Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:50
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:50:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11688.67 | 1030.27 | 1030.27 |
Net Site Energy | 11688.67 | 1030.27 | 1030.27 |
Total Source Energy | 24100.72 | 2124.29 | 2124.29 |
Net Source Energy | 24100.72 | 2124.29 | 2124.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2132.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 819.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 818.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.02 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 973.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 545.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 205.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2279.89 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5487.38 | 6201.29 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2132.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 819.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 818.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 163.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 545.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 64.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 205.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.76 | 2279.89 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.05 | 388.92 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 263.08 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.67 | 546.60 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.05 | 388.92 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 263.08 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.67 | 546.60 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5487.376 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5487.376 | 100.00 |
Total On-Site and Utility Electric Sources | 5487.376 | 100.00 |
Total Electricity End Uses | 5487.376 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 316.86 | 6.35 |
Air to Air Heat Recovery for Heating | 4670.27 | 93.65 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4987.13 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 272.67 |
Time Setpoint Not Met During Occupied Cooling | 269.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7975.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 7.2656 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 10.2688 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 10.2688 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.4563 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.1656 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 9.0094 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 10.2688 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 7.4594 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 7.4594 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 7.4594 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 7.4594 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 7.4594 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 7.4594 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.0094 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.0094 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 10.2688 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 6.3938 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 7.6469 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 7.6469 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:10 | 02-FEB-20:00 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 718619.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180711.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71869.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50342.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23808.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5055.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3770.21 | 175071.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2393.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 436930.12 | 983401.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 718619.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 180711.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 71869.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1303.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23808.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5055.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3770.21 | 175071.16 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1091.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2311.69 | 0.00 | 0.00 | 0.00 |
Cooling | 2595.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2592.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 516.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.49 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3082.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1727.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 205.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 650.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.44 | 2471.40 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17378.52 | 6722.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 203.76 | 0.00 | 0.00 | 0.00 |
Cooling | 228.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 228.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 57.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1531.78 | 592.51 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 203.76 | 0.00 | 0.00 | 0.00 |
Cooling | 228.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 228.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.12 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 57.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1531.78 | 592.51 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.30 | 0.655639 | 0.571000 | 1.31 | 1.00 | 0.500000 | 0.000581 | 0.000189 | 1.31 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.312266 | 0.163670 | 0.571000 | 0.178304 | 0.571000 | 0.500000 | 0.002328 | 0.000117 | 0.194732 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.222640 | 0.265827 | 0.571000 | 0.127127 | 0.708871 | 0.500000 | 0.001433 | 0.000039 | 0.127127 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.163617 | 0.764914 | 0.571000 | 0.093426 | 1.00 | 0.500000 | 0.000498 | 0.000054 | 0.093426 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.090462 | 0.798195 | 0.571000 | 0.051654 | 1.00 | 0.500000 | 0.000477 | 0.000040 | 0.065873 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.40 | 0.069340 | 0.571000 | 1.94 | 0.571000 | 0.500000 | 0.021804 | 0.000274 | 1.94 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.36 | 0.105452 | 0.571000 | 0.779255 | 0.571000 | 0.500000 | 0.003613 | 0.000336 | 0.779255 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.70 | 0.211920 | 0.571000 | 2.69 | 0.571000 | 0.500000 | 0.001798 | 0.000812 | 2.69 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.571000 | 0.677723 | 1.00 | 0.500000 | 0.000381 | 0.000334 | 0.677723 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.15 | 0.117328 | 0.571000 | 1.23 | 0.571000 | 0.500000 | 0.003247 | 0.000311 | 1.23 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.26 | 0.111706 | 0.571000 | 1.29 | 0.571000 | 0.500000 | 0.003411 | 0.000321 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.34 | 0.700000 | 0.571000 | 1.34 | 0.571000 | 0.500000 | 0.011345 | 0.000216 | 1.34 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.591850 | 0.530606 | 0.571000 | 0.337946 | 1.00 | 0.500000 | 0.000718 | 0.000225 | 0.372552 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8551.54 | 0.000189 | 153.85 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5312.89 | 0.000117 | 115.16 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1778.21 | 0.000039 | 34.73 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2446.69 | 0.000054 | 52.50 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1797.16 | 0.000040 | 38.95 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12421.42 | 0.000274 | 223.17 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15215.13 | 0.000336 | 308.80 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 36772.37 | 0.000812 | 716.80 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 7884.02 | 0.000174 | 179.49 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 7905.73 | 0.000175 | 179.99 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 44442.20 | 0.000982 | 1011.80 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 44830.42 | 0.000990 | 1020.64 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 7845.60 | 0.000173 | 178.62 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 7867.21 | 0.000174 | 179.11 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15099.51 | 0.000334 | 313.22 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 2410.70 | 0.000053 | 54.88 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 2423.05 | 0.000054 | 55.16 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 11506.27 | 0.000254 | 261.95 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14072.73 | 0.000311 | 268.27 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14527.17 | 0.000321 | 276.28 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9770.46 | 0.000216 | 177.37 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10165.62 | 0.000225 | 220.35 |
VAV WITH REHEAT_HEATC | 308010.68 | 0.006805 | 3921.81 |
FLR_3_DOAS_HEATC | 30467.96 | 0.000673 | 387.94 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.15 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.14 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.82 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.93 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.03 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.03 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.300546 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.295531 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.15 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.15 | 0.000174 | 0.000453 |
ROOM_2_FLR_3 FAN COIL | 1.14 | 0.000175 | 0.000446 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.82 | 0.000982 | 0.002252 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.93 | 0.000990 | 0.002444 |
ROOM_5_FLR_3 FAN COIL | 1.03 | 0.000173 | 0.000408 |
ROOM_6_FLR_3 FAN COIL | 1.03 | 0.000174 | 0.000406 |
ROOM_1_FLR_6 FAN COIL | 0.300546 | 0.000053 | 0.000118 |
ROOM_2_FLR_6 FAN COIL | 0.295531 | 0.000054 | 0.000116 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.15 | 0.000254 | 0.000464 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.15 |
ROOM_2_FLR_3 FAN COILFAN | 1.14 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.82 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.93 |
ROOM_5_FLR_3 FAN COILFAN | 1.03 |
ROOM_6_FLR_3 FAN COILFAN | 1.03 |
ROOM_1_FLR_6 FAN COILFAN | 0.300546 |
ROOM_2_FLR_6 FAN COILFAN | 0.295531 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.15 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000453 | 1.15 | 0.008690 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000446 | 1.14 | 0.008693 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002252 | 5.82 | 0.008631 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002444 | 5.93 | 0.008872 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000408 | 1.03 | 0.008715 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000406 | 1.03 | 0.008716 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000118 | 0.300546 | 0.008683 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000116 | 0.295531 | 0.008686 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000464 | 1.15 | 0.008792 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.024784 | 0.012998 | 28.18 | 6.70 | 10.90 | 0.008683 | 693889.34 | 20.74 | |
FLR_3_DOAS_COOLC | 0.003132 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 87700.73 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.05 | 12.05 | 21.10 | 12.05 | 20.74 | 20.74 | 0.300000 | 0.581004 | 20.74 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.74 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 12.05 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 20.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024784 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.006805 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003132 | 0.000152 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000673 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.035025 | 8388.80 |
HEATSYS1 PUMP | 0.013776 | 3519.60 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.013776 | 1.65 |
COOLSYS1 | 0.035025 | 4.20 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.035025 | 2796.27 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 623524.72 | 623524.72 | 0.013776 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.035025 | 980608.01 | 981197.15 | 111.86 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 7.266 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.646 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 10.269 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 21.029 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 10.269 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 21.029 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.456 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 7.146 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.166 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 601.696 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.009 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.389 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.269 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.339 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 7.459 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 14.209 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 7.459 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 17.979 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.009 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.829 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.009 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.829 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.269 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2944.756 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 14377.467 | 7.266 | 135.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14377.467 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 688.740 | 10.269 | 63.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 688.740 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 797.564 | 10.269 | 63.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 797.564 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 684.177 | 4.166 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 422.272 | 4.456 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 422.272 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 325.084 | 4.166 | 38.700 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 325.084 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1701.531 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1701.531 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 13433.463 | 10.269 | 31.800 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13433.463 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 182.933 | 7.459 | 121.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.933 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 182.983 | 7.459 | 121.989 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.983 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2489.761 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.761 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 291.080 | 7.459 | 194.054 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.080 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 291.046 | 7.459 | 194.031 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 291.046 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 182.983 | 7.459 | 121.989 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 182.983 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2988.032 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2988.032 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2988.032 | 9.009 | 11.957 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2988.032 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1060.810 | 10.269 | 47.703 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1060.810 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2635.028 | 6.394 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.028 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4874 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.884 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.22071239E-14 | -0.25891382E-15 | -0.17018650E-09 | -0.41695020E-16 |
25 | 8 | 0.24744598E-07 | 0.66649001E-13 | 0.40731198E-03 | -0.28135460E-09 |
26 | 7 | -0.13120292E-01 | 0.33703133E-08 | -0.24350396E-01 | 0.14918252E-03 |
27 | 6 | 0.42922440 | 0.11607716E-05 | 0.49237259 | -0.50291810E-02 |
28 | 5 | -5.4235101 | 0.42968024E-04 | -4.5968048 | 0.66072313E-01 |
29 | 4 | 34.033019 | 0.34874410E-03 | 22.047808 | -0.43580094 |
30 | 3 | -113.41739 | 0.75474606E-03 | -56.824750 | 1.5468526 |
31 | 2 | 199.30218 | 0.42189037E-03 | 78.976973 | -2.9351941 |
32 | 1 | -171.96619 | 0.44777434E-04 | -55.576854 | 2.7596376 |
33 | 0 | 57.057407 | 0.25325413E-06 | 15.506813 | |
34 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
35 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
36 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
37 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
38 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
39 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
40 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
41 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
42 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
43 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
44 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
45 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
46 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
47 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
48 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
49 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 31 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
2 | RESWINDOW_U_0.37_SHGC_0.4 | 32 | 1 | VerySmooth | 2.102 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.55893E-002 | 0.31435 | 0.48047 | 0.48047 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11739 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 30191.31392 | 30191.31392 | 2.29985 | 2.29985 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.48300 | 1.53444E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 1938.33291 | 1938.33291 | 8.71054E-002 | 0.85413 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4098.33724 | 4098.33724 | 0.31227 | 0.31227 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4334.00924 | 4334.00924 | 0.19473 | 0.19473 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2922.30759 | 2922.30759 | 0.22264 | 0.22264 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53444E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1138.83801 | 1138.83801 | 5.11754E-002 | 9.16993E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2148.11669 | 2148.11669 | 0.16362 | 0.16362 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53444E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1976.96006 | 1976.96006 | 8.88374E-002 | 8.88374E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1187.66338 | 1187.66338 | 9.04623E-002 | 9.04623E-002 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53444E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1465.91176 | 1465.91176 | 6.58728E-002 | 6.58728E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44672.73677 | 44672.73677 | 3.40315 | 3.40315 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53444E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2652.39860 | 2652.39860 | 0.11918 | 0.23597 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17896.57888 | 17896.57888 | 1.36472 | 1.36472 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11297.67133 | 11297.67133 | 0.50762 | 0.67613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61723.06064 | 61723.06064 | 4.70383 | 4.70383 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23266.07294 | 23266.07294 | 1.04549 | 1.89326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11240.20696 | 11240.20696 | 1.15386 | 1.15386 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7884.35973 | 7884.35973 | 0.35636 | 0.35636 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11058.97954 | 11058.97954 | 1.13525 | 1.13525 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7906.07309 | 7906.07309 | 0.35734 | 0.35734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 56737.74888 | 56737.74888 | 5.82387 | 5.82387 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 44443.14103 | 44443.14103 | 2.00884 | 2.00884 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 57808.28445 | 57808.28445 | 5.93422 | 5.93422 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 44831.36744 | 44831.36744 | 2.02639 | 2.02639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10057.51982 | 10057.51982 | 1.03245 | 1.03245 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7845.93617 | 7845.93617 | 0.35462 | 0.35462 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9997.62601 | 9997.62601 | 1.02630 | 1.02630 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7867.55497 | 7867.55497 | 0.35560 | 0.35560 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 12573.24809 | 12573.24809 | 0.95766 | 1.18691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11689.40589 | 11689.40589 | 0.52529 | 0.52529 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2927.74463 | 2927.74463 | 0.30055 | 0.30055 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2410.80353 | 2410.80353 | 0.10896 | 0.10896 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2878.89479 | 2878.89479 | 0.29553 | 0.29553 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2423.14639 | 2423.14639 | 0.10952 | 0.10952 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11206.36225 | 11206.36225 | 1.15040 | 1.15040 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11506.64772 | 11506.64772 | 0.52009 | 0.52009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28240.69818 | 28240.69818 | 2.15398 | 2.15398 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7882.98249 | 7882.98249 | 0.35424 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29662.49486 | 29662.49486 | 2.26239 | 2.26239 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8026.08046 | 8026.08046 | 0.36067 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30689.05011 | 30689.05011 | 2.34390 | 2.34390 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53444E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3049.21232 | 3049.21232 | 0.13700 | 0.36721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7770.43683 | 7770.43683 | 0.59185 | 0.59185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8290.52049 | 8290.52049 | 0.37255 | 0.37255 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 367954.20 | 20.73625 | 20.73625 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 383244.24 | 7.74036 | 7.74036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43559.48 | 16.54799 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101559.87 | 6.19771 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29985 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65564 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31321 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.81112E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88936E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31321 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8551.54347 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88936E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.85228 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31227 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16367 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17830 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32786E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17382E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19473 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5312.88825 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17382E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.15604 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22264 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26583 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12713 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70887 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43326E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.92873E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12713 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1778.20703 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92873E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.72602 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.16362 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.76491 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.34255E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.98095E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.40566E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.34255E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2446.69037 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.40566E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.50452 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.04623E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.79820 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.16540E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.77327E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.97061E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.58728E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1797.16018 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.97061E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.95288 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40315 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.93398E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94320 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18040E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.74436E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94320 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12421.41905 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.74436E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.17286 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36472 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10545 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77925 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61301E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.36160E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77925 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15215.12863 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36160E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 308.80098 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.70383 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21192 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.68589 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79785E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.12441E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.68589 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36772.36791 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.12441E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 716.80082 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15386 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15386 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.15386 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74188E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.53346E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.53346E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.15386 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69029E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70997 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7884.01880 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74188E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.49342 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13525 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13525 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.13525 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74667E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.46360E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.46360E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.13525 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69302E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70996 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7905.73118 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74667E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.98764 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.82387 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.82387 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.82387 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.81896E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.25223E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.25223E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.82387 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.63078E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.71076 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44442.20386 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.81896E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1011.79985 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.93422 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.93422 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.93422 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.90473E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.44420E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.44420E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.93422 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.87246E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70984 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44830.42281 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.90473E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1020.63679 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03245 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.03245 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.03245 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73339E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.08309E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.08309E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.03245 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71505E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70992 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7845.59673 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73339E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.61883 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02630 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02630 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.02630 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.73816E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.06032E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.06032E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.02630 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71649E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70991 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7867.21455 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73816E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.11091 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.67772 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33605E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67772 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15099.50803 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33605E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 313.21968 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30055 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30055 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30055 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.32616E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.17854E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.17854E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.30055 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68296E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70998 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2410.70374 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32616E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.88200 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29553 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29553 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.29553 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.35342E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.15971E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.15971E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.29553 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68567E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70998 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2423.04610 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.35342E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.16294 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15040 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15040 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.15040 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.54217E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.64156E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.64156E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.15040 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.79185E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70975 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 11506.26544 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54217E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.95043 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15398 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11733 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22992 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24730E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.10920E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22992 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14072.72697 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.10920E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 268.27487 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26239 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11171 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29182 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41073E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.20960E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29182 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14527.16700 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20960E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.27673 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34390 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33837 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13446E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.15866E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33837 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9770.45596 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.15866E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.37055 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59185 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53061 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33795 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.18047E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24597E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37255 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10165.62033 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24597E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.34510 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.04785 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.04785 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.09956 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.04785 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.73625 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.73625 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.58100 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.73625 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.73625 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 12.05026 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 693889.33983 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.47841E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 20.73625 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.29983E-002 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.18062 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.90415 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 308010.67510 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.80512E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3921.81092 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 20.73625 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.47841E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.92135E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.80512E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 87700.73147 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.13247E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 30467.96244 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.73152E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 387.93976 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.13247E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.52018E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73152E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.50250E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8388.79844 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.37760E-002 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.65312 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.37760E-002 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3519.59566 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 623524.72393 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 623524.72000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37760E-002 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.50250E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.20301 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.50250E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2796.26615 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.50250E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 980608.00807 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 981197.15000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 111.85648 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8600.04 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5343.52 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1789.83 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2461.06 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1807.52 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12491.95 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15309.39 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 37013.35 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 8507.94 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 8531.37 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 47959.31 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 48378.20 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 8466.48 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 8489.81 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15190.41 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2601.42 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2614.73 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 12416.52 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14147.26 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14604.30 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9825.41 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10224.22 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 187370.29 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 18534.39 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 19581.70 | 15412.02 | 4169.68 | 0.79 | 2369.90 | 24.04 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 19274.97 | 15167.60 | 4107.36 | 0.79 | 2332.51 | 23.66 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 97831.80 | 77335.02 | 20496.78 | 0.79 | 11870.27 | 120.39 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 103775.46 | 80650.76 | 23124.70 | 0.78 | 12472.08 | 126.50 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 17595.04 | 13823.75 | 3771.29 | 0.79 | 2127.29 | 21.58 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 17494.50 | 13743.35 | 3751.15 | 0.79 | 2115.01 | 21.45 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 5094.09 | 4011.50 | 1082.59 | 0.79 | 616.71 | 6.25 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 5011.42 | 3945.62 | 1065.80 | 0.79 | 606.63 | 6.15 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 19857.05 | 15516.95 | 4340.10 | 0.78 | 2393.53 | 24.28 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 653707.24 | 412670.18 | 241037.06 | 0.63 | 93149.87 | 944.78 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67062.26 | 41857.36 | 25204.89 | 0.62 | 8925.08 | 90.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.4 | N/A | 2.102 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6695670772E-002 | 2.2020361561E-002 | Pass | Pass | 2.5790775025E-003 | 4.2056049067E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6547514533E-003 | 1.2378567633E-003 | Pass | Pass | 5.6347780557E-002 | 0.1324532159 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5603957010E-002 | 2.3557406824E-002 | Pass | Pass | 1.7021331742E-002 | 4.7175114310E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1177537556E-004 | 3.2102688824E-004 | Pass | Pass | 0.5902094803 | 2.6697997422 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6819484566E-004 | 3.4140496651E-004 | Pass | Pass | 3.0165099472E-002 | 5.6662118494E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.4214021499E-002 | 0.2239525342 | Pass | Pass | 1.8168009034E-002 | 5.0026976199E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7729739454E-003 | 1.7418777460E-002 | Pass | Pass | 0.1570198956 | 0.6473576700 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6631378916E-002 | 4.5241627910E-002 | Pass | Pass | 1.4769711678E-002 | 4.1058949405E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2402218518E-002 | 0.3066172734 | Pass | Pass | 9.0665072187E-002 | 0.2727173535 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2605509251E-002 | 0.3112528418 | Pass | Pass | 9.2339875006E-002 | 0.2730316531 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0123180164E-002 | 3.4031278207E-002 | Pass | Pass | 9.7200552981E-002 | 0.4902949653 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5481143297E-002 | 8.4967863048E-002 | Pass | Pass | 0.3044233285 | 1.0405302547 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2231385211E-002 | 0.3025095316 | Pass | Pass | 9.3967560850E-002 | 0.2821992848 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2522324399E-002 | 0.3068746352 | Pass | Pass | 9.3218337412E-002 | 0.2751770164 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3303981715E-004 | 3.3761265291E-004 | Pass | Pass | 3.3182125849E-002 | 4.7208057133E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2649487968E-002 | 0.3289282713 | Pass | Pass | 0.1226309905 | 0.4579297778 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2661947444E-002 | 0.3329815533 | Pass | Pass | 0.1459997991 | 0.5324046831 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.0938000848E-002 | 0.2613613987 | Pass | Pass | 0.2450700696 | 1.7816850889 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5791222261E-002 | 8.5743208341E-002 | Pass | Pass | 8.5213700082E-003 | 2.3303292022E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.6042545382E-002 | 6.8598059813E-002 | Pass | Pass | 9.1132937326E-003 | 2.9122180285E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6297283883E-002 | 0.1102017419 | Pass | Pass | 2.0492819685E-002 | 3.8194406618E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.9180564836E-004 | 4.9904410251E-004 | Pass | Pass | 0.2103572965 | 1.0754226830 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.394 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.394 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.394 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.102 | 0.394 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.394 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.394 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.102 | 0.394 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.085 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 432.93 | 2.087 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 781.15 | 2.084 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.2656 | 1978.83 | 14377.47 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.52 | 168.00 | 52.46 | 0.0000 | Y | 141.59 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 10.2688 | 67.07 | 688.74 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.58 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 10.2688 | 77.67 | 797.56 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.78 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 4.1656 | 164.24 | 684.18 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.4563 | 94.76 | 422.27 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 30.52 | 168.00 | 30.49 | 0.0000 | Y | 2.42 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 4.1656 | 78.04 | 325.08 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.58 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 9.0094 | 188.86 | 1701.53 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.69 | 0.0000 | Y | 15.55 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 10.2688 | 1308.19 | 13433.46 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 56.90 | 0.0000 | Y | 143.49 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 7.4594 | 156.09 | 1164.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 7.4594 | 156.07 | 1164.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 7.4594 | 1863.81 | 13902.90 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 111.28 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 7.4594 | 1864.32 | 13906.70 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 111.31 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 7.4594 | 156.09 | 1164.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 7.4594 | 156.07 | 1164.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 9.32 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 6.3938 | 1557.62 | 9959.04 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 7.4594 | 39.02 | 291.08 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.33 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 7.4594 | 39.02 | 291.05 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.33 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 7.4594 | 220.77 | 1646.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 13.18 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 9.0094 | 331.66 | 2988.03 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.62 | 0.0000 | Y | 30.08 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 9.0094 | 331.66 | 2988.03 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 53.62 | 0.0000 | Y | 30.08 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 10.2688 | 103.30 | 1060.81 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.67 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 6.3938 | 412.12 | 2635.03 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 7.6469 | 11345.29 | 86756.83 | 477.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1701.53 | 663.60 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1701.53 | 0.00 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 13433.46 | 940.34 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 13433.46 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2988.03 | 597.61 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2988.03 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2988.03 | 597.61 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2988.03 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 10390.54 | AstronomicalClock | - | 83.63 | 83.63 | 163.11 | |
Exterior Lighting Total | 10390.54 | 163.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 623524.72 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 981197.15 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12692.71 | 19581.70 | 15412.02 | 4169.68 | 0.79 | - | 2369.90 | 24.04 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12497.13 | 19274.97 | 15167.60 | 4107.36 | 0.79 | - | 2332.51 | 23.66 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 63057.75 | 97831.80 | 77335.02 | 20496.78 | 0.79 | - | 11870.27 | 120.39 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 68432.29 | 103775.46 | 80650.76 | 23124.70 | 0.78 | - | 12472.08 | 126.50 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11431.79 | 17595.04 | 13823.75 | 3771.29 | 0.79 | - | 2127.29 | 21.58 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11368.01 | 17494.50 | 13743.35 | 3751.15 | 0.79 | - | 2115.01 | 21.45 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3299.65 | 5094.09 | 4011.50 | 1082.59 | 0.79 | - | 616.71 | 6.25 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3246.94 | 5011.42 | 3945.62 | 1065.80 | 0.79 | - | 606.63 | 6.15 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12995.38 | 19857.05 | 15516.95 | 4340.10 | 0.78 | - | 2393.53 | 24.28 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 693889.34 | 653707.24 | 412670.18 | 241037.06 | 0.63 | - | 93149.87 | 944.78 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 87700.73 | 67062.26 | 41857.36 | 25204.89 | 0.62 | - | 8925.08 | 90.52 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8551.54 | 8600.04 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5312.89 | 5343.52 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1778.21 | 1789.83 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2446.69 | 2461.06 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1797.16 | 1807.52 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12421.42 | 12491.95 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15215.13 | 15309.39 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36772.37 | 37013.35 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7884.02 | 8507.94 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7905.73 | 8531.37 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44442.20 | 47959.31 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44830.42 | 48378.20 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7845.60 | 8466.48 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7867.21 | 8489.81 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15099.51 | 15190.41 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2410.70 | 2601.42 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2423.05 | 2614.73 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 11506.27 | 12416.52 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14072.73 | 14147.26 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14527.17 | 14604.30 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9770.46 | 9825.41 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10165.62 | 10224.22 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 308010.68 | 187370.29 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 30467.96 | 18534.39 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 811.90 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.14 | 798.81 | 703.64 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.82 | 4097.88 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.93 | 4175.53 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 726.47 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 722.14 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 211.47 | 703.64 | 1.00 | 1.71 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 207.95 | 703.64 | 1.00 | 1.72 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 809.46 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.74 | 46462.44 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.035025 | 8388.80 | 239508.57 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.013776 | 3519.60 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.035025 | 2796.27 | 79836.19 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 30191.31 | 30191.31 | 15.26 | 2.300 | 2.300 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00930 | 26.48 | 0.01534 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4098.34 | 4098.34 | 61.10 | 0.312 | 0.312 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00944 | 30.85 | 0.01534 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2922.31 | 2922.31 | 37.63 | 0.223 | 0.223 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00957 | 30.14 | 0.01534 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44672.74 | 44672.74 | 572.44 | 3.403 | 3.403 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01534 | 0.236 | 0.00 |
CAFE_FLR_1 | 17896.58 | 17896.58 | 94.76 | 1.365 | 1.365 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01046 | 30.85 | 0.01534 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61723.06 | 61723.06 | 47.18 | 4.704 | 4.704 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01015 | 30.93 | 0.01534 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 11240.21 | 11240.21 | 288.05 | 1.154 | 1.154 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11058.98 | 11058.98 | 283.44 | 1.135 | 1.135 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 56737.75 | 56737.75 | 2313.58 | 5.824 | 5.824 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00863 | 30.93 | 0.01534 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 57808.28 | 57808.28 | 2356.58 | 5.934 | 5.934 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00887 | 31.20 | 0.01534 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10057.52 | 10057.52 | 257.74 | 1.032 | 1.032 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00872 | 25.37 | 0.01534 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9997.63 | 9997.63 | 256.23 | 1.026 | 1.026 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 21.11 | 21.11 | 0.00872 | 25.03 | 0.01534 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2927.74 | 2927.74 | 75.03 | 0.301 | 0.301 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2878.89 | 2878.89 | 73.78 | 0.296 | 0.296 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11206.36 | 11206.36 | 456.83 | 1.150 | 1.150 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00879 | 30.93 | 0.01534 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28240.70 | 28240.70 | 85.15 | 2.154 | 2.154 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01053 | 31.20 | 0.01534 | 1.187 | 0.00 |
DINING_FLR_6 | 29662.49 | 29662.49 | 89.44 | 2.262 | 2.262 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01043 | 31.20 | 0.01534 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30689.05 | 30689.05 | 297.07 | 2.344 | 2.344 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 23.97 | 0.01003 | 25.97 | 0.01534 | 0.367 | 0.00 |
MECH_FLR_1 | 2148.12 | 2148.12 | 13.08 | 0.164 | 0.164 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00884 | 30.88 | 0.01534 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1187.66 | 1187.66 | 12.53 | 0.090 | 0.090 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00892 | 31.20 | 0.01534 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 12573.25 | 12573.25 | 32.29 | 0.958 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00869 | 31.11 | 0.01534 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7770.44 | 7770.44 | 18.85 | 0.592 | 0.592 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00863 | 31.20 | 0.01534 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1938.33 | 1938.33 | 0.98 | 0.087 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4334.01 | 4334.01 | 64.62 | 0.195 | 0.195 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00720 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1138.84 | 1138.84 | 14.66 | 0.051 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00734 | -26.20 | 0.00036 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2652.40 | 2652.40 | 33.99 | 0.119 | 0.236 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00716 | -26.20 | 0.00036 | 0.236 | 0.00 |
CAFE_FLR_1 | 11297.67 | 11297.67 | 59.82 | 0.508 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00722 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23266.07 | 23266.07 | 17.78 | 1.045 | 1.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00724 | -26.20 | 0.00036 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 7884.36 | 7884.36 | 202.05 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7906.07 | 7906.07 | 202.63 | 0.357 | 0.357 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 44443.14 | 44443.14 | 1812.24 | 2.009 | 2.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 44831.37 | 44831.37 | 1827.57 | 2.026 | 2.026 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00750 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7845.94 | 7845.94 | 201.06 | 0.355 | 0.355 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7867.55 | 7867.55 | 201.64 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2410.80 | 2410.80 | 61.78 | 0.109 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2423.15 | 2423.15 | 62.10 | 0.110 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00756 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11506.65 | 11506.65 | 469.07 | 0.520 | 0.520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7882.98 | 7882.98 | 23.77 | 0.354 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
DINING_FLR_6 | 8026.08 | 8026.08 | 24.20 | 0.361 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00767 | -26.20 | 0.00036 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 3049.21 | 3049.21 | 29.52 | 0.137 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00688 | -26.20 | 0.00036 | 0.367 | 0.00 |
MECH_FLR_1 | 1976.96 | 1976.96 | 12.04 | 0.089 | 0.089 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00719 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1465.91 | 1465.91 | 15.47 | 0.066 | 0.066 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00723 | -26.20 | 0.00036 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11689.41 | 11689.41 | 30.02 | 0.525 | 0.525 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00755 | -26.20 | 0.00036 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8290.52 | 8290.52 | 20.12 | 0.373 | 0.373 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.74 | 20.74 | 7.74 | 7.74 | 20.7362 | 12.0478 | 20.7362 | 0.5810 | 0.3000 |
FLR_3_DOAS | 16.55 | 2.05 | 6.20 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8551.543 | 8551.543 | 1.313212 | 0.00018894 | 153.852 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8600.04 | 8551.54 | 1.313212 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00797470 | 49.1749 | 1938.33 | 0.00 | 8601.91 | 8601.91 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5312.888 | 5312.888 | 0.194732 | 0.00011738 | 115.156 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5343.52 | 5312.89 | 0.194732 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00719513 | 44.4273 | 4334.01 | 0.00 | 5346.83 | 5346.83 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1778.207 | 1778.207 | 0.127127 | 0.00003929 | 34.726 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1789.83 | 1778.21 | 0.127127 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00734327 | 45.3285 | 1138.84 | 0.00 | 1790.26 | 1790.26 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2446.690 | 2446.690 | 0.093426 | 0.00005406 | 52.505 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2461.06 | 2446.69 | 0.093426 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718581 | 44.3678 | 1976.96 | 0.00 | 2462.51 | 2462.51 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1797.160 | 1797.160 | 0.065873 | 0.00003971 | 38.953 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1807.52 | 1797.16 | 0.065873 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723140 | 44.6453 | 1465.91 | 0.00 | 1808.64 | 1808.64 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12421.419 | 12421.419 | 1.943197 | 0.00027444 | 223.173 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12491.95 | 12421.42 | 1.943197 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00715617 | 44.1875 | 2652.40 | 0.00 | 12494.62 | 12494.62 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15215.129 | 15215.129 | 0.779255 | 0.00033616 | 308.801 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15309.39 | 15215.13 | 0.779255 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00721817 | 44.5676 | 11297.67 | 0.00 | 15315.41 | 15315.41 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 36772.368 | 36772.368 | 2.685888 | 0.00081244 | 716.801 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 37013.35 | 36772.37 | 2.685888 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00724037 | 44.7002 | 23266.07 | 0.00 | 37021.93 | 37021.93 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12692.711 | -999.000 | 1.153857 | 0.00045335 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12692.71 | 12160.43 | 1.153857 | 21.71 | 15.24 | 0.00869029 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869029 | 53.1663 | 11240.21 | 0.00 | 13264.80 | 12444.64 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7884.019 | 7884.019 | 0.356356 | 0.00017419 | 179.493 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8507.94 | 7884.02 | 0.356356 | 21.11 | 13.93 | 0.00746253 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746253 | 45.7441 | 7884.36 | 0.00 | 8511.01 | 8511.01 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12497.133 | -999.000 | 1.135254 | 0.00044636 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12497.13 | 11965.83 | 1.135254 | 21.71 | 15.25 | 0.00869302 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869302 | 53.1829 | 11058.98 | 0.00 | 13060.21 | 12245.13 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7905.731 | 7905.731 | 0.357338 | 0.00017467 | 179.988 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8531.37 | 7905.73 | 0.357338 | 21.11 | 13.93 | 0.00746394 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746394 | 45.7527 | 7906.07 | 0.00 | 8534.45 | 8534.45 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 63057.747 | -999.000 | 5.823867 | 0.00225223 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 63057.75 | 61216.33 | 5.823867 | 21.71 | 15.19 | 0.00863078 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00863078 | 52.8049 | 56737.75 | 0.00 | 65921.85 | 62687.84 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 44442.204 | 44442.204 | 2.008842 | 0.00098190 | 1011.800 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47959.31 | 44442.20 | 2.008842 | 21.11 | 13.95 | 0.00749240 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749240 | 45.9234 | 44443.14 | 0.00 | 47977.03 | 47977.03 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 68432.290 | -999.000 | 5.934221 | 0.00244420 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 68432.29 | 63031.89 | 5.934221 | 21.71 | 15.40 | 0.00887246 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 0.0000 | 21.11 | 0.00887246 | 54.2649 | 57808.28 | 0.00 | 71446.22 | 64386.04 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 44830.423 | 44830.423 | 2.026390 | 0.00099047 | 1020.637 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48378.20 | 44830.42 | 2.026390 | 21.11 | 13.96 | 0.00749638 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749638 | 45.9475 | 44831.37 | 0.00 | 48396.13 | 48396.13 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11431.786 | -999.000 | 1.032452 | 0.00040831 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 11431.79 | 10892.93 | 1.032452 | 21.71 | 15.27 | 0.00871505 | 12.80 | 11.67 | 0.00850000 | 25.37 | 0.01534436 | 21.50 | 0.0000 | 21.11 | 0.00871505 | 53.3158 | 10057.52 | 0.00 | 11945.40 | 11144.57 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7845.597 | 7845.597 | 0.354620 | 0.00017334 | 178.619 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8466.48 | 7845.60 | 0.354620 | 21.11 | 13.92 | 0.00746008 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746008 | 45.7293 | 7845.94 | 0.00 | 8469.54 | 8469.54 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11368.013 | -999.000 | 1.026304 | 0.00040603 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | 7/21 08:50:00 | 11368.01 | 10828.75 | 1.026304 | 21.71 | 15.27 | 0.00871649 | 12.80 | 11.67 | 0.00850000 | 25.03 | 0.01534436 | 21.41 | 0.0000 | 21.11 | 0.00871649 | 53.3245 | 9997.63 | 0.00 | 11878.67 | 11078.74 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7867.215 | 7867.215 | 0.355597 | 0.00017382 | 179.111 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8489.81 | 7867.21 | 0.355597 | 21.11 | 13.93 | 0.00746150 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00746150 | 45.7379 | 7867.55 | 0.00 | 8492.87 | 8492.87 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15099.508 | 15099.508 | 0.677723 | 0.00033361 | 313.220 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15190.41 | 15099.51 | 0.677723 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00755343 | 46.6092 | 11689.41 | 0.00 | 15197.57 | 15197.57 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3299.654 | -999.000 | 0.300546 | 0.00011785 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3299.65 | 3166.39 | 0.300546 | 21.71 | 15.24 | 0.00868296 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868296 | 53.1221 | 2927.74 | 0.00 | 3448.52 | 3240.65 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2410.704 | 2410.704 | 0.108963 | 0.00005326 | 54.882 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2601.42 | 2410.70 | 0.108963 | 21.11 | 14.01 | 0.00755473 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755473 | 46.3025 | 2410.80 | 0.00 | 2602.42 | 2602.42 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3246.939 | -999.000 | 0.295531 | 0.00011597 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3246.94 | 3113.94 | 0.295531 | 21.71 | 15.24 | 0.00868567 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868567 | 53.1385 | 2878.89 | 0.00 | 3393.37 | 3186.88 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2423.046 | 2423.046 | 0.109521 | 0.00005353 | 55.163 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2614.73 | 2423.05 | 0.109521 | 21.11 | 14.01 | 0.00755691 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755691 | 46.3157 | 2423.15 | 0.00 | 2615.74 | 2615.74 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12995.380 | -999.000 | 1.150398 | 0.00046416 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 12995.38 | 12177.82 | 1.150398 | 21.71 | 15.33 | 0.00879185 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00879185 | 53.7794 | 11206.36 | 0.00 | 13573.56 | 12449.28 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11506.265 | 11506.265 | 0.520087 | 0.00025422 | 261.950 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12416.52 | 11506.27 | 0.520087 | 21.11 | 14.02 | 0.00756958 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00756958 | 46.3919 | 11506.65 | 0.00 | 12421.37 | 12421.37 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14072.727 | 14072.727 | 1.229924 | 0.00031092 | 268.275 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14147.26 | 14072.73 | 1.229924 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766060 | 47.2627 | 7882.98 | 0.00 | 14152.80 | 14152.80 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14527.167 | 14527.167 | 1.291823 | 0.00032096 | 276.277 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14604.30 | 14527.17 | 1.291823 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766640 | 47.2984 | 8026.08 | 0.00 | 14609.91 | 14609.91 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9770.456 | 9770.456 | 1.338369 | 0.00021587 | 177.371 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9825.41 | 9770.46 | 1.338369 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00688203 | 42.5196 | 3049.21 | 0.00 | 9827.81 | 9827.81 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10165.620 | 10165.620 | 0.372552 | 0.00022460 | 220.345 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.22 | 10165.62 | 0.372552 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771511 | 47.5949 | 8290.52 | 0.00 | 10230.56 | 10230.56 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 693889.340 | -999.000 | 20.736247 | 0.02478412 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 693889.34 | 424241.28 | 20.736247 | 28.18 | 20.70 | 0.01299829 | 10.90 | 10.89 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 58.1121 | 23.99 | 0.00957107 | 49.0834 | 271914.93 | 0.00 | 747298.56 | 435645.25 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 308010.675 | 308010.675 | 6.220874 | 0.00680512 | 3921.811 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 187370.29 | 308010.68 | 6.220874 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 193.7069 | 21.00 | 0.00748676 | 46.2036 | 85844.66 | 0.00 | 186937.95 | 186937.95 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 10.91 | 11.67 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 100.0000 | 21.11 | 0.00875221 | 53.5387 | 159983.71 | 0.00 | 93045.89 | 49604.71 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 0.615360 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3333 | 21.11 | 0.00749497 | 45.9390 | 137119.03 | 0.00 | 18491.63 | 18491.63 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8551.543 | 8551.543 | 1.313212 | 0.00018894 | 153.852 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.3521 | 1.371484 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8600.04 | 8551.54 | 1.0000 | 1.50829697 | 1.313212 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.18891663 | 60.00 | 49.00 | 11.00 | 0.000 | 8600.04 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797470 | 21.00 | 0.00797470 | 49.1749 | 1938.33 | 0.00 | 8601.91 | 8601.91 | 1.50829697 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.19 | 15.28 | 0.00800000 | 42637.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5312.888 | 5312.888 | 0.194732 | 0.00011738 | 115.156 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.8401 | 0.852073 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5343.52 | 5312.89 | 1.0000 | 0.22366046 | 0.194732 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.11736980 | 60.00 | 49.00 | 11.00 | 0.000 | 5343.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00719513 | 21.00 | 0.00719513 | 44.4273 | 4334.01 | 0.00 | 5346.83 | 5346.83 | 0.22366046 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1778.207 | 1778.207 | 0.127127 | 0.00003929 | 34.726 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.2814 | 0.285186 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1789.83 | 1778.21 | 1.0000 | 0.14601302 | 0.127127 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03928330 | 60.00 | 49.00 | 11.00 | 0.000 | 1789.83 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00734327 | 21.00 | 0.00734327 | 45.3285 | 1138.84 | 0.00 | 1790.26 | 1790.26 | 0.14601302 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.62 | 17.55 | 0.00800000 | 49195.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2446.690 | 2446.690 | 0.093426 | 0.00005406 | 52.505 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.3869 | 0.392397 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2461.06 | 2446.69 | 1.0000 | 0.10730444 | 0.093426 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05405112 | 60.00 | 49.00 | 11.00 | 0.000 | 2461.06 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718581 | 21.00 | 0.00718581 | 44.3678 | 1976.96 | 0.00 | 2462.51 | 2462.51 | 0.10730444 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 39.11 | 20.88 | 0.00800000 | 59883.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1797.160 | 1797.160 | 0.065873 | 0.00003971 | 38.953 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.2842 | 0.288226 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1807.52 | 1797.16 | 1.0000 | 0.07565861 | 0.065873 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03970201 | 60.00 | 49.00 | 11.00 | 0.000 | 1807.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723140 | 21.00 | 0.00723140 | 44.6453 | 1465.91 | 0.00 | 1808.64 | 1808.64 | 0.07565861 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12421.419 | 12421.419 | 1.943197 | 0.00027444 | 223.173 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.9639 | 1.992129 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12491.95 | 12421.42 | 1.0000 | 2.23187035 | 1.943197 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.27440808 | 60.00 | 49.00 | 11.00 | 0.000 | 12491.95 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00715617 | 21.00 | 0.00715617 | 44.1875 | 2652.40 | 0.00 | 12494.62 | 12494.62 | 2.23187035 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.09 | 15.24 | 0.00800000 | 42533.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15215.129 | 15215.129 | 0.779255 | 0.00033616 | 308.801 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 2.4069 | 2.440180 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15309.39 | 15215.13 | 1.0000 | 0.89501784 | 0.779255 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33612538 | 60.00 | 49.00 | 11.00 | 0.000 | 15309.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00721817 | 21.00 | 0.00721817 | 44.5676 | 11297.67 | 0.00 | 15315.41 | 15315.41 | 0.89501784 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 33.38 | 19.12 | 0.00800000 | 54046.6 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36772.368 | 36772.368 | 2.685888 | 0.00081244 | 716.801 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 5.8190 | 5.897500 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 37013.35 | 36772.37 | 1.0000 | 3.08489271 | 2.685888 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.81235766 | 60.00 | 49.00 | 11.00 | 0.000 | 37013.35 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00724037 | 21.00 | 0.00724037 | 44.7002 | 23266.07 | 0.00 | 37021.93 | 37021.93 | 3.08489271 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.37 | 17.47 | 0.00800000 | 48935.8 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12692.711 | -999.000 | 1.153857 | 0.00045335 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9948 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.153857 | 1.32526935 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 1.2944 | 1.294347 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12692.71 | 12160.43 | 1.0000 | 1.32526935 | 1.153857 | 21.71 | 15.24 | 0.00869029 | 43899.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.45329952 | 6.70 | 11.72 | 6.67 | 0.000 | 12692.71 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869029 | 21.11 | 0.00869029 | 53.1663 | 11240.21 | 0.00 | 13264.80 | 12444.64 | 1.32526935 | 21.71 | 15.72 | 0.00869029 | 43899.7 | 12.51 | 11.92 | 0.00844511 | 33890.5 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7884.019 | 7884.019 | 0.356356 | 0.00017419 | 179.493 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.153857 | 1.32526935 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.3376 | 1.264428 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8507.94 | 7884.02 | 1.0000 | 0.40929512 | 0.356356 | 21.11 | 13.93 | 0.00746253 | 40168.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17416999 | 60.00 | 49.00 | 11.00 | 0.000 | 8507.94 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746253 | 21.11 | 0.00746253 | 45.7441 | 7884.36 | 0.00 | 8511.01 | 8511.01 | 0.40929512 | 16.60 | 12.62 | 0.00746253 | 35574.0 | 37.01 | 19.85 | 0.00746253 | 56368.3 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12497.133 | -999.000 | 1.135254 | 0.00044636 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9999 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.135254 | 1.30390288 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 1.2744 | 1.274403 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12497.13 | 11965.83 | 1.0000 | 1.30390288 | 1.135254 | 21.71 | 15.25 | 0.00869302 | 43906.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.44631475 | 6.70 | 11.72 | 6.67 | 0.000 | 12497.13 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869302 | 21.11 | 0.00869302 | 53.1829 | 11058.98 | 0.00 | 13060.21 | 12245.13 | 1.30390288 | 21.71 | 15.72 | 0.00869302 | 43906.6 | 12.51 | 11.92 | 0.00844538 | 33890.4 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7905.731 | 7905.731 | 0.357338 | 0.00017467 | 179.988 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.135254 | 1.30390288 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.3413 | 1.267910 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8531.37 | 7905.73 | 1.0000 | 0.41042231 | 0.357338 | 21.11 | 13.93 | 0.00746394 | 40171.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17464965 | 60.00 | 49.00 | 11.00 | 0.000 | 8531.37 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746394 | 21.11 | 0.00746394 | 45.7527 | 7906.07 | 0.00 | 8534.45 | 8534.45 | 0.41042231 | 16.60 | 12.62 | 0.00746394 | 35577.5 | 37.01 | 19.85 | 0.00746394 | 56371.9 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 63057.747 | -999.000 | 5.823867 | 0.00225223 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8842 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.823867 | 6.68903653 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 6.4305 | 6.430354 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 63057.75 | 61216.33 | 1.0000 | 6.68903653 | 5.823867 | 21.71 | 15.19 | 0.00863078 | 43749.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.25200480 | 6.70 | 11.72 | 6.67 | 0.000 | 63057.75 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00863078 | 21.11 | 0.00863078 | 52.8049 | 56737.75 | 0.00 | 65921.85 | 62687.84 | 6.68903653 | 21.71 | 15.67 | 0.00863078 | 43749.2 | 12.53 | 11.93 | 0.00843924 | 33894.0 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44442.204 | 44442.204 | 2.008842 | 0.00098190 | 1011.800 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.823867 | 6.68903653 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 7.5399 | 7.127577 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47959.31 | 44442.20 | 1.0000 | 2.30726729 | 2.008842 | 21.11 | 13.95 | 0.00749240 | 40244.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.98179603 | 60.00 | 49.00 | 11.00 | 0.000 | 47959.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749240 | 21.11 | 0.00749240 | 45.9234 | 44443.14 | 0.00 | 47977.03 | 47977.03 | 2.30726729 | 16.60 | 12.65 | 0.00749240 | 35649.6 | 37.01 | 19.87 | 0.00749240 | 56443.5 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68432.290 | -999.000 | 5.934221 | 0.00244420 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3335 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.934221 | 6.81578390 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 6.9786 | 6.978427 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 68432.29 | 63031.89 | 1.0000 | 6.81578390 | 5.934221 | 21.71 | 15.40 | 0.00887246 | 44362.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.44394788 | 6.70 | 11.72 | 6.67 | 0.000 | 68432.29 | 31.20 | 0.01534436 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00887246 | 21.11 | 0.00887246 | 54.2649 | 57808.28 | 0.00 | 71446.22 | 64386.04 | 6.81578390 | 21.71 | 15.88 | 0.00887246 | 44362.5 | 12.46 | 11.92 | 0.00846207 | 33880.0 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44830.423 | 44830.423 | 2.026390 | 0.00099047 | 1020.637 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.934221 | 6.81578390 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 7.6058 | 7.189839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 48378.20 | 44830.42 | 1.0000 | 2.32742211 | 2.026390 | 21.11 | 13.96 | 0.00749638 | 40254.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.99037237 | 60.00 | 49.00 | 11.00 | 0.000 | 48378.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749638 | 21.11 | 0.00749638 | 45.9475 | 44831.37 | 0.00 | 48396.13 | 48396.13 | 2.32742211 | 16.60 | 12.65 | 0.00749638 | 35659.7 | 37.01 | 19.87 | 0.00749638 | 56453.5 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11431.786 | -999.000 | 1.032452 | 0.00040831 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0408 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.032452 | 1.18582863 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 1.1658 | 1.165764 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 11431.79 | 10892.93 | 1.0000 | 1.18582863 | 1.032452 | 21.71 | 15.27 | 0.00871505 | 43962.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.40826762 | 6.70 | 11.72 | 6.67 | 0.000 | 11431.79 | 25.37 | 0.01534436 | 21.50 | 0.00000000 | 0.0000 | 21.11 | 0.00871505 | 21.11 | 0.00871505 | 53.3158 | 10057.52 | 0.00 | 11945.40 | 11144.57 | 1.18582863 | 21.71 | 15.74 | 0.00871505 | 43962.5 | 12.51 | 11.92 | 0.00844751 | 33889.1 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7845.597 | 7845.597 | 0.354620 | 0.00017334 | 178.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.032452 | 1.18582863 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.3311 | 1.258266 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8466.48 | 7845.60 | 1.0000 | 0.40730046 | 0.354620 | 21.11 | 13.92 | 0.00746008 | 40162.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17332119 | 60.00 | 49.00 | 11.00 | 0.000 | 8466.48 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746008 | 21.11 | 0.00746008 | 45.7293 | 7845.94 | 0.00 | 8469.54 | 8469.54 | 0.40730046 | 16.60 | 12.61 | 0.00746008 | 35567.8 | 37.01 | 19.84 | 0.00746008 | 56362.1 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11368.013 | -999.000 | 1.026304 | 0.00040603 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0435 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.026304 | 1.17876728 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 1.1593 | 1.159260 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | unknown | unknown | 7/21 08:50:00 | 11368.01 | 10828.75 | 1.0000 | 1.17876728 | 1.026304 | 21.71 | 15.27 | 0.00871649 | 43966.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.40599010 | 6.70 | 11.72 | 6.67 | 0.000 | 11368.01 | 25.03 | 0.01534436 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00871649 | 21.11 | 0.00871649 | 53.3245 | 9997.63 | 0.00 | 11878.67 | 11078.74 | 1.17876728 | 21.71 | 15.74 | 0.00871649 | 43966.2 | 12.51 | 11.92 | 0.00844764 | 33889.0 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7867.215 | 7867.215 | 0.355597 | 0.00017382 | 179.111 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.026304 | 1.17876728 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.3347 | 1.261733 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8489.81 | 7867.21 | 1.0000 | 0.40842274 | 0.355597 | 21.11 | 13.93 | 0.00746150 | 40165.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17379876 | 60.00 | 49.00 | 11.00 | 0.000 | 8489.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00746150 | 21.11 | 0.00746150 | 45.7379 | 7867.55 | 0.00 | 8492.87 | 8492.87 | 0.40842274 | 16.60 | 12.61 | 0.00746150 | 35571.4 | 37.01 | 19.85 | 0.00746150 | 56365.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15099.508 | 15099.508 | 0.677723 | 0.00033361 | 313.220 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 2.3882 | 2.421637 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15190.41 | 15099.51 | 1.0000 | 0.77840272 | 0.677723 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33357115 | 60.00 | 49.00 | 11.00 | 0.000 | 15190.41 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00755343 | 21.00 | 0.00755343 | 46.6092 | 11689.41 | 0.00 | 15197.57 | 15197.57 | 0.77840272 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.75 | 19.86 | 0.00800000 | 56458.8 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3299.654 | -999.000 | 0.300546 | 0.00011785 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9812 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.300546 | 0.34519351 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 0.3365 | 0.336484 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3299.65 | 3166.39 | 1.0000 | 0.34519351 | 0.300546 | 21.71 | 15.24 | 0.00868296 | 43881.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.11784178 | 6.70 | 11.72 | 6.67 | 0.000 | 3299.65 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868296 | 21.11 | 0.00868296 | 53.1221 | 2927.74 | 0.00 | 3448.52 | 3240.65 | 0.34519351 | 21.71 | 15.71 | 0.00868296 | 43881.0 | 12.51 | 11.92 | 0.00844440 | 33890.9 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2410.704 | 2410.704 | 0.108963 | 0.00005326 | 54.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.300546 | 0.34519351 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.4090 | 0.386625 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2601.42 | 2410.70 | 1.0000 | 0.12515059 | 0.108963 | 21.11 | 14.01 | 0.00755473 | 40402.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05325612 | 60.00 | 49.00 | 11.00 | 0.000 | 2601.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755473 | 21.11 | 0.00755473 | 46.3025 | 2410.80 | 0.00 | 2602.42 | 2602.42 | 0.12515059 | 16.60 | 12.71 | 0.00755473 | 35807.4 | 37.01 | 19.91 | 0.00755473 | 56601.7 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3246.939 | -999.000 | 0.295531 | 0.00011597 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9862 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.295531 | 0.33943418 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 0.3311 | 0.331109 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3246.94 | 3113.94 | 1.0000 | 0.33943418 | 0.295531 | 21.71 | 15.24 | 0.00868567 | 43887.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.11595915 | 6.70 | 11.72 | 6.67 | 0.000 | 3246.94 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868567 | 21.11 | 0.00868567 | 53.1385 | 2878.89 | 0.00 | 3393.37 | 3186.88 | 0.33943418 | 21.71 | 15.71 | 0.00868567 | 43887.9 | 12.51 | 11.92 | 0.00844467 | 33890.8 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2423.046 | 2423.046 | 0.109521 | 0.00005353 | 55.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.295531 | 0.33943418 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 0.4111 | 0.388605 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2614.73 | 2423.05 | 1.0000 | 0.12579134 | 0.109521 | 21.11 | 14.01 | 0.00755691 | 40408.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05352878 | 60.00 | 49.00 | 11.00 | 0.000 | 2614.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755691 | 21.11 | 0.00755691 | 46.3157 | 2423.15 | 0.00 | 2615.74 | 2615.74 | 0.12579134 | 16.60 | 12.71 | 0.00755691 | 35812.9 | 37.01 | 19.92 | 0.00755691 | 56607.2 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12995.380 | -999.000 | 1.150398 | 0.00046416 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1836 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.150398 | 1.32129627 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 1.3252 | 1.325212 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 12995.38 | 12177.82 | 1.0000 | 1.32129627 | 1.150398 | 21.71 | 15.33 | 0.00879185 | 44157.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.46410884 | 6.70 | 11.72 | 6.67 | 0.000 | 12995.38 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00879185 | 21.11 | 0.00879185 | 53.7794 | 11206.36 | 0.00 | 13573.56 | 12449.28 | 1.32129627 | 21.71 | 15.81 | 0.00879185 | 44157.5 | 12.48 | 11.92 | 0.00845475 | 33884.6 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11506.265 | 11506.265 | 0.520087 | 0.00025422 | 261.950 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.150398 | 1.32129627 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.9521 | 1.845358 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12416.52 | 11506.27 | 1.0000 | 0.59734900 | 0.520087 | 21.11 | 14.02 | 0.00756958 | 40440.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.25419094 | 60.00 | 49.00 | 11.00 | 0.000 | 12416.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756958 | 21.11 | 0.00756958 | 46.3919 | 11506.65 | 0.00 | 12421.37 | 12421.37 | 0.59734900 | 16.60 | 12.72 | 0.00756958 | 35845.0 | 37.01 | 19.93 | 0.00756958 | 56639.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14072.727 | 14072.727 | 1.229924 | 0.00031092 | 268.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 2.2242 | 2.256964 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 14147.26 | 14072.73 | 1.0000 | 1.41263650 | 1.229924 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.31088799 | 60.00 | 49.00 | 11.00 | 0.000 | 14147.26 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766060 | 21.00 | 0.00766060 | 47.2627 | 7882.98 | 0.00 | 14152.80 | 14152.80 | 1.41263650 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.43 | 16.80 | 0.00800000 | 46953.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14527.167 | 14527.167 | 1.291823 | 0.00032096 | 276.277 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 2.2960 | 2.329846 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14604.30 | 14527.17 | 1.0000 | 1.48373126 | 1.291823 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.32092726 | 60.00 | 49.00 | 11.00 | 0.000 | 14604.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766640 | 21.00 | 0.00766640 | 47.2984 | 8026.08 | 0.00 | 14609.91 | 14609.91 | 1.48373126 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.26 | 16.74 | 0.00800000 | 46781.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9770.456 | 9770.456 | 1.338369 | 0.00021587 | 177.371 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.5447 | 1.566972 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9825.41 | 9770.46 | 1.0000 | 1.53719133 | 1.338369 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.21584426 | 60.00 | 49.00 | 11.00 | 0.000 | 9825.41 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.67 | 0.00688203 | 21.00 | 0.00688203 | 42.5196 | 3049.21 | 0.00 | 9827.81 | 9827.81 | 1.53719133 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.87 | 15.53 | 0.00800000 | 43328.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10165.620 | 10165.620 | 0.372552 | 0.00022460 | 220.345 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 1.6074 | 1.630348 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.22 | 10165.62 | 1.0000 | 0.42789729 | 0.372552 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.22457405 | 60.00 | 49.00 | 11.00 | 0.000 | 10224.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771511 | 21.00 | 0.00771511 | 47.5949 | 8290.52 | 0.00 | 10230.56 | 10230.56 | 0.42789729 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.7 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 693889.340 | -999.000 | 20.736247 | 0.02478412 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.0032 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.736247 | 23.81673764 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 70.7611 | 70.761133 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 693889.34 | 424241.28 | 1.0000 | 23.81673764 | 20.736247 | 28.18 | 20.70 | 0.01299829 | 61505.9 | 10.90 | 10.89 | 0.00868318 | 32387.2 | 24.78159123 | 6.70 | 11.72 | 6.67 | 46462.436 | 647426.90 | 31.20 | 0.01534436 | 23.10 | 12.05026000 | 58.1121 | 23.99 | 0.00974055 | 23.99 | 0.00957107 | 49.0834 | 271914.93 | 0.00 | 747298.56 | 435645.25 | 23.81673764 | 28.18 | 21.24 | 0.01299829 | 61505.9 | 10.40 | 10.37 | 0.00780622 | 30128.9 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 308010.675 | 308010.675 | 6.220874 | 0.00680512 | 3921.811 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.736247 | 23.81673764 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 29.4573 | 49.398310 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 187370.29 | 308010.68 | 1.0000 | 7.14502129 | 6.220874 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 6.80442530 | 60.00 | 49.00 | 11.00 | 0.000 | 187370.29 | -26.20 | 0.00036134 | -26.20 | 12.05026000 | 193.7069 | 20.98 | 0.00737208 | 21.00 | 0.00748676 | 46.2036 | 85844.66 | 0.00 | 186937.95 | 186937.95 | 7.14502129 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87700.731 | -999.000 | 2.051199 | 0.00313247 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 35.02147305 | 13.37 | 6.70 | 6.67 | 980608.01 | 8.9435 | 8.943506 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 1.0000 | 2.35591662 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 11.67 | 0.00868318 | 34322.2 | 3.13214738 | 6.70 | 11.72 | 6.67 | 2194.880 | 85505.85 | 31.20 | 0.01534436 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00876303 | 21.11 | 0.00875221 | 53.5387 | 159983.71 | 0.00 | 93045.89 | 49604.71 | 2.35591662 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.82 | 10.78 | 0.00803030 | 31121.7 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 13.77461157 | 71.00 | 82.00 | 11.00 | 636073.41 | 2.9139 | 4.886408 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 1.0000 | 0.70677499 | 0.615360 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 0.67308373 | 60.00 | 49.00 | 11.00 | 0.000 | 18534.39 | -26.20 | 0.00036134 | -26.20 | 2.05119905 | 333.3333 | 21.11 | 0.00749543 | 21.11 | 0.00749497 | 45.9390 | 137119.03 | 0.00 | 18491.63 | 18491.63 | 0.70677499 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 20.74 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003539 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003539 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 286.17 | 8500.67 | 284.83 |
RETAIL_1_FLR_1 | 2611.67 | 8292.00 | 2415.67 |
RETAIL_2_FLR_1 | 652.00 | 8612.00 | 640.50 |
LAUNDRY_FLR_1 | 5428.83 | 3415.50 | 2077.33 |
CAFE_FLR_1 | 2158.83 | 7368.50 | 1449.17 |
LOBBY_FLR_1 | 783.83 | 7739.50 | 515.33 |
ROOM_1_FLR_3 | 3054.00 | 8374.50 | 2996.67 |
ROOM_2_FLR_3 | 3487.50 | 8474.33 | 3441.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2241.83 | 8760.00 | 2241.83 |
ROOM_5_FLR_3 | 2985.00 | 8360.17 | 2963.67 |
ROOM_6_FLR_3 | 3376.50 | 8491.33 | 3355.67 |
ROOM_1_FLR_6 | 3618.50 | 8233.00 | 3459.17 |
ROOM_2_FLR_6 | 3996.33 | 8325.67 | 3873.50 |
ROOM_3_MULT9_FLR_6 | 2419.17 | 8269.33 | 2367.83 |
BANQUET_FLR_6 | 3199.67 | 4489.00 | 788.83 |
DINING_FLR_6 | 4016.00 | 3076.83 | 627.17 |
KITCHEN_FLR_6 | 7927.50 | 6391.33 | 5957.17 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8738.50 | 8760.00 | 7975.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 203.67 | 0.00 | 203.67 | 0.00 |
RETAIL_1_FLR_1 | 206.50 | 0.00 | 206.50 | 0.00 |
RETAIL_2_FLR_1 | 204.83 | 0.00 | 204.83 | 0.00 |
LAUNDRY_FLR_1 | 151.50 | 83.17 | 151.50 | 83.17 |
CAFE_FLR_1 | 175.00 | 0.00 | 175.00 | 0.00 |
LOBBY_FLR_1 | 184.00 | 0.00 | 184.00 | 0.00 |
ROOM_1_FLR_3 | 32.50 | 0.00 | 32.50 | 0.00 |
ROOM_2_FLR_3 | 60.00 | 0.00 | 60.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 95.50 | 9.33 | 95.50 | 9.33 |
ROOM_5_FLR_3 | 50.83 | 0.33 | 50.83 | 0.33 |
ROOM_6_FLR_3 | 72.83 | 0.33 | 72.83 | 0.33 |
ROOM_1_FLR_6 | 31.67 | 1.33 | 31.67 | 1.33 |
ROOM_2_FLR_6 | 66.00 | 0.50 | 66.00 | 0.50 |
ROOM_3_MULT9_FLR_6 | 24.67 | 9.67 | 24.67 | 9.67 |
BANQUET_FLR_6 | 147.50 | 0.00 | 147.50 | 0.00 |
DINING_FLR_6 | 143.33 | 0.00 | 143.33 | 0.00 |
KITCHEN_FLR_6 | 132.17 | 177.33 | 132.17 | 177.33 |
MECH_FLR_1 | 263.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 319.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 279.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 257.17 | 0.00 | 0.00 | 0.00 |
Facility | 346.67 | 269.83 | 272.67 | 269.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.72 | 106.50 | 4826.41 | 1.003 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.453 | 0.276 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.509 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 25.168 | 0.154 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.47 | 142.30 | 748.35 | 3.818 | 0.249 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.83 | 422.44 | 5183.56 | 1.897 | 0.072 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.062 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.081 | 0.000 | 0.099 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.063 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.083 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.075 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.148 | 0.000 | 0.131 |
BANQUET_FLR_6 | 144.83 | 249.90 | 1010.89 | 4.744 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.83 | 249.90 | 1010.89 | 5.112 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 21.654 | 0.151 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.72 | 106.50 | 4826.41 | 0.935 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.283 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.411 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.729 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.47 | 142.30 | 748.35 | 3.550 | 0.005 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.83 | 422.44 | 5183.56 | 1.771 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.83 | 249.90 | 1010.89 | 4.147 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.83 | 249.90 | 1010.89 | 4.353 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 14.200 | 0.003 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
Electricity:Building | 2570.78 | 32700.73 | 03-JUN-05:00 | 162081.79 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 291.85 | 3415.73 | 02-JAN-02:10 | 21692.39 | 02-JAN-20:10 |
InteriorLights:Electricity | 818.67 | 6867.78 | 03-JUN-05:00 | 73068.04 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 141.59 | 1286.51 | 02-JAN-02:10 | 11578.59 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 818.67 | 6867.78 | 03-JUN-05:00 | 73068.04 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 17.77 | 213.21 | 02-JAN-02:10 | 1305.47 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 7.58 | 68.87 | 02-JAN-02:10 | 619.87 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 20.57 | 246.90 | 02-JAN-02:10 | 1511.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 8.78 | 79.76 | 02-JAN-02:10 | 717.81 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.01 | 72.94 | 02-JAN-02:10 | 439.78 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.42 | 21.96 | 02-JAN-02:10 | 197.62 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.52 | 995.20 | 02-JAN-02:10 | 4865.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.58 | 32.51 | 02-JAN-02:10 | 292.58 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 29.89 | 307.01 | 03-JUN-05:00 | 2496.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 15.55 | 103.79 | 03-JUN-05:00 | 1531.38 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 292.50 | 3392.07 | 03-JUN-05:00 | 22119.33 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 143.50 | 1280.66 | 03-JUN-05:00 | 12090.12 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 21.61 | 280.58 | 01-JAN-02:10 | 1668.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 9.32 | 58.22 | 01-JAN-11:10 | 931.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 21.61 | 280.55 | 01-JAN-02:10 | 1668.78 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 9.32 | 58.21 | 01-JAN-11:10 | 931.35 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 340.04 | 4755.63 | 01-JAN-02:10 | 24847.43 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 111.28 | 695.15 | 01-JAN-11:10 | 11122.32 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 340.13 | 4756.94 | 01-JAN-02:10 | 24854.23 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 111.31 | 695.34 | 01-JAN-11:10 | 11125.36 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 21.61 | 280.58 | 01-JAN-02:10 | 1668.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 9.32 | 58.22 | 01-JAN-11:10 | 931.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 21.61 | 280.55 | 01-JAN-02:10 | 1668.78 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 9.32 | 58.21 | 01-JAN-11:10 | 931.35 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.61 | 995.90 | 02-JAN-02:10 | 8963.14 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.40 | 70.14 | 01-JAN-02:10 | 417.24 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.33 | 14.55 | 01-JAN-11:10 | 232.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.40 | 70.14 | 01-JAN-02:10 | 417.19 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.33 | 14.55 | 01-JAN-11:10 | 232.84 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 40.28 | 563.32 | 01-JAN-02:10 | 2943.26 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 13.18 | 82.34 | 01-JAN-11:10 | 1317.48 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 205.93 | 2488.34 | 03-JUN-05:00 | 9437.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 30.08 | 239.04 | 03-JUN-05:00 | 2689.23 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 205.93 | 2488.34 | 03-JUN-05:00 | 9437.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 30.08 | 239.04 | 03-JUN-05:00 | 2689.23 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 452.51 | 6238.01 | 02-JAN-02:10 | 18899.03 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 11.67 | 106.08 | 02-JAN-02:10 | 954.73 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.02 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 959.57 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.08 | 686.45 | 02-FEB-23:30 | 3257.33 | 05-SEP-07:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1029.26 | 2491.81 | 25-APR-03:00 | 215237.37 | 04-AUG-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.19 | 0.00 | 01-JAN-11:10 | 1942.11 | 09-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.80 | 420.87 | 02-FEB-06:00 | 1195.94 | 06-JUN-13:10 |
WaterSystems:Electricity | 90.76 | 1086.68 | 15-SEP-00:20 | 4750.74 | 02-FEB-07:20 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.68 | 15-SEP-00:20 | 4750.74 | 02-FEB-07:20 |
Fans:Electricity | 545.57 | 12571.50 | 05-JAN-08:10 | 28743.36 | 24-OCT-21:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 773.77 | 14159.68 | 08-NOV-15:00 | 40263.77 | 24-OCT-21:00 |
ExteriorEquipment:Electricity | 973.29 | 6518.85 | 02-JAN-02:20 | 62600.61 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.84 | 388.92 | 17-JUN-05:00 | 1321.13 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
ElectricityPurchased:Plant | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
Cogeneration:ElectricityPurchased | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
ElectricityNet:Plant | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
Cogeneration:ElectricityNet | 5487.38 | 72776.07 | 30-OCT-02:40 | 436930.12 | 26-JUL-19:10 |
General:Fans:Electricity | 545.57 | 12571.50 | 05-JAN-08:10 | 28743.36 | 24-OCT-21:00 |
ExteriorLights:Electricity | 163.11 | 0.00 | 01-JAN-08:00 | 10390.54 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 163.11 | 0.00 | 01-JAN-08:00 | 10390.54 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 205.36 | 0.00 | 18-MAR-13:10 | 10206.30 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 819.62 | 0.00 | 01-JAN-00:10 | 206788.95 | 04-AUG-15:20 |
General:Cooling:Electricity | 819.62 | 0.00 | 01-JAN-00:10 | 206788.95 | 04-AUG-15:20 |
Pumps:Electricity | 64.90 | 47.91 | 20-MAR-10:10 | 5674.44 | 30-JAN-16:30 |
General:Pumps:Electricity | 64.90 | 47.91 | 20-MAR-10:10 | 5674.44 | 30-JAN-16:30 |
WIRED_LTG_ELECTRICITY | 28.82 | 0.00 | 01-JAN-00:10 | 2572.00 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 6201.29 | 29270.80 | 05-SEP-01:10 | 983401.64 | 02-FEB-21:00 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 4412.44 | 15908.90 | 20-OCT-10:10 | 898540.71 | 02-FEB-21:20 |
WaterSystems:Gas | 2279.89 | 15908.90 | 02-JAN-16:10 | 180194.64 | 17-FEB-21:30 |
Water Heater:WaterSystems:Gas | 2279.89 | 15908.90 | 02-JAN-16:10 | 180194.64 | 17-FEB-21:30 |
Heating:Gas | 2132.55 | 0.00 | 24-FEB-14:30 | 762309.68 | 02-FEB-06:00 |
Boiler:Heating:Gas | 2132.55 | 0.00 | 24-FEB-14:30 | 762309.68 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2665.09 | 0.00 | 01-JAN-00:10 | 670691.85 | 26-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 2665.09 | 0.00 | 01-JAN-00:10 | 670691.85 | 26-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 2665.09 | 0.00 | 01-JAN-00:10 | 670691.85 | 26-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22789.76 | 150884.02 | 10-APR-11:10 | 2853473.91 | 26-JUL-18:20 |
EnergyTransfer:Building | 4764.43 | 62245.92 | 06-JAN-11:10 | 314631.35 | 26-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 709.74 | 8385.39 | 05-FEB-04:00 | 35649.35 | 29-JUL-10:40 |
Refrigeration:EnergyTransfer | 179.59 | 826.12 | 02-FEB-04:00 | 10329.88 | 16-MAY-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.80 | 413.06 | 02-FEB-04:00 | 5164.94 | 16-MAY-07:20 |
EnergyTransfer:Plant | 8780.65 | 20800.80 | 06-OCT-14:10 | 1575384.41 | 26-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.52 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.27 | 212.62 | 02-FEB-06:00 | 2537.81 | 06-JUN-13:10 |
PlantLoopHeatingDemand:Facility | 2440.21 | 9859.34 | 30-AUG-00:10 | 668847.82 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.75 | 9817.54 | 23-AUG-00:10 | 63664.82 | 21-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 847.75 | 9817.54 | 23-AUG-00:10 | 63664.82 | 21-FEB-07:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 371.74 | 0.22 | 06-FEB-04:30 | 37184.31 | 25-NOV-21:50 |
Heating:EnergyTransfer | 328.66 | 0.00 | 13-JAN-11:20 | 119618.15 | 04-FEB-19:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.41 | 0.00 | 01-JAN-00:10 | 7811.62 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 4345.97 | 12270.78 | 04-FEB-11:20 | 311026.50 | 26-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 371.33 | 0.00 | 31-JAN-11:50 | 37184.31 | 25-NOV-21:50 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.65 | 0.06 | 30-NOV-21:40 | 3878.88 | 20-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 7.45 | 0.00 | 02-JAN-09:50 | 2853.08 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.21 | 0.00 | 01-JAN-00:10 | 3878.88 | 20-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.07 | 0.77 | 07-JAN-17:20 | 1862.08 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 1316.09 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 32.95 | 0.00 | 06-JAN-10:50 | 1862.08 | 02-FEB-06:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 19.62 | 0.02 | 13-FEB-14:40 | 1840.97 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 2.06 | 0.00 | 01-JAN-00:10 | 1840.97 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.56 | 0.00 | 01-JAN-02:10 | 1123.29 | 30-JUN-21:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.47 | 0.01 | 24-FEB-08:00 | 1187.30 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.11 | 0.00 | 12-JAN-19:10 | 1187.30 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.36 | 0.00 | 01-JAN-00:10 | 600.82 | 30-JUN-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.77 | 3419.79 | 04-FEB-11:30 | 38767.41 | 05-JAN-22:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 349.49 | 04-FEB-11:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.77 | 3230.16 | 04-FEB-11:30 | 38767.41 | 05-JAN-22:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 193.53 | 0.17 | 29-JAN-17:20 | 14127.21 | 04-NOV-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.30 | 0.00 | 01-JAN-00:10 | 6328.03 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 192.23 | 0.00 | 01-JAN-13:50 | 14127.21 | 04-NOV-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 743.88 | 31.21 | 31-JAN-16:20 | 41277.22 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.89 | 0.00 | 01-JAN-00:10 | 21887.39 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 742.99 | 0.00 | 06-JAN-10:50 | 41277.22 | 02-FEB-06:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 61.64 | 0.00 | 01-JAN-08:10 | 11247.94 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.56 | 0.00 | 01-JAN-08:10 | 7845.18 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 32.08 | 0.00 | 01-JAN-00:10 | 11247.94 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.37 | 0.00 | 01-JAN-08:10 | 11053.23 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.07 | 0.00 | 01-JAN-08:10 | 8110.70 | 04-FEB-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.29 | 0.00 | 01-JAN-00:10 | 11053.23 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 218.41 | 0.00 | 01-JAN-00:10 | 53312.08 | 20-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 9.89 | 0.00 | 01-JAN-00:10 | 19915.99 | 19-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 208.53 | 0.00 | 01-JAN-00:10 | 53312.08 | 20-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 390.52 | 0.00 | 01-JAN-08:10 | 70263.55 | 18-JUN-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 83.70 | 0.00 | 01-JAN-08:10 | 44307.43 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 306.82 | 0.00 | 01-JAN-00:10 | 70263.55 | 18-JUN-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.74 | 0.00 | 01-JAN-08:10 | 9713.23 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.56 | 0.00 | 01-JAN-08:10 | 7783.48 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 31.18 | 0.00 | 01-JAN-00:10 | 9713.23 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 62.40 | 0.00 | 01-JAN-08:10 | 9717.14 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 35.11 | 0.00 | 01-JAN-08:10 | 8009.47 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.30 | 0.00 | 01-JAN-00:10 | 9717.14 | 02-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 121.31 | 0.49 | 21-NOV-09:50 | 9254.59 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 24.70 | 0.00 | 02-JAN-10:40 | 9254.59 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 96.61 | 0.00 | 01-JAN-00:10 | 7377.86 | 30-JUN-19:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.45 | 0.00 | 01-JAN-08:10 | 3109.36 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.46 | 0.00 | 01-JAN-08:10 | 2369.85 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.99 | 0.00 | 01-JAN-00:10 | 3109.36 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.18 | 0.00 | 01-JAN-08:10 | 3064.28 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.20 | 0.00 | 01-JAN-08:10 | 2372.84 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.98 | 0.00 | 01-JAN-00:10 | 3064.28 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 85.36 | 0.00 | 01-JAN-08:10 | 13548.46 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 29.33 | 0.00 | 01-JAN-08:10 | 10259.07 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 56.03 | 0.00 | 01-JAN-00:10 | 13548.46 | 07-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 417.73 | 48.37 | 31-JAN-13:50 | 21992.70 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.07 | 0.00 | 01-JAN-00:10 | 5630.68 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 417.66 | 0.00 | 06-JAN-10:50 | 21992.70 | 26-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 458.96 | 3.80 | 04-FEB-15:00 | 23802.46 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 5311.04 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 458.91 | 0.00 | 31-JAN-11:40 | 23802.46 | 19-JAN-02:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 619.94 | 6402.21 | 05-FEB-04:00 | 30579.69 | 29-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.91 | 0.10 | 13-NOV-19:00 | 6902.33 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 13.66 | 0.00 | 01-JAN-10:50 | 6902.33 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 57.24 | 0.00 | 01-JAN-00:10 | 4310.55 | 30-JUN-15:00 |
WaterSystems:EnergyTransfer | 847.75 | 9817.54 | 23-AUG-00:10 | 63664.82 | 21-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 847.75 | 9817.54 | 23-AUG-00:10 | 63664.82 | 21-FEB-07:40 |
EnergyTransfer:HVAC | 9244.68 | 3649.53 | 19-MAR-10:30 | 987862.99 | 26-JUL-18:20 |
HeatingCoils:EnergyTransfer | 1592.46 | 0.00 | 19-MAR-19:20 | 614823.71 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1592.46 | 0.00 | 19-MAR-19:20 | 614823.71 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1592.46 | 0.00 | 19-MAR-19:20 | 614823.71 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2665.09 | 0.00 | 01-JAN-00:10 | 670691.85 | 26-JUL-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 4670.27 | 0.00 | 05-JAN-08:00 | 553829.19 | 05-JAN-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 316.86 | 0.00 | 01-JAN-00:10 | 324353.83 | 04-AUG-13:00 |
Boilers:EnergyTransfer | 1588.26 | 0.00 | 24-FEB-14:30 | 611095.51 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2717.61 | 0.00 | 01-JAN-00:10 | 673931.87 | 26-JUL-18:20 |
HeatRejection:EnergyTransfer | 3537.23 | 0.00 | 01-JAN-00:10 | 865509.93 | 26-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.409 | -371.335 | 0.000 | 0.000 | 148.304 | 141.590 | 150.259 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -69.227 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 7.449 | -28.205 | 0.000 | 0.000 | 16.023 | 7.580 | 10.186 | 20.527 | 0.000 | 0.258 | 0.000 | 0.000 | -14.184 | 0.000 | -11.691 | -7.942 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.116 | -32.954 | 0.000 | 0.000 | 17.725 | 8.778 | 11.795 | 0.000 | 0.000 | 0.058 | 0.000 | 0.000 | 0.000 | 0.000 | -2.552 | -2.965 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.001 | -594.768 | 0.000 | 0.000 | 11.707 | 3.578 | 658.148 | 0.000 | 0.000 | 0.202 | 0.000 | 0.000 | 0.000 | 0.000 | -8.011 | -70.857 |
CAFE_FLR_1 | 0.000 | 0.000 | 1.295 | -192.237 | 0.000 | 0.000 | 200.490 | 15.551 | 14.341 | 57.039 | 0.000 | 0.617 | 0.000 | 0.000 | -41.512 | 0.000 | -30.739 | -24.844 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.891 | -742.989 | 0.000 | 0.000 | 582.624 | 143.496 | 149.002 | 75.527 | 0.000 | 1.343 | 0.000 | 0.000 | -56.206 | 0.000 | -62.499 | -91.189 |
ROOM_1_FLR_3 | 29.563 | -20.836 | 0.000 | -11.241 | 0.000 | 0.000 | 9.759 | 9.320 | 12.292 | 39.234 | 0.000 | 0.626 | 0.000 | 0.000 | -34.303 | 0.000 | -14.443 | -19.971 |
ROOM_2_FLR_3 | 35.070 | -17.114 | 0.000 | -11.180 | 0.000 | 0.000 | 9.783 | 9.318 | 12.291 | 28.574 | 0.000 | 0.596 | 0.000 | 0.000 | -36.385 | 0.000 | -14.290 | -16.666 |
ROOM_3_MULT19_FLR_3 | 9.881 | -196.007 | 0.005 | -12.520 | 0.000 | 0.000 | 0.000 | 111.282 | 228.754 | 226.508 | 0.000 | 0.286 | 0.004 | 0.000 | -209.436 | 0.000 | -83.974 | -74.781 |
ROOM_4_MULT19_FLR_3 | 83.696 | -155.027 | 0.000 | -151.783 | 0.000 | 0.000 | 185.308 | 111.313 | 228.817 | 67.904 | 0.000 | 7.053 | 0.000 | 0.000 | -207.952 | 0.000 | -84.370 | -84.958 |
ROOM_5_FLR_3 | 29.555 | -19.933 | 0.000 | -11.246 | 0.000 | 0.000 | 9.754 | 9.320 | 12.292 | 37.916 | 0.000 | 0.627 | 0.000 | 0.000 | -33.694 | 0.000 | -14.481 | -20.110 |
ROOM_6_FLR_3 | 35.107 | -16.107 | 0.000 | -11.187 | 0.000 | 0.000 | 9.779 | 9.318 | 12.291 | 27.088 | 0.000 | 0.598 | 0.000 | 0.000 | -35.616 | 0.000 | -14.328 | -16.942 |
ROOM_1_FLR_6 | 10.457 | -6.180 | 0.000 | -2.808 | 0.000 | 0.000 | 2.442 | 2.330 | 3.073 | 9.751 | 0.000 | 0.169 | 0.000 | 0.000 | -8.600 | 0.000 | -3.649 | -6.985 |
ROOM_2_FLR_6 | 12.202 | -5.184 | 0.000 | -2.794 | 0.000 | 0.000 | 2.448 | 2.330 | 3.073 | 7.093 | 0.000 | 0.159 | 0.000 | 0.000 | -9.119 | 0.000 | -3.608 | -6.600 |
ROOM_3_MULT9_FLR_6 | 29.328 | -37.830 | 0.000 | -18.195 | 0.000 | 0.000 | 21.870 | 13.182 | 27.097 | 52.384 | 0.000 | 1.176 | 0.000 | 0.000 | -39.990 | 0.000 | -17.861 | -31.160 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.067 | -417.663 | 0.000 | 0.000 | 324.517 | 30.077 | 175.857 | 7.073 | 0.000 | 0.134 | 0.000 | 0.000 | -26.089 | 0.000 | -9.436 | -84.538 |
DINING_FLR_6 | 0.000 | 0.000 | 0.041 | -458.917 | 0.000 | 0.000 | 322.086 | 30.077 | 175.857 | 6.825 | 0.000 | 0.126 | 0.000 | 0.000 | -26.784 | 0.000 | -9.522 | -39.788 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -619.926 | 0.000 | 0.000 | 29.173 | 11.675 | 550.372 | 18.126 | 0.000 | 0.094 | 36.104 | 0.000 | -17.078 | 0.000 | -8.541 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 2.058 | -17.562 | 0.000 | 0.000 | 0.000 | 7.530 | 12.472 | 0.000 | 0.000 | 0.131 | 0.820 | 0.000 | 0.000 | 0.000 | -5.448 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.107 | -8.365 | 0.000 | 0.000 | 0.000 | 2.417 | 3.598 | 0.000 | 0.000 | 0.094 | 2.902 | 0.000 | 0.000 | 0.000 | -3.752 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 24.697 | -96.609 | 0.000 | 0.000 | 0.000 | 109.607 | 0.000 | 34.834 | 0.000 | 0.468 | 0.000 | 0.000 | -41.649 | 0.000 | -16.533 | -14.814 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 13.663 | -57.243 | 0.000 | 0.000 | 0.000 | 29.000 | 0.000 | 16.906 | 0.000 | 0.139 | 23.823 | 0.000 | -18.867 | 0.000 | -7.420 | -0.001 |
Total Facility | 274.861 | -474.216 | 53.798 | -3871.727 | 0.000 | 0.000 | 1903.791 | 818.668 | 2451.865 | 733.308 | 0.000 | 14.953 | 63.653 | 0.000 | -857.464 | 0.000 | -427.149 | -684.339 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-21:33 | 0.00 | 0.00 | 0.00 | -37450.75 | 0.00 | 0.00 | 5704.65 | 9005.57 | 8516.89 | 0.00 | 0.00 | 0.00 | 14223.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-OCT-12:50 | 0.00 | 0.00 | 0.00 | -3878.87 | 0.00 | 0.00 | 150.60 | 172.19 | 252.59 | 6801.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.40 | -3447.01 |
RETAIL_2_FLR_1 | 05-JAN-21:22 | 0.00 | 0.00 | 0.00 | -2093.12 | 0.00 | 0.00 | 829.09 | 638.05 | 752.15 | 0.00 | 0.00 | 0.00 | 124.19 | 0.00 | -0.00 | 0.00 | -250.35 | 0.00 |
LAUNDRY_FLR_1 | 05-JAN-21:33 | 0.00 | 0.00 | 0.00 | -41070.50 | 0.00 | 0.00 | 510.95 | 260.07 | 41967.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -788.10 | -880.25 |
CAFE_FLR_1 | 04-NOV-12:40 | 0.00 | 0.00 | 0.00 | -14126.20 | 0.00 | 0.00 | 2968.72 | 259.48 | 355.63 | 19736.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -613.22 | -8580.44 |
LOBBY_FLR_1 | 25-NOV-21:12 | 0.00 | 0.00 | 0.00 | -49424.86 | 0.00 | 0.00 | 24435.41 | 9403.42 | 8445.65 | 0.00 | 0.00 | 0.00 | 19853.46 | 0.00 | -6771.17 | 0.00 | -5941.91 | 0.00 |
ROOM_1_FLR_3 | 05-JUL-18:02 | 0.00 | -12991.84 | 0.00 | -715.59 | 0.00 | 0.00 | 335.50 | 826.67 | 516.26 | 8043.99 | 0.00 | 401.18 | 3583.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 05-JUL-18:02 | 0.00 | -12680.51 | 0.00 | -716.34 | 0.00 | 0.00 | 335.50 | 826.57 | 516.20 | 8299.04 | 0.00 | 340.42 | 3079.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-OCT-12:30 | 0.00 | -53312.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.15 | 5097.90 | 82231.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -727.73 | -33983.48 |
ROOM_4_MULT19_FLR_3 | 15-APR-18:02 | 0.00 | -68267.73 | 0.00 | -9818.71 | 0.00 | 0.00 | 5380.98 | 11125.36 | 9610.21 | 5213.16 | 0.00 | 672.75 | 46083.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 27-JUN-15:02 | 0.00 | -11503.64 | 0.00 | -704.80 | 0.00 | 0.00 | 235.28 | 74.52 | 273.93 | 3186.61 | 0.00 | 203.61 | 8234.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 28-JUN-15:02 | 0.00 | -11401.45 | 0.00 | -703.36 | 0.00 | 0.00 | 235.28 | 74.51 | 273.90 | 2884.75 | 0.00 | 163.46 | 8472.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 25-JUN-18:02 | 0.00 | -3397.03 | 0.00 | -179.74 | 0.00 | 0.00 | 70.80 | 232.86 | 129.07 | 2037.44 | 0.00 | 50.91 | 1055.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 25-JUN-18:02 | 0.00 | -3345.68 | 0.00 | -179.95 | 0.00 | 0.00 | 70.80 | 232.84 | 129.05 | 2104.88 | 0.00 | 50.83 | 937.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:02 | 0.00 | -11631.07 | 0.00 | -2833.44 | 0.00 | 0.00 | 537.17 | 105.40 | 603.86 | 2031.91 | 0.00 | 0.00 | 12874.36 | 0.00 | -0.00 | 0.00 | -1688.19 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -33685.10 | 0.00 | 0.00 | 18111.04 | 448.20 | 2249.30 | 0.00 | 0.00 | 0.00 | 16662.03 | 0.00 | -2928.80 | 0.00 | -856.67 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -35702.44 | 0.00 | 0.00 | 17888.02 | 448.20 | 2249.30 | 0.00 | 0.00 | 0.00 | 18944.64 | 0.00 | -2966.97 | 0.00 | -860.75 | 0.00 |
KITCHEN_FLR_6 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | -30579.31 | 0.00 | 0.00 | 464.28 | 265.20 | 24259.91 | 2735.69 | 0.00 | 26.08 | 2828.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 30-JUN-21:10 | 0.00 | 0.00 | 0.00 | -1123.27 | 0.00 | 0.00 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 104.29 | 0.00 | -0.00 | 0.00 | -10.06 | 0.00 |
STORAGE_FLR_1 | 30-JUN-21:10 | 0.00 | 0.00 | 0.00 | -600.81 | 0.00 | 0.00 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 295.23 | 0.00 | -0.00 | 0.00 | -4.60 | 0.00 |
CORRIDOR_FLR_3 | 30-JUN-19:20 | 0.00 | 0.00 | 0.00 | -7377.76 | 0.00 | 0.00 | 0.00 | 8963.14 | 0.00 | 1130.26 | 0.00 | 95.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2811.32 |
CORRIDOR_FLR_6 | 30-JUN-15:15 | 0.00 | 0.00 | 0.00 | -4313.92 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 1531.93 | 0.00 | 74.80 | 2048.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-SEP-18:02 | 0.00 | -163025.40 | 0.00 | -187446.14 | 0.00 | 0.00 | 70391.68 | 63987.42 | 122326.88 | 11996.12 | 0.00 | 3829.65 | 77939.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:21 | 0.00 | 0.00 | 8526.15 | -0.00 | 0.00 | 0.00 | 3380.89 | 3216.28 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18849.45 |
RETAIL_1_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 2939.35 | -0.00 | 0.00 | 0.00 | 420.93 | 344.37 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1490.37 | 0.00 | -1058.19 | -1589.10 |
RETAIL_2_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1405.70 | -0.00 | 0.00 | 0.00 | 393.65 | 199.39 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -206.36 | -2084.88 |
LAUNDRY_FLR_1 | 06-JAN-10:41 | 0.00 | 0.00 | 3129.73 | -0.00 | 0.00 | 0.00 | 165.39 | 81.27 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -706.10 | -18991.11 |
CAFE_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 6989.99 | -0.00 | 0.00 | 0.00 | 5236.42 | 740.17 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4343.28 | 0.00 | -2764.06 | -6468.89 |
LOBBY_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 24507.59 | -0.00 | 0.00 | 0.00 | 12666.39 | 3123.28 | 3694.97 | 23372.70 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5151.10 | -62213.84 |
ROOM_1_FLR_3 | 02-FEB-08:05 | 8739.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.30 | 407.51 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4457.57 | 0.00 | -1835.79 | -3534.18 |
ROOM_2_FLR_3 | 02-FEB-11:03 | 9140.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 | 58.21 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3464.85 | 0.00 | -1639.71 | -4475.11 |
ROOM_3_MULT19_FLR_3 | 19-JAN-06:00 | 19915.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.32 | 3921.46 | 0.00 | 0.00 | 0.00 | 4740.43 | 0.00 | -22895.78 | 0.00 | -7210.93 | 0.00 |
ROOM_4_MULT19_FLR_3 | 03-FEB-11:01 | 49294.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.53 | 695.34 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15785.16 | 0.00 | -8203.29 | -33184.86 |
ROOM_5_FLR_3 | 04-FEB-08:04 | 8559.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.25 | 523.94 | 948.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3231.54 | 0.00 | -1589.98 | -5491.48 |
ROOM_6_FLR_3 | 03-FEB-18:02 | 8799.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.63 | 628.66 | 537.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4379.94 | 0.00 | -1491.67 | -4382.03 |
ROOM_1_FLR_6 | 09-DEC-16:13 | 2429.85 | 85.97 | 0.00 | -85.97 | 0.00 | 0.00 | 37.43 | 14.55 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -895.16 | 0.00 | -301.63 | -1361.43 |
ROOM_2_FLR_6 | 31-JAN-08:04 | 2619.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.88 | 101.87 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1093.71 | 0.00 | -387.83 | -1407.92 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 10477.67 | 527.14 | 0.00 | -527.14 | 0.00 | 0.00 | 341.11 | 82.34 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4211.49 | 0.00 | -1381.04 | -5982.13 |
BANQUET_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 7037.06 | -0.00 | 0.00 | 0.00 | 7053.65 | 597.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1382.69 | 0.00 | -768.79 | -19284.75 |
DINING_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6856.47 | -0.00 | 0.00 | 0.00 | 6973.06 | 597.61 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1406.67 | 0.00 | -773.52 | -18994.85 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1865.21 | -0.00 | 0.00 | 0.00 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -444.34 | -1901.19 |
STORAGE_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1199.23 | -0.00 | 0.00 | 0.00 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -304.80 | -1038.55 |
CORRIDOR_FLR_3 | 04-FEB-11:21 | 0.00 | 0.00 | 9433.78 | -0.00 | 0.00 | 0.00 | 0.00 | 2489.76 | 0.00 | 7035.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1483.24 | -17476.09 |
CORRIDOR_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 7019.12 | -0.00 | 0.00 | 0.00 | 0.00 | 658.76 | 0.00 | 4159.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -617.10 | -11220.26 |
Total Facility | 04-FEB-19:02 | 37827.84 | 59600.87 | 35462.51 | -59600.87 | 0.00 | 0.00 | 71473.44 | 62998.80 | 115172.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90025.93 | 0.00 | -34219.22 | -198689.70 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.0996 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 20.7362 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.0478 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 12.0478 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2998 | 2.2998 | 1.3132 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3123 | 0.3123 | 0.1783 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2226 | 0.2226 | 0.1271 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4031 | 3.4031 | 1.9432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3647 | 1.3647 | 0.7793 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7038 | 4.7038 | 2.6859 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1540 | 2.1540 | 1.2299 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2624 | 2.2624 | 1.2918 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3439 | 2.3439 | 1.3384 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1636 | 0.1636 | 0.0934 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0905 | 0.0905 | 0.0517 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6777 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5918 | 0.5918 | 0.3379 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.0996 | 20.7362 | 21.0996 | 12.0478 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3132 | 1.3132 | 1.3132 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1783 | 0.1783 | 0.1783 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1271 | 0.1271 | 0.1271 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9432 | 1.9432 | 1.9432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7793 | 0.7793 | 0.7793 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6859 | 2.6859 | 2.6859 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2299 | 1.2299 | 1.2299 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2918 | 1.2918 | 1.2918 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3384 | 1.3384 | 1.3384 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0934 | 0.0934 | 0.0934 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0517 | 0.0517 | 0.0517 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6777 | 0.6777 | 0.6777 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3379 | 0.3379 | 0.3379 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.0478 | 12.0478 | 12.0478 | 12.0478 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:50:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 272.67 |
Number of hours cooling loads not met | 269.83 |
Number of hours not met | 542.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 2132.55 | 762309.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 819.62 | 206788.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 818.67 | 73068.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 163.11 | 10390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.57 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.84 | 1321.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 545.57 | 28743.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 64.90 | 5674.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 205.36 | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4750.74 | 2279.89 | 180194.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.19 | 1942.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.80 | 1195.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.10 | 5487.38 |
Natural Gas | 1788.85 | 6201.29 |
Additional | 0.00 | 0.00 |
Total | 3594.96 | 11688.67 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.16 |
Space Heating | 0.00 |
Space Cooling | 72.24 |
Fans (All) | 48.09 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 483.67 |
Subtotal | 483.67 |
Natural Gas [MJ/m2] | |
Space Heating | 187.97 |
Service Water Heating | 200.95 |
Miscellaneous (All) | 546.60 |
Subtotal | 546.60 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.00 |
Space Heating | 18.24 |
Space Cooling | 7.01 |
Fans (All) | 4.67 |
Service Water Heating | 20.28 |
Receptacle Equipment | 30.23 |
Miscellaneous | 12.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 3061. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2739. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1591. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.608091E+12 |
February | 0.000 | 0.428569E+12 |
March | 0.000 | 0.173412E+12 |
April | 0.000 | 0.903015E+11 |
May | 0.000 | 0.544040E+11 |
June | 0.000 | 0.330781E+11 |
July | 0.000 | 0.114133E+11 |
August | 0.000 | 0.148240E+11 |
September | 0.000 | 0.480569E+11 |
October | 0.000 | 0.778578E+11 |
November | 0.000 | 0.229562E+12 |
December | 0.000 | 0.362983E+12 |
Annual Sum or Average | 0.213255E+13 | |
Minimum of Months | 0.000 | 0.114133E+11 |
Maximum of Months | 0.000 | 0.608091E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326138E+11 | 37155.91 | 19-JAN-01:51 | -23.9 | -24.0 | 0.689421E+10 | 4618.06 | 04-JAN-22:10 | -17.1 | -17.4 |
February | 0.257559E+11 | 32368.60 | 02-FEB-06:02 | -36.7 | -36.8 | 0.552492E+10 | 4386.64 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.252990E+11 | 11745.10 | 25-MAR-15:00 | 18.90 | 10.41 | 0.665923E+10 | 4306.37 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.229019E+11 | 12973.14 | 15-APR-21:10 | 22.52 | 16.91 | 0.615717E+10 | 3993.43 | 21-APR-21:10 | -0.1 | -0.4 |
May | 0.262886E+11 | 13401.39 | 31-MAY-21:10 | 21.80 | 16.81 | 0.637450E+10 | 4066.41 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.295370E+11 | 14118.80 | 08-JUN-20:00 | 21.10 | 15.58 | 0.623368E+10 | 4218.11 | 05-JUN-21:10 | 11.70 | 11.34 |
July | 0.338255E+11 | 14508.45 | 12-JUL-21:00 | 21.10 | 16.84 | 0.649546E+10 | 4129.63 | 11-JUL-21:10 | 15.92 | 14.61 |
August | 0.361769E+11 | 15453.50 | 09-AUG-20:00 | 21.10 | 15.58 | 0.702269E+10 | 4460.03 | 18-AUG-21:10 | 16.02 | 13.73 |
September | 0.353756E+11 | 17688.62 | 29-SEP-21:00 | 2.80 | 1.14 | 0.737702E+10 | 4837.02 | 22-SEP-21:19 | 8.87 | 5.98 |
October | 0.363320E+11 | 19125.86 | 18-OCT-21:00 | 0.00 | -1.4 | 0.811990E+10 | 4837.05 | 31-OCT-23:19 | 0.90 | -1.2 |
November | 0.345166E+11 | 37451.11 | 25-NOV-21:33 | -24.0 | -24.4 | 0.774872E+10 | 4837.04 | 01-NOV-23:19 | 5.93 | 4.73 |
December | 0.327110E+11 | 15902.16 | 01-DEC-22:00 | -3.9 | -4.7 | 0.794050E+10 | 4836.97 | 01-DEC-22:19 | -3.7 | -4.5 |
Annual Sum or Average | 0.371334E+12 | 0.825480E+11 | ||||||||
Minimum of Months | 0.229019E+11 | 11745.10 | -36.7 | -36.8 | 0.552492E+10 | 3993.43 | -17.1 | -17.4 | ||
Maximum of Months | 0.363320E+11 | 37451.11 | 22.52 | 16.91 | 0.811990E+10 | 4837.05 | 16.02 | 14.61 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308635E+09 | 1863.44 | 12-JAN-12:40 | 2.03 | 0.42 | 0.586714E+09 | 364.17 | 26-JAN-04:40 | -17.0 | -17.4 |
February | 0.548118E+09 | 2545.98 | 08-FEB-13:20 | 2.40 | 1.27 | 0.512528E+09 | 368.44 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.116172E+10 | 2069.33 | 25-MAR-14:25 | 17.80 | 10.03 | 0.629612E+09 | 395.49 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.195303E+10 | 2858.76 | 15-APR-13:20 | 28.67 | 20.38 | 0.616301E+09 | 424.36 | 18-APR-21:10 | 16.32 | 13.38 |
May | 0.324725E+10 | 2078.35 | 31-MAY-18:40 | 26.47 | 18.89 | 0.634080E+09 | 424.46 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.398696E+10 | 2209.51 | 26-JUN-18:10 | 29.72 | 22.35 | 0.633988E+09 | 450.40 | 26-JUN-21:10 | 25.40 | 21.25 |
July | 0.456365E+10 | 2185.33 | 30-JUL-13:20 | 26.87 | 20.17 | 0.658579E+09 | 439.60 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.456391E+10 | 2328.64 | 29-AUG-13:30 | 23.60 | 16.38 | 0.667643E+09 | 437.83 | 22-AUG-21:10 | 22.02 | 19.96 |
September | 0.374018E+10 | 3696.44 | 07-SEP-13:00 | 31.70 | 18.03 | 0.644112E+09 | 460.32 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.252316E+10 | 3878.88 | 20-OCT-12:50 | 21.68 | 12.53 | 0.642983E+09 | 436.27 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 0.110545E+10 | 3508.63 | 04-NOV-13:10 | 13.98 | 6.79 | 0.601496E+09 | 400.42 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.503128E+09 | 2932.59 | 03-DEC-13:00 | 5.60 | 2.40 | 0.622487E+09 | 364.15 | 22-DEC-04:49 | -13.8 | -14.0 |
Annual Sum or Average | 0.282052E+11 | 0.745052E+10 | ||||||||
Minimum of Months | 0.308635E+09 | 1863.44 | 2.03 | 0.42 | 0.512528E+09 | 364.15 | -17.0 | -17.4 | ||
Maximum of Months | 0.456391E+10 | 3878.88 | 31.70 | 22.35 | 0.667643E+09 | 460.32 | 25.40 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192539E+10 | 2093.15 | 05-JAN-21:22 | -23.6 | -23.9 | 0.706310E+09 | 513.68 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.200476E+10 | 1862.08 | 02-FEB-06:00 | -36.7 | -36.8 | 0.627221E+09 | 527.45 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.240789E+10 | 1259.86 | 25-MAR-15:00 | 18.90 | 10.41 | 0.793614E+09 | 547.36 | 24-MAR-21:10 | 2.43 | 0.92 |
April | 0.264752E+10 | 1547.06 | 15-APR-21:10 | 22.52 | 16.91 | 0.794431E+09 | 560.97 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.310445E+10 | 1582.63 | 31-MAY-21:10 | 21.80 | 16.81 | 0.835746E+09 | 545.24 | 22-MAY-21:10 | 9.32 | 7.91 |
June | 0.333439E+10 | 1630.43 | 30-JUN-21:10 | 22.03 | 17.03 | 0.814980E+09 | 553.75 | 30-JUN-21:10 | 22.03 | 17.03 |
July | 0.361504E+10 | 1620.45 | 03-JUL-21:10 | 24.22 | 22.81 | 0.838006E+09 | 549.50 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.358497E+10 | 1610.10 | 22-AUG-21:10 | 22.02 | 19.96 | 0.852484E+09 | 554.45 | 04-AUG-21:10 | 18.30 | 17.90 |
September | 0.318921E+10 | 1660.36 | 07-SEP-21:10 | 22.43 | 16.37 | 0.830010E+09 | 569.51 | 08-SEP-21:10 | 17.38 | 14.80 |
October | 0.281358E+10 | 1434.38 | 20-OCT-15:50 | 21.63 | 12.81 | 0.846394E+09 | 562.53 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.233171E+10 | 1780.69 | 25-NOV-21:33 | -24.0 | -24.4 | 0.763903E+09 | 557.66 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.199487E+10 | 1066.50 | 05-DEC-22:10 | -7.1 | -9.3 | 0.754476E+09 | 507.77 | 05-DEC-22:10 | -7.1 | -9.3 |
Annual Sum or Average | 0.329538E+11 | 0.945758E+10 | ||||||||
Minimum of Months | 0.192539E+10 | 1066.50 | -36.7 | -36.8 | 0.627221E+09 | 507.77 | -7.1 | -9.3 | ||
Maximum of Months | 0.361504E+10 | 2093.15 | 24.22 | 22.81 | 0.852484E+09 | 569.51 | 24.22 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172967E+09 | 626.15 | 13-JAN-22:10 | 2.02 | 0.71 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.338494E+09 | 644.76 | 24-FEB-22:10 | 1.93 | 1.42 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.864797E+09 | 832.94 | 25-MAR-15:00 | 18.90 | 10.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.142778E+10 | 1037.32 | 16-APR-20:00 | 23.30 | 18.48 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.209073E+10 | 1067.75 | 31-MAY-21:10 | 21.80 | 16.81 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.234039E+10 | 1123.29 | 30-JUN-21:10 | 22.03 | 17.03 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.257111E+10 | 1114.30 | 03-JUL-21:10 | 24.22 | 22.81 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.253662E+10 | 1107.71 | 03-AUG-21:10 | 24.32 | 23.15 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.218172E+10 | 1111.29 | 07-SEP-21:10 | 22.43 | 16.37 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.178008E+10 | 941.77 | 20-OCT-15:00 | 23.30 | 13.34 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.985309E+09 | 840.37 | 08-NOV-22:10 | 14.40 | 12.79 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.271943E+09 | 618.13 | 04-DEC-22:10 | 1.78 | 0.08 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.175619E+11 | 0.00 | ||||||||
Minimum of Months | 0.172967E+09 | 618.13 | 1.78 | 0.08 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.257111E+10 | 1123.29 | 24.32 | 23.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6045320.69 | 245.01 | 13-JAN-22:00 | 2.20 | 0.77 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 31040710.74 | 325.48 | 24-FEB-22:00 | 2.20 | 1.69 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.258423E+09 | 427.22 | 25-MAR-15:00 | 18.90 | 10.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.579878E+09 | 555.61 | 16-APR-21:10 | 21.93 | 18.00 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.110013E+10 | 570.25 | 31-MAY-21:10 | 21.80 | 16.81 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.126443E+10 | 600.82 | 30-JUN-21:10 | 22.03 | 17.03 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.139447E+10 | 597.11 | 03-JUL-21:10 | 24.22 | 22.81 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.137181E+10 | 593.23 | 03-AUG-21:10 | 24.32 | 23.15 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.115479E+10 | 594.73 | 07-SEP-21:10 | 22.43 | 16.37 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.849825E+09 | 517.00 | 20-OCT-15:00 | 23.30 | 13.34 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.339828E+09 | 442.32 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 14191990.34 | 237.01 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.836486E+10 | 0.00 | ||||||||
Minimum of Months | 6045320.69 | 237.01 | 2.20 | 0.77 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.139447E+10 | 600.82 | 24.32 | 23.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476754E+11 | 41074.57 | 05-JAN-21:33 | -23.7 | -24.0 | 0.509373E+09 | 397.87 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.437036E+11 | 36261.29 | 24-FEB-21:00 | 2.20 | 1.49 | 0.454082E+09 | 399.63 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.491894E+11 | 36756.96 | 28-MAR-20:00 | 11.70 | 8.26 | 0.575216E+09 | 401.95 | 24-MAR-21:10 | 2.43 | 0.92 |
April | 0.486506E+11 | 37704.54 | 18-APR-20:00 | 18.30 | 15.20 | 0.552556E+09 | 403.86 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.519458E+11 | 37957.13 | 31-MAY-20:00 | 24.40 | 17.90 | 0.561327E+09 | 402.75 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.512290E+11 | 38125.40 | 26-JUN-20:00 | 26.70 | 21.51 | 0.531739E+09 | 400.82 | 01-JUN-21:10 | 9.90 | 8.78 |
July | 0.531315E+11 | 37994.64 | 03-JUL-20:00 | 26.70 | 23.79 | 0.540572E+09 | 381.53 | 07-JUL-21:10 | 18.22 | 16.14 |
August | 0.532207E+11 | 38009.73 | 03-AUG-20:00 | 25.00 | 23.43 | 0.546586E+09 | 381.55 | 09-AUG-21:10 | 17.62 | 14.82 |
September | 0.504718E+11 | 38117.39 | 07-SEP-20:00 | 23.90 | 17.03 | 0.540550E+09 | 402.89 | 25-SEP-21:10 | 10.00 | 6.67 |
October | 0.505634E+11 | 37533.91 | 20-OCT-20:00 | 15.00 | 9.89 | 0.575827E+09 | 402.43 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.475511E+11 | 39825.92 | 25-NOV-21:12 | -23.7 | -24.1 | 0.544856E+09 | 402.38 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.474350E+11 | 35742.65 | 01-DEC-21:00 | -5.0 | -5.7 | 0.568157E+09 | 396.29 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.594767E+12 | 0.650084E+10 | ||||||||
Minimum of Months | 0.437036E+11 | 35742.65 | -23.7 | -24.1 | 0.454082E+09 | 381.53 | -3.8 | -4.6 | ||
Maximum of Months | 0.532207E+11 | 41074.57 | 26.70 | 23.79 | 0.575827E+09 | 403.86 | 18.22 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.857631E+10 | 8457.37 | 12-JAN-12:30 | 1.95 | 0.37 | 0.792880E+10 | 5833.51 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.103413E+11 | 10346.50 | 08-FEB-13:20 | 2.40 | 1.27 | 0.717319E+10 | 6019.25 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.134840E+11 | 9181.56 | 25-MAR-14:05 | 17.07 | 9.75 | 0.895051E+10 | 6305.33 | 23-MAR-21:40 | 9.07 | 5.84 |
April | 0.153816E+11 | 11392.05 | 15-APR-13:00 | 28.30 | 20.27 | 0.902315E+10 | 6407.13 | 17-APR-22:10 | 13.30 | 9.43 |
May | 0.190235E+11 | 9900.71 | 31-MAY-21:20 | 21.40 | 16.39 | 0.959127E+10 | 6274.81 | 05-MAY-22:10 | 14.03 | 10.36 |
June | 0.206513E+11 | 10252.38 | 26-JUN-21:20 | 25.20 | 21.19 | 0.944065E+10 | 6434.48 | 26-JUN-21:40 | 24.80 | 21.07 |
July | 0.224918E+11 | 10163.72 | 25-JUL-21:30 | 25.85 | 21.21 | 0.972332E+10 | 6377.57 | 25-JUL-21:40 | 25.77 | 21.14 |
August | 0.224758E+11 | 10135.61 | 02-AUG-21:30 | 24.15 | 21.61 | 0.992302E+10 | 6406.85 | 29-AUG-22:10 | 14.40 | 12.80 |
September | 0.200888E+11 | 12780.17 | 16-SEP-13:10 | 28.48 | 18.06 | 0.959655E+10 | 6462.02 | 07-SEP-22:19 | 20.03 | 16.02 |
October | 0.175015E+11 | 13883.66 | 20-OCT-12:50 | 21.68 | 12.53 | 0.963374E+10 | 6461.43 | 20-OCT-22:19 | 13.90 | 9.57 |
November | 0.126071E+11 | 14127.21 | 04-NOV-12:40 | 13.53 | 6.71 | 0.854474E+10 | 6323.65 | 03-NOV-21:40 | 5.37 | 2.99 |
December | 0.961192E+10 | 11999.32 | 03-DEC-12:50 | 5.50 | 2.39 | 0.843758E+10 | 5612.85 | 01-DEC-22:40 | -3.5 | -4.3 |
Annual Sum or Average | 0.192235E+12 | 0.107967E+12 | ||||||||
Minimum of Months | 0.857631E+10 | 8457.37 | 1.95 | 0.37 | 0.717319E+10 | 5612.85 | -3.5 | -4.3 | ||
Maximum of Months | 0.224918E+11 | 14127.21 | 28.48 | 21.61 | 0.992302E+10 | 6462.02 | 25.77 | 21.14 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477375E+11 | 44641.54 | 05-JAN-21:22 | -23.6 | -23.9 | 0.247764E+11 | 18351.85 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.471250E+11 | 41277.22 | 02-FEB-06:00 | -36.7 | -36.8 | 0.223210E+11 | 18699.51 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.553974E+11 | 28167.77 | 19-MAR-21:00 | 15.00 | 11.82 | 0.282224E+11 | 19180.24 | 24-MAR-21:30 | 1.70 | 0.37 |
April | 0.592288E+11 | 33361.23 | 16-APR-21:10 | 21.93 | 18.00 | 0.280395E+11 | 19183.40 | 20-APR-21:30 | 7.50 | 3.08 |
May | 0.687097E+11 | 34274.49 | 31-MAY-21:10 | 21.80 | 16.81 | 0.294713E+11 | 19183.17 | 18-MAY-21:00 | 10.00 | 7.43 |
June | 0.728467E+11 | 35001.56 | 26-JUN-21:10 | 25.40 | 21.25 | 0.285059E+11 | 19146.40 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.783967E+11 | 34789.52 | 03-JUL-21:10 | 24.22 | 22.81 | 0.291326E+11 | 18804.03 | 28-JUL-22:10 | 19.22 | 17.09 |
August | 0.780193E+11 | 34823.11 | 22-AUG-21:10 | 22.02 | 19.96 | 0.297163E+11 | 19181.86 | 17-AUG-22:10 | 14.32 | 12.46 |
September | 0.702283E+11 | 36116.48 | 07-SEP-21:10 | 22.43 | 16.37 | 0.290884E+11 | 19184.01 | 22-SEP-21:10 | 9.13 | 6.06 |
October | 0.633941E+11 | 32738.70 | 20-OCT-21:10 | 13.90 | 9.44 | 0.299796E+11 | 19183.63 | 24-OCT-21:10 | 9.90 | 5.73 |
November | 0.539014E+11 | 49425.94 | 25-NOV-21:12 | -23.7 | -24.1 | 0.270879E+11 | 19183.41 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.480000E+11 | 24306.48 | 04-DEC-23:10 | 2.30 | 0.32 | 0.267246E+11 | 18028.18 | 05-DEC-23:10 | -6.8 | -9.1 |
Annual Sum or Average | 0.742985E+12 | 0.333066E+12 | ||||||||
Minimum of Months | 0.471250E+11 | 24306.48 | -36.7 | -36.8 | 0.223210E+11 | 18028.18 | -6.8 | -9.1 | ||
Maximum of Months | 0.783967E+11 | 49425.94 | 25.40 | 22.81 | 0.299796E+11 | 19184.01 | 19.22 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4425394.85 | 2900.40 | 12-JAN-16:02 | 2.62 | 1.03 | 92688336.98 | 56.69 | 21-JAN-01:30 | -10.8 | -11.2 |
February | 35511771.80 | 3056.41 | 24-FEB-16:02 | 8.12 | 5.75 | 83871538.92 | 56.69 | 28-FEB-04:30 | -16.4 | -16.8 |
March | 0.126124E+09 | 3187.00 | 25-MAR-15:01 | 18.72 | 10.43 | 95185863.78 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.541725E+09 | 3285.24 | 16-APR-18:02 | 26.42 | 19.76 | 93373313.85 | 56.69 | 17-APR-21:49 | 13.40 | 9.43 |
May | 0.894698E+09 | 3320.81 | 30-MAY-18:02 | 25.40 | 19.83 | 98190522.54 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.149040E+10 | 3350.12 | 18-JUN-15:02 | 30.87 | 22.39 | 95426965.75 | 56.70 | 26-JUN-21:00 | 24.40 | 20.94 |
July | 0.181969E+10 | 3426.45 | 05-JUL-18:02 | 26.52 | 21.26 | 98831213.74 | 56.70 | 03-JUL-21:40 | 23.67 | 22.66 |
August | 0.162787E+10 | 3388.76 | 01-AUG-15:02 | 28.80 | 21.51 | 98866012.08 | 56.70 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.108448E+10 | 3303.19 | 11-SEP-15:02 | 28.22 | 20.07 | 94877489.26 | 56.69 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.314129E+09 | 3219.82 | 19-OCT-15:01 | 18.53 | 10.63 | 96715772.02 | 56.69 | 10-OCT-21:10 | 10.67 | 9.78 |
November | 72905150.04 | 3102.65 | 04-NOV-15:02 | 14.13 | 6.69 | 91359674.19 | 56.69 | 07-NOV-22:49 | 12.80 | 11.46 |
December | 7580526.24 | 2865.73 | 02-DEC-16:02 | 4.95 | 2.78 | 93118877.83 | 56.69 | 13-DEC-05:00 | -10.6 | -10.9 |
Annual Sum or Average | 0.801954E+10 | 0.113251E+10 | ||||||||
Minimum of Months | 4425394.85 | 2865.73 | 2.62 | 1.03 | 83871538.92 | 56.69 | -16.4 | -16.8 | ||
Maximum of Months | 0.181969E+10 | 3426.45 | 30.87 | 22.39 | 98866012.08 | 56.70 | 24.40 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 370913.37 | 451.35 | 13-JAN-19:05 | 0.40 | -0.5 | 92268486.12 | 56.69 | 23-JAN-23:10 | -16.3 | -16.9 |
February | 11989282.30 | 2899.34 | 24-FEB-16:02 | 8.12 | 5.75 | 82733907.64 | 56.69 | 28-FEB-02:20 | -16.1 | -16.6 |
March | 63308076.75 | 3115.06 | 25-MAR-15:01 | 18.72 | 10.43 | 94288503.37 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.433900E+09 | 3312.05 | 15-APR-15:02 | 30.00 | 19.17 | 92914774.02 | 56.69 | 15-APR-23:00 | 20.00 | 16.36 |
May | 0.822178E+09 | 3299.59 | 05-MAY-15:02 | 26.78 | 16.88 | 98023602.64 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.144718E+10 | 3341.44 | 18-JUN-15:02 | 30.87 | 22.39 | 95400662.66 | 56.70 | 26-JUN-21:00 | 24.40 | 20.94 |
July | 0.174490E+10 | 3348.84 | 05-JUL-18:02 | 26.52 | 21.26 | 98813243.14 | 56.70 | 03-JUL-21:40 | 23.67 | 22.66 |
August | 0.148780E+10 | 3328.96 | 05-AUG-15:02 | 26.60 | 18.95 | 98816884.98 | 56.70 | 03-AUG-21:10 | 24.32 | 23.15 |
September | 0.866546E+09 | 3270.77 | 16-SEP-15:02 | 28.90 | 18.27 | 94534817.59 | 56.69 | 09-SEP-00:20 | 18.87 | 15.39 |
October | 0.163765E+09 | 3124.79 | 19-OCT-15:01 | 18.53 | 10.63 | 95584954.54 | 56.69 | 20-OCT-21:19 | 13.90 | 9.46 |
November | 30939933.42 | 2980.67 | 04-NOV-15:02 | 14.13 | 6.69 | 90622300.12 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 747812.38 | 495.72 | 14-DEC-16:04 | 0.92 | -0.3 | 92415888.93 | 56.69 | 28-DEC-04:40 | -17.0 | -17.3 |
Annual Sum or Average | 0.707362E+10 | 0.112642E+10 | ||||||||
Minimum of Months | 370913.37 | 451.35 | 0.40 | -0.5 | 82733907.64 | 56.69 | -17.0 | -17.3 | ||
Maximum of Months | 0.174490E+10 | 3348.84 | 30.87 | 22.39 | 98816884.98 | 56.70 | 24.40 | 23.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4231195.93 | 219.88 | 30-JAN-15:05 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 9703249.48 | 259.71 | 02-FEB-15:03 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 58074785.20 | 434.45 | 24-MAR-13:00 | 12.20 | 6.44 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.149669E+09 | 545.39 | 15-APR-12:50 | 28.22 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.287538E+09 | 346.18 | 05-MAY-13:05 | 23.68 | 18.13 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.409928E+09 | 368.35 | 26-JUN-17:30 | 30.55 | 21.97 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.497313E+09 | 370.31 | 30-JUL-13:05 | 26.78 | 20.35 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.517860E+09 | 480.25 | 29-AUG-13:20 | 23.50 | 16.48 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.446034E+09 | 632.74 | 07-SEP-12:50 | 31.52 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.268678E+09 | 701.47 | 20-OCT-12:30 | 21.45 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 88226442.07 | 684.21 | 04-NOV-12:30 | 13.35 | 6.67 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 6536639.31 | 140.08 | 07-DEC-15:20 | -3.9 | -7.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.274379E+10 | 0.00 | ||||||||
Minimum of Months | 4231195.93 | 140.08 | -28.9 | -29.2 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.517860E+09 | 701.47 | 31.52 | 21.97 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7564014.80 | 577.60 | 01-JAN-09:02 | -3.2 | -3.4 | 93052662.70 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 23626753.91 | 833.67 | 25-FEB-09:02 | 0.78 | -0.3 | 83373595.96 | 56.69 | 22-FEB-22:10 | 1.20 | 0.67 |
March | 0.115280E+09 | 920.59 | 25-MAR-15:01 | 18.72 | 10.43 | 95726642.11 | 56.69 | 29-MAR-21:10 | 7.70 | 7.14 |
April | 0.279871E+09 | 1027.46 | 15-APR-18:02 | 27.85 | 18.46 | 93597646.86 | 56.69 | 17-APR-00:10 | 13.80 | 12.79 |
May | 0.533429E+09 | 1019.52 | 31-MAY-18:02 | 27.02 | 18.99 | 98057457.71 | 56.69 | 31-MAY-21:19 | 21.40 | 16.39 |
June | 0.708613E+09 | 1025.60 | 26-JUN-18:02 | 29.72 | 22.35 | 95400892.77 | 56.69 | 29-JUN-21:49 | 23.48 | 18.85 |
July | 0.774450E+09 | 1014.04 | 02-JUL-18:02 | 28.12 | 21.01 | 98603322.22 | 56.69 | 03-JUL-21:40 | 23.67 | 22.66 |
August | 0.712804E+09 | 1025.48 | 09-AUG-18:02 | 25.13 | 17.32 | 98611072.80 | 56.69 | 03-AUG-21:30 | 24.15 | 22.94 |
September | 0.508438E+09 | 1017.86 | 07-SEP-18:02 | 28.95 | 19.10 | 94757761.41 | 56.69 | 11-SEP-21:10 | 19.40 | 17.91 |
October | 0.251195E+09 | 909.07 | 19-OCT-15:01 | 18.53 | 10.63 | 96689348.33 | 56.69 | 02-OCT-21:40 | 11.43 | 10.03 |
November | 0.111745E+09 | 864.25 | 04-NOV-18:01 | 5.50 | 2.13 | 92221915.02 | 56.69 | 08-NOV-22:19 | 14.40 | 12.79 |
December | 10128148.88 | 654.98 | 03-DEC-09:02 | -1.5 | -1.7 | 93882816.80 | 56.69 | 04-DEC-22:10 | 1.78 | 0.08 |
Annual Sum or Average | 0.403714E+10 | 0.113398E+10 | ||||||||
Minimum of Months | 7564014.80 | 577.60 | -3.2 | -3.4 | 83373595.96 | 56.69 | 1.20 | 0.08 | ||
Maximum of Months | 0.774450E+09 | 1027.46 | 29.72 | 22.35 | 98611072.80 | 56.69 | 24.15 | 22.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3822554.85 | 746.02 | 12-JAN-09:03 | -4.1 | -4.6 | 92573309.74 | 56.69 | 31-JAN-23:00 | -23.9 | -24.2 |
February | 25241979.05 | 2660.93 | 24-FEB-09:02 | 3.07 | 0.60 | 83441428.68 | 56.69 | 28-FEB-00:00 | -15.6 | -16.1 |
March | 0.119116E+09 | 2853.70 | 25-MAR-15:01 | 18.72 | 10.43 | 95363133.31 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.454869E+09 | 3022.31 | 16-APR-15:02 | 28.40 | 20.32 | 93492395.25 | 56.69 | 15-APR-23:00 | 20.00 | 16.36 |
May | 0.951019E+09 | 2994.76 | 31-MAY-18:02 | 27.02 | 18.99 | 98602403.76 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.150144E+10 | 3051.99 | 27-JUN-15:02 | 30.50 | 21.67 | 95631460.69 | 56.70 | 26-JUN-22:10 | 24.32 | 20.87 |
July | 0.175665E+10 | 3035.22 | 29-JUL-15:02 | 28.12 | 19.76 | 99003461.14 | 56.70 | 14-JUL-21:10 | 22.70 | 20.22 |
August | 0.155204E+10 | 2994.22 | 18-AUG-15:02 | 25.60 | 18.05 | 99073880.50 | 56.69 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.108313E+10 | 3000.43 | 07-SEP-18:02 | 28.95 | 19.10 | 95167477.41 | 56.69 | 07-SEP-21:19 | 22.07 | 16.31 |
October | 0.273807E+09 | 2887.38 | 19-OCT-15:01 | 18.53 | 10.63 | 96890362.77 | 56.69 | 20-OCT-22:10 | 13.90 | 9.55 |
November | 64480279.38 | 2764.22 | 04-NOV-15:02 | 14.13 | 6.69 | 91334633.20 | 56.69 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 9560464.99 | 2328.39 | 03-DEC-09:02 | -1.5 | -1.7 | 93041747.68 | 56.69 | 22-DEC-05:00 | -14.4 | -14.6 |
Annual Sum or Average | 0.779518E+10 | 0.113362E+10 | ||||||||
Minimum of Months | 3822554.85 | 746.02 | -4.1 | -4.6 | 83441428.68 | 56.69 | -23.9 | -24.2 | ||
Maximum of Months | 0.175665E+10 | 3051.99 | 30.50 | 21.67 | 99073880.50 | 56.70 | 24.32 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 587349.15 | 455.23 | 13-JAN-09:05 | -0.5 | -1.5 | 92107360.78 | 56.69 | 15-JAN-04:10 | -15.1 | -15.8 |
February | 6889974.64 | 2537.62 | 24-FEB-09:02 | 3.07 | 0.60 | 82168769.78 | 56.69 | 01-FEB-00:20 | -24.4 | -24.6 |
March | 59542477.53 | 2691.86 | 28-MAR-08:62 | 5.37 | 3.26 | 94438158.40 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.353271E+09 | 2962.29 | 15-APR-18:02 | 27.85 | 18.46 | 93002416.87 | 56.69 | 17-APR-21:10 | 13.80 | 9.26 |
May | 0.872642E+09 | 3010.11 | 31-MAY-15:02 | 29.72 | 19.53 | 98495948.42 | 56.69 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.145664E+10 | 3026.10 | 28-JUN-15:02 | 28.90 | 20.31 | 95611513.89 | 56.70 | 26-JUN-21:49 | 24.60 | 21.01 |
July | 0.168020E+10 | 2992.66 | 02-JUL-18:02 | 28.12 | 21.01 | 98993903.88 | 56.70 | 19-JUL-21:10 | 22.62 | 20.36 |
August | 0.140784E+10 | 3008.35 | 09-AUG-15:02 | 27.20 | 17.24 | 99047090.20 | 56.69 | 03-AUG-02:00 | 23.90 | 22.63 |
September | 0.852288E+09 | 3013.85 | 08-SEP-15:02 | 29.90 | 18.97 | 94909249.72 | 56.69 | 10-SEP-23:40 | 22.40 | 17.18 |
October | 0.115010E+09 | 2674.06 | 21-OCT-15:01 | 20.67 | 14.26 | 95703507.58 | 56.69 | 20-OCT-21:49 | 13.90 | 9.51 |
November | 18194748.33 | 2158.45 | 04-NOV-08:62 | 2.77 | 0.70 | 90581481.23 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 740479.63 | 514.83 | 05-DEC-09:03 | -6.6 | -8.4 | 92394322.23 | 56.69 | 16-DEC-05:10 | -14.4 | -14.8 |
Annual Sum or Average | 0.682385E+10 | 0.112745E+10 | ||||||||
Minimum of Months | 587349.15 | 455.23 | -6.6 | -8.4 | 82168769.78 | 56.69 | -24.4 | -24.6 | ||
Maximum of Months | 0.168020E+10 | 3026.10 | 29.90 | 21.01 | 99047090.20 | 56.70 | 24.60 | 22.63 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366007E+09 | 1374.54 | 31-JAN-04:00 | -31.1 | -31.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.494632E+09 | 1741.08 | 02-FEB-06:10 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.840513E+09 | 1519.16 | 25-MAR-15:00 | 18.90 | 10.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.170757E+10 | 1753.29 | 18-APR-18:50 | 21.15 | 16.17 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.302332E+10 | 1756.05 | 31-MAY-19:20 | 25.53 | 18.52 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.368449E+10 | 1844.47 | 30-JUN-19:20 | 25.17 | 19.00 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.420614E+10 | 1832.68 | 03-JUL-19:20 | 27.77 | 24.08 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.408402E+10 | 1786.58 | 04-AUG-15:13 | 33.90 | 25.65 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.315576E+10 | 1813.17 | 08-SEP-14:00 | 30.60 | 19.31 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.177710E+10 | 1703.67 | 20-OCT-14:40 | 23.07 | 13.23 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.679335E+09 | 1426.43 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.133309E+09 | 1091.55 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.241522E+11 | 0.00 | ||||||||
Minimum of Months | 0.133309E+09 | 1091.55 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.420614E+10 | 1844.47 | 33.90 | 25.65 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2828637.51 | 2969.41 | 12-JAN-16:02 | 2.62 | 1.03 | 92445067.83 | 56.69 | 31-JAN-00:30 | -29.4 | -29.6 |
February | 33375987.19 | 3172.49 | 24-FEB-16:02 | 8.12 | 5.75 | 83657991.44 | 56.69 | 01-FEB-22:19 | -31.0 | -31.1 |
March | 0.113189E+09 | 3297.37 | 25-MAR-15:01 | 18.72 | 10.43 | 94723769.12 | 56.69 | 19-MAR-23:40 | 13.67 | 11.25 |
April | 0.589115E+09 | 3384.17 | 16-APR-18:02 | 26.42 | 19.76 | 93155520.81 | 56.69 | 17-APR-21:30 | 13.60 | 9.35 |
May | 0.100311E+10 | 3392.64 | 30-MAY-18:02 | 25.40 | 19.83 | 98258963.75 | 56.70 | 27-MAY-03:00 | 13.90 | 13.61 |
June | 0.171953E+10 | 3576.68 | 25-JUN-18:02 | 30.82 | 21.74 | 95465750.04 | 56.70 | 29-JUN-22:10 | 23.30 | 18.79 |
July | 0.210437E+10 | 3527.48 | 02-JUL-18:02 | 28.12 | 21.01 | 98857719.85 | 56.70 | 12-JUL-21:10 | 20.73 | 16.71 |
August | 0.185554E+10 | 3400.06 | 22-AUG-18:02 | 26.73 | 21.31 | 98873014.69 | 56.70 | 02-AUG-21:19 | 24.23 | 21.62 |
September | 0.119565E+10 | 3379.66 | 11-SEP-18:02 | 25.92 | 18.96 | 94793710.47 | 56.70 | 05-SEP-02:30 | 8.05 | 7.37 |
October | 0.304149E+09 | 3340.65 | 19-OCT-15:01 | 18.53 | 10.63 | 96410964.17 | 56.69 | 20-OCT-21:40 | 13.90 | 9.50 |
November | 61749480.52 | 3225.04 | 04-NOV-15:02 | 14.13 | 6.69 | 90943722.81 | 56.69 | 07-NOV-22:10 | 12.80 | 11.46 |
December | 5420937.45 | 2919.62 | 02-DEC-16:02 | 4.95 | 2.78 | 92773374.36 | 56.69 | 10-DEC-02:00 | -21.1 | -21.5 |
Annual Sum or Average | 0.898801E+10 | 0.113036E+10 | ||||||||
Minimum of Months | 2828637.51 | 2919.62 | 2.62 | 1.03 | 83657991.44 | 56.69 | -31.0 | -31.1 | ||
Maximum of Months | 0.210437E+10 | 3576.68 | 30.82 | 21.74 | 98873014.69 | 56.70 | 24.23 | 21.62 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 122484.48 | 718.64 | 12-JAN-16:03 | 2.62 | 1.03 | 92087865.35 | 56.69 | 10-JAN-03:09 | -13.1 | -13.3 |
February | 8384770.01 | 2916.82 | 24-FEB-16:02 | 8.12 | 5.75 | 82537819.23 | 56.69 | 18-FEB-01:19 | -15.2 | -15.6 |
March | 51051524.98 | 3212.37 | 25-MAR-15:01 | 18.72 | 10.43 | 93902656.03 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.468743E+09 | 3333.75 | 18-APR-15:02 | 27.75 | 20.45 | 92697516.71 | 56.70 | 13-APR-22:30 | 12.20 | 10.17 |
May | 0.921144E+09 | 3366.07 | 04-MAY-15:02 | 25.00 | 17.66 | 98127135.98 | 56.70 | 31-MAY-21:19 | 21.40 | 16.39 |
June | 0.167293E+10 | 3525.53 | 25-JUN-18:02 | 30.82 | 21.74 | 95450211.60 | 56.70 | 29-JUN-22:10 | 23.30 | 18.79 |
July | 0.202364E+10 | 3478.04 | 26-JUL-15:02 | 30.00 | 25.72 | 98854220.38 | 56.70 | 27-JUL-21:10 | 20.92 | 17.78 |
August | 0.170325E+10 | 3438.30 | 13-AUG-15:02 | 26.02 | 20.37 | 98850570.07 | 56.70 | 22-AUG-21:10 | 22.02 | 19.96 |
September | 0.958500E+09 | 3402.94 | 11-SEP-15:02 | 28.22 | 20.07 | 94473000.80 | 56.70 | 24-SEP-02:20 | 14.80 | 12.10 |
October | 0.146917E+09 | 3227.40 | 19-OCT-15:01 | 18.53 | 10.63 | 95178765.52 | 56.69 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 23155640.05 | 3072.44 | 04-NOV-15:02 | 14.13 | 6.69 | 90269562.77 | 56.69 | 24-NOV-03:09 | -14.1 | -14.4 |
December | 188840.72 | 638.04 | 03-DEC-16:04 | 3.03 | 0.60 | 92261408.13 | 56.69 | 07-DEC-02:09 | -11.2 | -12.4 |
Annual Sum or Average | 0.797803E+10 | 0.112469E+10 | ||||||||
Minimum of Months | 122484.48 | 638.04 | 2.62 | 0.60 | 82537819.23 | 56.69 | -15.2 | -15.6 | ||
Maximum of Months | 0.202364E+10 | 3525.53 | 30.82 | 25.72 | 98854220.38 | 56.70 | 23.30 | 19.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69976253.26 | 1607.21 | 30-JAN-16:02 | -24.5 | -24.8 | 94396362.26 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.118446E+09 | 1541.24 | 01-FEB-16:02 | -26.2 | -26.5 | 85815435.46 | 56.69 | 08-FEB-22:19 | -0.2 | -1.0 |
March | 0.199918E+09 | 1474.23 | 24-MAR-15:01 | 12.43 | 6.31 | 96351334.27 | 56.69 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.387134E+09 | 1594.09 | 15-APR-15:02 | 30.00 | 19.17 | 93699827.09 | 56.69 | 16-APR-23:10 | 17.32 | 14.61 |
May | 0.616541E+09 | 1556.16 | 31-MAY-18:02 | 27.02 | 18.99 | 98415346.84 | 56.69 | 05-MAY-21:30 | 15.00 | 10.58 |
June | 0.915032E+09 | 1585.69 | 10-JUN-15:02 | 26.78 | 20.53 | 95542939.08 | 56.70 | 28-JUN-21:10 | 22.85 | 17.35 |
July | 0.109624E+10 | 1576.66 | 17-JUL-15:02 | 26.52 | 23.02 | 98826908.60 | 56.70 | 19-JUL-21:10 | 22.62 | 20.36 |
August | 0.109142E+10 | 1601.53 | 22-AUG-15:02 | 30.00 | 22.35 | 98881983.24 | 56.69 | 28-AUG-22:00 | 21.70 | 20.86 |
September | 0.895871E+09 | 1598.57 | 06-SEP-15:02 | 32.02 | 20.85 | 95183396.14 | 56.70 | 07-SEP-21:49 | 20.97 | 16.08 |
October | 0.517658E+09 | 1538.85 | 19-OCT-15:01 | 18.53 | 10.63 | 97694363.60 | 56.69 | 20-OCT-22:10 | 13.90 | 9.55 |
November | 0.193722E+09 | 1500.68 | 04-NOV-15:02 | 14.13 | 6.69 | 92765929.99 | 56.69 | 07-NOV-22:10 | 12.80 | 11.46 |
December | 0.123249E+09 | 1451.70 | 05-DEC-16:01 | -5.1 | -8.0 | 94690506.00 | 56.69 | 25-DEC-03:20 | -9.8 | -10.4 |
Annual Sum or Average | 0.622520E+10 | 0.114226E+10 | ||||||||
Minimum of Months | 69976253.26 | 1451.70 | -26.2 | -26.5 | 85815435.46 | 56.69 | -9.8 | -10.4 | ||
Maximum of Months | 0.109624E+10 | 1607.21 | 32.02 | 23.02 | 98881983.24 | 56.70 | 22.85 | 20.86 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291688E+11 | 33689.24 | 19-JAN-01:51 | -23.9 | -24.0 | 0.167277E+11 | 11347.84 | 02-JAN-00:20 | -3.0 | -3.3 |
February | 0.276740E+11 | 21879.03 | 02-FEB-06:00 | -36.7 | -36.8 | 0.149533E+11 | 11347.88 | 21-FEB-00:20 | -4.1 | -5.8 |
March | 0.319136E+11 | 18133.38 | 28-MAR-22:00 | 8.90 | 7.21 | 0.187821E+11 | 11348.03 | 27-MAR-00:20 | 2.60 | 1.08 |
April | 0.339264E+11 | 19908.24 | 18-APR-21:10 | 16.32 | 13.38 | 0.183165E+11 | 11348.10 | 10-APR-00:20 | 6.87 | 4.45 |
May | 0.388407E+11 | 21109.85 | 31-MAY-21:10 | 21.80 | 16.81 | 0.189986E+11 | 11348.06 | 22-MAY-00:20 | 7.57 | 4.33 |
June | 0.404353E+11 | 21992.70 | 26-JUN-21:10 | 25.40 | 21.25 | 0.184377E+11 | 11348.09 | 01-JUN-23:19 | 9.40 | 8.92 |
July | 0.426630E+11 | 21746.44 | 03-JUL-21:10 | 24.22 | 22.81 | 0.189414E+11 | 11347.87 | 24-JUL-00:20 | 12.57 | 11.44 |
August | 0.419500E+11 | 21375.33 | 03-AUG-22:00 | 23.90 | 22.63 | 0.189725E+11 | 11348.02 | 07-AUG-00:20 | 9.40 | 8.21 |
September | 0.375697E+11 | 20967.88 | 07-SEP-21:10 | 22.43 | 16.37 | 0.183239E+11 | 11348.09 | 25-SEP-00:20 | 6.83 | 3.77 |
October | 0.343622E+11 | 18552.39 | 20-OCT-22:00 | 13.90 | 9.53 | 0.189026E+11 | 11348.07 | 23-OCT-00:20 | 0.87 | -0.5 |
November | 0.306274E+11 | 24001.80 | 25-NOV-21:12 | -23.7 | -24.1 | 0.177444E+11 | 11347.89 | 04-NOV-23:19 | 3.30 | 1.68 |
December | 0.285293E+11 | 15994.65 | 04-DEC-23:00 | 2.20 | 0.30 | 0.180682E+11 | 11347.91 | 05-DEC-04:19 | 2.23 | 0.71 |
Annual Sum or Average | 0.417660E+12 | 0.217169E+12 | ||||||||
Minimum of Months | 0.276740E+11 | 15994.65 | -36.7 | -36.8 | 0.149533E+11 | 11347.84 | -4.1 | -5.8 | ||
Maximum of Months | 0.426630E+11 | 33689.24 | 25.40 | 22.81 | 0.189986E+11 | 11348.10 | 12.57 | 11.44 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321906E+11 | 35707.00 | 19-JAN-01:51 | -23.9 | -24.0 | 0.170794E+11 | 11347.94 | 17-JAN-00:20 | -3.7 | -3.8 |
February | 0.306898E+11 | 22816.89 | 02-FEB-06:00 | -36.7 | -36.8 | 0.151890E+11 | 11347.95 | 13-FEB-00:20 | -6.7 | -7.1 |
March | 0.356096E+11 | 20141.91 | 28-MAR-21:10 | 9.82 | 7.62 | 0.190288E+11 | 11348.06 | 27-MAR-00:20 | 2.60 | 1.08 |
April | 0.376127E+11 | 21621.39 | 18-APR-21:10 | 16.32 | 13.38 | 0.184836E+11 | 11348.12 | 10-APR-00:20 | 6.87 | 4.45 |
May | 0.426370E+11 | 22748.56 | 31-MAY-21:10 | 21.80 | 16.81 | 0.191377E+11 | 11348.10 | 22-MAY-00:20 | 7.57 | 4.33 |
June | 0.438276E+11 | 23472.80 | 26-JUN-21:10 | 25.40 | 21.25 | 0.185465E+11 | 11348.14 | 01-JUN-23:19 | 9.40 | 8.92 |
July | 0.460118E+11 | 23161.07 | 03-JUL-21:10 | 24.22 | 22.81 | 0.190490E+11 | 11347.89 | 24-JUL-00:20 | 12.57 | 11.44 |
August | 0.453373E+11 | 22913.64 | 03-AUG-21:10 | 24.32 | 23.15 | 0.190929E+11 | 11348.05 | 07-AUG-00:20 | 9.40 | 8.21 |
September | 0.410262E+11 | 22489.32 | 07-SEP-21:10 | 22.43 | 16.37 | 0.184551E+11 | 11348.13 | 25-SEP-00:20 | 6.83 | 3.77 |
October | 0.381914E+11 | 20449.19 | 02-OCT-22:00 | 11.30 | 9.84 | 0.190765E+11 | 11348.11 | 23-OCT-00:20 | 0.87 | -0.5 |
November | 0.340403E+11 | 25698.10 | 25-NOV-21:12 | -23.7 | -24.1 | 0.180013E+11 | 11347.95 | 13-NOV-00:20 | -2.6 | -4.3 |
December | 0.317400E+11 | 18008.19 | 04-DEC-23:00 | 2.20 | 0.30 | 0.184602E+11 | 11347.97 | 26-DEC-00:20 | -6.5 | -7.1 |
Annual Sum or Average | 0.458914E+12 | 0.219600E+12 | ||||||||
Minimum of Months | 0.306898E+11 | 18008.19 | -36.7 | -36.8 | 0.151890E+11 | 11347.89 | -6.7 | -7.1 | ||
Maximum of Months | 0.460118E+11 | 35707.00 | 25.40 | 23.15 | 0.191377E+11 | 11348.14 | 12.57 | 11.44 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465621E+11 | 28344.71 | 29-JAN-19:33 | -23.7 | -23.9 | 0.186291E+11 | 11336.65 | 14-JAN-18:00 | -9.4 | -10.4 |
February | 0.436034E+11 | 26011.20 | 24-FEB-11:50 | 6.02 | 3.02 | 0.168041E+11 | 11361.20 | 25-FEB-18:00 | 1.70 | 0.04 |
March | 0.503564E+11 | 27768.86 | 19-MAR-10:50 | 14.13 | 10.20 | 0.188059E+11 | 11372.25 | 18-MAR-17:00 | 8.90 | 7.46 |
April | 0.510624E+11 | 29927.92 | 18-APR-10:40 | 26.33 | 20.74 | 0.182083E+11 | 11374.65 | 22-APR-17:00 | 3.90 | 1.51 |
May | 0.557035E+11 | 30172.21 | 29-MAY-10:40 | 24.63 | 18.65 | 0.188134E+11 | 11361.49 | 13-MAY-17:00 | 12.20 | 10.89 |
June | 0.557960E+11 | 30553.76 | 11-JUN-10:40 | 29.67 | 22.03 | 0.181867E+11 | 11336.17 | 03-JUN-17:00 | 14.40 | 10.98 |
July | 0.582675E+11 | 30586.11 | 29-JUL-10:40 | 25.93 | 19.87 | 0.187723E+11 | 11319.66 | 22-JUL-17:19 | 19.80 | 14.29 |
August | 0.576160E+11 | 30137.00 | 27-AUG-10:40 | 25.53 | 19.85 | 0.187883E+11 | 11319.65 | 05-AUG-17:19 | 25.03 | 17.78 |
September | 0.538559E+11 | 30338.39 | 08-SEP-10:40 | 28.33 | 18.76 | 0.181967E+11 | 11376.05 | 30-SEP-17:00 | 6.10 | 1.60 |
October | 0.522996E+11 | 28491.62 | 20-OCT-10:50 | 17.62 | 11.23 | 0.188191E+11 | 11369.65 | 28-OCT-17:00 | 7.20 | 3.19 |
November | 0.478785E+11 | 27989.70 | 25-NOV-21:12 | -23.7 | -24.1 | 0.181662E+11 | 11373.31 | 04-NOV-17:49 | 5.97 | 2.43 |
December | 0.469430E+11 | 25764.66 | 03-DEC-11:50 | 4.90 | 2.33 | 0.187709E+11 | 11353.95 | 02-DEC-18:00 | 1.10 | 0.61 |
Annual Sum or Average | 0.619944E+12 | 0.220961E+12 | ||||||||
Minimum of Months | 0.436034E+11 | 25764.66 | -23.7 | -24.1 | 0.168041E+11 | 11319.65 | -9.4 | -10.4 | ||
Maximum of Months | 0.582675E+11 | 30586.11 | 29.67 | 22.03 | 0.188191E+11 | 11376.05 | 25.03 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192840E+09 | 2195.87 | 12-JAN-12:50 | 2.12 | 0.46 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.630670E+09 | 2456.08 | 24-FEB-14:20 | 7.97 | 5.31 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.236659E+10 | 3240.95 | 19-MAR-14:00 | 18.30 | 13.67 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.449813E+10 | 3911.45 | 18-APR-13:50 | 28.12 | 20.64 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.743992E+10 | 4029.42 | 31-MAY-18:02 | 27.02 | 18.99 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.869249E+10 | 4313.93 | 30-JUN-15:15 | 29.23 | 21.32 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.965682E+10 | 4271.30 | 03-JUL-18:20 | 29.03 | 24.12 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.928126E+10 | 4281.98 | 04-AUG-15:50 | 33.90 | 26.15 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.737704E+10 | 4298.77 | 07-SEP-13:50 | 32.12 | 18.31 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.469826E+10 | 3700.02 | 20-OCT-13:50 | 22.47 | 12.93 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.200649E+10 | 3136.60 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.402608E+09 | 2343.62 | 03-DEC-13:20 | 5.60 | 2.34 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.572431E+11 | 0.00 | ||||||||
Minimum of Months | 0.192840E+09 | 2195.87 | 2.12 | 0.46 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.965682E+10 | 4313.93 | 33.90 | 26.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1276856.70 | 1677.99 | 31-JAN-11:42 | -23.1 |
February | 0.407790E+09 | 8526.12 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.409067E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.407790E+09 | 8526.12 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241739E+10 | 2939.31 | 20-JAN-07:51 | -23.3 |
February | 0.120713E+10 | 2756.26 | 04-FEB-11:21 | -23.0 |
March | 0.649481E+09 | 1516.97 | 06-MAR-04:50 | -15.7 |
April | 0.229704E+09 | 1083.23 | 03-APR-06:05 | -7.1 |
May | 14563.63 | 22.79 | 02-MAY-06:10 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8152154.36 | 380.38 | 30-SEP-06:30 | 0.60 |
October | 29794943.68 | 495.55 | 23-OCT-06:05 | -3.0 |
November | 0.849343E+09 | 2794.05 | 26-NOV-08:51 | -23.3 |
December | 0.205819E+10 | 2359.45 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.744921E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.241739E+10 | 2939.31 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43109975.39 | 1022.02 | 31-JAN-11:42 | -23.1 |
February | 65830350.95 | 1405.69 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 6942283.95 | 671.05 | 26-NOV-09:02 | -22.7 |
December | 1399.17 | 2.33 | 12-DEC-14:50 | -15.7 |
Annual Sum or Average | 0.115884E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 65830350.95 | 1405.69 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867704E+09 | 1454.39 | 31-JAN-11:42 | -23.1 |
February | 0.492987E+09 | 1865.21 | 04-FEB-11:21 | -23.0 |
March | 84828014.26 | 514.84 | 06-MAR-05:00 | -15.6 |
April | 6631575.48 | 177.74 | 03-APR-04:00 | -6.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.184404E+09 | 1186.57 | 26-NOV-09:02 | -22.7 |
December | 0.420930E+09 | 917.79 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.205748E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.867704E+09 | 1865.21 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108713E+10 | 974.34 | 31-JAN-11:42 | -23.1 |
February | 0.624463E+09 | 1199.23 | 04-FEB-11:21 | -23.0 |
March | 0.268819E+09 | 555.95 | 06-MAR-05:00 | -15.6 |
April | 52167424.91 | 293.47 | 03-APR-04:00 | -6.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.310050E+09 | 825.87 | 26-NOV-09:02 | -22.7 |
December | 0.764173E+09 | 716.71 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.310681E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.108713E+10 | 1199.23 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 338519.64 | 3130.29 | 06-JAN-10:41 | -23.2 |
February | 323469.80 | 3024.65 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 156643.55 | 2610.73 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 818633.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 338519.64 | 3130.29 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509918E+09 | 6989.79 | 20-JAN-07:51 | -23.3 |
February | 0.116200E+09 | 6306.40 | 04-FEB-11:21 | -23.0 |
March | 14698417.56 | 618.85 | 01-MAR-15:00 | -3.9 |
April | 995827.42 | 349.76 | 03-APR-08:03 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.109400E+09 | 6799.01 | 26-NOV-08:51 | -23.3 |
December | 0.543871E+09 | 3918.07 | 09-DEC-17:00 | -19.4 |
Annual Sum or Average | 0.129508E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.543871E+09 | 6989.79 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273928E+09 | 17683.92 | 31-JAN-11:42 | -23.1 |
February | 0.586532E+09 | 24507.37 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 30714572.07 | 12278.58 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.891174E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.586532E+09 | 24507.37 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206905E+10 | 2071.51 | 18-JAN-16:12 | -18.0 |
February | 0.136682E+10 | 2184.82 | 02-FEB-08:05 | -36.5 |
March | 0.732277E+09 | 2004.91 | 13-MAR-08:62 | -7.7 |
April | 0.292351E+09 | 1995.70 | 03-APR-08:62 | -5.9 |
May | 21528544.89 | 1507.10 | 02-MAY-08:62 | 4.08 |
June | 7572299.57 | 995.58 | 01-JUN-18:03 | 8.27 |
July | 1628987.39 | 1023.60 | 11-JUL-15:04 | 17.77 |
August | 1452814.40 | 920.56 | 06-AUG-08:04 | 12.80 |
September | 51730404.09 | 1833.79 | 30-SEP-08:62 | 3.35 |
October | 0.212861E+09 | 1871.82 | 23-OCT-08:62 | 0.70 |
November | 0.920134E+09 | 2049.32 | 26-NOV-16:13 | -13.9 |
December | 0.171342E+10 | 2085.21 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.739082E+10 | |||
Minimum of Months | 1452814.40 | 920.56 | -36.5 | |
Maximum of Months | 0.206905E+10 | 2184.82 | 17.77 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242816E+10 | 2082.49 | 19-JAN-16:02 | -22.9 |
February | 0.164533E+10 | 2285.12 | 02-FEB-11:03 | -31.6 |
March | 0.863957E+09 | 2009.88 | 06-MAR-09:02 | -9.5 |
April | 0.330728E+09 | 1990.36 | 03-APR-08:62 | -5.9 |
May | 26537274.54 | 1735.74 | 02-MAY-08:62 | 4.08 |
June | 8134563.88 | 970.11 | 09-JUN-08:04 | 21.97 |
July | 1617058.89 | 1022.46 | 11-JUL-15:04 | 17.77 |
August | 1605756.72 | 916.73 | 12-AUG-18:04 | 19.32 |
September | 65824595.78 | 1838.64 | 30-SEP-08:62 | 3.35 |
October | 0.313837E+09 | 1889.44 | 23-OCT-08:62 | 0.70 |
November | 0.109614E+10 | 2057.81 | 26-NOV-09:02 | -22.7 |
December | 0.198580E+10 | 2083.23 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.876767E+10 | |||
Minimum of Months | 1605756.72 | 916.73 | -31.6 | |
Maximum of Months | 0.242816E+10 | 2285.12 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76969793.22 | 262.05 | 19-JAN-06:00 | -27.8 |
February | 18997099.10 | 243.84 | 04-FEB-06:00 | -30.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 492527.47 | 67.06 | 28-NOV-05:00 | -21.7 |
December | 33629840.11 | 204.12 | 13-DEC-04:05 | -11.6 |
Annual Sum or Average | 0.130089E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 76969793.22 | 262.05 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397037E+09 | 594.27 | 31-JAN-16:01 | -20.1 |
February | 0.234674E+09 | 648.60 | 03-FEB-11:01 | -29.2 |
March | 67094615.93 | 562.82 | 05-MAR-16:02 | -9.6 |
April | 8709930.30 | 531.69 | 03-APR-15:02 | -3.2 |
May | 482167.45 | 308.81 | 01-MAY-08:05 | 7.80 |
June | 121143.40 | 159.07 | 16-JUN-08:05 | 17.98 |
July | 101383.80 | 210.84 | 23-JUL-15:07 | 22.80 |
August | 123724.11 | 277.89 | 17-AUG-08:05 | 18.77 |
September | 548549.26 | 433.73 | 23-SEP-18:04 | 16.83 |
October | 1897655.14 | 498.18 | 30-OCT-15:04 | 16.23 |
November | 0.111428E+09 | 585.08 | 25-NOV-16:02 | -18.1 |
December | 0.279053E+09 | 581.86 | 10-DEC-16:02 | -17.9 |
Annual Sum or Average | 0.110127E+10 | |||
Minimum of Months | 101383.80 | 159.07 | -29.2 | |
Maximum of Months | 0.397037E+09 | 648.60 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205666E+10 | 1993.87 | 19-JAN-16:02 | -22.9 |
February | 0.137380E+10 | 2139.80 | 04-FEB-08:04 | -30.3 |
March | 0.714333E+09 | 1925.19 | 05-MAR-19:02 | -14.0 |
April | 0.317467E+09 | 1913.40 | 03-APR-08:62 | -5.9 |
May | 17869517.09 | 1293.24 | 09-MAY-15:04 | 17.62 |
June | 5187450.62 | 1055.90 | 04-JUN-18:04 | 13.22 |
July | 783638.83 | 958.16 | 10-JUL-15:04 | 18.30 |
August | 1097365.14 | 997.37 | 06-AUG-08:04 | 12.80 |
September | 46163860.97 | 1092.62 | 13-SEP-15:04 | 19.22 |
October | 0.213085E+09 | 1788.87 | 26-OCT-08:62 | 1.28 |
November | 0.924954E+09 | 1966.33 | 26-NOV-16:13 | -13.9 |
December | 0.171745E+10 | 2001.65 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.738884E+10 | |||
Minimum of Months | 783638.83 | 958.16 | -30.3 | |
Maximum of Months | 0.205666E+10 | 2139.80 | 19.22 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241523E+10 | 2022.66 | 31-JAN-16:01 | -20.1 |
February | 0.166125E+10 | 2199.73 | 03-FEB-18:02 | -27.8 |
March | 0.846735E+09 | 1941.17 | 05-MAR-19:02 | -14.0 |
April | 0.362210E+09 | 1914.00 | 03-APR-08:62 | -5.9 |
May | 22434581.32 | 1276.53 | 09-MAY-15:04 | 17.62 |
June | 5854981.84 | 997.39 | 04-JUN-18:04 | 13.22 |
July | 926918.66 | 1046.46 | 10-JUL-15:04 | 18.30 |
August | 1644520.07 | 960.46 | 06-AUG-08:04 | 12.80 |
September | 56965768.32 | 1111.87 | 24-SEP-18:03 | 11.52 |
October | 0.307467E+09 | 1798.70 | 26-OCT-08:62 | 1.28 |
November | 0.109985E+10 | 1984.50 | 25-NOV-16:02 | -18.1 |
December | 0.199631E+10 | 2006.59 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.877688E+10 | |||
Minimum of Months | 926918.66 | 960.46 | -27.8 | |
Maximum of Months | 0.241523E+10 | 2199.73 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199395E+10 | 1847.33 | 31-JAN-11:42 | -23.1 |
February | 0.112539E+10 | 2358.44 | 04-FEB-11:21 | -23.0 |
March | 0.483551E+09 | 1180.81 | 06-MAR-05:00 | -15.6 |
April | 0.140157E+09 | 824.66 | 03-APR-04:00 | -6.7 |
May | 348849.72 | 67.00 | 02-MAY-04:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8997210.77 | 348.50 | 30-SEP-05:00 | 0.00 |
October | 41671046.04 | 399.69 | 27-OCT-04:00 | 0.00 |
November | 0.727173E+09 | 1691.15 | 26-NOV-09:02 | -22.7 |
December | 0.165288E+10 | 1463.24 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.617411E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.199395E+10 | 2358.44 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280968E+10 | 2413.46 | 18-JAN-16:12 | -18.0 |
February | 0.182279E+10 | 2390.98 | 03-FEB-08:04 | -33.7 |
March | 0.109210E+10 | 2314.67 | 06-MAR-09:02 | -9.5 |
April | 0.466673E+09 | 2297.32 | 03-APR-08:62 | -5.9 |
May | 44312778.69 | 2093.74 | 02-MAY-08:62 | 4.08 |
June | 15993978.56 | 1012.64 | 09-JUN-08:04 | 21.97 |
July | 1331180.66 | 911.25 | 13-JUL-08:04 | 21.38 |
August | 1248311.14 | 986.31 | 07-AUG-08:03 | 15.47 |
September | 98488616.14 | 2136.93 | 30-SEP-08:62 | 3.35 |
October | 0.385691E+09 | 2184.57 | 23-OCT-08:62 | 0.70 |
November | 0.133833E+10 | 2390.57 | 26-NOV-16:13 | -13.9 |
December | 0.238041E+10 | 2429.88 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.104571E+11 | |||
Minimum of Months | 1248311.14 | 911.25 | -33.7 | |
Maximum of Months | 0.280968E+10 | 2429.88 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322866E+10 | 2619.35 | 31-JAN-08:04 | -29.7 |
February | 0.216322E+10 | 2613.51 | 02-FEB-11:03 | -31.6 |
March | 0.127453E+10 | 2323.49 | 06-MAR-09:02 | -9.5 |
April | 0.520308E+09 | 2292.91 | 03-APR-08:62 | -5.9 |
May | 52749797.64 | 2096.55 | 02-MAY-08:62 | 4.08 |
June | 17215264.28 | 961.37 | 04-JUN-15:04 | 15.00 |
July | 1281184.90 | 960.70 | 28-JUL-08:04 | 22.48 |
August | 1372357.56 | 956.02 | 07-AUG-08:03 | 15.47 |
September | 0.121980E+09 | 2144.83 | 30-SEP-08:62 | 3.35 |
October | 0.531889E+09 | 2205.39 | 23-OCT-08:62 | 0.70 |
November | 0.156810E+10 | 2395.16 | 26-NOV-16:13 | -13.9 |
December | 0.272081E+10 | 2427.95 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.122021E+11 | |||
Minimum of Months | 1281184.90 | 956.02 | -31.6 | |
Maximum of Months | 0.322866E+10 | 2619.35 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.952062E+09 | 1150.35 | 18-JAN-16:12 | -18.0 |
February | 0.545048E+09 | 1130.26 | 28-FEB-19:02 | -15.7 |
March | 0.325330E+09 | 1119.78 | 13-MAR-08:62 | -7.7 |
April | 0.147827E+09 | 1112.04 | 03-APR-08:62 | -5.9 |
May | 5870527.50 | 375.57 | 20-MAY-18:05 | 15.22 |
June | 1249143.01 | 564.36 | 06-JUN-15:05 | 16.28 |
July | 292417.47 | 299.58 | 10-JUL-18:05 | 18.90 |
August | 664994.14 | 312.10 | 09-AUG-08:05 | 21.05 |
September | 14870243.77 | 692.02 | 29-SEP-08:62 | 5.05 |
October | 55283107.57 | 1032.21 | 26-OCT-08:62 | 1.28 |
November | 0.395065E+09 | 1139.91 | 26-NOV-16:13 | -13.9 |
December | 0.815128E+09 | 1164.19 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.325869E+10 | |||
Minimum of Months | 292417.47 | 299.58 | -19.1 | |
Maximum of Months | 0.952062E+09 | 1164.19 | 21.05 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18657444.07 | 5410.32 | 31-JAN-11:42 | -23.1 |
February | 47987339.54 | 7036.86 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 594526.51 | 2640.02 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 67239310.11 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 47987339.54 | 7036.86 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14259595.29 | 5464.36 | 31-JAN-11:42 | -23.1 |
February | 25806409.43 | 6856.27 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 507089.79 | 2471.80 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 40573094.52 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 25806409.43 | 6856.27 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483426E+10 | 5600.59 | 31-JAN-11:42 | -23.1 |
February | 0.260832E+10 | 7019.10 | 04-FEB-11:21 | -23.0 |
March | 0.904287E+09 | 3052.64 | 06-MAR-04:50 | -15.7 |
April | 0.169591E+09 | 1520.56 | 03-APR-05:00 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6481214.06 | 448.01 | 30-SEP-04:50 | -0.1 |
October | 30021065.22 | 542.26 | 27-OCT-04:00 | 0.00 |
November | 0.146307E+10 | 5129.47 | 26-NOV-09:02 | -22.7 |
December | 0.364650E+10 | 4295.09 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.136625E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.483426E+10 | 7019.10 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.120209E+11 | 11578.59 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.108538E+11 | 11578.59 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.120626E+11 | 11578.59 | 01-MAR-20:10 | 0.127894E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.116133E+11 | 11578.59 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.120417E+11 | 11578.59 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.116666E+11 | 11578.59 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.119885E+11 | 11578.59 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.120626E+11 | 11578.59 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.116133E+11 | 11578.59 | 01-SEP-19:10 | 0.123314E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.120209E+11 | 11578.59 | 02-OCT-19:10 | 0.127587E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.116573E+11 | 11578.59 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.119885E+11 | 11578.59 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.141590E+12 | 0.150259E+12 | ||||
Minimum of Months | 0.108538E+11 | 11578.59 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.120626E+11 | 11578.59 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.643545E+09 | 619.87 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.581063E+09 | 619.87 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.645777E+09 | 619.87 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.621726E+09 | 619.87 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.644661E+09 | 619.87 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.624577E+09 | 619.87 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.641810E+09 | 619.87 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.645777E+09 | 619.87 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.621726E+09 | 619.87 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.643545E+09 | 619.87 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.624081E+09 | 619.87 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.641810E+09 | 619.87 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.758010E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.581063E+09 | 619.87 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.645777E+09 | 619.87 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.745228E+09 | 717.81 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.672873E+09 | 717.81 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.747812E+09 | 717.81 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.719961E+09 | 717.81 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.746520E+09 | 717.81 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.723263E+09 | 717.81 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.743218E+09 | 717.81 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.747812E+09 | 717.81 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.719961E+09 | 717.81 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.745228E+09 | 717.81 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.722689E+09 | 717.81 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.743218E+09 | 717.81 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.877778E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.672873E+09 | 717.81 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.747812E+09 | 717.81 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577213E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641498E+09 | 615.76 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640390E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617606E+09 | 615.76 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639281E+09 | 615.76 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752987E+10 | 0.124715E+11 | ||||
Minimum of Months | 0.577213E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.205172E+09 | 197.62 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.185252E+09 | 197.62 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.205884E+09 | 197.62 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.198216E+09 | 197.62 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.205528E+09 | 197.62 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.199125E+09 | 197.62 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.204619E+09 | 197.62 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.205884E+09 | 197.62 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.198216E+09 | 197.62 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.205172E+09 | 197.62 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.198967E+09 | 197.62 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.204619E+09 | 197.62 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.241666E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.185252E+09 | 197.62 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.205884E+09 | 197.62 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.303752E+09 | 292.58 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.274260E+09 | 292.58 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.304805E+09 | 292.58 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.293453E+09 | 292.58 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.304278E+09 | 292.58 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.294799E+09 | 292.58 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.302933E+09 | 292.58 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.304805E+09 | 292.58 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.293453E+09 | 292.58 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.303752E+09 | 292.58 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.294565E+09 | 292.58 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.302933E+09 | 292.58 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.357779E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.274260E+09 | 292.58 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.304805E+09 | 292.58 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.140737E+10 | 1531.38 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.124803E+10 | 1531.38 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.133762E+10 | 1531.38 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.124626E+10 | 1531.38 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.123452E+10 | 1531.38 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.118393E+10 | 1531.38 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.122085E+10 | 1531.38 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.126214E+10 | 1531.38 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.127336E+10 | 1531.38 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.136756E+10 | 1531.38 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.135474E+10 | 1531.38 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.141477E+10 | 1531.38 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.155511E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.118393E+10 | 1531.38 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.141477E+10 | 1531.38 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123012E+11 | 12090.12 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.110739E+11 | 12090.12 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.122427E+11 | 12090.12 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.117328E+11 | 12090.12 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.120863E+11 | 12090.12 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.116896E+11 | 12090.12 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.120173E+11 | 12090.12 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.121409E+11 | 12090.12 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.117645E+11 | 12090.12 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122455E+11 | 12090.12 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119150E+11 | 12090.12 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122866E+11 | 12090.12 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.143496E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.110739E+11 | 12090.12 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123012E+11 | 12090.12 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124452E+09 | 146.35 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.112401E+09 | 146.35 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.123995E+09 | 146.35 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.120512E+09 | 146.35 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.124224E+09 | 146.35 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.120054E+09 | 146.35 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.124681E+09 | 146.35 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.123995E+09 | 146.35 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.120512E+09 | 146.35 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.124452E+09 | 146.35 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.120283E+09 | 146.35 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.124681E+09 | 146.35 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.146424E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.112401E+09 | 146.35 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.124681E+09 | 146.35 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124486E+09 | 146.39 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.112432E+09 | 146.39 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.124029E+09 | 146.39 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.120544E+09 | 146.39 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.124258E+09 | 146.39 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.120087E+09 | 146.39 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124715E+09 | 146.39 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.124029E+09 | 146.39 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.120544E+09 | 146.39 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.124486E+09 | 146.39 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.120316E+09 | 146.39 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124715E+09 | 146.39 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.146464E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.112432E+09 | 146.39 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.124715E+09 | 146.39 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.232638E+10 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233445E+10 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224751E+10 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233042E+10 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224751E+10 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232638E+10 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274017E+11 | ||||
Minimum of Months | 0.210051E+10 | 2240.79 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.79 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198027E+09 | 232.86 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.178851E+09 | 232.86 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.197299E+09 | 232.86 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.191756E+09 | 232.86 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.197663E+09 | 232.86 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.191029E+09 | 232.86 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.198391E+09 | 232.86 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.197299E+09 | 232.86 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.191756E+09 | 232.86 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.198027E+09 | 232.86 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.191392E+09 | 232.86 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.198391E+09 | 232.86 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.232988E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.178851E+09 | 232.86 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.198391E+09 | 232.86 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.198004E+09 | 232.84 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.178830E+09 | 232.84 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.197276E+09 | 232.84 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.191734E+09 | 232.84 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.197640E+09 | 232.84 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.191006E+09 | 232.84 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.198368E+09 | 232.84 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.197276E+09 | 232.84 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.191734E+09 | 232.84 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.198004E+09 | 232.84 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.191370E+09 | 232.84 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.198368E+09 | 232.84 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.232961E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.178830E+09 | 232.84 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.198368E+09 | 232.84 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.124486E+09 | 146.39 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.112432E+09 | 146.39 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.124029E+09 | 146.39 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.120544E+09 | 146.39 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.124258E+09 | 146.39 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.120087E+09 | 146.39 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.124715E+09 | 146.39 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.124029E+09 | 146.39 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.120544E+09 | 146.39 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.124486E+09 | 146.39 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.120316E+09 | 146.39 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.124715E+09 | 146.39 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.146464E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.112432E+09 | 146.39 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.124715E+09 | 146.39 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.264112E+10 | 2689.23 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.236355E+10 | 2689.23 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.257683E+10 | 2689.23 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243734E+10 | 2689.23 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246827E+10 | 2689.23 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.237629E+10 | 2689.23 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.244905E+10 | 2689.23 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.249839E+10 | 2689.23 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.246515E+10 | 2689.23 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260237E+10 | 2689.23 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.255067E+10 | 2689.23 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.264795E+10 | 2689.23 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.300770E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.236355E+10 | 2689.23 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.264795E+10 | 2689.23 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.264112E+10 | 2689.23 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.236355E+10 | 2689.23 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.257683E+10 | 2689.23 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.243734E+10 | 2689.23 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.246827E+10 | 2689.23 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.237629E+10 | 2689.23 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.244905E+10 | 2689.23 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.249839E+10 | 2689.23 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.246515E+10 | 2689.23 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.260237E+10 | 2689.23 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.255067E+10 | 2689.23 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.264795E+10 | 2689.23 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.300770E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.236355E+10 | 2689.23 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.264795E+10 | 2689.23 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.991199E+09 | 954.73 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.894963E+09 | 954.73 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.994636E+09 | 954.73 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.957593E+09 | 954.73 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.992918E+09 | 954.73 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.961985E+09 | 954.73 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.988526E+09 | 954.73 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.994636E+09 | 954.73 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.957593E+09 | 954.73 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.991199E+09 | 954.73 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.961221E+09 | 954.73 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.988526E+09 | 954.73 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.116750E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.894963E+09 | 954.73 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.994636E+09 | 954.73 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.246212E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222307E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.247065E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246639E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238955E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245548E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237864E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246212E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245548E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290004E+11 | ||||
Minimum of Months | 0.222307E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.120209E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.108538E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.116133E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.120417E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.116666E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.119885E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.116133E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.120209E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.116573E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.119885E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.141590E+12 | 0.150259E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.108538E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.120626E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.643545E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225388E+10 |
February | 0.179968E+10 | 0.581063E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168610E+10 |
March | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134826E+10 |
April | 0.192973E+10 | 0.621726E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8689559.66 | 0.892066E+09 |
May | 0.199475E+10 | 0.644661E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13117617.05 | 0.449890E+09 |
June | 0.193394E+10 | 0.624577E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73112026.68 | 0.217008E+09 |
July | 0.199054E+10 | 0.641810E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70260779.28 | 0.115362E+09 |
August | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61824792.47 | 0.167510E+09 |
September | 0.192973E+10 | 0.621726E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30529947.70 | 0.417960E+09 |
October | 0.199054E+10 | 0.643545E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.95 | 0.889477E+09 |
November | 0.192552E+10 | 0.624081E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133599E+10 |
December | 0.199054E+10 | 0.641810E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191789E+10 |
Annual Sum or Average | 0.234734E+11 | 0.758010E+10 | 0.101859E+11 | 0.257536E+09 | 0.116914E+11 | ||||
Minimum of Months | 0.179968E+10 | 0.581063E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115362E+09 |
Maximum of Months | 0.199896E+10 | 0.645777E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73112026.68 | 0.225388E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.745228E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475824E+09 |
February | 0.208403E+10 | 0.672873E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356374E+09 |
March | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290360E+09 |
April | 0.223463E+10 | 0.719961E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2293646.78 | 0.197400E+09 |
May | 0.230993E+10 | 0.746520E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2990085.30 | 0.107673E+09 |
June | 0.223950E+10 | 0.723263E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15367832.70 | 55144236.61 |
July | 0.230505E+10 | 0.743218E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14921125.43 | 32936484.39 |
August | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14075174.84 | 44826478.86 |
September | 0.223463E+10 | 0.719961E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8119430.57 | 98532023.64 |
October | 0.230505E+10 | 0.745228E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16720.77 | 0.198712E+09 |
November | 0.222975E+10 | 0.722689E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288691E+09 |
December | 0.230505E+10 | 0.743218E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405888E+09 |
Annual Sum or Average | 0.271823E+11 | 0.877778E+10 | 0.117953E+11 | 57784016.39 | 0.255236E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.672873E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32936484.39 |
Maximum of Months | 0.231480E+10 | 0.747812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15367832.70 | 0.475824E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.303752E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147948E+10 |
February | 0.139600E+10 | 0.274260E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110383E+10 |
March | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931519E+09 |
April | 0.149688E+10 | 0.293453E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 7920696.10 | 0.628861E+09 |
May | 0.154732E+10 | 0.304278E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 10009375.18 | 0.336408E+09 |
June | 0.150015E+10 | 0.294799E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 51310912.40 | 0.166548E+09 |
July | 0.154405E+10 | 0.302933E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 51316899.00 | 93949648.51 |
August | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50325401.09 | 0.130134E+09 |
September | 0.149688E+10 | 0.293453E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 30483969.45 | 0.300422E+09 |
October | 0.154405E+10 | 0.303752E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 253090.60 | 0.622823E+09 |
November | 0.149361E+10 | 0.294565E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916270E+09 |
December | 0.154405E+10 | 0.302933E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130031E+10 |
Annual Sum or Average | 0.182082E+11 | 0.357779E+10 | 0.679373E+11 | 0.590211E+12 | 0.201620E+09 | 0.801056E+10 | |||
Minimum of Months | 0.139600E+10 | 0.274260E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93949648.51 |
Maximum of Months | 0.155059E+10 | 0.304805E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 51316899.00 | 0.147948E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.140737E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572057E+10 |
February | 0.236489E+11 | 0.124803E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432065E+10 |
March | 0.262677E+11 | 0.133762E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349256E+10 |
April | 0.253579E+11 | 0.124626E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21722275.33 | 0.236795E+10 |
May | 0.262123E+11 | 0.123452E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31211083.09 | 0.129231E+10 |
June | 0.254132E+11 | 0.118393E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173676E+09 | 0.668723E+09 |
July | 0.261570E+11 | 0.122085E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166484E+09 | 0.405442E+09 |
August | 0.262677E+11 | 0.126214E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147776E+09 | 0.547519E+09 |
September | 0.253579E+11 | 0.127336E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75793510.96 | 0.119171E+10 |
October | 0.261570E+11 | 0.136756E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239774E+10 |
November | 0.253025E+11 | 0.135474E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345488E+10 |
December | 0.261570E+11 | 0.141477E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487880E+10 |
Annual Sum or Average | 0.308456E+12 | 0.155511E+11 | 0.143409E+11 | 0.616663E+09 | 0.307388E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.118393E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405442E+09 |
Maximum of Months | 0.262677E+11 | 0.141477E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173676E+09 | 0.572057E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123012E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115096E+11 |
February | 0.702046E+11 | 0.110739E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867376E+10 |
March | 0.779788E+11 | 0.122427E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710573E+10 |
April | 0.752779E+11 | 0.117328E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52584245.67 | 0.484759E+10 |
May | 0.778146E+11 | 0.120863E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68153176.40 | 0.269084E+10 |
June | 0.754422E+11 | 0.116896E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360321E+09 | 0.139853E+10 |
July | 0.776503E+11 | 0.120173E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349932E+09 | 0.851785E+09 |
August | 0.779788E+11 | 0.121409E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325195E+09 | 0.114189E+10 |
September | 0.752779E+11 | 0.117645E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186295E+09 | 0.245429E+10 |
October | 0.776503E+11 | 0.122455E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95337.76 | 0.490714E+10 |
November | 0.751137E+11 | 0.119150E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705257E+10 |
December | 0.776503E+11 | 0.122866E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986474E+10 |
Annual Sum or Average | 0.915690E+12 | 0.143496E+12 | 0.149002E+12 | 0.134258E+10 | 0.624985E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.110739E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851785E+09 |
Maximum of Months | 0.779788E+11 | 0.123012E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360321E+09 | 0.115096E+11 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664573E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507744E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393660E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130656.62 | 0.262421E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3436136.87 | 0.138886E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21541034.44 | 66718316.24 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20210445.72 | 35785583.51 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18777487.26 | 49926158.03 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11522269.69 | 0.122228E+09 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20271.62 | 0.259257E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389687E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555932E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 78638302.22 | 0.344682E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35785583.51 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21541034.44 | 0.664573E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662693E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503940E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389837E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3144598.54 | 0.260472E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451206.46 | 0.138210E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21553059.97 | 66601233.14 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20240824.12 | 35738769.23 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18837297.42 | 49778842.44 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11615522.16 | 0.121002E+09 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23792.05 | 0.254781E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386682E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552765E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 78866300.71 | 0.342250E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35738769.23 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21553059.97 | 0.662693E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124452E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167033E+09 |
February | 0.00 | 0.112401E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140613E+09 |
March | 0.00 | 0.123995E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118691E+09 |
April | 0.00 | 0.120512E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171422.09 | 93651086.91 |
May | 0.00 | 0.124224E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131936.67 | 63154666.89 |
June | 0.00 | 0.120054E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444753.30 | 37976776.43 |
July | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543370.78 | 29314865.39 |
August | 0.00 | 0.123995E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 768415.56 | 33995534.23 |
September | 0.00 | 0.120512E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704341.93 | 55888731.51 |
October | 0.00 | 0.124452E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98322247.55 |
November | 0.00 | 0.120283E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122509E+09 |
December | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143775E+09 |
Annual Sum or Average | 0.00 | 0.146424E+10 | 0.300992E+10 | 3764240.34 | 0.110493E+10 | ||||
Minimum of Months | 0.00 | 0.112401E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29314865.39 |
Maximum of Months | 0.00 | 0.124681E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444753.30 | 0.167033E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185866E+09 |
February | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141558E+09 |
March | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110317E+09 |
April | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 898278.01 | 73531159.56 |
May | 0.303504E+09 | 0.124258E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 986249.33 | 38671866.38 |
June | 0.293842E+09 | 0.120087E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6089442.42 | 18662033.09 |
July | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5760432.17 | 9895310.28 |
August | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5378789.81 | 13812054.43 |
September | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3324239.46 | 34068924.99 |
October | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10834.40 | 72169583.72 |
November | 0.293661E+09 | 0.120316E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109452E+09 |
December | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155668E+09 |
Annual Sum or Average | 0.357224E+10 | 0.146464E+10 | 0.301074E+10 | 22448265.60 | 0.963672E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9895310.28 |
Maximum of Months | 0.303685E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6089442.42 | 0.185866E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664345E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507205E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394893E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3128794.15 | 0.263239E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3426309.28 | 0.140364E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21500976.85 | 67357081.76 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20179300.19 | 36224269.58 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18736097.73 | 50429669.51 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11514597.01 | 0.123171E+09 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21338.09 | 0.260122E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389561E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555614E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 78507413.31 | 0.345253E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36224269.58 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21500976.85 | 0.664345E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662487E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503131E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391081E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3135338.68 | 0.261351E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3428231.36 | 0.139971E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21505317.08 | 67281764.88 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20191954.05 | 36199012.54 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18761501.40 | 50360175.91 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11546342.50 | 0.122272E+09 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22151.12 | 0.255704E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386522E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552632E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 78590836.19 | 0.342899E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36199012.54 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21505317.08 | 0.662487E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664896E+09 |
February | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507897E+09 |
March | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393066E+09 |
April | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3073831.93 | 0.262697E+09 |
May | 0.303504E+09 | 0.197663E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3355156.09 | 0.140214E+09 |
June | 0.293842E+09 | 0.191029E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21173389.62 | 67549852.03 |
July | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19733160.15 | 36486499.41 |
August | 0.303685E+09 | 0.197299E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18371236.66 | 50649883.60 |
September | 0.293479E+09 | 0.191756E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11307018.64 | 0.122832E+09 |
October | 0.303322E+09 | 0.198027E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18397.48 | 0.259297E+09 |
November | 0.293661E+09 | 0.191392E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389316E+09 |
December | 0.303141E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555802E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232988E+10 | 0.307301E+10 | 77032190.56 | 0.345070E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178851E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36486499.41 |
Maximum of Months | 0.303685E+09 | 0.198391E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21173389.62 | 0.664896E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663502E+09 |
February | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504374E+09 |
March | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389625E+09 |
April | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3086383.43 | 0.260742E+09 |
May | 0.303504E+09 | 0.197640E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3358789.53 | 0.139663E+09 |
June | 0.293842E+09 | 0.191006E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21177012.03 | 67471560.25 |
July | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19745674.39 | 36472793.27 |
August | 0.303685E+09 | 0.197276E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18405877.85 | 50582811.68 |
September | 0.293479E+09 | 0.191734E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11375963.75 | 0.121662E+09 |
October | 0.303322E+09 | 0.198004E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21562.52 | 0.254418E+09 |
November | 0.293661E+09 | 0.191370E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386573E+09 |
December | 0.303141E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553455E+09 |
Annual Sum or Average | 0.357224E+10 | 0.232961E+10 | 0.307265E+10 | 77171263.51 | 0.342854E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.178830E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36472793.27 |
Maximum of Months | 0.303685E+09 | 0.198368E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21177012.03 | 0.663502E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344725E+09 |
February | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264107E+09 |
March | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204443E+09 |
April | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1567689.94 | 0.135650E+09 |
May | 0.303504E+09 | 0.124258E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1717274.83 | 72091622.07 |
June | 0.293842E+09 | 0.120087E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10842691.97 | 34709252.65 |
July | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10105531.67 | 18634213.76 |
August | 0.303685E+09 | 0.124029E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9384843.92 | 25919404.53 |
September | 0.293479E+09 | 0.120544E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5756305.40 | 63517808.61 |
October | 0.303322E+09 | 0.124486E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1294.94 | 0.134915E+09 |
November | 0.293661E+09 | 0.120316E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202690E+09 |
December | 0.303141E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288253E+09 |
Annual Sum or Average | 0.357224E+10 | 0.146464E+10 | 0.301074E+10 | 39375632.67 | 0.178966E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.112432E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18634213.76 |
Maximum of Months | 0.303685E+09 | 0.124715E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10842691.97 | 0.344725E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.264112E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169672E+10 |
February | 0.415303E+11 | 0.236355E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128536E+10 |
March | 0.461292E+11 | 0.257683E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107268E+10 |
April | 0.445315E+11 | 0.243734E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6039155.25 | 0.742125E+09 |
May | 0.460320E+11 | 0.246827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6007995.11 | 0.428257E+09 |
June | 0.446286E+11 | 0.237629E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36538713.83 | 0.231964E+09 |
July | 0.459349E+11 | 0.244905E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30991835.90 | 0.152374E+09 |
August | 0.461292E+11 | 0.249839E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32277507.98 | 0.189896E+09 |
September | 0.445315E+11 | 0.246515E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22073085.82 | 0.379057E+09 |
October | 0.459349E+11 | 0.260237E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51048.92 | 0.734990E+09 |
November | 0.444343E+11 | 0.255067E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105453E+10 |
December | 0.459349E+11 | 0.264795E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146766E+10 |
Annual Sum or Average | 0.541686E+12 | 0.300770E+11 | 0.175857E+12 | 0.133979E+09 | 0.943561E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.236355E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152374E+09 |
Maximum of Months | 0.461292E+11 | 0.264795E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36538713.83 | 0.169672E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.264112E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170852E+10 |
February | 0.415303E+11 | 0.236355E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129375E+10 |
March | 0.461292E+11 | 0.257683E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108259E+10 |
April | 0.445315E+11 | 0.243734E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5671685.37 | 0.749127E+09 |
May | 0.460320E+11 | 0.246827E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5516486.83 | 0.433964E+09 |
June | 0.446286E+11 | 0.237629E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34929579.60 | 0.235144E+09 |
July | 0.459349E+11 | 0.244905E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28855030.43 | 0.154811E+09 |
August | 0.461292E+11 | 0.249839E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29966406.03 | 0.192656E+09 |
September | 0.445315E+11 | 0.246515E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20828899.94 | 0.383504E+09 |
October | 0.459349E+11 | 0.260237E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25405.52 | 0.742615E+09 |
November | 0.444343E+11 | 0.255067E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106442E+10 |
December | 0.459349E+11 | 0.264795E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148108E+10 |
Annual Sum or Average | 0.541686E+12 | 0.300770E+11 | 0.175857E+12 | 0.125793E+09 | 0.952218E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.236355E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154811E+09 |
Maximum of Months | 0.461292E+11 | 0.264795E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34929579.60 | 0.170852E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.991199E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153694E+10 |
February | 0.369574E+10 | 0.894963E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115682E+10 |
March | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974756E+09 |
April | 0.396281E+10 | 0.957593E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4131548.90 | 0.672516E+09 |
May | 0.409635E+10 | 0.992918E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3920775.17 | 0.388377E+09 |
June | 0.397146E+10 | 0.961985E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27999964.39 | 0.204114E+09 |
July | 0.408770E+10 | 0.988526E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21317056.23 | 0.129790E+09 |
August | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21809553.99 | 0.166556E+09 |
September | 0.396281E+10 | 0.957593E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15211910.30 | 0.341290E+09 |
October | 0.408770E+10 | 0.991199E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668963E+09 |
November | 0.395417E+10 | 0.961221E+09 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959486E+09 |
December | 0.408770E+10 | 0.988526E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134169E+10 |
Annual Sum or Average | 0.482041E+11 | 0.116750E+11 | 0.392709E+12 | 0.359593E+12 | 94390808.98 | 0.854130E+10 | |||
Minimum of Months | 0.369574E+10 | 0.894963E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129790E+09 |
Maximum of Months | 0.410499E+10 | 0.994636E+09 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27999964.39 | 0.153694E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104503E+10 |
February | 0.00 | 0.577213E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770613E+09 |
March | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619518E+09 |
April | 0.00 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5683221.12 | 0.412462E+09 |
May | 0.00 | 0.640390E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6955152.42 | 0.219284E+09 |
June | 0.00 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34562926.95 | 0.111878E+09 |
July | 0.00 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33339001.76 | 65159997.26 |
August | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31646813.76 | 90301966.45 |
September | 0.00 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18995524.00 | 0.202654E+09 |
October | 0.00 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121195.39 | 0.409709E+09 |
November | 0.00 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619084E+09 |
December | 0.00 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882560E+09 |
Annual Sum or Average | 0.752987E+10 | 0.124715E+11 | 0.131304E+09 | 0.544826E+10 | |||||
Minimum of Months | 0.00 | 0.577213E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65159997.26 |
Maximum of Months | 0.00 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34562926.95 | 0.104503E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.205172E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723851E+09 |
February | 0.00 | 0.185252E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533238E+09 |
March | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429474E+09 |
April | 0.00 | 0.198216E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019206.00 | 0.284372E+09 |
May | 0.00 | 0.205528E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4975105.84 | 0.147741E+09 |
June | 0.00 | 0.199125E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24550485.68 | 74777158.78 |
July | 0.00 | 0.204619E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23931201.89 | 42813080.02 |
August | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22625225.15 | 59724023.84 |
September | 0.00 | 0.198216E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13492680.93 | 0.136247E+09 |
October | 0.00 | 0.205172E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91038.96 | 0.279032E+09 |
November | 0.00 | 0.198967E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427740E+09 |
December | 0.00 | 0.204619E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613297E+09 |
Annual Sum or Average | 0.241666E+10 | 0.359769E+10 | 93684944.46 | 0.375231E+10 | |||||
Minimum of Months | 0.00 | 0.185252E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42813080.02 |
Maximum of Months | 0.00 | 0.205884E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24550485.68 | 0.723851E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806120E+09 |
February | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601497E+09 |
March | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476065E+09 |
April | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4617417.37 | 0.314148E+09 |
May | 0.00 | 0.233042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5938075.50 | 0.158741E+09 |
June | 0.00 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30453515.28 | 76659302.53 |
July | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30378910.52 | 40434999.71 |
August | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28937469.87 | 57230143.49 |
September | 0.00 | 0.224751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16673005.51 | 0.143180E+09 |
October | 0.00 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92563.09 | 0.306836E+09 |
November | 0.00 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472914E+09 |
December | 0.00 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679545E+09 |
Annual Sum or Average | 0.274017E+11 | 0.117091E+09 | 0.413337E+10 | ||||||
Minimum of Months | 0.00 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40434999.71 |
Maximum of Months | 0.00 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30453515.28 | 0.806120E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142286E+10 |
February | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105183E+10 |
March | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846859E+09 |
April | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6399573.48 | 0.565381E+09 |
May | 0.00 | 0.246639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6896723.46 | 0.299517E+09 |
June | 0.00 | 0.238955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37441893.55 | 0.155098E+09 |
July | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32666755.28 | 92386467.10 |
August | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34411863.12 | 0.121742E+09 |
September | 0.00 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21334322.29 | 0.268122E+09 |
October | 0.00 | 0.246212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53118.01 | 0.550590E+09 |
November | 0.00 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840111E+09 |
December | 0.00 | 0.245548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120592E+10 |
Annual Sum or Average | 0.290004E+11 | 0.139204E+09 | 0.742042E+10 | ||||||
Minimum of Months | 0.00 | 0.222307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92386467.10 |
Maximum of Months | 0.00 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37441893.55 | 0.142286E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 11578.59 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 11578.59 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 11578.59 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 11578.59 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 11578.59 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 11578.59 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 11578.59 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 11578.59 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 11578.59 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 11578.59 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 11578.59 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 11578.59 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 619.87 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1229.16 | 30-JAN-12:30 |
February | 1169.53 | 01-FEB-00:10 | 619.87 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1319.72 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 619.87 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 985.26 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 619.87 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.87 | 15-APR-17:00 | 702.27 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 619.87 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.57 | 31-MAY-13:00 | 495.37 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 619.87 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 11-JUN-15:00 | 376.69 | 03-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 619.87 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.21 | 26-JUL-15:00 | 256.69 | 23-JUL-04:00 |
August | 1169.53 | 01-AUG-00:10 | 619.87 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.47 | 04-AUG-16:00 | 297.74 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 619.87 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.95 | 07-SEP-14:00 | 537.14 | 30-SEP-01:00 |
October | 1169.53 | 02-OCT-00:10 | 619.87 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 21-OCT-15:00 | 599.66 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 619.87 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1177.67 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 619.87 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1150.13 | 09-DEC-01:30 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 619.87 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.69 | |||||
Maximum of Months | 1169.53 | 619.87 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 1319.72 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 717.81 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.29 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 717.81 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 289.58 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 717.81 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 208.40 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 717.81 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.64 | 15-APR-16:00 | 149.32 | 03-APR-21:00 |
May | 1354.32 | 01-MAY-00:10 | 717.81 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.06 | 31-MAY-13:00 | 110.74 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 717.81 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.53 | 11-JUN-15:00 | 87.74 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 717.81 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 26-JUL-15:00 | 62.34 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 717.81 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 04-AUG-15:00 | 71.44 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 717.81 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 | 06-SEP-14:00 | 119.70 | 30-SEP-01:00 |
October | 1354.32 | 02-OCT-00:10 | 717.81 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 20-OCT-15:00 | 131.85 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 717.81 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 259.28 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 717.81 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 245.27 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 717.81 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | |||||
Maximum of Months | 1354.32 | 717.81 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 289.58 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 292.58 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 819.50 | 05-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 292.58 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 794.55 | 02-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 292.58 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 664.48 | 05-MAR-23:00 |
April | 907.20 | 01-APR-00:10 | 292.58 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 124.47 | 15-APR-15:00 | 498.40 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 292.58 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 125.12 | 31-MAY-15:00 | 343.08 | 03-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 292.58 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 168.81 | 11-JUN-15:00 | 268.89 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 292.58 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 126.12 | 26-JUL-15:05 | 196.97 | 24-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 292.58 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 176.59 | 04-AUG-15:00 | 236.38 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 292.58 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 156.07 | 07-SEP-14:00 | 371.52 | 29-SEP-06:10 |
October | 907.20 | 02-OCT-00:10 | 292.58 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 32.57 | 20-OCT-15:00 | 430.25 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 292.58 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 806.76 | 25-NOV-21:03 |
December | 907.20 | 01-DEC-00:10 | 292.58 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 800.48 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 196.97 | ||||||
Maximum of Months | 907.20 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.59 | 819.50 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1531.38 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3179.64 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1531.38 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3476.56 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1531.38 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2486.40 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1531.38 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.09 | 15-APR-16:00 | 1773.66 | 03-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1531.38 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.53 | 31-MAY-13:00 | 1337.18 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1531.38 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.12 | 11-JUN-15:00 | 1072.99 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1531.38 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.24 | 26-JUL-15:00 | 775.88 | 24-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1531.38 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.79 | 04-AUG-15:00 | 872.55 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1531.38 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.49 | 06-SEP-15:00 | 1428.39 | 30-SEP-01:00 |
October | 15368.40 | 02-OCT-00:10 | 1531.38 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 1528.32 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1531.38 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3030.40 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1531.38 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2923.49 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1531.38 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.88 | |||||
Maximum of Months | 15368.40 | 1531.38 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 586.12 | 3476.56 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 12090.12 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6367.62 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 12090.12 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6996.41 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 12090.12 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 5080.22 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 12090.12 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 852.78 | 15-APR-16:00 | 3668.94 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 12090.12 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 906.56 | 31-MAY-13:00 | 2738.86 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 12090.12 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.84 | 11-JUN-15:00 | 2176.08 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 12090.12 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.88 | 26-JUL-15:00 | 1572.35 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 12090.12 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.23 | 04-AUG-15:00 | 1773.79 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 12090.12 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.13 | 06-SEP-14:00 | 2957.11 | 30-SEP-01:00 |
October | 45622.98 | 02-OCT-00:10 | 12090.12 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.11 | 20-OCT-15:00 | 3221.67 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 12090.12 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6214.51 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 12090.12 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5913.13 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1572.35 | |||||
Maximum of Months | 45622.98 | 12090.12 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.23 | 6996.41 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 416.58 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 466.67 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.19 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.73 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 466.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 413.10 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 462.57 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.77 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:10 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.37 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.17 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.70 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 462.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 146.35 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 104.56 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 146.35 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 120.85 | 02-FEB-06:06 |
March | 0.00 | 01-MAR-00:10 | 146.35 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.93 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 146.35 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 15-APR-15:00 | 63.00 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 146.35 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 31-MAY-13:00 | 49.90 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 146.35 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-JUN-15:00 | 41.46 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 146.35 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 26-JUL-15:00 | 31.91 | 24-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 146.35 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 04-AUG-15:00 | 35.40 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 146.35 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 07-SEP-14:00 | 52.65 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 146.35 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 58.20 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 146.35 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 103.72 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 146.35 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.21 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 146.35 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.91 | |||||
Maximum of Months | 0.00 | 146.35 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 120.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 146.39 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 113.79 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 146.39 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 128.77 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 146.39 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 81.16 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 146.39 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 15-APR-15:08 | 57.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 146.39 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 31-MAY-15:10 | 40.95 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 146.39 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 11-JUN-15:10 | 31.20 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 146.39 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 26-JUL-15:10 | 21.35 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 146.39 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 04-AUG-15:10 | 24.72 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 146.39 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 06-SEP-15:10 | 44.37 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 146.39 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 20-OCT-15:10 | 49.50 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 146.39 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 109.59 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 146.39 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.37 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 128.77 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 413.33 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 464.21 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.79 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:08 | 111.81 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 06-SEP-15:08 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.20 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.74 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 464.21 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 409.46 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 459.99 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.77 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:08 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:08 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.37 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 394.36 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 459.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.86 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 415.96 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.86 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 466.03 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.86 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.33 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.86 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.08 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.86 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 31-MAY-15:10 | 147.18 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.86 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.24 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.86 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 | 26-JUL-15:10 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.86 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.86 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 06-SEP-15:10 | 159.45 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.86 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:10 | 177.86 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.86 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.78 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.86 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.29 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 232.86 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 466.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 232.84 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 411.82 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 232.84 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 461.08 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 232.84 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.30 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 232.84 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.06 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 232.84 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 | 31-MAY-15:10 | 147.16 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 232.84 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 | 11-JUN-15:10 | 112.23 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 232.84 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 26-JUL-15:10 | 76.92 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 232.84 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 232.84 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 06-SEP-15:10 | 159.44 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 232.84 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:10 | 177.84 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 232.84 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.10 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 232.84 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.26 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | |||||
Maximum of Months | 180.00 | 232.84 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 461.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 146.39 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 213.92 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 146.39 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 240.56 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 146.39 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 149.04 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 146.39 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-APR-16:10 | 106.45 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 146.39 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 31-MAY-15:10 | 75.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 146.39 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 11-JUN-15:10 | 57.42 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 146.39 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 26-JUL-15:10 | 39.36 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 146.39 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 04-AUG-15:10 | 45.54 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 146.39 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 06-SEP-15:10 | 81.58 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 146.39 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 20-OCT-15:10 | 90.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 146.39 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 202.48 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 146.39 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.11 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | |||||
Maximum of Months | 180.00 | 146.39 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 240.56 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2689.23 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 915.48 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2689.23 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1003.25 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2689.23 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 756.36 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2689.23 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.77 | 15-APR-16:00 | 556.42 | 03-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2689.23 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.67 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2689.23 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.58 | 11-JUN-15:00 | 322.82 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2689.23 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.85 | 26-JUL-15:00 | 236.11 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2689.23 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.98 | 04-AUG-15:00 | 265.91 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2689.23 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.92 | 06-SEP-14:00 | 439.68 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 2689.23 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 20-OCT-15:00 | 485.40 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2689.23 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 890.59 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2689.23 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.11 | |||||
Maximum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 157.98 | 1003.25 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2689.23 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 911.56 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2689.23 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 997.69 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2689.23 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 761.38 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2689.23 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.35 | 15-APR-16:00 | 559.68 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2689.23 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.93 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2689.23 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.25 | 11-JUN-15:00 | 322.83 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2689.23 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.70 | 26-JUL-15:00 | 236.17 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2689.23 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.60 | 04-AUG-15:00 | 265.91 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2689.23 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 06-SEP-14:00 | 439.69 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 2689.23 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 | 20-OCT-15:00 | 485.41 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2689.23 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 889.51 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2689.23 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.17 | |||||
Maximum of Months | 26988.77 | 2689.23 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 155.60 | 997.69 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 954.73 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 815.21 | 05-JAN-21:10 |
February | 2401.70 | 01-FEB-00:10 | 954.73 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 800.58 | 04-FEB-11:40 |
March | 2401.70 | 01-MAR-00:10 | 954.73 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 663.51 | 05-MAR-23:10 |
April | 2401.70 | 01-APR-00:10 | 954.73 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 81.41 | 15-APR-15:40 | 500.86 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 954.73 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 81.87 | 31-MAY-13:00 | 353.38 | 03-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 954.73 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 125.89 | 11-JUN-15:00 | 280.85 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 954.73 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 82.54 | 26-JUL-15:40 | 206.73 | 24-JUL-05:10 |
August | 2401.70 | 01-AUG-00:10 | 954.73 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 133.73 | 04-AUG-15:40 | 237.95 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 954.73 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 112.49 | 06-SEP-14:40 | 374.89 | 29-SEP-23:00 |
October | 2401.70 | 02-OCT-00:10 | 954.73 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 434.41 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 954.73 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 805.05 | 25-NOV-21:03 |
December | 2401.70 | 01-DEC-00:10 | 954.73 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 791.56 | 09-DEC-08:04 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 954.73 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 206.73 | ||||||
Maximum of Months | 2401.70 | 954.73 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 133.73 | 815.21 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 597.73 | 30-JAN-08:00 |
February | 0.00 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 656.63 | 02-FEB-06:10 |
March | 0.00 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 455.22 | 06-MAR-01:00 |
April | 0.00 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.81 | 15-APR-16:40 | 324.51 | 03-APR-06:00 |
May | 0.00 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.70 | 31-MAY-13:00 | 228.87 | 03-MAY-03:00 |
June | 0.00 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.59 | 11-JUN-15:00 | 183.40 | 01-JUN-05:00 |
July | 0.00 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 26-JUL-15:00 | 128.20 | 23-JUL-04:00 |
August | 0.00 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.79 | 04-AUG-15:00 | 149.90 | 07-AUG-06:00 |
September | 0.00 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 | 06-SEP-14:00 | 250.91 | 30-SEP-01:00 |
October | 0.00 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 20-OCT-15:00 | 279.80 | 23-OCT-06:00 |
November | 0.00 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 590.46 | 26-NOV-07:00 |
December | 0.00 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 535.22 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | ||||
Maximum of Months | 0.00 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 113.79 | 656.63 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 197.62 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 410.89 | 30-JAN-08:00 |
February | 0.00 | 197.62 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 451.19 | 02-FEB-06:10 |
March | 0.00 | 197.62 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 316.50 | 06-MAR-01:00 |
April | 0.00 | 197.62 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 15-APR-16:50 | 225.62 | 03-APR-06:00 |
May | 0.00 | 197.62 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 31-MAY-13:00 | 159.13 | 03-MAY-03:00 |
June | 0.00 | 197.62 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.71 | 11-JUN-15:00 | 125.50 | 01-JUN-05:00 |
July | 0.00 | 197.62 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 | 26-JUL-15:00 | 86.88 | 23-JUL-04:00 |
August | 0.00 | 197.62 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 04-AUG-15:00 | 101.68 | 07-AUG-06:00 |
September | 0.00 | 197.62 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.45 | 06-SEP-14:00 | 172.55 | 30-SEP-01:00 |
October | 0.00 | 197.62 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 20-OCT-15:00 | 192.62 | 23-OCT-06:00 |
November | 0.00 | 197.62 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 406.77 | 26-NOV-07:00 |
December | 0.00 | 197.62 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 369.48 | 09-DEC-00:30 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 197.62 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 | ||||
Maximum of Months | 0.00 | 197.62 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 451.19 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2240.79 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 471.00 | 31-JAN-04:00 |
February | 0.00 | 2240.79 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 524.79 | 02-FEB-06:10 |
March | 0.00 | 2240.79 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 350.61 | 06-MAR-01:00 |
April | 0.00 | 2240.79 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 | 15-APR-17:00 | 250.04 | 03-APR-06:00 |
May | 0.00 | 2240.79 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 | 31-MAY-13:00 | 176.44 | 03-MAY-03:00 |
June | 0.00 | 2240.79 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.80 | 11-JUN-15:00 | 134.27 | 03-JUN-04:00 |
July | 0.00 | 2240.79 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.42 | 26-JUL-15:00 | 91.59 | 23-JUL-04:00 |
August | 0.00 | 2240.79 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 04-AUG-15:00 | 106.45 | 07-AUG-06:00 |
September | 0.00 | 2240.79 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 06-SEP-14:00 | 191.30 | 30-SEP-01:00 |
October | 0.00 | 2240.79 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 20-OCT-15:00 | 213.51 | 23-OCT-06:00 |
November | 0.00 | 2240.79 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 455.53 | 26-NOV-07:00 |
December | 0.00 | 2240.79 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 409.24 | 09-DEC-00:20 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | |||
Maximum of Months | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 524.79 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 791.77 | 31-JAN-04:00 |
February | 0.00 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 867.58 | 02-FEB-06:02 |
March | 0.00 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 621.55 | 06-MAR-01:00 |
April | 0.00 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.12 | 15-APR-17:00 | 443.51 | 03-APR-06:00 |
May | 0.00 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.08 | 31-MAY-13:00 | 313.23 | 03-MAY-03:00 |
June | 0.00 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.46 | 11-JUN-15:00 | 247.21 | 01-JUN-05:00 |
July | 0.00 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.92 | 26-JUL-15:00 | 172.05 | 24-JUL-03:00 |
August | 0.00 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.41 | 04-AUG-15:00 | 196.98 | 07-AUG-06:00 |
September | 0.00 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.53 | 06-SEP-15:00 | 339.49 | 30-SEP-01:00 |
October | 0.00 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 | 20-OCT-15:00 | 378.86 | 23-OCT-06:00 |
November | 0.00 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 781.83 | 26-NOV-07:00 |
December | 0.00 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 725.38 | 09-DEC-08:50 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.05 | |||
Maximum of Months | 0.00 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.41 | 867.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37155.91 | 19-JAN-01:51 | 115018.92 | 19297.65 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32368.60 | 02-FEB-06:02 | 44729.58 | 25730.20 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11745.10 | 25-MAR-15:00 | 3833.96 | 3216.28 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12973.14 | 15-APR-21:10 | 8945.92 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13401.39 | 31-MAY-21:10 | 11501.89 | 7719.06 | 7452.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14118.80 | 08-JUN-20:00 | 8945.92 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14508.45 | 12-JUL-21:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15453.50 | 09-AUG-20:00 | 8945.92 | 11578.59 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17688.62 | 29-SEP-21:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19125.86 | 18-OCT-21:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37451.11 | 25-NOV-21:33 | 26837.75 | 27016.71 | 25550.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15902.16 | 01-DEC-22:00 | 10223.90 | 10292.08 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11745.10 | 3833.96 | 3216.28 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37451.11 | 115018.92 | 27016.71 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1863.44 | 12-JAN-12:40 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.22 |
February | 2545.98 | 08-FEB-13:20 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.37 |
March | 2069.33 | 25-MAR-14:25 | 779.69 | 344.37 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.00 |
April | 2858.76 | 15-APR-13:20 | 779.69 | 344.37 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 100.40 | 0.00 |
May | 2078.35 | 31-MAY-18:40 | 909.64 | 550.99 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 81.39 | 0.00 |
June | 2209.51 | 26-JUN-18:10 | 5457.82 | 3305.95 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.16 | 0.00 |
July | 2185.33 | 30-JUL-13:20 | 259.90 | 137.75 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
August | 2328.64 | 29-AUG-13:30 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
September | 3696.44 | 07-SEP-13:00 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 166.43 | 0.00 |
October | 3878.88 | 20-OCT-12:50 | 259.90 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 |
November | 3508.63 | 04-NOV-13:10 | 389.84 | 172.19 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.10 |
December | 2932.59 | 03-DEC-13:00 | 389.84 | 206.62 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1863.44 | 259.90 | 137.75 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3878.88 | 5457.82 | 3305.95 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 166.43 | 520.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2093.15 | 05-JAN-21:22 | 6019.20 | 3190.26 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.35 |
February | 1862.08 | 02-FEB-06:00 | 1354.32 | 159.51 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.58 |
March | 1259.86 | 25-MAR-15:00 | 451.44 | 199.39 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
April | 1547.06 | 15-APR-21:10 | 1053.36 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
May | 1582.63 | 31-MAY-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
June | 1630.43 | 30-JUN-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
July | 1620.45 | 03-JUL-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 0.00 |
August | 1610.10 | 22-AUG-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
September | 1660.36 | 07-SEP-21:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 |
October | 1434.38 | 20-OCT-15:50 | 752.40 | 199.39 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
November | 1780.69 | 25-NOV-21:33 | 3160.08 | 1674.88 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.01 |
December | 1066.50 | 05-DEC-22:10 | 1354.32 | 478.54 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1066.50 | 451.44 | 159.51 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2093.15 | 6019.20 | 3190.26 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 289.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 626.15 | 13-JAN-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.00 |
February | 644.76 | 24-FEB-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.78 |
March | 832.94 | 25-MAR-15:00 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 |
April | 1037.32 | 16-APR-20:00 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 0.00 |
May | 1067.75 | 31-MAY-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
June | 1123.29 | 30-JUN-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 |
July | 1114.30 | 03-JUL-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 | 0.00 |
August | 1107.71 | 03-AUG-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 |
September | 1111.29 | 07-SEP-21:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
October | 941.77 | 20-OCT-15:00 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 0.00 |
November | 840.37 | 08-NOV-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 |
December | 618.13 | 04-DEC-22:10 | 0.00 | 410.51 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 618.13 | 0.00 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1123.29 | 0.00 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 214.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 245.01 | 13-JAN-22:00 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.09 |
February | 325.48 | 24-FEB-22:00 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.51 |
March | 427.22 | 25-MAR-15:00 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
April | 555.61 | 16-APR-21:10 | 0.00 | 109.79 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
May | 570.25 | 31-MAY-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
June | 600.82 | 30-JUN-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
July | 597.11 | 03-JUL-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 0.00 |
August | 593.23 | 03-AUG-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 |
September | 594.73 | 07-SEP-21:10 | 0.00 | 131.75 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 517.00 | 20-OCT-15:00 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 0.00 |
November | 442.32 | 03-NOV-14:00 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 |
December | 237.01 | 03-DEC-13:00 | 0.00 | 65.87 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 237.01 | 0.00 | 54.90 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 600.82 | 0.00 | 175.67 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 143.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41074.57 | 05-JAN-21:33 | 3225.60 | 1040.27 | 17328.51 | 150542.82 | 0.00 | 0.00 | 0.00 | 0.00 | 788.10 |
February | 36261.29 | 24-FEB-21:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 345.48 |
March | 36756.96 | 28-MAR-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 187.70 |
April | 37704.54 | 18-APR-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 |
May | 37957.13 | 31-MAY-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.62 | 0.00 |
June | 38125.40 | 26-JUN-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
July | 37994.64 | 03-JUL-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.01 | 0.00 |
August | 38009.73 | 03-AUG-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
September | 38117.39 | 07-SEP-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
October | 37533.91 | 20-OCT-20:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 131.18 |
November | 39825.92 | 25-NOV-21:12 | 4233.60 | 1365.35 | 23104.68 | 200723.75 | 0.00 | 0.00 | 0.00 | 0.00 | 787.34 |
December | 35742.65 | 01-DEC-21:00 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 467.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35742.65 | 705.60 | 292.58 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41074.57 | 4233.60 | 1365.35 | 23104.68 | 200723.75 | 0.00 | 0.00 | 0.00 | 38.49 | 788.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8457.37 | 12-JAN-12:30 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1317.96 |
February | 10346.50 | 08-FEB-13:20 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.41 |
March | 9181.56 | 25-MAR-14:05 | 10245.60 | 518.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.21 |
April | 11392.05 | 15-APR-13:00 | 5122.80 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 233.81 | 0.00 |
May | 9900.71 | 31-MAY-21:20 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.46 |
June | 10252.38 | 26-JUN-21:20 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 69.89 | 0.00 |
July | 10163.72 | 25-JUL-21:30 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 110.30 | 0.00 |
August | 10135.61 | 02-AUG-21:30 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 0.00 |
September | 12780.17 | 16-SEP-13:10 | 10245.60 | 518.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 245.90 | 0.00 |
October | 13883.66 | 20-OCT-12:50 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 |
November | 14127.21 | 04-NOV-12:40 | 5122.80 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.22 |
December | 11999.32 | 03-DEC-12:50 | 5122.80 | 311.38 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8457.37 | 3415.20 | 259.48 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14127.21 | 15368.40 | 1020.92 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 245.90 | 1317.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 44641.54 | 05-JAN-21:22 | 202768.80 | 53733.85 | 47506.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6020.13 |
February | 41277.22 | 02-FEB-06:00 | 45622.98 | 2686.69 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6996.41 |
March | 28167.77 | 19-MAR-21:00 | 40553.76 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.46 |
April | 33361.23 | 16-APR-21:10 | 40553.76 | 6716.73 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 |
May | 34274.49 | 31-MAY-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.50 |
June | 35001.56 | 26-JUN-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 176.40 | 0.00 |
July | 34789.52 | 03-JUL-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 0.00 |
August | 34823.11 | 22-AUG-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.52 |
September | 36116.48 | 07-SEP-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 |
October | 32738.70 | 20-OCT-21:10 | 45622.98 | 8060.08 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.45 |
November | 49425.94 | 25-NOV-21:12 | 212907.24 | 56420.54 | 50673.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.91 |
December | 24306.48 | 04-DEC-23:10 | 45622.98 | 4030.04 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2471.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24306.48 | 40553.76 | 2686.69 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49425.94 | 212907.24 | 56420.54 | 50673.90 | 0.00 | 0.00 | 0.00 | 0.00 | 176.40 | 6996.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2900.40 | 12-JAN-16:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.54 |
February | 3056.41 | 24-FEB-16:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.74 |
March | 3187.00 | 25-MAR-15:01 | 378.00 | 101.88 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
April | 3285.24 | 16-APR-18:02 | 702.00 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
May | 3320.81 | 30-MAY-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 | 0.00 |
June | 3350.12 | 18-JUN-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 0.00 |
July | 3426.45 | 05-JUL-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 0.00 |
August | 3388.76 | 01-AUG-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 | 0.00 |
September | 3303.19 | 11-SEP-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
October | 3219.82 | 19-OCT-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
November | 3102.65 | 04-NOV-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
December | 2865.73 | 02-DEC-16:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2865.73 | 324.00 | 87.32 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3426.45 | 831.60 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 133.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 451.35 | 13-JAN-19:05 | 831.60 | 1239.86 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.59 |
February | 2899.34 | 24-FEB-16:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.94 |
March | 3115.06 | 25-MAR-15:01 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 |
April | 3312.05 | 15-APR-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 46.52 | 0.00 |
May | 3299.59 | 05-MAY-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 | 0.00 |
June | 3341.44 | 18-JUN-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 0.00 |
July | 3348.84 | 05-JUL-18:02 | 831.60 | 1239.86 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
August | 3328.96 | 05-AUG-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 | 0.00 |
September | 3270.77 | 16-SEP-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 | 0.00 |
October | 3124.79 | 19-OCT-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 2980.67 | 04-NOV-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.95 |
December | 495.72 | 14-DEC-16:04 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 |
Annual Sum or Average | |||||||||||
Minimum of Months | 451.35 | 324.00 | 87.31 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3348.84 | 831.60 | 1239.86 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 144.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 219.88 | 30-JAN-15:05 | 0.00 | 18.29 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.84 |
February | 259.71 | 02-FEB-15:03 | 0.00 | 27.44 | 201.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.70 |
March | 434.45 | 24-MAR-13:00 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 |
April | 545.39 | 15-APR-12:50 | 0.00 | 9.15 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
May | 346.18 | 05-MAY-13:05 | 0.00 | 18.29 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
June | 368.35 | 26-JUN-17:30 | 0.00 | 197.57 | 263.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 |
July | 370.31 | 30-JUL-13:05 | 0.00 | 18.29 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
August | 480.25 | 29-AUG-13:20 | 0.00 | 18.29 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
September | 632.74 | 07-SEP-12:50 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
October | 701.47 | 20-OCT-12:30 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 |
November | 684.21 | 04-NOV-12:30 | 0.00 | 9.15 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
December | 140.08 | 07-DEC-15:20 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 |
Annual Sum or Average | |||||||||||
Minimum of Months | 140.08 | 0.00 | 9.15 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 701.47 | 0.00 | 197.57 | 263.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 106.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 577.60 | 01-JAN-09:02 | 324.00 | 204.94 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 |
February | 833.67 | 25-FEB-09:02 | 270.00 | 170.78 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 |
March | 920.59 | 25-MAR-15:01 | 378.00 | 64.04 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
April | 1027.46 | 15-APR-18:02 | 702.00 | 878.32 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
May | 1019.52 | 31-MAY-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 0.00 |
June | 1025.60 | 26-JUN-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
July | 1014.04 | 02-JUL-18:02 | 702.00 | 878.32 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 0.00 |
August | 1025.48 | 09-AUG-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
September | 1017.86 | 07-SEP-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 0.00 |
October | 909.07 | 19-OCT-15:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
November | 864.25 | 04-NOV-18:01 | 819.00 | 1024.70 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 |
December | 654.98 | 03-DEC-09:02 | 324.00 | 204.94 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 577.60 | 270.00 | 64.04 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1027.46 | 831.60 | 1024.70 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 48.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 746.02 | 12-JAN-09:03 | 216.00 | 611.27 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 |
February | 2660.93 | 24-FEB-09:02 | 216.00 | 611.27 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.57 |
March | 2853.70 | 25-MAR-15:01 | 378.00 | 101.88 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 |
April | 3022.31 | 16-APR-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 | 0.00 |
May | 2994.76 | 31-MAY-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 0.00 |
June | 3051.99 | 27-JUN-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.90 | 0.00 |
July | 3035.22 | 29-JUL-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 0.00 |
August | 2994.22 | 18-AUG-15:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | 0.00 |
September | 3000.43 | 07-SEP-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 0.00 |
October | 2887.38 | 19-OCT-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
November | 2764.22 | 04-NOV-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 |
December | 2328.39 | 03-DEC-09:02 | 324.00 | 326.01 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 746.02 | 216.00 | 87.32 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3051.99 | 831.60 | 1240.00 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 50.90 | 180.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 455.23 | 13-JAN-09:05 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.99 |
February | 2537.62 | 24-FEB-09:02 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.04 |
March | 2691.86 | 28-MAR-08:62 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.45 |
April | 2962.29 | 15-APR-18:02 | 702.00 | 1397.02 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 0.00 |
May | 3010.11 | 31-MAY-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 | 0.00 |
June | 3026.10 | 28-JUN-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 | 0.00 |
July | 2992.66 | 02-JUL-18:02 | 702.00 | 1397.02 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 35.81 | 0.00 |
August | 3008.35 | 09-AUG-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 30.40 | 0.00 |
September | 3013.85 | 08-SEP-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 0.00 |
October | 2674.06 | 21-OCT-15:01 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 |
November | 2158.45 | 04-NOV-08:62 | 270.00 | 271.64 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.28 |
December | 514.83 | 05-DEC-09:03 | 216.00 | 611.20 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 455.23 | 216.00 | 101.87 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3026.10 | 702.00 | 1397.02 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 199.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1374.54 | 31-JAN-04:00 | 0.00 | 248.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.00 |
February | 1741.08 | 02-FEB-06:10 | 0.00 | 4979.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.79 |
March | 1519.16 | 25-MAR-15:00 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
April | 1753.29 | 18-APR-18:50 | 0.00 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
May | 1756.05 | 31-MAY-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 | 0.00 |
June | 1844.47 | 30-JUN-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 | 0.00 |
July | 1832.68 | 03-JUL-19:20 | 0.00 | 2240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 | 0.00 |
August | 1786.58 | 04-AUG-15:13 | 0.00 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 | 0.00 |
September | 1813.17 | 08-SEP-14:00 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.60 | 0.00 |
October | 1703.67 | 20-OCT-14:40 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | 0.00 |
November | 1426.43 | 03-NOV-14:00 | 0.00 | 622.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 |
December | 1091.55 | 03-DEC-13:00 | 0.00 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1091.55 | 0.00 | 248.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1844.47 | 0.00 | 4979.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 | 524.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2969.41 | 12-JAN-16:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.78 |
February | 3172.49 | 24-FEB-16:02 | 583.20 | 111.77 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.10 |
March | 3297.37 | 25-MAR-15:01 | 378.00 | 101.88 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 |
April | 3384.17 | 16-APR-18:02 | 702.00 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 0.00 |
May | 3392.64 | 30-MAY-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 0.00 |
June | 3576.68 | 25-JUN-18:02 | 702.00 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 0.00 |
July | 3527.48 | 02-JUL-18:02 | 702.00 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 | 0.00 |
August | 3400.06 | 22-AUG-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
September | 3379.66 | 11-SEP-18:02 | 831.60 | 1240.00 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 0.00 |
October | 3340.65 | 19-OCT-15:01 | 680.40 | 130.40 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 |
November | 3225.04 | 04-NOV-15:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 |
December | 2919.62 | 02-DEC-16:02 | 324.00 | 87.32 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2919.62 | 324.00 | 87.32 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3576.68 | 831.60 | 1397.19 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 132.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 718.64 | 12-JAN-16:03 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.95 |
February | 2916.82 | 24-FEB-16:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.78 |
March | 3212.37 | 25-MAR-15:01 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 |
April | 3333.75 | 18-APR-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
May | 3366.07 | 04-MAY-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 0.00 |
June | 3525.53 | 25-JUN-18:02 | 702.00 | 1397.02 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 0.00 |
July | 3478.04 | 26-JUL-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 | 0.00 |
August | 3438.30 | 13-AUG-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 0.00 |
September | 3402.94 | 11-SEP-15:02 | 583.20 | 111.76 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 36.39 | 0.00 |
October | 3227.40 | 19-OCT-15:01 | 680.40 | 130.39 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 |
November | 3072.44 | 04-NOV-15:02 | 324.00 | 87.31 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 |
December | 638.04 | 03-DEC-16:04 | 378.00 | 101.87 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.20 |
Annual Sum or Average | |||||||||||
Minimum of Months | 638.04 | 324.00 | 87.31 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3525.53 | 702.00 | 1397.02 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 128.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1607.21 | 30-JAN-16:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.58 |
February | 1541.24 | 01-FEB-16:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.95 |
March | 1474.23 | 24-MAR-15:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 |
April | 1594.09 | 15-APR-15:02 | 324.00 | 54.89 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
May | 1556.16 | 31-MAY-18:02 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 | 0.00 |
June | 1585.69 | 10-JUN-15:02 | 324.00 | 54.89 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 0.00 |
July | 1576.66 | 17-JUL-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
August | 1601.53 | 22-AUG-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
September | 1598.57 | 06-SEP-15:02 | 583.20 | 70.27 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 0.00 |
October | 1538.85 | 19-OCT-15:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 |
November | 1500.68 | 04-NOV-15:02 | 324.00 | 54.89 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 |
December | 1451.70 | 05-DEC-16:01 | 680.40 | 81.98 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1451.70 | 324.00 | 54.89 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1607.21 | 831.60 | 779.51 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 191.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33689.24 | 19-JAN-01:51 | 269887.68 | 4482.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.67 |
February | 21879.03 | 02-FEB-06:00 | 26988.77 | 597.61 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.25 |
March | 18133.38 | 28-MAR-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.06 |
April | 19908.24 | 18-APR-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
May | 21109.85 | 31-MAY-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 |
June | 21992.70 | 26-JUN-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 | 0.00 |
July | 21746.44 | 03-JUL-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
August | 21375.33 | 03-AUG-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
September | 20967.88 | 07-SEP-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 |
October | 18552.39 | 20-OCT-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.01 |
November | 24001.80 | 25-NOV-21:12 | 125947.58 | 12549.74 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.81 |
December | 15994.65 | 04-DEC-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15994.65 | 26988.77 | 597.61 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33689.24 | 269887.68 | 12549.74 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 | 1003.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35707.00 | 19-JAN-01:51 | 269887.68 | 4482.05 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.75 |
February | 22816.89 | 02-FEB-06:00 | 26988.77 | 597.61 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.69 |
March | 20141.91 | 28-MAR-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.11 |
April | 21621.39 | 18-APR-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 |
May | 22748.56 | 31-MAY-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 |
June | 23472.80 | 26-JUN-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 | 0.00 |
July | 23161.07 | 03-JUL-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
August | 22913.64 | 03-AUG-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
September | 22489.32 | 07-SEP-21:10 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 |
October | 20449.19 | 02-OCT-22:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.19 |
November | 25698.10 | 25-NOV-21:12 | 125947.58 | 12549.74 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.00 |
December | 18008.19 | 04-DEC-23:00 | 26988.77 | 1792.82 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18008.19 | 26988.77 | 597.61 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35707.00 | 269887.68 | 12549.74 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 | 997.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28344.71 | 29-JAN-19:33 | 6404.54 | 2970.27 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 775.28 |
February | 26011.20 | 24-FEB-11:50 | 533.71 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 288.82 |
March | 27768.86 | 19-MAR-10:50 | 800.57 | 318.24 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 153.19 |
April | 29927.92 | 18-APR-10:40 | 1067.42 | 530.40 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 31.31 | 0.00 |
May | 30172.21 | 29-MAY-10:40 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
June | 30553.76 | 11-JUN-10:40 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 77.30 | 0.00 |
July | 30586.11 | 29-JUL-10:40 | 1601.14 | 530.40 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 26.10 | 0.00 |
August | 30137.00 | 27-AUG-10:40 | 1601.14 | 636.49 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 |
September | 30338.39 | 08-SEP-10:40 | 1067.42 | 530.40 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 59.62 | 0.00 |
October | 28491.62 | 20-OCT-10:50 | 533.71 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.80 |
November | 27989.70 | 25-NOV-21:12 | 11207.95 | 4455.40 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 791.07 |
December | 25764.66 | 03-DEC-11:50 | 800.57 | 318.24 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 306.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25764.66 | 533.71 | 265.20 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30586.11 | 11207.95 | 4455.40 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 77.30 | 791.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2195.87 | 12-JAN-12:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.65 |
February | 2456.08 | 24-FEB-14:20 | 0.00 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.23 |
March | 3240.95 | 19-MAR-14:00 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 |
April | 3911.45 | 18-APR-13:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 0.00 |
May | 4029.42 | 31-MAY-18:02 | 0.00 | 12648.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.31 | 0.00 |
June | 4313.93 | 30-JUN-15:15 | 0.00 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 | 0.00 |
July | 4271.30 | 03-JUL-18:20 | 0.00 | 4216.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.03 | 0.00 |
August | 4281.98 | 04-AUG-15:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.11 | 0.00 |
September | 4298.77 | 07-SEP-13:50 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.70 | 0.00 |
October | 3700.02 | 20-OCT-13:50 | 0.00 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 0.00 |
November | 3136.60 | 03-NOV-14:00 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.03 |
December | 2343.62 | 03-DEC-13:20 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2195.87 | 0.00 | 527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4313.93 | 0.00 | 12648.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.11 | 285.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.407002E+12 | 264966.67 | 12-JAN-20:10 | 0.964822E+12 | 949076.04 | 30-JAN-19:30 |
February | 0.366165E+12 | 266527.87 | 24-FEB-20:19 | 0.753375E+12 | 983401.64 | 02-FEB-20:00 |
March | 0.405420E+12 | 275898.72 | 24-MAR-19:10 | 0.532352E+12 | 496917.04 | 05-MAR-19:10 |
April | 0.415066E+12 | 379686.69 | 16-APR-19:10 | 0.432644E+12 | 403977.26 | 26-APR-17:30 |
May | 0.462502E+12 | 381941.75 | 31-MAY-19:40 | 0.401468E+12 | 386736.95 | 02-MAY-18:19 |
June | 0.541301E+12 | 410847.98 | 26-JUN-19:00 | 0.362153E+12 | 393641.27 | 01-JUN-17:40 |
July | 0.609995E+12 | 436930.12 | 26-JUL-19:10 | 0.345533E+12 | 279618.22 | 03-JUL-17:19 |
August | 0.586912E+12 | 427918.70 | 03-AUG-19:30 | 0.346708E+12 | 304839.86 | 06-AUG-21:00 |
September | 0.475511E+12 | 383076.25 | 07-SEP-19:10 | 0.370178E+12 | 403919.39 | 27-SEP-17:00 |
October | 0.418203E+12 | 288214.57 | 20-OCT-19:30 | 0.415359E+12 | 406042.20 | 30-OCT-17:49 |
November | 0.393535E+12 | 279925.11 | 03-NOV-19:10 | 0.562434E+12 | 876203.88 | 25-NOV-21:40 |
December | 0.405763E+12 | 263185.32 | 11-DEC-20:49 | 0.714265E+12 | 594582.94 | 11-DEC-17:19 |
Annual Sum or Average | 0.548738E+13 | 0.620129E+13 | ||||
Minimum of Months | 0.366165E+12 | 263185.32 | 0.345533E+12 | 279618.22 | ||
Maximum of Months | 0.609995E+12 | 436930.12 | 0.964822E+12 | 983401.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.699115E+11 | 0.172317E+11 | 0.148212E+12 | 0.826626E+11 | 0.473968E+11 | 0.204971E+10 | 0.00 | 0.351312E+09 | 0.00 | 0.00 | 0.264939E+11 | 0.770840E+10 | 0.00 |
February | 0.630319E+11 | 0.143576E+11 | 0.133859E+12 | 0.746630E+11 | 0.418518E+11 | 0.229135E+10 | 0.00 | 0.749055E+09 | 0.00 | 0.00 | 0.239299E+11 | 0.696684E+10 | 0.00 |
March | 0.696627E+11 | 0.142267E+11 | 0.148234E+12 | 0.826646E+11 | 0.450470E+11 | 0.319406E+10 | 0.00 | 0.579997E+10 | 0.00 | 0.00 | 0.237060E+11 | 0.770506E+10 | 0.00 |
April | 0.671008E+11 | 0.120572E+11 | 0.143397E+12 | 0.799956E+11 | 0.441680E+11 | 0.498102E+10 | 0.00 | 0.323459E+11 | 0.00 | 0.00 | 0.185143E+11 | 0.746535E+10 | 0.00 |
May | 0.691820E+11 | 0.109662E+11 | 0.148223E+12 | 0.826632E+11 | 0.463320E+11 | 0.786868E+10 | 0.00 | 0.764902E+11 | 0.00 | 0.00 | 0.779743E+10 | 0.770496E+10 | 0.00 |
June | 0.669075E+11 | 0.986270E+10 | 0.143446E+12 | 0.799974E+11 | 0.454388E+11 | 0.838960E+10 | 0.00 | 0.164834E+12 | 0.00 | 0.00 | 0.984244E+10 | 0.745781E+10 | 0.00 |
July | 0.690267E+11 | 0.105111E+11 | 0.148174E+12 | 0.826611E+11 | 0.466159E+11 | 0.921414E+10 | 0.00 | 0.220739E+12 | 0.00 | 0.00 | 0.100669E+11 | 0.771360E+10 | 0.00 |
August | 0.693285E+11 | 0.118016E+11 | 0.148234E+12 | 0.826644E+11 | 0.465663E+11 | 0.896009E+10 | 0.00 | 0.197010E+12 | 0.00 | 0.00 | 0.934196E+10 | 0.770524E+10 | 0.00 |
September | 0.672153E+11 | 0.130048E+11 | 0.143397E+12 | 0.799957E+11 | 0.451557E+11 | 0.758243E+10 | 0.00 | 0.963869E+11 | 0.00 | 0.00 | 0.102123E+11 | 0.746574E+10 | 0.00 |
October | 0.697385E+11 | 0.152055E+11 | 0.148212E+12 | 0.826625E+11 | 0.465333E+11 | 0.594999E+10 | 0.00 | 0.190198E+11 | 0.00 | 0.00 | 0.179579E+11 | 0.770477E+10 | 0.00 |
November | 0.676748E+11 | 0.162404E+11 | 0.143462E+12 | 0.799966E+11 | 0.443879E+11 | 0.308160E+10 | 0.00 | 0.525305E+10 | 0.00 | 0.00 | 0.210002E+11 | 0.744989E+10 | 0.00 |
December | 0.698877E+11 | 0.176494E+11 | 0.148174E+12 | 0.826617E+11 | 0.460785E+11 | 0.133270E+10 | 0.00 | 0.637701E+09 | 0.00 | 0.00 | 0.264939E+11 | 0.771364E+10 | 0.00 |
Annual Sum or Average | 0.818668E+12 | 0.163115E+12 | 0.174502E+13 | 0.973288E+12 | 0.545572E+12 | 0.648954E+11 | 0.00 | 0.819617E+12 | 0.205357E+12 | 0.907613E+11 | |||
Minimum of Months | 0.630319E+11 | 0.986270E+10 | 0.133859E+12 | 0.746630E+11 | 0.418518E+11 | 0.133270E+10 | 0.00 | 0.351312E+09 | 0.00 | 0.00 | 0.779743E+10 | 0.696684E+10 | 0.00 |
Maximum of Months | 0.699115E+11 | 0.176494E+11 | 0.148234E+12 | 0.826646E+11 | 0.473968E+11 | 0.921414E+10 | 0.00 | 0.220739E+12 | 0.00 | 0.00 | 0.264939E+11 | 0.771364E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.608091E+12 | 0.00 | 0.204813E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.428569E+12 | 0.00 | 0.187602E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.173412E+12 | 0.00 | 0.206901E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.903015E+11 | 0.00 | 0.195387E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.544040E+11 | 0.00 | 0.195086E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.330781E+11 | 0.00 | 0.181961E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.114133E+11 | 0.00 | 0.182300E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.148240E+11 | 0.00 | 0.179845E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.480569E+11 | 0.00 | 0.175165E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.778578E+11 | 0.00 | 0.185583E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.229562E+12 | 0.00 | 0.185781E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.362983E+12 | 0.00 | 0.199462E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.213255E+13 | 0.227989E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.114133E+11 | 0.00 | 0.175165E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.608091E+12 | 0.00 | 0.206901E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 73068.04 | 02-JAN-20:10 | 10390.54 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 62600.61 | 02-JAN-07:19 | 26219.19 | 05-JAN-19:10 | 5674.44 | 30-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 73068.04 | 01-FEB-20:10 | 10390.54 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 62600.61 | 01-FEB-07:19 | 24522.91 | 28-FEB-19:10 | 3870.98 | 01-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 73068.04 | 01-MAR-20:10 | 10390.54 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 62600.61 | 13-MAR-06:19 | 25914.51 | 24-MAR-18:10 | 3063.88 | 19-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 73068.04 | 03-APR-19:10 | 10390.54 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 62600.52 | 14-APR-06:19 | 27611.82 | 19-APR-18:10 | 4039.94 | 16-APR-20:30 | 0.00 | 01-APR-00:10 |
May | 73068.04 | 01-MAY-19:10 | 10390.54 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 62599.55 | 10-MAY-06:19 | 27048.92 | 22-MAY-20:40 | 4053.71 | 05-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 73068.04 | 01-JUN-19:10 | 10390.54 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 62599.82 | 13-JUN-06:19 | 26716.40 | 01-JUN-18:10 | 4369.26 | 11-JUN-19:40 | 0.00 | 01-JUN-00:10 |
July | 73068.04 | 03-JUL-19:30 | 10390.54 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 62599.55 | 20-JUL-06:19 | 27115.68 | 05-JUL-18:30 | 5209.20 | 03-JUL-21:00 | 0.00 | 01-JUL-00:10 |
August | 73068.04 | 01-AUG-19:30 | 10390.54 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 62599.72 | 25-AUG-06:19 | 26113.04 | 02-AUG-19:10 | 5115.79 | 28-AUG-19:19 | 0.00 | 01-AUG-00:10 |
September | 73068.04 | 01-SEP-19:10 | 10390.54 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 62600.61 | 21-SEP-06:19 | 27880.03 | 25-SEP-20:00 | 4109.91 | 11-SEP-19:19 | 0.00 | 01-SEP-00:10 |
October | 73068.04 | 02-OCT-19:10 | 10390.54 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 62600.61 | 02-OCT-06:19 | 28743.36 | 24-OCT-20:00 | 3395.79 | 11-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 73068.04 | 01-NOV-19:10 | 10390.54 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 62600.61 | 01-NOV-06:19 | 28422.46 | 03-NOV-20:10 | 3083.67 | 25-NOV-10:50 | 0.00 | 01-NOV-00:10 |
December | 73068.04 | 01-DEC-20:10 | 10390.54 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 62600.61 | 01-DEC-07:19 | 26719.28 | 11-DEC-19:19 | 3068.91 | 10-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 73068.04 | 10390.54 | 89475.41 | 62599.55 | 24522.91 | 3063.88 | 0.00 | |||||||
Maximum of Months | 73068.04 | 10390.54 | 89475.41 | 62600.61 | 28743.36 | 5674.44 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3873.07 | 12-JAN-16:10 | 0.00 | 0.00 | 10206.30 | 01-JAN-09:09 | 4745.36 | 30-JAN-07:30 | 0.00 |
February | 7933.23 | 08-FEB-16:10 | 0.00 | 0.00 | 10206.30 | 01-FEB-16:10 | 4750.74 | 02-FEB-07:19 | 0.00 |
March | 56984.34 | 25-MAR-15:09 | 0.00 | 0.00 | 10206.30 | 01-MAR-09:09 | 4738.28 | 09-MAR-07:19 | 0.00 |
April | 131121.38 | 16-APR-15:30 | 0.00 | 0.00 | 10206.30 | 01-APR-08:09 | 4738.27 | 27-APR-18:10 | 0.00 |
May | 126685.66 | 31-MAY-15:09 | 0.00 | 0.00 | 10206.30 | 01-MAY-08:09 | 4738.72 | 30-MAY-18:10 | 0.00 |
June | 185688.18 | 11-JUN-15:09 | 0.00 | 0.00 | 10206.30 | 01-JUN-18:10 | 4738.59 | 07-JUN-18:10 | 0.00 |
July | 191583.45 | 26-JUL-18:10 | 0.00 | 0.00 | 10206.30 | 01-JUL-15:09 | 4738.50 | 24-JUL-18:10 | 0.00 |
August | 206788.95 | 04-AUG-15:20 | 0.00 | 0.00 | 10206.30 | 01-AUG-15:09 | 4738.71 | 07-AUG-18:10 | 0.00 |
September | 149901.39 | 06-SEP-15:09 | 0.00 | 0.00 | 10206.30 | 01-SEP-15:09 | 4738.74 | 11-SEP-18:10 | 0.00 |
October | 90077.89 | 20-OCT-15:09 | 0.00 | 0.00 | 10206.30 | 15-OCT-15:09 | 4738.59 | 20-OCT-18:10 | 0.00 |
November | 42211.79 | 03-NOV-15:09 | 0.00 | 0.00 | 10206.30 | 03-NOV-18:10 | 4738.56 | 24-NOV-19:10 | 0.00 |
December | 5756.68 | 07-DEC-14:30 | 0.00 | 0.00 | 10206.30 | 01-DEC-09:09 | 4738.51 | 20-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 3873.07 | 0.00 | 0.00 | 10206.30 | 4738.27 | 0.00 | |||
Maximum of Months | 206788.95 | 0.00 | 0.00 | 10206.30 | 4750.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 264966.67 | 12-JAN-20:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 21983.76 | 2853.95 | 0.00 | 1043.69 | 0.00 |
February | 266527.87 | 24-FEB-20:19 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 22579.10 | 2854.11 | 0.00 | 2448.24 | 0.00 |
March | 275898.72 | 24-MAR-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 24318.87 | 2887.67 | 0.00 | 10233.86 | 0.00 |
April | 379686.69 | 16-APR-19:10 | 68033.42 | 87285.99 | 10390.54 | 50307.10 | 24111.87 | 3865.98 | 0.00 | 120022.90 | 0.00 |
May | 381941.75 | 31-MAY-19:40 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 24887.18 | 3792.49 | 0.00 | 114031.69 | 0.00 |
June | 410847.98 | 26-JUN-19:00 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 25921.39 | 4189.36 | 0.00 | 141893.41 | 0.00 |
July | 436930.12 | 26-JUL-19:10 | 71869.73 | 88772.42 | 0.00 | 50342.67 | 23808.41 | 5055.34 | 0.00 | 180711.14 | 0.00 |
August | 427918.70 | 03-AUG-19:30 | 73068.04 | 88772.42 | 10390.54 | 50350.88 | 25126.59 | 4674.12 | 0.00 | 158979.73 | 0.00 |
September | 383076.25 | 07-SEP-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 24183.82 | 3801.73 | 0.00 | 116273.29 | 0.00 |
October | 288214.57 | 20-OCT-19:30 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 23524.26 | 3003.28 | 0.00 | 33340.50 | 0.00 |
November | 279925.11 | 03-NOV-19:10 | 73068.04 | 88772.42 | 10390.54 | 50344.37 | 26149.18 | 2902.33 | 0.00 | 12189.01 | 0.00 |
December | 263185.32 | 11-DEC-20:49 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 23570.42 | 475.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 263185.32 | 68033.42 | 87285.99 | 0.00 | 50307.10 | 21983.76 | 475.55 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 436930.12 | 73068.04 | 88772.42 | 10390.54 | 50351.36 | 26149.18 | 5055.34 | 0.00 | 180711.14 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 724553.37 | 31-JAN-04:10 | 0.00 | 180063.92 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 762309.68 | 02-FEB-05:00 | 0.00 | 180194.64 | 17-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 238244.31 | 05-MAR-19:10 | 0.00 | 180159.46 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 179675.47 | 03-APR-08:09 | 0.00 | 179528.09 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 144600.65 | 17-MAY-06:00 | 0.00 | 178524.72 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 141695.38 | 01-JUN-06:19 | 0.00 | 177255.10 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 116660.58 | 24-JUL-03:09 | 0.00 | 176116.90 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 127621.56 | 07-AUG-01:30 | 0.00 | 175492.88 | 02-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 141566.03 | 29-SEP-15:09 | 0.00 | 175846.55 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 145900.93 | 05-OCT-12:00 | 0.00 | 176843.77 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 693860.13 | 26-NOV-06:00 | 0.00 | 178066.93 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 351359.97 | 11-DEC-16:19 | 0.00 | 179192.59 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 116660.58 | 0.00 | 175492.88 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 762309.68 | 0.00 | 180194.64 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.33 | 19.04 | 64.33 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 139.33 | 15.82 | 139.33 | 15.82 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 203.67 | 16.83 | 203.67 | 16.83 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.33 | 19.04 | 139.33 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.67 | 16.34 | 81.67 | 16.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99.67 | 14.36 | 99.67 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 16.81 | 12.00 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.17 | 20.34 | 13.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.50 | 15.67 | 206.50 | 15.67 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.67 | 20.34 | 99.67 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.67 | 17.43 | 89.67 | 17.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 14.17 | 103.33 | 14.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.83 | 18.39 | 11.83 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.83 | 15.84 | 204.83 | 15.84 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.33 | 18.39 | 103.33 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 107.83 | 18.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 143.50 | 15.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.00 | 16.98 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.50 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 148.17 | 18.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 150.83 | 15.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20.50 | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.50 | 17.13 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.83 | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.67 | 9.62 | 69.67 | 9.62 | 1.67 | 24.62 | 1.67 | 24.62 |
February | 73.50 | 6.01 | 73.50 | 6.01 | 5.83 | 24.62 | 5.83 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 24.64 | 13.50 | 24.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 24.66 | 14.83 | 24.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.65 | 5.50 | 24.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.67 | 0.83 | 24.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.67 | 9.33 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 24.68 | 18.50 | 24.68 |
November | 8.33 | 10.93 | 8.33 | 10.93 | 9.83 | 24.64 | 9.83 | 24.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.60 | 3.33 | 24.60 |
Annual Sum or Average | 151.50 | 7.94 | 151.50 | 7.94 | 83.17 | 24.65 | 83.17 | 24.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.50 | 10.93 | 73.50 | 10.93 | 18.50 | 24.68 | 18.50 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.00 | 16.95 | 80.00 | 16.95 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.33 | 14.00 | 83.33 | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 17.52 | 11.67 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.00 | 15.58 | 175.00 | 15.58 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.33 | 17.52 | 83.33 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.17 | 17.32 | 81.17 | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91.33 | 13.83 | 91.33 | 13.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.50 | 18.39 | 11.50 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.00 | 15.65 | 184.00 | 15.65 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.33 | 18.39 | 91.33 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.36 | 2.00 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29.17 | 19.94 | 29.17 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.44 | 1.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.50 | 19.98 | 32.50 | 19.98 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.17 | 20.54 | 29.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.83 | 20.36 | 10.83 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46.50 | 19.64 | 46.50 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.46 | 2.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.00 | 19.81 | 60.00 | 19.81 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.50 | 20.51 | 46.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.50 | 20.09 | 28.50 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62.17 | 19.29 | 62.17 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.69 | 2.00 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.71 | 3.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.72 | 2.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.68 | 0.67 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.37 | 1.33 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 20.34 | 3.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.50 | 19.58 | 95.50 | 19.58 | 9.33 | 21.71 | 9.33 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.17 | 20.37 | 62.17 | 20.37 | 3.33 | 21.77 | 3.33 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 20.40 | 7.83 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41.00 | 19.68 | 41.00 | 19.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 20.43 | 1.83 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.83 | 19.82 | 50.83 | 19.82 | 0.33 | 21.78 | 0.33 | 21.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.00 | 20.49 | 41.00 | 20.49 | 0.33 | 21.78 | 0.33 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 20.20 | 15.00 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55.00 | 19.33 | 55.00 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.48 | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.41 | 2.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.83 | 19.56 | 72.83 | 19.56 | 0.33 | 21.76 | 0.33 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.00 | 20.48 | 55.00 | 20.48 | 0.33 | 21.76 | 0.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.50 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 153.33 | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.67 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 279.50 | 18.17 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.33 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.41 | 4.17 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25.33 | 19.97 | 25.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.42 | 2.00 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.67 | 20.06 | 31.67 | 20.06 | 1.33 | 21.72 | 1.33 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.33 | 20.49 | 25.33 | 20.49 | 0.67 | 21.74 | 0.67 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 20.26 | 15.00 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47.83 | 19.71 | 47.83 | 19.71 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.38 | 2.67 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.00 | 19.87 | 66.00 | 19.87 | 0.50 | 21.69 | 0.50 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.83 | 20.47 | 47.83 | 20.47 | 0.33 | 21.74 | 0.33 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.42 | 4.00 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17.83 | 20.16 | 17.83 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.84 | 3.17 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.99 | 2.50 | 21.99 |
November | 0.17 | 20.46 | 0.17 | 20.46 | 1.33 | 22.02 | 1.33 | 22.02 |
December | 2.67 | 20.40 | 2.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.67 | 20.23 | 24.67 | 20.23 | 9.67 | 21.88 | 9.67 | 21.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 20.46 | 17.83 | 20.46 | 3.17 | 22.02 | 3.17 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.00 | 16.37 | 54.00 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85.33 | 13.45 | 85.33 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.17 | 18.01 | 8.17 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.50 | 14.77 | 147.50 | 14.77 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.33 | 18.01 | 85.33 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.67 | 16.22 | 51.67 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84.33 | 13.29 | 84.33 | 13.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.33 | 17.94 | 7.33 | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.33 | 14.58 | 143.33 | 14.58 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.33 | 17.94 | 84.33 | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.50 | 12.52 | 53.50 | 12.52 | 1.50 | 24.69 | 1.50 | 24.69 |
February | 69.67 | 9.80 | 69.67 | 9.80 | 7.00 | 24.72 | 7.00 | 24.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 24.73 | 30.17 | 24.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 24.75 | 40.83 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 24.74 | 11.00 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.75 | 3.83 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 24.74 | 18.00 | 24.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 24.73 | 44.67 | 24.73 |
November | 9.00 | 12.97 | 9.00 | 12.97 | 17.00 | 24.70 | 17.00 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.69 | 3.33 | 24.69 |
Annual Sum or Average | 132.17 | 11.12 | 132.17 | 11.12 | 177.33 | 24.73 | 177.33 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.67 | 12.97 | 69.67 | 12.97 | 44.67 | 24.75 | 44.67 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.17 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 133.50 | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.50 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.17 | 16.47 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.50 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.06 | 108.17 | 19.78 | 108.17 | 19.78 |
February | 672.00 | 20.74 | 161.83 | 16.51 | 161.83 | 16.51 |
March | 744.00 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.30 | 14.83 | 21.01 | 14.83 | 21.01 |
May | 744.00 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.39 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.49 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 698.17 | 23.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 620.50 | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 606.00 | 23.59 | 1.33 | 23.99 | 0.00 | 0.00 |
December | 744.00 | 23.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8500.67 | 22.14 | 286.17 | 18.01 | 284.83 | 17.99 |
Minimum of Months | 606.00 | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.75 | 161.83 | 23.99 | 161.83 | 21.01 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.00 | 20.54 | 625.00 | 20.39 | 625.00 | 20.39 |
February | 658.00 | 20.06 | 437.67 | 19.53 | 431.17 | 19.47 |
March | 730.50 | 21.15 | 294.17 | 21.02 | 292.17 | 21.00 |
April | 689.50 | 21.23 | 143.33 | 21.29 | 127.67 | 21.00 |
May | 743.00 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 669.00 | 21.41 | 5.83 | 23.21 | 0.00 | 0.00 |
July | 699.33 | 21.53 | 3.83 | 23.16 | 0.00 | 0.00 |
August | 661.67 | 21.57 | 29.17 | 23.39 | 0.00 | 0.00 |
September | 599.83 | 21.44 | 81.83 | 23.59 | 5.33 | 21.00 |
October | 670.83 | 21.25 | 59.17 | 23.11 | 17.00 | 21.00 |
November | 698.00 | 21.02 | 339.67 | 20.95 | 328.17 | 20.85 |
December | 731.33 | 21.08 | 592.00 | 20.99 | 589.17 | 20.97 |
Annual Sum or Average | 8292.00 | 21.12 | 2611.67 | 20.78 | 2415.67 | 20.54 |
Minimum of Months | 599.83 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 743.00 | 21.57 | 625.00 | 23.59 | 625.00 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 306.00 | 19.95 | 306.00 | 19.95 |
February | 672.00 | 20.35 | 159.17 | 16.55 | 159.17 | 16.55 |
March | 744.00 | 21.75 | 0.17 | 21.00 | 0.17 | 21.00 |
April | 717.17 | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 742.00 | 22.22 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 698.50 | 22.25 | 0.67 | 23.67 | 0.00 | 0.00 |
July | 717.00 | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 684.83 | 22.31 | 1.83 | 23.65 | 0.00 | 0.00 |
September | 686.33 | 22.46 | 9.00 | 23.79 | 0.00 | 0.00 |
October | 742.17 | 22.41 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.75 | 59.83 | 20.48 | 59.83 | 20.48 |
December | 744.00 | 21.37 | 115.33 | 21.00 | 115.33 | 21.00 |
Annual Sum or Average | 8612.00 | 21.83 | 652.00 | 19.42 | 640.50 | 19.34 |
Minimum of Months | 672.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.46 | 306.00 | 23.79 | 306.00 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.17 | 20.00 | 354.83 | 20.77 | 182.67 | 18.23 |
February | 340.83 | 18.59 | 371.83 | 19.84 | 186.17 | 16.34 |
March | 277.17 | 22.74 | 393.67 | 23.59 | 146.00 | 24.17 |
April | 273.33 | 22.94 | 442.50 | 23.26 | 167.83 | 24.10 |
May | 272.50 | 23.21 | 522.00 | 22.84 | 202.17 | 23.97 |
June | 226.83 | 23.39 | 527.67 | 22.49 | 186.83 | 23.90 |
July | 189.83 | 23.56 | 567.50 | 22.25 | 169.67 | 23.87 |
August | 213.67 | 23.49 | 561.50 | 22.34 | 185.67 | 23.86 |
September | 249.50 | 23.25 | 487.67 | 22.81 | 186.50 | 24.00 |
October | 277.50 | 23.05 | 466.17 | 23.40 | 179.00 | 24.14 |
November | 314.83 | 22.30 | 403.50 | 23.16 | 161.33 | 23.33 |
December | 339.33 | 22.35 | 330.00 | 23.72 | 123.50 | 24.14 |
Annual Sum or Average | 3415.50 | 22.15 | 5428.83 | 22.56 | 2077.33 | 22.76 |
Minimum of Months | 189.83 | 18.59 | 330.00 | 19.84 | 123.50 | 16.34 |
Maximum of Months | 440.17 | 23.56 | 567.50 | 23.72 | 202.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.00 | 20.69 | 407.67 | 20.22 | 406.33 | 20.20 |
February | 648.50 | 20.46 | 224.67 | 18.57 | 212.00 | 18.25 |
March | 707.83 | 21.68 | 78.33 | 21.35 | 68.17 | 21.00 |
April | 619.83 | 21.90 | 51.33 | 23.02 | 6.00 | 21.00 |
May | 690.83 | 22.18 | 52.17 | 23.08 | 42.00 | 23.02 |
June | 510.00 | 22.14 | 140.33 | 23.23 | 50.83 | 23.06 |
July | 519.50 | 22.21 | 224.50 | 23.14 | 119.33 | 23.09 |
August | 483.83 | 22.36 | 285.67 | 23.22 | 135.33 | 23.26 |
September | 461.50 | 22.34 | 208.33 | 23.51 | 35.00 | 23.48 |
October | 602.67 | 22.18 | 79.67 | 23.91 | 0.00 | 0.00 |
November | 678.33 | 21.52 | 130.83 | 21.20 | 108.33 | 20.63 |
December | 715.67 | 21.27 | 275.33 | 21.11 | 265.83 | 21.00 |
Annual Sum or Average | 7368.50 | 21.68 | 2158.83 | 21.75 | 1449.17 | 20.92 |
Minimum of Months | 461.50 | 20.46 | 51.33 | 18.57 | 0.00 | 0.00 |
Maximum of Months | 730.00 | 22.36 | 407.67 | 23.91 | 406.33 | 23.48 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 186.17 | 19.39 | 186.17 | 19.39 |
February | 672.00 | 20.78 | 138.33 | 16.26 | 138.33 | 16.26 |
March | 735.17 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 672.67 | 22.38 | 4.00 | 23.79 | 0.00 | 0.00 |
May | 655.50 | 22.46 | 42.33 | 23.33 | 26.33 | 23.16 |
June | 547.00 | 22.32 | 54.17 | 23.53 | 6.17 | 23.02 |
July | 563.50 | 22.27 | 81.83 | 23.39 | 26.67 | 23.11 |
August | 507.67 | 22.31 | 131.33 | 23.52 | 44.83 | 23.28 |
September | 540.50 | 22.63 | 67.50 | 23.60 | 12.83 | 23.38 |
October | 675.33 | 22.76 | 2.67 | 23.97 | 0.00 | 0.00 |
November | 682.17 | 22.08 | 30.50 | 20.15 | 29.00 | 19.96 |
December | 744.00 | 21.76 | 45.00 | 21.00 | 45.00 | 21.00 |
Annual Sum or Average | 7739.50 | 22.05 | 783.83 | 20.97 | 515.33 | 19.59 |
Minimum of Months | 507.67 | 20.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.76 | 186.17 | 23.97 | 186.17 | 23.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 712.17 | 20.54 | 712.17 | 20.54 |
February | 672.00 | 20.69 | 530.67 | 20.52 | 530.67 | 20.52 |
March | 743.50 | 21.01 | 389.33 | 20.72 | 389.33 | 20.72 |
April | 701.67 | 21.20 | 147.50 | 20.65 | 143.83 | 20.59 |
May | 718.00 | 21.52 | 7.00 | 21.82 | 5.17 | 21.47 |
June | 646.33 | 21.47 | 23.67 | 22.60 | 9.00 | 22.15 |
July | 639.67 | 21.46 | 30.67 | 22.71 | 8.33 | 22.09 |
August | 645.83 | 21.47 | 33.00 | 22.50 | 22.83 | 22.30 |
September | 660.83 | 21.42 | 16.00 | 21.55 | 11.33 | 20.97 |
October | 739.67 | 21.33 | 57.33 | 20.85 | 57.33 | 20.85 |
November | 719.00 | 20.89 | 420.50 | 20.64 | 420.50 | 20.64 |
December | 744.00 | 20.68 | 686.17 | 20.62 | 686.17 | 20.62 |
Annual Sum or Average | 8374.50 | 21.13 | 3054.00 | 20.67 | 2996.67 | 20.63 |
Minimum of Months | 639.67 | 20.57 | 7.00 | 20.52 | 5.17 | 20.52 |
Maximum of Months | 744.00 | 21.52 | 712.17 | 22.71 | 712.17 | 22.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 742.33 | 20.48 | 742.33 | 20.48 |
February | 672.00 | 20.47 | 623.17 | 20.42 | 623.17 | 20.42 |
March | 744.00 | 20.81 | 466.67 | 20.58 | 466.67 | 20.58 |
April | 707.83 | 21.11 | 180.50 | 20.59 | 178.17 | 20.56 |
May | 725.50 | 21.50 | 7.17 | 21.59 | 6.00 | 21.36 |
June | 656.00 | 21.49 | 23.33 | 22.64 | 10.67 | 22.37 |
July | 654.67 | 21.50 | 28.67 | 22.72 | 8.50 | 22.11 |
August | 673.33 | 21.53 | 33.83 | 22.48 | 25.00 | 22.29 |
September | 689.33 | 21.41 | 17.50 | 20.97 | 16.67 | 20.89 |
October | 743.67 | 21.10 | 147.67 | 20.72 | 147.67 | 20.72 |
November | 720.00 | 20.73 | 475.17 | 20.55 | 475.17 | 20.55 |
December | 744.00 | 20.51 | 741.50 | 20.51 | 741.50 | 20.51 |
Annual Sum or Average | 8474.33 | 21.04 | 3487.50 | 20.57 | 3441.50 | 20.54 |
Minimum of Months | 654.67 | 20.47 | 7.17 | 20.42 | 6.00 | 20.42 |
Maximum of Months | 744.00 | 21.53 | 742.33 | 22.72 | 742.33 | 22.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 632.50 | 20.56 | 632.50 | 20.56 |
February | 672.00 | 20.67 | 408.00 | 20.38 | 408.00 | 20.38 |
March | 744.00 | 21.09 | 257.50 | 20.85 | 257.50 | 20.85 |
April | 720.00 | 21.30 | 24.50 | 20.71 | 24.50 | 20.71 |
May | 744.00 | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.63 | 5.83 | 22.27 | 5.83 | 22.27 |
July | 744.00 | 21.66 | 9.67 | 22.31 | 9.67 | 22.31 |
August | 744.00 | 21.64 | 19.83 | 21.97 | 19.83 | 21.97 |
September | 720.00 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 21.03 | 269.33 | 20.73 | 269.33 | 20.73 |
December | 744.00 | 20.77 | 614.67 | 20.70 | 614.67 | 20.70 |
Annual Sum or Average | 8760.00 | 21.24 | 2241.83 | 20.65 | 2241.83 | 20.65 |
Minimum of Months | 672.00 | 20.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.66 | 632.50 | 22.31 | 632.50 | 22.31 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 707.83 | 20.53 | 707.83 | 20.53 |
February | 672.00 | 20.66 | 534.83 | 20.50 | 534.83 | 20.50 |
March | 744.00 | 21.08 | 361.67 | 20.78 | 361.67 | 20.78 |
April | 703.33 | 21.25 | 165.17 | 20.67 | 164.50 | 20.66 |
May | 720.50 | 21.61 | 5.50 | 21.52 | 4.67 | 21.33 |
June | 641.17 | 21.49 | 10.83 | 22.53 | 5.33 | 22.16 |
July | 627.00 | 21.45 | 15.00 | 22.54 | 5.83 | 22.13 |
August | 640.83 | 21.48 | 23.17 | 22.33 | 19.50 | 22.25 |
September | 659.33 | 21.47 | 6.17 | 21.40 | 4.67 | 21.11 |
October | 744.00 | 21.39 | 50.00 | 20.98 | 50.00 | 20.98 |
November | 720.00 | 20.89 | 423.17 | 20.63 | 423.17 | 20.63 |
December | 744.00 | 20.66 | 681.67 | 20.61 | 681.67 | 20.61 |
Annual Sum or Average | 8360.17 | 21.15 | 2985.00 | 20.64 | 2963.67 | 20.62 |
Minimum of Months | 627.00 | 20.56 | 5.50 | 20.50 | 4.67 | 20.50 |
Maximum of Months | 744.00 | 21.61 | 707.83 | 22.54 | 707.83 | 22.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 739.33 | 20.46 | 739.33 | 20.46 |
February | 672.00 | 20.43 | 622.83 | 20.38 | 622.83 | 20.38 |
March | 744.00 | 20.87 | 446.83 | 20.66 | 446.83 | 20.66 |
April | 709.83 | 21.17 | 183.67 | 20.64 | 183.17 | 20.64 |
May | 730.83 | 21.61 | 5.50 | 21.51 | 4.83 | 21.32 |
June | 648.83 | 21.51 | 11.17 | 22.46 | 5.67 | 22.04 |
July | 646.33 | 21.51 | 15.83 | 22.51 | 6.17 | 22.04 |
August | 685.67 | 21.59 | 24.50 | 22.39 | 21.17 | 22.32 |
September | 701.83 | 21.52 | 8.33 | 21.27 | 7.17 | 21.11 |
October | 744.00 | 21.15 | 105.17 | 20.93 | 105.17 | 20.93 |
November | 720.00 | 20.72 | 476.33 | 20.53 | 476.33 | 20.53 |
December | 744.00 | 20.50 | 737.00 | 20.50 | 737.00 | 20.50 |
Annual Sum or Average | 8491.33 | 21.08 | 3376.50 | 20.55 | 3355.67 | 20.54 |
Minimum of Months | 646.33 | 20.43 | 5.50 | 20.38 | 4.83 | 20.38 |
Maximum of Months | 744.00 | 21.61 | 739.33 | 22.51 | 739.33 | 22.32 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 728.67 | 20.50 | 728.67 | 20.50 |
February | 672.00 | 20.62 | 592.00 | 20.52 | 592.00 | 20.52 |
March | 743.17 | 20.91 | 474.00 | 20.66 | 474.00 | 20.66 |
April | 694.83 | 21.14 | 226.67 | 20.73 | 217.50 | 20.63 |
May | 696.67 | 21.49 | 21.83 | 21.86 | 14.33 | 21.26 |
June | 615.33 | 21.39 | 46.67 | 22.77 | 12.00 | 21.99 |
July | 606.50 | 21.37 | 68.50 | 22.84 | 17.17 | 22.09 |
August | 612.67 | 21.38 | 67.17 | 22.58 | 29.83 | 21.97 |
September | 647.83 | 21.36 | 42.00 | 21.90 | 23.50 | 20.91 |
October | 738.17 | 21.27 | 165.17 | 20.88 | 164.33 | 20.87 |
November | 717.83 | 20.80 | 471.67 | 20.59 | 471.67 | 20.59 |
December | 744.00 | 20.60 | 714.17 | 20.57 | 714.17 | 20.57 |
Annual Sum or Average | 8233.00 | 21.05 | 3618.50 | 20.72 | 3459.17 | 20.61 |
Minimum of Months | 606.50 | 20.52 | 21.83 | 20.50 | 12.00 | 20.50 |
Maximum of Months | 744.00 | 21.49 | 728.67 | 22.84 | 728.67 | 22.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 743.67 | 20.45 | 743.67 | 20.45 |
February | 672.00 | 20.43 | 648.50 | 20.40 | 648.50 | 20.40 |
March | 744.00 | 20.73 | 529.17 | 20.55 | 529.17 | 20.55 |
April | 702.83 | 21.05 | 263.50 | 20.65 | 257.00 | 20.59 |
May | 707.67 | 21.48 | 24.67 | 21.71 | 18.17 | 21.24 |
June | 622.67 | 21.41 | 41.17 | 22.77 | 9.83 | 22.01 |
July | 617.50 | 21.40 | 60.17 | 22.77 | 17.17 | 22.08 |
August | 634.67 | 21.44 | 61.83 | 22.45 | 33.33 | 21.97 |
September | 672.67 | 21.36 | 47.00 | 21.09 | 40.00 | 20.77 |
October | 743.67 | 21.01 | 299.17 | 20.73 | 299.17 | 20.73 |
November | 720.00 | 20.66 | 533.67 | 20.52 | 533.67 | 20.52 |
December | 744.00 | 20.48 | 743.83 | 20.48 | 743.83 | 20.48 |
Annual Sum or Average | 8325.67 | 20.97 | 3996.33 | 20.61 | 3873.50 | 20.53 |
Minimum of Months | 617.50 | 20.43 | 24.67 | 20.40 | 9.83 | 20.40 |
Maximum of Months | 744.00 | 21.48 | 743.83 | 22.77 | 743.83 | 22.08 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.00 | 20.96 | 598.50 | 20.72 | 598.50 | 20.72 |
February | 661.33 | 21.06 | 399.00 | 20.73 | 399.00 | 20.73 |
March | 735.50 | 21.24 | 267.50 | 20.81 | 267.50 | 20.81 |
April | 693.67 | 21.27 | 145.50 | 20.82 | 139.50 | 20.71 |
May | 719.50 | 21.57 | 0.17 | 21.29 | 0.17 | 21.29 |
June | 658.17 | 21.52 | 10.83 | 22.07 | 10.83 | 22.07 |
July | 644.33 | 21.47 | 15.50 | 22.29 | 15.50 | 22.29 |
August | 642.00 | 21.45 | 29.17 | 22.14 | 25.00 | 21.94 |
September | 640.83 | 21.42 | 34.83 | 22.99 | 4.83 | 21.10 |
October | 689.50 | 21.38 | 24.83 | 21.64 | 18.00 | 21.00 |
November | 705.33 | 21.14 | 325.17 | 20.79 | 320.83 | 20.75 |
December | 736.17 | 20.97 | 568.17 | 20.71 | 568.17 | 20.71 |
Annual Sum or Average | 8269.33 | 21.28 | 2419.17 | 20.82 | 2367.83 | 20.76 |
Minimum of Months | 640.83 | 20.96 | 0.17 | 20.71 | 0.17 | 20.71 |
Maximum of Months | 743.00 | 21.57 | 598.50 | 22.99 | 598.50 | 22.29 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 710.50 | 21.99 | 115.83 | 18.42 | 115.83 | 18.42 |
February | 559.83 | 21.37 | 122.50 | 15.76 | 122.50 | 15.76 |
March | 508.67 | 23.10 | 49.50 | 23.96 | 0.00 | 0.00 |
April | 291.00 | 23.06 | 151.33 | 23.88 | 5.33 | 23.93 |
May | 184.00 | 23.17 | 421.17 | 23.86 | 65.50 | 23.94 |
June | 124.33 | 23.53 | 586.33 | 23.78 | 83.17 | 23.97 |
July | 184.83 | 23.77 | 613.83 | 23.77 | 161.83 | 23.97 |
August | 201.83 | 23.57 | 562.83 | 23.80 | 151.17 | 23.95 |
September | 191.00 | 23.04 | 381.50 | 23.83 | 46.00 | 23.97 |
October | 311.50 | 22.98 | 91.67 | 23.97 | 0.00 | 0.00 |
November | 505.83 | 22.81 | 90.33 | 23.00 | 24.67 | 20.41 |
December | 715.67 | 22.88 | 12.83 | 21.03 | 12.83 | 21.03 |
Annual Sum or Average | 4489.00 | 22.69 | 3199.67 | 23.28 | 788.83 | 21.72 |
Minimum of Months | 124.33 | 21.37 | 12.83 | 15.76 | 0.00 | 0.00 |
Maximum of Months | 715.67 | 23.77 | 613.83 | 23.97 | 161.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 651.83 | 22.09 | 111.17 | 18.39 | 108.50 | 18.25 |
February | 460.50 | 21.11 | 116.33 | 15.51 | 113.17 | 15.27 |
March | 302.17 | 23.09 | 86.83 | 23.98 | 0.00 | 0.00 |
April | 126.33 | 23.10 | 248.17 | 23.90 | 1.50 | 23.95 |
May | 49.83 | 23.91 | 571.83 | 23.84 | 45.67 | 23.97 |
June | 55.83 | 23.98 | 665.33 | 23.78 | 55.83 | 23.98 |
July | 127.83 | 23.98 | 702.33 | 23.74 | 127.83 | 23.98 |
August | 126.17 | 23.92 | 665.00 | 23.74 | 121.83 | 23.97 |
September | 94.83 | 23.36 | 503.83 | 23.82 | 37.00 | 23.98 |
October | 148.83 | 23.06 | 202.17 | 23.96 | 0.00 | 0.00 |
November | 362.00 | 22.84 | 143.00 | 23.44 | 15.83 | 19.22 |
December | 570.67 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3076.83 | 22.64 | 4016.00 | 23.40 | 627.17 | 21.30 |
Minimum of Months | 49.83 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 651.83 | 23.98 | 702.33 | 23.98 | 127.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 532.50 | 22.08 | 585.83 | 22.75 | 414.33 | 22.28 |
February | 504.17 | 21.56 | 553.50 | 21.97 | 439.67 | 21.51 |
March | 547.50 | 23.89 | 628.00 | 23.98 | 489.67 | 24.10 |
April | 516.00 | 24.06 | 650.17 | 23.92 | 501.50 | 24.12 |
May | 545.83 | 24.04 | 731.83 | 23.77 | 545.83 | 24.04 |
June | 537.00 | 24.00 | 719.67 | 23.64 | 537.00 | 24.00 |
July | 555.83 | 23.98 | 742.17 | 23.58 | 555.83 | 23.98 |
August | 555.00 | 23.98 | 744.00 | 23.62 | 555.00 | 23.98 |
September | 519.83 | 24.04 | 705.33 | 23.74 | 519.50 | 24.04 |
October | 521.33 | 24.11 | 675.50 | 23.94 | 517.67 | 24.13 |
November | 520.67 | 23.64 | 613.67 | 23.77 | 463.67 | 23.85 |
December | 535.67 | 23.57 | 577.83 | 23.99 | 417.50 | 24.03 |
Annual Sum or Average | 6391.33 | 23.59 | 7927.50 | 23.58 | 5957.17 | 23.72 |
Minimum of Months | 504.17 | 21.56 | 553.50 | 21.97 | 414.33 | 21.51 |
Maximum of Months | 555.83 | 24.11 | 744.00 | 23.99 | 555.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.06052 | 17.49342 | -0.2849 | 8.22825 |
February | 672.00000 | 20.74152 | 21.82523 | -0.5785 | 18.51757 |
March | 744.00000 | 21.69336 | 28.47289 | -0.3268 | 7.37899 |
April | 720.00000 | 21.30229 | 36.48458 | -0.3780 | 8.10024 |
May | 744.00000 | 21.31066 | 49.78744 | -1.4709 | 49.35993 |
June | 720.00000 | 21.38938 | 56.36624 | -1.3873 | 44.93037 |
July | 744.00000 | 21.49078 | 58.83432 | -1.3228 | 41.55355 |
August | 744.00000 | 22.19596 | 55.96318 | -1.0861 | 30.15037 |
September | 720.00000 | 23.05852 | 44.03537 | -0.8635 | 21.10976 |
October | 744.00000 | 23.78247 | 31.42777 | 0.23223 | 6.19740 |
November | 720.00000 | 23.63622 | 26.97873 | 0.16482 | 6.00508 |
December | 744.00000 | 23.52999 | 19.99755 | 0.08274 | 5.26179 |
Annual Sum or Average | 8760.00000 | 22.19269 | 37.39268 | -0.6016 | 20.58875 |
Minimum of Months | 672.00000 | 20.74152 | 17.49342 | -1.4709 | 5.26179 |
Maximum of Months | 744.00000 | 23.78247 | 58.83432 | 0.23223 | 49.35993 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55186 | 16.53606 | -0.7556 | 19.41576 |
February | 672.00000 | 20.14254 | 20.65231 | -0.7712 | 21.24297 |
March | 744.00000 | 21.19612 | 27.25356 | -0.4534 | 10.31229 |
April | 720.00000 | 21.31979 | 34.67171 | -0.3327 | 8.73247 |
May | 744.00000 | 21.22146 | 48.90638 | -1.3645 | 44.02650 |
June | 720.00000 | 21.51717 | 55.73018 | -1.1804 | 35.38703 |
July | 744.00000 | 21.61291 | 58.99349 | -1.1042 | 31.60811 |
August | 744.00000 | 21.73210 | 57.62035 | -1.0691 | 30.44421 |
September | 720.00000 | 21.79608 | 45.46601 | -1.1548 | 36.10343 |
October | 744.00000 | 21.50904 | 33.75355 | -0.2592 | 8.05764 |
November | 720.00000 | 21.11070 | 28.78702 | -0.4762 | 11.41233 |
December | 744.00000 | 21.12606 | 20.13938 | -0.5930 | 13.50790 |
Annual Sum or Average | 8760.00000 | 21.24312 | 37.47178 | -0.7931 | 22.52714 |
Minimum of Months | 672.00000 | 20.14254 | 16.53606 | -1.3645 | 8.05764 |
Maximum of Months | 744.00000 | 21.79608 | 58.99349 | -0.2592 | 44.02650 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74725 | 18.72534 | -0.5889 | 14.27825 |
February | 672.00000 | 20.35328 | 22.51750 | -0.6431 | 18.96320 |
March | 744.00000 | 21.74868 | 28.73037 | -0.2718 | 7.16057 |
April | 720.00000 | 22.07499 | 35.54056 | -0.1385 | 6.06585 |
May | 744.00000 | 22.22589 | 48.20271 | -1.0775 | 30.00423 |
June | 720.00000 | 22.28837 | 54.70556 | -0.9970 | 26.59675 |
July | 744.00000 | 22.28432 | 57.59407 | -0.9703 | 25.44059 |
August | 744.00000 | 22.39928 | 56.50684 | -0.9386 | 24.20025 |
September | 720.00000 | 22.51261 | 45.75670 | -0.9824 | 26.12661 |
October | 744.00000 | 22.41390 | 34.37732 | -0.0600 | 5.40258 |
November | 720.00000 | 21.75407 | 29.93745 | -0.2627 | 7.64407 |
December | 744.00000 | 21.36865 | 22.32038 | -0.4177 | 8.96300 |
Annual Sum or Average | 8760.00000 | 21.85649 | 37.99689 | -0.6123 | 16.72028 |
Minimum of Months | 672.00000 | 20.35328 | 18.72534 | -1.0775 | 5.40258 |
Maximum of Months | 744.00000 | 22.51261 | 57.59407 | -0.0600 | 30.00423 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.18194 | 13.85408 | 0.09874 | 19.05480 |
February | 672.00000 | 20.65636 | 17.62906 | 0.01877 | 23.07336 |
March | 744.00000 | 22.67972 | 23.46406 | 0.53544 | 14.39558 |
April | 720.00000 | 22.59897 | 30.61958 | 0.58300 | 15.42247 |
May | 744.00000 | 22.33928 | 43.69117 | -0.1507 | 12.68333 |
June | 720.00000 | 22.09913 | 50.84066 | -0.1638 | 12.83847 |
July | 744.00000 | 21.95544 | 54.01303 | -0.1864 | 12.75984 |
August | 744.00000 | 22.01948 | 53.10156 | -0.1693 | 12.97573 |
September | 720.00000 | 22.29253 | 42.18905 | -0.1687 | 12.72536 |
October | 744.00000 | 22.69717 | 29.68954 | 0.60767 | 15.97177 |
November | 720.00000 | 22.46586 | 24.84511 | 0.49296 | 15.21980 |
December | 744.00000 | 22.58628 | 17.05861 | 0.44006 | 12.31058 |
Annual Sum or Average | 8760.00000 | 22.14058 | 33.50542 | 0.16239 | 14.89572 |
Minimum of Months | 672.00000 | 20.65636 | 13.85408 | -0.1864 | 12.31058 |
Maximum of Months | 744.00000 | 22.69717 | 54.01303 | 0.60767 | 23.07336 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74250 | 21.83262 | -0.6050 | 15.33467 |
February | 672.00000 | 20.57654 | 25.53480 | -0.5701 | 17.70238 |
March | 744.00000 | 21.76035 | 32.03887 | -0.2266 | 7.53206 |
April | 720.00000 | 22.08468 | 38.92844 | -0.0720 | 6.81380 |
May | 744.00000 | 22.24317 | 51.82857 | -0.9484 | 24.85617 |
June | 720.00000 | 22.40468 | 58.29538 | -0.8086 | 19.88530 |
July | 744.00000 | 22.43281 | 61.26808 | -0.7570 | 17.89748 |
August | 744.00000 | 22.59932 | 59.99044 | -0.7047 | 16.40569 |
September | 720.00000 | 22.71400 | 48.88322 | -0.7652 | 19.96773 |
October | 744.00000 | 22.47348 | 37.80061 | 0.04426 | 6.49915 |
November | 720.00000 | 21.65008 | 33.40632 | -0.2549 | 8.73037 |
December | 744.00000 | 21.35939 | 25.55556 | -0.4313 | 10.22512 |
Annual Sum or Average | 8760.00000 | 21.92791 | 41.37023 | -0.5081 | 14.29820 |
Minimum of Months | 672.00000 | 20.57654 | 21.83262 | -0.9484 | 6.49915 |
Maximum of Months | 744.00000 | 22.71400 | 61.26808 | 0.04426 | 24.85617 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04009 | 20.98801 | -0.4852 | 12.32584 |
February | 672.00000 | 20.77777 | 24.56130 | -0.5118 | 17.12037 |
March | 744.00000 | 22.19000 | 30.81823 | -0.1315 | 6.18510 |
April | 720.00000 | 22.45261 | 37.62394 | -0.0103 | 5.83129 |
May | 744.00000 | 22.58766 | 50.07647 | -0.9019 | 23.05984 |
June | 720.00000 | 22.57282 | 56.68300 | -0.8414 | 20.83483 |
July | 744.00000 | 22.51379 | 59.67831 | -0.8307 | 20.38991 |
August | 744.00000 | 22.65917 | 58.53150 | -0.7876 | 18.94089 |
September | 720.00000 | 22.84525 | 47.76876 | -0.8102 | 19.74931 |
October | 744.00000 | 22.86237 | 36.38697 | 0.09044 | 5.60237 |
November | 720.00000 | 22.16712 | 31.99777 | -0.1277 | 6.91792 |
December | 744.00000 | 21.76156 | 24.55354 | -0.2927 | 7.41426 |
Annual Sum or Average | 8760.00000 | 22.21086 | 40.06012 | -0.4700 | 13.67352 |
Minimum of Months | 672.00000 | 20.77777 | 20.98801 | -0.9019 | 5.60237 |
Maximum of Months | 744.00000 | 22.86237 | 59.67831 | 0.09044 | 23.05984 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57099 | 25.26205 | -0.7792 | 18.42075 |
February | 672.00000 | 20.68604 | 29.19485 | -0.6893 | 16.17101 |
March | 744.00000 | 21.01056 | 35.29880 | -0.5197 | 11.55763 |
April | 720.00000 | 21.25294 | 41.77195 | -0.3556 | 8.97540 |
May | 744.00000 | 21.57305 | 53.18968 | -1.2977 | 41.19109 |
June | 720.00000 | 21.64061 | 57.42790 | -1.1844 | 35.93512 |
July | 744.00000 | 21.70117 | 59.43803 | -1.1202 | 32.97712 |
August | 744.00000 | 21.69319 | 59.54749 | -1.1402 | 33.90649 |
September | 720.00000 | 21.56233 | 50.52912 | -1.3019 | 41.77707 |
October | 744.00000 | 21.34192 | 41.79873 | -0.3499 | 8.31458 |
November | 720.00000 | 20.89634 | 37.29318 | -0.5607 | 12.68143 |
December | 744.00000 | 20.67523 | 28.73123 | -0.7197 | 16.58734 |
Annual Sum or Average | 8760.00000 | 21.22007 | 43.36813 | -0.8359 | 23.24785 |
Minimum of Months | 672.00000 | 20.57099 | 25.26205 | -1.3019 | 8.31458 |
Maximum of Months | 744.00000 | 21.70117 | 59.54749 | -0.3499 | 41.77707 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47720 | 25.45830 | -0.8310 | 20.21750 |
February | 672.00000 | 20.47128 | 29.55517 | -0.7687 | 18.58635 |
March | 744.00000 | 20.80706 | 35.70636 | -0.5862 | 12.97260 |
April | 720.00000 | 21.14411 | 42.16247 | -0.3944 | 9.44401 |
May | 744.00000 | 21.53516 | 53.39084 | -1.3196 | 42.19206 |
June | 720.00000 | 21.63333 | 57.53392 | -1.1916 | 36.22477 |
July | 744.00000 | 21.69684 | 59.72792 | -1.1285 | 33.29231 |
August | 744.00000 | 21.68155 | 60.17282 | -1.1574 | 34.58056 |
September | 720.00000 | 21.48682 | 51.32451 | -1.3534 | 44.10386 |
October | 744.00000 | 21.09768 | 42.35796 | -0.4335 | 9.35652 |
November | 720.00000 | 20.73201 | 37.65317 | -0.6205 | 14.03111 |
December | 744.00000 | 20.51190 | 29.03338 | -0.7818 | 18.45323 |
Annual Sum or Average | 8760.00000 | 21.10990 | 43.75080 | -0.8814 | 24.48641 |
Minimum of Months | 672.00000 | 20.47128 | 25.45830 | -1.3534 | 9.35652 |
Maximum of Months | 744.00000 | 21.69684 | 60.17282 | -0.3944 | 44.10386 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64645 | 24.40323 | -0.6987 | 15.87619 |
February | 672.00000 | 20.66822 | 28.23845 | -0.6551 | 15.12080 |
March | 744.00000 | 21.09430 | 34.42221 | -0.4825 | 10.18926 |
April | 720.00000 | 21.30326 | 40.82178 | -0.3615 | 8.16786 |
May | 744.00000 | 21.54849 | 50.88528 | -1.3584 | 43.76784 |
June | 720.00000 | 21.63207 | 56.09435 | -1.2682 | 39.34687 |
July | 744.00000 | 21.65767 | 58.99932 | -1.2354 | 37.76574 |
August | 744.00000 | 21.63982 | 58.66140 | -1.2535 | 38.62894 |
September | 720.00000 | 21.52900 | 49.58190 | -1.3795 | 44.88234 |
October | 744.00000 | 21.30209 | 40.66088 | -0.3685 | 8.00354 |
November | 720.00000 | 21.03276 | 36.02611 | -0.4956 | 10.73010 |
December | 744.00000 | 20.76895 | 28.07977 | -0.6403 | 13.97686 |
Annual Sum or Average | 8760.00000 | 21.23839 | 42.31747 | -0.8511 | 23.92235 |
Minimum of Months | 672.00000 | 20.64645 | 24.40323 | -1.3795 | 8.00354 |
Maximum of Months | 744.00000 | 21.65767 | 58.99932 | -0.3615 | 44.88234 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55981 | 25.23675 | -0.7800 | 18.45473 |
February | 672.00000 | 20.65904 | 29.16995 | -0.6972 | 16.48780 |
March | 744.00000 | 21.07618 | 35.16905 | -0.5029 | 11.21585 |
April | 720.00000 | 21.29855 | 41.58627 | -0.3553 | 9.02368 |
May | 744.00000 | 21.65512 | 52.37869 | -1.2640 | 39.60225 |
June | 720.00000 | 21.67984 | 56.59705 | -1.1710 | 35.34598 |
July | 744.00000 | 21.72763 | 58.81005 | -1.1178 | 32.89843 |
August | 744.00000 | 21.72376 | 58.76348 | -1.1394 | 33.87603 |
September | 720.00000 | 21.61623 | 50.08990 | -1.2827 | 40.85503 |
October | 744.00000 | 21.38833 | 41.73779 | -0.3418 | 8.19083 |
November | 720.00000 | 20.88913 | 37.29888 | -0.5632 | 12.72662 |
December | 744.00000 | 20.65847 | 28.73852 | -0.7233 | 16.66467 |
Annual Sum or Average | 8760.00000 | 21.24776 | 43.04051 | -0.8291 | 22.98133 |
Minimum of Months | 672.00000 | 20.55981 | 25.23675 | -1.2827 | 8.19083 |
Maximum of Months | 744.00000 | 21.72763 | 58.81005 | -0.3418 | 40.85503 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46734 | 25.42608 | -0.8324 | 20.30190 |
February | 672.00000 | 20.42923 | 29.52545 | -0.7804 | 19.09082 |
March | 744.00000 | 20.87342 | 35.54345 | -0.5695 | 12.51342 |
April | 720.00000 | 21.19371 | 41.94664 | -0.3940 | 9.44548 |
May | 744.00000 | 21.63387 | 52.55931 | -1.2811 | 40.35952 |
June | 720.00000 | 21.67544 | 56.71865 | -1.1772 | 35.59216 |
July | 744.00000 | 21.72553 | 59.13914 | -1.1251 | 33.17729 |
August | 744.00000 | 21.71850 | 59.40241 | -1.1544 | 34.46721 |
September | 720.00000 | 21.56340 | 50.75338 | -1.3275 | 42.83759 |
October | 744.00000 | 21.14745 | 42.25799 | -0.4255 | 9.10241 |
November | 720.00000 | 20.72282 | 37.65349 | -0.6242 | 14.12515 |
December | 744.00000 | 20.50472 | 29.03025 | -0.7845 | 18.57629 |
Annual Sum or Average | 8760.00000 | 21.14212 | 43.40547 | -0.8737 | 24.15889 |
Minimum of Months | 672.00000 | 20.42923 | 25.42608 | -1.3275 | 9.10241 |
Maximum of Months | 744.00000 | 21.72553 | 59.40241 | -0.3940 | 42.83759 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51796 | 25.60217 | -0.8450 | 20.70536 |
February | 672.00000 | 20.62471 | 29.68680 | -0.7422 | 17.77984 |
March | 744.00000 | 20.91390 | 35.97998 | -0.5728 | 12.96248 |
April | 720.00000 | 21.20895 | 42.39999 | -0.3778 | 9.67610 |
May | 744.00000 | 21.59025 | 53.52334 | -1.2826 | 40.70879 |
June | 720.00000 | 21.65057 | 57.39151 | -1.1577 | 34.98510 |
July | 744.00000 | 21.70843 | 59.22627 | -1.0882 | 31.81391 |
August | 744.00000 | 21.69738 | 59.49866 | -1.1146 | 32.98589 |
September | 720.00000 | 21.54879 | 50.93639 | -1.3021 | 42.07525 |
October | 744.00000 | 21.28112 | 42.57694 | -0.3818 | 8.96790 |
November | 720.00000 | 20.81046 | 38.08271 | -0.6155 | 14.22237 |
December | 744.00000 | 20.60041 | 29.17890 | -0.7867 | 18.73179 |
Annual Sum or Average | 8760.00000 | 21.18260 | 43.74992 | -0.8564 | 23.83496 |
Minimum of Months | 672.00000 | 20.51796 | 25.60217 | -1.3021 | 8.96790 |
Maximum of Months | 744.00000 | 21.70843 | 59.49866 | -0.3778 | 42.07525 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.44996 | 25.78403 | -0.8931 | 22.51510 |
February | 672.00000 | 20.42726 | 30.04008 | -0.8209 | 20.32339 |
March | 744.00000 | 20.73043 | 36.38781 | -0.6378 | 14.42744 |
April | 720.00000 | 21.10025 | 42.79697 | -0.4184 | 10.18729 |
May | 744.00000 | 21.56034 | 53.72576 | -1.3031 | 41.62874 |
June | 720.00000 | 21.64611 | 57.47891 | -1.1642 | 35.23683 |
July | 744.00000 | 21.70702 | 59.45824 | -1.0958 | 32.08922 |
August | 744.00000 | 21.69177 | 60.10096 | -1.1302 | 33.57684 |
September | 720.00000 | 21.47828 | 51.73247 | -1.3540 | 44.38751 |
October | 744.00000 | 21.01519 | 43.20934 | -0.4735 | 10.25540 |
November | 720.00000 | 20.65998 | 38.44565 | -0.6747 | 15.65255 |
December | 744.00000 | 20.48002 | 29.45088 | -0.8421 | 20.56099 |
Annual Sum or Average | 8760.00000 | 21.08268 | 44.12704 | -0.9013 | 25.09492 |
Minimum of Months | 672.00000 | 20.42726 | 25.78403 | -1.3540 | 10.18729 |
Maximum of Months | 744.00000 | 21.70702 | 60.10096 | -0.4184 | 44.38751 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96671 | 27.20563 | -0.6383 | 14.97837 |
February | 672.00000 | 21.09697 | 30.81733 | -0.5422 | 12.71877 |
March | 744.00000 | 21.26238 | 36.51189 | -0.4361 | 10.36028 |
April | 720.00000 | 21.34565 | 42.55512 | -0.3382 | 8.83560 |
May | 744.00000 | 21.62859 | 52.58947 | -1.2974 | 41.28079 |
June | 720.00000 | 21.66615 | 56.95655 | -1.2083 | 37.01603 |
July | 744.00000 | 21.70373 | 59.08215 | -1.1560 | 34.58956 |
August | 744.00000 | 21.69970 | 58.36126 | -1.1606 | 34.90475 |
September | 720.00000 | 21.62747 | 50.19006 | -1.2694 | 40.49126 |
October | 744.00000 | 21.52214 | 42.44648 | -0.2702 | 7.75997 |
November | 720.00000 | 21.18593 | 38.38502 | -0.4566 | 10.94082 |
December | 744.00000 | 20.99599 | 30.48219 | -0.5991 | 14.26581 |
Annual Sum or Average | 8760.00000 | 21.39350 | 43.86997 | -0.7826 | 22.40264 |
Minimum of Months | 672.00000 | 20.96671 | 27.20563 | -1.2974 | 7.75997 |
Maximum of Months | 744.00000 | 21.70373 | 59.08215 | -0.2702 | 41.28079 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07625 | 22.64722 | -0.2456 | 10.65147 |
February | 672.00000 | 21.80694 | 25.75478 | -0.2663 | 16.31655 |
March | 744.00000 | 23.36477 | 31.50770 | 0.16643 | 6.31927 |
April | 720.00000 | 23.53616 | 37.60328 | 0.28763 | 7.26318 |
May | 744.00000 | 23.58177 | 49.03078 | -0.4836 | 10.45237 |
June | 720.00000 | 23.60352 | 55.10135 | -0.3901 | 8.69922 |
July | 744.00000 | 23.57048 | 57.91526 | -0.3682 | 8.36259 |
August | 744.00000 | 23.51250 | 57.34159 | -0.4051 | 9.04744 |
September | 720.00000 | 23.53038 | 47.74136 | -0.5125 | 11.27825 |
October | 744.00000 | 23.53176 | 36.94782 | 0.27390 | 6.94798 |
November | 720.00000 | 23.14209 | 32.82709 | 0.11607 | 6.97376 |
December | 744.00000 | 22.92087 | 26.06236 | -0.0222 | 6.08839 |
Annual Sum or Average | 8760.00000 | 23.18978 | 40.12154 | -0.1535 | 8.97877 |
Minimum of Months | 672.00000 | 21.80694 | 22.64722 | -0.5125 | 6.08839 |
Maximum of Months | 744.00000 | 23.60352 | 57.91526 | 0.28763 | 16.31655 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.32195 | 21.93169 | -0.1479 | 10.21701 |
February | 672.00000 | 22.00734 | 24.90872 | -0.1777 | 16.40162 |
March | 744.00000 | 23.58038 | 30.50252 | 0.25952 | 6.93519 |
April | 720.00000 | 23.70505 | 36.57523 | 0.36743 | 8.19505 |
May | 744.00000 | 23.72390 | 47.98797 | -0.3815 | 8.41268 |
June | 720.00000 | 23.71848 | 54.15794 | -0.3033 | 7.27086 |
July | 744.00000 | 23.67734 | 56.99828 | -0.2870 | 7.09258 |
August | 744.00000 | 23.63103 | 56.39116 | -0.3190 | 7.56408 |
September | 720.00000 | 23.66556 | 46.77106 | -0.4157 | 9.14221 |
October | 744.00000 | 23.70277 | 35.90265 | 0.35466 | 7.87103 |
November | 720.00000 | 23.36285 | 31.86379 | 0.20936 | 7.43647 |
December | 744.00000 | 23.20216 | 25.21906 | 0.08641 | 6.06138 |
Annual Sum or Average | 8760.00000 | 23.36655 | 39.18197 | -0.0622 | 8.49139 |
Minimum of Months | 672.00000 | 22.00734 | 21.93169 | -0.4157 | 6.06138 |
Maximum of Months | 744.00000 | 23.72390 | 56.99828 | 0.36743 | 16.40162 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.51839 | 21.85911 | 0.53154 | 24.21416 |
February | 672.00000 | 22.01203 | 25.65402 | 0.47095 | 30.04483 |
March | 744.00000 | 23.72312 | 29.06915 | 0.94148 | 26.96537 |
April | 720.00000 | 23.78239 | 35.29824 | 1.04454 | 30.99820 |
May | 744.00000 | 23.75366 | 46.79538 | 0.59173 | 18.68572 |
June | 720.00000 | 23.64075 | 53.18705 | 0.64566 | 20.76700 |
July | 744.00000 | 23.57207 | 56.03264 | 0.65854 | 21.57043 |
August | 744.00000 | 23.61525 | 55.25721 | 0.64803 | 20.79612 |
September | 720.00000 | 23.70931 | 45.58029 | 0.56440 | 18.37618 |
October | 744.00000 | 23.81387 | 34.51986 | 1.03707 | 30.43092 |
November | 720.00000 | 23.53520 | 30.59837 | 0.88865 | 26.78334 |
December | 744.00000 | 23.57439 | 23.76498 | 0.80164 | 22.01275 |
Annual Sum or Average | 8760.00000 | 23.44674 | 38.20405 | 0.73697 | 24.25736 |
Minimum of Months | 672.00000 | 22.01203 | 21.85911 | 0.47095 | 18.37618 |
Maximum of Months | 744.00000 | 23.81387 | 56.03264 | 1.04454 | 30.99820 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.351312E+09 | 10729.82 | 01-JAN-09:02 | 60.37 | 0.111943E+10 | 0.00 | 0.147074E+10 | 0.26 | 3.19 | 01-JAN-09:02 | 0.00 | 0.00 |
February | 0.749055E+09 | 12880.23 | 25-FEB-16:02 | 108.71 | 0.238682E+10 | 0.00 | 0.313587E+10 | 0.52 | 3.19 | 06-FEB-16:02 | 0.00 | 0.00 |
March | 0.579997E+10 | 73433.25 | 25-MAR-15:01 | 296.43 | 0.180217E+11 | 0.00 | 0.238217E+11 | 1.26 | 3.37 | 25-MAR-15:01 | 0.00 | 0.00 |
April | 0.323459E+11 | 140919.09 | 18-APR-15:03 | 463.38 | 0.102917E+12 | 0.00 | 0.135263E+12 | 2.04 | 3.99 | 18-APR-08:62 | 0.00 | 0.00 |
May | 0.764902E+11 | 136354.21 | 31-MAY-15:03 | 731.25 | 0.239769E+12 | 0.00 | 0.316260E+12 | 3.08 | 4.05 | 11-MAY-18:02 | 0.00 | 0.00 |
June | 0.164834E+12 | 195624.34 | 11-JUN-15:03 | 713.58 | 0.546218E+12 | 0.00 | 0.711052E+12 | 3.21 | 4.18 | 13-JUN-08:62 | 0.00 | 0.00 |
July | 0.220739E+12 | 207273.64 | 26-JUL-18:03 | 744.00 | 0.763618E+12 | 0.00 | 0.984357E+12 | 3.37 | 4.29 | 20-JUL-08:62 | 0.00 | 0.00 |
August | 0.197010E+12 | 211519.63 | 04-AUG-15:03 | 744.00 | 0.668159E+12 | 0.00 | 0.865170E+12 | 3.30 | 4.31 | 04-AUG-18:03 | 0.00 | 0.00 |
September | 0.963869E+11 | 160691.70 | 06-SEP-15:03 | 689.39 | 0.297933E+12 | 0.00 | 0.394320E+12 | 2.98 | 4.00 | 10-SEP-08:62 | 0.00 | 0.00 |
October | 0.190198E+11 | 96899.69 | 20-OCT-15:02 | 570.66 | 0.588518E+11 | 0.00 | 0.778717E+11 | 2.43 | 3.54 | 20-OCT-15:02 | 0.00 | 0.00 |
November | 0.525305E+10 | 57520.68 | 03-NOV-15:03 | 269.82 | 0.165839E+11 | 0.00 | 0.218370E+11 | 1.19 | 3.19 | 01-NOV-07:10 | 0.00 | 0.00 |
December | 0.637701E+09 | 11642.03 | 02-DEC-09:02 | 92.19 | 0.203199E+10 | 0.00 | 0.266970E+10 | 0.39 | 3.19 | 01-DEC-10:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819617E+12 | 5483.80 | 0.271761E+13 | 0.353723E+13 | 2.01 | |||||||
Minimum of Months | 0.351312E+09 | 10729.82 | 60.37 | 0.111943E+10 | 0.00 | 0.147074E+10 | 0.26 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.220739E+12 | 211519.63 | 744.00 | 0.763618E+12 | 0.00 | 0.984357E+12 | 3.37 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.477518E+12 | 0.00 | 744.00 | 581418.79 | 31-JAN-04:03 | 0.00 | 49.99 | 59.77 | 4.34 | 0.00 | 0.29 | 0.93 | 31-JAN-04:03 |
February | 0.329858E+12 | 0.00 | 671.17 | 611095.51 | 02-FEB-06:00 | 0.00 | 50.31 | 59.40 | 3.32 | 0.00 | 0.22 | 0.98 | 02-FEB-06:00 |
March | 0.121569E+12 | 0.00 | 740.62 | 225524.24 | 05-MAR-19:02 | 0.00 | 49.12 | 58.77 | 1.12 | 0.00 | 0.07 | 0.36 | 05-MAR-19:02 |
April | 0.603768E+11 | 0.00 | 679.71 | 181430.83 | 03-APR-08:62 | 0.00 | 48.12 | 57.43 | 0.58 | 0.00 | 0.04 | 0.29 | 03-APR-08:62 |
May | 0.363000E+11 | 0.00 | 623.25 | 124667.47 | 01-MAY-15:05 | 0.00 | 43.59 | 55.12 | 0.25 | 0.00 | 0.02 | 0.20 | 01-MAY-15:05 |
June | 0.223010E+11 | 0.00 | 515.07 | 110544.36 | 02-JUN-08:07 | 0.00 | 41.95 | 52.76 | 0.15 | 0.00 | 0.01 | 0.18 | 02-JUN-08:07 |
July | 0.758636E+10 | 0.00 | 470.54 | 73449.22 | 24-JUL-03:00 | 0.00 | 41.66 | 51.45 | 0.05 | 0.00 | 0.00 | 0.12 | 24-JUL-03:00 |
August | 0.105507E+11 | 0.00 | 490.12 | 83568.28 | 06-AUG-23:00 | 0.00 | 41.53 | 51.84 | 0.06 | 0.00 | 0.01 | 0.13 | 06-AUG-23:00 |
September | 0.324159E+11 | 0.00 | 534.13 | 132649.83 | 29-SEP-15:05 | 0.00 | 43.85 | 53.47 | 0.25 | 0.00 | 0.02 | 0.21 | 29-SEP-15:05 |
October | 0.510056E+11 | 0.00 | 694.13 | 148549.45 | 28-OCT-15:03 | 0.00 | 48.60 | 57.02 | 0.49 | 0.00 | 0.03 | 0.24 | 28-OCT-15:03 |
November | 0.165676E+12 | 0.00 | 710.48 | 557749.05 | 26-NOV-07:00 | 0.00 | 48.59 | 58.54 | 1.56 | 0.00 | 0.10 | 0.89 | 26-NOV-07:00 |
December | 0.273107E+12 | 0.00 | 744.00 | 300350.82 | 09-DEC-09:06 | 0.00 | 49.77 | 59.68 | 2.49 | 0.00 | 0.16 | 0.48 | 09-DEC-09:06 |
Annual Sum or Average | 0.158826E+13 | 7617.21 | 46.40 | 56.25 | 1.21 | 0.00 | 0.08 | ||||||
Minimum of Months | 0.758636E+10 | 0.00 | 470.54 | 73449.22 | 0.00 | 41.53 | 51.45 | 0.05 | 0.00 | 0.00 | 0.12 | ||
Maximum of Months | 0.477518E+12 | 0.00 | 744.00 | 611095.51 | 0.00 | 50.31 | 59.77 | 4.34 | 0.00 | 0.29 | 0.98 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 6039123.42 | 0.00 | 1.35 | 6039123.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13419.14 | 12-JAN-16:02 | 13419.14 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.108987E+09 | 0.00 | 17.24 | 0.108978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13801.23 | 25-FEB-16:02 | 13801.23 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.381113E+09 | 0.00 | 74.44 | 0.329342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14227.66 | 25-MAR-15:01 | 14227.66 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.204052E+10 | 0.00 | 242.08 | 0.146545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16098.79 | 16-APR-08:61 | 14244.59 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.335847E+10 | 0.00 | 480.22 | 0.196125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17295.13 | 29-MAY-08:61 | 14444.20 | 30-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.629637E+10 | 0.00 | 578.01 | 0.347675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19674.16 | 26-JUN-08:62 | 14549.96 | 13-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.807283E+10 | 0.00 | 681.47 | 0.434500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18771.07 | 26-JUL-08:61 | 14728.21 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.709407E+10 | 0.00 | 677.11 | 0.363737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21261.24 | 03-AUG-08:62 | 14725.01 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.419719E+10 | 0.00 | 470.14 | 0.253133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17100.11 | 11-SEP-08:62 | 14549.52 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.102319E+10 | 0.00 | 184.48 | 0.829814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14857.50 | 02-OCT-15:01 | 14218.20 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.195009E+09 | 0.00 | 43.78 | 0.150780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13796.57 | 04-NOV-15:02 | 13796.57 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 9289389.81 | 0.00 | 1.79 | 9289389.81 | 0.00 | 0.00 | 0.00 | 0.00 | 13298.00 | 02-DEC-16:02 | 13298.00 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327831E+11 | 3452.09 | 0.188514E+11 | ||||||||||||
Minimum of Months | 6039123.42 | 0.00 | 1.35 | 6039123.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13298.00 | 13298.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.807283E+10 | 0.00 | 681.47 | 0.434500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21261.24 | 14728.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 332379.27 | 0.00 | 0.11 | 332379.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.03 | 13-JAN-19:05 | 1485.03 | 13-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 31810151.99 | 0.00 | 7.25 | 31810151.99 | 0.00 | 0.00 | 0.00 | 0.00 | 13318.06 | 24-FEB-16:02 | 13318.06 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.170718E+09 | 0.00 | 42.04 | 0.143827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14002.42 | 25-MAR-15:01 | 14002.42 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.160388E+10 | 0.00 | 204.70 | 0.112566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15847.92 | 16-APR-08:61 | 14361.58 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.305707E+10 | 0.00 | 450.43 | 0.177808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17013.37 | 29-MAY-08:61 | 14362.46 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.609716E+10 | 0.00 | 569.41 | 0.335736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19281.94 | 26-JUN-08:62 | 14489.67 | 18-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.771925E+10 | 0.00 | 671.13 | 0.412579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18502.47 | 26-JUL-08:61 | 14488.02 | 30-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.644505E+10 | 0.00 | 657.21 | 0.324666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20986.41 | 03-AUG-08:62 | 14420.50 | 22-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.326552E+10 | 0.00 | 410.33 | 0.185561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16543.70 | 11-SEP-08:62 | 14244.50 | 16-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.478666E+09 | 0.00 | 93.98 | 0.374494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14641.97 | 02-OCT-15:01 | 13993.58 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 68912316.84 | 0.00 | 15.73 | 51377246.31 | 0.00 | 0.00 | 0.00 | 0.00 | 13577.50 | 04-NOV-15:02 | 13577.50 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 670733.10 | 0.00 | 0.18 | 670733.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.71 | 14-DEC-16:04 | 1677.71 | 14-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289390E+11 | 3122.50 | 0.160917E+11 | ||||||||||||
Minimum of Months | 332379.27 | 0.00 | 0.11 | 332379.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.03 | 1485.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.771925E+10 | 0.00 | 671.13 | 0.412579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20986.41 | 14489.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 8947323.42 | 0.00 | 1.25 | 8947323.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2828.49 | 25-FEB-14:50 | 2828.49 | 25-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.376072E+10 | 0.00 | 116.13 | 0.372384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34293.08 | 24-MAR-13:00 | 34293.08 | 24-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.110324E+11 | 0.00 | 249.06 | 0.786447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43765.64 | 15-APR-11:40 | 38186.85 | 15-APR-11:40 | 0.00 | 0.00 | 0.00 |
May | 0.221370E+11 | 0.00 | 582.43 | 0.123920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29648.08 | 05-MAY-13:10 | 20929.88 | 06-MAY-12:50 | 0.00 | 0.00 | 0.00 |
June | 0.332420E+11 | 0.00 | 650.49 | 0.159007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31976.37 | 26-JUN-17:25 | 22394.46 | 26-JUN-17:30 | 0.00 | 0.00 | 0.00 |
July | 0.412739E+11 | 0.00 | 730.70 | 0.197328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32686.45 | 30-JUL-12:50 | 22652.62 | 30-JUL-13:05 | 0.00 | 0.00 | 0.00 |
August | 0.425971E+11 | 0.00 | 735.58 | 0.219595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40302.52 | 22-AUG-13:00 | 37455.46 | 29-AUG-13:15 | 0.00 | 0.00 | 0.00 |
September | 0.348011E+11 | 0.00 | 586.81 | 0.241141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50275.40 | 07-SEP-12:50 | 42894.93 | 20-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.201377E+11 | 0.00 | 424.03 | 0.185594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55652.81 | 20-OCT-12:30 | 55652.81 | 20-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.614180E+10 | 0.00 | 149.29 | 0.541935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54381.75 | 04-NOV-12:30 | 54381.75 | 04-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 98071742.71 | 0.00 | 4.42 | 98071742.71 | 0.00 | 0.00 | 0.00 | 0.00 | 10385.24 | 07-DEC-14:40 | 10385.24 | 07-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215231E+12 | 4230.18 | 0.129773E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.425971E+11 | 0.00 | 735.58 | 0.241141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55652.81 | 55652.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 40840629.10 | 0.00 | 3.56 | 40840629.10 | 0.00 | 0.00 | 0.00 | 0.00 | 42440.57 | 01-JAN-09:02 | 42440.57 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.259247E+09 | 0.00 | 27.39 | 0.259247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65961.39 | 25-FEB-09:02 | 65961.39 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.404430E+10 | 0.00 | 161.86 | 0.316342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70124.96 | 25-MAR-15:01 | 70124.96 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.145687E+11 | 0.00 | 337.62 | 0.105324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88188.25 | 18-APR-15:02 | 76197.19 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.351356E+11 | 0.00 | 542.53 | 0.229208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88616.35 | 29-MAY-18:02 | 75409.88 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.525444E+11 | 0.00 | 582.61 | 0.325444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107398.57 | 26-JUN-08:62 | 75608.33 | 29-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.615779E+11 | 0.00 | 613.40 | 0.358302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103421.59 | 17-JUL-18:02 | 74930.29 | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.558122E+11 | 0.00 | 604.04 | 0.318369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117838.49 | 03-AUG-08:62 | 75735.17 | 09-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.319330E+11 | 0.00 | 523.26 | 0.207343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86349.37 | 11-SEP-08:62 | 75385.48 | 05-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.104905E+11 | 0.00 | 365.64 | 0.823330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72455.28 | 02-OCT-15:01 | 69188.87 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.438740E+10 | 0.00 | 157.31 | 0.269698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68059.88 | 08-NOV-19:02 | 67351.05 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 58764335.11 | 0.00 | 4.19 | 58764335.11 | 0.00 | 0.00 | 0.00 | 0.00 | 50104.19 | 03-DEC-09:02 | 50104.19 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270853E+12 | 3923.39 | 0.168851E+12 | ||||||||||||
Minimum of Months | 40840629.10 | 0.00 | 3.56 | 40840629.10 | 0.00 | 0.00 | 0.00 | 0.00 | 42440.57 | 42440.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.615779E+11 | 0.00 | 613.40 | 0.358302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117838.49 | 76197.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 916691.51 | 0.00 | 0.88 | 916691.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.28 | 12-JAN-09:03 | 2727.28 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 65540410.80 | 0.00 | 12.53 | 64329658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 12041.41 | 24-FEB-09:02 | 12041.41 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.336706E+09 | 0.00 | 87.68 | 0.278979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12766.39 | 25-MAR-15:01 | 12766.39 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.168187E+10 | 0.00 | 240.39 | 0.113583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14052.57 | 18-APR-18:02 | 13157.48 | 16-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.362527E+10 | 0.00 | 530.81 | 0.211776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14528.87 | 26-MAY-15:01 | 13099.67 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.640254E+10 | 0.00 | 603.87 | 0.356088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16010.42 | 30-JUN-08:62 | 13204.39 | 27-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.784651E+10 | 0.00 | 699.97 | 0.415865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16567.40 | 20-JUL-08:62 | 13200.21 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.682802E+10 | 0.00 | 689.84 | 0.345356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18016.57 | 31-AUG-08:62 | 12992.49 | 18-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.421888E+10 | 0.00 | 488.88 | 0.252594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14770.72 | 10-SEP-08:62 | 13109.90 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.841428E+09 | 0.00 | 192.17 | 0.670009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13370.94 | 02-OCT-15:01 | 12758.24 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.151227E+09 | 0.00 | 47.20 | 0.115144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12379.81 | 04-NOV-15:02 | 12379.81 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 13006131.32 | 0.00 | 3.68 | 13006131.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10563.75 | 03-DEC-09:02 | 10563.75 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320119E+11 | 3597.90 | 0.180950E+11 | ||||||||||||
Minimum of Months | 916691.51 | 0.00 | 0.88 | 916691.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.28 | 2727.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.784651E+10 | 0.00 | 699.97 | 0.415865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18016.57 | 13204.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 363592.90 | 0.00 | 0.11 | 363592.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1507.79 | 13-JAN-09:05 | 1507.79 | 13-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 12333277.70 | 0.00 | 4.10 | 12054835.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11540.90 | 24-FEB-09:02 | 11540.90 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.142067E+09 | 0.00 | 43.50 | 0.113709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12158.98 | 28-MAR-08:62 | 12158.98 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.127795E+10 | 0.00 | 195.01 | 0.834476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14419.57 | 14-APR-15:01 | 13073.13 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.329400E+10 | 0.00 | 496.95 | 0.190165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14701.03 | 12-MAY-15:02 | 13094.56 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.618958E+10 | 0.00 | 599.45 | 0.343042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15905.75 | 30-JUN-08:62 | 13116.42 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.748115E+10 | 0.00 | 696.29 | 0.392970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16484.95 | 26-JUL-08:61 | 13051.29 | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.615236E+10 | 0.00 | 677.52 | 0.302798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17913.54 | 31-AUG-08:62 | 13135.27 | 09-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.323490E+10 | 0.00 | 435.58 | 0.180322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14668.48 | 10-SEP-08:62 | 13130.82 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.261501E+09 | 0.00 | 83.85 | 0.189886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12933.09 | 02-OCT-15:01 | 11825.37 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 21070945.45 | 0.00 | 9.94 | 17394456.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9871.52 | 04-NOV-08:62 | 9871.52 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 698973.81 | 0.00 | 0.17 | 698973.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1742.19 | 05-DEC-09:03 | 1742.19 | 05-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280680E+11 | 3242.46 | 0.152616E+11 | ||||||||||||
Minimum of Months | 363592.90 | 0.00 | 0.11 | 363592.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1507.79 | 1507.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.748115E+10 | 0.00 | 696.29 | 0.392970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17913.54 | 13135.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1151366.94 | 0.00 | 0.77 | 1151366.94 | 0.00 | 0.00 | 0.00 | 0.00 | 3453.10 | 12-JAN-16:02 | 3453.10 | 12-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 27764811.87 | 0.00 | 14.87 | 27691145.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3591.98 | 25-FEB-16:02 | 3591.98 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 90484761.62 | 0.00 | 62.08 | 78565751.85 | 0.00 | 0.00 | 0.00 | 0.00 | 3702.93 | 25-MAR-15:01 | 3702.93 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.571768E+09 | 0.00 | 228.30 | 0.424494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4255.09 | 16-APR-08:61 | 3648.08 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.979515E+09 | 0.00 | 474.63 | 0.600786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4606.58 | 29-MAY-08:61 | 3670.61 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.184810E+10 | 0.00 | 581.29 | 0.108024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5192.72 | 26-JUN-08:62 | 3823.80 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.235679E+10 | 0.00 | 689.19 | 0.133127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4987.87 | 20-JUL-08:62 | 3779.25 | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.205352E+10 | 0.00 | 679.78 | 0.112192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5628.39 | 03-AUG-08:62 | 3705.40 | 22-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.118769E+10 | 0.00 | 448.14 | 0.763419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4581.02 | 11-SEP-08:62 | 3700.07 | 11-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.261401E+09 | 0.00 | 148.11 | 0.216055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3883.95 | 02-OCT-15:01 | 3700.52 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 48608481.50 | 0.00 | 28.48 | 39155748.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3590.67 | 04-NOV-15:02 | 3590.67 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 1751300.68 | 0.00 | 0.97 | 1751300.68 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.23 | 02-DEC-16:02 | 3407.23 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.942855E+10 | 3356.62 | 0.568650E+10 | ||||||||||||
Minimum of Months | 1151366.94 | 0.00 | 0.77 | 1151366.94 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.23 | 3407.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.235679E+10 | 0.00 | 689.19 | 0.133127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5628.39 | 3823.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 107888.74 | 0.00 | 0.06 | 107888.74 | 0.00 | 0.00 | 0.00 | 0.00 | 647.90 | 12-JAN-16:03 | 647.90 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 5620621.86 | 0.00 | 6.28 | 5610596.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3376.11 | 24-FEB-16:02 | 3376.11 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 34775655.54 | 0.00 | 35.98 | 29002007.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3641.73 | 25-MAR-15:01 | 3641.73 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.448760E+09 | 0.00 | 192.88 | 0.324335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4214.45 | 16-APR-08:61 | 3622.55 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.892869E+09 | 0.00 | 446.82 | 0.545227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.34 | 29-MAY-08:61 | 3652.36 | 04-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.179417E+10 | 0.00 | 577.12 | 0.104691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5092.85 | 26-JUN-08:62 | 3761.35 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.226323E+10 | 0.00 | 686.67 | 0.127612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4909.36 | 20-JUL-08:62 | 3767.00 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.187682E+10 | 0.00 | 672.03 | 0.100513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.96 | 03-AUG-08:62 | 3764.28 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.933779E+09 | 0.00 | 399.51 | 0.567094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4446.10 | 11-SEP-08:62 | 3752.56 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.114710E+09 | 0.00 | 74.05 | 91139458.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3835.87 | 02-OCT-15:01 | 3639.89 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 16247986.23 | 0.00 | 7.74 | 12337692.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3531.26 | 04-NOV-15:02 | 3531.26 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 104463.92 | 0.00 | 0.05 | 104463.92 | 0.00 | 0.00 | 0.00 | 0.00 | 566.82 | 03-DEC-16:04 | 566.82 | 03-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.838119E+10 | 3099.19 | 0.490311E+10 | ||||||||||||
Minimum of Months | 104463.92 | 0.00 | 0.05 | 104463.92 | 0.00 | 0.00 | 0.00 | 0.00 | 566.82 | 566.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.226323E+10 | 0.00 | 686.67 | 0.127612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.96 | 3767.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.519304E+09 | 0.00 | 58.71 | 0.519304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13916.80 | 13-JAN-16:02 | 13916.80 | 13-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.876420E+09 | 0.00 | 94.34 | 0.872740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13922.79 | 25-FEB-16:02 | 13922.79 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.147101E+10 | 0.00 | 195.83 | 0.130214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13997.93 | 23-MAR-15:01 | 13997.93 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.318116E+10 | 0.00 | 298.40 | 0.234424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16264.49 | 16-APR-08:61 | 14771.72 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.518798E+10 | 0.00 | 549.42 | 0.303030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17592.63 | 31-MAY-08:61 | 14583.97 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.865024E+10 | 0.00 | 607.85 | 0.499808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20756.03 | 26-JUN-08:62 | 14822.74 | 10-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.110214E+11 | 0.00 | 684.34 | 0.617295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19533.42 | 20-JUL-08:62 | 14603.85 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.108900E+11 | 0.00 | 681.60 | 0.628328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22355.80 | 03-AUG-08:62 | 14763.10 | 22-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.783142E+10 | 0.00 | 550.06 | 0.554891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17700.79 | 11-SEP-08:62 | 14668.16 | 16-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.408528E+10 | 0.00 | 379.25 | 0.367167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14631.33 | 02-OCT-15:01 | 14339.78 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.143325E+10 | 0.00 | 167.82 | 0.120348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13918.94 | 04-NOV-15:02 | 13918.94 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.101796E+10 | 0.00 | 89.55 | 0.101796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13921.05 | 02-DEC-16:02 | 13921.05 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561654E+11 | 4357.16 | 0.369651E+11 | ||||||||||||
Minimum of Months | 0.519304E+09 | 0.00 | 58.71 | 0.519304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13916.80 | 13916.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110214E+11 | 0.00 | 684.34 | 0.628328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22355.80 | 14822.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.467832E+10 | 0.00 | 30.83 | 0.467832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96124.08 | 19-MAR-16:00 | 96124.08 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.589696E+11 | 0.00 | 135.67 | 0.453218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 289715.33 | 16-APR-20:20 | 205298.68 | 15-APR-17:10 | 0.00 | 0.00 | 0.00 |
May | 0.147912E+12 | 0.00 | 406.57 | 0.109394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 304582.26 | 30-MAY-19:40 | 209551.56 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.392250E+12 | 0.00 | 561.17 | 0.251160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 381276.28 | 11-JUN-15:10 | 231662.87 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.570797E+12 | 0.00 | 709.50 | 0.322494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 530734.72 | 03-JUL-22:00 | 228856.13 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.491530E+12 | 0.00 | 671.00 | 0.286296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500969.37 | 04-AUG-06:00 | 231644.50 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.189034E+12 | 0.00 | 403.33 | 0.159280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 321605.51 | 11-SEP-19:20 | 225172.39 | 07-SEP-18:03 | 0.00 | 0.00 | 0.00 |
October | 0.152949E+11 | 0.00 | 84.17 | 0.152949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164183.07 | 20-OCT-15:10 | 164183.07 | 20-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.164180E+10 | 0.00 | 30.17 | 0.164180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43931.07 | 03-NOV-14:20 | 43931.07 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187211E+13 | 3032.40 | 0.119556E+13 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.570797E+12 | 0.00 | 709.50 | 0.322494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 530734.72 | 231662.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.212705E+09 | 0.00 | 17.33 | 0.212705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8513.24 | 19-MAR-16:00 | 8513.24 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.324324E+10 | 0.00 | 81.50 | 0.256250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26458.36 | 18-APR-12:20 | 18719.15 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.734146E+10 | 0.00 | 247.83 | 0.558532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29496.52 | 29-MAY-15:02 | 18625.32 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.238603E+11 | 0.00 | 410.83 | 0.154869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36954.70 | 26-JUN-08:62 | 20099.76 | 11-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.356327E+11 | 0.00 | 538.67 | 0.203860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38647.12 | 26-JUL-15:02 | 18987.01 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.294316E+11 | 0.00 | 494.67 | 0.171496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43840.91 | 04-AUG-08:61 | 20394.58 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.107281E+11 | 0.00 | 280.33 | 0.923216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28765.38 | 11-SEP-08:03 | 19475.58 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.650479E+09 | 0.00 | 41.00 | 0.650479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15520.21 | 20-OCT-15:02 | 15520.21 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 24314290.39 | 0.00 | 7.00 | 24314290.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2177.41 | 03-NOV-15:01 | 2177.41 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111125E+12 | 2119.17 | 0.712900E+11 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.356327E+11 | 0.00 | 538.67 | 0.203860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43840.91 | 20394.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.80 | 591.77 | 272.03 | 701.39 | 953.74 | 0.00 | 0.00 | 744.00 |
February | 931.56 | 632.07 | 299.49 | 765.99 | 759.73 | 0.00 | 0.00 | 672.00 |
March | 798.14 | 417.95 | 380.19 | 622.86 | 563.75 | 0.00 | 0.00 | 744.00 |
April | 711.24 | 325.93 | 385.30 | 544.75 | 401.37 | 0.00 | 0.00 | 720.00 |
May | 606.52 | 169.60 | 436.93 | 489.70 | 210.23 | 0.00 | 0.00 | 744.00 |
June | 578.99 | 115.55 | 463.44 | 538.56 | 125.73 | 0.00 | 0.00 | 720.00 |
July | 614.42 | 153.58 | 460.84 | 594.69 | 98.56 | 0.00 | 0.00 | 744.00 |
August | 680.89 | 235.73 | 445.16 | 692.21 | 125.90 | 0.00 | 0.00 | 744.00 |
September | 822.35 | 424.41 | 397.94 | 824.84 | 246.87 | 0.00 | 0.00 | 720.00 |
October | 886.38 | 558.94 | 327.44 | 855.30 | 411.77 | 0.00 | 0.00 | 744.00 |
November | 663.13 | 415.16 | 247.97 | 560.51 | 619.62 | 0.00 | 0.00 | 720.00 |
December | 705.87 | 534.51 | 171.36 | 626.82 | 896.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.51 | 379.87 | 357.64 | 650.90 | 449.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 578.99 | 115.55 | 171.36 | 489.70 | 98.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 931.56 | 632.07 | 463.44 | 855.30 | 953.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2432.41 | 1666.38 | 766.03 | 1961.83 | 2705.73 | 0.00 | 0.00 | 744.00 |
February | 2623.21 | 1779.87 | 843.34 | 2140.02 | 2181.07 | 0.00 | 0.00 | 672.00 |
March | 2247.50 | 1176.92 | 1070.58 | 1731.51 | 1635.67 | 0.00 | 0.00 | 744.00 |
April | 2002.79 | 917.81 | 1084.99 | 1512.10 | 1192.81 | 0.00 | 0.00 | 720.00 |
May | 1707.93 | 477.58 | 1230.35 | 1343.64 | 657.33 | 0.00 | 0.00 | 744.00 |
June | 1630.40 | 325.37 | 1305.02 | 1482.82 | 406.03 | 0.00 | 0.00 | 720.00 |
July | 1730.18 | 432.47 | 1297.71 | 1642.66 | 320.74 | 0.00 | 0.00 | 744.00 |
August | 1917.35 | 663.80 | 1253.55 | 1920.96 | 407.10 | 0.00 | 0.00 | 744.00 |
September | 2315.69 | 1195.11 | 1120.58 | 2296.18 | 759.97 | 0.00 | 0.00 | 720.00 |
October | 2495.99 | 1573.95 | 922.04 | 2381.54 | 1235.70 | 0.00 | 0.00 | 744.00 |
November | 1867.32 | 1169.06 | 698.26 | 1559.80 | 1792.44 | 0.00 | 0.00 | 720.00 |
December | 1987.68 | 1505.14 | 482.54 | 1751.02 | 2549.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2076.78 | 1069.70 | 1007.08 | 1808.70 | 1316.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1630.40 | 325.37 | 482.54 | 1343.64 | 320.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2623.21 | 1779.87 | 1305.02 | 2381.54 | 2705.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3159.84 | 2164.73 | 995.12 | 2583.39 | 3650.50 | 0.00 | 0.00 | 744.00 |
February | 3407.69 | 2312.15 | 1095.55 | 2831.94 | 2931.26 | 0.00 | 0.00 | 672.00 |
March | 2919.63 | 1528.89 | 1390.74 | 2288.14 | 2228.02 | 0.00 | 0.00 | 744.00 |
April | 2601.74 | 1192.28 | 1409.46 | 2005.77 | 1628.54 | 0.00 | 0.00 | 720.00 |
May | 2218.70 | 620.40 | 1598.30 | 1776.11 | 894.37 | 0.00 | 0.00 | 744.00 |
June | 2117.98 | 422.68 | 1695.30 | 1975.91 | 548.03 | 0.00 | 0.00 | 720.00 |
July | 2247.60 | 561.80 | 1685.80 | 2192.85 | 426.48 | 0.00 | 0.00 | 744.00 |
August | 2490.75 | 862.31 | 1628.44 | 2559.90 | 539.33 | 0.00 | 0.00 | 744.00 |
September | 3008.21 | 1552.52 | 1455.69 | 3051.53 | 1020.71 | 0.00 | 0.00 | 720.00 |
October | 3242.43 | 2044.65 | 1197.78 | 3143.17 | 1676.27 | 0.00 | 0.00 | 744.00 |
November | 2425.76 | 1518.67 | 907.08 | 2049.61 | 2447.51 | 0.00 | 0.00 | 720.00 |
December | 2582.11 | 1955.26 | 626.85 | 2307.24 | 3459.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2697.86 | 1389.60 | 1308.26 | 2394.94 | 1782.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 2117.98 | 422.68 | 626.85 | 1776.11 | 426.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3407.69 | 2312.15 | 1695.30 | 3143.17 | 3650.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.48 | 202.93 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 148.04 | 164.43 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 122.10 | 118.43 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.32 | 84.19 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 94.73 | 43.83 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 106.01 | 25.05 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 117.07 | 18.91 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 137.28 | 24.14 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 164.67 | 48.74 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 169.35 | 84.03 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 110.26 | 129.40 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.64 | 186.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 127.98 | 93.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 94.73 | 18.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 169.35 | 202.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 31.42 | 437.42 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 76.41 | 348.93 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 108.95 | 227.12 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 242.06 | 153.15 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 273.36 | 79.02 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 367.92 | 45.86 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 409.80 | 34.93 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 357.46 | 44.63 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 259.11 | 90.25 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 128.73 | 162.86 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 44.69 | 267.24 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 27.28 | 391.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 194.52 | 189.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 27.28 | 34.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 409.80 | 437.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.76 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.46 | 201.01 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 9.90 | 128.77 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.61 | 84.53 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 56.82 | 40.75 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 88.13 | 23.03 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 88.11 | 17.64 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 76.66 | 22.86 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 45.72 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.44 | 89.56 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.87 | 148.98 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 34.18 | 105.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 88.13 | 248.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 32.83 | 433.21 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 79.14 | 343.94 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 112.74 | 224.36 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 244.88 | 151.87 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 274.75 | 78.54 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 368.57 | 45.59 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 410.61 | 34.67 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 358.94 | 44.20 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 262.26 | 89.16 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 133.81 | 160.18 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 47.22 | 264.00 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 29.03 | 387.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 196.81 | 187.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 29.03 | 34.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 410.61 | 433.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.33 | 93.39 | 42.93 | 111.48 | 147.22 | 0.00 | 0.00 | 744.00 |
February | 147.02 | 99.75 | 47.27 | 117.29 | 134.43 | 0.00 | 0.00 | 672.00 |
March | 125.96 | 65.96 | 60.00 | 92.59 | 104.82 | 0.00 | 0.00 | 744.00 |
April | 112.25 | 51.44 | 60.81 | 78.10 | 89.67 | 0.00 | 0.00 | 720.00 |
May | 95.72 | 26.77 | 68.96 | 62.88 | 54.88 | 0.00 | 0.00 | 744.00 |
June | 91.38 | 18.24 | 73.14 | 71.18 | 37.28 | 0.00 | 0.00 | 720.00 |
July | 96.97 | 24.24 | 72.73 | 79.90 | 30.75 | 0.00 | 0.00 | 744.00 |
August | 107.46 | 37.20 | 70.26 | 96.71 | 36.87 | 0.00 | 0.00 | 744.00 |
September | 129.78 | 66.98 | 62.80 | 120.46 | 61.10 | 0.00 | 0.00 | 720.00 |
October | 139.89 | 88.21 | 51.68 | 123.97 | 92.90 | 0.00 | 0.00 | 744.00 |
November | 104.65 | 65.52 | 39.13 | 82.02 | 121.18 | 0.00 | 0.00 | 720.00 |
December | 111.40 | 84.36 | 27.04 | 98.86 | 140.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.39 | 59.95 | 56.44 | 94.51 | 87.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 91.38 | 18.24 | 27.04 | 62.88 | 30.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 147.02 | 99.75 | 73.14 | 123.97 | 147.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.86 | 0.00 | 21.86 | 0.00 | 205.28 | 0.00 | 0.00 | 744.00 |
February | 27.72 | 0.00 | 27.72 | 0.25 | 165.71 | 0.00 | 0.00 | 672.00 |
March | 41.55 | 0.00 | 41.55 | 7.39 | 106.37 | 0.00 | 0.00 | 744.00 |
April | 48.15 | 0.39 | 47.76 | 21.17 | 69.01 | 0.00 | 0.00 | 720.00 |
May | 62.60 | 2.37 | 60.24 | 47.09 | 32.71 | 0.00 | 0.00 | 744.00 |
June | 73.26 | 6.78 | 66.48 | 73.34 | 18.15 | 0.00 | 0.00 | 720.00 |
July | 68.71 | 4.73 | 63.98 | 73.95 | 13.36 | 0.00 | 0.00 | 744.00 |
August | 57.57 | 1.16 | 56.41 | 64.35 | 17.70 | 0.00 | 0.00 | 744.00 |
September | 44.06 | 0.04 | 44.02 | 38.10 | 39.28 | 0.00 | 0.00 | 720.00 |
October | 32.72 | 0.00 | 32.72 | 10.29 | 73.57 | 0.00 | 0.00 | 744.00 |
November | 22.89 | 0.00 | 22.89 | 2.01 | 124.15 | 0.00 | 0.00 | 720.00 |
December | 14.85 | 0.00 | 14.85 | 0.00 | 180.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.08 | 1.29 | 41.78 | 28.33 | 86.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.85 | 0.00 | 14.85 | 0.00 | 13.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.26 | 6.78 | 66.48 | 73.95 | 205.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 25.87 | 430.85 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 56.56 | 341.80 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 112.90 | 221.15 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 193.84 | 148.89 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 299.51 | 74.21 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.08 | 43.17 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 392.10 | 32.49 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 329.24 | 41.51 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 264.73 | 87.36 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 108.38 | 156.97 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 31.50 | 262.33 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.47 | 386.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 184.54 | 184.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.47 | 32.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 392.10 | 430.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 136.26 | 202.74 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 147.73 | 163.76 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 121.14 | 118.20 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 106.81 | 83.40 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 93.45 | 43.81 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 105.19 | 24.85 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 116.49 | 18.46 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 136.88 | 23.77 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 163.74 | 48.43 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 168.76 | 83.67 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 110.14 | 129.15 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 123.58 | 186.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 127.41 | 93.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 93.45 | 18.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 168.76 | 202.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 248.69 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.36 | 200.42 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 9.46 | 129.07 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.25 | 83.86 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 55.51 | 40.81 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 87.30 | 22.84 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 87.53 | 17.19 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 76.26 | 22.52 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 44.79 | 48.80 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.02 | 89.32 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.79 | 148.75 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 217.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 33.72 | 105.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 17.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 87.53 | 248.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 26.48 | 425.82 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 57.96 | 335.34 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 115.87 | 217.61 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 196.47 | 147.36 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 300.72 | 73.74 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.75 | 42.97 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 392.91 | 32.28 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 330.64 | 41.09 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 267.51 | 86.22 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 112.84 | 153.69 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 33.10 | 258.16 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.92 | 381.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 186.29 | 182.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.92 | 32.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 392.91 | 425.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.00 | 321.46 | 0.00 | 0.00 | 744.00 |
February | 43.87 | 0.00 | 43.87 | 0.39 | 253.85 | 0.00 | 0.00 | 672.00 |
March | 65.76 | 0.00 | 65.76 | 12.40 | 165.71 | 0.00 | 0.00 | 744.00 |
April | 76.21 | 0.61 | 75.60 | 35.17 | 106.41 | 0.00 | 0.00 | 720.00 |
May | 99.09 | 3.74 | 95.34 | 78.99 | 49.88 | 0.00 | 0.00 | 744.00 |
June | 115.95 | 10.73 | 105.22 | 120.36 | 27.67 | 0.00 | 0.00 | 720.00 |
July | 108.76 | 7.49 | 101.27 | 121.05 | 20.65 | 0.00 | 0.00 | 744.00 |
August | 91.13 | 1.84 | 89.29 | 105.54 | 27.34 | 0.00 | 0.00 | 744.00 |
September | 69.74 | 0.06 | 69.68 | 62.61 | 60.65 | 0.00 | 0.00 | 720.00 |
October | 51.79 | 0.00 | 51.79 | 17.40 | 113.64 | 0.00 | 0.00 | 744.00 |
November | 36.23 | 0.00 | 36.23 | 3.50 | 193.89 | 0.00 | 0.00 | 720.00 |
December | 23.50 | 0.00 | 23.50 | 0.00 | 284.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.18 | 2.05 | 66.13 | 46.73 | 134.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.50 | 0.00 | 23.50 | 0.00 | 20.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 115.95 | 10.73 | 105.22 | 121.05 | 321.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.00 | 118.50 | 0.00 | 0.00 | 744.00 |
February | 16.17 | 0.00 | 16.17 | 0.14 | 93.58 | 0.00 | 0.00 | 672.00 |
March | 24.24 | 0.00 | 24.24 | 4.57 | 61.09 | 0.00 | 0.00 | 744.00 |
April | 28.10 | 0.23 | 27.87 | 12.96 | 39.23 | 0.00 | 0.00 | 720.00 |
May | 36.53 | 1.38 | 35.15 | 29.12 | 18.39 | 0.00 | 0.00 | 744.00 |
June | 42.74 | 3.96 | 38.79 | 44.37 | 10.20 | 0.00 | 0.00 | 720.00 |
July | 40.09 | 2.76 | 37.33 | 44.62 | 7.61 | 0.00 | 0.00 | 744.00 |
August | 33.59 | 0.68 | 32.92 | 38.91 | 10.08 | 0.00 | 0.00 | 744.00 |
September | 25.71 | 0.02 | 25.69 | 23.08 | 22.36 | 0.00 | 0.00 | 720.00 |
October | 19.09 | 0.00 | 19.09 | 6.42 | 41.89 | 0.00 | 0.00 | 744.00 |
November | 13.35 | 0.00 | 13.35 | 1.29 | 71.48 | 0.00 | 0.00 | 720.00 |
December | 8.66 | 0.00 | 8.66 | 0.00 | 104.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.13 | 0.75 | 24.38 | 17.23 | 49.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.66 | 0.00 | 8.66 | 0.00 | 7.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 42.74 | 3.96 | 38.79 | 44.62 | 118.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.53 | 54.48 | 25.05 | 63.77 | 95.35 | 0.00 | 0.00 | 744.00 |
February | 85.76 | 58.19 | 27.57 | 70.24 | 75.55 | 0.00 | 0.00 | 672.00 |
March | 73.48 | 38.48 | 35.00 | 57.73 | 55.37 | 0.00 | 0.00 | 744.00 |
April | 65.48 | 30.01 | 35.47 | 51.76 | 38.68 | 0.00 | 0.00 | 720.00 |
May | 55.84 | 15.61 | 40.23 | 47.02 | 19.49 | 0.00 | 0.00 | 744.00 |
June | 53.31 | 10.64 | 42.67 | 52.79 | 10.93 | 0.00 | 0.00 | 720.00 |
July | 56.57 | 14.14 | 42.43 | 58.27 | 8.03 | 0.00 | 0.00 | 744.00 |
August | 62.69 | 21.70 | 40.98 | 67.47 | 10.44 | 0.00 | 0.00 | 744.00 |
September | 75.71 | 39.07 | 36.64 | 79.32 | 21.95 | 0.00 | 0.00 | 720.00 |
October | 81.61 | 51.46 | 30.15 | 80.61 | 38.70 | 0.00 | 0.00 | 744.00 |
November | 61.05 | 38.22 | 22.83 | 51.84 | 61.06 | 0.00 | 0.00 | 720.00 |
December | 64.99 | 49.21 | 15.78 | 57.83 | 88.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.90 | 34.97 | 32.93 | 61.51 | 43.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.31 | 10.64 | 15.78 | 47.02 | 8.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.76 | 58.19 | 42.67 | 80.61 | 95.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.85 | 147.87 | 67.98 | 173.09 | 258.80 | 0.00 | 0.00 | 744.00 |
February | 232.78 | 157.95 | 74.84 | 190.65 | 205.06 | 0.00 | 0.00 | 672.00 |
March | 199.44 | 104.44 | 95.00 | 156.70 | 150.30 | 0.00 | 0.00 | 744.00 |
April | 177.73 | 81.45 | 96.28 | 140.48 | 104.98 | 0.00 | 0.00 | 720.00 |
May | 151.56 | 42.38 | 109.18 | 127.63 | 52.91 | 0.00 | 0.00 | 744.00 |
June | 144.68 | 28.87 | 115.81 | 143.28 | 29.66 | 0.00 | 0.00 | 720.00 |
July | 153.54 | 38.38 | 115.16 | 158.16 | 21.79 | 0.00 | 0.00 | 744.00 |
August | 170.15 | 58.91 | 111.24 | 183.14 | 28.34 | 0.00 | 0.00 | 744.00 |
September | 205.49 | 106.05 | 99.44 | 215.29 | 59.56 | 0.00 | 0.00 | 720.00 |
October | 221.49 | 139.67 | 81.82 | 218.78 | 105.03 | 0.00 | 0.00 | 744.00 |
November | 165.71 | 103.74 | 61.96 | 140.69 | 165.72 | 0.00 | 0.00 | 720.00 |
December | 176.39 | 133.57 | 42.82 | 156.95 | 241.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.29 | 94.93 | 89.37 | 166.95 | 118.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 144.68 | 28.87 | 42.82 | 127.63 | 21.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 232.78 | 157.95 | 115.81 | 218.78 | 258.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 135.92 | 203.63 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 147.38 | 165.07 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 121.99 | 118.54 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 106.98 | 84.29 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 93.78 | 44.18 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 105.08 | 25.25 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 116.05 | 19.08 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 136.32 | 24.41 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 164.08 | 48.77 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 168.96 | 83.97 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 110.08 | 129.46 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 123.47 | 187.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 127.41 | 94.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 93.78 | 19.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 168.96 | 203.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 31.28 | 439.53 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 75.86 | 351.16 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 108.72 | 227.36 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 240.60 | 153.27 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 270.71 | 79.51 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 365.20 | 46.15 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 406.88 | 35.19 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 354.78 | 45.05 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 257.64 | 90.29 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 128.24 | 162.64 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 44.84 | 267.11 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 27.40 | 392.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 193.26 | 190.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 27.40 | 35.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 406.88 | 439.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 249.72 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.48 | 201.90 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 10.06 | 128.74 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 25.31 | 84.61 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 55.58 | 41.02 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 86.84 | 23.21 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 86.78 | 17.78 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 75.43 | 23.07 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 45.19 | 48.86 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 13.68 | 89.12 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 2.98 | 148.56 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 217.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 33.73 | 105.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 17.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 86.84 | 249.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 32.66 | 435.36 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 78.75 | 346.12 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 112.64 | 224.63 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 243.59 | 151.89 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 272.08 | 79.01 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 365.81 | 45.88 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 407.65 | 34.94 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 356.21 | 44.61 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 260.87 | 89.11 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 133.90 | 159.68 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 47.53 | 263.90 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 29.15 | 388.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 195.65 | 187.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 29.15 | 34.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 407.65 | 435.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.17 | 171.39 | 78.79 | 191.79 | 306.12 | 0.00 | 0.00 | 744.00 |
February | 269.80 | 183.06 | 86.74 | 209.06 | 249.29 | 0.00 | 0.00 | 672.00 |
March | 231.15 | 121.05 | 110.11 | 173.59 | 178.20 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 94.40 | 111.59 | 155.76 | 124.64 | 0.00 | 0.00 | 720.00 |
May | 175.66 | 49.12 | 126.54 | 138.44 | 64.28 | 0.00 | 0.00 | 744.00 |
June | 167.69 | 33.46 | 134.22 | 157.23 | 36.10 | 0.00 | 0.00 | 720.00 |
July | 177.95 | 44.48 | 133.47 | 173.96 | 26.55 | 0.00 | 0.00 | 744.00 |
August | 197.20 | 68.27 | 128.93 | 202.22 | 34.79 | 0.00 | 0.00 | 744.00 |
September | 238.17 | 122.92 | 115.25 | 239.80 | 72.04 | 0.00 | 0.00 | 720.00 |
October | 256.71 | 161.88 | 94.83 | 243.13 | 126.70 | 0.00 | 0.00 | 744.00 |
November | 192.05 | 120.24 | 71.82 | 156.28 | 196.23 | 0.00 | 0.00 | 720.00 |
December | 204.43 | 154.80 | 49.63 | 174.93 | 282.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.60 | 110.02 | 103.58 | 184.56 | 140.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 167.69 | 33.46 | 49.63 | 138.44 | 26.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 269.80 | 183.06 | 134.22 | 243.13 | 306.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1843.27 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.72 | 1479.74 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 50.40 | 1024.99 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 160.63 | 688.73 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 370.39 | 346.77 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 589.88 | 210.23 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 595.74 | 165.61 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 520.31 | 210.88 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 303.86 | 413.25 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 71.20 | 731.04 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 12.15 | 1176.05 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1673.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 224.29 | 827.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 165.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 595.74 | 1843.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1878.23 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.40 | 1512.27 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 45.07 | 1054.47 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 151.76 | 710.45 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 354.95 | 358.80 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 575.04 | 219.05 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 581.26 | 173.21 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 506.41 | 220.25 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 292.73 | 428.07 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 63.77 | 754.35 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 10.06 | 1208.20 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1711.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 216.42 | 849.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 173.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 581.26 | 1878.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 238.08 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.65 | 187.05 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 12.47 | 129.61 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 33.59 | 85.35 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 73.26 | 44.11 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 108.85 | 26.53 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 110.85 | 20.04 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 97.69 | 25.40 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 60.34 | 49.95 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 18.66 | 89.16 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 4.61 | 146.95 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 216.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 43.67 | 104.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 20.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 110.85 | 238.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 218.23 | 89.44 | 128.79 | 61.31 | 822.19 | 0.00 | 0.00 | 744.00 |
February | 290.57 | 127.90 | 162.68 | 128.34 | 632.49 | 0.00 | 0.00 | 672.00 |
March | 394.65 | 156.59 | 238.06 | 249.65 | 445.13 | 0.00 | 0.00 | 744.00 |
April | 481.67 | 209.93 | 271.73 | 428.71 | 306.65 | 0.00 | 0.00 | 720.00 |
May | 608.53 | 266.12 | 342.41 | 668.70 | 162.36 | 0.00 | 0.00 | 744.00 |
June | 668.73 | 291.27 | 377.46 | 829.20 | 100.28 | 0.00 | 0.00 | 720.00 |
July | 676.06 | 312.03 | 364.04 | 872.83 | 75.98 | 0.00 | 0.00 | 744.00 |
August | 570.03 | 245.65 | 324.38 | 741.71 | 95.10 | 0.00 | 0.00 | 744.00 |
September | 510.75 | 242.25 | 268.49 | 597.51 | 181.31 | 0.00 | 0.00 | 720.00 |
October | 323.41 | 134.61 | 188.80 | 254.02 | 314.03 | 0.00 | 0.00 | 744.00 |
November | 191.31 | 62.09 | 129.22 | 76.80 | 516.34 | 0.00 | 0.00 | 720.00 |
December | 147.64 | 63.22 | 84.42 | 38.37 | 760.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 424.12 | 183.68 | 240.44 | 413.82 | 366.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 147.64 | 62.09 | 84.42 | 38.37 | 75.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 676.06 | 312.03 | 377.46 | 872.83 | 822.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 141.97 | 194.99 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 156.64 | 154.72 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 128.26 | 119.30 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 117.03 | 84.83 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 111.07 | 46.54 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 126.23 | 28.31 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 139.55 | 21.09 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 158.21 | 26.45 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 181.29 | 49.72 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 180.27 | 84.76 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 115.92 | 128.76 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 127.43 | 185.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 140.24 | 93.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 111.07 | 21.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 181.29 | 194.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.63 | 0.00 | 34.63 | 0.00 | 324.16 | 0.00 | 0.00 | 744.00 |
February | 43.91 | 0.00 | 43.91 | 0.25 | 254.03 | 0.00 | 0.00 | 672.00 |
March | 65.82 | 0.00 | 65.82 | 11.13 | 169.55 | 0.00 | 0.00 | 744.00 |
April | 76.28 | 0.61 | 75.66 | 32.16 | 110.45 | 0.00 | 0.00 | 720.00 |
May | 99.17 | 3.75 | 95.42 | 73.10 | 53.86 | 0.00 | 0.00 | 744.00 |
June | 116.05 | 10.74 | 105.31 | 111.25 | 32.41 | 0.00 | 0.00 | 720.00 |
July | 108.85 | 7.49 | 101.35 | 111.26 | 25.75 | 0.00 | 0.00 | 744.00 |
August | 91.20 | 1.84 | 89.37 | 97.02 | 32.64 | 0.00 | 0.00 | 744.00 |
September | 69.80 | 0.06 | 69.74 | 57.45 | 65.35 | 0.00 | 0.00 | 720.00 |
October | 51.83 | 0.00 | 51.83 | 15.35 | 117.35 | 0.00 | 0.00 | 744.00 |
November | 36.26 | 0.00 | 36.26 | 2.94 | 197.68 | 0.00 | 0.00 | 720.00 |
December | 23.52 | 0.00 | 23.52 | 0.00 | 289.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.24 | 2.05 | 66.19 | 42.92 | 138.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 0.00 | 25.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.05 | 10.74 | 105.31 | 111.26 | 324.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.99 | 0.00 | 30.99 | 0.00 | 290.02 | 0.00 | 0.00 | 744.00 |
February | 39.29 | 0.00 | 39.29 | 0.23 | 227.28 | 0.00 | 0.00 | 672.00 |
March | 58.89 | 0.00 | 58.89 | 9.96 | 151.69 | 0.00 | 0.00 | 744.00 |
April | 68.24 | 0.55 | 67.70 | 28.77 | 98.82 | 0.00 | 0.00 | 720.00 |
May | 88.73 | 3.35 | 85.38 | 65.40 | 48.19 | 0.00 | 0.00 | 744.00 |
June | 103.83 | 9.61 | 94.22 | 99.54 | 29.00 | 0.00 | 0.00 | 720.00 |
July | 97.38 | 6.70 | 90.68 | 99.54 | 23.04 | 0.00 | 0.00 | 744.00 |
August | 81.60 | 1.64 | 79.96 | 86.80 | 29.21 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 0.06 | 62.39 | 51.40 | 58.47 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 0.00 | 46.37 | 13.73 | 104.99 | 0.00 | 0.00 | 744.00 |
November | 32.44 | 0.00 | 32.44 | 2.63 | 176.86 | 0.00 | 0.00 | 720.00 |
December | 21.04 | 0.00 | 21.04 | 0.00 | 258.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.05 | 1.83 | 59.22 | 38.40 | 124.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.00 | 23.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.83 | 9.61 | 94.22 | 99.54 | 290.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.83 | 436.27 | 200.55 | 505.46 | 768.36 | 0.00 | 0.00 | 744.00 |
February | 686.78 | 465.98 | 220.79 | 558.75 | 604.68 | 0.00 | 0.00 | 672.00 |
March | 588.42 | 308.13 | 280.29 | 454.28 | 452.65 | 0.00 | 0.00 | 744.00 |
April | 524.35 | 240.29 | 284.06 | 404.61 | 321.37 | 0.00 | 0.00 | 720.00 |
May | 447.15 | 125.03 | 322.12 | 360.00 | 169.04 | 0.00 | 0.00 | 744.00 |
June | 426.85 | 85.19 | 341.67 | 397.30 | 103.09 | 0.00 | 0.00 | 720.00 |
July | 452.98 | 113.22 | 339.75 | 438.89 | 80.74 | 0.00 | 0.00 | 744.00 |
August | 501.98 | 173.79 | 328.19 | 515.67 | 100.35 | 0.00 | 0.00 | 744.00 |
September | 606.27 | 312.89 | 293.38 | 618.70 | 189.78 | 0.00 | 0.00 | 720.00 |
October | 653.47 | 412.07 | 241.40 | 634.80 | 319.26 | 0.00 | 0.00 | 744.00 |
November | 488.88 | 306.07 | 182.81 | 408.39 | 498.40 | 0.00 | 0.00 | 720.00 |
December | 520.39 | 394.06 | 126.33 | 457.51 | 720.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.72 | 280.06 | 263.66 | 479.12 | 359.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 426.85 | 85.19 | 126.33 | 360.00 | 80.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 686.78 | 465.98 | 341.67 | 634.80 | 768.36 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.187860E+10 | 0.255451E+10 |
February | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.185308E+10 | 0.183793E+10 |
March | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.166828E+10 | 0.150995E+10 |
April | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.141200E+10 | 0.104036E+10 |
May | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.131161E+10 | 0.563071E+09 |
June | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.139595E+10 | 0.325895E+09 |
July | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.159281E+10 | 0.263984E+09 |
August | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.185402E+10 | 0.337223E+09 |
September | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.213799E+10 | 0.639897E+09 |
October | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.229084E+10 | 0.110289E+10 |
November | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.145285E+10 | 0.160606E+10 |
December | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.167887E+10 | 0.240176E+10 |
Annual Sum or Average | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.205269E+11 | 0.141835E+11 |
Minimum of Months | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.131161E+10 | 0.263984E+09 |
Maximum of Months | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.229084E+10 | 0.255451E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.525455E+10 | 0.724703E+10 |
February | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.517714E+10 | 0.527644E+10 |
March | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.463768E+10 | 0.438099E+10 |
April | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.391936E+10 | 0.309177E+10 |
May | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.359880E+10 | 0.176060E+10 |
June | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.384347E+10 | 0.105244E+10 |
July | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.439971E+10 | 0.859073E+09 |
August | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.514511E+10 | 0.109038E+10 |
September | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.595169E+10 | 0.196985E+10 |
October | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.637872E+10 | 0.330970E+10 |
November | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.404300E+10 | 0.464601E+10 |
December | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.468994E+10 | 0.682819E+10 |
Annual Sum or Average | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.570392E+11 | 0.415125E+11 |
Minimum of Months | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.359880E+10 | 0.859073E+09 |
Maximum of Months | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.637872E+10 | 0.724703E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.691936E+10 | 0.977751E+10 |
February | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.685103E+10 | 0.709129E+10 |
March | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.612857E+10 | 0.596753E+10 |
April | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.519894E+10 | 0.422116E+10 |
May | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.475713E+10 | 0.239547E+10 |
June | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.512156E+10 | 0.142050E+10 |
July | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.587332E+10 | 0.114227E+10 |
August | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.685644E+10 | 0.144455E+10 |
September | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.790958E+10 | 0.264569E+10 |
October | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.841866E+10 | 0.448973E+10 |
November | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.531258E+10 | 0.634396E+10 |
December | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.617972E+10 | 0.926647E+10 |
Annual Sum or Average | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.755269E+11 | 0.562061E+11 |
Minimum of Months | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.475713E+10 | 0.114227E+10 |
Maximum of Months | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.841866E+10 | 0.977751E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.365535E+09 | 0.543529E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.358150E+09 | 0.397796E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.327039E+09 | 0.317204E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.278165E+09 | 0.218227E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.253724E+09 | 0.117400E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.274783E+09 | 64924418.12 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.313555E+09 | 50657265.48 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.367697E+09 | 64665003.15 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.426816E+09 | 0.126324E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.453574E+09 | 0.225077E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.285793E+09 | 0.335395E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.331165E+09 | 0.500526E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.403599E+10 | 0.296172E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.253724E+09 | 50657265.48 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.453574E+09 | 0.543529E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 84147480.79 | 0.117158E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.184858E+09 | 0.844123E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.291810E+09 | 0.608325E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.627423E+09 | 0.396957E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.732161E+09 | 0.211644E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.953659E+09 | 0.118862E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109760E+10 | 93549906.55 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.957414E+09 | 0.119529E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.671608E+09 | 0.233932E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.344802E+09 | 0.436193E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.115847E+09 | 0.692679E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 73070201.36 | 0.104851E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.613440E+10 | 0.597588E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 73070201.36 | 93549906.55 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109760E+10 | 0.117158E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 4564.71 | 0.666292E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 1100969.22 | 0.486276E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 26522973.16 | 0.344904E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 66391801.30 | 0.219107E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.152173E+09 | 0.109147E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.228435E+09 | 59701382.48 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.235982E+09 | 47248545.09 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.205313E+09 | 61215303.66 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.118506E+09 | 0.126755E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 35992125.23 | 0.239871E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7430687.95 | 0.386144E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.582652E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.107785E+10 | 0.332931E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 47248545.09 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.235982E+09 | 0.666292E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 87920266.55 | 0.116032E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.191453E+09 | 0.832052E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.301970E+09 | 0.600937E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.634726E+09 | 0.393635E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.735879E+09 | 0.210363E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.955329E+09 | 0.118176E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109977E+10 | 92867881.76 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.961387E+09 | 0.118385E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.679765E+09 | 0.231092E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.358391E+09 | 0.429030E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.122385E+09 | 0.684290E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 77759670.63 | 0.103669E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.620674E+10 | 0.590784E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 77759670.63 | 92867881.76 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109977E+10 | 0.116032E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.298601E+09 | 0.394311E+09 |
February | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.283754E+09 | 0.325217E+09 |
March | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.247983E+09 | 0.280751E+09 |
April | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.202425E+09 | 0.232417E+09 |
May | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.168410E+09 | 0.146997E+09 |
June | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.184509E+09 | 96636876.11 |
July | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.214016E+09 | 82358264.93 |
August | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.259015E+09 | 98753255.99 |
September | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.312242E+09 | 0.158375E+09 |
October | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.332039E+09 | 0.248810E+09 |
November | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.212590E+09 | 0.314102E+09 |
December | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.264784E+09 | 0.377004E+09 |
Annual Sum or Average | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.298037E+10 | 0.275573E+10 |
Minimum of Months | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.168410E+09 | 82358264.93 |
Maximum of Months | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.332039E+09 | 0.394311E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.549821E+09 |
February | 67056690.67 | 0.00 | 67056690.67 | 602525.78 | 0.400886E+09 |
March | 0.111280E+09 | 941.15 | 0.111279E+09 | 19794008.25 | 0.284894E+09 |
April | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 54885343.75 | 0.178876E+09 |
May | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.126130E+09 | 87600738.03 |
June | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.190106E+09 | 47043064.44 |
July | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.198057E+09 | 35789374.85 |
August | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.172365E+09 | 47408691.54 |
September | 0.114208E+09 | 102488.46 | 0.114105E+09 | 98753825.97 | 0.101819E+09 |
October | 87633982.09 | 0.00 | 87633982.09 | 27568243.35 | 0.197061E+09 |
November | 59323427.52 | 0.00 | 59323427.52 | 5214569.50 | 0.321793E+09 |
December | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.483225E+09 |
Annual Sum or Average | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.893477E+09 | 0.273622E+10 |
Minimum of Months | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 35789374.85 |
Maximum of Months | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.198057E+09 | 0.549821E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 69296803.01 | 0.115398E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.136836E+09 | 0.826872E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.302396E+09 | 0.592323E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.502441E+09 | 0.385929E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.802204E+09 | 0.198753E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.969613E+09 | 0.111909E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105019E+10 | 87034551.77 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.881826E+09 | 0.111171E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.686170E+09 | 0.226429E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.290283E+09 | 0.420433E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 81636766.96 | 0.679965E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 46783408.04 | 0.103635E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.581968E+10 | 0.583115E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 46783408.04 | 87034551.77 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105019E+10 | 0.115398E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.364950E+09 | 0.543017E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.357390E+09 | 0.396168E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.324461E+09 | 0.316596E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.276853E+09 | 0.216176E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.250287E+09 | 0.117330E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.272647E+09 | 64398750.89 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.312000E+09 | 49440630.10 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.366622E+09 | 63660705.88 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.424413E+09 | 0.125534E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.452012E+09 | 0.224112E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.285482E+09 | 0.334756E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.330986E+09 | 0.500027E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.401810E+10 | 0.295122E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.250287E+09 | 49440630.10 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.452012E+09 | 0.543017E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 1007.58 | 0.666087E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 879185.71 | 0.484851E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 25344673.16 | 0.345698E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 65456249.15 | 0.217360E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.148666E+09 | 0.109298E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.226294E+09 | 59192242.10 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.234428E+09 | 46043267.31 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.204254E+09 | 60313120.66 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.116085E+09 | 0.126493E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 34876854.27 | 0.239233E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7226745.45 | 0.385565E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.582633E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.106351E+10 | 0.332277E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 46043267.31 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.234428E+09 | 0.666087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 70923709.89 | 0.114053E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.140225E+09 | 0.811253E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.310359E+09 | 0.582854E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.509251E+09 | 0.381959E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.805441E+09 | 0.197517E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.971364E+09 | 0.111368E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105238E+10 | 86452855.47 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.885576E+09 | 0.110052E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.693383E+09 | 0.223488E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.302237E+09 | 0.411649E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 85798191.17 | 0.669163E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 47994312.12 | 0.102155E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.587493E+10 | 0.574783E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 47994312.12 | 86452855.47 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105238E+10 | 0.114053E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92689285.68 | 0.00 | 92689285.68 | 0.00 | 0.861002E+09 |
February | 0.106140E+09 | 0.00 | 0.106140E+09 | 948326.35 | 0.614120E+09 |
March | 0.176138E+09 | 1489.68 | 0.176137E+09 | 33202562.11 | 0.443841E+09 |
April | 0.197544E+09 | 1584139.79 | 0.195960E+09 | 91148818.02 | 0.275817E+09 |
May | 0.265400E+09 | 10027981.57 | 0.255372E+09 | 0.211564E+09 | 0.133612E+09 |
June | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.311972E+09 | 71718009.82 |
July | 0.291293E+09 | 20051601.33 | 0.271241E+09 | 0.324221E+09 | 55314553.77 |
August | 0.244082E+09 | 4919085.54 | 0.239163E+09 | 0.282670E+09 | 73229256.40 |
September | 0.180773E+09 | 162222.46 | 0.180610E+09 | 0.162287E+09 | 0.157195E+09 |
October | 0.138710E+09 | 0.00 | 0.138710E+09 | 46613100.99 | 0.304369E+09 |
November | 93899275.44 | 0.00 | 93899275.44 | 9064173.89 | 0.502565E+09 |
December | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 0.762809E+09 |
Annual Sum or Average | 0.215016E+10 | 64566489.21 | 0.208559E+10 | 0.147369E+10 | 0.425559E+10 |
Minimum of Months | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 55314553.77 |
Maximum of Months | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.324221E+09 | 0.861002E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34169108.66 | 0.00 | 34169108.66 | 0.00 | 0.317401E+09 |
February | 39127512.35 | 0.00 | 39127512.35 | 349592.36 | 0.226390E+09 |
March | 64931807.30 | 549.16 | 64931258.14 | 12239839.20 | 0.163618E+09 |
April | 72822870.96 | 583979.52 | 72238891.44 | 33601228.50 | 0.101677E+09 |
May | 97837340.20 | 3696729.23 | 94140610.97 | 77991253.17 | 49254744.01 |
June | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.115006E+09 | 26438228.03 |
July | 0.107383E+09 | 7391850.52 | 99990758.17 | 0.119521E+09 | 20391234.91 |
August | 89978876.20 | 1813378.61 | 88165497.59 | 0.104204E+09 | 26995336.10 |
September | 66640246.57 | 59801.92 | 66580444.66 | 59825573.29 | 57948519.40 |
October | 51134341.44 | 0.00 | 51134341.44 | 17183519.12 | 0.112203E+09 |
November | 34615160.99 | 0.00 | 34615160.99 | 3341429.82 | 0.185266E+09 |
December | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 0.281203E+09 |
Annual Sum or Average | 0.792636E+09 | 23801881.41 | 0.768834E+09 | 0.543264E+09 | 0.156879E+10 |
Minimum of Months | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 20391234.91 |
Maximum of Months | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.119521E+09 | 0.317401E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213005E+09 | 0.145924E+09 | 67080677.26 | 0.170804E+09 | 0.255389E+09 |
February | 0.207482E+09 | 0.140778E+09 | 66703954.00 | 0.169927E+09 | 0.182776E+09 |
March | 0.196812E+09 | 0.103063E+09 | 93749766.36 | 0.154636E+09 | 0.148316E+09 |
April | 0.169726E+09 | 77778998.96 | 91946673.79 | 0.134153E+09 | 0.100249E+09 |
May | 0.149563E+09 | 41821325.16 | 0.107741E+09 | 0.125949E+09 | 52208521.45 |
June | 0.138167E+09 | 27573501.09 | 0.110594E+09 | 0.136827E+09 | 28327496.46 |
July | 0.151510E+09 | 37870946.71 | 0.113640E+09 | 0.156070E+09 | 21502512.83 |
August | 0.167901E+09 | 58128357.07 | 0.109773E+09 | 0.180724E+09 | 27965069.26 |
September | 0.196242E+09 | 0.101279E+09 | 94962720.04 | 0.205592E+09 | 56882678.58 |
October | 0.218572E+09 | 0.137830E+09 | 80742463.40 | 0.215897E+09 | 0.103648E+09 |
November | 0.158245E+09 | 99071298.74 | 59174088.99 | 0.134359E+09 | 0.158256E+09 |
December | 0.174060E+09 | 0.131804E+09 | 42256009.05 | 0.154882E+09 | 0.237911E+09 |
Annual Sum or Average | 0.214129E+10 | 0.110292E+10 | 0.103836E+10 | 0.193982E+10 | 0.137343E+10 |
Minimum of Months | 0.138167E+09 | 27573501.09 | 42256009.05 | 0.125949E+09 | 21502512.83 |
Maximum of Months | 0.218572E+09 | 0.145924E+09 | 0.113640E+09 | 0.215897E+09 | 0.255389E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578139E+09 | 0.396068E+09 | 0.182071E+09 | 0.463596E+09 | 0.693178E+09 |
February | 0.563149E+09 | 0.382101E+09 | 0.181048E+09 | 0.461217E+09 | 0.496090E+09 |
March | 0.534189E+09 | 0.279733E+09 | 0.254456E+09 | 0.419714E+09 | 0.402559E+09 |
April | 0.460670E+09 | 0.211108E+09 | 0.249562E+09 | 0.364118E+09 | 0.272096E+09 |
May | 0.405943E+09 | 0.113512E+09 | 0.292432E+09 | 0.341853E+09 | 0.141705E+09 |
June | 0.375014E+09 | 74840121.99 | 0.300174E+09 | 0.371378E+09 | 76886619.66 |
July | 0.411230E+09 | 0.102789E+09 | 0.308441E+09 | 0.423606E+09 | 58362218.06 |
August | 0.455718E+09 | 0.157772E+09 | 0.297946E+09 | 0.490523E+09 | 75902918.10 |
September | 0.532641E+09 | 0.274893E+09 | 0.257748E+09 | 0.558019E+09 | 0.154391E+09 |
October | 0.593250E+09 | 0.374098E+09 | 0.219152E+09 | 0.585988E+09 | 0.281322E+09 |
November | 0.429510E+09 | 0.268900E+09 | 0.160611E+09 | 0.364678E+09 | 0.429540E+09 |
December | 0.472435E+09 | 0.357743E+09 | 0.114691E+09 | 0.420380E+09 | 0.645738E+09 |
Annual Sum or Average | 0.581189E+10 | 0.299356E+10 | 0.281833E+10 | 0.526507E+10 | 0.372777E+10 |
Minimum of Months | 0.375014E+09 | 74840121.99 | 0.114691E+09 | 0.341853E+09 | 58362218.06 |
Maximum of Months | 0.593250E+09 | 0.396068E+09 | 0.308441E+09 | 0.585988E+09 | 0.693178E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.364050E+09 | 0.545395E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.356534E+09 | 0.399337E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.326729E+09 | 0.317506E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.277302E+09 | 0.218485E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.251182E+09 | 0.118336E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.272356E+09 | 65442058.13 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.310820E+09 | 51110135.42 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.365130E+09 | 65377101.27 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.425304E+09 | 0.126402E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.452530E+09 | 0.224892E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.285323E+09 | 0.335551E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.330697E+09 | 0.501250E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.401796E+10 | 0.296908E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.251182E+09 | 51110135.42 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.452530E+09 | 0.545395E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 83782574.45 | 0.117724E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.183511E+09 | 0.849525E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.291190E+09 | 0.608970E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.623622E+09 | 0.397287E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.725062E+09 | 0.212964E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.946590E+09 | 0.119626E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108978E+10 | 94266273.16 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.950249E+09 | 0.120655E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.667801E+09 | 0.234033E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.343466E+09 | 0.435602E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.116236E+09 | 0.692351E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 73382976.58 | 0.105057E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.609468E+10 | 0.599309E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 73382976.58 | 94266273.16 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108978E+10 | 0.117724E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 14029.57 | 0.668845E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1162934.23 | 0.488446E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 26944480.56 | 0.344825E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 65592956.98 | 0.219315E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.148873E+09 | 0.109877E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.225081E+09 | 60161107.07 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.232422E+09 | 47635002.70 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.202044E+09 | 61793689.40 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.117126E+09 | 0.126650E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 36629158.55 | 0.238711E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 7721369.93 | 0.385073E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.583377E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.106361E+10 | 0.333471E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 47635002.70 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.232422E+09 | 0.668845E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 87474675.54 | 0.116606E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.190511E+09 | 0.837344E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.301703E+09 | 0.601651E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.631391E+09 | 0.393700E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.728748E+09 | 0.211612E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.948176E+09 | 0.118926E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109184E+10 | 93592923.42 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.954077E+09 | 0.119484E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.676175E+09 | 0.230982E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.358648E+09 | 0.427675E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.123209E+09 | 0.684034E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 78086884.37 | 0.103947E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.617004E+10 | 0.592453E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 78086884.37 | 93592923.42 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.109184E+10 | 0.116606E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.513689E+09 | 0.819901E+09 |
February | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.505760E+09 | 0.603086E+09 |
March | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.464951E+09 | 0.477279E+09 |
April | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.403730E+09 | 0.323059E+09 |
May | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.370791E+09 | 0.172158E+09 |
June | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.407528E+09 | 93568881.13 |
July | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.465929E+09 | 71115285.57 |
August | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.541621E+09 | 93175571.76 |
September | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.621564E+09 | 0.186735E+09 |
October | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.651211E+09 | 0.339363E+09 |
November | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.405083E+09 | 0.508617E+09 |
December | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.468536E+09 | 0.755322E+09 |
Annual Sum or Average | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.582039E+10 | 0.444338E+10 |
Minimum of Months | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.370791E+09 | 71115285.57 |
Maximum of Months | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.651211E+09 | 0.819901E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.493701E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 1742890.49 | 0.357978E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.135001E+09 | 0.274532E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.416347E+09 | 0.178519E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.992051E+09 | 0.928792E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.152897E+10 | 0.544921E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.159562E+10 | 0.443575E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.139360E+10 | 0.564821E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.787616E+09 | 0.107114E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.190707E+09 | 0.195802E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 31498309.77 | 0.304833E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.448196E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.707315E+10 | 0.260889E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.443575E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.159562E+10 | 0.493701E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.503064E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 958332.19 | 0.365849E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.120710E+09 | 0.282430E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.393361E+09 | 0.184149E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.950686E+09 | 0.961005E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.149050E+10 | 0.567788E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.155684E+10 | 0.463933E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.135636E+10 | 0.589907E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.758752E+09 | 0.110957E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.170797E+09 | 0.202044E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 26072325.82 | 0.313166E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.458485E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.682503E+10 | 0.267841E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.463933E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.155684E+10 | 0.503064E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 24414.93 | 0.637670E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1584243.76 | 0.452508E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 33394977.18 | 0.347157E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 87069153.10 | 0.221216E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.196211E+09 | 0.118135E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.282138E+09 | 68766506.49 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.296899E+09 | 53663757.59 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.261643E+09 | 68032909.14 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.156390E+09 | 0.129465E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 49967820.81 | 0.238818E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 11959848.14 | 0.380891E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.579088E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.137728E+10 | 0.329541E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 53663757.59 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.296899E+09 | 0.637670E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.584511E+09 | 0.239563E+09 | 0.344948E+09 | 0.164217E+09 | 0.220215E+10 |
February | 0.702953E+09 | 0.309404E+09 | 0.393549E+09 | 0.310482E+09 | 0.153011E+10 |
March | 0.105704E+10 | 0.419414E+09 | 0.637627E+09 | 0.668669E+09 | 0.119223E+10 |
April | 0.124848E+10 | 0.544148E+09 | 0.704333E+09 | 0.111122E+10 | 0.794826E+09 |
May | 0.162988E+10 | 0.712773E+09 | 0.917103E+09 | 0.179104E+10 | 0.434857E+09 |
June | 0.173334E+10 | 0.754970E+09 | 0.978368E+09 | 0.214928E+10 | 0.259917E+09 |
July | 0.181076E+10 | 0.835731E+09 | 0.975034E+09 | 0.233778E+10 | 0.203508E+09 |
August | 0.152676E+10 | 0.657939E+09 | 0.868824E+09 | 0.198660E+10 | 0.254728E+09 |
September | 0.132385E+10 | 0.627922E+09 | 0.695933E+09 | 0.154874E+10 | 0.469954E+09 |
October | 0.866230E+09 | 0.360550E+09 | 0.505680E+09 | 0.680374E+09 | 0.841093E+09 |
November | 0.495872E+09 | 0.160945E+09 | 0.334927E+09 | 0.199071E+09 | 0.133835E+10 |
December | 0.395447E+09 | 0.169327E+09 | 0.226119E+09 | 0.102776E+09 | 0.203747E+10 |
Annual Sum or Average | 0.133751E+11 | 0.579269E+10 | 0.758245E+10 | 0.130503E+11 | 0.115592E+11 |
Minimum of Months | 0.395447E+09 | 0.160945E+09 | 0.226119E+09 | 0.102776E+09 | 0.203508E+09 |
Maximum of Months | 0.181076E+10 | 0.835731E+09 | 0.978368E+09 | 0.233778E+10 | 0.220215E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.380249E+09 | 0.522274E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.378951E+09 | 0.374295E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.343530E+09 | 0.319534E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.303339E+09 | 0.219886E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.297489E+09 | 0.124660E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.327185E+09 | 73378180.06 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.373763E+09 | 56491796.62 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.423744E+09 | 70840045.79 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.469896E+09 | 0.128873E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.482825E+09 | 0.227032E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.300463E+09 | 0.333733E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.341321E+09 | 0.496372E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.442276E+10 | 0.294737E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.297489E+09 | 56491796.62 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.482825E+09 | 0.522274E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92765322.83 | 0.00 | 92765322.83 | 0.00 | 0.868226E+09 |
February | 0.106227E+09 | 0.00 | 0.106227E+09 | 613778.34 | 0.614540E+09 |
March | 0.176283E+09 | 1490.90 | 0.176281E+09 | 29818499.84 | 0.454113E+09 |
April | 0.197706E+09 | 1585439.33 | 0.196121E+09 | 83356360.20 | 0.286288E+09 |
May | 0.265617E+09 | 10036207.97 | 0.255581E+09 | 0.195795E+09 | 0.144257E+09 |
June | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.288362E+09 | 84013488.22 |
July | 0.291532E+09 | 20068050.55 | 0.271464E+09 | 0.297994E+09 | 68963073.38 |
August | 0.244283E+09 | 4923120.89 | 0.239360E+09 | 0.259855E+09 | 87432008.65 |
September | 0.180921E+09 | 162355.54 | 0.180758E+09 | 0.148918E+09 | 0.169397E+09 |
October | 0.138824E+09 | 0.00 | 0.138824E+09 | 41115799.63 | 0.314305E+09 |
November | 93976305.19 | 0.00 | 93976305.19 | 7624453.14 | 0.512385E+09 |
December | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 0.774541E+09 |
Annual Sum or Average | 0.215192E+10 | 64619455.98 | 0.208730E+10 | 0.135345E+10 | 0.437846E+10 |
Minimum of Months | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 68963073.38 |
Maximum of Months | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.297994E+09 | 0.868226E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82997485.82 | 0.00 | 82997485.82 | 0.00 | 0.776792E+09 |
February | 95041552.99 | 0.00 | 95041552.99 | 549149.81 | 0.549831E+09 |
March | 0.157721E+09 | 1333.91 | 0.157719E+09 | 26678724.79 | 0.406297E+09 |
April | 0.176888E+09 | 1418498.57 | 0.175470E+09 | 74579251.31 | 0.256143E+09 |
May | 0.237649E+09 | 8979433.30 | 0.228670E+09 | 0.175178E+09 | 0.129067E+09 |
June | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.257999E+09 | 75167186.24 |
July | 0.260835E+09 | 17954960.87 | 0.242880E+09 | 0.266616E+09 | 61701523.05 |
August | 0.218561E+09 | 4404734.91 | 0.214156E+09 | 0.232493E+09 | 78225749.42 |
September | 0.161871E+09 | 145260.12 | 0.161725E+09 | 0.133238E+09 | 0.151560E+09 |
October | 0.124206E+09 | 0.00 | 0.124206E+09 | 36786461.71 | 0.281210E+09 |
November | 84080956.33 | 0.00 | 84080956.33 | 6821627.11 | 0.458433E+09 |
December | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 0.692968E+09 |
Annual Sum or Average | 0.192533E+10 | 57815272.11 | 0.186752E+10 | 0.121094E+10 | 0.391740E+10 |
Minimum of Months | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 61701523.05 |
Maximum of Months | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.266616E+09 | 0.776792E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170568E+10 | 0.116852E+10 | 0.537162E+09 | 0.135383E+10 | 0.205798E+10 |
February | 0.166146E+10 | 0.112731E+10 | 0.534145E+09 | 0.135174E+10 | 0.146284E+10 |
March | 0.157601E+10 | 0.825294E+09 | 0.750720E+09 | 0.121675E+10 | 0.121237E+10 |
April | 0.135911E+10 | 0.622831E+09 | 0.736281E+09 | 0.104876E+10 | 0.832980E+09 |
May | 0.119765E+10 | 0.334893E+09 | 0.862759E+09 | 0.964212E+09 | 0.452762E+09 |
June | 0.110640E+10 | 0.220800E+09 | 0.885601E+09 | 0.102981E+10 | 0.267205E+09 |
July | 0.121325E+10 | 0.303259E+09 | 0.909991E+09 | 0.117553E+10 | 0.216243E+09 |
August | 0.134450E+10 | 0.465474E+09 | 0.879028E+09 | 0.138116E+10 | 0.268770E+09 |
September | 0.157145E+10 | 0.811014E+09 | 0.760433E+09 | 0.160366E+10 | 0.491902E+09 |
October | 0.175026E+10 | 0.110370E+10 | 0.646561E+09 | 0.170026E+10 | 0.855094E+09 |
November | 0.126718E+10 | 0.793333E+09 | 0.473848E+09 | 0.105853E+10 | 0.129185E+10 |
December | 0.139382E+10 | 0.105545E+10 | 0.338373E+09 | 0.122540E+10 | 0.192956E+10 |
Annual Sum or Average | 0.171468E+11 | 0.883188E+10 | 0.831490E+10 | 0.151096E+11 | 0.113396E+11 |
Minimum of Months | 0.110640E+10 | 0.220800E+09 | 0.338373E+09 | 0.964212E+09 | 0.216243E+09 |
Maximum of Months | 0.175026E+10 | 0.116852E+10 | 0.909991E+09 | 0.170026E+10 | 0.205798E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 701.39 | 953.74 | 863.80 | 591.77 | 272.03 | 0.00 | 0.00 |
February | 765.99 | 759.73 | 931.56 | 632.07 | 299.49 | 0.00 | 0.00 |
March | 622.86 | 563.75 | 798.14 | 417.95 | 380.19 | 0.00 | 0.00 |
April | 544.75 | 401.37 | 711.24 | 325.93 | 385.30 | 0.00 | 0.00 |
May | 489.70 | 210.23 | 606.52 | 169.60 | 436.93 | 0.00 | 0.00 |
June | 538.56 | 125.73 | 578.99 | 115.55 | 463.44 | 0.00 | 0.00 |
July | 594.69 | 98.56 | 614.42 | 153.58 | 460.84 | 0.00 | 0.00 |
August | 692.21 | 125.90 | 680.89 | 235.73 | 445.16 | 0.00 | 0.00 |
September | 824.84 | 246.87 | 822.35 | 424.41 | 397.94 | 0.00 | 0.00 |
October | 855.30 | 411.77 | 886.38 | 558.94 | 327.44 | 0.00 | 0.00 |
November | 560.51 | 619.62 | 663.13 | 415.16 | 247.97 | 0.00 | 0.00 |
December | 626.82 | 896.72 | 705.87 | 534.51 | 171.36 | 0.00 | 0.00 |
Annual Sum or Average | 650.90 | 449.76 | 737.51 | 379.87 | 357.64 | 0.00 | 0.00 |
Minimum of Months | 489.70 | 98.56 | 578.99 | 115.55 | 171.36 | 0.00 | 0.00 |
Maximum of Months | 855.30 | 953.74 | 931.56 | 632.07 | 463.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1961.83 | 2705.73 | 2432.41 | 1666.38 | 766.03 | 0.00 | 0.00 |
February | 2140.02 | 2181.07 | 2623.21 | 1779.87 | 843.34 | 0.00 | 0.00 |
March | 1731.51 | 1635.67 | 2247.50 | 1176.92 | 1070.58 | 0.00 | 0.00 |
April | 1512.10 | 1192.81 | 2002.79 | 917.81 | 1084.99 | 0.00 | 0.00 |
May | 1343.64 | 657.33 | 1707.93 | 477.58 | 1230.35 | 0.00 | 0.00 |
June | 1482.82 | 406.03 | 1630.40 | 325.37 | 1305.02 | 0.00 | 0.00 |
July | 1642.66 | 320.74 | 1730.18 | 432.47 | 1297.71 | 0.00 | 0.00 |
August | 1920.96 | 407.10 | 1917.35 | 663.80 | 1253.55 | 0.00 | 0.00 |
September | 2296.18 | 759.97 | 2315.69 | 1195.11 | 1120.58 | 0.00 | 0.00 |
October | 2381.54 | 1235.70 | 2495.99 | 1573.95 | 922.04 | 0.00 | 0.00 |
November | 1559.80 | 1792.44 | 1867.32 | 1169.06 | 698.26 | 0.00 | 0.00 |
December | 1751.02 | 2549.35 | 1987.68 | 1505.14 | 482.54 | 0.00 | 0.00 |
Annual Sum or Average | 1808.70 | 1316.35 | 2076.78 | 1069.70 | 1007.08 | 0.00 | 0.00 |
Minimum of Months | 1343.64 | 320.74 | 1630.40 | 325.37 | 482.54 | 0.00 | 0.00 |
Maximum of Months | 2381.54 | 2705.73 | 2623.21 | 1779.87 | 1305.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2583.39 | 3650.50 | 3159.84 | 2164.73 | 995.12 | 0.00 | 0.00 |
February | 2831.94 | 2931.26 | 3407.69 | 2312.15 | 1095.55 | 0.00 | 0.00 |
March | 2288.14 | 2228.02 | 2919.63 | 1528.89 | 1390.74 | 0.00 | 0.00 |
April | 2005.77 | 1628.54 | 2601.74 | 1192.28 | 1409.46 | 0.00 | 0.00 |
May | 1776.11 | 894.37 | 2218.70 | 620.40 | 1598.30 | 0.00 | 0.00 |
June | 1975.91 | 548.03 | 2117.98 | 422.68 | 1695.30 | 0.00 | 0.00 |
July | 2192.85 | 426.48 | 2247.60 | 561.80 | 1685.80 | 0.00 | 0.00 |
August | 2559.90 | 539.33 | 2490.75 | 862.31 | 1628.44 | 0.00 | 0.00 |
September | 3051.53 | 1020.71 | 3008.21 | 1552.52 | 1455.69 | 0.00 | 0.00 |
October | 3143.17 | 1676.27 | 3242.43 | 2044.65 | 1197.78 | 0.00 | 0.00 |
November | 2049.61 | 2447.51 | 2425.76 | 1518.67 | 907.08 | 0.00 | 0.00 |
December | 2307.24 | 3459.70 | 2582.11 | 1955.26 | 626.85 | 0.00 | 0.00 |
Annual Sum or Average | 2394.94 | 1782.28 | 2697.86 | 1389.60 | 1308.26 | 0.00 | 0.00 |
Minimum of Months | 1776.11 | 426.48 | 2117.98 | 422.68 | 626.85 | 0.00 | 0.00 |
Maximum of Months | 3143.17 | 3650.50 | 3407.69 | 2312.15 | 1695.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.19 | 598.65 | 279.39 | 161.07 | 118.31 | 0.00 | 0.00 |
February | 192.15 | 481.05 | 342.80 | 202.99 | 139.81 | 0.00 | 0.00 |
March | 220.86 | 335.36 | 347.24 | 153.05 | 194.19 | 0.00 | 0.00 |
April | 345.64 | 233.60 | 417.83 | 201.64 | 216.19 | 0.00 | 0.00 |
May | 366.88 | 121.64 | 397.69 | 144.76 | 252.93 | 0.00 | 0.00 |
June | 473.54 | 70.51 | 439.45 | 163.38 | 276.06 | 0.00 | 0.00 |
July | 526.69 | 53.66 | 470.54 | 195.99 | 274.54 | 0.00 | 0.00 |
August | 494.46 | 68.49 | 439.37 | 186.08 | 253.29 | 0.00 | 0.00 |
September | 422.53 | 137.74 | 409.80 | 201.05 | 208.75 | 0.00 | 0.00 |
October | 292.93 | 241.74 | 348.40 | 187.80 | 160.60 | 0.00 | 0.00 |
November | 139.93 | 381.61 | 234.37 | 120.36 | 114.01 | 0.00 | 0.00 |
December | 123.41 | 550.83 | 218.97 | 143.18 | 75.79 | 0.00 | 0.00 |
Annual Sum or Average | 311.02 | 271.93 | 362.17 | 171.53 | 190.64 | 0.00 | 0.00 |
Minimum of Months | 123.41 | 53.66 | 218.97 | 120.36 | 75.79 | 0.00 | 0.00 |
Maximum of Months | 526.69 | 598.65 | 470.54 | 202.99 | 276.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.42 | 671.57 | 136.27 | 44.31 | 91.96 | 0.00 | 0.00 |
February | 65.73 | 531.08 | 193.64 | 78.28 | 115.36 | 0.00 | 0.00 |
March | 115.49 | 345.98 | 241.68 | 70.58 | 171.10 | 0.00 | 0.00 |
April | 267.10 | 233.00 | 337.68 | 137.81 | 199.86 | 0.00 | 0.00 |
May | 330.99 | 118.72 | 356.26 | 114.25 | 242.00 | 0.00 | 0.00 |
June | 455.64 | 67.57 | 416.76 | 149.06 | 267.70 | 0.00 | 0.00 |
July | 498.14 | 51.74 | 435.18 | 171.60 | 263.58 | 0.00 | 0.00 |
August | 435.43 | 66.89 | 376.98 | 141.02 | 235.96 | 0.00 | 0.00 |
September | 306.87 | 136.95 | 302.60 | 117.36 | 185.25 | 0.00 | 0.00 |
October | 143.81 | 246.30 | 214.39 | 77.51 | 136.88 | 0.00 | 0.00 |
November | 44.85 | 407.75 | 132.13 | 38.44 | 93.69 | 0.00 | 0.00 |
December | 21.66 | 597.22 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Annual Sum or Average | 226.52 | 288.44 | 270.48 | 98.19 | 172.30 | 0.00 | 0.00 |
Minimum of Months | 21.66 | 51.74 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Maximum of Months | 498.14 | 671.57 | 435.18 | 171.60 | 267.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.48 | 147.22 | 136.33 | 93.39 | 42.93 | 0.00 | 0.00 |
February | 117.29 | 134.43 | 147.02 | 99.75 | 47.27 | 0.00 | 0.00 |
March | 92.59 | 104.82 | 125.96 | 65.96 | 60.00 | 0.00 | 0.00 |
April | 78.10 | 89.67 | 112.25 | 51.44 | 60.81 | 0.00 | 0.00 |
May | 62.88 | 54.88 | 95.72 | 26.77 | 68.96 | 0.00 | 0.00 |
June | 71.18 | 37.28 | 91.38 | 18.24 | 73.14 | 0.00 | 0.00 |
July | 79.90 | 30.75 | 96.97 | 24.24 | 72.73 | 0.00 | 0.00 |
August | 96.71 | 36.87 | 107.46 | 37.20 | 70.26 | 0.00 | 0.00 |
September | 120.46 | 61.10 | 129.78 | 66.98 | 62.80 | 0.00 | 0.00 |
October | 123.97 | 92.90 | 139.89 | 88.21 | 51.68 | 0.00 | 0.00 |
November | 82.02 | 121.18 | 104.65 | 65.52 | 39.13 | 0.00 | 0.00 |
December | 98.86 | 140.76 | 111.40 | 84.36 | 27.04 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 87.38 | 116.39 | 59.95 | 56.44 | 0.00 | 0.00 |
Minimum of Months | 62.88 | 30.75 | 91.38 | 18.24 | 27.04 | 0.00 | 0.00 |
Maximum of Months | 123.97 | 147.22 | 147.02 | 99.75 | 73.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 205.28 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
February | 0.25 | 165.71 | 27.72 | 0.00 | 27.72 | 0.00 | 0.00 |
March | 7.39 | 106.37 | 41.55 | 0.00 | 41.55 | 0.00 | 0.00 |
April | 21.17 | 69.01 | 48.15 | 0.39 | 47.76 | 0.00 | 0.00 |
May | 47.09 | 32.71 | 62.60 | 2.37 | 60.24 | 0.00 | 0.00 |
June | 73.34 | 18.15 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
July | 73.95 | 13.36 | 68.71 | 4.73 | 63.98 | 0.00 | 0.00 |
August | 64.35 | 17.70 | 57.57 | 1.16 | 56.41 | 0.00 | 0.00 |
September | 38.10 | 39.28 | 44.06 | 0.04 | 44.02 | 0.00 | 0.00 |
October | 10.29 | 73.57 | 32.72 | 0.00 | 32.72 | 0.00 | 0.00 |
November | 2.01 | 124.15 | 22.89 | 0.00 | 22.89 | 0.00 | 0.00 |
December | 0.00 | 180.42 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Annual Sum or Average | 28.33 | 86.76 | 43.08 | 1.29 | 41.78 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 13.36 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Maximum of Months | 73.95 | 205.28 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.64 | 596.10 | 279.47 | 161.45 | 118.02 | 0.00 | 0.00 |
February | 172.71 | 473.98 | 328.99 | 188.62 | 140.37 | 0.00 | 0.00 |
March | 225.27 | 330.58 | 354.66 | 160.70 | 193.96 | 0.00 | 0.00 |
April | 296.58 | 228.22 | 380.99 | 169.20 | 211.79 | 0.00 | 0.00 |
May | 389.52 | 114.58 | 423.71 | 166.42 | 257.29 | 0.00 | 0.00 |
June | 477.63 | 66.39 | 448.36 | 168.32 | 280.03 | 0.00 | 0.00 |
July | 507.57 | 49.94 | 459.01 | 186.20 | 272.81 | 0.00 | 0.00 |
August | 464.71 | 63.87 | 419.15 | 169.24 | 249.91 | 0.00 | 0.00 |
September | 426.56 | 133.88 | 417.44 | 204.78 | 212.67 | 0.00 | 0.00 |
October | 273.27 | 236.78 | 336.48 | 177.54 | 158.94 | 0.00 | 0.00 |
November | 127.13 | 376.98 | 226.43 | 112.94 | 113.49 | 0.00 | 0.00 |
December | 113.01 | 545.58 | 213.04 | 137.05 | 75.99 | 0.00 | 0.00 |
Annual Sum or Average | 300.58 | 267.11 | 357.42 | 166.73 | 190.70 | 0.00 | 0.00 |
Minimum of Months | 113.01 | 49.94 | 213.04 | 112.94 | 75.99 | 0.00 | 0.00 |
Maximum of Months | 507.57 | 596.10 | 459.01 | 204.78 | 280.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.59 | 662.62 | 136.36 | 44.69 | 91.67 | 0.00 | 0.00 |
February | 43.92 | 521.35 | 179.82 | 63.90 | 115.92 | 0.00 | 0.00 |
March | 116.33 | 337.67 | 249.11 | 78.24 | 170.87 | 0.00 | 0.00 |
April | 217.42 | 226.91 | 300.83 | 105.37 | 195.46 | 0.00 | 0.00 |
May | 354.21 | 112.54 | 382.28 | 135.92 | 246.36 | 0.00 | 0.00 |
June | 461.62 | 65.37 | 425.67 | 154.00 | 271.67 | 0.00 | 0.00 |
July | 480.22 | 49.25 | 423.65 | 161.81 | 261.85 | 0.00 | 0.00 |
August | 406.19 | 62.90 | 356.76 | 124.18 | 232.58 | 0.00 | 0.00 |
September | 309.77 | 132.50 | 310.25 | 121.09 | 189.17 | 0.00 | 0.00 |
October | 120.14 | 237.28 | 202.48 | 67.26 | 135.22 | 0.00 | 0.00 |
November | 29.76 | 400.79 | 124.19 | 31.02 | 93.16 | 0.00 | 0.00 |
December | 11.30 | 592.31 | 92.32 | 31.59 | 60.74 | 0.00 | 0.00 |
Annual Sum or Average | 214.74 | 282.35 | 265.74 | 93.39 | 172.35 | 0.00 | 0.00 |
Minimum of Months | 11.30 | 49.25 | 92.32 | 31.02 | 60.74 | 0.00 | 0.00 |
Maximum of Months | 480.22 | 662.62 | 425.67 | 161.81 | 271.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.55 | 732.81 | 342.74 | 202.36 | 140.39 | 0.00 | 0.00 |
February | 214.29 | 580.91 | 378.60 | 216.14 | 162.46 | 0.00 | 0.00 |
March | 220.42 | 421.49 | 362.93 | 142.92 | 220.01 | 0.00 | 0.00 |
April | 239.28 | 288.21 | 347.52 | 112.29 | 235.23 | 0.00 | 0.00 |
May | 282.21 | 140.12 | 343.02 | 63.12 | 279.90 | 0.00 | 0.00 |
June | 359.30 | 76.97 | 356.68 | 54.20 | 302.48 | 0.00 | 0.00 |
July | 381.34 | 57.32 | 358.95 | 62.76 | 296.19 | 0.00 | 0.00 |
August | 394.82 | 75.96 | 357.56 | 83.12 | 274.44 | 0.00 | 0.00 |
September | 379.82 | 164.03 | 376.66 | 145.21 | 231.44 | 0.00 | 0.00 |
October | 317.16 | 293.21 | 373.98 | 191.13 | 182.85 | 0.00 | 0.00 |
November | 173.25 | 468.07 | 276.34 | 141.96 | 134.37 | 0.00 | 0.00 |
December | 171.84 | 676.76 | 273.53 | 182.78 | 90.76 | 0.00 | 0.00 |
Annual Sum or Average | 276.14 | 330.17 | 345.51 | 132.70 | 212.81 | 0.00 | 0.00 |
Minimum of Months | 171.84 | 57.32 | 273.53 | 54.20 | 90.76 | 0.00 | 0.00 |
Maximum of Months | 394.82 | 732.81 | 378.60 | 216.14 | 302.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.39 | 601.35 | 279.62 | 161.20 | 118.41 | 0.00 | 0.00 |
February | 190.75 | 483.74 | 343.09 | 203.16 | 139.93 | 0.00 | 0.00 |
March | 220.52 | 335.72 | 347.52 | 153.17 | 194.35 | 0.00 | 0.00 |
April | 343.73 | 233.72 | 418.18 | 201.81 | 216.37 | 0.00 | 0.00 |
May | 363.21 | 122.41 | 398.02 | 144.88 | 253.14 | 0.00 | 0.00 |
June | 469.84 | 70.96 | 439.81 | 163.52 | 276.29 | 0.00 | 0.00 |
July | 522.72 | 54.07 | 470.92 | 196.15 | 274.77 | 0.00 | 0.00 |
August | 490.78 | 69.13 | 439.73 | 186.24 | 253.50 | 0.00 | 0.00 |
September | 420.46 | 137.79 | 410.13 | 201.21 | 208.92 | 0.00 | 0.00 |
October | 292.13 | 241.54 | 348.68 | 187.95 | 160.73 | 0.00 | 0.00 |
November | 140.04 | 381.69 | 234.56 | 120.46 | 114.10 | 0.00 | 0.00 |
December | 123.66 | 552.17 | 219.15 | 143.30 | 75.85 | 0.00 | 0.00 |
Annual Sum or Average | 309.19 | 272.71 | 362.46 | 171.67 | 190.80 | 0.00 | 0.00 |
Minimum of Months | 123.66 | 54.07 | 219.15 | 120.46 | 75.85 | 0.00 | 0.00 |
Maximum of Months | 522.72 | 601.35 | 470.92 | 203.16 | 276.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.32 | 674.73 | 136.38 | 44.34 | 92.04 | 0.00 | 0.00 |
February | 65.43 | 534.22 | 193.80 | 78.34 | 115.46 | 0.00 | 0.00 |
March | 115.57 | 346.24 | 241.88 | 70.64 | 171.24 | 0.00 | 0.00 |
April | 265.39 | 232.99 | 337.95 | 137.92 | 200.03 | 0.00 | 0.00 |
May | 327.06 | 119.42 | 356.55 | 114.35 | 242.20 | 0.00 | 0.00 |
June | 451.58 | 68.03 | 417.11 | 149.18 | 267.92 | 0.00 | 0.00 |
July | 493.85 | 52.15 | 435.53 | 171.74 | 263.79 | 0.00 | 0.00 |
August | 431.46 | 67.50 | 377.29 | 141.14 | 236.15 | 0.00 | 0.00 |
September | 304.92 | 136.83 | 302.85 | 117.45 | 185.40 | 0.00 | 0.00 |
October | 144.15 | 245.37 | 214.57 | 77.57 | 137.00 | 0.00 | 0.00 |
November | 45.38 | 407.33 | 132.24 | 38.47 | 93.76 | 0.00 | 0.00 |
December | 21.86 | 598.61 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Annual Sum or Average | 224.92 | 289.15 | 270.70 | 98.27 | 172.44 | 0.00 | 0.00 |
Minimum of Months | 21.86 | 52.15 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Maximum of Months | 493.85 | 674.73 | 435.53 | 171.74 | 267.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 191.79 | 306.12 | 250.17 | 171.39 | 78.79 | 0.00 | 0.00 |
February | 209.06 | 249.29 | 269.80 | 183.06 | 86.74 | 0.00 | 0.00 |
March | 173.59 | 178.20 | 231.15 | 121.05 | 110.11 | 0.00 | 0.00 |
April | 155.76 | 124.64 | 205.99 | 94.40 | 111.59 | 0.00 | 0.00 |
May | 138.44 | 64.28 | 175.66 | 49.12 | 126.54 | 0.00 | 0.00 |
June | 157.23 | 36.10 | 167.69 | 33.46 | 134.22 | 0.00 | 0.00 |
July | 173.96 | 26.55 | 177.95 | 44.48 | 133.47 | 0.00 | 0.00 |
August | 202.22 | 34.79 | 197.20 | 68.27 | 128.93 | 0.00 | 0.00 |
September | 239.80 | 72.04 | 238.17 | 122.92 | 115.25 | 0.00 | 0.00 |
October | 243.13 | 126.70 | 256.71 | 161.88 | 94.83 | 0.00 | 0.00 |
November | 156.28 | 196.23 | 192.05 | 120.24 | 71.82 | 0.00 | 0.00 |
December | 174.93 | 282.00 | 204.43 | 154.80 | 49.63 | 0.00 | 0.00 |
Annual Sum or Average | 184.56 | 140.90 | 213.60 | 110.02 | 103.58 | 0.00 | 0.00 |
Minimum of Months | 138.44 | 26.55 | 167.69 | 33.46 | 49.63 | 0.00 | 0.00 |
Maximum of Months | 243.13 | 306.12 | 269.80 | 183.06 | 134.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1843.27 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.72 | 1479.74 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 50.40 | 1024.99 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 160.63 | 688.73 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 370.39 | 346.77 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 589.88 | 210.23 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 595.74 | 165.61 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 520.31 | 210.88 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 303.86 | 413.25 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 71.20 | 731.04 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 12.15 | 1176.05 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1673.37 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 224.29 | 827.27 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 165.61 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 595.74 | 1843.27 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1878.23 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.40 | 1512.27 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 45.07 | 1054.47 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 151.76 | 710.45 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 354.95 | 358.80 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 575.04 | 219.05 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 581.26 | 173.21 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 506.41 | 220.25 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 292.73 | 428.07 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 63.77 | 754.35 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 10.06 | 1208.20 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1711.79 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 216.42 | 849.32 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 173.21 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 581.26 | 1878.23 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.49 | 1176.46 | 416.16 | 206.30 | 209.86 | 0.00 | 0.00 |
February | 222.18 | 910.80 | 509.21 | 252.71 | 256.49 | 0.00 | 0.00 |
March | 370.97 | 674.63 | 604.24 | 239.13 | 365.11 | 0.00 | 0.00 |
April | 572.68 | 470.17 | 682.35 | 274.78 | 407.57 | 0.00 | 0.00 |
May | 848.91 | 248.90 | 806.61 | 302.57 | 504.04 | 0.00 | 0.00 |
June | 1062.53 | 153.37 | 874.70 | 322.57 | 552.13 | 0.00 | 0.00 |
July | 1122.35 | 116.24 | 883.34 | 348.27 | 535.07 | 0.00 | 0.00 |
August | 996.21 | 145.56 | 776.51 | 293.65 | 482.86 | 0.00 | 0.00 |
September | 836.16 | 278.01 | 728.26 | 326.11 | 402.14 | 0.00 | 0.00 |
October | 445.72 | 480.73 | 539.38 | 244.99 | 294.39 | 0.00 | 0.00 |
November | 165.91 | 760.62 | 350.89 | 144.08 | 206.81 | 0.00 | 0.00 |
December | 105.87 | 1102.30 | 305.61 | 168.77 | 136.83 | 0.00 | 0.00 |
Annual Sum or Average | 574.77 | 541.53 | 623.64 | 260.32 | 363.33 | 0.00 | 0.00 |
Minimum of Months | 105.87 | 116.24 | 305.61 | 144.08 | 136.83 | 0.00 | 0.00 |
Maximum of Months | 1122.35 | 1176.46 | 883.34 | 348.27 | 552.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.28 | 1292.36 | 702.45 | 436.27 | 266.18 | 0.00 | 0.00 |
February | 490.81 | 1017.55 | 769.98 | 465.98 | 303.99 | 0.00 | 0.00 |
March | 458.23 | 756.75 | 713.12 | 308.13 | 404.99 | 0.00 | 0.00 |
April | 463.67 | 528.77 | 668.87 | 241.45 | 427.42 | 0.00 | 0.00 |
May | 497.48 | 270.07 | 635.05 | 132.13 | 502.92 | 0.00 | 0.00 |
June | 604.67 | 161.08 | 646.73 | 105.54 | 541.19 | 0.00 | 0.00 |
July | 647.81 | 127.63 | 659.21 | 127.42 | 531.79 | 0.00 | 0.00 |
August | 699.01 | 161.72 | 674.79 | 177.27 | 497.51 | 0.00 | 0.00 |
September | 726.72 | 312.77 | 738.52 | 313.01 | 425.51 | 0.00 | 0.00 |
October | 653.96 | 531.66 | 751.68 | 412.07 | 339.60 | 0.00 | 0.00 |
November | 377.81 | 836.80 | 557.58 | 306.07 | 251.51 | 0.00 | 0.00 |
December | 394.15 | 1204.96 | 564.95 | 394.06 | 170.89 | 0.00 | 0.00 |
Annual Sum or Average | 536.09 | 598.28 | 673.01 | 283.94 | 389.07 | 0.00 | 0.00 |
Minimum of Months | 377.81 | 127.63 | 557.58 | 105.54 | 170.89 | 0.00 | 0.00 |
Maximum of Months | 726.72 | 1292.36 | 769.98 | 465.98 | 541.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187860E+10 | 0.255451E+10 | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.00 | 0.00 |
February | 0.185308E+10 | 0.183793E+10 | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.00 | 0.00 |
March | 0.166828E+10 | 0.150995E+10 | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.00 | 0.00 |
April | 0.141200E+10 | 0.104036E+10 | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.00 | 0.00 |
May | 0.131161E+10 | 0.563071E+09 | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.00 | 0.00 |
June | 0.139595E+10 | 0.325895E+09 | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.00 | 0.00 |
July | 0.159281E+10 | 0.263984E+09 | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.00 | 0.00 |
August | 0.185402E+10 | 0.337223E+09 | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.00 | 0.00 |
September | 0.213799E+10 | 0.639897E+09 | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.00 | 0.00 |
October | 0.229084E+10 | 0.110289E+10 | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.00 | 0.00 |
November | 0.145285E+10 | 0.160606E+10 | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.00 | 0.00 |
December | 0.167887E+10 | 0.240176E+10 | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205269E+11 | 0.141835E+11 | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131161E+10 | 0.263984E+09 | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.00 | 0.00 |
Maximum of Months | 0.229084E+10 | 0.255451E+10 | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525455E+10 | 0.724703E+10 | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.00 | 0.00 |
February | 0.517714E+10 | 0.527644E+10 | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.00 | 0.00 |
March | 0.463768E+10 | 0.438099E+10 | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.00 | 0.00 |
April | 0.391936E+10 | 0.309177E+10 | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.00 | 0.00 |
May | 0.359880E+10 | 0.176060E+10 | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.384347E+10 | 0.105244E+10 | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.00 | 0.00 |
July | 0.439971E+10 | 0.859073E+09 | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.00 | 0.00 |
August | 0.514511E+10 | 0.109038E+10 | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.00 | 0.00 |
September | 0.595169E+10 | 0.196985E+10 | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.00 | 0.00 |
October | 0.637872E+10 | 0.330970E+10 | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.00 | 0.00 |
November | 0.404300E+10 | 0.464601E+10 | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.00 | 0.00 |
December | 0.468994E+10 | 0.682819E+10 | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.570392E+11 | 0.415125E+11 | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.359880E+10 | 0.859073E+09 | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.637872E+10 | 0.724703E+10 | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691936E+10 | 0.977751E+10 | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.00 | 0.00 |
February | 0.685103E+10 | 0.709129E+10 | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.00 | 0.00 |
March | 0.612857E+10 | 0.596753E+10 | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.00 | 0.00 |
April | 0.519894E+10 | 0.422116E+10 | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.00 | 0.00 |
May | 0.475713E+10 | 0.239547E+10 | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.00 | 0.00 |
June | 0.512156E+10 | 0.142050E+10 | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.00 | 0.00 |
July | 0.587332E+10 | 0.114227E+10 | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.00 | 0.00 |
August | 0.685644E+10 | 0.144455E+10 | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.00 | 0.00 |
September | 0.790958E+10 | 0.264569E+10 | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.00 | 0.00 |
October | 0.841866E+10 | 0.448973E+10 | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.00 | 0.00 |
November | 0.531258E+10 | 0.634396E+10 | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.00 | 0.00 |
December | 0.617972E+10 | 0.926647E+10 | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.755269E+11 | 0.562061E+11 | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.00 | 0.00 |
Minimum of Months | 0.475713E+10 | 0.114227E+10 | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841866E+10 | 0.977751E+10 | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337995E+09 | 0.160342E+10 | 0.748309E+09 | 0.431415E+09 | 0.316894E+09 | 0.00 | 0.00 |
February | 0.464837E+09 | 0.116375E+10 | 0.829313E+09 | 0.491083E+09 | 0.338230E+09 | 0.00 | 0.00 |
March | 0.591561E+09 | 0.898240E+09 | 0.930041E+09 | 0.409925E+09 | 0.520116E+09 | 0.00 | 0.00 |
April | 0.895891E+09 | 0.605487E+09 | 0.108302E+10 | 0.522652E+09 | 0.560370E+09 | 0.00 | 0.00 |
May | 0.982647E+09 | 0.325805E+09 | 0.106517E+10 | 0.387727E+09 | 0.677444E+09 | 0.00 | 0.00 |
June | 0.122742E+10 | 0.182762E+09 | 0.113905E+10 | 0.423494E+09 | 0.715557E+09 | 0.00 | 0.00 |
July | 0.141068E+10 | 0.143735E+09 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
August | 0.132435E+10 | 0.183435E+09 | 0.117681E+10 | 0.498404E+09 | 0.678406E+09 | 0.00 | 0.00 |
September | 0.109520E+10 | 0.357035E+09 | 0.106219E+10 | 0.521121E+09 | 0.541072E+09 | 0.00 | 0.00 |
October | 0.784591E+09 | 0.647484E+09 | 0.933147E+09 | 0.503000E+09 | 0.430148E+09 | 0.00 | 0.00 |
November | 0.362693E+09 | 0.989126E+09 | 0.607482E+09 | 0.311969E+09 | 0.295513E+09 | 0.00 | 0.00 |
December | 0.330545E+09 | 0.147535E+10 | 0.586489E+09 | 0.383497E+09 | 0.202992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980842E+10 | 0.857563E+10 | 0.114213E+11 | 0.540923E+10 | 0.601208E+10 | 0.00 | 0.00 |
Minimum of Months | 0.330545E+09 | 0.143735E+09 | 0.586489E+09 | 0.311969E+09 | 0.202992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141068E+10 | 0.160342E+10 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60051092.32 | 0.179874E+10 | 0.364990E+09 | 0.118673E+09 | 0.246317E+09 | 0.00 | 0.00 |
February | 0.159019E+09 | 0.128479E+10 | 0.468450E+09 | 0.189369E+09 | 0.279081E+09 | 0.00 | 0.00 |
March | 0.309320E+09 | 0.926668E+09 | 0.647318E+09 | 0.189044E+09 | 0.458274E+09 | 0.00 | 0.00 |
April | 0.692322E+09 | 0.603946E+09 | 0.875254E+09 | 0.357208E+09 | 0.518045E+09 | 0.00 | 0.00 |
May | 0.886516E+09 | 0.317975E+09 | 0.954195E+09 | 0.306014E+09 | 0.648181E+09 | 0.00 | 0.00 |
June | 0.118102E+10 | 0.175134E+09 | 0.108025E+10 | 0.386366E+09 | 0.693885E+09 | 0.00 | 0.00 |
July | 0.133421E+10 | 0.138574E+09 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
August | 0.116625E+10 | 0.179147E+09 | 0.100970E+10 | 0.377708E+09 | 0.631991E+09 | 0.00 | 0.00 |
September | 0.795405E+09 | 0.354980E+09 | 0.784351E+09 | 0.304189E+09 | 0.480163E+09 | 0.00 | 0.00 |
October | 0.385183E+09 | 0.659701E+09 | 0.574235E+09 | 0.207605E+09 | 0.366630E+09 | 0.00 | 0.00 |
November | 0.116257E+09 | 0.105688E+10 | 0.342478E+09 | 99641378.41 | 0.242837E+09 | 0.00 | 0.00 |
December | 58007716.79 | 0.159959E+10 | 0.263144E+09 | 0.101017E+09 | 0.162127E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.714356E+10 | 0.909613E+10 | 0.852994E+10 | 0.309645E+10 | 0.543350E+10 | 0.00 | 0.00 |
Minimum of Months | 58007716.79 | 0.138574E+09 | 0.263144E+09 | 99641378.41 | 0.162127E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133421E+10 | 0.179874E+10 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298601E+09 | 0.394311E+09 | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.00 | 0.00 |
February | 0.283754E+09 | 0.325217E+09 | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.00 | 0.00 |
March | 0.247983E+09 | 0.280751E+09 | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.00 | 0.00 |
April | 0.202425E+09 | 0.232417E+09 | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.00 | 0.00 |
May | 0.168410E+09 | 0.146997E+09 | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.00 | 0.00 |
June | 0.184509E+09 | 96636876.11 | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.00 | 0.00 |
July | 0.214016E+09 | 82358264.93 | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.00 | 0.00 |
August | 0.259015E+09 | 98753255.99 | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.00 | 0.00 |
September | 0.312242E+09 | 0.158375E+09 | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.00 | 0.00 |
October | 0.332039E+09 | 0.248810E+09 | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.00 | 0.00 |
November | 0.212590E+09 | 0.314102E+09 | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.00 | 0.00 |
December | 0.264784E+09 | 0.377004E+09 | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.298037E+10 | 0.275573E+10 | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.168410E+09 | 82358264.93 | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.00 | 0.00 |
Maximum of Months | 0.332039E+09 | 0.394311E+09 | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.549821E+09 | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.00 |
February | 602525.78 | 0.400886E+09 | 67056690.67 | 0.00 | 67056690.67 | 0.00 | 0.00 |
March | 19794008.25 | 0.284894E+09 | 0.111280E+09 | 941.15 | 0.111279E+09 | 0.00 | 0.00 |
April | 54885343.75 | 0.178876E+09 | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 0.00 | 0.00 |
May | 0.126130E+09 | 87600738.03 | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.00 | 0.00 |
June | 0.190106E+09 | 47043064.44 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
July | 0.198057E+09 | 35789374.85 | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.00 | 0.00 |
August | 0.172365E+09 | 47408691.54 | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.00 | 0.00 |
September | 98753825.97 | 0.101819E+09 | 0.114208E+09 | 102488.46 | 0.114105E+09 | 0.00 | 0.00 |
October | 27568243.35 | 0.197061E+09 | 87633982.09 | 0.00 | 87633982.09 | 0.00 | 0.00 |
November | 5214569.50 | 0.321793E+09 | 59323427.52 | 0.00 | 59323427.52 | 0.00 | 0.00 |
December | 0.00 | 0.483225E+09 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.893477E+09 | 0.273622E+10 | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 35789374.85 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Maximum of Months | 0.198057E+09 | 0.549821E+09 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333834E+09 | 0.159659E+10 | 0.748545E+09 | 0.432434E+09 | 0.316111E+09 | 0.00 | 0.00 |
February | 0.417831E+09 | 0.114664E+10 | 0.795886E+09 | 0.456300E+09 | 0.339586E+09 | 0.00 | 0.00 |
March | 0.603361E+09 | 0.885424E+09 | 0.949929E+09 | 0.430432E+09 | 0.519498E+09 | 0.00 | 0.00 |
April | 0.768732E+09 | 0.591543E+09 | 0.987526E+09 | 0.438565E+09 | 0.548961E+09 | 0.00 | 0.00 |
May | 0.104330E+10 | 0.306894E+09 | 0.113487E+10 | 0.445751E+09 | 0.689117E+09 | 0.00 | 0.00 |
June | 0.123802E+10 | 0.172071E+09 | 0.116214E+10 | 0.436297E+09 | 0.725840E+09 | 0.00 | 0.00 |
July | 0.135947E+10 | 0.133754E+09 | 0.122942E+10 | 0.498717E+09 | 0.730702E+09 | 0.00 | 0.00 |
August | 0.124469E+10 | 0.171072E+09 | 0.112265E+10 | 0.453303E+09 | 0.669350E+09 | 0.00 | 0.00 |
September | 0.110564E+10 | 0.347022E+09 | 0.108201E+10 | 0.530786E+09 | 0.551228E+09 | 0.00 | 0.00 |
October | 0.731933E+09 | 0.634183E+09 | 0.901231E+09 | 0.475534E+09 | 0.425696E+09 | 0.00 | 0.00 |
November | 0.329527E+09 | 0.977129E+09 | 0.586899E+09 | 0.292740E+09 | 0.294159E+09 | 0.00 | 0.00 |
December | 0.302691E+09 | 0.146129E+10 | 0.570618E+09 | 0.367081E+09 | 0.203537E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.947903E+10 | 0.842362E+10 | 0.112717E+11 | 0.525794E+10 | 0.601379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.302691E+09 | 0.133754E+09 | 0.570618E+09 | 0.292740E+09 | 0.203537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135947E+10 | 0.159659E+10 | 0.122942E+10 | 0.530786E+09 | 0.730702E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39073409.42 | 0.177477E+10 | 0.365226E+09 | 0.119692E+09 | 0.245534E+09 | 0.00 | 0.00 |
February | 0.106245E+09 | 0.126124E+10 | 0.435023E+09 | 0.154586E+09 | 0.280437E+09 | 0.00 | 0.00 |
March | 0.311568E+09 | 0.904417E+09 | 0.667206E+09 | 0.209551E+09 | 0.457655E+09 | 0.00 | 0.00 |
April | 0.563549E+09 | 0.588160E+09 | 0.779757E+09 | 0.273121E+09 | 0.506636E+09 | 0.00 | 0.00 |
May | 0.948720E+09 | 0.301428E+09 | 0.102389E+10 | 0.364038E+09 | 0.659854E+09 | 0.00 | 0.00 |
June | 0.119653E+10 | 0.169430E+09 | 0.110334E+10 | 0.399169E+09 | 0.704169E+09 | 0.00 | 0.00 |
July | 0.128622E+10 | 0.131904E+09 | 0.113471E+10 | 0.433385E+09 | 0.701329E+09 | 0.00 | 0.00 |
August | 0.108794E+10 | 0.168470E+09 | 0.955542E+09 | 0.332608E+09 | 0.622934E+09 | 0.00 | 0.00 |
September | 0.802923E+09 | 0.343436E+09 | 0.804173E+09 | 0.313854E+09 | 0.490319E+09 | 0.00 | 0.00 |
October | 0.321772E+09 | 0.635540E+09 | 0.542318E+09 | 0.180140E+09 | 0.362178E+09 | 0.00 | 0.00 |
November | 77138191.01 | 0.103884E+10 | 0.321895E+09 | 80412113.67 | 0.241483E+09 | 0.00 | 0.00 |
December | 30262833.47 | 0.158645E+10 | 0.247273E+09 | 84600328.40 | 0.162673E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.677193E+10 | 0.890409E+10 | 0.838036E+10 | 0.294516E+10 | 0.543520E+10 | 0.00 | 0.00 |
Minimum of Months | 30262833.47 | 0.131904E+09 | 0.247273E+09 | 80412113.67 | 0.162673E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128622E+10 | 0.177477E+10 | 0.113471E+10 | 0.433385E+09 | 0.704169E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470180E+09 | 0.196275E+10 | 0.918002E+09 | 0.541992E+09 | 0.376010E+09 | 0.00 | 0.00 |
February | 0.518410E+09 | 0.140534E+10 | 0.915899E+09 | 0.522880E+09 | 0.393019E+09 | 0.00 | 0.00 |
March | 0.590383E+09 | 0.112893E+10 | 0.972071E+09 | 0.382798E+09 | 0.589274E+09 | 0.00 | 0.00 |
April | 0.620215E+09 | 0.747033E+09 | 0.900763E+09 | 0.291055E+09 | 0.609707E+09 | 0.00 | 0.00 |
May | 0.755868E+09 | 0.375290E+09 | 0.918743E+09 | 0.169058E+09 | 0.749685E+09 | 0.00 | 0.00 |
June | 0.931311E+09 | 0.199498E+09 | 0.924524E+09 | 0.140489E+09 | 0.784035E+09 | 0.00 | 0.00 |
July | 0.102137E+10 | 0.153525E+09 | 0.961416E+09 | 0.168104E+09 | 0.793313E+09 | 0.00 | 0.00 |
August | 0.105748E+10 | 0.203447E+09 | 0.957681E+09 | 0.222633E+09 | 0.735048E+09 | 0.00 | 0.00 |
September | 0.984482E+09 | 0.425176E+09 | 0.976296E+09 | 0.376394E+09 | 0.599902E+09 | 0.00 | 0.00 |
October | 0.849470E+09 | 0.785331E+09 | 0.100167E+10 | 0.511928E+09 | 0.489739E+09 | 0.00 | 0.00 |
November | 0.449056E+09 | 0.121324E+10 | 0.716270E+09 | 0.367971E+09 | 0.348299E+09 | 0.00 | 0.00 |
December | 0.460246E+09 | 0.181264E+10 | 0.732636E+09 | 0.489548E+09 | 0.243088E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870847E+10 | 0.104122E+11 | 0.108960E+11 | 0.418485E+10 | 0.671112E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449056E+09 | 0.153525E+09 | 0.716270E+09 | 0.140489E+09 | 0.243088E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105748E+10 | 0.196275E+10 | 0.100167E+10 | 0.541992E+09 | 0.793313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335848E+09 | 0.161065E+10 | 0.748923E+09 | 0.431769E+09 | 0.317154E+09 | 0.00 | 0.00 |
February | 0.461454E+09 | 0.117027E+10 | 0.829993E+09 | 0.491486E+09 | 0.338508E+09 | 0.00 | 0.00 |
March | 0.590632E+09 | 0.899189E+09 | 0.930804E+09 | 0.410261E+09 | 0.520543E+09 | 0.00 | 0.00 |
April | 0.890951E+09 | 0.605798E+09 | 0.108391E+10 | 0.523081E+09 | 0.560830E+09 | 0.00 | 0.00 |
May | 0.972815E+09 | 0.327871E+09 | 0.106604E+10 | 0.388045E+09 | 0.678000E+09 | 0.00 | 0.00 |
June | 0.121781E+10 | 0.183935E+09 | 0.113998E+10 | 0.423841E+09 | 0.716144E+09 | 0.00 | 0.00 |
July | 0.140005E+10 | 0.144827E+09 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
August | 0.131450E+10 | 0.185156E+09 | 0.117778E+10 | 0.498813E+09 | 0.678963E+09 | 0.00 | 0.00 |
September | 0.108983E+10 | 0.357163E+09 | 0.106306E+10 | 0.521548E+09 | 0.541516E+09 | 0.00 | 0.00 |
October | 0.782435E+09 | 0.646933E+09 | 0.933913E+09 | 0.503412E+09 | 0.430500E+09 | 0.00 | 0.00 |
November | 0.362990E+09 | 0.989334E+09 | 0.607981E+09 | 0.312225E+09 | 0.295756E+09 | 0.00 | 0.00 |
December | 0.331203E+09 | 0.147894E+10 | 0.586970E+09 | 0.383812E+09 | 0.203158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975053E+10 | 0.860007E+10 | 0.114307E+11 | 0.541366E+10 | 0.601701E+10 | 0.00 | 0.00 |
Minimum of Months | 0.331203E+09 | 0.144827E+09 | 0.586970E+09 | 0.312225E+09 | 0.203158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140005E+10 | 0.161065E+10 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59772453.56 | 0.180719E+10 | 0.365289E+09 | 0.118770E+09 | 0.246519E+09 | 0.00 | 0.00 |
February | 0.158276E+09 | 0.129239E+10 | 0.468835E+09 | 0.189524E+09 | 0.279310E+09 | 0.00 | 0.00 |
March | 0.309550E+09 | 0.927379E+09 | 0.647849E+09 | 0.189199E+09 | 0.458650E+09 | 0.00 | 0.00 |
April | 0.687889E+09 | 0.603920E+09 | 0.875972E+09 | 0.357501E+09 | 0.518470E+09 | 0.00 | 0.00 |
May | 0.875985E+09 | 0.319854E+09 | 0.954978E+09 | 0.306265E+09 | 0.648713E+09 | 0.00 | 0.00 |
June | 0.117051E+10 | 0.176334E+09 | 0.108114E+10 | 0.386683E+09 | 0.694454E+09 | 0.00 | 0.00 |
July | 0.132273E+10 | 0.139691E+09 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
August | 0.115563E+10 | 0.180786E+09 | 0.101053E+10 | 0.378018E+09 | 0.632509E+09 | 0.00 | 0.00 |
September | 0.790342E+09 | 0.354673E+09 | 0.784995E+09 | 0.304438E+09 | 0.480556E+09 | 0.00 | 0.00 |
October | 0.386088E+09 | 0.657197E+09 | 0.574706E+09 | 0.207776E+09 | 0.366931E+09 | 0.00 | 0.00 |
November | 0.117622E+09 | 0.105580E+10 | 0.342759E+09 | 99723118.67 | 0.243036E+09 | 0.00 | 0.00 |
December | 58558062.70 | 0.160332E+10 | 0.263360E+09 | 0.101100E+09 | 0.162260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.709294E+10 | 0.911853E+10 | 0.853694E+10 | 0.309899E+10 | 0.543795E+10 | 0.00 | 0.00 |
Minimum of Months | 58558062.70 | 0.139691E+09 | 0.263360E+09 | 99723118.67 | 0.162260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132273E+10 | 0.180719E+10 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.513689E+09 | 0.819901E+09 | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.00 | 0.00 |
February | 0.505760E+09 | 0.603086E+09 | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.00 | 0.00 |
March | 0.464951E+09 | 0.477279E+09 | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.00 | 0.00 |
April | 0.403730E+09 | 0.323059E+09 | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.00 | 0.00 |
May | 0.370791E+09 | 0.172158E+09 | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.00 | 0.00 |
June | 0.407528E+09 | 93568881.13 | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.00 | 0.00 |
July | 0.465929E+09 | 71115285.57 | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.00 | 0.00 |
August | 0.541621E+09 | 93175571.76 | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.00 | 0.00 |
September | 0.621564E+09 | 0.186735E+09 | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.00 | 0.00 |
October | 0.651211E+09 | 0.339363E+09 | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.00 | 0.00 |
November | 0.405083E+09 | 0.508617E+09 | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.00 | 0.00 |
December | 0.468536E+09 | 0.755322E+09 | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.582039E+10 | 0.444338E+10 | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370791E+09 | 71115285.57 | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.651211E+09 | 0.819901E+09 | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.493701E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 1742890.49 | 0.357978E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.135001E+09 | 0.274532E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.416347E+09 | 0.178519E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.992051E+09 | 0.928792E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.152897E+10 | 0.544921E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.159562E+10 | 0.443575E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.139360E+10 | 0.564821E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.787616E+09 | 0.107114E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.190707E+09 | 0.195802E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 31498309.77 | 0.304833E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.448196E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.707315E+10 | 0.260889E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.443575E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159562E+10 | 0.493701E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.503064E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 958332.19 | 0.365849E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.120710E+09 | 0.282430E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.393361E+09 | 0.184149E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.950686E+09 | 0.961005E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.149050E+10 | 0.567788E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.155684E+10 | 0.463933E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.135636E+10 | 0.589907E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.758752E+09 | 0.110957E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.170797E+09 | 0.202044E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 26072325.82 | 0.313166E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.458485E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.682503E+10 | 0.267841E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.463933E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.155684E+10 | 0.503064E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333439E+09 | 0.315104E+10 | 0.111464E+10 | 0.552562E+09 | 0.562081E+09 | 0.00 | 0.00 |
February | 0.537498E+09 | 0.220340E+10 | 0.123187E+10 | 0.611366E+09 | 0.620503E+09 | 0.00 | 0.00 |
March | 0.993599E+09 | 0.180693E+10 | 0.161839E+10 | 0.640478E+09 | 0.977909E+09 | 0.00 | 0.00 |
April | 0.148438E+10 | 0.121868E+10 | 0.176864E+10 | 0.712232E+09 | 0.105641E+10 | 0.00 | 0.00 |
May | 0.227373E+10 | 0.666645E+09 | 0.216042E+10 | 0.810402E+09 | 0.135001E+10 | 0.00 | 0.00 |
June | 0.275407E+10 | 0.397524E+09 | 0.226721E+10 | 0.836098E+09 | 0.143111E+10 | 0.00 | 0.00 |
July | 0.300612E+10 | 0.311336E+09 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
August | 0.266826E+10 | 0.389876E+09 | 0.207979E+10 | 0.786509E+09 | 0.129328E+10 | 0.00 | 0.00 |
September | 0.216733E+10 | 0.720593E+09 | 0.188764E+10 | 0.845288E+09 | 0.104235E+10 | 0.00 | 0.00 |
October | 0.119381E+10 | 0.128758E+10 | 0.144467E+10 | 0.656187E+09 | 0.788485E+09 | 0.00 | 0.00 |
November | 0.430046E+09 | 0.197153E+10 | 0.909504E+09 | 0.373447E+09 | 0.536057E+09 | 0.00 | 0.00 |
December | 0.283566E+09 | 0.295240E+10 | 0.818534E+09 | 0.452039E+09 | 0.366494E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181258E+11 | 0.170775E+11 | 0.196673E+11 | 0.820941E+10 | 0.114578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283566E+09 | 0.311336E+09 | 0.818534E+09 | 0.373447E+09 | 0.366494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300612E+10 | 0.315104E+10 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111228E+10 | 0.346144E+10 | 0.188144E+10 | 0.116852E+10 | 0.712925E+09 | 0.00 | 0.00 |
February | 0.118736E+10 | 0.246167E+10 | 0.186272E+10 | 0.112731E+10 | 0.735414E+09 | 0.00 | 0.00 |
March | 0.122733E+10 | 0.202687E+10 | 0.191002E+10 | 0.825297E+09 | 0.108472E+10 | 0.00 | 0.00 |
April | 0.120184E+10 | 0.137056E+10 | 0.173371E+10 | 0.625835E+09 | 0.110787E+10 | 0.00 | 0.00 |
May | 0.133245E+10 | 0.723354E+09 | 0.170092E+10 | 0.353908E+09 | 0.134701E+10 | 0.00 | 0.00 |
June | 0.156730E+10 | 0.417511E+09 | 0.167632E+10 | 0.273554E+09 | 0.140276E+10 | 0.00 | 0.00 |
July | 0.173509E+10 | 0.341856E+09 | 0.176562E+10 | 0.341282E+09 | 0.142433E+10 | 0.00 | 0.00 |
August | 0.187224E+10 | 0.433155E+09 | 0.180735E+10 | 0.474802E+09 | 0.133254E+10 | 0.00 | 0.00 |
September | 0.188367E+10 | 0.810708E+09 | 0.191424E+10 | 0.811322E+09 | 0.110292E+10 | 0.00 | 0.00 |
October | 0.175156E+10 | 0.142401E+10 | 0.201329E+10 | 0.110370E+10 | 0.909592E+09 | 0.00 | 0.00 |
November | 0.979291E+09 | 0.216898E+10 | 0.144524E+10 | 0.793333E+09 | 0.651906E+09 | 0.00 | 0.00 |
December | 0.105569E+10 | 0.322736E+10 | 0.151317E+10 | 0.105545E+10 | 0.457722E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169061E+11 | 0.188675E+11 | 0.212240E+11 | 0.895431E+10 | 0.122697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.979291E+09 | 0.341856E+09 | 0.144524E+10 | 0.273554E+09 | 0.457722E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188367E+10 | 0.346144E+10 | 0.201329E+10 | 0.116852E+10 | 0.142433E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.510487E+11 | -.799002E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154223E+10 | 58.97 | 0.00 | 0.00 |
February | 0.477478E+11 | -.736382E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.144220E+10 | 58.95 | 0.00 | 0.00 |
March | 0.519957E+11 | -.807628E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.155702E+10 | 58.96 | 0.00 | 0.00 |
April | 0.470429E+11 | -.751029E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.152337E+10 | 58.97 | 0.00 | 0.00 |
May | 0.436251E+11 | -.729823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157431E+10 | 58.99 | 0.00 | 0.00 |
June | 0.371894E+11 | -.659618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.152374E+10 | 59.07 | 0.00 | 0.00 |
July | 0.342301E+11 | -.642694E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157154E+10 | 59.10 | 0.00 | 0.00 |
August | 0.324294E+11 | -.626248E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154503E+10 | 59.17 | 0.00 | 0.00 |
September | 0.321976E+11 | -.613952E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.145958E+10 | 59.15 | 0.00 | 0.00 |
October | 0.366336E+11 | -.665938E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147593E+10 | 59.10 | 0.00 | 0.00 |
November | 0.402608E+11 | -.689047E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.143033E+10 | 59.01 | 0.00 | 0.00 |
December | 0.468434E+11 | -.760607E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.148097E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.501245E+12 | -.848197E+12 | 8760.00 | -.181262E+11 | 59.04 | |||||
Minimum of Months | 0.321976E+11 | -.807628E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.157431E+10 | 58.95 | 0.00 | 0.00 |
Maximum of Months | 0.519957E+11 | -.613952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.143033E+10 | 59.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770832E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165549454.1 | 81.21 | 0.00 | 0.00 |
February | 0.696679E+10 | -.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -150814026.0 | 81.21 | 0.00 | 0.00 |
March | 0.770496E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162150687.3 | 81.21 | 0.00 | 0.00 |
April | 0.746535E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156759686.0 | 81.21 | 0.00 | 0.00 |
May | 0.770487E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162069536.6 | 81.21 | 0.00 | 0.00 |
June | 0.745769E+10 | -.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157152073.6 | 81.21 | 0.00 | 0.00 |
July | 0.771343E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162586016.7 | 81.21 | 0.00 | 0.00 |
August | 0.770527E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162462080.6 | 81.21 | 0.00 | 0.00 |
September | 0.746556E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156962292.0 | 81.21 | 0.00 | 0.00 |
October | 0.770468E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161893963.4 | 81.21 | 0.00 | 0.00 |
November | 0.744987E+10 | -.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157429738.3 | 81.21 | 0.00 | 0.00 |
December | 0.771342E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162570144.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907602E+11 | -.888418E+11 | 8760.00 | -.191840E+10 | 81.21 | |||||
Minimum of Months | 0.696679E+10 | -.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165549454.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771343E+10 | -.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150814026.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.795295E+11 | -.783525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117693E+10 | 61.11 | 0.00 | 0.00 |
February | 0.719850E+11 | -.708972E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108787E+10 | 60.70 | 0.00 | 0.00 |
March | 0.796045E+11 | -.784246E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117991E+10 | 60.84 | 0.00 | 0.00 |
April | 0.767446E+11 | -.755696E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.117503E+10 | 61.58 | 0.00 | 0.00 |
May | 0.788393E+11 | -.775943E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124501E+10 | 62.61 | 0.00 | 0.00 |
June | 0.758241E+11 | -.745900E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.123403E+10 | 63.69 | 0.00 | 0.00 |
July | 0.779704E+11 | -.766730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129737E+10 | 64.53 | 0.00 | 0.00 |
August | 0.777925E+11 | -.765050E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128748E+10 | 64.91 | 0.00 | 0.00 |
September | 0.753619E+11 | -.741467E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.121514E+10 | 64.72 | 0.00 | 0.00 |
October | 0.781880E+11 | -.769755E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121251E+10 | 64.01 | 0.00 | 0.00 |
November | 0.761149E+11 | -.749659E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.114894E+10 | 63.02 | 0.00 | 0.00 |
December | 0.791414E+11 | -.779846E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.115680E+10 | 61.91 | 0.00 | 0.00 |
Annual Sum or Average | 0.927096E+12 | -.912679E+12 | 8760.00 | -.144170E+11 | 62.81 | |||||
Minimum of Months | 0.719850E+11 | -.784246E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129737E+10 | 60.70 | 0.00 | 0.00 |
Maximum of Months | 0.796045E+11 | -.708972E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108787E+10 | 64.91 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.93 | 0.93 | 01-JAN-09:39 | 5932.51 | 37.80 | 207.17 | 248.17 | 3985.16 | 37.27 | 208.17 | 216.33 |
February | 226.83 | 0.93 | 0.93 | 01-FEB-07:49 | 7191.88 | 37.61 | 221.17 | 256.17 | 1525.40 | 28.83 | 206.83 | 230.50 |
March | 334.33 | 0.93 | 0.93 | 01-MAR-07:40 | 4015.40 | 25.90 | 188.83 | 328.67 | 693.16 | 22.05 | 229.33 | 279.50 |
April | 285.17 | 0.93 | 0.93 | 01-APR-06:49 | 1486.10 | 20.59 | 99.50 | 348.17 | 606.48 | 22.33 | 217.50 | 274.83 |
May | 428.67 | 0.93 | 0.93 | 01-MAY-05:00 | 1222.64 | 19.68 | 45.83 | 397.50 | 479.02 | 21.41 | 269.67 | 325.00 |
June | 400.67 | 0.93 | 0.93 | 01-JUN-05:19 | 1245.24 | 20.07 | 91.17 | 398.67 | 499.27 | 21.81 | 275.17 | 328.00 |
July | 414.00 | 0.93 | 0.93 | 01-JUL-05:40 | 1280.53 | 20.41 | 99.17 | 408.33 | 517.12 | 22.15 | 303.50 | 338.50 |
August | 410.83 | 0.93 | 0.93 | 01-AUG-05:00 | 1435.96 | 20.15 | 101.50 | 379.83 | 563.74 | 21.87 | 297.33 | 324.67 |
September | 326.50 | 0.93 | 0.93 | 01-SEP-06:10 | 2431.46 | 22.83 | 160.67 | 334.83 | 669.68 | 22.47 | 243.67 | 286.83 |
October | 325.17 | 0.93 | 0.93 | 01-OCT-06:40 | 6240.09 | 33.55 | 295.17 | 308.67 | 849.06 | 23.47 | 230.33 | 276.67 |
November | 254.83 | 0.93 | 0.93 | 01-NOV-07:40 | 4242.42 | 33.07 | 238.17 | 250.50 | 2039.70 | 30.51 | 220.50 | 218.33 |
December | 186.17 | 0.93 | 0.93 | 01-DEC-07:00 | 5142.07 | 37.90 | 180.17 | 224.50 | 4567.17 | 38.88 | 180.83 | 171.83 |
Annual Sum or Average | 3807.33 | 0.93 | 3065.82 | 25.79 | 1928.50 | 3884.00 | 1134.66 | 24.77 | 2882.83 | 3271.00 | ||
Minimum of Months | 186.17 | 0.93 | 0.93 | 1222.64 | 19.68 | 45.83 | 224.50 | 479.02 | 21.41 | 180.83 | 171.83 | |
Maximum of Months | 428.67 | 0.93 | 0.93 | 7191.88 | 37.90 | 295.17 | 408.33 | 4567.17 | 38.88 | 303.50 | 338.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.62 | 0.61 | 01-JAN-09:39 | 6416.74 | 37.89 | 207.17 | 257.50 | 4468.49 | 37.25 | 203.17 | 234.83 |
February | 226.83 | 0.62 | 0.61 | 01-FEB-07:49 | 7668.71 | 37.67 | 221.50 | 263.83 | 1998.22 | 28.57 | 195.83 | 247.50 |
March | 334.33 | 0.62 | 0.61 | 01-MAR-07:40 | 4362.67 | 26.14 | 195.17 | 340.50 | 1037.25 | 22.20 | 226.83 | 309.17 |
April | 285.17 | 0.62 | 0.61 | 01-APR-06:40 | 1820.93 | 20.83 | 107.50 | 360.33 | 940.22 | 22.42 | 217.17 | 327.50 |
May | 428.67 | 0.62 | 0.61 | 01-MAY-05:49 | 1443.82 | 20.27 | 102.67 | 412.17 | 699.35 | 21.81 | 287.17 | 370.83 |
June | 400.67 | 0.63 | 0.61 | 01-JUN-05:10 | 1465.40 | 20.64 | 150.67 | 412.83 | 718.58 | 22.19 | 300.67 | 376.33 |
July | 414.00 | 0.62 | 0.61 | 01-JUL-05:40 | 1516.01 | 20.93 | 163.67 | 422.83 | 751.71 | 22.48 | 323.50 | 387.00 |
August | 410.83 | 0.63 | 0.61 | 01-AUG-05:49 | 1695.83 | 20.61 | 145.33 | 392.50 | 822.58 | 22.16 | 312.67 | 362.00 |
September | 326.50 | 0.62 | 0.61 | 01-SEP-05:00 | 2782.69 | 23.03 | 160.17 | 344.17 | 1019.54 | 22.56 | 254.67 | 316.00 |
October | 325.17 | 0.62 | 0.61 | 01-OCT-06:40 | 6619.08 | 33.71 | 297.00 | 315.17 | 1228.11 | 23.51 | 227.83 | 295.67 |
November | 254.83 | 0.62 | 0.61 | 01-NOV-07:30 | 4569.71 | 33.19 | 240.00 | 259.50 | 2367.10 | 30.56 | 224.67 | 238.50 |
December | 186.17 | 0.62 | 0.61 | 01-DEC-07:49 | 5593.27 | 38.00 | 180.33 | 235.67 | 5014.66 | 38.95 | 180.83 | 205.33 |
Annual Sum or Average | 3807.33 | 0.62 | 3385.22 | 26.12 | 2171.17 | 4017.00 | 1452.73 | 24.95 | 2955.00 | 3670.67 | ||
Minimum of Months | 186.17 | 0.62 | 0.61 | 1443.82 | 20.27 | 102.67 | 235.67 | 699.35 | 21.81 | 180.83 | 205.33 | |
Maximum of Months | 428.67 | 0.63 | 0.61 | 7668.71 | 38.00 | 297.00 | 422.83 | 5014.66 | 38.95 | 323.50 | 387.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.82 | 0.80 | 01-JAN-09:39 | 426.55 | 15.27 | 0.00 | 228.33 | 208.04 | 18.77 | 0.17 | 114.83 |
February | 226.83 | 0.82 | 0.80 | 01-FEB-08:30 | 437.85 | 15.51 | 0.00 | 239.83 | 215.46 | 18.96 | 0.00 | 140.17 |
March | 334.33 | 0.81 | 0.80 | 01-MAR-07:40 | 615.19 | 16.80 | 0.00 | 327.00 | 275.71 | 20.02 | 3.33 | 255.17 |
April | 285.17 | 0.81 | 0.80 | 01-APR-06:49 | 699.12 | 17.97 | 0.00 | 358.67 | 332.82 | 21.19 | 105.17 | 288.50 |
May | 428.67 | 0.80 | 0.80 | 01-MAY-05:40 | 825.64 | 18.05 | 4.17 | 419.67 | 360.79 | 22.07 | 183.33 | 379.67 |
June | 400.67 | 0.81 | 0.80 | 01-JUN-04:00 | 1002.05 | 21.06 | 66.83 | 421.83 | 464.56 | 24.14 | 281.33 | 392.83 |
July | 414.00 | 0.80 | 0.80 | 01-JUL-05:40 | 936.54 | 20.61 | 53.83 | 429.67 | 433.82 | 23.29 | 275.00 | 400.67 |
August | 410.83 | 0.81 | 0.80 | 01-AUG-05:40 | 770.21 | 18.13 | 4.50 | 396.17 | 349.93 | 21.52 | 172.00 | 364.17 |
September | 326.50 | 0.81 | 0.80 | 01-SEP-05:00 | 618.06 | 17.50 | 0.00 | 338.50 | 297.04 | 20.70 | 39.00 | 280.00 |
October | 325.17 | 0.81 | 0.80 | 01-OCT-06:00 | 501.03 | 15.99 | 0.00 | 295.17 | 231.33 | 19.31 | 0.00 | 204.17 |
November | 254.83 | 0.81 | 0.80 | 01-NOV-07:40 | 438.96 | 15.06 | 0.00 | 235.00 | 194.35 | 18.37 | 0.00 | 118.33 |
December | 186.17 | 0.83 | 0.80 | 01-DEC-08:20 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 |
Annual Sum or Average | 3807.33 | 0.81 | 679.79 | 17.60 | 129.33 | 3883.17 | 313.86 | 20.92 | 1059.33 | 2972.67 | ||
Minimum of Months | 186.17 | 0.80 | 0.80 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 | |
Maximum of Months | 428.67 | 0.83 | 0.80 | 1002.05 | 21.06 | 66.83 | 429.67 | 464.56 | 24.14 | 281.33 | 400.67 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.82 | 0.80 | 01-JAN-09:39 | 426.55 | 15.27 | 0.00 | 228.33 | 208.04 | 18.77 | 0.17 | 114.83 |
February | 226.83 | 0.82 | 0.80 | 01-FEB-08:30 | 437.85 | 15.51 | 0.00 | 239.83 | 215.46 | 18.96 | 0.00 | 140.17 |
March | 334.33 | 0.81 | 0.80 | 01-MAR-07:40 | 615.19 | 16.80 | 0.00 | 327.00 | 275.71 | 20.02 | 3.33 | 255.17 |
April | 285.17 | 0.81 | 0.80 | 01-APR-06:49 | 699.12 | 17.97 | 0.00 | 358.67 | 332.82 | 21.19 | 105.17 | 288.50 |
May | 428.67 | 0.80 | 0.80 | 01-MAY-05:40 | 825.64 | 18.05 | 4.17 | 419.67 | 360.79 | 22.07 | 183.33 | 379.67 |
June | 400.67 | 0.81 | 0.80 | 01-JUN-04:00 | 1002.05 | 21.06 | 66.83 | 421.83 | 464.56 | 24.14 | 281.33 | 392.83 |
July | 414.00 | 0.80 | 0.80 | 01-JUL-05:40 | 936.54 | 20.61 | 53.83 | 429.67 | 433.82 | 23.29 | 275.00 | 400.67 |
August | 410.83 | 0.81 | 0.80 | 01-AUG-05:40 | 770.21 | 18.13 | 4.50 | 396.17 | 349.93 | 21.52 | 172.00 | 364.17 |
September | 326.50 | 0.81 | 0.80 | 01-SEP-05:00 | 618.06 | 17.50 | 0.00 | 338.50 | 297.04 | 20.70 | 39.00 | 280.00 |
October | 325.17 | 0.81 | 0.80 | 01-OCT-06:00 | 501.03 | 15.99 | 0.00 | 295.17 | 231.33 | 19.31 | 0.00 | 204.17 |
November | 254.83 | 0.81 | 0.80 | 01-NOV-07:40 | 438.96 | 15.06 | 0.00 | 235.00 | 194.35 | 18.37 | 0.00 | 118.33 |
December | 186.17 | 0.83 | 0.80 | 01-DEC-08:20 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 |
Annual Sum or Average | 3807.33 | 0.81 | 679.79 | 17.60 | 129.33 | 3883.17 | 313.86 | 20.92 | 1059.33 | 2972.67 | ||
Minimum of Months | 186.17 | 0.80 | 0.80 | 302.50 | 13.82 | 0.00 | 193.33 | 153.42 | 17.46 | 0.00 | 34.17 | |
Maximum of Months | 428.67 | 0.83 | 0.80 | 1002.05 | 21.06 | 66.83 | 429.67 | 464.56 | 24.14 | 281.33 | 400.67 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232107E+10 | 7887.93 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398168E+10 | 8301.25 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26856900.60 | 2251.83 | 19-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151211E+10 | 5463.67 | 18-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199411E+10 | 5463.68 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129623E+10 | 4161.43 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218537E+09 | 2736.95 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136016E+09 | 7722.39 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114866E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398168E+10 | 8301.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.601015E+10 | 4747.13 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435041E+10 | 5005.92 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264727E+10 | 2633.45 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160280E+10 | 2201.72 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541801E+09 | 1142.95 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.268896E+09 | 896.37 | 03-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127816E+09 | 567.01 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87578651.50 | 476.36 | 20-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432646E+09 | 1499.93 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103296E+10 | 1615.82 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296418E+10 | 4643.99 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462741E+10 | 3303.90 | 12-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246939E+11 | |||||||
Minimum of Months | 87578651.50 | 476.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.601015E+10 | 5005.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.979835E+09 | 1653.47 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.761577E+09 | 1741.64 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66640857.49 | 477.87 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14395136.73 | 358.16 | 03-APR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196682E+09 | 1618.23 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287544E+09 | 796.65 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230667E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.979835E+09 | 1741.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276844E+10 | 2295.40 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200028E+10 | 2420.78 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839704E+09 | 1100.26 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303125E+09 | 764.06 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1036025.81 | 75.33 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 160739.33 | 58.95 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4509730.97 | 165.23 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.885270E+09 | 2245.44 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171819E+10 | 1502.94 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.852071E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276844E+10 | 2420.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220826E+10 | 1466.31 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159598E+10 | 1545.68 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895750E+09 | 879.82 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405686E+09 | 617.77 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16529084.66 | 205.49 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 316371.79 | 33.31 | 05-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11153795.30 | 246.48 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90191496.16 | 283.67 | 27-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881084E+09 | 1434.65 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161527E+10 | 1022.29 | 12-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772022E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220826E+10 | 1545.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.384052E+10 | 11456.30 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396016E+10 | 12056.43 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544158E+09 | 3326.06 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792328E+09 | 4281.03 | 16-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146997E+10 | 4957.03 | 31-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274190E+10 | 7354.84 | 26-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.365277E+10 | 7243.54 | 26-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329292E+10 | 7126.95 | 04-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186303E+10 | 7243.48 | 11-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476558E+09 | 3240.92 | 01-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.992187E+09 | 11215.95 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618821E+09 | 3600.09 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242453E+11 | |||||||
Minimum of Months | 0.476558E+09 | 3240.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396016E+10 | 12056.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.947126E+10 | 14199.46 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.687632E+10 | 14964.36 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174556E+10 | 5501.10 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985740E+09 | 5229.05 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72942879.07 | 1871.86 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92546438.01 | 1884.31 | 13-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 64068677.40 | 1706.58 | 10-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21851264.74 | 1276.68 | 31-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106230E+09 | 1981.78 | 27-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196236E+09 | 2850.74 | 26-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286025E+10 | 13894.12 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.495533E+10 | 8779.35 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274483E+11 | |||||||
Minimum of Months | 21851264.74 | 1276.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.947126E+10 | 14964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155008E+11 | 34186.81 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137669E+11 | 36009.01 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638482E+09 | 8542.38 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158030E+09 | 6045.81 | 03-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283029E+10 | 33458.42 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355762E+10 | 15816.97 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364522E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155008E+11 | 36009.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.874185E+10 | 8355.77 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604555E+10 | 8354.68 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333584E+10 | 8354.15 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147276E+10 | 8333.19 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189760E+09 | 6369.07 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77688264.82 | 4088.49 | 01-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7836827.89 | 4269.28 | 11-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7756008.35 | 3810.22 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.342025E+09 | 7803.96 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123042E+10 | 7933.81 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409652E+10 | 8353.88 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.714196E+10 | 8354.84 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326900E+11 | |||||||
Minimum of Months | 7756008.35 | 3810.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.874185E+10 | 8355.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100805E+11 | 8324.31 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710308E+10 | 8323.22 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388311E+10 | 8323.18 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164475E+10 | 8301.82 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221464E+09 | 7356.67 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82037643.78 | 4186.36 | 09-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7802487.98 | 4273.62 | 11-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8879664.64 | 3918.01 | 12-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423577E+09 | 7802.01 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168817E+10 | 7969.63 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479916E+10 | 8322.42 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819302E+10 | 8323.56 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381356E+11 | |||||||
Minimum of Months | 7802487.98 | 3918.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100805E+11 | 8324.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544937E+10 | 18894.80 | 19-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134904E+10 | 17555.51 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33739277.36 | 4652.34 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236480E+10 | 14638.09 | 13-DEC-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919696E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.544937E+10 | 18894.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418028E+11 | 45841.15 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285404E+11 | 46260.46 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102150E+11 | 45082.62 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271124E+10 | 43498.93 | 03-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97459443.75 | 26467.93 | 01-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24560357.13 | 17559.39 | 16-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17437895.17 | 22745.22 | 23-JUL-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22934086.10 | 25741.59 | 17-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213090E+09 | 34782.28 | 23-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152791E+10 | 39403.95 | 30-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140087E+11 | 45835.64 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292610E+11 | 45844.33 | 08-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128442E+12 | |||||||
Minimum of Months | 17437895.17 | 17559.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418028E+11 | 46260.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871332E+10 | 8009.87 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609598E+10 | 8010.65 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327663E+10 | 8007.88 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158248E+10 | 7988.24 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159056E+09 | 5131.76 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 62516826.94 | 4195.52 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4890883.91 | 4036.03 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9537198.67 | 4119.87 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316696E+09 | 4438.43 | 13-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123731E+10 | 7557.20 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.412133E+10 | 8007.74 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718442E+10 | 8008.94 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327642E+11 | |||||||
Minimum of Months | 4890883.91 | 4036.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871332E+10 | 8010.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100604E+11 | 8006.51 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718081E+10 | 8107.56 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382595E+10 | 8004.70 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178668E+10 | 7984.88 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189365E+09 | 5077.23 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67117231.45 | 4138.74 | 04-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5621541.27 | 4206.97 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13253097.55 | 3982.79 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388726E+09 | 4403.46 | 24-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167506E+10 | 7587.96 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.483613E+10 | 8004.33 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825936E+10 | 8005.57 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382885E+11 | |||||||
Minimum of Months | 5621541.27 | 3982.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100604E+11 | 8107.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216424E+11 | 14120.28 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165344E+11 | 14885.13 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101761E+11 | 8970.01 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.582011E+10 | 7552.18 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196128E+10 | 4529.01 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830599E+09 | 3770.00 | 06-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290930E+09 | 2420.88 | 12-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295571E+09 | 2553.95 | 26-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170483E+10 | 5654.62 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511870E+10 | 5861.99 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120122E+11 | 13815.17 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174225E+11 | 9841.86 | 12-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938097E+11 | |||||||
Minimum of Months | 0.290930E+09 | 2420.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216424E+11 | 14885.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288784E+10 | 2412.81 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195155E+10 | 2412.42 | 17-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118715E+10 | 2412.31 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541813E+09 | 2406.28 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78073129.47 | 2239.36 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30782608.11 | 1090.74 | 09-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1775254.09 | 989.60 | 13-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2621505.54 | 1014.76 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138758E+09 | 2286.09 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485560E+09 | 2327.23 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143105E+10 | 2412.16 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242586E+10 | 2412.56 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111628E+11 | |||||||
Minimum of Months | 1775254.09 | 989.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288784E+10 | 2412.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328118E+10 | 2405.26 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227398E+10 | 2413.75 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136867E+10 | 2404.75 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599450E+09 | 2398.75 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89409864.57 | 2239.28 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32469066.52 | 1026.42 | 09-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1824370.48 | 1038.11 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2904097.77 | 987.98 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168734E+09 | 2286.75 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.641345E+09 | 2335.96 | 23-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165600E+10 | 2404.59 | 21-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274857E+10 | 2405.02 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128645E+11 | |||||||
Minimum of Months | 1824370.48 | 987.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328118E+10 | 2413.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.966102E+10 | 10550.82 | 18-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605150E+10 | 10547.60 | 27-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359671E+10 | 10547.38 | 13-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181425E+10 | 10494.50 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160839E+09 | 3787.99 | 20-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51037288.08 | 5284.12 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4758727.89 | 3336.35 | 14-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11270414.45 | 3547.98 | 09-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264126E+09 | 6771.32 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.885019E+09 | 9876.71 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422273E+10 | 10547.65 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801624E+10 | 10549.05 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347395E+11 | |||||||
Minimum of Months | 4758727.89 | 3336.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.966102E+10 | 10550.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397759E+10 | 13036.80 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425945E+10 | 13728.31 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548454E+09 | 12760.30 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35775561.12 | 1403.28 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882127E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425945E+10 | 13728.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.399965E+10 | 13455.39 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425303E+10 | 14168.75 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544879E+09 | 13170.13 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51453.62 | 85.76 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879761E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425303E+10 | 14168.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248407E+10 | 9018.45 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270309E+10 | 9491.91 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352217E+09 | 8828.87 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1557588.28 | 449.59 | 10-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554094E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270309E+10 | 9491.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120362E+11 | 9034.59 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.862805E+10 | 9526.89 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437380E+10 | 5170.40 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194351E+10 | 3641.23 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120265E+09 | 1673.72 | 03-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21805569.62 | 699.24 | 03-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.335812E+09 | 2572.37 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148831E+10 | 2667.98 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537230E+10 | 8838.37 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891570E+10 | 6281.49 | 12-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432358E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120362E+11 | 9526.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275067E+12 | 314045.34 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179947E+12 | 328025.45 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667813E+11 | 121911.70 | 05-MAR-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343525E+11 | 90977.34 | 30-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289789E+11 | 94228.61 | 21-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166635E+11 | 92758.77 | 02-JUN-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319022E+10 | 70127.96 | 24-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.678868E+10 | 88156.68 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256933E+11 | 94807.41 | 27-SEP-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.332580E+11 | 99659.15 | 22-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.924650E+11 | 308338.09 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147399E+12 | 164485.12 | 08-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910585E+12 | |||||||
Minimum of Months | 0.319022E+10 | 70127.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275067E+12 | 328025.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161617E+11 | 31339.03 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109293E+11 | 32737.04 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230509E+10 | 6979.02 | 06-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434048E+09 | 3783.42 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5077.54 | 0.23 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6488.43 | 0.23 | 08-JUN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6698.88 | 0.23 | 24-JUL-23:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5952.29 | 0.23 | 28-AUG-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 290910.59 | 188.66 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21306894.53 | 1120.01 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379540E+10 | 30768.44 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686094E+10 | 11600.85 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405081E+11 | |||||||
Minimum of Months | 5077.54 | 0.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161617E+11 | 32737.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6039123.42 | 6039123.42 | 13419.14 | 12-JAN-16:02 | 13419.14 | 0.00 |
February | 0.00 | 0.00 | 0.108987E+09 | 0.108978E+09 | 13801.23 | 25-FEB-16:02 | 13801.23 | 0.00 |
March | 0.00 | 0.00 | 0.381113E+09 | 0.329342E+09 | 14227.66 | 25-MAR-15:01 | 14227.66 | 0.03 |
April | 0.00 | 0.00 | 0.204052E+10 | 0.146545E+10 | 16098.79 | 16-APR-08:61 | 12426.69 | 0.22 |
May | 0.00 | 0.00 | 0.335847E+10 | 0.196125E+10 | 17295.13 | 29-MAY-08:61 | 11997.58 | 0.57 |
June | 0.00 | 0.00 | 0.629637E+10 | 0.347675E+10 | 19674.16 | 26-JUN-08:62 | 11374.86 | 0.80 |
July | 0.00 | 0.00 | 0.807283E+10 | 0.434500E+10 | 18771.07 | 26-JUL-08:61 | 11470.84 | 0.92 |
August | 0.00 | 0.00 | 0.709407E+10 | 0.363737E+10 | 21261.24 | 03-AUG-08:62 | 10491.96 | 0.91 |
September | 0.00 | 0.00 | 0.419719E+10 | 0.253133E+10 | 17100.11 | 11-SEP-08:62 | 12094.09 | 0.59 |
October | 0.00 | 0.00 | 0.102319E+10 | 0.829814E+09 | 14857.50 | 02-OCT-15:01 | 12792.47 | 0.12 |
November | 0.00 | 0.00 | 0.195009E+09 | 0.150780E+09 | 13796.57 | 04-NOV-15:02 | 13796.57 | 0.04 |
December | 0.00 | 0.00 | 9289389.81 | 9289389.81 | 13298.00 | 02-DEC-16:02 | 13298.00 | 0.00 |
Annual Sum or Average | 0.327831E+11 | 0.188514E+11 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 6039123.42 | 6039123.42 | 13298.00 | 10491.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.807283E+10 | 0.434500E+10 | 21261.24 | 14227.66 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 332379.27 | 332379.27 | 1485.03 | 13-JAN-19:05 | 1485.03 | 0.00 |
February | 0.00 | 0.00 | 31810151.99 | 31810151.99 | 13318.06 | 24-FEB-16:02 | 13318.06 | 0.00 |
March | 0.00 | 0.00 | 0.170718E+09 | 0.143827E+09 | 14002.42 | 25-MAR-15:01 | 14002.42 | 0.02 |
April | 0.00 | 0.00 | 0.160388E+10 | 0.112566E+10 | 15847.92 | 16-APR-08:61 | 12379.16 | 0.19 |
May | 0.00 | 0.00 | 0.305707E+10 | 0.177808E+10 | 17013.37 | 29-MAY-08:61 | 11814.04 | 0.54 |
June | 0.00 | 0.00 | 0.609716E+10 | 0.335736E+10 | 19281.94 | 26-JUN-08:62 | 11246.69 | 0.79 |
July | 0.00 | 0.00 | 0.771925E+10 | 0.412579E+10 | 18502.47 | 26-JUL-08:61 | 11274.28 | 0.90 |
August | 0.00 | 0.00 | 0.644505E+10 | 0.324666E+10 | 20986.41 | 03-AUG-08:62 | 10290.27 | 0.88 |
September | 0.00 | 0.00 | 0.326552E+10 | 0.185561E+10 | 16543.70 | 11-SEP-08:62 | 12040.32 | 0.52 |
October | 0.00 | 0.00 | 0.478666E+09 | 0.374494E+09 | 14641.97 | 02-OCT-15:01 | 12579.15 | 0.07 |
November | 0.00 | 0.00 | 68912316.84 | 51377246.31 | 13577.50 | 04-NOV-15:02 | 13577.50 | 0.02 |
December | 0.00 | 0.00 | 670733.10 | 670733.10 | 1677.71 | 14-DEC-16:04 | 1677.71 | 0.00 |
Annual Sum or Average | 0.289390E+11 | 0.160917E+11 | 0.33 | |||||
Minimum of Months | 0.00 | 0.00 | 332379.27 | 332379.27 | 1485.03 | 1485.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.771925E+10 | 0.412579E+10 | 20986.41 | 14002.42 | 0.90 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 8947323.42 | 8947323.42 | 2828.49 | 25-FEB-14:50 | 2828.49 | 0.00 |
March | 0.00 | 0.00 | 0.376072E+10 | 0.372384E+10 | 34293.08 | 24-MAR-13:00 | 34293.08 | 0.00 |
April | 0.00 | 0.00 | 0.110324E+11 | 0.786447E+10 | 43765.64 | 15-APR-11:40 | 38186.85 | 0.19 |
May | 0.00 | 0.00 | 0.221370E+11 | 0.123920E+11 | 29648.08 | 05-MAY-13:10 | 20303.86 | 0.58 |
June | 0.00 | 0.00 | 0.332420E+11 | 0.159007E+11 | 31976.37 | 26-JUN-17:25 | 22390.86 | 0.90 |
July | 0.00 | 0.00 | 0.412739E+11 | 0.197328E+11 | 32686.45 | 30-JUL-12:50 | 22500.58 | 0.98 |
August | 0.00 | 0.00 | 0.425971E+11 | 0.219595E+11 | 40302.52 | 22-AUG-13:00 | 32274.41 | 0.99 |
September | 0.00 | 0.00 | 0.348011E+11 | 0.241141E+11 | 50275.40 | 07-SEP-12:50 | 40659.16 | 0.60 |
October | 0.00 | 0.00 | 0.201377E+11 | 0.185594E+11 | 55652.81 | 20-OCT-12:30 | 55652.81 | 0.12 |
November | 0.00 | 0.00 | 0.614180E+10 | 0.541935E+10 | 54381.75 | 04-NOV-12:30 | 54381.75 | 0.08 |
December | 0.00 | 0.00 | 98071742.71 | 98071742.71 | 10385.24 | 07-DEC-14:40 | 10385.24 | 0.00 |
Annual Sum or Average | 0.215231E+12 | 0.129773E+12 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.425971E+11 | 0.241141E+11 | 55652.81 | 55652.81 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 40840629.10 | 40840629.10 | 42440.57 | 01-JAN-09:02 | 42440.57 | 0.00 |
February | 0.00 | 0.00 | 0.259247E+09 | 0.259247E+09 | 65961.39 | 25-FEB-09:02 | 65961.39 | 0.00 |
March | 0.00 | 0.00 | 0.404430E+10 | 0.316342E+10 | 70124.96 | 25-MAR-15:01 | 70124.96 | 0.08 |
April | 0.00 | 0.00 | 0.145687E+11 | 0.105324E+11 | 88188.25 | 18-APR-15:02 | 70505.46 | 0.25 |
May | 0.00 | 0.00 | 0.351356E+11 | 0.229208E+11 | 88616.35 | 29-MAY-18:02 | 65072.16 | 0.59 |
June | 0.00 | 0.00 | 0.525444E+11 | 0.325444E+11 | 107398.57 | 26-JUN-08:62 | 57974.96 | 0.81 |
July | 0.00 | 0.00 | 0.615779E+11 | 0.358302E+11 | 103421.59 | 17-JUL-18:02 | 58933.98 | 0.82 |
August | 0.00 | 0.00 | 0.558122E+11 | 0.318369E+11 | 117838.49 | 03-AUG-08:62 | 52219.55 | 0.81 |
September | 0.00 | 0.00 | 0.319330E+11 | 0.207343E+11 | 86349.37 | 11-SEP-08:62 | 65213.37 | 0.60 |
October | 0.00 | 0.00 | 0.104905E+11 | 0.823330E+10 | 72455.28 | 02-OCT-15:01 | 66859.32 | 0.19 |
November | 0.00 | 0.00 | 0.438740E+10 | 0.269698E+10 | 68059.88 | 08-NOV-19:02 | 64884.52 | 0.14 |
December | 0.00 | 0.00 | 58764335.11 | 58764335.11 | 50104.19 | 03-DEC-09:02 | 50104.19 | 0.00 |
Annual Sum or Average | 0.270853E+12 | 0.168851E+12 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 40840629.10 | 40840629.10 | 42440.57 | 42440.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.615779E+11 | 0.358302E+11 | 117838.49 | 70505.46 | 0.82 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 916691.51 | 916691.51 | 2727.28 | 12-JAN-09:03 | 2727.28 | 0.00 |
February | 0.00 | 0.00 | 65540410.80 | 64329658.76 | 12041.41 | 24-FEB-09:02 | 12041.41 | 0.00 |
March | 0.00 | 0.00 | 0.336706E+09 | 0.278979E+09 | 12766.39 | 25-MAR-15:01 | 12766.39 | 0.04 |
April | 0.00 | 0.00 | 0.168187E+10 | 0.113583E+10 | 14052.57 | 18-APR-18:02 | 12056.58 | 0.23 |
May | 0.00 | 0.00 | 0.362527E+10 | 0.211776E+10 | 14528.87 | 26-MAY-15:01 | 11237.80 | 0.62 |
June | 0.00 | 0.00 | 0.640254E+10 | 0.356088E+10 | 16010.42 | 30-JUN-08:62 | 11089.24 | 0.84 |
July | 0.00 | 0.00 | 0.784651E+10 | 0.415865E+10 | 16567.40 | 20-JUL-08:62 | 9537.47 | 0.94 |
August | 0.00 | 0.00 | 0.682802E+10 | 0.345356E+10 | 18016.57 | 31-AUG-08:62 | 8791.16 | 0.93 |
September | 0.00 | 0.00 | 0.421888E+10 | 0.252594E+10 | 14770.72 | 10-SEP-08:62 | 11031.93 | 0.62 |
October | 0.00 | 0.00 | 0.841428E+09 | 0.670009E+09 | 13370.94 | 02-OCT-15:01 | 11429.97 | 0.11 |
November | 0.00 | 0.00 | 0.151227E+09 | 0.115144E+09 | 12379.81 | 04-NOV-15:02 | 12379.81 | 0.04 |
December | 0.00 | 0.00 | 13006131.32 | 13006131.32 | 10563.75 | 03-DEC-09:02 | 10563.75 | 0.00 |
Annual Sum or Average | 0.320119E+11 | 0.180950E+11 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 916691.51 | 916691.51 | 2727.28 | 2727.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.784651E+10 | 0.415865E+10 | 18016.57 | 12766.39 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 363592.90 | 363592.90 | 1507.79 | 13-JAN-09:05 | 1507.79 | 0.00 |
February | 0.00 | 0.00 | 12333277.70 | 12054835.08 | 11540.90 | 24-FEB-09:02 | 11540.90 | 0.00 |
March | 0.00 | 0.00 | 0.142067E+09 | 0.113709E+09 | 12158.98 | 28-MAR-08:62 | 12158.98 | 0.02 |
April | 0.00 | 0.00 | 0.127795E+10 | 0.834476E+09 | 14419.57 | 14-APR-15:01 | 11470.78 | 0.19 |
May | 0.00 | 0.00 | 0.329400E+10 | 0.190165E+10 | 14701.03 | 12-MAY-15:02 | 11414.61 | 0.59 |
June | 0.00 | 0.00 | 0.618958E+10 | 0.343042E+10 | 15905.75 | 30-JUN-08:62 | 11032.65 | 0.83 |
July | 0.00 | 0.00 | 0.748115E+10 | 0.392970E+10 | 16484.95 | 26-JUL-08:61 | 10405.55 | 0.94 |
August | 0.00 | 0.00 | 0.615236E+10 | 0.302798E+10 | 17913.54 | 31-AUG-08:62 | 8685.62 | 0.91 |
September | 0.00 | 0.00 | 0.323490E+10 | 0.180322E+10 | 14668.48 | 10-SEP-08:62 | 10978.14 | 0.56 |
October | 0.00 | 0.00 | 0.261501E+09 | 0.189886E+09 | 12933.09 | 02-OCT-15:01 | 10839.75 | 0.07 |
November | 0.00 | 0.00 | 21070945.45 | 17394456.03 | 9871.52 | 04-NOV-08:62 | 9871.52 | 0.01 |
December | 0.00 | 0.00 | 698973.81 | 698973.81 | 1742.19 | 05-DEC-09:03 | 1742.19 | 0.00 |
Annual Sum or Average | 0.280680E+11 | 0.152616E+11 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 363592.90 | 363592.90 | 1507.79 | 1507.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.748115E+10 | 0.392970E+10 | 17913.54 | 12158.98 | 0.94 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1151366.94 | 1151366.94 | 3453.10 | 12-JAN-16:02 | 3453.10 | 0.00 |
February | 0.00 | 0.00 | 27764811.87 | 27691145.28 | 3591.98 | 25-FEB-16:02 | 3591.98 | 0.00 |
March | 0.00 | 0.00 | 90484761.62 | 78565751.85 | 3702.93 | 25-MAR-15:01 | 3702.93 | 0.03 |
April | 0.00 | 0.00 | 0.571768E+09 | 0.424494E+09 | 4255.09 | 16-APR-08:61 | 3162.67 | 0.21 |
May | 0.00 | 0.00 | 0.979515E+09 | 0.600786E+09 | 4606.58 | 29-MAY-08:61 | 3059.23 | 0.57 |
June | 0.00 | 0.00 | 0.184810E+10 | 0.108024E+10 | 5192.72 | 26-JUN-08:62 | 2914.15 | 0.81 |
July | 0.00 | 0.00 | 0.235679E+10 | 0.133127E+10 | 4987.87 | 20-JUL-08:62 | 2658.22 | 0.93 |
August | 0.00 | 0.00 | 0.205352E+10 | 0.112192E+10 | 5628.39 | 03-AUG-08:62 | 2668.26 | 0.91 |
September | 0.00 | 0.00 | 0.118769E+10 | 0.763419E+09 | 4581.02 | 11-SEP-08:62 | 3069.78 | 0.57 |
October | 0.00 | 0.00 | 0.261401E+09 | 0.216055E+09 | 3883.95 | 02-OCT-15:01 | 3319.42 | 0.10 |
November | 0.00 | 0.00 | 48608481.50 | 39155748.12 | 3590.67 | 04-NOV-15:02 | 3590.67 | 0.02 |
December | 0.00 | 0.00 | 1751300.68 | 1751300.68 | 3407.23 | 02-DEC-16:02 | 3407.23 | 0.00 |
Annual Sum or Average | 0.942855E+10 | 0.568650E+10 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 1151366.94 | 1151366.94 | 3407.23 | 2658.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235679E+10 | 0.133127E+10 | 5628.39 | 3702.93 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 107888.74 | 107888.74 | 647.90 | 12-JAN-16:03 | 647.90 | 0.00 |
February | 0.00 | 0.00 | 5620621.86 | 5610596.93 | 3376.11 | 24-FEB-16:02 | 3376.11 | 0.00 |
March | 0.00 | 0.00 | 34775655.54 | 29002007.03 | 3641.73 | 25-MAR-15:01 | 3641.73 | 0.02 |
April | 0.00 | 0.00 | 0.448760E+09 | 0.324335E+09 | 4214.45 | 16-APR-08:61 | 3153.17 | 0.18 |
May | 0.00 | 0.00 | 0.892869E+09 | 0.545227E+09 | 4529.34 | 29-MAY-08:61 | 3010.58 | 0.54 |
June | 0.00 | 0.00 | 0.179417E+10 | 0.104691E+10 | 5092.85 | 26-JUN-08:62 | 2876.14 | 0.80 |
July | 0.00 | 0.00 | 0.226323E+10 | 0.127612E+10 | 4909.36 | 20-JUL-08:62 | 2599.51 | 0.92 |
August | 0.00 | 0.00 | 0.187682E+10 | 0.100513E+10 | 5550.96 | 03-AUG-08:62 | 2615.97 | 0.90 |
September | 0.00 | 0.00 | 0.933779E+09 | 0.567094E+09 | 4446.10 | 11-SEP-08:62 | 3053.33 | 0.51 |
October | 0.00 | 0.00 | 0.114710E+09 | 91139458.88 | 3835.87 | 02-OCT-15:01 | 3256.46 | 0.05 |
November | 0.00 | 0.00 | 16247986.23 | 12337692.73 | 3531.26 | 04-NOV-15:02 | 3531.26 | 0.01 |
December | 0.00 | 0.00 | 104463.92 | 104463.92 | 566.82 | 03-DEC-16:04 | 566.82 | 0.00 |
Annual Sum or Average | 0.838119E+10 | 0.490311E+10 | 0.33 | |||||
Minimum of Months | 0.00 | 0.00 | 104463.92 | 104463.92 | 566.82 | 566.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226323E+10 | 0.127612E+10 | 5550.96 | 3641.73 | 0.92 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.519304E+09 | 0.519304E+09 | 13916.80 | 13-JAN-16:02 | 13916.80 | 0.00 |
February | 0.00 | 0.00 | 0.876420E+09 | 0.872740E+09 | 13922.79 | 25-FEB-16:02 | 13922.79 | 0.00 |
March | 0.00 | 0.00 | 0.147101E+10 | 0.130214E+10 | 13997.93 | 23-MAR-15:01 | 13997.93 | 0.09 |
April | 0.00 | 0.00 | 0.318116E+10 | 0.234424E+10 | 16264.49 | 16-APR-08:61 | 12389.76 | 0.27 |
May | 0.00 | 0.00 | 0.518798E+10 | 0.303030E+10 | 17592.63 | 31-MAY-08:61 | 12518.41 | 0.66 |
June | 0.00 | 0.00 | 0.865024E+10 | 0.499808E+10 | 20756.03 | 26-JUN-08:62 | 10999.91 | 0.84 |
July | 0.00 | 0.00 | 0.110214E+11 | 0.617295E+10 | 19533.42 | 20-JUL-08:62 | 10243.53 | 0.92 |
August | 0.00 | 0.00 | 0.108900E+11 | 0.628328E+10 | 22355.80 | 03-AUG-08:62 | 10120.28 | 0.91 |
September | 0.00 | 0.00 | 0.783142E+10 | 0.554891E+10 | 17700.79 | 11-SEP-08:62 | 12137.21 | 0.67 |
October | 0.00 | 0.00 | 0.408528E+10 | 0.367167E+10 | 14631.33 | 02-OCT-15:01 | 13108.31 | 0.20 |
November | 0.00 | 0.00 | 0.143325E+10 | 0.120348E+10 | 13918.94 | 04-NOV-15:02 | 13918.94 | 0.13 |
December | 0.00 | 0.00 | 0.101796E+10 | 0.101796E+10 | 13921.05 | 02-DEC-16:02 | 13921.05 | 0.00 |
Annual Sum or Average | 0.561654E+11 | 0.369651E+11 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 0.519304E+09 | 0.519304E+09 | 13916.80 | 10120.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110214E+11 | 0.628328E+10 | 22355.80 | 13997.93 | 0.92 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.467832E+10 | 0.467832E+10 | 96124.08 | 19-MAR-16:00 | 96124.08 | 0.02 |
April | 0.00 | 0.00 | 0.589696E+11 | 0.453218E+11 | 289715.33 | 16-APR-20:20 | 174659.38 | 0.13 |
May | 0.00 | 0.00 | 0.147912E+12 | 0.109394E+12 | 304582.26 | 30-MAY-19:40 | 183621.72 | 0.44 |
June | 0.00 | 0.00 | 0.392250E+12 | 0.251160E+12 | 381276.28 | 11-JUN-15:10 | 217442.09 | 0.77 |
July | 0.00 | 0.00 | 0.570797E+12 | 0.322494E+12 | 530734.72 | 03-JUL-22:00 | 185604.83 | 0.95 |
August | 0.00 | 0.00 | 0.491530E+12 | 0.286296E+12 | 500969.37 | 04-AUG-06:00 | 162294.40 | 0.88 |
September | 0.00 | 0.00 | 0.189034E+12 | 0.159280E+12 | 321605.51 | 11-SEP-19:20 | 186989.29 | 0.47 |
October | 0.00 | 0.00 | 0.152949E+11 | 0.152949E+11 | 164183.07 | 20-OCT-15:10 | 164183.07 | 0.03 |
November | 0.00 | 0.00 | 0.164180E+10 | 0.164180E+10 | 43931.07 | 03-NOV-14:20 | 43931.07 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.187211E+13 | 0.119556E+13 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.570797E+12 | 0.322494E+12 | 530734.72 | 217442.09 | 0.95 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212705E+09 | 0.212705E+09 | 8513.24 | 19-MAR-16:00 | 8513.24 | 0.01 |
April | 0.00 | 0.00 | 0.324324E+10 | 0.256250E+10 | 26458.36 | 18-APR-12:20 | 17761.17 | 0.08 |
May | 0.00 | 0.00 | 0.734146E+10 | 0.558532E+10 | 29496.52 | 29-MAY-15:02 | 14681.04 | 0.28 |
June | 0.00 | 0.00 | 0.238603E+11 | 0.154869E+11 | 36954.70 | 26-JUN-08:62 | 17206.09 | 0.57 |
July | 0.00 | 0.00 | 0.356327E+11 | 0.203860E+11 | 38647.12 | 26-JUL-15:02 | 18987.01 | 0.72 |
August | 0.00 | 0.00 | 0.294316E+11 | 0.171496E+11 | 43840.91 | 04-AUG-08:61 | 17437.73 | 0.65 |
September | 0.00 | 0.00 | 0.107281E+11 | 0.923216E+10 | 28765.38 | 11-SEP-08:03 | 15197.73 | 0.34 |
October | 0.00 | 0.00 | 0.650479E+09 | 0.650479E+09 | 15520.21 | 20-OCT-15:02 | 15520.21 | 0.02 |
November | 0.00 | 0.00 | 24314290.39 | 24314290.39 | 2177.41 | 03-NOV-15:01 | 2177.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.111125E+12 | 0.712900E+11 | 0.23 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.356327E+11 | 0.203860E+11 | 43840.91 | 18987.01 | 0.72 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31415.63 | 64776.25 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 32045.08 | 65233.17 | 21-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31757.08 | 65131.71 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30551.20 | 63307.44 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28808.37 | 60316.16 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26878.70 | 56291.95 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25380.84 | 52728.58 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24656.41 | 50566.98 | 02-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24988.48 | 51711.21 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26240.45 | 55018.28 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28109.80 | 58907.50 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29977.20 | 62326.69 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 28379.24 | ||||
Minimum of Months | 0.00 | 0.00 | 24656.41 | 50566.98 | ||
Maximum of Months | 0.00 | 0.00 | 32045.08 | 65233.17 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 178284.93 | 581418.79 | 31-JAN-04:03 |
February | 0.01 | 17.39 | 24-FEB-14:55 | 136349.84 | 611095.51 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45388.75 | 225524.24 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23293.51 | 181430.83 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 13552.86 | 124667.47 | 01-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 8603.78 | 110544.36 | 02-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2832.42 | 73449.22 | 24-JUL-03:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3939.18 | 83568.28 | 06-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12506.13 | 132649.83 | 29-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 19043.32 | 148549.45 | 28-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 63918.22 | 557749.05 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 101966.53 | 300350.82 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 50363.54 | ||||
Minimum of Months | 0.00 | 0.00 | 2832.42 | 73449.22 | ||
Maximum of Months | 0.01 | 17.39 | 178284.93 | 611095.51 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 417.95 | 34189.89 | 01-JAN-09:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 986.61 | 41042.03 | 25-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 6728.54 | 247807.64 | 25-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 39705.72 | 486525.22 | 18-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 89519.62 | 499139.08 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 210732.37 | 603727.74 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 285102.25 | 728325.36 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 249462.10 | 668335.11 | 04-AUG-08:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 114943.14 | 506247.27 | 11-SEP-08:62 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21972.75 | 342808.81 | 20-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 6398.11 | 175244.30 | 03-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 758.66 | 37096.58 | 02-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 86174.86 | 0.00 | ||||
Minimum of Months | 417.95 | 34189.89 | 0.00 | 0.00 | ||
Maximum of Months | 285102.25 | 728325.36 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270916E+10 | 0.73 | 1298.89 | 01-JAN-01:30 | 0.92 |
February | 0.244698E+10 | 0.73 | 1298.89 | 01-FEB-00:01 | 0.93 |
March | 0.270916E+10 | 0.73 | 1298.89 | 01-MAR-02:30 | 0.92 |
April | 0.262177E+10 | 0.73 | 1298.89 | 01-APR-08:62 | 0.92 |
May | 0.270916E+10 | 0.72 | 1298.89 | 01-MAY-15:02 | 0.92 |
June | 0.262177E+10 | 0.72 | 1298.89 | 01-JUN-08:62 | 0.92 |
July | 0.270916E+10 | 0.72 | 1298.89 | 01-JUL-08:61 | 0.91 |
August | 0.270916E+10 | 0.72 | 1298.89 | 01-AUG-08:61 | 0.91 |
September | 0.262177E+10 | 0.72 | 1298.89 | 01-SEP-08:62 | 0.91 |
October | 0.270916E+10 | 0.73 | 1298.89 | 01-OCT-15:02 | 0.92 |
November | 0.262177E+10 | 0.73 | 1298.89 | 01-NOV-08:62 | 0.92 |
December | 0.270916E+10 | 0.73 | 1298.89 | 01-DEC-09:02 | 0.92 |
Annual Sum or Average | 0.318982E+11 | 0.73 | |||
Minimum of Months | 0.244698E+10 | 0.72 | 1298.89 | 0.91 | |
Maximum of Months | 0.270916E+10 | 0.73 | 1298.89 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357336E+11 | 0.90 | 20082.93 | 12-JAN-22:00 | 1.14 |
February | 0.329208E+11 | 0.91 | 20588.88 | 24-FEB-21:10 | 1.16 |
March | 0.380739E+11 | 0.93 | 21722.01 | 29-MAR-21:00 | 1.19 |
April | 0.372273E+11 | 0.93 | 23213.12 | 19-APR-21:00 | 1.25 |
May | 0.381022E+11 | 0.93 | 22490.67 | 22-MAY-20:50 | 1.22 |
June | 0.357366E+11 | 0.91 | 22395.87 | 01-JUN-21:00 | 1.21 |
July | 0.359387E+11 | 0.89 | 18652.51 | 10-JUL-21:00 | 1.08 |
August | 0.362911E+11 | 0.90 | 19810.59 | 06-AUG-21:00 | 1.13 |
September | 0.364869E+11 | 0.92 | 23850.67 | 25-SEP-21:00 | 1.26 |
October | 0.394588E+11 | 0.95 | 24841.11 | 30-OCT-21:00 | 1.30 |
November | 0.368174E+11 | 0.93 | 24470.47 | 03-NOV-20:10 | 1.29 |
December | 0.367139E+11 | 0.91 | 20878.21 | 04-DEC-22:00 | 1.17 |
Annual Sum or Average | 0.439501E+12 | 0.92 | |||
Minimum of Months | 0.329208E+11 | 0.89 | 18652.51 | 1.08 | |
Maximum of Months | 0.394588E+11 | 0.95 | 24841.11 | 1.30 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:03 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:10 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:05 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:03 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:05 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.683044E+09 | 0.53 | 811.90 | 01-JAN-09:02 | 0.60 |
February | 0.497610E+09 | 0.50 | 811.90 | 01-FEB-04:00 | 0.61 |
March | 0.282662E+09 | 0.46 | 811.90 | 01-MAR-09:02 | 0.60 |
April | 0.252535E+09 | 0.47 | 811.90 | 01-APR-08:62 | 0.60 |
May | 0.220674E+09 | 0.48 | 811.90 | 01-MAY-15:02 | 0.60 |
June | 0.325825E+09 | 0.52 | 811.90 | 01-JUN-08:62 | 0.60 |
July | 0.388132E+09 | 0.55 | 811.90 | 01-JUL-08:61 | 0.60 |
August | 0.349516E+09 | 0.55 | 811.90 | 01-AUG-08:61 | 0.60 |
September | 0.267513E+09 | 0.51 | 811.90 | 01-SEP-15:02 | 0.60 |
October | 0.195793E+09 | 0.46 | 811.90 | 01-OCT-15:02 | 0.60 |
November | 0.329342E+09 | 0.47 | 811.90 | 03-NOV-15:01 | 0.60 |
December | 0.512574E+09 | 0.51 | 811.90 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.430522E+10 | 0.50 | |||
Minimum of Months | 0.195793E+09 | 0.46 | 811.90 | 0.60 | |
Maximum of Months | 0.683044E+09 | 0.55 | 811.90 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.791580E+09 | 0.57 | 798.81 | 01-JAN-09:02 | 0.60 |
February | 0.558632E+09 | 0.52 | 798.81 | 01-FEB-02:00 | 0.61 |
March | 0.300567E+09 | 0.46 | 798.81 | 01-MAR-09:02 | 0.60 |
April | 0.237481E+09 | 0.46 | 798.81 | 01-APR-08:62 | 0.60 |
May | 0.204887E+09 | 0.47 | 798.81 | 01-MAY-15:02 | 0.60 |
June | 0.316659E+09 | 0.52 | 798.81 | 01-JUN-08:62 | 0.60 |
July | 0.371698E+09 | 0.54 | 798.81 | 01-JUL-08:61 | 0.60 |
August | 0.317657E+09 | 0.53 | 798.81 | 01-AUG-08:61 | 0.60 |
September | 0.227123E+09 | 0.48 | 798.81 | 01-SEP-15:02 | 0.60 |
October | 0.195014E+09 | 0.43 | 798.81 | 01-OCT-15:02 | 0.60 |
November | 0.370780E+09 | 0.48 | 798.81 | 01-NOV-08:62 | 0.60 |
December | 0.568583E+09 | 0.55 | 798.81 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.446066E+10 | 0.50 | |||
Minimum of Months | 0.195014E+09 | 0.43 | 798.81 | 0.60 | |
Maximum of Months | 0.791580E+09 | 0.57 | 798.81 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.398311E+09 | 0.16 | 1021.20 | 19-JAN-06:00 | 0.61 |
February | 95480663.58 | 0.04 | 976.66 | 04-FEB-06:00 | 0.61 |
March | 0.184330E+09 | 0.09 | 1274.87 | 24-MAR-13:00 | 0.60 |
April | 0.483824E+09 | 0.21 | 1941.53 | 15-APR-12:40 | 0.60 |
May | 0.994481E+09 | 0.47 | 1063.42 | 06-MAY-12:50 | 0.60 |
June | 0.130717E+10 | 0.54 | 1042.93 | 26-JUN-17:30 | 0.60 |
July | 0.155117E+10 | 0.59 | 1049.48 | 30-JUL-13:00 | 0.60 |
August | 0.161932E+10 | 0.59 | 1338.70 | 29-AUG-13:15 | 0.60 |
September | 0.144521E+10 | 0.49 | 2187.29 | 07-SEP-12:50 | 0.60 |
October | 0.929486E+09 | 0.34 | 2341.57 | 20-OCT-12:30 | 0.60 |
November | 0.301507E+09 | 0.13 | 2382.00 | 04-NOV-12:30 | 0.60 |
December | 0.194445E+09 | 0.09 | 874.86 | 13-DEC-04:05 | 0.61 |
Annual Sum or Average | 0.950473E+10 | 0.31 | |||
Minimum of Months | 95480663.58 | 0.04 | 874.86 | 0.60 | |
Maximum of Months | 0.161932E+10 | 0.59 | 2382.00 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.319320E+10 | 0.47 | 4175.53 | 01-JAN-16:02 | 0.60 |
February | 0.233304E+10 | 0.46 | 4175.53 | 01-FEB-00:01 | 0.61 |
March | 0.110253E+10 | 0.43 | 4175.53 | 01-MAR-09:02 | 0.60 |
April | 0.112793E+10 | 0.43 | 4175.53 | 01-APR-08:62 | 0.60 |
May | 0.187473E+10 | 0.45 | 4175.53 | 01-MAY-08:62 | 0.60 |
June | 0.256670E+10 | 0.49 | 4175.53 | 01-JUN-08:62 | 0.60 |
July | 0.284096E+10 | 0.49 | 4175.53 | 01-JUL-08:61 | 0.60 |
August | 0.259764E+10 | 0.49 | 4175.53 | 01-AUG-08:61 | 0.60 |
September | 0.172429E+10 | 0.45 | 4175.53 | 01-SEP-08:62 | 0.60 |
October | 0.889562E+09 | 0.43 | 4175.53 | 01-OCT-08:62 | 0.60 |
November | 0.137373E+10 | 0.43 | 4175.53 | 01-NOV-08:62 | 0.60 |
December | 0.210588E+10 | 0.44 | 4175.53 | 01-DEC-16:02 | 0.60 |
Annual Sum or Average | 0.237302E+11 | 0.45 | |||
Minimum of Months | 0.889562E+09 | 0.43 | 4175.53 | 0.60 | |
Maximum of Months | 0.319320E+10 | 0.49 | 4175.53 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.656906E+09 | 0.54 | 726.47 | 01-JAN-09:02 | 0.60 |
February | 0.465671E+09 | 0.49 | 726.47 | 01-FEB-02:15 | 0.61 |
March | 0.257034E+09 | 0.46 | 726.47 | 01-MAR-09:02 | 0.60 |
April | 0.225071E+09 | 0.48 | 726.47 | 01-APR-08:62 | 0.60 |
May | 0.227065E+09 | 0.51 | 726.47 | 01-MAY-08:62 | 0.60 |
June | 0.320707E+09 | 0.54 | 726.47 | 01-JUN-08:62 | 0.60 |
July | 0.367516E+09 | 0.57 | 726.47 | 01-JUL-08:61 | 0.60 |
August | 0.324132E+09 | 0.56 | 726.47 | 01-AUG-08:61 | 0.60 |
September | 0.259455E+09 | 0.53 | 726.47 | 01-SEP-08:62 | 0.60 |
October | 0.175458E+09 | 0.46 | 726.47 | 01-OCT-08:62 | 0.60 |
November | 0.313307E+09 | 0.47 | 726.47 | 03-NOV-15:01 | 0.60 |
December | 0.481318E+09 | 0.51 | 726.47 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.407364E+10 | 0.51 | |||
Minimum of Months | 0.175458E+09 | 0.46 | 726.47 | 0.60 | |
Maximum of Months | 0.656906E+09 | 0.57 | 726.47 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.755885E+09 | 0.57 | 722.14 | 01-JAN-09:02 | 0.60 |
February | 0.539848E+09 | 0.52 | 722.14 | 01-FEB-00:12 | 0.61 |
March | 0.278324E+09 | 0.45 | 722.14 | 01-MAR-09:02 | 0.60 |
April | 0.216160E+09 | 0.46 | 722.14 | 01-APR-08:62 | 0.60 |
May | 0.211713E+09 | 0.50 | 722.14 | 01-MAY-08:62 | 0.60 |
June | 0.311846E+09 | 0.54 | 722.14 | 01-JUN-08:62 | 0.60 |
July | 0.351002E+09 | 0.56 | 722.14 | 01-JUL-08:61 | 0.60 |
August | 0.293719E+09 | 0.55 | 722.14 | 01-AUG-08:61 | 0.60 |
September | 0.216399E+09 | 0.50 | 722.14 | 01-SEP-08:62 | 0.60 |
October | 0.170947E+09 | 0.43 | 722.14 | 01-OCT-08:62 | 0.60 |
November | 0.351910E+09 | 0.48 | 722.14 | 09-NOV-16:02 | 0.60 |
December | 0.543870E+09 | 0.56 | 722.14 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.424162E+10 | 0.51 | |||
Minimum of Months | 0.170947E+09 | 0.43 | 722.14 | 0.60 | |
Maximum of Months | 0.755885E+09 | 0.57 | 722.14 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210812E+09 | 0.56 | 211.47 | 01-JAN-09:02 | 0.60 |
February | 0.143579E+09 | 0.52 | 211.47 | 01-FEB-03:40 | 0.61 |
March | 85615767.44 | 0.47 | 211.47 | 01-MAR-09:02 | 0.60 |
April | 75333002.01 | 0.48 | 211.47 | 01-APR-08:62 | 0.60 |
May | 64897176.44 | 0.50 | 211.47 | 01-MAY-15:02 | 0.60 |
June | 97126590.02 | 0.54 | 211.47 | 01-JUN-08:62 | 0.60 |
July | 0.115985E+09 | 0.56 | 211.47 | 01-JUL-08:61 | 0.60 |
August | 0.101656E+09 | 0.55 | 211.47 | 01-AUG-08:61 | 0.59 |
September | 77946499.65 | 0.52 | 211.47 | 01-SEP-15:02 | 0.60 |
October | 59251961.99 | 0.45 | 211.47 | 01-OCT-15:02 | 0.60 |
November | 0.105146E+09 | 0.49 | 211.47 | 03-NOV-15:01 | 0.60 |
December | 0.156775E+09 | 0.53 | 211.47 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.129412E+10 | 0.51 | |||
Minimum of Months | 59251961.99 | 0.45 | 211.47 | 0.59 | |
Maximum of Months | 0.210812E+09 | 0.56 | 211.47 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238186E+09 | 0.59 | 207.95 | 01-JAN-09:02 | 0.60 |
February | 0.161561E+09 | 0.55 | 207.95 | 01-FEB-01:15 | 0.61 |
March | 92728747.59 | 0.49 | 207.95 | 01-MAR-09:02 | 0.60 |
April | 71060616.66 | 0.47 | 207.95 | 01-APR-08:62 | 0.60 |
May | 60609914.25 | 0.49 | 207.95 | 01-MAY-15:02 | 0.60 |
June | 94592356.34 | 0.53 | 207.95 | 01-JUN-08:62 | 0.60 |
July | 0.111019E+09 | 0.56 | 207.95 | 01-JUL-08:61 | 0.60 |
August | 92859931.74 | 0.55 | 207.95 | 01-AUG-08:61 | 0.59 |
September | 66589624.19 | 0.50 | 207.95 | 01-SEP-15:02 | 0.60 |
October | 59482009.45 | 0.43 | 207.95 | 01-OCT-15:02 | 0.60 |
November | 0.115935E+09 | 0.51 | 207.95 | 01-NOV-08:62 | 0.60 |
December | 0.178516E+09 | 0.58 | 207.95 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.134314E+10 | 0.52 | |||
Minimum of Months | 59482009.45 | 0.43 | 207.95 | 0.59 | |
Maximum of Months | 0.238186E+09 | 0.59 | 207.95 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.658115E+09 | 0.50 | 809.46 | 01-JAN-09:02 | 0.60 |
February | 0.452962E+09 | 0.48 | 809.46 | 01-FEB-04:50 | 0.61 |
March | 0.312150E+09 | 0.49 | 809.46 | 01-MAR-09:02 | 0.60 |
April | 0.305614E+09 | 0.49 | 809.46 | 01-APR-15:02 | 0.60 |
May | 0.293526E+09 | 0.51 | 809.46 | 01-MAY-08:62 | 0.60 |
June | 0.415960E+09 | 0.53 | 809.46 | 01-JUN-08:62 | 0.60 |
July | 0.502546E+09 | 0.55 | 809.46 | 01-JUL-08:61 | 0.60 |
August | 0.501555E+09 | 0.55 | 809.46 | 01-AUG-08:61 | 0.59 |
September | 0.438631E+09 | 0.53 | 809.46 | 01-SEP-08:62 | 0.60 |
October | 0.322308E+09 | 0.50 | 809.46 | 01-OCT-08:62 | 0.60 |
November | 0.363172E+09 | 0.48 | 809.46 | 01-NOV-15:02 | 0.60 |
December | 0.545508E+09 | 0.52 | 809.46 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.511205E+10 | 0.51 | |||
Minimum of Months | 0.293526E+09 | 0.48 | 809.46 | 0.59 | |
Maximum of Months | 0.658115E+09 | 0.55 | 809.46 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.131331E+10 | 0.118198E+10 | 3458.68 | 19-JAN-06:00 | 3112.81 | 3112.81 | 49.84 | 13.49 |
February | 0.108015E+10 | 0.972133E+09 | 3436.89 | 04-FEB-06:00 | 3093.20 | 3093.20 | 49.57 | 13.46 |
March | 65731522.25 | 59158370.02 | 255.36 | 05-MAR-24:00 | 229.83 | 229.83 | 50.18 | 4.50 |
April | 22431541.22 | 20188387.10 | 124.42 | 03-APR-08:62 | 111.98 | 111.98 | 46.40 | 3.22 |
May | 8109535.93 | 7298582.34 | 75.92 | 03-MAY-08:05 | 68.33 | 68.33 | 46.53 | 2.53 |
June | 4673864.84 | 4206478.36 | 66.34 | 03-JUN-08:03 | 59.71 | 59.71 | 49.22 | 2.36 |
July | 1022055.26 | 919849.73 | 20.88 | 24-JUL-04:00 | 18.79 | 18.79 | 43.57 | 1.27 |
August | 1638268.43 | 1474441.59 | 34.49 | 07-AUG-06:10 | 31.05 | 31.05 | 47.73 | 1.68 |
September | 8544314.78 | 7689883.30 | 74.97 | 29-SEP-15:05 | 67.48 | 67.48 | 44.60 | 2.51 |
October | 17516546.98 | 15764892.28 | 94.33 | 28-OCT-15:03 | 84.89 | 84.89 | 44.73 | 2.82 |
November | 0.227722E+09 | 0.204950E+09 | 2995.39 | 26-NOV-07:00 | 2695.85 | 2695.85 | 49.53 | 12.75 |
December | 0.275712E+09 | 0.248141E+09 | 713.66 | 09-DEC-09:04 | 642.30 | 642.30 | 49.95 | 7.08 |
Annual Sum or Average | 0.302656E+10 | 0.272390E+10 | ||||||
Minimum of Months | 1022055.26 | 919849.73 | 20.88 | 18.79 | 18.79 | 43.57 | 1.27 | |
Maximum of Months | 0.131331E+10 | 0.118198E+10 | 3458.68 | 3112.81 | 3112.81 | 50.18 | 13.49 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 315714.18 | 284142.76 | 26.23 | 16-JAN-09:02 | 23.61 | 23.61 | 8.39 | 2.23 |
February | 930675.66 | 837608.10 | 51.64 | 25-FEB-16:02 | 46.48 | 46.48 | 8.39 | 3.33 |
March | 15952987.42 | 14357688.68 | 369.64 | 25-MAR-15:01 | 332.68 | 332.68 | 7.90 | 9.19 |
April | 0.169793E+09 | 0.152813E+09 | 1195.77 | 16-APR-20:30 | 1076.19 | 1076.19 | 7.31 | 15.66 |
May | 0.371085E+09 | 0.333976E+09 | 1239.40 | 29-MAY-18:02 | 1115.46 | 1115.46 | 7.48 | 15.90 |
June | 0.107743E+10 | 0.969684E+09 | 1550.68 | 26-JUN-18:02 | 1395.61 | 1395.61 | 6.72 | 17.52 |
July | 0.159529E+10 | 0.143576E+10 | 2365.03 | 03-JUL-22:00 | 2128.52 | 2128.52 | 7.22 | 20.94 |
August | 0.134061E+10 | 0.120655E+10 | 2271.62 | 28-AUG-19:20 | 2044.45 | 2044.45 | 7.22 | 20.59 |
September | 0.509935E+09 | 0.458941E+09 | 1271.64 | 11-SEP-08:62 | 1144.48 | 1144.48 | 7.38 | 16.08 |
October | 59540318.56 | 53586286.70 | 752.49 | 11-OCT-15:01 | 677.25 | 677.25 | 7.90 | 12.76 |
November | 13550512.47 | 12195461.22 | 286.07 | 03-NOV-15:01 | 257.47 | 257.47 | 8.32 | 8.13 |
December | 640806.61 | 576725.95 | 42.53 | 02-DEC-09:02 | 38.28 | 38.28 | 8.39 | 2.98 |
Annual Sum or Average | 0.515507E+10 | 0.463956E+10 | ||||||
Minimum of Months | 315714.18 | 284142.76 | 26.23 | 23.61 | 23.61 | 6.72 | 2.23 | |
Maximum of Months | 0.159529E+10 | 0.143576E+10 | 2365.03 | 2128.52 | 2128.52 | 8.39 | 20.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 46.84 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 46.30 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.33 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.12 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 50.00 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 50.91 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.93 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 51.68 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 51.99 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.67 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.94 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.35 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.30 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.99 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.607768E+09 | 0.546992E+09 | 2796.27 | 01-JAN-09:02 | 2516.64 | 2516.64 | 8.60 | 35.02 |
February | 0.109437E+10 | 0.984937E+09 | 2796.27 | 01-FEB-16:02 | 2516.64 | 2516.64 | 8.42 | 35.02 |
March | 0.298406E+10 | 0.268566E+10 | 2796.27 | 01-MAR-09:05 | 2516.64 | 2516.64 | 8.41 | 35.02 |
April | 0.466462E+10 | 0.419816E+10 | 2796.27 | 01-APR-08:62 | 2516.64 | 2516.64 | 8.53 | 35.02 |
May | 0.736117E+10 | 0.662505E+10 | 2796.27 | 01-MAY-00:03 | 2516.64 | 2516.64 | 8.44 | 35.02 |
June | 0.718333E+10 | 0.646500E+10 | 2796.27 | 01-JUN-00:10 | 2516.64 | 2516.64 | 8.75 | 35.02 |
July | 0.748952E+10 | 0.674057E+10 | 2796.27 | 01-JUL-00:10 | 2516.64 | 2516.64 | 9.22 | 35.02 |
August | 0.748952E+10 | 0.674057E+10 | 2796.27 | 01-AUG-00:10 | 2516.64 | 2516.64 | 9.83 | 35.02 |
September | 0.693977E+10 | 0.624580E+10 | 2796.27 | 01-SEP-00:10 | 2516.64 | 2516.64 | 9.26 | 35.02 |
October | 0.574462E+10 | 0.517016E+10 | 2796.27 | 01-OCT-00:05 | 2516.64 | 2516.64 | 8.39 | 35.02 |
November | 0.271615E+10 | 0.244454E+10 | 2796.27 | 01-NOV-05:03 | 2516.64 | 2516.64 | 8.41 | 35.02 |
December | 0.928033E+09 | 0.835230E+09 | 2796.27 | 01-DEC-09:03 | 2516.64 | 2516.64 | 8.46 | 35.02 |
Annual Sum or Average | 0.552029E+11 | 0.496826E+11 | ||||||
Minimum of Months | 0.607768E+09 | 0.546992E+09 | 2796.27 | 2516.64 | 2516.64 | 8.39 | 35.02 | |
Maximum of Months | 0.748952E+10 | 0.674057E+10 | 2796.27 | 2516.64 | 2516.64 | 9.83 | 35.02 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.84 | 59.87 | 31415.63 | 64776.25 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.30 | 58.87 | 32045.08 | 65233.17 | 21-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.33 | 59.50 | 31757.08 | 65131.71 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.12 | 59.93 | 30551.20 | 63307.44 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 50.00 | 59.93 | 28808.37 | 60316.16 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 50.91 | 58.24 | 26878.70 | 56291.95 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.93 | 58.89 | 25380.84 | 52728.58 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 51.68 | 58.23 | 24656.41 | 50566.98 | 02-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 51.99 | 58.55 | 24988.48 | 51711.21 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.67 | 59.46 | 26240.45 | 55018.28 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.94 | 59.89 | 28109.80 | 58907.50 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.35 | 59.88 | 29977.20 | 62326.69 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 28379.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.30 | 58.23 | 24656.41 | 50566.98 | ||
Maximum of Months | 0.00 | 0.00 | 51.99 | 59.93 | 32045.08 | 65233.17 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 51.00 | 59.36 | 178284.93 | 581418.79 | 31-JAN-04:03 |
February | 0.01 | 17.39 | 24-FEB-14:55 | 57.52 | 57.52 | 136349.84 | 611095.51 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.27 | 60.00 | 45388.75 | 225524.24 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.71 | 59.09 | 23293.51 | 181430.83 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 47.23 | 57.52 | 13552.86 | 124667.47 | 01-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 46.70 | 57.22 | 8603.78 | 110544.36 | 02-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.39 | 57.22 | 2832.42 | 73449.22 | 24-JUL-03:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 40.82 | 57.22 | 3939.18 | 83568.28 | 06-AUG-23:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.71 | 57.22 | 12506.13 | 132649.83 | 29-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 52.94 | 58.24 | 19043.32 | 148549.45 | 28-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.20 | 58.61 | 63918.22 | 557749.05 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.41 | 59.01 | 101966.53 | 300350.82 | 09-DEC-09:06 |
Annual Sum or Average | 0.00 | 50363.54 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.71 | 57.22 | 2832.42 | 73449.22 | ||
Maximum of Months | 0.01 | 17.39 | 57.52 | 60.00 | 178284.93 | 611095.51 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 417.95 | 34189.89 | 01-JAN-09:02 | 8.60 | 8.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 986.61 | 41042.03 | 25-FEB-16:02 | 8.65 | 8.37 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 6728.54 | 247807.64 | 25-MAR-15:01 | 9.59 | 7.90 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 39705.72 | 486525.22 | 18-APR-15:03 | 10.01 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 89519.62 | 499139.08 | 30-MAY-18:03 | 10.30 | 6.90 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 210732.37 | 603727.74 | 11-JUN-15:03 | 10.81 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 285102.25 | 728325.36 | 26-JUL-18:03 | 11.66 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 249462.10 | 668335.11 | 04-AUG-08:03 | 11.39 | 6.84 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 114943.14 | 506247.27 | 11-SEP-08:62 | 10.78 | 7.33 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21972.75 | 342808.81 | 20-OCT-15:02 | 9.60 | 7.26 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 6398.11 | 175244.30 | 03-NOV-15:03 | 9.52 | 8.32 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 758.66 | 37096.58 | 02-DEC-09:02 | 8.62 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 86174.86 | 0.00 | ||||||
Minimum of Months | 417.95 | 34189.89 | 8.60 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 285102.25 | 728325.36 | 11.66 | 8.37 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 3.76 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 3.76 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 3.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 1.68 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.03 | 4.20 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.11 | 2.31 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 4.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 56.92 |
February | 0.25 | 56.92 |
March | 0.00 | 0.00 |
April | 0.08 | 56.92 |
May | 0.00 | 0.00 |
June | 0.50 | 56.92 |
July | 0.92 | 56.92 |
August | 0.58 | 56.92 |
September | 0.17 | 56.92 |
October | 0.00 | 0.00 |
November | 0.08 | 99.61 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 58.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.92 | 99.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 108.81 |
February | 0.14 | 126.73 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.06 | 211.22 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.65 | 121.34 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.46 | 211.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.64 | 0.63 |
February | 2.79 | 0.68 |
March | 1.72 | 0.70 |
April | 1.26 | 0.71 |
May | 1.53 | 0.61 |
June | 3.07 | 0.54 |
July | 3.32 | 0.53 |
August | 3.25 | 0.49 |
September | 1.86 | 0.46 |
October | 0.65 | 0.81 |
November | 1.92 | 0.59 |
December | 5.40 | 0.67 |
Annual Sum or Average | 31.42 | 0.61 |
Minimum of Months | 0.65 | 0.46 |
Maximum of Months | 5.40 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.39 | 0.63 |
February | 2.40 | 0.68 |
March | 2.17 | 0.70 |
April | 1.88 | 0.74 |
May | 1.18 | 0.66 |
June | 3.14 | 0.55 |
July | 3.44 | 0.56 |
August | 2.83 | 0.52 |
September | 1.21 | 0.52 |
October | 0.49 | 0.81 |
November | 1.96 | 0.55 |
December | 5.35 | 0.64 |
Annual Sum or Average | 29.43 | 0.61 |
Minimum of Months | 0.49 | 0.52 |
Maximum of Months | 5.35 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.08 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.72 | 0.66 |
February | 0.36 | 0.61 |
March | 0.22 | 0.81 |
April | 0.89 | 0.75 |
May | 2.54 | 0.73 |
June | 4.69 | 0.68 |
July | 3.83 | 0.72 |
August | 3.85 | 0.72 |
September | 2.51 | 0.70 |
October | 0.39 | 0.81 |
November | 0.64 | 0.61 |
December | 1.07 | 0.59 |
Annual Sum or Average | 24.72 | 0.69 |
Minimum of Months | 0.22 | 0.59 |
Maximum of Months | 4.69 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.40 | 0.64 |
February | 2.32 | 0.71 |
March | 1.50 | 0.68 |
April | 1.15 | 0.66 |
May | 2.86 | 0.62 |
June | 2.04 | 0.62 |
July | 2.04 | 0.70 |
August | 2.47 | 0.70 |
September | 1.67 | 0.67 |
October | 0.81 | 0.38 |
November | 2.01 | 0.61 |
December | 5.62 | 0.67 |
Annual Sum or Average | 28.90 | 0.65 |
Minimum of Months | 0.81 | 0.38 |
Maximum of Months | 5.62 | 0.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.17 | 0.61 |
February | 2.72 | 0.63 |
March | 1.71 | 0.70 |
April | 1.46 | 0.63 |
May | 2.72 | 0.56 |
June | 2.68 | 0.63 |
July | 2.26 | 0.68 |
August | 3.44 | 0.68 |
September | 2.31 | 0.59 |
October | 0.00 | 0.00 |
November | 2.13 | 0.57 |
December | 5.79 | 0.63 |
Annual Sum or Average | 31.39 | 0.63 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.79 | 0.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.75 | 0.59 |
February | 1.94 | 0.66 |
March | 1.51 | 0.74 |
April | 1.12 | 0.70 |
May | 2.08 | 0.53 |
June | 3.25 | 0.51 |
July | 3.58 | 0.50 |
August | 3.19 | 0.48 |
September | 1.53 | 0.47 |
October | 0.74 | 0.81 |
November | 1.50 | 0.55 |
December | 3.17 | 0.67 |
Annual Sum or Average | 26.38 | 0.57 |
Minimum of Months | 0.74 | 0.47 |
Maximum of Months | 3.58 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.46 | 0.65 |
February | 1.22 | 0.59 |
March | 1.54 | 0.72 |
April | 1.62 | 0.73 |
May | 1.71 | 0.56 |
June | 3.54 | 0.51 |
July | 3.86 | 0.51 |
August | 3.25 | 0.48 |
September | 1.44 | 0.46 |
October | 1.12 | 0.71 |
November | 1.46 | 0.54 |
December | 2.14 | 0.65 |
Annual Sum or Average | 24.37 | 0.57 |
Minimum of Months | 1.12 | 0.46 |
Maximum of Months | 3.86 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.58 | 0.61 |
February | 2.22 | 0.69 |
March | 1.60 | 0.69 |
April | 1.38 | 0.71 |
May | 3.07 | 0.60 |
June | 4.04 | 0.56 |
July | 3.85 | 0.54 |
August | 3.64 | 0.50 |
September | 1.67 | 0.63 |
October | 1.50 | 0.65 |
November | 1.29 | 0.58 |
December | 3.31 | 0.58 |
Annual Sum or Average | 30.14 | 0.59 |
Minimum of Months | 1.29 | 0.50 |
Maximum of Months | 4.04 | 0.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.83 | 150.11 |
February | 0.25 | 99.96 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 99.96 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.08 | 224.91 |
December | 0.08 | 224.91 |
Annual Sum or Average | 1.33 | 146.91 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.83 | 224.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.48 | 105.77 |
February | 0.25 | 99.96 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.73 | 103.77 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.48 | 105.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 14.45 |
February | 0.33 | 8.34 |
March | 0.00 | 0.00 |
April | 0.17 | 12.23 |
May | 0.17 | 20.01 |
June | 0.08 | 20.01 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.17 | 20.01 |
October | 0.08 | 20.01 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.39 | 14.72 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.39 | 20.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.362308E+12 | 0.00 | 0.00 | 0.357336E+11 | 0.00 | 0.00 |
February | 0.253619E+12 | 0.00 | 0.00 | 0.329208E+11 | 0.00 | 0.00 |
March | 0.887356E+11 | 0.00 | 0.467832E+10 | 0.380739E+11 | 0.00 | 0.00 |
April | 0.478903E+11 | 0.00 | 0.589696E+11 | 0.372273E+11 | 0.00 | 0.00 |
May | 0.351568E+11 | 0.00 | 0.147912E+12 | 0.381022E+11 | 0.00 | 0.00 |
June | 0.219158E+11 | 0.00 | 0.392250E+12 | 0.357366E+11 | 0.00 | 0.00 |
July | 0.754434E+10 | 0.00 | 0.570797E+12 | 0.359387E+11 | 0.00 | 0.00 |
August | 0.104866E+11 | 0.00 | 0.491530E+12 | 0.362911E+11 | 0.00 | 0.00 |
September | 0.301472E+11 | 0.00 | 0.189034E+12 | 0.364869E+11 | 0.00 | 0.00 |
October | 0.416655E+11 | 0.00 | 0.152949E+11 | 0.394588E+11 | 0.00 | 0.00 |
November | 0.123041E+12 | 0.00 | 0.164180E+10 | 0.368174E+11 | 0.00 | 0.00 |
December | 0.191155E+12 | 0.00 | 0.00 | 0.367139E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.121366E+13 | 0.00 | 0.187211E+13 | 0.439501E+12 | 0.00 | 0.00 |
Minimum of Months | 0.754434E+10 | 0.00 | 0.00 | 0.329208E+11 | 0.00 | 0.00 |
Maximum of Months | 0.362308E+12 | 0.00 | 0.570797E+12 | 0.394588E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161617E+11 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
February | 0.109293E+11 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
March | 0.230509E+10 | 0.00 | 0.212705E+09 | 0.270916E+10 | 0.00 | 0.00 |
April | 0.434048E+09 | 0.00 | 0.324324E+10 | 0.262177E+10 | 0.00 | 0.00 |
May | 5077.54 | 0.00 | 0.734146E+10 | 0.270916E+10 | 0.00 | 0.00 |
June | 6488.43 | 0.00 | 0.238603E+11 | 0.262177E+10 | 0.00 | 0.00 |
July | 6698.88 | 0.00 | 0.356327E+11 | 0.270916E+10 | 0.00 | 0.00 |
August | 5952.29 | 0.00 | 0.294316E+11 | 0.270916E+10 | 0.00 | 0.00 |
September | 290910.59 | 0.00 | 0.107281E+11 | 0.262177E+10 | 0.00 | 0.00 |
October | 21306894.53 | 0.00 | 0.650479E+09 | 0.270916E+10 | 0.00 | 0.00 |
November | 0.379540E+10 | 0.00 | 24314290.39 | 0.262177E+10 | 0.00 | 0.00 |
December | 0.686094E+10 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.405081E+11 | 0.00 | 0.111125E+12 | 0.318982E+11 | 0.00 | 0.00 |
Minimum of Months | 5077.54 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.161617E+11 | 0.00 | 0.356327E+11 | 0.270916E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357336E+11 | 0.00 | 0.362308E+12 | 0.808765E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329208E+11 | 0.00 | 0.253619E+12 | 0.603112E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380739E+11 | 0.467832E+10 | 0.887356E+11 | 0.608054E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372273E+11 | 0.589696E+11 | 0.478903E+11 | 0.362073E+12 | 0.911246E+10 | 0.00 | 0.00 | 0.00 |
May | 0.381022E+11 | 0.147912E+12 | 0.351568E+11 | 0.753658E+11 | 0.108756E+11 | 0.00 | 0.00 | 0.00 |
June | 0.357366E+11 | 0.392250E+12 | 0.219158E+11 | 0.175793E+11 | 0.759601E+11 | 0.00 | 0.00 | 0.00 |
July | 0.359387E+11 | 0.570797E+12 | 0.754434E+10 | 0.425767E+09 | 0.944126E+11 | 0.00 | 0.00 | 0.00 |
August | 0.362911E+11 | 0.491530E+12 | 0.104866E+11 | 0.276695E+10 | 0.844605E+11 | 0.00 | 0.00 | 0.00 |
September | 0.364869E+11 | 0.189034E+12 | 0.301472E+11 | 0.908968E+11 | 0.165211E+11 | 0.00 | 0.00 | 0.00 |
October | 0.394588E+11 | 0.152949E+11 | 0.416655E+11 | 0.331385E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368174E+11 | 0.164180E+10 | 0.123041E+12 | 0.544738E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367139E+11 | 0.00 | 0.191155E+12 | 0.849518E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439501E+12 | 0.187211E+13 | 0.121366E+13 | 0.429468E+13 | 0.291342E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329208E+11 | 0.00 | 0.754434E+10 | 0.425767E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394588E+11 | 0.570797E+12 | 0.362308E+12 | 0.849518E+12 | 0.944126E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270916E+10 | 0.00 | 0.161617E+11 | 0.673366E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.00 | 0.109293E+11 | 0.500755E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.212705E+09 | 0.230509E+10 | 0.512668E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.324324E+10 | 0.434048E+09 | 0.317775E+11 | 0.718988E+09 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 0.734146E+10 | 5077.54 | 0.104455E+11 | 0.765406E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 0.238603E+11 | 6488.43 | 0.360306E+10 | 0.671839E+10 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 0.356327E+11 | 6698.88 | 0.554350E+09 | 0.850180E+10 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 0.294316E+11 | 5952.29 | 0.128475E+10 | 0.715157E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 0.107281E+11 | 290910.59 | 0.109931E+11 | 0.165769E+10 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 0.650479E+09 | 21306894.53 | 0.307971E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 24314290.39 | 0.379540E+10 | 0.467758E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.00 | 0.686094E+10 | 0.706839E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.111125E+12 | 0.405081E+11 | 0.375594E+12 | 0.255138E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244698E+10 | 0.00 | 5077.54 | 0.554350E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.356327E+11 | 0.161617E+11 | 0.706839E+11 | 0.850180E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.357336E+11 | 0.362308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329208E+11 | 0.253619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380739E+11 | 0.887356E+11 | 0.467832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372273E+11 | 0.478903E+11 | 0.589696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381022E+11 | 0.351568E+11 | 0.147912E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.357366E+11 | 0.219158E+11 | 0.392250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.359387E+11 | 0.754434E+10 | 0.570797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.362911E+11 | 0.104866E+11 | 0.491530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364869E+11 | 0.301472E+11 | 0.189034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394588E+11 | 0.416655E+11 | 0.152949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368174E+11 | 0.123041E+12 | 0.164180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367139E+11 | 0.191155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439501E+12 | 0.121366E+13 | 0.187211E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.329208E+11 | 0.754434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.394588E+11 | 0.362308E+12 | 0.570797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.270916E+10 | 0.161617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.109293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.230509E+10 | 0.212705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.434048E+09 | 0.324324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 5077.54 | 0.734146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 6488.43 | 0.238603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 6698.88 | 0.356327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 5952.29 | 0.294316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 290910.59 | 0.107281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 21306894.53 | 0.650479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.379540E+10 | 24314290.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.686094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.405081E+11 | 0.111125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.244698E+10 | 5077.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.161617E+11 | 0.356327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.596134E+11 | 0.00 | 0.00 | 27.81 | 0.00 | 0.150175E+11 | 17096975.04 | 0.00 | 0.99 |
February | 0.350965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259391E+11 | 0.00 | 0.00 | 0.99 |
March | 0.485519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
April | 0.411073E+11 | 0.00 | 28999719.96 | 0.00 | 0.850779E+09 | 0.00 | 0.00 | 192761.54 | 0.99 |
May | 0.365857E+11 | 0.00 | 4206105.98 | 0.00 | 0.131501E+10 | 0.00 | 0.00 | 29170.18 | 0.99 |
June | 0.197524E+11 | 0.00 | 0.00 | 0.00 | 0.883141E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 0.967635E+10 | 0.00 | 0.00 | 0.00 | 0.148995E+11 | 0.00 | 0.00 | 0.00 | 1.00 |
August | 0.150140E+11 | 0.00 | 0.00 | 0.00 | 0.119379E+11 | 0.00 | 0.00 | 0.00 | 1.00 |
September | 0.215097E+11 | 0.00 | 0.00 | 8088967.29 | 0.131378E+10 | 0.00 | 0.115709E+11 | 0.00 | 1.01 |
October | 0.762740E+10 | 0.00 | 0.00 | 42038077.60 | 0.00 | 0.00 | 0.420398E+11 | 0.00 | 1.05 |
November | 0.193107E+11 | 0.00 | 0.00 | 31354408.85 | 0.00 | 0.00 | 0.344273E+11 | 0.00 | 1.03 |
December | 0.307510E+11 | 0.00 | 0.00 | 12803999.60 | 0.00 | 0.00 | 0.264557E+11 | 0.00 | 1.00 |
Annual Sum or Average | 0.344596E+12 | 0.00 | 33205825.93 | 94285481.14 | 0.391484E+11 | 0.409566E+11 | 0.114511E+12 | 221931.72 | 1.00 |
Minimum of Months | 0.762740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.596134E+11 | 0.00 | 28999719.96 | 42038077.60 | 0.148995E+11 | 0.259391E+11 | 0.420398E+11 | 192761.54 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104922E+10 | 0.00 | 0.00 | 30087.30 | 0.00 | 0.900112E+10 | 85269246.76 | 0.00 | 2.43 |
February | 0.161039E+10 | 0.00 | 0.00 | 185855.95 | 0.00 | 0.656735E+10 | 0.124277E+09 | 0.00 | 2.44 |
March | 0.339582E+10 | 0.00 | 0.00 | 105055.13 | 0.00 | 0.305773E+10 | 0.139657E+09 | 0.00 | 2.45 |
April | 0.400585E+10 | 75090899.68 | 0.00 | 43749.19 | 46142273.23 | 0.151285E+10 | 62673779.30 | 0.00 | 2.44 |
May | 0.496537E+10 | 2144407.21 | 0.00 | 0.00 | 0.176979E+09 | 2128164.93 | 0.00 | 0.00 | 2.45 |
June | 0.268173E+10 | 0.219743E+09 | 0.00 | 348.87 | 0.979356E+09 | 0.00 | 195460.21 | 0.00 | 2.46 |
July | 0.131382E+10 | 0.240719E+09 | 0.00 | 0.00 | 0.178228E+10 | 0.00 | 0.00 | 0.00 | 2.46 |
August | 0.203474E+10 | 0.333022E+09 | 0.00 | 31656.68 | 0.128787E+10 | 0.00 | 3787340.79 | 0.00 | 2.46 |
September | 0.413988E+10 | 0.133187E+09 | 0.00 | 452658.29 | 62431602.04 | 0.122635E+09 | 0.179356E+09 | 0.00 | 2.49 |
October | 0.543516E+10 | 0.00 | 0.00 | 1091542.33 | 0.00 | 0.395865E+09 | 0.683946E+09 | 0.00 | 2.48 |
November | 0.319945E+10 | 0.00 | 0.00 | 383703.16 | 0.00 | 0.366755E+10 | 0.239109E+09 | 0.00 | 2.46 |
December | 0.128622E+10 | 0.00 | 0.00 | 181171.75 | 0.00 | 0.622018E+10 | 0.204451E+09 | 0.00 | 2.43 |
Annual Sum or Average | 0.351177E+11 | 0.100391E+10 | 0.00 | 2505828.65 | 0.433506E+10 | 0.305474E+11 | 0.172272E+10 | 0.00 | 2.45 |
Minimum of Months | 0.104922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
Maximum of Months | 0.543516E+10 | 0.333022E+09 | 0.00 | 1091542.33 | 0.178228E+10 | 0.900112E+10 | 0.683946E+09 | 0.00 | 2.49 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.498682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223959E+10 | 0.00 | 0.00 | 1.50 |
February | 0.364811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226054E+10 | 0.00 | 0.00 | 1.50 |
March | 0.465423E+10 | 0.00 | 0.00 | 9808.53 | 0.00 | 0.00 | 45892718.64 | 0.00 | 1.51 |
April | 0.382326E+10 | 225077.25 | 0.00 | 55422.30 | 84961900.13 | 0.00 | 0.156134E+09 | 0.00 | 1.51 |
May | 0.336152E+10 | 1829340.19 | 0.00 | 31942.11 | 0.125882E+09 | 0.00 | 0.180187E+09 | 0.00 | 1.52 |
June | 0.179764E+10 | 46483970.67 | 0.00 | 41328.15 | 0.808454E+09 | 0.00 | 0.114482E+09 | 0.00 | 1.52 |
July | 0.908100E+09 | 0.155581E+09 | 0.00 | 19335.86 | 0.128679E+10 | 0.00 | 28614730.40 | 0.00 | 1.52 |
August | 0.124249E+10 | 0.104676E+09 | 0.00 | 126616.58 | 0.105099E+10 | 0.00 | 0.210841E+09 | 0.00 | 1.52 |
September | 0.282170E+10 | 8398724.96 | 0.00 | 198558.67 | 0.118783E+09 | 0.00 | 0.344826E+09 | 0.00 | 1.52 |
October | 0.418506E+10 | 0.00 | 0.00 | 132482.88 | 0.00 | 0.00 | 0.396377E+09 | 0.00 | 1.51 |
November | 0.455977E+10 | 0.00 | 0.00 | 29581.14 | 0.00 | 0.348612E+09 | 0.128507E+09 | 0.00 | 1.51 |
December | 0.548683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1485976.98 | 0.00 | 0.00 | 1.49 |
Annual Sum or Average | 0.414755E+11 | 0.317194E+09 | 0.00 | 645076.21 | 0.347586E+10 | 0.485023E+10 | 0.160586E+10 | 0.00 | 1.51 |
Minimum of Months | 0.908100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
Maximum of Months | 0.548683E+10 | 0.155581E+09 | 0.00 | 198558.67 | 0.128679E+10 | 0.226054E+10 | 0.396377E+09 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.718682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459198E+10 | 0.00 | 0.00 | 0.52 |
February | 0.150001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284224E+10 | 0.00 | 0.00 | 0.52 |
March | 0.264048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813632E+09 | 0.00 | 0.00 | 0.52 |
April | 0.280439E+10 | 0.00 | 0.00 | 0.00 | 62603599.56 | 0.120097E+09 | 0.00 | 0.00 | 0.52 |
May | 0.260281E+10 | 0.00 | 0.00 | 0.00 | 93854830.05 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.140524E+10 | 0.00 | 0.00 | 0.00 | 0.628291E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.688402E+09 | 0.00 | 0.00 | 0.00 | 0.105999E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.106814E+10 | 0.00 | 0.00 | 0.00 | 0.849295E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.232719E+10 | 0.00 | 0.00 | 0.00 | 93465685.02 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.336698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.265297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104864E+10 | 0.00 | 0.00 | 0.52 |
December | 0.158168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245166E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.233570E+11 | 0.00 | 0.00 | 0.00 | 0.278750E+10 | 0.118683E+11 | 0.00 | 0.00 | 0.52 |
Minimum of Months | 0.688402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.336698E+10 | 0.00 | 0.00 | 0.00 | 0.105999E+10 | 0.459198E+10 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49818058.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288639E+10 | 0.00 | 0.00 | 0.50 |
February | 0.214812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218597E+10 | 0.00 | 0.00 | 0.50 |
March | 0.835312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107443E+10 | 0.00 | 0.00 | 0.50 |
April | 0.127508E+10 | 0.00 | 0.00 | 0.00 | 34612851.74 | 0.341841E+09 | 0.00 | 0.00 | 0.50 |
May | 0.143907E+10 | 0.00 | 0.00 | 0.00 | 51891318.40 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.776944E+09 | 0.00 | 0.00 | 0.00 | 0.347375E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.380610E+09 | 0.00 | 0.00 | 0.00 | 0.586057E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.590564E+09 | 0.00 | 0.00 | 0.00 | 0.469566E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.128668E+10 | 0.00 | 0.00 | 0.00 | 51676164.33 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.186157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.993217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105336E+10 | 0.00 | 0.00 | 0.50 |
December | 0.109607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212038E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.981327E+10 | 0.00 | 0.00 | 0.00 | 0.154118E+10 | 0.966238E+10 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 49818058.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.186157E+10 | 0.00 | 0.00 | 0.00 | 0.586057E+09 | 0.288639E+10 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.347368E+10 | 0.00 | 0.00 | 77216907.66 | 0.00 | 0.248765E+11 | 0.917587E+11 | 0.00 | 25.07 |
February | 0.190203E+10 | 0.00 | 0.00 | 69927491.38 | 0.00 | 0.259983E+11 | 0.696482E+11 | 0.00 | 25.14 |
March | 0.506787E+09 | 0.00 | 0.00 | 89944896.22 | 0.00 | 0.00 | 0.804421E+11 | 0.00 | 25.84 |
April | 0.322857E+09 | 0.128360E+10 | 0.00 | 82662447.90 | 43437068.90 | 0.00 | 0.677695E+11 | 0.00 | 25.50 |
May | 0.346915E+09 | 0.195882E+10 | 0.00 | 82805192.35 | 63895652.22 | 0.00 | 0.596302E+11 | 0.00 | 25.19 |
June | 0.207792E+09 | 0.133317E+11 | 0.00 | 50127940.81 | 0.298583E+09 | 0.00 | 0.315384E+11 | 0.00 | 24.65 |
July | 81765485.39 | 0.230703E+11 | 0.00 | 30028460.39 | 0.393014E+09 | 0.00 | 0.147876E+11 | 0.00 | 24.29 |
August | 0.127344E+09 | 0.183351E+11 | 0.00 | 43819592.87 | 0.329266E+09 | 0.00 | 0.235709E+11 | 0.00 | 24.52 |
September | 0.307352E+09 | 0.194374E+10 | 0.00 | 74599164.81 | 62913904.95 | 0.00 | 0.533752E+11 | 0.00 | 25.07 |
October | 0.367487E+09 | 0.00 | 0.00 | 89461019.00 | 0.00 | 0.00 | 0.784396E+11 | 0.00 | 25.72 |
November | 0.136303E+10 | 0.00 | 0.00 | 85148252.16 | 0.00 | 0.296807E+10 | 0.815261E+11 | 0.00 | 25.62 |
December | 0.934959E+09 | 0.00 | 0.00 | 88583148.85 | 0.00 | 0.00 | 0.929267E+11 | 0.00 | 25.40 |
Annual Sum or Average | 0.994200E+10 | 0.599233E+11 | 0.00 | 0.864325E+09 | 0.119111E+10 | 0.538429E+11 | 0.745413E+12 | 0.00 | 25.17 |
Minimum of Months | 81765485.39 | 0.00 | 0.00 | 30028460.39 | 0.00 | 0.00 | 0.147876E+11 | 0.00 | 24.29 |
Maximum of Months | 0.347368E+10 | 0.230703E+11 | 0.00 | 89944896.22 | 0.393014E+09 | 0.259983E+11 | 0.929267E+11 | 0.00 | 25.84 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263126E+11 | 0.00 | 0.00 | 455092.11 | 0.00 | 0.169965E+11 | 0.987726E+09 | 0.00 | 3.77 |
February | 0.204401E+11 | 0.00 | 0.00 | 1431865.70 | 0.00 | 0.137768E+11 | 0.205912E+10 | 0.00 | 3.79 |
March | 0.229807E+11 | 0.00 | 0.00 | 2439781.96 | 0.00 | 0.496787E+09 | 0.533551E+10 | 0.00 | 3.81 |
April | 0.162722E+11 | 0.431473E+09 | 0.00 | 4148393.86 | 94241809.98 | 70946634.36 | 0.804563E+10 | 0.00 | 3.81 |
May | 0.103200E+11 | 0.226569E+09 | 0.00 | 5663314.10 | 0.556267E+09 | 0.00 | 0.113841E+11 | 0.00 | 3.82 |
June | 0.486740E+10 | 0.304341E+10 | 0.00 | 5182319.68 | 0.219711E+10 | 0.00 | 0.684845E+10 | 0.00 | 3.83 |
July | 0.143311E+10 | 0.517842E+10 | 0.00 | 4229210.39 | 0.366287E+10 | 0.00 | 0.430458E+10 | 0.00 | 3.83 |
August | 0.197090E+10 | 0.404675E+10 | 0.00 | 7480866.34 | 0.303715E+10 | 0.00 | 0.693090E+10 | 0.00 | 3.84 |
September | 0.801334E+10 | 0.675657E+09 | 0.00 | 10470796.22 | 0.131294E+09 | 0.00 | 0.113972E+11 | 0.00 | 3.85 |
October | 0.140697E+11 | 0.00 | 0.00 | 10941749.61 | 0.00 | 0.00 | 0.143354E+11 | 0.00 | 3.86 |
November | 0.220636E+11 | 0.00 | 0.00 | 4044125.93 | 0.00 | 0.274475E+10 | 0.623399E+10 | 0.00 | 3.82 |
December | 0.261445E+11 | 0.00 | 0.00 | 1377629.09 | 0.00 | 0.579315E+10 | 0.176652E+10 | 0.00 | 3.78 |
Annual Sum or Average | 0.174888E+12 | 0.136023E+11 | 0.00 | 57865144.98 | 0.967894E+10 | 0.398789E+11 | 0.796292E+11 | 0.00 | 3.82 |
Minimum of Months | 0.143311E+10 | 0.00 | 0.00 | 455092.11 | 0.00 | 0.00 | 0.987726E+09 | 0.00 | 3.77 |
Maximum of Months | 0.263126E+11 | 0.517842E+10 | 0.00 | 10941749.61 | 0.366287E+10 | 0.169965E+11 | 0.143354E+11 | 0.00 | 3.86 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109105E+12 | 0.00 | 0.00 | 291232.71 | 0.00 | 0.426440E+11 | 0.926442E+09 | 0.00 | 1.88 |
February | 0.761511E+11 | 0.00 | 0.00 | 834373.97 | 0.00 | 0.455984E+11 | 0.308475E+10 | 0.00 | 1.88 |
March | 0.859748E+11 | 0.00 | 0.00 | 4736442.43 | 0.00 | 0.00 | 0.133227E+11 | 0.00 | 1.90 |
April | 0.617232E+11 | 0.157224E+09 | 0.00 | 10387026.00 | 0.164256E+10 | 0.00 | 0.223695E+11 | 0.00 | 1.90 |
May | 0.386395E+11 | 0.134832E+09 | 0.00 | 15317558.71 | 0.256340E+10 | 0.00 | 0.361746E+11 | 0.00 | 1.90 |
June | 0.183005E+11 | 0.404249E+10 | 0.00 | 11763283.27 | 0.140202E+11 | 0.00 | 0.220871E+11 | 0.00 | 1.91 |
July | 0.803931E+10 | 0.973407E+10 | 0.00 | 6916120.20 | 0.207396E+11 | 0.00 | 0.117446E+11 | 0.00 | 1.91 |
August | 0.927834E+10 | 0.625713E+10 | 0.00 | 17113721.99 | 0.181592E+11 | 0.00 | 0.214136E+11 | 0.00 | 1.91 |
September | 0.323011E+11 | 0.409453E+09 | 0.00 | 23806721.91 | 0.227759E+10 | 0.00 | 0.346672E+11 | 0.00 | 1.91 |
October | 0.586295E+11 | 0.00 | 0.00 | 20805877.38 | 0.00 | 0.00 | 0.383269E+11 | 0.00 | 1.90 |
November | 0.823804E+11 | 0.00 | 0.00 | 8207093.40 | 0.00 | 0.616201E+10 | 0.178977E+11 | 0.00 | 1.89 |
December | 0.113977E+12 | 0.00 | 0.00 | 282663.10 | 0.00 | 0.00 | 0.197736E+10 | 0.00 | 1.88 |
Annual Sum or Average | 0.694500E+12 | 0.207352E+11 | 0.00 | 0.120462E+09 | 0.594026E+11 | 0.944044E+11 | 0.223993E+12 | 0.00 | 1.90 |
Minimum of Months | 0.803931E+10 | 0.00 | 0.00 | 282663.10 | 0.00 | 0.00 | 0.926442E+09 | 0.00 | 1.88 |
Maximum of Months | 0.113977E+12 | 0.973407E+10 | 0.00 | 23806721.91 | 0.207396E+11 | 0.455984E+11 | 0.383269E+11 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26483415.43 | 0.00 | 0.00 | 56055.20 | 0.00 | 0.243972E+10 | 3573210.94 | 0.00 | 0.35 |
February | 35008771.94 | 0.00 | 0.00 | 466317.88 | 0.00 | 0.202258E+10 | 48162819.00 | 0.00 | 0.35 |
March | 62866851.24 | 0.00 | 0.00 | 1658169.86 | 0.00 | 0.116463E+10 | 0.231170E+09 | 0.00 | 0.36 |
April | 51192884.59 | 22321794.36 | 997.50 | 4209132.66 | 0.00 | 0.699086E+09 | 0.475918E+09 | 3281.47 | 0.35 |
May | 43465657.68 | 32169591.34 | 74332.75 | 7171303.20 | 0.00 | 0.147422E+09 | 0.813080E+09 | 9028.09 | 0.36 |
June | 17046007.87 | 0.298204E+09 | 235734.36 | 4587577.92 | 800333.12 | 70245282.69 | 0.404592E+09 | 29371.23 | 0.36 |
July | 1933388.23 | 0.502594E+09 | 325309.76 | 3100663.94 | 11484.75 | 354168.93 | 0.206892E+09 | 46536.20 | 0.36 |
August | 86193.93 | 0.353444E+09 | 243065.57 | 4377781.25 | 1791462.58 | 433943.95 | 0.343029E+09 | 26079.65 | 0.36 |
September | 29076372.90 | 58372285.11 | 23218.09 | 5790975.54 | 0.00 | 0.230347E+09 | 0.619160E+09 | 10690.72 | 0.36 |
October | 62906775.18 | 0.00 | 0.00 | 3541967.14 | 0.00 | 0.764894E+09 | 0.533038E+09 | 0.00 | 0.35 |
November | 55418488.29 | 0.00 | 0.00 | 816150.96 | 0.00 | 0.129443E+10 | 0.195767E+09 | 0.00 | 0.35 |
December | 39757689.85 | 0.00 | 0.00 | 104095.59 | 0.00 | 0.160910E+10 | 7361756.39 | 0.00 | 0.35 |
Annual Sum or Average | 0.425242E+09 | 0.126711E+10 | 902658.02 | 35880191.14 | 2603280.45 | 0.104432E+11 | 0.388174E+10 | 124987.37 | 0.35 |
Minimum of Months | 86193.93 | 0.00 | 0.00 | 56055.20 | 0.00 | 354168.93 | 3573210.94 | 0.00 | 0.35 |
Maximum of Months | 62906775.18 | 0.502594E+09 | 325309.76 | 7171303.20 | 1791462.58 | 0.243972E+10 | 0.813080E+09 | 46536.20 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2693252.30 | 0.00 | 0.00 | 4808.45 | 0.00 | 0.246682E+10 | 315904.03 | 0.00 | 0.35 |
February | 18357091.23 | 0.00 | 0.00 | 177793.48 | 0.00 | 0.206531E+10 | 22373401.06 | 0.00 | 0.35 |
March | 52051798.88 | 0.00 | 0.00 | 918231.62 | 0.00 | 0.126098E+10 | 0.146369E+09 | 0.00 | 0.36 |
April | 54358694.44 | 22321794.36 | 610.88 | 3472757.87 | 0.00 | 0.753077E+09 | 0.419497E+09 | 3668.08 | 0.35 |
May | 48478372.66 | 31069382.57 | 73669.73 | 6689129.58 | 1100208.77 | 0.168108E+09 | 0.787863E+09 | 9691.12 | 0.36 |
June | 17801122.19 | 0.297969E+09 | 251759.97 | 4509981.53 | 1020293.13 | 72440206.54 | 0.401719E+09 | 28964.95 | 0.36 |
July | 3727332.38 | 0.502119E+09 | 344404.69 | 3029836.20 | 468144.65 | 354168.93 | 0.205169E+09 | 45382.53 | 0.36 |
August | 5132566.64 | 0.351441E+09 | 309366.03 | 4073319.60 | 3726343.27 | 459056.64 | 0.338262E+09 | 27584.39 | 0.36 |
September | 42056401.35 | 58280079.90 | 23183.46 | 4801914.12 | 92205.21 | 0.289761E+09 | 0.547755E+09 | 10725.35 | 0.36 |
October | 72150224.55 | 0.00 | 0.00 | 2105698.64 | 0.00 | 0.942257E+09 | 0.347867E+09 | 0.00 | 0.35 |
November | 43956047.95 | 0.00 | 0.00 | 397831.02 | 0.00 | 0.138840E+10 | 0.113678E+09 | 0.00 | 0.35 |
December | 4866238.09 | 0.00 | 0.00 | 9868.12 | 0.00 | 0.165097E+10 | 484377.92 | 0.00 | 0.35 |
Annual Sum or Average | 0.365629E+09 | 0.126320E+10 | 1002994.76 | 30191170.24 | 6407195.02 | 0.110589E+11 | 0.333135E+10 | 126016.42 | 0.35 |
Minimum of Months | 2693252.30 | 0.00 | 0.00 | 4808.45 | 0.00 | 354168.93 | 315904.03 | 0.00 | 0.35 |
Maximum of Months | 72150224.55 | 0.502119E+09 | 344404.69 | 6689129.58 | 3726343.27 | 0.246682E+10 | 0.787863E+09 | 45382.53 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.986449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128032E+09 | 0.00 | 0.00 | 0.02 |
February | 0.128643E+10 | 0.00 | 0.00 | 5744.15 | 0.00 | 0.00 | 10800648.26 | 0.00 | 0.02 |
March | 0.664629E+09 | 0.00 | 0.00 | 1155313.09 | 0.00 | 0.00 | 0.359772E+09 | 0.00 | 0.02 |
April | 0.691159E+09 | 46090479.00 | 0.00 | 871745.99 | 0.00 | 0.00 | 0.346468E+09 | 0.00 | 0.02 |
May | 0.144009E+09 | 80113244.78 | 0.00 | 1271679.38 | 0.00 | 0.00 | 0.676817E+09 | 0.00 | 0.02 |
June | 0.146523E+09 | 0.336865E+09 | 0.00 | 922064.82 | 0.00 | 0.00 | 0.281324E+09 | 0.00 | 0.02 |
July | 0.00 | 0.530638E+09 | 0.00 | 610773.45 | 0.00 | 0.00 | 0.122341E+09 | 0.00 | 0.02 |
August | 0.00 | 0.462403E+09 | 0.00 | 890503.87 | 0.00 | 0.00 | 0.110031E+09 | 0.00 | 0.02 |
September | 0.192512E+09 | 63551553.54 | 0.00 | 2236674.49 | 0.00 | 0.00 | 0.575307E+09 | 0.00 | 0.02 |
October | 0.378621E+09 | 0.00 | 0.00 | 3814089.84 | 0.00 | 0.00 | 0.904335E+09 | 0.00 | 0.02 |
November | 0.899107E+09 | 0.00 | 0.00 | 1082854.96 | 0.00 | 0.00 | 0.278564E+09 | 0.00 | 0.02 |
December | 0.790957E+09 | 0.00 | 0.00 | 14925.29 | 0.00 | 0.107569E+09 | 30757409.44 | 0.00 | 0.02 |
Annual Sum or Average | 0.618039E+10 | 0.151966E+10 | 0.00 | 12876369.33 | 0.00 | 0.235601E+09 | 0.369652E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.128643E+10 | 0.530638E+09 | 0.00 | 3814089.84 | 0.00 | 0.128032E+09 | 0.904335E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.726076E+09 | 0.00 | 0.00 | 874394.28 | 0.00 | 0.317800E+11 | 0.977966E+09 | 0.00 | 0.40 |
February | 0.734119E+09 | 0.00 | 0.00 | 3568828.73 | 0.00 | 0.244474E+11 | 0.337017E+10 | 0.00 | 0.40 |
March | 0.986925E+09 | 0.00 | 0.00 | 22242490.22 | 0.00 | 0.896196E+10 | 0.982734E+10 | 0.00 | 0.40 |
April | 0.832204E+09 | 0.269045E+09 | 58653.02 | 48763320.74 | 33564894.20 | 0.209106E+10 | 0.137093E+11 | 18948.76 | 0.40 |
May | 0.668159E+09 | 0.377615E+09 | 19940.15 | 0.102325E+09 | 59621431.33 | 30036551.65 | 0.129081E+11 | 15900.92 | 0.40 |
June | 0.274887E+09 | 0.394475E+10 | 0.00 | 63814362.50 | 0.112628E+09 | 10983056.03 | 0.638126E+10 | 0.00 | 0.40 |
July | 56731536.68 | 0.654615E+10 | 446184.38 | 36676794.16 | 0.272547E+09 | 1772327.48 | 0.278283E+10 | 12179.32 | 0.40 |
August | 89535476.51 | 0.455113E+10 | 71895.76 | 51509747.93 | 0.268571E+09 | 2624575.81 | 0.457339E+10 | 4651.27 | 0.40 |
September | 0.582833E+09 | 0.743529E+09 | 490358.30 | 76009586.76 | 47817567.34 | 47378963.97 | 0.112838E+11 | 10369.28 | 0.40 |
October | 0.978183E+09 | 0.00 | 0.00 | 51103870.79 | 0.00 | 0.404743E+09 | 0.170637E+11 | 0.00 | 0.40 |
November | 0.961671E+09 | 0.00 | 0.00 | 20737128.93 | 0.00 | 0.111555E+11 | 0.882805E+10 | 0.00 | 0.40 |
December | 0.886563E+09 | 0.00 | 0.00 | 1291255.19 | 0.00 | 0.202407E+11 | 0.132724E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.777789E+10 | 0.164322E+11 | 1087031.61 | 0.478917E+09 | 0.794750E+09 | 0.991742E+11 | 0.930331E+11 | 62049.55 | 0.40 |
Minimum of Months | 56731536.68 | 0.00 | 0.00 | 874394.28 | 0.00 | 1772327.48 | 0.977966E+09 | 0.00 | 0.40 |
Maximum of Months | 0.986925E+09 | 0.654615E+10 | 490358.30 | 0.102325E+09 | 0.272547E+09 | 0.317800E+11 | 0.170637E+11 | 18948.76 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31099177.62 | 0.00 | 0.00 | 17828.91 | 0.00 | 0.243110E+10 | 7608931.82 | 0.00 | 0.35 |
February | 35897916.98 | 0.00 | 0.00 | 329308.30 | 0.00 | 0.202956E+10 | 40430974.44 | 0.00 | 0.35 |
March | 56468808.87 | 0.00 | 0.00 | 1412598.59 | 0.00 | 0.112776E+10 | 0.274679E+09 | 0.00 | 0.36 |
April | 45353818.27 | 22307073.76 | 18383.48 | 3657470.64 | 0.00 | 0.699784E+09 | 0.481611E+09 | 616.07 | 0.35 |
May | 21942866.02 | 32183895.97 | 66469.83 | 8241848.49 | 0.00 | 0.117522E+09 | 0.863431E+09 | 2586.38 | 0.36 |
June | 13403506.30 | 0.298190E+09 | 107356.81 | 5195263.42 | 968437.60 | 56544361.87 | 0.421328E+09 | 3731.59 | 0.36 |
July | 1933388.23 | 0.502754E+09 | 208113.69 | 3439797.43 | 0.00 | 229603.27 | 0.206678E+09 | 14473.01 | 0.36 |
August | 0.00 | 0.351536E+09 | 303183.84 | 4559490.19 | 3649587.53 | 350337.07 | 0.343018E+09 | 15526.85 | 0.36 |
September | 21510068.00 | 58374609.31 | 26601.22 | 6272017.66 | 0.00 | 0.213222E+09 | 0.643371E+09 | 4983.39 | 0.36 |
October | 52712722.18 | 0.00 | 0.00 | 3216289.76 | 0.00 | 0.756550E+09 | 0.551901E+09 | 0.00 | 0.35 |
November | 54655731.51 | 0.00 | 0.00 | 700378.24 | 0.00 | 0.128019E+10 | 0.210884E+09 | 0.00 | 0.35 |
December | 38583346.60 | 0.00 | 0.00 | 77716.90 | 0.00 | 0.159644E+10 | 21224941.38 | 0.00 | 0.35 |
Annual Sum or Average | 0.373561E+09 | 0.126535E+10 | 730108.88 | 37120008.52 | 4618025.13 | 0.103093E+11 | 0.406616E+10 | 41917.28 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17828.91 | 0.00 | 229603.27 | 7608931.82 | 0.00 | 0.35 |
Maximum of Months | 56468808.87 | 0.502754E+09 | 303183.84 | 8241848.49 | 3649587.53 | 0.243110E+10 | 0.863431E+09 | 15526.85 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4009811.06 | 0.00 | 0.00 | 4980.66 | 0.00 | 0.246529E+10 | 522427.48 | 0.00 | 0.35 |
February | 20054984.11 | 0.00 | 0.00 | 81366.82 | 0.00 | 0.206934E+10 | 16740437.12 | 0.00 | 0.35 |
March | 57727068.09 | 0.00 | 0.00 | 713927.25 | 0.00 | 0.124321E+10 | 0.158677E+09 | 0.00 | 0.36 |
April | 51840837.50 | 22263957.24 | 59771.08 | 2879373.55 | 0.00 | 0.775825E+09 | 0.399860E+09 | 2345.00 | 0.35 |
May | 38014821.32 | 32160576.97 | 87946.96 | 7724059.63 | 0.00 | 0.136451E+09 | 0.828948E+09 | 4428.25 | 0.36 |
June | 14404758.59 | 0.298137E+09 | 159967.25 | 5108680.87 | 968437.60 | 58697371.13 | 0.418260E+09 | 4128.05 | 0.36 |
July | 1938382.70 | 0.502356E+09 | 334079.02 | 3367934.21 | 268902.98 | 238801.85 | 0.206736E+09 | 17841.66 | 0.36 |
August | 2506725.57 | 0.350988E+09 | 358436.99 | 4257572.25 | 4136016.78 | 4232776.86 | 0.336930E+09 | 22003.63 | 0.36 |
September | 35981176.74 | 58259353.12 | 131903.74 | 5167797.33 | 0.00 | 0.271969E+09 | 0.571257E+09 | 14937.05 | 0.36 |
October | 72150224.55 | 0.00 | 0.00 | 1365371.42 | 0.00 | 0.935417E+09 | 0.355448E+09 | 0.00 | 0.35 |
November | 42462766.71 | 0.00 | 0.00 | 173045.51 | 0.00 | 0.139443E+10 | 0.109371E+09 | 0.00 | 0.35 |
December | 4491193.51 | 0.00 | 0.00 | 9182.89 | 0.00 | 0.165027E+10 | 1560203.17 | 0.00 | 0.35 |
Annual Sum or Average | 0.345583E+09 | 0.126416E+10 | 1132105.05 | 30853292.39 | 5373357.36 | 0.110054E+11 | 0.340431E+10 | 65683.64 | 0.35 |
Minimum of Months | 1938382.70 | 0.00 | 0.00 | 4980.66 | 0.00 | 238801.85 | 522427.48 | 0.00 | 0.35 |
Maximum of Months | 72150224.55 | 0.502356E+09 | 358436.99 | 7724059.63 | 4136016.78 | 0.246529E+10 | 0.828948E+09 | 22003.63 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370457E+11 | 0.00 | 0.00 | 0.52 |
February | 0.411518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273841E+11 | 0.00 | 0.00 | 0.52 |
March | 0.134608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115959E+11 | 0.00 | 0.00 | 0.52 |
April | 0.164762E+11 | 0.00 | 0.00 | 0.00 | 0.454136E+09 | 0.473842E+10 | 0.00 | 0.00 | 0.52 |
May | 0.187833E+11 | 0.00 | 0.00 | 0.00 | 0.680837E+09 | 97903761.71 | 0.00 | 0.00 | 0.52 |
June | 0.101939E+11 | 0.00 | 0.00 | 0.00 | 0.455772E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.499378E+10 | 0.00 | 0.00 | 0.00 | 0.768933E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.774846E+10 | 0.00 | 0.00 | 0.00 | 0.616092E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.163426E+11 | 0.00 | 0.00 | 0.00 | 0.678014E+09 | 0.539182E+09 | 0.00 | 0.00 | 0.52 |
October | 0.218130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261162E+10 | 0.00 | 0.00 | 0.52 |
November | 0.115127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153393E+11 | 0.00 | 0.00 | 0.52 |
December | 0.356898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256895E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.130488E+12 | 0.00 | 0.00 | 0.00 | 0.202210E+11 | 0.125042E+12 | 0.00 | 0.00 | 0.52 |
Minimum of Months | 0.147866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.218130E+11 | 0.00 | 0.00 | 0.00 | 0.768933E+10 | 0.370457E+11 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3683968.89 | 0.00 | 0.00 | 10818.23 | 0.00 | 0.612932E+09 | 831102.77 | 0.00 | 0.35 |
February | 6628243.62 | 0.00 | 0.00 | 108572.18 | 0.00 | 0.511925E+09 | 7892637.44 | 0.00 | 0.35 |
March | 15183787.31 | 0.00 | 0.00 | 377909.29 | 0.00 | 0.309196E+09 | 40322664.72 | 0.00 | 0.36 |
April | 10954413.82 | 5580448.59 | 338.15 | 1095044.98 | 0.00 | 0.191104E+09 | 0.104448E+09 | 731.59 | 0.35 |
May | 8561790.23 | 8053073.25 | 8378.53 | 1886445.26 | 0.00 | 55938378.43 | 0.186398E+09 | 1786.26 | 0.36 |
June | 3625280.14 | 74726383.02 | 42892.41 | 1221479.88 | 42558.08 | 25101759.16 | 94169146.01 | 5564.73 | 0.36 |
July | 483347.06 | 0.125666E+09 | 69158.03 | 801279.01 | 0.00 | 91622.60 | 51693916.17 | 9187.15 | 0.36 |
August | 0.00 | 88825988.27 | 45328.22 | 1114495.51 | 0.00 | 249839.22 | 85617503.01 | 4744.26 | 0.36 |
September | 6340066.51 | 14594748.13 | 4453.82 | 1488012.74 | 0.00 | 79336889.20 | 0.133929E+09 | 2346.53 | 0.36 |
October | 16328031.10 | 0.00 | 0.00 | 864853.26 | 0.00 | 0.225809E+09 | 98093508.59 | 0.00 | 0.35 |
November | 10886830.34 | 0.00 | 0.00 | 182759.17 | 0.00 | 0.346058E+09 | 29481205.59 | 0.00 | 0.35 |
December | 7851061.53 | 0.00 | 0.00 | 20041.89 | 0.00 | 0.405237E+09 | 974236.97 | 0.00 | 0.35 |
Annual Sum or Average | 90526820.56 | 0.317447E+09 | 170549.14 | 9171711.40 | 42558.08 | 0.276298E+10 | 0.833851E+09 | 24360.53 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10818.23 | 0.00 | 91622.60 | 831102.77 | 0.00 | 0.35 |
Maximum of Months | 16328031.10 | 0.125666E+09 | 69158.03 | 1886445.26 | 42558.08 | 0.612932E+09 | 0.186398E+09 | 9187.15 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 1208.37 | 0.00 | 0.617428E+09 | 28777.22 | 0.00 | 0.35 |
February | 1801803.98 | 0.00 | 0.00 | 30585.33 | 0.00 | 0.520135E+09 | 4587137.32 | 0.00 | 0.35 |
March | 9413914.18 | 0.00 | 0.00 | 193091.60 | 0.00 | 0.330823E+09 | 24651103.71 | 0.00 | 0.36 |
April | 12900640.88 | 5580448.59 | 223.64 | 890935.31 | 0.00 | 0.203582E+09 | 90227928.00 | 846.10 | 0.35 |
May | 10523223.16 | 8026046.45 | 8408.85 | 1761151.44 | 27026.80 | 62298138.69 | 0.178202E+09 | 1755.94 | 0.36 |
June | 3742839.48 | 74730215.13 | 39509.06 | 1203803.17 | 42558.08 | 26193543.06 | 92977479.48 | 5115.98 | 0.36 |
July | 483347.06 | 0.125666E+09 | 69611.28 | 783716.12 | 0.00 | 90954.64 | 51712147.02 | 8733.90 | 0.36 |
August | 101721.21 | 88765311.87 | 62735.92 | 1040969.79 | 43462.57 | 950537.51 | 84888609.23 | 4550.38 | 0.36 |
September | 9870035.88 | 14595320.43 | 3960.29 | 1227742.11 | 0.00 | 92476938.58 | 0.117519E+09 | 2267.76 | 0.36 |
October | 18125347.36 | 0.00 | 0.00 | 472019.52 | 0.00 | 0.256516E+09 | 65981472.32 | 0.00 | 0.35 |
November | 8394210.87 | 0.00 | 0.00 | 80221.31 | 0.00 | 0.365116E+09 | 13018213.83 | 0.00 | 0.35 |
December | 192757.65 | 0.00 | 0.00 | 1344.19 | 0.00 | 0.413842E+09 | 45373.46 | 0.00 | 0.35 |
Annual Sum or Average | 75549841.73 | 0.317363E+09 | 184449.04 | 7686788.27 | 113047.45 | 0.288945E+10 | 0.723839E+09 | 23270.07 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1208.37 | 0.00 | 90954.64 | 28777.22 | 0.00 | 0.35 |
Maximum of Months | 18125347.36 | 0.125666E+09 | 69611.28 | 1761151.44 | 43462.57 | 0.617428E+09 | 0.178202E+09 | 8733.90 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75006777.42 | 0.00 | 0.00 | 1334112.78 | 0.00 | 0.364977E+10 | 0.239210E+09 | 0.00 | 0.40 |
February | 0.123087E+09 | 0.00 | 0.00 | 2354409.32 | 0.00 | 0.291963E+10 | 0.336476E+09 | 0.00 | 0.40 |
March | 47988795.62 | 0.00 | 0.00 | 4383199.03 | 0.00 | 0.158929E+10 | 0.702895E+09 | 0.00 | 0.40 |
April | 44736981.32 | 35844606.61 | 0.00 | 6247706.59 | 0.00 | 0.953085E+09 | 0.971352E+09 | 0.00 | 0.40 |
May | 28649856.85 | 51732804.70 | 48893.97 | 11396658.27 | 0.00 | 0.129138E+09 | 0.145420E+10 | 554.59 | 0.40 |
June | 17769452.55 | 0.479203E+09 | 245989.42 | 6821970.76 | 1025148.75 | 27231421.70 | 0.745263E+09 | 4891.83 | 0.40 |
July | 3104063.11 | 0.807241E+09 | 276844.18 | 4272104.48 | 0.00 | 356834.78 | 0.333085E+09 | 13505.78 | 0.40 |
August | 0.00 | 0.569983E+09 | 328610.48 | 6640279.52 | 434171.13 | 3546728.16 | 0.548412E+09 | 17917.19 | 0.40 |
September | 21892705.63 | 93763745.77 | 4862.40 | 10886468.88 | 0.00 | 0.185228E+09 | 0.120186E+10 | 2787.02 | 0.40 |
October | 43437264.99 | 0.00 | 0.00 | 10767237.12 | 0.00 | 0.638303E+09 | 0.149801E+10 | 0.00 | 0.40 |
November | 56237840.19 | 0.00 | 0.00 | 4052821.70 | 0.00 | 0.169631E+10 | 0.726203E+09 | 0.00 | 0.40 |
December | 32175804.70 | 0.00 | 0.00 | 2164033.18 | 0.00 | 0.238798E+10 | 0.236923E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.494086E+09 | 0.203777E+10 | 905200.45 | 71321001.63 | 1459319.87 | 0.141799E+11 | 0.899389E+10 | 39656.41 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1334112.78 | 0.00 | 356834.78 | 0.236923E+09 | 0.00 | 0.40 |
Maximum of Months | 0.123087E+09 | 0.807241E+09 | 328610.48 | 11396658.27 | 1025148.75 | 0.364977E+10 | 0.149801E+10 | 17917.19 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290086E+11 | 0.00 | 0.00 | 19499969.58 | 0.00 | 0.121590E+11 | 0.291993E+11 | 0.00 | 4.47 |
February | 0.122711E+11 | 0.00 | 0.00 | 24821954.11 | 0.00 | 0.192481E+11 | 0.266395E+11 | 0.00 | 4.55 |
March | 0.764335E+10 | 0.00 | 0.00 | 42766057.78 | 0.00 | 0.00 | 0.403156E+11 | 0.00 | 4.72 |
April | 0.253075E+10 | 0.756348E+09 | 0.00 | 50704422.82 | 72933065.67 | 0.00 | 0.396443E+11 | 0.00 | 4.84 |
May | 0.689372E+09 | 0.113076E+10 | 0.00 | 60214972.02 | 0.116477E+09 | 0.00 | 0.381478E+11 | 0.00 | 4.94 |
June | 0.355379E+09 | 0.824452E+10 | 0.00 | 41561053.66 | 0.345173E+09 | 0.00 | 0.207739E+11 | 0.00 | 4.89 |
July | 57025902.83 | 0.141028E+11 | 0.00 | 29596829.60 | 0.559085E+09 | 0.00 | 0.100503E+11 | 0.00 | 4.79 |
August | 0.168958E+09 | 0.109128E+11 | 0.00 | 38124528.33 | 0.689027E+09 | 0.00 | 0.159889E+11 | 0.00 | 4.83 |
September | 0.108634E+10 | 0.115655E+10 | 0.00 | 51777992.38 | 93354604.71 | 0.00 | 0.330795E+11 | 0.00 | 4.86 |
October | 0.206398E+10 | 0.00 | 0.00 | 52152038.66 | 0.00 | 0.00 | 0.463405E+11 | 0.00 | 4.85 |
November | 0.109540E+11 | 0.00 | 0.00 | 37146094.97 | 0.00 | 0.183414E+10 | 0.383096E+11 | 0.00 | 4.69 |
December | 0.193443E+11 | 0.00 | 0.00 | 27164683.08 | 0.00 | 0.00 | 0.345361E+11 | 0.00 | 4.50 |
Annual Sum or Average | 0.861731E+11 | 0.363037E+11 | 0.00 | 0.475531E+09 | 0.187605E+10 | 0.332413E+11 | 0.373025E+12 | 0.00 | 4.74 |
Minimum of Months | 57025902.83 | 0.00 | 0.00 | 19499969.58 | 0.00 | 0.00 | 0.100503E+11 | 0.00 | 4.47 |
Maximum of Months | 0.290086E+11 | 0.141028E+11 | 0.00 | 60214972.02 | 0.689027E+09 | 0.192481E+11 | 0.463405E+11 | 0.00 | 4.94 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260907E+11 | 0.00 | 0.00 | 27466196.92 | 0.00 | 0.121925E+11 | 0.362838E+11 | 0.00 | 4.75 |
February | 0.806844E+10 | 0.00 | 0.00 | 34406519.23 | 0.00 | 0.199675E+11 | 0.340798E+11 | 0.00 | 4.89 |
March | 0.308414E+10 | 0.00 | 0.00 | 57148828.82 | 0.00 | 0.00 | 0.490618E+11 | 0.00 | 5.13 |
April | 0.715131E+09 | 0.840937E+09 | 0.00 | 64939763.85 | 35105940.97 | 0.00 | 0.453470E+11 | 0.00 | 5.27 |
May | 0.183926E+09 | 0.127801E+10 | 0.00 | 74287345.48 | 40836514.18 | 0.00 | 0.421707E+11 | 0.00 | 5.35 |
June | 83739404.73 | 0.893270E+10 | 0.00 | 49996810.25 | 0.199006E+09 | 0.00 | 0.228315E+11 | 0.00 | 5.24 |
July | 22689731.04 | 0.152835E+11 | 0.00 | 34123650.69 | 0.323898E+09 | 0.00 | 0.108861E+11 | 0.00 | 5.12 |
August | 89796761.71 | 0.119374E+11 | 0.00 | 44467106.26 | 0.399518E+09 | 0.00 | 0.173401E+11 | 0.00 | 5.17 |
September | 0.284049E+09 | 0.127101E+10 | 0.00 | 63462529.04 | 49789701.71 | 0.00 | 0.368629E+11 | 0.00 | 5.25 |
October | 0.785885E+09 | 0.00 | 0.00 | 66985418.14 | 0.00 | 0.00 | 0.520961E+11 | 0.00 | 5.29 |
November | 0.744007E+10 | 0.00 | 0.00 | 49633486.43 | 0.00 | 0.174215E+10 | 0.459626E+11 | 0.00 | 5.06 |
December | 0.139711E+11 | 0.00 | 0.00 | 38051557.92 | 0.00 | 0.00 | 0.436102E+11 | 0.00 | 4.81 |
Annual Sum or Average | 0.608197E+11 | 0.395436E+11 | 0.00 | 0.604969E+09 | 0.104815E+10 | 0.339022E+11 | 0.436532E+12 | 0.00 | 5.11 |
Minimum of Months | 22689731.04 | 0.00 | 0.00 | 27466196.92 | 0.00 | 0.00 | 0.108861E+11 | 0.00 | 4.75 |
Maximum of Months | 0.260907E+11 | 0.152835E+11 | 0.00 | 74287345.48 | 0.399518E+09 | 0.199675E+11 | 0.520961E+11 | 0.00 | 5.35 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410240E+10 | 0.00 | 0.00 | 97810781.76 | 0.00 | 0.134367E+11 | 0.790017E+11 | 0.00 | 20.59 |
February | 0.313610E+10 | 0.00 | 0.00 | 89119795.05 | 0.00 | 0.170926E+11 | 0.588555E+11 | 0.00 | 21.20 |
March | 2704795.58 | 0.00 | 0.00 | 0.115394E+09 | 0.00 | 0.00 | 0.710468E+11 | 0.00 | 22.65 |
April | 0.00 | 0.130406E+10 | 0.00 | 0.108868E+09 | 0.00 | 0.00 | 0.600471E+11 | 0.00 | 22.53 |
May | 0.00 | 0.195752E+10 | 0.00 | 0.113751E+09 | 0.00 | 0.00 | 0.512974E+11 | 0.00 | 22.04 |
June | 0.00 | 0.125725E+11 | 0.00 | 70448773.57 | 0.00 | 0.00 | 0.267485E+11 | 0.00 | 21.29 |
July | 0.00 | 0.208026E+11 | 0.00 | 41060700.97 | 0.00 | 0.00 | 0.115365E+11 | 0.00 | 20.71 |
August | 0.00 | 0.168572E+11 | 0.00 | 58070945.99 | 0.00 | 0.00 | 0.185202E+11 | 0.00 | 20.79 |
September | 0.00 | 0.192690E+10 | 0.00 | 0.101180E+09 | 0.00 | 0.00 | 0.457891E+11 | 0.00 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.116775E+09 | 0.00 | 0.00 | 0.696028E+11 | 0.00 | 22.70 |
November | 0.283067E+09 | 0.00 | 0.00 | 0.107911E+09 | 0.00 | 0.222406E+10 | 0.712383E+11 | 0.00 | 22.09 |
December | 41080462.51 | 0.00 | 0.00 | 0.110595E+09 | 0.00 | 0.00 | 0.801069E+11 | 0.00 | 21.54 |
Annual Sum or Average | 0.756535E+10 | 0.554207E+11 | 0.00 | 0.113098E+10 | 0.00 | 0.327533E+11 | 0.643791E+12 | 0.00 | 21.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 41060700.97 | 0.00 | 0.00 | 0.115365E+11 | 0.00 | 20.59 |
Maximum of Months | 0.410240E+10 | 0.208026E+11 | 0.00 | 0.116775E+09 | 0.00 | 0.170926E+11 | 0.801069E+11 | 0.00 | 22.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:50:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181955E+11 | 0.00 | 0.00 | 0.97 |
February | 0.312298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125841E+11 | 0.00 | 0.00 | 0.97 |
March | 0.744996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504453E+10 | 0.00 | 0.00 | 0.98 |
April | 0.891752E+10 | 0.00 | 0.00 | 0.00 | 0.226455E+09 | 0.166116E+10 | 0.00 | 0.00 | 0.98 |
May | 0.941509E+10 | 0.00 | 0.00 | 0.00 | 0.339499E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 0.508316E+10 | 0.186294E+09 | 0.00 | 0.00 | 0.208641E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.249014E+10 | 0.132070E+09 | 0.00 | 0.00 | 0.370221E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
August | 0.386376E+10 | 70392270.96 | 0.00 | 0.00 | 0.300174E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 0.826523E+10 | 22714961.04 | 0.00 | 0.00 | 0.315376E+09 | 0.152860E+09 | 0.00 | 0.00 | 0.98 |
October | 0.115826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596717E+09 | 0.00 | 0.00 | 0.98 |
November | 0.699620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639356E+10 | 0.00 | 0.00 | 0.98 |
December | 0.197097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126187E+11 | 0.00 | 0.00 | 0.97 |