | 0.130913E+09 | 0.55 | 184.41 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351294E+09 | 0.45 | 763.82 | 01-JAN-16:02 | 0.58 |
February | 0.297707E+09 | 0.47 | 763.82 | 01-FEB-16:02 | 0.58 |
March | 0.263042E+09 | 0.46 | 763.82 | 01-MAR-09:02 | 0.57 |
April | 0.237242E+09 | 0.46 | 763.82 | 01-APR-15:02 | 0.57 |
May | 0.287075E+09 | 0.48 | 763.82 | 01-MAY-08:62 | 0.57 |
June | 0.460939E+09 | 0.52 | 763.82 | 01-JUN-08:62 | 0.57 |
July | 0.639330E+09 | 0.54 | 763.82 | 01-JUL-08:62 | 0.57 |
August | 0.672874E+09 | 0.54 | 763.82 | 01-AUG-08:62 | 0.57 |
September | 0.496673E+09 | 0.52 | 763.82 | 01-SEP-08:62 | 0.57 |
October | 0.469603E+09 | 0.51 | 763.82 | 01-OCT-08:62 | 0.57 |
November | 0.259103E+09 | 0.46 | 763.82 | 01-NOV-15:02 | 0.57 |
December | 0.323298E+09 | 0.46 | 763.82 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.475818E+10 | 0.49 | |||
Minimum of Months | 0.237242E+09 | 0.45 | 763.82 | 0.57 | |
Maximum of Months | 0.672874E+09 | 0.54 | 763.82 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.216683E+10 | 0.195014E+10 | 1785.89 | 02-JAN-07:15 | 1607.30 | 1607.30 | 49.98 | 3.97 |
February | 0.191149E+10 | 0.172034E+10 | 1841.46 | 06-FEB-07:15 | 1657.31 | 1657.31 | 50.25 | 4.34 |
March | 0.114156E+10 | 0.102741E+10 | 1423.31 | 15-MAR-08:04 | 1280.98 | 1280.98 | 47.43 | 2.50 |
April | 0.832493E+09 | 0.749243E+09 | 1377.68 | 05-APR-08:05 | 1239.92 | 1239.92 | 45.88 | 2.38 |
May | 0.377732E+09 | 0.339959E+09 | 1207.15 | 01-MAY-06:40 | 1086.43 | 1086.43 | 48.04 | 1.94 |
June | 0.149718E+09 | 0.134747E+09 | 565.69 | 06-JUN-08:06 | 509.12 | 509.12 | 42.10 | 0.76 |
July | 0.127005E+09 | 0.114305E+09 | 347.76 | 24-JUL-08:05 | 312.99 | 312.99 | 42.93 | 0.44 |
August | 0.105612E+09 | 95050523.05 | 529.67 | 20-AUG-15:07 | 476.71 | 476.71 | 47.05 | 0.70 |
September | 0.168055E+09 | 0.151250E+09 | 1078.87 | 24-SEP-06:00 | 970.99 | 970.99 | 45.86 | 1.66 |
October | 0.548550E+09 | 0.493695E+09 | 1444.59 | 09-OCT-08:06 | 1300.13 | 1300.13 | 46.47 | 2.57 |
November | 0.129721E+10 | 0.116749E+10 | 1550.44 | 27-NOV-16:04 | 1395.39 | 1395.39 | 45.90 | 2.91 |
December | 0.158006E+10 | 0.142206E+10 | 1568.70 | 31-DEC-24:00 | 1411.83 | 1411.83 | 49.58 | 2.98 |
Annual Sum or Average | 0.104063E+11 | 0.936569E+10 | ||||||
Minimum of Months | 0.105612E+09 | 95050523.05 | 347.76 | 312.99 | 312.99 | 42.10 | 0.44 | |
Maximum of Months | 0.216683E+10 | 0.195014E+10 | 1841.46 | 1657.31 | 1657.31 | 50.25 | 4.34 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1425868.41 | 1283281.57 | 49.47 | 19-JAN-09:02 | 44.53 | 44.53 | 8.39 | 3.22 |
February | 2378752.16 | 2140876.94 | 75.98 | 19-FEB-16:02 | 68.38 | 68.38 | 8.39 | 4.08 |
March | 21543428.21 | 19389085.39 | 470.29 | 27-MAR-18:01 | 423.26 | 423.26 | 7.90 | 10.15 |
April | 0.124964E+09 | 0.112468E+09 | 851.45 | 07-APR-18:02 | 766.30 | 766.30 | 7.29 | 13.29 |
May | 0.408569E+09 | 0.367712E+09 | 1456.80 | 31-MAY-18:03 | 1311.12 | 1311.12 | 7.49 | 16.81 |
June | 0.180578E+10 | 0.162520E+10 | 2909.93 | 24-JUN-18:03 | 2618.94 | 2618.94 | 7.32 | 22.49 |
July | 0.272550E+10 | 0.245295E+10 | 2622.02 | 14-JUL-18:03 | 2359.82 | 2359.82 | 7.32 | 21.54 |
August | 0.221089E+10 | 0.198980E+10 | 2263.71 | 10-AUG-21:00 | 2037.34 | 2037.34 | 7.23 | 20.26 |
September | 0.123896E+10 | 0.111507E+10 | 2512.33 | 22-SEP-18:03 | 2261.10 | 2261.10 | 7.44 | 21.16 |
October | 0.474613E+09 | 0.427151E+09 | 1648.50 | 24-OCT-15:03 | 1483.65 | 1483.65 | 7.48 | 17.72 |
November | 28582224.39 | 25724001.95 | 474.51 | 04-NOV-15:01 | 427.06 | 427.06 | 8.14 | 10.19 |
December | 5132188.19 | 4618969.37 | 95.24 | 20-DEC-09:02 | 85.72 | 85.72 | 8.39 | 4.61 |
Annual Sum or Average | 0.904833E+10 | 0.814350E+10 | ||||||
Minimum of Months | 1425868.41 | 1283281.57 | 49.47 | 44.53 | 44.53 | 7.23 | 3.22 | |
Maximum of Months | 0.272550E+10 | 0.245295E+10 | 2909.93 | 2618.94 | 2618.94 | 8.39 | 22.49 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 47.60 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.44 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.83 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.98 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 51.66 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.08 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.79 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.54 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.12 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.42 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.73 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.41 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.60 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.54 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.146664E+10 | 0.131998E+10 | 2726.03 | 01-JAN-09:03 | 2453.42 | 2453.42 | 8.40 | 34.14 |
February | 0.174507E+10 | 0.157056E+10 | 2726.03 | 01-FEB-09:02 | 2453.42 | 2453.42 | 8.41 | 34.14 |
March | 0.373856E+10 | 0.336470E+10 | 2726.03 | 01-MAR-07:05 | 2453.42 | 2453.42 | 8.40 | 34.14 |
April | 0.546457E+10 | 0.491811E+10 | 2726.03 | 01-APR-06:50 | 2453.42 | 2453.42 | 8.39 | 34.14 |
May | 0.726950E+10 | 0.654255E+10 | 2726.03 | 01-MAY-00:03 | 2453.42 | 2453.42 | 8.44 | 34.14 |
June | 0.706586E+10 | 0.635928E+10 | 2726.03 | 01-JUN-00:10 | 2453.42 | 2453.42 | 9.47 | 34.14 |
July | 0.730139E+10 | 0.657125E+10 | 2726.03 | 01-JUL-00:10 | 2453.42 | 2453.42 | 10.23 | 34.14 |
August | 0.730139E+10 | 0.657125E+10 | 2726.03 | 01-AUG-00:10 | 2453.42 | 2453.42 | 9.73 | 34.14 |
September | 0.706586E+10 | 0.635928E+10 | 2726.03 | 01-SEP-00:10 | 2453.42 | 2453.42 | 9.54 | 34.14 |
October | 0.700289E+10 | 0.630260E+10 | 2726.03 | 01-OCT-00:05 | 2453.42 | 2453.42 | 8.53 | 34.14 |
November | 0.410521E+10 | 0.369469E+10 | 2726.03 | 01-NOV-00:05 | 2453.42 | 2453.42 | 8.41 | 34.14 |
December | 0.218626E+10 | 0.196763E+10 | 2726.03 | 01-DEC-06:15 | 2453.42 | 2453.42 | 8.39 | 34.14 |
Annual Sum or Average | 0.617132E+11 | 0.555419E+11 | ||||||
Minimum of Months | 0.146664E+10 | 0.131998E+10 | 2726.03 | 2453.42 | 2453.42 | 8.39 | 34.14 | |
Maximum of Months | 0.730139E+10 | 0.657125E+10 | 2726.03 | 2453.42 | 2453.42 | 10.23 | 34.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47.60 | 59.92 | 28261.68 | 57871.66 | 30-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.44 | 58.91 | 28527.77 | 57954.76 | 07-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.83 | 58.06 | 27920.99 | 57484.26 | 02-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.98 | 58.15 | 26481.66 | 55095.37 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 51.66 | 59.96 | 24580.70 | 51982.23 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.08 | 58.32 | 22717.71 | 48204.76 | 01-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.79 | 58.69 | 21426.90 | 45030.06 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.54 | 59.33 | 21035.83 | 44052.74 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.12 | 58.89 | 21781.72 | 46083.30 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.42 | 58.12 | 23404.67 | 49590.96 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.73 | 58.38 | 25313.57 | 53266.99 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.41 | 59.09 | 27057.52 | 56196.89 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24854.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.60 | 58.06 | 21035.83 | 44052.74 | ||
Maximum of Months | 0.00 | 0.00 | 53.54 | 59.96 | 28527.77 | 57954.76 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 49.88 | 60.00 | 47972.58 | 194455.84 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.28 | 59.06 | 46694.76 | 197743.25 | 06-FEB-09:04 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.86 | 57.97 | 21512.52 | 132651.35 | 17-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.88 | 58.01 | 19894.55 | 117087.28 | 14-APR-15:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 45.45 | 57.22 | 10594.52 | 87859.20 | 01-MAY-22:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 46.11 | 57.22 | 3794.80 | 47890.43 | 06-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.60 | 57.22 | 2869.64 | 26520.74 | 24-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 41.07 | 57.22 | 2327.06 | 35739.97 | 07-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 41.23 | 57.22 | 4735.74 | 78877.01 | 24-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 39.88 | 57.22 | 14214.00 | 116894.63 | 09-OCT-08:06 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 45.62 | 57.22 | 28512.83 | 139165.33 | 27-NOV-16:04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.15 | 57.89 | 27642.40 | 145866.88 | 31-DEC-19:02 |
Annual Sum or Average | 0.00 | 19059.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.88 | 57.22 | 2327.06 | 26520.74 | ||
Maximum of Months | 0.00 | 0.00 | 52.15 | 60.00 | 47972.58 | 197743.25 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1167.52 | 35863.61 | 19-JAN-19:02 | 8.62 | 8.37 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1888.49 | 48968.56 | 19-FEB-16:02 | 8.71 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 8261.55 | 299987.71 | 27-MAR-15:01 | 9.82 | 7.73 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 34338.25 | 349799.87 | 07-APR-15:03 | 9.31 | 6.87 | 0.00 | 0.00 | 01-APR-00:10 |
May | 100235.03 | 513272.65 | 31-MAY-18:03 | 11.07 | 7.48 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 311532.84 | 770321.74 | 24-JUN-18:03 | 12.69 | 7.30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 427479.18 | 734404.09 | 14-JUL-18:03 | 12.44 | 7.30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 363162.37 | 695940.22 | 03-AUG-20:00 | 11.66 | 6.79 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 230954.54 | 737977.72 | 22-SEP-18:03 | 12.59 | 7.43 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 104552.59 | 537346.45 | 24-OCT-15:03 | 11.22 | 7.47 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 11671.77 | 193781.81 | 02-NOV-15:01 | 9.57 | 8.22 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3045.34 | 53104.34 | 20-DEC-09:02 | 8.74 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 134117.29 | 0.00 | ||||||
Minimum of Months | 1167.52 | 35863.61 | 8.62 | 6.79 | 0.00 | 0.00 | ||
Maximum of Months | 427479.18 | 770321.74 | 12.69 | 8.37 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 1.68 |
May | 0.17 | 1.68 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.36 | 2.26 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.61 | 2.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.36 | 2.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 56.92 |
May | 0.33 | 56.92 |
June | 1.50 | 59.29 |
July | 1.58 | 56.92 |
August | 1.58 | 53.92 |
September | 1.00 | 56.92 |
October | 0.42 | 56.92 |
November | 0.08 | 56.92 |
December | 0.00 | 0.00 |
Annual Sum or Average | 6.58 | 56.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.58 | 59.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.71 | 0.69 |
February | 2.19 | 0.70 |
March | 1.14 | 0.77 |
April | 1.64 | 0.74 |
May | 2.44 | 0.70 |
June | 4.12 | 0.59 |
July | 6.00 | 0.55 |
August | 5.61 | 0.47 |
September | 3.82 | 0.55 |
October | 2.94 | 0.61 |
November | 0.10 | 0.66 |
December | 0.71 | 0.63 |
Annual Sum or Average | 33.43 | 0.60 |
Minimum of Months | 0.10 | 0.47 |
Maximum of Months | 6.00 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.24 | 0.63 |
February | 2.60 | 0.61 |
March | 1.22 | 0.76 |
April | 1.68 | 0.78 |
May | 2.53 | 0.70 |
June | 4.12 | 0.59 |
July | 6.12 | 0.56 |
August | 5.28 | 0.46 |
September | 3.10 | 0.65 |
October | 1.01 | 0.81 |
November | 0.62 | 0.64 |
December | 1.29 | 0.56 |
Annual Sum or Average | 32.82 | 0.61 |
Minimum of Months | 0.62 | 0.46 |
Maximum of Months | 6.12 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 0.58 |
February | 0.18 | 0.81 |
March | 0.14 | 0.81 |
April | 0.94 | 0.81 |
May | 3.35 | 0.74 |
June | 5.67 | 0.69 |
July | 7.68 | 0.65 |
August | 6.64 | 0.65 |
September | 3.39 | 0.79 |
October | 0.71 | 0.80 |
November | 0.08 | 0.80 |
December | 0.00 | 0.00 |
Annual Sum or Average | 29.17 | 0.69 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.68 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.22 | 0.70 |
February | 1.00 | 0.80 |
March | 0.42 | 0.67 |
April | 1.00 | 0.56 |
May | 2.58 | 0.72 |
June | 3.40 | 0.70 |
July | 2.35 | 0.69 |
August | 1.32 | 0.67 |
September | 3.14 | 0.65 |
October | 3.17 | 0.49 |
November | 0.58 | 0.38 |
December | 0.69 | 0.65 |
Annual Sum or Average | 21.88 | 0.65 |
Minimum of Months | 0.42 | 0.38 |
Maximum of Months | 3.40 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.74 | 0.66 |
February | 2.53 | 0.61 |
March | 0.19 | 0.81 |
April | 1.13 | 0.53 |
May | 2.75 | 0.70 |
June | 3.65 | 0.71 |
July | 2.56 | 0.69 |
August | 2.82 | 0.62 |
September | 3.74 | 0.62 |
October | 0.99 | 0.52 |
November | 0.25 | 0.63 |
December | 0.92 | 0.67 |
Annual Sum or Average | 25.25 | 0.65 |
Minimum of Months | 0.19 | 0.52 |
Maximum of Months | 3.74 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.21 | 0.68 |
February | 2.06 | 0.66 |
March | 1.44 | 0.77 |
April | 1.39 | 0.72 |
May | 1.87 | 0.67 |
June | 3.79 | 0.61 |
July | 4.37 | 0.58 |
August | 3.94 | 0.49 |
September | 3.07 | 0.53 |
October | 3.14 | 0.60 |
November | 0.90 | 0.75 |
December | 1.25 | 0.68 |
Annual Sum or Average | 30.44 | 0.62 |
Minimum of Months | 0.90 | 0.49 |
Maximum of Months | 4.37 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.81 | 0.65 |
February | 2.22 | 0.61 |
March | 1.72 | 0.65 |
April | 1.60 | 0.75 |
May | 1.75 | 0.67 |
June | 3.79 | 0.61 |
July | 4.33 | 0.58 |
August | 4.53 | 0.46 |
September | 3.03 | 0.57 |
October | 1.35 | 0.78 |
November | 1.29 | 0.65 |
December | 2.46 | 0.57 |
Annual Sum or Average | 31.88 | 0.60 |
Minimum of Months | 1.29 | 0.46 |
Maximum of Months | 4.53 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.15 | 0.51 |
February | 0.62 | 0.47 |
March | 1.22 | 0.67 |
April | 1.28 | 0.74 |
May | 2.60 | 0.70 |
June | 5.07 | 0.63 |
July | 4.62 | 0.55 |
August | 3.78 | 0.51 |
September | 2.76 | 0.69 |
October | 2.81 | 0.67 |
November | 1.21 | 0.61 |
December | 0.49 | 0.33 |
Annual Sum or Average | 27.61 | 0.61 |
Minimum of Months | 0.49 | 0.33 |
Maximum of Months | 5.07 | 0.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 174.93 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 99.96 |
May | 0.08 | 99.96 |
June | 1.33 | 99.96 |
July | 1.33 | 99.96 |
August | 1.17 | 92.82 |
September | 1.08 | 105.73 |
October | 0.42 | 99.96 |
November | 0.08 | 99.96 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 100.69 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.33 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 174.93 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.08 | 99.96 |
August | 0.50 | 83.30 |
September | 0.33 | 99.96 |
October | 0.08 | 99.96 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.08 | 98.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.50 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 4.45 |
May | 0.00 | 0.00 |
June | 0.17 | 17.79 |
July | 0.00 | 0.00 |
August | 0.30 | 13.56 |
September | 0.36 | 13.17 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.92 | 13.35 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.36 | 17.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.859337E+11 | 0.00 | 0.00 | 0.385451E+11 | 0.00 | 0.00 |
February | 0.741335E+11 | 0.00 | 0.00 | 0.348290E+11 | 0.00 | 0.00 |
March | 0.417534E+11 | 0.00 | 0.580398E+10 | 0.394840E+11 | 0.00 | 0.00 |
April | 0.461671E+11 | 0.00 | 0.467937E+11 | 0.380455E+11 | 0.00 | 0.00 |
May | 0.279869E+11 | 0.00 | 0.176930E+12 | 0.381053E+11 | 0.00 | 0.00 |
June | 0.994366E+10 | 0.00 | 0.622615E+12 | 0.353781E+11 | 0.00 | 0.00 |
July | 0.779910E+10 | 0.00 | 0.889791E+12 | 0.364013E+11 | 0.00 | 0.00 |
August | 0.630921E+10 | 0.00 | 0.736942E+12 | 0.366231E+11 | 0.00 | 0.00 |
September | 0.122529E+11 | 0.00 | 0.446440E+12 | 0.354162E+11 | 0.00 | 0.00 |
October | 0.363457E+11 | 0.00 | 0.180362E+12 | 0.383315E+11 | 0.00 | 0.00 |
November | 0.581251E+11 | 0.00 | 0.674918E+10 | 0.384025E+11 | 0.00 | 0.00 |
December | 0.430992E+11 | 0.00 | 0.00 | 0.390187E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.449849E+12 | 0.00 | 0.311243E+13 | 0.448580E+12 | 0.00 | 0.00 |
Minimum of Months | 0.630921E+10 | 0.00 | 0.00 | 0.348290E+11 | 0.00 | 0.00 |
Maximum of Months | 0.859337E+11 | 0.00 | 0.889791E+12 | 0.394840E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.151991E+10 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
February | 0.172416E+10 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
March | 0.126425E+09 | 0.00 | 0.267193E+09 | 0.270916E+10 | 0.00 | 0.00 |
April | 1251.68 | 0.00 | 0.214739E+10 | 0.262177E+10 | 0.00 | 0.00 |
May | 18418.98 | 0.00 | 0.886479E+10 | 0.270916E+10 | 0.00 | 0.00 |
June | 9283.65 | 0.00 | 0.414139E+11 | 0.262177E+10 | 0.00 | 0.00 |
July | 6498.93 | 0.00 | 0.585410E+11 | 0.270916E+10 | 0.00 | 0.00 |
August | 17502.57 | 0.00 | 0.477072E+11 | 0.270916E+10 | 0.00 | 0.00 |
September | 9321.47 | 0.00 | 0.280954E+11 | 0.262177E+10 | 0.00 | 0.00 |
October | 7958.86 | 0.00 | 0.988544E+10 | 0.270916E+10 | 0.00 | 0.00 |
November | 0.137014E+09 | 0.00 | 0.209433E+09 | 0.262177E+10 | 0.00 | 0.00 |
December | 0.194698E+09 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.370227E+10 | 0.00 | 0.197132E+12 | 0.318982E+11 | 0.00 | 0.00 |
Minimum of Months | 1251.68 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.172416E+10 | 0.00 | 0.585410E+11 | 0.270916E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.385451E+11 | 0.00 | 0.859337E+11 | 0.602912E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348290E+11 | 0.00 | 0.741335E+11 | 0.602879E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394840E+11 | 0.580398E+10 | 0.417534E+11 | 0.434326E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380455E+11 | 0.467937E+11 | 0.461671E+11 | 0.175260E+12 | 0.453575E+09 | 0.00 | 0.00 | 0.00 |
May | 0.381053E+11 | 0.176930E+12 | 0.279869E+11 | 0.148247E+11 | 0.603071E+10 | 0.00 | 0.00 | 0.00 |
June | 0.353781E+11 | 0.622615E+12 | 0.994366E+10 | 0.00 | 0.984576E+11 | 0.00 | 0.00 | 0.00 |
July | 0.364013E+11 | 0.889791E+12 | 0.779910E+10 | 0.00 | 0.314901E+12 | 0.00 | 0.00 | 0.00 |
August | 0.366231E+11 | 0.736942E+12 | 0.630921E+10 | 0.00 | 0.236655E+12 | 0.00 | 0.00 | 0.00 |
September | 0.354162E+11 | 0.446440E+12 | 0.122529E+11 | 0.00 | 0.494294E+11 | 0.00 | 0.00 | 0.00 |
October | 0.383315E+11 | 0.180362E+12 | 0.363457E+11 | 0.711543E+11 | 0.345283E+10 | 0.00 | 0.00 | 0.00 |
November | 0.384025E+11 | 0.674918E+10 | 0.581251E+11 | 0.310878E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390187E+11 | 0.00 | 0.430992E+11 | 0.550886E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448580E+12 | 0.311243E+13 | 0.449849E+12 | 0.276312E+13 | 0.709380E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348290E+11 | 0.00 | 0.630921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394840E+11 | 0.889791E+12 | 0.859337E+11 | 0.602912E+12 | 0.314901E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270916E+10 | 0.00 | 0.151991E+10 | 0.513755E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.00 | 0.172416E+10 | 0.501683E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.267193E+09 | 0.126425E+09 | 0.372625E+11 | 1676698.04 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.214739E+10 | 1251.68 | 0.187768E+11 | 52837306.15 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 0.886479E+10 | 18418.98 | 0.455882E+10 | 0.492888E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 0.414139E+11 | 9283.65 | 98221577.90 | 0.915006E+10 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 0.585410E+11 | 6498.93 | 62185.80 | 0.306576E+11 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 0.477072E+11 | 17502.57 | 61491456.13 | 0.229629E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 0.280954E+11 | 9321.47 | 0.948171E+09 | 0.613039E+10 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 0.988544E+10 | 7958.86 | 0.102267E+11 | 0.232413E+09 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.209433E+09 | 0.137014E+09 | 0.300508E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.00 | 0.194698E+09 | 0.455781E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.197132E+12 | 0.370227E+10 | 0.249105E+12 | 0.696807E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244698E+10 | 0.00 | 1251.68 | 62185.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.585410E+11 | 0.172416E+10 | 0.513755E+11 | 0.306576E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.385451E+11 | 0.859337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348290E+11 | 0.741335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394840E+11 | 0.417534E+11 | 0.580398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380455E+11 | 0.461671E+11 | 0.467937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381053E+11 | 0.279869E+11 | 0.176930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353781E+11 | 0.994366E+10 | 0.622615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364013E+11 | 0.779910E+10 | 0.889791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.366231E+11 | 0.630921E+10 | 0.736942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.354162E+11 | 0.122529E+11 | 0.446440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383315E+11 | 0.363457E+11 | 0.180362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384025E+11 | 0.581251E+11 | 0.674918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390187E+11 | 0.430992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448580E+12 | 0.449849E+12 | 0.311243E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.348290E+11 | 0.630921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394840E+11 | 0.859337E+11 | 0.889791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.270916E+10 | 0.151991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.172416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.126425E+09 | 0.267193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 1251.68 | 0.214739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 18418.98 | 0.886479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 9283.65 | 0.414139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 6498.93 | 0.585410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 17502.57 | 0.477072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 9321.47 | 0.280954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 7958.86 | 0.988544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.137014E+09 | 0.209433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.194698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.370227E+10 | 0.197132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.244698E+10 | 1251.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.172416E+10 | 0.585410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.439558E+11 | 0.00 | 0.00 | 2110625.57 | 0.00 | 0.00 | 0.592931E+10 | 0.00 | 1.01 |
February | 0.442617E+11 | 0.00 | 0.00 | 126968.27 | 0.00 | 0.00 | 0.547445E+09 | 0.00 | 1.01 |
March | 0.473001E+11 | 0.00 | 0.00 | 0.00 | 9722382.64 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 0.443853E+11 | 0.00 | 0.00 | 0.00 | 57089987.18 | 0.00 | 0.00 | 0.00 | 1.01 |
May | 0.347165E+11 | 0.00 | 1566146.97 | 0.00 | 0.807322E+09 | 0.00 | 0.00 | 44850.95 | 1.01 |
June | 0.646002E+10 | 0.00 | 0.00 | 0.00 | 0.188382E+11 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.204454E+09 | 0.00 | 0.00 | 0.00 | 0.369428E+11 | 0.00 | 0.00 | 0.00 | 1.01 |
August | 0.337620E+10 | 0.00 | 0.00 | 0.00 | 0.235735E+11 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 0.162004E+11 | 0.00 | 0.00 | 9809.79 | 0.100414E+11 | 0.00 | 88689666.16 | 0.00 | 1.01 |
October | 0.192319E+11 | 47503318.26 | 0.00 | 13538723.62 | 0.176146E+10 | 0.00 | 0.187240E+11 | 0.00 | 1.02 |
November | 0.999084E+10 | 0.00 | 0.00 | 39906685.20 | 0.00 | 0.00 | 0.408047E+11 | 0.00 | 1.06 |
December | 0.184662E+11 | 0.00 | 0.00 | 20070127.29 | 0.00 | 0.00 | 0.293409E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.288549E+12 | 47503318.26 | 1566146.97 | 75762939.75 | 0.920316E+11 | 0.00 | 0.954350E+11 | 44850.95 | 1.02 |
Minimum of Months | 0.204454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.473001E+11 | 47503318.26 | 1566146.97 | 39906685.20 | 0.369428E+11 | 0.00 | 0.408047E+11 | 44850.95 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247859E+10 | 0.00 | 0.00 | 61171.37 | 0.00 | 0.389487E+10 | 90536285.15 | 0.00 | 2.35 |
February | 0.254174E+10 | 0.00 | 0.00 | 53150.24 | 0.00 | 0.315177E+10 | 0.109991E+09 | 0.00 | 2.37 |
March | 0.458933E+10 | 0.00 | 0.00 | 164251.21 | 1259214.68 | 0.136103E+10 | 0.177889E+09 | 0.00 | 2.36 |
April | 0.528049E+10 | 2119468.23 | 0.00 | 16611.90 | 5274660.61 | 0.465004E+09 | 3135414.82 | 0.00 | 2.37 |
May | 0.449638E+10 | 0.00 | 0.00 | 0.00 | 0.104771E+09 | 0.00 | 0.00 | 0.00 | 2.38 |
June | 0.836665E+09 | 57390637.36 | 0.00 | 115.26 | 0.238247E+10 | 0.00 | 17516.70 | 0.00 | 2.39 |
July | 26217509.58 | 0.432295E+09 | 0.00 | 769.64 | 0.435243E+10 | 0.00 | 261982.53 | 0.00 | 2.39 |
August | 0.432886E+09 | 0.105678E+10 | 0.00 | 25862.02 | 0.199640E+10 | 0.00 | 4363209.34 | 0.00 | 2.39 |
September | 0.205956E+10 | 0.169193E+09 | 0.00 | 289525.12 | 0.113147E+10 | 0.00 | 51481168.04 | 0.00 | 2.38 |
October | 0.440610E+10 | 0.125577E+09 | 0.00 | 726268.25 | 0.116267E+09 | 0.00 | 0.475028E+09 | 0.00 | 2.39 |
November | 0.509298E+10 | 0.00 | 0.00 | 199715.41 | 0.00 | 0.105622E+10 | 0.193685E+09 | 0.00 | 2.38 |
December | 0.317586E+10 | 0.00 | 0.00 | 280951.55 | 0.00 | 0.271121E+10 | 0.234086E+09 | 0.00 | 2.38 |
Annual Sum or Average | 0.354168E+11 | 0.184335E+10 | 0.00 | 1818391.97 | 0.100903E+11 | 0.126401E+11 | 0.134047E+10 | 0.00 | 2.38 |
Minimum of Months | 26217509.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
Maximum of Months | 0.528049E+10 | 0.105678E+10 | 0.00 | 726268.25 | 0.435243E+10 | 0.389487E+10 | 0.475028E+09 | 0.00 | 2.39 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
February | 0.436384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
March | 0.459023E+10 | 0.00 | 0.00 | 908.58 | 946833.62 | 0.00 | 16177447.55 | 0.00 | 1.53 |
April | 0.431451E+10 | 0.00 | 0.00 | 279.06 | 5559822.25 | 0.00 | 8040564.26 | 0.00 | 1.54 |
May | 0.336445E+10 | 387589.87 | 0.00 | 612.20 | 78391983.14 | 0.00 | 16489150.87 | 0.00 | 1.55 |
June | 0.620040E+09 | 25802095.04 | 0.00 | 8138.28 | 0.180879E+10 | 0.00 | 9073206.41 | 0.00 | 1.55 |
July | 19713572.24 | 0.159309E+09 | 0.00 | 276.30 | 0.343844E+10 | 0.00 | 197293.33 | 0.00 | 1.55 |
August | 0.311794E+09 | 0.253111E+09 | 0.00 | 35274.94 | 0.204264E+10 | 0.00 | 16968173.11 | 0.00 | 1.55 |
September | 0.154618E+10 | 34623354.16 | 0.00 | 10126.72 | 0.943283E+09 | 0.00 | 40162354.48 | 0.00 | 1.55 |
October | 0.344026E+10 | 2070109.27 | 0.00 | 68650.77 | 0.174100E+09 | 0.00 | 0.221166E+09 | 0.00 | 1.54 |
November | 0.471448E+10 | 0.00 | 0.00 | 5735.03 | 0.00 | 0.00 | 50001137.60 | 0.00 | 1.54 |
December | 0.458926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
Annual Sum or Average | 0.367331E+11 | 0.475304E+09 | 0.00 | 130001.88 | 0.849216E+10 | 0.00 | 0.378275E+09 | 0.00 | 1.54 |
Minimum of Months | 19713572.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
Maximum of Months | 0.485837E+10 | 0.253111E+09 | 0.00 | 68650.77 | 0.343844E+10 | 0.00 | 0.221166E+09 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130744E+10 | 0.00 | 0.00 | 0.54 |
February | 0.197071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130943E+10 | 0.00 | 0.00 | 0.55 |
March | 0.335297E+10 | 0.00 | 0.00 | 0.00 | 711700.34 | 0.109499E+09 | 0.00 | 0.00 | 0.54 |
April | 0.324910E+10 | 0.00 | 0.00 | 0.00 | 4179115.83 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.254133E+10 | 0.00 | 0.00 | 0.00 | 59215734.94 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.472888E+09 | 0.00 | 0.00 | 0.00 | 0.137900E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 14966479.95 | 0.00 | 0.00 | 0.00 | 0.270430E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.247145E+09 | 0.00 | 0.00 | 0.00 | 0.172564E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.119240E+10 | 0.00 | 0.00 | 0.00 | 0.735056E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.275221E+10 | 0.00 | 0.00 | 0.00 | 0.132421E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.350250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78789755.61 | 0.00 | 0.00 | 0.55 |
December | 0.329726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152322E+09 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.249379E+11 | 0.00 | 0.00 | 0.00 | 0.674051E+10 | 0.295748E+10 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 14966479.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.350250E+10 | 0.00 | 0.00 | 0.00 | 0.270430E+10 | 0.130943E+10 | 0.00 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.618755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140651E+10 | 0.00 | 0.00 | 0.52 |
February | 0.480827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133829E+10 | 0.00 | 0.00 | 0.52 |
March | 0.144666E+10 | 0.00 | 0.00 | 0.00 | 394698.20 | 0.473571E+09 | 0.00 | 0.00 | 0.52 |
April | 0.176578E+10 | 0.00 | 0.00 | 0.00 | 2317674.18 | 36119040.74 | 0.00 | 0.00 | 0.53 |
May | 0.140938E+10 | 0.00 | 0.00 | 0.00 | 32840147.49 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.262256E+09 | 0.00 | 0.00 | 0.00 | 0.764770E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 8300182.53 | 0.00 | 0.00 | 0.00 | 0.149976E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.137063E+09 | 0.00 | 0.00 | 0.00 | 0.957011E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.661287E+09 | 0.00 | 0.00 | 0.00 | 0.407651E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.152633E+10 | 0.00 | 0.00 | 0.00 | 73438418.88 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.169368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292455E+09 | 0.00 | 0.00 | 0.53 |
December | 0.105451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858577E+09 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.110648E+11 | 0.00 | 0.00 | 0.00 | 0.373819E+10 | 0.440552E+10 | 0.00 | 0.00 | 0.53 |
Minimum of Months | 8300182.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.176578E+10 | 0.00 | 0.00 | 0.00 | 0.149976E+10 | 0.140651E+10 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.947771E+09 | 0.00 | 0.00 | 84484254.27 | 0.00 | 0.00 | 0.786490E+11 | 0.00 | 24.94 |
February | 0.859378E+09 | 0.00 | 0.00 | 76527408.97 | 0.00 | 0.00 | 0.706280E+11 | 0.00 | 25.10 |
March | 0.607976E+09 | 14035856.56 | 0.00 | 84749799.21 | 0.00 | 0.00 | 0.751437E+11 | 0.00 | 25.08 |
April | 0.476926E+09 | 81032797.43 | 0.00 | 81150033.22 | 1385977.93 | 0.00 | 0.701848E+11 | 0.00 | 24.93 |
May | 0.413380E+09 | 0.116437E+10 | 0.00 | 78799720.99 | 35426706.24 | 0.00 | 0.539148E+11 | 0.00 | 24.43 |
June | 87041664.83 | 0.277765E+11 | 0.00 | 23777744.63 | 0.575634E+09 | 0.00 | 0.978966E+10 | 0.00 | 24.00 |
July | 7871653.68 | 0.542908E+11 | 0.00 | 898836.61 | 0.123105E+10 | 0.00 | 0.287360E+09 | 0.00 | 23.79 |
August | 46693776.59 | 0.347225E+11 | 0.00 | 13800295.18 | 0.902320E+09 | 0.00 | 0.490792E+10 | 0.00 | 23.89 |
September | 0.262996E+09 | 0.148185E+11 | 0.00 | 46928995.50 | 0.307518E+09 | 0.00 | 0.245906E+11 | 0.00 | 23.92 |
October | 0.512047E+09 | 0.255495E+10 | 0.00 | 74552827.57 | 0.121615E+09 | 0.00 | 0.582820E+11 | 0.00 | 24.54 |
November | 0.602343E+09 | 0.00 | 0.00 | 82302484.73 | 0.00 | 0.00 | 0.774260E+11 | 0.00 | 25.16 |
December | 0.685363E+09 | 0.00 | 0.00 | 85998604.51 | 0.00 | 0.00 | 0.745222E+11 | 0.00 | 25.22 |
Annual Sum or Average | 0.550979E+10 | 0.135423E+12 | 0.00 | 0.733971E+09 | 0.317495E+10 | 0.00 | 0.598326E+12 | 0.00 | 24.58 |
Minimum of Months | 7871653.68 | 0.00 | 0.00 | 898836.61 | 0.00 | 0.00 | 0.287360E+09 | 0.00 | 23.79 |
Maximum of Months | 0.947771E+09 | 0.542908E+11 | 0.00 | 85998604.51 | 0.123105E+10 | 0.00 | 0.786490E+11 | 0.00 | 25.22 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252929E+11 | 0.00 | 0.00 | 798044.96 | 0.00 | 0.579989E+09 | 0.243194E+10 | 0.00 | 3.67 |
February | 0.231972E+11 | 0.00 | 0.00 | 976885.20 | 0.00 | 0.207148E+09 | 0.201123E+10 | 0.00 | 3.69 |
March | 0.197253E+11 | 0.00 | 0.00 | 2923827.88 | 5514452.46 | 0.00 | 0.711476E+10 | 0.00 | 3.68 |
April | 0.166738E+11 | 11609358.65 | 0.00 | 3015031.79 | 20771594.87 | 0.00 | 0.849808E+10 | 0.00 | 3.70 |
May | 0.991917E+10 | 76667916.06 | 0.00 | 4204308.05 | 0.382152E+09 | 0.00 | 0.976754E+10 | 0.00 | 3.71 |
June | 0.127718E+10 | 0.482409E+10 | 0.00 | 2528577.87 | 0.586077E+10 | 0.00 | 0.238436E+10 | 0.00 | 3.73 |
July | 20122267.38 | 0.126166E+11 | 0.00 | 238924.29 | 0.833704E+10 | 0.00 | 95603263.84 | 0.00 | 3.73 |
August | 0.370851E+09 | 0.972337E+10 | 0.00 | 3065025.59 | 0.365186E+10 | 0.00 | 0.154104E+10 | 0.00 | 3.73 |
September | 0.347217E+10 | 0.327958E+10 | 0.00 | 6481786.77 | 0.241586E+10 | 0.00 | 0.576429E+10 | 0.00 | 3.71 |
October | 0.644307E+10 | 0.776701E+09 | 0.00 | 13253169.47 | 0.252980E+09 | 0.00 | 0.149122E+11 | 0.00 | 3.72 |
November | 0.193248E+11 | 0.00 | 0.00 | 3958569.93 | 0.00 | 0.00 | 0.845146E+10 | 0.00 | 3.71 |
December | 0.228714E+11 | 0.00 | 0.00 | 2411398.23 | 0.00 | 27794307.82 | 0.393590E+10 | 0.00 | 3.72 |
Annual Sum or Average | 0.148588E+12 | 0.313086E+11 | 0.00 | 43855550.04 | 0.209270E+11 | 0.814931E+09 | 0.669084E+11 | 0.00 | 3.71 |
Minimum of Months | 20122267.38 | 0.00 | 0.00 | 238924.29 | 0.00 | 0.00 | 95603263.84 | 0.00 | 3.67 |
Maximum of Months | 0.252929E+11 | 0.126166E+11 | 0.00 | 13253169.47 | 0.833704E+10 | 0.579989E+09 | 0.149122E+11 | 0.00 | 3.73 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.963223E+11 | 0.00 | 0.00 | 735369.02 | 0.00 | 0.00 | 0.315924E+10 | 0.00 | 1.86 |
February | 0.864139E+11 | 0.00 | 0.00 | 509880.03 | 0.00 | 0.00 | 0.294161E+10 | 0.00 | 1.88 |
March | 0.819387E+11 | 0.00 | 0.00 | 4132766.90 | 19387814.26 | 0.00 | 0.123802E+11 | 0.00 | 1.87 |
April | 0.711281E+11 | 0.00 | 0.00 | 5579079.61 | 0.113846E+09 | 0.00 | 0.173768E+11 | 0.00 | 1.88 |
May | 0.534703E+11 | 59987042.57 | 0.00 | 5193630.25 | 0.155314E+10 | 0.00 | 0.157542E+11 | 0.00 | 1.88 |
June | 0.892743E+10 | 0.586652E+10 | 0.00 | 2312761.22 | 0.316995E+11 | 0.00 | 0.395245E+10 | 0.00 | 1.89 |
July | 0.128785E+09 | 0.173411E+11 | 0.00 | 246283.69 | 0.563281E+11 | 0.00 | 0.278679E+09 | 0.00 | 1.89 |
August | 0.332115E+10 | 0.141735E+11 | 0.00 | 3523106.09 | 0.328355E+11 | 0.00 | 0.340794E+10 | 0.00 | 1.89 |
September | 0.225823E+11 | 0.438756E+10 | 0.00 | 5245434.47 | 0.156365E+11 | 0.00 | 0.989531E+10 | 0.00 | 1.88 |
October | 0.419044E+11 | 0.329747E+09 | 0.00 | 17201136.85 | 0.327759E+10 | 0.00 | 0.330781E+11 | 0.00 | 1.88 |
November | 0.787670E+11 | 0.00 | 0.00 | 6813043.95 | 0.00 | 0.00 | 0.187862E+11 | 0.00 | 1.88 |
December | 0.872068E+11 | 0.00 | 0.00 | 1646435.68 | 0.00 | 0.00 | 0.676340E+10 | 0.00 | 1.88 |
Annual Sum or Average | 0.632111E+12 | 0.421585E+11 | 0.00 | 53138927.75 | 0.141464E+12 | 0.00 | 0.127774E+12 | 0.00 | 1.88 |
Minimum of Months | 0.128785E+09 | 0.00 | 0.00 | 246283.69 | 0.00 | 0.00 | 0.278679E+09 | 0.00 | 1.86 |
Maximum of Months | 0.963223E+11 | 0.173411E+11 | 0.00 | 17201136.85 | 0.563281E+11 | 0.00 | 0.330781E+11 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 52643535.97 | 0.00 | 0.00 | 255224.59 | 0.00 | 0.137799E+10 | 28819885.40 | 0.00 | 0.35 |
February | 52263030.06 | 0.00 | 0.00 | 523665.57 | 0.00 | 0.123470E+10 | 46772037.59 | 0.00 | 0.35 |
March | 68317778.77 | 15120.54 | 0.00 | 2254446.54 | 94949.11 | 0.101596E+10 | 0.323973E+09 | 0.00 | 0.35 |
April | 60329170.05 | 903960.01 | 0.00 | 4709556.83 | 0.00 | 0.605427E+09 | 0.610592E+09 | 0.00 | 0.35 |
May | 41638780.83 | 22541708.26 | 13033.92 | 8251882.90 | 368831.33 | 76915995.80 | 0.881564E+09 | 1579.67 | 0.36 |
June | 1717365.46 | 0.550689E+09 | 320227.24 | 3645077.08 | 4175089.52 | 140596.10 | 0.175999E+09 | 30278.75 | 0.36 |
July | 0.00 | 0.100383E+10 | 381237.50 | 72190.56 | 0.00 | 723.68 | 1219549.29 | 19647.23 | 0.36 |
August | 0.00 | 0.712779E+09 | 171086.73 | 1782495.80 | 862244.85 | 98369.07 | 69035641.91 | 19603.04 | 0.36 |
September | 7061515.02 | 0.266790E+09 | 215070.45 | 5186591.09 | 4171720.46 | 11474931.40 | 0.428776E+09 | 14175.14 | 0.35 |
October | 30397349.75 | 51980517.27 | 1883.42 | 6098297.16 | 0.00 | 0.193015E+09 | 0.774458E+09 | 4201.15 | 0.35 |
November | 68021816.65 | 0.00 | 0.00 | 1207499.82 | 0.00 | 0.100962E+10 | 0.297467E+09 | 0.00 | 0.35 |
December | 58165296.36 | 0.00 | 0.00 | 347174.66 | 0.00 | 0.128990E+10 | 58568104.78 | 0.00 | 0.36 |
Annual Sum or Average | 0.440556E+09 | 0.260953E+10 | 1102539.27 | 34334102.60 | 9672835.26 | 0.681526E+10 | 0.369725E+10 | 89484.98 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 72190.56 | 0.00 | 723.68 | 1219549.29 | 0.00 | 0.35 |
Maximum of Months | 68317778.77 | 0.100383E+10 | 381237.50 | 8251882.90 | 4175089.52 | 0.137799E+10 | 0.881564E+09 | 30278.75 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36408149.92 | 0.00 | 0.00 | 55921.22 | 0.00 | 0.141642E+10 | 6826093.90 | 0.00 | 0.35 |
February | 32962536.67 | 0.00 | 0.00 | 132849.12 | 0.00 | 0.127686E+10 | 24304571.56 | 0.00 | 0.35 |
March | 69444816.25 | 15120.54 | 0.00 | 1321728.34 | 94949.11 | 0.114049E+10 | 0.199252E+09 | 0.00 | 0.35 |
April | 64508233.77 | 848197.85 | 0.00 | 3981081.25 | 55762.16 | 0.663718E+09 | 0.548851E+09 | 0.00 | 0.35 |
May | 46283100.40 | 22541708.26 | 13449.42 | 7909312.22 | 368831.33 | 89075495.50 | 0.865103E+09 | 1164.17 | 0.36 |
June | 2448461.05 | 0.549475E+09 | 233572.97 | 3584100.08 | 5478642.26 | 140596.10 | 0.175329E+09 | 27232.90 | 0.36 |
July | 0.00 | 0.100394E+10 | 277494.09 | 71452.24 | 0.00 | 723.68 | 1220287.61 | 16198.53 | 0.36 |
August | 0.00 | 0.712228E+09 | 126517.68 | 1648034.91 | 1459950.48 | 98369.07 | 69170102.80 | 17196.99 | 0.36 |
September | 15636467.74 | 0.266020E+09 | 248344.73 | 4319387.72 | 4907452.62 | 12454424.40 | 0.420089E+09 | 15194.96 | 0.35 |
October | 51344652.35 | 48334914.72 | 10396.92 | 4028262.31 | 3632707.54 | 0.333982E+09 | 0.614612E+09 | 8582.67 | 0.35 |
November | 69562134.09 | 0.00 | 0.00 | 482844.28 | 0.00 | 0.115670E+10 | 0.149577E+09 | 0.00 | 0.35 |
December | 45476277.37 | 0.00 | 0.00 | 35342.36 | 0.00 | 0.135763E+10 | 3846217.09 | 0.00 | 0.36 |
Annual Sum or Average | 0.434075E+09 | 0.260340E+10 | 909775.81 | 27570316.08 | 15998295.49 | 0.744757E+10 | 0.307818E+10 | 85570.21 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 35342.36 | 0.00 | 723.68 | 1220287.61 | 0.00 | 0.35 |
Maximum of Months | 69562134.09 | 0.100394E+10 | 277494.09 | 7909312.22 | 5478642.26 | 0.141642E+10 | 0.865103E+09 | 27232.90 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.883817E+09 | 0.00 | 0.00 | 762.21 | 487358.09 | 0.00 | 7912118.16 | 0.00 | 0.02 |
February | 0.936100E+09 | 0.00 | 0.00 | 207689.30 | 0.00 | 0.00 | 0.201289E+09 | 0.00 | 0.02 |
March | 0.899766E+09 | 0.00 | 0.00 | 668953.15 | 0.00 | 0.00 | 0.431785E+09 | 0.00 | 0.02 |
April | 0.715506E+09 | 0.00 | 0.00 | 1064217.34 | 0.00 | 0.00 | 0.465394E+09 | 0.00 | 0.02 |
May | 0.217478E+09 | 20702874.60 | 0.00 | 1462011.26 | 0.00 | 0.00 | 0.728969E+09 | 0.00 | 0.02 |
June | 0.00 | 0.509674E+09 | 0.00 | 884598.42 | 0.00 | 0.00 | 0.182137E+09 | 0.00 | 0.02 |
July | 0.00 | 0.986516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.713146E+09 | 0.00 | 793520.89 | 0.00 | 0.00 | 20737457.58 | 0.00 | 0.02 |
September | 68664913.46 | 0.294808E+09 | 0.00 | 2236383.59 | 18107595.43 | 0.00 | 0.333105E+09 | 0.00 | 0.02 |
October | 72344423.26 | 65174991.48 | 0.00 | 4135820.48 | 0.00 | 0.00 | 0.843151E+09 | 0.00 | 0.02 |
November | 0.948323E+09 | 0.00 | 0.00 | 907137.57 | 0.00 | 0.00 | 0.390442E+09 | 0.00 | 0.02 |
December | 0.993632E+09 | 0.00 | 0.00 | 487870.16 | 0.00 | 0.00 | 0.279763E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.573563E+10 | 0.259002E+10 | 0.00 | 12848964.36 | 18594953.52 | 0.00 | 0.388469E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.993632E+09 | 0.986516E+09 | 0.00 | 4135820.48 | 18107595.43 | 0.00 | 0.843151E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.947631E+09 | 0.00 | 0.00 | 8323181.47 | 0.00 | 0.118334E+11 | 0.700073E+10 | 0.00 | 0.40 |
February | 0.902751E+09 | 0.00 | 0.00 | 5971616.55 | 0.00 | 0.117121E+11 | 0.546858E+10 | 0.00 | 0.40 |
March | 0.998220E+09 | 204998.14 | 0.00 | 31877770.04 | 1287281.25 | 0.332277E+10 | 0.147703E+11 | 0.00 | 0.40 |
April | 0.885969E+09 | 11499520.22 | 0.00 | 70680561.17 | 756000.56 | 0.154489E+09 | 0.162569E+11 | 0.00 | 0.40 |
May | 0.651577E+09 | 0.290425E+09 | 0.00 | 0.114239E+09 | 20384479.33 | 29844348.03 | 0.128754E+11 | 0.00 | 0.40 |
June | 44052428.21 | 0.725706E+10 | 516786.14 | 41311271.82 | 0.269754E+09 | 1099150.13 | 0.237427E+10 | 35497.04 | 0.40 |
July | 0.00 | 0.133402E+11 | 0.00 | 888095.94 | 0.274682E+09 | 0.00 | 16634596.99 | 0.00 | 0.40 |
August | 11149628.59 | 0.949329E+10 | 75032.68 | 18787049.48 | 0.184471E+09 | 388198.58 | 0.931132E+09 | 9292.46 | 0.40 |
September | 0.240305E+09 | 0.350830E+10 | 0.00 | 62834467.65 | 0.168388E+09 | 11858848.38 | 0.581980E+10 | 0.00 | 0.40 |
October | 0.694793E+09 | 0.650354E+09 | 394611.25 | 70398458.26 | 54030607.81 | 90975765.88 | 0.127552E+11 | 34134.37 | 0.40 |
November | 0.996625E+09 | 0.00 | 0.00 | 35741256.63 | 0.00 | 0.288369E+10 | 0.147435E+11 | 0.00 | 0.40 |
December | 0.959051E+09 | 0.00 | 0.00 | 10411514.27 | 0.00 | 0.889250E+10 | 0.921337E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.733212E+10 | 0.345514E+11 | 986430.07 | 0.471464E+09 | 0.973753E+09 | 0.389331E+11 | 0.102226E+12 | 78923.87 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 888095.94 | 0.00 | 0.00 | 16634596.99 | 0.00 | 0.40 |
Maximum of Months | 0.998220E+09 | 0.133402E+11 | 516786.14 | 0.114239E+09 | 0.274682E+09 | 0.118334E+11 | 0.162569E+11 | 35497.04 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53269098.53 | 0.00 | 0.00 | 241439.05 | 0.00 | 0.136385E+10 | 42347404.92 | 0.00 | 0.35 |
February | 54707326.23 | 0.00 | 0.00 | 405067.01 | 0.00 | 0.121248E+10 | 66673900.22 | 0.00 | 0.35 |
March | 63060749.44 | 15120.54 | 0.00 | 2046697.73 | 94949.11 | 0.102270E+10 | 0.322706E+09 | 0.00 | 0.35 |
April | 48341707.98 | 903960.01 | 0.00 | 4942237.37 | 0.00 | 0.578061E+09 | 0.649713E+09 | 0.00 | 0.35 |
May | 20023672.71 | 22552133.16 | 3564.27 | 8717756.34 | 368831.33 | 92982433.15 | 0.886647E+09 | 624.42 | 0.36 |
June | 0.00 | 0.549107E+09 | 185813.89 | 3932456.85 | 5909522.00 | 121804.26 | 0.177448E+09 | 12305.47 | 0.36 |
July | 0.00 | 0.100414E+10 | 89511.56 | 77544.78 | 0.00 | 0.00 | 1214918.75 | 1156.10 | 0.36 |
August | 0.00 | 0.713073E+09 | 25082.18 | 1932053.48 | 732722.55 | 5434.20 | 68979019.09 | 1486.75 | 0.36 |
September | 4987831.85 | 0.266872E+09 | 137621.41 | 5722714.78 | 4171720.46 | 10518781.16 | 0.431270E+09 | 9460.18 | 0.35 |
October | 22349546.77 | 51980517.27 | 3272.37 | 6429934.32 | 0.00 | 0.209339E+09 | 0.765849E+09 | 2812.20 | 0.35 |
November | 66168695.88 | 0.00 | 0.00 | 1717958.40 | 0.00 | 0.968341E+09 | 0.340091E+09 | 0.00 | 0.35 |
December | 58017641.34 | 0.00 | 0.00 | 507311.89 | 0.00 | 0.125696E+10 | 91504126.03 | 0.00 | 0.36 |
Annual Sum or Average | 0.390926E+09 | 0.260864E+10 | 444865.68 | 36673172.00 | 11277745.44 | 0.671535E+10 | 0.384444E+10 | 27845.12 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 77544.78 | 0.00 | 0.00 | 1214918.75 | 0.00 | 0.35 |
Maximum of Months | 66168695.88 | 0.100414E+10 | 185813.89 | 8717756.34 | 5909522.00 | 0.136385E+10 | 0.886647E+09 | 12305.47 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35688301.39 | 0.00 | 0.00 | 40912.62 | 0.00 | 0.141445E+10 | 9524655.04 | 0.00 | 0.35 |
February | 35540341.00 | 0.00 | 0.00 | 104453.03 | 0.00 | 0.127830E+10 | 20319242.30 | 0.00 | 0.35 |
March | 69444816.25 | 15120.54 | 0.00 | 1105294.35 | 94949.11 | 0.112723E+10 | 0.212734E+09 | 0.00 | 0.35 |
April | 63752836.42 | 903960.01 | 0.00 | 4130699.58 | 0.00 | 0.636373E+09 | 0.576802E+09 | 0.00 | 0.35 |
May | 30297451.49 | 22552133.16 | 3430.64 | 8351553.01 | 368831.33 | 0.107325E+09 | 0.862397E+09 | 758.05 | 0.36 |
June | 137089.80 | 0.548892E+09 | 182269.11 | 3859788.99 | 6128441.85 | 121804.26 | 0.177384E+09 | 11886.97 | 0.36 |
July | 0.00 | 0.100414E+10 | 89248.31 | 76678.75 | 0.00 | 0.00 | 1215784.78 | 1419.35 | 0.36 |
August | 0.00 | 0.712345E+09 | 25056.66 | 1800828.12 | 1459950.48 | 5434.20 | 69110244.45 | 1512.28 | 0.36 |
September | 11791921.92 | 0.266684E+09 | 173513.35 | 4829894.10 | 4322260.84 | 12123815.51 | 0.423753E+09 | 11438.32 | 0.35 |
October | 50521949.16 | 50016946.37 | 98334.48 | 4052759.59 | 1859651.57 | 0.337382E+09 | 0.612011E+09 | 11669.41 | 0.35 |
November | 69850877.10 | 0.00 | 0.00 | 643692.53 | 0.00 | 0.110058E+10 | 0.205242E+09 | 0.00 | 0.35 |
December | 50147062.79 | 0.00 | 0.00 | 83079.60 | 0.00 | 0.134085E+10 | 15905229.91 | 0.00 | 0.36 |
Annual Sum or Average | 0.417173E+09 | 0.260555E+10 | 571852.55 | 29079634.25 | 14234085.18 | 0.735474E+10 | 0.318640E+10 | 38684.36 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 40912.62 | 0.00 | 0.00 | 1215784.78 | 0.00 | 0.35 |
Maximum of Months | 69850877.10 | 0.100414E+10 | 182269.11 | 8351553.01 | 6128441.85 | 0.141445E+10 | 0.862397E+09 | 11886.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185430E+11 | 0.00 | 0.00 | 0.54 |
February | 0.852113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150855E+11 | 0.00 | 0.00 | 0.54 |
March | 0.184179E+11 | 0.00 | 0.00 | 0.00 | 5122002.83 | 0.650104E+10 | 0.00 | 0.00 | 0.54 |
April | 0.211651E+11 | 0.00 | 0.00 | 0.00 | 30076482.98 | 0.221817E+10 | 0.00 | 0.00 | 0.54 |
May | 0.182778E+11 | 0.00 | 0.00 | 0.00 | 0.426167E+09 | 11760348.96 | 0.00 | 0.00 | 0.54 |
June | 0.340330E+10 | 0.00 | 0.00 | 0.00 | 0.992443E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.107712E+09 | 0.00 | 0.00 | 0.00 | 0.194624E+11 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.177867E+10 | 0.00 | 0.00 | 0.00 | 0.124191E+11 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.858153E+10 | 0.00 | 0.00 | 0.00 | 0.529009E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.197953E+11 | 0.00 | 0.00 | 0.00 | 0.953011E+09 | 11941502.79 | 0.00 | 0.00 | 0.54 |
November | 0.191795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659450E+10 | 0.00 | 0.00 | 0.54 |
December | 0.105900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142361E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.137557E+12 | 0.00 | 0.00 | 0.00 | 0.485105E+11 | 0.632020E+11 | 0.00 | 0.00 | 0.54 |
Minimum of Months | 0.107712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.211651E+11 | 0.00 | 0.00 | 0.00 | 0.194624E+11 | 0.185430E+11 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11250688.69 | 0.00 | 0.00 | 58018.99 | 0.00 | 0.348985E+09 | 4633162.39 | 0.00 | 0.35 |
February | 12294799.72 | 0.00 | 0.00 | 121325.24 | 0.00 | 0.311781E+09 | 9368328.36 | 0.00 | 0.35 |
March | 16595784.75 | 3780.14 | 0.00 | 563114.58 | 23737.28 | 0.273850E+09 | 61618506.66 | 0.00 | 0.35 |
April | 13846376.03 | 225990.00 | 0.00 | 1241794.61 | 0.00 | 0.171146E+09 | 0.134030E+09 | 0.00 | 0.35 |
May | 5715247.24 | 5638988.29 | 0.00 | 2238510.71 | 92207.83 | 35577312.74 | 0.208562E+09 | 92.18 | 0.36 |
June | 0.00 | 0.138493E+09 | 57598.44 | 989593.33 | 246847.26 | 53167.91 | 44332853.38 | 6357.01 | 0.36 |
July | 0.00 | 0.250997E+09 | 57533.35 | 18560.18 | 0.00 | 180.92 | 304374.78 | 2717.04 | 0.36 |
August | 0.00 | 0.178417E+09 | 36830.85 | 472053.97 | 0.00 | 24592.27 | 17232480.46 | 3810.74 | 0.36 |
September | 1613283.63 | 66876383.21 | 32180.99 | 1387683.66 | 886148.67 | 4332723.31 | 0.105791E+09 | 2966.13 | 0.35 |
October | 6379382.94 | 12995129.32 | 712.25 | 1515009.09 | 0.00 | 72168946.50 | 0.170929E+09 | 808.89 | 0.35 |
November | 16719131.28 | 0.00 | 0.00 | 259750.97 | 0.00 | 0.269056E+09 | 58044792.78 | 0.00 | 0.35 |
December | 12533046.56 | 0.00 | 0.00 | 70333.45 | 0.00 | 0.332041E+09 | 7101855.44 | 0.00 | 0.36 |
Annual Sum or Average | 96947740.84 | 0.653647E+09 | 184855.88 | 8935748.78 | 1248941.03 | 0.181902E+10 | 0.821948E+09 | 16751.99 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18560.18 | 0.00 | 180.92 | 304374.78 | 0.00 | 0.35 |
Maximum of Months | 16719131.28 | 0.250997E+09 | 57598.44 | 2238510.71 | 886148.67 | 0.348985E+09 | 0.208562E+09 | 6357.01 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3836873.66 | 0.00 | 0.00 | 9385.83 | 0.00 | 0.359628E+09 | 1452596.83 | 0.00 | 0.35 |
February | 6397594.07 | 0.00 | 0.00 | 17231.62 | 0.00 | 0.322945E+09 | 4206274.23 | 0.00 | 0.35 |
March | 15421479.43 | 3780.14 | 0.00 | 324492.40 | 23737.28 | 0.295932E+09 | 40949059.80 | 0.00 | 0.35 |
April | 15754113.28 | 225990.00 | 0.00 | 1042156.96 | 0.00 | 0.181567E+09 | 0.121902E+09 | 0.00 | 0.35 |
May | 7981258.17 | 5638988.29 | 0.00 | 2144451.50 | 92207.83 | 37810613.03 | 0.204156E+09 | 92.18 | 0.36 |
June | 0.00 | 0.138384E+09 | 58227.22 | 975748.86 | 355167.97 | 45366.01 | 44354499.76 | 5728.23 | 0.36 |
July | 0.00 | 0.250997E+09 | 58100.85 | 18362.70 | 0.00 | 180.92 | 304572.26 | 2149.53 | 0.36 |
August | 0.00 | 0.178436E+09 | 18890.92 | 436089.69 | 0.00 | 24592.27 | 17268444.73 | 3378.98 | 0.36 |
September | 2924325.51 | 66703443.99 | 44997.84 | 1152457.69 | 1045991.76 | 6669240.78 | 0.102379E+09 | 3245.41 | 0.35 |
October | 12672754.26 | 12656144.93 | 1154.27 | 973223.42 | 338090.72 | 0.109381E+09 | 0.127965E+09 | 1260.54 | 0.35 |
November | 14427843.65 | 0.00 | 0.00 | 96911.36 | 0.00 | 0.305517E+09 | 24038179.64 | 0.00 | 0.35 |
December | 6797850.73 | 0.00 | 0.00 | 8992.90 | 0.00 | 0.344141E+09 | 798015.92 | 0.00 | 0.36 |
Annual Sum or Average | 86214092.76 | 0.653045E+09 | 181371.11 | 7199504.93 | 1855195.55 | 0.196366E+10 | 0.689773E+09 | 15854.87 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8992.90 | 0.00 | 180.92 | 304572.26 | 0.00 | 0.35 |
Maximum of Months | 15754113.28 | 0.250997E+09 | 58227.22 | 2144451.50 | 1045991.76 | 0.359628E+09 | 0.204156E+09 | 5728.23 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65425236.10 | 0.00 | 0.00 | 2520312.69 | 0.00 | 0.186450E+10 | 0.411125E+09 | 0.00 | 0.40 |
February | 46108883.01 | 0.00 | 0.00 | 3268347.43 | 0.00 | 0.154760E+10 | 0.545188E+09 | 0.00 | 0.40 |
March | 52223043.17 | 176717.30 | 0.00 | 5654559.75 | 0.00 | 0.116785E+10 | 0.103886E+10 | 0.00 | 0.40 |
April | 56091354.56 | 1451311.67 | 0.00 | 8042239.57 | 0.00 | 0.639208E+09 | 0.135340E+10 | 0.00 | 0.40 |
May | 24902670.40 | 36180748.00 | 30104.26 | 12758430.68 | 591554.34 | 38144084.15 | 0.154314E+10 | 4025.30 | 0.40 |
June | 0.00 | 0.886518E+09 | 350517.55 | 5229159.95 | 4522401.88 | 196634.51 | 0.285977E+09 | 8200.25 | 0.40 |
July | 0.00 | 0.161153E+10 | 754273.22 | 115508.28 | 0.00 | 0.00 | 1959547.46 | 7229.08 | 0.40 |
August | 0.00 | 0.114564E+10 | 407614.74 | 2862416.96 | 0.00 | 23510.54 | 0.110971E+09 | 9604.44 | 0.40 |
September | 7175700.23 | 0.429471E+09 | 224543.67 | 10114473.12 | 5690861.98 | 1240510.51 | 0.707958E+09 | 11405.23 | 0.40 |
October | 8680435.87 | 83447965.05 | 14395.49 | 14891131.05 | 0.00 | 91670935.53 | 0.149663E+10 | 2352.01 | 0.40 |
November | 62750317.32 | 0.00 | 0.00 | 6618543.41 | 0.00 | 0.985834E+09 | 0.115448E+10 | 0.00 | 0.40 |
December | 58379231.95 | 0.00 | 0.00 | 4303222.88 | 0.00 | 0.157930E+10 | 0.616935E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.381737E+09 | 0.419442E+10 | 1781448.93 | 76378345.80 | 10804818.20 | 0.791556E+10 | 0.926663E+10 | 42816.31 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 115508.28 | 0.00 | 0.00 | 1959547.46 | 0.00 | 0.40 |
Maximum of Months | 65425236.10 | 0.161153E+10 | 754273.22 | 14891131.05 | 5690861.98 | 0.186450E+10 | 0.154314E+10 | 11405.23 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127886E+11 | 0.00 | 0.00 | 33732514.72 | 0.00 | 0.00 | 0.343284E+11 | 0.00 | 4.55 |
February | 0.108310E+11 | 0.00 | 0.00 | 30219274.27 | 0.00 | 0.00 | 0.313466E+11 | 0.00 | 4.56 |
March | 0.561325E+10 | 1260630.78 | 0.00 | 45280809.98 | 7711691.54 | 0.00 | 0.402682E+11 | 0.00 | 4.67 |
April | 0.197723E+10 | 45493058.70 | 0.00 | 50069776.42 | 7192562.21 | 0.00 | 0.418063E+11 | 0.00 | 4.75 |
May | 0.108183E+10 | 0.670671E+09 | 0.00 | 54426809.64 | 79195817.10 | 0.00 | 0.332651E+11 | 0.00 | 4.72 |
June | 0.106769E+09 | 0.164113E+11 | 0.00 | 20674064.28 | 0.130087E+10 | 0.00 | 0.616030E+10 | 0.00 | 4.63 |
July | 2570524.74 | 0.335257E+11 | 0.00 | 975765.05 | 0.148343E+10 | 0.00 | 0.187344E+09 | 0.00 | 4.62 |
August | 49905775.94 | 0.213905E+11 | 0.00 | 13862259.47 | 0.104970E+10 | 0.00 | 0.315391E+10 | 0.00 | 4.64 |
September | 0.726585E+09 | 0.811904E+10 | 0.00 | 32540317.56 | 0.127055E+10 | 0.00 | 0.149014E+11 | 0.00 | 4.59 |
October | 0.179006E+10 | 0.130389E+10 | 0.00 | 46579736.75 | 0.368999E+09 | 0.00 | 0.348375E+11 | 0.00 | 4.67 |
November | 0.595076E+10 | 0.00 | 0.00 | 42288475.84 | 0.00 | 0.00 | 0.414073E+11 | 0.00 | 4.69 |
December | 0.966742E+10 | 0.00 | 0.00 | 37888183.55 | 0.00 | 0.00 | 0.350072E+11 | 0.00 | 4.61 |
Annual Sum or Average | 0.505859E+11 | 0.814679E+11 | 0.00 | 0.408538E+09 | 0.556765E+10 | 0.00 | 0.316670E+12 | 0.00 | 4.64 |
Minimum of Months | 2570524.74 | 0.00 | 0.00 | 975765.05 | 0.00 | 0.00 | 0.187344E+09 | 0.00 | 4.55 |
Maximum of Months | 0.127886E+11 | 0.335257E+11 | 0.00 | 54426809.64 | 0.148343E+10 | 0.00 | 0.418063E+11 | 0.00 | 4.75 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.703179E+10 | 0.00 | 0.00 | 46325219.67 | 0.00 | 0.00 | 0.435508E+11 | 0.00 | 4.88 |
February | 0.684555E+10 | 0.00 | 0.00 | 41817314.81 | 0.00 | 0.00 | 0.383889E+11 | 0.00 | 4.89 |
March | 0.213934E+10 | 5460809.67 | 0.00 | 59660361.27 | 3957129.89 | 0.00 | 0.476929E+11 | 0.00 | 5.07 |
April | 0.785594E+09 | 49354376.14 | 0.00 | 64496020.76 | 5947916.38 | 0.00 | 0.468650E+11 | 0.00 | 5.15 |
May | 0.546751E+09 | 0.730276E+09 | 0.00 | 68698014.13 | 59549649.60 | 0.00 | 0.367586E+11 | 0.00 | 5.09 |
June | 49156568.24 | 0.180218E+11 | 0.00 | 24694598.61 | 0.762842E+09 | 0.00 | 0.670130E+10 | 0.00 | 4.93 |
July | 1018925.91 | 0.362901E+11 | 0.00 | 1089208.57 | 0.815808E+09 | 0.00 | 0.200338E+09 | 0.00 | 4.90 |
August | 18913429.27 | 0.231532E+11 | 0.00 | 15872845.58 | 0.611669E+09 | 0.00 | 0.340394E+10 | 0.00 | 4.92 |
September | 0.400943E+09 | 0.941576E+10 | 0.00 | 40672663.32 | 0.511074E+09 | 0.00 | 0.164556E+11 | 0.00 | 4.89 |
October | 0.934085E+09 | 0.148394E+10 | 0.00 | 58749792.04 | 0.276803E+09 | 0.00 | 0.387098E+11 | 0.00 | 5.03 |
November | 0.232624E+10 | 0.00 | 0.00 | 55760010.90 | 0.00 | 0.00 | 0.489818E+11 | 0.00 | 5.08 |
December | 0.341812E+10 | 0.00 | 0.00 | 51605610.99 | 0.00 | 0.00 | 0.448523E+11 | 0.00 | 4.98 |
Annual Sum or Average | 0.244975E+11 | 0.891500E+11 | 0.00 | 0.529442E+09 | 0.304765E+10 | 0.00 | 0.372561E+12 | 0.00 | 4.98 |
Minimum of Months | 1018925.91 | 0.00 | 0.00 | 1089208.57 | 0.00 | 0.00 | 0.200338E+09 | 0.00 | 4.88 |
Maximum of Months | 0.703179E+10 | 0.362901E+11 | 0.00 | 68698014.13 | 0.815808E+09 | 0.00 | 0.489818E+11 | 0.00 | 5.15 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20826003.66 | 0.00 | 0.00 | 0.111903E+09 | 0.00 | 0.00 | 0.677546E+11 | 0.00 | 21.14 |
February | 16441342.89 | 0.00 | 0.00 | 0.101938E+09 | 0.00 | 0.00 | 0.610460E+11 | 0.00 | 21.36 |
March | 0.00 | 11879050.86 | 0.00 | 0.114748E+09 | 0.00 | 0.00 | 0.654924E+11 | 0.00 | 21.63 |
April | 0.00 | 78871367.24 | 0.00 | 0.112853E+09 | 0.00 | 0.00 | 0.602502E+11 | 0.00 | 21.39 |
May | 0.00 | 0.112742E+10 | 0.00 | 0.113774E+09 | 0.00 | 0.00 | 0.441551E+11 | 0.00 | 20.50 |
June | 141187.02 | 0.234788E+11 | 0.00 | 33883184.44 | 7462185.66 | 0.00 | 0.759166E+10 | 0.00 | 19.53 |
July | 1322015.11 | 0.461852E+11 | 0.00 | 1438415.23 | 3831275.11 | 0.00 | 0.217439E+09 | 0.00 | 19.47 |
August | 1430570.42 | 0.303499E+11 | 0.00 | 19515920.29 | 2803604.16 | 0.00 | 0.363303E+10 | 0.00 | 19.62 |
September | 0.00 | 0.123534E+11 | 0.00 | 71973539.52 | 1561784.28 | 0.00 | 0.197491E+11 | 0.00 | 19.54 |
October | 0.00 | 0.240439E+10 | 0.00 | 0.103022E+09 | 424884.28 | 0.00 | 0.495377E+11 | 0.00 | 20.69 |
November | 2714538.07 | 0.00 | 0.00 | 0.110520E+09 | 0.00 | 0.00 | 0.670792E+11 | 0.00 | 21.54 |
December | 5405518.48 | 0.00 | 0.00 | 0.113773E+09 | 0.00 | 0.00 | 0.645064E+11 | 0.00 | 21.56 |
Annual Sum or Average | 48281175.65 | 0.115990E+12 | 0.00 | 0.100934E+10 | 16083733.49 | 0.00 | 0.511013E+12 | 0.00 | 20.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1438415.23 | 0.00 | 0.00 | 0.217439E+09 | 0.00 | 19.47 |
Maximum of Months | 20826003.66 | 0.461852E+11 | 0.00 | 0.114748E+09 | 7462185.66 | 0.00 | 0.677546E+11 | 0.00 | 21.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:45:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.646238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642996E+10 | 0.00 | 0.00 | 0.99 |
February | 0.543334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614671E+10 | 0.00 | 0.00 | 1.00 |
March | 0.107081E+11 | 0.00 | 0.00 | 0.00 | 2512553.33 | 0.151570E+10 | 0.00 | 0.00 | 0.99 |
April | 0.113086E+11 | 0.00 | 0.00 | 0.00 | 14753753.55 | 0.161907E+09 | 0.00 | 0.00 | 1.00 |
May | 0.897178E+10 | 0.00 | 0.00 | 0.00 | 0.209052E+09 | 0.00 | 0.00 | 0.00 | 1.00 |
June | 0.166946E+10 | 0.00 | 0.00 | 0.00 | 0.486834E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 52836955.39 | 17325416.81 | 0.00 | 0.00 | 0.952980E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
August | 0.872509E+09 | 14324314.88 | 0.00 | 0.00 | 0.607778E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 0.420960E+10 | 0.00 | 0.00 | 0.00 | 0.259501E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
October | 0.969495E+10 | 0.00 | 0.00 | 0.00 | 0.467491E+09 | 21322618.78 | 0.00 | 0.00 | 1.00 |
November | 0.112893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135394E+10 | 0.00 | 0.00 | 1.00 |
December | 0.814511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403312E+10 | 0.00 | 0.00 | 1.00 |
Annual Sum or Average | 0.788179E+11 | 31649731.69 | 0.00 | 0.00 | 0.237647E+11 | 0.196627E+11 | 0.00 | 0.00 | 1.00 |
Minimum of Months | 52836955.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.113086E+11 | 17325416.81 | 0.00 | 0.00 | 0.952980E+10 | 0.642996E+10 | 0.00 | 0.00 | 1.01 |